GRUNDFOS DATA BOOKLET

Fire DNF, Fire HSF


Grundfos fire systems
http://www.grundfos.vn/web/homevn.nsf/GrafikOpslag/DB_Fire_dielse/$File/Fire%20DNF,%20Fire%
20HSF%20%28Dielse%29.pdf

Fire systems with diesel-powered pumps


certified by FM and UL according to NFPA 20

Contents

NFPA standards
Introduction to the NFPA
NFPA 20
FM Global
Underwriters Laboratories
Standards approval process
Certificates
Overview of fire system
Performance requirements
Other system components

Engine construction
4
4
4
4
4
5
8
9
10

11
11
11

Pump unit location


Ambient temperature
Inlet pressure
Ventilation requirements
Engine protection

12

Installation

Performance range
DNF, HSF

Piping
Alignment

Product range
Product numbers
FM/UL certification numbers

13
14

15
16

Pump construction
Sectional drawing, DNF
Material specification, DNF
Sectional drawing, HSF
Material specification, HSF pumps
Mechanical construction
Pump housing
Bearing bracket and shaft
Stuffing box
Impeller
Foundation
Surface treatment
Test pressure

18
19
20
21
22
22
22
23
23
24
24
24

Diesel engine data


Diesel engine range
Engine specifications

25
25

31
31
31
31
31

32
32

Bare shaft pumps


DNF
HSF
Flange dimensions

Identification
Nameplates
Type keys

27
29
29
29
29
29
29
30

Operating conditions

Product description
Introduction
DNF end-suction pumps
HSF horizontal, split-case pumps

Engine specifications
Engine type and rating
Instrumentation and control devices
Starting system
Engine cooling
Engine exhaust
Fuel arrangement
Coupling

33
34
35

Curve charts
How to read the curve charts
Guide
Curve conditions
Selection of pumps
Calculation of total head
Performance tests
FM/UL certificates

36
37
37
37
37
37
37

Contents

Performance curves, DNF


250 gpm, 66-80 psi
250 gpm, 116-130 psi
300 gpm, 119-129 psi
500 gpm, 64-75 psi
500 gpm, 101-125 psi

38
39
40
41
42

Performance curves, HSF


500 gpm, 40-49 psi
750 gpm, 41-69 psi
750 gpm, 67-127 psi
750 gpm, 47-88 psi
750 gpm, 60-104 psi
1000 gpm, 50-86 psi
1000 gpm, 59-103 psi
1000 gpm, 102-130 psi
1000 gpm, 129-150 psi
1000 gpm, 109-194 psi
1250 gpm, 76-98 psi
1250 gpm, 95-126 psi
1250 gpm, 104-187 psi
1250 gpm, 126-149 psi
1250 gpm, 162-191 psi
1500 gpm, 75-101 psi
1500 gpm, 79-123 psi
1500 gpm, 95-118 psi
1500 gpm, 98-142 psi
1500 gpm, 116-179 psi
1500 gpm, 188-190 psi
2000 gpm, 56-86 psi
2000 gpm, 93-116 psi
2000 gpm, 94-120 psi
2000 gpm, 105-141 psi
2000 gpm, 125-148 psi
2500 gpm, 49-81 psi
2500 gpm, 88-111 psi
2500 gpm, 118-141 psi
3000 gpm, 46-79 psi
3500 gpm, 59-76 psi

43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73

Technical data
Installation dimensions

74

Further product documentation


WebCAPS

80

NFPA standards

Fire DNF, Fire HSF

Introduction to the NFPA

Underwriters Laboratories

The National Fire Protection Association (NFPA) is an


international, non-profit organisation of fire safety
professionals. The NFPA headquarters is located in the
USA.
The organisation creates and maintains minimum
standards and requirements for fire prevention and
suppression activities, training, equipment and other
life-safety codes and standards.

See the NFPA homepage: www.nfpa.org.

The "UL File Number" of a product can be used to look


up a certificate at the UL homepage.
See www.ul.com > Online Certifications Directory.

NFPA 20
The DNF, HSF bare shaft pumps comply with the
NFPA 20, Standard for the Installation of Stationary
Fire Pumps for Fire Protection. The standard covers
systems for commercial and private buildings.

Standards approval process

TM03 5392 3606

TM03 5369 3606

The pumps have been tested and certified by


FM Global (FM) and Underwriters Laboratories Inc.
(UL) to comply with the requirements of the NFPA 20.
Compliance with the requirements is indicated by the
FM and UL marks affixed to the pumps. See fig. 1.

APPROVED

Fig. 1 FM and UL marks

Other NFPA standards


These standards are also of relevance to the products
described in this data booklet:
NFPA 13. Installation of sprinkler systems
NFPA 25. Standard for the inspection, testing and
maintenance of water-based fire protection systems
NFPA 70. National Electrical Code.
See the NFPA homepage: www.nfpa.org.

FM Global
The FM Global (FM*) is a mutual commercial and industrial property insurance and risk management organisation, located in the USA with offices worldwide.
* FM is short for Factory Mutual.

FM tests and approves industrial and commercial products in compliance with its own standards, or other
nationally recognised requirements.
The FM Approved mark indicates that the product complies with the required standards. See fig. 1.
See the FM homepage: www.fmglobal.com.

UL does not "approve" any product. Rather it tests


product samples and permits acceptable products to
carry the UL mark, as long as they remain in conformity
with the standards and with the samples tested to those
standards.
UL maintains a list of more than 100,000 products it has
tested. The database with the UL-listed products is
available online to the public.

The NFPA standards are often revised, due to new


information and technical equipment.

FM

Underwriters Laboratories Inc. (UL) is an independent,


non-profit, product-safety testing and certification
organisation located in the USA.

Grundfos tests the pumps and fills in the application


forms for each individual pump size. We submit this
documentation to FM and UL:
Expected pump performance, including total head,
power requirements and efficiency versus flow
characteristics.
If different impeller diameters are used to obtain the
rated head for the pump to be examined, complete
details must be provided concerning performance
specifications to be evaluated.
Calculations to determinate shaft size, casing bolt
size and anti-friction bearing life.
General assembly drawings, a complete set of manufacturing drawings, materials lists and physical
property specifications, expected marking format,
brochures, sales literature, specification sheets, installation, operating and maintenance procedures.
If the application forms are accepted, FM and UL will
attend the final test at the Grundfos premises.
If the evaluation of the test results is positive, FM and
UL issue a certificate of compliance of the pump with
the standards specified.
If a pump component is replaced after the certificate of
compliance has been issued, representative samples
of the pump may need to be re-tested.

NFPA standards

Fire DNF, Fire HSF

Certificates

TM03 5814 4006

Examples of FM certificates of compliance

Fire DNF, Fire HSF

TM03 5813 4006

NFPA standards

NFPA standards

Fire DNF, Fire HSF

Examples of UL certificates of compliance


For information on the UL certificates, please look up
the UL File Numbers (listed below) at the UL
homepage: www.ul.com > Online Certifications Directory.
UL File Numbers
DNF pumps:

EX6922

HSF pumps:

EX6873

NFPA standards

Fire DNF, Fire HSF

Overview of fire system


4

4
5
6

5
8

7
9

8
9

6
10
12

1b

1a

14

11

TM03 5471 1507

13

Fig. 2 Overview of fire system


Pos. Description

Pos. Description

Description

Fire pump, electrically powered (duty pump)

Valve

10

Waste cone with sight glass

1b

Fire pump, diesel-powered (standby pump)

Expansion joint

11

Discharge from relief valve

Jockey pump

Main relief valve

12

Flowmeter

From supply tank

Check valve/non-return valve

13

Discharge from test line

To system

Pressure gauge

14

Supply to jockey pump

System design
A fire system typically consists of three pumps: one
pressure pump (jockey pump) and two fire pumps, one
duty and the other acting as standby. Each of the fire
pumps is capable of achieving the required
performance.
Systems with only one fire pump or more than two fire
pumps are, however, also seen.
Operation
The jockey pump maintains pressure in the system and
compensates for any loss of pressure caused by leaks
and thus prevents the duty pump from starting unnecessarily. The jockey pump has two pressure levels:
a low pressure level to start the jockey pump
a high pressure level to stop the jockey pump.
In case of further decrease of system pressure due to
fire (i.e. sprinkler opens), the duty pump starts. In case
this pump fails to start or breaks down, the standby
pump will start.

Pos.

1a

The duty and standby pumps are not powered by the


same source. This ensures that if one pump fails, for
example due to fire damage, the other will operate. The
pumps are controlled by pressure sensors.
Although individually designed for the specific installation, each fire unit must comply with NFPA standards.
Fire pumps
FM-approved and UL-listed Grundfos end-suction and
split-case pumps are designed for the distribution of
water in automatic sprinkler and standpipe systems.
They are operated in case of fire and during tests.
Materials
Impeller, wear rings, guide or diffusion vane rings,
lantern rings, bottoms of stuffing boxes, interior nuts,
linings of stuffing-box throats, glands, gland nuts and
drain plugs are made of corrosion-resistant material.

NFPA standards

Fire DNF, Fire HSF

Performance requirements
FM-approved and UL-listed pumps comply with requirements concerning these features:

Closed-valve pressure
The closed-valve pressure must be at least 101% and
not higher than 140% of the total rated pressure. See
fig. 4 and the example below.

flow vs. pressure


H
[m]

engine power rating.

p
[psi]

61

HSF 6-12

140%

60

40

Flow vs. pressure


The approval/listing of the pump is based on a certain
rated flow, indicated by the solid line in the curve
charts. The pump must be able to supply not less than
150% of the rated flow (broken line) and still be able to
provide at least 65% of the total rated pressure. See
fig. 3 and the example below.

ISO 9906 Annex A


/311

53

50

100%

4430
40

30

20

20
10
10

0
0

H
[m]

p
[psi]

P2

HSF 6-12

60

100%

40

200

P2

400

600

800

100

1000

1200

200

1400

1600

300

Q [US GPM]
400

Q [m/h]

Fig. 4 Closed-valve pressure

n nom = 1450 min-1

150%

n nom = 1450 min-1

TM03 4236 1906

closed valve pressure

ISO 9906 Annex A

/311

Example
The curve shows a rated pressure of 44 psi (31 mH).
To be FM-approved/UL-listed, the pump must comply
with these requirements:

50

100%

4430
40

34
24
20

30

65%

0
0

P2

P2

200

400

100

600

800

1000

1200

200

1400
300

1600

Q [US GPM]
400

Q [m/h]

Fig. 3 Flow vs. pressure

Example
The pump complies with a flow requirement of 750 gpm
(170 m/h). At this flow, the pump delivers a pressure of
44 psi (31 mH). To be FM-approved/UL-listed, the
pump must comply with these requirements:
Rated flow (100%):

750 gpm (170 m/h)

Minimum flow supplied by the pump (150%):

1125 gpm (256 m/h)

Rated pressure (100%):

44 psi (31 mH)

Minimum pressure supplied by the pump


(65%):

28 psi (31 mH)

At 150% of the total rated flow, the pump delivers a


pressure of 34 psi (24 mH). This means that the pump
complies with the requirements.

Rated pressure (100%):

44 psi (31 mH)

Minimum closed-valve pressure (101%):

44 psi (31 mH)

Maximum closed-valve pressure (140%):

61 psi (43 mH)

The pump has a closed-valve pressure of 53 psi


(37 mH). This means that the pump complies with the
requirements.
Engine power rating
To ensure that the engine is capable of operating the
pump at any time, the NFPA demands that the manufacturer determines the maximum power required at a
certain duty range. The maximum power occurs when
there is no increase in power with an increase in the
flow. See fig. 5.
P2
[kW]

P2
[hp]

30

40

100

200

300

400

25

Q [m/h]

/311
30

20
20
10
10

0
0

200

400

600

800

1000

1200

1400

1600

TM03 4236 1906

10

TM03 4236 1906

20
10

Q [US GPM]

Et

Fig. 5 Engine power rating

NFPA standards
Other system components
Diesel engines
Engines must be listed for fire pump operation. The
engines must be of the compression-ignition type.
Jockey pumps
Grundfos CR pumps are used as jockey pumps,
maintaining the pressure. Under normal conditions, the
jockey pump is activated by the low-pressure switch as
a result of small leakages or if one or more sprinklers
are activated.
The jockey pump is not subject to any specific NFPA
requirements.
Control panel
The control panel for the fire pumps must comply with
NFPA 20 requirements. In addition, the cabinet must be
listed by UL and ULC and approved by FM and CSA.
The control panel is painted with RAL 3000 (red) and
housed in a NEMA Type-2 drip-proof enclosure.
The control panel is suitable for wall mounting or floor
mounting. See Type keys, page 16.

10

Fire DNF, Fire HSF

Product description

Fire DNF, Fire HSF

Introduction

DNF end-suction pumps

This data booklet covers the DNF, HSF pump range.


The pumps have been tested and certified by FM and
UL to comply with the requirements of the NFPA 20
covering fire systems for commercial and private buildings.

The DNF pumps are non-self-priming, single-stage,


centrifugal, volute pumps. The pumps feature

Pump designations
DNF, HSF are pumps without engine
(bare shaft pumps).

axial suction port, radial discharge port and horizontal shaft components
cast iron pump housing, bronze impeller, carbon
steel shaft, bronze shaft sleeves and wear rings
dimensions and rated performance according to
DIN 24256 and ISO 2858

Fire DNF is a DNF pump and engine mounted on a


common base frame. The unit can be incorporated
in a fire system.

dynamically balanced rotating parts according to


ISO 1940, class 6.3; hydraulically balanced impellers

Fire HSF is an HSF pump and engine mounted on a


common base frame. The unit can be incorporated
in a fire system.

two sturdy, oil-lubricated, anti-friction bearings


stuffing box.

