JAL International

Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 1

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2 1. GENERAL DATA & INFORMATION:
Make Model / Type Sr. No.

Designation Aux. Voltage Rated Voltage (Vn) Rated Current (In)

2. GENERAL INSPECTION & WIRING CHECK:


SR.NO. 1 2 3 4 ITEM DESCRIPTION Inspect for any physical damage or defects. Verify connections as per approved drawings. Check tightness of all the connections. Case Earthing verified REMARKS

3. ELECTRICAL TEST:
RELAY CHECKS: (WITH RELAY ENERGISED)

Sr. No. 1 2 3 4 5 6 7

Description Watchdog contacts (M11-M12 opened. M13-M14 Closed) Dated & time - Set Clock to local time - Time Maintained when aux. Supply removed Alarm (yellow) LED - to check make test Mode Enable under commissioning test meanu. Out of service (yellow) LED - to check make test Mode Enable under commissioning test meanu. Trip (red) LED - apply any fault to produce any trip condition All & programmable LEDs - apply test LED under commissioning test menu. Measured Field supply voltage Between terminals M7 and M9 = Between terminals M8 and M10 =

Tested By Name Sign

JAL INTL USMAN

Test Witnessed & Accepted By Name Sign

SEC-ERB

Date

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 2

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2


INPUT OPTO-ISOLATORS CHECKS: (WITH RELAY ENERGISED)

Opto Input No. Opto 1 Opto 2 Opto 3 Opto 4 Opto 5 Opto 6 Opto 7 Opto 8 Opto 9 Opto 10 Opto 11 Opto 12 Opto 13 Opto 14 Opto 15 Opto 16 Opto 17 Opto 18 Opto 19 Opto 20 Opto 21 Opto 22 Opto 23 Opto 24

Test Method (Energize only one at a time with 48V DC Voltage) Energize TB No. E2-E1 Energize TB No. E4-E3 Energize TB No. E6-E5 Energize TB No. E8-E7 Energize TB No. E10-E9 Energize TB No. E12-E11 Energize TB No. E14-E13 Energize TB No. E16-E15 Energize TB No. C2-C1 Energize TB No. C4-C3 Energize TB No. C6-C5 Energize TB No. C8-C7 Energize TB No. C10-C9 Energize TB No. C12-C11 Energize TB No. C14-C13 Energize TB No. C16-C15 Energize TB No. G2-G1 Energize TB No. G4-G3 Energize TB No. G6-G5 Energize TB No. G8-G7 Energize TB No. G10-G9 Energize TB No. G12-G11 Energize TB No. G14-G13 Energize TB No. G16-G15

Result Display 0 to 1

OUTPUT RELAYS CHECKS: (WITH RELAY ENERGISED)

Tested By Name Sign

JAL INTL USMAN

Test Witnessed & Accepted By Name Sign

SEC-ERB

Date

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 3

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2

Enter Commissioning Test, Test Mode, Contacts Blocked, Test pattern, and select relay no. make 1T1, Go to contact test; apply test, after checking remove test.

Output Relay No. RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8 RL9 RL10 RL11 RL12 RL13 RL14 RL15 RL16 RL17 RL18 RL19 RL20 RL21 RL22 RL23 RL24 RL25 RL26 RL27 RL28 RL29 RL30 Tested By Name Sign

Test Method (Energize only one relay at a time in 'Contract test' by' Apply test) Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated Contact Operated JAL INTL USMAN L1-L2 L3-L4 L5-L6 L7-L8 L9-L10 L11-L12 L13-L14-15 L16-L17-18 K1-K2 K3-K4 K5-K6 K7-K8 K9-K10 K11-K12 K13-K14-15 K16-K17-18 J1-J2 J3-J4 J5-J6 J7-J8 J9-J10 J11-J12 J13-J14-15 J16-J17-18 H1-H2 H3-H4 H5-H6 H7-H8 H9-H10 H11-H12 Test Witnessed & Accepted By Name Sign SEC-ERB

