DATA U4

2009 CITY MULTI ENGINEERING MANUAL


OUTDOOR UNITS
GENERAL LINE-UP......................................................................................................................................................... OD-1
Y-SERIES.............................................................................................................................................................................Y-1
R2-SERIES....................................................................................................................................................................... R2-1
S-SERIES............................................................................................................................................................................ S-1

INDOOR UNITS
GENERAL LINE-UP........................................................................................................................................................... ID-1
Ceiling-concealed (Low-profile Option/Alternate High-static Option)........ PEFY-P-NMSU-E/PEFY-P-NMHU-E....................PEFY-1
Ceiling-concealed (Ducted).............................................................. PDFY-P-NMU-E...................................................PDFY-1
Ceiling-recessed Cassette (1-way airflow)....................................... PMFY-P-NBMU-E............................................... PMFY-1
Ceiling-recessed Cassette (4-way airflow)....................................... PLFY-P-NCMU-E/NBMU-E.................................. PLFY-1
Ceiling-suspended............................................................................ PCFY-P-NGMU-E................................................PCFY-1
Wall-mounted................................................................................... PKFY-P-NAMU-E, NGMU-E, NFMU-E................PKFY-1
Floor-standing (Exposed/Concealed)............................................... PFFY-P-NEMU-E/PFFY-P-NRMU-E.................... PFFY-1
Vertical-concealed............................................................................ PVFY-P-E00A......................................................PVFY-1
Nominal Capacity Tables (Cooling/Heating)..................................... ALL INDOOR UNITS.............................................NCT-1
BC Controller (with R2-Series PURY and WR2-Series PQRY)........ CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB........BC-1
LOSSNAY......................................................................................... LGH-F-RX3-E........................................................ERV-1

CONTROLS
MITSUBISHI ELECTRICs Air-conditioner Network System (MELANS)......................................................................CNTR-1
Local remote controller.................................................................................................................................................CNTR-4
System controller..........................................................................................................................................................CNTR-9
System component.....................................................................................................................................................CNTR-75

SYSTEM DESIGN
Y-Series System Design................................................................................................................................................. YSD-1
R2-Series System Design............................................................................................................................................ R2SD-1
S-Series System Design................................................................................................................................................ SSD-1

GENERAL LINE-UP (Feb. 2009)

DATA U4

GENERAL LINE-UP......................................................................................................................................................... OD-1


Y-Series (PUHY-P-T[S]HMU [-BS] [208 / 230V], PUHY-P-Y[S]HMU [-BS] [460V])........................................................ OD-2
R2-Series (PUHY-P-T[S]HMU [-BS] [208 / 230V], PUHY-P-Y[S]HMU [-BS] [460V])..................................................... OD-3
S-Series (PUMY-P-NHMU)............................................................................................................................................ OD-3

GENERAL LINE-UP (Feb. 2009)

OD-1

GENERAL LINE-UP

CITY MULTI INVERTER OUTDOOR UNITS


GENERAL LINE-UP

GENERAL LINE-UP

DATA U4

GENERAL LINE-UP

Line-up of R410A CITY MULTIoOutdoor Units


Heat Pump Y Series - 208-230V (PUHY-T[S]HMU-A [-BS])
- 460V (PUHY-Y[S]HMU-A [-BS])

208-230V
460V

208-230V
460V

208-230V
460V

208-230V
460V

208-230V
460V

208-230V
460V

Twinning Kit CMY-Y300VBK2


for PUHY-P264~360T/YSHMU (-BS)

Twinning Kit CMY-Y100VBK2


for PUHY-P144~240T/YSHMU (-BS)

Field piping

Field piping
Twinning kit

Twinning kit

Field piping

Field piping

The
le
twinn ngth of
th
be 5 ing kit to e field p
00 m
ip
th
m (1 e indoo ing from
9 in.)
r
th
or lo units mu e
nger
st

OD-2

GENERAL LINE-UP (Feb. 2009)

The
le
Twinning kit
units ngth of
th
mus
t be e field p
Field piping
500
iping
mm
(19 in from the
twinn
.) or
long
ing k
er.
it to
the in
door

GENERAL LINE-UP

DATA U4

Line-up of R410A CITY MULTIoOutdoor Units

Line-up of R410A CITY MULTIoOutdoor Units

GENERAL LINE-UP

Heat Recovery R2 Series - 208-230V (PURY-P-T[S]HMU-A [-BS]) Heat Pump S Series (PUMY-P-NHMU [-BS])
- 460V (PURY-P-Y[S]HMU-A [-BS])

208-230V
460V

208-230V
460V

208-230V
460V

Twinning Kit CMY-R100VBK


for PURY-P144~240T/YSHMU-A (-BS)
A

Twinning pipe (low-pressure side)

Twinning pipe (high-pressure side)

Field-supplied piping (low-pressure connecting pipe: between outdoor units)

Field-supplied piping (low-pressure main pipe: to BC controller)

Field-supplied piping (high-pressure main pipe: to BC controller)

The length of the field piping from the twinning kit to the indoor units/
BC Controller must be 500 mm [19 in.] or longer.
See Twinning Kit Installation Manual for details.
F

E
F

GENERAL LINE-UP (Feb. 2009)

OD-3

Y-SERIES

DATA U4

OUTDOOR UNITS


1. SPECIFICATIONS..........................................................................................................................................................Y-2
1-1. PUHY-P72~360T(S)HMU-A (-BS) 208 / 230V Specifications..........................................................................Y-2
1-2. PUHY-P72~360Y(S)HMU-A (-BS) 460V Specifications.................................................................................Y-14
1-3. Energy Efficiencies........................................................................................................................................Y-26
2. EXTERNAL DIMENSIONS...........................................................................................................................................Y-27
3. Center of Gravity................................................................................................................................................Y-47

5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS...........................................................................Y-51


OUTDOOR
UNITS
6 SOUND Pressure LEVELS.....................................................................................................................................Y-52

7. Capacity Tables......................................................................................................................................................Y-55
GENERAL
LINE-UP............................................................................................................................................................
G-1
7-1. Correction
by Temperature.............................................................................................................................Y-55
7-2.
Correction
by
Total
Indoor..............................................................................................................................Y-60
H2i Y-SERIES (PUHY-HP)................................................................................................................................................ H2i-1
7-3. Correction by Refrigerant Piping Length........................................................................................................Y-68
Optional parts for PUHY-HP..................................................................................................................................Op-1
7-4. Correction at Frost and Defrost......................................................................................................................Y-71

7-5. Operation Temperature Range.......................................................................................................................Y-72


8. OPTIONAL PARTS.......................................................................................................................................................Y-73
8-1. Branch Joint...................................................................................................................................................Y-73
8-2. Headers.........................................................................................................................................................Y-74
8-3. Twinning Kit....................................................................................................................................................Y-75

Y-SERIES (Feb. 2009)

Y-1

Y-SERIES

4. ELECTRICAL WIRING DIAGRAMS.............................................................................................................................Y-48

1. SPECIFICATIONS
1-1. PUHY-P72~360T(S)HMU-A Specifications
Model
Power source
Cooling capacity (Nominal) *1
Power input
Current input
(208 / 230)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(208
/ 230V)

Temp. range of
cooling

Heating capacity (Nominal) *2

Fan

Compressor

W.B.
D.B.
BTU / h
kW
kW

25.9 / 23.4 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
108,000
31.7
8.63 *3

17.5 / 15.8 *3

26.6 / 24.0 *3

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 15

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 20
58.0

Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Control, Driving
mechanism
Motor output
kW
External static pressure
*4
Type x Quantity
Manufacturer
Operating Range
Starting method
Motor output
kW
Case heater
kW
Lubricant

3/4"(19.05) Brazed
Propeller fan x 1
7,050
200
3,330

3/8"(9.52) Brazed (1/2"(12.7) Brazed,total length


>= 295' [90m])
7/8"(22.2) Brazed
Propeller fan x 1
7,050
200
3,330

Inverter-control, Direct-driven by motor

Inverter-control, Direct-driven by motor

in.
mm

Compressor / Fan
Inverter
Type x original charge
Control
lbs (kg)

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory
Optional parts

Remark

Outdoor:

16.2 / 14.6 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
80,000
23.4
5.68 *3

58.0

High pressure protection

Note:

Indoor:

96,000
28.1
8.42 *3

3/8"(9.52) Brazed

External dimension H x W x D

Refrigerant

72,000
21.1
5.27 *3

External finish

Protection devices

PUHY-P96THMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz

in. (mm)

Liquid pipe

Refrigerant piping
diameter

PUHY-P72THMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
BTU / h
kW
kW

Power input
Current input
A
(208 / 230)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)

0.92

0.92

0 in.WG (0 Pa) *4

0 in.WG (0 Pa) *4

Inverter scroll hermetic compressor x 1


Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
18-100%
13-100%
Inverter
Inverter
5.1
6.8
0.051(230 V)
0.051(230 V)
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5
coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
Over-heat protection,Over-current protection
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
LEV and HIC circuit
LEV and HIC circuit
441(200)
441(200)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
KB94L642
KB94L642
WKE94C207X01
Installation Manual
Installation Manual
Refrigerant conn. pipe
Refrigerant conn. pipe
Joint: CMY-Y102S/L-G2
Joint: CMY-Y102S/L-G2
Header: CMY-Y104/108/1010-G
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design
section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

PUHY-P72THMU: MCA = 23 / 21A; Max. Fuse Size: 30 / 30A.


PUHY-P96THMU: MCA = 35 / 32A; Max. Fuse Size: 40 / 40A.

Y-2

DATA U4

Y-SERIES (Feb. 2009)

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

1. SPECIFICATIONS

DATA U4

Model

PUHY-P120THMU-A(-BS)

Power source

3-phase 3-wire 208 / 230V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(208 / 230)
Indoor
Outdoor

Heating capacity (Nominal) *2

BTU / h
kW
kW
A

Remark

Outdoor:

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
120,000
35.2
9.26 *3

Y-SERIES
(208
/ 230V)
Y-SERIES

Optional parts

Note:

31.1 / 28.1 *3

W.B.
D.B.
BTU / h
kW
kW

Power input
Current input
A
(208 / 230)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Liquid pipe
in. (mm)
Refrigerant piping
diameter
Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Fan
Control, Driving
mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Compressor
Starting method
Motor output
kW
Case heater
kW
Lubricant
External finish
in.
External dimension H x W x D
mm
High pressure protection
Protection devices
Compressor / Fan
Inverter
Type x original charge
Refrigerant
Control
Net weight
lbs (kg)
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory

Indoor:

120,000
35.2
10.11 *3

28.5 / 25.8 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 26
60.0
3/8"(9.52) Brazed (1/2"(12.7) Brazed,total length >= >= 131' [40m])
7/8"(22.2) Brazed
Propeller fan x 1
7,950
225
3,750
Inverter-control, Direct-driven by motor
0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
18-100%
Inverter
8.8
0.057(230 V)
MEL32
Pre-coated galvanized steel sheet (+powder coating for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
R410A x 25 lbs + 6 oz (11.5kg)
LEV and HIC circuit
541(245)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Auto-defrost mode (Reversed refrigerant cycle)
KB94L643
WKE94C208X01
Installation Manual
Refrigerant conn. Pipe
Joint: CMY-Y102S/L-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design
section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

*1 Nominal cooling conditions


80degF D.B./ 67degF W.B.
(26.7degC D.B./ 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

Unit converter
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.

Y-SERIES (Feb. 2009)

Y-3

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1
Power input
Current input (208 / 230)
Indoor
Outdoor

Temp. range of
cooling

Y-SERIES
(208
/ 230V)
Y-SERIES

Heating capacity (Nominal) *2


Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter from Liquid pipe
Twinning Kit to Indoor Units
Gas pipe
Set Model
Model
Type x Quantity

PUHY-P144TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
144,000
42.2
10.87 *3
33.5 / 30.3 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
160,000
46.9
11.69 *3
36.0 / 32.6 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 31
61.0
1/2"(12.7) Brazed
1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

dB <A>
in. (mm)
in. (mm)

PUHY-P72THMU-A(-BS)
PUHY-P72THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,050
Airflow rate
m3 / min
200
200
Fan
L/s
3,330
3,330
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP. AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
5.1
5.1
Case heater
kW
0.051(230 V)
0.051(230 V)
Lubricant
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
441(200)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed
3/8"(9.52)Brazed
Liquid pipe
in. (mm)
Refrigerant piping diameter
from Module to Twinning Kit
Gas pipe
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L644
Drawing
Wiring
WKE94C207X01
WKE94C207X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant
flows of the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch,
and other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
Remark
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa,
60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series
System Design section, p. 293.
Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-4

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Y-SERIES
Y-SERIES
(208
/ 230V)

Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

PUHY-P168TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
168,000
49.2
14.11 *3
43.5 / 39.3 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
188,000
55.1
14.73 *3
45.4 / 41.0 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
8-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 36
61.0
5/8"(15.88) Brazed

Set Model
Model

PUHY-P72THMU-A(-BS)
PUHY-P96THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,050
Airflow rate
m3 / min
200
200
Fan
L/s
3,330
3,330
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
5.1
6.8
Case heater
kW
0.051(230 V)
0.051(230 V)
Lubricant
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
441(200)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
in. (mm)
3/8"(9.52)Brazed
3/8"(9.52)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L644
Drawing
Wiring
WKE94C207X01
WKE94C207X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Remark
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.
Type x Quantity

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-5

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(208
/ 230V)

Heating capacity (Nominal) *2


Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

dB <A>
in. (mm)

PUHY-P192TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
192,000
56.3
15.84 *3
48.8 / 44.1 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
200,000
58.6
15.38 *3
47.4 / 42.8 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
6-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 41
62.5
5/8"(15.88) Brazed

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

PUHY-P72THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,950
Airflow rate
m3 / min
200
225
Fan
L/s
3,330
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
5.1
8.8
Case heater
kW
0.051(230 V)
0.057(230 V)
Lubricant
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
in. (mm)
3/8"(9.52)Brazed
1/2"(12.7)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L645
Drawing
Wiring
WKE94C207X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-6

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Y-SERIES
Y-SERIES
(208
/ 230V)

Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

PUHY-P216TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
216,000
63.3
19.09 *3
58.8 / 53.2 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
228,000
66.8
18.42 *3
56.8 / 51.3 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
6-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 46
62.5
5/8"(15.88) Brazed

PUHY-P96THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,950
Airflow rate
m3 / min
200
225
Fan
L/s
3,330
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
6.8
8.8
Case heater
kW
0.051(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed
1/2"(12.7)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L645
Drawing
Wiring
WKE94C207X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-7

1. SPECIFICATIONS

DATA U4

Model
Power source

Power input

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW

Current input (208 / 230)

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(208
/ 230V)

Heating capacity (Nominal) *2

Indoor
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

Temp. range of
heating

PUHY-P240TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
240,000
70.3
20.82 *3
64.2 / 58.0 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
240,000
70.3
19.07 *3
58.8 / 53.1 *3

D.B.
W.B.

dB <A>
in. (mm)

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
8-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50
63.0
5/8"(15.88) Brazed

in. (mm)

1-1/8"(28.58) Brazed

PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,950
7,950
Airflow rate
m3 / min
225
225
Fan
L/s
3,750
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
8.8
8.8
Case heater
kW
0.057(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
541(245)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
1/2"(12.7)Brazed
1/2"(12.7)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L648
Drawing
Wiring
WKE94C208X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-8

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P264TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz

Cooling capacity (Nominal) *1

BTU / h

264,000

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications also apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-9

Y-SERIES
Y-SERIES
(208
/ 230V)

kW
77.4
Power input
kW
21.28 *3
Current input (208 / 230) A
65.6 / 59.3 *3
Indoor
W.B.
59 to 75degF(15 to 24degC)
Temp. range of
cooling
Outdoor
D.B.
23 to 109degF(-5 to 43degC)
BTU / h
280,000
Heating capacity (Nominal) *2
kW
82.1
Power input
kW
21.23 *3
Current input (208 / 230) A
65.4 / 59.2 *3
Indoor
D.B.
59 to 81degF(15 to 27degC)
Temp. range of
heating
Outdoor
W.B.
-4 to 60degF(-20 to 15.5degC)
System Compressor Operating Range
5-100%
Total capacity
50 to 130 % of outdoor unit capacity
Indoor unit
connectable
Model / Quantity
P06 to P96 / 2 to 50
Sound pressure level (measured in
dB <A>
63.5
anechoic room)
Refrigerant piping Liquid pipe
in. (mm)
3/4"(19.05) Brazed
diameter from
Twinning Kit to
Gas pipe
in. (mm)
1-3/8"(34.93) Brazed
Indoor Units
Set Model
Model
PUHY-P72THMU-A(-BS)
PUHY-P72THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,050
7,950
3
Airflow rate
m / min
200
200
225
Fan
L/s
3,330
3,330
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC AC&R Works, MITSUBISHI ELECTRIC
AC&R Works, MITSUBISHI ELECTRIC
Manufacturer
CORPORATION
CORPORATION
CORPORATION
Starting
method
Inverter
Inverter
Inverter
Compressor
Motor output
kW
5.1
5.1
8.8
Case heater
kW
0.051(230 V)
0.051(230 V)
0.057(230 V)
Lubricant
MEL32
MEL32
MEL32
Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
External finish
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Over-heat protection / Thermal
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
switch
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
441(200)
541(245)
Salt-resistant cross fin & copper
Heat exchanger
Salt-resistant
cross
fin
&
copper
tube
Salt-resistant
cross
fin & copper tube
tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
Liquid pipe
in. (mm)
3/8"(9.52)Brazed
3/8"(9.52)Brazed
1/2"(12.7)Brazed
piping diameter
from Module to
Gas pipe
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L651
Drawing
Wiring
WKE94C207X01
WKE94C207X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall
be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P288TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz

Y-SERIES
Y-SERIES
(208
/ 230V)

Cooling capacity (Nominal) *1

BTU / h

288,000

kW
84.4
Power input
kW
24.52 *3
Current input (208 / 230) A
75.6 / 68.3 *3
Indoor
W.B.
59 to 75degF(15 to 24degC)
Temp. range of
cooling
Outdoor
D.B.
23 to 109degF(-5 to 43degC)
BTU / h
308,000
Heating capacity (Nominal) *2
kW
90.3
Power input
kW
24.27 *3
Current input (208 / 230) A
74.8 / 67.6 *3
Indoor
D.B.
59 to 81degF(15 to 27degC)
Temp. range of
heating
Outdoor
W.B.
-4 to 60degF(-20 to 15.5degC)
System Compressor Operating Range
5-100%
Total capacity
50 to 130 % of outdoor unit capacity
Indoor unit
connectable
Model / Quantity
P06 to P96 / 2 to 50
Sound pressure level (measured in
dB
<A>
63.5
anechoic room)
Refrigerant piping Liquid pipe
in. (mm)
3/4"(19.05) Brazed
diameter from
Twinning Kit to
Gas pipe
in. (mm)
1-3/8"(34.93) Brazed
Indoor Units
Set Model
Model
PUHY-P72THMU-A(-BS)
PUHY-P96THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,050
7,950
Airflow rate
m3 / min
200
200
225
Fan
L/s
3,330
3,330
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Compressor
Motor output
kW
5.1
6.8
8.8
Case heater
kW
0.051(230 V)
0.051(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
441(200)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
3/8"(9.52)Brazed
3/8"(9.52)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L651
Drawing
Wiring
WKE94C207X01
WKE94C207X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-10

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P312TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz

Cooling capacity (Nominal) *1

BTU / h

312,000

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
541(245)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
3/8"(9.52)Brazed
1/2"(12.7)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L652
Drawing
Wiring
WKE94C207X01
WKE94C208X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-11

Y-SERIES
Y-SERIES
(208
/ 230V)

kW
91.4
Power input
kW
26.25 *3
Current input (208 / 230) A
80.9 / 73.2 *3
Indoor
W.B.
59 to 75degF(15 to 24degC)
Temp. range of
cooling
Outdoor
D.B.
23 to 109degF(-5 to 43degC)
BTU / h
320,000
Heating capacity (Nominal) *2
kW
93.8
Power input
kW
24.92 *3
Current input (208 / 230) A
76.8 / 69.5 *3
Indoor
D.B.
59 to 81degF(15 to 27degC)
Temp. range of
heating
Outdoor
W.B.
-4 to 60degF(-20 to 15.5degC)
System Compressor Operating Range
4-100%
Total capacity
50 to 130 % of outdoor unit capacity
Indoor unit
connectable
Model / Quantity
P06 to P96 / 2 to 50
Sound pressure level (measured in
dB <A>
64.5
anechoic room)
Refrigerant piping Liquid pipe
in. (mm)
3/4"(19.05) Brazed
diameter from
Twinning Kit to
Gas pipe
in. (mm)
1-3/8"(34.93) Brazed
Indoor Units
Set Model
Model
PUHY-P72THMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,950
7,950
3
Airflow rate
m / min
200
225
225
Fan
L/s
3,330
3,750
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Compressor
Motor output
kW
5.1
8.8
8.8
Case heater
kW
0.051(230 V)
0.057(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P336TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz

Y-SERIES
(208
/ 230V)
Y-SERIES

Cooling capacity (Nominal) *1

BTU / h

kW
Power input
kW
Current input (208 / 230) A
Indoor
W.B.
Temp. range of
cooling
Outdoor
D.B.
BTU / h
Heating capacity (Nominal) *2
kW
Power input
kW
Current input (208 / 230) A
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Refrigerant piping Liquid pipe
in. (mm)
diameter from
Twinning Kit to
Gas pipe
in. (mm)
Indoor Units
Set Model
Model
Type x Quantity
cfm
Airflow rate
m3 / min
L/s
Fan
Control , Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Compressor

Starting method
Motor output
Case heater
Lubricant

kW
kW

336,000
98.5
29.50 *3
90.9 / 82.2 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
348,000
102.0
27.96 *3
86.2 / 77.9 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
4-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50
64.5
3/4"(19.05) Brazed
1-5/8"(41.28) Brazed

PUHY-P96THMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
7,050
7,950
7,950
200
225
225
3,330
3,750
3,750
Inverter-control, Direct-driven by
Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
motor
0.92
0.92
0.92
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Inverter
Inverter
Inverter
6.8
8.8
8.8
0.051(230 V)
0.057(230 V)
0.057(230 V)
MEL32
MEL32
MEL32

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
441(200)
541(245)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
3/8"(9.52)Brazed
1/2"(12.7)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L652
Drawing
Wiring
WKE94C207X01
WKE94C208X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-12

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P360TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz

Cooling capacity (Nominal) *1

BTU / h

360,000

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
541(245)
541(245)
541(245)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
1/2"(12.7)Brazed
1/2"(12.7)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L653
Drawing
Wiring
WKE94C208X01
WKE94C208X01
WKE94C208X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
External finish

Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72THMU: MCA = 23 / 21A, Max. Fuse Size: 30 / 30A; PUHY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PUHY-P120THMU: MCA = 41 / 38A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-13

Y-SERIES
Y-SERIES
(208
/ 230V)

kW
105.5
Power input
kW
31.23 *3
Current input (208 / 230) A
96.3 / 87.1 *3
Indoor
W.B.
59 to 75degF(15 to 24degC)
Temp. range of
cooling
Outdoor
D.B.
23 to 109degF(-5 to 43degC)
BTU / h
360,000
Heating capacity (Nominal) *2
kW
105.5
Power input
kW
28.61 *3
Current input (208 / 230) A
88.2 / 79.7 *3
Indoor
D.B.
59 to 81degF(15 to 27degC)
Temp. range of
heating
Outdoor
W.B.
-4 to 60degF(-20 to 15.5degC)
System Compressor Operating Range
6-100%
Total capacity
50 to 130 % of outdoor unit capacity
Indoor unit
connectable
Model / Quantity
P06 to P96 / 2 to 50
Sound pressure level (measured in
dB
<A>
65.0
anechoic room)
Refrigerant piping Liquid pipe
in. (mm)
3/4"(19.05) Brazed
diameter from
Twinning Kit to
Gas pipe
in. (mm)
1-5/8"(41.28) Brazed
Indoor Units
Set Model
Model
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,950
7,950
7,950
Airflow rate
m3 / min
225
225
225
L/s
3,750
3,750
3,750
Fan
Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Control , Driving mechanism
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Compressor
Motor output
kW
8.8
8.8
8.8
Case heater
kW
0.057(230 V)
0.057(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

1. SPECIFICATIONS

DATA U4

1-2. PUHY-P72~360Y(S)HMU-A Specifications


Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(460)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(460V)

Heating capacity (Nominal) *2

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW

Power input
Current input
A
(460)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Refrigerant piping
diameter

Fan

Compressor

Liquid pipe

in. (mm)

Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Control, Driving
mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Starting method
Motor output
kW
Case heater
kW
Lubricant

External finish
External dimension H x W x D

in.
mm

High pressure protection


Protection devices

Refrigerant

Compressor / Fan
Inverter
Type x original charge
Control
lbs (kg)

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory
Optional parts

Outdoor:

PUHY-P96YHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

72,000
21.1
5.27 *3

96,000
28.1
8.42 *3

7.3 *3

11.7 *3

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
80,000
23.4
5.68 *3

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
108,000
31.7
8.63 *3

7.9 *3

12.0 *3

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 15

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 20

58.0

58.0

3/8"(9.52) Brazed
3/4"(19.05) Brazed
Propeller fan x 1
7,050
200
3,330

3/8"(9.52) Brazed (1/2"(12.7) Brazed,total length


>= 295' [90m])
7/8"(22.2) Brazed
Propeller fan x 1
7,050
200
3,330

Inverter-control, Direct-driven by motor

Inverter-control, Direct-driven by motor

0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
18-100%
Inverter
5.1
0.051(230 V)
MEL32
Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
R410A x 19 lbs + 13 oz (9.0kg)
LEV and HIC circuit
474(215)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Auto-defrost mode (Reversed refrigerant cycle)
KB94L654
WKE94C211X01
Installation Manual
Refrigerant conn. pipe
Joint: CMY-Y102S/L-G2
Header: CMY-Y104/108/1010-G

0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
13-100%
Inverter
6.8
0.051(230 V)
MEL32
Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
R410A x 19 lbs + 13 oz (9.0kg)
LEV and HIC circuit
474(215)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Auto-defrost mode (Reversed refrigerant cycle)
KB94L654
WKE94C211X01
Installation Manual
Refrigerant conn. pipe
Joint: CMY-Y102S/L-G2
Header: CMY-Y104/108/1010-G

Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design
section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Remark

Note:

Indoor:

PUHY-P72YHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A.


PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A.

Y-14

Y-SERIES (Feb. 2009)

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

1. SPECIFICATIONS

DATA U4

Model

PUHY-P120YHMU-A(-BS)

Power source

3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(460)
Indoor
Outdoor

Heating capacity (Nominal) *2

BTU / h
kW
kW
A

Remark

Outdoor:

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
120,000
35.2
9.26 *3

Y-SERIES
Y-SERIES
(460V)

Optional parts

Note:

14.0 *3

W.B.
D.B.
BTU / h
kW
kW

Power input
Current input
A
(460)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Liquid pipe
in. (mm)
Refrigerant piping
diameter
Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Fan
Control, Driving
mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Compressor
Starting method
Motor output
kW
Case heater
kW
Lubricant
External finish
in.
External dimension H x W x D
mm
High pressure protection
Protection devices
Compressor / Fan
Inverter
Type x original charge
Refrigerant
Control
Net weight
lbs (kg)
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory

Indoor:

120,000
35.2
10.11 *3

12.9 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 26
60.0
3/8"(9.52) Brazed (1/2"(12.7) Brazed,total length >= 131' [40m])
7/8"(22.2) Brazed
Propeller fan x 1
7,950
225
3,750
Inverter-control, Direct-driven by motor
0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
18-100%
Inverter
8.8
0.057(230 V)
MEL32
Pre-coated galvanized steel sheet (+powder coating for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
R410A x 25 lbs + 6 oz (11.5kg)
LEV and HIC circuit
574(260)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Auto-defrost mode (Reversed refrigerant cycle)
KB94L655
WKE94C211X01
Installation Manual
Refrigerant conn. Pipe
Joint: CMY-Y102S/L-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design
section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design
section, p. 293.

*1 Nominal cooling conditions


80degF D.B./ 67degF W.B.
(26.7degC D.B./ 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

Unit converter
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.

Y-SERIES (Feb. 2009)

Y-15

1. SPECIFICATIONS

DATA U4

Model
Power source
BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Cooling capacity (Nominal) *1


Power input
Current input (460)
Indoor
Outdoor

Temp. range of
cooling

Y-SERIES
Y-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter from Liquid pipe
Twinning Kit to Indoor Units
Gas pipe
Set Model
Model
Type x Quantity

dB <A>
in. (mm)
in. (mm)

cfm
m3 / min
L/s
Control , Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity

Airflow rate
Fan

Manufacturer
Starting method
Motor output
Case heater
Lubricant

Compressor

kW
kW

External finish
in.
mm

External dimension H x W x D
Protection
devices
Refrigerant

High pressure protection


Compressor / Fan
Inverter
Type x original charge
Control

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Refrigerant piping diameter from Liquid pipe
Module to Twinning Kit
Gas pipe
Defrosting method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory
Optional parts

Remark

PUHY-P144YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
144,000
42.2
10.87 *3
15.1 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
160,000
46.9
11.69 *3
16.3 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 31
61.0
1/2"(12.7) Brazed
1-1/8"(28.58) Brazed

lbs (kg)

in. (mm)
in. (mm)

PUHY-P72YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
7,050
7,050
200
200
3,330
3,330
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
0.92
0.92
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
CORPORATION
Inverter
Inverter
5.1
5.1
0.051(230 V)
0.051(230 V)
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5
coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
4.15MPa (601 psi)
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
LEV and HIC circuit
474(215)
474(215)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed
3/8"(9.52)Brazed
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Auto-defrost mode (Reversed refrigerant cycle)
KB94L656
WKE94C211X01
WKE94C211X01
Installation Manual
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant
flows of the modules and is included in the outdoor unit set)
Joint: CMY-Y102S/L-G2,CMY-Y202-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch,
and other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa,
60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series
System Design section, p. 293.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-16

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

cfm
m3 / min
L/s
Control , Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Airflow rate

Fan

Manufacturer
Compressor

Starting method
Motor output
Case heater
Lubricant

kW
kW

External finish
External dimension H x W x D
Protection
devices
Refrigerant

in.
mm

High pressure protection


Compressor / Fan
Inverter
Type x original charge
Control

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
Defrosting method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory
Optional parts

Remark

lbs (kg)

in. (mm)
in. (mm)

Y-SERIES
Y-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

PUHY-P168YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
168,000
49.2
14.11 *3
19.6 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
188,000
55.1
14.73 *3
20.5 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
8-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 36
61.0
5/8"(15.88) Brazed

PUHY-P72YHMU-A(-BS)
PUHY-P96YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
7,050
7,050
200
200
3,330
3,330
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
0.92
0.92
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC
AC&R Works, MITSUBISHI ELECTRIC
CORPORATION
CORPORATION
Inverter
Inverter
5.1
6.8
0.051(230 V)
0.051(230 V)
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5
coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
LEV and HIC circuit
474(215)
474(215)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed
3/8"(9.52)Brazed
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Auto-defrost mode (Reversed refrigerant cycle)
KB94L656
WKE94C211X01
WKE94C211X01
Installation Manual
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Joint: CMY-Y102S/L-G2,CMY-Y202-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-17

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

dB <A>
in. (mm)

PUHY-P192YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
192,000
56.3
15.84 *3
22.0 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
200,000
58.6
15.38 *3
21.4 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
6-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 1 to 41
62.5
5/8"(15.88) Brazed

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

PUHY-P72YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,950
Airflow rate
m3 / min
200
225
Fan
L/s
3,330
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
5.1
8.8
Case heater
kW
0.051(230 V)
0.057(230 V)
Lubricant
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5
coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
474(215)
574(260)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed
1/2"(12.7)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L657
Drawing
Wiring
WKE94C211X01
WKE94C211X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-18

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Y-SERIES
Y-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

PUHY-P216YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
216,000
63.3
19.09 *3
26.6 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
228,000
66.8
18.42 *3
25.6 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
6-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 46
62.5
5/8"(15.88) Brazed

Set Model
Model

PUHY-P96YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
7,050
7,950
cfm
200
225
Airflow rate
m3 / min
3,330
3,750
Fan
L/s
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Control , Driving mechanism
0.92
0.92
Motor output
kW
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
External static pressure *4
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Type x Quantity
AC&R Works, MITSUBISHI ELECTRIC
AC&R Works, MITSUBISHI ELECTRIC
Manufacturer
CORPORATION
CORPORATION
Inverter
Inverter
Starting method
Compressor
6.8
8.8
Motor output
kW
0.051(230 V)
0.057(230 V)
Case heater
kW
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
in.
External dimension H x W x D
1,650 x 920 x 760
1,650 x 1,220 x 760
mm
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Compressor / Fan
devices
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Inverter
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Type x original charge
Refrigerant
LEV and HIC circuit
Control
474(215)
574(260)
Net weight
lbs (kg)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Heat exchanger
Copper pipe, tube-in-tube structure
Copper pipe, tube-in-tube structure
HIC circuit (HIC: Heat Inter-Changer)
3/8"(9.52)Brazed
1/2"(12.7)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
7/8"(22.2)Brazed
7/8"(22.2)Brazed
in. (mm)
Auto-defrost mode (Reversed refrigerant cycle)
Defrosting method
KB94L657
External
WKE94C211X01
WKE94C211X01
Drawing
Wiring
Refrigerant cycle
Installation Manual
Document
Standard attachment
Refrigerant conn. Pipe
Accessory
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Remark
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.
Type x Quantity

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-19

1. SPECIFICATIONS

DATA U4

Model

dB <A>
in. (mm)

PUHY-P240YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
240,000
70.3
20.82 *3
29.0 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
240,000
70.3
19.07 *3
26.5 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
8-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50
63.0
5/8"(15.88) Brazed

in. (mm)

1-1/8"(28.58) Brazed

Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Set Model
Model

PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,950
7,950
Airflow rate
m3 / min
225
225
Fan
L/s
3,750
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
8.8
8.8
Case heater
kW
0.057(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder coating Pre-coated galvanized steel sheet (+powder coating
External finish
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
for -BS type) *5 <MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Type x original charge
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
574(260)
574(260)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
1/2"(12.7)Brazed
1/2"(12.7)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L658
Drawing
Wiring
WKE94C211X01
WKE94C211X01
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y100VBK2 (Twinning Kit is necessary to combine the refrigerant flows of
the modules and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Type x Quantity

Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System
Design section, pgs. 255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System
Design section, p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-20

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P264YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

Fan

Compressor

264,000

kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

77.4
21.28 *3
29.6 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
280,000
82.1
21.23 *3
29.6 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
5-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50

dB <A>

63.5

in. (mm)

3/4"(19.05) Brazed

in. (mm)

1-3/8"(34.93) Brazed

PUHY-P72YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,050
7,950
3
Airflow rate
m / min
200
200
225
L/s
3,330
3,330
3,750
Inverter-control, Direct-driven by
Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Control , Driving mechanism
motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *5
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
5.1
5.1
8.8
Case heater
kW
0.051(230 V)
0.051(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

External finish
External dimension H x W x D

in.
mm

High pressure protection


Protection
devices

Compressor / Fan
Inverter

Refrigerant

Y-SERIES
Y-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
anechoic room)
Refrigerant piping Liquid pipe
diameter from
Twinning Kit to
Gas pipe
Indoor Units
Set Model
Model
Type x Quantity

BTU / h

Type x original charge


Control

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Refrigerant
Liquid pipe
piping diameter
from Module to
Gas pipe
Twinning Kit
Defrosting method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard
attachment
Accessory

Pre-coated galvanized steel sheet


(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
High pressure sensor, High pressure
switch at 4.15MPa (601 psi)
Over-heat protection / Thermal
switch
Over-heat protection,Over-current
protection
R410A x 19 lbs + 13 oz (9.0kg)

lbs (kg)

474(215)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed
in. (mm)
in. (mm)

Optional parts

Remark

Pre-coated galvanized steel sheet


(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 36-1/4" x 29-15/16"
1,650 x 920 x 760
High pressure sensor, High pressure
switch at 4.15MPa (601 psi)
Over-heat protection / Thermal switch

Pre-coated galvanized steel sheet


(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 1,220 x 760
High pressure sensor, High pressure
switch at 4.15MPa (601 psi)
Over-heat protection / Thermal switch

Over-heat protection,Over-current
protection
R410A x 19 lbs + 13 oz (9.0kg)
LEV and HIC circuit
474(215)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
3/8"(9.52)Brazed

Over-heat protection,Over-current
protection
R410A x 25 lbs + 6 oz (11.5kg)
574(260)
Salt-resistant cross fin & copper tube
Copper pipe,tube-in-tube structure
1/2"(12.7)Brazed

3/4"(19.05)Brazed

7/8"(22.2)Brazed

3/4"(19.05)Brazed

Auto-defrost mode (Reversed refrigerant cycle)


KB94L659
WKE94C211X01
WKE94C211X01
WKE94C211X01
Installation Manual
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall
be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-21

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P288YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
anechoic room)
Refrigerant piping Liquid pipe
diameter from
Twinning Kit to
Gas pipe
Indoor Units
Set Model
Model
Type x Quantity

Fan

Compressor

BTU / h

288,000

kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

84.4
24.52 *3
34.1 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
308,000
90.3
24.27 *3
33.8 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
5-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50

dB <A>

63.5

in. (mm)

3/4"(19.05) Brazed

in. (mm)

1-3/8"(34.93) Brazed

PUHY-P72YHMU-A(-BS)
PUHY-P96YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,050
7,950
3
Airflow rate
m / min
200
200
225
L/s
3,330
3,330
3,750
Inverter-control, Direct-driven by
Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Control , Driving mechanism
motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
5.1
6.8
8.8
Case heater
kW
0.051(230 V)
0.051(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
474(215)
474(215)
574(260)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
3/8"(9.52)Brazed
3/8"(9.52)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L659
Drawing
Wiring
WKE94C211X01
WKE94C211X01
WKE94C211X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-22

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P312YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

Fan

Compressor

312,000

kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

91.4
26.25 *3
36.6 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
320,000
93.8
24.92 *3
34.7 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
4-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50

dB <A>

64.5

in. (mm)

3/4"(19.05) Brazed

in. (mm)

1-3/8"(34.93) Brazed

Y-SERIES
Y-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
anechoic room)
Refrigerant piping Liquid pipe
diameter from
Twinning Kit to
Gas pipe
Indoor Units
Set Model
Model
Type x Quantity

BTU / h

PUHY-P72YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,950
7,950
Airflow rate
m3 / min
200
225
225
L/s
3,330
3,750
3,750
Inverter-control, Direct-driven by
Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Control , Driving mechanism
motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
5.1
8.8
8.8
Case heater
kW
0.051(230 V)
0.057(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
474(215)
574(260)
574(260)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
3/8"(9.52)Brazed
1/2"(12.7)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L660
Drawing
Wiring
WKE94C211X01
WKE94C211X01
WKE94C211X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-23

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P336YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Y-SERIES
Y-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
anechoic room)
Refrigerant piping Liquid pipe
diameter from
Twinning Kit to
Gas pipe
Indoor Units
Set Model
Model
Type x Quantity

Fan

Compressor

BTU / h

336,000

kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

98.5
29.50 *3
41.1 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
348,000
102.0
27.96 *3
38.9 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
4-100%
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50

dB <A>

64.5

in. (mm)

3/4"(19.05) Brazed

in. (mm)

1-5/8"(41.28) Brazed

PUHY-P96YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,050
7,950
7,950
Airflow rate
m3 / min
200
225
225
L/s
3,330
3,750
3,750
Inverter-control, Direct-driven by
Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Control , Driving mechanism
motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
6.8
8.8
8.8
Case heater
kW
0.051(230 V)
0.057(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 19 lbs + 13 oz (9.0kg)
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
474(215)
574(260)
574(260)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
3/8"(9.52)Brazed
1/2"(12.7)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L660
Drawing
Wiring
WKE94C211X01
WKE94C211X01
WKE94C211X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
External finish

Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-24

Y-SERIES (Feb. 2009)

1. SPECIFICATIONS

DATA U4

Model
Power source

PUHY-P360YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

Indoor
Outdoor
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
anechoic room)
Refrigerant piping Liquid pipe
diameter from
Twinning Kit to
Gas pipe
Indoor Units
Set Model
Model
Type x Quantity
Temp. range of
heating

Fan

Compressor

360,000

kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A

105.5
31.23 *3
43.5 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
360,000
105.5
28.61 *3
39.8 *3
6-100%

D.B.
W.B.

Y-SERIES
Y-SERIES
(460V)

Power input
Current input (460)
System Compressor Operating Rane

BTU / h

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 130 % of outdoor unit capacity
P06 to P96 / 2 to 50

dB <A>

65.0

in. (mm)

3/4"(19.05) Brazed

in. (mm)

1-5/8"(41.28) Brazed

PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
Propeller fan x 1
cfm
7,950
7,950
7,950
Airflow rate
m3 / min
225
225
225
L/s
3,750
3,750
3,750
Inverter-control, Direct-driven by
Inverter-control, Direct-driven by motor Inverter-control,Direct-driven by motor
Control , Driving mechanism
motor
Motor output
kW
0.92
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
AC&R Works, MITSUBISHI
Manufacturer
ELECTRIC CORPORATION
ELECTRIC CORPORATION
ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Inverter
Motor output
kW
8.8
8.8
8.8
Case heater
kW
0.057(230 V)
0.057(230 V)
0.057(230 V)
MEL32
MEL32
MEL32
Lubricant

Pre-coated galvanized steel sheet


Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
(+powder coating for -BS type) *5
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure High pressure sensor, High pressure
High pressure sensor, High pressure
High pressure protection
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
switch at 4.15MPa (601 psi)
Protection
Compressor / Fan
Over-heat protection / Thermal switch Over-heat protection / Thermal switch Over-heat protection / Thermal switch
devices
Over-heat protection,Over-current
Over-heat protection,Over-current
Over-heat protection,Over-current
Inverter
protection
protection
protection
Type x original charge
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
R410A x 25 lbs + 6 oz (11.5kg)
Refrigerant
Control
LEV and HIC circuit
Net weight
lbs (kg)
574(260)
574(260)
574(260)
Heat exchanger
Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Refrigerant
1/2"(12.7)Brazed
1/2"(12.7)Brazed
1/2"(12.7)Brazed
Liquid pipe
in. (mm)
piping diameter
from Module to
Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Twinning Kit
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
KB94L661
Drawing
Wiring
WKE94C211X01
WKE94C211X01
WKE94C211X01
Refrigerant cycle
Document
Installation Manual
Standard
attachment
Accessory
Refrigerant conn. Pipe
Outdoor Twinning kit: CMY-Y300VBK2 (Twinning Kit is necessary to combine the refrigerant flows of the modules
and is included in the outdoor unit set)
Optional parts
Joint: CMY-Y102S/L-G2,CMY-Y202/302-G2
Header: CMY-Y104/108/1010-G
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the Y-Series System Design section, pgs.
Remark
255-261.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the Y-Series System Design section,
p. 293.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PUHY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PUHY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PUHY-P120YHMU: MCA = 19A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PUHY-P144-P360).

Y-SERIES (Feb. 2009)

Y-25

1. SPECIFICATIONS

DATA U4

1-3. Energy Efficiencies


Model

Nominal Cooling
Capacity

Cooling
EER

Heating 47 F
COP

Heating 17 F
COP

IPLV

Y-SERIES

HEAT PUMP Models 208/230V and 460V, 3-phase


PUHY-P72T/YHMU-A

72,000 Btu/h

12.4

3.7

2.5

18.6

PUHY-P96T/YHMU-A

96,000 Btu/h

10.8

3.3

2.3

16.1

PUHY-P120T/YHMU-A

120,000 Btu/h

10.9

3.5

2.4

17.4

PUHY-P144T/YSHMU-A

144,000 Btu/h

12.4

3.7

2.5

18.6

PUHY-P168T/YSHMU-A

168,000 Btu/h

11.5

3.5

2.4

17.2

PUHY-P192T/YSHMU-A

192,000 Btu/h

11.4

3.6

2.4

17.9

PUHY-P216T/YSHMU-A

216,000 Btu/h

10.8

3.4

2.4

16.8

PUHY-P240T/YSHMU-A

240,000 Btu/h

10.9

3.5

2.4

17.4

PUHY-P264T/YSHMU-A

264,000 Btu/h

11.7

3.6

2.4

18.1

PUHY-P288T/YSHMU-A

288,000 Btu/h

11.2

3.5

2.4

17.3

PUHY-P312T/YSHMU-A

312,000 Btu/h

11.2

3.5

2.4

17.7

PUHY-P336T/YSHMU-A

336,000 Btu/h

10.8

3.4

2.4

17.0

PUHY-P360T/YSHMU-A

360,000 Btu/h

10.9

3.5

2.4

17.4

These units were tested per the guidelines provided by the Department of Energy (DOE) in the Federal Register / Vol. 73 No. 239 /
Thursday, December 11, 2008 / Notices / pages 75408 75417. Testing was done in accordance with the DOE guidelines and ARI Draft
Standard 1230, which is based on ARI Standard 340/360 and ISO Standard 13256-1. All units meet or exceed ASHRAE 90.1 efficiency
requirements.

Important: Interpreting the Test Results


COP and EER
Testing on these units was performed at full load per the test standard so the Energy Efficiency Ratio (EER) and Coefficient of
Performance (COP) are based on a fixed energy consumption level. Because of this, many of the energy saving benefits of these Variable
Refrigerant Flow Zoning (VRFZ ) systems are not truly reflected in these numbers. Some of the other ways these units maximize energy
use, which are not included in EER and COP are:
1. Inverter driven compressor varies the system capacity based on load demands. Capacity can vary from 100% down to 16%.
2. Smart coil technology automatically varies the indoor unit capacity based on space cooling or heating requirements.
3. The CITY MULTI VRFZ systems can take advantage of building load diversity by using up 130% (Y Series) and 150% (R2 Series)
connected indoor unit capacity. In many cases this can result in smaller capacity outdoor units required to condition the space.
4. Each R2Series system has the ability to transfer heat from one area of the building to another. As an example; at 50% heating and
50% cooling demand, no energy is rejected or absorbed from the outdoors. The energy is moved from one part of the building to another
within the system.

IPLV
Integrated Part-Load Value (IPLV) is not an ASHRAE 90.1 requirement but it better demonstrates the energy saving capabilities of the
CITY MULTI VRFZ systems by taking into account efficiencies at varying capacity conditions. However, it still doesnt account for items 2
4 above. Another important note when comparing these IPLV number to chillers is to know how the calculation/testing was done. The IPLV
values above include all power required to condition the space. Chillers that commonly use IPLV ratings often do not include other energy
consuming devices within the system when arriving at their values. Items such as pumps for water circulation and blower motors in the air
handling devices are often excluded.

Y-26

Y-SERIES (Feb. 2009)

760
(29-15/16)

142
(5-19/32)

172
(6-25/32)

170
(6-23/32)

Refrigerant service
valve <gas>

19.05 Brazed
(3/4)

Gas

9.52 Brazed
(3/8)
22.2 Brazed
(7/8)
(12.7 Brazed)*2
(1/2)

9.52 Brazed
(3/8)

Liquid

Connection specifications for


the refrigerant service valve *1

55
(2-3/16)

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Total length => 90m (295')

PUHY-P96THMU
(-BS)

PUHY-P72THMU
(-BS)

25
(1)

Left side view

25
(1)

Connecting pipe specifications


Position dimensions
for the refrigerant
service valve
Model
Gas
Liquid
B
A

55
(2-3/16)

54 (2-5/32)

Refrigerant service
valve <liquid>

Intake
air

145 (5-23/32)

80
(3-5/32)

Refrigerant service
valve <liquid>

Front view

98
(3-7/8)
102
(4-1/32)

6
72
(2-27/32)

Bottom view

760 (29-15/16)
80
(Mounting pitch)
(3-5/32)

Refrigerant service
valve <gas>

(ID9.52(3/8) X OD9.52(3/8)) P72,P96

NO.

1pc.

1pc.
1pc.
1pc.

Specifications
102 X 72 Knockout hole
(4-1/32) (2-27/32)
For pipes
150 X 92 Knockout hole
Bottom through hole
(5-29/32) (3-5/8)
62.7 or 34.5 Knockout hole
Front through hole
(2-15/32) (1-3/8)
43.7 or 22.2 Knockout hole
Front through hole
For wires
(7/8)
(1-3/4)
52 Knockout hole
Bottom through hole
(2-1/16)
34 Knockout hole
For transmission cables Front through hole
(1-11/32)
Front through hole

Usage

Note1.Please refer to the next page for information


regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

<Liquid> Pipe

<Accessories>
Connecting pipe
<Gas> Elbow (ID25.4(1) X OD25.4(1)) P72,P96
Pipe (ID25.4(1) X OD19.05(3/4)) P72
Pipe (ID25.4(1) X OD22.2(7/8)) P96

2 X 2-14(9/16) X 20(13/16) Oval hole

Service
panel

Intake
air

240 (9-15/32)
1410 (55-17/32)
1650 (64-31/32)

920 (36-1/4)

Top view

150 (5-29/32)
83(3-9/32)

204
(8-1/16)
251
(9-29/32)

(8-23/32) 221
(9-29/32) 251
(7-11/32) 186

Intake
air

Control box

(5-7/32) 132 88 (3-15/32)


131 (5-3/16)

760 (29-15/16)
18
(23/32)

90
(3-9/16)
145 (5-23/32)
86 (3-13/32)
92
(3-5/8)

Y-SERIES (Feb. 2009)


(28-17/32)
724(721 ~ 727)
(28-13/32 ~ 28-5/8)
(Mounting pitch)

Discharge air

Y-SERIES

(760) (29-15/16)

PUHY-P72,96THMU-A(-BS)

18
(23/32)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_THMU-A_EXD_USDB_P72-96_Y1
Unit : mm(in)

Y-27

(19/32)

15 min.*

50 min.*

(1-31/32)

<Top view>

50 min.*

(1-31/32)

Front

100 min.*

(11-13/16)
(17-23/32)

300 min.*
450 min.*

Unit height

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

3
4

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure. (Fig.A)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>

PUHY-P72,96THMU-A(-BS)

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

<Side view>

Front

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

h
500

300 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

In case of collective installation

Front

(11-13/16)
(17-23/32)
15 min.*

(3-15/16)
(17-23/32)

With a space of at least


300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on
the back of the unit
the back of the unit

<To be left open>


Front

1 When multiple units are installed adjacent to each other, secure enough space to allow

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


(19/32)

Front

In case of single installation

Front

<To be left open>


<To be left open>

Front

1 Secure enough space around the unit as shown in the figure below.

(1-3/16)

<To be left open>


<To be left open>

Front

1.Required space around the unit

30mm max.

(11-13/16)

100 min.*
450 min.*

(11-13/16)
900 min.

300 min.*

(35-7/16)
(11-13/16)

Y-SERIES (Feb. 2009)


300 min.*

Wall <H>
300 min.*
900 min.

Y-28
(35-7/16)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_THMU-A_EXD_USDB_P72-96_Y2
Unit : mm(in)

<To be left open>

760
(29-15/16)

25
(1)

Left side view

25
(1)

55
(2-3/16)

9.52 Brazed
172
22.2 Brazed
(3/8)
(6-25/32) (12.7 Brazed) (7/8)
(1/2) *2 *3

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
*3 Total length => 40m (131')

PUHY-P120THMU
(-BS)

158
(6-1/4)

145 (5-23/32)

301
(11-7/8)

254 (9)

(10-11/16) 271
(11-7/8)
301
(8-17/32) 216

Intake
air

80
(3-5/32)

Refrigerant service
valve <liquid>

Refrigerant service
valve <gas>

Connecting pipe specifications


Position dimensions
Connection specifications for
for the refrigerant
the refrigerant service valve *1
service valve
Model
Liquid
Gas
Gas
Liquid
A
B

55
(2-3/16)

54 (2-5/32)

Refrigerant service
valve <liquid>

Intake
air

Control box

(5-7/32) 132 88 (3-15/32)


131 (5-3/16)

145 (5-23/32)

Bottom view

1060 (41-3/4)
(Mounting pitch)

Refrigerant service
valve <gas>

150 (5-29/32)
83 (3-9/32)

Front view

98
(3-7/8)
102
(4-1/32)

80
(3-5/32)

1650 (64-31/32)

(ID15.88(5/8) X OD9.52(3/8))
(ID15.88(5/8) X OD12.7(1/2))

NO.

1pc.
1pc.

1pc.
1pc.

Specifications
102 X 72 Knockout hole
(4-1/32) (2-27/32)
For pipes
150 X 94 Knockout hole
Bottom through hole
(5-29/32)(3-23/32)
62.7 or 34.5 Knockout hole
Front through hole
(2-15/32) (1-3/8)
43.7 or 22.2 Knockout hole
Front through hole
For wires
(7/8)
(1-3/4)
Bottom through hole 65 Knockout hole
(2-9/16)
34 Knockout hole
For transmission cables Front through hole
(1-11/32)
Front through hole

Usage

Note1.Please refer to the next page for information


regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

<Liquid> Pipe
Pipe

<Accessories>
Connecting pipe
<Gas> Elbow (ID25.4(1) X OD25.4(1))
Pipe (ID25.4(1) X OD22.2(7/8))

2 X 2-14(9/16) X 20(13/16) Oval hole

Service
panel

Intake
air

240 (9-15/32)
1410 (55-17/32)

1220 (48-1/16)

72
(2-27/32)

90
(3-9/16)

760 (29-15/16)
18
(23/32)

Top view

84 (3-5/16)
94
(3-23/32)

Y-SERIES (Feb. 2009)


(28-17/32)
724(721 ~ 727)
(28-13/32 ~ 28-5/8)
(Mounting pitch)

Discharge air

Y-SERIES

(760) (29-15/16)

PUHY-P120THMU-A(-BS)

18
(23/32)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_THMU-A_EXD_USDB_P120_Y1
Unit : mm(in)

Y-29

(19/32)

15 min.*

<Top view>

50 min.*

(1-31/32)

50 min.*

(1-31/32)

100 min.*

(11-13/16)
(17-23/32)

300 min.*
450 min.*

Unit height

<Side view>

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>

3
4

securely supported as shown in the right figure. (Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

2 Build the foundation in such way that the corner of the installation leg is

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

300 min.*
450 min.*

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.

Front

2 At least two sides must be left open.


3 As with the single installation, add the height that exceeds the height limit <h>

PUHY-P120THMU-A(-BS)

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

Front

100 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

In case of collective installation

Front

(11-13/16)
(17-23/32)
15 min.*

Front

h
500

<To be left open>


(19/32)

(3-15/16)
(17-23/32)

With a space of at least


300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on
the back of the unit
the back of the unit

<To be left open>


Front

1 When multiple units are installed adjacent to each other, secure enough space to allow

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


<To be left open>

Front

In case of single installation

Front

<To be left open>


<To be left open>

Front

1 Secure enough space around the unit as shown in the figure below.

(1-3/16)

(11-13/16)

1.Required space around the unit

30mm max.

300 min.*
900 min.
300 min.*

(11-13/16)
(35-7/16)

Y-SERIES (Feb. 2009)


(11-13/16)

Wall <H>
300 min.*
900 min.

Y-30
(35-7/16)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_THMU-A_EXD_USDB_P120_Y2
Unit : mm(in)

<To be left open>

Y-SERIES (Feb. 2009)

Left view

Intake
air

Twinning pipe ~ Outdoor unit

1650 (64-31/32)

P72
P96

Unit model

Liquid
c or e
9.52 (3/8)
9.52 (3/8)

Gas
d or f
19.05 (3/4)
22.2 (7/8)

Outdoor unit 1

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Twinning pipe connection size


Package unit name
PUHY-P144TSHMU-A(-BS) PUHY-P168TSHMU-A(-BS)
PUHY-P96THMU-A(-BS)
Outdoor unit 1
PUHY-P72THMU-A(-BS)
Component unit name
Outdoor unit 2
PUHY-P72THMU-A(-BS)
PUHY-P72THMU-A(-BS)
CMY-Y100VBK2
Outdoor Twinning Kit (optional parts)
Liquid a
12.7 (1/2)
15.88 (5/8)
Indoor unit ~ Twinning pipe
28.58 (1-1/8)
Gas
b

Intake
air

Discharge air

920 (36-1/4)

Front view

30 (1-3/16)

Intake
air

b
To indoor unit
Gas Twinning pipe <optional parts>

a
To indoor unit
Liquid Twinning pipe <optional parts>

Outdoor unit 2

920 (36-1/4)

PUHY-P144,168TSHMU-A(-BS)

Y-SERIES

760 (29-15/16)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_TSHMU_EXD_USDB_P144-168
Unit : mm(in)

Y-31

Intake
air

Y-32

Left view

Y-SERIES (Feb. 2009)


Twinning pipe ~ Outdoor unit

9.52 (3/8)
9.52 (3/8)
12.7 (1/2)

P72
P96
P120

Gas
d or f
19.05 (3/4)
22.2 (7/8)
22.2 (7/8)

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Liquid
c or e
Unit model

Outdoor unit 1

Discharge air

Front view

30 (1-3/16)

Intake
air

b
To indoor unit
Gas Twinning pipe <optional parts>

a
To indoor unit
Liquid Twinning pipe <optional parts>

Outdoor unit 2

920 (36-1/4)

PUHY-P192,216TSHMU-A(-BS)

Twinning pipe connection size


Package unit name
PUHY-P192TSHMU-A(-BS) PUHY-P216TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
Outdoor unit 1
PUHY-P120THMU-A(-BS)
Component unit name
Outdoor unit 2
PUHY-P96THMU-A(-BS)
PUHY-P72THMU-A(-BS)
CMY-Y100VBK2
Outdoor Twinning Kit (optional parts)
Liquid a
15.88 (5/8)
Indoor unit ~ Twinning pipe
28.58 (1-1/8)
Gas
b

Intake
air

1220 (48-1/16)

760 (29-15/16)

1650 (64-31/32)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_TSHMU_EXD_USDB_P192-216
Unit : mm(in)

Y-SERIES (Feb. 2009)

Intake
air

Twinning pipe ~ Outdoor unit

1650 (64-31/32)

Liquid
c or e
12.7 (1/2)

Unit model

P120

22.2 (7/8)

Gas
d or f

Outdoor unit 1

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

PUHY-P240TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
CMY-Y100VBK2
15.88 (5/8)
28.58 (1-1/8)

Left view

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe
Gas b

Intake
air

Discharge air

1220 (48-1/16)

Front view

30 (1-3/16)

a
To indoor unit
Liquid Twinning pipe <optional parts>
b
To indoor unit
Gas Twinning pipe <optional parts>

Outdoor unit 2

1220 (48-1/16)

Intake
air

PUHY-P240TSHMU-A(-BS)

Y-SERIES

760 (29-15/16)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_TSHMU_EXD_USDB_P240
Unit : mm(in)

Y-33

Y-34

Left view

Y-SERIES (Feb. 2009)


PUHY-P288TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P96THMU-A(-BS)
PUHY-P72THMU-A(-BS)

Twinning pipe ~ Outdoor unit

Liquid
c or e
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)

Unit model

P72
P96
P120

30 (1-3/16)
920 (36-1/4)

19.05 (3/4)
22.2 (7/8)
22.2 (7/8)

Gas
d or f

30 (1-3/16)

Gas Twinning pipe 1 <optional parts>

Intake
air

b
To indoor unit
Gas Twinning pipe 2 <optional parts>

To indoor unit
Liquid Twinning pipe 2 <optional parts>

Outdoor unit 3

920 (36-1/4)

Liquid Twinning pipe 1 <optional parts>


d

Front view

Outdoor unit 2

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

19.05 (3/4)
34.93 (1-3/8)
19.05 (3/4)
34.93 (1-3/8)

CMY-Y300VBK2

PUHY-P264TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P72THMU-A(-BS)
PUHY-P72THMU-A(-BS)

Intake
air

Outdoor unit 1

1220 (48-1/16)

PUHY-P264,288TSHMU-A(-BS)

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor unit 3
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe 2
Gas b
Twinning pipe 1 ~ Twinning pipe 2 Liquid c
Gas d

Intake
air

Discharge air

760 (29-15/16)

1650 (64-31/32)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_TSHMU_EXD_USDB_P264-288
Unit : mm(in)

Y-SERIES (Feb. 2009)

Twinning pipe connection size


Package unit name
Outdoor unit 1
Outdoor unit 2
Component unit name
Outdoor unit 3
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe 2
Gas b
Twinning pipe 1 ~ Twinning pipe 2 Liquid c
Gas d

Left view

1650 (64-31/32)

PUHY-P336TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P96THMU-A(-BS)

19.05 (3/4)
34.93 (1-3/8)
41.28 (1-5/8)
19.05 (3/4)
34.93 (1-3/8)

CMY-Y300VBK2

PUHY-P312TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P72THMU-A(-BS)

Intake
air

Twinning pipe ~ Outdoor unit

Outdoor unit 1

Liquid
e or g or i
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)

P72
P96
P120

30 (1-3/16)

19.05 (3/4)
22.2 (7/8)
22.2 (7/8)

Gas
f or h or j

Gas Twinning pipe 1 <optional parts>

Liquid Twinning pipe 1 <optional parts>


d

Outdoor unit 2

1220 (48-1/16)

Unit model

Front view

30 (1-3/16)

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Intake
air

Discharge air

1220 (48-1/16)

Intake
air

To indoor unit
Gas Twinning pipe 2 <optional parts>

To indoor unit
Liquid Twinning pipe 2 <optional parts>

Outdoor unit 3

920 (36-1/4)

PUHY-P312,336TSHMU-A(-BS)

Y-SERIES

760 (29-15/16)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_TSHMU_EXD_USDB_P312-336
Unit : mm(in)

Y-35

Y-36

Y-SERIES (Feb. 2009)

Left view

1650 (64-31/32)
19.05 (3/4)
41.28 (1-5/8)
19.05 (3/4)
34.93 (1-3/8)

CMY-Y300VBK2

PUHY-P360TSHMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)
PUHY-P120THMU-A(-BS)

Intake
air

Twinning pipe ~ Outdoor unit

Liquid
e or g or i
12.7 (1/2)

P120

22.2 (7/8)

Gas
f or h or j

30 (1-3/16)

Unit model

Outdoor unit 1

1220 (48-1/16)

30 (1-3/16)

Gas Twinning pipe 1 <optional parts>

Liquid Twinning pipe 1 <optional parts>


d

Front view

Outdoor unit 2

1220 (48-1/16)

Intake
air

To indoor unit
Gas Twinning pipe 2 <optional parts>

a
To indoor unit
Liquid Twinning pipe 2 <optional parts>

Outdoor unit 3

1220 (48-1/16)

PUHY-P360TSHMU-A(-BS)

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor unit 3
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe 2
Gas b
Liquid c
Twinning pipe 1 ~ Twinning pipe 2
Gas d

Intake
air

Discharge air

760 (29-15/16)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_TSHMU_EXD_USDB_P360
Unit : mm(in)

760
(29-15/16)

142
(5-19/32)

172
(6-25/32)

170
(6-23/32)

Refrigerant service
valve <gas>

19.05 Brazed
(3/4)

Gas

9.52 Brazed
(3/8)
22.2 Brazed
(7/8)
(12.7 Brazed)*2
(1/2)

9.52 Brazed
(3/8)

Liquid

Connection specifications for


the refrigerant service valve *1

55
(2-3/16)

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Total length => 90m (295')

PUHY-P96YHMU
(-BS)

PUHY-P72YHMU
(-BS)

25
(1)

Left side view

25
(1)

Connecting pipe specifications


Position dimensions
for the refrigerant
service valve
Model
Gas
Liquid
B
A

55
(2-3/16)

54 (2-5/32)

Refrigerant service
valve <liquid>

Intake
air

80
(3-5/32)

Refrigerant service
valve <liquid>

145 (5-23/32)

Front view

98
(3-7/8)
102
(4-1/32)

6
1

920 (36-1/4)

Top view

Bottom view

760 (29-15/16)
80
(Mounting pitch)
(3-5/32)

Refrigerant service
valve <gas>

150 (5-29/32)
83(3-9/32)

204
(8-1/16)
251
(9-29/32)

(8-23/32) 221
(9-29/32) 251
(7-11/32) 186

Intake
air

Control box

(5-7/32) 132 88 (3-15/32)


131 (5-3/16)

72
(2-27/32)
90
(3-9/16)
145 (5-23/32)
86 (3-13/32)

1650 (64-31/32)

(ID9.52(3/8) X OD9.52(3/8)) P72,P96

NO.

1pc.

1pc.
1pc.
1pc.

Specifications
102 X 72 Knockout hole
(4-1/32) (2-27/32)
For pipes
150 X 92 Knockout hole
Bottom through hole (5-29/32)(3-5/8)
62.7 or 34.5 Knockout hole
Front through hole (2-15/32)
(1-3/8)
43.7
or 22.2 Knockout hole
Front through hole
For wires
(7/8)
(1-3/4)
52 Knockout hole
Bottom through hole (2-1/16)
34 Knockout hole
For transmission cables Front through hole (1-11/32)
Front through hole

Usage

Note1.Please refer to the next page for information


regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

<Liquid> Pipe

<Accessories>
Connecting pipe
<Gas> Elbow (ID25.4(1) X OD25.4(1)) P72,P96
Pipe (ID25.4(1) X OD19.05(3/4)) P72
Pipe (ID25.4(1) X OD22.2(7/8)) P96

2 X 2-14(9/16) X 20(13/16) Oval hole

Transformer box

Service
panel

Intake
air

760 (29-15/16)
18
(23/32)
(28-17/32)
724(721 ~ 727)
(28-13/32 ~ 28-5/8)
(Mounting pitch)
18
(23/32)

Y-SERIES (Feb. 2009)


92
(3-5/8)

240 (9-15/32)
1410 (55-17/32)
(760)(29-15/16)

PUHY-P72,96YHMU-A(-BS)

Y-SERIES

Discharge air

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YHMU-A_EXD_USDB_P72-96_Y1
Unit : mm(in)

Y-37

(19/32)

15 min.*

<Top view>

50 min.*

(1-31/32)

50 min.*

(1-31/32)

Front

100 min.*

(11-13/16)
(17-23/32)

300 min.*

450 min.*

Unit height

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

3
4

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure. (Fig.A)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>

PUHY-P72,96YHMU-A(-BS)

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

<Side view>

Front

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

h
500

300 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

In case of collective installation

Front

(11-13/16)
(17-23/32)
15 min.*

(3-15/16)
(17-23/32)

With a space of at least


300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on
the back of the unit
the back of the unit

<To be left open>


Front

1 When multiple units are installed adjacent to each other, secure enough space to allow

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


(19/32)

Front

In case of single installation

Front

<To be left open>


<To be left open>

Front

1 Secure enough space around the unit as shown in the figure below.

(1-3/16)

<To be left open>


<To be left open>

Front

1.Required space around the unit

30mm max.

(11-13/16)

100 min.*
450 min.*

(11-13/16)
900 min.

300 min.*

(35-7/16)
(11-13/16)

Y-SERIES (Feb. 2009)


300 min.*

Wall <H>
300 min.*
900 min.

Y-38
(35-7/16)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YHMU-A_EXD_USDB_P72-96_Y2
Unit : mm(in)

<To be left open>

760
(29-15/16)

25
(1)

Left side view

25
(1)

55
(2-3/16)

158
(6-1/4)

9.52 Brazed
22.2 Brazed
172
(3/8)
(6-25/32) (12.7 Brazed) (7/8)
(1/2) *2 *3

*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
*3 Total length => 40m (131')

PUHY-P120YHMU
(-BS)

145 (5-23/32)

301
(11-7/8)

254 (9)

(10-11/16) 271
(11-7/8)
301
(8-17/32) 216

Intake
air

80
(3-5/32)

Refrigerant service
valve <liquid>

Refrigerant service
valve <gas>

Connecting pipe specifications


Position dimensions
Connection specifications for
for the refrigerant
the refrigerant service valve *1
service valve
Model
Liquid
Gas
Gas
Liquid
A
B

55
(2-3/16)

54 (2-5/32)

Refrigerant service
valve <liquid>

Intake
air

Control box

(5-7/32) 132 88 (3-15/32)


131 (5-3/16)

Bottom view

1060 (41-3/4)
(Mounting pitch)

Refrigerant service
valve <gas>

150 (5-29/32)
83 (3-9/32)

Front view

98
(3-7/8)
102
(4-1/32)

145 (5-23/32)

1220 (48-1/16)

Top view

72
(2-27/32)

90
(3-9/16)

1650 (64-31/32)

80
(3-5/32)

(ID15.88(5/8) X OD9.52(3/8))
(ID15.88(5/8) X OD12.7(1/2))

1pc.
1pc.

1pc.
1pc.

NO.

Specifications
102 X 72 Knockout hole
(4-1/32) (2-27/32)
For pipes
150 X 94 Knockout hole
Bottom through hole (5-29/32)(3-23/32)
62.7 or 34.5 Knockout hole
Front through hole (2-15/32)
(1-3/8)
43.7 or 22.2 Knockout hole
Front through hole (1-3/4)
For wires
(7/8)
Bottom through hole 65 Knockout hole
(2-9/16)
34 Knockout hole
For transmission cables Front through hole (1-11/32)
Front through hole

Usage

Note1.Please refer to the next page for information


regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

<Liquid> Pipe
Pipe

<Accessories>
Connecting pipe
<Gas> Elbow (ID25.4(1) X OD25.4(1))
Pipe (ID25.4(1) X OD22.2(7/8))

2 X 2-14(9/16) X 20(13/16) Oval hole

Transformer box

Service
panel

Intake
air

760 (29-15/16)
18
(23/32)
(28-17/32)
724(721 ~ 727)
18
(28-13/32 ~ 28-5/8)
(23/32)
(Mounting pitch)

Y-SERIES (Feb. 2009)


84 (3-5/16)
94
(3-23/32)

240 (9-15/32)
1410 (55-17/32)
(760) (29-15/16)

PUHY-P120YHMU-A(-BS)

Y-SERIES

Discharge air

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YHMU-A_EXD_USDB_P120_Y1
Unit : mm(in)

Y-39

(19/32)

15 min.*

50 min.*

(1-31/32)

<Top view>

50 min.*

(1-31/32)

Front

100 min.*

(11-13/16)
(17-23/32)

300 min.*

450 min.*

Unit height

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>

3
4

securely supported as shown in the right figure. (Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

2 Build the foundation in such way that the corner of the installation leg is

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit<h>

PUHY-P120YHMU-A(-BS)

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

<Side view>

Front

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

h
500

300 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

In case of collective installation

Front

(11-13/16)
(17-23/32)
15 min.*

(3-15/16)
(17-23/32)

With a space of at least


300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on
the back of the unit
the back of the unit

<To be left open>


Front

1 When multiple units are installed adjacent to each other, secure enough space to allow

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


(19/32)

Front

In case of single installation

Front

<To be left open>


<To be left open>

Front

1 Secure enough space around the unit as shown in the figure below.

(1-3/16)

<To be left open>


<To be left open>

Front

1.Required space around the unit

30mm max.

(11-13/16)

100 min.*
450 min.*

(11-13/16)
900 min.

300 min.*

(35-7/16)
(11-13/16)

Y-SERIES (Feb. 2009)


300 min.*

Wall <H>
300 min.*
900 min.

Y-40
(35-7/16)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YHMU-A_EXD_USDB_P120_Y2
Unit : mm(in)

<To be left open>

Y-SERIES (Feb. 2009)

Left view

Intake
air

Twinning pipe ~ Outdoor unit

1650 (64-31/32)

P72
P96

Unit model

Liquid
c or e
9.52 (3/8)
9.52 (3/8)

Gas
d or f
19.05 (3/4)
22.2 (7/8)

Outdoor unit 1

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Twinning pipe connection size


Package unit name
PUHY-P144YSHMU-A(-BS) PUHY-P168YSHMU-A(-BS)
Outdoor unit 1 PUHY-P72YHMU-A(-BS) PUHY-P96YHMU-A(-BS)
Component unit name
Outdoor unit 2 PUHY-P72YHMU-A(-BS) PUHY-P72YHMU-A(-BS)
Outdoor Twinning Kit (optional parts)
CMY-Y100VBK2
12.7 (1/2)
15.88 (5/8)
Liquid a
Indoor unit ~ Twinning pipe
28.58 (1-1/8)
Gas
b

Intake
air

Discharge air

920 (36-1/4)

Front view

30 (1-3/16)

Intake
air

b
To indoor unit
Gas Twinning pipe <optional parts>

a
To indoor unit
Liquid Twinning pipe <optional parts>

Outdoor unit 2

920 (36-1/4)

PUHY-P144,168YSHMU-A(-BS)

Y-SERIES

760 (29-15/16)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YSHMU-A_EXD_USDB_P144-168
Unit : mm(in)

Y-41

Intake
air

Y-42

Y-SERIES (Feb. 2009)


PUHY-P216YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P96YHMU-A(-BS)

Twinning pipe ~ Outdoor unit

P72
P96
P120

Unit model

Liquid
c or e
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)

Gas
d or f
19.05 (3/4)
22.2 (7/8)
22.2 (7/8)

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

CMY-Y100VBK2
15.88 (5/8)
28.58 (1-1/8)

PUHY-P192YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)

Left view

Outdoor unit 1

Discharge air

Front view

30 (1-3/16)

Intake
air

b
To indoor unit
Gas Twinning pipe <optional parts>

a
To indoor unit
Liquid Twinning pipe <optional parts>

Outdoor unit 2

920 (36-1/4)

PUHY-P192,216YSHMU-A(-BS)

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe
Gas
b

Intake
air

1220 (48-1/16)

760 (29-15/16)

1650 (64-31/32)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YSHMU_EXD_USDB_P192-216
Unit : mm(in)

Y-SERIES (Feb. 2009)

Intake
air

Twinning pipe ~ Outdoor unit

1650 (64-31/32)

P120

Unit model

Liquid
c or e
12.7 (1/2)

Gas
d or f
22.2 (7/8)

Outdoor unit 1

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

CMY-Y100VBK2
15.88 (5/8)
28.58 (1-1/8)

PUHY-P240YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)

Left view

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe
Gas b

Intake
air

Discharge air

1220 (48-1/16)

Front view

30 (1-3/16)

a
To indoor unit
Liquid Twinning pipe <optional parts>
b
To indoor unit
Gas Twinning pipe <optional parts>

Outdoor unit 2

1220 (48-1/16)

Intake
air

PUHY-P240YSHMU-A(-BS)

Y-SERIES

760 (29-15/16)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YSHMU_EXD_USDB_P240
Unit : mm(in)

Y-43

Y-44

Left view

Y-SERIES (Feb. 2009)

1650 (64-31/32)
PUHY-P288YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P96YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)

Twinning pipe ~ Outdoor unit

P72
P96
P120

Unit model

Liquid
e or g or i
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)

30 (1-3/16)
920 (36-1/4)

Gas
f or h or j
19.05 (3/4)
22.2 (7/8)
22.2 (7/8)

30 (1-3/16)
920 (36-1/4)

Gas Twinning pipe 1 <optional parts>

Intake
air

b
To indoor unit
Gas Twinning pipe 2 <optional parts>

To indoor unit
Liquid Twinning pipe 2 <optional parts>

Outdoor unit 3

Liquid Twinning pipe 1 <optional parts>


d

Front view

Outdoor unit 2

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

CMY-Y300VBK2
19.05 (3/4)
34.93 (1-3/8)
19.05 (3/4)
34.93 (1-3/8)

PUHY-P264YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)

Intake
air

Outdoor unit 1

1220 (48-1/16)

PUHY-P264,288YSHMU-A(-BS)

Twinning pipe connection size


Package unit name
Outdoor unit 1
Outdoor unit 2
Component unit name
Outdoor unit 3
Outdoor Twinning Kit (optional parts)
Liquid a
Indoor unit ~ Twinning pipe 2
Gas b
Liquid c
Twinning pipe 1 ~ Twinning pipe 2
Gas d

Intake
air

Discharge air

760 (29-15/16)

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YSHMU_EXD_USDB_P264-288
Unit : mm(in)

Y-SERIES (Feb. 2009)

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor unit 3
Outdoor Twinning Kit(optional parts)
Liquid a
Indoor unit ~ Twinning pipe 2
Gas b
Liquid c
Twinning pipe 1 ~ Twinning pipe 2
Gas d

Left view

1650 (64-31/32)

PUHY-P336YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P96YHMU-A(-BS)

CMY-Y300VBK2
19.05 (3/4)
41.28 (1-5/8)
34.93 (1-3/8)
19.05 (3/4)
34.93 (1-3/8)

PUHY-P312YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)

Intake
air

Twinning pipe ~ Outdoor unit

Outdoor unit 1

P72
P96
P120

Unit model

1220 (48-1/16)

Liquid
e or g or i
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)

30 (1-3/16)

Gas
f or h or j
19.05 (3/4)
22.2 (7/8)
22.2 (7/8)

Gas Twinning pipe 1 <optional parts>

Liquid Twinning pipe 1 <optional parts>

Outdoor unit 2

Front view

30 (1-3/16)

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Intake
air

Discharge air

1220 (48-1/16)

Intake
air

To indoor unit
Gas Twinning pipe 2 <optional parts>

To indoor unit
Liquid Twinning pipe 2 <optional parts>

Outdoor unit 3

920 (36-1/4)

PUHY-P312,336YSHMU-A(-BS)

Y-SERIES

760 (29-15/16)

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YSHMU-A_EXD_USDB_P312-336
Unit : mm(in)

Y-45

Y-46

Y-SERIES (Feb. 2009)

Left view

1650 (64-31/32)
CMY-Y300VBK2
19.05 (3/4)
41.28 (1-5/8)
19.05 (3/4)
34.93 (1-3/8)

PUHY-P360YSHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)
PUHY-P120YHMU-A(-BS)

Intake
air

1220 (48-1/16)

Unit model

Outdoor unit 1

Liquid
e or g or i
12.7 (1/2)

Gas
f or h or j
22.2 (7/8)

30 (1-3/16)

1220 (48-1/16)

30 (1-3/16)

Gas Twinning pipe 1 <optional parts>

Liquid Twinning pipe 1 <optional parts>


d

Front view

Outdoor unit 2

1220 (48-1/16)

Intake
air

b
To indoor unit
Gas Twinning pipe 2 <optional parts>

To indoor unit
Liquid Twinning pipe 2 <optional parts>

Outdoor unit 3

PUHY-P360YSHMU-A(-BS)

Twinning pipe ~ Outdoor unit P120


Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a", "b", "c" and "d" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor unit 3
Outdoor Twinning Kit(optional parts)
Liquid a
Indoor unit ~ Twinning pipe 2
Gas b
Twinning pipe 1 ~ Twinning pipe 2 Liquid c
Gas d

Intake
air

760 (29-15/16)

Discharge air

Y-SERIES

2. EXTERNAL DIMENSIONS
DATA U4

Ref. : PUHY_YSHMU-A_EXD_USDB_P360
Unit : mm(in)

3. CENTER OF GRAVITY

DATA U4

PUHY-P72,96THMU-A (-BS)
PUHY-P72,96YHMU-A (-BS)
920 (36-1/4)

760 (29-15/16)

Unit : mm[in]

PUHY-P72THMU-A (-BS)

334[13-5/32] 329[12-31/32] 592[23-5/16]

PUHY-P96THMU-A (-BS)

334[13-5/32] 329[12-31/32] 592[23-5/16]

PUHY-P72YHMU-A (-BS)

327[12-7/8]

321[12-21/32] 608[23-15/16]

PUHY-P96YHMU-A (-BS)

327[12-7/8]

321[12-21/32] 608[23-15/16]

1410 (55-17/32)

X
760 (29-15/16)

724 (28-17/32)

80 (3-5/32)

PUHY-P120THMU-A (-BS)
PUHY-P120YHMU-A (-BS)
1220 (48-1/16)

1410 (55-17/32)

760 (29-15/16)

Unit : mm[in]

Model

PUHY-P120THMU-A (-BS)

440[17-11/32] 329[12-31/32] 570[22-15/32]


584[23]

PUHY-P120YHMU-A (-BS) 429[16-29/32] 321[12-21/32]

X
1060 (41-3/4)

Y
80 (3-5/32)

724 (28-17/32)

Ref. : PUHY_YHMU-A_COG_USDB_ALL

Y-SERIES (Feb. 2009)

Y-47

Y-SERIES

Model

Y-48

Y-SERIES (Feb. 2009)

CN01

CX1
F1
AC250V
6.3A T

Z1

DSA1

Symbol

4-way valve

Explanation

Z3
TB21

CX5

CX6

TH7
THBOX
THHS
Z24,25

TH3
TH4
TH5
TH6

TH2

TB7

TB1
TB3

Symbol

Power supply
3~
60Hz
208/230V

L3

L3

black

TB23

L2

L2

L1

white

red

TB22

CX4

TB1 L1

CX3
CX2
F2
AC250V
6.3A T

Z2

Cooling/Heating switching
Heat exchanger capacity control
Pressure
High pressure protection for the
switch
outdoor unit
63HS1
Discharge pressure
Pressure
sensor
63LS
Low pressure
72C
Magnetic relay(inverter main circuit)
CT12,22,3 Current sensor(AC)
Crankcase heater(for heating the compressor)
CH11
DC reactor
DCL
HIC bypass,Controls refrigerant
Linear
LEV1
expansion
flow in HIC circuit
valve
LEV2a,b
Pressure control,Refrigerant flow
rate control
Solenoid
For opening/closing the bypass
SV1a
valve
circuit under the O/S
SV5b
Outdoor unit heat exchanger
capacity control
SV9
For opening/closing the bypass
circuit

21S4a
21S4b
63H1

Z4

CY1
CY2
CY3

1 3 CN02

C1

2
1

black

red

*5

*5

black

CT3

SC-T

THBOX

1 3

CN5V
yellow

12

red

Power supply
Indoor/Outdoor transmission
cable
Central control transmission
cable
Thermistor
Subcool bypass outlet
temperature
Pipe temperature
Discharge pipe temperature
ACC inlet pipe temperature
Subcooled liquid refrigerant
temperature
OA temperature
Control box internal temperature
IGBT temperature
Function setting connector

white

SC-R

red

red

V
W

white

white

MS
3~

CT12

SC-U

C1

SC-V

RSH2

CN2

5
7

black

black

CT22

SC-W

CNDC
pink

1
2

CN4 12

SV9

SV5b

21S4a

CH11

SV1a

21S4b

A2 red
72C
A1 white

CN502

CN508
black

CN506

CN504
1 green

CN503
1 blue

1 CN501

CN505
1 black

12
CNT01

red
CNAC

X09

X05

X04

X03

X02

X01

X72

321

SWU1
1's digit

LED1

SW5

10

SW4

10

SW3

10

Function setting

F01
AC250V
3.15A T

1234

CN41

M-NET power
supply
circuit

CN04

1234

CN102

3 red

321

1234

54321

CNIT
red

21

TB3
M1 M2

TB7
M1 M2 S
TP1 TP2

LED1:Power supply to
Indoor/Outdoor
transmission line

CNS2
yellow

12345

CN211 12

CN215 2
black 1

4321

12

red
CNIT

CN201 2

CN202 23
red
1

CN990 12

CN212 2

CN213 3
2
red
1

CNTYP4 21
green

CNTYP5 3
1
green

LED1
Display
setting

CN102

OFF

6
CNLVB 5
4
red
3
2
1
6
CNLVC 5
4
red
3
2
1

SW1

10

6
5

2
1

CNLVA 43

Indoor/Outdoor Central control


transmission
transmission
cable
cable

*4

SW2

10

yellow
CNS2

Power selecting
connector

M-NET Board

321

red
CN3S CN3D

CN40

LED2:CPU in operation

ON

*3
Compressor ON/OFF output
Error detection output

CN03
black

321

yellow blue
CN3K CN3N

*3

F01
AC250V
3.15A T

CN2

12
CN4

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

LED3:Lit when powered

3
4
5

12V CN51
1

2
1

7
5

12 21
CNT02 CN332
blue

Control Board

1 3
CN801
yellow

Unit address setting

SWU2
10's digit

Power
failure
detection
circuit

CPU power
supply circuit

CNDC
3 pink

CNAC2
2 black
1

*1.Single-dotted lines indicate wiring


not supplied with the unit.
*2.Dot-dash lines indicate the control
box boundaries.
*3.Refer to the Data book for connecting
input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the
outdoor units in the same refrigerant
system together.
*5.Faston terminals have a locking
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
terminals to remove them.

Motor
(Compressor)

THHS

RSH1

LED1:Normal
operation
LED2:Error

CN6

R30 C30 C31 C32

SC-S

ZNR1

IPM

LED1:Normal operation(Lit)
/Error(Blink)
1

SC-P1

black

R630

C630

IGBT

Explanation

TB-N

TB-P

SC-P2

INV Board

black

Terminal
block

Ground

black

white

red

red

33
43

72C

23

44

13

R1

24

14

*5

CNINV

3
1

6
CN22 5
LED3:CPU in red 4
3
operation
2
1

CN21 3
blue 2

12 45

21

CN18V CN4
blue

Z24

Z25

1
2
3
1
2
3

TH7

LEV2b

LEV2a

LEV1

TH4

TH2

63HS1

63LS

TH5

TH3

TH6
t
t

PUHY-P72,96THMU-A(-BS)

<Symbol explanation>

Noise Filter

V
W

DCL 34

red

M
3~

Fan motor
(Heat exchanger)

F01
AC250V
CNVDC 15A T

FAN Board

63H1

Y-SERIES

4. ELECTRICAL WIRING DIAGRAMS


DATA U4

Ref.:PUHY_THMU-A_EWD_USDB_P72-96

CN01 5

CY3

Z1

F1 CX1
AC250V
6.3A T

CY2

CY1

Y-SERIES (Feb. 2009)

TB1

L2

L2

white

L3

L3

black

Z5
C41

TH7
THBOX
THHS
Z24,25,26

TH3
TH4
TH5
TH6

TH2

TB7

Symbol
TB1
TB3

U
V

red

C1

black

DCCT1

black

R01

21

R630

C630

21

Z26
21

IPM

IPM

C007

FT-N

*5

white

MS
3~

white

SW1

pink

3 1 CNDC3

21S4c

SV9

SV5c

SV5b

21S4a

CH11

SV1a

21S4b
CN502

CN501

1
6
5

CN508
black

CN507
red

CN506

CN504
1 green

CN503
1 blue

CN505
1 black

12
CNT01

CNAC
red

X09

X08

X07

X05

X04

X03

X02

X01

X72

12V

SWU1
1's digit

321

LED1

SW4

SW5

SW3

10

Function setting

10

10

M-NET power
supply
circuit

CN04
red

CN41
1234

6
CNLVC 5
4
red
3
2
1

red
CNIT

CNS2
yellow

21

12345

CNIT
red

54321

CN211 1
2

CN215 2
1
black

CN202 3
2
red
1
3
CN201 2
1

CN990 2
1

TB3
M1 M2

CN212 2

CN213 3
2
red
1

CNTYP4 2
1
green

CNTYP5 3
1
green

LED1
Display
setting

SW1

10

2
1

CNLVB 5
4
red
3

2
1

6
5

4
CNLVA 3

TP1 TP2

Central control
transmission
cable

TB7
M1 M2 S

LED1:Power supply to
Indoor/Outdoor
transmission line

CN102

4321

OFF

12

yellow
CNS2

SW2

10

Indoor/Outdoor
transmission
cable

*4

M-NET Board

1234

F01
AC250V
3.15A T

CN102
321

321

red
CN3S CN3D

Power selecting
connector

1234

CN40

LED2:CPU in operation

ON

*3
Compressor ON/OFF output
Error detection output

CN03
black

321

CN2

12
CN4

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

LED3:Lit when powered

3
4
5

CN51
1

yellow blue
CN3K CN3N

*3

F01
AC250V
3.15A T

SWU2
10's digit

2
1

7
5

12 21
CNT02 CN332
blue

Control Board

1 3
CN801
yellow

Unit address setting

Power
failure
detection
circuit

CPU power
supply circuit

CNDC
3 pink

CNAC2
2 black
1

*1.Single-dotted lines indicate wiring


not supplied with the unit.
*2.Dot-dash lines indicate the control
box boundaries.
*3.Refer to the Data book for connecting
input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the
outdoor units in the same refrigerant
system together.
*5.Faston terminals have a locking
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
terminals to remove them.

red

CNFG 2
blue 1
F02
AC250V
3.15A T

IPM power
supply
circuit

2
1

7
5

CN4 2

CN2

CN5V
yellow

3 1

LED3:Charge

Function
setting

OFF ON
1

ACCT1

red

25

Motor
(Compressor)

black

CNDC1
C008

ACCT2

LED1:Normal operation
LED2:Error

CNIPM

black

THBOX

CN21 3
blue 2

LED1:Normal
operation
LED2:Error

INV Board

CN4

6
CN22 5
LED3:CPU in red 4
3
operation
2
1

12 45

21

CN18V
blue

LED4:CPU in
operation

CNTH CNTYP CNCT3


green
black

THHS

1
2
3 CNCT
4

CNCT2
blue

4321

2
1

CNINV

3
1

F01
AC250V
CNVDC 15A T

FAN Board

Explanation
Power supply
Terminal
block
Indoor/Outdoor transmission
cable
Central control transmission
cable
Thermistor
Subcool bypass outlet
temperature
Pipe temperature
Discharge pipe temperature
ACC inlet pipe temperature
Subcooled liquid refrigerant
temperature
OA temperature
Control box internal temperature
IGBT temperature
Function setting connector

Ground

M
3~

72C

TB23

~ ~

Stack

TB22

R2

black

R1

Power supply
3~
60Hz
208/230V

L1

L1

red

F2
AC250V
6.3A T

CX3 TB21
CX2

Z2

Z3

Diode

F3
AC250V
6.3A T

TB42

72C

black

1 3 CN03

TB31

red

Explanation
4-way valve Cooling/Heating switching
Heat exchanger capacity control
Pressure
High pressure protection for the
switch
outdoor unit
63HS1
Discharge pressure
Pressure
sensor
63LS
Low pressure
72C
Magnetic relay(inverter main circuit)
ACCT1,2,3 Current sensor(AC)
CH11
Crankcase heater(for heating the compressor)
DCCT1
Current sensor(DC)
DC reactor
DCL
HIC bypass,Controls refrigerant
LEV1
Linear
expansion
flow in HIC circuit
valve
LEV2a,b
Pressure control,Refrigerant flow
rate control
Solenoid
For opening/closing the bypass
SV1a
valve
circuit under the O/S
SV5b,c
Outdoor unit heat exchanger
capacity control
SV9
For opening/closing the bypass
circuit

Symbol
21S4a
21S4b,c
63H1

CN02 1 3

<Symbol explanation>

Z4 DSA1

Noise
Filter

CX4 CX5

DCL

ACCT3

CX6

Fan motor
(Heat exchanger)

SC-P1

Z24

Z25

1
2
3
1
2
3

LEV2b

LEV2a

LEV1

TH4

TH2

63HS1

63LS

TH5

TH3

TH7

TH6

PUHY-P120THMU-A(-BS)

Y-SERIES

CNDC2

63H1

4. ELECTRICAL WIRING DIAGRAMS


DATA U4

Ref.:PUHY_THMU-A_EWD_USDB_P120

Y-49

Y-50

*7 exist

Y-SERIES (Feb. 2009)

Explanation
4-way valve Cooling/Heating switching
Heat exchanger capacity control
Pressure
High pressure protection for the
switch
outdoor unit
63HS1
Discharge pressure
Pressure
sensor
63LS
Low pressure
72C
Magnetic relay(inverter main circuit)
CT12,22,3 Current sensor(AC)
Crankcase heater(for heating the compressor)
CH11
DC reactor
DCL
HIC bypass,Controls refrigerant
Linear
LEV1
expansion
flow in HIC circuit
valve
LEV2a,b
Pressure control,Refrigerant flow
rate control
Solenoid
For opening/closing the bypass
SV1a
valve
circuit under the O/S
SV5b,c
Outdoor unit heat exchanger
capacity control
SV9
For opening/closing the bypass
circuit
TB1
Power supply
Terminal
block
Indoor/Outdoor transmission
TB3
cable
Central control transmission
TB7
cable
Thermistor
Subcool bypass outlet
TH2
temperature
TH3
Pipe temperature
TH4
Discharge pipe temperature
ACC inlet pipe temperature
TH5
TH6
Subcooled liquid refrigerant
temperature
TH7
OA temperature
Control box internal temperature
THBOX
THHS
IGBT temperature
Z24,25
Function setting connector

Symbol
21S4a
21S4b,c
63H1

<Symbol explanation>

*7 do not exist

P120

Appliance

P72/P96

Model name

red

CN1A 3

Z1 Z2 Z3
U U U

R1

white

R2

R3

C9
C8
C7

TB1

black

+
C17

R6

R4

C5

C6

F4
600V
3A F

red
white
black

black

white

red

2
purple 1

460V

6
5
4
3

CN07

2
purple 1

460V

6
5
4
3

CN06

T03
(Tranasformer)

T02
(Tranasformer)

F5
600V
3A F

+
+
+
+

SC-P2

black

white

red

+
+
+
+
R31
R33
R35

CN5V
yellow

CT12

SC-L2

SC-U

t
THHS

white

MS
3~

white

SC-V

2
1

black

black

CT22

SC-W

CNTYP
black

CN2

Motor
(Compressor)

red

red

RSH1

C1

7
5

CN4 1

LED1:Normal operation(Lit)
/ Error(Blink)

CN6

21S4c

*7

5
72C
6

SV9

SV5c

SV5b

21S4a

CH11

SV1a

21S4b

CN503

CN502

CN501

CN504

CN508

CN507
red

CN506

3 black

6
5

1 green

CPU power
supply circuit

CNAC
red

X09

X08

X07

X05

X04

X03

X02

X01

12

CNT01

F01
AC250V
3.15A T

2 CN72 ZNR01
1 red
U
CNAC2
black

1 blue

2
1

CNDC
3 pink
12

CN2

SW5

10

12

CN4

LED1

SW3

10

yellow
CN3K
321

blue
CN3N
321

CN04
3 red

CN102
1234

CN41
1234

CN40
1234

M-NET Board

M-NET power
supply circuit

red
CN3S CN3D
321 321

LED2:CPU in operation

LED1
Display
setting

SW1

10

CNTR3

63H1

4321

CN102

2
1

54321

1
2

CN215 1
2
black

CN201 2

CN202 23
red
1

CN990 21

CN212 21

CN213 3
2
red

CNTYP4 2
1
green

CNTYP5 3
green
1

CNTYP2
black

6
5
CNLVC 4
3
red
2
1

6
5
CNLVB 4
3
red
2
1

red
CN211
CNIT
12345

21

6
5

CNLVA 34

Central control
transmission
cable

CNS2
CNIT
yellow
red
LED1:Power supply to
Indoor/Outdoor
transmission line
TB7
TB3
M1 M2
M1 M2 S
TP1 TP2

yellow
CNS2
12

OFF

ON

TB7 Power
selecting
connector

SW2

10

Function
setting

SW4

10

LED3:Lit when powered

3
4
5

21

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

2
1

CNT02 CN332
blue

*3
Compressor ON/OFF output
Error detection output

Unit address
setting

SWU2 SWU1
10's 1's
digit digit

12V CN51

*3

Control Board

Power failure
detection circuit

CN801
yellow

*4

CT3

SC-L3

SC-L1

Indoor/Outdoor
transmission
cable

ZNR1

THBOX

6
5
CN22 4
3
red
2
1

LED1:Normal
operation
LED2:Error

21

CN21 3
blue 2

12
CN5

SC-P1

black

*5

IPM

C31
U
C33
IGBT
C35
C37

FT-N

FT-P

*6

2
1
3 72C 4
black

R5

C100

R631

R630

R1

INV Board

R30
R32
R34

C30
C32
C34
C36

4
1

CN1

red

C631

1 3
CN4
red

LED3:CPU in
operation

21
CN18V
blue

CNTR2

L1L2L2 L3

CNTR1 1

Diode
Bridge
F4
AC250V
6.3A T

L1 L2 L3 Ground
Power Source
3~
60Hz
460V

L1 L2 L3

Z5

CN6 1
yellow

TB21 TB22 TB23

L1 L2 L3

C4

Noise
Filter
C10

1 CN1B

C1

C2

F1
C3

F2

Z4
U
F3

DSA

red

DCL

C630

CNINV

4
1

CNVDC

4
1

F01
DC700V
4A T

FAN Board

Z24

Z25

1
2
3

1
2
3

TH4

TH2

63HS1

63LS

TH5

TH3

TH7

TH6

LEV2b

LEV2a

LEV1

PUHY-P72,96,120YHMU-A(-BS)

Tranasformer Box

F1,F2,F3
AC250V
6.3A T

6
5

*1.Single-dotted lines indicate wiring not supplied with the unit.


*2.Dot-dash lines indicate the control box boundaries.
*3.Refer to the Data book for connecting input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the outdoor units in the
same refrigerant system together.
*5.Faston terminals have a locking function.
Make sure the terminals are securely locked
Fan motor
(Heat exchanger)
in place after insertion. Press the tab
U
on the terminals to removed them.
M V
3~
*6.Control box houses high-voltage parts.
W
Before inspecting the inside of the
control box,turn off the power,keep
the unit off for at least 10 minutes,
and confirm that the voltage between
G
G
FT-P and FT-N on INV Board has dropped
to DC20V or less.
CN5
CN4
red
*7.Difference of appliance
blue
D1 R5
CN2

Y-SERIES

4. ELECTRICAL WIRING DIAGRAMS


DATA U4

Ref.:PUHY_YHMU-A_EWD_USDB_P72-120

5. Refrigerant Circuit Diagrams and Thermal Sensors

DATA U4

PUHY-P72,P96THMU/YHMU(-BS) Models
21S4b
TH7

BV1

TH5

21S4a

ST1

HEX
CJ1
63H1
63HS1

CV

Y-SERIES

63LS
SV1a
O/S
CP1

ST3

ACC

TH4

CJ2

Comp

ST6
ST7
SV9

SV5b

CP2 TH2
LEV2a
LEV1

SCC

TH3

ST2

BV2

TH6
LEV2b

PUHY-P120THMU/YHMU(-BS) Models
21S4c

21S4b
21S4a

TH7

ST1

BV1

HEX
63H1
63HS1
CJ1

CV

63LS
TH5

SV1a
O/S
ST3

CP1

ACC

TH4
Comp
CJ2

ST6
ST7
SV9
SV5c

CP2 TH2

SV5b
TH3

LEV2a
SCC

LEV1

ST2

BV2

TH6
LEV2b

Y-SERIES (Feb. 2009)

Y-51

6. SOUND PRESSURE LEVELS

DATA U4
Measurement condition
PUHY-P120THMU/YHMU

Measurement condition
PUHY-P72,96THMU/YHMU

3-1/4' (1m)

Y-SERIES

3-1/4' (1m)

Measurement
location

3-1/4' (1m)

3-1/4' (1m)

Measurement
location

Ref.:PUHY_THMU_NCC_USDB_Y1

Sound Pressure Level of PUHY-P72T/YHMU-A(-BS) Ref.:PUHY_THMU_NCC_USDB_P72

Ref.:PUHY_THMU_NCC_USDB_Y2

Sound Pressure Level of PUHY-P120T/YHMU-A(-BS)


Stand 60Hz

Stand 60Hz
60Hz

Low

80

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

Octave band sound level (dB)

Low

80
Octave band sound level (dB)

Ref.:PUHY_THMU_NCC_USDB_P120

90

90

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30

NC-30
20

20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

Approximate minimum
audible limit on
continuous noise

NC-20
10

500

1k

2k

4k

8k

63

125

63 125 250 500


1k
2k
4k
8k dB(A)
65.0 63.5 61.0 54.5 51.5 47.0 40.5 37.5 58.0
56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound Pressure Level of PUHY-P96T/YHMU-A(-BS) Ref.:PUHY_THMU_NCC_USDB_P96


90
Stand 60Hz
Low

Octave band sound level (dB)

80

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
60.0 63.0 61.0 55.0 51.5 47.0 42.0 36.0 58.0
58.0 53.5 44.0 39.0 36.5 32.5 31.0 24.5 44.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Y-52

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

250

NC-20

Y-SERIES (Feb. 2009)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
72.0 65.0 61.5 57.0 53.5 50.0 46.5 40.0 60.0
51.0 52.0 47.0 43.0 42.5 44.0 42.0 38.5 50.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

6. SOUND PRESSURE LEVELS

DATA U4
Sound Pressure Level of PUHY-P192T/YSHMU-A(-BS)

Measurement condition
PUHY-P144,168,192,216,240TSHMU/YSHMU

Ref.:PUHY_THMU_NCC_USDB_P192

90
Stand 60Hz
Low

3-1/4' (1m)

Measurement
location

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

3-1/4' (1m)

NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

NC-20

250

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz
Ref.:PUHY_THMU_NCC_USDB_Y3

Sound Pressure Level of PUHY-P144T/YSHMU-A(-BS)

Ref.:PUHY_THMU_NCC_USDB_P144

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound Pressure Level of PUHY-P216T/YSHMU-A(-BS)

90

Octave band sound level (dB)

Stand 60Hz

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

Low

80
Octave band sound level (dB)

Low

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
Approximate minimum
audible limit on
continuous noise

NC-20
10

1k

2k

4k

8k

63

125

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Ref.:PUHY_THMU_NCC_USDB_P168

Standard
60Hz
Low noise mode 60Hz

500

1k

2k

4k

8k

63 125 250 500


1k
2k
4k
8k dB(A)
72.5 67.5 64.5 59.5 56.0 52.0 48.0 41.5 62.5
59.0 56.0 49.0 44.5 43.5 44.5 42.5 38.5 51.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound Pressure Level of PUHY-P240T/YSHMU-A(-BS)

Ref.:PUHY_THMU_NCC_USDB_P240

90

90

Stand 60Hz

Stand 60Hz
60Hz

Low

80

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

Octave band sound level (dB)

Low

80
Octave band sound level (dB)

250

NC-20

Octave band central frequency (Hz)

63 125 250 500


1k
2k
4k
8k dB(A)
68.0 66.5 64.0 57.5 54.5 50.0 43.5 40.5 61.0
59.5 51.5 49.0 42.0 41.5 35.5 36.0 28.5 47.0

Sound Pressure Level of PUHY-P168T/YSHMU-A(-BS)

60Hz

70

20

500

Ref.:PUHY_THMU_NCC_USDB_P216

90

Stand 60Hz
80

63 125 250 500


1k
2k
4k
8k dB(A)
64.5 67.5 65.5 59.5 56.0 51.5 46.5 40.5 62.5
64.0 60.5 51.0 46.0 43.5 39.5 38.0 31.5 51.0

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30

NC-30
20

20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

Approximate minimum
audible limit on
continuous noise

NC-20

10
500

1k

2k

4k

8k

63

125

63 125 250 500


1k
2k
4k
8k dB(A)
66.0 66.5 64.0 58.0 54.5 50.0 44.5 40.0 61.0
60.5 54.5 48.0 42.0 40.5 35.5 35.0 28.0 47.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

250

NC-20

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
73.0 68.0 65.0 60.0 56.5 52.5 48.5 42.0 63.0
61.0 58.0 51.0 46.5 45.5 46.5 44.5 40.5 53.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Y-SERIES (Feb. 2009)

Y-53

Y-SERIES

Octave band sound level (dB)

80

6. SOUND PRESSURE LEVELS

DATA U4
Sound Pressure Level of PUHY-P312T/YSHMU-A(-BS)

Measurement condition
PUHY-P264,288,312,336,360TSHMU/YSHMU

Stand 60Hz
Low

Octave band sound level (dB)

80

3-1/4' (1m)

Y-SERIES

Ref.:PUHY_THMU_NCC_USDB_P312

90

3-1/4' (1m)

Measurement
location

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz
Ref.:PUHY_THMU_NCC_USDB_Y4

Sound Pressure Level of PUHY-P264T/YSHMU-A(-BS)

Ref.:PUHY_THMU_NCC_USDB_P264

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound Pressure Level of PUHY-P336T/YSHMU-A(-BS)

Ref.:PUHY_THMU_NCC_USDB_P336

90

90

Stand 60Hz

Stand 60Hz
60Hz

Low

80

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

Octave band sound level (dB)

Low

80
Octave band sound level (dB)

63 125 250 500


1k
2k
4k
8k dB(A)
76.0 69.5 66.5 61.5 58.0 54.5 50.5 44.5 64.5
58.5 56.0 51.5 47.0 46.5 47.0 45.5 41.5 53.5

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30

NC-30
20

20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

Approximate minimum
audible limit on
continuous noise

NC-20
10

500

1k

2k

4k

63

8k

125

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

250

NC-20

63 125 250 500


1k
2k
4k
8k dB(A)
73.5 69.0 66.0 60.5 57.0 53.0 48.5 43.5 63.5
60.0 55.0 51.0 45.5 45.0 44.5 43.0 39.0 52.0

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
75.5 69.5 66.5 61.5 58.0 54.0 50.5 44.0 64.5
59.5 57.5 51.0 47.0 46.0 47.0 45.0 41.5 53.5

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P288T/YSHMU-A(-BS)

Sound level of PUHY-P360T/YSHMU-A(-BS)

Ref.:PUHY_THMU_NCC_USDB_P288

Stand 60Hz

Stand 60Hz
60Hz

Low

80

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

Octave band sound level (dB)

Low

80
Octave band sound level (dB)

Ref.:PUHY_THMU_NCC_USDB_P360

90

90

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-30
20

Approximate minimum
audible limit on
continuous noise

NC-20

10
500

1k

2k

4k

8k

63

125

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
73.5 68.5 66.0 60.5 57.0 53.0 48.5 43.0 63.5
61.0 56.5 50.5 45.5 44.5 44.5 43.0 39.0 52.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Y-54

Y-SERIES (Feb. 2009)

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
77.0 70.0 66.5 62.0 58.5 55.0 51.5 45.0 65.0
56.0 57.0 52.0 48.0 47.5 49.0 47.0 44.0 55.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

7. CAPACITY TABLES
7-1. Correction by Temperature

DATA U4

CITY MULTI could have varied capacity at different design temperatures. Using the nominal cooling/heating capacity value
and the ratio below, the capacity can be observed at various temperatures.

PUHY-

21.1

28.1

72,000

96,000

5.27

8.42

P72YHMU P96YHMU
21.1

28.1

72,000

96,000

5.27

8.42

1.3

Indoor Temperature

1.2
75 WB
23.9 WB

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB
59 WB
15.0 WB

1.3
1.2
75 WB
23.9 WB

Ratio of power input

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB

0.6

59 WB
15.0 WB

0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

23.4

31.7

80,000

108,000

5.68

8.63

P72YHMU P96YHMU
23.4

31.7

80,000

108,000

5.68

8.63

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
59 DB
15.0 DB

1.2
Ratio of heating capacity

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

P72THMU P96THMU

1.1
1.0

70 DB
21.1 DB

0.9
0.8

77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5
Indoor Temperature
1.1
59 DB
15.0 DB

1.0
Ratio of power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

0.9
0.8

70 DB
21.1 DB

0.7
77 DB
25.0 DB

0.6

81 DB
27.2 DB

0.5
0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

50
60
WB
10.0
15.6 WB
Outdoor temperature
Ref:PUHY_THMU_C10_USDB_P72-96

Y-SERIES (Feb. 2009)

Y-55

Y-SERIES

Nominal kW
Cooling
Capacity BTU/h
Input
kW

P72THMU P96THMU

Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

7. CAPACITY TABLES

PUHY-

35.2

42.2

120,000

144,000

10.11

10.87

P120YHMU P144YSHMU
35.2

42.2

120,000

144,000

10.11

10.87

Y-SERIES

Nominal kW
Cooling
Capacity BTU/h
Input
kW

P120THMU P144TSHMU

1.4

Indoor Temperature

1.3
Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U4

75 WB
23.9 WB

1.2

72 WB
22.2 WB

1.1

69 WB
20.6 WB

1.0

67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8

61 WB
16.1 WB
59 WB
15.0 WB

0.7

1.2
75 WB
23.9 WB

Ratio of power input

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB

0.6

59 WB
15.0 WB

0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

P120THMU P144TSHMU
35.2

46.9

120,000

160,000

9.26

11.69

P120YHMU P144YSHMU
35.2

46.9

120,000

160,000

9.26

11.69

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
1.2
Ratio of heating capacity

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

59 DB
15.0 DB

1.1
1.0

70 DB
21.1 DB

0.9
0.8
77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5

Indoor Temperature
1.1

Ratio of power input

1.0
59 DB
15.0 DB

0.9
0.8
0.7

70 DB
21.1 DB

0.6
77 DB
25.0 DB

0.5

81 DB
27.2 DB

0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

60
50
WB
15.6 WB
10.0
Outdoor temperature
Ref:PUHY_THMU_C10_USDB_P120-144

Y-56

Y-SERIES (Feb. 2009)

7. CAPACITY TABLES

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

Nominal kW
Cooling
Capacity BTU/h
Input
kW

PUHY-

56.3

168,000

192,000

14.11

15.84

P216TSHMU P240TSHMU
63.3

70.3

216,000

240,000

19.09

20.82

P168YSHMU P192YSHMU
49.2

56.3

168,000

192,000

14.11

15.84

1.4

Indoor Temperature

1.3
75 WB
23.9 WB

1.2

72 WB
22.2 WB

1.1

69 WB
20.6 WB

1.0

67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8

61 WB
16.1 WB
59 WB
15.0 WB

0.7

P216YSHMU P240YSHMU
63.3

70.3

216,000

240,000

19.09

20.82

1.2
75 WB
23.9 WB

1.1
Ratio of power input

Nominal kW
Cooling
Capacity BTU/h
Input
kW

49.2

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB

0.6

59 WB
15.0 WB

0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

P168TSHMU P192TSHMU
55.1

58.6

188,000

200,000

14.73

15.38

P216TSHMU P240TSHMU
66.8

70.3

228,000

240,000

18.42

19.07

P168YSHMU P192YSHMU
55.1

58.6

188,000

200,000

14.73

15.38

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
1.2
Ratio of heating capacity

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

59 DB
15.0 DB

1.1
1.0

70 DB
21.1 DB

0.9
0.8

77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5

Nominal kW
Heating
Capacity BTU/h
Input
kW

Indoor Temperature

P216YSHMU P240YSHMU
66.8

70.3

228,000

240,000

18.42

19.07

1.1
1.0
Ratio of power input

PUHY-

59 DB
15.0 DB

0.9
0.8

70 DB
21.1 DB

0.7
77 DB
25.0 DB

0.6

81 DB
27.2 DB

0.5
0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

60
50
WB
15.6 WB
10.0
Outdoor temperature
Ref:PUHY_THMU_C10_USDB_P168-240

Y-SERIES (Feb. 2009)

Y-57

Y-SERIES

PUHY-

P168TSHMU P192TSHMU

Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U4

7. CAPACITY TABLES

PUHY-

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

PUHY-

84.4

264,000

288,000

21.28

24.52

P312TSHMU
91.4
312,000
26.25

P264YSHMU P288YSHMU
77.4

84.4

264,000

288,000

21.28

24.52

1.4

Indoor Temperature

1.3
75 WB
23.9 WB

1.2

72 WB
22.2 WB

1.1

69 WB
20.6 WB

1.0

67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8

61 WB
16.1 WB
59 WB
15.0 WB

0.7

P312YSHMU
91.4

1.2

312,000
26.25

75 WB
23.9 WB

1.1
Ratio of power input

Nominal kW
Cooling
Capacity BTU/h
Input
kW

77.4

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB

0.6

59 WB
15.0 WB

0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

P264TSHMU P288TSHMU
82.1

90.3

280,000

308,000

21.23

24.27

P312TSHMU
93.8
320,000
24.92

P264YSHMU P288YSHMU
82.1

90.3

280,000

308,000

21.23

24.27

100
37.8

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
1.2
Ratio of heating capacity

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

59 DB
15.0 DB

1.1
1.0

70 DB
21.1 DB

0.9
0.8

77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

Indoor Temperature

P312YSHMU
93.8

1.1

320,000
24.92

1.0
Ratio of power input

Y-SERIES

Nominal kW
Cooling
Capacity BTU/h
Input
kW

P264TSHMU P288TSHMU

Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U4

0.9

59 DB
15.0 DB

0.8
0.7

70 DB
21.1 DB

0.6
77 DB
25.0 DB

0.5

81 DB
27.2 DB

0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

60
50
WB
15.6 WB
10.0
Outdoor temperature
Ref:PUHY_THMU_C10_USDB_P264-312

Y-58

Y-SERIES (Feb. 2009)

7. CAPACITY TABLES

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

P336TSHMU P360TSHMU
98.5

105.5

336,000

360,000

29.50

31.23

P336YSHMU P360YSHMU
98.5

105.5

336,000

360,000

29.50

31.23

1.3

Indoor Temperature

1.2
75 WB
23.9 WB

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB
59 WB
15.0 WB

1.2
1.1
75 WB
23.9 WB

Ratio of power input

1.0

72 WB
22.2 WB

0.9

69 WB
20.6 WB

0.8

67 WB
19.4 WB

0.7

64 WB
17.8 WB

0.6

61 WB
16.1 WB

0.5

59 WB
15.0 WB

0.4
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

102.0

105.5

348,000

360,000

27.96

28.61

P336YSHMU P360YSHMU
102.0

105.5

348,000

360,000

27.96

28.61

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
1.2
Ratio of heating capacity

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

P336TSHMU P360TSHMU

59 DB
15.0 DB

1.1
1.0

70 DB
21.1 DB

0.9
0.8

77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5
Indoor Temperature
1.1
1.0
Ratio of power input

PUHYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

59 DB
15.0 DB

0.9
0.8

70 DB
21.1 DB

0.7
77 DB
25.0 DB

0.6

81 DB
27.2 DB

0.5
0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

50
60
WB
10.0
15.6 WB
Outdoor temperature
Ref:PUHY_THMU_C10_USDB_P336-360

Y-SERIES (Feb. 2009)

Y-59

Y-SERIES

Ratio of cooling capacity

PUHYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U4

7. CAPACITY TABLES
7-2. Correction by Total Indoor

DATA U4

CITY MULTI systems have different capacities and inputs when different combinations of indoor units with different total
capacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with
enough capacity for a particular application.

PUHY-P72,96THMU/YHMU
50.0

Capacity(kW)

Y-SERIES

40.0

30.0

20.0

10.0

0.0

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units

PUHY-P120,144T(S)HMU/Y(S)HMU
50.0

Capacity(kW)

40.0

30.0

20.0

10.0

Input(kW)

10.0

5.0

P120

P144
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P72-144

Y-60

Y-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

PUHY-P168,192TSHMU/YSHMU
70.0

50.0

Y-SERIES

Capacity(kW)

60.0

40.0

30.0

20.0
20.0

Input(kW)

15.0

10.0

5.0

P168

P192
Cooling
Heating

Cooling
Heating

0.0
0

100

200

300

400

Total capacity of indoor units

PUHY-P216,240TSHMU/YSHMU
80.0

Capacity(kW)

70.0

60.0

50.0

40.0

30.0
25.0

Input(kW)

20.0

15.0

10.0

P216

P240
Cooling
Heating

Cooling
Heating

5.0
0

100

200

300

400

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P168-240

Y-SERIES (Feb. 2009)

Y-61

7. CAPACITY TABLES

DATA U4

PUHY-P264,288TSHMU/YSHMU
100.0

Capacity(kW)

60.0

40.0

20.0

0.0
25.0

Input(kW)

20.0

15.0

10.0

P264

P288
Cooling
Heating

5.0
100

200

300

Cooling
Heating

400

500

Total capacity of indoor units

PUHY-P312,336TSHMU/YSHMU
120.0

Capacity(kW)

100.0

80.0

60.0

40.0

20.0
40.0

30.0

Input(kW)

Y-SERIES

80.0

20.0

10.0

P312

P336
Cooling
Heating

0.0
100

200

300

400

Cooling
Heating
500

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P264-336

Y-62

Y-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

PUHY-P360TSHMU/YSHMU
120.0

80.0

Y-SERIES

Capacity(kW)

100.0

60.0

40.0

20.0
40.0

Input(kW)

30.0

20.0

10.0

P360
Cooling
Heating

0.0
100

200

300

400

500

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P360

Y-SERIES (Feb. 2009)

Y-63

7. CAPACITY TABLES

DATA U4

PUHY-P72,96THMU/YHMU
120,000

Capacity(BTU/h)

80,000

60,000

40,000

20,000

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units

PUHY-P120,144T(S)HMU/Y(S)HMU
200,000

Capacity(BTU/h)

160,000

120,000

80,000

40,000

10.0

Input(kW)

Y-SERIES

100,000

5.0

P120

P144
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P72-144_2

Y-64

Y-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

PUHY-P168,192TSHMU/YSHMU
210,000

150,000

Y-SERIES

Capacity(BTU/h)

180,000

120,000

90,000

60,000
20.0

Input(kW)

15.0

10.0

5.0

P168

P192
Cooling
Heating

Cooling
Heating

0.0
0

100

200

300

400

Total capacity of indoor units

PUHY-P216,240TSHMU/YSHMU
300,000

Capacity(BTU/h)

250,000

200,000

150,000

100,000

50,000
25.0

Input(kW)

20.0

15.0

10.0

P216

P240
Cooling
Heating

Cooling
Heating

5.0
0

100

200

300

400

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P168-240_2

Y-SERIES (Feb. 2009)

Y-65

7. CAPACITY TABLES

DATA U4

PUHY-P264,288TSHMU/YSHMU
350,000

Capacity(BTU/h)

250,000

200,000

150,000

100,000
25.0

Input(kW)

20.0

15.0

10.0

P264

P288
Cooling
Heating

5.0
100

200

300

Cooling
Heating

400

500

Total capacity of indoor units

PUHY-P312,336TSHMU/YSHMU
400,000

Capacity(BTU/h)

350,000

300,000

250,000

200,000

150,000
40.0

30.0

Input(kW)

Y-SERIES

300,000

20.0

10.0

P312

P336
Cooling
Heating

0.0
100

200

300

400

Cooling
Heating
500

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P264-336_2

Y-66

Y-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

PUHY-P360TSHMU/YSHMU
400,000

300,000

Y-SERIES

Capacity(BTU/h)

350,000

250,000

200,000

150,000
40.0

Input(kW)

30.0

20.0

10.0

P360
Cooling
Heating

0.0
100

200

300

400

500

Total capacity of indoor units


Ref: PUHY_THMU_C20_USDB_P360_2

Y-SERIES (Feb. 2009)

Y-67

7. CAPACITY TABLES

DATA U4

7-3. Correction by Refrigerant Piping Length


CITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating capacity could be
reduced. Using the following correction factor by equivalent piping length shown at 7-3-1 and 7-3-2, capacity can be found. 7-3-3
shows how to obtain the equivalent piping length.
7-3-1. Cooling Capacity Correction
PUHY-P168TSHMU/YSHMU

PUHY-P72THMU/YHMU

0.8
54

0.75
0.7

72
94

0.65
0

100

200

300

400

Piping equivalent length

500

0.85

0.75

0.65
0

0.85
0.8

72

0.75

96
125

0.7
0.65
300

400

Piping equivalent length

500

0.85
0.8
90

0.75
0.7

120

0.65

156
300

400

Piping equivalent length

500

0.85
0.8

144

0.75

192

0.7

250

0.65
100

200

300

400

Piping equivalent length

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P192

108

0.95
0.9
0.85
0.8

162

0.75

216
281

0.7
0.65

600 ft.

Ref:PUHY_THMU_C30_USDB_P120

100

200

300

400

Piping equivalent length

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P216

PUHY-P240TSHMU/YSHMU

PUHY-P144TSHMU/YSHMU
1

72

0.95
0.9
0.85

108

0.8
144
0.75

187

0.7
0.65
200

600 ft.

96

Cooling capacity correction factor

0.9

100

500

Ref:PUHY_THMU_C30_USDB_P168

PUHY-P216TSHMU/YSHMU

0.95

400

0.9

60

200

300

0.95

Ref:PUHY_THMU_C30_USDB-P96

100

200

600 ft.

PUHY-P120THMU/YHMU

100

Piping equivalent length

Cooling capacity correction factor

0.9

200

218

PUHY-P192TSHMU/YSHMU

0.95

100

168

0.7

48

126

0.8

Ref:PUHY_THMU_C30_USDB-P72

Cooling capacity correction factor

0.9

600 ft.

PUHY-P96THMU/YHMU

Cooling capacity correction factor

Cooling capacity correction factor

0.85

84

0.95

300

Piping equivalent length

400

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P144

Y-SERIES (Feb. 2009)

Cooling capacity correction factor

Cooling capacity correction factor

0.9

Y-68

36

0.95

Cooling capacity correction factor

Y-SERIES

120

0.95
0.9
0.85
0.8
180

0.75
0.7

240
312

0.65
0

100

200

300

Piping equivalent length

400

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P240

7. CAPACITY TABLES

DATA U4
PUHY-P336TSHMU/YSHMU

PUHY-P264TSHMU/YSHMU

0.9
0.85
0.8

198

0.75

264

0.7

343

0.65
100

200

300

400

Piping equivalent length

500

Cooling capacity correction factor

0.95

252

0.8
336
0.75

437

0.7
0.65
100

200

300

400

Piping equivalent length

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P336

PUHY-P360TSHMU/YSHMU
1

0.9
0.85
0.8

216

0.75

288

0.7

374

0.65
300

400

Piping equivalent length

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P288

Cooling capacity correction factor

0.95

200

0.85

144

100

0.9

Ref:PUHY_THMU_C30_USDB_P264

168

0.95

600 ft.

PUHY-P288TSHMU/YSHMU
Cooling capacity correction factor

132

180

0.95
0.9
0.85
270

0.8
0.75

360
468

0.7
0.65
0

100

200

300

Piping equivalent length

400

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P360

PUHY-P312TSHMU/YSHMU
Cooling capacity correction factor

156

0.95
0.9
0.85
0.8

234

0.75

312
406

0.7
0.65
0

100

200

300

Piping equivalent length

400

500

600 ft.

Ref:PUHY_THMU_C30_USDB_P312

Y-SERIES (Feb. 2009)

Y-69

Y-SERIES

Cooling capacity correction factor

7. CAPACITY TABLES

DATA U4

7-3-2. Heating Capacity Correction


PUHY-P264,288,312TSHMU/YSHMU

PUHY-P72, 96THMU/YHMU

1.00
Heating capacity correction factor

Heating capacity correction factor

0.95

0.90
50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Ref:PUHY-THMU_C30_USDB_P264-312

PUHY-P336,360TSHMU/YSHMU

1.00

1.00
Heating capacity correction factor

Heating capacity correction factor

Ref:PUHY-THMU_C30_USDB_P72-96

PUHY-P120,144,168T(S)HMU/Y(S)HMU

0.95

0.90
0

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Ref:PUHY-THMU_C30_USDB_P120-168

PUHY-P192,216,240TSHMU/YSHMU
1.00

0.95

0.90
0

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Y-70

0.95

0.90
0

Heating capacity correction factor

Y-SERIES

1.00

Ref:PUHY-THMU_C30_USDB_P192-240

Y-SERIES (Feb. 2009)

0.95

0.90
0

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Ref:PUHY-THMU_C30_USDB_P336-360

7. CAPACITY TABLES

DATA U4

7-3-3. How to Obtain the Equivalent Piping Length

bends in
bends in
bends in
bends in
bends in
bends in

Y-SERIES

bends in
bends in
bends in
bends in

7-4. Correction at Frost and Defrost


Due to frost on the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit should be
considered by multiplying the correction factor, which is shown in the table below.
Correction Factor Table when Frost and Defrost Occurs

WB
WB

Y-SERIES (Feb. 2009)

Y-71

7. CAPACITY TABLES

DATA U4

7-5. Operation Temperature Range


Cooling

Y-SERIES

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

25
77

30
86

35
95

40
104

45
113

50
122

25
77

30
86

35
95

40
104

45
113

50
122

Outdoor temperature

Heating

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

Outdoor temperature
Ref.: tr-ygm-y
* Tables above show published performance operation range. Units will try to continue to cool and heat above and below temperature range
shown, but there is no published performance data at these ranges.

Y-72

Y-SERIES (Feb. 2009)

8. OPTIONAL PARTS

DATA U4

8-1. Branch Joint


Piping for CITY MULTI systems can be easily performed with branch joints and headers provided by MITSUBISHI ELECTRIC
CORP. For PUHY-P-T(S)HMU/Y(S)HMU, the following sets of branch joints are available. Details for installing the branch joint
sets are found in the System Design section, or in the Branch Joint Installation Manual.

Ref.: CMY_Y102S_G2_EXD_EUDB_SI
in.

CMY-Y102S-G2
For Gas pipe:

For Liquid pipe:


<Reducer Pipe (Accessory)>

5/8

3/8

3/4

3/4

15/16

1-3/16

<Reducer pipe (Accessory)>

1/2
1-15/16

3/4

5-31/32

3/8

3/8

3/8

5/8

Y-SERIES

5/8

1/4
1-15/16

( 2 Pcs.)

2-1/2
( 2 Pcs.)

3/4
ID: Inner Diameter

1/2

OD: Outer Diameter


2-1/2
Ref.: CMY_Y102L_G2_EXD_EUDB_SI
in.

CMY-Y102L- G2
For Gas pipe:

For Liquid pipe:

<Reducer Pipe (Accessory)>

3/4"

5/8"

3/4"

1/2"

1"

<Reducer Pipe (Accessory)>

7/8"

2-15/32"

1"

1"

3/4"

2-15/32"

1/2"
1-1/8"

2-15/32"

5-31/32"

1"

13/16"

1-9/16"

3/4"
3/8"
1/2"

2-15/32"

7/8"

( 2 Pcs.)

1"

1-15/16"
( 2 Pcs.)

4"
5/8"

3/8"

2-15/32"
( 2 Pcs.)

1"
ID: Inner Diameter

OD: Outer Diameter

3/8"

1/2"

1/4"

2-15/32"

3/4"

1-15/16"

2-15/32"
( 2 Pcs.)

CMY-Y202-G2

Ref.: CMY_Y202_G2_EXD_EUDB_SI
in.

For Gas pipe:

<Reducer Pipe (Accessory)>

7/8"

3/4"

1"

1"

2-15/32"
3/4"

2-15/32"

1/2"

5/8"

1/2"

5/8"

5/8"

1-15/16"

7/8"

1"

<Reducer(Accessory)>

1/2"
29/32"

5/8"

3/4"

3/4"
1-9/16"

For Liquid pipe:

1/2"

4"

3/8"
1-15/16"

5-31/32"

2-15/32"
1"

1/2"

2-15/32"

1-1/8"

1"

3/4"

1/4"
1-15/16"

5/8"

3/8"

2-15/32"

2-15/32"

1-15/16"

( 3 Pcs.)

ID: Inner Diameter

OD: Outer Diameter

CMY-Y302-G2

Ref.: CMY_Y302_G2_EXD_EUDB_SI
in.

1-3/8"
2-3/4"

1-13/16"

For Liquid pipe:

<Reducer pipe (Accessory)>

1-1/4"

1-1/4"

1"

( 2 Pcs.)

1-1/8"

1"
1"

1-1/4"

1-1/4"

2-3/4"

1-1/8"

1"
6-3/4"
2-1/2"

1-1/4"

1"
1"

<Reducer pipe (Accessory)>

7/8"

5/8"

2-1/2"

3/4"
2-1/2"

5/8"

5/8"
1-3/16"

For Gas pipe:

3/4"

3/4"

3/4"

5-31/32"

3/4"
5/8"

3/8"
1-15/16"

5/8"

2-3/4"

OD: Outer Diameter

1/2"
2-1/2"

1/2"
2-1/2"

ID: Inner Diameter

5/8"

2-1/2"

2-1/2"

1-5/8"

1/2"

1-15/16"

1/4"

( 2 Pcs.)
1-15/16"

Y-SERIES (Feb. 2009)

Y-73

8. OPTIONAL PARTS
8-2. Headers

DATA U4

Piping for CITY MULTI systems can be easily performed with branch joints and headers provided by MITSUBISHI ELECTRIC
CORP. For PUHY-P-T(S)HMU/Y(S)HMU, the following sets of headers are available. Details for installing the headers are found
in the System Design section, or in the Outdoor Units Installation Manual.
Ref.: W901636
in.

CMY-Y104-G
For gas pipe:

Y-SERIES

<Reducer(Accessory)>

For liquid pipe:


<Reducer(Accessory)>

Ref.: W901637
in.

CMY-Y108-G
For gas pipe:
<Reducer(Accessory)>

For liquid pipe:


<Reducer(Accessory)>

Ref.: W901638
in.

CMY-Y1010-G
For gas pipe:
<Reducer(Accessory)>

For liquid pipe:


<Reducer(Accessory)>

Y-74

Y-SERIES (Feb. 2009)

8. OPTIONAL PARTS

DATA U4

8-3. Outdoor Twinning Kit


The outdoor twinning kit is needed to PUHY-P-TSHMU/YSHMU to combine the refrigerant flows of the PUHY-P-THMU/YHMU
units.
Ref.: CMY_Y100VBK2_EXD_EUDB_SI
in.

CMY-Y100VBK2
For Gas pipe:

For Liquid pipe:


19-29/32"

<Reducer(Accessory)>

7-7/32"
1"

1/2"

1/2"
5/8"

1/2"

Local brazing
1/2"

6-5/16"

1-1/8"
7/8"

Note 2 13-15/32"

Distributer

Note 2
3-9/32"

Pipe cover
(Dot-dashed part)

1"

1/2"

3/4"

7/8"

2-15/32"
(2 pcs.)

2-15/32"

Distributer

23-5/32"

1/2"
1-15/16"

1-1/8"

7/8"
5/8"

1-1/8"

5/8"

3/8"
1-15/16"
(2 pcs.)

9-1/2"

ID: Inner Diameter

OD: Outer Diameter

Ref.: CMY_Y300VBK2_EXD_EUDB_SI
in.

CMY-Y300VBK2
For Gas pipe:

For Liquid pipe:

19-15/16"

<Deformed pipe(Accessory)>

1-1/8"

1-1/2"

1-1/8"
7-9/16"

Note 2
13-3/8"
22-15/16"
19-11/16"

1"

1-1/8"

5/8"

Pipe cover
(Dot-dashed part)
Local brazing

Pipe cover
(Dot-dashed part)
Distributer
9-11/16"
7-5/16"
1/2"
Local brazing

3/4"
Note 2
3-3/8"

Note 2
13-5/16"

1"
23-1/16"

ID: Inner Diameter

Note 2
3-3/8"

7/8"

1-1/8"

Pipe cover
(Dot-dashed part)
Distributer
9-5/8"

3/8"

5/8"
1-15/16"

5/8"
1/2"

3/8"

1-1/2"

1-3/8"

1/2"
1-15/16"
2-3/4"
1/2"

1-1/8"
1-3/8"

1-15/16"

2-1/2"
(3 pcs.)

6-7/16"

1-1/8"

3/4"

1-1/8"
Distributer

4-9/16"

3/4"

1/2"

5/8"

2-3/4"

Local brazing

3-7/8"

3/4"

1-3/8"
1-1/2"

1-5/8"

5/8"

5/8"
6-7/16"

1-1/4"

Pipe cover
(Dot-dashed part)
Local brazing

5/8"

1/2"
1-15/16"
(2 pcs.)

1/2"

1-1/8"

3/4"

2-1/2"
(2 pcs.)

Distributer

OD: Outer Diameter

Note 1. Reference the angle of the branch pipe below the fig.

15

Distributer

The angle of the branch pipe for hign pressure is within 15 against the horizontal plane.
2. Use the attached pipe to braze the port-opening of the distributer.
3. Pipe diameter is indicated by inside diameter.
4. Only use the Twinning pipe by Mitsubishi (optional parts).

Y-SERIES (Feb. 2009)

Y-75

Y-SERIES

3-7/8"

7/8"
Pipe cover
(Dot-dashed part)
Local brazing

R2-SERIES

DATA U4

OUTDOOR UNITS


1. SPECIFICATIONS....................................................................................................................................................... R2-2
1-1. PURY-P72~240T(S)HMU-A (-BS) 208 / 230V Specifications....................................................................... R2-2
1-2. PURY-P72~240Y(S)HMU-A (-BS) 460V Specifications................................................................................ R2-9
1-3. Energy Efficiencies..................................................................................................................................... R2-16
2. EXTERNAL DIMENSIONS........................................................................................................................................ R2-17
3. Center of Gravity............................................................................................................................................. R2-31
4. ELECTRICAL WIRING DIAGRAMS.......................................................................................................................... R2-32
5. Refrigerant Circuit Diagrams and Thermal Sensors........................................................................ R2-35
6. SOUND Pressure LEVELS.................................................................................................................................. R2-36
7. Capacity Tables................................................................................................................................................... R2-39
7-1. Correction by Temperature.......................................................................................................................... R2-39
7-2. Correction by Total Indoor........................................................................................................................... R2-42
7-3. Correction by Refrigerant Piping Length..................................................................................................... R2-46
7-4. Correction at Frost and Defrost................................................................................................................... R2-48
7-5. Operation Temperature Range.................................................................................................................... R2-48

8. OPTIONAL PARTS.................................................................................................................................................... R2-49


8-1. Joint............................................................................................................................................................ R2-49
8-2. Twinning Kit................................................................................................................................................. R2-50
8-3. Joint Adapter Kit CMY-R160J for BC Controller.......................................................................................... R2-51

R2-SERIES (Feb. 2009)

R2-1

R2-SERIES

1. Specifications

DATA U4

1-1. PURY-P72~360T(S)HMU-A Specifications


Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(208 / 230)
Indoor
Outdoor

R2-SERIES
(208
/ 230V)
R2-SERIES

Heating capacity (Nominal) *2

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW

Power input
Current input
A
(208 / 230)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Liquid
pipe
in. (mm)
Refrigerant piping
diameter
Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Fan
Control, Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Compressor
Starting method
Motor output
kW
Case heater
kW
Lubricant
External finish
External dimension H x W x D

in.
mm

High pressure protection


Protection devices

Refrigerant

Compressor / Fan
Inverter
Type x original charge
Control
lbs (kg)

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory

Optional parts

Remark

PURY-P72THMU-A(-BS)

PURY-P96THMU-A(-BS)

3-phase 3-wire 208 / 230V 10% 60Hz

3-phase 3-wire 208 / 230V 10% 60Hz

72,000
21.1
5.55 *3

96,000
28.1
8.35 *3

17.1 / 15.4 *3

25.7 / 23.2 *3

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
80,000
23.4
6.04 *3

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
108,000
31.7
8.66 *3

18.6 / 16.8 *3

26.7 / 24.1 *3

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 18

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 24

58.0

58.0

5/8"(15.88) Brazed
3/4"(19.05) Brazed
3/4"(19.05) Brazed
7/8"(22.2) Brazed
Propeller fan x 1
Propeller fan x 1
6,550
7,750
185
220
3,080
3,670
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
0.92
0.92
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
19-100%
19-100%
Inverter
Inverter
4.4
7.0
0.051(230 V)
0.057(230 V)
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder coating
coating for -BS type) *5 <MUNSELL 5Y 8/1>
for -BS type) *5 <MUNSELL 5Y 8/1>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
R410A x 23 lbs + 2 oz (10.5kg)
R410A x 26 lbs + 1 oz (11.8kg)
Indoor LEV and BC controller
Indoor LEV and BC controller
519(235)
585(265)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
WKB94L662
WKB94L663
WKE94C209
WKE94C210
Installation Manual
Installation Manual
Details refer to External Drw
Details refer to External Drw
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-R160J
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-R160J
BC controller: CMBBC controller: CMBP105,106,108,1010,1013,1016NU-G
P105,106,108,1010,1013,1016NU-G
Main BC controller: CMB-P108,1010,1013,1016NU-GA Main BC controller: CMB-P108,1010,1013,1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMBSub BC controller: CMB-P104, 108NU-GB, CMBP1016NU-HB
P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System Design
section, p. 336.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P72THMU: MCA = 24 / 22A, Max. Fuse Size: 30 / 30A; PURY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 30 / 30A.

R2-2

R2-SERIES (Feb. 2009)

1. Specifications

DATA U4

Model

PURY-P120THMU-A(-BS)

Power source

3-phase 3-wire 208 / 230V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(208 / 230)
Indoor
Outdoor

Heating capacity (Nominal) *2

BTU / h
kW
kW

120,000
35.2
10.59 *3

32.6 / 29.5 *3

W.B.
D.B.
BTU / h
kW
kW

Optional parts

Remark

31.3 / 28.3 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 30
60.0
3/4"(19.05) Brazed
1-1/8"(28.58) Brazed
Propeller fan x 1
7,950
225
3,750
Inverter-control, Direct-driven by motor
0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
17-100%
Inverter
8.1
0.057(230 V)
MEL32
Pre-coated galvanized steel sheet (+powder coating for -BS type) *5 <MUNSELL 5Y 8/1>
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
R410A x 26 lbs + 1 oz (11.8kg)
Indoor LEV and BC controller
585(265)
Salt-resistant cross fin & copper tube
Auto-defrost mode (Reversed refrigerant cycle)
WKB94L663
WKE94C210
Installation Manual
Details refer to External Drw
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-R160J
BC controller: CMB-P105, 106, 108, 1010, 1013, 1016NU-G
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P120THMU: MCA = 43 / 40A, Max. Fuse Size: 50 / 50A.

R2-SERIES (Feb. 2009)

R2-3

R2-SERIES
R2-SERIES
(208
/ 230V)

Power input
Current input
A
(208 / 230)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Liquid pipe
in. (mm)
Refrigerant piping
diameter
Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Fan
Control, Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Compressor
Starting method
Motor output
kW
Case heater
kW
Lubricant
External finish
in.
External dimension H x W x D
mm
High pressure protection
Protection devices
Compressor / Fan
Inverter
Type x original charge
Refrigerant
Control
Net weight
lbs (kg)
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Wiring
Drawing
Refrigerant cycle
Document
Standard attachment
Accessory

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
120,000
35.2
10.16 *3

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

R2-SERIES
R2-SERIES
(208
/ 230V)

Heating capacity (Nominal) *2


Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

dB <A>
in. (mm)

PURY-P144TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
144,000
42.2
11.32 *3
34.9 / 31.5 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
160,000
46.9
12.44 *3
38.3 / 34.6 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
10-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 36
61.0
7/8"(22.2) Brazed

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

PURY-P72THMU-A(-BS)
PURY-P72THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
6,550
6,550
Airflow rate
m3 / min
185
185
Fan
L/s
3,080
3,080
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
4.4
4.4
Case heater
kW
0.051(230 V)
0.051(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5
coating for -BS type) *5
<MUNSELL 5Y 8/1>
<MUNSELL 5Y 8/1>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 23 lbs + 2 oz (10.5kg)
R410A x 23 lbs + 2 oz (10.5kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
519(235)
519(235)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
5/8"(15.88)Brazed
5/8"(15.88)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L664
Drawing
Wiring
WKE94C209
WKE94C209
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System
Remark
Design section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series
System Design section, p. 336.
Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P72THMU: MCA = 24 / 22A, Max. Fuse Size: 30 / 30A; PURY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PURY-P120THMU: MCA = 43 / 40A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-4

R2-SERIES (Feb. 2009)

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

cfm
m3 / min
L/s
Control , Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Starting method
Motor output
kW
Case heater
kW
Lubricant

Airflow rate
Fan

Compressor

External finish
External dimension H x W x D

Protection
devices

Refrigerant

in.
mm

High pressure protection


Compressor / Fan
Inverter
Type x original charge
Control

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
Defrosting method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory

Optional parts

lbs (kg)

in. (mm)
in. (mm)

PURY-P72THMU-A(-BS)
PURY-P96THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
6,550
7,750
185
220
3,080
3,670
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
0.92
0.92
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Inverter
Inverter
4.4
7.0
0.051(230 V)
0.057(230 V)
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
R410A x 23 lbs + 2 oz (10.5kg)
R410A x 26 lbs + 1 oz (11.8kg)
Indoor LEV and BC controller
519(235)
585(265)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
5/8"(15.88)Brazed
3/4"(19.05)Brazed
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Auto-defrost mode (Reversed refrigerant cycle)
WKB94L665
WKE94C209
WKE94C210
Installation Manual
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.

Remark

Note:
Indoor:
Outdoor:

*1 Nominal cooling conditions


80degF D.B./ 67degF W.B.
(26.7degC D.B./ 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

Unit converter
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P72THMU: MCA = 24 / 22A, Max. Fuse Size: 30 / 30A; PURY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PURY-P120THMU: MCA = 43 / 40A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-SERIES (Feb. 2009)

R2-5

R2-SERIES
R2-SERIES
(208
/ 230V)

Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

PURY-P168TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
168,000
49.2
14.19 *3
43.7 / 39.5 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
188,000
55.1
15.14 *3
46.6 / 42.2 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
8-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 42
61.0
7/8"(22.2) Brazed

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

R2-SERIES
R2-SERIES
(208
/ 230V)

Heating capacity (Nominal) *2


Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

dB <A>
in. (mm)

PURY-P192TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
192,000
56.3
17.04 *3
52.5 / 47.5 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
200,000
58.6
15.85 *3
48.8 / 44.2 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 48
62.0
7/8"(22.2) Brazed

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Set Model
Model

PURY-P96THMU-A(-BS)
PURY-P96THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,750
7,750
Airflow rate
m3 / min
220
220
Fan
L/s
3,670
3,670
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
7.0
7.0
Case heater
kW
0.057(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 26 lbs + 1 oz (11.8kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
585(265)
585(265)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L666
Drawing
Wiring
WKE94C210
WKE94C210
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
Remark
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.
Type x Quantity

Note:
Indoor:
Outdoor:

*1 Nominal cooling conditions


80degF D.B./ 67degF W.B.
(26.7degC D.B./ 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

Unit converter
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P72THMU: MCA = 24 / 22A, Max. Fuse Size: 30 / 30A; PURY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PURY-P120THMU: MCA = 43 / 40A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-6

R2-SERIES (Feb. 2009)

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

PURY-P96THMU-A(-BS)
PURY-P120THMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,750
7,950
Airflow rate
m3 / min
220
225
Fan
L/s
3,670
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
7.0
8.1
Case heater
kW
0.057(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 26 lbs + 1 oz (11.8kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
585(265)
585(265)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
in. (mm)
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
1-1/8"(28.58)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L666
Drawing
Wiring
WKE94C210
WKE94C210
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
Remark
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.
Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PURY-P72THMU: MCA = 24 / 22A, Max. Fuse Size: 30 / 30A; PURY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PURY-P120THMU: MCA = 43 / 40A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-SERIES (Feb. 2009)

R2-7

R2-SERIES
R2-SERIES
(208
/ 230V)

Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

PURY-P216TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
216,000
63.3
19.32 *3
59.5 / 53.8 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
228,000
66.8
19.38 *3
59.7 / 54.0 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 2 to 50 (Connectable branch pipe number is max. 48.)
62.0
1-1/8"(28.58) Brazed

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (208 / 230)
Indoor
Outdoor

R2-SERIES
R2-SERIES
(208
/ 230V)

Heating capacity (Nominal) *2


Power input
Current input (208 / 230)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

Compressor

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

cfm
m3 / min
L/s
Control , Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Starting method
Motor output
kW
Case heater
kW
Lubricant

Airflow rate
Fan

dB <A>
in. (mm)

PURY-P240TSHMU-A(-BS)
3-phase 3-wire 208 / 230V 10% 60Hz
240,000
70.3
21.61 *3
66.6 / 60.2 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
240,000
70.3
20.92 *3
64.5 / 58.3 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 2 to 50 (Connectable branch pipe number is max. 48.)
63.0
1-1/8"(28.58) Brazed

PURY-P120THMU-A(-BS)
Propeller fan x 1
7,950
225
3,750
Inverter-control, Direct-driven by motor
0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
Inverter
8.1
0.057(230 V)
MEL32

PURY-P120THMU-A(-BS)
Propeller fan x 1
7,950
225
3,750
Inverter-control, Direct-driven by motor
0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
Inverter
8.1
0.057(230 V)
MEL32

Pre-coated galvanized steel sheet (+powder


Pre-coated galvanized steel sheet (+powder
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 26 lbs + 1 oz (11.8kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
585(265)
585(265)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
in. (mm)
3/4"(19.05)Brazed
3/4(19.05)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
1-1/8"(28.58)Brazed
1-1/8"(28.58)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L666
Drawing
Wiring
WKE94C210
WKE94C210
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
Remark
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.
External finish

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PURY-P72THMU: MCA = 24 / 22A, Max. Fuse Size: 30 / 30A; PURY-P96THMU: MCA = 35 / 32A, Max. Fuse Size: 40 / 40A;
PURY-P120THMU: MCA = 43 / 40A, Max. Fuse Size: 50 / 50A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-8

R2-SERIES (Feb. 2009)

1. Specifications
1-2. PURY-P72~360Y(S)HMU-A Specifications
Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(460)
Indoor
Outdoor

Heating capacity (Nominal) *2

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW

External finish
External dimension H x W x D

in.
mm

High pressure protection


Protection devices

Refrigerant

Compressor / Fan
Inverter
Type x original charge
Control
lbs (kg)

Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory

Optional parts

Remark

PURY-P72YHMU-A(-BS)

PURY-P96YHMU-A(-BS)

3-phase 3-wire 460V 10% 60Hz

3-phase 3-wire 460V 10% 60Hz

72,000
21.1
5.55 *3

96,000
28.1
8.27 *3

7.7 *3

11.6 *3

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
80,000
23.4
6.04 *3

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
108,000
31.7
8.66 *3

8.4 *3

12.0 *3

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 18

59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 24

58.0

58.0

5/8"(15.88) Brazed
3/4"(19.05) Brazed
3/4"(19.05) Brazed
7/8"(22.2) Brazed
Propeller fan x 1
Propeller fan x 1
6,550
7,750
185
220
3,080
3,670
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
0.92
0.92
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORP.
AC&R Works, MITSUBISHI ELECTRIC CORP.
19-100%
19-100%
Inverter
Inverter
4.4
7.0
0.051(230 V)
0.057(230 V)
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder coating
coating for -BS type) *5 <MUNSELL 5Y 8/1>
for -BS type) *5 <MUNSELL 5Y 8/1>
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at
High pressure sensor, High pressure switch at
4.15MPa (601 psi)
4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
R410A x 23 lbs + 2 oz (10.5kg)
R410A x 26 lbs + 1 oz (11.8kg)
Indoor LEV and BC controller
Indoor LEV and BC controller
552(250)
618(280)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
WKB94L667
WKB94L668
WKE94C212
WKE94C212
Installation Manual
Installation Manual
Details refer to External Drw
Details refer to External Drw
Joint: CMY-Y102S-G2, CMY-Y102L-G2,
Joint: CMY-Y102S-G2, CMY-Y102L-G2,
CMY-R160J
CMY-R160J
BC controller: CMB-P105, 106, 108, 1010, 1013,
BC controller: CMB-P105, 106, 108, 1010, 1013,
1016NU-G
1016NU-G
Main BC controller: CMB-P108, 1010, 1013,
Main BC controller: CMB-P108, 1010, 1013,
1016NU-GA
1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMBSub BC controller: CMB-P104, 108NU-GB, CMBP1016NU-HB
P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System Design
section, p. 336.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PURY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PURY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A.

R2-SERIES (Feb. 2009)

R2-9

R2-SERIES
R2-SERIES
(460V)

Power input
Current input
A
(460)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Liquid
pipe
in. (mm)
Refrigerant piping
diameter
Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Fan
Control, Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Compressor
Starting method
Motor output
kW
Case heater
kW
Lubricant

DATA U4

1. Specifications

DATA U4

Model

PURY-P120YHMU-A(-BS)

Power source

3-phase 3-wire 460V 10% 60Hz

Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input
(460)
Indoor
Outdoor

R2-SERIES
R2-SERIES
(460V)

Heating capacity (Nominal) *2

BTU / h
kW
kW

120,000
35.2
10.59 *3

14.7 *3

W.B.
D.B.
BTU / h
kW
kW

Power input
Current input
A
(460)
Indoor
D.B.
Temp. range of
heating
Outdoor
W.B.
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in
dB <A>
anechoic room)
Liquid
pipe
in.
(mm)
Refrigerant piping
diameter
Gas pipe
in. (mm)
Type x Quantity
cfm
Air flow rate
m3 / min
L/s
Fan
Control, Driving mechanism
Motor output
kW
External static pressure *4
Type x Quantity
Manufacturer
Operating Range
Compressor
Starting method
Motor output
kW
Case heater
kW
Lubricant
External finish
in.
External dimension H x W x D
mm
High pressure protection
Protection devices
Compressor / Fan
Inverter
Type x original charge
Refrigerant
Control
Net weight
lbs (kg)
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrost method
External
Wiring
Drawing
Refrigerant cycle
Document
Standard attachment
Accessory

Optional parts

Remark

59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
120,000
35.2
10.16 *3
14.1 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 30
60.0
3/4"(19.05) Brazed
1-1/8"(28.58) Brazed
Propeller fan x 1
7,950
225
3,750
Inverter-control, Direct-driven by motor
0.92
0 in.WG (0 Pa) *4
Inverter scroll hermetic compressor x 1
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
17-100%
Inverter
8.1
0.057(230 V)
MEL32
Pre-coated galvanized steel sheet (+powder coating for -BS type) *5 <MUNSELL 5Y 8/1>
64-31/32" x 48-1/16" x 29-15/16"
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection / Thermal switch
Over-heat protection, Over-current protection
R410A x 26 lbs + 1 oz (11.8kg)
Indoor LEV and BC controller
618(280)
Salt-resistant cross fin & copper tube
Auto-defrost mode (Reversed refrigerant cycle)
WKB94L668
WKE94C212
Installation Manual
Details refer to External Drw
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-R160J
BC controller: CMB-P105, 106, 108, 1010, 1013, 1016NU-G
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System Design
section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

PURY-P120YHMU: MCA = 20A, Max. Fuse Size: 25A.

R2-10

R2-SERIES (Feb. 2009)

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Set Model
Model

PURY-P72YHMU-A(-BS)
PURY-P72YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
6,550
6,550
Airflow rate
m3 / min
185
185
Fan
L/s
3,080
3,080
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP. AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
4.4
4.4
Case heater
kW
0.051(230 V)
0.051(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 36-1/4" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 920 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
Compressor / Fan
devices
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 23 lbs + 2 oz (10.5kg)
R410A x 23 lbs + 2 oz (10.5kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
552(250)
552(250)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
in. (mm)
5/8"(15.88)Brazed
5/8"(15.88)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L670
Drawing
Wiring
WKE94C212
WKE94C212
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System
Remark
Design section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.
Type x Quantity

Note:
Indoor:
Outdoor:

*1 Nominal cooling conditions


80degF D.B./ 67degF W.B.
(26.7degC D.B./ 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

Unit converter
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PURY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PURY-P120YHMU: MCA = 20A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-SERIES (Feb. 2009)

R2-11

R2-SERIES
R2-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

PURY-P144YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
144,000
42.2
11.32 *3
15.7 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
160,000
46.9
12.44 *3
17.3 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
10-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 36
61.0
7/8"(22.2) Brazed

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

R2-SERIES
R2-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

dB <A>
in. (mm)

PURY-P168YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
168,000
49.2
14.19 *3
19.7 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
188,000
55.1
15.14 *3
21.1 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
8-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 42
61.0
7/8"(22.2) Brazed

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Set Model
Model

PURY-P72YHMU-A(-BS)
PURY-P96YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
6,550
7,750
Airflow rate
m3 / min
185
220
Fan
L/s
3,080
3,670
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP. AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
4.4
7.0
Case heater
kW
0.051(230 V)
0.057(230 V)
Lubricant
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 36-1/4" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 920 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 23 lbs + 2 oz (10.5kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
552(250)
618(280)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
in. (mm)
5/8"(15.88)Brazed
3/4"(19.05)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
3/4"(19.05)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L671
Drawing
Wiring
WKE94C212
WKE94C212
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Type x Quantity

Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System
Design section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.

Remark

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PURY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PURY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PURY-P120YHMU: MCA = 20A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-12

R2-SERIES (Feb. 2009)

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

PURY-P96YHMU-A(-BS)
PURY-P96YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,750
7,750
Airflow rate
m3 / min
220
220
Fan
L/s
3,670
3,670
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP. AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
7.0
7.0
Case heater
kW
0.057(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 26 lbs + 1 oz (11.8kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
618(280)
618(280)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
7/8"(22.2)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L672
Drawing
Wiring
WKE94C212
WKE94C212
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System
Remark
Design section, pgs. 296-303.
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336
Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PURY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PURY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PURY-P120YHMU: MCA = 20A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-SERIES (Feb. 2009)

R2-13

R2-SERIES
R2-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

PURY-P192YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
192,000
56.3
17.04 *3
23.7 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
200,000
58.6
15.85 *3
22.1 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 1 to 48
62.0
7/8"(22.2) Brazed

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

R2-SERIES
R2-SERIES
(460V)

Heating capacity (Nominal) *2


Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units

dB <A>
in. (mm)

PURY-P216YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
216,000
63.3
19.32 *3
26.9 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
228,000
66.8
19.38 *3
27.0 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 2 to 50 (Connectable branch pipe number is max. 48.)
62.0
1-1/8"(28.58) Brazed

in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

Set Model
Model

PURY-P96YHMU-A(-BS)
PURY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,750
7,950
Airflow rate
m3 / min
220
225
Fan
L/s
3,670
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP. AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
7.0
8.1
Case heater
kW
0.057(230 V)
0.057(230 V)
MEL32
MEL32
Lubricant
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
devices
Compressor / Fan
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 26 lbs + 1 oz (11.8kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
618(280)
618(280)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
7/8"(22.2)Brazed
1-1/8"(28.58)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L672
Drawing
Wiring
WKE94C212
WKE94C212
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System
Design section, pgs. 296-303.
Remark
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.
Type x Quantity

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PURY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PURY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PURY-P120YHMU: MCA = 20A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-14

R2-SERIES (Feb. 2009)

1. Specifications

DATA U4

Model
Power source
Cooling capacity (Nominal) *1

Temp. range of
cooling

Power input
Current input (460)
Indoor
Outdoor

Heating capacity (Nominal) *2

dB <A>
in. (mm)
in. (mm)

1-1/8"(28.58) Brazed

BTU / h
kW
kW
A
W.B.
D.B.
BTU / h
kW
kW
A
D.B.
W.B.

PURY-P120YHMU-A(-BS)
PURY-P120YHMU-A(-BS)
Propeller fan x 1
Propeller fan x 1
cfm
7,950
7,950
Airflow rate
m3 / min
225
225
Fan
L/s
3,750
3,750
Control , Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92
0.92
External static pressure *4
0 in.WG (0 Pa) *4
0 in.WG (0 Pa) *4
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacturer
AC&R Works, MITSUBISHI ELECTRIC CORP. AC&R Works, MITSUBISHI ELECTRIC CORP.
Starting method
Inverter
Inverter
Compressor
Motor output
kW
8.1
8.1
Case heater
kW
0.057(230 V)
0.057(230 V)
Lubricant
MEL32
MEL32
Pre-coated galvanized steel sheet (+powder
Pre-coated galvanized steel sheet (+powder
External finish
coating for -BS type) *5 <MUNSELL 5Y 8/1>
coating for -BS type) *5 <MUNSELL 5Y 8/1>
in.
64-31/32" x 48-1/16" x 29-15/16"
64-31/32" x 48-1/16" x 29-15/16"
External dimension H x W x D
mm
1,650 x 1,220 x 760
1,650 x 1,220 x 760
High pressure sensor, High pressure switch at High pressure sensor, High pressure switch at
High pressure protection
4.15MPa (601 psi)
4.15MPa (601 psi)
Protection
Compressor / Fan
devices
Over-heat protection / Thermal switch
Over-heat protection / Thermal switch
Inverter
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Type x original charge
R410A x 26 lbs + 1 oz (11.8kg)
R410A x 26 lbs + 1 oz (11.8kg)
Refrigerant
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
618(280)
618(280)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
in. (mm)
3/4"(19.05)Brazed
3/4"(19.05)Brazed
Refrigerant piping diameter Liquid pipe
from Module to Twinning Kit Gas pipe
in. (mm)
1-1/8"(28.58)Brazed
1-1/8"(28.58)Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
External
WKB94L672
Drawing
Wiring
WKE94C212
WKE94C212
Refrigerant cycle
Document
Installation Manual
Standard attachment
Accessory
Details refer to External Drw
Outdoor Twinning kit: CMY-R100VBK
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2, CMY-R160J
Optional parts
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA
Sub BC controller: CMB-P104, 108NU-GB, CMB-P1016NU-HB
Details on foundation work, duct work, insullation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.
*3 For details on the electrical data needed for installing these units, see the R2-Series System
Design section, pgs. 296-303.
Remark
*4 External static pressure is adjustable via dipswitch setting (0.12 in.WG, 0.24 in.WG / 30Pa, 60Pa).
*5 For information on standard anti-corrosion protection and -BS treatment, see the R2-Series System
Design section, p. 336.
Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding


variation.

PURY-P72YHMU: MCA = 11A, Max. Fuse Size: 15A; PURY-P96YHMU: MCA = 16A, Max. Fuse Size: 20A;
PURY-P120YHMU: MCA = 20A, Max. Fuse Size: 25A.
These electrical specifications apply to the individual units that make up the larger, combined units (PURY-P144-P240).

R2-SERIES (Feb. 2009)

R2-15

R2-SERIES
R2-SERIES
(460V)

Power input
Current input (460)
Indoor
Temp. range of
heating
Outdoor
System Compressor Operating Range
Total capacity
Indoor unit
connectable
Model / Quantity
Sound pressure level (measured in anechoic room)
Refrigerant piping diameter Liquid pipe
from Twinning Kit to Indoor
Gas pipe
Units
Set Model
Model
Type x Quantity

PURY-P240YSHMU-A(-BS)
3-phase 3-wire 460V 10% 60Hz
240,000
70.3
21.61 *3
30.1 *3
59 to 75degF(15 to 24degC)
23 to 109degF(-5 to 43degC)
240,000
70.3
20.92 *3
29.1 *3
59 to 81degF(15 to 27degC)
-4 to 60degF(-20 to 15.5degC)
9-100%
50 to 150 % of outdoor unit capacity
P06 to P96 / 2 to 50 (Connectable branch pipe number is max. 48.)
63.0
1-1/8"(28.58) Brazed

1. Specifications

DATA U4

1-3. energy Efficiencies


Model Number

Nominal Cooling
Capacity

Cooling
EER

Heating 47 F
COP

Heating 17 F
COP

IPLV

HEAT RECOVERY Models 208/230V and 460V, 3-phase

R2-SERIES

PURY-P72T/YHMU-A

72,000 Btu/h

12.0

3.5

2.4

15.3
16.2

PURY-P96T/YHMU-A

96,000 Btu/h

11.6

3.3

2.3

PURY-P120T/YHMU-A

120,000 Btu/h

10.5

3.2

2.2

17.4

PURY-P144T/YSHMU-A

144,000 Btu/h

12.0

3.5

2.4

15.3

PURY-P168T/YSHMU-A

168,000 Btu/h

11.8

3.4

2.3

15.8

PURY-P192T/YSHMU-A

192,000 Btu/h

11.6

3.3

2.3

16.2

PURY-P216T/YSHMU-A

216,000 Btu/h

11.0

3.3

2.2

16.9

PURY-P240T/YSHMU-A

240,000 Btu/h

10.5

3.2

2.2

17.4

These units were tested per the guidelines provided by the Department of Energy (DOE) in the Federal Register / Vol. 73 No. 239 /
Thursday, December 11, 2008 / Notices / pages 75408 75417. Testing was done in accordance with the DOE guidelines and ARI Draft
Standard 1230, which is based on ARI Standard 340/360 and ISO Standard 13256-1. All units meet or exceed ASHRAE 90.1 efficiency
requirements.

Important: Interpreting the Test Results


COP and EER
Testing on these units was performed at full load per the test standard so the Energy Efficiency Ratio (EER) and Coefficient of
Performance (COP) are based on a fixed energy consumption level. Because of this, many of the energy saving benefits of these Variable
Refrigerant Flow Zoning (VRFZ ) systems are not truly reflected in these numbers. Some of the other ways these units maximize energy
use, which are not included in EER and COP are:
1. Inverter driven compressor varies the system capacity based on load demands. Capacity can vary from 100% down to 16%.
2. Smart coil technology automatically varies the indoor unit capacity based on space cooling or heating requirements.
3. The CITY MULTI VRFZ systems can take advantage of building load diversity by using up 130% (Y Series) and 150% (R2 Series)
connected indoor unit capacity. In many cases this can result in smaller capacity outdoor units required to condition the space.
4. Each R2Series system has the ability to transfer heat from one area of the building to another. As an example; at 50% heating and
50% cooling demand, no energy is rejected or absorbed from the outdoors. The energy is moved from one part of the building to another
within the system.

IPLV
Integrated Part-Load Value (IPLV) is not an ASHRAE 90.1 requirement but it better demonstrates the energy saving capabilities of the
CITY MULTI VRFZ systems by taking into account efficiencies at varying capacity conditions. However, it still doesnt account for items 2
4 above. Another important note when comparing these IPLV number to chillers is to know how the calculation/testing was done. The IPLV
values above include all power required to condition the space. Chillers that commonly use IPLV ratings often do not include other energy
consuming devices within the system when arriving at their values. Items such as pumps for water circulation and blower motors in the air
handling devices are often excluded.

R2-16

R2-SERIES (Feb. 2009)

760
(29-15/16)

Left side view

25
(1)

25
(1)

Refrigerant service
valve <Low pressure>

Refrigerant service
valve <High pressure>

55
(2-3/16)

*1.Expand the field pipes(for bottom piping and front piping)


and connect directly to the valve.

PURY-P72THMU 15.88 Brazed 19.05 Brazed


(5/8)
(3/4)

Connecting pipe specifications


Connection specifications for
the refrigerant service valve *1
High
Low
Model
pressure
pressure

55
(2-3/16)

54 (2-5/32)

Intake
air

239
(9-7/16)
261
(10-9/32)

80
(3-5/32)

Refrigerant service
valve <High pressure>

(8-23/32) 221
(9-29/32) 251
(7-11/32) 186

(8-23/32) 221

(7-15/16) 201

(7-5/16) 185

Intake
air

Control box

(8-9/16) 217
(5-3/4) 146
145 (5-23/32)
131 (5-3/16)

77 (3-1/16)

Refrigerant service
valve <Low pressure>

Bottom view

760 (29-15/16)
80
(Mounting pitch)
(3-5/32)

150 (5-29/32)
83 (3-9/32)

Front view

58 (2-5/16)
75 (2-31/32)
140 (5-17/32)

1650 (64-31/32)
7

NO.

Specifications
140 X 77 Knockout hole
(5-17/32) (3-1/16)

Front through hole


(Uses when twinning kit (optional 45 Knockout hole
(1-25/32)
parts) is mounted.)
150 X 92 Knockout hole
Bottom through hole
(5-29/32)(3-5/8)
62.7 or 34.5 Knockout hole
Front through hole
(2-15/32) (1-3/8)
43.7 or 22.2 Knockout hole
Front through hole
For wires
(1-3/4)
(7/8)
52 Knockout hole
Bottom through hole
(2-1/16)
34 Knockout hole
For transmission cables Front through hole
(1-11/32)
For pipes

Front through hole

Usage

Note 1.Please refer to the next page for information


regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service
valve with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

2 X 2-14(9/16) X 20(13/16) Oval hole

Service
panel

Intake
air

240 (9-15/32)
1410 (55-17/32)

920 (36-1/4)

Top view

760 (29-15/16)
18
(23/32)

(3-9/16) 90
145 (5-23/32)
86 (3-13/32)
92
(3-5/8)

R2-SERIES (Feb. 2009)


(28-17/32)
724 (721 ~ 727)
(28-13/32 ~ 28-5/8)
(Mounting pitch)

Discharge air

R2-SERIES

(760) (29-15/16)

PURY-P72THMU-A(-BS)

18
(23/32)

2. External Dimensions
DATA U4

Ref. : PURY_THMU-A_EXD_USDB_P72_R1
Unit : mm(in)

R2-17

(19/32)

15 min.*

50 min.*

(1-31/32)

<Top view>

50 min.*

(1-31/32)

Front

100 min.*

(11-13/16)

(17-23/32)

300 min.*

450 min.*

Unit height

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>

3
4

securely supported as shown in the right figure. (Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

2 Build the foundation in such way that the corner of the installation leg is

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit <h>

PURY-P72THMU-A(-BS)

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

<Side view>

Front

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

h
500

300 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

In case of collective installation

Front

(3-15/16)
(17-23/32)

With a space of at least


300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on
the back of the unit
the back of the unit

<To be left open>


Front

1 When multiple units are installed adjacent to each other, secure enough space to allow

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


(19/32)

(11-13/16)
(17-23/32)
15 min.*

Front

In case of single installation

Front

<To be left open>


<To be left open>

Front

1 Secure enough space around the unit as shown in the figure below.

(1-3/16)

<To be left open>


<To be left open>

Front

1.Required space around the unit

30mm max.

(11-13/16)

100 min.*
450 min.*

(11-13/16)
900 min.

300 min.*

(35-7/16)
(11-13/16)

R2-SERIES (Feb. 2009)


300 min.*

Wall <H>
300 min.*
900 min.

R2-18
(35-7/16)

R2-SERIES

2. External Dimensions
DATA U4

Ref. : PURY_THMU-A_EXD_USDB_P72_R2
Unit : mm(in)

<To be left open>

Intake
air

760
(29-15/16)

Left side view

25
(1)

25
(1)

55
(2-3/16)

263
(10-3/8)

271

(10-11/16)

80
(3-5/32)

Refrigerant service
valve <High pressure>

(10-11/16) 271
301
(11-7/8)
(8-17/32) 216

235
251

(9-9/32)
(9-29/32)

Refrigerant service
valve <High pressure>

Refrigerant service
valve <Low pressure>

Intake
air

*1.Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.

PURY-P96THMU

22.2 Brazed
19.05 Brazed (7/8)
(3/4)
28.58 Brazed
PURY-P120THMU
(1-1/8)

Connecting pipe specifications


Connection specifications for
the refrigerant service valve *1
High
Low
Model
pressure
pressure

55
(2-3/16)

54 (2-5/32)

Control box

(8-9/16) 217
(5-3/4) 146
145 (5-23/32)
131 (5-3/16)

Bottom view

1060 (41-3/4)
(Mounting pitch)

Refrigerant service
valve <Low pressure>

150 (5-29/32)
83 (3-9/32)

Front view

58 (2-5/16)
75 (2-31/32)
140 (5-17/32)

Top view

1220 (48-1/16)

77 (3-1/16)
(3-9/16) 90
145 (5-23/32)

1650 (64-31/32)
7

NO.

84 (3-5/16)

80
(3-5/32)

1 pc.
1 pc.

Specifications
140 X 77 Knockout hole
(5-17/32)(3-1/16)

Front through hole


45 Knockout hole
(Uses when twinning kit (optional
(1-25/32)
parts) is mounted.)
150 X 94 Knockout hole
Bottom through hole
(5-29/32) (3-23/32)
62.7 or 34.5 Knockout hole
Front through hole
(2-15/32) (1-3/8)
43.7 or 22.2 Knockout hole
Front through hole
For wires
(7/8)
(1-3/4)
65 Knockout hole
Bottom through hole
(2-9/16)
34 Knockout hole
For transmission cables Front through hole
(1-11/32)

Front through hole

Usage

<High pressure> Pipe (ID25.4(1) X OD19.05(3/4)) P96,P120 1 pc.


Elbow (ID19.05(3/4) X OD19.05(3/4)) P96,P120 1 pc.
Note 1.Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service
valve with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

<Accessories>
Connecting pipe
<Low pressure> Pipe (ID25.4(1) X ID22.2(7/8)) P96
Pipe (ID25.4(1) X ID28.58(1-1/8)) P120

For pipes

2 X 2-14(9/16) X 20(13/16) Oval hole

Service
panel

Intake
air

760 (29-15/16)
18
(23/32)
(28-17/32)
724 (721 ~ 727)
18
(28-13/32 ~ 28-5/8)
(23/32)
(Mounting pitch)

R2-SERIES (Feb. 2009)


94
(3-23/32)

240 (9-15/32)
1410 (55-17/32)
(760) (29-15/16)

PURY-P96,120THMU-A(-BS)

R2-SERIES

Discharge air

2. External Dimensions
DATA U4

Ref. : PURY_THMU-A_EXD_USDB_P96-120_R1
Unit : mm(in)

R2-19

(19/32)

15 min.*

50 min.*

(1-31/32)

<Top view>

50 min.*

(1-31/32)

Front

(17-23/32)

100 min.*

(11-13/16)
(17-23/32)

300 min.*

450 min.*

3
4

securely supported as shown in the right figure. (Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

2 Build the foundation in such way that the corner of the installation leg is

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

<Side view>

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

300 min.*
450 min.*

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.

1 When multiple units are installed adjacent to each other, secure enough space to allow
2 At least two sides must be left open.
3 As with the single installation, add the height that exceeds the height limit <h>

100 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Unit height

Front

With a space of at least

Front

Front

Front

<To be left open>


(19/32)

(11-13/16)
(17-23/32)
15 min.*

(3-15/16)
(17-23/32)

300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on


the back of the unit
the back of the unit

h
500

<To be left open>


Front

In case of collective installation

Wall<H>

With a space of at least

(19-11/16)

<To be left open>


<To be left open>

Front

In case of single installation

Front

<To be left open>


<To be left open>

Front

1 Secure enough space around the unit as shown in the figure below.

(11-13/16)

1.Required space around the unit

(1-3/16)

PURY-P96,120THMU-A(-BS)

30mm max.

300 min.*
900 min.
300 min.*

(11-13/16)
(35-7/16)

R2-SERIES (Feb. 2009)


(11-13/16)

Wall <H>
300 min.*
900 min.

R2-20
(35-7/16)

R2-SERIES

2. External Dimensions
DATA U4

Ref. : PURY_THMU-A_EXD_USDB_P96-120_R2
Unit : mm(in)

<To be left open>

R2-SERIES (Feb. 2009)


a
b

CMY-R100VBK
22.2 (7/8)
28.58 (1-1/8)

PURY-P144TSHMU-A(-BS)
PURY-P72THMU-A(-BS)
PURY-P72THMU-A(-BS)

Left view

Twinning pipe ~ Outdoor unit

1650 (64-31/32)

P72

Unit model

Intake
air

High
pressure
c or e
15.88 (5/8)

Low
pressure
d or f
19.05 (3/4)

Twinning pipe (Low pressure)


<optional parts>

Outdoor unit 1

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3. Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).

Twinning pipe connection size


Package unit name
Component unit name Outdoor unit 1
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
BC controller ~ Twinning pipe High pressure
Low pressure

Intake
air

Discharge air

920 (36-1/4)

30 (1-3/16)

Front view

Intake
air

a
To BC controller
Twinning pipe (High pressure)
<optional parts>
b
To BC controller

Outdoor unit 2

920 (36-1/4)

PURY-P144TSHMU-A(-BS)

R2-SERIES

760 (29-15/16)

2. External Dimensions
DATA U4

Ref. : PURY_TSHMU-A_EXD_USDB_P144
Unit : mm(in)

R2-21

Intake
air

R2-22
d

R2-SERIES (Feb. 2009)


P72
P96

CMY-R100VBK
22.2 (7/8)
28.58 (1-1/8)
Twinning pipe ~ Outdoor unit

Unit model

PURY-P168TSHMU-A(-BS)
PURY-P96THMU-A(-BS)
PURY-P72THMU-A(-BS)

c or e
15.88 (5/8)
19.05 (3/4)

High
pressure

d or f
19.05 (3/4)
22.2 (7/8)

Low
pressure

Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3. Be sure to see the Installation Manual for details of Twinning pipe installation.
4. The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5. Only use the Twinning pipe by Mitsubishi (optional parts).

a
b

Left view

Twinning pipe (Low pressure)


<optional parts>

Outdoor unit 1

Discharge air

Front view

30 (1-3/16)

Intake
air

a
To BC controller
Twinning pipe (High pressure)
<optional parts>
b
To BC controller

Outdoor unit 2

920 (36-1/4)

PURY-P168TSHMU-A(-BS)

Twinning pipe connection size


Package unit name
Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
BC controller ~ Twinning pipe High pressure
Low pressure

Intake
air

1220 (48-1/16)

760 (29-15/16)

1650 (64-31/32)

R2-SERIES

2. External Dimensions
DATA U4

Ref. : PURY_TSHMU-A_EXD_USDB_P168
Unit : mm(in)

R2-SERIES (Feb. 2009)

Left view

a
b

Intake
air

22.2(7/8)

CMY-R100VBK
28.58(1-1/8)
28.58(1-1/8)

Twinning pipe ~ Outdoor unit

P96
P120

Unit model

High
pressure
c or e
19.05(3/4)
19.05(3/4)

Front view

30 (1-3/16)

Twinning pipe(Low pressure)


<optional parts>

Outdoor unit 1

PURY-P192TSHMU-A(-BS) PURY-P216TSHMU-A(-BS) PURY-P240TSHMU-A(-BS)


PURY-P96THMU-A(-BS) PURY-P120THMU-A(-BS) PURY-P120THMU-A(-BS)
PURY-P96THMU-A(-BS) PURY-P96THMU-A(-BS) PURY-P120THMU-A(-BS)

1650 (64-31/32)

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3.Be sure to see the Installation Manual for details of Twinning pipe installation.
4.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5.Only use the Twinning pipe by Mitsubishi (optional parts).

Package unit name


Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit(optional parts)
High pressure
BC controller ~ Twinning pipe
Low pressure

Twinning pipe connection size

Intake
air

Discharge air

1220 (48-1/16)

Low
pressure
d or f
22.2(7/8)
28.58(1-1/8)

a
To BC controller
Twinning pipe (High pressure)
<optional parts>
b
To BC controller

Outdoor unit 2

1220 (48-1/16)

Intake
air

PURY-P192,216,240TSHMU-A(-BS)

R2-SERIES

760 (29-15/16)

2. External Dimensions
DATA U4

Ref. : PURY_TSHMU-A_EXD_USDB_P192-240
Unit : mm(in)

R2-23

760
(29-15/16)

25
(1)

Left side view

(1)

25

55
(2-3/16)

*1.Expand the field pipes(for bottom piping and front piping)


and connect directly to the valve.

PURY-P72YHMU 15.88 Brazed 19.05 Brazed


(5/8)
(3/4)

Front view

58 (2-5/16)
75 (2-31/32)
140 (5-17/32)

7
1

920 (36-1/4)

Top view

80
(3-5/32)

(3-5/8)

Bottom view

Intake
air

NO.

R2-SERIES

Specifications
140 X 77 Knockout hole
(5-17/32)(3-1/16)

Front through hole


(Uses when twinning kit (optional 45 Knockout hole
(1-25/32)
parts) is mounted.)
150 X 92 Knockout hole
Bottom through hole
(5-29/32)(3-5/8)
62.7 or 34.5 Knockout hole
Front through hole
(2-15/32) (1-3/8)
43.7 or 22.2 Knockout hole
Front through hole
For wires
(1-3/4)
(7/8)
52 Knockout hole
Bottom through hole
(2-1/16)
34 Knockout hole
For transmission cables Front through hole
(1-11/32)

For pipes

Front through hole

Usage

Note 1.Please refer to the next page for information


regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service
valve with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

2 X 2-14(9/16) X 20(13/16) Oval hole

Transformer box

Service
panel

760 (29-15/16)
80
(Mounting pitch) (3-5/32)

valve <Low pressure>

3 Refrigerant service

(8-23/32) 221 150 (5-29/32)


83(3-9/32)
(9-29/32) 251
(7-11/32) 186

(8-23/32) 221

(7-15/16) 201

(7-5/16) 185

Intake
air

Control box

Refrigerant service
valve <High pressure>

Refrigerant service
valve <Low pressure>

Connecting pipe specifications


Connection specifications for
the refrigerant service valve *1
High
Low
Model
pressure
pressure

55
(2-3/16)

54 (2-5/32)

Refrigerant service
valve <High pressure>

239
(9-7/16)
261
(10-9/32)

Intake
air

Discharge air

(8-9/16) 217
(5-3/4) 146
145 (5-23/32)
131 (5-3/16)

77 (3-1/16)
(3-9/16) 90
145 (5-23/32)
86 (3-13/32)

760 (29-15/16)
18
(23/32)
(28-17/32)
724 (721 ~ 727)
(28-13/32 ~ 28-5/8)
(Mounting pitch)

R2-SERIES (Feb. 2009)


92

240 (9-15/32)
1410 (55-17/32)
1650 (64-31/32)

R2-24
(760) (29-15/16)

PURY-P72YHMU-A(-BS)

18
(23/32)

2. External Dimensions
DATA U4

Ref. : PURY_YHMU-A_EXD_USDB_P72_R1
Unit : mm(in)

(19/32)

15 min.*

50 min.*

(1-31/32)

<Top view>

50 min.*

(1-31/32)

Front

100 min.*

(11-13/16)
(17-23/32)

300 min.*

450 min.*

Unit height

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

R2-SERIES (Feb. 2009)

3
4

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure. (Fig.A)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

<Side view>

Front

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

h
500

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

300 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.

(17-23/32)

300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on


the back of the unit
the back of the unit

<To be left open>


Front

1 When multiple units are installed adjacent to each other, secure enough space to allow

Front

(11-13/16)
(17-23/32)
15 min.*

(3-15/16)

2 At least two sides must be left open.


3 As with the single installation, add the height that exceeds the height limit <h>

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


(19/32)

Front

With a space of at least

Front

<To be left open>


<To be left open>

100 min.*
300 min.*
900 min.

Front

In case of collective installation

(1-3/16)

<To be left open>


<To be left open>

Front

In case of single installation

30mm max.

300 min.*
900 min.

450 min.*

(11-13/16)
(35-7/16)
(11-13/16)
300 min.*

Wall <H>
(11-13/16)
(35-7/16)

1 Secure enough space around the unit as shown in the figure below.

PURY-P72YHMU-A(-BS)

R2-SERIES

1.Required space around the unit

2. External Dimensions
DATA U4

Ref. : PURY_YHMU-A_EXD_USDB_P72_R2
Unit : mm(in)

R2-25

<To be left open>

760
(29-15/16)

Left side view

25
(1)

25
(1)

55
(2-3/16)

263
(10-3/8)

271
271
301
216

(10-11/16)
(10-11/16)
(11-7/8)
(8-17/32)

80
(3-5/32)

Refrigerant service
valve <High pressure>

235
251

(9-9/32)
(9-29/32)

Refrigerant service
valve <High pressure>

Refrigerant service
valve <Low pressure>

Intake
air

Control box

*1.Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.

PURY-P96YHMU

22.2 Brazed
19.05 Brazed (7/8)
(3/4)
28.58 Brazed
PURY-P120YHMU
(1-1/8)

Connecting pipe specifications


Connection specifications for
the refrigerant service valve *1
High
Low
Model
pressure
pressure

55
(2-3/16)

54 (2-5/32)

Intake
air

Discharge air

(8-9/16) 217
(5-3/4) 146
145 (5-23/32)
131 (5-3/16)

Bottom view

1060 (41-3/4)
(Mounting pitch)

Refrigerant service
valve <Low pressure>

150 (5-29/32)
83 (3-9/32)

Front view

58 (2-5/16)
75 (2-31/32)
140 (5-17/32)

Top view

1220 (48-1/16)

77 (3-1/16)
(3-9/16) 90
145 (5-23/32)

1650 (64-31/32)

84 (3-5/16)

80
(3-5/32)

(ID25.4(1) X ID22.2(7/8)) P96


(ID25.4(1) X ID28.58(1-1/8)) P120

For pipes

Specifications
140 X 77 Knockout hole
(5-17/32)(3-1/16)

Front through hole


45 Knockout hole
(Uses when twinning kit (optional
(1-25/32)
parts) is mounted.)
150 X 94 Knockout hole
Bottom through hole
(5-29/32) (3-23/32)
62.7 or 34.5 Knockout hole
Front through hole
(2-15/32) (1-3/8)
43.7 or 22.2 Knockout hole
Front through hole
For wires
(7/8)
(1-3/4)
65 Knockout hole
Bottom through hole
(2-9/16)
34 Knockout hole
For transmission cables Front through hole
(1-11/32)

Usage
Front through hole

1
2

1 pc.
1 pc.

<High pressure> Pipe (ID25.4(1) X OD19.05(3/4)) P96,P120 1 pc.


Elbow (ID19.05(3/4) X OD19.05(3/4)) P96,P120 1 pc.
Note 1.Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service
valve with wet cloth and keep the temperature of
refrigerant service valve under 120C (248F).

<Accessories>
Connecting pipe
<Low pressure> Pipe
Pipe

NO.

2 X 2-14(9/16) X 20(13/16) Oval hole

Transformer box

Service
panel

Intake
air

760 (29-15/16)
18
(23/32)

R2-SERIES (Feb. 2009)


94
(3-23/32)

240 (9-15/32)
1410 (55-17/32)

R2-26
(28-17/32)
724 (721 ~ 727)
18
(28-13/32 ~ 28-5/8)
(23/32)
(Mounting pitch)

PURY-P96,120YHMU-A(-BS)

(760) (29-15/16)

R2-SERIES

2. External Dimensions
DATA U4

Ref. : PURY_YHMU-A_EXD_USDB_P96-120_R1
Unit : mm(in)

(19/32)

15 min.*

50 min.*

(1-31/32)

<Top view>

50 min.*

(1-31/32)

Front

100 min.*

(11-13/16)

(17-23/32)

300 min.*

450 min.*

Unit height

<Side view>

<Wall height limit> Front : Up to the unit height


Back : Up to 500mm (19-11/16) from
the unit bottom
Side : Up to the unit height

R2-SERIES (Feb. 2009)

3
4

securely supported as shown in the right figure. (Fig.A)


When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm (1-3/16). (Fig.A)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts. (Fig.B)
To prevent small animals and water from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.

2 Build the foundation in such way that the corner of the installation leg is

piping route,and wiring route when preparing the installation site.


<Note that the drain water comes out of the unit during operation.>

1 Take into consideration the surface strength,water drainage route,

2.Foundation work

exceeds the wall height limit as defined below


add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.

h
500

Wall <H>

Wall <H>

Front

Wall <H>

(1-3/16)

30 min.

M10 anchor bolt


<field supply required>

Corner of the
installation leg

Wall <H>

Fig.A (without detachable legs)

450 min.

(17-23/32)

450 min.

(17-23/32)

Front

Wall <H>

Wall <H>

Front

Wall <H>

to the figures that are marked with an asterisk.

(3-15/16)

100 min.

<To be left open>

Front

Wall <H>

Fig.B (without detachable legs)

Fixing plate
<field supply required>

(39-3/8)

1000 min.*

450 min.

(17-23/32) (3-15/16)

450 min.

(17-23/32)

<To be left open>

450 min.*

(17-23/32)

100 min.*

<To be left open>

for air circulation and walkway between groups of units as shown in the figures below.

300 min.*
450 min.*

(3-15/16)
450 min.*

2 When the height of the walls on the front,back or on the sides <H>

<Top view>

(19/32)

15 min.*

Front

(17-23/32)

1 When multiple units are installed adjacent to each other, secure enough space to allow

Front

(3-15/16)
(17-23/32)

300mm (11-13/16) to the wall on 100mm (3-15/16) to the wall on


the back of the unit
the back of the unit

<To be left open>


(19/32)

(11-13/16)
(17-23/32)
15 min.*

Front

2 At least two sides must be left open.


3 As with the single installation, add the height that exceeds the height limit <h>

Wall <H>

With a space of at least

(19-11/16)

<To be left open>


<To be left open>

100 min.*
300 min.*
900 min.
300 min.*

Front

With a space of at least

Front

<To be left open>


Front

In case of collective installation

Front

<To be left open>


<To be left open>

Front

In case of single installation

(1-3/16)

300 min.*
900 min.

450 min.*

(11-13/16)
(35-7/16)
(11-13/16)

Wall <H>
(11-13/16)
(35-7/16)

1 Secure enough space around the unit as shown in the figure below.

30mm max.

PURY-P96,120YHMU-A(-BS)

R2-SERIES

1.Required space around the unit

2. External Dimensions
DATA U4

Ref. : PURY_YHMU-A_EXD_USDB_P96-120_R2
Unit : mm(in)

R2-27

<To be left open>

R2-28

R2-SERIES (Feb. 2009)


a
b

CMY-R100VBK
22.2(7/8)
28.58(1-1/8)

PURY-P144YSHMU-A(-BS)
PURY-P72YHMU-A(-BS)
PURY-P72YHMU-A(-BS)

Left view

Twinning pipe ~ Outdoor unit

P72

Unit model

High
Low
pressure
pressure
c or e
d or f
15.88(5/8) 19.05(3/4)

Twinning pipe (Low pressure)


<optional parts>

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3.Be sure to see the Installation Manual for details of Twinning pipe installation.
4.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5.Only use the Twinning pipe by Mitsubishi (optional parts).

Package unit name


Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
High pressure
BC controller ~ Twinning pipe
Low pressure

Intake
air

Outdoor unit 1

Discharge air

30 (1-3/16)

Front view

Intake
air

a
To BC controller
Twinning pipe (High pressure)
<optional parts>
b
To BC controller

Outdoor unit 2

920 (36-1/4)

PURY-P144YSHMU-A(-BS)

Twinning pipe connection size

Intake
air

920 (36-1/4)

760 (29-15/16)

1650 (64-31/32)

R2-SERIES

2. External Dimensions
DATA U4

Ref. : PURY_YSHMU-A_EXD_USDB_P144
Unit : mm(in)

R2-SERIES (Feb. 2009)


PURY-P168YSHMU-A(-BS)
PURY-P96YHMU-A(-BS)
PURY-P72YHMU-A(-BS)
CMY-R100VBK
22.2(7/8)
28.58(1-1/8)

1650 (64-31/32)
Twinning pipe ~ Outdoor unit

Intake
air

P72
P96

Unit model

High
pressure
c or e
15.88(5/8)
19.05(3/4)

Low
pressure
d or f
19.05(3/4)
22.2(7/8)

30 (1-3/16)

Front view

Twinning pipe (Low pressure)


<optional parts>

Outdoor unit 1

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3.Be sure to see the Installation Manual for details of Twinning pipe installation.
4.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5.Only use the Twinning pipe by Mitsubishi (optional parts).

Component unit name


a
b

Left view

Package unit name


Outdoor unit 1
Outdoor unit 2
Outdoor Twinning Kit (optional parts)
High pressure
BC controller ~ Twinning pipe
Low pressure

Twinning pipe connection size

Intake
air

Discharge air

1220 (48-1/16)

Intake
air

Ref. : PURY_YSHMU-A_EXD_USDB_P168
Unit : mm(in)

a
To BC controller
Twinning pipe (High pressure)
<optional parts>
b
To BC controller

Outdoor unit 2

920 (36-1/4)

PURY-P168YSHMU-A(-BS)

R2-SERIES

760 (29-15/16)

2. External Dimensions
DATA U4

R2-29

R2-30

Left view

R2-SERIES (Feb. 2009)


a
b

22.2(7/8)

CMY-R100VBK
28.58(1-1/8)
28.58(1-1/8)

PURY-P192YSHMU-A(-BS) PURY-P216YSHMU-A(-BS) PURY-P240YSHMU-A(-BS)


PURY-P96YHMU-A(-BS) PURY-P120YHMU-A(-BS) PURY-P120YHMU-A(-BS)
PURY-P96YHMU-A(-BS) PURY-P96YHMU-A(-BS) PURY-P120YHMU-A(-BS)

Twinning pipe ~ Outdoor unit

P96
P120

Unit model

High
pressure
c or e
19.05(3/4)
19.05(3/4)

Front view

30 (1-3/16)

Twinning pipe(Low pressure)


<optional parts>

Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
3.Be sure to see the Installation Manual for details of Twinning pipe installation.
4.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
5.Only use the Twinning pipe by Mitsubishi (optional parts).

Package unit name


Outdoor unit 1
Component unit name
Outdoor unit 2
Outdoor Twinning Kit(optional parts)
High pressure
BC controller ~ Twinning pipe
Low pressure

Intake
air

Outdoor unit 1

1220 (48-1/16)

Low
pressure
d or f
22.2(7/8)
28.58(1-1/8)

a
To BC controller
Twinning pipe (High pressure)
<optional parts>
b
To BC controller

Outdoor unit 2

1220 (48-1/16)

Intake
air

PURY-P192,216,240YSHMU-A(-BS)

Twinning pipe connection size

Intake
air

Discharge air

760 (29-15/16)

1650 (64-31/32)

R2-SERIES

2. External Dimensions
DATA U4

Ref. : PURY_YSHMU-A_EXD_USDB_P192-240
Unit : mm(in)

3. Center of Gravity

DATA U4

PURY-P72THMU-A (-BS)
PURY-P72YHMU-A (-BS)
920[36-1/4]

760[29-15/16]

Unit : mm[in]

PURY-P72THMU-A (-BS)

345[13-19/32] 332[13-3/32]

595[23-7/16]

PURY-P72YHMU-A (-BS)

338[13-5/16] 325[12-13/16] 608[23-15/16]

R2-SERIES

1410[55-17/32]

Model

X
760[29-15/16]

724[28-17/32]

80[3-5/32]

PURY-P96, 120THMU-A (-BS)


PURY-P96, 120YHMU-A (-BS)
1220[48-1/16]

760[29-15/16]

1410[55-17/32]

Unit : mm[in]

Model

PURY-P96THMU-A (-BS)

450[17-23/32] 322[12-11/16] 570[22-15/32]

PURY-P120THMU-A (-BS)

450[17-23/32] 322[12-11/16] 570[22-15/32]

PURY-P96YHMU-A (-BS)

440[17-11/32] 315[12-13/32] 583[22-31/32]

PURY-P120YHMU-A (-BS) 440[17-11/32] 315[12-13/32] 583[22-31/32]

X
1060[41-3/4]

80[3-5/32]

724[28-17/32]

Ref. : PURY_YHMU-A_COG_USDB_ALL

R2-SERIES (Feb. 2009)

R2-31

R2-32

R2-SERIES (Feb. 2009)

SV9

SV5c

SV2
SV4a,b,d
SV5b

63HS1
63LS
72C
CT12,22,3
CH11
DCL
SV1a

Symbol
21S4a
63H1

Z3
TB21

TH7
THBOX
THHS
Z24,25

TH3
TH4
TH5
TH6

TB7

Symbol
TB1
TB3

Power supply
3~
60Hz
208/230V

L3

L3

black

TB23

CX5

CX6

3 CN02

L2

L2

L1

white

red

TB22

CX4

TB1 L1

CX3
CX2
F2
AC250V
6.3A T

Z2

Explanation
4-way valve(Cooling/Heating switching)
Pressure
High pressure protection for the
switch
outdoor unit
Discharge pressure
Pressure
sensor
Low pressure
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
DC reactor
For opening/closing the bypass
Solenoid
valve
circuit under the O/S
Discharge suction bypass
Heat exchanger capacity control
For opening/closing the bypass
circuit
Heat exchanger low pressure
bypass
For opening/closing the bypass
circuit

Z4

CN01 5

CX1
F1
AC250V
6.3A T

Z1

DSA1

CY1
CY2
CY3

C1
black

red

TB-N

*5

TB-P

*5

SC-P2

INV Board

black

CT3

SC-T

IGBT

THBOX

1 3

CN5V
yellow

12

CN6

white

THHS

red

SC-R

white

MS
3~

white

CN2

5
7

1
2

SV4d

SV2

SV4b

CH11

SV5c

SV9

SV4a

SV5b

21S4a

SV1a

A2 red
72C
A1 white

*1.Single-dotted lines indicate wiring


not supplied with the unit.
*2.Dot-dash lines indicate the control
box boundaries.
*3.Refer to the Data book for connecting
input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the
outdoor units in the same refrigerant
system together.
*5.Faston terminals have a locking
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
terminals to remove them.

black

black

CT22

SC-W

Motor
(Compressor)

red

red

C1

SC-V

RSH2

CT12

SC-U

RSH1

CNDC
pink

CN4 21

CN21 3
blue 2

LED1:Normal t
operation
LED2:Error

LED3:CPU in
operation

R30 C30 C31 C32

SC-S

ZNR1

IPM

LED1:Normal operation(Lit)
/Error(Blink)
1

SC-P1

black

R630

C630

Explanation
Power supply
Terminal
block
Indoor/Outdoor transmission
cable
Central control transmission
cable
Liquid pipe temperature
Thermistor
Discharge pipe temperature
ACC inlet pipe temperature
Heat exchanger inlet pipe
temperature
OA temperature
Control box internal temperature
IGBT temperature
Function setting connector

Ground

black

white

red

red

43

23

44

13
33

24

black

2
1

CNINV

3
1

CN4
6
CN22 5
red 4
3
2
1

12 45

21

CN18V
blue

CN502

CN506

6
5

CN510
yellow

CN509
blue

CN508
3 black

6
5

CN507
3 red

1
6
5

CN504
1 green

CN503
1 blue

CN505
1 black

red
CNAC

X13

X12

X10

X09

X08

X07

X05

X04

X03

X02

X72

*3

SWU1
1's digit

321

SW5

10

SW4

10

SW3

10

red
CNIT

CNIT
red

TB3
M1 M2

TB7
M1 M2 S
TP1 TP2

54321

21

LED1:Power supply to
Indoor/Outdoor
transmission line

CNS2
yellow

CN211 12

4321

12345

CN102

12

yellow
CNS2

OFF

CN201 2

CN202 32
red
1

CN990 21

CN212 2

CN213 3
2
red
1

CNTYP4 21
green

CNTYP5 3
1
green

LED1
Display
setting

SW1

10

Indoor/Outdoor Central control


transmission
transmission
cable
cable

*4

M-NET power
supply
circuit

CN04
3 red

CN41
1234

M-NET Board

321

CN102
1234

red
CN3S CN3D

F01
AC250V
3.15A T

ON
Power selecting
connector

1234

CN40

SW2

10

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

LED2:CPU in operation

321

12
CN4

LED1

*3
Compressor ON/OFF output
Error detection output

CN03
black

blue
CN3N
321

CN2

Function setting

LED3:Lit when powered

3
4
5

CN51
1

yellow
CN3K

12V

2
1

7
5

12 21
CNT02 CN332
blue

Control Board

1 3
CN801
yellow

Unit address setting

SWU2
10's digit

Power
failure
detection
circuit

12
CNT01

F01
AC250V
3.15A T

CPU power
supply circuit

CNDC
3 pink

CNAC2
2 black
1

63H1

Z24

Z25

1
2
3
1
2
3

TH7

TH4

63HS1

63LS

TH5

TH3

TH6
t
t

PURY-P72THMU-A(-BS)

<Symbol explanation>

Noise Filter

R1

72C

*5

14

DCL 34

red

M
3~

Fan motor
(Heat exchanger)

F01
AC250V
CNVDC 15A T

FAN Board

R2-SERIES

4. Electrical Wiring Diagrams


DATA U4

Ref.:PURY_THMU-A_EWD_USDB_P72

R2-SERIES (Feb. 2009)

SV9

SV5c

SV2
SV4a,b,c,d
SV5b

63HS1
63LS
72C
ACCT1,2,3
CH11
DCCT1
DCL
SV1a

Symbol
21S4a
63H1

Z1

CN01 5

CY3

F1 CX1
AC250V
6.3A T

CY2

CY1

R2

TB1

L2

L2

white

L3

L3

black

red

C1

black

DCCT1

black

R01

21

R630

C630

21

Z26
21

IPM

IPM

C007

FT-N

*5

white

MS
3~

white

red

ACCT1

red

3 1

3 1 pink

CNDC3

CNFG 2
blue 1

F02
AC250V
3.15A T

IPM power
supply
circuit

LED3:Charge

2
1

7
5

CN4 2

CN2

CN5V
yellow

SV4d

SV2

SV4b

CH11

SV5c

SV4c

SV9

SV4a

SV5b

21S4a

SV1a

*1.Single-dotted lines indicate wiring


not supplied with the unit.
*2.Dot-dash lines indicate the control
box boundaries.
*3.Refer to the Data book for connecting
input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the
outdoor units in the same refrigerant
system together.
*5.Faston terminals have a locking
function.Make sure the terminals
are securely locked in place after
insertion.Press the tab on the
terminals to remove them.

Motor
(Compressor)

black

ACCT2

black

25

CNDC1
C008

CNIPM

SW1

Function
setting

OFF ON
1

LED1:Normal operation
LED2:Error

INV Board

THBOX

CN21 3
blue 2

LED1:Normal t
operation
LED2:Error

LED3:CPU in
operation

CN4
6
CN22 5
red 4
3
2
1

12 45

21

CN18V
blue

LED4:CPU in
operation

CNTH CNTYP CNCT3


black
green

THHS

1
2
3 CNCT
4

CNCT2
blue

4321

2
1

CNINV

3
1

F01
AC250V
CNVDC 15A T

FAN Board

Explanation
Power supply
Terminal
block
Indoor/Outdoor transmission
cable
Central control transmission
cable
Liquid pipe temperature
Thermistor
Discharge pipe temperature
ACC inlet pipe temperature
Heat exchanger inlet pipe
temperature
OA temperature
Control box internal temperature
IGBT temperature
Function setting connector

Ground

TH7
THBOX
THHS
Z24,25,26

TH3
TH4
TH5
TH6

TB7

Symbol
TB1
TB3

Power supply
3~
60Hz
208/230V

L1

L1

red

F2
AC250V
6.3A T

CX3 TB21
CX2
TB22

TB23

M
3~

72C

Z5
C41

Z2

Z3

black

R1

+
Diode Stack
~
~
~

F3
AC250V
6.3A T

TB42

72C

black

TB31

red

1 3 CN03

Explanation
4-way valve(Cooling/Heating switching)
Pressure
High pressure protection for the
switch
outdoor unit
Discharge pressure
Pressure
sensor
Low pressure
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
Current sensor(DC)
DC reactor
Solenoid
For opening/closing the bypass
valve
circuit under the O/S
Discharge suction bypass
Heat exchanger capacity control
For opening/closing the bypass
circuit
Heat exchanger low pressure
bypass
For opening/closing the bypass
circuit

<Symbol explanation>

Z4 DSA1

CN02 1 3

CX4 CX5

DCL

ACCT3

Noise
Filter

CX6

Fan motor
(Heat exchanger)

SC-P1

CN502

CN506

CN510
yellow

CN509
3 blue

6
5

CN508
3 black

6
5

CN507
3 red

1
6
5

CN504
1 green

CN503
1 blue

CN505
1 black

CNAC 2
red

X13

X12

X11

X10

X09

X08

X07

X05

X04

X03

X02

X72

SWU1
1's digit

LED1

SW5

10

SW4

10

Function setting

SW3

10

F01
AC250V
3.15A T

321

ON

12

red
CNIT

CNS2
yellow

21

12345

TB3
M1 M2

Central control
transmission
cable

TB7
M1 M2 S
TP1 TP2

CNIT
red

54321

CN211 21

CN201 2

CN202 32
red
1

CN990 12

CN212 2

CN213 3
2
red
1

CNTYP4 21
green

CNTYP5 3
1
green

LED1
Display
setting

SW1

10

LED1:Power supply to
Indoor/Outdoor
transmission line

CN102

4321

OFF

yellow
CNS2

SW2

10

Indoor/Outdoor
transmission
cable

*4

M-NET power
supply
circuit

CN04
red

CN41
1234

CN102
1234

M-NET Board

321

red
CN3S CN3D

1234

Power selecting
connector

LED2:CPU in operation
CN40

*3
Compressor ON/OFF output
Error detection output

CN03
black

321

*3

blue
CN3N
321

CN2

12
CN4

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

LED3:Lit when powered

3
4
5

CN51
1

yellow
CN3K

12V

2
1

7
5

12 21
CNT02 CN332
blue

Control Board

1 3
CN801
yellow

Unit address setting

SWU2
10's digit

Power
failure
detection
circuit

12
CNT01

F01
AC250V
3.15A T

CPU power
supply circuit

CNDC
3 pink

CNAC2
2 black
1

Z24

Z25

1
2
3
1
2
3

TH4

63HS1

63LS

TH5

TH3

TH7

TH6

PURY-P96,120THMU-A(-BS)

R2-SERIES

CNDC2

63H1

4. Electrical Wiring Diagrams


DATA U4

Ref.:PURY_THMU-A_EWD_USDB_P96-120

R2-33

R2-34

R2-SERIES (Feb. 2009)

*7 exist

*7 do not exist

Appliance

TH7
THBOX
THHS
Z24,25

TH3
TH4
TH5
TH6

TB7

TB1
TB3

SV9

Explanation
4-way valve(Cooling/Heating switching)
Pressure
High pressure protection for the
switch
outdoor unit
Discharge pressure
Pressure
sensor
Low pressure
Magnetic relay(inverter main circuit)
Current sensor(AC)
Crankcase heater(for heating the compressor)
DC reactor
For opening/closing the bypass
Solenoid
valve
circuit under the O/S
Discharge suction bypass
Heat exchanger capacity control
For opening/closing the bypass
circuit
Heat exchanger low pressure
bypass
For opening/closing the bypass
circuit
Power supply
Terminal
block
Indoor/Outdoor transmission
cable
Central control transmission
cable
Thermistor
Liquid pipe temperature
Discharge pipe temperature
ACC inlet pipe temperature
Heat exchanger inlet pipe
temperature
OA temperature
Control box internal temperature
IGBT temperature
Function setting connector
red

CN1A 3

Z1 Z2 Z3
U U U

F1,F2,F3
AC250V
6.3A T

R1

white

R2

R3

C9
C8
C7

C10

black

TB1

1 CN1B

C1

C2

F1
C3

F2

Z4
U
F3

DSA

C5

C6

Power Source
3~
60Hz
460V

L1 L2 L3

L1 L2 L3

purple

460V

purple

460V

6
5
4
3

CN07

6
5
4
3

CN06

Z5

T03
(Transformer)

T02
(Transformer)

Ground

F4
600V
3A F

red
white
black

black

white

red

U
V
W

CNTR3

L1 L2 L2 L3

CNTR1 1

F5
600V
3A F

CNTR2

Diode
Bridge
F4
AC250V
6.3A T

CN6
yellow

+ U

CN5
red
D1
R5

TB21 TB22 TB23

L1 L2 L3

C4

R4
R6

Noise
Filter

C17

CN4
3 blue

Transformer Box

CN2 3

6
5

M
3~

Fan motor
(Heat exchanger)
7
4
1

4
1
+
+
+
+

black

white

red

1
3

SC-P1

72C
black

2
4

R31
R33
R35

CT3

ZNR1

black

*5

IPM

SC-L3

SC-L1

C31
C33
IGBT
C35
C37

FT-N

FT-P

*6

red

C100
R5

R631

R630

R1

C631

INV Board

R30
R32
R34

C30
C32
C34
C36

CN1

+
+
+
+

SC-P2

red

CNINV

DCL

C630

CNVDC

4
1

F01
DC700V
4A T

FAN Board
1 3
CN4
red

6
5

THBOX

SC-U

THHS

CT12

SC-L2

white

MS
3~

white

SC-V

Motor
(Compressor)

red

red

RSH1

C1

2
1

black

black

CT22

SC-W

CNTYP
black

CN2

7
5

CN4 1

LED1:Normal operation(Lit)
/ Error(Blink)

CN6 CN5V
yellow

LED1:Normal
operation
LED2:Error

21

CN21 3
blue 2

12
CN5

CN22 43
red
2

LED3:CPU in
operation

21
CN18V
blue

SV4d

*7

SV2

SV4b

5
72C
6

SV5c

SV4c

SV9

SV4a

SV5b

21S4a

CH11

SV1a

CN502

CNAC2
black

CN504

CN508

CN507
red

CN506

CN510
yellow

CN509
3 blue

6
5

3 black

6
5

6
5

1 green

CNAC
red

X13

X12

X11

X10

X09

X08

X07

X05

X04

X03

X02

2 CN72 ZNR01
1 red
U

CPU power
supply circuit

CNDC

3 pink

CN503
1 blue

2
1

12

F01
AC250V
3.15A T

CNT01

*3

12V

12

21

LED1

SW5

10

10

SW3

blue
CN3N
321

CN04

CN102
1234

3 red

CN3D
321

M-NET Board

M-NET power
supply circuit

red
CN3S
321

10

4321

*4

CN102

21

CN201

CN202
red

CN990

CN212

CN213
red

54321

1
2

1
2
3

3
2
1

Central control
transmission
cable

1
2
3

Z24

Z25

3
2
1

2
1

2
1

4
3
2
1

CNTYP4 2
1
green

CNTYP5 3
1
green

CNTYP2
black

red
CN211
CNIT
12345

63H1

CNS2
CNIT
yellow
red
LED1:Power supply to
Indoor/Outdoor
transmission line
TB3
TB7
M1 M2 S
M1 M2
TP1 TP2

yellow
CNS2
12

OFF

Indoor/Outdoor
transmission
cable

CN41
1234

SW1

LED1
Display
setting

10

TB7 Power
selecting
connector
ON

SW2

CN40
1234

Function
setting

SW4

*3
Compressor ON/OFF output
Error detection output

10

LED2:CPU in operation

yellow
CN3K
321

12

CN4

OFF ON OFF ON OFF ON OFF ON OFF ON


1
1
1
1
1

CN2

LED3:Lit when powered

3
4
5

CN51

Unit address
setting

SWU2 SWU1
10's
1's
digit
digit

2
1

CNT02 CN332
blue

Control Board

Power failure
detection circuit

CN801
yellow

TH4

63HS1

63LS

TH5

TH3

TH7

TH6

PURY-P72,96,120YHMU-A(-BS)

SV5c

SV2
SV4a,b,c,d
SV5b

63HS1
63LS
72C
CT12,22,3
CH11
DCL
SV1a

Symbol
21S4a
63H1

<Symbol explanation>

P96/P120

P72

Model name

*1.Single-dotted lines indicate wiring not supplied with the unit.


*2.Dot-dash lines indicate the control box boundaries.
*3.Refer to the Data book for connecting input/output signal connectors.
*4.Daisy-chain terminals (TB3) on the outdoor units in the
same refrigerant system together.
*5.Faston terminals have a locking function.
Make sure the terminals are securely locked
in place after insertion. Press the tab
on the terminals to removed them.
*6.Control box houses high-voltage parts.
Before inspecting the inside of the
control box,turn off the power,keep
the unit off for at least 10 minutes,
and confirm that the voltage between
FT-P and FT-N on INV Board has dropped
to DC20V or less.
G
G
*7.Difference of appliance

R2-SERIES

4. Electrical Wiring Diagrams


DATA U4

Ref.:PURY_YHMU-A_EWD_USDB_P72-120

5. Refrigerant Circuit Diagrams and Thermal Sensors

DATA U4

PURY-P72THMU/YHMU(-BS) Model

21S4a
Solenoid valve block
SV2
SV4a
SV9

SV4b

SV4d

CP2

ST17

CV7a

63H1

TH6

TH7

63HS1
CJ1
CJ2

CP1
O/S

TH5

SV1a

63LS

CV3a

HEX

CV2a

CV5a

SV5b
TH4
ACC

BV1

CV8a
CV9a

ST1

CV10a

COMP
BV2

CV6a

ST7
ST6

TH3
CV4a

SV5c

PURY-P96,P120THMU/YHMU(-BS) Models

21S4a

Solenoid valve block

CJ1

SV2
SV4c
SV9

SV4a

CP2

SV4d

SV4b

ST17

CV7a

63H1

TH6

TH7

63HS1
CJ2

CP1
O/S

TH5

ST3

SV1a

63LS

CV3a

HEX

CV2a

CV5a

SV5b
TH4
ACC

BV1

CV8a
CV9a

ST1

CV10a

COMP
BV2

CV6a

ST7
ST6

TH3
CV4a

SV5c

R2-SERIES (Feb. 2009)

R2-35

R2-SERIES

ST3

6. Sound Pressure Levels

DATA U4
Measurement condition
PURY-P96,120THMU/YHMU

Measurement condition
PURY-P72THMU/YHMU

3-1/4' [1m]
3-1/4' [1m]

Measurement
location

R2-SERIES

3-1/4' [1m]

3-1/4' [1m]

Measurement
location

Ref.:PURY_THMU_NCC_USDB_R1

Sound Pressure Level of PURY-P72T/YHMU-A(-BS)

Ref.:PURY_THMU_NCC_USDB_P72

Ref.:PURY_THMU_NCC_USDB_R2

Sound Pressure Level of PURY-P120T/YHUM-A(-BS)


Stand 60Hz

Stand 60Hz
60Hz

Low

80

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

Octave band sound level (dB)

Low

80
Octave band sound level (dB)

Ref.:PURY_THMU_NCC_USDB_P120

90

90

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30

NC-30
20

20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

Approximate minimum
audible limit on
continuous noise

NC-20

10
500

1k

2k

4k

63

8k

125

63 125 250 500


1k
2k
4k
8k dB(A)
65.0 63.5 61.0 54.5 51.5 47.0 40.5 37.5 58.0
56.5 48.5 46.0 39.0 38.5 32.5 33.0 25.5 44.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
fromLow noise mode automatically in the case that the operation condition is severe.

Sound Pressure Level of PURY-P96T/YHUM-A(-BS)

Ref.:PURY_THMU_NCC_USDB_P96

90
Stand 60Hz
Low

Octave band sound level (dB)

80

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
70.0 63.0 59.5 55.0 51.5 48.0 44.5 38.0 58.0
49.0 50.0 45.0 41.0 40.5 42.0 40.0 36.5 48.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

R2-36

500

1k

2k

4k

8k

Octave band central frequency (Hz)

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

250

NC-20

R2-SERIES (Feb. 2009)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
72.0 65.0 61.5 57.0 53.5 50.0 46.5 40.0 60.0
51.0 52.0 47.0 43.0 42.5 44.0 42.0 38.5 50.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

6. Sound Pressure Levels

DATA U4

Measurement condition
PURY-P144TSHMU/YSHMU

Measurement condition
PURY-P168TSHMU/YSHMU

3-1/4' [1m]

3-1/4' [1m]

Measurement
location

3-1/4' [1m]

3-1/4' [1m]

Measurement
location

Sound level of PURY-P144T/YSHMU-A(-BS)

Ref.:PURY_THMU_NCC_USDB_P144

Ref.:PURY_THMU_NCC_USDB_R4

Sound level of PURY-P168T/YSHMU-A(-BS)

90

Stand 60Hz

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

Low

80
Octave band sound level (dB)

Low

80

Octave band sound level (dB)

Ref.:PURY_THMU_NCC_USDB_P168

90
Stand 60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

NC-20
500

1k

2k

4k

8k

10
63

125

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
68.0 66.5 64.0 57.5 54.5 50.0 43.5 40.5 61.0
59.5 51.5 49.0 42.0 41.5 35.5 36.0 28.5 47.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

60Hz

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
71.0 66.5 63.5 58.0 54.5 50.5 46.0 41.0 61.0
57.0 52.5 48.5 43.0 42.5 42.5 41.0 37.0 49.5

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

R2-SERIES (Feb. 2009)

R2-37

R2-SERIES

Ref.:PURY_THMU_NCC_USDB_R3

6. Sound Pressure Levels

DATA U4

Measurement condition
PURY-P192,216,240TSHMU/YSHMU

Sound Pressure Level of PURY-P240T/YSHMU-A(-BS)

Ref.:PURY_THMU_NCC_USDB_P240

90
Stand 60Hz
Low

Octave band sound level (dB)

80

3-1/4' [1m]

Measurement
location

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30

3-1/4' [1m]

NC-30
20

Approximate minimum
audible limit on
continuous noise

10

R2-SERIES

63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
75.0 68.0 64.5 60.0 56.5 53.0 49.5 43.0 63.0
54.0 55.0 50.0 46.0 45.5 47.0 45.0 41.5 53.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Ref.:PURY_THMU_NCC_USDB_R5

Sound Pressure Level of PURY-P192T/YSHMU-A(-BS)

Ref.:PURY_THMU_NCC_USDB_P192

90
Stand 60Hz
Low

Octave band sound level (dB)

80

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
74.0 67.0 63.5 59.0 55.5 52.0 48.5 42.0 62.0
53.0 54.0 49.0 45.0 44.5 46.0 44.0 40.5 52.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

Sound Pressure Level of PURY-P216T/YSHMU-A(-BS)

Ref.:PURY_THMU_NCC_USDB_P216

90
Stand 60Hz
Low

Octave band sound level (dB)

80

60Hz

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Standard
60Hz
Low noise mode 60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
74.0 67.0 63.5 59.0 55.5 52.0 48.5 42.0 62.0
53.0 54.0 49.0 45.0 44.5 46.0 44.0 40.5 52.0

When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.

