SR750 & SR760 FEEDER MANAGEMENT RELAYS

Total Protection, Control, Metering & Monitoring of Utility Distribution Feeders

Presentation Overview
k

Requirements k Meeting the Needs k Cost Analysis

Our Strengths k Key Benefits k Ordering

Customer Requirements
k

Protection k Control k Monitoring k Metering

Communication k Inputs & Outputs k User Interface k Reliability

Meeting the Needs of Protection


k

Phase Timed Overcurrent (51P)


k
k

Voltage Restraint
(12 selectable curves plus 2 Flexcurves)

k k k k

Ground Timed Overcurrent (51N) Phase & Ground Loset Overcurrent (50PL, 50NL) Phase & Ground Hiset Overcurrent (50PH, 50NH) Phase & Ground Directional Control
k k

Zero Sequence (67P) Negative Sequence (67N)

k k k k k

Negative Sequence Instantaneous (46/50) and Time (46/51) Overcurrent Voltage Phase Reversal (47) Negative Sequence Overvoltage (59Q) Undervoltage & Overvoltage (27-1, 27-2, 59-1, 59-2) Underfrequency & Overfrequency (81U-1, 81U-2, 81O-1, 81O-2)
5

Meeting the Needs of Control


k k k

Full Remote/Local Control Manual Close Control 4 ShotAutoreclose (760)


k k

TOC Curves Selection Between Reclosures Current Supervison

k k k k k k

Synchrocheck (Voltage, Phase Angle and Frequency) Cold Load Pickup Power Factor Control Load Shedding & Restoration Control 4 Settings Groups Transfer scheme
6

Cold Load Pickup

Capacitor Switching

Meeting the Needs of Monitoring


k

Event Recorder (Last 128 Events) k Trace Memory (10 x 16 Cycle Captures) k Fault Locator k Breaker Trip & Close Coil Detection k Breaker Failure k VT Failure k Total Breaker Arcing
9

Waveform Analysis

10

Breaker Arcing

11

Meeting the Needs of Metering


k

Individual Voltages & Currents k Real, Reactive & Apparent Power Demand k Real & Reactive Power Costs & Usage k Running & Maximum Demand Levels k Frequency & Power Factor k Synchronizing Voltage & Frequency

12

Meeting the Needs of Communications


k

RS485/RS422 Serial Port (PLC, SCADA, PC, DNP 3.0 etc.) k Front Panel RS232 Program Port k Fully programmable front keyboard with a 40 character display & status indicators

13

Meeting the Needs of Inputs


k

1 analog input channel k Universal Power Supply (ac/dc) k 3 phase CTs & VTs k Zero Sequence ground CT k 14 selectable logic inputs (21 functions)

14

Meeting the Needs of Outputs


k

6 E/M aux relays, 10A Continuous & 30A make/carry k E/M trip, and close relays 20A Continuous & 40A make/carry (0.2s) k 1 solid state, 15A @ 250Vdc for 500ms k 8 analog outputs

15

Meeting the Needs of User Interface


k

Setup Software k Flash Memory for Future or Utility Upgrades or modifications k Fully Programmable keyboard with 40 character display and status indicators k Fast and easy to use k Draw out construction
16

Meeting the Needs of Reliability


k

Extensive IEC & ANSI Testing k Complete Burn-in and testing on Relays k Self Testing k Draw out Case (no external hardware) k Front Door with Gasket and Lock Provision k Heavy Duty Terminals k ISO 9002 Certified, UL, CSA, ACA (Australian Standard) & UK Approvals k Halt testing and CE
17

Cost Analysis
k

Full Protection Package k Full Metering Package complete with Transducers k Time Saving Fast and Easy User Setup k Programmable inputs and outputs k Fault Recording and Simulation Testing

18

Our Strengths
k

Customer Input for Design & Application k High Quality & Dependable Products k Built in Flexibility including Flash Memory k Continuous Upgrading & Windows Software k Full Technical & Applications Service

19

Key Benefits
k

Combines all elements into one, easy to use, reliable, cost effective package: Protection Control Monitoring Metering Communications User Interface

20

Ordering
k k k k k

k k

Specify SR 750 or SR 760 Specify phase current of 5 amp or 1 amp Specify ground current of 5 amp or 1 amp Specify sensitive ground current of 5A or 1A. LO Power Supply range is - DC: 20 to 60V AC: 20 to 48 V @ 48 to 62 Hz HI Power Supply range is - DC: 88 to 300 V AC: 70 to 265 V @ 48 to 62Hz Specify Analog outputs: 0-1mA, 0-5mA, 0-10mA and 420mA Specify Breaker Closed LED: Red or Green