Vous êtes sur la page 1sur 132

www.eaton.

com

EX

2200 RT 2U 2200 RT 3U 3000 RT 2U 3000 RT 3U 3000 RT 3U XL EXB RT 3U


Installation and User Manual Manuel dinstallation et dutilisation Manual de instalacin y de usuario Manual de instalao e do usurio

English Franais Espaol

Pulsar Series

Portuguese

www.eaton.com

EX

2200 RT 2U 2200 RT 3U 3000 RT 2U 3000 RT 3U 3000 RT 3U XL EXB RT 3U


Installation and User Manual

Pulsar Series

Copyright 2008 EATON All rights reserved.

For Technical Support, Customer Care Center, or Customer FAQ, please call us at (800) 356-5794, or visit our website: www.eaton.com

Contents

Introduction........................................................................................................................ 5 Important Safety Instructions............................................................................................. 6 Symbol Usage.................................................................................................................... 7

1. Presentation
1.1 Standard Positions. ............................................................................................................. 9 1.2 Rear Panels...................................................................................................................... 10 1.3 Control Panel ................................................................................................................... 10

2. Installation
2.1 Unpacking and Contents Check....................................................................................... 11 2.2 Installation in Tower Position .......................................................................................... 12 2.3 Installation in Rack Position. ............................................................................................. 12 2.4 Communication Ports....................................................................................................... 13 2.5 Connections with a FlexPDU (Power Distribution Unit) Module (optional)..................... 14 2.6 Connection with a HotSwap MBP Module (optional)...................................................... 14 2.7 UPS Connection Without a FlexPDU or HotSwap MBP Module..................................... 15

3. Operation
3.1 Start-Up and Normal Operation........................................................................................ 17 3.2 Operation on Battery Power. ............................................................................................ 18 3.3 Return of AC Power......................................................................................................... 18 3.4 UPS Shutdown................................................................................................................. 18 3.5 Using the UPS Remote Control Functions. ...................................................................... 19

4. Access to Maintenance and Personalization Data


4.1 4.2 4.3 4.4 Display Organization......................................................................................................... 21 Access to Measurements................................................................................................ 21 Personalization Using the Control Panel.......................................................................... 21 Personalization Using External Software. ......................................................................... 22

5. Maintenance
5.1 Troubleshooting................................................................................................................ 23 5.2 Battery Module Replacement.......................................................................................... 24 5.3 Maintenance on a UPS Equipped With the HotSwap MBP Module............................... 26

6. Appendices
6.1 Technical Specifications.................................................................................................. .27 6.2 Programming the Programmable Outlets........................................................................ 28 6.3 Glossary............................................................................................................................ 31

86-86710-00EN A02 - Page 3

86-86710-00EN A02 - Page 4

Introduction
Thank you for selecting an EATON product to protect your electrical equipment. The EX range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS (Uninterruptible Power Supply). Warning: This is a class A UPS product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take additional measures. If the device must be installed in overvoltage category III or IV environments, additional upstream overvoltage protection must be provided for. Before installing EX, please read the booklet on the required safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products and the options available for the EX range, we invite you to visit our web site at www.eaton.com or contact your EATON representative.

Environmental Protection
EATON has implemented an environmental-protection policy. Products are developed according to an eco-design approach.

Substances
This product does not contain CFCs, HCFCs or asbestos.

Packing
To improve waste treatment and facilitate recycling, separate the various packing components. w The cardboard we use comprises over 50% of recycled cardboard. w Sacks and bags are made of polyethylene. 01 w Packing materials are recyclable and bear the appropriate identification symbol.
PET

Material Polyethylene terephthalate High-density polyethylene Polyvinyl chloride Low-density polyethylene Polypropylene Polystyrene

Abbreviation PET HDPE PVC LDPE PP PS

Symbol number 01 02 03 04 05 06

01
PET

Follow all local regulations for the disposal of packing materials.

End of life
EATON will process products at the end of their service life in compliance with local regulations. EATON works with companies in charge of collecting and eliminating our products at the end of their service life.
w Product The product is made up of recyclable materials. Dismantling and destruction must take place in compliance with all local regulations concerning waste. At the end of its service life, the product must be transported to a processing centre for electrical and electronic waste. w Battery The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batteries. The battery may be removed to comply with regulations and in view of correct disposal. The Material Safety Data Sheets (MSDS) for the batteries are available on our web site*.

(*) For more information or to contact the Product Environmental manager, please visit our website: www.eaton.com/ pulsar.

86-86710-00EN A02 - Page 5

IMPORTANT SAFETY INSTRUCTIONS


SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. The EX models that are covered in this manual are intended for installation in an environment within 0 to 40C (32F to 104F), free of conductive contaminant. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Certification Standards
w w w w w w w w w w

IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability FCC rules and regulations of Part 15, Subpart J, Class A UL listed under 1778, Standards for Uninterruptible Power Supply Equipment IEC 61000-4-2 (ESD): level 4 IEC 61000-4-3 (Radiated field): level 3 IEC 61000-4-4 (EFT): level 4 IEC 61000-4-5 (Fast transients): level 4 IEEE-C6241 Category B (ring wave) IEC 61000-4-6 (electromagnetic field) IEC 61000-4-8 (conducted magnetic field)

Safety of Persons
w w w w


w w w w w w w w w w w

The system has its own power source (the battery). Consequently, the power outlets may be energized even if the systems is disconnected from the AC power source. Dangerous voltage levels are present within the system. It should be opened exclusively by qualified service personnel. The system must be properly grounded. The battery supplied with the system contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed: - Never burn the battery (risk of explosion). - Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin). - Comply with all applicable regulations for the disposal of the battery. - Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles. - Do not lay tools or metal parts on top of batteries. The UPS connection instructions and operation described in the manual must be followed in the indicated order. A protection circuit breaker must be installed upstream and be easily accessible. The system can be disconnected from the AC power source by opening this circuit breaker. Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the system. The socket-outlet shall be installed near the equipment and shall be easily accessible. Never install the system near liquids or in an excessively damp environment. Never let a foreign body penetrate inside the system. Never block the ventilation grates of the system. Never expose the system to direct sunlight or source of heat. If the system must be stored prior to installation, storage must be in a dry place. The admissible storage temperature range is -20C to +40C (-4F to 104F). The maximum operating temperature without power derating is 40C (104F).

Product Safety

Special Precautions
w w

All handling operations will require at least two people (unpacking, installation in rack system). Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature less than 25C (77F)). This charges the battery, thus avoiding possible irreversible damage. During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of doubt, dont hesitate to contact your EATON representative. This product has been designed to respect the environment: It does not contain any Chlorofluorocarbon (CFC) or Hydrochlorofluorocarbon (HCFC). UPS recycling at the end of service life: EATON undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your EATON branch office). Packing: UPS packing materials must be recycled in compliance with all applicable regulations. WARNING: This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled by specialized companies.

Environment
w

86-86710-00EN A02 - Page 6

Symbol Usage

Important instructions that must always be followed.

Information, advice, help.

Visual indication.

Action.

Audible signal.

LED off.

LED on.

LED flashing.

86-86710-00EN A02 - Page 7

86-86710-00EN A02 - Page 8

1. Presentation
1.1 Standard Positions
Tower Position

Dimensions (H x W x D) in inches EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 17.3 x 3.38 x 25.2 17.3 x 5.16 x 19.3 17.3 x 3.38 x 25.2 17.3 x 5.16 x 19.3 17.3 x 5.16 x 19.3 17.3 x 5.16 x 19.3


Rack Position

Weight in pounds EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U 70 68 72 70 41 93

EX 3000 RT 3U XL EX EXB RT 3U

Part Numbers EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 86722 86723 86732 86733 86735 68405

86-86710-00EN A02 - Page 9

1. Presentation
1.2 Rear Panels
EX 2200 / 3000 / 3000 XL
EX 2200 (1) USB communication port (2) RS232 communication port (3) Connector for automatic recognition of an additional battery module (4) Slot for optional communication card (5) Connector for remote ON/OFF and RPO (Remote Power Off) control (6) Connector for additional battery module (7) L5-20R (or L5-30R for EX 3000) receptacle for connection of equipment (8) 2 programmable outlets for connection of equipment (9) Groups of 4 outlets for connection of equipment (10) 10-foot input power cord w L5-30P for EX 3000 w 5-20P for EX 2200 (11) LED (SWF) indicating distribution system phase/neutral reversal (12) Connectors for battery modules (to the UPS or to the other battery modules) (13) Connectors for automatic recognition of battery modules

EX EXB (optional battery module)

12

12

13

1.3

Control Panel
(20) (21) (22) (23) (24) (25) (26) (27) Load protected LED Downgraded operation LED Load not protected LED LCD Escape (cancel) button Scroll button Enter (confirm) button ON/OFF button for UPS and outlets

86-86710-00EN A02 - Page 10

2. Installation
2.1 Unpacking and Contents Check

(30) (33) (34) (36) (37) EX 2200 or 3000 UPS RS232 communications cable USB communications cable Solution-Pac CD-ROM Documentations supplied depending on the UPS model (38) Mounting kit for 19-inch bays, except for RT 3U models (39) 2 supports for the upright position (2U version only) (40) FlexPDU module (optional) (42) NMC communication card (optional) (43) HotSwap MBP module (optional)

Packing materials must be disposed of in compliance with all local regulations concerning waste. Recycling symbols are printed on the packing materials to facilitate sorting.

86-86710-00EN A02 - Page 11

2. Installation
2.2 Installation in Tower Position

2.3

Installation in Rack Position


It is advised to first install the battery module, then the power module above.

Follow steps 1 to 4 for module mounting on the rails.

The rails and necessary hardware are supplied, except for 3U models, by EATON.

86-86710-00EN A02 - Page 12

2. Installation
2.4 Communication Ports
Connection of RS232 or USB communication port (optional)

The RS232 and USB communication ports cannot operate simultaneously. 1. Connect the RS232 (33) or USB (34) communication cable to the serial or USB port on the computer equipment. 2. Connect the other end of the communication cable (33) or (34) to the USB (1) or RS232 (2) communication port on the UPS. The UPS can now communicate with EATON power management software.


Installation of the communication cards (optional)
Communication card slot (restricted access)

It is not necessary to shutdown the UPS before installing a communications card. 1. Remove the UPS cover (4) secured by screws. 2. Insert the communications card in the slot. 3. Secure the card with screws.

86-86710-00EN A02 - Page 13

2. Installation
2.5 Connections with a FlexPDU (Power Distribution Unit) Module (optional)
EX 3000 1. Connect the UPS powercord (10) to the AC power source. 2. Connect the input cord of the FlexPDU module (48) to the UPS outlet (9). The cord and the outlet are marked in red. 3. Connect the equipment to the outlets (45), (46) on the FlexPDU module. These outlets differ, depending on the version of the FlexPDU module.

2.6

Connections with a HotSwap MBP Module (optional)


The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function). EX 3000 1. Connect the input cord (56) of the HotSwap MBP module to the AC power source. 2. Connect the UPS input cord (10) to the UPS Input (55) of the HotSwap MBP module. This cord and the receptacle are marked blue. 3. Connect the UPS outlet (7) to the UPS Output cord (54) of the HotSwap MBP module. This cord and the outlet are marked red. 4. Connect the equipment to the outlets (49) on the HotSwap MBP module.

Caution: Do not use UPS outlets (8)and (9) to supply equipment because use of switch (53) on the HotSwap MBP module would cut supply to the equipment. It is advised not to remove the protective film from outlets (8) and (9).

86-86710-00EN A02 - Page 14

2. Installation
HotSwap MBP module operation
The HotSwap MBP module has a rotary switch (53) with two positions: Normal the load is supplied by the UPS, LED (51) is ON. Bypass the load is supplied directly by the AC power source. LED (52) is ON.

UPS start-up with the HotSwap MBP module


2. Set switch (53) to the Normal position.

1. Check that the UPS is correctly connected to the HotSwap MBP module.

3. Start the UPS by pressing the ON/OFF button (27) on the UPS control panel. The load is supplied by the UPS. LED (51) UPS ON - OK to switch on the HotSwap MBP module goes ON.

HotSwap MBP module test


1. Set switch (53) to the Bypass position and check that the load is still supplied. 2. Set switch (53) back to the Normal position.

2.7

UPS Connection Without a FlexPDU or HotSwap MBP Module


Check that the indications on the name plate located on the back of the UPS correspond to the AC power source and the true electrical consumption of the total load. 1. Connect the input cord (31) (120V 30A / or 20A on EX 2200) to the AC power source. 2. Connect the loads to the UPS. It is preferable to connect the priority loads to the four outlets marked (9) and the non-priority loads to the two outlets marked (8) that can be programmed. Connect any high-power devices to the 20A (or 30A on EX 3000) outlet (7) as shown at left for EX 2200. To program shutdown of outlets (8) during operation on battery power and thus optimise the available backup time, the EATON communications software is required.

Note: The UPS charges the battery as soon as it is connected to the AC power source, even if button (27) is not pressed. Once the UPS is connected to the AC power source, eight hours of charging are required before the battery can supply the rated backup time
86-86710-00EN A02 - Page 15

(This page left blank intentionally)

86-86710-00EN A02 - Page 16

3. Operation
3.1 Start-Up and Normal Operation

For the initial start-up, AC power must be present to detect any wiring errors. After inital start-up, the UPS can start even if AC power is not present. Press button (27) for approximately 1 second. w The buzzer beeps once and all the LEDs go ON simultaneously. w The buzzer then beeps twice during the self-test, then button (27) remains ON, indicating power to the output receptacles.

The connected devices are protected by the UPS. w LED (20) is ON.

If LED (22) is ON, a fault has occurred (see the Troubleshooting section). w During normal operation, the scroll button (25) may be used to read UPS measurements (voltage on normal and bypass AC inputs, operating mode, battery capacity and UPS serial number).

UPS personalization

If UPS personalization is desired, it is advised to enter the personalization mode at this time. This mode may be entered using the buttons on the control panel or the Personal Solution-Pac Software (Windows) included on the Solution-Pac CD-ROM provided by EATON.

86-86710-00EN A02 - Page 17

3. Operation
3.2 Operation on Battery Power
Transfer to power battery power Transfer to battery

w The connected devices continue to be supplied by the UPS when AC power is no longer available. The necessary energy is provided by the battery. w LEDs (20) and (21) go ON. w The audio alarm beeps every ten seconds.

The connected devices are supplied by the battery. The display indicates the remaining backup time.

Low-battery warning Low on battery power


20

w LEDs (20) and (21) go ON. w The audio alarm beeps every three seconds.

The remaining battery power is low. Shut down all applications on the connected equipment because automatic UPS shutdown is imminent.

End of battery backup time

w w

All the LEDs go OFF. The audio alarms stop.

i
3.3

The UPS is completely shut down

Return of AC power
Following an outage, the UPS restarts automatically when AC power returns (unless the restart function was disabled via UPS personalization) and the load is again supplied.

3.4

UPS shutdown
Press button (27) for approximately 2 seconds. The devices connected to the UPS are no longer supplied.

86-86710-00EN A02 - Page 18

3. Operation
3.5 Using the UPS Remote Control Functions
EX has the choice of two remote control options. w w RPO: Remote Power Off allows a remote contact to be used to disconnect all the equipment connected to the UPS from the power supply. Restarting the UPS requires manual intervention. ROO: Remote ON/OFF allows remote action of button (27).

These functions are obtained by opening a contact connected between the appropriate pins of connector (5) on the rear panel of the UPS (see diagram below). EX 3000


Remote control connection and test
1. 2. Check the UPS is shut down and the electrical supply network disconnected. Remove connector (5) after unscrewing the screws.

3. Connect a normally closed volt-free contact (60 Vdc / 30 Vac max, 20 mA max, 0.75 mm2 cable cross section) between the two pins of connector (5), see diagram. Contact open: shut down of UPS Contact closed: start-up of UPS (UPS connected ROO to the network and network energized)

Note: local On/Off control via button (27) has priority over the remote control order. Contact open: shut down of UPS
RPO

To return to normal operation, deactivate the external remote shut down contact and restart the UPS using button (27).

4. Plug connector (5) into the back of the UPS. 5. Connect and restart the UPS according to the previously described procedures. 6. Activate the external remote shut down contact to test the function.

Warning: This connector must only be connected to SELV (Safety Extra Low Voltage) circuits.

86-86710-00EN A02 - Page 19

(This page left blank intentionally)

86-86710-00EN A02 - Page 20

4. Access to Maintenance and Personalization Data


4.1 Display Organization
Status and Alarms Status and Alarms

Measurements UPS input measurements UPS output measurements Battery measurements

Personalization Local personalization Output personalization On/Off personalization Battery personalization

4.2

Access to Measurements
Press the scroll button (25) to access any status conditions and alarms, then the measurements for voltage, current, frequency, power output and battery backup time.

4.3

Personalization using the control panel


w Press the Scroll button (25) several times until the personalization menu is reached. w Press the Enter button (26) to access the different possibilities. w Finally, confirm the selection by pressing the Enter button (26) again.

Function Language Audio alarm

Factory setting English Enabled

Other available settings French, Spanish, Portuguese Disabled

86-86710-00EN A02 - Page 21

4. Access to Maintenance and Personalization Data


Output Personalization
Function Output voltage
(1)

Factory Setting 120 Volts AC


(1)

Options 100/104/110/120/127 Volts AC Enabled


(2)

Comments

Frequency converter Output frequency

Disabled Automatic selection

The connected devices are never transferred to the bypass. User selectable only if the frequency-converter function is enabled.

(1)

50 or 60 Hz

Transfer to the bypass Bypass AC power must be Bypass AC power may be within tolances outside tolerances AC input (1)

Overload level

(1)

102%

50 / 70%

Alarm if threshold is overrun.

ON/OFF Personalization
Function Factory Setting Options Disabled Disabled The UPS restarts automatically when AC power returns. When function enabled, battery shuts down when power drops to <5%. When function enabled, the UPS remains OFF if the system detects phase/neutral inversion. Comments

Start on battery power Enabled Automatic restart Enabled

Energy savings Detection of phase/ neutral inversion (SWF)

Disabled Enabled

Enabled Disabled

Battery Personalization
Function Battery test Selection of the backup time Battery protection against excessive discharges Factory Setting Weekly test Options No test / daily test / monthly test UPS restarts automatically when Normal AC source is restored. When function disabled, EATON warranty no longer applies. Comments

Automatic detection of 0 to 200 Ah number of battery modules Enabled Disabled

4.4

Personalization Using External Software

w w w

Insert the Solution-Pac CD-ROM in the drive. On the first navigation screen, select Point to Point solution and follow the instructions on how to install the Personal Solution-Pac software. Then select Settings, Advanced settings and UPS settings.

Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility. (1). These Parameters may be modified only when the UPS is OFF. (2). Bypass is disabled when frequency converter is enabled.

86-86710-00EN A02 - Page 22

5. Maintenance
5.1 Troubleshooting
If LED (21) or (22) is ON, a fault or an alarm has occurred. Use the escape button (24) to stop the audio alarm.

Indication

Diagnostic

Correction w Check ACpower availability. w Check the UPS is correctly connected to the AC input power. Check polarity and grounding system.