Please note that in the following the term unit covers


the fire pump and motor mounted on a common base
plate/frame, as described in this data booklet, whereas
the term system covers the fire hydrants or sprinkler
systems of a building.

TM03 5388 3606

Scope of delivery
A complete Fire DNF, Fire HSF unit assembled and
supplied from factory normally comprises these elements:
a pump and engine mounted on a common base
frame
a PTO (Power Take-Off) shaft protected by a
coupling guard
pressure gauges
plugs and screws in stainless steel.
The control panel for the fire systems must be ordered
separately.
The standard engine comes with these features:
cooling loop
flexible exhaust
industrial silencer
two storage battery units

Fig. 6 Fire DNF: A DNF end-suction pump and engine


mounted on a base frame

HSF horizontal, split-case pumps


The HSF pumps are horizontal, split-case centrifugal
pumps. The pumps have these features:
automatic air relief valve
cast iron pump housing, double-suction bronze impeller, carbon steel shaft, bronze shaft sleeves and
wear rings
two sturdy, grease-lubricated, anti-friction bearings
stuffing box.

heat exchanger (valves included).


Grundfos offers the following accessories approved/
listed by FM/UL:
fuel tank
main relief valve
TM03 5389 3606

flowmeter.

Fig. 7 Fire HSF: An HSF horizontal split-case pump and


engine mounted on a base frame

11

12

30

40

50

60

70

80

90

100

120

150

200

60

70

300

400

80 90 100

DNF 65-20 2900 min-1

DNF 65-25
2900 min-1

250

p
[psi]

TM02 9838 0907

30

40

50

60

70

80

90

100

H
[m]

500

600

HSF 6-12 1450 min-1

DNF 80-20
2900 min-1

DNF 80-25 2900 min

-1

HSF 6-16 1450 min-1

200

300

1000 1200

HSF 6-12 1750 min-1

800

HSF 6-16
1750 min-1

HSF 6-18 1450 min-1

HSF 5-11 2900 min-1

1500
400

HSF 8-20
1450 min-1

HSF 8-20G
1450 min-1

500

600

1000 Q [m/h]

4000 Q [US GPM]

1450 min-1

HSF 10-16

700 800

2500 3000

HSF 8-17
1450 min-1

HSF 10-20
1450 min-1

HSF 8-20G
1750 min-1

HSF 8-20G 1770 min-1

HSF 8-20 1750 min-1

HSF 10-20
1450 min-1

2000

HSF 8-20G
1450 min-1

HSF 6-18 1750 min-1

HSF 6-12 2900 min-1

HSF 6-18 2000 min-1

Diesel

Performance range
Fire DNF, Fire HSF

DNF, HSF

Product range

Fire DNF, Fire HSF

Product numbers
The product number covers the pump unit, comprising
pump, engine, coupling and base frame.

Pump unit
Fire DNF 65-20
Fire DNF 65-25
Fire DNF 80-20
Fire DNF 80-25

Fire HSF 5-11

P2
Speed Product
[kW] [hp] [rpm] numbers

Flow
[gpm]

Engine
type

250

JU4H-UF14

53

71

2900

95100792

250

JU4H-UF14

53

71

2900

95100793

300

JU4H-UF14

53

71

2900

95100794

500

JU4H-UF14

53

71

2900

JU4H-UF14

53

71

JU4H-UF24

61

82

JU4H-UF14

53

71

JU4H-UF24

61

82

JU4H-UF34

82

110

JU4H-UF58

59

79

JU4H-UF10

31

41

JU4H-UF20

45

60

JU4H-UF54

108

145

95100820

JU6H-UF34

125

168

95100821

JU6H-UF54

161

216

JU6H-UF84

199

JU4H-UF54

500

750
500
750

1000
Fire HSF 6-12
1250

1500

750

1000
Fire HSF 6-16

1250

750

1000

Fire HSF 6-18

1250

1500

2900

2900

95100796

Pump unit
Fire HSF 8-17

Flow
[gpm]
2000
1500

Engine
type

P2
Speed
[kW] [hp] [rpm]

Product
numbers
95100855

JU6H-UF58

103

138

JU6H-UF68

131

176

JU6H-UF58

103

138

JU6H-UF68

1450
1450

95100856
95100839

149

200

2000 JW6H-UF38 188

252

95100798

JW6H-UF60 268

360

95100868

95100806

JU6H-UF58

103

138

95100840

JU6H-UF68

95100797

Fire HSF 8-20

95100807

95100866
1770

95100867

131

176

JW6H-UF30 164

220

95100795

JU6H-UF48

179

240

95100843

95100799

JU6H-UF58

103

138

95100860

95100800

JU6H-UF68

131

176

JW6H-UF30 164

220

JW6H-UF48 179

240

95100863

95100822

JW6H-UF58 224

300

95100864

267

95100823

JW6H-UF60 268

360

108

145

95100833

JW6H-UF58 224

300

JU6H-UF34

125

168

JW6H-UF60 268

360

JU6H-UF54

161

216

JU6H-UF58

103

138

JU6H-UF68

131

176

JW6H-UF30 164

220

1500

95100808
1450
1750

2900

2900

199

267

95100836

125

168

96734795

JU6H-UF54

161

216

JU6H-UF84

199

267

JU4H-UF58

59

79

JU6H-UF30

70

94

JU4H-UF58

59

79

JU6H-UF30

70

94

1450

2500

95100835

JU6H-UF34

1450

2000

95100834

JU6H-UF84

2900

Fire HSF 8-20G

2500

95100872

JU6H-UF68

131

176

JW6H-UF30 164

220

95100809

JW6H-UF48 179

240

95100881

95100810

JU6H-UF68

131

176

95100882

95100814

3500 JW6H-UF30 164

220

95100815

JW6H-UF48 179

240

95100884

220

95100844

95100801

Fire HSF 10-16

95100802

3000

183

95100816

JW6H-UF30 164

JU4H-UF58

82

110

95100826

1500 JW6H-UF48 179

240

JU6H-UF30

104

140

95100827

JX6H-UF30

261

350

JU6H-UFG8

111

149

JU6H-UF58

137

183

95100829

JU4H-UF58

59

79

95100803

JU4H-UF58

59

79

JU6H-UF30

70

94

1450

1450

JW6H-UF30 164

220

2000 JW6H-UF48 179

240

JX6H-UF30

261

350

95100804

JW6H-UF30 164

220

95100805

2500 JW6H-UF48 179

240

95100811

JX6H-UF30

350

95100828

103

138

95100813

JU6H-UF58

137

183

95100817

JU6H-UF68

149

200

JW6H-UF38 188

252

JU6H-UF30

70

94

JU6H-UF58

103

138

JU6H-UF58

137

183

JU6H-UF68

149

200

JW6H-UF38 188

252

JW6H-UF30 203

272

JW6H-UF40 222

297

JU6H-UF58

137

183

JU6H-UF68

149

200

JW6H-UF38 188

252

JW6H-UF40 222

297

Fire HSF 10-20

261

1450

1450

1450

95100879
95100880

95100883

95100845
95100846
95100857

1450

95100858
95100859
95100873

1450

95100874
95100875

95100812

JU6H-UF58

1750

95100870
95100871
95100878

137

94

1450

240

JU6H-UF58

138

95100877
95100869

138

110

70

95100865
95100876

103

149

103

95100862

JU6H-UF58

82

JU6H-UF58

1750

95100861

JW6H-UF48 179

111

JU6H-UF30

1770

95100842

95100851

JU4H-UF58

1750

1450

95100841

95100850

JU6H-UFG8

1750

1450

95100818
95100819

1450

95100824
95100825
95100830

1765

95100831
95100832

2000

95100837
95100838
95100847

1750

95100848
95100849

2000

95100854

13

Product range
FM/UL certification numbers
DNF
Pump type

FM
approval no.

DNF 65-20

3019994

DNF 65-25
DNF 80-20

3019994
3022323

DNF 80-25

3019994

UL
file no.

EX6922

HSF
Pump type
HSF 5-11
HSF 6-12

UL
file no.

3025607

EX6873

HSF 6-16

3009099
3019994

HSF 6-18

3009099
3019994
3022323

HSF 8-17

3019994
3022323

HSF 8-20
HSF 8-20G
HSF 10-16
HSF 10-20

14

FM
approval no.

3009099
3019994
3019994

EX6873

Fire DNF, Fire HSF

Identification

Fire DNF, Fire HSF

Nameplates
DNF
The nameplate shows a DNF end-suction pump with a
rated capacity of 500 gpm (114 m/h) at 2900 min-1.
See fig. 8. To deliver a rated net pressure of 115 psi
(81 mH), the actual impeller size is 251 mm.

AV. H. A. CASTELO BRANCO. 630


SAO BERNARDO DO CAMPO - SP - BRASIL

CENTRIFUGAL FIRE PUMPS - END SUCTION 20SV

FM
APPROVED

CAPACITY
MAXIMUM NET
PRES. DEVELOPED

SERIAL NUMMER

06040002

gal/min AT

RATED NET
PRESSURE

115

psi

NET PRES. AT 150%


RATED CAPACITY

rpm

IMPELLER
DIAMETER

DNF 80-25

500
119

RATED
SPEED RPM.

2900

NUMBER OF
STAGES

psi

92

251

mm

MAXIMUM POSITIVE
SUCTION PRESSURE

MAXIMUM BRAKE-HORSEPOWER REQUIRED


AT RATED SPEED AT ANY CAPACITY CONDITION

psi

100

psi

hp

71

TM03 4621 2406

MODEL

Fig. 8 Nameplate, DNF end-suction pump

HSF
The nameplate shows an HSF horizontal split-case
pump with a rated capacity of 750 gpm (170 m3/h) at
1450 min-1. See fig. 9. To deliver a rated net pressure
of 80 psi (56 mH), the actual impeller size is 395 mm.

MODEL

CAPACITY
MAXIMUM NET
PRES. DEVELOPED
RATED
SPEED RPM.
NUMBER OF
STAGES

HSF 6-16

750
84
1450
1

FM

CENTRIFUGAL FIRE PUMPS - SPLIT CASE


16GG

APPROVED

06020009

SERIAL NUMMER

gal/min AT

RATED NET
PRESSURE

psi

NET PRES. AT 150%


RATED CAPACITY

rpm

IMPELLER
DIAMETER

80

395

75

psi

74
mm

MAXIMUM POSITIVE
SUCTION PRESSURE

MAXIMUM BRAKE-HORSEPOWER REQUIRED


AT RATED SPEED AT ANY CAPACITY CONDITION

psi

100

psi

hp

TM03 4623 2406

AV. H. A. CASTELO BRANCO. 630


SAO BERNARDO DO CAMPO - SP - BRASIL

Fig. 9 Nameplate, HSF horizontal split-case pump

15

Identification

Fire DNF, Fire HSF

Type keys
Fire systems
Examples

Fire

DN

80

-25

/260

-D

-A

-X

-A

-A

-B

-B

Fire

HS

-16

/210

-D

-A

-X

-A

-A

-C

-B

Fire: Fire system


Pump type
DN
HS
F: The pump is approved for fire protection
Nominal diameter of discharge port (DN)
[mm] or [inch]
Pump housing size
[mm], [cm] or [inch]
Actual impeller diameter
[mm]
Driver
D: Diesel engine
E: Electric motor, 50 Hz *
F: Electric motor, 60 Hz **
X: Special configuration
Approval/listing, pump
A: FM/UL
B: FM
C: UL
X: No approval
Approval, system
X: No approval
Pipe connection
A: ANSI
D: DIN
Control panel
F: For floor mounting
W: For wall mounting
X: No panel
Stuffing box
B: SNEA
C: SNFA
Coupling
A: Standard * **
D: PTO (Power Take-Off) shaft
C: Other types
*

See Grundfos data booklet, Fire DNF, Fire HSF, fire systems with
electrically powered (50 Hz) pumps, available in WebCAPS.
See page 80.

** See Grundfos data booklet, Fire DNF, Fire HSF, fire systems with
electrically powered (60 Hz) pumps, available in WebCAPS.
See page 80.

Diesel engine
Example

J U 4 H

-UF

14

Engine type
John Deere
Base engine series
Number of cylinders
Heat exchanger
UL-listed and FM-approved
Reference number for power range

Stuffing box
Example
S: Packing-type stuffing box
N: Uncooled stuffing box
E: With internal barrier fluid
F: With external barrier fluid
A: PTFE-impregnated fibre packing rings and EPDM
O-ring in pump housing

16

17

Pump construction

Fire DNF, Fire HSF

Sectional drawing, DNF


6

49

20
72a
66a

20

26
96 96a
115a 115c
45b

115

51

86

154

114

76
156a
45a
11a
11
66
20
66a
67

159f

107

155b
88
88a

20

108

77

Fig. 10 Sectional drawing, DNF pump

18

116

106

109

159d

97

97

99

TM03 5505 3706

87

Pump construction

Fire DNF, Fire HSF

Material specification, DNF


Material code
Pos.

Description

Material
DIN W.-Nr.

