Division 15
June 26, 2009 (change #46 changes throughout)
DIVISION 15 PLUMBING ........................................................................................................ 3 15010 CYLINDER GAS MANIFOLDS ................................................................................... 3 15060 PIPE MATERIALS ...................................................................................................... 4 15060 FIRE PROTECTION PIPE AND FITTINGS ...............................................................19 15080 TRAPS AND STRAINERS .........................................................................................22 15080 FIRE PROTECTION VALVES ...................................................................................23 15100 SPECIAL VALVES ....................................................................................................24 15140 HOT WATER CIRCULATING PUMPS.......................................................................26 15170 THERMOMETERS AND PRESSURE GAUGES .......................................................27 15170 WATER METER ........................................................................................................28 15180 INSULATION .............................................................................................................29 15310 VACUUM SYSTEM ...................................................................................................31 15310 AIR COMPRESSORS (LABORATORY) ....................................................................34 15310 AIR DRYER ...............................................................................................................36 15310 COMPRESSED AIR FILTER .....................................................................................37 15405 DUPLEX SUMP PUMP VERTICAL PEDESTAL TYPE PUMPS ................................38 15405 DUPLEX SUMP PUMP SUBMERSIBLE TYPE PUMPS ............................................39 15405 DUPLEX SEWAGE EJECTOR - VERTICAL (PEDESTAL) PUMPS ..........................40 15405 DUPLEX SEWAGE EJECTOR - SUBMERSIBLE PUMPS ........................................41 15406 FLOOR, ROOF AND AREA DRAINS ........................................................................42 15423 CLEANOUTS.............................................................................................................43 15450 WALL HYDRANTS AND HOSE BIBBS .....................................................................44 15450 WATER HAMMER ARRESTORS ..............................................................................45 15450 PLUMBING FIXTURES & TRIM ................................................................................46 15450 LABORATORY TRIM FITTINGS ...............................................................................49 15730 STEAM-TO-WATER INSTANTANEOUS DUAL WATER HEATER ............................50 15XXX PURE WATER SYSTEM ...........................................................................................51
B.
Top of Document
MAXIMUM SERVICE OPERATING LIMITS SERVICE CODE (PSIG) DOMESTIC COLD WATER DOMESTIC HOT RETURN DOMESTIC HOT WATER NON-POTABLE WATER NATURAL GAS LABORATORY AIR NITROGEN LABORATORY VACUUM MEDICAL AIR CARBON DIOXIDE MEDICAL VACUUM VACUUM EXHAUST SANITARY WASTE & VENT STORM DRAIN FORCE MAIN LAB VENT LAB WASTE PURE WATER S&R PURE WATER S&R (ALTERNATE) CW HWR HW NPW G CA N2 VAC CA CO2 VAC VE S D FM LV LW PW PW 100 100 100 100 50 125 250 29" HG 125 125 29" HG 50 GRAVITY GRAVITY 50 GRAVITY GRAVITY 150 150 TEMP (F) 250 250 250 250 70 120 120 120 120 120 120 120 120 80 120 100 120 73 72 A10 A10 A10 A10 A11 A13 A14 A13 A14 A14 A15 A16 D10 D10 D11 D12 D12 P10 P11 COPPER COPPER COPPER COPPER C. STEEL COPPER COPPER COPPER COPPER COPPER COPPER G. STEEL CAST IRON CAST IRON G. STEEL POLYPROPYLENE POLYPROPYLENE LXT PVC POLYPROPYLENE CLASS PIPE MATERIAL
GENERAL PIPE SPEC NOTES: 1. EACH VALVE TYPE SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER. EACH SYSTEM SHALL BE PROVIDED WITH VALVES AS REQUIRED BY CODE AND SHOWN ON THE DWGS. AND SHALL BE INSTALLED TO FACILITATE OPERATION, REPLACEMENT AND REPAIR. 2. PROVIDE ACCESS PANELS FOR CONCEALED VALVES BEHIND NON-REMOVABLE CEILINGS OR WALLS. 3. PROVIDE SHUT-OFF VALVES ON SUPPLY PIPING TO INDIVIDUAL PIECES OF EQUIPMENT. 4. PROVIDE PIPE DOPE, TEFLON TAPE, WAX RINGS, NEOPRENE GASKETS AND OTHER JOINTING COMPOUNDS AS REQUIRED BY BEST STANDARD PRACTICE AND ONLY ON SERVICE AS RECOMMENDED BY MANUFACTURER. 5. APPLY PUTTIES AND JOINTING COMPOUNDS FOR PLUMBING FIXTURES AND TRIM AS RECOMMENDED BY MANUFACTURERS. 6. VALVES ON INSULATED PIPING SYSTEMS SHALL BE EQUIPPED WITH EXTENDED HANDLES TO ACCOMMODATE INSULATION THICKNESS. 7. PURE WATER S&R PIPING SYSTEM SHALL BE PIPE CLASS P10 HARVEL LXT PVC. POLYPROPYLENE PIPING SYSTEM PIPE CLASS P11 IS SUBJECT TO YALE UNIVERSITY APPROVAL.
Top of Document 4
4" AND LARGER COPPER, TYPE L TUBING ASTM B8872 SOLDER JOINT WROUGHT COPPER SOFT USE FLANGES OR SWEAT FITTINGS COPPER TO COPPER FLANGED JOINT.
FITTINGS
JOINTS
UNIONS
CAST BRONZE B62 2" AND SMALLER WITH CAST COPPER ALLOY NUT AND THD. ANSI B16.22. 3" ALL CAST COPPER ALLOY ANSI B16.18
VALVES GATE USE BALL VALVE 4" AND LARGER, 125# CLASS, IRON BODY, OS&Y BRONZE MOUNTED, FLANGED ENDS.LUNKENHEIMER 1430, MILWAUKEE F-2885-M, HAMMOND IR 1140.
SOLENOID VALVES
AUTOMATIC SWITCH CO. "FREE HANDLE" MANUAL RESET SHUTOFF VALVE ASCO 8211 SERIES. VALVE TO BE HEAVY DUTY SEALED UNIT WITH HIGHLY VISIBLE POSITION INDICATOR SHOWING VALVE POSITION. VALVE SHALL BE WIRED TO OPERATE AT (120 VOLT) AC POWER. 200 PSI WORKING PRESSURE, ALL BRONZE, BRONZE DISC, SOLDER ENDS LUNKENHEIMER 2145, HAMMOND IB912. 200 PSI WORKING PRESSURE, IRON BODY, BRONZE MOUNTED, FLANGED. LUNKENHEIMER 1790, HAMMOND IR1124.
CHECK
BALL
2 PIECE, ALL BRONZE, FULL PORT, STAINLESS STEEL USE GATE VALVE. BALL, PTFE SEATS SOLDER END, 600 PSI CW WORKING PRESS. APOLLO 77-200. (NO SUBSTITUTES) 2 PIECE, 600 WOG BRONZE BALL VALVE WITH THREAD X SOLDER END CONNECTIONS. APOLLO 70-100 WITH BRONZE PLUG. CAST BRONZE, ANSI B16.15
DRAIN VALVE
THREADED FITTINGS
NOTES:
WHEN COPPER COMES IN CONTACT WITH DISSIMILAR MATERIAL, PROVIDE DI-ELECTRIC COUPLINGS OR DIELECTRIC FLANGES. CONTACT BETWEEN FERROUS STUD BOLTS AND BRONZE FLANGES SHALL BE ELECTRICALLY INSULATED WITH NON METALLIC WASHERS. PROVIDE UNION CONNECTIONS TO ALL FIXTURES AND EQUIPMENT SUCH AS WATER HEATERS, AIR COMPRESSORS, PUMPS, ETC. BELOW GRADE WATER 4" AND LARGER TO BE DUCTILE IRON CEMENT LINED CLASS 52 WITH PUSH ON JOINTS. BELOW GRADE WATER 3" AND SMALLER TO BE TYPE K COPPER WITH BITUMINOUS COATING AND BRAZED JOINTS.
