HARMONIC POWER QUALITY ON NAVAL SHIP ELECTRIC SYSTEMS ( OVERVIEW OF STANDARDS FIELD MEASUREMENTS ON HN "MEKO" CLASS FRIGATES )

I.K. HATZILAU(1), AR. MAGOULAS(2), S. PERROS(3), D. KAVOULAKOS(4), E. SAKIOTIS(4), E. CHRISTOFIS(4), F. MARTINOS(5), J. PROUSALIDIS(6)
(1)

Prof. Dr. Ing., Chair of Electrical Engineering , Hellenic Naval Academy (HNA) Tel: +3010-4581332, Fax: +3010-4181768, e-mail: ikx@snd.edu.gr (2) Dr., Lecturer, Chair Electrical Engineering, Hellenic Naval Academy (HNA) (3) Commander Hellenic Navy (HN), M.S.E.E. (4) Lieutenant Commander Hellenic Navy (HN), M.S.E.E. (5) Lieutenant Hellenic Navy (HN), MSc.M.E.S.E. (6) Dr., Lecturer, Naval and Marine Engineering Dept., National Technical University of Athens (NTUA) 9 Heroon Politechniou St, 15773 Greece. Tel: +3010-7722869, Fax: +3010-7721117, e-mail: jprousal@naval.ntua.gr

ABSTRACT: The main objective of this paper is a discussion on the power quality problems encountered on naval vessels with respect to the harmonic distortion limits imposed by relevant standards, namely IEEE-519 which refers to all electric systems and STANAG-1008 which is dedicated to warships. A brief discussion is also made on the causes, consequences and remedies of harmonic distortion in the electrical plants, while measurements conducted onboard HN MEKO class frigates are presented. The evaluation of the measurements indicates that it can not be easily argued if the STANAG-1008 as well as IEEE-519 current restrictions are violated or not, while the voltage distortion remains within the imposed limits. Keywords: Naval vessel, power quality, harmonic distortion, STANAG 1008, IEEE-519.

However, the main harmonic distortion is caused by the non-linear behavior of a number of electrical loads which, even though driven by a purely sinusoidal voltage, they absorb a deformed current (magnetic current of transformers, induction motors, fluorescent lamps and mainly static converters and power supplies of numerous electronic devices). The flow of these non-sinusoidal currents through the electric network creates voltage harmonic distortion in various points as a result of the distorted voltage drops on the internal impedance of all elements of the electric network. Furthermore, the main consequences of the high harmonic content in voltage and current are : increase of iron-losses in electric machinery resulting in efficiency decrease and overheating, hums and vibrations in electric machinery, malfunctions of electric devices, over-voltage and over-current due to resonance resulting in insulation fatigue and breakdowns, EMI/EMC problems to neighboring communication systems.

I. INTRODUCTION During the last years there has been a deterioration to the problem of the harmonic distortion, observed in voltage and current, in the electrical plants of modern warships. This anomaly is caused by the increasing use of non- linear electrical loads and the fact that many of the loads are sensitive to a voltage supply with a high harmonic content. The problem is expected to become more severe in the future constructions due to the extensive use of devices with power electronics and the perspective of implementing electric propulsion utilizing electric converters feeding innovative A.C. motors. In brief, the problem is stated as follows [1-2]: The generation of harmonic distortion has two causes. Synchronous generators produce - due to structural asymmetries - power with voltage harmonic distortion 1% approximately.

The electric system of a ship can be regarded as a noninterconnected one, comprising a reduced number of generators and an increased number of non-linear loads of low or high voltage, e.g. 440V or 6.6 kV. Therefore, it can be argued that the standards issued for ordinary electric systems can be applied to ships, too. On the other hand, specific standards have been released covering the electric installations on shipboard taking into account their particularities, [3]. Similarly, referring to power quality problems, standards like IEEE-519 [1] can be applied to ships, although standards dedicated to ships have been issued, while particularly for warships the STANAG 1008 [4] is used. In this paper, a discussion is made concerning the restrictions on voltage and current harmonic distortion implied by STANAG 1008. This discussion is supported by field measurements on HN MEKO class frigates, while some problems emerged from the application of the standards, are highlighted. Finally it is argued that IEEE-519 can resolve most of these difficulties.

Paper accepted for presentation at the 3rd Mediterranean Conference and Exhibition on Power Generation, Transmission, Distribution and Energy Conversion MED POWER 2002, jointly organized by National Technical University of Athens, IEE Hellas, Israel and Cyprus, Athens, Greece, November 4-6, 2002

II. POWER QUALITY STANDARDS AND MEASUREMENTS A. STANAG-1008/ Edition 8 The specifications of the electrical power plants in NATO naval vessels are laid down in STANAG-1008 [4]. According to Editions 7 and 8 which hold for about fifteen years, the Total voltage Harmonic Distortion (THD) of a 60Hz and 400Hz network must not exceed 5%, while no harmonic should exceed 3% of the fundamental. To achieve the above, STANAG 1008 provides design constraints for current harmonics produced by each separate load presented in Table I. The constraints refer to the %portion of the rated full load (nominal) fundamental current, I1fL, of each load. Table I. Current harmonic constraints by STANAG 1008 / Edition 8 Acceptable level of harmonic value in % of the rated full load (nominal) fundamental current, I1fL Loads < (1kVA/60Hz or 0.2kVA/400Hz and 2A/115V/400Hz) n >1 100/n % Loads > (1kVA/60Hz or 0.2kVA/400Hz and 2A/115V/400Hz) 3% 2 n < 33 100/n % n 34 The validity of this constraint has been more and more under reconsideration for the last years. The NATO AC/141(NG/6)SG/4 Group which is the custodian of STANAG 1008, considers the limitation of this STANAG with skepticism, since theoretical estimations and measurements in the electrical plants of naval ships indicate that STANAG 1008 current constraints appear too strict on the harmonic distortion allowed. Moreover, the reference term rated full load fundamental current, I1fL has occasionally lead to misinterpretations as well as difficulties to validate the STANAG constraints on shipboard, [5], [6], [7], [8]. Thus, the equipment rated power is often overestimated so that its actual load is lower - and much lower in some cases - than the rated full load. It is worth noting, that, in general, the harmonic spectrum in actual load could be considerably different from that in rated full load. This remark holds and is further supported by the field measurements presented in the following. B. FIELD MEASUREMENTS AND RESULTS During a project investigating electric power quality in Hellenic Navy ships, several measurements on voltage and current harmonics have been conducted onboard HN MEKO frigates, [9]. The electric plant (Fig. 1) in these ships is served by four generators (775KVA, 450V/60Hz, 3-phase), laid in two Harmonic order n

separate engine-rooms. The generators feed two main switchboards supplying thirteen Load Centers (LCi, i = 1,...,13). These LC distribute power (440/220/115V, 60Hz, 3-phase/1-phase and 24V DC) to all separate loads, see ref. [9],[10]. The instruments DRANETZ 658 Power Quality Analyzer and ELCONTROL VIP SYSTEM3' Energy analyzer, which can analyze current and voltage measurements up to the 50th and 25th harmonic respectively (for 50 and 60 Hz systems), have been used. Measurements have been taken at load inputs (440V 115V), transformer (440/115V) primary and secondary coils, 60/400Hz converter inputs (440V), LC inputs, and generator outputs, while generators were operating in normal power levels. Representative results are shown in Fig. 2. The spectrum of the current harmonics in these measurements, and the respective limits according to STANAG1008/Edition 8 are shown in Fig. 3. In Fig. 3(A) single consumers' current appears, while in Fig. 3(B) grouped consumers' current is presented (e.g. Load Centers, etc.) and finally in Fig. 3(C) the corresponding voltage harmonic spectrum is shown. From the measurements performed, it is evident that: a) The highest harmonics of current are of the order 3, 5, and 7 with their values being fairly large. b) The current harmonics measured appear to be of considerable portion of the corresponding (actual load) fundamental. These figures appear to exceed by far the constraints of STANAG 1008/ Edition 8. Similar sets of measurements in ships of several NATO Navies have lead to the impression that these constraints are too strict. However, in the authors opinion no safe conclusion according to Edition 8 stipulation, can be drawn based only on actual load spectra as few electric loads operate near to their rated power. Typical examples of this category are power transformers and power electronic converters, with their THD being a function of their demand in electric power. For instance, measurements at 60/400 Hz frequency converter of MEKO frigate performed in the usually operating power range (actual load) indicate excessive current harmonic distortion, as shown in Fig. 4. However, STANAG constraints are not necessarily violated, as, according to the trend of the measurement points presented in Fig. 4, which trend is also confirmed by the calculations according to IEEE-519 - the more operating power increases towards its rated value (rated power), the more harmonic distortion levels decrease, reaching eventually the permissible limits. Therefore in many cases, it is difficult to assess the distortion of currents of a stand-alone equipment, as defined by STANAG, without resorting to manufacturers test results or laboratory experiments performed in rated load conditions, which in current practice are rarely available. c) Nevertheless, no matter what the relevant values of the measured current harmonics are, the measured voltage distortion - referring to either the THD or the individual harmonics - is well beyond the imposed marginal values of STANAG.