AISI/ASTM/SAE

Cast iron

EN-JS-1030

A536 - 60-40-18

Steel

1.0503

1045

Pump housing

11

Impeller key

11a

Key

Steel

1.0503

1045

20

Plug

Stainless steel

1.4301

304

26

Screw

45a

Wear ring

Bronze TM-23

45b

Wear ring

Bronze TM-23

49

Impeller

51

Shaft

66

Washer

66a

Pressure washer

67

Nut

72a

Gasket

76

Steel

Bronze

SAE 40

Steel

1.0503

1045

Stainless steel

1.4401

316

Steel

1.0633

1070

Stainless steel

1.4401

316

Plate

Stainless steel

1.4401

316

77

Cover

Cast iron

EN-JS-1030

A536 - 60-40-18

86

Bearing bracket

Cast iron

EN-JL-1030

A48-30

87

Support

Cast iron

EN-JS-1030

A536 - 60-40-18

88

Screw

88a

Washer

1.4301

304

96

Screw

96a

Pressure washer

97

Plug

1.4301

304

99

Oil dipstick

106

Packing gland

EN-JS-1030

A536 - 60-40-18

107

Packing ring

PTFE impregnated aramid

108

Lantern ring

Bronze TM-23

Steel
Stainless steel
Steel
Steel
Stainless steel
Polyethylene
Cast iron

109

Gasket

114

Screw

Steel

115

Gland

Steel

1.0044

1020

115a

Nut

Stainless steel

1.4301

304

115c

Pressure washer

EN-JL-1030

A48-30

116

Shaft sleeve

Bronze TM-23

154

Ball bearing

Steel

155b

Gasket

156a

Bearing housing cover

159d

Deflector

NBR elastomer

Cast iron

159f

Seal

NBR elastomer

19

Pump construction

Fire DNF, Fire HSF

Sectional drawing, HSF


156a 155a 111a

54

113a 107

72a 116a

45

32

33

49

6a

11

116b

47c

30

115a

115

111b 113b

53

155b 156b 159e

11a

95

114

159a 159c

51

106

108

109

6b

159d 159b

159f
TM03 5506 3706

112

Fig. 11 Sectional drawing, HSF pump

20

Pump construction

Fire DNF, Fire HSF

Material specification, HSF pumps


Material code
Pos.

Description

Material
DIN W.-Nr.

AISI/ASTM/SAE

6a

Pump housing, upper

Cast iron

EN-JL-1040

A48-35

6b

Pump housing, lower

Cast iron

EN-JL-1040

A48-35

Steel

1.0503

1045

11

Impeller key

11a

Key

30

Connector

Brass

32

Piping seal

Copper

1.0503

33

T-shaped pipe

45

Wear ring

Bronze, TM-23

47c

Stuffing box bushing

Bronze, TM-23

49

Impeller

1045
SAE 72

Brass

SAE 72

Bronze

SAE 40

51

Shaft

Steel

53

Ball bearing, drive end

Steel

1.7225

4140

54

Ball bearing, non-drive end

Steel

72a

Gasket

95

Plug

106

Packing gland

107

Packing ring

PTFE-impregnated aramide

108

Lantern ring

Bronze, TM-23

109

O-ring

NBR Elastomer

111a

Bearing housing cap, non-drive end

Cast iron

EN-JL-1030

A48-30

111b

Bearing housing cap, drive end

Cast iron

EN-JL-1030

A48-30

112

Bearing retaining ring

Steel

1.0603

1070

113a

Bearing housing, non-drive end

Cast iron

EN-JL-1030

A48-30

113b

Bearing housing, drive end

Cast iron

EN-JL-1030

A48-30

114

Screw

115

Gland stud

Stainless steel

1.4301

304

115a

Nut

Stainless steel

1.4301

304

116a

Shaft sleeve, non-drive end

Bronze, TM-23

116b

Shaft sleeve, drive end

Bronze, TM-23

155a

Bearing cover gasket, non-drive end

155b

Bearing cover gasket, drive end

156a

Bearing housing cover, non-drive end

Cast iron

EN-JL-1030

A48-30

156b

Bearing housing cover, drive end

Cast iron

EN-JL-1030

A48-30

159a

Bearing housing seal, non-drive end

159b

Bearing housing seal, drive end

NBR

159c

Deflector, non-drive end

NBR

159d

Deflector, drive end

NBR

159e

Deflector

NBR

159f

Inboard bearing cover seal

NBR

Steel
Bronze

SAE 40

Steel

NBR

21

Pump construction

Fire DNF, Fire HSF

Mechanical construction

Bearing bracket and shaft

Pump housing

DNF
The bearing bracket has two sturdy, anti-friction, oillubricated bearings.

DNF
The cast iron, volute pump housing has axial suction
port and radial discharge port. Flange dimensions are
according to DIN 2533.

The shaft is made of steel, SAE1045. The shaft


diameter is 32 mm.
A rubber deflector on the shaft prevents water from
entering the bearing bracket.

TM03 0232 4504

The pump housing has a priming hole and a drain hole


closed by plugs.

The bearing bracket is made of cast iron, ASTM A48


CL30.

TM03 4599 2306

Fig. 12 Pump housing, DNF

HSF
The cast iron, volute pump housing has radial suction
and discharge port. Flange dimensions are according
to ANSI B16.1.
The pump housing has a priming hole and a drain hole
closed by plugs.

Fig. 14 Bearing bracket and shaft, DNF

HSF
The bearing bracket has two sturdy, anti-friction,
grease-lubricated bearings.

TM03 4600 2306

The bearing bracket is made of cast iron, ASTM A48


CL30.
The shaft is made of steel, SAE4140. The shaft
diameter is 39.7, 47.6, 57.2 or 63.5 mm.
A rubber deflector on the shaft prevents water from
entering the bearing bracket.

TM03 4598 2306

Fig. 13 Pump housing, HSF

Fig. 15 Bearing bracket and shaft, HSF

22

Pump construction

Fire DNF, Fire HSF

Stuffing box

Impeller

The stuffing box is made of braided packing rings.


Braided material ensures a long service life of packing
rings and protects the pump shaft (sleeve). The packing
rings are installed symmetrically with parallel faces to
prevent tilting.

The closed impeller made of bronze has double-curved


blades with smooth surfaces for high efficiency.

TM03 4680 2506

Materials
PTFE-impregnated fibre packing rings and EPDM Orings in pump housing.
Type of barrier fluid
DNF: internal barrier fluid

TM03 4597 2306

Fig. 16 Sectional view of uncooled stuffing box with


internal flushing liquid for DNF pumps

TM03 4681 2506

Fig. 18 Impeller for a DNF pump

HSF: external barrier fluid.

Fig. 19 Double-suction impeller for an HSF pump

The impellers are hydraulically balanced and


dynamically balanced together with the shaft. The
hydraulic balancing compensates for axial thrust.
The direction of rotation of the impeller is clockwise
when viewed from the engine.

TM03 4596 2306

The impellers are adapted to the duty point required by


the customer.

Fig. 17 Sectional view of uncooled stuffing box with


external flushing liquid for HSF pumps
Pump type

Stuffing box dimensions


[inch]

DNF

3/8 x 3/8

HSF

1/2 x 1/2
9/16 x 9/16
5/8 x 5/8

23

Pump construction

Fire DNF, Fire HSF

Foundation

30

40

50

20

60

10

70
0
90

80

TM03 5500 3706

Diesel-powered DNF, HSF pumps and engine are


mounted on a common steel base frame. See fig. 20.

Fig. 20 Schematic view of Fire DNF

Surface treatment
Cast iron parts are coated with a protective primer
(thickness of 30 m 5 m).
The part is cleaned with an organic solvent and finally
spray-painted with red two-component paint,
RAL 3000. The thickness of the dry coating is
30 m 5 m.

Test pressure
Before delivery, the pumps are hydrostatically tested
for 5 minutes to 1.5 times the sum of the closed-valve
pressure plus the maximum permissible suction head,
1.5 x (Pmax + Pmax suction), but not less than 250 psi.
Test liquid: Water at 20C (68F).

24

Diesel engine data

Fire DNF, Fire HSF

Diesel engine range


Speed [rpm]
Engine type

1450

1750

2000

2900

Power

Power

Power

Power

[kW]

[hp]

JU4H-UF10

[kW]

[hp]

31

41

45

60

[kW]

[hp]

JU4H-UF14
JU4H-UF20

[kW]

[hp]

53

71

JU4H-UF24

61

82

JU4H-UF34

82

110

108

145

125

168

161

216

199

267

JU4H-UF54
JU4H-UF58

59

79

82

110

JU6H-UF30

70

94

104

140

111

149

JU6H-UF34
JU6H-UFG8
JU6H-UF54
JU6H-UF58

103

138

137

183

JU6H-UF68

131

176

149

200

164

220

JU6H-UF84
JW6H-UF30
JW6H-UF38

188
179

222

297

240

JW6H-UF58

224

300

JW6H-UF60

268

360

JX6H-UF30

272

252

JW6H-UF40
JW6H-UF48

203

261

350

Engine specifications
JU4H-UFxx
JU4H model

-UF10, -UF14, -UF20, -UF24

Number of cylinders
Aspiration
Rotation

-UF34, -UF54, -UF58


4

Naturally aspirated

Turbocharged

Clockwise rotation viewed from heat exchanger/front of engine

Weight [kg] ([lb.])

413 (910)

424 (935)

Compression ratio

17.6:1

17.0:1

Displacement [l] ([cu. in.])


Engine type

4.5 (275)
4-stroke cycle - inline construction

Bore and stroke [mm] ([inch])


Installation drawing
Wiring diagram
Engine

106 x 127 (4.19 x 5.00)


D-534-US

D-545-UK

C07575 (DC engine wiring)

C07651 (AC heater wiring)

John Deere 4045 series

25

Diesel engine data

Fire DNF, Fire HSF

JU6H-UFxx
JU6H model

-UF30, -UF34, -UFG8, -UF54, -UF58

-UF68, -UF84

Number of cylinders

Aspiration

Turbocharged

Rotation

Clockwise rotation viewed from heat exchanger/front of engine

Weight [kg] ([lb.])

Turbocharged with raw water after cooling

750 (1657)

766 (1693)

Compression ratio

17.0:1

Displacement [l] ([cu. in.])

6.8 (414)

Engine type

4-stroke cycle - inline construction

Bore and stroke [mm] ([inch])


Installation drawing
Wiring diagram

106 x 127 (4.19 x 5.00)


D-536-US

D-538-UK

C07575 (DC engine wiring)

C07651 (AC heater wiring)

Engine

John Deere 6068 Series

JW6H-UFxx
JW6H model

-UF30, -UF38

-UF40, -UF48

Number of cylinders
Aspiration
Rotation

Turbocharged and after-cooled

Turbocharged with raw water after cooling

Clockwise rotation viewed from heat exchanger/front of engine

Weight [kg] ([lb.])

910 (2012)

Compression ratio

16.5:1

906 (2003)

929 (2053)
15.7:1

Displacement [l] ([cu. in.])


Engine type

-UF58, -UF60

8.1 (496)
4-stroke cycle - inline construction

Bore and stroke [mm] ([inch])

116 x 127 (4.56 x 5.00)

Installation drawing

D-495

Wiring diagram

C07602

Engine

John Deere 6081 Series

JX6H-UFxx
JX6H model
Number of cylinders
Aspiration
Rotation
Weight [kg] ([lb.])
Compression ratio
Displacement [l] ([cu. in.])
Engine type
Bore and stroke [mm] ([inch])
Installation drawing
Wiring diagram
Engine

26

-UF30
6
Turbocharged with jacket water after-cooled
Clockwise rotation viewed from heat exchanger/front of engine
1429 (3150)
16:1
12.5 (766)
4-stroke cycle - inline construction
127 x 165 (5.00 x 6.50)
D-546
C07957
John Deere 6125 Series

Engine construction

Fire DNF, Fire HSF

JX6H-UF30

JW6H-UF30
JW6H-UF38
JW6H-UF40
JW6H-UF48
JW6H-UF58
JW6H-UF60

JU6H-UF30
JU6H-UF34
JU6H-UFG8
JU6H-UF54
JU6H-UF58
JU6H-UF68
JU6H-UF84

JU4H-UF58

JU4H-UF10
JU4H-UF20

JU4H-UF34
JU4H-UF54

Engine type

JU4H-UF14
JU4H-UF24

Engine specifications

Air cleaner
Direct mounted, washable, for indoor service

Disposable, drip-proof, for indoor service

Outdoor type

Alternator
12 VDC, 42 ampere, with belt guard

24 VDC, 40 ampere, with belt guard

SC2140

Exhaust protection
Blankets for manifold and turbocharger

z
z

Metal guards on manifolds and turbocharger

SC55

SC2130

SC2130

Coupling
PTO shaft and guard. PTO shaft system series:

41

55

SC41

Exhaust connection
Flex exhaust, 2" to 3" NPT

z
z

Flex exhaust, 4" to 5" 150

Flex exhaust, 5" to 6" 150


Flywheel housing

SAE2
SAE3

Flywheel power take-off


11.5" pattern
11.5" SAE, industrial flywheel connection
Fuel connections
Fire-resistant flexible supply and return lines

