MiCOM P43x
Distance Protection
The distance protection devices of the MiCOM P43x range are designed for selective short-circuit protection, ground fault protection and overload protection. They can be applied in all kind of medium-, high- and extra-high-voltage systems. The wide range of protection functions covers all kind of applications in cable and overhead line protection. In addition numerous back-up protection and control functions are available. P43x provide four setting groups for easy adaptation to varying system operation conditions. The user-friendly user interface as well as the various communication interfaces allow easy and entire device settings and readings from extensive recordings. Numerous integrated communication protocols allow easy interfacing to almost any kind of substation control or SCADA system. Furthermore the integrated protection interface InterMiCOM provides direct end-end communication between two protection devices. The specially flat compact case of P430C as well as the standard 19'' modular cases of P433, P435 and P437 with variable number of plug-in modules provide a flexible solution for easy integration of the devices into the substation. Both case variants are available for flush monting and wall mounting.
compact P430C
Customer Benefits 1A/5A settable via software Two communication interfaces (for substation control system and remote access) Protection interface InterMiCOM
AREVA T&D
APPLICATION
Distance protection devices MiCOM P43x provide a wide range of protection functions. The integrated functions reflect the different requirements in system protections. The preferred applications are as follows: > P430C: MV systems with 3pole tripping only > P433: MV systems with 3pole tripping only > P435: MV and HV systems with 1pole or 3pole tripping > P437: HV and EHV systems with 1pole or 3pole tripping .
GLOBAL FUNCTIONS
The following global functions are generally available in all devices: > Parameter subset selection (4 alternative setting groups) > Metering > Operating data recording > Overload recording incl. overload data acquisition > Ground fault recording incl. ground fault data acquisition > Fault recording of all CT/VT inputs and binary event incl. fault measurands (e.g. fault location).
Functions Overview 21 DIST Distance Protection No. of measuring systems Mutual compensation Protective signaling (channel aided scheme logic) Switch on to fault protection Power swing blocking and out-of-step tripping Measuring-circuit monitoring (CT/VT supervision) Backup overcurrent-time protection Definite-time overcurrent protection Directional Inverse-time overcurrent protection Ground fault (short-circuit) protection (Br.: Directional earth fault protection, DEF) Ground fault (short-circuit) protection signaling (Br.: DEF scheme logic) Directional power protection Thermal overload protection Over-/undervoltage protection Over-/underfrequency protection Transient ground fault direction determination Ground fault direct. determ: using steady-state values Ground fault tripping Ground fault protection signaling Automatic synchronism check Auto-reclosing control Limit value monitoring Programmable scheme logic 2 communication interfaces, IRIG-B, InterMiCOM Binary inputs / output relays (maximum number) Analog-I/O (2x 20 mA outputs, 20 mA and PT-100 inputs)
P430C
P433
P435
P437
1 -
1 -
1 -
3 option
85-21 50/27 68
PSIG SOTF PSB MCMON BUOC DTOC IDMT GFSC GSCSG P<> THERM V<> f<> TGFD GFDSS GFTRP GFSIG ASC ARC LIMIT LOGIc COMMx INP/ OUTP MEASI / MEASO
option
option
option 1/3p
option 3p
option 3p
option 1/3p
25 79
option 2/8 -
option 10 / 22 option
option 28 / 46 option
option 28 / 46 option
2>3
MAIN FUNCTIONS
Main functions are autonomous function groups and can be individually configured or disabled to suit a particular application. Function groups that are not required and have been disabled by the user are masked completely (except for the configuration parameter) and functional support is withdrawn from such groups. This concept permits an extensive scope of functions and universal application of the device in a single design version, while at the same time providing for a clear and straight-forward setting procedure and adaptation to the protection and control task under consideration. Simple Function Selection by Mouseclick
FUNCTIONAL OVERVIEW
Communication COMM1
COMM2
Self Monitoring
to SCADA / substation control / RTU / modem ... via RS485 or Fibre Optics using IEC 60870-5-101, -103, Modbus, DNP3, Courier, UCA2, IEC61850
LIMIT
Vref
21 DIST
50/27 SOTF
VTS/CTS MCMON
51 P,N BUOC
67N GFSC
49 THERM
32 P<>
TGFD
25 ASC
79 ARC
I V IE,par
85-21 PSIG
68 PSB
85-67N GSCSG
81 O/U f<>
GFDSS
GFSIG
GFTRP
LOGIC
conventional signalling
InterMiCOM
protection communication
DISTANCE PROTECTION
The devices are equipped with elaborate fault detection elements that can be adapted to the individual application. They provide reliable fault detection and fault type determination even under difficult system conditions. The following criteria are continuously monitored: > > > > Overcurrent (I>>) Undervoltage (V<) Underimpedance with load blinding (Z<) Ground fault detection adaptable to system grounding.
