Académique Documents
Professionnel Documents
Culture Documents
14
14.1
14.2
SELV and PELV tests Site applied insulation Electrical separation tests Non-conducting locations tests
14.3
Test between the ELV live conductors and any other live conductors in the same containment at 500 V
And additionally for SELV Test for insulation at 250 V between live parts and primary Earth (connected to the PE conductor)
14
32
Appendices
It is best if the voltage and procedure for test is replicated from an appropriate British standard. Failing this tests should be carried out as follows (between live parts and live parts and equipment earth not connected to the system earthing):
14.4
test with installation 500 V insulation tester and if greater than 2 M test at 1000 ac 50 Hz, increasing to test at 1500 V ac 50 Hz for 1 minute
No ashovers or breakdowns shall occur during this period. A earth leakage will be present depending upon the size and nature of the components. Generally this should be in the order of a few milliamps.
14.5
Test at 500 V between live parts of the separated circuit and earth connected to the system PE conductor if available and, Test at 500 V between live parts of the separated circuit and supply live conductors and, Test at 500 V between live parts of the separated circuit and live conductors of other circuits in a common enclosure.
In all cases, the insulation resistance for nominal voltage to earth circuits of 230 volts, shall not be less than 1 M.
test with installation 500 V insulation tester and if greater than 1 M, test at 1000 V ac 50 Hz, increasing to test at 2000 V ac 50 Hz for 1 minute.
33
14