TECHNICAL SPECIFICATIONS
A. GENERAL CHARACTERISTICS Design standars Transformer type Service Condition Type of oil Number of phase Frequency B. TECHNICAL SPECIFICATION Capacity Primary Voltage Secondary Voltage Vector Group Cooling Temperature Rise - Oil - Winding No load losses at nominal voltage On load losses at principal tapping Impedance voltage Off load current at nominal voltage Temperature Insulation Class Noise Tapping value C. INSULATION CLASS OF THE WINDINGS Highest system voltage (kV) Impulse test voltage (kV) Applied test voltage (kV) D. EFFICIENCY AND VOLTAGE REGULATION Efficiency ( % ) 4/4 load Pf 0.8 Pf 1.0 98.18 98.54 3/4 load 98.50 98.80 2/4 load 98.75 99.00 1/4 load 98.71 98.97 : : : : : : : : Voltage Regulation in Volt 384 394 1,720 1,050 1,845 575 955 2,550 mm mm mm kg kg kg in % 3.98 1.42 : : : : : : : : : : : : : : : : : : : : : : : IEC 76 Hermetically Sealed Totally Oil Filled Indoor Mineral Oil Class 1 acc. to IEC 296 Phase 3 Hz 50 1000 kVA 20 kV 0.4 kV Dyn5 ONAN 60 oC 65 oC 1800 Watts 13000 Watts 5 % 1.8 % A dB 56 +/-2.5%;+/-5% Primary 24 125 50 Secondary 1.1 0 3

E. APPROXIMATE WEIGHTS AND DIMENSION Total length Total width Total height Weight of oil Weight of core and winding Total weight Approximate Drawing No. Painting Colour

Light Grey RAL 7032

The above dimensions and masses are approximate and provided to give a general description of our proposed transformer.
Revision Date Est. Chk App. Original 22-Jan-10 SGT

Client / Project:
No : D 8086 1/2 Page :

Jakarta - Indonesia

TECHNICAL SPECIFICATIONS
F. ACCESSORIES - Name Plate and Rating Plate - HV Plug in Bushings and LV Porcelain Bushings - Off Circuit Tap Changer - Oil Filling Plug - Oil Draining Valve - Lifting Lugs - Grounding Terminal - Bidirectional Rollers - Pressure Relief Device Without Contact - Protection Relay RIS - Fins Type Radiator

G. DEVIATIONS / EXCEPTIONS - None

H. NOTES - None

I. LIST OF TEST Routine Test : - Measurement of the resistance value and checking of polarities - Measurement of the ratio on all taps - No load test for measurement of the no load loss and no load current - Short circuit test for determination of the on load loss and impedance - Applied voltage test - Induced voltage test Type test : - Temperature rise test - Full wave impuls test ( 1.2 / 50 us )

Yes : : : : : : : :

No

Tests other than the above mentioned list needs further confirmation
Revision Date Est. Chk App. Original 22-Jan-10 SGT

Client / Project:
No : D 8086 2/2 Page :