Top of Document
3" AND SMALLER SCHEDULE 40 CARBON STEEL ASTM A53 GRADE B, A106 GRADE A OR A120
4" AND LARGER SCHEDULE 40 CARBON STEEL ASTM A53 GRADE B, A106 GRADE A OR A120
FITTINGS
SCREWED MALLEABLE IRON 125 PSI. BLACK BUTT WELD CARBON STEEL NIPPLES, ALL EXTRA HEAVY. SCHEDULE 40, A 234 SCREWED 150# MALLEABLE IRON A105 GRADE II 150# RAISED FACE, SCREWED, A105 USE FLANGES
UNIONS
FLANGES
150# RAISED FACE WELD NECK A105 ASTM A181, GRADE I. 150# FLAT FACE FOR CAST IRON VALVE.
VALVES PLUG/GAS COCK USE BALL VALVE (SEE BELOW). IRON BODY, LUBRICATED TAPERED PLUG, FLANGED END, 175 WORKING PRESSURE. NORDSTROM 143, SERCK AUDCO LSW-133-GG.
BALL
BRONZE, SCREWED END, 600 PSI WORKING PRESSURE, TFE SEATS AND SEALS. APOLLO 81-100 SERIES. 150# CLASS, BRONZE SWING CHECK VALVE. SCREWED CAP, AND THREADED ENDS. 1/16" RED RUBBER, WIRE INSERTED. 150 RAISED FACE AND 125 FLATFACE GASKET.
CHECK
GASKETS
NOTES:
FOR LABORATORY GAS PIPING SYSTEMS, SUPPLY AN ECLIPSE, INC., SERIES 1000 POSITIVE SILENT CHECK VALVE ON THE PIPE BRANCH ENTRANCE TO EACH LAB. PROVIDE TWO WRENCHES FOR EACH GAS COCK SIZE. PROVIDE GAS VALVE CABINETS AND APOLLO BALL VALVE #80-100 SERIES AS INDICATED ON THE DRAWINGS.
Top of Document
2-1/2" AND LARGER COPPER, TYPE L TUBING ASTM B8872 SOLDER JOINT WROUGHT COPPER SOFT. SOLDER, SILVABRITE 100. USE FLANGES.
FITTINGS
JOINTS UNIONS
SOLDER, SILVABRITE 100. CAST BRONZE B62 2" AND SMALLER WITH CAST COPPER ALLOY NUT AND THD. ANSI B16.22. 3" ALL CAST COPPER ALLOY ANSI B16.18
VALVES CHECK 200 PSI WORKING PRESSURE, ALL BRONZE, BRONZE DISC, SOLDER ENDS FACTORY WASHED AND CAPPED. LUNKENHEIMER 2145, STOCKHAM B-309. 2 PIECE ALL BRONZE, FULL PORT, TEFLON SEAT, STAINLESS STEEL BALL, SOLDERED END, 400 PSI WP. APOLLO 77-200 (NO SUBSTITUTES). CAST BRONZE, ANSI B16.15 4" AND LARGER HORIZONTAL, FLANGED END, 200# WP, CAST IRON BODY, STAINLESS STEEL OR BRONZE TRIMMED. SAME AS 2" AND SMALLER
BALL
THREADED FITTINGS
NOTES:
WHEN COPPER COMES IN CONTACT WITH DISSIMILAR MATERIAL, PROVIDE DI-ELECTRIC COUPLINGS OR DIELECTRIC FLANGES. CONTACT BETWEEN FERROUS STUD BOLTS AND BRONZE FLANGES SHALL BE ELECTRICALLY INSULATED WITH NON-METALLIC WASHERS. PROVIDE UNION CONNECTIONS TO ALL PNEUMATICALLY OPERATED EQUIPMENT.
Top of Document
2" AND SMALLER COPPER, TYPE L TUBING ASTM B8872 FACTORY WASHED AND CAPPED.
2-1/2" AND LARGER COPPER, TYPE L TUBING ASTM B8872 FACTORY WASHED AND CAPPED. WROUGHT COPPER FACTORY CLEANED AND BAGGED. SILVER SOLDER OR COPPER BRAZE. USE NO FLUX INERT GAS PURGE DURING PROCESS. USE FLANGES. FACTORY WASHED AND CAPPED.
FITTINGS
WROUGHT COPPER FACTORY CLEANED AND BAGGED. SILVER SOLDER OR COPPER BRAZE. USE NO FLUX. INERT GAS PURGE DURING BRAZING PROCESS WITH NITROGEN OR ARGON. CAST BRONZE B62 2" AND SMALLER WITH CAST COPPER ALLOY NUT AND THD. ANSI B16.22. 3" ALL CAST COPPER ALLOY ANSI B16.18 FACTORY WASHED AND CAPPED.
JOINTS
UNIONS
VALVES CHECK 200 PSI WORKING PRESSURE, ALL BRONZE, BRONZE DISC, SOLDER ENDS FACTORY WASHED AND CAPPED. LUNKENHEIMER 2145, STOCKHAM B-309 4" AND LARGER HORIZONTAL, FLANGED END, 200# WP, CAST IRON BODY, STAINLESS STEEL OR BRONZE TRIMMED. FACTORY WASHED AND CAPPED. SAME AS 2" AND SMALLER, EXCEPT FOR REDUCED PORT DESIGN. 300 PSI WORKING PRESSURE. FACTORY DEGREASED, WASHED AND BAGGED. EACH VALVE SHALL BE EQUIPPED WITH LOCKABLE BRACKETS.
BALL
3 PIECE ALL BRONZE, FULL PORT, TEFLON SEAT, STAINLESS STEEL BALL, BRAZED END, 300 PSI WP. FACTORY DEGREASED, WASHED AND BAGGED. APOLLO 82-200 (NO SUBSTITUTES). EACH VALVE SHALL BE EQUIPPED WITH LOCKABLE BRACKETS.
THREADED FITTINGS
NOTES: ALL PIPE FITTINGS AND VALVES FOR THE ABOVE SPECIFIED SYSTEM IS TO BE CERTIFIED FACTORY CLEANED AND CAPPED/BAGGED FOR OXYGEN SERVICE. ZONE VALVES ON MEDICAL GASES ARE TO BE GROUPED AND HOUSED IN ZONE VALVE BOXES AT LOCATIONS SHOWN ON THE DRAWINGS. VALVES FOR ABOVE SERVICE ON 2 1/2" AND LARGER LINES ARE TO BE FLANGED CONNECTIONS. ZONE VALVE BOXES BEACON MEDAES, CHEMETRON OR EQUAL MODELS AS FOLLOWS: 1. 2. 3. SINGLE ZONE VALVE AND BOX ASSEMBLY BEACON MEDAES MODEL NO. 6-15010X-00. DOUBLE ZONE VALVE AND BOX ASSEMBLY BEACON MEDAES MODEL NO. 6-15020X-00. TRIPLE ZONE VALVE AND BOX ASSEMBLY BEACON MEDAES MODEL NO. 6-15030X-00.
PROVIDE SAFETY CHECK/SHUTOFF AT INLET PORT TO PRESSURE GAUGES FOR ALL PRESSURE SYSTEMS.
Top of Document
2-1/2" AND LARGER COPPER, TYPE L TUBING ASTM B8872 SOLDER JOINT WROUGHT COPPER SOFT Y PATTERN, PROVIDE CLEANOUTS SILVER SOLDER OR COPPER BRAZE. USE NO FLUX. INERT GAS PRGE DURING BRAZING PROCESS WITH NITROGEN OR ARGON. USE FLANGES.
FITTINGS
JOINTS
SILVER SOLDER OR COPPER BRAZE USE NO FLUX. INERT GAS PURGE DURING BRAZING PROCESS WITH NITROGEN OR ARGON.