Fuel-injection system
Direct injection

Unit injectors with electronic control


z

Direct injection, inline


Fuel filter
Primary filter with priming pump

z
z

Primary and secondary with priming pump


Engine heater
115 VAC, 2500 W
230 VAC, 2500 W
240 VAC, 1500 W

Govenor, speed
Constant speed, mechanical
Electronic

z
z

Droop
9%

4%

0%

z Standard
Optional

27

Engine construction

Fire DNF, Fire HSF

JU4H-UF34
JU4H-UF54

JU4H-UF10
JU4H-UF20

JU4H-UF58

JU6H-UF30
JU6H-UF34
JU6H-UFG8
JU6H-UF54
JU6H-UF58
JU6H-UF68
JU6H-UF84

JW6H-UF30
JW6H-UF38
JW6H-UF40
JW6H-UF48
JW6H-UF58
JW6H-UF60

JX6H-UF30

Engine type

JU4H-UF14
JU4H-UF24

(Continued from the previous page)

Heat exchanger
Tube and shell type, rated 60 psi with NPTF connections
Instrument panel
Tachometer, hourmeter, water temperature, oil pressure, two voltmeters
Tachometer, hourmeter, water temperature, oil pressure, voltmeter with
selector switch

Junction box
Integral with instrument panel for DC wiring interconnection to engine
controller

Lubricating-oil cooler
Engine water-cooled, plate type
Lubricating-oil filter
Full flow with by-pass valve
Lubricating-oil pump
Gear driven, gear type
Manual start controls
On instrument panel
Overspeed control
z

Electronic with reset


Electronic with reset and test on instrument panel
Raw-water solenoid operation
Automatic from engine controller and from emergency local control

z
z

Automatic from engine controller and from instrument panel

Run-stop control
On instrument panel with control panel position warning light

Run solenoid
12 VDC

24 VDC

Starters
z

One 12 VDC engine


Two 12 VDC engines

One 24 VDC engine


Two 24 VDC engines

Throttle control
Adjustable speed control, tamper-proof

z
z

Adjustable speed control by increase/decrease button, tamper-proof


Water pump
Poly-vee belt drive with guard
Gear driven, centrifugal type
z Standard
Optional

28

z
z

Engine construction

Fire DNF, Fire HSF

Engine type and rating

Starting system

The compression-ignition diesel engine must be


approved/listed for fire pump operation. The mark of the
listing laboratory (FM and/or UL) is displayed on the
engine nameplate showing compliance with the performance ratings and functional requirements.

The engine is provided with two storage battery units.


At 4.5C (40F) each battery must have twice the
capacity sufficient to maintain a 3-minute attempt to
start cycle (6 consecutive cycles of 15 seconds cranking and 15 seconds rest).

The engines are rated at standard SAE conditions at


752.1 mmHg barometer and 25C (77F) inlet air temperature. (SAE = Society of Automotive Engineers).

Two systems for recharging the batteries are used:

Listed engines have an additional 10% power reserve


of the pumps maximum requirement.

An engine-driven generator/alternator recharging


the batteries when the diesel engine is running.
This system is completely independent of external
resources.

Instrumentation and control devices

Automatically controlled charger power supplied


from the building and fitted in the control panel.

The local instrumentation on the engine is shown in


fig. 21. The control panel monitoring the fire system is
described in a different data booklet.
XXXXXXXXX
1.Position MODE SELECTOR switch to MANUAL RUN.

Cooling water is piped through a threaded, rigid pipe


from the pump discharge to the inlet of the heat
exchanger. The wastewater can be discharged into a
visible, open waste cone or go back to a suction reservoir.

2.Lift and hold MANUAL CRANK #1 until engine starts, or release


after 15 seconds. If unit fails to start, wait for 15 seconds,
use MANUAL CRANK #2 and repeat step.
3.If COOLING WATER is not flowing or engine TEMPERATURE is too HIGH,
open cooling system manual by-pass valve.
TO STOP ENGINE
1.Push and hold MANUAL STOP until Engine Stops.

2.Return MODE SELECTOR switch to AUTOMATIC and MANUAL STOP position,


engine will stop.
3.Close cooling system manual by-pass valve.
IMPORTANT
DO leave
NOT the MODE SELECTOR switch in the MANUAL RUN position
during AUTOMATIC operation.
OVERSPEED RESET

XXXXXXX

1.After problem has been corrected, reset the speed sensing device by
lifting the OVERSPEED RESET and hold for 30 seconds.

10

11

12

TM03 5402 3606

Fig. 21 Instrumentation on the engine


Pos. Description

Engine cooling
The engine cooling system is of the closed-circuit heat
exchanger type.

TO START ENGINE

Both chargers must be listed for fire pumps.

Pos. Description

Tachometer (rpm) with


hourmeter (run time)

Manual start contactor 2

Mode selector switch

Overspeed verification

Manual operating
instructions

Engine oil pressure gauge

Warning light, red

10

Voltmeter for battery set 1

Overspeed reset switch

11

Voltmeter for battery set 2

Manual start contactor 1

12

Coolant temperature gauge

The heat exchanger has the best efficiency at 60 psi.

Engine exhaust
Each engine must have an independent exhaust system.
A flexible connection is used between the engine and
the exhaust pipe to provide thermal expansion and to
isolate engine vibration to the rest of the exhaust run.
The flex connector should not be used for misalignment.
The exhaust system must be building-supported, not
engine supported.

The engine requires these devices:

Fuel arrangement

a governor cable for regulating the engine speed


within a range of 10% between shut-off and maximum load

The fuel tank outlet must be placed above the engine


fuel inlet.

an overspeed shut-down device arranged to shut


down the engine at a speed approximately 20%
above the rated engine speed.

The fuel tank must be sized for 5.1 l/kW (1 gallon/hp)


plus 10% (5% for expansion and 5% for sump).
In zones with temperatures below 0C (32F), the fuel
tank shall be located in the pump room.
Fuel supply and return lines shall be flame-resistant,
reinforced flexible hose.

29

Engine construction

Fire DNF, Fire HSF

Coupling

TM03 5458 3606

The engine is connected to the pumps by means of a


PTO (Power Take-Off) shaft. See fig. 22.

Fig. 22 PTO shaft

30

Operating conditions
Pump unit location

Fire DNF, Fire HSF

Inlet pressure

The pump unit is designed for installation in a nonaggressive and non-explosive atmosphere.

Maximum inlet pressure


The inlet pressure is limited by the maximum operating
pressure. The maximum inlet pressure is 100 psi
(approx. 7 bar).

Ambient temperature
The ambient temperature must not exceed +25C
(77F).
If the ambient temperature exceeds +25C (77F) or if
the engine is installed more than 90 metres (300 ft)
above sea level, the engine power must be derated
according to figures 23 and 24. It may be necessary to
use an oversize engine with a higher output.

Minimum inlet pressure


The pressure at the pump suction flange must be 0 bar
(atmospheric pressure) or higher (positive inlet pressure) in any operating condition.

Ventilation requirements
The inlet louvre and ventilation system must ensure
that the temperature in the room does not exceed 49C
(120F) and supply adequate air for engine combustion.

P2
[%]
100

Adequate air for ventilating radiated heat; both engine


and exhaust system.

90
80
70

20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
T [C]
80

100

120

140

160

180 T [F]

Fig. 23 Relation between engine output (P2) and ambient


temperature

30

40

50

20

60

10

70
0
90

80

TM03 5501 3706

50

TM03 4718 2606

60

Fig. 25 Room ventilation

Minimum temperature of the pump room


4.5C (40F).

P2
[%]
100

Maximum temperature of the pump room


49C (120F) at the air cleaner inlet with the engine running at rated load.

90
80

Air humidity
The relative air humidity must not exceed 95%.

70

50
0

500 1000 1500 2000 2500 3000 3500 4000 4500 5000

[m]
0

2000

4000

6000 8000 10000 12000 14000

[ft]

TM03 4717 2606

60

Engine protection
The engine must be protected against possible interruption of operation through explosion, fire, flood,
earthquake, freezing and other adverse conditions.

Fig. 24 Relation between engine output (P2) and altitude

31

Installation

Fire DNF, Fire HSF

Piping

Alignment

When installing the pipes, make sure that the pump


housing is not stressed by the pipework.

The engine crankshaft and the pump shaft must be parallel aligned. We recommend a 3-degree disalignment
between the PTO shaft and the engine/pump shaft to
ensure even wear of the joints in the PTO shaft.

The suction and discharge pipes must be of an adequate size, taking the pump inlet pressure into account.
Install the pipes so that air locks are avoided, especially
on the suction side of the pump. See fig. 26.

The pump/engine alignment may be affected during


transport. Always check alignment after the pump has
been installed.

TM00 2263 3393

Take care to align carefully as this will increase the


working lives of the coupling, bearings and stuffing
boxes.

Fig. 26 Pipe sections

Fit isolating valves on either side of the pump to avoid


having to drain the system if the pump needs to be
cleaned or repaired.

30

40

50

20

60

10

70
0
90

Fig. 27 Example of piping, Fire DNF.

32

80

TM03 5499 4006

Make sure the pipes are adequately supported as close


to the pump as possible, both on the suction and on the
discharge side. The counter flanges should lie true
against the pump flanges without being stressed; otherwise, the pump will be damaged.

Bare shaft pumps

Fire DNF, Fire HSF

DNF

DNs

DNd

m2

TM03 4784 2806

n3

m1

n2
n1

Fig. 28 DNF bare shaft pump

Pump [mm]
Pump type DNs

DNF 65-20
DNF 65-25
DNF 80-20
DNF 80-25

DNd

100

65

125

80

a
100
125
125

500
500

Supporting feet [mm]

h1

h2

m1

m2

n1

n2

180

225

65

200

250

80

125

95

320

250

160

120

360

280

180

250

65

225

280

80

125

95

345

280

160

120

400

315

n3

110

370

110

370

Shaft [mm]
s1
M12
M16
M12
M16

s2

M12

32

80

M12

32

80

Pump
moment
of inertia
[kgm 2]

Weight
[kg]

100

0.0963

71

140

0.2357

69

140

0.1397

72

0.2476

82

33

Bare shaft pumps

Fire DNF, Fire HSF

HSF

Suction port

TM03 4593 2806

Discharge port

Fig. 29 HSF bare shaft pump

Pump type
HSF 5-11

Pump [mm]

DNs DNd
[in] [in]
6

HSF 6-12
HSF 6-16
HSF 8-17
10

HSF 10-20

12

10

Pump type
HSF 5-11

HSF 6-16

HSF 6-18
HSF 8-17
HSF 8-20
HSF 8-20G
HSF 10-16
HSF 10-20

34

h2

Supporting feet [mm]

sd

h1

hs

hd

ss

dd

305 203 171 171 337 318 36.6 35.0

406 175 305 127 25.4

89

19.0

254 194 210 391 375 41.1

368 152 457 197 28.4

86

22.4

476 203 432 191

86

19.0

330 305

635

375 483

858

419 305

724

476

857

457

863

381 289 232 273 409 438

502

883

432

838

302 229 267 406 432

394 502

896

483 381

864

406

476 610 1086 533 419

952

Weight
[kg]

39.688

70

51

9.52 x 4.76

175

102

76

12.7 x 6.35

343

39.668

89

51

9.52 x 4.76

359

47.625

102

76

12.7 x 6.35

398

102

76

12.7 x 6.35

461

124

102

12.7 x 6.35

606

57.150

124

102

12.7 x 6.35

696

63.500

127

95

15.9 x 7.94

910

28.4

378 274 330 489 527 30.2

457 353 274 305

Keyway

47.625

qs

qd

36.6

n1

n2

m1

m2

559 241 406 178

e1

25.4

102 25.4

353 254 305 483 502 47.8


457

521 660 1181 559 584 1143 495 404 279 356

47.625
58.150

736

db
db
Shaft [mm]
+0.000 +0.000
l
v
-0.013 -0.025

HSF 6-12

476 610 1086 508 533 1041

HSF 8-20G
HSF 10-16

af

330 406

381

HSF 6-18
HSF 8-20

527

514
584

31.8

41.1
30.2
47.8

559 241 483 210 28.4 102 25.4

559

241 559 241 28.4


216 660 292 31.8

102 25.4

Bare shaft pumps

Fire DNF, Fire HSF

Flange dimensions
DNF

HSF
D

K
K

DN

DN

Fig. 30 Flange for DNF end-suction pumps

Fig. 31 Flange for HSF horizontal split-case pumps

Flange dimensions to DIN 2533

Flange dimensions to ANSI B 16.1

d4

dz

65

185

145

20

122

4 x 18

80

200

160

22

138

8 x 18

100

220

180

24

158

8 x 18

125

250

210

26

188

8 x 18

DNs
Number of
class 125
holes
[inch]

Flange [mm]
D

254.0

215.9

279.4

241.3

342.9

298.5

10*

12

406.4

362.0

12

12

482.6

431.8

dz

For dimensions of
"qs" and "qd",
see page 34

Flange [mm]
D

22.2
22.2
22.2
25.4
25.4

*HSF 10-16 has DNs and DNd, class 125


DNd
Number of
class 250
holes
[inch]

Flange [mm]
D

279.4

235.0

12

317.5

269.7

12

381.0

330.2

10

16

444.5

387.4

12

16

520.7

450.9

dz

For dimensions of
"qs" and "qd",
see page 34

DNs and DNd

dz

TM03 4591 2306

dz

TM03 4592 2306

d4

22.2
22.2
25.4
28.58
31.75

35

Curve charts

Fire DNF, Fire HSF

How to read the curve charts


The solid line represents the
rated flow at which the pump has
been FM-approved and UL-listed.

QH curve for the


individual pump
Size of impeller

H
[m]

p
[psi]

DNF 80-20

90

2-pole, 50 Hz
/210

60

/205

80

50

ISO 9906 Annex A

Pump type and nominal


pump speed.

/200

70

60
40

The broken line represents


the maximum permissible
flow at which the pump has
been FM-approved and ULlisted.

50
30
40

20

30

20
0

100

P2
[kW]

P2
[hp]

30

40

200

300

40

400
80

500

600

120

700

800

Q [US GPM]

160

200

Q [m/h]

The power curve indicates


pump input power, P2, for
the individual pump.

/210
/205

25

/200

35
30

20
25
15

20
15
0

100

200

300

400

500

600

700

800

Q [US GPM]

Eta
[%]

The eta curve indicates


the pump efficiency for
the individual pump.

80
70
60
/205

50

/210

/200
40
30

36

100

200

300

400

500

600

700

800

Q [US GPM]

TM02 9834 5004

20

Curve charts

Fire DNF, Fire HSF

Guide

Curve conditions

The tables above the curve charts on the following


pages show these data:

Selection of pumps

the FM-approved and UL-listed pressure range


the Clarke range of engines.
FM-approved and UL-listed pressure range
Example: DNF 80-20, 500 gpm

Pressure range
[psi]

FM-approved:
UL-listed:
FM and UL:

FMapproved

ULlisted

64-72

67-75

Emerson and WEG range of engines


Example: DNF 80-20 500 gpm

65-75

JU4H-UF14

The curves show pump performance with different


impeller diameters at the nominal speed.

Calculation of total head

The curve charts show curves at 5 psi pressure intervals, in this example at 65, 70 and 75 psi.
If a duty point at 65 psi is required, the pump will only
be FM approved.

Engine type

Tolerances according to ISO 9906, Annex A.

The curves apply to the pumping of water at a temperature of +20C (68F) and a kinematic viscosity
of 1 mm2/s (1 cSt).

64-72 psi
67-75 psi
67-72 psi

Pressure range
[psi]

The guidelines below apply to the performance curves


shown in the curve charts, pages 38 to 73.

The total pump head consists of the height difference


between the measuring points + the differential head +
the dynamic head.
H

total

= H

geo

+H

stat

+H

dyn

Hgeo: Height difference between measuring points.

Rated power
[kW]

[hp]

52.6

70.5

The engine type, JU4H-UF14, covers the whole pressure range. For more specific information on the
engines, see Engine construction, pages 27 to 30, and
Diesel engine data, pages 25 to 26.

Hstat: Differential head between the suction and the


discharge side of the pump.
Hdyn: Calculated values based on the velocity of the
pumped water on the suction and the discharge
side of the pump.

Performance tests
The requested duty point for every pump is tested
according to ISO 9906, Annex A.
If the customer requires either more points on the curve
to be checked or certain minimum performances or certificates, individual measurements must be made.

FM/UL certificates
The pump order includes a test certificate confirming
the required QH performance. See page 5.

37

Performance curves, DNF

DNF 65-20
250 gpm, 66-80 psi

250 gpm, 66-80 psi


FM-approved

UL-listed

66-80

Pressure range
[psi]

H
[m]

Pressure range
[psi]

Engine type

66-80

JU4H-UF14

p
[psi]

Rated power
[kW]

[hp]

53

71

DNF 65-20

90
60
80

/208

n nom = 2900 min-1

/202

ISO 9906 Annex A

/195
50

70

/190

60
40
50
30

20

40
30
20

10
10
0

0
0

50

P2
[kW]

100

150

20

200
40

250

300

60

350

400

80

450

500

100

Q [US GPM]
120

P2
[hp]

Q [m/h]

30
20

/208
/202
/195
/190

25
15

10

20
15
10

5
5
0

50

100

150

200

250

300

350

400

450

500

Q [US GPM]

Eta
[%]
70
60
50
40

20

/190

10
0

38

/208
/195 /202

50

100

150

200

250

300

350

400

450

500

Q [US GPM]

TM03 8222 0907

30

Performance curves, DNF

DNF 65-25
250 gpm, 116-130 psi

250 gpm, 116-130 psi


FM-approved
Pressure range
[psi]

H
[m]
100

116-129

UL-listed
120-130

Pressure range
[psi]

Engine type

116-130

JU4H-UF14

p
[psi]

Rated power
[kW]

[hp]

53

71

DNF 65-25

140

n nom = 2900 min-1


ISO 9906 Annex A

90

/260
/258

130

/253
/250

120
80
110

70

100

90
60
80

50

70
0

P2
[kW]

P2
[hp]

50

100

150

20

200
40

250

300

60

350

400

80

450
100

60
50

20

Q [m/h]

/260
/258
/253
/250

40

30

Q [US GPM]

40
30
20

10
10
0
0

50

100

150

200

250

300

350

400

450

Q [US GPM]

Eta
[%]
60

/260
/258
/253

50
/250
40
30
20
10
0

50

100

150

200

250

300

350

400

450

Q [US GPM]

TM03 8223 0907

39

Performance curves, DNF

DNF 65-25
300 gpm, 119-129 psi

300 gpm, 119-129 psi


FM-approved
Pressure range
[psi]

H
[m]
100

120-127

UL-listed
119-129

Pressure range
[psi]

Engine type

119-129

JU4H-UF14

p
[psi]

[hp]

53

71

DNF 65-25

140

n nom = 2900 min-1


/260

90

Rated power
[kW]

130

ISO 9906 Annex A

/255
/250

120
80
110

70

100

90
60
80
50

70

60
0

50

P2
[kW]

100

150

20

200
40

250

300

60

350

400

80

450
100

Q [US GPM]
120

P2
[hp]

Q [m/h]

/260
/255
/250

50
30

500

40

30
20
20
10
10
0

50

100

150

200

250

300

350

400

450

500

Q [US GPM]

Eta
[%]
60
/250

50

/260
/255

40

20
10
0

40

50

100

150

200

250

300

350

400

450

500

Q [US GPM]

TM03 8224 0907

30

Performance curves, DNF

DNF 80-20
500 gpm, 64-75 psi

500 gpm, 64-75 psi


FM-approved
Pressure range
[psi]

H
[m]

64-72

UL-listed
67-75

Pressure range
[psi]

Engine type

64-75

JU4H-UF14

p
[psi]

[hp]

53

71

DNF 80-20

90

n nom = 2900 min-1


/210

60

ISO 9906 Annex A

/205

80

50

Rated power
[kW]

/200

70

60
40
50
30
40

20

30

20
0

100

P2
[kW]

P2
[hp]

30

40

200

300

40

400
80

500

600

120

700

800

Q [US GPM]

160

200

Q [m/h]

/210
/205

25

/200

35
30

20
25
20
15
0

100

200

300

400

500

600

700

800

Q [US GPM]

Eta
[%]
80
70
60
/205

50

/210

/200
40
30
20
0

100

200

300

400

500

600

700

800

Q [US GPM]

TM03 8225 0907

15

41

Performance curves, DNF

DNF 80-25
500 gpm, 101-125 psi

500 gpm, 101-125 psi


FM-approved
Pressure range
[psi]

H
[m]
90

101-125

106-125

Engine type

101-115

JU4H-UF14

53

71

120-125

JU4H-UF24

61

82

80
110

[kW]

[hp]

DNF 80-25

/260
/256
/251
/246
/242
/240

130

Rated power

Pressure range
[psi]

p
[psi]

120

70

UL-listed

n nom = 2900 min-1


ISO 9906 Annex A

100
90

60
80
50

40

70
60
50

30

40
30
0

P2
[kW]

P2
[hp]

60

80

50

100
20

200
40

300
60

400
80

500
100

120

600
140

700
160

800
180

Q [US GPM]
200

Q [m/h]

/260
/256
/251
/246
/242

70
60
/240

40
50
30

20

40
30
20
0

100

200

300

400

500

600

700

800

Q [US GPM]

Eta
[%]
70
60
50

/240
/242
/246

30

/260
/256
/251

20
10
0

42

100

200

300

400

500

600

700

800

Q [US GPM]

TM03 8226 0907

40

Performance curves, HSF

HSF 6-12
500 gpm, 40-49 psi

500 gpm, 40-49 psi


FM-approved

UL-listed

40-49

40-49

Pressure range
[psi]

H
[m]

Pressure range
[psi]

Engine type

40-49

JU4H-UF58

p
[psi]

Rated power
[kW]

[hp]

59

79

HSF 6-12
n nom = 1450 min-1

60
40

ISO 9906 Annex A


/311
/301

50

/286
30
40

20

30

20
10
10

P2
[kW]
25

P2
[hp]

200

50

400
100

600

800

150

1000
200

1200
250

1400
300

Q [US GPM]
350

Q [m/h]

35
/311

30

/301

20
25
15

10

/286

20
15
10
0

200

400

600

800

1000

1200

1400

Q [US GPM]

Eta
[%]
70
60
50
40
30
/286
20

/301

/311

10
0

200

400

600

800

1000

1200

1400

Q [US GPM]

TM03 8227 0907

43

Performance curves, HSF

HSF 6-12
750 gpm, 41-69 psi

750 gpm, 41-69 psi


FM-approved
Pressure range
[psi]

H
[m]

41-66

UL-listed
42-69

Pressure range
[psi]

Engine type

41-50
55-69

[hp]

JU4H-UF10

31

41

JU4H-UF20

45

60

p
[psi]

HSF 6-12

80
50

Rated power
[kW]

n nom = 1750 min-1

/311
/304

70

ISO 9906 Annex A

/292
/281

60

/270
/259
/254

40
50
30
40

20

30

20
10
10

P2
[kW]

P2
[hp]

200

50

400
100

600

800

150

1000
200

1200
250

1400
300

1600
350

1800

Q [US GPM]

400

Q [m/h]

60

/311
/304

40
50
30

20

/292
/281
/270
/259
/254

40
30
20

10
10
0

200

400

600

800

1000

1200

1400

1600

1800

Q [US GPM]

Eta
[%]
70
60
50
40
/311
/259
/270

20

/281

/304
/292

10
0

44

200

400

600

800

1000

1200

1400

1600

1800

Q [US GPM]

TM03 8228 0907

/254

30

Performance curves, HSF

HSF 5-11
750 gpm, 67-127 psi

750 gpm, 67-127 psi


FM-approved
Pressure range
[psi]

67-127

H
[m]

p
[psi]

100

140

UL-listed
67-127

Engine type

67-90

JU4H-UF14

53

71

95-105

JU4H-UF24

61

82

110-127

JU4H-UF34

82

110

[kW]

[hp]

HSF 5-11
n nom = 2900 min-1

/266
/261
120

ISO 9906 Annex A

/251

80

/241
/230

100

/218
/210

60
80

40

Rated power

Pressure range
[psi]

60

40
20
20

P2
[kW]

P2
[hp]

200

50

400
100

600

800

150

1000
200

1200
250

1400
300

1600
350

1800
400

100
60

40

Q [US GPM]
Q [m/h]

/266
/261
/251
/241
/230

80
60

/218
/210

40
20
20
0
0

200

400

600

800

1000

1200

1400

1600

1800

Q [US GPM]

Eta
[%]
80
70
60
50
40
30

/210

20
0

200

400

600

800

1000

1200

1400

/266
/218 /230 /241 /251 /261

1600

1800

Q [US GPM]

TM03 8229 0907

45

Performance curves, HSF

HSF 6-16
750 gpm, 47-88 psi

750 gpm, 47-88 psi


FM-approved
Pressure range
[psi]

UL-listed

54-88

H
[m]

p
[psi]

70

100

47-88

Pressure range
[psi]

Engine type

47-80
85-88

59

79

JU6H-UF30

70

94

n nom = 1450 min-1

/419

ISO 9906 Annex A

/407
/395
/383
/370
/358

60
80

40

[hp]

JU4H-UF58

HSF 6-16

90

50

Rated power
[kW]

70

/344
/331
/317

60
50

30

20

40
30
20

10
10
0

0
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

Q [US GPM]

500

Q [m/h]

100
60

40

/419
/407
/395
/383
/370
/358
/344
/331
/317

80
60
40

20
20
0

0
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

Eta
[%]
90
80
70
60
50

/317
/331

30
20
0

46

200

400

600

800

1000

1200

1400

1600

1800

/419
/407
/344 /358 /370 /383 /395

2000

2200

Q [US GPM]

TM03 8230 0907

40

Performance curves, HSF

HSF 6-18
750 gpm, 60-104 psi

750 gpm, 60-104 psi


FM-approved
Pressure range
[psi]

H
[m]

62-103

UL-listed
60-104

Pressure range
[psi]

Engine type

60-70

[hp]

JU4H-UF58

59

79

75-85

JU6H-UF30

70

94

90-104

JU6H-UF58

103

138

p
[psi]

HSF 6-18

110
70

90
80

40

n nom = 1450 min-1

/438
/432
/421
/410
/399
/387
/375
/363

100

60

50

Rated power
[kW]

70

ISO 9906 Annex A

/343

60
50

30

20

40
30
20

10
10
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

Q [US GPM]

500

Q [m/h]

/438
/432
/421
/410
/399
/387
/375
/363

120
80
100
60

40

80
60

/343

40
20
20
0
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

Eta
[%]
90
80
70
60

/438

/343

/363
/432
/375
/421
/387 /399 /410

50
40
30
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

TM03 8231 0907

47

Performance curves, HSF

HSF 6-16
1000 gpm, 50-86 psi

1000 gpm, 50-86 psi


FM-approved
Pressure range
[psi]

H
[m]

p
[psi]

