Fire Alarm Cable Conversion Guide

Honeywell Cabling & Custom Electronics Honeywell 7701 95th Street L/FIREALMB/D Pleasant Praine, WI 53158-0060 August 2008 www.honeywell.com 2008 Honeywell International Inc.

NEC Article 760 The scope of this article covers:


Installation of wiring and equipment of fire alarm systems including all circuits controlled and powered by the fire alarm system including fire detection and alarm notification, guard's tour, sprinkler waterflow and sprinkler supervisory systems. Circuits controlled and powered by the fire alarm system include circuits for the control of building systems safety functions, elevator capture, elevator shutdown, door release, smoke doors and damper control, fire doors and damper control and fan shutdown, but only where these circuits are powered by and controlled by the fire alarm system.

Honeywell Cable Part Number


All of Honeywells cables have an eight digit part number. The first four digits are the catalog number, the fifth and sixth digits are the put-up code and the seventh and eighth digits are the jacket color code. Part number 41065504 would be a catalog number 4106 in a 500 box with a red jacket (see charts below).

4106

55

04

XXXX
Catalog Part Number

XX
Put-up Code

XX
Jacket Color Code

Code
FPL...For general use in buildings FPLR...For use within buildings in vertical shafts FPLP...For use in ducts, plenums or other environmental spaces Direct Burial....For use outdoor or underground, sunlight resistant

Put-up
500' Box 1,000' Box 500' Reel

Code
55 11 50 10 61 21 Red

Jacket Color
White Blue Black Red with Black Stripe Red with Yellow Stripe Red with Blue Stripe Red with Green Stripe

Code
04 01 06 08 4K 4Y 4B 4G 4

Article 760 Cable Substitution


Cable Type
FPLP FPLR FPL 3

1,000' Reel 500' Reel in Box

Cable Substitutions
MPP, CMP, CL3P MPP, CMP, CL3P, MPR, CMR, CL3R MPP, CMP, CL3P, MPR, CMR, CL3R, MP, CM, CL3 1,000' Reel in Box

www.honeywellcable.com

MS-9200UDLS

Wire Requirements
Twisted-pair Shielded Twisted-pair Shielded Twisted-pair Shielded Twisted-pair Shielded Untwisted, Unshielded Cable, in or out of conduit

Distance in Feet (m)


10,000 (3,048) 8,000 (2,438) 4,875 (1486) 3,225 (983) 3,000 (914)

Wire Size
12 AWG 14 AWG 16 AWG 18 AWG 12-18 AWG

1Cable #
4410 Non-Plenum 4610 Plenum 4408 Non-Plenum 4608 Plenum 4406 Non-Plenum 4606 Plenum 4402 Non-Plenum 4602 Plenum 4315, 4313, 4311, 4306 Non-Plenum 4515, 4513, 4511, 4506 Plenum

CLIP

MS-9200UDLS SLC Protocol

Wire Requirements
Twisted-pair Unshielded Twisted-pair Unshielded Twisted-pair Unshielded Twisted-pair Unshielded

Distance in Feet (m)


10,000 (3,048) 8,000 (2,438) 4,875 (1486) 3,225 (983)

Wire Size
12 AWG 14 AWG 16 AWG 18 AWG 4315 Non-Plenum 4313 Non-Plenum 4311 Non-Plenum 4306 Non-Plenum

Cable #
4515 Plenum 4513 Plenum 4511 Plenum 4506 Plenum

Light Speed

Firelite

MS-9050UD

Wire Requirements
Twisted-pair Unshielded Twisted-pair Unshielded Twisted-pair Unshielded Twisted-pair Unshielded

Distance in Feet (m)


10,000 (3,048) 8,000 (2,438) 4,875 (1486) 3,225 (983)

Wire Size
12 AWG 14 AWG 16 AWG 18 AWG 4315 Non-Plenum 4313 Non-Plenum 4311 Non-Plenum 4306 Non-Plenum

Cable #
4515 Plenum 4513 Plenum 4511 Plenum 4506 Plenum

MS-9600

Wire Requirements
Twisted-pair Shielded Twisted-pair Shielded Twisted-pair Shielded Twisted-pair Shielded Untwisted, Unshielded Cable, in or out of conduit

Distance in Feet (m)


10,000 (3,048) 8,000 (2,438) 4,875 (1486) 3,225 (983) 3,000 (914)