V/Vnom
or
V/V / nom
3
1,0
V<
0,5
1,0
2,0
I/I
nom
I>
I>>
All fault detection measurement elements operate simultaneously. Inrush stabilization and Fuse Failure monitoring (VT circuit supervision) are integrated. A well proven voltage memory eliminates all problems with directional determination in case of small fault voltage, CVT transients or in series compensated lines applications.
X X fw
70
fw
Z
bw
Z
fw
fw , P P
,P G
Rfw,PG R Rfw,PP
Tripping Characteristics Six distance zones can be set in total. Each zone can be set as forward, backward or non-directional to suit requirements. Zone 1 extension is provided and controlled by integrated functions such as autoreclosing control or protective signaling or by an external signal. Special zone 4 is provided, to allow auto-reclosing only on the overhead-line section in cable/line systems or to compensate the bundle conductor effect. P437 could optionally be equipped with an additional CT input to measure the residual current of a parallel line to provide mutual coupling compensation.
45
X1
R1,PG R1,PP
Z1 45
R
arc compensation
4>5
3 N 2 1 CE E N
3 2 1 N
3 2 1 N
3 2 1
isolated starpoint
Peterson-coil compensated
low-impedance earthed/grounded
non-effectively earthed/grounded
effectively earthed/grounded
X
X
Power-Swing Characteristic
2 1 Z(t)
R
1: stable power swing 2: instable power swing (out-of-step condition)
PROTECTIVE SIGNALING
The distance reach is usually set to values below 100 % line length so as to avoid overlapping of adjacent substations. Protective signaling (teleprotection scheme logic) extends the reach of protection to 100 % by a logic operation on the signals received from the remote substation. Protective signaling can be operated using one of the standard schemes: > > > > > > Direct Transfer Trip (DTT) Permissive Underreaching Transfer Trip (PUTT) Zone Extension Permissive Overreaching Transfer Trip (POTT) Blocking Scheme (incl. DC loop) Reverse Interlocking (busbar protection)
With P437 phase-selective signal transmission is possible. Where required, the following additional features can be activated: > > > > > Weak infeed trip logic Echo Transient blocking Deblocking Channel Test Send signal.
6>7
INFORMATION INTERFACES
Information exchange is done via the local control panel, the PC interface and two optional communication interfaces. One of the communication interfaces conforms to IEC 60870-5-103, IEC 60870-5-101, DNP 3.0, Modbus and Courier (IEC 61850 under development) and is intended for integration with substation control systems. The 2nd communication interface conforms to IEC 60870-5-103 and is intended for central settings or remote access. Clock synchronization can be achieved using one of the protocols or using the IRIG-B signal input. One Record per Fault (incl. oscillography, SOE, Fault Measurands)
AREVA T&D Worldwide Contact Centre: http://www.areva-td.com/contactcentre/ Tel.: +44 (0) 1785 250 070
www.areva-td.com www.areva-td.com/protectionrelays
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
AUTOMATION-L3-P43x-BR-05.05-0938-GB - - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP