The boiler Steam system consists of SH,RH & BLOWDOWN SYSTEM SUPERHEATER
The saturated steam from the drum flows into three stages of superheaters. Steam is superheated up to rated temperature through primary, secondary and tertiary superheaters. Auxiliary steam and soot blower steam are extracted from the primary superheater outlet. Two stages of attemperators are provided between each superheater to control the boiler outlet main steam temperature. The boiler main steam stop valve is provided for the maintenance purpose such as hydrostatic test. Finally, superheated steam is supplied to the HP turbine from the boiler through the Main Steam Piping. Superheater spray water is supplied from the HP feedwater heater inlet. The superheater spray water piping distributes spray water to superheater first and second stage attemperators.
REHEATER
The Cold-Reheat Piping conveys HP turbine exhaust steam from the HP turbine outlet to the reheater. The steam is reheated up to rated temperature through the reheater. The reheater outlet steam temperature is controlled by flue gas recirculation flow regulated by the Gas Recirculation Fans. Also an attemperator is provided at the Cold-Reheat Piping to control the
reheater outlet steam temperature in abnormal condition. Then, reheated steam is supplied to the IP/LP turbine from the reheater through the Hot-Reheat Piping. -Reheater spray water is supplied from middle stage of boiler feedwater pumps. The reheater spray water piping supplies spray water to reheater attemperator.