The UPS does not start, the LCD The AC input power is not indicates: COLD START NOK connected or is connected to the CHECK AC WIRING UPS output. LED (22) is ON, the SWF LED Phase inversion on AC input (11) at the rear of the UPS is ON. power. The UPS does not start. The LCD indicates: SITE WIR. FAULT CHECK AC WIRING LED (22) is ON, the LCD indicates: NO BATTERY CHECK CONNECTION LED (22) is ON, the LCD indicates: BATTERY FAULT SERV REQUIRED LED (21) is ON, the LCD indicates: OVERLOAD ALARM REDUCE LOAD The battery is incorrectly connected. A fault is detected on the battery.

Check battery connections (see Section 5.2, Battery-module replacement). Replace the battery (see Section 5.2, Battery-module replacement). Call the after-sales support department. Reduce the load.

The load level exceeds the programmed overload level or UPS capacity.

LED (22) is ON, the LCD The UPS is overloaded. Devices indicates: LOAD UNPROTECTED connected to the UPS are fed OUTPUT OVERLOAD directly by the electrical network via the By-pass. LED (22) is ON, the LCD indicates: REDUCE LOAD RESTART UPS After repetitive overloads, the UPS is locked in the By-pass position. Devices connected to the UPS are fed directly by the electrical network. The UPS shut down automatically because of overload at the UPS output.

Check the power drawn by the connected devices and disconnect any non-priority devices. Check the power drawn by the connected devices and disconnect any non-priority devices. Shut down and restart the UPS to return to normal operation. Check the power drawn by the connected devices and disconnect any non-priority devices.

LED (22) is ON, the LCD indicates: OVERLOAD FAULT REDUCE LOAD LED (22) is ON, the LCD indicates: LOAD SHORT-CIRCU CHECK WIRING LED (22) is ON, the LCD indicates: INTERNAL FAULT SERV REQUIRED

The UPS shut down automatically Remove the load, and then restart the because of a short-circuit at the UPS. UPS output. A UPS internal fault has occurred. Call the after-sales support There are two possible situations: department. w the load is still supplied, but directly with AC power via the bypass, w the load is no longer supplied. Switching of the Remote Power Off (RPO) has led to the shut down of the UPS. Return the contact in the normal position, and press the ON/OFF button to restart.

10

11

The LCD indicates: REMOTE POWER OFF RPO

86-86710-00EN A02 - Page 23

5. Troubleshooting
Troubleshooting a UPS equipped with the HotSwap MBP module
Indication The load is no longer supplied when the rotary switch (53) on the HotSwap MBP module is set to the Bypass position.

Diagnostic

Correction

12

Check the wiring between the UPS w The protected devices are connected to the UPS output instead and the HotSwap MBP module (see of to the HotSwap MBP module. Section 2.6). w The AC power cord is connected to the UPS input instead of to the HotSwap MBP module. w The UPS is shut down. w The wiring between the UPS and the HotSwap MBP module is not correct. w The rotary switch (53) on the HotSwap MBP module is set to the Bypass position. w The wiring between the UPS and the HotSwap MBP module is not correct. w Start the UPS. w Check the wiring between the UPS and the HotSwap MBP module (see Section 2.6). w Set the rotary switch (53) on the HotSwap MBP module to the Normal position. w Check the wiring between the UPS and the HotSwap MBP module (see Section 2.6). w Ups is shutdown

13

The load is no longer supplied when the rotary switch (53) on the HotSwap MBP module is set to the Normal position. The load is no longer supplied if AC power fails.

14

If a fault leads to UPS shutdown, press the ON/OFF button (27) to clear the fault.

5.2

Battery Module Replacement


Safety recommendations
Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions. Risk of explosion if battery is replaced by an incorrect type. When replacing batteries, replace with the same type and number of batteries or battery packs. CAUTION: CAUTION: CAUTION: Do not dispose of batteries in a fire. The batteries may explode. Dispose of used batteries according to the instructions. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:

a. Remove watches, rings, or other metal objects. b. Use tools with insulated handles. c. Wear rubber gloves and boots. d. Do not lay tools or metal parts on top of batteries. e. Disconnect charging source prior to connecting or disconnecting battery terminals. f. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).

86-86710-00EN A02 - Page 24

5. Troubleshooting
Battery-module removal
A. Unscrew the left-hand side of the front panel (two screws), then remove the part.

B. Disconnect the battery block by separating the two connectors (never pull on the wires).

C. Unscrew the metal bracket and remove the part.

D. Pull out the battery pack.

Mounting the new battery module


Carry out the above instructions in reverse order. w To ensure safety and high performance, use only batteries supplied by EATON. w Take care to firmly press together the two parts of the connector during remounting.

86-86710-00EN A02 - Page 25

5. Troubleshooting
5.3 Maintenance on a UPS Equipped With the HotSwap MBP Module

The HotSwap MBP module makes possible to service or even replace the UPS without affecting the connected loads (HotSwap function). Maintenance: 1. Set switch (53) to the Bypass position. The red LED (52) on the HotSwap MBP module goes ON, indicating that the load is supplied directly with AC power. 2. Stop the UPS by pressing the ON/OFF button (27) on the UPS control panel. LED (51) UPS ON - OK to switch goes OFF, the UPS can now be disconnected and replaced. Return to normal operation: 1. Check that the UPS is correctly connected to the HotSwap MBP module. 2. Start the UPS by pressing the ON/OFF button (27) on the UPS control panel. LED (51) UPS ON - OK to switch on the HotSwap MBP module goes ON (otherwise, there is a connection error between the HotSwap MBP module and the UPS). 3. Set switch (53) to the Normal position. The red LED (52) on the HotSwap MBP module goes OFF.

86-86710-00EN A02 - Page 26

6. Appendices
6.1 Technical Specifications


EX 2200 Output power Electrical supply network w Rated input voltage w Input voltage range w Frequency w Power factor w Leakage current Load output w Voltage w Frequency w Harmonic distortion w Overload capacity w Current Battery Environment w Operating temperature range w Relative humidity w Storage temperature range w Altitude 2100 VA (1) / 1650 W EX 3000 3000 VA (2) / 2550 W (3) Single phase 120 V 55 / 72 / 100 to 142 V
(4)

EX 3000 XL 3000 VA (2) / 2150 W

EXB

(9)

50/60 Hz (autoselection) > 0.95 < 2 mA Single phase 120 V 3% (5) 50/60 Hz 0,5% (6) < 4% for linear load, < 6% for nonlinear load 102% continuous, 105% 20s, > 130% 1.5s 17.5 A
(7)

25 A 6 x 12V - 9 Ah, sealed lead acid, maintenance free

(8)

6 x 12V - 7 Ah, sealed lead acid, maintenance free

without internal battery

Two 6 x 12 V - 9 Ah strings, sealed lead acid, maintenance free

0C to 40C (32F to 104F ) 20% to 90% (without condensation) -20C to 40C (-4F to 104F) 1000 m < 47 dBA

w Noise level

(1) (2) (3) (4) (5) (6) (7) (8) (9)

Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the output power is 1890VA / 1890VA / 2100VA / 2100VA / 2100VA. Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the output power is 2500VA / 2500VA / 2500VA / 3000VA / 3000VA. Standard output power is 2550 W, 2400 W with an EXB module. Values for 33% / 66% / 100% of UPS output. Programmable: 100V / 104V / 110V / 120V / 127V using the UPS Config software. Frequency-converter mode is programmable using the UPS Config software. Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the maximum output current is 18.9A / 18.2A / 19.1A / 17.5A / 16.5A. Depending on the output voltage selected: 100V / 104V / 110V / 120V / 127V, the output current is 25A / 24A / 22.7A / 25A / 23.6A. EXB is in 3U model only. Standard UPScan be connected with up to 4 EXB.

86-86710-00EN A02 - Page 27

6. Appendices
6.2 Programming the Programmable Outlets
1. To open the Setting window, left-click on Start Menu / Programs / EATON / Personal Solution Pac / Settings, or right-click on the PSP power plug located in the SYS Tray. 2. Click on the + symbol next to UPS Settings to expand the UPS Settings section.

3. Click on Startup Timer and change the The group of outlets restarts after to 0 to have powershare outlet provide power at the same time the as main outlets.

86-86710-00EN A02 - Page 28

6. Appendices
4. Repeat step 3 for each programmable outlet. 5. After making the changes,s click on the Apply button. The section entitled Shutdown timer allows the user to define how long the powershare outlet should provide power after a power loss. To configure the powershare to power off at the same time as the main outlets: 6. Set the The group of outlet is powered OFF after to 65535.

86-86710-00EN A02 - Page 29

(This page left blank intentionally)

86-86710-00EN A02 - Page 30

6. Appendices
6.3 Glossary
Bypass line from the AC power source, controlled by the UPS, used to directly supply the load if an overload or a malfunction occurs on the UPS. Time during which the load can be supplied by the UPS operating on battery power. Internal UPS test to check battery status. Devices connected to the UPS output. Battery discharge beyond the permissible limit, resulting in irreversible damage to the battery. Module with UPS outlets for installation in a bay. There are different modules with different types of outlets. Operating mode used to convert the AC power frequency between the UPS input and output (50 Hz -> 60 Hz or 60 Hz -> 50 Hz). UPS manual-bypass module for maintenance. There are different modules with different types of outlets. This is a battery-voltage level indicating that battery power is low and that the user must take action in light of the imminent break in the supply of power to the load. Liquid Crystal Display. The AC power line supplying the UPS under normal conditions. Ratio of the power effectively drawn by the load to the maximum output of the UPS. It is possible to modify certain UPS parameters set in the factory. Certain UPS functions can also be modified by the Personal Solution-Pac software to better suit user needs. These outlets can be automatically shut down during operation on battery power (shutdown time delays can be programmed with the Personal Solution Pac software). The UPS has two sets of two programmable outlets. The devices connected to the UPS can be started even if AC power is not available. The UPS operates on battery power alone. Uninterruptible Power Supply. This function enables or disables initiation of UPS ON/OFF control sequences by computer pwower management software.

Bypass AC input
Backup time Battery test Equipments Excessive discharge FlexPDU Frequency converter HotSwap MBP Low-battery warning LCD Normal AC input Percent load Personalization Programmable Outlets Start on battery power UPS UPS ON/OFF Controlled by software

86-86710-00EN A02 - Page 31

Notes:

86-86710-00EN A02 - Page 32

www.eaton.com

EX

2200 RT 2U 2200 RT 3U 3000 RT 2U 3000 RT 3U 3000 RT 3U XL EXB RT 3U


Manuel dinstallation et dutilisation

Pulsar Series

Copyright 2008 EATON All rights reserved.

For Technical Support, Customer Care Center, or Customer FAQ, please call us at (800) 356-5794, or visit our website: www.eaton.com

86-86710-00FR A02 - Page 2

Table des matires

Introduction........................................................................................................................ 5 Consignes de scurit importantes .................................................................................. 6 Symboles utiliss. ............................................................................................................... 7

1. Prsentation
1.1 Positions standard.............................................................................................................. 9 1.2 Panneaux arrire. .............................................................................................................. 10 1.3 Panneau de commande .................................................................................................. 10

2. Installation
2.1 Dballage et vrification du contenu................................................................................ 11 2.2 Installation en position tour ............................................................................................. 12 2.3 Installation en position rack.............................................................................................. 12 2.4 Ports de communication.................................................................................................. 13 2.5 Connexions avec un module FlexPDU (unit de distribution dalimentation) (optionnel) ........................................................................................................................ 14 2.6 Connexions avec un module HotSwap MBP (optionnel)................................................. 14 2.7 Connexion onduleur sans module FlexPDU ou HotSwap MBP. ...................................... 15

3. Fonctionnement
3.1 Dmarrage et fonctionnement normal............................................................................. 17 3.2 Fonctionnement avec alimentation par pile..................................................................... 18 3.3 Retour de lalimentation c.a.. ............................................................................................ 18 3.4 Mise hors tension de londuleur. ...................................................................................... 18 3.5 Utilisation de la commande distance de londuleur. ...................................................... 19

4. Accs aux donnes de personnalisation et de maintenance


4.1 4.2 4.3 4.4 Structure daffichage........................................................................................................ 21 Accs aux mesures.......................................................................................................... 21 Personnalisation laide du panneau de configuration.................................................... 21 Personnalisation laide du logiciel externe. .................................................................... 22

5. Entretien
5.1 Dpannage....................................................................................................................... 23 5.2 Remplacement de la pile du module. ............................................................................... 24 5.3 Maintenance sur un onduleur dot du module HotSwap MBP....................................... 26

6. Annexes
6.1 Caractristiques techniques............................................................................................ .27 6.2 Programmation des prises programmables.................................................................... .28 6.3 Glossaire........................................................................................................................... 31

86-86710-00FR A02 - Page 3

86-86710-00FR A02 - Page 4

Introduction
Merci davoir choisi un produit de EATON pour protger votre quipement lectrique. Les produits de la gamme des produits EX on t conus avec le plus grand soin. Nous vous recommandons de lire attentivement le prsent manuel afin de profiter pleinement de toutes les caractristiques de votre onduleur ou UPS (systme dalimentation sans coupure). Avertissement : Il sagit dun onduleur de classe A. Dans un environnement domiciliaire, ce produit peut causer de linterfrence radio. Le cas chant, lutilisateur pourrait devoir prendre des mesures additionnelles. Si vous installez lappareil dans un environnement de surtension de catgorie III ou IV, vous devez galement prvoir une protection supplmentaire contre les surtensions en amont. Avant dinstaller votre EX, veuillez lire la brochure sur les instructions de scurit obligatoires. Suivez ensuite les indications dans le prsent manuel. Pour connatre tous les produits de EATON, ainsi que les options offertes pour la gamme EX, nous vous invitons consulter notre site Web au www.eaton.com ou communiquer avec votre reprsentant de EATON.

Protection environnementale
EATON a mis en uvre une politique de protection environnementale. Nos produits sont conus en adoptant une approche cologique.

Substances
Ce produit ne contient pas de CFC, de HCFC ou damiante.

Emballage
Pour amliorer le traitement des dchets et faciliter le recyclage, triez les divers matriaux demballage. w Le carton utilis est compos 50 % de carton recycl. w Les sacs sont faits de polythylne. w Les matriaux demballages sont recyclables et affichent le symbole didentification appropri. 01
PET

Matriau Polythylne trphthalate Polythylne de haute densit Polychlorure de vinyle Polythylne de faible densit Polypropylne Polystyrne

Abrviation PET HDPE PVC LDPE PP PS

Symbole numro 01 02 03 04 05 06

01
PET

Au moment dliminer les matriaux demballage, respectez les rglements locaux.

Fin de vie
EATON traitera les produits en fin de vie de service conformment aux rglements locaux. EATON collabore avec les entreprises responsables de recueillir et dliminer nos produits en fin de dure de vie.
w Produit Ce produit est fait de matriaux recyclables. Il faut dsassembler et dtruire le produit conformment tous les rglements locaux sur les dchets. Lorsque le produit atteint la fin de sa vie de service, il faut le transporter dans un centre de traitement des dchets lectriques et lectroniques. w Pile Ce produit contient des piles au plomb qui doivent tre traites conformment aux rglements locaux sur les piles.

Conformment aux rglements et des fins dlimination correcte, il est possible de retirer la pile. La fiche signaltique des piles est accessible dans notre site Web.* (*) Pour obtenir de plus amples renseignements ou pour communiquer avec le directeur de la politique environnementale du produit, utilisez le formulaire environnemental dans notre site : www.eaton.com/pulsar

86-86710-00FR A02 - Page 5

DIRECTIVES IMPORTANTES SUR LA SCURIT


CONSERVEZ CES INSTRUCTIONS. Le prsent manuel contient des instructions importantes quil faut suivre durant linstallation et lentretien de londuleur et des piles. Les modles de la gamme EX entionns dans le prsent manuels sont conus pour un environnement ayant une temprature ambiante entre 0 et 40C (32F et 104F), exempt de contaminants conducteurs. Cet quipement a fait lobjet dessais et a t dclar conforme aux limites des dispositifs numriques de classe A, conformment la partie 15 des rglements de la FCC. Ces limites ont t tablies pour offrir une protection raisonnable contre linterfrence nuisible lorsque lquipement est utilis dans un environnement commercial. Cet quipement gnre, utilise et met de lnergie RF et, sil nest pas install et utilis conformment au manuel dinstruction, peut causer des interfrences nuisibles aux communications radio. Lutilisation de cet quipement dans une zone rsidentielle pourrait causer des interfrences nuisibles. Le cas chant, lutilisateur devra corriger le problme dinterfrence ses frais.

Normes de certification
w w

Normes de rsistance aux surtensions IEEE 587-1980/ANSI C62,41 1980 Rgles et rglements du FCC de la partie 15, sous-partie B, classe A w Liste de lUL 1778, normes en matire dquipement dalimentation sans coupure w IEC 61000-4-2 (DES) : niveau 4 w IEC 61000-4-3 (champ de rayonnement) : niveau 3 w IEC 61000-4-4 (transitoires lectriques rapides) : niveau 4 w IEC 61000-4-5 (transitoires rapides) : niveau 4 w IEEE-C6241 Catgorie B (onde oscillatoire) w IEC 61000-4-6 (champ lectromagntique) w IEC 61000-4-8 (champ magntique par conduction)
w w w w

Scurit des personnes


w w w w w w w w w w w

Le systme est muni de sa propre source dalimentation (la pile). Les prises dalimentation peuvent donc tre nergises mme si le systme nest pas branch une source dalimentation c.a. Le systme comporte des niveaux de tension dangereux. Pour cette raison, seul le personnel qualifi peut louvrir. Le systme doit tre mis la terre correctement. La pile fournie avec le systme contient de petites quantits de matires toxiques. Pour viter les accidents, respectez les directives suivantes : - Ne brlez jamais la pile (elle risque dexploser). - Nessayez pas douvrir la pile (llectrolyte est dangereux pour les yeux et la peau). - Respectez tous les rglements applicables au moment dliminer la pile. - La pile constitue un danger (choc lectrique, brlure). Le courant en court-circuit peut tre trs lev. Prenez donc les prcautions suivantes pour toutes les manipulations : enlevez montre, bagues, bracelets et tout autre objet mtallique; utilisez des outils munis de poignes isoles. - Ne placez pas doutils ou de pices en mtal sur la pile. Suivez les instructions de branchement et dutilisation de lUPS dans lordre indiqu dans le manuel. Il faut installer un disjoncteur de protection facilement accessible en amont. Il est possible de couper lalimentation c.a. du systme par le disjoncteur. Assurez-vous que les indications de la plaque signaltique correspondent votre systme aliment par une source c.a. et la consommation lectrique de tout lquipement raccorder au systme. Il faut installer une prise de courant proximit de lappareil et celle-ci devra tre facilement accessible. Ninstallez jamais le systme prs de liquide ou dans un environnement excessivement humide. Ne laissez jamais un corps tranger entrer dans le systme. Ne bloquez jamais les grilles de ventilation du systme. Nexposez jamais le systme la lumire directe du soleil ou une source de chaleur. Si vous devez entreposer le systme avant de lutiliser, entreposez-le dans un endroit sec. La plage de tempratures appropries pour lentreposage du systme est de -20 C +40 C (-4 F 104 F). La temprature maximale de fonctionnement sans diminution de puissance est 40C (104F). Toute les manipulations requirent au moins deux personnes (dballage, installation dans un rack). Avant et aprs linstallation, si lUPS demeure hors-tension pendant une longue priode, mettez-le sous tension pendant 24 heures au moins une fois tous les six mois ( une temprature dentreposage normale de moins de 25 C (77 F)). Vous chargez ainsi la pile et vitez des dommages irrparables. Durant le remplacement de la pile, il est essentiel dutiliser le mme type et le mme nombre dlments que la pile originale, fournie avec londuleur, afin dobtenir le mme niveau de rendement et de scurit. En cas de doute, nhsitez pas communiquer avec votre reprsentant EATON.