R2-38

R2-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

7-1. Correction by Temperature


CITY MULTI could have varied capacity at different design temperatures. Using the nominal cooling/heating capacity value and
the ratio below, the capacity can be observed at various temperatures.

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

P72THMU P96THMU
21.1

28.1

72,000

96,000

5.55

8.35

P72YHMU P96YHMU
21.1

28.1

72,000

96,000

5.55

8.35

1.3

Indoor Temperature

1.2
Ratio of cooling capacity

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

75 WB
23.9 WB

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB

0.9

67 WB
19.4 WB

0.8

64 WB
17.8 WB

0.7

61 WB
16.1 WB
59 WB
15.0 WB

Ratio of power input

1.2

75 WB
23.9 WB

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB
67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8
61 WB
16.1 WB

0.7

59 WB
15.0 WB

0.6
0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

23.4

31.7

80,000

108,000

6.04

8.66

P72YHMU P96YHMU
23.4

31.7

80,000

108,000

6.04

8.66

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
59 DB
15.0 DB

1.2
Ratio of heating capacity

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

P72THMU P96THMU

1.1
1.0

70 DB
21.1 DB

0.9
0.8

77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5
Indoor Temperature
1.1
59 DB
15.0 DB

1.0
Ratio of power input

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

0.9
0.8

70 DB
21.1 DB

0.7
77 DB
25.0 DB

0.6

81 DB
27.2 DB

0.5
0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

50
60
WB
10.0
15.6 WB
Outdoor temperature
Ref:PURY_THMU_C10_USDB_P72-96

R2-SERIES (Feb. 2009)

R2-39

R2-SERIES

1.3

7. CAPACITY TABLES

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

P120THMU

1.4

Indoor Temperature

35.2
1.3

120,000
10.59

P120YHMU
35.2
120,000
10.59

Ratio of cooling capacity

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U4

75 WB
23.9 WB

1.2

72 WB
22.2 WB

1.1

69 WB
20.6 WB

1.0

67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8

61 WB
16.1 WB
59 WB
15.0 WB

1.3

Ratio of power input

R2-SERIES

1.2

75 WB
23.9 WB

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB
67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8
61 WB
16.1 WB

0.7

59 WB
15.0 WB

0.6
0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

P120THMU

P120YHMU
35.2
120,000
10.16

120
48.9

DB
DB

Outdoor temperature

1.2

120,000
10.16

110
43.3

1.3

35.2
Ratio of heating capacity

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

59 DB
15.0 DB

1.1
1.0

70 DB
21.1 DB

0.9
0.8
77 DB
25.0 DB

0.7

81 DB
27.2 DB

0.6
0.5

Indoor Temperature
1.1

Ratio of power input

1.0
0.9

59 DB
15.0 DB

0.8
0.7

70 DB
21.1 DB

0.6
77 DB
25.0 DB

0.5

81 DB
27.2 DB

0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

50
60
WB
10.0
15.6 WB
Outdoor temperature
Ref:PURY_THMU_C10_USDB_P120

R2-40

R2-SERIES (Feb. 2009)

7. CAPACITY TABLES

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

PURY-

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

49.2

144,000

168,000

11.32

14.19

P192TSHMU P216TSHMU
56.3

63.3

192,000

216,000

17.04

19.32

P240TSHMU

1.4

Indoor Temperature

1.3

70.3
240,000

75 WB
23.9 WB

1.2

72 WB
22.2 WB

1.1

69 WB
20.6 WB

1.0

67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8

61 WB
16.1 WB
59 WB
15.0 WB

21.61
1.3

P144YSHMU P168YSHMU
42.2

49.2

144,000

168,000

11.32

14.19

P192YSHMU P216YSHMU
56.3

63.3

192,000

216,000

17.04

19.32

P240YSHMU

1.2

75 WB
23.9 WB

1.1

72 WB
22.2 WB

1.0

69 WB
20.6 WB
67 WB
19.4 WB

0.9

64 WB
17.8 WB

0.8
61 WB
16.1 WB

0.7

70.3

59 WB
15.0 WB

240,000
0.6

21.61

0.5
20
-6.7

30
-1.1

40
4.4

50
10.0

60
15.6

70
21.1

80
26.7

90
32.2

Ratio of cooling capacity and power input

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

P144TSHMU P168TSHMU
46.9

55.1

160,000

188,000

12.44

15.14

P192TSHMU P216TSHMU
58.6

66.8

200,000

228,000

15.85

19.38

P240TSHMU

110
43.3

120
48.9

DB
DB

Outdoor temperature

1.3
1.2
Ratio of heating capacity

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

100
37.8

59 DB
15.0 DB

1.1
1.0

70 DB
21.1 DB

0.9
0.8

77 DB
25.0 DB

0.7

81 DB
27.2 DB

70.3
0.6

240,000
20.92

0.5
Nominal kW
Heating
Capacity BTU/h
Input
kW

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

PURYNominal kW
Heating
Capacity BTU/h
Input
kW

Indoor Temperature

P144YSHMU P168YSHMU
46.9

55.1

160,000

188,000

12.44

15.14

P192YSHMU P216YSHMU
58.6

66.8

200,000

228,000

15.85

19.38

P240YSHMU
70.3

1.1
1.0
Ratio of power input

PURY-

59 DB
15.0 DB

0.9
0.8

70 DB
21.1 DB

0.7
77 DB
25.0 DB

0.6

81 DB
27.2 DB

240,000
20.92

0.5
0.4
-10
-23.3

0
-17.8

10
20
30
40
-12.2
-6.7
-1.1
4.4
Ratio of heating capacity and power input

50
60
WB
10.0
15.6 WB
Outdoor temperature
Ref:PURY_THMU_C10_USDB_P144-240

R2-SERIES (Feb. 2009)

R2-41

R2-SERIES

Nominal kW
Cooling
Capacity BTU/h
Input
kW

42.2

Ratio of cooling capacity

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

P144TSHMU P168TSHMU

Ratio of power input

PURYNominal kW
Cooling
Capacity BTU/h
Input
kW

DATA U4

7. CAPACITY TABLES
7-2. Correction by Total Indoor

DATA U4

CITY MULTI systems have different capacities and inputs when different combinations of indoor units with different total
capacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with
enough capacity for a particular application.

PURY-P72,96THMU/YHMU
50.0

Capacity(kW)

40.0

30.0

20.0

R2-SERIES

10.0

0.0

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units

PURY-P120,144T(S)HMU/Y(S)HMU
60.0

Capacity(kW)

50.0

40.0

30.0

20.0

Input(kW)

10.0

5.0

P120

P144
Cooling
Heating

Cooling
Heating

2.5
50

100

150

200

250

Total capacity of indoor units


Ref: PURY_THMU_C20_USDB_P72-144_

R2-42

R2-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

PURY-P168,192TSHMU/YSHMU
70.0

Capacity(kW)

60.0

50.0

40.0

30.0

Input(kW)

R2-SERIES

20.0

10.0

P168

P192
Cooling
Heating

Cooling
Heating

0.0
0

100

200

300

400

Total capacity of indoor units

PURY-P216,240TSHMU/YSHMU
80.0

Capacity(kW)

70.0

60.0

50.0

40.0

Input(kW)

30.0

15.0

P216

P240
Cooling
Heating

Cooling
Heating

5.0
0

100

200

300

400

Total capacity of indoor units


Ref: PURY_THMU_C20_USDB_P168-240_

R2-SERIES (Feb. 2009)

R2-43

7. CAPACITY TABLES

DATA U4

PURY-P72,96THMU/YHMU
120,000

Capacity(BTU/h)

100,000

80,000

60,000

40,000

R2-SERIES

20,000

Input(kW)

10.0

5.0

P72

P96
Cooling
Heating

Cooling
Heating

0.0
0

50

100

150

200

Total capacity of indoor units

PURY-P120,144T(S)HMU/Y(S)HMU
200,000

Capacity(BTU/h)

160,000

120,000

80,000

40,000

Input(kW)

10.0

5.0

P120

P144
Cooling
Heating

Cooling
Heating

2.5
50

100

150

200

250

Total capacity of indoor units


Ref: PURY_THMU_C20_USDB_P72-144_2

R2-44

R2-SERIES (Feb. 2009)

7. CAPACITY TABLES

DATA U4

PURY-P168,192TSHMU/YSHMU
250,000

Capacity(BTU/h)

200,000

150,000

100,000

50,000

R2-SERIES

Input(kW)

20.0

10.0

P168

P192
Cooling
Heating

Cooling
Heating

0.0
0

100

200

300

400

Total capacity of indoor units

PURY-P216,240TSHMU/YSHMU
300,000

Capacity(BTU/h)

250,000

200,000

150,000

100,000

50,000

Input(kW)

25.0

15.0

P216

P240
Cooling
Heating

Cooling
Heating

5.0
0

100

200

300

400

Total capacity of indoor units


Ref: PURY_THMU_C20_USDB_P168-240_2

R2-SERIES (Feb. 2009)

R2-45

7. CAPACITY TABLES
7-3. Correction by Refrigerant Piping Length

DATA U4

CITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating capacity could be
reduced. Using the following correction factor by equivalent piping length shown at 7-3-1 and 7-3-2, capacity can be found. 7-3-3
shows how to obtain the equivalent piping length.
7-3-1. Cooling Capacity Correction
PURY-P72THMU/YHMU

PURY-P168TSHMU/YSHMU

0.9

To
ta

lc

0.85

ap

ac

ity

0.8

of

ind

oo

ru

54

nit

0.75
0.7

72
108

0.65
100

200

300

400

500

l ca

pac

ity

0.85

of i

ndo

or

0.8

uni

0.75

72

96
144

0.7

200

300

400

Piping equivalent length

500

lc

0.85

ap

ac

ity

0.8

of

ind

oo

ru

nit

0.75
0.7

90

120
180

0.65
200

300

400

Piping equivalent length

500

126

200

300

400

500

600 ft.

Ref:PURY_THMU_C31_USDB_P168

96

0.95
Tot
a

0.9

l ca

pac

ity

0.85

of i

ndo

or

uni

0.8
0.75

144
192
288

0.7
0.65
0

100

200

300

400

Piping equivalent length

500

600 ft.

Ref:PURY_THMU_C31_USDB_P192

108

0.95
Tot
a

0.9

l ca

pac

ity

0.85

of

ind

oo

ru

0.8

nit

0.75

162
216
324

0.7
0.65
0

600 ft.

100

200

300

400

Piping equivalent length

Ref:PURY_THMU_C31_USDB_P120

500

600 ft.

Ref:PURY_THMU_C31_USDB_P216

PURY-P240TSHMU/YSHMU

PURY-P144TSHMU/YSHMU
1

Tot
a

l ca

0.85

pac

ity

of i

ndo

or u

nit

108

0.8
144
216

0.75
0.7
0.65
300

Piping equivalent length

400

500

600 ft.

Ref:PURY_THMU_C31_USDB_P144

R2-SERIES (Feb. 2009)

Cooling capacity correction factor

72

0.95

R2-46

100

Cooling capacity correction factor

To
ta

200

nit

PURY-P216TSHMU/YSHMU

0.95

100

ru

0.65
Piping equivalent length

60

oo

168
252

Ref:PURY_THMU_C31_USDB_P96

0.9

ind

0.7

600 ft.

PURY-P120THMU/YHMU

100

of

0.75

0.65

ity

0.8

Cooling capacity correction factor

Tot
a

0.9

pac

PURY-P192TSHMU/YSHMU

0.95

100

l ca

0.85

48

Tot
a

0.9

Ref:PURY_THMU_C31_USDB_P72

0.9

84

0.95

600 ft.

PURY-P96THMU/YHMU
Cooling capacity correction factor

Cooling capacity correction factor

0.95

Piping equivalent length

Cooling capacity correction factor

36

Cooling capacity correction factor

R2-SERIES

Cooling capacity correction factor

120

0.95
0.9

To
ta

lc

0.85

ap

ac

0.8

ity

of

ind

oo

0.75

ru

nit

0.7

180

240
360

0.65
0

100

200

300

Piping equivalent length

400

500

600 ft.

Ref:PURY_THMU_C31_USDB_P240

7. CAPACITY TABLES

DATA U4

7-3-2. Heating Capacity Correction


PURY-P144,168,192TSHMU/YSHMU

PURY-P72THMU/YHMU

1.00
Heating capacity correction factor

Heating capacity correction factor

1.00

0.95

0.90

0.85

0.80

0.90

0.85

0.80
0

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Ref:PURY_THMU_C32_USDB_P72

Ref:PURY_THMU_C32_USDB_P144-192

R2-SERIES

PURY-P96,120THMU/YHMU

PURY-P216,240TSHMU/YSHMU

1.00

1.00

Heating capacity correction factor

Heating capacity correction factor

0.95

0.95

0.90

0.85

0.80

0.95

0.90

0.85

0.80

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Ref:PURY_THMU_C32_USDB_P96-120

50 100 150 200 250 300 350 400 450 500 550 600 ft.
Piping equivalent length

Ref:PURY_THMU_C32_USDB_P216-240

7-3-3. How to Obtain the Equivalent Piping Length

bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in
bends in

R2-SERIES (Feb. 2009)

R2-47

7. CAPACITY TABLES

DATA U4

7-4. Correction at Frost and Defrost


Correction Factor Table when Frost and Defrost Occurs

R2-SERIES

WB
WB

7-5. Operation Temperature Range

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

25
77

30
86

35
95

40
104

45
113

50
122

25
77

30
86

35
95

40
104

45
113

50
122

Outdoor temperature

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

Outdoor temperature
* Tables above show published performance operation range. Units will try to continue to cool and heat above and below temperature range shown, but
there is no published performance data at these ranges.

Simultaneous Operation Temperature Ranges


*Temperature Range
Outdoor
Indoor
Cooling Main
23 to 70FDB (-5 to +21CDB)
59 to 75FWB (15 to 24CWB)
Heating Main
21 to 60FWB (-5 to +15.5CWB)
59 to 81FDB (15 to 27CDB)
* Depending on the application, these ranges may be extended. Please consult your Mitsubishi representative.
R2-48

R2-SERIES (Feb. 2009)

8. OPTIONAL PARTS

DATA U4

8-1. Branch Joint


Piping for CITY MULTI systems can be easily performed with branch joints provided by MITSUBISHI ELECTRIC CORP. For
PURY-P-T(S)HMU/Y(S)HMU, the following sets of branch joints are available. Details for installing the branch joint sets are found
in the System Design section, or in the Branch Joint Installation Manual.
Ref.: CMY_Y102S_G2_EXD_EUDB_SI
in.

CMY-Y102S-G2
For Gas pipe:

For Liquid pipe:


<Reducer Pipe (Accessory)>

5/8

<Reducer pipe (Accessory)>

1/2

3/8

3/4

3/4

15/16

1-3/16

5/8

1-15/16
3/4

5-31/32

5/8

3/8

3/8

3/8

1/4
1-15/16

( 2 Pcs.)

2-1/2

ID: Inner Diameter

( 2 Pcs.)

1/2

R2-SERIES

3/4
OD: Outer Diameter

2-1/2

Ref.: CMY_Y102L_G2_EXD_EUDB_SI
in.

CMY-Y102L- G2
For Gas pipe:

For Liquid pipe:

<Reducer Pipe (Accessory)>

3/4"

5/8"

3/4"

1/2"

1"

<Reducer Pipe (Accessory)>

7/8"

1"

1"
5-31/32"

2-15/32"

3/4"

2-15/32"

1/2"
1-1/8"

2-15/32"

1"

2-15/32"

7/8"
1"

( 2 Pcs.)

13/16"

1-9/16"

3/4"
3/8"
1/2"

( 2 Pcs.)

1"
ID: Inner Diameter

OD: Outer Diameter

3/4"

1-15/16"
( 2 Pcs.)

4"
5/8"

2-15/32"

3/8"

1/2"

3/8"

1/4"

2-15/32"
1-15/16"

2-15/32"
( 2 Pcs.)

R2-SERIES (Feb. 2009)

R2-49

8. OPTIONAL PARTS

DATA U4

8-2. Outdoor Twinning Kit


The outdoor twinning kit is needed to PURY-P-TSHMU/YSHMU to combine the refrigerant flows of the PURY-P-THMU/YHMU
units.
CMY-R100VBK Low-pressure pipe twinning kit

1
(Outside diameter)

<Elbow pipe(Accessory)>
1-5/32"

1-31/32"

7/8
21/32 (Outside

4-5/32

1-3/32

5-1/4

<Deformed pipe(Accessory)>

<Low-pressure pipe twinning kit(Accessory)>


1

3/4"

2-3/8

<Pipe for routing through the bottom


(Accessory)>
3/4"
(Outside diameter)

3/4"

21/32"

4-17/32"
4-17/32"

5/8
7-9/16"

7-17/32"

7-17/32"

5/8
5/8"
21/32"

<Deformed pipe(Accessory)>

5/8"
(Outside diameter)

1"

3/4"
3/4"

3/4"

3/4
(Outside diameter)

<Pipe for routing through the front


(Accessory)>

3/4"
8-7/16

3-5/32"

2-15/32"

3-5/32"

1-13/32

7/8"

3/4

3/4

2-5/16"

High-pressure twinning pipe

7/8"
(Outside diameter)

2-3/8

3-5/32"

1"
2-3/8

R2-SERIES

1-7/16

diameter)

17-1/32

5/8"

2-5/16"

7/8"
7/8"

1-7/16

1-1/4

3-17/32

1-5/32
(Outside diameter)

6-15/16

1-31/32"

1-5/32"

2-15/32"
3-11/16"

1-5/32"

3/4"
(Outside diameter)
8-7/16

2-15/32"

7-17/32"

1"

21/32"

(2Pcs.)
7/8"
(Outside diameter)

Ref: CMY_R100VBK_EXD_EUDB_SI

Note 1. Reference the angle of the branch pipe below the fig.

15

Distributer

The angle of the branch pipe for hign pressure is within 15 against the horizontal plane.
2. Use the attached pipe to braze the port-opening of the distributer.
3. Pipe diameter is indicated by inside diameter.
4. Only use the Twinning pipe by Mitsubishi (optional parts).

R2-50

R2-SERIES (Feb. 2009)

8. OPTIONAL PARTS
8-3. Joint Adapter Kit CMY-R160J for BC Controller

DATA U4

Joint Adapter Kit CMY-R160J for BC Controllers is used to combine two ports of the BC Controller for a PURY-P-T(S)HMU/
Y(S)HMU system to enable downstream indoor unit capacity above P54 as shown in Figure 1.

The Joint Adapter Kit includes following items:


2 Joint pipe
(for liquid side)

1pc

3 Joint pipe

4 Cover 1

5 Cover 2

(for gas side)

1pc

6 Cover 3

(for gas side)

1pc

2pcs

1pc

1pc

8 Reducer

8pcs

2pcs

3 Joint Adapter Pipe (for gas side)

in.(mm)

1. Designing CMY-R160J to a PURY-P-T(S)HMU/


Y(S)HMU System
The maximum downstream indoor unit capacity for one
port on a BC Controller is P54. When the downstream
indoor unit capacity is above P54, Joint Adapter Kit
CMY-R160J is needed to combine two ports on a BC
Controller to enlarge the capacity; see Groups 2 and 3
in Figure 1.
A maximum of three indoor units are allowed to connect
to one port of a BC Controller or two combined ports of
a BC Controller using CMY-R160J.
When connecting indoor units to one port of a BC
Controller or two combined ports of a BC Controller
using CMY-R160J, CMY-Y102S-G2, and CMY-Y102LG2 is applicable; see Groups 1 and 2 in Figure 1.
Caution: Simultaneous operation of cooling and heating
modes for indoor units connected to the same BC
Controller ports is not available.

R2-SERIES

2-3/8"(60)

2 Joint Adapter Pipe (for liquid side)

7 Band

(for liquid side)

2-3/8"(60)

1 Instructions

PURY-P-T(S)HMU/Y(S)HMU
BC controller
CMY-Y102S-G

IU
IU
Group1
Total Indoor Capacity
<=P54

IU

IU
IU
Group2
Total Indoor Capacity
P55 to P96

Joint kit
CMY-R160-J

IU

IU
Group3
Total Indoor Capacity
P72 or P96

Fig.1. CMY-R160-J applying scheme


2. Piping at the Installation Site
Refer to Figure 2 for connecting the CMY-R160J to the BC Controller and the pipe leading to the indoor units. Non-oxidized brazing is necessary. Avoid getting foreign material inside the piping. After piping installation and testing for air-tightness, insulate the
joint and pipe. Details are available in the Installation Manual.

2 Joint pipe (for liquid side)

Piping to indoor unit


(Non-oxidized brazing)

Flare nut 3/8" (9.52)


Clamping torque 35Nm (26 ft.lb.)
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
Flare nut 5/8" (15.88)
Clamping torque 80Nm (59 ft.lb.)
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
3 Joint pipe(for gas side)

Fig.2. Connecting CMY-R160-J

R2-SERIES (Feb. 2009)

R2-51

S-SERIES

DATA U4

OUTDOOR UNITS
1. SPECIFICATIONS......................................................................................................................................................... S-2
2. EXTERNAL DIMENSIONS............................................................................................................................................ S-3
3. Center of Gravity................................................................................................................................................. S-4
4. ELECTRICAL WIRING DIAGRAMS.............................................................................................................................. S-5
5. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS............................................................................ S-7
6. SOUND Pressure LEVELS...................................................................................................................................... S-8

7. CAPACITY TABLES....................................................................................................................................................... S-9


7-1. Correction by Temperature.............................................................................................................................. S-9
7-2. Correction by Total Indoor............................................................................................................................. S-10
7-3. Correction by Refrigerant Piping Length....................................................................................................... S-12
7-4. Correction at Frost and Defrost..................................................................................................................... S-13
7-5. Operation Temperature Range...................................................................................................................... S-13

8. OPtional Parts...................................................................................................................................................... S-14


8-1. Branch Joint.................................................................................................................................................. S-14
8-2. Header.......................................................................................................................................................... S-15

S-SERIES

S-SERIES (Feb. 2009)

S-1

1. Specifications

DATA U4

Model
Power source

PUMY-P36NHMU(-BS)

PUMY-P48NHMU(-BS)
1-phase 208 / 230 V 60Hz
36,000
48,000
10.6
14.1
3.22 *3
4.97 *3
14.23 / 15.74 *3
24.0 / 21.7 *3
3.29
2.83
59 to 75 degFW.B. (15 to 24 degCW.B.)
23 to 115 degFD.B. (-5 to 46 degCD.B.)
50 to 115 degFD.B.(10 to 46 degCD.B.): in case of connecting PKFY-P06/P08 type indoor unit.
40,000
54,000
11.7
15.8
2.93 *3
4.88 *3
12.88 / 14.24 *3
23.6 / 21.3 *3
3.99
3.23
59 to 81 degFD.B. (15 to 27 degCD.B.)
0 to 60 degFW.B. (-18 to 15.5 degCW.B.)
50-130% of outdoor unit capacity
50-130% of outdoor unit capacity
P06-P36 / 1-6
P06-P54 / 1-8
49 / 51
50 / 52
3/8 (9.52) Flare (total length>=393ft. [120m])
3/8 (9.52) Flare (total length>=393ft. [120m])
5/8 (15.88) Flare
5/8 (15.88) Flare
Galvanized sheets (+powder coating for -BS type) *4 <MUNSELL 3Y 7.8/1.1>
53-5/32 x 37-13/32 x 13
53-5/32 x 37-13/32 x 13
1,350 x 950 x 330
1,350 x 950 x 330
287 (130)
287 (130)
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
Inverter scroll hermetic comp.
Inverter scroll hermetic comp.
SHIZUOKA Works,MITSUBISHI ELECTRIC CORPORATION
Inverter
Inverter
2.4
2.4
FV50S
FV50S
3,530
3,530
100
100
1,667
1,667

BTU / h
kW
Power input
kW
Current input (208 / 230) A
COP (kW / kW)
Indoor

Cooling capacity (Nominal) *1

Temp. range of
cooling

Outdoor

BTU / h
kW
Power input
kW
Current input (208 / 230) A
COP (kW / kW)
Indoor
Temp. range of
heating
Outdoor
Indoor unit
Total capacity
connectable
Model / Quantity
Sound pressure level (measured in anechoic room) dB <A>
Liquid (High pressure)
in. (mm)
Diameter of
refrigerant pipe (O.D.) Gas (Low pressure)
in. (mm)
External finish
in.
External dimension H x W x D
mm
Net weight
lbs(kg)
Heat exchanger
Type
Manufacturer
Starting method
Compressor
Motor output
kW
Case heater
kW
Lubricant
cfm
Airflow rate
m3 / min
L/s

S-SERIES

Heating capacity (Nominal) *2

FAN

External static press.

in.WG(Pa)

Type x Quantity
Control, Driving mechanism
Motor output
kW
HIC circuit (HIC: Heat Inter-Changer)
High pressure protection
Inverter circuit (COMP., FAN)
Protection
Compressor
Fan motor
Defrosting method
Refrigerant
Type x Original charge
lbs + oz (kg)
Control
Drawing
External
Wiring
Refrigerant cycle
Standard
Document
attachment
Accessory
Optional parts

Remark

0 (0)

0 (0)

Propeller fan x 2
DC-control, Direct-driven
0.086 x 2

Propeller fan x 2
DC-control, Direct-driven
0.086 x 2

High pressure sensor, High pressure switch 601 psi (4.15 MPa)
Over-current protection,Over-heat protection
Discharge thermo protection,Over-current protection
Over-heat protection,Voltage protection
Auto-defrost mode (Reversed refrigerant circle)
R410A x (18 lbs + 12 oz) (8.5kg)
R410A x (18 lbs + 12 oz) (8.5kg)
Indoor LEV
BK01B409
RG79V166
Installation Manual
Grounded lead wire x 2 , Conduit plate
Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E
Air Outlet Guide (One piece, requires two pieces): PAC-SG59SG-E; Wind Baffle (One piece,
requires two pieces: WB-PA2); Drain Pan: PAC-SG64DP-E; Drain Socket: PAC-SG61DS-E
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
3. For details on the electrical data needed for installing these units, see the S-Series System Design section, p ???.
4. For information on standard anti-corrosion protection and -BS treatment, see the S-Series System Design section, p. ???.

Note:

*1 Nominal cooling conditions

*2 Nominal heating conditions

Unit converter

Indoor:

80degF D.B./ 67degF W.B.


(26.7degC D.B./ 19.4degC W.B.)

70degF D.B.
(21.1degC D.B.)

Outdoor:

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

kcal =kW x 860


BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

* Above specification data is subject to rounding variation.

Energy Efficiencies
Model

PUMY-P36NHMU: MCA = 26A, Max. Fuse Size: 40A;


PUMY-P48NHMU: MCA = 26A, Max. Fuse Size: 40A.

PUMY-P36NHMU (-BS)

PUMY-P48NHMU (-BS)

S-2

S-SERIES (Feb. 2009)

Indoor Unit Type


Non-ducted
Ducted and Non-ducted
Ducted
Non-ducted
Ducted and Non-ducted
Ducted

SEER
13.60
13.33
13.05
14.40
14.10
13.85

HSPF
7.70
7.70
7.70
7.70
7.70
7.70

Min.150mm<5-29/32>

Front piping hole


(Knockout)

Front trunking hole


(Knockout)

65<2-9/16>

92<3-5/8>

92 >
/8
<3-5

40<1-9/16>

45<1-25/32>

Conduit hole
(2-27<1-1/16>Knockout)

19<3/4>

75
<2-31/32>

FOUNDATION

92<3-5/8>

55<2-3/16>

>

92
<3-5
/8

45<1-25/32>

65<2-9/16>

92<3-5/8>

40<1-9/16>

Right trunking hole


(Knockout)

>

92
<3-5
/8

Rear piping hole


(Knockout)

Rear trunking hole


(Knockout)

Side Air Intake

40<1-9/16>
74<2-19/32>

mm<inch>

1/2 Conduit attachment

When installing the conduit.


Set the attachment to the
inner side of each panel.

2-22<7/8>

Handle

Handle

Side Air Intake

Rear Air Intake

Conduit hole
(2-27<1-1/16>Knockout)

<Foundation bolt height>

Conduit hole
(2-27<1-1/16>Knockout)

40<1-9/16>

Air intake

Right piping hole


(Knockout)

Piping Knockout Hole Details

92<3-5/8>

Handle

Min.500mm
<19-11/16>

1 ......Refrigerant GAS pipe connction (FLARE) 15.88 (5/8 inch)


2 ......Refrigerant LIQUID pipe connection (FLARE) 9.52 (3/8 inch)
*1......Indication of STOP VALVE connection location.

Service space

Min.10mm<3/8>

Min.10mm<3/8>

Example of Notes

Min.1000mm<39-3/8>

Min.10mm<3/8>

FREE

63<2-1/2>
73<2-7/8>

Piping and wiring connections


can be made from 4 directions:
front,right,rear and below.

63<2-1/2>

Min.500mm
<19-11/16>

Please secure the unit firmly


with 4 foundation (M10<W3/8>)
bolts.(Bolts and washers must
be purchased locally.)

55<2-3/16>
27<1-1/16>

Min.150mm
<5-29/32>

Dimensions of space needed


for service access are
shown in the below diagram.

73<2-7/8>
23<29/32>

The diagram below shows a


basic example.
Explantion of particular details is
given in the installation manuals etc.

55<2-3/16>
63
<2-1/2>

27<1-1/16>

73<2-7/8>

23<29/32>

27<1-1/16>
23<29/32>

Max.
30mm<1-3/16>

4 PIPING-WIRING DIRECTIONS

330<13>

Handle

1350<53-5/32>

30<1-3/16>

600<23-5/8>

220
<8-21/32>

Drain hole
5-n33<1-5/16>

71<2-13/16>

Ground for the power supply


("GR"marking position)

950<37-13/32>

145
145
145
<5-23/32> <5-23/32> <5-23/32>

322<12-11/16>

2-U Shaped notched hole


(Foundation Bolt M10<W3/8>)
175
<6-7/8>

56<2-7/32>

Air Discharge

2-12 x 36 Oval hole


(Foundation Bolt M10<W3/8>)

175
<6-7/8>

Rear Air Intake

Handle

Bottom piping hole


(Knockout)

Rear piping cover

Front piping cover

Service panel

Ground for the transmission line


Ground for concentration control

Terminal block
Left ........ For the power supply
Center ... For the transmission line
Right ...... For concentration control

42<1-21/32>

70<2-3/4>

37<1-15/32>

*1 423<16-21/32>

30<1-3/16>

23<29/32>

417<16-13/32>

1088<42-27/32>

3 FOUNDATION BOLTS

71<2-13/16>

635<25>
371<14-19/32>
219<8-5/8>

19<3/4>
370<14-9/16>
28<1-3/32>

56<2-7/32>
53<2-3/32>

*1 507<19-31/32>

2 SERVICE SPACE

31<1-7/32>

S-SERIES (Feb. 2009)

81<3-3/16>

PUMY-P36,48NHMU(-BS)

S-SERIES

1 FREE SPACE (Around the unit)

2. External Dimensions
DATA U4

Ref. : PUMY_NHMU_EXD_USDB_P36-48
Unit : mm(in)

S-3

3. CENTER OF GRAVITY

DATA U4

PUMY-P36,48NHMU

Unit : mm[in.]

Model
PUMY-P36NHMU
PUMY-P48NHMU

X
590(23-1/4)
590(23-1/4)

Y
Z
185(7-5/16) 500(19-11/16)
185(7-5/16) 500(19-11/16)

S-SERIES

Ref. : PUMY_ NHMU_COG_USDB_P36-48

S-4

S-SERIES (Feb. 2009)

4. Electrical Wiring Diagrams

DATA U4
Ref. : PUMY-NHMU_EWD_USDB_P36-48_2

PUMY-P36,48NHMU(-BS)
SYMBOL

TB1
TB3
TB7
MC
MF1,MF2
21S4
63H
63L
63HS
SV1
TH3
TH4
TH6
TH7
TH8
DCL
ACTM
CE

NAME

SYMBOL

Terminal Block <Power Supply>


P.B.
Terminal Block <Comunication Line>
TABU/V/W
Terminal Block <Centralized Control Line> TABS/T
Motor For Compressor
TABP1/P2/P
Fan Motor
TABN1/N2/N
Solenoid Valve<Four-Way Valve>
DS2,DS3
IPM
High Pressure Switch
N.F.
Low Pressure Switch
LI/LO
High Pressure Sensor
NI/NO
Solenoid Valve<Bypass valve>
EI,E2
Thermistor<Outdoor Pipe>
52C
Thermistor<Discharge>
Thermistor<Low Pressure Saturated> C.B.
SW1
Thermistor<Outdoor>
SW2
Thermistor<Heatsink>
SW3
Reactor
SW4
Active Filter Module
SW5
Main Smoothing Capacitor

NAME

SYMBOL

Power Circuit Board


Connection Terminal<U/V/W-Phase>
Connection Terminal<L/N-Phase>
Connection Terminal<DC Voltage>
Connection Terminal<DC Voltage>
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Terminal<L-Phase>
Connection Terminal<N-Phase>
Connection Terminal<Ground>
52C Relay
Controller Circuit Board
Switch<Display Selection>
Switch<Function Selection>
Switch<Test Run>
Switch<Model Selection>
Switch<Function Selection>

NAME

SW6
SW7
SW8
SWU1
SWU2
CNLVB

Switch<Function Selection>
Switch<Function Selection>
Switch<Function Selection>
Switch<Unit Address Selection, 1st digit>
Switch<Unit Address Selection, 2nd digit>
Connector<To N.F. Board CN52C>
(Symbol of Board is CNLVB)
SS
Connector<Connection For Option>
CN3D
Connector<Connection For Option>
CN3S
Connector<Connection For Option>
CN3N
Connector<Connection For Option>
CN51
Connector<Connection For Option>
LED1,LED2 LED<Operation Inspection Display>
LED3
LED<Power Supply to Main Microcomputer>
Fuse<T6,3AL250V>
F1,F2
X501~505 Relay
M-NET P.B. M-NET Power Circuit Board
TP1
ConnectionTerminal<Ground>

Caution for electrical work


Use copper supply wires.

Cautions when Servicing

S-SERIES

! WARNING: When the main supply is turned off, the voltage [340 V] in the main capacitor will drop to 20 V in approx. 2
minutes (input voltage: 240 V). When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then
wait for at least 1 minute.
Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual.
Do not replace the outdoor board without checking.

NOTES:
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
Bit
Indication

1
Compressor
operated

52C

21S4

SV1

(SV2)

Always lit

[Example]
When the compressor and
SV1 are turned during cooling
operation.
1 23 45 67 8

When fault requiring inspection has occurred


The LED alternately indicates the inspection code and the location of the unit in which
the fault has occurred.

S-SERIES (Feb. 2009)

S-5

4. Electrical Wiring Diagrams

DATA U4
Ref. : PUMY-NHMU_EWD_USDB_P36-48_1

PUMY-P36,48NHMU(-BS)

63H

63L

63HS TH7 TH6 TH3 TH4


C. B.
MF1
MS
3~
MF2
MS
3~

CNF1
7 (WHT)

CNF2
7 (WHT)

CN3D CN3S CN3N


(WHT) (RED) (BLU)

1 3 1
4 1 2 2 1
63HS TH7/6 TH3 TH4
(WHT) (RED) (WHT) (WHT)

LED3

X501

X502

X503

X504

X505

21S4

SW1 SW8 SW2

M-NET P.B.
LED1

LED2
1 CN2 4
(WHT)
TP1 BLK
CN1
(WHT)
1
5

F2

CNS1 CNS2
(RED) (YLW)
1 SS 2 1 CNAC 1 2 1 2
(RED)
(WHT)
2

SV1

*1

F1

1 SV2 2 1 SV1 3
(BLU)
(WHT)

SW6

SW4 SW3 SW7

1 CN51 5
(WHT)

TRANS

1 21S4 3
(GRN)

CN4
CN2
(WHT)
1 (WHT) 7 1 2

1
CNDC
(PNK)

S-SERIES

3 1

SWU2 SWU1 SW5

3
63H
(YLW)

1 52C 3
(BLK)

3 1

1 3
63L
(RED)

3 1

CNLVB
(RED)

CN40
CN41
(WHT) (WHT)
1 4
1
4

CN102
(WHT)
1
4

P. B.

CE +
RED

TB7
M1
M2

YLW 2

TABP1 RED

YLW

MS
3~

BLU

3
1

W
MC

BLK
E2

FOR CENTRALIZED
CONTROL
DC 30V(Non-polar)

L2
GR

S-6

N1
N2
Io

ACTM

RED

BLK
WHT

BLU N I

L2

LI

L1

RED

BLK

CNAC1
(WHT)

RED

DCL

POWER SUPPLY
~/N 208/230V 60Hz
TB1
RED
L1

CN52C
(BLK)

N. F.

CN5
(RED)

2
WHT

TABS WHT

52C

7
1 CN3
2 (WHT)
1 CN5
2 (RED)
1 CN4
2 (WHT)
TABN
TABP

DS2
+

CNAC2
(RED)

TH8

TABT BLU

WHT TABN2

IPM

TABN1
BLK

RED

RED

CN2
(WHT)

TO INDOOR UNIT
CONNECTING WIRES
DC 30V(Non-polar)

CNDC
(PIN) 2
1

6
1

RED TABU
WHT TABV
BLK
TABW

M2

RED 2

TABP2

M1

DS3
+

NO

CNAF
(WHT)

WHT

TB3

LO

EI

BLU

*1 MODEL SELECT 1:ON 0:OFF


SW4
MODELS
1 2 3 4 5 6
PUMY-P36NHMU 0 1 1 0 1 0
PUMY-P48NHMU 0 1 1 0 0 1

GRN

S-SERIES (Feb. 2009)

5. Refrigerant Circuit Diagrams and Thermal Sensors


PUMY-P36,P48-NHMU(-BS)

Service
port
Refrigerant Gas pipe
<5/8 inch>

Stop valve
Strainer

DATA U4

Refrigerant flow in cooling


Refrigerant flow in heating

Pressure sensor
(63HS)
High pressure
switch(63H)
4-way valve
Solenoid
valve(SV1)

Thermistor(TH7)
(Outdoor temperature)

Capillary tube
Thermistor<Saturation temperature
of suction pressure>(TH6)

Strainer

Check valve<Low pressure>


Accumulator

Stop valve

Low pressure
switch(63L)

Check valve
<High pressure>
Oil separator
Strainer

Distributor
Thermistor(TH3)
(Pipe temperature)

Discharge
thermistor(TH4)
Compressor
Heatsink
thermistor(TH8)

S-SERIES

Refrigerant Liquid pipe


<3/8 inch>
Strainer
Service port

Unit: mm<inch>

S-SERIES (Feb. 2009)

S-7

6. Sound Pressure Levels

DATA U4

Measurement condition
PUMY-P36,48NHMU(-BS)

Measurement
location

3-1/4ft. (1m)

4-7/8ft. (1.5m)

UNIT

GROUND

Sound Pressure Level of PUMY-P36NHMU(-BS)

Ref.:PUMY_NHMU_NCC_USDB_P36

90

Heating 60Hz

Octave band sound level (dB)

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Cooling
Heating

60Hz
60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
55.2 49.7 47.9 47.8 43.5 39.1 33.9 35.1 49.0
58.9 53.4 50.1 49.4 45.5 41.2 35.1 38.3 51.0

Sound Pressure Level of PUMY-P48NHMU(-BS)

Ref.:NC_PUMY-P48

90

Cooling 60Hz
Heating 60Hz

80
Octave band sound level (dB)

S-SERIES

Cooling 60Hz
80

70

NC-70

60
NC-60
50

NC-50

40
NC-40
30
NC-30
20

Approximate minimum
audible limit on
continuous noise

10
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band central frequency (Hz)

Cooling
Heating

S-8

60Hz
60Hz

63 125 250 500


1k
2k
4k
8k dB(A)
56.2 50.7 48.9 48.8 44.5 40.1 34.9 36.1 50.0
59.9 54.4 51.1 50.4 46.5 42.2 36.1 39.3 52.0

S-SERIES (Feb. 2009)

7. Capacity Tables
7-1. Correction by Temperature

DATA U4

CITY MULTI systems could have various capacities at different design temperatures. Using the nominal cooling/heating capacity
values and the ratios below, the capacity can be found for different temperatures.
PUMYNominal kW
Cooling
Capacity BTU/h
Input
kW

P36NHMU P48NHMU
10.6

14.1

36,000

48,000

3.22

4.97

S-SERIES

PUMYNominal kW
Heating
Capacity BTU/h
Input
kW

P36NHMU P48NHMU
11.7

15.8

40,000

54,000

2.93

4.88

Ref:cbt_p100-140

S-SERIES (Feb. 2009)

S-9

7. Capacity tables
7-2. Correction by Total Indoor

DATA U4

CITY MULTI systems have different capacities and inputs when different combinations of indoor units with different total
capacities are connected. Using following tables, the maximum capacity can be found to ensure the system is installed with
enough capacity for a particular application.

S-SERIES

7-2-1.PUMY-P36NHMU(-BS)

Capacity(Btu/h)
Power Consumption(kW)
Current(A)/230V
Current(A)/208V
Total capacity
of Indoor units* Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
18
18,000
20,200
1.38
1.45
6.1
6.4
6.8
7.1
19
19,000
21,300
1.45
1.52
6.4
6.7
7.1
7.4
20
20,000
22,400
1.52
1.60
6.7
7.0
7.4
7.8
21
21,000
23,500
1.60
1.67
7.1
7.4
7.8
8.1
22
22,000
24,700
1.68
1.75
7.4
7.7
8.2
8.5
23
23,000
25,800
1.76
1.83
7.8
8.0
8.6
8.9
24
24,000
26,900
1.85
1.91
8.2
8.4
9.0
9.3
25
25,000
28,000
1.94
1.98
8.6
8.7
9.5
9.6
26
26,000
29,200
2.04
2.06
9.0
9.1
9.9
10.0
27
27,000
30,300
2.14
2.15
9.4
9.4
10.4
10.4
28
28,000
31,400
2.24
2.23
9.9
9.8
10.9
10.8
29
29,000
32,500
2.35
2.31
10.4
10.2
11.5
11.2
30
30,000
33,700
2.46
2.40
10.9
10.5
12.0
11.7
31
31,000
34,800
2.58
2.48
11.4
10.9
12.6
12.1
32
32,000
35,900
2.70
2.57
11.9
11.3
13.2
12.5
33
33,000
37,000
2.82
2.66
12.5
11.7
13.8
12.9
34
34,000
38,200
2.95
2.75
13.0
12.1
14.4
13.4
35
35,000
39,300
3.08
2.84
13.6
12.5
15.1
13.8
36
36,000
40,000
3.22
2.93
14.2
12.9
15.7
14.2
37
36,200
40,200
3.23
2.92
14.3
12.9
15.8
14.2
38
36,400
40,400
3.25
2.89
14.3
12.7
15.9
14.1
39
36,600
40,700
3.26
2.86
14.4
12.6
15.9
13.9
40
36,900
40,900
3.27
2.84
14.5
12.5
16.0
13.8
41
37,100
41,100
3.28
2.81
14.5
12.3
16.0
13.6
42
37,300
41,300
3.30
2.78
14.6
12.2
16.1
13.5
43
37,500
41,600
3.31
2.75
14.6
12.1
16.2
13.4
44
37,700
41,800
3.32
2.72
14.7
11.9
16.2
13.2
45
37,900
42,000
3.34
2.69
14.7
11.8
16.3
13.1
46
38,100
42,200
3.35
2.66
14.8
11.7
16.4
12.9
Note)
1. In some combination patterns, numerical value of the heating data may differ slightly (CAPACITY : about
several hundred Btu/h)
2. *. Indoor capacity is described by its model size. For example, PEFY-P08NMSU-E, its capacity is P08.

S-10

S-SERIES (Feb. 2009)

7. Capacity tables

DATA U4

7-2-2.PUMY-P48NHMU(-BS)
Capacity(Btu/h)
Total capacity
of Indoor units* Cooling
Heating
24,000
25,000
26,000
27,000
28,000
29,000
30,000
31,000
32,000
33,000
34,000
35,000
36,000
37,000
38,000
39,000
40,000
41,000
42,000
43,000
44,000
45,000
46,000
47,000
48,000
48,300
48,500
48,700
48,900
49,100
49,300
49,600
49,800
50,000
50,200
50,400
50,600
50,800
51,100

26,900
28,000
29,200
30,300
31,400
32,500
33,700
34,800
35,900
37,000
38,200
39,300
40,400
41,500
42,700
43,800
44,900
46,000
47,200
48,300
49,400
50,500
51,700
52,800
54,000
54,200
54,300
54,400
54,500
54,600
54,800
54,900
55,000
55,100
55,200
55,300
55,500
55,600
55,700

Current(A)/230V

Current(A)/208V

Cooling
Heating
Cooling
Heating
Cooling
Heating
2.11
2.32
9.2
10.2
10.2
11.2
2.20
2.41
9.6
10.5
10.6
11.6
2.29
2.50
10.0
10.9
11.1
12.1
2.38
2.59
10.4
11.3
11.5
12.5
2.48
2.68
10.8
11.7
12.0
13.0
2.58
2.78
11.3
12.1
12.4
13.4
2.68
2.87
11.7
12.6
12.9
13.9
2.78
2.97
12.2
13.0
13.4
14.4
2.89
3.07
12.6
13.4
14.0
14.8
3.00
3.17
13.1
13.9
14.5
15.3
3.11
3.28
13.6
14.3
15.0
15.8
3.23
3.38
14.1
14.8
15.6
16.3
3.35
3.49
14.6
15.2
16.2
16.9
3.47
3.60
15.2
15.7
16.8
17.4
3.60
3.71
15.7
16.2
17.4
17.9
3.72
3.82
16.3
16.7
18.0
18.5
3.85
3.93
16.8
17.2
18.6
19.0
3.99
4.05
17.4
17.7
19.3
19.6
4.12
4.17
18.0
18.2
19.9
20.1
4.26
4.28
18.6
18.7
20.6
20.7
4.41
4.41
19.3
19.3
21.3
21.3
4.55
4.53
19.9
19.8
22.0
21.9
4.70
4.65
20.5
20.3
22.7
22.5
4.85
4.78
21.2
20.9
23.4
23.1
4.97
4.88
21.7
21.3
24.0
23.6
4.98
4.83
21.8
21.1
24.1
23.3
4.99
4.79
21.8
20.9
24.1
23.2
5.00
4.75
21.8
20.8
24.1
23.0
5.01
4.71
21.9
20.6
24.2
22.8
5.01
4.67
21.9
20.4
24.2
22.6
5.02
4.63
21.9
20.2
24.3
22.4
5.03
4.59
22.0
20.1
24.3
22.2
5.04
4.55
22.0
19.9
24.3
22.0
5.04
4.51
22.0
19.7
24.4
21.8
5.05
4.47
22.1
19.5
24.4
21.6
5.06
4.43
22.1
19.4
24.4
21.4
5.07
4.39
22.1
19.2
24.5
21.2
5.07
4.35
22.2
19.0
24.5
21.0
5.08
4.31
22.2
18.8
24.6
20.8

Note)
1. In some combination patterns, numerical value of the heating data may differ slightly (CAPACITY : about
several hundred Btu/h)
2. *. Indoor capacity is described by its model size. For example, PEFY-P08NMSU-E, its capacity is P08.

S-SERIES (Feb. 2009)

S-11

S-SERIES

24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62

Power Consumption(kW)

7. Capacity Tables

DATA U4

7-3. Correction by Refrigerant Piping Length


CITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating capacity could be
reduced. Using the following correction factor by equivalent piping length shown at 7-3-1 and 7-3-2, capacity can be found. 7-3-3
shows how to obtain the equivalent piping length.
7-3-1. Cooling Capacity Correction
PUMY-P48NHMU

PUMY-P36NHMU

0.95

Tota
l

0.9

capa

city

of in

doo

0.85

it

0.8
0.75
0.7
0.65
7 10
23 33

15
49

20
66

25
82

30 35 40 45 50 55 60 65 70 75 80 m
98 115 131 148 164 180 197 213 230 246 262 ft

Piping equivalent length

Ref.: CbRPL_PUMY-P36NHMU_C

7-3-2. Heating Capacity Correction


PUMY-P-NHMU
1.00
Heating capacity correction factor

S-SERIES

r un

0.95

0.90

7 10
23 33

15
49

20
66

25
82

30 35 40 45 50 55 60 65 70 75 80 m
98 115 131 148 164 180 197 213 230 246 262 ft

Piping equivalent length

Ref.: PUMY_NHMU_C32_USDB

7-3-3. How to Obtain the Equivalent Piping Length

S-12

S-SERIES (Feb. 2009)

Cooling capacity correction factor

Cooling capacity correction factor

0.95
Tota
l

0.9
0.85

cap

acit

y of

indo

or u

nit

0.8
0.75
0.7
0.65
7 10
23 33

15
49

20
66

25
82

30 35 40 45 50 55 60 65 70 75 80 m
98 115 131 148 164 180 197 213 230 246 262 ft

Piping equivalent length

Ref.: CbRPL_PUMY-P48NHMU_C

7. Capacity tables

DATA U4

7-4. Correction at Frost and Defrost


Due to frost on the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be
calculated by multiplying the correction factor shown in the table below.
Correction Factor Table when Frost and Defrost Occurs

WB
WB

7-5. Operation Temperature Range

Indoor temperature

86 30
77 25
68 20
59 15
50 10
5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

25
77

30
86

35
95

40
104

45
113

50
122

25
77

30
86

35
95

40
104

45
113

50
122

S-SERIES

41

Outdoor temperature

Indoor temperature

86 30
77 25
68 20
59 15
50 10
41

5
-20
-4

-15
5

-10
14

-5
23

0
32

5
41

10
50

15
59

20
68

Outdoor temperature
Ref.: tr-NHMU-S
* Tables above show published performance operation range. Units will try to continue to cool and heat above and below temperature range
shown, but there is no published performance data at these ranges.

S-SERIES (Feb. 2009)

S-13

8. Optional Parts
8-1. Branch Joint

DATA U4

CITY MULTI piping can be easily done with branch joints and headers provided by MITSUBISHI ELECTRIC CORP. There is
one branch joint set used for piping PUMY-P-NHMU. Details for installing the branch joint can be found in the System Design
sections, or in the PUMY-P-NHMU Installation Manual.
Ref.: 7FAGFA
in.

CMY-Y62-G
1. Specification

Inner Diameter

Inner Diameter

A (Inner Diameter)
1/2"
3/4"

B (Outer Diameter)
3/8"
5/8"

Inner Diameter

4-7/32"

3-5/32"

C
2-15/16"

Pipe cover

C (Inner Diameter)
1/4"
1/2"
1/2"
5/8"

5-29/32"
3-15/16"

S-14

5/8" Note) Connection only to downstream units

(External view :
2-15/16"X3-15/16"X1-23/32")
Inner Diameter
3/4"

Inner Diameter
3/4"

Number of reducers
2
1

3/4"

7/8"

Inner Diameter

For gas pipe:

3/8"

3-5/32"

Outer Diameter

3-9/32"

1-25/32"

3-3/16"
3-15/16"

3/8"

1-31/32"

S-SERIES

(External view :
3-9/32"X3-3/16"X1-23/32")

Reducer (Accessory):

Pipe cover

Inner Diameter

3/8" Note) Connection only to downstream units

3-5/32"
4-1/8"

1-9/16"

For liquid pipe:

2. External drawing

S-SERIES (Feb. 2009)

3-5/32"

D (Outer Diameter)
3/8"
5/8"
3/4"
3/4"

Outer Diameter

Accessory

Main

Details
2 ports
One for each liquid and gas pipe
Phosphorus deoxidized copper C1220T-OL (JIS H3300)
Foamed polyethylene (one for each liquid and gas pipe)
10 reducers of 7 types (Refer to the external drawing for details.)

Inner Diameter

Items
Number of ports
Number of branch joints
Pipe material
Insulation material
Reducer

Number of reducers
2
1
1
2

8. Optional Parts
8-2. Header

DATA U4

CITY MULTI piping can be easily done with branch joints and headers provided by MITSUBISHI ELECTRIC CORP. There are
two header sets used for piping PUMY-P-NHMU. Details for installing the headers can be found in the System Design sections,
or in the PUMY-P-NHMU Installation Manual.
Ref.: 7FAGFB
in.

CMY-Y64-G
1. Specification
Items
Number of ports
Number of branch joints
Pipe material
Insulation material
Reducer
Cap

Main

Accessory

Details
3 ~ 4 ports
One for each liquid and gas pipe
Phosphorus deoxidized copper C1220T-OL (JIS H3300)
Foamed polyethylene
7 reducers of 5 types
2 caps of 2 different types for each liquid and gas pipe ; 4 caps in total

2. External drawing
For liquid pipe:

Reducer (Accessory):
13-25/32"

Dimension table
B

Symbol

2-3/8"

2-3/8"

1-31/32"

19/32"
2-23/32"

7/8"(Inner Diameter)

3-5/32"

3/4"(Inner Diameter)

C (Inner Diameter)
5/8"
3/8"

25 /32"

D (Outer Diameter)
3/4"
1/2"

Number of reducers
1
1

Dimension table

D
D

Symbol

2-3/8"

1/4"
3/8"

14-3/16"

1/4"

3/8"

Inner Diameter
(mm)

Number of reducers
1
2

S-SERIES

For gas pipe:

2-3/8"

B (Outer Diameter)
5/8"
1/2"

2-3/8"

A (Inner Diameter)
3/4"
5/8"

4-1/2"

13/32"
2-5/16"

3-5/32"

13 /32"

5-3/32"

3/8"(Inner Diameter)

1/2"(Inner Diameter)

2-3/8"

2-3/8"

2-3/8"

2-3/8"

Inner Diameter
(mm)
1/2"
5/8"

Ref.: 7FAGFC
in.

CMY-Y68-G
1. Specification
Items
Number of ports
Number of branch joints
Pipe material
Insulation material
Reducer
Cap

Main

Accessory

Details
5 ~ 8 ports
One for each liquid and gas pipe
Phosphorus deoxidized copper C1220T-OL (JIS H3300)
Foamed polyethylene
3 reducers of 3 types
3 caps for each liquid and gas pipe ; 6 in total

2. External drawing
For liquid pipe:

Reducer (Accessory):
Insulation material (Accessory)

1/2"(Inner Diameter)

B
A

B
A

B
A

B
A

Dimension table
2-3/8"

2-3/8"

2-3/8"

2-3/8"
2-3/8"
21-27/32"

2-3/8"

2-3/8"

2-15/16"

B
3-5/32"

Symbol
A
B

A (Inner Diameter)
3/4"
1/2"

B (Outer Diameter)
5/8"
3/8"

Number of reducers
1
1

Inner Diameter
(mm)
1/4"
3/8"

For gas pipe:

2-1/ 16"
2-3/16"
4-9/16"
6-5/32"

24-1/2"

3-5/32"

2-1/ 16"

24-1/2"

7/8"(Inner Diameter)
3/4"(Inner Diameter)

D
C
2-3/8"

2-3/8"

C
D

2-3/8"

2-3/8"

2-3/8"
23-5/8"

2-3/8"

2-3/8"

C (Inner Diameter)
5/8"
2-1/2"
5-1/16"
6-5/32"

Insulation material (Accessory)

Number of reducers
1

Dimension table
Symbol

4-23/32"

D (Outer Diameter)
3/4"

C
D

Inner Diameter
(mm)
1/2"
5/8"

S-SERIES (Feb. 2009)

S-15

DATA
DATAU4
U3

GENERAL
GENERALLINE-UP...........................................................................................................................................................
LINE-UP.....................................................................................................................................ID-1
1
Ceiling-concealed (Low/High-static Pressure)..............................................................................................................PEFY-1
PEFY-P-NMSU-E/PEFY-P-NMHU-E

Ceiling concealed (Low/High static pressure type) ........................................................................... IU - A -1

Ceiling-concealed
(Ducted)...........................................................................................................................................PDFY-1
PEFY-P-NMLU-E/PEFY-P-NMHU-E
PDFY-P-NMU-E

Ceiling concealed (All fresh air type) ................................................................................................ IU - B -1

Ceiling-recessed Cassette (One-way Airflow).............................................................................................................. PMFY-1


PEFY-P-NMHU-E-F
PMFY-P-NBMU-E

Ceiling mounted(Built-in type)........................................................................................................... IU - C -1

Ceiling-recessed Cassette (Four-way Airflow)............................................................................................................... PLFY-1


PDFY-P-NMU-E
PLFY-P-NCMU-E/PLFY-P-NBMU-E

Cassette ceiling .(1-way


flow type) .................................................................................................... IU - D -1
Ceiling-suspended.
.......................................................................................................................................................PCFY-1
PCFY-P-NGMU-E
PMFY-P-NBMU-E
Wall-mounted................................................................................................................................................................PKFY-1
Cassette ceiling (2-way flow type) .................................................................................................... IU - E -1
PKFY-P-NAMU-E, NGMU-E, NFMU-E
PLFY-P-NLMU-E
Floor-standing
(Exposed/Concealed).
...........................................................................................................................
Cassette ceiling
(4-way flow type)
.................................................................................................... IU PFFY-1
- F -1
PFFY-P-NEMU-E/PFFY-P-NRMU-E
PLFY-P-NAMU-E
Vertical/Concealed........................................................................................................................................................PVFY-1
Ceiling suspended ............................................................................................................................IU - G -1
PVFY-P-E00A
PCFY-P-NGMU-E
Nominal Capacity Tables.................................................................................................................................................NCT-1

Wall mounted .................................................................................................................................... IU - H -1

BC Controller (with R2-Series PURY-P-T/Y(S)HMU-A).....................................................................................................BC-1


PKFY-P-NAMU-E, NGMU-E, NFMU-E
CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/CMB-p-NU-HB

Floor standing (Exposed type/Concealed type) ................................................................................. IU - I -1

LOSSNAY. ....................................................................................................................................................................ERV-1
PFFY-P-NEMU-E/PFFY-P-NRMU-E
LGH-F-RX3-E

LOSSNAY ..........................................................................................................................................IU - J -1
LGH-F-RX3-E

BC controller (with R2 PURY)........................................................................................................... IU - K -1


CMB-P-NU-G, NU-GA, NU-GB

INDOOR UNITS (Feb. 2009)


INDOOR UNITS

ID-1
1

INDOOR UNITS

CITY
MULTITM
CITY MULTI
INDOOR
UNITS
INDOOR UNITS

General Line-UP

DATA U4

INDOOR UNITS

Line-up of CITY MULTI R410A Indoor Units


All the indoor units are subject to UL regulation.
P06
P08
Model size
0.5
0.67
TON
Nominal cooling cap.*1 BTU/h
6,000
8,000
1.8
2.3
kW
6,700
9,000
Nominal heating cap.*2 BTU/h
2.0
2.6
kW
Ceiling concealed

Model size
PEFY-P-NMSU-E
PEFY-P-NMHU-E

P06

P08

P12
1.0
12,000
3.5
13,500
4.0

P15
1.25
15,000
4.4
17,000
5.0

P18
1.5
18,000
5.3
20,000
5.9

Model size
PMFY-P-NBMU-E
PLFY-P-NCMU-E
PLFY-P-NBMU-E

P27
2.25
27,000
7.9
30,000
8.8

P30
2.5
30,000
8.8
34,000
10.0

PEFY-P-NMSU-E

P12

P15

P18

P24

Ceiling concealed

Model size
PDFY-P-NMU-E
Ceiling cassette

P24
2.0
24,000
7.0
27,000
7.9

P36
3.0
36,000
10.6
40,000
11.7

P48
4.0
48,000
14.1
54,000
15.8

P54
4.5
54,000
15.8
60,000
17.6

P72
6.0
72,000
21.1
80,000
23.4

P96
8.0
96,000
28.1
108,000
31.7

PEFY-P-NMHU-E

P27

P30

P36

P48

P54

P72

P96

P36

P48

P54

P72

P96

PDFY-P-NMU-E

P06

P08

P12

P15

P18

P24

PMFY-P-NBMU-E

P06

P08

P12

P15

P27

P30

PLFY-P-NBMU-E

PLFY-P-NCMU-E

P18

P24

Ceiling suspended

P27

P30

P36

P48

P54

P72

P96

P36

P48

P54

P72

P96

PCFY-P-NGMU-E

Model size
PCFY-P-NGMU-E
Wall mounted

P06

Model size
PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E
Floor standing

P06

Model size
PFFY-P-NEMU-E
PFFY-P-NRMU-E

P06

P08

P12

P15

P18

PKFY-P-NAMU-E

P08

P12

P24

P27

P30

PKFY-P-NGMU-E

P15

P18

P24

P27

PKFY-P-NFMU-E

P30

P48

P54

P72

P96

PFFY-P-NRMU-E

PFFY-P-NEMU-E

P08

P36

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

Model size
P06
P08
P12
PVFY-P-E00A
* Refer to notes *1 and *2 on the Specification sheet pages.

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

Vertical concealed

ID-2

INDOOR UNITS (Feb. 2009)

Ceiling-concealed (Low/High-static Pressure)

DATA U4

PEFY-P-NMSU-E/PEFY-P-NMHU-E

1. SPECIFICATIONS...................................................................................................................................................PEFY-3
2. EXTERNAL DIMENSIONS......................................................................................................................................PEFY-8
3. Center of Gravity.........................................................................................................................................PEFY-11

5. SOUND Pressure LEVELS..............................................................................................................................PEFY-15


5-1. Sound Pressure Levels...............................................................................................................................PEFY-15
5-2. NC Curves...................................................................................................................................................PEFY-15
6. FAN CHARACTERISTIC CURVES.......................................................................................................................PEFY-21
7. OPTIONAL PARTS................................................................................................................................................PEFY-27
7-1. Optional Parts Line Up for the Indoor Unit..................................................................................................PEFY-27
7-2. Long-life Filter PAC-KE-LAF and Filter Box PAC-KE-TB-F for PEFY-P-NMHU-E........................................PEFY-27
7-3. Drain Pump Kit PAC-KE04DM-F for PEFY-P-NMHU-E...............................................................................PEFY-28
7-4. External Heater Adapter PAC-YU24HT . ....................................................................................................PEFY-28
7-5. External Heater Adapter PAC-YU25HT . ....................................................................................................PEFY-29

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

PEFY-1

PEFY-P-NMSU-E
PEFY-P-NMHU-E

4. ELECTRICAL WIRING DIAGRAMS......................................................................................................................PEFY-12

Ceiling-concealed (Low/High-static Pressure)

DATA U4

PEFY-P-NMSU-E
PEFY-P-NMHU-E
PEFY-P-NMSU-E

Flexible design allows for elegant interior layout

The PEFY models are high-performance, ceiling-concealed indoor units. in fact, if it werent for the constantly comfortable environment these units deliver, you
would not know they were there. The ducted fan coils are designed to be installed above the ceiling, hidden from public view, and theyre extremely quiet with
lowest sound of 22 dBa. The PEFY are extremely easy to access and maintain according to their application. They open on one side so you can easily access
the fan or motor for maintenance. They can be easily customized to your cooling and heating needs. The external static pressure settings are adjustable to
meet different application conditions such as the use of a high performance filter.

7-7/8" extremely thin body of PEFY-NMSU-E requires less ceiling space

10 mm
[13/32 in]
or more

100 mm
[3-15/16 in]
or more

the additional external static pressure up to 0.8 in.wg


on PEFY-NMHU-E provides exibility for duct extension,
branching, and air outlet conguration.

600 mm [23-5/8 in] or more

200 [7-7/8]

PEFY-P-NMSU-E
PEFY-P-NMHU-E

PEFY-P-NMHU-E

long room
Service space (viewed from the side)

Access door

PEFY-P06,08,12,15,18,24NMSU-E Model

l-shaped rooms

Ceiling surface

room with fixed


ceiling fixtures

unit: mm(in.)

For PEFY-P-NMHU-E,
all the maintenance work
can be done from the side
inspection hole.

operation
PEFY-P06NMSU-E
PEFY-P08NMSU-E
PEFY-P12NMSU-E
PEFY-P15NMSU-E
PEFY-P18NMSU-E
PEFY-P24NMSU-E

Low airflow
22 dBa
23 dBa
23 dBa
28 dBa
30 dBa
30 dBa

Middle airflow
24 dBa
26 dBa
28 dBa
30 dBa
34 dBa
35 dBa

High airflow
28 dBa
30 dBa
35 dBa
33 dBa
37 dBa
40 dBa

* (Details are referred to in the specification sheet.)

Ceiling concealed

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PEFY-P-NMSU-E
PEFY-P-NMHU-E
* Refer to the Nominal conditions *1, *2 in the Specification sheet.

PEFY-2

PEFY-P-NMSU-E/PEFY-P-NMHU-E
* Refer to the Nominal conditions
*1, *2 in the Specification sheet.

(Feb. 2009)

1. Specifications

DATA U4

Model
Power source

Pefy-p06nmsu-e
Btu / h

Cooling capacity *1
(Nominal)

6,000

kW
Power input
Current input

Heating capacity *2
(Nominal)

1.8

2.3

3.5

4.4

0.06/0.06
0.51/0.49
9,000
2.6
0.04/0.04
0.41/0.39

0.07/0.07
0.56/0.53
13,500
4.0
0.05/0.05
0.46/0.43

0.07/0.07
0.57/0.55
17,000
5.0
0.05/0.05
0.47/0.45

7-7/8 X 31-1/8 x 27-9/16

7-7/8 X 31-1/8 x 27-9/16

7-7/8 X 31-1/8 x 27-9/16

7-7/8 x 39 x 27-9/16

Galvanized
in.

External dimension H x W x D

mm
Lbs (kg)

Net weight
Heat exchanger
Type x quantity

in.WG
External
Static pressure

Pa
in.WG

Pa
Motor type
Motor output
kW
Driving mechanism
cfm
Airflow rate
m3 / min.
(Low-Mid-High)
L/s
dB <A>
Sound pressure level (Low-Mid-High)
dB<A>
(Measured in anechoic room)
dB <A>
Insulation material
Air filter
Protection Device
Refrigerant Control Device
Connectable Outdoor Unit
Fan

Liquid (R410a)
(R22 )
Gas
(R410a)
(R22 )

Diameter of drain pipe


Drain life mechanism
Drawing
Standard
Attachment
Optional Parts

Remark

Indoor:
Outdoor:
Pipe length:

in. (mm)

in. (mm)
in. (mm)
in. (mm)

External
Wiring
Refrigerant cycle
Document
Accessory
External heater adaptor

200 X 790 x 700


42(19)
Sirocco fan x 2
0.02-0.06-0.14-0.20
(208v)
5-15-35-50
0.02-0.06-0.14-0.20
(230v)
5-15-35-50
0.096
176-212-247
5-6-7
83-100-117
22-24-28 (208v)
22-24-28 (230v)
-

*3
1/4 (6.35) Brazed

200 X 790 x 700


200 X 790 x 700
42(19)
46(20)
Cross fin(aluminium fin and copper tube)
Sirocco fan x 2
Sirocco fan x 2
0.02-0.06-0.14-0.20
0.02-0.06-0.14-0.20
(208v)
(208v)
5-15-35-50
5-15-35-50
0.02-0.06-0.14-0.20
0.02-0.06-0.14(230v)
0.20(230v)
5-15-35-50
5-15-35-50
DC brushless motor
0.096
0.096
Direct-driven
194-247-317
211-282-370
5.5-7-9
6-8-10.5
91-116-150
100-133-175
23-26-30 (208v)
23-28-35 (208v)
23-26-30 (230v)
23-28-35 (230v)
Polystyrene foam,polyethylene foam,urethane foam
PP honeycomb fabric (washable)
Fuse
Lev
R410a,r22 city multi R410a,r22 city multi
1/4 (6.35) Brazed
1/4 (6.35) Brazed

200 x 990 x 700


54(24)
Sirocco fan x 3
0.02-0.06-0.14-0.20
(208V)
5-15-35-50
0.02-0.06-0.140.20(230V)
5-15-35-50
0.096
282-335-388
8-9.5-11
133-158-183
28-30-33 (208V)
28-30-33 (230V)
-

R410A,R22 CITY MULTI


1/4 (6.35) Brazed

1/4 (6.35) Brazed

1/4 (6.35) Brazed

1/4 (6.35) Brazed

1/4 (6.35) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

O.D. 1-1/4(32)
21-11/16 (551)

Pac-yu25ht

O.D. 1-1/4(32)
O.D. 1-1/4(32)
21-11/16 (551)
21-11/16 (551)
Wkb94l522
Wkb94l523
Installation manual, instruction book
Drain hose (flexible joint)
Pac-yu25ht
Pac-yu25ht

O.D. 1-1/4(32)
21-11/16 (551)

PAC-YU25HT

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local
codes.
Installation

Note:

15,000

0.05/0.05
0.42/0.41
6,700
2.0
0.03/0.03
0.32/0.31

kW
A
Btu / h
kW
kW
A

External finish

Diameter of
refrigerant pipe
(O.D.)

PEFY-P15NMSU-E

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.

*1 Nominal cooling conditions


80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B. (21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B. / 43degF W.B.


(8.3degC D.B. / 6.1degC W.B.)

25 ft. (7.6 m)

25 ft. (7.6 m)

Level difference:
0 ft. (0 m)
0 ft. (0 m)
*3 PUHY-THMU,PURY-THMU,PUHY-YHMU,PURY-YHMU,PUMY-NHMU
*The external static pressure is set to 15 Pa at factory shipment.
*Due to continuing improvement, above specification may be subject to change without notice.

Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm = m3/min x 35.31
lbs = kg / 0.4536
*Above specification data is
subject to rounding variation.

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

PEFY-3

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Power input
Current input

Pefy-p08nmsu-e
Pefy-p12nmsu-e
1-Phase 208/230v 60hz
8,000
12,000

1. Specifications
Model
Power source
Cooling capacity *1
(Nominal)
Power input
Current input
Heating capacity *2
(Nominal)

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Power input
Current input

DATA U4

Btu / h
kW
kW
A
Btu / h
kW
kW
A

External finish
in.
mm
Lbs (kg)

External dimension H x W x D
Net weight
Heat exchanger
Type x quantity
External
Static pressure

in.WG
Pa
in.WG
Pa

Motor type
Motor output
kW
Driving mechanism
cfm
Airflow rate
m3 / min.
(Low-Mid-High)
L/s
dB <A>
Sound pressure level (Low-Mid-High)
dB<A>
(Measured in anechoic room)
dB <A>
Insulation material
Air filter
Protection Device
Refrigerant Control Device
Connectable Outdoor Unit
Fan

Diameter of
refrigerant pipe
(O.D.)

Standard
Attachment
Optional Parts

Remark

Indoor:
Outdoor:
Pipe length:

Galvanized
7-7/8 x 39 x 27-9/16
7-7/8 x 46-7/8 x 27-9/16
200 x 990 x 700
200 x 1190 x 700
54(24)
62(28)
Cross fin(Aluminium fin and copper tube)
Sirocco fan x 3
Sirocco fan x 4
0.02-0.06-0.14-0.20 (208V)
0.02-0.06-0.14-0.20(208V)
5-15-35-50
5-15-35-50
0.02-0.06-0.14-0.20 (230V)
0.02-0.06-0.14-0.20(230V)
5-15-35-50
5-15-35-50
DC brushless motor
0.096
0.096
Direct-driven
353-441-529
423-565-706
10-12.5-15
12-16-20
167-208-250
200-267-333
30-34-37 (208V)
30-35-40 (208V)
30-34-37 (230V)
30-35-40 (230V)
Polystyrene foam,Polyethylene foam,Urethane foam
PP Honeycomb fabric (washable)
Fuse
LEV
R410A,R22 CITY MULTI
R410A,R22 CITY MULTI
1/4 (6.35) Brazed
3/8 (9.52) Brazed
3/8 (9.52) Brazed
3/8 (9.52) Brazed

Gas
(R410a)
(R22 )

in. (mm)

1/2 (12.7) Brazed


5/8 (15.88) Brazed

5/8 (15.88) Brazed


5/8 (15.88) Brazed

in. (mm)
in. (mm)

O.D. 1-1/4(32)
21-11/16 (551)

O.D. 1-1/4(32)
21-11/16 (551)

External
Wiring
Refrigerant cycle
Document
Accessory
External heater adaptor

WKB94L522
WKB94L523
Installation Manual, Instruction Book
Drain hose (flexible joint)
PAC-YU25HT

PAC-YU25HT

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local
codes.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.

*1 Nominal cooling conditions


80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B. (21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B. / 43degF W.B.


(8.3degC D.B. / 6.1degC W.B.)

25 ft. (7.6 m)

25 ft. (7.6 m)

Level difference:
0 ft. (0 m)
0 ft. (0 m)
*3 PUHY-THMU,PURY-THMU,PUHY-YHMU,PURY-YHMU,PUMY-NHMU
*The external static pressure is set to 15 Pa at factory shipment.
*Due to continuing improvement, above specification may be subject to change without notice.

PEFY-4

24,000
7.0
0.12/0.12
0.98/0.93
27,000
7.9
0.10/0.10
0.88/0.83

in. (mm)

Installation

Note:

PEFY-P24NMSU-E

Liquid (R410a)
(R22 )

Diameter of drain pipe


Drain life mechanism
Drawing

PEFY-P18NMSU-E
1-phase 208/230V 60Hz
18,000
5.3
0.09/0.09
0.74/0.70
20,000
5.9
0.07/0.07
0.64/0.60

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm = m3/min x 35.31
lbs = kg / 0.4536
*Above specification data is
subject to rounding variation.

1. SPECIFICATIONS
1. Specifications

DATA U3

DATA U4

Model

PEFY-P15NMHU-E

PEFY-P18NMHU-E

Power source

PEFY-P24NMHU-E

PEFY-P27NMHU-E

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW
Power input

kW

Current input

15,000

18,000

24,000

4.4

5.3

7.0

7.9

0.188/0.207

0.188/0.207

0.245/0.270

0.270/0.297

0.96/1.06

0.96/1.06

1.25/1.38

1.37/1.51

17,000

20,000

27,000

30,000

5.0

5.9

7.9

8.8

0.188/0.207

0.188/0.207

0.245/0.270

0.270/0.297

0.96/1.06

0.96/1.06

1.25/1.38

1.37/1.51

Galvanized

External dimension H x W x D
Net weight

in.

14-31/32 x 29-17/32 x 35-7/16

14-31/32 x 29-17/32 x 35-7/16

14-31/32 x 29-17/32 x 35-7/16

14-31/32 x 39-3/8 x 35-7/16

mm

380 x 750 x 900

380 x 750 x 900

380 x 750 x 900

380 x 1,000 x 900

98 (44)

100 (45)

100 (45)

111 (50)

lbs (kg)

Heat exchanger

Cross fin(Aluminium fin and copper tube)

FAN

Type x Quantity

Sirocco fan x 1

External
static
static pressure
press

in.WG

Sirocco fan x 1

0.201-0.642 (208V)

Pa

50-160

in.WG

Sirocco fan x 1

0.201-0.642 (208V)

0.201-0.642 (208V)

50-160

50-160

Sirocco fan x 1
0.201-0.642 (208V)
50-160

0.401-0.602-0.803 (230V)

0.401-0.602-0.803 (230V)

0.401-0.602-0.803 (230V)

0.401-0.602-0.803 (230V)

100-150-200

100-150-200

100-150-200

100-150-200

Pa
Motor type

1-phase induction motor

Motor output

kW

0.130

0.130

0.180

Driving mechanism

0.220

Direct-driven

Airflow rate

cfm

353-494

353-494

477-671

547-777

(Low-High)

m3 / min

10.0-14.0

10.0-14.0

13.5-19.0

15.5-22.0

167-233

167-233

225-317

258-367

Sound
Pressure
Level (Low-High)
Noise level
(Low-High)

dB <A>

L/s

25-32 (208V)

25-32 (208V)

29-36 (208V)

30-38 (208V)

(measured in anechoic room)

dB <A>

34-39 (230V)

34-39 (230V)

36-41 (230V)

35-41 (230V)

dB <A>

Insulation material

Polystyrene foam,Polyethylene foam,Urethane foam

Air filter

Optional parts
See Optional

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22 )
Gas

(R410A)
(R22 )

Field drain pipe size


Drawing

in. (mm)
in. (mm)
in. (mm)

1/4 (6.35) Flare

1/4 (6.35) Flare

3/8 (9.52) Flare

1/4 (6.35) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

1/2 (12.7) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

External

W277664

Wiring

W660134

Refrigerant cycle

3/8 (9.52) Flare

Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

Drain pump kit

PAC-KE04DM-F

PAC-KE04DM-F

PAC-KE04DM-F

PAC-KE04DM-F

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

Filter box

PAC-KE63TB-F

PAC-KE63TB-F

PAC-KE63TB-F

PAC-KE80TB-F

Long life filter

PAC-KE86LAF

PAC-KE86LAF

PAC-KE86LAF

PAC-KE88LAF

Drain hose I.D. 1-1/4inch (32mm)(flexible joint)

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PEFY-P15-27NMHU-E

PEFY-P-NMLU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

IU - A - 4
PEFY-5

PEFY-P-NMSU-E
PEFY-P-NMHU-E

External finish

27,000

1. Specifications
SPECIFICATIONS
1.

DATA U3

DATA U4

Model

PEFY-P30NMHU-E

PEFY-P36NMHU-E

Power source
Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

PEFY-P-NMSU-E
PEFY-P-NMHU-E

PEFY-P48NMHU-E

PEFY-P54NMHU-E

1-phase 208/230 V 60Hz

Heating capacity

*2 BTU / h

(Nominal)

*2 kW
Power input

kW

Current input

30,000

36,000

48,000

8.8

10.6

14.1

15.8

0.326/0.360

0.683/0.754

0.683/0.754

0.695/0.767

1.66/1.83

3.38/3.73

3.38/3.73

3.43/3.78

34,000

40,000

54,000

60,000

10.0

11.7

15.8

17.6

0.326/0.360

0.683/0.754

0.683/0.754

0.695/0.767

1.66/1.83

3.38/3.73

3.38/3.73

3.43/3.78

External finish

Galvanized

External dimension H x W x D
Net weight

in.

14-31/32 x 39-3/8 x 35-7/16

14-31/32 x 47-1/4 x 35-7/16

14-31/32 x 47-1/4 x 35-7/16

14-31/32 x 47-1/4 x 35-7/16

mm

380 x 1,000 x 900

380 x 1,200 x 900

380 x 1,200 x 900

380 x 1,200 x 900

111 (50)

155 (70)

155 (70)

155 (70)

lbs (kg)

Heat exchanger
FAN

54,000

Cross fin(Aluminium fin and copper tube)


Type x Quantity
External

in.WG

static
static pressure
press

Pa

Sirocco fan x 1

Sirocco fan x 2

0.201-0.642 (208V)

0.201-0.642 (208V)

50-160

in.WG

Sirocco fan x 2
0.201-0.642 (208V)
50-160

50-160

0.401-0.602-0.803 (230V)

0.401-0.602-0.803 (230V)

0.401-0.602-0.803 (230V)

0.401-0.602-0.803 (230V)

100-150-200

100-150-200

100-150-200

100-150-200

Pa

50-160

Sirocco fan x 2
0.201-0.642 (208V)

Motor type

1-phase induction motor

Motor output

kW

0.230

0.400

Driving mechanism

0.400

0.400

Direct-driven

Airflow rate

cfm

636-883

936-1,342

936-1,342

989-1,412

(Low-High)

m3 / min

18.0-25.0

26.5-38.0

26.5-38.0

28.0-40.0

L/s

300-417

442-633

442-633

467-667

Sound
Pressure
Level (Low-High)
Noise level
(Low-High)

dB <A>

33-40 (208V)

31-41 (208V)

31-41 (208V)

31-41 (208V)

(measured in anechoic room)

dB <A>

38-43 (230V)

38-44 (230V)

38-44 (230V)

38-44 (230V)

dB <A>

Insulation material

Polystyrene foam,Polyethylene foam,Urethane foam

Air filter

See Optional
Optional parts

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22 )
Gas

(R410A)
(R22 )

Field drain pipe size


Drawing

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

3/4 (19.05) Flare

3/4 (19.05) Flare

3/4 (19.05) Flare

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

in. (mm)
in. (mm)
in. (mm)

External

W277664

Wiring

W660134

Refrigerant cycle
Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

Drain pump kit

PAC-KE04DM-F

PAC-KE04DM-F

Drain hose I.D. 1-1/4inch (32mm)(flexible joint)


PAC-KE04DM-F

PAC-KE04DM-F

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

Filter box

PAC-KE80TB-F

PAC-KE140TB-F

PAC-KE140TB-F

PAC-KE140TB-F

Long life filter

PAC-KE88LAF

PAC-KE89LAF

PAC-KE89LAF

PAC-KE89LAF

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PEFY-P30-54NMHU-E

PEFY-6

PEFY-P-NMLU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

IU - A - 5

1. SPECIFICATIONS
1. Specifications

DATA U3

DATA U4

Model

PEFY-P72NMHU-E

PEFY-P96NMHU-E

72,000

96,000

Power source

3-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW

21.1

28.1

1.352/1.495

1.690/1.870

4.48/4.94

5.69/6.28

80,000

108,000

23.4

31.7

1.352/1.495

1.690/1.870

Power input

kW

Current input

4.48/4.94

5.69/6.28

in.

18-17/32 x 49-7/32 x 44-1/8

18-17/32 x 49-7/32 x 44-1/8

mm

470 x 1,250 x 1,120

470 x 1,250 x 1,120

221 (100)

221 (100)

Sirocco fan x 2

Sirocco fan x 2

0.281-0.642 (208V)

0.281-0.642 (208V)

External finish

Galvanized

Net weight

lbs (kg)

Heat exchanger
FAN

PEFY-P-NMSU-E
PEFY-P-NMHU-E

External dimension H x W x D

Cross fin(Aluminium fin and copper tube)


Type x Quantity
External
static
static pressure
press

in.WG
Pa

70-160

70-160

0.401-0.803 (230V)

0.401-0.803 (230V)

Pa

100-200

100-200

kW

0.650

0.850

cfm

2,048

2,541

m3 / min

58.0

72.0

L/s

967

1,200

in.WG
Motor type

3-phase induction motor

Motor output
Driving mechanism
Airflow rate

Direct-driven

Sound
Pressure Level (Low-High)
Noise level

dB <A>

45 (208V)

52 (208V)

(measured in anechoic room)

dB <A>

47 (230V)

54 (230V)

dB <A>

Insulation material

Polystyrene foam,Polyethylene foam,Urethane foam

Air filter

See Optional
Optionalparts

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22 )
Gas

(R410A)
(R22 )

Field drain pipe size


Drawing

in. (mm)
in. (mm)

3/8 (9.52) Brazed

3/8 (9.52) Brazed

1/2 (12.7) Brazed

1/2 (12.7) Brazed

3/4 (19.05) Brazed

7/8 (22.2) Brazed

1 (25.4) Brazed

1-1/8 (28.58) Brazed

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

in. (mm)

External

W277665

Wiring

W660130

Refrigerant cycle
Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

Drain pump kit

PAC-KE04DM-F

Drain hose I.D. 1-1/4inch (32mm)(flexible joint)

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

Filter box

PAC-KE250TB-F

PAC-KE250TB-F

Long life filter

PAC-KE85LAF

PAC-KE85LAF

PAC-KE04DM-F

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PEFY-P72-96NMHU-E

PEFY-P-NMLU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

IU - A - 6
PEFY-7

100 (3-15/16)

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

57(2-1/4)

70
(2-25/32)
270 (10-21/32)

700 (27-9/16)
677 (26-21/32)

25(1)

9
11

1100 1152 1198 1060


PEFY-P24NMSU-E (43-5/16)
(45-3/8) (47-3/16) (41-3/4)

PEFY-P15NMSU-E 900 952 998 860


(35-7/16) (37-1/2) (39-5/16) (33-7/8)
PEFY-P18NMSU-E

B
C
D
Model
A
700 752 798 660
PEFY-P06,08,12NMSU-E (27-9/16)
(29-5/8) (31-7/16) (26)
(26)

1060

860

(39-3/8) (47-1/4) (41-3/4)

1000 1200

1000

H
660

(31-1/2) (39-3/8) (33-7/8)

800

(23-5/8) (31-1/2)

G
800

F
600

23 (29/32)

N
790

(33-1/16) (31-1/8)

M
839

(35-7/16) 24

900

(48-25/32) (46-7/8)

1239 1190

15.88(5/8)

*1 12.7(1/2) *1
*2 15.88(5/8) *2

12.7(1/2)

1 Gas pipe

31

/32

2)

(17 450
-23
/32
)

0
0
45 2)
30 6)
/3
-23 than 13/1
7
1
(
re (11
Mo

)
7
77 9/32
-1 Access
(30

door

Drain hose (I.D.32(1-1/4))


<accessory>

Less than 300


(11-13/16)

Make the access door at the appointed


position properly for service maintenance.

Ceiling surface Access door

Required space for service and maintenance

1/3 50~
2~ 15
5-2 0
9/3
2)

(13

50
(1
G -31/3

1755(6-29/327/32)
(Actual length)

Note2

( 150

Knockout hole 27(1-3/32)


(Transmission wiring)

Air filter

37(1-15/32)
100(3-15/16)
157.5 (6-7/32)
37(1-15/32)

9.52(3/8)

6.35(1/4)
9.52(3/8)

6.35(1/4)

*1:R410A outdoor unit


*2:R22 outdoor unit

Note 1. Use M10 screw for the Suspension bolt (field supply).
2. Keep the service space for the maintenance at the bottom.
3. This chart indicates for PEFY-P1518NMSU-E models,which has
3 fans.
PEFY-P06~12NMSU-E models have 2 fans.
PEFY-P24NMSU-E model have 4 fans.
mm(in.) 4. In case of the inlet duct is used,remove the air filter(supply with
2 Liquid pipe
the unit), then install the filter(field supply) at suction side.

Knockout hole 27(1-3/32)


(Power source wiring)

1039 990
(27-9/16) 20 (40-29/32) (39)
700

(19-11/16) 16

K
500

20 (13/16)
12 (1/2)

L-2.9(1/8)

Terminal bed(Power source)


Terminal bed(Transmission)
Drain pipe(O.D.32(1-1/4))
(Spontaneous draining)

Control box

2x2-2.9(1/8)
2 Refrigerant piping
1 Refrigerant piping
brazing connection (gas) brazing connection (liquid)

116
(4-19/32)

23(29/32)
10(13/32)

Drain pump

10 (13/32)
625 (Suspension bolt pitch)
(24-5/8)

Drain pipe(O.D.32(1-1/4))

49
(1-15/16)

Air
inlet

48(1-29/32)
102 (4-1/32)
90
170 (6-23/32) (3-9/16)
200(7-7/8)

88(3-15/32)
88 (3-15/32)

159(6-9/32)

Air
outlet

A
N
B (Suspension bolt pitch)
C
M

Suspension bolt hole


4-14x30(9/16x1-3/16) Slot

H
20 (13/16)

Drain pipe(O.D.32(1-1/4))
(Emergency draining)

100(3-15/16)xJ=K
100(3-15/16)

2xE-2.9(1/8)

25 (1)

More than 10
(13/32)
More than 20
(13/16)

15 (19/32)

D (Duct)
100(3-15/16)x(E-1)=F
100(3-15/16)

20 (13/16)
30 (1-3/16)

150(Duct)
(5-29/32) 23 (29/32)

345 (13-19/32)

PEFY-P06,08,12,15,18,24NMSU-E

100
(3-15/16)

Less than 550


(21-21/32)

PEFY-8
12 (1/2)

PEFY-P-NMSU-E
PEFY-P-NMHU-E

2. External DImensions
DATA U4

Ref.: PEFY_NMSU_EXD_USDB_ALL
Unit : mm(in)

PEFY-P-NMLU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)
24(31/32)
10(13/32)

50(1-31/32)

70
(2-25/32)

PEFY-P36 4854NMHU-E

383(15-3/32)

Terminal box

Terminal bed
(Power source)

1050
1004
930
850
800
(41-11/32) (39-17/32) (36-5/8) (33-1/2) (31-1/2)
1204
1130
1050
1000
1250
(49-7/32) (47-13/32) (44-1/2) (41-11/32) (39-3/8)

25
(1)
25
(1)

21

17

11

Terminal bed
(Transmission)

Control box

847(33-3/8)

900(35-7/16)

904(35-19/32)

814(32-1/16)(Suspension bolt pitch)

800
754
680
600
550
50
(31-1/2) (29-11/16) (26-25/32) (23-5/8) (21-21/32) (1-31/32)

Keep duct-work length 850mm(33-15/32 in.) or more.

PEFY-P27 30NMHU-E

PEFY-P24NMHU-E

PEFY-P18NMHU-E

Model
PEFY-P15NMHU-E

50(1-31/32)

50(1-31/32)X(G-1)=H
F

41
(1-5/8)

Suspension bolt hole


4-14X30(9/16X1-3/16) Slot

Drain hole

800
(31-1/2)
1000
(39-3/8)

500
(19-11/16)

60
((2-3/8)
)

19

15

10

200(7-7/8)

1030
700
(27-9/16) (40-9/16)
900
1230
(35-7/16) (48-7/16)

450
780
(17-23/32) (30-23/32)

387(15-1/4)

163 (6-13/32)

75
((2-31/32)
)

343(13-17/32)

(3-5/8)
92

Drain hole
(option)

29(1-5/32)
15(19/32)

60(2-3/8)

(3-1/16)
77
(5-1/8)
130

340(13-13/32)

(15/8)

50(1-31/32)X(J-1)=K
50 (1-31/32)

Model:P15~30(Note3)

30(1-3/16)

50 (1-31/32)
15(19/32)

41

10(13/32)

250(9-27/32)

380(14-31/32)

B(Suspension bolt pitch)

(3-5/32)
80 50
(1-31/32)
23(29/32)

(1-31/32X4=7-7/8)
50X4=200
25(1)

340(13-13/32)
17(11/16)

50X5=250
(1-31/32)X5=(9-27/32)
45(1-25/32)

250(9-27/32)
94(3-23/32)

Drain hose
I.D.32mm (1-1/4inch)
<flexible joint>
(accessory)

mm(in.)

(3-1

Access door

(17-2 450
3/32
)

Ceiling surface

(17

)
1/32 L
-3
50(1
50
(1-3
1/3
450-23/32)
2)

When installing the drain pump kit (option).

300(11-13/16) or less

-5/8

(24

Note2

625

Make the access door at the appointed position properly for service maintenance.

Access door

5/16 00~2
~7-7 00
/8)

6)
-9/1
(27
/8)
700 9/32~7-7 ~200
150
(5-2

20(13/16) or more

Required space for service and maintenance.

550(21-21/32) Max

Air outlet

20(13/16) or more

Air inlet

PEFY-P15,18,24,27,30,36,48,54NMHU-E

PEFY-P-NMSU-E
PEFY-P-NMHU-E

E
328(12-15/16)

Note1.Use M10 screw for the Suspension bolt (field supply).


2.Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.
3.This chart indicates for PEFY-P36 4854NMHU-E models, which has 2 fans.
PEFY-P15 18242730NMHU-E models have 1 fan.
4.Make sure to install the air filter(field supply) on the air intake side.
In case field supplied air filter is used, attach it where the filter
service is easily done.
5.On Model :18,36,48,54, you would use flare nut packed with the
Indoor Unit, when connecting the Outdoor Unit for R22.

2. EXTERNAL DIMENSIONS
2. External DImensions
DATA U4

DATA U3

Drw. : IU-W277664
Unit : mm(in)

IU - A - 8
PEFY-9

50X21=1050(1-31/32X21=41-11/32)
24(31/32)
10(13/32)

Suspension bolt hole


4-14X30(9/16X3/16) Slot

1250(49-7/32)

Keep duct-work length 850mm(33-15/32 in.) or more.

420(16-9/16)
20(13/16)

420(16-9/16)

50(1-31/32)
50 (1-31/32)

Terminal bed
(Power source)
Terminal bed
(Transmission)

Control box

Drain hole
(option)

78
((3-3/32)
)
222(8-3/4)
(3-3/4)
95
249(9-13/16)
422(16-5/8)
489(19-9/32)

PEFY-P96NMHU-E

29(1-5/32)
15(19/32)

60(2-3/8)

mm(in.)

Drain hose
I.D.32mm (1-1/4inch)
<flexible joint >
(accessory)

340(13-13/32)

Access door

(17 450
-23
/32
)

(1

Ceiling surface

2)
3-5/3
)
0(5
1/32 135
(1-3

50

(1-3
1/3
450-23/32)
2)
7

50

730

300(11-13/16) or less

When installing the drain pump kit (option).

Note2

-3/4

(28

Make the access door at the appointed position properly for service maintenance.

Access door

/8~1 200~
1-13 300
/16)

(7-7

)
-1/2 )
(31
/8
800 9/32~7-7~200
(5-2 150

Required space for service and maintenance.

Note1.Use M10 screw for the Suspension bolt (field supply).


2.Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned.
3.Make sure to install the air filter(field supply)
on the air intake side.
In case field supplied air filter is used, attach it where
the filter service is easily done.
4.On this model, you would use pipe
packed with the Indoor Unit, when connecting
the Outdoor Unit for R22.

PEFY-P72,96NMHU-E

PEFY-P72NMHU-E

Drain hole

Model

1120(44-1/8)
1067(42-1/32)

1124(44-9/32)

1034(40-23/32)(Suspension bolt pitch)

15(19/32)

327(12-7/8)

10 (13/32)

30
(1-3/16)

50X20=1000(1-31/32X20=39-3/8)
50X6=300
(13/16)
20 (1-31/32X6=11-13/16)

(4-1/32) (1)
102 25
50X7=350
(1-31/32X7=13-25/32)
35(1-13/32)

1372(54-1/32)
340(13-13/32)

Air outlet

41(1-5/8)

1326(52-7/32)(Suspension bolt pitch)


23(29/32)

(3-15/16)
100 50
(1-31/32)

50(1-31/32)
(1-3/4)
44
(6-15/32)
164

PEFY-P-NMLU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E
(Feb. 2009)
(4-5/32)
105

Air inlet

550(21-21/32) Max

PEFY-10
20(13/16) or more

PEFY-P-NMSU-E
PEFY-P-NMHU-E

2.
2. External
EXTERNAL DImensions
DIMENSIONS
DATAU4
U3
DATA

Drw. : IU-W277665
Unit : mm(in)

IU - A - 9

20(13/16) or more

1100(43-5/16)
470(18-17/32)

110(43-5/16)

3. Center of Gravity

DATA U4

PEFY-P06,08,12,15,18,24NMSU-E

Ref.: PEFY_NMSU_COG_USDB_ALL

PEFY-P-NMSU-E
PEFY-P-NMHU-E

A: Center of gravity

(mm)[in]
Model name
PEFY-P06NMSU-E
PEFY-P08NMSU-E
PEFY-P12NMSU-E
PEFY-P15NMSU-E
PEFY-P18NMSU-E
PEFY-P24NMSU-E

W
625 [24-5/8]
625 [24-5/8]
625 [24-5/8]
625 [24-5/8]
625 [24-5/8]
625 [24-5/8]

L
752 [29-5/8]
752 [29-5/8]
752 [29-5/8]
952 [37-1/2]
952 [37-1/2]
1152 [45-3/8]

X
263 [10-3/8]
263 [10-3/8]
275 [10-27/32]
280 [11-1/32]
280 [11-1/32]
285 [11-1/4]

Y
338 [13-5/16]
338 [13-5/16]
340 [13-13/32]
422 [16-5/8]
422 [16-5/8]
511 [20-1/8]

Z
105 [4-5/32]
105 [4-5/32]
104 [4-1/8]
104 [4-1/8]
104 [4-1/8]
104 [4-1/8]

PEFY-P15,18,24,27,30,36,48,54,72,96NMHU-E
L

A: Center of gravity

(mm)[in]
Model name
PEFY-P15NMHU-E
PEFY-P18NMHU-E
PEFY-P24NMHU-E
PEFY-P27NMHU-E
PEFY-P30NMHU-E
PEFY-P36NMHU-E
PEFY-P48NMHU-E
PEFY-P54NMHU-E
PEFY-P72NMHU-E
PEFY-P96NMHU-E

W
814 [32-1/16]
814 [32-1/16]
814 [32-1/16]
814 [32-1/16]
814 [32-1/16]
814 [32-1/16]
814 [32-1/16]
814 [32-1/16]
1034 [40-23/32]
1034 [40-23/32]

L
754 [29-11/16]
754 [29-11/16]
754 [29-11/16]
1004 [39-17/32]
1004 [39-17/32]
1204 [47-13/32]
1204 [47-13/32]
1204 [47-13/32]
1326 [52-7/32]
1326 [52-7/32]

H
210 [8-9/32]
210 [8-9/32]
210 [8-9/32]
210 [8-9/32]
210 [8-9/32]
210 [8-9/32]
210 [8-9/32]
210 [8-9/32]
255 [10-1/16]
255 [10-1/16]

X
374 [14-3/4]
374 [14-3/4]
374 [14-3/4]
394 [15-17/32]
394 [15-17/32]
364 [14-11/32]
364 [14-11/32]
364 [14-11/32]
462 [18-7/32]
462 [18-7/32]

Y
440 [17-11/32]
440 [17-11/32]
440 [17-11/32]
584 [22-32/32]
584 [22-32/32]
649 [25-9/16]
649 [25-9/16]
649 [25-9/16]
660 [25-32/32]
660 [25-32/32]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

Z
190 [7-1/2]
190 [7-1/2]
190 [7-1/2]
190 [7-1/2]
190 [7-1/2]
190 [7-1/2]
190 [7-1/2]
190 [7-1/2]
235 [9-9/32]
235 [9-9/32]

PEFY-11

PEFY-12

6 5 4

9 0 1

2
3

SW1

SW5

8
7

4
3
2
1

6 5 4

9 0 1

2
3

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

SYMBOL
I.B.
A.B.
TB2
TB5
TB15
FUSE
ZNR01,02
DSA
X1
CN24
CN27

NAME
Indoor controller board
Address board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A
Varistor
Arrester
Aux. relay
Connector (Heater)
Connector (Damper)

TB15

CN51

LED2

LEV

CN41

CN42
(Red)

SW4

CN90

SW2

FS

1234

1234

CN4F

CN44

(Yellow) (Red)
CN24
CN27

SWE

OFF ON

TH22 TH23

SW3

TH21

12

LED1
CN20(Red)

DC310~340V
Rectify circuit

CNMF

SYMBOL
CN32
CN41
CN51
CN52
CN90
FS
CN4Y
TH21
TH22
TH23
SW2(I.B.)

NAME
Connector (Remote switch)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote indication)
Connector (Wireless)
Float switch
Connector
Thermistor (inlet air temp.detection)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)
Switch (for capacity code)

SYMBOL
SW3(I.B.)
SW4(I.B.)
SWE(I.B.)
SW1(A.B.)
SW5(A.B.)
SW11(A.B.)
SW12(A.B.)
SW14(A.B.)
SWA(A.B.)
SWB(A.B.)
SWC(A.B.)

NAME
Switch (for mode selection)
Switch (for model selection)
Connector (emergency operation)
Switch (for mode selection)
Switch (for mode selection)
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (connection No.set)
Switch (for static pressure selection)
Switch (for model selection)
Switch (for static pressure selection)

ZNR01

I.B.

M
1~

(Blue)

1 CNP

X1

A.B.

I.B.

POWER SUPPLY
~ 208V/230V 60Hz

BREAKER (16A)

FUSE (16A)

PULL BOX

TO NEXT INDOOR UNIT

TB5 TB15 TB2

TB2
L1
L2

PARTS LOCATION

CONTROL BOX

Drainpump

FUSE

ZNR02

DSA

CND
(Black)

Fan motor

7654

CN2M
(Blue)

21

NOTE: 1.The wirings to TB2,TB5,TB15 shown in dotted line are field work.
2.Mark indicates terminal bed, connector.
3.Use copper supply wire.

TO OUTDOOR UNIT
TO MA REMOTE
BC CONTROLLER
CONTROLLER
REMOTE CONTROLLER

TB5
M1 M2 S(SHIELD) 1

CN52

CN4Y

CN81
(Red)

1234

PEFY-P06,08,12,15,18,24NMSU-E

SYMBOL EXPLANATION

8
7
6
5
4
3
2
1

CN82

SW14
(Connection No.)

SWC

0
EF 1 2
D
3
4
C
B
5
A
9 8 76

SWA SWB CN43

SW12
SW11
(2nd digit) (1st digit)

8
7

A.B.

1
2
3 CN60
4
5
(Green)
6

1 CN3A
(Blue)
3

CN32

12345678

INSIDE SECTION OF CONTROL BOX

PEFY-P-NMSU-E
PEFY-P-NMHU-E

4. Electrical Wiring Diagrams


DATA U4

Ref.: PEFY_NMSU_EWD_USDB_ALL

Fan motor
Capacitor (for MF)
Indoor controller board
Address board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T
Fuse AC250V 5A F
Transformer
Drain pump
Electronic linear expan.valve
Varistor

NAME

SYMBOL EXPLANATION

SYMBOL
MF
C
I.B.
A.B.
TB2
TB5
TB15
F1
<F2>
T
<DP>
LEV
ZNR,ZNR1

90 1
2
3

654

8
7

90 1
2
3

654

SW7

LED2

21

21

*NOTE 1

DS

CN31

21

(White)
CN31
(White)
CN60

LEV

654321

1 1
2 2

1
2

*NOTE 1,2

*A connector is
attached to the
drain pump kit,
which is an
optional part.

*A

(White)
CNT

1 31
T

(Red)
CN3T
3

SYMBOL
<DS>
S.B.
LED1
LED2
CN22
CN23
CN24
CN25
CN27
CN32
CN41
CN51
CN52

NAME
Drain sensor
Surge absorber board
Power supply (I.B.)
Power supply (Remote controller)
Connector
Connector
Connector
Connector
Connector
Connector (Centrally control)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote indication)
SYMBOL
TH21
TH22
TH23
SW11(A.B.)
SW12(A.B.)
SW14(A.B.)
SW1(A.B.)
SW5(A.B.)
SW7(A.B.)
SW2(I.B.)
SW3(I.B.)
SW4(I.B.)
X01,X04~X06

XO1

(Yellow)
FAN2

13

PEFY-P-NMLU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)
Inside < > is the optional parts.

NAME
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (connection No.set)
Switch(for mode selection)
Switch(for voltage selection)
Switch(for model selection)
Switch(for capacity code)
Switch(for mode selection)
Switch(for model selection)
Aux.relay

531

MF

98 6

98

I.B.

4 31

(Blue)

(Red)

31 9 8 5 31

4 31 9 8

*insert

DSA1

ZNR1

2
1

L2
G

TO DUCT

L1 TB2

PARTS LOCATION

S.B.

TB2

A.B.

CONTROL BOX

TB5,TB15

I.B.

POWER SUPPLY
~ 208/230V 60Hz

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

TO OUTDOOR UNIT
BC CONTROLLER
ME REMOTE CONTROLLER

TB5 (TRANSMISSION TERMINAL BED)

TO MA REMOTE CONTROLLER

TB15 (TRANSMISSION TERMINAL BED)

S(SHIELD)
M2
M1

S.B.
(Yellow)
CN1 1

(Blue) 2
CN2M 1

(Blue) 3
CN3A 1

attachment to alter the external static pressure on the fan


Color/External static pressure
Red/High Pressure
Blue/Low Pressure
White/Middle Pressure

98

431
(White) 9 8 65 4 3 1

13 7

(White)
FAN3

XO6 XO5 XO4

(AC250V
5A F )

F2

*NOTE 1

DP

31

(Red) (Blue)
CND CNP

ZNR

NOTE;1.The part of the broken line indicates the circuit for optional parts.
2.*A in the chart is the connector for a drain pump test run operation.
(The Drain Pump operates continuously if the connector is inserted
and the power is supplied.)
After the test run, make sure to remove the *A connector.
3.The wirings to TB2,TB5,TB15 shown in chained line are field work.
4.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.

TH21 TH22 TH23

21

AC250V
6.3A T

( )F1

(White)(Green) (White) (White) (Green)(Yellow) (White) (Red) (Green)

CN32 CN52 CN51 CN41 CN23 CN24 CN25 CN27 CN22

(Red) (White) (Black)


CN20 CN21 CN29

LED1

SW4 SW3 SW2

SW14
SW12
SW11
(Connection No.) (2nd digit) (1st digit)

8
7

SW5

CN62
(White)

12 3 4 5 6

8 CN82
7 (White)
6
SW1
5
4
EF012
3
D
3
C
4
2
BA
5
1
9876

A.B.

(Red)
CN81

(Red)
CN42

INSIDE SECTION OF CONTROL BOX

PEFY-P15,18,24,27,30,36,48,54NMHU-E

PEFY-P-NMSU-E
PEFY-P-NMHU-E

1
2
3
4
1
2
3
4
5
6
7
8

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA U4
U3
DATA

Drw. : IU-W660134

IUPEFY-13
- A - 11

PEFY-14
CN62
(White)

90 1
2
8
3
7
654

SW5

SW14
SW12
(Connection No.) (2nd digit)

EF012
D
3
C
4
BA
5
9876

SW1

CN82
(White)

123456

(Red)
CN81

(Red)
CN42

SW11
(1st digit)

90 1
2
8
3
7
654

SW7

SW4 SW3 SW2


CN52

CN51

CN41

CN23

CN24

CN25

CN27

CN22

TH22

21

21

TH21

(White)
CN21

(Red)
CN20

LED1

TH23

21

21

*NOTE 1

DS

CN31

(White)
CN31

(Black)
CN29

LED2

*A

1
2

31

PEFY-P-NMSU-E/PEFY-P-NMHU-E
(Feb. 2009)
PEFY-P-NMLU-E/PEFY-P-NMHU-E

SYMBOL
MF
I.B.
A.B.
TB2
TB5
TB15
F1
<F2>
T
<DP>
LEV1,LEV2
<DS>
S.B.
ZNR,ZNR1

Fan motor
Indoor controller board
Address board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T
Fuse AC250V 5A F
Transformer
Drain pump
Electronic linear expan.valve
Drain sensor
Surge absorber board
Varistor

NAME
SYMBOL
52F
51F
LED1
LED2
CN22
CN23
CN24
CN25
CN27
CN32
CN41
CN51
CN52

SYMBOL
NAME
TH21
Contactor (fan motor)
TH22
Over current relay (fan motor)
Power supply (I.B.)
TH23
Power supply (Remote controller) SW11(A.B.)
SW12(A.B.)
Connector
SW14(A.B.)
Connector
Connector
SW1(A.B.)
Connector
SW5(A.B.)
Connector
SW7(A.B.)
Connector (Centrally control) SW2(I.B.)
Connector (HA terminal-A)
SW3(I.B.)
Connector (Centrally control) SW4(I.B.)
Connector (Remote indication) X01,X04~X06
49F

(White)
CNT

( )
AC250V
6.3A T F1

13

F2

(Red)
CND

ZNR

654321
654321

LEV2

654321

LEV1

LEV adapter board

NAME
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (connection No.set)
Switch(for mode selection)
Switch(for voltage selection)
Switch(for model selection)
Switch(for capacity code)
Switch(for mode selection)
Switch(for model selection)
Aux.relay
Inner thermostat
Inside < > is the optional parts.

*NOTE 1

DP

CR
51F

89
89

( 9A )

6 54

52F

DSA1

51F

2
1

89

L1
L2
L3

TB2

TB5,TB15

TB2

S.B.

52F

51F

CONTROL BOX

A.B.

I.B.

TO DUCT

BREAKER
POWER SUPPLY
3~ 208V/230V 60Hz

TB5 (TRANSMISSION TERMINAL BED)


TO OUTDOOR UNIT
BC CONTROLLER
ME REMOTE CONTROLLER

S(SHIELD)

TO MA REMOTE CONTROLLER

TB15 (TRANSMISSION TERMINAL BED)

2
1

M2
M1

(Blue)

S.B.
(Yellow)
CN1 1

ZNR1

(Blue)
CN2M

3
1

PARTS LOCATION

MF
49F

321654

I.B.
(Blue)
CN3A

Color/External static pressure


White/High Pressure
Blue/Low Pressure

(White)
FAN3

XO5 XO4

1 35 7
52F

XO6

(White) 3 2 1

31

(Blue)
CNP

XO1

(Yellow) 5 3 1
FAN2

INSIDE SECTION OF CONTROL BOX

*A connector is attached AC250V


to the drain pump kit,
5A F
which is an optional part.
*NOTE 1,2

(Red)
CN3T

654321

654321

6 5 4 3 21

(White)
CN60

(White) (Green) (White) (White) (Green) (Yellow) (White) (Red) (Green)

CN32

CAUTION;1.To protect Fan motor from abnormal current, Over current relays<51F>
is installed. Therefore, do not change factory set value of Over
current relays.
NOTE;1.The part of the broken line indicates the circuit for optional parts.
2.*A in the chart is the connector for a drain pump test run operation.
(The Drain Pump operates continuously if the connector is inserted
and the power is supplied.)
After the test run, make sure to remove the *A connector.
3.The wirings to TB2,TB5,TB15 shown in chained line are field work.
4.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.
SYMBOL EXPLANATION

8
7
6
5
4
3
2
1

A.B.

1
2
3
4
5
6
7
8

1
2
3
4

PEFY-P-NMSU-E
PEFY-P-NMHU-E

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATAU4
U3

PEFY-P72,96NMHU-E
Drw. : IU-W660130

IU - A - 12

5. Sound Pressure Levels

DATA U4

5-1. Sound Pressure Levels


3-1/4ft.
(1m)

6-1/2ft.
(2.0m)

PEFY-P-NMSU-E
PEFY-P-NMHU-E

4-7/8ft.
(1.5m)

aux.duct

Measurement location

Measured in an anechoic room.

5-2. NC Curves

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P06-1

Octave band pressure level (dB) 0dB=20Pa

PEFY-P06NMSU-E
External Static Pressure: 35Pa
Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P06NMSU-E
External Static Pressure: 15Pa
Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P06NMSU-E
External Static Pressure: 5Pa
Power Source: 208/230V(60Hz)

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

2k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P06-2

External Static Pressure: 15Pa


Power Source: 208/230V(60Hz)

60Hz
High
Middle 60Hz
60Hz
Low

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:PEFY_NMSU_NCC_USDB_P06-4

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Octave band pressure level (dB) 0dB=20Pa

PEFY-P08NMSU-E

External Static Pressure: 5Pa


Power Source: 208/230V(60Hz)
Octave band pressure level (dB) 0dB=20Pa

PEFY-P08NMSU-E

Octave band pressure level (dB) 0dB=20Pa

PEFY-P06NMSU-E

65.0

8k

Ref.:PEFY_NMSU_NCC_USDB_P06-3

External Static Pressure: 50Pa


Power Source: 208/230V(60Hz)
70.0

4k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P08-1

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

8k

Ref.:PEFY_NMSU_NCC_USDB_P08-2

PEFY-15

DATA U4

DATA U4

External Static Pressure: 5Pa


Power Source: 208/230V(60Hz)

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

NC-20

250

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P08-3

Octave band pressure level (dB) 0dB=20Pa

PEFY-P12NMSU-E

External Static Pressure: 50Pa


Power Source: 208/230V(60Hz)
Octave band pressure level (dB) 0dB=20Pa

PEFY-P08NMSU-E

External Static Pressure: 35Pa


Power Source: 208/230V(60Hz)
Octave band pressure level (dB) 0dB=20Pa

PEFY-P08NMSU-E

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

NC-20

250

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P12-2

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 50Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P12NMSU-E

External Static Pressure: 35Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P12NMSU-E

60Hz
High
Middle 60Hz
60Hz
Low

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

NC-20

250

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P15-1

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 35Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P15NMSU-E

External Static Pressure: 15Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P15NMSU-E

60Hz
High
Middle 60Hz
60Hz
Low

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:PEFY_NMSU_NCC_USDB_P15-4

PEFY-16

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:PEFY_NMSU_NCC_USDB_P18-1

PEFY-P-NMSU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 15Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMSU-E

External Static Pressure: 5Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMSU-E

60Hz
High
Middle 60Hz
60Hz
Low

8k

Ref.:PEFY_NMSU_NCC_USDB_P15-3

External Static Pressure: 50Pa


Power Source: 208/230V(60Hz)
65.0

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P15-2

PEFY-P15NMSU-E

70.0

8k

Ref.:PEFY_NMSU_NCC_USDB_P12-4

External Static Pressure: 5Pa


Power Source: 208/230V(60Hz)
65.0

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P12-3

PEFY-P15NMSU-E

70.0

8k

Ref.:PEFY_NMSU_NCC_USDB_P12-1

External Static Pressure: 15Pa


Power Source: 208/230V(60Hz)
65.0

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P08-4

PEFY-P12NMSU-E

70.0

PEFY

PEFY-P-NMSU-E
PEFY-P-NMHU-E

5. Sound
SOUND Pressure
LEVELS
5.
Levels

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:PEFY_NMSU_NCC_USDB_P18-2

PEFY - 15

DATA U4

DATA U4

External Static Pressure: 5Pa


Power Source: 208/230V(60Hz)

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P18-3

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P18-4

External Static Pressure: 35Pa


Power Source: 208/230V(60Hz)

External Static Pressure: 50Pa


Power Source: 208/230V(60Hz)

60Hz
High
Middle 60Hz
60Hz
Low

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P24-2

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 15Pa


Power Source: 208/230V(60Hz)

Octave band pressure level (dB) 0dB=20Pa

PEFY-P24NMSU-E

Octave band pressure level (dB) 0dB=20Pa

PEFY-P24NMSU-E

65.0

8k

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

External Static Pressure: 100Pa


Power Source: 230V 60Hz

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P15NMHU-E_WYN B0-4423-2

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 160Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 50Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P15NMHU-E

High
Low

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P15NMHU-E_WYN B0-4423-4

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 50Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMHU-E

External Static Pressure: 200Pa


Power Source: 230V 60Hz
60Hz
60Hz

4k

8k

Ref.:NC_PEFY-P15NMHU-E_WYN B0-4423-5

PEFY-P15NMHU-E

High
Low

2k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P15NMHU-E_WYN B0-4423-1

External Static Pressure: 150Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PEFY-P15NMHU-E

70.0

8k

Ref.:PEFY_NMSU_NCC_USDB_P24-4

PEFY-P15NMHU-E

65.0

4k

Octave band center frequencies (Hz)

Ref.:PEFY_NMSU_NCC_USDB_P24-3

PEFY-P15NMHU-E

70.0

8k

Ref.:PEFY_NMSU_NCC_USDB_P24-1

PEFY-P24NMSU-E

70.0

4k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P15NMHU-E_WYN B0-4423-3

PEFY-P-NMSU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

8k

Ref.:NC_PEFY-P18NMHU-E_WYN B0-4424-2

PEFY - 16
PEFY-17

PEFY-P-NMSU-E
PEFY-P-NMHU-E

35.0

70.0

Octave band pressure level (dB) 0dB=20Pa

PEFY-P24NMSU-E

External Static Pressure: 50Pa


Power Source: 208/230V(60Hz)
Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMSU-E

External Static Pressure: 35Pa


Power Source: 208/230V(60Hz)
Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMSU-E

Octave band pressure level (dB) 0dB=20Pa

PEFY

5.
5. SOUND
Sound LEVELS
Pressure Levels

DATA U4

DATA U4

External Static Pressure: 150Pa


Power Source: 230V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P18NMHU-E_WYN B0-4424-1

Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMHU-E

External Static Pressure: 100Pa


Power Source: 230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMHU-E

External Static Pressure: 160Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P18NMHU-E

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P18NMHU-E_WYN B0-4424-3

Octave band pressure level (dB) 0dB=20Pa

60Hz
60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 160Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P24NMHU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz

High
Low

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P24NMHU-E_WYN B0-4425-5

Octave band pressure level (dB) 0dB=20Pa

60.0

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 200Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P24NMHU-E

External Static Pressure: 150Pa


Power Source: 230V 60Hz
60Hz
60Hz

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P27NMHU-E_WYN B0-4426-2

PEFY-18

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P27NMHU-E_WYN B0-4426-1

PEFY-P-NMSU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 100Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 160Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 50Pa


Power Source: 208V 60Hz
60Hz
60Hz

8k

Ref.:NC_PEFY-P24NMHU-E_WYN B0-4425-3

PEFY-P27NMHU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P24NMHU-E_WYN B0-4425-4

PEFY-P27NMHU-E

65.0

60Hz
60Hz

60.0

PEFY-P27NMHU-E

70.0

8k

Ref.:NC_PEFY-P24NMHU-E_WYN B0-4425-1

PEFY-P24NMHU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P24NMHU-E_WYN B0-4425-2

External Static Pressure: 100Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PEFY-P24NMHU-E

70.0

8k

Ref.:NC_PEFY-P18NMHU-E_WYN B0-4424-4

PEFY-P24NMHU-E

60.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P18NMHU-E_WYN B0-4424-5

External Static Pressure: 200Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PEFY-P18NMHU-E

70.0

PEFY

PEFY-P-NMSU-E
PEFY-P-NMHU-E

5. Sound
SOUND Pressure
LEVELS
5.
Levels

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P27NMHU-E_WYN B0-4426-5

PEFY - 17

DATA U4

DATA U4

External Static Pressure: 50Pa


Power Source: 208V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P27NMHU-E_WYN B0-4426-4

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P30NMHU-E_WYN B0-4427-1

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 150Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P30NMHU-E

External Static Pressure: 100Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P30NMHU-E

High
Low

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P30NMHU-E_WYN B0-4427-3

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 160Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 50Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 200Pa


Power Source: 230V 60Hz
60Hz
60Hz

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

500

NC-20
1k

2k

60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P36,48,54NMHU-E_WYN B0-4428-5

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P36,48,54NMHU-E_WYN B0-4428-4

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 200Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P36,48,54NMHU-E

External Static Pressure: 150Pa


Power Source: 230V 60Hz

High
Low

8k

Ref.:NC_PEFY-P36,48,54NMHU-E_WYN B0-4428-1

PEFY-P36,48,54NMHU-E

60.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P36,48,54NMHU-E_WYN B0-4428-2

External Static Pressure: 100Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PEFY-P36,48,54NMHU-E

70.0

8k

Ref.:NC_PEFY-P30NMHU-E_WYN B0-4427-4

PEFY-P36,48,54NMHU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P30NMHU-E_WYN B0-4427-5

PEFY-P36,48,54NMHU-E

65.0

60Hz
60Hz

60.0

PEFY-P30NMHU-E

70.0

8k

Ref.:NC_PEFY-P30NMHU-E_WYN B0-4427-2

External Static Pressure: 160Pa


Power Source: 208V 60Hz
65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P27NMHU-E_WYN B0-4426-3

PEFY-P30NMHU-E

70.0

60Hz
60Hz

60.0

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P36,48,54NMHU-E_WYN B0-4428-3

PEFY-P-NMSU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

PEFY - 18
PEFY-19

PEFY-P-NMSU-E
PEFY-P-NMHU-E

30.0

70.0

Octave band pressure level (dB) 0dB=20Pa

PEFY-P30NMHU-E

External Static Pressure: 200Pa


Power Source: 230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P27NMHU-E

External Static Pressure: 150Pa


Power Source: 230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P27NMHU-E

Octave band pressure level (dB) 0dB=20Pa

PEFY

5. SOUND LEVELS
5. Sound Pressure Levels

DATA U4

DATA U4

External Static Pressure: 100Pa


Power Source: 230V 60Hz

70.0

High

65.0

60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High

65.0

60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P72NMHU-E_WYN B0-4441-2

Octave band pressure level (dB) 0dB=20Pa

PEFY-P72NMHU-E

External Static Pressure: 160Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P72NMHU-E

External Static Pressure: 70Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PEFY-P72NMHU-E

8k

70.0

High

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P96NMHU-E_WYN B0-4442-4

PEFY-20

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 200Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P96NMHU-E

External Static Pressure: 100Pa


Power Source: 230V 60Hz
High

8k

Ref.:NC_PEFY-P96NMHU-E_WYN B0-4442-2

PEFY-P96NMHU-E

65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P72NMHU-E_WYN B0-4441-3

70.0

60Hz

70.0

High

65.0

50.0

60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P96NMHU-E_WYN B0-4442-1

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0

10.0

High

65.0

NC-60

55.0

15.0

70.0

60Hz

60.0

20.0

Octave band pressure level (dB) 0dB=20Pa

60.0

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 160Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PEFY-P96NMHU-E

External Static Pressure: 70Pa


Power Source: 208V 60Hz
60Hz

8k

Ref.:NC_PEFY-P72NMHU-E_WYN B0-4441-4

PEFY-P96NMHU-E

High

4k

Octave band center frequencies (Hz)

Ref.:NC_PEFY-P72NMHU-E_WYN B0-4441-1

External Static Pressure: 200Pa


Power Source: 230V 60Hz
65.0

60Hz

60.0

PEFY-P72NMHU-E

70.0

PEFY

PEFY-P-NMSU-E
PEFY-P-NMHU-E

SOUND Pressure
LEVELS
5. Sound
Levels

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PEFY-P96NMHU-E_WYN B0-4442-3

PEFY-P-NMSU-E/PEFY-P-NMHU-E
PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

PEFY - 19

6. Fan Characteristics Curves


PEFY-P06NMSU-E
External static pressure : 5Pa,0.020[in.WG]
Power source : 208,230v / 60Hz

Suction : Back inlet


60Hz

40
[0.161]
35
[0.141]

30
[0.121]

30
[0.121]
Static pressure (Pa)[in.WG]

35
[0.141]

25
[0.100]
20
[0.080]
15
[0.060]
10
[0.040]
Middle

0
[0] 4
[141]

6
7
[212]
[247]
airflow rate (m3/min)[cfm]

8
[282]

PEFY-P06NMSU-E
External static pressure : 35Pa,0.141[in.WG]
Power source : 208,230v / 60Hz

60
[0.241]
Static pressure (Pa)[in.WG]

60
[0.241]
50
[0.201]
High

30
[0.121]
Middle

5
[177]

6
7
[212]
[247]
airflow rate (m3/min)[cfm]

8
[282]

9
[318]

Suction : Back inlet


60Hz

High

50
[0.201]
40
[0.161]
Middle
30
[0.121]
Low

20
[0.080]

Low

10
[0.040]

10
[0.040]

5
[177]

6
7
[212]
[247]
airflow rate (m3/min)[cfm]

8
[282]

PEFY-P08NMSU-E
External static pressure : 5Pa,0.020[in.WG]
Power source : 208,230v / 60Hz

0
[0] 4
[141]

9
[318]

Suction : Back inlet


60Hz

40
[0.161]

30
[0.121]
Static pressure (Pa)[in.WG]

30
[0.121]

20
[0.080]
15
[0.060]

High

10
[0.040]

Middle

5
[177]

25
[0.100]

8
[282]

9
[318]

Suction : Back inlet


60Hz

High

20
[0.080]
15
[0.060]

Middle

10
[0.040]

Low

5
[0.020]

6
7
[212]
[247]
airflow rate (m3/min)[cfm]

40
[0.161]
35
[0.141]

25
[0.100]

5
[177]

PEFY-P08NMSU-E
External static pressure : 15Pa,0.060[in.WG]
Power source : 208,230v / 60Hz

35
[0.141]

0
[0] 4
[141]

Low

80
[0.321]
70
[0.281]

0
[0] 4
[141]

Middle

PEFY-P06NMSU-E
External static pressure : 50Pa,0.201[in.WG]
Power source : 208,230v / 60Hz

70
[0.281]

20
[0.080]

Static pressure (Pa)[in.WG]

15
[0.060]

0
[0] 4
[141]

9
[318]

Suction : Back inlet


60Hz

80
[0.321]

40
[0.161]

High

20
[0.080]

5
[0.020]

Low
5
[177]

Suction : Back inlet


60Hz

25
[0.100]

10
[0.040]

High

5
[0.020]

Static pressure (Pa)[in.WG]

PEFY-P06NMSU-E
External static pressure : 15Pa,0.060[in.WG]
Power source : 208,230v / 60Hz

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Static pressure (Pa)[in.WG]

40
[0.161]

DATA U4

Low

5
[0.020]

6
7
8
[212]
[247]
[282]
airflow rate (m3/min)[cfm]

9
[318]

10
[353]

0
[0] 4
[141]

5
[177]

6
7
8
[212]
[247]
[282]
airflow rate (m3/min)[cfm]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

9
[318]

10
[353]

PEFY-21

6. Fan Characteristics Curves


PEFY-P08NMSU-E
External static pressure : 35Pa,0.141[in.WG]
Power source : 208,230v / 60Hz

Suction : Back inlet


60Hz

80
[0.321]

DATA U4
PEFY-P08NMSU-E
External static pressure : 50Pa,0.201[in.WG]
Power source : 208,230v / 60Hz

Suction : Back inlet


60Hz

80
[0.321]

70
[0.281]

70
[0.281]

60
[0.241]

60
[0.241]
Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

50
[0.201]

High

40
[0.161]
30
[0.121]

Middle

20
[0.080]

0
[0] 4
[141]

5
[177]

6
7
8
[212]
[247]
[282]
airflow rate (m3/min)[cfm]

40
[0.161]

9
[318]

Suction : Back inlet


60Hz

Low

5
[177]

6
7
8
[212]
[247]
[282]
airflow rate (m3/min)[cfm]

PEFY-P12NMSU-E
External static pressure : 15Pa,0.060[in.WG]
Power source : 208,230v / 60Hz
50
[0.201]

40
[0.161]
High

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

Middle

9
[318]

10
[353]

Suction : Back inlet


60Hz

45
[0.181]

30
[0.121]
25
[0.100]
20
[0.080]
15
[0.060]

Middle

10
[0.040]

High

35
[0.141]
30
[0.121]
25
[0.100]
Middle

20
[0.080]
15
[0.060]

Low

10
[0.040]

Low
5
[0.020]

5
[0.020]
5
[177]

6
7
8
9
[212]
[247]
[282]
[318]
airflow rate (m3/min)[cfm]

PEFY-P12NMSU-E
External static pressure : 35Pa,0.141[in.WG]
Power source : 208,230v / 60Hz
80
[0.321]

10
[353]

0
[0] 4
[141]

11
[388]

Suction : Back inlet


60Hz

5
[177]

6
7
8
9
[212]
[247]
[282]
[318]
airflow rate (m3/min)[cfm]

PEFY-P12NMSU-E
External static pressure : 50Pa,0.201[in.WG]
Power source : 208,230v / 60Hz
80
[0.321]

70
[0.281]

70
[0.281]

60
[0.241]

Static pressure (Pa)[in.WG]

40
[0.161]
Middle

30
[0.121]
20
[0.080]

10
[353]

11
[388]

Suction : Back inlet


60Hz

High

60
[0.241]

High

50
[0.201]

50
[0.201]
40
[0.161]

Middle

30
[0.121]

Low

20
[0.080]

Low

10
[0.040]

PEFY-22

30
[0.121]

0
[0] 4
[141]

10
[353]

35
[0.141]

0
[0] 4
[141]

40
[0.161]

10
[0.040]

PEFY-P12NMSU-E
External static pressure : 5Pa,0.020[in.WG]
Power source : 208,230v / 60Hz

0
[0] 4
[141]

50
[0.201]

20
[0.080]

Low

10
[0.040]

Static pressure (Pa)[in.WG]

PEFY-P-NMSU-E
PEFY-P-NMHU-E

High

10
[0.040]

5
[177]

6
7
8
9
[212]
[247]
[282]
[318]
airflow rate (m3/min)[cfm]

10
[353]

11
[388]

0
[0] 4
[141]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

5
[177]

6
7
8
9
[212]
[247]
[282]
[318]
airflow rate (m3/min)[cfm]

10
[353]

11
[388]

6. Fan Characteristics Curves


PEFY-P15NMSU-E
External static pressure : 5Pa,0.020[in.WG]
Power source : 208,230v / 60Hz

Suction : Back inlet


60Hz

PEFY-P15NMSU-E
External static pressure : 15Pa,0.060[in.WG]
Power source : 208,230v / 60Hz
40
[0.161]
35
[0.141]

30
[0.121]

30
[0.121]
Static pressure (Pa)[in.WG]

35
[0.141]

25
[0.100]
20
[0.080]

High

15
[0.060]

Middle
Low

10
[0.040]

High

25
[0.100]
Middle
20
[0.080]
Low

15
[0.060]
10
[0.040]
5
[0.020]

5
[0.020]
0
[0] 6
[212]

Suction : Back inlet


60Hz

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Static pressure (Pa)[in.WG]

40
[0.161]

DATA U4

7
[247]

8
9
10
11
[282]
[318]
[353]
[388]
airflow rate (m3/min)[cfm]

PEFY-P15NMSU-E
External static pressure : 35Pa,0.141[in.WG]
Power source : 208,230v / 60Hz
80
[0.321]

12
[424]

0
[0] 6
[212]

13
[459]

Suction : Back inlet


60Hz

7
[247]

8
9
10
11
[282]
[318]
[353]
[388]
airflow rate (m3/min)[cfm]

PEFY-P15NMSU-E
External static pressure : 50Pa,0.201[in.WG]
Power source : 208,230v / 60Hz
80
[0.321]

70
[0.281]

70
[0.281]

60
[0.241]

60
[0.241]

12
[424]

13
[459]

Suction : Back inlet


60Hz

50
[0.201]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

High

High

40
[0.161]

Middle

30
[0.121]

Low

50
[0.201]

Low
30
[0.121]

20
[0.080]

20
[0.080]

10
[0.040]

10
[0.040]

0
[0] 6
[212]

7
[247]

8
9
10
11
[282]
[318]
[353]
[388]
airflow rate (m3/min)[cfm]

PEFY-P18NMSU-E
External static pressure : 5Pa,0.020[in.WG]
Power source : 208,230v / 60Hz
40
[0.161]

12
[424]

0
[0] 6
[212]

13
[459]

Suction : Back inlet


60Hz

Middle

40
[0.161]

7
[247]

8
9
10
11
[282]
[318]
[353]
[388]
airflow rate (m3/min)[cfm]

PEFY-P18NMSU-E
External static pressure : 15Pa,0.060[in.WG]
Power source : 208,230v / 60Hz
50
[0.201]

12
[424]

13
[459]

Suction : Back inlet


60Hz

35
[0.141]
40
[0.161]
Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

30
[0.121]
25
[0.100]
High

20
[0.080]
15
[0.060]
Middle
10
[0.040]

High

30
[0.121]

20
[0.080]

Middle

Low

Low

10
[0.040]

5
[0.020]
0
[0] 8
[282]

9
[318]

10
[353]

11
12
13
14
[388] [424] [459] [494]
airflow rate (m3/min)[cfm]

15
[530]

16
[565]

0
[0] 8
[282]

9
[318]

10
[353]

11
12
13
14
[388] [424] [459] [494]
airflow rate (m3/min)[cfm]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

15
[530]

16
[565]

PEFY-23

6. FAN CHARACTERISTIC CURVES


PEFY-P15,18NMHU-E
External static pressure : 50,160Pa,0.201,0.642[in.WG]
Suction : Back inlet
Power source : 208V / 60Hz
60Hz

250
[1.004]

DATA U4
PEFY-P15,18NMHU-E
External static pressure : 100,150,200Pa,0.401,0.602,0.803[in.WG]
Suction : Back inlet
Power source : 230V / 60Hz
60Hz

250
[1.004]
High(200)

High(160)

150
[0.602]

100
[0.401]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

200
[0.803]

Low

High(150)

150
[0.602]

High(100)
Low

100
[0.401]

High(50)
50
[0.201]

50
[0.201]
Long-life
filter

0
[0]

10
[353]

Long-life
filter
0
[0]

15
[530]
Airflow rate (m3/min)[cfm]

PEFY-P24NMHU-E
External static pressure : 50,160Pa,0.201,0.642[in.WG]
Suction : Back inlet
Power source : 208V / 60Hz
60Hz

250
[1.004]

250
[1.004]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

15
[530]
Airflow rate (m3/min)[cfm]

60Hz

High(150)

High(200)

200
[0.803]

150
[0.602]
High(160)

100
[0.401]

10
[353]

PEFY-P24NMHU-E
External static pressure : 100,150,200Pa,0.401,0.602,0.803[in.WG]
Suction : Back inlet
Power source : 230V / 60Hz

200
[0.803]

High(50)

Low

50
[0.201]

High(100)
150
[0.602]
Low
100
[0.401]

50
[0.201]
Long-life
filter

0
[0]

15
[530]

60Hz

250
[1.004]

200
[0.803]

Long-life
filter

0
[0]

20
[706]
Airflow rate (m3/min)[cfm]

PEFY-P27NMHU-E
External static pressure : 50,160Pa,0.201,0.642[in.WG]
Suction : Back inlet
Power source : 208V / 60Hz

15
[530]

20
[706]
Airflow rate (m3/min)[cfm]

PEFY-P27NMHU-E
External static pressure : 100,150,200Pa,0.401,0.602,0.803[in.WG]
Suction : Back inlet
Power source : 230V / 60Hz
250
[1.004]

60Hz

High(150)

High(200)

200
[0.803]

High(160)

Static pressure (Pa)[in.WG]

High(100)

Static pressure (Pa)[in.WG]

PEFY-P-NMSU-E
PEFY-P-NMHU-E

200
[0.803]

150
[0.602]
High(50)
100
[0.401]

Low

50
[0.201]

0
[0]

PEFY-24

150
[0.602]

Low
100
[0.401]

50
[0.201]

Long-life
filter
15
[530]

20
[706]
Airflow rate (m3/min)[cfm]

25
[883]

0
[0]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

Long-life
filter
15
[530]

20
[706]
Airflow rate (m3/min)[cfm]

25
[883]

6. FAN CHARACTERISTIC CURVES


PEFY-P30NMHU-E
External static pressure : 50,160Pa,0.201,0.642[in.WG]
Suction : Back inlet
Power source : 208V / 60Hz
60Hz

250
[1.004]

DATA U4
PEFY-P30NMHU-E
External static pressure : 100,150,200Pa,0.401,0.602,0.803[in.WG]
Suction : Back inlet
Power source : 230V / 60Hz
60Hz

250
[1.004]
High(200)
200
[0.803]

High(160)

High(100)

Static pressure (Pa)[in.WG]

High(50)
150
[0.602]

Low
100
[0.401]

50
[0.201]

High
(150)

150
[0.602]

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Static pressure (Pa)[in.WG]

200
[0.803]

Low

100
[0.401]

50
[0.201]

Long-life
filter

0
[0]15
[530]

20
25
[706]
[883]
Airflow rate (m3/min)[cfm]

PEFY-P36,48NMHU-E
External static pressure : 50,160Pa,0.201,0.642[in.WG]
Suction : Back inlet
Power source : 208V / 60Hz
60Hz

250
[1.004]

Long-life
filter

0
[0] 15
[530]

20
25
[706]
[883]
Airflow rate (m3/min)[cfm]

PEFY-P36,48NMHU-E
External static pressure : 100,150,200Pa,0.401,0.602,0.803[in.WG]
Suction : Back inlet
Power source : 230V / 60Hz
60Hz

250
[1.004]

High(200)
High(150)

200
[0.803]

200
[0.803]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

High(160)

150
[0.602]
High(50)

100
[0.401]

Low

50
[0.201]

0
[0]

High(100)

150
[0.602]
Low
100
[0.401]

50
[0.201]
Long-life
filter
25
[883]

30
35
40
[1059]
[1236]
[1412]
Airflow rate (m3/min)[cfm]

45
[1589]

PEFY-P54NMHU-E
External static pressure : 50,160Pa,0.201,0.642[in.WG]
Suction : Back inlet
Power source : 208V / 60Hz
60Hz

250
[1.004]

0
[0]

Long-life
filter
25
[883]

30
35
40
[1059]
[1236]
[1412]
Airflow rate (m3/min)[cfm]

45
[1589]

PEFY-P54NMHU-E
External static pressure : 100,150,200Pa,0.401,0.602,0.803[in.WG]
Suction : Back inlet
Power source : 230V / 60Hz
60Hz

250
[1.004]
High(200)

High(160)
150
[0.602]

High(50)
100
[0.401]
Low
50
[0.201]

0
[0]

High(150)

200
[0.803]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

200
[0.803]

150
[0.602]

High(100)

100
[0.401]
Low
50
[0.201]

Long-life
filter
25
[883]

30
[1059]

35
40
[1236]
[1412]
Airflow rate (m3/min)[cfm]

45
[1589]

50
[1766]

0
[0]

Long-life
filter

25
[883]

30
[1059]

35
40
[1236]
[1412]
Airflow rate (m3/min)[cfm]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

45
[1589]

50
[1766]

PEFY-25

6. FAN CHARACTERISTIC CURVES


PEFY-P72NMHU-E
External static pressure : 70,160Pa,0.281,0.642[in.WG]
Suction : Back inlet
Power source : 208v / 60Hz
60Hz

300
[1.204]

300
[1.204]

250
[1.004]

250
[1.004]

200
[0.803]
(160)
150
[0.602]
(70)
100
[0.401]

0
[0] 40
[1412]

60Hz

350
[1.405]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

PEFY-P72NMHU-E
External static pressure : 100,200Pa,0.401,0.803[in.WG]
Suction : Back inlet
Power source : 230v / 60Hz

50
[0.201]

(200)
200
[0.803]
150
[0.602]

(100)

100
[0.401]
50
[0.201]

Long-life
filter
45
[1589]

50
[1766]

55
60
65
[1942]
[2119]
[2295]
airflow rate (m3/min)[cfm]

70
[2472]

60Hz

350
[1.405]

0
[0]40
[1412]

75
[2648]

PEFY-P96NMHU-E
External static pressure : 70,160Pa,0.281,0.642[in.WG]
Suction : Back inlet
Power source : 208v / 60Hz

45
[1589]

50
55
60
65
[1766]
[1942]
[2119]
[2295]
airflow rate (m3/min)[cfm]

300
[1.204]

250
[1.004]

250
[1.004]

200
[0.803]
(160)

100
[0.401]

70
[2472]

75
[2648]

60Hz

350
[1.405]

300
[1.204]

150
[0.602]

Long-life
filter

PEFY-P96NMHU-E
External static pressure : 100,200Pa,0.401,0.803[in.WG]
Suction : Back inlet
Power source : 230v / 60Hz

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

PEFY-P-NMSU-E
PEFY-P-NMHU-E

350
[1.405]

DATA U4

200
[0.803]
(200)

150
[0.602]
(100)

100
[0.401]

(70)
50
[0.201]
0
[0]

55
[1942]

PEFY-26

50
[0.201]
Long-life
filter
60
[2119]

65
[2295]

70
75
80
[2472]
[2648]
[2825]
airflow rate (m3/min)[cfm]

85
[3001]

90
[3178]

0
[0]

55
[1942]

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

Long-life
filter

60
[2119]

65
70
75
80
[2295]
[2472]
[2648]
[2825]
airflow rate (m3/min)[cfm]

85
[3001]

90
[3178]

7. OPTIONAL PARTS

DATA U4

PEFY-P-NMSU-E
PEFY-P-NMHU-E

PEFY-P-NMHU-E

Drain pump
PaC-kE04DM-F
PEFY-P-NMHU-E

Long-life filter
PaC-kE-LaF

Long-life filter
PaC-kE-LaF
Filter box
PaC-kE-TB-F

7-2. Long-life Filter PAC-KE-LAF; Filter Box PAC-KE-TB-F for PEFY-P-NMHU-E


Life span: 2,500 hr
*. The actual dust situation affects the filter life span, which should be considered at the applying site.

Material: Synthetic fiber unwoven cloth filter


For information regarding static pressure loss, see subsection 6. Fan Characteristic Curves.
Long-life filter should be used together with filter box PaC-kE-TB-F.

PaC-kE-LaF
item

PaC-kE86LaF

PaC-kE88LaF

PaC-kE89LaF

PaC-kE85LaF

Quantity

(298X300)

(298X300)

(298X300)

(411X600)

Shape

Detailed installation information should be referred to its installation Manual (WT02574X04)


PaC-kE-TB-F
item
Quantity

Screw
10/12*

Filter box
1

installation manual
1
*PaC-kE250TB has 12 pieces of screw..

Shape

Detailed installation information should be referred to its installation Manual (WT03018X02, WT03019X02)

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

PEFY-27

7. OPTIONAL PARTS

DATA U4

7-3. Drain Pump Kit PAC-KE04DM-F for PEFY-NMHU-E


If drain water can not flow out the Indoor unit by gravity and gradient, a Drain pump for draining is needed.
Drain pump PAC-KE04DM-F can pump water up to 550mm [21-21/32 in.] high from the drain pan.

Item

Drain pump ass'y

Quantity

Separator

Rubber plug

Connector

Dummy connector

Shape
Drain socket
Item

Rubber bushing

Quantity

Band

PTT screw 4X10

Fixing plate

6+1 (spare)

Installation manual

Shape

Detailed installation information should be referred to its Installation Manual (WT03312X02)

7-4. External Heater Adapter PAC-YU24HT for PEFY-P-NMHU-E


External heater adaptor PaC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
a basic connection method is shown as follows:(For details, refer to its installation Manual.)
remote control Board

relay circuit

Electric Heater
power source

indoor unit
control board

adapter

X
X

red

White

red

red

Electric
Heater

Yellow

CN24

outdoor unit
control board
Dip switch
PUHY,PUrY-P-TGMU type
SW5-2 "oN"
PUHY,PUrY-P-YHMU type
SW5-10 "oN"

CN22
Green

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Drain sensor

PUMY series
SW4-4 "oN"

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below operation coil


rated voltage : 12vDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PaC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : Cvv, CvS, CPEv or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 aWG)
Don't extend the cable more than 10 meters (32ft)
recommended circuit

88H

FS1

H1

88H

FS2
FS1

H2

r
1-phase power
supply

208v, 230v/60Hz

Wiring diagram

FS1, 2 ----- Thermal fuse

FS2

H1, H2 ----- Heater


26H

88H
Control board

88H --------- Electromagnetic contactor


CN24

item
Quantity

External output cable


2

Fan speed setting cable


with resistance
2

Shape

refer to the installation Manual (WT04645X02) wiring and installation details.

PEFY-28

26H --------- overheat protection


thermostat

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

7. OPTIONAL PARTS

DATA U4

7-5. External Heater Adapter PAC-YU25HT for PEFY-P-NMSU-E


External heater adaptor PaC-YU25HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
a basic connection method is shown as follows:(For details, refer to its installation Manual.)
relay circuit

indoor unit
control board

adapter

White

2
1

X
Electric
Heater

Dip switch
PUHY,PUrY-P-TGMU type
SW5-2 "oN"
PUHY,PUrY-P-YHMU type
SW5-10 "oN"

CN4Y
White

red

Yellow

CN24

outdoor unit
control board

PUMY series
SW4-4 "oN"

(for use with the panel heater)

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below operation coil


rated voltage : 12vDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PaC-YU25HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : Cvv, CvS, CPEv or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 aWG)
Don't extend the cable more than 10 meters (32ft)
recommended circuit

88H

FS1

H1

88H

FS2
FS1

H2

r
1-phase power
supply

208v, 230v/60Hz

Wiring diagram

FS1, 2 ----- Thermal fuse

FS2

H1, H2 ----- Heater


26H

88H
Control board

26H --------- overheat protection


thermostat
88H --------- Electromagnetic contactor

CN24

item
Quantity

External output cable


2

Connector
(for use with the panel heater)
3

Shape

refer to the installation Manual (WT05383X01) for wiring and installation details.

PEFY-P-NMSU-E/PEFY-P-NMHU-E (Feb. 2009)

PEFY-29

PEFY-P-NMSU-E
PEFY-P-NMHU-E

Electric Heater
power source

remote control Board

Ceiling-concealed (Ducted)

DATA U4

PDFY-P-NMU-E
1. SPECIFICATIONS...................................................................................................................................................PDFY-3
2. EXTERNAL DIMENSIONS......................................................................................................................................PDFY-6
3. Center of Gravity...........................................................................................................................................PDFY-8
4. ELECTRICAL WIRING DIAGRAMS........................................................................................................................PDFY-9
5. SOUND PRESSURE LEVELS..............................................................................................................................PDFY-11
5-1. Sound Pressure Levels...............................................................................................................................PDFY-11
5-2. NC Curves...................................................................................................................................................PDFY-11
6. FAN CHARACTERISTIC CURVES.......................................................................................................................PDFY-15

7-4. External Heater Adapter PAC-YU24HT-F....................................................................................................PDFY-23

PDFY-P-NMU-E (Feb. 2009)

PDFY-1

PDFY-P-NMU-E

7. OPTIONAL PARTS................................................................................................................................................PDFY-21
7-1. Optional Parts Line Up for the Indoor Unit..................................................................................................PDFY-21
7-2. Round Duct Flange PAC-KD-EDF-F for PDFY-P-NMU-E............................................................................PDFY-21
7-3. Drain Pump Kit PAC-KD02DM-FA...............................................................................................................PDFY-22

Ceiling-concealed
(Ducted)
Ceiling
mounted(Built-in
type)

DATA
DATA U4
U3

I.Ceiling mounted(Built-in type)

PDFY-P-NMU-E

PDFY-P-NMU-E

PDFY-P-NMU-E

Flexible design allows elegant interior layout, suitable for high class hotels, residential, etc..

Long room
L-shaped rooms
Room with fixed
ceiling fixtures

The PDFY models are high-performance, ceiling-concealed indoor units. In fact, if it werent for the constantly comfortable environment these units deliver, you
would not know they were there. The ducted fan coils are designed to be installed above the ceiling, hidden from public view. And theyre extremely quiet, with
sound ratings that range from 28 46 dB(A). Hidden doesnt mean hard to reach. The PDFY fan coils are extremely easy to access and maintain according
to their application. They can be easily customized to your cooling and heating needs. The external static pressure settings are adjustable to meet different
application conditions such as the use of a high performance filter.

Ceiling mounted

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PDFY-P-NMU-E

Nominal conditions
conditions *1,
*1, *2
*2 are
are referred
referabletoatinthe
** Nominal
theSpecification
Specificationsheet.
sheet.

PDFY-2

PDFY-P-NMU-E
(Feb. 2009)
PDFY-P-NMU-E

IU - C - 2

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

1. SPECIFICATIONS

Model

PDFY-P06NMU-E

PDFY-P08NMU-E

Power source

PDFY-P12NMU-E

PDFY-P15NMU-E

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW
Power input

kW

Current input

6,000

8,000

12,000

1.8

2.3

3.5

4.4

0.120/0.120

0.120/0.120

0.120/0.120

0.150/0.150

0.61/0.68

0.61/0.68

0.61/0.68

0.77/0.85

6,700

9,000

13,500

17,000

2.0

2.6

4.0

5.0

0.120/0.120

0.120/0.120

0.120/0.120

0.150/0.150

0.61/0.68

0.61/0.68

0.61/0.68

0.77/0.85

External finish

Galvanized

External dimension H x W x D

in.

11-5/8 x 27-31/32 x 28-15/16

11-5/8 x 27-31/32 x 28-15/16

11-5/8 x 27-31/32 x 28-15/16

11-5/8 x 37-13/16 x 28-15/16

295 x 710 x 735

295 x 710 x 735

295 x 710 x 735

295 x 960 x 735

57 (26)

57 (26)

60 (27)

71 (32)

mm
Net weight

lbs (kg)

Heat exchanger
FAN

15,000

Cross fin(Aluminium fin and copper tube)


Type x Quantity
External

in.WG

static
static pressure
press

Sirocco fan x 1

Sirocco fan x 1

Sirocco fan x 1

Sirocco fan x 2

0.120-0.200-0.321 (208V)

0.120-0.200-0.321 (208V)

0.120-0.200-0.321 (208V)

0.120-0.200-0.321 (208V)

Pa

30-50-80

30-50-80

30-50-80

30-50-80

0.161-0.241-0.401 (230V)

0.161-0.241-0.401 (230V)

0.161-0.241-0.401 (230V)

0.161-0.241-0.401 (230V)

40-60-100

40-60-100

40-60-100

40-60-100

Pa
Motor type

1-phase induction motor

Motor output

kW

0.075

0.075

0.075

Driving mechanism

0.085

Direct-driven

Airflow rate

cfm

(Low-Mid1-Mid2-High)

m3 / min

211-229-264-300

211-229-264-300

211-229-264-300

353-388-441-494

6.0-6.5-7.5-8.5

6.0-6.5-7.5-8.5

6.0-6.5-7.5-8.5

10.0-11.0-12.5-14.0

L/s
Sound
Pressure
Level (Low-Mid1-Mid2-High) dB <A>
Noise level
(Low-Mid1-Mid2-High)

100-108-125-142

100-108-125-142

100-108-125-142

167-183-208-233

26-28-31-34 (208V)

26-28-31-34 (208V)

26-28-31-34 (208V)

32-34-35-37 (208V)

(measured in anechoic room)

dB <A>

28-30-33-36 (230V)

28-30-33-36 (230V)

28-30-33-36 (230V)

34-36-37-39 (230V)

dB <A>

Insulation material

Polystyrene foam,Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit


Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

R410A CITY MULTI

R410A CITY MULTI

R410A,R22 CITY MULTI

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

in. (mm)
in. (mm)
in. (mm)

External

W277668

Wiring

W660136

Refrigerant cycle

R410A,R22 CITY MULTI

Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

Circular
ductflange
flange
Round duct

PAC-KD32EDF-F

PAC-KD32EDF-F

PAC-KD32EDF-F

PAC-KD50EDF-F

Drain pump kit

PAC-KD02DM-FA

PAC-KD02DM-FA

PAC-KD02DM-FA

PAC-KD02DM-FA

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

Maintenance panel with air intake

MCMP-P36DSW-H

MCMP-P36DSW-H

MCMP-P36DSW-H

MCMP-P56DSW-H

Drain hose I.D. 1-1/4inch (32mm)

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PDFY-P06-15NMU-E

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

IUPDFY-3
-C-3

PDFY-P-NMU-E

in.WG

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

Model

PDFY-P18NMU-E

PDFY-P24NMU-E

Power source

PDFY-P27NMU-E

PDFY-P30NMU-E

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW
Power input

kW

Current input

18,000

24,000

27,000

5.3

7.0

7.9

8.8

0.150/0.150

0.170/0.170

0.180/0.180

0.210/0.210

0.77/0.85

0.87/0.96

0.94/1.04

1.07/1.19

20,000

27,000

30,000

34,000

5.9

7.9

8.8

10.0

0.150/0.150

0.170/0.170

0.180/0.180

0.210/0.210

0.77/0.85

0.87/0.96

0.94/1.04

1.07/1.19

External finish

Galvanized

External dimension H x W x D

in.

11-5/8 x 37-13/16 x 28-15/16

11-5/8 x 45-11/16 x 28-15/16

11-5/8 x 45-11/16 x 28-15/16

11-5/8 x 45-11/16 x 28-15/16

295 x 960 x 735

295 x 1,160 x 735

295 x 1,160 x 735

295 x 1,160 x 735

75 (34)

86 (39)

86 (39)

86 (39)

mm
Net weight

lbs (kg)

Heat exchanger
FAN

Cross fin(Aluminium fin and copper tube)


Type x Quantity
External

in.WG

static
static pressure
press

Sirocco fan x 2

Sirocco fan x 2

Sirocco fan x 2

Sirocco fan x 2

0.120-0.200-0.321 (208V)

0.120-0.200-0.321 (208V)

0.120-0.200-0.321 (208V)

0.120-0.200-0.401 (208V)

Pa
in.WG

PDFY-P-NMU-E

30,000

30-50-80

30-50-80

30-50-80

30-50-100

0.161-0.241-0.401 (230V)

0.161-0.241-0.401 (230V)

0.161-0.241-0.401 (230V)

0.161-0.241-0.462 (230V)

40-60-100

40-60-100

40-60-100

40-60-115

Pa
Motor type

1-phase induction motor

Motor output

kW

0.085

0.095

0.095

Driving mechanism

0.095

Direct-driven

Airflow rate

cfm

(Low-Mid1-Mid2-High)

m3 / min
L/s

353-388-441-494

441-494-565-635

477-547-618-689

494-582-653-741

10.0-11.0-12.5-14.0

12.5-14.0-16.0-18.0

13.5-15.5-17.5-19.5

14.0-16.5-18.5-21.0

167-183-208-233

208-233-267-300

225-258-292-325

233-275-308-350

Sound
Level (Low-Mid1-Mid2-High) dB <A>
Noise Pressure
level (Low-Mid1-Mid2-High)

32-34-35-37 (208V)

28-32-34-37 (208V)

31-35-37-40 (208V)

32-35-38-40 (208V)

(measured in anechoic room)

dB <A>

34-36-37-39 (230V)

30-34-36-39 (230V)

32-36-38-40 (230V)

34-37-40-42 (230V)

dB <A>

Insulation material

Polystyrene foam,Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

1/4 (6.35) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

1/2 (12.7) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

in. (mm)
in. (mm)
in. (mm)

External

W277668

Wiring

W660136

Refrigerant cycle

3/8 (9.52) Flare

Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

Circular
ductflange
flange
Round duct

PAC-KD50EDF-F

PAC-KD80EDF-F

PAC-KD80EDF-F

PAC-KD80EDF-F

Drain pump kit

PAC-KD02DM-FA

PAC-KD02DM-FA

PAC-KD02DM-FA

PAC-KD02DM-FA

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

Maintenance panel with air intake

MCMP-P56DSW-H

MCMP-P90DSW-H

MCMP-P90DSW-H

MCMP-P90DSW-H

Drain hose I.D. 1-1/4inch (32mm)

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

*2 Nominal heating conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PDFY-P18-30NMU-E

PDFY-4

PDFY-P-NMU-E
(Feb. 2009)
PDFY-P-NMU-E

IU - C - 4

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

Model

PDFY-P36NMU-E

PDFY-P48NMU-E

36,000

48,000

Power source

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW

10.6

14.1

0.290/0.290

0.390/0.390

1.48/1.64

1.99/2.21

40,000

54,000

11.7

15.8

0.290/0.290

0.390/0.390

Power input

kW

Current input

1.48/1.64

1.99/2.21

External dimension H x W x D

in.

13-7/32 x 59-15/32 x 30-17/32

13-7/32 x 59-15/32 x 30-17/32

335 x 1,510 x 775

335 x 1,510 x 775

Net weight

lbs (kg)

115 (52)

115 (52)

Sirocco fan x 2

Sirocco fan x 2

0.200-0.401-0.522 (208V)

0.200-0.401-0.522 (208V)

External finish

Galvanized
mm

Heat exchanger
FAN

Cross fin(Aluminium fin and copper tube)


Type x Quantity
External

in.WG

static
static pressure
press

Pa

50-100-130

0.241-0.462-0.602 (230V)

0.241-0.462-0.602 (230V)

Pa

60-115-150

60-115-150

kW

0.140

0.190

Airflow rate

cfm

688-988

847-1,200

(Low-High)

m3 / min

19.5-28.0

24.0-34.0

L/s

325-467

400-567

in.WG
Motor type

PDFY-P-NMU-E

50-100-130

1-phase induction motor

Motor output
Driving mechanism

Direct-driven

Sound
Pressure
Level (Low-High)
Noise level
(Low-High)

dB <A>

36-44 (208V)

42-46 (208V)

(measured in anechoic room)

dB <A>

38-45 (230V)

43-47 (230V)

dB <A>

Insulation material

Polystyrene foam,Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

in. (mm)
in. (mm)

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

3/4 (19.05) Flare

3/4 (19.05) Flare

O.D. 1-1/4 (32)

O.D. 1-1/4 (32)

in. (mm)

External

W277669

Wiring

W660135

Refrigerant cycle
Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

Circularduct
ductflange
flange
Round

Drain hose I.D. 1-1/4inch (32mm)


PAC-KD125EDF-F

PAC-KD125EDF-F

Drain pump kit

PAC-KD02DM-FA

PAC-KD02DM-FA

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

Maintenance panel with air intake

MCMP-P160DSW-H

MCMP-P160DSW-H

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PDFY-P36-48NMU-E

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

IUPDFY-5
-C-5

251(9-29/32)
Drain hole

13
16

902
1000
960
936
90
886
(35-17/32) (39-3/8) (37-13/16) (36-7/8) (3-9/16) (34-29/32)
1136
1102
1200
1160
92.5
1086
(43-13/32) (47-1/4) (45-11/16) (44-3/4) (3-21/32) (42-25/32)

PDFY-P242730NMU-E

PDFY-P18NMU-E

F
9

13

936
902
960
90
886
1000
(35-17/32) (39-3/8) (37-13/16) (36-7/8) (3-9/16) (34-29/32)

90
(3-9/16)
190(7-1/2)

652
710
636
686
95
750
(25-11/16) (29-17/32) (27-31/32) (27-1/32) (3-3/4) (25-1/16)

274(10-13/16)
(2-17/32) (4-31/32)
64
126

PDFY-P060812NMU-E

(option)

Drain hole

35(1-13/32)
34(1-11/32)

PDFY-P15NMU-E

Model

In case of bottom inlet.

10
Air Filter
(13/32)

735(28-15/16)

670(26-13/32)(Suspension bolt pitch)

Water filling port

30(1-3/16)

Control box

Airflow

(4-3/8)
111

10 (13/32)

101
(4)

975
(38-3/4)

300
151
780
(11-13/16) (5-31/32) (30-23/32)

300
780
151
(11-13/16) (5-31/32) (30-23/32)

300
(11-13/16)

65(2-9/16)X(G-1)=M

Airflow

D(Suspension bolt pitch)

200
126
520
(7-7/8) (4-31/32) (20-15/32)

65(2-9/16)

mm(in.)

35(1-13/32)

12(1/2)

20(13/16) or more

Drain hose
I.D.32mm (1-1/4inch)
<flexible joint >
(accessory)

20(13/16) or more

29(1-5/32)

Make the access door at the appointed position properly


for service maintenance.

Ceiling surface

0 (22

Airflow

Access door

6)
-9/1
(27
0
700 50~202~7-7/8)
1 -29/3
(3-1 100
(5
5/16 ~2
~7-7 00
/8)
(17-2450
3/32
)

60 (2
-3

/8)

126(4-31/32)

(17

450-23/32)

)
3/16
(1
20

Note2

/32

-15

PDFY-P06,08,12,15,18,24,27,30NMU-E

52(2-1/16)

35(1-13/32)

12(1/2)

Suspension bolt hole


4-14X22(9/16X7/8) hole

295(11-5/8)

600(23-5/8) Max

When installing the drain pump(option).

59(2-11/32)

133 (5-1/4)

22(7/8)

251(9-29/32)

33 (1-5/16)
(6-7/8)
174

30 (1-3/16)
10(13/32)

300(11-13/16) or less

172 (6-25/32)
(1-1/8)
28

Access door

31(1-1/4)

Required space for service and maintenance.


Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned and fan motor or fan is
changed.
57

/32
25

PDFY-P-NMU-E (Feb. 2009)

(6-

Note:1. Use M10 screw for the Suspension bolt (field supply).
2. On Model :18, you would use flare nut
packed with the Indoor Unit, when connecting
the Outdoor Unit for R22.

(4-27/32)
123

PDFY-6
670(26-13/32)(Suspension bolt pitch)

PDFY-P-NMU-E

2. External Dimensions
DATA U4

Drw. : IU-W277668
Unit : mm(in)

Control box
30(1-3/16)

59(2-11/32)

600(23-5/8) Max

10
Air Filter
(13/32)
In case of bottom inlet.

173 (6-13/16)

22(7/8)

291(11-15/32)

Drain hole

(3-9/16)
190(7-1/2)

90

274(10-13/16)
(2-17/32) (4-25/32)
64 121

35(1-13/32)
34(1-11/32)

305(12-1/32)

52(2-1/16)

35(1-13/32)

12(1/2)

Model

PDFY-P48NMU-E

PDFY-P36NMU-E

1452(57-3/16)

1440(56-23/32)

1510(59-15/32)

1486(58-17/32)(Suspension bolt pitch)

65X20=1300(2-9/16X20=51-3/16)

Airflow

300X4=1200(11-3/16X4=47-1/4)

20(13/16) or more

Drain hose
I.D.32mm (1-1/4inch)
<flexible joint >
(accessory)

105
(4-5/32)

mm(in.)

65(2-9/16)

300(11-13/16)

(4-31/32)
126

29(1-5/32)

35(1-13/32)

12(1/2)

Access door

(2-3
/8)

Airflow

(17-2

4503/32)

22-

15/3

156(6-5/32)

/32)
(61-1
/16) 1550
(13

20

20(13/16) or more

Make the access door at the appointed position properly for service maintenance.

30(1-3/16)

(17-2 450
3/32
)

60

/32

Ceiling surface

25

6)
-9/1
(27
00
700 50~22~7-7/8)
1 -29/3
(3-1 10
(5
5/16 0~
~7-7 20
/8) 0

31(1-1/4)
710(27-31/32)(Suspension bolt pitch)

70 (

Note2

2)

(5-1/2)
139

Access door

10 (13/32)

Required space for service and maintenance.


Keep the service space for the maintenance from the bottom
when the heat exchanger is cleaned and fan motor or fan is
changed.
5

PDFY-P36,48NMU-E

Water filling port

291(11-15/32)

(option)

Drain hole

710(27-31/32)(Suspension bolt pitch)

775(30-17/32)

Airflow

33
(15/16)
(8-7/16)
214

When installing the drain pump(option).

(5-31/32)
151

Suspension bolt hole


4-14X22(9/16X7/8) hole

335(13-7/32)

300(11-13/16) or less

206(8-1/8)
(11/8)
28

PDFY-P-NMU-E (Feb. 2009)

(6-

10(13/32)

PDFY-P-NMU-E

Note:1. Use M10 screw for the Suspension bolt (field supply).
2. On this model, you would use flare nut
packed with the Indoor Unit, when connecting
the Outdoor Unit for R22.

2. External Dimensions
DATA U4

Drw. : IU-W277669
Unit : mm(in)

PDFY-7

3. Center of Gravity

DATA U4

PDFY-P06,08,12,15,18,24,27,30,36,48NMU-E
W

L
Y

X
H

Ref.: PDFY_NMU_COG_USDB_ALL

A: Center of gravity

PDFY-P-NMU-E

(mm)[in]
Model name
PDFY-P06NMU-E
PDFY-P08NMU-E
PDFY-P12NMU-E
PDFY-P15NMU-E
PDFY-P18NMU-E
PDFY-P24NMU-E
PDFY-P27NMU-E
PDFY-P30NMU-E
PDFY-P36NMU-E
PDFY-P48NMU-E

PDFY-8

W
670 [26-13/32]
670 [26-13/32]
670 [26-13/32]
670 [26-13/32]
670 [26-13/32]
670 [26-13/32]
670 [26-13/32]
670 [26-13/32]
710 [27-31/32]
710 [27-31/32]

L
686 [27-1/32]
686 [27-1/32]
686 [27-1/32]
936 [36-7/8]
936 [36-7/8]
1136 [44-3/4]
1136 [44-3/4]
1136 [44-3/4]
1486 [58-17/32]
1486 [58-17/32]

H
148 [5-27/32]
148 [5-27/32]
148 [5-27/32]
148 [5-27/32]
148 [5-27/32]
148 [5-27/32]
148 [5-27/32]
148 [5-27/32]
168 [6-5/8]
168 [6-5/8]

PDFY-P-NMU-E (Feb. 2009)

X
285 [11-1/4]
285 [11-1/4]
285 [11-1/4]
285 [11-1/4]
285 [11-1/4]
285 [11-1/4]
285 [11-1/4]
285 [11-1/4]
305 [12-1/32]
305 [12-1/32]

Y
343 [13-17/32]
343 [13-17/32]
343 [13-17/32]
468 [18-7/16]
468 [18-7/16]
568 [22-3/8]
568 [22-3/8]
568 [22-3/8]
743 [29-9/32]
743 [29-9/32]

Z
128 [5-1/16]
128 [5-1/16]
128 [5-1/16]
128 [5-1/16]
128 [5-1/16]
128 [5-1/16]
128 [5-1/16]
128 [5-1/16]
148 [5-27/32]
148 [5-27/32]

0 1

2 3

Power source terminal bed


Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T
Fuse AC250V 5A F
Transformer
Drain pump
Drain sensor
Electronic linear expan. valve
Varistor

NAME
Fan motor
Capacitor (for MF)
Indoor controller board
Address board

SYMBOL EXPLANATION

SYMBOL
MF
C
I.B.
A.B.
TB2
TB5
TB15
F
<F2>
T
<DP>
<DS>
LEV
ZNR,ZNR1

CN62
(White)

0 1

(White)
CN82

(Red)
CN42

2 3

8
7
6
5
4
3
2
1

TH22

2 1

(Red)
CN20

TH23

2 1

(White)
CN21

LED2

2 1

(Black)
CN29

*NOTE 1

DS

CN31

2 1

(White)
CN31

LEV

6 5 4 3 2 1

(White)
CN60
3

(White) (Green)(White) (White) (Green)(Yellow)(White) (Red) (Green)

CN32 CN52 CN51 CN41 CN23 CN24 CN25 CN27 CN22

LED1

TH21

8 7 6 5 4 3 2 1

(Red)
CN81

SW2

(Red)
CN3T

SYMBOL
TH21
TH22
TH23
LED1
LED2
CNV
CN22
CN23
CN24
CN25
CN27
CN32
CN41
CN51
CN52
NAME
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)
Power supply (I.B.)
Power supply (Remote controller)
Connector
Connector
Connector
Connector
Connector
Connector
Connector (Centrally control)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote indication)

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

X01

NAME
Aux.relay
Surge absorber board
Switch (optional parts)
Switch (optional parts)
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (connection No.set)
Switch(for mode selection)
Switch(for voltage selection)
Switch(for model selection)
Switch(for capacity code)
Switch(for mode selection)
Switch(for model selection)

*NOTE 1

DP

5 3 1

AC250V
6.3A T

AC250V
5A F

( )

F2

S.B.

A.B.

TB15

M2
M1

TB5,TB15

TO MA REMOTE CONTROLLER

(TRANSMISSION TERMINAL BED)

L2

L1

TB2

TB2

TO DUCT

CONTROL BOX

I.B.

POWER SUPPLY
~ 208V/230V 60Hz

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

ME REMOTE CONTROLLER

BC CONTROLLER

TO OUTDOOR UNIT

TB5 (TRANSMISSION TERMINAL BED)


S(SHIELD)

2
1

S.B.
CN1 1 (Yellow)

2
1

3
1

*A
*A connector is
attached to the
drain pump kit,
which is an
optional part.
*NOTE 1,2

DSA1

ZNR1

CND (Red)

PARTS LOCATION

MF

(Blue)
CN2M

(Blue)
CN3A

I.B.

( )

3 1

ZNR

(White)
FAN3

(White) 4 2 1

3 1

FAN CON

(Green)
CNV

X03

FAN2

(Yellow) 5

INSIDE SECTION OF CONTROL BOX

(Blue)
CNP

(White) 3 2 1

3 1

(White)
CNT

Inside < > is the optional parts.

SYMBOL
X01,X03
S.B.
SWA(A.B.)
SWC(A.B.)
SW11(A.B.)
SW12(A.B.)
SW14(A.B.)
SW1(A.B.)
SW5(A.B.)
SW7(A.B.)
SW2(I.B.)
SW3(I.B.)
SW4(I.B.)

NOTE;1.The part of the broken line indicates the circuit for optional parts.
2.*A in the chart is the connector for a drain pump test run operation.
(The Drain Pump operates continuously if the connector is inserted
and the power is supplied.)
After the test run, make sure to remove the *A connector.
3.The wirings to TB2,TB5,TB15 shown in chained line are field work.
4.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.

SW14
SW11
SW12
(Connection No.) (2nd digit) (1st digit)

7 8 9A

F 0 12

345

SW5
SW7

SWC

SW1

SWA

5 6

B CD

1 2 3 4 5 6

A.B.

5 6

7 8

1
2
3
4

7 8

SW3

PDFY-P06,08,12,15,18,24,27,30NMU-E

PDFY-P-NMU-E

SW4

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATA U4
U3

3. ELECTRICAL WIRING DIAGRAMS

Drw. : IU-W660136

IUPDFY-9
-C-8

B CD

F 0 12

PDFY-P-NMU-E
(Feb. 2009)
PDFY-P-NMU-E

SYMBOL
MF
C
I.B.
TB2
TB5
TB15
F901
ZNR1,ZNR901
T
LEV
TH21
TH22
TH23

TH21

SW3

0 1

(White)

2 1

CN29(Black)

*NOTE1

DS

CN31

2 1

CN31(White)

LED2

LEV

6 5 4 3 2 1

CN60(White)
3

CN3T(Red)
3 1

CNP(Blue)
3 1

*NOTE1

DP

3 2 1

T1

(White)
CNT

CN7V(White)

SYMBOL
SW11
SW12
SW14
SW1
SW2
SW3
SW4
SW5
SW7
SW8
X01,X04~X07
<T1>,T2,T3

NAME
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (connection No.set)
Switch (for mode selection)
Switch (for capacity code)
Switch(for mode selection)
Switch(for model selection)
Switch(for voltage selection)
Switch(for model selection)
Switch(for mode selection 3)
Aux.relay
Terminal

SYMBOL
CNV
CN22
CN24
CN25
CN27
CN32
CN41
CN51
CN52
LED1
LED2
<DP>
<DS>
<F2>

NAME
Connector
Connector
Connector
Connector
Connector
Connector (centrally control)
Connector (HA terminal-A)
Connector (centrally control)
Connector (remote indication)
Power supply (I.B.)
Power supply (Remote controller)
Drain pump
Drain sensor
Fuse AC250V 5A F

X01

5 4 3 2 1

NOTE;1.The part of the broken line indicates the circuit for optional parts.
2.*A in the chart is the connector for a drain pump test run operation.
(The Drain Pump operates continuously if the connector is inserted
and the power is supplied.)
After the test run, make sure to remove the *A connector.
3.The wirings to TB2,TB5,TB15 shown in chained line are field work.
4.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.

TH23

2 1

2 1

TH22

CN21(White)

CN20(Red)

SW1

SW11
(1st digit)

LED1

(Green)

(Yellow)

CN32

(White)

Inside < > is the optional parts.

SW2

SW12
(2nd digit)

NAME
Fan motor
Capacitor (for MF)
Indoor controller board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T
Varistor
Transformer
Electronic linear expan. valve
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)

SYMBOL EXPLANATION

SW7

0 1

2 3

SW4

(Green)

CN52

(White)

CN22

CN24

2 3

SW14
(Connection No.)

7 8 9A

SW8
345

SW5

(White)

(Red)

CN41

5 6

CN27

7 8

CN25

5 6

CN51

PDFY-10
7 8

MF

4 2 1

T2

DSA1

ZNR1

(Blue)

CN2M

AC250V
6.3A T

CND(Red)

AC250V
5A F

( )

F2

2
1

3
1

PARTS LOCATION

2
1

TO MA REMOTE CONTROLLER

TB15 (TRANSMISSION TERMINAL BED)

TB5,TB15

L2

L1

TO DUCT

TB2

BC CONTROLLER

CONTROL BOX

I.B.

~ 208/230V 60Hz

POWER SUPPLY

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

ME REMOTE CONTROLLER

TO OUTDOOR UNIT

M2
M1

TB2

S(SHIELD) TB5 (TRANSMISSION TERMINAL BED)

*A
*A connector is
attached to the
drain pump kit,
which is an
optional part.
*NOTE 1,2

(Blue)
4 2 1

5 3 1

(Red)
4 2 1

(Blue)

CN3A

( )

F 901

C
Color/External static pressure
White/Low Pressure
Red/Middle Pressure
Blue/High Pressure

(White)

T3

1 3 5 7 9

(White)
CN90

X06 X07 X05 X04 ZNR901

I.B.

INSIDE SECTION OF CONTROL BOX

PDFY-P-NMU-E

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATAU4
U3

PDFY-P36,48NMU-E
Drw. : IU-W660135

IU - C - 9

5.
4. Sound
SOUND Pressure
PRESSURE Levels
LEVELS

DATA
DATAU4
U3

4-1. Sound
Levels
5-1.
SoundPressure
Pressure
Levels
4. SOUND LEVELS

Operating sound pressure levels


PDFY-P-NMU-E

( Low - ( Middle2 - Middle1 ) - High )

6-1/2ft.
(2.0m)

Sound pressure level ( A weighted )

PDFY-P06,P08,P12NMU-E
PDFY-P15,P18NMU-E

7/8ft.
(0.27m)

Unit : dB (A)

Model

Aux. duct

4-7/8ft.
(1.5m)

PDFY-P24NMU-E

Measurement location

208V

26 - 28 - 31 - 34

230V

28 - 30 - 33 - 36

208V

32 - 34 - 35 - 37

230V

34 - 36 - 37 - 39

208V

28 - 32 - 34 - 37

230V

30 - 34 - 36 - 39

PDFY-P27NMU-E

208V

31 - 35 - 37 - 40

230V

32 - 36 - 38 - 40

PDFY-P30NMU-E

208V

32 - 35 - 38 - 40

230V

34 - 37 - 40 - 42

PDFY-P36NMU-E

208V

36 - 44

PDFY-P48NMU-E

230V

38 - 45

208V

42 - 46

230V

43 - 47

PDFY-P-NMU-E

* Measured in anechoic room

4-2. NC
5-2.
NCcurves
Curves

External Static Pressure: 80Pa


Power Source: 208V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P06,08,12NMU-E_WYN B0-4401-1

Octave band pressure level (dB) 0dB=20Pa

PDFY-P06,08,12NMU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P06,08,12NMU-E

External Static Pressure: 30Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P06,08,12NMU-E

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

External Static Pressure: 100Pa


Power Source: 230V 60Hz

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P06,08,12NMU-E_WYN B0-4401-4

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 60Pa


Power Source: 230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 40Pa


Power Source: 230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P06,08,12NMU-E

High
Low

8k

Ref.:NC_PDFY-P06,08,12NMU-E_WYN B0-4401-3

PDFY-P06,08,12NMU-E

65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P06,08,12NMU-E_WYN B0-4401-2

PDFY-P06,08,12NMU-E

70.0

60Hz
60Hz

60.0

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

Ref.:NC_PDFY-P06,08,12NMU-E_WYN B0-4401-5

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P06,08,12NMU-E_WYN B0-4401-6

IUPDFY-11
- C - 10

5.
4. Sound
SOUND Pressure
PRESSURE Levels
LEVELS

DATA
DATAU4
U3

External Static Pressure: 80Pa


Power Source: 208V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P15,18NMU-E_WYN B0-4402-1

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P15,18NMU-E_WYN B0-4402-4

Octave band pressure level (dB) 0dB=20Pa

60Hz
60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 100Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P15,18NMU-E

External Static Pressure: 60Pa


Power Source: 230V 60Hz
High
Low

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P24NMU-E_WYN B0-4403-1

Octave band pressure level (dB) 0dB=20Pa

60.0

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 80Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P24NMU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz
60Hz
60Hz

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P24NMU-E_WYN B0-4403-4

PDFY-12

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P24NMU-E_WYN B0-4403-5

PDFY-P-NMU-E
(Feb. 2009)
PDFY-P-NMU-E

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 100Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P24NMU-E

External Static Pressure: 60Pa


Power Source: 230V 60Hz
60Hz
60Hz

8k

Ref.:NC_PDFY-P24NMU-E_WYN B0-4403-3

PDFY-P24NMU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P24NMU-E_WYN B0-4403-2

External Static Pressure: 40Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PDFY-P24NMU-E

70.0

8k

Ref.:NC_PDFY-P15,18NMU-E_WYN B0-4402-6

PDFY-P24NMU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P15,18NMU-E_WYN B0-4402-5

External Static Pressure: 30Pa


Power Source: 208V 60Hz
65.0

60Hz
60Hz

60.0

PDFY-P24NMU-E

70.0

8k

Ref.:NC_PDFY-P15,18NMU-E_WYN B0-4402-3

PDFY-P15,18NMU-E

65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P15,18NMU-E_WYN B0-4402-2

External Static Pressure: 40Pa


Power Source: 230V 60Hz
70.0

60Hz
60Hz

60.0

PDFY-P15,18NMU-E

Octave band pressure level (dB) 0dB=20Pa

PDFY-P-NMU-E

60Hz
60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P15,18NMU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P15,18NMU-E

External Static Pressure: 30Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P15,18NMU-E

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P24NMU-E_WYN B0-4403-6

IU - C - 11

5. SOUND
Sound PRESSURE
Pressure LEVELS
Levels
4.

DATA
DATAU4
U3

External Static Pressure: 80Pa


Power Source: 208V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P27NMU-E_WYN B0-4404-1

Octave band pressure level (dB) 0dB=20Pa

PDFY-P27NMU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P27NMU-E

External Static Pressure: 30Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P27NMU-E

8k

70.0

High
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P27NMU-E_WYN B0-4404-4

Octave band pressure level (dB) 0dB=20Pa

High
Low

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 100Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P27NMU-E

External Static Pressure: 60Pa


Power Source: 230V 60Hz

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P30NMU-E_WYN B0-4405-1

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 100Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P30NMU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P30NMU-E

High
Low

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P30NMU-E_WYN B0-4405-4

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Octave band pressure level (dB) 0dB=20Pa

60.0

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 115Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P30NMU-E

External Static Pressure: 60Pa


Power Source: 230V 60Hz
60Hz
60Hz

8k

Ref.:NC_PDFY-P30NMU-E_WYN B0-4405-3

PDFY-P30NMU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P30NMU-E_WYN B0-4405-2

External Static Pressure: 40Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PDFY-P30NMU-E

70.0

8k

Ref.:NC_PDFY-P27NMU-E_WYN B0-4404-6

External Static Pressure: 30Pa


Power Source: 208V 60Hz
65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P27NMU-E_WYN B0-4404-5

PDFY-P30NMU-E

70.0

60Hz
60Hz

60.0

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

Ref.:NC_PDFY-P30NMU-E_WYN B0-4405-5

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P30NMU-E_WYN B0-4405-6

IUPDFY-13
- C - 12

PDFY-P-NMU-E

PDFY-P27NMU-E

60.0

8k

Ref.:NC_PDFY-P27NMU-E_WYN B0-4404-3

External Static Pressure: 40Pa


Power Source: 230V 60Hz
65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P27NMU-E_WYN B0-4404-2

PDFY-P27NMU-E

70.0

60Hz
60Hz

4. Sound
SOUND Pressure
PRESSURE Levels
LEVELS
5.

DATA U3
DATA
U4

External Static Pressure: 130Pa


Power Source: 208V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P36NMU-E_WYN B0-4406-1

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P36NMU-E_WYN B0-4406-4

Octave band pressure level (dB) 0dB=20Pa

60Hz
60Hz

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 150Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P36NMU-E

External Static Pressure: 115Pa


Power Source: 230V 60Hz
High
Low

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P48NMU-E_WYN B0-4407-1

Octave band pressure level (dB) 0dB=20Pa

60.0

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 130Pa


Power Source: 208V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P48NMU-E

External Static Pressure: 100Pa


Power Source: 208V 60Hz
60Hz
60Hz

8k

70.0

High
Low

65.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P48NMU-E_WYN B0-4407-4

PDFY-14

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P48NMU-E_WYN B0-4407-5

PDFY-P-NMU-E
PDFY-P-NMU-E (Feb. 2009)

Octave band pressure level (dB) 0dB=20Pa

External Static Pressure: 150Pa


Power Source: 230V 60Hz

Octave band pressure level (dB) 0dB=20Pa

PDFY-P48NMU-E

External Static Pressure: 115Pa


Power Source: 230V 60Hz
60Hz
60Hz

8k

Ref.:NC_PDFY-P48NMU-E_WYN B0-4407-3

PDFY-P48NMU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P48NMU-E_WYN B0-4407-2

External Static Pressure: 60Pa


Power Source: 230V 60Hz
65.0

60Hz
60Hz

60.0

PDFY-P48NMU-E

70.0

8k

Ref.:NC_PDFY-P36NMU-E_WYN B0-4406-6

PDFY-P48NMU-E

High
Low

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P36NMU-E_WYN B0-4406-5

External Static Pressure: 50Pa


Power Source: 208V 60Hz
65.0

60Hz
60Hz

60.0

PDFY-P48NMU-E

70.0

8k

Ref.:NC_PDFY-P36NMU-E_WYN B0-4406-3

PDFY-P36NMU-E

65.0

4k

Octave band center frequencies (Hz)

Ref.:NC_PDFY-P36NMU-E_WYN B0-4406-2

External Static Pressure: 60Pa


Power Source: 230V 60Hz
70.0

60Hz
60Hz

60.0

PDFY-P36NMU-E

Octave band pressure level (dB) 0dB=20Pa

PDFY-P-NMU-E

60Hz
60Hz

60.0

Octave band pressure level (dB) 0dB=20Pa

PDFY-P36NMU-E

External Static Pressure: 100Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P36NMU-E

External Static Pressure: 50Pa


Power Source: 208V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PDFY-P36NMU-E

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PDFY-P48NMU-E_WYN B0-4407-6

IU - C - 13

6.
CURVES
5. FAN
FAN CHARACTERISTIC
CHARACTERISTICS
CURVES

DATAU4
U3
DATA

5. FAN CHARACTERISTICS CURVES

PDFY-P06,08,12NMU-E
External static pressure : 30(Pa),0.120[in.WG]
(208V / 60Hz)

PDFY-P06,08,12NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)

Hi
Lo

120
[0.482]

Upper limit

Upper limit

120
[0.482]

80
[0.321]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

100
[0.401]

60
[0.241]

40
[0.161]

20
[0.080]

6
7
8
[212]
[247]
[282]
Airflow rate (m3/min)[cfm]

9
[318]

40
[0.161]

5
[177]

6
7
8
[212]
[247]
[282]
Airflow rate (m3/min)[cfm]

9
[318]

PDFY-P06,08,12NMU-E
External static pressure : 40(Pa),0.161[in.WG]
(230V / 60Hz)

10
[353]

Hi
Lo

140
[0.562]

Upper limit

160
[0.642]

120
[0.482]

Upper limit

120
[0.482]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

60
[0.241]

0
[0] 4
[141]

10
[353]

Hi
Lo

180
[0.723]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

20
[0.080]
0
[0] 4
[141]

5
[177]

6
7
8
[212]
[247]
[282]
Airflow rate (m3/min)[cfm]

9
[318]

PDFY-P06,08,12NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)

0
[0] 4
[141]

10
[353]

6
7
8
[212]
[247]
[282]
Airflow rate (m3/min)[cfm]

9
[318]

10
[353]

Hi
Lo

180
[0.723]

Upper limit

160
[0.642]
140 Upper limit
[0.562]

Static pressure (Pa)[in.WG]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

20
[0.080]
0
[0] 4
[141]

5
[177]

PDFY-P06,08,12NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(230V / 60Hz)

Hi
Lo

160
[0.642]

Static pressure (Pa)[in.WG]

80
[0.321]

20
[0.080]
5
[177]

6
7
8
[212]
[247]
[282]
Airflow rate (m3/min)[cfm]

9
[318]

10
[353]

0
[0] 4
[141]

5
[177]

6
7
8
[212]
[247]
[282]
Airflow rate (m3/min)[cfm]

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

9
[318]

10
[353]

IUPDFY-15
- C - 14

PDFY-P-NMU-E

5
[177]

PDFY-P06,08,12NMU-E
External static pressure : 80(Pa),0.321[in.WG]
(208V / 60Hz)

140
[0.562]

100
[0.401]

20
[0.080]

0
[0] 4
[141]

140
[0.562]

Hi
Lo

140
[0.562]

6. FAN CHARACTERISTIC CURVES


5. FAN CHARACTERISTICS CURVES
PDFY-P15,18NMU-E
External static pressure : 30(Pa),0.120[in.WG]
(208V / 60Hz)

DATA U3

PDFY-P15,18NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)

Hi
Lo

140
[0.562]

DATA U4

Upper limit

Upper limit

140
[0.562]
120
[0.482]

Static pressure (Pa)[in.WG]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

8
[282]

9
[318]

10
11
12
13
[353] [388] [424] [459]
Airflow rate (m3/min) [cfm]

PDFY-P15,18NMU-E
External static pressure : 80(Pa),0.321[in.WG]
(208V / 60Hz)
160
[0.642]

14
[494]

15
[530]

Hi
Lo

40
[0.161]

PDFY-P15,18NMU-E
External static pressure : 40(Pa),0.161[in.WG]
(230V / 60Hz)

Hi
Lo

140
[0.562]

Upper limit

120
[0.482]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

60
[0.241]

Upper limit

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

20
[0.080]
0
[0] 7
8
9
[247] [282] [318]

0
[0] 7
[247]

10
11
12
13
14
15
16
17
[353] [388] [424] [459] [494] [530] [565] [600]
Airflow rate (m3/min) [cfm]

PDFY-P15,18NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)

Hi
Lo

8
[282]

9
[318]

10
11
12
13
[353] [388] [424] [459]
Airflow rate (m3/min) [cfm]

PDFY-P15,18NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(230V / 60Hz)
180
[0.723]

Upper limit

160
[0.642]

140
[0.562]

14
[494]

15
[530]

16
[565]

Hi
Lo

Upper limit

140
[0.562]

Static pressure (Pa)[in.WG]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

20
[0.080]

20
[0.080]

0
[0] 6
7
8
9
10
11
12
13
14
15
16
[212] [247] [282] [318] [353] [388] [424] [459] [494] [530] [565]
Airflow rate (m3/min)[cfm]

PDFY-16

80
[0.321]

0
[0] 6
7
8
9
10
11
12
13
14
15
16
[212] [247] [282] [318] [353] [388] [424] [459] [494] [530] [565]
Airflow rate (m3/min) [cfm]

16
[565]

140
[0.562]

160
[0.642]

100
[0.401]

20
[0.080]

0
[0] 7
[247]

Static pressure (Pa)[in.WG]

PDFY-P-NMU-E

Static pressure (Pa)[in.WG]

120
[0.482]

180
[0.723]

Hi
Lo

160
[0.642]

0
[0] 7
8
9
[247] [282] [318]

PDFY-P-NMU-E (Feb. 2009)


PDFY-P-NMU-E

10
11
12
13
14
15
16
17
[353] [388] [424] [459] [494] [530] [565] [600]
Airflow rate (m3/min)[cfm]

IU - C - 15

6.
CURVES
5. FAN
FAN CHARACTERISTIC
CHARACTERISTICS
CURVES
PDFY-P24NMU-E
External static pressure : 30(Pa),0.120[in.WG]
(208V / 60Hz)
100
[0.401]

DATA U3
DATA
U4
PDFY-P24NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)

Hi
Lo

Upper limit

100
[0.401]

Hi
Lo

Upper limit

80
[0.321]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

80
[0.321]
60
[0.241]

40
[0.161]

20
[0.080]

160
[0.642]

0
[0] 9
10
11
12 13 14
15
16 17
18
19
20 21
[318] [353] [388] [424] [459] [494] [530] [565] [600] [636] [671] [706] [742]
Airflow rate (m3/min) [cfm]

PDFY-P24NMU-E
External static pressure : 40(Pa),0.161[in.WG]
(230V / 60Hz)

Hi
Lo

100
[0.401]

Upper limit

120
[0.482]

Hi
Lo

Upper limit

Static pressure (Pa)[in.WG]

80
[0.321]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

60
[0.241]

40
[0.161]

20
[0.080]

20
[0.080]

0
[0] 9
10
11
12 13 14
15
16 17
18
19
20 21
[318] [353] [388] [424] [459] [494] [530] [565] [600] [636] [671] [706] [742]
Airflow rate (m3/min) [cfm]

0
[0] 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
[282][318][353][388][424][459][494][530][565][600][636][671][706][742][777]
Airflow rate (m3/min) [cfm]

PDFY-P24NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)
120
[0.482]

PDFY-P24NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(230V / 60Hz)

Hi
Lo

160
[0.642]

Upper limit

140
[0.562]

100
[0.401]

Hi
Lo

Upper limit

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

120
[0.482]
80
[0.321]

60
[0.241]

40
[0.161]

20
[0.080]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

0
[0] 9
10
11
12 13 14
15
16 17
18
19
20 21
[318] [353] [388] [424] [459] [494] [530] [565] [600] [636] [671] [706] [742]
Airflow rate (m3/min)[cfm]

0
[0] 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
[282][318][353][388][424][459][494][530][565][600][636][671][706][742][777]
Airflow rate (m3/min)[cfm]

PDFY-P-NMU-E
PDFY-P-NMU-E (Feb. 2009)

IU - C - 16
PDFY-17

PDFY-P-NMU-E

PDFY-P24NMU-E
External static pressure : 80(Pa),0.321[in.WG]
(208V / 60Hz)

Static pressure (Pa)[in.WG]

40
[0.161]

20
[0.080]

0
[0] 9
10
11
12 13 14
15
16 17
18
19
20 21
[318] [353] [388] [424] [459] [494] [530] [565] [600] [636] [671] [706] [742]
Airflow rate (m3/min) [cfm]

140
[0.562]

60
[0.241]

6. FAN
FAN CHARACTERISTICS
CHARACTERISTIC CURVES
5.
CURVES
PDFY-P27NMU-E
External static pressure : 30(Pa),0.120[in.WG]
(208V / 60Hz)
120
[0.482]

Hi
Lo

DATA U3

DATA U4
PDFY-P27NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)
140
[0.562]

Upper limit

80
[0.321]

60
[0.241]

40
[0.161]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

PDFY-P27NMU-E
External static pressure : 80(Pa),0.321[in.WG]
(208V / 60Hz)
160
[0.642]

Hi
Lo

PDFY-P27NMU-E
External static pressure : 40(Pa),0.161[in.WG]
(230V / 60Hz)
120
[0.482]

Upper limit

100
[0.401]

Hi
Lo

Upper limit

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

PDFY-P27NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)

40
[0.161]

Hi
Lo

PDFY-P27NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(230V / 60Hz)
180
[0.723]
160
[0.642]

Upper limit

120
[0.482]

Hi
Lo

Upper limit

140
[0.562]

Static pressure (Pa)[in.WG]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

20
[0.080]

20
[0.080]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min)[cfm]

PDFY-18

60
[0.241]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

140
[0.562]

80
[0.321]

20
[0.080]

20
[0.080]

Static pressure (Pa)[in.WG]

PDFY-P-NMU-E

20
[0.080]

140
[0.562]

Upper limit

120
[0.482]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

100
[0.401]

Hi
Lo

0
[0]10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min)[cfm]

PDFY-P-NMU-E
PDFY-P-NMU-E
(Feb. 2009)

IU - C - 17

6.
5. FAN
FAN CHARACTERISTIC
CHARACTERISTICSCURVES
CURVES
PDFY-P30NMU-E
External static pressure : 30(Pa),0.120[in.WG]
(208V / 60Hz)
120
[0.482]

DATA U4
U3
DATA

PDFY-P30NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)

Hi
Lo

140
[0.562]

Upper limit

80
[0.321]

60
[0.241]

40
[0.161]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

PDFY-P30NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(208V / 60Hz)
160
[0.642]

PDFY-P30NMU-E
External static pressure : 40(Pa),0.161[in.WG]
(230V / 60Hz)

Hi
Lo

120
[0.482]

Upper limit

100
[0.401]

Hi
Lo

Upper limit

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

40
[0.161]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min) [cfm]

PDFY-P30NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)

PDFY-P30NMU-E
External static pressure : 115(Pa),0.462[in.WG]
(230V / 60Hz)

Hi
Lo

180
[0.723]
160
[0.642]

Upper limit

120
[0.482]

Hi
Lo

Upper limit

140
[0.562]

100
[0.401]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

60
[0.241]

20
[0.080]

20
[0.080]

140
[0.562]

80
[0.321]

80
[0.321]
60
[0.241]
40
[0.161]

120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

20
[0.080]

20
[0.080]

0
[0] 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min)[cfm]

0
[0]10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
[353][388][424][459][494] [530][565][600][636][671][706][742][777][812][847]
Airflow rate (m3/min)[cfm]

PDFY-P-NMU-E
PDFY-P-NMU-E (Feb. 2009)

IU - C - 18
PDFY-19

PDFY-P-NMU-E

20
[0.080]

140
[0.562]

Upper limit

120
[0.482]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

100
[0.401]

Hi
Lo

6. FAN
FAN CHARACTERISTICS
CHARACTERISTIC CURVES
5.
CURVES
PDFY-P36NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)
240
[0.964]
220
[0.883]

Hi
Lo

240
[0.964]
220
[0.883]
200
[0.803]

180
[0.723]

180
[0.723]

160
[0.642]

160
[0.642]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

PDFY-P36NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(208V / 60Hz)

Upper limit

200
[0.803]

140
[0.562]
120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
16
[565]

18
[636]

20
22
24
26
[706]
[777]
[847]
[918]
Airflow rate (m3/min) [cfm]

PDFY-P36NMU-E
External static pressure : 130(Pa),0.522[in.WG]
(208V / 60Hz)

28
[989]

140
[0.562]
120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]

Hi
Lo

240
[0.964]
220
[0.883]

Upper limit

200
[0.803]

180
[0.723]

180
[0.723]

160
[0.642]

160
[0.642]

140
[0.562]
120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

18
[636]

20
22
24
26
[706]
[777]
[847]
[918]
Airflow rate (m3/min) [cfm]

28
[989]

30
[1059]

Hi
Lo

Upper limit

140
[0.562]
120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

0
[0] 14
[494]

16
[565]

18
[636]

20
22
24
26
[706]
[777]
[847]
[918]
Airflow rate (m3/min) [cfm]

PDFY-P36NMU-E
External static pressure : 115(Pa),0.462[in.WG]
(230V / 60Hz)

28
[989]

0
[0] 14
[494]

30
[1059]

Hi
Lo

Upper limit

180
[0.723]

Static pressure (Pa)[in.WG]

160
[0.642]
140
[0.562]
120
[0.482]
100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 14
[494]

16
[565]

18
[636]

20
22
24
26
[706]
[777]
[847]
[918]
Airflow rate (m3/min)[cfm]

28
[989]

16
[565]

18
[636]

20
22
24
[706]
[777]
[847]
Airflow rate (m3/min) [cfm]

26
[918]

PDFY-P36NMU-E
External static pressure : 150(Pa),0.602[in.WG]
(230V / 60Hz)

200
[0.803]

PDFY-20

16
[565]

PDFY-P36NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)

200
[0.803]

240
[0.964]
220
[0.883]

Upper limit

0
[0] 14
[494]

30
[1059]

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

240
[0.964]
220
[0.883]

Hi
Lo

20
[0.080]

0
[0] 14
[494]

Static pressure (Pa)[in.WG]

PDFY-P-NMU-E

DATA U3

DATA U4

30
[1059]

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 14
[494]

PDFY-P-NMU-E
PDFY-P-NMU-E (Feb. 2009)

28
[989]

30
[1059]

Hi
Lo

Upper limit

16
[565]

18
[636]

20
22
24
[706]
[777]
[847]
Airflow rate (m3/min)[cfm]

26
[918]

28
[989]

30
[1059]

IU - C - 19

5.FAN
FANCHARACTERISTIC
CHARACTERISTICS
CURVES
6.
CURVES

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

PDFY-P48NMU-E
External static pressure : 100(Pa),0.401[in.WG]
(208V / 60Hz)

Hi
Lo

Upper limit

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

PDFY-P48NMU-E
External static pressure : 50(Pa),0.200[in.WG]
(208V / 60Hz)

DATAU4
U3
DATA

Hi
Lo

Upper limit

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 16
18
20
22
24
26
28
30
32
34
36
38
[565] [636] [706] [777] [847] [918] [989] [1059][1130][1201] [1271] [1342]
Airflow rate (m3/min) [cfm]

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

Hi
Lo

Upper limit

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 16
18
20
22
24
26
28
30
32
34
36
38
[565] [636] [706] [777] [847] [918] [989] [1059][1130][1201] [1271] [1342]
Airflow rate (m3/min)[cfm]

Hi
Lo

Upper limit

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 16 18
20 22 24
26 28
30
32
34 36
38 40
[565] [636] [706] [777] [847] [918] [989] [1059] [1130] [1201] [1271] [1342] [1413]
Airflow rate (m3/min) [cfm]

PDFY-P48NMU-E
External static pressure : 150(Pa),0.602[in.WG]
(230V / 60Hz)

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

PDFY-P48NMU-E
External static pressure : 115(Pa),0.462[in.WG]
(230V / 60Hz)

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

PDFY-P48NMU-E
External static pressure : 60(Pa),0.241[in.WG]
(230V / 60Hz)

Static pressure (Pa)[in.WG]

Static pressure (Pa)[in.WG]

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

Upper limit

0
[0] 16
18
20
22
24
26
28
30
32
34
36
38
[565] [636] [706] [777] [847] [918] [989] [1059][1130][1201] [1271] [1342]
Airflow rate (m3/min) [cfm]

0
[0] 16
18
20
22
24
26
28
30
32
34
36
38
[565] [636] [706] [777] [847] [918] [989] [1059][1130][1201] [1271] [1342]
Airflow rate (m3/min) [cfm]

PDFY-P48NMU-E
External static pressure : 130(Pa),0.522[in.WG]
(208V / 60Hz)

Hi
Lo

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

Hi
Lo

Upper limit

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]
0
[0] 16
34
36
38
18
20
22
24
26
28
30
32
[565] [636] [706] [777] [847] [918] [989] [1059][1130][1201] [1271] [1342]
Airflow rate (m3/min)[cfm]

PDFY-P-NMU-E
PDFY-P-NMU-E (Feb. 2009)

IU - C - 20
PDFY-21

PDFY-P-NMU-E

100
[0.401]
80
[0.321]
60
[0.241]
40
[0.161]
20
[0.080]

260
[1.044]
240
[0.964]
220
[0.883]
200
[0.803]
180
[0.723]
160
[0.642]
140
[0.562]
120
[0.482]

7. Optional Parts
7. OPTIONAL PARTS

DATA
DATA U4
U3

7-1.
Optionalparts
Parts
Upthe
forIndoor
the Indoor
Unit
7-1. Optional
lineLine
up for
unit
PDFY-P06,08,12NMU-E
PDFY-P15,18NMU-E
PDFY-P24,27,30NMU-E
PDFY-P36,48NMU-E

Round duct flange

Drain pump kit

External heater adaptor

PAC-KD32EDF-F
PAC-KD50EDF-F
PAC-KD80EDF-F
PAC-KD125EDF-F

PAC-KD02DM-FA
PAC-KD02DM-FA
PAC-KD02DM-FA
PAC-KD02DM-FA

PAC-YU24HT-F
PAC-YU24HT-F
PAC-YU24HT-F
PAC-YU24HT-F

PDFY-P-NMU-E
Round
flange
Round duct
duct flange
PAC-KD-EDF-F

PDFY-P-NMU-E

Drain pump kit


PAC-KD02DM-FA

7-2. Round
flange
PAC-KD-EDF-F
for PDFY-P-NMU-E
7-2.
Roundduct
Duct
Flange
PAC-KD-EDF-F
for PDFY-P-NMU-E
Round duct flange PAC-KE-EDF-F makes air ducting and distributing easier.
Material: Polystyrene

Item

Screw

Quantity

Round duct flange

Installation manual

Shape
2 - 8" Round
<for PDFY-P06, 08, 12, 15, 18NMU-E>
Refer to the Installation Manual (WT02840X02) for detailed installation information.

3 - 8" Round
<for PDFY-P24, 27, 30NMU-E>

4 - 8" Round
<for PDFY-P36, 48NMU-E>

Screws
Model
Screw Quantity
PDFY-P-NMU-E
06, 08, 12

15, 18

24, 27, 30

36, 48

10

PDFY-22

PDFY-P-NMU-E
(Feb. 2009)
PDFY-P-NMU-E

IU - C - 49

7. Optional Parts

DATA U4

7-3. Drain Pump Kit PAC-KD02DM-FA


If drain water cannot flow out from the indoor unit by gravity and gradient, a Drain-pump-kit for draining is needed.
Item

1. Drain Pump Assy.

2. Pump Cover Assy.

4. Band

3. Rubber Plug

Shape

Quantity

Item

1
6. Screw 4X10

5. PTT Screw 4X10

1
7. Connector

(Light Brown)

Shape
Quantity

*8. Wiring Assy. A1

Item

*9. Wiring Assy. A2

*10. Wiring Assy. B

Red
Red

Red

To L1

To L1

Green

PDFY-P-NMU-E

Yellow

Blue

Shape
To

White
PDFY-P08, P15, P24, P30NMU-E
Quantity
Item

1
*11. Fuse Holder

PDFY-P36, P48NMU-E
1

*13. PTT Screw 3.5X10

250V 5A

Shape

Quantity

*12. Fuse

*8-13; PDFY-P08, P15, P24, P30, P36, P48NMU-E type only.


Refer to the Installation Manual for detailed installation information.

PDFY-P-NMU-E (Feb. 2009)

PDFY-23

7. Optional Parts

DATA U4

7-4. External Heater Adapter PAC-YU24HT


External heater adaptor PAC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Relay circuit

Electric Heater
power source

Remote control Board

Indoor unit
control board

Adapter

White

Red

Red

PDFY-P-NMU-E

Electric
Heater

Dip switch
PUHY,PURY-P-TGMU type
SW5-2 "ON"
PUHY,PURY-P-YHMU type
SW5-10 "ON"

CN22
Green

Red

Yellow

CN24

Outdoor unit
control board

PUMY series
SW4-4 "ON"

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below Operation coil


Rated voltage : 12VDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit

88H

FS1

H1

88H

FS2
FS1

H2

R
1-phase power
supply

208V, 230V/60Hz

Wiring diagram

FS1, 2 ----- Thermal fuse

FS2

H1, H2 ----- Heater


26H

88H
Control board

88H --------- Electromagnetic contactor


CN24

Item
Quantity

External output cable


2

Fan speed setting cable


with resistance
2

Shape

Refer to the Installation Manual (WT04645X02) wiring and installation details.

PDFY-24

26H --------- Overheat protection


thermostat

PDFY-P-NMU-E (Feb. 2009)

Ceiling-recessed Cassette (One-way Airflow)

DATA U4

PMFY-P-NBMU-E
1. SPECIFICATIONS.................................................................................................................................................. PMFY-3
2. EXTERNAL DIMENSIONS..................................................................................................................................... PMFY-4
3. Center of Gravity.......................................................................................................................................... PMFY-5
4. ELECTRICAL WIRING DIAGRAMS....................................................................................................................... PMFY-6
5. SOUND PRESSURE LEVELS............................................................................................................................... PMFY-7
5-1. Sound Pressure Levels................................................................................................................................ PMFY-7
5-2. NC Curves.................................................................................................................................................... PMFY-7
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS....................................................................................................... PMFY-8
6-1. Temperature Distributions............................................................................................................................ PMFY-8
6-2. Airflow Distributions...................................................................................................................................... PMFY-8

PMFY-P-NBMU-E

PMFY-P-NBMU-E (Feb. 2009)

PMFY-1

Ceiling-recessed
Cassette
Cassette ceiling (1-way
flow type)(One-way Airflow)

DATA
DATAU4
U3

I.Cassette ceiling (1-way flow type)

PMFY-P-NBMU-E

PMFY-P-NBMU-E

PMFY-P-NBMU-E

Compact and lightweight-perfect for limited ceiling space applications.

The PMFY models are one-way ceiling-recessed cassette units


perfect for shallow ceiling spaces.

Drain pipe
max.
15-13/16

max.
23-5/8

It is designed especially for use in areas like hotel rooms that


cannot support ductwork or lack sufficient space to allow
for wall-mounted units.

PMFY-NBMU

9-1/16

7-25/32

Unit body
body size
size has
has been
been standardized
standardized for
for all
all models
models at
at 33-5/8"
33-5/8" for
for
Unit

MULTI
easier installation. This profile is the smallest of all CITY MULTI
ceiling models
models with
with a
a depth
depth of
of only
only 9-1/16-ideal
9-1/16"-ideal for
for tight
tight location.
location.
ceiling

Cassette ceiling

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

Ceiling
unit: in.

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PMFY-P-NBMU-E

*1, *2
*2 are
are referable
referred to
theSpecification
Specification
sheet.
* Nominal conditions *1,
atinthe
sheet.

PMFY-2

PMFY-P-NBMU-E (Feb.
2009)
PMFY-P-NBMU-E

IU - D - 2

1. Specifications
Model
Power source
Cooling capacity *1
(Nominal)
Power input
Current input
Heating capacity *2
(Nominal)
Power input
Current input
External finish
External dimension H x W x D
Net weight

PMFY-P06NBMU-E

BTU / h
kW
kW
A
BTU / h
kW
kW
A
in.
mm
lbs (kg)

Indoor:
Outdoor:
Pipe length:

Direct-driven
230-254-283-307
6.5-7.2-8.0-8.7
108-120-133-145
27-30-33-35 (208-230V)
-

R410A CITY MULTI

258-283-304-328
258-283-304-328
7.3-8.0-8.6-9.3
7.3-8.0-8.6-9.3
122-133-143-155
122-133-143-155
32-34-36-37 (208-230V)
32-34-36-37 (208-230V)
PS foam, Polyethylene foam
PP honeycomb
Fuse
LEV
R410A CITY MULTI
R410A,R22 CITY MULTI

1/4 (6.35) Flare


-

1/4 (6.35) Flare


-

1/4 (6.35) Flare


1/4 (6.35) Flare

1/2 (12.7) Flare


O.D. 1 (26)
23-5/8 (600)

1/2 (12.7) Flare


O.D. 1 (26)
23-5/8 (600)

1/2 (12.7) Flare


1/2 (12.7) Flare
O.D. 1 (26)
23-5/8 (600)

272-307-343-378
7.7-8.7-9.7-10.7
128-145-162-178
33-35-37-39 (208-230V)
-

R410A,R22 CITY MULTI


1/4 (6.35) Flare
1/4 (6.35) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
O.D. 1 (26)
23-5/8 (600)

BH01C848
BH79C630
Installation Manual,Installation Book

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.
Installation

Note:

PMFY-P08NBMU-E
PMFY-P12NBMU-E
PMFY-P15NBMU-E
1-phase 208-230 V 60Hz
6,000
8,000
12,000
15,000
1.8
2.3
3.5
4.4
0.04
0.04
0.04
0.05
0.20
0.20
0.21
0.26
6,700
9,000
13,500
17,000
2.0
2.6
4.0
5.0
0.04
0.04
0.04
0.05
0.20
0.20
0.21
0.26
9-1/16 x 31-31/32 x 15-9/16 9-1/16 x 31-31/32 x 15-9/16 9-1/16 x 31-31/32 x 15-9/16 9-1/16 x 31-31/32 x 15-9/16
230 x 812 x 395
230 x 812 x 395
230 x 812 x 395
230 x 812 x 395
31 (14)
31 (14)
31 (14)
31 (14)
PMP-16BMUW
PMP-16BMUW
PMP-16BMUW
PMP-16BMUW
6.4Y 8.9/0.4
1-3/16 x 39-3/8 x 18-17/32 1-3/16 x 39-3/8 x 18-17/32 1-3/16 x 39-3/8 x 18-17/32 1-3/16 x 39-3/8 x 18-17/32
30 x 1,000 x 470
30 x 1,000 x 470
30 x 1,000 x 470
30 x 1,000 x 470
7(3)
7(3)
7(3)
7(3)
Cross fin
Line flow fan x 1
Line flow fan x 1
Line flow fan x 1
Line flow fan x 1
0.000 (208V)
0.000 (208V)
0.000 (208V)
0.000 (208V)
0
0
0
0
0.000 (230V)
0.000 (230V)
0.000 (230V)
0.000 (230V)
0
0
0
0
DC Brushless
0.028
0.028
0.028
0.028

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to
the Installation Manual.
*1 Nominal cooling conditions
80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)
95degF D.B. (35degC D.B.)
25 ft. (7.6 m)

*2 Nominal heating conditions


70degF D.B. (21.1degC D.B.)
47degF D.B. / 43degF W.B.

Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)

*Above specification data is

Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.

PMFY-P-NBMU-E (Feb. 2009)

subject to rounding variation.

PMFY-3

PMFY-P-NBMU-E

Model
External finish
Decoration
Dimension
in.
panel
HxWxD
mm
Net Weight
lbs (kg)
Heat exchanger
Type x Quantity
in.WG
Pa
External
static pressure in.WG
Pa
Motor type
FAN
Motor output
kW
Driving
mechanism
cfm
Airflow rate
(Low-Mid1m3 / min
Mid2-High)
L/s
dB <A>
Sound pressure level
(Low-Mid1-Mid2-High)
dB <A>
(measured in anechoic room) dB <A>
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Liquid (R410A)
(R22)
in. (mm)
Diameter of
refrigerant
pipe (O.D.)
Gas (R410A)
in. (mm)
(R22)
Field drain pipe size
in. (mm)
Drain lift mechanism
in. (mm)
External
Drawing
Wiring
Refrigerant cycle
Standard
Document
attachment
Accessory

Remark

DATA U4

6-15/16(176)

3-3/8(96)

ceiling
drain pan
panel
same line

Left side

outer side of grille

18-1/2(470)

drain pan

31-15/16(812)
29-7/8(759)

Air outlet(lower)

Lower view

7-7/8(200)

7-7/8(200)

13/16(20)
2-15/18(74.5)
1-1/32(26)

outer line of grille

1-3/16(30)

Terminal block for


remote-controller

electrical box

center of unit

2-1/16(53)

Panel(grille):PMP-40BM

23-5/8(600)

39-3/8(1000) outer side of grille

Front

2-3/16(56)

1-11/16(43)

1-13/18(46)

1-25/32(45)

13/16(20)
13/32(10) 7-13/16(198)

15-9/16(395)
11-7/8(302)
10(254)
Drainage pipe
5-9/16(141)

Refrigerant
pipe(liquid)

ceiling panel

3-3/8(96)

Refrigerant pipe(gas)

16-15/16(430)
ceiling opening
13-3/8(340) suspension bolt pitch

13/16(20)
1-25/32(45)

13/16(20) 9-1/16(230)

11/16(17.5) 11/16(17.5)

39-3/8(1000) outer side of grille


37-13-16(960) ceiling opening
31-15/18(811)suspension bolt pitch
29-7/8(759)
13/16(20)
13/16(20)

outer side of grille


18-1/2(470)

1-9/16(40)
2-3/8(60)

9-3/8(247)
2-11/16(69)

13/16(20)
2-15/18(74.5)
1-1/32(26)

Panel(grille):PMP-40BM

suspension bolt(M10 or W 3/8)

Fresh air intake hole

9-13/16(250) 11-3/8(288.5)

Installation space required around indoor unit

Terminal block for transmission

Right side

I.D. 1-1/32" (26)

Detail drawing of ventilation air intake hole

Knock out

Pipe cover
Liquid pipe
Gas pipe

Terminal block for power supply

Drainage piping

Refrigerant
piping

4-5/16 (110)

Top

9-1/16(230)
9-1/2
(235) or more

PMFY-P-NBMU-E (Feb.
2009)
PMFY-P-NBMU-E

mounting plate

4-5/16
(110)

PMFY-4
4-1/4
(108)

PMFY-P-NBMU-E

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATAU4
U3

2. EXTERNAL DIMENSIONS

PMFY-P06,08,12,15NBMU-E
Drw. : IU-BH01C848
Unit : in(mm)

IU - D - 4

3. Center of Gravity

DATA U4

PMFY-P06,08,12,15NBMU-E

Ref.: PMFY_NBMU_COG_USDB_ALL

Pipe side
A

A: Center of gravity

(mm)[in]
Model name
PMFY-P06NBMU-E
PMFY-P08NBMU-E
PMFY-P12NBMU-E
PMFY-P15NBMU-E

X
165 [6-1/2]
165 [6-1/2]
165 [6-1/2]
165 [6-1/2]

Y
390 [15-3/8]
390 [15-3/8]
390 [15-3/8]
390 [15-3/8]

Z
130 [5-1/8]
130 [5-1/8]
130 [5-1/8]
130 [5-1/8]

PMFY-P-NBMU-E

PMFY-P-NBMU-E (Feb. 2009)

PMFY-5

TB15

TO NEXT INDOOR UNIT

PULL BOX

FUSE(15A)

BREAKER
(15A)

POWER SUPPLY
~ / N 208-230V 60Hz

DC24-30V

L1
L2
G

TB2

MF

GRN / YLW

RED
BLU

S(SHIELD) TB5
TO OUTDOOR UNIT
M2
BC CONTROLLER
M1
ME REMOTE CONTROLLER

TO MA-REMOTE
CONTROLLER
DC8.7-13V

BLU
BLU

ORN

ORN

(BLU)
(M-NET)
CN2M

LED2

CN3A
(BLU)

LED1

6
5
4 FAN
3 (WHT)
2
1

1
2

1
2
3

I.B
(WHT)
DRAIN
CN31

3 2 1

2 1

(BLK)
GAS
CN29

TH23

CND
(RED)

FUSE
250V
6A

2 1

LEV

(WHT)
LEV
CN60

MV
1 2 3 4 5

(GRN)
VANE
CN6V

X1

DP

1 2 3

X1

6 5 4 3 2 1

(GRN)
REMOTE
INDICATION
CN52

1 5

(WHT)
CENTRALLY
CONTROL
CN51

6 5 4 3 2 1

BLU
BRN
ORN
YLW
RED
WHT

3 2 1

2 1

TH21

(WHT) (RED)
LIQUID INTAKE
CN21 CN20

TH22

Note
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5.
(Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
: terminal block,
:connecter.
6.The setting of the SW2, SW3 dip switches differs in the capacity for the detail, refer to the fig :
7.Please set the switch SW5 according to the power supply voltage.
DS

Name

A.B
Address board
SW1 Switch
Mode selection
SW5
Voltage selection
SW11
Address setting 1st digit
SW12
Address setting 2nd digit
SW14
Connection No.