70

100

UL-listed

50-86

50-86

Pressure range
[psi]

Engine type

50-80
85-86

Rated power
[kW]

[hp]

JU4H-UF58

59

79

JU6H-UF30

70

94

HSF 6-16

90
60

/422

n nom = 1450 min-1

/410

ISO 9906 Annex A

/397
80

/385
/373

50

70

/360
/347

60
40

/335
50

30

20

40
30
20

10
10
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

Q [US GPM]

500

Q [m/h]

90
60

80

50

70

/422
/410
/397
/385
/373
/360
/347
/335

60
40
30
20

50
40
30
20

10

10
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

Eta
[%]
90
80
70
60

40

/442
/410

/335
30

/347 /360 /373 /385 /397

20
0

48

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

TM03 8232 0907

50

Performance curves, HSF

HSF 6-18
1000 gpm, 59-103 psi

1000 gpm, 59-103 psi


FM-approved
Pressure range
[psi]

H
[m]

83-102

UL-listed
59-103

Pressure range
[psi]

Engine type

59-70

Rated power
[kW]

[hp]

JU4H-UF58

59

79

75-83

JU6H-UF30

70

94

85-103

JU6H-UF58

103

138

p
[psi]

HSF 6-18

110

n nom = 1450 min-1


70

/435
/425
/415
/403
/392
/380
/368
/356
/344

100
90

60
80
50

40

70
60

ISO 9906 Annex A

50
30

20

40
30
20

10
10
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

100

40

Q [US GPM]

500

Q [m/h]

/435
/425
/415
/403
/392
/380
/368
/356
/344

120
80

60

2200

80
60
40

20
20
0
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

Eta
[%]
90
80
70
60
/435

/344

50

/356
/368
/380

40

/425
/415
/392 /403

30
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

TM03 8233 0907

49

Performance curves, HSF

HSF 6-16
1000 gpm, 102-130 psi

1000 gpm, 102-130 psi


FM-approved
Pressure range
[psi]

H
[m]

102-129

UL-listed
102-130

Engine type

102-105

JU4H-UF58

82

110

110-125

JU6H-UFG8

111

149

130

JU6H-UF58

137

183

p
[psi]
/425
/418
/412
/403
/394
/385

130
120

80
110
70

[kW]

[hp]

HSF 6-16

140
90

Rated power

Pressure range
[psi]

n nom = 1750 min-1


ISO 9906 Annex A

100
90

60
80
50

40

70
60
50

30

40
30
0

200

P2
[kW]
100

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

2400

500

600

P2
[hp]
120
100

40

Q [m/h]

/425
/418
/412
/403
/394
/385

140

80

60

Q [US GPM]

80
60
40

20

20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

Eta
[%]
90
80
70
60
/385

50

/425

/394 /403 /412 /418

30
20
0

50

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

TM03 8234 0907

40

Performance curves, HSF

HSF 6-18
1000 gpm, 129-150 psi

1000 gpm, 129-150 psi


FM-approved
Pressure range
[psi]

H
[m]

129-145

UL-listed
132-150

Rated power

Pressure range
[psi]

Engine type

129-135

JU6H-UF58

137

183

140

JU6H-UF68

149

200

145-150

JW6H-UF38

188

252

p
[psi]

[kW]

[hp]

HSF 6-18

160

n nom = 1750 min-1

110

ISO 9906 Annex A


150

/445
/438

100

90

140

/430
/423
/419

130

120
80
110

70

100

90
60
80
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

Q [US GPM]

500

Q [m/h]

200

/445
/438
/430
/423
/419

140
180
120

160

100

140
120

60
40

100
80
60
40
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

Eta
[%]
90
80
/419 /423 /430 /438 /445
70
60
50
40
30
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

TM03 8249 0907

80

51

Performance curves, HSF

HSF 6-12
1000 gpm, 109-194 psi

1000 gpm, 109-194 psi


FM-approved
Pressure range
[psi]

H
[m]

UL-listed

109-191

115-194

Pressure range
[psi]

Engine type

109-120

[hp]

JU4H-UF54

108

145

125-135

JU6H-UF34

125

168

140-170

JU6H-UF54

161

216

175-194

JU6H-UF84

199

267

p
[psi]

HSF 6-12

220
140

ISO 9906 Annex A

/302
/295

180

/286
/278
/269
/261
/252

160

80

n nom = 2900 min-1

/310

200

120

100

Rated power
[kW]

140

/242

120
100

60

40

80
60
40

20
20
0

P2
[kW]

P2
[hp]

200

400

600

100

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
200

300

400

500

600

160
200

80

Q [m/h]

/310
/302
/295
/286
/278
/269
/261
/252
/242

240

120

Q [US GPM]

160
120
80

40
40
0

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Q [US GPM]

Eta
[%]
90
80
70
60

/242
/252
/261
/269 /278

40
30
0

52

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

/310
/302
/295
/286

Q [US GPM]

TM03 8235 0907

50

Performance curves, HSF

HSF 6-18
1250 gpm, 76-98 psi

1250 gpm, 76-98 psi


FM-approved
Pressure range
[psi]

H
[m]

76-96

UL-listed
80-98

Engine type

76-80

JU6H-UF30

70

94

85-98

JU6H-UF58

103

138

p
[psi]

[kW]

[hp]

HSF 6-18

110
70

Rated power

Pressure range
[psi]

n nom = 1450 min-1

/445
/435
/425
/415
/405

100
90

60

ISO 9906 Annex A

80
50

70
60

40
50
30

20

40
30
20
0

200

P2
[kW]

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

Q [US GPM]
500

120

/445
/435
/425
/415
/405

80
100
60

40

Q [m/h]

P2
[hp]

80
60
40

20
20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

Q [US GPM]

Eta
[%]
90
80
/445

70
/405
60

/415

/435
/425

50

30
20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

Q [US GPM]

TM03 8236 0907

40

53

Performance curves, HSF

HSF 6-16
1250 gpm, 95-126 psi

1250 gpm, 95-126 psi


FM-approved
Pressure range
[psi]

H
[m]

98-125

UL-listed
95-126

Engine type

95-100

JU4H-UF58

82

110

105-115

JU6H-UF30

104

140

120

JU6H-UFG8

111

149

125-126

JU6H-UF58

137

183

p
[psi]
/425
/417
/409
/400
/391
/382

130
120

80
110
70

[kW]

[hp]

HSF 6-16

140
90

Rated power

Pressure range
[psi]

n nom = 1750 min-1


ISO 9906 Annex A

100
90

60
80
50

40

70
60
50

30

40
30
0

200

P2
[kW]
100

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200
500

P2
[hp]
120
100

40

Q [US GPM]
600

Q [m/h]

/425
/417
/409
/400
/391
/382

140

80

60

2400

80
60
40

20

20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

Eta
[%]
90
80
70
60
/382
/425
/391 /400 /409 /417

50

30
20
0

54

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

TM03 8250 0907

40

Performance curves, HSF

HSF 6-12
1250 gpm, 104-187 psi

1250 gpm, 104-187 psi


FM-approved
Pressure range
[psi]

H
[m]

UL-listed

104-187

106-186

Engine type

104-115

JU4H-UF54

108

145

120-130

JU6H-UF34

125

168

135-160

JU6H-UF54

161

216

165-187

JU6H-UF84

199

267

p
[psi]

[kW]

[hp]

HSF 6-12

220
140

Rated power

Pressure range
[psi]

n nom = 2900 min-1

/311
/303

200

ISO 9906 Annex A

/295
/287
/279

180
120
160

/267
100

80

/258
/249
/241

140
120
100

60

40

80
60
40

20
20
0

P2
[kW]

P2
[hp]

200

400

600

100

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
200

300

400

500

600

Q [m/h]
/311
/303
/295
/287
/279

240
160
200
120

80

Q [US GPM]

160

/267
/258
/249
/241

120
80

40
40
0

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Q [US GPM]

Eta
[%]
90
80
70

50
/241
/249
/258
/267

40
30
0

200

400

600

/279

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

/311
/303
/295
/287

Q [US GPM]

TM03 8237 0907

60

55

Performance curves, HSF

HSF 6-18
1250 gpm, 126-149 psi

1250 gpm, 126-149 psi


FM-approved
Pressure range
[psi]

H
[m]

126-144

UL-listed
130-149

Rated power

Pressure range
[psi]

Engine type

126-135

JU6H-UF58

137

183

140

JU6H-UF68

149

200

144-149

JW6H-UF38

188

252

p
[psi]

[kW]

[hp]

HSF 6-18

160

n nom = 1765 min-1

110

ISO 9906 Annex A


150
/440
100

90

/432

140

/425
/419

130

120
80
110

70

100

90
60
80
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

Q [US GPM]

500

Q [m/h]

200

/440
/432
/425
/419

140
180
120

160

100

140
120

80
60
40

100
80
60
40
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

Eta
[%]
90
80
/419 /425 /432 /440
70
60

40
30
0

56

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

Q [US GPM]

TM03 8252 0907

50

Performance curves, HSF

HSF 6-18
1250 gpm, 162-191 psi

1250 gpm, 162-191 psi


FM-approved
Pressure range
[psi]

H
[m]

140

162-191

110

162-189

Pressure range
[psi]

Engine type

162-180
170-191

p
[psi]

Rated power
[kW]

[hp]

JW6H-UF30

203

272

JW6H-UF40

222

297

210

HSF 6-18

200

n nom = 2000 min-1

190

/445
/440

180

/432
/425

130

120

UL-listed

170

ISO 9906 Annex A

/415

160
150

100

90

140
130
120

80

70

110
100
90
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

2400

500

Q [US GPM]
600

Q [m/h]

/445
/440
/432
/425

300
200
250
/415
150

100

200
150
100

50
50
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

Eta
[%]
90
80

/415

/445
/425 /432 /440

70
60
50

30
20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

TM03 4222 1906

40

57

Performance curves, HSF

HSF 8-20
1500 gpm, 75-101 psi

1500 gpm, 75-101 psi


FM-approved
Pressure range
[psi]

H
[m]

UL-listed

75-100

76-101

Pressure range
[psi]

Engine type

75-101

JU6H-UF58

p
[psi]

[hp]

103

138

HSF 8-20

110

/470

n nom = 1450 min-1

/459
70

Rated power
[kW]

100

ISO 9906 Annex A

/448
/437

90

/425
/414

60
80
50

70
60

40
50
30

20

40
30
20
0

P2
[kW]

P2
[hp]

200

400

600

100

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
200

300

400

500

Q [US GPM]

600

Q [m/h]

160
100

/470

140

/459
/448
/437
/425
/414

120
80
100
60
40

80
60
40

20

20
0

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Q [US GPM]

Eta
[%]
90
80
70

/470

/414
/425
/437

60

/459
/448

40
30
0

58

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Q [US GPM]

TM03 8238 0907

50

Performance curves, HSF

HSF 8-20G
1500 gpm, 79-123 psi

1500 gpm, 79-123 psi


FM-approved
Pressure range
[psi]

H
[m]
90

80-123

79-123

Rated power

Pressure range
[psi]

Engine type

79-80

JU6H-UF58

103

138

85-100

JU6H-UF68

131

176

105-120

JW6H-UF30

164

220

123

JW6H-UF48

179

240

p
[psi]

[kW]

[hp]

HSF 8-20G

130

n nom = 1450 min-1

/500
/491
/481
/470
/459
/448
/436
/425
/413

120
80
110
70

UL-listed

100
90

60

ISO 9906 Annex A

80
50

40

70
60
50

30

20

40
30
20
0

P2
[kW]

P2
[hp]

400
100

800
200

1200
300

1600

2000

400

2400
500

2800
600

3200
700

3600
800

4000

Q [US GPM]

900

Q [m/h]

240
160
200
120

80

160
120
/413

/500
/491
/481
/470
/459
/448
/436
/425

80
40
40
0
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

Q [US GPM]

Eta
[%]
90
80
70
60

/413
/425
/436
/448

50
40

/500
/491
/481
/459 /470

30
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

Q [US GPM]

TM03 8239 0907

59

Performance curves, HSF

HSF 10-20
1500 gpm, 95-118 psi

1500 gpm, 95-118 psi


FM-approved
Pressure range
[psi]

H
[m]
90

95-118

95-117

Rated power

Pressure range
[psi]

Engine type

95

JW6H-UF30

164

220

100-105

JW6H-UF48

179

240

110-118

JX6H-UF30

261

350

p
[psi]

[kW]

[hp]

HSF 10-20

130

n nom = 1450 min-1

/483
/476
/465
/455
/444
/433

120
80
110
70

UL-listed

100

ISO 9906 Annex A

90
60
80
50

40

70
60
50

30

20

40
30
20
0

P2
[kW]
200

P2
[hp]

500

1000

1500

200

2000
400

2500

3000

600

3500

4000

800

4500

5000

1000

1200

240
200

80

Q [m/h]

/483
/476
/465
/455
/444
/433

280

160

120

Q [US GPM]

160
120
80

40

40
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

Q [US GPM]

Eta
[%]
90
80
70
/483

/433
/444
/455

50

/476
/465

40
30
0

60

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

Q [US GPM]

TM03 8240 0907

60

Performance curves, HSF

HSF 6-18
1500 gpm, 98-142 psi

1500 gpm, 98-142 psi


FM-approved
Pressure range
[psi]

H
[m]

98-141

90

Engine type

98-120

JU6H-UF58

137

183

125-130

JU6H-UF68

149

200

135-142

JW6H-UF38

188

252

140
130

[kW]

