Bridge Watch Alarm System BW-700 Manual

BW-700 is produced in accordance with international and Danish laws for one man bridge operation e.g. IMO resolution A.830. BW-700 has been designed for mounting on a DIN rail in the power cabinet or flush mounting. The purpose of the bridge watch alarm system is to ensure the continuous monitoring of the bridge operators fitness during "one man bridge" operation.

BW-700 Manual English 2010-1

Page 1 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Technical specifications:
Main supply: 12 or 24 V 12 V ( Min. 11V / Max. 15V ) 24 volt ( Min. 16V / Max. 29V ) Max. 0,4 A. The power supply must be secured against overcurrent externally. Max. 2.0 A Mount a suitable relay and connect to General alarm. Se wiring diagram page 6. Max. 10.0 Watt Width 105 mm / Height 86 mm / Depth 58 mm. -10 up to +65 degrees C. Qty.: 2 pcs. Timer 1: adjustable from 3 up to 12 minutes. Timer 2: adjustable from 60 up to 180 sec. (internal) Qty.: 4 pcs. All relay contacts are galvanic separated from the BW-700 unit and from each other. Relay contacts: Max. 250V AC, 5A. IP54. Key disconnector: 3 positions. The key can be taken out in all positions. Adjustment of the light intensity from max. to 80%. Adjustment of both internal and external light. Supply to external light: 12V Max. 200mA. To movement detectors. Max 200 mA. Marine proof cable min. 0,5mm and maximum 1mm.

Power consumption: Power failure alarm: Consumption: Dimensions: Operating Temperature: Adjustable timers:

Relay contacts:

Protection: Operation: Dimmer function:

12 V output: Cable requirements:

BW-700 Manual English 2010-1

Page 2 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Cable connections:
Terminal 1: Terminal 2: Terminal 3: Terminal 4: Terminal 5: Terminal 6: Terminal 7: Plus 24 V supply Minus ( GND ) Plus 12 V supply Minus ( GND ) Plus 12 V max. 200mA. To movement detector Disconnects in case of overload. Reset in. Terminal 4-6 closed by resetting the timer. Emergency button. Terminal 4-7 must be closed for 2 sec. to activate the emergency function. Plus 12 V max. 200mA To background light, is adjusted by the DIMMER button Minus ( GND ) Supply to auto pilot. When active terminal 9-10 must be closed. Relay contact. Togler 5 sec. before timer has ran out Relay contact. Closed by alarm 1. Relay contact. Closed by alarm 2. Relay contact. Closed by alarm 3.

Terminal 8: Terminal 9: Terminal 10: Terminal 11 12: Terminal 13 14: Terminal 15 16: Terminal 17 18:

BW-700 Manual English 2010-1

Page 3 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Operating instructions:
The Bridge Watch can only be activated and deactivated by use of a key. Therefore, only authorised personnel (usually the captain) can decide if the bridge watch alarm should be active or not. The key function has 3 setting modes: The 3 modes are: ON (the BW is active all the time), Off (the BW is not active) and Auto (in this mode the BW is only active when the ships autopilot is on). When the BW-700 is active, the built-in timer must be reset, before the preset timer has run out. The reset of the timer can be done in two different ways: manually by activating a reset button or by ensuring a constant movement (activity) sensed by the movement detector on the bridge. The time is set on the adjusting button Timer before the BW is activated. The preset time cannot be changed as long as the BW-700 is active. When the timer is 15 sec. from running out, a warning is activated. The warning can be a small alarm buzzer or a light signal depending on what is connected. This gives the captain time to reset the timer before the alarm is activated. If the captain of the ship has not reset the timer within 15 seconds the 1st of the 3 alarms will be activated. Alarm 1: This alarm is placed on the bridge and is meant to ensure a weakening of e.g. a drowsy ships master. The alarm can be switched off by resetting the timer. If the timer is not reset after 15 seconds the alarm switches to alarm 2. Both alarm 1 and 2 is now active. Alarm 2: This alarm is placed where the back-up officer / captain is presumed to be. Now the alarm can only be switched off by using a key. However, the alarm on the bridge will be silent when the timer is reset. Alarm 2 stays active until the key is used to switch it off. If the alarm is not switched off and there is still no activity on the bridge after 60180 seconds the alarm 3, now alarm 1, 2 and 3 is activated. The timer can be set from 60180 seconds during installation, to give time to the back-up officer to react on the alarm. Alarm 3: This alarm is placed in the crew area. The alarm can only be switched off by using a key. However, the alarm on the bridge becomes silent when the timer is reset in order to avoid stressed personnel. Alarm 2 and 3 remains active until the key is used to switch it off. Emergency calls: BW-700 also has an option for connection of emergency calls. This will be in the form of a push button. When activated for 2 seconds the alarm will automatically go to alarm 2 and subsequently to alarm 3 if no action is taken. Using this function the ships master is able to call for assistance if needed. The alarm can only be switched off by using a key. However, the alarm on the bridge becomes silent when the timer is reset in order to avoid stressed personnel. Alarm 2 and 3 remains active until the key is used to switch it off.