Scurit du produit

Prcautions spciales
w w

Environnement

w w

Ce produit a t conu pour respecter lenvironnement : Il ne contient aucun Chlorofluorocarbone (CFC) ou Hydrochlorofluorocarbone (HCFC). Recyclage de lUPS la fin de sa vie de service : EATON sengage recycler, par lentremise dentreprises certifies et conformment tous les rglements, tous les onduleurs rcuprs la fin de leur vie de service (communiquez avec votre succursale de EATON). Emballage : Il faut recycler les matriaux demballage des onduleurs conformment tous les rglements applicables. AVERTISSEMENT: Ce produit contient une pile au plomb. Le plomb est une substance nocive pour lenvironnement sil nest pas recycl correctement par des entreprises spcialises.

86-86710-00FR A02 - Page 6

Symboles utiliss
Instructions importantes quil faut toujours suivre.

Information, conseil, aide.

Aide visuelle.

Action.

Signal sonore.

Voyant teint.

Voyant allum.

Voyant clignotant.

86-86710-00FR A02 - Page 7

86-86710-00FR A02 - Page 8

1. Prsentation
1.1 Positions standard
Position tour
Dimensions (L x H x P) en pouces EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 17,3 x 3,38 x 25,2 17,3 x 5,16 x 19,3 17,3 x 3,38 x 25,2 17,3 x 5,16 x 19,3 17,3 x 5,16 x 19,3 17,3 x 5,16 x 19,3


Position rack

Poids en livres EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL 70 68 72 70 41 93

EX EXB RT 3U

Numros de pice EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 86722 86723 86732 86733 86735 68405

86-86710-00FR A02 - Page 9

1. Prsentation
1.2 Panneaux arrire
EX 2200 / 3000 / 3000 XL
EX 2200

EX EXB (pile en option)

12

12

13

(1) Port de communication USB (2) Port de communication RS232 (3) Connecteur de reconnaissance automatique de lajout dune pile supplmentaire (4) Fente pour carte de communication facultative (5) Connecteur de MHTD et ADD (mise hors tension distance et activation / dsactivation distance) (6) Connecteur pour pile additionnelle (7) botier L5-20R (ou L5-30R pour EX 3000) pour la connexion de lappareil (8) 2 prises programmables pour le branchement dquipement (9) Groupe de 4 prises pour le branchement dquipement (10) Cble dalimentation dentre de 3 m w L5-30P pour EX 3000 w 5-20P pour EX 2200 (11) LED (SWF) indiquant linversion phase/ neutre du systme dalimentation (12) Connecteurs de pile (vers londuleur ou les autres piles) (13) Connecteur de reconnaissance automatique de pile

1.3

Panneau de commande

(20) (21) (22) (23) (24) (25) (26) (27)

Voyant de charge protge Voyant de fonctionnement dgrad Voyant de charge non protge LCD Bouton Echappement (annuler) Bouton dfilement Bouton Entre (confirmer) Bouton dactivation/dsactivation de lUPS et des prises

86-86710-00FR A02 - Page 10

2. Installation
2.1 Dballage et vrification du contenu

(30) (33) (34) (36) (37) EX 2200 ou 3000 UPS Cble de communication RS232 Cble de communication USB CD-ROM Solution-Pac Documentations fournies selon la version ou loption (38) Kit de montage pour les baies de 19 pouces (48 cm), lexception des modles RT 3U. (39) Deux supports dinstallation la verticale (version 2U seulement) (40) Module FlexPDU (optionnel) (42) Carte de communication NMC (optionnelle) (43) Fonctionnement du module HotSwap MBP (optionnel)

Il faut liminer les matriaux demballage conformment tous les rglements locaux sur les dchets. Les symboles de recyclage sont imprims sur les matriaux demballage pour en faciliter le triage.

86-86710-00FR A02 - Page 11

2. Installation
2.2 Installation en position tour

2.3

Installation en position rack


Il est conseill dinstaller la pile, puis le module dalimentation au dessus.

Suivez les tapes 1 4 pour installer le module sur des rails.

Les rails et la quincaillerie ncessaire sont fournis, lexception des modles 3U, par EATON.

86-86710-00FR A02 - Page 12

2. Installation
2.4 Ports de communication
Raccordement du port de communication RS232 ou USB (facultatif)
Les ports de communication RS232 et USB ne peuvent pas fonctionner simultanment. 1. Branchez le cble de communication RS232 (33) ou USB (34) dans le port srie ou USB de lordinateur. 2. Branchez lautre extrmit du cble de communication (33) ou (34) dans le port de communication USB (1) ou RS232 (2) de lUPS. Londuleur peut maintenant communiquer avec le logiciel de gestion de lalimentation de EATON.

Installation des cartes de communication (optionnelles)


Fente de carte de communication (accs limit)

Il nest pas ncessaire de mettre londuleur hors tension avant dinsrer une carte de communication. 1. Enlevez le cache de lUPS maintenu en place par quatre vis. 2. Insrez la carte de communication dans la fente. 3. Fixez la carte laide de vis.

86-86710-00FR A02 - Page 13

2. Installation
2.5 Connexions avec un module FlexPDU (unit de distribution dalimentation) (optionnel)
EX 3000 1. Branchez le cble dalimentation de lUPS (10) la source dalimentation secteur. 2. Branchez le cble dentre du module FlexPDU (48) la prise de londuleur (9). Le cble et la prise apparaissent en rouge. 3. Branchez lappareil aux prises (45), (46) sur le module FlexPDU. Les prises ne seront pas les mmes selon la version du module FlexPDU.

2.6

Connexions avec un module HotSwap MBP (optionnel)


Le module HotSwap MBP permet de remettre en service ou de rparer lUPS sans altrer les charges connectes (fonction HotSwap). 1. Branchez le cble dentre (56) du module HotSwap MBP la source dalimentation secteur. 2. Branchez le cble dentre de londuleur (10) lentre de londuleur (55) du module HotSwap MBP. Ce cble et le botier apparaissent en bleu. 3. Branchez le cble dentre de londuleur (7) au cordon de sortie de londuleur (54) du module HotSwap MBP. Ce cble et le botier apparaissent en bleu. 4. Branchez lappareil aux prises (49) sur le module HotSwap MBP. Prcaution: Nutilisez pas de prises de londuleur (8) et (9) pour alimenter lquipement car lutilisation de linterrupteur (53) du module HotSwap MBP couperait lalimentation lquipement. Il est recommand de ne pas retirer le film protecteur des prises (8) et (9). .

EX 3000

86-86710-00FR A02 - Page 14

2. Installation
Fonctionnement du module HotSwap MBP
Le module HotSwap MBP possde un interrupteur rotatif (53) deux positions: Normal La charge est alimente par la pile de londuleur. Le voyant (51) est allum. Bypass La charge est alimente par lalimentationsource dalimentation secteur. Le voyant (52) est allum.

Dmarrage de londuleur avec le module HotSwap MBP


1. Vrifiez que londuleur est correctement connect au module HotSwap MBP. 2. Placez linterrupteur (53) sur la position Normal. 3. Dmarrez londuleur en appuyant sur le bouton MARCHE/ARRET (27) du panneau de configuration de londuleur. La charge est alimente par londuleur Le voyant (51) UPS ON - OK to switch du module HotSwap MBP sallume.

Test du module HotSwap MBP


1. Rglez linterrupteur (53) sur la position Bypass et vrifiez que la charge est toujours alimente. 2. Placez linterrupteur (53) sur la position Normal.

2.7

Connexion de londuleur sans module FlexPDU ou HotSwap MBP


Assurez-vous que les indications de la plaque signaltique larrire de londuleur correspondent lalimentation c.a. et la consommation lectrique relle de la charge totale. 1. Branchez le cble dentre (31) (120 V 30 A / ou 20 A sur le EX 2200) la source dalimentation secteur. 2. Branchez les charges sur londuleur. Il est prfrable de brancher les charges prioritaires dans les quatres prises (9) et les charges non prioritaires aux deux prises marques (8) pouvant tre programmes. Branchez les appareils grande puissance la prise (7) 20 A (ou 30 A sur le EX 3000) comme indiqu sur la gauche pour EX 2200. Vous devez utiliser le logiciel de communication de EATON pour programmer la mise hors-tension des prises (8) durant le fonctionnement en mode pile afin doptimiser la dure dutilisation du systme.

Remarque : Londuleur charge la batterie ds lors quelle est connecte sur une source dalimentation CA, mme si le bouton (27) nest pas enfonc. Une fois londuleur branch la source dalimentation CA, il faut compter huit heures avant que la batterie ne puisse alimenter le temps de secours nominal.

86-86710-00FR A02 - Page 15

(Page laisse vierge volontairement)

86-86710-00FR A02 - Page 16

3. Fonctionnement
3.1 Dmarrage et fonctionnement normal
Pour le dmarrage initial, lalimentation secteur doit pouvoir dtecter tout erreur de cblage. Aprs le dmarrage inital, londuleur peut dmarrer mme si lalimentation secteur nest prsente. Appuyez sur le bouton (27) pendant environ 1 seconde. w Lindicateur sonore met un bip et tous les voyants sallument simultanment. w Lavertisseur sonore met dux bips pendant le test automatique, puis le bouton (27) reste activ, indiquant que les botiers de sortie sont aliments.

Les dispositifs branchs sont protgs par londuleur. w Le voyant (20) est allum.

Si le voyant (22) est allum, une faute sest produite (voir la section Dpannage ). w Dans des conditions normales de fonctionnement, le bouton de dfilement (25) peut tre utilis pour lire les mesures de londuleur (la tension sur les entres secteur de drivation et normale, le mode de fonctionnement, la capacit de la pile et le numro de srie de londuleur).

Personnalisation de londuleur

Si la personnalisation de londuleur est souhaite, il est recommand de saisir le mode personnalisation ce stade. Il est possible daccder au mode laide des boutons du panneau de configuration ou le logiciel Pac-Solution personnelle (Windows) inclus dans le CD-ROM Solution-Pac fourni par EATON.

86-86710-00FR A02 - Page 17

3. Fonctionnement
3.2 Fonctionnement avec alimentation par pile
to battery power Passer Transfer lalimentation par pile

w Les dispositifs connects demeurent protgs par londuleur lorsque lalimentation secteur nest plus fonctionnelle. Lnergie ncessaire est fournie par la pile. w Les voyants (20) et (21) sont allums. w Lalarme sonore met un bip toutes les dix secondes.

Low-battery Alimentation faible warning


20

Les dispositifs branchs sont aliments par la pile. Lcran affiche le temps de secours restant.

w Les voyants (20) et (21) sont allums. w Lavertisseur sonore met un bip toutes les trois secondes.

La charge de la pile est faible. Fermez tous les dispositifs branchs dans londuleur, car celui-ci sera bientt hors-fonction.

Fin de la priode dalimentation par pile


w Tous les voyants steignent. w Lavertisseur sonore sarrte.

i
3.3

LUPS est entirement hors tension

Retour de lalimentation secteur


la suite dune panne, londuleur redmarre automatiquement lorsque lalimentation secteur fonctionne de nouveau ( moins que la fonction de redmarrage automatique a t dsactive en personnalisant les options de londuleur); la charge est alors nouveau alimente.

3.4

Mise hors service de londuleur


Appuyez sur le bouton (27) pendant environ 2 sec. Les dispositifs branchs londuleur ne sont plus aliments.

86-86710-00FR A02 - Page 18

3. Fonctionnement
3.5 Utilisation de la commande distance de londuleur
EX possde deux options de commande distance. w w MHTD: La mise hors tension distance permet dutiliser un contact distance pour couper lalimentation de tous les dispositifs branchs londuleur. Il faut ensuite redmarrer londuleur manuellement. ROO (mise sous tension et hors tension distance): Lactivation/dsactivation distance permet de mettre londuleur hors tension laide dune action distance du bouton (27).

Ces fonctions sont accessibles en ouvrant le contact entre les broches appropries du connecteur (5) du panneau arrire de londuleur (voir le schma ci-dessous). EX 3000


Connexion et essai de commande distance
1. 2. Vrifiez si londuleur est teint et si le rseau dalimentation est dconnect. Dbranchez le connecteur (5) aprs avoir retir les vis.

3. Branchez un contact normalement ferm sans tension (maximum de 60 V c.c. / 30 V c.a., maximum de 20 mA, 0,75 mm2 de section du cble) entre les deux broches du connecteur (5), reportez-vous au diagramme.

ROO

Contact ouvert : mise hors tension de londuleur Contact ferm : dmarrage de londuleur (onduleur connect au rseau et rseau aliment) Remarque : La commande dactivation/ dsactivation locale, laide du bouton (27), prvaut sur la fonction distance.

RPO

Contact ouvert : mise hors tension de londuleur Pour retourner en fonctionnement normal, dsactivez le contact distance (le voyant (14) steint) et appuyez sur le bouton (27) pour redmarrer londuleur. 4. Branchez le connecteur (5) larrire de londuleur. 5. Branchez et mettez londuleur sous tension conformment aux procdures prcdemment dcrites. 6. Activez le contact de mise hors tension distance pour tester la fonction. Avertissement : Il faut brancher ce connecteur des circuits TBTS (trs basse tension de scurit).

86-86710-00FR A02 - Page 19

(Page laisse vierge volontairement)

86-86710-00FR A02 - Page 20

4. Accs aux donnes de personnalisation et de maintenance


4.1 Structure daffichage
tats et Alarmes tats et Alarmes

Mesures Mesures d'entre de l'onduleur Mesures de sortie de l'onduleur Mesures de la batterie

Personnalisation Personnalisation locale Personnalisation de sortie


Personnalisation des options de mise en marche/arrt

Personnalisation des options de la pile

4.2

Accs aux mesures


Appuyez sur le bouton de dfilement (25) pour accder aux conditions et alarmes dtat, puis aux mesures relatives la tension, courant, frquence, la puissance et le temps de secours de la batterie.

4.3

Personnalisation laide du panneau de configuration


w Appuyez plusieurs fois sur le bouton de dfilement (25) jusqu trouver le menu de personnalisation. w Appuyez sur Entre (26) pour accder aux diffrentes options. w Confirmez enfin la slection en appuyant nouveau sur Entre (26).

Fonction Langue Avertisseur sonore Configuration dusine Anglais Activ

. Autres rglages possibles Franais, Espagnol, Portugais Dsactiv

86-86710-00FR A02 - Page 21

4. Accs aux donnes de personnalisation et de maintenance


Personnalisation de sortie
Fonction Puissance de sortie Convertisseur de frquence (1)
(1)

Configuration dusine 120 Volts c.a. Dsactiv

Options 100/104/110/120/127 Volts C.A. Activ


(2)

Commentaires

Les dispositifs connects ne sont jamais transfrs par la drivation. Slectionnable par lutilisateur que si la fonction de convertisseur de frquence est active

Frquence de sortie

(1)

Slection automatique

50 ou 60 Hz

Lalimentation secteur en Transfert vers lentre drivation doit se situer secteur en drivation (1) dans les limites Niveau de surcharge
(1)

Lalimentation secteur en drivation peut dpasser les limites 50 / 70% Alarme en cas de dpassement de seuil.

102%

Personnalisation des options de mise en marche/arrt


Fonction Dmarrage sur lalimentation par pile Configuration dusine Activ Options Dsactiv Dsactiv Londuleur redmarre automatiquement lors du retour de lalimentation secteur. Une fois la fonction active, la pile steint lorsque lalimentation atteint Une fois la fonction active, londuleur reste hors tension si le systme dtecte linversion de phase/neutre. Commentaires

Redmarrage automaActiv tique

Economies dnergie

Dsactiv

Activ

Dtection dinversion Activ de phase/neutre (SWF)

Dsactiv

Personnalisation des options de pile


Fonction Test de pile Configuration dusine Test hebdomadaire Options Aucun test / test quotidien / test mensuel Londuleur redmarre automatiquement lors du retour de la source secteur Normal est rtablie. Une fois la fonction dsactive, la garantie EATON nest plus valable. Commentaires

Slection du temps de Dtection automatique du de 0 200 Ah secours nombre de piles La protection de la pile Activ contre les dcharges excessives

Dsactiv

4.4

Personnalisation laide du logiciel externe


w Insrez le CD-ROM Solution-Pac dans le lecteur. Dans le premier cran de navigation, slectionnez Solution Point point, puis suivez les instructions sur la faon dinstaller le logiciel Personal Solution-Pac. Slectionnez ensuite Configuration, Configuration avance et Configuration UPS.

w w

Veuillez noter que les versions de Personal Solution-Pac pour Linux/Unix/MacOS noffrent pas cette option. (1). Ces paramtres ne peuvent tre modifis que si londuleurest teint. (2). La drivation est dsactive lorsque le convertisseur de frquence est enclench.

86-86710-00FR A02 - Page 22

5. Entretien
5.1 Dpannage

Si le voyant (21) ou (22) est allum, une dfaillance ou une alarme sest produit. Utilisez le bouton Echappement (24) pour arrter lavertisseur sonore. Problme Diagnostic Solution

Londuleur ne dmarre pas, Lalimentation dentre nest pas w Vrifiez la disponibilit de lcran LCD indique : COLD connecte ou elle est connecte lalimentationsecteur. START NOK CHECK AC WIRING la sortie de londuleur. w Vrifiez que londuleur est correctement connect lalimentation dentre secteur. Le voyant (22) est allum, le Inversion de phase sur Vrifiez la polarit et le systme de mise la terre. voyant SWF (11) au dos de lalimentation dentre secteur. londuleur est allum. Lcran Londuleur ne dmarre pas. LCD indique: SITE WIR. FAULT CHECK AC WIRING Le voyant (22) est allum, La pile nest pas correctement lcran LCD indique : NO connecte. BATTERY CHECK CONNECTION Le voyant (22) est allum, lcran LCD indique : BATTERY FAULT SERV REQUIRED Le voyant (21) est allum, lcran LCD indique : OVERLOAD ALARM REDUCE LOAD Le voyant (22) est allum, lcran LCD indique : LOAD UNPROTECTED OUTPUT OVERLOAD Le voyant (22) est allum, lcran LCD indique : REDUCE LOAD RESTART UPS Vrifiez les branchements de la pile (se reporter au chapitre 5.2, Rinstallation du support pile).

Une panne est dtecte sur la pile. Remplacez la pile (se reporter au chapitre 5.2, Rinstallation du support pile). Appelez le service aprs-vente. Le niveau de charge dpasse le niveau de surcharge programm ou la capacit de londuleur. Londuleur est surcharg. Les dispositifs connects londuleur sont directement aliments par le rseau lectrique via le circuit de drivation. Aprs des charges rptes, londuleur est verrouill en position drivation. Les dispositifs connects londuleur sont directement aliments par le rseau lectrique. Londuleur steint automatiquement en raison de la surcharge sa sortie. Londuleur steint automatiquement en raison dun court-circuit sa sortie. Reduisez la charge.

Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire.

Le voyant (22) est allum, lcran LCD indique : OVERLOAD FAULT REDUCE LOAD Le voyant (22) est allum, lcran LCD indique : LOAD SHORT-CIRCU CHECK WIRING

Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire. Eteignez et redmarrez londuleur pour revenir en fonctionnement normal. Vrifiez la puissance de la charge des dispositifs branchs et dbranchez tout dispositif non prioritaire. Retirez la charge, et redmarrez londuleur. Appelez le service aprs-vente.

10

11

Le voyant (22) est allum, Une panne interne londuleur lcran LCD indique : INTERNAL sest produite. Il y a deux FAULT SERV REQUIRED possibles situations : w la charge est toujours alimente, mais directement laide dalimentation secteur via la drivation, w la charge nest plus alimente. Lcran LCD indique : REMOTE La commutation de la mise POWER OFF RPO hors tension distance (RPO) a provoqu la mise hors tension de londuleur.

Replacez le contact dans sa position normale, puis appuyez sur le bouton marche/arrt pour redmarrer.

86-86710-00FR A02 - Page 23

5. Entretien
Remise en service dun onduleur quip du module HotSwap MBP
Problme La charge nest plus fournie lorsque linterrupteur rotatif (53) du module HotSwap MBP est rgl sur la position Bypass (drivation).

Diagnostic

Solution

12

Vrifiez le cblage entre londuleur w Les dispositifs protgs sont connects la sortie de londuleur et le module HotSwap MBP (se en lieu et place du module reporter au chapitre 2.6). HotSwap MBP. w Le cble dalimentation secteur est connect lentre de londuleur en lieu et place du module HotSwap MBP. w Londuleur est hors tension. w Le cblage entre londuleur et le module HotSwap MBP nest pas correct. w Linterrupteur rotatif (53) du module HotSwap MBP est rgl sur la position Bypass (drivation). w Le cblage entre londuleur et le module HotSwap MBP nest pas correct. w Dmarrez londuleur. w Vrifiez le cblage entre londuleur et le module HotSwap MBP (se reporter au chapitre 2.6). w Rglez linterrupteur rotatif (53) du module HotSwap MBP sur la position Normal. w Vrifiez le cblage entre londuleur et le module HotSwap MBP (se reporter au chapitre 2.6). w Londuleur est hors tension

13

La charge nest plus fournie lorsque linterrupteur rotatif (53) du module HotSwap MBP est rgl sur la position Normal. La charge nest plus fournie si lalimentation secteur est en panne.

14

Si la panne provoque lextinction de londuleur, appuyez sur le bouton ON/OFF (27) pour mettre fin la panne.

5.2

Remplacement de la pile du module


Recommandations de scurit
La remise en services des piles doit tre effectue ou supervise par des personnes comptentes en matire de piles et au fait des prcautions ncessaires. Risque dexplosion si la pile est remplace par une autre type de pile. Lors du remplacement des piles, veillez installer des piles ou de pack daccus du mme type et du mme nombre. ATTENTION: Ne jetez pas les piles au feu. Elles risqueraient dexploser. Jetez les piles usages conformment aux instructions. ATTENTION: Nouvrez pas ou ne dmontez pas les piles. Llectrolyte libr est nocif pour la peau et les yeux. Il peut tre toxique. ATTENTION: Une pile peut comporter un risque dlectrocution et un courant puissant de court-circuit. Les prcautions suivantes doivent tre respectes si vous travaillez sur des piles: a. Retirez les montres, les bagues ou tout autre objet mtallique. b. Utilisez les outils avec des poignes isoles. c. Portez des gants en caoutchouc et des bottes. d. Ne placez pas doutils ou de pices en mtal sur la pile. e. Dconnectez la source en cours de charge avant de connecter ou de dconnecter les bornes de la pile. f. Vrifiez si la pile a t mise la terre par erreur. Le cas chant, retirez la source de la terre. Un contact avec toute partie de la pile mise la terre peut provoquer une lectrocution. La probabilit dun tel choc peut tre rduite si de telles terres sont retires au cours de linstallation et la maintenance (applicable lquipement et alimentations distance ne disposant pas dun circuit dalimentation mis la terre).

86-86710-00FR A02 - Page 24

5. Entretien
Dsinstallation du support piles
A. Enlevez les deux vis du ct gauche du panneau avant, puis retirez la pice.

B. Tirez sur les deux connecteurs pour dbrancher la pile (ne tirez pas sur les fils).

C. Dvissez le support mtallique et retirez la pice.

D. Retirez le pack daccus.

Installation du nouveau support pile


Excutez les instructions ci-dessus dans lordre inverse. w Afin de garantir la scurit et un rendement optimal, utilisez seulement les piles fournies par EATON. w Durant linstallation, assurez-vous dappuyer fermement lune contre lautre les deux parties du connecteur.

86-86710-00FR A02 - Page 25

5. Entretien
5.3 Maintenance sur un onduleur dot du module HotSwap MBP

Le module HotSwap MBP permet de remettre en service ou de rparer londuleur sans altrer les charges connectes (fonction HotSwap). Maintenance : 1. Placez linterrupteur (53) sur la position Bypass (drivation). Le voyant rouge (52) du module HotSwap MBP est allum, indiquant que la charge est directement fournie avec lalimentation secteur. 2. Arrtez londuleur en appuyant sur le bouton MARCHE/ARRET (27) du panneau de configuration de londuleur. Le voyant (51) UPS ON - OK to switch steint, londuleur peut dsormais tre dconnect et rinstall. Revenir au fonctionnement normal: 1. Vrifiez que londuleur est correctement connect au module HotSwap MBP. 2. Dmarrez londuleur en appuyant sur le bouton MARCHE/ARRT (27) du panneau de configuration de londuleur. Le voyant (51) UPS ON - OK to switch du module HotSwap MBP sallume (si ce nest pas le cas, cela est d un erreur de branchement entre le module HotSwap MBP et londuleur). 3. Placez linterrupteur (53) sur la position Normal. Le voyant rouge (52) du module HotSwap MBP steint.

86-86710-00FR A02 - Page 26

6. Annexes
6.1 Caractristiques techniques


EX 2200 Puissance de sortie Rseau dalimentation lectrique w Tension dentre nominale w Plage des tensions dentre w Frquence w Facteur de puissance w Courant de fuite Charge de sortie w Tension w Frquence w Distorsion harmonique w Capacit de surcharge w Courant Pile 17,5 A
(7)

EX 3000 3000 VA (2) / 2550 W (3) 120 V monophas de 55 / 72 / 100 142 V > 0,95 < 2 mA Monophas 120 V 3 % (5) 50/60 Hz 0,5 % (6) < 4 % pour charge linaire, < 6 % pour charge non linaire 102 % continu, 105 % 20s, > 130% 1,5s 25 A 6 x 12V - 9 Ah, batterie sans entretien, au plomb
(8) (4)

EX 3000 XL 3000 VA (2) / 2150 W

EX EXB

(9)

2100 VA (1) / 1650 W

50/60 Hz (slection automatique)

6 x 12V - 7 Ah, batterie sans entretien, au plomb

sans batterie interne

Deux cbles 6 x 12 V - 9 Ah, batterie sans entretien, au plomb

Environnement w Plage de tempratures de fonctionnement w Humidit relative w Plage de tempratures de stockage w Altitude w Niveau sonore

De 0 C 40 C (de 32 F 104 F ) De 20 % 90 % (sans condensation) De -20 C 40 C (de -4 F 104 F) 1000 m < 47 dBA

(1) (2) (3) (4) (5) (6) (7) (8) (9)

Selon la tension de sortie slectionne: 100 V / 104 V / 110 V / 120 V / 127 V, la puissance de sortie est de 1890 VA / 1890 VA / 2100 VA / 2100 VA / 2100 VA. Selon la tension de sortie slectionne: 100 V / 104 V / 110 V / 120 V / 127 V, la puissance de sortie est de 2500VA / 2500VA / 2500VA / 3000VA / 3000VA. La puissance de sortie standard est de 2550 W, 2400 W avec un module EXB. Valeurs pour 33 % / 66 % / 100 % de la sortie de londuleur. Programmable: 100 V / 104 V / 110 V / 120 V / 127 V en utilisant le logiciel UPS Config (Configuration de londuleur). Le mode convertisseur de frquence est programmable laide du logiciel UPS Config. Selon la tension de sortie slectionne: 100 V / 104 V / 110 V / 120 V / 127 V, le courant de sortie maximal est de 18,9 A / 18,2 A / 19,1 A / 17,5 A / 16,5 A. Selon la tension de sortie slectionne: 100 V / 104 V / 110 V / 120 V / 127 V, le courant de sortie est de 25A / 24A / 22,7A / 25A / 23,6A. Le module EXB existe uniquement en modle 3U. Londuleur standardpeut tre connect 4 EXB.
86-86710-00FR A02 - Page 27

6. Annexes
6.2 Programmation des prises programmables
1. Pour ouvrir la fentre de configuration, faites un clic gauche sur Dmarrer / Programmes / EATON / Personal Solution Pac / Paramtres, ou cliquez droit sur la prise dalimentation PSP situ sur le SYS Tray. 2. Cliquez sur le symbole + ct de UPS Settings pour agrandir la section UPS Settings.

3. Cliquez sur Startup Timer et configurez Le group de prises redmarre aprs sur 0 pour que la prise Powershare alimente les prises principales en mme temps.

86-86710-00FR A02 - Page 28

6. Annexes
4. Rtpez ltape 3 pour chacune des prises programmables. 5. Aprs avoir effectu les changements, cliquez sur le bouton Appliquer. La section intitule Shutdown timer permet lutilisateur de dfinir la dure pendant laquelle la prise powershare doit fournir une alimentation aprs une perte de puissance. Pour configurer larrt de la prise powershare en mme temps que les prises principales: 6. Rglez Le groupe de prise est hors tension aprs sur 65535.

86-86710-00FR A02 - Page 29

(Page laisse vierge volontairement)

86-86710-00FR A02 - Page 30

6. Annexes
6.3 Glossaire
Entre c.a. de drivation Ligne de drivation de la source secteur, commande par londuleur, utilise pour alimenter directement la charge en cas de surcharge ou de dfaillance de londuleur.
Temps dalimentation de secours

Le temps durant lequel la charge est alimente par la pile de londuleur. Test interne de londuleur pour vrifier le statut de la pile. Les dispositifs connects aux sorties de londuleur. Dcharge de la pile au-del de la limite permise, entranant des dommages irrversibles celle-ci. Le module avec des prises donduleur pour une installation dans une baie. Il existe diffrents modules avec diffrents types de prises. Le mode de fonctionnement utilis pour convertir la frquence dalimentation secteur entre lentre et la sortie de londuleur (50 Hz -> 60 Hz ou 60 Hz -> 50 Hz). Le module drivation manuelle de londuleur des fins de maintenance. Il existe diffrents modules avec diffrents types de prises. Un niveau de tension de la pile indiquant que celle-ci est faible et que lutilisateur doit prendre des mesures, car lalimentation de la charge sera bientt interrompue. cran cristaux liquides. La ligne de courant c.a. alimentant londuleur dans des conditions normales. Le ratio de la puissance utilise par la charge comparativement la puissance maximale de lUPS. Il est possible de personnaliser certains paramtres de londuleur configurs en usine. Certaines fonctions de lUPS peuvent galement tre modifies laide du logiciel Personal Solution-Pac pour mieux satisfaire vos besoins. Ces sorties peuvent tre automatiquement mises hors tension en fonctionnement par pile (mise hors tension les dures peuvent tre programmes laide du logiciel Personal Solution Pac). Londuleur possde deux jeux de deux prises programmables. Il est possible de dmarrer les dispositifs connects londuleur mme en labsence dalimentation c.a. Londuleur ne fonctionne quavec une alimentation par pile Systme dalimentation sans coupure Cette fonction active ou dsactive le lancement des squences de mise en marche ou darrt de londuleur laide du logiciel de gestion de lalimentation le logiciel de gestion de lalimentation.

Tests de pile Equipements Dcharge profonde FlexPDU Convertisseur de frquence HotSwap MBP Avertissement de pile faible LCD Entre c.a. normale Pourcentage de charge Personnalisation

Sorties programmable

Dmarrage en mode lalimentation par pile Onduleur Mise en marche/arrt de lUPS

86-86710-00FR A02 - Page 31

Notes :

86-86710-00FR A02 - Page 32

www.eaton.com

EX

2200 RT 2U 2200 RT 3U 3000 RT 2U 3000 RT 3U 3000 RT 3U XL EXB RT 3U


Manual de instalacin y de usuario

Pulsar Series

Copyright 2008 EATON All rights reserved.

For Technical Support, Customer Care Center, or Customer FAQ, please call us at (800) 356-5794, or visit our website: www.eaton.com

86-86710-00ES A02 - Page 2

Contenido

Introduccin........................................................................................................................ 5 Importantes instrucciones de seguridad............................................................................ 6 Uso de smbolos. ................................................................................................................ 7

1. Presentacin
1.1 Posiciones estndar. ........................................................................................................... 9 1.2 Paneles posteriores.......................................................................................................... 10 1.3 Panel de control ............................................................................................................. 10

2. Instalacin
2.1 Desembalaje y control del contenido........................................................................... 11 2.2 Instalacin en posicin vertical . .................................................................................. 12 2.3 Instalacin en posicin horizontal................................................................................ 12 2.4 Puertos de comunicacin.............................................................................................. 13 2.5 Conexiones con un Mdulo FlexPDU (Unidad de distribucin elctrica) (opcional) ....................................................................................................................... 14 2.6 Conexin con un Mdulo HotSwap MBP (opcional). .................................................. 14 2.7 Conexin de la UPS sin mdulos FlexPDU o HotSwap MBP. .................................... 15

3. Uso
3.1 Arranque y funcionamiento normal.................................................................................. 17 3.2 Funcionamiento con alimentacin de batera................................................................... 18 3.3 Retorno a la alimentacin con CA.................................................................................... 18 3.4 Apagado de la UPS. .......................................................................................................... 18 3.5 Uso de las Funciones de control remoto de la UPS........................................................ 19

4. Acceso a Mantenimiento y a Personalizacin de datos


4.1 4.2 4.3 4.4 Organizacin de la pantalla........................................................................................... 21 Acceso a Mediciones.. .................................................................................................... 21 Personalizacin utilizando el Panel de control............................................................ 21 Personalizacin utilizando software externo............................................................... 22

5. Mantenimiento
5.1 Solucin de inconvenientes. ............................................................................................. 23 5.2 Reemplazo del mdulo de la batera................................................................................ 24 5.3 Mantenimiento de una UPS equipada con el Mdulo HotSwap MBP. ............................ 26

6. Apndices
6.1 Especificaciones tcnicas. ............................................................................................... .27 6.2 Programacin de las Salidas programables...................................................................... 28 6.3 Glosario. ............................................................................................................................ 31

86-86710-00ES A02 - Page 3

86-86710-00ES A02 - Page 4

Introduccin
Gracias por elegir un producto EATON para proteger su equipo elctrico. La gama EX ha sido diseada con el mayor cuidado. Recomendamos dedicar tiempo a leer este manual para poder aprovechar todas las caractersticas de su UPS (Fuente de alimentacin ininterrumpida, por sus siglas en ingls). Advertencia: Esta es una UPS clase A. En un ambiente domstico, este producto puede causar interferencia radial, en cuyo caso el usuario puede tener que tomar medidas adicionales. En caso que el dispositivo sea instalado en ambientes con sobretensin categora III o IV, se deber protegerlo colocando una proteccin contra sobretensin antes de la conexin a la lnea de alimentacin. Antes de instalar una EX, lea el folleto sobre las instrucciones de seguridad necesarias. Luego siga las indicaciones de este manual. Para descubrir toda la gama de los productos EATON y otras opciones para la gama EX, le invitamos a visitar nuestro sitio en internet www.eaton.com o comunquese con su representante de EATON.

Proteccin del medio ambiente


EATON ha implementado una poltica de proteccin del medio ambiente. Los productos son desarrollados utilizando un enfoque ecolgico.

Sustancias
Este producto no contiene CFC, HCFC o asbestos.

Embalaje
Para mejorar el tratamiento de los residuos y facilitar el reciclaje, separe los diferentes componentes del embalaje. w El cartn que utilizamos incluye ms del 50% de cartn reciclado. w Las bolsas estn hechas de polietileno. 01 w Los materiales del embalaje son reciclables y cuentan con el correspondiente smbolo de identificacin.
PET

Materialo Tereflatalato de polietileno Polietileno de alta densidad Cloruro de polivinilo Polietileno de baja densidad Polipropileno Poliestiren

Abreviatura PET HDPE PVC LDPE PP PS

Nm. de Smbolo 01 02 03 04 05 06

01
PET

Siga la reglamentacin local para la disposicin de los materiales del embalaje.

Final de la vida til


EATON procesar los productos al final de su vida til de conformidad con la reglamentacin local. EATON trabaja con compaas encargadas de recolectar y eliminar nuestros productos al final de su vida til.
w Producto Este producto est hecho con materiales reciclables. El desmantelado y destruccin debe ser llevado a cabo obedeciendo todas las reglamentaciones locales sobre desechos. Al final de su vida til, este producto debe ser transportado a un centro de procesamiento de residuos elctricos y electrnicos. w Batera Este producto contiene bateras de plomo/cido que deben ser procesadas conforme a la reglamentacin local sobre bateras. La batera puede ser retirada para cumplir con la reglamentacin y con el propsito de su correcta disposicin final. En nuestro sitio internet* est disponible la MSDS (Planilla de seguridad del material, por sus siglas en ingls) de las bateras.

(*) Para obtener ms informacin o comunicarse con el gerente de control ambiental del Producto, visite nuestro sitio en internet: www.eaton.com/pulsar.