Wire Size
12 AWG 14 AWG 16 AWG 18 AWG 12 -18 AWG

Cable #
4315 Non-Plenum 4515 Plenum 4313 Non-Plenum 4513 Plenum 4311 Non-Plenum 4511 Plenum 4306 Non-Plenum 4506 Plenum 4513, 4315, 4313, 4311, 4306 Non-Plenum 4515,4513, 4511, 4506 Plenum 6

www.honeywellcable.com

Control/Circuit Use
VISTA 32FB/128FB/128FBP/250FBP Transformer-Primary Power NAC (Notification Circuit) Polling Loop Protective Loops ECP Bus (Keypad and Device Bus) DACT (Telephone Connection)

Size/#Con

Distance Max

Type

Cable Listing

18/2 AWG Min. Voltage drop must not exceed 15%, Calc. longer runs 18/2 AWG Min. Voltage drop must not exceed 15%, Calc. longer runs 18/2 AWG Min. 22/2 AWG Min. Varies based upon number of devices, current draw, wire size, SEE Chart on Web 22 AWG min, increase size as needed to reduce resistance on circuit

Twisted, Stranded, or Solid Twisted, Stranded, or Solid

FPL/FPLR/FPLR FPL/FPLR/FPLR

Twisted, Stranded, or Solid* FPL/FPLR/FPLR Twisted, Stranded or Solid FPL/FPLR/FPLR FPL/FPLR/FPLR FPL/FPLR/FPLR

Honeywell

22/4 AWG Min. >450 use 18 AWG, 2000 ft. max. w/16awg. See Chart I&I Twisted, Stranded or Solid* 24/4 AWG Min. Cat 5 or 5e, or 22-4 station wire acceptable Solid

Use of Shielded Wire reduces the effective operation of data circuits on Vista controls. Max distance is reduced by 50%. See I&I for further information Once any fire detection initiating devices are connected to the system All Keypad, NAC, Primary power, DACT, and shared power circuits must use FPL/R/P cable or equiv. as dictated by the environment

Note: Use of Shielded Wire Note: Wiring for FASS

www.honeywellcable.com

5700, 5808, 5820XL IFP-50, IFP-100, IFP-1000

Cable Requirements 4 Conductor 14 AWG Unshielded 4 Conductor 16 AWG Unshielded 4 Conductor 18 AWG Unshielded

Cable # 4314 Non-Plenum 4514 Plenum 4312 Non-Plenum 4512 Plenum 4307 Non-Plenum 4507 Plenum

FCI602, FCI7100 & FCI E3 Series Speaker/Firefighter phone

Cable Requirements

Cable #

2 Conductor 16 AWG Shielded

4206 General Purpose 4406 Riser 4606 Plenum 4202 General Purpose 4402 Riser 4602 Plenum

2 Conductor 18 AWG Shielded

Silent Knight

Models SK-2, SK-4, 5104B & SK5208 Use wire gauge to keep the maximum loop resistance at 50 ohms for the 2 conductor zone runs and the 4 conductor SBUS runs. Notification Appliance Circuit (NAC) 2 Conductor 12 AWG Shielded 2 Conductor, 12 AWG Unshielded 2 Conductor 14 AWG Shielded 2 Conductor 14 AWG Unshielded 2225 Non-Plenum, 3225 Plenum 2125 Non-Plenum, 3125 Plenum 2223 Non-Plenum, 3223 Plenum 2123 Non-Plenum, 3123 Plenum

Signal Loop Circuit (SLC) 2 Conductor 16 AWG Unshielded 4111 General Purpose 4311 Riser 4511 Plenum 4106 General Purpose 4306 Riser 4506 Plenum

Gamewell

2 Conductor 18 AWG Unshielded

Notification Appliance Circuit (NAC) 2 Conductor 14 AWG Unshielded 4113 General Purpose 4313 Riser 4513 Plenum 4111 General Purpose 4311 Riser 4511 Plenum 10

2 Conductor 16 AWG Shielded 2 Conductor 16 AWG Unshielded 2 Conductor 18 AWG Shielded 2 Conductor 18 AWG Unshielded 9 www.honeywellcable.com

2221 Non-Plenum, 3221 Plenum 2121 Non-plenum, 3121 Plenum 2214 Non-Plenum, 3214 Plenum 2114 Non-plenum, 3114 Plenum 2 Conductor 16 AWG Unshielded

Network Requirements
Part number, Number of Conductors and Gauges Manufacturers Specifications