BW-700 Manual English 2010-1

Page 4 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Alarm 3 output

18 17 16 15 14 13 12 11

PRINCIPLE DIAGRAM BW-700


Relay Int. Adjust. 1-3 min. Timer 4 Relay Timer 3 Relay Timer 2 Relay

CE

Alarm 2 output

Alarm 1 output

Alarm for timer

Auto pilot signal input10 Minus ( GND ) output 9


Emergency detector

Plus 2-12 V output to background light

8 6 5

Dimmer 20-100% Ext. just.

Emergency input 7 Reset input Plus 12 V movement detector

Ext. Adjust. Timer 3-15 min. 1

Autopilot detector On Auto Key Power adjust. 24 >12 volt reg.

Minus ( GND ) output 4 Plus 12 V input Minus ( GND ) input

3 2

Plus 24 V input 1

BW-700 Manual English 2010-1

Page 5 of 14

BW-700
(Item: 703)

WIRING DIAGRAM BW-700

On

Off

Auto

General alarm, visual alarm or audio alarm.


Assistance to bridge

BW-700 Manual English 2010-1

AB-2
(Item: 702)

Alarm 3: General alarm - crew area. Activated 60-180 sec. after the 2nd. alarm.

Power faliure alarm relay NO (Not standard supply).

24 V. 12 V.

Assistance to bridge

Alarm 2: Captains quarters. Activated15 sec. after the 1st. alarm. (Item: 702)

Fuse

AB-2

2Amp

Assistance to bridge

RB-1R

(Item: 703)

Alarm 1: Bridge. Activated when the timer has ran out. (Item: 702)

AB-2

RB-1RNA

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Page 6 of 14

(Item: 704)

When active, the contact is closed

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

125 mm.

On

Off

Auto

125 mm.

135 mm.

115 mm.

110 mm.

BW-700 Manual English 2010-1

Page 7 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

The picture below shows the BW-700 mounted in a mounting box no. 710. Dimensions: Height = 185 mm. Width = 145 mm. Depth = 85 mm.

BW-700 Manual English 2010-1

Page 8 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

AB-2:
AB-2 is designed for use together with BW-700. AB-2 will sound an alarm when the timer has expired. It sounds a powerfull tone from the 4 loudspeakers and the red warnings light flashes. AB-2 can be preset to 5 different warning pitches during the installation. To avoid disturbance when the alarm goes off, AB-2 is constructed to start with low volume, and rising to high volume within seconds. The maximum volume can be set between 75 and 90 DB.

Voltage: Power compsumption: Compsumption: Dimensions: Temerature range: Protection: Terminal 1: Terminal 2: Volume

12 to 24 volt DC. internal. stab. to 12 volt. Max 0,15 Amp. Max 3,6 Watt. W:50mm H:75mm D:30mm -10 to +55 degrees. IP 54. Ground Alarm plus.

Sound switch H-0 H-H L-0 L-L H-L H= high tone L=low tone 0= no tone
Principle diagram 1 2

Assistance to bridge

BW-700 Manual English 2010-1

Page 9 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

RB-1R:
RB-1RNA is designed for use together with BW-700 as reset button with light warning. The unit has background light and this is regulated by the dimmer function on BW-700. 5 seconds before the timer has ran out, the alarm and the background light starts flashing.

Mains supply: Power consumption: Consumption: Dimensions: Temperature range: Protection: Terminal 1: Terminal 2: Terminal 3: Terminal 4:

2-12 volt DC for background light 12 to 24 volt DC. For warning light. Max 0,04 Amp. Max 1,0 Watt. W:50mm H:50mm D:30mm -10 to +55 degrees. IP 54. Background light ( plus ) Minus ( GND ) Reset contact Warning light ( plus )

Principle diagram 1 2 3 4

BW-700 Manual English 2010-1

Page 10 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

RB-1RNA:
RB-1RNA is designed for use together with BW-700 as reset button with sound and light warning. RB-1RNA also has an emergency function. The unit has background light and this is regulated by the dimmer function on BW-700. 5 seconds before the timer has ran out, the alarm and the background light starts flashing. To activate the emergency function press the reset button for more than 2 seconds. After 2 seconds the sound warning will sound shortly to notify that the emergency function is activated. Mains supply: Power consumption: Consumption: Dimensions: Temperature range: Protection: Terminal 1: Terminal 2: Terminal 3: Terminal 4: Terminal 5: 2-12 volt DC for background light 12 to 24 volt DC. For warning light. Max 0,04 Amp. Max 1,0 Watt. W:50mm H:50mm D:30mm -10 to +55 degrees. IP 54. Background light ( plus ) Minus ( GND ) Reset contact Emergency contact Warning light ( plus )

