CLIENT

ARCHITECT
CONSULTANT
NAME OF THE PROJECT
LOCATION OF THE PROJECT

AREA TO BE AIR CONDITIONED

TOTAL HEIGHT
BOTTOM OF BEAM
FALSE CEILING HEIGHT

AREA
OCCUPANCY
LOAD OF COMPUTERS
EQUIPMENT LOAD
LIGHT LOAD

FLOOR ABOVE
FLOOR BELOW

OUTSIDE TEMP
INSIDE TEMP
RELATIVE HUMIDITY

AIR CHANGE / HOUR


CFM / PERSON

EXPOSED WALL
NORTH
SOUTH
EAST
WEST
NORTH EAST
SOUTH EAST
SOUTH WEST
NORTH WEST

EXPOSED GLASS
NORTH
SOUTH
EAST
WEST
NORTH EAST
SOUTH EAST
SOUTH WEST
NORTH WEST

PARTITION

TONNAGE

TOTAL CFM
TONNAGE AS PER CFM

EQUIPMENT SELECTED
REMARKS / COMMENTS
PROJECT/CLIENT:
APPLICATION :
AREA
Description Area U-factor TD Heat Load DESIGN CONDITIONS 16.00 HRS SUMMER
sft F BTU/H DB F WB F RH % ENTH GR/LB
INTERNAL SPACE SENSIBLE HEAT GAINS OUTSIDE 118 86 52 144
WALL N 0 0.34 9 - INSIDE 76 55 26 58
S 0 0.34 21 - DIFFERENCE 42 26 86
E 0 0.34 23 -
W 0 0.34 17 - OCCUPANCY 2 AREA (SFT) 2000
NE 0 0.34 10 - LIGHT LOAD(w/sft) 2 HEIGHT (FT) 15
SE 0 0.34 18 - EQPT. LOAD(W) 0
SW 0 0.34 14 -
NW 0 0.34 6 - VENTILATION CFM BF 0.15
GLASS N 0 0.56 28 - CFM/PERSON 7.5 15 CF 0.85
S 0 0.56 12 - ACH 1 500
E 0 0.56 12 - SELECTED CFM 500
W 0 0.56 163 -
NE 0 0.56 12 - REHEAT ( IF REQUIRED)
SE 0 0.56 12 - NEW SHF 0.88
SW 0 0.56 85 - NEW TOTAL SPACE HEAT 41400.67 BTU/H
NW 0 0.56 138 - NEW SPACE SENSIBLE HEAT 36432.59 BTU/H
GLASS TRANS: 0 1.13 42 - MINIMUM REHEAT REQUIRED 13396.39 BTU/H
PARTITION 0 0.4 37 - REHEAT 0 BTU/H
ROOF INSUL 0 0.1 72 -
ROOF EXPOSED 0 0.4 72 - SOLAR COEFFICIENTS WALL U-FACTOR
CEILING 0 0.3 37 - EAST 12 EAST 0.34
FLOOR 0 0.3 37 - WEST 163 WEST 0.34
VENTILATION 500 0.16 42 3,402.00 NORTH 28 NORTH 0.34
INFILTRATION - SOUTH 12 SOUTH 0.34
PEOPLE 2 245 490.00 NORTH EAST 12 NORTH EAST 0.34
LIGHTING LOAD 4000 1.25 3.41 17,050.00 NORTH WEST 138 NORTH WEST 0.34
EQUIP LOAD (W) 0 3.41 - SOUTH EAST 12 SOUTH EAST 0.34
MISCELLANEOUS - SOUTH WEST 85 SOUTH WEST 0.34
TOTAL 20,942.00 TRANSMISSION 1.13 PARTITION 0.4
DEDUCT FOR STORAGE EFFECT
SENSIBLE HEAT SUBTOTAL 20,942.00 ROOF 0.12 FLOOR 0.3
DUCT GAIN AND SAFETY 2,094.20 CEILING
TOTAL SPACE SENSIBLE HEAT 23,036.20
INTERNAL SPACE LATENT HEAT GAINS WALL TD
VENTILATION 500 0.1 86 4,321.50 EAST 23 NORTH EAST 10
INFILTRATION - WEST 17 NORTH WEST 6
PEOPLE 2 205 410.00 NORTH 9 SOUTH EAST 18
MISCELLANEOUS - SOUTH 21 SOUTH WEST 14
LATENT HEAT SUBTOTAL 4,731.50
SAFETY FACTOR % 236.58 ESTIMATED BY
TOTAL SPACE LATENT HEAT 4,968.08 DATE
TOTAL SPACE HEAT 28,004.28
VENTILATION AIR HEAT
SENSIBLE HEAT 500 0.92 42 19,278.00
LATENT HEAT 500 3.83 26 49,725.00
RETURN AIR GAIN @ 5% 1,400.21
GRAND TOTAL HEAT 98,407.49

SHF 0.82 REHEAT (W) 0


ADP 55 CFM REQUIRED 1195
DHA 1194.95 TONS 8.2