NEC Code 430.6(A) (Size of Cable for Group of Motors or Elect. Load).
Cables or Feeder which is supplying more than one motors other load(s), shall have an ampacity not less than 125 % of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all the other motors in the group, as determined by 430.6(A). For Calculating minimum Ampere Capacity of Main feeder and Cable is 125% of Highest Full Load Current + Sum of Full Load Current of remaining Motors. Example: what is the minimum rating in amperes for Cables supplying 1 No of 5 hp, 415-volt, 3-phase motor at 0.8 Power Factor , 1 No of 10 hp, 415-volt, 3-phase motor at 0.8 Power Factor, 1 No of 15 hp, 415-volt, 3-phase motor at 0.8 Power Factor and 1 No of 5hp, 230-volt, single-phase motor at 0.8 Power Factor? Full-load currents for 5 hp = 7Amp. Full-load currents for 10 hp = 13Amp. Full-load currents for 15 hp = 19Amp. Full-load currents for 10 hp (1 Ph) = 21Amp. Here Capacity wise Large Motor is 15 Hp but Highest Full Load current is 21Amp of 5hp Single Phase Motor so 125% of Highest Full Load current is 21X125%=26.25Amp Min Capacity of Cable= (26.25+7+13+19) =65.25 Amp.
NEC Code 430.24 (Size of Cable for Group of Motors or Electrical Load).
As specified in 430.24, conductors supplying two or more motors must have an ampacity not less than 125 % of the full-load current rating of the highest rated motor + the sum of the full-load current ratings of all the other motors in the group or on the same phase. It may not be necessary to include all the motors into the calculation. It is permissible to balance the motors as evenly as possible between phases before performing motor-load calculations. Example: what is the minimum rating in amperes for conductors supplying 1No of 10 hp, 415-volt, 3-phase motor at 0.8 P.F and 3 No of 3 hp, 230-volt, single-phase motors at 0.8 P.F. The full-load current for a 10 hp, 415-volt, 3-phase motor is 13 amperes. The Full-load current for single-phase 3 hp motors is 12 amperes. Here for Load Balancing one Single Phase Motor is connected on R Phase Second in B Phase and third is in Y Phase. Because the motors are balanced between phases, the full-load current on each phase is 25 amperes (13 + 12 = 25). Here multiply 13 amperes by 125 %=(13 125% = 16.25 Amp). Add to this value the full-load currents of the other motor on the same phase (16.25 + 12 = 28.25 Amp). The minimum rating in amperes for conductors supplying these motors is 28 amperes.
Maximum Overload Maximum overload = F.L.C. (full load current of a motor) X allowable % of the maximum setting of an overload, 130% for motors, found in NEC Article 430/34. Increase of 5% allowed if the marked temperature rise is not over 40 degrees or the marked service factor is not less than 1.15.
Minimum Overload Minimum Overload = F.L.C. (full load current of a motor) X allowable % of the minimum setting of an overload, 115% for motors found in NEC Article 430/32/B/1. Increase of 10% allowed to 125% if the marked temperature rise is not over 40 degrees or the marked service factor is not less than 1.15.