UNIONS
CAST BRONZE B62 2" AND SMALLER WITH CAST COPPER ALLOY NUT AND THD. ANSI B16.22. 3" ALL CAST COPPER ALLOY ANSI B16.18
VALVES CHECK 200 PSI WORKING PRESSURE, ALL BRONZE, BRONZE DISC, SOLDER ENDS FACTORY WASHED AND CAPPED. LUNKENHEIMER 2145, HAMMOND IB912. 4" AND LARGER HORIZONTAL, FLANGED END, 200# WP, CAST IRON BODY, STAINLESS STEEL OR BRONZE TRIMMED. FACTORY WASHED AND CAPPED. SAME AS 2" AND SMALLER, EXCEPT FOR REDUCED PORT DESIGN. 300 PSI WORKING PRESSURE. EACH MEDICAL VACUUM VALVE SHALL BE EQUIPPED WITH LOCKABLE BRACKETS. FACTORY DEGREASED, WASHED AND BAGGED.
BALL
3 PIECE ALL BRONZE, FULL PORT, TEFLON SEAT, STAINLESS STEEL BALL, BRAZED END, 300 PSI WP. APOLLO 82-200 (NO SUBSTITUTES). EACH MEDICAL VACUUM VALVE SHALL BE EQUIPPED WITH LOCKABLE BRACKETS. FACTORY DEGREASED, WASHED AND BAGGED.
THREADED FITTINGS
NOTES: PROVIDE CLEANOUTS AT 50 FEET ON CENTER AND AT ALL DIRECTION CHANGES GREATER THAN 45 DEGREES. ZONE VALVE ON MEDICAL VACUUM IS TO BE HOUSED IN ZONE VALVE BOX AT LOCATION SHOWN ON THE DRAWING. ZONE VALVE BOXES SHALL BE MEDAES (OHMEDA), CHEMETRON OR APPROVED EQUAL.
Top of Document
3" AND SMALLER SCHEDULE 40 GALVANIZED STEEL. ASTM A53 GRADE B, A106 GRADE A OR A120. SCREWED MALLEABLE IRON 125 PSI GALVANIZED. SCREWED 150# MALLEABLE IRON A105 GRADE II, GALVANIZED. 150# RAISED FACE, SCREWED, A105 GALVANIZED
4" AND LARGER SCHEDULE 40 GALVANIZED STEEL. ASTM A53 GRADE B, A106 GRADE A OR A120 GROOVED MALLEABLE IRON 125 PSI GALVANIZED. USE FLANGES
FITTINGS
UNIONS
FLANGES
150# RAISED FACE GALVANIZED UNIFLANGE, ASTM A181, GRADE I. 150# FLAT FACE FOR CAST IRON VALVE.
GASKETS
1/16" RED RUBBER, WIRE INSERTED. 150 RAISED FACE AND 125 FLAT FACE GASKET.
VALVES GATE 2-1/2" & SMALLER, 125# CLASS, ALL BRONZE, RISING STEM, SOLID DISC, SOLDER ENDS SCREWED BONNET, SOLID DISC, SCREW ENDS LUNKENHEIMER 2125, STOCKHAM B-114. HORIZONTAL SWING, COMPOSITION DISC, ALL BRONZE, THREADED ENDS, 200 PSI WP. LUNKENHEIMER 2144, STOCKHAM B319. 3" AND LARGER, 125# CLASS, IRON BODY, OS&Y BRONZE MOUNTED, FLANGED ENDS. LUNKENHEIMER 1430, STOCKHAM G-623. OUTSIDE LEVER AND WEIGHT SWING SWING CHECK, FOR INSTALLATION AT NO MORE THAN 45 deg. FROM HORIZONTAL, FLANGED END, 200 PSI WP. STOCKHAM G931-L&W.
CHECK
Top of Document
10
ABOVE GRADE SERVICE WEIGHT CAST IRON NO-HUB PIPE CONFORMING TO CS 301, TYPE L COPPER TUBING. CAST IRON DRAINAGE PATTERN, WROUGHT COPPER DRAINAGE PATTERN, TO SUIT PIPE MATERIAL. HEAVY DUTY CISPI APPROVED STAINLESS STEEL NO-HUB COUPLING NEOPRENE GASKET. EQUAL TO HUSKY SD 4000 OR CLAMP-ALTORQUE 80 WITH 4 BAND STAINLESS STEEL CLAMPS. SILVABRITE 100 FOR COPPER JOINTS. CAST IRON GRAVITY FLOW TYPE, BRONZE MOUNTED, HUB END. EXTERIOR SHALL BE MASTIC COATED, BOLTED OR EXTENDED COVER IN ACCORDANCE WITH INSTALLATION PARAMETERS. J.R. SMITH CO. 7012 - 7022, JOSAM 67500, ZURN INDUSTRIES Z-1095.
BELOW GRADE SERVICE WEIGHT CAST IRON SOIL PIPE ASPHALT OR COAL TAR PITCH COATED. CAST IRON DRAINAGE PATTERN, TO SUIT PIPE MATERIAL. CAULKED WITH LEAD AND OAKUM. NEOPRENE GASKETS.
FITTINGS
JOINTS
BACKWATER VALVE
Top of Document
11
3" AND SMALLER SCHEDULE 40 GALVANIZED STEEL. ASTM A53 GRADE B, A106 GRADE A OR A120. SCREWED CAST IRON 125 PSI GALVANIZED SCREWED 150# MALLEABLE IRON A105 GRADE II, GALVANIZED. 150# RAISED FACE, SCREWED, A105 GALVANIZED.
4" AND LARGER SCHEDULE 40 GALVANIZED STEEL. ASTM A53 GRADE B, A106 GRADE A OR A120. GROOVED MALLEABLE IRON 125 PSI GALVANIZED USE FLANGES.
FITTINGS
UNIONS
FLANGES
150# RAISED FACE GALVANIZED UNIFLANGE, ASTM A181, GRADE I. 150# FLAT FACE FOR CAST IRON VALVE.
GASKETS
1/16" RED RUBBER, WIRE INSERTED. 150 RAISED FACE AND 125 FLAT FACE GASKET.
VALVES GATE 2-1/2" & SMALLER, 125# CLASS, ALL BRONZE, RISING STEM, SOLID DISC, SOLDER ENDS SCREWED BONNET, SOLID DISC, SCREW ENDS LUNKENHEIMER 2125, STOCKHAM B-114. HORIZONTAL SWING, COMPOSITION DISC, ALL BRONZE, THREADED ENDS, 200 PSI WP. LUNKEHEIMER 2144, STOCKHAM B319. 3" AND LARGER, 125# CLASS, IRON BODY, OS&Y BRONZE MOUNTED, FLANGED ENDS. LUNKENHEIMER 1430, STOCKHAM G-623. OUTSIDE LEVER AND WEIGHT SWING SWING CHECK, FOR INSTALLATION AT NO MORE THAN 45 deg. FROM HORIZONTAL, FLANGED END, 200 PSI WP. STOCKHAM G931-L&W.
CHECK
Top of Document
12
ABOVE GRADE SCHEDULE 40 POLYPROPYLENE PIPE (PPFR) FLAME RETARDANT MANUFACTURED TO MEET SCHEDULE 40 IRON PIPE SIZE DIMENSIONAL STANDARDS IN ACCORDANCE WITH ASTM D 2122, SECTION 4 & 7 ENFIELD INDUSTRIAL CORP. (NO SUBSTITUTIONS).
BELOW GRADE SCHEDULE 40 POLYPROPYLENE PIPE FLAME RETARDANT MANUFACTURED TO MEET SCHEDULE 40 IRON PIPE SIZE. ENFIELD INDUSTRIAL CORP. (NO SUBSTITUTIONS). DWV PATTERN SCHEDULE 40 FITTINGS BASED ON LAYING LENGTH DIMENSIONS IN ANSE B16-12 WALL THICKNESS SHALL CONFORM TO ASTM D 2122, SECTION 4. ENFIELD INDUSTRIAL CORP. (NO SUBSTITUTIONS)
FITTINGS
DWV PATTERN FLAME RETARDANT SCHEDULE 40 FITTINGS BASED ON LAYING LENGTH DIMENSIONS IN ANSI B16-12 WALL THICKNESS SHALL CONFORM TO ASTM D 2122, SECTION 4. ENFIELD INDUSTRIAL CORP. (NO SUBSTITUTIONS).