TH23

TH22

Symbol
Thermistor
TH21

BRN
RED
ORN
YLW
GRN

Name
Drain pump
Aux.relay
Transformer
Power supply (I.B)
Power supply (I.B)
Fan motor (with inner thermo)
Vane motor
Drain pump kit
Drain sensor
Linear expansion valve
Terminal
Power supply
Transmission
block
MA-Remote Controller

(WHT)
CNP

CN25

2 1

LED2

2 1
CN27

(WHT)
REMOTE
SWITCH
CN32

4
3
2
1
(RED)
ADDRESS
CN42

ON
OFF

P15

ON
OFF

P12

(RED)
ADDRESS
CN81

ON
OFF

P08

8
7
6
5
4
3
2
1

ON
OFF

P06

Models

Power supply for


MA-Remote controller

LED1 Main power supply

LED on indoor board for service


Mark
Meaning

ON
OFF
SW4
SW3
SW2

1 2 34 5
1 2 3 4 5 6 1 2 3 4 5 6 7 8 910
ON
OFF

Symbol
X1
T
LED1
LED2
MF
MV
DP
DS
LEV
TB2
TB5
TB15

(RED)
ADDRESS
CN43

(RED)
ADDRESS
CN82

1 2 3 4 5 6 7 8 910

1 2 3 4 5 6 7 8 910

1 2 3 4 5 6 7 8 910

1 2 3 4 5 6 7 8 910

SW3

8 7 6 5 4 3 2 1

ON
OFF

ON
OFF

4 3 2 1

A.B

123456

123456

123456

ON
OFF

ON
OFF

Function

123456

SW2

SW5

Name
Indoor controller board
Connector
Humidifier
Damper
Remote switch
Centrally control
Remote Indication
Switch
Capacity code
Mode selection
Model selection
Varistor
Fuse (6A / 250V)

SW1

Symbol
I.B
CN25
CN27
CN32
CN51
CN52
SW2
SW3
SW4
ZNR
FUSE

1 2 3 4 5 6 7 8 910

[Legend]

230V
208V

SWC SW14
SW12 SW11

CONNECTION
No.

PMFY-P-NBMU-E (Feb.
2009)
PMFY-P-NBMU-E

1ST
DIGIT

PMFY-6
ON
OFF

PMFY-P06,08,12,15NBMU-E

3RD
2ND
DIGIT DIGIT

PMFY-P-NBMU-E

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATAU4
U3

3. ELECTRICAL WIRING DIAGRAMS

Drw. : IU-BH79C630

IU - D - 5

5.
4. Sound
SOUND Pressure
PRESSURE Levels
LEVELS

DATA
DATAU4
U3

4-1. Sound
Levels
5-1.
SoundPressure
Pressure
Levels
4. SOUND LEVELS

Cassette ceiling series


UNIT

Operating sound pressure levels


(Low-Medium2-Medium1-High)

CEILING

Model

4-7/ 8 ft

(1.5m)

Unit : dB(A)

Sound pressure levels (A weighted)

PMFY-P06NBMU-E

27-30-33-35

PMFY-P08NBMU-E

32-34-36-37

PMFY-P12NBMU-E

32-34-36-37

PMFY-P15NBMU-E

33-35-37-39

MICROPHONE
Measurement location

4-2. NC
5-2.
NCcurves
Curves
PMFY-P06NBMU-E

PMFY-P08,12NBMU-E

PMFY-P15NBMU-E

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

High
Low
Middle1
Middle2

65.0
60.0

70.0

60Hz
60Hz
60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

High
Low
Middle1
Middle2

65.0
60.0

70.0

60Hz
60Hz
60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>


Ref.:NC_PMFY-P06NBMU-E

15.0
10.0

High
Low
Middle1
Middle2

65.0
60.0

60Hz
60Hz
60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

Octave band center frequencies <Hz>


Ref.:NC_PMFY-P08,12NBMU-E

PMFY-P-NBMU-E (Feb. 2009)


PMFY-P-NBMU-E

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>


Ref.:NC_PMFY-P15NBMU-E

IUPMFY-7
-D-6

PMFY-P-NBMU-E

70.0

6. Temperature/Airflow Distributions
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

DATA
DATAU4
U3

6-1. Temperature
Temperature distributions
6-1.
Distributions
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

<Cooling mode>

<Heating mode>

2.7

2.7

(8' 10-5/16")
19(66)

2
(6' 6-3/4")

Height <m(ft)>

Height <m(ft)>

(8' 10-5/16")

21(70)
23(73)

25(77)

1
(3' 3-3/8")

23(73)
25(77)

2
(6' 6-3/4")

33
(91)
24(75)

1
(3' 3-3/8")

27
(81)

30
(86)

24(75)
21(70)

25(77)

5
(16' 4-7/8")

4
(13' 1-1/2")

3
(9' 10-1/8")

2
(6' 6-3/4")

Floor distance <m(ft)>

6-2. Airflow
Airflow distributions
6-2.
Distributions

1
(3' 3-3/8")

5
(16' 4-7/8")

4
(13' 1-1/2")

3
(9' 10-1/8")

2
(6' 6-3/4")

Floor distance <m(ft)>

Ref.:TD_PMFY-P-NBMU-E_C30

<Fan mode>
m/s(ft/s)

m/s(ft/s)
2.7
(8' 10-5/16")

2
(6' 6-3/4")

3.0(9' 10-1/8")
2.0(6' 6-3/4")

1.0(3' 3-3/8")

1
(3' 3-3/8")

Height <m(ft)>

Height <m(ft)>

2.7
(8' 10-5/16")

PMFY-P-NBMU-E

Ref.:TD_PMFY-P-NBMU-E_H70

<Fan mode>

0.5(1' 7-11/16")

3.0(9' 10-1/8")

2
(6' 6-3/4")

2.0(6' 6-3/4")

1
(3' 3-3/8")
0.5(1' 7-11/16")

5
(16' 4-7/8")

4
(13' 1-1/2")

3
(9' 10-1/8")

2
(6' 6-3/4")

Floor distance <m(ft)>

1
(3' 3-3/8")

Ref.:AD_PMFY-P-NBMU-E_30

PMFY-8

1
(3' 3-3/8")

PMFY-P-NBMU-E (Feb.
2009)
PMFY-P-NBMU-E

5
(16' 4-7/8")

4
(13' 1-1/2")

3
(9' 10-1/8")

1.0
(3' 3-3/8")
0.5(1' 7-11/16")

2
(6' 6-3/4")

Floor distance <m(ft)>

1
(3' 3-3/8")

Ref.:AD_PMFY-P-NBMU-E_70

IU - D - 25

Ceiling-recessed Cassette (Four-way Airflow)

DATA U4

PLFY-P-NCMU-E/PLFY-P-NBMU-E
1. SPECIFICATIONS................................................................................................................................................... PLFY-3
2. EXTERNAL DIMENSIONS...................................................................................................................................... PLFY-6
3. Center of Gravity........................................................................................................................................... PLFY-8
4. ELECTRICAL WIRING DIAGRAMS........................................................................................................................ PLFY-9
5 SOUND Pressure LEVELS.............................................................................................................................. PLFY-11
5-1. Sound Pressure Levels............................................................................................................................... PLFY-11
5-2. NC Curves................................................................................................................................................... PLFY-11
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS...................................................................................................... PLFY-12
6-1. Temperature Distributions........................................................................................................................... PLFY-12
6-2. Airflow Distributions..................................................................................................................................... PLFY-13
6-3. Branch Duct Capacities............................................................................................................................... PLFY-14
7. Ventilation AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS.......................................... PLFY-20
7-1. PLFY-P-NCMU-E......................................................................................................................................... PLFY-20
7-2. PLFY-P-NBMU-E with Multi-function Casement and Filters........................................................................ PLFY-20

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-1

PLFY-P-NCMU-E
PLFY-P-NBMU-E

8. OPTIONAL PARTS................................................................................................................................................ PLFY-22


8-1. Air Outlet Shutter Plate PAC-SH51SP-E for PLFY-P-NBMU-E................................................................... PLFY-22
8-2. High Efficiency Filter Element PAC-SH59KF-E for PLFY-P-NBMU-E......................................................... PLFY-23
8-3. Multi-function Casement PAC-SH53TM-E for PLFY-P-NBMU-E................................................................. PLFY-23
8-4. i-see Sensor Corner Panel PAC-SA1ME-E for PLFY-P-NBMU-E............................................................... PLFY-24
8-5. Wireless Signal Receiver PAR-SF9FA-E for for PLFY-P-NBMU-E ............................................................. PLFY-24
8-6. External Heater Adapter PAC-YU24HT....................................................................................................... PLFY-25

Ceiling-recessed Cassette (Four-way Airflow)

DATA U4

PLFY-P-NCMU-E
PLFY-P-NBMU-E

PLFY-P-NBMU-E

PLFY-P-NCMU-E

various airflow pattern to meet your needs, strong airflow power, suitable for ceiling of max.13 -9" height

1
Uniformly distribute the air onto the louver.
2 3 Avoid airflow rising up.
2 3 Avoid dust attachment.

(on PLFY-P-NBMU-E)

PLFY-P-NCMU-E
PLFY-P-NBMU-E

4-, 3-, or
2-way
outlet
selection

Outside

Inside

Grille

Fixed airflow
direction per
vane

Vane

Motor
for the
vane

72 airflow patterns
drain water lifted to 33 (PLFY-P-NBMU-E) or 19-7/16 (PLFY-P-NCMU-E)
Allowing long piping and versatility.

Precise airflow pattern on PLFY-P-NBMU-E


Example (Convenient chain store)
Airflow doesn't disturb the cooled air in show-case
helps energy saving.

850mm PLFY-P-NBMU-E
(33-1/2in.)
Fixed
Fixed

Fixed

Top or bottom
airflow setting via
remote controller

Fixed

The PLFY not only brings outside air into your space, but the PLFY-P-NBMU-E
can also branch over to air-condition an adjacent room.

Refrigerated
showcase not
affected by air
conditioning

Cassette ceiling

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PLFY-P-NCMU-E
PLFY-P-NBMU-E

* Nominal conditions *1, *2 are referred to in the Specification sheet.

PLFY-2

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

1. Specifications

DATA U4

Model
Power source
Cooling capacity *1
(Nominal)

PLFY-P08NCMU-E
BTU / h
kW
kW
A
BTU / h
kW
kW
A

8,000
2.3
0.05
0.23
9,000
2.6
0.05
0.23

in.
mm
lbs (kg)

8-3/16 x 22-7/16 x 22-7/16


208 x 570 x 570
34 (15.5)
SLP-15AAUW

in.
mm
lbs (kg)

25/32 x 25-19/32 x 25-19/32


20 x 650 x 650
7(3)

External
static pressure

in.WG
Pa
in.WG
Pa

Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0

Motor type
Motor output
Driving mechanism

kW

Airflow rate
(Low-Mid-High)

cfm
m3 / min
L/s

280-320-350
8.0-9.0-10.0
133-150-167

PLFY-P12NCMU-E
1-phase 208-230 V 60Hz
12,000
3.5
0.06
0.28
13,500
4.0
0.06
0.28
Galvanized Steel Sheet
8-3/16 x 22-7/16 x 22-7/16
208 x 570 x 570
37 (17)
SLP-15AAUW
Munsell No. 6.4Y 8.9/0.4
25/32 x 25-19/32 x 25-19/32
20 x 650 x 650
7(3)
Cross fin
Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0
1-phase induction motor
0.020
Direct-driven
320-350-390
9.0-10.0-11.0
150-167-183

dB <A>

29-32-38 (208-230V)

30-34-39 (208-230V)

Power input
Current input
Heating capacity *2
(Nominal)
Power input
Current input
External finish
External dimension H x W x D
Net weight
Model
External finish
Dimension
HxWxD
Net Weight

Decoration
panel

Heat exchanger
Type x Quantity

Fan

Remark

in. (mm)
in. (mm)
in. (mm)
in. (mm)

Note:
Indoor:
Outdoor:
Pipe length:

8-3/16 x 22-7/16 x 22-7/16


208 x 570 x 570
37 (17)
SLP-15AAUW
25/32 x 25-19/32 x 25-19/32
20 x 650 x 650
7(3)
Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0
0.020
320-350-390
9.0-10.0-11.0
150-167-183
31-35-40(208-230V)

Polyethylene foam
Polypropylene honeycomb fabric
Fuse
LEV
R410A,R22 CITY MULTI
1/4 (6.35) Flare
1/4 (6.35) Flare
1/4 (6.35) Flare
1/4 (6.35) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
O.D. 1-1/4(32)
O.D. 1-1/4(32)
19-11/16 (500)
19-11/16 (500)
RG01N654
RG79V389
Installation Manual,Installation Book
Drain hose<1-1/4in.(32mm)>
SLP-15AAUW
SLP-15AAUW
*PLFY-P-NCMU-E should used together with SLP-15AAUW.

1/4 (6.35) Flare


3/8 (9.52) Flare
1/2 (12.7) Flare
5/8 (15.88) Flare
O.D. 1-1/4(32)
19-11/16 (500)

SLP-15AAUW

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local
codes.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and
other items shall be referred to the Installation Manual.

Installation

15,000
4.4
0.06
0.28
17,000
5.0
0.06
0.28


*1 Nominal cooling conditions
*2 Nominal heating conditions
80degF D.B. / 67degF W.B.
70degF D.B. (21.1degC D.B.)
(26.7degC D.B. / 19.4degC W.B.)
95degF D.B. (35degC D.B.)

47degF D.B. / 43degF W.B.


(8.3degC D.B. / 6.1degC W.B.)

25 ft. (7.6 m)

25 ft. (7.6 m)

Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.

Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm = m3/min x 35.31
lbs = kg / 0.4536
*Above specification data is subject to
rounding variation.

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-3

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Sound pressure level (Low-Mid-High)


(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Liquid (R410A)
Diameter of
(R22)
refrigerant pipe
Gas
(R410A)
(O.D.)
(R22)
Field drain pipe size
Drain Lift Mechanism
External
Drawing
Wiring
Refrigerant cycle
Document
Standard attachment
Accessory
Optional parts
Decoration panel

0.015

PLFY-P15NCMU-E

1. Specifications

DATA U4

Model
Power source
Cooling capacity *1
(Nominal)

PLFY-P12NBMU-E
BTU / h
kW
kW
A
BTU / h
kW
kW
A

12,000
3.5
0.03
0.22
13,500
4.0
0.02
0.14

in.
mm
lbs (kg)

10-3/16 x 33-3/32 x 33-3/32


258 x 840 x 840
49 (22)
PLP-40BAU

in.
mm
lbs (kg)

1-3/8 x 37-13/32 x 37-13/32


35 x 950 x 950
13 (6)

External static pressure

in.WG
Pa
in.WG
Pa

Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0

Motor type
Motor output
Driving mechanism

kW

Airflow rate (Low-Mid2Mid1-High)

cfm
m3 / min
L/s

388 - 424 - 459 - 494


11.0 - 12.0 - 13.0 - 14.0
183 - 200 - 217 - 233

dB <A>

27 - 28 - 29 - 31(208-230V)

Power input
Current input
Heating capacity *2
(Nominal)
Power input
Current input
External finish
External dimension H x W x D
Net weight
Decoration

panel

Model
External finish
Dimension
HxWxD
Net Weight

Heat exchanger
Type x Quantity

PLFY-P-NCMU-E
PLFY-P-NBMU-E

FAN

Sound pressure level (Low-Mid2-Mid1-High)


(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device

0.050

PLFY-P15NBMU-E
1-phase 208-230 V 60Hz
15,000
4.4
0.04
0.29
17,000
5.0
0.03
0.22
Galvanized steel sheet
10-3/16 x 33-3/32 x 33-3/32
258 x 840 x 840
49 (22)
PLP-40BAU
Munsell No. (6.4Y 8.9/0.4)
1-3/8 x 37-13/32 x 37-13/32
35 x 950 x 950
13 (6)
Cross fin
Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0
DC motor
0.050
Direct-driven
424 - 459 - 494 - 565
12.0 - 13.0 - 14.0 - 16.0
200 - 217 - 233 - 267
27 - 28 - 30 - 31(208-230V)

in. (mm)

Gas (R410A)
(R22)

in. (mm)

Indoor:
Outdoor:
Pipe length:

1/4 (6.35) Flare


1/4 (6.35) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
O.D. 1-1/4(32)
33-1/2 (851)

Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0
0.050
494 - 530 - 565 - 636
14.0 - 15.0 - 16.0 - 18.0
233 - 250 - 267 - 300
28 - 29 - 30- 32(208-230V)

1/4 (6.35) Flare


1/4 (6.35) Flare
1/2 (12.7) Flare
1/2 (12.7) Flare
O.D. 1-1/4(32)
33-1/2 (851)

1/4 (6.35) Flare


3/8 (9.52) Flare
1/2 (12.7) Flare
5/8 (15.88) Flare
O.D. 1-1/4(32)
33-1/2 (851)

Installation Manual, Instruction Book


PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PAC-SA1ME-E
PAC-SH65OF-E
PAR-SA9FA-E

PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PAC-SA1ME-E
PAC-SH65OF-E
PAR-SA9FA-E

PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PAC-SA1ME-E
PAC-SH65OF-E
PAR-SA9FA-E

Details on foundation work, duct work, insulation work, electrical wiring, power source switch,
and other items shall be referred to the Installation Manual.

*1 Nominal cooling conditions


80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B. (21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B. / 43degF W.B.


(8.3degC D.B. / 6.1degC W.B.)

25 ft. (7.6 m)

25 ft. (7.6 m)

Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.

PLFY-4

1-3/8 x 37-13/32 x 37-13/32


35 x 950 x 950
13 (6)

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local
codes.

Installation
Note:

10-3/16 x 33-3/32 x 33-3/32


258 x 840 x 840
51 (23)
PLP-40BAU

R410A,R22 CITY MULTI

Liquid (R410A)
(R22)

Field drain pipe size


in. (mm)
Drain lift mechanism
in. (mm)
Standard
Document
attachment
Accessory
Air outlet shutter plate
High efficiency filter element (MERV 10)
Multi-function casement
Optional parts
i-see sensor corner panel
Flange for fresh air intake
Wireless signal receiver

Remark

18,000
5.3
0.05
0.36
20,000
5.9
0.04
0.29

PS
PP honeycomb (long life filter, anti-bacterial type)
Fuse
LEV

Connectable outdoor unit


Diameter of
refrigerant pipe
(O.D.)

PLFY-P18NBMU-E

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm = m3/min x 35.31
lbs = kg / 0.4536
*Above specification data is subject to
rounding variation.

1. Specifications

DATA U4

Model
Power source
Cooling capacity *1
(Nominal)

PLFY-P24NBMU-E

Power input

BTU / h
kW
kW
A
BTU / h
kW
kW

Current input

Power input
Current input
Heating capacity *2
(Nominal)

External finish
External dimension H x W x D
Net weight

Dimension
HxWxD

10-3/16 x 33-3/32 x 33-3/32


258 x 840 x 840
51 (23)
PLP-40BAU
Munsell No. (6.4Y 8.9/0.4)

11-3/4 x 33-3/32 x 33-3/32


298 x 840 x 840
60 (27)
PLP-40BAU

1-3/8 x 37-13/32 x 37-13/32

1-3/8 x 37-13/32 x 37-13/32

1-3/8 x 37-13/32 x 37-13/32

35 x 950 x 950
13 (6)
Cross fin
Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0

35 x 950 x 950
13 (6)

35 x 950 x 950
13 (6)
Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0

0.050
Direct-driven
530 - 565 - 636 - 706
15.0 - 16.0 - 18.0 -20.0
250 - 267 - 300 - 333

Turbo fan x 1
0.000 (208V)
0
0.000 (230V)
0
DC motor
0.050
565 - 636 - 706 - 777
16.0 - 18.0 - 20.0 - 22.0
267 - 300 - 333 - 367

777 - 883 - 989 - 1,059


22.0 - 25.0 - 28.0 - 30.0
367 - 417 - 467 - 500

28 - 30 - 32 - 34(208-230V)

30 - 32 - 35 - 37(208-230V)

35 - 38 - 41 - 43(208-230V)

Type x Quantity
External
static pressure

in.WG
Pa
in.WG
Pa

Motor type
Motor output
Driving mechanism

kW

Airflow rate
(Low-Mid2-Mid1-High)

cfm
m3 / min
L/s

0.120

PS
PP honeycomb (long life filter, anti-bacterial type)
Fuse
LEV
R410A,R22 CITY MULTI
3/8 (9.52) Flare
3/8 (9.52) Flare
3/8 (9.52) Flare
3/8 (9.52) Flare
3/8 (9.52) Flare
3/8 (9.52) Flare
5/8 (15.88) Flare
5/8 (15.88) Flare
5/8 (15.88) Flare
5/8 (15.88) Flare
5/8 (15.88) Flare
3/4 (19.05) Flare
O.D. 1-1/4(32)
O.D. 1-1/4(32)
O.D. 1-1/4(32)
33-1/2 (851)
33-1/2 (851)
33-1/2 (851)
Installation Manual, Instruction Book
PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PAC-SA1ME-E
PAC-SH65OF-E
PAR-SA9FA-E

PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PAC-SA1ME-E
PAC-SH65OF-E
PAR-SA9FA-E

PAC-SH51SP-E
PAC-SH59KF-E
PAC-SH53TM-E
PAC-SA1ME-E
PAC-SH65OF-E
PAR-SA9FA-E

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Details on foundation work, duct work, insulation work, electrical wiring, power source switch,
and other items shall be referred to the Installation Manual.

Installation

Note:
Indoor:
Outdoor:
Pipe length:

*1 Nominal cooling conditions


80degF D.B. / 67degF W.B.
(26.7degC D.B. / 19.4degC W.B.)

*2 Nominal heating conditions

Unit converter
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm = m3/min x 35.31

70degF D.B. (21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B. / 43degF W.B.


(8.3degC D.B. / 6.1degC W.B.)

25 ft. (7.6 m)

25 ft. (7.6 m)

Level difference:
0 ft. (0 m)
0 ft. (0 m)
*Due to continuing improvement, above specification may be subject to change without notice.

lbs = kg / 0.4536
*Above specification data is subject to
rounding variation.

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-5

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Sound pressure level (Low-Mid2-Mid1-High)


dB <A>
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit
Liquid (R410A)
in. (mm)
Diameter of
(R22)
refrigerant pipe
Gas (R410A)
(O.D.)
in. (mm)
(R22)
Field drain pipe size
in. (mm)
Drain lift mechanism
in. (mm)
Standard
Document
attachment
Accessory
Air outlet shutter plate
High efficiency filter element (MERV 10)
Multi-function casement
Optional parts
i-see sensor corner panel
Flange for fresh air intake
Wireless signal receiver

Remark

1.00

in.

Heat exchanger

Fan

0.43

in.
mm
lbs (kg)

mm
lbs (kg)

Net Weight

0.36

36,000
10.5
0.16
1.07
40,000
11.7
0.15

Galvanized steel sheet


10-3/16 x 33-3/32 x 33-3/32
258 x 840 x 840
51 (23)
PLP-40BAU

Model
External finish
Decoration
panel

PLFY-P36NBMU-E

24,000
7.0
0.06
0.43
27,000
7.9
0.05

PLFY-P30NBMU-E
1-phase 208-230 V 60Hz
30,000
8.8
0.07
0.51
34,000
10.0
0.06

2. External DImensions

DATA U4

Ref. : PLFY-NCMU-E_EXD_USDB_P08-15
Unit : in.(mm)

PLFY-P08,12,15 NCMU-E

1-7/32(31)

12

4-21/32(118)

22-7/16(570)

Ceiling surface

13-27/32(352)
13-3/16(335)
19/32~1-15/32(15~37)

22-11/16~24-13/32(576~620) Ceiling hole

Drainpipe
VP-25 connection
(O.D. 1-1/4( 32))
Suspension bolt M10 or W3/8

9-1/16(230)

Wiring entry

7-5/32(182)

7-15/16(202)

Ceiling surface

8-3/16(208)

9-1/4(235)

1-7/8(48)

Grille

1-1/16

Terminal block

+3/16 (27 + )
0
0
25/32(20)

1-1/2~2-9/32(38~58)

3-21/32(93)

7-19/32(193)

4-3/4(121)

2-7/8( 73.4)
Cut out hole

3-7/16(87)

2-7/32(56)

2-1/14(57)

19/32~1-15/32(15~37)

2-19/32(66)

22-7/16(570)

13-3/16(335)

16-17/32(420)
Suspension bolt pitch

22-11/16~24-13/32(576~620)

Suspension bolt pitch

7-27/32(199)

Unit : in.(mm)

25-19/32(650)
11-27/32(301)
Air outlet hole

PLFY-P08NCMU-E
PLFY-P12NCMU-E
PLFY-P15NCMU-E
Brand label
Grille

2-5/32(55)

Drain hole

14-27/32(377)
Air intake hole

11-27/32(301)
Air outlet hole

Auto vane

Air intake grille


Vane motor
14-27/32(377)
Air intake hole
1-3/8(35)

PLFY-6

2-5/32(55)

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

Service Access Required

1-3/8(35)

Models

25-19/32(650)

PLFY-P-NCMU-E
PLFY-P-NBMU-E

1(25)

3- 1/8( 2.8)
Burring hole

20-7/8(530)

120

19/32~1-15/32(15~37)

Detail drawing of ventilation air intake


3-15/16( 100)

Ceiling hole

19/32~1-15/32(15~37)

Ventilation air intake

1
Refrigerant pipe
(1/4 (6.35) dia.)
flared connection
1/4F

2
Refrigerant pipe
(1/2 (12.7) dia.)
flared connection
1/2F

2. External DImensions

DATA U4

PLFY-P12,15,18,24,30,36 NBMU-E

Unit : in. (mm)

3-17/64
(83)
1-27/64
(36)

Min.94-1/2(2400)
from floor

PLFY-P12NBMU-E
PLFY-P15NBMU-E
PLFY-P18NBMU-E

Min.19-11/16(500)
Entire
periphery

w6-9/16(167)

w6-3/32(155)

Burring hole pitch


4-29/32(125)

(w158)
6-7/32

120

120

Keep 25/64(10) to 19/32(15)


between unit ceiling
and ceiling slab.

1-27/64 (36)
3-17/64
(83)

Models

Grille

Connected the attached


flexible pipe or socket.

1-3/8
(35)

Vane motor

Indoor unit

Ceiling

70

33-27/32 to 35-13/16(860~910)
Ceiling hole

24-13/32 (620)

25/32
to 1-25/32
(20~45)

M
19-11/16 (500)
Air outlet hole
37-3/8 (950)

In case of standard grille

Cut out hole


3-15/16(100)

Floor
PLFY-P24NBMU-E
PLFY-P30NBMU-E
PLFY-P36NBMU-E

In case of wireless remote controller


Emergency operation switch<Cooling>
Emergency operation
switch<Heating>

Receiver

Auto vane
(Air outlet)

Corner pocket

Burring hole
3-1/8(3-2.8)

Ceiling

23-1/2(597)
Air intake hole

37-3/8 (950)

19-11/16 (500)
Air outlet hole

Air intake
grille

Detail drawing of ventilation air intake hole

Drain hole
Drain pump clean hole
and Drain emergency
drainage hole

14-1/8(14-2.8)
Burring hole

Operation lamp

DEFROST/STAND BY lamp

Note:
1. As for drain pipe, please use VP-25 O.D. 1-1/4(32) PVC TUBE.
Drain pump is included.
Max. lifting height is 33-1/2 (850mm) from the ceiling.
2. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
3. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/power wires connection.
4. The height of the indoor unit is able to be adjusted with the grille attached.
5. For the installation of the optional high efficiency filter or optional multi-functional
casement.
1 Add 5-5/16"(135mm) to the dimensions Wmarked on the figure.
2 The optional high efficiency filter becomes optional multi-functional casement
and concomitant use.
6. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/water dew.)
As for necessary installation / service space, please refer to the left figure.
AccessoryDrain socket(I.D.1-1/4)
Flare nut 3/8 (For P18)
Flare nut 5/8 (For P18)
Flare nut 3/4 (For P36)

1
Refrigerant pipe
6.35
Flared connection
1/4
Refrigerant pipe
6.35 / 9.52
Flared connection
1/4 / 3/8
(compatible)

Refrigerant pipe 12.7


Flared connection 1/2
Refrigerant pipe 12.7 / 15.88
Flared connection 1/2 / 5/8
(compatible)

9-1/2 10-3/16 3-5/32 2-29/32


(241) (258)
(80)
(74)

Refrigerant pipe 15.88


Refrigerant pipe Flared connection 5/8
9.52
Flared connection Refrigerant pipe 15.88 / 19.05
11-1/16 11-3/4 3-11/32 3-1/32
3/8
Flared connection 5/8 / 3/4
(281) (298)
(85)
(77)
(compatible)

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-7

PLFY-P-NCMU-E
PLFY-P-NBMU-E

23-1/2 (597)
Air intake hole

(17 +50 )
11/16 +3/16
0

1-31/32 to 2-3/4
(50~70)

w5-1/2
(140)

Ceiling
Grille

13-25/32
(350)

(175) 6-7/8
Burring hole pitch

5-29/32(150)
Cut out hole

Drain pipe
connected to VP-25

(377)
14-27/32

Suspension bolt
lower edge

+35
23-13/16 -3/16
+1-3/8 (605 -5 )

Suspension bolt pitch


15/16 (24)

(284)
11-3/16

w4-1/8(105)

6-5/16
(160)

w6-9/64
(156)
w7-15/32
(190)
A

33-1/16 (840)
(60)
2-3/8

6-5/16 (160)

3-17/32 (90)

7-3/8
(187.5)

Suspension bolt
M10 or W3/8

Branch
duct hole

(5/16)
(7.5)

6-5/16
(160)

Indoor unit/Outdoor unit


connecting terminal block

Branch duct hole

5-29/32 (150)

33-1/16(840)

For MA-Remote controller


terminal block

w6-11/16
(170)

3-15/16(100)
3-17/32(90)
Cut out hole

3-15/16 (100)
3-17/32 (90)

(5/16)
(7.5)

6-16/5
(160)

Detail connecting of branch duct(Both aspects)

25/32 to
1-25/32
(20~45)

Ventilation air
intake hole

25/32 to 1-25/32(20~45)

31-7/8(810)
Suspension bolt pitch

3-15/16 (100)
5-1/8 (130)

Ceiling hole
33-27/32 to 35-13/16(860~910)

25/32~1-25/32(20~45)

3. Center of Gravity

DATA U4

PLFY-P08,12,15NCMU-E

Ref.: PLFY_NCMU_COG_USDB_ALL

Refrigerant pipe
Refrigerant pipe side

(mm)[in]
Model name
PLFY-P08NCMU-E
PLFY-P12NCMU-E
PLFY-P15NCMU-E

X
150 [5-29/32]
150 [5-29/32]
150 [5-29/32]

Y
260 [10-1/4]
260 [10-1/4]
260 [10-1/4]

Z
105 [4-5/32]
105 [4-5/32]
105 [4-5/32]

PLFY-P-NCMU-E
PLFY-P-NBMU-E

PLFY-P12,15,18,24,30,36NBMU-E

Refrigerant pipe
Refrigerant pipe side

(mm)[in]
Model name
PLFY-P12NBMU-E
PLFY-P15NBMU-E
PLFY-P18NBMU-E
PLFY-P24NBMU-E
PLFY-P30NBMU-E
PLFY-P36NBMU-E

PLFY-8

X
280 [11-1/32]
280 [11-1/32]
280 [11-1/32]
280 [11-1/32]
280 [11-1/32]
280 [11-1/32]

Y
400 [15-3/4]
400 [15-3/4]
400 [15-3/4]
400 [15-3/4]
400 [15-3/4]
400 [15-3/4]

Z
105 [4-5/32]
105 [4-5/32]
105 [4-5/32]
105 [4-5/32]
105 [4-5/32]
125 [4-15/16]

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

4. Electrical Wiring Diagrams

DATA U4

PLFY-P08,12,15 NCMU-E

Ref. : PLFY-NCMU-E_EWD_USDB_P08-15

[LEGEND]
SYMBOL
NAME
INDOOR CONTROLLER BOARD
I.B
CN32 CONNECTOR REMOTE SWITCH
CN41
HA TERMINAL-A
CN51
CENTRALLY CONTROL
CN52
REMOTE INDICATION
FUSE FUSE (6.3A/250V)
SW1
SWITCH
MODE SELECTION
SW2
CAPACITY CODE
SW3
MODE SELECTION
SW4
MODEL SELECTION
SW11
ADDRESS SETTING 1ST DIGIT
SW12
ADDRESS SETTING 2ND DIGIT
SW14
CONNECTION No.
X1
AUX. RELAY DRAIN PUMP/DEW PREVENTION HEATER
FAN MOTOR (LL)
X4
X5
FAN MOTOR (Lo)
X6
FAN MOTOR (Hi)
X7
FAN MOTOR (Me)
VARISTOR
ZNR

SYMBOL
NAME
CAPACITOR (FAN MOTOR)
C1
DRAIN PUMP
DP
DRAIN SENSOR
DS
DEW PREVENTION HEATER
H2
LINEAR EXPANSION VALVE
LEV
FAN MOTOR (WITH THERMAL FUSE)
MF
VANE MOTOR
MV
POWER SUPPLY
TB2
TERMINAL
BLOCK
TRANSMISSION
TB5
MA-REMOTE CONTROLLER
TB15
THERMISTOR ROOM TEMPERATURE DETECTION
TH21
(32F/15k 77F/5.4k)
PIPE TEMPERATURE DETECTION/LIQUID
TH22
(32F/15k 77F/5.4k)
PIPE TEMPERATURE DETECTION/GAS
TH23
(32F/15k 77F/5.4k)
INDOOR POWER BOARD
P.B

TO NEXT INDOOR UNIT


RED

TB2

BLU
GRN/YLW

FUSE(15A)

AC208-230V
CNSK(RED)

WHT
(FAN)
FAN

1 3

GRILLE

ORN
(POWER)
CND

1 3

RED
(D+HEATER)
CNC

BLU
(D+U+M)
CNP

1 3

3 1

RED
(POWER
BORD)
CNDK

WHT
(POWER
BORD)
CN2D

YLW
YLW

1 3 5 7 9

POWER SUPPLY
~/N 208-230V 60Hz

FUSE

BLK
WHT

LED1

MV 5
MV 5

WHT
HA
CN41

WHT
(CENTRALLY
CONTROL)
CN51

4 3 2 1

5 4 3 2 1

SW1
0N
0FF

1 2 3 4 5 6 7 8 9 10

SW2

SW4

SW3

1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10

0N
0FF

12345

GRN
(REMOTE
INDICATION)
CN52

5 4 3 2 1

WHT
(LEV)
CN60

WHT
(DRAIN)
CN31

6 5 4 3 2 1

3 2 1

See fig: 1

SW12

SW11

2ND
DIGIT

1ST
DIGIT

RED
WHT
(INTAKE) (LIQUID)
CN20
CN21

6 5 4 3 2 1

CONNECTION
No.

S(SHIELD)

TB15

1
2

TO OUTDOOR UNIT
BC CONTROLLER
M-NET REMOTE
CONTROLLER
DC24-30V
TO MA-REMOTE
CONTROLLER
DC8.7-13V

LED2

SW14

GRN
(VANE)
CN6V

RED
ORN
YLW
WHT
BLU

0N
0FF

X1

M1
M2

2 1

ZNR

3 1

BLU
(M-NET)
CN2M

X7

X7

BLU
(REMOCON)
CN3A

X6 X5 X4

X6 X5 X4

BRN
RED
BLU
ORN
YLW
WHT

MV 5

3 2 1

MV

9
8
RED
10
RED
5
RED 4
7
ORN
6
YLW
3
WHT
2
BLU 1

WHT
(REMOTE SWITCH)
CN32

H2

TB5

X1

3RD
DIGIT

BLK
(GAS)
CN29

2 1

2 1

2 1

TH21

TH22

TH23

LEV

DS

LED on indoor controller board for service


Mark

Meaning

LED1

Main power supply

Main power supply(Indoor unit:208-230V) power on

Function

LED2

Power supply for


MA-Remote controller

Power supply for MA-Remote controller on

lamp is lit

lamp is lit

Notes:
1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmisson line is non-polar.)
4.Symbol[S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
:terminal block,
:connecter.
6.The setting of the SW2 dip switches differs in the capacity for the detail,refer to the fig: 1.
7.Use copper supply wire.

<fig: 1>
MODELS

SW2

P08

ON
OFF

P12

ON
OFF

P15

ON
OFF

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

123456

123456

123456

PLFY-9

PLFY-P-NCMU-E
PLFY-P-NBMU-E

I.B

2
1

WHT
RED

RED

BLK
YLW
BRN
WHT
BLU

C1

BREAKER
(15A)

DC13.1V
CN2S(WHT)

TRANS

3
2
1

1 2

ORN

PULL BOX

P.B

DP

2 1

MF

L1
L2
GR

(/(&75,&$/ :,5,1*',$*5$06
4. Electrical Wiring Diagrams

'$7$ 8

DATA U4

PLFY-P12,15,18,24,30,36 NBMU-E
A.B
GRILLE
ON
OFF

MV MV MV MV
M M M M

SW1
1 2 3 4 5 6 7 8 910

3
2
1

2
3
4

SW12 SW11
0

0
5

(RED) 4
ADDRESS
CN43
SWA SWB
1

3RD.DIGIT 2ND.DIGIT 1ST.DIGIT

SWC
2
1

<w1>
P12

(RED)
SW14 ADDRESS
0
CN82

P15

ON
OFF

P18

ON
OFF

CONNECTION
No.

19 17 15 13 11 9 7 5 3 1
VANE CNV
I-SEE SENSOR MOTOR
(WHT)
CN6Y
(RED) 6
1
MA REMOCON
CN3A
(BLU)
1 3
I-SEE SENSOR
CN4Y
1 (WHT) 4
LEV
CN60
1 (WHT) 6
CN52
1 (GRN) 5

CN51
1 (WHT) 5

Pair No.

P24

ON
OFF

P30

ON
OFF

P36

ON
OFF

1 2 3 4 5 6

ADDRESS
CN81
(RED)

w2

SW4

ON
OFF
1 2 34 5 67 8 910

1 2 3 4 5 1 2 34 5 6

CN24
(YLW)

1 2

ZNR01 U

CN25
3 (WHT)
1 2
LED1

LIQUID/PIPE
CN44
1 (WHT)4

CN41
1 (WHT) 4

WHT
YLW
ORN
BLU
RED
BRN

I-SEE
SENSOR

TB15
BLU
1
BLU

TO MA-REMOTE
CONTROLLER
DC8.7-13V

MT

PLFY-P-NCMU-E
PLFY-P-NBMU-E

I-SEE SENSOR CORNER PANEL


(OPTION PART)

ZNR02 U
FUSE

CN3G
(BLK)

FLOAT SW
CN4F
1(WHT) 4

INTAKE
CN20
(RED)

1 2

FAN
CNMF
(WHT)

CN27
(RED)

1 2

X1

9
4

DSA

DC311~339V
RECTIFICATION

OFF ON

CND

2 1
M-NET
CN2M
(BLU)

SWE

LED2

TO NEXT
INDOOR UNIT

I.B

1 3 5

SW2

ON
OFF

ADDRESS
CN42
(RED)

WIRELESS
CN90
(WHT)

GR

FUSE(16A)
PULL BOX

See fig:w1
SW3

BREAKER
(16A)

TB2
RED
L1
BLU
L2
GRN/YLW

1 2 3 4 5 6

TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER
DC24-30V
S
(SHIELD)

1 2 3 4 5 6

1 2 3 4 5 6

POWER SUPPLY
~/N 208-230V 60Hz

TB5
BLU
M1
BLU M2

1 2 3 4 5 6

1 2 3 4 5 6

CN32
(WHT) J42 J41

SW2

MODELS

ON
OFF

20 18 16 14 12 10 8 6 4 2

SW2

MODELS

CNB

RU

W.B

LEV

MS
3~
t

LED1

SW2

BZ
LED2

SW1

TH22 TH23

FS

D.U.M 3
CNP
(BLU)

CNAC
(WHT)

3 1

M
1~
DP

MF

wBe sure to turn off the power source


and then disconnect fan motor connector.
TH21
(Failure to do so will cause trouble in Fan motor.)

NOTES:
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
: terminal block,
: connecter.
6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig<w1>.
w2.Use copper supply wires.
[LEGEND]
SYMBOL
I. B
CN27
CN32
CN51
CN52
DSA
FUSE
LED1
LED2
SW2
SW3
SW4
SWE
X1
ZNR01,02

NAME
INDOOR CONTROLLER BOARD
CONNECTOR DAMPER
REMOTE SWITCH
CENTRALLY CONTROL
REMOTE INDICATION
SURGE ABSORBER
FUSE (T6.3AL250V)
POWER SUPPLY (I. B)
POWER SUPPLY (I. B)
CAPACITY CODE
SWITCH
MODE SELECTION
MODEL SELECTION
DRAIN-UP MACHINE (TEST MODE)
AUX. RELAY
DRAIN WATER LIFTING-UP MACH.
VARISTOR

SYMBOL
DP
FS
LEV
MF
MV
TB2
TB5
TB15
TH21
TH22
TH23

NAME
DRAIN-UP MACHINE
DRAIN FLOAT SWITCH
LINEAR EXPANSION VALVE
FAN MOTOR
VANE MOTOR
TERMINAL
POWER SUPPLY
TRANSMISSION
BLOCK
MA-REMOTE CONTROLLER
THERMISTOR ROOM TEMP. DETECTION
(0: / 15k, 25:/ 5.4k)
PIPE TEMP. DETECTION / LIQUID
(0:/ 15k, 25:/ 5.4k)
PIPE TEMP. DETECTION / GAS
(0:/ 15k, 25:/ 5.4k)

SYMBOL
A. B
SWA
SWB
SWC
SW1
SW11
SW12
SW14
OPTION PART
W.B
BZ
LED1
LED2
RU
SW1
SW2

NAME
ADDRESS BOARD
CEILING HEIGHT SELECTOR
SWITCH
DISCHARGE OUTLET NUMBER
SELECTOR
OPTION SELECTOR
MODE SELECTION
ADDRESS SETTING 1ST DIGIT
ADDRESS SETTING 2ND DIGIT
CONNECTION NO.
PCB FOR WIRELESS REMOTE CONTROLLER
BUZZER
LED (OPERATION INDICATION : GREEN)
LED (PREPARATION FOR HEATING : ORANGE)
RECEIVING UNIT
EMERGENCY OPERATION (HEAT / DOWN)
EMERGENCY OPERATION (COOL / UP)

LED on indoor board for service


Mark

Meaning

LED1

Main power supply

LED2

Power supply for


MA-Remote controller

Function
Main Power supply (Indoor unit:208-230V)
power on
Lamp is lit.
Power supply for MA-Remote controller
on
Lamp is lit.

3/)<31&08(  3/)<31%08(

PLFY-10

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

,8)

5. Sound Pressure Levels

DATA U4

5-1. Sound Pressure Levels


Cassette ceiling series

Operating sound levels


(Low-Middle2-Middle1-High)
UNIT

Unit : dB(A)

Model

CEILING

Sound level A (weighted)

PLFY-P08NCMU-E

29-32-38

PLFY-P12NCMU-E

30-34-39

PLFY-P15NCMU-E

31-35-40

PLFY-P12NBMU-E

27-28-29-31

PLFY-P15NBMU-E

27-28-30-31

PLFY-P18NBMU-E

28-29-30-32

PLFY-P24NBMU-E

28-30-32-34

MICROPHONE

PLFY-P30NBMU-E

30-32-35-37

Measurement location

PLFY-P36NBMU-E

35-38-41-43

4- 7/8ft
(1.5m)

5-2. NC Curves
PLFY-P08NCMU-E

PLFY-P12NCMU-E

PLFY-P15NCMU-E

External Static Pressure: 0Pa


Power Source: 208-230V 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V 60Hz

70.0

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0

NC-60

55.0

NC-50

NC-50

NC-40

40.0
NC-40

35.0

250

15.0
10.0

500

1k

2k

4k

8k

63

125

250

500

PLFY-P12NBMU-E
External static pressure : 0Pa
Power source : 208,230V, 60Hz
Middle1 60Hz
Middle2 60Hz

65.0
60.0
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

60.0
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
63

NC-60

50.0
NC-50

40.0
NC-40

35.0
30.0

NC-30

25.0
Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

125

250

500

2k

1k

2k

4k

4k

Octave band center frequencies (Hz)

8k

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
Approximate minimum
audible limit on
continuous noise
125

250

NC-20
500

1k

2k

Middle1 60Hz
Middle2 60Hz

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
63

125

250

NC-20
500

1k

2k

4k

8k

4k

Octave band center frequencies (Hz)

8k

Middle1 60Hz
Middle2 60Hz

High 60Hz
Low 60Hz

70.0
65.0
60.0
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

8k

60.0

Middle1 60Hz
Middle2 60Hz

60.0

10.0

4k

Octave band center frequencies (Hz)

65.0

15.0

2k

High 60Hz
Low 60Hz

8k

70.0

20.0

NC-20
1k

PLFY-P36NBMU-E
External static pressure : 0Pa
Power source : 208,230V, 60Hz

High 60Hz
Low 60Hz

Octave band pressure level (dB) 0dB=20Pa

Octave band pressure level (dB) 0dB=20Pa

60.0

500

70.0
65.0

10.0

Middle1 60Hz
Middle2 60Hz

65.0

20.0

NC-20

PLFY-P30NBMU-E
External static pressure : 0Pa
Power source : 208,230V, 60Hz

70.0

250

Middle1 60Hz
Middle2 60Hz

65.0

10.0

8k

PLFY-P24NBMU-E
External static pressure : 0Pa
Power source : 208,230V, 60Hz

45.0

125

Ref.:PLFY-NCMU-E_NCC_USDB_P15

Octave band center frequencies (Hz)

55.0

63

Octave band center frequencies (Hz)

70.0

Octave band center frequencies (Hz)

High 60Hz
Low 60Hz

10.0

PLFY-P18NBMU-E
External static pressure : 0Pa
Power source : 208,230V, 60Hz

High 60Hz
Low 60Hz

Octave band pressure level (dB) 0dB=20Pa

Octave band pressure level (dB) 0dB=20Pa

High 60Hz
Low 60Hz

15.0

8k

PLFY-P15NBMU-E
External static pressure : 0Pa
Power source : 208,230V, 60Hz

70.0

10.0

4k

Ref.:PLFY-NCMU-E_NCC_USDB_P12

Ref.:PLFY-NCMU-E_NCC_USDB_P08

15.0

2k

Approximate minimum
audible limit on
continuous noise

Octave band center frequencies (Hz)

Octave band center frequencies (Hz)

20.0

NC-20
1k

Octave band pressure level (dB) 0dB=20Pa

125

NC-20

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

Octave band pressure level (dB) 0dB=20Pa

63

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

30.0

63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies (Hz)

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-11

PLFY-P-NCMU-E
PLFY-P-NBMU-E

NC-30

25.0

NC-40

35.0

30.0

30.0

NC-50

45.0

40.0

35.0

NC-60

55.0
50.0

45.0

40.0

10.0

NC-60

50.0

45.0

15.0

60.0

55.0

50.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0

60.0

60.0

20.0

70.0

60Hz
High
Middle 60Hz
60Hz
Low

65.0

6. Temperature/Airflow Distributions

DATA U4

6-1. Temperature Distributions


PLFY-P08,12,15 NCMU-E
<Cooling mode>
Flow angle 30
<C(F)>

<Heating mode>
Flow angle 70

<C(F)>

2.7
(8.8)

2.7
(8.8)

35(95)

23(73)

25(77)

1
(3.3)

2
(6.6)

Height <m(ft)>

Height <m(ft)>

21(70)
2
(6.6)

25(77)

1
(3.3)

31(88)
27(81)

23(73)

23(73)

19(66)
0

3
(9.8)

2
(6.6)

1
(3.3)

3
(9.8)

Floor distance <m(ft)>

2
(6.6)

1
(3.3)

Floor distance <m(ft)>

PLFY-P-NBMU-E
PLFY-P12,15,18,24,30NBMU-E
<Cooling mode> Standard
Flow angle : 30 4-way flow
ceiling height : 2.7 m(8.8ft)

PLFY-P12,15,18,24,30NBMU-E
<Heating mode> Standard
Flow angle : 60 4-way flow
ceiling height : 2.7 m(8.8ft)
<C(F)>

2.7

(8.8)

Height <m(ft)>

Height <m(ft)>

(6.6)

27(81)
1

(6.6)

29(84)

26(79)

23(73)

(3.3)

(3.3)

23(73)

27(81)

20(68)
20

(68)

0
4
(13.1)

(9.8)

(6.6)

(3.3)

(13.1)

(9.8)

(6.6)

(3.3)

Floor distance <m(ft)>

Floor distance <m(ft)>

PLFY-P36NBMU-E
<Heating mode> Standard
Flow angle : 60 4-way flow
ceiling height : 3.2 m(10.4ft)

PLFY-P36NBMU-E
<Cooling mode> Standard
Flow angle : 30 4-way flow
ceiling height : 3.2 m(10.4ft)
<C(F)>

3.2
(10.5)

3.2
(10.5)

23
(73)

<C(F)>
20(68)

32
(90)
25
(77)

27(81)

Height <m(ft)>

Height <m(ft)>

PLFY-P-NCMU-E
PLFY-P-NBMU-E

32
(90)

25(77)

<C(F)>

2.7
(8.8)

23
(73)

(6.6)

29
(84)

2
(6.6)
26(79)

20(68)
27(81)

1
(3.3)

(3.3)

23(73)

23(73)

5
(16.4)

4
(13.1)

3
(9.8)

2
(6.6)

1
(3.3)

Floor distance <m(ft)>

5
(16.4)

4
(13.1)

3
(9.8)

2
(6.6)

1
(3.3)

Floor distance <m(ft)>

Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differ
from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

PLFY-12

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

6. Temperature/Airflow Distributions

DATA U4

6-2. Airflow Distributions


PLFY-P08,12,15 NCMU-E
<Fan mode>
Flow angle 70

<Fan mode>
Flow angle 30
<m/s(ft/s)>

2.7
(8.8)
3.0(3.3)
2.0(6.6)

3.0(9.8)
2
(6.6)

Height <m(ft)>

Height <m(ft)>

2
(6.6)

<m/s(ft/s)>

2.7
(8.8)

1.0(3.3)
1
(3.3)

1.0(3.3)
0.5(1.6)

2.0(6.6)

1
(3.3)

0.5(1.6)

4
(13.1)

3
(9.8)

2
(6.6)

1
(3.3)

4
(13.1)

3
(9.8)

Floor distance <m(ft)>

<Cooling mode>
Flow angle 30

<m/s(ft/s)>

2.7

(8.8)

Height <m(ft)>

3.0
(9.8)

(6.6)

2.0
(6.6)

3.0
(9.8)

(6.6)

1.0
(3.3)

1.0
(3.3)

1
(3.3)

(3.3)

0.5
(1.6)

(13.1)

(9.8)

2.0
(6.6)

(6.6)

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Height <m(ft)>

<m/s(ft/s)>

2.7

(8.8)

0.5
(1.6)

(3.3)

(13.1)

(9.8)

(6.6)

(3.3)

PLFY-P36NBMU-E
<Heating mode>
Flow angle 60

<Cooling mode>
Flow angle 30
<m/s(ft/s)>

3.2
(10.5)

<m/s(ft/s)>

3.2
(10.5)

4.0
(13.1)
3.0
(9.8)

3.0
(9.8)

2.0
(6.6)

Height <m(ft)>

Height <m(ft)>

Floor distance <m(ft)>

Floor distance <m(ft)>

2
(6.6)

2.0
(6.6)

1.0
(3.3)

4
(13.1)

3
(9.8)

0.5
(1.6)

1.0
(3.3)

0.5
(1.6)

2
(6.6)

Floor distance <m(ft)>

4.0
(13.1)

2
(6.6)

1
(3.3)

1
(3.3)

0
5
(16.4)

1
(3.3)

Floor distance <m(ft)>

PLFY-P12,15,18,24,30NBMU-E
<Heating mode>
Flow angle 60

2
(6.6)

1
(3.3)

5
(16.4)

4
(13.1)

3
(9.8)

2
(6.6)

1
(3.3)

Floor distance <m(ft)>

Note : These figures show typical airflow distributions in the conditions above. In the actual installation, they may differ from
these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-13

6. Temperature/Airflow Distributions

PLFY-P-NCMU-E
PLFY-P-NBMU-E

6-3. Branch Duct Capacities

PLFY-14

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

DATA U4

6. Temperature/Airflow Distributions

DATA U4

PLFY-P-NCMU-E
PLFY-P-NBMU-E

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-15

PLFY-P-NCMU-E
PLFY-P-NBMU-E

6. Temperature/Airflow Distributions

PLFY-16

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

DATA U4

6. Temperature/Airflow Distributions

DATA U4

PLFY-P-NCMU-E
PLFY-P-NBMU-E

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-17

PLFY-P-NCMU-E
PLFY-P-NBMU-E

6. Temperature/Airflow Distributions

PLFY-18

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

DATA U4

6. Temperature/Airflow Distributions

DATA U4

PLFY-P-NCMU-E
PLFY-P-NBMU-E

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-19

7. Ventilation Air Intake amount and Static Pressure

DATA U4

7-1. PLFY-P08, 12, 15NCMU-E

Ventilation air intake hole diagram

Ventilation air intake

3 - { 1/8
Burring hole

4-21/32

120_

120_

(Unit : inch)

{ 3-15/16
Burring hole pitch

{ 2-7/8
(Cut out hole)

Ceiling surface
Electrical Box

Refrigerant pipe

Drain pipe

Taking air into the unit


Static pressure : P [in.W.G.]
20
20
40
60
0

80

100

Air flow : Q [CFM]


120

20
40

PLFY-P-NCMU-E
PLFY-P-NBMU-E

60
80
100
120
NOTE: Ventilation air intake amount should be 20% or less of
total air amount to prevent condensate dripping.

7-2. PLFY-P12, 15, 18, 24, 30, 36NBMU-E


with Multi-function
with Multi-function
CasementCasement
and Filters and Filters
By mounting the optional multi-function casement (PAC-SH53TM-E) to the indoor unit main body, increased
ventilation air intake can be accomplished. (The mounting of the multi-function casement increase the height
of the ceiling plenum by 5-5/16 [135mm].)

Knockout hole for


ventilation air intake

Direct ventilation air intake into the


main body is also possible.

PLFY-20

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

Static pressure [Pa(in.W.G.]

Static pressure [Pa(in.W.G.]

7. Ventilation Air Intake amount and Static Pressure

50(0.20)

2 - inlet
100(0.40)

150(0.60)

1 - inlet
200(0.80)
0

2
50

100

6[CMM]

5
150

200

50(0.20)

2 - inlet

100(0.40)

150(0.60)

1 - inlet
200(0.80)
0

50

[CFM]

100

Airflow rate

Static pressure [Pa(in.W.G.]

DATA U4

6[CMM]

5
150

200

[CFM]

Airflow rate

50(0.20)

100(0.40)

150(0.60)

200(0.80)
0

2
50

100
Airflow rate

6[CMM]

150

200

[CFM]

Static pressure [Pa(in.W.G.]

Static pressure [Pa(in.W.G.]

PLFY-P-NCMU-E
PLFY-P-NBMU-E

50(0.20)

2 - inlet
100(0.40)

150(0.60)

1 - inlet
200(0.80)
0

2
50

4
100

150

6
200

[CMM]
[CFM]

250

Airflow rate

50(0.20)

100(0.40)

2 - inlet
150(0.60)

1 - inlet
200(0.80)
0

2
50

4
100

150

6
200

8
250

[CMM]
[CFM]

Airflow rate

Static pressure [Pa(in.W.G.]

connection only

50(0.20)

100(0.40)

150(0.60)

200(0.80)
0

2
50

4
100

150

6
200

8
250

[CMM]
[CFM]

Airflow rate

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-21

8. Optional Parts

DATA U4

PLFY-P-NBMU-E
PLFY-P-NBMU-E

Air outlet shutter plate


PAC-SH51SP-E

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Multi-function casement
PAC-SH53TM-E

High efficiency filter element


PAC-SH59KF-E (MERV 10)
PAC-SH53TM-E is necessary to use with filter PAC-SH59KF-E.

8-1.Air
AirOutlet
Outlet
Shutter
Plate
PAC-SH51SP-E
for PLFY-P-NBMU-E
8-1.
Shutter
Plate
PAC-SH51SP-E
for PLFY-P-NBMU-E
Using the air outlet shutter plate to block the air outlet to modify the air-way from 4 to 3 or 2.
With 1 PAC-SH51SP-E, 4 air-ways can be changed to 3;
With 2 PAC-SH51SP-E, 4 air-ways can be changed to 2;
Changing to 1 way is not allowed.
Material: Foamed polyethylene + foamed urethane, color: Black
Item

1. Shutter plate

Quantity

2. Insulator
1

Shape

Detailed installation information should be referred to its Installation Manual.

PLFY-22

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

8. Optional Parts

DATA U4

8-2.
HighEfficiency
Efficiency
Filter
Element
PAC-SH59KF-E
for PLFY-P-NBMU
8-2. High
Filter
Element
PAC-SH59KF-E
(MERV(MERV
10) for 10)
PLFY-P-NBMU-E
Life span: 2,500 hr (Dust concentration 0.15mg/m3 ); Colorimetric method 65% (JIS 11 class)); No re-production.
*.The actual dust situation affects the filter life span, which should be considered at the applying site.
Material: Electrostatic polyolefin fiber
High efficiency filter element PAC-SH59KF-E must be used together with the Multi-function casement PAC-SH53TM-E. When using
PAC-SH59KF-E, switching on SWC of the Indoor unit address board is needed. Details should be referred to its Installation Manual.

Quantity

Shape

Detailed installation information is referred in its Installation Manual.

8-3.Multi-function
Multi-function
Casement
PAC-SH53TM-E
for PLFY-P-NBMU-E
8-3.
Casement
PAC-SH53TM-E
for PLFY-P-NBMU-E
Multi-function casement is used for High efficiency filter element and/or ventilation air intake from outdoor.
It should be used with High efficiency filter element PAC-SH59KF-E (Colorimetric method 65%).
ventilation air intake on the Multi-function casement is possible from any 2 or less corners among the 4 ones.
But duct and flange on the casement should be prepare locally.

Item
Quantity

1. Multi-functional casement

2. Screw with washer (black)

3. Screw

8
M5X0.8X25

M5X0.8X12

Shape

4. Decorative panel securing bracket


4

5. Insulator A for Decorative panel

6. Insulator B for Decorative panel

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Item
Quantity

With insulator
Shape

Detailed installation information should be referred to its Installation Manual.

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-23

8. Optional Parts

DATA U4

8-4.
i-seeSensor
Sensor
Corner
Panel
PAC-SA1ME-E
for PLFY-P-NBMU-E
8-4. i-see
Corner
Panel
PAC-SA1ME-E
for PLFY-P-NBMU-E
i-see sensor provides comfortable space as it detects the floor temperature to prevent spotty temperature.
It also enables the unit to save energy.
Attention
Make sure that there are no gaps between the unit and the grille, and the grille and ceiling.
It may cause condensate dripping.
Item

1. i-see sensor corner panel

Quantity

2. Plastic fastener
2

Shape

Detailed installation information should be referred to its Installation Manual.

8-5.
Signal
Receiver
PAR-SA9FA-E
for PLFY-P-NBMU-E
8-5. Wireless
Wireless Signal
Receiver
PAR-SF9FA-E
for PLFY-P-NBMU-E
Using the wireless signal receiver to use wireles remote controller.
The corner panel(the other side of refrigerant piping) is changed for the wireless signal receiver.

Item

1. Wireless signal receiver

Quantity

Shape

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Detailed installation information should be referred to its Installation Manual.

PLFY-24

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

8. Optional Parts

DATA U4

8-6. External Heater Adapter PAC-YU24HT


External heater adaptor PAC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Relay circuit

Electric Heater
power source

Remote control Board

Indoor unit
control board

Adapter

White

Red

Red

Electric
Heater

Dip switch
PUHY,PURY-P-TGMU type
SW5-2 "ON"
PUHY,PURY-P-YHMU type
SW5-10 "ON"

CN22
Green

Red

Yellow

CN24

Outdoor unit
control board

PUMY series
SW4-4 "ON"

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below Operation coil


Rated voltage : 12VDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit

88H

FS1

H1

88H

FS2
FS1

H2

R
1-phase power
supply

208V, 230V/60Hz

FS1, 2 ----- Thermal fuse

FS2

H1, H2 ----- Heater


26H

88H
Control board

PLFY-P-NCMU-E
PLFY-P-NBMU-E

Wiring diagram

26H --------- Overheat protection


thermostat
88H --------- Electromagnetic contactor

CN24

Item
Quantity

External output cable


2

Fan speed setting cable


with resistance
2

Shape

Refer to the Installation Manual (WT04645X02) wiring and installation details.

PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-25

Ceiling-suspended

DATA U4

PCFY-P-NGMU-E
1. SPECIFICATIONS...................................................................................................................................................PCFY-3
2. EXTERNAL DIMENSIONS......................................................................................................................................PCFY-4
3. Center of Gravity...........................................................................................................................................PCFY-8
4. ELECTRICAL WIRING DIAGRAMS........................................................................................................................PCFY-9
5. SOUND PRESSURE LEVELS..............................................................................................................................PCFY-10
5-1. Sound Pressure Levels...............................................................................................................................PCFY-10
5-2. NC Curves...................................................................................................................................................PCFY-10
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS......................................................................................................PCFY-11
6-1. Temperature Distributions...........................................................................................................................PCFY-11
6-2. Airflow Distributions.....................................................................................................................................PCFY-11
7. OPTIONAL PARTS................................................................................................................................................PCFY-12
7-1. Optional Parts Line Up for the Indoor Unit..................................................................................................PCFY-12
7-2. High Efficiency Filter PAC-SE-KF-E for PCFY-P-NGMU-E..........................................................................PCFY-12
7-3. External Heater Adapter PAC-YU24HT.......................................................................................................PCFY-13

PCFY-P-NGMU-E

PCFY-P-NGMU-E (Feb. 2009)

PCFY-1

Ceiling-suspended
Ceiling suspended

DATA
DATAU4
U3

I.Ceiling suspended

PCFY-P-NGMU-E

PCFY-P-NGMU-E
Ceiling-suspended types
and stores.
type's compact dimensions ideal for restaurants
restaurant, stores
uses

Wide-range outlet, strong air-flow make uniform air temperature


and extremely quiet.
PCFY-P15NGMU-E
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
PCFY-P36NGMU-E

Outlet
35-19/32in.
35-5/8
in.
48-11/32in.
47-13/16
in.
48-11/32in.
47-13-16 in.
607/16in.
60 in.

Noisepressure
level atlevel
low atairlow
flow
Max. airflow Sound
air flow
424cfm
29 dBA
dBA
424cfm
29
636cfm
32 dBA
dBA
636cfm
32
883cfm
36 dBA
dBA
883cfm
36
1236cfm
37
dBA
1236cfm
37 dBA

1 Suspend the bolts;


2 Suspend the unit;
3 Tight the nuts.

Suspension
bolts

Ceiling surface

Strong air flow could even be used at a ceiling of 11'-5'' height.

Attachment
fixture

The
auto-vane swings
swing the
The PCFY's
PCFYs auto-vane
theconditioned
conditionedair
airand
anddistribute
distributesit ituniformly
uniformly
to
of the
the room.
room.
to corners
corners of

PCFY-P-NGMU-E

Air outlet

Auto vane

Swing

Ceiling suspended

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PCFY-P-NGMU-E

* Nominal conditions *1,


atinthe
sheet.
*1, *2
*2 are
are referable
referred to
theSpecification
Specification
sheet.

PCFY-2

PCFY-P-NGMU-E (Feb. 2009)


PCFY-P-NGMU-E

IU - G - 2

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

1. SPECIFICATIONS

Model

PCFY-P15NGMU-E

PCFY-P24NGMU-E

Power source

PCFY-P30NGMU-E

PCFY-P36NGMU-E

1-phase 208-230 V 60Hz

Cooling capacity

*1 BTU / h

15,000

24,000

30,000

(Nominal)

*1 kW

4.4

7.0

8.8

10.6

kW

0.08

0.09

0.23

0.27

Power input
Current input

Heating capacity

*2 BTU / h

(Nominal)

0.40

0.45

1.12

1.32

17,000

27,000

34,000

40,000
11.7

*2 kW

5.0

7.9

10.0

Power input

kW

0.08

0.09

0.23

0.27

Current input

0.40

0.45

1.12

1.32

in.

8-9/32 x 39-3/8 x 26-25/32

8-9/32 x 51-19/32 x 26-25/32

mm

210 x 1,000 x 680

210 x 1,310 x 680

270 x 1,310 x 680

270 x 1,620 x 680

60 (27)

75 (34)

82 (37)

95 (43)

External finish

Polyester painted steel sheet, Plastic 0.70Y 8.59/0.97

External dimension H x W x D
Net weight

lbs (kg)

Heat exchanger
FAN

36,000

10-21/32 x 51-19/32 x 26-25/32 10-21/32 x 63-25/32 x 26-25/32

Cross fin
Type x Quantity
External

in.WG

static pressure
static
press

Pa
in.WG
Pa

Sirocco fan x 2

Sirocco fan x 3

Sirocco fan x 3

Sirocco fan x 4

0.000 (208V)

0.000 (208V)

0.000 (208V)

0.000 (208V)

0.000 (230V)

0.000 (230V)

0.000 (230V)

0.000 (230V)

0.090

0.150

Motor type

1-phase induction motor

Motor output

kW

0.054

0.070

Driving mechanism

Direct-driven

Airflow rate

cfm

(Low-Mid1-Mid2-High)

m3 / min

283-353-388-424

424-494-565-636

636-706-812-883

918-989-1,130-1,236

8.0-10.0-11.0-12.0

12.0-14.0-16.0-18.0

18.0-20.0-23.0-25.0

26.0-28.0-32.0-35.0

133-167-183-200

200-233-267-300

300-333-383-417

433-467-533-583

29-33-36-38 (208-230V)

32-34-37-39 (208-230V)

36-38-41-43 (208-230V)

37-39-42-44 (208-230V)

dB <A>

dB <A>

L/s
Noise level
(Low-Mid1-Mid2-High)
Sound
pressure
level (Low-Mid1-Mid2-High) dB <A>
(measured in anechoic room)
Insulation material

PS foam, Polyethylene foam

Air filter

PP honeycomb (anti-virus type)

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

in. (mm)

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

3/4 (19.05) Flare

O.D. 1-1/32 (26)

O.D. 1-1/32 (26)

O.D. 1-1/32 (26)

O.D. 1-1/32 (26)

RG01N982-01

RG01N982-02

RG01N982-03

RG01N982-04

RG79Y106

RG79Y106

RG79Y106

RG79Y106

Accessory

Optional parts

PCFY-P-NGMU-E

5/8 (15.88) Flare

Refrigerant cycle
attachment

3/8 (9.52) Flare


3/8 (9.52) Flare

5/8 (15.88) Flare

Wiring
Document

3/8 (9.52) Flare


3/8 (9.52) Flare

1/2 (12.7) Flare

External

Standard

3/8 (9.52) Flare


3/8 (9.52) Flare

1/2 (12.7) Flare

in. (mm)
in. (mm)

1/4 (6.35) Flare


1/4 (6.35) Flare

Installation Manual,Installation Book

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

High
Efficiency
Filterfilter
(MERV 8)
Medium
efficiency

PAC-SE80KF-E

PAC-SE81KF-E

PAC-SE81KF-E

PAC-SE82KF-E

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PCFY-P15-36NGMU-E

PCFY-P-NGMU-E (Feb. 2009)


PCFY-P-NGMU-E

IUPCFY-3
-G-3

1
2
3
4
5
6
7
8
9

7/16(11)

9-1/32(229)

1/16(1)

Air outlet

5-5/32(131)

Drainage pipe connection(I.D.1-1/32(26mm))


Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Air intake
Knock out hole for ventilation air intake

Electrical box

10-3/8(263)
11-13/16(300)
13-7/8(352)

3-11/16(86)
5-7/16(138)
6-3/4(171)

1-15/16(49)
2-7/16(62)

6-7/8
(175)
1-13/16(46)

3-1/8(79)
1-1/2(38)
1-1/2(38)
2-3/4(70)

36-17/32(928)

1-3/4(45)
20-21/32(525)

Ceiling

(Suspension bolt pitch)

36-5/32(918)

6-3/8(161)

39-5/8(1000)

35-19/32(904)

38-11/16(983)

36-23/32(933)

23/32(18)
5-29/32
(150)
5-1/2(140)

2-3/4(70)

3-25/32(96)
3-17/32(90)

3-1/8(80)
12-5/8(320)

5/8(16)

39-3/8(1000)

Ceiling

Rear wall

3-7/16(87)

liquid 1/4 ( 6.35)F


gas
1/2 ( 12.7)F
(Drainage)

or more

11-13/16(300)

Less than

9-13/16(230)

Allowing clearances

7-3/16(182)
7-15/16(201)
9-1/2(241)

NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain pump kit
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.

PCFY-P15NGMU-E

or more

10-5/8(270)

6-3/16(157)

1-1/4(32)

7-1/16(179)

1-21/32(42)
1/4 9/32
(7 8)
6-11/32(161)

When electrical box


is pulled down

8-9/32(210)
26-25/32(680)

Less than

(FRONT VIEW)

26-25/32(680)

Electrical box

7-3/32(180)
2-7/32(56)
19-29/32(506)

3-3/16(81)

10(254)

PCFY-P-NGMU-E (Feb. 2009)

or more

PCFY-4
19-11/16(500)

PCFY-P-NGMU-E

2. External Dimensions
2. EXTERNAL DIMENSIONS
DATA
DATA U4
U3

2. EXTERNAL DIMENSIONS

Drw. : IU-RG01N982-01
Unit : in(mm)

1/16(1)
(Gap to ceiling)

1/4 9/32
(6 7)

1-1/4(32)

6-11/32(161)

1
2
3
4
5
6
7
8
9

7/16(11)

10-3/8(263)

9-1/32(229)

2-3/4(70)

16-3/8(416)

11-13/16(300)

Air outlet

6-3/4(171)

5-7/16(138)

3-3/8(86)

5-5/32(131)

Drainage pipe connection(I.D.1-1/32(26mm))


Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Air intake
Knock out hole for ventilation air intake

Electrical box

48-5/8(1235)

3-1/8(79)
1-1/2(38)
1-1/2(38)

1/16(1)
6-7/8
(175)
1-13/16(46)

48-3/8(1228)

47-13/16(1214)
51-9/16(1310)

6-3/8(161)

(Suspension bolt pitch)

50-13/16(1290)

48-13/16(1240)

2-3/4(70)

PCFY-P-NGMU-E (Feb. 2009)

or more

10-5/8(270)

3-17/32(90)

51-9/16(1310)

Ceiling

Rear wall

5/8(16)

3-7/16(87)

Less than

23/32(18)
5-29/32
(150)
5-1/2(140)

26-25/32(680)

3-1/8(80)
12-5/8(320)
6-3/16(157)

2-1/4(57)

2-1/8(54)

20-21/32(525)

3-15/16(100)

Ceiling

liquid 3/8 ( 9.52)F


gas
5/8 ( 15.88)F
(Drainage)

or more

11-13/16(300)

Less than

9-13/16(250)

Allowing clearances

7-3/16(182)
7/15/16(201)
9-1/2(241)

or more

NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain pump kit
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.

PCFY-P24NGMU-E

PCFY-P-NGMU-E

7-1/16(179)

1-21/32(42)

When electrical box


is pulled down

7-3/32(180)
2-7/32(56)

3-25/32(96)
2-3/16(81)

10(254)

8-9/32(210)

19-29/32(506)
26-25/32(680)

1/16(1)
(Gap to ceiling)

(FRONT VIEW)

19-11/16(500)

Electrical box

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATAU3
U4
DATA

Drw. : IU-RG01N982-02
Unit : in(mm)

PCFY-5

1
2
3
4
5
6
7
8
9

6-5/16

Electrical box

9-1/32(229)

2-3/4(70)

13(330)

Air outlet

6-3/4(171)

5-7/16(138)

3-3/8(86)

7-9/16

1/4 9/32

(6 7)

Drainage pipe connection(I.D.1-1/32(26mm))


Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Air intake
Knock out hole for ventilation air intake

2-3/16(55)
7/16(11)
5-7/8(150)

48-5/8(1235)

10-3/8(263)

5-1/2(140)

27-1/16(687)

7-7/8(200)

1-1/2(38)
1-1/2(38)

1/16(1)

(196)

3-21/32(93)

(160)

20-21/32(525)

Ceiling

9
9-9/32(236)
1-25/32(45)

7-2/32(289)

1-21/32(42)

When electrical box


is pulled down

23/32(18)
5-29/32(150)
48-3/8(1228)

51-9/16(1310)

47-13/16(1214)

6-3/8(160)

(Suspension bolt pitch)

50-13/16(1290)

48-13/16(1240)

5-1/2(140)

2-3/4(70)

3-1/8(80)
12-5/8(320)
5/8(16)

3-7/16(87)

51-9/16(1310)

Ceiling

Rear wall

9-5/8(245)

7-13/16(198)

7-3/16(182)

3/8 ( 9.52)F
5/8 ( 15.88)F

(300)
or more

11-13/16

Less than

9-13/16(250)

Allowing clearances

(Drainage)

liquid
gas

NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain punp kit
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.

PCFY-P30NGMU-E

or more

10-5/8(270)

3-17/32(90)

8-17/32(217)

(56)

3-25/32(96)
3-3/16(81)
10(254)

8-5/32(207)
2-7/32

19-29/32(506)

10-5/8(270)
26-25/32(680)

(FRONT VIEW)

26-25/32(680)

Electrical box

Less than

PCFY-P-NGMU-E (Feb. 2009)

19-11/16(500)

PCFY-6
1/16(1)
(Gap to ceiling)

PCFY-P-NGMU-E

2. External Dimensions
2. EXTERNAL DIMENSIONS
DATAU3
U4
DATA

Drw. : IU-RG01N982-03
Unit : in(mm)

7-1/16(239)

1
2
3
4
5
6
7
8
9

2-3/4(70)

9-1/32(229)

Electrical box

27-1/16(687)

5-1/2(140)

Air outlet

13(330)

10-3/8(263)

Drainage pipe connection(I.D.1-1/32(26mm))


Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Knock out hole for ventilation air intake
Air intake

When electrical box


is pulled down

1-21/32(42)

3-21/32(93)

6-5/16(160)

1-1/2(38)
1-1/2(38)

2-3/16(55)
7/16(11)
5-7/8(150)

60-13/16(1545)

20-21/32(525)

7-7/8(200)

23/32(18)
5-29/32(150)

60-7/16(1535)

63-3/4(1620)

6-3/8(161)

(Suspension bolt pitch)

60(1524)

60-29/32(1547)

5-1/2(140)

2-3/4(70)

PCFY-P-NGMU-E (Feb. 2009)

or more

10-5/8(270)

3-17/32(90)

3-1/8(80)
12-5/8(320)
5/8(16)

3-7/16(87)

7-3/16(182)

63-3/8(1620)

Ceiling

Rear wall

9-5/8(245)

7-13/16(198)

Less than

7-9/16(192)
1/16(1)
9-9/32(236)
1-25/32(45)

3-3/8(86)
5-7/16(138)
6-3/4(171)

10-5/8(270)
26-25/32(680)

Ceiling

3-25/32(96)
3-3/16(81)
10(254)

8-5/32(207)
2-7/32(56)
19-29/32(506)

(for R410A)
(for R22A)

or more

11-13/16(300)

Less than

9-13/16(250)

Allowing clearances

(Drainage)

gas

NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain pump kit
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.

26-25/32(680)

8-17/32(217)

8 5

or more

19-11/16(500)

PCFY-P36NGMU-E

PCFY-P-NGMU-E

(Gap to ceiling)

(FRONT VIEW)

1/16(1)

Electrical box

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATA U4
U3

Drw. : IU-RG01N982-04
Unit : in(mm)

PCFY-7

3. Center of Gravity

DATA U4

PCFY-P15,24,30,36NGMU-E

Ref.: PCFY_NGMU_COG_USDB_ALL

(mm)[in]
130
110
110
80

X
[5-1/8]
[4-11/32]
[4-11/32]
[3-5/32]

470
600
580
710

Y
[18-17/32]
[23-5/8]
[22-27/32]
[27-31/32]

120
140
145
140

PCFY-P-NGMU-E

Model name
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E

PCFY-8

PCFY-P-NGMU-E (Feb. 2009)

Z
[4-3/4]
[5-17/32]
[5-23/32]
[5-17/32]

Name

I.B

1 3 5

MF

Varistor

C1

F.C

X4

6 5 4 3 2 1

MV

(RED)
ADDRESS
CN81

FUSE
250V
6A

(RED)
ADDRESS
CN42

X1

X1

CNP 1 3
(BLU)
(RED)

P.B

1 3 CNDK

ON

3
2
1

AC208-230V
(RED)
CNSK

SW3

6 5 4 3 2 1

12345

SW4

4 3 2 1

(WHT)
LEV
CN60

123456 12345678910

SW2

(GRN)
(WHT)
REMOTE CENTRALLY
INDICATION CONTROL
CN52
CN51
5
15
1 6 5

8 7 6 5 4 3 2 1 4 3 2 1 OFF

ZNR

CND 1 3
(RED)

TB15

TB5

6 5 4 3 2 1

(GRN)
VANE
CN6V

X4

FAN 1 3 5
(WHT)

(YLW)
HEATER
CN24

ZNR

X4

TB2

Drain-up machine

Fan motor

BLU

Aux.Relay

Model selection

SW4

BRN
RED
ORN
YLW
WHT
BLU

RED

X1

Mode selection

SW3

TH23

TRANS

LED1

LEV

3 2 1

TH21 TH22

2 1

CN3A 2
(BLU)

CN2M 1
(BLU)
M-NET 2

TH23

ORN

ORN

BLU
BLU

BLK
WHT

RED
BLU

TB2

BREAKER
(15A)

FUSE(15A)

PULL BOX

POWER SUPPLY
~/N 208-230V 60Hz

L1
L2
GR

MV

MV

6 5 4 3 2 1

6 5 4 3 2 1

MODEL
PCFY-P36NGMU-E
(GRN)
VAHE
CN6V

6 5 4 3 2 1

6 5 4 3 2 1

MODEL
PCFY-P30NGMU-E
(GRN)
VAHE
CN6V

TB5 S(SHIELD)
TO OUTDOOR UNIT
M2
BC CONTROLLER
M1
ME REMOTE CONTROLLER
DC24-30V
TB15
1
TO MA REMOTE
CONTROLLER
2
DC8.7-13V

GRN/YLW

Option Selector

TO NEXT INDDOR UNIT

Connection No.

Address setting 2nd digit

Address setting 1st digit

Voltage selection

Ceiling height Selector

CN2D 1
(WHT) 2

2 1

Name
Circuit board Address
Switch
Mode selection

(RED) (WHT) (BLK)


INTAKE LIQUID GAS
ON CN20 CN21 CN29
OFF
2 1 2 1 2 1 LED2

(WHT)
REMOTO
SWITCH
CN32
1
3

(WHT)
DRAIN
CN31

2
1

DC13.1V
(WHT)
CN2S

SWC

RED
WHT
BLK

TH22

Switch

Capacity code

FUSE (6A/250V)

SW2

SW14

FUSE

TH21

Drain-up machine

CNP

SW12

SW11

SW5

Symbol
A. B
SW1

SWA

MV

Remote indication

CN52

Name

Fan phase control

MF

Centrally control

CN51

BLK
WHT

F.C

LEV

Remote switch

C1

Symbol
P. B

CN32

Indoor controller board


Connector
Heater

BRN
RED
ORN
YLW
WHT
BLU

Symbol
I. B
CN24

BRN
RED
BLU
ORN
YLW
WHT

SW1

SW5
230V

3RD 2ND 1ST


DIGIT DIGIT DIGIT

SW12 SW11
0
0

12345678910

ON
OFF

208V

A.B

8
7

CONNECTION
NO.

3
2
1

(RED)
ADDRESS 6
SW14 CN82 5
4
0

Use Copper Supply Wire.

Power supply for


LED2 MA-Remote controller

LED1 Main power supply

4
SWA
(RED)
321
ADDRESS 3
CN43 2

SWC

ON
OFF

ON
OFF

ON
OFF

ON
OFF

123456

123456

123456

123456

SW2

LED on indoor board for service


Meaning
Mark

PCFY-P36NGMU-E

PCFY-P30NGMU-E

PCFY-P24NGMU-E

PCFY-P15NGMU-E

Models

12345678910

12345678910

SW3

Function

ON
OFF

ON
OFF

Note
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
: terminal block,
: connector.
6.The setting of the SW2/SW3 dip switches differs in the capacity.
For the detail, refer to the fig:
7.Please set the switch SW5 according to the power supply voltage.
Set SW5 to 230V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 208V side.

PCFY-P15,24,30,36NGMU-E

PCFY-P-NGMU-E

PCFY-P-NGMU-E (Feb. 2009)


PCFY-P-NGMU-E
RED
ORN
YLW
WHT
BLU

Legend

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATAU4
U3

3. ELECTRICAL WIRING DIAGRAMS

Drw. : IU-RG79Y106

IUPCFY-9
-G-8

5.
4. Sound
SOUND Pressure
PRESSURE Levels
LEVELS

DATAU3
U4
DATA

4-1. Sound
Sound Pressure
Levels
5-1.
Pressure
Levels
4. SOUND LEVELS

Ceiling suspended

Sound pressure level at anechoic room : Low-Mid1-Mid2-Hi


Sound pressure level dB (A)
29-33-36-38
32-34-37-39
36-38-41-43
37-39-42-44

3-1/4 ft
(1.0m)

PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E

3-1/4 ft
(1.0m)

Measurement location

* Measured in anechoic room.

5-2.
Curves
4-2. NC
NC curves
PCFY-P15NGMU-E

PCFY-P24NGMU-E

PCFY-P30NGMU-E

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

70.0

High
Low

65.0

70.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

70.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>

15.0
10.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>

Ref.:NC_PCFY-P15NGMU-E

High
Low

65.0

20.0

15.0
10.0

High
Low

65.0

Ref.:NC_PCFY-P24NGMU-E

15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>


Ref.:NC_PCFY-P30NGMU-E

PCFY-P-NGMU-E

PCFY-P36NGMU-E
External Static Pressure: 0Pa
Power Source: 208-230V, 60Hz
70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>


Ref.:NC_PCFY-P36NGMU-E

PCFY-10

PCFY-P-NGMU-E (Feb. 2009)


PCFY-P-NGMU-E

IU - G - 9

6.
6. Temperature/Airflow
TEMPERATURE/AIRFLOWDistributions
DISTRIBUTIONS

DATA
DATAU4
U3

6-1.Temperature
Temperature distributions
6-1.
Distributions
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

<Cooling mode>
20(68)

Height <m(ft)>

(9' 10-1/8")

22(72)

2
(6' 6-3/4")
24(75)

1
(3' 3-3/8")
0

1
(3' 3-3/8")

24(75)

(9' 10-1/8")

Height <m(ft)>

<Heating mode>

2
3
4
5
6
7
8
(6' 6-3/4") (9' 10-1/8") (13' 1-1/2") (16' 4-7/8") (19' 8-1/4") (22' 11-9/16") (26' 2-15/16")

33
(91)

24
2
(75)
(6' 6-3/4")

27(81)

1
21(70)
(3' 3-3/8")

24(75)
21(70)

30(86)

27(81)

1
2
3
4
5
6
7
8
(3' 3-3/8") (6' 6-3/4") (9' 10-1/8") (13' 1-1/2") (16' 4-7/8") (19' 8-1/4") (22' 11-9/16") (26' 2-15/16")

Floor distance <m(ft)>

Floor distance <m(ft)>

Ref.:TD_PCFY-P-NGMU-E_C0

Ref.:TD_PCFY-P-NGMU-E_H60

Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differ
from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

6-2. Airflow
Airflow distributions
6-2.
Distributions
<Fan mode>
3.0
(9' 10-1/8")

2
(6' 6-3/4") 4.0(13' 1-1/2")

2.0(6' 6-3/4")
1.0(3' 3-3/8")

0.5(1' 7-11/16")

1
(3' 3-3/8")
0

0.5
(1' 7-11/16")

1
(3' 3-3/8")

2
3
4
5
6
7
8
(6' 6-3/4") (9' 10-1/8") (13' 1-1/2") (16' 4-7/8") (19' 8-1/4") (22' 11-9/16") (26' 2-15/16")

Floor distance <m(ft)>

Ref.:AD_PCFY-P-NGMU-E_0

m/s (ft/s)

3.0(9' 10-1/8")

(9' 10-1/8")

Height <m(ft)>

(9' 10-1/8")

Height <m(ft)>

<Fan mode>
m/s (ft/s)

4.0
2
(13' 1-1/2")
(6' 6-3/4")
2.0
(6' 6-3/4")

1
(3' 3-3/8")
0

0.5(1' 7-11/16")
1.0(3' 3-3/8")

1
2
3
4
6
7
8
5
(3' 3-3/8") (6' 6-3/4") (9' 10-1/8") (13' 1-1/2") (16' 4-7/8") (19' 8-1/4") (22' 11-9/16") (26' 2-15/16")

Floor distance <m(ft)>

Ref.:AD_PCFY-P-NGMU-E_60

Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differ
from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

PCFY-P-NGMU-E

PCFY-P-NGMU-E (Feb. 2009)


PCFY-P-NGMU-E

IUPCFY-11
- G - 28

7. Optional Parts
7. OPTIONAL PARTS

DATA
DATAU4
U3

7-1. Optional
Optional parts
line
up for
unit Unit
7-1.
Parts
Line
Upthe
forIndoor
the Indoor
7. OPTIONAL PARTS

High efficiency filter (MERV 8)


PCFY-P15NGMU-E
PCFY-P24,30NGMU-E
PCFY-P36NGMU-E

External heater adaptor

PAC-SE80KF-E
PAC-SE81KF-E
PAC-SE82KF-E

PAC-YU24HT-F
PAC-YU24HT-F
PAC-YU24HT-F

A
B

D
C
A Filter

B Intake Grille

C Knob

D Stopper

7-2.
Efficiency
Filter
PAC-SE-KF-E
8) for PCFY-P-NGMU-E
7-2. High
High efficiency
filter
PAC-SE-KF-E
(MERV(MERV
8) for PCFY-P-NGMU-E
Life
Life span:
span: 2,500hr
2,500hr

*.*. The
which should
should be
becondsidered
condsideredat
atthe
theapplying
installation
The actual
actual dust
dust situation
situation affects
affects the
the filter
filter life
life span,
span,which
site.site.

PCFY-P-NGMU-E

Dust
method)
Dust collection
collection efficiency:
efficiency: 70%
70% (weighing
(weighing method)
Material:
honeycomb weave
weave (Identification:
(Identification: gray
gray yarn
yarnwoven)
woven)
Material: PP
PP fiber
fiber (antibacterial
(antibacterial +
+ mildew-proof),
mildew-proof), honeycomb

Item
Quantity

Filter (large)
1

Filter (small)
PAC-SE80KF-E

PAC-SE81KF-E

8-3/4 x 23-15/16 x 7/16"


(221x608x11mm)

8-3/4 x 11-7/8 x 7/16"


(221x301x11mm)

Shape
PAC-SE82KF-E

Detailed
andand
Service
Manual
(OC343
) )
Detailed installation
installation information
information should
should be
bereferred
referredto
toits
in Technical
the Technical
Service
Manual
(OC343

PCFY-12

PCFY-P-NGMU-E (Feb. 2009)


PCFY-P-NGMU-E

IU - G - 29

7. Optional Parts

DATA U4

7-3. External Heater Adapter PAC-YU24HT


External heater adaptor PAC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Relay circuit

Electric Heater
power source

Remote control Board

Indoor unit
control board

Adapter

White

Red

Red

Electric
Heater

Dip switch
PUHY,PURY-P-TGMU type
SW5-2 "ON"
PUHY,PURY-P-YHMU type
SW5-10 "ON"

CN22
Green

Red

Yellow

CN24

Outdoor unit
control board

PUMY series
SW4-4 "ON"

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below Operation coil


Rated voltage : 12VDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit
R

Wiring diagram

1-phase power
supply

208V, 230V/60Hz

88H

FS1

H1

88H

FS2
FS1

H2
FS1, 2 ----- Thermal fuse

FS2
88H

Control board

H1, H2 ----- Heater


26H

26H --------- Overheat protection


thermostat
88H --------- Electromagnetic contactor

CN24

Quantity

External output cable


2

PCFY-P-NGMU-E

Item

Fan speed setting cable


with resistance
2

Shape

Refer to the Installation Manual (WT04645X02) wiring and installation details.

PCFY-P-NGMU-E (Feb. 2009)

PCFY-13

Wall-mounted

DATA U4

PKFY-P-NAMU-E, NGMU-E, NFMU-E



1. SPECIFICATIONS...................................................................................................................................................PKFY-3
2. EXTERNAL DIMENSIONS......................................................................................................................................PKFY-5
3. Center of Gravity...........................................................................................................................................PKFY-9
4 ELECTRICAL WIRING DIAGRAMS......................................................................................................................PKFY-10
5. SOUND PRESSURE LEVELS..............................................................................................................................PKFY-12
5-1. Sound Pressure Levels...............................................................................................................................PKFY-12
5-2. NC Curves...................................................................................................................................................PKFY-12
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS......................................................................................................PKFY-13
6-1. Temperature Distributions...........................................................................................................................PKFY-13
6-2. Airflow Distributions.....................................................................................................................................PKFY-13
7. OPTIONAL PARTS................................................................................................................................................PKFY-14
7-1. Optional Parts Line Up for the Indoor Unit..................................................................................................PKFY-15
7-2. L-shaped Connection Pipe PAC-SC84PI-E for PKFY-P-NFMU-E...............................................................PKFY-15
7-3. External Heater Adapter PAC-YU24HT.......................................................................................................PKFY-16

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E (Feb. 2009)

PKFY-1

Wall-mounted
Wall mounted

DATA
DATAU4
U3

I.Wall mounted

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

PKFY-P-NAMU-E
PKFY-P-NGMU-E

PKFY-P-NFMU-E
PKFY-P-NFMU-A
Elegant design
design and
and compact
compactdimensions
dimensionsideal
idealfor
foroffices,
offices,stores
storesand
andresidential
residentialuses
uses, etc.
Elegant

needs.
A wide selection for your design and performance needs

Operation is among the quietest available

They are more compact and weigh less than most competitive
units. In addition, they are extremely quiet with one of the
lowest sound ratings available from any manufacturer.

Optimized airflow passage.


Avoid turbo air returning.
Avoid dewing at outlet.

The PKFY auto-vane feature delivers optimal air distribution


the space.
and uniform temperature throughout your
space.

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

All of the performance and design flexibility come in a unit


that is remarkably easy to install and maintain.

Front grille opens for easy filter cleaning

The template and back-mounting


back mounting plate shipped with each
installation a snap.
unit makes application

Front grille
opens out

Wall mounted

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

* Nominal conditions *1,


atinthe
sheet.
*1, *2
*2 are
are referable
referred to
theSpecification
Specification
sheet.

PKFY-2

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E

IU - H - 2

1.
1. Specifications
SPECIFICATIONS

DATA
DATA U4
U3

1. SPECIFICATIONS

Model

PKFY-P06NAMU-E

PKFY-P08NAMU-E

Power source

PKFY-P12NGMU-E

PKFY-P15NGMU-E

1-phase 208-230 V 60Hz

Cooling capacity

*1 BTU / h

6,000

8,000

12,000

(Nominal)

*1 kW

1.8

2.3

3.5

4.4

kW

0.03

0.03

0.07

0.07

Power input
Current input

Heating capacity

*2 BTU / h

(Nominal)

0.15

0.15

0.34

0.34

6,700

9,000

13,500

17,000

*2 kW

2.0

2.6

4.0

5.0

Power input

kW

0.03

0.03

0.07

0.07

Current input

0.15

0.15

0.34

External finish (Munsell No.)

0.34

2.60Y 8.66/0.69

External dimension H x W x D
Net weight

0.70Y 8.59/0.97

in.

11-5/8 x 32-3/32 x 6-1/4

11-5/8 x 32-3/32 x 6-1/4

13-13/32 x 39 x 9-9/32

13-13/32 x 39 x 9-9/32

mm

295 x 815 x 158

295 x 815 x 158

340 x 990 x 235

340 x 990 x 235

19 (9)

19 (9)

36 (16)

36 (16)

lbs (kg)

Heat exchanger
FAN

15,000

Cross fin
Type x Quantity
External

in.WG

static pressure
static
press

Pa

Line flow fan x 1

Line flow fan x 1

Line flow fan x 1

Line flow fan x 1

0.000 (208V)

0.000 (208V)

0.000 (208V)

0.000 (208V)

0.000 (230V)

0.000 (230V)

0.000 (230V)

0.000 (230V)

0.030

0.030

in.WG
Pa
Motor type

1-phase induction motor

Motor output

kW

0.017

0.017

Driving mechanism

Direct-driven

Airflow rate

cfm

(Low-Mid1-Mid2-High)

m3 / min

173-184-198-208

173-184-198-208

283-335-371-406

283-335-371-406

4.9-5.2-5.6-5.9

4.9-5.2-5.6-5.9

8.0-9.5-10.5-11.5

8.0-9.5-10.5-11.5

L/s

82-87-93-98

82-87-93-98

133-158-175-192

133-158-175-192

32-33-35-36 (208-230V)

32-33-35-36 (208-230V)

32-36-40-42 (208-230V)

32-36-40-42 (208-230V)

dB <A>

dB <A>

R410A,R22 CITY MULTI

Sound
pressure
level (Low-Mid1-Mid2-High) dB <A>
Noise level
(Low-Mid1-Mid2-High)

(measured in anechoic room)


Insulation material

Polyethylene foam

Air filter

PP honeycomb

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit


Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

R410A CITY MULTI

R410A CITY MULTI

R410A,R22 CITY MULTI

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

in. (mm)
in. (mm)

I.D. 5/8 (16)

I.D. 5/8 (16)

I.D.13/16
5/8 (16)
I.D.
(20)

I.D.13/16
5/8 (16)
I.D.
(20)

External

in. (mm)

RG01N979

RG01N979

RG01N981

RG01N981

Wiring

RG79N933

RG79N933

RG79N931

RG79N931

Refrigerant cycle
Standard

Document

Installation Manual,Installation Book

attachment

Accessory

Optional parts

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

Remark

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PKFY-P06-15NAMU,NGMU-E

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E,
NGMU-E, NFMU-E

IUPKFY-3
-H-3

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

Model

PKFY-P18NFMU-E

PKFY-P24NFMU-E

Power source

PKFY-P30NFMU-E

1-phase 208-230 V 60Hz

Cooling capacity

*1 BTU / h

18,000

24,000

(Nominal)

*1 kW

5.3

7.0

8.8

kW

0.09

0.09

0.12

Power input
Current input

Heating capacity

*2 BTU / h

(Nominal)

30,000

0.44

0.44

0.58

20,000

27,000

34,000
10.0

*2 kW

5.9

7.9

Power input

kW

0.09

0.09

0.12

Current input

0.44

0.44

0.58

in.

13-13/32 x 55-1/8 x 9-9/32

13-13/32 x 55-1/8 x 9-9/32

13-13/32 x 66-5/32 x 9-9/32

340 x 1,400 x 235

340 x 1,400 x 235

340 x 1,680 x 235

53 (24)

53 (24)

External finish (Munsell No.)

3.4Y 7.7/0.8

External dimension H x W x D

mm
Net weight

lbs (kg)

62 (28)

Heat exchanger

Cross fin

FAN

Type x Quantity
External

in.WG

static
static pressure
press

Pa

Line flow fan x 2

Line flow fan x 2

Line flow fan x 2

0.000 (208V)

0.000 (208V)

0.000 (208V)

0.000 (230V)

0.000 (230V)

0.000 (230V)

in.WG
Pa
Motor type

1-phase induction motor

Motor output

kW

0.045

0.045

0.070

Driving mechanism

Direct-driven

Airflow rate

cfm

494-636

494-636

777-989

(Low-High)

m3 / min

14.0-18.0

14.0-18.0

22.0-28.0

233-300

233-300

367-467

Sound
pressure
level (Low-High)
Noise level
(Low-High)

dB <A>

L/s

39-45 (208-230V)

39-45 (208-230V)

46-49 (208-230V)

(measured in anechoic room)

dB <A>

dB <A>

Insulation material

Polyethylene foam

Air filter

PP honeycomb

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

in. (mm)
in. (mm)

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

I.D. 13/16 (20)

I.D. 13/16 (20)

I.D. 13/16 (20)

RG01N980-1

RG01N980-1

RG01N980-2

RG79N931

RG79N931

RG79N931

Wiring
Refrigerant cycle
attachment

Accessory

Optional parts

3/8 (9.52) Flare


3/8 (9.52) Flare

1/2 (12.7) Flare

in. (mm)

Document

3/8 (9.52) Flare


3/8 (9.52) Flare

5/8 (15.88) Flare

External

Standard

1/4 (6.35) Flare


3/8 (9.52) Flare

Installation Manual,Installation Book

External Heater Adaptor

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

L-Shaped Connection Pipe(15.88)

PAC-SC84PI-E

PAC-SC84PI-E

PAC-SC84PI-E

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PKFY-P18-30NFMU-E

PKFY-4

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E

IU - H - 4

31/32(24.4)

2-1/8(54)

Detailed figure dwg (ABC)


(Knock out hole)
15
)
8)

1-25/32 (45)

3-19/32 (91.5)

3/32(2.5)

13/32(10)
1-11/32(34)

6(R8

R5/1

Knock out hole for


under piping
Knock out hole of 5/8(16)
remocon wiring

(R

12

15)
/32(R
R19
R5/1
6(R
8)

Knock out hole for


left piping

19
/3
2(
R

/16

R5

17-23/32(450)
Gas pipe
20-25/32(520)
Liquid pipe

1-25/32(45)

1(25.5)

Air intake

Air intake
(Direction)

Terminal block

1/2(13)

Knock out hole for


remocon wiring

12-29/32(328)
12-29/32 (328)

16-1/32(407.5)

2-25/32(70.3)

installation plate

3/16(5)

Air outlet

6-7/32(158)

3-17/32(90)
4-1/32(102.5)
4-7/8(124)

19/32(15)

6-1/4(159)
5-1/4(133)
4-13/16(122.5)
3-27/32(97.5)
3-11/32(85)
2-27/32(72.5)
2-3/8(60)
1-7/8(47.5)
7/8(22.5)

3-11/32(85)

8-27/32(225)
8-1/16(205)
6-7/8(175)
6-11/16(170)

3-15/16(100) or more

6-3/32(155)
7-3/32(180)
7-15/32(190)

10-1/4(260)
9-1/4(235)

3-11/32(85)

8-27/32(225)

6-5/8(168)
5-5/16(135)
4-29/32(125)
4-11/32(110)

5-1/8(130) or more

1-3/8(35)
13/32(10)
0
1-3/32(27.5)
1-9/16(40)
2-3/32(53)
2-9/16(65)
3-7/16(87)
4-7/16(113)
5-1/32(128)

Sleeve

Through hole

3.Sleeves are available on the market.

I.D.5/8"(16)

1/4 F
1/2 F

Liquid pipe
Gas pipe
Drain pipe

Refrigerant
piping

Notes 1.Use M10 or W3/8 screw for installation plate.


2.Extension piping side.

Supporting piece

Installation space

Knock of hole

13/32(10)
0
13/32(10)

4-23/32(120)

1-31/32(50)
1-23/32(44)

16-1/32(407.5)

3/16x1-15/32 (4.5x37) 4 holes


3/16x1-9/16 (4.5x40) 4 holes

Details of installation plate


10-1/4(260)

6-11/16(170)
6-7/8(175)
8-1/16(205)
9-1/4(235)

Installation plate

Wiring entrance holes

Air outlet
(Direction)

1-11/16(42.5)

Knock out hole of


right piping

4-9/16(116)

4-11/32(110)

5-3/4 (146)
2-3/8 (60)

1-11/ 32(34)

intake
Air outlet
26-31/32(660) (Drain pipe total 29-29/32(760))

Air
24-13/16(630)
27-3/8(695)

5-29/32(150)

1-5/8(40.5)

Air intake

2-3/8(60)
3/32(2.5)

Air outlet

9-3/4(247.5)

1-15/32(37.4)

7-15/32(190)
6-1/4(159)
6-3/32(155)
4-23/32(120)

11-23/32(298)

1-3/16(30)
0
1-3/16(30)
1-3/4(45)
25/32(20) or more

32-3/32(815)

1-31/32(50)

11-5/8(295)

27/32(21.5)

13/32(10)

1/2(13)
1-31/32 (50)

2-1/8(54) of more
left piping
left-rear piping

30-13/16(783)

5/8 (16)

15

(R

(R

R1

/32

13/32(10)

PKFY-P06,08NAMU-E

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E,
NGMU-E, NFMU-E

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

/3
2

5
R1

3/32(2.5)
5/32(4)

Air intake

7-3/32(180)

11-23/32(298)

Installation plate balance point hole

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATA U4
U3

2. EXTERNAL DIMENSIONS

Drw. : IU-RG01N979
Unit : in(mm)

IUPKFY-5
-H-5

11-5/8(295)

15-15/16(405)

16-17/32(420)

19-1/2(495)

Unit center

14-3/16(360)

2-3/8(60)

R5
2.
5)

Right-rear
piping hole

13-3/8(340)

27-3/4(705) Air outlet

Filter grip

9-1/4(235)

7-15/32(190)

6-5/16(160)

27-9/16(700)
(Flexible hose total length 31-1/2(800))

3/16(5)

15-9/16(395)

2-3/4(70)

22-7/8(581)
17-11/16(449)

Front view (top open the grille)

15-3/4(400)

9-3/16(233)

8-27/32(225)

Auto vane

11-1/32(280)
Air intake

12-Louvers (manual)

Liquid pipe 1/4 F


Gas pipe 1/2 F

Drain hose I.D.1(25)

(Left side piping


1-3/8(35) installation)

10-23/32(272)
12-7/32(310)

9-1/16(230)

7-15/32(190)

5-1/8(130)

0
1-3/8(35)
2-5/32(55)
3-5/32(80)

1-31/32(50)

Lower side

39(990)

3-5/32(80)

1-9/16(40)

1-3/8(35)

Less than 19/32(15)

Knock out hole for right piping


Refrigerant pipe.Drain pipe.
Wiring hole

1-5/16(33)
2-1/8(54)
3-3/8(86)
6-1/32(153)
(Right side piping installation)

Wiring entrance holes

Service panel
(Power supply access)

Knock out hole for under piping


Refrigerant piping.Drain pipe.
Wiring hole

9-1/4(235)

2-3/8(60)

Address board

Right side

9-21/32(245)

28-5/32(715) Air intake


13-3/8(340)
Air intake

3-1/8(80)

Front view

PKFY-P12,15NGMU-E

Through hole

6(

Knock out hole for


right-rear piping

.5)

6(R52

R2-1/1

R2
1
1/

Knock out hole for


left-rear piping

Left-rear
piping hole

for tapping screw

for bolts

11-13/16(300)

Installation plate
balance point hole
3-3/4(95)

Details of installation plate


8-1/16(205)

(Necessary clearance for


Unit installation)

5-29/32(150)
6-11/16(170)
7-15/32(190)

1-31/32(50) or more

9-21/32(245)

13/16(21)
10-1/4(260)

1-13/16(30) or more

9-21/32(245)
2-3/4(70)

Less than 5-1/8(130)

12-19/32(320)
13-19/32(345)

5-29/32(150) or more

7-15/32(190)

7-3/32(180) or more

2-15/16(75)
1-1/4(32)
25/32(20)
0
1-3/8(35)

.5)
(

Right side

19-1/2(495)

2-3/32(53)
3-1/8(79)

Service space required around indoor unit

16-23/32(425)

7-25/32(198)
Air intake
2-3/8(60)
1(25)

Left side

11-1/32(280)

Knock out hole for left piping


Refrigerant pipe.Drain pipe.Wiring hole.

5-5/16(135)
R5
2

/16
-1

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E
R2

2-

.5

9-1/16(230)
8-9/32(210)

52

1-7/32(31)

(R

6
/1

1-11/32(34)

13/16(21)

PKFY-6
2-3/4(70)

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATAU4
U3

Drw. : IU-RG01N981
Unit : in(mm)

IU - H - 6

3-15/16(100)

1-17/32(39)

1-15/32(37)
2-29/32(74)

1-9/16(39)

1-3/16(30)

for bolts

for tapping screws

23/32(18)

35-7/16(900)
23/32(18)
3-19/32(91)

12-1/4(6) holes
for tapping screws

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E,
NGMU-E, NFMU-E
3-17/32(90)

Range for left rear piping hole

24-1/32(610)

12-3/8(314)

3/4(19)

11-7/32(285)

9-21/32(245)

13-3/8(340)

Rear piping hole

1-25/32(45)

1-25/32(45)

9-1/4(235)

Knock out hole for under-piping


Refrigerant pipe /Drain pipe

21-23/32(552) Air outlet

44-3/32(1120)

9-7/16(240)

Louvers(Manual)

Wiring entrance holes


43-11/16(1110) Drain hose

21-23/32(552) Air outlet

9-1/4(235)

Drain hose I.D.1(25)

42-29/32(1090) Air intake

55-1/8(1400)

Lower side Auto vanes

Front view

9-1/4(235)
1-25/32(45)

Under panel(Removable at
left-hand side piping)

Drain hose for


left-hand side piping

31/32(25)

Knock out hole


for left piping

Left side

Drainage range on
right-hand side

Less than 9-27/32(250)

2-29/32(74)

17-29/32(455)

Unit center

38-31/32(990)

1-1/4(32)

1-15/32(37)

1-3/16(30)

8-27/32(225) 9-7/16(240) 7-3/32(180) 11-1/32(280)

Wall fixture

Drainage range on
left hand side

3-27/32(98)

Details of installation plate

Knock out hole for wiring

9-27/32(250) or more

9-1/4(235)

7-3/4(197)

Terminal block

3/8 F
5/8 F

4-3/8(111)

4-7/32(107)

Drain hose

Bolt

Less than 19/32(15)

Knock out hole


for right piping

Through hole

on the market.

Sleeve

1 Liquid pipe
2 Gas pipe

15/16(24)
2-5/32(55)
4-23/32(120)
7-7/32(183)

9-1/4(235)

Right side

PKFY-P18,24NFMU-E

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

5/32(4)

9-27/32(250) or more

1-15/32(37)
2-9/16(65)

1-3/16(30) or more
1-17/32(39)
3-15/16(100)
5/32(4)

1-31/32(50) or more

7-1/4(184)
1-3/16(30)

Air
outlet

13/32(10)
1-3/16(30)
1-3/16(30)

Air
intake

1-5/32(29)
3-1/8(80)

Service space required around indoor unit

11-1/32(280)
2-3/8(60)

2-15/32(62.5)
1/2(13)
1-5/16(34)
1-7/16(36)
1-21/32(42)
2-9/32(58)

Top side

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATA U4
U3

Drw. : IU-RG01N980-1
Unit : in(mm)

IUPKFY-7
-H-7

1-17/32(39)

3-15/16(100)

11-5/8(295)

2-9/16(65)

50(1270)

for tapping screws

23-7/16(595)

Front view

1-25/32(45)

9-1/4(235)

3-9/16(90)

9-1/4(235)

Auto vanes

27-5/16(694) Air outlet

Rear piping hole

1-25/32(45)

9-1/4(235)

66-1/8(1680)

1-25/32(45)

9-1/4(235)

Louvers(Manual)

27-5/16(694) Air outlet

Knock out hole for under-piping


Refrigerant pipe /Drain pipe

Under panel(Removable at
left-hand side piping)

55-1/8(1400)

43-11/16(1110) Drain hose

9-1/4(235)

Right side

Terminal block

Through hole

3/8 F
5/8 F

4-3/8(111)

4-1/32(102)

Bolt

on the market.

Sleeve

Less than 9/16(15)

1 Liquid pipe
2 Gas pipe

1
15/16(24)
2-5/32(55)
4-23/32(120)
7-7/32(183)
9-7/16(240)

Knock out hole


for right piping

9-1/4(235)

Drain hose I.D.1(25)


Wiring entrance holes

53-15/16(1370) Air intake

1-25/32(45)

Lower side

Drain hose for


left-hand side piping

31/32(25)

Range for left rear piping hole

29-17/32(750)

12-3/8(314)

3-19/32(91)

3/4(19)

11-7/32(285)

Knock out hole


for left piping

Left side

9-21/32(245)

Drainage range on
right-hand side

35-7/16(900)

Unit center

2-29/32(74)

Less than 5-29/32(150)

8-27/32(225) 9-7/16(240) 7-3/32(180) 11-1/32(280)

23/32(18)

23/32(18)

Wall fixture

1-15/32(37)
1-1/4(32)

1-15/32(37)

1-3/16(30)

9-27/32(250) or more

Top side

PKFY-P30NFMU-E

for bolts

for tapping screws

3-27/32(98)

Unit out line

2-29/32(74)

1-17/32(39)
1-15/32(37)

1-3/16(30)

Knock out hole for wiring

9-27/32(250) or more

1-31/32(50) or more

Drainage range on
left hand side

5/32(4)

1-3/16(30) or more
3-15/16(100)
5/32(4)

Air
outlet

1-17/32(39)

Air
intake

7-1/4(184)
13/32(10)
1-3/16(30)

11-1/32(280)

Service space required around indoor unit

13-3/8(340)
1-3/16(30)
1-3/16(30)

1-5/32(29)
3-5/32(80)

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E
2-3/8(60)

2-15/32(62.5)
1/2(13)
7-3/4(197)

PKFY-8
1-5/16(34)
1-7/16(36)
1-21/32(42)
2-9/32(58)

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATAU4
U3

Drw. : IU-RG01N980-2
Unit : in(mm)

IU - H - 8

3. Center of Gravity

DATA U4

PKFY-P12,15,36,45,56NGMU-E

Ref.: PKFY_NGMU_COG_USDB_ALL

(mm)[in]
Model name
PKFY-P12NGMU-E
PKFY-P15NGMU-E
PKFY-P36NGMU-E
PKFY-P45NGMU-E
PKFY-P56NGMU-E

W
990 [39]
990 [39]
990 [39]
990 [39]

D
[9-9/32]
[9-9/32]
[9-9/32]
[9-9/32]

235
235
235
235

990 [39]

235 [9-9/32]

340
340
340
340
340

H
[13-13/32]
[13-13/32]
[13-13/32]
[13-13/32]
[13-13/32]

118
118
118
118
118

X
[4-21/32]
[4-21/32]
[4-21/32]
[4-21/32]
[4-21/32]

380
380
380
380
380

Y
[14-31/32]
[14-31/32]
[14-31/32]
[14-31/32]
[14-31/32]

170
170
170
170
170

Z
[6-23/32]
[6-23/32]
[6-23/32]
[6-23/32]
[6-23/32]

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E (Feb. 2009)

PKFY-9

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS

DATA
DATAU4
U3

3. ELECTRICAL WIRING DIAGRAMS

PKFY-P06,08NAMU-E

Drw. : IU-RG79N933

[ LEGEND ]
SYMBOL

NAME

SYMBOL

CIRCUIT BOARD (ADDRESS)

A. B

P. B

NAME

SYMBOL
LEV

LINEAR EXPANSION VALVE

MODE SELECTION

CAPACITOR (FAN MOTOR)

MF

FAN MOTOR

SW5

VOLTAGE SELECTION

F.C

FAN PHASE CONTROL

MV

VANE MOTOR

SW11

ADDRESS SETTING 1ST DIGIT

FUSE

FUSE (6A/250V)

TB2

SW12

ADDRESS SETTING 2ST DIGIT

ZNR

VARISTOR

TB5

TERMINAL
BLOCK

SW14

CONNECTION No.

TH21

THERMISTOR

SW1

SWITCH

M. B

TRANSMISSION

TH22

REMOTE SWITCH
CENTRALLY CONTROL

CN51

TH23

REMOTE INDICATION

CN52

CAPACITY CODE
MODE SELECTION

A.B

5VDC SUPPLY

SW5

(RED) 4
ADDRESS 3
CN43 2

230V

SW1

3RD 2ND 1ST


DIGIT DIGIT DIGIT NO.

LED2

YLW
ORN
BRN

1 2

CN2M
M-NET

1 2 3 (BLU)

1 2

CN3A CN20
(BLU) INTAKE
(RED)

CN53M
POWER BOARD 1 2 3 4 5
(RED)

BLK
YLW
ORN
RED
BRN

SW2

CN35M
POWER BOARD 1 2 3
(BLU)

See fig : 1

M.B

1 2 3

CN35P
MICON
BOARD
(BLU)

5
4
3
2
1

CN53P F.C
MICON
BOARD
(RED)

1 2 3 4 5 6
FAN
(GRN)

BLU

BLU

1 2

1 2 3 4 5

SW3

5
4
3
2
CONNECTION 1
SW14
0

Notes:

1 2

CN29 CN21
GAS LIQUID
(BLK) (WHT)

1 2 3 4 1 2 3 4 5 6 7 8
CN51
CN52
CENTRALLY REMOTE
CN42
CN81
CONTROL INDICATION ADDRESS
ADDRESS
(WHT)
(GRN)
(RED)
(RED)

12345678910 1234

SW12 SW11
0
0

1 2 3 4 5

1 2 3 1 2 3

CN32 CN34
REMOTE (GRN)
SWITCH
(WHT)

ON
OFF

12345678910

(RED) 8
ADDRESS 7
CN82 6

CN5V
(BLU)

RED

CN60
LEV
(WHT)

ORN

1 2 3 4 5 6 1 2 3 4 5

S(SHIELD)

MF

YLW
GRY
BRN

RED
BLU
ORN
YLW

WHT
YLW
ORN
BLU
RED
BRN

M1 M2
TB5

1 2

TB2

GRN/YLW

MV

RED

LEV

TO OUTDOOR UNIT
BC CONTROLLER
ME REMOTE CONTROLLER
DC24-30V

TO MA-REMOTE
CONTROLLER
DC8.7-13V

TH23 TH22 TH21

ORN

SW3

BLK

SWITCH

BLU
WHT

SW2

208V

POWER SUPPLY

INDOOR CONTROLLER BOARD


CONNECTOR

CN32

ON
OFF

NAME

INDOOR POWER BOARD

TO NEXT
INDOOR UNIT

L1
L2
GR

PULL
BOX
FUSE
(15A)

BREAKER
(15A)

1 2 3

POWER SUPPLY
~/N 208-230V 60Hz

CND
(RED)

ZNR

FUSE
250V
6A

LED1

P.B

1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2.In case of connecting MA-Remote controller, please connect MA remote controller cable in an accessory
to the connector 1 2 . (Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbols used in wiring diagram above are,

: terminal block,

: connecter, : direct wire connection.

5.Please set the switch SW5 according to the power supply voltage.
Set SW5 to 230V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 208V side.
6. The setting of the SW2 dip switches differs in the capacity for the detail, refer to the fig : 1.

MODELS

SW2
ON

PKFY-P06NAMU-E OFF

1234

ON

PKFY-P08NAMU-E OFF

1234

LED on indoor board for service

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

Mark

PKFY-10

Meaning

LED1

Main power supply

LED2

Power supply for


MA -Remote controller

Function

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E

IU - H - 9

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS

DATA
DATA U4
U3

PKFY-P12,15NGMU-E
PKFY-P18,24,30NFMU-E

Drw. : IU-RG79N934

[LEGEND]
SYMBOL
I. B

NAME

SYMBOL

INDOOR CONTROLLER BOARD

NAME

CAPACITOR (FAN MOTOR)

SYMBOL

NAME

TH23

THERMISTOR

A. B
SW1

SWITCH

HEATER

LEV

LINEAR EXPANSION VALVE

CN32

REMOTE SWITCH

MF

FAN MOTOR (WITH INNER THERMOSTAT)

CN51

CENTRALLY CONTROL

MV

VANE MOTOR

CN52

REMOTE INDICATION

P.B

INDOOR POWER BOARD

SW5

VOLTAGE SELECTION

CN24

CONNECTOR

CIRCUIT BOARD (ADDRESS)


MODE SELECTION

F.C

FAN PHASE CONTROL

TB2

TERMINAL

POWER SUPPLY

SW11

ADDRESS SETTING 1ST DIGIT

FUSE

FUSE (6A/250V)

TB5

BLOCK

TRANSMISSION

SW12

ADDRESS SETTING 2ND DIGIT

SW2

SWITCH

MA-REMOTE CONTROLLER

SW14

CONNECTION No.

SWC

OPTION SELECTOR

CAPACITY CODE

TB15

SW3

MODE SELECTION

TH21

SW4

MODEL SELECTION

X4

AUX. RELAY (FAN MOTOR)

ZNR

VARISTOR

THERMISTOR

TH22

TO NEXT INDOOR UNIT

P.B AC208-230V

MF
RED
WHT
BLK

(RED)
CNSK
3
2
1

BLK
WHT

I.B

FAN
(WHT) 1 3 5

CND
(RED) 1 3
X4

F.C

X4

LED1
DRAIN
CN31(WHT)

3 2 1

(YLW)
HEATER
CN24

REMOTE CENTRALLY
INDICATION CONTROL
CN52(GRN) CN51(WHT)

1 5

LEV
CN60(WHT)

BRN
RED
ORN
YLW
PNK
BLU

MV

ON
OFF

3RD 2ND
1ST
DIGIT DIGIT DIGIT

CN2D 1
(WHT) 2

BLK
WHT

M-NET 1
CN2M 2
(BLU)

BLU
BLU

CN3A 1
(BLU) 3

ORN
ORN

POWER SUPPLY
~/N 208-230V 60HZ

TB5

TO OUTDOOR UNIT
M2 BC CONTROLLER
ME REMOTE CONTM1 ROLLER DC24-30V
S(SHIELD)

TB15

1
2

TO MA-REMOTE
CONTROLLER
DC8.7-13V

BRN
RED
BLU
ORN
YLW
WHT

5
4
3
2
CONNECTION
1
NO.

ON
OFF

PKFY-P15NGMU-E

ON
OFF

PKFY-P18NFMU-E

ON
OFF

PKFY-P24NFMU-E

ON
OFF

PKFY-P30NFMU-E

ON
OFF

123456
123456
123456
123456
123456

SW3
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF

1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910
1 2 3 4 5 6 7 8 910

SW4
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF

12345
12345
12345

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

PKFY-P12NGMU-E

SW14

TH21 TH22 TH23

SW2

Models

8
7

BREAKER
(15A)

(RED) (WHT) (BLK)


SW4
ON INTAKE LIQUID GAS
CN20 CN21 CN29
OFF
2 1 2 1 2 1 LED2
12345

LEV

ADDRESS
CN82(RED) 6

SW12 SW11 SWC


0

4
3

ADDRESS 2
CN43(RED)

12345678910

FUSE
(15A)

5VDC SUPPLY

230V
SW1

PULL BOX

SW5
208V

REMOTE
SWITCH
CN32(WHT)

1 6 5 4 3 2 1 1

ADDRESS
ADDRESS
SW3
SW2
CN81(RED)
CN42(RED) ON
8 7 6 5 4 3 2 1 4 3 2 1 OFF
123456 12345678910

A.B

TRANS

ZNR

VANE
CN6V(GRN)
6 5 4 3 2 1

DC13.1V
(WHT)
CN2S
2
1

1 3 CNDK
(RED)

FUSE
250V
6A

TB2
RED
L1
BLU
L2
GRN/YLW
GR

12345
12345

Notes:

1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)
3. In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4. Symbol [S] of TB5 is the shield wire connection.
5. Symbols used in wiring diagram above are,

:terminal block,

:connecter.

6. The setting of the SW2/SW3/SW4 dip switches differs in the capacity for the detail, refer to the fig :
7. Please set the switch SW5 according to the power supply voltage.
Set SW5 to 230V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 208V side.

LED on indoor board for service


Mark

Meaning

LED1

Main power supply

LED2

Power supply for


MA -Remote controller

Function

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E,
NGMU-E, NFMU-E

IUPKFY-11
- H - 10

5.
4. Sound
SOUND Pressure
PRESSURE Levels
LEVELS

DATA
DATAU4
U3

5-1.
Pressure
Levels
4-1. Sound
Sound Pressure
Levels
4. SOUND LEVELS

Wall mounted
Operating sound level
(Low-Middle2-Middle1-High)

Unit
Wall

3-1/4 ft
(1.0m)

Model

3-1/4 ft
(1.0m)

Unit : dB(A)

Sound pressure level (A weighted)

PKFY-P06,08NAMU-E

32-33-35-36

PKFY-P12,15NGMU-E

32-36-40-42

PKFY-P18,24NFMU-E

39-45

PKFY-P30NFMU-E

46-49

Measurement location

5-2.
Curves
4-2. NC
NC curves
PKFY-P06,08NAMU-E

PKFY-P12,15NGMU-E

PKFY-P18,24NFMU-E

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

External Static Pressure: 0Pa


Power Source: 208-230V, 60Hz

70.0

High
Low
Middle1
Middle2

65.0
60.0

70.0

60Hz
60Hz
60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

60.0

70.0

60Hz
60Hz
60Hz
60Hz
NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>

15.0
10.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>

Ref.:NC_PKFY-P06,08NAMU-E

High
Low

65.0

20.0

15.0
10.0

High
Low
Middle1
Middle2

65.0

Ref.:NC_PKFY-P12,15NGMU-E

15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>


Ref.:NC_PKFY-P18,24NFMU-E

PKFY-P30NFMU-E
External Static Pressure: 0Pa
Power Source: 208-230V, 60Hz
70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

30.0

NC-30

25.0
20.0
Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20
500

1k

2k

4k

8k

Octave band center frequencies <Hz>


Ref.:NC_PKFY-P30NFMU-E

PKFY-12

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E

IU - H - 11

6.
6. Temperature/Airflow
TEMPERATURE/AIRFLOWDistributions
DISTRIBUTIONS

DATA
DATA U4
U3

6-1.Temperature
Temperature distributions
6-1.
Distributions
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

2
(6' 6-3/4")

2.7
(8' 10-5/16")

27
(81)

1
(3' 3-3/8")

25
(77)

21
(70)

1
(3' 3-3/8")

23
(73)

23
(73)

25
(77)

Height <m(ft)>

Height <m(ft)>

2.7
(8' 10-5/16")

PKFY-P06,08NAMU-E
<Cooling mode>
Horizontal air flow

2
(6' 6-3/4")

3
(9' 10-1/8")

2
(6' 6-3/4")

33
(91)

1
(3' 3-3/8")

23(73)

31
(88)
27 29
(81) (84)

4
(13' 1-1/2")

Floor distance <m(ft)>

<Heating mode>
Downward air flow

25(77)

2
(6' 6-3/4")

3
(9' 10-1/8")

4
(13' 1-1/2")

Floor distance <m(ft)>

Ref.:TD_PKFY-P-NAMU-E_H

PKFY-P12,15NGMU-E
<Cooling mode>

<Heating mode>

2.7

2.7

(8' 10-5/16")

(8' 10-5/16")

27
(81)

25

(77)

2
(6' 6-3/4")

Height <m(ft)>

Height <m(ft)>

27(81)

1
(3' 3-3/8")

Ref.:TD_PKFY-P-NAMU-E_C

21

(70)

23(73)

1
(3' 3-3/8")

29
(84)

31
(88)

23(73)
25(77)

1
(3' 3-3/8")

2
(6' 6-3/4")

3
(9' 10-1/8")

4
(13' 1-1/2")

2
(6' 6-3/4")
27
(81)

35
(95)

1
(3' 3-3/8")
23
(73)

5
5.5
(16' 4-7/8") (18' 9/16")

25
(77)

25(77)

29
(84) 31(88)

1
(3' 3-3/8")

Floor distance <m(ft)>

27(81)
29(84)

31(88)

2
(6' 6-3/4")

3
(9' 10-1/8")

4
(13' 1-1/2")

5
5.5
(16' 4-7/8") (18' 9/16")

Floor distance <m(ft)>

Ref.:TD_PKFY-P-NGMU-E_C10

2.7
8' 10-5/16"

23(73)

33
(91)

Ref.:TD_PKFY-P-NGMU-E_H70

PKFY-P18,24,30NFMU-E
<Cooling mode>
Horizontal air flow

C (F)

23 (73)

1
3' 3-3/8"

21 (70)
25 (77)
23 (73)


aa

1
3' 3-3/8"

Height <m(ft)>

2.7
8' 10-5/16"

2
6' 6-3/4"

3
9' 10-1/8"

PKFY-P18,24,30NFMU-E
<Heating mode>
Downward air flow

4
13' 1-1/2"
Floor Distance <m(ft)>

5
16' 4-7/8"

6
19' 8-3/16"

7
22' 11-11/16"

8
26' 2-15/16"

C (F)

2
6' 6-3/4"

27 (81)

27 (81)
33 (91)

25 (77)
31 (88)

29 (84)

1
3' 3-3/8"
25 (77)


aa

29 31 (88)
(84)

1
3' 3-3/8"

2
6' 6-3/4"

3
9' 10-1/8"

4
13' 1-1/2"

5
16' 4-7/8"

6
19' 8-3/16"

7
22' 11-11/16"

8
26' 2-15/16"

Floor Distance <m(ft)>

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E,
NGMU-E, NFMU-E

IUPKFY-13
- H - 32

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

Height <m(ft)>

25 (77)

2
6' 6-3/4"

6.
6. Temperature/Airflow
TEMPERATURE/AIRFLOWDistributions
DISTRIBUTIONS

DATA
DATAU4
U3

6-2.
Distributions
6-2. Airflow
Airflow distributions
PKFY-P06,08NAMU-E
<Fan mode>
Horizontal air flow

2.7
(8' 10-5/16")
2
(6' 6-3/4")

m/s (ft/s)

2.7
(8' 10-5/16")

0.5(1' 7-11/16")

1
(3' 3-3/8")

Height <m(ft)>

Height <m(ft)>

1
(3' 3-3/8")

3.0(9' 10-1/8")
2.0(6' 6-3/4")

1
(3' 3-3/8")

2
(6' 6-3/4")

3
(9' 10-1/8")

1.0
0.5
(1' 7-11/16") 1.0 (3' 3-3/8")
3
(3' 3- /8")

4
(13' 1-1/2")

m/s (ft/s)

2.0(6' 6-3/4")

1
(3' 3-3/8")

2.7
(8' 10-5/16")

Height <m(ft)>

Height <m(ft)>

0.5(1' 7-11/16")

3.0(9' 10-1/8")

1.0(3' 3-3/8")

1
(3' 3-3/8")

2
(6' 6-3/4")

3
(9' 10-1/8")

4
(13' 1-1/2")

5
5.5
(16' 4-7/8") (18' 9/16")

<Fan mode>
Flow angle : 70

1
(3' 3-3/8")

m/s (ft/s)

3.0
(9' 10-1/8")

0.5
1.0
(1' 7-11/16") (3' 3-3/8") 2.0(6' 6-3/4")

0
0

1
(3' 3-3/8")

Floor distance <m(ft)>

1.0(3' 3-3/8")

2
(6' 6-3/4")

0.5(1' 7-11/16")

3
(9' 10-1/8")

4
(13' 1-1/2")

5
5.5
(16' 4-7/8") (18' 9/16")

Floor distance <m(ft)>

Ref.:AD_PKFY-P-NGMU-E_10

PKFY-P18,24,30NFMU-E
<Fan mode>
Horizontal air flow

4
(13' 1-1/2")

4.0
(13' 1-1/2")

2
(6' 6-3/4")

0.5(1' 7-11/16")

3
(9' 10-1/8")

Ref.:AD_PKFY-P-NAMU-E_2

PKFY-P12,15NGMU-E
<Fan mode>

4.0
(13' 1-1/2")

2
(6' 6-3/4")

Floor distance <m(ft)>

Ref.:AD_PKFY-P-NAMU-E_1

2.7
(8' 10-5/16")

0.5
(1' 7-11/16")

1
(3' 3-3/8")

Floor distance <m(ft)>

2
(6' 6-3/4")

m/s (ft/s)

2
(6' 6-3/4")

3.0(9' 10-1/8")
2.0(6' 6-3/4")
1.0
(3' 3-3/8")

<Fan mode>
Downward air flow

Ref.:AD_PKFY-P-NGMU-E_70

Height <m(ft)>

2
6' 6-3/4"

0.5 (1' 7-5/8")


4.0 (13' 1-1/2"
3.0 (9' 10-1/8")

2.0 (6' 6-3/4")

1
3' 3-3/8"

0.5 (1' 7-5/8")


aa

1
3' 3-3/8"

2
6' 6-3/4"

1.0 (3' 3-3/8")

3
9' 10-1/8"

4
13' 1-1/2"

5
16' 4-7/8"

6
19' 8-3/16"

7
22' 11-11/16"

8
26' 2-15/16"

Floor Distance <m(ft)>

PKFY-P18,24,30NFMU-E
<Fan mode>
Downward air flow
2.7
8' 10-5/16"

Height <m(ft)>

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

2.7
8' 10-5/16"

2
6' 6-3/4"

4.0 (13' 1-1/2")

3.0 (9' 10-1/8")

1
3' 3-3/8"

2.0 (6' 6-3/4")


0.5 (1' 7-5/8")

0.5 (1' 7-5/8")

1.0 (3' 3-3/8")


1.0 (3' 3-3/8")


aa

1
3' 3-3/8"

2
6' 6-3/4"

3
9' 10-1/8"

4
13' 1-1/2"

5
16' 4-7/8"

6
19' 8-3/16"

7
22' 11-11/16"

8
26' 2-15/16"

Floor Distance <m(ft)>

PKFY-14

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E, NGMU-E,
NFMU-E

IU - H - 33

7.
7. Optional
OPTIONAL Parts
PARTS

DATA
DATA U4
U3

7-1. Optional
lineLine
up for
unit
7-1.
Optionalparts
Parts
Upthe
forIndoor
the Indoor
Unit

7. OPTIONAL PARTS

L-Shaped Connection Pipe(15.88)

Condensate pump

External heater adaptor

PAC-SC84PI-E

SI1730-230
EE1750-230
SI1730-230
EE1750-230
SI1730-230
EE1750-230

PAC-YU24HT-F
PAC-YU24HT-F

PKFY-P06,08NAMU-E
PKFY-P12,15NGMU-E
PKFY-P18,24,30NFMU-E

PKFY-P-NFMU-E

Pipe cover provided attached to


indoor unit
Band (large) attached to indoor unit
Connection Pipe

Pipe cover
Tighten using two bands . (Apply heat
insulation processing to flare connection part.)

7-2.
L-shaped
Connection
PAC-SC84PI-E
for PKFY-P-NFMU-E
7-2. L-shaped
connection
pipePipe
PAC-SC84PI-E
for PKFY-P-NFMU-E
This connection pipe is used when refrigerant
pipe (gas pipe) is to be drawn out to the left,
the left rear, the right, or the right rear on the
wall type indoor unit.

Connection Pipe (gas pipe)


1

5/8"
(15.88mm)*
15.88
(5/8")

1 (for gas)
Phosphate deoxidized copper C1220T-OL (JIS H3300)
EPT sponge rubber

Pipe cover
1

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

Item
Quantity

Pipe diameter (mm)


Number of pipes
Pipe material
Heat insulator

Band
2

PAC-SC84PI-E... 15.88 (5/8")


Shape

Detailed
installation information
information should
should be
be referred
referred to
to in
itsthe
Technical
Service
Manual
Detailed installation
Technical
Service
Manual.
* In order to use PAC-SC84PI-E with PKFY-P18, a pipe adjuster must be used (included in PKFY-P18 components).

7-3. Condensate pump EE1750-230


To be conformed.

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E
(Feb. 2009)
PKFY-P-NAMU-E,
NGMU-E, NFMU-E

IUPKFY-15
- H - 34

7. Optional Parts

DATA U4

7-3. External Heater Adapter PAC-YU24HT (For PKFY-P-NGMU, -NFMU)


External heater adaptor PAC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Relay circuit

Electric Heater
power source

Remote control Board

Indoor unit
control board

Adapter

White

Red

Red

Electric
Heater

Dip switch
PUHY,PURY-P-TGMU type
SW5-2 "ON"
PUHY,PURY-P-YHMU type
SW5-10 "ON"

CN22
Green

Red

Yellow

CN24

Outdoor unit
control board

PUMY series
SW4-4 "ON"

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below Operation coil


Rated voltage : 12VDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit

88H

FS1

H1

88H

FS2
FS1

H2

R
1-phase power
supply

208V, 230V/60Hz

Wiring diagram

FS1, 2 ----- Thermal fuse

FS2

H1, H2 ----- Heater


26H

88H
Control board

88H --------- Electromagnetic contactor


CN24

Item
Quantity

External output cable


2

Fan speed setting cable


with resistance
2

PKFY-P-NAMU-E
PKFY-P-NGMU-E
PKFY-P-NFMU-E

Shape

Refer to the Installation Manual (WT04645X02) wiring and installation details.

PKFY-16

26H --------- Overheat protection


thermostat

PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E (Feb. 2009)

Floor-standing (Exposed/Concealed)

DATA U4

PFFY-P-NEMU-E, -NRMU-E

1. SPECIFICATIONS................................................................................................................................................... PFFY-3
2. EXTERNAL DIMENSIONS...................................................................................................................................... PFFY-7
3. Center of Gravity........................................................................................................................................... PFFY-9
4. ELECTRICAL WIRING DIAGRAMS...................................................................................................................... PFFY-10
5. SOUND PRESSURE LEVELS.............................................................................................................................. PFFY-12
5-1. Sound Pressure Levels............................................................................................................................... PFFY-12
5-2. NC Curves................................................................................................................................................... PFFY-12
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS...................................................................................................... PFFY-13
6-1. Temperature Distributions........................................................................................................................... PFFY-13
6-2. Airflow Distributions..................................................................................................................................... PFFY-13
7. OPTIONAL PARTS................................................................................................................................................ PFFY-14
7-1. Optional Parts Line Up for the Indoor Unit.................................................................................................. PFFY-14
7-2. External Heater Adapter PAC-YU24HT....................................................................................................... PFFY-14

PFFY-P-NEMU-E
PFFY-P-NRMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)

PFFY-1

Floor-standing
(Exposed/Concealed)
Floor standing (Exposed
type/Concealed type)

DATA
DATAU4
U3

I.Floor standing (Exposed type/Concealed type)

PFFY-P-NEMU-E
PFFY-P-NRMU-E
PFFY-P-NEMU-E
PFFY-P-NRMU-E
Compact unit provides simple, effective air conditioning in perimeter zones

Less than 9
9" deep, these PFFY floor-standing units are easy
to install in peripheral spaces, yet offer highly efficient airair
conditioning performance.

Dehumidification using the Dry mode


This function keeps humidity at the optimum level in response to changes
in room temperature, preventing over-cooling and dehumidifying the air to
keep it fresh and invigorating.

Perfect for spaces with little or no ceiling space.


Low operating sound and compact size make PFFY ideal for
hotel rooms.

The PFFY offers tremendous flexibility in two distinct versions.

PFFY-P-NEMU-E
PFFY-P-NRMU-E

PFFY-P-NEMU-E
PFFY-P-NEMU-E exposed-type
exposed-type model
modelisisperfect
perfectfor
formost
most
applications
applications and
and requires
requires no
no finish
finish work.
work.
PFFY-P-NRMU-E
large
jobs
requiringa a
PFFY-P-NRMU-E was
was designed
design forfor
large
jobs
requiring
built-in, concealed,
concealed, floor-mounted
floor-mounted unit.
unit.

Floor standing

Nominal cooling cap.*1 BTU/h


Nominal heating cap.*2 BTU/h

P06

P08

P12

P15

P18

P24

P27

P30

P36

P48

P54

P72

P96

0.8HP
6,000
6,700

1.0HP
8,000
9,000

1.3HP
12,000
13,500

1.6HP
15,000
17,000

2.0HP
18,000
20,000

2.5HP
24,000
27,000

2.8HP
27,000
30,000

3.2HP
30,000
34,000

4.0HP
36,000
40,000

5.0HP
48,000
54,000

5.6HP
54,000
60,000

8.0HP
72,000
80,000

10.0HP
96,000
108,000

PFFY-P-NEMU-E
PFFY-P-NRMU-E

* Nominal conditions *1,


atinthe
sheet.
*1, *2
*2 are
are referable
referred to
theSpecification
Specification
sheet.

PFFY-2

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E

IU - I - 2

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

1. SPECIFICATIONS

Model

PFFY-P06NEMU-E

PFFY-P08NEMU-E

Power source

PFFY-P12NEMU-E

PFFY-P15NEMU-E

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW
Power input

kW

Current input

6,000

8,000

12,000

1.8

2.3

3.5

4.4

0.051/0.061

0.051/0.061

0.055/0.067

0.065/0.078

0.25/0.27

0.25/0.27

0.27/0.30

0.32/0.35

6,700

9,000

13,500

17,000

2.0

2.6

4.0

5.0

0.051/0.061

0.051/0.061

0.055/0.067

0.065/0.078

0.25/0.27

0.25/0.27

0.27/0.30

0.32/0.35

External finish

Acrylic painted,MUNSELL(5Y 8/1)

External dimension H x W x D

in.

24-13/16 x 41-11/32 x 8-11/16

24-13/16 x 41-11/32 x 8-11/16

24-13/16 x 46-3/32 x 8-11/16

24-13/16 x 46-3/32 x 8-11/16

630 x 1,050 x 220

630 x 1,050 x 220

630 x 1,170 x 220

630 x 1,170 x 220

51 (23)

51 (23)

56 (25)

58 (26)

mm
Net weight

lbs (kg)

Heat exchanger
FAN

15,000

Cross fin(Aluminium fin and copper tube)


Sirocco fan x 1

Sirocco fan x 1

Sirocco fan x 2

Sirocco fan x 2

External

Type x Quantity
in.WG

static pressure
static
press

Pa

0.018

0.030

Motor type

1-phase induction motor

Motor output

kW

0.015

0.015

Driving mechanism

Direct-driven

Airflow rate

cfm

194-229

194-229

247-317

300-388

(Low-High)

m3 / min

5.5-6.5

5.5-6.5

7.0-9.0

8.5-11.0

92-108

92-108

117-150

142-183

Sound
pressure
level (Low-High)
Noise level
(Low-High)

dB <A>

L/s

36-41 (208V)

36-41 (208V)

37-41 (208V)

38-43 (208V)

(measured in anechoic room)

dB <A>

36-41 (230V)

36-41 (230V)

37-41 (230V)

38-43 (230V)

dB <A>

Insulation material

Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit


Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22 )
Gas

(R410A)
(R22 )

Field drain pipe size


Drawing

R410A CITY MULTI

R410A CITY MULTI

R410A,R22 CITY MULTI

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

in. (mm)
in. (mm)
in. (mm)

O.D. 1-1/32 (26)

External

W660125

Wiring

W660133

Refrigerant cycle
Standard

Document

attachment

Accessory

Optional parts

External Heater Adaptor

R410A,R22 CITY MULTI

Installation Manual,Installation Book


PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PFFY-P06-15NEMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)


PFFY-P-NEMU-E/PFFY-P-NRMU-E

PFFY-3
IU
-I-3

PFFY-P-NEMU-E
PFFY-P-NRMU-E

Installation

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

Model

PFFY-P18NEMU-E

PFFY-P24NEMU-E

18,000

24,000

Power source

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW

5.3

7.0

0.078/0.093

0.096/0.114

0.38/0.42

0.47/0.51

20,000

27,000

5.9

7.9

0.078/0.093

0.096/1.114

Power input

kW

Current input

0.38/0.42

0.47/0.51

in.

24-13/16 x 55-17/32 x 8-11/16

24-13/16 x 55-17/32 x 8-11/16

630 x 1,410 x 220

630 x 1,410 x 220

External finish

Acrylic painted,MUNSELL(5Y 8/1)

External dimension H x W x D

mm
Net weight

lbs (kg)

67 (30)

71 (32)

Heat exchanger
FAN

Cross fin(Aluminium fin and copper tube)


Sirocco fan x 2

Sirocco fan x 2

External

Type x Quantity
in.WG

static
static pressure
press

Pa

kW

0.035

0.063

Airflow rate

cfm

353-459

353-494

(Low-High)

m3 / min

10.0-13.0

10.0-14.0

L/s

167-217

167-233

Motor type

1-phase induction motor

Motor output
Driving mechanism

Direct-driven

Sound
pressure
level (Low-High)
Noise level
(Low-High)

dB <A>

38-43 (208V)

40-46 (208V)

(measured in anechoic room)

dB <A>

38-43 (230V)

40-46 (230V)

dB <A>

Insulation material

Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22)
Gas

(R410A)
(R22)

Field drain pipe size


Drawing

1/4 (6.35) Flare

in. (mm)
in. (mm)

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

1/2 (12.7) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

in. (mm)

O.D. 1-1/32 (26)

External

W660125

Wiring

W660133

Refrigerant cycle
Standard

Document

attachment

Accessory

Optional parts

External Heater Adaptor

Installation Manual,Installation Book


PAC-YU24HT-F

PAC-YU24HT-F

Remark

PFFY-P-NEMU-E
PFFY-P-NRMU-E

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PFFY-P18-24NEMU-E

PFFY-4

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E

IU - I - 4

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

Model

PFFY-P06NRMU-E

PFFY-P08NRMU-E

Power source

PFFY-P12NRMU-E

PFFY-P15NRMU-E

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW
Power input

kW

Current input

6,000

8,000

12,000

1.8

2.3

3.5

4.4

0.051/0.061

0.051/0.061

0.055/0.067

0.065/0.078

0.25/0.27

0.25/0.27

0.27/0.30

0.32/0.35

6,700

9,000

13,500

17,000

2.0

2.6

4.0

5.0

0.051/0.061

0.051/0.061

0.055/0.067

0.065/0.078

0.25/0.27

0.25/0.27

0.27/0.30

0.32/0.35

External finish

Galvanized

External dimension H x W x D

in.

25-3/16 x 34-29/32 x 8-11/16

25-3/16 x 34-29/32 x 8-11/16

25-3/16 x 39-5/8 x 8-11/16

25-3/16 x 39-5/8 x 8-11/16

639 x 886 x 220

639 x 886 x 220

639 x 1,006 x 220

639 x 1,006 x 220

41 (19)

41 (19)

45 (20)

47 (21)

mm
Net weight

lbs (kg)

Heat exchanger
FAN

15,000

Cross fin(Aluminium fin and copper tube)


Sirocco fan x 1

Sirocco fan x 1

Sirocco fan x 2

Sirocco fan x 2

External

Type x Quantity
in.WG

static
static pressure
press

Pa

0.018

0.030

Motor type

1-phase induction motor

Motor output

kW

0.015

0.015

Driving mechanism

Direct-driven

Airflow rate

cfm

194-229

194-229

247-317

300-388

(Low-High)

m3 / min

5.5-6.5

5.5-6.5

7.0-9.0

8.5-11.0

92-108

92-108

117-150

142-183

Sound
pressure
level (Low-High)
Noise level
(Low-High)

dB <A>

L/s

36-41 (208V)

36-41 (208V)

37-41 (208V)

38-43 (208V)

(measured in anechoic room)

dB <A>

36-41 (230V)

36-41 (230V)

37-41 (230V)

38-43 (230V)

dB <A>

Insulation material

Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit


Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22 )
Gas

(R410A)
(R22 )

Field drain pipe size


Drawing

R410A CITY MULTI

R410A CITY MULTI

R410A,R22 CITY MULTI

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/4 (6.35) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

1/2 (12.7) Flare

in. (mm)
in. (mm)
in. (mm)

O.D. 1-1/32 (26)

External

W660126

Wiring

W660133

Refrigerant cycle
Standard

Document

attachment

Accessory

Optional parts

External Heater Adaptor

R410A,R22 CITY MULTI

Installation Manual,Installation Book


PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

PAC-YU24HT-F

Remark

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PFFY-P06-15NRMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)


PFFY-P-NEMU-E/PFFY-P-NRMU-E

PFFY-5
IU
-I-5

PFFY-P-NEMU-E
PFFY-P-NRMU-E

Installation

1.
1. Specifications
SPECIFICATIONS

DATA
DATAU4
U3

Model

PFFY-P18NRMU-E

PFFY-P24NRMU-E

18,000

24,000

Power source

1-phase 208/230 V 60Hz

Cooling capacity

*1 BTU / h

(Nominal)

*1 kW
Power input

kW

Current input

Heating capacity

*2 BTU / h

(Nominal)

*2 kW

5.3

7.0

0.078/0.093

0.096/0.114

0.38/0.42

0.47/0.51

20,000

27,000

5.9

7.9

0.078/0.093

0.096/0.114

Power input

kW

Current input

0.38/0.42

0.47/0.51

in.

25-3/16 x 49-1/16 x 8-11/16

25-3/16 x 49-1/16 x 8-11/16

mm

639 x 1,246 x 220

639 x 1,246 x 220

External finish

Galvanized

External dimension H x W x D
Net weight

lbs (kg)

56 (25)

60 (27)

Heat exchanger
FAN

Cross fin(Aluminium fin and copper tube)


Sirocco fan x 2

Sirocco fan x 2

External

Type x Quantity
in.WG

static
static pressure
press

Pa

kW

0.035

0.063

Airflow rate

cfm

353-459

353-494

(Low-High)

m3 / min

10.0-13.0

10.0-14.0

L/s

167-217

167-233

Motor type

1-phase induction motor

Motor output
Driving mechanism

Direct-driven

Sound
pressure
level (Low-High)
Noise level
(Low-High)

dB <A>

38-43 (208V)

40-46 (208V)

(measured in anechoic room)

dB <A>

38-43 (230V)

40-46 (230V)

dB <A>

Insulation material

Polyethylene foam,Urethane foam

Air filter

Standard filter

Protection device

Fuse

Refrigerant control device

LEV

Connectable outdoor unit

R410A,R22 CITY MULTI

Diameter of

Liquid

(R410A)

refrigerant pipe
(O.D.)

(R22 )
Gas

(R410A)
(R22 )

Field drain pipe size


Drawing

1/4 (6.35) Flare

in. (mm)
in. (mm)

3/8 (9.52) Flare

3/8 (9.52) Flare

3/8 (9.52) Flare

1/2 (12.7) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

5/8 (15.88) Flare

in. (mm)

O.D. 1-1/32 (26)

External

W660126

Wiring

W660133

Refrigerant cycle
Standard

Document

attachment

Accessory

Optional parts

External Heater Adaptor

Installation Manual,Installation Book


PAC-YU24HT-F

PAC-YU24HT-F

Remark

PFFY-P-NEMU-E
PFFY-P-NRMU-E

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Installation

Note :

Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the
Installation Manual.
*1 Nominal cooling conditions

Indoor : 80degF D.B. / 67degF W.B.


(26.7degC D.B. / 19.4degC W.B.)
Outdoor : 95degF D.B.
(35degC D.B.)
Pipe length : 25 ft. (7.6 m)
Level difference : 0 ft. (0 m)

*2 Nominal heating conditions

Unit converter

70degF D.B.

kcal/h = kW x 860

(21.1degC D.B.)

BTU/h = kW x 3,412

47degF D.B. / 43degF W.B.

cfm = m3/min x 35.31

(8.3degC D.B. / 6.1degC W.B.)

lbs = kg / 0.4536

25 ft. (7.6 m)
0 ft. (0 m)

*Above specification data is


subject to rounding variation.

*Due to continuing improvement, above specification may be subject to change without notice.
Ref.: Spec_PFFY-P18-24NRMU-E

PFFY-6

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E

IU - I - 6

(1-31/32)
50

630(24-13/16)

100(3-15/16)

( )
(2-3/8)
60

(4-3/4)
120

Strainer

Drain pan

C
600(23-5/8)
600(23-5/8)
720(28-3/8)
720(28-3/8)
960(37-13/16)
960(37-13/16)

B
640(25-7/32)
640(25-7/32)
760(29-15/16)
760(29-15/16)
1000(39-3/8)
1000(39-3/8)

1410(55-17/32)

1410(55-17/32)

PFFY-P18NEMU-E

PFFY-P24NEMU-E

970(38-1/4)

970(38-1/4)

D
610(24-1/16)
610(24-1/16)
730(28-3/4)
730(28-3/4)

25(1)

10(7/16)

Drain hose(accessory)
O.D.27(1-3/32)
top end O.D.20(13/16)

A
1050(41-11/32)
1050(41-11/32)
1170(46-1/16)
1170(46-1/16)

90(3-9/16)

6(1/4)

35(1-13/32)

35(1-7/16)

Piping
space

170(6-3/4)

220(8-11/16)

(3-1/8)
78

Air filter
(D)

Air inlet

Air outlet

mm(in.)

B(Floor mounting hole pitch)

45(1-25/32)

15(5/8)

80(3-5/32)

C
A

15(5/8)

220(8-11/16)

170(6-3/4)

2X2-12X16(1/2X11/16)

Wall mounting hole

Remote controller
can be built-in.
(Program timer can not be
built-in together.)

2-12X16(1/2X11/16)
Floor mounting hole

10(7/16)

PFFY-P06,08,12,15,18,24NEMU-E

PFFY-7
IU
-I-7

PFFY-P-NEMU-E
PFFY-P-NRMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)


PFFY-P-NEMU-E/PFFY-P-NRMU-E

Model
PFFY-P06NEMU-E
PFFY-P08NEMU-E
PFFY-P12NEMU-E
PFFY-P15NEMU-E

220(8-11/16)

20(13/16)

Note.On Model :18, you would use flare nut


packed with the Indoor Unit, when connecting
the Outdoor Unit for R22.

Level adjusting screw


4 pcs.(attached)

430(16-15/16)

108(4-5/16)
310(12-1/4)
106(4-3/16)

500(19-11/16)
75(3)

)
Floor mounting hole pitch

(1-5/8)
40
21(7/8)
183.5(7-1/4)

(6-5/16)
160

(
(11-13/16)
300
(6-23/32)
170

Air supply grille

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATAU4
U3

2. EXTERNAL DIMENSIONS

Drw. : IU-W660125
Unit : mm(in)

50(1-31/32)

100(3-15/16)

Duct mounting hole

220(8-11/16)

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E
932(36-3/4)
932(36-3/4)

A
886(34-15/16)
886(34-15/16)
1006(39-5/8)
1006(39-5/8)

1246(49-1/16) 1000(39-3/8)

1246(49-1/16) 1000(39-3/8)

PFFY-P18NRMU-E

PFFY-P24NRMU-E

C
572(22-9/16)
572(22-9/16)
692(27-1/4)
692(27-1/4)

29(1-3/16)
720(28-3/8)
720(28-3/8)

970(38-1/4)

F
4
4
5
5

Drain hose(accessory)
O.D.27(1-3/32)
top end O.D.20(13/16)

Strainer

80(3-5/32)

76(3)

Duct mounting hole

Drain pan

E
360(14-3/16)
360(14-3/16)
480(18-15/16)
480(18-15/16)

639(25-3/16)

970(38-1/4)

D
610(24-1/16)
610(24-1/16)
730(28-3/4)
730(28-3/4)

90(3-9/16)

9(3/8)

35(1-13/32)

49(1-15/16)

30(1-3/16)

15(5/8)

mm(in.)

45(1-25/32)
D

Air inlet

Air outlet

B(Floor mounting hole pitch)

Air filter

E
120(4-3/4)

2-12X16(1/2X11/16)
Floor mounting hole

15(5/8)

(5/8)
15
132(5-1/4)

2X2-12X16(1/2X11/16)
Wall mounting hole

167(6-5/8)

PFFY-P06,08,12,15,18,24NRMU-E

Model
PFFY-P06NRMU-E
PFFY-P08NRMU-E
PFFY-P12NRMU-E
PFFY-P15NRMU-E

B
640(25-7/32)
640(25-7/32)
760(29-15/16)
760(29-15/16)

(3-5/16) (3-7/8)
84
98

90(3-9/16)
310(12-1/4)

Note.On Model :18, you would use flare nut


packed with the Indoor Unit, when connecting
the Outdoor Unit for R22.

Level adjusting screw


4 pcs.(attached)

430(16-15/16)

10(7/16)
400(15-3/4)
75(3)

300(11-13/16)
170(6-23/32)
106(4-3/16)

PFFY-8
Floor mounting hole pitch

PFFY-P-NEMU-E
PFFY-P-NRMU-E

2.
2. External
EXTERNAL Dimensions
DIMENSIONS
DATA
DATAU4
U3

Drw. : IU-W660126
Unit : mm(in)

IU - I - 8

3. Center of Gravity

DATA U4

PFFY-P06,08,12,15,18,24NEMU-E

Ref.: PFFY_NEMU_COG_USDB_ALL

Floor hole for fixing

Center of gravity

(mm)[in]
Model name
PFFY-P06NEMU-E
PFFY-P08NEMU-E
PFFY-P12NEMU-E
PFFY-P15NEMU-E
PFFY-P18NEMU-E
PFFY-P24NEMU-E

640
640
760
760
1000
1000

W
[25-7/32]
[25-7/32]
[29-15/16]
[29-15/16]
[39-3/8]
[39-3/8]

100
100
100
100
100
100

L
[3-15/16]
[3-15/16]
[3-15/16]
[3-15/16]
[3-15/16]
[3-15/16]

17
17
17
17
17
17

X
[21/32]
[21/32]
[21/32]
[21/32]
[21/32]
[21/32]

Z
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]

X
[21/32]
[21/32]
[21/32]
[21/32]
[21/32]
[21/32]

Z
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]
335 [13-3/16]

PFFY-P06,08,12,15,18,24NRMU-E

Floor hole for fixing

Center of gravity

(mm)[in]
Model name
PFFY-P06NRMU-E
PFFY-P08NRMU-E
PFFY-P12NRMU-E
PFFY-P15NRMU-E
PFFY-P18NRMU-E
PFFY-P24NRMU-E

640
640
760
760
1000
1000

W
[25-7/32]
[25-7/32]
[29-15/16]
[29-15/16]
[39-3/8]
[39-3/8]

100
100
100
100
100
100

L
[3-15/16]
[3-15/16]
[3-15/16]
[3-15/16]
[3-15/16]
[3-15/16]

17
17
17
17
17
17

PFFY-P-NEMU-E
PFFY-P-NRMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)

PFFY-9

PFFY-10
SW5
8
7

90 1
2
3
654

8
7

SW7

CN62
(White)

123456

1
2
3
4

90 1
2
3
654

(Red)
CN42

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E

Transformer
Electronic linear expan. valve

T
LEV
S.B.
X04~06

CN51

CN41
CN23

CN24

CN25

CN27

CN22

21

(Red)
CN20

31

21

TH22 TH23

31

21

21

21
21

(White)
CN31

(Black)

(White) (Black)
CN21 CN29

(White)

LED2

LEV

654321

654321

654321

(White)
CN60

(White)

3
T

(Red)
CN3T

SYMBOL
LED1
LED2
CN22
CN23
CN24
CN25
CN27
CN32
CN41
CN51
CN52
ZNR,ZNR1

NAME
Power supply (I.B.)
Power supply (Remote controller)
Connector
Connector
Connector
Connector
Connector
Connector (Centrally control)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote indication)
Varistor
SW3(I.B.)
SW4(I.B.)

SYMBOL
TH21
TH22
TH23
SW11(A.B.)
SW12(A.B.)
SW14(A.B.)
SW1(A.B.)
SW5(A.B.)
SW7(A.B.)
SW2(I.B.)

31

(White)
CNT

( )
AC250V F
6.3A T

Switch(for voltage selection)


Switch(for model selection)
Switch(for capacity code)
Switch(for mode selection)
Switch(for model selection)

Switch (connection No.set)


Switch(for mode selection)

Thermistor (piping temp.detection/gas)


Switch (1st digit address set)
Switch (2nd digit address set)

NAME
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)

NOTE;1.The wirings to TB2,TB5,TB15 shown in chained line are field work.


2.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.

TH21

(Red)

8765432 1

(Red)
CN81

LED1

13

(Red)
CND

ZNR

I.B.

S.B.

A.B.

3
L1
L2
G

M2
M1

TO MA REMOTE CONTROLLER

TB2

TB2

I.B.

POWER SUPPLY
~ 208/230V 60Hz

CONTROL BOX

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

TO OUTDOOR UNIT
BC CONTROLLER
ME REMOTE CONTROLLER

TB5 (TRANSMISSION TERMINAL BED)

S(SHIELD)

(Yellow) S.B.
CN1 1

2
1

TB15 (TRANSMISSION TERMINAL BED)

TB5,TB15

DSA1

ZNR1

(Blue)
CN2M

(Blue)
CN3A

PARTS LOCATION

MF

4 321

4 321

1357

(White)
FAN3

XO6 XO5 XO4

(White)

(Yellow) 5 3 1
FAN2

INSIDE SECTION OF CONTROL BOX

PFFY-P06,08,12,15,18,24NEMU-E

Surge absorber board


Aux.relay

NAME
Fan motor
Capacitor (for MF)
Indoor controller board
Address board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T

SYMBOL
MF
C
I.B.
A.B.
TB2
TB5
TB15
F

SYMBOL EXPLANATION

CN52

(White) (Green) (White) (White) (Green) (Yellow) (White) (Red) (Green)

CN32

MODEL 06/08 ONLY

8
7
6
5
4
3
2
1

SW4 SW3 SW2

CN82
(White)

SW12
SW11
SW14
(Connection No.) (2nd digit) (1st digit)

EF012
D
3
C
4
BA
5
9876

SW1

A.B.

PFFY-P-NEMU-E
PFFY-P-NRMU-E

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATAU4
U3

3. ELECTRICAL WIRING DIAGRAMS

Drw. : IU-W660133

IU - I - 9

SW5
8
7

90 1
2
3
654

8
7

SW7

CN62
(White)

123456

90 1
2
3
654

(Red)
CN42

Transformer
Electronic linear expan. valve

T
LEV
S.B.
X04~06

CN51

CN41
CN23

CN24

CN25

CN27

CN22

21

(Red)
CN20

31

21

TH22 TH23

31

21

21

21
21

(White)
CN31

(Black)

(White) (Black)
CN21 CN29

(White)

LED2

LEV

654321

654321

654321

(White)
CN60

(White)

3
T

(Red)
CN3T

SYMBOL
LED1
LED2
CN22
CN23
CN24
CN25
CN27
CN32
CN41
CN51
CN52
ZNR,ZNR1

NAME
Power supply (I.B.)
Power supply (Remote controller)
Connector
Connector
Connector
Connector
Connector
Connector (Centrally control)
Connector (HA terminal-A)
Connector (Centrally control)
Connector (Remote indication)
Varistor

PFFY-P-NEMU-E
PFFY-P-NRMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)


PFFY-P-NEMU-E/PFFY-P-NRMU-E
SW3(I.B.)
SW4(I.B.)

SYMBOL
TH21
TH22
TH23
SW11(A.B.)
SW12(A.B.)
SW14(A.B.)
SW1(A.B.)
SW5(A.B.)
SW7(A.B.)
SW2(I.B.)

31

(White)
CNT

( )
AC250V F
6.3A T

Switch(for voltage selection)


Switch(for model selection)
Switch(for capacity code)
Switch(for mode selection)
Switch(for model selection)

Switch (connection No.set)


Switch(for mode selection)

Thermistor (piping temp.detection/gas)


Switch (1st digit address set)
Switch (2nd digit address set)

NAME
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)

NOTE;1.The wirings to TB2,TB5,TB15 shown in chained line are field work.


2.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.

TH21

(Red)

8765432 1

(Red)
CN81

LED1

13

(Red)
CND

ZNR

I.B.

S.B.

A.B.

3
L1
L2
G

M2
M1

TO MA REMOTE CONTROLLER

TB2

TB2

I.B.

POWER SUPPLY
~ 208/230V 60Hz

CONTROL BOX

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

TO OUTDOOR UNIT
BC CONTROLLER
ME REMOTE CONTROLLER

TB5 (TRANSMISSION TERMINAL BED)

S(SHIELD)

(Yellow) S.B.
CN1 1

2
1

TB15 (TRANSMISSION TERMINAL BED)

TB5,TB15

DSA1

ZNR1

(Blue)
CN2M

(Blue)
CN3A

PARTS LOCATION

MF

4 321

4 321

1357

(White)
FAN3

XO6 XO5 XO4

(White)

(Yellow) 5 3 1
FAN2

INSIDE SECTION OF CONTROL BOX

PFFY-P06,08,12,15,18,24NRMU-E

Surge absorber board


Aux.relay

NAME
Fan motor
Capacitor (for MF)
Indoor controller board
Address board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T

SYMBOL
MF
C
I.B.
A.B.
TB2
TB5
TB15
F

SYMBOL EXPLANATION

8
7
6
5
4
3
2
1

CN52

(White) (Green) (White) (White) (Green) (Yellow) (White) (Red) (Green)

CN32

MODEL 06/08 ONLY

CN82
(White)

SW12
SW11
SW14
(Connection No.) (2nd digit) (1st digit)

EF012
D
3
C
4
BA
5
9876

SW1

A.B.

1
2
3
4

SW4 SW3 SW2

4.
3. Electrical
ELECTRICAL Wiring
WIRING Diagrams
DIAGRAMS
DATA
DATAU4
U3

Drw. : IU-W660133

PFFY-11
IU
- I - 10

5.
4. SOund
SOUND Pressure
PRESSURE Levels
LEVELS

DATA
DATAU4
U3

4-1. Sound
Levels
5-1.
SoundPressure
Pressure
Levels

4. SOUND LEVELS

Operating sound pressure levels


PFFY-P-NEMU,NRMU-E

( Low - High )

Unit : dB (A)
Model

Sound pressure level (A weighted)

PFFY-P06,P08NEMU-E

3-1/4ft.
(1.0m)

PFFY-P12NEMU-E

Measurement location
PFFY-P15,P18NEMU-E

3-1/4ft.
(1.0m)

PFFY-P24NEMU-E

208V

36 - 41

230V

36 - 41

208V

37 - 41

230V

37 - 41

208V

38 - 43

230V

38 - 43

208V

40 - 46

230V

40 - 46

( Low - High )

Unit : dB (A)
Model

Sound pressure level (A weighted)

PFFY-P06,P08NRMU-E
PFFY-P12NRMU-E
* Measured in anechoic room
PFFY-P15,P18NRMU-E
PFFY-P24NRMU-E

208V

36 - 41

230V

36 - 41

208V

37 - 41

230V

37 - 41

208V

38 - 43

230V

38 - 43

208V

40 - 46

230V

40 - 46

4-2. NC
NC curves
5-2.
Curves

External Static Pressure: 0Pa


Power Source: 208,230V 60Hz

70.0

High
Low

65.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

70.0

High
Low

65.0
60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

1k

2k

External Static Pressure: 0Pa


Power Source: 208,230V 60Hz

External Static Pressure: 0Pa


Power Source: 208,230V 60Hz

High
Low

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0

Approximate minimum
audible limit on
continuous noise

15.0
10.0

63

125

250

NC-20

500

1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PFFY-P18NEMU_NRMU-E_WYN B0-4399

PFFY-12

Octave band pressure level (dB) 0dB=20Pa

PFFY-P24NEMU/NRMU-E

65.0

4k

8k

Ref.:NC_PFFY-P12NEMU_NRMU-E_WYN B0-4397

PFFY-P18NEMU/NRMU-E

Octave band pressure level (dB) 0dB=20Pa

PFFY-P-NEMU-E
PFFY-P-NRMU-E

NC-20

500

Octave band center frequencies (Hz)

Ref.:NC_PFFY-P06,08NEMU_NRMU-E_WYN B0-4396

70.0

60Hz
60Hz

70.0

High
Low

65.0

50.0

60Hz
60Hz

60.0

NC-60

55.0
50.0

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0
20.0
15.0
10.0

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PFFY-P15NEMU_NRMU-E_WYN B0-4398

NC-50

45.0
40.0

NC-40

35.0
30.0

NC-30

25.0

10.0

High
Low

65.0

NC-60

55.0

15.0

70.0

60Hz
60Hz

60.0

20.0

Octave band pressure level (dB) 0dB=20Pa

PFFY-P15NEMU/NRMU-E

External Static Pressure: 0Pa


Power Source: 208,230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PFFY-12NEMU/NRMU-E

External Static Pressure: 0Pa


Power Source: 208,230V 60Hz
Octave band pressure level (dB) 0dB=20Pa

PFFY-P06,08NEMU/NRMU-E

Approximate minimum
audible limit on
continuous noise
63

125

250

500

NC-20
1k

2k

4k

Octave band center frequencies (Hz)

8k

Ref.:NC_PFFY-P24NEMU_NRMU-E_WYN B0-4400

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E

IU - I - 11

6.
6. Temperature/Airflow
TEMPERATURE/AIRFLOW Distributions
DISTRIBUTIONS

DATA
DATA U4
U3

6-1. Temperature
Temperature distributions
6-1.
Distributions
6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

<Cooling mode>

<Heating mode>

2
(6' 6-3/4")

2
(6' 6-3/4")

Height m(ft.)

3
(9' 10-1/8")

Height m(ft.)

3
(9' 10-1/8")

1
(3' 3 -3/8")

1
(3' 3 -3/8")

1
(3' 3 -3/8")

2
(6' 6-3/4")

3
(9' 10-1/8")

4
(13' 1-1/2" )

1
(3' 3 -3/8")

2
(6' 6-3/4")

Floor distance m(ft.)

3
(9' 10-1/8")

4
(13' 1-1/2" )

Floor distance m(ft.)

6-2.
Distributions
6-2. Airflow
Airflow distributions
<Cooling mode>

<Heating mode>

Room temp. : 27C(81F)

3.0
(9' 10-1/8")

2
(6' 6-3/4")

3
(9' 10-1/8" )

(5' 1.8
10- 7
/8")

2.0
(6' 6-3/4")

9 /16" )

( 1' 0 . 4
3- 3
/4"
)

1.5
(4' 11-1/16")

1.0
(1 0.
(3' 3-3/8") ' 3- 3/4 4
")
0.5
(1' 7-11/16")

( 1' 0 . 6
11- 5
/8"
)

( 6' 1 . 9
2- 13
/16"
)

(2' 0.9
11- 7
/16"
)
(6' 1.9
2- 13
/16"
)

Distance m(ft.)
3
(9' 10-1/8" )

4
(13' 1-1/2" )

m/s
(ft./s)
0.8
(2' 7-1/2" )

0.79 16")
/
(2' 3-

(2' 1
0.65
7 16")
1- /
(2' 1

Height m(ft.)

.9
) 0

(2' 0.7
5- 1 5
/2"
)

0.6
(1' 11-5/8 " )

2.5
(8' 2-7/16")

2
(6' 6-3/4")

1.33 16" )
/
(4' 3-

-1 /8"

(11 1 0.3
- /3
16"
)

(1' 0.4
3- 3
/4"
)

(5' 1.
6- 15 7
/16"
)

.0 )
) 1' 33- /8"
(3

0.5
(1' 7-11/16")

(5' 1.8
10- 7
/8")

"
1- 5 /16

(11 0.3
- 13
1.0
/1 6"
)( 1
(3' 3-3/8")
5' 1 . 8
0- 7
/8")

( 1' 0 . 4
3- 3
/4"
)

(5' 6

1.5
(4' 11-1/16")

(4' 7

1 .7

(2' 0 . 6
1- 9 5
/1 6"
)

2.0
(6' 6-3/4")

1
(3' 3-3/8")

3.0
(9' 10-1/8")

m/s
(ft./s)

1.4

5
0.71- /2" )
(2' 5

2.5
(8' 2-7/16")

Room temp. : 20C(68F)

4
(13' 1-1/2" )

Height m(ft.)

1
(3' 3-3/8")

Distance m(ft.)

(1' 0.4
3- 3/
4" )

(11 10.3
- /3
16"
)

PFFY-P-NEMU-E
PFFY-P-NRMU-E

PFFY-P-NEMU-E/PFFY-P-NRMU-E (Feb. 2009)


PFFY-P-NEMU-E/PFFY-P-NRMU-E

PFFY-13
IU
- I - 32

7.
7. Optional
OPTIONAL Parts
PARTS

DATA
DATAU4
U3

7-1. Optional
parts
lineLine
up for
the
Indoor
unit
7-1.
Optional
Parts
Up
for
the Indoor
Unit

7. OPTIONAL PARTS

External heater adaptor


adapter
PAC-YU24HT-F
PAC-YU24HT-F

PFFY-P06,08,12,15,18,24NEMU-E
PFFY-P06,08,12,15,18,24NRMU-E

7-2.
External
Heater
Adapter
PAC-YU24HT
7-2. External
heater
adapter
PAC-YU24HT

X
X

Electric
Electric
Heater
Heater

1
1

White
White
Red
Red

2
2
1
1

Red
Red

2
2

Yellow
Yellow

X
X

Red
Red

Green
Green

Electric Heater
Electric
Heater
power source
power source

External heater adaptor PAC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
External
heater
adapter
PAC-YU24HT
a set
of special
wiring
*The
electric
heater
should
be designed isand
prepared
at the
site.parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Indoor unit
Remote control Board
Relay circuit
Indoor
controlunit
board
Adapter
Remote control Board
Relay circuit
control board
Adapter

CN24
CN24

Outdoor unit
Outdoor
unit
control board
control board
Dip switch
Dip
switch
PUHY,PURY-P-TGMU
type
SW5-2 "ON"
SW5-2 "ON"
PUHY,PURY-P-YHMU type
SW5-10 "ON"

CN22
CN22

PUMY series
SW4-4 "ON"

Maximum cable length


Maximum
cable length
is
10 m (32ft)
is 10 m (32ft)

Preparations in the field


Preparations in the field

For
Forrelay
relayXXuse
usethe
thespecifications
specificationsgiven
givenbelow
below Operation
Operation coil
coil
Rated
Ratedvoltage
voltage: :12VDC
12VDC
Power
Powerconsumption
consumption: :0.9W
0.9Wor
orless
less
* *Use
ends of
of the
the relay
relay coil.
coil.
Usethe
thediode
diodethat
thatisisrecommended
recommendedby
bythe
the relay
relay manufacturer
manufacturer at
at both
both ends
The
Thelength
lengthofofthe
theelectrical
electricalwiring
wiringfor
forthe
thePAC-YU24HT
PAC-YU24HT is
is 22 meters
meters (6-1/2
(6-1/2 ft)
ft)
ToToextend
extendthis
thislength,
length,use
usesheathed
sheathed2-core
2-corecable.
cable.
Control
Controlcable
cabletype
type: :CVV,
CVV,CVS,
CVS,CPEV
CPEVor
orequivalent.
equivalent.
22
22
Cable
1.25mm
mm (16
(16to
to22
22AWG)
AWG)
Cablesize
size: 0.5
: 0.5mm
mm~~1.25
Don't
Dontextend
extendthe
thecable
cablemore
morethan
than10
10meters
meters (32ft)
(32ft)
Recommended
Recommendedcircuit
circuit

Wiring
Wiringdiagram
diagram

1-phase
1-phasepower
power
supply
supply
208V,
208V,230V/60Hz
230V/60Hz

RR
SS
RR
SS

88H
88H

FS1
FS1

H1
H1

88H
88H

FS2
FS2
FS1
FS1

H2
H2
FS1, 22 ---------Thermal
Thermalfuse
fuse
FS1,

FS2
FS2
88H
88H

Controlboard
board
Control

26H
26H

H1, H2
H2---------Heater
Heater
H1,
26H
26H-----------------Overheat
Overheatprotection
protection
thermostat
thermostat
88H
88H-----------------Electromagnetic
Electromagneticcontactor
contactor

CN24
CN24

Item
Item
Quantity
Quantity

Externaloutput
outputcable
cable
External

22

Fanspeed
speedsetting
setting cable
cable
Fan
withresistance
resistance
with

22

Shape
Shape

PFFY-P-NEMU-E
PFFY-P-NRMU-E

Wiing
and Installation
should be refrerred
to installation
its Installation
Manual. (WT04645X02)
Refer
todetails
the Installation
Manualdetails
(WT04645X02)
wiring and
details.

PFFY-14

PFFY-P-NEMU-E/PFFY-P-NRMU-E
(Feb. 2009)
PFFY-P-NEMU-E/PFFY-P-NRMU-E

IU - I - 33

Vertical-Concealed

DATA U4

PVFY-P-E00A
1. SPECIFICATIONS...................................................................................................................................................PVFY-3
2. EXTERNAL DIMENSIONS......................................................................................................................................PVFY-4
3. ELECTRICAL WIRING DIAGRAMS........................................................................................................................PVFY-7
4. Fan Characteristic Curves.........................................................................................................................PVFY-8
5. OPTIONAL PARTS................................................................................................................................................PVFY-11
5-1. Optional Parts Line Up for the Indoor Unit..................................................................................................PVFY-11
5-2. External Heater Adapter PAC-YU25HT.......................................................................................................PVFY-11

DATA U4
PVFY-P-E00A

Manufactured for Mitsubishi Electric & Electronics USA

PVFY-P-E00A (Feb. 2009)

PVFY-1

vERTICAL-cONCEALED

DATA U4

PVFY-P-E00A
I.Ceiling mounted(Built-in type)

Other features include:


An adjustable blower static pressure from a
factory set 0.30" W.G. to 0.50" W.G.
The blower includes three fan speeds
selectable at the remote controller, allowing the
occupant to fine tune the occupants comfort.
High efficiency DC motors and a forward
curved blower provide quiet, efficient operation.
A standard plug-in connection allows easy
integration with auxiliary heat when using the
optional relay kit.
The control board allows an easy connection
for a condensate overflow safety switch.
The cabinets are constructed of heavygauge pre-printed steel with one inch insulation
providing an R-4.2 insulating value.
Linear expansion valve (LEV) modulates
capacity to meet load requirements.

Ideal for closet or attic applications

The vertical air hander is ideal for installations in closets or equipment


rooms where space is limited. The air handler also has a side drain pan,
allowing it to be installed in a horizontal left position. The vertical air handler
can be connected to a system with all other CITY MULTI indoor units for
complete system design flexibility.
Vertical Airflow

PVFY-P-E00A

Horizontal Left Airflow

Vertical concealed
Nominal cooling cap. *1
Nominal heating cap. *2
PVFY-P-E00A

BTU/h
BTU/h

P06
0.8HP
6,000
6,700

P08
1.0HP
8,000
9,000

P12
1.3HP
12,000
13,500

P15
1.6HP
15,000
17,000

P18
2.0HP
18,000
20,000

P24
2.5HP
24,000
27,000

P27
2.8HP
24,000
30,000

P30
3.2HP
30,000
34,000

P36
4.0HP
36,000
40,000

P48
5.0HP
48,000
54,000

P54
5.6HP
54,000
60,000

P72
P96
8.0HP 10.0HP
72,000 96,000
80,000 100,000

* Nominal conditions *1, *2 are referred to in the Specification sheet.

PVFY-2

PVFY-P-E00A (Feb. 2009)

Manufactured for Mitsubishi Electric & Electronics USA

1. Specifications

DATA U4
PVFY Specifications

Model Name

PVFYP12E00A

PVFYP18E00A

PVFYP24E00A

PVFYP30E00A

Cooling Capacity

Btu/h *1

Heating Capacity

Current

Btu/h *1

Cooling

12,000

18,000

24,000

30,000

20,000

27,000

34,000

40,000

54,000

60,000

0.280 / 0.280

0.258 / 0.258

0.379 / 0.379

0.324 / 0.324

0.362 / 0.362

0.410 / 0.410
0.410 / 0.410

Heating

kW

0.171 / 0.171

0.280 / 0.280

0.258 / 0.258

0.379 / 0.379

0.324 / 0.324

0.362 / 0.362

0.69 / 0.61

1.48 / 1.31

1.48 / 1.31

2.38 / 2.11

1.93 / 1.71

2.27 / 2.01

2.83 / 2.51

Heating

0.69 / 0.61

1.48 / 1.31

1.48 / 1.31

2.38 / 2.11

1.93 / 1.71

2.27 / 2.01

2.83 / 2.51

0.86 / 0.76

1.85 / 1.64

1.85 / 1.64

2.97 / 2.64

2.41 / 2.14

2.84 / 2.51

3.53 / 3.14

15

Height

Inches

42-3/4

48

Width

Inches

17-3/4

21

Depth

Inches

Unit

Pounds

Fan
External
Static
Pressure

88

98

21-3/4

108

115

120

160

168

Forward Curved Blower x 1


0.30
ESP

243-320-376

385-481-531

483-636-705

637-800-886

784-9541 ,057

982-1,2681,405

1,114-1,4261,576

0.50
ESP

202-249-346

402-485-520

560-632-713

725-815-873

880-9911,033

1.162-1,3031,438

1,360-1,4971,570

In. WG

0.30 / 0.50 (Selectable)


High-efficiency DC

Motor Type

Outdoor:

24-1/2

21

Filter and rack - field-supplied

Air Filter

Indoor:

58-3/4

Cross Fin (Aluminum Plate Fin and Copper Tube)

Airflow
Rate *2

Note:

54,000

13,500

Type x Qty.

Drain Pipe
Dimension

48,000

0.171 / 0.171

Heat Exchanger

Refrigerant
Pipe
Dimensions

36,000

kW

MCA (208 / 230V)

Net Weight

PVFYP54E00A

Cooling

MOCP

Dimensions

PVFYP48E00A

208/230V, 1-phase, 60Hz

Power Source

Power
Consumption

PVFYP36E00A

Low
Pressure
(Brazed)

Inches

1/2

5/8

High
Pressure
(Brazed)

Inches

1/4

3/8

Primary

3/4 FPT
Inches

Secondary

DATA U4

3/4 FPT

*1 Nominal cooling conditions


80degF D.B./ 67degF W.B.
(26.7degC D.B./ 19.4degC W.B.)

*2 Nominal heating conditions


70degF D.B.
(21.1degC D.B.)

95degF D.B. (35degC D.B.)

47degF D.B./ 43degF W.B.


(8.3degC D.B./ 6.1degC W.B.)

Pipe length:
25ft.(7.6m)
25ft.(7.6m)
Level difference:
0ft.(0m)
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.

Unit converter
kcal =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.

PVFY-P-E00A

Ventilation Air: Providing sufficient ventilation air is an important part of every building design.
ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

Manufactured for Mitsubishi Electric & Electronics USA

PVFY-P-E00A (Feb. 2009)

PVFY-3

DATA U4

PVFY-P-E00A

2. EXTERNAL DIMENSIONS

PVFY-4

PVFY-P-E00A (Feb. 2009)

Manufactured for Mitsubishi Electric & Electronics USA

2. EXTERNAL DIMENSIONS

DATA U4

DATA U4
PVFY-P-E00A

Manufactured for Mitsubishi Electric & Electronics USA

PVFY-P-E00A (Feb. 2009)

PVFY-5

DATA U4

PVFY-P-E00A

2. EXTERNAL DIMENSIONS

PVFY-6

PVFY-P-E00A (Feb. 2009)

Manufactured for Mitsubishi Electric & Electronics USA

B CD

F 0 12

SW2

Manufactured for Mitsubishi Electric & Electronics USA

PVFY-P-E00A (Feb. 2009)

PVFY-7

CN52

0 1

(Green)

SW12

NAME

0 1

(White)

SW11

SW1

(1st digit)

LED1

LED2

21

TH22

21

CN60(White)

NAME

LEV

65 4 3 21

CN3T(Red)
3

Connector
Connector
Connector
Connector
Connector
Connector (central control)
Connector (HA terminal-A)
Connector (central control)
Connector (remote indication)
Power supply (I.B.)
Power supply (Remote controller)

2 1

NOTE: 1.The wirings to TB2,TB5,TB15 shown in chained line are field work.
2.Mark indicates terminal bed, connector, board insertion
connector or fastening connector of control board.

SYMBOL
CNV
CN22
CN24
CN25
CN27
CN32
CN41
CN51
CN52
LED1
LED2

TH23

21

CN20(Red) CN21(White) CN29(Black) CN31(White)

TH21

SW3

(2nd digit)

(Green)

(Yellow)

CN25
(White)

CN32

CN22

Fan motor
Capacitor (for MF)
Indoor controller board
Power source terminal bed
Transmission terminal bed
Transmission terminal bed
Fuse AC250V 6.3A T
Varistor
Transformer
Electronic linear expan. valve
Thermistor (inlet temp.detection)
Thermistor (piping temp.detection/liquid)
Thermistor (piping temp.detection/gas)
Switch (1st digit address set)
Switch (2nd digit address set)
Switch (connection No.set)
Switch (for mode selection)
Switch (for capacity code)
Switch(for mode selection)
Switch(for model selection)
Switch(for voltage selection)
Switch(for model selection)
Switch(for mode selection 3)
Aux.relay
Terminal

PVFY-P-E00A

SYMBOL
MF
C
I.B.
TB2
TB5
TB15
F901
ZNR1,ZNR901
T
LEV
TH21
TH22
TH23
SW11
SW12
SW14
SW1
SW2
SW3
SW4
SW5
SW7
SW8
X01,X04 X07
<T1>,T2,T3

SYMBOL EXPLANATION

SW4 SW7

(Connection No.)

SW14

7 8 9A

345
6

SW5 SW8

(White)

CN27 CN41

5 6

(Red)

7 8

(White)

7 8

CN24

5 6

CN51

2 3

31

CNP(Blue)

5 3 1

G
N

3
4
5

C
2

FAN MOTOR

24 VAC

208/230V 60Hz

Ground

N
4
5

L
G
3

C
2

FAN MOTOR

For field selected .50 esp, change low


voltage connections as shown

24 VAC

24 VAC

24 VAC

L2

TB2
L1

M2
M1

For 208V power supply,


switch the transformer
lead marked 230V with
the one marker 208V.
Reattach wire nut to bare
wire.

POWER SUPPLY
208/230V 60Hz

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

TO OUTDOOR UNIT
BC CONTROLLER
REMOTE CONTROLLER

TB5 (TRANSMISSION TERMINAL BED)

TB15 (TRANSMISSION TERMINAL BED)


2
TO MA REMOTE
1
CONTROLLER
S(SHIELD)

24 Volts AC

2
1

3
1

208/230V 60Hz

As shipped
.30 esp connection

24 VAC

24 VAC

R3

Low

DSA1

CN2M
(Blue)
ZNR1

CN3A
(Blue)
F 901
AC250V
6.3A T

I.B.

CND(Red)

24 VAC

(White)
CN90
1 3 5 79

24 VAC

R2

Med.

R1

31

High

(White)
CNT

X01 X06 X07 X05 X04 ZNR901

CN7V(White)

INSIDE SECTION OF CONTROL BOX

208 V

2 3

L2

DATA U4
230 V

5 4 3 2 1

3. Electrical
PVFY-P12, P18,Wiring
P24, P30,Diagram
P36, P48, P54E00A
DATA U4

4. Fan Characteristic Curves

DATA U4

PVfY-P12e00a

PVfY-P12e00a

0.30 [in. Wg] setting

0.50 [in. Wg] setting

500

500

450

450

400

Airflow [cfm]

550

Airflow [cfm]

550

400

high

350

350

Medium

300

high

300

250

Low

200
150

250

Medium

200

Low

150

0.1

0.2

0.3

0.3

static Pressure [in. Wg]

PVfY-P18e00a

PVfY-P18e00a

0.30 [in. Wg] setting

0.50 [in. Wg] setting

700

700

650

650

600

Medium

450

Airflow [cfm]

Airflow [cfm]

high

500

550
high

500
Medium

450

400

Low

Low

400

350
300

350

0.1

0.2

0.3

0.3

static Pressure [in. Wg]

0.4

PVfY-P24e00a

PVfY-P24e00a
0.50 [in. Wg] setting

800

800

750

750
high

700

Airflow [cfm]

high

Airflow [cfm]

0.5

static Pressure [in. Wg]

0.30 [in. Wg] setting

700

PVFY-P-E00A

0.5

600

550

650

650

Medium

Medium

600

600

Low

550

550
500

Low

500
450

450
400

400

0.1

0.2

static Pressure [in. Wg]

PVFY-8

0.4

static Pressure [in. Wg]

PVFY-P-E00A (Feb. 2009)

0.3

0.3

0.4

0.5

static Pressure [in. Wg]

Manufactured for Mitsubishi Electric & Electronics USA

4. Fan Characteristic Curves

DATA U4

PVfY-P30e00a

PVfY-P30e00a

0.30 [in. Wg] setting

0.50 [in. Wg] setting

1000

1000

950

950

900

900

high

Medium

800
750

Airflow [cfm]

Airflow [cfm]

high

850

850
Medium
800
750
Low

700

700

650

650

Low

600

600

0.1

0.2

0.3

0.3

static Pressure [in. Wg]

PVfY-P36e00a

PVfY-P36e00a

0.30 [in. Wg] setting

0.50 [in. Wg] setting

1150

1150

1100

1100

high

1050

0.5

1050
high

Airflow [cfm]

Airflow [cfm]

0.4

static Pressure [in. Wg]

1000

1000
Medium

950
900

Medium

950
900
Low

850

850

800
750

800

Low

DATA U4
0.1

750

0.2

0.3

0.3

0.4

0.5

static Pressure [in. Wg]

static Pressure [in. Wg]

PVfY-P48e00a

PVfY-P48e00a

0.30 [in. Wg] setting

0.50 [in. Wg] setting

1650

1750

1600

1700

1550

1650
1600

1500

1550

Airflow [cfm]

1350

1500
1450

high

1400

1300

1350

Medium

1250

Medium

1300
1250

1200

1200

1150

Low

1150

1100

1100

1050

1050

1000

Low

950

1000
950

0.1

0.2

0.3

static Pressure [in. Wg]

Manufactured for Mitsubishi Electric & Electronics USA

0.3

0.4

0.5

static Pressure [in. Wg]

PVFY-P-E00A (Feb. 2009)

PVFY-9

PVFY-P-E00A

high

1400

Airflow [cfm]

1450

4. Fan Characteristic Curves

DATA U4

PVfY-P54e00a

PVfY-P54e00a

0.30 [in. Wg] setting

0.50 [in. Wg] setting

1750

1750

1700

1700
1650

1650
1600

high

1550

1600
high

Airflow [cfm]

1500

Airflow [cfm]

1550
1500

1450

Medium

1400

Medium

1450
1400

1350

Low

1350

1300

1300

1250

1250

1200

1200

1150
Low

1100
1050

1150
1100
1050

0.1

0.2

0.3

0.4

0.5

static Pressure [in. Wg]

PVFY-P-E00A

static Pressure [in. Wg]

0.3

PVFY-10

PVFY-P-E00A (Feb. 2009)

Manufactured for Mitsubishi Electric & Electronics USA

5. Optional Parts

DATA U4

5-1. Optional Parts Line Up for the Indoor Unit


Model

CN24 Relay Kit

External Heat Adaptor

PVFY-P12~54E00A

CN24RELAY-KIT-CM

PAC-YU25HT

5-1. External Heat Adapter PAC-YU25HT


External heater adaptor PAC-YU25HT is a set of special wiring parts for controlling the electric heater* with the air conditioner system.
*The electric heater should be designed and prepared at the site.
A basic connection method is shown as follows:(For details, refer to its Installation Manual.)
Relay circuit

Electric Heater
power source

Remote control Board

Indoor unit
control board

Adapter

White

2
1

X
Electric
Heater

Dip switch
PUHY,PURY-P-TGMU type
SW5-2 "ON"
PUHY,PURY-P-YHMU type
SW5-10 "ON"

CN4Y
White

Red

Yellow

CN24

Outdoor unit
control board

PUMY series
SW4-4 "ON"

(for use with the panel heater)

Maximum cable length


is 10 m (32ft)

Preparations in the field

For relay X use the specifications given below Operation coil


Rated voltage : 12VDC
Power consumption : 0.9W or less
* Use the diode that is recommended by the relay manufacturer at both ends of the relay coil.
The length of the electrical wiring for the PAC-YU25HT is 2 meters (6-1/2 ft)
To extend this length, use sheathed 2-core cable.
Control cable type : CVV, CVS, CPEV or equivalent.
Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)
Don't extend the cable more than 10 meters (32ft)
Recommended circuit
R
1-phase power
supply

208V, 230V/60Hz

Wiring diagram

Quantity

FS1

H1

88H

FS2
FS1

H2
FS1, 2 ----- Thermal fuse

FS2
88H

DATA U4
Item

88H

26H

Control board

H1, H2 ----- Heater


26H --------- Overheat protection
thermostat
88H --------- Electromagnetic contactor

CN24

External output cable


2

Connector
(for use with the panel heater)
3

Shape

Manufactured for Mitsubishi Electric & Electronics USA

PVFY-P-E00A (Feb. 2009)

PVFY-P-E00A

Wiring details and Installation details should be refrerred to its Installation Manual. (WT05383X01)

PVFY-11

NOMINAL CAPACITY TABLES

DATA U4

Outdoor UNit to Indoor Unit Nominal Capacity Tables



1. Capacity Tables in Fahrenheit......................................................................................................................NCT-2

1-1. Cooling and Heating Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A.................................................NCT-2

1-1-1. Cooling Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A...........................................................NCT-2

1-1-2. Heating Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A.........................................................NCT-13

1-2. Cooling and Heating Capacity with PUHY-P120~144, PURY-P120T(S)HMU-A/Y(S)HMU-A.......................NCT-14

1-2-1. Cooling Capacity with PUHY-P120~144, PURY-P120T(S)HMU-A/Y(S)HMU-A..................................NCT-14

1-2-2. Heating Capacity with PUHY-P120~144, PURY-P120T(S)HMU-A/Y(S)HMU-A.................................NCT-25

1-3. Cooling and Heating Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A....................NCT-26

1-3-1. Cooling Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A..............................NCT-26

1-3-2. Heating Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A..............................NCT-37

1-4. Cooling and Heating Capacity with PUHY-P264~360TSHMU-A/YSHMU-A.................................................NCT-38

1-4-1. Cooling Capacity with PUHY-P264~360TSHMU-A/YSHMU-A...........................................................NCT-38

1-4-2. Heating Capacity with PUHY-P264~360TSHMU-A/YSHMU-A...........................................................NCT-49

1-5. Cooling and Heating Capacity with PUMY-P36~48NHMU-A........................................................................NCT-50

1-5-1. Cooling Capacity with PUMY-P36~48NHMU-A..................................................................................NCT-50

1-5-2. Heating Capacity with PUMY-P36~48NHMU-A..................................................................................NCT-61

2. Capacity Tables in CelSius............................................................................................................................NCT-62



2-1. Cooling and Heating Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A...............................................NCT-62

2-1-1. Cooling Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A.........................................................NCT-62

2-1-2. Heating Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A.........................................................NCT-73

2-2. Cooling and Heating Capacity with PUHY-P120~144, PURY-P120TSHMU-A/YSHMU-A............................NCT-74

2-2-1. Cooling Capacity with PUHY-P120~144, PURY-P120TSHMU-A/YSHMU-A......................................NCT-74

2-2-2. Heating Capacity with PUHY-P120~144, PURY-P120TSHMU-A/YSHMU-A......................................NCT-85

2-3. Cooling and Heating Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A....................NCT-86

2-3-1. Cooling Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A..............................NCT-86

2-3-2. Heating Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A..............................NCT-97

2-4. Cooling and Heating Capacity with PUHY-P264~360TSHMU-A/YSHMU-A.................................................NCT-98

2-4-1. Cooling Capacity with PUHY-P264~360TSHMU-A/YSHMU-A...........................................................NCT-98

2-4-2. Heating Capacity with PUHY-P264~360TSHMU-A/YSHMU-A.........................................................NCT-109

2-5. Cooling and Heating Capacity with PUMY-P36~48NHMU-A......................................................................NCT-110

2-5-1. Cooling Capacity with PUMY-P36~48NHMU-A................................................................................NCT-110

2-5-2. Heating Capacity with PUMY-P36~48NHMU-A................................................................................NCT-121

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-1

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1. Cooing and Heating Capacity with PUHY, PURY-P72~96THMU-A/YHMU-A


1-1-1. Cooling CapacityPUHY, PURY-P72~96THMU/YHMU-A with PEFY-P-NMSU-E
CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

NOMINAL
CAPACITY
TABLES

24

Entering air temp.


.
71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,400

5,100

5,800

5,100

6,200

5,300

6,500

5,300

6,700

5,500

7,200

5,500

7,600

5,700

73.0

5,400

5,100

5,800

5,100

6,200

5,300

6,500

5,300

6,700

5,500

7,200

5,500

7,600

5,700

77.0

5,400

5,100

5,800

5,100

6,200

5,300

6,500

5,300

6,600

5,500

7,100

5,500

7,500

5,600

82.0

5,400

5,000

5,700

5,100

6,100

5,300

6,400

5,300

6,500

5,500

6,900

5,400

7,300

5,600

86.0

5,300

5,000

5,600

5,000

5,900

5,200

6,300

5,200

6,400

5,400

6,800

5,400

7,200

5,500

91.0

5,200

5,000

5,500

5,000

5,800

5,200

6,100

5,200

6,200

5,400

6,700

5,300

7,000

5,500

95.0

5,100

4,900

5,400

5,000

5,700

5,100

6,000

5,200

6,100

5,300

6,600

5,300

6,900

5,400

100.0

5,100

4,900

5,300

4,900

5,600

5,100

5,900

5,100

6,000

5,300

6,400

5,200

6,700

5,400

104.0

5,000

4,900

5,200

4,900

5,500

5,000

5,800

5,100

5,900

5,300

6,300

5,200

6,600

5,300

110.0

4,900

4,800

5,100

4,800

5,300

5,000

5,600

5,000

5,700

5,200

6,100

5,100

6,400

5,300

68.0

7,100

6,500

7,600

6,600

8,200

6,900

8,600

6,900

8,800

7,100

9,500

7,100

10,100

7,300

73.0

7,100

6,500

7,600

6,600

8,200

6,900

8,600

6,900

8,800

7,100

9,500

7,100

10,100

7,300

77.0

7,100

6,500

7,600

6,600

8,200

6,900

8,600

6,900

8,800

7,100

9,400

7,000

9,900

7,200

82.0

7,100

6,500

7,500

6,500

8,000

6,800

8,400

6,800

8,600

7,000

9,200

7,000

9,700

7,100

86.0

7,000

6,400

7,400

6,500

7,900

6,700

8,300

6,800

8,400

7,000

9,000

6,900

9,500

7,100

91.0

6,900

6,400

7,200

6,400

7,700

6,700

8,100

6,700

8,200

6,900

8,800

6,800

9,300

7,000

95.0

6,800

6,400

7,100

6,400

7,600

6,600

8,000

6,600

8,100

6,900

8,700

6,800

9,100

7,000

100.0

6,700

6,300

7,000

6,300

7,400

6,500

7,800

6,600

7,900

6,800

8,500

6,700

8,900

6,900

104.0

6,600

6,300

6,900

6,300

7,200

6,500

7,700

6,500

7,800

6,700

8,300

6,700

8,700

6,800

110.0

6,500

6,200

6,700

6,200

7,000

6,400

7,500

6,400

7,600

6,700

8,100

6,600

8,500

6,800

68.0

10,700

8,600

11,500

8,800

12,300

9,100

13,000

9,100

13,300

9,400

14,300

9,300

15,100

9,500

73.0

10,700

8,600

11,500

8,800

12,300

9,100

13,000

9,100

13,300

9,400

14,300

9,300

15,100

9,500

77.0

10,700

8,600

11,500

8,800

12,300

9,100

13,000

9,100

13,200

9,400

14,100

9,200

14,900

9,400

82.0

10,700

8,600

11,300

8,700

12,000

9,000

12,700

9,000

12,900

9,200

13,800

9,100

14,600

9,300

86.0

10,500

8,500

11,100

8,600

11,800

8,900

12,500

8,900

12,700

9,200

13,600

9,000

14,300

9,200

91.0

10,400

8,400

10,900

8,500

11,600

8,800

12,200

8,800

12,400

9,000

13,300

8,900

14,000

9,100

95.0

10,200

8,400

10,700

8,400

11,400

8,700

12,000

8,700

12,200

9,000

13,000

8,800

13,700

9,000

100.0

10,100

8,300

10,500

8,300

11,100

8,600

11,700

8,600

11,900

8,800

12,700

8,700

13,400

8,900

104.0

9,900

8,200

10,400

8,200

10,900

8,500

11,500

8,500

11,700

8,800

12,500

8,600

13,100

8,800

110.0

9,700

8,100

10,100

8,100

10,600

8,300

11,200

8,400

11,400

8,600

12,200

8,500

12,800

8,700

68.0

13,400

10,300

14,400

10,500

15,300

10,800

16,300

10,900

16,600

11,200

17,900

11,100

18,900

11,300

73.0

13,400

10,300

14,400

10,500

15,300

10,800

16,300

10,900

16,600

11,200

17,900

11,100

18,900

11,300

77.0

13,400

10,300

14,400

10,500

15,300

10,800

16,200

10,900

16,500

11,200

17,600

11,000

18,600

11,200

82.0

13,300

10,300

14,100

10,400

15,000

10,700

15,900

10,700

16,100

11,000

17,200

10,900

18,200

11,100

86.0

13,200

10,200

13,900

10,300

14,800

10,600

15,600

10,600

15,900

10,900

17,000

10,800

17,900

11,000

91.0

13,000

10,100

13,600

10,100

14,500

10,500

15,300

10,500

15,500

10,800

16,600

10,600

17,500

10,800

95.0

12,800

10,000

13,400

10,000

14,200

10,300

15,000

10,400

15,200

10,600

16,300

10,500

17,200

10,700

100.0

12,600

9,900

13,200

9,900

13,900

10,200

14,700

10,200

14,900

10,500

15,900

10,400

16,700

10,600

104.0

12,400

9,800

12,900

9,800

13,600

10,100

14,400

10,100

14,600

10,400

15,600

10,300

16,400

10,500

110.0

12,200

9,700

12,600

9,700

13,200

9,900

14,000

10,000

14,200

10,200

15,200

10,100

15,900

10,300

68.0

16,100

12,700

17,300

13,000

18,400

13,400

19,500

13,500

19,900

13,900

21,500

13,800

22,700

14,100

73.0

16,100

12,700

17,300

13,000

18,400

13,400

19,500

13,500

19,900

13,900

21,500

13,800

22,700

14,100

77.0

16,100

12,700

17,300

13,000

18,400

13,400

19,500

13,400

19,800

13,800

21,200

13,600

22,300

13,900

82.0

16,000

12,700

16,900

12,800

18,100

13,300

19,100

13,300

19,300

13,600

20,700

13,500

21,900

13,800

86.0

15,800

12,600

16,700

12,700

17,700

13,100

18,700

13,100

19,000

13,500

20,400

13,300

21,500

13,600

91.0

15,500

12,500

16,400

12,500

17,300

12,900

18,300

13,000

18,600

13,300

19,900

13,200

21,000

13,500

95.0

15,300

12,400

16,100

12,400

17,000

12,800

18,000

12,800

18,300

13,200

19,500

13,000

20,600

13,300

100.0

15,100

12,300

15,800

12,300

16,700

12,600

17,600

12,700

17,900

13,000

19,100

12,900

20,100

13,200

104.0

14,900

12,200

15,500

12,200

16,400

12,500

17,300

12,600

17,500

12,900

18,800

12,700

19,700

13,000

110.0

14,600

12,000

15,100

12,000

15,900

12,300

16,800

12,400

17,000

12,700

18,200

12,600

19,100

12,800

68.0

21,400

16,800

22,900

17,100

24,500

17,700

25,900

17,800

26,500

18,300

28,500

18,100

30,200

18,500

73.0

21,400

16,800

22,900

17,100

24,500

17,700

25,900

17,800

26,500

18,300

28,500

18,100

30,200

18,500

77.0

21,400

16,800

22,900

17,100

24,500

17,700

25,900

17,700

26,300

18,200

28,100

18,000

29,700

18,400

82.0

21,300

16,700

22,500

16,900

24,000

17,500

25,300

17,500

25,700

18,000

27,500

17,700

29,100

18,100

86.0

21,000

16,600

22,200

16,700

23,600

17,300

24,900

17,300

25,300

17,800

27,100

17,600

28,600

17,900

91.0

20,700

16,400

21,700

16,500

23,100

17,100

24,400

17,100

24,700

17,600

26,500

17,300

27,900

17,700

95.0

20,400

16,300

21,400

16,400

22,700

16,900

24,000

16,900

24,300

17,400

26,000

17,200

27,400

17,500

100.0

20,100

16,100

21,000

16,200

22,200

16,700

23,400

16,700

23,700

17,200

25,400

16,900

26,700

17,300

104.0

19,800

16,000

20,600

16,000

21,700

16,500

23,000

16,500

23,300

17,000

24,900

16,800

26,200

17,100

110.0

19,400

15,800

20,100

15,800

21,100

16,200

22,400

16,300

22,700

16,700

24,200

16,500

25,400

16,900

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-2

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL CAPACITY TABLES IN Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY-P72~96THMU/YHMU with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

13,400

9,300

14,400

9,600

15,300

9,800

16,300

9,900

16,600

10,100

17,900

10,100

18,900

10,200

73.0

13,400

9,300

14,400

9,600

15,300

9,800

16,300

9,900

16,600

10,100

17,900

10,100

18,900

10,200

77.0

13,400

9,300

14,400

9,600

15,300

9,800

16,200

9,900

16,500

10,100

17,600

9,900

18,600

10,100

82.0

13,300

9,300

14,100

9,400

15,000

9,700

15,900

9,700

16,100

9,900

17,200

9,800

18,200

9,900

86.0

13,200

9,200

13,900

9,300

14,800

9,600

15,600

9,600

15,900

9,800

17,000

9,600

17,900

9,800

91.0

13,000

9,100

13,600

9,200

14,500

9,400

15,300

9,400

15,500

9,600

16,600

9,500

17,500

9,600

95.0

12,800

9,000

13,400

9,000

14,200

9,300

15,000

9,300

15,200

9,500

16,300

9,300

17,200

9,500

100.0

12,600

8,900

13,200

8,900

13,900

9,100

14,700

9,100

14,900

9,300

15,900

9,200

16,700

9,300

104.0

12,400

8,800

12,900

8,800

13,600

9,000

14,400

9,000

14,600

9,200

15,600

9,100

16,400

9,200

110.0

12,200

8,600

12,600

8,600

13,200

8,800

14,000

8,800

14,200

9,000

15,200

8,900

15,900

9,000

68.0

16,100

11,400

17,300

11,700

18,500

12,000

19,600

12,100

20,000

12,300

21,500

12,300

22,800

12,500

73.0

16,100

11,400

17,300

11,700

18,500

12,000

19,600

12,100

20,000

12,300

21,500

12,300

22,800

12,500

77.0

16,100

11,400

17,300

11,700

18,500

12,000

19,500

12,000

19,800

12,300

21,200

12,100

22,400

12,300

82.0

16,100

11,300

17,000

11,500

18,100

11,800

19,100

11,800

19,400

12,100

20,800

11,900

21,900

12,100

86.0

15,900

11,200

16,700

11,400

17,800

11,700

18,800

11,700

19,100

11,900

20,400

11,800

21,600

12,000

91.0

15,600

11,100

16,400

11,200

17,400

11,500

18,400

11,500

18,700

11,700

20,000

11,600

21,000

11,800

95.0

15,400

11,000

16,200

11,100

17,100

11,300

18,000

11,400

18,300

11,600

19,600

11,400

20,700

11,600

100.0

15,200

10,800

15,800

10,900

16,700

11,100

17,700

11,200

17,900

11,400

19,200

11,300

20,200

11,400

104.0

15,000

10,700

15,600

10,800

16,400

11,000

17,400

11,000

17,600

11,300

18,800

11,100

19,800

11,300

110.0

14,700

10,600

15,200

10,600

15,900

10,800

16,900

10,800

17,100

11,000

18,300

10,900

19,200

11,000

68.0

21,300

14,900

22,900

15,300

24,400

15,800

25,900

15,900

26,400

16,200

28,400

16,100

30,100

16,400

73.0

21,300

14,900

22,900

15,300

24,400

15,800

25,900

15,900

26,400

16,200

28,400

16,100

30,100

16,400

77.0

21,300

14,900

22,900

15,300

24,400

15,800

25,800

15,800

26,200

16,100

28,000

15,900

29,600

16,200

82.0

21,200

14,900

22,500

15,100

23,900

15,500

25,300

15,600

25,700

15,900

27,400

15,700

29,000

15,900

86.0

20,900

14,700

22,100

14,900

23,500

15,300

24,800

15,400

25,200

15,700

27,000

15,500

28,500

15,700

91.0

20,600

14,600

21,700

14,700

23,000

15,100

24,300

15,100

24,600

15,400

26,400

15,200

27,800

15,400

95.0

20,300

14,400

21,400

14,500

22,600

14,900

24,000

14,900

24,200

15,200

25,900

15,000

27,300

15,200

100.0

20,000

14,200

20,900

14,300

22,100

14,600

23,400

14,700

23,700

15,000

25,300

14,800

26,600

15,000

104.0

19,800

14,100

20,600

14,100

21,700

14,400

22,900

14,500

23,200

14,800

24,900

14,600

26,100

14,800

110.0

19,400

13,900

20,100

13,900

21,100

14,100

22,300

14,200

22,600

14,500

24,200

14,300

25,400

14,500

68.0

24,000

17,100

25,800

17,500

27,500

18,100

29,200

18,100

29,800

18,600

32,100

18,500

34,000

18,800

73.0

24,000

17,100

25,800

17,500

27,500

18,100

29,200

18,100

29,800

18,600

32,100

18,500

34,000

18,800

77.0

24,000

17,100

25,800

17,500

27,500

18,100

29,100

18,100

29,600

18,500

31,600

18,300

33,400

18,500

82.0

23,900

17,000

25,300

17,300

27,000

17,800

28,500

17,800

28,900

18,200

31,000

18,000

32,700

18,300

86.0

23,600

16,900

25,000

17,100

26,600

17,600

28,000

17,600

28,500

18,000

30,500

17,800

32,100

18,000

91.0

23,300

16,700

24,500

16,800

26,000

17,300

27,400

17,300

27,800

17,700

29,800

17,500

31,400

17,700

95.0

23,000

16,500

24,100

16,600

25,500

17,100

27,000

17,100

27,300

17,500

29,200

17,200

30,800

17,500

100.0

22,600

16,300

23,600

16,400

24,900

16,800

26,400

16,800

26,700

17,200

28,600

17,000

30,100

17,200

104.0

22,300

16,200

23,200

16,200

24,500

16,600

25,900

16,600

26,200

17,000

28,100

16,800

29,500

17,000

110.0

21,900

15,900

22,600

15,900

23,800

16,200

25,200

16,300

25,500

16,700

27,300

16,400

28,600

16,700

68.0

26,800

19,000

28,800

19,500

30,700

20,100

32,500

20,200

33,200

20,700

35,800

20,500

37,800

20,900

73.0

26,800

19,000

28,800

19,500

30,700

20,100

32,500

20,200

33,200

20,700

35,800

20,500

37,800

20,900

77.0

26,800

19,000

28,800

19,500

30,700

20,100

32,400

20,100

32,900

20,600

35,300

20,300

37,200

20,600

82.0

26,700

18,900

28,200

19,200

30,100

19,800

31,800

19,800

32,200

20,200

34,500

20,000

36,400

20,300

86.0

26,300

18,800

27,800

19,000

29,600

19,500

31,200

19,600

31,700

20,000

33,900

19,700

35,800

20,000

91.0

25,900

18,500

27,300

18,700

28,900

19,200

30,600

19,300

31,000

19,700

33,200

19,400

34,900

19,700

95.0

25,600

18,400

26,800

18,500

28,400

19,000

30,000

19,000

30,400

19,400

32,600

19,200

34,300

19,500

100.0

25,200

18,200

26,300

18,200

27,800

18,700

29,400

18,700

29,800

19,100

31,800

18,900

33,500

19,100

104.0

24,800

18,000

25,900

18,000

27,300

18,400

28,800

18,500

29,200

18,900

31,300

18,600

32,800

18,900

110.0

24,400

17,700

25,200

17,700

26,500

18,000

28,000

18,100

28,400

18,500

30,400

18,300

31,900

18,500

68.0

32,300

23,500

34,600

24,000

37,000

24,800

39,200

24,900

40,000

25,500

43,100

25,400

45,600

25,800

73.0

32,300

23,500

34,600

24,000

37,000

24,800

39,200

24,900

40,000

25,500

43,100

25,400

45,600

25,800

77.0

32,300

23,500

34,600

24,000

37,000

24,800

39,100

24,800

39,700

25,400

42,500

25,100

44,800

25,500

82.0

32,100

23,400

34,000

23,700

36,200

24,400

38,300

24,500

38,800

25,000

41,600

24,700

43,900

25,200

86.0

31,700

23,200

33,500

23,500

35,600

24,100

37,600

24,200

38,200

24,800

40,900

24,400

43,100

24,900

91.0

31,200

22,900

32,800

23,100

34,800

23,800

36,800

23,800

37,300

24,400

40,000

24,100

42,100

24,500

95.0

30,800

22,700

32,300

22,900

34,200

23,500

36,000

23,500

36,700

24,100

39,200

23,800

41,300

24,200

100.0

30,300

22,500

31,700

22,600

33,500

23,100

35,400

23,200

35,800

23,700

38,300

23,400

40,300

23,800

104.0

29,900

22,300

31,200

22,300

32,800

22,800

34,700

22,900

35,200

23,400

37,700

23,100

39,600

23,500

110.0

29,300

22,000

30,400

21,900

31,900

22,400

33,800

22,500

34,200

23,000

36,600

22,700

38,400

23,100

68.0

42,900

30,000

46,100

30,800

49,200

31,700

52,100

31,800

53,200

32,600

57,300

32,400

60,600

32,900

73.0

42,900

30,000

46,100

30,800

49,200

31,700

52,100

31,800

53,200

32,600

57,300

32,400

60,600

32,900

77.0

42,900

30,000

46,100

30,800

49,200

31,700

52,000

31,800

52,800

32,400

56,500

32,000

59,700

32,500

82.0

42,700

29,800

45,200

30,300

48,200

31,200

50,900

31,200

51,700

31,800

55,300

31,500

58,400

31,900

86.0

42,200

29,600

44,500

29,900

47,400

30,800

50,000

30,800

50,800

31,400

54,400

31,100

57,300

31,500

91.0

41,500

29,200

43,700

29,500

46,300

30,200

49,000

30,300

49,600

30,900

53,200

30,500

56,000

30,900

95.0

41,000

28,900

43,000

29,100

45,500

29,800

48,000

29,900

48,800

30,500

52,200

30,100

55,000

30,500

100.0

40,300

28,500

42,100

28,700

44,500

29,300

47,100

29,400

47,700

30,000

51,000

29,600

53,600

30,000

104.0

39,800

28,300

41,500

28,300

43,700

28,900

46,200

29,000

46,800

29,600

50,100

29,200

52,600

29,600

110.0

39,000

27,800

40,400

27,800

42,400

28,300

44,900

28,400

45,500

29,000

48,700

28,600

51,100

29,000

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-3

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

1. NOMINAL CAPACITY TABLES IN Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY-P72~96THMU/YHMU with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

54

72

96

71degF D.B.

73degF D.B.

77degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

Entering air temp.


80degF D.B.
67degF W.B.

82degF D.B.

86degF D.B.