Permissible Single Twisted Pair Range Data: Threshold: (in feet) For Each Cable Segment All Nodes and/or Repeaters on Bus a Cable Segment Point-to-Point Configuration 2 Node/Repeaters 1-400 400-800 1-41-500 500-1,000 1-500 500-1,000 1-600 600-1,200 1-600 600-1,200 1-1,200 1,000-2,800 1-500 500-1,000 1-1,400 1,200-2,000 1-1,400 1,200-2,000 1-1,400 1,200-2000 1-1,400 1,200-2,000 1-800 800-1,400 3 to 7 Nodes Repeaters 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 1-100 N/A 12

4608 4606 4602 4641

Shielded Shielded Shielded Shielded Shielded Unshielded Unshielded Unshielded Unshielded Unshielded Unshielded Unshielded

14 AWG 16 AWG 18 AWG 18 AWG 18 AWG 18 AWG 18 AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG

1 Pair 1 Pair 1 Pair 1 Pair 1 Pair 1 Pair 1 Pair 3 Pair 4 Pair 6 Pair 4 Pair 4 Pair

FPLP, NEC 760 FPLP, NEC 760 FPLP, NEC 760 Mid-Cap., FPLP, NEC 760 Mid-Cap., FPLP, NEC 760 FPLP, NEC 760 Mid-Cap FPL, NEC 760 Mid-Cap CMR CMR CMR CMR CMP

High: Low: High: Low: High: Low: High: Low: High: Low: High: Low: High: Low: High: Low: High: Low: High: Low: High: Low: High: Low:

Notifier

Notifier

4070 4631 4050 5032 5033 5034 5078 5088

11

www.honeywellcable.com

Notifier Number NFW-100-2 CLIP

Wire Requirements

Wire Size

Part Number FPL FPLR FPLP 4210 4208 4206 4202 4115 4113 4111 4106 4410 4408 4406 4402 4315 4313 4311 4306 4610 4608 4606 4602 4515 4513 4511 4506

Notifier Number Fire Warden CLIP

Wire Requirements

Wire Size

Part Number FPL FPLR FPLP 4210 4208 4206 4202 4115 4113 4111 4106 4410 4408 4406 4402 4315 4313 4311 4306 4610 4608 4606 4602 4515 4513 4511 4506

Twisted Shielded

LiteSpeed

Twisted Unshielded

12 AWG 14 AWG 16 AWG 18 AWG 12 AWG 14 AWG 16 AWG 18 AWG

Twisted Shielded

LiteSpeed

Twisted Unshielded

12 AWG 14 AWG 16 AWG 18 AWG 12 AWG 14 AWG 16 AWG 18 AWG

NFW-50

NFS2-3030 Twisted Unshielded or Twisted Shielded 12 AWG 14 AWG 16 AWG 18 AWG CLIP Twisted Unshielded 12 AWG 14 AWG 16 AWG 18 AWG 4115 4113 4111 4106 4315 4313 4311 4306 4515 4513 4511 4506

Notifier

Notifier

CLIP

NFS2-640, LEM-320 on NFS2-640, NFS-320, LCM-320/LEM-320 on NFS-3030/NFS2-3030 SLC Twisted Unshielded 12 AWG 14 AWG 16 AWG 18 AWG 4115 4113 4111 4106 4315 4313 4311 4306 4515 4513 4511 4506

AFP-100, AFP-200, AFP-300/AFP-400, LIB-200 ON AM2020/AFP1010, System 5000 with AIM 200 SLC Twisted Shielded 12 AWG 14 AWG 16 AWG 18 AWG 4210 4208 4206 4202 4410 4408 4406 4402 4610 4608 4606 4602

13

www.honeywellcable.com

14

Part Number, Number of Conductors and Gauges

Recommended Distances

Notes

The following fire-rated cables have been tested and approved by Notifier for use with the DVC System as digital audio loop segments.

4050

18 AWG

Twisted Pair

Unshielded

FPL

1,000 ft. (305.8 m)

4431

18 AWG

Twisted Pair

Unshielded

FPLR 1,000 ft. (305.5 m)

Notifier

4433

14 AWG

Twisted Pair

Unshielded

FPLR 1,000 ft. (305.8 m)

4631

18 AWG

Twisted Pair

Unshielded

FPLP 1,000 ft. (305.8)

4633

14 AWG

Twisted Pair

Unshielded

FPLP 1,000 ft. (305.8 m)

