SECTI ON 0 32 00 CONCRETE REINFORCEMENT

A. Scope of Work: This Section specifies reinforcing steel and welded wire mesh for castin-place or precast concrete structures. B. Related Work: 1. Section 03100 "Concrete Formwork" 2. Section 03300 "Cast-in-Place Concrete" 3. Section 03410 "Precast Concrete Structures"

111.2 QUALITY ASSURANCE 12 13 14 15 16 17 A. Standards: Unless otherwise indicated, all materials, workmanship, and practices shall meet all requirements of the current editions of the following standards: 1. Standard Building Code 2. ACI 318 Building Code Requirements for Reinforced Concrete 3. ACI 315 Details and Detailing of Concrete Reinforcement 4. CRSI Manual of Standard Practice, MSP-2

181.3 SHOP DRAWINGS AND SUBMITTALS 19 20 21 22 23 24 25 A. Submittals shall be submitted to the County/Professional for review and acceptance prior to construction in accordance with the General Conditions and specifications Section 01300 "Submittals." B. Complete shop drawings shall be submitted for comment, including bar lists and placing drawings. Drawings shall show the type, spacing, and location of metal bar supports, the grade of the reinforcing and the name of the manufacturer. The type of coupler splice devices shall be designated.

26PART 2 - PRODUCTS 272.1 GENERAL 28 29 A. All material supplied shall be one of the products specified in Appendix D "List of Approved Products" appended to these technical specifications.

1
2OCU Master CIP Technical Specifications

03200 - 1 of 4
rev: August, 2012

12.2 MATERIALS 2 3 4 5 6 7 8 9 A. Reinforcing Bars: ASTM A615, Grade 60, deformed billet steel bars of a USA manufacturer. B. Welded Wire Fabric: ASTM A185, galvanized. C. Metal Bar Supports: CRSI MSP-2, Chapter 3, Class 2, Type B, Stainless Steel Protected Bar Supports. D. Coupler Splice Devices: Cadweld tension couplers capable of developing the ultimate strength of the bar, as manufactured by Erico Products, Incorporated, Solon, Ohio, or equal where acceptable to the County.

102.3 FABRICATION 11 12 13 14 15 16 A. Fabrication shall meet all requirements of the specified standards. Unless otherwise indicated, the following shall apply: 1. Hooks shall be standard hooks. 2. Bottom bars shall extend a minimum of 6-inches into supporting members. 3. Minimum cover shall be measured to the outermost stirrup, tie or bar. 4. Splices are permitted only where indicated on the Drawings.

17PART 3 - EXECUTION 183.1 INSTALLATION 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 A. Supporting Reinforcing: Bar supports shall be provided as required by CRSI MSP-2 and AC1315. Top and bottom bars in slabs formed on earth shall be supported on precast concrete block supports except where such bars are properly supported from formwork. Precast concrete block supports are not required in slabs formed on tremie concrete but may be used at the Contractor's option. B. Placing Reinforcing: Placing of reinforcing steel and welded wire fabric shall conform to CRSI MSP-2, ACI 315, and the Drawings. Reinforcing shall be securely tied and supported to prevent displacement during concrete placement. C. Welded Wire Fabric: Splices in welded wire fabric shall be such that the overlap between outermost cross wires of each fabric sheet is not less than the spacing of the cross wires, plus 2-inches. Fabric shall not be extended through expansion joints or construction joints in slabs on grade except as otherwise indicated on the Drawings. D. Coupler Splice: Unless indicated on the Drawings or where conventional lap splices cannot be achieved, full positive tension connections shall be provided. Such devices shall be installed in accordance with the recommendations of the manufacturer.

1
2OCU Master CIP Technical Specifications

03200 - 2 of 4
rev: August, 2012

1 2 3 4 5 6

E. Dowels: Dowels shall be wired in position prior to placing concrete. F. Field Bending: Heat shall not be used to bend bars. Bars shall not be bent after being embedded in concrete. G. Welding: Welding of reinforcing will not be permitted. H. Place reinforcement a minimum of 2-inches clear of any metal pipe or fittings.

END OF SECTION

1
2OCU Master CIP Technical Specifications

03200 - 3 of 4
rev: August, 2012

THIS PAGE LEFT BLANK INTENTIONALLY

1
2OCU Master CIP Technical Specifications

03200 - 4 of 4
rev: August, 2012