Vous êtes sur la page 1sur 14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH I.

SCOPE : This specification covers the electricity meter test bench . supply of semiautomatic

II. STANDARD OF MANUAFACTURE AND TEST : The equipment shall conform to the latest edition of the appropriate IEC standards and/or other international standards. III. DESCRIPTION : 1. Function of equipment : Semiautomatic test equipment for simultaneously testing of 10 three or single phases meter . Typical accuracy on the energy measurement of 0.05% within a continuous range. The equipment shall be designed for an easy testing of electricity meters. It consist of : Fictitious and variables shift power supply. Measuring devices of the different parameters considered. The measurement on each phase, of the voltage, the current and the power, by means of voltmeters, amperemeters, phasemeters and the reference standard meter. Regulation, control and protection elements. Calculation and data acquisition system. It permits individual or group calibration of the following electricity meters : - Single or multi-phase. - Any type of active or reactive energy. - Direct connection or to measurement energy. - Induction or electronic meters. 2. Technical specification of semi-automatic electricity meter test bench : The measuring equipment is formed of three main component : - Test bench : A metallic modular test bench or console, with the different measuring elements and manual controls assembled on it. Testing and control software. - Meter test rack. - Test console with built in PC. 2.1. Test bench :
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 1/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH Fictitious power supply of measuring circuits of the meters to be tested by means of : 2.1.1. Test Voltage circuit : Three test voltage ranges : Range Star Delta 1 45-80 V 80-138 V 2 80-160 V 138-277 V 3 160-290 V 277-502 V

Every range continuously adjustable in each phase, with coarse and fine regulators. Every range is automatically selected by software. - Rotator Switch for no load testing with 80 100 120% Un. - Voltage symmetrization system. - Inver sequence RST/SRT selector. - The voltage range and coupling ( delta or star ) are automatically selected by software as a function of the desired test. 2.1.2. Test Voltage circuit : Two current ranges : 10mA 2A, 2A 150A continuously adjustable in each phase, with coarse and fine regulators. - Illuminated push button to decide the testing current by a factor of 10. - Illuminated push button to decide the testing current by a factor of 100. - Three illuminated push button for the individually switching on and off the test current in each phase. - Current symmetrization system. 2.1.3. Phase Shift : Phase angle adjustment by AC motor. Phase shifter with continuous adjustment within 0 180( lagging and leading ) One quick selector illuminated push button for power factor cos = 1 to cos = 0.5 ( or Sin = 1 to Sin = 0.5 ). 2.1.4. Power output : Voltage power output 300VA per phase.
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 2/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH Current power output 1000VA per phase. 2.1.5. Reference standard meter : - Reference standard meter with a built in multimeter. - Built in solid state reference standard meter with a typical accuracy of 0.05% for active energy. - Testing of following meters : Star Wh : single phase and three phase four wire meters for active energy. Delta Wh : three phase three wire meters for active energy. Star Varh : three phase four wire for reactive energy of the cross connected variety ( class 90 ). Delta Varh : : three phase three wire meters for reactive energy of the cross connected variety ( class 90 , 60 or artificial neutral ). Star Varh : single phase and three phase four wire meters for reactive energy of the true varmetric variety (class 0 ). Delta Varh : three phase three wire meters for reactive energy of the true varmetric variety (class 0 ). 2.1.6. Error calculator : This component, programmable from PC, calculates the error of one meter by using the scanning head provided. 2.1.7. Built in PC : In charge of the control of the bench and the meter tests. All the measured parameters are shown on the VGA screen, allowing also an important reduction in space in the test laboratories. The PC built in the test bench. The console also includes a 80 column printer. 2.1.8. Safety devices : Fuses, differential breakdown and overload protection. 2.1.9. Test bench console : The testing unit is mounted in a welded steel rack with wheels. The front, rear and side panels are removable, the input and output connections and the grounding connector, are located and protected at the back side.
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 3/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH 2.2. Meter Test Rack : The meter test rack with capacity for 10 meters each. The test rack is equipped with the following items : A scanning head capable to detect the disk mark without remove the meter cover, or the led of a static meters ( for those static meters with a LED with the following characteristics : 20 milicandela, red spectrum, centered on 630 nanometers ). The scanning head is mounted in moving supporters, designed to facilitate its displacement along the rack to test any meter. Under request, are available scanning heads for infra-red emitters. Error calculators, for individual error display having several functions : - Error calculations. - Tolerance indication system, it display will blink in order to attract the operators attention when the error of the meters is out of the defined tolerance. - Individual reset push button. - Also used in the starting and creeping automatic test. - LED type error display each with sign and three digits with one decimal +/- 00.0 ( with the provided software, it is possible to have on the screen four digits, +/- 00.00 ). 2.3. Testing and control software : The testing procedure is controlled by an easy to manage menu driven software. The software controls practically all the task performed by the test bench. During the execution of attest, it is possible to visualize on the screen, all the measurements taken by the reference standard meter and the multimeter. There are two displays showing all the parameters measured by the standard, on the screen. Pressing a key will show the basic testing information or the general testing information. The most important functions performed by the software are : - Error calculation control ( capacity standard software up to 128 meters ). - Automatic verification of meter registers ( constant ). - Automatic verification of maximum load indicators ( electronics or mechanical ) - Calculation of average error and standard deviation.
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 4/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH - All the results are stored in a file compatible with DBASE III. - Plotting of the error meter curve on the screen and printer. - Capacity it test meters with different constant, at the same time. IV. REQUIREMENT OF TECHNICAL DOCUMENT SUBMITTED WITH THE QUOTATION : - Technical description, data sheet, catalogues and other material submitted with the quotation must enable the Purchaser to thoroughly evaluate the proposals as to its compliance with the inquiry specification. - Minimum requirements : + Detail summary of deviations to the inquiry specification. + Completed inquiry datasheet expressed at section V. + Catalogues containing outline dimension, technical data + List of main equipment and completed accessories which can perform all function described in section III have the following requirements : . Individual cost of main equipment and each accessory . Total cost of main equipment and completed accessory . Manufactures code of main equipment and each accessory + Connection diagram. + Certificate of quality management. V. REQUIREMENT OF DOCUMENT INCASE OF BID WINNING : 1. Documents required to be provide for commission : In order to ensure the quality of supplied goods, in case of bid winning, the Tenderer shall supply the following documents for the Purchaser : - Manufacturers Certificate of Quality. - Certificate of Origin issued by Chamber of Commerce of the manufacturing country. - Certificate of calibration of equipment approved by an independent lawful organization. 2. Documents required to be provide in accompany with supplied products :
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 5/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH The Supplier shall enclose the following documents for supplied products : - 01 catalog - 01 instruction manual of installation, operation and maintenance. VI. REQUIREMENT OF INSTALLATION AND INSTRUCTION FOR USE : The Supplier shall ensure to supply the following service : - Installation the equipment completely. - Instruction to Purchasers staff how to use this equipment on site. - Trial run this equipment. VII. DATA SHEET : N 1. 2. 3. 4. 5. 6. 7. DESCRIPTION Manufacturer Country of origin Manufacturers code Standards of manufacture and test Standards of quality management Organization which approved certificate of quality management In case of bid winning, the Tenderer shall supply the following documents for the Purchaser : - Manufacturers Certificate of Quality. - Certificate of Origin issued by Chamber of Commerce of the manufacturing country. - Certificate of calibration of equipment approved by an independent lawful organization. REQUIREMENT QUOTED