JOINTS
MECHANICAL JOINTS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. JOINTS MADE BETWEEN PP PIPE AND DISSIMILAR MATERIALS SHALL BE JOINED WITH PROPER ADAPTERS AND TRANSITION FITTINGS ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
NOTES: INTERIOR LAB WASTE AND VENT PIPING UNDER LAB BENCHES SHALL BE MADE WITH PPFR PIPE AND MECHANICAL JOINTS.
Top of Document
13
through 6
PIPING SHALL BE MANUFACTURED FROM A VIRGIN, SPECIALTY LOWEXTRACTABLE (LXT), POLYVINYL CHLORIDE (PVC) COMPOUND WITH A CELL CLASSIFICATION OF 12343 PER ASTM D1784. ALL PIPE SHALL BE PRODUCED TO SCHEDULE 80 DIMENSIONS, MANUFACTURED IN STRICT COMPLIANCE TO ASTM D1785. THE PIPE SHALL CARRY A TYPE II PRESSURE RATING, AND CONSISTENTLY MEET OR EXCEED THE APPLICABLE QUALITY ASSURANCE TEST REQUIREMENTS OF ASTM D1785 STANDARD WITH REGARD TO DIMENSIONS, WORKMANSHIP, BURST PRESSURE, FLATTENING RESISTANCE AND END-PRODUCT QUALITY. PIPE SHALL BE TRANSLUCENT BLUE IN COLOR, AND SHALL CONTAIN PERMANENT LASER MARKING THAT INCLUDES MATERIAL DESIGNATION (HARVEL LXT), PIPE SIZE, DIMENSIONS, AND THE EXACT DATE AND TIME OF MANUFACTURE FOR TRACEABILITY. ACCEPTABLE MANUFACTURERS HARVEL LXT BY HARVEL PLASTICS, INC. (NO EQUAL - NO SUBSTITUTIONS). FITTINGS SHALL BE MANUFACTURED FROM THE SAME VIRGIN, SPECIALTY LOW-EXTRACTABLE (HARVEL LXT) POLYVINYL CHLORIDE (PVC) COMPOUND WITH A CELL CLASSIFICATION OF 12343 PER ASTM D1784. ALL FITTINGS SHALL BE PRODUCED TO SCHEDULE 80 DIMENSIONS MANUFACTURED IN STRICT COMPLIANCE TO ASTM D2467. SOCKET STYLE FITTINGS SHALL HAVE TAPERED SOCKETS MANUFACTURED IN ACCORDANCE TO THE REQUIREMENTS OF ASTM D2467 TO CREATE AN INTERFERENCE TYPE FIT. THREADED FITTINGS SHALL BE MANUFACTURED IN ACCORDANCE WITH ASTM 1498 TO TAPERED PIPE THREAD DIMENSIONS. ALL FEMALE THREADED ADAPTERS SHALL BE STAINLESS STEEL REINFORCED. ALL FLANGES SHALL HAVE ANSI CLASS 150 BOLT PATTERNS, AND CARRY A MAXIMUM PRESSURE RATING OF 150 PSI, NON-SHOCK @73F. ALL FITTINGS SHALL BE LXT FITTINGS AS SUPPLIED BY HARVEL PLASTICS, INC. (NO EQUAL - NO SUBSTITUTIONS).
FITTINGS
Top of Document
14
CONNECTIONS TO VALVES, FAUCETS AND EQUIPMENT SHALL BE JOINED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS INCORPORATING VAN STONE STYLE FLANGES, UNIONS, AND/OR AT CONNECTIONS SPECIALTY STAINLESS STEEL REINFORCED FEMALE ADAPTERS WHERE TO VALVES, DISASSEMBLY MAY BE NECESSARY. ALL SOLVENT WELD FAUCETS AND CONNECTIONS ASSOCIATED WITH ANY OF THESE CONNECTIONS SHALL EQUIPMENT BE MADE-UP UTILIZING HARVEL LXT ONE-STEP SOLVENT CEMENT IN STRICT ACCORDANCE WITH THE MANUFACTURERS PUBLISHED RECOMMENDATIONS (SEE JOINTS BELOW). HARVEL LXT PIPING SHALL BE JOINED UTILIZING HARVEL LXT ONEJONITS STEP UPW GRADE SOLVENT CEMENT SPECIFICALLY FORMULATED FOR JOINING THIS MATERIAL. ALL SOLVENT WELDS SHALL BE MADE-UP IN FOR PIPING WITHIN STRICT ACCORDANCE WITH THE WRITTEN ASSEMBLY PROCEDURES WALLS AND ABOVE FOR THE PRODUCT AS STATED IN HARVEL LXT PRODUCT BULLETIN CEILINGS (HPB-114). INSTALLERS MUST BECOME FAMILIAR WITH THESE PROCEDURES PRIOR TO USE. THE USE OF SOLVENT CEMENTS AND/OR PRIMERS OTHER THAN HARVEL LXT ONE-STEP IS NOT ACCEPTABLE. JOINT INTEGRITY OF SOLVENT WELDED CONNECTIONS SHALL BE CONFIRMED WITH VISUAL INSPECTION UTILIZING A LIGHT SOURCE TO INSPECT THE SOLVENT WELDED SURFACES FOR UNIFORMITY. ALL SOLVENT WELDED CONNECTIONS MUST BE ALLOWED TO SET AND CURE PROPERLY PRIOR TO PRESSURE TESTING/RINSING PROCEDURES PER THE JOINT CURE SCHEDULES AS STATED IN HARVEL LXT PRODUCT BULLETIN (HPB-114). JOINTS TRUE UNION LXT BALL CHECK VALVES, SOCKET STYLE WITH VITON O RINGS. CHECK VALVES SIZES THROUGH 2 SHALL CARRY A MAX. CHECK PRESSURE RATING OF 235 PSI NON-SHOCK AT 73F, CHECK VALVES SIZES 3 THROUGH 4 SHALL CARRY A MAX. PRESSURE RATING OF 150 PSI NON-SHOCK AT 73F. ALL VALVE UNION NUTS SHALL INCORPORATE BUTTRESS STYLE THREADS. AS SUPPLIED BY HARVEL PLASTICS, INC. (NO EQUAL - NO SUBSTITUTIONS). TRUE UNION LXT TURN FULL PORT, TRUE UNION BALL VALVE WITH BALL PTFE SEAT AND VITON O RING. BALL VALVES SIZES THROUGH 2 SHALL CARRY A MAX. PRESSURE RATING OF 235 PSI NON-SHOCK AT 73F, BALL VALVES SIZES 3 THROUGH 4 SHALL CARRY A MAX. PRESSURE RATING OF 150 PSI NON-SHOCK AT 73F. ALL VALVE UNION NUTS SHALL INCORPORATE BUTTRESS STYLE THREADS. AS SUPPLIED BY HARVEL PLASTICS, INC. (NO EQUAL - NO SUBSTITUTIONS). MANUALLY OPERATED DIAPHRAGM VALVE TRUE UNION LXT DIAPHRAGM DIAPHRAGM VALVES, SOCKET STYLE, WEIR-TYPE DESIGN, EPDM BACKED PTFE DIAPHRAGM WITH EPDM O RING SEAL, AND BUILT-IN POSITION INDICATOR. TRUE UNION DIAPHRAGM VALVES SIZES 1/2 THROUGH 2 SHALL CARRY A MAX. PRESSURE RATING OF 150 PSI NONSHOCK AT 73F. AS SUPPLIED BY HARVEL PLASTICS, INC. (NO EQUAL NO SUBSTITUTIONS). POLYPROPYLENE FLANGED ENDS, ADJUSTMENT RANGE 5 50 PSI. PRESSURE SANITECT (NO SUBSTITUTIONS). REGULATING POLYPROPYLENE FLANGED ENDS, FLOW RATE RANGE 0 10 GPM. FLOW METERS SANITECT (NO SUBSTITUTIONS). VALVES Top of Document
15
POLYPROPYLENE FLANGED ENDS, VERTICAL PRESSURE GAUGE GUARD, PRESSURE RANGE 0 100 PSI. SANITECT (NO SUBSTITUTIONS).