SC

G1

G2

T.L

G3

G4

SC

LC 1 LC 2

LC 3 LC 7

. . .

LC7

LC 8 . . .

LC11 LC 12

LC 13

440V 60H z

2pT

2sT

115V 60H z

440V 400H z

115V 400H z

2.1 2.2

....

2.i

T2.1 . . .

24VDC

C 2.1 . . C 2.i

C T2.1 . . .

Fig. 1.

Schematic Presentation of the Electrical Plant of F/G MEKO.

V olt
75 0 50 0 25 0 0 -2 50 -5 00 -7 50 0:34 .73 5 0:34 .74 0 0:34 .74 5 0:34 .75 0 s

Am ps

% FND
60 50 40 30 20 10 0 Thd H 0 5 H 1 0

P hase
35 0 30 0 25 0 20 0 15 0 10 0 50 0

15 0 10 0 50 0 -5 0 -1 00 -1 50

sec Amp

H15 H20 H25 H30 H35 H40

V olt
75 0 50 0 25 0 0 -2 50 -5 00 -7 50 0:36 .81 0 0:36 .81 5

A .1 V I

% FND

A .2

P hase
40 0 35 0 30 0 25 0 20 0 15 0

15 12 5 10 10 0 5 0 75

50 -5 -1 0 25 -1 5 0:36 .82 0 0:36 .82 5

sec

10 0 50 0 0 Thd H 0 5 H 1 0 H 1 5 H 2 0 H 2 5 H 3 0 H 3 5 H 4 0 H 4 5

B .1

B .2

Fig. 2. Voltage (V) and current (I) waveshape as well as Current magnitude and phase harmonic spectrum of a 100 kW rated power load on the 440 V/60 Hz system, in two different operating conditions (A and B).

Fig. 3.

(A) Current harmonic spectra for independent loads (power 1 kVA). (B) Current harmonic spectra for groups of loads (e.g. LC inputs etc.) (power 1 kVA). (C) Respective voltage harmonic spectra.

Fig. 4.

Current THD and 5th HD of the 60/400 Hz converter as a function of operating power

C. STANAG-1008/ Edition 9 As mentioned above, STANAG-1008 / Edition 8 is to be replaced by Edition 9, being currently under ratification. In this edition, the voltage distortion constraints still hold, whereas the current constraints have been completely removed and substituted by (see also Table II): If the sum of the power of all loads which distort the current waveform connected to the supply system, Pdist is less than 1% of the short circuit power of the generation capacity, Ssc, with the largest single distorting load less than 0.5%, normally no measures are necessary to reduce current harmonics. This limit can be further extended to 2% of Ssc, if this load is due to the sum of only small distorting equipment, each less than 0.1% of Ssc. If any of these limits is reached or exceeded by the distorting load, analyses to whether STANAG-1008 requirements are still met with respect to voltage harmonics and an early coordination between the system design authority and the equipment manufacturer should be undertaken. Table II. Current harmonic constraints by STANAG 1008 / Edition 9 Condition

basis. This definition is much more readily applicable to any electric installation including the shipboard ones. Moreover, at an initial approximation, the average maximum load can be estimated by the service load simultaneous factors fs, which are extensively used at the electric balance of the ship power plant and are often readily available for a great variety of ship types. Factors fs are defined as the ratio of the actual energy required on a daily basis over the energy corresponding to the rated power for the same daily interval, therefore: (average maximum load) = fs * (rated load) Furthermore, the ship electric networks drop into the category between 120 V and 69 kV (section 10.2), while the short circuit current over maximum load current ratio is normally less than 20 (ship grounding systems are designed so that short circuit currents are just few times greater than the maximum load currents [12]). Consequently : identically to STANAG 1008, the voltage distortion is limited to 5% while no harmonic should exceed 3%. Concerning current distortion, this is limited as explained in the Table III. Table III. Current harmonic constraints by IEEE-519 Harmonic order n n< 11 11<=n<17 17<=n<23 23<=n<35 35<=n Acceptable level of harmonic value in % of the maximum load current (fundamental), I1fL, at PCC <4% <2% <1.5% <0.6% <0.3%