Result Contact Checked

Date

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 4

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2


RL31 RL32 Contact Operated Contact Operated H13-H14-15 H16-H17-18

ZONE REACHES CHEK

Zone

Type of Fault L1-N

Reach at 0 Degree Calc Act

Reach at 90 Degree Calc Act

Reach at 180Degree Calc Act

Reach at 270 Degree Calc Act

Zone1

L2-N L3-N L1-N

Zone2

L2-N L3-N L1-N

Zone3

L2-N L3-N

6.2 ZONE TIMING TEST

Type of Fault L1-N L2-N L3-N L1-L2 L2-L3 L3-L1 L1-L2-L3

Zone1 Set Time Act Time Set Time

Zone-2 Act Time

Zone-3 Set Time Act Time

FAULT LOCATOR

Distance: _______ kilometer,


Tested By Name Sign JAL INTL USMAN

Impedance: ________
Test Witnessed & Accepted By Name Sign SEC-ERB Date

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 5

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2


Fault impedance Value setting in test set X ( ) 25% 50% 75% 100% 25% 50% 100%

Type of Fault AN BN CN AB BC CA ABC

Calculated value of distance in Km.

Display at relay distance in km

MEASUREMENT ACCURACY CHECK

Current Inputs Check: CT Input IA IB IC IN IM Applied Value Displayed Secondary Value % Error CT Ratio Applied Displayed Primary Value % Error

Voltage Inputs Check: VT Input Tested By Name Sign Applied Value JAL INTL USMAN Displayed Secondary Value % Error VT Ratio Applied SEC-ERB Displayed Primary Value % Error Date

Test Witnessed & Accepted By Name Sign

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 6

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2


VA VB VC V C/S

SETTING CHECK (DIFFERENTIAL & BIAS FEATURE CHECK):


Ensure all the settings are applied.
BIAS CHARACTERISTIC TEST:

Lower Slope Check - Set the relay in Test Loop back mode - Set relay as 1st = 0.2A, k1=30% 1s2 = 2A - Set phase & E/F CT correction Factor = 1.00 Bias Current Phase Magnitude Phase Differential Current Expected Magnitude Actual Magnitude Pick-up Drop-Off

1pu=1A

0.25A +/-10%

1pu=1A

0.25A +/-10%

1pu=1A

0.25A +/-10%

Upper Slope Check : - Set the relay in loop back mode - Set relay as 1s1 = 0.2A, k1=30%, 1s2 = 2A, k2=as in table below

Tested By Name Sign

JAL INTL USMAN

Test Witnessed & Accepted By Name Sign

SEC-ERB

Date

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 7

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2


Bias Current Phase Magnitude Phase

Differential Current Expected Magnitude K2 Actual Magnitude Pick-up Drop-Off

3pu=3A

150% 100% K2

1.15A +/-20% 0.9A +/-20%

3pu=3A

150% 100% K2

1.15A +/-20% 0.9A +/-20%

3pu=3A

150% 100%

1.15A +/-20% 0.9A +/-20%

DIFFERENTIAL PICK-UP CHECK:

Setting = 200mA 2 - TERMINAL Phase Injected A B C Note: Idiff = k1 (1 bias) + 1s1, I bias = 1/2 (Ia + Ib) for 2-Terminal I diff & I bias are display values on the relay. Pick-up (mA) I diff I bias Injected Drop-Out (mA) I diff I bias

DIFFERENTIAL OPERATION & CONTACTS CHECK :

Note:

Inject only one current for this test to the phase under test. Injected Current JAL INTL USMAN Expected Trip Time Measured Trip Time SEC-ERB Contacts Operated Date

Phase Tested By Name Sign

Test Witnessed & Accepted By Name Sign

JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.

JAL International
Description : MICOM P546 LINE

INSPECTION AND TEST RECORD


DIFFERENTIAL & DISTNACE

Contract No. 30433118/00 Customer Ref: Panel/Feeder Ref.

Sheet no. 8

Customer SEC-ERB Site 230kV POWER SUPPLY TO HADEED -2


A B C 3A 3A 3A < 35ms < 35ms < 35ms

4. TEST EQUIPMENTS:
Sverker 760 Freja 300 Fluke 187 / 189

Tested By Name Sign

JAL INTL USMAN

Test Witnessed & Accepted By Name Sign

SEC-ERB

Date