90degF D.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

48,100

34,700

51,600

35,500

55,100

36,600

58,400

36,800

59,600

37,700

64,200

37,400

67,900

38,100

73.0

48,100

34,700

51,600

35,500

55,100

36,600

58,400

36,800

59,600

37,700

64,200

37,400

67,900

38,100

77.0

48,100

34,700

51,600

35,500

55,100

36,600

58,200

36,700

59,100

37,500

63,300

37,000

66,800

37,700

82.0

47,900

34,600

50,700

35,000

54,000

36,100

57,000

36,200

57,900

37,000

61,900

36,500

65,400

37,100

86.0

47,300

34,300

49,900

34,600

53,100

35,600

56,100

35,700

56,900

36,500

60,900

36,100

64,300

36,700

91.0

46,500

33,900

48,900

34,100

51,900

35,100

54,900

35,200

55,600

35,900

59,600

35,500

62,800

36,100

95.0

45,900

33,600

48,200

33,800

51,000

34,600

54,000

34,700

54,700

35,500

58,500

35,100

61,600

35,600

100.0

45,200

33,200

47,200

33,300

49,900

34,100

52,700

34,200

53,400

35,000

57,100

34,500

60,100

35,100

104.0

44,600

32,900

46,500

32,900

48,900

33,700

51,800

33,800

52,500

34,600

56,100

34,100

59,000

34,600

110.0

43,700

32,400

45,300

32,300

47,500

33,000

50,400

33,200

51,000

33,900

54,600

33,500

57,300

34,000

68.0

64,200

45,500

69,000

46,700

73,600

48,100

78,000

48,300

79,600

49,500

85,700

49,200

90,700

50,000

73.0

64,200

45,500

69,000

46,700

73,600

48,100

78,000

48,300

79,600

49,500

85,700

49,200

90,700

50,000

77.0

64,200

45,500

69,000

46,700

73,600

48,100

77,800

48,200

79,000

49,200

84,500

48,600

89,300

49,400

82.0

63,900

45,400

67,700

46,000

72,100

47,400

76,200

47,500

77,300

48,500

82,700

47,900

87,300

48,600

86.0

63,100

45,000

66,700

45,500

70,900

46,800

74,900

46,900

76,000

47,900

81,400

47,300

85,800

48,000

91.0

62,100

44,400

65,400

44,800

69,300

46,000

73,300

46,100

74,300

47,100

79,600

46,500

83,800

47,200

95.0

61,300

44,000

64,400

44,300

68,100

45,400

72,000

45,500

73,000

46,500

78,100

45,900

82,300

46,600

100.0

60,300

43,500

63,100

43,600

66,600

44,700

70,400

44,800

71,300

45,800

76,300

45,200

80,300

45,800

104.0

59,500

43,100

62,100

43,100

65,400

44,100

69,100

44,200

70,000

45,200

74,900

44,600

78,800

45,200

110.0

58,400

42,500

60,500

42,300

63,500

43,200

67,200

43,400

68,100

44,300

72,900

43,700

76,500

44,400

68.0

85,500

61,200

91,900

62,700

98,000

64,600

103,800

64,900

105,900

66,500

114,200

66,000

120,800

67,100

73.0

85,500

61,200

91,900

62,700

98,000

64,600

103,800

64,900

105,900

66,500

114,200

66,000

120,800

67,100

77.0

85,500

61,200

91,900

62,700

98,000

64,600

103,500

64,700

105,200

66,100

112,600

65,300

118,900

66,400

82.0

85,100

61,000

90,100

61,800

96,100

63,600

101,400

63,800

103,000

65,100

110,200

64,300

116,300

65,300

86.0

84,100

60,400

88,800

61,100

94,400

62,800

99,700

63,000

101,200

64,400

108,300

63,500

114,300

64,500

91.0

82,700

59,700

87,100

60,200

92,300

61,800

97,600

62,000

98,900

63,300

105,900

62,500

111,600

63,500

95.0

81,700

59,100

85,700

59,500

90,700

61,000

96,000

61,200

97,200

62,500

104,000

61,700

109,600

62,700

100.0

80,300

58,400

84,000

58,700

88,700

60,100

93,800

60,200

95,000

61,600

101,600

60,800

106,900

61,700

104.0

79,300

57,900

82,600

58,000

87,100

59,300

92,000

59,500

93,300

60,800

99,800

60,000

104,900

60,900

110.0

77,800

57,100

80,500

56,900

84,600

58,100

89,500

58,400

90,700

59,700

97,000

58,900

101,800

59,800

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-4

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL CAPACITY TABLES IN Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY-P72~96THMU/YHMU with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,500

4,300

5,900

4,400

6,300

4,500

6,700

4,600

6,800

4,700

7,300

4,700

7,700

4,800

73.0

5,500

4,300

5,900

4,400

6,300

4,500

6,700

4,600

6,800

4,700

7,300

4,700

7,700

4,800

77.0

5,500

4,300

5,900

4,400

6,300

4,500

6,600

4,600

6,700

4,700

7,200

4,600

7,600

4,700

82.0

5,500

4,300

5,800

4,300

6,200

4,500

6,500

4,500

6,600

4,600

7,100

4,600

7,400

4,700

86.0

5,400

4,300

5,700

4,300

6,000

4,400

6,400

4,500

6,500

4,600

6,900

4,500

7,300

4,600

91.0

5,300

4,200

5,600

4,200

5,900

4,400

6,300

4,400

6,300

4,500

6,800

4,500

7,100

4,600

95.0

5,200

4,200

5,500

4,200

5,800

4,300

6,000

4,300

6,200

4,500

6,700

4,400

7,000

4,500

100.0

5,100

4,200

5,400

4,200

5,700

4,300

6,000

4,300

6,100

4,400

6,500

4,400

6,800

4,400

104.0

5,100

4,100

5,300

4,100

5,600

4,200

5,900

4,200

6,000

4,400

6,400

4,300

6,700

4,400

110.0

5,000

4,100

5,200

4,100

5,400

4,200

5,700

4,200

5,800

4,300

6,200

4,200

6,500

4,300

68.0

7,000

5,300

7,500

5,400

8,000

5,600

8,500

5,600

8,700

5,700

9,300

5,700

9,900

5,800

73.0

7,000

5,300

7,500

5,400

8,000

5,600

8,500

5,600

8,700

5,700

9,300

5,700

9,900

5,800

77.0

7,000

5,300

7,500

5,400

8,000

5,600

8,500

5,600

8,600

5,700

9,200

5,600

9,700

5,700

82.0

7,000

5,200

7,400

5,300

7,900

5,500

8,300

5,500

8,400

5,600

9,000

5,600

9,500

5,700

86.0

6,900

5,200

7,300

5,300

7,700

5,400

8,200

5,400

8,300

5,600

8,900

5,500

9,400

5,600

91.0

6,800

5,100

7,100

5,200

7,600

5,300

8,000

5,400

8,100

5,500

8,700

5,400

9,100

5,500

95.0

6,700

5,100

7,000

5,100

7,400

5,300

8,000

5,300

8,000

5,400

8,500

5,400

9,000

5,500

100.0

6,600

5,100

6,900

5,100

7,300

5,200

7,700

5,200

7,800

5,400

8,300

5,300

8,800

5,400

104.0

6,500

5,000

6,800

5,000

7,100

5,100

7,500

5,200

7,600

5,300

8,200

5,200

8,600

5,300

110.0

6,400

4,900

6,600

4,900

6,900

5,100

7,300

5,100

7,400

5,200

7,900

5,100

8,300

5,200

68.0

10,700

7,600

11,400

7,800

12,200

8,000

12,900

8,100

13,200

8,300

14,200

8,200

15,000

8,300

73.0

10,700

7,600

11,400

7,800

12,200

8,000

12,900

8,100

13,200

8,300

14,200

8,200

15,000

8,300

77.0

10,700

7,600

11,400

7,800

12,200

8,000

12,900

8,000

13,100

8,200

14,000

8,100

14,800

8,200

82.0

10,600

7,600

11,200

7,700

12,000

7,900

12,600

7,900

12,800

8,100

13,700

8,000

14,500

8,100

86.0

10,500

7,500

11,100

7,600

11,800

7,800

12,400

7,800

12,600

8,000

13,500

7,900

14,200

8,000

91.0

10,300

7,400

10,800

7,500

11,500

7,700

12,200

7,700

12,300

7,900

13,200

7,800

13,900

7,900

95.0

10,200

7,300

10,700

7,400

11,300

7,600

12,000

7,600

12,100

7,800

13,000

7,700

13,600

7,800

100.0

10,000

7,300

10,500

7,300

11,000

7,500

11,700

7,500

11,800

7,600

12,700

7,500

13,300

7,600

104.0

9,900

7,200

10,300

7,200

10,800

7,400

11,500

7,400

11,600

7,500

12,400

7,400

13,100

7,600

110.0

9,700

7,100

10,000

7,100

10,500

7,200

11,200

7,200

11,300

7,400

12,100

7,300

12,700

7,400

68.0

13,400

10,400

14,400

10,600

15,300

10,900

16,300

11,000

16,600

11,300

17,900

11,200

18,900

11,500

73.0

13,400

10,400

14,400

10,600

15,300

10,900

16,300

11,000

16,600

11,300

17,900

11,200

18,900

11,500

77.0

13,400

10,400

14,400

10,600

15,300

10,900

16,200

11,000

16,500

11,300

17,600

11,100

18,600

11,300

82.0

13,300

10,300

14,100

10,500

15,000

10,800

15,900

10,800

16,100

11,100

17,200

11,000

18,200

11,200

86.0

13,200

10,300

13,900

10,400

14,800

10,700

15,600

10,700

15,900

11,000

17,000

10,900

17,900

11,100

91.0

13,000

10,200

13,600

10,200

14,500

10,500

15,300

10,600

15,500

10,900

16,600

10,700

17,500

10,900

95.0

12,800

10,100

13,400

10,100

14,200

10,400

15,000

10,500

15,200

10,700

16,300

10,600

17,200

10,800

100.0

12,600

10,000

13,200

10,000

13,900

10,300

14,700

10,300

14,900

10,600

15,900

10,500

16,700

10,700

104.0

12,400

9,900

12,900

9,900

13,600

10,200

14,400

10,200

14,600

10,500

15,600

10,400

16,400

10,600

110.0

12,200

9,800

12,600

9,800

13,200

10,000

14,000

10,100

14,200

10,300

15,200

10,200

15,900

10,400

68.0

16,100

12,200

17,300

12,500

18,500

12,900

19,600

12,900

20,000

13,300

21,500

13,200

22,800

13,500

73.0

16,100

12,200

17,300

12,500

18,500

12,900

19,600

12,900

20,000

13,300

21,500

13,200

22,800

13,500

77.0

16,100

12,200

17,300

12,500

18,500

12,900

19,500

12,900

19,800

13,300

21,200

13,100

22,400

13,300

82.0

16,100

12,200

17,000

12,300

18,100

12,700

19,100

12,700

19,400

13,100

20,800

12,900

21,900

13,200

86.0

15,900

12,100

16,700

12,200

17,800

12,600

18,800

12,600

19,100

12,900

20,400

12,800

21,600

13,000

91.0

15,600

12,000

16,400

12,000

17,400

12,400

18,400

12,400

18,700

12,800

20,000

12,600

21,000

12,800

95.0

15,400

11,900

16,200

11,900

17,100

12,300

18,000

12,300

18,300

12,600

19,600

12,500

20,700

12,700

100.0

15,200

11,700

15,800

11,800

16,700

12,100

17,700

12,100

17,900

12,400

19,200

12,300

20,200

12,500

104.0

15,000

11,600

15,600

11,700

16,400

12,000

17,400

12,000

17,600

12,300

18,800

12,100

19,800

12,400

110.0

14,700

11,500

15,200

11,500

15,900

11,800

16,900

11,800

17,100

12,100

18,300

12,000

19,200

12,200

68.0

21,300

16,100

22,900

16,400

24,400

17,000

25,900

17,000

26,400

17,500

28,400

17,400

30,100

17,700

73.0

21,300

16,100

22,900

16,400

24,400

17,000

25,900

17,000

26,400

17,500

28,400

17,400

30,100

17,700

77.0

21,300

16,100

22,900

16,400

24,400

17,000

25,800

17,000

26,200

17,400

28,000

17,200

29,600

17,500

82.0

21,200

16,000

22,500

16,200

23,900

16,700

25,300

16,800

25,700

17,200

27,400

17,000

29,000

17,300

86.0

20,900

15,900

22,100

16,000

23,500

16,500

24,800

16,600

25,200

17,000

27,000

16,800

28,500

17,100

91.0

20,600

15,700

21,700

15,800

23,000

16,300

24,300

16,400

24,600

16,800

26,400

16,600

27,800

16,900

95.0

20,300

15,600

21,400

15,700

22,600

16,100

24,000

16,200

24,200

16,600

25,900

16,400

27,300

16,700

100.0

20,000

15,400

20,900

15,500

22,100

15,900

23,400

15,900

23,700

16,400

25,300

16,100

26,600

16,400

104.0

19,800

15,300

20,600

15,300

21,700

15,700

22,900

15,800

23,200

16,200

24,900

16,000

26,100

16,300

110.0

19,400

15,100

20,100

15,100

21,100

15,400

22,300

15,500

22,600

15,900

24,200

15,700

25,400

16,000

68.0

24,000

17,800

25,800

18,200

27,500

18,800

29,200

18,900

29,800

19,400

32,100

19,300

34,000

19,600

73.0

24,000

17,800

25,800

18,200

27,500

18,800

29,200

18,900

29,800

19,400

32,100

19,300

34,000

19,600

77.0

24,000

17,800

25,800

18,200

27,500

18,800

29,100

18,900

29,600

19,300

31,600

19,100

33,400

19,400

82.0

23,900

17,800

25,300

18,000

27,000

18,600

28,500

18,600

28,900

19,100

31,000

18,800

32,700

19,200

86.0

23,600

17,600

25,000

17,800

26,600

18,400

28,000

18,400

28,500

18,800

30,500

18,600

32,100

18,900

91.0

23,300

17,400

24,500

17,600

26,000

18,100

27,400

18,100

27,800

18,600

29,800

18,300

31,400

18,700

95.0

23,000

17,300

24,100

17,400

25,500

17,900

27,000

17,900

27,300

18,400

29,200

18,100

30,800

18,500

100.0

22,600

17,100

23,600

17,200

24,900

17,600

26,400

17,700

26,700

18,100

28,600

17,900

30,100

18,200

104.0

22,300

17,000

23,200

17,000

24,500

17,400

25,900

17,500

26,200

17,900

28,100

17,700

29,500

18,000

110.0

21,900

16,800

22,600

16,700

23,800

17,100

25,200

17,200

25,500

17,600

27,300

17,400

28,600

17,700

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-5

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

26,800

19,700

28,800

20,100

30,700

20,800

32,500

20,800

33,200

21,400

35,800

21,200

37,800

21,600

73.0

26,800

19,700

28,800

20,100

30,700

20,800

32,500

20,800

33,200

21,400

35,800

21,200

37,800

21,600

77.0

26,800

19,700

28,800

20,100

30,700

20,800

32,400

20,800

32,900

21,300

35,300

21,000

37,200

21,400

82.0

26,700

19,600

28,200

19,900

30,100

20,500

31,800

20,500

32,200

21,000

34,500

20,700

36,400

21,100

86.0

26,300

19,400

27,800

19,600

29,600

20,200

31,200

20,300

31,700

20,800

33,900

20,500

35,800

20,900

91.0

25,900

19,200

27,300

19,400

28,900

19,900

30,600

20,000

31,000

20,400

33,200

20,200

34,900

20,500

95.0

25,600

19,100

26,800

19,200

28,400

19,700

30,000

19,700

30,400

20,200

32,600

19,900

34,300

20,300

100.0

25,200

18,900

26,300

18,900

27,800

19,400

29,400

19,400

29,800

19,900

31,800

19,700

33,500

20,000

104.0

24,800

18,700

25,900

18,700

27,300

19,200

28,800

19,200

29,200

19,700

31,300

19,400

32,800

19,800

110.0

24,400

18,400

25,200

18,400

26,500

18,800

28,000

18,900

28,400

19,300

30,400

19,100

31,900

19,400

68.0

32,300

24,400

34,600

24,900

37,000

25,700

39,200

25,800

40,000

26,600

43,100

26,400

45,600

26,900

73.0

32,300

24,400

34,600

24,900

37,000

25,700

39,200

25,800

40,000

26,600

43,100

26,400

45,600

26,900

77.0

32,300

24,400

34,600

24,900

37,000

25,700

39,100

25,800

39,700

26,500

42,500

26,100

44,800

26,600

82.0

32,100

24,300

34,000

24,600

36,200

25,400

38,300

25,500

38,800

26,100

41,600

25,800

43,900

26,300

86.0

31,700

24,100

33,500

24,400

35,600

25,100

37,600

25,200

38,200

25,800

40,900

25,500

43,100

26,000

91.0

31,200

23,900

32,800

24,100

34,800

24,800

36,800

24,800

37,300

25,500

40,000

25,100

42,100

25,600

95.0

30,800

23,700

32,300

23,800

34,200

24,500

36,000

24,600

36,700

25,200

39,200

24,900

41,300

25,300

100.0

30,300

23,400

31,700

23,500

33,500

24,200

35,400

24,200

35,800

24,800

38,300

24,500

40,300

25,000

104.0

29,900

23,300

31,200

23,300

32,800

23,900

34,700

23,900

35,200

24,600

37,700

24,300

39,600

24,700

110.0

29,300

23,000

30,400

22,900

31,900

23,500

33,800

23,500

34,200

24,200

36,600

23,900

38,400

24,300

68.0

42,900

31,200

46,100

32,000

49,200

32,900

52,100

33,100

53,200

34,000

57,300

33,700

60,600

34,300

73.0

42,900

31,200

46,100

32,000

49,200

32,900

52,100

33,100

53,200

34,000

57,300

33,700

60,600

34,300

77.0

42,900

31,200

46,100

32,000

49,200

32,900

52,000

33,000

52,800

33,800

56,500

33,400

59,700

33,900

82.0

42,700

31,100

45,200

31,500

48,200

32,500

50,900

32,500

51,700

33,300

55,300

32,900

58,400

33,400

86.0

42,200

30,800

44,500

31,200

47,400

32,100

50,000

32,200

50,800

32,900

54,400

32,500

57,300

33,000

91.0

41,500

30,500

43,700

30,700

46,300

31,600

49,000

31,700

49,600

32,400

53,200

32,000

56,000

32,500

95.0

41,000

30,200

43,000

30,400

45,500

31,200

48,000

31,300

48,800

32,000

52,200

31,600

55,000

32,100

100.0

40,300

29,900

42,100

30,000

44,500

30,700

47,100

30,800

47,700

31,500

51,000

31,100

53,600

31,600

104.0

39,800

29,600

41,500

29,700

43,700

30,400

46,200

30,400

46,800

31,200

50,100

30,800

52,600

31,300

110.0

39,000

29,200

40,400

29,100

42,400

29,800

44,900

29,900

45,500

30,600

48,700

30,200

51,100

30,700

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-6

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PMFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

71degF D.B.

73degF D.B.

77degF D.B.

Entering air temp.


80degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

82degF D.B.

86degF D.B.

90degF D.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,500

5,100

5,900

5,100

6,300

5,300

6,700

5,400

6,800

5,600

7,300

5,500

7,700

5,700

73.0

5,500

5,100

5,900

5,100

6,300

5,300

6,700

5,400

6,800

5,600

7,300

5,500

7,700

5,700

77.0

5,500

5,100

5,900

5,100

6,300

5,300

6,600

5,400

6,700

5,600

7,200

5,500

7,600

5,600

82.0

5,500

5,100

5,800

5,100

6,200

5,300

6,500

5,300

6,600

5,500

7,100

5,400

7,400

5,600

86.0

5,400

5,000

5,700

5,100

6,000

5,300

6,400

5,300

6,500

5,500

6,900

5,400

7,300

5,500

91.0

5,300

5,000

5,600

5,000

5,900

5,200

6,300

5,200

6,300

5,400

6,800

5,300

7,100

5,500

95.0

5,200

5,000

5,500

5,000

5,800

5,200

6,000

5,200

6,200

5,400

6,700

5,300

7,000

5,400

100.0

5,100

4,900

5,400

4,900

5,700

5,100

6,000

5,100

6,100

5,300

6,500

5,200

6,800

5,400

104.0

5,100

4,900

5,300

4,900

5,600

5,100

5,900

5,100

6,000

5,300

6,400

5,200

6,700

5,400

110.0

5,000

4,900

5,200

4,800

5,400

5,000

5,700

5,000

5,800

5,200

6,200

5,100

6,500

5,300

68.0

7,000

6,100

7,500

6,200

8,000

6,400

8,500

6,500

8,700

6,700

9,300

6,600

9,900

6,800

73.0

7,000

6,100

7,500

6,200

8,000

6,400

8,500

6,500

8,700

6,700

9,300

6,600

9,900

6,800

77.0

7,000

6,100

7,500

6,200

8,000

6,400

8,500

6,500

8,600

6,700

9,200

6,600

9,700

6,700

82.0

7,000

6,100

7,400

6,100

7,900

6,400

8,300

6,400

8,400

6,600

9,000

6,500

9,500

6,700

86.0

6,900

6,100

7,300

6,100

7,700

6,300

8,200

6,300

8,300

6,500

8,900

6,500

9,400

6,600

91.0

6,800

6,000

7,100

6,000

7,600

6,200

8,000

6,300

8,100

6,500

8,700

6,400

9,100

6,500

95.0

6,700

6,000

7,000

6,000

7,400

6,200

8,000

6,200

8,000

6,400

8,500

6,300

9,000

6,500

100.0

6,600

5,900

6,900

5,900

7,300

6,100

7,700

6,100

7,800

6,300

8,300

6,300

8,800

6,400

104.0

6,500

5,900

6,800

5,900

7,100

6,100

7,500

6,100

7,600

6,300

8,200

6,200

8,600

6,400

110.0

6,400

5,800

6,600

5,800

6,900

6,000

7,300

6,000

7,400

6,200

7,900

6,100

8,300

6,300

68.0

10,700

7,900

11,400

8,100

12,200

8,300

12,900

8,400

13,200

8,600

14,200

8,500

15,000

8,700

73.0

10,700

7,900

11,400

8,100

12,200

8,300

12,900

8,400

13,200

8,600

14,200

8,500

15,000

8,700

77.0

10,700

7,900

11,400

8,100

12,200

8,300

12,900

8,400

13,100

8,600

14,000

8,400

14,800

8,600

82.0

10,600

7,900

11,200

8,000

12,000

8,200

12,600

8,200

12,800

8,400

13,700

8,300

14,500

8,500

86.0

10,500

7,800

11,100

7,900

11,800

8,100

12,400

8,100

12,600

8,300

13,500

8,200

14,200

8,400

91.0

10,300

7,700

10,800

7,800

11,500

8,000

12,200

8,000

12,300

8,200

13,200

8,100

13,900

8,300

95.0

10,200

7,700

10,700

7,700

11,300

7,900

12,000

7,900

12,100

8,100

13,000

8,000

13,600

8,200

100.0

10,000

7,600

10,500

7,600

11,000

7,800

11,700

7,800

11,800

8,000

12,700

7,900

13,300

8,000

104.0

9,900

7,500

10,300

7,500

10,800

7,700

11,500

7,700

11,600

7,900

12,400

7,800

13,100

8,000

110.0

9,700

7,400

10,000

7,400

10,500

7,600

11,200

7,600

11,300

7,800

12,100

7,700

12,700

7,800

68.0

13,400

9,600

14,400

9,900

15,300

10,200

16,300

10,200

16,600

10,500

17,900

10,400

18,900

10,600

73.0

13,400

9,600

14,400

9,900

15,300

10,200

16,300

10,200

16,600

10,500

17,900

10,400

18,900

10,600

77.0

13,400

9,600

14,400

9,900

15,300

10,200

16,200

10,200

16,500

10,400

17,600

10,300

18,600

10,500

82.0

13,300

9,600

14,100

9,700

15,000

10,000

15,900

10,000

16,100

10,300

17,200

10,100

18,200

10,300

86.0

13,200

9,500

13,900

9,600

14,800

9,900

15,600

9,900

15,900

10,100

17,000

10,000

17,900

10,200

91.0

13,000

9,400

13,600

9,500

14,500

9,700

15,300

9,800

15,500

10,000

16,600

9,900

17,500

10,000

95.0

12,800

9,300

13,400

9,400

14,200

9,600

15,000

9,600

15,200

9,900

16,300

9,700

17,200

9,900

100.0

12,600

9,200

13,200

9,200

13,900

9,500

14,700

9,500

14,900

9,700

15,900

9,600

16,700

9,700

104.0

12,400

9,100

12,900

9,100

13,600

9,400

14,400

9,400

14,600

9,600

15,600

9,500

16,400

9,600

110.0

12,200

9,000

12,600

9,000

13,200

9,200

14,000

9,200

14,200

9,400

15,200

9,300

15,900

9,400

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-7

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PLFY-P-NCMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

08

12

15

71degF D.B.

73degF D.B.

77degF D.B.

Entering air temp.


80degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

82degF D.B.

86degF D.B.

90degF D.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

7,000

6,400

7,500

6,500

8,000

6,800

8,500

6,800

8,700

7,100

9,300

7,000

9,900

7,200

73.0

7,000

6,400

7,500

6,500

8,000

6,800

8,500

6,800

8,700

7,100

9,300

7,000

9,900

7,200

77.0

7,000

6,400

7,500

6,500

8,000

6,800

8,500

6,800

8,600

7,000

9,200

7,000

9,700

7,200

82.0

7,000

6,400

7,400

6,500

7,900

6,700

8,300

6,700

8,400

7,000

9,000

6,900

9,500

7,100

86.0

6,900

6,400

7,300

6,400

7,700

6,700

8,200

6,700

8,300

6,900

8,900

6,800

9,400

7,000

91.0

6,800

6,300

7,100

6,400

7,600

6,600

8,000

6,600

8,100

6,900

8,700

6,800

9,100

7,000

95.0

6,700

6,300

7,000

6,300

7,400

6,600

12,000

6,600

8,000

6,800

8,500

6,700

9,000

6,900

100.0

6,600

6,300

6,900

6,300

7,300

6,500

7,700

6,500

7,800

6,700

8,300

6,700

8,800

6,800

104.0

6,500

6,200

6,800

6,200

7,100

6,400

7,500

6,500

7,600

6,700

8,200

6,600

8,600

6,800

110.0

6,400

6,200

6,600

6,100

6,900

6,400

7,300

6,400

7,400

6,600

7,900

6,500

8,300

6,700

68.0

10,700

8,500

11,400

8,700

12,200

9,000

12,900

9,000

13,200

9,300

14,200

9,200

15,000

9,400

73.0

10,700

8,500

11,400

8,700

12,200

9,000

12,900

9,000

13,200

9,300

14,200

9,200

15,000

9,400

77.0

10,700

8,500

11,400

8,700

12,200

9,000

12,900

9,000

13,100

9,300

14,000

9,100

14,800

9,300

82.0

10,600

8,500

11,200

8,600

12,000

8,900

12,600

8,900

12,800

9,200

13,700

9,000

14,500

9,200

86.0

10,500

8,400

11,100

8,500

11,800

8,800

12,400

8,800

12,600

9,100

13,500

8,900

14,200

9,100

91.0

10,300

8,400

10,800

8,400

11,500

8,700

12,200

8,700

12,300

8,900

13,200

8,800

13,900

9,000

95.0

10,200

8,300

10,700

8,300

11,300

8,600

15,000

8,600

12,100

8,900

13,000

8,700

13,600

8,900

100.0

10,000

8,200

10,500

8,200

11,000

8,500

11,700

8,500

11,800

8,800

12,700

8,600

13,300

8,800

104.0

9,900

8,200

10,300

8,200

10,800

8,400

11,500

8,400

11,600

8,700

12,400

8,600

13,100

8,700

110.0

9,700

8,100

10,000

8,000

10,500

8,300

11,200

8,300

11,300

8,500

12,100

8,400

12,700

8,600

68.0

13,400

9,900

14,400

10,100

15,300

10,500

16,300

10,500

16,600

10,800

17,900

10,700

18,900

10,900

73.0

13,400

9,900

14,400

10,100

15,300

10,500

16,300

10,500

16,600

10,800

17,900

10,700

18,900

10,900

77.0

13,400

9,900

14,400

10,100

15,300

10,500

16,200

10,500

16,500

10,700

17,600

10,600

18,600

10,800

82.0

13,300

9,900

14,100

10,000

15,000

10,300

15,900

10,300

16,100

10,600

17,200

10,400

18,200

10,600

86.0

13,200

9,800

13,900

9,900

14,800

10,200

15,600

10,200

15,900

10,500

17,000

10,300

17,900

10,500

91.0

13,000

9,700

13,600

9,800

14,500

10,000

15,300

10,100

15,500

10,300

16,600

10,200

17,500

10,400

95.0

12,800

9,600

13,400

9,700

14,200

9,900

18,000

10,000

15,200

10,200

16,300

10,100

17,200

10,200

100.0

12,600

9,500

13,200

9,500

13,900

9,800

14,700

9,800

14,900

10,100

15,900

9,900

16,700

10,100

104.0

12,400

9,400

12,900

9,400

13,600

9,700

14,400

9,700

14,600

9,900

15,600

9,800

16,400

10,000

110.0

12,200

9,300

12,600

9,300

13,200

9,500

14,000

9,500

14,200

9,800

15,200

9,600

15,900

9,800

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-8

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PLFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

10,700

9,400

11,400

9,500

12,200

9,900

12,900

9,900

13,200

10,300

14,200

10,200

15,000

10,400

73.0

10,700

9,400

11,400

9,500

12,200

9,900

12,900

9,900

13,200

10,300

14,200

10,200

15,000

10,400

77.0

10,700

9,400

11,400

9,500

12,200

9,900

12,900

9,900

13,100

10,200

14,000

10,100

14,800

10,400

82.0

10,600

9,300

11,200

9,400

12,000

9,800

12,600

9,800

12,800

10,100

13,700

10,000

14,500

10,300

86.0

10,500

9,300

11,100

9,300

11,800

9,700

12,400

9,700

12,600

10,000

13,500

9,900

14,200

10,200

91.0

10,300

9,200

10,800

9,200

11,500

9,600

12,200

9,600

12,300

9,900

13,200

9,800

13,900

10,100

95.0

10,200

9,100

10,700

9,200

11,300

9,500

12,000

9,500

12,100

9,800

13,000

9,700

13,600

10,000

100.0

10,000

9,100

10,500

9,100

11,000

9,400

11,700

9,400

11,800

9,700

12,700

9,600

13,300

9,900

104.0

9,900

9,000

10,300

9,000

10,800

9,300

11,500

9,300

11,600

9,700

12,400

9,500

13,100

9,800

110.0

9,700

8,900

10,000

8,900

10,500

9,200

11,200

9,200

11,300

9,500

12,100

9,400

12,700

9,700

68.0

13,400

11,400

14,400

11,600

15,300

12,000

16,300

12,100

16,600

12,500

17,900

12,400

18,900

12,700

73.0

13,400

11,400

14,400

11,600

15,300

12,000

16,300

12,100

16,600

12,500

17,900

12,400

18,900

12,700

77.0

13,400

11,400

14,400

11,600

15,300

12,000

16,200

12,000

16,500

12,400

17,600

12,300

18,600

12,600

82.0

13,300

11,400

14,100

11,500

15,000

11,900

15,900

11,900

16,100

12,300

17,200

12,100

18,200

12,400

86.0

13,200

11,300

13,900

11,400

14,800

11,800

15,600

11,800

15,900

12,200

17,000

12,000

17,900

12,300

91.0

13,000

11,200

13,600

11,300

14,500

11,600

15,300

11,700

15,500

12,000

16,600

11,900

17,500

12,200

95.0

12,800

11,100

13,400

11,200

14,200

11,500

15,000

11,600

15,200

11,900

16,300

11,800

17,200

12,100

100.0

12,600

11,000

13,200

11,000

13,900

11,400

14,700

11,400

14,900

11,800

15,900

11,700

16,700

11,900

104.0

12,400

11,000

12,900

10,900

13,600

11,300

14,400

11,300

14,600

11,700

15,600

11,600

16,400

11,800

110.0

12,200

10,800

12,600

10,800

13,200

11,100

14,000

11,200

14,200

11,500

15,200

11,400

15,900

11,700

68.0

16,100

13,600

17,300

13,900

18,500

14,400

19,600

14,400

20,000

14,900

21,500

14,800

22,800

15,100

73.0

16,100

13,600

17,300

13,900

18,500

14,400

19,600

14,400

20,000

14,900

21,500

14,800

22,800

15,100

77.0

16,100

13,600

17,300

13,900

18,500

14,400

19,500

14,400

19,800

14,800

21,200

14,700

22,400

15,000

82.0

16,100

13,600

17,000

13,700

18,100

14,200

19,100

14,200

19,400

14,700

20,800

14,500

21,900

14,900

86.0

15,900

13,500

16,700

13,600

17,800

14,100

18,800

14,100

19,100

14,600

20,400

14,400

21,600

14,700

91.0

15,600

13,400

16,400

13,400

17,400

13,900

18,400

14,000

18,700

14,400

20,000

14,200

21,000

14,600

95.0

15,400

13,300

16,200

13,300

17,100

13,800

18,000

13,800

18,300

14,300

19,600

14,100

20,700

14,400

100.0

15,200

13,200

15,800

13,200

16,700

13,600

17,700

13,700

17,900

14,100

19,200

13,900

20,200

14,300

104.0

15,000

13,100

15,600

13,100

16,400

13,500

17,400

13,500

17,600

14,000

18,800

13,800

19,800

14,100

110.0

14,700

13,000

15,200

12,900

15,900

13,300

16,900

13,400

17,100

13,800

18,300

13,600

19,200

13,900

68.0

21,300

16,700

22,900

17,000

24,400

17,600

25,900

17,600

26,400

18,200

28,400

18,000

30,100

18,400

73.0

21,300

16,700

22,900

17,000

24,400

17,600

25,900

17,600

26,400

18,200

28,400

18,000

30,100

18,400

77.0

21,300

16,700

22,900

17,000

24,400

17,600

25,800

17,600

26,200

18,100

28,000

17,900

29,600

18,200

82.0

21,200

16,600

22,500

16,800

23,900

17,400

25,300

17,400

25,700

17,900

27,400

17,600

29,000

18,000

86.0

20,900

16,500

22,100

16,600

23,500

17,200

24,800

17,200

25,200

17,700

27,000

17,500

28,500

17,800

91.0

20,600

16,300

21,700

16,400

23,000

16,900

24,300

17,000

24,600

17,400

26,400

17,200

27,800

17,600

95.0

20,300

16,200

21,400

16,300

22,600

16,800

24,000

16,800

24,200

17,300

25,900

17,000

27,300

17,400

100.0

20,000

16,000

20,900

16,100

22,100

16,500

23,400

16,600

23,700

17,000

25,300

16,800

26,600

17,200

104.0

19,800

15,900

20,600

15,900

21,700

16,400

22,900

16,400

23,200

16,900

24,900

16,700

26,100

17,000

110.0

19,400

15,700

20,100

15,700

21,100

16,100

22,300

16,200

22,600

16,600

24,200

16,400

25,400

16,700

68.0

26,800

19,900

28,800

20,300

30,700

21,000

32,500

21,100

33,200

21,700

35,800

21,500

37,800

21,900

73.0

26,800

19,900

28,800

20,300

30,700

21,000

32,500

21,100

33,200

21,700

35,800

21,500

37,800

21,900

77.0

26,800

19,900

28,800

20,300

30,700

21,000

32,400

21,000

32,900

21,500

35,300

21,300

37,200

21,700

82.0

26,700

19,800

28,200

20,100

30,100

20,700

31,800

20,700

32,200

21,200

34,500

21,000

36,400

21,400

86.0

26,300

19,700

27,800

19,900

29,600

20,500

31,200

20,500

31,700

21,000

33,900

20,700

35,800

21,100

91.0

25,900

19,500

27,300

19,600

28,900

20,200

30,600

20,200

31,000

20,700

33,200

20,400

34,900

20,800

95.0

25,600

19,300

26,800

19,400

28,400

19,900

30,000

20,000

30,400

20,500

32,600

20,200

34,300

20,600

100.0

25,200

19,100

26,300

19,100

27,800

19,600

29,400

19,700

29,800

20,200

31,800

19,900

33,500

20,300

104.0

24,800

18,900

25,900

18,900

27,300

19,400

28,800

19,500

29,200

20,000

31,300

19,700

32,800

20,000

110.0

24,400

18,700

25,200

18,600

26,500

19,100

28,000

19,100

28,400

19,600

30,400

19,400

31,900

19,700

68.0

32,300

25,500

34,600

26,000

37,000

26,900

39,200

27,000

40,000

27,800

43,100

27,600

45,600

28,200

73.0

32,300

25,500

34,600

26,000

37,000

26,900

39,200

27,000

40,000

27,800

43,100

27,600

45,600

28,200

77.0

32,300

25,500

34,600

26,000

37,000

26,900

39,100

27,000

39,700

27,700

42,500

27,300

44,800

27,900

82.0

32,100

25,400

34,000

25,700

36,200

26,600

38,300

26,600

38,800

27,400

41,600

27,000

43,900

27,600

86.0

31,700

25,200

33,500

25,400

35,600

26,300

37,600

26,300

38,200

27,100

40,900

26,700

43,100

27,300

91.0

31,200

25,000

32,800

25,100

34,800

25,900

36,800

26,000

37,300

26,700

40,000

26,400

42,100

27,000

95.0

30,800

24,800

32,300

24,900

34,200

25,700

36,000

25,700

36,700

26,500

39,200

26,100

41,300

26,700

100.0

30,300

24,600

31,700

24,600

33,500

25,300

35,400

25,400

35,800

26,100

38,300

25,800

40,300

26,400

104.0

29,900

24,400

31,200

24,400

32,800

25,100

34,700

25,200

35,200

25,900

37,700

25,500

39,600

26,100

110.0

29,300

24,100

30,400

24,000

31,900

24,700

33,800

24,800

34,200

25,500

36,600

25,200

38,400

25,700

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-9

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PCFY-P-NGMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

13,400

10,400

14,400

10,600

15,300

10,900

16,300

11,000

16,600

11,300

17,900

11,200

18,900

11,500

73.0

13,400

10,400

14,400

10,600

15,300

10,900

16,300

11,000

16,600

11,300

17,900

11,200

18,900

11,500

77.0

13,400

10,400

14,400

10,600

15,300

10,900

16,200

11,000

16,500

11,300

17,600

11,100

18,600

11,300

82.0

13,300

10,300

14,100

10,500

15,000

10,800

15,900

10,800

16,100

11,100

17,200

11,000

18,200

11,200

86.0

13,200

10,300

13,900

10,400

14,800

10,700

15,600

10,700

15,900

11,000

17,000

10,900

17,900

11,100

91.0

13,000

10,200

13,600

10,200

14,500

10,500

15,300

10,600

15,500

10,900

16,600

10,700

17,500

10,900

95.0

12,800

10,100

13,400

10,100

14,200

10,400

15,000

10,500

15,200

10,700

16,300

10,600

17,200

10,800

100.0

12,600

10,000

13,200

10,000

13,900

10,300

14,700

10,300

14,900

10,600

15,900

10,500

16,700

10,700

104.0

12,400

9,900

12,900

9,900

13,600

10,200

14,400

10,200

14,600

10,500

15,600

10,400

16,400

10,600

110.0

12,200

9,800

12,600

9,800

13,200

10,000

14,000

10,100

14,200

10,300

15,200

10,200

15,900

10,400

68.0

21,300

16,100

22,900

16,400

24,400

17,000

25,900

17,000

26,400

17,500

28,400

17,400

30,100

17,700

73.0

21,300

16,100

22,900

16,400

24,400

17,000

25,900

17,000

26,400

17,500

28,400

17,400

30,100

17,700

77.0

21,300

16,100

22,900

16,400

24,400

17,000

25,800

17,000

26,200

17,400

28,000

17,200

29,600

17,500

82.0

21,200

16,000

22,500

16,200

23,900

16,700

25,300

16,800

25,700

17,200

27,400

17,000

29,000

17,300

86.0

20,900

15,900

22,100

16,000

23,500

16,500

24,800

16,600

25,200

17,000

27,000

16,800

28,500

17,100

91.0

20,600

15,700

21,700

15,800

23,000

16,300

24,300

16,400

24,600

16,800

26,400

16,600

27,800

16,900

95.0

20,300

15,600

21,400

15,700

22,600

16,100

24,000

16,200

24,200

16,600

25,900

16,400

27,300

16,700

100.0

20,000

15,400

20,900

15,500

22,100

15,900

23,400

15,900

23,700

16,400

25,300

16,100

26,600

16,400

104.0

19,800

15,300

20,600

15,300

21,700

15,700

22,900

15,800

23,200

16,200

24,900

16,000

26,100

16,300

110.0

19,400

15,100

20,100

15,100

21,100

15,400

22,300

15,500

22,600

15,900

24,200

15,700

25,400

16,000

68.0

26,800

19,700

28,800

20,100

30,700

20,800

32,500

20,800

33,200

21,400

35,800

21,200

37,800

21,600

73.0

26,800

19,700

28,800

20,100

30,700

20,800

32,500

20,800

33,200

21,400

35,800

21,200

37,800

21,600

77.0

26,800

19,700

28,800

20,100

30,700

20,800

32,400

20,800

32,900

21,300

35,300

21,000

37,200

21,400

82.0

26,700

19,600

28,200

19,900

30,100

20,500

31,800

20,500

32,200

21,000

34,500

20,700

36,400

21,100

86.0

26,300

19,400

27,800

19,600

29,600

20,200

31,200

20,300

31,700

20,800

33,900

20,500

35,800

20,900

91.0

25,900

19,200

27,300

19,400

28,900

19,900

30,600

20,000

31,000

20,400

33,200

20,200

34,900

20,500

95.0

25,600

19,100

26,800

19,200

28,400

19,700

30,000

19,700

30,400

20,200

32,600

19,900

34,300

20,300

100.0

25,200

18,900

26,300

18,900

27,800

19,400

29,400

19,400

29,800

19,900

31,800

19,700

33,500

20,000

104.0

24,800

18,700

25,900

18,700

27,300

19,200

28,800

19,200

29,200

19,700

31,300

19,400

32,800

19,800

110.0

24,400

18,400

25,200

18,400

26,500

18,800

28,000

18,900

28,400

19,300

30,400

19,100

31,900

19,400

68.0

32,300

24,400

34,600

24,900

37,000

25,700

39,200

25,800

40,000

26,600

43,100

26,400

45,600

26,900

73.0

32,300

24,400

34,600

24,900

37,000

25,700

39,200

25,800

40,000

26,600

43,100

26,400

45,600

26,900

77.0

32,300

24,400

34,600

24,900

37,000

25,700

39,100

25,800

39,700

26,500

42,500

26,100

44,800

26,600

82.0

32,100

24,300

34,000

24,600

36,200

25,400

38,300

25,500

38,800

26,100

41,600

25,800

43,900

26,300

86.0

31,700

24,100

33,500

24,400

35,600

25,100

37,600

25,200

38,200

25,800

40,900

25,500

43,100

26,000

91.0

31,200

23,900

32,800

24,100

34,800

24,800

36,800

24,800

37,300

25,500

40,000

25,100

42,100

25,600

95.0

30,800

23,700

32,300

23,800

34,200

24,500

36,000

24,600

36,700

25,200

39,200

24,900

41,300

25,300

100.0

30,300

23,400

31,700

23,500

33,500

24,200

35,400

24,200

35,800

24,800

38,300

24,500

40,300

25,000

104.0

29,900

23,300

31,200

23,300

32,800

23,900

34,700

23,900

35,200

24,600

37,700

24,300

39,600

24,700

110.0

29,300

23,000

30,400

22,900

31,900

23,500

33,800

23,500

34,200

24,200

36,600

23,900

38,400

24,300

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-10

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

73degF D.B.

77degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

82degF D.B.

86degF D.B.

90degF D.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,500

4,300

5,900

4,400

6,300

4,500

6,700

4,600

6,800

4,700

7,300

4,700

7,700

4,800

73.0

5,500

4,300

5,900

4,400

6,300

4,500

6,700

4,600

6,800

4,700

7,300

4,700

7,700

4,800

77.0

5,500

4,300

5,900

4,400

6,300

4,500

6,600

4,600

6,700

4,700

7,200

4,600

7,600

4,700

82.0

5,500

4,300

5,800

4,300

6,200

4,500

6,500

4,500

6,600

4,600

7,100

4,600

7,400

4,700

86.0

5,400

4,300

5,700

4,300

6,000

4,400

6,400

4,500

6,500

4,600

6,900

4,500

7,300

4,600

91.0

5,300

4,200

5,600

4,200

5,900

4,400

6,300

4,400

6,300

4,500

6,800

4,500

7,100

4,600

95.0

5,200

4,200

5,500

4,200

5,800

4,300

6,000

4,300

6,200

4,500

6,700

4,400

7,000

4,500

100.0

5,100

4,200

5,400

4,200

5,700

4,300

6,000

4,300

6,100

4,400

6,500

4,400

6,800

4,400

104.0

5,100

4,100

5,300

4,100

5,600

4,200

5,900

4,200

6,000

4,400

6,400

4,300

6,700

4,400

110.0

5,000

4,100

5,200

4,100

5,400

4,200

5,700

4,200

5,800

4,300

6,200

4,200

6,500

4,300

68.0

7,000

5,400

7,500

5,500

8,000

5,700

8,500

5,700

8,700

5,900

9,300

5,800

9,900

6,000

73.0

7,000

5,400

7,500

5,500

8,000

5,700

8,500

5,700

8,700

5,900

9,300

5,800

9,900

6,000

77.0

7,000

5,400

7,500

5,500

8,000

5,700

8,500

5,700

8,600

5,900

9,200

5,800

9,700

5,900

82.0

7,000

5,400

7,400

5,400

7,900

5,600

8,300

5,600

8,400

5,800

9,000

5,700

9,500

5,800

86.0

6,900

5,300

7,300

5,400

7,700

5,600

8,200

5,600

8,300

5,700

8,900

5,700

9,400

5,800

91.0

6,800

5,300

7,100

5,300

7,600

5,500

8,000

5,500

8,100

5,700

8,700

5,600

9,100

5,700

95.0

6,700

5,300

7,000

5,300

7,400

5,400

8,000

5,400

8,000

5,600

8,500

5,500

9,000

5,600

100.0

6,600

5,200

6,900

5,200

7,300

5,400

7,700

5,400

7,800

5,500

8,300

5,400

8,800

5,600

104.0

6,500

5,200

6,800

5,200

7,100

5,300

7,500

5,300

7,600

5,500

8,200

5,400

8,600

5,500

110.0

6,400

5,100

6,600

5,100

6,900

5,200

7,300

5,200

7,400

5,400

7,900

5,300

8,300

5,400

68.0

10,700

8,700

11,400

8,900

12,200

9,200

12,900

9,200

13,200

9,500

14,200

9,400

15,000

9,700

73.0

10,700

8,700

11,400

8,900

12,200

9,200

12,900

9,200

13,200

9,500

14,200

9,400

15,000

9,700

77.0

10,700

8,700

11,400

8,900

12,200

9,200

12,900

9,200

13,100

9,500

14,000

9,400

14,800

9,600

82.0

10,600

8,700

11,200

8,800

12,000

9,100

12,600

9,100

12,800

9,400

13,700

9,300

14,500

9,500

86.0

10,500

8,600

11,100

8,700

11,800

9,000

12,400

9,000

12,600

9,300

13,500

9,200

14,200

9,400

91.0

10,300

8,600

10,800

8,600

11,500

8,900

12,200

8,900

12,300

9,200

13,200

9,100

13,900

9,300

95.0

10,200

8,500

10,700

8,500

11,300

8,800

12,000

8,800

12,100

9,100

13,000

9,000

13,600

9,200

100.0

10,000

8,400

10,500

8,400

11,000

8,700

11,700

8,700

11,800

9,000

12,700

8,900

13,300

9,100

104.0

9,900

8,400

10,300

8,400

10,800

8,600

11,500

8,600

11,600

8,900

12,400

8,800

13,100

9,000

110.0

9,700

8,300

10,000

8,200

10,500

8,500

11,200

8,500

11,300

8,800

12,100

8,700

12,700

8,900

68.0

13,400

10,500

14,400

10,700

15,300

11,000

16,300

11,100

16,600

11,400

17,900

11,300

18,900

11,600

73.0

13,400

10,500

14,400

10,700

15,300

11,000

16,300

11,100

16,600

11,400

17,900

11,300

18,900

11,600

77.0

13,400

10,500

14,400

10,700

15,300

11,000

16,200

11,100

16,500

11,400

17,600

11,200

18,600

11,400

82.0

13,300

10,400

14,100

10,500

15,000

10,900

15,900

10,900

16,100

11,200

17,200

11,100

18,200

11,300

86.0

13,200

10,400

13,900

10,400

14,800

10,800

15,600

10,800

15,900

11,100

17,000

11,000

17,900

11,200

91.0

13,000

10,200

13,600

10,300

14,500

10,600

15,300

10,700

15,500

11,000

16,600

10,800

17,500

11,000

95.0

12,800

10,200

13,400

10,200

14,200

10,500

15,000

10,500

15,200

10,800

16,300

10,700

17,200

10,900

100.0

12,600

10,100

13,200

10,100

13,900

10,400

14,700

10,400

14,900

10,700

15,900

10,600

16,700

10,800

104.0

12,400

10,000

12,900

10,000

13,600

10,300

14,400

10,300

14,600

10,600

15,600

10,500

16,400

10,700

110.0

12,200

9,900

12,600

9,800

13,200

10,100

14,000

10,100

14,200

10,400

15,200

10,300

15,900

10,500

68.0

16,100

13,300

17,300

13,600

18,500

14,000

19,600

14,100

20,000

14,600

21,500

14,400

22,800

14,800

73.0

16,100

13,300

17,300

13,600

18,500

14,000

19,600

14,100

20,000

14,600

21,500

14,400

22,800

14,800

77.0

16,100

13,300

17,300

13,600

18,500

14,000

19,500

14,100

19,800

14,500

21,200

14,300

22,400

14,600

82.0

16,100

13,300

17,000

13,400

18,100

13,900

19,100

13,900

19,400

14,300

20,800

14,100

21,900

14,500

86.0

15,900

13,200

16,700

13,300

17,800

13,800

18,800

13,800

19,100

14,200

20,400

14,000

21,600

14,400

91.0

15,600

13,100

16,400

13,100

17,400

13,600

18,400

13,600

18,700

14,000

20,000

13,900

21,000

14,200

95.0

15,400

13,000

16,200

13,000

17,100

13,500

18,000

13,500

18,300

13,900

19,600

13,700

20,700

14,100

100.0

15,200

12,900

15,800

12,900

16,700

13,300

17,700

13,300

17,900

13,700

19,200

13,600

20,200

13,900

104.0

15,000

12,800

15,600

12,800

16,400

13,200

17,400

13,200

17,600

13,600

18,800

13,400

19,800

13,800

110.0

14,700

12,600

15,200

12,600

15,900

13,000

16,900

13,000

17,100

13,400

18,300

13,300

19,200

13,600

68.0

21,300

16,500

22,900

16,800

24,400

17,400

25,900

17,400

26,400

17,900

28,400

17,800

30,100

18,200

73.0

21,300

16,500

22,900

16,800

24,400

17,400

25,900

17,400

26,400

17,900

28,400

17,800

30,100

18,200

77.0

21,300

16,500

22,900

16,800

24,400

17,400

25,800

17,400

26,200

17,900

28,000

17,600

29,600

18,000

82.0

21,200

16,400

22,500

16,600

23,900

17,100

25,300

17,200

25,700

17,600

27,400

17,400

29,000

17,800

86.0

20,900

16,300

22,100

16,400

23,500

17,000

24,800

17,000

25,200

17,500

27,000

17,200

28,500

17,600

91.0

20,600

16,100

21,700

16,200

23,000

16,700

24,300

16,800

24,600

17,200

26,400

17,000

27,800

17,300

95.0

20,300

16,000

21,400

16,100

22,600

16,600

24,000

16,600

24,200

17,000

25,900

16,800

27,300

17,200

100.0

20,000

15,800

20,900

15,900

22,100

16,300

23,400

16,400

23,700

16,800

25,300

16,600

26,600

16,900

104.0

19,800

15,700

20,600

15,700

21,700

16,200

22,900

16,200

23,200

16,600

24,900

16,400

26,100

16,800

110.0

19,400

15,500

20,100

15,500

21,100

15,900

22,300

15,900

22,600

16,400

24,200

16,200

25,400

16,500

68.0

26,800

22,200

28,800

22,600

30,700

23,400

32,500

23,500

33,200

24,300

35,800

24,100

37,800

24,700

73.0

26,800

22,200

28,800

22,600

30,700

23,400

32,500

23,500

33,200

24,300

35,800

24,100

37,800

24,700

77.0

26,800

22,200

28,800

22,600

30,700

23,400

32,400

23,500

32,900

24,200

35,300

23,900

37,200

24,500

82.0

26,700

22,200

28,200

22,400

30,100

23,200

31,800

23,200

32,200

23,900

34,500

23,600

36,400

24,200

86.0

26,300

22,000

27,800

22,200

29,600

23,000

31,200

23,000

31,700

23,700

33,900

23,400

35,800

24,000

91.0

25,900

21,800

27,300

21,900

28,900

22,700

30,600

22,700

31,000

23,400

33,200

23,100

34,900

23,700

95.0

25,600

21,700

26,800

21,700

28,400

22,500

30,000

22,500

30,400

23,200

32,600

22,900

34,300

23,500

100.0

25,200

21,500

26,300

21,500

27,800

22,200

29,400

22,300

29,800

22,900

31,800

22,600

33,500

23,200

104.0

24,800

21,300

25,900

21,300

27,300

22,000

28,800

22,000

29,200

22,700

31,300

22,400

32,800

23,000

110.0

24,400

21,100

25,200

21,000

26,500

21,600

28,000

21,700

28,400

22,400

30,400

22,100

31,900

22,700

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-11

NOMINAL
CAPACITY
TABLES

30

71degF D.B.

Entering air temp.


80degF D.B.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-1-1. Cooling CapacityPUHY, PURY72~96THMU/YHMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,500

4,200

5,900

4,300

6,300

4,500

6,700

4,500

6,800

4,600

7,300

4,600

7,700

4,700

73.0

5,500

4,200

5,900

4,300

6,300

4,500

6,700

4,500

6,800

4,600

7,300

4,600

7,700

4,700

77.0

5,500

4,200

5,900

4,300

6,300

4,500

6,600

4,500

6,700

4,600

7,200

4,500

7,600

4,600

82.0

5,500

4,200

5,800

4,300

6,200

4,400

6,500

4,400

6,600

4,500

7,100

4,500

7,400

4,600

86.0

5,400

4,200

5,700

4,200

6,000

4,400

6,400

4,400

6,500

4,500

6,900

4,400

7,300

4,500

91.0

5,300

4,100

5,600

4,200

5,900

4,300

6,300

4,300

6,300

4,400

6,800

4,400

7,100

4,400

95.0

5,200

4,100

5,500

4,100

5,800

4,200

6,000

4,300

6,200

4,400

6,700

4,300

7,000

4,400

100.0

5,100

4,100

5,400

4,100

5,700

4,200

6,000

4,200

6,100

4,300

6,500

4,300

6,800

4,300

104.0

5,100

4,000

5,300

4,000

5,600

4,100

5,900

4,200

6,000

4,300

6,400

4,200

6,700

4,300

110.0

5,000

4,000

5,200

4,000

5,400

4,100

5,700

4,100

5,800

4,200

6,200

4,100

6,500

4,200

68.0

7,000

5,500

7,500

5,600

8,000

5,800

8,500

5,800

8,700

6,000

9,300

6,000

9,900

6,100

73.0

7,000

5,500

7,500

5,600

8,000

5,800

8,500

5,800

8,700

6,000

9,300

6,000

9,900

6,100

77.0

7,000

5,500

7,500

5,600

8,000

5,800

8,500

5,800

8,600

6,000

9,200

5,900

9,700

6,000

82.0

7,000

5,500

7,400

5,500

7,900

5,700

8,300

5,700

8,400

5,900

9,000

5,800

9,500

6,000

86.0

6,900

5,400

7,300

5,500

7,700

5,700

8,200

5,700

8,300

5,800

8,900

5,800

9,400

5,900

91.0

6,800

5,400

7,100

5,400

7,600

5,600

8,000

5,600

8,100

5,800

8,700

5,700

9,100

5,800

95.0

6,700

5,400

7,000

5,400

7,400

5,500

8,000

5,600

8,000

5,700

8,500

5,600

9,000

5,800

100.0

6,600

5,300

6,900

5,300

7,300

5,500

7,700

5,500

7,800

5,600

8,300

5,600

8,800

5,700

104.0

6,500

5,300

6,800

5,300

7,100

5,400

7,500

5,400

7,600

5,600

8,200

5,500

8,600

5,600

110.0

6,400

5,200

6,600

5,200

6,900

5,300

7,300

5,300

7,400

5,500

7,900

5,400

8,300

5,500

68.0

10,700

7,500

11,400

7,700

12,200

8,000

12,900

8,000

13,200

8,200

14,200

8,100

15,000

8,300

73.0

10,700

7,500

11,400

7,700

12,200

8,000

12,900

8,000

13,200

8,200

14,200

8,100

15,000

8,300

77.0

10,700

7,500

11,400

7,700

12,200

8,000

12,900

8,000

13,100

8,200

14,000

8,100

14,800

8,200

82.0

10,600

7,500

11,200

7,600

12,000

7,800

12,600

7,900

12,800

8,000

13,700

7,900

14,500

8,000

86.0

10,500

7,400

11,100

7,500

11,800

7,700

12,400

7,800

12,600

7,900

13,500

7,800

14,200

7,900

91.0

10,300

7,400

10,800

7,400

11,500

7,600

12,200

7,600

12,300

7,800

13,200

7,700

13,900

7,800

95.0

10,200

7,300

10,700

7,300

11,300

7,500

12,000

7,500

12,100

7,700

13,000

7,600

13,600

7,700

100.0

10,000

7,200

10,500

7,200

11,000

7,400

11,700

7,400

11,800

7,600

12,700

7,500

13,300

7,600

104.0

9,900

7,100

10,300

7,100

10,800

7,300

11,500

7,300

11,600

7,500

12,400

7,400

13,100

7,500

110.0

9,700

7,000

10,000

7,000

10,500

7,200

11,200

7,200

11,300

7,300

12,100

7,200

12,700

7,300

68.0

13,400

9,600

14,400

9,900

15,300

10,200

16,300

10,200

16,600

10,500

17,900

10,400

18,900

10,600

73.0

13,400

9,600

14,400

9,900

15,300

10,200

16,300

10,200

16,600

10,500

17,900

10,400

18,900

10,600

77.0

13,400

9,600

14,400

9,900

15,300

10,200

16,200

10,200

16,500

10,400

17,600

10,300

18,600

10,400

82.0

13,300

9,600

14,100

9,700

15,000

10,000

15,900

10,000

16,100

10,200

17,200

10,100

18,200

10,300

86.0

13,200

9,500

13,900

9,600

14,800

9,900

15,600

9,900

15,900

10,100

17,000

10,000

17,900

10,200

91.0

13,000

9,400

13,600

9,500

14,500

9,700

15,300

9,700

15,500

10,000

16,600

9,800

17,500

10,000

95.0

12,800

9,300

13,400

9,400

14,200

9,600

15,000

9,600

15,200

9,800

16,300

9,700

17,200

9,900

100.0

12,600

9,200

13,200

9,200

13,900

9,500

14,700

9,500

14,900

9,700

15,900

9,600

16,700

9,700

104.0

12,400

9,100

12,900

9,100

13,600

9,300

14,400

9,400

14,600

9,600

15,600

9,400

16,400

9,600

110.0

12,200

9,000

12,600

9,000

13,200

9,200

14,000

9,200

14,200

9,400

15,200

9,300

15,900

9,400

68.0

16,100

11,800

17,300

12,100

18,500

12,500

19,600

12,500

20,000

12,900

21,500

12,800

22,800

13,000

73.0

16,100

11,800

17,300

12,100

18,500

12,500

19,600

12,500

20,000

12,900

21,500

12,800

22,800

13,000

77.0

16,100

11,800

17,300

12,100

18,500

12,500

19,500

12,500

19,800

12,800

21,200

12,600

22,400

12,900

82.0

16,100

11,800

17,000

11,900

18,100

12,300

19,100

12,300

19,400

12,600

20,800

12,500

21,900

12,700

86.0

15,900

11,700

16,700

11,800

17,800

12,200

18,800

12,200

19,100

12,500

20,400

12,300

21,600

12,500

91.0

15,600

11,600

16,400

11,600

17,400

12,000

18,400

12,000

18,700

12,300

20,000

12,100

21,000

12,300

95.0

15,400

11,500

16,200

11,500

17,100

11,800

18,000

11,900

18,300

12,100

19,600

12,000

20,700

12,200

100.0

15,200

11,300

15,800

11,400

16,700

11,700

17,700

11,700

17,900

12,000

19,200

11,800

20,200

12,000

104.0

15,000

11,200

15,600

11,200

16,400

11,500

17,400

11,500

17,600

11,800

18,800

11,700

19,800

11,900

110.0

14,700

11,100

15,200

11,100

15,900

11,300

16,900

11,300

17,100

11,600

18,300

11,500

19,200

11,700

68.0

21,300

15,100

22,900

15,500

24,400

16,000

25,900

16,000

26,400

16,400

28,400

16,300

30,100

16,600

73.0

21,300

15,100

22,900

15,500

24,400

16,000

25,900

16,000

26,400

16,400

28,400

16,300

30,100

16,600

77.0

21,300

15,100

22,900

15,500

24,400

16,000

25,800

16,000

26,200

16,400

28,000

16,100

29,600

16,400

82.0

21,200

15,100

22,500

15,300

23,900

15,700

25,300

15,800

25,700

16,100

27,400

15,900

29,000

16,100

86.0

20,900

14,900

22,100

15,100

23,500

15,500

24,800

15,600

25,200

15,900

27,000

15,700

28,500

15,900

91.0

20,600

14,800

21,700

14,900

23,000

15,300

24,300

15,300

24,600

15,600

26,400

15,400

27,800

15,700

95.0

20,300

14,600

21,400

14,700

22,600

15,100

24,000

15,100

24,200

15,500

25,900

15,200

27,300

15,500

100.0

20,000

14,400

20,900

14,500

22,100

14,800

23,400

14,900

23,700

15,200

25,300

15,000

26,600

15,200

104.0

19,800

14,300

20,600

14,300

21,700

14,700

22,900

14,700

23,200

15,000

24,900

14,800

26,100

15,000

110.0

19,400

14,100

20,100

14,100

21,100

14,400

22,300

14,400

22,600

14,700

24,200

14,500

25,400

14,700

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-12

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL CApacity Tables in Fahrenheit

DATA U4

1-1-2. Heating CapacityPUHY, PURY72~96THMU/YHMU with All Indoor Units


SHC : Sensible Heat Capacity(BTU/h)
Model
size

06

08

12

15

18

24

Entering air temp.

SHC : Sensible Heat Capacity(BTU/h)


Model
size

Outdoor

Entering air temp.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

81degF D.B.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

degF W.B.

SHC

SHC

SHC

SHC

degF W.B.

SHC

SHC

SHC

SHC

5.0

4,300

4,200

4,200

4,100

5.0

21,400

20,800

20,800

20,500

14.0

5,100

4,900

4,900

4,800

14.0

25,500

24,600

24,300

24,200

23.0

5,900

5,600

5,500

5,000

23.0

29,500

28,200

27,700

24,900

32.0

6,700

6,400

5,700

5,000

32.0

33,500

32,000

28,400

24,900

37.0

7,200

6,700

5,700

5,000

37.0

35,900

34,000

28,400

24,900

43.0

7,400

6,700

5,700

5,000

43.0

36,800

34,000

28,400

24,900

46.0

7,700

6,700

5,700

5,000

46.0

38,700

34,000

28,400

24,900

50.0

8,100

6,700

5,700

5,000

50.0

40,500

34,000

28,400

24,900

55.0

8,700

6,700

5,700

5,000

55.0

43,300

34,000

28,400

24,900

60.0

9,200

6,700

5,700

5,000

60.0

46,100

34,000

28,400

24,900

65.0

9,600

6,700

5,700

5,000

65.0

47,900

34,000

28,400

24,900

5.0

5,600

5,400

5,400

5,300

5.0

25,100

24,400

24,300

24,000

14.0

6,600

6,400

6,300

6,300

14.0

29,800

28,700

28,400

28,300

23.0

7,700

7,300

7,200

6,500

23.0

34,500

33,000

32,500

29,100

32.0

8,700

8,300

7,400

6,500

32.0

39,200

37,400

33,300

29,100

37.0

9,300

9,000

7,400

6,500

37.0

42,000

40,000

33,300

29,100

43.0

9,600

9,000

7,400

6,500

43.0

43,100

40,000

33,300

29,100

46.0

10,100

9,000

7,400

6,500

46.0

45,200

40,000

33,300

29,100

50.0

10,500

9,000

7,400

6,500

50.0

47,400

40,000

33,300

29,100

55.0

11,300

9,000

7,400

6,500

55.0

50,700

40,000

33,300

29,100

60.0

12,000

9,000

7,400

6,500

60.0

53,900

40,000

33,300

29,100

65.0

12,500

9,000

7,400

6,500

65.0

56,000

40,000

33,300

29,100

5.0

8,600

8,300

8,300

8,200

5.0

33,900

32,900

32,800

32,500

30

36

81degF D.B.

14.0

10,200

9,800

9,700

9,700

14.0

40,200

38,800

38,300

38,200

23.0

11,800

11,300

11,100

9,900

23.0

46,600

44,600

43,800

39,300

32.0

13,400

12,800

11,400

9,900

37.0

14,400

13,500

11,400

9,900

48

32.0

52,900

50,500

44,900

39,300

37.0

56,700

54,000

44,900

39,300

43.0

14,700

13,500

11,400

9,900

43.0

58,200

54,000

44,900

39,300

46.0

15,500

13,500

11,400

9,900

46.0

61,100

54,000

44,900

39,300

50.0

16,200

13,500

11,400

9,900

50.0

64,000

54,000

44,900

39,300

55.0

17,300

13,500

11,400

9,900

55.0

68,400

54,000

44,900

39,300

60.0

18,400

13,500

11,400

9,900

60.0

72,800

54,000

44,900

39,300

65.0

19,200

13,500

11,400

9,900

65.0

75,700

54,000

44,900

39,300

5.0

10,700

10,400

10,400

10,300

5.0

37,700

36,600

36,600

36,200

14.0

12,700

12,300

12,100

12,100

14.0

44,800

43,200

42,700

42,500

23.0

14,700

14,100

13,900

12,400

23.0

51,900

49,700

48,800

43,800

32.0

16,700

16,000

14,200

12,400

32.0

58,900

56,300

50,000

43,800

37.0

17,900

17,000

14,200

12,400

37.0

63,200

60,000

50,000

43,800

43.0

18,400

17,000

14,200

12,400

43.0

64,800

60,000

50,000

43,800

46.0

19,300

17,000

14,200

12,400

46.0

68,000

60,000

50,000

43,800

50.0

20,300

17,000

14,200

12,400

50.0

71,300

60,000

50,000

43,800

55.0

21,600

17,000

14,200

12,400

55.0

76,200

60,000

50,000

43,800

60.0

23,000

17,000

14,200

12,400

60.0

81,100

60,000

50,000

43,800

65.0

24,000

17,000

14,200

12,400

65.0

84,300

60,000

50,000

43,800

5.0

12,600

12,300

12,300

12,100

5.0

50,100

48,700

48,600

48,100

14.0

15,000

14,500

14,300

14,300

14.0

59,600

57,500

56,800

56,500

23.0

17,400

16,600

16,400

14,700

23.0

69,000

66,000

64,900

58,200

32.0

19,700

18,900

16,800

14,700

32.0

78,300

74,800

66,500

58,200

37.0

21,200

20,000

16,800

14,700

37.0

84,000

80,000

66,500

58,200

43.0

21,700

20,000

16,800

14,700

43.0

86,100

80,000

66,500

58,200

46.0

22,800

20,000

16,800

14,700

46.0

90,500

80,000

66,500

58,200

50.0

23,900

20,000

16,800

14,700

50.0

94,800

80,000

66,500

58,200

55.0

25,500

20,000

16,800

14,700

55.0

101,300

80,000

66,500

58,200

60.0

27,200

20,000

16,800

14,700

60.0

107,800

80,000

66,500

58,200

65.0

28,300

20,000

16,800

14,700

65.0

112,100

80,000

66,500

58,200

5.0

16,900

16,400

16,400

16,200

5.0

67,900

66,000

65,900

65,100

14.0

20,100

19,400

19,200

19,100

14.0

80,700

77,900

76,900

76,600

23.0

23,300

22,300

21,900

19,700

23.0

93,500

89,400

87,900

78,800

32.0

26,400

25,300

22,500

19,700

32.0

106,100

101,300

90,100

78,800

37.0

28,400

27,000

22,500

19,700

37.0

113,800

108,000

90,100

78,800

43.0

29,100

27,000

22,500

19,700

43.0

116,700

108,000

90,100

78,800

46.0

30,500

27,000

22,500

19,700

46.0

122,500

108,000

90,100

78,800

50.0

32,000

27,000

22,500

19,700

50.0

128,400

108,000

90,100

78,800

55.0

34,200

27,000

22,500

19,700

55.0

137,300

108,000

90,100

78,800

60.0

36,400

27,000

22,500

19,700

60.0

146,000

108,000

90,100

78,800

65.0

37,800

27,000

22,500

19,700

65.0

151,900

108,000

90,100

78,800

5.0

18,900

18,300

18,300

18,100

14.0

22,400

21,600

21,300

21,300

23.0

25,900

24,800

24,400

21,900

32.0

29,500

28,100

25,000

21,900

37.0

31,600

30,000

25,000

21,900

43.0

32,400

30,000

25,000

21,900

46.0

34,000

30,000

25,000

21,900

50.0

35,600

30,000

25,000

21,900

55.0

38,100

30,000

25,000

21,900

60.0

40,500

30,000

25,000

21,900

65.0

42,200

30,000

25,000

21,900

54

72

96

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

27

Outdoor

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-13

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2. Cooing and Heating Capacity with PUHY-P120~144, PURY-P120T(S)HMU-A/Y(S)HMU-A


1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PEFY-NMSU-E
CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

5,300

6,100

5,200

6,500

5,500

6,800

5,400

7,000

5,700

7,500

5,600

7,800

5,700

73.0

5,800

5,300

6,000

5,200

6,400

5,400

6,700

5,400

6,800

5,600

7,300

5,500

7,700

5,700

77.0

5,800

5,200

5,900

5,200

6,300

5,400

6,500

5,400

6,700

5,600

7,200

5,500

7,500

5,600

82.0

5,700

5,200

5,800

5,100

6,100

5,300

6,400

5,300

6,600

5,500

7,000

5,400

7,400

5,600

86.0

5,600

5,100

5,700

5,100

6,000

5,300

6,300

5,300

6,500

5,500

6,900

5,400

7,200

5,500

91.0

5,500

5,100

5,600

5,000

5,900

5,200

6,200

5,200

6,300

5,400

6,700

5,300

7,100

5,500

95.0

5,400

5,000

5,500

5,000

5,800

5,200

6,000

5,200

6,200

5,400

6,600

5,300

6,900

5,400

100.0

5,300

5,000

5,400

4,900

5,700

5,100

5,900

5,100

6,100

5,300

6,500

5,200

6,800

5,400

104.0

5,200

5,000

5,300

4,900

5,500

5,100

5,800

5,100

5,900

5,300

6,300

5,200

6,700

5,400

110.0

5,100

4,900

5,100

4,800

5,400

5,000

5,600

5,000

5,800

5,200

6,200

5,100

6,500

5,300

68.0

7,800

6,800

8,000

6,800

8,600

7,000

9,000

7,000

9,200

7,300

9,900

7,200

10,300

7,400

73.0

7,700

6,800

8,000

6,700

8,400

7,000

8,800

6,900

9,000

7,200

9,700

7,100

10,100

7,300

77.0

7,600

6,700

7,800

6,700

8,300

6,900

8,700

6,900

8,900

7,200

9,500

7,100

10,000

7,200

82.0

7,500

6,700

7,700

6,600

8,100

6,800

8,500

6,800

8,700

7,100

9,300

7,000

9,700

7,200

86.0

7,400

6,600

7,600

6,600

8,000

6,800

8,300

6,800

8,500

7,000

9,100

6,900

9,600

7,100

91.0

7,200

6,500

7,400

6,500

7,800

6,700

8,100

6,700

8,300

7,000

8,900

6,900

9,300

7,000

95.0

7,100

6,500

7,200

6,400

7,700

6,600

8,000

6,600

8,200

6,900

8,800

6,800

9,200

7,000

100.0

7,000

6,400

7,100

6,400

7,500

6,600

7,800

6,600

8,000

6,800

8,500

6,700

9,000

6,900

104.0

6,900

6,400

7,000

6,300

7,300

6,500

7,600

6,500

7,800

6,800

8,400

6,700

8,800

6,900

110.0

6,700

6,300

6,800

6,200

7,100

6,400

7,400

6,400

7,600

6,700

8,100

6,600

8,500

6,800

68.0

11,700

9,100

12,100

9,000

12,900

9,300

13,500

9,300

13,900

9,600

14,800

9,500

15,600

9,700

73.0

11,600

9,000

12,000

9,000

12,700

9,300

13,200

9,200

13,600

9,500

14,500

9,400

15,200

9,600

77.0

11,400

9,000

11,800

8,900

12,500

9,200

13,000

9,100

13,400

9,400

14,300

9,300

15,000

9,500

82.0

11,200

8,900

11,600

8,800

12,200

9,000

12,700

9,000

13,100

9,300

14,000

9,200

14,700

9,400

86.0

11,100

8,800

11,400

8,700

12,000

9,000

12,500

8,900

12,800

9,200

13,700

9,100

14,400

9,300

91.0

10,900

8,700

11,100

8,600

11,700

8,800

12,200

8,800

12,600

9,100

13,400

9,000

14,100

9,200

95.0

10,700

8,600

10,900

8,500

11,500

8,700

12,000

8,700

12,300

9,000

13,200

8,900

13,800

9,100

100.0

10,500

8,500

10,700

8,400

11,200

8,600

11,700

8,600

12,000

8,900

12,900

8,800

13,500

9,000

104.0

10,300

8,400

10,500

8,300

11,000

8,500

11,500

8,500

11,800

8,800

12,600

8,700

13,200

8,900

110.0

10,100

8,300

10,200

8,200

10,700

8,400

11,200

8,400

11,500

8,700

12,300

8,600

12,900

8,700

68.0

14,600

10,900

15,100

10,800

16,100

11,200

16,900

11,200

17,300

11,500

18,500

11,400

19,400

11,500

73.0

14,500

10,800

15,000

10,800

15,900

11,100

16,500

11,000

17,000

11,400

18,200

11,200

19,000

11,400

77.0

14,300

10,700

14,800

10,700

15,600

11,000

16,300

10,900

16,700

11,300

17,800

11,100

18,700

11,300

82.0

14,100

10,600

14,400

10,500

15,300

10,800

15,900

10,700

16,300

11,100

17,500

11,000

18,300

11,100

86.0

13,800

10,500

14,200

10,400

15,000

10,700

15,600

10,600

16,000

11,000

17,100

10,800

18,000

11,000

91.0

13,600

10,400

13,900

10,300

14,700

10,500

15,300

10,500

15,700

10,800

16,800

10,700

17,600

10,900

95.0

13,400

10,300

13,600

10,100

14,400

10,400

15,000

10,400

15,400

10,700

16,500

10,600

17,300

10,800

100.0

13,100

10,200

13,300

10,000

14,100

10,300

14,700

10,200

15,000

10,600

16,100

10,400

16,900

10,600

104.0

12,900

10,100

13,100

9,900

13,800

10,200

14,400

10,100

14,800

10,400

15,800

10,300

16,500

10,500

110.0

12,600

9,900

12,700

9,700

13,400

10,000

14,000

9,900

14,300

10,300

15,300

10,100

16,100

10,300

68.0

17,500

13,400

18,100

13,400

19,300

13,800

20,300

13,800

20,800

14,300

22,200

14,100

23,300

14,300

73.0

17,400

13,400

18,000

13,300

19,000

13,700

19,900

13,600

20,400

14,100

21,800

13,900

22,800

14,100

77.0

17,200

13,300

17,700

13,200

18,700

13,500

19,500

13,500

20,000

13,900

21,400

13,700

22,500

14,000

82.0

16,900

13,100

17,300

13,000

18,300

13,400

19,100

13,300

19,600

13,800

21,000

13,600

22,000

13,800

86.0

16,600

13,000

17,000

12,900

18,000

13,200

18,800

13,200

19,300

13,600

20,600

13,400

21,600

13,700

91.0

16,300

12,800

16,700

12,700

17,600

13,000

18,400

13,000

18,800

13,400

20,100

13,300

21,100

13,500

95.0

16,100

12,700

16,400

12,500

17,300

12,900

18,000

12,800

18,500

13,300

19,700

13,100

20,700

13,400

100.0

15,700

12,600

16,000

12,400

16,900

12,700

17,600

12,700

18,100

13,100

19,300

12,900

20,200

13,200

104.0

15,500

12,400

15,700

12,200

16,500

12,600

17,300

12,500

17,700

13,000

18,900

12,800

19,900

13,100

110.0

15,100

12,300

15,200

12,000

16,100

12,400

16,800

12,300

17,200

12,800

18,400

12,600

19,300

12,900

68.0

23,300

17,700

24,100

17,600

25,700

18,200

26,900

18,200

27,700

18,800

29,600

18,500

31,000

18,800

73.0

23,200

17,600

24,000

17,600

25,300

18,100

26,400

17,900

27,100

18,500

29,000

18,300

30,400

18,600

77.0

22,800

17,500

23,500

17,400

24,900

17,900

26,000

17,800

26,600

18,400

28,500

18,100

29,900

18,400

82.0

22,400

17,300

23,000

17,100

24,400

17,600

25,400

17,500

26,100

18,100

27,900

17,900

29,200

18,200

86.0

22,100

17,100

22,700

17,000

23,900

17,400

25,000

17,300

25,600

17,900

27,400

17,700

28,700

18,000

91.0

21,700

16,900

22,200

16,700

23,400

17,200

24,400

17,100

25,000

17,700

26,800

17,500

28,000

17,800

95.0

21,300

16,800

21,700

16,500

23,000

17,000

24,000

16,900

24,600

17,500

26,300

17,300

27,500

17,600

100.0

20,900

16,600

21,200

16,300

22,400

16,800

23,400

16,700

24,000

17,300

25,600

17,000

26,900

17,400

104.0

20,600

16,400

20,900

16,100

22,000

16,600

22,900

16,500

23,500

17,100

25,100

16,900

26,400

17,200

110.0

20,100

16,200

20,300

15,900

21,400

16,300

22,300

16,200

22,900

16,800

24,400

16,600

25,600

16,900

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-14

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PEFY-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,600

10,000

15,100

10,000

16,100

10,300

16,900

10,200

17,300

10,500

18,500

10,400

19,400

10,400

73.0

14,500

9,900

15,000

9,900

15,900

10,100

16,500

10,000

17,000

10,300

18,200

10,200

19,000

10,300

77.0

14,300

9,800

14,800

9,800

15,600

10,000

16,300

9,900

16,700

10,200

17,800

10,000

18,700

10,100

82.0

14,100

9,700

14,400

9,600

15,300

9,800

15,900

9,700

16,300

10,000

17,500

9,900

18,300

10,000

86.0

13,800

9,600

14,200

9,500

15,000

9,700

15,600

9,600

16,000

9,900

17,100

9,700

18,000

9,800

91.0

13,600

9,400

13,900

9,300

14,700

9,500

15,300

9,400

15,700

9,700

16,800

9,600

17,600

9,600

95.0

13,400

9,300

13,600

9,200

14,400

9,400

15,000

9,300

15,400

9,500

16,500

9,400

17,300

9,500

100.0

13,100

9,200

13,300

9,000

14,100

9,200

14,700

9,100

15,000

9,400

16,100

9,200

16,900

9,300

104.0

12,900

9,000

13,100

8,900

13,800

9,000

14,400

9,000

14,800

9,200

15,800

9,100

16,500

9,200

110.0

12,600

8,900

12,700

8,700

13,400

8,800

14,000

8,800

14,300

9,000

15,300

8,900

16,100

9,000

68.0

17,600

12,100

18,200

12,100

19,400

12,500

20,300

12,400

20,900

12,800

22,300

12,600

23,400

12,700

73.0

17,500

12,100

18,100

12,100

19,100

12,300

19,900

12,200

20,500

12,600

21,900

12,400

22,900

12,500

77.0

17,200

12,000

17,800

11,900

18,800

12,200

19,600

12,100

20,100

12,400

21,500

12,200

22,600

12,400

82.0

16,900

11,800

17,400

11,700

18,400

12,000

19,200

11,900

19,700

12,200

21,000

12,000

22,100

12,200

86.0

16,700

11,700

17,100

11,500

18,100

11,800

18,800

11,700

19,300

12,000

20,700

11,900

21,700

12,000

91.0

16,400

11,500

16,700

11,300

17,600

11,600

18,400

11,500

18,900

11,800

20,200

11,700

21,200

11,800

95.0

16,100

11,400

16,400

11,200

17,300

11,400

18,000

11,400

18,600

11,700

19,800

11,500

20,800

11,700

100.0

15,800

11,200

16,000

11,000

16,900

11,200

17,700

11,200

18,100

11,500

19,300

11,300

20,300

11,500

104.0

15,600

11,100

15,800

10,800

16,600

11,100

17,300

11,000

17,800

11,300

19,000

11,200

19,900

11,300

110.0

15,200

10,900

15,300

10,600

16,100

10,800

16,800

10,800

17,300

11,100

18,400

11,000

19,300

11,100

68.0

23,200

16,000

24,000

15,900

25,700

16,400

26,900

16,400

27,600

16,800

29,500

16,600

30,900

16,700

73.0

23,100

15,900

23,900

15,900

25,200

16,200

26,300

16,100

27,000

16,500

28,900

16,300

30,300

16,500

77.0

22,800

15,700

23,500

15,600

24,800

16,000

25,900

15,900

26,600

16,300

28,400

16,100

29,800

16,200

82.0

22,400

15,500

23,000

15,400

24,300

15,700

25,300

15,600

26,000

16,000

27,800

15,800

29,100

16,000

86.0

22,000

15,300

22,600

15,200

23,900

15,500

24,900

15,400

25,500

15,800

27,300

15,600

28,600

15,800

91.0

21,600

15,100

22,100

14,900

23,300

15,200

24,300

15,100

25,000

15,500

26,700

15,300

28,000

15,500

95.0

21,300

14,900

21,700

14,700

22,900

15,000

24,000

14,900

24,500

15,300

26,200

15,100

27,500

15,300

100.0

20,900

14,700

21,200

14,400

22,400

14,700

23,300

14,600

23,900

15,100

25,600

14,900

26,800

15,000

104.0

20,500

14,500

20,800

14,200

21,900

14,500

22,900

14,400

23,500

14,900

25,100

14,700

26,300

14,800

110.0

20,100

14,300

20,200

13,900

21,300

14,200

22,200

14,100

22,800

14,600

24,400

14,400

25,600

14,500

68.0

26,200

18,200

27,100

18,200

28,900

18,800

30,300

18,700

31,100

19,200

33,300

19,000

34,900

19,200

73.0

26,100

18,200

27,000

18,100

28,500

18,500

29,700

18,400

30,500

18,900

32,600

18,700

34,200

18,900

77.0

25,700

18,000

26,500

17,900

28,000

18,300

29,200

18,200

30,000

18,700

32,000

18,400

33,600

18,600

82.0

25,200

17,700

25,900

17,600

27,400

18,000

28,600

17,800

29,300

18,400

31,300

18,100

32,900

18,300

86.0

24,900

17,500

25,500

17,400

26,900

17,700

28,100

17,600

28,800

18,100

30,800

17,900

32,300

18,100

91.0

24,400

17,300

24,900

17,100

26,300

17,400

27,500

17,300

28,200

17,800

30,100

17,600

31,600

17,800

95.0

24,000

17,100

24,500

16,800

25,800

17,200

27,000

17,100

27,700

17,600

29,500

17,400

31,000

17,600

100.0

23,600

16,800

23,900

16,500

25,200

16,900

26,300

16,800

27,000

17,300

28,800

17,100

30,300

17,300

104.0

23,200

16,600

23,500

16,300

24,700

16,700

25,800

16,600

26,500

17,100

28,300

16,900

29,700

17,100

110.0

22,600

16,400

22,800

16,000

24,000

16,400

25,100

16,300

25,700

16,800

27,500

16,500

28,800

16,700

68.0

29,200

20,300

30,200

20,200

32,200

20,900

33,800

20,800

34,700

21,400

37,100

21,100

38,900

21,300

73.0

29,000

20,200

30,000

20,200

31,700

20,600

33,100

20,400

34,000

21,000

36,300

20,800

38,100

21,000

77.0

28,600

20,000

29,500

19,900

31,200

20,300

32,500

20,200

33,400

20,800

35,700

20,500

37,400

20,700

82.0

28,100

19,700

28,900

19,600

30,500

20,000

31,800

19,800

32,700

20,400

34,900

20,200

36,600

20,400

86.0

27,700

19,500

28,400

19,300

30,000

19,700

31,300

19,600

32,100

20,200

34,300

19,900

36,000

20,100

91.0

27,200

19,200

27,800

19,000

29,300

19,400

30,600

19,300

31,400

19,800

33,500

19,600

35,200

19,800

95.0

26,800

19,000

27,300

18,700

28,800

19,100

30,000

19,000

30,800

19,600

32,900

19,300

34,500

19,500

100.0

26,200

18,700

26,600

18,400

28,100

18,800

29,300

18,700

30,100

19,300

32,100

19,000

33,700

19,200

104.0

25,800

18,500

26,200

18,100

27,600

18,600

28,800

18,400

29,500

19,000

31,500

18,700

33,100

19,000

110.0

25,200

18,200

25,400

17,800

26,800

18,200

28,000

18,100

28,700

18,600

30,600

18,400

32,100

18,600

68.0

35,100

25,000

36,300

24,900

38,800

25,700

40,700

25,600

41,800

26,400

44,700

26,000

46,800

26,300

73.0

35,000

24,900

36,200

24,800

38,200

25,400

39,900

25,200

40,900

26,000

43,700

25,600

45,900

25,900

77.0

34,500

24,600

35,600

24,500

37,600

25,100

39,200

24,900

40,200

25,700

43,000

25,300

45,100

25,600

82.0

33,900

24,300

34,800

24,100

36,800

24,700

38,300

24,500

39,300

25,300

42,100

24,900

44,100

25,300

86.0

33,300

24,000

34,200

23,800

36,100

24,400

37,700

24,200

38,700

25,000

41,300

24,600

43,400

25,000

91.0

32,700

23,700

33,500

23,400

35,300

24,000

36,900

23,800

37,800

24,600

40,400

24,300

42,400

24,600

95.0

32,200

23,500

32,800

23,100

34,700

23,700

36,000

23,500

37,100

24,300

39,600

23,900

41,600

24,300

100.0

31,600

23,100

32,100

22,800

33,900

23,300

35,300

23,200

36,200

23,900

38,700

23,600

40,600

23,900

104.0

31,100

22,900

31,500

22,500

33,200

23,000

34,600

22,900

35,600

23,600

38,000

23,300

39,900

23,600

110.0

30,400

22,500

30,600

22,000

32,300

22,600

33,700

22,500

34,500

23,200

36,900

22,800

38,700

23,200

68.0

46,700

32,100

48,300

32,000

51,700

33,000

54,100

32,800

55,600

33,700

59,400

33,300

62,300

33,600

73.0

46,500

32,000

48,100

31,900

50,900

32,500

53,000

32,300

54,400

33,200

58,200

32,800

61,000

33,000

77.0

45,800

31,600

47,300

31,400

50,000

32,100

52,200

31,900

53,500

32,700

57,200

32,300

60,000

32,600

82.0

45,000

31,100

46,300

30,900

48,900

31,500

51,000

31,300

52,300

32,200

56,000

31,800

58,700

32,100

86.0

44,400

30,800

45,500

30,500

48,100

31,100

50,100

30,900

51,400

31,700

54,900

31,300

57,700

31,600

91.0

43,500

30,300

44,500

29,900

47,000

30,500

49,000

30,300

50,300

31,200

53,700

30,800

56,300

31,100

95.0

42,900

29,900

43,700

29,500

46,100

30,100

48,000

29,900

49,400

30,800

52,700

30,300

55,300

30,700

100.0

42,000

29,500

42,700

28,900

45,000

29,600

47,000

29,400

48,200

30,200

51,500

29,800

54,000

30,100

104.0

41,400

29,100

41,900

28,500

44,200

29,100

46,100

28,900

47,300

29,800

50,500

29,400

53,000

29,700

110.0

40,400

28,600

40,700

27,900

42,900

28,500

44,800

28,300

45,900

29,200

49,100

28,800

51,500

29,100

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-15

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PEFY-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

52,300

36,900

54,200

36,800

57,900

38,000

60,600

37,800

62,300

38,900

66,600

38,400

69,800

38,800

73.0

52,100

36,800

53,900

36,700

57,000

37,500

59,400

37,200

61,000

38,300

65,200

37,800

68,400

38,300

77.0

51,400

36,400

53,000

36,200

56,000

37,100

58,400

36,800

59,900

37,900

64,000

37,400

67,200

37,800

82.0

50,500

35,900

51,900

35,600

54,800

36,500

57,100

36,200

58,700

37,300

62,700

36,800

65,800

37,200

86.0

49,700

35,500

51,000

35,200

53,900

36,000

56,200

35,800

57,600

36,800

61,600

36,300

64,600

36,800

91.0

48,800

35,000

49,900

34,600

52,600

35,400

54,900

35,200

56,300

36,300

60,200

35,800

63,100

36,200

95.0

48,000

34,600

48,900

34,100

51,700

35,000

54,000

34,700

55,300

35,800

59,100

35,300

62,000

35,800

100.0

47,100

34,200

47,800

33,600

50,500

34,400

52,700

34,200

54,000

35,200

57,700

34,700

60,500

35,200

104.0

46,400

33,800

47,000

33,200

49,500

33,900

51,600

33,700

53,000

34,800

56,600

34,300

59,400

34,800

110.0

45,300

33,200

45,600

32,500

48,100

33,300

50,200

33,100

51,500

34,100

55,000

33,700

57,700

34,200

68.0

69,900

48,600

72,400

48,500

77,300

50,000

81,000

49,800

83,200

51,200

88,900

50,600

93,200

51,000

73.0

69,600

48,500

72,000

48,300

76,100

49,400

79,300

49,000

81,400

50,400

87,000

49,700

91,300

50,200

77.0

68,600

47,900

70,800

47,600

74,800

48,700

78,000

48,400

80,100

49,700

85,500

49,100

89,800

49,600

82.0

67,400

47,200

69,300

46,800

73,200

47,900

76,300

47,500

78,300

48,900

83,700

48,300

87,800

48,800

86.0

66,400

46,700

68,100

46,200

71,900

47,300

75,000

46,900

77,000

48,300

82,200

47,600

86,300

48,200

91.0

65,200

46,000

66,600

45,500

70,300

46,500

73,400

46,200

75,200

47,500

80,400

46,900

84,300

47,400

95.0

64,100

45,500

65,400

44,800

69,000

45,900

72,000

45,500

73,900

46,900

78,900

46,200

82,800

46,800

100.0

62,900

44,800

63,900

44,100

67,400

45,100

70,300

44,800

72,100

46,100

77,000

45,500

80,800

46,000

104.0

61,900

44,300

62,700

43,500

66,100

44,400

69,000

44,200

70,800

45,500

75,600

44,900

79,300

45,500

110.0

60,500

43,600

60,900

42,600

64,200

43,500

67,000

43,300

68,800

44,600

73,400

44,000

77,000

44,600

68.0

93,100

65,200

96,400

65,000

103,000

67,100

107,900

66,800

110,700

68,700

118,400

67,800

124,200

68,500

73.0

92,700

65,000

95,900

64,800

101,300

66,300

105,700

65,700

108,400

67,600

115,900

66,800

121,600

67,500

77.0

91,400

64,300

94,200

63,900

99,600

65,400

103,900

64,900

106,600

66,800

113,900

65,900

119,600

66,600

82.0

89,700

63,400

92,200

62,900

97,500

64,300

101,600

63,800

104,300

65,700

111,500

64,900

117,000

65,600

86.0

88,400

62,700

90,700

62,100

95,800

63,500

99,900

63,000

102,500

64,900

109,500

64,000

115,000

64,800

91.0

86,800

61,800

88,700

61,000

93,600

62,400

97,700

62,000

100,200

63,900

107,100

63,000

112,300

63,800

95.0

85,400

61,100

87,100

60,200

91,900

61,600

96,000

61,200

98,400

63,100

105,100

62,200

110,300

63,000

100.0

83,800

60,200

85,000

59,200

89,700

60,600

93,700

60,200

96,100

62,000

102,600

61,200

107,700

62,000

104.0

82,500

59,500

83,500

58,400

88,000

59,800

91,900

59,400

94,200

61,200

100,700

60,400

105,700

61,200

110.0

80,500

58,500

81,100

57,200

85,500

58,600

89,300

58,200

91,600

60,100

97,800

59,200

102,600

60,100

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-16

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PDFY-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

6,000

4,500

6,200

4,500

6,600

4,700

6,900

4,700

7,100

4,800

7,600

4,800

8,000

4,800

73.0

5,900

4,500

6,100

4,500

6,500

4,600

6,800

4,600

6,900

4,800

7,400

4,700

7,800

4,800

77.0

5,900

4,500

6,000

4,500

6,400

4,600

6,700

4,600

6,800

4,700

7,300

4,700

7,700

4,700

82.0

5,700

4,400

5,900

4,400

6,200

4,500

6,500

4,500

6,700

4,700

7,100

4,600

7,500

4,700

86.0

5,700

4,400

5,800

4,400

6,100

4,500

6,400

4,500

6,600

4,600

7,000

4,500

7,400

4,600

91.0

5,600

4,300

5,700

4,300

6,000

4,400

6,300

4,400

6,400

4,500

6,900

4,500

7,200

4,600

95.0

5,500

4,300

5,600

4,200

5,900

4,400

6,000

4,300

6,300

4,500

6,700

4,400

7,100

4,500

100.0

5,400

4,300

5,400

4,200

5,700

4,300

6,000

4,300

6,200

4,400

6,600

4,400

6,900

4,500

104.0

5,300

4,200

5,300

4,100

5,600

4,300

5,900

4,200

6,000

4,400

6,400

4,300

6,800

4,400

110.0

5,200

4,200

5,200

4,100

5,500

4,200

5,700

4,200

5,900

4,300

6,300

4,300

6,600

4,400

68.0

7,600

5,600

7,900

5,600

8,400

5,700

8,800

5,700

9,100

5,900

9,700

5,800

10,200

5,900
5,800

73.0

7,600

5,600

7,800

5,500

8,300

5,700

8,600

5,600

8,900

5,800

9,500

5,700

10,000

77.0

7,500

5,500

7,700

5,500

8,200

5,600

8,500

5,600

8,700

5,800

9,300

5,700

9,800

5,800

82.0

7,300

5,400

7,500

5,400

8,000

5,500

8,300

5,500

8,500

5,700

9,100

5,600

9,600

5,700

86.0

7,200

5,400

7,400

5,300

7,800

5,500

8,200

5,400

8,400

5,600

9,000

5,500

9,400

5,600

91.0

7,100

5,300

7,300

5,300

7,700

5,400

8,000

5,400

8,200

5,500

8,800

5,500

9,200

5,500

95.0

7,000

5,300

7,100

5,200

7,500

5,300

8,000

5,300

8,100

5,500

8,600

5,400

9,000

5,500

100.0

6,900

5,200

7,000

5,100

7,300

5,200

7,700

5,200

7,900

5,400

8,400

5,300

8,800

5,400

104.0

6,700

5,100

6,800

5,000

7,200

5,200

7,500

5,200

7,700

5,300

8,200

5,300

8,600

5,300

110.0

6,600

5,100

6,600

5,000

7,000

5,100

7,300

5,100

7,500

5,200

8,000

5,200

8,400

5,300

68.0

11,600

8,100

12,000

8,100

12,800

8,300

13,400

8,300

13,800

8,500

14,700

8,400

15,500

8,500

73.0

11,500

8,100

11,900

8,000

12,600

8,200

13,200

8,200

13,500

8,400

14,400

8,300

15,100

8,400

77.0

11,400

8,000

11,700

7,900

12,400

8,100

12,900

8,100

13,300

8,300

14,200

8,200

14,900

8,300

82.0

11,200

7,900

11,500

7,800

12,100

8,000

12,700

7,900

13,000

8,200

13,900

8,100

14,600

8,100

86.0

11,000

7,800

11,300

7,700

11,900

7,900

12,400

7,800

12,800

8,100

13,600

7,900

14,300

8,000

91.0

10,800

7,700

11,000

7,600

11,700

7,700

12,200

7,700

12,500

7,900

13,300

7,800

14,000

7,900

95.0

10,600

7,600

10,800

7,500

11,500

7,600

12,000

7,600

12,300

7,800

13,100

7,700

13,700

7,800

100.0

10,400

7,500

10,600

7,300

11,200

7,500

11,700

7,500

12,000

7,700

12,800

7,600

13,400

7,700

104.0

10,300

7,400

10,400

7,200

11,000

7,400

11,400

7,400

11,700

7,600

12,500

7,500

13,200

7,600

110.0

10,000

7,300

10,100

7,100

10,700

7,300

11,100

7,200

11,400

7,400

12,200

7,300

12,800

7,400

68.0

14,600

11,000

15,100

10,900

16,100

11,300

16,900

11,300

17,300

11,600

18,500

11,500

19,400

11,600

73.0

14,500

10,900

15,000

10,900

15,900

11,200

16,500

11,100

17,000

11,500

18,200

11,300

19,000

11,500

77.0

14,300

10,800

14,800

10,800

15,600

11,100

16,300

11,000

16,700

11,400

17,800

11,200

18,700

11,400

82.0

14,100

10,700

14,400

10,600

15,300

10,900

15,900

10,800

16,300

11,200

17,500

11,100

18,300

11,200

86.0

13,800

10,600

14,200

10,500

15,000

10,800

15,600

10,700

16,000

11,100

17,100

10,900

18,000

11,100

91.0

13,600

10,500

13,900

10,400

14,700

10,600

15,300

10,600

15,700

10,900

16,800

10,800

17,600

11,000

95.0

13,400

10,400

13,600

10,200

14,400

10,500

15,000

10,500

15,400

10,800

16,500

10,700

17,300

10,900

100.0

13,100

10,200

13,300

10,100

14,100

10,400

14,700

10,300

15,000

10,700

16,100

10,500

16,900

10,700

104.0

12,900

10,100

13,100

10,000

13,800

10,200

14,400

10,200

14,800

10,600

15,800

10,400

16,500

10,600

110.0

12,600

10,000

12,700

9,800

13,400

10,100

14,000

10,000

14,300

10,400

15,300

10,200

16,100

10,400

68.0

17,600

12,900

18,200

12,900

19,400

13,300

20,300

13,300

20,900

13,700

22,300

13,500

23,400

13,700

73.0

17,500

12,900

18,100

12,900

19,100

13,200

19,900

13,100

20,500

13,500

21,900

13,300

22,900

13,500

77.0

17,200

12,800

17,800

12,700

18,800

13,000

19,600

13,000

20,100

13,400

21,500

13,200

22,600

13,400

82.0

16,900

12,600

17,400

12,500

18,400

12,800

19,200

12,800

19,700

13,200

21,000

13,000

22,100

13,200

86.0

16,700

12,500

17,100

12,400

18,100

12,700

18,800

12,600

19,300

13,000

20,700

12,900

21,700

13,100

91.0

16,400

12,300

16,700

12,200

17,600

12,500

18,400

12,400

18,900

12,900

20,200

12,700

21,200

12,900

95.0

16,100

12,200

16,400

12,000

17,300

12,400

18,000

12,300

18,600

12,700

19,800

12,500

20,800

12,700

100.0

15,800

12,100

16,000

11,900

16,900

12,200

17,700

12,100

18,100

12,500

19,300

12,300

20,300

12,600

104.0

15,600

11,900

15,800

11,700

16,600

12,000

17,300

12,000

17,800

12,400

19,000

12,200

19,900

12,400

110.0

15,200

11,800

15,300

11,500

16,100

11,800

16,800

11,800

17,300

12,200

18,400

12,000

19,300

12,200

68.0

23,200

17,000

24,000

17,000

25,700

17,500

26,900

17,500

27,600

18,000

29,500

17,800

30,900

18,000

73.0

23,100

17,000

23,900

16,900

25,200

17,300

26,300

17,200

27,000

17,800

28,900

17,500

30,300

17,800

77.0

22,800

16,800

23,500

16,700

24,800

17,100

25,900

17,000

26,600

17,600

28,400

17,300

29,800

17,600

82.0

22,400

16,600

23,000

16,500

24,300

16,900

25,300

16,800

26,000

17,300

27,800

17,100

29,100

17,400

86.0

22,000

16,400

22,600

16,300

23,900

16,700

24,900

16,600

25,500

17,100

27,300

16,900

28,600

17,200

91.0

21,600

16,200

22,100

16,000

23,300

16,500

24,300

16,400

25,000

16,900

26,700

16,700

28,000

16,900

95.0

21,300

16,100

21,700

15,800

22,900

16,300

24,000

16,200

24,500

16,700

26,200

16,500

27,500

16,700

100.0

20,900

15,900

21,200

15,600

22,400

16,000

23,300

15,900

23,900

16,500

25,600

16,200

26,800

16,500

104.0

20,500

15,700

20,800

15,400

21,900

15,800

22,900

15,700

23,500

16,300

25,100

16,000

26,300

16,300

110.0

20,100

15,500

20,200

15,100

21,300

15,600

22,200

15,500

22,800

16,000

24,400

15,800

25,600

16,100

68.0

26,200

18,900

27,100

18,900

28,900

19,500

30,300

19,400

31,100

20,000

33,300

19,700

34,900

20,000

73.0

26,100

18,900

27,000

18,800

28,500

19,300

29,700

19,100

30,500

19,700

32,600

19,500

34,200

19,700

77.0

25,700

18,700

26,500

18,600

28,000

19,000

29,200

18,900

30,000

19,500

32,000

19,200

33,600

19,500

82.0

25,200

18,400

25,900

18,300

27,400

18,800

28,600

18,600

29,300

19,200

31,300

19,000

32,900

19,200

86.0

24,900

18,300

25,500

18,100

26,900

18,500

28,100

18,400

28,800

19,000

30,800

18,700

32,300

19,000

91.0

24,400

18,000

24,900

17,800

26,300

18,200

27,500

18,100

28,200

18,700

30,100

18,500

31,600

18,700

95.0

24,000

17,800

24,500

17,600

25,800

18,000

27,000

17,900

27,700

18,500

29,500

18,200

31,000

18,500

100.0

23,600

17,600

23,900

17,300

25,200

17,700

26,300

17,700

27,000

18,200

28,800

18,000

30,300

18,300

104.0

23,200

17,400

23,500

17,100

24,700

17,500

25,800

17,400

26,500

18,000

28,300

17,800

29,700

18,000

110.0

22,600

17,100

22,800

16,800

24,000

17,200

25,100

17,100

25,700

17,700

27,500

17,400

28,800

17,700

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-17

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PDFY-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

29,200

20,900

30,200

20,800

32,200

21,500

33,800

21,400

34,700

22,100

37,100

21,800

38,900

22,000

73.0

29,000

20,800

30,000

20,800

31,700

21,300

33,100

21,100

34,000

21,800

36,300

21,500

38,100

21,700

77.0

28,600

20,600

29,500

20,500

31,200

21,000

32,500

20,900

33,400

21,500

35,700

21,200

37,400

21,500

82.0

28,100

20,400

28,900

20,200

30,500

20,700

31,800

20,500

32,700

21,200

34,900

20,900

36,600

21,200

86.0

27,700

20,100

28,400

19,900

30,000

20,400

31,300

20,300

32,100

20,900

34,300

20,600

36,000

20,900

91.0

27,200

19,900

27,800

19,600

29,300

20,100

30,600

20,000

31,400

20,600

33,500

20,300

35,200

20,600

95.0

26,800

19,700

27,300

19,400

28,800

19,900

30,000

19,700

30,800

20,400

32,900

20,100

34,500

20,400

100.0

26,200

19,400

26,600

19,100

28,100

19,500

29,300

19,400

30,100

20,100

32,100

19,800

33,700

20,100

104.0

25,800

19,200

26,200

18,800

27,600

19,300

28,800

19,200

29,500

19,800

31,500

19,500

33,100

19,800

110.0

25,200

18,900

25,400

18,500

26,800

18,900

28,000

18,800

28,700

19,500

30,600

19,200

32,100

19,500

68.0

35,100

25,800

36,300

25,800

38,800

26,600

40,700

26,500

41,800

27,400

44,700

27,000

46,800

27,400

73.0

35,000

25,800

36,200

25,700

38,200

26,300

39,900

26,100

40,900

27,000

43,700

26,600

45,900

27,000

77.0

34,500

25,500

35,600

25,400

37,600

26,000

39,200

25,900

40,200

26,700

43,000

26,300

45,100

26,700

82.0

33,900

25,200

34,800

25,000

36,800

25,700

38,300

25,500

39,300

26,300

42,100

26,000

44,100

26,400

86.0

33,300

24,900

34,200

24,700

36,100

25,400

37,700

25,200

38,700

26,000

41,300

25,700

43,400

26,100

91.0

32,700

24,600

33,500

24,300

35,300

25,000

36,900

24,800

37,800

25,700

40,400

25,300

42,400

25,700

95.0

32,200

24,400

32,800

24,100

34,700

24,700

36,000

24,600

37,100

25,400

39,600

25,000

41,600

25,400

100.0

31,600

24,100

32,100

23,700

33,900

24,300

35,300

24,200

36,200

25,000

38,700

24,700

40,600

25,100

104.0

31,100

23,800

31,500

23,400

33,200

24,000

34,600

23,900

35,600

24,700

38,000

24,400

39,900

24,800

110.0

30,400

23,500

30,600

23,000

32,300

23,600

33,700

23,500

34,500

24,300

36,900

24,000

38,700

24,400

68.0

46,700

33,200

48,300

33,100

51,700

34,200

54,100

34,000

55,600

35,000

59,400

34,600

62,300

35,000

73.0

46,500

33,100

48,100

33,000

50,900

33,800

53,000

33,500

54,400

34,500

58,200

34,100

61,000

34,500

77.0

45,800

32,800

47,300

32,600

50,000

33,300

52,200

33,100

53,500

34,100

57,200

33,600

60,000

34,100

82.0

45,000

32,300

46,300

32,000

48,900

32,800

51,000

32,600

52,300

33,600

56,000

33,100

58,700

33,600

86.0

44,400

32,000

45,500

31,700

48,100

32,400

50,100

32,200

51,400

33,200

54,900

32,700

57,700

33,200

91.0

43,500

31,500

44,500

31,200

47,000

31,900

49,000

31,700

50,300

32,700

53,700

32,200

56,300

32,700

95.0

42,900

31,200

43,700

30,700

46,100

31,500

48,000

31,300

49,400

32,300

52,700

31,800

55,300

32,300

100.0

42,000

30,800

42,700

30,200

45,000

31,000

47,000

30,800

48,200

31,800

51,500

31,300

54,000

31,800

104.0

41,400

30,400

41,900

29,900

44,200

30,600

46,100

30,400

47,300

31,400

50,500

30,900

53,000

31,400

110.0

40,400

29,900

40,700

29,300

42,900

30,000

44,800

29,800

45,900

30,800

49,100

30,400

51,500

30,800

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-18

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PMFY-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

6,000

5,300

6,200

5,300

6,600

5,500

6,900

5,500

7,100

5,700

7,600

5,600

8,000

5,700

73.0

5,900

5,300

6,100

5,300

6,500

5,400

6,800

5,400

6,900

5,600

7,400

5,600

7,800

5,700

77.0

5,900

5,200

6,000

5,200

6,400

5,400

6,700

5,400

6,800

5,600

7,300

5,500

7,700

5,700

82.0

5,700

5,200

5,900

5,200

6,200

5,300

6,500

5,300

6,700

5,500

7,100

5,500

7,500

5,600

86.0

5,700

5,200

5,800

5,100

6,100

5,300

6,400

5,300

6,600

5,500

7,000

5,400

7,400

5,600

91.0

5,600

5,100

5,700

5,100

6,000

5,200

6,300

5,200

6,400

5,400

6,900

5,400

7,200

5,500

95.0

5,500

5,100

5,600

5,000

5,900

5,200

6,000

5,200

6,300

5,400

6,700

5,300

7,100

5,500

100.0

5,400

5,000

5,400

5,000

5,700

5,100

6,000

5,100

6,200

5,300

6,600

5,300

6,900

5,400

104.0

5,300

5,000

5,300

4,900

5,600

5,100

5,900

5,100

6,000

5,300

6,400

5,200

6,800

5,400

110.0

5,200

4,900

5,200

4,900

5,500

5,000

5,700

5,000

5,900

5,200

6,300

5,200

6,600

5,300

68.0

7,600

6,400

7,900

6,400

8,400

6,600

8,800

6,600

9,100

6,800

9,700

6,700

10,200

6,900

73.0

7,600

6,400

7,800

6,300

8,300

6,500

8,600

6,500

8,900

6,800

9,500

6,700

10,000

6,800

77.0

7,500

6,300

7,700

6,300

8,200

6,500

8,500

6,500

8,700

6,700

9,300

6,600

9,800

6,800

82.0

7,300

6,300

7,500

6,200

8,000

6,400

8,300

6,400

8,500

6,600

9,100

6,500

9,600

6,700

86.0

7,200

6,200

7,400

6,200

7,800

6,400

8,200

6,300

8,400

6,600

9,000

6,500

9,400

6,600

91.0

7,100

6,200

7,300

6,100

7,700

6,300

8,000

6,300

8,200

6,500

8,800

6,400

9,200

6,600

95.0

7,000

6,100

7,100

6,000

7,500

6,200

8,000

6,200

8,100

6,400

8,600

6,400

9,000

6,500

100.0

6,900

6,000

7,000

6,000

7,300

6,200

7,700

6,100

7,900

6,400

8,400

6,300

8,800

6,400

104.0

6,700

6,000

6,800

5,900

7,200

6,100

7,500

6,100

7,700

6,300

8,200

6,200

8,600

6,400

110.0

6,600

5,900

6,600

5,800

7,000

6,000

7,300

6,000

7,500

6,200

8,000

6,200

8,400

6,300

68.0

11,600

8,400

12,000

8,400

12,800

8,600

13,400

8,600

13,800

8,900

14,700

8,700

15,500

8,900

73.0

11,500

8,400

11,900

8,300

12,600

8,500

13,200

8,500

13,500

8,700

14,400

8,600

15,100

8,700

77.0

11,400

8,300

11,700

8,200

12,400

8,400

12,900

8,400

13,300

8,600

14,200

8,500

14,900

8,600

82.0

11,200

8,200

11,500

8,100

12,100

8,300

12,700

8,200

13,000

8,500

13,900

8,400

14,600

8,500

86.0

11,000

8,100

11,300

8,000

11,900

8,200

12,400

8,200

12,800

8,400

13,600

8,300

14,300

8,400

91.0

10,800

8,000

11,000

7,900

11,700

8,100

12,200

8,000

12,500

8,300

13,300

8,200

14,000

8,300

95.0

10,600

7,900

10,800

7,800

11,500

8,000

12,000

7,900

12,300

8,200

13,100

8,100

13,700

8,200

100.0

10,400

7,800

10,600

7,700

11,200

7,900

11,700

7,800

12,000

8,100

12,800

8,000

13,400

8,100

104.0

10,300

7,700

10,400

7,600

11,000

7,800

11,400

7,700

11,700

8,000

12,500

7,900

13,200

8,000

110.0

10,000

7,600

10,100

7,400

10,700

7,600

11,100

7,600

11,400

7,800

12,200

7,700

12,800

7,800

68.0

14,600

10,300

15,100

10,200

16,100

10,600

16,900

10,500

17,300

10,800

18,500

10,700

19,400

10,800

73.0

14,500

10,200

15,000

10,200

15,900

10,400

16,500

10,400

17,000

10,700

18,200

10,500

19,000

10,600

77.0

14,300

10,100

14,800

10,100

15,600

10,300

16,300

10,200

16,700

10,500

17,800

10,400

18,700

10,500

82.0

14,100

10,000

14,400

9,900

15,300

10,100

15,900

10,100

16,300

10,400

17,500

10,200

18,300

10,300

86.0

13,800

9,900

14,200

9,800

15,000

10,000

15,600

9,900

16,000

10,200

17,100

10,100

18,000

10,200

91.0

13,600

9,700

13,900

9,600

14,700

9,800

15,300

9,800

15,700

10,100

16,800

9,900

17,600

10,100

95.0

13,400

9,600

13,600

9,500

14,400

9,700

15,000

9,600

15,400

9,900

16,500

9,800

17,300

9,900

100.0

13,100

9,500

13,300

9,300

14,100

9,600

14,700

9,500

15,000

9,800

16,100

9,600

16,900

9,800

104.0

12,900

9,400

13,100

9,200

13,800

9,400

14,400

9,400

14,800

9,700

15,800

9,500

16,500

9,700

110.0

12,600

9,200

12,700

9,000

13,400

9,200

14,000

9,200

14,300

9,500

15,300

9,300

16,100

9,500

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-19

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PLFY-NCMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

7,600

6,700

7,900

6,700

8,400

7,000

8,800

7,000

9,100

7,200

9,700

7,100

10,200

7,300
7,200

73.0

7,600

6,700

7,800

6,700

8,300

6,900

8,600

6,900

8,900

7,100

9,500

7,100

10,000

77.0

7,500

6,700

7,700

6,600

8,200

6,800

8,500

6,800

8,700

7,100

9,300

7,000

9,800

7,200

82.0

7,300

6,600

7,500

6,500

8,000

6,800

8,300

6,800

8,500

7,000

9,100

6,900

9,600

7,100

86.0

7,200

6,600

7,400

6,500

7,800

6,700

8,200

6,700

8,400

7,000

9,000

6,900

9,400

7,100

91.0

7,100

6,500

7,300

6,400

7,700

6,600

8,000

6,600

8,200

6,900

8,800

6,800

9,200

7,000

95.0

7,000

6,400

7,100

6,400

7,500

6,600

12,000

6,600

8,100

6,800

8,600

6,800

9,000

6,900

100.0

6,900

6,400

7,000

6,300

7,300

6,500

7,700

6,500

7,900

6,800

8,400

6,700

8,800

6,900

104.0

6,700

6,300

6,800

6,200

7,200

6,500

7,500

6,400

7,700

6,700

8,200

6,600

8,600

6,800

110.0

6,600

6,300

6,600

6,200

7,000

6,400

7,300

6,400

7,500

6,600

8,000

6,500

8,400

6,700

68.0

11,600

9,000

12,000

8,900

12,800

9,300

13,400

9,200

13,800

9,500

14,700

9,400

15,500

9,600

73.0

11,500

9,000

11,900

8,900

12,600

9,200

13,200

9,100

13,500

9,400

14,400

9,300

15,100

9,500

77.0

11,400

8,900

11,700

8,800

12,400

9,100

12,900

9,000

13,300

9,300

14,200

9,200

14,900

9,400

82.0

11,200

8,800

11,500

8,700

12,100

9,000

12,700

8,900

13,000

9,200

13,900

9,100

14,600

9,300

86.0

11,000

8,700

11,300

8,600

11,900

8,900

12,400

8,800

12,800

9,100

13,600

9,000

14,300

9,200

91.0

10,800

8,600

11,000

8,500

11,700

8,700

12,200

8,700

12,500

9,000

13,300

8,900

14,000

9,100

95.0

10,600

8,500

10,800

8,400

11,500

8,700

15,000

8,600

12,300

8,900

13,100

8,800

13,700

9,000

100.0

10,400

8,400

10,600

8,300

11,200

8,500

11,700

8,500

12,000

8,800

12,800

8,700

13,400

8,900

104.0

10,300

8,300

10,400

8,200

11,000

8,400

11,400

8,400

11,700

8,700

12,500

8,600

13,200

8,800

110.0

10,000

8,200

10,100

8,100

10,700

8,300

11,100

8,300

11,400

8,600

12,200

8,500

12,800

8,600

68.0

14,600

10,500

15,100

10,500

16,100

10,800

16,900

10,800

17,300

11,100

18,500

11,000

19,400

11,100

73.0

14,500

10,500

15,000

10,500

15,900

10,700

16,500

10,600

17,000

11,000

18,200

10,800

19,000

11,000

77.0

14,300

10,400

14,800

10,300

15,600

10,600

16,300

10,500

16,700

10,800

17,800

10,700

18,700

10,800

82.0

14,100

10,300

14,400

10,200

15,300

10,400

15,900

10,400

16,300

10,700

17,500

10,500

18,300

10,700

86.0

13,800

10,100

14,200

10,000

15,000

10,300

15,600

10,200

16,000

10,600

17,100

10,400

18,000

10,600

91.0

13,600

10,000

13,900

9,900

14,700

10,100

15,300

10,100

15,700

10,400

16,800

10,300

17,600

10,400

95.0

13,400

9,900

13,600

9,800

14,400

10,000

18,000

10,000

15,400

10,300

16,500

10,100

17,300

10,300

100.0

13,100

9,800

13,300

9,600

14,100

9,900

14,700

9,800

15,000

10,100

16,100

10,000

16,900

10,100

104.0

12,900

9,700

13,100

9,500

13,800

9,700

14,400

9,700

14,800

10,000

15,800

9,900

16,500

10,000

110.0

12,600

9,500

12,700

9,300

13,400

9,600

14,000

9,500

14,300

9,800

15,300

9,700

16,100

9,800

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-20

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PLFY-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

11,600

9,800

12,000

9,800

12,800

10,100

13,400

10,100

13,800

10,500

14,700

10,400

15,500

10,600

73.0

11,500

9,800

11,900

9,700

12,600

10,000

13,200

10,000

13,500

10,400

14,400

10,200

15,100

10,500

77.0

11,400

9,700

11,700

9,600

12,400

10,000

12,900

9,900

13,300

10,300

14,200

10,200

14,900

10,400

82.0

11,200

9,600

11,500

9,500

12,100

9,800

12,700

9,800

13,000

10,200

13,900

10,000

14,600

10,300

86.0

11,000

9,500

11,300

9,400

11,900

9,800

12,400

9,700

12,800

10,100

13,600

10,000

14,300

10,200

91.0

10,800

9,400

11,000

9,300

11,700

9,600

12,200

9,600

12,500

10,000

13,300

9,900

14,000

10,100
10,000

95.0

10,600

9,400

10,800

9,200

11,500

9,600

12,000

9,500

12,300

9,900

13,100

9,800

13,700

100.0

10,400

9,300

10,600

9,100

11,200

9,400

11,700

9,400

12,000

9,800

12,800

9,700

13,400

9,900

104.0

10,300

9,200

10,400

9,100

11,000

9,400

11,400

9,300

11,700

9,700

12,500

9,600

13,200

9,800

110.0

10,000

9,100

10,100

8,900

10,700

9,200

11,100

9,200

11,400

9,600

12,200

9,400

12,800

9,700

68.0

14,600

12,000

15,100

11,900

16,100

12,300

16,900

12,300

17,300

12,800

18,500

12,600

19,400

12,900

73.0

14,500

11,900

15,000

11,900

15,900

12,200

16,500

12,200

17,000

12,600

18,200

12,500

19,000

12,700

77.0

14,300

11,800

14,800

11,800

15,600

12,100

16,300

12,100

16,700

12,500

17,800

12,300

18,700

12,600

82.0

14,100

11,700

14,400

11,600

15,300

12,000

15,900

11,900

16,300

12,400

17,500

12,200

18,300

12,500

86.0

13,800

11,600

14,200

11,500

15,000

11,900

15,600

11,800

16,000

12,300

17,100

12,100

18,000

12,400

91.0

13,600

11,500

13,900

11,400

14,700

11,700

15,300

11,700

15,700

12,100

16,800

12,000

17,600

12,200

95.0

13,400

11,400

13,600

11,300

14,400

11,600

15,000

11,600

15,400

12,000

16,500

11,800

17,300

12,100

100.0

13,100

11,300

13,300

11,100

14,100

11,500

14,700

11,400

15,000

11,900

16,100

11,700

16,900

12,000

104.0

12,900

11,200

13,100

11,000

13,800

11,400

14,400

11,300

14,800

11,800

15,800

11,600

16,500

11,900

110.0

12,600

11,000

12,700

10,800

13,400

11,200

14,000

11,200

14,300

11,600

15,300

11,400

16,100

11,700

68.0

17,600

14,300

18,200

14,200

19,400

14,800

20,300

14,700

20,900

15,300

22,300

15,100

23,400

15,400

73.0

17,500

14,300

18,100

14,200

19,100

14,600

19,900

14,600

20,500

15,100

21,900

14,900

22,900

15,200

77.0

17,200

14,100

17,800

14,100

18,800

14,500

19,600

14,400

20,100

15,000

21,500

14,800

22,600

15,100

82.0

16,900

14,000

17,400

13,900

18,400

14,300

19,200

14,300

19,700

14,800

21,000

14,600

22,100

14,900

86.0

16,700

13,900

17,100

13,800

18,100

14,200

18,800

14,100

19,300

14,600

20,700

14,400

21,700

14,800

91.0

16,400

13,700

16,700

13,600

17,600

14,000

18,400

14,000

18,900

14,500

20,200

14,300

21,200

14,600

95.0

16,100

13,600

16,400

13,400

17,300

13,900

18,000

13,800

18,600

14,300

19,800

14,200

20,800

14,500

100.0

15,800

13,500

16,000

13,300

16,900

13,700

17,700

13,700

18,100

14,200

19,300

14,000

20,300

14,300

104.0

15,600

13,400

15,800

13,200

16,600

13,600

17,300

13,500

17,800

14,000

19,000

13,900

19,900

14,200

110.0

15,200

13,200

15,300

13,000

16,100

13,400

16,800

13,300

17,300

13,800

18,400

13,700

19,300

14,000

68.0

23,200

17,600

24,000

17,500

25,700

18,100

26,900

18,100

27,600

18,700

29,500

18,400

30,900

18,700

73.0

23,100

17,500

23,900

17,500

25,200

17,900

26,300

17,800

27,000

18,400

28,900

18,200

30,300

18,500

77.0

22,800

17,400

23,500

17,300

24,800

17,700

25,900

17,600

26,600

18,200

28,400

18,000

29,800

18,300

82.0

22,400

17,200

23,000

17,000

24,300

17,500

25,300

17,400

26,000

18,000

27,800

17,800

29,100

18,100

86.0

22,000

17,000

22,600

16,800

23,900

17,300

24,900

17,200

25,500

17,800

27,300

17,600

28,600

17,900

91.0

21,600

16,800

22,100

16,600

23,300

17,100

24,300

17,000

25,000

17,600

26,700

17,300

28,000

17,600

95.0

21,300

16,600

21,700

16,400

22,900

16,900

24,000

16,800

24,500

17,400

26,200

17,100

27,500

17,500

100.0

20,900

16,500

21,200

16,200

22,400

16,700

23,300

16,600

23,900

17,200

25,600

16,900

26,800

17,200

104.0

20,500

16,300

20,800

16,000

21,900

16,500

22,900

16,400

23,500

17,000

25,100

16,700

26,300

17,100

110.0

20,100

16,100

20,200

15,700

21,300

16,200

22,200

16,100

22,800

16,700

24,400

16,500

25,600

16,800

68.0

29,200

21,100

30,200

21,000

32,200

21,700

33,800

21,600

34,700

22,300

37,100

22,000

38,900

22,300

73.0

29,000

21,000

30,000

21,000

31,700

21,500

33,100

21,300

34,000

22,000

36,300

21,700

38,100

22,000

77.0

28,600

20,800

29,500

20,700

31,200

21,200

32,500

21,100

33,400

21,700

35,700

21,400

37,400

21,700

82.0

28,100

20,600

28,900

20,400

30,500

20,900

31,800

20,800

32,700

21,400

34,900

21,100

36,600

21,400

86.0

27,700

20,400

28,400

20,200

30,000

20,700

31,300

20,500

32,100

21,200

34,300

20,900

36,000

21,200

91.0

27,200

20,100

27,800

19,800

29,300

20,300

30,600

20,200

31,400

20,900

33,500

20,600

35,200

20,900

95.0

26,800

19,900

27,300

19,600

28,800

20,100

30,000

20,000

30,800

20,600

32,900

20,300

34,500

20,700

100.0

26,200

19,600

26,600

19,300

28,100

19,800

29,300

19,700

30,100

20,300

32,100

20,000

33,700

20,400

104.0

25,800

19,400

26,200

19,100

27,600

19,500

28,800

19,400

29,500

20,100

31,500

19,800

33,100

20,100

110.0

25,200

19,100

25,400

18,700

26,800

19,200

28,000

19,100

28,700

19,700

30,600

19,500

32,100

19,800

68.0

35,100

26,900

36,300

26,800

38,800

27,700

40,700

27,600

41,800

28,600

44,700

28,200

46,800

28,600

73.0

35,000

26,800

36,200

26,700

38,200

27,500

39,900

27,300

40,900

28,200

43,700

27,800

45,900

28,300

77.0

34,500

26,600

35,600

26,400

37,600

27,200

39,200

27,000

40,200

27,900

43,000

27,500

45,100

28,000

82.0

33,900

26,300

34,800

26,100

36,800

26,800

38,300

26,600

39,300

27,600

42,100

27,200

44,100

27,700

86.0

33,300

26,000

34,200

25,800

36,100

26,500

37,700

26,400

38,700

27,300

41,300

26,900

43,400

27,400

91.0

32,700

25,700

33,500

25,400

35,300

26,200

36,900

26,000

37,800

26,900

40,400

26,600

42,400

27,100

95.0

32,200

25,500

32,800

25,100

34,700

25,900

36,000

25,700

37,100

26,600

39,600

26,300

41,600

26,800

100.0

31,600

25,200

32,100

24,800

33,900

25,500

35,300

25,400

36,200

26,300

38,700

25,900

40,600

26,500

104.0

31,100

24,900

31,500

24,500

33,200

25,200

34,600

25,100

35,600

26,000

38,000

25,700

39,900

26,200

110.0

30,400

24,600

30,600

24,100

32,300

24,800

33,700

24,700

34,500

25,600

36,900

25,300

38,700

25,800

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-21

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PCFY-P-NGMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,600

11,000

15,100

10,900

16,100

11,300

16,900

11,300

17,300

11,600

18,500

11,500

19,400

11,600

73.0

14,500

10,900

15,000

10,900

15,900

11,200

16,500

11,100

17,000

11,500

18,200

11,300

19,000

11,500

77.0

14,300

10,800

14,800

10,800

15,600

11,100

16,300

11,000

16,700

11,400

17,800

11,200

18,700

11,400

82.0

14,100

10,700

14,400

10,600

15,300

10,900

15,900

10,800

16,300

11,200

17,500

11,100

18,300

11,200

86.0

13,800

10,600

14,200

10,500

15,000

10,800

15,600

10,700

16,000

11,100

17,100

10,900

18,000

11,100

91.0

13,600

10,500

13,900

10,400

14,700

10,600

15,300

10,600

15,700

10,900

16,800

10,800

17,600

11,000

95.0

13,400

10,400

13,600

10,200

14,400

10,500

15,000

10,500

15,400

10,800

16,500

10,700

17,300

10,900

100.0

13,100

10,200

13,300

10,100

14,100

10,400

14,700

10,300

15,000

10,700

16,100

10,500

16,900

10,700

104.0

12,900

10,100

13,100

10,000

13,800

10,200

14,400

10,200

14,800

10,600

15,800

10,400

16,500

10,600

110.0

12,600

10,000

12,700

9,800

13,400

10,100

14,000

10,000

14,300

10,400

15,300

10,200

16,100

10,400

68.0

23,200

17,000

24,000

17,000

25,700

17,500

26,900

17,500

27,600

18,000

29,500

17,800

30,900

18,000

73.0

23,100

17,000

23,900

16,900

25,200

17,300

26,300

17,200

27,000

17,800

28,900

17,500

30,300

17,800

77.0

22,800

16,800

23,500

16,700

24,800

17,100

25,900

17,000

26,600

17,600

28,400

17,300

29,800

17,600

82.0

22,400

16,600

23,000

16,500

24,300

16,900

25,300

16,800

26,000

17,300

27,800

17,100

29,100

17,400

86.0

22,000

16,400

22,600

16,300

23,900

16,700

24,900

16,600

25,500

17,100

27,300

16,900

28,600

17,200

91.0

21,600

16,200

22,100

16,000

23,300

16,500

24,300

16,400

25,000

16,900

26,700

16,700

28,000

16,900

95.0

21,300

16,100

21,700

15,800

22,900

16,300

24,000

16,200

24,500

16,700

26,200

16,500

27,500

16,700

100.0

20,900

15,900

21,200

15,600

22,400

16,000

23,300

15,900

23,900

16,500

25,600

16,200

26,800

16,500

104.0

20,500

15,700

20,800

15,400

21,900

15,800

22,900

15,700

23,500

16,300

25,100

16,000

26,300

16,300

110.0

20,100

15,500

20,200

15,100

21,300

15,600

22,200

15,500

22,800

16,000

24,400

15,800

25,600

16,100

68.0

29,200

20,900

30,200

20,800

32,200

21,500

33,800

21,400

34,700

22,100

37,100

21,800

38,900

22,000

73.0

29,000

20,800

30,000

20,800

31,700

21,300

33,100

21,100

34,000

21,800

36,300

21,500

38,100

21,700

77.0

28,600

20,600

29,500

20,500

31,200

21,000

32,500

20,900

33,400

21,500

35,700

21,200

37,400

21,500

82.0

28,100

20,400

28,900

20,200

30,500

20,700

31,800

20,500

32,700

21,200

34,900

20,900

36,600

21,200

86.0

27,700

20,100

28,400

19,900

30,000

20,400

31,300

20,300

32,100

20,900

34,300

20,600

36,000

20,900

91.0

27,200

19,900

27,800

19,600

29,300

20,100

30,600

20,000

31,400

20,600

33,500

20,300

35,200

20,600

95.0

26,800

19,700

27,300

19,400

28,800

19,900

30,000

19,700

30,800

20,400

32,900

20,100

34,500

20,400

100.0

26,200

19,400

26,600

19,100

28,100

19,500

29,300

19,400

30,100

20,100

32,100

19,800

33,700

20,100

104.0

25,800

19,200

26,200

18,800

27,600

19,300

28,800

19,200

29,500

19,800

31,500

19,500

33,100

19,800

110.0

25,200

18,900

25,400

18,500

26,800

18,900

28,000

18,800

28,700

19,500

30,600

19,200

32,100

19,500

68.0

35,100

25,800

36,300

25,800

38,800

26,600

40,700

26,500

41,800

27,400

44,700

27,000

46,800

27,400

73.0

35,000

25,800

36,200

25,700

38,200

26,300

39,900

26,100

40,900

27,000

43,700

26,600

45,900

27,000

77.0

34,500

25,500

35,600

25,400

37,600

26,000

39,200

25,900

40,200

26,700

43,000

26,300

45,100

26,700

82.0

33,900

25,200

34,800

25,000

36,800

25,700

38,300

25,500

39,300

26,300

42,100

26,000

44,100

26,400

86.0

33,300

24,900

34,200

24,700

36,100

25,400

37,700

25,200

38,700

26,000

41,300

25,700

43,400

26,100

91.0

32,700

24,600

33,500

24,300

35,300

25,000

36,900

24,800

37,800

25,700

40,400

25,300

42,400

25,700

95.0

32,200

24,400

32,800

24,100

34,700

24,700

36,000

24,600

37,100

25,400

39,600

25,000

41,600

25,400

100.0

31,600

24,100

32,100

23,700

33,900

24,300

35,300

24,200

36,200

25,000

38,700

24,700

40,600

25,100

104.0

31,100

23,800

31,500

23,400

33,200

24,000

34,600

23,900

35,600

24,700

38,000

24,400

39,900

24,800

110.0

30,400

23,500

30,600

23,000

32,300

23,600

33,700

23,500

34,500

24,300

36,900

24,000

38,700

24,400

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-22

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

6,000

4,500

6,200

4,500

6,600

4,700

6,900

4,700

7,100

4,800

7,600

4,800

8,000

4,800

73.0

5,900

4,500

6,100

4,500

6,500

4,600

6,800

4,600

6,900

4,800

7,400

4,700

7,800

4,800

77.0

5,900

4,500

6,000

4,500

6,400

4,600

6,700

4,600

6,800

4,700

7,300

4,700

7,700

4,700

82.0

5,700

4,400

5,900

4,400

6,200

4,500

6,500

4,500

6,700

4,700

7,100

4,600

7,500

4,700

86.0

5,700

4,400

5,800

4,400

6,100

4,500

6,400

4,500

6,600

4,600

7,000

4,500

7,400

4,600

91.0

5,600

4,300

5,700

4,300

6,000

4,400

6,300

4,400

6,400

4,500

6,900

4,500

7,200

4,600

95.0

5,500

4,300

5,600

4,200

5,900

4,400

6,000

4,300

6,300

4,500

6,700

4,400

7,100

4,500

100.0

5,400

4,300

5,400

4,200

5,700

4,300

6,000

4,300

6,200

4,400

6,600

4,400

6,900

4,500

104.0

5,300

4,200

5,300

4,100

5,600

4,300

5,900

4,200

6,000

4,400

6,400

4,300

6,800

4,400

110.0

5,200

4,200

5,200

4,100

5,500

4,200

5,700

4,200

5,900

4,300

6,300

4,300

6,600

4,400

68.0

7,600

5,700

7,900

5,700

8,400

5,900

8,800

5,900

9,100

6,100

9,700

6,000

10,200

6,100

73.0

7,600

5,700

7,800

5,700

8,300

5,800

8,600

5,800

8,900

6,000

9,500

5,900

10,000

6,000

77.0

7,500

5,600

7,700

5,600

8,200

5,800

8,500

5,700

8,700

5,900

9,300

5,800

9,800

5,900

82.0

7,300

5,600

7,500

5,500

8,000

5,700

8,300

5,600

8,500

5,800

9,100

5,800

9,600

5,900

86.0

7,200

5,500

7,400

5,500

7,800

5,600

8,200

5,600

8,400

5,800

9,000

5,700

9,400

5,800

91.0

7,100

5,500

7,300

5,400

7,700

5,500

8,000

5,500

8,200

5,700

8,800

5,600

9,200

5,700

95.0

7,000

5,400

7,100

5,300

7,500

5,500

8,000

5,400

8,100

5,600

8,600

5,600

9,000

5,700

100.0

6,900

5,300

7,000

5,300

7,300

5,400

7,700

5,400

7,900

5,600

8,400

5,500

8,800

5,600

104.0

6,700

5,300

6,800

5,200

7,200

5,300

7,500

5,300

7,700

5,500

8,200

5,400

8,600

5,500

110.0

6,600

5,200

6,600

5,100

7,000

5,200

7,300

5,200

7,500

5,400

8,000

5,300

8,400

5,400

68.0

11,600

9,200

12,000

9,100

12,800

9,500

13,400

9,400

13,800

9,800

14,700

9,600

15,500

9,800

73.0

11,500

9,100

11,900

9,100

12,600

9,400

13,200

9,300

13,500

9,600

14,400

9,500

15,100

9,700

77.0

11,400

9,100

11,700

9,000

12,400

9,300

12,900

9,200

13,300

9,600

14,200

9,400

14,900

9,600

82.0

11,200

9,000

11,500

8,900

12,100

9,200

12,700

9,100

13,000

9,400

13,900

9,300

14,600

9,500

86.0

11,000

8,900

11,300

8,800

11,900

9,100

12,400

9,000

12,800

9,400

13,600

9,200

14,300

9,400

91.0

10,800

8,800

11,000

8,700

11,700

9,000

12,200

8,900

12,500

9,200

13,300

9,100

14,000

9,300

95.0

10,600

8,700

10,800

8,600

11,500

8,900

12,000

8,800

12,300

9,100

13,100

9,000

13,700

9,200

100.0

10,400

8,600

10,600

8,500

11,200

8,800

11,700

8,700

12,000

9,000

12,800

8,900

13,400

9,100

104.0

10,300

8,500

10,400

8,400

11,000

8,700

11,400

8,600

11,700

8,900

12,500

8,800

13,200

9,000

110.0

10,000

8,400

10,100

8,300

10,700

8,500

11,100

8,500

11,400

8,800

12,200

8,700

12,800

8,900

68.0

14,600

11,000

15,100

11,000

16,100

11,400

16,900

11,300

17,300

11,700

18,500

11,600

19,400

11,700

73.0

14,500

11,000

15,000

11,000

15,900

11,300

16,500

11,200

17,000

11,600

18,200

11,400

19,000

11,600

77.0

14,300

10,900

14,800

10,800

15,600

11,100

16,300

11,100

16,700

11,400

17,800

11,300

18,700

11,500

82.0

14,100

10,800

14,400

10,700

15,300

11,000

15,900

10,900

16,300

11,300

17,500

11,100

18,300

11,300

86.0

13,800

10,700

14,200

10,600

15,000

10,900

15,600

10,800

16,000

11,200

17,100

11,000

18,000

11,200

91.0

13,600

10,600

13,900

10,400

14,700

10,700

15,300

10,700

15,700

11,000

16,800

10,900

17,600

11,100

95.0

13,400

10,500

13,600

10,300

14,400

10,600

15,000

10,500

15,400

10,900

16,500

10,800

17,300

11,000

100.0

13,100

10,300

13,300

10,200

14,100

10,500

14,700

10,400

15,000

10,800

16,100

10,600

16,900

10,800

104.0

12,900

10,200

13,100

10,100

13,800

10,300

14,400

10,300

14,800

10,700

15,800

10,500

16,500

10,700

110.0

12,600

10,100

12,700

9,900

13,400

10,200

14,000

10,100

14,300

10,500

15,300

10,300

16,100

10,500

68.0

17,600

14,000

18,200

13,900

19,400

14,400

20,300

14,400

20,900

14,900

22,300

14,700

23,400

15,000

73.0

17,500

14,000

18,100

13,900

19,100

14,300

19,900

14,200

20,500

14,700

21,900

14,500

22,900

14,800

77.0

17,200

13,800

17,800

13,800

18,800

14,200

19,600

14,100

20,100

14,600

21,500

14,400

22,600

14,700

82.0

16,900

13,700

17,400

13,600

18,400

14,000

19,200

13,900

19,700

14,400

21,000

14,200

22,100

14,500

86.0

16,700

13,600

17,100

13,500

18,100

13,900

18,800

13,800

19,300

14,300

20,700

14,100

21,700

14,400

91.0

16,400

13,400

16,700

13,300

17,600

13,700

18,400

13,600

18,900

14,100

20,200

13,900

21,200

14,200

95.0

16,100

13,300

16,400

13,100

17,300

13,600

18,000

13,500

18,600

14,000

19,800

13,800

20,800

14,100

100.0

15,800

13,200

16,000

13,000

16,900

13,400

17,700

13,300

18,100

13,800

19,300

13,600

20,300

13,900

104.0

15,600

13,000

15,800

12,800

16,600

13,200

17,300

13,200

17,800

13,700

19,000

13,500

19,900

13,800

110.0

15,200

12,900

15,300

12,600

16,100

13,000

16,800

13,000

17,300

13,500

18,400

13,300

19,300

13,600

68.0

23,200

17,400

24,000

17,300

25,700

17,900

26,900

17,900

27,600

18,500

29,500

18,200

30,900

18,500

73.0

23,100

17,400

23,900

17,300

25,200

17,700

26,300

17,600

27,000

18,200

28,900

18,000

30,300

18,200

77.0

22,800

17,200

23,500

17,100

24,800

17,500

25,900

17,400

26,600

18,000

28,400

17,800

29,800

18,100

82.0

22,400

17,000

23,000

16,800

24,300

17,300

25,300

17,200

26,000

17,800

27,800

17,500

29,100

17,800

86.0

22,000

16,800

22,600

16,700

23,900

17,100

24,900

17,000

25,500

17,600

27,300

17,300

28,600

17,600

91.0

21,600

16,600

22,100

16,400

23,300

16,900

24,300

16,800

25,000

17,300

26,700

17,100

28,000

17,400

95.0

21,300

16,500

21,700

16,200

22,900

16,700

24,000

16,600

24,500

17,200

26,200

16,900

27,500

17,200

100.0

20,900

16,300

21,200

16,000

22,400

16,400

23,300

16,400

23,900

16,900

25,600

16,700

26,800

17,000

104.0

20,500

16,100

20,800

15,800

21,900

16,300

22,900

16,200

23,500

16,700

25,100

16,500

26,300

16,800

110.0

20,100

15,900

20,200

15,500

21,300

16,000

22,200

15,900

22,800

16,500

24,400

16,200

25,600

16,600

68.0

29,200

23,300

30,200

23,300

32,200

24,100

33,800

24,000

34,700

24,900

37,100

24,600

38,900

25,000

73.0

29,000

23,300

30,000

23,200

31,700

23,900

33,100

23,800

34,000

24,600

36,300

24,300

38,100

24,700

77.0

28,600

23,100

29,500

22,900

31,200

23,600

32,500

23,500

33,400

24,400

35,700

24,000

37,400

24,500

82.0

28,100

22,800

28,900

22,700

30,500

23,400

31,800

23,200

32,700

24,100

34,900

23,800

36,600

24,300

86.0

27,700

22,600

28,400

22,400

30,000

23,100

31,300

23,000

32,100

23,900

34,300

23,500

36,000

24,000

91.0

27,200

22,400

27,800

22,200

29,300

22,800

30,600

22,700

31,400

23,600

33,500

23,300

35,200

23,800

95.0

26,800

22,200

27,300

21,900

28,800

22,600

30,000

22,500

30,800

23,300

32,900

23,000

34,500

23,500

100.0

26,200

22,000

26,600

21,600

28,100

22,300

29,300

22,200

30,100

23,100

32,100

22,800

33,700

23,300

104.0

25,800

21,800

26,200

21,400

27,600

22,100

28,800

22,000

29,500

22,800

31,500

22,500

33,100

23,100

110.0

25,200

21,500

25,400

21,100

26,800

21,800

28,000

21,700

28,700

22,500

30,600

22,200

32,100

22,700

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-23

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PFFY-NEMU/NRMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Indoor air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

6,000

4,500

6,200

4,400

6,600

4,600

6,900

4,600

7,100

4,700

7,600

4,700

8,000

4,700

73.0

5,900

4,500

6,100

4,400

6,500

4,600

6,800

4,500

6,900

4,700

7,400

4,600

7,800

4,700

77.0

5,900

4,400

6,000

4,400

6,400

4,500

6,700

4,500

6,800

4,600

7,300

4,600

7,700

4,600

82.0

5,700

4,400

5,900

4,300

6,200

4,400

6,500

4,400

6,700

4,600

7,100

4,500

7,500

4,600

86.0

5,700

4,300

5,800

4,300

6,100

4,400

6,400

4,400

6,600

4,500

7,000

4,400

7,400

4,500

91.0

5,600

4,300

5,700

4,200

6,000

4,300

6,300

4,300

6,400

4,400

6,900

4,400

7,200

4,500

95.0

5,500

4,200

5,600

4,200

5,900

4,300

6,000

4,300

6,300

4,400

6,700

4,300

7,100

4,400

100.0

5,400

4,200

5,400

4,100

5,700

4,200

6,000

4,200

6,200

4,300

6,600

4,300

6,900

4,400

104.0

5,300

4,100

5,300

4,100

5,600

4,200

5,900

4,100

6,000

4,300

6,400

4,200

6,800

4,300

110.0

5,200

4,100

5,200

4,000

5,500

4,100

5,700

4,100

5,900

4,200

6,300

4,200

6,600

4,200

68.0

7,600

5,800

7,900

5,800

8,400

6,000

8,800

6,000

9,100

6,200

9,700

6,100

10,200

6,200

73.0

7,600

5,800

7,800

5,800

8,300

5,900

8,600

5,900

8,900

6,100

9,500

6,000

10,000

6,100

77.0

7,500

5,700

7,700

5,700

8,200

5,900

8,500

5,800

8,700

6,000

9,300

5,900

9,800

6,000

82.0

7,300

5,700

7,500

5,600

8,000

5,800

8,300

5,800

8,500

5,900

9,100

5,900

9,600

6,000

86.0

7,200

5,600

7,400

5,600

7,800

5,700

8,200

5,700

8,400

5,900

9,000

5,800

9,400

5,900

91.0

7,100

5,600

7,300

5,500

7,700

5,600

8,000

5,600

8,200

5,800

8,800

5,700

9,200

5,800

95.0

7,000

5,500

7,100

5,400

7,500

5,600

8,000

5,600

8,100

5,700

8,600

5,700

9,000

5,800

100.0

6,900

5,400

7,000

5,400

7,300

5,500

7,700

5,500

7,900

5,700

8,400

5,600

8,800

5,700

104.0

6,700

5,400

6,800

5,300

7,200

5,400

7,500

5,400

7,700

5,600

8,200

5,500

8,600

5,600

110.0

6,600

5,300

6,600

5,200

7,000

5,400

7,300

5,300

7,500

5,500

8,000

5,400

8,400

5,600

68.0

11,600

8,100

12,000

8,000

12,800

8,300

13,400

8,200

13,800

8,500

14,700

8,400

15,500

8,400

73.0

11,500

8,000

11,900

8,000

12,600

8,200

13,200

8,100

13,500

8,300

14,400

8,200

15,100

8,300

77.0

11,400

7,900

11,700

7,900

12,400

8,100

12,900

8,000

13,300

8,200

14,200

8,100

14,900

8,200

82.0

11,200

7,800

11,500

7,800

12,100

7,900

12,700

7,900

13,000

8,100

13,900

8,000

14,600

8,100

86.0

11,000

7,700

11,300

7,700

11,900

7,800

12,400

7,800

12,800

8,000

13,600

7,900

14,300

8,000

91.0

10,800

7,600

11,000

7,500

11,700

7,700

12,200

7,600

12,500

7,900

13,300

7,800

14,000

7,800

95.0

10,600

7,500

10,800

7,400

11,500

7,600

12,000

7,500

12,300

7,800

13,100

7,700

13,700

7,700

100.0

10,400

7,400

10,600

7,300

11,200

7,500

11,700

7,400

12,000

7,600

12,800

7,500

13,400

7,600

104.0

10,300

7,300

10,400

7,200

11,000

7,400

11,400

7,300

11,700

7,500

12,500

7,400

13,200

7,500

110.0

10,000

7,200

10,100

7,000

10,700

7,200

11,100

7,200

11,400

7,400

12,200

7,300

12,800

7,400

68.0

14,600

10,200

15,100

10,200

16,100

10,500

16,900

10,500

17,300

10,800

18,500

10,700

19,400

10,800

73.0

14,500

10,200

15,000

10,200

15,900

10,400

16,500

10,300

17,000

10,600

18,200

10,500

19,000

10,600

77.0

14,300

10,100

14,800

10,000

15,600

10,300

16,300

10,200

16,700

10,500

17,800

10,400

18,700

10,500

82.0

14,100

10,000

14,400

9,900

15,300

10,100

15,900

10,000

16,300

10,300

17,500

10,200

18,300

10,300

86.0

13,800

9,900

14,200

9,800

15,000

10,000

15,600

9,900

16,000

10,200

17,100

10,100

18,000

10,200

91.0

13,600

9,700

13,900

9,600

14,700

9,800

15,300

9,800

15,700

10,000

16,800

9,900

17,600

10,000

95.0

13,400

9,600

13,600

9,500

14,400

9,700

15,000

9,600

15,400

9,900

16,500

9,800

17,300

9,900

100.0

13,100

9,500

13,300

9,300

14,100

9,500

14,700

9,500

15,000

9,800

16,100

9,600

16,900

9,800

104.0

12,900

9,400

13,100

9,200

13,800

9,400

14,400

9,300

14,800

9,600

15,800

9,500

16,500

9,600

110.0

12,600

9,200

12,700

9,000

13,400

9,200

14,000

9,200

14,300

9,500

15,300

9,300

16,100

9,500

68.0

17,600

12,600

18,200

12,500

19,400

12,900

20,300

12,900

20,900

13,300

22,300

13,100

23,400

13,200

73.0

17,500

12,500

18,100

12,500

19,100

12,800

19,900

12,700

20,500

13,100

21,900

12,900

22,900

13,100

77.0

17,200

12,400

17,800

12,300

18,800

12,600

19,600

12,500

20,100

12,900

21,500

12,700

22,600

12,900

82.0

16,900

12,200

17,400

12,100

18,400

12,400

19,200

12,300

19,700

12,700

21,000

12,600

22,100

12,700

86.0

16,700

12,100

17,100

12,000

18,100

12,300

18,800

12,200

19,300

12,600

20,700

12,400

21,700

12,600

91.0

16,400

11,900

16,700

11,800

17,600

12,100

18,400

12,000

18,900

12,400

20,200

12,200

21,200

12,400

95.0

16,100

11,800

16,400

11,600

17,300

11,900

18,000

11,900

18,600

12,200

19,800

12,100

20,800

12,200

100.0

15,800

11,700

16,000

11,500

16,900

11,700

17,700

11,700

18,100

12,100

19,300

11,900

20,300

12,100

104.0

15,600

11,500

15,800

11,300

16,600

11,600

17,300

11,500

17,800

11,900

19,000

11,700

19,900

11,900

110.0

15,200

11,300

15,300

11,100

16,100

11,400

16,800

11,300

17,300

11,700

18,400

11,500

19,300

11,700

68.0

23,200

16,200

24,000

16,100

25,700

16,600

26,900

16,500

27,600

17,000

29,500

16,800

30,900

16,900

73.0

23,100

16,100

23,900

16,000

25,200

16,400

26,300

16,300

27,000

16,700

28,900

16,500

30,300

16,700

77.0

22,800

15,900

23,500

15,800

24,800

16,200

25,900

16,100

26,600

16,500

28,400

16,300

29,800

16,500

82.0

22,400

15,700

23,000

15,600

24,300

15,900

25,300

15,800

26,000

16,300

27,800

16,000

29,100

16,200

86.0

22,000

15,500

22,600

15,400

23,900

15,700

24,900

15,600

25,500

16,000

27,300

15,800

28,600

16,000

91.0

21,600

15,300

22,100

15,100

23,300

15,400

24,300

15,300

25,000

15,800

26,700

15,600

28,000

15,700

95.0

21,300

15,100

21,700

14,900

22,900

15,200

24,000

15,100

24,500

15,600

26,200

15,400

27,500

15,500

100.0

20,900

14,900

21,200

14,600

22,400

15,000

23,300

14,900

23,900

15,300

25,600

15,100

26,800

15,300

104.0

20,500

14,700

20,800

14,400

21,900

14,800

22,900

14,700

23,500

15,100

25,100

14,900

26,300

15,100

110.0

20,100

14,500

20,200

14,100

21,300

14,500

22,200

14,400

22,800

14,800

24,400

14,600

25,600

14,800

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-24

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-2-2. Heating CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with All Indoor Units


All indoor units
Model
size

06

08

12

15

18

CT

24

Entering air temp.

SHC : Sensible Heat Capacity(BTU/h)


Model
size

Entering air temp.

Outdoor

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

81degF D.B.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

degF W.B.

SHC

SHC

SHC

SHC

degF W.B.

SHC

SHC

SHC

SHC

5.0

4,200

4,100

4,000

4,000

5.0

21,100

20,500

20,100

20,100

14.0

5,000

4,800

4,600

4,600

14.0

24,800

23,800

23,200

23,000

23.0

5,700

5,400

5,200

4,600

23.0

28,500

27,000

26,200

23,000

32.0

6,400

6,000

5,400

4,600

32.0

32,200

30,200

26,800

23,000

37.0

6,900

6,400

5,400

4,600

37.0

34,500

32,200

26,800

23,000

43.0

7,300

6,700

5,400

4,600

43.0

36,700

34,000

26,800

23,000

46.0

7,600

6,700

5,400

4,600

46.0

38,100

34,000

26,800

23,000

50.0

7,900

6,700

5,400

4,600

50.0

39,600

34,000

26,800

23,000

55.0

8,300

6,700

5,400

4,600

55.0

41,300

34,000

26,800

23,000

60.0

8,300

6,700

5,400

4,600

60.0

41,300

34,000

26,800

23,000

65.0

8,300

6,700

5,400

4,600

65.0

41,300

34,000

26,800

23,000

5.0

5,500

5,300

5,200

5,200

5.0

24,700

24,000

23,500

23,500

14.0

6,400

6,200

6,000

6,000

14.0

29,000

27,900

27,100

26,900

23.0

7,400

7,000

6,800

6,000

23.0

33,400

31,500

30,700

26,900

32.0

8,400

7,900

7,000

6,000

32.0

37,700

35,300

31,400

26,900

37.0

9,000

8,400

7,000

6,000

37.0

40,300

37,600

31,400

26,900

43.0

9,500

9,000

7,000

6,000

43.0

42,900

40,000

31,400

26,900

46.0

9,900

9,000

7,000

6,000

46.0

44,600

40,000

31,400

26,900

50.0

10,300

9,000

7,000

6,000

50.0

46,400

40,000

31,400

26,900

55.0

10,700

9,000

7,000

6,000

55.0

48,300

40,000

31,400

26,900

60.0

10,700

9,000

7,000

6,000

60.0

48,300

40,000

31,400

26,900

65.0

10,700

9,000

7,000

6,000

65.0

48,300

40,000

31,400

26,900

5.0

8,400

8,200

8,000

8,000

5.0

33,300

32,300

31,800

31,800

30

36

81degF D.B.

14.0

9,900

9,500

9,300

9,200

14.0

39,200

37,600

36,600

36,300

23.0

11,400

10,800

10,500

9,200

23.0

45,100

42,600

41,400

36,300

32.0

12,900

12,100

10,700

9,200

37.0

13,800

12,900

10,700

9,200

48

32.0

50,900

47,700

42,400

36,300

37.0

54,400

50,800

42,400

36,300

43.0

14,700

13,500

10,700

9,200

43.0

58,000

54,000

42,400

36,300

46.0

15,300

13,500

10,700

9,200

46.0

60,300

54,000

42,400

36,300

50.0

15,900

13,500

10,700

9,200

50.0

62,600

54,000

42,400

36,300

55.0

16,500

13,500

10,700

9,200

55.0

65,200

54,000

42,400

36,300

60.0

16,500

13,500

10,700

9,200

60.0

65,200

54,000

42,400

36,300

65.0

16,500

13,500

10,700

9,200

65.0

65,200

54,000

42,400

36,300

5.0

10,500

10,200

10,000

10,000

5.0

37,100

36,000

35,400

35,400

14.0

12,400

11,900

11,600

11,500

14.0

43,700

41,900

40,800

40,500

23.0

14,300

13,500

13,100

11,500

23.0

50,200

47,400

46,100

40,500

32.0

16,100

15,100

13,400

11,500

32.0

56,700

53,100

47,200

40,500

37.0

17,200

16,100

13,400

11,500

37.0

60,700

56,600

47,200

40,500

43.0

18,300

17,000

13,400

11,500

43.0

64,600

60,000

47,200

40,500

46.0

19,100

17,000

13,400

11,500

46.0

67,100

60,000

47,200

40,500

50.0

19,800

17,000

13,400

11,500

50.0

69,800

60,000

47,200

40,500

55.0

20,600

17,000

13,400

11,500

55.0

72,700

60,000

47,200

40,500

60.0

20,600

17,000

13,400

11,500

60.0

72,700

60,000

47,200

40,500

65.0

20,600

17,000

13,400

11,500

65.0

72,700

60,000

47,200

40,500

5.0

12,400

12,100

11,900

11,900

5.0

49,300

47,900

47,000

47,000

14.0

14,600

14,100

13,700

13,600

14.0

58,000

55,700

54,200

53,800

23.0

16,800

15,900

15,500

13,600

23.0

66,700

63,100

61,300

53,800

32.0

19,000

17,800

15,800

13,600

32.0

75,400

70,700

62,800

53,800

37.0

20,300

19,000

15,800

13,600

37.0

80,600

75,300

62,800

53,800

43.0

21,600

20,000

15,800

13,600

43.0

85,800

80,000

62,800

53,800

46.0

22,500

20,000

15,800

13,600

46.0

89,300

80,000

62,800

53,800

50.0

23,400

20,000

15,800

13,600

50.0

92,800

80,000

62,800

53,800

55.0

24,400

20,000

15,800

13,600

55.0

96,600

80,000

62,800

53,800

60.0

24,400

20,000

15,800

13,600

60.0

96,600

80,000

62,800

53,800

65.0

24,400

20,000

15,800

13,600

65.0

96,600

80,000

62,800

53,800

5.0

16,700

16,200

15,900

15,900

5.0

66,800

64,900

63,700

63,700

14.0

19,600

18,800

18,300

18,200

14.0

78,600

75,500

73,400

72,900

23.0

22,500

21,300

20,700

18,200

23.0

90,400

85,400

83,100

72,900

32.0

25,400

23,900

21,200

18,200

32.0

102,100

95,700

85,000

72,900

37.0

27,200

25,400

21,200

18,200

37.0

109,200

102,000

85,000

72,900

54

72

96

43.0

29,000

27,000

21,200

18,200

43.0

116,300

108,000

85,000

72,900

46.0

30,100

27,000

21,200

18,200

46.0

120,900

108,000

85,000

72,900

50.0

31,300

27,000

21,200

18,200

50.0

125,700

108,000

85,000

72,900

55.0

32,600

27,000

21,200

18,200

55.0

130,900

108,000

85,000

72,900

60.0

32,600

27,000

21,200

18,200

60.0

130,900

108,000

85,000

72,900

65.0

32,600

27,000

21,200

18,200

65.0

130,900

108,000

85,000

72,900

5.0

18,600

18,000

17,700

17,700

14.0

21,800

21,000

20,400

20,200

23.0

25,100

23,700

23,100

20,200

32.0

28,300

26,600

23,600

20,200

37.0

30,300

28,300

23,600

20,200

43.0

32,300

30,000

23,600

20,200

46.0

33,600

30,000

23,600

20,200

50.0

34,900

30,000

23,600

20,200

55.0

36,300

30,000

23,600

20,200

60.0

36,300

30,000

23,600

20,200

65.0

36,300

30,000

23,600

20,200

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

27

SHC : Sensible Heat Capacity(BTU/h)


Outdoor

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-25

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3. Cooing and Heating Capacity with PUHY-P168~240, PURY-P144~240TSHMU-A/YSHMU-A


1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PEFY-P-NMSU-E
CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,700

5,200

5,900

5,200

6,200

5,400

6,400

5,300

6,700

5,600

7,200

5,500

7,600

5,600

73.0

5,600

5,200

5,800

5,100

6,200

5,300

6,400

5,300

6,600

5,500

7,100

5,500

7,500

5,600

77.0

5,600

5,100

5,800

5,100

6,100

5,300

6,300

5,300

6,600

5,500

7,100

5,500

7,400

5,600

82.0

5,500

5,100

5,700

5,100

6,000

5,300

6,200

5,200

6,500

5,500

7,000

5,400

7,400

5,600

86.0

5,500

5,100

5,600

5,100

6,000

5,200

6,200

5,200

6,400

5,500

6,900

5,400

7,300

5,600

91.0

5,400

5,100

5,600

5,000

5,900

5,200

6,100

5,200

6,400

5,400

6,800

5,400

7,200

5,500

95.0

5,400

5,000

5,500

5,000

5,800

5,200

6,000

5,200

6,300

5,400

6,800

5,400

7,200

5,500

100.0

5,300

5,000

5,400

5,000

5,800

5,200

6,000

5,100

6,200

5,400

6,700

5,300

7,100

5,500

104.0

5,200

5,000

5,400

4,900

5,700

5,100

5,900

5,100

6,200

5,400

6,700

5,300

7,000

5,500

110.0

5,200

5,000

5,300

4,900

5,600

5,100

5,800

5,100

6,100

5,300

6,600

5,300

6,900

5,400

68.0

7,500

6,700

7,800

6,700

8,300

6,900

8,500

6,800

8,900

7,100

9,500

7,100

10,000

7,200

73.0

7,500

6,700

7,700

6,600

8,200

6,900

8,400

6,800

8,800

7,100

9,400

7,000

9,900

7,200

77.0

7,400

6,600

7,600

6,600

8,100

6,800

8,400

6,800

8,700

7,100

9,300

7,000

9,800

7,200

82.0

7,300

6,600

7,500

6,500

8,000

6,800

8,200

6,700

8,600

7,000

9,200

7,000

9,700

7,200

86.0

7,200

6,600

7,400

6,500

7,900

6,700

8,200

6,700

8,500

7,000

9,200

6,900

9,600

7,100

91.0

7,200

6,500

7,300

6,500

7,800

6,700

8,100

6,700

8,400

7,000

9,100

6,900

9,500

7,100

95.0

7,100

6,500

7,300

6,400

7,700

6,700

8,000

6,600

8,300

6,900

9,000

6,900

9,500

7,100

100.0

7,000

6,500

7,200

6,400

7,600

6,600

7,900

6,600

8,200

6,900

8,900

6,800

9,400

7,000

104.0

6,900

6,400

7,100

6,400

7,500

6,600

7,800

6,600

8,100

6,900

8,800

6,800

9,300

7,000

110.0

6,800

6,400

7,000

6,300

7,400

6,500

7,700

6,500

8,000

6,800

8,700

6,800

9,200

7,000

68.0

11,300

8,900

11,700

8,900

12,400

9,100

12,800

9,000

13,300

9,400

14,300

9,300

15,000

9,500

73.0

11,200

8,900

11,600

8,800

12,300

9,100

12,700

9,000

13,200

9,400

14,200

9,300

14,900

9,400

77.0

11,100

8,800

11,400

8,700

12,100

9,000

12,600

8,900

13,100

9,300

14,000

9,200

14,800

9,400

82.0

11,000

8,700

11,300

8,700

12,000

8,900

12,400

8,900

12,900

9,200

13,900

9,200

14,600

9,300

86.0

10,900

8,700

11,200

8,600

11,900

8,900

12,300

8,800

12,800

9,200

13,800

9,100

14,500

9,300

91.0

10,800

8,600

11,000

8,500

11,700

8,800

12,100

8,700

12,600

9,100

13,600

9,100

14,400

9,300

95.0

10,700

8,600

10,900

8,500

11,600

8,800

12,000

8,700

12,500

9,100

13,500

9,000

14,200

9,200

100.0

10,500

8,500

10,800

8,400

11,400

8,700

11,900

8,600

12,400

9,000

13,300

9,000

14,100

9,200

104.0

10,400

8,500

10,700

8,400

11,300

8,700

11,700

8,600

12,300

9,000

13,200

8,900

14,000

9,100

110.0

10,300

8,400

10,500

8,300

11,100

8,600

11,600

8,500

12,100

8,900

13,100

8,800

13,800

9,100

68.0

14,200

10,700

14,600

10,600

15,500

10,900

16,000

10,800

16,700

11,200

17,900

11,100

18,800

11,300

73.0

14,000

10,600

14,500

10,500

15,300

10,800

15,900

10,700

16,500

11,200

17,700

11,000

18,600

11,200

77.0

13,900

10,500

14,300

10,500

15,200

10,800

15,700

10,700

16,300

11,100

17,500

11,000

18,500

11,200

82.0

13,800

10,500

14,100

10,400

15,000

10,700

15,500

10,600

16,100

11,000

17,400

10,900

18,300

11,100

86.0

13,600

10,400

14,000

10,300

14,800

10,600

15,400

10,500

16,000

11,000

17,200

10,900

18,100

11,100

91.0

13,500

10,300

13,800

10,200

14,700

10,500

15,200

10,400

15,800

10,900

17,000

10,800

18,000

11,000

95.0

13,300

10,300

13,600

10,100

14,500

10,500

15,000

10,400

15,700

10,800

16,900

10,700

17,800

10,900

100.0

13,200

10,200

13,500

10,100

14,300

10,400

14,800

10,300

15,500

10,700

16,700

10,700

17,600

10,900

104.0

13,000

10,100

13,300

10,000

14,200

10,300

14,700

10,200

15,300

10,700

16,500

10,600

17,500

10,800

110.0

12,900

10,000

13,100

9,900

13,900

10,200

14,500

10,100

15,100

10,600

16,300

10,500

17,300

10,800

68.0

17,000

13,200

17,600

13,100

18,600

13,500

19,200

13,400

20,000

13,900

21,500

13,800

22,600

14,000

73.0

16,800

13,100

17,300

13,000

18,400

13,400

19,000

13,300

19,800

13,800

21,200

13,700

22,300

13,900

77.0

16,700

13,000

17,200

12,900

18,200

13,300

18,800

13,200

19,600

13,800

21,100

13,600

22,200

13,900

82.0

16,500

12,900

17,000

12,800

18,000

13,200

18,600

13,100

19,400

13,700

20,800

13,500

21,900

13,800

86.0

16,300

12,900

16,800

12,700

17,800

13,100

18,400

13,000

19,200

13,600

20,700

13,500

21,800

13,700

91.0

16,200

12,800

16,600

12,600

17,600

13,000

18,200

12,900

19,000

13,500

20,400

13,400

21,500

13,700

95.0

16,000

12,700

16,400

12,600

17,400

13,000

18,000

12,800

18,800

13,400

20,200

13,300

21,400

13,600

100.0

15,800

12,600

16,100

12,400

17,200

12,900

17,800

12,800

18,600

13,300

20,000

13,200

21,200

13,500

104.0

15,700

12,500

16,000

12,400

17,000

12,800

17,600

12,700

18,400

13,300

19,900

13,200

21,000

13,500

110.0

15,400

12,400

15,700

12,200

16,700

12,700

17,300

12,600

18,100

13,100

19,600

13,100

20,700

13,400

68.0

22,600

17,400

23,400

17,300

24,800

17,800

25,600

17,600

26,600

18,300

28,600

18,100

30,000

18,500

73.0

22,400

17,300

23,100

17,200

24,500

17,700

25,300

17,500

26,300

18,200

28,200

18,000

29,700

18,400

77.0

22,200

17,200

22,800

17,000

24,200

17,600

25,100

17,400

26,100

18,100

28,000

17,900

29,500

18,300

82.0

21,900

17,000

22,500

16,900

23,900

17,400

24,700

17,200

25,700

18,000

27,700

17,800

29,200

18,200

86.0

21,700

16,900

22,300

16,800

23,700

17,300

24,500

17,100

25,500

17,900

27,500

17,700

28,900

18,100

91.0

21,500

16,800

22,000

16,700

23,400

17,200

24,200

17,000

25,200

17,800

27,200

17,600

28,600

18,000

95.0

21,300

16,700

21,800

16,500

23,100

17,100

24,000

16,900

25,000

17,700

26,900

17,500

28,400

17,900

100.0

21,000

16,600

21,500

16,400

22,800

16,900

23,700

16,800

24,700

17,500

26,600

17,400

28,100

17,800

104.0

20,800

16,500

21,200

16,300

22,600

16,800

23,400

16,700

24,400

17,500

26,400

17,300

27,900

17,700

110.0

20,500

16,400

20,900

16,100

22,200

16,700

23,100

16,600

24,100

17,300

26,000

17,200

27,500

17,600

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-26

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,200

9,800

14,600

9,700

15,500

9,900

16,000

9,800

16,700

10,200

17,900

10,100

18,800

10,200

73.0

14,000

9,700

14,500

9,600

15,300

9,800

15,900

9,700

16,500

10,100

17,700

10,000

18,600

10,100

77.0

13,900

9,600

14,300

9,500

15,200

9,800

15,700

9,600

16,300

10,000

17,500

9,900

18,500

10,000

82.0

13,800

9,500

14,100

9,400

15,000

9,700

15,500

9,500

16,100

9,900

17,400

9,800

18,300

9,900

86.0

13,600

9,400

14,000

9,300

14,800

9,600

15,400

9,400

16,000

9,800

17,200

9,800

18,100

9,900

91.0

13,500

9,300

13,800

9,200

14,700

9,500

15,200

9,400

15,800

9,700

17,000

9,700

18,000

9,800

95.0

13,300

9,300

13,600

9,200

14,500

9,400

15,000

9,300

15,700

9,700

16,900

9,600

17,800

9,700

100.0

13,200

9,200

13,500

9,100

14,300

9,300

14,800

9,200

15,500

9,600

16,700

9,500

17,600

9,700

104.0

13,000

9,100

13,300

9,000

14,200

9,200

14,700

9,100

15,300

9,500

16,500

9,500

17,500

9,600

12,900

9,000

13,100

8,900

13,900

9,100

14,500

9,000

15,100

9,400

16,300

9,400

17,300

9,500

68.0

17,100

11,900

17,600

11,800

18,700

12,100

19,300

11,900

20,100

12,400

21,600

12,300

22,600

12,400

73.0

16,900

11,800

17,400

11,700

18,500

12,000

19,100

11,800

19,800

12,300

21,300

12,200

22,400

12,300

77.0

16,700

11,700

17,200

11,600

18,300

11,900

18,900

11,700

19,700

12,200

21,100

12,100

22,200

12,200

82.0

16,600

11,600

17,000

11,500

18,000

11,800

18,700

11,600

19,400

12,100

20,900

12,000

22,000

12,200

86.0

16,400

11,500

16,800

11,400

17,900

11,700

18,500

11,500

19,300

12,000

20,700

11,900

21,800

12,100

91.0

16,200

11,400

16,600

11,300

17,600

11,600

18,300

11,400

19,000

11,900

20,500

11,800

21,600

12,000

95.0

16,100

11,300

16,400

11,200

17,500

11,500

18,000

11,400

18,900

11,800

20,300

11,700

21,400

11,900

100.0

15,900

11,200

16,200

11,100

17,200

11,400

17,900

11,300

18,600

11,700

20,100

11,600

21,200

11,800

104.0

15,700

11,100

16,000

11,000

17,100

11,300

17,700

11,200

18,400

11,600

19,900

11,600

21,100

11,800

110.0

15,500

11,000

15,800

10,800

16,800

11,200

17,400

11,000

18,200

11,500

19,700

11,500

20,800

11,700

68.0

22,600

15,600

23,300

15,500

24,700

15,900

25,500

15,700

26,500

16,300

28,500

16,100

29,900

16,300

73.0

22,300

15,500

23,000

15,400

24,400

15,800

25,200

15,500

26,200

16,100

28,200

16,000

29,600

16,200

77.0

22,100

15,400

22,800

15,300

24,100

15,600

25,000

15,400

26,000

16,000

27,900

15,900

29,400

16,100

82.0

21,900

15,200

22,500

15,100

23,800

15,500

24,700

15,300

25,700

15,900

27,600

15,800

29,100

16,000

86.0

21,700

15,100

22,200

15,000

23,600

15,400

24,400

15,200

25,400

15,800

27,400

15,700

28,900

15,900

91.0

21,400

15,000

21,900

14,800

23,300

15,200

24,100

15,000

25,100

15,600

27,100

15,500

28,600

15,700

95.0

21,200

14,900

21,700

14,700

23,100

15,100

24,000

14,900

24,900

15,500

26,800

15,400

28,300

15,600

100.0

21,000

14,700

21,400

14,500

22,800

14,900

23,600

14,800

24,600

15,400

26,500

15,300

28,000

15,500

104.0

20,800

14,600

21,200

14,400

22,500

14,800

23,400

14,700

24,400

15,300

26,300

15,200

27,800

15,400

110.0

20,500

14,500

20,800

14,200

22,200

14,700

23,000

14,500

24,000

15,100

26,000

15,000

27,500

15,300

68.0

25,500

17,900

26,300

17,800

27,900

18,200

28,800

18,000

29,900

18,600

32,100

18,500

33,700

18,700

73.0

25,200

17,700

26,000

17,600

27,500

18,000

28,500

17,800

29,600

18,500

31,800

18,300

33,400

18,500

77.0

25,000

17,600

25,700

17,500

27,300

17,900

28,200

17,700

29,300

18,400

31,500

18,200

33,200

18,400

82.0

24,700

17,400

25,400

17,300

26,900

17,700

27,800

17,500

29,000

18,200

31,200

18,100

32,800

18,300

86.0

24,400

17,300

25,100

17,100

26,600

17,600

27,600

17,400

28,700

18,100

30,900

17,900

32,600

18,200

91.0

24,200

17,200

24,800

17,000

26,300

17,400

27,200

17,200

28,400

17,900

30,600

17,800

32,200

18,100

95.0

23,900

17,000

24,500

16,800

26,000

17,300

27,000

17,100

28,100

17,800

30,300

17,700

32,000

18,000

100.0

23,700

16,900

24,200

16,700

25,700

17,100

26,600

16,900

27,800

17,700

29,900

17,500

31,600

17,800

104.0

23,400

16,800

23,900

16,500

25,400

17,000

26,400

16,800

27,500

17,500

29,700

17,400

31,400

17,700

110.0

23,100

16,600

23,500

16,300

25,000

16,800

26,000

16,600

27,100

17,400

29,300

17,300

31,000

17,600

68.0

28,400

19,900

29,300

19,800

31,000

20,300

32,100

20,000

33,300

20,700

35,800

20,500

37,600

20,800

73.0

28,100

19,700

28,900

19,600

30,700

20,100

31,700

19,800

32,900

20,600

35,400

20,400

37,200

20,600

77.0

27,800

19,600

28,600

19,400

30,400

19,900

31,400

19,700

32,700

20,400

35,100

20,200

36,900

20,500

82.0

27,500

19,400

28,300

19,200

30,000

19,700

31,000

19,500

32,300

20,200

34,700

20,100

36,600

20,400

86.0

27,200

19,300

28,000

19,100

29,700

19,600

30,700

19,300

32,000

20,100

34,400

20,000

36,300

20,200

91.0

26,900

19,100

27,600

18,900

29,300

19,400

30,300

19,100

31,600

19,900

34,000

19,800

35,900

20,100

95.0

26,700

18,900

27,300

18,700

29,000

19,300

30,000

19,000

31,300

19,800

33,700

19,700

35,600

20,000

100.0

26,400

18,800

26,900

18,500

28,600

19,100

29,700

18,800

30,900

19,600

33,400

19,500

35,300

19,800

104.0

26,100

18,600

26,600

18,400

28,300

18,900

29,400

18,700

30,600

19,500

33,100

19,400

35,000

19,700

110.0

25,700

18,500

26,200

18,200

27,900

18,700

28,900

18,500

30,200

19,300

32,600

19,200

34,500

19,500

68.0

34,200

24,500

35,300

24,300

37,400

25,000

38,600

24,600

40,100

25,600

43,100

25,400

45,300

25,700

73.0

33,800

24,300

34,800

24,100

36,900

24,800

38,200

24,500

39,700

25,400

42,600

25,200

44,800

25,500

77.0

33,500

24,100

34,500

23,900

36,600

24,600

37,800

24,300

39,300

25,300

42,300

25,000

44,500

25,400

82.0

33,100

23,900

34,000

23,700

36,100

24,400

37,400

24,100

38,900

25,100

41,800

24,800

44,100

25,200

86.0

32,800

23,800

33,700

23,500

35,700

24,200

37,000

23,900

38,500

24,900

41,500

24,700

43,700

25,100

91.0

32,400

23,600

33,200

23,300

35,300

24,000

36,500

23,700

38,000

24,700

41,000

24,500

43,300

24,900

95.0

32,100

23,400

32,900

23,100

34,900

23,800

36,000

23,500

37,700

24,500

40,700

24,400

42,900

24,800

100.0

31,800

23,200

32,400

22,900

34,500

23,600

35,700

23,300

37,300

24,300

40,200

24,200

42,500

24,600

104.0

31,400

23,100

32,100

22,800

34,100

23,400

35,400

23,200

36,900

24,200

39,900

24,000

42,100

24,500

110.0

31,000

22,800

31,500

22,500

33,600

23,200

34,800

23,000

36,300

23,900

39,300

23,800

41,600

24,300

68.0

45,500

31,400

46,900

31,200

49,700

32,000

51,400

31,500

53,400

32,700

57,300

32,400

60,200

32,700

73.0

45,000

31,100

46,300

30,900

49,100

31,600

50,800

31,200

52,800

32,400

56,700

32,100

59,700

32,500

77.0

44,500

30,900

45,800

30,600

48,600

31,400

50,300

31,000

52,300

32,200

56,200

31,900

59,200

32,300

82.0

44,100

30,600

45,300

30,300

48,000

31,100

49,700

30,700

51,700

31,900

55,700

31,600

58,600

32,000

86.0

43,600

30,400

44,800

30,100

47,500

30,800

49,200

30,400

51,200

31,600

55,200

31,400

58,100

31,800

91.0

43,200

30,100

44,200

29,800

47,000

30,500

48,600

30,100

50,600

31,300

54,600

31,100

57,500

31,600

95.0

42,700

29,800

43,700

29,500

46,500

30,300

48,000

29,900

50,200

31,100

54,100

30,900

57,100

31,400

100.0

42,200

29,600

43,100

29,200

45,800

30,000

47,500

29,600

49,600

30,800

53,400

30,700

56,500

31,100

104.0

41,800

29,300

42,700

28,900

45,400

29,700

47,100

29,400

49,100

30,600

53,000

30,500

56,000

31,000

110.0

41,200

29,000

42,000

28,600

44,600

29,400

46,300

29,100

48,300

30,300

52,300

30,200

55,300

30,700

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-27

NOMINAL
CAPACITY
TABLES

110.0

CT

48

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

50,900

36,200

52,600

36,000

55,700

36,900

57,600

36,400

59,800

37,800

64,300

37,500

67,500

37,900

73.0

50,400

35,900

51,900

35,700

55,000

36,600

56,900

36,100

59,100

37,500

63,600

37,200

66,800

37,700

77.0

49,900

35,600

51,400

35,400

54,500

36,300

56,400

35,900

58,700

37,300

63,000

36,900

66,300

37,500

82.0

49,400

35,400

50,700

35,000

53,800

36,000

55,700

35,500

58,000

37,000

62,400

36,700

65,700

37,200

86.0

48,900

35,100

50,200

34,800

53,300

35,700

55,100

35,300

57,400

36,700

61,800

36,400

65,100

37,000

91.0

48,400

34,800

49,500

34,400

52,600

35,400

54,400

35,000

56,700

36,400

61,100

36,100

64,500

36,700

95.0

47,900

34,600

49,000

34,200

52,100

35,200

54,000

34,700

56,200

36,200

60,600

35,900

63,900

36,500

100.0

47,300

34,300

48,300

33,800

51,400

34,800

53,300

34,400

55,500

35,900

59,900

35,600

63,300

36,300

104.0

46,800

34,000

47,800

33,600

50,800

34,600

52,700

34,200

55,000

35,700

59,400

35,400

62,800

36,100

110.0

46,200

33,700

47,000

33,200

50,000

34,200

51,900

33,800

54,200

35,300

58,600

35,100

62,000

35,800

68.0

68,000

47,600

70,200

47,300

74,400

48,500

76,900

47,800

79,900

49,700

85,800

49,200

90,100

49,700

73.0

67,300

47,200

69,300

46,900

73,500

48,100

76,000

47,400

79,000

49,200

84,900

48,800

89,300

49,400

77.0

66,700

46,900

68,600

46,500

72,800

47,700

75,300

47,100

78,300

48,900

84,200

48,500

88,600

49,100

82.0

65,900

46,500

67,700

46,100

71,800

47,200

74,400

46,600

77,400

48,500

83,300

48,100

87,700

48,800

86.0

65,300

46,100

67,000

45,700

71,100

46,900

73,600

46,300

76,700

48,200

82,600

47,800

87,000

48,500

91.0

64,600

45,700

66,200

45,200

70,300

46,500

72,700

45,900

75,700

47,700

81,600

47,400

86,100

48,100

95.0

63,900

45,400

65,400

44,900

69,500

46,100

72,000

45,500

75,100

47,400

80,900

47,100

85,400

47,800

100.0

63,200

45,000

64,500

44,400

68,600

45,700

71,100

45,100

74,200

47,000

80,000

46,700

84,500

47,500

104.0

62,600

44,700

63,900

44,100

67,900

45,300

70,400

44,800

73,400

46,700

79,300

46,400

83,900

47,200

110.0

61,700

44,200

62,800

43,500

66,800

44,800

69,300

44,300

72,400

46,200

78,300

46,000

82,800

46,800

68.0

90,600

63,900

93,500

63,500

99,100

65,200

102,400

64,200

106,400

66,700

114,300

66,100

120,000

66,800

73.0

89,600

63,400

92,300

62,900

97,900

64,500

101,200

63,700

105,200

66,100

113,000

65,500

118,900

66,400

77.0

88,800

62,900

91,400

62,400

96,900

64,100

100,300

63,200

104,300

65,700

112,100

65,100

117,900

66,000

82.0

87,800

62,400

90,200

61,800

95,700

63,500

99,000

62,600

103,100

65,200

110,900

64,600

116,800

65,500

86.0

87,000

61,900

89,300

61,300

94,700

63,000

98,100

62,200

102,100

64,700

110,000

64,200

115,800

65,200

91.0

86,000

61,400

88,100

60,700

93,600

62,400

96,800

61,600

100,900

64,200

108,700

63,700

114,700

64,700

95.0

85,100

61,000

87,200

60,300

92,600

62,000

96,000

61,200

100,000

63,800

107,800

63,300

113,700

64,300

100.0

84,200

60,400

85,900

59,600

91,400

61,400

94,700

60,700

98,800

63,200

106,500

62,800

112,600

63,900

104.0

83,300

60,000

85,000

59,200

90,400

60,900

93,800

60,200

97,800

62,800

105,700

62,400

111,700

63,500

110.0

82,200

59,400

83,600

58,500

89,000

60,200

92,300

59,600

96,400

62,200

104,200

61,800

110,300

63,000

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-28

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,800

4,500

6,000

4,400

6,400

4,600

6,600

4,500

6,800

4,700

7,300

4,700

7,700

4,700

73.0

5,700

4,400

5,900

4,400

6,300

4,500

6,500

4,500

6,700

4,700

7,200

4,600

7,600

4,700

77.0

5,700

4,400

5,900

4,400

6,200

4,500

6,400

4,500

6,700

4,700

7,200

4,600

7,600

4,700

82.0

5,600

4,400

5,800

4,300

6,100

4,500

6,300

4,400

6,600

4,600

7,100

4,600

7,500

4,700

86.0

5,600

4,400

5,700

4,300

6,100

4,500

6,300

4,400

6,500

4,600

7,000

4,600

7,400

4,600

91.0

5,500

4,300

5,600

4,300

6,000

4,400

6,200

4,400

6,500

4,600

7,000

4,500

7,300

4,600

95.0

5,500

4,300

5,600

4,300

5,900

4,400

6,000

4,300

6,400

4,500

6,900

4,500

7,300

4,600

100.0

5,400

4,300

5,500

4,200

5,900

4,400

6,000

4,300

6,300

4,500

6,800

4,500

7,200

4,600

104.0

5,300

4,200

5,400

4,200

5,800

4,300

6,000

4,300

6,300

4,500

6,800

4,500

7,200

4,600

110.0

5,300

4,200

5,400

4,100

5,700

4,300

5,900

4,300

6,200

4,400

6,700

4,400

7,100

4,500

68.0

7,400

5,500

7,700

5,400

8,100

5,600

8,400

5,500

8,700

5,700

9,400

5,700

9,800

5,800

73.0

7,300

5,400

7,600

5,400

8,000

5,500

8,300

5,500

8,600

5,700

9,300

5,600

9,700

5,700

77.0

7,300

5,400

7,500

5,400

7,900

5,500

8,200

5,400

8,500

5,700

9,200

5,600

9,700

5,700

82.0

7,200

5,400

7,400

5,300

7,800

5,500

8,100

5,400

8,400

5,600

9,100

5,600

9,600

5,700

86.0

7,100

5,300

7,300

5,300

7,800

5,400

8,000

5,400

8,400

5,600

9,000

5,500

9,500

5,600
5,600

91.0

7,000

5,300

7,200

5,200

7,700

5,400

8,000

5,300

8,300

5,600

8,900

5,500

9,400

95.0

7,000

5,200

7,100

5,200

7,600

5,300

8,000

5,300

8,200

5,500

8,800

5,500

9,300

5,600

100.0

6,900

5,200

7,000

5,100

7,500

5,300

7,800

5,300

8,100

5,500

8,700

5,400

9,200

5,500

104.0

6,800

5,200

7,000

5,100

7,400

5,300

7,700

5,200

8,000

5,400

8,600

5,400

9,100

5,500

110.0

6,700

5,100

6,800

5,100

7,300

5,200

7,600

5,200

7,900

5,400

8,500

5,400

9,000

5,500

68.0

11,300

7,900

11,600

7,900

12,300

8,100

12,800

8,000

13,300

8,300

14,200

8,200

15,000

8,300

73.0

11,200

7,900

11,500

7,800

12,200

8,000

12,600

7,900

13,100

8,200

14,100

8,100

14,800

8,200

77.0

11,100

7,800

11,400

7,800

12,100

8,000

12,500

7,800

13,000

8,200

14,000

8,100

14,700

8,200

82.0

10,900

7,700

11,200

7,700

11,900

7,900

12,300

7,800

12,800

8,100

13,800

8,000

14,500

8,100

86.0

10,800

7,700

11,100

7,600

11,800

7,800

12,200

7,700

12,700

8,000

13,700

8,000

14,400

8,100

91.0

10,700

7,600

11,000

7,500

11,700

7,700

12,100

7,600

12,600

8,000

13,500

7,900

14,300

8,000

95.0

10,600

7,600

10,900

7,500

11,500

7,700

12,000

7,600

12,500

7,900

13,400

7,900

14,200

8,000

100.0

10,500

7,500

10,700

7,400

11,400

7,600

11,800

7,500

12,300

7,800

13,300

7,800

14,000

7,900

10,400

7,400

10,600

7,300

11,300

7,600

11,700

7,500

12,200

7,800

13,200

7,700

13,900

7,900

10,200

7,400

10,400

7,300

11,100

7,500

11,500

7,400

12,000

7,700

13,000

7,700

13,700

7,800

68.0

14,200

10,800

14,600

10,700

15,500

11,000

16,000

10,900

16,700

11,300

17,900

11,200

18,800

11,400

73.0

14,000

10,700

14,500

10,600

15,300

10,900

15,900

10,800

16,500

11,300

17,700

11,100

18,600

11,300

77.0

13,900

10,600

14,300

10,500

15,200

10,900

15,700

10,800

16,300

11,200

17,500

11,100

18,500

11,300

82.0

13,800

10,600

14,100

10,500

15,000

10,800

15,500

10,700

16,100

11,100

17,400

11,000

18,300

11,200

86.0

13,600

10,500

14,000

10,400

14,800

10,700

15,400

10,600

16,000

11,100

17,200

11,000

18,100

11,200

91.0

13,500

10,400

13,800

10,300

14,700

10,600

15,200

10,500

15,800

11,000

17,000

10,900

18,000

11,100

95.0

13,300

10,300

13,600

10,200

14,500

10,600

15,000

10,500

15,700

10,900

16,900

10,800

17,800

11,100

100.0

13,200

10,300

13,500

10,100

14,300

10,500

14,800

10,400

15,500

10,800

16,700

10,800

17,600

11,000

104.0

13,000

10,200

13,300

10,100

14,200

10,400

14,700

10,300

15,300

10,800

16,500

10,700

17,500

10,900

110.0

12,900

10,100

13,100

10,000

13,900

10,300

14,500

10,200

15,100

10,700

16,300

10,600

17,300

10,900

68.0

17,100

12,700

17,600

12,600

18,700

13,000

19,300

12,800

20,100

13,400

21,600

13,200

22,600

13,400

73.0

16,900

12,600

17,400

12,500

18,500

12,900

19,100

12,700

19,800

13,300

21,300

13,100

22,400

13,300

77.0

16,700

12,500

17,200

12,400

18,300

12,800

18,900

12,700

19,700

13,200

21,100

13,000

22,200

13,300

82.0

16,600

12,400

17,000

12,300

18,000

12,700

18,700

12,600

19,400

13,100

20,900

13,000

22,000

13,200

86.0

16,400

12,400

16,800

12,200

17,900

12,600

18,500

12,500

19,300

13,000

20,700

12,900

21,800

13,100

91.0

16,200

12,300

16,600

12,100

17,600

12,500

18,300

12,400

19,000

12,900

20,500

12,800

21,600

13,000

95.0

16,100

12,200

16,400

12,100

17,500

12,400

18,000

12,300

18,900

12,800

20,300

12,700

21,400

13,000

100.0

15,900

12,100

16,200

11,900

17,200

12,300

17,900

12,200

18,600

12,700

20,100

12,600

21,200

12,900

104.0

15,700

12,000

16,000

11,900

17,100

12,200

17,700

12,100

18,400

12,700

19,900

12,600

21,100

12,800

110.0

15,500

11,900

15,800

11,700

16,800

12,100

17,400

12,000

18,200

12,500

19,700

12,500

20,800

12,700

68.0

22,600

16,700

23,300

16,600

24,700

17,100

25,500

16,900

26,500

17,600

28,500

17,400

29,900

17,600

73.0

22,300

16,600

23,000

16,500

24,400

16,900

25,200

16,700

26,200

17,400

28,200

17,200

29,600

17,500

77.0

22,100

16,500

22,800

16,400

24,100

16,800

25,000

16,600

26,000

17,300

27,900

17,200

29,400

17,400

82.0

21,900

16,400

22,500

16,200

23,800

16,700

24,700

16,500

25,700

17,200

27,600

17,000

29,100

17,300

86.0

21,700

16,300

22,200

16,100

23,600

16,600

24,400

16,400

25,400

17,100

27,400

16,900

28,900

17,200

91.0

21,400

16,100

21,900

16,000

23,300

16,500

24,100

16,300

25,100

17,000

27,100

16,800

28,600

17,100

95.0

21,200

16,000

21,700

15,900

23,100

16,300

24,000

16,200

24,900

16,900

26,800

16,700

28,300

17,100

100.0

21,000

15,900

21,400

15,700

22,800

16,200

23,600

16,000

24,600

16,700

26,500

16,600

28,000

17,000

104.0

20,800

15,800

21,200

15,600

22,500

16,100

23,400

15,900

24,400

16,600

26,300

16,500

27,800

16,900

110.0

20,500

15,700

20,800

15,400

22,200

15,900

23,000

15,800

24,000

16,500

26,000

16,400

27,500

16,700

68.0

25,500

18,600

26,300

18,500

27,900

19,000

28,800

18,700

29,900

19,500

32,100

19,300

33,700

19,500

73.0

25,200

18,400

26,000

18,300

27,500

18,800

28,500

18,600

29,600

19,300

31,800

19,100

33,400

19,400

77.0

25,000

18,300

25,700

18,200

27,300

18,700

28,200

18,500

29,300

19,200

31,500

19,000

33,200

19,300

82.0

24,700

18,200

25,400

18,000

26,900

18,500

27,800

18,300

29,000

19,100

31,200

18,900

32,800

19,200

86.0

24,400

18,000

25,100

17,900

26,600

18,400

27,600

18,200

28,700

18,900

30,900

18,800

32,600

19,100

91.0

24,200

17,900

24,800

17,700

26,300

18,200

27,200

18,000

28,400

18,800

30,600

18,600

32,200

19,000

95.0

23,900

17,800

24,500

17,600

26,000

18,100

27,000

17,900

28,100

18,700

30,300

18,500

32,000

18,900

100.0

23,700

17,700

24,200

17,400

25,700

18,000

26,600

17,800

27,800

18,500

29,900

18,400

31,600

18,800

104.0

23,400

17,500

23,900

17,300

25,400

17,800

26,400

17,700

27,500

18,400

29,700

18,300

31,400

18,700

110.0

23,100

17,400

23,500

17,100

25,000

17,700

26,000

17,500

27,100

18,300

29,300

18,100

31,000

18,500

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-29

NOMINAL
CAPACITY
TABLES

104.0
110.0

CT

27

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

28,400

20,500

29,300

20,400

31,000

20,900

32,100

20,600

33,300

21,500

35,800

21,200

37,600

21,500

73.0

28,100

20,300

28,900

20,200

30,700

20,700

31,700

20,500

32,900

21,300

35,400

21,100

37,200

21,400

77.0

27,800

20,200

28,600

20,000

30,400

20,600

31,400

20,300

32,700

21,200

35,100

21,000

36,900

21,300

82.0

27,500

20,000

28,300

19,900

30,000

20,400

31,000

20,200

32,300

21,000

34,700

20,800

36,600

21,100

86.0

27,200

19,900

28,000

19,700

29,700

20,300

30,700

20,000

32,000

20,900

34,400

20,700

36,300

21,000

91.0

26,900

19,700

27,600

19,500

29,300

20,100

30,300

19,900

31,600

20,700

34,000

20,500

35,900

20,900

95.0

26,700

19,600

27,300

19,400

29,000

20,000

30,000

19,700

31,300

20,600

33,700

20,400

35,600

20,800

100.0

26,400

19,500

26,900

19,200

28,600

19,800

29,700

19,600

30,900

20,400

33,400

20,300

35,300

20,600

104.0

26,100

19,300

26,600

19,100

28,300

19,600

29,400

19,400

30,600

20,300

33,100

20,200

35,000

20,500

110.0

25,700

19,100

26,200

18,900

27,900

19,400

28,900

19,300

30,200

20,100

32,600

20,000

34,500

20,400

68.0

34,200

25,400

35,300

25,200

37,400

25,900

38,600

25,600

40,100

26,700

43,100

26,400

45,300

26,800

73.0

33,800

25,200

34,800

25,000

36,900

25,700

38,200

25,400

39,700

26,500

42,600

26,200

44,800

26,600

77.0

33,500

25,000

34,500

24,800

36,600

25,600

37,800

25,300

39,300

26,300

42,300

26,000

44,500

26,500

82.0

33,100

24,800

34,000

24,600

36,100

25,300

37,400

25,100

38,900

26,100

41,800

25,900

44,100

26,300

86.0

32,800

24,700

33,700

24,500

35,700

25,200

37,000

24,900

38,500

26,000

41,500

25,700

43,700

26,200

91.0

32,400

24,500

33,200

24,200

35,300

25,000

36,500

24,700

38,000

25,800

41,000

25,500

43,300

26,000

95.0

32,100

24,300

32,900

24,100

34,900

24,800

36,000

24,600

37,700

25,600

40,700

25,400

42,900

25,900

100.0

31,800

24,200

32,400

23,800

34,500

24,600

35,700

24,400

37,300

25,400

40,200

25,200

42,500

25,700

104.0

31,400

24,000

32,100

23,700

34,100

24,400

35,400

24,200

36,900

25,300

39,900

25,100

42,100

25,600

110.0

31,000

23,800

31,500

23,400

33,600

24,200

34,800

24,000

36,300

25,100

39,300

24,900

41,600

25,400

68.0

45,500

32,600

46,900

32,400

49,700

33,200

51,400

32,800

53,400

34,100

57,300

33,700

60,200

34,200

73.0

45,000

32,300

46,300

32,100

49,100

32,900

50,800

32,500

52,800

33,800

56,700

33,500

59,700

33,900

77.0

44,500

32,100

45,800

31,800

48,600

32,700

50,300

32,300

52,300

33,600

56,200

33,300

59,200

33,700

82.0

44,100

31,800

45,300

31,500

48,000

32,400

49,700

32,000

51,700

33,300

55,700

33,000

58,600

33,500

86.0

43,600

31,600

44,800

31,300

47,500

32,200

49,200

31,800

51,200

33,100

55,200

32,800

58,100

33,300

91.0

43,200

31,300

44,200

31,000

47,000

31,900

48,600

31,500

50,600

32,800

54,600

32,600

57,500

33,100

95.0

42,700

31,100

43,700

30,800

46,500

31,700

48,000

31,300

50,200

32,600

54,100

32,400

57,100

32,900

100.0

42,200

30,900

43,100

30,500

45,800

31,400

47,500

31,000

49,600

32,400

53,400

32,100

56,500

32,700

104.0

41,800

30,600

42,700

30,200

45,400

31,100

47,100

30,800

49,100

32,100

53,000

31,900

56,000

32,500

110.0

41,200

30,400

42,000

29,900

44,600

30,800

46,300

30,500

48,300

31,800

52,300

31,600

55,300

32,300

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-30

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PMFY-P-NBMU-E


E
Model

Outdoor

size

air temp.