86-86710-00ES A02 - Page 5

IMPORTANTES INSTRUCCIONES DE SEGURIDAD


GUARDE ESTAS INSTRUCCIONES.
Este manual contiene instrucciones importantes que deben ser seguidas durante la instalacin y mantenimiento de la UPS y de las bateras. Los modelos EX incluidos en este manual estn diseados para ser instalados en ambientes con temperaturas entre 0 y 40 C (32 F a 104 F), libre de contaminantes conductivos. Este equipo ha sido evaluado y se ha determinado que cumple con los lmites para un dispositivo digital Clase A, conforme a la Parte 15 de las Reglas de la FCC. Estos lmites estn diseados para brindar una proteccin razonable contra interferencia daina cuando el equipo es utilizado en un ambiente comercial. Este equipo genera, utiliza y puede irradiar energa en frecuencia radial, y en caso que no sea instalado y utilizado conforme al manual de instrucciones, puede ocasionar interferencia daina a las comunicaciones por radio. El empleo de este equipo en una zona residencial puede causar interferencia daina, en cuyo caso el usuario deber solventar los gastos para corregir la interferencia. w w w w w w w w
w w w w w w

Normas de certificacin

Estndares IEEE 587-1980/ANSI C62,41 1980 para Capacidad para soportar saltos de tensin Reglas y normas de la FCC correspondientes a la Parte 15, Inciso J, Clase A Certificado UL con nmero 1778, Estndares para Equipo de alimentacin elctrica ininterrumpible IEC 61000-4-2 (ESD): nivel 4 IEC 61000-4-3 (Campo irradiado): nivel 3 IEC 61000-4-4 (EFT): nivel 4 IEC 61000-4-5 (Sobretensiones transitorias veloces): nivel 4 IEEE-C6241 Categora B (ondas oscilatorias) IEC 61000-4-6 (campo electromagntico) IEC 61000-4-8 (campo magntico conducido) El sistema cuenta con su propia fuente de alimentacin (la batera). Por lo tanto, las tomas de corriente pueden estar vivas inclusive si los sistemas estn desconectados de la fuente de alimentacin de CA. El sistema cuenta con un peligroso nivel de tensin. Slo lo deber abrir personal capacitado de servicio. El sistema deber contar con una buena puesta a tierra. La batera provista con el sistema contiene pequeas cantidades de materiales txicos. Para evitar accidentes, se debern seguir las siguientes directivas: - Nunca exponga una batera al fuego (riesgo de explosin). - No intente abrir la batera (el electrolito es peligroso para los ojos y la piel). - Cumpla con todas las reglamentaciones correspondientes para hacer la disposicin final de la batera. - Las bateras constituyen un peligro (choques elctricos, quemaduras). La tensin de cortocircuito puede ser muy alta. Tenga en cuenta los siguientes puntos para la manipulacin: qutese el reloj, anillos, brazaletes y cualquier otro objeto metlico, use herramientas con manijas aisladas. - No coloque herramientas ni piezas metlicas sobre las bateras.

Seguridad de las personas


w w w w w w w w w w w

Seguridad del producto

Las instrucciones para conexin y uso de la UPS descritas en este manual deben ser seguidas en el orden indicado. Se debe colocar un disyuntor de proteccin antes de la conexin a la red en un lugar de fcil acceso. El sistema puede ser desconectado de la red de alimentacin de CA abriendo este disyuntor. Controle que todas las indicaciones en la placa de datos coincidan con su sistema de alimentacin de CA y con el consumo elctrico real de todo el equipo conectado al sistema. El tomacorriente debe estar colocado cerca del equipo y de fcil acceso. Nunca instale el sistema cerca de lquidos o en un ambiente excesivamente hmedo. Nunca permita que ingresen elementos extraos dentro del sistema. Nunca obstruya las rejillas de ventilacin del sistema. Nunca exponga el sistema a la luz solar directa o a fuentes de calor. En caso que el sistema deba ser almacenado antes de su instalacin, hgalo en un lugar seco. El rango admisible de temperatura es de -20 C a +40 C (-4 F a 104 F). La temperatura operativa mxima sin reduzcion de potencia es de 40C (104F).

Precauciones especiales
w w

Todas las operaciones de manipulacin requieren de dos personas como mnimo (desembalaje, instalacin en un bastidor de sistema). Antes y despus de la instalacin, si la UPS se mantiene descargada por un largo perodo, la UPS debe ser cargada por un perodo de 24 horas al menos una vez cada 6 meses (con temperaturas normales de almacenamiento inferiores a 25 C (77F)). Esto permite cargar la batera y evitar posibles daos irreversibles. Durante el reemplazo del Mdulo de la batera, es imperativo utilizar el mismo tipo y nmero de elemento que el Mdulo de batera original provisto con la UPS para mantener el mismo nivel de rendimiento y seguridad. En caso de duda, pngase inmediatamente en contacto con su representante EATON. Este producto ha sido diseado para respetar el medio ambiente: No contiene Clorofluocarbono (CFC) o Hidroclorofluocarbono (HCFC). Reciclado de la UPS al final de su vida til: EATON se encarga de reciclar, por medio de empresas autorizadas y que cumplen con todas las reglamentaciones vigentes, todos los productos UPS recuperados al final de su vida til (pngase en contacto con una sucursal de EATON). Embalaje: Los materiales del embalaje de la UPS deben ser reciclados conforme a la reglamentacin vigente. ADVERTENCIA: Este producto contiene bateras de plomo/cido. El plomo es una sustancia peligrosa para el medio ambiente en caso que no sea reciclado correctamente por compaas especializadas.

Medio ambiente

w w

86-86710-00ES A02 - Page 6

Uso de smbolos
Las instrucciones son importantes y siempre deben ser seguidas.

Informacin, consejo, ayuda.

Indicacin visual.

Accin.

Seal audible.

LED apagado.

LED encendido.

LED parpadeando.

86-86710-00ES A02 - Page 7

86-86710-00ES A02 - Page 8

1. Presentacin
1.1 Posiciones estndar
Posicin vertical
Dimensiones (A x A x P) en pulgadas EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 17,3 x 3,38 x 25,2 17,3 x 5,16 x 19,3 17,3 x 3,38 x 25,2 17,3 x 5,16 x 19,3 17,3 x 5,16 x 19,3 17,3 x 5,16 x 19,3


Posicin horizontal

Peso en libras EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL 70 68 72 70 41 93

EX EXB RT 3U

Nmero de las piezas EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 86722 86723 86732 86733 86735 68405

86-86710-00ES A02 - Page 9

1. Presentacin
1.2 Paneles posteriores
EX 2200 / 3000 / 3000 XL
EX 2200 (1) Puerto de comunicacin USB (2) Puerto de comunicacin RS232 (3) Conector para reconocimiento automtico del mdulo de batera adicional (4) Ranura para plaqueta opcional de comunicaciones (5) Conector para encendido/apagado remoto o para control RPO (Apagado remoto) (6) Conector para mdulo de batera adicional (7) Zcalo L5-20R (o L5-30R para EX 3000) para conexin de equipo (8) 2 salidas programables para la conexin de equipo (9) Grupos de 4 salidas para conectar equipos (10) Cable de entrada elctrica de 10 pies (3 m) w L5-30P para EX 3000 w 5-20P para EX 2200 (11) LED (SWF) que indica la inversin de fase/ neutro del sistema de distribucin (12) Conectores para los mdulos de batera (a la UPS o a otros mdulos de batera) (13) Conectores para reconocimiento automtico de los mdulos adicionales de batera
12 13

EX EXB (mdulo de batera opcional)

12

1.3

Panel de control

(20) (21) (22) (23) (24) (25) (26) (27)

LED de carga protegida LED de funcionamiento reducido LED de carga no protegida LCD Botn Escape (cancelar) Botn de avance de pgina Botn Enter (confirmar) Botn ON/OFF para la UPS y las salidas

86-86710-00ES A02 - Page 10

2. Instalacin
2.1 Desembalaje y control del contenido

(30) (33) (34) (36) (37) UPS EX 2200 o 3000 Cable de comunicacin RS232 Cable de comunicacin USB CD-ROM del Solution-Pac La documentacin provista depender de la versin o de los opcionales (38) Kit de instalacin en bahas de 19 pulgadas, excepto con modelos RT 3U (39) 2 soportes para posicin vertical (slo para versin 2U) (40) Mdulo FlexPDU (opcional) (42) Plaqueta de comunicacin NMC (opcional) (43) Funcionamiento del mdulo HotSwap MBP (opcional)

Los materiales de embalaje deben ser dispuestos de conformidad con todas las reglamentaciones locales sobre desechos. Los materiales de embalaje tienen impresos los smbolos de reciclaje para facilitar su clasificacin.

86-86710-00ES A02 - Page 11

2. Instalacin
2.2 Instalacin en posicin vertical


2.3

Instalacin en posicin horizontal


Se recomienda instalar primero el mdulo de batera, luego colocar el mdulo de alimentacin arriba.

Siga los pasos 1 al 4 para montar el mdulo en los soportes.

Loes rieles y herrajes necesarios estn incluidos, excepto para modelos 3U, por EATON.

86-86710-00ES A02 - Page 12

2. Instalacin
2.4 Puertos de comunicacin
Conexin del puerto de comunicaciones RS232 o USB (opcional)
Los puertos de comunicacin RS232 y USB no pueden ser utilizados al mismo tiempo.

1. Conecte el cable de comunicacin RS232 (33) o USB (34) al puerto serial o USB en el equipo de computacin. 2. Conecte el otro extremo del cable de comunicacin (33) o (34) al puerto de comunicacin USB (1) o RS232 (2) en la UPS. Ahora la UPS puede comunicarse con el software de administracin de alimentacin del EATON.

Instalacin de plaquetas de comunicacin (opcional)


Ranura para plaqueta de comunicacin (acceso restringido)

No es necesario apagar la UPS antes de instalar una plaqueta de comunicacin. 1. Retire la tapa de la UPS (4) que est sujeta con tornillos. 2. Introduzca la plaqueta de comunicacin en la ranura. 3. Fije la plaqueta con tornillos.

86-86710-00ES A02 - Page 13

2. Instalacin
2.5 Conexiones con un Mdulo FlexPDU (Unidad de distribucin elctrica) (opcional)
EX 3000 1. Conecte el cable de alimentacin de la UPS (10) a una fuente de CA. 2. Conecte el cable de entrada del mdulo FlexPDU (48) en la salida de la UPS (9). El cable y el tomacorriente estn marcados de color rojo. 3. Conecte el equipo en las salidas (45) y (46) del mdulo FlexPDU. Estas salidas varan, dependiendo de la versin del mdulo FlexPDU.

2.6

Conexiones con un Mdulo HotSwap MBP (opcional)


El mdulo HotSwap MBP permite hacer mantenimiento o hasta reemplazar la UPS sin afectar las cargas conectadas (funcin HotSwap). EX 3000

1. Conecte el cable de entrada (56) del mdulo HotSwap MBP a la fuente de CA. 2. Conecte el cable de entrada (10) de la UPS a la entrada UPS Input (55) del mdulo HotSwap MBP. El cable y el tomacorriente estn marcados de color azul. 3. Conecte el tomacorriente de salida (7) de la UPS al cable UPS Output (54) del mdulo HotSwap MBP. El cable y el tomacorriente estn marcados de color rojo. 4. Conecte el equipo en la salida (49) del mdulo HotSwap MBP.

Precaucin: No utilice las salidas (8) y (9) de la UPS para alimentar equipo debido a que el empleo del interruptor (53) del mdulo HotSwap MBP podra cortar la alimentacin del equipo. No se recomienda retirar la cinta protectora de las salidas (8) y (9).

86-86710-00ES A02 - Page 14

2. Instalacin
Funcionamiento del mdulo HotSwap MBP
El mdulo HotSwap MBP cuenta con una perilla selectora (53) con dos posiciones: Normal la carga es alimentada por la UPS, el LED (51) est encendido. Bypass la carga es alimentada directamente por la fuente de alimentacin de CA. El LED (52) est encendido.

Arranque de la UPS con el mdulo HotSwap MBP


1. Controle que la UPS est correctamente conectada al mdulo HotSwap MBP. 2. Coloque el selector (53) en la posicin Normal. 3. Encienda la UPS oprimiendo el botn ON/OFF (27) en el panel de control de la UPS. La carga es alimentada por la UPS. El LED (51) UPS ON - OK to switch (UPS encendida - OK para cambiar) en el mdulo HotSwap MBP se enciende.

Mdulo de prueba del HotSwap MBP


1. Coloque el selector (53) en la posicin Bypass y controle que toda la carga siga alimentada. 2. Coloque el selector (53) nuevamente en la posicin Normal.

2.7

Conexin de la UPS sin mdulos FlexPDU o HotSwap MBP


Controle que las indicaciones en la placa de datos ubicada en la parte posterior de la UPS corresponde a la fuente de alimentacin de CA y el verdadero consumo elctrico de la carga total. 1. Conecte el cable de entrada (31) (120V 30A / o 20A del EX 2200) a la fuente de alimentacin de CA. 2. Conecte las cargas a la UPS. Es preferible conectar las cargas prioritarias en las cuatro salidas marcadas (9) y las cargas no prioritarias en las dos salidas marcadas (8) que pueden ser programadas. Conecte todos los dispositivos de alto consumo a la salida de 20A (o 30A en el EX 3000) (7) tal como se muestra a la izquierda de la EX 2200. Para programar el apagado de las salidas (8) durante el uso de la alimentacin con batera y as optimizar el tiempo de respaldo disponible, se necesita del software de comunicacin EATON.

Nota: La UPS carga la batera tan pronto como se la conecta a una fuente de alimentacin de CA, aunque no se haya oprimido el botn (27). Una vez que la UPS est conectada a una fuente de alimentacin de CA, sern necesarias ocho horas de carga para que la batera pueda ofrecer el tiempo de respaldo ofrecido.

86-86710-00ES A02 - Page 15

(Esta pgina ha quedado intencionalmente en blanco)

86-86710-00ES A02 - Page 16

3. Uso
3.1 Arranque y funcionamiento normal
Para en encendido inicial, se debe conectar la CA para detectar errores de conexin. Luego del arranque inicial, la UPS puede arrancar incluso si no hay tensin de CA presente. Oprima el botn (27) durante aproximadamente 1 seg. w El zumbador suena una vez y todos los LED se encienden simultneamente. w El zumbador suena dos veces durante la autoverificacin, luego el botn (27) se mantiene encendido, lo que indica la presencia de energa en los tomacorrientes de salida.

Los dispositivos conectados estn protegidos por la UPS. w El LED (20) est encendido.

En caso que el LED (22) est encendido, se ha producido una falla (consulte la seccin Solucin de inconvenientes). w Durante el funcionamiento normal, el botn de avance de pgina (25) puede ser utilizado para leer las mediciones de la UPS (voltaje en las entradas normal y derivacin de CA, modo operativo, capacidad de la batera y nmero de serie de la UPS).

Personalizacin de la UPS

En caso que se desee personalizar la UPS, se recomienda ingresar al modo de personalizacin en este momento. Se ingresa a este modo utilizando los botones en el panel posterior o en el software Personal Solution-Pac (Windows) incluido en el CD-ROM del Solution-Pac provisto por EATON.

86-86710-00ES A02 - Page 17

3. Uso
3.2 Funcionamiento con alimentacin de batera
Transfer to battery power Transferencia a alimentacin con batera

w Los dispositivos conectados siguen alimentados por la UPS cuando se pierde la alimentacin de CA. La energa necesaria es provista por la batera. w Los LED (20) y (21) estn encendidos. w La alarma audible suena cada diez segundos.

Baja carga de batera Low-battery warning


20

Los dispositivos conectados son alimentados por la batera. La pantalla indica el tiempo restante de alimentacin con batera.

w Los LED (20) y (21) estn encendidos. w La alarma audible suena cada tres segundos.

La carga remanente en la batera es baja. Cierre todas las aplicaciones del equipo conectado porque es inminente el apagado automtico de la UPS.

Final del tiempo de respaldo de la batera


w Todos los LED se apagan. w Se detiene la alarma audible.

i
3.3

La UPS queda completamente apagada.

Retorno a la alimentacin con CA


Luego de un corte, la UPS se enciende automticamente cuando recupera alimentacin de CA (excepto se haya deshabilitado la funcin de reencendido por medio de la personalizacin de la UPS) y nuevamente se alimenta la carga.

3.4

Apagado de la UPS
Oprima el botn (27) durante aproximadamente 2 seg. Los dispositivos conectados a la UPS ya no reciben alimentacin.

86-86710-00ES A02 - Page 18

3. Uso
3.5 Uso de las Funciones de control remoto de la UPS
La EX tiene la opcin de dos controles remotos. w w RPO: El Apagado remoto permite utilizar un contacto remoto para desconectar de la fuente de alimentacin a todos los equipos conectados a la UPS. El reencendido de la UPS requiere de accionamiento manual. ROO: El encendido y apagado remoto permite el accionamiento remoto del botn (27).

Estas funciones se seleccionan abriendo un contacto conectado entre las correspondientes clavijas del conector (5) en el panel posterior de la UPS (vea el diagrama que aparece a continuacin). EX 3000


Conexin y prueba de la conexin remota
1. 2. Controle que la UPS est apagada y que est desconectada la red de alimentacin elctrica. Retire el conector (5) luego de destornillar los tornillos.

3. Conecte un contacto normal cerrado sin tensin (60 V CC / 30 V CA mx., 20 mA mx., cable de 0,75 mm2 de seccin) entre las dos clavijas del conector (5), vea el diagrama.

ROO

Contacto abierto: apagado de la UPS Contacto cerrado: encendido de la UPS (UPS conectada a la red y la red con tensin) Nota: el control local de encendido/apagado por medio del botn (27) tiene prioridad sobre la orden del control remoto.

RPO

Contacto abierto: apagado de la UPS Para volver al funcionamiento normal, desactive el botn externo de apagado remoto y encienda nuevamente la UPS utilizando el botn (27).

4. Conector de clavija (5) en la parte posterior de la UPS. 5. Conecte y encienda nuevamente la UPS de acuerdo los procedimientos descritos anteriormente. 6. Active el contacto de apagado remoto externo para probar la funcin. Advertencia: Este conector slo debe ser conectado a circuitos SELV (Circuito de seguridad para voltajes muy bajos, por sus siglas en ingls).

86-86710-00ES A02 - Page 19

(Esta pgina ha quedado intencionalmente en blanco)

86-86710-00ES A02 - Page 20

4. Acceso a Mantenimiento y a Personalizacin de datos


4.1 Organizacin de la pantalla
Estado y alarmas Estado y alarmas

Mediciones Mediciones de entrada en la UPS Mediciones de salida de la UPS Mediciones de la batera

Personalizacin Personalizacin local Personalizacin de salida


Personalizacin de encendido/apagado

Personalizacin de la batera

4.2

Acceso a Mediciones.
Oprima el botn de avance de pgina (25) para ingresar a todas las condiciones de estado y alarma, luego a las mediciones de voltaje, corriente, frecuencia, potencia de salida y tiempo de respaldo de la batera.

4.3

Personalizacin utilizando el panel de control


w Oprima el botn Scroll (25) (avance de pantalla) varias veces hasta alcanzar el men de personalizacin. w Oprima el botn Enter (26) (Confirmar) para ingresar a las diferentes posibilidades. w Finalmente confirme la eleccin oprimiendo nuevamente el botn Enter (26).

Funcin Idioma Alarma audible

Configuracin de fbrica Ingls Habilitado

Otras configuraciones disponibles Francs, Espaol, Portugus Deshabilitado

86-86710-00ES A02 - Page 21

4. Acceso a Mantenimiento y a Personalizacin de datos


Personalizacin de salida
Funcin Voltaje de salida Convertidor de frecuencia (1) Frecuencia de salida
(1)

Configuracin de fbrica 120 Voltios CA Deshabilitado

Opciones 100/104/110/120/127 Voltios CA Habilitado(2)

Comentarios

(1)

Seleccin automtica

50 o 60 Hz

Los dispositivos conectados nunca son transferidos a la derivacin. Slo modificable por el usuario en caso que est habilitada la funcin del convertidor de frecuencia.

Transferir a la entrada derivada de CA (1) Nivel de sobrecarga


(1)

La alimentacin derivada La alimentacin derivada de CA debe quedar dentro de CA puede estar fuera de tolerancia de las tolerancias 102% 50 / 70% Se dispara la alarma si se sobrepasa el umbral.

