Key to Numerals
1 Sealing fitting. EYS for horizontal or vertical.
2 Sealing fitting. EZS for vertical or horizontal
conduits.
3 Circuit breaker. Type EPC.
4 Panelboard. D2PB, N2PB. Branch circuits
are factory sealed.
5 Junction box or conduit fitting. NJB,
Condulet

.
6 Fixture hanger. AHG, GS, UNJ.
7 Lighting fixture. VMV, DMV, and LMV
(CHAMP

).
8 Flexible fixture support. ECHF.
9 Handlamp. EVH.
11 Signal. ETH horns and sirens. ESR bells,
FlexTone, and W2H.
12 Compact fluorescent lighting fixture. FVS.
13 Plug receptacle. CES delayed action.
14 Plug receptacle. ENR or CPS delayed
action with GFS-1 ground fault circuit
interrupter.
15 Breather. ECD.
16 Drain. ECD.
17 Union. UNY.
18 Switch. Series EFS.
19 Magnetic line starter. EBMS.
20 Manual line starter. EMN.
21 Motors. Suitable for Class I, Division 2
locations.
22 Emergency lighting system. N2LPS.
23 Fluorescent fixture. FVN.
24 Floodlight. FMV.
References
a Sec. 501.15(B)(2). Seal required where
conduit passes from hazardous to non-
hazardous area.
b Sec. 501.15(B)(1). Seals required within 18
inches of all arcing devices.
c Sec. 408.36. Circuit breaker protection
required ahead of panelboard.
d Sec. 501.130(B)(2). All fixed lighting fixtures
shall be enclosed and gasketed and not
exceed ignition temperature of the gas.
e Sec. 501.115(B)(1). Most arcing devices must
be explosionproof.
f Sec. 501.10(B). All boxes must be threaded
for rigid or IMC conduit.
h Sec. 501.130(B)(1). All portable lighting
fixtures must be explosionproof.
i Sec. 501.130(B)(3). Pendant fixture stems
must be threaded rigid conduit or IMC.
Rigid stems if over 12 inches must have
flexible connector, or must be braced.
j Sec. 501.150(B). All signaling equipment
must be approved for Class I location.
k Sec. 501.145. Receptacles and plugs must
be explosionproof and provide grounding
connections for portable equipment.
l Sec. 501.15(F)(1). Breathers and drains
needed in all humid locations.
m Sec. 501.10(B). Not all joints and fittings are
required to be explosionproof.
n Sec. 501.125(B). Motor shall be suitable for
Division 2.
p Art. 430. Motor overcurrent protection.

--
-

`Also applicable for Class I, Zone 2