06

08

12

15

CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)


Entering air temp.
71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,800

5,200

6,000

5,200

6,400

5,400

6,600

5,300

6,800

5,600

7,300

5,500

7,700

5,700

73.0

5,700

5,200

5,900

5,200

6,300

5,300

6,500

5,300

6,700

5,600

7,200

5,500

7,600

5,600

77.0

5,700

5,200

5,900

5,100

6,200

5,300

6,400

5,300

6,700

5,500

7,200

5,500

7,600

5,600

82.0

5,600

5,100

5,800

5,100

6,100

5,300

6,300

5,300

6,600

5,500

7,100

5,400

7,500

5,600

86.0

5,600

5,100

5,700

5,100

6,100

5,300

6,300

5,200

6,500

5,500

7,000

5,400

7,400

5,600

91.0

5,500

5,100

5,600

5,000

6,000

5,200

6,200

5,200

6,500

5,400

7,000

5,400

7,300

5,600

95.0

5,500

5,100

5,600

5,000

5,900

5,200

6,000

5,200

6,400

5,400

6,900

5,400

7,300

5,500

100.0

5,400

5,000

5,500

5,000

5,900

5,200

6,000

5,100

6,300

5,400

6,800

5,300

7,200

5,500

104.0

5,300

5,000

5,400

5,000

5,800

5,200

6,000

5,100

6,300

5,400

6,800

5,300

7,200

5,500

110.0

5,300

5,000

5,400

4,900

5,700

5,100

5,900

5,100

6,200

5,300

6,700

5,300

7,100

5,500

68.0

7,400

6,300

7,700

6,300

8,100

6,500

8,400

6,400

8,700

6,700

9,400

6,600

9,800

6,800

73.0

7,300

6,300

7,600

6,200

8,000

6,400

8,300

6,400

8,600

6,700

9,300

6,600

9,700

6,700

77.0

7,300

6,200

7,500

6,200

7,900

6,400

8,200

6,300

8,500

6,600

9,200

6,600

9,700

6,700

82.0

7,200

6,200

7,400

6,100

7,800

6,400

8,100

6,300

8,400

6,600

9,100

6,500

9,600

6,700

86.0

7,100

6,200

7,300

6,100

7,800

6,300

8,000

6,300

8,400

6,600

9,000

6,500

9,500

6,700

91.0

7,000

6,100

7,200

6,100

7,700

6,300

8,000

6,200

8,300

6,500

8,900

6,500

9,400

6,600

95.0

7,000

6,100

7,100

6,000

7,600

6,300

8,000

6,200

8,200

6,500

8,800

6,400

9,300

6,600

100.0

6,900

6,100

7,000

6,000

7,500

6,200

7,800

6,200

8,100

6,500

8,700

6,400

9,200

6,600

104.0

6,800

6,000

7,000

6,000

7,400

6,200

7,700

6,100

8,000

6,400

8,600

6,400

9,100

6,600

110.0

6,700

6,000

6,800

5,900

7,300

6,100

7,600

6,100

7,900

6,400

8,500

6,300

9,000

6,500

68.0

11,300

8,200

11,600

8,200

12,300

8,400

12,800

8,300

13,300

8,600

14,200

8,500

15,000

8,700

73.0

11,200

8,200

11,500

8,100

12,200

8,300

12,600

8,200

13,100

8,600

14,100

8,500

14,800

8,600

77.0

11,100

8,100

11,400

8,000

12,100

8,300

12,500

8,200

13,000

8,500

14,000

8,400

14,700

8,600

82.0

10,900

8,000

11,200

8,000

11,900

8,200

12,300

8,100

12,800

8,400

13,800

8,400

14,500

8,500

86.0

10,800

8,000

11,100

7,900

11,800

8,100

12,200

8,100

12,700

8,400

13,700

8,300

14,400

8,500

91.0

10,700

7,900

11,000

7,800

11,700

8,100

12,100

8,000

12,600

8,300

13,500

8,300

14,300

8,400

95.0

10,600

7,900

10,900

7,800

11,500

8,000

12,000

7,900

12,500

8,300

13,400

8,200

14,200

8,400

100.0

10,500

7,800

10,700

7,700

11,400

7,900

11,800

7,900

12,300

8,200

13,300

8,100

14,000

8,300

104.0

10,400

7,800

10,600

7,700

11,300

7,900

11,700

7,800

12,200

8,200

13,200

8,100

13,900

8,300

110.0

10,200

7,700

10,400

7,600

11,100

7,800

11,500

7,700

12,000

8,100

13,000

8,000

13,700

8,200

68.0

14,200

10,100

14,600

10,000

15,500

10,300

16,000

10,100

16,700

10,500

17,900

10,400

18,800

10,500

73.0

14,000

10,000

14,500

9,900

15,300

10,200

15,900

10,000

16,500

10,400

17,700

10,300

18,600

10,500

77.0

13,900

9,900

14,300

9,800

15,200

10,100

15,700

10,000

16,300

10,400

17,500

10,300

18,500

10,400

82.0

13,800

9,800

14,100

9,700

15,000

10,000

15,500

9,900

16,100

10,300

17,400

10,200

18,300

10,300

86.0

13,600

9,800

14,000

9,700

14,800

9,900

15,400

9,800

16,000

10,200

17,200

10,100

18,100

10,300

91.0

13,500

9,700

13,800

9,600

14,700

9,800

15,200

9,700

15,800

10,100

17,000

10,000

18,000

10,200

95.0

13,300

9,600

13,600

9,500

14,500

9,800

15,000

9,600

15,700

10,100

16,900

10,000

17,800

10,100

100.0

13,200

9,500

13,500

9,400

14,300

9,700

14,800

9,600

15,500

10,000

16,700

9,900

17,600

10,100

104.0

13,000

9,500

13,300

9,300

14,200

9,600

14,700

9,500

15,300

9,900

16,500

9,800

17,500

10,000

110.0

12,900

9,400

13,100

9,200

13,900

9,500

14,500

9,400

15,100

9,800

16,300

9,700

17,300

9,900

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-31

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PLFY-P-NCMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

7,400

6,600

7,700

6,600

8,100

6,800

8,400

6,800

8,700

7,100

9,400

7,000

9,800

7,200

73.0

7,300

6,600

7,600

6,600

8,000

6,800

8,300

6,700

8,600

7,000

9,300

7,000

9,700

7,200

77.0

7,300

6,600

7,500

6,500

7,900

6,800

8,200

6,700

8,500

7,000

9,200

6,900

9,700

7,100

82.0

7,200

6,500

7,400

6,500

7,800

6,700

8,100

6,700

8,400

7,000

9,100

6,900

9,600

7,100

86.0

7,100

6,500

7,300

6,400

7,800

6,700

8,000

6,600

8,400

7,000

9,000

6,900

9,500

7,100

91.0

7,000

6,500

7,200

6,400

7,700

6,600

7,900

6,600

8,300

6,900

8,900

6,900

9,400

7,000

95.0

7,000

6,400

7,100

6,400

7,600

6,600

12,000

6,600

8,200

6,900

8,800

6,800

9,300

7,000

100.0

6,900

6,400

7,000

6,300

7,500

6,600

7,800

6,500

8,100

6,900

8,700

6,800

9,200

7,000

104.0

6,800

6,400

7,000

6,300

7,400

6,500

7,700

6,500

8,000

6,800

8,600

6,800

9,100

7,000

110.0

6,700

6,300

6,800

6,200

7,300

6,500

7,600

6,500

7,900

6,800

8,500

6,700

9,000

6,900

68.0

11,300

8,800

11,600

8,800

12,300

9,000

12,800

8,900

13,300

9,300

14,200

9,200

15,000

9,400

73.0

11,200

8,800

11,500

8,700

12,200

9,000

12,600

8,900

13,100

9,300

14,100

9,200

14,800

9,300

77.0

11,100

8,700

11,400

8,700

12,100

8,900

12,500

8,800

13,000

9,200

14,000

9,100

14,700

9,300

82.0

10,900

8,700

11,200

8,600

11,900

8,900

12,300

8,800

12,800

9,200

13,800

9,100

14,500

9,300

86.0

10,800

8,600

11,100

8,500

11,800

8,800

12,200

8,700

12,700

9,100

13,700

9,000

14,400

9,200

91.0

10,700

8,600

11,000

8,500

11,700

8,700

12,100

8,700

12,600

9,000

13,500

9,000

14,300

9,200

95.0

10,600

8,500

10,900

8,400

11,500

8,700

15,000

8,600

12,500

9,000

13,400

8,900

14,200

9,100

100.0

10,500

8,400

10,700

8,300

11,400

8,600

11,800

8,600

12,300

8,900

13,300

8,900

14,000

9,100

104.0

10,400

8,400

10,600

8,300

11,300

8,600

11,700

8,500

12,200

8,900

13,200

8,800

13,900

9,000

110.0

10,200

8,300

10,400

8,200

11,100

8,500

11,500

8,400

12,000

8,800

13,000

8,800

13,700

9,000

68.0

14,200

10,300

14,600

10,300

15,500

10,500

16,000

10,400

16,700

10,800

17,900

10,700

18,800

10,900

73.0

14,000

10,200

14,500

10,200

15,300

10,500

15,900

10,300

16,500

10,700

17,700

10,600

18,600

10,800

77.0

13,900

10,200

14,300

10,100

15,200

10,400

15,700

10,300

16,300

10,700

17,500

10,600

18,500

10,700

82.0

13,800

10,100

14,100

10,000

15,000

10,300

15,500

10,200

16,100

10,600

17,400

10,500

18,300

10,700

86.0

13,600

10,000

14,000

9,900

14,800

10,200

15,400

10,100

16,000

10,500

17,200

10,400

18,100

10,600

91.0

13,500

10,000

13,800

9,800

14,700

10,100

15,200

10,000

15,800

10,400

17,000

10,400

18,000

10,500

95.0

13,300

9,900

13,600

9,800

14,500

10,100

18,000

10,000

15,700

10,400

16,900

10,300

17,800

10,500

100.0

13,200

9,800

13,500

9,700

14,300

10,000

14,800

9,900

15,500

10,300

16,700

10,200

17,600

10,400

104.0

13,000

9,700

13,300

9,600

14,200

9,900

14,700

9,800

15,300

10,200

16,500

10,200

17,500

10,400

110.0

12,900

9,700

13,100

9,500

13,900

9,800

14,500

9,700

15,100

10,100

16,300

10,100

17,300

10,300

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-32

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PLFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

11,300

9,700

11,600

9,600

12,300

9,900

12,800

9,800

13,300

10,300

14,200

10,200

15,000

10,400

73.0

11,200

9,600

11,500

9,500

12,200

9,900

12,600

9,800

13,100

10,200

14,100

10,100

14,800

10,400

77.0

11,100

9,500

11,400

9,500

12,100

9,800

12,500

9,700

13,000

10,200

14,000

10,100

14,700

10,300

82.0

10,900

9,500

11,200

9,400

11,900

9,800

12,300

9,700

12,800

10,100

13,800

10,000

14,500

10,300

86.0

10,800

9,400

11,100

9,400

11,800

9,700

12,200

9,600

12,700

10,100

13,700

10,000

14,400

10,200

91.0

10,700

9,400

11,000

9,300

11,700

9,600

12,100

9,600

12,600

10,000

13,500

9,900

14,300

10,200

95.0

10,600

9,300

10,900

9,300

11,500

9,600

12,000

9,500

12,500

10,000

13,400

9,900

14,200

10,100

100.0

10,500

9,300

10,700

9,200

11,400

9,500

11,800

9,500

12,300

9,900

13,300

9,800

14,000

10,100

104.0

10,400

9,200

10,600

9,100

11,300

9,500

11,700

9,400

12,200

9,900

13,200

9,800

13,900

10,100

110.0

10,200

9,200

10,400

9,100

11,100

9,400

11,500

9,400

12,000

9,800

13,000

9,700

13,700

10,000

68.0

14,200

11,800

14,600

11,700

15,500

12,100

16,000

12,000

16,700

12,500

17,900

12,400

18,800

12,600

73.0

14,000

11,700

14,500

11,600

15,300

12,000

15,900

11,900

16,500

12,400

17,700

12,300

18,600

12,600

77.0

13,900

11,600

14,300

11,600

15,200

11,900

15,700

11,800

16,300

12,400

17,500

12,200

18,500

12,500

82.0

13,800

11,600

14,100

11,500

15,000

11,900

15,500

11,800

16,100

12,300

17,400

12,200

18,300

12,500

86.0

13,600

11,500

14,000

11,400

14,800

11,800

15,400

11,700

16,000

12,200

17,200

12,100

18,100

12,400

91.0

13,500

11,400

13,800

11,300

14,700

11,700

15,200

11,600

15,800

12,200

17,000

12,000

18,000

12,300

95.0

13,300

11,400

13,600

11,300

14,500

11,700

15,000

11,600

15,700

12,100

16,900

12,000

17,800

12,300

100.0

13,200

11,300

13,500

11,200

14,300

11,600

14,800

11,500

15,500

12,000

16,700

11,900

17,600

12,200

104.0

13,000

11,200

13,300

11,100

14,200

11,500

14,700

11,400

15,300

12,000

16,500

11,900

17,500

12,200

110.0

12,900

11,200

13,100

11,000

13,900

11,400

14,500

11,300

15,100

11,900

16,300

11,800

17,300

12,100

68.0

17,100

14,100

17,600

14,000

18,700

14,500

19,300

14,300

20,100

14,900

21,600

14,800

22,600

15,100

73.0

16,900

14,000

17,400

13,900

18,500

14,400

19,100

14,200

19,800

14,800

21,300

14,700

22,400

15,000

77.0

16,700

13,900

17,200

13,800

18,300

14,300

18,900

14,200

19,700

14,800

21,100

14,600

22,200

15,000

82.0

16,600

13,800

17,000

13,700

18,000

14,200

18,700

14,100

19,400

14,700

20,900

14,500

22,000

14,900

86.0

16,400

13,800

16,800

13,600

17,900

14,100

18,500

14,000

19,300

14,600

20,700

14,500

21,800

14,800

91.0

16,200

13,700

16,600

13,500

17,600

14,000

18,300

13,900

19,000

14,500

20,500

14,400

21,600

14,800

95.0

16,100

13,600

16,400

13,500

17,500

13,900

18,000

13,800

18,900

14,500

20,300

14,300

21,400

14,700

100.0

15,900

13,500

16,200

13,400

17,200

13,800

17,900

13,700

18,600

14,400

20,100

14,200

21,200

14,600

104.0

15,700

13,400

16,000

13,300

17,100

13,800

17,700

13,700

18,400

14,300

19,900

14,200

21,100

14,600

110.0

15,500

13,300

15,800

13,200

16,800

13,600

17,400

13,600

18,200

14,200

19,700

14,100

20,800

14,500

68.0

22,600

17,300

23,300

17,200

24,700

17,700

25,500

17,500

26,500

18,200

28,500

18,000

29,900

18,300

73.0

22,300

17,200

23,000

17,000

24,400

17,600

25,200

17,400

26,200

18,100

28,200

17,900

29,600

18,200

77.0

22,100

17,100

22,800

16,900

24,100

17,400

25,000

17,300

26,000

18,000

27,900

17,800

29,400

18,100

82.0

21,900

16,900

22,500

16,800

23,800

17,300

24,700

17,100

25,700

17,900

27,600

17,700

29,100

18,000

86.0

21,700

16,800

22,200

16,700

23,600

17,200

24,400

17,000

25,400

17,800

27,400

17,600

28,900

18,000

91.0

21,400

16,700

21,900

16,500

23,300

17,100

24,100

16,900

25,100

17,600

27,100

17,500

28,600

17,900

95.0

21,200

16,600

21,700

16,400

23,100

17,000

24,000

16,800

24,900

17,600

26,800

17,400

28,300

17,800

100.0

21,000

16,500

21,400

16,300

22,800

16,800

23,600

16,700

24,600

17,400

26,500

17,300

28,000

17,700

104.0

20,800

16,400

21,200

16,200

22,500

16,700

23,400

16,600

24,400

17,300

26,300

17,200

27,800

17,600

110.0

20,500

16,300

20,800

16,000

22,200

16,600

23,000

16,400

24,000

17,200

26,000

17,100

27,500

17,500

68.0

28,400

20,700

29,300

20,600

31,000

21,200

32,100

20,900

33,300

21,700

35,800

21,500

37,600

21,800

73.0

28,100

20,600

28,900

20,400

30,700

21,000

31,700

20,700

32,900

21,500

35,400

21,300

37,200

21,700

77.0

27,800

20,400

28,600

20,300

30,400

20,800

31,400

20,600

32,700

21,400

35,100

21,200

36,900

21,600

82.0

27,500

20,300

28,300

20,100

30,000

20,700

31,000

20,400

32,300

21,300

34,700

21,100

36,600

21,400

86.0

27,200

20,100

28,000

19,900

29,700

20,500

30,700

20,300

32,000

21,100

34,400

20,900

36,300

21,300

91.0

26,900

20,000

27,600

19,800

29,300

20,300

30,300

20,100

31,600

21,000

34,000

20,800

35,900

21,200

95.0

26,700

19,800

27,300

19,600

29,000

20,200

30,000

20,000

31,300

20,800

33,700

20,700

35,600

21,100

100.0

26,400

19,700

26,900

19,400

28,600

20,000

29,700

19,800

30,900

20,700

33,400

20,500

35,300

20,900

104.0

26,100

19,500

26,600

19,300

28,300

19,900

29,400

19,700

30,600

20,600

33,100

20,400

35,000

20,800

110.0

25,700

19,400

26,200

19,100

27,900

19,700

28,900

19,500

30,200

20,400

32,600

20,200

34,500

20,700

68.0

34,200

26,400

35,300

26,300

37,400

27,100

38,600

26,800

40,100

27,900

43,100

27,600

45,300

28,100

73.0

33,800

26,300

34,800

26,100

36,900

26,900

38,200

26,600

39,700

27,700

42,600

27,400

44,800

27,900

77.0

33,500

26,100

34,500

25,900

36,600

26,700

37,800

26,400

39,300

27,600

42,300

27,300

44,500

27,800

82.0

33,100

25,900

34,000

25,700

36,100

26,500

37,400

26,200

38,900

27,400

41,800

27,100

44,100

27,700

86.0

32,800

25,800

33,700

25,500

35,700

26,300

37,000

26,100

38,500

27,200

41,500

27,000

43,700

27,500

91.0

32,400

25,600

33,200

25,300

35,300

26,200

36,500

25,900

38,000

27,000

41,000

26,800

43,300

27,400

95.0

32,100

25,400

32,900

25,200

34,900

26,000

36,000

25,700

37,700

26,900

40,700

26,700

42,900

27,200

100.0

31,800

25,300

32,400

24,900

34,500

25,800

35,700

25,600

37,300

26,700

40,200

26,500

42,500

27,100

104.0

31,400

25,100

32,100

24,800

34,100

25,600

35,400

25,400

36,900

26,600

39,900

26,400

42,100

27,000

110.0

31,000

24,900

31,500

24,500

33,600

25,400

34,800

25,200

36,300

26,300

39,300

26,200

41,600

26,800

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-33

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PCFY-P-NGMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,200

10,800

14,600

10,700

15,500

11,000

16,000

10,900

16,700

11,300

17,900

11,200

18,800

11,400

73.0

14,000

10,700

14,500

10,600

15,300

10,900

15,900

10,800

16,500

11,300

17,700

11,100

18,600

11,300

77.0

13,900

10,600

14,300

10,500

15,200

10,900

15,700

10,800

16,300

11,200

17,500

11,100

18,500

11,300

82.0

13,800

10,600

14,100

10,500

15,000

10,800

15,500

10,700

16,100

11,100

17,400

11,000

18,300

11,200

86.0

13,600

10,500

14,000

10,400

14,800

10,700

15,400

10,600

16,000

11,100

17,200

11,000

18,100

11,200

91.0

13,500

10,400

13,800

10,300

14,700

10,600

15,200

10,500

15,800

11,000

17,000

10,900

18,000

11,100

95.0

13,300

10,300

13,600

10,200

14,500

10,600

15,000

10,500

15,700

10,900

16,900

10,800

17,800

11,100

100.0

13,200

10,300

13,500

10,100

14,300

10,500

14,800

10,400

15,500

10,800

16,700

10,800

17,600

11,000

104.0

13,000

10,200

13,300

10,100

14,200

10,400

14,700

10,300

15,300

10,800

16,500

10,700

17,500

10,900

110.0

12,900

10,100

13,100

10,000

13,900

10,300

14,500

10,200

15,100

10,700

16,300

10,600

17,300

10,900

68.0

22,600

16,700

23,300

16,600

24,700

17,100

25,500

16,900

26,500

17,600

28,500

17,400

29,900

17,600

73.0

22,300

16,600

23,000

16,500

24,400

16,900

25,200

16,700

26,200

17,400

28,200

17,200

29,600

17,500

77.0

22,100

16,500

22,800

16,400

24,100

16,800

25,000

16,600

26,000

17,300

27,900

17,200

29,400

17,400

82.0

21,900

16,400

22,500

16,200

23,800

16,700

24,700

16,500

25,700

17,200

27,600

17,000

29,100

17,300

86.0

21,700

16,300

22,200

16,100

23,600

16,600

24,400

16,400

25,400

17,100

27,400

16,900

28,900

17,200

91.0

21,400

16,100

21,900

16,000

23,300

16,500

24,100

16,300

25,100

17,000

27,100

16,800

28,600

17,100

95.0

21,200

16,000

21,700

15,900

23,100

16,300

24,000

16,200

24,900

16,900

26,800

16,700

28,300

17,100

100.0

21,000

15,900

21,400

15,700

22,800

16,200

23,600

16,000

24,600

16,700

26,500

16,600

28,000

17,000

104.0

20,800

15,800

21,200

15,600

22,500

16,100

23,400

15,900

24,400

16,600

26,300

16,500

27,800

16,900

110.0

20,500

15,700

20,800

15,400

22,200

15,900

23,000

15,800

24,000

16,500

26,000

16,400

27,500

16,700

68.0

28,400

20,500

29,300

20,400

31,000

20,900

32,100

20,600

33,300

21,500

35,800

21,200

37,600

21,500

73.0

28,100

20,300

28,900

20,200

30,700

20,700

31,700

20,500

32,900

21,300

35,400

21,100

37,200

21,400

77.0

27,800

20,200

28,600

20,000

30,400

20,600

31,400

20,300

32,700

21,200

35,100

21,000

36,900

21,300

82.0

27,500

20,000

28,300

19,900

30,000

20,400

31,000

20,200

32,300

21,000

34,700

20,800

36,600

21,100

86.0

27,200

19,900

28,000

19,700

29,700

20,300

30,700

20,000

32,000

20,900

34,400

20,700

36,300

21,000

91.0

26,900

19,700

27,600

19,500

29,300

20,100

30,300

19,900

31,600

20,700

34,000

20,500

35,900

20,900

95.0

26,700

19,600

27,300

19,400

29,000

20,000

30,000

19,700

31,300

20,600

33,700

20,400

35,600

20,800

100.0

26,400

19,500

26,900

19,200

28,600

19,800

29,700

19,600

30,900

20,400

33,400

20,300

35,300

20,600

104.0

26,100

19,300

26,600

19,100

28,300

19,600

29,400

19,400

30,600

20,300

33,100

20,200

35,000

20,500

110.0

25,700

19,100

26,200

18,900

27,900

19,400

28,900

19,300

30,200

20,100

32,600

20,000

34,500

20,400

68.0

34,200

25,400

35,300

25,200

37,400

25,900

38,600

25,600

40,100

26,700

43,100

26,400

45,300

26,800

73.0

33,800

25,200

34,800

25,000

36,900

25,700

38,200

25,400

39,700

26,500

42,600

26,200

44,800

26,600

77.0

33,500

25,000

34,500

24,800

36,600

25,600

37,800

25,300

39,300

26,300

42,300

26,000

44,500

26,500

82.0

33,100

24,800

34,000

24,600

36,100

25,300

37,400

25,100

38,900

26,100

41,800

25,900

44,100

26,300

86.0

32,800

24,700

33,700

24,500

35,700

25,200

37,000

24,900

38,500

26,000

41,500

25,700

43,700

26,200

91.0

32,400

24,500

33,200

24,200

35,300

25,000

36,500

24,700

38,000

25,800

41,000

25,500

43,300

26,000

95.0

32,100

24,300

32,900

24,100

34,900

24,800

36,000

24,600

37,700

25,600

40,700

25,400

42,900

25,900

100.0

31,800

24,200

32,400

23,800

34,500

24,600

35,700

24,400

37,300

25,400

40,200

25,200

42,500

25,700

104.0

31,400

24,000

32,100

23,700

34,100

24,400

35,400

24,200

36,900

25,300

39,900

25,100

42,100

25,600

110.0

31,000

23,800

31,500

23,400

33,600

24,200

34,800

24,000

36,300

25,100

39,300

24,900

41,600

25,400

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-34

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,800

4,500

6,000

4,400

6,400

4,600

6,600

4,500

6,800

4,700

7,300

4,700

7,700

4,700

73.0

5,700

4,400

5,900

4,400

6,300

4,500

6,500

4,500

6,700

4,700

7,200

4,600

7,600

4,700

77.0

5,700

4,400

5,900

4,400

6,200

4,500

6,400

4,500

6,700

4,700

7,200

4,600

7,600

4,700

82.0

5,600

4,400

5,800

4,300

6,100

4,500

6,300

4,400

6,600

4,600

7,100

4,600

7,500

4,700

86.0

5,600

4,400

5,700

4,300

6,100

4,500

6,300

4,400

6,500

4,600

7,000

4,600

7,400

4,600

91.0

5,500

4,300

5,600

4,300

6,000

4,400

6,200

4,400

6,500

4,600

7,000

4,500

7,300

4,600

95.0

5,500

4,300

5,600

4,300

5,900

4,400

6,000

4,300

6,400

4,500

6,900

4,500

7,300

4,600

100.0

5,400

4,300

5,500

4,200

5,900

4,400

6,000

4,300

6,300

4,500

6,800

4,500

7,200

4,600

104.0

5,300

4,200

5,400

4,200

5,800

4,300

6,000

4,300

6,300

4,500

6,800

4,500

7,200

4,600

110.0

5,300

4,200

5,400

4,100

5,700

4,300

5,900

4,300

6,200

4,400

6,700

4,400

7,100

4,500

68.0

7,400

5,600

7,700

5,600

8,100

5,700

8,400

5,700

8,700

5,900

9,400

5,800

9,800

5,900

73.0

7,300

5,600

7,600

5,500

8,000

5,700

8,300

5,600

8,600

5,900

9,300

5,800

9,700

5,900

77.0

7,300

5,500

7,500

5,500

7,900

5,700

8,200

5,600

8,500

5,800

9,200

5,800

9,700

5,900

82.0

7,200

5,500

7,400

5,500

7,800

5,600

8,100

5,600

8,400

5,800

9,100

5,700

9,600

5,800

86.0

7,100

5,500

7,300

5,400

7,800

5,600

8,000

5,500

8,400

5,800

9,000

5,700

9,500

5,800

91.0

7,000

5,400

7,200

5,400

7,700

5,500

8,000

5,500

8,300

5,700

8,900

5,700

9,400

5,800

95.0

7,000

5,400

7,100

5,300

7,600

5,500

8,000

5,400

8,200

5,700

8,800

5,600

9,300

5,800

100.0

6,900

5,400

7,000

5,300

7,500

5,500

7,800

5,400

8,100

5,600

8,700

5,600

9,200

5,700

104.0

6,800

5,300

7,000

5,300

7,400

5,400

7,700

5,400

8,000

5,600

8,600

5,600

9,100

5,700

110.0

6,700

5,300

6,800

5,200

7,300

5,400

7,600

5,300

7,900

5,600

8,500

5,500

9,000

5,700

68.0

11,300

9,000

11,600

9,000

12,300

9,300

12,800

9,200

13,300

9,500

14,200

9,400

15,000

9,600

73.0

11,200

9,000

11,500

8,900

12,200

9,200

12,600

9,100

13,100

9,500

14,100

9,400

14,800

9,600

77.0

11,100

8,900

11,400

8,800

12,100

9,100

12,500

9,000

13,000

9,400

14,000

9,300

14,700

9,500

82.0

10,900

8,900

11,200

8,800

11,900

9,100

12,300

9,000

12,800

9,400

13,800

9,300

14,500

9,500

86.0

10,800

8,800

11,100

8,700

11,800

9,000

12,200

8,900

12,700

9,300

13,700

9,200

14,400

9,500

91.0

10,700

8,700

11,000

8,700

11,700

9,000

12,100

8,900

12,600

9,300

13,500

9,200

14,300

9,400

95.0

10,600

8,700

10,900

8,600

11,500

8,900

12,000

8,800

12,500

9,200

13,400

9,100

14,200

9,400

100.0

10,500

8,600

10,700

8,500

11,400

8,800

11,800

8,800

12,300

9,200

13,300

9,100

14,000

9,300

104.0

10,400

8,600

10,600

8,500

11,300

8,800

11,700

8,700

12,200

9,100

13,200

9,100

13,900

9,300

110.0

10,200

8,500

10,400

8,400

11,100

8,700

11,500

8,600

12,000

9,000

13,000

9,000

13,700

9,200

68.0

14,200

10,800

14,600

10,800

15,500

11,100

16,000

11,000

16,700

11,400

17,900

11,300

18,800

11,500

73.0

14,000

10,800

14,500

10,700

15,300

11,000

15,900

10,900

16,500

11,400

17,700

11,200

18,600

11,400

77.0

13,900

10,700

14,300

10,600

15,200

11,000

15,700

10,800

16,300

11,300

17,500

11,200

18,500

11,400

82.0

13,800

10,600

14,100

10,500

15,000

10,900

15,500

10,800

16,100

11,200

17,400

11,100

18,300

11,300

86.0

13,600

10,600

14,000

10,500

14,800

10,800

15,400

10,700

16,000

11,200

17,200

11,100

18,100

11,300

91.0

13,500

10,500

13,800

10,400

14,700

10,700

15,200

10,600

15,800

11,100

17,000

11,000

18,000

11,200

95.0

13,300

10,400

13,600

10,300

14,500

10,700

15,000

10,500

15,700

11,000

16,900

10,900

17,800

11,200

100.0

13,200

10,400

13,500

10,200

14,300

10,600

14,800

10,500

15,500

10,900

16,700

10,800

17,600

11,100

104.0

13,000

10,300

13,300

10,200

14,200

10,500

14,700

10,400

15,300

10,900

16,500

10,800

17,500

11,000

110.0

12,900

10,200

13,100

10,100

13,900

10,400

14,500

10,300

15,100

10,800

16,300

10,700

17,300

11,000

68.0

17,100

13,800

17,600

13,700

18,700

14,100

19,300

14,000

20,100

14,600

21,600

14,400

22,600

14,700

73.0

16,900

13,700

17,400

13,600

18,500

14,000

19,100

13,900

19,800

14,500

21,300

14,300

22,400

14,600

77.0

16,700

13,600

17,200

13,500

18,300

14,000

18,900

13,800

19,700

14,400

21,100

14,300

22,200

14,600

82.0

16,600

13,500

17,000

13,400

18,000

13,900

18,700

13,700

19,400

14,300

20,900

14,200

22,000

14,500

86.0

16,400

13,400

16,800

13,300

17,900

13,800

18,500

13,700

19,300

14,300

20,700

14,100

21,800

14,500

91.0

16,200

13,400

16,600

13,200

17,600

13,700

18,300

13,600

19,000

14,200

20,500

14,000

21,600

14,400

95.0

16,100

13,300

16,400

13,100

17,500

13,600

18,000

13,500

18,900

14,100

20,300

14,000

21,400

14,300

100.0

15,900

13,200

16,200

13,000

17,200

13,500

17,900

13,400

18,600

14,000

20,100

13,900

21,200

14,200

104.0

15,700

13,100

16,000

13,000

17,100

13,400

17,700

13,300

18,400

13,900

19,900

13,800

21,100

14,200

110.0

15,500

13,000

15,800

12,800

16,800

13,300

17,400

13,200

18,200

13,800

19,700

13,700

20,800

14,100

68.0

22,600

17,100

23,300

17,000

24,700

17,500

25,500

17,300

26,500

18,000

28,500

17,800

29,900

18,100

73.0

22,300

17,000

23,000

16,900

24,400

17,400

25,200

17,200

26,200

17,900

28,200

17,700

29,600

18,000

77.0

22,100

16,900

22,800

16,700

24,100

17,200

25,000

17,100

26,000

17,800

27,900

17,600

29,400

17,900

82.0

21,900

16,700

22,500

16,600

23,800

17,100

24,700

16,900

25,700

17,600

27,600

17,500

29,100

17,800

86.0

21,700

16,600

22,200

16,500

23,600

17,000

24,400

16,800

25,400

17,500

27,400

17,400

28,900

17,700

91.0

21,400

16,500

21,900

16,400

23,300

16,900

24,100

16,700

25,100

17,400

27,100

17,300

28,600

17,600

95.0

21,200

16,400

21,700

16,200

23,100

16,800

24,000

16,600

24,900

17,300

26,800

17,200

28,300

17,500

100.0

21,000

16,300

21,400

16,100

22,800

16,600

23,600

16,500

24,600

17,200

26,500

17,100

28,000

17,400

104.0

20,800

16,200

21,200

16,000

22,500

16,500

23,400

16,400

24,400

17,100

26,300

17,000

27,800

17,400

110.0

20,500

16,100

20,800

15,800

22,200

16,400

23,000

16,200

24,000

17,000

26,000

16,800

27,500

17,200

68.0

28,400

23,000

29,300

22,800

31,000

23,600

32,100

23,300

33,300

24,300

35,800

24,100

37,600

24,600

73.0

28,100

22,800

28,900

22,700

30,700

23,400

31,700

23,200

32,900

24,200

35,400

23,900

37,200

24,500

77.0

27,800

22,700

28,600

22,500

30,400

23,300

31,400

23,100

32,700

24,100

35,100

23,800

36,900

24,400

82.0

27,500

22,600

28,300

22,400

30,000

23,100

31,000

22,900

32,300

23,900

34,700

23,700

36,600

24,200

86.0

27,200

22,400

28,000

22,200

29,700

23,000

30,700

22,800

32,000

23,800

34,400

23,600

36,300

24,100

91.0

26,900

22,300

27,600

22,100

29,300

22,800

30,300

22,600

31,600

23,700

34,000

23,400

35,900

24,000

95.0

26,700

22,200

27,300

21,900

29,000

22,700

30,000

22,500

31,300

23,500

33,700

23,300

35,600

23,900

100.0

26,400

22,000

26,900

21,800

28,600

22,500

29,700

22,400

30,900

23,400

33,400

23,200

35,300

23,800

104.0

26,100

21,900

26,600

21,600

28,300

22,400

29,400

22,300

30,600

23,300

33,100

23,100

35,000

23,700

110.0

25,700

21,700

26,200

21,400

27,900

22,200

28,900

22,100

30,200

23,100

32,600

22,900

34,500

23,500

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-35

NOMINAL
CAPACITY
TABLES

30

Indoor air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,800

4,400

6,000

4,400

6,400

4,500

6,600

4,400

6,800

4,600

7,300

4,600

7,700

4,600

73.0

5,700

4,400

5,900

4,300

6,300

4,500

6,500

4,400

6,700

4,600

7,200

4,500

7,600

4,600

77.0

5,700

4,300

5,900

4,300

6,200

4,400

6,400

4,400

6,700

4,600

7,200

4,500

7,600

4,600

82.0

5,600

4,300

5,800

4,300

6,100

4,400

6,300

4,300

6,600

4,500

7,100

4,500

7,500

4,600

86.0

5,600

4,300

5,700

4,200

6,100

4,400

6,300

4,300

6,500

4,500

7,000

4,500

7,400

4,500

91.0

5,500

4,200

5,600

4,200

6,000

4,300

6,200

4,300

6,500

4,500

7,000

4,400

7,300

4,500

95.0

5,500

4,200

5,600

4,200

5,900

4,300

6,000

4,300

6,400

4,400

6,900

4,400

7,300

4,500

100.0

5,400

4,200

5,500

4,100

5,900

4,300

6,000

4,200

6,300

4,400

6,800

4,400

7,200

4,500

104.0

5,300

4,200

5,400

4,100

5,800

4,200

6,000

4,200

6,300

4,400

6,800

4,400

7,200

4,500

110.0

5,300

4,100

5,400

4,100

5,700

4,200

5,900

4,200

6,200

4,300

6,700

4,300

7,100

4,400

68.0

7,400

5,700

7,700

5,700

8,100

5,800

8,400

5,800

8,700

6,000

9,400

6,000

9,800

6,100

73.0

7,300

5,700

7,600

5,600

8,000

5,800

8,300

5,700

8,600

6,000

9,300

5,900

9,700

6,000

77.0

7,300

5,600

7,500

5,600

7,900

5,800

8,200

5,700

8,500

5,900

9,200

5,900

9,700

6,000

82.0

7,200

5,600

7,400

5,500

7,800

5,700

8,100

5,700

8,400

5,900

9,100

5,800

9,600

6,000

86.0

7,100

5,600

7,300

5,500

7,800

5,700

8,000

5,600

8,400

5,900

9,000

5,800

9,500

5,900

91.0

7,000

5,500

7,200

5,500

7,700

5,600

8,000

5,600

8,300

5,800

8,900

5,800

9,400

5,900

95.0

7,000

5,500

7,100

5,400

7,600

5,600

8,000

5,600

8,200

5,800

8,800

5,800

9,300

5,900

100.0

6,900

5,500

7,000

5,400

7,500

5,600

7,800

5,500

8,100

5,800

8,700

5,700

9,200

5,800

104.0

6,800

5,400

7,000

5,400

7,400

5,500

7,700

5,500

8,000

5,700

8,600

5,700

9,100

5,800

110.0

6,700

5,400

6,800

5,300

7,300

5,500

7,600

5,400

7,900

5,700

8,500

5,600

9,000

5,800

68.0

11,300

7,900

11,600

7,800

12,300

8,000

12,800

7,900

13,300

8,200

14,200

8,100

15,000

8,200

73.0

11,200

7,800

11,500

7,800

12,200

8,000

12,600

7,900

13,100

8,200

14,100

8,100

14,800

8,200

77.0

11,100

7,800

11,400

7,700

12,100

7,900

12,500

7,800

13,000

8,100

14,000

8,000

14,700

8,100

82.0

10,900

7,700

11,200

7,600

11,900

7,800

12,300

7,700

12,800

8,000

13,800

8,000

14,500

8,100

86.0

10,800

7,600

11,100

7,600

11,800

7,800

12,200

7,700

12,700

8,000

13,700

7,900

14,400

8,000

91.0

10,700

7,600

11,000

7,500

11,700

7,700

12,100

7,600

12,600

7,900

13,500

7,800

14,300

8,000

95.0

10,600

7,500

10,900

7,400

11,500

7,600

12,000

7,500

12,500

7,900

13,400

7,800

14,200

7,900

100.0

10,500

7,500

10,700

7,300

11,400

7,600

11,800

7,500

12,300

7,800

13,300

7,700

14,000

7,900

104.0

10,400

7,400

10,600

7,300

11,300

7,500

11,700

7,400

12,200

7,700

13,200

7,700

13,900

7,800

110.0

10,200

7,300

10,400

7,200

11,100

7,400

11,500

7,300

12,000

7,600

13,000

7,600

13,700

7,700

68.0

14,200

10,000

14,600

10,000

15,500

10,200

16,000

10,100

16,700

10,500

17,900

10,400

18,800

10,500

73.0

14,000

10,000

14,500

9,900

15,300

10,100

15,900

10,000

16,500

10,400

17,700

10,300

18,600

10,400

77.0

13,900

9,900

14,300

9,800

15,200

10,100

15,700

9,900

16,300

10,300

17,500

10,200

18,500

10,400

82.0

13,800

9,800

14,100

9,700

15,000

10,000

15,500

9,900

16,100

10,300

17,400

10,200

18,300

10,300

86.0

13,600

9,700

14,000

9,600

14,800

9,900

15,400

9,800

16,000

10,200

17,200

10,100

18,100

10,300

91.0

13,500

9,700

13,800

9,600

14,700

9,800

15,200

9,700

15,800

10,100

17,000

10,000

18,000

10,200

95.0

13,300

9,600

13,600

9,500

14,500

9,700

15,000

9,600

15,700

10,000

16,900

10,000

17,800

10,100

100.0

13,200

9,500

13,500

9,400

14,300

9,700

14,800

9,500

15,500

9,900

16,700

9,900

17,600

10,100

104.0

13,000

9,400

13,300

9,300

14,200

9,600

14,700

9,500

15,300

9,900

16,500

9,800

17,500

10,000

110.0

12,900

9,300

13,100

9,200

13,900

9,500

14,500

9,400

15,100

9,800

16,300

9,700

17,300

9,900

68.0

17,100

12,300

17,600

12,300

18,700

12,600

19,300

12,400

20,100

12,900

21,600

12,800

22,600

12,900

73.0

16,900

12,200

17,400

12,100

18,500

12,500

19,100

12,300

19,800

12,800

21,300

12,700

22,400

12,900

77.0

16,700

12,100

17,200

12,100

18,300

12,400

18,900

12,200

19,700

12,700

21,100

12,600

22,200

12,800

82.0

16,600

12,000

17,000

11,900

18,000

12,300

18,700

12,100

19,400

12,600

20,900

12,500

22,000

12,700

86.0

16,400

12,000

16,800

11,900

17,900

12,200

18,500

12,000

19,300

12,500

20,700

12,400

21,800

12,600

91.0

16,200

11,900

16,600

11,700

17,600

12,100

18,300

11,900

19,000

12,400

20,500

12,300

21,600

12,600

95.0

16,100

11,800

16,400

11,700

17,500

12,000

18,000

11,900

18,900

12,400

20,300

12,300

21,400

12,500

100.0

15,900

11,700

16,200

11,500

17,200

11,900

17,900

11,800

18,600

12,300

20,100

12,200

21,200

12,400

104.0

15,700

11,600

16,000

11,500

17,100

11,800

17,700

11,700

18,400

12,200

19,900

12,100

21,100

12,300

110.0

15,500

11,500

15,800

11,300

16,800

11,700

17,400

11,600

18,200

12,100

19,700

12,000

20,800

12,200

68.0

22,600

15,800

23,300

15,700

24,700

16,100

25,500

15,900

26,500

16,500

28,500

16,300

29,900

16,500

73.0

22,300

15,700

23,000

15,600

24,400

16,000

25,200

15,700

26,200

16,400

28,200

16,200

29,600

16,400

77.0

22,100

15,600

22,800

15,400

24,100

15,800

25,000

15,600

26,000

16,300

27,900

16,100

29,400

16,300

82.0

21,900

15,400

22,500

15,300

23,800

15,700

24,700

15,500

25,700

16,100

27,600

16,000

29,100

16,200

86.0

21,700

15,300

22,200

15,200

23,600

15,600

24,400

15,400

25,400

16,000

27,400

15,900

28,900

16,100

91.0

21,400

15,200

21,900

15,000

23,300

15,400

24,100

15,200

25,100

15,900

27,100

15,700

28,600

16,000

95.0

21,200

15,100

21,700

14,900

23,100

15,300

24,000

15,100

24,900

15,800

26,800

15,600

28,300

15,900

100.0

21,000

14,900

21,400

14,700

22,800

15,200

23,600

15,000

24,600

15,600

26,500

15,500

28,000

15,800

104.0

20,800

14,800

21,200

14,600

22,500

15,100

23,400

14,900

24,400

15,500

26,300

15,400

27,800

15,700

110.0

20,500

14,700

20,800

14,500

22,200

14,900

23,000

14,700

24,000

15,400

26,000

15,300

27,500

15,500

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-36

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-3-2. Heating CapacityPUHY-P168~240, PURY-P144~240TSHMU/YSHMU with All Indoor Units


SHC : Sensible Heat Capacity(BTU/h)
Model
size

06

08

12

15

18

24

Entering air temp.

SHC : Sensible Heat Capacity(BTU/h)


Model
size

Outdoor

Entering air temp.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

81degF D.B.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

degF W.B.

SHC

SHC

SHC

SHC

degF W.B.

SHC

SHC

SHC

SHC

5.0

4,200

4,100

4,100

4,000

5.0

21,200

20,700

20,300

20,000

14.0

5,000

4,800

4,700

4,700

14.0

24,800

24,000

23,600

23,300

23.0

5,700

5,500

5,400

5,000

23.0

28,500

27,300

26,900

25,200

32.0

6,400

6,100

5,600

5,000

32.0

32,100

30,500

28,200

25,200

37.0

6,900

6,500

5,600

5,000

37.0

34,300

32,500

28,200

25,200

43.0

7,300

6,700

5,600

5,000

43.0

36,500

34,000

28,200

25,200

46.0

7,600

6,700

5,600

5,000

46.0

37,900

34,000

28,200

25,200

50.0

7,900

6,700

5,600

5,000

50.0

39,400

34,000

28,200

25,200

55.0

8,200

6,700

5,600

5,000

55.0

41,200

34,000

28,200

25,200

60.0

8,200

6,700

5,600

5,000

60.0

41,200

34,000

28,200

25,200

65.0

8,200

6,700

5,600

5,000

65.0

41,200

34,000

28,200

25,200

5.0

5,500

5,400

5,300

5,200

5.0

24,800

24,200

23,800

23,400

14.0

6,500

6,200

6,100

6,100

14.0

29,100

28,000

27,600

27,200

23.0

7,400

7,100

7,000

6,600

23.0

33,300

31,900

31,500

29,500

32.0

8,300

7,900

7,300

6,600

32.0

37,600

35,700

33,000

29,500

37.0

8,900

8,400

7,300

6,600

37.0

40,100

38,000

33,000

29,500

43.0

9,500

9,000

7,300

6,600

43.0

42,700

40,000

33,000

29,500

46.0

9,900

9,000

7,300

6,600

46.0

44,400

40,000

33,000

29,500

50.0

10,200

9,000

7,300

6,600

50.0

46,100

40,000

33,000

29,500

55.0

10,700

9,000

7,300

6,600

55.0

48,200

40,000

33,000

29,500

60.0

10,700

9,000

7,300

6,600

60.0

48,200

40,000

33,000

29,500

65.0

10,700

9,000

7,300

6,600

65.0

48,200

40,000

33,000

29,500

5.0

8,500

8,300

8,100

8,000

5.0

33,500

32,700

32,100

31,600

30

36

81degF D.B.

14.0

9,900

9,600

9,400

9,300

14.0

39,200

37,800

37,300

36,800

23.0

11,400

10,900

10,800

10,100

23.0

45,000

43,100

42,500

39,900

32.0

12,800

12,200

11,300

10,100

37.0

13,700

13,000

11,300

10,100

48

32.0

50,700

48,200

44,600

39,900

37.0

54,200

51,300

44,600

39,900

43.0

14,600

13,500

11,300

10,100

43.0

57,600

54,000

44,600

39,900

46.0

15,200

13,500

11,300

10,100

46.0

59,900

54,000

44,600

39,900

50.0

15,700

13,500

11,300

10,100

50.0

62,200

54,000

44,600

39,900

55.0

16,500

13,500

11,300

10,100

55.0

65,100

54,000

44,600

39,900

60.0

16,500

13,500

11,300

10,100

60.0

65,100

54,000

44,600

39,900

65.0

16,500

13,500

11,300

10,100

65.0

65,100

54,000

44,600

39,900

5.0

10,600

10,400

10,200

10,000

5.0

37,400

36,500

35,700

35,200

14.0

12,400

12,000

11,800

11,600

14.0

43,700

42,200

41,600

41,000

23.0

14,200

13,600

13,400

12,600

23.0

50,100

48,000

47,300

44,400

32.0

16,100

15,300

14,100

12,600

32.0

56,500

53,700

49,700

44,400

37.0

17,100

16,200

14,100

12,600

37.0

60,400

57,200

49,700

44,400

43.0

18,200

17,000

14,100

12,600

43.0

64,200

60,000

49,700

44,400

46.0

19,000

17,000

14,100

12,600

46.0

66,800

60,000

49,700

44,400

50.0

19,700

17,000

14,100

12,600

50.0

69,300

60,000

49,700

44,400

55.0

20,600

17,000

14,100

12,600

55.0

72,500

60,000

49,700

44,400

60.0

20,600

17,000

14,100

12,600

60.0

72,500

60,000

49,700

44,400

65.0

20,600

17,000

14,100

12,600

65.0

72,500

60,000

49,700

44,400

5.0

12,500

12,200

12,000

11,800

5.0

49,700

48,500

47,500

46,800

14.0

14,700

14,100

13,900

13,700

14.0

58,100

56,000

55,200

54,500

23.0

16,800

16,100

15,900

14,900

23.0

66,700

63,900

62,900

59,100

32.0

18,900

18,000

16,600

14,900

32.0

75,100

71,500

66,000

59,100

37.0

20,200

19,200

16,600

14,900

37.0

80,200

76,000

66,000

59,100

43.0

21,500

20,000

16,600

14,900

43.0

85,300

80,000

66,000

59,100

46.0

22,400

20,000

16,600

14,900

46.0

88,800

80,000

66,000

59,100

50.0

23,200

20,000

16,600

14,900

50.0

92,100

80,000

66,000

59,100

55.0

24,300

20,000

16,600

14,900

55.0

96,400

80,000

66,000

59,100

60.0

24,300

20,000

16,600

14,900

60.0

96,400

80,000

66,000

59,100

65.0

24,300

20,000

16,600

14,900

65.0

96,400

80,000

66,000

59,100

5.0

16,800

16,400

16,000

15,800

5.0

67,300

65,700

64,400

63,400

14.0

19,600

18,900

18,700

18,400

14.0

78,700

75,900

74,800

73,800

23.0

22,500

21,600

21,200

19,900

23.0

90,300

86,500

85,200

80,000

32.0

25,400

24,100

22,300

19,900

32.0

101,800

96,800

89,400

80,000

37.0

27,100

25,700

22,300

19,900

37.0

108,700

103,000

89,400

80,000

43.0

28,800

27,000

22,300

19,900

43.0

115,600

108,000

89,400

80,000

54

72

96

46.0

30,000

27,000

22,300

19,900

46.0

120,300

108,000

89,400

80,000

50.0

31,100

27,000

22,300

19,900

50.0

124,800

108,000

89,400

80,000

55.0

32,600

27,000

22,300

19,900

55.0

130,700

108,000

89,400

80,000

60.0

32,600

27,000

22,300

19,900

60.0

130,700

108,000

89,400

80,000

65.0

32,600

27,000

22,300

19,900

65.0

130,700

108,000

89,400

80,000

5.0

18,700

18,200

17,900

17,600

14.0

21,900

21,100

20,800

20,500

23.0

25,100

24,000

23,700

22,200

32.0

28,300

26,900

24,800

22,200

37.0

30,200

28,600

24,800

22,200

43.0

32,100

30,000

24,800

22,200

46.0

33,400

30,000

24,800

22,200

50.0

34,600

30,000

24,800

22,200

55.0

36,300

30,000

24,800

22,200

60.0

36,300

30,000

24,800

22,200

65.0

36,300

30,000

24,800

22,200

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

27

Outdoor

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-37

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4. Cooing and Heating Capacity with PUHY-P264~360TSHMU-A/YSHMU-A


1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PEFY-P-NMSU-E
CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,800

5,200

6,000

5,200

6,500

5,400

6,700

5,400

6,900

5,600

7,500

5,600

7,800

5,700

73.0

5,700

5,200

5,900

5,200

6,300

5,400

6,600

5,400

6,800

5,600

7,300

5,500

7,700

5,700

77.0

5,700

5,200

5,800

5,100

6,200

5,300

6,500

5,300

6,700

5,600

7,200

5,500

7,600

5,600

82.0

5,500

5,100

5,700

5,100

6,100

5,300

6,300

5,300

6,600

5,500

7,100

5,500

7,600

5,700

86.0

5,400

5,100

5,700

5,100

6,000

5,200

6,200

5,200

6,400

5,500

6,900

5,400

7,400

5,600

91.0

5,300

5,000

5,500

5,000

5,900

5,200

6,100

5,200

6,300

5,400

6,800

5,400

7,200

5,500

95.0

5,200

5,000

5,500

5,000

5,700

5,200

6,000

5,200

6,200

5,400

6,700

5,300

7,000

5,500

100.0

5,200

4,900

5,400

4,900

5,700

5,100

5,900

5,100

6,100

5,300

6,600

5,300

6,900

5,400

104.0

5,100

4,900

5,200

4,900

5,500

5,100

5,800

5,100

6,000

5,300

6,400

5,200

6,800

5,400

110.0

4,900

4,900

5,100

4,800

5,400

5,000

5,700

5,000

5,800

5,200

6,300

5,200

6,600

5,300

68.0

7,700

6,800

8,000

6,700

8,500

7,000

8,900

7,000

9,100

7,300

9,900

7,200

10,400

7,400

73.0

7,500

6,700

7,800

6,700

8,300

6,900

8,700

6,900

9,000

7,200

9,700

7,100

10,200

7,300

77.0

7,500

6,700

7,700

6,600

8,200

6,900

8,600

6,800

8,800

7,100

9,500

7,100

10,000

7,300

82.0

7,300

6,600

7,600

6,600

8,000

6,800

8,400

6,800

8,700

7,100

9,400

7,000

10,000

7,300

86.0

7,200

6,500

7,500

6,500

7,900

6,700

8,200

6,700

8,500

7,000

9,200

6,900

9,700

7,200

91.0

7,000

6,500

7,300

6,400

7,800

6,700

8,100

6,700

8,300

6,900

9,000

6,900

9,500

7,100

95.0

6,900

6,400

7,200

6,400

7,600

6,600

8,000

6,600

8,200

6,900

8,800

6,800

9,300

7,000

100.0

6,800

6,400

7,100

6,400

7,500

6,600

7,800

6,600

8,100

6,800

8,700

6,800

9,100

7,000

104.0

6,700

6,300

6,900

6,300

7,300

6,500

7,700

6,500

7,900

6,800

8,500

6,700

8,900

6,900

110.0

6,500

6,200

6,700

6,200

7,100

6,400

7,500

6,400

7,700

6,700

8,300

6,700

8,700

6,800

68.0

11,600

9,000

12,000

9,000

12,800

9,300

13,300

9,200

13,700

9,600

14,900

9,500

15,600

9,700

73.0

11,300

8,900

11,800

8,900

12,600

9,200

13,100

9,100

13,500

9,500

14,600

9,400

15,300

9,600

77.0

11,200

8,900

11,600

8,800

12,400

9,100

12,900

9,000

13,300

9,400

14,300

9,300

15,100

9,500

82.0

11,000

8,700

11,400

8,700

12,100

9,000

12,600

8,900

13,000

9,300

14,100

9,200

15,100

9,500

86.0

10,800

8,600

11,200

8,600

11,900

8,900

12,300

8,800

12,800

9,200

13,800

9,100

14,600

9,300

91.0

10,600

8,500

11,000

8,500

11,700

8,800

12,200

8,800

12,500

9,100

13,500

9,000

14,300

9,200

95.0

10,400

8,500

10,900

8,500

11,400

8,700

12,000

8,700

12,400

9,000

13,300

8,900

14,000

9,100

100.0

10,200

8,400

10,700

8,400

11,300

8,600

11,800

8,600

12,100

8,900

13,000

8,800

13,700

9,000

104.0

10,100

8,300

10,400

8,200

11,000

8,500

11,600

8,500

12,000

8,900

12,800

8,700

13,500

8,900

110.0

9,800

8,200

10,100

8,100

10,700

8,400

11,300

8,400

11,600

8,700

12,500

8,600

13,100

8,800

68.0

14,500

10,800

15,000

10,800

16,000

11,200

16,700

11,100

17,200

11,500

18,700

11,400

19,500

11,600

73.0

14,200

10,700

14,800

10,700

15,700

11,000

16,300

10,900

16,900

11,400

18,200

11,300

19,100

11,400

77.0

14,100

10,600

14,500

10,600

15,500

10,900

16,100

10,800

16,600

11,200

17,900

11,100

18,800

11,300

82.0

13,800

10,500

14,300

10,400

15,100

10,800

15,700

10,700

16,300

11,100

17,600

11,000

18,900

11,300

86.0

13,500

10,300

14,100

10,300

14,800

10,600

15,400

10,500

16,000

11,000

17,200

10,900

18,300

11,100

91.0

13,200

10,200

13,700

10,200

14,700

10,500

15,200

10,500

15,600

10,800

16,900

10,700

17,900

11,000

95.0

13,000

10,100

13,600

10,100

14,300

10,400

15,000

10,400

15,500

10,800

16,600

10,600

17,500

10,800

100.0

12,800

10,000

13,300

10,000

14,100

10,300

14,800

10,300

15,200

10,600

16,300

10,500

17,200

10,700

104.0

12,700

9,900

12,900

9,800

13,700

10,100

14,500

10,200

14,900

10,500

15,900

10,400

16,800

10,600

110.0

12,300

9,700

12,600

9,600

13,300

10,000

14,100

10,000

14,500

10,300

15,600

10,300

16,400

10,400

68.0

17,400

13,400

18,000

13,300

19,300

13,800

20,000

13,700

20,600

14,200

22,400

14,100

23,400

14,300

73.0

17,000

13,200

17,700

13,200

18,800

13,600

19,600

13,500

20,300

14,000

21,900

13,900

23,000

14,200

77.0

16,900

13,100

17,400

13,000

18,600

13,500

19,300

13,400

20,000

13,900

21,400

13,700

22,600

14,000

82.0

16,500

12,900

17,100

12,900

18,200

13,300

18,900

13,200

19,500

13,700

21,100

13,600

22,700

14,100

86.0

16,200

12,800

16,900

12,800

17,800

13,100

18,500

13,100

19,200

13,600

20,700

13,500

21,900

13,800

91.0

15,900

12,600

16,500

12,600

17,600

13,000

18,300

13,000

18,800

13,400

20,200

13,300

21,500

13,600

95.0

15,600

12,500

16,300

12,500

17,100

12,900

18,000

12,800

18,600

13,300

19,900

13,200

21,000

13,500

100.0

15,400

12,400

16,000

12,400

16,900

12,700

17,700

12,700

18,200

13,200

19,600

13,000

20,600

13,300

104.0

15,200

12,300

15,500

12,200

16,500

12,600

17,400

12,600

17,900

13,100

19,100

12,900

20,200

13,200

110.0

14,700

12,100

15,100

12,000

16,000

12,400

16,900

12,400

17,400

12,900

18,800

12,800

19,600

13,000

68.0

23,100

17,600

24,000

17,600

25,600

18,200

26,600

18,000

27,400

18,700

29,800

18,600

31,100

18,800

73.0

22,600

17,400

23,500

17,400

25,000

17,900

26,100

17,800

27,000

18,500

29,100

18,300

30,500

18,700

77.0

22,400

17,300

23,200

17,200

24,700

17,800

25,700

17,600

26,500

18,300

28,500

18,100

30,100

18,500

82.0

21,900

17,000

22,800

17,000

24,100

17,500

25,100

17,400

26,000

18,100

28,100

18,000

30,100

18,500

86.0

21,500

16,800

22,400

16,800

23,700

17,300

24,600

17,200

25,500

17,900

27,500

17,700

29,200

18,200

91.0

21,100

16,700

21,900

16,600

23,400

17,200

24,300

17,100

25,000

17,700

26,900

17,500

28,500

17,900

95.0

20,800

16,500

21,700

16,500

22,800

16,900

24,000

16,900

24,700

17,600

26,400

17,300

27,900

17,700

100.0

20,400

16,300

21,300

16,300

22,500

16,800

23,500

16,800

24,200

17,400

26,000

17,200

27,400

17,500

104.0

20,200

16,200

20,600

16,000

21,900

16,500

23,200

16,600

23,800

17,200

25,400

17,000

26,800

17,300

110.0

19,600

15,900

20,100

15,800

21,300

16,300

22,500

16,300

23,100

16,900

25,000

16,800

26,100

17,100

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-38

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,500

9,900

15,000

9,900

16,000

10,200

16,700

10,100

17,200

10,400

18,700

10,400

19,500

10,500

73.0

14,200

9,800

14,800

9,800

15,700

10,000

16,300

9,900

16,900

10,300

18,200

10,200

19,100

10,300

77.0

14,100

9,700

14,500

9,600

15,500

9,900

16,100

9,800

16,600

10,100

17,900

10,000

18,800

10,200

82.0

13,800

9,500

14,300

9,500

15,100

9,700

15,700

9,600

16,300

10,000

17,600

9,900

18,900

10,200

86.0

13,500

9,300

14,100

9,400

14,800

9,600

15,400

9,500

16,000

9,800

17,200

9,800

18,300

9,900

91.0

13,200

9,200

13,700

9,200

14,700

9,500

15,200

9,400

15,600

9,700

16,900

9,600

17,900

9,800

95.0

13,000

9,100

13,600

9,100

14,300

9,300

15,000

9,300

15,500

9,600

16,600

9,500

17,500

9,600

100.0

12,800

9,000

13,300

9,000

14,100

9,200

14,800

9,200

15,200

9,400

16,300

9,400

17,200

9,500

104.0

12,700

8,900

12,900

8,800

13,700

9,000

14,500

9,100

14,900

9,300

15,900

9,200

16,800

9,300

110.0

12,300

8,700

12,600

8,600

13,300

8,800

14,100

8,800

14,500

9,100

15,600

9,100

16,400

9,200

68.0

17,500

12,100

18,100

12,100

19,300

12,400

20,100

12,300

20,700

12,700

22,500

12,700

23,400

12,700

73.0

17,100

11,900

17,800

11,900

18,900

12,200

19,700

12,100

20,400

12,500

22,000

12,500

23,100

12,600

77.0

16,900

11,800

17,500

11,800

18,600

12,100

19,400

12,000

20,000

12,400

21,500

12,300

22,700

12,400

82.0

16,600

11,600

17,200

11,600

18,200

11,900

18,900

11,800

19,600

12,200

21,200

12,100

22,800

12,500

86.0

16,200

11,400

16,900

11,400

17,900

11,700

18,600

11,600

19,300

12,000

20,700

11,900

22,000

12,200

91.0

16,000

11,300

16,500

11,200

17,600

11,600

18,400

11,500

18,800

11,800

20,300

11,700

21,500

12,000

95.0

15,700

11,100

16,300

11,100

17,200

11,400

18,100

11,400

18,700

11,700

20,000

11,600

21,100

11,800

100.0

15,400

11,000

16,100

11,000

17,000

11,300

17,800

11,200

18,300

11,600

19,600

11,400

20,700

11,600

104.0

15,300

10,900

15,600

10,800

16,500

11,000

17,500

11,100

18,000

11,400

19,200

11,300

20,300

11,400

110.0

14,800

10,600

15,100

10,500

16,100

10,800

17,000

10,800

17,500

11,200

18,800

11,100

19,700

11,200

68.0

23,000

15,900

23,900

15,900

25,500

16,400

26,500

16,200

27,300

16,700

29,700

16,700

31,000

16,800

73.0

22,600

15,600

23,500

15,600

25,000

16,100

26,000

15,900

26,900

16,500

29,000

16,400

30,400

16,500

77.0

22,400

15,500

23,100

15,500

24,600

15,900

25,600

15,700

26,500

16,300

28,400

16,100

30,000

16,300

82.0

21,900

15,200

22,700

15,200

24,100

15,600

25,000

15,500

25,900

16,000

28,000

15,900

30,100

16,400

86.0

21,400

15,000

22,400

15,000

23,600

15,400

24,600

15,200

25,400

15,800

27,400

15,700

29,100

16,000

91.0

21,100

14,800

21,800

14,800

23,300

15,200

24,200

15,100

24,900

15,500

26,800

15,400

28,400

15,700

95.0

20,700

14,600

21,600

14,600

22,700

14,900

23,900

14,900

24,700

15,400

26,400

15,200

27,900

15,500

100.0

20,400

14,400

21,200

14,500

22,400

14,800

23,500

14,700

24,100

15,200

25,900

15,000

27,300

15,200

104.0

20,200

14,300

20,600

14,100

21,800

14,500

23,100

14,500

23,800

15,000

25,400

14,800

26,800

15,000

110.0

19,500

14,000

20,000

13,800

21,200

14,200

22,400

14,200

23,100

14,700

24,900

14,600

26,000

14,700

68.0

26,000

18,200

27,000

18,100

28,800

18,700

29,900

18,500

30,900

19,100

33,500

19,100

35,000

19,200

73.0

25,500

17,900

26,500

17,900

28,200

18,400

29,300

18,200

30,400

18,900

32,700

18,700

34,400

18,900

77.0

25,200

17,700

26,100

17,700

27,800

18,200

28,900

18,000

29,900

18,600

32,100

18,400

33,800

18,700

82.0

24,700

17,400

25,600

17,400

27,200

17,900

28,200

17,700

29,200

18,300

31,600

18,200

33,900

18,800

86.0

24,200

17,200

25,200

17,200

26,600

17,600

27,700

17,400

28,700

18,100

30,900

17,900

32,800

18,300

91.0

23,800

17,000

24,600

16,900

26,300

17,400

27,400

17,300

28,100

17,800

30,300

17,700

32,100

18,000

95.0

23,400

16,800

24,400

16,800

25,600

17,100

27,000

17,100

27,800

17,700

29,800

17,500

31,400

17,800

100.0

23,000

16,500

24,000

16,600

25,300

16,900

26,500

16,900

27,200

17,400

29,300

17,300

30,800

17,500

104.0

22,700

16,400

23,200

16,200

24,600

16,600

26,100

16,700

26,800

17,200

28,600

17,000

30,200

17,300

110.0

22,000

16,000

22,600

15,900

23,900

16,300

25,300

16,300

26,000

16,900

28,100

16,800

29,400

17,000

68.0

29,000

20,200

30,000

20,200

32,100

20,800

33,300

20,600

34,400

21,200

37,300

21,200

38,900

21,300

73.0

28,400

19,900

29,500

19,900

31,400

20,400

32,700

20,300

33,800

21,000

36,500

20,800

38,300

21,100

77.0

28,100

19,700

29,100

19,600

31,000

20,200

32,200

20,000

33,300

20,700

35,700

20,500

37,700

20,800

82.0

27,500

19,400

28,600

19,400

30,300

19,900

31,500

19,700

32,600

20,400

35,200

20,300

37,800

20,900

86.0

26,900

19,100

28,100

19,100

29,700

19,600

30,900

19,400

32,000

20,100

34,400

20,000

36,600

20,400

91.0

26,500

18,800

27,400

18,800

29,300

19,400

30,500

19,200

31,300

19,800

33,700

19,700

35,800

20,000

95.0

26,100

18,600

27,100

18,700

28,600

19,000

30,000

19,000

31,000

19,700

33,100

19,400

35,000

19,700

100.0

25,600

18,400

26,700

18,400

28,200

18,800

29,500

18,800

30,300

19,400

32,600

19,200

34,400

19,500

104.0

25,300

18,200

25,900

18,000

27,400

18,500

29,100

18,600

29,900

19,200

31,900

18,900

33,600

19,200

110.0

24,500

17,800

25,100

17,600

26,700

18,100

28,200

18,200

29,000

18,800

31,300

18,600

32,700

18,800

68.0

34,900

24,900

36,200

24,800

38,700

25,600

40,200

25,400

41,400

26,200

44,900

26,100

46,900

26,300

73.0

34,200

24,500

35,600

24,500

37,800

25,200

39,400

25,000

40,800

25,900

43,900

25,700

46,100

26,000

77.0

33,900

24,300

35,000

24,200

37,300

24,900

38,700

24,700

40,100

25,600

43,000

25,300

45,400

25,700

82.0

33,100

23,900

34,400

23,900

36,500

24,500

37,900

24,300

39,200

25,200

42,400

25,100

45,500

25,800

86.0

32,400

23,600

33,900

23,600

35,700

24,200

37,200

24,000

38,500

24,900

41,500

24,700

44,100

25,200

91.0

31,900

23,300

33,100

23,200

35,300

24,000

36,700

23,800

37,700

24,500

40,700

24,400

43,100

24,800

95.0

31,400

23,000

32,700

23,100

34,400

23,600

36,200

23,500

37,400

24,400

39,900

24,100

42,200

24,500

100.0

30,900

22,800

32,200

22,800

33,900

23,300

35,600

23,300

36,500

24,000

39,300

23,800

41,400

24,200

104.0

30,500

22,600

31,200

22,300

33,000

22,900

35,000

23,000

36,000

23,800

38,400

23,400

40,500

23,900

110.0

29,600

22,100

30,300

21,900

32,100

22,500

33,900

22,600

34,900

23,300

37,700

23,200

39,400

23,500

68.0

46,400

31,900

48,100

31,900

51,400

32,800

53,400

32,500

55,100

33,500

59,800

33,500

62,400

33,600

73.0

45,500

31,400

47,300

31,400

50,300

32,300

52,400

32,000

54,200

33,100

58,400

32,900

61,300

33,200

77.0

45,000

31,100

46,600

31,000

49,600

31,900

51,500

31,500

53,300

32,600

57,200

32,300

60,400

32,800

82.0

44,100

30,600

45,800

30,600

48,500

31,300

50,400

31,000

52,200

32,100

56,400

32,000

60,600

32,800

86.0

43,200

30,100

45,000

30,200

47,500

30,800

49,500

30,500

51,200

31,600

55,200

31,400

58,600

32,000

91.0

42,400

29,700

44,000

29,600

47,000

30,500

48,800

30,200

50,100

31,100

54,100

30,900

57,300

31,500

95.0

41,800

29,300

43,500

29,400

45,800

29,900

48,100

29,900

49,700

30,900

53,100

30,500

56,100

31,000

100.0

41,000

28,900

42,800

29,000

45,100

29,600

47,300

29,500

48,600

30,400

52,200

30,100

55,000

30,600

104.0

40,600

28,700

41,500

28,300

43,900

29,000

46,600

29,200

47,900

30,100

51,100

29,600

53,900

30,100

110.0

39,300

28,000

40,300

27,700

42,700

28,500

45,100

28,500

46,400

29,400

50,100

29,200

52,500

29,500

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-39

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

52,000

36,800

53,900

36,700

57,600

37,900

59,900

37,500

61,700

38,700

67,000

38,600

69,900

38,900
38,400

73.0

50,900

36,200

53,000

36,200

56,400

37,200

58,700

36,900

60,800

38,200

65,500

38,000

68,700

77.0

50,500

35,900

52,200

35,800

55,600

36,800

57,700

36,500

59,700

37,800

64,100

37,400

67,700

38,000

82.0

49,400

35,400

51,300

35,300

54,300

36,200

56,500

35,900

58,500

37,200

63,200

37,000

67,900

38,100

86.0

48,400

34,800

50,500

34,900

53,300

35,700

55,400

35,400

57,400

36,700

61,800

36,400

65,700

37,200

91.0

47,600

34,400

49,300

34,300

52,600

35,400

54,700

35,100

56,200

36,200

60,600

35,900

64,200

36,600

95.0

46,800

34,000

48,700

34,000

51,300

34,800

53,900

34,700

55,700

36,000

59,500

35,500

62,900

36,100

100.0

46,000

33,600

47,900

33,600

50,600

34,400

53,000

34,300

54,500

35,400

58,500

35,100

61,700

35,700

104.0

45,500

33,300

46,500

32,900

49,200

33,800

52,200

34,000

53,600

35,100

57,200

34,600

60,400

35,200

110.0

44,100

32,600

45,100

32,300

47,900

33,200

50,600

33,200

52,000

34,400

56,200

34,100

58,800

34,600

68.0

69,500

48,400

72,000

48,300

76,900

49,800

79,900

49,300

82,400

50,900

89,500

50,800

93,400

51,100

73.0

68,000

47,600

70,800

47,600

75,300

49,000

78,400

48,500

81,100

50,200

87,400

49,900

91,800

50,400

77.0

67,400

47,200

69,700

47,100

74,200

48,400

77,100

47,900

79,800

49,600

85,600

49,100

90,300

49,800

82.0

65,900

46,500

68,500

46,400

72,600

47,600

75,400

47,100

78,100

48,800

84,400

48,600

90,600

49,900

86.0

64,600

45,700

67,400

45,900

71,100

46,900

74,000

46,500

76,700

48,200

82,600

47,800

87,700

48,800

91.0

63,500

45,200

65,800

45,000

70,300

46,500

73,100

46,000

75,000

47,400

80,900

47,100

85,700

48,000

95.0

62,500

44,600

65,100

44,700

68,500

45,600

72,000

45,500

74,400

47,100

79,500

46,500

83,900

47,300

100.0

61,400

44,000

64,000

44,100

67,500

45,100

70,800

45,000

72,700

46,400

78,200

45,900

82,400

46,600

104.0

60,800

43,700

62,100

43,100

65,800

44,300

69,700

44,500

71,600

45,900

76,500

45,200

80,600

46,000

110.0

58,800

42,700

60,300

42,200

64,000

43,400

67,500

43,500

69,500

44,900

75,000

44,600

78,500

45,100

68.0

92,500

64,900

95,900

64,800

102,500

66,800

106,500

66,100

109,800

68,300

119,100

68,100

124,300

68,600

73.0

90,600

63,900

94,200

63,900

100,300

65,700

104,400

65,100

108,000

67,500

116,400

67,000

122,200

67,700

77.0

89,700

63,400

92,800

63,200

98,800

65,000

102,700

64,300

106,200

66,600

114,000

65,900

120,300

66,900

82.0

87,800

62,400

91,200

62,300

96,600

63,900

100,500

63,300

104,000

65,600

112,400

65,200

120,700

67,100

86.0

86,000

61,400

89,700

61,600

94,700

63,000

98,600

62,400

102,100

64,700

110,000

64,200

116,800

65,500

91.0

84,600

60,700

87,600

60,500

93,600

62,400

97,300

61,900

99,900

63,800

107,800

63,300

114,200

64,500

95.0

83,200

59,900

86,700

60,000

91,200

61,300

95,900

61,200

99,000

63,400

105,800

62,500

111,800

63,600

100.0

81,800

59,200

85,200

59,300

89,900

60,700

94,200

60,500

96,800

62,400

104,100

61,800

109,700

62,800

104.0

80,900

58,700

82,600

58,000

87,600

59,600

92,800

59,800

95,400

61,700

101,800

60,800

107,400

61,900

110.0

78,300

57,400

80,300

56,800

85,200

58,400

89,900

58,500

92,500

60,500

99,900

60,100

104,600

60,800

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-40

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA
DATAU4
U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

4,500

6,100

4,500

6,600

4,700

6,800

4,600

7,000

4,800

7,600

4,800

8,000

4,800

73.0

5,800

4,500

6,000

4,500

6,400

4,600

6,700

4,600

6,900

4,800

7,500

4,700

7,800

4,800

77.0

5,700

4,400

5,900

4,400

6,300

4,600

6,600

4,500

6,800

4,700

7,300

4,700

7,700

4,800

82.0

5,600

4,400

5,800

4,400

6,200

4,500

6,400

4,500

6,700

4,600

7,200

4,600

7,700

4,800

86.0

5,500

4,300

5,700

4,300

6,100

4,500

6,300

4,400

6,500

4,600

7,000

4,600

7,500

4,700

91.0

5,400

4,300

5,600

4,300

6,000

4,400

6,200

4,400

6,400

4,500

6,900

4,500

7,300

4,600

95.0

5,300

4,200

5,600

4,200

5,800

4,400

6,100

4,300

6,300

4,500

6,800

4,500

7,200

4,600

100.0

5,200

4,200

5,500

4,200

5,800

4,300

6,000

4,300

6,200

4,500

6,700

4,400

7,000

4,500

104.0

5,200

4,200

5,300

4,100

5,600

4,300

5,900

4,300

6,100

4,400

6,500

4,400

6,900

4,500

110.0

5,000

4,100

5,100

4,100

5,500

4,200

5,800

4,200

5,900

4,400

6,400

4,300

6,700

4,400

68.0

7,600

5,600

7,800

5,500

8,400

5,700

8,700

5,700

9,000

5,900

9,800

5,800

10,200

5,900

73.0

7,400

5,500

7,700

5,500

8,200

5,600

8,500

5,600

8,800

5,800

9,500

5,800

10,000

5,800

77.0

7,300

5,400

7,600

5,400

8,100

5,600

8,400

5,500

8,700

5,700

9,300

5,700

9,800

5,800

82.0

7,200

5,400

7,500

5,300

7,900

5,500

8,200

5,500

8,500

5,700

9,200

5,600

9,900

5,800

86.0

7,000

5,300

7,300

5,300

7,800

5,400

8,100

5,400

8,400

5,600

9,000

5,500

9,600

5,700

91.0

6,900

5,200

7,200

5,200

7,700

5,400

8,000

5,300

8,200

5,500

8,800

5,500

9,300

5,600

95.0

6,800

5,200

7,100

5,200

7,500

5,300

7,800

5,300

8,100

5,500

8,700

5,400

9,200

5,500

100.0

6,700

5,100

7,000

5,100

7,400

5,300

7,700

5,200

7,900

5,400

8,500

5,400

9,000

5,500

104.0

6,600

5,100

6,800

5,000

7,200

5,200

7,600

5,200

7,800

5,400

8,300

5,300

8,800

5,400

110.0

6,400

5,000

6,600

4,900

7,000

5,100

7,400

5,100

7,600

5,300

8,200

5,200

8,600

5,300

68.0

11,500

8,100

11,900

8,000

12,800

8,300

13,300

8,200

13,700

8,500

14,800

8,500

15,500

8,500

73.0

11,300

7,900

11,700

7,900

12,500

8,200

13,000

8,100

13,500

8,400

14,500

8,300

15,200

8,400

77.0

11,200

7,900

11,600

7,800

12,300

8,100

12,800

8,000

13,200

8,300

14,200

8,200

15,000

8,300

82.0

10,900

7,700

11,400

7,700

12,000

7,900

12,500

7,900

13,000

8,100

14,000

8,100

15,000

8,300

86.0

10,700

7,600

11,200

7,600

11,800

7,800

12,300

7,700

12,700

8,000

13,700

8,000

14,500

8,100

91.0

10,500

7,500

10,900

7,500

11,700

7,700

12,100

7,700

12,400

7,900

13,400

7,900

14,200

8,000

95.0

10,400

7,400

10,800

7,400

11,400

7,600

11,900

7,600

12,300

7,900

13,200

7,800

13,900

7,900

100.0

10,200

7,300

10,600

7,400

11,200

7,500

11,700

7,500

12,100

7,700

13,000

7,700

13,700

7,800

104.0

10,100

7,300

10,300

7,200

10,900

7,400

11,600

7,400

11,900

7,700

12,700

7,500

13,400

7,700

110.0

9,800

7,100

10,000

7,000

10,600

7,200

11,200

7,300

11,500

7,500

12,400

7,400

13,000

7,500

68.0

14,500

10,900

15,000

10,900

16,000

11,300

16,700

11,200

17,200

11,600

18,700

11,500

19,500

11,700

73.0

14,200

10,800

14,800

10,800

15,700

11,100

16,300

11,000

16,900

11,400

18,200

11,400

19,100

11,500

77.0

14,100

10,700

14,500

10,700

15,500

11,000

16,100

10,900

16,600

11,300

17,900

11,200

18,800

11,400

82.0

13,800

10,600

14,300

10,500

15,100

10,800

15,700

10,800

16,300

11,200

17,600

11,100

18,900

11,400

86.0

13,500

10,400

14,100

10,400

14,800

10,700

15,400

10,600

16,000

11,100

17,200

11,000

18,300

11,200

91.0

13,200

10,300

13,700

10,300

14,700

10,600

15,200

10,600

15,600

10,900

16,900

10,800

17,900

11,100

95.0

13,000

10,200

13,600

10,200

14,300

10,500

15,000

10,500

15,500

10,900

16,600

10,700

17,500

11,000

100.0

12,800

10,100

13,300

10,100

14,100

10,400

14,800

10,400

15,200

10,700

16,300

10,600

17,200

10,800

104.0

12,700

10,000

12,900

9,900

13,700

10,200

14,500

10,300

14,900

10,600

15,900

10,500

16,800

10,700

110.0

12,300

9,800

12,600

9,700

13,300

10,100

14,100

10,100

14,500

10,400

15,600

10,400

16,400

10,600

68.0

17,500

12,900

18,100

12,900

19,300

13,300

20,100

13,200

20,700

13,600

22,500

13,600

23,400

13,700

73.0

17,100

12,700

17,800

12,700

18,900

13,100

19,700

13,000

20,400

13,500

22,000

13,400

23,100

13,600

77.0

16,900

12,600

17,500

12,600

18,600

13,000

19,400

12,800

20,000

13,300

21,500

13,200

22,700

13,400

82.0

16,600

12,400

17,200

12,400

18,200

12,800

18,900

12,700

19,600

13,200

21,200

13,100

22,800

13,500

86.0

16,200

12,300

16,900

12,300

17,900

12,600

18,600

12,500

19,300

13,000

20,700

12,900

22,000

13,200

91.0

16,000

12,100

16,500

12,100

17,600

12,500

18,400

12,400

18,800

12,800

20,300

12,700

21,500

13,000

95.0

15,700

12,000

16,300

12,000

17,200

12,300

18,100

12,300

18,700

12,800

20,000

12,600

21,100

12,800

100.0

15,400

11,900

16,100

11,900

17,000

12,200

17,800

12,200

18,300

12,600

19,600

12,500

20,700

12,700

104.0

15,300

11,800

15,600

11,700

16,500

12,000

17,500

12,100

18,000

12,500

19,200

12,300

20,300

12,500

110.0

14,800

11,600

15,100

11,400

16,100

11,800

17,000

11,800

17,500

12,300

18,800

12,200

19,700

12,400

68.0

23,000

17,000

23,900

16,900

25,500

17,500

26,500

17,300

27,300

17,900

29,700

17,900

31,000

18,000

73.0

22,600

16,700

23,500

16,700

25,000

17,200

26,000

17,100

26,900

17,700

29,000

17,600

30,400

17,800

77.0

22,400

16,600

23,100

16,500

24,600

17,100

25,600

16,900

26,500

17,500

28,400

17,300

30,000

17,700

82.0

21,900

16,400

22,700

16,300

24,100

16,800

25,000

16,700

25,900

17,300

28,000

17,200

30,100

17,700

86.0

21,400

16,100

22,400

16,200

23,600

16,600

24,600

16,500

25,400

17,100

27,400

16,900

29,100

17,300

91.0

21,100

16,000

21,800

15,900

23,300

16,500

24,200

16,300

24,900

16,900

26,800

16,700

28,400

17,100

95.0

20,700

15,800

21,600

15,800

22,700

16,200

23,900

16,200

24,700

16,800

26,400

16,500

27,900

16,900

100.0

20,400

15,600

21,200

15,600

22,400

16,000

23,500

16,000

24,100

16,500

25,900

16,400

27,300

16,700

104.0

20,200

15,500

20,600

15,300

21,800

15,800

23,100

15,800

23,800

16,400

25,400

16,200

26,800

16,500

110.0

19,500

15,200

20,000

15,000

21,200

15,500

22,400

15,500

23,100

16,100

24,900

16,000

26,000

16,200

68.0

26,000

18,900

27,000

18,800

28,800

19,400

29,900

19,200

30,900

19,900

33,500

19,800

35,000

20,000

73.0

25,500

18,600

26,500

18,600

28,200

19,100

29,300

19,000

30,400

19,700

32,700

19,500

34,400

19,800

77.0

25,200

18,400

26,100

18,400

27,800

18,900

28,900

18,800

29,900

19,500

32,100

19,200

33,800

19,600

82.0

24,700

18,200

25,600

18,100

27,200

18,600

28,200

18,500

29,200

19,200

31,600

19,100

33,900

19,600

86.0

24,200

17,900

25,200

17,900

26,600

18,400

27,700

18,200

28,700

18,900

30,900

18,800

32,800

19,200

91.0

23,800

17,700

24,600

17,700

26,300

18,200

27,400

18,100

28,100

18,700

30,300

18,500

32,100

18,900

95.0

23,400

17,500

24,400

17,500

25,600

17,900

27,000

17,900

27,800

18,600

29,800

18,300

31,400

18,700

100.0

23,000

17,300

24,000

17,300

25,300

17,800

26,500

17,700

27,200

18,300

29,300

18,100

30,800

18,500

104.0

22,700

17,200

23,200

17,000

24,600

17,500

26,100

17,500

26,800

18,100

28,600

17,900

30,200

18,200

110.0

22,000

16,800

22,600

16,700

23,900

17,200

25,300

17,200

26,000

17,800

28,100

17,700

29,400

17,900

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-41

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

29,000

20,800

30,000

20,800

32,100

21,400

33,300

21,200

34,400

21,900

37,300

21,900

38,900

22,100

73.0

28,400

20,500

29,500

20,500

31,400

21,100

32,700

20,900

33,800

21,700

36,500

21,500

38,300

21,800

77.0

28,100

20,400

29,100

20,300

31,000

20,900

32,200

20,700

33,300

21,400

35,700

21,200

37,700

21,600

82.0

27,500

20,000

28,600

20,000

30,300

20,600

31,500

20,400

32,600

21,100

35,200

21,000

37,800

21,600

86.0

26,900

19,800

28,100

19,800

29,700

20,300

30,900

20,100

32,000

20,900

34,400

20,700

36,600

21,100

91.0

26,500

19,500

27,400

19,500

29,300

20,100

30,500

19,900

31,300

20,600

33,700

20,400

35,800

20,800

95.0

26,100

19,300

27,100

19,300

28,600

19,800

30,000

19,700

31,000

20,500

33,100

20,200

35,000

20,600

100.0

25,600

19,100

26,700

19,100

28,200

19,600

29,500

19,500

30,300

20,200

32,600

20,000

34,400

20,300

104.0

25,300

18,900

25,900

18,700

27,400

19,200

29,100

19,300

29,900

20,000

31,900

19,700

33,600

20,000

110.0

24,500

18,500

25,100

18,300

26,700

18,900

28,200

18,900

29,000

19,600

31,300

19,400

32,700

19,700

68.0

34,900

25,700

36,200

25,700

38,700

26,500

40,200

26,300

41,400

27,200

44,900

27,100

46,900

27,400

73.0

34,200

25,400

35,600

25,400

37,800

26,100

39,400

25,900

40,800

26,900

43,900

26,700

46,100

27,100

77.0

33,900

25,200

35,000

25,100

37,300

25,900

38,700

25,700

40,100

26,600

43,000

26,300

45,400

26,800

82.0

33,100

24,800

34,400

24,800

36,500

25,500

37,900

25,300

39,200

26,300

42,400

26,100

45,500

26,900

86.0

32,400

24,500

33,900

24,500

35,700

25,200

37,200

25,000

38,500

26,000

41,500

25,700

44,100

26,300

91.0

31,900

24,200

33,100

24,200

35,300

25,000

36,700

24,800

37,700

25,600

40,700

25,400

43,100

26,000

95.0

31,400

24,000

32,700

24,000

34,400

24,600

36,200

24,600

37,400

25,500

39,900

25,100

42,200

25,600

100.0

30,900

23,700

32,200

23,700

33,900

24,400

35,600

24,300

36,500

25,100

39,300

24,900

41,400

25,400

104.0

30,500

23,500

31,200

23,300

33,000

24,000

35,000

24,100

36,000

24,900

38,400

24,500

40,500

25,000

110.0

29,600

23,100

30,300

22,800

32,100

23,600

33,900

23,600

34,900

24,500

37,700

24,300

39,400

24,700

68.0

46,400

33,100

48,100

33,000

51,400

34,000

53,400

33,700

55,100

34,800

59,800

34,700

62,400

35,000

73.0

45,500

32,500

47,300

32,600

50,300

33,500

52,400

33,200

54,200

34,400

58,400

34,200

61,300

34,600

77.0

45,000

32,300

46,600

32,200

49,600

33,200

51,500

32,800

53,300

34,000

57,200

33,700

60,400

34,200

82.0

44,100

31,800

45,800

31,800

48,500

32,600

50,400

32,300

52,200

33,500

56,400

33,300

60,600

34,300

86.0

43,200

31,300

45,000

31,400

47,500

32,200

49,500

31,900

51,200

33,100

55,200

32,800

58,600

33,500

91.0

42,400

31,000

44,000

30,900

47,000

31,900

48,800

31,600

50,100

32,600

54,100

32,400

57,300

33,000

95.0

41,800

30,600

43,500

30,600

45,800

31,300

48,100

31,300

49,700

32,400

53,100

32,000

56,100

32,600

100.0

41,000

30,300

42,800

30,300

45,100

31,000

47,300

30,900

48,600

31,900

52,200

31,600

55,000

32,200

104.0

40,600

30,000

41,500

29,700

43,900

30,500

46,600

30,600

47,900

31,600

51,100

31,200

53,900

31,700

110.0

39,300

29,400

40,300

29,100

42,700

29,900

45,100

30,000

46,400

31,000

50,100

30,800

52,500

31,200

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-42

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PMFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

5,300

6,100

5,300

6,600

5,500

6,800

5,400

7,000

5,700

7,600

5,600

8,000

5,800

73.0

5,800

5,200

6,000

5,200

6,400

5,400

6,700

5,400

6,900

5,600

7,500

5,600

7,800

5,700

77.0

5,700

5,200

5,900

5,200

6,300

5,400

6,600

5,300

6,800

5,600

7,300

5,500

7,700

5,700

82.0

5,600

5,100

5,800

5,100

6,200

5,300

6,400

5,300

6,700

5,500

7,200

5,500

7,700

5,700

86.0

5,500

5,100

5,700

5,100

6,100

5,300

6,300

5,200

6,500

5,500

7,000

5,400

7,500

5,600

91.0

5,400

5,000

5,600

5,000

6,000

5,200

6,200

5,200

6,400

5,400

6,900

5,400

7,300

5,500

95.0

5,300

5,000

5,600

5,000

5,800

5,200

6,100

5,200

6,300

5,400

6,800

5,300

7,200

5,500

100.0

5,200

5,000

5,500

5,000

5,800

5,100

6,000

5,100

6,200

5,400

6,700

5,300

7,000

5,400

104.0

5,200

4,900

5,300

4,900

5,600

5,100

5,900

5,100

6,100

5,300

6,500

5,200

6,900

5,400

110.0

5,000

4,900

5,100

4,800

5,500

5,000

5,800

5,000

5,900

5,200

6,400

5,200

6,700

5,300

68.0

7,600

6,400

7,800

6,300

8,400

6,600

8,700

6,500

9,000

6,800

9,800

6,800

10,200

6,900

73.0

7,400

6,300

7,700

6,300

8,200

6,500

8,500

6,500

8,800

6,800

9,500

6,700

10,000

6,800

77.0

7,300

6,300

7,600

6,200

8,100

6,500

8,400

6,400

8,700

6,700

9,300

6,600

9,800

6,800

82.0

7,200

6,200

7,500

6,200

7,900

6,400

8,200

6,400

8,500

6,600

9,200

6,600

9,900

6,800

86.0

7,000

6,100

7,300

6,100

7,800

6,300

8,100

6,300

8,400

6,600

9,000

6,500

9,600

6,700

91.0

6,900

6,100

7,200

6,000

7,700

6,300

8,000

6,300

8,200

6,500

8,800

6,400

9,300

6,600

95.0

6,800

6,000

7,100

6,000

7,500

6,200

7,800

6,200

8,100

6,500

8,700

6,400

9,200

6,600

100.0

6,700

6,000

7,000

6,000

7,400

6,200

7,700

6,200

7,900

6,400

8,500

6,300

9,000

6,500

104.0

6,600

5,900

6,800

5,900

7,200

6,100

7,600

6,100

7,800

6,400

8,300

6,300

8,800

6,400

110.0

6,400

5,800

6,600

5,800

7,000

6,000

7,400

6,000

7,600

6,300

8,200

6,200

8,600

6,400

68.0

11,500

8,300

11,900

8,300

12,800

8,600

13,300

8,500

13,700

8,800

14,800

8,800

15,500

8,900

73.0

11,300

8,200

11,700

8,200

12,500

8,500

13,000

8,400

13,500

8,700

14,500

8,600

15,200

8,800

77.0

11,200

8,200

11,600

8,100

12,300

8,400

12,800

8,300

13,200

8,600

14,200

8,500

15,000

8,700

82.0

10,900

8,000

11,400

8,000

12,000

8,300

12,500

8,200

13,000

8,500

14,000

8,400

15,000

8,700

86.0

10,700

7,900

11,200

7,900

11,800

8,100

12,300

8,100

12,700

8,400

13,700

8,300

14,500

8,500

91.0

10,500

7,800

10,900

7,800

11,700

8,100

12,100

8,000

12,400

8,300

13,400

8,200

14,200

8,400

95.0

10,400

7,800

10,800

7,800

11,400

7,900

11,900

7,900

12,300

8,200

13,200

8,100

13,900

8,300

100.0

10,200

7,700

10,600

7,700

11,200

7,900

11,700

7,800

12,100

8,100

13,000

8,000

13,700

8,200

104.0

10,100

7,600

10,300

7,500

10,900

7,700

11,600

7,800

11,900

8,000

12,700

7,900

13,400

8,100

110.0

9,800

7,500

10,000

7,400

10,600

7,600

11,200

7,600

11,500

7,900

12,400

7,800

13,000

7,900

68.0

14,500

10,200

15,000

10,200

16,000

10,500

16,700

10,400

17,200

10,700

18,700

10,700

19,500

10,800

73.0

14,200

10,100

14,800

10,100

15,700

10,300

16,300

10,300

16,900

10,600

18,200

10,500

19,100

10,700

77.0

14,100

10,000

14,500

9,900

15,500

10,200

16,100

10,100

16,600

10,500

17,900

10,400

18,800

10,500

82.0

13,800

9,800

14,300

9,800

15,100

10,100

15,700

10,000

16,300

10,300

17,600

10,300

18,900

10,600

86.0

13,500

9,700

14,100

9,700

14,800

9,900

15,400

9,800

16,000

10,200

17,200

10,100

18,300

10,300

91.0

13,200

9,600

13,700

9,500

14,700

9,800

15,200

9,700

15,600

10,100

16,900

10,000

17,900

10,200

95.0

13,000

9,400

13,600

9,500

14,300

9,700

15,000

9,600

15,500

10,000

16,600

9,900

17,500

10,000

100.0

12,800

9,300

13,300

9,300

14,100

9,600

14,800

9,500

15,200

9,800

16,300

9,700

17,200

9,900

104.0

12,700

9,300

12,900

9,100

13,700

9,400

14,500

9,400

14,900

9,700

15,900

9,600

16,800

9,800

110.0

12,300

9,100

12,600

9,000

13,300

9,200

14,100

9,200

14,500

9,500

15,600

9,500

16,400

9,600

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-43

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PLFY-P-NCMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

7,600

6,700

7,800

6,700

8,400

7,000

8,700

6,900

9,000

7,200

9,800

7,200

10,200

7,300

73.0

7,400

6,600

7,700

6,600

8,200

6,900

8,500

6,900

8,800

7,200

9,500

7,100

10,000

7,300

77.0

7,300

6,600

7,600

6,600

8,100

6,800

8,400

6,800

8,700

7,100

9,300

7,000

9,800

7,200

82.0

7,200

6,500

7,500

6,500

7,900

6,800

8,200

6,700

8,500

7,000

9,200

7,000

9,900

7,200

86.0

7,000

6,500

7,300

6,500

7,800

6,700

8,100

6,700

8,400

7,000

9,000

6,900

9,600

7,100

91.0

6,900

6,400

7,200

6,400

7,700

6,700

8,000

6,600

8,200

6,900

8,800

6,800

9,300

7,000

95.0

6,800

6,400

7,100

6,400

7,500

6,600

7,800

6,600

8,100

6,900

8,700

6,800

9,200

7,000

100.0

6,700

6,300

7,000

6,300

7,400

6,500

7,700

6,500

7,900

6,800

8,500

6,700

9,000

6,900

104.0

6,600

6,300

6,800

6,200

7,200

6,500

7,600

6,500

7,800

6,800

8,300

6,700

8,800

6,900

110.0

6,400

6,200

6,600

6,100

7,000

6,400

7,400

6,400

7,600

6,700

8,200

6,600

8,600

6,800

68.0

11,500

8,900

11,900

8,900

12,800

9,200

13,300

9,200

13,700

9,500

14,800

9,400

15,500

9,600

73.0

11,300

8,800

11,700

8,800

12,500

9,100

13,000

9,000

13,500

9,400

14,500

9,300

15,200

9,500

77.0

11,200

8,800

11,600

8,700

12,300

9,000

12,800

9,000

13,200

9,300

14,200

9,200

15,000

9,400

82.0

10,900

8,700

11,400

8,600

12,000

8,900

12,500

8,800

13,000

9,200

14,000

9,100

15,000

9,400

86.0

10,700

8,500

11,200

8,600

11,800

8,800

12,300

8,700

12,700

9,100

13,700

9,000

14,500

9,200

91.0

10,500

8,500

10,900

8,400

11,700

8,700

12,100

8,700

12,400

9,000

13,400

8,900

14,200

9,100

95.0

10,400

8,400

10,800

8,400

11,400

8,600

11,900

8,600

12,300

8,900

13,200

8,800

13,900

9,000

100.0

10,200

8,300

10,600

8,300

11,200

8,500

11,700

8,500

12,100

8,800

13,000

8,700

13,700

8,900

104.0

10,100

8,200

10,300

8,100

10,900

8,400

11,600

8,400

11,900

8,800

12,700

8,600

13,400

8,800

110.0

9,800

8,100

10,000

8,000

10,600

8,300

11,200

8,300

11,500

8,600

12,400

8,500

13,000

8,700

68.0

14,500

10,500

15,000

10,400

16,000

10,800

16,700

10,700

17,200

11,000

18,700

11,000

19,500

11,100

73.0

14,200

10,300

14,800

10,300

15,700

10,600

16,300

10,500

16,900

10,900

18,200

10,800

19,100

11,000

77.0

14,100

10,200

14,500

10,200

15,500

10,500

16,100

10,400

16,600

10,800

17,900

10,700

18,800

10,900

82.0

13,800

10,100

14,300

10,100

15,100

10,400

15,700

10,300

16,300

10,600

17,600

10,600

18,900

10,900

86.0

13,500

9,900

14,100

10,000

14,800

10,200

15,400

10,100

16,000

10,500

17,200

10,400

18,300

10,700

91.0

13,200

9,800

13,700

9,800

14,700

10,100

15,200

10,000

15,600

10,400

16,900

10,300

17,900

10,500

95.0

13,000

9,700

13,600

9,700

14,300

10,000

15,000

9,900

15,500

10,300

16,600

10,200

17,500

10,400

100.0

12,800

9,600

13,300

9,600

14,100

9,900

14,800

9,800

15,200

10,200

16,300

10,100

17,200

10,200

104.0

12,700

9,500

12,900

9,400

13,700

9,700

14,500

9,700

14,900

10,100

15,900

9,900

16,800

10,100

110.0

12,300

9,300

12,600

9,200

13,300

9,500

14,100

9,500

14,500

9,900

15,600

9,800

16,400

10,000

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-44

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PLFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

11,500

9,800

11,900

9,700

12,800

10,100

13,300

10,000

13,700

10,400

14,800

10,400

15,500

10,600

73.0

11,300

9,700

11,700

9,600

12,500

10,000

13,000

9,900

13,500

10,400

14,500

10,300

15,200

10,500

77.0

11,200

9,600

11,600

9,600

12,300

9,900

12,800

9,900

13,200

10,300

14,200

10,200

15,000

10,400

82.0

10,900

9,500

11,400

9,500

12,000

9,800

12,500

9,700

13,000

10,200

14,000

10,100

15,000

10,400

86.0

10,700

9,400

11,200

9,400

11,800

9,700

12,300

9,700

12,700

10,100

13,700

10,000

14,500

10,300

91.0

10,500

9,300

10,900

9,300

11,700

9,600

12,100

9,600

12,400

10,000

13,400

9,900

14,200

10,200

95.0

10,400

9,200

10,800

9,200

11,400

9,500

11,900

9,500

12,300

9,900

13,200

9,800

13,900

10,100

100.0

10,200

9,200

10,600

9,100

11,200

9,500

11,700

9,400

12,100

9,800

13,000

9,700

13,700

10,000

104.0

10,100

9,100

10,300

9,000

10,900

9,300

11,600

9,400

11,900

9,800

12,700

9,600

13,400

9,900

110.0

9,800

9,000

10,000

8,900

10,600

9,200

11,200

9,200

11,500

9,600

12,400

9,500

13,000

9,800

68.0

14,500

11,900

15,000

11,900

16,000

12,300

16,700

12,200

17,200

12,700

18,700

12,600

19,500

12,900

73.0

14,200

11,800

14,800

11,800

15,700

12,200

16,300

12,100

16,900

12,600

18,200

12,500

19,100

12,800

77.0

14,100

11,700

14,500

11,700

15,500

12,100

16,100

12,000

16,600

12,500

17,900

12,300

18,800

12,600

82.0

13,800

11,600

14,300

11,500

15,100

11,900

15,700

11,900

16,300

12,400

17,600

12,300

18,900

12,700

86.0

13,500

11,400

14,100

11,400

14,800

11,800

15,400

11,700

16,000

12,200

17,200

12,100

18,300

12,500

91.0

13,200

11,300

13,700

11,300

14,700

11,700

15,200

11,700

15,600

12,100

16,900

12,000

17,900

12,300

95.0

13,000

11,200

13,600

11,200

14,300

11,600

15,000

11,600

15,500

12,000

16,600

11,900

17,500

12,200

100.0

12,800

11,100

13,300

11,100

14,100

11,500

14,800

11,500

15,200

11,900

16,300

11,800

17,200

12,100

104.0

12,700

11,100

12,900

10,900

13,700

11,300

14,500

11,400

14,900

11,800

15,900

11,700

16,800

12,000

110.0

12,300

10,900

12,600

10,800

13,300

11,200

14,100

11,200

14,500

11,700

15,600

11,600

16,400

11,800

68.0

17,500

14,200

18,100

14,200

19,300

14,700

20,100

14,600

20,700

15,200

22,500

15,100

23,400

15,400

73.0

17,100

14,100

17,800

14,100

18,900

14,500

19,700

14,500

20,400

15,100

22,000

14,900

23,100

15,200

77.0

16,900

14,000

17,500

13,900

18,600

14,400

19,400

14,300

20,000

14,900

21,500

14,800

22,700

15,100

82.0

16,600

13,800

17,200

13,800

18,200

14,300

18,900

14,200

19,600

14,800

21,200

14,600

22,800

15,100

86.0

16,200

13,700

16,900

13,700

17,900

14,100

18,600

14,000

19,300

14,600

20,700

14,500

22,000

14,900

91.0

16,000

13,500

16,500

13,500

17,600

14,000

18,400

13,900

18,800

14,500

20,300

14,300

21,500

14,700

95.0

15,700

13,400

16,300

13,400

17,200

13,800

18,100

13,800

18,700

14,400

20,000

14,200

21,100

14,600

100.0

15,400

13,300

16,100

13,300

17,000

13,700

17,800

13,700

18,300

14,200

19,600

14,100

20,700

14,400

104.0

15,300

13,200

15,600

13,100

16,500

13,500

17,500

13,600

18,000

14,100

19,200

13,900

20,300

14,300

110.0

14,800

13,000

15,100

12,900

16,100

13,400

17,000

13,400

17,500

13,900

18,800

13,800

19,700

14,100

68.0

23,000

17,500

23,900

17,500

25,500

18,100

26,500

17,900

27,300

18,600

29,700

18,500

31,000

18,700

73.0

22,600

17,300

23,500

17,300

25,000

17,800

26,000

17,700

26,900

18,400

29,000

18,200

30,400

18,500

77.0

22,400

17,200

23,100

17,100

24,600

17,700

25,600

17,500

26,500

18,200

28,400

18,000

30,000

18,400

82.0

21,900

16,900

22,700

16,900

24,100

17,400

25,000

17,300

25,900

18,000

28,000

17,800

30,100

18,400

86.0

21,400

16,700

22,400

16,700

23,600

17,200

24,600

17,100

25,400

17,800

27,400

17,600

29,100

18,000

91.0

21,100

16,500

21,800

16,500

23,300

17,100

24,200

17,000

24,900

17,500

26,800

17,400

28,400

17,800

95.0

20,700

16,400

21,600

16,400

22,700

16,800

23,900

16,800

24,700

17,500

26,400

17,200

27,900

17,600

100.0

20,400

16,200

21,200

16,200

22,400

16,700

23,500

16,600

24,100

17,200

25,900

17,100

27,300

17,400

104.0

20,200

16,100

20,600

15,900

21,800

16,400

23,100

16,500

23,800

17,100

25,400

16,800

26,800

17,200

110.0

19,500

15,800

20,000

15,600

21,200

16,200

22,400

16,200

23,100

16,800

24,900

16,700

26,000

17,000

68.0

29,000

21,000

30,000

21,000

32,100

21,700

33,300

21,400

34,400

22,200

37,300

22,100

38,900

22,300

73.0

28,400

20,700

29,500

20,700

31,400

21,300

32,700

21,100

33,800

21,900

36,500

21,800

38,300

22,100

77.0

28,100

20,600

29,100

20,500

31,000

21,100

32,200

20,900

33,300

21,700

35,700

21,500

37,700

21,800

82.0

27,500

20,300

28,600

20,200

30,300

20,800

31,500

20,600

32,600

21,400

35,200

21,200

37,800

21,900

86.0

26,900

20,000

28,100

20,000

29,700

20,500

30,900

20,300

32,000

21,100

34,400

20,900

36,600

21,400

91.0

26,500

19,700

27,400

19,700

29,300

20,300

30,500

20,200

31,300

20,800

33,700

20,700

35,800

21,100

95.0

26,100

19,500

27,100

19,500

28,600

20,000

30,000

20,000

31,000

20,700

33,100

20,400

35,000

20,800

100.0

25,600

19,300

26,700

19,300

28,200

19,800

29,500

19,800

30,300

20,400

32,600

20,200

34,400

20,600

104.0

25,300

19,200

25,900

18,900

27,400

19,500

29,100

19,600

29,900

20,200

31,900

19,900

33,600

20,300

110.0

24,500

18,800

25,100

18,600

26,700

19,100

28,200

19,200

29,000

19,900

31,300

19,700

32,700

20,000

68.0

34,600

26,600

35,800

26,500

38,300

27,500

39,800

27,300

41,000

28,300

44,500

28,100

46,500

28,500

73.0

33,900

26,300

35,200

26,300

37,500

27,100

39,000

26,900

40,400

28,000

43,500

27,700

45,700

28,200

77.0

33,500

26,100

34,700

26,000

36,900

26,900

38,400

26,700

39,700

27,700

42,600

27,400

45,000

28,000

82.0

32,800

25,800

34,100

25,700

36,100

26,500

37,500

26,300

38,900

27,400

42,000

27,200

45,100

28,000

86.0

32,100

25,400

33,500

25,500

35,400

26,200

36,800

26,000

38,200

27,100

41,100

26,800

43,600

27,500

91.0

31,600

25,200

32,700

25,100

35,000

26,000

36,400

25,800

37,300

26,700

40,300

26,500

42,700

27,200

95.0

31,100

24,900

32,400

24,900

34,100

25,600

35,800

25,600

37,000

26,600

39,500

26,200

41,800

26,900

100.0

30,600

24,700

31,800

24,700

33,600

25,400

35,200

25,400

36,200

26,300

38,900

26,000

41,000

26,600

104.0

30,200

24,500

30,900

24,200

32,700

25,000

34,700

25,100

35,600

26,100

38,000

25,700

40,100

26,300

110.0

29,300

24,100

30,000

23,800

31,800

24,700

33,600

24,700

34,600

25,600

37,300

25,400

39,100

25,900

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-45

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PCFY-P-NGMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,500

10,900

15,000

10,900

16,000

11,300

16,700

11,200

17,200

11,600

18,700

11,500

19,500

11,700

73.0

14,200

10,800

14,800

10,800

15,700

11,100

16,300

11,000

16,900

11,400

18,200

11,400

19,100

11,500

77.0

14,100

10,700

14,500

10,700

15,500

11,000

16,100

10,900

16,600

11,300

17,900

11,200

18,800

11,400

82.0

13,800

10,600

14,300

10,500

15,100

10,800

15,700

10,800

16,300

11,200

17,600

11,100

18,900

11,400

86.0

13,500

10,400

14,100

10,400

14,800

10,700

15,400

10,600

16,000

11,100

17,200

11,000

18,300

11,200

91.0

13,200

10,300

13,700

10,300

14,700

10,600

15,200

10,600

15,600

10,900

16,900

10,800

17,900

11,100

95.0

13,000

10,200

13,600

10,200

14,300

10,500

15,000

10,500

15,500

10,900

16,600

10,700

17,500

11,000

100.0

12,800

10,100

13,300

10,100

14,100

10,400

14,800

10,400

15,200

10,700

16,300

10,600

17,200

10,800

104.0

12,700

10,000

12,900

9,900

13,700

10,200

14,500

10,300

14,900

10,600

15,900

10,500

16,800

10,700

110.0

12,300

9,800

12,600

9,700

13,300

10,100

14,100

10,100

14,500

10,400

15,600

10,400

16,400

10,600

68.0

23,000

17,000

23,900

16,900

25,500

17,500

26,500

17,300

27,300

17,900

29,700

17,900

31,000

18,000

73.0

22,600

16,700

23,500

16,700

25,000

17,200

26,000

17,100

26,900

17,700

29,000

17,600

30,400

17,800

77.0

22,400

16,600

23,100

16,500

24,600

17,100

25,600

16,900

26,500

17,500

28,400

17,300

30,000

17,700

82.0

21,900

16,400

22,700

16,300

24,100

16,800

25,000

16,700

25,900

17,300

28,000

17,200

30,100

17,700

86.0

21,400

16,100

22,400

16,200

23,600

16,600

24,600

16,500

25,400

17,100

27,400

16,900

29,100

17,300

91.0

21,100

16,000

21,800

15,900

23,300

16,500

24,200

16,300

24,900

16,900

26,800

16,700

28,400

17,100

95.0

20,700

15,800

21,600

15,800

22,700

16,200

23,900

16,200

24,700

16,800

26,400

16,500

27,900

16,900

100.0

20,400

15,600

21,200

15,600

22,400

16,000

23,500

16,000

24,100

16,500

25,900

16,400

27,300

16,700

104.0

20,200

15,500

20,600

15,300

21,800

15,800

23,100

15,800

23,800

16,400

25,400

16,200

26,800

16,500

110.0

19,500

15,200

20,000

15,000

21,200

15,500

22,400

15,500

23,100

16,100

24,900

16,000

26,000

16,200

68.0

29,000

20,800

30,000

20,800

32,100

21,400

33,300

21,200

34,400

21,900

37,300

21,900

38,900

22,100

73.0

28,400

20,500

29,500

20,500

31,400

21,100

32,700

20,900

33,800

21,700

36,500

21,500

38,300

21,800

77.0

28,100

20,400

29,100

20,300

31,000

20,900

32,200

20,700

33,300

21,400

35,700

21,200

37,700

21,600

82.0

27,500

20,000

28,600

20,000

30,300

20,600

31,500

20,400

32,600

21,100

35,200

21,000

37,800

21,600

86.0

26,900

19,800

28,100

19,800

29,700

20,300

30,900

20,100

32,000

20,900

34,400

20,700

36,600

21,100

91.0

26,500

19,500

27,400

19,500

29,300

20,100

30,500

19,900

31,300

20,600

33,700

20,400

35,800

20,800

95.0

26,100

19,300

27,100

19,300

28,600

19,800

30,000

19,700

31,000

20,500

33,100

20,200

35,000

20,600

100.0

25,600

19,100

26,700

19,100

28,200

19,600

29,500

19,500

30,300

20,200

32,600

20,000

34,400

20,300

104.0

25,300

18,900

25,900

18,700

27,400

19,200

29,100

19,300

29,900

20,000

31,900

19,700

33,600

20,000

110.0

24,500

18,500

25,100

18,300

26,700

18,900

28,200

18,900

29,000

19,600

31,300

19,400

32,700

19,700

68.0

34,900

25,700

36,200

25,700

38,700

26,500

40,200

26,300

41,400

27,200

44,900

27,100

46,900

27,400

73.0

34,200

25,400

35,600

25,400

37,800

26,100

39,400

25,900

40,800

26,900

43,900

26,700

46,100

27,100

77.0

33,900

25,200

35,000

25,100

37,300

25,900

38,700

25,700

40,100

26,600

43,000

26,300

45,400

26,800

82.0

33,100

24,800

34,400

24,800

36,500

25,500

37,900

25,300

39,200

26,300

42,400

26,100

45,500

26,900

86.0

32,400

24,500

33,900

24,500

35,700

25,200

37,200

25,000

38,500

26,000

41,500

25,700

44,100

26,300

91.0

31,900

24,200

33,100

24,200

35,300

25,000

36,700

24,800

37,700

25,600

40,700

25,400

43,100

26,000

95.0

31,400

24,000

32,700

24,000

34,400

24,600

36,200

24,600

37,400

25,500

39,900

25,100

42,200

25,600

100.0

30,900

23,700

32,200

23,700

33,900

24,400

35,600

24,300

36,500

25,100

39,300

24,900

41,400

25,400

104.0

30,500

23,500

31,200

23,300

33,000

24,000

35,000

24,100

36,000

24,900

38,400

24,500

40,500

25,000

110.0

29,600

23,100

30,300

22,800

32,100

23,600

33,900

23,600

34,900

24,500

37,700

24,300

39,400

24,700

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-46

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

4,500

6,100

4,500

6,600

4,700

6,800

4,600

7,000

4,800

7,600

4,800

8,000

4,800

73.0

5,800

4,500

6,000

4,500

6,400

4,600

6,700

4,600

6,900

4,800

7,500

4,700

7,800

4,800

77.0

5,700

4,400

5,900

4,400

6,300

4,600

6,600

4,500

6,800

4,700

7,300

4,700

7,700

4,800

82.0

5,600

4,400

5,800

4,400

6,200

4,500

6,400

4,500

6,700

4,600

7,200

4,600

7,700

4,800

86.0

5,500

4,300

5,700

4,300

6,100

4,500

6,300

4,400

6,500

4,600

7,000

4,600

7,500

4,700

91.0

5,400

4,300

5,600

4,300

6,000

4,400

6,200

4,400

6,400

4,500

6,900

4,500

7,300

4,600

95.0

5,300

4,200

5,600

4,200

5,800

4,400

6,100

4,300

6,300

4,500

6,800

4,500

7,200

4,600

100.0

5,200

4,200

5,500

4,200

5,800

4,300

6,000

4,300

6,200

4,500

6,700

4,400

7,000

4,500

104.0

5,200

4,200

5,300

4,100

5,600

4,300

5,900

4,300

6,100

4,400

6,500

4,400

6,900

4,500

110.0

5,000

4,100

5,100

4,000

5,500

4,200

5,800

4,200

5,900

4,300

6,400

4,300

6,700

4,400

68.0

7,600

5,700

7,800

5,700

8,400

5,900

8,700

5,800

9,000

6,000

9,800

6,000

10,200

6,100

73.0

7,400

5,600

7,700

5,600

8,200

5,800

8,500

5,700

8,800

6,000

9,500

5,900

10,000

6,000

77.0

7,300

5,600

7,600

5,600

8,100

5,700

8,400

5,700

8,700

5,900

9,300

5,800

9,800

6,000

82.0

7,200

5,500

7,500

5,500

7,900

5,600

8,200

5,600

8,500

5,800

9,200

5,800

9,900

6,000

86.0

7,000

5,400

7,300

5,400

7,800

5,600

8,100

5,500

8,400

5,800

9,000

5,700

9,600

5,800

91.0

6,900

5,400

7,200

5,400

7,700

5,500

8,000

5,500

8,200

5,700

8,800

5,600

9,300

5,800

95.0

6,800

5,300

7,100

5,300

7,500

5,500

7,800

5,400

8,100

5,700

8,700

5,600

9,200

5,700

100.0

6,700

5,300

7,000

5,300

7,400

5,400

7,700

5,400

7,900

5,600

8,500

5,500

9,000

5,600

104.0

6,600

5,200

6,800

5,200

7,200

5,300

7,600

5,300

7,800

5,500

8,300

5,500

8,800

5,600

110.0

6,400

5,100

6,600

5,100

7,000

5,200

7,400

5,200

7,600

5,400

8,200

5,400

8,600

5,500

68.0

11,500

9,100

11,900

9,100

12,800

9,400

13,300

9,400

13,700

9,700

14,800

9,700

15,500

9,800

73.0

11,300

9,000

11,700

9,000

12,500

9,300

13,000

9,300

13,500

9,600

14,500

9,500

15,200

9,700

77.0

11,200

9,000

11,600

8,900

12,300

9,200

12,800

9,200

13,200

9,500

14,200

9,400

15,000

9,600

82.0

10,900

8,900

11,400

8,800

12,000

9,100

12,500

9,100

13,000

9,400

14,000

9,400

15,000

9,700

86.0

10,700

8,700

11,200

8,800

11,800

9,000

12,300

9,000

12,700

9,300

13,700

9,200

14,500

9,500

91.0

10,500

8,700

10,900

8,600

11,700

9,000

12,100

8,900

12,400

9,200

13,400

9,100

14,200

9,400

95.0

10,400

8,600

10,800

8,600

11,400

8,800

11,900

8,800

12,300

9,200

13,200

9,100

13,900

9,300

100.0

10,200

8,500

10,600

8,500

11,200

8,800

11,700

8,700

12,100

9,100

13,000

9,000

13,700

9,200

104.0

10,100

8,500

10,300

8,400

10,900

8,600

11,600

8,700

11,900

9,000

12,700

8,900

13,400

9,100

110.0

9,800

8,300

10,000

8,200

10,600

8,500

11,200

8,500

11,500

8,900

12,400

8,800

13,000

9,000

68.0

14,500

11,000

15,000

11,000

16,000

11,300

16,700

11,200

17,200

11,700

18,700

11,600

19,500

11,800

73.0

14,200

10,800

14,800

10,800

15,700

11,200

16,300

11,100

16,900

11,500

18,200

11,400

19,100

11,600

77.0

14,100

10,800

14,500

10,700

15,500

11,100

16,100

11,000

16,600

11,400

17,900

11,300

18,800

11,500

82.0

13,800

10,600

14,300

10,600

15,100

10,900

15,700

10,900

16,300

11,300

17,600

11,200

18,900

11,500

86.0

13,500

10,500

14,100

10,500

14,800

10,800

15,400

10,700

16,000

11,200

17,200

11,100

18,300

11,300

91.0

13,200

10,400

13,700

10,400

14,700

10,700

15,200

10,600

15,600

11,000

16,900

10,900

17,900

11,200

95.0

13,000

10,300

13,600

10,300

14,300

10,600

15,000

10,500

15,500

11,000

16,600

10,800

17,500

11,000

100.0

12,800

10,200

13,300

10,200

14,100

10,500

14,800

10,400

15,200

10,800

16,300

10,700

17,200

10,900

104.0

12,700

10,100

12,900

10,000

13,700

10,300

14,500

10,400

14,900

10,700

15,900

10,600

16,800

10,800

110.0

12,300

9,900

12,600

9,800

13,300

10,100

14,100

10,200

14,500

10,500

15,600

10,500

16,400

10,700

68.0

17,500

13,900

18,100

13,900

19,300

14,400

20,100

14,300

20,700

14,800

22,500

14,800

23,400

15,000

73.0

17,100

13,800

17,800

13,800

18,900

14,200

19,700

14,100

20,400

14,700

22,000

14,600

23,100

14,900

77.0

16,900

13,700

17,500

13,600

18,600

14,100

19,400

14,000

20,000

14,600

21,500

14,400

22,700

14,700

82.0

16,600

13,500

17,200

13,500

18,200

13,900

18,900

13,800

19,600

14,400

21,200

14,300

22,800

14,800

86.0

16,200

13,400

16,900

13,400

17,900

13,800

18,600

13,700

19,300

14,300

20,700

14,100

22,000

14,500

91.0

16,000

13,200

16,500

13,200

17,600

13,700

18,400

13,600

18,800

14,100

20,300

14,000

21,500

14,300

95.0

15,700

13,100

16,300

13,100

17,200

13,500

18,100

13,500

18,700

14,000

20,000

13,800

21,100

14,200

100.0

15,400

13,000

16,100

13,000

17,000

13,400

17,800

13,400

18,300

13,900

19,600

13,700

20,700

14,100

104.0

15,300

12,900

15,600

12,800

16,500

13,200

17,500

13,300

18,000

13,800

19,200

13,600

20,300

13,900

110.0

14,800

12,700

15,100

12,600

16,100

13,000

17,000

13,000

17,500

13,600

18,800

13,400

19,700

13,700

68.0

23,000

17,300

23,900

17,300

25,500

17,900

26,500

17,700

27,300

18,300

29,700

18,300

31,000

18,500

73.0

22,600

17,100

23,500

17,100

25,000

17,600

26,000

17,500

26,900

18,200

29,000

18,000

30,400

18,300

77.0

22,400

17,000

23,100

16,900

24,600

17,500

25,600

17,300

26,500

18,000

28,400

17,800

30,000

18,100

82.0

21,900

16,700

22,700

16,700

24,100

17,200

25,000

17,100

25,900

17,700

28,000

17,600

30,100

18,200

86.0

21,400

16,500

22,400

16,500

23,600

17,000

24,600

16,900

25,400

17,500

27,400

17,400

29,100

17,800

91.0

21,100

16,300

21,800

16,300

23,300

16,900

24,200

16,700

24,900

17,300

26,800

17,200

28,400

17,600

95.0

20,700

16,200

21,600

16,200

22,700

16,600

23,900

16,600

24,700

17,200

26,400

17,000

27,900

17,400

100.0

20,400

16,000

21,200

16,000

22,400

16,500

23,500

16,400

24,100

17,000

25,900

16,800

27,300

17,200

104.0

20,200

15,900

20,600

15,700

21,800

16,200

23,100

16,300

23,800

16,900

25,400

16,600

26,800

17,000

110.0

19,500

15,600

20,000

15,400

21,200

15,900

22,400

16,000

23,100

16,600

24,900

16,400

26,000

16,700

68.0

29,000

23,300

30,000

23,200

32,100

24,000

33,300

23,900

34,400

24,800

37,300

24,600

38,900

25,000

73.0

28,400

23,000

29,500

22,900

31,400

23,700

32,700

23,600

33,800

24,600

36,500

24,300

38,300

24,800

77.0

28,100

22,800

29,100

22,700

31,000

23,500

32,200

23,400

33,300

24,300

35,700

24,100

37,700

24,600

82.0

27,500

22,600

28,600

22,500

30,300

23,200

31,500

23,100

32,600

24,000

35,200

23,900

37,800

24,600

86.0

26,900

22,300

28,100

22,300

29,700

23,000

30,900

22,900

32,000

23,800

34,400

23,600

36,600

24,200

91.0

26,500

22,100

27,400

22,000

29,300

22,800

30,500

22,700

31,300

23,500

33,700

23,300

35,800

24,000

95.0

26,100

21,900

27,100

21,900

28,600

22,500

30,000

22,500

31,000

23,400

33,100

23,100

35,000

23,700

100.0

25,600

21,700

26,700

21,700

28,200

22,400

29,500

22,300

30,300

23,200

32,600

22,900

34,400

23,500

104.0

25,300

21,600

25,900

21,300

27,400

22,000

29,100

22,100

29,900

23,000

31,900

22,700

33,600

23,200

110.0

24,500

21,200

25,100

21,000

26,700

21,700

28,200

21,800

29,000

22,600

31,300

22,400

32,700

22,900

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-47

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-1. Cooling CapacityPUHY-P264~360TSHMU/YSHMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

4,400

6,100

4,400

6,600

4,600

6,800

4,500

7,000

4,700

7,600

4,700

8,000

4,700

73.0

5,800

4,400

6,000

4,400

6,400

4,500

6,700

4,500

6,900

4,700

7,500

4,600

7,800

4,700

77.0

5,700

4,400

5,900

4,300

6,300

4,500

6,600

4,400

6,800

4,600

7,300

4,600

7,700

4,700

82.0

5,600

4,300

5,800

4,300

6,200

4,400

6,400

4,400

6,700

4,600

7,200

4,500

7,700

4,700

86.0

5,500

4,200

5,700

4,200

6,100

4,400

6,300

4,300

6,500

4,500

7,000

4,500

7,500

4,600

91.0

5,400

4,200

5,600

4,200

6,000

4,300

6,200

4,300

6,400

4,400

6,900

4,400

7,300

4,500

95.0

5,300

4,200

5,600

4,200

5,800

4,300

6,100

4,300

6,300

4,400

6,800

4,400

7,200

4,500

100.0

5,200

4,100

5,500

4,100

5,800

4,200

6,000

4,200

6,200

4,400

6,700

4,300

7,000

4,400

104.0

5,200

4,100

5,300

4,000

5,600

4,200

5,900

4,200

6,100

4,300

6,500

4,300

6,900

4,400

110.0

5,000

4,000

5,100

4,000

5,500

4,100

5,800

4,100

5,900

4,200

6,400

4,200

6,700

4,300

68.0

7,600

5,800

7,800

5,800

8,400

6,000

8,700

5,900

9,000

6,100

9,800

6,100

10,200

6,200

73.0

7,400

5,700

7,700

5,700

8,200

5,900

8,500

5,800

8,800

6,100

9,500

6,000

10,000

6,100

77.0

7,300

5,700

7,600

5,600

8,100

5,800

8,400

5,800

8,700

6,000

9,300

5,900

9,800

6,100

82.0

7,200

5,600

7,500

5,600

7,900

5,800

8,200

5,700

8,500

5,900

9,200

5,900

9,900

6,100

86.0

7,000

5,500

7,300

5,500

7,800

5,700

8,100

5,600

8,400

5,900

9,000

5,800

9,600

6,000

91.0

6,900

5,500

7,200

5,400

7,700

5,600

8,000

5,600

8,200

5,800

8,800

5,800

9,300

5,900

95.0

6,800

5,400

7,100

5,400

7,500

5,600

7,800

5,600

8,100

5,800

8,700

5,700

9,200

5,800

100.0

6,700

5,400

7,000

5,400

7,400

5,500

7,700

5,500

7,900

5,700

8,500

5,600

9,000

5,800

104.0

6,600

5,300

6,800

5,300

7,200

5,400

7,600

5,500

7,800

5,600

8,300

5,600

8,800

5,700

110.0

6,400

5,200

6,600

5,200

7,000

5,300

7,400

5,400

7,600

5,600

8,200

5,500

8,600

5,600

68.0

11,500

8,000

11,900

8,000

12,800

8,200

13,300

8,200

13,700

8,400

14,800

8,400

15,500

8,500

73.0

11,300

7,900

11,700

7,900

12,500

8,100

13,000

8,000

13,500

8,300

14,500

8,300

15,200

8,300

77.0

11,200

7,800

11,600

7,800

12,300

8,000

12,800

7,900

13,200

8,200

14,200

8,100

15,000

8,200

82.0

10,900

7,700

11,400

7,700

12,000

7,900

12,500

7,800

13,000

8,100

14,000

8,000

15,000

8,300

86.0

10,700

7,600

11,200

7,600

11,800

7,800

12,300

7,700

12,700

8,000

13,700

7,900

14,500

8,100

91.0

10,500

7,500

10,900

7,500

11,700

7,700

12,100

7,600

12,400

7,800

13,400

7,800

14,200

7,900

95.0

10,400

7,400

10,800

7,400

11,400

7,500

11,900

7,500

12,300

7,800

13,200

7,700

13,900

7,800

100.0

10,200

7,300

10,600

7,300

11,200

7,500

11,700

7,400

12,100

7,700

13,000

7,600

13,700

7,700

104.0

10,100

7,200

10,300

7,100

10,900

7,300

11,600

7,400

11,900

7,600

12,700

7,500

13,400

7,600

110.0

9,800

7,100

10,000

7,000

10,600

7,200

11,200

7,200

11,500

7,400

12,400

7,400

13,000

7,500

68.0

14,500

10,200

15,000

10,200

16,000

10,500

16,700

10,400

17,200

10,700

18,700

10,700

19,500

10,800

73.0

14,200

10,000

14,800

10,000

15,700

10,300

16,300

10,200

16,900

10,600

18,200

10,500

19,100

10,600

77.0

14,100

10,000

14,500

9,900

15,500

10,200

16,100

10,100

16,600

10,500

17,900

10,400

18,800

10,500

82.0

13,800

9,800

14,300

9,800

15,100

10,000

15,700

10,000

16,300

10,300

17,600

10,300

18,900

10,600

86.0

13,500

9,700

14,100

9,700

14,800

9,900

15,400

9,800

16,000

10,200

17,200

10,100

18,300

10,300

91.0

13,200

9,500

13,700

9,500

14,700

9,800

15,200

9,700

15,600

10,000

16,900

10,000

17,900

10,200

95.0

13,000

9,400

13,600

9,400

14,300

9,600

15,000

9,600

15,500

10,000

16,600

9,800

17,500

10,000

100.0

12,800

9,300

13,300

9,300

14,100

9,500

14,800

9,500

15,200

9,800

16,300

9,700

17,200

9,900

104.0

12,700

9,200

12,900

9,100

13,700

9,400

14,500

9,400

14,900

9,700

15,900

9,600

16,800

9,700

110.0

12,300

9,000

12,600

8,900

13,300

9,200

14,100

9,200

14,500

9,500

15,600

9,500

16,400

9,600

68.0

17,500

12,500

18,100

12,500

19,300

12,900

20,100

12,800

20,700

13,200

22,500

13,200

23,400

13,300

73.0

17,100

12,300

17,800

12,300

18,900

12,700

19,700

12,600

20,400

13,000

22,000

12,900

23,100

13,100

77.0

16,900

12,200

17,500

12,200

18,600

12,600

19,400

12,400

20,000

12,900

21,500

12,800

22,700

13,000

82.0

16,600

12,000

17,200

12,000

18,200

12,400

18,900

12,200

19,600

12,700

21,200

12,600

22,800

13,000

86.0

16,200

11,900

16,900

11,900

17,900

12,200

18,600

12,100

19,300

12,500

20,700

12,400

22,000

12,700

91.0

16,000

11,700

16,500

11,700

17,600

12,100

18,400

12,000

18,800

12,400

20,300

12,300

21,500

12,500

95.0

15,700

11,600

16,300

11,600

17,200

11,900

18,100

11,900

18,700

12,300

20,000

12,100

21,100

12,400

100.0

15,400

11,500

16,100

11,500

17,000

11,800

17,800

11,700

18,300

12,100

19,600

12,000

20,700

12,200

104.0

15,300

11,400

15,600

11,200

16,500

11,600

17,500

11,600

18,000

12,000

19,200

11,800

20,300

12,000

110.0

14,800

11,100

15,100

11,000

16,100

11,400

17,000

11,400

17,500

11,800

18,800

11,700

19,700

11,800

68.0

23,000

16,100

23,900

16,000

25,500

16,500

26,500

16,400

27,300

16,900

29,700

16,900

31,000

17,000

73.0

22,600

15,800

23,500

15,800

25,000

16,300

26,000

16,100

26,900

16,700

29,000

16,600

30,400

16,700

77.0

22,400

15,700

23,100

15,600

24,600

16,100

25,600

15,900

26,500

16,500

28,400

16,300

30,000

16,500

82.0

21,900

15,400

22,700

15,400

24,100

15,800

25,000

15,700

25,900

16,200

28,000

16,100

30,100

16,600

86.0

21,400

15,200

22,400

15,200

23,600

15,600

24,600

15,400

25,400

16,000

27,400

15,900

29,100

16,200

91.0

21,100

15,000

21,800

15,000

23,300

15,400

24,200

15,300

24,900

15,800

26,800

15,600

28,400

15,900

95.0

20,700

14,800

21,600

14,800

22,700

15,100

23,900

15,100

24,700

15,700

26,400

15,400

27,900

15,700

100.0

20,400

14,600

21,200

14,700

22,400

15,000

23,500

14,900

24,100

15,400

25,900

15,300

27,300

15,500

104.0

20,200

14,500

20,600

14,300

21,800

14,700

23,100

14,800

23,800

15,200

25,400

15,000

26,800

15,300

110.0

19,500

14,200

20,000

14,000

21,200

14,400

22,400

14,500

23,100

14,900

24,900

14,800

26,000

15,000

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-48

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-4-2. Heating CapacityPUHY-P264~360TSHMU/YSHMU with All Indoor Units


SHC : Sensible Heat Capacity(BTU/h)
Model
size

06

08

12

15

18

24

Entering air temp.

SHC : Sensible Heat Capacity(BTU/h)


Model
size

Outdoor

Entering air temp.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

81degF D.B.

air temp.

59degF D.B.

70degF D.B.

77degF D.B.

degF W.B.

SHC

SHC

SHC

SHC

degF W.B.

SHC

SHC

SHC

81degF D.B.
SHC

5.0

4,100

4,100

4,100

4,000

5.0

20,700

20,700

20,400

20,000

14.0

4,900

4,800

4,800

4,700

14.0

24,400

23,800

23,800

23,400

23.0

5,600

5,400

5,400

5,200

23.0

28,100

27,100

27,200

26,000

32.0

6,400

6,100

5,600

5,200

37.0

6,800

6,700

5,600

5,200

30

32.0

31,800

30,300

28,200

26,000

37.0

34,100

34,000

28,200

26,000

43.0

7,300

6,700

5,600

5,200

43.0

36,300

34,000

28,200

26,000

46.0

7,600

6,700

5,600

5,200

46.0

37,800

34,000

28,200

26,000

50.0

7,900

6,700

5,600

5,200

50.0

39,300

34,000

28,200

26,000

55.0

8,200

6,700

5,600

5,200

55.0

40,900

34,000

28,200

26,000

60.0

8,200

6,700

5,600

5,200

60.0

40,900

34,000

28,200

26,000

65.0

8,200

6,700

5,600

5,200

65.0

40,900

34,000

28,200

26,000
23,500

5.0

5,400

5,400

5,300

5,200

5.0

24,200

24,200

23,900

14.0

6,300

6,200

6,200

6,100

14.0

28,500

27,900

27,800

27,300

23.0

7,300

7,000

7,100

6,700

23.0

32,900

31,700

31,800

30,400

32.0

8,300

7,900

7,300

6,700

37.0

8,900

9,000

7,300

6,700

36

32.0

37,200

35,400

33,000

30,400

37.0

39,900

40,000

33,000

30,400

43.0

9,400

9,000

7,300

6,700

43.0

42,500

40,000

33,000

30,400

46.0

9,800

9,000

7,300

6,700

46.0

44,300

40,000

33,000

30,400

50.0

10,200

9,000

7,300

6,700

50.0

46,000

40,000

33,000

30,400

55.0

10,600

9,000

7,300

6,700

55.0

47,800

40,000

33,000

30,400

60.0

10,600

9,000

7,300

6,700

60.0

47,800

40,000

33,000

30,400

65.0

10,600

9,000

7,300

6,700

65.0

47,800

40,000

33,000

30,400
31,700

5.0

8,300

8,300

8,200

8,000

5.0

32,600

32,600

32,200

14.0

9,700

9,500

9,500

9,300

14.0

38,500

37,700

37,600

36,900

23.0

11,200

10,800

10,900

10,400

23.0

44,400

42,800

42,900

41,000

32.0

12,700

12,100

11,300

10,400

37.0

13,600

13,500

11,300

10,400

48

32.0

50,300

47,800

44,600

41,000

37.0

53,900

54,000

44,600

41,000
41,000

43.0

14,500

13,500

11,300

10,400

43.0

57,400

54,000

44,600

46.0

15,100

13,500

11,300

10,400

46.0

59,800

54,000

44,600

41,000

50.0

15,700

13,500

11,300

10,400

50.0

62,100

54,000

44,600

41,000

55.0

16,300

13,500

11,300

10,400

55.0

64,600

54,000

44,600

41,000

60.0

16,300

13,500

11,300

10,400

60.0

64,600

54,000

44,600

41,000

65.0

16,300

13,500

11,300

10,400

65.0

64,600

54,000

44,600

41,000

5.0

10,300

10,300

10,200

10,000

5.0

36,400

36,400

35,900

35,300

14.0

12,200

11,900

11,900

11,700

14.0

42,900

42,000

41,900

41,100

23.0

14,100

13,600

13,600

13,000

23.0

49,500

47,700

47,800

45,700

32.0

15,900

15,100

14,100

13,000

37.0

17,000

17,000

14,100

13,000

54

32.0

56,000

53,300

49,700

45,700

37.0

60,000

60,000

49,700

45,700

43.0

18,200

17,000

14,100

13,000

43.0

63,900

60,000

49,700

45,700

46.0

18,900

17,000

14,100

13,000

46.0

66,600

60,000

49,700

45,700

50.0

19,700

17,000

14,100

13,000

50.0

69,200

60,000

49,700

45,700

55.0

20,400

17,000

14,100

13,000

55.0

71,900

60,000

49,700

45,700

60.0

20,400

17,000

14,100

13,000

60.0

71,900

60,000

49,700

45,700

65.0

20,400

17,000

14,100

13,000

65.0

71,900

60,000

49,700

45,700
46,900

5.0

12,200

12,200

12,000

11,800

5.0

48,300

48,400

47,700

14.0

14,400

14,100

14,000

13,800

14.0

57,000

55,800

55,700

54,600

23.0

16,600

16,000

16,000

15,300

23.0

65,800

63,400

63,500

60,700

32.0

18,800

17,900

16,600

15,300

37.0

20,100

20,000

16,600

15,300

72

32.0

74,500

70,900

66,000

60,700

37.0

79,800

80,000

66,000

60,700

43.0

21,400

20,000

16,600

15,300

43.0

85,000

80,000

66,000

60,700

46.0

22,300

20,000

16,600

15,300

46.0

88,500

80,000

66,000

60,700

50.0

23,200

20,000

16,600

15,300

50.0

92,000

80,000

66,000

60,700

55.0

24,100

20,000

16,600

15,300

55.0

95,600

80,000

66,000

60,700

60.0

24,100

20,000

16,600

15,300

60.0

95,600

80,000

66,000

60,700

65.0

24,100

20,000

16,600

15,300

65.0

95,600

80,000

66,000

60,700
63,500

5.0

16,300

16,300

16,100

15,800

5.0

65,500

65,500

64,600

14.0

19,300

18,800

18,800

18,500

14.0

77,300

75,600

75,400

74,000

23.0

22,200

21,400

21,500

20,500

23.0

89,100

85,900

86,100

82,300
82,300

32.0

25,200

23,900

22,300

20,500

37.0

26,900

25,400

22,300

20,500

43.0

28,700

27,000

22,300

20,500

96

32.0

100,900

96,000

89,400

37.0

108,000

108,000

89,400

82,300

43.0

115,200

108,000

89,400

82,300

46.0

29,900

27,000

22,300

20,500

46.0

119,900

108,000

89,400

82,300

50.0

31,100

27,000

22,300

20,500

50.0

124,600

108,000

89,400

82,300

55.0

32,300

27,000

22,300

20,500

55.0

129,500

108,000

89,400

82,300

60.0

32,300

27,000

22,300

20,500

60.0

129,500

108,000

89,400

82,300

65.0

129,500

108,000

89,400

82,300

65.0

32,300

27,000

22,300

20,500

5.0

18,200

18,200

17,900

17,600

14.0

21,400

21,000

20,900

20,600

23.0

24,700

23,900

23,900

22,800

32.0

28,000

26,700

24,800

22,800

37.0

30,000

28,300

24,800

22,800

43.0

32,000

30,000

24,800

22,800

46.0

33,300

30,000

24,800

22,800

50.0

34,600

30,000

24,800

22,800

55.0

36,000

30,000

24,800

22,800

60.0

36,000

30,000

24,800

22,800

65.0

36,000

30,000

24,800

22,800

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

27

Outdoor

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-49

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5. Cooing and Heating Capacity with PUMY-P36~48NHMU-A


1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PEFY-P-NMSU-E
CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

80degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

67degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,800

5,200

6,000

5,200

6,300

5,400

6,500

5,300

6,700

5,600

7,100

5,500

7,400

5,600

73.0

5,700

5,200

5,900

5,200

6,300

5,400

6,500

5,300

6,600

5,500

7,000

5,400

7,400

5,600

77.0

5,600

5,200

5,800

5,100

6,200

5,300

6,400

5,300

6,600

5,500

6,900

5,400

7,300

5,600

82.0

5,600

5,100

5,800

5,100

6,100

5,300

6,300

5,300

6,500

5,500

6,800

5,400

7,200

5,500

86.0

5,500

5,100

5,700

5,100

6,000

5,300

6,200

5,200

6,400

5,400

6,800

5,400

7,100

5,500

91.0

5,400

5,000

5,600

5,000

5,900

5,200

6,100

5,200

6,300

5,400

6,700

5,300

7,100

5,500

95.0

5,300

5,000

5,500

5,000

5,900

5,200

6,000

5,200

6,200

5,400

6,600

5,300

7,000

5,500

100.0

5,200

5,000

5,400

4,900

5,800

5,200

5,900

5,100

6,100

5,400

6,500

5,300

6,900

5,400

104.0

5,000

4,900

5,200

4,900

5,700

5,100

5,900

5,100

6,100

5,300

6,500

5,200

6,900

5,400

110.0

4,900

4,800

5,100

4,800

5,500

5,100

5,700

5,000

5,900

5,300

6,300

5,200

6,800

5,400

68.0

7,700

6,700

7,900

6,700

8,400

7,000

8,600

6,900

8,900

7,200

9,400

7,000

9,800

7,200

73.0

7,600

6,700

7,800

6,700

8,300

6,900

8,500

6,800

8,800

7,100

9,300

7,000

9,700

7,200

77.0

7,500

6,700

7,700

6,600

8,200

6,900

8,400

6,800

8,700

7,100

9,200

6,900

9,600

7,100

82.0

7,400

6,600

7,600

6,600

8,100

6,800

8,300

6,800

8,600

7,000

9,100

6,900

9,500

7,100

86.0

7,300

6,600

7,500

6,500

8,000

6,800

8,200

6,700

8,500

7,000

9,000

6,900

9,400

7,100

91.0

7,100

6,500

7,400

6,500

7,900

6,700

8,100

6,700

8,400

7,000

8,900

6,800

9,300

7,000

95.0

7,000

6,400

7,200

6,400

7,700

6,700

8,000

6,600

8,200

6,900

8,800

6,800

9,300

7,000

100.0

6,800

6,400

7,100

6,400

7,600

6,600

7,900

6,600

8,100

6,900

8,700

6,800

9,200

7,000

104.0

6,700

6,300

6,900

6,300

7,500

6,600

7,700

6,500

8,000

6,800

8,600

6,700

9,100

7,000

110.0

6,500

6,200

6,800

6,200

7,300

6,500

7,600

6,500

7,900

6,800

8,400

6,700

8,900

6,900

68.0

11,500

9,000

11,900

8,900

12,600

9,200

13,000

9,100

13,400

9,400

14,100

9,200

14,800

9,400

73.0

11,400

8,900

11,700

8,900

12,500

9,200

12,800

9,000

13,200

9,400

13,900

9,200

14,700

9,400

77.0

11,200

8,900

11,600

8,800

12,300

9,100

12,700

9,000

13,000

9,300

13,800

9,100

14,500

9,300

82.0

11,100

8,800

11,400

8,700

12,200

9,000

12,500

8,900

12,900

9,200

13,600

9,100

14,400

9,300

86.0

10,900

8,700

11,300

8,700

12,000

9,000

12,400

8,900

12,700

9,200

13,500

9,000

14,200

9,200

91.0

10,700

8,600

11,100

8,600

11,800

8,900

12,200

8,800

12,600

9,100

13,300

8,900

14,100

9,200

95.0

10,500

8,500

10,900

8,500

11,600

8,800

12,000

8,700

12,400

9,000

13,200

8,900

13,900

9,100

100.0

10,300

8,400

10,700

8,400

11,400

8,700

11,800

8,600

12,200

9,000

13,000

8,800

13,800

9,100

104.0

10,000

8,300

10,400

8,300

11,300

8,600

11,600

8,600

12,100

8,900

12,900

8,800

13,700

9,000

110.0

9,800

8,200

10,200

8,200

11,000

8,500

11,400

8,500

11,800

8,800

12,600

8,700

13,400

8,900

68.0

14,400

10,800

14,900

10,700

15,800

11,000

16,200

10,900

16,700

11,300

17,600

11,000

18,500

11,200

73.0

14,200

10,700

14,700

10,600

15,600

11,000

16,000

10,800

16,500

11,200

17,400

10,900

18,300

11,100

77.0

14,000

10,600

14,500

10,500

15,400

10,900

15,900

10,700

16,300

11,100

17,200

10,900

18,100

11,100

82.0

13,800

10,500

14,300

10,500

15,200

10,800

15,700

10,600

16,100

11,000

17,000

10,800

17,900

11,000

86.0

13,700

10,400

14,100

10,400

15,000

10,700

15,500

10,600

15,900

10,900

16,800

10,700

17,700

10,900

91.0

13,400

10,300

13,800

10,200

14,800

10,600

15,300

10,500

15,700

10,800

16,600

10,600

17,600

10,900

95.0

13,100

10,100

13,600

10,100

14,500

10,500

15,000

10,400

15,500

10,800

16,500

10,600

17,400

10,800

100.0

12,800

10,000

13,300

10,000

14,300

10,400

14,800

10,300

15,300

10,700

16,300

10,500

17,200

10,700

104.0

12,600

9,900

13,000

9,900

14,100

10,300

14,600

10,200

15,100

10,600

16,100

10,400

17,100

10,700

110.0

12,200

9,700

12,700

9,700

13,800

10,100

14,300

10,100

14,800

10,500

15,800

10,300

16,800

10,600

68.0

17,300

13,300

17,800

13,200

18,900

13,600

19,500

13,500

20,000

13,900

21,100

13,600

22,200

13,900

73.0

17,100

13,200

17,600

13,100

18,700

13,500

19,300

13,400

19,800

13,800

20,900

13,500

22,000

13,800

77.0

16,800

13,100

17,400

13,000

18,500

13,400

19,000

13,300

19,600

13,700

20,700

13,500

21,800

13,700

82.0

16,600

13,000

17,200

12,900

18,200

13,300

18,800

13,200

19,300

13,600

20,400

13,400

21,500

13,700

86.0

16,400

12,900

16,900

12,800

18,000

13,200

18,600

13,100

19,100

13,600

20,200

13,300

21,300

13,600

91.0

16,100

12,700

16,600

12,700

17,700

13,100

18,300

13,000

18,900

13,400

20,000

13,200

21,100

13,500

95.0

15,700

12,600

16,300

12,500

17,500

13,000

18,000

12,800

18,600

13,300

19,700

13,100

20,900

13,400

100.0

15,400

12,400

16,000

12,400

17,200

12,900

17,700

12,700

18,300

13,200

19,500

13,000

20,700

13,400

104.0

15,100

12,200

15,700

12,200

16,900

12,700

17,500

12,600

18,100

13,100

19,300

12,900

20,500

13,300

110.0

14,700

12,100

15,300

12,100

16,500

12,600

17,100

12,500

17,700

13,000

18,900

12,800

20,100

13,200

68.0

23,000

17,600

23,700

17,500

25,200

18,000

25,900

17,700

26,600

18,400

28,100

18,000

29,500

18,300

73.0

22,700

17,400

23,400

17,300

24,900

17,900

25,600

17,600

26,300

18,200

27,800

17,800

29,200

18,200

77.0

22,400

17,300

23,100

17,200

24,600

17,700

25,300

17,500

26,000

18,100

27,500

17,700

28,900

18,100

82.0

22,100

17,100

22,800

17,000

24,300

17,600

25,000

17,300

25,700

18,000

27,200

17,600

28,600

18,000

86.0

21,800

17,000

22,500

16,900

24,000

17,400

24,700

17,200

25,400

17,900

26,900

17,500

28,300

17,900

91.0

21,300

16,800

22,100

16,700

23,600

17,300

24,300

17,100

25,100

17,700

26,600

17,400

28,000

17,800

95.0

20,900

16,600

21,700

16,500

23,200

17,100

24,000

16,900

24,700

17,600

26,300

17,300

27,800

17,700

100.0

20,500

16,300

21,200

16,300

22,800

16,900

23,600

16,800

24,400

17,400

26,000

17,200

27,500

17,600

104.0

20,000

16,100

20,800

16,100

22,400

16,800

23,200

16,600

24,000

17,300

25,700

17,000

27,300

17,500

110.0

19,500

15,900

20,300

15,900

21,900

16,600

22,800

16,400

23,600

17,100

25,200

16,900

26,800

17,300

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-50

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,400

9,900

14,900

9,800

15,800

10,100

16,200

10,500

16,700

10,200

17,600

9,900

18,500

10,000
10,000

73.0

14,200

9,800

14,700

9,700

15,600

10,000

16,000

10,400

16,500

10,100

17,400

9,800

18,300

77.0

14,000

9,700

14,500

9,600

15,400

9,900

15,900

10,300

16,300

10,000

17,200

9,800

18,100

9,900

82.0

13,800

9,600

14,300

9,500

15,200

9,800

15,700

10,200

16,100

9,900

17,000

9,700

17,900

9,800

86.0

13,700

9,500

14,100

9,400

15,000

9,700

15,500

10,100

15,900

9,800

16,800

9,600

17,700

9,700

91.0

13,400

9,300

13,800

9,300

14,800

9,600

15,300

10,000

15,700

9,700

16,600

9,500

17,600

9,600

95.0

13,100

9,100

13,600

9,100

14,500

9,400

15,000

9,900

15,500

9,600

16,500

9,400

17,400

9,600

100.0

12,800

9,000

13,300

9,000

14,300

9,300

14,800

9,800

15,300

9,500

16,300

9,300

17,200

9,500

104.0

12,600

8,800

13,000

8,800

14,100

9,200

14,600

9,700

15,100

9,400

16,100

9,300

17,100

9,400

110.0

12,200

8,700

12,700

8,700

13,800

9,000

14,300

9,500

14,800

9,200

15,800

9,100

16,800

9,300

68.0

17,400

12,000

17,900

12,000

19,000

12,300

19,500

12,800

20,100

12,400

21,200

12,100

22,300

12,300

73.0

17,100

11,900

17,700

11,900

18,800

12,200

19,300

12,700

19,900

12,300

21,000

12,000

22,100

12,200

77.0

16,900

11,800

17,500

11,700

18,600

12,000

19,100

12,600

19,600

12,200

20,700

11,900

21,800

12,100

82.0

16,700

11,700

17,200

11,600

18,300

11,900

18,900

12,500

19,400

12,100

20,500

11,800

21,600

12,000

86.0

16,500

11,500

17,000

11,500

18,100

11,800

18,600

12,400

19,200

12,000

20,300

11,700

21,400

11,900

91.0

16,100

11,400

16,700

11,300

17,800

11,700

18,400

12,300

18,900

11,900

20,100

11,600

21,200

11,800

95.0

15,800

11,200

16,400

11,200

17,500

11,500

18,100

12,100

18,700

11,700

19,800

11,500

21,000

11,700

100.0

15,400

11,000

16,000

11,000

17,200

11,400

17,800

12,000

18,400

11,600

19,600

11,400

20,800

11,700

104.0

15,100

10,800

15,700

10,800

16,900

11,200

17,500

11,900

18,200

11,500

19,400

11,300

20,600

11,600

110.0

14,700

10,600

15,400

10,600

16,600

11,100

17,200

11,700

17,800

11,300

19,000

11,200

20,200

11,400

68.0

22,900

15,800

23,600

15,700

25,100

16,100

25,800

16,900

26,600

16,300

28,000

15,900

29,400

16,100

73.0

22,600

15,700

23,400

15,600

24,800

16,000

25,500

16,700

26,200

16,200

27,700

15,800

29,100

16,000

77.0

22,300

15,500

23,000

15,400

24,500

15,800

25,200

16,600

25,900

16,000

27,400

15,700

28,900

15,900

82.0

22,000

15,300

22,800

15,300

24,200

15,700

24,900

16,400

25,700

15,900

27,100

15,500

28,500

15,700

86.0

21,700

15,200

22,500

15,100

23,900

15,500

24,600

16,300

25,300

15,700

26,800

15,400

28,200

15,600

91.0

21,300

14,900

22,000

14,900

23,500

15,300

24,300

16,100

25,000

15,600

26,500

15,300

28,000

15,500

95.0

20,900

14,700

21,600

14,700

23,100

15,100

23,900

15,900

24,600

15,400

26,200

15,100

27,700

15,400

100.0

20,400

14,400

21,200

14,400

22,800

14,900

23,500

15,700

24,300

15,200

25,900

15,000

27,400

15,300

104.0

20,000

14,200

20,800

14,200

22,400

14,800

23,200

15,600

24,000

15,100

25,600

14,900

27,200

15,200

110.0

19,500

13,900

20,300

14,000

21,900

14,500

22,700

15,300

23,500

14,900

25,100

14,700

26,700

15,000

68.0

25,900

18,100

26,700

18,000

28,300

18,400

29,100

19,300

30,000

18,700

31,600

18,200

33,200

18,500

73.0

25,500

17,900

26,400

17,800

28,000

18,300

28,800

19,200

29,600

18,500

31,300

18,100

32,900

18,300

77.0

25,200

17,700

26,000

17,600

27,700

18,100

28,500

19,000

29,300

18,300

30,900

17,900

32,600

18,200

82.0

24,900

17,500

25,700

17,500

27,300

17,900

28,100

18,800

28,900

18,200

30,600

17,800

32,200

18,100

86.0

24,500

17,400

25,300

17,300

27,000

17,800

27,800

18,700

28,600

18,000

30,200

17,700

31,900

17,900

91.0

24,000

17,100

24,900

17,000

26,600

17,600

27,400

18,500

28,200

17,900

29,900

17,500

31,600

17,800

95.0

23,500

16,800

24,400

16,800

26,100

17,400

27,000

18,300

27,800

17,700

29,500

17,400

31,300

17,700

100.0

23,000

16,600

23,900

16,500

25,700

17,100

26,600

18,100

27,400

17,500

29,200

17,200

31,000

17,600

104.0

22,500

16,300

23,400

16,300

25,300

16,900

26,100

17,900

27,100

17,300

28,900

17,100

30,700

17,500

110.0

22,000

16,000

22,900

16,000

24,700

16,700

25,600

17,600

26,500

17,100

28,300

16,900

30,100

17,200

68.0

28,800

20,100

29,700

20,000

31,600

20,500

32,500

21,500

33,400

20,800

35,200

20,300

37,000

20,500

73.0

28,400

19,900

29,400

19,800

31,200

20,300

32,100

21,300

33,000

20,600

34,800

20,100

36,600

20,400

77.0

28,100

19,700

29,000

19,600

30,800

20,100

31,700

21,100

32,600

20,400

34,400

20,000

36,300

20,200

82.0

27,700

19,500

28,600

19,400

30,400

19,900

31,300

20,900

32,200

20,200

34,000

19,800

35,900

20,100

86.0

27,300

19,300

28,200

19,200

30,000

19,800

31,000

20,800

31,900

20,100

33,700

19,600

35,500

19,900

91.0

26,800

19,000

27,700

18,900

29,600

19,500

30,500

20,500

31,400

19,900

33,300

19,500

35,200

19,800

95.0

26,200

18,700

27,200

18,700

29,100

19,300

30,000

20,300

31,000

19,700

32,900

19,300

34,800

19,700

100.0

25,600

18,400

26,600

18,400

28,600

19,100

29,600

20,100

30,600

19,500

32,500

19,200

34,500

19,500

104.0

25,100

18,100

26,100

18,100

28,100

18,800

29,100

19,900

30,100

19,300

32,200

19,000

34,200

19,400

110.0

24,500

17,800

25,500

17,800

27,500

18,500

28,500

19,600

29,500

19,000

31,600

18,700

33,600

19,200

68.0

34,700

24,800

35,800

24,600

38,000

25,300

39,100

26,600

40,200

25,700

42,400

25,100

44,600

25,400

73.0

34,300

24,500

35,400

24,400

37,500

25,100

38,700

26,400

39,700

25,400

42,000

24,900

44,100

25,300

77.0

33,800

24,300

34,900

24,200

37,100

24,900

38,200

26,200

39,300

25,200

41,500

24,700

43,700

25,100

82.0

33,300

24,000

34,500

23,900

36,600

24,600

37,700

25,900

38,800

25,000

41,000

24,500

43,200

24,900

86.0

32,900

23,800

34,000

23,700

36,200

24,400

37,300

25,700

38,400

24,800

40,600

24,300

42,700

24,700

91.0

32,200

23,500

33,300

23,400

35,600

24,100

36,700

25,500

37,900

24,600

40,100

24,100

42,400

24,600

95.0

31,600

23,100

32,700

23,100

35,000

23,900

36,200

25,200

37,300

24,400

39,600

23,900

42,000

24,400

100.0

30,900

22,800

32,100

22,800

34,500

23,600

35,600

25,000

36,800

24,100

39,200

23,800

41,600

24,300

104.0

30,200

22,400

31,400

22,400

33,900

23,300

35,100

24,700

36,300

23,900

38,700

23,600

41,200

24,100

110.0

29,500

22,100

30,700

22,100

33,100

23,000

34,400

24,400

35,600

23,600

38,000

23,300

40,400

23,800

68.0

46,200

31,800

47,600

31,600

50,600

32,400

52,000

33,800

53,500

32,700

56,400

31,900

59,300

32,300

73.0

45,600

31,400

47,100

31,300

49,900

32,100

51,400

33,500

52,900

32,400

55,800

31,700

58,700

32,100

77.0

45,000

31,100

46,400

30,900

49,400

31,800

50,800

33,200

52,200

32,100

55,200

31,400

58,100

31,800

82.0

44,400

30,800

45,800

30,600

48,700

31,400

50,200

32,900

51,700

31,800

54,600

31,100

57,500

31,600

86.0

43,800

30,400

45,200

30,300

48,100

31,100

49,600

32,600

51,000

31,500

54,000

30,900

56,900

31,300

91.0

42,900

29,900

44,400

29,800

47,400

30,800

48,900

32,300

50,400

31,200

53,400

30,600

56,300

31,100

95.0

42,000

29,500

43,500

29,400

46,600

30,400

48,100

31,900

49,600

30,900

52,700

30,300

55,800

30,900

100.0

41,100

29,000

42,700

28,900

45,800

30,000

47,400

31,500

49,000

30,600

52,200

30,100

55,300

30,600

104.0

40,200

28,500

41,800

28,500

45,100

29,600

46,700

31,200

48,300

30,300

51,500

29,800

54,800

30,500

110.0

39,200

27,900

40,800

28,000

44,100

29,100

45,700

30,700

47,300

29,800

50,600

29,400

53,800

30,000

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-51

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PEFY-P-NMHU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

54

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

51,800

36,600

53,400

36,400

56,700

37,400

58,300

39,200

59,900

37,900

63,200

37,000

66,500

37,500

73.0

51,100

36,200

52,700

36,100

56,000

37,000

57,600

38,900

59,200

37,600

62,500

36,700

65,800

37,200

77.0

50,400

35,900

52,000

35,700

55,300

36,700

56,900

38,600

58,500

37,200

61,800

36,400

65,100

37,000

82.0

49,700

35,500

51,400

35,400

54,600

36,400

56,200

38,300

57,900

37,000

61,100

36,100

64,400

36,700

86.0

49,100

35,200

50,700

35,000

53,900

36,000

55,600

38,000

57,200

36,600

60,500

35,900

63,700

36,400

91.0

48,000

34,600

49,700

34,500

53,100

35,600

54,800

37,600

56,400

36,300

59,800

35,600

63,100

36,200

95.0

47,100

34,100

48,800

34,100

52,200

35,200

53,900

37,200

55,600

35,900

59,100

35,300

62,500

36,000

100.0

46,000

33,600

47,800

33,600

51,400

34,800

53,100

36,800

54,900

35,600

58,400

35,000

61,900

35,800

104.0

45,100

33,100

46,800

33,100

50,500

34,400

52,300

36,500

54,100

35,300

57,700

34,800

61,400

35,600

110.0

43,900

32,500

45,800

32,600

49,400

33,900

51,200

36,000

53,000

34,800

56,700

34,300

60,300

35,100

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-52

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

4,500

6,100

4,500

6,500

4,600

6,600

4,900

6,800

4,700

7,200

4,600

7,600

4,700

73.0

5,800

4,500

6,000

4,500

6,400

4,600

6,600

4,900

6,700

4,700

7,100

4,600

7,500

4,700

77.0

5,700

4,400

5,900

4,400

6,300

4,600

6,500

4,800

6,700

4,700

7,000

4,600

7,400

4,600

82.0

5,700

4,400

5,900

4,400

6,200

4,500

6,400

4,800

6,600

4,600

7,000

4,500

7,300

4,600

86.0

5,600

4,400

5,800

4,300

6,100

4,500

6,300

4,800

6,500

4,600

6,900

4,500

7,300

4,600

91.0

5,500

4,300

5,700

4,300

6,000

4,400

6,200

4,700

6,400

4,600

6,800

4,500

7,200

4,600

95.0

5,400

4,300

5,600

4,200

6,000

4,400

6,100

4,700

6,300

4,500

6,700

4,400

7,100

4,500

100.0

5,200

4,200

5,400

4,200

5,900

4,400

6,000

4,700

6,300

4,500

6,700

4,400

7,100

4,500

104.0

5,100

4,100

5,300

4,100

5,800

4,300

6,000

4,600

6,200

4,400

6,600

4,400

7,000

4,500

110.0

5,000

4,100

5,200

4,100

5,600

4,300

5,800

4,600

6,000

4,400

6,500

4,300

6,900

4,500

68.0

7,500

5,500

7,800

5,500

8,200

5,700

8,500

6,000

8,700

5,800

9,200

5,600

9,700

5,700

73.0

7,400

5,500

7,700

5,500

8,100

5,600

8,400

5,900

8,600

5,700

9,100

5,600

9,600

5,700

77.0

7,300

5,400

7,600

5,400

8,100

5,600

8,300

5,900

8,500

5,700

9,000

5,500

9,500

5,600

82.0

7,200

5,400

7,500

5,400

7,900

5,500

8,200

5,800

8,400

5,600

8,900

5,500

9,400

5,600

86.0

7,100

5,300

7,400

5,300

7,800

5,500

8,100

5,800

8,300

5,600

8,800

5,500

9,300

5,600

91.0

7,000

5,300

7,200

5,200

7,700

5,400

8,000

5,700

8,200

5,500

8,700

5,400

9,200

5,500

95.0

6,900

5,200

7,100

5,200

7,600

5,400

7,800

5,700

8,100

5,500

8,600

5,400

9,100

5,500

100.0

6,700

5,100

7,000

5,100

7,500

5,300

7,700

5,600

8,000

5,400

8,500

5,400

9,000

5,500

104.0

6,600

5,000

6,800

5,000

7,400

5,200

7,600

5,600

7,900

5,400

8,400

5,300

8,900

5,400

110.0

6,400

5,000

6,700

5,000

7,200

5,200

7,500

5,500

7,700

5,300

8,200

5,300

8,800

5,400

68.0

11,500

8,000

11,800

8,000

12,600

8,200

12,900

8,600

13,300

8,300

14,000

8,100

14,700

8,200

73.0

11,300

7,900

11,700

7,900

12,400

8,100

12,800

8,500

13,100

8,200

13,900

8,000

14,600

8,100

77.0

11,200

7,900

11,500

7,800

12,300

8,000

12,600

8,400

13,000

8,100

13,700

8,000

14,400

8,100

82.0

11,000

7,800

11,400

7,800

12,100

8,000

12,500

8,400

12,800

8,100

13,500

7,900

14,300

8,000

86.0

10,900

7,700

11,200

7,700

11,900

7,900

12,300

8,300

12,700

8,000

13,400

7,800

14,100

8,000

91.0

10,600

7,600

11,000

7,600

11,800

7,800

12,100

8,200

12,500

7,900

13,200

7,800

14,000

7,900

95.0

10,400

7,500

10,800

7,500

11,600

7,700

11,900

8,100

12,300

7,900

13,100

7,700

13,900

7,900

100.0

10,200

7,400

10,600

7,300

11,400

7,600

11,800

8,000

12,200

7,800

12,900

7,700

13,700

7,800

104.0

10,000

7,200

10,400

7,200

11,200

7,500

11,600

8,000

12,000

7,700

12,800

7,600

13,600

7,800

110.0

9,700

7,100

10,100

7,100

10,900

7,400

11,300

7,800

11,800

7,600

12,600

7,500

13,400

7,700

68.0

14,400

10,900

14,900

10,800

15,800

11,100

16,200

11,800

16,700

11,400

17,600

11,100

18,500

11,300

73.0

14,200

10,800

14,700

10,700

15,600

11,100

16,000

11,700

16,500

11,300

17,400

11,000

18,300

11,200

77.0

14,000

10,700

14,500

10,600

15,400

11,000

15,900

11,600

16,300

11,200

17,200

11,000

18,100

11,200

82.0

13,800

10,600

14,300

10,500

15,200

10,900

15,700

11,600

16,100

11,100

17,000

10,900

17,900

11,100

86.0

13,700

10,500

14,100

10,500

15,000

10,800

15,500

11,500

15,900

11,000

16,800

10,800

17,700

11,000

91.0

13,400

10,400

13,800

10,300

14,800

10,700

15,300

11,400

15,700

10,900

16,600

10,700

17,600

11,000

95.0

13,100

10,200

13,600

10,200

14,500

10,600

15,000

11,300

15,500

10,900

16,500

10,700

17,400

10,900

100.0

12,800

10,100

13,300

10,100

14,300

10,500

14,800

11,200

15,300

10,800

16,300

10,600

17,200

10,900

104.0

12,600

10,000

13,000

10,000

14,100

10,400

14,600

11,100

15,100

10,700

16,100

10,500

17,100

10,800

110.0

12,200

9,800

12,700

9,800

13,800

10,200

14,300

11,000

14,800

10,600

15,800

10,400

16,800

10,700

68.0

17,400

12,800

17,900

12,800

19,000

13,100

19,500

13,900

20,100

13,400

21,200

13,100

22,300

13,300

73.0

17,100

12,700

17,700

12,700

18,800

13,000

19,300

13,800

19,900

13,300

21,000

13,000

22,100

13,200

77.0

16,900

12,600

17,500

12,500

18,600

12,900

19,100

13,700

19,600

13,200

20,700

12,900

21,800

13,100

82.0

16,700

12,500

17,200

12,400

18,300

12,800

18,900

13,600

19,400

13,100

20,500

12,800

21,600

13,000

86.0

16,500

12,400

17,000

12,300

18,100

12,700

18,600

13,500

19,200

13,000

20,300

12,700

21,400

13,000

91.0

16,100

12,200

16,700

12,200

17,800

12,600

18,400

13,400

18,900

12,900

20,100

12,600

21,200

12,900

95.0

15,800

12,100

16,400

12,000

17,500

12,500

18,100

13,200

18,700

12,800

19,800

12,500

21,000

12,800

100.0

15,400

11,900

16,000

11,900

17,200

12,300

17,800

13,100

18,400

12,600

19,600

12,400

20,800

12,700

104.0

15,100

11,700

15,700

11,700

16,900

12,200

17,500

13,000

18,200

12,500

19,400

12,400

20,600

12,700

110.0

14,700

11,500

15,400

11,500

16,600

12,000

17,200

12,800

17,800

12,400

19,000

12,200

20,200

12,500

68.0

22,900

16,900

23,600

16,800

25,100

17,300

25,800

18,300

26,600

17,600

28,000

17,200

29,400

17,500

73.0

22,600

16,700

23,400

16,700

24,800

17,100

25,500

18,100

26,200

17,400

27,700

17,100

29,100

17,400

77.0

22,300

16,600

23,000

16,500

24,500

17,000

25,200

18,000

25,900

17,300

27,400

16,900

28,900

17,200

82.0

22,000

16,400

22,800

16,400

24,200

16,900

24,900

17,800

25,700

17,200

27,100

16,800

28,500

17,100

86.0

21,700

16,300

22,500

16,200

23,900

16,700

24,600

17,700

25,300

17,100

26,800

16,700

28,200

17,000

91.0

21,300

16,100

22,000

16,000

23,500

16,500

24,300

17,600

25,000

16,900

26,500

16,600

28,000

16,900

95.0

20,900

15,900

21,600

15,800

23,100

16,400

23,900

17,400

24,600

16,800

26,200

16,500

27,700

16,800

100.0

20,400

15,600

21,200

15,600

22,800

16,200

23,500

17,200

24,300

16,600

25,900

16,400

27,400

16,700

104.0

20,000

15,400

20,800

15,400

22,400

16,000

23,200

17,100

24,000

16,500

25,600

16,200

27,200

16,600

110.0

19,500

15,200

20,300

15,200

21,900

15,800

22,700

16,900

23,500

16,300

25,100

16,100

26,700

16,500

68.0

25,900

18,800

26,700

18,700

28,300

19,200

29,100

20,200

30,000

19,500

31,600

19,100

33,200

19,400

73.0

25,500

18,600

26,400

18,500

28,000

19,000

28,800

20,100

29,600

19,300

31,300

18,900

32,900

19,200

77.0

25,200

18,400

26,000

18,300

27,700

18,900

28,500

19,900

29,300

19,200

30,900

18,800

32,600

19,100

82.0

24,900

18,300

25,700

18,200

27,300

18,700

28,100

19,800

28,900

19,100

30,600

18,600

32,200

19,000

86.0

24,500

18,100

25,300

18,000

27,000

18,500

27,800

19,600

28,600

18,900

30,200

18,500

31,900

18,800

91.0

24,000

17,800

24,900

17,800

26,600

18,400

27,400

19,400

28,200

18,700

29,900

18,400

31,600

18,700

95.0

23,500

17,600

24,400

17,500

26,100

18,200

27,000

19,200

27,800

18,600

29,500

18,200

31,300

18,600

100.0

23,000

17,300

23,900

17,300

25,700

18,000

26,600

19,100

27,400

18,400

29,200

18,100

31,000

18,500

104.0

22,500

17,100

23,400

17,100

25,300

17,800

26,100

18,900

27,100

18,200

28,900

18,000

30,700

18,400

110.0

22,000

16,800

22,900

16,800

24,700

17,500

25,600

18,700

26,500

18,000

28,300

17,800

30,100

18,200

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-53

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PDFY-P-NMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

28,800

20,700

29,700

20,600

31,600

21,200

32,500

22,300

33,400

21,500

35,200

21,000

37,000

21,300

73.0

28,400

20,500

29,400

20,400

31,200

21,000

32,100

22,100

33,000

21,300

34,800

20,900

36,600

21,200

77.0

28,100

20,300

29,000

20,200

30,800

20,800

31,700

21,900

32,600

21,200

34,400

20,700

36,300

21,000

82.0

27,700

20,100

28,600

20,000

30,400

20,600

31,300

21,800

32,200

21,000

34,000

20,500

35,900

20,900

86.0

27,300

20,000

28,200

19,900

30,000

20,400

31,000

21,600

31,900

20,800

33,700

20,400

35,500

20,700

91.0

26,800

19,700

27,700

19,600

29,600

20,200

30,500

21,400

31,400

20,600

33,300

20,200

35,200

20,600

95.0

26,200

19,400

27,200

19,300

29,100

20,000

30,000

21,200

31,000

20,400

32,900

20,100

34,800

20,500

100.0

25,600

19,100

26,600

19,100

28,600

19,800

29,600

21,000

30,600

20,300

32,500

19,900

34,500

20,400

104.0

25,100

18,800

26,100

18,800

28,100

19,600

29,100

20,800

30,100

20,100

32,200

19,800

34,200

20,300

110.0

24,500

18,500

25,500

18,500

27,500

19,300

28,500

20,500

29,500

19,800

31,600

19,500

33,600

20,000

68.0

34,700

25,600

35,800

25,500

38,000

26,200

39,100

27,700

40,200

26,700

42,400

26,100

44,600

26,500

73.0

34,300

25,400

35,400

25,300

37,500

26,000

38,700

27,500

39,700

26,500

42,000

25,900

44,100

26,400

77.0

33,800

25,200

34,900

25,000

37,100

25,800

38,200

27,300

39,300

26,300

41,500

25,700

43,700

26,200

82.0

33,300

24,900

34,500

24,800

36,600

25,600

37,700

27,100

38,800

26,100

41,000

25,500

43,200

26,000

86.0

32,900

24,700

34,000

24,600

36,200

25,400

37,300

26,900

38,400

25,900

40,600

25,400

42,700

25,900

91.0

32,200

24,400

33,300

24,300

35,600

25,100

36,700

26,700

37,900

25,700

40,100

25,200

42,400

25,700

95.0

31,600

24,100

32,700

24,000

35,000

24,900

36,200

26,400

37,300

25,500

39,600

25,000

42,000

25,600

100.0

30,900

23,700

32,100

23,700

34,500

24,600

35,600

26,200

36,800

25,200

39,200

24,800

41,600

25,400

104.0

30,200

23,400

31,400

23,400

33,900

24,300

35,100

26,000

36,300

25,000

38,700

24,700

41,200

25,300

110.0

29,500

23,000

30,700

23,000

33,100

24,000

34,400

25,600

35,600

24,700

38,000

24,400

40,400

25,000

68.0

46,200

32,900

47,600

32,700

50,600

33,600

52,000

35,400

53,500

34,100

56,400

33,300

59,300

33,800

73.0

45,600

32,600

47,100

32,400

49,900

33,300

51,400

35,100

52,900

33,800

55,800

33,100

58,700

33,600

77.0

45,000

32,300

46,400

32,100

49,400

33,000

50,800

34,800

52,200

33,500

55,200

32,800

58,100

33,300

82.0

44,400

32,000

45,800

31,800

48,700

32,700

50,200

34,500

51,700

33,300

54,600

32,600

57,500

33,100

86.0

43,800

31,700

45,200

31,500

48,100

32,400

49,600

34,200

51,000

33,000

54,000

32,300

56,900

32,900

91.0

42,900

31,200

44,400

31,100

47,400

32,100

48,900

33,900

50,400

32,700

53,400

32,100

56,300

32,700

95.0

42,000

30,700

43,500

30,700

46,600

31,700

48,100

33,600

49,600

32,400

52,700

31,800

55,800

32,500

100.0

41,100

30,300

42,700

30,200

45,800

31,400

47,400

33,200

49,000

32,100

52,200

31,600

55,300

32,300

104.0

40,200

29,800

41,800

29,800

45,100

31,000

46,700

32,900

48,300

31,800

51,500

31,300

54,800

32,100

110.0

39,200

29,300

40,800

29,400

44,100

30,500

45,700

32,500

47,300

31,400

50,600

31,000

53,800

31,700

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-54

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PMFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

5,300

6,100

5,200

6,500

5,400

6,600

5,800

6,800

5,600

7,200

5,500

7,600

5,600

73.0

5,800

5,200

6,000

5,200

6,400

5,400

6,600

5,800

6,700

5,600

7,100

5,500

7,500

5,600

77.0

5,700

5,200

5,900

5,200

6,300

5,400

6,500

5,800

6,700

5,500

7,000

5,400

7,400

5,600

82.0

5,700

5,200

5,900

5,100

6,200

5,300

6,400

5,700

6,600

5,500

7,000

5,400

7,300

5,500

86.0

5,600

5,100

5,800

5,100

6,100

5,300

6,300

5,700

6,500

5,500

6,900

5,400

7,300

5,500

91.0

5,500

5,100

5,700

5,100

6,000

5,300

6,200

5,700

6,400

5,400

6,800

5,300

7,200

5,500

95.0

5,400

5,000

5,600

5,000

6,000

5,200

6,100

5,600

6,300

5,400

6,700

5,300

7,100

5,500

100.0

5,200

5,000

5,400

5,000

5,900

5,200

6,000

5,600

6,300

5,400

6,700

5,300

7,100

5,500

104.0

5,100

4,900

5,300

4,900

5,800

5,100

6,000

5,600

6,200

5,300

6,600

5,300

7,000

5,400

110.0

5,000

4,900

5,200

4,900

5,600

5,100

5,800

5,500

6,000

5,300

6,500

5,200

6,900

5,400

68.0

7,500

6,300

7,800

6,300

8,200

6,500

8,500

7,000

8,700

6,700

9,200

6,600

9,700

6,700

73.0

7,400

6,300

7,700

6,300

8,100

6,500

8,400

7,000

8,600

6,700

9,100

6,500

9,600

6,700

77.0

7,300

6,300

7,600

6,200

8,100

6,400

8,300

6,900

8,500

6,600

9,000

6,500

9,500

6,700

82.0

7,200

6,200

7,500

6,200

7,900

6,400

8,200

6,900

8,400

6,600

8,900

6,500

9,400

6,600

86.0

7,100

6,200

7,400

6,100

7,800

6,400

8,100

6,800

8,300

6,500

8,800

6,400

9,300

6,600

91.0

7,000

6,100

7,200

6,100

7,700

6,300

8,000

6,800

8,200

6,500

8,700

6,400

9,200

6,600

95.0

6,900

6,000

7,100

6,000

7,600

6,300

7,800

6,700

8,100

6,500

8,600

6,400

9,100

6,500

100.0

6,700

6,000

7,000

6,000

7,500

6,200

7,700

6,700

8,000

6,400

8,500

6,300

9,000

6,500

104.0

6,600

5,900

6,800

5,900

7,400

6,200

7,600

6,700

7,900

6,400

8,400

6,300

8,900

6,500

110.0

6,400

5,800

6,700

5,800

7,200

6,100

7,500

6,600

7,700

6,300

8,200

6,200

8,800

6,400

68.0

11,500

8,300

11,800

8,300

12,600

8,500

12,900

9,000

13,300

8,600

14,000

8,400

14,700

8,600

73.0

11,300

8,200

11,700

8,200

12,400

8,400

12,800

8,900

13,100

8,600

13,900

8,400

14,600

8,500

77.0

11,200

8,200

11,500

8,100

12,300

8,400

12,600

8,800

13,000

8,500

13,700

8,300

14,400

8,500

82.0

11,000

8,100

11,400

8,000

12,100

8,300

12,500

8,700

12,800

8,400

13,500

8,300

14,300

8,400

86.0

10,900

8,000

11,200

8,000

11,900

8,200

12,300

8,700

12,700

8,400

13,400

8,200

14,100

8,300

91.0

10,600

7,900

11,000

7,900

11,800

8,100

12,100

8,600

12,500

8,300

13,200

8,100

14,000

8,300

95.0

10,400

7,800

10,800

7,800

11,600

8,000

11,900

8,500

12,300

8,200

13,100

8,100

13,900

8,200

100.0

10,200

7,700

10,600

7,700

11,400

7,900

11,800

8,400

12,200

8,100

12,900

8,000

13,700

8,200

104.0

10,000

7,600

10,400

7,600

11,200

7,900

11,600

8,400

12,000

8,100

12,800

8,000

13,600

8,100

110.0

9,700

7,400

10,100

7,400

10,900

7,700

11,300

8,300

11,800

8,000

12,600

7,900

13,400

8,100

68.0

14,400

10,200

14,900

10,100

15,800

10,400

16,200

10,900

16,700

10,500

17,600

10,300

18,500

10,400

73.0

14,200

10,100

14,700

10,000

15,600

10,300

16,000

10,800

16,500

10,400

17,400

10,200

18,300

10,300

77.0

14,000

10,000

14,500

9,900

15,400

10,200

15,900

10,700

16,300

10,300

17,200

10,100

18,100

10,300

82.0

13,800

9,900

14,300

9,800

15,200

10,100

15,700

10,600

16,100

10,300

17,000

10,000

17,900

10,200

86.0

13,700

9,800

14,100

9,700

15,000

10,000

15,500

10,500

15,900

10,200

16,800

10,000

17,700

10,100

91.0

13,400

9,600

13,800

9,600

14,800

9,900

15,300

10,400

15,700

10,100

16,600

9,900

17,600

10,100

95.0

13,100

9,500

13,600

9,500

14,500

9,800

15,000

10,300

15,500

10,000

16,500

9,800

17,400

10,000

100.0

12,800

9,300

13,300

9,300

14,300

9,700

14,800

10,200

15,300

9,900

16,300

9,700

17,200

9,900

104.0

12,600

9,200

13,000

9,200

14,100

9,600

14,600

10,100

15,100

9,800

16,100

9,700

17,100

9,900

110.0

12,200

9,000

12,700

9,000

13,800

9,400

14,300

10,000

14,800

9,700

15,800

9,500

16,800

9,800

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-55

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PLFY-P-NCMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

7,500

6,700

7,800

6,600

8,200

6,900

8,500

7,400

8,700

7,100

9,200

7,000

9,700

7,100

73.0

7,400

6,600

7,700

6,600

8,100

6,800

8,400

7,400

8,600

7,100

9,100

6,900

9,600

7,100

77.0

7,300

6,600

7,600

6,600

8,100

6,800

8,300

7,300

8,500

7,000

9,000

6,900

9,500

7,100
7,000

82.0

7,200

6,600

7,500

6,500

7,900

6,800

8,200

7,300

8,400

7,000

8,900

6,900

9,400

86.0

7,100

6,500

7,400

6,500

7,800

6,700

8,100

7,300

8,300

6,900

8,800

6,800

9,300

7,000

91.0

7,000

6,400

7,200

6,400

7,700

6,700

8,000

7,200

8,200

6,900

8,700

6,800

9,200

7,000

95.0

6,900

6,400

7,100

6,400

7,600

6,600

7,800

7,200

8,100

6,900

8,600

6,800

9,100

7,000

100.0

6,700

6,300

7,000

6,300

7,500

6,600

7,700

7,100

8,000

6,800

8,500

6,700

9,000

6,900

104.0

6,600

6,200

6,800

6,200

7,400

6,500

7,600

7,100

7,900

6,800

8,400

6,700

8,900

6,900

110.0

6,400

6,200

6,700

6,200

7,200

6,500

7,500

7,000

7,700

6,700

8,200

6,600

8,800

6,800

68.0

11,500

8,900

11,800

8,900

12,600

9,100

12,900

9,700

13,300

9,300

14,000

9,100

14,700

9,300

73.0

11,300

8,800

11,700

8,800

12,400

9,100

12,800

9,700

13,100

9,300

13,900

9,100

14,600

9,300

77.0

11,200

8,800

11,500

8,700

12,300

9,000

12,600

9,600

13,000

9,200

13,700

9,000

14,400

9,200

82.0

11,000

8,700

11,400

8,700

12,100

8,900

12,500

9,500

12,800

9,200

13,500

9,000

14,300

9,200

86.0

10,900

8,600

11,200

8,600

11,900

8,900

12,300

9,500

12,700

9,100

13,400

8,900

14,100

9,100

91.0

10,600

8,500

11,000

8,500

11,800

8,800

12,100

9,400

12,500

9,000

13,200

8,900

14,000

9,100

95.0

10,400

8,400

10,800

8,400

11,600

8,700

11,900

9,300

12,300

8,900

13,100

8,800

13,900

9,000

100.0

10,200

8,300

10,600

8,300

11,400

8,600

11,800

9,200

12,200

8,900

12,900

8,700

13,700

9,000

104.0

10,000

8,200

10,400

8,200

11,200

8,500

11,600

9,200

12,000

8,800

12,800

8,700

13,600

8,900

110.0

9,700

8,100

10,100

8,100

10,900

8,400

11,300

9,100

11,800

8,700

12,600

8,600

13,400

8,800

68.0

14,400

10,400

14,900

10,400

15,800

10,700

16,200

11,200

16,700

10,800

17,600

10,600

18,500

10,800

73.0

14,200

10,300

14,700

10,300

15,600

10,600

16,000

11,200

16,500

10,800

17,400

10,500

18,300

10,700

77.0

14,000

10,200

14,500

10,200

15,400

10,500

15,900

11,100

16,300

10,700

17,200

10,400

18,100

10,600

82.0

13,800

10,100

14,300

10,100

15,200

10,400

15,700

11,000

16,100

10,600

17,000

10,400

17,900

10,500

86.0

13,700

10,100

14,100

10,000

15,000

10,300

15,500

10,900

15,900

10,500

16,800

10,300

17,700

10,500

91.0

13,400

9,900

13,800

9,900

14,800

10,200

15,300

10,800

15,700

10,400

16,600

10,200

17,600

10,400

95.0

13,100

9,800

13,600

9,700

14,500

10,100

15,000

10,700

15,500

10,300

16,500

10,100

17,400

10,300

100.0

12,800

9,600

13,300

9,600

14,300

10,000

14,800

10,600

15,300

10,200

16,300

10,100

17,200

10,300

104.0

12,600

9,500

13,000

9,500

14,100

9,900

14,600

10,500

15,100

10,100

16,100

10,000

17,100

10,200

110.0

12,200

9,300

12,700

9,300

13,800

9,700

14,300

10,400

14,800

10,000

15,800

9,900

16,800

10,100

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-56

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PLFY-P-NBMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

11,500

9,700

11,800

9,700

12,600

10,000

12,900

10,700

13,300

10,300

14,000

10,100

14,700

10,300

73.0

11,300

9,700

11,700

9,600

12,400

9,900

12,800

10,700

13,100

10,200

13,900

10,000

14,600

10,300

77.0

11,200

9,600

11,500

9,500

12,300

9,900

12,600

10,600

13,000

10,200

13,700

10,000

14,400

10,200

82.0

11,000

9,500

11,400

9,500

12,100

9,800

12,500

10,600

12,800

10,100

13,500

9,900

14,300

10,200

86.0

10,900

9,500

11,200

9,400

11,900

9,800

12,300

10,500

12,700

10,100

13,400

9,900

14,100

10,100

91.0

10,600

9,400

11,000

9,300

11,800

9,700

12,100

10,400

12,500

10,000

13,200

9,800

14,000

10,100

95.0

10,400

9,300

10,800

9,200

11,600

9,600

11,900

10,400

12,300

9,900

13,100

9,800

13,900

10,000

100.0

10,200

9,200

10,600

9,100

11,400

9,500

11,800

10,300

12,200

9,900

12,900

9,700

13,700

10,000

104.0

10,000

9,100

10,400

9,000

11,200

9,400

11,600

10,200

12,000

9,800

12,800

9,700

13,600

10,000

110.0

9,700

8,900

10,100

8,900

10,900

9,300

11,300

10,100

11,800

9,700

12,600

9,600

13,400

9,900

68.0

14,400

11,900

14,900

11,800

15,800

12,200

16,200

13,100

16,700

12,500

17,600

12,300

18,500

12,500

73.0

14,200

11,800

14,700

11,700

15,600

12,100

16,000

13,000

16,500

12,400

17,400

12,200

18,300

12,500

77.0

14,000

11,700

14,500

11,600

15,400

12,000

15,900

12,900

16,300

12,400

17,200

12,100

18,100

12,400

82.0

13,800

11,600

14,300

11,600

15,200

12,000

15,700

12,800

16,100

12,300

17,000

12,000

17,900

12,300

86.0

13,700

11,500

14,100

11,500

15,000

11,900

15,500

12,700

15,900

12,200

16,800

12,000

17,700

12,300

91.0

13,400

11,400

13,800

11,300

14,800

11,800

15,300

12,700

15,700

12,100

16,600

11,900

17,600

12,200

95.0

13,100

11,300

13,600

11,200

14,500

11,700

15,000

12,600

15,500

12,000

16,500

11,800

17,400

12,200

100.0

12,800

11,100

13,300

11,100

14,300

11,600

14,800

12,500

15,300

12,000

16,300

11,800

17,200

12,100

104.0

12,600

11,000

13,000

11,000

14,100

11,500

14,600

12,400

15,100

11,900

16,100

11,700

17,100

12,100

110.0

12,200

10,900

12,700

10,900

13,800

11,300

14,300

12,300

14,800

11,800

15,800

11,600

16,800

12,000

68.0

17,400

14,200

17,900

14,100

19,000

14,600

19,500

15,600

20,100

15,000

21,200

14,600

22,300

15,000

73.0

17,100

14,100

17,700

14,000

18,800

14,500

19,300

15,500

19,900

14,900

21,000

14,600

22,100

14,900

77.0

16,900

14,000

17,500

13,900

18,600

14,400

19,100

15,400

19,600

14,800

20,700

14,500

21,800

14,800

82.0

16,700

13,900

17,200

13,800

18,300

14,300

18,900

15,300

19,400

14,700

20,500

14,400

21,600

14,700

86.0

16,500

13,800

17,000

13,700

18,100

14,200

18,600

15,200

19,200

14,600

20,300

14,300

21,400

14,700

91.0

16,100

13,600

16,700

13,600

17,800

14,100

18,400

15,100

18,900

14,500

20,100

14,200

21,200

14,600

95.0

15,800

13,500

16,400

13,400

17,500

14,000

18,100

15,000

18,700

14,400

19,800

14,200

21,000

14,500

100.0

15,400

13,300

16,000

13,300

17,200

13,800

17,800

14,900

18,400

14,300

19,600

14,100

20,800

14,500

104.0

15,100

13,200

15,700

13,100

16,900

13,700

17,500

14,800

18,200

14,200

19,400

14,000

20,600

14,400

110.0

14,700

13,000

15,400

13,000

16,600

13,600

17,200

14,600

17,800

14,000

19,000

13,900

20,200

14,300

68.0

22,900

17,500

23,600

17,300

25,100

17,900

25,800

19,000

26,600

18,200

28,000

17,800

29,400

18,200

73.0

22,600

17,300

23,400

17,200

24,800

17,700

25,500

18,800

26,200

18,100

27,700

17,700

29,100

18,100

77.0

22,300

17,200

23,000

17,100

24,500

17,600

25,200

18,700

25,900

18,000

27,400

17,600

28,900

18,000

82.0

22,000

17,000

22,800

16,900

24,200

17,500

24,900

18,600

25,700

17,900

27,100

17,500

28,500

17,800

86.0

21,700

16,900

22,500

16,800

23,900

17,300

24,600

18,400

25,300

17,700

26,800

17,400

28,200

17,700

91.0

21,300

16,600

22,000

16,600

23,500

17,200

24,300

18,300

25,000

17,600

26,500

17,300

28,000

17,600

95.0

20,900

16,400

21,600

16,400

23,100

17,000

23,900

18,100

24,600

17,400

26,200

17,100

27,700

17,600

100.0

20,400

16,200

21,200

16,200

22,800

16,800

23,500

18,000

24,300

17,300

25,900

17,000

27,400

17,500

104.0

20,000

16,000

20,800

16,000

22,400

16,700

23,200

17,800

24,000

17,200

25,600

16,900

27,200

17,400

110.0

19,500

15,800

20,300

15,800

21,900

16,400

22,700

17,600

23,500

17,000

25,100

16,700

26,700

17,200

68.0

28,800

20,900

29,700

20,800

31,600

21,400

32,500

22,600

33,400

21,700

35,200

21,200

37,000

21,600

73.0

28,400

20,700

29,400

20,600

31,200

21,200

32,100

22,400

33,000

21,600

34,800

21,100

36,600

21,400

77.0

28,100

20,600

29,000

20,400

30,800

21,000

31,700

22,200

32,600

21,400

34,400

20,900

36,300

21,300

82.0

27,700

20,400

28,600

20,300

30,400

20,900

31,300

22,000

32,200

21,200

34,000

20,800

35,900

21,200

86.0

27,300

20,200

28,200

20,100

30,000

20,700

31,000

21,900

31,900

21,100

33,700

20,600

35,500

21,000

91.0

26,800

19,900

27,700

19,800

29,600

20,500

30,500

21,700

31,400

20,900

33,300

20,500

35,200

20,900

95.0

26,200

19,600

27,200

19,600

29,100

20,200

30,000

21,500

31,000

20,700

32,900

20,300

34,800

20,800

100.0

25,600

19,300

26,600

19,300

28,600

20,000

29,600

21,300

30,600

20,500

32,500

20,200

34,500

20,600

104.0

25,100

19,100

26,100

19,000

28,100

19,800

29,100

21,100

30,100

20,300

32,200

20,000

34,200

20,500

110.0

24,500

18,700

25,500

18,700

27,500

19,500

28,500

20,800

29,500

20,100

31,600

19,800

33,600

20,300

68.0

34,700

26,700

35,800

26,500

38,000

27,400

39,100

29,100

40,200

27,900

42,400

27,300

44,600

27,800

73.0

34,300

26,500

35,400

26,300

37,500

27,100

38,700

28,900

39,700

27,700

42,000

27,200

44,100

27,700

77.0

33,800

26,300

34,900

26,100

37,100

27,000

38,200

28,700

39,300

27,500

41,500

27,000

43,700

27,500

82.0

33,300

26,000

34,500

25,900

36,600

26,700

37,700

28,500

38,800

27,400

41,000

26,800

43,200

27,400

86.0

32,900

25,800

34,000

25,700

36,200

26,500

37,300

28,300

38,400

27,200

40,600

26,600

42,700

27,200

91.0

32,200

25,500

33,300

25,400

35,600

26,300

36,700

28,100

37,900

27,000

40,100

26,500

42,400

27,100

95.0

31,600

25,200

32,700

25,100

35,000

26,000

36,200

27,800

37,300

26,700

39,600

26,300

42,000

26,900

100.0

30,900

24,800

32,100

24,800

34,500

25,800

35,600

27,600

36,800

26,500

39,200

26,100

41,600

26,800

104.0

30,200

24,500

31,400

24,500

33,900

25,500

35,100

27,400

36,300

26,300

38,700

25,900

41,200

26,700

110.0

29,500

24,200

30,700

24,200

33,100

25,200

34,400

27,000

35,600

26,000

38,000

25,700

40,400

26,400

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-57

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PCFY-P-NGMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

14,400

10,900

14,900

10,800

15,800

11,100

16,200

11,800

16,700

11,400

17,600

11,100

18,500

11,300

73.0

14,200

10,800

14,700

10,700

15,600

11,100

16,000

11,700

16,500

11,300

17,400

11,000

18,300

11,200

77.0

14,000

10,700

14,500

10,600

15,400

11,000

15,900

11,600

16,300

11,200

17,200

11,000

18,100

11,200

82.0

13,800

10,600

14,300

10,500

15,200

10,900

15,700

11,600

16,100

11,100

17,000

10,900

17,900

11,100

86.0

13,700

10,500

14,100

10,500

15,000

10,800

15,500

11,500

15,900

11,000

16,800

10,800

17,700

11,000

91.0

13,400

10,400

13,800

10,300

14,800

10,700

15,300

11,400

15,700

10,900

16,600

10,700

17,600

11,000

95.0

13,100

10,200

13,600

10,200

14,500

10,600

15,000

11,300

15,500

10,900

16,500

10,700

17,400

10,900

100.0

12,800

10,100

13,300

10,100

14,300

10,500

14,800

11,200

15,300

10,800

16,300

10,600

17,200

10,900

104.0

12,600

10,000

13,000

10,000

14,100

10,400

14,600

11,100

15,100

10,700

16,100

10,500

17,100

10,800

110.0

12,200

9,800

12,700

9,800

13,800

10,200

14,300

11,000

14,800

10,600

15,800

10,400

16,800

10,700

68.0

22,900

16,900

23,600

16,800

25,100

17,300

25,800

18,300

26,600

17,600

28,000

17,200

29,400

17,500

73.0

22,600

16,700

23,400

16,700

24,800

17,100

25,500

18,100

26,200

17,400

27,700

17,100

29,100

17,400

77.0

22,300

16,600

23,000

16,500

24,500

17,000

25,200

18,000

25,900

17,300

27,400

16,900

28,900

17,200

82.0

22,000

16,400

22,800

16,400

24,200

16,900

24,900

17,800

25,700

17,200

27,100

16,800

28,500

17,100

86.0

21,700

16,300

22,500

16,200

23,900

16,700

24,600

17,700

25,300

17,100

26,800

16,700

28,200

17,000

91.0

21,300

16,100

22,000

16,000

23,500

16,500

24,300

17,600

25,000

16,900

26,500

16,600

28,000

16,900

95.0

20,900

15,900

21,600

15,800

23,100

16,400

23,900

17,400

24,600

16,800

26,200

16,500

27,700

16,800

100.0

20,400

15,600

21,200

15,600

22,800

16,200

23,500

17,200

24,300

16,600

25,900

16,400

27,400

16,700

104.0

20,000

15,400

20,800

15,400

22,400

16,000

23,200

17,100

24,000

16,500

25,600

16,200

27,200

16,600

110.0

19,500

15,200

20,300

15,200

21,900

15,800

22,700

16,900

23,500

16,300

25,100

16,100

26,700

16,500

68.0

28,800

20,700

29,700

20,600

31,600

21,200

32,500

22,300

33,400

21,500

35,200

21,000

37,000

21,300

73.0

28,400

20,500

29,400

20,400

31,200

21,000

32,100

22,100

33,000

21,300

34,800

20,900

36,600

21,200

77.0

28,100

20,300

29,000

20,200

30,800

20,800

31,700

21,900

32,600

21,200

34,400

20,700

36,300

21,000

82.0

27,700

20,100

28,600

20,000

30,400

20,600

31,300

21,800

32,200

21,000

34,000

20,500

35,900

20,900

86.0

27,300

20,000

28,200

19,900

30,000

20,400

31,000

21,600

31,900

20,800

33,700

20,400

35,500

20,700

91.0

26,800

19,700

27,700

19,600

29,600

20,200

30,500

21,400

31,400

20,600

33,300

20,200

35,200

20,600

95.0

26,200

19,400

27,200

19,300

29,100

20,000

30,000

21,200

31,000

20,400

32,900

20,100

34,800

20,500

100.0

25,600

19,100

26,600

19,100

28,600

19,800

29,600

21,000

30,600

20,300

32,500

19,900

34,500

20,400

104.0

25,100

18,800

26,100

18,800

28,100

19,600

29,100

20,800

30,100

20,100

32,200

19,800

34,200

20,300

110.0

24,500

18,500

25,500

18,500

27,500

19,300

28,500

20,500

29,500

19,800

31,600

19,500

33,600

20,000

68.0

34,700

25,600

35,800

25,500

38,000

26,200

39,100

27,700

40,200

26,700

42,400

26,100

44,600

26,500

73.0

34,300

25,400

35,400

25,300

37,500

26,000

38,700

27,500

39,700

26,500

42,000

25,900

44,100

26,400

77.0

33,800

25,200

34,900

25,000

37,100

25,800

38,200

27,300

39,300

26,300

41,500

25,700

43,700

26,200

82.0

33,300

24,900

34,500

24,800

36,600

25,600

37,700

27,100

38,800

26,100

41,000

25,500

43,200

26,000

86.0

32,900

24,700

34,000

24,600

36,200

25,400

37,300

26,900

38,400

25,900

40,600

25,400

42,700

25,900

91.0

32,200

24,400

33,300

24,300

35,600

25,100

36,700

26,700

37,900

25,700

40,100

25,200

42,400

25,700

95.0

31,600

24,100

32,700

24,000

35,000

24,900

36,200

26,400

37,300

25,500

39,600

25,000

42,000

25,600

100.0

30,900

23,700

32,100

23,700

34,500

24,600

35,600

26,200

36,800

25,200

39,200

24,800

41,600

25,400

104.0

30,200

23,400

31,400

23,400

33,900

24,300

35,100

26,000

36,300

25,000

38,700

24,700

41,200

25,300

110.0

29,500

23,000

30,700

23,000

33,100

24,000

34,400

25,600

35,600

24,700

38,000

24,400

40,400

25,000

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-58

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

4,500

6,100

4,500

6,500

4,600

6,600

4,900

6,800

4,700

7,200

4,600

7,600

4,700

73.0

5,800

4,500

6,000

4,500

6,400

4,600

6,600

4,900

6,700

4,700

7,100

4,600

7,500

4,700

77.0

5,700

4,400

5,900

4,400

6,300

4,600

6,500

4,800

6,700

4,700

7,000

4,600

7,400

4,600

82.0

5,700

4,400

5,900

4,400

6,200

4,500

6,400

4,800

6,600

4,600

7,000

4,500

7,300

4,600

86.0

5,600

4,400

5,800

4,300

6,100

4,500

6,300

4,800

6,500

4,600

6,900

4,500

7,300

4,600

91.0

5,500

4,300

5,700

4,300

6,000

4,400

6,200

4,700

6,400

4,600

6,800

4,500

7,200

4,600

95.0

5,400

4,300

5,600

4,200

6,000

4,400

6,100

4,700

6,300

4,500

6,700

4,400

7,100

4,500

100.0

5,200

4,200

5,400

4,200

5,900

4,400

6,000

4,700

6,300

4,500

6,700

4,400

7,100

4,500

104.0

5,100

4,100

5,300

4,100

5,800

4,300

6,000

4,600

6,200

4,400

6,600

4,400

7,000

4,500

110.0

5,000

4,100

5,200

4,100

5,600

4,300

5,800

4,600

6,000

4,400

6,500

4,300

6,900

4,500

68.0

7,500

5,700

7,800

5,600

8,200

5,800

8,500

6,100

8,700

5,900

9,200

5,800

9,700

5,900

73.0

7,400

5,600

7,700

5,600

8,100

5,800

8,400

6,100

8,600

5,900

9,100

5,700

9,600

5,900

77.0

7,300

5,600

7,600

5,500

8,100

5,700

8,300

6,100

8,500

5,800

9,000

5,700

9,500

5,800

82.0

7,200

5,500

7,500

5,500

7,900

5,700

8,200

6,000

8,400

5,800

8,900

5,700

9,400

5,800

86.0

7,100

5,500

7,400

5,400

7,800

5,600

8,100

6,000

8,300

5,700

8,800

5,600

9,300

5,700

91.0

7,000

5,400

7,200

5,400

7,700

5,600

8,000

5,900

8,200

5,700

8,700

5,600

9,200

5,700

95.0

6,900

5,300

7,100

5,300

7,600

5,500

7,800

5,900

8,100

5,700

8,600

5,600

9,100

5,700

100.0

6,700

5,300

7,000

5,300

7,500

5,500

7,700

5,800

8,000

5,600

8,500

5,500

9,000

5,700

104.0

6,600

5,200

6,800

5,200

7,400

5,400

7,600

5,800

7,900

5,600

8,400

5,500

8,900

5,600

110.0

6,400

5,100

6,700

5,100

7,200

5,300

7,500

5,700

7,700

5,500

8,200

5,400

8,800

5,600

68.0

11,500

9,100

11,800

9,100

12,600

9,300

12,900

10,000

13,300

9,600

14,000

9,400

14,700

9,600

73.0

11,300

9,000

11,700

9,000

12,400

9,300

12,800

9,900

13,100

9,500

13,900

9,300

14,600

9,500

77.0

11,200

9,000

11,500

8,900

12,300

9,200

12,600

9,800

13,000

9,400

13,700

9,200

14,400

9,500

82.0

11,000

8,900

11,400

8,800

12,100

9,100

12,500

9,800

12,800

9,400

13,500

9,200

14,300

9,400

86.0

10,900

8,800

11,200

8,800

11,900

9,100

12,300

9,700

12,700

9,300

13,400

9,100

14,100

9,300

91.0

10,600

8,700

11,000

8,700

11,800

9,000

12,100

9,600

12,500

9,200

13,200

9,100

14,000

9,300

95.0

10,400

8,600

10,800

8,600

11,600

8,900

11,900

9,600

12,300

9,200

13,100

9,000

13,900

9,300

100.0

10,200

8,500

10,600

8,500

11,400

8,800

11,800

9,500

12,200

9,100

12,900

9,000

13,700

9,200

104.0

10,000

8,400

10,400

8,400

11,200

8,800

11,600

9,400

12,000

9,000

12,800

8,900

13,600

9,200

110.0

9,700

8,300

10,100

8,300

10,900

8,700

11,300

9,300

11,800

9,000

12,600

8,800

13,400

9,100

68.0

14,400

11,000

14,900

10,900

15,800

11,200

16,200

11,900

16,700

11,400

17,600

11,200

18,500

11,400

73.0

14,200

10,900

14,700

10,800

15,600

11,100

16,000

11,800

16,500

11,400

17,400

11,100

18,300

11,300

77.0

14,000

10,800

14,500

10,700

15,400

11,100

15,900

11,700

16,300

11,300

17,200

11,100

18,100

11,300

82.0

13,800

10,700

14,300

10,600

15,200

11,000

15,700

11,700

16,100

11,200

17,000

11,000

17,900

11,200

86.0

13,700

10,600

14,100

10,500

15,000

10,900

15,500

11,600

15,900

11,100

16,800

10,900

17,700

11,100

91.0

13,400

10,500

13,800

10,400

14,800

10,800

15,300

11,500

15,700

11,000

16,600

10,800

17,600

11,100

95.0

13,100

10,300

13,600

10,300

14,500

10,700

15,000

11,400

15,500

11,000

16,500

10,800

17,400

11,000

100.0

12,800

10,200

13,300

10,200

14,300

10,600

14,800

11,300

15,300

10,900

16,300

10,700

17,200

11,000

104.0

12,600

10,100

13,000

10,000

14,100

10,500

14,600

11,200

15,100

10,800

16,100

10,600

17,100

10,900

110.0

12,200

9,900

12,700

9,900

13,800

10,300

14,300

11,100

14,800

10,700

15,800

10,500

16,800

10,800

68.0

17,400

13,900

17,900

13,800

19,000

14,300

19,500

15,200

20,100

14,600

21,200

14,300

22,300

14,600

73.0

17,100

13,800

17,700

13,700

18,800

14,200

19,300

15,100

19,900

14,500

21,000

14,200

22,100

14,500

77.0

16,900

13,700

17,500

13,600

18,600

14,100

19,100

15,000

19,600

14,400

20,700

14,100

21,800

14,500

82.0

16,700

13,600

17,200

13,500

18,300

14,000

18,900

14,900

19,400

14,300

20,500

14,000

21,600

14,400

86.0

16,500

13,500

17,000

13,400

18,100

13,900

18,600

14,800

19,200

14,200

20,300

14,000

21,400

14,300

91.0

16,100

13,300

16,700

13,300

17,800

13,800

18,400

14,700

18,900

14,100

20,100

13,900

21,200

14,200

95.0

15,800

13,200

16,400

13,100

17,500

13,600

18,100

14,600

18,700

14,000

19,800

13,800

21,000

14,200

100.0

15,400

13,000

16,000

13,000

17,200

13,500

17,800

14,500

18,400

13,900

19,600

13,700

20,800

14,100

104.0

15,100

12,800

15,700

12,800

16,900

13,400

17,500

14,400

18,200

13,800

19,400

13,600

20,600

14,000

110.0

14,700

12,700

15,400

12,700

16,600

13,200

17,200

14,200

17,800

13,700

19,000

13,500

20,200

13,900

68.0

22,900

17,300

23,600

17,200

25,100

17,700

25,800

18,700

26,600

18,000

28,000

17,600

29,400

17,900

73.0

22,600

17,100

23,400

17,000

24,800

17,500

25,500

18,600

26,200

17,900

27,700

17,500

29,100

17,800

77.0

22,300

17,000

23,000

16,900

24,500

17,400

25,200

18,500

25,900

17,800

27,400

17,400

28,900

17,700

82.0

22,000

16,800

22,800

16,700

24,200

17,300

24,900

18,300

25,700

17,600

27,100

17,300

28,500

17,600

86.0

21,700

16,700

22,500

16,600

23,900

17,100

24,600

18,200

25,300

17,500

26,800

17,200

28,200

17,500

91.0

21,300

16,500

22,000

16,400

23,500

17,000

24,300

18,100

25,000

17,400

26,500

17,000

28,000

17,400

95.0

20,900

16,200

21,600

16,200

23,100

16,800

23,900

17,900

24,600

17,200

26,200

16,900

27,700

17,300

100.0

20,400

16,000

21,200

16,000

22,800

16,600

23,500

17,700

24,300

17,100

25,900

16,800

27,400

17,200

104.0

20,000

15,800

20,800

15,800

22,400

16,500

23,200

17,600

24,000

16,900

25,600

16,700

27,200

17,100

110.0

19,500

15,600

20,300

15,600

21,900

16,200

22,700

17,400

23,500

16,800

25,100

16,500

26,700

17,000

68.0

28,800

23,200

29,700

23,000

31,600

23,800

32,500

25,400

33,400

24,400

35,200

23,900

37,000

24,400

73.0

28,400

23,000

29,400

22,900

31,200

23,600

32,100

25,300

33,000

24,200

34,800

23,700

36,600

24,300

77.0

28,100

22,800

29,000

22,700

30,800

23,500

31,700

25,100

32,600

24,100

34,400

23,600

36,300

24,100

82.0

27,700

22,600

28,600

22,500

30,400

23,300

31,300

24,900

32,200

23,900

34,000

23,400

35,900

24,000

86.0

27,300

22,500

28,200

22,400

30,000

23,100

31,000

24,800

31,900

23,800

33,700

23,300

35,500

23,900

91.0

26,800

22,200

27,700

22,100

29,600

23,000

30,500

24,600

31,400

23,600

33,300

23,200

35,200

23,800

95.0

26,200

22,000

27,200

21,900

29,100

22,700

30,000

24,400

31,000

23,400

32,900

23,000

34,800

23,600

100.0

25,600

21,700

26,600

21,600

28,600

22,500

29,600

24,200

30,600

23,300

32,500

22,900

34,500

23,500

104.0

25,100

21,400

26,100

21,400

28,100

22,300

29,100

24,000

30,100

23,100

32,200

22,800

34,200

23,400

110.0

24,500

21,200

25,500

21,100

27,500

22,100

28,500

23,800

29,500

22,900

31,600

22,500

33,600

23,200

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-59

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PFFY-P-NEMU/NRMU-E


CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


71degF D.B.

73degF D.B.

77degF D.B.

81degF D.B.

82degF D.B.

86degF D.B.

90degF D.B.

59degF W.B.

61degF W.B.

64degF W.B.

66degF W.B.

68degF W.B.

72degF W.B.