4307

18 AWG

4 Conductor

Unshielded

FPLP 750 ft. (228.6) FPLP, 450 ft. (137.1) LL5 FPLP, 400 ft. (121.9) LL5

5500

18 Awg

Twisted Pair

Unshielded

5502

16 AWG

Twisted Pair

Unshielded

15

www.honeywellcable.com

16

Fire Alarm Jacketed Unshielded


Our Fire Alarm Cables are manufactured in a wide variety of gage sizes, shielding configurations and jacketing materials including plenum, riser and general purpose. Genesis also manufactures fire alarm cables that meet the requirements of New York City Local Law 5 and New York State Toxicity requirements. Features: Countdown New Labeling System on box Color Coded Boxes Zone and Room Markings Article 760 The scope of this article covers the installation of wiring and equipment of fire alarm systems. These include all circuits controlled and powered by the fire alarm system including fire detection and alarm notification, guards tour, sprinkler waterflow and sprinkler supervisory systems. Circuits controlled and powered by the fire alarm system include circuits for the control of building systems safety functions, elevator capture, elevator shutdown, door release, smoke doors and damper control, fire doors and damper control and fan shutdown. Applicable only where these circuits are powered by and controlled by the fire alarm system. Fire Power Limited Cable: Type FPL, FPLR, FPLP Applications: Code Restrictions: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Risers and Plenums. Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. Sequential Footage Markings. Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red or White. Conductor Color Code Chart 4.

Features:

Construction:
Article 760

FIRE ALARM JACKETED UNSHIELDED 75 C


AWG#/COND. SOL NOM. O.D. NOM. CAP. PF/FT LISTINGS AVG. WT. PER MFT PART#

22 22 22 22 22 18 18 18 18 18 16 16 14 14 12

4 6 8 10 12 2 4 6 8 10 2 4 2 4 2

SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL.

.122 .144 .156 .182 .188 .134 .170 .192 .208 .244 .154 .180 .182 .214 .214

15 15 15 15 15 20 20 20 20 20 20 20 22 22 22

FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL

15 19 24 31 37 17 29 41 52 68 24 43 35 64 52

(LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.)

4101* 4102 4103 4104 4105 4106 4107* 4108+ 4109+ 4110+ 4111 4112+ 4113+ 4114+ 4115+ 18

*Not Twisted +Spools Only

17

www.honeywellcable.com

Fire Alarm Jacketed Unshielded, Direct Burial


Applications: Code Restrictions: Wiring for Outdoor or Underground. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Risers and Plenums, but intended for Outdoor or Underground Use. Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Stranded Copper Conductors, PVC Insulation, High Molecular Weight PVC Jacket Color: Black. Conductor Color Code Chart 4.

Fire Alarm Jacketed Shielded (Overall Shield)


Applications: Code Restrictions: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Risers and Plenums. Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Twisted Copper Conductors, Polypropylene Insulation, Aluminum/Mylar Shield with Drain Wire applied overall the assembled conductors. Flexible Polyvinyl-Chloride Jacket. Standard Jacket Color: Red or White, Conductor Color Code Chart 4.

Features:

Features: Construction:

Construction:

Article 760

FIRE ALARM JACKETED UNSHIELDED, DIRECT BURIAL 75 C


AWG#/COND. STR NOM. O.D. NOM. CAP. PF/FT LISTINGS AVG. WT. PER MFT PART#

FIRE ALARM JACKETED SHIELDED (OVERALL SHIELD) 75 C


AWG #/COND. SOL NOM. O.D. NOM. CAP. PF/FT LISTINGS AVG. WT. PER MFT PART#

18 18 18 16 14 14

2 4 6 2 2 4

STR. STR. STR. STR. STR. STR.

.260 .295 .345 .282 .310 .355

19 19 19 21 23 23

FPL, FPL, FPL, FPL, FPL, FPL,

CL2 CL2 CL2 CL2 CL2 CL2

19 15 24 31 37 17

(LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.)

4156 4157* 4158 4151 4153 4154

*Not Twisted

22 18 18 18 18 16 16 14 14 12

4 2 4 6 8 2 4 2 4 2

SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL.

.124 .138 .160 .196 .212 .158 .186 .186 .218 .218

31 42 42 42 42 46 46 52 52 56

FPL FPL FPL FPL FPL FPL FPL FPL FPL FPL

17 20 31 50 57 29 49 40 67 59

(LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.)

4201 4202 4203 4204 4205+ 4206 4207+ 4208+ 4209+ 4210+

+Spools Only

19

www.honeywellcable.com

20

Fire Alarm Zipcord


Applications: Code Restrictions: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Risers and Plenums. Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. One Conductor Ribbed for Polarity. Sequential Footage Markings. Copper Conductors Laid Parallel in a Zipcord Style. Integral Polyvinyl-Chloride Insulation. Standard Colors: Red, White.

