Chilled Water System

Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.acson-international.com.

AP - AHS - 10

www.acson-international.com

2010 Acson International

Chilled Water System Solution


Product Overview Acson Offers : Chilled Water System Air cooled mini chiller series Air cooled Tandem Compressor Mini Chiller Inverter Mini Chiller Chilled Water Fan coil unit Wall Mounted Ceiling Cassette Ceiling Convertible Ceiling Concealed Ducted Blower Hydroaire Controller NIM Networking Control System

1 3 5 11 12 14

Angola Benin Reunion Island Seychelles Tahiti

Barbados

Bangladesh Indonesia Kazakhstan Malaysia Myanmar Nepal Pakistan Sri Lanka

18 21

Czech Republic Denmark Finland Germany Greece Hungary Italy Netherlands Norway Poland Portugal Romania Russian Federation Spain Sweden Turkey United Kingdom

Specifications
Mini Chiller Specifications Chilled Water Fan Coil Unit Specifications

Kuwait Lebanon Qatar Syria United Arab Emirates

S1 S6

Australia Fiji New Caledonia Papua New Guinea

Mini Chiller

R22

AMAC 20/25/30 C/CR A4AC 20/25/30 C A5ACV 30 CR, A5AC 20/25 CR 4.9 - 8.8 AMAC 40/50/60 C/CR A4AC 40/50/60/ C, A4AC 60CR A5ACV 55/75 CR 11.1 - 20.5 AMAC 80/100/120/150 C/CR A4AC 80/100/120/150 C/CR A5ACV 100/135/210 CR 21.6 - 58.6 50Hz 12.6 - 21.3 26.4 - 57.7 50Hz 50Hz 50Hz 9.5 - 16.1 7.3 - 13.2 A5AC 30/40/50/55 CR

Model Range

R407C R410A

Cooling Capacity (kW) Heating Capacity (kW) Electrical Supply

6.4 - 9.7

Fan Coil Unit


Wall Mounted GW series Wall Mounted 301W Ceiling Cassette AW Series Ceiling Cassette AWH Series Ceiling Cassette CW Series Ceiling Exposed CBW Series Ceiling Convertible DW Series Ceiling Concealed CW Series Ceilling Concealed CW-C Series Ducted Split BW Series

Model Range Cooling Capacity (kW) Heating Capacity (kW) Electrical Supply

AWM 07/10/ 15/20 GW 2.34 - 5.28 3.02 - 6.74 50Hz & 60Hz

AWM 301W 2.34 - 5.28 3.02 - 6.74 50Hz & 60Hz

ACK 20/25/30/ 40/50 AW 6.62 - 10.80 8.40 - 12.90 50Hz & 60Hz

ACK 20/25/30/ 40/50 AWH 3.81 - 5.16 10.55 - 13.77 50Hz

ACK 10/15/20 CW 2.34 - 4.25 3.22 - 5.42 50Hz

RCM 07/10/15 CBW 1.90 - 3.08 2.34 - 4.25 50Hz & 60Hz

RCM 20/25/30/ 40/50 DW 5.19 - 13.19 6.45 - 15.10 50Hz & 60Hz

ACC 10/15/20/25/28 CW ACC 30/38/40/50/60 CW 2.9 - 15.8 3.4 - 19.6 50Hz & 60Hz

ACW 200/300/400/ 600 C/H ACW 800/1000/1200 C/H 2.2 - 10.7 3.5 - 19.2 50Hz

ADB 75/100/ 125/150 BW


22.2 - 44 16.5 - 31.2 50Hz

Chilled Water System


Acson International is committed to offer you with the better solution in your air conditioning needs. In the new HydroTech series of chilled water products, Acson International is not just offering you with wide range of chilled water air conditioning equipments, but a better solution from selecting the equipments, designing the water piping systems to providing easy control of the complete chilled water system. This is facilitated by the user friendly computer selection programs and remote monitoring of the operation of complete system through the smart HydroIntel controller. The HydroTech series of chilled water product has incorporated the technology of advanced communicating controls, microprocessor controlled chillers with a wide range and variety of fan coil unit that offers total flexibility. Can be used in variety of climates with systems that are available in two versions, cooling only and heat pump. The refrigerant of the system is confined to within the chiller itself and therefore no refrigerant is circulating throughout the building. This will be no risk of refrigerant leakages in building or risk of poor oil return that will damage compressor caused by poor installation. Multiple compressors in Hydrotech chiller series offers stages capacity control that will offer better efficiency.

The HydroTech series avoids the limitation of piping lengths and bends that exist in Direct Expansion refrigerant system. The chiller can be installed far away from the fan coil units, thus offering flexibility and creativity in the installation site.

The operation of the fan coil units can be managed independently by zones according to similar air conditioning comfort needs.

The HydroTech chiller is equipped with reliable and quality components.

Air Cooled
Acson International offering you the range of air cooled chiller that is suitable for many applications from residential to commercial. The HydroTech chiller is incorporated with the basic necessary components such as circulating water pump, expansion tank, compact brazed plate heat exchanger, differential pressure switch and the microprocessor controller and wired control panel.

Mini Chiller System

Model : AMAC 20/25/30 C/CR A4AC 20/25/30 C/CR A5AC 20/25 CR A5ACV 30CR Capacity : Cooling : 4.9 kW to 8.8 kW Heating : 6.4 kW to 9.7 kW Refrigerant : R-22, R-407C, R-410A

Model : AMAC 40/50/60 C/CR A4AC 40/50/60 C/CR A5ACV 55/75 CR Capacity : Cooling Heating : 11.1 kW to 20.5 kW : 12.6 kW to 21.3 kW

Refrigerant : R-22, R-407C, R-410A

In addition, the selection of the HydroTech chiller could not be more easy than the user friendly yet versatile HydroPro selection softwares for chiller as well as connecting piping. In short, HydroTech Chilled Water Product Range offers you the better solution to your chilled water product needs.

Model : AMAC 80/100/120/150 C/CR A4AC 80/100/120/150 C/CR A5ACV 100/135/210 CR Capacity : Cooling : 21.6 kW to 58.6 kW Heating : 26.4 kW to 57.7 kW Refrigerant : R-22, R-407C, R-410A

Model : A5AC 30/40/50/55 CR Capacity : Cooling Heating : 7.3 kW to 13.2 kW : 9.5 kW to 16.1 kW

Tandem Compressors

Refrigerant : R-410A

Product Range
5 6

Features
Easy Installation and Maintenance
Acson Mini Chiller is fully integrated and equipped with key hydronic components such as expansion tank, water tank, brazed plate heat exchanger and water circulating pump. As all hydronic components are assembled and tested in the factory, installation of additional component on site can be eliminated.

Acson chilled water system has no limitation in piping length unlike Direct Expansion refrigerant system. As long as the water pump head pressure is sufficient to pump the water through the pipe network, the chiller can be installed far away from the fan coil units. Acson Mini Chiller had been designed to support maximum water operating pressure up to 1000kPA. With such pressure, Acson Mini Chiller is enough to support most HVAC application. In the case where the Mini Chiller's built in pump head is insufficient to support the overall friction loss, additional pump can be installed to cater for higher pump head requirement.

Each heat exchanger in the chiller is brazed and tested against leakages through dried air at 30 bars. After that, another process to vacuum the system before it is accurately charged with refrigerant to ensure optimum performance. Thus, it saves the hustles of field charging by installers.

By opening the front panel, one can access and service all the components in the chiller. The chiller is equipped with self diagnosis function which allow the chiller panel to display total of 19 type of faulty occurred in the system by showing different error code on the LCD screen of the panel.

Multistage End Suction Water Pump


Impeller and all movable parts in contact with the water are made of stainless steels.

Diaphragm Expansion Tank


Prevent damage of hydraulic components and cracking of piping due to expansion of hot water in the pipes.

Water Storage Tank Filter Drier


Prevent the compressor from switching ON/OFF too frequently during low load conditions such as night time. NOTE: Model AM4AC/AMAC080 ~ 150C/CR water tank is offered as an optional device. Supported Up To 50 Units Of Chiller Chiller 0 Chiller 1 Chiller 2

Long Piping

Remove dirt and moisture in the refrigerant circuit.

Application
7

Acson Mini Chiller provides flexibility in adding capacity for building extension. This can be done by installing the mini chiller in modular connection. A network of up to 50 chillers is possible to be connected in a system. For ease of controlling and setting, Acson Mini Chiller panel implement Master and Slave function. This function allows user to do the setting at the Master unit only and all the slave unit in the group will follow the same setting.

5 way wire (CM8) Chiller Communication Bus Chiller Panel 0 (Master) Chiller Panel 1 (Slave)

State-Of-The-Art Components
Scroll Compressors are used for the units to offer a quieter and more reliable performance over a wide operating temperature range. (Except AMAC/AM4AC 20 C/CR which uses rotary compressor). For AMAC/AM4AC 30, 40, 50, 60, 80, 100, 120, 150 CR, phase protector is provided to prevent the compressor from rotating in the wrong directions. The chiller panel controller is designed to control the chiller operation. This device allows the user to have customized control for each connected unit. Each chiller will have a chiller control panel that comes as a standard accessory. At the same time, the chiller control panel is able to be installed remotely through the cable up to a distance of 100 meters. Example, the chiller panel can be installed in a centralized plant control room for the building. The chiller control panel has been designed taking into consideration of the user friendly and yet versatile control features. Features: Whole system configuration. Unique parameter settings. Operation status display. Tracing fault record (offer quick troubleshooting solutions). The display is shown in an 8-lines graphical LCD display. There are 8 dedicated keys available in the panel. Menu selection. Navigation on the screen. Modification of the selected value.

The chiller unit has several anti-freeze protection features: 1. Built-in heater in BPHE The BPHE has a strip heater around it to prevent water freezing inside. 2. Anti-Freeze sensor BPHE can avoid the frosting as the anti-freeze sensor will send the signal to cut out the compressor if the water temperature becomes too cold. 3. Water pressure differential switch This protection feature will ensure there is water flow in pipings when the chiller is in operation. Otherwise, the compressor will cut out immediately.
Copeland Compliant Scrolls

For AMAC/A4AC 80~150 C/CR, both compressors will cut in and cut out depending on their accumulative operating time. This sequencing control feature will ensure no single compressor is overload in operation as well as to ensure longer reliability of compressors.

High Efficiency Motor

Gold Aluminum fin is offered as the standard material of the condenser heat exchanger of this series of chiller.

Models AMAC/A4AC 80~150 C/CR has been designed with two separate refrigerant circuits, i.e. it has two compressors. By doing so, the unit has part loading capabilities, i.e. 0-50-100% of rated capacity. This will improve the reliability and energy efficiency of the unit, especially during low loading operations.

Superior Reliability
Acson chillers are equipped with microprocessor controller that will control and regulate the operation of the unit. Besides, the controller that contains the well developed algorithm will provide protection to the chiller by accurately sensing the key temperatures in both the water and refrigerant circuit. Should there be any abnormal reading received by controller, an alarm signal will be sent to chiller panel, followed by protection action plans such as to stop the operation of compressor, condenser fan motor or circulating water pump. The safety protections provided for the Acson chiller are: High & Low Pressure Switches Anti-Freeze Protection Sensor Discharge Temperature Sensor Over Pressure Relief Valve Water Pressure Differential Switch Anti-Freeze Heater on BPHE Compressor Water Pump & Fan Motor Overload Protector 9 The heat exchanger is made of AISI 316 stainless steel plates closely arranged and brazed together to maximize possible heat exchange efficiency.
AISI 316 stainless steel BPHE

Quiet Shutdown Device

Efficient And Performance


10

The new series of Inverter Mini Chillers are specially designed / developed to achieve better system energy saving as well as towards perfect control during part load condition.

The true dual BPHE puts the secondary circuit (water) in contact with 2 primary circuits (refrigerant). So even if one primary circuit is shut off, each secondary channel is still in contact with a primary channel. These advantages have made the product the natural choice for flexible chillers, climate control applications and high- precision systems food cooling cabinets in supermarkets.
Ref.1 Ref.2 Ref.1 Ref.2 Ref.1

water

water

water

water

This new line of innovative air cooled chiller by Acson International was designed with one purpose in mind, which is to offer user with cost and energy saving for users.

Hydrotech Mini Chiller


Usage of higher efficient R-410A rotary compressors in tandem configuration Tight tolerances between moving parts resulting in high compressor volumetric efficiency Minimize mechanical losses Minimize gas flow losses and turbulence Optimize compressor oil return Both compressors will cut in cut out depending on water temperature. This is possibly improving the compressor life cycle as well as the compressor reliability. Combining the Tandem Compressors technology with the algorithm of the microprocessor Acontrol, water tank can be eliminated in most instances.

Inverter compressor is programmed to run at the optimum speed, which is regulated by the input frequency as it can varies according to the heat load requirement.
Water In

Primary Circuit 1

Primary Circuit 2

Compatible with HydroIntel

Water Out

3 steps compressor loading (0%-40%-60%-100%) for A5AC 40 CR & A5AC 50 CR 2 steps compressor loading (0%-50%-100%) for A5AC 30 CR & A5AC 55 CR Usage of single phase power supply compressors and circulating water pump. Offers flexibility to field installation.

Inverter Chiller
12

11

A network up to 50 chillers in a system is possible. Control on the operation of the chillers will be done through the microprocessor controller. The external water piping connection can be made either from the left or right side of the unit.

Chiller Panel comes as the standard controller.

Advantages
Advantages of inverter compressor applications are: Less Start & Stop - Frequency regulated compressor resulting in lesser in the sense of start and stop of compressor, which is greatly reduce the energy consumption. Fast cooling/Heating - Unlike the other conventional systems, inverter compressor has the ability to produce faster cooling/ heating capacity at the frequency higher than the dominant capacity frequency. Better Compressor Reliability - Reliability of inverter compressor is always better since there is lesser ON/OFF of the system especially during the low load condition. Low Starting Surge - Reliability of inverter compressor is always better since there is lesser ON/OFF of the system especially during the low load condition. High & Low Pressure Switches Anti-Freeze Protection Sensor Discharge Temperature Sensor Over Pressure Relief Valve Water Pressure Differential Switch Anti-Freeze Heater on BPHE Compressor, Water Pump Overload Protector Gold Aluminum fin is offered as the standard material of the condenser heat exchanger of this series of chiller.
Room Temperature Set Temperature Time Fast Cooling

To complement the new innovative HydroTech range of air cooled chillers, Acson International is offering an extensive range of chilled water fan coil units that will meet most of indoor application requirements covering residential, light commercial and commercial. The aesthetically attractive decorative fan coil units such as Wall Mounted models, Ceiling Cassette and Ceiling Convertible is compact and ergonomic, the ranges can blend in easily to any interior designs whether it is residential houses, office, restaurant or shops. In addition, the HydroTech chilled water fan coil units are designed with easy installation and easy servicing in mind. The fan coil units also include the microprocessor controller that has built in algorithm to control the operation of the fan coil unit as well as to provide protection to the unit.

Precise & Stable Temperature Control

Room Temperature

Fan speed is now controlled by the built in algorithm, resulting in cost saving since installation of external FSC (Fan Speed Controller) can be exempted. It is regulated at 100%, 70% and 50% based on the ambient and outdoor condensing temperature.

Set Temperature Inverter System Conventional System

Time

Inverter compressor require lower starting torque and thus, resulting in lower starting current.

Chilled Water Fan Coil Units


14

13

Wall Mounted
AWM 05/10/15/20/25 GW Slim and compact Wide capacity range Wide air flow range Incorporated with NanoShield (except AWM301W) Able to communicate with the versatile HydroNIM for fan coil units networking Light weight Detachable and washable air intake grille Microprocessor control Self diagnosis features Automatic air swing Wireless Control as standard Mode selection, fan speed, 24 hours real timers Optional wired controller
OPTIONAL

Ceiling Convertible
RCM 07/10/15 CBW (Ceiling Exposed Only) Ceiling Convertible feature offers flexibility on installation - Installation method of under ceiling or floor standing* 2 way air discharge** ensure better air distribution horizontal air throw and bottom air throw Automatic Air swing* Aesthetically attractive with round profile outlook fits in to any indoor architectural Strong air flow volume and strong air throw distance makes it a perfect choice for light commercial such as restaurant and shop Microprocessor control Able to communicate with the versatile HydroNIM for fan coil units networking Self diagnosis feature Wireless Control as standard Mode selection, fan speed, 24 hours real timers Optional wired controller
* Applicable for RCM30-50DW and ACM15-25EW models only ** Applicable for RCM30-50DW models only

AWM 301 W

STANDARD

RCM 20/25/30/40/50 DW

STANDARD
G18 Wireless Controller SLM Wired Controller AC-5300 Wireless Controller

OPTIONAL

HydroTech Chilled Water


Fan Coil Units Range
STANDARD
G18 Wireless Controller

ACM 15/20/25 EW
G18 Wireless Controller SLM Wired Controller AC-5300 Wireless Controller

OPTIONAL

STANDARD

OPTIONAL

Ceiling Cassette
Netware III Wired Controller

Ceiling Concealed
SLM Wired Controller Netware III Wired Controller

ACK 10/15/20 CW

2 Pipes System: ACK 20/25/30/40/50 AW 4 Pipes System: ACKK 20/25/30/40/50 AWH

3 range of ceiling cassette to be chosen from. - ACK-CW - 570mm (w) x 570mm (l) - ACK-AW - 820mm (w) x 820mm (I) Aesthetically attractive and slim front panel 4 way air discharge to provide better air distribution to room Automatic air swing 4 pipes system is available for model ACK20/25/30/40/50AWH Easy servicing and maintenance Built in high pressure head drain pump - Ability to pump up condensate water to 700mm high Built in water float switch to protect the unit from problems of condensate water overflow Microprocessor control Able to communicate with the versatile HydroNIM for fan coil units networking Self diagnosis feature Wireless Control as standard - Mode selection, fan speed, 24 hours real timers Optional wired controller

ACC 10/15/20/25/30/40/50/60 CW

ACC 28/38 CW

Wide capacity range 4 speed fan motor offers flexibility for installation to suit application Each speed will offer different external static pressure and air flow High External Static Pressure is available up to 18mm Extra secondary drain pan to provide protection against condensate water leaking Availability of various optional duct accessories specially designed to fit to ACC-CW range Microprocessor control Filter adaptor kit of 1 inch is available as optional accessory Able to communicate with the versatile HydroNIM for fan coil units networking Self diagnosis feature Wired Control as standard Mode selection, fan speed selection

15

16

Ceiling Concealed

2 Pipes System: ACW 200/300/400/600/800/1000/1200 C 4 Pipes System: ACW 200/300/400/600/800/1000/1200 CH

Wide capacity range Multiple rooms can be cooled by just 1 unit of ACW Simple design with easy serviceability feature Extremely low height of unit 251mm for complete range Water piping connection can be easily converted from one side to the other Fan motor assembly is not cased, allowing free return or back return or bottom return with optional return plenum Availability of optional extended drain to receive the condensate water dripping from the water piping connection Availability of 4 pipes ACW weries Other optional accessory available: - Wired thermostat - Choice of external static pressure (ESP) - Four types of ESP are available: 0Pa, 30Pa, 60Pa, 80Pa. - PTC (Positive Temperature Coefficient) electric heater - 2 way & 3 way valves

Controller
By adopting the HydroTech chilled water system, the comfort in residential and light commercial buildings such as offices, hospital, restaurant, hotel and shopping complex can be controlled and managed from just one point, that is through the smart HydroIntel Controller. The HydroIntel controller is acting as a center to manage the operation of both the chilled water fan coil units and the chillers. Besides allowing the user to have customized control for each connected unit, the smart HydroIntel controller is also able to manage the overall system operating mode of all units based on the air conditioning system load demand of the building.

Chiller Network BUS

Fan Coil Network BUS

Ducted Blower
These units are design with high air flow and high external static pressure, enables adequate distribution of air to the desired space Multiple rooms can be cooled by just 1 unit of ADB Simple design with easy serviceability feature The robust unit is designed with durability and reliability in mind ADB125/150BW is using the belt driven fan motor and blower fan thus it offers flexibility for upgrading should higher air flow is required ADB150BW is designed to cater for either horizontal air discharge or vertical air discharge

Through the versatile HydroIntel controller, the operation of each equipments in the HydroTech chilled water system connected through the chiller Bus and Acson own proprietary HydroNIM BUS can be managed and controlled.

CHILLER PANEL

CHILLER PANEL

CHILLER PANEL

CHILLER

CHILLER

CHILLER

HydroIntel Controller

CHILLER BUS

A B

Up to 50 units of Chiller

HYDRO BUS HYDRO NIM FCU HYDRO NIM FCU HYDRO NIM FCU

A B

Up to 120 units of FCUs

ADB 75/100/125/150 BW

Optional Accessories
Return Bracket Assembly come with Adaptor
(ACC 10CW - 1 outlet; ACC 15~20CW - 2 outlets)

WIRED CONTROLLER

(ACC10CW~ACC25CW)
Adaptor
Discharge and Return

Y-Joint

Return Grille Assembly come with Adaptor

Features
(Ch 0)
Whenever a fault occurred in either the chiller or fan coil unit, a signal will be sent to HydroIntel controller and an alarm message will appear on the LCD, showing type of alarm, alarm occurred time, date and unit. This will greatly ease the troubleshooting process and thus reduce the valuable time of service technicians. As soon as the fault is being solved, the alarm will automatically dissolve from the LCD. 18

Alarm 1

(Front View)

Supply Grille Assembly come with Adaptor

Comp 1 overload
01/01/00 12.00am

(Side View)

(Front View)

17

Heat Treshold
Chiller to operate at Heat Mode 0 1 2 3 4 5 6 7 8 9 10

Chiller to operate at Cool Mode

Cool Treshold
If the priority setting is being preset to fan coil unit, the operating mode of the complete HydroTech Chilled water system can be synchronized to operate under one same mode. This is achievable through the unique feature called Threshold Value Setting HydroIntel Controller can command chiller operating mode to switch from current operating mode if the threshold value is meet. Example, In a network of 10 fan coil units that is currently operating in COOL mode and a threshold of 60% was set for COOL mode and threshold of 50% was set for HEAT mode. Should 6 of the fan coil units are requesting for HEAT mode then the threshold for HEAT is crossed. Signal will be sent by HydroIntel to chiller BUS to switch the operating mode of all chillers to HEAT mode. Requirement of users will be met.

Depending on the application requirement, the HydroIntel controller offers the flexibility to allow user to set the priority on the operation of fan coil unit and Chiller in a complete HydroTech chilled water product system. If priority is set to fan coil unit, the chiller will be forced to OFF if all fan coil units are OFF. If Chiller Priority is being set, all fan coil units will be OFF if chillers are OFF.

When there is power failure occurs during operation, HydroIntel Controller will load the last state memory from EEPROM after power On reset. Besides, extra memory space inside the HydroIntel controller will allow user to view the previous alarm records even though its have been dissolved. This useful information will benefit the service technician to view the history of maintenance record done to the unit.

Features
At the same time, the HydroIntel controller allows setting up to five sets of 7 days programmable operating schedules (2 On/Off timer per day) for each fan coil unit.
Unit
ACC ACK RCM2 RCM1 AWM

HOLIDAY SETTINGS
Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5

Set Holiday 1
Month Day Duration : 1 : 1 : Disable

The operation of the chiller and each fan coil unit can be preset to operate and to stop at different time schedule and at different day of a week. Taking consideration of the fact that certain rooms in a building will be empty at certain period of the day, setting timer to On and to Off the operation of units in those areas will greatly reduce the energy cost of the building.

ACC

A HydroTech chilled water product system with key parameters that were set by personnel to optimize operating conditions will need to be protected against any unauthorized disturbance or changes. The built in Password Settings feature will prevent the losing of key parameter settings in the HydroIntel controller.

ACK RCM 2

RCM 1 AWM

HydroIntel controller will turn into low power mode during electricity power breakdown. It will operate based on the built in backup battery and only one timer and interrupt is active. CPU operation is Off and no display on LCD as well for energy saving purpose.

For easy serviceability and maintenance, HydroIntel Controller's is able to display the key parameter such as defrost and compressor discharge sensor temperature, water in/out temperature, status of compressor On/Off, Cool/Heat mode water in temperature, etc. Thus, it reduces the cumbersome of requiring the service technicians to physically go to site of chiller installation to do the troubleshooting process.

8.00 am

9.00 am

10.00 11.00 12.00 am am am

1.00 pm

2.00 pm

3.00 pm

4.00 pm

5.00 pm

6.00 pm

7.00 pm

Time

RTC will always appear at the summary pages and the user is able to set the time and date. 20

User can also check the compressor run time of chiller in HydroIntel Controller. It will provide a guideline as well as posting a reminder for requirement of routine system service.

19

HydroNIM Networking
For multiple fan coil unit installation in an office, a centralised controlled operation can be achieved through the Acson proprietary HydroNIM networking system. Network Interface Module (HydroNIM) is a networking system which enables communication among Acson air conditioners. With the HydroNIM, all your air conditioning systems can be controlled with just a single controller giving you boundless benefits:

Control System (optional)


BENEFITS Ultimate convenience. No more individually controlling air conditioning units Quick and easy zone control from the master control unit Better control of air conditioning systems operating conditions HydroNIM utilizes master-slave type system whereby the master node will issue commands to each of the slave nodes.

A new developed thermostat series, AC8100A is now available to be ordered as Chilled Water Fan Coil unit controller, inclusive of AC8100A and AC8000C. Its adopt micro-computer technology and is designed for the easier of installation. AC8100A practises the most simple and conventional installation method where it consists of a wired controller and a power board. Both of its are attached together while being installed. Same with AC8100A, AC8000C also consist of a wired controller and a power board, but the power board is attached to the fan coil unit while the wired controller will be installed away from it. Moreover AC8000C has the networking capability, with compatibility to the Network Interface Module (NIM); better control over whole operating system can be achieved as it offers quick and easy zone control from the master operating unit.

For HydroNIM PC only


HydroNIM HydroNIM

AC8100A Features:
Four Operating Modes: Cool/Fan/Heat/Auto Variable Indoor Fan Speed Selection: High /Medium/Low/Auto Selectable Function: 1) Cooling only 2) Cooling and Heating (2 pipes) * 3) Cooling and Heating (4 pipes) LCD display LED indication of power supply 7 days programmable timer Real time clock Selectable room temperature / Set temperature display (in C or F) Temperature setting range from 16C to 30C (60F to 80F)
* Standard is with 4 pipes setting. For 2 pipes application, user might need to do jumper setting.

HydroNIM

HydroNIM

HydroNIM

HydroNIM

HydroNIM

HydroNIM

HydroNIM

Additional Features for AC8000C:


Networking capability Last state memory backup Auto random restart AC8000C is compatible with Smart Manager and NIM PC. By using RS485 cable, it can easily form a NIM bus as described in schematic diagram above

Features
With HydroNIM PC, a personal computer will act as a centralised unit for both controlling and monitoring of all the air conditioning units in the HydroNIM network. For controlling, settings can be set from the PC and send out to the system for execution. While for monitoring, there is a graphical user interface for displaying the status of each unit. The HydroNIM PC provides a Global Control Hub that offers control for better system management: 21 Easy to operate full graphical user interface. Control units globally, as a group, or as individual units. Configure a super master unit. Support up to 42 On/Off timers per week. Real time monitoring of online units. Error diagnostic and alerting features for all units. Data logging and printing ability. Database to store unit location. Login protected by password.

HydroIntel

NIM PC

OR RS485 AC8100A FCU AC8000C FCU AC8000C FCU More FCUs

AC8000C

AC8000C (Network Controller)

LCD Panel

LCD Panel

LCD Panel

22

Mini Chiller Specifications


AMAC20C - AMAC60C (Cooling Only, R-22)
MODEL Btu/h W W V/Ph/Hz AMAC20C 18000 5275 2669 AMAC25C 23500 6887 2730 220-240 / 1 / 50 R-22 CAPILLARY TUBE HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME L / ft3 22 / 0.78 0 - 100% mm/in mm/in mm/in kg/lb dBA l/s / m3/hr 116 / 256 57 0.25 / 0.9 800 / 31.5 1160 / 45.7 460 / 18.1 123 / 271 57 0.33 / 1.2 188 / 414 58 0.42 / 1.51 188 / 414 59 0.56 / 2.0 1410 / 55.5 1160 / 45.7 460 / 18.1 190 / 417 59 0.67 / 2.4 196 / 432 59 0.74 / 2.7 AMAC30C 30000 8790 3520 AMAC40C 39500 11580 4508 AMAC50C 48500 14210 5150 380-415 / 3 / 50 AMAC60C 54000 15830 5780

AMAC80C - AMAC150C (Cooling Only, R-22)


MODEL Btu/h W W V/Ph/Hz AMAC80C 85000 24910 9050 AMAC100C 95000 27840 10800 380-415 / 3 / 50 R-22 TXV HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME L/ ft3 mm/in mm/in mm/in kg/lb dBA l/s/ m /hr mm/in
3

AMAC120C 116000 34000 11900

AMAC150C 138000 40450 13740

NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL

NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL

1245 / 49.0 1500 / 59.1 900 / 35.4 340 / 750 63 1.22 / 4.4 340 / 750 63 1.36 / 4.9 BSPT 460 / 1014 67 1.67 / 6.0 31.75 / 1.25 NA NA 0 - 50 - 100% 1800 / 70.9 1150 / 45.3 540 / 1190 69 2.00 / 7.2

mm/in

BSPT 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

AMAC20CR - AMAC60CR (Heatpump, R-22)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY COOLING NOMINAL TOTAL INPUT POWER HEATING POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s / m3/hr l/s / m3/hr mm/in L / ft3 22 / 0.78 0 - 100% 116 / 256 57 0.25 / 0.9 0.31 / 1.1 800 / 31.5 1160 / 45.7 460 / 18.1 123 / 271 57 0.32 / 1.2 0.35 / 1.3 128 / 282 58 0.39 / 1.4 0.44 / 1.6 195 / 430 59 0.56 / 2.0 0.56 / 2.0 Btu/h W Btu/h W W W V/Ph/Hz AMAC20CR 18000 5360 22000 6570 2610 2700 AMAC25CR 23000 6740 25000 7330 2800 2630 220-240 / 1 / 50 R-22 CAPILLARY TUBE 1410 / 55.5 1160 / 45.7 460 / 18.1 197 / 433 59 0.61 / 2.2 0.61 / 2.2 203 / 448 61 0.74 / 2.7 0.83 / 3.0 AMAC30CR 27500 8060 35000 10260 3450 3430 AMAC40CR 38000 11140 43000 12602 4300 4450 AMAC50CR 44000 12900 50000 14650 5250 5150 380-415 / 3 / 50 AMAC60CR 53000 15530 59000 17292 6270 5960

AMAC80CR - AMAC150CR (Heatpump, R-22)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in L / ft3 340 / 750 63 1.13 / 4.05 1.13 / 4.05 1500 / 59.1 900 / 35.4 340 / 750 63 1.33 / 4.8 1.47 / 5.3 BSPT NA NA 0 - 50 - 100% 480 / 1058 67 1.67 / 6.0 1.79 / 6.4 31.75 / 1.25 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz AMAC80CR 80000 23450 95000 27840 8650 8900 AMAC100CR 95000 27840 105000 30770 11200 10500 380-415 / 3 / 50 R-22 CAPILLARY TUBE 1245 / 49.0 1800 / 70.9 1150 / 45.3 560 / 1235 69 2.00 / 7.2 2.10 / 7.6 AMAC120CR 113000 33118 120000 35169 11650 11880 AMAC150CR 138000 40450 132000 38686 13840 14530

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

BSPT 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

NOTES: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : A) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. B) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1M IN FRONT AND 1M BELOW THE UNIT.

NOTE : 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S1

S2

Mini Chiller Specifications


A4AC20C - A4AC60C (Cooling Only, R-407C)
MODEL Btu/h W W V/Ph/Hz A4AC20C 21000 6154 2617 A4AC25C 23000 6740 2960 220-240 / 1 / 50 R-407C CAPILLARY TUBE HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME L/ ft3 22 / 0.78 0 - 100% mm/in mm/in mm/in kg/lb dBA l/s / m3/hr mm/in 116 / 256 57 0.29 / 1.0 800 / 31.5 1160 / 45.7 460 / 18.1 123 / 271 57 0.32 / 1.2 188 / 414 58 0.38 / 1.4 188 / 414 59 0.53 / 1.9 1410 / 55.5 1160 / 45.7 460 / 18.1 190 / 417 59 0.64 / 2.3 196 / 432 59 0.7 / 2.5 A4AC30C 26900 7880 3770 A4AC40C 38500 11280 4700 A4AC50C 47500 13920 5450 380-415 / 3 / 50 A4AC60C 50000 14650 6050

A4AC80C - A4AC150C (Cooling Only, R-407C)


MODEL NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME
L/ ft3

A4AC80C Btu/h W W V/Ph/Hz 80000 23450 9600

A4AC100C 90000 26380 11400

A4AC120C 115000 33700 11740

A4AC150C 137000 40150 14490

NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL

380-415 / 3 / 50 R-407C TXV

mm/in mm/in mm/in kg/lb dBA


l/s/ m3 /hr

1245 / 49.0 1500 / 59.1 900 / 35.4 340 / 750 63 1.14 / 4.1 340 / 750 63 1.25 / 4.5 BSPT 460 / 1014 67 1.67 / 6.0 31.75 / 1.25 NA NA 0 - 50 - 100% 1800 / 70.9 1150 / 45.3 540 / 1190 69 2.00 / 7.2

BSPT 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41

mm/in

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

A4AC60CR (Heatpump, R-407C)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s / m3/hr l/s / m3/hr mm/in L / ft3 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz A4AC60CR 51000 15000 60000 17800 6530 6280 380-415 / 3 / 50 R-407C CAPILLARY TUBE 1410 / 55.5 1160 / 45.7 460 / 18.1 203 / 448 61 0.71 / 2.6 0.84 / 3.0 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41 0 - 100%

A4AC80CR - A4AC150CR (Heatpump, R-407C)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in L / ft3 340 / 750 63 1.03 / 3.7 1.03 / 3.7 1500 / 59.1 900 / 35.4 340 / 750 63 1.23 / 4.41 1.35 / 4.84 BSPT NA NA 0 - 50 - 100% 460 / 1014 67 1.67 / 6.0 1.79 / 6.4 31.75 / 1.25 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz A4AC80CR 74000 21700 90000 26400 9200 9500 A4AC100CR 87500 25640 96000 28140 11300 11300 380-415 / 3 / 50 R-407C TXV 1245 / 49.0 1800 / 70.9 1150 / 45.3 540 / 1190 69 2.00 / 7.2 2.10 / 7.6 A4AC120CR 110000 32240 118000 34600 12200 12300 A4AC150CR 130000 38100 144000 42200 15500 15700

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S3

S4

Mini Chiller Specifications


A5AC020CR - A5AC055CR (Heatpump, R-410A)
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in CAST IRON / STAINLESS STEEL L / ft3 22 / 0.78 0 - 100% 0 - 50 - 100% 128 / 282 58 0.23 / 0.86 0.32 / 1.16 CAPILLARY TUBE 791 / 31.1 1160 / 45.7 460 / 18.1 128 / 282 59 0.28 / 1.00 0.35 / 1.25 790 / 31.1 1059 / 41.7 460 / 18.1 128 / 282 59 0.42 / 1.5 0.42 / 1.5 BSPT COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz A5AC020CR 15700 4610 21500 6300 2620 2590 A5AC025CR 19400 5690 25000 7300 2830 2790 A5AC030CR 24800 7270 32500 9500 3830 3630 R-410A CAPILLARY TUBE & TXV 1410 / 55.5 1059 / 41.7 460 / 18.1 195 / 430 59 0.50 / 1.8 0.50 / 1.8 25.4 / 1 NA NA 0 - 40 - 60 - 100% 0 - 50 - 100% 195 / 430 59 0.60 / 2.15 0.60 / 2.15 1410 / 55.5 1059 / 41.7 460 / 18.1 195 / 430 61 0.75 / 2.7 0.75 / 2.7 A5AC040CR 34100 10000 43000 12600 5000 4650 A5AC050CR 41600 12200 48000 14100 5310 5150 A5AC055CR 45000 13200 55000 16100 5490 5440 220-240 / 1 / 50 220-240 / 1 / 50 or 380-415 / 3 / 50

Chilled Water Fan Coil Specifications


ACK20AW - ACK50AW (Ceilling Cassette A Series)
MODEL NOMINAL TOTAL COOLING CAPACITY ACK20AW ACK25AW ACK30AW ACK40AW ACK50AW 22500 25500 30000 33500 36500 Btu/h 6620 7500 8800 9950 10800 W 16700 18400 21800 24200 26300 Btu/h NOMINAL SENSIBLE COOLING CAPACITY 4900 5400 6400 7100 7700 W 28500 32000 37500 40500 44000 Btu/h NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 12900 8400 9500 11000 12000 W 50HZ 511 / 1083 364 / 771 383 / 812 433 / 918 483 / 1024 l/s / CFM HIGH NOMINAL AIR FLOW 467 / 989 314 / 665 328 / 695 367 / 777 425 / 901 l/s / CFM MEDIUM 428 / 906 297 / 630 297 / 630 336 / 712 372 / 789 l/s / CFM LOW 8.19 5.02 5.68 6.65 7.53 USGPM NOMINAL WATER FLOW RATE 30.97 19.00 21.55 25.23 28.52 LITRES/M 220-240/1/50 V/Ph/Hz POWER SOURCE 253 127 151 164 192 W TOTAL INPUT POWER 40000 24000 26000 29500 35000 Btu/h NOMINAL TOTAL COOLING CAPACITY 11720 7030 7620 8640 10250 W 42000 30000 32000 36000 39000 Btu/h NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 12310 8790 9380 10550 11430 W 60HZ 492 / 1040 350 / 740 369 / 779 416 / 879 468 / 989 l/s / CFM HIGH NOMINAL AIR FLOW 7.49 5.51 5.81 6.70 7.31 USGPM NOMINAL WATER FLOW RATE 28.33 20.83 22.00 25.33 27.67 LITRES/M 208-230/1/60 V/Ph/Hz POWER SOURCE 312 132 155 198 306 W TOTAL INPUT POWER 305 / 12.0 ( 355 / 13.9 ) HEIGHT mm/in 824 / 32.4 ( 930 / 36.6 ) WIDTH mm/in UNIT DIMENSION - ( ) WITH PANEL 824 / 32.4 ( 930 / 36.6 ) DEPTH mm/in ( 25+4 ) / ( 55.1+8.8 ) ( 36+4 ) / ( 79.3+8.8 ) ( 38+4 ) / ( 83.7+8.8 ) ( 42+4 ) / (92.5+8.8 ) ( 44+4 ) / ( 97.0+8.8 ) kg/lb UNIT WEIGHT ( UNIT + PANEL ) 53 / 52 / 50 42 / 39 / 37 45 / 42 / 40 49 / 45 / 43 51 / 48 / 46 dBA SOUND PRESSURE LEVEL ( H/M/L ) 69 / 10 25 / 3.6 31 / 4.5 42 / 6 52 / 7.6 HEAD LOSS (COOLING) kPa / psi 64 / 9.3 21 / 3.1 27 / 3.9 35 / 5.1 45 / 6.6 HEAD LOSS (HEATING) : 50C kPa / psi 3/4" BSP FEMALE UNION CONNECTION Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

A5ACV030CR - A5ACV135CR (Inverter Heatpump, R-410A)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in L / ft3 0 - 100% ELECTRONIC EXPANSION VALVE (EXV) 790 / 31.1 1160 / 45.6 460 / 18.1 128 / 282 58 0.3 / 1.3 0.4 / 1.5 1410 / 55.5 1160 / 45.6 460 / 18.1 195 / 430 62 1.3 / 4.8 0.8 / 2.7 1460 / 57.5 1150 / 45.3 550 / 21.7 200 / 440 65 0.9 / 3.4 1.0 / 3.7 NA NA 0 - 50 - 100% 0 - 50 - 100% 0 - 20 - 40 - 60 - 100% 1245 / 49 1500 / 59 900 / 35 405 / 893 63 1.3 / 4.8 1.4 / 5.0 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz A5ACV30CR 27000 7910 31900 9350 5370 4370 220-240 / 1 / 50 A5ACV55CR 50000 14700 53200 15600 7350 5640 A5ACV75CR 70000 20500 72700 21300 9050 7650 R-410A EXV / CAPILLARY TUBE 1245 / 49 1800 / 70 1150 / 45 525 / 1157 67 1.8 / 6.6 2.0 / 7.1 1786 / 70 2093 / 82 1192 / 47 642 / 1415 67 2.7 / 9.6 2.9 / 10.3 BSPT 38.10 / 1.5 A5ACV100CR 95000 27800 96600 28300 12000 11000 380-415 / 3 / 50 A5ACV135CR 131500 38540 136800 40100 15750 15700 A5ACV210CR 200000 58600 196900 57700 22300 20500

ACK20AWH - ACK50AWH (4 Pipies Ceilling Cassette)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW Cooling 50HZ NOMINAL WATER FLOW RATE Add.Heat Exch Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M USGPM LITRES/M V/Ph/Hz W HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 70C CONNECTION mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ( 25+4 ) / ( 55.1+8.8 ) ( 36+4 ) / ( 79.3+8.8 ) 42 / 39 / 37 4 / 0.5 5 / 0.7 45 / 42 / 40 4 / 0.5 6 / 0.8 122 138 ACK20AWH 13000 3810 11600 3400 36000 10550 364 / 771 314 / 665 297/ 630 2.90 10.92 4.00 15.12 ACK25AWH 13500 3960 12000 3520 37500 10990 383 / 812 328 / 695 297 / 630 3.00 11.35 4.18 15.75 ACK30AWH 15500 4630 13900 4070 42500 12510 433 / 918 367 / 777 336 / 712 3.52 13.27 4.76 17.93 220-240/1/50 153 305 / 12.0 ( 355 / 13.9 ) 824 / 32.4 ( 930 / 36.6 ) 824 / 32.4 ( 930 / 36.6 ) ( 38+4 ) / ( 83.7+8.8 ) ( 42+4 ) / (83.6+8.8 ) 49 / 45 / 43 5 / 0.7 7/1 3/4" BSP FEMALE UNION 51 / 48 / 46 6 / 0.8 9 / 1.2 ( 44+4 ) / ( 97+8.8 ) 53 / 52 / 50 6 / 0.9 9 / 1.3 184 232 ACK40AWH 17100 5010 15000 4400 45500 13480 484 / 1024 425 / 901 372 / 789 3.80 14.37 5.10 19.32 ACK50AWH 17500 5160 15500 4540 46500 13770 511 / 1083 467 / 989 428 / 906 3.92 14.80 5.20 19.73

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

BSPT 31.75 / 1.25

POWER SOURCE TOTAL INPUT POWER

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 70C (158F), LEAVING WATER TEMP. : 75C (167F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

S5

S6

Chilled Water Fan Coil Specifications


ACK10CW - ACK20CW (Ceilling Cassette C Series)
MODEL NOMINAL TOTAL COOLING CAPACITY Btu/h W Btu/h W Btu/h W HIGH NOMINAL AIR FLOW MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ( 22+2 ) / (48.5+4.4) 44 / 43 / 42 67 / 9.8 62 / 9 51.00 1.76 6.70 ACK10CW 8000 2340 6700 1970 11000 3220 184 / 390 175 / 371 165 / 350 3.13 11.75 220-240/1/50 75.00 250 / 9.8 ( 295 / 11.6 ) 570 / 22.4 ( 640 / 25.2 ) 570 / 22.4 ( 640 / 25.2 ) ( 23+2 ) / ( 50.6+4.4 ) 44 / 42 / 41 69 / 9.9 71 / 10.2 3/4" BSP FEMALE UNION 47 / 46 / 44 69 / 10 71.2 / 10.3 78.00 ACK15CW 14000 4100 10400 3060 17500 5120 ACK20CW 14500 4250 11100 3240 18500 5420 203 / 430 193 / 409 184 / 390 3.21 12.18 NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C)

Chilled Water Fan Coil Specifications


RCM20DW - RCM50DW (Ceilling Convertible)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW HIGH NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION HEIGHT WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi RCM20DW 17700 5190 13700 4000 22000 6450 264 / 560 238 / 505 189 / 400 3.92 14.84 96.00 17700 5190 22000 6450 264 / 560 3.92 14.84 104.00 214 / 8.4 RCM25DW 20800 6100 15000 4400 25900 7590 297 / 630 293 / 620 262 / 555 4.62 17.49 130.00 20800 6100 25900 7590 297 / 630 4.62 17.49 163.00 1214 / 47.8 43 / 94.8 50 / 47 / 40 54 / 53 / 50 46 / 6.6 56 / 8.1 39 / 5.7 48 / 7 RCM30DW 24600 7210 17700 5190 28000 8210 329 / 697 324 / 687 307 / 650 5.46 20.67 220-240/1/50 132.00 24600 7210 28000 8210 329 / 697 5.46 20.67 208-230/1/60 163.00 RCM40DW 31200 9140 25600 7500 42300 12400 451 / 956 428 / 908 419 / 889 6.91 26.16 240.00 31200 9140 42300 12400 451 / 956 6.91 26.16 306.00 249 / 9.8 1714 / 67.5 670 / 26.4 45 / 99.2 70 / 154.3 51 / 50 / 48 54 / 53 / 52 54 / 53 / 52 49 / 7.2 24.0 / 3.5 38 / 5.5 43 / 6.2 22 / 3.1 32 / 4.6 3/4" BSP FEMALE ADAPTOR RCM50DW 45000 13190 31400 9200 51500 15090 500 / 1059 483 / 1023 451 / 956 9.99 37.82 240.00 45000 13190 51500 15090 500 / 1059 9.99 37.82 306.00 50HZ

50HZ

60HZ

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.

RCM07CBW - RCM15CBW (Ceilling Exposed)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW 50 / 60HZ NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz w mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi 45 / 42 / 37 9 / 1.4 7.0 / 1.01 824 / 32.4 33 / 72.8 46 / 43 / 38 15 / 2.2 13 / 1.8 3/4" BSP FEMALE ADAPTOR 49.00 RCM07CBW 6500 1910 5000 1460 8000 2340 94 / 200 82 / 173 71 / 150 1.45 5.49 RCM10CBW 8500 2490 6700 1960 11000 3220 142 / 300 134 / 280 119 / 250 1.89 7.15 220-240/1/50 , 208-230/1/60 50.00 235 / 9.3 666 / 26.2 1174 / 46.2 35 / 77.2 47 / 44 / 39 5 / 0.7 4 / 0.5 81.00 RCM15CBW 10500 3080 8600 2520 14500 4250 190 / 400 156 / 330 139 / 292 2.33 8.82

RCM15EW - RCM25EW (Ceiling Convertible)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 50HZ NOMINAL AIR FLOW HIGH MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi 50 / 43 / 41 27 / 4.0 24 / 3.5 101.00 ACM15EW 15500 4540 12700 3720 19500 5720 236 / 500 213 / 450 189 / 400 3.43 12.98 ACM20EW 20300 5950 15400 4510 25000 7330 274 / 580 250 / 530 231 / 490 4.49 17.00 220-240/1/50 109.00 212 / 8.3 1090 / 42.9 630 / 24.8 27 / 59.5 53 / 51 / 49 48 / 7.0 42 / 6.1 1/2" BSP FEMALE ADAPTOR 56 / 51 / 44 57 / 8.3 50 / 7.3 113.00 ACM25EW 21000 6150 16200 4750 28000 8210 293 / 620 269 / 570 245 / 520 4.67 17.68

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. RCM20/025DW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT. RCM30/040/050DW : 1 m IN FRONT AND 1m BELOW THE VERTICAL CENTRE LINE OF THE UNIT (JIS B 8615). MCE007-015CBW: 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.

S7

S8

Chilled Water Fan Coil Specifications


ACC10CW - ACC28CW (Ceiling Concealed)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW HIGH NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER EXTERNAL STATIC ( H/M/L ) UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION HEIGHT WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mmAq mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ACC10CW 9900 2900 7000 2050 11500 3370 142 / 300 123 / 260 104 / 220 2.20 8.33 67.60 9900 2900 11500 3370 142 / 300 2.20 8.33 78.00 5/4/3 261 / 10.3 765 / 30.1 411 / 16.2 17 / 37.5 33 / 30 / 26 11 / 1.5 9 / 1.3 ACC15CW 11600 3400 10600 3100 15000 4400 241 / 510 208 / 440 170 / 360 2.55 9.65 ACC20CW ACC25CW 22500 6590 15800 4620 29000 8500 344 / 730 340 / 720 274 / 580 4.98 18.85 165.00 22500 6590 29000 8500 382 / 810 4.98 18.85 219.00 6/4/3 261 / 10.3 1200 / 47.2 411 / 16.2 25 / 55.1 40 / 39 / 36 32 / 4.7 28 / 4 ACC28CW 26000 7620 18200 5330 33000 9670 382 / 810 363 / 770 335 / 710 5.77 21.84 273.00 18000 5280 12600 3690 23000 6740 330 / 700 321 / 680 293 / 620 4.00 15.14 220-240/1/50 97.20 141.00 11600 18000 3400 5280 15000 23000 4400 6740 330 / 700 344 / 730 2.55 4.00 9.65 15.14 208-230/1/60 114.00 165.00 5/4/2 7/6/3 261 / 10.3 261 / 10.3 905 / 35.6 1065 / 41.9 411 / 16.2 411 / 16.2 21 / 46.3 22 / 48.5 37 / 34 / 29 38 / 36 / 34 24 / 3.5 20 / 2.9 20 / 2.9 17 / 2.5 3/4" BSP FEMALE ADAPTOR 50HZ

Chilled Water Fan Coil Specifications


ACW200C - ACW1200C (Ceilling Concealed)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60C) HIGH NOMINAL AIR FLOW MEDIUM LOW HIGH MEDIUM LOW HIGH MEDIUM LOW HIGH MEDIUM LOW HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa NOMINAL WATER FLOW RATE HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 60C CONNECTION Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM l/s l/s l/s CFM CFM CFM m3h m3h m3h mmAq mm/in mm/in mm/in kg/lb dBA USGPM LITRES/M kPa / psi kPa / psi ACW200C 7507 2200 5930 1738 11942 3500 109 / 230 73 / 153 53 / 112 109 73 53 230 153 112 390 260 190 251 / 9.88 714 / 28.11 490 / 19.29 19 / 41.9 37 / 34 / 31 1.80 6.80 14.6 / 2.12 14.6 / 2.12 ACW300C 10919 3200 8049 2359 17402 5100 148 / 312 103 / 218 67 / 142 148 103 67 312 218 142 530 370 240 251 / 9.88 884 / 34.8 490 / 19.29 20 / 44.1 38 / 35 / 31 2.50 9.45 12 / 1.74 12 / 1.74 ACW400C 14979 4390 11062 3242 24909 7300 212 / 447 137 / 289 95 / 200 212 137 95 447 289 200 760 490 340 251 / 9.88 1014 / 39.92 490 / 19.29 26 / 57.3 41 / 36 / 33 3.40 12.85 21.6 / 3.13 21.6 / 3.13 ACW600C 21019 6160 15017 4401 33985 9960 290 / 612 217 / 459 139 / 294 290 217 139 612 459 294 1040 780 500 8.16 / 6.12 / 3.06 251 / 9.88 1214 / 47.8 490 / 19.29 30 / 66.1 47 / 44 / 38 4.80 18.14 38.2 / 5.54 38.2 / 5.54 ACW800C 26649 7810 20609 6040 44631 13081 395 / 835 304 / 641 206 / 436 395 304 206 835 641 436 1420 1090 740 251 / 9.88 1464 / 57.64 490 / 19.29 41 / 90.4 47 / 44 / 39 6.10 23.06 18.4 / 2.67 18.4 / 2.67 ACW1000C 30129 8830 21868 6409 50431 14780 451 / 953 317 / 671 231 / 489 451 317 231 953 671 489 1620 1140 830 251 / 9.88 1564 / 61.57 490 / 19.29 44 / 97.0 49 / 46 / 40 6.90 26.08 21 / 3.05 21 / 3.05 ACW1200C 36510 10700 26488 7763 65411 19171 568 / 1200 417 / 882 284 / 600 568 417 284 1200 882 600 2040 1500 1020 251 / 9.88 1824 / 71.81 490 / 19.29 46 / 101.4 49 / 45 / 42 8.50 32.13 32.7 / 4.74 32.7 / 4.74

For Conversion purpose

60HZ

-NAEXTERNAL STATIC ( H/M/L )

8/7/6 285 / 11.3 997 / 39.3 600 / 23.7 38 / 83.8 41 / 38 / 34 24 / 3.5 22 / 3.2

3/4" BSP FEMALE ADAPTOR

NOTES : 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.

ACW200H - ACW1200H (Ceilling Concealed)


MODEL ACW200H Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM mmAq HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa NOMINAL WATER FLOW RATE - 3 ROWS mm/in mm/in mm/in kg/lb dBA USGPM LITRES/M USGPM LITRES/M kPa / psi kPa / psi kPa / psi kPa / psi 251 / 9.9 714 / 28.1 490 / 19.3 20 / 44.1 37 / 34 / 31 1.80 6.80 1.10 4.16 14.6 / 2.12 14.6 / 2.12 12 / 1.74 12 / 1.74 251 / 9.9 884 / 34.8 490 / 19.3 24 / 52.9 38 / 35 / 31 2.50 9.45 1.10 4.16 12 / 1.74 12 / 1.74 13.5 / 1.96 13.5 / 1.96 251 / 9.9 1014 / 39.9 490 / 19.3 28 / 61.7 41 / 36 / 33 3.40 12.85 1.10 4.16 21.6 / 3.13 21.6 / 3.13 14.8 / 2.15 14.8 / 2.15 7268 2130 5742 1683 4606 1350 101 / 212 70 / 147 51 / 106 ACW300H 10578 3100 7798 2285 7780 2280 142 / 300 98 / 206 64 / 136 ACW400H 14536 4260 10735 3146 10953 3210 209 / 441 131 / 277 92 / 195 ACW600H 20405 5980 14578 4273 14638 4290 281 / 594 215 / 453 137 / 289 8.16 / 6.12 / 3.06 251 / 9.9 1214 / 47.8 490 / 19.3 32 / 70.5 47 / 44 / 38 4.80 18.14 1.10 4.16 38.2 / 5.54 38.2 / 5.54 20.7 / 3 20.7 / 3 3/4" BSP FEMALE ADAPTOR 251 / 9.9 1464 / 57.6 490 / 19.3 44 / 97 47 / 44 / 39 6.10 23.06 1.10 4.16 18.4 / 2.67 18.4 / 2.67 4 / 0.58 4 / 0.58 251 / 9.9 1564 / 61.6 490 / 19.3 47 / 103.6 49 / 46 / 40 6.90 26.08 2.20 8.32 21 / 3.05 21 / 3.05 12.8 / 1.86 12.8 / 1.86 251 / 9.9 1824 / 71.8 490 / 19.3 49 / 108 49 / 45 / 42 8.50 32.13 2.20 8.32 32.7 / 4.74 32.7 / 4.74 14.6 / 2.12 14.6 / 2.12 ACW800H 25864 7580 20002 5862 17470 5120 384 / 812 298 / 630 201 / 424 ACW1000H 29242 8570 21224 6220 23680 6940 437 / 924 309 / 653 228 / 483 ACW1200H 35418 10380 25696 7531 28969 8490 556 / 1176 409 / 865 281 / 594

ACC30CW - ACC60CW (Ceiling Concealed)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW HIGH NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER EXTERNAL STATIC ( H/M/L ) UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION HEIGHT WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mmAq mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ACC30CW 28000 8210 19900 5830 36000 10550 392 / 830 359 / 760 335 / 710 6.21 23.51 421 28000 8210 36000 10550 392 / 830 6.21 23.51 208-230/1/60 486 17 / 13 / 9 384 / 15.2 1004 / 39.6 541 / 21.3 39 / 86.0 46 / 42 / 38 15 / 2.1 12 / 1.8 ACC38CW 35200 10320 24600 7220 43000 12600 694 / 1470 670 / 1420 637 / 1350 7.84 29.68 486 ACC40CW 38000 11140 26600 7800 46000 13480 500 / 1060 467 / 990 425 / 900 8.45 31.99 220-240/1/50 448 38000 11140 46000 13480 500 / 1060 8.45 31.99 ACC50CW 47000 13770 32900 9640 57000 16710 651 / 1380 604 / 1280 571 / 1210 10.40 39.37 ACC60CW 54000 15830 37800 11080 67000 19640 722 / 1530 675 / 1430 609 / 1290 11.98 45.35 562 54000 15830 67000 19640 722 / 1530 11.98 45.35 804 16 / 14 / 10 384 / 15.2 1374 / 54.1 541 / 21.3 62 / 136.7 53 / 50 / 47 8 / 1.1 7/1
NOMINAL TOTAL COOLING CAPACITY

NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60C) - 1 ROW HIGH NOMINAL AIR FLOW MEDIUM LOW EXTERNAL STATIC ( H/M/L )

50HZ

60HZ

510 47000 13770 57000 16710 -NA651 / 1380 10.40 39.37 208-230/1/60 661 767 12 / 11 / 9 18 / 13 / 10 16 / 14 / 11 305 / 12.1 380 / 15 384 / 15.2 1302 / 51.3 1111 / 43.8 1374 / 54.1 638 / 25.2 541 / 21.3 541 / 21.3 41 / 90.4 42 / 92.6 54 / 119.0 51 / 48 / 45 49 / 45 / 41 52 / 50 / 47 49 / 7.1 21 / 3 41 / 5.9 44 / 6.3 18 / 2.6 36 / 5.2 3/4" BSP FEMALE ADAPTOR

NOMINAL WATER FLOW RATE - 1 ROW HEAD LOSS (COOLING) - 3 ROWS HEAD LOSS (HEATING) : 60C - 3 ROWs HEAD LOSS (COOLING) - 1 ROW HEAD LOSS (HEATING) : 60C - 1 ROW CONNECTION

NOTES : 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.

NOTES: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19.5C (67.1F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 21C (69.8F) DB, ENTERING WATER TEMP. : 60C (140F), LEAVING WATER TEMP. : 55C (131F) 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.

S9

S10

Chilled Water Fan Coil Specifications


AWM07GW - AWM25GW (Wall Mount)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH MEDIUM NOMINAL AIR FLOW LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi AWM07GW 8000 2340 5900 1730 10300 3020 130 / 275 106 / 225 83 / 175 1.76 6.66 24.00 AWM10GW 9500 2780 6900 2030 12800 3750 142 / 300 118 / 250 94 / 200 2.11 7.99 AWM15GW AWM20GW AWM25GW MWM301W 22000 6450 16720 4900 23000 6740 316 / 670 297 / 630 236 / 500 4.90 18.50 71.00 11000 15500 18000 3220 4540 5280 8000 12500 14800 2350 3650 4330 14000 20500 23000 4100 6010 6740 163 / 345 297 / 630 312 / 660 134 / 285 231 / 490 274 / 580 104 / 220 208 / 440 222 / 470 2.42 3.43 4.00 9.16 12.98 15.14 220-240/1/50 25.00 29.00 66.00 69.00 9500 11000 15500 18000 2780 3220 4540 5280 12800 14000 20500 23000 3750 4100 6010 6740 142 / 300 163 / 345 297 / 630 312 / 660 2.11 2.42 3.43 4.00 7.99 9.16 12.98 15.14 208-230/1/60 28.60 28.60 63.00 65.80 260 / 10.2 304 / 12.0 899 / 35.4 1062 / 41.8 198 / 7.8 222 / 8.7 9.4 / 20.8 15 / 33.1 39 / 34 / 28 42 / 36 / 29 49 / 44 / 42 50 / 48 / 45 65 / 9.4 77 / 11.1 50 / 7.3 69 / 10 59 / 8.5 64 / 9.2 51 / 7.3 71 / 10.2 1/2" BSP FEMALE ADAPTOR 50HZ

60HZ

-NA-

-NA-

260 / 10.2 799 / 31.5 198 / 7.8 8.5 / 18.8 38 / 33 / 28 48 / 7 42 / 6.1

291 / 11.4 815 / 32.1 181 / 7.1 20 / 44.1 49 / 47 / 45 52 / 7.6 19 / 2.7

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.

ADB75BW - ADB150BW (Ducted Blower)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY 50HZ NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER EXTERNAL STATIC ( H/M/L ) HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION Btu/h W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mmAq mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ADB75BW 75600 22160 56400 16520 78000 22860 1180 / 2500 16.78 63.52 220-240/1/50 810.00 75600 22160 78000 22860 1180 / 2500 16.78 63.52 208-230/1/60 1098.00 10.2 572 / 22.5 1502 / 59.1 761 / 30.0 96 / 211.6 56 35 / 5 33 / 4.8 1063.00 15.2 572 / 22.5 885 / 34.8 1502 / 59.1 1640 / 64.6 761 / 30.0 1040 / 40.9 100 / 220.5 140 / 308.6 57 58 42 / 6.1 22.75 / 3.30 27 / 4 17.93 / 2.60 1 1/8" BRAZING 1396.00 1840.00 95000 27840 97500 28580 1510 / 3200 21.09 79.83 1550.00 122500 36640 138000 40450 1982 / 4200 27.74 105.01 208-230/3/60 1575.00 15.2 885 / 34.8 1640 / 64.6 1040 / 40.9 145 / 319.7 58 18.96 / 2.75 14.89 / 2.16 ADB100BW 95000 27840 69400 20330 97500 28580 1510 / 3200 21.09 79.83 ADB125BW 12500 36640 90000 26380 138000 40450 1982 / 4200 27.74 105.01 380-415/3/50 1620.00 150000 43960 170000 49820 2171 / 4600 33.29 126.02 ADB150BW 150000 43960 106500 31210 170000 49820 2171 / 4600 33.29 126.02

60HZ

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE UNIT (FREE RETURN AND DISCHARGE AIR WAS DUCTED TO ADJACENT ROOM)

S11