INSTALLATION, INCLUDING ASSEMBLY, SUPPORT SPACING, COMPENSATION FOR EXPANSION AND CONTRACTION, AND JOINING SHALL BE IN COMPLIANCE WITH MANUFACTURERS RECOMMENDATIONS. JOINTING METHOD TO BE OUTLINED AND SUBMITTED WITH PIPE, FITTINGS AND VALVES SHOP DRAWINGS ALL PIPING SHALL BE STORED IN MANUFACTURERS ORIGINAL PACKAGING IN A CLEAN DRY AREA. THE PURE INTEGRITY OF PIPE, FITTINGS, AND VALVES SHALL NOT BE JEOPARDIZED.
Top of Document
16
2" AND SMALLER PURE UNPIGMENTED SCHEDULE 80 PIPE SHALL BE MANUFACTURED FROM A VIRGIN, UNPIGMENTED POLYPROPYLENE COMPOUND WHICH MEETS THE REQUIREMENTS OF ASTM D 2146 AND ASTM D4101. SANI-PRO T BY SANI-TECH (NO SUBSTITUTES).
2-1/2" AND LARGER PURE UNPIGMENTED SCHEDULE 80 PIPE SHALL BE MANUFACTURED FROM A VIRGIN, UNPIGMENTED POLYPROPYLENE COMPOUND WHICH MEETS THE REQUIREMENTS OF ASTM D 2146 AND ASTM D4101. SANI-PRO BY SANI-TECH (NO SUBSTITUTE).
PIPE
FITTINGS
FITTINGS SHALL BE SANI-PRO T WITH FLANGE FITTINGS SHALL BE SANI-PRO T WITH END CONNECTIONS FOR EXPOSED PIPING FLANGE END CONNECTIONS FOR AND BUTT FUSION FOR PIPING WITHIN WALLS. EXPOSED PIPING AND BUTT FUSION FOR PIPING WITHIN WALLS. SANI-PRO T FLANGE END WITH TRUE UNION CLAMP AND/OR STAINLESS STEEL V-BAND CLAMP METHOD SHALL BE JOINED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. CUSTOM FLANGING METHOD FOR SANI-PRO TUBING SHALL BE USED. FLANGE FORMING EQUIPMENT SUPPLIED BY THE MANUFACTURER AND IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. SANI-PRO T FLANGE END WITH TRUE UNION CLAMP AND/OR STAINLESS STEEL V-BAND CLAMP METHOD SHALL BE JOINED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. CUSTOM FLANGING METHOD FOR SANI-PRO TUBING SHALL BE USED. FLANGE FORMING EQUIPMENT SUPPLIED BY THE MANUFACTURER AND IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
JOINTS FOR ALL CONCEALED PIPING INCLUDING PIPING WITHIN WALLS AND ABOVE CEILINGS.
BUTT FUSION MEHTOD AND SHALL BE JOINED SAME AS 2" AND SMALLER. IN ACCORDANCE WITH ASTM D2657 USING FUSION JOINING EQUIPMENT SUPPLIED BY THE MANUFACTURER AND IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. INFRARED FUSION EQUIPMENT SHALL BE USED FOR BUTT FUSION. COIL FUSION INSERTS OR PRE-FAB COIL FUSION FITTINGS ARE NOT PERMITTED.
VALVES CHECK TRUE UNION WITH PP FLANGED ENDS, VITON "O" RING. SANI-TECH (NO SUBSTITUTES). TRUE UNION WITH PP END CONNECTIONS FLANGED, VITON "O" RING. SANI-TECH (NO SUBSTITUTES).
BALL
TRU-UNION PP, FLANGED ENDS, 1/4 TURN TRUE UNION BALL VALVE, FULL PORT, SELFLUBRICATION, FE SEAT VITON "O" RING. SANI-TECH (NO SUBSTITUTES).
FLANGE END CONNECTIONS, 1/4 TURN BALL VALVE, FULL PORT, SELFLUBRICATION, FE SEAT VITON "O" RING. SANI-TECH (NO SUBSTITUTES).
DIAPHRAM
MANUALLY OPERATED DIAPHRAM VALVE WITH FLANGED ENDS, PTFE DIAPHRAM FLOW IN EITHER DIRECTION, BRACKETING FACILITY IN VALVE AND POSITION INDICATOR. SANITECH (NO SUBSTITUTES). POLYPROPYLENE FLANGED ENDS, ADJUSTMENT RANGE 5 50 PSI. SANITECT (NO SUBSTITUTIONS).
MANUALLY OPERATED FLANGE END CONNECTIONS PTFE DIAPHRAM, POLYPROPYLENE BODY, FLOW IN EITHER DIRECTION, BRACKETING AND POSITION INDICATOR. SANI TECH (NO SUBSTITUTES) SAME AS 2 AND SMALLER
PRESSURE REGULATING
Top of Document
17
FLOW METERS
POLYPROPYLENE FLANGED ENDS, FLOW RATE RANGE 0 10 GPM. SANITECT (NO SUBSTITUTIONS). POLYPROPYLENE FLANGED END, VERTICAL PRESSURE GAUGE GUARD, PRESSURE RANGE 0 100 PSI. SANITECT (NO SUBSTITUTIONS). SAME AS 2 AND SMALLER
PRESSURE GAUGES
NOTES: 1. 2. 3. 4. 5. PIPE CLASS P11 FOR PURE WATER PIPING SYSTEM IS SUBJECT TO YALE UNIVERSITY APPROVAL. INSTALLATION, INCLUDING SUPPORT SPACING, COMPENSATION FOR EXPANSION AND CONTRACTION, AND JOINING SHALL BE IN COMPLIANCE WITH MANUFACTURERS RECOMMENDATIONS. JOINTING METHOD TO BE OUTLINED AND SUBMITTED WITH PIPE, FITTINGS AND VALVES SHOP DRAWINGS. ALL PIPING SHALL BE STORED WITH CAPS IN A CLEAN DRY AREA. THE PURE INTEGRITY OF PIPE FITTINGS, AND VALVES SHALL NOT BE JEOPARDIZED. ALL PIPING SHALL BE SUPPORTED WITH CONTINUOUS SUPPORT CHANNEL UNDER ALL HORIZONTAL PIPING RUNS. PIPING AND CHANNEL WILL BE SUPPORTED BY THE PIPING SUSPENSION SYSTEM.
Top of Document
18
General Material Notes: System components shall be rated for the maximum working pressure to which they are exposed but not less than 175 psig. 1. Pipe, tube valves and fittings shall meet or exceed ASTM/ANSI standards listed in the National Fire Codes and specifically in NFPA-13. All threaded piping and fittings shall conform to thread cuts listed in ANSI/ASME B1.20.1. Welding methods shall comply with all the requirements listed in American Welding Society document D10.9 levels AR-3.
2. 3.
Top of Document
19
2" and smaller Welded and seamless black steel pipe conforming to ASTM A53 Schedule 40.
3" and larger Welded and seamless black steel pipe conforming to ASTM A53 Schedule 40 or Schedule 10 ASTM-A135. Cast Iron Class 150 fittings ANSI/ASME B16.1 and screw fittings per ANSI/ASME B16.4. Mechanical grooved couplings with malleable iron housing clamps to engage and lock, "C" shaped composition sealing gasket, steel bolts, nuts and washers. Weld, roll groove, or thread. Apply joint compound or Teflon tape to male pipe threads on threaded systems. Welding procedures shall conform to the requirements of AWS D10.9, level AR3. Flanges shall be plain faced and shall be Cl 150 and shall conform to ANSI B16.5 Gaskets shall be full face rubber 1/8 in. thick. Bolts and nuts shall conform to ANSI B18.2.1 and B18.2.2 respectively.