75degF W.B.

degF D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

68.0

5,900

4,400

6,100

4,400

6,500

4,500

6,600

4,800

6,800

4,600

7,200

4,500

7,600

4,600

73.0

5,800

4,400

6,000

4,400

6,400

4,500

6,600

4,800

6,700

4,600

7,100

4,500

7,500

4,600

77.0

5,700

4,400

5,900

4,300

6,300

4,500

6,500

4,700

6,700

4,600

7,000

4,500

7,400

4,500

82.0

5,700

4,300

5,900

4,300

6,200

4,400

6,400

4,700

6,600

4,500

7,000

4,400

7,300

4,500

86.0

5,600

4,300

5,800

4,300

6,100

4,400

6,300

4,700

6,500

4,500

6,900

4,400

7,300

4,500

91.0

5,500

4,200

5,700

4,200

6,000

4,400

6,200

4,600

6,400

4,500

6,800

4,400

7,200

4,500

95.0

5,400

4,200

5,600

4,200

6,000

4,300

6,100

4,600

6,300

4,400

6,700

4,300

7,100

4,400

100.0

5,200

4,100

5,400

4,100

5,900

4,300

6,000

4,500

6,300

4,400

6,700

4,300

7,100

4,400

104.0

5,100

4,100

5,300

4,100

5,800

4,200

6,000

4,500

6,200

4,300

6,600

4,300

7,000

4,400

110.0

5,000

4,000

5,200

4,000

5,600

4,200

5,800

4,500

6,000

4,300

6,500

4,200

6,900

4,300

68.0

7,500

5,800

7,800

5,700

8,200

5,900

8,500

6,300

8,700

6,000

9,200

5,900

9,700

6,000

73.0

7,400

5,700

7,700

5,700

8,100

5,900

8,400

6,200

8,600

6,000

9,100

5,900

9,600

6,000

77.0

7,300

5,700

7,600

5,600

8,100

5,800

8,300

6,200

8,500

5,900

9,000

5,800

9,500

5,900

82.0

7,200

5,600

7,500

5,600

7,900

5,800

8,200

6,100

8,400

5,900

8,900

5,800

9,400

5,900

86.0

7,100

5,600

7,400

5,500

7,800

5,700

8,100

6,100

8,300

5,900

8,800

5,700

9,300

5,900

91.0

7,000

5,500

7,200

5,500

7,700

5,700

8,000

6,100

8,200

5,800

8,700

5,700

9,200

5,800

95.0

6,900

5,400

7,100

5,400

7,600

5,600

7,800

6,000

8,100

5,800

8,600

5,700

9,100

5,800

100.0

6,700

5,400

7,000

5,400

7,500

5,600

7,700

5,900

8,000

5,700

8,500

5,600

9,000

5,800

104.0

6,600

5,300

6,800

5,300

7,400

5,500

7,600

5,900

7,900

5,700

8,400

5,600

8,900

5,700

110.0

6,400

5,200

6,700

5,200

7,200

5,400

7,500

5,800

7,700

5,600

8,200

5,500

8,800

5,700

68.0

11,500

8,000

11,800

7,900

12,600

8,100

12,900

8,500

13,300

8,200

14,000

8,000

14,700

8,100

73.0

11,300

7,900

11,700

7,900

12,400

8,100

12,800

8,500

13,100

8,200

13,900

8,000

14,600

8,100

77.0

11,200

7,800

11,500

7,800

12,300

8,000

12,600

8,400

13,000

8,100

13,700

7,900

14,400

8,000

82.0

11,000

7,700

11,400

7,700

12,100

7,900

12,500

8,300

12,800

8,000

13,500

7,800

14,300

8,000

86.0

10,900

7,700

11,200

7,600

11,900

7,800

12,300

8,200

12,700

8,000

13,400

7,800

14,100

7,900

91.0

10,600

7,500

11,000

7,500

11,800

7,700

12,100

8,100

12,500

7,900

13,200

7,700

14,000

7,800

95.0

10,400

7,400

10,800

7,400

11,600

7,700

11,900

8,100

12,300

7,800

13,100

7,700

13,900

7,800

100.0

10,200

7,300

10,600

7,300

11,400

7,600

11,800

8,000

12,200

7,700

12,900

7,600

13,700

7,700

104.0

10,000

7,200

10,400

7,200

11,200

7,500

11,600

7,900

12,000

7,600

12,800

7,500

13,600

7,700

110.0

9,700

7,100

10,100

7,100

10,900

7,300

11,300

7,800

11,800

7,500

12,600

7,400

13,400

7,600

68.0

14,400

10,200

14,900

10,100

15,800

10,400

16,200

10,900

16,700

10,500

17,600

10,300

18,500

10,400

73.0

14,200

10,100

14,700

10,000

15,600

10,300

16,000

10,800

16,500

10,400

17,400

10,200

18,300

10,300

77.0

14,000

10,000

14,500

9,900

15,400

10,200

15,900

10,700

16,300

10,300

17,200

10,100

18,100

10,300

82.0

13,800

9,900

14,300

9,800

15,200

10,100

15,700

10,600

16,100

10,200

17,000

10,000

17,900

10,200

86.0

13,700

9,800

14,100

9,700

15,000

10,000

15,500

10,500

15,900

10,200

16,800

9,900

17,700

10,100

91.0

13,400

9,600

13,800

9,600

14,800

9,900

15,300

10,400

15,700

10,100

16,600

9,900

17,600

10,000

95.0

13,100

9,500

13,600

9,400

14,500

9,800

15,000

10,300

15,500

10,000

16,500

9,800

17,400

10,000

100.0

12,800

9,300

13,300

9,300

14,300

9,700

14,800

10,200

15,300

9,900

16,300

9,700

17,200

9,900

104.0

12,600

9,200

13,000

9,200

14,100

9,500

14,600

10,100

15,100

9,800

16,100

9,600

17,100

9,800

110.0

12,200

9,000

12,700

9,000

13,800

9,400

14,300

10,000

14,800

9,600

15,800

9,500

16,800

9,700

68.0

17,400

12,500

17,900

12,400

19,000

12,700

19,500

13,400

20,100

12,900

21,200

12,600

22,300

12,800

73.0

17,100

12,300

17,700

12,300

18,800

12,600

19,300

13,300

19,900

12,800

21,000

12,500

22,100

12,700

77.0

16,900

12,200

17,500

12,200

18,600

12,500

19,100

13,200

19,600

12,700

20,700

12,400

21,800

12,600

82.0

16,700

12,100

17,200

12,100

18,300

12,400

18,900

13,100

19,400

12,600

20,500

12,300

21,600

12,600

86.0

16,500

12,000

17,000

11,900

18,100

12,300

18,600

13,000

19,200

12,500

20,300

12,300

21,400

12,500

91.0

16,100

11,800

16,700

11,800

17,800

12,200

18,400

12,900

18,900

12,400

20,100

12,200

21,200

12,400

95.0

15,800

11,700

16,400

11,600

17,500

12,000

18,100

12,700

18,700

12,300

19,800

12,100

21,000

12,300

100.0

15,400

11,500

16,000

11,500

17,200

11,900

17,800

12,600

18,400

12,200

19,600

12,000

20,800

12,200

104.0

15,100

11,300

15,700

11,300

16,900

11,800

17,500

12,500

18,200

12,100

19,400

11,900

20,600

12,200

110.0

14,700

11,100

15,400

11,100

16,600

11,600

17,200

12,300

17,800

11,900

19,000

11,700

20,200

12,000

68.0

22,900

16,000

23,600

15,900

25,100

16,300

25,800

17,100

26,600

16,500

28,000

16,100

29,400

16,300

73.0

22,600

15,800

23,400

15,800

24,800

16,200

25,500

17,000

26,200

16,400

27,700

16,000

29,100

16,200

77.0

22,300

15,700

23,000

15,600

24,500

16,000

25,200

16,800

25,900

16,200

27,400

15,900

28,900

16,100

82.0

22,000

15,500

22,800

15,400

24,200

15,900

24,900

16,700

25,700

16,100

27,100

15,700

28,500

16,000

86.0

21,700

15,400

22,500

15,300

23,900

15,700

24,600

16,500

25,300

16,000

26,800

15,600

28,200

15,800

91.0

21,300

15,100

22,000

15,100

23,500

15,500

24,300

16,400

25,000

15,800

26,500

15,500

28,000

15,700

95.0

20,900

14,900

21,600

14,900

23,100

15,400

23,900

16,200

24,600

15,600

26,200

15,400

27,700

15,600

100.0

20,400

14,600

21,200

14,600

22,800

15,200

23,500

16,000

24,300

15,500

25,900

15,200

27,400

15,500

104.0

20,000

14,400

20,800

14,400

22,400

15,000

23,200

15,800

24,000

15,300

25,600

15,100

27,200

15,400

110.0

19,500

14,200

20,300

14,200

21,900

14,700

22,700

15,600

23,500

15,100

25,100

14,900

26,700

15,300

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-60

NOMINAL CAPACITY TABLES (Feb. 2009)

1. NOMINAL Capacity Tables in Fahrenheit

DATA U4

1-5-2. Heating CapacityPUMY-P36~48NHMU-A with All Indoor Units


Entering air temp

Entering air temp

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-61

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1. Cooing and Heating Capacity with PUHY,PURY-P72~96THMU/YHMU-A


2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PEFY-P-NMSU-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

NOMINAL
CAPACITY
TABLES

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

SHC
1.7

22.8

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.7

25.0

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

1.9

1.6

2.1

1.6

2.2

1.6

27.8

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

1.9

1.6

2.0

1.6

2.1

1.6

30.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

32.8

1.5

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

35.0

1.5

1.4

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

1.9

1.5

2.0

1.6

37.8

1.5

1.4

1.6

1.4

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

40.0

1.5

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.5

1.9

1.6

43.3

1.4

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.5

1.9

1.5

20.0

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

22.8

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

25.0

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.7

2.1

2.9

2.1

27.8

2.1

1.9

2.2

1.9

2.3

2.0

2.5

2.0

2.5

2.1

2.7

2.0

2.8

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.0

2.8

2.1

32.8

2.0

1.9

2.1

1.9

2.3

2.0

2.4

2.0

2.4

2.0

2.6

2.0

2.7

2.1

35.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.7

2.0

37.8

2.0

1.8

2.0

1.9

2.2

1.9

2.3

1.9

2.3

2.0

2.5

2.0

2.6

2.0

40.0

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.6

2.0

43.3

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.2

2.0

2.4

1.9

2.5

2.0

20.0

3.1

2.5

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.8

4.2

2.7

4.4

2.8

22.8

3.1

2.5

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.8

4.2

2.7

4.4

2.8

25.0

3.1

2.5

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.7

4.1

2.7

4.4

2.8

27.8

3.1

2.5

3.3

2.5

3.5

2.6

3.7

2.6

3.8

2.7

4.0

2.7

4.3

2.7

30.0

3.1

2.5

3.3

2.5

3.5

2.6

3.7

2.6

3.7

2.7

4.0

2.6

4.2

2.7

32.8

3.0

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.6

2.6

3.9

2.6

4.1

2.7

35.0

3.0

2.5

3.1

2.5

3.3

2.5

3.5

2.5

3.6

2.6

3.8

2.6

4.0

2.6

37.8

2.9

2.4

3.1

2.4

3.3

2.5

3.4

2.5

3.5

2.6

3.7

2.6

3.9

2.6

40.0

2.9

2.4

3.0

2.4

3.2

2.5

3.4

2.5

3.4

2.6

3.7

2.5

3.9

2.6

43.3

2.9

2.4

3.0

2.4

3.1

2.4

3.3

2.5

3.3

2.5

3.6

2.5

3.7

2.6

20.0

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.3

22.8

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.3

25.0

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.8

3.3

5.2

3.2

5.5

3.3

27.8

3.9

3.0

4.1

3.0

4.4

3.1

4.7

3.1

4.7

3.2

5.1

3.2

5.3

3.3

30.0

3.9

3.0

4.1

3.0

4.3

3.1

4.6

3.1

4.6

3.2

5.0

3.2

5.2

3.2

32.8

3.8

3.0

4.0

3.0

4.2

3.1

4.5

3.1

4.5

3.2

4.9

3.1

5.1

3.2

35.0

3.7

2.9

3.9

2.9

4.2

3.0

4.4

3.0

4.5

3.1

4.8

3.1

5.0

3.1

37.8

3.7

2.9

3.9

2.9

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.0

4.9

3.1

40.0

3.6

2.9

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.0

4.6

3.0

4.8

3.1

43.3

3.6

2.8

3.7

2.8

3.9

2.9

4.1

2.9

4.2

3.0

4.5

3.0

4.7

3.0

20.0

4.7

3.7

5.1

3.8

5.4

3.9

5.7

3.9

5.8

4.1

6.3

4.0

6.7

4.1

22.8

4.7

3.7

5.1

3.8

5.4

3.9

5.7

3.9

5.8

4.1

6.3

4.0

6.7

4.1

25.0

4.7

3.7

5.1

3.8

5.4

3.9

5.7

3.9

5.8

4.0

6.2

4.0

6.5

4.1

27.8

4.7

3.7

5.0

3.8

5.3

3.9

5.6

3.9

5.7

4.0

6.1

3.9

6.4

4.0

30.0

4.6

3.7

4.9

3.7

5.2

3.8

5.5

3.9

5.6

4.0

6.0

3.9

6.3

4.0

32.8

4.6

3.7

4.8

3.7

5.1

3.8

5.4

3.8

5.4

3.9

5.8

3.9

6.1

3.9

35.0

4.5

3.6

4.7

3.6

5.0

3.8

5.3

3.8

5.4

3.9

5.7

3.8

6.0

3.9

37.8

4.4

3.6

4.6

3.6

4.9

3.7

5.2

3.7

5.2

3.8

5.6

3.8

5.9

3.9
3.8

40.0

4.4

3.6

4.6

3.6

4.8

3.7

5.1

3.7

5.1

3.8

5.5

3.7

5.8

43.3

4.3

3.5

4.4

3.5

4.7

3.6

4.9

3.6

5.0

3.7

5.3

3.7

5.6

3.8

20.0

6.3

4.9

6.7

5.0

7.2

5.2

7.6

5.2

7.8

5.4

8.4

5.3

8.8

5.4

22.8

6.3

4.9

6.7

5.0

7.2

5.2

7.6

5.2

7.8

5.4

8.4

5.3

8.8

5.4

25.0

6.3

4.9

6.7

5.0

7.2

5.2

7.6

5.2

7.7

5.3

8.2

5.3

8.7

5.4

27.8

6.2

4.9

6.6

5.0

7.0

5.1

7.4

5.1

7.5

5.3

8.1

5.2

8.5

5.3

30.0

6.2

4.9

6.5

4.9

6.9

5.1

7.3

5.1

7.4

5.2

7.9

5.2

8.4

5.3

32.8

6.1

4.8

6.4

4.8

6.8

5.0

7.1

5.0

7.2

5.1

7.8

5.1

8.2

5.2

35.0

6.0

4.8

6.3

4.8

6.6

4.9

7.0

5.0

7.1

5.1

7.6

5.0

8.0

5.1

37.8

5.9

4.7

6.1

4.7

6.5

4.9

6.9

4.9

7.0

5.0

7.4

5.0

7.8

5.1

40.0

5.8

4.7

6.1

4.7

6.4

4.8

6.7

4.8

6.8

5.0

7.3

4.9

7.7

5.0

43.3

5.7

4.6

5.9

4.6

6.2

4.8

6.6

4.8

6.6

4.9

7.1

4.8

7.5

4.9

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-62

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.9

2.7

4.2

2.8

4.5

2.9

4.8

2.9

4.9

3.0

5.2

2.9

5.5

SHC
3.0

22.8

3.9

2.7

4.2

2.8

4.5

2.9

4.8

2.9

4.9

3.0

5.2

2.9

5.5

3.0

25.0

3.9

2.7

4.2

2.8

4.5

2.9

4.8

2.9

4.8

2.9

5.2

2.9

5.5

3.0

27.8

3.9

2.7

4.1

2.8

4.4

2.8

4.7

2.8

4.7

2.9

5.1

2.9

5.3

2.9

30.0

3.9

2.7

4.1

2.7

4.3

2.8

4.6

2.8

4.6

2.9

5.0

2.8

5.2

2.9

32.8

3.8

2.7

4.0

2.7

4.2

2.8

4.5

2.8

4.5

2.8

4.9

2.8

5.1

2.8

35.0

3.7

2.6

3.9

2.6

4.2

2.7

4.4

2.7

4.5

2.8

4.8

2.7

5.0

2.8

37.8

3.7

2.6

3.9

2.6

4.1

2.7

4.3

2.7

4.4

2.7

4.7

2.7

4.9

2.7

40.0

3.6

2.6

3.8

2.6

4.0

2.6

4.2

2.6

4.3

2.7

4.6

2.7

4.8

2.7

43.3

3.6

2.5

3.7

2.5

3.9

2.6

4.1

2.6

4.2

2.6

4.5

2.6

4.7

2.6

20.0

4.7

3.3

5.1

3.4

5.4

3.5

5.7

3.5

5.9

3.6

6.3

3.6

6.7

3.7

22.8

4.7

3.3

5.1

3.4

5.4

3.5

5.7

3.5

5.9

3.6

6.3

3.6

6.7

3.7

25.0

4.7

3.3

5.1

3.4

5.4

3.5

5.7

3.5

5.8

3.6

6.2

3.6

6.6

3.6

27.8

4.7

3.3

5.0

3.4

5.3

3.5

5.6

3.5

5.7

3.5

6.1

3.5

6.4

3.6

30.0

4.6

3.3

4.9

3.3

5.2

3.4

5.5

3.4

5.6

3.5

6.0

3.5

6.3

3.5

32.8

4.6

3.2

4.8

3.3

5.1

3.4

5.4

3.4

5.5

3.4

5.9

3.4

6.2

3.4

35.0

4.5

3.2

4.7

3.2

5.0

3.3

5.3

3.3

5.4

3.4

5.8

3.4

6.1

3.4

37.8

4.4

3.2

4.6

3.2

4.9

3.3

5.2

3.3

5.3

3.3

5.6

3.3

5.9

3.3

40.0

4.4

3.1

4.6

3.2

4.8

3.2

5.1

3.2

5.2

3.3

5.5

3.3

5.8

3.3

43.3

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.0

3.2

5.4

3.2

5.6

3.2

20.0

6.2

4.4

6.7

4.5

7.2

4.6

7.6

4.6

7.7

4.8

8.3

4.7

8.8

4.8

22.8

6.2

4.4

6.7

4.5

7.2

4.6

7.6

4.6

7.7

4.8

8.3

4.7

8.8

4.8

25.0

6.2

4.4

6.7

4.5

7.2

4.6

7.6

4.6

7.7

4.7

8.2

4.7

8.7

4.7

27.8

6.2

4.4

6.6

4.4

7.0

4.6

7.4

4.6

7.5

4.7

8.0

4.6

8.5

4.7

30.0

6.1

4.3

6.5

4.4

6.9

4.5

7.3

4.5

7.4

4.6

7.9

4.5

8.3

4.6

32.8

6.0

4.3

6.4

4.3

6.7

4.4

7.1

4.4

7.2

4.5

7.7

4.5

8.1

4.5

35.0

6.0

4.2

6.3

4.3

6.6

4.4

7.0

4.4

7.1

4.5

7.6

4.4

8.0

4.5

37.8

5.9

4.2

6.1

4.2

6.5

4.3

6.8

4.3

6.9

4.4

7.4

4.3

7.8

4.4

40.0

5.8

4.1

6.0

4.1

6.4

4.2

6.7

4.2

6.8

4.3

7.3

4.3

7.7

4.3

43.3

5.7

4.1

5.9

4.1

6.2

4.1

6.5

4.2

6.6

4.2

7.1

4.2

7.4

4.2

20.0

7.0

5.0

7.6

5.1

8.1

5.3

8.6

5.3

8.7

5.4

9.4

5.4

10.0

5.5

22.8

7.0

5.0

7.6

5.1

8.1

5.3

8.6

5.3

8.7

5.4

9.4

5.4

10.0

5.5

25.0

7.0

5.0

7.6

5.1

8.1

5.3

8.5

5.3

8.7

5.4

9.3

5.4

9.8

5.4

27.8

7.0

5.0

7.4

5.1

7.9

5.2

8.4

5.2

8.5

5.3

9.1

5.3

9.6

5.3

30.0

6.9

4.9

7.3

5.0

7.8

5.1

8.2

5.2

8.3

5.3

8.9

5.2

9.4

5.3

32.8

6.8

4.9

7.2

4.9

7.6

5.1

8.0

5.1

8.2

5.2

8.7

5.1

9.2

5.2

35.0

6.7

4.8

7.1

4.9

7.5

5.0

7.9

5.0

8.0

5.1

8.6

5.1

9.0

5.1

37.8

6.6

4.8

6.9

4.8

7.3

4.9

7.7

4.9

7.8

5.0

8.4

5.0

8.8

5.0

40.0

6.5

4.7

6.8

4.7

7.2

4.9

7.6

4.9

7.7

5.0

8.2

4.9

8.6

5.0

43.3

6.4

4.7

6.6

4.7

7.0

4.8

7.4

4.8

7.5

4.9

8.0

4.8

8.4

4.9

20.0

7.8

5.6

8.4

5.7

9.0

5.9

9.5

5.9

9.7

6.1

10.5

6.0

11.1

6.1

22.8

7.8

5.6

8.4

5.7

9.0

5.9

9.5

5.9

9.7

6.1

10.5

6.0

11.1

6.1

25.0

7.8

5.6

8.4

5.7

9.0

5.9

9.5

5.9

9.7

6.0

10.3

6.0

10.9

6.0

27.8

7.8

5.6

8.3

5.6

8.8

5.8

9.3

5.8

9.5

5.9

10.1

5.9

10.7

5.9

30.0

7.7

5.5

8.1

5.6

8.7

5.7

9.2

5.7

9.3

5.9

9.9

5.8

10.5

5.9

32.8

7.6

5.4

8.0

5.5

8.5

5.6

9.0

5.6

9.1

5.8

9.7

5.7

10.2

5.8

35.0

7.5

5.4

7.9

5.4

8.3

5.6

8.8

5.6

8.9

5.7

9.5

5.6

10.1

5.7

37.8

7.4

5.3

7.7

5.3

8.1

5.5

8.6

5.5

8.7

5.6

9.3

5.5

9.8

5.6

40.0

7.3

5.3

7.6

5.3

8.0

5.4

8.4

5.4

8.6

5.5

9.2

5.5

9.6

5.5

43.3

7.1

5.2

7.4

5.2

7.8

5.3

8.2

5.3

8.3

5.4

8.9

5.4

9.3

5.4

20.0

9.5

6.9

10.2

7.0

10.8

7.3

11.5

7.3

11.7

7.5

12.6

7.4

13.4

7.6

22.8

9.5

6.9

10.2

7.0

10.8

7.3

11.5

7.3

11.7

7.5

12.6

7.4

13.4

7.6

25.0

9.5

6.9

10.2

7.0

10.8

7.3

11.4

7.3

11.6

7.4

12.4

7.4

13.1

7.5

27.8

9.4

6.9

10.0

6.9

10.6

7.2

11.2

7.2

11.4

7.3

12.2

7.2

12.9

7.4

30.0

9.3

6.8

9.8

6.9

10.4

7.1

11.0

7.1

11.2

7.3

12.0

7.2

12.6

7.3

32.8

9.1

6.7

9.6

6.8

10.2

7.0

10.8

7.0

10.9

7.1

11.7

7.1

12.3

7.2

35.0

9.0

6.7

9.5

6.7

10.0

6.9

10.6

6.9

10.7

7.1

11.5

7.0

12.1

7.1

37.8

8.9

6.6

9.3

6.6

9.8

6.8

10.4

6.8

10.5

7.0

11.2

6.9

11.8

7.0

40.0

8.8

6.5

9.1

6.5

9.6

6.7

10.2

6.7

10.3

6.9

11.0

6.8

11.6

6.9

43.3

8.6

6.4

8.9

6.4

9.3

6.6

9.9

6.6

10.0

6.7

10.7

6.7

11.3

6.8

20.0

12.6

8.8

13.5

9.0

14.4

9.3

15.3

9.3

15.6

9.5

16.8

9.5

17.8

9.6

22.8

12.6

8.8

13.5

9.0

14.4

9.3

15.3

9.3

15.6

9.5

16.8

9.5

17.8

9.6

25.0

12.6

8.8

13.5

9.0

14.4

9.3

15.2

9.3

15.5

9.5

16.6

9.4

17.5

9.5

27.8

12.5

8.7

13.3

8.9

14.1

9.1

14.9

9.2

15.1

9.3

16.2

9.2

17.1

9.4

30.0

12.4

8.7

13.1

8.8

13.9

9.0

14.7

9.0

14.9

9.2

15.9

9.1

16.8

9.2

32.8

12.2

8.6

12.8

8.6

13.6

8.9

14.4

8.9

14.6

9.1

15.6

8.9

16.4

9.1

35.0

12.0

8.5

12.6

8.5

13.3

8.7

14.1

8.8

14.3

8.9

15.3

8.8

16.1

8.9

37.8

11.8

8.4

12.4

8.4

13.0

8.6

13.8

8.6

14.0

8.8

14.9

8.7

15.7

8.8

40.0

11.7

8.3

12.2

8.3

12.8

8.5

13.5

8.5

13.7

8.7

14.7

8.6

15.4

8.7

43.3

11.4

8.2

11.8

8.1

12.4

8.3

13.2

8.3

13.3

8.5

14.3

8.4

15.0

8.5

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-63

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

14.1

10.2

15.1

10.4

16.1

10.7

17.1

10.8

17.5

11.1

18.8

11.0

19.9

11.2

22.8

14.1

10.2

15.1

10.4

16.1

10.7

17.1

10.8

17.5

11.1

18.8

11.0

19.9

11.2

25.0

14.1

10.2

15.1

10.4

16.1

10.7

17.1

10.8

17.3

11.0

18.5

10.9

19.6

11.0

27.8

14.0

10.1

14.9

10.3

15.8

10.6

16.7

10.6

17.0

10.8

18.2

10.7

19.2

10.9

30.0

13.9

10.0

14.6

10.2

15.6

10.4

16.4

10.5

16.7

10.7

17.9

10.6

18.8

10.7

32.8

13.6

9.9

14.3

10.0

15.2

10.3

16.1

10.3

16.3

10.5

17.5

10.4

18.4

10.6

35.0

13.5

9.8

14.1

9.9

14.9

10.2

15.8

10.2

16.0

10.4

17.1

10.3

18.1

10.4

37.8

13.2

9.7

13.8

9.8

14.6

10.0

15.5

10.0

15.7

10.3

16.7

10.1

17.6

10.3

40.0

13.1

9.6

13.6

9.6

14.3

9.9

15.2

9.9

15.4

10.1

16.4

10.0

17.3

10.2

43.3

12.8

9.5

13.3

9.5

13.9

9.7

14.8

9.7

14.9

9.9

16.0

9.8

16.8

10.0

20.0

18.8

13.3

20.2

13.7

21.6

14.1

22.9

14.2

23.3

14.5

25.1

14.4

26.6

14.7

22.8

18.8

13.3

20.2

13.7

21.6

14.1

22.9

14.2

23.3

14.5

25.1

14.4

26.6

14.7

25.0

18.8

13.3

20.2

13.7

21.6

14.1

22.8

14.1

23.1

14.4

24.8

14.3

26.2

14.5

27.8

18.7

13.3

19.8

13.5

21.1

13.9

22.3

13.9

22.7

14.2

24.2

14.0

25.6

14.2

30.0

18.5

13.2

19.5

13.3

20.8

13.7

21.9

13.7

22.3

14.0

23.8

13.9

25.2

14.1

32.8

18.2

13.0

19.2

13.1

20.3

13.5

21.5

13.5

21.8

13.8

23.3

13.6

24.6

13.8

35.0

18.0

12.9

18.9

13.0

20.0

13.3

21.1

13.3

21.4

13.6

22.9

13.5

24.1

13.7

37.8

17.7

12.7

18.5

12.8

19.5

13.1

20.6

13.1

20.9

13.4

22.4

13.2

23.5

13.4

40.0

17.4

12.6

18.2

12.6

19.2

12.9

20.3

13.0

20.5

13.2

22.0

13.1

23.1

13.3

43.3

17.1

12.4

17.7

12.4

18.6

12.7

19.7

12.7

20.0

13.0

21.4

12.8

22.4

13.0

20.0

25.1

17.9

26.9

18.4

28.7

18.9

30.4

19.0

31.1

19.5

33.5

19.3

35.4

19.7

22.8

25.1

17.9

26.9

18.4

28.7

18.9

30.4

19.0

31.1

19.5

33.5

19.3

35.4

19.7

25.0

25.1

17.9

26.9

18.4

28.7

18.9

30.3

19.0

30.8

19.4

33.0

19.1

34.8

19.5

27.8

25.0

17.9

26.4

18.1

28.2

18.7

29.7

18.7

30.2

19.1

32.3

18.8

34.1

19.2

30.0

24.6

17.7

26.0

17.9

27.7

18.4

29.2

18.5

29.7

18.9

31.8

18.6

33.5

18.9

32.8

24.3

17.5

25.5

17.6

27.1

18.1

28.6

18.2

29.0

18.6

31.1

18.3

32.7

18.6

35.0

23.9

17.3

25.1

17.4

26.6

17.9

28.1

17.9

28.5

18.3

30.5

18.1

32.1

18.4

37.8

23.5

17.1

24.6

17.2

26.0

17.6

27.5

17.7

27.8

18.0

29.8

17.8

31.3

18.1

40.0

23.2

17.0

24.2

17.0

25.5

17.4

27.0

17.4

27.3

17.8

29.3

17.6

30.7

17.9

43.3

22.8

16.7

23.6

16.7

24.8

17.0

26.2

17.1

26.6

17.5

28.4

17.3

29.8

17.5

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-64

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

SHC
1.4

22.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

1.4

25.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.2

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.1

1.3

2.2

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.0

1.3

2.1

1.4

32.8

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

40.0

1.5

1.2

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.3

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.8

1.2

1.9

1.3

20.0

2.1

1.5

2.2

1.6

2.4

1.6

2.5

1.6

2.5

1.7

2.7

1.7

2.9

1.7

22.8

2.1

1.5

2.2

1.6

2.4

1.6

2.5

1.6

2.5

1.7

2.7

1.7

2.9

1.7

25.0

2.1

1.5

2.2

1.6

2.4

1.6

2.5

1.6

2.5

1.7

2.7

1.7

2.9

1.7

27.8

2.0

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.6

1.6

2.8

1.7

30.0

2.0

1.5

2.1

1.5

2.3

1.6

2.4

1.6

2.4

1.6

2.6

1.6

2.7

1.6

32.8

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.7

1.6

35.0

2.0

1.5

2.1

1.5

2.2

1.5

2.3

1.6

2.3

1.6

2.5

1.6

2.6

1.6

37.8

1.9

1.5

2.0

1.5

2.1

1.5

2.2

1.5

2.3

1.6

2.4

1.5

2.6

1.6

40.0

1.9

1.5

2.0

1.5

2.1

1.5

2.2

1.5

2.2

1.6

2.4

1.5

2.5

1.6

43.3

1.9

1.5

1.9

1.4

2.0

1.5

2.1

1.5

2.2

1.5

2.3

1.5

2.4

1.5

20.0

3.1

2.2

3.4

2.3

3.6

2.3

3.8

2.4

3.9

2.4

4.2

2.4

4.4

2.4

22.8

3.1

2.2

3.4

2.3

3.6

2.3

3.8

2.4

3.9

2.4

4.2

2.4

4.4

2.4

25.0

3.1

2.2

3.4

2.3

3.6

2.3

3.8

2.4

3.8

2.4

4.1

2.4

4.3

2.4

27.8

3.1

2.2

3.3

2.2

3.5

2.3

3.7

2.3

3.8

2.4

4.0

2.3

4.2

2.4

30.0

3.1

2.2

3.2

2.2

3.4

2.3

3.6

2.3

3.7

2.3

4.0

2.3

4.2

2.3

32.8

3.0

2.2

3.2

2.2

3.4

2.2

3.6

2.3

3.6

2.3

3.9

2.3

4.1

2.3

35.0

3.0

2.2

3.1

2.2

3.3

2.2

3.5

2.2

3.5

2.3

3.8

2.2

4.0

2.3

37.8

2.9

2.1

3.1

2.1

3.2

2.2

3.4

2.2

3.5

2.2

3.7

2.2

3.9

2.2

40.0

2.9

2.1

3.0

2.1

3.2

2.2

3.4

2.2

3.4

2.2

3.6

2.2

3.8

2.2

43.3

2.8

2.1

2.9

2.1

3.1

2.1

3.3

2.1

3.3

2.2

3.5

2.1

3.7

2.2

20.0

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.4

22.8

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.4

25.0

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.8

3.3

5.2

3.3

5.5

3.3

27.8

3.9

3.0

4.1

3.1

4.4

3.2

4.7

3.2

4.7

3.3

5.1

3.2

5.3

3.3

30.0

3.9

3.0

4.1

3.0

4.3

3.1

4.6

3.1

4.6

3.2

5.0

3.2

5.2

3.2

32.8

3.8

3.0

4.0

3.0

4.2

3.1

4.5

3.1

4.5

3.2

4.9

3.1

5.1

3.2

35.0

3.7

3.0

3.9

3.0

4.2

3.1

4.4

3.1

4.5

3.1

4.8

3.1

5.0

3.2

37.8

3.7

2.9

3.9

2.9

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.1

40.0

3.6

2.9

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.0

4.8

3.1

43.3

3.6

2.9

3.7

2.9

3.9

2.9

4.1

2.9

4.2

3.0

4.5

3.0

4.7

3.0

20.0

4.7

3.6

5.1

3.7

5.4

3.8

5.7

3.8

5.9

3.9

6.3

3.9

6.7

3.9

22.8

4.7

3.6

5.1

3.7

5.4

3.8

5.7

3.8

5.9

3.9

6.3

3.9

6.7

3.9

25.0

4.7

3.6

5.1

3.7

5.4

3.8

5.7

3.8

5.8

3.9

6.2

3.8

6.6

3.9

27.8

4.7

3.6

5.0

3.6

5.3

3.7

5.6

3.7

5.7

3.8

6.1

3.8

6.4

3.9

30.0

4.6

3.5

4.9

3.6

5.2

3.7

5.5

3.7

5.6

3.8

6.0

3.7

6.3

3.8

32.8

4.6

3.5

4.8

3.5

5.1

3.6

5.4

3.6

5.5

3.7

5.9

3.7

6.2

3.8

35.0

4.5

3.5

4.7

3.5

5.0

3.6

5.3

3.6

5.4

3.7

5.8

3.6

6.1

3.7

37.8

4.4

3.4

4.6

3.5

4.9

3.5

5.2

3.6

5.3

3.6

5.6

3.6

5.9

3.7
3.6

40.0

4.4

3.4

4.6

3.4

4.8

3.5

5.1

3.5

5.2

3.6

5.5

3.6

5.8

43.3

4.3

3.4

4.5

3.4

4.7

3.4

5.0

3.5

5.0

3.5

5.4

3.5

5.6

3.6

20.0

6.2

4.7

6.7

4.8

7.2

5.0

7.6

5.0

7.7

5.1

8.3

5.1

8.8

5.2

22.8

6.2

4.7

6.7

4.8

7.2

5.0

7.6

5.0

7.7

5.1

8.3

5.1

8.8

5.2

25.0

6.2

4.7

6.7

4.8

7.2

5.0

7.6

5.0

7.7

5.1

8.2

5.0

8.7

5.1

27.8

6.2

4.7

6.6

4.8

7.0

4.9

7.4

4.9

7.5

5.0

8.0

5.0

8.5

5.1

30.0

6.1

4.7

6.5

4.7

6.9

4.9

7.3

4.9

7.4

5.0

7.9

4.9

8.3

5.0

32.8

6.0

4.6

6.4

4.6

6.7

4.8

7.1

4.8

7.2

4.9

7.7

4.9

8.1

4.9

35.0

6.0

4.6

6.3

4.6

6.6

4.7

7.0

4.7

7.1

4.9

7.6

4.8

8.0

4.9

37.8

5.9

4.5

6.1

4.5

6.5

4.7

6.8

4.7

6.9

4.8

7.4

4.7

7.8

4.8

40.0

5.8

4.5

6.0

4.5

6.4

4.6

6.7

4.6

6.8

4.7

7.3

4.7

7.7

4.8

43.3

5.7

4.4

5.9

4.4

6.2

4.5

6.5

4.5

6.6

4.7

7.1

4.6

7.4

4.7

20.0

7.0

5.2

7.6

5.3

8.1

5.5

8.6

5.5

8.7

5.7

9.4

5.6

10.0

5.8

22.8

7.0

5.2

7.6

5.3

8.1

5.5

8.6

5.5

8.7

5.7

9.4

5.6

10.0

5.8

25.0

7.0

5.2

7.6

5.3

8.1

5.5

8.5

5.5

8.7

5.7

9.3

5.6

9.8

5.7

27.8

7.0

5.2

7.4

5.3

7.9

5.4

8.4

5.5

8.5

5.6

9.1

5.5

9.6

5.6

30.0

6.9

5.2

7.3

5.2

7.8

5.4

8.2

5.4

8.3

5.5

8.9

5.5

9.4

5.6

32.8

6.8

5.1

7.2

5.2

7.6

5.3

8.0

5.3

8.2

5.4

8.7

5.4

9.2

5.5

35.0

6.7

5.1

7.1

5.1

7.5

5.2

7.9

5.3

8.0

5.4

8.6

5.3

9.0

5.4

37.8

6.6

5.0

6.9

5.0

7.3

5.2

7.7

5.2

7.8

5.3

8.4

5.2

8.8

5.3

40.0

6.5

5.0

6.8

5.0

7.2

5.1

7.6

5.1

7.7

5.2

8.2

5.2

8.6

5.3

43.3

6.4

4.9

6.6

4.9

7.0

5.0

7.4

5.0

7.5

5.2

8.0

5.1

8.4

5.2

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-65

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

7.8

5.8

8.4

5.9

9.0

6.1

9.5

6.1

9.7

6.3

10.5

6.2

11.1

6.3

22.8

7.8

5.8

8.4

5.9

9.0

6.1

9.5

6.1

9.7

6.3

10.5

6.2

11.1

6.3

25.0

7.8

5.8

8.4

5.9

9.0

6.1

9.5

6.1

9.7

6.2

10.3

6.2

10.9

6.3

27.8

7.8

5.7

8.3

5.8

8.8

6.0

9.3

6.0

9.5

6.2

10.1

6.1

10.7

6.2

30.0

7.7

5.7

8.1

5.8

8.7

5.9

9.2

5.9

9.3

6.1

9.9

6.0

10.5

6.1

32.8

7.6

5.6

8.0

5.7

8.5

5.8

9.0

5.9

9.1

6.0

9.7

5.9

10.2

6.0

35.0

7.5

5.6

7.9

5.6

8.3

5.8

8.8

5.8

8.9

5.9

9.5

5.8

10.1

5.9

37.8

7.4

5.5

7.7

5.5

8.1

5.7

8.6

5.7

8.7

5.8

9.3

5.8

9.8

5.9

40.0

7.3

5.5

7.6

5.5

8.0

5.6

8.4

5.6

8.6

5.8

9.2

5.7

9.6

5.8

43.3

7.1

5.4

7.4

5.4

7.8

5.5

8.2

5.5

8.3

5.7

8.9

5.6

9.3

5.7

20.0

9.5

7.2

10.2

7.3

10.8

7.5

11.5

7.6

11.7

7.8

12.6

7.7

13.4

7.9

22.8

9.5

7.2

10.2

7.3

10.8

7.5

11.5

7.6

11.7

7.8

12.6

7.7

13.4

7.9

25.0

9.5

7.2

10.2

7.3

10.8

7.5

11.4

7.6

11.6

7.8

12.4

7.7

13.1

7.8
7.7

27.8

9.4

7.1

10.0

7.2

10.6

7.4

11.2

7.5

11.4

7.6

12.2

7.5

12.9

30.0

9.3

7.1

9.8

7.1

10.4

7.4

11.0

7.4

11.2

7.6

12.0

7.5

12.6

7.6

32.8

9.1

7.0

9.6

7.0

10.2

7.3

10.8

7.3

10.9

7.5

11.7

7.4

12.3

7.5

35.0

9.0

6.9

9.5

7.0

10.0

7.2

10.6

7.2

10.7

7.4

11.5

7.3

12.1

7.4

37.8

8.9

6.9

9.3

6.9

9.8

7.1

10.4

7.1

10.5

7.3

11.2

7.2

11.8

7.3

40.0

8.8

6.8

9.1

6.8

9.6

7.0

10.2

7.0

10.3

7.2

11.0

7.1

11.6

7.2

43.3

8.6

6.7

8.9

6.7

9.3

6.9

9.9

6.9

10.0

7.1

10.7

7.0

11.3

7.1

20.0

12.6

9.1

13.5

9.4

14.4

9.7

15.3

9.7

15.6

10.0

16.8

9.9

17.8

10.1
10.1

22.8

12.6

9.1

13.5

9.4

14.4

9.7

15.3

9.7

15.6

10.0

16.8

9.9

17.8

25.0

12.6

9.1

13.5

9.4

14.4

9.7

15.2

9.7

15.5

9.9

16.6

9.8

17.5

9.9

27.8

12.5

9.1

13.3

9.2

14.1

9.5

14.9

9.5

15.1

9.8

16.2

9.6

17.1

9.8

30.0

12.4

9.0

13.1

9.1

13.9

9.4

14.7

9.4

14.9

9.6

15.9

9.5

16.8

9.7

32.8

12.2

8.9

12.8

9.0

13.6

9.3

14.4

9.3

14.6

9.5

15.6

9.4

16.4

9.5

35.0

12.0

8.9

12.6

8.9

13.3

9.1

14.1

9.2

14.3

9.4

15.3

9.3

16.1

9.4

37.8

11.8

8.8

12.4

8.8

13.0

9.0

13.8

9.0

14.0

9.2

14.9

9.1

15.7

9.3

40.0

11.7

8.7

12.2

8.7

12.8

8.9

13.5

8.9

13.7

9.1

14.7

9.0

15.4

9.2

43.3

11.4

8.6

11.8

8.5

12.4

8.7

13.2

8.8

13.3

9.0

14.3

8.9

15.0

9.0

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-66

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSIus

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PMFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.3

SHC
1.7

22.8

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.3

1.7

25.0

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.7

27.8

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

1.9

1.6

2.1

1.6

2.2

1.6

30.0

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.5

1.9

1.6

2.0

1.6

2.1

1.6

32.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

35.0

1.5

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

37.8

1.5

1.4

1.6

1.4

1.7

1.5

1.8

1.5

1.8

1.6

1.9

1.5

2.0

1.6

40.0

1.5

1.4

1.6

1.4

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.5

2.0

1.6

43.3

1.5

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.5

1.9

1.5

20.0

2.1

1.8

2.2

1.8

2.4

1.9

2.5

1.9

2.5

2.0

2.7

1.9

2.9

2.0

22.8

2.1

1.8

2.2

1.8

2.4

1.9

2.5

1.9

2.5

2.0

2.7

1.9

2.9

2.0

25.0

2.1

1.8

2.2

1.8

2.4

1.9

2.5

1.9

2.5

2.0

2.7

1.9

2.9

2.0

27.8

2.0

1.8

2.2

1.8

2.3

1.9

2.4

1.9

2.5

1.9

2.6

1.9

2.8

2.0

30.0

2.0

1.8

2.1

1.8

2.3

1.9

2.4

1.9

2.4

1.9

2.6

1.9

2.7

1.9

32.8

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.5

1.9

2.7

1.9

35.0

2.0

1.7

2.1

1.8

2.2

1.8

2.3

1.8

2.3

1.9

2.5

1.9

2.6

1.9

37.8

1.9

1.7

2.0

1.7

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.8

2.6

1.9

40.0

1.9

1.7

2.0

1.7

2.1

1.8

2.2

1.8

2.2

1.8

2.4

1.8

2.5

1.9

43.3

1.9

1.7

1.9

1.7

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.8

20.0

3.1

2.3

3.4

2.4

3.6

2.4

3.8

2.5

3.9

2.5

4.2

2.5

4.4

2.5

22.8

3.1

2.3

3.4

2.4

3.6

2.4

3.8

2.5

3.9

2.5

4.2

2.5

4.4

2.5

25.0

3.1

2.3

3.4

2.4

3.6

2.4

3.8

2.4

3.8

2.5

4.1

2.5

4.3

2.5

27.8

3.1

2.3

3.3

2.3

3.5

2.4

3.7

2.4

3.8

2.5

4.0

2.4

4.2

2.5

30.0

3.1

2.3

3.2

2.3

3.4

2.4

3.6

2.4

3.7

2.4

4.0

2.4

4.2

2.5

32.8

3.0

2.3

3.2

2.3

3.4

2.3

3.6

2.4

3.6

2.4

3.9

2.4

4.1

2.4

35.0

3.0

2.2

3.1

2.3

3.3

2.3

3.5

2.3

3.5

2.4

3.8

2.4

4.0

2.4

37.8

2.9

2.2

3.1

2.2

3.2

2.3

3.4

2.3

3.5

2.3

3.7

2.3

3.9

2.4

40.0

2.9

2.2

3.0

2.2

3.2

2.3

3.4

2.3

3.4

2.3

3.6

2.3

3.8

2.3

43.3

2.8

2.2

2.9

2.2

3.1

2.2

3.3

2.2

3.3

2.3

3.5

2.3

3.7

2.3

20.0

3.9

2.8

4.2

2.9

4.5

3.0

4.8

3.0

4.9

3.1

5.2

3.0

5.5

3.1

22.8

3.9

2.8

4.2

2.9

4.5

3.0

4.8

3.0

4.9

3.1

5.2

3.0

5.5

3.1

25.0

3.9

2.8

4.2

2.9

4.5

3.0

4.8

3.0

4.8

3.1

5.2

3.0

5.5

3.1

27.8

3.9

2.8

4.1

2.9

4.4

2.9

4.7

2.9

4.7

3.0

5.1

3.0

5.3

3.0

30.0

3.9

2.8

4.1

2.8

4.3

2.9

4.6

2.9

4.6

3.0

5.0

2.9

5.2

3.0

32.8

3.8

2.8

4.0

2.8

4.2

2.9

4.5

2.9

4.5

2.9

4.9

2.9

5.1

2.9

35.0

3.7

2.7

3.9

2.7

4.2

2.8

4.4

2.8

4.5

2.9

4.8

2.9

5.0

2.9

37.8

3.7

2.7

3.9

2.7

4.1

2.8

4.3

2.8

4.4

2.8

4.7

2.8

4.9

2.9

40.0

3.6

2.7

3.8

2.7

4.0

2.7

4.2

2.7

4.3

2.8

4.6

2.8

4.8

2.8

43.3

3.6

2.6

3.7

2.6

3.9

2.7

4.1

2.7

4.2

2.8

4.5

2.7

4.7

2.8

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-67

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PLFY-P-NCMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.1

2.9

2.1

22.8

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.1

2.9

2.1

25.0

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.0

2.9

2.1

27.8

2.0

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.0

2.8

2.1

30.0

2.0

1.9

2.1

1.9

2.3

2.0

2.4

2.0

2.4

2.0

2.6

2.0

2.7

2.1
2.0

32.8

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.7

35.0

2.0

1.8

2.1

1.9

2.2

1.9

2.3

1.9

2.3

2.0

2.5

2.0

2.6

2.0

37.8

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.6

2.0
2.0

40.0

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.2

2.0

2.4

1.9

2.5

43.3

1.9

1.8

1.9

1.8

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

20.0

3.1

2.5

3.4

2.5

3.6

2.6

3.8

2.6

3.9

2.7

4.2

2.7

4.4

2.8
2.8

22.8

3.1

2.5

3.4

2.5

3.6

2.6

3.8

2.6

3.9

2.7

4.2

2.7

4.4

25.0

3.1

2.5

3.4

2.5

3.6

2.6

3.8

2.6

3.8

2.7

4.1

2.7

4.3

2.7

27.8

3.1

2.5

3.3

2.5

3.5

2.6

3.7

2.6

3.8

2.7

4.0

2.6

4.2

2.7

30.0

3.1

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.7

2.7

4.0

2.6

4.2

2.7

32.8

3.0

2.4

3.2

2.5

3.4

2.5

3.6

2.6

3.6

2.6

3.9

2.6

4.1

2.6

35.0

3.0

2.4

3.1

2.4

3.3

2.5

3.5

2.5

3.5

2.6

3.8

2.6

4.0

2.6
2.6

37.8

2.9

2.4

3.1

2.4

3.2

2.5

3.4

2.5

3.5

2.6

3.7

2.5

3.9

40.0

2.9

2.4

3.0

2.4

3.2

2.5

3.4

2.5

3.4

2.5

3.6

2.5

3.8

2.6

43.3

2.8

2.4

2.9

2.4

3.1

2.4

3.3

2.4

3.3

2.5

3.5

2.5

3.7

2.5
3.2

20.0

3.9

2.9

4.2

3.0

4.5

3.1

4.8

3.1

4.9

3.2

5.2

3.1

5.5

22.8

3.9

2.9

4.2

3.0

4.5

3.1

4.8

3.1

4.9

3.2

5.2

3.1

5.5

3.2

25.0

3.9

2.9

4.2

3.0

4.5

3.1

4.8

3.1

4.8

3.1

5.2

3.1

5.5

3.2

27.8

3.9

2.9

4.1

2.9

4.4

3.0

4.7

3.0

4.7

3.1

5.1

3.1

5.3

3.1

30.0

3.9

2.9

4.1

2.9

4.3

3.0

4.6

3.0

4.6

3.1

5.0

3.0

5.2

3.1
3.0

32.8

3.8

2.8

4.0

2.9

4.2

2.9

4.5

3.0

4.5

3.0

4.9

3.0

5.1

35.0

3.7

2.8

3.9

2.8

4.2

2.9

4.4

2.9

4.5

3.0

4.8

3.0

5.0

3.0

37.8

3.7

2.8

3.9

2.8

4.1

2.9

4.3

2.9

4.4

2.9

4.7

2.9

4.9

3.0

40.0

3.6

2.8

3.8

2.8

4.0

2.8

4.2

2.8

4.3

2.9

4.6

2.9

4.8

2.9

43.3

3.6

2.7

3.7

2.7

3.9

2.8

4.1

2.8

4.2

2.9

4.5

2.8

4.7

2.9

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-68

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PLFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.1

2.7

3.4

2.8

3.6

2.9

3.8

2.9

3.9

3.0

4.2

3.0

4.4

SHC
3.1

22.8

3.1

2.7

3.4

2.8

3.6

2.9

3.8

2.9

3.9

3.0

4.2

3.0

4.4

3.1

25.0

3.1

2.7

3.4

2.8

3.6

2.9

3.8

2.9

3.8

3.0

4.1

3.0

4.3

3.0

27.8

3.1

2.7

3.3

2.8

3.5

2.9

3.7

2.9

3.8

3.0

4.0

2.9

4.2

3.0

30.0

3.1

2.7

3.2

2.7

3.4

2.8

3.6

2.8

3.7

2.9

4.0

2.9

4.2

3.0

32.8

3.0

2.7

3.2

2.7

3.4

2.8

3.6

2.8

3.6

2.9

3.9

2.9

4.1

2.9

35.0

3.0

2.7

3.1

2.7

3.3

2.8

3.5

2.8

3.5

2.9

3.8

2.8

4.0

2.9

37.8

2.9

2.7

3.1

2.7

3.2

2.8

3.4

2.8

3.5

2.9

3.7

2.8

3.9

2.9

40.0

2.9

2.6

3.0

2.6

3.2

2.7

3.4

2.7

3.4

2.8

3.6

2.8

3.8

2.9

43.3

2.8

2.6

2.9

2.6

3.1

2.7

3.3

2.7

3.3

2.8

3.5

2.8

3.7

2.8

20.0

3.9

3.3

4.2

3.4

4.5

3.5

4.8

3.5

4.9

3.7

5.2

3.6

5.5

3.7

22.8

3.9

3.3

4.2

3.4

4.5

3.5

4.8

3.5

4.9

3.7

5.2

3.6

5.5

3.7

25.0

3.9

3.3

4.2

3.4

4.5

3.5

4.8

3.5

4.8

3.6

5.2

3.6

5.5

3.7

27.8

3.9

3.3

4.1

3.4

4.4

3.5

4.7

3.5

4.7

3.6

5.1

3.6

5.3

3.6

30.0

3.9

3.3

4.1

3.3

4.3

3.5

4.6

3.5

4.6

3.6

5.0

3.5

5.2

3.6

32.8

3.8

3.3

4.0

3.3

4.2

3.4

4.5

3.4

4.5

3.5

4.9

3.5

5.1

3.6

35.0

3.7

3.3

3.9

3.3

4.2

3.4

4.4

3.4

4.5

3.5

4.8

3.5

5.0

3.5

37.8

3.7

3.2

3.9

3.2

4.1

3.3

4.3

3.4

4.4

3.5

4.7

3.4

4.9

3.5

40.0

3.6

3.2

3.8

3.2

4.0

3.3

4.2

3.3

4.3

3.4

4.6

3.4

4.8

3.5

43.3

3.6

3.2

3.7

3.2

3.9

3.3

4.1

3.3

4.2

3.4

4.5

3.3

4.7

3.4

20.0

4.7

4.0

5.1

4.1

5.4

4.2

5.7

4.2

5.9

4.4

6.3

4.3

6.7

4.4

22.8

4.7

4.0

5.1

4.1

5.4

4.2

5.7

4.2

5.9

4.4

6.3

4.3

6.7

4.4

25.0

4.7

4.0

5.1

4.1

5.4

4.2

5.7

4.2

5.8

4.4

6.2

4.3

6.6

4.4

27.8

4.7

4.0

5.0

4.0

5.3

4.2

5.6

4.2

5.7

4.3

6.1

4.2

6.4

4.4

30.0

4.6

4.0

4.9

4.0

5.2

4.1

5.5

4.1

5.6

4.3

6.0

4.2

6.3

4.3

32.8

4.6

3.9

4.8

3.9

5.1

4.1

5.4

4.1

5.5

4.2

5.9

4.2

6.2

4.3

35.0

4.5

3.9

4.7

3.9

5.0

4.0

5.3

4.1

5.4

4.2

5.8

4.1

6.1

4.2

37.8

4.4

3.9

4.6

3.9

4.9

4.0

5.2

4.0

5.3

4.1

5.6

4.1

5.9

4.2

40.0

4.4

3.8

4.6

3.8

4.8

4.0

5.1

4.0

5.2

4.1

5.5

4.0

5.8

4.1

43.3

4.3

3.8

4.5

3.8

4.7

3.9

5.0

3.9

5.0

4.0

5.4

4.0

5.6

4.1

20.0

6.2

4.9

6.7

5.0

7.2

5.1

7.6

5.2

7.7

5.3

8.3

5.3

8.8

5.4

22.8

6.2

4.9

6.7

5.0

7.2

5.1

7.6

5.2

7.7

5.3

8.3

5.3

8.8

5.4

25.0

6.2

4.9

6.7

5.0

7.2

5.1

7.6

5.2

7.7

5.3

8.2

5.2

8.7

5.3

27.8

6.2

4.9

6.6

4.9

7.0

5.1

7.4

5.1

7.5

5.2

8.0

5.2

8.5

5.3

30.0

6.1

4.8

6.5

4.9

6.9

5.0

7.3

5.0

7.4

5.2

7.9

5.1

8.3

5.2

32.8

6.0

4.8

6.4

4.8

6.7

5.0

7.1

5.0

7.2

5.1

7.7

5.0

8.1

5.2

35.0

6.0

4.7

6.3

4.8

6.6

4.9

7.0

4.9

7.1

5.1

7.6

5.0

8.0

5.1

37.8

5.9

4.7

6.1

4.7

6.5

4.8

6.8

4.9

6.9

5.0

7.4

4.9

7.8

5.0

40.0

5.8

4.7

6.0

4.7

6.4

4.8

6.7

4.8

6.8

4.9

7.3

4.9

7.7

5.0

43.3

5.7

4.6

5.9

4.6

6.2

4.7

6.5

4.7

6.6

4.9

7.1

4.8

7.4

4.9

20.0

7.8

5.8

8.4

6.0

9.0

6.2

9.5

6.2

9.7

6.3

10.5

6.3

11.1

6.4

22.8

7.8

5.8

8.4

6.0

9.0

6.2

9.5

6.2

9.7

6.3

10.5

6.3

11.1

6.4

25.0

7.8

5.8

8.4

6.0

9.0

6.2

9.5

6.2

9.7

6.3

10.3

6.2

10.9

6.3

27.8

7.8

5.8

8.3

5.9

8.8

6.1

9.3

6.1

9.5

6.2

10.1

6.1

10.7

6.3

30.0

7.7

5.8

8.1

5.8

8.7

6.0

9.2

6.0

9.3

6.2

9.9

6.1

10.5

6.2

32.8

7.6

5.7

8.0

5.7

8.5

5.9

9.0

5.9

9.1

6.1

9.7

6.0

10.2

6.1

35.0

7.5

5.7

7.9

5.7

8.3

5.8

8.8

5.9

8.9

6.0

9.5

5.9

10.1

6.0

37.8

7.4

5.6

7.7

5.6

8.1

5.8

8.6

5.8

8.7

5.9

9.3

5.8

9.8

5.9

40.0

7.3

5.5

7.6

5.5

8.0

5.7

8.4

5.7

8.6

5.8

9.2

5.8

9.6

5.9

43.3

7.1

5.5

7.4

5.5

7.8

5.6

8.2

5.6

8.3

5.7

8.9

5.7

9.3

5.8

20.0

9.5

7.5

10.2

7.6

10.8

7.9

11.5

7.9

11.7

8.2

12.6

8.1

13.4

8.3

22.8

9.5

7.5

10.2

7.6

10.8

7.9

11.5

7.9

11.7

8.2

12.6

8.1

13.4

8.3

25.0

9.5

7.5

10.2

7.6

10.8

7.9

11.4

7.9

11.6

8.1

12.4

8.0

13.1

8.2

27.8

9.4

7.5

10.0

7.5

10.6

7.8

11.2

7.8

11.4

8.0

12.2

7.9

12.9

8.1

30.0

9.3

7.4

9.8

7.5

10.4

7.7

11.0

7.7

11.2

7.9

12.0

7.8

12.6

8.0

32.8

9.1

7.3

9.6

7.4

10.2

7.6

10.8

7.6

10.9

7.8

11.7

7.7

12.3

7.9

35.0

9.0

7.3

9.5

7.3

10.0

7.5

10.6

7.5

10.7

7.8

11.5

7.7

12.1

7.8

37.8

8.9

7.2

9.3

7.2

9.8

7.4

10.4

7.5

10.5

7.7

11.2

7.6

11.8

7.7

40.0

8.8

7.1

9.1

7.1

9.6

7.4

10.2

7.4

10.3

7.6

11.0

7.5

11.6

7.6

43.3

8.6

7.1

8.9

7.0

9.3

7.2

9.9

7.3

10.0

7.5

10.7

7.4

11.3

7.5

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-69

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PCFY-P-NGMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.4

22.8

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.4
3.3

SHC

25.0

3.9

3.0

4.2

3.1

4.5

3.2

4.8

3.2

4.8

3.3

5.2

3.3

5.5

27.8

3.9

3.0

4.1

3.1

4.4

3.2

4.7

3.2

4.7

3.3

5.1

3.2

5.3

3.3

30.0

3.9

3.0

4.1

3.0

4.3

3.1

4.6

3.1

4.6

3.2

5.0

3.2

5.2

3.2

32.8

3.8

3.0

4.0

3.0

4.2

3.1

4.5

3.1

4.5

3.2

4.9

3.1

5.1

3.2

35.0

3.7

3.0

3.9

3.0

4.2

3.1

4.4

3.1

4.5

3.1

4.8

3.1

5.0

3.2
3.1

37.8

3.7

2.9

3.9

2.9

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

40.0

3.6

2.9

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.0

4.8

3.1

43.3

3.6

2.9

3.7

2.9

3.9

2.9

4.1

2.9

4.2

3.0

4.5

3.0

4.7

3.0
5.2

20.0

6.2

4.7

6.7

4.8

7.2

5.0

7.6

5.0

7.7

5.1

8.3

5.1

8.8

22.8

6.2

4.7

6.7

4.8

7.2

5.0

7.6

5.0

7.7

5.1

8.3

5.1

8.8

5.2

25.0

6.2

4.7

6.7

4.8

7.2

5.0

7.6

5.0

7.7

5.1

8.2

5.0

8.7

5.1

27.8

6.2

4.7

6.6

4.8

7.0

4.9

7.4

4.9

7.5

5.0

8.0

5.0

8.5

5.1

30.0

6.1

4.7

6.5

4.7

6.9

4.9

7.3

4.9

7.4

5.0

7.9

4.9

8.3

5.0
4.9

32.8

6.0

4.6

6.4

4.6

6.7

4.8

7.1

4.8

7.2

4.9

7.7

4.9

8.1

35.0

6.0

4.6

6.3

4.6

6.6

4.7

7.0

4.7

7.1

4.9

7.6

4.8

8.0

4.9

37.8

5.9

4.5

6.1

4.5

6.5

4.7

6.8

4.7

6.9

4.8

7.4

4.7

7.8

4.8
4.8

40.0

5.8

4.5

6.0

4.5

6.4

4.6

6.7

4.6

6.8

4.7

7.3

4.7

7.7

43.3

5.7

4.4

5.9

4.4

6.2

4.5

6.5

4.5

6.6

4.7

7.1

4.6

7.4

4.7

20.0

7.8

5.8

8.4

5.9

9.0

6.1

9.5

6.1

9.7

6.3

10.5

6.2

11.1

6.3

22.8

7.8

5.8

8.4

5.9

9.0

6.1

9.5

6.1

9.7

6.3

10.5

6.2

11.1

6.3

25.0

7.8

5.8

8.4

5.9

9.0

6.1

9.5

6.1

9.7

6.2

10.3

6.2

10.9

6.3

27.8

7.8

5.7

8.3

5.8

8.8

6.0

9.3

6.0

9.5

6.2

10.1

6.1

10.7

6.2

30.0

7.7

5.7

8.1

5.8

8.7

5.9

9.2

5.9

9.3

6.1

9.9

6.0

10.5

6.1

32.8

7.6

5.6

8.0

5.7

8.5

5.8

9.0

5.9

9.1

6.0

9.7

5.9

10.2

6.0

35.0

7.5

5.6

7.9

5.6

8.3

5.8

8.8

5.8

8.9

5.9

9.5

5.8

10.1

5.9

37.8

7.4

5.5

7.7

5.5

8.1

5.7

8.6

5.7

8.7

5.8

9.3

5.8

9.8

5.9

40.0

7.3

5.5

7.6

5.5

8.0

5.6

8.4

5.6

8.6

5.8

9.2

5.7

9.6

5.8

43.3

7.1

5.4

7.4

5.4

7.8

5.5

8.2

5.5

8.3

5.7

8.9

5.6

9.3

5.7

20.0

9.5

7.2

10.2

7.3

10.8

7.5

11.5

7.6

11.7

7.8

12.6

7.7

13.4

7.9

22.8

9.5

7.2

10.2

7.3

10.8

7.5

11.5

7.6

11.7

7.8

12.6

7.7

13.4

7.9

25.0

9.5

7.2

10.2

7.3

10.8

7.5

11.4

7.6

11.6

7.8

12.4

7.7

13.1

7.8
7.7

27.8

9.4

7.1

10.0

7.2

10.6

7.4

11.2

7.5

11.4

7.6

12.2

7.5

12.9

30.0

9.3

7.1

9.8

7.1

10.4

7.4

11.0

7.4

11.2

7.6

12.0

7.5

12.6

7.6

32.8

9.1

7.0

9.6

7.0

10.2

7.3

10.8

7.3

10.9

7.5

11.7

7.4

12.3

7.5

35.0

9.0

6.9

9.5

7.0

10.0

7.2

10.6

7.2

10.7

7.4

11.5

7.3

12.1

7.4

37.8

8.9

6.9

9.3

6.9

9.8

7.1

10.4

7.1

10.5

7.3

11.2

7.2

11.8

7.3

40.0

8.8

6.8

9.1

6.8

9.6

7.0

10.2

7.0

10.3

7.2

11.0

7.1

11.6

7.2

43.3

8.6

6.7

8.9

6.7

9.3

6.9

9.9

6.9

10.0

7.1

10.7

7.0

11.3

7.1

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-70

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

SHC
1.4

22.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

1.4

25.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.2

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.1

1.3

2.2

1.4

30.0

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.0

1.3

2.1

1.4

32.8

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

40.0

1.5

1.2

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.3

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.8

1.2

1.9

1.3

20.0

2.1

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.7

2.7

1.7

2.9

1.7

22.8

2.1

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.7

2.7

1.7

2.9

1.7

25.0

2.1

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.7

2.7

1.7

2.9

1.7

27.8

2.0

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.7

2.6

1.7

2.8

1.7

30.0

2.0

1.6

2.1

1.6

2.3

1.6

2.4

1.6

2.4

1.7

2.6

1.7

2.7

1.7

32.8

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.6

2.7

1.7

35.0

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.3

1.6

2.5

1.6

2.6

1.7

37.8

1.9

1.5

2.0

1.5

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.6

1.6

40.0

1.9

1.5

2.0

1.5

2.1

1.6

2.2

1.6

2.2

1.6

2.4

1.6

2.5

1.6

43.3

1.9

1.5

1.9

1.5

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

20.0

3.1

2.6

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.8

4.2

2.8

4.4

2.8

22.8

3.1

2.6

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.8

4.2

2.8

4.4

2.8

25.0

3.1

2.6

3.4

2.6

3.6

2.7

3.8

2.7

3.8

2.8

4.1

2.7

4.3

2.8

27.8

3.1

2.5

3.3

2.6

3.5

2.7

3.7

2.7

3.8

2.7

4.0

2.7

4.2

2.8

30.0

3.1

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.7

2.7

4.0

2.7

4.2

2.8

32.8

3.0

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.6

2.7

3.9

2.7

4.1

2.7

35.0

3.0

2.5

3.1

2.5

3.3

2.6

3.5

2.6

3.5

2.7

3.8

2.6

4.0

2.7

37.8

2.9

2.5

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.6

3.7

2.6

3.9

2.7

40.0

2.9

2.4

3.0

2.4

3.2

2.5

3.4

2.5

3.4

2.6

3.6

2.6

3.8

2.6

43.3

2.8

2.4

2.9

2.4

3.1

2.5

3.3

2.5

3.3

2.6

3.5

2.5

3.7

2.6

20.0

3.9

3.1

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.4

22.8

3.9

3.1

4.2

3.1

4.5

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.4

25.0

3.9

3.1

4.2

3.1

4.5

3.2

4.8

3.2

4.8

3.3

5.2

3.3

5.5

3.4

27.8

3.9

3.1

4.1

3.1

4.4

3.2

4.7

3.2

4.7

3.3

5.1

3.2

5.3

3.3

30.0

3.9

3.0

4.1

3.1

4.3

3.2

4.6

3.2

4.6

3.3

5.0

3.2

5.2

3.3

32.8

3.8

3.0

4.0

3.0

4.2

3.1

4.5

3.1

4.5

3.2

4.9

3.2

5.1

3.2

35.0

3.7

3.0

3.9

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.8

3.1

5.0

3.2

37.8

3.7

3.0

3.9

3.0

4.1

3.0

4.3

3.1

4.4

3.1

4.7

3.1

4.9

3.2

40.0

3.6

2.9

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.1

4.8

3.1

43.3

3.6

2.9

3.7

2.9

3.9

3.0

4.1

3.0

4.2

3.1

4.5

3.0

4.7

3.1

20.0

4.7

3.9

5.1

4.0

5.4

4.1

5.7

4.1

5.9

4.3

6.3

4.2

6.7

4.3

22.8

4.7

3.9

5.1

4.0

5.4

4.1

5.7

4.1

5.9

4.3

6.3

4.2

6.7

4.3

25.0

4.7

3.9

5.1

4.0

5.4

4.1

5.7

4.1

5.8

4.2

6.2

4.2

6.6

4.3

27.8

4.7

3.9

5.0

3.9

5.3

4.1

5.6

4.1

5.7

4.2

6.1

4.1

6.4

4.2

30.0

4.6

3.9

4.9

3.9

5.2

4.0

5.5

4.0

5.6

4.2

6.0

4.1

6.3

4.2

32.8

4.6

3.8

4.8

3.9

5.1

4.0

5.4

4.0

5.5

4.1

5.9

4.1

6.2

4.2

35.0

4.5

3.8

4.7

3.8

5.0

3.9

5.3

4.0

5.4

4.1

5.8

4.0

6.1

4.1

37.8

4.4

3.8

4.6

3.8

4.9

3.9

5.2

3.9

5.3

4.0

5.6

4.0

5.9

4.1
4.0

40.0

4.4

3.7

4.6

3.7

4.8

3.9

5.1

3.9

5.2

4.0

5.5

3.9

5.8

43.3

4.3

3.7

4.5

3.7

4.7

3.8

5.0

3.8

5.0

3.9

5.4

3.9

5.6

4.0

20.0

6.2

4.8

6.7

4.9

7.2

5.1

7.6

5.1

7.7

5.3

8.3

5.2

8.8

5.3

22.8

6.2

4.8

6.7

4.9

7.2

5.1

7.6

5.1

7.7

5.3

8.3

5.2

8.8

5.3

25.0

6.2

4.8

6.7

4.9

7.2

5.1

7.6

5.1

7.7

5.2

8.2

5.2

8.7

5.3

27.8

6.2

4.8

6.6

4.9

7.0

5.0

7.4

5.0

7.5

5.2

8.0

5.1

8.5

5.2

30.0

6.1

4.8

6.5

4.8

6.9

5.0

7.3

5.0

7.4

5.1

7.9

5.0

8.3

5.2

32.8

6.0

4.7

6.4

4.8

6.7

4.9

7.1

4.9

7.2

5.0

7.7

5.0

8.1

5.1

35.0

6.0

4.7

6.3

4.7

6.6

4.9

7.0

4.9

7.1

5.0

7.6

4.9

8.0

5.0

37.8

5.9

4.6

6.1

4.7

6.5

4.8

6.8

4.8

6.9

4.9

7.4

4.9

7.8

5.0

40.0

5.8

4.6

6.0

4.6

6.4

4.7

6.7

4.7

6.8

4.9

7.3

4.8

7.7

4.9

43.3

5.7

4.6

5.9

4.5

6.2

4.7

6.5

4.7

6.6

4.8

7.1

4.7

7.4

4.8

20.0

7.8

6.5

8.4

6.6

9.0

6.9

9.5

6.9

9.7

7.1

10.5

7.1

11.1

7.2

22.8

7.8

6.5

8.4

6.6

9.0

6.9

9.5

6.9

9.7

7.1

10.5

7.1

11.1

7.2

25.0

7.8

6.5

8.4

6.6

9.0

6.9

9.5

6.9

9.7

7.1

10.3

7.0

10.9

7.2

27.8

7.8

6.5

8.3

6.6

8.8

6.8

9.3

6.8

9.5

7.0

10.1

6.9

10.7

7.1

30.0

7.7

6.5

8.1

6.5

8.7

6.7

9.2

6.7

9.3

6.9

9.9

6.9

10.5

7.0

32.8

7.6

6.4

8.0

6.4

8.5

6.6

9.0

6.7

9.1

6.9

9.7

6.8

10.2

6.9

35.0

7.5

6.3

7.9

6.4

8.3

6.6

8.8

6.6

8.9

6.8

9.5

6.7

10.1

6.9

37.8

7.4

6.3

7.7

6.3

8.1

6.5

8.6

6.5

8.7

6.7

9.3

6.6

9.8

6.8

40.0

7.3

6.2

7.6

6.2

8.0

6.4

8.4

6.5

8.6

6.7

9.2

6.6

9.6

6.7

43.3

7.1

6.2

7.4

6.2

7.8

6.3

8.2

6.4

8.3

6.6

8.9

6.5

9.3

6.6

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-71

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-1-1. Cooling CapacityPUHY,PURY-P72~96THMU/YHMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.3

SHC
1.4

22.8

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.3

1.4

25.0

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.2

1.4

27.8

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.3

1.9

1.3

2.1

1.3

2.2

1.3

30.0

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.3

1.9

1.3

2.0

1.3

2.1

1.3

32.8

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.5

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.8

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.8

1.3

1.9

1.2

2.0

1.3

40.0

1.5

1.2

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.2

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.8

1.2

1.9

1.2

20.0

2.1

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.8

2.7

1.7

2.9

1.8

22.8

2.1

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.8

2.7

1.7

2.9

1.8

25.0

2.1

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.8

2.7

1.7

2.9

1.8

27.8

2.0

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.6

1.7

2.8

1.7

30.0

2.0

1.6

2.1

1.6

2.3

1.7

2.4

1.7

2.4

1.7

2.6

1.7

2.7

1.7

32.8

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.7

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.3

1.7

2.5

1.7

2.6

1.7

37.8

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.6

2.6

1.7

40.0

1.9

1.5

2.0

1.5

2.1

1.6

2.2

1.6

2.2

1.6

2.4

1.6

2.5

1.6

43.3

1.9

1.5

1.9

1.5

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

20.0

3.1

2.2

3.4

2.3

3.6

2.3

3.8

2.3

3.9

2.4

4.2

2.4

4.4

2.4

22.8

3.1

2.2

3.4

2.3

3.6

2.3

3.8

2.3

3.9

2.4

4.2

2.4

4.4

2.4

25.0

3.1

2.2

3.4

2.3

3.6

2.3

3.8

2.3

3.8

2.4

4.1

2.4

4.3

2.4

27.8

3.1

2.2

3.3

2.2

3.5

2.3

3.7

2.3

3.8

2.4

4.0

2.3

4.2

2.4

30.0

3.1

2.2

3.2

2.2

3.4

2.3

3.6

2.3

3.7

2.3

4.0

2.3

4.2

2.3

32.8

3.0

2.2

3.2

2.2

3.4

2.2

3.6

2.2

3.6

2.3

3.9

2.3

4.1

2.3

35.0

3.0

2.1

3.1

2.1

3.3

2.2

3.5

2.2

3.5

2.3

3.8

2.2

4.0

2.3

37.8

2.9

2.1

3.1

2.1

3.2

2.2

3.4

2.2

3.5

2.2

3.7

2.2

3.9

2.2

40.0

2.9

2.1

3.0

2.1

3.2

2.1

3.4

2.1

3.4

2.2

3.6

2.2

3.8

2.2

43.3

2.8

2.1

2.9

2.1

3.1

2.1

3.3

2.1

3.3

2.1

3.5

2.1

3.7

2.2

20.0

3.9

2.8

4.2

2.9

4.5

3.0

4.8

3.0

4.9

3.1

5.2

3.0

5.5

3.1

22.8

3.9

2.8

4.2

2.9

4.5

3.0

4.8

3.0

4.9

3.1

5.2

3.0

5.5

3.1

25.0

3.9

2.8

4.2

2.9

4.5

3.0

4.8

3.0

4.8

3.0

5.2

3.0

5.5

3.1

27.8

3.9

2.8

4.1

2.8

4.4

2.9

4.7

2.9

4.7

3.0

5.1

3.0

5.3

3.0

30.0

3.9

2.8

4.1

2.8

4.3

2.9

4.6

2.9

4.6

3.0

5.0

2.9

5.2

3.0

32.8

3.8

2.8

4.0

2.8

4.2

2.8

4.5

2.9

4.5

2.9

4.9

2.9

5.1

2.9

35.0

3.7

2.7

3.9

2.7

4.2

2.8

4.4

2.8

4.5

2.9

4.8

2.8

5.0

2.9

37.8

3.7

2.7

3.9

2.7

4.1

2.8

4.3

2.8

4.4

2.8

4.7

2.8

4.9

2.8

40.0

3.6

2.7

3.8

2.7

4.0

2.7

4.2

2.7

4.3

2.8

4.6

2.8

4.8

2.8

43.3

3.6

2.6

3.7

2.6

3.9

2.7

4.1

2.7

4.2

2.8

4.5

2.7

4.7

2.8

20.0

4.7

3.5

5.1

3.5

5.4

3.7

5.7

3.7

5.9

3.8

6.3

3.7

6.7

3.8

22.8

4.7

3.5

5.1

3.5

5.4

3.7

5.7

3.7

5.9

3.8

6.3

3.7

6.7

3.8

25.0

4.7

3.5

5.1

3.5

5.4

3.7

5.7

3.7

5.8

3.8

6.2

3.7

6.6

3.8

27.8

4.7

3.5

5.0

3.5

5.3

3.6

5.6

3.6

5.7

3.7

6.1

3.6

6.4

3.7

30.0

4.6

3.4

4.9

3.5

5.2

3.6

5.5

3.6

5.6

3.7

6.0

3.6

6.3

3.7

32.8

4.6

3.4

4.8

3.4

5.1

3.5

5.4

3.5

5.5

3.6

5.9

3.6

6.2

3.6

35.0

4.5

3.4

4.7

3.4

5.0

3.5

5.3

3.5

5.4

3.6

5.8

3.5

6.1

3.6

37.8

4.4

3.3

4.6

3.3

4.9

3.4

5.2

3.4

5.3

3.5

5.6

3.5

5.9

3.5
3.5

40.0

4.4

3.3

4.6

3.3

4.8

3.4

5.1

3.4

5.2

3.5

5.5

3.4

5.8

43.3

4.3

3.2

4.5

3.2

4.7

3.3

5.0

3.3

5.0

3.4

5.4

3.4

5.6

3.4

20.0

6.2

4.4

6.7

4.5

7.2

4.7

7.6

4.7

7.7

4.8

8.3

4.8

8.8

4.9

22.8

6.2

4.4

6.7

4.5

7.2

4.7

7.6

4.7

7.7

4.8

8.3

4.8

8.8

4.9

25.0

6.2

4.4

6.7

4.5

7.2

4.7

7.6

4.7

7.7

4.8

8.2

4.7

8.7

4.8

27.8

6.2

4.4

6.6

4.5

7.0

4.6

7.4

4.6

7.5

4.7

8.0

4.7

8.5

4.7

30.0

6.1

4.4

6.5

4.4

6.9

4.6

7.3

4.6

7.4

4.7

7.9

4.6

8.3

4.7

32.8

6.0

4.3

6.4

4.4

6.7

4.5

7.1

4.5

7.2

4.6

7.7

4.5

8.1

4.6

35.0

6.0

4.3

6.3

4.3

6.6

4.4

7.0

4.4

7.1

4.5

7.6

4.5

8.0

4.5

37.8

5.9

4.2

6.1

4.2

6.5

4.4

6.8

4.4

6.9

4.5

7.4

4.4

7.8

4.5

40.0

5.8

4.2

6.0

4.2

6.4

4.3

6.7

4.3

6.8

4.4

7.3

4.3

7.7

4.4

43.3

5.7

4.1

5.9

4.1

6.2

4.2

6.5

4.2

6.6

4.3

7.1

4.3

7.4

4.3

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-72

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSIus

DATA U4

2-1-2. Heating CapacityPUHY,PURY-P72~96THMU/YHMU with All Indoor Units


Model
size

06

08

12

15

18

24

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
1.3
1.2
1.2
1.2
1.5
1.4
1.4
1.4
1.7
1.7
1.6
1.5
2.0
1.9
1.7
1.5
2.1
2.0
1.7
1.5
2.2
2.0
1.7
1.5
2.3
2.0
1.7
1.5
2.4
2.0
1.7
1.5
2.5
2.0
1.7
1.5
2.7
2.0
1.7
1.5
2.8
2.0
1.7
1.5
1.6
1.6
1.6
1.6
1.9
1.9
1.8
1.8
2.2
2.2
2.1
1.9
2.6
2.4
2.2
1.9
2.7
2.6
2.2
1.9
2.8
2.6
2.2
1.9
2.9
2.6
2.2
1.9
3.1
2.6
2.2
1.9
3.3
2.6
2.2
1.9
3.5
2.6
2.2
1.9
3.7
2.6
2.2
1.9
2.5
2.4
2.4
2.4
3.0
2.9
2.8
2.8
3.5
3.3
3.3
2.9
3.9
3.7
3.3
2.9
4.2
4.0
3.3
2.9
4.3
4.0
3.3
2.9
4.5
4.0
3.3
2.9
4.7
4.0
3.3
2.9
5.1
4.0
3.3
2.9
5.4
4.0
3.3
2.9
5.6
4.0
3.3
2.9
3.1
3.1
3.0
3.0
3.7
3.6
3.6
3.5
4.3
4.1
4.1
3.6
4.9
4.7
4.2
3.6
5.3
5.0
4.2
3.6
5.4
5.0
4.2
3.6
5.7
5.0
4.2
3.6
5.9
5.0
4.2
3.6
6.3
5.0
4.2
3.6
6.8
5.0
4.2
3.6
7.0
5.0
4.2
3.6
3.7
3.6
3.6
3.6
4.4
4.2
4.2
4.2
5.1
4.9
4.8
4.3
5.8
5.5
4.9
4.3
6.2
5.9
4.9
4.3
6.4
5.9
4.9
4.3
6.7
5.9
4.9
4.3
7.0
5.9
4.9
4.3
7.5
5.9
4.9
4.3
8.0
5.9
4.9
4.3
8.3
5.9
4.9
4.3
5.0
4.8
4.8
4.8
5.9
5.7
5.6
5.6
5.8
6.8
6.5
6.4
7.7
7.4
6.6
5.8
8.3
7.9
6.6
5.8
8.5
7.9
6.6
5.8
9.0
7.9
6.6
5.8
9.4
7.9
6.6
5.8
10.0
7.9
6.6
5.8
10.7
7.9
6.6
5.8
11.1
7.9
6.6
5.8
5.5
5.4
5.4
5.3
6.6
6.3
6.3
6.2
7.6
7.3
7.2
6.4
8.6
8.2
7.3
6.4
9.3
8.8
7.3
6.4
9.5
8.8
7.3
6.4
10.0
8.8
7.3
6.4
10.4
8.8
7.3
6.4
11.2
8.8
7.3
6.4
11.9
8.8
7.3
6.4
12.4
8.8
7.3
6.4
kcal/h = kW x 860, BTU/h = kW x 3,412

Model
size

30

36

48

54

72

96

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
6.3
6.1
6.1
6.0
7.5
7.2
7.1
7.1
8.6
8.3
8.1
7.3
9.8
9.4
8.3
7.3
10.5
10.0
8.3
7.3
10.8
10.0
8.3
7.3
11.3
10.0
8.3
7.3
11.9
10.0
8.3
7.3
12.7
10.0
8.3
7.3
13.5
10.0
8.3
7.3
14.0
10.0
8.3
7.3
7.3
7.1
7.1
7.0
8.7
8.4
8.3
8.3
10.1
9.7
9.5
8.5
11.5
11.0
9.7
8.5
12.3
11.7
9.7
8.5
12.6
11.7
9.7
8.5
13.3
11.7
9.7
8.5
13.9
11.7
9.7
8.5
14.8
11.7
9.7
8.5
15.8
11.7
9.7
8.5
16.4
11.7
9.7
8.5
9.9
9.6
9.6
9.5
11.8
11.4
11.2
11.2
13.7
13.1
12.8
11.5
15.5
14.8
13.2
11.5
16.6
15.8
13.2
11.5
17.0
15.8
13.2
11.5
17.9
15.8
13.2
11.5
18.8
15.8
13.2
11.5
20.1
15.8
13.2
11.5
21.3
15.8
13.2
11.5
22.2
15.8
13.2
11.5
11.1
10.7
10.7
10.6
13.1
12.7
12.5
12.5
15.2
14.6
14.3
12.8
17.3
16.5
14.7
12.8
18.5
17.6
14.7
12.8
19.0
17.6
14.7
12.8
19.9
17.6
14.7
12.8
20.9
17.6
14.7
12.8
22.3
17.6
14.7
12.8
23.8
17.6
14.7
12.8
24.7
17.6
14.7
12.8
14.7
14.3
14.3
14.1
17.5
16.8
16.6
16.6
20.2
19.4
19.0
17.1
23.0
21.9
19.5
17.1
24.6
23.4
19.5
17.1
25.2
23.4
19.5
17.1
26.5
23.4
19.5
17.1
27.8
23.4
19.5
17.1
29.7
23.4
19.5
17.1
31.6
23.4
19.5
17.1
32.9
23.4
19.5
17.1
19.9
19.3
19.3
19.1
23.6
22.8
22.5
22.4
27.4
26.2
25.8
23.1
31.1
29.7
26.4
23.1
33.3
31.7
26.4
23.1
34.2
31.7
26.4
23.1
35.9
31.7
26.4
23.1
37.6
31.7
26.4
23.1
40.2
31.7
26.4
23.1
42.8
31.7
26.4
23.1
44.5
31.7
26.4
23.1
kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NOMINAL
CAPACITY
TABLES

27

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

NCT-73

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2. Cooing and Heating Capacity with PUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU-A


2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PEFY-P-NMSU-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.0

1.7

2.2

1.6

2.3

SHC
1.7

22.8

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.0

1.6

2.1

1.6

2.2

1.7

25.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.7

27.8

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

1.9

1.6

2.1

1.6

2.2

1.6

30.0

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

32.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

35.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

1.9

1.6

2.0

1.6

37.8

1.5

1.5

1.6

1.4

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

40.0

1.5

1.5

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.9

1.5

2.0

1.6

43.3

1.5

1.4

1.5

1.4

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

20.0

2.3

2.0

2.4

2.0

2.5

2.1

2.6

2.1

2.7

2.1

2.9

2.1

3.0

2.2

22.8

2.3

2.0

2.3

2.0

2.5

2.0

2.6

2.0

2.6

2.1

2.8

2.1

3.0

2.1

25.0

2.2

2.0

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

27.8

2.2

2.0

2.3

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.0

2.9

2.1

30.0

2.2

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.8

2.1

32.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.4

2.0

2.6

2.0

2.7

2.1

35.0

2.1

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.0

37.8

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.3

2.0

2.5

2.0

2.6

2.0

40.0

2.0

1.9

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.5

2.0

2.6

2.0

43.3

2.0

1.9

2.0

1.8

2.1

1.9

2.2

1.9

2.2

2.0

2.4

1.9

2.5

2.0

20.0

3.4

2.7

3.5

2.6

3.8

2.7

4.0

2.7

4.1

2.8

4.3

2.8

4.6

2.8

22.8

3.4

2.6

3.5

2.6

3.7

2.7

3.9

2.7

4.0

2.8

4.3

2.8

4.5

2.8

25.0

3.4

2.6

3.5

2.6

3.7

2.7

3.8

2.7

3.9

2.8

4.2

2.7

4.4

2.8

27.8

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.6

3.8

2.7

4.1

2.7

4.3

2.7

30.0

3.2

2.6

3.3

2.5

3.5

2.6

3.7

2.6

3.8

2.7

4.0

2.7

4.2

2.7

32.8

3.2

2.5

3.3

2.5

3.4

2.6

3.6

2.6

3.7

2.7

3.9

2.6

4.1

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.5

3.6

2.6

3.9

2.6

4.0

2.7

37.8

3.1

2.5

3.1

2.5

3.3

2.5

3.4

2.5

3.5

2.6

3.8

2.6

4.0

2.6

40.0

3.0

2.5

3.1

2.4

3.2

2.5

3.4

2.5

3.5

2.6

3.7

2.5

3.9

2.6

43.3

3.0

2.4

3.0

2.4

3.1

2.5

3.3

2.5

3.4

2.5

3.6

2.5

3.8

2.6

20.0

4.3

3.2

4.4

3.2

4.7

3.3

5.0

3.3

5.1

3.4

5.4

3.3

5.7

3.4

22.8

4.3

3.2

4.4

3.2

4.7

3.3

4.8

3.2

5.0

3.3

5.3

3.3

5.6

3.3

25.0

4.2

3.1

4.3

3.1

4.6

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.3

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.7

3.1

4.8

3.3

5.1

3.2

5.4

3.3

30.0

4.1

3.1

4.2

3.1

4.4

3.1

4.6

3.1

4.7

3.2

5.0

3.2

5.3

3.2

32.8

4.0

3.0

4.1

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.1

5.2

3.2

35.0

3.9

3.0

4.0

3.0

4.2

3.1

4.4

3.0

4.5

3.1

4.8

3.1

5.1

3.2

37.8

3.8

3.0

3.9

2.9

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.1

40.0

3.8

2.9

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.0

4.8

3.1

43.3

3.7

2.9

3.7

2.8

3.9

2.9

4.1

2.9

4.2

3.0

4.5

3.0

4.7

3.0

20.0

5.1

3.9

5.3

3.9

5.7

4.1

5.9

4.0

6.1

4.2

6.5

4.1

6.8

4.2

22.8

5.1

3.9

5.3

3.9

5.6

4.0

5.8

4.0

6.0

4.1

6.4

4.1

6.7

4.1

25.0

5.0

3.9

5.2

3.9

5.5

4.0

5.7

3.9

5.9

4.1

6.3

4.0

6.6

4.1

27.8

4.9

3.8

5.1

3.8

5.4

3.9

5.6

3.9

5.7

4.0

6.1

4.0

6.4

4.0

30.0

4.9

3.8

5.0

3.8

5.3

3.9

5.5

3.9

5.6

4.0

6.0

3.9

6.3

4.0

32.8

4.8

3.8

4.9

3.7

5.2

3.8

5.4

3.8

5.5

3.9

5.9

3.9

6.2

4.0

35.0

4.7

3.7

4.8

3.7

5.1

3.8

5.3

3.8

5.4

3.9

5.8

3.8

6.1

3.9

37.8

4.6

3.7

4.7

3.6

4.9

3.7

5.2

3.7

5.3

3.8

5.6

3.8

5.9

3.9
3.8

40.0

4.5

3.6

4.6

3.6

4.8

3.7

5.1

3.7

5.2

3.8

5.5

3.8

5.8

43.3

4.4

3.6

4.5

3.5

4.7

3.6

4.9

3.6

5.0

3.7

5.4

3.7

5.6

3.8

20.0

6.8

5.2

7.1

5.2

7.5

5.3

7.9

5.3

8.1

5.5

8.7

5.4

9.1

5.5

22.8

6.8

5.2

7.0

5.1

7.4

5.3

7.7

5.3

7.9

5.4

8.5

5.4

8.9

5.5

25.0

6.7

5.1

6.9

5.1

7.3

5.2

7.6

5.2

7.8

5.4

8.3

5.3

8.8

5.4

27.8

6.6

5.1

6.8

5.0

7.1

5.2

7.4

5.1

7.6

5.3

8.2

5.2

8.6

5.3

30.0

6.5

5.0

6.6

5.0

7.0

5.1

7.3

5.1

7.5

5.3

8.0

5.2

8.4

5.3

32.8

6.4

5.0

6.5

4.9

6.9

5.0

7.2

5.0

7.3

5.2

7.8

5.1

8.2

5.2

35.0

6.3

4.9

6.4

4.8

6.7

5.0

7.0

5.0

7.2

5.1

7.7

5.1

8.1

5.2

37.8

6.1

4.9

6.2

4.8

6.6

4.9

6.9

4.9

7.0

5.1

7.5

5.0

7.9

5.1

40.0

6.0

4.8

6.1

4.7

6.4

4.9

6.7

4.8

6.9

5.0

7.4

4.9

7.7

5.0

43.3

5.9

4.7

5.9

4.6

6.3

4.8

6.5

4.8

6.7

4.9

7.2

4.9

7.5

5.0

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-74

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

4.3

2.9

4.4

2.9

4.7

3.0

5.0

3.0

5.1

3.1

5.4

3.0

5.7

SHC
3.1

22.8

4.3

2.9

4.4

2.9

4.7

3.0

4.8

2.9

5.0

3.0

5.3

3.0

5.6

3.0

25.0

4.2

2.9

4.3

2.9

4.6

2.9

4.8

2.9

4.9

3.0

5.2

2.9

5.5

3.0

27.8

4.1

2.8

4.2

2.8

4.5

2.9

4.7

2.8

4.8

2.9

5.1

2.9

5.4

2.9

30.0

4.1

2.8

4.2

2.8

4.4

2.8

4.6

2.8

4.7

2.9

5.0

2.8

5.3

2.9

32.8

4.0

2.8

4.1

2.7

4.3

2.8

4.5

2.8

4.6

2.8

4.9

2.8

5.2

2.8

35.0

3.9

2.7

4.0

2.7

4.2

2.7

4.4

2.7

4.5

2.8

4.8

2.8

5.1

2.8

37.8

3.8

2.7

3.9

2.6

4.1

2.7

4.3

2.7

4.4

2.7

4.7

2.7

4.9

2.7

40.0

3.8

2.6

3.8

2.6

4.0

2.7

4.2

2.6

4.3

2.7

4.6

2.7

4.8

2.7

43.3

3.7

2.6

3.7

2.5

3.9

2.6

4.1

2.6

4.2

2.7

4.5

2.6

4.7

2.6

20.0

5.1

3.6

5.3

3.6

5.7

3.7

6.0

3.6

6.1

3.7

6.5

3.7

6.9

3.7

22.8

5.1

3.5

5.3

3.5

5.6

3.6

5.8

3.6

6.0

3.7

6.4

3.6

6.7

3.7

25.0

5.1

3.5

5.2

3.5

5.5

3.6

5.7

3.5

5.9

3.6

6.3

3.6

6.6

3.6

27.8

5.0

3.5

5.1

3.4

5.4

3.5

5.6

3.5

5.8

3.6

6.2

3.5

6.5

3.6

30.0

4.9

3.4

5.0

3.4

5.3

3.5

5.5

3.4

5.7

3.5

6.1

3.5

6.4

3.5

32.8

4.8

3.4

4.9

3.3

5.2

3.4

5.4

3.4

5.5

3.5

5.9

3.4

6.2

3.5

35.0

4.7

3.3

4.8

3.3

5.1

3.4

5.3

3.3

5.4

3.4

5.8

3.4

6.1

3.4

37.8

4.6

3.3

4.7

3.2

5.0

3.3

5.2

3.3

5.3

3.4

5.7

3.3

6.0

3.4

40.0

4.6

3.2

4.6

3.2

4.9

3.2

5.1

3.2

5.2

3.3

5.6

3.3

5.8

3.3

43.3

4.5

3.2

4.5

3.1

4.7

3.2

4.9

3.2

5.1

3.3

5.4

3.2

5.7

3.3

20.0

6.8

4.7

7.0

4.7

7.5

4.8

7.9

4.8

8.1

4.9

8.6

4.9

9.1

4.9

22.8

6.8

4.7

7.0

4.7

7.4

4.8

7.7

4.7

7.9

4.8

8.5

4.8

8.9

4.8

25.0

6.7

4.6

6.9

4.6

7.3

4.7

7.6

4.7

7.8

4.8

8.3

4.7

8.7

4.8

27.8

6.6

4.5

6.7

4.5

7.1

4.6

7.4

4.6

7.6

4.7

8.1

4.6

8.5

4.7

30.0

6.5

4.5

6.6

4.4

7.0

4.5

7.3

4.5

7.5

4.6

8.0

4.6

8.4

4.6

32.8

6.3

4.4

6.5

4.4

6.8

4.5

7.1

4.4

7.3

4.6

7.8

4.5

8.2

4.5

35.0

6.2

4.4

6.4

4.3

6.7

4.4

7.0

4.4

7.2

4.5

7.7

4.4

8.1

4.5

37.8

6.1

4.3

6.2

4.2

6.6

4.3

6.8

4.3

7.0

4.4

7.5

4.4

7.9

4.4

40.0

6.0

4.3

6.1

4.2

6.4

4.3

6.7

4.2

6.9

4.4

7.4

4.3

7.7

4.3

43.3

5.9

4.2

5.9

4.1

6.2

4.2

6.5

4.1

6.7

4.3

7.1

4.2

7.5

4.3

20.0

7.7

5.3

7.9

5.3

8.5

5.5

8.9

5.5

9.1

5.6

9.8

5.6

10.2

5.6

22.8

7.6

5.3

7.9

5.3

8.4

5.4

8.7

5.4

8.9

5.5

9.6

5.5

10.0

5.5

25.0

7.5

5.3

7.8

5.2

8.2

5.4

8.6

5.3

8.8

5.5

9.4

5.4

9.9

5.5

27.8

7.4

5.2

7.6

5.2

8.0

5.3

8.4

5.2

8.6

5.4

9.2

5.3

9.6

5.4

30.0

7.3

5.1

7.5

5.1

7.9

5.2

8.2

5.2

8.4

5.3

9.0

5.2

9.5

5.3

32.8

7.1

5.1

7.3

5.0

7.7

5.1

8.1

5.1

8.3

5.2

8.8

5.2

9.3

5.2

35.0

7.0

5.0

7.2

4.9

7.6

5.0

7.9

5.0

8.1

5.2

8.7

5.1

9.1

5.2

37.8

6.9

4.9

7.0

4.8

7.4

5.0

7.7

4.9

7.9

5.1

8.5

5.0

8.9

5.1

40.0

6.8

4.9

6.9

4.8

7.3

4.9

7.6

4.9

7.8

5.0

8.3

4.9

8.7

5.0

43.3

6.6

4.8

6.7

4.7

7.0

4.8

7.4

4.8

7.5

4.9

8.1

4.8

8.5

4.9

20.0

8.5

5.9

8.8

5.9

9.5

6.1

9.9

6.1

10.2

6.3

10.9

6.2

11.4

6.2

22.8

8.5

5.9

8.8

5.9

9.3

6.0

9.7

6.0

10.0

6.2

10.6

6.1

11.2

6.1

25.0

8.4

5.9

8.7

5.8

9.1

6.0

9.5

5.9

9.8

6.1

10.5

6.0

11.0

6.1

27.8

8.2

5.8

8.5

5.7

8.9

5.9

9.3

5.8

9.6

6.0

10.2

5.9

10.7

6.0

30.0

8.1

5.7

8.3

5.7

8.8

5.8

9.2

5.7

9.4

5.9

10.0

5.8

10.6

5.9

32.8

8.0

5.6

8.1

5.6

8.6

5.7

9.0

5.6

9.2

5.8

9.8

5.7

10.3

5.8

35.0

7.8

5.6

8.0

5.5

8.4

5.6

8.8

5.6

9.0

5.7

9.6

5.7

10.1

5.7

37.8

7.7

5.5

7.8

5.4

8.2

5.5

8.6

5.5

8.8

5.6

9.4

5.6

9.9

5.6
5.6

40.0

7.6

5.4

7.7

5.3

8.1

5.4

8.4

5.4

8.7

5.6

9.2

5.5

9.7

43.3

7.4

5.3

7.4

5.2

7.8

5.3

8.2

5.3

8.4

5.5

9.0

5.4

9.4

5.5

20.0

10.3

7.3

10.7

7.3

11.4

7.5

11.9

7.5

12.2

7.7

13.1

7.6

13.7

7.7

22.8

10.3

7.3

10.6

7.3

11.2

7.4

11.7

7.4

12.0

7.6

12.8

7.5

13.4

7.6

25.0

10.1

7.2

10.4

7.2

11.0

7.4

11.5

7.3

11.8

7.5

12.6

7.4

13.2

7.5

27.8

9.9

7.1

10.2

7.1

10.8

7.2

11.2

7.2

11.5

7.4

12.3

7.3

12.9

7.4

30.0

9.8

7.0

10.0

7.0

10.6

7.1

11.0

7.1

11.3

7.3

12.1

7.2

12.7

7.3

32.8

9.6

7.0

9.8

6.9

10.3

7.0

10.8

7.0

11.1

7.2

11.8

7.1

12.4

7.2

35.0

9.4

6.9

9.6

6.8

10.2

6.9

10.6

6.9

10.9

7.1

11.6

7.0

12.2

7.1

37.8

9.3

6.8

9.4

6.7

9.9

6.8

10.4

6.8

10.6

7.0

11.3

6.9

11.9

7.0

40.0

9.1

6.7

9.2

6.6

9.7

6.7

10.2

6.7

10.4

6.9

11.1

6.8

11.7

6.9

43.3

8.9

6.6

9.0

6.5

9.5

6.6

9.9

6.6

10.1

6.8

10.8

6.7

11.3

6.8

20.0

13.7

9.4

14.2

9.4

15.1

9.7

15.9

9.6

16.3

9.9

17.4

9.8

18.3

9.8

22.8

13.6

9.4

14.1

9.3

14.9

9.5

15.5

9.5

15.9

9.7

17.0

9.6

17.9

9.7

25.0

13.4

9.3

13.9

9.2

14.6

9.4

15.3

9.3

15.7

9.6

16.8

9.5

17.6

9.6

27.8

13.2

9.1

13.6

9.0

14.3

9.2

14.9

9.2

15.3

9.4

16.4

9.3

17.2

9.4

30.0

13.0

9.0

13.3

8.9

14.1

9.1

14.7

9.0

15.1

9.3

16.1

9.2

16.9

9.3

32.8

12.8

8.9

13.0

8.8

13.8

9.0

14.4

8.9

14.7

9.1

15.7

9.0

16.5

9.1

35.0

12.6

8.8

12.8

8.6

13.5

8.8

14.1

8.8

14.5

9.0

15.5

8.9

16.2

9.0

37.8

12.3

8.6

12.5

8.5

13.2

8.7

13.8

8.6

14.1

8.9

15.1

8.7

15.8

8.8

40.0

12.1

8.5

12.3

8.4

12.9

8.5

13.5

8.5

13.9

8.7

14.8

8.6

15.5

8.7

43.3

11.8

8.4

11.9

8.2

12.6

8.4

13.1

8.3

13.5

8.6

14.4

8.4

15.1

8.5

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-75

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

15.3

10.8

15.9

10.8

17.0

11.1

17.8

11.1

18.2

11.4

19.5

11.3

20.5

11.4

22.8

15.3

10.8

15.8

10.8

16.7

11.0

17.4

10.9

17.9

11.2

19.1

11.1

20.0

11.2

25.0

15.1

10.7

15.5

10.6

16.4

10.9

17.1

10.8

17.6

11.1

18.8

10.9

19.7

11.1

27.8

14.8

10.5

15.2

10.4

16.1

10.7

16.7

10.6

17.2

10.9

18.4

10.8

19.3

10.9

30.0

14.6

10.4

14.9

10.3

15.8

10.6

16.5

10.5

16.9

10.8

18.0

10.6

18.9

10.8

32.8

14.3

10.3

14.6

10.1

15.4

10.4

16.1

10.3

16.5

10.6

17.6

10.5

18.5

10.6

35.0

14.1

10.2

14.3

10.0

15.2

10.3

15.8

10.2

16.2

10.5

17.3

10.3

18.2

10.5

37.8

13.8

10.0

14.0

9.8

14.8

10.1

15.4

10.0

15.8

10.3

16.9

10.2

17.7

10.3

40.0

13.6

9.9

13.8

9.7

14.5

9.9

15.1

9.9

15.5

10.2

16.6

10.1

17.4

10.2

43.3

13.3

9.7

13.4

9.5

14.1

9.8

14.7

9.7

15.1

10.0

16.1

9.9

16.9

10.0

20.0

20.5

14.3

21.2

14.2

22.7

14.7

23.7

14.6

24.4

15.0

26.1

14.8

27.3

15.0

22.8

20.4

14.2

21.1

14.2

22.3

14.5

23.3

14.4

23.9

14.8

25.5

14.6

26.8

14.7

25.0

20.1

14.0

20.7

14.0

21.9

14.3

22.9

14.2

23.5

14.6

25.1

14.4

26.3

14.5

27.8

19.7

13.8

20.3

13.7

21.5

14.0

22.4

13.9

23.0

14.3

24.5

14.2

25.7

14.3

30.0

19.5

13.7

20.0

13.6

21.1

13.9

22.0

13.8

22.6

14.2

24.1

14.0

25.3

14.1

32.8

19.1

13.5

19.5

13.3

20.6

13.6

21.5

13.5

22.0

13.9

23.6

13.7

24.7

13.9

35.0

18.8

13.3

19.2

13.1

20.2

13.4

21.1

13.3

21.6

13.7

23.1

13.6

24.3

13.7

37.8

18.4

13.1

18.7

12.9

19.7

13.2

20.6

13.1

21.1

13.5

22.6

13.3

23.7

13.5

40.0

18.1

13.0

18.4

12.7

19.4

13.0

20.2

12.9

20.7

13.3

22.2

13.1

23.3

13.3

43.3

17.7

12.8

17.9

12.5

18.8

12.8

19.6

12.7

20.2

13.1

21.5

12.9

22.6

13.1

20.0

27.3

19.1

28.2

19.1

30.2

19.7

31.6

19.6

32.5

20.1

34.7

19.9

36.4

20.1

22.8

27.2

19.1

28.1

19.0

29.7

19.4

31.0

19.3

31.8

19.8

34.0

19.6

35.6

19.8

25.0

26.8

18.8

27.6

18.7

29.2

19.2

30.5

19.0

31.2

19.6

33.4

19.3

35.0

19.5

27.8

26.3

18.6

27.0

18.4

28.6

18.9

29.8

18.7

30.6

19.3

32.7

19.0

34.3

19.2

30.0

25.9

18.4

26.6

18.2

28.1

18.6

29.3

18.5

30.0

19.0

32.1

18.8

33.7

19.0

32.8

25.4

18.1

26.0

17.9

27.4

18.3

28.6

18.2

29.4

18.7

31.4

18.5

32.9

18.7

35.0

25.0

17.9

25.5

17.6

26.9

18.1

28.1

17.9

28.8

18.5

30.8

18.2

32.3

18.5

37.8

24.6

17.7

24.9

17.3

26.3

17.8

27.5

17.6

28.2

18.2

30.1

17.9

31.6

18.2

40.0

24.2

17.5

24.5

17.1

25.8

17.5

26.9

17.4

27.6

17.9

29.5

17.7

31.0

17.9

43.3

23.6

17.2

23.8

16.8

25.1

17.2

26.2

17.1

26.8

17.6

28.7

17.4

30.1

17.6

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-76

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.1

1.4

2.2

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.0

1.4

2.2

1.4

2.3

1.4

25.0

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.0

1.4

2.1

1.4

2.2

1.4

27.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.3

2.2

1.4

30.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.1

1.3

2.2

1.4

32.8

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.3

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

37.8

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

40.0

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.8

1.3

1.9

1.3

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.8

1.3

1.9

1.3

20.0

2.2

1.6

2.3

1.6

2.5

1.7

2.6

1.7

2.7

1.7

2.8

1.7

3.0

1.7

22.8

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.7

2.6

1.7

2.8

1.7

2.9

1.7

25.0

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.6

1.7

2.7

1.7

2.9

1.7

27.8

2.2

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

2.7

1.6

2.8

1.7

30.0

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.6

1.6

2.8

1.6

32.8

2.1

1.6

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.6

1.6

2.7

1.6

35.0

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.6

1.6

37.8

2.0

1.5

2.0

1.5

2.2

1.5

2.2

1.5

2.3

1.6

2.5

1.6

2.6

1.6

40.0

2.0

1.5

2.0

1.5

2.1

1.5

2.2

1.5

2.3

1.6

2.4

1.5

2.5

1.6

43.3

1.9

1.5

1.9

1.5

2.1

1.5

2.1

1.5

2.2

1.5

2.3

1.5

2.5

1.5

20.0

3.4

2.4

3.5

2.4

3.8

2.4

3.9

2.4

4.0

2.5

4.3

2.5

4.5

2.5

22.8

3.4

2.4

3.5

2.4

3.7

2.4

3.9

2.4

4.0

2.5

4.2

2.4

4.4

2.5

25.0

3.3

2.3

3.4

2.3

3.6

2.4

3.8

2.4

3.9

2.4

4.2

2.4

4.4

2.4

27.8

3.3

2.3

3.4

2.3

3.6

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.3

2.4

30.0

3.2

2.3

3.3

2.3

3.5

2.3

3.6

2.3

3.7

2.4

4.0

2.3

4.2

2.4

32.8

3.2

2.2

3.2

2.2

3.4

2.3

3.6

2.3

3.7

2.3

3.9

2.3

4.1

2.3

35.0

3.1

2.2

3.2

2.2

3.4

2.2

3.5

2.2

3.6

2.3

3.8

2.3

4.0

2.3

37.8

3.1

2.2

3.1

2.2

3.3

2.2

3.4

2.2

3.5

2.3

3.7

2.2

3.9

2.3

40.0

3.0

2.2

3.0

2.1

3.2

2.2

3.4

2.2

3.4

2.2

3.7

2.2

3.9

2.2

43.3

2.9

2.1

3.0

2.1

3.1

2.1

3.3

2.1

3.3

2.2

3.6

2.2

3.7

2.2

20.0

4.3

3.2

4.4

3.2

4.7

3.3

5.0

3.3

5.1

3.4

5.4

3.4

5.7

3.4

22.8

4.3

3.2

4.4

3.2

4.7

3.3

4.8

3.3

5.0

3.4

5.3

3.3

5.6

3.4

25.0

4.2

3.2

4.3

3.2

4.6

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.3

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.7

3.2

4.8

3.3

5.1

3.2

5.4

3.3

30.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.1

4.7

3.2

5.0

3.2

5.3

3.3

32.8

4.0

3.1

4.1

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.2

5.2

3.2

35.0

3.9

3.0

4.0

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.8

3.1

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.1

40.0

3.8

3.0

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.1

4.8

3.1

43.3

3.7

2.9

3.7

2.9

3.9

3.0

4.1

2.9

4.2

3.0

4.5

3.0

4.7

3.1

20.0

5.1

3.8

5.3

3.8

5.7

3.9

6.0

3.9

6.1

4.0

6.5

4.0

6.9

4.0

22.8

5.1

3.8

5.3

3.8

5.6

3.9

5.8

3.8

6.0

4.0

6.4

3.9

6.7

4.0

25.0

5.1

3.7

5.2

3.7

5.5

3.8

5.7

3.8

5.9

3.9

6.3

3.9

6.6

3.9

27.8

5.0

3.7

5.1

3.7

5.4

3.8

5.6

3.7

5.8

3.9

6.2

3.8

6.5

3.9

30.0

4.9

3.7

5.0

3.6

5.3

3.7

5.5

3.7

5.7

3.8

6.1

3.8

6.4

3.8

32.8

4.8

3.6

4.9

3.6

5.2

3.7

5.4

3.6

5.5

3.8

5.9

3.7

6.2

3.8

35.0

4.7

3.6

4.8

3.5

5.1

3.6

5.3

3.6

5.4

3.7

5.8

3.7

6.1

3.7

37.8

4.6

3.5

4.7

3.5

5.0

3.6

5.2

3.6

5.3

3.7

5.7

3.6

6.0

3.7
3.6

40.0

4.6

3.5

4.6

3.4

4.9

3.5

5.1

3.5

5.2

3.6

5.6

3.6

5.8

43.3

4.5

3.4

4.5

3.4

4.7

3.5

4.9

3.5

5.1

3.6

5.4

3.5

5.7

3.6

20.0

6.8

5.0

7.0

5.0

7.5

5.1

7.9

5.1

8.1

5.3

8.6

5.2

9.1

5.3

22.8

6.8

5.0

7.0

5.0

7.4

5.1

7.7

5.0

7.9

5.2

8.5

5.1

8.9

5.2

25.0

6.7

4.9

6.9

4.9

7.3

5.0

7.6

5.0

7.8

5.2

8.3

5.1

8.7

5.2

27.8

6.6

4.9

6.7

4.8

7.1

5.0

7.4

4.9

7.6

5.1

8.1

5.0

8.5

5.1

30.0

6.5

4.8

6.6

4.8

7.0

4.9

7.3

4.9

7.5

5.0

8.0

5.0

8.4

5.0

32.8

6.3

4.8

6.5

4.7

6.8

4.8

7.1

4.8

7.3

5.0

7.8

4.9

8.2

5.0

35.0

6.2

4.7

6.4

4.6

6.7

4.8

7.0

4.7

7.2

4.9

7.7

4.8

8.1

4.9

37.8

6.1

4.6

6.2

4.6

6.6

4.7

6.8

4.7

7.0

4.8

7.5

4.8

7.9

4.8

40.0

6.0

4.6

6.1

4.5

6.4

4.6

6.7

4.6

6.9

4.8

7.4

4.7

7.7

4.8

43.3

5.9

4.5

5.9

4.4

6.2

4.6

6.5

4.5

6.7

4.7

7.1

4.6

7.5

4.7

20.0

7.7

5.5

7.9

5.5

8.5

5.7

8.9

5.7

9.1

5.9

9.8

5.8

10.2

5.9

22.8

7.6

5.5

7.9

5.5

8.4

5.6

8.7

5.6

8.9

5.8

9.6

5.7

10.0

5.8

25.0

7.5

5.5

7.8

5.4

8.2

5.6

8.6

5.5

8.8

5.7

9.4

5.6

9.9

5.7

27.8

7.4

5.4

7.6

5.4

8.0

5.5

8.4

5.5

8.6

5.6

9.2

5.6

9.6

5.6

30.0

7.3

5.3

7.5

5.3

7.9

5.4

8.2

5.4

8.4

5.6

9.0

5.5

9.5

5.6

32.8

7.1

5.3

7.3

5.2

7.7

5.3

8.1

5.3

8.3

5.5

8.8

5.4

9.3

5.5

35.0

7.0

5.2

7.2

5.2

7.6

5.3

7.9

5.3

8.1

5.4

8.7

5.3

9.1

5.4

37.8

6.9

5.2

7.0

5.1

7.4

5.2

7.7

5.2

7.9

5.3

8.5

5.3

8.9

5.3

40.0

6.8

5.1

6.9

5.0

7.3

5.1

7.6

5.1

7.8

5.3

8.3

5.2

8.7

5.3

43.3

6.6

5.0

6.7

4.9

7.0

5.0

7.4

5.0

7.5

5.2

8.1

5.1

8.5

5.2

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-77

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

8.5

6.1

8.8

6.1

9.5

6.3

9.9

6.3

10.2

6.5

10.9

6.4

11.4

6.5

22.8

8.5

6.1

8.8

6.1

9.3

6.2

9.7

6.2

10.0

6.4

10.6

6.3

11.2

6.4

25.0

8.4

6.0

8.7

6.0

9.1

6.2

9.5

6.1

9.8

6.3

10.5

6.2

11.0

6.3

27.8

8.2

6.0

8.5

5.9

8.9

6.1

9.3

6.0

9.6

6.2

10.2

6.1

10.7

6.2

30.0

8.1

5.9

8.3

5.8

8.8

6.0

9.2

5.9

9.4

6.1

10.0

6.0

10.6

6.1

32.8

8.0

5.8

8.1

5.8

8.6

5.9

9.0

5.9

9.2

6.0

9.8

6.0

10.3

6.0

35.0

7.8

5.8

8.0

5.7

8.4

5.8

8.8

5.8

9.0

6.0

9.6

5.9

10.1

6.0

37.8

7.7

5.7

7.8

5.6

8.2

5.7

8.6

5.7

8.8

5.9

9.4

5.8

9.9

5.9

40.0

7.6

5.6

7.7

5.5

8.1

5.7

8.4

5.6

8.7

5.8

9.2

5.7

9.7

5.8

43.3

7.4

5.5

7.4

5.4

7.8

5.6

8.2

5.5

8.4

5.7

9.0

5.6

9.4

5.7

20.0

10.3

7.6

10.7

7.5

11.4

7.8

11.9

7.8

12.2

8.0

13.1

7.9

13.7

8.0

22.8

10.3

7.6

10.6

7.5

11.2

7.7

11.7

7.7

12.0

7.9

12.8

7.8

13.4

7.9

25.0

10.1

7.5

10.4

7.4

11.0

7.6

11.5

7.6

11.8

7.8

12.6

7.7

13.2

7.8

27.8

9.9

7.4

10.2

7.3

10.8

7.5

11.2

7.5

11.5

7.7

12.3

7.6

12.9

7.7

30.0

9.8

7.3

10.0

7.2

10.6

7.4

11.0

7.4

11.3

7.6

12.1

7.5

12.7

7.6

32.8

9.6

7.2

9.8

7.1

10.3

7.3

10.8

7.3

11.1

7.5

11.8

7.4

12.4

7.5

35.0

9.4

7.1

9.6

7.0

10.2

7.2

10.6

7.2

10.9

7.4

11.6

7.3

12.2

7.5

37.8

9.3

7.1

9.4

6.9

9.9

7.1

10.4

7.1

10.6

7.3

11.3

7.2

11.9

7.4

40.0

9.1

7.0

9.2

6.9

9.7

7.0

10.2

7.0

10.4

7.2

11.1

7.1

11.7

7.3

43.3

8.9

6.9

9.0

6.7

9.5

6.9

9.9

6.9

10.1

7.1

10.8

7.0

11.3

7.2

20.0

13.7

9.7

14.2

9.7

15.1

10.0

15.9

10.0

16.3

10.3

17.4

10.1

18.3

10.2

22.8

13.6

9.7

14.1

9.7

14.9

9.9

15.5

9.8

15.9

10.1

17.0

10.0

17.9

10.1

25.0

13.4

9.6

13.9

9.5

14.6

9.8

15.3

9.7

15.7

10.0

16.8

9.9

17.6

10.0
9.8

27.8

13.2

9.5

13.6

9.4

14.3

9.6

14.9

9.6

15.3

9.8

16.4

9.7

17.2

30.0

13.0

9.4

13.3

9.3

14.1

9.5

14.7

9.4

15.1

9.7

16.1

9.6

16.9

9.7

32.8

12.8

9.2

13.0

9.1

13.8

9.3

14.4

9.3

14.7

9.6

15.7

9.4

16.5

9.6

35.0

12.6

9.1

12.8

9.0

13.5

9.2

14.1

9.2

14.5

9.5

15.5

9.3

16.2

9.5

37.8

12.3

9.0

12.5

8.9

13.2

9.1

13.8

9.0

14.1

9.3

15.1

9.2

15.8

9.3

40.0

12.1

8.9

12.3

8.8

12.9

9.0

13.5

8.9

13.9

9.2

14.8

9.1

15.5

9.2

43.3

11.8

8.8

11.9

8.6

12.6

8.8

13.1

8.7

13.5

9.0

14.4

8.9

15.1

9.0

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-78

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PMFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.6

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.7

2.2

1.6

2.3

SHC
1.7

22.8

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.0

1.6

2.2

1.6

2.3

1.7

25.0

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.0

1.6

2.1

1.6

2.2

1.7

27.8

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.6

30.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

1.9

1.6

2.1

1.6

2.2

1.6

32.8

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

35.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

37.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

1.9

1.5

2.0

1.6

40.0

1.5

1.5

1.6

1.4

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

43.3

1.5

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.5

1.9

1.6

20.0

2.2

1.9

2.3

1.9

2.5

1.9

2.6

1.9

2.7

2.0

2.8

2.0

3.0

2.0

22.8

2.2

1.9

2.3

1.9

2.4

1.9

2.5

1.9

2.6

2.0

2.8

2.0

2.9

2.0

25.0

2.2

1.9

2.3

1.8

2.4

1.9

2.5

1.9

2.6

2.0

2.7

1.9

2.9

2.0

27.8

2.2

1.8

2.2

1.8

2.3

1.9

2.4

1.9

2.5

1.9

2.7

1.9

2.8

2.0

30.0

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.9

2.5

1.9

2.6

1.9

2.8

1.9

32.8

2.1

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.6

1.9

2.7

1.9

35.0

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.5

1.9

2.6

1.9

37.8

2.0

1.8

2.0

1.7

2.2

1.8

2.2

1.8

2.3

1.9

2.5

1.8

2.6

1.9

40.0

2.0

1.8

2.0

1.7

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.8

2.5

1.9

43.3

1.9

1.7

1.9

1.7

2.1

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.5

1.8

20.0

3.4

2.5

3.5

2.4

3.8

2.5

3.9

2.5

4.0

2.6

4.3

2.6

4.5

2.6

22.8

3.4

2.4

3.5

2.4

3.7

2.5

3.9

2.5

4.0

2.6

4.2

2.5

4.4

2.6

25.0

3.3

2.4

3.4

2.4

3.6

2.5

3.8

2.5

3.9

2.5

4.2

2.5

4.4

2.5

27.8

3.3

2.4

3.4

2.4

3.6

2.4

3.7

2.4

3.8

2.5

4.1

2.5

4.3

2.5

30.0

3.2

2.4

3.3

2.3

3.5

2.4

3.6

2.4

3.7

2.5

4.0

2.4

4.2

2.5

32.8

3.2

2.3

3.2

2.3

3.4

2.4

3.6

2.4

3.7

2.4

3.9

2.4

4.1

2.4

35.0

3.1

2.3

3.2

2.3

3.4

2.3

3.5

2.3

3.6

2.4

3.8

2.4

4.0

2.4

37.8

3.1

2.3

3.1

2.2

3.3

2.3

3.4

2.3

3.5

2.4

3.7

2.3

3.9

2.4

40.0

3.0

2.3

3.0

2.2

3.2

2.3

3.4

2.3

3.4

2.3

3.7

2.3

3.9

2.3

43.3

2.9

2.2

3.0

2.2

3.1

2.2

3.3

2.2

3.3

2.3

3.6

2.3

3.7

2.3

20.0

4.3

3.0

4.4

3.0

4.7

3.1

5.0

3.1

5.1

3.2

5.4

3.1

5.7

3.2

22.8

4.3

3.0

4.4

3.0

4.7

3.1

4.8

3.0

5.0

3.1

5.3

3.1

5.6

3.1

25.0

4.2

3.0

4.3

2.9

4.6

3.0

4.8

3.0

4.9

3.1

5.2

3.0

5.5

3.1

27.8

4.1

2.9

4.2

2.9

4.5

3.0

4.7

2.9

4.8

3.0

5.1

3.0

5.4

3.0

30.0

4.1

2.9

4.2

2.9

4.4

2.9

4.6

2.9

4.7

3.0

5.0

3.0

5.3

3.0

32.8

4.0

2.9

4.1

2.8

4.3

2.9

4.5

2.9

4.6

3.0

4.9

2.9

5.2

2.9

35.0

3.9

2.8

4.0

2.8

4.2

2.8

4.4

2.8

4.5

2.9

4.8

2.9

5.1

2.9

37.8

3.8

2.8

3.9

2.7

4.1

2.8

4.3

2.8

4.4

2.9

4.7

2.8

4.9

2.9

40.0

3.8

2.8

3.8

2.7

4.0

2.8

4.2

2.7

4.3

2.8

4.6

2.8

4.8

2.8

43.3

3.7

2.7

3.7

2.6

3.9

2.7

4.1

2.7

4.2

2.8

4.5

2.7

4.7

2.8

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-79

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PLFY-P-NCMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

2.2

2.0

2.3

2.0

2.5

2.0

2.6

2.0

2.7

2.1

2.8

2.1

3.0

SHC
2.1

22.8

2.2

2.0

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

25.0

2.2

2.0

2.3

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.7

2.1

2.9

2.1

27.8

2.2

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.8

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.0

2.8

2.1

32.8

2.1

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.0

35.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.6

2.0

37.8

2.0

1.9

2.0

1.8

2.2

1.9

2.2

1.9

2.3

2.0

2.5

2.0

2.6

2.0

40.0

2.0

1.9

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

1.9

2.5

2.0

43.3

1.9

1.8

1.9

1.8

2.1

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.5

2.0

20.0

3.4

2.6

3.5

2.6

3.8

2.7

3.9

2.7

4.0

2.8

4.3

2.8

4.5

2.8

22.8

3.4

2.6

3.5

2.6

3.7

2.7

3.9

2.7

4.0

2.8

4.2

2.7

4.4

2.8

25.0

3.3

2.6

3.4

2.6

3.6

2.7

3.8

2.6

3.9

2.7

4.2

2.7

4.4

2.7

27.8

3.3

2.6

3.4

2.6

3.6

2.6

3.7

2.6

3.8

2.7

4.1

2.7

4.3

2.7

30.0

3.2

2.5

3.3

2.5

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.6

4.2

2.7

32.8

3.2

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.7

2.6

3.9

2.6

4.1

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.5

3.5

2.5

3.6

2.6

3.8

2.6

4.0

2.6

37.8

3.1

2.5

3.1

2.4

3.3

2.5

3.4

2.5

3.5

2.6

3.7

2.5

3.9

2.6

40.0

3.0

2.4

3.0

2.4

3.2

2.5

3.4

2.5

3.4

2.6

3.7

2.5

3.9

2.6

43.3

2.9

2.4

3.0

2.4

3.1

2.4

3.3

2.4

3.3

2.5

3.6

2.5

3.7

2.5

20.0

4.3

3.1

4.4

3.1

4.7

3.2

5.0

3.2

5.1

3.3

5.4

3.2

5.7

3.3

22.8

4.3

3.1

4.4

3.1

4.7

3.1

4.8

3.1

5.0

3.2

5.3

3.2

5.6

3.2

25.0

4.2

3.0

4.3

3.0

4.6

3.1

4.8

3.1

4.9

3.2

5.2

3.1

5.5

3.2

27.8

4.1

3.0

4.2

3.0

4.5

3.1

4.7

3.0

4.8

3.1

5.1

3.1

5.4

3.1

30.0

4.1

3.0

4.2

2.9

4.4

3.0

4.6

3.0

4.7

3.1

5.0

3.0

5.3

3.1

32.8

4.0

2.9

4.1

2.9

4.3

3.0

4.5

3.0

4.6

3.0

4.9

3.0

5.2

3.0

35.0

3.9

2.9

4.0

2.9

4.2

2.9

4.4

2.9

4.5

3.0

4.8

3.0

5.1

3.0

37.8

3.8

2.9

3.9

2.8

4.1

2.9

4.3

2.9

4.4

3.0

4.7

2.9

4.9

3.0

40.0

3.8

2.8

3.8

2.8

4.0

2.9

4.2

2.8

4.3

2.9

4.6

2.9

4.8

2.9

43.3

3.7

2.8

3.7

2.7

3.9

2.8

4.1

2.8

4.2

2.9

4.5

2.8

4.7

2.9

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-80

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PLFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.4

2.9

3.5

2.9

3.8

3.0

3.9

3.0

4.0

3.1

4.3

3.0

4.5

3.1

22.8

3.4

2.9

3.5

2.9

3.7

2.9

3.9

2.9

4.0

3.0

4.2

3.0

4.4

3.1
3.0

SHC

25.0

3.3

2.8

3.4

2.8

3.6

2.9

3.8

2.9

3.9

3.0

4.2

3.0

4.4

27.8

3.3

2.8

3.4

2.8

3.6

2.9

3.7

2.9

3.8

3.0

4.1

2.9

4.3

3.0

30.0

3.2

2.8

3.3

2.8

3.5

2.9

3.6

2.8

3.7

3.0

4.0

2.9

4.2

3.0

32.8

3.2

2.8

3.2

2.7

3.4

2.8

3.6

2.8

3.7

2.9

3.9

2.9

4.1

3.0

35.0

3.1

2.7

3.2

2.7

3.4

2.8

3.5

2.8

3.6

2.9

3.8

2.9

4.0

2.9

37.8

3.1

2.7

3.1

2.7

3.3

2.8

3.4

2.8

3.5

2.9

3.7

2.8

3.9

2.9

40.0

3.0

2.7

3.0

2.7

3.2

2.7

3.4

2.7

3.4

2.8

3.7

2.8

3.9

2.9

43.3

2.9

2.7

3.0

2.6

3.1

2.7

3.3

2.7

3.3

2.8

3.6

2.8

3.7

2.8

20.0

4.3

3.5

4.4

3.5

4.7

3.6

5.0

3.6

5.1

3.7

5.4

3.7

5.7

3.8
3.7

22.8

4.3

3.5

4.4

3.5

4.7

3.6

4.8

3.6

5.0

3.7

5.3

3.7

5.6

25.0

4.2

3.5

4.3

3.4

4.6

3.6

4.8

3.5

4.9

3.7

5.2

3.6

5.5

3.7

27.8

4.1

3.4

4.2

3.4

4.5

3.5

4.7

3.5

4.8

3.6

5.1

3.6

5.4

3.7

30.0

4.1

3.4

4.2

3.4

4.4

3.5

4.6

3.5

4.7

3.6

5.0

3.5

5.3

3.6

32.8

4.0

3.4

4.1

3.3

4.3

3.4

4.5

3.4

4.6

3.6

4.9

3.5

5.2

3.6

35.0

3.9

3.3

4.0

3.3

4.2

3.4

4.4

3.4

4.5

3.5

4.8

3.5

5.1

3.6

37.8

3.8

3.3

3.9

3.3

4.1

3.4

4.3

3.4

4.4

3.5

4.7

3.4

4.9

3.5

40.0

3.8

3.3

3.8

3.2

4.0

3.3

4.2

3.3

4.3

3.4

4.6

3.4

4.8

3.5
3.4

43.3

3.7

3.2

3.7

3.2

3.9

3.3

4.1

3.3

4.2

3.4

4.5

3.4

4.7

20.0

5.1

4.2

5.3

4.2

5.7

4.3

6.0

4.3

6.1

4.5

6.5

4.4

6.9

4.5

22.8

5.1

4.2

5.3

4.2

5.6

4.3

5.8

4.3

6.0

4.4

6.4

4.4

6.7

4.5

25.0

5.1

4.1

5.2

4.1

5.5

4.2

5.7

4.2

5.9

4.4

6.3

4.3

6.6

4.4

27.8

5.0

4.1

5.1

4.1

5.4

4.2

5.6

4.2

5.8

4.3

6.2

4.3

6.5

4.4

30.0

4.9

4.1

5.0

4.0

5.3

4.2

5.5

4.1

5.7

4.3

6.1

4.2

6.4

4.3

32.8

4.8

4.0

4.9

4.0

5.2

4.1

5.4

4.1

5.5

4.2

5.9

4.2

6.2

4.3

35.0

4.7

4.0

4.8

3.9

5.1

4.1

5.3

4.1

5.4

4.2

5.8

4.1

6.1

4.2

37.8

4.6

3.9

4.7

3.9

5.0

4.0

5.2

4.0

5.3

4.2

5.7

4.1

6.0

4.2
4.2

40.0

4.6

3.9

4.6

3.9

4.9

4.0

5.1

4.0

5.2

4.1

5.6

4.1

5.8

43.3

4.5

3.9

4.5

3.8

4.7

3.9

4.9

3.9

5.1

4.1

5.4

4.0

5.7

4.1

20.0

6.8

5.2

7.0

5.1

7.5

5.3

7.9

5.3

8.1

5.5

8.6

5.4

9.1

5.5
5.4

22.8

6.8

5.1

7.0

5.1

7.4

5.3

7.7

5.2

7.9

5.4

8.5

5.3

8.9

25.0

6.7

5.1

6.9

5.1

7.3

5.2

7.6

5.2

7.8

5.3

8.3

5.3

8.7

5.4

27.8

6.6

5.0

6.7

5.0

7.1

5.1

7.4

5.1

7.6

5.3

8.1

5.2

8.5

5.3

30.0

6.5

5.0

6.6

4.9

7.0

5.1

7.3

5.0

7.5

5.2

8.0

5.1

8.4

5.2

32.8

6.3

4.9

6.5

4.9

6.8

5.0

7.1

5.0

7.3

5.1

7.8

5.1

8.2

5.2

35.0

6.2

4.9

6.4

4.8

6.7

5.0

7.0

4.9

7.2

5.1

7.7

5.0

8.1

5.1
5.1

37.8

6.1

4.8

6.2

4.7

6.6

4.9

6.8

4.9

7.0

5.0

7.5

5.0

7.9

40.0

6.0

4.8

6.1

4.7

6.4

4.8

6.7

4.8

6.9

5.0

7.4

4.9

7.7

5.0

43.3

5.9

4.7

5.9

4.6

6.2

4.7

6.5

4.7

6.7

4.9

7.1

4.8

7.5

4.9

20.0

8.5

6.2

8.8

6.2

9.5

6.4

9.9

6.3

10.2

6.5

10.9

6.5

11.4

6.5

22.8

8.5

6.2

8.8

6.1

9.3

6.3

9.7

6.3

10.0

6.4

10.6

6.4

11.2

6.4

25.0

8.4

6.1

8.7

6.1

9.1

6.2

9.5

6.2

9.8

6.4

10.5

6.3

11.0

6.4

27.8

8.2

6.0

8.5

6.0

8.9

6.1

9.3

6.1

9.6

6.3

10.2

6.2

10.7

6.3

30.0

8.1

6.0

8.3

5.9

8.8

6.1

9.2

6.0

9.4

6.2

10.0

6.1

10.6

6.2

32.8

8.0

5.9

8.1

5.8

8.6

6.0

9.0

5.9

9.2

6.1

9.8

6.0

10.3

6.1

35.0

7.8

5.8

8.0

5.7

8.4

5.9

8.8

5.9

9.0

6.0

9.6

6.0

10.1

6.1

37.8

7.7

5.8

7.8

5.7

8.2

5.8

8.6

5.8

8.8

6.0

9.4

5.9

9.9

6.0

40.0

7.6

5.7

7.7

5.6

8.1

5.7

8.4

5.7

8.7

5.9

9.2

5.8

9.7

5.9

43.3

7.4

5.6

7.4

5.5

7.8

5.6

8.2

5.6

8.4

5.8

9.0

5.7

9.4

5.8

20.0

10.3

7.9

10.7

7.9

11.4

8.1

11.9

8.1

12.2

8.4

13.1

8.3

13.7

8.4

22.8

10.3

7.9

10.6

7.8

11.2

8.0

11.7

8.0

12.0

8.3

12.8

8.2

13.4

8.3
8.2

25.0

10.1

7.8

10.4

7.7

11.0

8.0

11.5

7.9

11.8

8.2

12.6

8.1

13.2

27.8

9.9

7.7

10.2

7.6

10.8

7.9

11.2

7.8

11.5

8.1

12.3

8.0

12.9

8.1

30.0

9.8

7.6

10.0

7.6

10.6

7.8

11.0

7.7

11.3

8.0

12.1

7.9

12.7

8.0

32.8

9.6

7.5

9.8

7.5

10.3

7.7

10.8

7.6

11.1

7.9

11.8

7.8

12.4

7.9

35.0

9.4

7.5

9.6

7.4

10.2

7.6

10.6

7.5

10.9

7.8

11.6

7.7

12.2

7.9

37.8

9.3

7.4

9.4

7.3

9.9

7.5

10.4

7.4

10.6

7.7

11.3

7.6

11.9

7.8

40.0

9.1

7.3

9.2

7.2

9.7

7.4

10.2

7.4

10.4

7.6

11.1

7.5

11.7

7.7

43.3

8.9

7.2

9.0

7.1

9.5

7.3

9.9

7.2

10.1

7.5

10.8

7.4

11.3

7.6

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-81

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PCFY-P-NGMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

4.3

3.2

4.4

3.2

4.7

3.3

5.0

3.3

5.1

3.4

5.4

3.4

5.7

3.4

22.8

4.3

3.2

4.4

3.2

4.7

3.3

4.8

3.3

5.0

3.4

5.3

3.3

5.6

3.4

25.0

4.2

3.2

4.3

3.2

4.6

3.2

4.8

3.2

4.9

3.3

5.2

3.3

5.5

3.3

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.7

3.2

4.8

3.3

5.1

3.2

5.4

3.3

30.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.1

4.7

3.2

5.0

3.2

5.3

3.3
3.2

32.8

4.0

3.1

4.1

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.2

5.2

35.0

3.9

3.0

4.0

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.8

3.1

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.1
3.1

40.0

3.8

3.0

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.1

4.8

43.3

3.7

2.9

3.7

2.9

3.9

3.0

4.1

2.9

4.2

3.0

4.5

3.0

4.7

3.1

20.0

6.8

5.0

7.0

5.0

7.5

5.1

7.9

5.1

8.1

5.3

8.6

5.2

9.1

5.3

22.8

6.8

5.0

7.0

5.0

7.4

5.1

7.7

5.0

7.9

5.2

8.5

5.1

8.9

5.2

25.0

6.7

4.9

6.9

4.9

7.3

5.0

7.6

5.0

7.8

5.2

8.3

5.1

8.7

5.2

27.8

6.6

4.9

6.7

4.8

7.1

5.0

7.4

4.9

7.6

5.1

8.1

5.0

8.5

5.1

30.0

6.5

4.8

6.6

4.8

7.0

4.9

7.3

4.9

7.5

5.0

8.0

5.0

8.4

5.0

32.8

6.3

4.8

6.5

4.7

6.8

4.8

7.1

4.8

7.3

5.0

7.8

4.9

8.2

5.0

35.0

6.2

4.7

6.4

4.6

6.7

4.8

7.0

4.7

7.2

4.9

7.7

4.8

8.1

4.9
4.8

37.8

6.1

4.6

6.2

4.6

6.6

4.7

6.8

4.7

7.0

4.8

7.5

4.8

7.9

40.0

6.0

4.6

6.1

4.5

6.4

4.6

6.7

4.6

6.9

4.8

7.4

4.7

7.7

4.8

43.3

5.9

4.5

5.9

4.4

6.2

4.6

6.5

4.5

6.7

4.7

7.1

4.6

7.5

4.7

20.0

8.5

6.1

8.8

6.1

9.5

6.3

9.9

6.3

10.2

6.5

10.9

6.4

11.4

6.5

22.8

8.5

6.1

8.8

6.1

9.3

6.2

9.7

6.2

10.0

6.4

10.6

6.3

11.2

6.4

25.0

8.4

6.0

8.7

6.0

9.1

6.2

9.5

6.1

9.8

6.3

10.5

6.2

11.0

6.3

27.8

8.2

6.0

8.5

5.9

8.9

6.1

9.3

6.0

9.6

6.2

10.2

6.1

10.7

6.2

30.0

8.1

5.9

8.3

5.8

8.8

6.0

9.2

5.9

9.4

6.1

10.0

6.0

10.6

6.1

32.8

8.0

5.8

8.1

5.8

8.6

5.9

9.0

5.9

9.2

6.0

9.8

6.0

10.3

6.0

35.0

7.8

5.8

8.0

5.7

8.4

5.8

8.8

5.8

9.0

6.0

9.6

5.9

10.1

6.0

37.8

7.7

5.7

7.8

5.6

8.2

5.7

8.6

5.7

8.8

5.9

9.4

5.8

9.9

5.9

40.0

7.6

5.6

7.7

5.5

8.1

5.7

8.4

5.6

8.7

5.8

9.2

5.7

9.7

5.8

43.3

7.4

5.5

7.4

5.4

7.8

5.6

8.2

5.5

8.4

5.7

9.0

5.6

9.4

5.7

20.0

10.3

7.6

10.7

7.5

11.4

7.8

11.9

7.8

12.2

8.0

13.1

7.9

13.7

8.0

22.8

10.3

7.6

10.6

7.5

11.2

7.7

11.7

7.7

12.0

7.9

12.8

7.8

13.4

7.9
7.8

25.0

10.1

7.5

10.4

7.4

11.0

7.6

11.5

7.6

11.8

7.8

12.6

7.7

13.2

27.8

9.9

7.4

10.2

7.3

10.8

7.5

11.2

7.5

11.5

7.7

12.3

7.6

12.9

7.7

30.0

9.8

7.3

10.0

7.2

10.6

7.4

11.0

7.4

11.3

7.6

12.1

7.5

12.7

7.6

32.8

9.6

7.2

9.8

7.1

10.3

7.3

10.8

7.3

11.1

7.5

11.8

7.4

12.4

7.5

35.0

9.4

7.1

9.6

7.0

10.2

7.2

10.6

7.2

10.9

7.4

11.6

7.3

12.2

7.5

37.8

9.3

7.1

9.4

6.9

9.9

7.1

10.4

7.1

10.6

7.3

11.3

7.2

11.9

7.4

40.0

9.1

7.0

9.2

6.9

9.7

7.0

10.2

7.0

10.4

7.2

11.1

7.1

11.7

7.3

43.3

8.9

6.9

9.0

6.7

9.5

6.9

9.9

6.9

10.1

7.1

10.8

7.0

11.3

7.2

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-82

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.1

1.4

2.2

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.0

1.4

2.2

1.4

2.3

1.4

25.0

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.0

1.4

2.1

1.4

2.2

1.4

27.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.3

2.2

1.4

30.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.1

1.3

2.2

1.4

32.8

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.3

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

37.8

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

40.0

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.8

1.3

1.9

1.3

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.8

1.3

1.9

1.3

20.0

2.2

1.7

2.3

1.7

2.5

1.7

2.6

1.7

2.7

1.8

2.8

1.8

3.0

1.8

22.8

2.2

1.7

2.3

1.7

2.4

1.7

2.5

1.7

2.6

1.8

2.8

1.7

2.9

1.8

25.0

2.2

1.7

2.3

1.6

2.4

1.7

2.5

1.7

2.6

1.7

2.7

1.7

2.9

1.7

27.8

2.2

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.7

1.7

2.8

1.7

30.0

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

2.6

1.7

2.8

1.7

32.8

2.1

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.6

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.6

2.6

1.7

37.8

2.0

1.6

2.0

1.5

2.2

1.6

2.2

1.6

2.3

1.6

2.5

1.6

2.6

1.6

40.0

2.0

1.5

2.0

1.5

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

43.3

1.9

1.5

1.9

1.5

2.1

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.5

1.6

20.0

3.4

2.7

3.5

2.7

3.8

2.8

3.9

2.8

4.0

2.9

4.3

2.8

4.5

2.9

22.8

3.4

2.7

3.5

2.7

3.7

2.7

3.9

2.7

4.0

2.8

4.2

2.8

4.4

2.8

25.0

3.3

2.7

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.8

4.2

2.8

4.4

2.8

27.8

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.7

3.8

2.8

4.1

2.7

4.3

2.8

30.0

3.2

2.6

3.3

2.6

3.5

2.7

3.6

2.6

3.7

2.7

4.0

2.7

4.2

2.8

32.8

3.2

2.6

3.2

2.5

3.4

2.6

3.6

2.6

3.7

2.7

3.9

2.7

4.1

2.7

35.0

3.1

2.6

3.2

2.5

3.4

2.6

3.5

2.6

3.6

2.7

3.8

2.6

4.0

2.7

37.8

3.1

2.5

3.1

2.5

3.3

2.6

3.4

2.6

3.5

2.6

3.7

2.6

3.9

2.7

40.0

3.0

2.5

3.0

2.5

3.2

2.5

3.4

2.5

3.4

2.6

3.7

2.6

3.9

2.6

43.3

2.9

2.5

3.0

2.4

3.1

2.5

3.3

2.5

3.3

2.6

3.6

2.5

3.7

2.6

20.0

4.3

3.2

4.4

3.2

4.7

3.3

5.0

3.3

5.1

3.4

5.4

3.4

5.7

3.4

22.8

4.3

3.2

4.4

3.2

4.7

3.3

4.8

3.3

5.0

3.4

5.3

3.3

5.6

3.4

25.0

4.2

3.2

4.3

3.2

4.6

3.3

4.8

3.2

4.9

3.4

5.2

3.3

5.5

3.4

27.8

4.1

3.2

4.2

3.1

4.5

3.2

4.7

3.2

4.8

3.3

5.1

3.3

5.4

3.3

30.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.7

3.3

5.0

3.2

5.3

3.3

32.8

4.0

3.1

4.1

3.1

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.2

5.2

3.2

35.0

3.9

3.1

4.0

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.8

3.2

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.1

3.1

4.3

3.0

4.4

3.2

4.7

3.1

4.9

3.2

40.0

3.8

3.0

3.8

2.9

4.0

3.0

4.2

3.0

4.3

3.1

4.6

3.1

4.8

3.1

43.3

3.7

3.0

3.7

2.9

3.9

3.0

4.1

3.0

4.2

3.1

4.5

3.0

4.7

3.1

20.0

5.1

4.1

5.3

4.1

5.7

4.2

6.0

4.2

6.1

4.4

6.5

4.3

6.9

4.4

22.8

5.1

4.1

5.3

4.1

5.6

4.2

5.8

4.2

6.0

4.3

6.4

4.3

6.7

4.3

25.0

5.1

4.1

5.2

4.0

5.5

4.2

5.7

4.1

5.9

4.3

6.3

4.2

6.6

4.3

27.8

5.0

4.0

5.1

4.0

5.4

4.1

5.6

4.1

5.8

4.2

6.2

4.2

6.5

4.3

30.0

4.9

4.0

5.0

3.9

5.3

4.1

5.5

4.0

5.7

4.2

6.1

4.1

6.4

4.2

32.8

4.8

3.9

4.9

3.9

5.2

4.0

5.4

4.0

5.5

4.1

5.9

4.1

6.2

4.2

35.0

4.7

3.9

4.8

3.9

5.1

4.0

5.3

4.0

5.4

4.1

5.8

4.0

6.1

4.1

37.8

4.6

3.9

4.7

3.8

5.0

3.9

5.2

3.9

5.3

4.0

5.7

4.0

6.0

4.1
4.0

40.0

4.6

3.8

4.6

3.8

4.9

3.9

5.1

3.9

5.2

4.0

5.6

4.0

5.8

43.3

4.5

3.8

4.5

3.7

4.7

3.8

4.9

3.8

5.1

4.0

5.4

3.9

5.7

4.0

20.0

6.8

5.1

7.0

5.1

7.5

5.3

7.9

5.2

8.1

5.4

8.6

5.3

9.1

5.4

22.8

6.8

5.1

7.0

5.1

7.4

5.2

7.7

5.2

7.9

5.3

8.5

5.3

8.9

5.3

25.0

6.7

5.0

6.9

5.0

7.3

5.1

7.6

5.1

7.8

5.3

8.3

5.2

8.7

5.3

27.8

6.6

5.0

6.7

4.9

7.1

5.1

7.4

5.0

7.6

5.2

8.1

5.1

8.5

5.2

30.0

6.5

4.9

6.6

4.9

7.0

5.0

7.3

5.0

7.5

5.2

8.0

5.1

8.4

5.2

32.8

6.3

4.9

6.5

4.8

6.8

4.9

7.1

4.9

7.3

5.1

7.8

5.0

8.2

5.1

35.0

6.2

4.8

6.4

4.8

6.7

4.9

7.0

4.9

7.2

5.0

7.7

5.0

8.1

5.0

37.8

6.1

4.8

6.2

4.7

6.6

4.8

6.8

4.8

7.0

5.0

7.5

4.9

7.9

5.0

40.0

6.0

4.7

6.1

4.6

6.4

4.8

6.7

4.7

6.9

4.9

7.4

4.8

7.7

4.9

43.3

5.9

4.6

5.9

4.6

6.2

4.7

6.5

4.7

6.7

4.8

7.1

4.8

7.5

4.9

20.0

8.5

6.8

8.8

6.8

9.5

7.1

9.9

7.0

10.2

7.3

10.9

7.2

11.4

7.3

22.8

8.5

6.8

8.8

6.8

9.3

7.0

9.7

7.0

10.0

7.2

10.6

7.1

11.2

7.3

25.0

8.4

6.8

8.7

6.7

9.1

6.9

9.5

6.9

9.8

7.1

10.5

7.0

11.0

7.2

27.8

8.2

6.7

8.5

6.6

8.9

6.8

9.3

6.8

9.6

7.1

10.2

7.0

10.7

7.1

30.0

8.1

6.6

8.3

6.6

8.8

6.8

9.2

6.7

9.4

7.0

10.0

6.9

10.6

7.0

32.8

8.0

6.6

8.1

6.5

8.6

6.7

9.0

6.7

9.2

6.9

9.8

6.8

10.3

7.0

35.0

7.8

6.5

8.0

6.4

8.4

6.6

8.8

6.6

9.0

6.8

9.6

6.8

10.1

6.9

37.8

7.7

6.4

7.8

6.3

8.2

6.5

8.6

6.5

8.8

6.8

9.4

6.7

9.9

6.8

40.0

7.6

6.4

7.7

6.3

8.1

6.5

8.4

6.5

8.7

6.7

9.2

6.6

9.7

6.8

43.3

7.4

6.3

7.4

6.2

7.8

6.4

8.2

6.4

8.4

6.6

9.0

6.5

9.4

6.7

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-83

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-1. Cooling CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.4

2.2

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.0

1.4

2.2

1.4

2.3

1.4

25.0

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.0

1.4

2.1

1.3

2.2

1.4

27.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.2

1.3

30.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.1

1.3

2.2

1.3

32.8

1.6

1.2

1.7

1.2

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.2

1.8

1.3

2.0

1.3

2.1

1.3

37.8

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.8

1.3

1.9

1.3

2.0

1.3

40.0

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.8

1.3

1.9

1.2

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.8

1.2

1.9

1.2

20.0

2.2

1.7

2.3

1.7

2.5

1.8

2.6

1.7

2.7

1.8

2.8

1.8

3.0

1.8

22.8

2.2

1.7

2.3

1.7

2.4

1.7

2.5

1.7

2.6

1.8

2.8

1.8

2.9

1.8

25.0

2.2

1.7

2.3

1.7

2.4

1.7

2.5

1.7

2.6

1.8

2.7

1.7

2.9

1.8

27.8

2.2

1.7

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.7

1.7

2.8

1.7

30.0

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.6

1.7

2.8

1.7

32.8

2.1

1.6

2.1

1.6

2.2

1.7

2.3

1.6

2.4

1.7

2.6

1.7

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.7

2.6

1.7

37.8

2.0

1.6

2.0

1.6

2.2

1.6

2.2

1.6

2.3

1.7

2.5

1.6

2.6

1.7

40.0

2.0

1.6

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

43.3

1.9

1.6

1.9

1.5

2.1

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.6

20.0

3.4

2.4

3.5

2.4

3.8

2.4

3.9

2.4

4.0

2.5

4.3

2.5

4.5

2.5

22.8

3.4

2.4

3.5

2.3

3.7

2.4

3.9

2.4

4.0

2.4

4.2

2.4

4.4

2.4

25.0

3.3

2.3

3.4

2.3

3.6

2.4

3.8

2.3

3.9

2.4

4.2

2.4

4.4

2.4

27.8

3.3

2.3

3.4

2.3

3.6

2.3

3.7

2.3

3.8

2.4

4.1

2.3

4.3

2.4

30.0

3.2

2.3

3.3

2.2

3.5

2.3

3.6

2.3

3.7

2.3

4.0

2.3

4.2

2.3

32.8

3.2

2.2

3.2

2.2

3.4

2.3

3.6

2.2

3.7

2.3

3.9

2.3

4.1

2.3

35.0

3.1

2.2

3.2

2.2

3.4

2.2

3.5

2.2

3.6

2.3

3.8

2.2

4.0

2.3

37.8

3.1

2.2

3.1

2.1

3.3

2.2

3.4

2.2

3.5

2.2

3.7

2.2

3.9

2.2

40.0

3.0

2.2

3.0

2.1

3.2

2.2

3.4

2.1

3.4

2.2

3.7

2.2

3.9

2.2

43.3

2.9

2.1

3.0

2.1

3.1

2.1

3.3

2.1

3.3

2.2

3.6

2.1

3.7

2.2

20.0

4.3

3.0

4.4

3.0

4.7

3.1

5.0

3.1

5.1

3.2

5.4

3.1

5.7

3.2

22.8

4.3

3.0

4.4

3.0

4.7

3.1

4.8

3.0

5.0

3.1

5.3

3.1

5.6

3.1

25.0

4.2

3.0

4.3

2.9

4.6

3.0

4.8

3.0

4.9

3.1

5.2

3.0

5.5

3.1

27.8

4.1

2.9

4.2

2.9

4.5

3.0

4.7

2.9

4.8

3.0

5.1

3.0

5.4

3.0

30.0

4.1

2.9

4.2

2.9

4.4

2.9

4.6

2.9

4.7

3.0

5.0

3.0

5.3

3.0

32.8

4.0

2.8

4.1

2.8

4.3

2.9

4.5

2.9

4.6

2.9

4.9

2.9

5.2

2.9

35.0

3.9

2.8

4.0

2.8

4.2

2.8

4.4

2.8

4.5

2.9

4.8

2.9

5.1

2.9

37.8

3.8

2.8

3.9

2.7

4.1

2.8

4.3

2.8

4.4

2.9

4.7

2.8

4.9

2.9

40.0

3.8

2.7

3.8

2.7

4.0

2.8

4.2

2.7

4.3

2.8

4.6

2.8

4.8

2.8

43.3

3.7

2.7

3.7

2.6

3.9

2.7

4.1

2.7

4.2

2.8

4.5

2.7

4.7

2.8

20.0

5.1

3.7

5.3

3.7

5.7

3.8

6.0

3.8

6.1

3.9

6.5

3.8

6.9

3.9

22.8

5.1

3.7

5.3

3.7

5.6

3.7

5.8

3.7

6.0

3.8

6.4

3.8

6.7

3.8

25.0

5.1

3.6

5.2

3.6

5.5

3.7

5.7

3.7

5.9

3.8

6.3

3.7

6.6

3.8

27.8

5.0

3.6

5.1

3.6

5.4

3.6

5.6

3.6

5.8

3.7

6.2

3.7

6.5

3.7

30.0

4.9

3.5

5.0

3.5

5.3

3.6

5.5

3.6

5.7

3.7

6.1

3.6

6.4

3.7

32.8

4.8

3.5

4.9

3.5

5.2

3.5

5.4

3.5

5.5

3.6

5.9

3.6

6.2

3.6

35.0

4.7

3.5

4.8

3.4

5.1

3.5

5.3

3.5

5.4

3.6

5.8

3.5

6.1

3.6

37.8

4.6

3.4

4.7

3.4

5.0

3.4

5.2

3.4

5.3

3.5

5.7

3.5

6.0

3.5
3.5

40.0

4.6

3.4

4.6

3.3

4.9

3.4

5.1

3.4

5.2

3.5

5.6

3.4

5.8

43.3

4.5

3.3

4.5

3.3

4.7

3.3

4.9

3.3

5.1

3.4

5.4

3.4

5.7

3.4

20.0

6.8

4.7

7.0

4.7

7.5

4.9

7.9

4.8

8.1

5.0

8.6

4.9

9.1

5.0

22.8

6.8

4.7

7.0

4.7

7.4

4.8

7.7

4.8

7.9

4.9

8.5

4.8

8.9

4.9

25.0

6.7

4.7

6.9

4.6

7.3

4.7

7.6

4.7

7.8

4.8

8.3

4.8

8.7

4.8

27.8

6.6

4.6

6.7

4.6

7.1

4.7

7.4

4.6

7.6

4.8

8.1

4.7

8.5

4.8

30.0

6.5

4.5

6.6

4.5

7.0

4.6

7.3

4.6

7.5

4.7

8.0

4.6

8.4

4.7

32.8

6.3

4.5

6.5

4.4

6.8

4.5

7.1

4.5

7.3

4.6

7.8

4.6

8.2

4.6

35.0

6.2

4.4

6.4

4.4

6.7

4.5

7.0

4.4

7.2

4.6

7.7

4.5

8.1

4.6

37.8

6.1

4.4

6.2

4.3

6.6

4.4

6.8

4.4

7.0

4.5

7.5

4.4

7.9

4.5

40.0

6.0

4.3

6.1

4.2

6.4

4.3

6.7

4.3

6.9

4.4

7.4

4.4

7.7

4.4

43.3

5.9

4.2

5.9

4.1

6.2

4.2

6.5

4.2

6.7

4.3

7.1

4.3

7.5

4.3

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-84

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-2-2. Heating CapacityPUHY-P120~144, PURY-P120T(S)HMU/Y(S)HMU with All Indoor Units


Model
size

06

08

12

15

18

24

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
1.2
1.2
1.2
1.2
1.5
1.4
1.4
1.3
1.7
1.6
1.5
1.3
1.9
1.8
1.6
1.3
2.0
1.9
1.6
1.3
2.2
2.0
1.6
1.3
2.2
2.0
1.6
1.3
2.3
2.0
1.6
1.3
2.4
2.0
1.6
1.3
2.4
2.0
1.6
1.3
2.4
2.0
1.6
1.3
1.6
1.6
1.5
1.5
1.9
1.8
1.8
1.8
2.2
2.1
2.0
1.8
2.5
2.3
2.0
1.8
2.6
2.5
2.0
1.8
2.8
2.6
2.0
1.8
2.9
2.6
2.0
1.8
3.0
2.6
2.0
1.8
3.1
2.6
2.0
1.8
3.1
2.6
2.0
1.8
3.1
2.6
2.0
1.8
2.5
2.4
2.4
2.4
2.9
2.8
2.7
2.7
3.3
3.2
3.1
2.7
3.8
3.5
3.1
2.7
4.0
3.8
3.1
2.7
4.3
4.0
3.1
2.7
4.5
4.0
3.1
2.7
4.6
4.0
3.1
2.7
4.8
4.0
3.1
2.7
4.8
4.0
3.1
2.7
4.8
4.0
3.1
2.7
3.1
3.0
2.9
2.9
3.6
3.5
3.4
3.4
4.2
4.0
3.8
3.4
4.7
4.4
3.9
3.4
5.1
4.7
3.9
3.4
5.4
5.0
3.9
3.4
5.6
5.0
3.9
3.4
5.8
5.0
3.9
3.4
6.1
5.0
3.9
3.4
6.1
5.0
3.9
3.4
6.1
5.0
3.9
3.4
3.6
3.5
3.5
3.5
4.3
4.1
4.0
4.0
4.9
4.7
4.5
4.0
5.6
5.2
4.6
4.0
6.0
5.6
4.6
4.0
6.3
5.9
4.6
4.0
6.6
5.9
4.6
4.0
6.9
5.9
4.6
4.0
7.1
5.9
4.6
4.0
7.1
5.9
4.6
4.0
7.1
5.9
4.6
4.0
4.9
4.7
4.7
4.7
5.7
5.5
5.4
5.3
6.6
6.2
6.1
5.3
5.3
7.5
7.0
6.2
8.0
7.4
6.2
5.3
8.5
7.9
6.2
5.3
8.8
7.9
6.2
5.3
9.2
7.9
6.2
5.3
9.6
7.9
6.2
5.3
9.6
7.9
6.2
5.3
9.6
7.9
6.2
5.3
5.4
5.3
5.2
5.2
6.4
6.1
6.0
5.9
7.4
7.0
6.8
5.9
8.3
7.8
6.9
5.9
8.9
8.3
6.9
5.9
9.5
8.8
6.9
5.9
9.8
8.8
6.9
5.9
10.2
8.8
6.9
5.9
10.6
8.8
6.9
5.9
10.6
8.8
6.9
5.9
10.6
8.8
6.9
5.9
kcal/h = kW x 860, BTU/h = kW x 3,412

Model
size

30

36

48

54

72

96

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
6.2
6.0
5.9
5.9
7.3
7.0
6.8
6.7
8.4
7.9
7.7
6.7
9.4
8.9
7.9
6.7
10.1
9.4
7.9
6.7
10.8
10.0
7.9
6.7
11.2
10.0
7.9
6.7
11.6
10.0
7.9
6.7
12.1
10.0
7.9
6.7
12.1
10.0
7.9
6.7
12.1
10.0
7.9
6.7
7.2
7.0
6.9
6.9
8.5
8.2
7.9
7.9
9.8
9.2
9.0
7.9
11.0
10.4
9.2
7.9
11.8
11.0
9.2
7.9
12.6
11.7
9.2
7.9
13.1
11.7
9.2
7.9
13.6
11.7
9.2
7.9
14.2
11.7
9.2
7.9
14.2
11.7
9.2
7.9
14.2
11.7
9.2
7.9
9.8
9.5
9.3
9.3
11.5
11.0
10.7
10.6
13.2
12.5
12.1
10.6
14.9
14.0
12.4
10.6
16.0
14.9
12.4
10.6
17.0
15.8
12.4
10.6
17.7
15.8
12.4
10.6
18.4
15.8
12.4
10.6
19.1
15.8
12.4
10.6
19.1
15.8
12.4
10.6
19.1
15.8
12.4
10.6
10.9
10.6
10.4
10.4
12.8
12.3
12.0
11.9
14.7
13.9
13.5
11.9
16.6
15.6
13.8
11.9
17.8
16.6
13.8
11.9
18.9
17.6
13.8
11.9
19.7
17.6
13.8
11.9
20.5
17.6
13.8
11.9
21.3
17.6
13.8
11.9
21.3
17.6
13.8
11.9
21.3
17.6
13.8
11.9
14.5
14.0
13.8
13.8
17.0
16.3
15.9
15.8
19.6
18.5
18.0
15.8
22.1
20.7
18.4
15.8
23.6
22.1
18.4
15.8
25.2
23.4
18.4
15.8
26.2
23.4
18.4
15.8
27.2
23.4
18.4
15.8
28.3
23.4
18.4
15.8
28.3
23.4
18.4
15.8
28.3
23.4
18.4
15.8
19.6
19.0
18.7
18.7
23.0
22.1
21.5
21.4
26.5
25.0
24.3
21.4
29.9
28.1
24.9
21.4
32.0
29.9
24.9
21.4
34.1
31.7
24.9
21.4
35.4
31.7
24.9
21.4
36.8
31.7
24.9
21.4
38.4
31.7
24.9
21.4
38.4
31.7
24.9
21.4
38.4
31.7
24.9
21.4
kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NOMINAL
CAPACITY
TABLES

27

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

NCT-85

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3. Cooing and Heating Capacity with PUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU-A


2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PEFY-P-NMSU-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.7

22.8

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

1.9

1.6

2.1

1.6

2.2

1.6

SHC

25.0

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

1.9

1.6

2.1

1.6

2.2

1.6

27.8

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.2

1.6

30.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

32.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

35.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

37.8

1.6

1.5

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.6

2.0

1.6

2.1

1.6

40.0

1.5

1.5

1.6

1.4

1.7

1.5

1.7

1.5

1.8

1.6

2.0

1.6

2.1

1.6

43.3

1.5

1.5

1.5

1.4

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

20.0

2.2

2.0

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

22.8

2.2

2.0

2.3

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

25.0

2.2

1.9

2.2

1.9

2.4

2.0

2.4

2.0

2.5

2.1

2.7

2.1

2.9

2.1

27.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.9

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.8

2.1

32.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.0

2.7

2.0

2.8

2.1

35.0

2.1

1.9

2.1

1.9

2.3

2.0

2.3

1.9

2.4

2.0

2.6

2.0

2.8

2.1

37.8

2.1

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.1

40.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.1

43.3

2.0

1.9

2.0

1.8

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.7

2.0

20.0

3.3

2.6

3.4

2.6

3.6

2.7

3.8

2.6

3.9

2.8

4.2

2.7

4.4

2.8

22.8

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.6

3.9

2.7

4.2

2.7

4.4

2.8

25.0

3.3

2.6

3.4

2.6

3.6

2.6

3.7

2.6

3.8

2.7

4.1

2.7

4.3

2.8

27.8

3.2

2.6

3.3

2.5

3.5

2.6

3.6

2.6

3.8

2.7

4.1

2.7

4.3

2.7

30.0

3.2

2.5

3.3

2.5

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.7

4.3

2.7

32.8

3.2

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.7

2.7

4.0

2.7

4.2

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.5

3.7

2.7

4.0

2.6

4.2

2.7

37.8

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.5

3.6

2.6

3.9

2.6

4.1

2.7

40.0

3.1

2.5

3.1

2.5

3.3

2.5

3.4

2.5

3.6

2.6

3.9

2.6

4.1

2.7

43.3

3.0

2.5

3.1

2.4

3.3

2.5

3.4

2.5

3.5

2.6

3.8

2.6

4.0

2.7

20.0

4.2

3.1

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

3.3

22.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.1

4.8

3.3

5.2

3.2

5.5

3.3

25.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.1

4.8

3.3

5.1

3.2

5.4

3.3

27.8

4.0

3.1

4.1

3.0

4.4

3.1

4.5

3.1

4.7

3.2

5.1

3.2

5.4

3.3

30.0

4.0

3.0

4.1

3.0

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.3

3.2

32.8

3.9

3.0

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

5.0

3.2

5.3

3.2

35.0

3.9

3.0

4.0

3.0

4.3

3.1

4.4

3.0

4.6

3.2

4.9

3.1

5.2

3.2

37.8

3.9

3.0

3.9

2.9

4.2

3.0

4.3

3.0

4.5

3.1

4.9

3.1

5.2

3.2

40.0

3.8

3.0

3.9

2.9

4.1

3.0

4.3

3.0

4.5

3.1

4.8

3.1

5.1

3.2

43.3

3.8

2.9

3.8

2.9

4.1

3.0

4.2

3.0

4.4

3.1

4.8

3.1

5.1

3.2

20.0

5.0

3.9

5.1

3.8

5.5

4.0

5.6

3.9

5.9

4.1

6.3

4.0

6.6

4.1

22.8

4.9

3.8

5.1

3.8

5.4

3.9

5.6

3.9

5.8

4.0

6.2

4.0

6.5

4.1

25.0

4.9

3.8

5.0

3.8

5.3

3.9

5.5

3.9

5.7

4.0

6.2

4.0

6.5

4.1

27.8

4.8

3.8

5.0

3.8

5.3

3.9

5.5

3.8

5.7

4.0

6.1

4.0

6.4

4.0

30.0

4.8

3.8

4.9

3.7

5.2

3.9

5.4

3.8

5.6

4.0

6.1

3.9

6.4

4.0

32.8

4.7

3.7

4.9

3.7

5.2

3.8

5.3

3.8

5.6

4.0

6.0

3.9

6.3

4.0

35.0

4.7

3.7

4.8

3.7

5.1

3.8

5.3

3.8

5.5

3.9

5.9

3.9

6.3

4.0

37.8

4.6

3.7

4.7

3.6

5.0

3.8

5.2

3.7

5.4

3.9

5.9

3.9

6.2

4.0
3.9

40.0

4.6

3.7

4.7

3.6

5.0

3.7

5.2

3.7

5.4

3.9

5.8

3.9

6.2

43.3

4.5

3.6

4.6

3.6

4.9

3.7

5.1

3.7

5.3

3.9

5.7

3.8

6.1

3.9

20.0

6.6

5.1

6.8

5.1

7.3

5.2

7.5

5.2

7.8

5.4

8.4

5.3

8.8

5.4

22.8

6.6

5.1

6.8

5.0

7.2

5.2

7.4

5.1

7.7

5.3

8.3

5.3

8.7

5.4

25.0

6.5

5.0

6.7

5.0

7.1

5.1

7.3

5.1

7.6

5.3

8.2

5.3

8.6

5.4

27.8

6.4

5.0

6.6

5.0

7.0

5.1

7.3

5.1

7.5

5.3

8.1

5.2

8.6

5.3

30.0

6.4

5.0

6.5

4.9

6.9

5.1

7.2

5.0

7.5

5.2

8.1

5.2

8.5

5.3

32.8

6.3

4.9

6.5

4.9

6.9

5.0

7.1

5.0

7.4

5.2

8.0

5.2

8.4

5.3

35.0

6.2

4.9

6.4

4.8

6.8

5.0

7.0

5.0

7.3

5.2

7.9

5.1

8.3

5.2

37.8

6.2

4.9

6.3

4.8

6.7

5.0

6.9

4.9

7.2

5.1

7.8

5.1

8.2

5.2

40.0

6.1

4.8

6.2

4.8

6.6

4.9

6.9

4.9

7.2

5.1

7.7

5.1

8.2

5.2

43.3

6.0

4.8

6.1

4.7

6.5

4.9

6.8

4.9

7.1

5.1

7.6

5.0

8.1

5.2

NOMINAL
CAPACITY
TABLES

24

Entering air temp.

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-86

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

4.2

2.9

4.3

2.8

4.5

2.9

4.7

2.9

4.9

3.0

5.2

2.9

5.5

SHC
3.0

22.8

4.1

2.8

4.2

2.8

4.5

2.9

4.6

2.8

4.8

2.9

5.2

2.9

5.5

3.0

25.0

4.1

2.8

4.2

2.8

4.4

2.9

4.6

2.8

4.8

2.9

5.1

2.9

5.4

2.9

27.8

4.0

2.8

4.1

2.8

4.4

2.8

4.5

2.8

4.7

2.9

5.1

2.9

5.4

2.9

30.0

4.0

2.8

4.1

2.7

4.3

2.8

4.5

2.8

4.7

2.9

5.0

2.9

5.3

2.9

32.8

3.9

2.7

4.0

2.7

4.3

2.8

4.4

2.7

4.6

2.9

5.0

2.8

5.3

2.9

35.0

3.9

2.7

4.0

2.7

4.3

2.8

4.4

2.7

4.6

2.8

4.9

2.8

5.2

2.9

37.8

3.9

2.7

3.9

2.7

4.2

2.7

4.3

2.7

4.5

2.8

4.9

2.8

5.2

2.8

40.0

3.8

2.7

3.9

2.6

4.1

2.7

4.3

2.7

4.5

2.8

4.8

2.8

5.1

2.8

43.3

3.8

2.6

3.8

2.6

4.1

2.7

4.2

2.6

4.4

2.8

4.8

2.7

5.1

2.8

20.0

5.0

3.5

5.2

3.5

5.5

3.6

5.7

3.5

5.9

3.6

6.3

3.6

6.6

3.6

22.8

5.0

3.5

5.1

3.4

5.4

3.5

5.6

3.5

5.8

3.6

6.2

3.6

6.6

3.6

25.0

4.9

3.4

5.1

3.4

5.4

3.5

5.5

3.4

5.8

3.6

6.2

3.5

6.5

3.6

27.8

4.9

3.4

5.0

3.4

5.3

3.5

5.5

3.4

5.7

3.5

6.1

3.5

6.5

3.6

30.0

4.8

3.4

4.9

3.3

5.2

3.4

5.4

3.4

5.6

3.5

6.1

3.5

6.4

3.5

32.8

4.8

3.3

4.9

3.3

5.2

3.4

5.4

3.4

5.6

3.5

6.0

3.5

6.3

3.5

35.0

4.7

3.3

4.8

3.3

5.1

3.4

5.3

3.3

5.5

3.5

6.0

3.4

6.3

3.5

37.8

4.7

3.3

4.7

3.2

5.1

3.3

5.2

3.3

5.5

3.4

5.9

3.4

6.2

3.5

40.0

4.6

3.3

4.7

3.2

5.0

3.3

5.2

3.3

5.4

3.4

5.8

3.4

6.2

3.4

43.3

4.5

3.2

4.6

3.2

4.9

3.3

5.1

3.2

5.3

3.4

5.8

3.4

6.1

3.4

20.0

6.6

4.6

6.8

4.6

7.2

4.7

7.5

4.6

7.8

4.8

8.3

4.7

8.8

4.8

22.8

6.5

4.5

6.7

4.5

7.1

4.6

7.4

4.6

7.7

4.7

8.3

4.7

8.7

4.7

25.0

6.5

4.5

6.7

4.5

7.1

4.6

7.3

4.5

7.6

4.7

8.2

4.7

8.6

4.7

27.8

6.4

4.5

6.6

4.4

7.0

4.5

7.2

4.5

7.5

4.7

8.1

4.6

8.5

4.7

30.0

6.3

4.4

6.5

4.4

6.9

4.5

7.2

4.4

7.5

4.6

8.0

4.6

8.5

4.6

32.8

6.3

4.4

6.4

4.3

6.8

4.5

7.1

4.4

7.4

4.6

7.9

4.5

8.4

4.6

35.0

6.2

4.4

6.4

4.3

6.8

4.4

7.0

4.4

7.3

4.5

7.9

4.5

8.3

4.6

37.8

6.1

4.3

6.3

4.3

6.7

4.4

6.9

4.3

7.2

4.5

7.8

4.5

8.2

4.6

40.0

6.1

4.3

6.2

4.2

6.6

4.3

6.8

4.3

7.1

4.5

7.7

4.5

8.2

4.5

43.3

6.0

4.2

6.1

4.2

6.5

4.3

6.7

4.2

7.0

4.4

7.6

4.4

8.1

4.5

20.0

7.5

5.2

7.7

5.2

8.2

5.3

8.4

5.3

8.8

5.5

9.4

5.4

9.9

5.5

22.8

7.4

5.2

7.6

5.2

8.1

5.3

8.3

5.2

8.7

5.4

9.3

5.4

9.8

5.4

25.0

7.3

5.2

7.5

5.1

8.0

5.2

8.3

5.2

8.6

5.4

9.2

5.3

9.7

5.4

27.8

7.2

5.1

7.4

5.1

7.9

5.2

8.2

5.1

8.5

5.3

9.1

5.3

9.6

5.4

30.0

7.2

5.1

7.4

5.0

7.8

5.2

8.1

5.1

8.4

5.3

9.1

5.3

9.5

5.3

32.8

7.1

5.0

7.3

5.0

7.7

5.1

8.0

5.0

8.3

5.3

9.0

5.2

9.4

5.3

35.0

7.0

5.0

7.2

4.9

7.6

5.1

7.9

5.0

8.2

5.2

8.9

5.2

9.4

5.3

37.8

6.9

5.0

7.1

4.9

7.5

5.0

7.8

5.0

8.1

5.2

8.8

5.1

9.3

5.2

40.0

6.9

4.9

7.0

4.8

7.4

5.0

7.7

4.9

8.1

5.1

8.7

5.1

9.2

5.2

43.3

6.8

4.9

6.9

4.8

7.3

4.9

7.6

4.9

7.9

5.1

8.6

5.1

9.1

5.2

20.0

8.3

5.8

8.6

5.8

9.1

5.9

9.4

5.9

9.8

6.1

10.5

6.0

11.0

6.1

22.8

8.2

5.8

8.5

5.7

9.0

5.9

9.3

5.8

9.7

6.0

10.4

6.0

10.9

6.0

25.0

8.1

5.7

8.4

5.7

8.9

5.8

9.2

5.8

9.6

6.0

10.3

5.9

10.8

6.0

27.8

8.1

5.7

8.3

5.6

8.8

5.8

9.1

5.7

9.5

5.9

10.2

5.9

10.7

6.0

30.0

8.0

5.6

8.2

5.6

8.7

5.7

9.0

5.7

9.4

5.9

10.1

5.8

10.6

5.9

32.8

7.9

5.6

8.1

5.5

8.6

5.7

8.9

5.6

9.3

5.8

10.0

5.8

10.5

5.9

35.0

7.8

5.6

8.0

5.5

8.5

5.6

8.8

5.6

9.2

5.8

9.9

5.8

10.4

5.9

37.8

7.7

5.5

7.9

5.4

8.4

5.6

8.7

5.5

9.1

5.8

9.8

5.7

10.3

5.8

40.0

7.6

5.5

7.8

5.4

8.3

5.5

8.6

5.5

9.0

5.7

9.7

5.7

10.3

5.8

43.3

7.5

5.4

7.7

5.3

8.2

5.5

8.5

5.4

8.8

5.7

9.6

5.6

10.1

5.7

20.0

10.0

7.2

10.3

7.1

11.0

7.3

11.3

7.2

11.8

7.5

12.6

7.4

13.3

7.5

22.8

9.9

7.1

10.2

7.1

10.8

7.3

11.2

7.2

11.6

7.4

12.5

7.4

13.1

7.5

25.0

9.8

7.1

10.1

7.0

10.7

7.2

11.1

7.1

11.5

7.4

12.4

7.3

13.0

7.4

27.8

9.7

7.0

10.0

7.0

10.6

7.1

10.9

7.1

11.4

7.3

12.3

7.3

12.9

7.4

30.0

9.6

7.0

9.9

6.9

10.5

7.1

10.8

7.0

11.3

7.3

12.2

7.2

12.8

7.4

32.8

9.5

6.9

9.7

6.8

10.3

7.0

10.7

6.9

11.2

7.2

12.0

7.2

12.7

7.3

35.0

9.4

6.9

9.6

6.8

10.2

7.0

10.6

6.9

11.1

7.2

11.9

7.1

12.6

7.3

37.8

9.3

6.8

9.5

6.7

10.1

6.9

10.5

6.8

10.9

7.1

11.8

7.1

12.4

7.2

40.0

9.2

6.8

9.4

6.7

10.0

6.9

10.4

6.8

10.8

7.1

11.7

7.0

12.3

7.2

43.3

9.1

6.7

9.2

6.6

9.8

6.8

10.2

6.7

10.7

7.0

11.5

7.0

12.2

7.1

20.0

13.3

9.2

13.7

9.1

14.6

9.4

15.1

9.2

15.7

9.6

16.8

9.5

17.7

9.6

22.8

13.2

9.1

13.6

9.1

14.4

9.3

14.9

9.1

15.5

9.5

16.6

9.4

17.5

9.5

25.0

13.1

9.0

13.4

9.0

14.3

9.2

14.7

9.1

15.3

9.4

16.5

9.3

17.3

9.5

27.8

12.9

9.0

13.3

8.9

14.1

9.1

14.6

9.0

15.2

9.3

16.3

9.3

17.2

9.4

30.0

12.8

8.9

13.1

8.8

13.9

9.0

14.4

8.9

15.0

9.3

16.2

9.2

17.0

9.3

32.8

12.6

8.8

13.0

8.7

13.8

9.0

14.2

8.8

14.8

9.2

16.0

9.1

16.9

9.3

35.0

12.5

8.7

12.8

8.6

13.6

8.9

14.1

8.8

14.7

9.1

15.8

9.1

16.7

9.2

37.8

12.4

8.7

12.6

8.5

13.4

8.8

13.9

8.7

14.5

9.0

15.7

9.0

16.6

9.1

40.0

12.3

8.6

12.5

8.5

13.3

8.7

13.8

8.6

14.4

9.0

15.5

8.9

16.4

9.1

43.3

12.1

8.5

12.3

8.4

13.1

8.6

13.6

8.5

14.2

8.9

15.3

8.8

16.2

9.0

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-87

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

14.9

10.6

15.4

10.5

16.3

10.8

16.9

10.7

17.5

11.1

18.8

11.0

19.8

11.1

22.8

14.8

10.5

15.2

10.4

16.1

10.7

16.7

10.6

17.3

11.0

18.6

10.9

19.6

11.0

25.0

14.6

10.4

15.1

10.4

16.0

10.6

16.5

10.5

17.2

10.9

18.5

10.8

19.4

11.0

27.8

14.5

10.4

14.9

10.3

15.8

10.5

16.3

10.4

17.0

10.8

18.3

10.7

19.2

10.9

30.0

14.3

10.3

14.7

10.2

15.6

10.5

16.2

10.3

16.8

10.8

18.1

10.7

19.1

10.8

32.8

14.2

10.2

14.5

10.1

15.4

10.4

16.0

10.3

16.6

10.7

17.9

10.6

18.9

10.8

35.0

14.0

10.1

14.4

10.0

15.3

10.3

15.8

10.2

16.5

10.6

17.8

10.5

18.7

10.7

37.8

13.9

10.0

14.2

9.9

15.1

10.2

15.6

10.1

16.3

10.5

17.6

10.4

18.5

10.6

40.0

13.7

10.0

14.0

9.8

14.9

10.1

15.5

10.0

16.1

10.5

17.4

10.4

18.4

10.6

43.3

13.5

9.9

13.8

9.7

14.7

10.0

15.2

9.9

15.9

10.3

17.2

10.3

18.2

10.5

20.0

19.9

14.0

20.6

13.9

21.8

14.2

22.5

14.0

23.4

14.6

25.2

14.4

26.4

14.6

22.8

19.7

13.8

20.3

13.7

21.5

14.1

22.3

13.9

23.1

14.4

24.9

14.3

26.2

14.5

25.0

19.5

13.7

20.1

13.6

21.3

14.0

22.1

13.8

23.0

14.3

24.7

14.2

26.0

14.4

27.8

19.3

13.6

19.9

13.5

21.1

13.8

21.8

13.7

22.7

14.2

24.4

14.1

25.7

14.3

30.0

19.1

13.5

19.6

13.4

20.8

13.7

21.6

13.6

22.5

14.1

24.2

14.0

25.5

14.2

32.8

18.9

13.4

19.4

13.3

20.6

13.6

21.3

13.4

22.2

14.0

23.9

13.9

25.2

14.1

35.0

18.7

13.3

19.2

13.1

20.4

13.5

21.1

13.3

22.0

13.9

23.7

13.8

25.0

14.0

37.8

18.5

13.2

18.9

13.0

20.1

13.4

20.8

13.2

21.7

13.8

23.4

13.7

24.8

13.9

40.0

18.3

13.1

18.7

12.9

19.9

13.3

20.6

13.1

21.5

13.7

23.3

13.6

24.6

13.8

43.3

18.1

13.0

18.4

12.8

19.6

13.1

20.3

13.0

21.2

13.5

22.9

13.5

24.3

13.7

20.0

26.6

18.7

27.4

18.6

29.1

19.1

30.0

18.8

31.2

19.5

33.5

19.4

35.2

19.6

22.8

26.3

18.6

27.1

18.4

28.7

18.9

29.7

18.7

30.8

19.4

33.1

19.2

34.8

19.5

25.0

26.0

18.4

26.8

18.3

28.4

18.8

29.4

18.5

30.6

19.3

32.8

19.1

34.6

19.3

27.8

25.7

18.3

26.4

18.1

28.0

18.6

29.0

18.4

30.2

19.1

32.5

18.9

34.2

19.2

30.0

25.5

18.1

26.2

18.0

27.8

18.5

28.7

18.2

29.9

19.0

32.2

18.8

33.9

19.1
19.0

32.8

25.2

18.0

25.8

17.8

27.4

18.3

28.4

18.1

29.6

18.8

31.9

18.7

33.6

35.0

25.0

17.9

25.5

17.7

27.1

18.2

28.1

17.9

29.3

18.7

31.6

18.6

33.3

18.9

37.8

24.7

17.7

25.2

17.5

26.8

18.0

27.8

17.8

28.9

18.5

31.2

18.4

33.0

18.7

40.0

24.4

17.6

24.9

17.3

26.5

17.8

27.5

17.7

28.7

18.4

31.0

18.3

32.7

18.6

43.3

24.1

17.4

24.5

17.1

26.1

17.6

27.1

17.5

28.2

18.2

30.5

18.1

32.3

18.5

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-88

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.2

1.4

25.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.2

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.1

1.3

2.2

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.1

1.3

2.2

1.4

32.8

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.2

1.4

35.0

1.6

1.3

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.6

1.3

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

40.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

43.3

1.5

1.2

1.6

1.2

1.7

1.3

1.7

1.2

1.8

1.3

2.0

1.3

2.1

1.3

20.0

2.2

1.6

2.2

1.6

2.4

1.6

2.5

1.6

2.6

1.7

2.7

1.7

2.9

1.7

22.8

2.2

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

2.7

1.7

2.9

1.7

25.0

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

2.7

1.6

2.8

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.7

1.6

2.8

1.7

30.0

2.1

1.6

2.1

1.5

2.3

1.6

2.4

1.6

2.4

1.6

2.6

1.6

2.8

1.7

32.8

2.1

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.6

1.6

2.8

1.6

35.0

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.6

1.6

2.7

1.6

37.8

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.5

2.4

1.6

2.6

1.6

2.7

1.6

40.0

2.0

1.5

2.0

1.5

2.2

1.5

2.2

1.5

2.3

1.6

2.5

1.6

2.7

1.6

43.3

2.0

1.5

2.0

1.5

2.1

1.5

2.2

1.5

2.3

1.6

2.5

1.6

2.6

1.6

20.0

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.3

3.9

2.4

4.2

2.4

4.4

2.4

22.8

3.3

2.3

3.4

2.3

3.6

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.3

2.4

25.0

3.2

2.3

3.3

2.3

3.5

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.3

2.4

27.8

3.2

2.3

3.3

2.2

3.5

2.3

3.6

2.3

3.8

2.4

4.0

2.4

4.3

2.4

30.0

3.2

2.3

3.3

2.2

3.5

2.3

3.6

2.3

3.7

2.4

4.0

2.3

4.2

2.4

32.8

3.1

2.2

3.2

2.2

3.4

2.3

3.5

2.2

3.7

2.3

4.0

2.3

4.2

2.4

35.0

3.1

2.2

3.2

2.2

3.4

2.3

3.5

2.2

3.7

2.3

3.9

2.3

4.2

2.3

37.8

3.1

2.2

3.1

2.2

3.3

2.2

3.5

2.2

3.6

2.3

3.9

2.3

4.1

2.3

40.0

3.0

2.2

3.1

2.2

3.3

2.2

3.4

2.2

3.6

2.3

3.9

2.3

4.1

2.3

43.3

3.0

2.2

3.1

2.1

3.2

2.2

3.4

2.2

3.5

2.3

3.8

2.2

4.0

2.3

20.0

4.2

3.2

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

3.3

22.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.2

4.8

3.3

5.2

3.3

5.5

3.3

25.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.8

3.3

5.1

3.2

5.4

3.3

27.8

4.0

3.1

4.1

3.1

4.4

3.2

4.5

3.1

4.7

3.3

5.1

3.2

5.4

3.3

30.0

4.0

3.1

4.1

3.0

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.3

3.3

32.8

3.9

3.1

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

5.0

3.2

5.3

3.3

35.0

3.9

3.0

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

4.9

3.2

5.2

3.2

37.8

3.9

3.0

3.9

3.0

4.2

3.1

4.3

3.0

4.5

3.2

4.9

3.2

5.2

3.2

40.0

3.8

3.0

3.9

3.0

4.1

3.1

4.3

3.0

4.5

3.2

4.8

3.1

5.1

3.2

43.3

3.8

3.0

3.8

2.9

4.1

3.0

4.2

3.0

4.4

3.1

4.8

3.1

5.1

3.2

20.0

5.0

3.7

5.2

3.7

5.5

3.8

5.7

3.8

5.9

3.9

6.3

3.9

6.6

3.9

22.8

5.0

3.7

5.1

3.7

5.4

3.8

5.6

3.7

5.8

3.9

6.2

3.8

6.6

3.9

25.0

4.9

3.7

5.1

3.6

5.4

3.8

5.5

3.7

5.8

3.9

6.2

3.8

6.5

3.9

27.8

4.9

3.6

5.0

3.6

5.3

3.7

5.5

3.7

5.7

3.8

6.1

3.8

6.5

3.9

30.0

4.8

3.6

4.9

3.6

5.2

3.7

5.4

3.7

5.6

3.8

6.1

3.8

6.4

3.8

32.8

4.8

3.6

4.9

3.6

5.2

3.7

5.4

3.6

5.6

3.8

6.0

3.8

6.3

3.8

35.0

4.7

3.6

4.8

3.5

5.1

3.6

5.3

3.6

5.5

3.8

6.0

3.7

6.3

3.8

37.8

4.7

3.5

4.7

3.5

5.1

3.6

5.2

3.6

5.5

3.7

5.9

3.7

6.2

3.8
3.8

40.0

4.6

3.5

4.7

3.5

5.0

3.6

5.2

3.6

5.4

3.7

5.8

3.7

6.2

43.3

4.5

3.5

4.6

3.4

4.9

3.6

5.1

3.5

5.3

3.7

5.8

3.7

6.1

3.7

20.0

6.6

4.9

6.8

4.9

7.2

5.0

7.5

4.9

7.8

5.1

8.3

5.1

8.8

5.2

22.8

6.5

4.9

6.7

4.8

7.1

5.0

7.4

4.9

7.7

5.1

8.3

5.1

8.7

5.1

25.0

6.5

4.8

6.7

4.8

7.1

4.9

7.3

4.9

7.6

5.1

8.2

5.0

8.6

5.1

27.8

6.4

4.8

6.6

4.8

7.0

4.9

7.2

4.8

7.5

5.0

8.1

5.0

8.5

5.1

30.0

6.3

4.8

6.5

4.7

6.9

4.9

7.2

4.8

7.5

5.0

8.0

5.0

8.5

5.1

32.8

6.3

4.7

6.4

4.7

6.8

4.8

7.1

4.8

7.4

5.0

7.9

4.9

8.4

5.0

35.0

6.2

4.7

6.4

4.6

6.8

4.8

7.0

4.7

7.3

4.9

7.9

4.9

8.3

5.0

37.8

6.1

4.7

6.3

4.6

6.7

4.7

6.9

4.7

7.2

4.9

7.8

4.9

8.2

5.0

40.0

6.1

4.6

6.2

4.6

6.6

4.7

6.8

4.7

7.1

4.9

7.7

4.8

8.2

4.9

43.3

6.0

4.6

6.1

4.5

6.5

4.7

6.7

4.6

7.0

4.8

7.6

4.8

8.1

4.9

20.0

7.5

5.4

7.7

5.4

8.2

5.6

8.4

5.5

8.8

5.7

9.4

5.6

9.9

5.7

22.8

7.4

5.4

7.6

5.4

8.1

5.5

8.3

5.4

8.7

5.7

9.3

5.6

9.8

5.7

25.0

7.3

5.4

7.5

5.3

8.0

5.5

8.3

5.4

8.6

5.6

9.2

5.6

9.7

5.7

27.8

7.2

5.3

7.4

5.3

7.9

5.4

8.2

5.4

8.5

5.6

9.1

5.5

9.6

5.6

30.0

7.2

5.3

7.4

5.2

7.8

5.4

8.1

5.3

8.4

5.6

9.1

5.5

9.5

5.6

32.8

7.1

5.2

7.3

5.2

7.7

5.3

8.0

5.3

8.3

5.5

9.0

5.5

9.4

5.6

35.0

7.0

5.2

7.2

5.2

7.6

5.3

7.9

5.3

8.2

5.5

8.9

5.4

9.4

5.5

37.8

6.9

5.2

7.1

5.1

7.5

5.3

7.8

5.2

8.1

5.4

8.8

5.4

9.3

5.5

40.0

6.9

5.1

7.0

5.1

7.4

5.2

7.7

5.2

8.1

5.4

8.7

5.4

9.2

5.5

43.3

6.8

5.1

6.9

5.0

7.3

5.2

7.6

5.1

7.9

5.4

8.6

5.3

9.1

5.4

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-89

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

8.3

6.0

8.6

6.0

9.1

6.1

9.4

6.1

9.8

6.3

10.5

6.2

11.0

6.3

22.8

8.2

6.0

8.5

5.9

9.0

6.1

9.3

6.0

9.7

6.2

10.4

6.2

10.9

6.3

25.0

8.1

5.9

8.4

5.9

8.9

6.0

9.2

6.0

9.6

6.2

10.3

6.1

10.8

6.2

27.8

8.1

5.9

8.3

5.8

8.8

6.0

9.1

5.9

9.5

6.2

10.2

6.1

10.7

6.2

30.0

8.0

5.8

8.2

5.8

8.7

5.9

9.0

5.9

9.4

6.1

10.1

6.1

10.6

6.2

32.8

7.9

5.8

8.1

5.7

8.6

5.9

8.9

5.8

9.3

6.1

10.0

6.0

10.5

6.1

35.0

7.8

5.7

8.0

5.7

8.5

5.9

8.8

5.8

9.2

6.0

9.9

6.0

10.4

6.1

37.8

7.7

5.7

7.9

5.6

8.4

5.8

8.7

5.7

9.1

6.0

9.8

5.9

10.3

6.1

40.0

7.6

5.7

7.8

5.6

8.3

5.8

8.6

5.7

9.0

5.9

9.7

5.9

10.3

6.0

43.3

7.5

5.6

7.7

5.5

8.2

5.7

8.5

5.6

8.8

5.9

9.6

5.9

10.1

6.0

20.0

10.0

7.4

10.3

7.4

11.0

7.6

11.3

7.5

11.8

7.8

12.6

7.7

13.3

7.9

22.8

9.9

7.4

10.2

7.3

10.8

7.5

11.2

7.5

11.6

7.8

12.5

7.7

13.1

7.8

25.0

9.8

7.3

10.1

7.3

10.7

7.5

11.1

7.4

11.5

7.7

12.4

7.6

13.0

7.8

27.8

9.7

7.3

10.0

7.2

10.6

7.4

10.9

7.3

11.4

7.7

12.3

7.6

12.9

7.7

30.0

9.6

7.2

9.9

7.2

10.5

7.4

10.8

7.3

11.3

7.6

12.2

7.5

12.8

7.7

32.8

9.5

7.2

9.7

7.1

10.3

7.3

10.7

7.2

11.2

7.6

12.0

7.5

12.7

7.6

35.0

9.4

7.1

9.6

7.1

10.2

7.3

10.6

7.2

11.1

7.5

11.9

7.4

12.6

7.6

37.8

9.3

7.1

9.5

7.0

10.1

7.2

10.5

7.1

10.9

7.5

11.8

7.4

12.4

7.5

40.0

9.2

7.0

9.4

6.9

10.0

7.2

10.4

7.1

10.8

7.4

11.7

7.4

12.3

7.5

43.3

9.1

7.0

9.2

6.9

9.8

7.1

10.2

7.0

10.7

7.3

11.5

7.3

12.2

7.5

20.0

13.3

9.5

13.7

9.5

14.6

9.7

15.1

9.6

15.7

10.0

16.8

9.9

17.7

10.0

22.8

13.2

9.5

13.6

9.4

14.4

9.7

14.9

9.5

15.5

9.9

16.6

9.8

17.5

9.9

25.0

13.1

9.4

13.4

9.3

14.3

9.6

14.7

9.5

15.3

9.8

16.5

9.7

17.3

9.9

27.8

12.9

9.3

13.3

9.2

14.1

9.5

14.6

9.4

15.2

9.8

16.3

9.7

17.2

9.8

30.0

12.8

9.3

13.1

9.2

13.9

9.4

14.4

9.3

15.0

9.7

16.2

9.6

17.0

9.8

32.8

12.6

9.2

13.0

9.1

13.8

9.3

14.2

9.2

14.8

9.6

16.0

9.5

16.9

9.7

35.0

12.5

9.1

12.8

9.0

13.6

9.3

14.1

9.2

14.7

9.6

15.8

9.5

16.7

9.7

37.8

12.4

9.0

12.6

8.9

13.4

9.2

13.9

9.1

14.5

9.5

15.7

9.4

16.6

9.6

40.0

12.3

9.0

12.5

8.9

13.3

9.1

13.8

9.0

14.4

9.4

15.5

9.4

16.4

9.5

43.3

12.1

8.9

12.3

8.8

13.1

9.0

13.6

8.9

14.2

9.3

15.3

9.3

16.2

9.5

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-90

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PMFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.8

1.5

1.9

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.3

SHC
1.7

22.8

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.7

25.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

2.1

1.6

2.2

1.6

27.8

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

1.9

1.6

2.1

1.6

2.2

1.6

30.0

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.1

1.6

2.2

1.6

32.8

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.2

1.6

35.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

37.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

40.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

43.3

1.5

1.5

1.6

1.4

1.7

1.5

1.7

1.5

1.8

1.6

2.0

1.6

2.1

1.6

20.0

2.2

1.8

2.2

1.8

2.4

1.9

2.5

1.9

2.6

2.0

2.7

1.9

2.9

2.0

22.8

2.2

1.8

2.2

1.8

2.3

1.9

2.4

1.9

2.5

2.0

2.7

1.9

2.9

2.0

25.0

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.9

2.5

1.9

2.7

1.9

2.8

2.0

27.8

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.8

2.5

1.9

2.7

1.9

2.8

2.0

30.0

2.1

1.8

2.1

1.8

2.3

1.9

2.4

1.8

2.4

1.9

2.6

1.9

2.8

2.0

32.8

2.1

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.6

1.9

2.8

1.9

35.0

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.6

1.9

2.7

1.9

37.8

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.6

1.9

2.7

1.9

40.0

2.0

1.8

2.0

1.7

2.2

1.8

2.2

1.8

2.3

1.9

2.5

1.9

2.7

1.9

43.3

2.0

1.8

2.0

1.7

2.1

1.8

2.2

1.8

2.3

1.9

2.5

1.9

2.6

1.9

20.0

3.3

2.4

3.4

2.4

3.6

2.5

3.7

2.4

3.9

2.5

4.2

2.5

4.4

2.5

22.8

3.3

2.4

3.4

2.4

3.6

2.4

3.7

2.4

3.8

2.5

4.1

2.5

4.3

2.5

25.0

3.2

2.4

3.3

2.4

3.5

2.4

3.7

2.4

3.8

2.5

4.1

2.5

4.3

2.5

27.8

3.2

2.4

3.3

2.3

3.5

2.4

3.6

2.4

3.8

2.5

4.0

2.5

4.3

2.5

30.0

3.2

2.3

3.3

2.3

3.5

2.4

3.6

2.4

3.7

2.5

4.0

2.4

4.2

2.5

32.8

3.1

2.3

3.2

2.3

3.4

2.4

3.5

2.3

3.7

2.4

4.0

2.4

4.2

2.5

35.0

3.1

2.3

3.2

2.3

3.4

2.4

3.5

2.3

3.7

2.4

3.9

2.4

4.2

2.4

37.8

3.1

2.3

3.1

2.3

3.3

2.3

3.5

2.3

3.6

2.4

3.9

2.4

4.1

2.4

40.0

3.0

2.3

3.1

2.2

3.3

2.3

3.4

2.3

3.6

2.4

3.9

2.4

4.1

2.4

43.3

3.0

2.3

3.1

2.2

3.2

2.3

3.4

2.3

3.5

2.4

3.8

2.4

4.0

2.4

20.0

4.2

2.9

4.3

2.9

4.5

3.0

4.7

3.0

4.9

3.1

5.2

3.0

5.5

3.1

22.8

4.1

2.9

4.2

2.9

4.5

3.0

4.6

2.9

4.8

3.1

5.2

3.0

5.5

3.1

25.0

4.1

2.9

4.2

2.9

4.4

3.0

4.6

2.9

4.8

3.0

5.1

3.0

5.4

3.0

27.8

4.0

2.9

4.1

2.9

4.4

2.9

4.5

2.9

4.7

3.0

5.1

3.0

5.4

3.0

30.0

4.0

2.9

4.1

2.8

4.3

2.9

4.5

2.9

4.7

3.0

5.0

3.0

5.3

3.0

32.8

3.9

2.8

4.0

2.8

4.3

2.9

4.4

2.8

4.6

3.0

5.0

2.9

5.3

3.0

35.0

3.9

2.8

4.0

2.8

4.3

2.9

4.4

2.8

4.6

2.9

4.9

2.9

5.2

3.0

37.8

3.9

2.8

3.9

2.8

4.2

2.8

4.3

2.8

4.5

2.9

4.9

2.9

5.2

3.0

40.0

3.8

2.8

3.9

2.7

4.1

2.8

4.3

2.8

4.5

2.9

4.8

2.9

5.1

2.9

43.3

3.8

2.7

3.8

2.7

4.1

2.8

4.2

2.8

4.4

2.9

4.8

2.9

5.1

2.9

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-91

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PLFY-P-NCMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

2.2

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.7

2.1

2.9

2.1

22.8

2.2

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.9

2.1

25.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.8

2.1

27.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.0

2.7

2.0

2.8

2.1

30.0

2.1

1.9

2.1

1.9

2.3

2.0

2.4

1.9

2.4

2.0

2.6

2.0

2.8

2.1

32.8

2.1

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.8

2.1

35.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.1
2.0

37.8

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

40.0

2.0

1.9

2.0

1.8

2.2

1.9

2.2

1.9

2.3

2.0

2.5

2.0

2.7

2.0

43.3

2.0

1.9

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.5

2.0

2.6

2.0

20.0

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.6

3.9

2.7

4.2

2.7

4.4

2.8

22.8

3.3

2.6

3.4

2.6

3.6

2.6

3.7

2.6

3.8

2.7

4.1

2.7

4.3

2.7
2.7

25.0

3.2

2.6

3.3

2.5

3.5

2.6

3.7

2.6

3.8

2.7

4.1

2.7

4.3

27.8

3.2

2.5

3.3

2.5

3.5

2.6

3.6

2.6

3.8

2.7

4.0

2.7

4.3

2.7

30.0

3.2

2.5

3.3

2.5

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.6

4.2

2.7

32.8

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.5

3.7

2.7

4.0

2.6

4.2

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.5

3.5

2.5

3.7

2.6

3.9

2.6

4.2

2.7

37.8

3.1

2.5

3.1

2.4

3.3

2.5

3.5

2.5

3.6

2.6

3.9

2.6

4.1

2.7

40.0

3.0

2.5

3.1

2.4

3.3

2.5

3.4

2.5

3.6

2.6

3.9

2.6

4.1

2.6
2.6

43.3

3.0

2.4

3.1

2.4

3.2

2.5

3.4

2.5

3.5

2.6

3.8

2.6

4.0

20.0

4.2

3.0

4.3

3.0

4.5

3.1

4.7

3.0

4.9

3.2

5.2

3.1

5.5

3.2

22.8

4.1

3.0

4.2

3.0

4.5

3.1

4.6

3.0

4.8

3.1

5.2

3.1

5.5

3.2
3.1

25.0

4.1

3.0

4.2

3.0

4.4

3.0

4.6

3.0

4.8

3.1

5.1

3.1

5.4

27.8

4.0

3.0

4.1

2.9

4.4

3.0

4.5

3.0

4.7

3.1

5.1

3.1

5.4

3.1

30.0

4.0

2.9

4.1

2.9

4.3

3.0

4.5

3.0

4.7

3.1

5.0

3.1

5.3

3.1
3.1

32.8

3.9

2.9

4.0

2.9

4.3

3.0

4.4

2.9

4.6

3.1

5.0

3.0

5.3

35.0

3.9

2.9

4.0

2.9

4.3

3.0

4.4

2.9

4.6

3.0

4.9

3.0

5.2

3.1

37.8

3.9

2.9

3.9

2.8

4.2

2.9

4.3

2.9

4.5

3.0

4.9

3.0

5.2

3.1

40.0

3.8

2.9

3.9

2.8

4.1

2.9

4.3

2.9

4.5

3.0

4.8

3.0

5.1

3.0

43.3

3.8

2.8

3.8

2.8

4.1

2.9

4.2

2.8

4.4

3.0

4.8

3.0

5.1

3.0

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-92

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PLFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.3

2.8

3.4

2.8

3.6

2.9

3.7

2.9

3.9

3.0

4.2

3.0

4.4

SHC
3.0

22.8

3.3

2.8

3.4

2.8

3.6

2.9

3.7

2.9

3.8

3.0

4.1

3.0

4.3

3.0

25.0

3.2

2.8

3.3

2.8

3.5

2.9

3.7

2.9

3.8

3.0

4.1

3.0

4.3

3.0

27.8

3.2

2.8

3.3

2.8

3.5

2.9

3.6

2.8

3.8

3.0

4.0

2.9

4.3

3.0

30.0

3.2

2.8

3.3

2.7

3.5

2.8

3.6

2.8

3.7

3.0

4.0

2.9

4.2

3.0

32.8

3.1

2.8

3.2

2.7

3.4

2.8

3.5

2.8

3.7

2.9

4.0

2.9

4.2

3.0

35.0

3.1

2.7

3.2

2.7

3.4

2.8

3.5

2.8

3.7

2.9

3.9

2.9

4.2

3.0

37.8

3.1

2.7

3.1

2.7

3.3

2.8

3.5

2.8

3.6

2.9

3.9

2.9

4.1

3.0

40.0

3.0

2.7

3.1

2.7

3.3

2.8

3.4

2.8

3.6

2.9

3.9

2.9

4.1

2.9

43.3

3.0

2.7

3.1

2.7

3.2

2.8

3.4

2.7

3.5

2.9

3.8

2.9

4.0

2.9

20.0

4.2

3.4

4.3

3.4

4.5

3.5

4.7

3.5

4.9

3.7

5.2

3.6

5.5

3.7

22.8

4.1

3.4

4.2

3.4

4.5

3.5

4.6

3.5

4.8

3.6

5.2

3.6

5.5

3.7

25.0

4.1

3.4

4.2

3.4

4.4

3.5

4.6

3.5

4.8

3.6

5.1

3.6

5.4

3.7

27.8

4.0

3.4

4.1

3.4

4.4

3.5

4.5

3.4

4.7

3.6

5.1

3.6

5.4

3.7

30.0

4.0

3.4

4.1

3.3

4.3

3.5

4.5

3.4

4.7

3.6

5.0

3.6

5.3

3.6

32.8

3.9

3.4

4.0

3.3

4.3

3.4

4.4

3.4

4.6

3.6

5.0

3.5

5.3

3.6

35.0

3.9

3.3

4.0

3.3

4.3

3.4

4.4

3.4

4.6

3.5

4.9

3.5

5.2

3.6

37.8

3.9

3.3

3.9

3.3

4.2

3.4

4.3

3.4

4.5

3.5

4.9

3.5

5.2

3.6

40.0

3.8

3.3

3.9

3.3

4.1

3.4

4.3

3.4

4.5

3.5

4.8

3.5

5.1

3.6

43.3

3.8

3.3

3.8

3.2

4.1

3.3

4.2

3.3

4.4

3.5

4.8

3.5

5.1

3.6

20.0

5.0

4.1

5.2

4.1

5.5

4.2

5.7

4.2

5.9

4.4

6.3

4.3

6.6

4.4

22.8

5.0

4.1

5.1

4.1

5.4

4.2

5.6

4.2

5.8

4.4

6.2

4.3

6.6

4.4

25.0

4.9

4.1

5.1

4.0

5.4

4.2

5.5

4.1

5.8

4.3

6.2

4.3

6.5

4.4

27.8

4.9

4.1

5.0

4.0

5.3

4.2

5.5

4.1

5.7

4.3

6.1

4.3

6.5

4.4

30.0

4.8

4.0

4.9

4.0

5.2

4.1

5.4

4.1

5.6

4.3

6.1

4.2

6.4

4.3

32.8

4.8

4.0

4.9

4.0

5.2

4.1

5.4

4.1

5.6

4.3

6.0

4.2

6.3

4.3

35.0

4.7

4.0

4.8

3.9

5.1

4.1

5.3

4.1

5.5

4.2

6.0

4.2

6.3

4.3

37.8

4.7

4.0

4.7

3.9

5.1

4.1

5.2

4.0

5.5

4.2

5.9

4.2

6.2

4.3

40.0

4.6

3.9

4.7

3.9

5.0

4.0

5.2

4.0

5.4

4.2

5.8

4.2

6.2

4.3

43.3

4.5

3.9

4.6

3.9

4.9

4.0

5.1

4.0

5.3

4.2

5.8

4.1

6.1

4.2

20.0

6.6

5.1

6.8

5.0

7.2

5.2

7.5

5.1

7.8

5.3

8.3

5.3

8.8

5.4

22.8

6.5

5.0

6.7

5.0

7.1

5.1

7.4

5.1

7.7

5.3

8.3

5.2

8.7

5.3

25.0

6.5

5.0

6.7

5.0

7.1

5.1

7.3

5.1

7.6

5.3

8.2

5.2

8.6

5.3

27.8

6.4

5.0

6.6

4.9

7.0

5.1

7.2

5.0

7.5

5.2

8.1

5.2

8.5

5.3

30.0

6.3

4.9

6.5

4.9

6.9

5.0

7.2

5.0

7.5

5.2

8.0

5.2

8.5

5.3

32.8

6.3

4.9

6.4

4.8

6.8

5.0

7.1

5.0

7.4

5.2

7.9

5.1

8.4

5.2

35.0

6.2

4.9

6.4

4.8

6.8

5.0

7.0

4.9

7.3

5.1

7.9

5.1

8.3

5.2

37.8

6.1

4.8

6.3

4.8

6.7

4.9

6.9

4.9

7.2

5.1

7.8

5.1

8.2

5.2

40.0

6.1

4.8

6.2

4.7

6.6

4.9

6.8

4.9

7.1

5.1

7.7

5.0

8.2

5.2

43.3

6.0

4.8

6.1

4.7

6.5

4.9

6.7

4.8

7.0

5.0

7.6

5.0

8.1

5.1

20.0

8.3

6.1

8.6

6.0

9.1

6.2

9.4

6.1

9.8

6.4

10.5

6.3

11.0

6.4

22.8

8.2

6.0

8.5

6.0

9.0

6.1

9.3

6.1

9.7

6.3

10.4

6.3

10.9

6.3

25.0

8.1

6.0

8.4

5.9

8.9

6.1

9.2

6.0

9.6

6.3

10.3

6.2

10.8

6.3

27.8

8.1

5.9

8.3

5.9

8.8

6.1

9.1

6.0

9.5

6.2

10.2

6.2

10.7

6.3

30.0

8.0

5.9

8.2

5.8

8.7

6.0

9.0

5.9

9.4

6.2

10.1

6.1

10.6

6.2

32.8

7.9

5.9

8.1

5.8

8.6

6.0

8.9

5.9

9.3

6.1

10.0

6.1

10.5

6.2

35.0

7.8

5.8

8.0

5.7

8.5

5.9

8.8

5.9

9.2

6.1

9.9

6.1

10.4

6.2

37.8

7.7

5.8

7.9

5.7

8.4

5.9

8.7

5.8

9.1

6.1

9.8

6.0

10.3

6.1

40.0

7.6

5.7

7.8

5.7

8.3

5.8

8.6

5.8

9.0

6.0

9.7

6.0

10.3

6.1

43.3

7.5

5.7

7.7

5.6

8.2

5.8

8.5

5.7

8.8

6.0

9.6

5.9

10.1

6.1

20.0

10.0

7.7

10.3

7.7

11.0

7.9

11.3

7.8

11.8

8.2

12.6

8.1

13.3

8.2

22.8

9.9

7.7

10.2

7.6

10.8

7.9

11.2

7.8

11.6

8.1

12.5

8.0

13.1

8.2

25.0

9.8

7.6

10.1

7.6

10.7

7.8

11.1

7.7

11.5

8.1

12.4

8.0

13.0

8.2

27.8

9.7

7.6

10.0

7.5

10.6

7.8

10.9

7.7

11.4

8.0

12.3

7.9

12.9

8.1

30.0

9.6

7.6

9.9

7.5

10.5

7.7

10.8

7.6

11.3

8.0

12.2

7.9

12.8

8.1

32.8

9.5

7.5

9.7

7.4

10.3

7.7

10.7

7.6

11.2

7.9

12.0

7.9

12.7

8.0

35.0

9.4

7.5

9.6

7.4

10.2

7.6

10.6

7.5

11.1

7.9

11.9

7.8

12.6

8.0

37.8

9.3

7.4

9.5

7.3

10.1

7.6

10.5

7.5

10.9

7.8

11.8

7.8

12.4

7.9

40.0

9.2

7.4

9.4

7.3

10.0

7.5

10.4

7.5

10.8

7.8

11.7

7.7

12.3

7.9

43.3

9.1

7.3

9.2

7.2

9.8

7.4

10.2

7.4

10.7

7.7

11.5

7.7

12.2

7.9

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-93

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PCFY-P-NGMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

4.2

3.2

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

3.3

22.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.2

4.8

3.3

5.2

3.3

5.5

3.3

SHC

25.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.8

3.3

5.1

3.2

5.4

3.3

27.8

4.0

3.1

4.1

3.1

4.4

3.2

4.5

3.1

4.7

3.3

5.1

3.2

5.4

3.3

30.0

4.0

3.1

4.1

3.0

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.3

3.3

32.8

3.9

3.1

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

5.0

3.2

5.3

3.3

35.0

3.9

3.0

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

4.9

3.2

5.2

3.2

37.8

3.9

3.0

3.9

3.0

4.2

3.1

4.3

3.0

4.5

3.2

4.9

3.2

5.2

3.2

40.0

3.8

3.0

3.9

3.0

4.1

3.1

4.3

3.0

4.5

3.2

4.8

3.1

5.1

3.2

43.3

3.8

3.0

3.8

2.9

4.1

3.0

4.2

3.0

4.4

3.1

4.8

3.1

5.1

3.2

20.0

6.6

4.9

6.8

4.9

7.2

5.0

7.5

4.9

7.8

5.1

8.3

5.1

8.8

5.2

22.8

6.5

4.9

6.7

4.8

7.1

5.0

7.4

4.9

7.7

5.1

8.3

5.1

8.7

5.1

25.0

6.5

4.8

6.7

4.8

7.1

4.9

7.3

4.9

7.6

5.1

8.2

5.0

8.6

5.1

27.8

6.4

4.8

6.6

4.8

7.0

4.9

7.2

4.8

7.5

5.0

8.1

5.0

8.5

5.1

30.0

6.3

4.8

6.5

4.7

6.9

4.9

7.2

4.8

7.5

5.0

8.0

5.0

8.5

5.1
5.0

32.8

6.3

4.7

6.4

4.7

6.8

4.8

7.1

4.8

7.4

5.0

7.9

4.9

8.4

35.0

6.2

4.7

6.4

4.6

6.8

4.8

7.0

4.7

7.3

4.9

7.9

4.9

8.3

5.0

37.8

6.1

4.7

6.3

4.6

6.7

4.7

6.9

4.7

7.2

4.9

7.8

4.9

8.2

5.0

40.0

6.1

4.6

6.2

4.6

6.6

4.7

6.8

4.7

7.1

4.9

7.7

4.8

8.2

4.9

43.3

6.0

4.6

6.1

4.5

6.5

4.7

6.7

4.6

7.0

4.8

7.6

4.8

8.1

4.9

20.0

8.3

6.0

8.6

6.0

9.1

6.1

9.4

6.1

9.8

6.3

10.5

6.2

11.0

6.3

22.8

8.2

6.0

8.5

5.9

9.0

6.1

9.3

6.0

9.7

6.2

10.4

6.2

10.9

6.3

25.0

8.1

5.9

8.4

5.9

8.9

6.0

9.2

6.0

9.6

6.2

10.3

6.1

10.8

6.2

27.8

8.1

5.9

8.3

5.8

8.8

6.0

9.1

5.9

9.5

6.2

10.2

6.1

10.7

6.2

30.0

8.0

5.8

8.2

5.8

8.7

5.9

9.0

5.9

9.4

6.1

10.1

6.1

10.6

6.2

32.8

7.9

5.8

8.1

5.7

8.6

5.9

8.9

5.8

9.3

6.1

10.0

6.0

10.5

6.1

35.0

7.8

5.7

8.0

5.7

8.5

5.9

8.8

5.8

9.2

6.0

9.9

6.0

10.4

6.1

37.8

7.7

5.7

7.9

5.6

8.4

5.8

8.7

5.7

9.1

6.0

9.8

5.9

10.3

6.1

40.0

7.6

5.7

7.8

5.6

8.3

5.8

8.6

5.7

9.0

5.9

9.7

5.9

10.3

6.0

43.3

7.5

5.6

7.7

5.5

8.2

5.7

8.5

5.6

8.8

5.9

9.6

5.9

10.1

6.0

20.0

10.0

7.4

10.3

7.4

11.0

7.6

11.3

7.5

11.8

7.8

12.6

7.7

13.3

7.9

22.8

9.9

7.4

10.2

7.3

10.8

7.5

11.2

7.5

11.6

7.8

12.5

7.7

13.1

7.8

25.0

9.8

7.3

10.1

7.3

10.7

7.5

11.1

7.4

11.5

7.7

12.4

7.6

13.0

7.8

27.8

9.7

7.3

10.0

7.2

10.6

7.4

10.9

7.3

11.4

7.7

12.3

7.6

12.9

7.7

30.0

9.6

7.2

9.9

7.2

10.5

7.4

10.8

7.3

11.3

7.6

12.2

7.5

12.8

7.7

32.8

9.5

7.2

9.7

7.1

10.3

7.3

10.7

7.2

11.2

7.6

12.0

7.5

12.7

7.6

35.0

9.4

7.1

9.6

7.1

10.2

7.3

10.6

7.2

11.1

7.5

11.9

7.4

12.6

7.6

37.8

9.3

7.1

9.5

7.0

10.1

7.2

10.5

7.1

10.9

7.5

11.8

7.4

12.4

7.5

40.0

9.2

7.0

9.4

6.9

10.0

7.2

10.4

7.1

10.8

7.4

11.7

7.4

12.3

7.5

43.3

9.1

7.0

9.2

6.9

9.8

7.1

10.2

7.0

10.7

7.3

11.5

7.3

12.2

7.5

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-94

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.2

1.4

25.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.2

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.1

1.3

2.2

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.1

1.3

2.2

1.4

32.8

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.2

1.4

35.0

1.6

1.3

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.6

1.3

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

40.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

43.3

1.5

1.2

1.6

1.2

1.7

1.3

1.7

1.2

1.8

1.3

2.0

1.3

2.1

1.3

20.0

2.2

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.6

1.7

2.7

1.7

2.9

1.7

22.8

2.2

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.7

1.7

2.9

1.7

25.0

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.6

2.5

1.7

2.7

1.7

2.8

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

2.7

1.7

2.8

1.7

30.0

2.1

1.6

2.1

1.6

2.3

1.6

2.4

1.6

2.4

1.7

2.6

1.7

2.8

1.7

32.8

2.1

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.7

2.8

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.7

2.7

1.7

37.8

2.0

1.6

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.6

2.7

1.7

40.0

2.0

1.6

2.0

1.5

2.2

1.6

2.2

1.6

2.3

1.6

2.5

1.6

2.7

1.7

43.3

2.0

1.5

2.0

1.5

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.6

2.6

1.7

20.0

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.7

3.9

2.8

4.2

2.8

4.4

2.8

22.8

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.7

3.8

2.8

4.1

2.8

4.3

2.8

25.0

3.2

2.6

3.3

2.6

3.5

2.7

3.7

2.7

3.8

2.8

4.1

2.7

4.3

2.8

27.8

3.2

2.6

3.3

2.6

3.5

2.7

3.6

2.6

3.8

2.7

4.0

2.7

4.3

2.8

30.0

3.2

2.6

3.3

2.6

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.7

4.2

2.8

32.8

3.1

2.6

3.2

2.5

3.4

2.6

3.5

2.6

3.7

2.7

4.0

2.7

4.2

2.8

35.0

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.6

3.7

2.7

3.9

2.7

4.2

2.7

37.8

3.1

2.5

3.1

2.5

3.3

2.6

3.5

2.6

3.6

2.7

3.9

2.7

4.1

2.7

40.0

3.0

2.5

3.1

2.5

3.3

2.6

3.4

2.6

3.6

2.7

3.9

2.7

4.1

2.7

43.3

3.0

2.5

3.1

2.5

3.2

2.6

3.4

2.5

3.5

2.7

3.8

2.6

4.0

2.7

20.0

4.2

3.2

4.3

3.2

4.5

3.3

4.7

3.2

4.9

3.4

5.2

3.3

5.5

3.4

22.8

4.1

3.2

4.2

3.1

4.5

3.2

4.6

3.2

4.8

3.3

5.2

3.3

5.5

3.4

25.0

4.1

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.8

3.3

5.1

3.3

5.4

3.3

27.8

4.0

3.1

4.1

3.1

4.4

3.2

4.5

3.2

4.7

3.3

5.1

3.3

5.4

3.3

30.0

4.0

3.1

4.1

3.1

4.3

3.2

4.5

3.1

4.7

3.3

5.0

3.2

5.3

3.3

32.8

3.9

3.1

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

5.0

3.2

5.3

3.3

35.0

3.9

3.1

4.0

3.0

4.3

3.1

4.4

3.1

4.6

3.2

4.9

3.2

5.2

3.3

37.8

3.9

3.0

3.9

3.0

4.2

3.1

4.3

3.1

4.5

3.2

4.9

3.2

5.2

3.3

40.0

3.8

3.0

3.9

3.0

4.1

3.1

4.3

3.1

4.5

3.2

4.8

3.2

5.1

3.2

43.3

3.8

3.0

3.8

2.9

4.1

3.0

4.2

3.0

4.4

3.2

4.8

3.1

5.1

3.2

20.0

5.0

4.0

5.2

4.0

5.5

4.1

5.7

4.1

5.9

4.3

6.3

4.2

6.6

4.3

22.8

5.0

4.0

5.1

4.0

5.4

4.1

5.6

4.1

5.8

4.2

6.2

4.2

6.6

4.3

25.0

4.9

4.0

5.1

4.0

5.4

4.1

5.5

4.1

5.8

4.2

6.2

4.2

6.5

4.3

27.8

4.9

4.0

5.0

3.9

5.3

4.1

5.5

4.0

5.7

4.2

6.1

4.2

6.5

4.3

30.0

4.8

3.9

4.9

3.9

5.2

4.0

5.4

4.0

5.6

4.2

6.1

4.1

6.4

4.2

32.8

4.8

3.9

4.9

3.9

5.2

4.0

5.4

4.0

5.6

4.2

6.0

4.1

6.3

4.2

35.0

4.7

3.9

4.8

3.9

5.1

4.0

5.3

4.0

5.5

4.1

6.0

4.1

6.3

4.2

37.8

4.7

3.9

4.7

3.8

5.1

4.0

5.2

3.9

5.5

4.1

5.9

4.1

6.2

4.2
4.2

40.0

4.6

3.8

4.7

3.8

5.0

3.9

5.2

3.9

5.4

4.1

5.8

4.1

6.2

43.3

4.5

3.8

4.6

3.8

4.9

3.9

5.1

3.9

5.3

4.1

5.8

4.0

6.1

4.1

20.0

6.6

5.0

6.8

5.0

7.2

5.1

7.5

5.1

7.8

5.3

8.3

5.2

8.8

5.3

22.8

6.5

5.0

6.7

4.9

7.1

5.1

7.4

5.0

7.7

5.2

8.3

5.2

8.7

5.3

25.0

6.5

4.9

6.7

4.9

7.1

5.1

7.3

5.0

7.6

5.2

8.2

5.2

8.6

5.2

27.8

6.4

4.9

6.6

4.9

7.0

5.0

7.2

5.0

7.5

5.2

8.1

5.1

8.5

5.2

30.0

6.3

4.9

6.5

4.8

6.9

5.0

7.2

4.9

7.5

5.1

8.0

5.1

8.5

5.2

32.8

6.3

4.8

6.4

4.8

6.8

4.9

7.1

4.9

7.4

5.1

7.9

5.1

8.4

5.2

35.0

6.2

4.8

6.4

4.8

6.8

4.9

7.0

4.9

7.3

5.1

7.9

5.0

8.3

5.1

37.8

6.1

4.8

6.3

4.7

6.7

4.9

6.9

4.8

7.2

5.0

7.8

5.0

8.2

5.1

40.0

6.1

4.7

6.2

4.7

6.6

4.8

6.8

4.8

7.1

5.0

7.7

5.0

8.2

5.1

43.3

6.0

4.7

6.1

4.6

6.5

4.8

6.7

4.8

7.0

5.0

7.6

4.9

8.1

5.0

20.0

8.3

6.7

8.6

6.7

9.1

6.9

9.4

6.8

9.8

7.1

10.5

7.1

11.0

7.2

22.8

8.2

6.7

8.5

6.6

9.0

6.9

9.3

6.8

9.7

7.1

10.4

7.0

10.9

7.2

25.0

8.1

6.7

8.4

6.6

8.9

6.8

9.2

6.8

9.6

7.1

10.3

7.0

10.8

7.1

27.8

8.1

6.6

8.3

6.6

8.8

6.8

9.1

6.7

9.5

7.0

10.2

6.9

10.7

7.1

30.0

8.0

6.6

8.2

6.5

8.7

6.7

9.0

6.7

9.4

7.0

10.1

6.9

10.6

7.1

32.8

7.9

6.5

8.1

6.5

8.6

6.7

8.9

6.6

9.3

6.9

10.0

6.9

10.5

7.0

35.0

7.8

6.5

8.0

6.4

8.5

6.7

8.8

6.6

9.2

6.9

9.9

6.8

10.4

7.0

37.8

7.7

6.5

7.9

6.4

8.4

6.6

8.7

6.6

9.1

6.9

9.8

6.8

10.3

7.0

40.0

7.6

6.4

7.8

6.3

8.3

6.6

8.6

6.5

9.0

6.8

9.7

6.8

10.3

6.9

43.3

7.5

6.4

7.7

6.3

8.2

6.5

8.5

6.5

8.8

6.8

9.6

6.7

10.1

6.9

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-95

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-1. Cooling CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.0

1.4

2.1

1.3

2.3

SHC
1.4

22.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.2

1.4

25.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.2

1.3

27.8

1.6

1.3

1.7

1.2

1.8

1.3

1.9

1.3

1.9

1.3

2.1

1.3

2.2

1.3

30.0

1.6

1.3

1.7

1.2

1.8

1.3

1.8

1.3

1.9

1.3

2.1

1.3

2.2

1.3

32.8

1.6

1.2

1.7

1.2

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.2

1.3

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.2

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.9

1.3

2.0

1.3

2.1

1.3

40.0

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.8

1.3

2.0

1.3

2.1

1.3

43.3

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.8

1.3

2.0

1.3

2.1

1.3

20.0

2.2

1.7

2.2

1.7

2.4

1.7

2.5

1.7

2.6

1.8

2.7

1.7

2.9

1.8

22.8

2.2

1.7

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.8

2.7

1.7

2.9

1.8

25.0

2.1

1.7

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.7

1.7

2.8

1.8

27.8

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.7

1.7

2.8

1.7

30.0

2.1

1.6

2.1

1.6

2.3

1.7

2.4

1.6

2.4

1.7

2.6

1.7

2.8

1.7

32.8

2.1

1.6

2.1

1.6

2.2

1.7

2.3

1.6

2.4

1.7

2.6

1.7

2.8

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.7

2.7

1.7

37.8

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.7

2.7

1.7

40.0

2.0

1.6

2.0

1.6

2.2

1.6

2.2

1.6

2.3

1.7

2.5

1.7

2.7

1.7

43.3

2.0

1.6

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.7

2.5

1.7

2.6

1.7

20.0

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.3

3.9

2.4

4.2

2.4

4.4

2.4

22.8

3.3

2.3

3.4

2.3

3.6

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.3

2.4

25.0

3.2

2.3

3.3

2.3

3.5

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.3

2.4

27.8

3.2

2.3

3.3

2.2

3.5

2.3

3.6

2.3

3.8

2.4

4.0

2.3

4.3

2.4

30.0

3.2

2.2

3.3

2.2

3.5

2.3

3.6

2.2

3.7

2.3

4.0

2.3

4.2

2.4

32.8

3.1

2.2

3.2

2.2

3.4

2.3

3.5

2.2

3.7

2.3

4.0

2.3

4.2

2.3

35.0

3.1

2.2

3.2

2.2

3.4

2.2

3.5

2.2

3.7

2.3

3.9

2.3

4.2

2.3

37.8

3.1

2.2

3.1

2.2

3.3

2.2

3.5

2.2

3.6

2.3

3.9

2.3

4.1

2.3

40.0

3.0

2.2

3.1

2.1

3.3

2.2

3.4

2.2

3.6

2.3

3.9

2.3

4.1

2.3

43.3

3.0

2.1

3.1

2.1

3.2

2.2

3.4

2.1

3.5

2.2

3.8

2.2

4.0

2.3

20.0

4.2

2.9

4.3

2.9

4.5

3.0

4.7

3.0

4.9

3.1

5.2

3.0

5.5

3.1

22.8

4.1

2.9

4.2

2.9

4.5

3.0

4.6

2.9

4.8

3.0

5.2

3.0

5.5

3.1

25.0

4.1

2.9

4.2

2.9

4.4

3.0

4.6

2.9

4.8

3.0

5.1

3.0

5.4

3.0

27.8

4.0

2.9

4.1

2.8

4.4

2.9

4.5

2.9

4.7

3.0

5.1

3.0

5.4

3.0

30.0

4.0

2.9

4.1

2.8

4.3

2.9

4.5

2.9

4.7

3.0

5.0

3.0

5.3

3.0

32.8

3.9

2.8

4.0

2.8

4.3

2.9

4.4

2.8

4.6

3.0

5.0

2.9

5.3

3.0

35.0

3.9

2.8

4.0

2.8

4.3

2.9

4.4

2.8

4.6

2.9

4.9

2.9

5.2

3.0

37.8

3.9

2.8

3.9

2.7

4.2

2.8

4.3

2.8

4.5

2.9

4.9

2.9

5.2

2.9

40.0

3.8

2.8

3.9

2.7

4.1

2.8

4.3

2.8

4.5

2.9

4.8

2.9

5.1

2.9

43.3

3.8

2.7

3.8

2.7

4.1

2.8

4.2

2.7

4.4

2.9

4.8

2.9

5.1

2.9

20.0

5.0

3.6

5.2

3.6

5.5

3.7

5.7

3.6

5.9

3.8

6.3

3.7

6.6

3.8

22.8

5.0

3.6

5.1

3.6

5.4

3.7

5.6

3.6

5.8

3.8

6.2

3.7

6.6

3.8

25.0

4.9

3.6

5.1

3.5

5.4

3.6

5.5

3.6

5.8

3.7

6.2

3.7

6.5

3.7

27.8

4.9

3.5

5.0

3.5

5.3

3.6

5.5

3.6

5.7

3.7

6.1

3.7

6.5

3.7

30.0

4.8

3.5

4.9

3.5

5.2

3.6

5.4

3.5

5.6

3.7

6.1

3.6

6.4

3.7

32.8

4.8

3.5

4.9

3.4

5.2

3.5

5.4

3.5

5.6

3.6

6.0

3.6

6.3

3.7

35.0

4.7

3.5

4.8

3.4

5.1

3.5

5.3

3.5

5.5

3.6

6.0

3.6

6.3

3.7

37.8

4.7

3.4

4.7

3.4

5.1

3.5

5.2

3.4

5.5

3.6

5.9

3.6

6.2

3.6
3.6

40.0

4.6

3.4

4.7

3.4

5.0

3.5

5.2

3.4

5.4

3.6

5.8

3.5

6.2

43.3

4.5

3.4

4.6

3.3

4.9

3.4

5.1

3.4

5.3

3.5

5.8

3.5

6.1

3.6

20.0

6.6

4.6

6.8

4.6

7.2

4.7

7.5

4.7

7.8

4.8

8.3

4.8

8.8

4.8

22.8

6.5

4.6

6.7

4.6

7.1

4.7

7.4

4.6

7.7

4.8

8.3

4.7

8.7

4.8

25.0

6.5

4.6

6.7

4.5

7.1

4.6

7.3

4.6

7.6

4.8

8.2

4.7

8.6

4.8

27.8

6.4

4.5

6.6

4.5

7.0

4.6

7.2

4.5

7.5

4.7

8.1

4.7

8.5

4.7

30.0

6.3

4.5

6.5

4.4

6.9

4.6

7.2

4.5

7.5

4.7

8.0

4.7

8.5

4.7

32.8

6.3

4.5

6.4

4.4

6.8

4.5

7.1

4.5

7.4

4.6

7.9

4.6

8.4

4.7

35.0

6.2

4.4

6.4

4.4

6.8

4.5

7.0

4.4

7.3

4.6

7.9

4.6

8.3

4.7

37.8

6.1

4.4

6.3

4.3

6.7

4.4

6.9

4.4

7.2

4.6

7.8

4.5

8.2

4.6

40.0

6.1

4.3

6.2

4.3

6.6

4.4

6.8

4.4

7.1

4.5

7.7

4.5

8.2

4.6

43.3

6.0

4.3

6.1

4.2

6.5

4.4

6.7

4.3

7.0

4.5

7.6

4.5

8.1

4.6

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-96

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-3-2. Heating CapacityPUHY-P168~240, PURY-P144~240T(S)HMU/Y(S)HMU with All Indoor Units


