Minimum Acceptable Specification of Current Transformer for Metering:

Sr. No 1 2 Particulars Highest System Voltage (kV rms) CT ratio. 11 kV 12 2000-1000/1-1 1600-800/1-1 1200-600/1-1 800-400/1-1 600-300/1-1 400-200/1-1 300-150/1-1 150-75/1-1 Two Nos 120% of rated primary current 25 33 kV 36 800-400/1-1 600-300/1-1 400-200/1-1 300-150/1-1 100-50/1-1 132 kV 145 400/1-1 220 kV 245 800/1-1

3 4

Number of metering cores Rated continuous thermal current. Rated short time thermal current of primary for 1 sec. (kA) CT characteristics : a) Rated primary current (Amps.)

Two Nos 120% of rated primary current 25

Two Nos 120% of rated primary current 31.5

Two Nos 120% of rated primary current 40

7 8

(b) Rated Secondary current (Amps.) (c) Class of accuracy. (d) Max. instrument security factor (e) Rated burden (VA). IS to which CT conforms. IS to which insulating oil conforms.

2000-1000 1600-800 1200-600 800-400 600-300 400-200 300-150 150-75 1 0.2 5 30

800-400 600-300 400-200 300-150 100-50

400

800

1 0.2 5 30

1 0.2 5 30

1 0.2 5 40

Minimum Acceptable Specification of Voltage Transformer for Metering:


Sr. No 1 2 3 Particulars Highest System Voltage (kV) Rated Capacitance (pF) For low voltage terminal over entire carrier frequency range. (a) Stray capacitance (b) Stray conductance (a) High frequency capacitance for entire carrier frequency range (b) Equivalent series resistance over the entire frequency range. No. of secondary windings for potential device. Transformation ratio: (i) Winding I (ii) Winding II Rated secondary burden (i)Winding I (VA) 245 kV CVTs 245 kV 145 kV CVT 145 kV

4400 pf with tolerance + 10% and 5%

Shall not exceed 200 pf Shall not exceed 20 us within 80% to 150% of rated capacitance less than 40 Ohms Two Two

5 6

20 kV- \/3/110 -\/3V 20 kV- \/3/110 -\/3V 50 VA 50 VA

9 10 11

(ii) Winding II (VA) Accuracy Class : (i)Winding I (VA) (ii) Winding II (VA) Voltage factor for winding I Voltage factor for winding II IS to which CVTs conform. IS to which Insulating Oil conform.

50 VA

50 VA

0.2 for metering 0.2 for metering 1.2 Cont. & 1.5 for 30 secs. 1.2 Cont. & 1.5 for 30 secs. IS 3156 with latest amendment IS 335 with latest amendment

Minimum Acceptable Specification of Single Phase Voltage Transformer for Metering:


Sr. No 1 2 3 4 5 6 7 Particulars Highest System Voltage (kV rms) Transformation ratio. 33 kV 11 kV

36 12 33kV/ V3/ 11 kV/110 V 110/ V3 Number of windings. Two Two Rated output/ burden (VA) per winding /phas 50 50 Accuracy class. (At 10 to 100% of VA burde 0.2 0.2 Rated voltage factor and duration. 1.2 continuous & 1.5 for 30 secs. IS to which PT conforms. 3156 with latest amendment