[hp]

HSF 6-18

/444
/436
/428
/422
/414

n nom = 1750 min-1


ISO 9906 Annex A

/405
/396
/390
/381

120
80
110
70

109-142

Rated power

Pressure range
[psi]

p
[psi]
150

100

UL-listed

100
90

60
80
50

40

70
60
50

30

40
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

2400

500

600

240
200

80

Q [m/h]

/444
/436
/428
/422
/414
/405
/396
/390
/381

160

120

Q [US GPM]

160
120
80

40
40
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

Eta
[%]
80
70

/444
/381

/436
/390
/422
/405
/428
/414
/396

60
50

30
20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

TM03 8253 0907

40

61

Performance curves, HSF

HSF 6-12
1500 gpm, 116-179 psi

1500 gpm, 116-179 psi


FM-approved
Pressure range
[psi]

H
[m]

UL-listed

116-176

119-179

Engine type

116-130

JU6H-UF34

125

168

135-155

JU6H-UF54

161

216

160-179

JU6H-UF84

199

267

p
[psi]

180

ISO 9906 Annex A

/289
/281
/273
/266

160

80

[hp]

n nom = 2900 min-1

/310
/306
/298

200

120

100

[kW]

HSF 6-12

220
140

Rated power

Pressure range
[psi]

140
120
100

60

40

80
60
40

20
20
0

P2
[kW]

P2
[hp]

200

400

600

100

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
200

300

400

500

600

240
200

80

Q [m/h]

/310
/306
/298
/289
/281
/273
/266

160

120

Q [US GPM]

160
120
80

40
40
0

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Q [US GPM]

Eta
[%]
90
80
70
60

/266

/310

50
40
30
0

62

200

400

600

800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

Q [US GPM]

TM03 8241 0907

/306
/273
/281 /289 /298

Performance curves, HSF

HSF 6-18
1500 gpm, 188-190 psi

1500 gpm, 188-190 psi


FM-approved
Pressure range
[psi]

H
[m]

p
[psi]

140

200

UL-listed

188

190

Pressure range
[psi]

Engine type

188-190

JW6H-UF40

Rated power
[kW]

[hp]

222

297

HSF 6-18

/445

n nom = 2000 min-1


180

ISO 9906 Annex A

120
160
100

80

140
120
100

60

40

80
60
40

20
20
0

0
0

P2
[kW]

P2
[hp]

200

400

600

100

800

1000

1200

200

1400

1600

300

1800

2000

400

2200

2400

500

Q [US GPM]
600

300

Q [m/h]

/445

200
250
150

100

200
150
100

50
50
0
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

Eta
[%]
90
80

/445

70
60
50
40
30
20
0

200

400

600

800

1000

1200

1400

1600

1800

2000

2200

2400

Q [US GPM]

TM03 4240 1906

63

Performance curves, HSF

HSF 8-17
2000 gpm, 56-86 psi

2000 gpm, 56-86 psi


FM-approved
Pressure range
[psi]

H
[m]

p
[psi]

70

100

56-84

UL-listed
57-86

Pressure range
[psi]

Engine type

56-75
80-86

Rated power
[kW]

[hp]

JU6H-UF58

103

138

JU6H-UF68

131

176

HSF 8-17
n nom = 1450 min-1
/427

90

ISO 9906 Annex A

/415

60
/400
/390

80
50

/375

70

/362

60
40
50
30
40

20

30

20
0

400

P2
[kW]

800

1200

200

1600

2000

2400

400

2800

3200

600

3600

Q [US GPM]

800

Q [m/h]

P2
[hp]

/427

160

/415
100

140

/400
/390

120

/375
/362

80
100
60

40

80
60
40
0

400

800

1200

1600

2000

2400

2800

3200

3600

Q [US GPM]

Eta
[%]
90
/427

/362

80

/375 /390 /400 /415


70
60

40
30
0

64

400

800

1200

1600

2000

2400

2800

3200

3600

Q [US GPM]

TM03 8242 0907

50

Performance curves, HSF

HSF 10-20
2000 gpm, 93-116 psi

2000 gpm, 93-116 psi


FM-approved
Pressure range
[psi]

H
[m]

93-116

94-115

Engine type

93-95

JW6H-UF30

164

220

100-105

JW6H-UF48

179

240

110-116

JX6H-UF30

261

350

100

[hp]

n nom = 1450 min-1

/467
/457
/447

110

[kW]

HSF 10-20

/478

80

Rated power

Pressure range
[psi]

p
[psi]
120

70

UL-listed

ISO 9906 Annex A

/432

90
60
80
50

40

70
60
50

30

20

40
30
20
0

400

P2
[kW]
200

800

1200

200

1600

2000

2400

400

2800

3200

600

3600

4000

800

4400

Q [US GPM]

1000

Q [m/h]

P2
[hp]
280

/478
/467
/457
/447
/432

240
160
200
120
80

160
120
80
40
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

4400

Q [US GPM]

Eta
[%]
90
80
/432
70

/478
/447 /457 /467

60
50
40
30
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

4400

Q [US GPM]

TM03 8243 0907

40

65

Performance curves, HSF

HSF 8-20G
2000 gpm, 94-120 psi

2000 gpm, 94-120 psi


FM-approved
Pressure range
[psi]

H
[m]
90

98-120

94-119

130

Engine type

94-95

JU6H-UF58

103

138

98-105

JU6H-UF68

131

176

110-119

JW6H-UF30

164

220

120

JW6H-UF48

179

240

110
100

[kW]

[hp]

HSF 8-20G

/508
/498
/488
/477
/467
/457

80

Rated power

Pressure range
[psi]

p
[psi]

120

70

UL-listed

n nom = 1450 min-1


ISO 9906 Annex A

90
60
80
50

40

70
60
50

30

20

40
30
20
0

P2
[kW]

P2
[hp]

400
100

800
200

1200
300

1600

2000

400

2400
500

2800
600

3200
700

3600
800

4000
900

240
200

80

Q [m/h]

/508
/498
/488
/477
/467
/457

160

120

Q [US GPM]

160
120
80

40
40
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

Q [US GPM]

Eta
[%]
90
80
70
60
/467
/477

40

/498
/488

30
0

66

400

800

1200

1600

2000

2400

2800

3200

3600

4000

Q [US GPM]

TM03 8244 0907

/508

/457
50

Performance curves, HSF

HSF 8-20
2000 gpm, 105-141 psi

2000 gpm, 105-141 psi


FM-approved
Pressure range
[psi]

H
[m]
110

105-139

90

70

Engine type

105-110

JU6H-UF68

149

200

115-135

JW6H-UF38

188

252

139-141

JW6H-UF60

268

360

[kW]

[hp]

HSF 8-20

160

n nom = 1770 min-1

/459
/451
/443
/436
/428
/420
/412
/406

140
130
120

80

108-141

Rated power

Pressure range
[psi]

p
[psi]
150

100

UL-listed

ISO 9906 Annex A

110
100
90

60
80
50

40

70
60
50

30

40
0

P2
[kW]
200

P2
[hp]

400
100

800
200

1200
300

1600

2000

400

2400
500

2800
600

3200
700

280

160
200

80

800

4000

Q [US GPM]

900

Q [m/h]

/459
/451
/443
/436
/428
/420
/406 /412

240

120

3600

160
120
80
40
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

Q [US GPM]

Eta
[%]
90
80
70

/406
/412
/420
/428

60

/459
/451
/443
/436

50
40
30
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

Q [US GPM]

TM03 8254 0907

40

67

Performance curves, HSF

HSF 8-20G
2000 gpm, 125-148 psi

2000 gpm, 125-148 psi


FM-approved
Pressure range
[psi]

H
[m]

125-146

90

131-148

Pressure range
[psi]

Engine type

125-135
140-148

p
[psi]
150

100

UL-listed

[hp]

JW6H-UF58

224

300

JW6H-UF60

268

360

HSF 8-20G

/453
/446
/438
/434

140

Rated power
[kW]

n nom = 1770 min-1


ISO 9906 Annex A

130
120

80

70

110
100
90

60
80
50

40

70
60
50

30

40
30
0

P2
[kW]

P2
[hp]

240

320

200

400
100

800
200

1200
300

1600
400

2000

2400

500

2800
600

3200
700

3600
800

4000

4400

900

1000

Q [US GPM]
1100

Q [m/h]

/453
/446
/438
/434

280
240

160
200
120

80

160
120
80
0

400

800

1200

1600

2000

2400

2800

3200

3600

4000

4400

Q [US GPM]

Eta
[%]
90
80
70

50

/453
/434
/438 /446

40
30
0

68

400

800

1200

1600

2000

2400

2800

3200

3600

4000

4400

Q [US GPM]

TM03 8255 0907

60

Performance curves, HSF

HSF 10-16
2500 gpm, 49-81 psi

2500 gpm, 49-81 psi


FM-approved
Pressure range
[psi]

UL-listed

49-81

H
[m]

p
[psi]

70

100

50-81

Pressure range
[psi]

Engine type

49-50

Rated power
[kW]

[hp]

JU6H-UF58

103

138

55-65

JU6H-UF68

131

176

70-80

JW6H-UF30

164

220

81

JW6H-UF48

179

240

HSF 10-16
n nom = 1450 min-1
/406

90

ISO 9906 Annex A

/392

60

/380

80

/367
50

/355

70

/340
60
40

/330
50

30

20

40
30
20

10
10
0

500

P2
[kW]

1000
200

1500

2000

400

2500

3000

600

3500

4000

800

4500

5000

1000

5500

1200

P2
[hp]

Q [US GPM]
1400 Q

[m/h]

240
/406

160

/392
/380
/367
/355
/340
/330

200
120

80

160
120
80

40
40
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Q [US GPM]

Eta
[%]
90
/406

/330

80

/340 /355 /367 /380 /392

70
60

40
30
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Q [US GPM]

TM03 8245 0907

50

69

Performance curves, HSF

HSF 10-20
2500 gpm, 88-111 psi

2500 gpm, 88-111 psi


FM-approved
Pressure range
[psi]

H
[m]

88-111

89-111

Pressure range
[psi]

Engine type

88-90

Rated power
[kW]

[hp]

JW6H-UF30

164

220

95-100

JW6H-UF48

179

240

105-111

JX6H-UF30

261

350

p
[psi]

HSF 10-20

120
110

/475
/466
/457
/448

100

/437

80

70

UL-listed

n nom = 1450 min-1


ISO 9906 Annex A

90
60
80
50

70
60

40
50
30

40
30
0

500

P2
[kW]
200

1000

1500

200

2000
400

2500

3000

600

3500

4000

800

4500
1000

280

[m/h]

/475
/466
/457
/448
/437

160
200

80

[US GPM]

1200 Q

P2
[hp]
240

120

5000 Q

160
120
80

40

40
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000 Q

[US GPM]

Eta
[%]
90
80
70

/475
/437
/448 /457 /466

60

40
30
0

70

500

1000

1500

2000

2500

3000

3500

4000

4500

5000 Q

[US GPM]

TM03 8246 0907

50

Performance curves, HSF

HSF 8-20G
2500 gpm, 118-141 psi

2500 gpm, 118-141 psi


FM-approved
Pressure range
[psi]

H
[m]
110

118-141

90

124-138

Rated power

Pressure range
[psi]

Engine type

118-130

JW6H-UF58

224

300

135-141

JW6H-UF60

268

360

p
[psi]

[kW]

[hp]

HSF 8-20G

160

n nom = 1750 min-1

/456
/450
/441
/434

150
100

UL-listed

140

ISO 9906 Annex A

130
120

80

70

110
100
90

60
80
50

40

70
60
50

30

40
0

500

P2
[kW]

1000

1500

200

2000
400

2500

3000

600

3500

4000

800

4500
1000

P2
[hp]

Q [m/h]
/456

320
200

Q [US GPM]

/450

280

/441
/434

240
160
200

80

160
120
80
0

500

1000

1500

2000

2500

3000

3500

4000

4500

Q [US GPM]

Eta
[%]
90
80
70
60
50

/456
/434
/441 /450

40
30
0

500

1000

1500

2000

2500

3000

3500

4000

4500

Q [US GPM]

TM03 8256 0907

120

71

Performance curves, HSF

HSF 10-16
3000 gpm, 46-79 psi

3000 gpm, 46-79 psi


FM-approved
Pressure range
[psi]

H
[m]

46-79

UL-listed
63-79

Pressure range
[psi]

Engine type

46-50

Rated power
[kW]

[hp]

JU6H-UF58

103

138

55-63

JU6H-UF68

131

176

65-75

JW6H-UF30

164

220

79

JW6H-UF48

179

240

p
[psi]

HSF 10-16

90

/406
/397

80

/385

60

n nom = 1450 min-1


ISO 9906 Annex A

/373
50

70

/360
/347

60

/330

40
50
30

20

40

30

20
10
10
0

P2
[kW]

P2
[hp]

500

1000
200

1500

2000

400

2500

3000

600

3500

4000

800

4500

5000

1000

240

1400

Q [m/h]

/406
/397
/385
/373
/360
/347
/330

200

80

Q [US GPM]

1200

160

120

5500

160
120
80

40
40
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Q [US GPM]

Eta
[%]
90
/330

80

/406
/397
/385

/347
/360

70

/373

60

40
30
0

72

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Q [US GPM]

TM03 8247 0907

50

Performance curves, HSF

HSF 10-16
3500 gpm, 59-76 psi

3500 gpm, 59-76 psi


FM-approved
Pressure range
[psi]