Model
size

06

08

12

15

18

24

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
1.2
1.2
1.2
1.2
1.5
1.4
1.4
1.4
1.7
1.6
1.6
1.5
1.9
1.8
1.7
1.5
2.0
1.9
1.7
1.5
2.1
2.0
1.7
1.5
2.2
2.0
1.7
1.5
2.3
2.0
1.7
1.5
2.4
2.0
1.7
1.5
2.4
2.0
1.7
1.5
2.4
2.0
1.7
1.5
1.6
1.6
1.5
1.5
1.9
1.8
1.8
1.8
2.2
2.1
2.0
1.9
2.4
2.3
2.2
1.9
2.6
2.5
2.2
1.9
2.8
2.6
2.2
1.9
2.9
2.6
2.2
1.9
3.0
2.6
2.2
1.9
3.1
2.6
2.2
1.9
3.1
2.6
2.2
1.9
3.1
2.6
2.2
1.9
2.5
2.4
2.4
2.3
2.9
2.8
2.8
2.7
3.3
3.2
3.2
3.0
3.8
3.6
3.3
3.0
4.0
3.8
3.3
3.0
4.3
4.0
3.3
3.0
4.4
4.0
3.3
3.0
4.6
4.0
3.3
3.0
4.8
4.0
3.3
3.0
4.8
4.0
3.3
3.0
4.8
4.0
3.3
3.0
3.1
3.0
3.0
2.9
3.6
3.5
3.5
3.4
4.2
4.0
3.9
3.7
4.7
4.5
4.1
3.7
5.0
4.8
4.1
3.7
5.3
5.0
4.1
3.7
5.6
5.0
4.1
3.7
5.8
5.0
4.1
3.7
6.0
5.0
4.1
3.7
6.0
5.0
4.1
3.7
6.0
5.0
4.1
3.7
3.7
3.6
3.5
3.5
4.3
4.1
4.1
4.0
4.9
4.7
4.6
4.4
5.6
5.3
4.9
4.4
5.9
5.6
4.9
4.4
6.3
5.9
4.9
4.4
6.6
5.9
4.9
4.4
6.8
5.9
4.9
4.4
7.1
5.9
4.9
4.4
7.1
5.9
4.9
4.4
7.1
5.9
4.9
4.4
4.9
4.8
4.7
4.6
5.8
5.5
5.5
5.4
6.6
6.3
6.2
5.8
7.4
7.1
6.5
5.8
7.9
7.5
6.5
5.8
8.4
7.9
6.5
5.8
8.8
7.9
6.5
5.8
9.1
7.9
6.5
5.8
9.5
7.9
6.5
5.8
9.5
7.9
6.5
5.8
9.5
7.9
6.5
5.8
5.5
5.3
5.2
5.2
6.4
6.2
6.1
6.0
7.3
7.0
6.9
6.5
8.3
7.9
7.3
6.5
8.8
8.4
7.3
6.5
9.4
8.8
7.3
6.5
9.8
8.8
7.3
6.5
10.2
8.8
7.3
6.5
10.6
8.8
7.3
6.5
10.6
8.8
7.3
6.5
10.6
8.8
7.3
6.5
kcal/h = kW x 860, BTU/h = kW x 3,412

Model
size

30

36

48

54

72

96

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
6.2
6.1
6.0
5.9
7.3
7.0
6.9
6.8
8.4
8.0
7.9
7.4
9.4
9.0
8.3
7.4
10.1
9.5
8.3
7.4
10.7
10.0
8.3
7.4
11.1
10.0
8.3
7.4
11.5
10.0
8.3
7.4
12.1
10.0
8.3
7.4
12.1
10.0
8.3
7.4
12.1
10.0
8.3
7.4
7.3
7.1
7.0
6.9
8.5
8.2
8.1
8.0
9.8
9.4
9.2
8.7
11.0
10.5
9.7
8.7
11.8
11.1
9.7
8.7
12.5
11.7
9.7
8.7
13.0
11.7
9.7
8.7
13.5
11.7
9.7
8.7
14.1
11.7
9.7
8.7
14.1
11.7
9.7
8.7
14.1
11.7
9.7
8.7
9.8
9.6
9.4
9.3
11.5
11.1
10.9
10.8
13.2
12.6
12.5
11.7
14.9
14.1
13.1
11.7
15.9
15.0
13.1
11.7
16.9
15.8
13.1
11.7
17.6
15.8
13.1
11.7
18.2
15.8
13.1
11.7
19.1
15.8
13.1
11.7
19.1
15.8
13.1
11.7
19.1
15.8
13.1
11.7
10.9
10.7
10.5
10.3
12.8
12.4
12.2
12.0
14.7
14.1
13.9
13.0
16.6
15.8
14.6
13.0
17.7
16.8
14.6
13.0
18.8
17.6
14.6
13.0
19.6
17.6
14.6
13.0
20.3
17.6
14.6
13.0
21.3
17.6
14.6
13.0
21.3
17.6
14.6
13.0
21.3
17.6
14.6
13.0
14.6
14.2
13.9
13.7
17.0
16.4
16.2
16.0
19.5
18.7
18.4
17.3
22.0
20.9
19.4
17.3
23.5
22.3
19.4
17.3
25.0
23.4
19.4
17.3
26.0
23.4
19.4
17.3
27.0
23.4
19.4
17.3
28.3
23.4
19.4
17.3
28.3
23.4
19.4
17.3
28.3
23.4
19.4
17.3
19.7
19.2
18.9
18.6
23.1
22.3
21.9
21.6
26.5
25.4
25.0
23.5
29.8
28.4
26.2
23.5
31.9
30.2
26.2
23.5
33.9
31.7
26.2
23.5
35.3
31.7
26.2
23.5
36.6
31.7
26.2
23.5
38.3
31.7
26.2
23.5
38.3
31.7
26.2
23.5
38.3
31.7
26.2
23.5
kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NOMINAL
CAPACITY
TABLES

27

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

NCT-97

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4. Cooing and Heating Capacity with PUHY-P264~360T(S)HMU/Y(S)HMU-A


2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PEFY-P-NMSU-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

NOMINAL
CAPACITY
TABLES

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.0

1.7

2.2

1.6

2.3

SHC
1.7

22.8

1.7

1.5

1.7

1.5

1.9

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.3

1.7

25.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

1.7

27.8

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

1.9

1.6

2.1

1.6

2.2

1.7

30.0

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.2

1.6

32.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

35.0

1.5

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

37.8

1.5

1.5

1.6

1.4

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

40.0

1.5

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

43.3

1.4

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.8

1.5

1.9

1.6

20.0

2.3

2.0

2.3

2.0

2.5

2.1

2.6

2.0

2.7

2.1

2.9

2.1

3.0

2.2

22.8

2.2

2.0

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

3.0

2.1

25.0

2.2

2.0

2.3

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

27.8

2.1

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.1

2.9

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.9

2.1

32.8

2.1

1.9

2.1

1.9

2.3

2.0

2.4

2.0

2.4

2.0

2.6

2.0

2.8

2.1

35.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.1

37.8

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.7

2.0

40.0

2.0

1.9

2.0

1.8

2.1

1.9

2.3

1.9

2.3

2.0

2.5

2.0

2.6

2.0

43.3

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.6

2.0

20.0

3.4

2.6

3.5

2.6

3.8

2.7

3.9

2.7

4.0

2.8

4.4

2.8

4.6

2.8

22.8

3.3

2.6

3.5

2.6

3.7

2.7

3.8

2.7

4.0

2.8

4.3

2.8

4.5

2.8

25.0

3.3

2.6

3.4

2.6

3.6

2.7

3.8

2.7

3.9

2.8

4.2

2.7

4.4

2.8

27.8

3.2

2.6

3.3

2.6

3.5

2.6

3.7

2.6

3.8

2.7

4.1

2.7

4.4

2.8

30.0

3.2

2.5

3.3

2.5

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.7

4.3

2.7

32.8

3.1

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.7

2.7

4.0

2.6

4.2

2.7

35.0

3.1

2.5

3.2

2.5

3.3

2.6

3.5

2.5

3.6

2.7

3.9

2.6

4.1

2.7

37.8

3.0

2.5

3.1

2.5

3.3

2.5

3.5

2.5

3.6

2.6

3.8

2.6

4.0

2.6

40.0

3.0

2.4

3.0

2.4

3.2

2.5

3.4

2.5

3.5

2.6

3.7

2.6

3.9

2.6

43.3

2.9

2.4

2.9

2.4

3.1

2.5

3.3

2.5

3.4

2.6

3.7

2.5

3.8

2.6

20.0

4.2

3.2

4.4

3.2

4.7

3.3

4.9

3.2

5.0

3.4

5.5

3.3

5.7

3.4

22.8

4.2

3.1

4.3

3.1

4.6

3.2

4.8

3.2

5.0

3.3

5.3

3.3

5.6

3.4

25.0

4.1

3.1

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

3.3

27.8

4.0

3.1

4.2

3.1

4.4

3.2

4.6

3.1

4.8

3.2

5.2

3.2

5.5

3.3

30.0

3.9

3.0

4.1

3.0

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.4

3.3

32.8

3.9

3.0

4.0

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.1

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.2

3.0

4.4

3.0

4.5

3.2

4.9

3.1

5.1

3.2

37.8

3.8

2.9

3.9

2.9

4.1

3.0

4.3

3.0

4.4

3.1

4.8

3.1

5.0

3.1

40.0

3.7

2.9

3.8

2.9

4.0

3.0

4.3

3.0

4.4

3.1

4.7

3.0

4.9

3.1

43.3

3.6

2.9

3.7

2.8

3.9

2.9

4.1

2.9

4.2

3.0

4.6

3.0

4.8

3.1

20.0

5.1

3.9

5.3

3.9

5.6

4.0

5.9

4.0

6.0

4.2

6.6

4.1

6.8

4.2

22.8

5.0

3.9

5.2

3.9

5.5

4.0

5.7

4.0

6.0

4.1

6.4

4.1

6.7

4.2

25.0

4.9

3.8

5.1

3.8

5.4

4.0

5.7

3.9

5.9

4.1

6.3

4.0

6.6

4.1

27.8

4.8

3.8

5.0

3.8

5.3

3.9

5.5

3.9

5.7

4.0

6.2

4.0

6.6

4.1

30.0

4.7

3.7

4.9

3.7

5.2

3.9

5.4

3.8

5.6

4.0

6.1

3.9

6.4

4.0

32.8

4.7

3.7

4.8

3.7

5.2

3.8

5.4

3.8

5.5

3.9

5.9

3.9

6.3

4.0

35.0

4.6

3.7

4.8

3.7

5.0

3.8

5.3

3.8

5.5

3.9

5.8

3.9

6.2

3.9

37.8

4.5

3.6

4.7

3.6

5.0

3.7

5.2

3.7

5.3

3.9

5.7

3.8

6.0

3.9
3.9

40.0

4.5

3.6

4.6

3.6

4.8

3.7

5.1

3.7

5.3

3.8

5.6

3.8

5.9

43.3

4.3

3.5

4.4

3.5

4.7

3.6

5.0

3.6

5.1

3.8

5.5

3.7

5.8

3.8

20.0

6.8

5.2

7.0

5.1

7.5

5.3

7.8

5.3

8.0

5.5

8.7

5.5

9.1

5.5

22.8

6.6

5.1

6.9

5.1

7.3

5.3

7.6

5.2

7.9

5.4

8.5

5.4

8.9

5.5

25.0

6.6

5.1

6.8

5.0

7.2

5.2

7.5

5.2

7.8

5.4

8.3

5.3

8.8

5.4

27.8

6.4

5.0

6.7

5.0

7.1

5.1

7.4

5.1

7.6

5.3

8.2

5.3

8.8

5.4

30.0

6.3

4.9

6.6

4.9

6.9

5.1

7.2

5.0

7.5

5.2

8.1

5.2

8.6

5.3

32.8

6.2

4.9

6.4

4.9

6.9

5.0

7.1

5.0

7.3

5.2

7.9

5.1

8.4

5.3

35.0

6.1

4.8

6.3

4.8

6.7

5.0

7.0

5.0

7.3

5.2

7.7

5.1

8.2

5.2

37.8

6.0

4.8

6.2

4.8

6.6

4.9

6.9

4.9

7.1

5.1

7.6

5.0

8.0

5.1

40.0

5.9

4.8

6.1

4.7

6.4

4.8

6.8

4.9

7.0

5.0

7.5

5.0

7.9

5.1

43.3

5.7

4.7

5.9

4.6

6.2

4.8

6.6

4.8

6.8

5.0

7.3

4.9

7.7

5.0

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-98

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

4.2

2.9

4.4

2.9

4.7

3.0

4.9

3.0

5.0

3.1

5.5

3.1

5.7

SHC
3.1

22.8

4.2

2.9

4.3

2.9

4.6

2.9

4.8

2.9

5.0

3.0

5.3

3.0

5.6

3.0

25.0

4.1

2.8

4.3

2.8

4.5

2.9

4.7

2.9

4.9

3.0

5.2

2.9

5.5

3.0

27.8

4.0

2.8

4.2

2.8

4.4

2.9

4.6

2.8

4.8

2.9

5.2

2.9

5.5

3.0

30.0

3.9

2.7

4.1

2.7

4.3

2.8

4.5

2.8

4.7

2.9

5.0

2.9

5.4

2.9

32.8

3.9

2.7

4.0

2.7

4.3

2.8

4.5

2.8

4.6

2.8

4.9

2.8

5.2

2.9

35.0

3.8

2.7

4.0

2.7

4.2

2.7

4.4

2.7

4.5

2.8

4.9

2.8

5.1

2.8

37.8

3.8

2.6

3.9

2.6

4.1

2.7

4.3

2.7

4.4

2.8

4.8

2.7

5.0

2.8

40.0

3.7

2.6

3.8

2.6

4.0

2.6

4.3

2.7

4.4

2.7

4.7

2.7

4.9

2.7

43.3

3.6

2.5

3.7

2.5

3.9

2.6

4.1

2.6

4.2

2.7

4.6

2.7

4.8

2.7

20.0

5.1

3.5

5.3

3.5

5.7

3.6

5.9

3.6

6.1

3.7

6.6

3.7

6.9

3.7

22.8

5.0

3.5

5.2

3.5

5.5

3.6

5.8

3.5

6.0

3.7

6.4

3.7

6.8

3.7

25.0

5.0

3.5

5.1

3.4

5.5

3.5

5.7

3.5

5.9

3.6

6.3

3.6

6.7

3.6

27.8

4.9

3.4

5.0

3.4

5.3

3.5

5.6

3.4

5.8

3.6

6.2

3.6

6.7

3.7

30.0

4.8

3.3

5.0

3.4

5.2

3.4

5.4

3.4

5.6

3.5

6.1

3.5

6.5

3.6

32.8

4.7

3.3

4.8

3.3

5.2

3.4

5.4

3.4

5.5

3.5

6.0

3.4

6.3

3.5

35.0

4.6

3.3

4.8

3.3

5.0

3.3

5.3

3.3

5.5

3.4

5.9

3.4

6.2

3.5

37.8

4.5

3.2

4.7

3.2

5.0

3.3

5.2

3.3

5.4

3.4

5.8

3.4

6.1

3.4

40.0

4.5

3.2

4.6

3.2

4.8

3.2

5.1

3.2

5.3

3.4

5.6

3.3

5.9

3.4

43.3

4.3

3.1

4.4

3.1

4.7

3.2

5.0

3.2

5.1

3.3

5.5

3.3

5.8

3.3

20.0

6.8

4.7

7.0

4.7

7.5

4.8

7.8

4.7

8.0

4.9

8.7

4.9

9.1

4.9

22.8

6.6

4.6

6.9

4.6

7.3

4.7

7.6

4.7

7.9

4.8

8.5

4.8

8.9

4.8

25.0

6.6

4.5

6.8

4.5

7.2

4.7

7.5

4.6

7.8

4.8

8.3

4.7

8.8

4.8

27.8

6.4

4.5

6.7

4.5

7.1

4.6

7.3

4.5

7.6

4.7

8.2

4.7

8.8

4.8

30.0

6.3

4.4

6.6

4.4

6.9

4.5

7.2

4.5

7.5

4.6

8.0

4.6

8.5

4.7

32.8

6.2

4.3

6.4

4.3

6.8

4.5

7.1

4.4

7.3

4.5

7.9

4.5

8.3

4.6

35.0

6.1

4.3

6.3

4.3

6.7

4.4

7.0

4.4

7.2

4.5

7.7

4.5

8.2

4.5

37.8

6.0

4.2

6.2

4.2

6.6

4.3

6.9

4.3

7.1

4.4

7.6

4.4

8.0

4.5

40.0

5.9

4.2

6.0

4.1

6.4

4.2

6.8

4.3

7.0

4.4

7.4

4.3

7.8

4.4

43.3

5.7

4.1

5.9

4.0

6.2

4.2

6.6

4.2

6.8

4.3

7.3

4.3

7.6

4.3

20.0

7.6

5.3

7.9

5.3

8.4

5.5

8.8

5.4

9.0

5.6

9.8

5.6

10.2

5.6

22.8

7.5

5.2

7.8

5.2

8.3

5.4

8.6

5.3

8.9

5.5

9.6

5.5

10.1

5.5

25.0

7.4

5.2

7.6

5.2

8.1

5.3

8.5

5.3

8.8

5.5

9.4

5.4

9.9

5.5

27.8

7.2

5.1

7.5

5.1

8.0

5.2

8.3

5.2

8.6

5.4

9.3

5.3

9.9

5.5

30.0

7.1

5.0

7.4

5.0

7.8

5.2

8.1

5.1

8.4

5.3

9.1

5.3

9.6

5.4

32.8

7.0

5.0

7.2

5.0

7.7

5.1

8.0

5.1

8.2

5.2

8.9

5.2

9.4

5.3

35.0

6.9

4.9

7.1

4.9

7.5

5.0

7.9

5.0

8.2

5.2

8.7

5.1

9.2

5.2

37.8

6.7

4.8

7.0

4.9

7.4

5.0

7.8

4.9

8.0

5.1

8.6

5.1

9.0

5.1

40.0

6.7

4.8

6.8

4.7

7.2

4.9

7.6

4.9

7.9

5.1

8.4

5.0

8.8

5.1

43.3

6.5

4.7

6.6

4.6

7.0

4.8

7.4

4.8

7.6

4.9

8.2

4.9

8.6

5.0

20.0

8.5

5.9

8.8

5.9

9.4

6.1

9.8

6.0

10.1

6.2

10.9

6.2

11.4

6.2

22.8

8.3

5.8

8.7

5.8

9.2

6.0

9.6

5.9

9.9

6.1

10.7

6.1

11.2

6.2

25.0

8.2

5.8

8.5

5.8

9.1

5.9

9.4

5.9

9.8

6.1

10.5

6.0

11.0

6.1

27.8

8.1

5.7

8.4

5.7

8.9

5.8

9.2

5.8

9.5

6.0

10.3

5.9

11.1

6.1

30.0

7.9

5.6

8.2

5.6

8.7

5.7

9.0

5.7

9.4

5.9

10.1

5.8

10.7

6.0

32.8

7.8

5.5

8.0

5.5

8.6

5.7

8.9

5.6

9.2

5.8

9.9

5.8

10.5

5.9

35.0

7.6

5.5

8.0

5.5

8.4

5.6

8.8

5.6

9.1

5.8

9.7

5.7

10.3

5.8

37.8

7.5

5.4

7.8

5.4

8.3

5.5

8.7

5.5

8.9

5.7

9.6

5.6

10.1

5.7

40.0

7.4

5.3

7.6

5.3

8.0

5.4

8.5

5.4

8.8

5.6

9.3

5.5

9.9

5.6

43.3

7.2

5.2

7.4

5.2

7.8

5.3

8.3

5.3

8.5

5.5

9.2

5.5

9.6

5.5

20.0

10.2

7.3

10.6

7.3

11.3

7.5

11.8

7.4

12.1

7.7

13.2

7.7

13.7

7.7

22.8

10.0

7.2

10.4

7.2

11.1

7.4

11.5

7.3

11.9

7.6

12.9

7.5

13.5

7.6

25.0

9.9

7.1

10.3

7.1

10.9

7.3

11.4

7.2

11.7

7.5

12.6

7.4

13.3

7.5

27.8

9.7

7.0

10.1

7.0

10.7

7.2

11.1

7.1

11.5

7.4

12.4

7.3

13.3

7.6

30.0

9.5

6.9

9.9

6.9

10.5

7.1

10.9

7.0

11.3

7.3

12.2

7.2

12.9

7.4

32.8

9.3

6.8

9.7

6.8

10.3

7.0

10.8

7.0

11.0

7.2

11.9

7.1

12.6

7.3

35.0

9.2

6.8

9.6

6.8

10.1

6.9

10.6

6.9

10.9

7.1

11.7

7.1

12.4

7.2

37.8

9.0

6.7

9.4

6.7

9.9

6.8

10.4

6.8

10.7

7.0

11.5

7.0

12.1

7.1

40.0

8.9

6.6

9.1

6.5

9.7

6.7

10.3

6.7

10.5

7.0

11.3

6.9

11.9

7.0

43.3

8.7

6.5

8.9

6.4

9.4

6.6

9.9

6.6

10.2

6.8

11.0

6.8

11.6

6.9

20.0

13.6

9.4

14.1

9.3

15.1

9.6

15.7

9.5

16.1

9.8

17.5

9.8

18.3

9.9

22.8

13.3

9.2

13.9

9.2

14.7

9.5

15.3

9.4

15.9

9.7

17.1

9.6

18.0

9.7

25.0

13.2

9.1

13.6

9.1

14.5

9.3

15.1

9.2

15.6

9.6

16.8

9.5

17.7

9.6

27.8

12.9

9.0

13.4

9.0

14.2

9.2

14.8

9.1

15.3

9.4

16.5

9.4

17.7

9.6

30.0

12.6

8.8

13.2

8.8

13.9

9.0

14.5

9.0

15.0

9.3

16.2

9.2

17.2

9.4

32.8

12.4

8.7

12.9

8.7

13.8

9.0

14.3

8.9

14.7

9.1

15.8

9.1

16.8

9.2

35.0

12.2

8.6

12.7

8.6

13.4

8.8

14.1

8.8

14.6

9.1

15.6

8.9

16.4

9.1

37.8

12.0

8.5

12.5

8.5

13.2

8.7

13.9

8.6

14.2

8.9

15.3

8.8

16.1

9.0

40.0

11.9

8.4

12.2

8.3

12.9

8.5

13.6

8.5

14.0

8.8

15.0

8.7

15.8

8.8

43.3

11.5

8.2

11.8

8.1

12.5

8.3

13.2

8.4

13.6

8.6

14.7

8.6

15.4

8.7

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-99

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

54

72

96

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

15.2

10.8

15.8

10.8

16.9

11.1

17.5

11.0

18.1

11.3

19.6

11.3

20.5

11.4

22.8

14.9

10.6

15.5

10.6

16.5

10.9

17.2

10.8

17.8

11.2

19.2

11.1

20.1

11.3

25.0

14.8

10.5

15.3

10.5

16.3

10.8

16.9

10.7

17.5

11.1

18.8

11.0

19.8

11.1

27.8

14.5

10.4

15.0

10.4

15.9

10.6

16.6

10.5

17.1

10.9

18.5

10.8

19.9

11.2

30.0

14.2

10.2

14.8

10.2

15.6

10.5

16.2

10.4

16.8

10.8

18.1

10.7

19.2

10.9

32.8

13.9

10.1

14.4

10.1

15.4

10.4

16.0

10.3

16.5

10.6

17.8

10.5

18.8

10.7

35.0

13.7

10.0

14.3

10.0

15.0

10.2

15.8

10.2

16.3

10.5

17.4

10.4

18.4

10.6

37.8

13.5

9.8

14.0

9.9

14.8

10.1

15.5

10.1

16.0

10.4

17.2

10.3

18.1

10.5

40.0

13.3

9.8

13.6

9.6

14.4

9.9

15.3

10.0

15.7

10.3

16.8

10.1

17.7

10.3

43.3

12.9

9.6

13.2

9.5

14.0

9.7

14.8

9.7

15.3

10.1

16.5

10.0

17.2

10.1

20.0

20.4

14.2

21.1

14.2

22.6

14.6

23.4

14.4

24.2

14.9

26.2

14.9

27.4

15.0

22.8

19.9

14.0

20.7

14.0

22.1

14.4

23.0

14.2

23.8

14.7

25.6

14.6

26.9

14.8

25.0

19.7

13.8

20.4

13.8

21.8

14.2

22.6

14.0

23.4

14.5

25.1

14.4

26.5

14.6

27.8

19.3

13.6

20.1

13.6

21.3

14.0

22.1

13.8

22.9

14.3

24.7

14.2

26.6

14.6

30.0

18.9

13.4

19.7

13.4

20.8

13.7

21.7

13.6

22.5

14.1

24.2

14.0

25.7

14.3

32.8

18.6

13.2

19.3

13.2

20.6

13.6

21.4

13.5

22.0

13.9

23.7

13.8

25.1

14.1

35.0

18.3

13.1

19.1

13.1

20.1

13.4

21.1

13.3

21.8

13.8

23.3

13.6

24.6

13.9

37.8

18.0

12.9

18.8

12.9

19.8

13.2

20.7

13.2

21.3

13.6

22.9

13.5

24.1

13.7

40.0

17.8

12.8

18.2

12.6

19.3

13.0

20.4

13.0

21.0

13.4

22.4

13.3

23.6

13.5

43.3

17.2

12.5

17.7

12.4

18.7

12.7

19.8

12.7

20.4

13.2

22.0

13.1

23.0

13.2

20.0

27.1

19.0

28.1

19.0

30.0

19.6

31.2

19.4

32.2

20.0

34.9

20.0

36.4

20.1

22.8

26.6

18.7

27.6

18.7

29.4

19.3

30.6

19.1

31.7

19.8

34.1

19.6

35.8

19.8

25.0

26.3

18.6

27.2

18.5

29.0

19.1

30.1

18.9

31.1

19.5

33.4

19.3

35.3

19.6

27.8

25.7

18.3

26.7

18.3

28.3

18.7

29.4

18.6

30.5

19.2

32.9

19.1

35.4

19.7

30.0

25.2

18.0

26.3

18.0

27.8

18.5

28.9

18.3

29.9

19.0

32.2

18.8

34.2

19.2

32.8

24.8

17.8

25.7

17.7

27.4

18.3

28.5

18.1

29.3

18.7

31.6

18.6

33.5

18.9

35.0

24.4

17.6

25.4

17.6

26.7

18.0

28.1

17.9

29.0

18.6

31.0

18.3

32.8

18.6

37.8

24.0

17.3

25.0

17.4

26.4

17.8

27.6

17.7

28.4

18.3

30.5

18.1

32.2

18.4

40.0

23.7

17.2

24.2

17.0

25.7

17.5

27.2

17.5

28.0

18.1

29.8

17.8

31.5

18.1

43.3

23.0

16.8

23.5

16.6

25.0

17.1

26.4

17.2

27.1

17.7

29.3

17.6

30.6

17.8

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-100

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.1

1.4

2.2

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.3

2.0

1.4

2.2

1.4

2.3

1.4

25.0

1.7

1.3

1.7

1.3

1.9

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.1

1.3

2.2

1.4

32.8

1.6

1.3

1.6

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.4

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

40.0

1.5

1.2

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.9

1.3

2.0

1.3

20.0

2.2

1.6

2.3

1.6

2.5

1.7

2.6

1.7

2.6

1.7

2.9

1.7

3.0

1.7

22.8

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.6

2.6

1.7

2.8

1.7

2.9

1.7

25.0

2.2

1.6

2.2

1.6

2.4

1.6

2.5

1.6

2.5

1.7

2.7

1.7

2.9

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.7

2.7

1.6

2.9

1.7

30.0

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.4

1.6

2.6

1.6

2.8

1.7

32.8

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.6

1.6

2.7

1.6

35.0

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.6

2.5

1.6

2.7

1.6

37.8

2.0

1.5

2.0

1.5

2.2

1.5

2.3

1.5

2.3

1.6

2.5

1.6

2.6

1.6

40.0

1.9

1.5

2.0

1.5

2.1

1.5

2.2

1.5

2.3

1.6

2.4

1.5

2.6

1.6

43.3

1.9

1.5

1.9

1.4

2.0

1.5

2.2

1.5

2.2

1.5

2.4

1.5

2.5

1.6

20.0

3.4

2.4

3.5

2.4

3.7

2.4

3.9

2.4

4.0

2.5

4.3

2.5

4.5

2.5

22.8

3.3

2.3

3.4

2.3

3.7

2.4

3.8

2.4

3.9

2.5

4.2

2.4

4.5

2.5

25.0

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.3

3.9

2.4

4.2

2.4

4.4

2.4

27.8

3.2

2.3

3.3

2.3

3.5

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.4

2.4

30.0

3.1

2.2

3.3

2.2

3.5

2.3

3.6

2.3

3.7

2.4

4.0

2.3

4.3

2.4

32.8

3.1

2.2

3.2

2.2

3.4

2.3

3.6

2.2

3.6

2.3

3.9

2.3

4.2

2.3

35.0

3.0

2.2

3.2

2.2

3.3

2.2

3.5

2.2

3.6

2.3

3.9

2.3

4.1

2.3

37.8

3.0

2.2

3.1

2.2

3.3

2.2

3.4

2.2

3.5

2.3

3.8

2.2

4.0

2.3

40.0

3.0

2.1

3.0

2.1

3.2

2.2

3.4

2.2

3.5

2.2

3.7

2.2

3.9

2.2

43.3

2.9

2.1

2.9

2.1

3.1

2.1

3.3

2.1

3.4

2.2

3.6

2.2

3.8

2.2

20.0

4.2

3.2

4.4

3.2

4.7

3.3

4.9

3.3

5.0

3.4

5.5

3.4

5.7

3.4

22.8

4.2

3.2

4.3

3.2

4.6

3.3

4.8

3.2

5.0

3.4

5.3

3.3

5.6

3.4

25.0

4.1

3.1

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

3.3

27.8

4.0

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.8

3.3

5.2

3.3

5.5

3.4

30.0

3.9

3.1

4.1

3.1

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.4

3.3

32.8

3.9

3.0

4.0

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.2

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.9

3.1

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.1

3.0

4.3

3.0

4.4

3.1

4.8

3.1

5.0

3.2

40.0

3.7

2.9

3.8

2.9

4.0

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.1

43.3

3.6

2.9

3.7

2.9

3.9

2.9

4.1

3.0

4.2

3.1

4.6

3.0

4.8

3.1

20.0

5.1

3.8

5.3

3.8

5.7

3.9

5.9

3.9

6.1

4.0

6.6

4.0

6.9

4.0

22.8

5.0

3.7

5.2

3.7

5.5

3.8

5.8

3.8

6.0

4.0

6.4

3.9

6.8

4.0

25.0

5.0

3.7

5.1

3.7

5.5

3.8

5.7

3.8

5.9

3.9

6.3

3.9

6.7

3.9

27.8

4.9

3.6

5.0

3.6

5.3

3.7

5.6

3.7

5.8

3.9

6.2

3.8

6.7

3.9

30.0

4.8

3.6

5.0

3.6

5.2

3.7

5.4

3.7

5.6

3.8

6.1

3.8

6.5

3.9

32.8

4.7

3.6

4.8

3.5

5.2

3.7

5.4

3.6

5.5

3.8

6.0

3.7

6.3

3.8

35.0

4.6

3.5

4.8

3.5

5.0

3.6

5.3

3.6

5.5

3.7

5.9

3.7

6.2

3.8

37.8

4.5

3.5

4.7

3.5

5.0

3.6

5.2

3.6

5.4

3.7

5.8

3.7

6.1

3.7
3.7

40.0

4.5

3.5

4.6

3.4

4.8

3.5

5.1

3.5

5.3

3.7

5.6

3.6

5.9

43.3

4.3

3.4

4.4

3.4

4.7

3.5

5.0

3.5

5.1

3.6

5.5

3.6

5.8

3.6

20.0

6.8

5.0

7.0

5.0

7.5

5.1

7.8

5.1

8.0

5.3

8.7

5.2

9.1

5.3

22.8

6.6

4.9

6.9

4.9

7.3

5.0

7.6

5.0

7.9

5.2

8.5

5.2

8.9

5.2

25.0

6.6

4.9

6.8

4.8

7.2

5.0

7.5

5.0

7.8

5.1

8.3

5.1

8.8

5.2

27.8

6.4

4.8

6.7

4.8

7.1

4.9

7.3

4.9

7.6

5.1

8.2

5.0

8.8

5.2

30.0

6.3

4.7

6.6

4.7

6.9

4.9

7.2

4.8

7.5

5.0

8.0

5.0

8.5

5.1

32.8

6.2

4.7

6.4

4.7

6.8

4.8

7.1

4.8

7.3

4.9

7.9

4.9

8.3

5.0

35.0

6.1

4.6

6.3

4.6

6.7

4.7

7.0

4.7

7.2

4.9

7.7

4.8

8.2

4.9

37.8

6.0

4.6

6.2

4.6

6.6

4.7

6.9

4.7

7.1

4.8

7.6

4.8

8.0

4.9

40.0

5.9

4.5

6.0

4.5

6.4

4.6

6.8

4.6

7.0

4.8

7.4

4.7

7.8

4.8

43.3

5.7

4.5

5.9

4.4

6.2

4.5

6.6

4.6

6.8

4.7

7.3

4.7

7.6

4.8

20.0

7.6

5.5

7.9

5.5

8.4

5.7

8.8

5.6

9.0

5.8

9.8

5.8

10.2

5.9

22.8

7.5

5.4

7.8

5.4

8.3

5.6

8.6

5.6

8.9

5.8

9.6

5.7

10.1

5.8

25.0

7.4

5.4

7.6

5.4

8.1

5.5

8.5

5.5

8.8

5.7

9.4

5.6

9.9

5.7

27.8

7.2

5.3

7.5

5.3

8.0

5.5

8.3

5.4

8.6

5.6

9.3

5.6

9.9

5.7

30.0

7.1

5.2

7.4

5.3

7.8

5.4

8.1

5.3

8.4

5.6

9.1

5.5

9.6

5.6

32.8

7.0

5.2

7.2

5.2

7.7

5.3

8.0

5.3

8.2

5.5

8.9

5.4

9.4

5.5

35.0

6.9

5.1

7.1

5.1

7.5

5.3

7.9

5.3

8.2

5.4

8.7

5.4

9.2

5.5

37.8

6.7

5.1

7.0

5.1

7.4

5.2

7.8

5.2

8.0

5.4

8.6

5.3

9.0

5.4

40.0

6.7

5.0

6.8

5.0

7.2

5.1

7.6

5.1

7.9

5.3

8.4

5.2

8.8

5.3

43.3

6.5

4.9

6.6

4.9

7.0

5.0

7.4

5.0

7.6

5.2

8.2

5.2

8.6

5.3

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-101

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

8.5

6.1

8.8

6.1

9.4

6.3

9.8

6.2

10.1

6.4

10.9

6.4

11.4

6.5

22.8

8.3

6.0

8.7

6.0

9.2

6.2

9.6

6.1

9.9

6.4

10.7

6.3

11.2

6.4

25.0

8.2

6.0

8.5

5.9

9.1

6.1

9.4

6.1

9.8

6.3

10.5

6.2

11.0

6.3

27.8

8.1

5.9

8.4

5.9

8.9

6.0

9.2

6.0

9.5

6.2

10.3

6.2

11.1

6.3

30.0

7.9

5.8

8.2

5.8

8.7

5.9

9.0

5.9

9.4

6.1

10.1

6.1

10.7

6.2

32.8

7.8

5.7

8.0

5.7

8.6

5.9

8.9

5.8

9.2

6.0

9.9

6.0

10.5

6.1

35.0

7.6

5.7

8.0

5.7

8.4

5.8

8.8

5.8

9.1

6.0

9.7

5.9

10.3

6.0

37.8

7.5

5.6

7.8

5.6

8.3

5.7

8.7

5.7

8.9

5.9

9.6

5.8

10.1

6.0

40.0

7.4

5.6

7.6

5.5

8.0

5.6

8.5

5.7

8.8

5.9

9.3

5.8

9.9

5.9

43.3

7.2

5.4

7.4

5.4

7.8

5.5

8.3

5.5

8.5

5.7

9.2

5.7

9.6

5.8

20.0

10.2

7.5

10.6

7.5

11.3

7.8

11.8

7.7

12.1

8.0

13.2

7.9

13.7

8.0

22.8

10.0

7.4

10.4

7.4

11.1

7.7

11.5

7.6

11.9

7.9

12.9

7.8

13.5

7.9

25.0

9.9

7.4

10.3

7.4

10.9

7.6

11.4

7.5

11.7

7.8

12.6

7.7

13.3

7.9

27.8

9.7

7.3

10.1

7.3

10.7

7.5

11.1

7.4

11.5

7.7

12.4

7.6

13.3

7.9

30.0

9.5

7.2

9.9

7.2

10.5

7.4

10.9

7.3

11.3

7.6

12.2

7.5

12.9

7.7

32.8

9.3

7.1

9.7

7.1

10.3

7.3

10.8

7.3

11.0

7.5

11.9

7.4

12.6

7.6

35.0

9.2

7.0

9.6

7.0

10.1

7.2

10.6

7.2

10.9

7.5

11.7

7.4

12.4

7.5

37.8

9.0

6.9

9.4

7.0

9.9

7.1

10.4

7.1

10.7

7.4

11.5

7.3

12.1

7.4

40.0

8.9

6.9

9.1

6.8

9.7

7.0

10.3

7.1

10.5

7.3

11.3

7.2

11.9

7.3

43.3

8.7

6.8

8.9

6.7

9.4

6.9

9.9

6.9

10.2

7.2

11.0

7.1

11.6

7.2

20.0

13.6

9.7

14.1

9.7

15.1

10.0

15.7

9.9

16.1

10.2

17.5

10.2

18.3

10.3

22.8

13.3

9.5

13.9

9.5

14.7

9.8

15.3

9.7

15.9

10.1

17.1

10.0

18.0

10.1

25.0

13.2

9.5

13.6

9.4

14.5

9.7

15.1

9.6

15.6

10.0

16.8

9.9

17.7

10.0
10.0

27.8

12.9

9.3

13.4

9.3

14.2

9.6

14.8

9.5

15.3

9.8

16.5

9.8

17.7

30.0

12.6

9.2

13.2

9.2

13.9

9.4

14.5

9.3

15.0

9.7

16.2

9.6

17.2

9.8

32.8

12.4

9.1

12.9

9.1

13.8

9.3

14.3

9.3

14.7

9.6

15.8

9.5

16.8

9.7

35.0

12.2

9.0

12.7

9.0

13.4

9.2

14.1

9.2

14.6

9.5

15.6

9.4

16.4

9.5

37.8

12.0

8.9

12.5

8.9

13.2

9.1

13.9

9.1

14.2

9.4

15.3

9.3

16.1

9.4

40.0

11.9

8.8

12.2

8.7

12.9

8.9

13.6

9.0

14.0

9.3

15.0

9.1

15.8

9.3

43.3

11.5

8.6

11.8

8.5

12.5

8.8

13.2

8.8

13.6

9.1

14.7

9.0

15.4

9.1

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-102

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PMFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.7

2.2

1.7

2.3

SHC
1.7

22.8

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.0

1.6

2.2

1.6

2.3

1.7

25.0

1.7

1.5

1.7

1.5

1.9

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.3

1.7

27.8

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.3

1.7

30.0

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.5

1.9

1.6

2.1

1.6

2.2

1.6

32.8

1.6

1.5

1.6

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

35.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

37.8

1.5

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

2.0

1.6

2.1

1.6

40.0

1.5

1.4

1.6

1.4

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

43.3

1.5

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.9

1.5

2.0

1.6

20.0

2.2

1.9

2.3

1.9

2.5

1.9

2.6

1.9

2.6

2.0

2.9

2.0

3.0

2.0

22.8

2.2

1.8

2.3

1.8

2.4

1.9

2.5

1.9

2.6

2.0

2.8

2.0

2.9

2.0

25.0

2.2

1.8

2.2

1.8

2.4

1.9

2.5

1.9

2.5

2.0

2.7

1.9

2.9

2.0

27.8

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.9

2.5

1.9

2.7

1.9

2.9

2.0

30.0

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.8

2.4

1.9

2.6

1.9

2.8

2.0

32.8

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.6

1.9

2.7

1.9

35.0

2.0

1.8

2.1

1.8

2.2

1.8

2.3

1.8

2.4

1.9

2.5

1.9

2.7

1.9

37.8

2.0

1.7

2.0

1.7

2.2

1.8

2.3

1.8

2.3

1.9

2.5

1.9

2.6

1.9

40.0

1.9

1.7

2.0

1.7

2.1

1.8

2.2

1.8

2.3

1.9

2.4

1.8

2.6

1.9

43.3

1.9

1.7

1.9

1.7

2.0

1.8

2.2

1.8

2.2

1.8

2.4

1.8

2.5

1.9

20.0

3.4

2.4

3.5

2.4

3.7

2.5

3.9

2.5

4.0

2.6

4.3

2.6

4.5

2.6

22.8

3.3

2.4

3.4

2.4

3.7

2.5

3.8

2.5

3.9

2.6

4.2

2.5

4.5

2.6

25.0

3.3

2.4

3.4

2.4

3.6

2.5

3.7

2.4

3.9

2.5

4.2

2.5

4.4

2.5

27.8

3.2

2.4

3.3

2.4

3.5

2.4

3.7

2.4

3.8

2.5

4.1

2.5

4.4

2.5

30.0

3.1

2.3

3.3

2.3

3.5

2.4

3.6

2.4

3.7

2.5

4.0

2.4

4.3

2.5

32.8

3.1

2.3

3.2

2.3

3.4

2.4

3.6

2.3

3.6

2.4

3.9

2.4

4.2

2.5

35.0

3.0

2.3

3.2

2.3

3.3

2.3

3.5

2.3

3.6

2.4

3.9

2.4

4.1

2.4

37.8

3.0

2.2

3.1

2.2

3.3

2.3

3.4

2.3

3.5

2.4

3.8

2.4

4.0

2.4

40.0

3.0

2.2

3.0

2.2

3.2

2.3

3.4

2.3

3.5

2.4

3.7

2.3

3.9

2.4

43.3

2.9

2.2

2.9

2.2

3.1

2.2

3.3

2.2

3.4

2.3

3.6

2.3

3.8

2.3

20.0

4.2

3.0

4.4

3.0

4.7

3.1

4.9

3.1

5.0

3.2

5.5

3.1

5.7

3.2

22.8

4.2

2.9

4.3

2.9

4.6

3.0

4.8

3.0

5.0

3.1

5.3

3.1

5.6

3.1

25.0

4.1

2.9

4.3

2.9

4.5

3.0

4.7

3.0

4.9

3.1

5.2

3.0

5.5

3.1

27.8

4.0

2.9

4.2

2.9

4.4

3.0

4.6

2.9

4.8

3.0

5.2

3.0

5.5

3.1

30.0

3.9

2.8

4.1

2.8

4.3

2.9

4.5

2.9

4.7

3.0

5.0

3.0

5.4

3.0

32.8

3.9

2.8

4.0

2.8

4.3

2.9

4.5

2.9

4.6

2.9

4.9

2.9

5.2

3.0

35.0

3.8

2.8

4.0

2.8

4.2

2.8

4.4

2.8

4.5

2.9

4.9

2.9

5.1

2.9

37.8

3.8

2.7

3.9

2.7

4.1

2.8

4.3

2.8

4.4

2.9

4.8

2.9

5.0

2.9

40.0

3.7

2.7

3.8

2.7

4.0

2.8

4.3

2.8

4.4

2.9

4.7

2.8

4.9

2.9

43.3

3.6

2.7

3.7

2.6

3.9

2.7

4.1

2.7

4.2

2.8

4.6

2.8

4.8

2.8

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-103

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PLFY-P-NCMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

2.2

2.0

2.3

2.0

2.5

2.0

2.6

2.0

2.6

2.1

2.9

2.1

3.0

SHC
2.1

22.8

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.6

2.1

2.8

2.1

2.9

2.1

25.0

2.2

1.9

2.2

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.1

2.9

2.1

27.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.9

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.4

2.0

2.6

2.0

2.8

2.1

32.8

2.0

1.9

2.1

1.9

2.2

2.0

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.1

35.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.7

2.0

37.8

2.0

1.9

2.0

1.9

2.2

1.9

2.3

1.9

2.3

2.0

2.5

2.0

2.6

2.0

40.0

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.6

2.0

43.3

1.9

1.8

1.9

1.8

2.0

1.9

2.2

1.9

2.2

2.0

2.4

1.9

2.5

2.0

20.0

3.4

2.6

3.5

2.6

3.7

2.7

3.9

2.7

4.0

2.8

4.3

2.8

4.5

2.8

22.8

3.3

2.6

3.4

2.6

3.7

2.7

3.8

2.6

3.9

2.8

4.2

2.7

4.5

2.8

25.0

3.3

2.6

3.4

2.6

3.6

2.6

3.7

2.6

3.9

2.7

4.2

2.7

4.4

2.8

27.8

3.2

2.5

3.3

2.5

3.5

2.6

3.7

2.6

3.8

2.7

4.1

2.7

4.4

2.8

30.0

3.1

2.5

3.3

2.5

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.6

4.3

2.7

32.8

3.1

2.5

3.2

2.5

3.4

2.6

3.6

2.5

3.6

2.6

3.9

2.6

4.2

2.7

35.0

3.0

2.5

3.2

2.5

3.3

2.5

3.5

2.5

3.6

2.6

3.9

2.6

4.1

2.6

37.8

3.0

2.4

3.1

2.4

3.3

2.5

3.4

2.5

3.5

2.6

3.8

2.6

4.0

2.6

40.0

3.0

2.4

3.0

2.4

3.2

2.5

3.4

2.5

3.5

2.6

3.7

2.5

3.9

2.6

43.3

2.9

2.4

2.9

2.3

3.1

2.4

3.3

2.4

3.4

2.5

3.6

2.5

3.8

2.6

20.0

4.2

3.1

4.4

3.1

4.7

3.2

4.9

3.1

5.0

3.2

5.5

3.2

5.7

3.3
3.2

22.8

4.2

3.0

4.3

3.0

4.6

3.1

4.8

3.1

5.0

3.2

5.3

3.2

5.6

25.0

4.1

3.0

4.3

3.0

4.5

3.1

4.7

3.1

4.9

3.2

5.2

3.1

5.5

3.2

27.8

4.0

3.0

4.2

3.0

4.4

3.0

4.6

3.0

4.8

3.1

5.2

3.1

5.5

3.2

30.0

3.9

2.9

4.1

2.9

4.3

3.0

4.5

3.0

4.7

3.1

5.0

3.1

5.4

3.1

32.8

3.9

2.9

4.0

2.9

4.3

3.0

4.5

2.9

4.6

3.0

4.9

3.0

5.2

3.1

35.0

3.8

2.9

4.0

2.9

4.2

2.9

4.4

2.9

4.5

3.0

4.9

3.0

5.1

3.0

37.8

3.8

2.8

3.9

2.8

4.1

2.9

4.3

2.9

4.4

3.0

4.8

2.9

5.0

3.0

40.0

3.7

2.8

3.8

2.8

4.0

2.8

4.3

2.9

4.4

3.0

4.7

2.9

4.9

3.0

43.3

3.6

2.7

3.7

2.7

3.9

2.8

4.1

2.8

4.2

2.9

4.6

2.9

4.8

2.9

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-104

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PLFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.4

2.9

3.5

2.9

3.7

3.0

3.9

2.9

4.0

3.1

4.3

3.0

4.5

3.1

22.8

3.3

2.8

3.4

2.8

3.7

2.9

3.8

2.9

3.9

3.0

4.2

3.0

4.5

3.1

SHC

25.0

3.3

2.8

3.4

2.8

3.6

2.9

3.7

2.9

3.9

3.0

4.2

3.0

4.4

3.1

27.8

3.2

2.8

3.3

2.8

3.5

2.9

3.7

2.9

3.8

3.0

4.1

3.0

4.4

3.1

30.0

3.1

2.8

3.3

2.8

3.5

2.8

3.6

2.8

3.7

3.0

4.0

2.9

4.3

3.0

32.8

3.1

2.7

3.2

2.7

3.4

2.8

3.6

2.8

3.6

2.9

3.9

2.9

4.2

3.0

35.0

3.0

2.7

3.2

2.7

3.3

2.8

3.5

2.8

3.6

2.9

3.9

2.9

4.1

3.0

37.8

3.0

2.7

3.1

2.7

3.3

2.8

3.4

2.8

3.5

2.9

3.8

2.8

4.0

2.9

40.0

3.0

2.7

3.0

2.6

3.2

2.7

3.4

2.7

3.5

2.9

3.7

2.8

3.9

2.9
2.9

43.3

2.9

2.6

2.9

2.6

3.1

2.7

3.3

2.7

3.4

2.8

3.6

2.8

3.8

20.0

4.2

3.5

4.4

3.5

4.7

3.6

4.9

3.6

5.0

3.7

5.5

3.7

5.7

3.8

22.8

4.2

3.4

4.3

3.4

4.6

3.6

4.8

3.5

5.0

3.7

5.3

3.7

5.6

3.7

25.0

4.1

3.4

4.3

3.4

4.5

3.5

4.7

3.5

4.9

3.7

5.2

3.6

5.5

3.7

27.8

4.0

3.4

4.2

3.4

4.4

3.5

4.6

3.5

4.8

3.6

5.2

3.6

5.5

3.7

30.0

3.9

3.4

4.1

3.4

4.3

3.5

4.5

3.4

4.7

3.6

5.0

3.6

5.4

3.7

32.8

3.9

3.3

4.0

3.3

4.3

3.4

4.5

3.4

4.6

3.5

4.9

3.5

5.2

3.6

35.0

3.8

3.3

4.0

3.3

4.2

3.4

4.4

3.4

4.5

3.5

4.9

3.5

5.1

3.6

37.8

3.8

3.3

3.9

3.3

4.1

3.4

4.3

3.4

4.4

3.5

4.8

3.5

5.0

3.5
3.5

40.0

3.7

3.2

3.8

3.2

4.0

3.3

4.3

3.3

4.4

3.5

4.7

3.4

4.9

43.3

3.6

3.2

3.7

3.2

3.9

3.3

4.1

3.3

4.2

3.4

4.6

3.4

4.8

3.5

20.0

5.1

4.2

5.3

4.2

5.7

4.3

5.9

4.3

6.1

4.5

6.6

4.4

6.9

4.5

22.8

5.0

4.1

5.2

4.1

5.5

4.3

5.8

4.2

6.0

4.4

6.4

4.4

6.8

4.5

25.0

5.0

4.1

5.1

4.1

5.5

4.2

5.7

4.2

5.9

4.4

6.3

4.3

6.7

4.4

27.8

4.9

4.1

5.0

4.0

5.3

4.2

5.6

4.2

5.8

4.3

6.2

4.3

6.7

4.4

30.0

4.8

4.0

5.0

4.0

5.2

4.1

5.4

4.1

5.6

4.3

6.1

4.2

6.5

4.4
4.3

32.8

4.7

4.0

4.8

4.0

5.2

4.1

5.4

4.1

5.5

4.2

6.0

4.2

6.3

35.0

4.6

3.9

4.8

3.9

5.0

4.1

5.3

4.1

5.5

4.2

5.9

4.2

6.2

4.3

37.8

4.5

3.9

4.7

3.9

5.0

4.0

5.2

4.0

5.4

4.2

5.8

4.1

6.1

4.2

40.0

4.5

3.9

4.6

3.8

4.8

4.0

5.1

4.0

5.3

4.1

5.6

4.1

5.9

4.2

43.3

4.3

3.8

4.4

3.8

4.7

3.9

5.0

3.9

5.1

4.1

5.5

4.0

5.8

4.1

20.0

6.8

5.1

7.0

5.1

7.5

5.3

7.8

5.3

8.0

5.4

8.7

5.4

9.1

5.5

22.8

6.6

5.1

6.9

5.1

7.3

5.2

7.6

5.2

7.9

5.4

8.5

5.3

8.9

5.4
5.4

25.0

6.6

5.0

6.8

5.0

7.2

5.2

7.5

5.1

7.8

5.3

8.3

5.3

8.8

27.8

6.4

5.0

6.7

5.0

7.1

5.1

7.3

5.1

7.6

5.3

8.2

5.2

8.8

5.4

30.0

6.3

4.9

6.6

4.9

6.9

5.0

7.2

5.0

7.5

5.2

8.0

5.2

8.5

5.3

32.8

6.2

4.8

6.4

4.8

6.8

5.0

7.1

5.0

7.3

5.1

7.9

5.1

8.3

5.2

35.0

6.1

4.8

6.3

4.8

6.7

4.9

7.0

4.9

7.2

5.1

7.7

5.0

8.2

5.2
5.1

37.8

6.0

4.8

6.2

4.8

6.6

4.9

6.9

4.9

7.1

5.1

7.6

5.0

8.0

40.0

5.9

4.7

6.0

4.7

6.4

4.8

6.8

4.8

7.0

5.0

7.4

4.9

7.8

5.0

43.3

5.7

4.6

5.9

4.6

6.2

4.7

6.6

4.7

6.8

4.9

7.3

4.9

7.6

5.0

20.0

8.5

6.2

8.8

6.1

9.4

6.3

9.8

6.3

10.1

6.5

10.9

6.5

11.4

6.5

22.8

8.3

6.1

8.7

6.1

9.2

6.3

9.6

6.2

9.9

6.4

10.7

6.4

11.2

6.5

25.0

8.2

6.0

8.5

6.0

9.1

6.2

9.4

6.1

9.8

6.4

10.5

6.3

11.0

6.4

27.8

8.1

5.9

8.4

5.9

8.9

6.1

9.2

6.0

9.5

6.3

10.3

6.2

11.1

6.4

30.0

7.9

5.9

8.2

5.9

8.7

6.0

9.0

6.0

9.4

6.2

10.1

6.1

10.7

6.3

32.8

7.8

5.8

8.0

5.8

8.6

6.0

8.9

5.9

9.2

6.1

9.9

6.1

10.5

6.2

35.0

7.6

5.7

8.0

5.7

8.4

5.9

8.8

5.9

9.1

6.1

9.7

6.0

10.3

6.1

37.8

7.5

5.7

7.8

5.7

8.3

5.8

8.7

5.8

8.9

6.0

9.6

5.9

10.1

6.0

40.0

7.4

5.6

7.6

5.5

8.0

5.7

8.5

5.7

8.8

5.9

9.3

5.8

9.9

6.0

43.3

7.2

5.5

7.4

5.4

7.8

5.6

8.3

5.6

8.5

5.8

9.2

5.8

9.6

5.9

20.0

10.1

7.8

10.5

7.8

11.2

8.1

11.7

8.0

12.0

8.3

13.0

8.2

13.6

8.4

22.8

9.9

7.7

10.3

7.7

11.0

7.9

11.4

7.9

11.8

8.2

12.7

8.1

13.4

8.3

25.0

9.8

7.7

10.2

7.6

10.8

7.9

11.2

7.8

11.6

8.1

12.5

8.0

13.2

8.2

27.8

9.6

7.6

10.0

7.5

10.6

7.8

11.0

7.7

11.4

8.0

12.3

8.0

13.2

8.2

30.0

9.4

7.5

9.8

7.5

10.4

7.7

10.8

7.6

11.2

7.9

12.0

7.9

12.8

8.1

32.8

9.3

7.4

9.6

7.4

10.2

7.6

10.7

7.6

10.9

7.8

11.8

7.8

12.5

8.0

35.0

9.1

7.3

9.5

7.3

10.0

7.5

10.5

7.5

10.8

7.8

11.6

7.7

12.2

7.9

37.8

9.0

7.2

9.3

7.2

9.9

7.4

10.3

7.4

10.6

7.7

11.4

7.6

12.0

7.8

40.0

8.9

7.2

9.1

7.1

9.6

7.3

10.2

7.4

10.4

7.6

11.2

7.5

11.8

7.7

43.3

8.6

7.1

8.8

7.0

9.3

7.2

9.8

7.2

10.1

7.5

10.9

7.5

11.5

7.6

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-105

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PCFY-P-NGMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

4.2

3.2

4.4

3.2

4.7

3.3

4.9

3.3

5.0

3.4

5.5

3.4

5.7

3.4

22.8

4.2

3.2

4.3

3.2

4.6

3.3

4.8

3.2

5.0

3.4

5.3

3.3

5.6

3.4
3.3

SHC

25.0

4.1

3.1

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

27.8

4.0

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.8

3.3

5.2

3.3

5.5

3.4

30.0

3.9

3.1

4.1

3.1

4.3

3.1

4.5

3.1

4.7

3.2

5.0

3.2

5.4

3.3

32.8

3.9

3.0

4.0

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.2

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.9

3.1

5.1

3.2
3.2

37.8

3.8

3.0

3.9

3.0

4.1

3.0

4.3

3.0

4.4

3.1

4.8

3.1

5.0

40.0

3.7

2.9

3.8

2.9

4.0

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.1

43.3

3.6

2.9

3.7

2.9

3.9

2.9

4.1

3.0

4.2

3.1

4.6

3.0

4.8

3.1

20.0

6.8

5.0

7.0

5.0

7.5

5.1

7.8

5.1

8.0

5.3

8.7

5.2

9.1

5.3

22.8

6.6

4.9

6.9

4.9

7.3

5.0

7.6

5.0

7.9

5.2

8.5

5.2

8.9

5.2

25.0

6.6

4.9

6.8

4.8

7.2

5.0

7.5

5.0

7.8

5.1

8.3

5.1

8.8

5.2

27.8

6.4

4.8

6.7

4.8

7.1

4.9

7.3

4.9

7.6

5.1

8.2

5.0

8.8

5.2

30.0

6.3

4.7

6.6

4.7

6.9

4.9

7.2

4.8

7.5

5.0

8.0

5.0

8.5

5.1

32.8

6.2

4.7

6.4

4.7

6.8

4.8

7.1

4.8

7.3

4.9

7.9

4.9

8.3

5.0

35.0

6.1

4.6

6.3

4.6

6.7

4.7

7.0

4.7

7.2

4.9

7.7

4.8

8.2

4.9

37.8

6.0

4.6

6.2

4.6

6.6

4.7

6.9

4.7

7.1

4.8

7.6

4.8

8.0

4.9

40.0

5.9

4.5

6.0

4.5

6.4

4.6

6.8

4.6

7.0

4.8

7.4

4.7

7.8

4.8

43.3

5.7

4.5

5.9

4.4

6.2

4.5

6.6

4.6

6.8

4.7

7.3

4.7

7.6

4.8

20.0

8.5

6.1

8.8

6.1

9.4

6.3

9.8

6.2

10.1

6.4

10.9

6.4

11.4

6.5

22.8

8.3

6.0

8.7

6.0

9.2

6.2

9.6

6.1

9.9

6.4

10.7

6.3

11.2

6.4

25.0

8.2

6.0

8.5

5.9

9.1

6.1

9.4

6.1

9.8

6.3

10.5

6.2

11.0

6.3

27.8

8.1

5.9

8.4

5.9

8.9

6.0

9.2

6.0

9.5

6.2

10.3

6.2

11.1

6.3

30.0

7.9

5.8

8.2

5.8

8.7

5.9

9.0

5.9

9.4

6.1

10.1

6.1

10.7

6.2

32.8

7.8

5.7

8.0

5.7

8.6

5.9

8.9

5.8

9.2

6.0

9.9

6.0

10.5

6.1

35.0

7.6

5.7

8.0

5.7

8.4

5.8

8.8

5.8

9.1

6.0

9.7

5.9

10.3

6.0

37.8

7.5

5.6

7.8

5.6

8.3

5.7

8.7

5.7

8.9

5.9

9.6

5.8

10.1

6.0

40.0

7.4

5.6

7.6

5.5

8.0

5.6

8.5

5.7

8.8

5.9

9.3

5.8

9.9

5.9

43.3

7.2

5.4

7.4

5.4

7.8

5.5

8.3

5.5

8.5

5.7

9.2

5.7

9.6

5.8

20.0

10.2

7.5

10.6

7.5

11.3

7.8

11.8

7.7

12.1

8.0

13.2

7.9

13.7

8.0

22.8

10.0

7.4

10.4

7.4

11.1

7.7

11.5

7.6

11.9

7.9

12.9

7.8

13.5

7.9

25.0

9.9

7.4

10.3

7.4

10.9

7.6

11.4

7.5

11.7

7.8

12.6

7.7

13.3

7.9

27.8

9.7

7.3

10.1

7.3

10.7

7.5

11.1

7.4

11.5

7.7

12.4

7.6

13.3

7.9

30.0

9.5

7.2

9.9

7.2

10.5

7.4

10.9

7.3

11.3

7.6

12.2

7.5

12.9

7.7

32.8

9.3

7.1

9.7

7.1

10.3

7.3

10.8

7.3

11.0

7.5

11.9

7.4

12.6

7.6

35.0

9.2

7.0

9.6

7.0

10.1

7.2

10.6

7.2

10.9

7.5

11.7

7.4

12.4

7.5

37.8

9.0

6.9

9.4

7.0

9.9

7.1

10.4

7.1

10.7

7.4

11.5

7.3

12.1

7.4

40.0

8.9

6.9

9.1

6.8

9.7

7.0

10.3

7.1

10.5

7.3

11.3

7.2

11.9

7.3

43.3

8.7

6.8

8.9

6.7

9.4

6.9

9.9

6.9

10.2

7.2

11.0

7.1

11.6

7.2

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-106

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.1

1.4

2.2

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.3

2.0

1.4

2.2

1.4

2.3

1.4

25.0

1.7

1.3

1.7

1.3

1.9

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.4

2.1

1.4

2.3

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.3

2.1

1.3

2.2

1.4

32.8

1.6

1.3

1.6

1.3

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.4

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

40.0

1.5

1.2

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.9

1.3

2.0

1.3

20.0

2.2

1.7

2.3

1.7

2.5

1.7

2.6

1.7

2.6

1.8

2.9

1.8

3.0

1.8

22.8

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.7

2.6

1.7

2.8

1.7

2.9

1.8

25.0

2.2

1.6

2.2

1.6

2.4

1.7

2.5

1.7

2.5

1.7

2.7

1.7

2.9

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.6

2.5

1.7

2.7

1.7

2.9

1.7

30.0

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.4

1.7

2.6

1.7

2.8

1.7

32.8

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.6

1.7

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.6

2.7

1.7

37.8

2.0

1.5

2.0

1.5

2.2

1.6

2.3

1.6

2.3

1.6

2.5

1.6

2.6

1.7

40.0

1.9

1.5

2.0

1.5

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.6

2.6

1.6

43.3

1.9

1.5

1.9

1.5

2.0

1.5

2.2

1.5

2.2

1.6

2.4

1.6

2.5

1.6

20.0

3.4

2.7

3.5

2.7

3.7

2.8

3.9

2.7

4.0

2.8

4.3

2.8

4.5

2.9

22.8

3.3

2.6

3.4

2.6

3.7

2.7

3.8

2.7

3.9

2.8

4.2

2.8

4.5

2.9

25.0

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.7

3.9

2.8

4.2

2.8

4.4

2.8

27.8

3.2

2.6

3.3

2.6

3.5

2.7

3.7

2.7

3.8

2.8

4.1

2.7

4.4

2.8

30.0

3.1

2.6

3.3

2.6

3.5

2.6

3.6

2.6

3.7

2.7

4.0

2.7

4.3

2.8

32.8

3.1

2.5

3.2

2.5

3.4

2.6

3.6

2.6

3.6

2.7

3.9

2.7

4.2

2.7

35.0

3.0

2.5

3.2

2.5

3.3

2.6

3.5

2.6

3.6

2.7

3.9

2.7

4.1

2.7

37.8

3.0

2.5

3.1

2.5

3.3

2.6

3.4

2.6

3.5

2.7

3.8

2.6

4.0

2.7

40.0

3.0

2.5

3.0

2.4

3.2

2.5

3.4

2.5

3.5

2.6

3.7

2.6

3.9

2.7

43.3

2.9

2.4

2.9

2.4

3.1

2.5

3.3

2.5

3.4

2.6

3.6

2.6

3.8

2.6

20.0

4.2

3.2

4.4

3.2

4.7

3.3

4.9

3.3

5.0

3.4

5.5

3.4

5.7

3.4

22.8

4.2

3.2

4.3

3.2

4.6

3.3

4.8

3.3

5.0

3.4

5.3

3.4

5.6

3.4

25.0

4.1

3.2

4.3

3.1

4.5

3.2

4.7

3.2

4.9

3.3

5.2

3.3

5.5

3.4

27.8

4.0

3.1

4.2

3.1

4.4

3.2

4.6

3.2

4.8

3.3

5.2

3.3

5.5

3.4

30.0

3.9

3.1

4.1

3.1

4.3

3.2

4.5

3.1

4.7

3.3

5.0

3.2

5.4

3.3

32.8

3.9

3.0

4.0

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.2

5.2

3.3

35.0

3.8

3.0

4.0

3.0

4.2

3.1

4.4

3.1

4.5

3.2

4.9

3.2

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.1

3.1

4.3

3.1

4.4

3.2

4.8

3.1

5.0

3.2

40.0

3.7

3.0

3.8

2.9

4.0

3.0

4.3

3.0

4.4

3.1

4.7

3.1

4.9

3.2

43.3

3.6

2.9

3.7

2.9

3.9

3.0

4.1

3.0

4.2

3.1

4.6

3.1

4.8

3.1

20.0

5.1

4.1

5.3

4.1

5.7

4.2

5.9

4.2

6.1

4.3

6.6

4.3

6.9

4.4

22.8

5.0

4.0

5.2

4.0

5.5

4.2

5.8

4.1

6.0

4.3

6.4

4.3

6.8

4.4

25.0

5.0

4.0

5.1

4.0

5.5

4.1

5.7

4.1

5.9

4.3

6.3

4.2

6.7

4.3

27.8

4.9

4.0

5.0

4.0

5.3

4.1

5.6

4.1

5.8

4.2

6.2

4.2

6.7

4.3

30.0

4.8

3.9

5.0

3.9

5.2

4.0

5.4

4.0

5.6

4.2

6.1

4.1

6.5

4.3

32.8

4.7

3.9

4.8

3.9

5.2

4.0

5.4

4.0

5.5

4.1

6.0

4.1

6.3

4.2

35.0

4.6

3.8

4.8

3.8

5.0

4.0

5.3

4.0

5.5

4.1

5.9

4.1

6.2

4.2

37.8

4.5

3.8

4.7

3.8

5.0

3.9

5.2

3.9

5.4

4.1

5.8

4.0

6.1

4.1
4.1

40.0

4.5

3.8

4.6

3.7

4.8

3.9

5.1

3.9

5.3

4.0

5.6

4.0

5.9

43.3

4.3

3.7

4.4

3.7

4.7

3.8

5.0

3.8

5.1

4.0

5.5

3.9

5.8

4.0

20.0

6.8

5.1

7.0

5.1

7.5

5.2

7.8

5.2

8.0

5.4

8.7

5.4

9.1

5.4

22.8

6.6

5.0

6.9

5.0

7.3

5.2

7.6

5.1

7.9

5.3

8.5

5.3

8.9

5.4

25.0

6.6

5.0

6.8

5.0

7.2

5.1

7.5

5.1

7.8

5.3

8.3

5.2

8.8

5.3

27.8

6.4

4.9

6.7

4.9

7.1

5.0

7.3

5.0

7.6

5.2

8.2

5.2

8.8

5.3

30.0

6.3

4.8

6.6

4.8

6.9

5.0

7.2

4.9

7.5

5.1

8.0

5.1

8.5

5.2

32.8

6.2

4.8

6.4

4.8

6.8

4.9

7.1

4.9

7.3

5.1

7.9

5.0

8.3

5.2

35.0

6.1

4.7

6.3

4.7

6.7

4.9

7.0

4.9

7.2

5.0

7.7

5.0

8.2

5.1

37.8

6.0

4.7

6.2

4.7

6.6

4.8

6.9

4.8

7.1

5.0

7.6

4.9

8.0

5.0

40.0

5.9

4.7

6.0

4.6

6.4

4.8

6.8

4.8

7.0

4.9

7.4

4.9

7.8

5.0

43.3

5.7

4.6

5.9

4.5

6.2

4.7

6.6

4.7

6.8

4.9

7.3

4.8

7.6

4.9

20.0

8.5

6.8

8.8

6.8

9.4

7.0

9.8

7.0

10.1

7.3

10.9

7.2

11.4

7.3

22.8

8.3

6.7

8.7

6.7

9.2

7.0

9.6

6.9

9.9

7.2

10.7

7.1

11.2

7.3

25.0

8.2

6.7

8.5

6.7

9.1

6.9

9.4

6.9

9.8

7.1

10.5

7.0

11.0

7.2

27.8

8.1

6.6

8.4

6.6

8.9

6.8

9.2

6.8

9.5

7.0

10.3

7.0

11.1

7.2

30.0

7.9

6.5

8.2

6.5

8.7

6.7

9.0

6.7

9.4

7.0

10.1

6.9

10.7

7.1

32.8

7.8

6.5

8.0

6.5

8.6

6.7

8.9

6.7

9.2

6.9

9.9

6.8

10.5

7.0

35.0

7.6

6.4

8.0

6.4

8.4

6.6

8.8

6.6

9.1

6.9

9.7

6.8

10.3

6.9

37.8

7.5

6.4

7.8

6.4

8.3

6.6

8.7

6.5

8.9

6.8

9.6

6.7

10.1

6.9

40.0

7.4

6.3

7.6

6.2

8.0

6.5

8.5

6.5

8.8

6.7

9.3

6.6

9.9

6.8

43.3

7.2

6.2

7.4

6.1

7.8

6.4

8.3

6.4

8.5

6.6

9.2

6.6

9.6

6.7

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-107

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-1. Cooling CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with PFFY-P-NEMU/NRMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.4

2.2

1.4

2.3

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.0

1.4

2.2

1.4

2.3

1.4

25.0

1.7

1.3

1.7

1.3

1.9

1.3

1.9

1.3

2.0

1.4

2.1

1.3

2.3

1.4

27.8

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

2.3

1.4

30.0

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.3

1.9

1.3

2.1

1.3

2.2

1.3

32.8

1.6

1.2

1.6

1.2

1.8

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.2

1.8

1.2

1.8

1.3

2.0

1.3

2.1

1.3

40.0

1.5

1.2

1.6

1.2

1.6

1.2

1.7

1.2

1.8

1.3

1.9

1.2

2.0

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.2

1.9

1.2

2.0

1.3

20.0

2.2

1.7

2.3

1.7

2.5

1.7

2.6

1.7

2.6

1.8

2.9

1.8

3.0

1.8

22.8

2.2

1.7

2.3

1.7

2.4

1.7

2.5

1.7

2.6

1.8

2.8

1.8

2.9

1.8

25.0

2.2

1.7

2.2

1.7

2.4

1.7

2.5

1.7

2.5

1.8

2.7

1.7

2.9

1.8

27.8

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.7

2.7

1.7

2.9

1.8

30.0

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.4

1.7

2.6

1.7

2.8

1.7

32.8

2.0

1.6

2.1

1.6

2.2

1.7

2.3

1.6

2.4

1.7

2.6

1.7

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.7

2.7

1.7

37.8

2.0

1.6

2.0

1.6

2.2

1.6

2.3

1.6

2.3

1.7

2.5

1.7

2.6

1.7

40.0

1.9

1.6

2.0

1.5

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.6

2.6

1.7

43.3

1.9

1.5

1.9

1.5

2.0

1.6

2.2

1.6

2.2

1.6

2.4

1.6

2.5

1.6

20.0

3.4

2.3

3.5

2.3

3.7

2.4

3.9

2.4

4.0

2.5

4.3

2.5

4.5

2.5

22.8

3.3

2.3

3.4

2.3

3.7

2.4

3.8

2.4

3.9

2.4

4.2

2.4

4.5

2.4

25.0

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.3

3.9

2.4

4.2

2.4

4.4

2.4

27.8

3.2

2.3

3.3

2.3

3.5

2.3

3.7

2.3

3.8

2.4

4.1

2.4

4.4

2.4

30.0

3.1

2.2

3.3

2.2

3.5

2.3

3.6

2.3

3.7

2.3

4.0

2.3

4.3

2.4

32.8

3.1

2.2

3.2

2.2

3.4

2.3

3.6

2.2

3.6

2.3

3.9

2.3

4.2

2.3

35.0

3.0

2.2

3.2

2.2

3.3

2.2

3.5

2.2

3.6

2.3

3.9

2.3

4.1

2.3

37.8

3.0

2.1

3.1

2.1

3.3

2.2

3.4

2.2

3.5

2.2

3.8

2.2

4.0

2.3

40.0

3.0

2.1

3.0

2.1

3.2

2.1

3.4

2.2

3.5

2.2

3.7

2.2

3.9

2.2

43.3

2.9

2.1

2.9

2.0

3.1

2.1

3.3

2.1

3.4

2.2

3.6

2.2

3.8

2.2

20.0

4.2

3.0

4.4

3.0

4.7

3.1

4.9

3.0

5.0

3.1

5.5

3.1

5.7

3.2

22.8

4.2

2.9

4.3

2.9

4.6

3.0

4.8

3.0

5.0

3.1

5.3

3.1

5.6

3.1

25.0

4.1

2.9

4.3

2.9

4.5

3.0

4.7

3.0

4.9

3.1

5.2

3.0

5.5

3.1

27.8

4.0

2.9

4.2

2.9

4.4

2.9

4.6

2.9

4.8

3.0

5.2

3.0

5.5

3.1

30.0

3.9

2.8

4.1

2.8

4.3

2.9

4.5

2.9

4.7

3.0

5.0

3.0

5.4

3.0

32.8

3.9

2.8

4.0

2.8

4.3

2.9

4.5

2.9

4.6

2.9

4.9

2.9

5.2

3.0

35.0

3.8

2.8

4.0

2.8

4.2

2.8

4.4

2.8

4.5

2.9

4.9

2.9

5.1

2.9

37.8

3.8

2.7

3.9

2.7

4.1

2.8

4.3

2.8

4.4

2.9

4.8

2.8

5.0

2.9

40.0

3.7

2.7

3.8

2.7

4.0

2.7

4.3

2.8

4.4

2.8

4.7

2.8

4.9

2.9

43.3

3.6

2.6

3.7

2.6

3.9

2.7

4.1

2.7

4.2

2.8

4.6

2.8

4.8

2.8

20.0

5.1

3.7

5.3

3.7

5.7

3.8

5.9

3.7

6.1

3.9

6.6

3.9

6.9

3.9

22.8

5.0

3.6

5.2

3.6

5.5

3.7

5.8

3.7

6.0

3.8

6.4

3.8

6.8

3.8

25.0

5.0

3.6

5.1

3.6

5.5

3.7

5.7

3.6

5.9

3.8

6.3

3.7

6.7

3.8

27.8

4.9

3.5

5.0

3.5

5.3

3.6

5.6

3.6

5.8

3.7

6.2

3.7

6.7

3.8

30.0

4.8

3.5

5.0

3.5

5.2

3.6

5.4

3.5

5.6

3.7

6.1

3.6

6.5

3.7

32.8

4.7

3.4

4.8

3.4

5.2

3.5

5.4

3.5

5.5

3.6

6.0

3.6

6.3

3.7

35.0

4.6

3.4

4.8

3.4

5.0

3.5

5.3

3.5

5.5

3.6

5.9

3.6

6.2

3.6

37.8

4.5

3.4

4.7

3.4

5.0

3.4

5.2

3.4

5.4

3.6

5.8

3.5

6.1

3.6
3.5

40.0

4.5

3.3

4.6

3.3

4.8

3.4

5.1

3.4

5.3

3.5

5.6

3.5

5.9

43.3

4.3

3.3

4.4

3.2

4.7

3.3

5.0

3.3

5.1

3.4

5.5

3.4

5.8

3.5

20.0

6.8

4.7

7.0

4.7

7.5

4.8

7.8

4.8

8.0

4.9

8.7

4.9

9.1

5.0

22.8

6.6

4.6

6.9

4.6

7.3

4.8

7.6

4.7

7.9

4.9

8.5

4.9

8.9

4.9

25.0

6.6

4.6

6.8

4.6

7.2

4.7

7.5

4.7

7.8

4.8

8.3

4.8

8.8

4.8

27.8

6.4

4.5

6.7

4.5

7.1

4.6

7.3

4.6

7.6

4.8

8.2

4.7

8.8

4.9

30.0

6.3

4.5

6.6

4.5

6.9

4.6

7.2

4.5

7.5

4.7

8.0

4.7

8.5

4.7

32.8

6.2

4.4

6.4

4.4

6.8

4.5

7.1

4.5

7.3

4.6

7.9

4.6

8.3

4.7

35.0

6.1

4.3

6.3

4.3

6.7

4.4

7.0

4.4

7.2

4.6

7.7

4.5

8.2

4.6

37.8

6.0

4.3

6.2

4.3

6.6

4.4

6.9

4.4

7.1

4.5

7.6

4.5

8.0

4.5

40.0

5.9

4.3

6.0

4.2

6.4

4.3

6.8

4.3

7.0

4.5

7.4

4.4

7.8

4.5

43.3

5.7

4.2

5.9

4.1

6.2

4.2

6.6

4.2

6.8

4.4

7.3

4.3

7.6

4.4

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-108

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-4-2. Heating CapacityPUHY-P264~360T(S)HMU/Y(S)HMU with All Indoor Units


Model
size

06

08

12

15

18

24

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
1.2
1.2
1.2
1.2
1.4
1.4
1.4
1.4
1.6
1.6
1.6
1.5
1.9
1.8
1.7
1.5
2.0
1.9
1.7
1.5
2.1
2.0
1.7
1.5
2.2
2.0
1.7
1.5
2.3
2.0
1.7
1.5
2.4
2.0
1.7
1.5
2.4
2.0
1.7
1.5
2.4
2.0
1.7
1.5
1.6
1.6
1.6
1.5
1.9
1.8
1.8
1.8
2.1
2.1
2.1
2.0
2.4
2.3
2.2
2.0
2.6
2.5
2.2
2.0
2.8
2.6
2.2
2.0
2.9
2.6
2.2
2.0
3.0
2.6
2.2
2.0
3.1
2.6
2.2
2.0
3.1
2.6
2.2
2.0
3.1
2.6
2.2
2.0
2.4
2.4
2.4
2.3
2.9
2.8
2.8
2.7
3.3
3.2
3.2
3.0
3.7
3.6
3.3
3.0
4.0
3.8
3.3
3.0
4.3
4.0
3.3
3.0
4.4
4.0
3.3
3.0
4.6
4.0
3.3
3.0
4.8
4.0
3.3
3.0
4.8
4.0
3.3
3.0
4.8
4.0
3.3
3.0
3.0
3.0
3.0
2.9
3.6
3.5
3.5
3.4
4.1
4.0
4.0
3.8
4.7
4.4
4.1
3.8
5.0
4.7
4.1
3.8
5.3
5.0
4.1
3.8
5.5
5.0
4.1
3.8
5.8
5.0
4.1
3.8
6.0
5.0
4.1
3.8
6.0
5.0
4.1
3.8
6.0
5.0
4.1
3.8
3.6
3.6
3.5
3.5
4.2
4.1
4.1
4.0
4.9
4.7
4.7
4.5
5.5
5.2
4.9
4.5
5.9
5.6
4.9
4.5
6.3
5.9
4.9
4.5
6.5
5.9
4.9
4.5
6.8
5.9
4.9
4.5
7.1
5.9
4.9
4.5
7.1
5.9
4.9
4.5
7.1
5.9
4.9
4.5
4.8
4.8
4.7
4.6
5.6
5.5
5.5
5.4
6.5
6.3
6.3
6.0
6.0
7.4
7.0
6.5
7.9
7.5
6.5
6.0
8.4
7.9
6.5
6.0
8.8
7.9
6.5
6.0
9.1
7.9
6.5
6.0
9.5
7.9
6.5
6.0
9.5
7.9
6.5
6.0
9.5
7.9
6.5
6.0
5.3
5.3
5.3
5.2
6.3
6.1
6.1
6.0
7.3
7.0
7.0
6.7
8.2
7.8
7.3
6.7
8.8
8.3
7.3
6.7
9.4
8.8
7.3
6.7
9.8
8.8
7.3
6.7
10.1
8.8
7.3
6.7
10.5
8.8
7.3
6.7
10.5
8.8
7.3
6.7
10.5
8.8
7.3
6.7
kcal/h = kW x 860, BTU/h = kW x 3,412

Model
size

30

36

48

54

72

96

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
6.1
6.1
6.0
5.9
7.1
7.0
7.0
6.8
8.2
7.9
8.0
7.6
9.3
8.9
8.3
7.6
10.0
9.4
8.3
7.6
10.6
10.0
8.3
7.6
11.1
10.0
8.3
7.6
11.5
10.0
8.3
7.6
12.0
10.0
8.3
7.6
12.0
10.0
8.3
7.6
12.0
10.0
8.3
7.6
7.1
7.1
7.0
6.9
8.4
8.2
8.2
8.0
9.6
9.3
9.3
8.9
10.9
10.4
9.7
8.9
11.7
11.0
9.7
8.9
12.5
11.7
9.7
8.9
13.0
11.7
9.7
8.9
13.5
11.7
9.7
8.9
14.0
11.7
9.7
8.9
14.0
11.7
9.7
8.9
14.0
11.7
9.7
8.9
9.6
9.6
9.4
9.3
11.3
11.0
11.0
10.8
13.0
12.6
12.6
12.0
14.7
14.0
13.1
12.0
15.8
14.9
13.1
12.0
16.8
15.8
13.1
12.0
17.5
15.8
13.1
12.0
18.2
15.8
13.1
12.0
18.9
15.8
13.1
12.0
18.9
15.8
13.1
12.0
18.9
15.8
13.1
12.0
10.7
10.7
10.5
10.3
12.6
12.3
12.3
12.0
14.5
14.0
14.0
13.4
16.4
15.6
14.6
13.4
17.6
16.6
14.6
13.4
18.7
17.6
14.6
13.4
19.5
17.6
14.6
13.4
20.3
17.6
14.6
13.4
21.1
17.6
14.6
13.4
21.1
17.6
14.6
13.4
21.1
17.6
14.6
13.4
14.2
14.2
14.0
13.7
16.7
16.3
16.3
16.0
19.3
18.6
18.6
17.8
21.8
20.8
19.4
17.8
23.4
22.1
19.4
17.8
24.9
23.4
19.4
17.8
26.0
23.4
19.4
17.8
27.0
23.4
19.4
17.8
28.0
23.4
19.4
17.8
28.0
23.4
19.4
17.8
28.0
23.4
19.4
17.8
19.2
19.2
18.9
18.6
22.6
22.1
22.1
21.7
26.1
25.2
25.2
24.1
29.6
28.1
26.2
24.1
31.7
29.9
26.2
24.1
33.8
31.7
26.2
24.1
35.2
31.7
26.2
24.1
36.5
31.7
26.2
24.1
38.0
31.7
26.2
24.1
38.0
31.7
26.2
24.1
38.0
31.7
26.2
24.1
kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NOMINAL
CAPACITY
TABLES

27

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
18.0

NCT-109

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5. Cooing and Heating Capacity with PUMY-P36~48NHMU-A


2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PEFY-P-NMSU-E
CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

NOMINAL
CAPACITY
TABLES

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

26.7degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

19.4degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.8

1.5

1.9

1.6

1.9

1.6

2.0

1.6

2.1

1.6

2.2

SHC
1.6

22.8

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.6

1.9

1.6

2.1

1.6

2.2

1.6

25.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

1.9

1.6

2.0

1.6

2.1

1.6

27.8

1.6

1.5

1.7

1.5

1.8

1.6

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

30.0

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

32.8

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.9

1.6

2.0

1.6

2.1

1.6

35.0

1.5

1.5

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.6

1.9

1.6

2.1

1.6

37.8

1.5

1.5

1.6

1.4

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

40.0

1.5

1.4

1.5

1.4

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.5

2.0

1.6

43.3

1.4

1.4

1.5

1.4

1.6

1.5

1.7

1.5

1.7

1.5

1.9

1.5

2.0

1.6

20.0

2.2

2.0

2.3

2.0

2.5

2.0

2.5

2.0

2.6

2.1

2.7

2.1

2.9

2.1

22.8

2.2

2.0

2.3

2.0

2.4

2.0

2.5

2.0

2.6

2.1

2.7

2.0

2.9

2.1

25.0

2.2

2.0

2.3

1.9

2.4

2.0

2.5

2.0

2.5

2.1

2.7

2.0

2.8

2.1

27.8

2.2

1.9

2.2

1.9

2.4

2.0

2.4

2.0

2.5

2.1

2.7

2.0

2.8

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.5

2.1

2.6

2.0

2.8

2.1

32.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.0

2.4

2.0

2.6

2.0

2.7

2.1

35.0

2.0

1.9

2.1

1.9

2.3

2.0

2.3

1.9

2.4

2.0

2.6

2.0

2.7

2.1

37.8

2.0

1.9

2.1

1.9

2.2

1.9

2.3

1.9

2.4

2.0

2.5

2.0

2.7

2.0

40.0

2.0

1.8

2.0

1.8

2.2

1.9

2.3

1.9

2.3

2.0

2.5

2.0

2.7

2.0

43.3

1.9

1.8

2.0

1.8

2.1

1.9

2.2

1.9

2.3

2.0

2.5

2.0

2.6

2.0

20.0

3.4

2.6

3.5

2.6

3.7

2.7

3.8

2.7

3.9

2.8

4.1

2.7

4.3

2.8

22.8

3.3

2.6

3.4

2.6

3.7

2.7

3.8

2.6

3.9

2.7

4.1

2.7

4.3

2.7

25.0

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.6

3.8

2.7

4.0

2.7

4.3

2.7

27.8

3.2

2.6

3.4

2.6

3.6

2.6

3.7

2.6

3.8

2.7

4.0

2.7

4.2

2.7

30.0

3.2

2.6

3.3

2.5

3.5

2.6

3.6

2.6

3.7

2.7

3.9

2.6

4.2

2.7

32.8

3.1

2.5

3.2

2.5

3.5

2.6

3.6

2.6

3.7

2.7

3.9

2.6

4.1

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.5

3.6

2.6

3.9

2.6

4.1

2.7

37.8

3.0

2.5

3.1

2.5

3.4

2.6

3.5

2.5

3.6

2.6

3.8

2.6

4.0

2.7

40.0

2.9

2.4

3.1

2.4

3.3

2.5

3.4

2.5

3.5

2.6

3.8

2.6

4.0

2.6

43.3

2.9

2.4

3.0

2.4

3.2

2.5

3.3

2.5

3.5

2.6

3.7

2.5

3.9

2.6

20.0

4.2

3.2

4.4

3.1

4.6

3.2

4.8

3.2

4.9

3.3

5.2

3.2

5.4

3.3

22.8

4.2

3.1

4.3

3.1

4.6

3.2

4.7

3.2

4.8

3.3

5.1

3.2

5.4

3.3

25.0

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.1

4.8

3.3

5.0

3.2

5.3

3.2

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.1

4.7

3.2

5.0

3.2

5.3

3.2

30.0

4.0

3.1

4.1

3.0

4.4

3.1

4.5

3.1

4.7

3.2

4.9

3.1

5.2

3.2

32.8

3.9

3.0

4.1

3.0

4.3

3.1

4.5

3.1

4.6

3.2

4.9

3.1

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.3

3.1

4.4

3.0

4.5

3.2

4.8

3.1

5.1

3.2

37.8

3.8

2.9

3.9

2.9

4.2

3.0

4.3

3.0

4.5

3.1

4.8

3.1

5.1

3.1

40.0

3.7

2.9

3.8

2.9

4.1

3.0

4.3

3.0

4.4

3.1

4.7

3.1

5.0

3.1

43.3

3.6

2.9

3.7

2.9

4.0

3.0

4.2

2.9

4.3

3.1

4.6

3.0

4.9

3.1

20.0

5.1

3.9

5.2

3.9

5.5

4.0

5.7

3.9

5.9

4.1

6.2

4.0

6.5

4.1

22.8

5.0

3.9

5.2

3.8

5.5

4.0

5.6

3.9

5.8

4.1

6.1

4.0

6.4

4.0

25.0

4.9

3.8

5.1

3.8

5.4

3.9

5.6

3.9

5.7

4.0

6.1

3.9

6.4

4.0

27.8

4.9

3.8

5.0

3.8

5.3

3.9

5.5

3.9

5.7

4.0

6.0

3.9

6.3

4.0

30.0

4.8

3.8

5.0

3.8

5.3

3.9

5.4

3.8

5.6

4.0

5.9

3.9

6.2

4.0

32.8

4.7

3.7

4.9

3.7

5.2

3.8

5.4

3.8

5.5

3.9

5.9

3.9

6.2

4.0

35.0

4.6

3.7

4.8

3.7

5.1

3.8

5.3

3.8

5.4

3.9

5.8

3.8

6.1

3.9

37.8

4.5

3.6

4.7

3.6

5.0

3.8

5.2

3.7

5.4

3.9

5.7

3.8

6.1

3.9
3.9

40.0

4.4

3.6

4.6

3.6

4.9

3.7

5.1

3.7

5.3

3.9

5.7

3.8

6.0

43.3

4.3

3.5

4.5

3.5

4.8

3.7

5.0

3.7

5.2

3.8

5.5

3.8

5.9

3.9

20.0

6.7

5.1

6.9

5.1

7.4

5.3

7.6

5.2

7.8

5.4

8.2

5.3

8.7

5.4

22.8

6.6

5.1

6.9

5.1

7.3

5.2

7.5

5.2

7.7

5.3

8.1

5.2

8.6

5.3

25.0

6.6

5.1

6.8

5.0

7.2

5.2

7.4

5.1

7.6

5.3

8.1

5.2

8.5

5.3

27.8

6.5

5.0

6.7

5.0

7.1

5.2

7.3

5.1

7.5

5.3

8.0

5.2

8.4

5.3

30.0

6.4

5.0

6.6

5.0

7.0

5.1

7.2

5.0

7.4

5.2

7.9

5.1

8.3

5.2

32.8

6.3

4.9

6.5

4.9

6.9

5.1

7.1

5.0

7.3

5.2

7.8

5.1

8.2

5.2

35.0

6.1

4.9

6.4

4.8

6.8

5.0

7.0

5.0

7.2

5.1

7.7

5.1

8.1

5.2

37.8

6.0

4.8

6.2

4.8

6.7

5.0

6.9

4.9

7.1

5.1

7.6

5.0

8.1

5.2

40.0

5.9

4.7

6.1

4.7

6.6

4.9

6.8

4.9

7.0

5.1

7.5

5.0

8.0

5.1

43.3

5.7

4.7

6.0

4.7

6.4

4.9

6.7

4.8

6.9

5.0

7.4

4.9

7.8

5.1

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-110

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

18

24

27

30

36

21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

4.2

2.9

4.4

2.9

4.6

3.0

4.8

3.1

4.9

3.0

5.2

2.9

5.4

SHC
2.9

22.8

4.2

2.9

4.3

2.9

4.6

2.9

4.7

3.1

4.8

3.0

5.1

2.9

5.4

2.9

25.0

4.1

2.8

4.2

2.8

4.5

2.9

4.6

3.0

4.8

2.9

5.0

2.9

5.3

2.9

27.8

4.1

2.8

4.2

2.8

4.5

2.9

4.6

3.0

4.7

2.9

5.0

2.8

5.3

2.9

30.0

4.0

2.8

4.1

2.8

4.4

2.8

4.5

3.0

4.7

2.9

4.9

2.8

5.2

2.8

32.8

3.9

2.7

4.1

2.7

4.3

2.8

4.5

2.9

4.6

2.8

4.9

2.8

5.2

2.8

35.0

3.8

2.7

4.0

2.7

4.3

2.8

4.4

2.9

4.5

2.8

4.8

2.8

5.1

2.8

37.8

3.8

2.6

3.9

2.6

4.2

2.7

4.3

2.9

4.5

2.8

4.8

2.7

5.1

2.8

40.0

3.7

2.6

3.8

2.6

4.1

2.7

4.3

2.8

4.4

2.8

4.7

2.7

5.0

2.8

43.3

3.6

2.5

3.7

2.5

4.0

2.6

4.2

2.8

4.3

2.7

4.6

2.7

4.9

2.7

20.0

5.1

3.5

5.2

3.5

5.6

3.6

5.7

3.8

5.9

3.6

6.2

3.6

6.5

3.6

22.8

5.0

3.5

5.2

3.5

5.5

3.6

5.7

3.7

5.8

3.6

6.1

3.5

6.5

3.6

25.0

5.0

3.5

5.1

3.4

5.4

3.5

5.6

3.7

5.8

3.6

6.1

3.5

6.4

3.5

27.8

4.9

3.4

5.1

3.4

5.4

3.5

5.5

3.7

5.7

3.5

6.0

3.5

6.3

3.5

30.0

4.8

3.4

5.0

3.4

5.3

3.5

5.5

3.6

5.6

3.5

5.9

3.4

6.3

3.5

32.8

4.7

3.3

4.9

3.3

5.2

3.4

5.4

3.6

5.5

3.5

5.9

3.4

6.2

3.5

35.0

4.6

3.3

4.8

3.3

5.1

3.4

5.3

3.6

5.5

3.4

5.8

3.4

6.1

3.4

37.8

4.5

3.2

4.7

3.2

5.1

3.3

5.2

3.5

5.4

3.4

5.7

3.4

6.1

3.4

40.0

4.4

3.2

4.6

3.2

5.0

3.3

5.1

3.5

5.3

3.4

5.7

3.3

6.0

3.4

43.3

4.3

3.1

4.5

3.1

4.9

3.2

5.0

3.4

5.2

3.3

5.6

3.3

5.9

3.3

20.0

6.7

4.6

6.9

4.6

7.4

4.7

7.6

4.9

7.8

4.8

8.2

4.7

8.6

4.7

22.8

6.6

4.6

6.8

4.6

7.3

4.7

7.5

4.9

7.7

4.7

8.1

4.6

8.5

4.7

25.0

6.5

4.5

6.8

4.5

7.2

4.6

7.4

4.9

7.6

4.7

8.0

4.6

8.5

4.6

27.8

6.5

4.5

6.7

4.5

7.1

4.6

7.3

4.8

7.5

4.7

7.9

4.5

8.4

4.6

30.0

6.4

4.4

6.6

4.4

7.0

4.5

7.2

4.8

7.4

4.6

7.9

4.5

8.3

4.6

32.8

6.2

4.4

6.5

4.4

6.9

4.5

7.1

4.7

7.3

4.6

7.8

4.5

8.2

4.5

35.0

6.1

4.3

6.3

4.3

6.8

4.4

7.0

4.7

7.2

4.5

7.7

4.4

8.1

4.5

37.8

6.0

4.2

6.2

4.2

6.7

4.4

6.9

4.6

7.1

4.5

7.6

4.4

8.0

4.5

40.0

5.9

4.2

6.1

4.2

6.6

4.3

6.8

4.6

7.0

4.4

7.5

4.4

8.0

4.5

43.3

5.7

4.1

5.9

4.1

6.4

4.3

6.7

4.5

6.9

4.4

7.4

4.3

7.8

4.4

20.0

7.6

5.3

7.8

5.3

8.3

5.4

8.5

5.7

8.8

5.5

9.3

5.3

9.7

5.4

22.8

7.5

5.2

7.7

5.2

8.2

5.4

8.4

5.6

8.7

5.4

9.2

5.3

9.6

5.4

25.0

7.4

5.2

7.6

5.2

8.1

5.3

8.3

5.6

8.6

5.4

9.1

5.3

9.5

5.3

27.8

7.3

5.1

7.5

5.1

8.0

5.3

8.2

5.5

8.5

5.3

9.0

5.2

9.4

5.3

30.0

7.2

5.1

7.4

5.1

7.9

5.2

8.1

5.5

8.4

5.3

8.9

5.2

9.3

5.3

32.8

7.0

5.0

7.3

5.0

7.8

5.1

8.0

5.4

8.3

5.2

8.8

5.1

9.3

5.2

35.0

6.9

4.9

7.1

4.9

7.7

5.1

7.9

5.4

8.2

5.2

8.7

5.1

9.2

5.2

37.8

6.7

4.9

7.0

4.8

7.5

5.0

7.8

5.3

8.0

5.1

8.6

5.1

9.1

5.1

40.0

6.6

4.8

6.9

4.8

7.4

5.0

7.7

5.2

7.9

5.1

8.5

5.0

9.0

5.1

43.3

6.4

4.7

6.7

4.7

7.2

4.9

7.5

5.2

7.8

5.0

8.3

4.9

8.8

5.1

20.0

8.4

5.9

8.7

5.9

9.2

6.0

9.5

6.3

9.8

6.1

10.3

5.9

10.9

6.0

22.8

8.3

5.8

8.6

5.8

9.1

6.0

9.4

6.2

9.7

6.0

10.2

5.9

10.7

6.0

25.0

8.2

5.8

8.5

5.7

9.0

5.9

9.3

6.2

9.6

6.0

10.1

5.8

10.6

5.9

27.8

8.1

5.7

8.4

5.7

8.9

5.8

9.2

6.1

9.5

5.9

10.0

5.8

10.5

5.9

30.0

8.0

5.7

8.3

5.6

8.8

5.8

9.1

6.1

9.3

5.9

9.9

5.8

10.4

5.8

32.8

7.8

5.6

8.1

5.5

8.7

5.7

8.9

6.0

9.2

5.8

9.8

5.7

10.3

5.8

35.0

7.7

5.5

8.0

5.5

8.5

5.7

8.8

6.0

9.1

5.8

9.6

5.7

10.2

5.8

37.8

7.5

5.4

7.8

5.4

8.4

5.6

8.7

5.9

9.0

5.7

9.5

5.6

10.1

5.7

40.0

7.4

5.3

7.6

5.3

8.2

5.5

8.5

5.8

8.8

5.7

9.4

5.6

10.0

5.7

43.3

7.2

5.2

7.5

5.2

8.1

5.4

8.4

5.7

8.7

5.6

9.2

5.5

9.8

5.6

20.0

10.2

7.3

10.5

7.2

11.1

7.4

11.5

7.8

11.8

7.5

12.4

7.3

13.1

7.5

22.8

10.0

7.2

10.4

7.2

11.0

7.3

11.3

7.7

11.6

7.5

12.3

7.3

12.9

7.4

25.0

9.9

7.1

10.2

7.1

10.9

7.3

11.2

7.7

11.5

7.4

12.2

7.2

12.8

7.4

27.8

9.8

7.0

10.1

7.0

10.7

7.2

11.1

7.6

11.4

7.3

12.0

7.2

12.7

7.3

30.0

9.6

7.0

10.0

6.9

10.6

7.2

10.9

7.5

11.2

7.3

11.9

7.1

12.5

7.2

32.8

9.4

6.9

9.8

6.9

10.4

7.1

10.8

7.5

11.1

7.2

11.8

7.1

12.4

7.2

35.0

9.3

6.8

9.6

6.8

10.3

7.0

10.6

7.4

10.9

7.1

11.6

7.0

12.3

7.2

37.8

9.1

6.7

9.4

6.7

10.1

6.9

10.4

7.3

10.8

7.1

11.5

7.0

12.2

7.1

40.0

8.9

6.6

9.2

6.6

9.9

6.8

10.3

7.2

10.6

7.0

11.4

6.9

12.1

7.1

43.3

8.6

6.5

9.0

6.5

9.7

6.7

10.1

7.2

10.4

6.9

11.1

6.8

11.9

7.0

20.0

13.5

9.3

14.0

9.3

14.8

9.5

15.2

9.9

15.7

9.6

16.5

9.4

17.4

9.5

22.8

13.4

9.2

13.8

9.2

14.6

9.4

15.1

9.8

15.5

9.5

16.4

9.3

17.2

9.4

25.0

13.2

9.1

13.6

9.1

14.5

9.3

14.9

9.7

15.3

9.4

16.2

9.2

17.0

9.3

27.8

13.0

9.0

13.4

9.0

14.3

9.2

14.7

9.6

15.1

9.3

16.0

9.1

16.8

9.2

30.0

12.8

8.9

13.3

8.9

14.1

9.1

14.5

9.6

15.0

9.2

15.8

9.1

16.7

9.2

32.8

12.6

8.8

13.0

8.7

13.9

9.0

14.3

9.5

14.8

9.2

15.6

9.0

16.5

9.1

35.0

12.3

8.6

12.8

8.6

13.7

8.9

14.1

9.3

14.6

9.1

15.5

8.9

16.4

9.0

37.8

12.0

8.5

12.5

8.5

13.4

8.8

13.9

9.2

14.4

9.0

15.3

8.8

16.2

9.0

40.0

11.8

8.3

12.3

8.4

13.2

8.7

13.7

9.1

14.2

8.9

15.1

8.7

16.1

8.9

43.3

11.5

8.2

12.0

8.2

12.9

8.5

13.4

9.0

13.9

8.7

14.8

8.6

15.8

8.8

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-111

NOMINAL
CAPACITY
TABLES

48

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PEFY-P-NMHU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

54

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

15.2

10.7

15.6

10.7

16.6

11.0

17.1

11.5

17.6

11.1

18.5

10.8

19.5

11.0

22.8

15.0

10.6

15.5

10.6

16.4

10.9

16.9

11.4

17.4

11.0

18.3

10.8

19.3

10.9

25.0

14.8

10.5

15.2

10.5

16.2

10.8

16.7

11.3

17.2

10.9

18.1

10.7

19.1

10.8

27.8

14.6

10.4

15.1

10.4

16.0

10.7

16.5

11.2

17.0

10.8

17.9

10.6

18.9

10.8

30.0

14.4

10.3

14.9

10.3

15.8

10.6

16.3

11.1

16.8

10.7

17.7

10.5

18.7

10.7

32.8

14.1

10.2

14.6

10.1

15.6

10.4

16.1

11.0

16.5

10.6

17.5

10.4

18.5

10.6

35.0

13.8

10.0

14.3

10.0

15.3

10.3

15.8

10.9

16.3

10.5

17.3

10.3

18.3

10.5

37.8

13.5

9.9

14.0

9.8

15.1

10.2

15.6

10.8

16.1

10.4

17.1

10.3

18.2

10.5

40.0

13.2

9.7

13.7

9.7

14.8

10.1

15.3

10.7

15.9

10.3

16.9

10.2

18.0

10.4

43.3

12.9

9.5

13.4

9.5

14.5

9.9

15.0

10.5

15.5

10.2

16.6

10.1

17.7

10.3

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-112

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.4

2.0

1.4

2.1

1.4

2.2

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.0

1.4

2.1

1.3

2.2

1.4

25.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.1

1.3

2.2

1.4

27.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.4

2.0

1.3

2.2

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.3

2.0

1.3

2.1

1.3

32.8

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.4

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.4

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.4

1.8

1.3

2.0

1.3

2.1

1.3

40.0

1.5

1.2

1.6

1.2

1.7

1.3

1.7

1.4

1.8

1.3

1.9

1.3

2.1

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

20.0

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.8

2.6

1.7

2.7

1.6

2.8

1.7

22.8

2.2

1.6

2.2

1.6

2.4

1.6

2.5

1.7

2.5

1.7

2.7

1.6

2.8

1.7

25.0

2.2

1.6

2.2

1.6

2.4

1.6

2.4

1.7

2.5

1.7

2.6

1.6

2.8

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.5

1.6

2.6

1.6

2.7

1.6

30.0

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.7

2.4

1.6

2.6

1.6

2.7

1.6

32.8

2.0

1.5

2.1

1.5

2.3

1.6

2.3

1.7

2.4

1.6

2.6

1.6

2.7

1.6

35.0

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.7

2.4

1.6

2.5

1.6

2.7

1.6

37.8

2.0

1.5

2.0

1.5

2.2

1.6

2.3

1.7

2.3

1.6

2.5

1.6

2.6

1.6

40.0

1.9

1.5

2.0

1.5

2.2

1.5

2.2

1.6

2.3

1.6

2.5

1.6

2.6

1.6

43.3

1.9

1.5

2.0

1.5

2.1

1.5

2.2

1.6

2.3

1.6

2.4

1.5

2.6

1.6

20.0

3.4

2.4

3.5

2.3

3.7

2.4

3.8

2.5

3.9

2.4

4.1

2.4

4.3

2.4

22.8

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.5

3.8

2.4

4.1

2.4

4.3

2.4

25.0

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.5

3.8

2.4

4.0

2.3

4.2

2.4

27.8

3.2

2.3

3.3

2.3

3.5

2.3

3.7

2.5

3.8

2.4

4.0

2.3

4.2

2.4

30.0

3.2

2.3

3.3

2.2

3.5

2.3

3.6

2.4

3.7

2.3

3.9

2.3

4.1

2.3

32.8

3.1

2.2

3.2

2.2

3.4

2.3

3.6

2.4

3.7

2.3

3.9

2.3

4.1

2.3

35.0

3.1

2.2

3.2

2.2

3.4

2.3

3.5

2.4

3.6

2.3

3.8

2.3

4.1

2.3

37.8

3.0

2.2

3.1

2.2

3.3

2.2

3.4

2.4

3.6

2.3

3.8

2.2

4.0

2.3

40.0

2.9

2.1

3.0

2.1

3.3

2.2

3.4

2.3

3.5

2.3

3.7

2.2

4.0

2.3

43.3

2.9

2.1

3.0

2.1

3.2

2.2

3.3

2.3

3.4

2.2

3.7

2.2

3.9

2.2

20.0

4.2

3.2

4.4

3.2

4.6

3.3

4.8

3.5

4.9

3.3

5.2

3.3

5.4

3.3

22.8

4.2

3.2

4.3

3.1

4.6

3.2

4.7

3.4

4.8

3.3

5.1

3.2

5.4

3.3

25.0

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.4

4.8

3.3

5.0

3.2

5.3

3.3

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.4

4.7

3.3

5.0

3.2

5.3

3.3

30.0

4.0

3.1

4.1

3.1

4.4

3.2

4.5

3.4

4.7

3.2

4.9

3.2

5.2

3.2

32.8

3.9

3.0

4.1

3.0

4.3

3.1

4.5

3.3

4.6

3.2

4.9

3.1

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.3

3.1

4.4

3.3

4.5

3.2

4.8

3.1

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.2

3.1

4.3

3.3

4.5

3.2

4.8

3.1

5.1

3.2

40.0

3.7

2.9

3.8

2.9

4.1

3.0

4.3

3.2

4.4

3.1

4.7

3.1

5.0

3.2

43.3

3.6

2.9

3.7

2.9

4.0

3.0

4.2

3.2

4.3

3.1

4.6

3.1

4.9

3.1

20.0

5.1

3.8

5.2

3.7

5.6

3.8

5.7

4.1

5.9

3.9

6.2

3.8

6.5

3.9

22.8

5.0

3.7

5.2

3.7

5.5

3.8

5.7

4.0

5.8

3.9

6.1

3.8

6.5

3.9

25.0

5.0

3.7

5.1

3.7

5.4

3.8

5.6

4.0

5.8

3.9

6.1

3.8

6.4

3.8

27.8

4.9

3.7

5.1

3.6

5.4

3.8

5.5

4.0

5.7

3.8

6.0

3.8

6.3

3.8

30.0

4.8

3.6

5.0

3.6

5.3

3.7

5.5

4.0

5.6

3.8

5.9

3.7

6.3

3.8

32.8

4.7

3.6

4.9

3.6

5.2

3.7

5.4

3.9

5.5

3.8

5.9

3.7

6.2

3.8

35.0

4.6

3.5

4.8

3.5

5.1

3.7

5.3

3.9

5.5

3.7

5.8

3.7

6.1

3.8

37.8

4.5

3.5

4.7

3.5

5.1

3.6

5.2

3.8

5.4

3.7

5.7

3.6

6.1

3.7
3.7

40.0

4.4

3.4

4.6

3.4

5.0

3.6

5.1

3.8

5.3

3.7

5.7

3.6

6.0

43.3

4.3

3.4

4.5

3.4

4.9

3.5

5.0

3.8

5.2

3.6

5.6

3.6

5.9

3.7

20.0

6.7

5.0

6.9

4.9

7.4

5.1

7.6

5.3

7.8

5.2

8.2

5.0

8.6

5.1

22.8

6.6

4.9

6.8

4.9

7.3

5.0

7.5

5.3

7.7

5.1

8.1

5.0

8.5

5.1

25.0

6.5

4.9

6.8

4.8

7.2

5.0

7.4

5.3

7.6

5.1

8.0

5.0

8.5

5.1

27.8

6.5

4.8

6.7

4.8

7.1

4.9

7.3

5.2

7.5

5.0

7.9

4.9

8.4

5.0

30.0

6.4

4.8

6.6

4.8

7.0

4.9

7.2

5.2

7.4

5.0

7.9

4.9

8.3

5.0

32.8

6.2

4.7

6.5

4.7

6.9

4.9

7.1

5.1

7.3

5.0

7.8

4.9

8.2

5.0

35.0

6.1

4.6

6.3

4.6

6.8

4.8

7.0

5.1

7.2

4.9

7.7

4.8

8.1

4.9

37.8

6.0

4.6

6.2

4.6

6.7

4.7

6.9

5.1

7.1

4.9

7.6

4.8

8.0

4.9

40.0

5.9

4.5

6.1

4.5

6.6

4.7

6.8

5.0

7.0

4.8

7.5

4.8

8.0

4.9

43.3

5.7

4.4

5.9

4.4

6.4

4.6

6.7

4.9

6.9

4.8

7.4

4.7

7.8

4.8

20.0

7.6

5.5

7.8

5.5

8.3

5.6

8.5

5.9

8.8

5.7

9.3

5.6

9.7

5.7

22.8

7.5

5.5

7.7

5.4

8.2

5.6

8.4

5.9

8.7

5.7

9.2

5.5

9.6

5.6

25.0

7.4

5.4

7.6

5.4

8.1

5.5

8.3

5.8

8.6

5.6

9.1

5.5

9.5

5.6

27.8

7.3

5.3

7.5

5.3

8.0

5.5

8.2

5.8

8.5

5.6

9.0

5.5

9.4

5.6

30.0

7.2

5.3

7.4

5.3

7.9

5.4

8.1

5.8

8.4

5.5

8.9

5.4

9.3

5.5

32.8

7.0

5.2

7.3

5.2

7.8

5.4

8.0

5.7

8.3

5.5

8.8

5.4

9.3

5.5

35.0

6.9

5.2

7.1

5.1

7.7

5.3

7.9

5.6

8.2

5.4

8.7

5.3

9.2

5.5

37.8

6.7

5.1

7.0

5.1

7.5

5.3

7.8

5.6

8.0

5.4

8.6

5.3

9.1

5.4

40.0

6.6

5.0

6.9

5.0

7.4

5.2

7.7

5.5

7.9

5.3

8.5

5.3

9.0

5.4

43.3

6.4

4.9

6.7

4.9

7.2

5.1

7.5

5.5

7.8

5.3

8.3

5.2

8.8

5.3

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-113

NOMINAL
CAPACITY
TABLES

27

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PDFY-P-NMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

30

36

48

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

8.4

6.1

8.7

6.0

9.2

6.2

9.5

6.5

9.8

6.3

10.3

6.2

10.9

6.2

22.8

8.3

6.0

8.6

6.0

9.1

6.2

9.4

6.5

9.7

6.2

10.2

6.1

10.7

6.2

25.0

8.2

6.0

8.5

5.9

9.0

6.1

9.3

6.4

9.6

6.2

10.1

6.1

10.6

6.2

27.8

8.1

5.9

8.4

5.9

8.9

6.0

9.2

6.4

9.5

6.2

10.0

6.0

10.5

6.1

30.0

8.0

5.8

8.3

5.8

8.8

6.0

9.1

6.3

9.3

6.1

9.9

6.0

10.4

6.1

32.8

7.8

5.8

8.1

5.7

8.7

5.9

8.9

6.3

9.2

6.0

9.8

5.9

10.3

6.0

35.0

7.7

5.7

8.0

5.7

8.5

5.9

8.8

6.2

9.1

6.0

9.6

5.9

10.2

6.0

37.8

7.5

5.6

7.8

5.6

8.4

5.8

8.7

6.1

9.0

5.9

9.5

5.8

10.1

6.0

40.0

7.4

5.5

7.6

5.5

8.2

5.7

8.5

6.1

8.8

5.9

9.4

5.8

10.0

5.9

43.3

7.2

5.4

7.5

5.4

8.1

5.6

8.4

6.0

8.7

5.8

9.2

5.7

9.8

5.9

20.0

10.2

7.5

10.5

7.5

11.1

7.7

11.5

8.1

11.8

7.8

12.4

7.6

13.1

7.8
7.7

22.8

10.0

7.4

10.4

7.4

11.0

7.6

11.3

8.1

11.6

7.8

12.3

7.6

12.9

25.0

9.9

7.4

10.2

7.3

10.9

7.6

11.2

8.0

11.5

7.7

12.2

7.5

12.8

7.7

27.8

9.8

7.3

10.1

7.3

10.7

7.5

11.1

7.9

11.4

7.6

12.0

7.5

12.7

7.6

30.0

9.6

7.2

10.0

7.2

10.6

7.4

10.9

7.9

11.2

7.6

11.9

7.4

12.5

7.6

32.8

9.4

7.1

9.8

7.1

10.4

7.4

10.8

7.8

11.1

7.5

11.8

7.4

12.4

7.5

35.0

9.3

7.1

9.6

7.0

10.3

7.3

10.6

7.7

10.9

7.5

11.6

7.3

12.3

7.5

37.8

9.1

7.0

9.4

6.9

10.1

7.2

10.4

7.7

10.8

7.4

11.5

7.3

12.2

7.5

40.0

8.9

6.9

9.2

6.9

9.9

7.1

10.3

7.6

10.6

7.3

11.4

7.2

12.1

7.4

43.3

8.6

6.8

9.0

6.8

9.7

7.0

10.1

7.5

10.4

7.2

11.1

7.1

11.9

7.3

20.0

13.5

9.7

14.0

9.6

14.8

9.9

15.2

10.4

15.7

10.0

16.5

9.8

17.4

9.9

22.8

13.4

9.6

13.8

9.5

14.6

9.8

15.1

10.3

15.5

9.9

16.4

9.7

17.2

9.8

25.0

13.2

9.5

13.6

9.4

14.5

9.7

14.9

10.2

15.3

9.8

16.2

9.6

17.0

9.8

27.8

13.0

9.4

13.4

9.3

14.3

9.6

14.7

10.1

15.1

9.8

16.0

9.5

16.8

9.7

30.0

12.8

9.3

13.3

9.2

14.1

9.5

14.5

10.0

15.0

9.7

15.8

9.5

16.7

9.6

32.8

12.6

9.1

13.0

9.1

13.9

9.4

14.3

9.9

14.8

9.6

15.6

9.4

16.5

9.6

35.0

12.3

9.0

12.8

9.0

13.7

9.3

14.1

9.8

14.6

9.5

15.5

9.3

16.4

9.5

37.8

12.0

8.9

12.5

8.9

13.4

9.2

13.9

9.7

14.4

9.4

15.3

9.3

16.2

9.5

40.0

11.8

8.7

12.3

8.7

13.2

9.1

13.7

9.6

14.2

9.3

15.1

9.2

16.1

9.4

43.3

11.5

8.6

12.0

8.6

12.9

9.0

13.4

9.5

13.9

9.2

14.8

9.1

15.8

9.3

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-114

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PMFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.5

1.8

1.5

1.9

1.6

1.9

1.7

2.0

1.6

2.1

1.6

2.2

SHC
1.6

22.8

1.7

1.5

1.8

1.5

1.9

1.6

1.9

1.7

2.0

1.6

2.1

1.6

2.2

1.6

25.0

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.7

2.0

1.6

2.1

1.6

2.2

1.6

27.8

1.7

1.5

1.7

1.5

1.8

1.6

1.9

1.7

1.9

1.6

2.0

1.6

2.2

1.6

30.0

1.6

1.5

1.7

1.5

1.8

1.6

1.9

1.7

1.9

1.6

2.0

1.6

2.1

1.6

32.8

1.6

1.5

1.7

1.5

1.8

1.5

1.8

1.7

1.9

1.6

2.0

1.6

2.1

1.6

35.0

1.6

1.5

1.6

1.5

1.7

1.5

1.8

1.7

1.9

1.6

2.0

1.6

2.1

1.6

37.8

1.5

1.5

1.6

1.5

1.7

1.5

1.8

1.6

1.8

1.6

2.0

1.6

2.1

1.6

40.0

1.5

1.4

1.6

1.4

1.7

1.5

1.7

1.6

1.8

1.6

1.9

1.5

2.1

1.6

43.3

1.5

1.4

1.5

1.4

1.6

1.5

1.7

1.6

1.8

1.6

1.9

1.5

2.0

1.6

20.0

2.2

1.9

2.3

1.8

2.4

1.9

2.5

2.1

2.6

2.0

2.7

1.9

2.8

2.0

22.8

2.2

1.8

2.2

1.8

2.4

1.9

2.5

2.0

2.5

2.0

2.7

1.9

2.8

2.0

25.0

2.2

1.8

2.2

1.8

2.4

1.9

2.4

2.0

2.5

1.9

2.6

1.9

2.8

2.0

27.8

2.1

1.8

2.2

1.8

2.3

1.9

2.4

2.0

2.5

1.9

2.6

1.9

2.7

1.9

30.0

2.1

1.8

2.2

1.8

2.3

1.9

2.4

2.0

2.4

1.9

2.6

1.9

2.7

1.9

32.8

2.0

1.8

2.1

1.8

2.3

1.9

2.3

2.0

2.4

1.9

2.6

1.9

2.7

1.9

35.0

2.0

1.8

2.1

1.8

2.2

1.8

2.3

2.0

2.4

1.9

2.5

1.9

2.7

1.9

37.8

2.0

1.7

2.0

1.7

2.2

1.8

2.3

2.0

2.3

1.9

2.5

1.9

2.6

1.9

40.0

1.9

1.7

2.0

1.7

2.2

1.8

2.2

1.9

2.3

1.9

2.5

1.8

2.6

1.9

43.3

1.9

1.7

2.0

1.7

2.1

1.8

2.2

1.9

2.3

1.9

2.4

1.8

2.6

1.9

20.0

3.4

2.4

3.5

2.4

3.7

2.5

3.8

2.6

3.9

2.5

4.1

2.5

4.3

2.5

22.8

3.3

2.4

3.4

2.4

3.6

2.5

3.7

2.6

3.8

2.5

4.1

2.5

4.3

2.5

25.0

3.3

2.4

3.4

2.4

3.6

2.4

3.7

2.6

3.8

2.5

4.0

2.4

4.2

2.5

27.8

3.2

2.4

3.3

2.4

3.5

2.4

3.7

2.6

3.8

2.5

4.0

2.4

4.2

2.5

30.0

3.2

2.3

3.3

2.3

3.5

2.4

3.6

2.5

3.7

2.5

3.9

2.4

4.1

2.4

32.8

3.1

2.3

3.2

2.3

3.4

2.4

3.6

2.5

3.7

2.4

3.9

2.4

4.1

2.4

35.0

3.1

2.3

3.2

2.3

3.4

2.4

3.5

2.5

3.6

2.4

3.8

2.4

4.1

2.4

37.8

3.0

2.2

3.1

2.2

3.3

2.3

3.4

2.5

3.6

2.4

3.8

2.3

4.0

2.4

40.0

2.9

2.2

3.0

2.2

3.3

2.3

3.4

2.5

3.5

2.4

3.7

2.3

4.0

2.4

43.3

2.9

2.2

3.0

2.2

3.2

2.3

3.3

2.4

3.4

2.3

3.7

2.3

3.9

2.4

20.0

4.2

3.0

4.4

3.0

4.6

3.0

4.8

3.2

4.9

3.1

5.2

3.0

5.4

3.1

22.8

4.2

3.0

4.3

2.9

4.6

3.0

4.7

3.2

4.8

3.1

5.1

3.0

5.4

3.0

25.0

4.1

2.9

4.2

2.9

4.5

3.0

4.6

3.1

4.8

3.0

5.0

3.0

5.3

3.0

27.8

4.1

2.9

4.2

2.9

4.5

3.0

4.6

3.1

4.7

3.0

5.0

2.9

5.3

3.0

30.0

4.0

2.9

4.1

2.9

4.4

2.9

4.5

3.1

4.7

3.0

4.9

2.9

5.2

3.0

32.8

3.9

2.8

4.1

2.8

4.3

2.9

4.5

3.1

4.6

3.0

4.9

2.9

5.2

2.9

35.0

3.8

2.8

4.0

2.8

4.3

2.9

4.4

3.0

4.5

2.9

4.8

2.9

5.1

2.9

37.8

3.8

2.7

3.9

2.7

4.2

2.8

4.3

3.0

4.5

2.9

4.8

2.9

5.1

2.9

40.0

3.7

2.7

3.8

2.7

4.1

2.8

4.3

3.0

4.4

2.9

4.7

2.8

5.0

2.9

43.3

3.6

2.6

3.7

2.7

4.0

2.8

4.2

2.9

4.3

2.8

4.6

2.8

4.9

2.9

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-115

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PLFY-P-NCMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

08

12

15

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

2.2

2.0

2.3

1.9

2.4

2.0

2.5

2.2

2.6

2.1

2.7

2.0

2.8

SHC
2.1

22.8

2.2

1.9

2.2

1.9

2.4

2.0

2.5

2.2

2.5

2.1

2.7

2.0

2.8

2.1

25.0

2.2

1.9

2.2

1.9

2.4

2.0

2.4

2.2

2.5

2.1

2.6

2.0

2.8

2.1

27.8

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.1

2.5

2.0

2.6

2.0

2.7

2.1

30.0

2.1

1.9

2.2

1.9

2.3

2.0

2.4

2.1

2.4

2.0

2.6

2.0

2.7

2.1

32.8

2.0

1.9

2.1

1.9

2.3

2.0

2.3

2.1

2.4

2.0

2.6

2.0

2.7

2.0

35.0

2.0

1.9

2.1

1.9

2.2

1.9

2.3

2.1

2.4

2.0

2.5

2.0

2.7

2.0

37.8

2.0

1.8

2.0

1.8

2.2

1.9

2.3

2.1

2.3

2.0

2.5

2.0

2.6

2.0

40.0

1.9

1.8

2.0

1.8

2.2

1.9

2.2

2.1

2.3

2.0

2.5

2.0

2.6

2.0

43.3

1.9

1.8

2.0

1.8

2.1

1.9

2.2

2.1

2.3

2.0

2.4

1.9

2.6

2.0

20.0

3.4

2.6

3.5

2.6

3.7

2.7

3.8

2.8

3.9

2.7

4.1

2.7

4.3

2.7

22.8

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.8

3.8

2.7

4.1

2.7

4.3

2.7

25.0

3.3

2.6

3.4

2.6

3.6

2.6

3.7

2.8

3.8

2.7

4.0

2.6

4.2

2.7

27.8

3.2

2.5

3.3

2.5

3.5

2.6

3.7

2.8

3.8

2.7

4.0

2.6

4.2

2.7

30.0

3.2

2.5

3.3

2.5

3.5

2.6

3.6

2.8

3.7

2.7

3.9

2.6

4.1

2.7

32.8

3.1

2.5

3.2

2.5

3.4

2.6

3.6

2.8

3.7

2.6

3.9

2.6

4.1

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.7

3.6

2.6

3.8

2.6

4.1

2.6

37.8

3.0

2.4

3.1

2.4

3.3

2.5

3.4

2.7

3.6

2.6

3.8

2.6

4.0

2.6

40.0

2.9

2.4

3.0

2.4

3.3

2.5

3.4

2.7

3.5

2.6

3.7

2.5

4.0

2.6

43.3

2.9

2.4

3.0

2.4

3.2

2.5

3.3

2.7

3.4

2.6

3.7

2.5

3.9

2.6

20.0

4.2

3.1

4.4

3.0

4.6

3.1

4.8

3.3

4.9

3.2

5.2

3.1

5.4

3.2

22.8

4.2

3.0

4.3

3.0

4.6

3.1

4.7

3.3

4.8

3.2

5.1

3.1

5.4

3.1

25.0

4.1

3.0

4.2

3.0

4.5

3.1

4.6

3.2

4.8

3.1

5.0

3.1

5.3

3.1

27.8

4.1

3.0

4.2

3.0

4.5

3.0

4.6

3.2

4.7

3.1

5.0

3.0

5.3

3.1

30.0

4.0

2.9

4.1

2.9

4.4

3.0

4.5

3.2

4.7

3.1

4.9

3.0

5.2

3.1

32.8

3.9

2.9

4.1

2.9

4.3

3.0

4.5

3.2

4.6

3.1

4.9

3.0

5.2

3.0

35.0

3.8

2.9

4.0

2.9

4.3

3.0

4.4

3.1

4.5

3.0

4.8

3.0

5.1

3.0

37.8

3.8

2.8

3.9

2.8

4.2

2.9

4.3

3.1

4.5

3.0

4.8

2.9

5.1

3.0

40.0

3.7

2.8

3.8

2.8

4.1

2.9

4.3

3.1

4.4

3.0

4.7

2.9

5.0

3.0

43.3

3.6

2.7

3.7

2.7

4.0

2.9

4.2

3.0

4.3

2.9

4.6

2.9

4.9

3.0

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-116

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PLFY-P-NBMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

12

15

18

24

30

36

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

3.4

2.9

3.5

2.8

3.7

2.9

3.8

3.1

3.9

3.0

4.1

3.0

4.3

3.0

22.8

3.3

2.8

3.4

2.8

3.6

2.9

3.7

3.1

3.8

3.0

4.1

2.9

4.3

3.0
3.0

SHC

25.0

3.3

2.8

3.4

2.8

3.6

2.9

3.7

3.1

3.8

3.0

4.0

2.9

4.2

27.8

3.2

2.8

3.3

2.8

3.5

2.9

3.7

3.1

3.8

3.0

4.0

2.9

4.2

3.0

30.0

3.2

2.8

3.3

2.8

3.5

2.9

3.6

3.1

3.7

2.9

3.9

2.9

4.1

3.0
3.0

32.8

3.1

2.7

3.2

2.7

3.4

2.8

3.6

3.1

3.7

2.9

3.9

2.9

4.1

35.0

3.1

2.7

3.2

2.7

3.4

2.8

3.5

3.0

3.6

2.9

3.8

2.9

4.1

2.9

37.8

3.0

2.7

3.1

2.7

3.3

2.8

3.4

3.0

3.6

2.9

3.8

2.8

4.0

2.9
2.9

40.0

2.9

2.7

3.0

2.7

3.3

2.8

3.4

3.0

3.5

2.9

3.7

2.8

4.0

43.3

2.9

2.6

3.0

2.6

3.2

2.7

3.3

3.0

3.4

2.8

3.7

2.8

3.9

2.9

20.0

4.2

3.5

4.4

3.5

4.6

3.6

4.8

3.8

4.9

3.7

5.2

3.6

5.4

3.7
3.7

22.8

4.2

3.5

4.3

3.4

4.6

3.6

4.7

3.8

4.8

3.6

5.1

3.6

5.4

25.0

4.1

3.4

4.2

3.4

4.5

3.5

4.6

3.8

4.8

3.6

5.0

3.6

5.3

3.6

27.8

4.1

3.4

4.2

3.4

4.5

3.5

4.6

3.8

4.7

3.6

5.0

3.5

5.3

3.6

30.0

4.0

3.4

4.1

3.4

4.4

3.5

4.5

3.7

4.7

3.6

4.9

3.5

5.2

3.6

32.8

3.9

3.3

4.1

3.3

4.3

3.5

4.5

3.7

4.6

3.6

4.9

3.5

5.2

3.6

35.0

3.8

3.3

4.0

3.3

4.3

3.4

4.4

3.7

4.5

3.5

4.8

3.5

5.1

3.6

37.8

3.8

3.3

3.9

3.3

4.2

3.4

4.3

3.7

4.5

3.5

4.8

3.5

5.1

3.6

40.0

3.7

3.2

3.8

3.2

4.1

3.4

4.3

3.6

4.4

3.5

4.7

3.4

5.0

3.5
3.5

43.3

3.6

3.2

3.7

3.2

4.0

3.3

4.2

3.6

4.3

3.4

4.6

3.4

4.9

20.0

5.1

4.2

5.2

4.1

5.6

4.3

5.7

4.6

5.9

4.4

6.2

4.3

6.5

4.4

22.8

5.0

4.1

5.2

4.1

5.5

4.2

5.7

4.5

5.8

4.4

6.1

4.3

6.5

4.4
4.3

25.0

5.0

4.1

5.1

4.1

5.4

4.2

5.6

4.5

5.8

4.3

6.1

4.2

6.4

27.8

4.9

4.1

5.1

4.0

5.4

4.2

5.5

4.5

5.7

4.3

6.0

4.2

6.3

4.3

30.0

4.8

4.0

5.0

4.0

5.3

4.2

5.5

4.5

5.6

4.3

5.9

4.2

6.3

4.3

32.8

4.7

4.0

4.9

4.0

5.2

4.1

5.4

4.4

5.5

4.2

5.9

4.2

6.2

4.3

35.0

4.6

3.9

4.8

3.9

5.1

4.1

5.3

4.4

5.5

4.2

5.8

4.1

6.1

4.3
4.2

37.8

4.5

3.9

4.7

3.9

5.1

4.1

5.2

4.4

5.4

4.2

5.7

4.1

6.1

40.0

4.4

3.9

4.6

3.9

5.0

4.0

5.1

4.3

5.3

4.2

5.7

4.1

6.0

4.2

43.3

4.3

3.8

4.5

3.8

4.9

4.0

5.0

4.3

5.2

4.1

5.6

4.1

5.9

4.2

20.0

6.7

5.1

6.9

5.1

7.4

5.2

7.6

5.6

7.8

5.3

8.2

5.2

8.6

5.3

22.8

6.6

5.1

6.8

5.0

7.3

5.2

7.5

5.5

7.7

5.3

8.1

5.2

8.5

5.3

25.0

6.5

5.0

6.8

5.0

7.2

5.2

7.4

5.5

7.6

5.3

8.0

5.2

8.5

5.3

27.8

6.5

5.0

6.7

5.0

7.1

5.1

7.3

5.4

7.5

5.2

7.9

5.1

8.4

5.2

30.0

6.4

4.9

6.6

4.9

7.0

5.1

7.2

5.4

7.4

5.2

7.9

5.1

8.3

5.2

32.8

6.2

4.9

6.5

4.9

6.9

5.0

7.1

5.4

7.3

5.2

7.8

5.1

8.2

5.2

35.0

6.1

4.8

6.3

4.8

6.8

5.0

7.0

5.3

7.2

5.1

7.7

5.0

8.1

5.1

37.8

6.0

4.8

6.2

4.7

6.7

4.9

6.9

5.3

7.1

5.1

7.6

5.0

8.0

5.1

40.0

5.9

4.7

6.1

4.7

6.6

4.9

6.8

5.2

7.0

5.0

7.5

5.0

8.0

5.1

43.3

5.7

4.6

5.9

4.6

6.4

4.8

6.7

5.2

6.9

5.0

7.4

4.9

7.8

5.0

20.0

8.4

6.1

8.7

6.1

9.2

6.3

9.5

6.6

9.8

6.4

10.3

6.2

10.9

6.3

22.8

8.3

6.1

8.6

6.0

9.1

6.2

9.4

6.6

9.7

6.3

10.2

6.2

10.7

6.3

25.0

8.2

6.0

8.5

6.0

9.0

6.2

9.3

6.5

9.6

6.3

10.1

6.1

10.6

6.2

27.8

8.1

6.0

8.4

5.9

8.9

6.1

9.2

6.5

9.5

6.2

10.0

6.1

10.5

6.2

30.0

8.0

5.9

8.3

5.9

8.8

6.1

9.1

6.4

9.3

6.2

9.9

6.1

10.4

6.2

32.8

7.8

5.8

8.1

5.8

8.7

6.0

8.9

6.4

9.2

6.1

9.8

6.0

10.3

6.1

35.0

7.7

5.7

8.0

5.7

8.5

5.9

8.8

6.3

9.1

6.1

9.6

6.0

10.2

6.1

37.8

7.5

5.7

7.8

5.7

8.4

5.9

8.7

6.2

9.0

6.0

9.5

5.9

10.1

6.1

40.0

7.4

5.6

7.6

5.6

8.2

5.8

8.5

6.2

8.8

6.0

9.4

5.9

10.0

6.0

43.3

7.2

5.5

7.5

5.5

8.1

5.7

8.4

6.1

8.7

5.9

9.2

5.8

9.8

6.0

20.0

10.2

7.8

10.5

7.8

11.1

8.0

11.5

8.5

11.8

8.2

12.4

8.0

13.1

8.2
8.1

22.8

10.0

7.8

10.4

7.7

11.0

8.0

11.3

8.5

11.6

8.1

12.3

8.0

12.9

25.0

9.9

7.7

10.2

7.7

10.9

7.9

11.2

8.4

11.5

8.1

12.2

7.9

12.8

8.1

27.8

9.8

7.6

10.1

7.6

10.7

7.8

11.1

8.3

11.4

8.0

12.0

7.9

12.7

8.0

30.0

9.6

7.6

10.0

7.5

10.6

7.8

10.9

8.3

11.2

8.0

11.9

7.8

12.5

8.0

32.8

9.4

7.5

9.8

7.4

10.4

7.7

10.8

8.2

11.1

7.9

11.8

7.8

12.4

7.9

35.0

9.3

7.4

9.6

7.4

10.3

7.6

10.6

8.2

10.9

7.8

11.6

7.7

12.3

7.9

37.8

9.1

7.3

9.4

7.3

10.1

7.6

10.4

8.1

10.8

7.8

11.5

7.7

12.2

7.8

40.0

8.9

7.2

9.2

7.2

9.9

7.5

10.3

8.0

10.6

7.7

11.4

7.6

12.1

7.8

43.3

8.6

7.1

9.0

7.1

9.7

7.4

10.1

7.9

10.4

7.6

11.1

7.5

11.9

7.7

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL
CAPACITY
TABLES

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-117

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PCFY-P-NGMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

15

24

30

36

Indoor air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

20.0

4.2

3.2

4.4

3.2

4.6

3.3

4.8

3.5

4.9

3.3

5.2

3.3

5.4

3.3

22.8

4.2

3.2

4.3

3.1

4.6

3.2

4.7

3.4

4.8

3.3

5.1

3.2

5.4

3.3

25.0

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.4

4.8

3.3

5.0

3.2

5.3

3.3

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.4

4.7

3.3

5.0

3.2

5.3

3.3

30.0

4.0

3.1

4.1

3.1

4.4

3.2

4.5

3.4

4.7

3.2

4.9

3.2

5.2

3.2

32.8

3.9

3.0

4.1

3.0

4.3

3.1

4.5

3.3

4.6

3.2

4.9

3.1

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.3

3.1

4.4

3.3

4.5

3.2

4.8

3.1

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.2

3.1

4.3

3.3

4.5

3.2

4.8

3.1

5.1

3.2

40.0

3.7

2.9

3.8

2.9

4.1

3.0

4.3

3.2

4.4

3.1

4.7

3.1

5.0

3.2
3.1

43.3

3.6

2.9

3.7

2.9

4.0

3.0

4.2

3.2

4.3

3.1

4.6

3.1

4.9

20.0

6.7

5.0

6.9

4.9

7.4

5.1

7.6

5.3

7.8

5.2

8.2

5.0

8.6

5.1

22.8

6.6

4.9

6.8

4.9

7.3

5.0

7.5

5.3

7.7

5.1

8.1

5.0

8.5

5.1
5.1

25.0

6.5

4.9

6.8

4.8

7.2

5.0

7.4

5.3

7.6

5.1

8.0

5.0

8.5

27.8

6.5

4.8

6.7

4.8

7.1

4.9

7.3

5.2

7.5

5.0

7.9

4.9

8.4

5.0

30.0

6.4

4.8

6.6

4.8

7.0

4.9

7.2

5.2

7.4

5.0

7.9

4.9

8.3

5.0

32.8

6.2

4.7

6.5

4.7

6.9

4.9

7.1

5.1

7.3

5.0

7.8

4.9

8.2

5.0

35.0

6.1

4.6

6.3

4.6

6.8

4.8

7.0

5.1

7.2

4.9

7.7

4.8

8.1

4.9

37.8

6.0

4.6

6.2

4.6

6.7

4.7

6.9

5.1

7.1

4.9

7.6

4.8

8.0

4.9

40.0

5.9

4.5

6.1

4.5

6.6

4.7

6.8

5.0

7.0

4.8

7.5

4.8

8.0

4.9

43.3

5.7

4.4

5.9

4.4

6.4

4.6

6.7

4.9

6.9

4.8

7.4

4.7

7.8

4.8

20.0

8.4

6.1

8.7

6.0

9.2

6.2

9.5

6.5

9.8

6.3

10.3

6.2

10.9

6.2

22.8

8.3

6.0

8.6

6.0

9.1

6.2

9.4

6.5

9.7

6.2

10.2

6.1

10.7

6.2

25.0

8.2

6.0

8.5

5.9

9.0

6.1

9.3

6.4

9.6

6.2

10.1

6.1

10.6

6.2

27.8

8.1

5.9

8.4

5.9

8.9

6.0

9.2

6.4

9.5

6.2

10.0

6.0

10.5

6.1

30.0

8.0

5.8

8.3

5.8

8.8

6.0

9.1

6.3

9.3

6.1

9.9

6.0

10.4

6.1

32.8

7.8

5.8

8.1

5.7

8.7

5.9

8.9

6.3

9.2

6.0

9.8

5.9

10.3

6.0

35.0

7.7

5.7

8.0

5.7

8.5

5.9

8.8

6.2

9.1

6.0

9.6

5.9

10.2

6.0

37.8

7.5

5.6

7.8

5.6

8.4

5.8

8.7

6.1

9.0

5.9

9.5

5.8

10.1

6.0

40.0

7.4

5.5

7.6

5.5

8.2

5.7

8.5

6.1

8.8

5.9

9.4

5.8

10.0

5.9

43.3

7.2

5.4

7.5

5.4

8.1

5.6

8.4

6.0

8.7

5.8

9.2

5.7

9.8

5.9

20.0

10.2

7.5

10.5

7.5

11.1

7.7

11.5

8.1

11.8

7.8

12.4

7.6

13.1

7.8
7.7

22.8

10.0

7.4

10.4

7.4

11.0

7.6

11.3

8.1

11.6

7.8

12.3

7.6

12.9

25.0

9.9

7.4

10.2

7.3

10.9

7.6

11.2

8.0

11.5

7.7

12.2

7.5

12.8

7.7

27.8

9.8

7.3

10.1

7.3

10.7

7.5

11.1

7.9

11.4

7.6

12.0

7.5

12.7

7.6

30.0

9.6

7.2

10.0

7.2

10.6

7.4

10.9

7.9

11.2

7.6

11.9

7.4

12.5

7.6

32.8

9.4

7.1

9.8

7.1

10.4

7.4

10.8

7.8

11.1

7.5

11.8

7.4

12.4

7.5

35.0

9.3

7.1

9.6

7.0

10.3

7.3

10.6

7.7

10.9

7.5

11.6

7.3

12.3

7.5

37.8

9.1

7.0

9.4

6.9

10.1

7.2

10.4

7.7

10.8

7.4

11.5

7.3

12.2

7.5

40.0

8.9

6.9

9.2

6.9

9.9

7.1

10.3

7.6

10.6

7.3

11.4

7.2

12.1

7.4

43.3

8.6

6.8

9.0

6.8

9.7

7.0

10.1

7.5

10.4

7.2

11.1

7.1

11.9

7.3

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-118

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PKFY-P-NAMU/NGMU/NFMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.4

2.0

1.4

2.1

1.4

2.2

SHC
1.4

22.8

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.0

1.4

2.1

1.3

2.2

1.4

25.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.4

2.1

1.3

2.2

1.4

27.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.4

2.0

1.3

2.2

1.4

30.0

1.6

1.3

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.3

2.0

1.3

2.1

1.3

32.8

1.6

1.3

1.7

1.3

1.8

1.3

1.8

1.4

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.4

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.4

1.8

1.3

2.0

1.3

2.1

1.3

40.0

1.5

1.2

1.6

1.2

1.7

1.3

1.7

1.4

1.8

1.3

1.9

1.3

2.1

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

20.0

2.2

1.7

2.3

1.7

2.4

1.7

2.5

1.8

2.6

1.7

2.7

1.7

2.8

1.7

22.8

2.2

1.6

2.2

1.6

2.4

1.7

2.5

1.8

2.5

1.7

2.7

1.7

2.8

1.7

25.0

2.2

1.6

2.2

1.6

2.4

1.7

2.4

1.8

2.5

1.7

2.6

1.7

2.8

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.8

2.5

1.7

2.6

1.7

2.7

1.7

30.0

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.8

2.4

1.7

2.6

1.7

2.7

1.7

32.8

2.0

1.6

2.1

1.6

2.3

1.6

2.3

1.7

2.4

1.7

2.6

1.6

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.7

2.5

1.6

2.7

1.7

37.8

2.0

1.5

2.0

1.5

2.2

1.6

2.3

1.7

2.3

1.6

2.5

1.6

2.6

1.7

40.0

1.9

1.5

2.0

1.5

2.2

1.6

2.2

1.7

2.3

1.6

2.5

1.6

2.6

1.6

43.3

1.9

1.5

2.0

1.5

2.1

1.6

2.2

1.7

2.3

1.6

2.4

1.6

2.6

1.6

20.0

3.4

2.7

3.5

2.7

3.7

2.7

3.8

2.9

3.9

2.8

4.1

2.7

4.3

2.8

22.8

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.9

3.8

2.8

4.1

2.7

4.3

2.8

25.0

3.3

2.6

3.4

2.6

3.6

2.7

3.7

2.9

3.8

2.8

4.0

2.7

4.2

2.8

27.8

3.2

2.6

3.3

2.6

3.5

2.7

3.7

2.9

3.8

2.7

4.0

2.7

4.2

2.8

30.0

3.2

2.6

3.3

2.6

3.5

2.7

3.6

2.8

3.7

2.7

3.9

2.7

4.1

2.7

32.8

3.1

2.6

3.2

2.5

3.4

2.6

3.6

2.8

3.7

2.7

3.9

2.7

4.1

2.7

35.0

3.1

2.5

3.2

2.5

3.4

2.6

3.5

2.8

3.6

2.7

3.8

2.6

4.1

2.7

37.8

3.0

2.5

3.1

2.5

3.3

2.6

3.4

2.8

3.6

2.7

3.8

2.6

4.0

2.7

40.0

2.9

2.5

3.0

2.5

3.3

2.6

3.4

2.8

3.5

2.7

3.7

2.6

4.0

2.7

43.3

2.9

2.4

3.0

2.4

3.2

2.5

3.3

2.7

3.4

2.6

3.7

2.6

3.9

2.7

20.0

4.2

3.2

4.4

3.2

4.6

3.3

4.8

3.5

4.9

3.4

5.2

3.3

5.4

3.3

22.8

4.2

3.2

4.3

3.2

4.6

3.3

4.7

3.5

4.8

3.3

5.1

3.3

5.4

3.3

25.0

4.1

3.2

4.2

3.1

4.5

3.2

4.6

3.4

4.8

3.3

5.0

3.2

5.3

3.3

27.8

4.1

3.1

4.2

3.1

4.5

3.2

4.6

3.4

4.7

3.3

5.0

3.2

5.3

3.3

30.0

4.0

3.1

4.1

3.1

4.4

3.2

4.5

3.4

4.7

3.3

4.9

3.2

5.2

3.3

32.8

3.9

3.1

4.1

3.1

4.3

3.2

4.5

3.4

4.6

3.2

4.9

3.2

5.2

3.2

35.0

3.8

3.0

4.0

3.0

4.3

3.1

4.4

3.3

4.5

3.2

4.8

3.2

5.1

3.2

37.8

3.8

3.0

3.9

3.0

4.2

3.1

4.3

3.3

4.5

3.2

4.8

3.1

5.1

3.2

40.0

3.7

2.9

3.8

2.9

4.1

3.1

4.3

3.3

4.4

3.2

4.7

3.1

5.0

3.2

43.3

3.6

2.9

3.7

2.9

4.0

3.0

4.2

3.2

4.3

3.1

4.6

3.1

4.9

3.2

20.0

5.1

4.1

5.2

4.0

5.6

4.2

5.7

4.5

5.9

4.3

6.2

4.2

6.5

4.3

22.8

5.0

4.0

5.2

4.0

5.5

4.2

5.7

4.4

5.8

4.3

6.1

4.2

6.5

4.3

25.0

5.0

4.0

5.1

4.0

5.4

4.1

5.6

4.4

5.8

4.2

6.1

4.1

6.4

4.2

27.8

4.9

4.0

5.1

4.0

5.4

4.1

5.5

4.4

5.7

4.2

6.0

4.1

6.3

4.2

30.0

4.8

3.9

5.0

3.9

5.3

4.1

5.5

4.4

5.6

4.2

5.9

4.1

6.3

4.2

32.8

4.7

3.9

4.9

3.9

5.2

4.0

5.4

4.3

5.5

4.1

5.9

4.1

6.2

4.2

35.0

4.6

3.9

4.8

3.8

5.1

4.0

5.3

4.3

5.5

4.1

5.8

4.0

6.1

4.1

37.8

4.5

3.8

4.7

3.8

5.1

4.0

5.2

4.2

5.4

4.1

5.7

4.0

6.1

4.1
4.1

40.0

4.4

3.8

4.6

3.8

5.0

3.9

5.1

4.2

5.3

4.1

5.7

4.0

6.0

43.3

4.3

3.7

4.5

3.7

4.9

3.9

5.0

4.2

5.2

4.0

5.6

4.0

5.9

4.1

20.0

6.7

5.1

6.9

5.0

7.4

5.2

7.6

5.5

7.8

5.3

8.2

5.2

8.6

5.3

22.8

6.6

5.0

6.8

5.0

7.3

5.1

7.5

5.5

7.7

5.2

8.1

5.1

8.5

5.2

25.0

6.5

5.0

6.8

4.9

7.2

5.1

7.4

5.4

7.6

5.2

8.0

5.1

8.5

5.2

27.8

6.5

4.9

6.7

4.9

7.1

5.1

7.3

5.4

7.5

5.2

7.9

5.1

8.4

5.2

30.0

6.4

4.9

6.6

4.9

7.0

5.0

7.2

5.3

7.4

5.1

7.9

5.0

8.3

5.1

32.8

6.2

4.8

6.5

4.8

6.9

5.0

7.1

5.3

7.3

5.1

7.8

5.0

8.2

5.1

35.0

6.1

4.8

6.3

4.7

6.8

4.9

7.0

5.2

7.2

5.0

7.7

5.0

8.1

5.1

37.8

6.0

4.7

6.2

4.7

6.7

4.9

6.9

5.2

7.1

5.0

7.6

4.9

8.0

5.0

40.0

5.9

4.6

6.1

4.6

6.6

4.8

6.8

5.2

7.0

5.0

7.5

4.9

8.0

5.0

43.3

5.7

4.6

5.9

4.6

6.4

4.8

6.7

5.1

6.9

4.9

7.4

4.8

7.8

5.0

20.0

8.4

6.8

8.7

6.8

9.2

7.0

9.5

7.4

9.8

7.1

10.3

7.0

10.9

7.1

22.8

8.3

6.7

8.6

6.7

9.1

6.9

9.4

7.4

9.7

7.1

10.2

7.0

10.7

7.1

25.0

8.2

6.7

8.5

6.7

9.0

6.9

9.3

7.4

9.6

7.1

10.1

6.9

10.6

7.1

27.8

8.1

6.6

8.4

6.6

8.9

6.8

9.2

7.3

9.5

7.0

10.0

6.9

10.5

7.0

30.0

8.0

6.6

8.3

6.6

8.8

6.8

9.1

7.3

9.3

7.0

9.9

6.8

10.4

7.0

32.8

7.8

6.5

8.1

6.5

8.7

6.7

8.9

7.2

9.2

6.9

9.8

6.8

10.3

7.0

35.0

7.7

6.4

8.0

6.4

8.5

6.7

8.8

7.2

9.1

6.9

9.6

6.8

10.2

6.9

37.8

7.5

6.4

7.8

6.3

8.4

6.6

8.7

7.1

9.0

6.8

9.5

6.7

10.1

6.9

40.0

7.4

6.3

7.6

6.3

8.2

6.5

8.5

7.0

8.8

6.8

9.4

6.7

10.0

6.9

43.3

7.2

6.2

7.5

6.2

8.1

6.5

8.4

7.0

8.7

6.7

9.2

6.6

9.8

6.8

kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NCT-119

NOMINAL
CAPACITY
TABLES

30

Entering air temp.

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-1. Cooling CapacityPUMY-P36~48NHMU-A with PFFY-P-NEMU/NRMU-E


CA : Capacity(kW) SHC : Sensible Heat Capacity(kW)
Model

Outdoor

size

air temp.

06

08

12

15

18

24

Entering air temp.


21.7degC D.B.

22.8degC D.B.

25degC D.B.

27.2degC D.B.

27.8degC D.B.

30degC D.B.

32.2degC D.B.

15degC W.B.

16.1degC W.B.

17.8degC W.B.

18.9degC W.B.

20degC W.B.

22.2degC W.B.

23.9degC W.B.

degC D.B.

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

SHC

CA

20.0

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.0

1.4

2.1

1.3

2.2

SHC
1.3

22.8

1.7

1.3

1.8

1.3

1.9

1.3

1.9

1.4

2.0

1.3

2.1

1.3

2.2

1.3

25.0

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.4

2.0

1.3

2.1

1.3

2.2

1.3

27.8

1.7

1.3

1.7

1.3

1.8

1.3

1.9

1.4

1.9

1.3

2.0

1.3

2.2

1.3

30.0

1.6

1.3

1.7

1.2

1.8

1.3

1.9

1.4

1.9

1.3

2.0

1.3

2.1

1.3

32.8

1.6

1.2

1.7

1.2

1.8

1.3

1.8

1.4

1.9

1.3

2.0

1.3

2.1

1.3

35.0

1.6

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.0

1.3

2.1

1.3

37.8

1.5

1.2

1.6

1.2

1.7

1.2

1.8

1.3

1.8

1.3

2.0

1.3

2.1

1.3

40.0

1.5

1.2

1.6

1.2

1.7

1.2

1.7

1.3

1.8

1.3

1.9

1.3

2.1

1.3

43.3

1.5

1.2

1.5

1.2

1.6

1.2

1.7

1.3

1.8

1.3

1.9

1.2

2.0

1.3

20.0

2.2

1.7

2.3

1.7

2.4

1.7

2.5

1.8

2.6

1.8

2.7

1.7

2.8

1.8

22.8

2.2

1.7

2.2

1.7

2.4

1.7

2.5

1.8

2.5

1.8

2.7

1.7

2.8

1.7

25.0

2.2

1.7

2.2

1.7

2.4

1.7

2.4

1.8

2.5

1.7

2.6

1.7

2.8

1.7

27.8

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.8

2.5

1.7

2.6

1.7

2.7

1.7

30.0

2.1

1.6

2.2

1.6

2.3

1.7

2.4

1.8

2.4

1.7

2.6

1.7

2.7

1.7

32.8

2.0

1.6

2.1

1.6

2.3

1.7

2.3

1.8

2.4

1.7

2.6

1.7

2.7

1.7

35.0

2.0

1.6

2.1

1.6

2.2

1.6

2.3

1.8

2.4

1.7

2.5

1.7

2.7

1.7

37.8

2.0

1.6

2.0

1.6

2.2

1.6

2.3

1.7

2.3

1.7

2.5

1.7

2.6

1.7

40.0

1.9

1.6

2.0

1.5

2.2

1.6

2.2

1.7

2.3

1.7

2.5

1.6

2.6

1.7

43.3

1.9

1.5

2.0

1.5

2.1

1.6

2.2

1.7

2.3

1.6

2.4

1.6

2.6

1.7

20.0

3.4

2.3

3.5

2.3

3.7

2.4

3.8

2.5

3.9

2.4

4.1

2.4

4.3

2.4

22.8

3.3

2.3

3.4

2.3

3.6

2.4

3.7

2.5

3.8

2.4

4.1

2.3

4.3

2.4

25.0

3.3

2.3

3.4

2.3

3.6

2.3

3.7

2.5

3.8

2.4

4.0

2.3

4.2

2.4

27.8

3.2

2.3

3.3

2.3

3.5

2.3

3.7

2.4

3.8

2.4

4.0

2.3

4.2

2.3

30.0

3.2

2.2

3.3

2.2

3.5

2.3

3.6

2.4

3.7

2.3

3.9

2.3

4.1

2.3

32.8

3.1

2.2

3.2

2.2

3.4

2.3

3.6

2.4

3.7

2.3

3.9

2.3

4.1

2.3

35.0

3.1

2.2

3.2

2.2

3.4

2.2

3.5

2.4

3.6

2.3

3.8

2.2

4.1

2.3

37.8

3.0

2.1

3.1

2.1

3.3

2.2

3.4

2.3

3.6

2.3

3.8

2.2

4.0

2.3

40.0

2.9

2.1

3.0

2.1

3.3

2.2

3.4

2.3

3.5

2.2

3.7

2.2

4.0

2.3

43.3

2.9

2.1

3.0

2.1

3.2

2.2

3.3

2.3

3.4

2.2

3.7

2.2

3.9

2.2

20.0

4.2

3.0

4.4

3.0

4.6

3.0

4.8

3.2

4.9

3.1

5.2

3.0

5.4

3.0

22.8

4.2

2.9

4.3

2.9

4.6

3.0

4.7

3.2

4.8

3.1

5.1

3.0

5.4

3.0

25.0

4.1

2.9

4.2

2.9

4.5

3.0

4.6

3.1

4.8

3.0

5.0

3.0

5.3

3.0

27.8

4.1

2.9

4.2

2.9

4.5

3.0

4.6

3.1

4.7

3.0

5.0

2.9

5.3

3.0

30.0

4.0

2.9

4.1

2.8

4.4

2.9

4.5

3.1

4.7

3.0

4.9

2.9

5.2

3.0

32.8

3.9

2.8

4.1

2.8

4.3

2.9

4.5

3.1

4.6

2.9

4.9

2.9

5.2

2.9

35.0

3.8

2.8

4.0

2.8

4.3

2.9

4.4

3.0

4.5

2.9

4.8

2.9

5.1

2.9

37.8

3.8

2.7

3.9

2.7

4.2

2.8

4.3

3.0

4.5

2.9

4.8

2.8

5.1

2.9

40.0

3.7

2.7

3.8

2.7

4.1

2.8

4.3

3.0

4.4

2.9

4.7

2.8

5.0

2.9

43.3

3.6

2.6

3.7

2.6

4.0

2.8

4.2

2.9

4.3

2.8

4.6

2.8

4.9

2.9

20.0

5.1

3.7

5.2

3.6

5.6

3.7

5.7

3.9

5.9

3.8

6.2

3.7

6.5

3.8

22.8

5.0

3.6

5.2

3.6

5.5

3.7

5.7

3.9

5.8

3.8

6.1

3.7

6.5

3.7

25.0

5.0

3.6

5.1

3.6

5.4

3.7

5.6

3.9

5.8

3.7

6.1

3.6

6.4

3.7

27.8

4.9

3.5

5.1

3.5

5.4

3.6

5.5

3.8

5.7

3.7

6.0

3.6

6.3

3.7

30.0

4.8

3.5

5.0

3.5

5.3

3.6

5.5

3.8

5.6

3.7

5.9

3.6

6.3

3.7

32.8

4.7

3.5

4.9

3.5

5.2

3.6

5.4

3.8

5.5

3.6

5.9

3.6

6.2

3.6

35.0

4.6

3.4

4.8

3.4

5.1

3.5

5.3

3.7

5.5

3.6

5.8

3.5

6.1

3.6

37.8

4.5

3.4

4.7

3.4

5.1

3.5

5.2

3.7

5.4

3.6

5.7

3.5

6.1

3.6
3.6

40.0

4.4

3.3

4.6

3.3

5.0

3.4

5.1

3.7

5.3

3.5

5.7

3.5

6.0

43.3

4.3

3.3

4.5

3.3

4.9

3.4

5.0

3.6

5.2

3.5

5.6

3.4

5.9

3.5

20.0

6.7

4.7

6.9

4.7

7.4

4.8

7.6

5.0

7.8

4.8

8.2

4.7

8.6

4.8

22.8

6.6

4.6

6.8

4.6

7.3

4.7

7.5

5.0

7.7

4.8

8.1

4.7

8.5

4.8

25.0

6.5

4.6

6.8

4.6

7.2

4.7

7.4

4.9

7.6

4.8

8.0

4.7

8.5

4.7

27.8

6.5

4.5

6.7

4.5

7.1

4.7

7.3

4.9

7.5

4.7

7.9

4.6

8.4

4.7

30.0

6.4

4.5

6.6

4.5

7.0

4.6

7.2

4.8

7.4

4.7

7.9

4.6

8.3

4.6

32.8

6.2

4.4

6.5

4.4

6.9

4.6

7.1

4.8

7.3

4.6

7.8

4.5

8.2

4.6

35.0

6.1

4.4

6.3

4.4

6.8

4.5

7.0

4.7

7.2

4.6

7.7

4.5

8.1

4.6

37.8

6.0

4.3

6.2

4.3

6.7

4.4

6.9

4.7

7.1

4.5

7.6

4.5

8.0

4.6

40.0

5.9

4.2

6.1

4.2

6.6

4.4

6.8

4.6

7.0

4.5

7.5

4.4

8.0

4.5

43.3

5.7

4.2

5.9

4.2

6.4

4.3

6.7

4.6

6.9

4.4

7.4

4.4

7.8

4.5

NOMINAL
CAPACITY
TABLES

kcal/h = kW x 860, BTU/h = kW x 3,412

NCT-120

NOMINAL CAPACITY TABLES (Feb. 2009)

2. NOMINAL Capacity Tables in CelSius

DATA U4

2-5-2. Heating CapacityPUMY-P36~48NHMU-A with All Indoor Units


Model
size

06

08

12

15

18

24

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 20.0degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
1.4
1.3
1.3
1.3
1.5
1.5
1.4
1.4
1.7
1.7
1.6
1.6
1.9
1.8
1.8
1.7
2.0
1.9
1.9
1.8
2.0
2.0
2.0
1.9
2.2
2.1
2.0
1.9
2.3
2.2
2.0
1.9
2.4
2.3
2.0
1.9
2.4
2.3
2.0
1.9
1.8
1.7
1.7
1.7
2.0
1.9
1.8
1.8
2.2
2.2
2.1
2.0
2.4
2.4
2.3
2.3
2.6
2.5
2.4
2.4
2.7
2.6
2.6
2.5
2.8
2.8
2.6
2.5
2.9
2.9
2.6
2.5
3.1
3.0
2.6
2.5
3.1
3.0
2.6
2.5
2.8
2.7
2.6
2.6
3.0
2.9
2.8
2.8
3.4
3.3
3.2
3.1
3.8
3.7
3.5
3.5
4.0
3.8
3.7
3.7
4.1
4.0
4.0
3.9
4.3
4.2
4.0
3.9
4.5
4.4
4.0
3.9
4.7
4.6
4.0
3.9
4.8
4.6
4.0
3.9
3.5
3.4
3.3
3.2
3.8
3.7
3.6
3.5
4.3
4.2
4.0
3.9
4.7
4.6
4.4
4.4
5.0
4.8
4.7
4.6
5.1
5.0
5.0
4.9
5.4
5.3
5.0
4.9
5.7
5.5
5.0
4.9
5.9
5.8
5.0
4.9
6.1
5.8
5.0
4.9
4.1
4.0
3.8
3.8
4.4
4.3
4.2
4.1
5.0
4.9
4.7
4.6
5.5
5.4
5.2
5.1
5.8
5.7
5.5
5.4
6.0
5.9
5.8
5.7
6.4
6.3
5.8
5.7
6.7
6.5
5.8
5.7
7.0
6.8
5.8
5.7
7.1
6.8
5.8
5.7
5.5
5.3
5.1
5.1
5.9
5.8
5.6
5.5
6.7
6.6
6.2
6.2
7.4
7.3
7.0
6.9
7.8
7.6
7.3
7.3
8.1
7.9
7.8
7.7
8.5
8.4
7.8
7.7
8.9
8.7
7.8
7.7
9.3
9.1
7.8
7.7
9.6
9.1
7.8
7.7
6.2
5.9
5.7
5.6
6.6
6.4
6.2
6.2
7.5
7.3
7.0
6.9
8.3
8.1
7.7
7.7
8.7
8.4
8.2
8.1
9.0
8.8
8.7
8.5
9.5
9.3
8.7
8.5
9.9
9.7
8.7
8.5
10.4
10.1
8.7
8.5
10.6
10.1
8.7
8.5
kcal/h = kW x 860, BTU/h = kW x 3,412

Model
size

30

36

48

54

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-

SHC : Sensible Heat Capacity(kW)


Entering air temp.
15.0degC D.B. 20.0degC D.B. 25.0degC D.B. 27.2degC D.B.
SHC
SHC
SHC
SHC
7.0
6.7
6.5
6.4
7.5
7.3
7.1
7.0
8.5
8.3
7.9
7.8
9.4
9.2
8.8
8.7
9.9
9.6
9.3
9.2
10.2
10.0
9.9
9.7
10.8
10.6
9.9
9.7
11.3
11.0
9.9
9.7
11.8
11.5
9.9
9.7
12.1
11.5
9.9
9.7
8.2
7.8
7.6
7.5
8.8
8.5
8.3
8.2
9.9
9.7
9.2
9.1
11.0
10.8
10.3
10.2
11.6
11.2
10.9
10.8
11.9
11.7
11.6
11.3
12.6
12.4
11.6
11.3
13.2
12.9
11.6
11.3
13.8
13.5
11.6
11.3
14.2
13.5
11.6
11.3
11.1
10.6
10.3
10.1
11.9
11.5
11.2
11.1
13.4
13.1
12.5
12.3
14.9
14.5
13.9
13.7
15.6
15.2
14.7
14.5
16.1
15.8
15.6
15.3
17.1
16.7
15.6
15.3
17.9
17.4
15.6
15.3
18.6
18.2
15.6
15.3
19.1
18.2
15.6
15.3
12.3
11.8
11.4
11.3
13.2
12.8
12.5
12.3
15.0
14.6
13.9
13.7
16.5
16.2
15.5
15.3
17.4
16.9
16.4
16.2
18.0
17.6
17.4
17.1
19.0
18.7
17.4
17.1
19.9
19.4
17.4
17.1
20.8
20.2
17.4
17.1
21.3
20.2
17.4
17.1
kcal/h = kW x 860, BTU/h = kW x 3,412

NOMINAL CAPACITY TABLES (Feb. 2009)

NOMINAL
CAPACITY
TABLES

27

Outdoor
air temp.
degC W.B.
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-15.0
-10.0
-5.0
0.0
3.0
6.0
8.0
10.0
13.0
16.0
-

NCT-121

DATA U4

LGH-F-RX3-E

2. Lossnay Principles..........................................................................................................................................ERV-2

2.1. Lossnay Energy Recovery Ventilatiors - Core...........................................................................ERV-2

2.2. Lossnay Construction..........................................................................................................................ERV-3

2.3. Calculation of Total Energy Recovery Efficiency....................................................................ERV-3

2.4. UNBALANCED AIRFLOW Correction......................................................................................................ERV-4

2.5. Lossnay Operation / VENTILATION MODES..........................................................................................ERV-4

2.6. Automatic Ventilation Switching - Bypass Damper Operation................................................ERV-5

2.7. Importance of Filters.............................................................................................................................ERV-5

2.8. Energy Recovery Ventilation Terminology..................................................................................ERV-7

3. Lossnay Models and Specifications.........................................................................................................ERV-8


LGH-F300RX3-E........................................................................................................................................................ERV-8
LGH-F470RX3-E......................................................................................................................................................ERV-10
LGH-F600RX3-E......................................................................................................................................................ERV-12
LGH-F1200RX3-E....................................................................................................................................................ERV-14
4. Wiring Diagrams...............................................................................................................................................ERV-16
5. Sound Analysis.................................................................................................................................................ERV-18

5.1. Sound Analysis........................................................................................................................................ERV-18

5.2. LGH-F-RX3-E NC Curves............................................................................................................................ERV-18

6. Fan Speed Control Considerations.........................................................................................................ERV-20


7. Installation........................................................................................................................................................ERV-20

7.1. Installation Diagrams...........................................................................................................................ERV-20


7.2. Alternate Installation for Lossnay.............................................................................................ERV-21

7.3. Selecting Duct Attachment Direction...........................................................................................ERV-22

7.4. Installation of Supplementary Fan Devices after Lossnay Unit......................................ERV-23

8. Electrical Installation................................................................................................................................ERV-23
9. System Control Examples...........................................................................................................................ERV-24

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-1

LGH-F-RX3-E

1. Comparison of Primary Building Ventilation Methods......................................................................ERV-2

DATA U4

LGH-F-RX3-E

1. Comparison of Primary Building Ventilation Methods


There are two main ventilation methods:
Centralized Ventilation Method
This is mainly used in large buildings, with the outside air
intake being installed in one machine room. For this method,
primary treatment of the outside air, such as energy recovery
and dust removal, is performed before distribution to the building duct system.

System operation with celiling cassette (recessed) air conditioner

Exhaust

Ceiling-cassette package air


conditioner or fan coil unit

Air exhaust
(stale air)

Air intake
(outside air)
Filters

Independent Zoned Ventilation Method


This is mainly used in small to medium-sized buildings,
with areas being ventilated using outside air intakes from
independent ventilation devices. The rate of use of this
method has recently increased as zone conditioning and
independent control have become more feasible.

Ceiling-recessed-type
Lossnay unit

Exhaust grill

Exhaust air
Outside air

Supply fan
Lossnay

Finished ceiling

Each unit

System operation with ducted air conditioner


Ceiling-embedded-type package
air conditioner or fan coil unit

Ceiling-recessedtype Lossnay

Exhaust grill

Exhaust air
Outside air
Finished ceiling

Independent operation with ceiling-suspended air conditioner


Ceiling-cassette or ceiling-suspended-type
package air conditioner or fan coil unit

Ceiling-mounted-type Lossnay or
ceiling-embedded-type Lossnay
Outside air
Exhaust air
Finished ceiling

2. LOSSNAY Principles
2.1. Lossnay Energy Recovery Ventilators Core
The sophisticated energy recovery technology of the LOSSNAY core is constructed from a specially treated cellulose membrane
separating cross-flow air passages with a corrugated structure for strength and durability. See below, right for an illustration of the
LOSSNAY core.

41F (5.2C)
Stale hot air (exhaust)

32F (0C)

Fresh air exhaust


(fresh heating/cooling air)

Stale air exhaust


(dirty indoor air)

Fresh cool air (outdoor)

68F (20C)
Stale warm air (indoor air)
Stale air induction
(dirty heating/cooling air)

Fresh air induction


(fresh air)

59F (14.8C)
Fresh warm air (indoor supply air)

CITY MULTI can integrate LOSSNAY ERVs into the air conditioning system, providing the best overall solution to ventilation
and air-conditioning.

Outdoor unit

Indoor unit

CENTRALIZED CONTROLLER AG-150A

Indoor unit

Centralized Controller
AG-150A

Remote controller

Lossnay

LOSSNAY Remote controller PZ-52SF-E


Performance Certified
to ARI 1060 Standard

Lineup of LOSSNAY ERV units


ERV-2

LGH-F-RX3-E (Feb. 2009) LGH-F300RX3-E

LGH-F470RX3-E
LGH-F600RX3-E

300 cfm
470 cfm
600 cfm

1-phase, 208/230V, 60Hz


1-phase, 208/230V, 60Hz
1-phase, 208/230V, 60Hz

Indoor unit

CENTRALIZED CONTROLLER AG-150A

Indoor unit

Lossnay

Centralized Controller
AG-150A

Remote controller

DATA U4

LOSSNAY Remote controller PZ-52SF-E

Lineup of LOSSNAY ERV units

2.2. Lossnay Construction

Lossnay ERVs are constructed so that the exhaust


air passage from the indoor side to the outdoor
side (RA EA) and the outside air passage from
the outdoor side to the indoor side (OA SA)
cross. The Lossnay energy recovery unit features
the Lossnay Core, which is installed at this cross
point and recovers the heat by conduction through
the separating medium between the airflows,
and latent energy by molecular transfer through
the separation plate driven by vapor pressure
differential between the airstreams. This enables
the total energy loss during exhaust to be greatly
reduced.

SA

300 cfm
470 cfm
600 cfm
1200 cfm

1-phase, 208/230V, 60Hz


1-phase, 208/230V, 60Hz
1-phase, 208/230V, 60Hz
1-phase, 208/230V, 60Hz

Lossnay Core

LGH-F-RX3-E

LGH-F300RX3-E
LGH-F470RX3-E
LGH-F600RX3-E
LGH-F1200RX3-E

EA

(Supply air diffuser)

(Exhaust air)

Exhaust fan

Supply fan

RA

OA

(Return air)

(Outside air)
Intake side filter

Exhaust side filter

Note: The duct inlet and outlet are arranged in-line


in the actual product.

SA = Supply Air; RA = Return Air


EA = Exhaust Air; OA = Outside Air

2.3. Calculation of Total Energy Recovery Efciency

The Lossnay Cores energy recovery efficiency can be considered using the following three transfer rates:
1. Temperature (sensible heat) recovery efficiency
2. Humidity (latent heat) recovery efficiency
3. Enthalpy (total heat) recovery efficiency
OUTDOORS
INDOORS
The energy recovery effect can be calculated if two of the
EA

above efficiencies are known. (Lossnay performance and


cost analysis can also be determined using Mitsubishi Electric Stale indoor
air exhaust
ERValue software.
Each recovery efficiency can be calculated with the formulas
in the table. 
Transmission
When the supply and exhaust air volumes are equal, the
plates
heat recovery efficiencies on the supply and exhaust sides
are the same.
When the supply and exhaust air volumes are not equal, the
total heat recovery efficiency is low if the exhaust volume is
lower, and high if the exhaust volume is higher. 

Item

Formula

[
[

Temperature recovery
efficiency (%)

t=

Enthalpy recovery
efficiency (%)

iOA - iSA
i = iOA - iRA

]
]

tOA - tSA
x 100
tOA - tRA
x 100

= Efficiency (%)
t = Dry Bulb
Temperature (F)
i = Enthalpy (Btu/lb)

ERV

Outside air intake

OA

SA
Supply
preconditioned
outside air to
AC system
Partition plates

Return stale indoor


air

RA

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-3

DATA U4

If the Lossnay energy recovery efficiency and the conditions


of the room and outdoor air are known, the conditions of the
air entering the room and the air exhausted outdoors can be
determined with the following formulas in the table.

Supply side

Exhaust side

Temperature

tSA = tOA - (tOA - t RA ) x t

tEA = tRA + (t OA - t RA ) x t

Enthalpy

iSA = i OA - (iOA - i RA ) x i

iEA = i RA + (i OA - i RA ) x i

2.4. Unbalanced Airflow Correction

In unbalanced applications, it is necessary to calculate the pressure


drops of the two air streams separately using the applicable chart
and correct the efficiencies using the instructions and the K-Factor
chart below.
(K-Factor)

1. In unbalanced airflow applications, the external


static pressure must be calculated for each air stream
separately using the ESP curves for the applicable
product.
2. The temperature effectiveness must also be
corrected using the K-Factor chart (at right).
A. Determine which correction factor to use by
calculating the K-Factor (Air Volume Ratio).
B. Determine the balanced airflow effectiveness
from the applicable product graphs using the outside
airflow (CFM).
C. Correct the effectiveness for the unbalanced
airflow by finding the Original Exchange Balanced
Efficiency (%), then find the appropriate K-Factor
Curve in the chart. From that point, read the
Corrected Exchange Efficiency (%) on the left side of
the chart.

Energy Recovery Efficiency Correction Curve


Energy Recovery
Efficiency (%)

(K-Factor)

100

1.4

1.3
1.2

1.1
1.0
0.9
Corrected Exchange Efficiency (%)

LGH-F-RX3-E

Calculation of Supply Air Condition After Passing Through Lossnay

0.8

0.7

0.6

0.5

Original Exchange Balanced Efficiency (%)

2.5. Lossnay Operation / Ventilation Modes


1. Energy Recovery Heat Exchange

2. Bypass No Exchange

Lossnay technology is a full enthalpic energy exchange that recovers both


sensible energy or heat recovery and latent energy or moisture transfer
between air streams.

3. Automatic Heat Exchange: Bypass


In cooling, the automatic mode
accomplishes an energy savings function.
When the inbound outside air is 7.2 F
cooler than the outbound exhaust air, the
bypass damper opens in the outbound
airstream. This increases airflow and
provides cooler air to the conditioned
space.
In heating, the automatic mode
may not be suitable without supply-air
preheating.
Performance Certified
to ARI 1060 Standard

ERV-4

LGH-F-RX3-E (Feb. 2009)

DATA U4

2.6. Automatic Ventilation Switching - Bypass Damper Operation


Effect of Automatic Ventilation Mode

LGH-F-RX3-E

The automatic damper mode automatically provides the correct ventilation for the conditions in the room. It eliminates the need for manual switch
operations when setting the Lossnay ventilator to bypass ventilation. The following shows the effect bypass ventilation will have under various
conditions. For automatic operation, when the air conditioning system is in the cooling mode, the bypass damper will open if the entering outside
air temperature is 7.2F or more lower than the exhaust air temperature.
(1) Reduces cooling load--If the air outside is cooler than the air inside the building during the cooling season (such as early morning or at night),
bypass ventilation will draw in the cooler outside air and reduce the cooling load on the system.
(2) Cooling using outdoor air--During cooler season (such as between spring and summer or between summer and fall), if the people in a room
cause the temperature of the room to rise, bypass ventilation will draw in the cool outside air and use it to cool the room.
(3) Night purge--Bypass ventilation can be used to release hot air from inside the building that has accumulated during the hot summer season.
(4) Office equipment room cooling--During the cold season, outdoor air can be drawn in to cool rooms where the temperature has risen due to the
use of office equipment. (Only when interlocked with CITY MULTI and Mr. Slim indoor units.)

2.7. Importance of Filters

2.7.1. Data Regarding Dust

Table 1 Aerosol particle diameters and applicable ranges of various filters

Table 2 Major dust concentrations

Type

Reference data

Remarks:

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-5

DATA U4

2.72. Calculation Table for Dust Collection Efficiency of each Lossnay Filter

LGH-F-RX3-E

Dust
Size
(m)*

MERV
Rating

6; 3.0-10.0 m
6.6-8.6 less than 49.9%

* Note: MERV rating is estimation from efficiency test data of AFI Gravitational method and ASHRAE Colorimetric method.

2.7.3. Pressure Loss


The pressure loss of the filter used within the Lossnay units is shown below, expressed in terms of collection ratio (%).

Performance Certified
to ARI 1060 Standard

ERV-6

LGH-F-RX3-E (Feb. 2009)

DATA U4

2.8. Energy Recovery Ventilation Terminology

CFM
Cubic Feet per Minute, a measure of air volume.
Delayed Operation
The On/Off operation of the Lossnay unit can
be delayed for 30 minutes following the operation of the indoor unit. When using PZ-41SLB-E,
the delay can be set for 10, 20, 30, 40, 50 and 60
minutes.
ESP
External static pressure, available motive force
to propel air in a duct system from a blower or
ventilator.
Enthalpy Exchange
The exchange of both sensible and latent heat
energy.
Exhaust Air (EA)
Air expelled from indoor space.
External Control Input
An On/Off input signal for operating the Lossnay
unit that can be sent from an external device. The
signal may be a 12V-24V DC or an uncharged
a-contact signal.
Interlocked Lossnay
Lossnay unit linked to City MultI or Mr. Slim
indoor units that receive signals and operates via
the indoor units remote controller.
Non-interlocked Lossnay
Lossnay unit controlled independently of
City Multi or Mr. Slim indoor units by the
Lossnay remote controller and/or centralized
controller.

Outdoor Air (OA)


Air drawn from outdoors - ventilation air.
Pulse Input
When the control signal
from an external device
outputs a pulse such as
the one shown at right,
200 ms or more
the pulse input control
is performed by the Lossnay unit. (Optional DIP
switch 2-2 ON) 200 ms or more.
Remote Operation
This is used for enabling/disabling the On/Off control signal from an external device and for setting
interlocked operation of the external device and the
Lossnay unit.
ON/OFF interlock: Enables both ON OFF and
OFF ON external signals.
ON interlock: Enables OFF ON external signal.
Disables ON OFF external signal.
OFF interlock: Enables ON OFF external signal. Disables OFF ON external signal.
External priority: Same as on/off interlock but the
OFF signal from the remote controller is ignored
when the external control signal is on.
Return Air (RA)
Air drawn from indoor space.
Supply Air (SA)
Air supplied to indoor space.
Ventilation Modes
Energy Recovery energy exchange through
Lossnay core at all times.
Bypass no exchange bypass damper open.
Automatic energy exchange or bypass as
determined by present temperature sensor in inlet
and discharge airstreams.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-7

LGH-F-RX3-E

Balanced Ventilation
A ventiliation strategy using both an exhaust air
blower and a supply or make-up air blower providing the same airflow and pressure so as not to
pressurize or depressurize a building.

DATA U4

3. LOSSNAY Models and Specifications

Model LGH-F300RX3-E
Position where duct direction change is possible
Damper plate

K
D

Air exhaust fan

Ceiling suspension fixture


RA
(return air)

B
J

EA
(exhaust air)

SA
(supply air)

Maintenance space for


heat exchanger, air
filters,and fans

7/8"

23-5/8" or more

OA
(outside air)
5-7/8" ~ 9-13/16"

K
Inspection
opening

Air supply fan

Control box
Maintenance cover

Energy exchanger (Lossnay core)


3-1/8"
A
K

3-1/8"

G
H

LGH-F-RX3-E

Model specifications and materials list for Lossnay units

Ceiling suspension fixture


Air filters

Dimensions
Unit
A

inches
mm

34-15/16
888

Ceiling suspension
fixture pitch
D
E
F

Nominal
diameter

Duct connecting
flange
G
H

40

12-1/2

31-1/8

41-1/4

1-9/16

7-9/16

1016

318

791

1048

40

203

192

Duct pitch
Weight
J

8-3/16

29-5/16

4-7/8

73 lb

208

745

124

33 kg

Model LGH-F300RX3-E Specifications Table

Performance Certified
to ARI 1060 Standard

ERV-8

LGH-F-RX3-E (Feb. 2009)

DATA U4

Model LGH-F300RX3-E Characteristic Curve

LGH-F-RX3-E

* Attention
1. The defrost mode must be operated at 14F or below.
2. The current, power consumption, and efficiency are based on the above air flow rate.
3. The sound at the air outlets are the values at a 45 angle, 59 in. in front of the unit.
4. Fan speed can be switched between high and low.
The main unit switch must be used to select the extra-high fan speed.
5. Air conditions as per ARI standard 1060-2005.
*Specifications may be subject to change without notice.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-9

DATA U4

Model LGH-F470RX3-E
Position where duct direction change is possible
Ceiling suspension fixture

Air exhaust fan

RA
(return air)

B
J
5-7/8" ~ 9-13/16"

EA
(exhaust air)

SA
(supply air)
7/8

Air supply fan

Inspection
opening

Control box
Maintenance cover

3-1/8

3-1/8

(79 mm)

(79 mm)

5-7/8

(149 mm)

G
H

Energy exchanger
(Lossnay core)

(22 mm)

23-5/8" or more

OA
(outside air)
Maintenance space for
heat exchanger, air
filters, and fans

3-9/16

(149-249 mm)

(149-249 mm)

Damper plate

(90 mm)

LGH-F-RX3-E

5-7/8
(149 mm)

Ceiling suspension fixture

Dimensions
Unit
A

inches
mm

45-13/16
1164

39-1/2 15-11/16
1003

398

Ceiling suspension
fixture pitch
D
E
F

40-9/16 40-13/16
1030

1037

Nominal
diameter

Air filters

Duct connecting
flange
G
H

3/8

10

9-1/2

9.5

254

241

Duct pitch
Weight
J

10-3/16 27-3/16
259

691

5-7/8

143 lb

149

65 kg

Model LGH-F470RX3-E Specifications Table

Performance Certified
to ARI 1060 Standard

ERV-10

LGH-F-RX3-E (Feb. 2009)

DATA U4

Model
ModelLGH-F470RX3-E
LGH-F470RX -E Characteristic Curve

LGH-F-RX3-E

* Attention
1. The defrost mode must be operated at 14F or below.
2. The current, power consumption, and efficiency are based on the above air flow rate.
3. The sound at the air outlets are the values at a 45 angle, 59 in. in front of the unit.
4. Fan speed can be switched between high and low.
The main unit switch must be used to select the extra-high fan speed.
5. Air conditions as per ARI standard 1060-2005.
*Specifications may be subject to change without notice.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-11

DATA U4

Model LGH-F600RX3-E

Model LGH-F600RX3-E
Position where duct direction change is possible
Damper plate

LGH-F-RX3-E

K
D

Air exhaust fan

Ceiling suspension fixture


RA
(return air)

B
J

EA
(exhaust air)

SA
(supply air)

(149-249 mm)

7/8"

K
Inspection
opening

(22 mm)

(600 mm or more)

23-5/8" or more

Maintenance space for


heat exchanger, air
filters, and fans

5-7/8" ~ 9-13/16"

OA
(outside air)

Air supply fan

Control box
Maintenance cover
3-1/8"
(79 mm)

G
H

Energy exchanger (Lossnay core)


3-1/8"
A
(79 mm)
K

Ceiling suspension fixture


Air filters

Dimensions
Unit
A

inches
mm

Ceiling suspension
fixture pitch
D
E
F

45-13/16 48-7/16 15-11/16 40-9/16


1164

1230

398

1030

Nominal
diameter

Duct connecting
flange
G
H

49-3/4

3/8

10

9-1/2

1264

9.5

254

241

Duct pitch
Weight
J

10-3/16 36-3/16
259

919

5-7/8

159 lb

149

72 kg

Model LGH-F600RX3-E Specifications Table

Performance Certified
to ARI 1060 Standard

ERV-12

LGH-F-RX3-E (Feb. 2009)

DATA U4

Model LGH-F600RX -E

Model LGH-F600RX3-E3Characteristic Curve

LGH-F-RX3-E

* Attention
1. The defrost mode must be operated at 14F or below.
2. The current, power consumption, and efficiency are based on the above air flow rate.
3. The sound at the air outlets are the values at a 45 angle, 59 in. in front of the unit.
4. Fan speed can be switched between high and low.
The main unit switch must be used to select the extra-high fan speed.
5. Air conditions as per ARI standard 1060-2005.
*Specifications may be subject to change without notice.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-13

DATA U4

Model LGH-F1200RX3-E

Model LGH-F1200RX3-E
Damper plate

LGH-F-RX3-E

Air exhaust fan

Ceiling suspension fixture

D
RA
(return air)
47"
E

B
29-1/8"

EA
(exhaust air)

OA
(outside air)
1"

Air supply fan

Inspection
opening

Control box
Maintenance cover

Maintenance space for Energy exchanger


heat exchanger,
(Lossnay core)
air filters,
and fans
5-1/8"
9-13/16"

A
45-13/16"

9-13/16"

F
C

inches
mm

5-1/8"

13-3/4"

LGH-F1200RX3-E has a double


circuit board and requires two
M-NET connections.

27-3/4"

23-5/8" or more

5-7/8" ~ 9-13/16"

SA
(supply air)

Ceiling suspension fixture


Power cord opening

Air filters

65-7/16

48-7/16

31-1/2

40-9/16

50-1/8

8-3/4

14

13-3/4

G
29- 1/8

395 lb

1164

1230

800

1030

1273

222

356

349

740

179 kg

Model LGH-F1200RX3-E Specifications Table


--Two addresses required.

Performance Certified
to ARI 1060 Standard

ERV-14

LGH-F-RX3-E (Feb. 2009)

DATA U4

Model LGH-F1200RX3-E

Model LGH-F1200RX3-E Characteristic Curve

LGH-F-RX3-E

* Attention
1. The defrost mode must be operated at 14F or below.
2. The current, power consumption, and efficiency are based on the above air flow rate.
3. The sound at the air outlets are the values at a 45 angle, 59 in. in front of the unit.
4. Fan speed can be switched between high and low.
The main unit switch must be used to select the extra-high fan speed.
5. Air conditions as per ARI standard 1060-2005.
*Specifications may be subject to change without notice.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-15

DATA U4

4. Wiring Diagrams
LGH-F-RX3-E

LGH-F300RX3-E, -F470RX3-E, -F600RX3-E


Dotted lines represent field-supplied wire.
Be sure to connect the ground wire.
Breaker should be provided by the
customer.
M1
M2
C
GM
LS
TH1
TH2
SW1
SW2,5
SW3

SW4

TM1
TM2


TM3

TB5

S1, S2
TR
X7

X8

CN1

CN2

CN5
CN6
CN7

CN8-1
CN8-2
CN9
CN10
CN16
CN32
SA1
SA2
LED1
LED2
LED4
LED6
MARK:


Motor for exhaust fan


Motor for supply fan
Capacitor
Motor for bypass movement
Microswitch
Thermistor for outside air
Thermistor for return air
Switch (Main/Sub change)
Switch (Function selection)
High/X-High select switch
(Exhaust fan)
M2
High/X-High select switch
SUPPLY
(Supply fan)
FAN MOTOR
Terminal block (Power supply)
Terminal block
(Transmission cable and
external control input)
Terminal block (Monitor
M1
output)
EXHAUST
Terminal block (M-NET
FAN MOTOR
Transmission cable)
Connector (Power supply)
Control circuit transformer
Relay contact (for operation
monitor output)
Relay contact (for
Operation monitor output
MIN.
malfunction monitor output) MAX.
AC240V 2A AC220V 100mA
Connector
DC 24V 2A DC 5V 100mA
(Transformer primary)
Connector
(Transformer secondary) Malfunction monitor output
Connector (Thermistor)
MAX.
MIN.
Connector (Microswitch) AC240V 1A AC220V 100mA
DC 24V 1A DC 5V 100mA
Connector
(Motor for bypass operation)
Tab connector (Fan motor)
Tab connector (Fan motor)
Connector (Fan motor)
Connector (Fan motor)
Connector (High/Low switch)
Connector (Remote control selection)
Address setting rotary switch (10 digit)
Address setting rotary switch (1 digit)
Inspection indicator lamp
Inspection indicator lamp
Power supply indicator lamp
M-NET indicator lamp
Indicates Terminal block
Connector
Board insertion connector or
fastening connector of control board

Power
Terminal
BROWN
GREEN/YELLOW

RED

CN8-1
CN10

BLACK
GREY
YELLOW

SW4

S1
250V6.3A

ZNR101

S2
3

ORANGE
BLUE
WHITE

CN1

1
HIGH

SW3

BLUE

C101

1 EXTRA
C HIGH

CN9

PE

ZNR102 DSA1 FUSE

3
HIGH

CIRCUIT BREAKER

TM1

CN8-2

5 1

1 EXTRA
HIGH

BROWN

L
N

POWER SUPPLY
220-240V ~ 50HZ
220V ~ 60HZ

WHITE
WHITE

YELLOWTR

CN7
6

GM
RED

LS

BROWN

CN2

10
9
8
7

CN16

CN32

TM3
7

SW2

SW1

CN5

SW5

CN6

SA1 SA2
TM2

1 2 3 4

5 6

12V or
24V DC
Mr. Slim
(nonpolar)
1

A B S

Transmission
cable

TB5

GREY
GREY
BLUE
BLUE
ORANGE

TH1 (OA)

TH2 (RA)

ORANGE

Shield wire

M-NET-transmission cable

PZ- Lossnay unit PZ41SLB-E Max.15 units 52SF-E

Uncharged
a-contact
External control input

BROWN

Control
Terminals

CN16
High

Uncharged
a-contact

Low

High/Lowselect connector

Note: CN16 is accessed using a PAC-715AD


3-wire connector.
Performance Certified
to ARI 1060 Standard

ERV-16

LGH-F-RX3-E (Feb. 2009)

DATA U4

LGH-F1200RX3-E

Note: The double control board for the


LGH-F12000RX has two M-NET addresses.

ORANGE

ORANGE

BROWN

BROWN

YELLOW

GREY
GREY
BLUE
BLUE

CN6
(TB5)

CN5

C101

(CN16)

CN2

WHITE
1
1

CN7

(CN32)

ZNR101

ZNR102 DSA1

CN1

S2

S1

FUSE
250V6.3A

CN8-2

TR

WHITE

BROWN
BLUE

RED

TH1 (OA) TH2 (RA)

S
B
A

SW1 (Subordination)
SA2

BROWN

6
5
4
3
2
1

SW5

(TM3)

(TM2)

HIGH

1 EXTRA
HIGH

1
5

CN9

SW2

ORANGE
BLUE
WHITE

CN10

SW3

BLACK
GREY
YELLOW

HIGH

SW4

1 EXTRA
HIGH

CN8-1

SA1

10 9

1
1

ORANGE

ORANGE

GREY
GREY
BLUE
BLUE

BROWN

RED

CN16

CN2

C101

CN7

CN6
TB5

CN5
CN32

ZNR101

ZNR102 DSA1

CN1

S2

S1
FUSE
250V6.3A

BROWN

BLUE

TR

YELLOW

BROWN

WHITE

WHITE

TH1 (OA) TH2 (RA)

S
B
A

SW1 (Main)
SA2

CN8-2

RED BROWN

TM3

SW5

10 9 8

6
5
4
3
2
1

TM2

1 EXTRA
HIGH

HIGH
5

CN9

SW2

SW3

ORANGE
BLUE
WHITE

CN10

HIGH

SW4

1 EXTRA
HIGH

CN8-1

SA1

BLACK
GREY
YELLOW

GREEN/YELLOW

TM1

TM2
L

PE

TB5
5

A B

Shield wire
Uncharged
a-contact

Operation monitor output


MAX.
MIN.
PZPZAC240V 2A AC220V 100mA
41SLB-E 52SF-E DC 24V 2A DC 5V 100mA

Transmissiion cable
Lossnay unit
Max. 7 units

Malfunction monitor output


MAX.
MIN.
AC240V 1A AC220V 100mA
DC 24V 1A DC 5V 100mA

12V or
24V DC
Mr. Slim
(nonpolar)
3

POWER SUPPLY L N
220 - 240V ~ 50HZ
220V ~ 60HZ
(Invalid in EU)

M-NET-transmissiion cable

LS
Motor for exhaust fan
GM
Motor for supply fan
Capacitor
Motor for bypass movement
Microswitch
Thermistor for outside air
Thermistor for return air
M1
Switch (Main/Sub change) SUPPLY
FAN MOTOR
Switch (Function selection)
High/X-High select switch
(Exhaust fan)
M2
High/X-High select switch
EXHAUST
FAN MOTOR
(Supply fan)
Terminal block (Power supply)
Terminal block
(Transmission cable and
external control input)
LS
Terminal block (Monitor
GM
output)
Terminal block (M-NET
Transmission cable)
Connector (Power supply)
SUPPLY
Control circuit transformer
FAN MOTOR
M2
Relay contact (for operation
monitor output)
Relay contact (for
EXHAUST
FAN MOTOR
malfunction monitor output)
M1
Connector
(Transformer primary)
Connector
(Transformer secondary)
Connector (Thermistor)
Connector (Microswitch)
Connector (Motor for
bypass operation)
Tab connector (Fan motor)
Tab connector (Fan motor)
Connector (Fan motor)
Connector (Fan motor)
Connector (High/Low switch)
Connector (Remote control selection)
Address setting rotary switch (10 digit)
Address setting rotary switch (1 digit)
Inspection indicator lamp
Inspection indicator lamp
Power supply indicator lamp
M-NET indicator lamp
Indicates Terminal block
Connector
Board insertion connector or
fastening connector of control board

RED

M1
M2
C
GM
LS
TH1
TH2
SW1
SW2,5
SW3

SW4

TM1
TM2


TM3

TB5

S1, S2
TR
X7

X8

CN1

CN2

CN5
CN6
CN7

CN8-1
CN8-2
CN9
CN10
CN16
CN32
SA1
SA2
LED1
LED2
LED4
LED6
MARK:


LGH-F-RX3-E

Dotted lines represent field-supplied wire.


Be sure to connect the ground wire.
Breaker should be provided by the
customer.

High Low

CN16

High/Low select connector

Uncharged
a-contact

External control input

Note: CN16 is accessed using a PAC-715AD


3-wire connectortwo required.
Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-17

DATA U4

5. Sound Analysis
The human ear senses differently according to frequency. However, sound generated from a vibration is not limited to one frequency but instead various frequencies are generated at different levels. This is expressed by the NC curve, which is determined according to the difficulty
of hearing a conversation. Even if the sound is a very low level, it is annoying if a specific frequency is emitted.These sounds are suppressed
to a minimum during product design stages, but the sound may become very disturbing with resonance of the ceiling, wall, etc.
Example Continuous frequency analysis

NC curve

Sound Pressure Level (dB)

LGH-F-RX3-E

5.1. Sound Analysis

Tolerable noise levels and NC values according to room application


Room application

dB

NC value

Room application

dB

NC value

5.2. LGH-F-RX3-E NC Curves


LGH-F300RX3

: Lossnay ventilation

5 ft. below

: Lossnay ventilation

5 ft. below

LGH-F470RX3

: Lossnay ventilation

5 ft. below

ERV-18

LGH-F-RX3-E (Feb. 2009)

: Lossnay ventilation

5 ft. below

Performance Certified
to ARI 1060 Standard

DATA U4

LGH-F470RX3

LGH-F-RX3-E

: Lossnay ventilation

: Lossnay ventilation

5 ft. below

5 ft. below

LGH-F600RX3

: Lossnay ventilation

: Lossnay ventilation

5 ft. below

5 ft. below

LGH-F1200RX33

Lossnay ventilation

Lossnay ventilation

5 ft. below

5 ft. below

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-19

DATA U4

LGH-F-RX3-E

6. Fan Speed Control Considerations


(1) The ceiling embedded type: 300, 470, 600 and 1200 CFM types are available. Select an adequate model according to the room size and air
volume for the application and sound levels.
(2) LGH units are supplied with two speed blowers. Speeds are LOW and either HIGH or EXTRA HIGH as selected. All types have an extrahigh speed. This setting is for a long duct run or when a large air volume is required. The positive and negative pressures of the room can also
be adjusted with dampers.
(3) The units have a low-sound design, however, for further sound reduction a silencer-type supply/return grille for supply/return air in the room, a
silencer box for reducing air sound into the room, and a flexible silencer should be used.

LGH-F300 F470 F600RX types

LGH-F1200RX type
Note: The double control board for the
LGH-F1200RX has two M-NET addresses.

7. Installation
7.1. Installation Diagrams
LGH- F300 F470 F600RX models
Installation diagram

on the air filter and Lossnay Core removal

Air volume (CFM)

Model

Dimensions
A

Always insulate the two ducts leading outside the building


(intake air and exhaust air ducts) to prevent condensation.

Performance Certified
to ARI 1060 Standard

ERV-20

LGH-F-RX3-E (Feb. 2009)

DATA U4

LGH- F1200RX model


Installation diagram

LGH-F-RX3-E

on the air filter and Lossnay Core removal

Always insulate the two ducts leading outside the


building (intake air and exhaust air ducts) to prevent
condensation.

Air volume (CFM)

Model

1200

LGH-F1200RX type

Dimensions
A

7.2. Alternate Installation for Lossnay


T op/bottom reverse installation
All LGH-RX models can be installed in top/bottom
reverse.

Vertical installation patterns


Vertical installation is possible, but the
installation pattern is limited for some
models. Refer to the examples shown for
installation patterns.

Special Note
The LGH-RX model was originally
designed for being embedded in
the ceiling. Vertical installation
is not normally desirable for
installation and maintenance.

Precautions

Slanted installation
Slanted installation is not recommended.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-21

DATA U4

7.3. Selecting Duct Attachment Direction

LGH-F-RX3-E

Choose between two directions for the outside duct (OA, EA) piping direction for optimum installation.

Installation and maintenance

condensation.

A centralized controller can also be used.

Installation applications

Performance Certified
to ARI 1060 Standard

ERV-22

LGH-F-RX3-E (Feb. 2009)

DATA U4

7.4. Installation of Supplementary Fan Devices After Lossnay Unit

LGH-F-RX3-E

(See chart, bottom right.)


Q-H for Lossnay without extra fan

Q-H for Lossnay with extra fan


Lossnay with extra fan

Static Pressure

Static Pressure

Lossnay
specfication curve

out

Lossnay
specfication curve

Extra fan
specification curve

Air Volume

Air Volume

8. Electrical Installation
With this product, the wiring installation method will vary according to the design of the system. Perform electrical installation for each of the required
sections. Observe local codes and the National Electric Code directives.

Names of components in control box

Ground

Bushing

Bushing

Ground
Bushing
Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-23

9. System Control Examples

DATA U4

Basic System Stand-alone Lossnay ERV with PZ-41SLB-E Remote Controller

Multiple Lossnay units with one remote controller

One Lossnay with one remote controller

LGH-F-RX3-E

Non-polar
2 wires

Non-polar
2 wires

Lossnay

Lossnay

Lossnay
Power supply

(Sub)
Remote controller
PZ-41SLB-E

Power supply

Up to 15 Lossnay units can be controlled at


one time with one remote controller.

One Lossnay unit is operated independently with


one remote controller.

Two remote controlle

Power supply

Remote
controller
PZ-41SLB-E

Remote controller
PZ-41SLB-E

Non-polar
2 wires

(Main)
Lossnay

Power supply

Two remote controller system with one Lossnay

The Lossnay can be controlled from two remote


locations.
The remote controller gives priority to the last
touch.

Rem
P

It is also possible to o
multiple Lossnay uni

Operation with Mr. Slim


Operating with external device

Operating with Mr. Slim (A-control) - Interlocked


Lossnay

Lossnay

Non-polar
two wires
Power supply

PAR-21MAA
Remote
controller

Power supply

Remote controller
PZ-41SLB-E

Power supply
Mr. Slim
(indoor unit)

Selection of interlocked operation


mode is possible.
Delayed start interlocked operation is
possible.

Power supply

Interlocking multiple
When the operat

Lossnay

Power s

Indoor unit
Remote controller
The operation of the Lossnay will be connected with the operation or
stopping of the external device.
Input of level signal or pulse signal (12V DC, 24V DC, uncharged acontact) is possible.

The Remote controller (A-control) controls the air conditioning device and
the Lossnay. It is possible to operate or switch fan speed for the
Lossnay individually.

Ai
Remote
un
controller
PZ-41SLB-E co
Interlocking is p
(excluding puls
(Separately sold

CITY MULTI and Lossnay Interlocked


Outdoor unit

Air conditioning device


and system control

Interlocking/individu
Indoor Lossnay
unit
MA remote controller
Group 1

Indoor Indoor Lossnay


unit
unit
MA remote controller
Group 2

Indoor Lossnay
unit
MA remote controller
Group 3

Lossnay
Indoor
unit
MA remote controller
Group 4

M - N E T SYST E M

Outdoor unit

Indoor Lossnay
unit
MA remote controller
Group 1

It is possible to operate
16 indoor units per 1 Lossnay

By making the gr
(Joint use of the C
controller is poss

Indoor
unit
MA remote controller
Group 5

Outdoor unit

Indoor
Lossnay
unit
MA remote controller
G ro up 2

Indoor unit

Lossnay

Indoor unit Indoor


unit
MA remote controller
G ro up 3

CENTRALIZED CONTROLLER AG-150A

Centralized
controller
AG-150A O
u
(201)

Centralized Management System


Centralized controller AG-150A
CENTRALIZED CONTROLLER AG-150A

Power
supply
unit

Lossnay

Lossnay M-NET
remote controller
PZ-52SF-E
Group 1

Lossnay

Group 2

Lossnay

Lossnay

Lossnay M-NET
remote controller
PZ-52SF-E
Group 3

Lossnay

Lossnay

Lossnay M-NET
remote controller
PZ-52SF-E
Group 4

Lossnay

Lossnay

Lossnay M-NET
remote controller
PZ-52SF-E
Group 5

Control of start/stop, fan speed and ventiliation mode is possible from the Lossnay M-NET remote controller PZ-52SF- E
Control of start/stop, fan speed and ventiliation mode is possible from the centralized controller.
It is possible to set a maximum of 16 units for 1 group.

Do not se
part of the

Note: In the LGH-F1200RX type, there are two circuit boards installed in each unit,
so count each unit as two Lossnay units.
Performance Certified
to ARI 1060 Standard

ERV-24

LGH-F-RX3-E (Feb. 2009)

Applicable

DATA U4

m with one Lossnay

Two remote controller system with multiple Lossnay units

Use Lossnay remote controller PZ-41SLB-E


(Do not use PZ-52SF-E).
Lossnay transmission connection terminal

Power supply
Power supply
Power supply

LGH-F300, F470
and F600RX types

Remote controller
PZ-41SLB-E

olled from two remote

es priority to the last

LGH-F1200RX type
6

It is also possible to operate two remote controller units when using


multiple Lossnay units.
Remote controller input terminal

Selection of interlocked operation


mode is possible.
Delayed start interlocked operation is
possible.

C, uncharged a-

Interlocking multiple units


When the operation signal is an uncharged a-contact signal

Lossnay
Power supply

A/C

A/C

Power supply

Setting

Main/Sub selection switch


(SW1)
Main

A/C
Power supply

Sub

Power supply

Air conditioning
Air conditioning Air conditioning
Remote
unit side remote
unit side remote unit side remote
controller
controller
controller
controller
PZ-41SLB-E
Interlocking is possible from multiple air conditioning units, etc.
(excluding pulse input)
(Separately sold parts are necessary depending on the operation signal).

(Set to Main when


shipped from the factory)
Transmission
cable

Use Lossnay M-NET remote controller PZ-52SF-E.


Interlocking/individual joint systems

(Do not use PZ-41SLB-E).

By making the group setting, interlock settings have become possible.


(Joint use of the CITY MULTI remote controller and Lossnay remote
controller is possible.)

Lossnay transmission connection terminal


M-NET transmission cable
input terminal block

e controller

LGH-F300, F470
and F600RX types
TB5
A B S

LGH-F1200RX type
TB5

A B S

Operation settings

Setting
LGH-F300, F470 and F600RX types
Lossnay M-NET
remote controller
(PZ-52SF-E)(102)

Group 1

Group 2

SA1
0

SA2
1

LGH-F1200RX type

SA1

MA remote
controller

Shielded wire

Lossnay

SA1

SA2

( ) address

Applicable indoor units use MA remote contoller models.


Do not set the air conditioning unit and Lossnay unit to be
part of the same group.

SA2

Round terminal

M-NET
transmission cable

Lossnay (02)

Indoor unit
(01)

CENTRALIZED CONTROLLER AG-150A

Centralized
controller
AG-150A Outdoor
unit (51)
(201)

ssnay M-NET
mote controller
PZ-52SF-E
up 5

-E

Transmission cable

ith the operation or

ay

LGH-F-RX3-E

nay

Upper
circuit
board
[Sub]
ex. SA1 = 0,
SA2 = 2
Lower
circuit
board
[Main]
ex. SA1 = 0,
SA2 = 1

When the address number has been changed, the data in the memory
is automatically reset.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-25

DATA U4

LGH-F-RX3-E

System Selection
Available
Not available

Interlocked with CITY MULTI

Lossnay operation when indoor unit is stopped


Lossnay stopping when indoor unit is operating
Selecting Lossnay fan speed
When interlocked with indoor unit for compatibility with R22, R407C and R410A
Ventilation mode
Filter maintenance indicator
Lossnay error indicator
Delayed operation - selectable times
External control operating mode selection
Number of indoor units for interlocked group setting with one Lossnay unit
Number of Lossnay units for interlocked group setting with one indoor unit
*1 Ventilation mode (Energy Recovery, Bypass, Auto) selectable from Centralized Controller,
from remote controller.

Interlocked with Mr. Slim

High/Low
*1

M-NET transmission cable

CITY MULTI
indoor unit

Lossnay unit
LGH-RX type

16 units
1 unit

Remote controller

PZ52SF-E

but not selectable

(Refer to page 118)

When using A-control remote controller


Lossnay operation when indoor unit is stopped
Lossnay stopping when indoor unit is operating

L os s na y fa n s pe e d sele ction
H igh/L ow
Other common items
Lossnay error indicator

Ventilation mode
Fixed to automatic
Filter maintenance indicator

Delayed operation - selectable times


External control operating mode selection

Number of indoor units for interlocked group setting with one Lossnay unit
1 unit
Number of Lossnay units for interlocked group setting with one indoor unit
1 unit

Mr.Slim (A-control)
indoor unit

Lossnay unit
LGH-RX type
Remote
controller
PAR-21MAA

Lossnay remote
controller
cannot be used.

Mr. Slim-Lossnay connecting cable


(Enclosed accessory )

Independent Lossnay Unit

(not interlocked with CITY MULTI or Mr. Slim systems)


Start/Stop
F a n s pe e d selection

H igh/L ow
Energy Recovery
By-pass/ Auto

Ventilation mode
Filter maintenance indicator
Lossnay error indicator
Delayed operation
External control operating mode selection
Number of Lossnay units
(In the case of LGH-200RX type, count each unit as two for calcultion)
N umbe r of re mote c ontrolle rs

15 units

Lossnay unit
LGH-RX type
Lossnay remote controller
(PZ41SLB-E)

EXT. signal source


for interlocking
to the Lossnay

2 units

Interlocked with external device


Start/Stop
Fan speed selection
Ventilation mode switching
Filter maintenance indicator
Lossnay error indicator
Delayed operation
External control operating mode selection

Fixed to high
Fixed to automatic

EXT. signal source


for interlocking
to the Lossnay

Lossnay unit
LGH-RX type

LGH-F-RX3-E

ERV-22
Performance Certified
to ARI 1060 Standard

ERV-26

LGH-F-RX3-E (Feb. 2009)

DATA U4

Centralized Control System with CITY MULTI

LGH-F-RX3-E

AG-150A
Centralized Controller

Outdoor unit

CENTRALIZED CONTROLLER AG-150A

Power supply unit


PAC-SC51KUA

Indoor unit

Lossnay

Indoor unit

Remote controller

Remote controller

A-control Mr. Slim P-Series outdoor unit


M-NET control adapter PAC-SF80MA-E

Lossnay
A-control
Mr. Slim indoor unit
Mr. Slim A-control
PAR- 21 MAA
remote controller

Lossnay

Lossnay

Lossnay M-NET
Lossnay M-NET
remote controller remote controller
(PZ-52SF-E)
(PZ-52SF-E)

Lossnay

PZ-52SF-E
connected to
M-NET
Terminals

EXT.
signal
source

Lossnay M-NET
remote controller
(PZ-52SF-E)

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-27

DATA U4

LGH-F-RX3-E

Remote controllers for Lossnay unit

Remote controllers for CITY MULTI indoor unit

TIME SUN MON TUE WED THU FRI SAT


TIMER
Hr
ON
AFTER

AFTER OFF

ERROR CODE

FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF

ONLY1Hr.

TEMP.

MENU
BACK

MONITOR/SET

PAR-21MAA

ON/OFF

ON/OFF

FILTER

DAY

CHECK TEST

OPERATION

CLOCK

CLEAR

Remote controllers for


Mr. Slim indoor unit

TIME SUN MON TUE WED THU FRI SAT


TIMER
Hr
ON
AFTER

AFTER OFF

ERROR CODE

TEMP.

MENU
BACK
PAR-21MAA

MONITOR/SET

FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF

ONLY1Hr.

ON/OFF

ON/OFF

FILTER

DAY

CLOCK

CHECK TEST

OPERATION

CLEAR

Possible System Configurations


(1) When using only the Lossnay remote controller.
(2) Linking Lossnay and CITY MULTI units.
(3) Linking Mr. Slim (A-control).
(4) Linking with external equipment.
General Features of the Lossnay Remote Controller
It can start and stop the unit, change fan speed, switch the
ventilation mode. It also includes indicators that show errors
and when filter maintenance is required. When using M-NET
transmission to operate from centralized control, use PZ-52SF-E.
Lossnay Remote Controller (PZ-41SLB-E)
Use when operating from 1 to 15 Lossnay units at the same time.
Lossnay M-NET Remote Controller (PZ-52SF-E)
It can be used on the M-NET with CITY MULTI. Since this remote
controller is supplied power from the M-NET tranmission line, it cannot
be linked with Mr. Slim and other such systems that do not use M-NET.

Please refer to the technical documentation for the


other systems: CITY MULTI and Mr. Slim.

Performance Certified
to ARI 1060 Standard

ERV-28

LGH-F-RX3-E (Feb. 2009)

DATA U4

LGH-F-RX3-E

Combination with CITY MULTI --Independent Lossnay System with Lossnay


M-NET Remote Controller and M-NET

AG-150A
Centralized controller

CENTRALIZED CONTROLLER AG-150A

Lossnay M-NET remote

Lossnay M-NET remote

Lossnay M-NET remote

Lossnay M-NET remote

Lossnay M-NET remote

Lossnay remote controller PZ-41SLB-E cannot be used in conjuction with M-NET.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-29

DATA U4

LGH-F-RX3-E

Details

Item
Number of Lossnay remote controllers that can be connected to
one Lossnay unit.

Heat exchanger / Bypass / Automatic

Local Remote
Lossnay MNET remote
controller

Model

ME remote
controller

MA remote
controller

Centralized
controller
AG-150A

o
O
o
O
o
O

O
O
O

o
O

O
O
O
O
O
O
O

Not used to control


non-interlocked Lossnay

O
O
O
O
O
O
O
O
24
24 x 7

O
o
O

Performance Certified
to ARI 1060 Standard

ERV-30

LGH-F-RX3-E (Feb. 2009)

DATA U4

CITY MULTI and Lossnay Interlocked System

LGH-F-RX3-E

Lossnay remote controller PZ-41SLB-E


cannot be used with any group on the M-NET.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-31

DATA U4

Details

LGH-F-RX3-E

Item

Local Remote
Lossnay
M-NET remote
controller

Model

ME remote
controller

MA remote
controller

O
O
O

O
O

O
O

O
O
O
O
O
O
O

O
O

O
O

O
O
O
O

O
O
O
O
8
8x7
min. increments

Performance Certified
to ARI 1060 Standard

ERV-32

LGH-F-RX3-E (Feb. 2009)

DATA U4

MA Remote Controller/ME Remote Controller in Combination with Lossnay


M-NET Remote Controller

LGH-F-RX3-E

Indoor Unit

Lossnay LGH-RX type


O

CENTRALIZED CONTROLLER AG-150A

AG-150A
z

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-33

DATA U4

LGH-F-RX3-E

A mixed system including the CITY MULTI can also be configured.


AG-150A
z

CENTRALIZED CONTROLLER AG-150A

AG-150A
z

CENTRALIZED CONTROLLER AG-150A

Performance Certified
to ARI 1060 Standard

ERV-34

LGH-F-RX3-E (Feb. 2009)

DATA U4

When Using the LonWorks Compatible Adaptor (LMAP03U) to Connect to LonWorks

Contents

Individual Lossnay
(Lossnay not set
for interlocked
operation)

LGH-F-RX3-E

By using the LON adaptor (model name: LMAP03U), it is possible to control and observe Lossnays
on a building management system using the LonWorks.
For specifications and functions of the LON adaptor, refer to the materials regarding the LonWorks
compatible adaptor.

Interlocked Lossnay
(Lossnay set for
interlocked operation with City Multi)

O
O
O
O
O
O
O
O
O
O

x
x
x
x
x
x
x
O
x
x

LMAP03U

LonWorks

LMAP03U

Connect the M-Net transmission cable to TB5 A,B of the Lossnay terminal block.
The Lossnay remote controller (PZ-41SLB-E) cannot be used with this system.
Up to 50 units can be connected with one LMAP03U (The LGH-F1200RX) type should be counted as two.
For details about the system or connection cables of the LMAP03U, refer to the technical materials, etc.,
regarding the LMPA03U.
* LonWorks is a registered international trademark, registered in the U.S.A. to the Echelon Corporation.

Performance Certified
to ARI 1060 Standard

LGH-F-RX3-E (Feb. 2009)

ERV-35

BC controller (with R2-Series PURY)

DATA U4

CMB-P-NU-G, NU-GA, NU-GB, NU-HB


1. SPECIFICATIONS.......................................................................................................................................................BC-2
2. EXTERNAL DIMENSIONS........................................................................................................................................BC-10
3. ELECTRICAL WIRING DIAGRAMS..........................................................................................................................BC-14
4. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS........................................................................BC-23
5. Sound Pressure Levels..................................................................................................................................BC-26

5-1. BC Controller Steady State Sound...........................................................................................................BC-26

5-2. BC Controller Peak Sound.......................................................................................................................BC-27
6. Optional Parts....................................................................................................................................................BC-28

6-1. BV-Series Ball Valves...............................................................................................................................BC-28

6-2. BV-Series Ball Valve Insulation................................................................................................................BC-28

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-1

1. Specifications

DATA U4

I.BC
1. SPECIFICATIONS
controller (for R2 PURY)

Model name

CMB-P105NU-G

Number of branches

Power source

1-phase 208/230V
60Hz

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

0.073

kW

0.033
0.35/0.32

0.16/0.14

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit

PURY-P72/96/120THMU-A(-BS), PURY-P72/96/120YHMU-A(-BS), PQRY-P72/96TGMU-A

Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)


To outdoor unit
High press. pipe

Low press. pipe

5/8 (15.88)

3/4 (19.05)

to P72
in. (mm) O.D.
P73 to P108
in. (mm) O.D.
P109 to P126
in. (mm) O.D.

Brazed

Brazed

3/4 (19.05)

7/8 (22.2)

Brazed

Brazed

3/4 (19.05)

1-1/8 (28.58)

Brazed

Brazed

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

To indoor unit

in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Flare

5/8 (15.88) Flare

(1/4 (6.35) with attached reducer used.)