P
k

dist , k

= 1%.S sc with

Action required No action

Max k ( Pdist ,k ) = 0.5%.S sc

P
k

dist , k

= 2%.S sc with

No action

Max k ( Pdist ,k ) = 0.1%.S sc


Otherwise Analysis Pdist,k: power of devices distorting current waveforms Ssc: short circuit power level of the supply system Therefore, it is stressed that after this amendment, no tangible limitation on current (or any other quantity) distortion for each stand-alone power consumer is actually set in an effort to restrict the voltage distortion within the specified limits. On the contrary, voltage distortion has to be investigated by performing a plethora of costly power quality analyses (simulations of operation of the entire electric system and/or field measurements on it), where all alternative solutions from various manufacturers and at several operating points must be taken into account whenever a piece of equipment is to be installed or replaced. D. IEEE-519

However, it has to be stressed that even in the IEEE-519 case, there have been discussions on the interpretation of the definitions of PCC, short circuit current and maximum load current values considered, as they may result in erroneous conclusions [11]. III. DISCUSSION Taking into account the aforementioned points, it is underlined that all standards require that the voltage total harmonic distortion is less than 5%, a constraint proven to hold almost by any measurements onboard. However, there seems to be no clear way of estimating this voltage distortion e.g. by investigating the current distortion caused by each separate load. More specifically: a) STANAG 1008/Edition 8, makes the effort to set constraints on current harmonics so that voltage distortion is kept within acceptable limits. However, these current distortion constraints are, on the one hand, difficult to interpret and finally measure, whereas on the other hand, it can be argued they are often exceeded without, though, leading to excessive values of voltage distortion. b) STANAG 1008/Edition 9, which is planned to succeed Edition 8, does not offer an actual solution to the problem,

According to IEEE-519 [1,11], the acceptable levels of current and voltage distortion are defined at the Point of Common Coupling (PCC), i.e. that busbar defined as the border between the power generation and power consumption sections. The limit values depend on the voltage level of the electric system studied and the ratio of short circuit current over maximum load current, the latter being the average of maximum loads achieved on a 12-monthly

by clarifying or even resetting the current harmonic distortion constraints. On the contrary, Edition 9 simply states that several analyses must be performed at the ship design stage or at any revamp to reassure that voltage distortion does not exceed the limit of 5%, without setting any guiding constraints for each separate manufactured equipment. c) Finally, IEEE-519, which could be applied to shipboard installations, appears more readily applicable referring more clearly to certain operating conditions and measurements. Therefore, it is believed, that IEEE-519 constraints on current could be applied onboard despite the difficulty to assess the average of maximum loads on a 12-monthly basis, as, even at the design stage, the service load simultaneous factors fs can be used. IV. CONCLUSIONS In this paper a discussion is made on the power quality harmonics on shipboard electric systems. The discussion is supported by field measurements on HN MEKO class frigates. Comparing the measurement results with the directives of STANAG 1008 / Edition 8, in many cases it is rather difficult to identify whether the suggested current harmonic limits are violated or not, as they refer to often unattainable operating points. On the other hand, the voltage harmonic distortion in operating plants, which is the ultimate objective, is measured to be well below the limits set by either STANAG-1008 or IEEE-519 (voltage THD less than 5%, each voltage harmonic very less than 3% ). STANAG 1008 / Edition 9, which will replace Edition 8, practically sets no limits on current harmonics of each separate or group of loads. On the contrary, IEEE-519 sets current distortion limits for the installed equipment and seems to be more readily applicable, as it refers to actual operating points. V. REFERENCES
[1] IEEE Std 519-1992 : "IEEE Recommended Practice and Requirements for Harmonics Control in Electrical Power Systems", IEEE, NewYork, 12 April 1993. [2] Vokas, G. ,Gazithellis, D. , Katsikaris, C., Peponis, G., "Electric Power Quality ", Technical Chamber of Greece, Athens, May 1993 (In Greek). [3] IEEE Standard 45-1993, "Recommended Practice for Electrical Installations on Shipboard", IEEE Press, New York, 1993 [4] STANAG 1008 : "Characteristics of Shipboard Electrical Power Systems in Warships of the North Atlantic Treaty Navies", NATO , Edition 8, 21 Febr. 1994./ Edition 9 under ratification. [5] NATO AC/141(SG/6)SG/4 FRANCE paper 93/08 (44)-8 Sept. 93, : "Harmonic pollution on Ship electric side circuit - Limitation of harmonic currents injected into side circuit" , DGA Note technique No 353/93 SY/SEP, Paris 8 Sept. 1993. [6] NATO AC/141(SG/6)SG/4 GERMANY paper (02)96/10-03.04.96 : "STANAG 1008, Harmonic Distortion, Compilation of Replies to Questionnaire" [7] NATO AC/141(SG/6)SG/4 GERMANY paper (07)97/24-12.12.97 : "Harmonic Distotion". [8] NATO AC/141(SG/6)SG/4 GREECE paper (03)00/28-03.04.00 : "Interpretation of Current Distortion Limits of STANAG 1008 Ed. 8