Fire Alarm Mid Cap Unshielded


Applications: Wiring of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Risers and Plenums. Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. Sequential Footage Markings. Twisted Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Code Restrictions:

Features:

Features:

Construction:

Construction:

Article 760

FIRE ALARM ZIPCORD 75 C


AWG #/COND. SOL NOM. NOM. CAP. O.D. PF/FT LISTINGS AVG. WT. PER MFT PART#

FIRE ALARM MID CAP UNSHIELDED 75 C


AWG #/COND. SOL NOM. O.D. NOM. CAP. PF/FT LISTINGS AVG. WT. PER MFT PART#

18 16 14 12

2 2 2 2

SOL. .105 x .217 17 SOL. .116 x .247 17 SOL. .129 x .273 17 SOL. .146 x .307 17

FPL, C(UL) CMG 18 (LBS.) FPL, C(UL) CMG 39 (LBS.) FPL, C(UL) CMG 39 (LBS.) FPL, C(UL) CMG 55 (LBS.)

4002 4003 4004 4005

18 16 14
+Spools Only

2 2 2

SOL. .150 SOL. .170 SOL. .208

15 17 19

FPL FPL FPL

17 (LBS.) 25 (LBS.) 36 (LBS.)

4050 4051+ 4052+

Consult factory for availability.

21

www.honeywellcable.com

22

Fire Alarm Mid Cap Shielded (Overall Shield)


Applications: Wiring of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Risers and Plenums. Available in 500 Ft. or 1000 Ft. Spools or Reel-in-the-Box. Sequential Footage Markings. Twisted Copper Conductors, Polypropylene Insulation, Aluminum /Mylar Shield with Drain Wire, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Fire Alarm Jacketed Unshielded, Riser Rated


Applications: Code Restrictions: Features: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Plenums. Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red or White, Conductor Color Code Chart 4.

Code Restrictions:

Features:

Construction:

Construction:

Article 760

FIRE ALARM JACKETED UNSHIELDED, RISER RATED 75C NOM. NOM. CAP. AWG #/COND. SOL O.D. PF/FT LISTINGS 22 22 22 22 22 18 18 18 18 18 16 16 14 14 12 4 6 8 10 12 2 4 6 8 10 2 4 2 4 2 SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. .122 .144 .156 .182 .188 .138 .174 .187 .208 .244 .160 .184 .184 .214 .214 15 15 15 15 15 19 19 19 19 19 20 20 22 22 22 AVG. WT. PER MFT PART# 4301 4302 4303 4304 4305 4306 4307 4308+ 4309+ 4310+ 4311 4312+ 4313+ 4314+ 4315+ 24

FIRE ALARM MID CAP SHIELDED (OVERALL SHIELD) 75 C


AWG #/COND. STR NOM. O.D. NOM. CAP. PF/FT LISTINGS AVG. WT. PER MFT PART#

18 16 14
+Spools Only

2 2 2

SOL. .150 SOL. .170 SOL. .210

32 36 37

FPL FPL FPL

20 (LBS.) 28 (LBS.) 42 (LBS.)

4070 4071+ 4072+

FPLR/CL2R, C(UL), FT4 15 (LBS.) FPLR/CL2R, C(UL), FT4 19 (LBS.) FPLR/CL2R, C(UL), FT4 25 (LBS.) FPLR/CL2R, C(UL), FT4 30 (LBS.) FPLR/CL2R, C(UL), FT4 36 (LBS.) FPLR/CL2R, C(UL), FT4 17 (LBS.) FPLR/CL2R, C(UL), FT4 34 (LBS.) FPLR/CL2R, C(UL), FT4 44 (LBS.) FPLR/CL2R, C(UL), FT4 54 (LBS.) FPLR/CL2R, C(UL), FT4 67 (LBS.) FPLR/CL2R, C(UL), FT4 24 (LBS.) FPLR/CL2R, C(UL), FT4 43 (LBS.) FPLR/CL2R, C(UL), FT4 37 (LBS.) FPLR/CL2R, C(UL), FT4 65 (LBS.) FPLR/CL2R, C(UL), FT4 55 (LBS.)

23

www.honeywellcable.com

+Spools Only Consult factory for availability.

Fire Alarm Jacketed (Overall Shield), Riser Rated


Applications:
Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. Circuits except those in Plenums.

