Vous êtes sur la page 1sur 4

Altivar 21

variable speed drive HVAC applications


Short form guide
June 2009

ATV21 helping to manage and monitor your HVAC solutions


Simple plug and drive usage, the ATV21 enables immediate start-up following its initial connection. Pressing the LOC/REM button provides access to the local controls for testing your application. Economical, specially designed to optimise your needs, both IP20 and IP54 products with (IEC/EN 61000-3-12) integrated harmonic less technology and (IEC/EN 61800-3) integrated EMC filters. Compact, it easily integrates in your machines with side-by-side mounting.

Integrated 7 segment display terminal


The Altivar 21 drive has an integrated 7-segment display is used to: Display status and faults. Access and modify parameters. Check your installation easily in local mode using the Loc/Rem key 3. Description 1 Display: Four 7-segment displays visible at 5 m. Display of numeric values and codes. The display flashes when a value is stored. Unit rating of displayed value. The display flashes to indicate a fault on the drive. 2 Display of drive status: RUN: Run command is active or speed reference present. PRG: Drive in automatic mode. MON: Drive in monitoring mode. Loc: Drive in local mode. 3 Use of keys: Loc/Rem: switching of the drive command, locally or remotely. As a local command, the speed reference are modified using the and V keys; the LED located between these keys lights up. and V vertical navigation in the menu, editing of values or speed reference depending on the mode selected. MODE: Selection of one of the following modes: - Default display mode. - Adjustment mode. - Status monitoring mode. RUN: Local motor run command; LED indicates that the RUN key is active. STOP: Local control of motor stopping/drive fault clearing. ENT: Saves the current value or the selected function.

Quick menu
The Quick Menu is used to: Access the essential parameters of your application quickly Enter the motor rating plate data (nominal voltage, nominal frequency, thermal current, etc.), so that the motor parameters can be adjusted quickly, thereby benefiting from optimum motor performance Protect the motor by setting the drives integrated electronic thermal overload relay

Parameter Quick menu


Parameters which can be accessed in the Quick Menu (AUF):

Parameter

Description

Factory default

ACC DEC LL UL tHr uL uLu Sr1

Acceleration Deceleration Low speed High speed Motor thermal current Nominal motor Frequency Nominal motor voltage Preset speed 1

10 sec. 10 sec. 0.0Hz 50.0Hz Rated current 50Hz 400V 15Hz

ATV21 Connection and sizes


Factory default connections

ATV21
L1 L2 L3 U V W P24 F R RES RY RC CC VIA PP FM FLB FLA FLC
415V 50Hz 3 phase line power

Motor 3~

Three phase motor power

Function Start/Stop Ext 0-10V Speed ref. Fault reset Preset speed 1 Fault output signal Run output signal

Terminal connection P24 - F CC(0) - VIA(+) P24 - RES P24 - R (SR1 = 15Hz) FLA - FLB - FLC (Relay) RY - RC (relay)

24VDC Common Run Forward Preset speed / Fire Run (F112 52) Fault reset Volt free contact Drive Running (Low speed reached) Common 0VDC Speed reference 0 to10VDC

Analogue input supply +10VDC

Analogue output Volt free NO/NC contacts Drive Fault

Specification

Motor Nominal Power kW 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0

Line Supply 380-480V 50/60Hz Line Current Apparent Power A @ 380V A @ 480V kVA @ 380V 1.7 1.4 1.6 3.2 2.5 2.8 4.6 3.6 3.9 6.2 4.9 5.5 9.1 6.4 6.9 10.9 8.6 9.1 14.7 11.7 12.2 21.1 16.8 17.1 22.9 22.8 23.2 34.8 27.8 28.2 41.6 33.1 33.2 56.7 44.7 44.6 68.9 54.4 52.0 83.8 65.9 61.9 102.7 89.0 76.3 141.8 111.3 105.3

Maximum continuous output current A @ 380V / 460V 2.2 3.7 5.1 7.2 9.1 12.0 16.0 22.5 30.5 37.0 43.5 58.5 79.0 94.0 116.0 160.0

Inverter MCCB W eight - kg Heat loss Rating Type - A D4 D4 D6 D6 D10 D16 D20 D25 D32 D50 D50 H80 H80 H100 H150 H220 IP20 2.0 2.0 2.0 3.4 3.4 3.4 6.5 6.5 11.7 11.7 26.4 26.4 38.1 38.1 55.4 55.4 IP54 7.5 7.5 7.5 10.6 10.6 10.6 11.9 36.5 36.5 45.0 58.5 58.5 77.4 77.4 88.4 88.4 Watts 55 78 103 137 176 215 291 430 625 603 626 847 976 1252 1455 1945

Dimensions W xHxD IP20 107x143x150 107x143x150 107x143x150 142x184x150 142x184x150 142x184x150 180x232x170 180x232x170 245x330x190 245x330x190 240x420x214 240x420x214 240x550x244 240x550x244 320x630x290 320x630x290 IP54 215x297x192 215x297x192 230x340x208 230x340x208 230x340x208 230x340x208 230x340x208 290x560x315 290x560x315 310x665x315 284x720x315 284x720x315 284x880x343 284x880x343 362x1000x364 362x1000x364

ATV21W IP54 ATV21H IP20

height

height depth depth width width

Schneider Electric Ltd.


University of Warwick Science Park Sir William Lyons Road Coventry CV4 7EZ Tel. 0870 608 8 608 Fax 0870 608 8 606 Web: http//www.schneider.co.uk Registered to ISO 9001 ASTA cert. No. 12600 IIP cert. No. 09649 Registered to ISO 14001 ASTA cert. No. 13431 Registered in England 1407228 Registered Office Stafford Park 5 Telford TF3 3BL