Académique Documents
Professionnel Documents
Culture Documents
Industrial Pharmacy/2013
Parts of an HVAC system include the heating or air conditioning unit, the ductwork, and vents, both intake and outflow. The intake vents return air to the heating and cooling units through the ducts. The outflow vents distribute heated or cooled air throughout the building. A thermostat barometer and hygrometer are also considered parts of this system. Besides these meters, in order to maintain the particulate quality and microbiology of air certain types of filters are also used which are generally termed as pocket filters. A pocket filter is an air filter with pockets that is used with heating, ventilation and air conditioning (HVAC) filter appliances. It is used for reducing dust in the air. A pocket filter also can take in many other particle types. There are two types of material used for pocket filters: glass fiber and synthetic fibers and HEPA filters. Heating Central heating often used in cold climates to heat private houses and public buildings. Heating systems usually comprise of a boiler, furnace, heat pump or district hot water to heat water, steam or air. Piping distributes heated fluid and radiators transfer this heat to air and structures, e.g. floor heating system Ventilation It is the process of changing or replacing air in any space to control temperature or remove moisture, smoke, carbon dioxide, etc. Ventilation includes both the exchange of air to the outside as well as circulation of air within the building. It is one of the most
Industrial Pharmacy/2013
1. Fiberglass filter: This throwaway air filter is the most common type. Layered fiberglass fibers are laid over each other to form the filter media and typically are reinforced with a metal grating that supports the fiberglass to prevent failure and collapse. 2. Polyester and pleated filters: These filters are similar to fiberglass filters but typically have a higher resistance to airflow and a superior duststopping ability. 3. High efficiency particulate arrestance (HEPA) filters: These units filter the air passing through them at a very fine scale. HEPA filters have the capability to filter 99.97 percent of all particles 0.3 microns or larger.
Composition of HVAC system A standard HVAC system consists of following parts: Starter panels Most motors (fans, pumps) are controlled through starter panels. Starter panels
usually include Run status indication Trip alarm indication (and reset)
Industrial Pharmacy/2013
Duct System It is the piping all over the organization which delivers the outcome of the HVAC system, Duct system should be carefully designed and special attention should be given to the air and heat leakage, the outer covering must be of good heat insulating material in order to minimize vapor condensation Air Handling Units (AHU) Air handling units are used for circulating air inside a building or a part of a building. AHU consists of two fans (exhaust and supply), filters, a heat recovery unit, and one or more coils for heating/cooling. To improve air quality circulating air is mixed with fresh air from fresh air handling units (FAHU).Usually equipped with a heat recovery unit for energy saving purposes. Supply air temperature kept constant so that temperature can be adjusted locally with thermostats. A standard air handling unit further divided into: Fresh air handling units (FAHU) Exhaust fans Supply fans Fan coil units (FCU) Variable air volume (VAV) systems
Besides these basic parts of air supply system, air handling units also equipped with some sensors too which include: Variable frequency drives
Industrial Pharmacy/2013
Industrial Pharmacy/2013
Airflow diagram
1. External fresh air inlet. 2. Heat Exchange Unit. Exhaust air to be released in the atmosphere is used to normalize the temperature of the incoming fresh air. 3. Fresh air intake conduit. Supplies fresh air to the distributor. 4. Distributor. Electronically controlled, it manages the air flowing into the cooling and heating units and the ratio of fresh to recycled air. 5. Air supply ducts. Supply air to the heating and cooling units. 6. Filters. Remove the smallest particles of dust, smoke, pollens and other contaminants. 7. Cooling (A/C) Unit. Electronically controlled, cools down the intake air to a temperature as a function of demand and other environment variables. 8. Cold air fan. Variable speed turbine type fan that maintains certain (positive) pressure in the cold air column. 9. Cold air column. Delivers cold air throughout the building. 10. Heating (Furnace) Unit. Electronically controlled, heats up the intake air to a temperature as a function of demand and other environment variables. 11. Warm air fan. Variable speed turbine type fan that maintains certain (positive) pressure in the warm air column.
Industrial Pharmacy/2013
Some suggested readings EU Guidelines to Good Manufacturing Practice, Medicinal Products for Human and Veterinary Use. HVAC: heating, ventilating, and air conditioning. Homewood, Illinois: American Technical Publishers. Swenson, S. Don (1995) Encyclopedic. Britannica Online. 2009. Indoor Air Quality and HVAC Systems. New York: Lewis Publishers. Bearg, David W. (1993). Ventilation and Infiltration chapter, Fundamentals volume of the ASHRAE Handbook, ASHRAE, Inc., Atlanta, Georgia, 2005 Air Change Rates for typical Rooms and Buildings. The Engineering ToolBox Room Air Change Rate. A Design Guide for Energy-Efficient Research Laboratories. Bell, Geoffrey. Geothermal HVAC: Heating and Cooling. United States of America: McGraw-Hill Companies. Egg, J (2011). Guidance for Filtration and Air-Cleaning Systems to Protect Building Environments. Howard, J (2003). Building environment standards. www.iso.org.
Industrial Pharmacy/2013
Relative Humidity N. A NMT 45 % NMT 45 % NMT 45 % N.A NMT 45 % NMT 45 % NMT 45 % 45 5 % 45 5 % 45 5 % 45 5 % 45 5 % 45 5 % 45 5 % N.A N.A N.A
NMT= Not More Than N.A= Not Applicable There must be a pressure difference of at least 5mmHg between corridor and section/room (Delta pressure), particularly negative pressure in corridor so that the contaminated air from the corridor may not enter into production area. As per WHO guidelines for cGMP recommends the clarity of air of production area should be 99.97%.