Fire Alarm Zipcord, Riser Rated


Applications:
Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. Circuits except those in Plenums.

Code Restrictions: OK for use with all Power-Limited Features:


Available In 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. Sequential Footage Markings. Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red or White, Conductor Color Code Chart 4.

Code Restrictions: OK for use with all Power-Limited Features:


Available in 500 Ft. or 1000 Ft. TangleFree Boxes or Spools. One Conductor Ribbed for Polarity. Sequential Footage Markings. Copper Conductors, Polyvinyl-Chloride Insulation. Standard Colors: White, Blue, Red.

Construction: Article 760

Construction:

FIRE ALARM JACKETED (OVERALL SHIELD), RISER RATED 75 C NOM. NOM. CAP. AWG #/COND. SOL O.D. PF/FT 22 18 18 18 18 16 16 14 14 12 25 4 2 4 6 8 2 4 2 4 2 SOL. .126 SOL. .138 SOL. .163 SOL. .196 SOL. .212 SOL. .158 SOL. .190 SOL. .192 SOL. .218 SOL. .218 31 42 42 42 42 46 46 52 52 56 LISTINGS AVG. WT. PER MFT PART#

FIRE ALARM ZIPCORD, RISER RATED 75 C AWG #/COND. SOL 18 16 14 12 2 2 2 2 NOM. NOM. CAP. O.D. PF/FT LISTINGS AVG. WT. PER MFT PART#

FPLR/CL2R, C(UL), FT416 (LBS.) 4401 FPLR/CL2R, C(UL), FT421 (LBS.) 4402 FPLR/CL2R, C(UL), FT432 (LBS.) 4403 FPLR/CL2R, C(UL), FT446 (LBS.) 4404 FPLR/CL2R, C(UL), FT456 (LBS.) 4405+ FPLR/CL2R, C(UL), FT431 (LBS.) 4406 FPLR/CL2R, C(UL), FT449 (LBS.) 4407+ FPLR/CL2R, C(UL), FT442 (LBS.) 4408+ FPLR/CL2R, C(UL), FT472 (LBS.) 4409+ FPLR/CL2R, C(UL), FT460 (LBS.) 4410+

SOL. .088 x .196 17 SOL. .094 x .200 17 SOL. .107 x .220 17 SOL. .124 x .250 17

FPLR/CL2R, C(UL), FT4 18 (LBS.) 4422 FPLR/CL2R, C(UL), FT4 26 (LBS.) 4423 FPLR/CL2R, C(UL), FT4 37 (LBS.) 4424+ FPLR/CL2R, C(UL), FT4 52 (LBS.) 4425+

+Spools Only

+Spools Only

www.honeywellcable.com

26

Fire Alarm Mid Cap (Overall Shield), Riser Rated


Applications:
Wiring of Mid-Capacitance FireProtective Signaling Circuits. Sunlight Resistant. Circuits except those in Plenums.

Fire Alarm Mid Cap Unshielded, Riser Rated


Applications:
Wiring of Mid-Capacitance Fire-Protective Signaling Circuits. Sunlight Resistant. Circuits except those in Plenums.

Code Restrictions: OK for use with all Power-Limited Features: Construction:


Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Twisted Copper Conductors, Polypropylene Insulation, Aluminum/Mylar Shield with Drain Wire, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Code Restrictions: OK for use with all Power-Limited Features: Construction:


Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Twisted Copper Conductors, Polypropylene Insulation, Aluminum/Mylar Shield with Drain Wire, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4.

FIRE ALARM MID CAP SHIELDED (OVERALL SHIELD) RISER RATED 75 C

FIRE ALARM MID CAP UNSHIELDED, RISER RATED 75 C AWG #/COND. SOL 18 16 14 12 2 2 2 2 NOM. NOM. CAP. O.D. PF/FT LISTINGS 15 17 19 22 AVG. WT. PER MFT PART#

NOM. NOM. CAP. AWG #/COND. SOL O.D. PF/FT 18 16 14 12 2 2 2 2 SOL. .148 SOL. .187 SOL. .212 SOL. .260 34 38 41 48

LISTINGS

AVG. WT. PER MFT

PART#

FPLR/CL2R, C(UL), FT4 21 (LBS.) 4441 FPLR/CL2R, C(UL), FT4 32 (LBS.) 4442 FPLR/CL2R, C(UL), FT4 43 (LBS.) 4443 FPLR/CL2R, C(UL), FT4 48 (LBS.) 4444

SOL. .144 SOL. .170 SOL. .208 SOL. .256

FPLR/CL2R, C(UL), FT4 19 (LBS.) 4431 FPLR/CL2R, C(UL), FT4 26 (LBS.) 4432+ FPLR/CL2R, C(UL), FT4 38 (LBS.) 4433+ FPLR/CL2R, C(UL), FT4 60 (LBS.) 4434+

Consult factory for availability.