Fittings
Cast Iron Class 150 fittings ANSI/ASME B16.1 and screw fittings per ANSI/ASME B16.4.
Joints
Threaded. Apply joint compound or Teflon tape to male pipe threads on threaded systems.
Flanges
Gaskets/Bolts
Notes: 1. Pipe material and fittings shall meet the standards set forth for pipe and tube in the National Fire Code NFPA 13, Section 2-3. Below grade fire water service 4" and larger shall be ductile iron cement line class 52 with push on joints. All grooved components including pipe couplings, fittings, grooving tools and lubricant shall be manufactured by Victaulic Company of America. No other manufacturers will be substituted.
2.
3.
Top of Document
20
2" and smaller Welded and seamless black steel pipe conforming to ASTM A53 Schedule 40. Galvanized to ASTM A795. Galvanized Cast Iron Class 150 fittings ANSI/ASME B16.1 and screw fittings per ANSI/ASME B16.4.
2-1/2" and larger Welded and seamless black steel pipe conforming to ASTM A53 Schedule 40 or Schedule 10. Galvanized to ASTM A795. Galvanized Cast Iron Class 150 fittings ANSI/ASME B16.1 and screw fittings per ANSI/ASME B16.4. Mechanical grooved couplings with malleable iron housing clamps to engage and lock, "C" shaped composition sealing gasket, steel bolts, nuts and washers. Roll groove, or thread. Apply joint compound or Teflon tape to male pipe threads on threaded systems. Flanges shall be plain faced and shall be Cl 150 and shall conform to ANSI B16.5. Gaskets shall be full face rubber 1/8 in. thick. Bolts and nuts shall conform to ANSI B18.2.1 and B18.2.2 respectively.
Fittings
Joints
Threaded. Apply joint compound or Teflon tape to male pipe threads on threaded systems.
Flanges
Gaskets/Bolts
Notes: 1. Pipe material and fittings shall meet the standards set forth for pipe and tube in the National Fire Code NFPA 13, Section 2-3. Holes drilled or cut into the piping system for fittings such as Mechanical tees, shall be regalvanized after the hole drilling process. Galvanic protection shall be re-applied after all cut groove processes. Rubber gaskets or rubber flange gaskets and couplings with rubber or neoprene gaskets are not allowed where ambient temperatures exceed 150 F unless listed for this service. All grooved components including pipe couplings, fittings, grooving tools and lubricant shall be manufactured by Victaulic Company of America. No other manufacturers will be substituted.
2.
3. 4.
5.
Top of Document
21
3.
Top of Document
22
C.
D.
E.
F.
Top of Document
23
B.
Pressure Reducing Valves on Water Services 1. PRV 1 1/2" and larger shall be pressure regulating, all bronze construction with separate strainer, threaded ends, inlet pressure up to 400 psi, adjustment range 25-75 psi: Leslie V223A 2. PRV 1" and smaller shall be pressure regulating, all-bronze construction with separate strainer, threaded ends 250 psi inlet pressure, adjustment range 25-75 psi with built-in bypass feature: Watts N223SB. 3. PRV 1" and smaller for high temperature applications shall be rated for 180F with integral strainers, 200 psi inlet pressure, 10-35 psi reduced pressure range, with thermal expansion bypass: Watts U5BLP. 4. Full flow range pressure reducing valves shall be equal to Watts control valve Model 115. Supply a strainer upstream of all PRV valves.
5. C.
Pressure and Temperature Relief Valves on Storage Type Water Heaters 1. Combination pressure and temperature (P&T) relief valves shall be automatic, ASME-rated, AGA- and CGA-certified, ANSI standard, bronze body. Pressure relieving setting shall be 150 psi; temperature relieving setting shall be 210F. Temperature relieving capacity shall be selected on AGA-CGA rating. Following model numbers are those of Watts Regulator Co.
2.
Top of Document
24
Heater Input 500,000 Btuh or less 500,001 - 700,000 Btuh 700,001 - 1,200,000 Btuh D.
Vacuum Relief Valves on Cold Water Inlet to Storage Type Water Heaters and Tanks 1. Relief valves shall be bronze body composition disc with 200 psi working pressure and 250 F temperature rating. Tanks larger than 500 gallons shall have multiple valves. Following model numbers are those of Watts Regulator Co. Tank Size - Gallons 500-999 1000-1999 2000-3000 Model 36A, 1/2" 2 required 3 required 5 required Model 36A, 3/4" 1 required 2 required 3 required
2.
E.
Backflow Preventers (BFP) 1. Provide reduced pressure backflow preventers with 175 psi working pressure, 140 F temperature rating, separate strainer and valves on inlet and outlet where indicated on the drawings. Provide Apollo ball valves and unions on both sides of the reduced pressure backflow preventers. Provide spare parts kit with full set of seals, washers, and special tools (if required). 2" and smaller BFP shall be all-bronze, threaded end, with ball valve shutoff tested and certified under AWWA-ASSE standards: Watts 909HW. 3. 2-1/2" and larger BFP shall be ductile epoxy coated body, bronze trim, flanged end, tested and certified under AWWA-ASSE standards: Watts 909. 4. For service temperatures greater than 140 F up to 210 F, supply stainless steel check modules. Atmosphere and pressure type vacuum beakers shall not be used as protection for connections to all type of non-potable water systems.
2.
5.
F.
Strainers
Top of Document
25
1.
2.
Strainers 2-1/2" and smaller shall be wye strainers, bronze body, stainless steel screens, 300 psi working pressure, threaded end with blow-off valved and piped to drain where possible, by Mueller (#351), or Spirax Sarco (BT). Strainers 3" and larger shall be wye strainers, iron body, stainless steel screens, 175 psi working pressure, flanged end with blow-off valved and piped to drain where possible, by Mueller (#751), Spirax Sarco (C1 125), Illinois and Nicholson
B.
Top of Document
26
1.
Gauges shall have white faces with black-filled engraved lettering. Gauge bodies shall be set in phenolic cases. Provide pulsation dampers and gauge cocks to isolate each gauge. Gauges shall be easily accessible and easily read. Gauges readable from floor at less than five feet shall have 4" dials. Other gauges shall have 6" dials. Gauges graduations shall meet limit requirements of normal operation. Gauges shall indicate at mid-scale. Provide pressure gauges at the inlet and outlet of each pump. Provide pressure gauges at each water entrance, downstream of the water meter, and on each side of PRV stations.
2.
3. 4.
B.
Provide separable well V-case thermometers by U.S. Gauge, Trerice, or Weksler where shown on Drawings and where specified. Thermometers shall have 9" scale and white face with black-filled engraved letters. Thermometers shall be angular or straight stemmed, as conditions necessitate. Thermometer wells shall be bronze and shall be installed so as to ensure minimum restriction of water flow in pipe and shall be installed to be able to be viewed from the floor. 1. Provide thermometer at the inlet and outlet of each water heater and where shown on Drawings. Thermometers shall have scale range of 30 - 240 F with 2 scale division. Provide thermometer in hot water return system at each hot water recirculation pump and where shown on drawings. Scale range shall be 30 - 240 F with 2 scale division.
2.
Top of Document
27
B.
C.
D. E.
F. G.
H.
Top of Document
28
15180 INSULATION
A. B. Insulation shall be by Owens-Corning, Certain-Teed or Manville. Insulation, jackets and adhesives shall be flame retardant and shall have ASTM E-84 fire hazard ratings of 25 flame spread, 50 smoke developed and 50 fuel contributed. 1. Interior applications: (Jackets) a. Type a: Vapor Barrier Jackets: Kraft reinforced foil vapor barrier with self-sealing adhesive joints. Jacket shall be heavy duty fire retardant material with glass fiber reinforcing and self-sealing lap. Jacket will be factory applied to the insulation. Jacket shall have neat, white Kraft finish or white vinyl suitable for painting, with bead puncture resistance of 50 units minimum. Vapor barrier shall be .001" aluminum foil adhered to the inner surface of the jacket. Permeance shall not exceed 0.02 perms. Jacket shall be Owens-Corning Fiberglass "ASJ-SSL" or Manville flamesafe "AP-T". Type b: PVC Jackets: One piece, pre-molded type.
b.