Yes Yes Yes

/var/www/apps/conversion/tmp/scratch_5/139052675.doc

6/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH List of main equipment and completed accessories met all requirements of section IV is supplied in tender proposal. 9. Quoted main equipment and completed accessories described in above list can perform all function described in section III without addition of other necessary materials. 10. The Supplier shall ensure to supply the following service : - Installation the equipment completely. - Instruction to Purchasers staff how to use this equipment on site. - Trial run this equipment. 11. Function of equipment : * Semiautomatic test equipment for simultaneously testing of 10 three or single phases meter. * Typical accuracy on the energy measurement of 0.05% within a continuous range. * The equipment shall be designed for an easy testing of electricity meters. It consist of : Fictitious and variables shift power supply. Measuring devices of the different parameters considered. The measurement on each
/var/www/apps/conversion/tmp/scratch_5/139052675.doc

8.

Yes

Yes

Yes Yes Yes

Yes Yes

Yes Yes

Yes
7/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH phase, of the voltage, the current and the power, by Yes means of voltmeters, amperemeters, phasemeters and the reference standard meter. Yes Regulation, control and Yes protection elements. Calculation and data Yes acquisition system. It permits individual or Yes group calibration of the following electricity meters : - Single or multi-phase. - Any type of active or reactive energy. - Direct connection or to measurement energy. - Induction or electronic meters. 12. The measuring equipment is formed of three main component : - A metallic modular - Test bench : test bench or console, with the different measuring elements and manual controls assembled on it. - Testing and - Meter test rack. control software is suppiled. - Test console with built in Yes PC. Yes 13. Test bench Fictitious power supply of measuring circuits of the meters 14. Test Voltage circuit :
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 8/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH + Three test voltage ranges - Star + Three test voltage ranges Delta + Every range is automatically selected by software. + Every range continuously adjustable in each phase, with coarse and fine regulators : . Rotator Switch for no load testing with 80 100 120% Un. . Voltage symmetrization system. . Inver sequence RST/SRT selector. . The voltage range and coupling (delta or star) are automatically selected by software as a function of the desired test. 15. Test current circuit : + Two current ranges : 45-80V 80-160V 160-190V 80-138V 138-277V 277-502V Yes