[9] Hatzilau, I.K., "Verification of Electric Power Quality on Shipboard ", Research Project Progress Report, Hellenic Naval Academy (HNA), July 1999 (In Greek) [10] "MEKO 200 General Purpose Frigate (HN) "HYDRA" Class" "System Manual, Electrical System and Automation" , Doc. No. 0720-1300 File 01 [11] McGranahan, M., Overview of the Guide for Applying Harmonic Limits on Power Systems-IEEE 519A, Proceedings of 8th International Conference of Harmonics and Quality Power, Athens (Greece), 16-18 October 1998, pp. 462-469. [12] Bal, R.,Stephens, G.W., Neutral Earthing of Marine Electrical Power Systems, Trans I Mar E (TM), Vol. 95, Paper No 32, 1982.

VI. BIOGRAPHIES
Prof. Dr. Ing. I.K. HATZILAU (Electrical & Mechanical Engineer from NTUA/1965, Dr. Ing. from University of Stuttgart/1969). After few years in the industry, he joined the Academic Staff of HNA where he has been for 25 years. He is also representative of HN in NATO AC/141(NG/6)SG/4 dealing with electric systems in warships. Dr A. MAGOULAS, (Electrical Engineer from NTUA/1985, PhD from NTUA/2000). He has been Lecturer at the HNA since 1990 and is interested in Electromagnetic Scattering problems and also in Electrical Power systems. Cdr. S. PERROS, (Engineer Officer from the HNA/1984, M.Sc in Electrical Engineering from Naval Postgraduate School in Monterey California, USA/ 1992). After many years of service in HN warships (including Frigate MEKO HN type), he is assigned now in HN General Staff. He is also an associate of the El. Engineering Chair of the HNA and is interested in the naval ships electric systems and the electrical power quality problems. Lt. Cdr. D. KAVOULAKOS, (Deck Officer from the HNA/1988, M.Sc in Electrical Engineering from Naval Postgraduate School in Monterey California, USA/ 1996). After many years of service in HN warships (including Frigate MEKO HN type), he is assigned now in HN General Staff. He is interested in Communication Systems and also in Electric Power Quality problems on ship electric systems. Lt. Cdr. E. SAKIOTIS, (Engineer Officer from the HNA/1987, M.Sc in Electrical Engineering from Naval Postgraduate School in Monterey California, USA/ 1996). He has served in many HN warships (including Frigate MEKO HN type) and is now serving in Souda Naval Base as head of Energy Division and Electrical & Electronic Workshops Manager. He was also an associate of the El. Engineering Chair of the HNA. Lt. Cdr. E. CHRISTOFIS (Deck Officer from the HNA/1988, M.Sc in Electrical Engineering from Naval Postgraduate School in Monterey California, USA/ 1996). After many years of service in HN warships (including Frigate MEKO HN type), he is assigned now in HN General Staff. He is interested in Communication Systems and also in Electric Power Quality problems on ship electric systems. Lt. F. MARTINOS (Engineer Officer from the HNA/1991, M.Sc in Military Electronic Systems Engineering from Royal Military College of Science of Cranfield University ,UK/1997). At present he is positioned as a Director of the Electronics Department (Electronics Officer) in H.S. SPETSAI (Frigate MEKO HN type) and he is an associate of the El. Engineering Chair of the HNA and he is interested in the naval ships electrical systems and the Electric Power Quality problems. Dr. J. PROUSALIDIS (Electrical Engineer from NTUA/1991, PhD from NTUA/1997). Currently, he is Lecturer at the Naval Architecture and Marine Engineering Department of National Technical University of Athens, dealing with electric energy systems and electric propulsion schemes on shipboard focusing on electric power quality problems and analysis of transients.