H
[m]

UL-listed

59-76

59-76

Pressure range
[psi]

Engine type

59-60

[hp]

JU6H-UF68

131

176

65-75

JW6H-UF30

164

220

76

JW6H-UF48

179

240

p
[psi]

HSF 10-16

90
60
80
50

Rated power
[kW]

/404

n nom = 1450 min-1

/393

ISO 9906 Annex A

/381
/370

70

60
40
50
30

20

40

30

20
10
10
0

P2
[kW]

P2
[hp]

500

1000
200

1500

2000

400

2500

3000

600

3500

4000

800

4500
1000

5000

5500

1200

Q [US GPM]
1400

Q [m/h]

240
160

/404
/393
/381
/370

200
120

80

160
120
80

40
40
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Q [US GPM]

Eta
[%]
90
80

/370

/404
/381 /393

70
60

40
30
0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

Q [US GPM]

TM03 8248 0907

50

73

Technical data

Fire DNF
JU4H-UFxx

Installation dimensions
JU4H-UFxx
CM
LTM

AM1

CB

AM2

BA

AC

AM

DNd

DNs

30

40

50

20

60

10

70
0

80

CH27

BB
300

CC2

CC1

50

TM03 4611 1507

AB

90

LEC
LTB

300

CTB

Assembly dimensions
[mm]

Engine type

DNs
[mm]

DNd
[mm]

CB

BA

AC

CM

LTM

AB

AM

AM1

AM2

BB

Fire DNF 65-20

JU4H-UF14

100

65

100

500

348

1171

740

590

1029

791

173

80

Fire DNF 65-25

JU4H-UF14

100

65

125

500

373

1171

740

590

1029

791

173

90

Fire DNF 80-20

JU4H-UF14

125

80

125

500

373

1171

740

590

1029

791

173

80

125

80

125

500

403

1171

740

590

1029

791

173

90

Fire DNF 80-25

Pump type

JU4H-UF14
JU4H-UF24

Engine type

DNs
[mm]

DNd
[mm]

Base frame dimensions


[mm]
CTB

CC1

CC2

LEC

LTB

CH
Number
of holes

Weight
[kg]

Fire DNF 65-20

JU4H-UF14

100

65

1900

650

650

760

800

20

6"

880

Fire DNF 65-25

JU4H-UF14

100

65

1900

650

650

760

800

20

6"

875

Fire DNF 80-20

JU4H-UF14

125

80

1900

650

650

760

800

20

6"

880

125

80

1900

650

650

760

800

20

6"

Fire DNF 80-25

74

Pump dimensions
[mm]

Pump type

JU4H-UF14
JU4H-UF24

890
890

Technical data

Fire HSF
JU4H-UFxx

Installation dimensions
JU4H-UFxx
CM

LTM

BS

BR

CB

AM

BA

30

40

50

20

60

10

70
0

80

CH27
BB
300

CC1

50

CC2

LEC
LTB

DNs

300

TM03 4615 1507

AB

90

DNd

CTB

Pump type

Engine type

DNs
[in]

DNd
[in]

Pump dimensions
[mm]

Assembly dimensions
[mm]

CB

BA

BS

BR

736

406

330

305

171

171

JU4H-UF14
Fire HSF 5-11

JU4H-UF24
JU4H-UF34

JU4H-UF20
JU4H-UF54

1171

LTM

AB

740

604

1184

JU4H-UF10
Fire HSF 6-12

CM

858

483

419

305

194

210

170

1029
740

604

1184

JU4H-UF58

1029

BB

1143

1171
8

AM

240
1143

Fire HSF 6-16

JU4H-UF58

857

476

406

457

232

273

1184

740

604

1143

230

Fire HSF 6-18

JU4H-UF58

883

502

406

432

229

267

1184

740

604

1143

220

Pump type

Engine type

DNs
[in]

DNd
[in]

Base frame dimensions


[mm]
CTB

CC1

CC2

LEC

LTB

CH
Number
of holes

1750

575

575

760

800

20

6"

JU4H-UF14
Fire HSF 5-11

Fire HSF 6-12

JU4H-UF24

Weight
[kg]

1035
1035

JU4H-UF34

1045

JU4H-UF10

1195

JU4H-UF20
JU4H-UF54

1750

575

575

760

800

20

6"

JU4H-UF58

1195
1205
1205

Fire HSF 6-16

JU4H-UF58

1750

575

575

760

800

20

6"

1220

Fire HSF 6-18

JU4H-UF58

1900

650

650

760

800

20

6"

1260

75

Technical data

Fire HSF
JU6H-UFxx

Installation dimensions
JU6H-UFxx
CM

LTM

BS

BR

CB

AM

BA

30

40

50

20

60

10

70
0

80

CH27
BB
300

CC1

50

CC2

DNs

300

LEC
LTB

DNd

CTB

Pump type

Engine type

DNs
[in]

DNd
[in]

Pump dimensions
[mm]

Assembly dimensions
[mm]

CB

BA

BS

BR

LTM

AB

AM

BB

858

483

419

305

194

210

759

604

1162

240

1561

759

604

1162

230

1561

759

604

1162

220

JU6H-UF68

1615

806

604

1162

220

JU6H-UF58

1561

759

1615

806

682

1162

260

1561

759

1615

806

626

1162

260

1561

759

1615

806

626

1162

260

1561

759

1615

806

793

1162

300

JU6H-UF34
Fire HSF 6-12

TM03 4615 1507

AB

90

JU6H-UF54
JU6H-UF84

CM
1561
1615

JU6H-UF30
Fire HSF 6-16

JU6H-UF58

857

476

406

457

232

273

883

502

406

432

229

267

JU6H-UFG8
JU6H-UF30
Fire HSF 6-18

Fire HSF 8-17

Fire HSF 8-20

Fire HSF 8-20G

Fire HSF 10-16

76

JU6H-UF58

JU6H-UF68
JU6H-UF58
JU6H-UF68
JU6H-UF58
JU6H-UF68
JU6H-UF58
JU6H-UF68

10

896

502

483

381

254

305

10

1086

610

508

533

274

330

10

1086

610

508

533

274

330

12

10

1086

610

533

419

274

305

Technical data

Fire HSF
JU6H-UFxx

Installation dimensions
JU6H-UFxx (continued)
CM

LTM

BS

BR

CB

AM

BA

30

40

50

20

60

10

70
0

80

CH27
BB
300

CC1

50

CC2

LEC
LTB

DNs

300

DNd

CTB

Pump type

Engine type

DNs
[in]

DNd
[in]

Base frame dimensions


[mm]
CTB

CC1

CC2

LEC

LTB

CH
Number
of holes

2100

750

750

760

800

20

6"

JU6H-UF34
Fire HSF 6-12

Fire HSF 6-16

Fire HSF 6-18

JU6H-UF54

Fire HSF 8-20

Fire HSF 8-20G

Fire HSF 10-16

Weight
[kg]

1480
1480

JU6H-UF84

1500

JU6H-UF30

1430

JU6H-UF58

2100

750

750

760

800

20

6"

1430

JU6H-UFG8

1430

JU6H-UF30

1370

JU6H-UF58

2100

750

750

760

800

20

6"

JU6H-UF68
Fire HSF 8-17

TM03 4615 1507

AB

90

JU6H-UF58
JU6H-UF68
JU6H-UF58
JU6H-UF68
JU6H-UF58
JU6H-UF68
JU6H-UF58
JU6H-UF68

1370
1390

10

2100

750

750

760

800

20

6"

10

2200

850

800

760

800

20

6"

10

2200

850

800

760

800

20

6"

12

10

2200

850

800

760

800

20

6"

1435
1455
1600
1620
1600
1620
1690
1710

77

Technical data

Fire HSF
JW6H-UFxx

Installation dimensions
JW6H-UFxx
LTM
140

CM
1191

BS

BR

AM

CB

BA

30

40

50

20

60

10

70
0

80

CH27
BB
300

Pump type

Engine type

CC1

CC2
CTB

DNs
[in]

DNd
[in]

50

LEC
LTB

DNs

300

Pump dimensions
[mm]

Assembly dimensions
[mm]

CB

BA

BS

BR

CM

883

502

406

432

229

267

1565

LTM

JW6H-UF30
Fire HSF 6-18

JW6H-UF38

749

JW6H-UF40
Fire HSF 8-20

JW6H-UF38
JW6H-UF60

Fire HSF 8-20G

JW6H-UF58

10

1086

610

508

533

274

330

749

1565

726

Fire HSF 10-20

Pump type

JW6H-UF30
JW6H-UF48
JW6H-UF30
JW6H-UF48

Engine type

AM

BB

631

1273

220

631

1273

260

631

1273

260

793

1273

300

793

1273

350

749
10

1086

610

508

533

274

330

726

1565

726

JW6H-UF60
Fire HSF 10-16

AB

726

JW6H-UF30
JW6H-UF48

DNd

12

10

1086

610

533

419

274

305

1565

12

10

1181

660

559

584

279

356

1565

DNs
[in]

DNd
[in]

749
726
749
726

Base frame dimensions


[mm]
CTB

CC1

CC2

LEC

LTB

CH
Number
of holes

2250

550

550

860

900

20

6"

JW6H-UF30
Fire HSF 6-18

JW6H-UF38

Fire HSF 8-20

JW6H-UF60

Fire HSF 8-20G

JW6H-UF58

10

2400

600

600

860

900

20

6"

Fire HSF 10-16

Fire HSF 10-20

78

JW6H-UF48
JW6H-UF30
JW6H-UF48

1895
1930
1910

10

2400

600

600

860

900

20

6"

JW6H-UF60
JW6H-UF30

1700
1695

JW6H-UF30
JW6H-UF48

Weight
[kg]

1700

JW6H-UF40
JW6H-UF38

TM03 4612 1507

AB

90

1905
1930
1930

12

10

2400

600

600

860

900

20

6"

12

10

2600

665

665

860

900

20

6"

2000
1995
2300
2295

Technical data

Fire HSF
JX6H-UF30

Installation dimensions
JX6H-UF30
LTM
140

CM
1191

BS

BR

AM

CB

BA

30

40

50

20

60

10

70
0

80

CH27
BB
300

CC1

CC2
CTB

Pump type

Engine type

DNs
[in]

DNd
[in]

Fire HSF 10-20

JX6H-UF30

12

10

Engine type

DNs
[in]

DNd
[in]

12

10

Pump type

Fire HSF 10-20

JX6H-UF30

50

DNs

300

Pump dimensions
[mm]

LEC
LTB

TM03 4612 1507

AB

90

DNd

Assembly dimensions
[mm]

CB

BA

BS

BR

CM

LTM

AB

AM

BB

1181

660

559

584

279

356

1904

991

750

1252

300

Base frame dimensions


[mm]
CTB

CC1

LEC

LTB

CH
Number
of holes

2700

700

860

900

20

8"

Weight
[kg]

2870

79

Further product
documentation

Fire DNF, Fire HSF

WebCAPS
WebCAPS is a Web-based Computer Aided Product
Selection program available on www.grundfos.com.
WebCAPS contains detailed information on more than
185,000 Grundfos products in more than 22 languages.
In WebCAPS, all information is divided into 6 sections:
Catalogue
Literature
Service
Sizing
Replacement
CAD drawings.

Catalogue
This section is based on fields of application and pump types, and
contains
technical data
curves (QH, Eta, P1, P2, etc) which can be adapted to the density and viscosity of the pumped liquid and show the number of
pumps in operation
product photos
dimensional drawings
wiring diagrams
quotation texts, etc.

Literature
In this section you can access all the latest documents of a given
pump, such as
data booklets
installation and operating instructions
service documentation, such as Service kit catalogue and
Service kit instructions
quick guides
product brochures, etc.

Service
This section contains an easy-to-use interactive service catalogue.
Here you can find and identify service parts of both existing and discontinued Grundfos pumps.
Furthermore, this section contains service videos showing you how
to replace service parts.

80

Further product
documentation

Fire DNF, Fire HSF

Sizing

This section is based on different fields of application and installation examples, and gives easy step-by-step instructions in how to
select the most suitable and efficient pump for your installation
carry out advanced calculations based on energy consumption,
payback periods, load profiles, life cycle costs, etc.
analyse your selected pump via the built-in life cycle cost tool
determine the flow velocity in wastewater applications, etc.

Replacement
In this section you find a guide to selecting and comparing replacement data of an installed pump in order to replace the pump with a
more efficient Grundfos pump.
The section contains replacement data of a wide range of pumps
produced by other manufacturers than Grundfos.
Based on an easy step-by-step guide, you can compare Grundfos
pumps with the one you have installed on your site. When you have
specified the installed pump, the guide will suggest a number of
Grundfos pumps which can improve both comfort and efficiency.

CAD drawings
In this section it is possible to download 2-dimensional (2D) and 3dimensional (3D) CAD drawings of most Grundfos pumps.
These formats are available in WebCAPS:
2-dimensional drawings:
.dxf, wireframe drawings
.dwg, wireframe drawings.
3-dimensional drawings:
.dwg, wireframe drawings (without surfaces)
.stp, solid drawings (with surfaces)
.eprt, E-drawings.

81

82

83

Being responsible is our foundation


Thinking ahead makes it possible
Innovation is the essence

96641118 0907
Repl. 96641118 1006

GB

GRUNDFOS A/S . DK-8850 Bjerringbro . Denmark


Telephone: +45 87 50 14 00
www.grundfos.com

Subject to alterations.