Personalizacin de encendido/apagado
Funcin
Arranque con alimentacin de batera

Configuracin de fbrica Habilitado Habilitado

Opciones Deshabilitado Deshabilitado

Comentarios

Reinicio automtico Ahorro de energa

La UPS se reiniciar automticamente cuando se reestablezca la alimentacin de CA. Cuando la funcin est habilitada, la batera se apaga cuando la reserva cae hasta el < 5%. Cuando la funcin est habilitada, la UPS se mantiene apagada si el sistema detecta una inversin de fase / neutro

Deshabilitado

Habilitado

Deteccin de inversin Habilitado de fase / neutro (SWF)

Deshabilitado

Personalizacin de la batera
Funcin Prueba de batera Seleccin del tiempo de respaldo Proteccin de batera contra descarga excesiva Configuracin de fbrica Prueba semanal Opciones No probar / prueba diaria / prueba mensual La UPS arranca automticamente cuando se reestablece la alimentacin de CA Normal. Cuando la funcin est deshabilitada, la garanta de EATON ya no tiene validez. Comentarios

Deteccin automtica de la cantidad de mdulos de 0 a 200 Ah batera Habilitado Deshabilitado

4.4

Personalizacin utilizando software externo


w Introduzca el CD-ROM del Solution-Pac en la lectora. w En la primera pantalla de navegacin, seleccione Point to Point solution y siga las instrucciones sobre cmo instalar el software Personal Solution-Pac.

w Luego seleccione Settings (Configuracin), Advanced settings (Configuracin avanzada) y UPS settings (Configuracin de la UPS). Tenga en cuenta que las versiones para Linux/Unix/MacOS del software Personal Solution-Pac no ofrecen esta posibilidad. (1). Estos parmetros pueden ser modificados nicamente cuando la UPSest apagada. (2). La derivacin queda deshabilitada cuando se habilita el convertidor de frecuencia.

86-86710-00ES A02 - Page 22

5. Mantenimiento
5.1 Solucin de inconvenientes
En caso de que el LED (21) o el (22) estn encendidos, se ha producido una falla o una alarma. Utilice el botn escape (24) para apagar la alarma audible.

Indicacin 1 Si la UPS no enciende, el LCD indicar: COLD START NOK CHECK AC WIRING El LED (22) est encendido, el LED SWF (11) en la parte posterior de la UPS est encendida. El LCD presenta: SITE WIR. FAULT CHECK AC WIRING El LED (22) est encendido, la LCD presenta: NO BATTERY CHECK CONNECTION El LED (22) est encendido, la LCD presenta: BATTERY FAULT SERV REQUIRED El LED (21) est encendido, la LCD presenta: OVERLOAD ALARM REDUCE LOAD El LED (22) est encendido, la LCD presenta: LOAD UNPROTECTED OUTPUT OVERLOAD El LED (22) est encendido, la LCD presenta: REDUCE LOAD RESTART UPS 7

Diagstico No se ha conectado la alimentacin elctrica o est conectada en la salida de la UPS.

Correccin w Compruebe la disponibilidad de CA. w Compruebe que la UPS est bien conectada a la alimentacin elctrica.

Inversin de fase en la entrada de Compruebe la polaridad y el sistema CA. La UPS no enciende. de puesta a masa.

La batera est conectada incorrectamente. Se ha detectado una falla en la batera.

Controle las conexiones de la batera (consulte la Seccin 5.2, reemplazo del mdulo de la batera). Reemplace la batera (consulte la Seccin 5.2: Reemplazo del mdulo de la batera). Llame al departamento de atencin post-venta.. Reduzca la carga.

El nivel de carga supera el nivel de sobrecarga programado o la capacidad de la UPS. La UPS est sobrecargada. Los dispositivos conectados a la UPS se alimentan directamente de la red de alimentacin elctrica a travs de la Derivacin. Luego de una repeticin de sobrecargas, la UPS quedar bloqueada en posicin Derivacin. Los dispositivos conectados a la UPS se alimentarn directamente de la red de alimentacin elctrica. La UPS se apaga automticamente debido a una sobrecarga en la salida de la UPS.

Verifique el consumo de los dispositivos conectados y desconecte aquellos que no sean prioritarios.

Verifique el consumo de los dispositivos conectados y desconecte aquellos que no sean prioritarios. Apague y reencienda la UPS para volver al funcionamiento normal.

El LED (22) est encendido, la LCD presenta: OVERLOAD FAULT REDUCE LOAD El LED (22) est encendido, la LCD presenta: LOAD SHORT-CIRCU CHECK WIRING

Verifique el consumo de los dispositivos conectados y desconecte aquellos que no sean prioritarios. Desconecte la carga y luego reencienda la UPS.

10

11

La UPS se apaga automticamente debido a un cortocircuito en la salida de la UPS. El LED (22) est encendido, la Se ha producido una falla interna LCD presenta: INTERNAL FAULT en la UPS. Existen dos situaciones SERV REQUIRED posibles: w la carga es todava alimentada, pero directamente con CA proveniente de la derivacin, w la carga ya no recibe alimentacin. El LCD presenta: REMOTE El accionamiento del Apagado POWER OFF RPO remoto (RPO) ha causado el apagado de la UPS.

Llame al departamento de atencin post-venta.

Ponga el contacto en posicin normal y oprima el botn ON/OFF para reiniciar.

86-86710-00ES A02 - Page 23

5. Mantenimiento
Solucin de inconvenientes de una UPS equipada con el Mdulo HotSwap MBP
Indicacin La carga no ser alimentada cuando la perilla selectora (53) del mdulo HotSwap MBP est en la posicin Bypass.

Diagstico
w Los dispositivos protegidos estn conectados a la salida de la UPS en lugar del mdulo HotSwap MBP. w El cable de alimentacin de CA est conectado a la entrada de la UPS en lugar del mdulo HotSwap MBP. w La UPS est apagada. w La conexin entre la UPS y el mdulo HotSwap MBP es incorrecta. w La perilla selectora (53) del mdulo HotSwap MBP se coloca en la posicin Bypass. w La conexin entre la UPS y el mdulo HotSwap MBP es incorrecta.

Correccin
Controle la conexin entre la UPS y el mdulo HotSwap MBP (consulte la Seccin 2.6).

12

13

La carga no ser alimentada cuando la perilla selectora (53) del mdulo HotSwap MBP est en la posicin Normal. La carga no ser alimentada si falla la alimentacin de CA.

w Encendido de la UPS. w Controle la conexin entre la UPS y el mdulo HotSwap MBP (consulte la Seccin 2.6). w Coloque la perilla selectora (53) del mdulo HotSwap MBP en posicin Normal. w Controle la conexin entre la UPS y el mdulo HotSwap MBP (consulte la Seccin 2.6). w La UPS est apagada

14

Si una falla conduce a un apagado de la UPS, oprima el botn ON/OFF (27) para eliminar la falla.

5.2

Reemplazo del mdulo de la batera


Recomendaciones de seguridad
El mantenimiento de las bateras debe ser llevado a cabo por personal capacitado en bateras y tomando las precauciones correspondientes. Existe riesgo de explosin si la batera es reemplazada por otra del tipo incorrecto. Al reemplazar bateras, utilice nuevas bateras del mismo tipo y cantidad de bateras o de paquetes de bateras. PRECAUCIN: PRECAUCIN: PRECAUCIN: No arroje las bateras en el fuego. Las bateras pueden estallar. Deseche las bateras usadas de acuerdo con las instrucciones. No abra ni dae las bateras. Los derrames de electrolito son peligrosos para la piel y para los ojos. Puede ser txico. Una batera puede presentar el peligro de choque elctrico y de una alta corriente de cortocircuito. Se debern tener en cuenta las siguientes precauciones al trabajar con bateras:

a. Qutese relojes, anillos y cualquier otro objeto metlico. b. Utilice herramientas con mangos aislados. c. Utilice guantes y botas de caucho. d. No coloque herramientas ni piezas metlicas sobre las bateras. e. Desconecte la fuente de carga antes de conectar o desconectar los terminales de las bateras. f. Controle que la batera no haya quedado inadvertidamente puesta a masa. En caso que est inadvertidamente a masa, desconecta la fuente de la masa. El contacto con cualquier parte de una batera puesta a masa puede causar un choque elctrico. La posibilidad de sufrir tal choque puede reducirse si tales puestas a masa son retiradas durante la instalacin y el mantenimiento (aplicable a la alimentacin de equipos y bateras que no cuenten con un circuito de alimentacin con puesta a masa).

86-86710-00ES A02 - Page 24

5. Mantenimiento
Extraccin del mdulo de batera
A. Destornille el lateral izquierdo del panel frontal (dos tornillos), luego retire la pieza.

B. Desconecte el bloque de la batera separando los dos conectores (nunca tire de los cables).

C. Destornille el soporte metlico y retire la pieza.

D. Retire el paquete de bateras.

Instalacin del nuevo mdulo de batera


Realice las instrucciones antes mencionadas en el orden inverso. w w Para garantizar la seguridad y un alto rendimiento, use solamente bateras provistas por EATON. Asegrese de conectar firmemente las dos partes del conector durante el armado.

86-86710-00ES A02 - Page 25

5. Mantenimiento
5.3 Mantenimiento de una UPS equipada con el Mdulo HotSwap MBP

El mdulo HotSwap MBP permite hacer mantenimiento o hasta reemplazar la UPS sin afectar las cargas conectadas (funcin HotSwap). Mantenimiento: 1. Coloque el selector (53) en la posicin Bypass. El LED rojo (52) del mdulo HotSwap MBP est encendido, lo que indica que la carga est siendo alimentada directamente con la fuente de CA. 2. Apague la UPS oprimiendo el botn ON/ OFF (27) en el panel de control de la UPS. Cuando el LED (51) UPS ON - OK to switch se apaga, se puede desconectar o reemplazar la UPS. Vuelta al funcionamiento normal: 1. Controle que la UPS est correctamente conectada al mdulo HotSwap MBP. 2. Encienda la UPS oprimiendo el botn ON/ OFF (27) en el panel de control de la UPS. El LED (51) UPS ON - OK to switch del mdulo HotSwap MBP se enciende (en caso contrario, existe un error de conexin entre el mdulo HotSwap MBP y la UPS). 3. Coloque el selector (53) en la posicin Normal. El LED rojo (52) del mdulo HotSwap MBP se apaga.

86-86710-00ES A02 - Page 26

6. Apndices
6.1 Especificaciones tcnicas


EX 2200 Potencia de salida Red de alimentacin elctrica w Tensin nominal de entrada w Rango de tensin de entrada w Frecuencia w Factor de potencia w Corriente de fuga Salida a carga w Tensin w Frecuencia w Distorsin armnica w Capacidad de sobrecarga w Corriente 2100 VA (1) / 1650 W EX 3000 3000 VA (2) / 2550 W (3) Monofase de 120 V 55 / 72 / 100 a 142 V (4) 50/60 Hz (seleccin automtica) > 0,95 < 2 mA Monofsica de 120 V 3% (5) 50/60 Hz 0,5% (6) < 4% para carga lineal, < 6% para carga no lineal 102% continua, 105% 20s, > 130% 1,5s 17,5 A
(7)

EX 3000 XL 3000 VA (2) / 2150 W

EX EXB

(9)

25 A

(8)

Batera

6 x 12V - 7 Ah, 6 x 12V - 9 Ah, sellada de plomo / cido sellada de plomo / cido libre de mantenimiento libre de mantenimiento

sin batera interna

Dos conjuntos de 6 x 12 V - 9 Ah, selladas de cido / plomo libres de mantenimiento

Medio ambiente w Rango de temperatura operativa w Humedad relativa w Rango de temperatura de almacenado w Altitud w Nivel de ruido

0C a 40C (32F a 104F ) 20% a 90% (sin condensacin) -20C a 40C (-4F a 104F) 1000 m < 47 dBA

(1) (2) (3) (4) (5) (6) (7)

(8) (9)

Dependiendo del voltaje de salida seleccionado: 100V / 104V / 110V / 120V / 127V, la potencia de salida es de 1890VA / 1890VA / 2100VA / 2100VA / 2100VA. Dependiendo del voltaje de salida seleccionado: 100V / 104V / 110V / 120V / 127V, la potencia de salida es de 2500VA / 2500VA / 2500VA / 3000VA / 3000VA. La potencia de salida es de 2550 W, 2400 W con un mdulo EXB. Valores para salidas del 33% / 66% / 100% de la UPS. Programable: 100V / 104V / 110V / 120V / 127V utilizando el software UPS Config. El modo del convertidor de frecuencia es programable usando el software UPS Config. Dependiendo del voltaje de salida seleccionado: 100V / 104V / 110V / 120V / 127V, la potencia mxima de salida es de 18,9A / 18,2A / 19,1A / 17,5A / 16,5A. Dependiendo del voltaje de salida seleccionado: 100V / 104V / 110V / 120V / 127V, la potencia mxima de salida es de 25A / 24A / 22,7A / 25A / 23,6A. El EXB slo est presente en el modelo 3U. Las UPS estndar pueden ser conectadas con hasta 4 EXB.
86-86710-00ES A02 - Page 27

6. Apndices
6.2 Programacin de las Salidas programables
1. Para abrir la ventana Setting (Configuracin), haga clic con botn izquierdo en Start Menu / Programs / EATON / Personal Solution Pac / Settings, o clic con botn derecho en el enchufe PSP de alimentacin que aparece en la SYS Tray. 2. Haga clic en el smbolo + al lado de UPS Settings para expandir la seccin UPS Settings

3. Haga clic en Startup Timer y cambie el The group of outlets restarts after (Grupo de tomacorrientes que se reencienden luego) a 0 para compartir la potencia disponible entre todos los tomacorrientes principales al mismo tiempo.

86-86710-00ES A02 - Page 28

6. Apndices
4. Repita el paso 3 para cada tomacorriente programable. 5. Luego de hacer los cambios, haga clic en el botn Apply (Aplicar). La seccin titulada Shutdown timer (Temporizador de apagado) le permite al usuario definir el tiempo que permanecer activo el tomacorriente luego de un corte de energa elctrica. Para configurar el apagado de la distribucin de energa al mismo tiempo que los tomacorrientes principales: 6. Programe el The group of outlet is powered OFF after en 65535.

86-86710-00ES A02 - Page 29

(Esta pgina ha quedado intencionalmente en blanco)

86-86710-00ES A02 - Page 30

6. Apndices
6.3 Glosario
Derivacin de entrada CA Tiempo de respaldo Prueba de batera Equipos Descarga excesiva FlexPDU Lnea derivada desde la fuente de alimentacin de CA, controlada por la UPS, usada de para alimentar directamente la carga, incluso si se produce una sobrecarga o una falla en la UPS. Tiempo durante el cual la UPS puede alimentar una carga con su batera. Prueba interna de la UPS para controlar el estado de su batera. Dispositivos conectados a la salida de la UPS. La batera se descarga por debajo del lmite aceptable, lo que le causa daos irreparables. Mdulo con tomacorrientes de UPS para instalacin en una baha. Existen diferentes tipos de mdulos con diferentes tipos de tomacorrientes.

Convertidor de frecuencia El mdulo operativo utilizado para convertir la CA entre la entrada y la salida de la UPS (50 Hz -> 60 Hz o 60 Hz -> 50 Hz). HotSwap MBP Advertencia de batera baja LCD Entrada normal de CA Porcentaje de carga Personalizacin Mdulo de derivacin manual de la UPS para mantenimiento. Existen diferentes tipos de mdulos con diferentes tipos de tomacorrientes. Este es un nivel de voltaje de batera que indica que la carga de la batera es baja y que el usuario debe tomar medidas en vista del inminente corte en la alimentacin de la carga. Pantalla de cristal lquido. La lnea de CA que alimenta la UPS est en condiciones normales. Proporcin entre el consumo efectivamente tomado por la carga y la salida mxima de la UPS. Es posible modificar ciertos parmetros de la UPS programados en fbrica. Ciertas funciones de la UPS tambin pueden ser modificadas por medio del software Personal Solution-Pac para satisfacer mejor las necesidades del usuario. Estas salidas pueden ser apagadas automticamente durante el funcionamiento con alimentacin de batera (el apagado por temporizador puede ser programado con el software Personal Solution Pac). La UPS cuenta con dos conjuntos de salidas programables. Los dispositivos conectados a la UPS pueden ser encendidos incluso si no hay entrada de alimentacin de CA. La alimentacin de energa elctrica de la UPS trabaja solamente con la carga de la batera. Sistema de alimentacin ininterrumpible. Esta funcin habilita o deshabilita el control de las secuencias de encendido y apagado de la UPS por medio de una computadora.

Salidas programables

Arranque con alimentacin de batera UPS Encendido/Apagado de la UPS controlado por software

86-86710-00ES A02 - Page 31

Notas:

86-86710-00ES A02 - Page 32

www.eaton.com

EX

2200 RT 2U 2200 RT 3U 3000 RT 2U 3000 RT 3U 3000 RT 3U XL EXB RT 3U


Manual de instalao e do usurio

Pulsar Series

Copyright 2008 EATON All rights reserved.

For Technical Support, Customer Care Center, or Customer FAQ, please call us at (800) 356-5794, or visit our website: www.eaton.com

86-86710-00PT A02 - Page 2

ndice

Introduo. .......................................................................................................................... 5 Instrues Importantes de Segurana............................................................................... 6 Uso de smbolos. ................................................................................................................ 7

1. Apresentao
1.1 Posies padro................................................................................................................. 9 1.2 Painis traseiros............................................................................................................... 10 1.3 Painel de controle . .......................................................................................................... 10

2. Instalao
2.1 Como desembalar e verificao de contedo.................................................................. 11 2.2 Instalao na posio de torre ........................................................................................ 12 2.3 Instalao na posio de rack. .......................................................................................... 12 2.4 Portas de comunicao.................................................................................................... 13 2.5 As conexes com um mdulo FlexPDU (Unidade de distribuio de energia) (opcional)......................................................................................................................... 14 2.6 Conexo com um mdulo HotSwap MBP (opcional)....................................................... 14 2.7 Conexo UPS sem um mdulo FlexPDU ou HotSwap MBP........................................... 15

3. Operao
3.1 Inicializao e operao normal........................................................................................ 17 3.2 Operao com bateria...................................................................................................... 18 3.3 Retorno de energia CA..................................................................................................... 18 3.4 Desligamento do UPS...................................................................................................... 18 3.5 Usando as funes de controle remoto do UPS. ............................................................. 19

4. Acesso aos dados de manuteno e de personalizao


4.1 4.2 4.3 4.4 Organizao da exibio................................................................................................... 21 Acesso s medies........................................................................................................ 21 Personalizao usando o painel de controle. .................................................................... 21 Personalizao usando o software externo. ..................................................................... 22

5. Manuteno
5.1 Soluo de problemas ..................................................................................................... 23 5.2 Substituio do mdulo da bateria................................................................................... 24 5.3 Manuteno de um UPS equipado com mdulo HotSwap MBP ................................. 526

6. Apndices
6.1 Especificaes tcnicas. .................................................................................................. .27 6.2 Programando as tomadas programveis.......................................................................... 28 6.3 Glossrio........................................................................................................................... 31

86-86710-00PT A02 - Page 3

86-86710-00PT A02 - Page 4

Introduo
Obrigado por selecionar um produto EATON para proteger seu equipamento eltrico. A linha EX foi criada com o maior cuidado. Recomendamos que voc leia este manual para aproveitar completamente os vrios recursos do seu UPS (Uninterruptible Power System, Sistema de energia ininterrupta). Aviso: Este um produto UPS de classe A. Em um ambiente domstico, este produto pode provocar interferncia de rdio e, nesse caso, o usurio pode ter que tomar medidas adicionais. Se o dispositivo estiver instalado em ambientes de categoria III ou IV de sobrevoltagem, a proteo contra sobrevoltagem contra a corrente deve ser fornecida. Antes de instalar o EX, leia o folheto sobre as instrues de segurana necessrias. Em seguida, siga as indicaes neste manual. Para descobrir toda a gama de produtos EATON e as opes disponveis para a linha EX, o convidamos a visitar nosso site na Web em www.eaton.com ou entre em contato com o representante da EATON.