C.
Insulation and jacketing shall be in accordance with following: 1. Type A: Glass fiber insulation; ANSI/ASTM C547; "k" value of 0.24 at 75 degrees F noncombustible. Type B: Cellular glass; ANSI/ASTM C552; maximum water vapor transmission rating of 0.1 perms; "k" value of 0.40 at 75 degrees F. Type C: Expanded polystyrene; ANSI/ASTM C578; rigid closed cell; maximum water vapor transmission rating of 0.1 perms; "k" value of 0.23 at 75 degrees F. Type D: Expanded perlite; ASTM C610; maximum water vapor transmission rating of 0.1 perms; "k" value of 0.28 at 75 degrees F. Type E: Hydrous calcium silicate; ANSI/ASTM C533; rigid white; asbestos free; "k" value of 0.44 at 300 degrees F. Type F: Phenolic foam, chemically neutral; "k" value of 0.24 at 75 degrees F. Type G: Cellular foam; flexible, plastic; "k" value of 0.28 at 75 degrees F 0.04 at 24 degrees C.
2.
3.
4.
5.
6. 7.
D.
Schedule: The following piping systems require insulation: PIPING SYSTEM Domestic Hot Water Supply Domestic Hot Water Recirculating Tempered Domestic Water Supply Tempered Domestic Water Recirculating Domestic Cold Water TYPE A A A A A INSULATION THICKNESS INCH (mm) 1" 1" 1" 1" 1" JACKET TYPE a a a a a
Top of Document 29
Roof Drains & Horizontal Rainwater Chilled Drinking Water Supply Chilled Drinking Water Recirculation Non-Potable Water Cold Condensate Floor Drains and Horizontal Pipe Extensions Piping Exposed to Freezing (water) Piping Exposed to Freezing (Sanitary) Handicap Lav Hot Water and Waste
A A A A A A A A
Note 1: The electrical contractor will furnish and install heat trace tape, prior to insulation installation. Note 2: Insulation shall include drain sump body and all horizontal piping to, and including the elbow down to vertical. Note 3: Unless noted otherwise section "F" pertains to ALL piping in a specified system. E. Insulation of exterior piping and fittings shall be covered with 0.016" thick smooth aluminum jacket with longitudinal zee closures. Jacket shall be secured at both joints with 2" wide aluminum straps centered over butt joint of jacket. Provide 1/2" wide aluminum bands on 12" centers. Fitting covers shall be manufactured for purpose intended and shall be of same material. Pipe hangers shall be outside insulation and shall incorporate 12", 26 gauge protection shields. Insulation on piping that passes through walls or partitions shall pass continuously through sleeves, except at firewalls, smoke partitions, and floor penetrations where space between sleeves and piping shall be fire stopped with approved packing.
F.
Top of Document
30
B.
C.
Top of Document
31
32
Liquid Ring Laboratory Vacuum System (Duplex) Equipment Tag Description SHM-BLDG-LVP-1 Single-stage, continuous duty, direct driven conical liquid-ring vacuum pump with recirculated water seals. Packaged and mounted on structural frame. Factory preassembled, pre-wired and tested for single point field connections. Vacuum Level: 24"Hg (160 Torr). Capable of passing fluids and soft debris without damage to pumps. Two (2) units with pipe headers and controls for a duplex lead/lag1/ operation with automatic alteration of units for even operating hours between the units. Arranged in skid mounted configuration. Rotor: Bronze. Casing: Cast iron. Packaged control panel in NEMA 12 enclosure with: combination circuit breaker magnetic across-the-line motor starters; thermal, magnetic and short circuit protection; low voltage control transformer with fused secondary; hour meters; pump run lights; power on lights; HOA switches; dual set-point vacuum switches; main disconnect. Vacuum gauge and backpressure gauge on each pump. Vacuum transducer on receiver to control pump operation. Pumps shall operate in a lead/lag cascading sequence with daily rotation of lead pump. Pump minimum run timers shall ensure motors do not exceed NEMA recommended maximum starts per hour. Alarm circuit with dry contacts for customer remote alarm. ODP electric motor. 1.15 service factor. Direct drive coupling. 1750 rpm max synchronous speed. Flexible braided stainless steel connectors. Each pump shall include inlet check and isolation ball valve, water flow control valve, shock-arrestor solenoid valve, strainer, water supply isolation valve, and discharge separator/silencer. Water supply anti-siphon device. Vibration isolators. Closed loop seal water. Maximum GPM water usage when one pump is operating. Carbon steel counter-flow shell and tube heat exchanger. Sized by vendor. 120 Gallons. Galvanized steel. ASME Boiler and Pressure Vessel Code Section VIII rated and stamped. Vacuum/pressure safety element, bypass piping and valving, manual drain valve and vacuum indicator. 460 VAC, 3, 60 Hz, single point of field connection. Vacuum setting at Receiver Vacuum level at delivery inlet (approx.) 20 Hg System capacity 150 ACFM at 24" Hg Pump split 1/2 each 75 ACFM each at 24 Hg Pump horsepower 3/3 Pump model number (Nash) MHC-130 Equipment cost shall include start-up service by factory-authorized technician and twelve (12) month minimum warranty agreement for materials and workmanship. Beacon Medaes Duplex Camel Vacuum System LPV or LVS. Elmo Rietschle Liquid Ring Packages L Series. Dedicated exhaust through Penthouse roof.
D.
All equipment and components supplied by the pump manufacturer shall be warranted for a period of two (2) years from date of start-up.
Top of Document 33
B.
C.
DUPLEX AIR COMPRESSOR Equipment Tag SHM-BLDG-LAC-1 Number Required Mounting Condition Arrangement Type Motor Inlet Filter/Silencer Materials of Construction Controls One with pipe headers and controls. Two self contained compressor package mounted on an ASME air receiver tank. Single-Stage Oil-less reciprocating NEMA frame ODP motor, V-belt drive with total belt guard and belt tension adjustment. Provide inlet filter/silencer for each machine with 10 micron replaceable element. Oil-less crankcase with teflon rings for oil free delivery. NEMA 12 control cabinet with: NEMA 1 alternator, magnetic starters, thermal overload relays, on/off switches, hour meters, fused disconnects with door interlocks, 120 V control voltage transformer, reset buttons, UL and CSA approved 460 V/3 /60 Hz single point 120 gallon ASME rated, electronic tank drain, pressure gauges, isolator pads, ASME relief valve, air outlet service valve, piping between the air compressors and receiver shall include: In-line check, valve spec per A-13 Flexible connectors. NEMA 1 unloading pressure switch Free air unloader 15F CTD air cooled after cooled with cooling fan NEMA 1 high temperature air safety shutdown feature 2 years Air Cooled Package See Drawing Schedule Single point electrical and piping connections Quincy Model No. QRD-S Duplex
Electrical Receiver
Start Up and Warranty Cooling Media Rated Duty Other Acceptable Manufacturers
Top of Document
34
DUPLEX AIR COMPRESSOR Equipment Tag SHM-BLDG-LAC-1 Number Required Mounting Condition Arrangement Type Motor Inlet Filter/Silencer Materials of Construction Controls Electrical Receiver One Two self contained compressor package. Oil-free rotary scroll with full feature. High efficiency TEFC motor with Class F insulation. Provide inlet filter/silencer for each machine with 10 micron replaceable element. Oil-less crankcase with interaction of a fixed and an orbiting scroll for oil free delivery. Elektronicon D controller and variable flow technology 460 V/3 /60 Hz single point 120 gallon ASME rated, electronic tank drain, pressure gauges, isolator pads, ASME relief valve, air outlet service valve, piping between the air compressors and receiver shall included. In-line check, valve spec per A-13 Flexible connectors. NEMA 1 unloading pressure switch Free air unloader 15F CTD air cooled aftercooled with cooling fan NEMA 1 high temperature air safety shutdown feature 2 years Air Cooled Package See Drawing Schedule Single point electrical and piping connections Atlas Copco Model No. SF multicore series with integrated refrigerated air dryer.