+Spools Only

Consult factory for availability.

27

www.honeywellcable.com

28

Fire Alarm Mid Cap Unshielded, Riser Rated


Applications: Wiring of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Sunlight Resistant. OK for use with all Power-Limited Circuits except those in Plenums. Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. Sequential Footage Markings. Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Fire Alarm Jacketed Unshielded, Plenum Rated


Applications:
Wiring of Fire-Protective Signaling Circuits. Circuits.

Code Restrictions: OK for use with all Power-Limited Features:


Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. Sequential Footage Markings. Copper Conductors, Low Smoke PVC Insulation, Low Smoke PVC Jacket And Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Code Restrictions: Features:

Construction:

Construction:

FIRE ALARM JACKETED UNSHIELDED, PLENUM RATED 75 C NOM. NOM. CAP. AVG. WT. AWG #/COND. SOL O.D. PF/FT LISTINGS PER MFT
22 22 22 22 22 18 18 18 18 18 16 16 14 14 12 4 6 8 10 12 2 4 6 8 10 2 4 2 4 2 SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. SOL. .122 .144 .156 .182 .188 .134 .156 .192 .208 .244 .154 .180 .182 .214 .214 22 22 22 22 22 24 24 24 24 24 27 27 27 27 30 FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P FPLP/CL2P C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), C(UL), FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 FT6 15 21 28 33 38 19 32 45 58 74 26 47 38 68 55

FIRE ALARM MID CAP UNSHIELDED, RISER RATED 75 C NOM. NOM. CAP. AWG #/COND. SOL O.D. PF/FT LISTINGS 18 16 14 12 2 2 2 2 SOL. .144 SOL. .170 SOL. .208 SOL. .256 AVG. WT. PER MFT PART#

PART#
(LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) (LBS.) 4501 4502 4503 4504 4505 4506 4507 4508+ 4509+ 4510+ 4511 4512+ 4513+ 4514+ 4515+

15 FPLR/CL2R, C(UL), FT4 19 (LBS.) 4431 17 FPLR/CL2R, C(UL), FT4 26 (LBS.) 4432+ 19 FPLR/CL2R, C(UL), FT4 38 (LBS.) 4433+ 22 FPLR/CL2R, C(UL), FT4 60 (LBS.) 4434+

+Spools Only

Consult factory for availability.

29

+Spools Only

Consult factory for availability.

30

Fire Alarm Jacketed (Overall Shield), Plenum Rated


Applications: Code Restrictions: Features: Wiring of Fire-Protective Signaling Circuits. OK for use with all Power-Limited Circuits. Available In 500 Ft. or 1000 Ft. Tangle-Free Boxes or Spools. Sequential Footage Markings. Twisted Copper Conductors, Low Smoke PVC Insulation, Aluminum /Mylar Shield With Drain Wire Low Smoke PVC Jacket and Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Fire Alarm Mid Cap Unshielded, Plenum Rated


Applications: Wiring of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. OK for use with all Power-Limited Circuits. Available In 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Copper Conductors, Fluoropolymer Insulation, Low Smoke PVC Jacket and Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Code Restrictions: Features:

Construction:

Construction:

FIRE ALARM JACKETED SHIELDED (OVERALL SHIELD) PLENUM RATED 750 C

FIRE ALARM MIDCAP UNSHIELDED, PLENUM RATED 75 C AWG #/COND. SOL 18 16 14 2 2 2 NOM. NOM. CAP. O.D. PF/FT LISTINGS AVG. WT. PER MFT PART#