Proteo ambiental
A EATON implementou uma poltica de proteo ambiental. Os produtos so desenvolvidos de acordo com a abordagem de projeto ecologicamente correto.

Substncias
Este produto no contm CFCs, HCFCs ou asbestos.

Embalagem
Para melhorar o tratamento de resduos e facilitar a reciclagem, separe os vrios componentes da embalagem. w A caixa que usamos composta de mais de 50% de papelo. w Sacos e sacolas so feitos de polietileno. 01 w Os materiais da embalagem so reciclveis e contm o smbolo de identificao adequado. Material Polietileno terefalato Polietileno de alta densidade Polivinil cloreto Polietileno de baixa densidade Polipropileno Poliestireno Abreviao PET HDPE PVC LDPE PP PS
PET

Nmero do smbolo 01 02 03 04 05 06

01
PET

Siga todas as regulamentaes locais para o descarte de materiais de embalagem.

Fim de vida
A EATON processar produtos no fim de sua vida de servio em conformidade com as regulamentaes locais. A EATON trabalha com empresas encarregadas de coletar e eliminar nossos produtos no fim de sua vida de servio.
w Produto O produto feito de materiais reciclveis. A desmontagem e a destruio devem ocorrer em conformidade com todas as regulamentaes locais relacionadas aos resduos. No fim de sua vida de servio, o produto dever ser transportado para um centro de processamentos para resduos eltricos e eletrnicos. w Bateria O produto contm baterias de cido-chumbo que devem ser processadas de acordo com as regulamentaes locais aplicveis relacionadas s baterias. A bateria pode ser removida para ficar em conformidade com as regulamentaes, objetivando o descarte correto. As Fichas tcnicas de segurana de material (MSDS) para as baterias esto disponveis no nosso site*.

(*) Para mais informaes ou para entrar em contato com o gerente ambiental do produto, visite nosso website: www.eaton. com./pulsar

86-86710-00PT A02 - Page 5

INSTRUES IMPORTANTES DE SEGURANA


GUARDE ESTAS INSTRUES. Este manual contm instrues importantes que devem ser seguidas durante a instalao
e a manuteno do UPS e das baterias. Os modelos do EX que so cobertos neste manual devem ser usados para instalao em um ambiente dentro de 0 C a 40 C (32F a 104F), sem contaminante condutor. Este equipamento foi testado e descobriu-se que ele est de acordo com os limites de um dispositivo digital Classe A, de acordo com a Parte 15 das regras da FCC. Esses limites foram criados para fornecer proteo razovel contra interferncia danosa quando o equipamento for operado em um ambiente comercial. Este equipamento gera, usa e irradia energia de rdio-freqncia e, se no instalado e usado em conformidade com o manual de instruo, pode causar interferncia nociva em comunicaes via rdio. provvel que a operao deste equipamento em uma rea residencial provoque interferncia danosa, caso em que o usurio precisar corrigir a interferncia s suas prprias custas. w w w w w w w w
w w w w w w

Padres de certificao

IEEE 587-1980/ANSI C62.41 1980 Padro de capacidade de resistir a picos Regras e regulamentos da FCC, Parte 15, Sub-parte J, Classe A UL listado em 1778, Padres para equipamentos fornecimento de energia sem interrupo IEC 61000-4-2 (ESD): nvel 4 IEC 61000-4-3 (Campo irradiado): nvel 3 IEC 61000-4-4 (ESD): nvel 4 IEC 61000-4-5 (transientes rpidos): nvel 4 IEEE-C6241 Categoria B (tenso de toque) IEC 61000-4-6 (campo eletromagntico) IEC 61000-4-8 (campo magntico conduzido) O sistema possui sua prpria fonte de alimentao (a bateria). Conseqentemente, as tomadas de fora podem estar energizadas mesmo que o sistema esteja desconectado da tomada de CA da parede. Nveis perigosos de voltagem esto presentes no sistema. Para ser aberto somente por pessoal de servio qualificado. O sistema deve ser aterrado de maneira apropriada. A bateria fornecida com o sistema contm pequenas quantias de materiais txicos. Para evitar acidentes, as diretrizes abaixo devem ser observadas: - Nunca queime a bateria (risco de exploso). - No tente abrir a bateria (os eletrlitos so perigosos para os olhos e para a pele). - Obedea a todas as regulamentaes aplicveis para o descarte da bateria. - As baterias constituem-se em perigo (choque eltrico, queimaduras). A corrente de curto-circuito pode ser muito alta. Devem ser tomadas precaues para qualquer manuseio: retire relgios, anis, braceletes quaisquer outros objetos de metal e use ferramentas com cabos isolados. - No deixe ferramentas ou peas de metal sobre baterias.

Segurana de pessoas


w w w w w w w w w w w

Segurana do produto

As instrues de conexo e a operao do UPS descritas neste manual devem ser seguidas na ordem indicada. Deve ser instalado um disjuntor antes da entrada e o mesmo deve ser facilmente acessvel. O sistema pode ser desconectado da fonte de alimentao de CA desligando esse disjuntor. Confira se as indicaes na etiqueta de especificaes tcnicas correspondem a seu sistema de alimentao CA e ao real consumo de energia eltrica de todos os equipamentos conectados ao sistema. O soquete-tomada deve ser instalado prximo ao equipamento e deve estar facilmente acessvel. Nunca instale o sistema prximo de lquidos ou em um ambiente excessivamente mido. Nunca deixe que algum corpo estranho caia dentro do sistema. Nunca obstrua as grades de ventilao do sistema. Nunca exponha o sistema luz solar direta ou a uma fonte de calor. Se o sistema precisar ser armazenando antes da instalao, a armazenagem deve ser feita em local seco. A faixa admissvel de temperaturas de armazenamento de -20C a +40C (-4F a 104F). A temperatura operational mxima sem diminuio de potenca 40C (104F). Todas as operaes que manuseio tero de ser a duas pessoas (desembalagem e instalao em sistema de prateleira). Antes e aps a instalao, se o UPS permanecer sem energia por um perodo muito grande ele deve ser energizado durante um perodo de vinte e quatro horas, pelo menos uma vez por semestre (para um temperatura de operao normal, inferior a 25C) (77F)). Esse procedimento carrega a bateria, evitando possveis danos irreversveis. Durante a substituio do Mdulo da bateria, obrigatrio o uso do mesmo tipo e nmero de elementos que o Mdulo de bateria original fornecido com o UPS, para manter um nvel idntico de desempenho e segurana. Em caso de dvida, no hesite em entrar em contato com o seu representante EATON.

Precaues especiais
w w

Ambiente
w w

Este produto foi projetado para respeitar o ambiente: Ele no contm clorofluorocarboneto (CFC) nem hidroclorofluorocarboneto (HCFC). Reciclagem do UPS aps seu tempo de vida til: A EATON se compromete a reciclar, pro meio de empresas certificadas e em conformidade com os regulamentos aplicveis, todas os UPS recolhidos ao final de sua vida til (entre em contato com um escritrio de filial da EATON.) Embalagem: Os materiais da embalagem do UPS devem ser reciclados em conformidade com os regulamentos aplicveis. AVISO: Este produto contm baterias de chumbo-cido. O chumbo uma substncia perigosa para o ambiente se no for reciclado de maneira ,apropriada por empresas especializadas.

86-86710-00PT A02 - Page 6

Uso de smbolos
Instrues importantes que devem ser sempre seguidas.

Informao, notcia, ajuda.

Indicao visual.

Ao.

Sinal audvel.

LED desligado.

LED ligado

LED piscante.

86-86710-00PT A02 - Page 7

86-86710-00PT A02 - Page 8

1. Apresentao
1.1 Posies padro
Posio de torre
Dimenses (H x W x D) em polegadas EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 17,3 x 3,38 x 25,2 17,3 x 5,16 x 19,3 17,3 x 3,38 x 25,2 17,3 x 5,16 x 19,3 17,3 x 5,16 x 19,3 17,3 x 5,16 x 19,3


Posio de rack

Peso em libras EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL 70 68 72 70 41 93

EX EXB RT 3U

Nmeros das peas EX 2200 RT 2U EX 2200 RT 3U EX 3000 RT 2U EX 3000 RT 3U EX 3000 RT 3U XL EX EXB RT 3U 86722 86723 86732 86733 86735 68405

86-86710-00PT A02 - Page 9

1. Apresentao
1.2 Painis traseiros
EX 2200 / 3000 / 3000 XL
EX 2200 (1) Porta de comunicao USB (2) Porta de comunicao RS232 (3) Conector para reconhecimento automtico de mdulo adicional de bateria (4) Encaixe para placa de comunicao opcional (5) Conector para controle ON/OFF (LIGAR/ DESLIGAR remoto) ou RPO (Desligamento remoto) (6) Conector para mdulo adicional de bateria (7) L5-20R (ou L5-30R para EX 3000) receptculo para a conexo do equipamento (8) 2 tomadas programveis para a conexo do equipamento (9) Grupos de 4 tomadas para a conexo do equipamento. (10) Cabo de fora de entrada de 10 ps (3 metros) w L5-30P para EX 3000 w 5-20P para EX 2200 (11) LED (SWF) indicando a reverso do neutro/fase do sistema de distribuio (12) Conectores para mdulos de bateria (at o UPS ou para outros mdulos de bateria) (13) Conector para reconhecimento automtico de mdulos de baterias

EX EXB (mdulo de bateria opcional)

12

12

13

1.3

Painel de controle

(20) (21) (22) (23) (24) (25) (26) (27)

LED de carga protegida LED de funcionamento reduzido LED de carga no protegida LCD Boto Escape (cancelar) Boto Scroll (rolar) Boto Enter (confirmar) Boto LIGAR/DESLIGAR para o UPS e tomadas

86-86710-00PT A02 - Page 10

2. Instalao
2.1 Como desembalar e verificao de contedo

(30) (33) (34) (36) (37) EX 2200 ou 3000 UPS Cabo de comunicaes RS232 Cabo de comunicaes USB CD-ROM Solution-Pac A documentao fornecida depende da verso ou do opcional (38) Kit de montagem para compartimentos de 19 polegadas, exceto para os mdulos RT 3U (39) 2 suportes para a posio vertical (somente verso 2U) (40) Mdulo FlexPDU (opcional) (42) Carto de comunicaes NMC (opcional) (43) Mdulo HotSwap MBP (opcional)

Os materiais da embalagem do UPS devem ser reciclados em conformidade com os regulamentos aplicveis resduos. Os smbolos de reciclagem esto impressos nos materiais de embalagem, para facilitar a separao.

86-86710-00PT A02 - Page 11

2. Instalao
2.2 Instalao na posio de torre


2.3

Instalao na posio de rack


aconselhvel primeiro instalar o mdulo da bateria e ento o mdulo de energia acima. Siga as etapas 1 a 4, para a montagem do mdulo em trilhos.

Os trilhos e o hardware necessrios so fornecidos, exceto para os modelos 3U pela EATON.

86-86710-00PT A02 - Page 12

2. Instalao
2.4 Portas de comunicao
Conexo da porta de comunicao RS232 ou USB (opcional)
As portas de comunicao RS232 e USB no podem funcionar simultaneamente.

1. Conecte o cabo de comunicao RS232 (33) ou USB (34) porta serial ou porta USB no computador. 2. Conecte o outra extremidade do cabo de comunicao (33) ou (34) porta de comunicao USB (1) ou RS232 (2) do UPS. Agora o UPS pode se comunicar com software de gerenciamento de energia EATON.

Instalao das placas de comunicao (opcional)


Encaixe do carto de comunicao (acesso restrito)

No necessrio desligar o UPS antes de instalar a placa de comunicaes. 1. Retire a tampa do UPS (4) presa por parafusos. 2. Insira a placa de comunicaes no encaixe. 3. Prenda o carto com os parafusos.

86-86710-00PT A02 - Page 13

2. Instalao
2.5 As conexes com um mdulo FlexPDU (Unidade de distribuio de energia) (opcional)
EX 3000 1. Conecte o cabo de alimentao do UPS (10) fonte de alimentao CA. 2. Conecte o cabo de entrada do mdulo FlexPDU (48) tomada do UPS (9). O cabo e a tomada so marcadas em vermelho. 3. Conecte o equipamento s tomadas (45), (46) no mdulo FlexPDU. Essas tomadas so diferentes, dependendo da verso do mdulo FlexPDU.

2.6

Conexes com um mdulo HotSwap MBP (opcional)


O mdulo HotSwap MBP torna possvel a manuteno ou at mesmo a substituio do UPS sem afetar as cargas conectadas (funo HotSwap). EX 3000 1. Conecte o cabo de entrada (56) do mdulo HotSwap MBP fonte de alimentao CA. 2. Conecte o cabo de entrada do UPS (10) Entrada do UPS (55) do mdulo HotSwap MBP. Este cabo e o receptculo so marcados em azul. 3. Conecte a tomada do UPS (7) Sada do UPS (54) do mdulo HotSwap MBP. Esse cabo e a tomada so marcados em vermelho. 4. Conecte o equipamento s tomadas (49) no mdulo HotSwap MBP. Precauo: No use as tomadas (8) e (9) do UPS para alimentar o equipamento porque usar a chave (53) no mdulo HotSwap MBP cortar a alimentao do equipamento. aconselhvel no remover o filme protetor das tomadas (8) e (9).

86-86710-00PT A02 - Page 14

2. Instalao
Operao do mdulo HotSwap MBP
O mdulo HotSwap MBP possui uma chave giratria (53) com duas posies: Normal a carga fornecida pelo UPS, LED (51) est na posio ON (ativado). Bypass a carga fornecida diretamente (desvio) pela fonte de alimentao CA. LED (52) est na posio ON (ativado).

Inicializao do UPS com o mdulo HotSwap MBP


1. Verifique se o UPS est corretamente conectado ao mdulo HotSwap MBP. 2. Coloque a chave (53) na posio Normal. 3. Inicie o UPS pressionando do boto ON/OFF (27) no painel de controle do UPS. A carga fornecida pelo UPS. LED (51) UPS ON (LIGADO) - OK a chave no mdulo HotSwap MBP vai para a posio ON (LIGADA).

Teste do mdulo HotSwap MBP


1. Coloque a chave (53) na posio de desvio (Bypass) e verifique se a carga ainda est sendo fornecida. 2. Coloque a chave (53) de volta posio Normal.

2.7 Conexo UPS sem um mdulo FlexPDU ou HotSwap MBP


Verifique se as indicaes na placa do nome localizada na parte de trs do UPS correspondem fonte de alimentao CA e ao consumo eltrico verdadeiro da carga total. 1. Conecte o cabo de entrada (31) (120V 30A / ou 20A no EX 2200) fonte de alimentao CA. 2. Conecte as cargas ao UPS. prefervel conectar as cargas prioritrias s quatro tomadas marcadas (9) e as cargas no prioritrias s duas tomadas marcadas (8) que podem ser programadas. Conecte qualquer aparelho de potncia alta tomada 20A (ou 30A no EX 3000) (7) conforme mostrado esquerda do EX 2200. Para programar o desligamento das tomadas (8) durante o funcionamento da energia da bateria e dessa forma otimizar o tempo de reserva disponvel, necessrio o software de comunicao EATON .

Nota: O UPS carrega a bateria assim que conectado fonte de alimentao CA, mesmo se o boto (27) no estiver pressionado. Aps o UPS ter sido conectado fonte de alimentao CA, sero necessrias oito horas de carga para que a bateria possa fornecer o tempo de reservanominal.

86-86710-00PT A02 - Page 15

(Esta pgina foi deixada intencionalmente em branco)

86-86710-00PT A02 - Page 16

3. Operao
3.1 Inicializao e operao normal
Para a partida inicial, a alimentao CA deve estar presente para detectar qualquer erro de cabeamento. Aps a partida inicial, o UPS pode ser inicializado, mesmo se a alimentao CA no estiver presente. Pressione o boto (27) por cerca de um segundo. w A campainha soa uma vez e todos os LEDs se acendem simultaneamente. w A campainha soa duas vezes durante o auto-teste, ento o boto (27) permanece ligado, indicado que h energia nos receptculos da tomada

Os dispositivos conectados so protegidos pelo UPS. w LED (20) est na posio ON (ativado).

Se o LED (22) estiver ativado, ocorreu uma falha (consulte a seo Soluo de problemas). w Durante a operao normal, o boto de rolagem (25) pode ser usado para ler as medies do UPS (voltagem nas entradas normais e de CA de desvio, modo de operao, capacidade da bateria e nmero de srie UPS).

Personalizao do UPS

Se desejar personalizar o UPS, aconselhvel inserir o modo de personalizao dessa vez. Esse modo pode ser inserido usando-se os botes do painel de controle ou o Software Personal Solution-Pac (Windows) includo no CD-ROM Solution-Pac fornecido pela EATON.

86-86710-00PT A02 - Page 17

3. Operao
3.2 Operao com bateria
Transfer to a battery power Transferncia para energia da bateria
w Os dispositivos conectados continuam a receber energia do UPS se a energia da fonte de alimentao CA no estiver mais disponvel. A energia necessria fornecida pela bateria. w LED (20) e (21) esto na posio ON (ativados). w O alarme de udio soa a cada dez segundos.

Low-battery warning Energia da bateria fraca


20

Os dispositivos conectados recebem energia da bateria. O visor indica o tempo de reserva restante.

w LED (20) e (21) esto na posio ON (ativados). w O alarme de udio soa a cada trs segundos.

A carga restante da bateria est baixa. Desligue todos os aplicativos dos equipamentos conectados porque o desligamento do UPS iminente.

Fim do tempo de reserva da bateria


w Todos os LEDS se apagam. w Os alarmes de udio param.

i
3.3

O UPS completamente desligado

Retorno de energia CA
Aps uma interrupo de energia, o UPS automaticamente reinicializado quando a energia de alimentao CA retorna (a menos que a funo de restaurao tenha sido desativada por meio de personalizao do UPS) e a energia passar a ser fornecida novamente.

3.4

Desligamento do UPS
Pressione o boto (27) por cerca de dois segundos. Os dispositivos conectados ao UPS no mais recebem energia.

86-86710-00PT A02 - Page 18

3. Operao
3.5 Usando as funes de controle remoto do UPS
EX tem a escolha de duas opes de controle remoto. w w RPO: O desligamento remoto permite que se use um contato remoto para desconectar todos os equipamentos conectados ao UPS. A reinicializao do UPS exige interveno manual. ROO: Ligar/desligar remoto permite a ao remota do boto (27).

