Vous êtes sur la page 1sur 1

PROJECT: PNUW HVAC Package -3

UNIT.NO. : AHU-FA-7.13.0-RF-01

SITE :
RIYADH
BUILDING :
ROOF
Drwg.# P3-ESC-7.13.0-SH-ME-0008

GENERAL DATA
DUCT MATERIAL

G. I. Sheet

ROUGHNESS COEF.

0.93

ALTITUDE

611

Meters

ALTITUDE COEF.

:
:

0.935
1.09

Kg/m3

AIR DENSITY

DUCTS PRESSURE LOSSES TABLE


SECTION
FLOW
FLOW
LENGTH
DIAM.
DIAM. EQUIV.
WIDTH
HEIGHT
AREA
VELOCITY

CFM
M3/H
M
mm

3
9735
16549.5
2.75
1004.00
1004.00
1000
850
10.16
5.80
0.32
0.88

4
9735
16549.5
6.20
1004.00
1004.00
1000
850
22.94
5.80
0.32
1.99

5
5037
8562.9
2.34
756.00
756.00
800
600
6.55
5.30
0.38
0.90

6
5037
8562.9
0.85
756.00
756.00
800
600
2.38
5.30
0.38
0.33

7
5037
8562.9
3.43
756.00
756.00
800
600
9.60
5.30
0.38
1.32

8
5037
8562.9
2.41
756.00
756.00
800
600
6.73
5.30
0.38
0.92

9
5037
8563
0.50
756.00
756.00
800
600
1.40
5.30
0.38
0.19

10
5037
8563
3.65
756.00
756.00
800
600
10.21
5.30
0.38
1.40

11
1382
2349
1.70
456.00
456.00
500
350
2.89
4.00
0.43
0.72

12

10

11

12

ELBOW 30
ELBOW 45
ELBOW 90
TEE 45
TEE 90
END TEE
BRANCH TEE
TRANSITION
CONTRACTION
WIRE MESH

Co
0.07
0.71
0.23
0.3
1
1.5
0.05
0.22
0.05
0.04
Co
Pa
Pa

0.00
0.00
0.15

TOTAL
DUCTS PD
PRESSURE DROP

External Static Pressure for Supply


2
9735
16549.5
1.51
1004.00
1004.00
1000
850
5.59
5.80
0.32
0.48

PD x LENGTH

27-11-10

Rev.4
By: K.IMRANUDDIN

1
18985
32274.5
1.00
1511.00
1511.00
2540
815
6.71
5.00
0.15
0.15

mm
mm
M2
M/S
Pa
Pa

PD per Meter

Date :
Revision :

13

14

15

16

17

18

19

20

21

TOTAL

26.3 ml

9.28 Pa
13

14

15

16

17

18

19

20

21

TOTAL

0.00
0.00
0.48

1.42
26.04
26.92

0.00
0.00
1.99

0.00
0.00
0.90

1.42
21.72
22.05

0.00
0.00
1.32

1.42
21.72
22.65

1.42
21.72
21.91

0.00
0.00
1.40

0.46
4.01
4.73

SPECIAL FITTING PRESSURE DROPS


DESIGNATION
FIRE DAMPER
VOLUME DAMPER
SUPPLY GRILLE
RETURN GRILLE
FRESH AIR LOUVER
SAND TRAP LOUVER
ALUMINUM FILTER
BAG FILTER
GREASE FILTER
DUCT HEATER
DISC EXHAUST VALVE
FLEXIBLE DUCT CONNECTION
SOUND ATTENUATOR
TOTAL

Calculated External Static Pressure is 139 Pa.


MAR ESP Calculation is 547 Pa.

6.14
95.22 Pa
104.50 Pa
0.56

PD (PA)

QTY

TOTAL

10
10
15
10
20
100
80
150
100
5
70
15
75

0
2
0
0
0
0
0
0
0
0
0
1
0

0
20
0
0
0
0
0
0
0
0
0
15
0
35 Pa

W.g

STATIC PRESSURE AT 100%


FLOW AT 100%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

139 Pa
32275 m/h
104 Pa
35 Pa

STATIC PRESSURE AT 110%


FLOW AT 110%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

0.62
W.g
153 Pa
35502 m/h
115 Pa
39 Pa

STATIC PRESSURE AT 120%


FLOW AT 120%
* DUCTS PRESSURE DROP :
* FITTING PRESSURE DROP :

0.67
W.g
167 Pa
39052 m/h
125 Pa
42 Pa

Vous aimerez peut-être aussi