Start Up and Warranty Cooling Media Rated Duty Other Acceptable Manufacturers D.
All equipment and components supplied by the pump manufacturer shall be warranted for a period of two years from date of start-up.
Top of Document
35
B.
C.
Top of Document 36
Top of Document
37
B.
C. D.
E. F.
Top of Document
38
B.
C. D.
E. F.
Top of Document
39
2.
3.
4.
5.
C.
Provide weighted horizontal swing check valve in pump discharge and gate valve downstream of each check valve. Valves shall meet requirements of valve paragraph of this section.
Top of Document
40
B.
C. D.
E. F.
G.
Top of Document
41
FD-B
FD-C
Kitchen
FD-D
Kitchen
FD-E
FD-F
Holding Room
RD-1
Roof
RD-2
Roof
AD-1
Area Way
PD-1
Planting Area
SD-1
Roof
42
15423 CLEANOUTS
A. Provide cleanouts in soil, waste and storm drainage piping on straight runs at changes in directions and at foot of stacks and other points where required by inspecting authorities. Cleanouts shall suit construction in which they are to be installed. Maximum horizontal distance on straight runs between cleanouts in piping 4" and smaller shall be 50 feet. In piping 5" and larger, maximum horizontal distance between cleanouts shall be 100 feet. Cleanouts shall be same size as pipe 4" and smaller. Cleanouts for piping larger than 4" shall be not less than 4" in diameter. No reduction in cleanout sizes for pipe 4" and smaller is permitted. Bodies of cleanout ferrules in bell and spigot piping shall be standard pipe sizes conforming in thickness to that required for pipe and fittings, and shall extend not less than 3/4" above hub of pipe. 1. Cleanout plug shall be cast brass with raised nut 3/4" high. 2. Cleanouts in copper waste piping shall be soldered brass cleanout fittings with extra heavy brass screw plugs of same size as line. 3. Cleanouts in threaded waste piping shall be cast iron, drainage T pattern, 90 degree branch fitting with extra heavy brass screw plugs of same size as pipe. 4. Floor cleanouts in finished areas shall be cast iron body and frame with round adjustable scoriated secured nickel bronze top, J. R. Smith No. 4020 or approved equal. 5. Floor cleanouts in unfinished areas shall be cast iron body and frame with round adjustable scoriated secured cast iron top, J. R. Smith No. 4220 or approved equal. 6. Cleanouts on vertical stacks at each floor shall be Dandy Cleanout. 7. Cleanout plugs shall be sealed with Teflon tape
B.
C.
D.
Top of Document
43
C.
Top of Document
44
B.
C.
D.
Top of Document 45
WC-1A L-1
L-1A
H.C. Toilets
L-2
L-2A
H.C. Toilets
UR-1
Men's Rm.
Top of Document
46
UR-1A LS-1
Urinal Same as U-1 except mount at handicap height. Laboratory sink (stainless steel) Elkay Model MDLR-XXXX; Just Model SLXD-316-XXXX Type 316 stainless steel, 18 gauge, self rimming, 12" deep sink with LK-372 316 stainless steel perforated grid strainer and 1 1/2" O.D. 316 ST. ST. tailpiece. T&S brass Model BL-5700-9 double ledge mixing faucet with BL-5500-1 wrist action handles, rigid/swing convertible gooseneck spout, integral vacuum breaker, chrome plated finish and T&S brass Model BL-5550-0-1F15 1.4 GPM non-splash aerator. Hydro Service and Supplies Picotap Model 04313 RO/DI pure water faucet with meter valve and vacuum breaker and MPT inlet. Pair supplies and angle stops Enfield 1 1/2" polypropylene "P" trap Sink Elkay MLR2522 316 stainless steel sink with 4 faucet holes Delta No. 450-WF single handle kitchen faucet with swing spout and spray attachment and Delta No. RP19754 1.5 GPM aerator. Elkay No. LK-18B stainless steel perforated grid drain outlet assembly Supplies and angle stops Cast brass P-trap Mop Service Basin Fiat MSB-36x24x10 with shelf or 24x24x10 without shelf T&S Brass No. B-665-BSTR faucet Mop Hanger Fiat No. 889-CC Hose and Hose Bracket. Fiat No. 832-AA Vinyl bumper guard. Fiat No. E-77-AA. Provide check valve on hot and cold water supplies to mop sink faucet. Provide cold water hose bibb T&S Brass No. B-720-POL and reduced pressure backflow preventer Watts No. 909 for cleaning solution system. Service Sink (slop sink) American Standard 7692.049 Lakewell service sink. T&S Brass No. B-674-BSTR service sink faucet American Standard 7798.176 trap standard with strainer. Provide check valve on hot and cold water supplies to service sink faucet. Provide cold water hose bibb T&S Brass No. B-720-POL and reduced pressure backflow preventer Watts No. 909 for cleaning solution system. Electric Water Cooler (barrier-free) Halsey Taylor HAC8FS-Q Self closing, front and side push bar actuators Stainless steel finish Supply stop Brass "P" trap with cleanout Water Cooler High Low Halsey Taylor OVLII Series Q Recessed with integral chiller Stainless steel finish
SK-1
Kichen/Lounge
MSB-1
Janitor's Closet
SS-1
Janitor's Closet
EWC-1
As shown
EWC-2
As Shown
Top of Document
47
EWC-3
Water Cooler Single barrier free Halsey Taylor OVL-ER-Q Recessed with integral chiller Stainless steel finish Emergency Shower / Eyewash Supply an emergency shower / eyewash assembly where indicated on the drawings Guardian Model GBF-2150 or GBF-2160(barrier free) Recessed stainless steel cabinet Emergency Shower, Supply an emergency shower where indicated on the drawings Guardian Model G-1672SSH (barrier free) Recessed stainless steel cabinet Emergency Shower / Eyewash Supply an emergency shower / eyewash assembly where indicated on the drawings Guardian Model G21-SL701 (barrier free) Recessed stainless steel cabinet with valve slot cover. Emergency Eyewash/Drench Hose Unit with Vacuum Breaker Deck Mounted Speakman Model No. SE-927-VB Install separate ball valve shut-off under sink. Shower Symmons Model No. S-25-1-131 shower assembly modified with Symmons Model No. 4-228 2.0 gpm flow rate Clear-Flo shower head. Fiat Model MFT3636 Base. Handicap Shower Symmons SafetyMix Visu-Temp Model No. 1-117VT-FS-XB30 shower unit modified with Symmons Model No. 4-228 2.0 gpm flow rate Clear-Flo shower head and Symmons Model No. EF-100 Euro-Flo wall/hand shower wand with 2.0 gpm flow restrictor. Fiat Model WTR-5000 Base.
As Shown
ES-1
Laboratory
ES-2
Toilets
ES-3
Vivarium
EW-1
Laboratory
SH-1
Bathroom
SH-1A
H.C. Bathroom
Top of Document
48
Standard Laboratory Island Bench Standard Laboratory Island Bench Standard Laboratory Wall Bench
T-3
T-4
Standard Laboratory Wall Bench Standard Laboratory Wall Bench Standard Laboratory Equipment Room Standard Laboratory Equipment Room Standard Laboratory Equipment Room Laboratory
T-6
T-7
T-9
T-X
Specialty Gas Outlets (O2, N2, N2O, AR, CO2, Mixed Gases) T&S Brass BL-4260-1 wall mounted panel flange with needle hose cock and BL-5500-7 supply nipple and locknut.
T-X
Specialty Gas Outlets (O2, N2, N2O, AR, CO2, Mixed Gases) T&S Brass BL-4260-2 wall mounted panel flange with two needle hose cocks at 90 deg F apart and BL-5500-7 supply nipple and locknut.
Laboratory
Top of Document 49
B.
C. D.
Top of Document
50
15XXX
A.
B.
Top of Document 51