AWG #/COND. SOL 22 18 18 18 18 16 16 14 14 12 31 4 2 4 6 8 2 4 2 4 2

NOM. NOM. CAP. O.D. PF/FT LISTINGS 53 68 68 68 68 77 77 86 86 96

AVG. WT. PER MFT

PART#

SOL. .126 SOL. .140 SOL. .168 SOL. .196 SOL. .212 SOL. .158 SOL. .186 SOL. .186 SOL. .218 SOL. .218

FPLP/CL2P C(UL), FT6 18 (LBS.) 4601 FPLP/CL2P C(UL), FT6 22 (LBS.) 4602 FPLP/CL2P C(UL), FT6 35 (LBS.) 4603 FPLP/CL2P C(UL), FT6 50 (LBS.) 4604+ FPLP/CL2P C(UL), FT6 62 (LBS.) 4605+ FPLP/CL2P C(UL), FT6 35 (LBS.) 4606 FPLP/CL2P C(UL), FT6 52 (LBS.) 4607+ FPLP/CL2P C(UL), FT6 44 (LBS.) 4608+ FPLP/CL2P C(UL), FT6 75 (LBS.) 4609+ FPLP/CL2P C(UL), FT6 63 (LBS.) 4610+

SOL. .146 SOL. .182 SOL. .210

16 FPLP/CL2P C(UL), FT621 (LBS.) 4631 16 FPLP/CL2P C(UL), FT629 (LBS.) 4632 16 FPLP/CL2P C(UL), FT642 (LBS.) 4633

Consult factory for availability.

+Spools Only

www.honeywellcable.com

32

Fire Alarm Mid Cap (Overall Shield), Plenum Rated


Applications: Code Restrictions: Features: Construction: Wiring of Mid-Capacitance FireProtective Signaling Circuits. OK for use with all Power-Limited Circuits. Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Copper Conductors, Fluoropolymer Insulation, Aluminum/Mylar Shield with Drain Wire, Low Smoke PVC Jacket and Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4.

Jacketed Unshielded LL5


Applications: Code Restrictions: Fire Protective Signaling Circuits installed in the City of New York. Meets the requirements of New York City Local Law 5, and New York State Toxicity. Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Copper Conductors, Fluoropolymer Insulation and Jacket. Standard Jacket Color: Red. Color Code Chart 4.

Features: Construction:

FIRE ALARM MIDCAP SHIELDED (OVERALL SHIELD) PLENUM RATED 75

JACKETED UNSHIELDED LL5 150 C AWG #/COND. SOL 18 18 16 16 14 14 12 1 2 1 2 1 2 1 SOL. SOL. SOL. SOL. SOL. SOL. SOL. NOM. NOM. CAP. AVG. WT. O.D. PF/FT LISTINGS PER MFT .198 .312 .214 .345 .244 .374 .272 45 45 55 55 60 60 65 PART#

NOM. NOM. CAP. AWG #/COND. SOL O.D. PF/FT LISTINGS 18 16 14 2 2 2 SOL. .150 SOL. .187 SOL. .214

AVG. WT. PER MFT

PART#

32 FPLP/CL2P C(UL), FT625 (LBS.) 4641 32 FPLP/CL2P C(UL), FT639 (LBS.) 4642 32 FPLP/CL2P C(UL), FT652 (LBS.) 4643

FPLP, NYC LL526 (LBS.) 5500 FPLP, NYC LL547 (LBS.) 5501 FPLP, NYC LL536 (LBS.) 5502 FPLP, NYC LL562 (LBS.) 5503 FPLP, NYC LL547 (LBS.) 5504 FPLP, NYC LL587 (LBS.) 5506 FPLP, NYC LL567 (LBS.) 5505

Consult factory for availability.

33

www.honeywellcable.com

34

Jacketed Shielded LL5 (Overall Shield)


Applications: Code Restrictions: Fire Protective Signaling Circuits installed in the City of New York. Meets the requirements of New York City Local Law 5, and New York State Toxicity. Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Copper Conductors, Fluoropolymer Insulation, Aluminum/Mylar Shield and Fluoropolymer Jacket. Standard Jacket Color: Red. Color Code Chart 4.

Notes

Features: Construction:

JACKETED SHIELDED LL5 (OVERALL SHIELD) 150 C AWG #/COND. SOL 18 18 16 16 14 14 12 1 2 1 2 1 2 1 SOL. SOL. SOL. SOL. SOL. SOL. SOL. NOM. O.D. .202 .316 .215 .343 .243 .398 .276 NOM. CAP. PF/FT LISTINGS 80 80 100 100 110 110 130 AVG. WT. PER MFT PART# 5550 5551 5552 5553 5554 5555 5556

FPLP, NYC LL5 28 (LBS.) FPLP, NYC LL5 51 (LBS.) FPLP, NYC LL5 42 (LBS.) FPLP, NYC LL5 71 (LBS.) FPLP, NYC LL5 51 (LBS.) FPLP, NYC LL5 93 (LBS.) FPLP, NYC LL5 75 (LBS.)