Vous êtes sur la page 1sur 11

Lab 3b: Cooling Tower Performance and Sensors for Thermal-Fluid Systems Introduction The Bench Top Water

Cooling Tower has been designed to give students an appreciation of the construction, design and operational characteristics of a modern evaporative cooling system. The unit is also an excellent example of an 'open system' through which two streams of fluid flow (water and air) and in which there is a mass transfer from one stream to the other. Convincing energy and mass balances are obtained and students can quickly investigate the effects of air flow rate, water flow rate, water temperature and cooling loads on the performance of a cooling tower. You will measure the performance of the cooling tower, and determine the errors of your sensors and uncertainties of your measurements.

Cooling Tower Schematic

Lab 3b: Bench Top Cooling Tower


Background The Bench Top Water Cooling Tower has been designed to give students an appreciation of the construction, design and operational characteristics of a modern evaporative cooling system. A cooling tower is a common method of removing heat from a thermodynamic cycles working fluid (such as water) and rejecting it to the atmosphere. The unit is also an excellent example of an 'open system' through which two streams of fluid flow (water and air) and in which there is mass transfer from one stream to the other. Using the unit, student can explore energy and mass balances for the system, and investigate the effects of air flow rate, water flow rate, water temperature and cooling loads on the performance of a cooling tower Much of the University of Iowas air conditioning capability is produced using chilled water, and an important component in this production is cooling towers. Objective To become familiar with the P.A. Hilton H891 Bench Top Cooling Tower and its operating principles. Check the accuracy of the temperature sensors (thermocouples) in the cooling tower. Students will measure wet and dry bulb temperatures, apply psychrometric principles to determine relative humidity, and measure humidity using Equipment P.A. Hilton H891 Bench Top Cooling Tower Data acquisition system for measuring thermocouples (type-K), turbine flow meter and pressure transducer Temperature calibration equipment thermistor temperature standard, and constant temperature thermo-cell Power supply for turbine flow meter and pressure transducer set to 8.22 VDC Handheld temperature-relative humidity probe Sling psychrometer Pre-Lab Questions What is difference between dry bulb temperature and wet bulb temperature? Operating Principle Familiarize yourself with the Bench Top Cooling Tower System, noting the locations of the 6 temperature readings to be taken when using the system:

1. The hot water enters the top of the tower (note T5 in system diagram on front of unit) and is fed into troughs, from which it flows via notches onto the packing material in the tower (packings). The troughs at the top of the tower are designed to distribute the water uniformly over the packing with minimum splashing. There are several packings that can be used in the tower; you will probably be using the flat, slat-like material. The packings have an easily wetted surface and the water spreads over this to expose a large surface to the air stream. 2. The cooled water falls from the lowest packing into the collection basin, and exits the cooling tower (note T6 in system diagram). Next, the water is pumped to heaters. The two amber switches on the front of the unit operate the heaters, and note that this allows for three combinations of heating load. In cooling tower applications the heating load results from a process requiring cooling, such as the condenser coils of an air conditioner. For the Bench Top Cooling Tower, this is a simulated load, and comes in the form of the load tank. 3. Due to evaporation from the water, an accumulator or make-up tank must maintain the quantity of water in the cooling system. The volume of water added to the system can be measured by the lost of water in the make-up tank. 4. Droplets of water (resulting from splashing, etc) may become entrained in the air stream and then lost from the system. This loss does not contribute to the cooling, but must replenish by the accumulator or make-up tank. To minimize this loss, a droplet arrester, or eliminator is fitted at the tower outlet. This component causes droplets to coalesce, forming drops which are too large to be entrained and these will fall back into the packings. 5. Water flow is controlled by the control valve on the float-type flow meter (rotameter) at the far right of the untit. Note that a turbine flow meter has been installed (retrofitted) to the unit to measure the flow rate using the data acquisition system. Air System: 1. Using a small centrifugal fan with damper to control flow rate, air is driven up through the wet packings. Air enters the bottom of the tower and flows past a dry bulb temperature sensor (T1) and a wet-bulb temperature sensor (T2). At the exit of the cooling (at the top) the exit air dry bulb temperature (T3) and wet-bulb temperature (T4) are measured. Note that the wicks on the wet bulb sensor are immersed in reservoirs of water that may require filling. It should be observed that the change of dry bulb temperature is smaller than the change of wet bulb temperatures. This indicates that the air leaving is almost saturated, ie, Relative Humidity approaches 100%. This increase in the moisture content of the air is due to the conversion of water into steam and the latent heat for this will account for most of the cooling effect.