Principle diagram 2 3 4 5

BW-700 Manual English 2010-1

Page 11 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Motion sensor 1. FEATURES Input Voltage: 9 to 16 VDC Current Drain: About 28 mA @ 12 VDC Size (H x W x D): 117 x 65 x 47 mm. Weight: 109 g (3.85 oz) w/o bracket, 124 g (4.4 oz) with bracket. PIR SECTION Detector: Low noise dual-element pyroelectric sensor Tripping Indication: LED flashes green for up to 5 seconds Motion Event Verification Counter: Selectable, 1 or 2 events No. of Beams: 36 in two layers (curtain beams in bottom layer) Max. Coverage: 12 x 12 m (40 x 40 ft) / 90 field of view Vertical Adjustment: FAR and NEAR, by sliding the circuit board along a two-position scale. MW SECTION Oscillator: Microstrip DRO-stabilized Doppler module Frequency: 10.525 GHz (U.S.A. only) or 2.45 GHz (Europe) Detection Range: Adjustable from 25% to 100% (3 m to 12 m) Tripping Indication: LED glows green for up to 5 seconds Alarm Indication: LED glows red for 1.3 to 5 seconds if both detectors trip MOUNTING Height: Up to 3.6 m (12 ft) Room Size: 8 -12 m (24 - 40 ft) in the FAR position; 2 - 8 m (6 - 24 ft) in the NEAR position. Bracket Adjustment: 20 downward, 20 left and right. Installation Options: Surface or corner (without bracket); surface or ceiling (with bracket) ENVIRONMENTAL RFI Protection: >30 V/m up to 1000 MHz. Operating Temperatures: -10C to 50C (14F to 122F). Storage Temperatures: -20C to 60C (-4F to 140F).

Mounting with Swivel Bracket A. Remove the front cover. B. Remove the PCB and put it temporarily aside. C. Punch out the large knockout in the round bulge at the top part of the base.

BW-700 Manual English 2010-1

Page 12 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Visual Indications The dual color LED is used to signal various alarm and trouble messages as shown in Table 1 below: Table 1. Interpreting the Visual Indications Visual Indication Significance None No detection Steady green (5 s) MW walk-test detection Flashing green PIR walk-test detection Steady red (5 s) Alarm: MW + PIR detection Flashing red and - Trouble or masking is being detected by the self test circuitry green (alternately) - Initial warm-up routine (stops 60 seconds after power up). Notes: During walk testing, the green light glows steadily (MW detection) or flashes (PIR detection), depending on which one of the two detectors discovered the movement first. Upon subsequent discovery of the movement by the other detector, the green light goes off and the red light glows (alarm). If the LED maintains alternate red and green flashing beyond the warm-up period, a malfunction or masking has been diagnosed. Replace the unit without delay. The DIP switch mode selector is mounted on the units PC board (see Figure 5). It controls four functions as demons- trated in Figure 12 and as detailed in Table 2.

Installation hints:

Prevent direct sunlight from reaching the detector

Keep wiring away from electrical power cables

Do not install behind partitions

Do not aim at heat sources

Mount on solid, stable surfaces

Do not expose to air drafts

Do not install outdoors

BW-700 Manual English 2010-1

Page 13 of 14

Amager Strandvej 124 2300 Copenhagen Denmark Tel. +45 3286 0525 Fax: +45 3258 1330 e-mail: info@unielec.dk www.unielec.dk

Troubleshooting guide: Step: Problem: 1 No reset from motion sensor. Description: Check voltage on Reset 1 input (BW-700 connector pin 6). Low voltage when LED in motion sensor is red. If constant low, remove the wire to the motion sensor and check again. Possible Causes: Standard mounting bracket not used and screws behind the PCB is shortcutting the sensor. Remove the screws and use the standard mounting bracket. BW-700 has no power

Check external fuses Check DC power on terminal 1-4 (12/24Vdc) Check the cable connections Check DC power on terminal 6 on BW-700 No alarm on (0V/low, only when reset button is pushed bridge and Alarm LED 2 or a movement is detected) Movement detector: When the red LED is and 3 are on, a low pulse is sent from terminal R always on If constantly low: 1) Turn the BW-700 off (key in position off) 2) Remove all wires from terminal 6 3) Set the alarm to 3 minutes and set the key in position on 4) Check that alarm 1 starts after 3 minutes (BW-700 is then ok) 5) Turn the BW-700 off 6) Mount the wire from one reset button to terminal 6 7) Set the key in position on 8) Check that alarm 1 starts after 3 minutes 9) Check that you can reset the alarm by pushing the reset button (reset button 1 is ok) 10) Turn the BW-700 off 11) Mount the wire from one movement detector to terminal 6 12) Set the key in position on and dont move 13) Check that alarm 1 starts after 3 minutes 14) Check that you can reset the alarm by walking around (movement detector is ok) 15) Check additional reset buttons and movement detectors by the same procedure as above No alarm 1-3 Check the cable connections. and the LEDs Check 12Vdc power at the terminals on the for alarm 1-3 alarm units. are on

No lights in BW-700

Installation failure Movement detectors defective Reset button defective

Cable failure Alarm units defective

BW-700 Manual English 2010-1

Page 14 of 14