Yes Yes Yes Yes

10mA 2A, 2A 150A continuously adjustable in each phase, with coarse and fine regulators. + Illuminated push button Yes to decide the testing current by a factor of 10 + Illuminated push button Yes to decide the testing current by a factor of 100 + Three illuminated push Yes button for the individually switching on and off the test
9/14

/var/www/apps/conversion/tmp/scratch_5/139052675.doc

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH current in each phase. + Current symmetrization system. 16. Phase Shift : + Phase angle adjustment by AC motor. + Phase shifter with continuous adjustment within 0 180( lagging and leading ) + One quick selector illuminated push button for power factor cos = 1 to cos = 0.5 (or Sin = 1 to Sin = 0.5). 17. Power output : + Voltage power output 300VA per phase. + Current power output 1000VA per phase. 18. Reference standard meter : Reference standard meter with a built in multimeter. - Built in solid state reference standard meter with a typical accuracy of 0.05% for active energy. - Testing of following meters : + Star Wh : single phase and three phase four wire meters for active energy. + Delta Wh : three phase three wire meters for active energy. + Star Varh : three phase four wire for reactive energy of the cross connected variety ( class 90 ).
/var/www/apps/conversion/tmp/scratch_5/139052675.doc

Yes Yes Yes Yes

Yes Yes

Yes Yes

Yes Yes Yes Yes

10/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH + Delta Varh : : three phase Yes three wire meters for reactive energy of the cross connected variety ( class Yes 90, 60 or artificial neutral ). + Star Varh : single phase and three phase four wire meters for reactive energy of the true varmetric variety (class 0 ). + Delta Varh : three phase three wire meters for reactive energy of the true varmetric variety (class 0). 19. Error calculator This component, programmable from PC, calculates the error of one meter by using the scanning head provided. 20. Built in PC : Yes - In charge of the control of the bench and the meter Yes tests. - All the measured parameters are shown on the VGA screen, allowing also an important Yes reduction in space in the test laboratories. - The PC built in the test bench. The console also includes a 80 column printer. 21. Safety devices Fuses, differential breakdown and overload protection 22. Test bench console : Yes - The testing unit is
/var/www/apps/conversion/tmp/scratch_5/139052675.doc 11/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH mounted in a welded steel rack with wheels. - The front, rear and side panels are removable. - The input and output connections and the grounding connector, are located and protected at the back side 23. Meter Test Rack : The meter test rack with capacity for 10 meters each. The test rack is equipped with the following items: - A scanning head capable to detect the disk mark without remove the meter cover, or the led of a static meters (for those static meters with a LED with the following characteristics: 20 milicandela, red spectrum, centered on 630 nanometers). - The scanning head is mounted in moving supporters, designed to facilitate its displacement along the rack to test any meter. Under request, are available scanning heads for infra-red emitters. - Error calculators, for individual error display having several functions : + Error calculations. + Tolerance indication system, it display will blink in order to attract the operators attention when
/var/www/apps/conversion/tmp/scratch_5/139052675.doc

Yes Yes

Yes

Yes

Yes Yes

Yes Yes Yes


12/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH the error of the meters is out of the defined tolerance. + Individual reset push button. + Also used in the starting and creeping automatic test. + LED type error display each with sign and three digits with one decimal +/00.0 ( with the provided software, it is possible to have on the screen four digits, +/- 00.00 ). 24. Testing and control software : - The testing procedure is controlled by an easy to manage menu driven software. The software controls practically all the task performed by the test bench. - During the execution of attest, it is possible to visualize on the screen, all the measurements taken by the reference standard meter and the multimeter. - There are two displays showing all the parameters measured by the standard, on the screen. Pressing a key will show the basic testing information or the general testing information. - The most important functions performed by the software are : + Error calculation control
/var/www/apps/conversion/tmp/scratch_5/139052675.doc

Yes Yes Yes

Yes

Yes Yes Yes

13/14

HCMC PC SPECIFICATION SEMI-AUTOMATIC ELECTRICITY METER TEST BENCH (capacity standard software up to 128 meters). Automatic verification of meter registers (constant ). + Automatic verification of maximum load indicators (electronics or mechanical) + Calculation of average error and standard deviation. + All the results are stored in a file compatible with DBASE III. + Plotting of the error meter curve on the screen and printer. + Capacity it test meters with different constant, at the same time. 25. - Dimensions : + Width + Height + Depth - Weight Yes Yes Yes Yes

The tendered has to quote the dimensions and weight of Semiautomatic electricity meter test bench, Meter test rack.

/var/www/apps/conversion/tmp/scratch_5/139052675.doc

14/14