2. If the cooling load was switched off and the unit allowed to stabilize, it should be found that the water will leave the basin close to the wet bulb temperature of the air entering. According to the local atmospheric conditions, this can be several degrees below the incoming air (dry bulb) temperature. 3. Without a simulated load, the cooling tower would be able to cool the water to a temperature that approaches the wet bulb temperature. This is an ideal parameter of this system.

Figure 1. Bench Top Cooling Tower diagram

Procedure (Day 1) 1. 2. 3. 4. Study the operating principle of a cooling tower before working with the bench top model. Identify the adjustable parameters and data acquisition systems built into the system. What three variables can be changed? Check wet bulb thermocouple reservoir wells for water (T2 and T4). Add if necessary. Determine the accuracy of thermocouple T1 relative to a standard: Removed T1 from tower and inserted into the constant temperature calibrator Insert thermistor (lab standard) into calibrator Turn on the main power switch to the cooling tower, and the red LED readout for the thermocouple/temperature reading should become active. Adjust the thermocouple selector dial to read the output from T1. At room temperature, and two temperature set-points (approximate 40C and 50C) take 10 measurements readings each from the thermistor (lab standard), cooling tower readout for channel 1 and DasyLAB software read out for T1. Establish a spreadsheet for the 10 readings for all three sensors at each temperature, determine the average of each sensor reading and determine the accuracy of the cooling tower readout and the DASYLab readout relative to the thermistor standard. Perform an accuracy check on the thermocouple in the tower using sensor T1. Reinstall T1 in the tower and turn the water flow rate adjustment knob (clockwise) to shut the water flow off. Switch on the main power so the pump will run, but no water will flow through the tower. Fully open the damper on the fan. Let the tower stabilize for 10 minutes. Operating the cooling tower with no water flow, only the fan with damper fully open, record the dry bulb thermocouple readings (T1 and T3 from the unit and DASYLab). Ideally, they should have the same readings; similarly the wet bulb thermocouples should the same values so record these as well. Compare the mean values of T1 and T3 with the mean values of the T2, T4, T5 and T6. A difference in instrument readings, will this require a possible correction factor to bias the sensor readings? Using the handheld temperature-relative humidity probe, carefully take readings at the inlet to the fan. Using the sling psychrometer (convert to degrees C if needed!), take wet and dry bulb measurements of the room. Record all data, and compare with the results of step 6 using a psychrometric chart given at the end of this handout. Put a copy of a chart in your log book indicating the three moist air states you have just determined (tower sensors at air inlet, handheld probe at air inlet, and room with sling psychrometer).

5.

6.

7.

8. Connect the water system to allow for proper operation. Start the Bench Top Cooling Tower and observe the effects of orifice differential pressure, water flow rate and all the thermocouple readings. Procedure (Day 2) 1. Check wet bulb thermocouple reservoir wells for water (t2 and t4). Add if necessary. 2. The make-up tank should be at least half full before the starting the cooling tower. Use distilled water if fluid must be added to the system. Monitor and calculate the amount of water evaporated during all of the test operations of the cooling tower. This can be done by measuring the cross-section of the make-up tower and finding the change in the water level. 3. Start the Bench Top Cooling Tower and allow to stabilize under the following suggested conditions: Air orifice differential pressure: 14 mm water Water flow rate: 30 gm/s Cooling load: 1.0 kW 4. Let the tower stabilize for 10 minutes. Go step 5 while waiting. 5. While you are waiting for the system to come to steady-state, there should be a power supply on the bench top, turned off with the black - lead unplugged. The power lead should read Pressure & Turbine Flow Meter Power 8.22 VDC. Make sure the red + side lead is plugged in, if it isnt. Turn the power supply on adjusting the voltage readout to as close to 8.22 V as you can. Observe the signal output leads (bundled with the power supply leads) from the pressure transducer and water turbine flow meter, and where they are connected to the data acquisition equipment. Be sure they are not touching each other or any other metal and that the connections appear sound. Now plug in the black - lead to the power supply. This should now provide power to the pressure transducer and turbine flow meter in the tower, and the power draw on the power supply should be about 0.01 A (10 mA). You can check the zero offset error on the transducer output by disconnecting the pressure tap tube connecting the high side pressure transducer port, which should be connected to the tap in the top/exit chamber of the cooling tower. Record this value from the DASYLab worksheet as you check it out in step 6. Then reconnect the pressure tap tubing. While continuing to wait for the system to come to steady-state proceed to step 6. 6. While you are waiting for the system to come to steady-state, familiarize yourself with the DASYLab worksheet created to acquire data from the