Essas funes so obtidas abrindo-se o contato conectado entre os pinos apropriados do conector (5) no painel traseiro do UPS (consulte o diagrama abaixo). EX 3000


Conexo e teste por controle remoto
1. 2. Verifique se o UPS est desligado e desconectado da rede de alimentao eltrica. Retire o conector (5) aps soltar os parafusos.

3. Conecte um contato sem voltagem normalmente fechado (60 Vdc / 30 Vac mx., 20 mA mx., seo transversal do cabo de 0,75 mm 2) entre os dois pinos do conector (5),consulte o diagrama.

ROO

Contato aberto: desligamento do UPS Contato fechado: inicializao do UPS (UPS conectado rede e rede energizada). Nota: o controle On/Off (liga/desliga) local por meio do boto (27) tem prioridade sobre a ordem de controle remota.

RPO

Contato aberto: desligamento do UPS Para retornar operao normal, desative o contato de desligamento remoto externo e reinicie o UPS usando o boto (27). 4. Ligue o plugue (5) na parte traseira do UPS. 5. Conecte e reinicie o UPS, conforme os procedimentos descritos anteriormente. 6. Ative o contato externo de desligamento remoto para testar a funo. Aviso: Este conector somente deve ser conectado a circuitos SELV (Voltagem segura extra-baixa).

86-86710-00PT A02 - Page 19

(Esta pgina foi deixada intencionalmente em branco)

86-86710-00PT A02 - Page 20

4. Acesso aos dados de manuteno e de personalizao


4.1 Organizao da exibio
Status e alarmes Status e alarmes

Medies Medies da entrada da UPS Medies da sada da UPS Medies da bateria

Personalizao Personalizao local Personalizao de sada


Personalizao ON/OFF (liga/desliga)

Personalizao da bateria

4.2 Acesso s medies


Pressione o boto de rolagem (25) para acessar qualquer condies de status e de alarme, ento as medies para tenso, corrente, freqncia, sada de energia e tempo de reserva da bateria.

4.3

Personalizao usando o painel de controle



w Pressione o boto de rolagem (Scroll) (25) diversas vezes at que o menu de personalizao seja alcanado. w Pressione o boto Enter (26) para acessar as diferentes possibilidades. w Finalmente, confirme a seleo, pressionando o boto Enter (26) novamente.

Funo Idioma Alarme de udio

Configurao de fbrica Ingls Ativado

Outras configuraes disponveis Francs, espanhol, portugus Desativada

86-86710-00PT A02 - Page 21

4. Acesso aos dados de manuteno e de personalizao


Personalizao de sada
Funo Voltagem de sada Conversor de freqncia (1) Freqncia de sada
(1) (1)

Configurao de fbrica 120 Volts CA Desativado Seleo automtica A energia CA de desvio deve estar dentro das tolerncias 102%

Opes 100/104/110/120/127 Volts CA Ativado


(2)

Comentrios

Os dispositivos conectados nunca so transferidos ao desvio. Usurio selecionvel somente se a funo do conversor de freqncia estiver ativada.

50 ou 60 Hz A energia CA de desvio pode estar fora das tolerncias 50 / 70%

Transferir para a entrada CA de desvio Nvel de sobrecarga


(1)

(1)

Alarme se o limite estiver ultrapassado.

Personalizao ON/OFF (liga/desliga)


Funo Inicializao com a energia da bateria Reinicializao automtica Economia de energia Configurao de fbrica Ativado Ativado Desativado Opes Desativado Desativado Ativado O UPS reinicia automaticamente quando a energia CA retorna. Quando a funo est ativada, a bateria desliga quando a energia cai para < 5%. Quando a funo est ativada, a UPS permanece OFF (desativada) se o sistema detectar a inverso fase/neutro. Comentrios

Deteco da inverso fase/ neutro (SWF)

Ativada

Desativado

Personalizao da bateria
Funo Teste da bateria Seleo do tempo de reserva Proteo da bateria contra descargas excessivas Configurao de fbrica Teste semanal Deteco automtica do nmero de mdulos da bateria Ativado Opes Sem testes / teste dirio / teste mensal 0 a 200 Ah UPS reinicia automaticamente quando a energia CA normal restaurada. Quando a funo est desativada, a garantia da EATON no mais se aplica. Comentrios

Desativado

4.4

Personalizao usando o software externo


w Insira o CD-ROM Solution-Pac na unidade. Na primeira tela de navegao, escolha a opo Soluo ponto a ponto e siga as instrues acerca de como instalar o software Personal Solution-Pac. A seguir selecione a opo Configuraes, Configuraes avanadas e Configuraes do UPS.

w
w

Observe que as verses do software Personal Solution-Pac para o Linux/Unix/MacOS no oferecem essa possibilidade. (1). Esses parmetros podem ser modificados somente quando o UPSest desligado (posio OFF). (2). O desvio desativado quando o conversor de freqncia estiver desativado.

86-86710-00PT A02 - Page 22

5. Manuteno
5.1 Soluo de problemas
Se o LED (21) ou (22) estiverem ativados, uma falha ou alarme ocorreram. Use o boto escape (24) para parar o alarme de udio.

Indicao O UPS no inicia, o LCD indica: COLD START NOK CHECK AC WIRING

Diagnstico

Correo

A fonte de alimentao CA no w Verifique a disponibilidade da est conectada ou est conectada alimentao CA. sada do UPS. w Verifique se o UPS est corretamente conectado fonte de alimentao CA. LED (22) est ligado, o LED SWF Inverso da fase na fonte de Verifique a polaridade e o sistema de (11) na parte traseira do UPS alimentao CA. O UPS no inicia. aterramento. est ativado. O LCD indica: SITE WIR. FAULT CHECK AC WIRING LED (22) est ativado, o LCD indica: NO BATTERY CHECK CONNECTION LED (22) est ativado, o LCD indica: BATTERY FAULT SERV REQUIRED LED (21) est ativado, o LCD indica: OVERLOAD ALARM REDUCE LOAD LED (22) est ativado, o LCD indica: LOAD UNPROTECTED OUTPUT OVERLOAD A bateria est incorretamente conectada. Foi detectada uma falha na bateria. Verifique as conexes da bateria (consulte a Seo 5.2, substituio do mdulo da bateria). Substitua a bateria (consulte a Seo 5.2, substituio do mdulo da bateria). Ligue para o departamento de suporte ps-venda. Reduza a carga.

O nvel da carga excede o nvel de sobrecarga programado ou a capacidade do UPS. A UPS est sobrecarregada. Os dispositivos conectados UPS so alimentados diretamente pela rede eltrica por meio do desvio.

Confira a carga total puxada pelos dispositivos conectados e desconecte quaisquer dispositivos no prioritrios. Confira a carga total puxada pelos dispositivos conectados e desconecte quaisquer dispositivos no prioritrios. Desligue e reinicie a UPS para retornar operao normal. Confira a carga total puxada pelos dispositivos conectados e desconecte quaisquer dispositivos no prioritrios. Retire a carga e ento reinicie a UPS.

LED (22) est ativado, o LCD Aps sobrecargas repetitivas, indica: REDUCE LOAD RESTART a UPS est travada na posio UPS Bypass (desvio). Os dispositivos conectados UPS so alimentados diretamente pela rede eltrica. LED (22) est ativado, o LCD A UPS desliga automaticamente indica: OVERLOAD FAULT devido sobrecarga na sada da REDUCE LOAD UPS. LED (22) est ativado, o LCD indica: LOAD SHORT-CIRCU CHECK WIRING LED (22) est ativado, o LCD indica: INTERNAL FAULT SERV REQUIRED A UPS desliga automaticamente devido ao curto-circuito na sada da UPS. Ocorreu uma falha interna na UPS. H duas situaes possveis: w a carga ainda est sendo fornecida, mas diretamente com a energia CA via desvio, w a carga no est mais sendo fornecida. A mudana para Remote Power Off (RPO) levou ao desligamento da UPS.

Ligue para o departamento de suporte de ps-venda.

10

11

O LCD indica: REMOTE POWER OFF RPO

Retorne o contato posio normal e pressione o boto ON/OFF para reiniciar.

86-86710-00PT A02 - Page 23

5. Manuteno
Resoluo de problemas de um UPS equipado com mdulo HotSwap MBP
Indicao A carga no est mais sendo fornecida quando a chave giratria (53) no mdulo HotSwap MBP estiver ajustada para a posio de desvio (Bypass). A carga no est mais sendo fornecida quando a chave giratria (53) no mdulo HotSwap MBP estiver ajustada para a posio Normal.

Diagnstico

Correo

12

Verifique o cabeamento entre o UPS w Os dispositivos protegidos so e o mdulo HotSwap MBP (consulte conectados sada do UPS no a Seo 2.6). lugar do mdulo HotSwap MBP. w A fonte de alimentao CA est conectada sada do UPS no lugar do mdulo HotSwap MBP. w O UPS est desligado. w O cabeamento entre o UPS e o mdulo HotSwap MBP no est correto. w Iniciar o UPS. w Verifique o cabeamento entre o UPS e o mdulo HotSwap MBP (consulte a Seo 2.6). w Ajuste a chave giratria (53) no mdulo HotSwap MBP para a posio Normal. w Verifique o cabeamento entre o UPS e o mdulo HotSwap MBP (consulte a Seo 2.6). w Ups est desligado

13

14

A carga no ser mais fornecida w A chave giratria (53) no mdulo se a alimentao CA falhar. HotSwap MBP est ajustada para a posio de desvio (Bypass). w O cabeamento entre o UPS e o mdulo HotSwap MBP no est correto.

Se uma falha levar ao desligamento do UPS, pressione o boto ON/OFF (27) para eliminar a falha.

5.2

Substituio do mdulo da bateria


Recomendaes de segurana
A manuteno das baterias deve ser realizada ou supervisionada por pessoal com conhecimento sobre baterias e tomando-se as precaues necessrias. Risco de exploso se a bateria for substituda por uma de tipo incorreto. Ao substituir as baterias, substitua por uma do mesmo tipo e nmero de baterias ou conjuntos de baterias. PRECAUO: PRECAUO: PRECAUO: No descarte as baterias no fogo. As baterias podem explodir. Descarte as baterias usadas de acordo com as instrues. No abra nem destrua as baterias. Os eletrolitos liberados so prejudiciais pele e aos olhos. Eles podem ser txicos. Uma bateria pode apresentar risco de choque eltrico e correntes de curto-circuito altas. As precaues a seguir devem ser observadas ao trabalhar com baterias:

a. Retire relgios, anis ou outros objetos metlicos. b. Use ferramentas com os cabos isolados. c. Use luvas e botas de borracha. d. No deixe ferramentas ou peas de metal sobre baterias. e. Desconecte a fonte de alimentao de carga antes de conectar ou desconectar os terminais da bateria. f. Determine se a bateria est inadvertidamente aterrada. Se estiver inadvertidamente aterrada, remova o aterramento. O contato com qualquer pea de uma bateria aterrada pode resultar em choque eltrico. A probabilidade de choque eltrico pode ser reduzida se tais aterramentos forem removidos durante a instalao e a manuteno (aplicveis ao equipamento e s fontes de bateria remotas que no tenham um circuito de alimentao aterrado).

86-86710-00PT A02 - Page 24

5. Manuteno
Retirada do mdulo da bateria
A. Desparafuse o lado esquerdo do painel dianteiro (dois parafusos) e ento remova a pea.

B. Desconecte o bloco da bateria, separando os dois conectores (nunca puxe pelos fios).

C. Desparafuse a abraadeira de metal e remova a pea.

D. Retire as baterias.

Montagem do novo mdulo da bateria


Siga as instrues acima na ordem inversa. w w Para garantir segurana e alto desempenho, use somente baterias fornecidas pela EATON. Cuide de pressionar firmemente as duas partes do conector entre si durante a remontagem.

86-86710-00PT A02 - Page 25

5. Manuteno
5.3 Manuteno de um UPS equipado com mdulo HotSwap MBP

O mdulo HotSwap MBP torna possvel a manuteno ou at mesmo a substituio do UPS, sem afetar as cargas conectadas (funo HotSwap). Manuteno: 1. Coloque a chave (53) na posio Bypass (desvio). O LED vermelho (52) no mdulo HotSwap MBP ativado, indicando que a carga est sendo fornecida diretamente com a alimentao CA. 2. Pare o UPS pressionando do boto ON/OFF (27) no painel de controle do UPS. LED (51) UPS ON - OK a chave desligada, o UPS agora pode ser desconectado e substitudo. Retornar operao normal: 1. Verifique se o UPS est corretamente conectado ao mdulo HotSwap MBP. 2. Inicie o UPS pressionando do boto ON/ OFF (27) no painel de controle do UPS. LED (51) UPS ON - OK a chave no mdulo HotSwap MBP vai para a posio ON (ligada) (do contrrio, h um erro entre o mdulo HotSwap MBP e o UPS). 3. Coloque a chave (53) na posio Normal. O LED vermelho (52) no mdulo HotSwap MBP vai para a posio OFF(desligada).

86-86710-00PT A02 - Page 26

6. Apndices
6.1 Especificaes tcnicas


EX 2200 Energia de sada Rede de alimentao eltrica w Voltagem de entrada nominal w Faixa de voltagem de entrada w Freqncia w Fator de potncia w Corrente de vazamento Sada da carga w Voltagem w Freqncia w Distoro harmnica w Capacidade de sobrecarga w Corrente 17,5 A
(7)

EX 3000 3000 VA (2) / 2550 W (3) Monofsico 120 V 55 / 72 / 100 a 142 V


(4)

EX 3000 XL 3000 VA (2) / 2150 W

EX EXB

(9)

2100 VA (1) / 1650 W

50/60 Hz (seleo automtica) > 0,95 < 2 mA Monofsico 120 V 3% (5) 50/60 Hz 0,5% (6) < 4 % para carga linear, < 6 % para carga no linear 102 % contnuo, 105 % 20s, > 130% 1,5s 25 A 6 x 12V - 9 Ah, cido e chumbo lacrados, sem necessidade de manuteno
(8)

Bateria

6 x 12V - 7 Ah, cido e chumbo lacrados, sem necessidade de manuteno

sem bateria interna

6 x 12 V - fileiras 9 Ah, cido e chumbo lacrados, sem necessidade de manuteno

Ambiente w Limite de temperatura operacional w Umidade relativa w Limite de temperatura de armazenagem w Altitude w Nvel de rudo

0C a 40C (32F a 104F ) 20% a 90% (sem condensao) -20C a 40C (-4F a 104F) 1000 m < 47 dBA

(1) (2) (3) (4) (5) (6) (7)

(8) (9)

Dependendo da voltagem de sada selecionada: 100V / 104V / 110V / 120V / 127V, a energia de sada 1890VA / 1890VA / 2100VA / 2100VA / 2100VA. Dependendo da voltagem de sada selecionada: 100V / 104V / 110V / 120V / 127V, a energia de sada 2500VA / 2500VA / 2500VA / 3000VA / 3000VA. Energia de sada padro 2550 W, 2400 W com um mdulo EXB. Valores para 33% / 66% / 100% da sada do UPS. Programvel: 100V / 104V / 110V / 120V / 127V usando o software de configurao do UPS. O modo do conversor de freqncia programvel usando o software de configurao do UPS. Dependendo da voltagem de sada selecionada: 100V / 104V / 110V / 120V / 127V, a corrente de sada mxima 18,9VA / 18,2A / 19,1A / 17,5A 16,5A. Dependendo da voltagem de sada selecionada: 100V / 104V / 110V / 120V / 127V, a corrente de sada 25A / 24A / 22,7A / 25A / 23,6A. EXB est somente no modelo 3U. UPS padropode ser conectado com at 4 EXB.
86-86710-00PT A02 - Page 27

6. Apndices
6.2
1. Para abrir a janela de configurao, clique com o boto esquerdo em Menu Iniciar/ Programas/ EATON / Personal Solution Pac / Configuraes, ou clique no plugue de energia da PSP localizado na bandeja SYS. 2. Clique no smbolo + prximo s Configuraes do UPS para expandir a seo Configuraes do UPS.

Programando as tomadas programveis

3. Clique no Timer de Inicializao e mude o Grupo de sada reinicia aps para 0 para ter a tomada de compartilhamento de energia fornecendo energia ao mesmo tempo das tomadas da rede eltrica.

86-86710-00PT A02 - Page 28

6. Apndices
4. Repita a etapa 3 para cada tomada programvel. 5. Aps fazer as mudanas, clique no boto Aplicar. A seo intitulada Timer de desligamento permite que o usurio defina por quanto tempo a tomada de compartilhamento de energia fornece energia aps uma perda de energia. Para configurar o compartilhamento de energia para desligar ao mesmo tempo da tomada da rede eltrica: 6. Ajuste o Grupo de tomada ser desligado aps para 65535.

86-86710-00PT A02 - Page 29

(Esta pgina foi deixada intencionalmente em branco)

86-86710-00PT A02 - Page 30

6. Apndices
6.3 Glossrio
Desvio da alimentao CA Tempo de reserva Teste de bateria Equipamentos Descarga excessiva FlexPDU Linha de desvio da fonte de alimentao CA, controlada pelo UPS, usada para fornecer diretamente a energia se ocorrer uma sobrecarga ou falha no UPS. Tempo durante o qual a energia pode ser fornecida pelo UPS, operando a partir da bateria. Teste interno do UPS para verificar o status da bateria. Dispositivos conectados sada do UPS. A descarga da bateria ultrapassou o limite permissvel, provocando dano irreversvel bateria. Mdulos com tomadas do UPS para instalao em um compartimento. H mdulos diferentes com tipos diferentes de tomadas.

Conversor de freqncia Modo de operao usado para converter a freqncia da energia CA entre a entrada e a sada do UPS (50 Hz -> 60 Hz ou 60 Hz -> 50 Hz). HotSwap MBP Aviso de bateria fraca Mdulo de desvio manual do UPS para manuteno. H mdulos diferentes com tipos diferentes de tomadas. um indicador de nvel baixo da voltagem da bateria, indicando que a carga da bateria est baixa e que o usurio deve agir rapidamente devido a risco iminente de interrupo de energia da carga da bateria. Visor de cristal lquido.

LCD

Alimentao CA Normal A fonte de alimentao CA que alimenta o UPS sob condies normais. Porcentagem da carga Personalizao Proporo da energia efetivamente puxada pela carga na sada mxima do UPS. possvel modificar certos parmetros do UPS vindos de fbrica. Certas funes do UPS tambm podem ser modificadas pelo software Personal Solution-Pac para melhor se adaptar s necessidades dos usurios. Essas tomadas podem ser automaticamente fechadas durante a operao com bateria (atrasos na hora do desligamento podem ser programados com o software Personal Solution Pac). O UPS tem dois conjuntos de duas e de uma tomada programvel. Os dispositivos conectados ao UPS podem ser iniciados mesmo se a energia da fonte de alimentao CA no estiver disponvel. O UPS funciona apenas com a energia suprida pela bateria. Sistema de alimentao ininterrupta. Esta funo ativa ou desativa a inicializao das seqncias de controle LIGAR/ DESLIGAR da UPS ON/OFF pelo computador software de gerenciamento de energia.

Tomadas programveis

Iniciar com bateria

UPS LIGAR/DESLIGAR da UPS controlado pelo software

86-86710-00PT A02 - Page 31

Notas:

86-86710-00PT A02 - Page 32

www.eaton.com