Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:25PM
Page 1 of 4
TABLE 1:
SYSTEM DATA
Dry-Bulb Temp (F) 95.8 74.9 53.1 56.0 56.0 72.9 74.6 Specific Humidity (lb/lb) 0.02212 0.00805 0.00776 0.00776 0.00776 0.00785 0.00785 Sensible Heat (BTU/hr) 386 27880 3753 21596 2367 Latent Heat (BTU/hr) 1142 1660 510 -
Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Cold Supply Duct Zone Air Return Plenum
CO2 Level (ppm) 400 1080 1080 1080 1080 1089 1089
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft
TABLE 2:
ZONE DATA
Zone Sensible Load (BTU/hr) 21681 Zone T-stat Cond Mode (BTU/hr) Cooling 21596 Zone Temp (F) 72.9 Zone Airflow (CFM) 1318 CO2 Level (ppm) 1089 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0
Page 2 of 4
TABLE 1:
SYSTEM DATA
Dry-Bulb Temp (F) 59.0 0.0 0.0 0.0 0.0 79.9 Specific Humidity (lb/lb) 0.00588 0.00000 0.00000 0.00000 0.00000 0.00000 Airflow (CFM) 0 0 0 0 0 0 CO2 Level (ppm) 400 0 0 0 0 0 Sensible Heat (BTU/hr) 0 0 0 0 0 Latent Heat (BTU/hr) 0 0 0 -
Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Zone Air Return Plenum
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft
TABLE 2:
ZONE DATA
Zone Sensible Load (BTU/hr) -244 Zone T-stat Cond Mode (BTU/hr) Deadband 0 Zone Temp (F) 59.3 Zone Airflow (CFM) 0 CO2 Level (ppm) 0 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0
Page 3 of 4
Location: Bangalore, India Altitude: 3021.0 ft. Data for: October DESIGN COOLING DAY, 1600
1. Outdoor Air 2. Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Room Air 6. Return Plenum Outlet
0.024
1
5 2 6
30
40
50
60
70 80 Temperature ( F )
90