cooling tower. In a past semester, two sensors were retrofitted to the tower by students as part of their final 58:080 project: a turbine flow meter (TFM) to measure water flow rate, and a piezo-resistive differential pressure transducer for measuring the mass of air flow through the tower. Observe that a counter is used on TFM to convert the wave pattern seen in the Y-t plot on the TFM output to a frequency. The frequency output has been calibrated as shown in Figure 2, and this calibration curve is applied in the DASYLab worksheet to output the water flow rate in gram/sec. The pressure transducer output has been calibrated as shown in Figure 3, and the calibration curve. The orifice at the top of the cooling tower (an example of an obstruction flow meter) has been calibrated by the manufacturer to measure mass flow rate of dry air as a function of differential pressure across the orifice and specific volume of the moist air mixture exiting the tower. This relationship is: P orifice & mass flow rate of dry air m = 0 . 0137 air (1 + out ) where Porifice is the orifice pressure difference in mm H2O, air is the specific volume of dry air (m3/kg), and out is the specific humidity of the air exiting the tower (kg/kg). 7. Record the six thermocouple values, and the inlet and exit air relative humidity and temperature using the handheld humidity probe. Note: each time you are told to record thermocouple values, record the digital readout from the unit, and the readout from the DASYLAB. Take thermocouple readings 3 times, in 2 minute intervals. 8. Before proceeding check the make up level of the water, and add water as needed to bring the level back to the level at the start of the cooling tower operation in step 2. Be sure to measure how much make up water you add. Increase the cooling load to 1.5kW. Let the tower stabilize for 10 minutes. Record the six thermocouple values, and the inlet and exit air relative humidity and temperature using the handheld humidity probe: 3 times, in 2 minute intervals. 9. Before proceeding check the make up level of the water, and add water as needed to bring the level back to the level at the start of the cooling tower operation in step 2. Start the Bench Top Cooling Tower and allow to stabilize under the following suggested conditions: Air orifice differential: 6 mm water Water flow rate: 30 gm/s Cooling load: 1.0 kW 10. Let the tower stabilize for 10 minutes. Record the six thermocouple values, and the inlet and exit air relative humidity and temperature using the handheld humidity probe. Take thermocouple readings 3 times, in 2 minute intervals.

11. Before proceeding check the make up level of the water, and add water as needed to bring the level back to the level at the start of the cooling tower operation in step 2. Increase the cooling load to 1.5kW. Let the tower stabilize for 10 minutes. Record thermocouple values. Record the six thermocouple values, and the inlet and exit air relative humidity and temperature using the handheld humidity probe - 3 times, in 2 minute intervals. Analysis: 1. Calculate average, precision and bias errors, and total error for the thermocouples. See the Appendix A Determining Bias and Precision Errors for a detailed procedure on these calculations. Essentially, the bias error is the difference between your standard and the mean of your measurements, and the precision error is the 95% confidence interval about your mean value. The total error is the root sum of the squares of both. 2. Using a psychrometric chart given at the end of this handout, determine the relative humidity in the room for each setting at which the unit was run using the wet and dry bulb inlet air temperatures (averaged). Compare with the handheld probe at each setting. Is the room becoming more humid as the testing progresses (systematic), or does it appear random? 3. Find the evaporation rate of the cooling tower at the different settings using your make up water measurements. Comment on the results, does the trend in the data make sense given the operating conditions used? 4. Calculate the effectiveness of the cooling tower by calculating the difference between the water exiting the cooling tower (T6) and the wet bulb temperature of the air entering the cooling tower (T2). This is known in cooling tower terminology as the approach temperature. Is it physically possible for the approach temperature (T6 T2) to be less than 0? 5. Compare and comment on the results between the cooling tower operating conditions. What test matrix of variables was used, which variables were held constant (or controlled) which did we vary? Remark on any other interesting tests that might be run, measurements which dont make sense, and any other engineering observations about the experiment.

Mass Flow Calibration Curve


45

Flow (g/s) = 0.1463(TFM y = 0.1463x + 0.0885 Output, Hz) + 0.0885 R2 = 0.9998

Measured flow (g/s)

35

25

15

5 0 50 100 150 200 250 300 Flow m eter output (Hz)

Figure 2 Calibration curve for the turbine flow meter added to the Experimental Engineering Labs Cooling Tower

Calibration Curve for Pressure Transducer


120 100 P (m m H 2 O ) 80 60 40 20 0 0 1 2 3 4 5 Pressure Transducer Output (V)

P (mm H2O) = 25.501(Volts) - 25.586 y = 25.501x - 25.586 R2 = 0.9994

Figure 3 Calibration curve for the pressure transducer added to the Experimental Engineering Labs Cooling Tower

Vous aimerez peut-être aussi