(1/2 (12.7) with attached reducer used,


3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

189,000 Btu/h

Maximum connected capacity for all branches


Field drain pipe size

in. (mm) O.D.

Net weight

lbs (kg)

1-1/4 (32)

64 (29)
Drain Connection pipe(with flexible hose and insulation)
Reducer

Accessories

189,000 Btu/h

1-1/4 (32)

72 (32)
Drain Connection pipe(with flexible hose and insulation)
Reducer

Remark

Note:

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
4. The data presented is based on a specific combination.
Ref.: Spec_CMB-P104-105NU-G

BC-2

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

1. Specifications

DATA U4

Model name

CMB-P106NU-G

Number of branches

CMB-P108NU-G

Power source

1-phase 208/230V

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

kW

60Hz

60Hz

0.086

0.112

0.040

0.053

0.41/0.37

0.54/0.49

0.19/0.17

0.25/0.23

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit

PURY-P72/96/120THMU-A(-BS), PURY-P72/96/120YHMU-A(-BS), PQRY-P72/96TGMU-A

Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indo or unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)


To outdoor unit
High press. pipe

Low press. pipe

5/8 (15.88)

3/4 (19.05)

to P72
in. (mm) O.D.
P73 to P108
in. (mm) O.D.
P109 to P126
in. (mm) O.D.

Brazed

Brazed

3/4 (19.05)

7/8 (22.2)

Brazed

Brazed

3/4 (19.05)

1-1/8 (28.58)

Brazed

Brazed
To indoor unit

Liquid pipe
in. (mm) O.D

3/8 (9.52) Flare (1/4 (6.35) with attached reducer used.)

in. (mm) O.D.

Net weight

lbs (kg)

189,000 Btu/h

1-1/4 (32)

1-1/4 (32)

76 (34)

84 (38)

Drain Connection pipe(with flexible hose and insulation)


Reducer

Accessories

5/8 (15.88) Flare (1/2 (12.7) with attached reducer used,


3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

Drain Connection pipe(with flexible hose and insulation)


Reducer

Remark

Note:

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other itemsare not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
4. The data presented is based on a specific combination.
Ref.: Spec_CMB-P106-108NU-G

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-3

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

189,000 Btu/h

Maximum connected capacity for all branches


Field drain pipe size

Gas pipe

1. Specifications

DATA U4

Model name

CMB-P1010NU-G

Number of branches

CMB-P1013NU-G

10

Power source

13
1-phase 208/230V

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

kW

60Hz

60Hz

0.138

0.178

0.066

0.086

0.66/0.60

0.86/0.77

0.32/0.29

External finish

0.41/0.37
Galvanized steel plate

(Lower part drain pan :Pre-coated galvanized sheets + powder coating)


Connectable outdoor unit

PURY-P72/96/120THMU-A(-BS), PURY-P72/96/120YHMU-A(-BS), PQRY-P72/96TGMU-A

Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)

11-3/16 x 43-1/4 x 17-1/32 (284 x 1,098 x 432)


To outdoor unit

High press. pipe

Low press. pipe

5/8 (15.88)

3/4 (19.05)

to P72
in. (mm) O.D.
P73 to P108
in. (mm) O.D.
P109 to P126
in. (mm) O.D.

Brazed

Brazed

3/4 (19.05)

7/8 (22.2)

Brazed

Brazed

3/4 (19.05)

1-1/8 (28.58)

Brazed

Brazed
To indoor unit

Liquid pipe

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

in. (mm) O.D.

in. (mm) O.D.

Net weight

lbs (kg)

Accessories

5/8 (15.88) Flare (1/2 (12.7) with attached reducer used,


3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

3/8 (9.52) Flare (1/4 (6.35) with attached reducer used.)


189,000 Btu/h

Maximum connected capacity for all branches


Field drain pipe size

Gas pipe

189,000 Btu/h

1-1/4 (32)

1-1/4 (32)

94 (42)

126 (57)

Drain Connection pipe(with flexible hose and insulation)

Drain Connection pipe(with flexible hose and insulation)

Reducer

Reducer

Remark

Note:

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
4. The data presented is based on a specific combination.
Ref.: Spec_CMB-P1010-1013NU-G

BC-4

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

1. Specifications

DATA U4

Model name

CMB-P1016NU-G

Number of branch

16

Power source

1-phase 208/230V
60Hz

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

0.217

kW

0.106
1.04/0.94

0.51/0.46

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit

PURY-P72/96/120THMU-A(-BS), PURY-P72/96/120YHMU-A(-BS), PQRY-P72/96TGMU-A

Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indo or unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-3/16 x 43-1/4 x 17-1/32 (284 x 1,098 x 432)


To outdoor unit
High press. pipe

Low press. pipe

5/8 (15.88)

3/4 (19.05)

to P72
in. (mm) O.D.
P73 to P108
in. (mm) O.D.
P109 to P126
in. (mm) O.D.

Brazed

Brazed

3/4 (19.05)

7/8 (22.2)

Brazed

Brazed

3/4 (19.05)

1-1/8 (28.58)

Brazed

Brazed
To indoor unit

Liquid pipe
in. (mm) O.D.

3/8 (9.52) Flare (1/4 (6.35) with attached reducer used.)

in. (mm) O.D.

Net weight

lbs (kg)

Accessories

189,000 Btu/h
1-1/4 (32)
138 (62)

Drain Connection pipe(with flexible hose and insulation)


Reducer

Remark

Note:

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other itemsare not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
4. The data presented is based on a specific combination.
Ref.: Spec_CMB-P1016NU-G

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-5

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

189,000 Btu/h

Maximum connected capacity for all branches


Field drain pipe size

Gas pipe
5/8 (15.88) Flare (1/2 (12.7) with attached reducer used,
3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

1. Specifications

DATA U4

Model name

CMB-P108NU-GA

Number of branches

CMB-P1010NU-GA

10

Power source

1-phase 208/230V

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

kW

60Hz

60Hz

0.112

0.138

0.053

0.066

0.54/0.49

0.66/0.60

0.25/0.23

0.32/0.29

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)
PURY-P72/96/120/144/168/192/216/240T(S)HMU-A(-BS),
PURY-P72/96/120/144/168/192/216/240Y(S)HMU-A(-BS), PQRY-P72/96TGMU-A

Connectable outdoor unit


Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-13/32 x 43-23/32 x 20-1/2 (289 x 1,110 x 520)


To outdoor unit
High press. pipe

Low press. pipe

5/8 (15.88)

3/4 (19.05)

to P72
in. (mm) O.D.
P73 to P108
in. (mm) O.D.
P109 to P126
in. (mm) O.D.
P127 to P192
in. (mm) O.D.

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

P193 to P240
in. (mm) O.D.

Brazed

Brazed

3/4 (19.05)

7/8 (22.2)

Brazed

Brazed

3/4 (19.05)

1-1/8 (28.58)

Brazed

Brazed

7/8 (22.2)

1-1/8 (28.58)

Brazed

Brazed

1-1/8 (28.58)

1-1/8 (28.58)

Brazed

Brazed
To indoor unit

in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Flare

5/8 (15.88) Flare

(1/4 (6.35) with attached reducer used.)

(1/2 (12.7) with attached reducer used,


3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)
To other BC controller

Total indoor unit capacity


High press. pipe

connected to this Sub BC

Low press. pipe


Liquid pipe

controller
to P72

5/8 (15.88) Brazed

in. (mm) O.D.

3/4 (19.05) Brazed


3/8 (9.52) Brazed

P73 to P108

3/4 (19.05) Brazed

in. (mm) O.D.

7/8 (22.2) Brazed


3/8 (9.52) Brazed

P109 to P126

3/4 (19.05) Brazed

in. (mm) O.D.

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

Maximum connected capacity for all branches

360,000 Btu/h

360,000 Btu/h

126,000 Btu/h

126,000 Btu/h

1-1/4 (32)

1-1/4 (32)

Maximum connected capacity to Sub BC Controller(s)*


*If two Sub BC Controllers are connected and at least one is
a CMB-P1016NU-HB, the maximum connected capacity is
168,000 Btu/h.

Field drain pipe size


Net weight
Accessories
Remark
Note:

in. (mm) O.D.


lbs (kg)

122 (55)
Drain Connection pipe(with flexible hose and insulation)
Reducer

132 (59)
Drain Connection pipe(with flexible hose and insulation)
Reducer

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. P204 to P240 type outdoor unit side high press. pipe can changed to "1-1/8 (28.58) Brazed".
4. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
5. The data presented is based on a specific combination.

Ref.: Spec_CMB-P108-1010NU-GA

BC-6

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

1. Specifications

DATA U4

Model name

CMB-P1013NU-GA

Number of branches

CMB-P1016NU-GA

13

16

Power source

1-phase 208/230V

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heatin

kW

60Hz

60Hz

0.178

0.217

0.086

0.106

0.86/0.77

1.04/0.94

0.41/0.37

0.51/0.46

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)
PURY-P72/96/120/144/168/192/216/240T(S)HMU-A(-BS),
PURY-P72/96/120/144/168/192/216/240Y(S)HMU-A(-BS), PQRY-P72/96TGMU-A

Connectable outdoor unit


Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indo or unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-13/32 x 43-23/32 x 20-1/2 (289 x 1,110 x 520)


To outdoor unit
High press. pipe

Low press. pipe

5/8 (15.88)

3/4 (19.05)

to P72
in. (mm) O.D.
P73 to P108
in. (mm) O.D.
P109 to P126
in. (mm) O.D.
P127 to P192
in. (mm) O.D.
P193 to P240

Brazed

3/4 (19.05)

7/8 (22.2)

Brazed

Brazed

3/4 (19.05)

1-1/8 (28.58)

Brazed

Brazed

7/8 (22.2)

1-1/8 (28.58)

Brazed

Brazed

1-1/8 (28.58)

1-1/8 (28.58)

Brazed

Brazed
To indoor unit

in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Flare

5/8 (15.88) Flare

(1/4 (6.35) with attached reducer used.)

(1/2 (12.7) with attached reducer used,


3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)
To other BC controller

Total indoor unit capacity


High press. pipe

connected to this Sub BC

to P72

5/8 (15.88) Brazed

in. (mm) O.D.


3/4 (19.05) Brazed

in. (mm) O.D.


3/4 (19.05) Brazed

in. (mm) O.D.


Max. connected capacity for all branches
*If two Sub BC Controllers are connected and at least one is
a CMB-P1016NU-HB, the maximum connected capacity is
168,000 Btu/h.

360,000 Btu/h

360,000 Btu/h

126,000 Btu/h

126,000 Btu/h

1-1/4 (32)
148 (67)
Drain Connection pipe(with flexible hose and insulation)
Reducer

1-1/4 (32)
162 (73)

BC

in. (mm) O.D.


lbs (kg)

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

Max. connected capacity to Sub BC Controller(s)*

Field drain pipe size

7/8 (22.2) Brazed


3/8 (9.52) Brazed

P109 to P126

Net weight

3/4 (19.05) Brazed


3/8 (9.52) Brazed

P73 to P108

Remark
Note:

Low press. pipe


Liquid pipe

controller

Accessories

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

in. (mm) O.D.

Brazed

Drain Connection pipe(with flexible hose and insulation)


Reducer

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other itemsare not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. P204 to P240 type outdoor unit side high press. pipe can changed to "1-1/8 (28.58) Brazed".
4. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
5. The data presented is based on a specific combination.

Ref.: Spec_CMB-P1013-1016NU-GA

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-7

1. Specifications

DATA U4

Model name

CMB-P104NU-GB

Number of branches

CMB-P108NU-GB

Power source

1-phase 208/230V

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

kW

60Hz

60Hz

0.053

0.106

0.027

0.053

0.25/0.23

0.51/0.46

0.13/0.12

0.25/0.23

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

( Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55. )
( Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected. )

External dimension H x W x D

in. (mm)

11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)


To indoor unit

Refrigerant
Liquid pipe

Gas pipe

3/8 (9.52) Flare

5/8 (15.88) Flare

piping
diameter
in. (mm) O.D.

(1/4 (6.35) with attached reducer used.)

(1/2 (12.7) with attached reducer used,


3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)
To other BC controller

Total indoor unit capacity


High press. pipe

connected to this Sub BC

to P72

5/8 (15.88) Brazed

in. (mm) O.D.


3/4 (19.05) Brazed

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

in. (mm) O.D.

7/8 (22.2) Brazed


3/8 (9.52) Brazed

P109 to P126

3/4 (19.05) Brazed

in. (mm) O.D.

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

Max. connected capacity for all branches

126,000 Btu/h

in. (mm) O.D.

126,000 Btu/h

1-1/4 (32)

lbs (kg)

Accessories

3/4 (19.05) Brazed


3/8 (9.52) Brazed

P73 to P108

Field drain pipe size


Net weight

Low press. pipe


Liquid pipe

controller

1-1/4 (32)

62 (28)
Drain Connection pipe(with flexible hose and insulation)
Reducer

82 (37)
Drain Connection pipe(with flexible hose and insulation)
Reducer

Remark

Note:

1. Works not included :


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. To use the Sub BC controller, the Main BC controller is necessary to be connected with.
4. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
5. The data presented is based on a specific combination.
Ref.: Spec_CMB-P104-108NU-GB

BC-8

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

1. Specifications

DATA U4

Model name

CMB-P1016NU-HB

Number of branch

16

Power source

1-phase 208/230 V 60Hz


60Hz

Power input

Cooling

(208/230)

Heating

Current

Cooling

(208/230)

Heating

0.314

kW

0.157
1.17/1.37

0.59/0.69

External finish

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

Connectable BC controller

Main BC

CMB-P108/1010/1013/1016NU-GA

Sub BC

CMB-P104/108NU-GB, CMB-P1016NU-HB

Indoor unit capacity

Model P54 or smaller

connectable to 1 branch

kW

(Use optional joint pipe combining 2 branches when the total unit capacity exceeds P55.)
(Use the reducer(standard accessory)when the indoor unit Model 18 or smaller is connected.

External dimension H x W x D

in. (mm)

Refrigerant

Connectable outdoor unit

piping

capacity

diameter

11-3/16 x 43-1/4 x 17-1/32 (284 x 1098 x 432)


To outdoor unit
High press. pipe

in. (mm) O.D.

Low press. pipe

To indoor unit

in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Flare

5/8 (15.88) Flare

(1/4 (6.35)with attached reducer used, 1/2 (12.7)with optional joint


pipe used.)

(1/2 (12.7)with attached reducer used, 3/4 (19.05)with optional joint


pipe used.)

To other BC controller

Total indoor unit capacity


connected to this Sub BC

High press. pipe

Low press. pipe


Liquid pipe

controller
5/8 (15.88) Brazed

in. (mm) O.D.


P73 to P108

3/4 (19.05) Brazed

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

7/8 (22.2) Brazed

in. (mm) O.D.


P145 to P168
in. (mm) O.D.

7/8 (22.2) Brazed


3/8 (9.52) Brazed

in. (mm) O.D.


P127 to P144

3/4 (19.05) Brazed


3/8 (9.52) Brazed

in. (mm) O.D.


P109 to P126

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

to P72

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed


5/8 (15.88) Brazed

Max. connected capacity for all branches

(For sub BC Controller CMB-P1016NU-HB, the connectable


indoor unit capacities may less than or equal to P126. However,
if two Sub BC Controllers are used and at least one is a
CMB-P1016NU-HB, the total sum of connectable indoor units
connected to be Sub BC Controllers must also not exceed P168.

Field drain pipe size


Net weight
Accessories

126,000 Btu/h

126,000 Btu/h

in. (mm) O.D.

1-1/4 (32mm)
136 (61)

lbs (kg)
Drain Connection pipe (with flexible hose and insulation)
Reducer

Remark
Note:

1. Works not included :


Installation/foundation work,electrical connection work,duct work, duct work, insulation work, power source switch, and other items are not specifiedin this specifications.
2. The equipment is for R410A refrigerant.
3. To use the Sub BC controller, it must be connected to the Main BC controller.
4. Install this product in a location where sound (refrigerant sound) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background
sound, position the BC CONTROLLER at least 5m [16 ft.] away from any indoor units.)
5. The data presented is based on a specific combination .
6. This BC Controller is for use only with PURY-THMU or PURY-YHMU systems.
Ref.: Spec_CMB-P1016NU-HB
wever, if two sub controllers are used

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-9

30

103

PQRY-P72: 19.05 (3/4) <Brazed>


(use attachment pipe)
PQRY-P96: 22.2 (7/8) <Brazed>

284 (11-3/16)

255 (10-1/16)

70

76

(7-7/8)

200

(2-25/32) (3)

Connection pipe of outdoor/water-source unit(Low pressure)

23

(29/32)

130

64

(5-1/8)

(9-25/32)

PQRY-P72: 15.88 (5/8)


<Brazed> (use attachment pipe)
PQRY-P96: 19.05 (3/4)
X
<Brazed>

(1-3/16)
1

60 (2-3/8)

12 (1/2)

Connection pipe of outdoor/water-source unit(High pressure)

(1-1/4)

248
(2-17/32) (4-1/16)

Drain piping
I.D.32 (1-1/4)

(2-17/32) (4-19/32) (5-1/16)


64
116
128

Detail of X section

58 (2-5/16)
27 (1-3/32)

14

10

60(2-3/8)XC=D

11

(Lifting bolt pitch)

Detail of Y section

(9/16)

12

13

14

Control box

15

16

200

CMB-P1016NU-G

1098
1152
(43-1/4) (45-3/8)

648
702
(25-17/32) (27-21/32)

Access
door

200

(7-7/8)

720(28-3/8)
900(35-7/16)
15

4
5

12

250

420(16-9/16)
540(21-9/32)

700
7
9

(9-27/32)

D
240(9-15/32)
300(11-13/16)

(27-9/16)
C

CMB-P105,106,108,1010,1013,1016NU-G

CMB-P1013NU-G

CMB-P108NU-G
CMB-P1010NU-G

CMB-P105NU-G
CMB-P106NU-G

(7-7/8)

Connection pipe of
indoor unit(Gas)

Connection pipe of
indoor unit(Liquid)

Service
space

prepare in the field.


2.Take notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)

<Accessories>

70

Band(Accessory)

128

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


(5-1/16)

298 (11-3/4)
(Lifting bolt pitch)

Drain hose(Accessory)

(2-25/32)

BC-10
362 (14-9/32)

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

2. External Dimensions
DATA U4

Drw. : CMB-P-NU-G_W659644
Unit : mm(in)

130

(5-1/8)

(1-1/4)

PURY-P72: 19.05 (3/4) <Brazed>


(Reducer is field supplied)
PURY-P96: 22.2 (7/8) <Brazed>
(Reducer is field supplied)
PURY-P120,144,168,192,216,240:
28.58 (1-1/8) <Brazed>
PQRY-P72: 19.05 (3/4) <Brazed>
(Reducer is field supplied)
PQRY-P96: 22.2 (7/8) <Brazed>
(Reducer is field supplied)

30

12 (1/2)
(1-3/16)

14
(9/16)

Detail of Y section

23

90

76

200
(7-7/8)

(2-25/32)

70

(3-9/16) (3)

60 (2-3/8)

1110 (43-23/32)

10

60(2-3/8)XA=B

11

12

13

14

Control box

1164 (45-27/32)
(Lifting bolt pitch)

PURY-P72:15.88(5/8)<Brazed>(Reducer is field supplied)


PURY-P96,108:19.05(3/4)<Brazed>(Reducer is field supplied)
PURY-P120:19.05(3/4)<Brazed>(use attachment pipe)
PURY-P144,168,192:22.2(7/8)<Brazed>
PURY-P216,240:28.58(1-1/8)<Brazed>(use attachment pipe)
PQRY-P72:15.88(5/8)<Brazed>(Reducer is field supplied)
PQRY-P96:19.05(3/4)<Brazed>(Reducer is field supplied)

(29/32)

263 (10-3/8)

Connection pipe of outdoor/


water-source unit (Low pressure)

(2-17/32) (4-19/32)
116
64

(8-17/32)
216

Drain piping
I.D.32 (1-1/4)

289 (11-13/32)

15

16

Connection pipe of
indoor unit(Gas)

70 (2-25/32)

Connection pipe of
indoor unit(Liquid)

Service
space

200 (7-7/8)

(2-15/16)

74

66 (2-5/8)

(5-1/16)

128

prepare in the field.


2.Take notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)
3.Please take space to connect SUB BC CONTROLLER.

388(15-9/32)
(Lifting bolt pitch)

Connection pipe of outdoor/water-source unit(High pressure)

128

70
450 (17-23/32)

Detail of X section

103
64

268
(2-17/32) (4-1/16)

(5-1/16)

(10-9/16)

74 (2-15/16)
27 (1-3/32)

(2-25/32)

268 (10-9/16)
210 (8-9/32)
103 (4-1/16)

B
420(16-9/16)
540(21-9/32)
720(28-3/8)
900(35-7/16)

Access
door

200 200 (Note 3.)

(use attachment pipe of


SUB CONTROLLER)
(7-7/8) (7-7/8)

(use attachment pipe of


SUB BC CONTROLLER)

Connection pipe of
SUB BC CONTROLLER
(Low pressure)
Total capacity of indoor unit
at SUB BC CONTROLLER

(use attachment pipe of


SUB BC CONTROLLER)

Connection pipe of
SUB BC CONTROLLER
(Liquid)
Total capacity of indoor unit
at SUB BC CONTROLLER

(use attachment pipe of


SUB BC CONTROLLER)

Connection pipe of
SUB BC CONTROLLER
(High pressure)
Total capacity of indoor unit
at SUB BC CONTROLLER

250

A
CMB-P108NU-GA
7
CMB-P1010NU-GA 9
CMB-P1013NU-GA 12
CMB-P1016NU-GA 15

700

<Accessories>

(9-27/32)

Band(Accessory)

CMB-P108,1010,1013,1016NU-GA

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

Drain hose(Accessory)

2. External Dimensions
DATA U4

Drw. : CMB-P-NU-GA_W659642
Unit : mm(in)

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-11

(27-9/16)

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


(1-1/4)

45 (1-25/32)

130
23
Connection pipe of MAIN BC CONTROLLER (5-1/8)
(29/32)
(Low pressure)
Total capacity of indoor units at SUB BC CONTROLLER

(2-17/32) (4-19/32) (5-1/16)


116
128
64

Drain piping
I.D.32 (1-1/4)

169
255 (10-1/16)

103
64

30

12 (1/2)
(1-3/16)

14
Detail of Y section

(9/16)

70

76

CMB-P104NU-GB
CMB-P108NU-GB

60 (2-3/8)

A
3
7

60(2-3/8)XA=B

B
180(7-3/32)
420(16-9/16)

702 (27-21/32)
(Lifting bolt pitch)

648 (25-17/32)

Control box

298 (11-3/4)
(Lifting bolt pitch)

Connection pipe of
indoor unit(Gas)

Connection pipe of
indoor unit(Liquid)

200
(7-7/8)

Service space

Access
door

200

(7-7/8)

prepare in the field.


2.Take notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)
3.Can't use singleness.(MAIN BC CONTROLLER is necessary.)

CMB-P104,108NU-GB

(7-7/8)

200

(2-25/32) (3)

Connection pipe of MAIN BC CONTROLLER(Liquid)


Total capacity of indoor units at SUB BC CONTROLLER

248
128

Connection pipe of MAIN BC CONTROLLER


(High pressure)
Total capacity of indoor units at SUB BC CONTROLLER

(6-21/32)
(5-1/16)

<Accessories>

(2-25/32)

Detail of X section

(2-17/32) (4-1/16)

284 (11-3/16)

(9-25/32)

58 (2-5/16)
27 (1-3/32)

70
362 (14-9/32)

Band(Accessory)

250

Drain hose(Accessory)

700

BC-12
(9-27/32)

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

2. External Dimensions
DATA U4

Drw. : CMB-P-NU-GB_W659643
Unit : mm(in)

(27-9/16)

Detail of X section

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

200

(7-7/8)

Service
space

(Note 2.)
Access
door
450

200

(7-7/8)

Total capacity of indoor units at SUB BC CONTROLLER


72 or less:19.05(3/4)<Brazed>(use attachment pipe)
108 or less:22.2(7/8)<Brazed>
108 over :28.58(1-1/8)<Brazed>(use attachment pipe)

130

(5-1/8)

45 (1-25/32)

23

(29/32)

(7-7/8)

200

(3)

76

60 (2-3/8)

90 46 (1-13/16)
60 (2-3/8)

(3-9/16)

1098(43-1/4)
1152(45-3/8)

Control box

10 11 12 13 14 15 16

60(2-3/8)15=900(35-7/16)

60(2-3/8)15=900(35-7/16)

(Lifting bolt pitch)

Connection pipe of MAIN BC CONTROLLER(Liquid)


Total capacity of indoor units at SUB BC CONTROLLER
108 or less:9.52(3/8)<Brazed>
108 over :12.7(1/2)<Brazed>(use attachment pipe)

Dtail of Y section

<Accessories>
.Refrigerant<Low pressure> conn. pipe...........4pcs.
.Refrigerant<High pressure> conn. pipe..........2pcs.
.Refrigerant<Liquid> conn. pipe.......................2pcs.
.Reducer(Large,Small)..............Quantity for all connections
.Drain hose(VP-25 connection)........................1pc.
.Hose band.......................................................1pc.
.Tie band..........................................................1pc.

Connection pipe of
indoor unit(Gas)
15.88(5/8)<Flare>

9.52(3/8)<Flare>

Connection pipe of
indoor unit(Liquid)

298 (11-3/4)

(1-1/4)
31

Connection pipe of MAIN BC CONTROLLER


(Low pressure)

(2-17/32) (4-19/32) (5-1/16)


64
116
128

Drain piping
VP-25 connection

700

103
64
284 (11-3/16)

Connection pipe of MAIN BC CONTROLLER


(High pressure)
Total capacity of indoor units at SUB BC CONTROLLER
72 or less:15.88(5/8)<Brazed>(use attachment pipe)
72 over :19.05(3/4)<Brazed>

250

(Lifting bolt pitch)

14

58 (2-5/16)

30

12 (1/2)
(27-9/16)

(9/16)

27 (1-3/32)

(1-3/16)
(9-27/32)

(2-25/32)

Drain hose(Accessory)

248

(5-1/16)

(2-17/32) (4-1/16)
169
(6-21/32)

255 (10-1/16)

(9-25/32)

128

70
362 (14-9/32)

Note1. Suspension bolt (10) , washer (M10) , and nut (M10)


prepare in the field.
2. Take notice of service space as follows.
(Please give attention not to occupy service
space by letting ducts and pipes through.)
3. Can't use singleness.(MAIN BC CONTROLLER is necessary.)
4. Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
(For use in quiet enviroments with low background noise,position
the BC CONTROLLER at least 5m away from any indoor units.)

CMB-P1016NU-HB

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

Band(Accessory)

2. External Dimensions
DATA U4

Ref. :CMB_NU-HB_EXD_USDB_P1016
Unit : mm(in)

BC-13

BC-14

TH16

TH15

TH12

TH11

PS3

PS1

3
2
1

3
2
1

ON

CN11

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


1

CN05
(Red)

DSA

LEV1

LEV3

1 2 3 4 5 6

SW5

SW4

ZNR01

ZNR02

CN12

F01
250VAC
6.3A F
3 5

X21

CN36(Green)

T1

T4

T3

T2

1
2

1
2

SVM1

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

Indoor/outdoor (heat source)


Transmission Line

POWER SUPPLY
~208V-230V 60Hz

BREAKER(15A)

FUSE(15A)

TB01 TO NEXT INDOOR UNIT


L1
L2
PULL BOX

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

TB02
S(SHIELD)
M2
M1

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

(Symbol explanation)
Symbol
Name
Transformer
TR
TH11,12,15,16 Thermistor sensor
Expansion valve
LEV1,3
Pressure sensor
PS1,3
Circuit BC controller
CONT.B
board
Terminal block
TB01
(for power source)
Terminal block
TB02
(for Transmission)
SV1~4A,B,C
Solenoid valve
SVM1
Solenoid valve
T1~4
Terminal
F01
Fuse AC250V 6.3A F

CMB-P104NU-G

1 2 3 4 5 6

CN07
(Yellow)

OFF

ON

OFF

SW1

X33

SW2
1

X7

CN29(Green)

X8

X32

CN10

X5

CN28(Blue)

X31

X3

CN26

CN27(Red)
X4

X30

X1

X2

10

CN02

CN03
(Yellow)

CNTR
(Red)

X6

CN13
(Red)

CNP3

2 1

3 2 1

1
2

1
2

CNP1
(Black)

1
2

CONT.B

TR

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-G_EWD_USDB_P104

TH16

TH15

TH12

TH11

PS3

PS1

3
2
1

ON

CN11

LEV1

CN05
(Red)

SW5

LEV3

SW4

1 2 3 4 5 6

OFF

ON

OFF

1 2 3 4 5 6

CN07
(Yellow)

SW1

DSA

ZNR01

TB01
L1
L2
G

ZNR02

CN12

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


G

POWER SUPPLY
~208V-230V 60Hz

3 5

F01
250VAC
6.3A F
7

4 4

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

BREAKER(15A)

FUSE(15A)

PULL BOX

TO NEXT INDOOR UNIT

CN36(Green)

X21

X35

X11

CN31(Yellow)
X12

X34

X9

CN30(Black)
X10

X33

SW2
1

X7

CN29(Green)

X8

X32

CN10

X5

CN28(Blue)

X31

X3

CN27(Red)
X4

X30

X1

10

CN02

2 1

X6

CN13
(Red)

CNP3

CN03
(Yellow)

3 2 1

CNTR
3
(Red)
CN26
X2

1
2

1
2

CNP1
(Black)

1
2

CONT.B

T5

T4

T3

SV5B
SV5A
SV5C

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

2
3
3

T6

SVM1

SV6B
SV6A
SV6C

1 CMB-P106NU-G ONLY

T1

Indoor/outdoor (heat source)


Transmission line

T2

TB02
S(SHIELD)
M2
M1

Name
Transformer
Thermistor sensor
Expansion valve
Pressure sensor
Circuit BC controller
board
Terminal block
(for power source)
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F
Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

TB02
SV1~6A,B,C
SVM1
T1~6
F01

TB01

CONT.B

Symbol
TR
TH11,12,15,16
LEV1,3
PS1,3

(Symbol explanation)

CMB-P105,106NU-G

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

3
2
1

TR

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-G_EWD_USDB_P105-106

BC-15

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

3
2
1

TB02
SV1~10A,B,C
SVM1
T1~10
F01

TB01

Name
Transformer
Thermistor sensor
Expansion valve
Pressure sensor
Circuit Relay
board BC controller
Terminal block
(for power source)
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.

LEV1

CN05
(Red)

LEV3

SW5

SW4

1 2 3 4 5 6

CN07
(Yellow)

OFF

1 2 3 4 5 6

4
ON

2
3

ON
OFF

ZNR01

ZNR02

1 3 5

X21

CN36(Green)

X35

X11

2.The initial set values


of switch on CONT.B
are as follows.
SW1:0
SW2:0

CN12

250VAC
6.3A F

DSA F01

CN31(Yellow)
X12

X34

X9

CN30(Black)
X10

X7

CN11

X8

X33

SW1

8
SW2

CN29(Green)

CN10

X32

CN28(Blue)

X31

X3

CN26
1

CN27(Red)
X4

X30

X1

X2

CNTR
(Red)

1 3

CN38

X5

10

CN50

X6

7 6 5 4 3 2 1

CN13
(Red)

CNP3

6 5 4 3 2 1

1
2

1
2

CN02

CN03
(Yellow)

CN51

TB01
L1
L2

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

T1

T2

T6

T5

T4

T3

SV6B
SV6A
SV6C

SV5B
SV5A
SV5C

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

FUSE(15A)

PULL BOX

3
1

CN39

SVM1
16
16

T10

T9
3

12 11 10
12 11 10

CN33(Red)

CN53

6 5 4 3 2 1

CMB-P1010NU-G ONLY

15 14 13
15 14 13

4
1

CMB-P1010NU-G ONLY

POWER SUPPLY
~208V-230V 60Hz
BREAKER(15A)

TO NEXT INDOOR UNIT

CN32

CN52

2 1

4
4

T7
3

5
5
6
6

7 6 5 4 3 2 1

7
7

8
8

T8
3

9
9

REL.B

CMB-P108,1010NU-G

Symbol
TR
TH11,12,15,16
LEV1,3
PS1,3
REL.B
CONT.B

(Symbol explanation)

TH16

TH15

TH12

TH11

PS3

CNP1
(Black)

2 1

CN35(Blue)

3 2 1

X20

1
2

X19

PS1

CN34(Black)

CONT.B

X18

3
2
1

X17

SV10C
SV10A
SV10B
X39

SV9C
SV9A
SV9B
X38

Indoor/outdoor (heat source)


Transmission line

X16

TB02
S(SHIELD)
M2
M1

X15

TR

X14

SV8C
SV8A
SV8B
X37

SV7C
SV7A
SV7B
X13

BC-16
X36

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-G_EWD_USDB_P108-1010

TH16

TH15

TH12

TH11

PS3

SW5

SW4

1 2 3 4 5 6

LEV1

LEV3

SW1

CN05
(Red)

SW2

10

1 2 3 4 5 6

CN07
(Yellow)

OFF

ON

ON

OFF

CN11

CN10

CN13
(Red)

CNP3

1
2

1
2

CN02

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

3
2
1

CNVCC1 CN03
(Yellow)
CNP1 (Blue)
(Black)

2 1

CN12

1
3 5

F01
250VAC
6.3A F

DSA

ZNR01

CNOUT3

ZNR02

X9

X21

CN36(Green)

X35

X11

CN31(Yellow)
X12

X34

CN30(Black)
X10

X33

X7

X8

CN29(Green)

X32

X5

X6

CN28(Blue)

X31

X3

CN26

CN27(Red)
X4

X30

X1

X2

CNTR
(Red)

CNOUT1

1 3

CN38
1 1

T1

T6

T5

T4

T3

T2

SV6B
SV6A
SV6C

SV5B
SV5A
SV5C

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

BREAKER(15A)

TO NEXT
INDOOR UNIT POWER SUPPLY
~208V-230V
PULL BOX
60Hz

G FUSE(15A)

TB01
L1
L2

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

16
16

T10

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

15 14 13
15 14 13

X20

3 2 1

X19

3 2 1

T9

12 11 10
12 11 10

X18

X17

SV10C
SV10A
SV10B
X39

SV9C
SV9A
SV9B
X38

1
2

7
7

8
8

T8

9
9

X16

PS1

X15

CONT.B

4
4

T7

5
5

6
6

X14

3
2
1

X13

SV8C
SV8A
SV8B
X37

SV7C
SV7A
SV7B
X36

Indoor/outdoor (heat source)


Transmission line

CN39

TB02
S(SHIELD)
M2
M1

3 2 1

CNVCC2
(Blue)

1 3

X57

X55

X56

CN45(Green)

X54

X52

X53

CN44(Yellow)

X51

X49

X50

CN43(Red)

X48

X46

X47

CN42

X45

X43

X44

CN41(Green)

X42

X40

X41

CN40
(Yellow)

REL.B

4 4

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

T12

T13

SV14B
SV14A
SV14C

1
2
3

T16

T15

SVM1

SV16B
SV16A
SV16C

SV15B
SV15A
SV15C

CMB-P1016NU-G ONLY
3

T14

SV13B
SV13A
SV13C

SV12B
SV12A
SV12C

SV11B
SV11A
SV11C

T11

1
2
3

(Symbol explanation)
Symbol
Name
Transformer
TR
TH11,12,15,16 Thermistor sensor
Expansion valve
LEV1,3
Pressure sensor
PS1,3
REL.B
Circuit Relay
board BC controller
CONT.B
Terminal block
TB01
(for power source)
Terminal block
TB02
(for Transmission)
SV1~16A,B,C Solenoid valve
SVM1
Solenoid valve
T1~16
Terminal
F01
Fuse AC250V 6.3A F

CMB-P1013,1016NU-G

CN35(Blue)

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

TR

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-G_EWD_USDB_P1013_1016

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-17

CN32

CN33(Red)

CN34(Black)

TH16

TH15

TH12

TH11

PS3

3
2
1

LEV2

LEV3

CN06
(Blue)

SW5

SW4

1 2 3 4 5 6

SW1

SW2

1 2 3 4 5 6

OFF

ON

OFF

1 2 3 4 5 6

CN05
(Red)

ZNR02

LEV1

CN12

3 5

F01
250VAC
6.3A F

DSA

CN46(Yellow)
X60

CN36(Green)
X21

X35

X11

CN31(Yellow)
X12

X34

X9

CN30(Black)

TB01
L1
L2

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

T6

T5

T4

T3

T2

T1

SV6B
SV6A
SV6C

SV5C

SV5B
SV5A

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

FUSE(15A) BREAKER(15A)

PULL BOX

TO NEXT INDOOR UNIT

1
2

3
4

POWER SUPPLY
~208V-230V
60Hz

4
4

3
3

1
1

3
1

CN39

2
2

TB02
SV1~10A,B,C
SVM1,2
T1~10
F01

TB01

CN53

16
16

T10
3

6 5 4 3 2 1

15 14 13
15 14 13

T9
3

4
4

REL.B

2 1

5
5

T7
3

6
6

CN52

7
7

8
8

T8
3

9
9

7 6 5 4 3 2 1

12 11 10
12 11 10

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

CMB-P1010NU-GA ONLY

Name
Transformer
Thermistor sensor
Expansion valve
Pressure sensor
Circuit Relay
board BC controller
Terminal block
(for power source)
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

CMB-P108,1010NU-GA

CN07
(Yellow)

10

X33

X10

X7

CN11

X8

CN29(Green)

CN10

X32

CN28(Blue)

X31

X3

CN27(Red)
X4

X30

X1

X2

CN26

CNTR
(Red)

X5

ZNR01

1 3

CN38

ON

CN50

X6

CN13
(Red)

CNP3

CN51

1
2

1
2

CNP1
(Black)

2 1

CN02

3 2 1

CN03
(Yellow)

Symbol
TR
TH11,12,15,16
LEV1~3
PS1,3
REL.B
CONT.B

SVM2
SVM1

CN35(Blue)

7 6 5 4 3 2 1

X20

PS1

6 5 4 3 2 1

X19

1
2

CN34(Black)

3
2
1

X18

SV10C
SV10A
SV10B
X39

SV9C
SV9A
SV9B
X17

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


X38

(Symbol explanation)

CN33(Red)

CONT.B

X16

Indoor/outdoor (heat source)


Transmission line

X15

TB02
S(SHIELD)
M2
M1

CN32

TR

X14

SV8C
SV8A
SV8B
X37

SV7C
SV7A
SV7B
X13

BC-18
X36

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-GA_EWD_USDB_P108-1010

3
2
1

1
2

1
2

1 2 3 4 5 6

LEV3

LEV2

3 2 1

CN11

CN10

CN13
(Red)

CNP3

LEV1

ON

OFF

ON

OFF

1 2 3 4 5 6

CN05
(Red)

CN06
(Blue)

CN07
(Yellow)

1 2 3 4 5 6

3 2 1

2 1

SW5

SW4

SW1

SW2

10

CN12

1
3 5

250VAC
6.3A F

DSA F01

ZNR01

CNOUT3

CN46(Yellow)
X60

CN36(Green)
X21

X35

X11

CN31(Yellow)
X12

X34

X9

CN30(Black)
X10

X33

X7

CN29(Green)

X32

X5

X8

CN28(Blue)
X6

X31

X3

CN26

CN27(Red)
X4

X30

X1

X2

ZNR02

1 3

CN38

CNOUT1

Note:1.TB02 is transmission terminal


block.Never connect power line
to it.
2.The initial set values of switch
on CONT.B are as follows.
SW1:0
SW2:0

TH16

TH15

TH12

TH11

PS3

TB01
L1
L2

1 1

T1

SV6B
SV6A
SV6C

SV5B
SV5A
SV5C

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

FUSE(15A) BREAKER(15A)

POWER SUPPLY
~208V-230V
60Hz

T6

T5

T4

T3

T2

PULL BOX

TO NEXT
INDOOR UNIT

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

16
16

T10

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

15 14 13
15 14 13

X20

CNVCC1 CN03 CN02


CNP1 (Blue) (Yellow)
(Black)

X19

PS1

T9

12 11 10
12 11 10

X18

X17

SV10C
SV10A
SV10B
X39

SV9C
SV9A
SV9B
X38

CNTR
(Red)

7
7

8
8

T8

9
9

X16

1
2

X15

3
2
1

4
4

T7

5
5

6
6

X14

CONT.B

X13

SV8C
SV8A
SV8B
X37

SV7C
SV7A
SV7B
X36

Indoor/outdoor (heat source)


Transmission line

CN39

TB02
S(SHIELD)
M2
M1

3 2 1

X57

X55

X56

CN45(Green)

X54

X52

X53

CN44(Yellow)

X51

X49

X50

CN43(Red)

X48

X46

X47

CN42

X45

X43

X44

CN41(Green)

X42

X40

X41

CNVCC2
(Blue)
CN40
(Yellow)

1 3

4 4

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

REL.B

1
2
3

T11

T16

T15

T14

T13

SVM1
SVM2

SV16B
SV16A
SV16C

SV15B
SV15A
SV15C

CMB-P1016NU-GA ONLY
SV14B
SV14A
SV14C

SV13B
SV13A
SV13C

SV12B
SV12A
SV12C

SV11B
SV11A
SV11C

Name
Transformer
Thermistor sensor
Expansion valve
Pressure sensor
Circuit Relay
board BC controller
Terminal block
(for power source)
Terminal block
(for Transmission)
Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

T12

TB02
SV1~16A,B,C
SVM1,2
T1~16
F01

TB01

Symbol
TR
TH11,12,15,16
LEV1~3
PS1,3
REL.B
CONT.B

(Symbol explanation)

CMB-P1013,1016NU-GA

CN35(Blue)

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

TR

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-GA_EWD_USDB_P1013-1016

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-19

CN32

CN33(Red)

CN34(Black)

BC-20

TH15

TH12

ON

CN11

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


1

LEV3

1 2 3 4 5 6

SW5

SW4
8

DSA

ZNR01

ZNR02

CN12

F01
250VAC
6.3A F

3 5

T2

T1

T4

T3

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

Indoor/outdoor (heat source)


Transmission Line

POWER SUPPLY
~208V-230V
60Hz

BREAKER(15A)

FUSE(15A)

TB01 TO NEXT INDOOR UNIT


L1
L2
PULL BOX

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

TB02
S(SHIELD)
M2
M1

Name
Transformer
Thermistor sensor
Expansion valve
Circuit BC controller
board
Terminal block
(for power source)
Terminal block
(for Transmission)
Solenoid valve
Terminal
Fuse AC250V 6.3A F
Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

TB02
SV1~4A,B,C
T1~4
F01

TB01

CONT.B

Symbol
TR
TH12,15
LEV3

(Symbol explanation)

CMB-P104NU-GB

CN07
(Yellow)

OFF

ON

OFF

SW1

X33

SW2
1

X7

CN29(Green)

X8

X32

CN10

CN28(Blue)

X31

X3

X4

X5

CN26

CN27(Red)

X30

X1

X2

10

CN02

CN03
(Yellow)

CN13
(Red)

2 1

3 2 1

CNTR
(Red)

X6

1
2

CONT.B

TR

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-GB_EWD_USDB_P104

TH15

TH12

10

CN11

CN07
(Yellow)

LEV3

1 2 3 4 5 6

OFF

ON

OFF

ON

SW5

SW1

SW4

SW2

ZNR01

ZNR02

CN12

DSA F01
250VAC
6.3A F

1 3 5

X35

X11

CN31(Yellow)
X12

X34

X9

CN30(Black)
X10

X7
X33

CN29(Green)
X8

X32

CN10

X5

CN28(Blue)

X31

X3

X4

CN26

TB01
L1
L2

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

T6

T5

T4

T3

T2

T1

SV6B
SV6A
SV6C

SV5B
SV5A
SV5C

SV4B
SV4A
SV4C

SV3B
SV3A
SV3C

SV2B
SV2A
SV2C

SV1B
SV1A
SV1C

CN39

3
1

16
16

CN35(Blue)

15 14 13
15 14 13

POWER SUPPLY
~208V-230V
60Hz
FUSE(15A) BREAKER(15A)

PULL BOX

TO NEXT INDOOR UNIT

CN34(Black)

CN27(Red)

X30

X1

X2

CNTR
(Red)

X6

CN13
(Red)

1 3

CN38

1
2

CN50

X20

CN02

X19

CN03

7 6 5 4 3 2 1

X39

2 1

CN33(Red)

CN32

4
4

2 1

5
5

T7
3

6
6

CN52

7
7

8
8

T8
3

9
9

7 6 5 4 3 2 1

12 11 10
12 11 10

X18

3 2 1

X17

CONT.B

X38

REL.B

Name
Transformer
Thermistor sensor
Expansion valve
Circuit Relay
board BC controller
Terminal block
TB01
(for power source)
Terminal block
TB02
(for Transmission)
SV1~8A,B,C Solenoid valve
T1~8
Terminal
F01
Fuse AC250V 6.3A F

X14

TB02
S(SHIELD)
M2
M1

X16

Symbol
TR
TH12,15
LEV3
REL.B
CONT.B

CMB-P108NU-GB

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

TR

X15

(Symbol explanation)

X13

SV8C
SV8A
SV8B
X37

SV7C
SV7A
SV7B
X36

Note:1.TB02 is transmission
terminal block.
Never connect power
Indoor/outdoor (heat source)
line to it.
Transmission line
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-GB_EWD_USDB_P108

BC-21

2 1

1
2
3
4
5
6

CN07
(Yellow)

CN11

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)


CN12

DSA

1
3 5

X10

X35

X11

X12

CN31(Yellow)

X34

X09

CN30(Black)

X33

X07

X08

CN29(Green)

X32

X05

X06

CN28(Blue)

X31

X03

X04

CN27(Red)

X30

X01

X02

CN26

CNTR(Red)

L2

3 T1

SV3A

SV4A

SV5A

SV6C

SV6A

3 T6
4

SV6B

2
3

SV5C

SV5B

3 T5
4

SV4C

SV4B

3 T4
4

SV3C

SV3B

3 T3
4

SV2C

SV2A

3 T2
4

SV2B

SV1C

SV1A

2
4

SV1B

2
3

16
16

FUSE(15A) BREAKER(15A)

TO NEXT
INDOOR UNIT
POWER SUPPLY
TB01
~208V-230V
PULL BOX
L1

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

2.The initial set values of swith


on CONT.B are as follows.
SW1:0
SW2:0

F01
250VAC
6.3A F

ZNR02

3 1

ZNR01

CNOUT3

CNOUT1

CN38

LD1:CPU in
operation

SW6

SW5

SW4

CONT.B

SW2 SW1

ON
OFF

ON
OFF

CN10

CN13
(Red)

ON
OFF

10

3 2 1

T10

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

15 14 13
15 14 13

T9

12 11 10
12 11 10

REL.B

7
7

8
8

T8

9
9

4
4

5
5

T7

6
6

3 2 1

CNVCC2
(Blue)

X57

X55

X56

CN45(Green)

X54

X52

X53

CN44(Yellow)

X51

X49

X50

CN43(Red)

X48

X46

X47

CN42

X45

X43

X44

CN41(Green)

X42

X40

X41

CN40
(Yellow)

1 3

4 4

3 3

2 2

1 1

16 16

15 15

2
3
4

3T16

4
4
1

3T15
3

2
14 14

13 13

3T14

1
2

3T13

3T12

4
1

3T11
4

1
3

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

SV16C

SV16A

SV16B

SV15C

SV15A

SV15B

SV14C

SV14A

SV14B

SV13C

SV13A

SV13B

SV12C

SV12A

SV12B

SV11C

SV11A

SV11B

Transformer
Thermister sensor
Expansion valve
Circuit Relay
board BC controller
Terminal block
TB01
(for power source)
Terminal block
TB02
(for Transmission)
SV1~16A,B,C Solenoid valve
T1~T16
Terminal
F01
Fuse AC250V 6.3A F

TR
TH12,15
LEV3
REL.B
CONT.B

(Symbol explanation)
Symbol
Name

CMB-P1016NU-HB

Note:1.TB02 is transmission terminal


block.Never connect power line
to it.

LEV3

TH15

TH12

1
2

3 2 1

CNVCC1 CN03 CN02


(Blue) (Yellow)

SV10C

X20

Indoor/outdoor
Transmission line

SV10A

X19

SV9C

X18

SV10B

X39

SV9A

X17

TB02
S(SHIELD)
M2
M1

CN34(Black)

SV9B

X38

TR

CN33(Red)

SV8C

X16

SV7C

X14

SV8A

X15

SV7A

X13

SV8B

X37

SV7B

X36

BC-22
CN39

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

3. ELEctrical Wiring Diagrams


DATA U4

Ref. : CMB_NU-HB_EWD_USDB_P1016

CN32

CN35(Blue)

4. Refrigerant Circuit Diagrams and Thermal Sensors

DATA U4

CMB-P104 - P1016NU-G (Single)

Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1
TH11

PS3
LEV1

SVM1

TH16
Check valve block

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-23

4. Refrigerant Circuit Diagrams and Thermal Sensors


CMB-P108, P1013, P1016NU-GA (Main)

Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1
TH11

SVM2

PS3
LEV1

TH16

LEV2

Check valve block

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

SVM1

CMB-P104, P108NU-GB (Sub)

Solenoid valve block

TH12
CP

TH15
HIC-C

LEV3

Check valve block

BC-24

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

DATA U4

4. Refrigerant Circuit Diagrams and Thermal Sensors

DATA U4

CMB-P1016NU-HB (Sub)

Solenoid valve block

TH12
CP

TH15
HIC-C

LEV3

Check valve block

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-25

5. SOund Pressure Levels

DATA U4

5-1. BC Controller Steady State Sound


BC Controller

1m (3-1/2 ft.)
Measurement
Location

CMB-P105~P1016NU-G
CMB-P108~P1016NU-GA
CMB-P104, P108NU-GB
CMB-P1016NU-HB

Measured when the solenoid


control valve operates

63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz


29

36

36

38

35

31.5

Octave Band Pressure Levels (dB) 0dB = 0.0002bar

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

Measured in an anechoic chamber

Approximate minimum
audible limit on continuous
sound

Octave Band Center Frequencies (Hz)

BC-26

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

29

25

Weighted
Average (dB)
40

5. SOund Pressure Levels

DATA U4

5-2. BC Controller Peak Sound


CMB-P105~P1016NU-G
CMB-P108~P1016NU-GA
CMB-P104, P108NU-GB
CMB-P1016NU-HB

Measured when the solenoid


control valve operates

BC Controller

1m (3-1/2 ft.)
Measurement
Location

27.5

Weighted
Average (dB)
49

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

BC-27

63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz


29.5

36.5

35.5

37

34

31

47

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

Octave Band Pressure Levels (dB) 0dB = 0.0002bar

Measured in an anechoic chamber

Approximate minimum
audible limit on continuous
sound

Octave Band Center Frequencies (Hz)

6. Optional Parts

DATA U4

6-1. BV-Series Ball Valves

CMB-P-NU-G
CMB-P-NU-GA
CMB-P-NU-GB/-HB

Fully factory assembled


Furnace brazed and pressure tested
Each ball valve is equipped with Schrader Valve for refrigerant
service
Design working pressure: 700 PSIG
Temperature range: -40F to +325F (-40C to +149C)
Forged brass body and seal cap
SAE
Model Number
A
B
C
D
Teflon seals and gaskets (no synthetic O-rings)
Flare
Seal cap design permits valve operation without
BV14FFSI
6.19
2.60
1.80
1.22
1/4"
removing seal cap
BV38FFSI
6.30
2.67
1.80
1.22
3/8"
Suitable for use with R-11, R-22, R-123, R-125,
R-134A, R-236FA, R-4202A, R-402B, R-404A,
BV12FFSI
6.51
2.67
1.80
1.22
1/2"
R-407C, R-410A, R-500, R-502, and R-507
BV58FFSI
6.64
2.67
1.80
1.28
5/8"
One year limited materials and workmanship
warranty on Ball Valves
*Insulation piece is included with the ball valves.

6-2. BV-Series Ball Valve Insulation


Materials:
InsulationInner and outer layer Polyethylene foam (PEF)
CoveringAdhesive tape of Polyvinyl chloride (PVC)
SeparatorSoft film of Polyvinyl chloride (PVC)

Model Number

d1
1-3/8"
(30mm)

HKG-20HF

(D)

L1

Physical Properties of the Insulation


Density

1.87 lb./ft.3 (30 kg/m3)

Heat Conductivity (at 23C)


Tensile Strength
Heat Resistant
UL-94

BC-28

0.040 W/mK
23 N/cm2
176F (80C)
HF-1

(d2)

3/4"
2-3/4"
8-9/16"
7/8"
(20mm) (70mm) (220mm) (11mm)

(d3)

(L2)

(L3)

1-9/64"
(29mm)

1-15/32"
(37mm)

2-7/8"
(73mm)

Ball Valve Accessories


Model Number

Female Flare X Solder Adaptor

BVUS5-44

1/4"

BVUS5-66

3/8"

BVUS5-88
BVUS5-1010

1/2"
5/8"

CMB-P-NU-G/CMB-P-NU-GA/CMB-P-NU-GB/-HB (Feb. 2009)

1.42

1.10

1.42

1.10

1.42

1.10

1.42

1.10

DATA U4

CITY MULTI
CONTROLLER
1. MITSUBISHI ELECTRICs Air-conditioner Network System (MELANS)..............................................CNTR-2
1-1. Function table of controllers.........................................................................................................................CNTR-3
2. Local remote controller..........................................................................................................................CNTR-4
2-1. Deluxe MA remote controller [PAR-21MAA].................................................................................................CNTR-4
2-2. ME remote controller [PAR-F27MEA-US]....................................................................................................CNTR-5
2-3. Simple MA remote controller [PAC-YT51CRB].............................................................................................CNTR-6
2-4. Wireless remote controller [PAR-FL32MA / PAR-FA32MA]..........................................................................CNTR-7
2-5. LOSSNAY M-NET remote controller [PZ-52SF]...........................................................................................CNTR-8
3. System controller.......................................................................................................................................CNTR-9
3-1. System group controller [PAC-SF44SRA]....................................................................................................CNTR-9
3-2. Schedule timer [PAC-YT34STA].................................................................................................................CNTR-11
3-3. ON/OFF controller [PAC-YT40ANRA]........................................................................................................CNTR-13
3-4. Central controller [G-50A]..........................................................................................................................CNTR-15
3-5. Central controller [GB-50A]........................................................................................................................CNTR-23
3-6. Central controller [AG-150].........................................................................................................................CNTR-31
3-7. Central controller [GB-24]..........................................................................................................................CNTR-39
3-8. Power supply unit [PAC-SC50KUA]............................................................................................................CNTR-47
3-9. Power supply unit [PAC-SC51KUA]............................................................................................................CNTR-50
3-10. Integrated centralized control software [TG-2000A]...................................................................................CNTR-53
3-11. Electric amount count software [PAC-YG11CDA]......................................................................................CNTR-57
3-12. PLC software for general equipment [PAC-YG21CDA (SW-PLC-GE)]......................................................CNTR-58
3-13. BACnet interface [PAC-YG31CDA (SW-BACnet)]....................................................................................CNTR-59
3-14. PLC software for demand input [PAC-YG41CDA]......................................................................................CNTR-60
3-15. LonWorks interface [LMAP03U]...............................................................................................................CNTR-62
3-16. DIDO Controller [PAC-YG66DCA]..............................................................................................................CNTR-64
3-17. AI Controller [PAC-YG63MCA]...................................................................................................................CNTR-69
3-18. Transmission booster [PAC-SF46EPA].......................................................................................................CNTR-74

CONTROLLER (Feb. 2009)

CNTR-1

CONTROLLER

4. System component......................................................................................................................................CNTR-75
4-1. Y-, R2-, S-Series........................................................................................................................................CNTR-78
4-2. Outdoor unit input/output connector (Y-, R2-, S-Series).............................................................................CNTR-79
4-3. Indoor unit -E type input/output connector (Y-, R2-, S-Series).................................................................CNTR-81

1. Mitsubishi Electrics Air-Conditioner Network System (MELANS)

DATA U4

MELANS has a large line-up, including local remote controllers, timers, group controllers, central controllers,
integrated system software, PLC and its software, as well as BMS interface hardware and software. The
combination of the MELANS products can fulfill the requirements of small-scaled control system, middlescaled control system up to 2,000 indoor units, and/or large-scaled open systems affiliated with a BMS system.
Moreover, with central controller G-50A/GB-50A, PC browser and remote access (monitoring and operating) via
communication network is possible and easy.

All of the local remote controllers


feature liquid crystal LED displays
and are easy to operate.

Group

24
I/O
Controllers

CONTROLLER

(SW-BACnet)
This is a middle-scaled air
conditioning management
system, in which up to 2,000
indoor units can be centrally
controlled

MITSUBISHI ELECTRICs CITY MULTI can be


easily connected to the building management
system through BACnet.

CNTR-2

CONTROLLER (Feb. 2009)

1. Mitsubishi Electrics Air-Conditioner Network System (MELANS)

DATA U4

1-1. Function table of controllers


4

4
4

GB-24A Browser *4

CONTROLLER

LMAP03U: LonWorks Interface


Controls up to 50 Groups/ 50 Indoor,
Details refer to its description.
PAC-YG31CDA: BACnet Interface Software
(SW-BACnet)
Controls up to 500 Groups/ 500 Indoor,
For details, see its description.

CONTROLLER (Feb. 2009)

CNTR-3

2. Local remote controller


2. Local Remote Controller

DATA U3

DATA U4

2-1. Deluxe MA remote controller [PAR-21MAA]


Functions
Item
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER

ERROR CODE

WEEKLY
SIMPLE
AUTO OFF

ONLY1Hr.

TEMP.

MENU

PAR-21MAA

MONITOR/SET

ON/OFF

FILTER

CLOCK

Operation mode
switching
Temperature
setting

Sets the temperature for a single group


Range of temperature setting
Cool/Dry :
:
Heat
Auto
:

Fan speed
setting

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low

Air flow
direction
setting

Air flow direction angles 100% - 80% - 60% - 40%, Swing,


Louver ON/OFF
Air flow direction settings vary depending on the model.

CHECK TEST

OPERATION

( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.

CLEAR

High-quality white color body and light-green display.


Dot liquid-crystal display is applied.
Choose from Japanese, Chinese, English, Germany,
Spanish, Russian, Italian, French displays.
Connectable to all CITY MULTI indoor unit, and automatically adjust its function with the indoor unit connected.
Limiting temperature setting range is possible.
Help to avoid over-cooling or over-heating. Save energy.
Auto-stop timer is available.
Help to avoid forgetting to stop the air conditioner.
Weekly timer is available.
ON/OFF/Temperature setting 8 times per day, 1 week
scheduling.
Grouping via cross-over wire directly.
Usable as the local remote controller for system
controller (MELANS)
Combining ME remote controller and/or LOSSNAY
remote controller in a group is not possible.

Weekly
Timer

ON/OFF/Temperature setting can be done up to 8 times one


day in the week.
The time can be set by the minute.

Permit / Prohibit
local operation

Individually prohibit operation of each local remote control


function (Start/Stop, Change operation mode, Set
temperature, Reset filter).
1: When the local remote controller inactivation command
is received from the master system controller,
" " is displayed.

Prohibition/permission
of specified mode
(Cooling prohibited
/heating prohibited
/cooling-heating prohibited)

By the setting from System Controller, the operation for the


following modes is prohibited.
At cooling prohibited
: Cool, Dry, Auto,
At heating prohibited
: Heat, Auto,
At cooling-heating prohibited : Cool, Heat, Dry, Auto

Indoor unit intake


temperature

Measures the intake temperature of the indoor unit when


the indoor unit is operating.

Error

When an error is currently occurring on an air conditioner


unit, the afflicted unit and the error code are displayed.

Test run

This operates air conditioner units in test run mode.

Ventilation
equipment

CONTROLLER

System example

Non-polarized
2-wire

Non-polarized
2-wire
MA
remote
controller

:Not available

Operations Display

Description
Run and stop operation for a single group

ON/OFF

DAY

:Each block

:Collective

Switches between Cool / Dry / Auto / Fan / Heat.


Operation modes vary depending on the air conditioner unit.
Auto mode is only for the CITY MULTI R2- and WR2-Series.

TEMP.

BACK

:Each group

:Each floor
ON/OFF

AFTER OFF

FUNCTION
FILTER

:Each unit

Up to 16 indoor units can be connected to an interlocked


system that has one LOSSNAY. LOSSNAY items that can
be set are "Hi" "Low" "Stop". Ventilation mode switching is
not available.

Function to limit
the setting range
of room
temperature
(Set temperature
range limit)

The range of room temperature setting can be limited by the


initial setting.The lowest limit temperature can be made higher
ying, while the upper
limit temperature lo

Easy-to-operate
simplified locking
function
(Auto lock function)

Setting/releasing of simplified locking for remote control


switch can be performed.
Locking of all switches
Locking of all switches except Start/Stop switch

MA
remote
controller

External dimension
(Side view)

(Rear view)

19
[ 3/4 ]

46 [1-13/16]

120 [4- 23 /32 ]

130 [5-1/8 ]

CNTR-4

Unit:mm[in.]

83.5 [3- 9 /32 ]

(Front view)

CONTROLLER (Feb. 2009)

2. Local remote controller


2. Local Remote Controller

DATA U3

DATA U4

2-2. ME remote controller [PAR-F27MEA-US]

2-2. ME remote controller [PAR-27MEA-US]


Functions
Item

SET TEMP.
TIMER

PAR-F27MEA-US

FAN SPEED

AIR DIRECTION

LOUVER

VENTILATION

Operations Display

Description
Switches between Cool / Dry / Auto / Fan / Heat.
Operation modes vary depending on the air conditioner unit.
Auto mode is only for the CITY MULTI R2- and WR2-Series.

FILTER

Three timer modes are available with its enhanced


timer function.
The room temperature can be limited by the initial
setting. By setting the room temperature range
narrower than usual setting, cooling/heating operation with excessive temperature can be prevented and thus save energy.
Allows for simple button locking function.

:Not available

Operation mode
switching
Temperature
setting

Sets the temperature for a single group


Range of temperature setting
Cool/Dry :
:
Heat
Auto
:

( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.

CHECK TEST

TIMER SET

:Each block

:Collective

Run and stop operation for a single group

ON/OFF
CLOCK ON OFF

:Each group

ON/OFF

SET TEMP.

MODE

:Each unit
:Each floor

Fan speed
setting

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low

Air flow
direction
setting

Air flow direction angles 100% - 80% - 60% - 40%, Swing,


Louver ON/OFF
Air flow direction settings vary depending on the model.

Permit / Prohibit
local operation

Individually prohibit operation of each local remote control


function (Start/Stop, Change operation mode, Set
temperature, Reset filter).
1: When the local remote controller inactivation command
is received from the master system controller, "CENTRALLY CONTROLLED -" is displayed.

Indoor unit intake


temperature

Measures the intake temperature of the indoor unit when


the indoor unit is operating.

Error

When an error is currently occurring on an air conditioner


unit, the afflicted unit and the error code are displayed.

Timer operation

Thanks to the three timer modes equipped, a proper mode


can be selected to meet the usage.
One day timer : ON/OFF setting of one time on one day can be applied.
Daily timer
: ON/OFF setting by the One day timer can be repeated for
everyday.
Auto OFF timer : OFF timer can be set in a range from 30 minutes to 4 hours.

Setting of Auto OFF timer automatically activates OFF timer at the next operation.
This function can be utilized to prevent the negligence of OFF setting.
Weekly schedule in only one patterns can be employed by connecting Program timer. 2

System example

This operates air conditioner units in test run mode.

Function to limit
the setting range
of room
temperature
(Set temperature
range limit)

The range of room temperature setting can be limited by the


initial setting.The lowest limit temperature can be made higher
ying, while the upper
limit temperature lo

Easy-to-operate
simplified locking
function
(Auto lock function)

Setting/releasing of simplified locking for remote control


switch can be performed.
Locking of all switches
Locking of all switches except Start/Stop switch

When making the function to limit room temperature setting range


effective, the operation mode cannot be set to the auto mode.

CONTROLLER

ME
remote
controller

Test run

ME
remote
controller

External dimension
(Side view)

(Rear view)

130 [5-1/8 ]

19
[ 3/4 ]

46 [1-13/16]

Unit:mm[in.]

120 [4- 23 /32 ]

83.5 [3- 9 /32 ]

(Front view)

CONTROLLER (Feb. 2009)


CONTROLLER

CNTR-5
Cntr- 5

2. Local Remote Controller

DATA U4

2-3. Simple MA remote


controller [PAC-YT51CRB]

:Each unit

:Each group

:Each block

:Each floor

:Collective

:Not available

Description

Item
ON/OFF

Run and stop operation for a single group

Operation mode
switching

Switches between Cool / Dry / Auto / Fan / Heat.


Operation modes vary depending on the air conditioner unit.
Auto mode is the CITY MULTI R2- and WR2-Series only.

Temperature
setting

Operations Display

Sets the temperature for a single group


Range of temperature setting
Cool/Dry :
:
Heat
Auto
:
( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to
HIGH fan speed only.

Control: START/STOP, room temperature, fan


speed, and operation mode selection
The only wiring required is cross-over wiring based
on two-wire signal lines.
Room temperature sensor is built in
LCD temperature setting and display in 1C /1F
unit.
Set temperature range limit
Can operate all types of indoor units
If additional features are needed beyond Simple MA
PAC-YT51CRB capabilities, use it in conjunction with
Deluxe MA PAR-21MAA or Central Controllers AG-150A,
G-50A, GB-50A or GB-24.
Using Simple MA PAC-YT51CRB in combination with
PAR-F27MEA-US M-NET Remote Controller is not
permitted inside a group.

CONTROLLER

Dimensions: 2-3/4 (W) x 4-3/4 (H) x 1-5/8 (D) in.

Fan speed setting

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low
Fan speed setting varies depending on the model.

Air flow direction


setting

Air flow direction angles (4-angle, Swing) Louver ON/OFF


Air flow direction settings vary depending on the model.

Timer operation

Not available

Permit / Prohibit
local operation

Individually prohibit operation of each local remote control


function (Start/Stop, Set temperature).
1: When the local remote controller inactivation command is
received from the master system controller, "CENTRAL" is
displayed.

Indoor unit intake


temperature

Measures the intake temperature of the indoor unit only when


the indoor unit is operating.

Error

When an error is currently occurring on an air conditioner unit,


the afflicted unit and the error code are displayed.

Test run

This operates air conditioner units in test run mode.


2: The display for test run mode will be the same as for normal
start/stop (no display "test run").

Ventilation
equipment

Function to limit
the setting range
of room temp.
(Set temperature
range limit)

The range of room temperature setting can be limited by the


initial setting.The lowest limit temperature can be made higher
than the usual (67F/19C) at cooling/drying, while the upper
limit temperature lower than the usual (83F/28C) at heating.

Prohibition/permission
of specified mode
/heating prohibited
/cooling-heating
prohibited)

By the setting from System Controller, the operation for the


following modes is prohibited.
At cooling prohibited
: Cool, Dry, Auto,
At heating prohibited
: Heat, Auto,
At cooling-heating prohibited : Cool, Heat, Dry, Auto

CENTRALIZED CONTROLLER AG-150A

AG-150A
PAC-SC51KUA
Power supply

CNTR-6

Up to 16 indoor units can be connected to an interlocked system


that has one LOSSNAY.
3: The interlocked LOSSNAY will be enabled when the indoor
unit(s) are enabled. LOSSNAY ON/OFF status is displayed
on the Simple MA PAC-YT51CRB. Fan speed and ventilation
mode switching are not available through the Simple MA.

CONTROLLER (Feb. 2009)

2. Local Remote Controller


2-4. Wireless remote controller
[PAR-FL32MA / PAR-FA32MA]

DATA U4

Functions

HEAT

PAR-FL32MA

It can operate in a group system without requiring


address settings.
When operating, it displays LED lamps. When
errors occur, the error code can be shown by the
LED flash count.

If an indoor unit with different functionality is operating inside the


same group, please note there may be cases when functionality
is partially disabled for batch control.
Wireless remote controllers can only be used for a single refrigerant system.
If you use a system controller to centrally control a group, you
will need cross-wiring between indoor units when using a wireless remote controller.
Also ensure there is no difference between the group setting of
the main system controller and the cross wiring across indoor
units when wiring and setting cross wires.

:Each block

:Collective

:Not available

Operations Display

ON/OFF

Run and stop operation for a single group

Operation mode
switching

Switches between Cool / Dry / Fan / Heat / Auto.


Operation modes vary depending on the air conditioner unit.
Auto mode is only for the CITY MULTI R2- and WR2-Series.

Temperature
setting

Sets the temperature for a single group


Range of temperature setting
Cool/Dry :
Heat :
Auto :

Fan speed setting

Models with 4 air flow speed settings: Hi/Mid-2/Mid-1/Low


Models with 2 air flow speed settings: Hi/Low

Air flow direction


setting

Air flow direction angles 100% - 80% - 60% - 40%, Swing.


Air flow direction settings vary depending on the model.

Timer operation

One ON/OFF setting can be set for one day.

COOL

PAR-FA32MA
(Signal receiving unit)

:Each group

:Each floor
Description

Item

ON/OFF

:Each unit

Permit / Prohibit
local operation

Individually prohibit operation of each local remote control


function (Start/Stop, Change operation mode, Set temperature,
Reset filter).
If operation is performed when the local remote controller
inactivation command is received from the main system
controller, a buzzer will ring and an LED will flash.

Indoor unit intake


temperature

Measures the intake temperature of the indoor unit when the


indoor unit is operating.

Error

When an error occurs on the air conditioner unit, the operation


lamp on the signal receiving unit will flash.

Test run

This operates air conditioner units in test run mode.

Ventilation
equipment

Up to 16 indoor units can be connected to an interlocked system


that has one LOSSNAY.
Some models will have different display for the air flowdirection and fan speed.
Set the air flow direction and fan speed when performing initial setting.

System example

Signal
receiving
unit
Wireless
remote
controller

Wireless
remote
controller

Nonpolarized
2-wire

Signal
receiving
unit

CONTROLLER

Non-polarized
2-wire

Signal
receiving
unit

Nonpolarized
2-wire

Wireless
remote
controller

External dimension
PAR-FL32MA
58[2-9/32]

19[3/4]
22.5[7/8]

70[2-3/4]
CHECK TEST RUN
MODEL SELECT

Unit:mm[in.]

PAR-FA32MA
9.9[3/8]
4.8[3/16]

%C
AMPM

COOL

4.6
[3/16]

HEAT

120[4-23/32]

ON/OFF

159[6-1/4]

TEMP

35.2[1-3/8]
83.5[3-9/32]

19[3/4]

AMPM
NOT AVAILABLE

ON/OFF

CONTROLLER (Feb. 2009)

9.2[3/8]

CNTR-7

2. Local Remote Controller

DATA U4

2-5. LOSSNAY M-NET remote controller [PZ-52SF]


Functions
ON/OFF

HEAT EX.
BY-PASS
AUTO

CHECK
NOT AVAILABLE FILTER

Operation mode
switching

ON/OFF

FILTER

Stand-alone LOSSNAY operation is possible by


commands from a central controller or LOSSNAY
remote controller. (AG-150A/G(B)-50A/GB-24A is a
central controller that supports LOSSNAY operation.)
The LOSSNAY remote controller is capable of
changing the air flow and vent modes.
All the wiring is cross-wiring that uses non-polar
two wire system signal cables.

:Each block

:Collective

:Not available

Operations Display

Run and stop operation for a LOSSNAY unit


Switches between automatic ventilation/ vent - heat
interchange/ normal ventilation
Note: Operation modes vary depending on the model.
When connecting to only models without a damper,
these models cannot be used.("NOT AVAILABLE" will
appear in the display.)

Temperature
setting

Not available

Fan speed setting

Models with 2 air flow speed settings: Hi/Low


When only connected to single notch models, this function is
disabled.

Air flow direction


setting

Not available

Timer operation
Permit / Prohibit
local operation

Not available
Individually prohibit operation of each local remote control
function (Start/Stop, Reset filter).
1: When the local remote controller inactivation command is
received from a master system controller, " CENTRAL " is
displayed.

Indoor unit intake


temperature

Not available

Error

When an error occurs on the air conditioner unit, the operation


lamp on the signal receiving unit will flash.

Test run

There is no test run switch for LOSSNAY remote controllers.


Set test run on a LOSSNAY by using the test run switch on the
LOSSNAY unit.
2: Cancel by operating the start/stop switch after switching off
the LOSSNAY unit test run switch.

Ventilation
equipment

Up to 16 indoor units can be connected to an interlocked system


that has one LOSSNAY.

Interlocked
operation

This is displayed to indicate it is being operated by an operation


control unit's external control terminal for an interlocked system
that contains LOSSNAY units and indoor units.

External dimension

System example

Unit:mm[in.]

LOSSNAY remote
controller

LOSSNAY
unit

ABS

LOSSNAY
unit

LOSSNAY remote
controller

REMOTE CONTROLLER
MODEL

ON/OFF

LOSSNAY
unit
LOSSNAY remote
controller

LOSSNAY
unit

LOSSNAY
unit

LOSSNAY
unit

PAC-SC51KUA
Power supply

LOSSNAY remote
controller

FILTER

70[ 2-3/4 ]

48[1-7/8 ]

CNTR-8

CONTROLLER (Feb. 2009)

8
[5/16] 33[1-5/16 ]
(41[1- 5/8])

PZ-52S F-E

INPUT VOLTAGE
WEIGHT
SERIAL No.
MADE IN JAPAN

DC30V
0.02A
0.15kg

KT79C117H01

83.5[3-9/32 ]

LOSSNAY
unit

78[3-1/16]

LOSSNAY
unit

120[ 4-23/32]

CONTROLLER

: When setting up a LOSSNAY stand-alone system or when setting up a LOSSNAY and central controller system, connect a
power supply unit for the signal cables.
: It is impossible to use a LOSSNAY remote controller for LOSSNAY unit that is interlocked other indoor unit (except for some
models).

:Each group

:Each floor
Description

Item
CENTRAL INTERLOCKED

:Each unit

3. System Controller

DATA U4

3-1. System group controller [PAC-SF44SRA]

Auto only supported for the CITY MULTI R2- and WR2-Series.

( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only.

CONTROLLER

CONTROLLER (Feb. 2009)

CNTR-9

3. System Controller

DATA U4

System example

System
remote
controller

PAC-SC51KUA
Power supply

MA remote
controller

LOSSNAY

MA remote
controller

LOSSNAY

LOSSNAY
LOSSNAY
remote
controller

LOSSNAY
remote controller

External dimension

18.5
2[3/32 ] [23/32 ]

(Rear view)

120[ 4-23/32 ]

130[5-1/8 ]

(Side view)

83.5[ 3-9/32 ]

CONTROLLER

Unit:mm[in.]

(Front view)

19
[ 3/4 ]

CNTR-10

CONTROLLER (Feb. 2009)

46[1-13/16]

3. System remote controller


3. System Controller

DATA U3

DATA U4

3-2. Schedule timer [PAC-YT34STA]

3-2. Schedule timer [PAC-YT34STA]


Functions
MONITOR
PATTERN Sun Mon Tue Wed Thu Fri Sat
WEEKLY SET
COLLECTIVE
GROUP
OPERATION
ON
ON

CHECK

OFF

TIMER OFF

SET TEMP.

PROH.

: Each group

: Each floor

: Group or collective

Details

Item

ON/OFF

: Each unit

Unit control

50 units/50 groups (Maximum 16 units connected in one group)

Schedule control

One week

: Each block
: Not available

Operations Display

PERMIT

ON/OFF
MODE
TEMP.

Operation

ON/OFF
Timer reset
Setting
details

Schedule
function
Number of
settings

The weekly schedule of up to 50 groups/50 units


can be controlled with one schedule timer.
The weekly schedule of up to ten patterns (no setting + nine patterns) is available for setting.
"ON/OFF", "Operation Prohibit", "COOL /HEAT"
and "Set Temperature" can be scheduled with up
to 16 settings in one pattern.
It can be connected to the central control transmission line or to the indoor/outdoor transmission
line without the power supply unit. It is non-polar
2-wire.
It can be interlocked with a building management
system using the external input/output managing
function.
An error unit address and error code appear on
the display in case of malfunction happening.

Time setting unit

ON/OFF operations can be carried out collectively or for each


group.
The timer setting details can be disabled collectively
ON/OFF
COOL/HEAT
Operation prohibit (ON/OFF, operation mode, setting temperature)
Number of setting patterns: Ten (no setting + nine patterns)
(Operation for a week can be set by selecting one of ten
patterns for each day.)
Number of operations: Up to 16 operations can be set in one pattern
The item can be set in five-minute units
Current time and day

Display

Error state
Unit operation state

External input
(Timer connection,
emergency stop
input, etc.)

The following can be input with the level signals or pulse signals.
Level signal: "Emergency stop input" or "Collective ON/OFF"
Pulse signal: "Collective ON/OFF" or "Local remote controller
prohibit/permit"
One input can be selected from those above.

External output
(Error output,
operation output)

"ON/OFF" and "error/normal" are output with the level signal.


The optional output cable is required.

Connection position

Indoor/outdoor transmission line: Connectable


Central system transmission line: Connectable (Optional power
supply unit (PAC-SC50KUA) is needed.)

CONTROLLER

CONTROLLER (Feb. 2009)


CONTROLLER

CNTR-11
Cntr- 12

3. System Controller

DATA U4

System example

System
group
controller

LOSSNAY

PAC-SC51KUA
Power supply

PAR-F27MEA-US

Schedule timer

PAR-21MAA

PAC-YT51CRA

External dimension

18.5
2[3/32 ] [23/32 ]

(Rear view)

120[ 4-23/32 ]

130[5-1/8 ]

(Side view)

83.5[ 3-9/32 ]

CONTROLLER

Unit:mm[in.]

(Front view)

19
[ 3/4 ]

CNTR-12

CONTROLLER (Feb. 2009)

46[1-13/16]

3. System
System remote
controller
3.
Controller

DATA U3

DATA U4

3-3. ON/OFF
ON/OFF remote
controller
[PAC-YT40ANRA]
3-3.
controller
[PAC-YT40ANRA]
Functions
CENTRALIZED

ON/OFF

Operation mode
switching

16 groups/50 units can be controlled.


Up to 16 groups/50 units can be operated with
one ON/OFF remote controller.
A general-purpose interface is available for control, so general devices can also be turned ON
and OFF.
Just press a switch to start.
All of the units can be started and stopped by
pressing the main switch, and each unit in the
group can be started and stopped with individual
switches.
LED flashing during failure.
If any error should occur in the air conditioner, its
details can be confirmed easily with the flashing
LED. The LED also indicates whether each group
is running or stopped.
operation with
with external
external system
system possible.
possible.
IInterlock
nterlock operation
It
can
be
flexibly
interlocked
with
a
card
It can be flexibly interlocked with a card reader,
reader,
fire
alarm system
or building
management
or building
management
system,
etc., usingsysthe
tem,
etc., using
the incorporated
incorporated
external
input/outputexternal
function.
input/output
Flexible
groupfunction.
setting.
Flexible
groupcan
setting.

The groups
be easily configured, so the
The
groups
can
bebe
easily
so the
group pattern can
freelyconfigured,
set according
to the
group pattern can be freely set according to the
layout.
layout.
The ON/OFF controller can be connected
The ON/OFF remote controller can be connected
at the indoor/outdoor transmission line without
at the indoor/outdoor transmission line without
the power supply unit.
the power supply unit.

.
.
.
.

.

: Each group

: Each block

: Each floor

: Group or collective

: Not available

Description

Item
ON/OFF

: Each unit

Operations Display

Run and stop operation for the air conditioner units

Not available

Temperature setting

Not available

Fan speed setting

Not available

Air flow direction setting

Not available

Manual operation
prohibit/permit
(ON/OFF, operation mode,
setting temperature, filter reset)

Compatible only with external input.

Specific mode
operation prohibit
(Cooling prohibit, heating
prohibit, cooling/heating prohibit)

Not available

Room temperature display

Not available

Error display

LED flashes during failure.


(The error code can be confirmed by removing the cover.)

Schedule operation

Not available

Ventilation operation
(independent)

Group operation of only LOSSNAY units possible.


Only ON/OFF of group.

Ventilation operation
(interlocked)

The LOSSNAY will run in interlock with the operation of indoor


unit.
The fan rate and mode cannot be changed. The LED will turn
ON only during operation after interlocking.

External output
(Error output,
operation output)

"ON/OFF" and "error/normal" are output with the level signal.


The optional output cable is required.

Connection position

Indoor/outdoor transmission line: Connectable


Central system transmission line: Connectable (Power supply
unit (PAC-SC50KUA) is needed.)

CONTROLLER

.
.

CONTROLLER
CONTROLLER (Feb. 2009)

CNTR-13
Cntr- 14

3. System Controller

DATA U4

System example

ON/OFF
remote
controller

LOSSNAY

PAC-SC51KUA
Power supply

PAR-F27MEA-US

PZ-52SF

PAC-YT51CRB
PAR-21MAA

CONTROLLER

External dimension
(Front view)

18.1
[ 23/32 ]

130[ 5-1/8 ]

(Rear view)

ON/OFF

83.5 [3-9/32 ]

120[4-23/32]

CENTRALIZED

Unit:mm[in.]

(Side view)

19
[ 3/4 ]

CNTR-14

CONTROLLER (Feb. 2009)

46[1-13/16 ]

3. System Controller

DATA U4

3-4. Central controller [G-50A]


Functions
ON/OFF
TEST RUN
ON/OFF

73 F

5
TEMP.

CLOCK/
PATTERN

VENTILATION

TIMER
MODE

RESET

BACK
SCREEN

ENTER

:Each block

:Collective

:Not available

ON/OFF

Run and stop operation for the air conditioner units

Operation mode
switching

Switches between Cool / Dry / Auto / Fan / Heat.


(Group of LOSSNAY unit : automatic ventilation/ vent - heat
interchange/ normal ventilation)
Operation modes vary depending on the air conditioner unit.

INS.

DEL.

:Each group

:Each floor

Operations

Description

Item

GROUP
SELECT

AIR
DIRECTION

REMOTE
PROHIBITION

CENTRAL CONTROLLER
G-50A

FAN SPEED

MODE

:Each unit

Display

Auto mode is only for the CITY MULTI R2 and WR2 series.
Range of temperature setting

Cool/Dry :
:
Heat
Auto
:

Temperature
setting

Fan speed setting

A. The central controller of G-50A combines Web


function (optional), which enable the air conditioner
system management on a PC browser screen.
The management can even carried out remotely.
Microsoft Internet explorer Ver. 5 or later by
Microsoft Corporation is needed. Microsoft is a
registered trade mark of Microsoft Corporation in
the United States and other countries.
B. Together with integrated centralized control software
TG-2000A, and/or PLC, many optional functions like
"Charging", "Peak-cut", "Energy saving", "General
equipment management", "Scheduling" etc, can be
carried out. Details, please refer to sections of TG2000A and PLC software.
C. One G-50A can control maximum 50 Indoor units
(including Lossnay). The TG-2000A can manage
maximum 40 G-50As, therefore can manage
maximum 2000 Indoor units (including Lossnay).
D. Taking advantage of G-50A's Web functions, alarming E-mail containing address and error code can
be sent to appointed E-mail address upon any fault
happen at the air conditioner system. This could
release standby personnel and save operation
cost.

( ) in case of PDFY/PEFY/PFFY-E indoor unit.

Range of temperature settings vary depending on model.


Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto
Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.

Air flow direction


setting

Air flow direction angles, 4-angle, 5-angle Swing, Auto


1: Louver cannot be set.
Air flow direction settings vary depending on the model.

Timer operation

For one day, you can set start/stop three times and you can set
enable/disable three times.
For a week's schedule, you can store three start/stop patterns
and one enable/disable pattern.
2: When the timer is set, "Timer enabled" is shown on the
operation setting screen of the LCD.

Permit / Prohibit
local operation

Indoor unit intake


temperature

Individually prohibit operation of each local remote control


function (Start/Stop, Change operation mode, Set temperature,
Reset filter).
3: When the local remote controller inactivation command is
received from the master system controller, disabled mark
appears in inverted display on the operation screen.

Measures the intake temperature of the indoor unit only when


the indoor unit is operating.
When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
4: When an error occurs, the LED flashes. The operation
monitor screen shows the abnormal unit by flashing it. The
error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit
address, error code and source of detection.

Error

This operates air conditioner units in test run mode.

Test run

The interlocked system settings can be performed by the master


system controller.
When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
"Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
and "Automatic ventilation".

Ventilation
equipment

External dimension

Unit:mm[in.]
25
[31/32]

300[11-13/16 ]

70[2-3/4 ]

ON/OFF

CENTRAL CONTROLLER

G-50A

3[1/8]

57[2-1/4 ]
19[3/4]

34
[1-5/16]

288[11-11/32]
138[5-7/16]
47[1-27/32 ]

83.6[3- 9 / 32]

13 [1/2]
83.5[3-9/32]

12VDC GND

RS232C

1 CN1 5

CN2

POWER

28
[1-1/8]

M-NET

91[ 3-19/32]

Installation plate

106[4-3/16]

220 [8-21/32]
280[11 ]

Ethernet

21
[13/16]

46
[1-13/16 ]

47[1-27/32 ]

CONTROLLER (Feb. 2009)

CNTR-15

CONTROLLER

By using accessory cables you can set and monitor the


following.
Input
By level signal: "Batch start/stop", "Batch emergency stop"
By pulse signal: "Batch start/stop", "Enable/disable local
remote controller"
Output
"Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
separately.

External
input/output

120[ 4-3/4]

3-4-1. Power supply to G-50A

3. System Controller

DATA U4
G-50A needs DC power supply of 24~30V and 12V; the former is for central control transmission use and the latter is for
G-50A's operating and LAN function use. G-50A can have power-supply at following 1,2,3 methods.

3-4-1-1. Power supply unit PAC-SC50KUA is the recommended power supplier for G-50A. The basic scheme is as follows. For
details, please refer to 3-6 Power supply unit PAC-SC50KUA.
LAN

M-NET

M-MET

12V DC
Central controller
G-50A

UP

POWER SUPPLY UNIT

PAC-SC50KUA

MODE
L

POWER TING
RA

2.11kg

WEIGHT

SERIA
L No.

MITSUBIS

HI ELECT

RIC CORP

ORATION

Power supply unit


PAC-SC50KUA

ME remote
controller

ME remote
controller

M-NET

LOSSNAY unit

ME remote
controller

LOSSNAY M-NET
remote controller

Fig. 3-4-1 G-50A and PAC-SC50KUA basic scheme.

3-4-1-2. Power supply of DC 30V from connector of TB7 or TB3 of Outdoor unit and field supplied DC12V, which specified at
Table 3-4-1.
3-4-1-2-1. TB7 and field supplied DC 12V, 0.2A.
As shown at Fig. 3-4-2, G-50A receives power supply of DC 30V from the connector of TB7 at the R410A Outdoor unit
together with a field supplied DC12V, 0.2A. In the case, one of the Outdoor units should change its power supply switch of
CN41 to CN40.

CONTROLLER

Centralized control
transmission line

R410A
Outdoor unit
Indoor/outdoor transmission line

CN41

CN40

Field supplied power


(DC12V 0.2A)
Indoor/outdoor transmission line

CN41

Fig. 3-4-2 G-50A, TB7 and field supplied DC12V scheme.

DC12V Power source should follow the specifications at Table 3-4-1, and the power cable to G-50A should not exceed 10m 32-3/4ft .
Table 3-4-1 DC12V power specifications

Source power

DC12V 0.2A (Maximum loading)

Ripple noise

Lower than 150mVp-p

Compatible
specification

Authorized or CE marked products.


Subject to regulations:
IEC60950 (or EN60950)
CISPR22/24 (or EN55022/24)
IEC61000-3-2/3-3 (or EN61000-3-2/3/3)

CNTR-16

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-4-1-2-2. TB3 and DC 12V, 0.2A


G-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. Yet, Outdoor unit down
will lead down to G-50A too. The kind of connection is possible but not recommended air conditioner system of multiple
Outdoor units. The DC 12V 0.2A can be supplied at TB3 connector of PAC-SC50KUA, or a field supplier power complying
specification at Table 3-4-1.

Indoor/outdoor transmission line


TB3
CN41
Field supplied power
(DC12V 0.2A)

Fig.3-4-3 G-50A, TB3 and field supplied DC 12V scheme.

3-4-1-2-3. The effect on connectable quantity of Indoor unit when TB7 or TB3 is used to supply power to the G-50A.
As Indoor unit controller and system controllers share the power supply from the Outdoor unit, the total power consumption of
control use needs following considerations.
Taking the power consumption of the control board of Indoor unit as 1, the equivalent power consumption of the system controller is as follows.
Table 3-4-2 The equivalent power consumption of controllers.

Other system controllers


Indoor unit
1

Central controller
(G-50A)
0.5

ON/OFF remote controller


(PAC-YT40ANRA)

System remote controller


(PAC-SF44SRA)
Schedule timer (PAC-YT34STA)

0.5

*In order to ensure the transmission quality in start-up of outdoor unit (or during communication traffic), the number of
system controllers which connected to indoor/outdoor transmission line in the same system, should not exceed3.

CONTROLLER (Feb. 2009)

CNTR-17

CONTROLLER

CAUTION

Any trouble caused by the failure of the field supplied DC12V power source is not responsible by Mitsubishi Electric Corporation.
When applying Charge and/or Peak-cut function on G-50A, Power Supply Unit (PAC-SC50KUA) is recommended to use. G-50A is possible to
receive power from the one of the Outdoor units, but there is a risk that the failure of power supply from the Outdoor unit will cause G-50A's
function-down on the whole system.
At the air conditioner system of multiple Outdoor units, the connector of CN41 is changed to CN40 at only one of the Outdoor units when TB7 is
used to supply power. When the Outdoor unit failed, the connector at another unit can be changed from CN41 to CN40 to recover the power
supply, but remember to change the CN40 back to CN41 at the failed Outdoor unit.

3. System remote controller


3. System Controller

DATA U3

DATA U4

3-4-2. External input/output usage


3-4-2-1. External signal input function
External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External input
Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (DC12V or DC24V) contact signal from an external source.
(Select with the function select setting)
External signal input function

No

Function
No.6
No.7

Do not use external input signal


(factory setting)
Execute emergency stop/normal
with level signal

OFF

OFF

OFF

ON

Perform ON/OFF with level signal

ON

OFF

Perform ON/OFF, prohibit/enable


with pulse signals.

ON

ON

1
2

Remarks

The local remote controller ON/OFF operations, and the


controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.
The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.
Set the pulse width while the contact is ON to 0.5 to 1 sec.

(2) Level signal and pulse signal (DC12V or DC24V)


(A) Level signal

(B) Pulse signal


(Example) for ON/OFF

Contact ON

0.5 to 1 sec

Contact OFF
Stop

Run

Stop

Signal 1 (run)

Contact ON
Contact OFF
0.5 to 1 sec

Contact ON
Contact OFF

Normal Emergency stop Normal

Contact ON
Signal 2 (stop)
Contact OFF
OFF

ON

OFF

The prohibit/enable input is the same.

CONTROLLER

(3)External input specifications


CN2
No.5
No.6

Lead wire
Orange
Yellow

Emergency stop/normal level signal


Emergency stop/normal input
Not used

ON/OFF, level signal


ON/OFF input
Not used

No.7

Blue

Not used

Not used

No.8

Gray

Not used

Not used

No.9

Red

External DC source

ON/OFF, prohibit/enable pulse signal


ON input
OFF input
Local remote controller operation
prohibit input
Local remote controller operation
enable input

(A) For level signal


When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Emergency stop signal will bring the air conditioners to stop, and canceling the
emergency stop will not automatically reset these units. To go back to the previous operation status, they must be
manually turned back on.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.
(B) For pulse signal
Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.

CNTR-18

CONTROLLER
CONTROLLER (Feb. 2009)

Cntr- 19

3. System remote controller


3. System Controller

DATA U3

DATA U4

(4)Recommended circuit example


(A) For level signal
CN2

This unit

Red
Orange X1

CN2
X1

Run/stop or
Emergency stop

Orange
Yellow
Blue
Purple

Power supply( 1)
(DC12V or DC24V)

Max.10m
32-3/4ft

This unit

Power supply( 1)
(DC12V or DC24V)

Red

Max.10m
32-3/4ft

X1
X2
Y1
Y2

X1
Y1

Run
Stop
Prohibit
Enable

X2
Y2

The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be e
10m 32-3/4ft (Use a 0.3mm2 [AWG22] or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

3-4-2-2. External signal output function


External signal output requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External output
When one or more air conditioners are running, the "ON" signal will be output and if a malfunction occurs in one or more air
conditioners, the "Malfunction" signal will be shown.

(2)External output specifications


CN 2
No.1

Lead wire
Green

Details of each terminal


Common (External ground)

No.2
No.3

Black
Brown

ON/OFF
Malfunction/normal

"ON" signal and " Malfunction" signal will


both be output.

(3)Recommended circuit example


CN2

Diode( 2)

Use Z1 and Z2 relays having the following specifications.


Operation coil
Rated voltage
:DC12V,DC24V
Power Consumption
: 0.9W or less
( 1)Prepare a power supply separately according to the
relay being used. (DC12V or DC24V)
( 2)Always insert a diode on both ends of the relay coil.

Z1

Black
Brown

Z2
Power ( 1)
Supply

CONTROLLER

Green
Max.10m
32-3/4ft

L1:Run display lamp


L2:Malfunction display lamp

Each element will turn on while ON operation or a malfunction occurs.


The connection cable can be e
10m 32-3/4ft
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

CAUTION

Peel off the label

When connecting the external input/output cables to connector CN2 on the controller, peel off the label on the controller connector section.

Ethernet

M-NET

POWER

CONTROLLER
CONTROLLER (Feb. 2009)

12VDC GND

RS232C

1 CN1 5

CN2

Cntr- 20
CNTR-19

3. System remote controller


3. System Controller

DATA U3

DATA U4

3-4-3. LAN connection function


When using the LAN connection function, connect the LAN cable to the Ethernet connector of this device.
Procure the LAN cable at the site, and use an enhanced category 5 UTP cable.
For a description of the IP address setting method, refer to Installation Manual.
LAN is 10 BASE-T Specification.
Ethernet

POWER

M-NET

12VDC GND

RS232C

1 CN1 5

CN2

NOTE

CONTROLLER

Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the MNET transmission line.
When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
When connecting an LAN connector, space for the connector and wiring is required. Provide this space at
this unit and the rear of the electric box. Refer to Installation Manual.
When the G-50A cover is opened, the LAN status lamp and LAN changeover switch are accessed. For detailed information, refer to Instruction Book.

CNTR-20

CONTROLLER
CONTROLLER (Feb. 2009)

Cntr- 21

3. System Controller

DATA U4

3-4-4. Browser screens of G-50A

Condition List (Overview)

81

81 F

81 F

81 F

79 F

81 F

82 F

81 F

81 F

81 F

82 F

81 F

79 F

81 F

81 F

-- F

-- F

Condition List (Block)

CONTROLLER

Operation

Malfunction List

79 F

79 F

82 F

Malfunction Log

Weekly Schedule

CONTROLLER (Feb. 2009)

CNTR-21

3. System Controller

Operation (DIDO Controller)

CONTROLLER

Trend Graph (temperature/humidity)

CNTR-22

CONTROLLER (Feb. 2009)

DATA U4

Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

3. System Controller

DATA U4

3-5. Central controller [GB-50A]

3-5. Central controller [GB-50A]


Functions
N623

CENTRAL CONTROLLER
MODEL

WEIGHT
SERIAL No.

DC30/24V;0.13/0.15A
1.1kg / 2

lb

:Each block

:Collective

:Not available

ON/OFF

Run and stop operation for the air conditioner units

Operation mode
switching

Switches between Cool / Dry / Auto / Fan / Heat.


(Group of LOSSNAY unit : automatic ventilation/ vent - heat
interchange/ normal ventilation)
Operation modes vary depending on the air conditioner unit.

MADE IN JAPAN

This device complies with Part15 of the FCCRules.Operation is


subject to the following two conditions:(1)this device may not cause
harmful interference,and(2)this device must accept any interference
received,including interference that may cause undesired operation.

:Each group

:Each floor

Operations

Description

Item

SERVICE REF. GB-50A-E

INPUT VOLTAGE
(M-NET)

:Each unit

Display

Range of temperature setting

Cool/Dry :
:
Heat
Auto
:

Temperature
setting

( ) in case of PDFY/PEFY/PFFY-E indoor unit.

Range of temperature settings vary depending on model.

A. The central controller of GB-50A combines with Web


function, which enables the air conditioner system to be
managed via PC browser screen. *1.
The management can even carried out remotely.
*1 Microsoft Internet explorer Ver. 5 or later by
Microsoft Corporation is needed. Java executing
environment is needed.(Microsoft VM Ver. 5.0 or
later, or SUN Microsystems Java plug-in Ver. 1.4.2 or
later) Microsoft is a registered trademark of
Microsoft Corporation in the United States and other
countries.
B. Together with integrated centralized control software
TG-2000A and/or PLC, many optional functions like
Charging, Peak-cut, Energy saving, General
equipment management, Scheduling etc, can be
performed. For details, please refer to sections of TG2000A and PLC software.
C. One GB-50A can control a maximum of 50 Indoor units
(including Lossnay). The TG-2000A can manage a
maximum of 40 GB-50As, and therefore, can manage
a maximum 2,000 Indoor units (including Lossnay).
D. Taking advantage of GB-50As Web functions,
an notification e-mail containing address and error code
can be sent to appointed e-mail address if any error
occurs at the air conditioner system.

Fan speed setting

Air flow direction


setting
Permit / Prohibit
local operation

Indoor unit intake


temperature

Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto


Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
Fan speed setting (including Auto) varies depending on the model.

Air flow direction angles, 4-angle or 5-angle, Swing, Auto


1: Louver cannot be set.
Air flow direction settings vary depending on the model.

Individually prohibit operation of each local remote control


function (Start/Stop, Change operation mode, Set temperature,
Reset filter).
3: When the local remote controller inactivation command is
received from the master system controller, disabled mark
appears in inverted display on the operation screen.

Measures the intake temperature of the indoor unit only when


the indoor unit is operating.
When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
4: When an error occurs, the LED flashes. The operation
monitor screen shows the abnormal unit by flashing it. The
error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit
address, error code and source of detection.

Error

The interlocked system settings can be performed by the master


system controller.
When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
"Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
and "Automatic ventilation".

Ventilation
equipment

GB-50A needs a PC(field supplied) connected together to monitor and operate the air conditioner system.

External dimension
Unit:mm[in.]

20[25/32]

38[1-1/2]
N623

20[25/32]

250[9-7/8 ]

L-shape metal
(included)

20[25/32] 10
[13/32]

20[25/32]

20[25/32]

250[9-7/8]

CENTRAL CONTROLLER
MODEL

SERVICE REF. GB-50A-E

DC30/24V;0.13/0.15A
1

lb

MADE IN JAPAN

This device complies with Part15 of the FCCRules.Operation is


subject to the following two conditions:(1)this device may not cause
harmful interference,and(2)this device must accept any interference
received,including interference that may cause undesired operation.

Mounting with L-shape metal

290[11-13/32]
310[12-7/32 ]

1.1kg / 2

130[5-1/ 8]

INPUT VOLTAGE
(M-NET)
WEIGHT
SERIAL No.

20[25/32]

35[1-3/8"] DIN Rail


Attachment for DIN Rail (included)

Mounting with DIN Rail

CONTROLLER (Feb. 2009)

CNTR-23

CONTROLLER

By using accessory cables you can set and monitor the


following.
Input
By level signal: "Batch start/stop", "Batch emergency stop"
By pulse signal: "Batch start/stop", "Enable/disable local
remote controller"
Output
"Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
separately.

External
input/output

3. System Controller

DATA U4

3-5-1. Power supply to GB-50A


GB-50A needs DC power supply of 24~30V for central control transmission use, operating and LAN function use. GB-50A can
have power supply at following 1,2,3 methods.
3-5-1-1. Power supply unit PAC-SC51KUA or PAC-SC50KUA are the recommended power supplies for GB-50A. See below for
basic system. For details, please refer to Power supply unit PAC-SC51KUA.

LAN

M-NET

M-MET
Central controller
GB-50A
Power supply unit
PAC-SC51KUA or
PAC-SC50KUA

ME remote
controller

ME remote
controller

M-NET

LOSSNAY unit

ME remote
controller

LOSSNAY remote
controller

Fig. 3-5-1 GB-50A and PAC-SC51KUA basic system.

3-5-1-2. Power supply of DC 30V from connector of TB7 or TB3 of Outdoor unit.

CONTROLLER

3-5-1-2-1. TB7 of Outdoor unit.


As shown at Fig. 3-5-2, GB-50A receives power supply of DC 30V from the connector of TB7 at the R410A Outdoor unit.
In the case, one of the Outdoor units should change its power supply switch of CN41 to CN40.

Central control
transmission line

R410A
Outdoor unit
Indoor/outdoor transmission line

CN41

CN40

Indoor/outdoor transmission line

CN41

Fig. 3-5-2 GB-50A, TB7 power supply

CNTR-24

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-5-1-2-2. TB3 of Outdoor unit.


GB-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. However, if the Outdoor
unit shuts down, G-50A will also automatically shuts down. Therefore, this connection is not recommended for air conditioner
system consisting multiple Outdoor units.
Indoor/outdoor transmission line
TB3
CN41

Fig.3-5-3 GB-50A, TB3 power supply

3-5-1-2-3. The effect on connectable quantity of Indoor unit when TB7 or TB3 is used to supply power to the GB-50A.
As Indoor unit controller and system controllers share the power supply from the Outdoor unit, the total power consumption of
control use needs following considerations.
Taking the power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 3-5-1 and Table 3-5-2.
Table 3-5-1 The equivalent power consumption index by Indoor units, LOSSNAY, controllers

Indoor, OA unit

Indoor unit

Sized P06-P54

BC controller

Sized P72,P96

MA RC. LOSSNAY ME Remote Contr.


PAR-21MAA
PAR-F27MEA
PAC-YT51CRA(B) PZ-52SF
PAR-FA32MA
LGH-RX-E

CMB

Timers, System Contr.


PAC-SF44SRA
PAC-YT34STA
G-50A
AG-150A
1/2

1/4

ON/OFF Contr.

GB-50A

PAC-YT40ANRA

In order to ensure the transmission quality in start-up of outdoor unit (or during communication traffic), the number of system controllers that connect to
indoor/outdoor transmission line in the same system, should not exceed three.
*RC : Remote Controller

Table 3-5-2 The equivalent power supply capability index of Trans.Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.

Transmission Booster
PAC-SF46EPA
25

Power supply unit


PAC-SC50KUA
6

PAC-SC51KUA
5

Outdoor unit

Outdoor unit

Connector TB3 and TB7 total *


32

Connector TB7 only


6

*If PAC-SC50(51)KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.
*Connector TB3 of PUMY gives equivalent power only 12. TB7 of PUMY should not be used to supply power, and power supply unit should be used.

CAUTION

Mitsubishi Electric Corporation is not responsible for any problems caused by the failure of the field supplied 12VDC power source.
When applying Charge and/or Peak-cut function on GB-50A, using a Power Supply Unit (PAC-SC50KUA or PAC-SC51KUA) is recommended.
GB-50A has the ability to receive power from the one of the Outdoor units, but there is a risk that a failure of the power supply from the
Outdoor unit will cause GB-50A to shut down the whole system.
On a multiple Outdoor unit system, the connector of CN41 is changed to CN40 at only one of the Outdoor units when TB7 is used to supply
power. If that Outdoor unit fails, the connector at another unit can be changed from CN41 to CN40 to recover the power supply, but remember
to change the CN40 back to CN41 at the failed Outdoor unit.

If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor unit sized P72, 96 is counted as 2 Indoor
units, but MA remote controller(s), LOSSNAY is NOT counted.
3-5-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption reaches 32,
a PAC-SF46EPA should be set. Yet, if a PAC-SC50(51)KUA is used to supply power at TB7 side, count from index TB3 side only.
3-5-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches 6,
a PAC-SF46EPA should be set.

System example

TB7

TB3

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

01

Transmission
booster
PAC-SF96EPA
(No.1)

02

ME remote
controller
TB7

TB3
Outdoor unit

N1

ME remote
controller

N2

Within N2, conditions 1,2 should be followed.


1.The total quantity of Indoor units and ME remote
controller should not exceed 40.
*Indoor unit sized P72,96 is counted as 2 units.
2.The total equivalent transmission power consumption
should not exceed 25.

Transmission booster (No.1) should be used,


if the total quantity of Indoor units and ME remote controllers
reaches 40, (Indoor unit sized P72,96 is counted as 2);
or if the total equivalent transmission power consumption reaches 32.
UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

M-NET
(24VDC)

Power supply unit


PAC-SC51KUA or
PAC-SC50KUA

LOSSNAY
unit

Central controller
(GB-50A)

PZ-52SF

N3

Transmission booster (No.2) should be used,


if the total equivalent transmission power consumption reaches 6.

Transmission
booster
PAC-SF46EPA
(No.2)

LOSSNAY
unit
PZ-52SF

N4

Within N4, the total equivalent transmission


power consumption should not exceed 25.

CONTROLLER (Feb. 2009)

CNTR-25

CONTROLLER

With the equivalent power consumption values in Table 3-5-1 and Table 3-5-2, PAC-SF46EPA can be designed into the airconditioner system to ensure proper system communication according to 3-5-2-A, B, C.
3-5-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System controllers.

3. System remote controller


3. System Controller

DATA U3

DATA U4

3-5-2. External input/output usage

CN2

3-5-2-1. External signal input function


External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External input
Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (DC12V or DC24V) contact signal from an external source.
(Select the function on the Initial Setting Web or the Initial Setting Tool)
External signal input function

No

Do not use external input signal


(factory setting)
Execute emergency stop/normal
with level signal

1
2

Perform ON/OFF with level signal

Perform ON/OFF, prohibit/enable


with pulse signals.

Remarks

The local remote controller ON/OFF operations, and the


controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.
The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.
Set the pulse width while the contact is ON to 0.5 to 1 sec.

(2) Level signal and pulse signal (DC12V or DC24V)


(A) Level signal

(B) Pulse signal


(Example) for ON/OFF

Contact ON

0.5 to 1 sec

Contact OFF
Stop

Run

Stop

Signal 1 (run)

Contact ON
Contact OFF
0.5 to 1 sec

Contact ON

CONTROLLER

Contact OFF

Normal Emergency stop Normal

Contact ON
Signal 2 (stop)
Contact OFF
OFF

ON

OFF

The prohibit/enable input is the same.

(3)External input specifications


CN2
No.5
No.6

Lead wire
Orange
Yellow

Emergency stop/normal level signal


Emergency stop/normal input
Not used

ON/OFF, level signal


ON/OFF input
Not used

No.7

Blue

Not used

Not used

No.8

Gray

Not used

Not used

No.9

Red

External DC source

ON/OFF, prohibit/enable pulse signal


ON input
OFF input
Local remote controller operation
prohibit input
Local remote controller operation
enable input

(A) For level signal


When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Emergency stop signal will bring the air conditioners to stop, and canceling the
emergency stop will not automatically reset these units. To go back to the previous operation status, they must be
manually turned back on.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.
(B) For pulse signal
Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.

CNTR-26

CONTROLLER (Feb. 2009)

CONTROLLER

Cntr- 26

3. System remote controller

DATA U3
DATA U4

3. System Controller
3-5-2-1. External signal input function
(4)Recommended circuit example
(A) For level signal
CN2

5
6
7
8

This unit

CN2

Red

Orange X1

X1

Run/stop or
Emergency stop
Power supply( 1)
(DC12V or DC24V)

Max.10m
32-3/4ft

Red

5
6
7
8

Orange
Yellow
Blue
Purple

This unit

Power supply( 1)
(DC12V or DC24V)
X1
X2
Y1
Y2

Max.10m
32-3/4ft

X1
Y1

X2
Y2

Run
Stop
Prohibit
Enable

The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m 32-3/4ft . (Use a 0.3mm2 [AWG22] or thicker wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

3-5-2-2. External signal output function


External signal output requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External output
When one or more air conditioners are running, the ON signal will be output and if a malfunction occurs in one or more air
conditioners, the Malfunction signal will be shown.

(2)External output specifications


CN 2
No.1

Lead wire
Green

Details of each terminal


Common (External ground)

No.2
No.3

Black
Brown

ON/OFF
Malfunction/normal

" ON" signal and " Malfunction" signal will


both be output.

(3)Recommended circuit example


CN2

Diode( 2)
Z1

Z2

Green
Max.10m
32-3/4ft

Power ( 1)
Supply

L1:Run display lamp


L2:Malfunction display lamp

Each element will turn on while ON operation or a malfunction occurs.


The connection cable can be extended up to 10m 32-3/4ft
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

CONTROLLER (Feb. 2009)

CNTR-27

CONTROLLER

Black
Brown

Use Z1 and Z2 relays having the following specifications.


Operation coil
Rated voltage
:DC12V,DC24V
Power Consumption
: 0.9W or less
( 1)Prepare a power supply separately according to the
relay being used. (DC12V or DC24V)
( 2)Always insert a diode on both ends of the relay coil.

3. System remote controller


3. System Controller

DATA U3

DATA U4

3-5-3. LAN connection function


Connect the LAN cable to the LAN connector of this device.
Procure the LAN cable at the site, and use an enhanced category 5 UTP cable.
For a description of the IP address setting method, refer to Installation Manual.
LAN is 10 BASE-T Specification.
The maximum wiring length from HUB to GB-50A is 100m [328ft].
GB-50A is connected to the monitoring PC via HUB.

NOTE

CONTROLLER

Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the MNET transmission line.
When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
Space for the connector and wiring is required. Refer to Installation Manual.

CNTR-28

CONTROLLER
CONTROLLER (Feb.
2009)

Cntr- 28

3. System Controller

DATA U4

3-5-4. Browser screens of GB-50A

Condition List (Overview)

81

81 F

81 F

81 F

79 F

81 F

82 F

81 F

81 F

81 F

82 F

81 F

79 F

81 F

81 F

-- F

-- F

Condition List (Block)

CONTROLLER

Operation

Malfunction List

79 F

79 F

82 F

Malfunction Log

Weekly Schedule

CONTROLLER (Feb. 2009)

CNTR-29

3. System Controller

Operation (DIDO Controller)

CONTROLLER

Trend Graph (temperature/humidity)

CNTR-30

CONTROLLER (Feb. 2009)

DATA U4

Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

3. System Controller

DATA U4

3-6. Central controller [AG-150A]


Functions

:Each unit

:Each group

:Each block

:Each floor

:Collective

:Not available
Operations

Description

Item
ON/OFF

Run and stop operation for the air conditioner units

Operation mode
switching

Switches between Cool / Dry / Auto / Fan / Heat. (Group of


LOSSNAY unit : automatic ventilation/ vent - heat interchange/
normal ventilation)
Operation modes vary depending on the air conditioner unit.
Auto mode is the City Multi R2 and WR2 series only.

Display

Range of temperature setting

Cool/Dry :
:
Heat
Auto
:

Temperature
setting

A. The centralized controller of AG-150A combines Web


function (optional), which enable the air conditioner
system management on a PC browser screen.
*1The management can even carried out remotely.
Microsoft Internet explorer Ver. 6 or later by Microsoft Corporation is needed.
(Note: You must have "Sun Microsystems Java".)
Microsoft Internet explorer is a registered trade mark of Microsoft
Corporation US in the USA and other countries.

Note: Connect AG-150A to a private network.

Range of temperature settings vary depending on model.

Fan speed setting (including Auto) varies depending on the model.


Air flow direction
setting

Indoor unit intake


temperature

Measures the intake temperature of the indoor unit only when


the indoor unit is operating.
When an error is currently occurring on an air conditioner unit,
the afflicted unit and the error code are displayed.
4: When an error occurs, the "ON/OFF" LED flashes. The
operation monitor screen shows the abnormal unit by flashing
it. The error monitor screen shows the abnormal unit address,
error code and source of detection. The error log monitor
screen shows the time and date, the abnormal unit address,
error code and source of detection.

Test run

This operates air conditioner units in test run mode.

Ventilation
equipment

The interlocked system settings can be performed by the master


system controller.
When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi",
"Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can
switch between "Normal ventilation", "Interchange ventilation"
and "Automatic ventilation".
By using accessory cables you can set and monitor the following.
Input: By level signal: "Batch start/stop", "Batch emergency stop"
By pulse signal: "Batch start/stop", "Enable/disable local remote
controller"
Output: "Start/stop", "Error/Normal"
5: Requires the external I/O cable (PAC-YG10HA-E) sold
separately.

25.6 44.7
(1-1/16)(1-13/16)

300 (11-13/16)

Individually prohibit operation of each local remote control


function (Start/Stop, Change operation mode, Set temperature,
Reset filter).
3: When the local remote controller inactivation command is
received from the master system controller,
"Disabled"appears in inverted display on the operation setting screen.

Permit / Prohibit
local operation

Error

Air flow direction angles, 4-angle or 5-angle Swing, Auto


1: Louver cannot be set.
Air flow direction settings vary depending on the model.
Weekly schedule can be set for each group of air conditioning units.
2 By registering a license for AG-150A, weekly (2 types), annual, and current day
scheduling function become available.
The system follows either the current day, annual schedule, or weekly, which are
in the descending order of overriding priority.
Twenty-four events can be scheduled per day, including Start/Stop, Mode,
Temperature Setting, Operation Prohibition, Vane Direction, and Fan Speed.
Two types of weekly schedule (Summer/Winter) can be set.
Settable items dependant on the indoor unit model.

Schedule
operation

External
input/output

External dimension

Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto


Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low

Fan speed setting

Unit:mm[in.]

185 (7-5/16)

Installation plate
290.8(11-1/2)
273(10-3/4)
250(9-7/8)
200(7-7/8)

167(6-5/8)

175.8(6-15/16)

147(5-13/16)

163.4(6-7/16)

CENTRALIZED CONTROLLER AG-150A

272 (10-3/4)
Back View

272 (10-3/4)
250 (9-7/8)

146 (5-3/4)

167 (6-5/8)

261(10-5/16)

CONTROLLER (Feb. 2009)

CNTR-31

CONTROLLER

B. Together with integrated centralized control software


TG-2000A, and/or PLC, many optional functions like
"Charging", "Peak-cut", "Energy saving", "General
equipment management", "Scheduling" etc, can be
carried out. Details, please refer to sections of
TG-2000A and PLC software.
C. One AG-150A can control maximum 50 Indoor units
(including LOSSNAY). The integrated centralized
control software TG-2000A can manage maximum
40 AG-150As, therefore can manage maximum
2000 Indoor units (including LOSSNAY).
D. Taking advantage of AG-150A's Web functions,
alarming E-mail containing address and error code
can be sent to appointed E-mail address upon any
fault happen at the air conditioner system.
E. AG-150A features a 9"-wide color LCD touch panel.
The settings for air conditioning units can be
changed by touching the corresponding icons on
the display.

( ) when using middle-temperature on PDFY, PEFY-NMSU/NMHU-by setting DipSW7-1


to ON.

3. System Controller

DATA U4

3-6-1. Power supply to AG-150A


AG-150A needs DC power supply of 24~30V (M-NET) and 24V; the former is for centralized control transmission use and the
latter is for AG-150A's operating and LAN function use. AG-150A can have power-supply at following 1,2 methods.
3-6-1-1. Power supply unit PAC-SC51KUA is the recommended power supply for AG-150A. The basic scheme is as follows.
For details, please refer to Power supply unit PAC-SC51KUA.

M-NET

M-NET

CENTRALIZED CONTROLLER AG-150A

Centralized controller
AG-150A
24VDC

TB2

ME remote
controller

PAC-SC51KUA
(TB2 and TB3 used)

ME remote
controller

M-NET

LOSSNAY unit

PZ-52SF

ME remote
controller

Fig. 3-6-1 AG-150A and PAC-SC51KUA basic scheme.

CONTROLLER

3-6-1-2. Power supply of 30VDC (M-NET) from connector of TB3 of Outdoor unit and PAC-SC51KUA.
AG-150A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit.Yet, Outdoor
unit down will lead down to AG-150A too. The kind of connection is possible but not recommended air conditioner
system of multiple Outdoor units. The 24VDC can be supplied at TB3 connector of PAC-SC51KUA.

Indoor/outdoor transmission line


TB3

CN41

PAC-SC51KUA
(TB3 24VDC used)
CENTRALIZED CONTROLLER AG-150A

Centralized controller
AG-150A

Fig. 3-6-2 AG-150A, TB3 and PAC-SC51KUA scheme.

CAUTION

CNTR-32

When applying Charge and/or Peak-cut function on AG-150A, Power Supply Unit (PAC-SC51KUA) is recommended to use. AG-150A is
possible to receive power from the one of the Outdoor units, but there is a risk that the failure of power supply from the Outdoor unit will
cause AG-150A's function-down on the whole system.
At the air conditioner system of multiple Outdoor units, the connector of CN41 is changed to CN40 at only one of the Outdoor units when
TB7 is used to supply power. When the Outdoor unit failed, the connector at another unit can be changed from CN41 to CN40 to recover
the power supply, but remember to change the CN40 back to CN41 at the failed Outdoor unit.

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-6-2. External input/output usage


3-6-2-1. External signal input function
External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1) External input
Emergency stop/normal, run/stop and prohibit/permit of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
(Select with the function select setting.)
No

Function
name

Not in use

Emergency
stop
(Level signal)

External signal input function


Do not use external input signal
(factory setting)
Execute emergency stop/normal
with level signal

Remarks

The local remote controller ON/OFF operations, and the


controller ON/OFF operation and prohibit/permit change
operations will be prohibited during emergency stop.
Timer operation will also be prohibited.

Perform ON/OFF with level signal

The local remote controller ON/OFF operations, and the


controller ON/OFF operations and prohibit/permit change
operations will be prohibited.
Timer operation will also be prohibited.

Perform ON/OFF, prohibit/permit


ON/OFF
4 prohibit/permit with pulse signals.
(Pulse signal)

Set the pulse width while the contact is ON to 0.5 to 1 sec.

ON/OFF
3
(Level signal)

(2) Level signal and pulse signal (12VDC or 24VDC)


(A) Level signal

(B) Pulse signal


(Example) for ON/OFF

Contact ON
Contact OFF

0.5 to 1 sec

Signal 1 (run)
Stop

Run

Stop

Contact ON
Contact OFF

Contact ON
Contact OFF

0.5 to 1 sec

Signal 2 (stop)
Contact ON
Normal Emergency stop Normal

Contact OFF
ON

OFF

*The prohibit/permit input is the same.

(3)External input specifications


CN5
No.5
No.6

Lead wire
Orange
Yellow

Emergency stop/normal level signal


Emergency stop/normal input
Not used

No.7

Blue

Not used

No.8

Gray

Not used

No.9

Red

ON/OFF, level signal


ON/OFF input
Not used

ON/OFF, prohibit/enable pulse signal


ON input
OFF input
Local remote controller operation
Not used
prohibit input
Local remote controller operation
Not used
enable input
External DC source + 12VDC or + 24VDC

(A) For level signal


When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Air conditioning units that came to an emergency stop will remain stopped after
the emergency stop is cancelled. Manually start up each unit to restore the previous operation.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.
(B) For pulse signal
Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.

CONTROLLER (Feb. 2009)

CNTR-33

CONTROLLER

OFF

3. System Controller

DATA U4

3-6-2-1. External signal input function


(4) Recommended circuit example
(A) For level signal
CN5

Red

X1

Run/stop or
Emergency stop
Orange

X1

Power supply(*1)
(12VDC or 24VDC)

Max.10m
(32 ft)

This unit

(B) For pulse signal


CN5

Power supply(*1)
(12VDC or 24VDC)

Red
Gray
Blue
Yellow
Orange

This unit

Y2
Y1
X2
X1

X1

X2

Y1

Use relays X1, X2, Y1, and Y2 that meet the


following specifications.
Contact rating
Rated voltage >= 12VDC
Rated current >= 0.1A
Minimum applicable load =< 1mA at DC

Y2

Run Stop Prohibit Enable

Max.10m
(32 ft)

The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm2 (AWG 22) or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

3-6-2-2. External signal output function


* External signal output requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately.
(1)External output
When one or more air conditioners are running, the " ON " signal will be output and if a malfunction occurs in one or more air
conditioners, the " Malfunction " signal will be output.

CONTROLLER

(2)External output specifications


CN5
No.1

Lead wire
Green

Details of each terminal


Common (External ground)

No.2
No.3

Black
Brown

ON/OFF
Malfunction/normal

The " ON" signal is output even while the " Malfunction"
signal is being output.

(3)Recommended circuit example


CN5

Brown
Black

This unit

Green
Max.10m
(32 ft)

Diode(*2)
(*2)
(*2)

Z1

Power (*1)
Supply

Z1

L1

Z2

Z2

L2

Use Z1 and Z2 relays that meet the following specifications.


Operation coil
Rated voltage
: 12VDC, 24VDC
Power Consumption: 0.9W or less
(*1) Prepare a power supply separately according to the relay
being used. (12VDC or 24VDC)
(*2) Always insert a diode on both ends of the relay coil.

L1: Run display lamp


L2: Malfunction display lamp

Each element will turn on while ON operation or a malfunction occurs.


The connection cable can be extended up to 10m (32 ft).
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.
Punch out the knockout hole

NOTE
* When connecting the external input/output cables to connector CN5
on the controller, punch out the knockout hole.

CNTR-34

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-6-3. LAN connection function


When using the LAN connection function, connect the LAN cable to the
LAN connector of this device.
Procure the LAN cable at the site, and use 100 BASE-TX Straight cable.
For a description of the IP address setting method, refer to Instruction Book.
LAN is 100 BASE-TX Specification.
LAN

NOTE
Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M-NET
transmission line.
When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
Connect AG-150A to a private network.

CONTROLLER

CONTROLLER (Feb. 2009)

CNTR-35

3. System Controller

DATA U4

3-6-4. Browser screens of AG-150A

Condition List (Overview)

Condition List (Block)

Operation

Malfunction List

Malfunction Log

Weekly Schedule

CONTROLLER

CNTR-36

CONTROLLER (Feb. 2009)

3. System Controller

Operation (DIDO Controller)

DATA U4

Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

CONTROLLER

Trend Graph (temperature/humidity)

CONTROLLER (Feb. 2009)

CNTR-37

3. System Controller

DATA U4

3-6-5. Liquid crystal displays of AG-150A

Weekly schedule setting screen

Floor layout screen

Annual schedule setting screen

Block display screen

Operation screen

Error status screen

Error history display screen

CONTROLLER

Floor layout screen

CNTR-38

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-7. Central controller [GB-24A]


Functions

130 (5 /8)

:Each group

:Each block

:Each floor

:Collective

:Not available

Operations

Description

Item
1

:Each unit

ON/OFF

Run and stop operation for the air conditioning units

Operation mode
switching

Switches between Cool / Dry / Auto / Fan / Heat / Setback.


(Group of LOSSNAY unit : automatic ventilation/ vent - heat
interchange/ normal ventilation)
*Operation modes vary depending on the air conditioner unit.

Display

Range of temperature setting

Cool/Dry
Heat
Auto
Setback

Temperature
setting

250 (97/8)

A. The centralized controller GB-24A combines Web


function, which enable the air conditioner system
management through a PC browser screen.
*1 The management can even be carried out remotely.
*1 Microsoft Internet explorer Ver. 6 or later by Microsoft Corporation is
needed. (Note: You must have Sun Microsystems Java; plug-in Ver.1.4.2
or later). Microsoft is a registered trademark of Microsoft Corporation in the
United States and other countries.

Note: Connect GB-24A to a private network.


B. One GB-24A can control maximum of 24 units
(including indoor units/LOSSNAY/DIDO*2/AI/PI controller).
*2 The maximum number of the controllable units varies depending on the
indoor unit or DIDO controller (the number of contacts used).

C. Using GB-24A's web functions, an error notification


email containing the address and error code can be
sent to the appointed email address if any problem
occurs in the air conditioning system.
D. Set back mode enables the indoor temperature
to be controlled within the setting range (C/F
C/F).
E. Hold operation is a priority function and when it is
effective, local remote controller operation
(ON/OFF,Mode,set temp) and schedule setting will
be prohibited.

: 19C - 30C(14C - 30C) / 67F - 87F(57F - 87F)


: 17C - 28C(17C - 28C) / 63F - 83F(63F - 83F)
: 19C - 28C(17C - 28C) / 67F - 83F(63F - 83F)
: Upper limit : 21C - 30C(21C - 30C) / 69F - 87F(69F - 87F)
Lower limit : 17C - 26C(17C - 26C) / 63F - 79F(63F - 79F)

( ) in case of using middle-temperature on PDFY, PEFY by setting DipSW7-1 to ON.

*Range of temperature settings vary depending on model.

Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto


Fan speed setting Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
*Fan speed settings vary depending on the model.
Air flow direction
setting

Air flow direction 4-angle or 5-angle, Swing, Auto


*1: Louver cannot be set.
*Air flow direction settings vary depending on the model.

Schedule
operation

Today /weekly /annual schedule can be set in groups from the units.
Schedule will be prioritized and performed in orders of Today
annual weekly. Schedules (ON/OFF, mode, set temp,
permit/prohibit) can be changed up to 12 times per day.
*2: Schedule operation setting vary depending on the model.

Permit / Prohibit
local operation

Individually prohibit operation of each local remote control function


(ON/OFF, Operation mode switching, Temperature setting, Reset filter).
*3: When the local remote controller inactivation command is
received from the main system controller, "Disabled"appears in
inverted display on the operation setting screen.

Hold

Prohibits the scheduled operation from being executed.

Indoor unit intake


temperature

Measures the intake temperature of the indoor unit only when the indoor
unit is in operation.

Error

When an error is currently occurring on an air conditioning unit, the


afflicted unit and the error code are displayed.
*4: When an error occurs, the "Error" LED flashes. The operation
monitor screen shows the abnormal unit by flashing. The error monitor
screen shows the abnormal unit's address, error code and source of
detection. The error log monitor screen shows the time, date, abnormal
unit's address, error code and source of detection.

Test run

This operates air conditioning units in test run mode.

Ventilation
equipment

Hold operation will maintain even after electric power failure. Use the
Automatic restoration after power failure function on the air conditioning units.
External
input/output

*1

*2

*3

*4

The interlocked system settings can be performed by the master system


controller. When setting the interlocked system, you can use the ventilation
switch to switch the free plan LOSSNAY settings between "Hi", "Low"
and "Stop". When setting a group of only free plan LOSSNAY units, you
can switch between "Normal ventilation", "Interchange ventilation" and
"Automatic ventilation".
*5

*5

CONTROLLER

By using accessory cables you can set and monitor the following.
Input: By level signal: "Batch start/stop", "Batch emergency stop"
By pulse signal: "Batch start/stop", "Enable/disable local remote controller"
Output: "Start/stop", "Error/Normal"
*5: Requires the external I/O cable (PAC-YG11HA) sold separately.

External dimension
Unit:mm[in.]

CONTROLLER (Feb. 2009)

CNTR-39

3. System Controller

DATA U4

3-7-1. Power supply to GB-24A


GB-24A needs DC power supply of M-NET (24~32VDC) for centralized control transmission use, operation and LAN function use.
(1). Power supply of M-NET from power supply unit PAC-SC51(50)KUA.
Power supply unit PAC-SC51(50)KUA is recommended for GB-24A. See the diagram below ; for details, please refer to
the IM of Power supply unit PAC-SC51(50)KUA

LAN

M-NET

M-NET

Centralized controller
GB-24A

Outdoor unit

Indoor unit

Indoor unit

Power supply unit


PAC-SC51(50)KUA
ME remote
controller

ME remote
controller

M-NET

Outdoor unit

LOSSNAY unit

Indoor unit

LOSSNAY M-NET
remote controller

ME remote
controller

Mr.Slim
Outdoor unit

M-NET
adapter

Indoor unit

MA: MA remote controller


MA

MA

CONTROLLER

Fig. 1 Basic structure of GB-24A and PAC-SC51(50)KUA

(2). Power supply of M-NET from outdoor unit connector TB7.


As shown on Fig. 2, GB-24A receives power supply of M-NET from R410A outdoor unit connector TB7.
In case one of the outdoor units should change its power supply, switch CN41 to CN40.
*NOTE: This method applies to R410A CITY MULTI outdoor unit except PUMY (S series)
R410A
Outdoor unit

Centralized control
transmission line
Centralized controller
GB-24A

Indoor/outdoor transmission line

CN41

CN40

TB7

Indoor/outdoor transmission line

TB7

CN41

Fig. 2 GB-24A, TB7 scheme

CNTR-40

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

(3) Power supply of M-NET from outdoor unit connector TB3.


GB-24A can also receive power supply from R410A/R407C/ R22 outdoor unit connector TB3. However, if the
outdoor unit shuts down, GB-24A will also automatically shut down. Therefore, this scheme is not recommended
for air conditioning system consisting of multiple outdoor units.

Indoor/outdoor transmission line


TB3
CN41
ME remote
cotroller

Centralized controller
GB-24A

Fig. 3 GB-24A, TB3 scheme.

CONTROLLER

CONTROLLER (Feb. 2009)

CNTR-41

3. System Controller

DATA U4

3-7-2. External input/output usage

CN2

(1). External signal input function


External signal input requires the external I/O adapter (Model: PAC-YG10HA) sold separately.
1). External input
Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
(Select the function on the Initial Setting Web or the Initial Setting Tool)
External signal input function

No

Do not use external input signal


(factory setting)
Execute emergency stop/normal
with level signal

1
2

Perform ON/OFF with level signal

Perform ON/OFF, prohibit/enable


with pulse signals.

Remarks

The local remote controller ON/OFF operations, and the


controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.
The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.
Set the pulse width while the contact is ON to 0.5 to 1 sec.

2). Level signal and pulse signal (12VDC or 24VDC)


(A) Level signal

(B) Pulse signal


(Example) for ON/OFF

Contact ON

0.5 to 1 sec

Contact OFF
Stop

Run

Stop

Signal 1 (run)

Contact ON
Contact OFF
0.5 to 1 sec

Contact ON

CONTROLLER

Contact OFF

Normal Emergency stop Normal

Contact ON
Signal 2 (stop)
Contact OFF
OFF

ON

OFF

The prohibit/enable input is the same.

3). External input specifications


CN2
No.5
No.6

Lead wire
Orange
Yellow

Emergency stop/normal level signal


Emergency stop/normal input
Not used

ON/OFF, level signal


ON/OFF input
Not used

No.7

Blue

Not used

Not used

No.8

Gray

Not used

Not used

No.9

Red

External DC source

ON/OFF, prohibit/enable pulse signal


ON input
OFF input
Local remote controller operation
prohibit input
Local remote controller operation
enable input

(A) For level signal


When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Emergency stop signal will bring the air conditioners to stop, and canceling the
emergency stop will not automatically reset these units. To go back to the previous operation status, they must be
manually turned back on.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.
(B) For pulse signal
Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.

CNTR-42

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

4). Recommended circuit example


(A) For level signal
CN2

Red

X1

Run/stop or
Emergency stop

8
7
6
5

Orange

X1

Power supply
(12VDC or 24VDC)

Max.10m
(32 ft)

This unit

(B) For pulse signal


CN2
9

Power supply
(12VDC or 24VDC)

Red
Gray
Blue
Yellow
Orange

8
7
6
5
1

Y2
Y1
X2
X1

X1

Y1

Y2

Run Stop Prohibit Enable

Max.10m
(32 ft)

This unit

X2

Use relays X1, X2, Y1, and Y2 that meet the


following specifications.
Contact rating
Rated voltage >= 12VDC
Rated current >= 0.1A
Minimum applicable load =< 1mA at DC

The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm2 (AWG 22) or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.

(2). External signal output function


External signal output requires the external I/o adapter (Model: PAC-YG10HA) sold separately.
1). External output
When one or more air conditioners are running, the ON signal will be output and if a malfunction occurs in one or more air
conditioners, the Malfunction signal will be shown.

2). External output specifications


Lead wire
Green

Details of each terminal


Common (External ground)

No.2
No.3

Black
Brown

ON/OFF
Malfunction/normal

" ON" signal and " Malfunction" signal will


both be output.

3). Recommended circuit example


CN2

Use Z1 and Z2 relays having the following specifications.


Operation coil
Rated voltage
:12VDC,24VDC
Power Consumption
: 0.9W or less
( 1)Prepare a power supply separately according to the
relay being used. (12VDC or 24VDC)
( 2)Always insert a diode on both ends of the relay coil.

9
4
3
2

1
This unit

Brown
Black

Green
Max.10m
(32 ft)

Diode(*2)
(*2)
(*2)

Z1

Power (*1)
Supply

Z1

L1

Z2

Z2

L2

L1: Run display lamp


L2: Malfunction display lamp

Each element will turn on while ON operation or a malfunction occurs.


The connection cable can be extended up to 10m (32ft).
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.

CONTROLLER (Feb. 2009)

CNTR-43

CONTROLLER

CN 2
No.1

3. System Controller

DATA U4

3-7-3. LAN connection function


Connect the LAN cable to the LAN connector of this device.
Procure the LAN cable at the site, and use an enhanced category 5 UTP cable.
For a description of the IP address setting method, refer to Installation Manual.
LAN is 10 BASE-T Specification.
The maximum wiring length from HUB to GB-24A is 100m [328ft].
GB-24A is connected to the monitoring PC via HUB.

NOTE

CONTROLLER

Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the MNET transmission line.
When a LAN is already connected, decide the IP address by consultation with the system administrator and
connect to the LAN body after changing the IP address.
Space f or the connector and wiring is required. Refer to Installation Manual.
Connect GB-24A to a private network.
Use a security device such as a VPN router when connecting the GB-24A to the Internet to prevent
unauthorized access.
(If no security devices are installed, the operation settings may be changed by an unauthorized person
without the knowledge of the user.)

CNTR-44

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-7-4. Browser screens of GB-24A

Condition List (Overview)

Malfunction Log

CONTROLLER

Operation (with Setback)

Condition List (Block)

Operation (without Setback)

Malfunction List

CONTROLLER (Feb. 2009)

CNTR-45

CONTROLLER

3. System Controller

CNTR-46

DATA U4

Operation (DIDO Controller)

Measurement status monitor (temperature


sensor/humidity sensor /measurement meter)

Trend Graph (temperature/humidity)

Weekly Schedule

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-8. Power supply unit [PAC-SC50KUA]


PAC-SC50KUA supplies DC powers of 24V and 12V at TB2 and TB3 respectively; the former is for central control transmission
use and the latter is for G-50A operation and LAN function use.
3-8-1. When using PAC-SC50KUA as the power supplier for system controller, the capacity for system controller is considered
as follows.
Central control
transmission line

Main SC

Indoor/outdoor transmission line

TB7

Add : 000

CN41

(DC12V)
TB3
TB2
(DC24V)
Power supply unit
PAC-SC50KUA

Indoor/outdoor transmission line

TB7

Sub SC

CN41
Add : 201

SC : System Controller

Lossnay

Lossnay can have its own Lossnay remote


controller, but the total quantity of the controllers
is limited.
Fig. 3-8-1 Equivalent power consumption of controllers

In this case, pay attention to leave the power supply switch connector on CN41 of the Outdoor unit as the factory setting
before shipment.
Taking the power consumption of the control board of Indoor unit as 1, the power consumption of various controllers is rated at
Table 3-8-1.
Table 3-8-1 Equivalent power consumption of controllers

Central controllers
GB-50A

GB-24A

0.5

Remote controllers

System remote controller


(PAC-SF44SRA)
Schedule timer
(PAC-YT34STA)

ME remote controller
(PAR-F27MEA)
LOSSNAY remote controller
(PZ-52SF)
0.25

0.5

PAC-SC50KUA is capable to supply equivalent power up to 6, therefore the maximum connectable number of system controllers is as follows.
Note: AG-150A cannot be connected to PAC-SC50KUA. Use PAC-SC51KUA to connect to AG-150A.
Table 3-8-2 Max. connectable quantity of controller when using PAC-SC50KUA

Other system controllers

Central controller
G-50A
2 units
(Note 1)

ON/OFF remote controller


GB-50A GB-24A (PAC-YT40ANRA)

2 units

1 unit

6 units

System remote controller


(PAC-SF44SRA)
Schedule timer
(PAC-YT34STA)

Remote controllers
ME remote controller
(PAR-F27MEA)
LOSSNAY remote controller
(PZ-52SF)

12 units

24 units

(Note 1) Due to its current limit of DC12V supplying, the PAC-SC50KUA can supply power for maximum 2 G-50As.
Note: AG-150A cannot be connected to PAC-SC50KUA. Use PAC-SC51KUA to connect to AG-150A.
As the air conditioner control system may combine all kinds of system controllers, the total power consumption of system controllers need to count with Table 3-8-1.
For example, the controller system contain 1 G-50A, 2 ON/OFF remote controllers (PAC-YT40ANRA), 1 schedule timer (PACYT34STA), 6 Lossnay remote controllers connected at centralized control communication line.
then the total power consumption is
1x0.5+2x1+1x0.5 +6x0.25 = 4.5 6.
One PAC-SC50KUA is therefore enough. The total power consumption should not exceed 6.

CONTROLLER (Feb. 2009)

CNTR-47

CONTROLLER

G-50A

Other system controllers


ON/OFF remote controller
(PAC-YT40ANRA)

3.
controller
3.System
Systemremote
Controller

DATA U3

DATA U4

3-8-2. When supply power to 1 G-50A, the PAC-SC50KUA can supply power to other system controllers as follows.
Table 3-8-3 Connectable number of system controller when 1 G-50A is used.

V : Connectable
Total number of ON/OFF remote controller (AN)

Total number of
System remote controller
Schedule timer

V
V

10

11

12

CAUTION

When applying Charge and/or Peak-cut function on G-50A, Power Supply Unit (PAC-SC50KUA) is recommended to use. G-50A is possible to
receive power from one of the Outdoor units, but there is a risk that the failure of power supply from the Outdoor unit will cause G-50A's functiondown on the whole system.

3-8-3. When supply power to 1 GB-50A, the PAC-SC50KUA can supply power to other system controllers as follows.
Table 3-8-4 Connectable number of system controller when 1 GB-50A is used.

CONTROLLER

V : Connectable
Total number of ON/OFF remote controller (AN)

Total number of
System remote controller
Schedule timer

7
8
9
10
11
12

CAUTION

CNTR-48

When applying Charge and/or Peak-cut function on GB-50A, Power Supply Unit (PAC-SC50KUA) is recommended to use. GB-50A is possible to
receive power from one of the Outdoor units, but there is a risk that the failure of power supply from the Outdoor unit will cause GB-50A's functiondown on the whole system.

CONTROLLER (Feb. 2009)

CONTROLLER

Cntr- 31

3. System Controller

DATA U4

External dimension
Unit:mm[in.]

265[10-7/16 ]
150[ 5-29/32]

240 [9-7/16]

225 [8-27/32 ]

59.2[ 2-11/32 ]

TB3
TB2

Cable fixture
TB1

Cable fixture

CONTROLLER

CONTROLLER (Feb. 2009)

CNTR-49

3. System Controller

DATA U4

3-9. Power supply unit [PAC-SC51KUA]


PAC-SC51KUA supplies DC power of 22-30V and 24V at TB2 and TB3 respectively; the former is for centralized transmission use
and the latter is for AG-150A operation and LAN function use.
3-9-1. When using PAC-SC51KUA as the power supplier for system controller, the capacity for system controller is
considered as follows.
Centralized control
transmission line

Main SC

Indoor/outdoor transmission line

TB7

CENTRALIZED CONTROLLER AG-150A

Add : 000

CN41

(24VDC)
TB3
TB2
(30VDC)

M-NET

Power supply unit


PAC-SC51KUA

Indoor/outdoor transmission line

TB7

Sub SC

CN41
Add : 201

SC : System Controller

LOSSNAY

Lossnay can have its own Lossnay remote


controller, but the total quantity of the controllers
is limited.
Fig. 3-9-1 Equivalent power consumption of controllers

In this case, pay attention to leave the power supply switch connector on CN41 of the Outdoor unit as the factory setting
before shipment.
Taking the power consumption of the control board of Indoor unit as 1, the power consumption of various controllers is rated
at Table 3-9-1.
Table 3-9-1 Equivalent power consumption of controllers

Other system controllers

CONTROLLER

Centralized controller *1

AG-150A

GB-50A

GB-24A

ON/OFF remote controller


(PAC-YT40ANRA)

0.5

Remote controllers

System remote controller


(PAC-44SRA)
Schedule timer
( PAC-YT34STA)

ME remote controller
(PAR-F27MEA)
LOSSNAY remote controller
(PZ-52SF)

0.5

0.25

*1: G-50A cannot be connected to PAC-SC51KUA. Use PAC-SC50KUA to connect G-50A.


PAC-SC51KUA is capable to supply eqovalent power up to 5, therefore the maximum connectable number of system controller
is as follows.
Table 3-9-2 Max. connectable quianity of controller when using PAC-SC51KUA

Centralized controller *1

Other system controllers

Remote controllers

AG-150A

GB-50A

GB-24A

ON/OFF remote controller


(PAC-YT40ANRA)

System remote controller


(PAC-44SRA)
Schedule timer
( PAC-YT34STA)

ME remote controller
(PAR-F27MEA)
LOSSNAY remote controller
(PZ-52SF)

1 unit

1 unit

1 unit

5 units

10 units

20 units

*1: G-50A cannot be connected to PAC-SC51KUA. Use PAC-SC50KUA to connect G-50A.


As the air conditioner control system may combine all kinds of system controllers, the total power
consumption of system controllers need to count with Table 3-9-2.
For example, the controller system contain 1 AG-150A, 2 ON/OFF remote controllers (PAC-YT40ANRA),
1 schedule timer (PAC-TY34STA), 6 Lossnay remote controllers connected at centralized control
communication line.
Then the total power consumption is
1 x 0.5+2 x 1+1 x 0.5+6 x 0.25 = 4.5 < 5.
One PAC-SC51KUA is therefore enough. The total power consumption should not exceed 5.
CNTR-50

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-9-2. When supply power to 1 AG-150A, the PAC-SC51KUA can supply power to other system controllers as follows.
Table 3-9-3 Connectable number of system controller when 1 AG-150A is used.

V : Connectable
Total number of ON/OFF remote controller(AN)

Total number of
System remote controller(SR)
Schedule timer(ST)

10

CAUTION

When applying Charge and/or Peak-cut function on AG-150A, Power Supply Unit (PAC-SC51KUA) is recommended to use.
AG-150A is possible to receive power from one of the Outdoor units, but there is a risk that the failure of power supply from
the Outdoor unit will cause AG-150A's functiondown on the whole system.

3-9-3. When supply power to 1 GB-50A, the PAC-SC51KUA can supply power to other system controllers as follows.
Table 3-9-4 Connectable number of system controller when 1 GB-50A is used.

V : Connectable
Total number of ON/OFF remote controller(AN)
1

CONTROLLER

Total number of
System remote controller(SR)
Schedule timer(ST)

5
6
7
8
9
10

CAUTION

When applying Charge and/or Peak-cut function on GB-50A, Power Supply Unit (PAC-SC51KUA) is recommended to use.
GB-50A is possible to receive power from one of the Outdoor units, but there is a risk that the failure of power supply from
the Outdoor unit will cause AG-150A's functiondown on the whole system.

CONTROLLER (Feb. 2009)

CNTR-51

3. System Controller

DATA U4

External dimension
Unit:mm[in.]
72(2-7/ 8)

130(5-1/ 8)
T

CONTROLLER

TB2,TB3

CNTR-52

CONTROLLER (Feb. 2009)

TB1

155(6-1/ 8)

This device complies with Part15 of the FCCRules.Operation is


subject to the following two conditions:(1)this device may not cause
harmful interference,and(2)this device must accept any interference
received,including interference that may cause undesired operation.

UP

169(6-11/ 16)

271(10-11/16)
90(3-9/16)

3. System Controller

DATA U4

3-10. Integrated centralized control software [TG-2000A]


3-10-1. Example of Basic System Configuration.
Single-phase 208/230V

M-NET
Charge
license

CENTRALIZED CONTROLLER AG-150A

Input

AG-150A

Web
monitor
license

Schedule
license

24VDC

Single-phase 208/230V

Power supply unit


PAC-SC51KUA

3-phase 208/230V
(3-wire)

Indoor unit system


watt-hour meter

Compatible with TG-2000A Ver. 4.10 and higher


The electric amount count software or separately
procured parts must be used with the designated PLC.

Indoor unit
watt-hour meter

power source

Outdoor unit system


watt-hour meter
USB or
RS-232C

Indoor unit
watt-hour meter
Outdoor unit system
watt-hour meter

RS-485
Converter
Central controller
personal computer
TG-2000A

Uninterruptive
power supply (UPS)

TG-2000
Integrated
centralized control
software installation

Indoor unit system


watt-hour meter

PLC (with electric amount count


software)
Central control
personal computer
TG-2000A

Uninterruptible
power supply (UPS)

Integrated centralized control


software installation

The TG-2000A can realize the following functions


using the AG-150A/G(B)-50A option (license).

Main features of TG-2000A

CONTROLLER

CENTRALIZED CONTROLLER AG-150A

Operation/monitor
Annual/weekly schedule
Charge
Energy saving 1
Peak cut 1
1: Compatible with TG-2000A Ver. 4.10 and
higher, G-50A Ver. 2.51 or later.

1 Up to 2000 indoor units (40 AG-150, G-50A, GB-24 or GB-50A units) can be operated and monitored
. simultaneously
2 The air-conditioner layout can be displayed on the screen, making control and operation easier.
3 The annual and weekly schedules can be set. Two schedules, such as the summer master and winter master, can be

saved in the weekly schedule.

4 Air-conditioning charges can be calculated based on the multiple air-conditioner usage results. The power apportionment

6
7
8

percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment
Power apportionment charging is not possible with the old model, A control or K control.
function, and can be output as a CSV format file.
Charging without WHM
: The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)
RS-485 WHM charging
: The RS-485 WHM value is automatically tabulated to calculate the air-conditioning charges.
PLC + pulse WHM charging : The pulse output WHM value is automatically tabulated by the PLC to calculate the airconditioning charges.
Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and
"performance save operation (60% to 90%)" functions.
Energy saving operation matching the amount of power in use is possible by using the PLC's electric amount count
software.
Night Set-Back function operation is possible with schedule settings. 1,4
General equipment can be operated and monitored. 2
General equipment can be schedule-controlled when using PAC-YG21CDA with PLC.
For details of PLC refer to Installation Manual of PAC-YG21CDA. 3
1: Compatible with TG-2000A Ver. 4.10 or later, G-50A Ver. 2.51 or later.
2: Compatible with TG-2000A Ver. 4.30 or later, G-50A Ver. 2.51 or later.
3: Compatible with TG-2000A Ver. 4.60 or later, G-50A Ver. 2.70 or later.
4: With Night Set-Back function, the CITY MULTI system can run at heating mode with target temperature set to 54
12 under
schedule control. This function can protect the room from dropping down to extremely low temperature at mid-night.
Note: AG-150A (Ver. 1XX Series) will be compatible with TG-2000 Ver. 5.5 or later. Depending on the versions of TG-2000 and
G(B)-50A, some functions may not be available.

CONTROLLER (Feb. 2009)

CNTR-53

3. System Controller

DATA U4

3-10-2. List of TG-2000A functions


The data for each G-50A/GB-50A can be grouped and used to control the operation of up to 2000 units in floor or block units, etc.,
from the personal computer screen. By using a PLC or a watt-hour meter, the power rate can be apportioned, energy saving
control can be executed, and other general equipment can be controlled.

List of integral software functions


G-50A/GB-50A license

CONTROLLER

Operation modes

The operation mode can be switched between COOL, DRY, FAN, AUTO and
HEAT for all floors or in block, floor or group units.

Temperature setting

The room temperature can be set for all floors or in block, floor or group units.
Set temperature range COOL / DR
HEAT
AUTO
Depend on unit type

Fan speed

The fan speed can be set to four stages for all floors or in block, floor or group units.

Air direction

The air direction can be set in four vertical directions or to swing for all floors or in block,
floor or group units.(The selectable air direction dif fers according to the model.)

Interlocked unit ON/OFF


(LOSSNAY)

If there is an interlocked unit (LOSSNAY), the unit can be turned ON (strong/weak) or OFF for all floors
or in block, floor or group units. (Note that the ventilation mode cannot be selected for interlocked units.)

Local operation
prohibit

The items for which operation with the local remote controller are to be prohibited can be selected for
all floors or in block, floor or group units. (The items that can be prohibited are ON/OFF, operation mode,
set temperature and filter sign reset.)

Annual / weekly
schedule

The annual/weekly schedule function can be used by registering the license.


Two settings, such as seasonal settings for summer and winter, can be saved.

Power rate
apportionment charging
(power rate manual input)

By registering the G-50A unit license number, the power rate apportionment percentage data for
each indoor unit can be output in CSV format. The power rate for each tenant can be easily
calculated by having each user input the power rate manually.

Power rate
apportionment charging

An RS-485 watt-hour meter is connected to calculate the air-conditioning charges based on the
amount each tenant's air-conditioner has operated. Two charging rates can be applied per day.
V

By using a PLC (with electric amount count software) and a watt-hour meter with pulse transmitter,
the air-conditioning charges can be calculated based on the amount each tenant's air-conditioner has
operated.Up to five charging rates can be applied per day. 1
History

Up to 3000 items for the error history and up to 10000 items for operation history can be saved.
Each history file can be output as a daily report or monthly report in CSV format.
The operation history consists only of the operations carried out with the TG-2000A, and is limited to some limited operation items.

The cumulative operation time of each indoor unit can be viewed or output as a CSV format file.
(This function is valid only when the charging function license is registered.)

Filter sign display


mask

Automatic display of the filter sign can be disabled. (System batch.)


In this case, the filter sign state is confirmed with manual operations .

Energy saving
control 1

Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation
changeover" and "performance save operation" functions.

Energy saving
(peak cut) 1

Energy saving operation matching the amount of power in use is possible.


(PLC (with electric amount count software) and watt-hour meter with pulse transmitter are required.)

V
V

Set temperature
limit 1

The set temperature lower limit can be set for cooling and the upper limit for heating.
(Valid only when PAR-F27MEA is used.)

Control other general


equipment

It is possible to control other general equipment on ON/OFF operation / monitoring / Alarm /


scheduling, if TG-2000A combines PLC installed with PLC software PAC-YG21CDA. 2

Setting inter-lock with CITY MULTI indoor units is possible.


(Table setting tool for input/output definition is needed.) 3

The ON/OFF status of the connected general equipment and the error status can be
changed or monitored from the DIDO (PAC-YG66DCA).

1: Compatible with TG-2000A Ver. 4.10 or later, G-50A Ver. 2.51 or later.
2: Compatible with TG-2000A Ver. 4.30 or later, G-50A Ver. 2.51 or later.
3: Compatible with TG-2000A Ver. 4.60 or later, G-50A Ver. 2.70 or later.
4: With Night Set-Back function, the CITY MULTI system can run at heating mode with target temperature set to 54
This function can protect the room from dropping down to extremely low temperature at midnight.
Note: Depending on the versions of TG-2000 and G(B)-50A, some of the functions may not be available for use.

CNTR-54

CONTROLLER (Feb. 2009)

12

Operation time monitor

Night Set-Back function 1,4

PLC for
general equipment

The general equipment can be turned ON and OFF.


( A PLC and the general equipment control PLC software required.) 2

Energy saving
(peak cut)

Energy saving

The units can be turned ON and OFF for all floors or in block, floor or group units.

Schedule

Details

Charge

ON/OFF

Web monitor

Item

under schedule control.

V
V
V

3.3.System
remote
controller
System
Controller

DATA U3

DATA U4

3-10-3. Browser screens of TG-2000A

Weekly schedule screen


Floor screen

Annual schedule screen


Block screen

CONTROLLER

All floor screen

Operation setting screen

Air-conditioning charge screen

CONTROLLER (Feb. 2009)


CONTROLLER

CNTR-55
Cntr35

3. System Controller

DATA U4

3-10-4. Requirements (system recommendations)


We recommend the following software and hardware when using this application (TG-2000A).

Item

Requirement

Recommended

PC

PC/AT interchangeable machine

Operation check completed, using IBM, and DELL

CPU

Within 1000 indoor units :


Pentium 4 1.8GHz or faster
1001 indoor units or over :
Pentium 4 1.8GHz or faster
(Case of temp, trend use : 2.8GHz or faster.)

Pentium 4

Memory

128MB or more (In Windows XP : 256MB or more)

512MB or more

HDD

6GB or more (2GB or more of C drive free


space necessary)

4GB or more of C drive free space necessary


When using the trend function, the drive used for automatic output must have the following free space according to the number of groups.
200 groups = 2GB, 500 groups = 5GB,
1000 groups = 10GB, 2000 groups = 20GB

Storage device

FDD, CD-ROM drive

Devices other than those shown at the left may also


be installed.

Resolution
Serial port

1024 768 or higher, 65536 colors or more


1 port or more

LAN
OS

Internal LAN (10/100 Mbps)


Windows XP Professional
Windows 2000 Professional
Service Pack 2 and above

Other

Computer must be dedicated for this use


(TG-2000A).

2.8GHz or faster

Required when using RS-485 communication WHM


1
English version only
Personal computer must support each OS.

1 Purchase the option, or use the equipment recommended for the personal computer when purchasing the personal computer.

CONTROLLER

3-10-5. Compatible Units

The TG-2000A has two main functions: centralized control of air conditioners and cost accounting. However, not all
functions are available with all air conditioners. (TG-2000A Ver.4.80 or later)
Table: Compatible units and function list ( : supported, : Certain restrictions apply, : Not supported)
Function
Model

Control/
Maintenance

Charging (Billing) with WHM

Y-Series

R2-Series

WR2-Series

WY-Series

S-Series

Indoor unit

LOSSNAY

OA processing unit
"A" control type 3

"K" control type

(Adapter required)
(Converter required)

1 : Can be calculated for each charging block. May not be available with some older models.
2 : Indoor unit models before Free Plan models do not support a charge apportioning billing method based on
the capacity save. The existence of even a single unit of those types in the system requires that the
method of charge apportioning billing be set to either Thermo on time or Fan operation time.
3 : Not all of the A-control and K-control units support these functions. The calculation of the charge for the
auxiliary heater may not be handled by these units.
4 : LOSSNAY groups to which the remote controller is connected support the charging system.

CNTR-56

CONTROLLER (Feb. 2009)

1
1

3. System
Controller
System remote
controller

DATA
DATA U3
U4

3-11. Electric
amount
count count
software
[PAC-YG11CDA]
3-11.
Electronic
amount
software
[PAC-YG11CDA]
MITSUBISHI ELECTRIC offers charging function for the air conditioner system. Detailed output of every indoor on electricity
consumption of air-conditioning is available. The electricity consumption of air-conditioner is counted based on the refrigerant
consumption of every indoor unit, which makes the proportion of electricity consumption precise.

System example
Single-phase 208/230V
Charge
license

Input

CENTRALIZED CONTROLLER AG-150A

AG-150A
DC12V

Single-phase 208/230V
Power supply unit
PAC-SC51KUA
3-phase 208/230V
(3-wire)
Outdoor unit system
watt-hour meter

Indoor unit system watt-hour meter


Indoor unit system watt-hour meter

PLC (Pulse counting software installed)

Uninterrupted
power source (UPS)

PC for TG-2000A

Install TG-2000A software

CONTROLLER

Necessary parts for the system


Name (Model name)
PC for central control

Manufacturer
PC/AT convertible unit

TG-2000A
Charge license
Web monitor license
PLC

MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC

PAC-YG11CDA
Watt-hour meter with pulse oscillator

MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC

Uninterrupted power source (UPS)

Remarks
Confirmed operation of IBM, DELL, Hp Compaq.
For details, refer to G-50A Technical Manual.
Requires for each AG-150A/G-50A/GB-50A.
Requires for each AG-150A/G-50A/GB-50A.
PLC for pulse counting connects maximum 5 sets.
For details, refer to Installation Manual of PAC-YG11CDA.
For details, refer to G-50A Technical Manual.
For the specification of the watt-hour meter, refer to G-50A
Technical Manual.
Field supplied.

CONTROLLER (Feb. 2009)


CONTROLLER

CNTR-57
Cntr- 37

3. System Controller

DATA U4

3-12.PLC
PLCsoftware
software
general
equipment
[PAC-YG21CDA]
(SW-PLC-GE])
3-12.
for for
general
equipment
[PAC-YG21CDA
(SW-PLC-GE)]
MITSUBISHI ELECTRIC's Air Conditioner control system can combine control of general equipment like lighting, air conditioners from others, and so on.
Functions on general equipment : On/Off operation, alarm, monitoring, scheduling.

System example
M-NET *1

LAN
CENTRALIZED CONTROLLER AG-150A

license

Input

AG-150A

*1.MITSUBISHI ELECTRIC Air Conditioner network.


M-NET *1
PAC-SC51KUA
Power supply unit

Free contact
(input and output signal)

CENTRALIZED CONTROLLER AG-150A

AG-150A

Pulse or Level output


Lighting

Level input

PLC

PC for TG-2000A

Other manufacturer's packaged


air-conditioning units

TG-2000A installed.
PLC software for general equipment
PAC-YG21CDA [SW-PLC-GE]

Other manufacturer's fan coil units

CONTROLLER

Chiller/heat source
machine

Necessary parts for the system


Materials (model names)
PC for central control

Maker
PC/AT compatible

TG-2000A
Web monitor license
PLC for general equipments license
PLC
PAC-YG21CDA [SW-PLC-GE]

MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC

CNTR-58

Remarks
Confirmed operation of IBM, DELL, Hp Compaq.
For details, refer to G-50A Technical Manual.
Use Ver.4.60 or later (Use G-50A's Ver. 2.70 or later)
Requires for each AG-150A/G-50A/GB-50A.
Table-setting of input/output is necessary.
Make sure DI board and DO board are mounted.
For details, refer to G-50A Technical Manual.

CONTROLLER (Feb. 2009)


CONTROLLER

Cntr- 38

3. System Controller

DATA U4

3-13.
BACnet interface
interface
[PAC-YG31CDA
(SW-BACnet)]
3-13. BACnet
[PAC-YG31CDA]
[SW-BACnet]
CITY MULTI can easily combine into a Building Management System (BMS) via the BACnet interface software and a PC.
BACnet is an opened transmission protocol widely used at BMS, and related equipment control. CITY MULTI is therefore
compatible with large-scaled BMS management via BACnet.
One BACnet interface software and PC serves up to 10 AG-150A/G-50As/GB-50As.

System example

Central
monitor
BACnet

BMS

M-NET

LAN
CENTRALIZED CONTROLLER AG-150A

AG-150A
BACnet interface software
PAC-YG31CDA (SW-BACnet)
M-NET
PAC-SC51KUA
Power supply unit

CENTRALIZED CONTROLLER AG-150A

AG-150A

Web
Browser
(Optional)

TG-2000A
(Optional)

CONTROLLER

Communication items at BACnet Interface Software PAC-YG31CDA (SW-BACnet)


On/Off
Mode
Fan speed
Air direction
Set temp.
Filter sign reset

Operation Prohibit local On/Off


Prohibit local Mode
Prohibit local Filter sign reset
Prohibit local Set temp.

On/Off
Mode
Fan speed
Air direction
Set temp.
Filter sign
Indoor temperature
State
Prohibit local On/Off
Monitoring
Prohibit local Mode
Prohibit local Filter sign reset
Prohibit local Set temp.

Forced Off
Use a dedicated PC with the BACnet interface software (PAC-YG31CDA).

Alarm signal
Error code
Communication state

CONTROLLER (Feb. 2009)

CNTR-59

3. System Controller

DATA U4

3-14.
for for
demand
inputinput
[PAC-YG41CDA]
3-14.PLC
PLCsoftware
software
demand
[PAC-YG41CDA]
MITSUBISHI ELECTRIC's CITY MULTI has its intelligent way to carry out peak-cut control while maximizing the air conditioning effect.

System example

- Energy saving setting


- Monitoring of current energy saving
state

The registration of
License energy saving control
or peak cut control is
necessary.

- Set temperature control (


- Fan (thermostat OFF) control
- Stopping control

CENTRALIZED CONTROLLER AG-150A

AG-150A

PC for TG-2000A

Collects current
daily consumption
(every per minute)

Collects daily
power
consumption

- Capacity saving control


(60/70/80/90%)

Watt-hour
meter
PLC PAC-YG11CDA
(Pulse counting
software installed)

Counts for electric power pulse

Requires to execute the peak cut control.


Either method should be used.These methods cannot be used together.

CONTROLLER

PLC
(PLC software
for demand input)

Demand
controller
Contact input (4 levels max.)

If the quantity of G-50A exceeds 11 sets, one set of PLC is required


for each 10 sets of PLC.

Necessary parts for the system


Name (Model name)
PC for central control

Maker
PC/AT convertible unit

TG-2000A
G-50A/GB-50A
Energy saving control (peak cut) license
Web monitor license

MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC

CNTR-60

CONTROLLER (Feb. 2009)

Remarks
Confirmed operation of IBM, DELL, Hp Compaq.
For details, refer to G-50A Technical Manual.
Use Ver.4.6 or later.
Use Ver.2.6 or later.
Requires for each AG-150A/G-50A/GB-50A.
Requires for each AG-150A/G-50A/GB-50A.

or

3. System remote controller


3. System Controller

DATA U3

DATA U4

Applying the energy saving setting from the integrated centralized control software TG-2000A or Initial setting Web allows
conducting the energy saving control by the indoor/outdoor units or peak-cut control by using PLC.
Energy saving
control

Item
Indoor unit control

Content
The TG-2000A or Initial setting Web sets the f ollowing energy saving items and energy saving
time to G-50A/GB-50A per operation block. G-50A/GB-50A conducts energy saving operation to
the indoor units with the set detail.
Temperature control (
Fan control (Thermostat ON)
Stopping control
For the block with temperature difference between set and inlet temperature exceeding the set,
the energy saving control set at level 0 is not applied.
The TG-2000A or Initial setting Web sets the following energy saving items and energy saving
time to G-50A/GB-50A per outdoor unit and the set G-50A/GB-50A conducts the energy saving
operation for the outdoor unit.

Outdoor unit
control 2
Peak cut control Power consumption
monitoring method
Demand controller
method

Monitoring of
energy saving
control
status/history1

Control status
Daily report
Monthly report

Connecting the watt-hour meter (PLC) allows conducting energy saving operation meeting the
power consumption. The control object and detail are same as that of the energy saving rotated
control. One set of the watt-hour meter can be set for each G-50A/GB-50A.
Energy-saving control that is appropriate to the current demand level is performed by receiving
the demand level contact signal from the demand controller using the PLC.
An installation of demand input PLC software is necessary to use the PLC.
Control targets and control content of this method are the same as those of the energy-saving control.
Each PLC unit can control up to ten G-50A units to be on the energy-saving control.
During the energy saving control, the energy saving mark is displayed on the air conditioner
group icon of Web, integrated software.
Daily power consumption and control level can be monitored by the integrated software. G-50A/GB-50A
can hold the data for 3 days max. including that of today, yesterday and the day before yesterday.
Monthly power consumption can be monitored by the integrated software (for 62 days max.).
The integrated software monitors from PLC for display and storing.

1; Daily Report and Monthly Report are functions that are enabled only when registering the "Energy-saving peak cut control license."TG2000A must always be kept in operation to gather data on energy-saving control status and the operation history. The auto-output CSV
files in the Daily Report and Monthly Report can be saved for two years in the appropriate folders.
2; For Mr. Slim units, apply Outdoor Unit Control function only to Inverter type units.

CONTROLLER

CONTROLLER
CONTROLLER (Feb. 2009)

Cntr- 41
CNTR-61

3. System Controller

DATA U4

interface [LMAP03U]
3-15.
LonWorks
3-15. LonWorks
interface [LMAP03U]

CITY MULTI can easily combine into a Building Management System (BMS) via the LONWORKS and M-NET adapter
LMAP03U. LONWORKS is an opened transmission protocol widely used at BMS and related equipment control.
CITY MULTI is therefore compatible with large-scaled BMS management via LONWORKS .

One LMAP03U serves up to 50 indoor units. (CITY MULTI , Mr. Slim , and LOSSNAY .)

System example

LMAP

Building management system

Protocol : LONWORKS

LMAP

Lighting

CONTROLLER

Elevator

Communication items at LONWORKS

and M-NET Adapter LMAP03U

On/Off
Mode
Set point from network (Set temp.)
Fan speed

Thermo On/Off
State
Indoor temperature
Monitoring Alarm signal

Operation
Prohibit local On/Off
Prohibit local Mode
Prohibit local Set temp.
Batch Off

CNTR-62

On/Off
Mode
Set point from network (Set temp.)
Fan speed

CONTROLLER (Feb. 2009)

Prohibit local On/Off


Prohibit local Mode
Prohibit local Set temp.

3. System
System remote
controller
3.
Controller

DATA U3

DATA U4

Environment specification
Item

Description

Connected Equipment

MITSUBISHI ELECTRIC

CITY MULTI
Mr.SLIM
LOSSNAY

Multiple split-type air conditioners


Split-type air conditioners
Heat recovery ventilators

( For details of the connectable models,please contact the dealer.)


Number of Units

LMAP can control 50 indoor units (Including


(including LOSSNAY
LOSSNAY))

Neuron CHIP

TMPN3150 (10MHz)

Network Transceiver
Performance

FTT-10A (Free Topology 78kbps)

Average communication capacity

2.5 inputs/second

Peak communication capacity

50 inputs/second (for one second)

The proper communication is not obtainable when communication intervals exceed its performance, assure sufficient intervals.
ACK Service is recommended for the network service.
Detailed specifications for the LONWORKS network can be found in " FTT-10A Free Topology Transceiver User's Guide " by Echelon Corporation.

<LMAP03U Network Variables>


Network Variables

Request On/Off

nv1n nviOnOff_n

nv2n

nvoOnOff_n

On/Off state

Request Mode

nv3n nviMode_n

nv4n

nvoMode_n

Mode state

Setpoint from network


(set temp.)

nv5n nviSetPoint_n

nv6n

nvoSetPoint_n

Setpoint state
(set temp.)

Request Fanspeed

nv7n nviFanSpeed_n

nv8n

nvoFanSpeed_n

FanSpeed state

Request prohibit
(note3,4) local On/Off
Request prohibit
(note3,4) local Mode
Request prohibit
(note3,4) local Setpoint

nv19n nviProOnOff_n
nv21n nviProMode_n
nv23n nviProSetPoint_n

nv10n nvoThermo_n

Thermo On/Off state

nv12n nvoSpaceTemp_n

Indoor Temperature state

nv16n nvoAlarm_n

Alarm signal

nv20n nvoProOnOff_n

Prohibit local
On/Off state

(note3, 4)

nv22n nviProMode_n

Prohibit local
Mode state

(note3, 4)

nv24n nviProSetPoint_n

Prohibit local
Setpoint state (note3, 4)

CONTROLLER

(note1) The case of CITY MULTITM is indicated.


(note2) There is a case which cannot be used with the system configuration of the air conditioners units.
(note3) "n" of the network variable shows indoor unit address (M-NET).
(note4) It is possible to use when the "MA" remote controller.

External dimension
Unit:mm[in.]

360[14-3/16 ]
60[2-3/8 ]

Item

Description
340 (H) x 360 (W) x 59.6 (D)

Dimensions

[13- 7/16(H) x 14-3/16 (W) x 2-3/8 (D)]


3.4 kg (7-1/2 lb)

Net Weight
Power Source

~ 208 - 230V (60 Hz)

Current Consumption
340[13-7/16 ]

Operating Range
Temperature
Operation
Storage Range
Environment
Humidity
Installation Environment

50 mA (Maximum)

30 to 95 RH (No condensation)
In the control box

Detail of A section
4.5[ 3/16]
R
7.5[ 5/16 ]

240[9-1/2 ]

325[12-13/16 ]

10[13/32]

59.6[ 2- 3/8]
9.6[3/8]

10

[13
/32 ]

CONTROLLER
CONTROLLER (Feb. 2009)

CNTR-63
Cntr- 43

3. System Controller

DATA U4

3-16. DIDO controller [PAC-YG66DCA]


The DIDO controller is used in combination with a(n) AG-150A/G(B)-50A/GB-24A to operate general-purpose equipment, as well as to
monitor operating and error status. It is equipped with two sets of standard terminal s (Channels 1 and 2), and four sets of expansion
connectors for the input/output terminals. Expansion cable is optional.
Other devices can only be controlled from AG-150A, AG-150A/G(B)-50A/GB-24A Web browser and TG-2000A. Operation cannot be
monitored or performed from the G-50A LCD.
In addition, this device includes a function that interlocks M-NET devices such as indoor units, general equipment, etc.

26 (11/32)

External Dimensions

111 (43/8)

52 (21/16)

200 (77/8)
150 (529/32)
46.5 (127/32)

45 (125/32)
9 (3/8)

4.5
(3/16)

DIDO controller

PAC-YG66DCA

[ Junction Terminal ]

[ OUTPUT ] Non-voltage Contact Output


Ch1
Ch2
ON/OFF,(ON)
(OFF) ON/OFF,(ON)
(OFF)

[ OUTPUT ] Transistor Output 24 VDC


Ch1
Ch2
ON/OFF,(ON)
(OFF) ON/OFF,(ON)
(OFF)

N623

DIDO controller
PAC-YG66DCA

MODEL

SERVICE REF. PAC-YG66MCA-J

INPUT VOLTAGE

This device complies with Part15 of the FCC Rules.Operation is


subject to the following two conditions: (1)this device may not cause
harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation.
[ Expansion I/O ]
Ch5,Ch6 Ch3,Ch4

26 (11/32)

[ INPUT ]

Ch1

ON/OFF

Error

WEIGHT

DC24V;0.2A

110 (411/32)
120 (43/4)

107.6 (41/4)

[ Output LEDs ]
Ch1
Ch2
ON/OFF (OFF) ON/OFF (OFF)
(ON)
(ON)

0.6 kg / 13/ 8 lb

SERIAL No.
MADE

Ch2

ON/OFF

IN

JAPAN

[ 24 VDC Power Supply]


Error

83.5 (35/16)

27 (13/32)

CONTROLLER

15 (19/32)

26 (11/32)

Unit: mm (in)

CAUTION

CNTR-64

Usage Restrictions
Mitsubishi Electric does not take financial responsibility for damages caused by issues beyond our control or
special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to
other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or
electrical power failure at the end-user site.
Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not
limited to, device testing, startup, readjustment, and replacement.
Do not use this device in disaster prevention, security, or "critical to life" applications.
It is recommended to provide an external switch for general-purpose equipment in case of a failure of the
DIDO controller or a peripheral part.

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-16-1. Specifications
3-16-1-1. Device Specifications
Item
Power Supply

Rating and Specification

M-NET communication

Standard

ON/OFF,
(ON)
(*4)

(OFF)
(*4)

Expansion

Input

Output

17 to 30 VDC (*2)

Screw terminal block


(M3) (*8)

Applied load
MAX: 24 VDC, 5 W
Non-voltage Relay contact (2)
MIN: 5 VDC, 2 mW
* AC loads cannot be
connected.

Screw terminal block


(M3.5) (*8)

24 VDC 40 mA or less
(*5)

Transistor (2)

Output
(*3)

Interface

Applied load
MAX: 24 VDC, 5 W
Non-voltage Relay contact (2)
MIN: 5 VDC, 2 mW
* AC loads cannot be
connected.

Screw terminal block


(M3.5) (*8)

24 VDC 40 mA or less
(*5)

Screwless terminal
block

Error/Normal

Non-voltage a contact
(2 each)

24 VDC 1 mA or less
(*6)

Screwless terminal
block

ON/OFF, (ON)
(*4)

Transistor (4 each)

24 VDC 40 mA or less
(*5)

9 pin connector

24 VDC input (4 each)

24 VDC 1 mA or less
(*7)

9 pin connector

ON/OFF

(OFF) (*4)
Input

Screwless terminal
block

Transistor (2)

ON/OFF
Error/Normal

Output Pulse Width


Interlock
Function

Screw terminal block


(M3) (*8)

24 VDC 10%: 5 W (*1)

1s

1s 30 ms

30 ms

Interlock M-NET devices and output contacts according to status of input contacts. (*8)
0 to 40

Storage temperature range

-20 to 60

[32

to 104

Temperature

Dimensions

200 (W) 120 (H) 45 (D) mm / 77/8 (W) 43/4 (H) 125/32 (D) in

Weight

0.6 kg / 13/8 lb

Time Backup
During Power
Failure

In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)

Installation
Environment

Inside a control panel (indoors)


* Use this product in a hotel, a business office environment or similar environment.

Humidity

[-4

to 140

30 to 90%RH (no condensation)

*1: For details, refer to "3-16-1-2. Parts Purchased Separately".


*2: Supply electric power from a power unit for the transmission line or an outdoor unit.
Furthermore, the power consumption factor of the M-NET circuitry of this device is "1/4" (equivalent to one ME Remote Controller).
*3: Non-voltage Relay contact or transistor is available for output. Only one can be used at a time.
*4: ( ) is in the case of a pulse.
*5: The output is open collector type. Power must be supplied from an external power source to the output circuit of this device.
*6: Power is supplied from this device to the external contacts.
*7: Power must be supplied from an external power source.
*8: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread).
The number indicates the screw diameter (mm).

CONTROLLER (Feb. 2009)

CNTR-65

CONTROLLER

Operating temperature range

Environment
Conditions

3. System Controller

DATA U4

3-16-1. Specifications
3-16-1-1. Device Specifications

Centralized control line


Power supply unit
PAC-SC51KUA

M-NET
LAN

M-NET

Indoor control line


DIDO controller

CENTRALIZED CONTROLLER AG-150A

AG-150A
or G(B)-50A *1

CITY MULTI

24 VDC
Power supply

(a) (b) (c) (d)

Ventilation fan,
lighting, etc.

up to 6 units

DIDO control
24 VDC
Power supply

(a) (b)
(c) (d)

AG-150A/G(B)-50A
Web or TG-2000A*2

Ventilation fan,
lighting, etc.

up to 6 units

* This figure omits the power supply line and only shows the transmission line.
*1: The DIDO controller can be connected to G(B)-50A with Ver.3.20 or later.
*2: The DIDO controller can be connected to TG-2000A with Ver.5.10 or later.

(a) ON/OFF, (ON) output


(b) (OFF) output
(c) ON/OFF input
(d) Error/Normal input
Standard: Terminal block (for 2 units)
Expansion: Connectors (for 4 units)
Total: 6 units

CONTROLLER

<Restrictions>
Maximum of 50 units (50 channels) per AG-150A/G(B)-50A, 24 units (24 channels) per GB-24A.
However, the number of units that can be connected to a(n) AG-150A/G(B)-50A is up to 50 (24 for the GB-24A) including the number of
contacts used on this device, an indoor unit, LOSSNAY unit, etc.
Up to 6 contacts can be connected to the DIDO controller (1 M-NET address per contact). One contact connected to this device is
calculated as the equivalent of one indoor unit connected to AG-150A/G(B)-50A/GB-24A.
For example, 5 contacts connected to the DIDO controller are calculated as the equivalent of 5 indoor units connected to
AG-150A/G(B)-50A.

NOTE

CNTR-66

For the shield ground of the M-NET centralized control line, use single-point grounding at the power unit for
the transmission line.
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor
unit without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit.
Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each
outdoor unit system.
If the M-NET transmission line of this device is connected to the M-NET indoor control line and the outdoor
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the DIDO
controller cannot be controlled from the system controller.
Controlling the system remote controller, ON/OFF remote controller, and schedule timer is only possible with
channel 1 of a standard terminal block.
DIDO controller can only be monitored or performed from AG-150A, AG-150A/G(B)-50A/GB-24A Web
browser, and TG-2000A. Operation cannot be monitored or performed from the G-50A LCD.
When AG-150A/G(B)-50A/GB-24A is connected, monitoring control can only be performed from AG-150A,
AG-150A/G(B)-50A/GB-24A Web or TG-2000A. Monitoring control cannot be performed from the system
remote controller (ON/OFF remote controller or schedule timer).

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-16-1. Specifications
3-16-1-2. Parts Purchased Separately
Prepare the following parts to install this device.
Required Part

Specification

Unit fixing screws

M4 screw

Power supply for this


device

Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with
grounding terminal
Ripple noise: Lower than 200 mVp-p
Compatible specification
Authorized or CE marked products
Subject to regulations: - IEC60950 (or EN60950)
- CISPR22/24 (or EN55022/24)
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)
When using transistor output (including extension output) for the 24 VDC output of this device, increase
the capacity to match the number used.
1 set used: 0.3 ADC (Minimum) 2 sets used: 0.4 ADC (Minimum) 3 sets used: 0.5 ADC (Minimum)
4 sets used: 0.6 ADC (Minimum) 5 sets used: 0.7 ADC (Minimum) 6 sets used: 0.8 ADC (Minimum)
* The increase of the power supply capacity is 0.1 ADC for every set.

Power line

Use a sheathed vinyl cord or cable. At least 0.75 mm2 (AWG18)

M-NET transmission
line

4 (*M4: ISO metric screw thread)

Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
CPEV 1.2 mm to 1.6 mm CVVS 1.25 mm2 to 2 mm2 (AWG 16)
* CPEV: PE insulated PVC jacketed shielded communication cable
* CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene PVC: Polyvinyl choloride

Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.

Signal lines

Use electric wire of an appropriate size for the terminal block of this device.
Electric wire size (1) Solid wire: 0.65 mm (AWG21) - 1.2 mm (AWG16)
(2) Stranded wire: 0.75 mm2 (AWG18) - 1.25 mm2 (AWG16)
Single strand: At least 0.18 mm
To use an expansion input/output, use a separa tely purchased external input/output adapter.

[Parts to be Purchased Separately]

Power supply unit

External I/O adapter

Model

Application

Remark

PAC-SC50KUA

Power supply to the M-NET transmission line

This is not required when power is to be


supplied from an outdoor unit.

PAC-SC51KUA

Power supply to the M-NET transmission line

This is not required when power is to be


supplied from an outdoor unit.

PAC-YG10HA

Connection adapter for using an expansion


input/output

This is required when an expansion input/


output is used.

[Commercially available parts]


Name

Application

Remark

External 24 VDC
power source

Supplies power when to use the DIDO controller or


transistor output.

Relay device

Requires commercially available relay device


depending on the electric specifications with an
external device.

Refer to "Power supply for this device" in "Required


Part" above for the power supply capacity.

CONTROLLER (Feb. 2009)

CNTR-67

CONTROLLER

Name

3. System Controller

DATA U4

3-16-3. Interlock control


The DIDO controller (PAC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the
M-NET devices such as indoor units and also enables signal output to the contacts on the DIDO controller.
Interlock control covers the units connected to the DIDO controller with M-NET system. AG-150A/G(B)-50A/GB-24A must be connected
to use the function. Ask your dealer for interlock control setting. The setting requires special tool support.

CAUTION

Before using the interlock control, you must agree to the following.
1.This feature must not be used for disaster prevention or security purpose.
(Not designed to be used in situations that are life-threatening)
2.No functions must be added that allow the malfunctioning unit to run by defeating the safety features, such as
an external ON/OFF switch or a short-circuit.
3.Those settings for the function that are not supported by the interlocked units must not be made. All the
settings must be made within the specified range.
(Failure to observe these precautions may result in malfunctions and failures.)
4.Perform a test run for interlock control, and confirm the correct settings and normal operation.
5.The system must be configured in the way that integrates the operation of the interlocked fire and emergency
control systems.

Item
Number of events
Determinant condition for
interlock control
Interlock control contents
(to be output)

Other

Content
24 events
At input contact change
1 action for 1 condition
ON/OFF operation of indoor units
Operation mode change of indoor units
Temperature setting of indoor units
Contact output to DIDO controller (*1)
Interlock control prohibition function is
enabled at emergency stop from AG-150A/
G(B)-50A/GB-24A

Remarks
1 event interlock with 1 unit
Operation input ON/OFF
Error input Error/Normal
Interlock control covers the units connected to
DIDO controllers with M-NET system.
(*1) DIDO controller itself or other DIDO controllers
in the same M-NET system.

Indoor unit
Operation ON/OFF

CENTRALIZED CONTROLLER AG-150A

CONTROLLER

AG-150A

Outdoor unit

Interlock with M-NET devices


DIDO Controller
Interlock with contact output
Card key
ON/OFF

Interlock control of DIDO controller (example)

CNTR-68

CONTROLLER (Feb. 2009)

Lights
ON/OFF

3. System Controller

DATA U4

3-17. AI controller [PAC-YG63MCA]


The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints.
Historical measurement data can be displayed via only the AG-150A, AG-150/G(B)-50A/GB-24A Web browser and TG-2000A.
Temperature and humidity cannot be displayed on the G-50A LCD.
Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.
The AI controller also features a function that interlocks M-NET devices for indoor units, etc.

26

(11/32)

External Dimensions

46 (113/16)

200 (77/8)
150 (529/32)

45 (125/32)
9 (3/8)

4.5

(3/16)
Al controller

PAC-YG63MCA
[ OUTPUT ] Non-voltage Contact Output
Ch1
Ch2
Alarm
Alarm

N623

Al controller
PAC-YG63MCA

MODEL

SERVICE REF. PAC-YG60MCA-J

INPUT VOLTAGE

This device complies with Part15 of the FCC Rules.Operation is


subject to the following two conditions: (1)this device may not cause
harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation.

15

(19/32)

26 (11/32)

Ch2

JAPAN

[ 24 VDC Power Supply]

4 to 20 mA / 1 to 5 V / 0 to 10 V

83.5 (35/16)

27 (13/32)

Unit: mm (in)

Usage Restrictions
Mitsubishi Electric does not take financial responsibility for damages caused by issues beyond our control or
special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to
other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or
electrical power failure at the end-user site.
Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not
limited to, device testing, startup, readjustment and replacement.
Do not use this device in disaster prevention security or "critical to life" applications.

CONTROLLER (Feb. 2009)

CNTR-69

CONTROLLER

CAUTION

Ch1

4 to 20 mA / 1 to 5 V / 0 to 10 V

IN

26

Pt100

0.6 kg / 13/ 8 lb

SERIAL No.
MADE

(11/32)

[ INPUT ]

WEIGHT

DC24V;0.2A

110 (411/32)
120 (43/4)

[ Output LEDs ]
Ch2
Ch1
Alarm
Alarm

3. System Controller

DATA U4

3-17-1. Specifications
3-17-1-1. Device Specifications
Item
Power
Supply

Description
24 VDC 10%: 5 W
M-NET communication
Ch

17 to 30 VDC (*1)

Sensor

Ch2
Output

(*2)

Interlock
Function
Environment
Conditions

CONTROLLER

Dimensions
Weight
Time Backup
During Power
Failure
Installation
Environment

Analog

Ch1

Analog

Interface

Input

Pt100
(3-wire system)
4 to 20 mADC
1 to 5 VDC
0 to 10 VDC
4 to 20 mADC
1 to 5 VDC
0 to 10 VDC

Upper/lower limit
alarm interlock output
(non-voltage contact)

Measurement
target

Measurement
range

Temperature

-30 to 60
[-22 to 140

Temperature/
humidity

(Set by system
controller)

Temperature/
humidity

(Set by system
controller)

Measurement error
0.3%FS

(0.18 )
(*3)
[at 25 (77 )]
0.5%FS 0.1 (0.18 )
(*3)
0.5%FS 0.1%RH
[at 25 (77 )]
0.5%FS

0.1

0.1

(0.18 )
(*3)
0.5%FS 0.1%RH
[at 25 (77 )]

Applied load
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be connected.

Screw terminal
block (M3) (*5)
Screw terminal
block (M3) (*5)
External
connection method
Screwless terminal
block (3 poles)
Screwless terminal
block (2 poles)
Screwless terminal
block (2 poles)
Screw terminal
block (M3.5) (*5)

Interlock M-NET devices according to measurement data values. (*4)


Operating temperature range
0 to 40 [32 to 104 ]
Storage temperature range
-20 to 60 [-4 to 140 ]
Humidity
30 to 90%RH (no condensation)
200 (W) 120 (H) 45 (D) mm / 77/8 (W) 43/4 (H) 125/32 (D) in
0.6 kg / 13/8 lb
Temperature

In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Inside a control panel (indoors)
* Use this product in a hotel, a business office environment or similar environment.

*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption
factor of the MNET circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).
*2: Configure the dip switch settings for the analog input method to use.
*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring.
a%FS (full scale) = a% ([measurement range's upper limit value] - [lower limit value])
*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the
Maintenance Tool.
*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter
(mm).

CNTR-70

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-17-1. Specifications
3-17-1-1. Device Specifications
Centralized control line
Power supply unit
PAC-SC51KUA

M-NET

LAN

M-NET
TB7

CENTRALIZED CONTROLLER AG-150A

AG-150A or
or G(B)-50A *1

Indoor control line

TB3

AI controller
CITY MULTI

24 VDC Power
Supply

(3) (4)

AI controller
AG-150A/
G(B)-50A Web
or TG-2000A *2

(1) (2)

24 VDC Power
Supply

Temperature sensor,
humidity sensor,
etc.

(3) (4)
(1) (2)

Temperature sensor,
humidity sensor,
etc.

Upper/lower limit
alarm interlock
devices, etc.

(1) Channel 1 temperature or humidity sensor input


(2) Channel 2 temperature or humidity sensor input
(3) Channel 1 upper/lower limit alarm output
(4) Channel 2 upper/lower limit alarm output

Upper/lower limit
alarm interlock
devices, etc.

* This figure omits the power supply line and only shows the transmission line.
*1: The AI controller can be connected to G(B)-50A with Ver.3.20 or later.
*2: The AI controller can be connected to TG-2000A with Ver.5.10 or later.
<Restrictions>
Maximum of 50 units per AG-150A/ G(B)-50A, 24 units per GB-24A.
However, the number of units that can be connected to an AG-150A/G(B)-50A is up to 50 (to 24 with the GB-24A) including this device,
an indoor unit, LOSSNAY unit, etc.

NOTE

CONTROLLER (Feb. 2009)

CNTR-71

CONTROLLER

For the shield ground of the M-NET centralized control line, use single-point grounding at the po wer unit for
the transmission line.
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor
unit without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit.
Furthermore, when connecting the M-NET transmission line of this device to the M-NET indoor control line,
use grounding at the TB3 for each outdoor unit system.
If the M-NET transmission line of this device is connected to an M-NET indoor control line and the outdoor
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the AI
controller cannot be set and monitored from the system controller.
The sensor connected to the AI controller can only be monitored from AG-150A, AG-150/G(B)-50A/GB-24A
Web browser and TG-2000A. The sensor cannot be monitored from the G-50A LCD.

3. System Controller

DATA U4

3-17-1. Specifications
3-17-1-2. Parts Purchased Separately
Prepare the following parts to install this device.
Required Part

Specification

Unit fixing screws

M4 screw

Power supply for this


device

Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with
grounding terminal
Ripple noise: Lower than 200 mVp-p
Compatible specification
Authorized or CE marked products.
Subject to regulations: - IEC60950 (or EN60950)
- CISPR22/24 (or EN55022/24)
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)

Power supply for


sensors

A separate power supply for sensors may be required.


In the case of 24 VDC voltage, the capacity of the power supply for this unit can be increased so that the
power supply can be shared.

Power line

Use a sheathed vinyl cord or cable.


At least 0.75 mm2 (AWG18)

M-NET transmission
line

4 (* M4: ISO metric screw thread)

Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
CPEV 1.2 mm to 1.6 mm CVVS 1.25 mm to 2 mm (AWG 16)
* CPEV: PE insulated PVC jacketed shielded communication cable
* CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene PVC: Polyvinyl chloride

Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.

Signal lines
(Sensor input lines)

Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device. Refer
to the usage and cautionary items of the sensor when performing settings. However, use a line with shielded
line.
Electric wire size (1)Solid wire: 0.65 mm (AWG21) - 1.2 mm (AWG16)
(2)Stranded wire: 0.75 mm (AWG18) - 1.25 mm (AWG16)
Single strand: At least 0.18 mm

CONTROLLER

[Parts to be Purchased Separately]


Name
Power supply unit

Model

Application

Remark

This is not required when power is to be


supplied from an outdoor unit.
This is not required when power is to be
PAC-SC51KUA Power supply to the M-NET transmission line
supplied from an outdoor unit.

PAC-SC50KUA

Power supply to the M-NET transmission line

[Commercially available parts]


Part

Use

Remark

External 24 VDC
power source

Supplies power to the AI controller.

Refer to "Power supply for this device" and "Power


supply for sensors" in "Required Part" above for the
capacity of the power supply.

Sensor

Measures temperature and humidity.

Temperature sensor (PAC-SE40TSA) cannot be


connected.

CNTR-72

CONTROLLER (Feb. 2009)

3. System Controller

DATA U4

3-17-2. Interlock control


AI controller (PAC-YG63MCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices
such as indoor units.
Interlock control covers the units connected to the AI controller with M-NET system. AG-150A/G(B)-50A /GB-24A must be connected to
use the function. Ask your dealer for interlock control setting. The setting requires special tool support.

CAUTION

Before using the interlock control, you must agree to the following.
1.This feature must not be used for disaster prevention or security purpose.
(Not designed to be used in situations that are life-threatening)
2.No functions must be added that allow the malfunctioning unit to run by defeating the safety features, such as
an external ON/OFF switch or a short-circuit.
3.Those settings for the function that are not supported by the interlocked units must not be made. All the
settings must be made within the specified range.
(Failure to observe these precautions may result in malfunctions and failures.)
4.Perform a test run for interlock control, and confirm the correct settings and normal operation.
5.The system must be configured in the way that integrates the operation of the interlocked fire and emergency
control systems.

Item
Number of events
Determinant condition for
interlock control

Content
Remarks
24 events
1 event interlock with 1 unit
Measurement value
Exceeding measurement value in setting range
Measurement interval is 1 to 7200 seconds. Exceeding upper/lower limit alarm detection
value and cancellation value

Interlock control contents


(to be output)

1 action for 1 condition


ON/OFF operation of indoor units
Operation mode change of indoor units
Temperature setting of indoor units
Contact output to DIDO controller
Interlock control prohibition function is
enabled at emergency stop from AG-150A/
G(B)-50A/GB-24A

Other

Interlock control covers the units connected to AI


controllers with M-NET system.

CONTROLLER

Indoor unit
Operation ON/OFF

CENTRALIZED CONTROLLER AG-150A

AG-150A
Outdoor unit

AI Controller

Interlock with M-NET devices


Cooling operation when the temperature is 28 (83 F) or above
Fun operation when the temperature is lower than 25 (77 F)

Temperature sensor
Interlock control of AI controller (example)

CONTROLLER (Feb. 2009)

CNTR-73

3. System Controller

DATA U4

3-18. Transmission booster [PAC-SF46EPA]


The Outdoor unit supplies transmission power 30VDC for the indoor-outdoor transmission line at its connector TB3 and TB7.
The power is consumed by the Indoor unit, ME remote controller, Timers and System controllers.When the total quantity of
Indoor units, and ME remote controller, Timers and System controllers is over 40, or when transmission power supply is not
enough, the transmission booster PAC-SF46EPA should be designed into the air-conditioner system to ensure the system
communication.Indoor unit sized P72, 96 is counted as 2 units.
3-18-1. Designing PAC-SF46EPA into an air-conditioner system.
Taking the power consumption of Indoor unit sized P06-P54 as 1, the equivalent power consumption or supply of others are
listed at Table 3-18-1 and Table 3-18-2.
Table 3-18-1 The equivalent power consumption by Indoor units, LOSSNAY, controllers
Indoor

Indoor unit

BC controller

Sized P06-P54

Sized P72-P96

CMB

MA RC. LOSSNAY

ME Remote Contr.

PAR-21MAA
PAC-YT51CRB
PAR-FA32MA
LGH-RX-E
PZ-41SLB
0

Timers, System Contr.

PAR-F27MEA-US PAC-SF44SRA
PZ-52SF
PAC-YT34STA
G-50A
AG-150A
1/4

1/2

ON/OFF Contr.

GB-50A

PAC-YT40ANRA
GB-24A

*RC : Remote Controller

Table 3-18-2 The equivalent power supply of Trans. Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster
PAC-SF46EPA
25

Power supply unit


PAC-SC50KUA
6

PAC-SC51KUA
5

Outdoor unit

Outdoor unit

Connector TB3 and TB7 total *


32

Connector TB7 only


6

*If PAC-SC50KUA or PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.

Transmission booster PAC-SF46EPA has equivalent transmission power 25.


With the equivalent power consumption values in Table 3-18-1 and Table 3-18-2, PAC-SF46EPA can be designed into the airconditioner system to ensure proper system communication according to 3-18-1-A, B, C.

3-18-1-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total power consumption
reaches 32, a PAC-SF46EPA should be set.Yet, if a PAC-SC50KUA or PAC-SC51KUA is used to supply power at TB7
side, count from TB3 side only.
3-18-1-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total power consumption reaches 6, a PAC-SF46EPA should be set.

External dimension
Unit:mm [in.]
360[14-3/16]
240[9-15/32]

CNTR-74

CONTROLLER (Feb. 2009)

340[13-13/32]

300[11-13/16]

165[6-1/2]

UP

160[6-5/16]

CONTROLLER

3-18-1-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System
controllers.If the total quantity reaches 40, a PAC-SF46EPA should be set.In this case, Indoor unit sized P72, 96
is counted as 2 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.

4. System Component

DATA U4

In a multi air conditioner system that is a free plan direct-expansion type, a connector for inputting and outputting signals
to/from the outside is fitted as standard on the control board of the indoor and outdoor units. Use this when you want
each unit to input/output signals individually. (Note: When there are many control units it is recommended that you use
MELANS. This would enable you to save on labor.) In order to have an input output signal from each connector, you must
have a dedicated adapter (sold separately) and a relay circuit (on-site arrangements).
Note : See next page for actual examples of use.
Types of control that uses connectors for the outdoor unit / water-source unit input output signal
(connection for each type of option).
Category

Application

Connector

Function

Y, WY

R2, WR2

CN3D

CN3D

Night mode

CN3D

CN3D

Autochangeover

CN3N

Method of disabling cool and heat operation (thermo Comp ON/OFF


off) by input from the outside to the outdoor unit.
The low noise operation of the indoor unit can be
commenced by the external input to the outdoor
unit (water-source unit).
(The night mode can be adapted only under
Input

less f

or heating)

You can switch the operation mode between cooling


and heating by input from the outside to the outdoor
unit.
Forces the heat source unit to stop operation by
receiving contact signals from the pump interlock
circuit
Forces outdoor unit to perform a fan operation by
receiving signals from the snow sensor. (note 10)

Output

TB8
(W-Series)

TB8
(W-Series)

CN3S
(Y-Series)

CN3S
(R2-Series)

CN51

CN51

TB8

TB8

Compressor is
run state
Error state or
frost prevention
output (note 8)
Operation ON
signal (note 9)

Types of control that uses connectors for the indoor unit input output signal (connection for each type of option)
Category

Input
(Note 2,3)

Application

Function

Method of ON/OFF control by turning on and off switches or contacts from an outside to each indoor unit group.
Can be used as a timer adapter (Note 1)
Can be used as a "forget to switch off prevention" or "forced stop".
Method of ON/OFF control by inverting start/stop using external
pulse (a-contact) for each indoor unit group.

Output

Method of sending signals to outside for each indoor unit group.


It can be used as a device to display operation states.
It can be used as an interlocked control with the external equipment.

Distant/local
switching (note 1)

Connector

CN32

ON/OFF (level)
ON/OFF (pulse)
Operation state
Error state
Operation mode
(heat) state
Operation mode
(cool, dry) state
Thermo ON
(fan) state

CONTROLLER (Feb. 2009)

CN51
CN51

CN52

CNTR-75

CONTROLLER

Method of receiving a signal from the outdoor unit


(water-source unit) to the outside.
Can be used as a device that displays the operation state.
Can be used as an interlocked control with external equipment.

Pump Interlock
signal input
(level)
Snow sensor
signal input

4. System Component

DATA U4

CONTROLLER

Note 1: Connect the signal input only to the principal unit in a group.
(However, the demand input is required to enter into indoor units individually.)
Note 2: When using star t/stop input at group operation, Local remote controller is necessary.
(MA remote controller or M-NET remote controller)
Note 3: When setting to Remote, operation can not be performed from Local remote controller.
The remote controller displa
Y CONTR
Note 4: When using start/stop input at group oper
utomatic address star
ormed.
Note 5: When CN51 or CN52 is commonly used as an output signal, be sure to use the remote display kit.
Note 6: The remote display kit can be used for the input signal of CN51 and CN52.
Note 7: Connect to the pr
ation mode (Heating/CoolingDry) of signal output.
mostat ON
(or f
Note 8: The error state of the heat source unit can be output when Dip SW3-3 is OFF.
When Dip SW3-3 is ON, the signal is output only when the heat source unit is stopped and the water
temperature (TH6) is 5C[41F] or lower.
Note 9: When Dip SW2-7 is OFF, the operation ON signal is output only when the compressor is in operation.
When Dip SW2-7 is ON, the signal is output when cooling or heating operation signal from the controller is
received. (The signal is kept active even if the compressor stops due to thermo OFF.)
Note 10: When multiple outdoor units exist in one refrigerant circuit, settings on every outdoor unit (signal input)
are required.

CNTR-76

CONTROLLER (Feb. 2009)

4. System Component

DATA U4

It is possible to have ON/OFF control by turning the indoor unit power on and off. You can select functions by setting the DipSW1-9 and 1-10 on the indoor unit.
Types of ON/OFF control (indoor unit settings)
It is possible to have ON/OFF control for each indoor unit (or group) by dip switches 9 and 10 (SW1-9, SW1-10)
of the indoor unit.
Setting SW 2 (note 1)

Operation when indoor unit recovers

Function

10

All auto
restart

All indoor units will always restart regardless of the state that was before the power was turned off (POWER OFF) (after 5 minutes).

OFF

ON

Auto
recovery

Indoor units which are operated before the power was turned off
(POWER OFF) will restart (after 5 minutes).

ON

OFF

All OFF

Operation stays stopped regardless of the state that was before the
power was turned off.

OFF

OFF

Note 1. The dip switch setting for all units in the indoor unit group is required.
Note 2. Do not cut-off the power to the outdoor unit. If you do, it will disconnect the power to the crankcase heater of the outdoor unit and that could cause damage to the compressor.
Note 3. This cannot be applied to the power ON/OFF of the drain pump and humidifier equipment.
Description of when using distant/local switching (CN32)
SW1
Local switching

SW2
ON/OFF

OFF

OFF

Local / Permit

ON

OFF

Distant / Stop

ON

ON

Distant / Operate

System example

State

Remote controller display/operation


The operation permit
It displays "CENTRALLY CONTROLLED", while
the state is distant.
It prohibits ON/OFF operation of remote
controller.

Outdoor unit

CONTROLLER

Outdoor unit
power supply
Indoor unit
Indoor unit
power supply

Local
remote
controller

Switch

When the power to the outdoor unit is cut-off for a long time, the crankcase heater for the compressor also stops. If the
compressor is started soon after the power is restored, there is a chance that a fault will occur in the compressor.
When using the above function, make sure the power to the outdoor units will not be cut-off.
Limitations to combining system controls
Control combining
Pulse ON/OFF Power ON/OFF
distant/local

Description
1

Control combining distant/local

CN32

Pulse ON/OFF

CN51

HA ON/OFF (JEMA)

CN51

Power ON/OFF

Automatic recover

Automatic recover
1

1: Pulse ON/OFF, Power ON/OFF and automatic recover can only be used when the distant/local setting
(CN32) is set to local. Therefore, always avoid this function when combining control.

CONTROLLER (Feb. 2009)

CNTR-77

4. System Component

DATA U4

4-1. Y-, R2-, S-Series


1) SW4-4: OFF (Compressor ON/OFF, Low sound mode)
CN3D 1-3P
Open
Short-circuit

2-level of on-Demand *1
100%(No Demand)
0%

CN3D 1-2P
Low sound mode *2
Open
OFF
Short-circuit
ON
*1 When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON (4 levels or 8 levels or 12 levels of on- DEMAND), this function cannot be used.
*2 This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on the outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND) (*3)
CN3D 1-3P
Open
Short-circuit

CN3D 1-2P
Short-circuit
75%
50%

Open
100% (No DEMAND)
0%

Note the following steps to be taken when using STEP DEMAND.


Example: When switching from 100% to 50%

If the demand settings are switched in the wrong order listed as the wrong
example above, the unit may go into thermo OFF mode.
The percentage of the DEMAND listed in the table above is an
<WRONG>
100%
0%
50%
NO
Steps in DEMAND
approximate value based on the compressor volume and does not
level setting
<CORRECT>
100%
75%
50% necessarily correspond with the capacity.
OK
This function and the Low sound mode function cannot be used together.
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND) (*3,*4)
8 levels of on-DEMAND
1-2P
Open

No.1 CN3D

Short-circuit

1-2P
1-3P
Open
Short-circuit
Open
Short-circuit

Open

No.2 CN3D

Open
Short-circuit
100% (No DEMAND) 50%
50%
0%
88%
38%
75%
25%

Open
88%
38%
75%
63%

Short-circuit
Short-circuit
75%
25%
63%
50%

4) When SW4-4 on the all outdoor units in one refrigerant circuit system is set to ON (12 levels of on-DEMAND) (*4)
12 levels of No.2 CN3D
on-DEMAND
No.3 CN3D
No.1 CN3D 1-2P
Open

CONTROLLER

Short-circuit

1-2P
1-3P
1-2P
1-3P
Open
Short-circuit
Open
Short-circuit

Open
Open

Open
100%
67%
92%
84%

Open
Short-circuit
67%
34%
59%
50%

Short-circuit
Open
Short-circuit
92%
84%
59%
50%
84%
75%
75%
67%

Open
67%
34%
59%
50%

Short-circuit
Open
Short-circuit
Short-circuit
Open
Short-circuit
34%
59%
50%
0%
25%
17%
25%
50%
42%
17%
42%
34%

1-2P
Short-circuit
1-3P
Open
Short-circuit
1-2P
Open
Short-circuit
Open
Short-circuit
1-3P
Open
Short-circuit
Open
Short-circuit
Open
Short-circuit
Open
Short-circuit
Open
92%
59%
84%
75%
84%
50%
75%
67%
Short-circuit
59%
25%
50%
42%
50%
17%
42%
34%
Open
Short-circuit
84%
50%
75%
67%
75%
42%
67%
59%
Short-circuit
75%
42%
67%
59%
67%
34%
59%
50%
*3 Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*4 CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.

12 levels of No.2 CN3D


on-DEMAND
No.3 CN3D
No.1 CN3D 1-2P
Open

CNTR-78

CONTROLLER (Feb. 2009)

4. System Component

DATA U4

4-2. Outdoor unit input/output connector (Y-, R2-, S-Series)


1.Wiring should be covered by insulation tube with supplementary insulation.
2.Use relays or switches with IEC or equivalent standard.
3.The electric strength between accessible parts and control circuit should have 2750V or more.

Caution:

4-2-1. Output

State (CN51)

Lamp power source

Distant control
board
L1

Relay circuit
X
Y

L2

Adapter *1

Outdoor unit
control board

5
4
3

Preparations
in the field

CN51

L1 : Outdoor unit error display lamp


L2 : Compressor operation lamp (compressor running state)
X, Y : Relay (coil =<0.9W : 12VDC)
*1. Optional part : PAC-725AD or field supply.

Maximum cable
length is 10m

4-2-2. Input
Y-, R2-Series
(1) Step demand and Silent mode
(Night mode) (CN3D)
For details, refer to "Table 4-1".

Outdoor unit
control board

Adapter *2

Relay circuit
X

1
2

CN3D

(2) Silent mode (Night mode)


(CN3D + DipSW4-4 OFF)
Relay circuit

Outdoor unit
Adapter *2 control board
1
2

CN3D

3
Preparations
in the field

Preparations
in the field

(3) System changeover (CN3N)


Relay circuit

Adapter *2

Outdoor unit
control board
CN3N

1
2

Maximum cable
length is 10m
X : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.
Silent mode
(Night mode)

-NoteThe sound pressure level cannot be reduced, when neither


the fan frequency nor the compressor frequency are maximum.

(4) Snow sensor (CN3S)


Relay circuit
X

: The sound pressure level is reduced by controlling


the maximum fan frequency and compressor frequency.

Adapter *2
1
2

Outdoor unit
control board
CN3S

3
Preparations
in the field

Maximum cable
length is 10m

X : Cooling / Heating
Y : Validity / Invalidity of X
X,Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.

X
OFF

Preparations
in the field
Maximum cable
length is 10m
X : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.
Snow sensor : The outdoor fan runs when X is closed
in stop mode or thermostat mode.

ON

OFF

Normal

ON

Cooling Heating

CONTROLLER (Feb. 2009)

CNTR-79

CONTROLLER

Maximum cable
length is 10m
X : Silent mode or demand
Y : Demand
X,Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.

4. System Component

DATA U4

S-Series
(1) Step demand and Silent mode (Night mode) (CN3D)
Relay circuit

Adapter *2

1
2

(2) Silent mode (Night mode) (CN3D + DipSW8-1 OFF)

Outdoor unit
control board
CN3D

X
OFF

ON

OFF

100%

75%

ON

0%

50%

Compressor
ON/OFF

Low noise mode

OPEN

ON

OPEN

OFF

SHORT

OFF

SHORT

ON

(3) System changeover (CN3N)


Relay circuit

Adapter *2

CONTROLLER

Outdoor unit
control board
CN3N

1
2

Preparations
in the field

Maximum cable
length is 10m

SW1 : Cooling / Heating


SW2 : Validity / Invalidity of X
X, Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.

X
OFF

CNTR-80

CN3D

OFF
ON

ON

Normal
Cooling

Maximum cable
length is 10m
X : Relay

Contact rating voltage >= 15VDC


Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
*2. Optional part : PAC-715AD or field supply.
Silent mode : The sound pressure level is reduced by controlling
(Night mode) the maximum fan frequency and compressor frequency.
-NoteThe sound pressure level cannot be reduced, when neither the
fan frequency nor the compressor frequency are maximum.

*They are rough values.


DipSW8-1 OFF (Compressor ON/OFF and Silent mode [Night mode)

1
2

Outdoor unit
control board

Preparations
in the field

Maximum cable
length is 10m
X,Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
*2. Optional part : PAC715AD or field supply.
DipSW8-1 ON (Step demand only)

Adapter *2

Preparations
in the field

Relay circuit

Heating

CONTROLLER (Feb. 2009)

4. System Component

DATA U4

4-3. Indoor unit -E type input/output connector (Y-, R2-, S-Series)


1.Wiring should be covered by insulation tube with supplementary insulation.
2.Use relays or switches with IEC or equivalent standard.
3.The electric strength between accessible parts and control circuit should have 2750V or more.

Caution:

ON/OFF (Pulse) input specification


Description

Item
Input signal

Pulse sign (a connect)

Standard of pulse
200msec or more

Input

Output
CN51

CN52

Distant control board

Relay circuit

Adapter
1

SW

Power supply
of relay

Indoor unit
control board
CN51

L2

Relay circuit

Power supply
of relay

L3

4
5

Maximum cable
length is 10m[32ft.]
SW : Distant ON/OFF switch
L1 : Status lamp
Every time the SW is pushed
L2 : Error lamp
(the pulse is inputted), it
X : Relay (a point of contact, fixed DC1mA)
reacts against ON/OFF.
Y, Z : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC

Adapter
1

L1
L2

3
L1

Distant control board

Y
Z

Indoor unit
control board
CN52

2
3
4

Maximum cable
length is 10m[32ft.]
L1 : Status lamp
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
L2 : Cooling/Dry status lamp
L3 : Heating status lamp
X, Y, Z : Relay (Coil with fixed 12VDC, a power consumption of 0.9W or less)

CN32
Distant control board

Adapter

Indoor unit
control board

SW1

SW2

CN32

CONTROLLER

Power supply
of relay

Relay circuit

Maximum cable
length is 10m[32ft.]
SW2 is available when SW1
is ON.

SW1 : Distant/Local switching


SW2 : ON/OFF switch
X, Y : Relay Contact rating voltage >= 15VDC
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC

CN52
Distant control board

Relay circuit

Adapter

Indoor unit
control board

Power supply
of relay

CN52

SW1

Maximum cable
length is 10m[32ft.]
SW1 : Demand switch
X : Relay (coil <=0.9W,12VDC)
SW1

Indoor unit

ON

Forced thermo-OFF

OFF

Normal running

1. Optional part : PAC-725AD or field supply


2. Optional part : PAC-715AD or field supply

CONTROLLER (Feb. 2009)

CNTR-81

DATA U4

CITY MULTI Y-SERIES


System Design
1. Electrical work............................................................................................................................................... YSD-2
1-1. General Cautions........................................................................................................................................... YSD-2
1-2. Power Supply for Indoor Unit and Outdoor Unit............................................................................................. YSD-3
1-3. Power Cable Specifications............................................................................................................................ YSD-7
1-4. Power Supply Examples................................................................................................................................ YSD-8
2. M-NET control................................................................................................................................................. YSD-11
2-1. Transmission Cable Length Limitation.......................................................................................................... YSD-11
2-2. Transmission Cable Specifications............................................................................................................... YSD-12
2-3. System Configuration Restrictions............................................................................................................... YSD-13
2-4. Address Setting............................................................................................................................................ YSD-16
3. Piping Design.................................................................................................................................................... YSD-25
3-1. R410A Piping Material................................................................................................................................. YSD-25
3-2. PUHY-P-T/Y(S)HMUs Piping Design........................................................................................................... YSD-26
4. Installation....................................................................................................................................................... YSD-31
4-1. PUHY-P-T/Y(S)HMUs Installation................................................................................................................ YSD-31
5. Standard and Seacoast Protection (-BS) Treatment....................................................................... YSD-40
5-1. Y-Series........................................................................................................................................................ YSD-40
6. CautionS............................................................................................................................................................. YSD-41
6-1. Refrigerant Properties.................................................................................................................................. YSD-41
6-2. Confirm the Critical Concentration and Perform Countermeasures............................................................. YSD-41

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-1

1. Electrical Work

DATA U4

1-1. General Cautions


Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 100V, 208~230,460V power source to terminal block of transmission cable. If connected,electrical parts will
be burnt out.
Use 2-core shield cable for transmission cable. If transmission cables of different systems are wired with the same
multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.

Indoor unit

Outdoor
unit

OK
2-core shield cable

NO
Multiplecore cable

Remote
controller

BC controller

Outdoor
unit

Indoor unit

Outdoor
unit

Indoor unit

Remote
controller

BC controller Indoor unit

Outdoor
unit

2-core shield cable

Y-SERIES
SYSTEM DESIGN

Remote
controller

YSD-2

Y-SERIES SYSTEM DESIGN (Feb. 2009)

Remote
controller

1. Electrical Work

DATA U4

1-2. Power Supply for Indoor Unit and Outdoor Unit

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-3

1. Electrical Work

PVFY-P12E00A
PVFY-P18E00A
PVFY-P24E00A
PVFY-P30E00A
PVFY-P36E00A

Y-SERIES
SYSTEM DESIGN

PVFY-P48E00A
PVFY-P54E00A

YSD-4

Y-SERIES SYSTEM DESIGN (Feb. 2009)

DATA U4

0.86 / 0.76
1.85 / 1.64
1.85 / 1.64
2.97 / 2.64

0.262 / 0.262

0.69 / 0.61

0.384 / 0.384
0.384 / 0.384
0.342 / 0.342

1.48 / 1.31
1.48 / 1.31

2.41 / 2.14
2.84 / 2.51
3.53 / 3.14

0.236 / 0.236
0.196 / 0.196
0.210 / 0.210

2.38 / 2.11
1.93 / 1.71
2.27 / 2.01
2.83 / 2.51

1. Electrical Work

DATA U4

1-2-2. Electrical characteristics of Outdoor unit at cooling mode


Symbols: MCA : Min. Circuit Amps
SC : Starting Current

PUHY-P-T(S)HMU

RLA : Rated Load Amps


Compressor

Outdoor Units

Fan

Model

Unit Combnation

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P96THMU-A(-BS)

23.8/21.5 35/32

40

6.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P96THMU-A(-BS)

23.8/21.5 35/32

40

6.8

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P96THMU-A(-BS)

23.8/21.5 35/32

40

6.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P288TSHMU-A(-BS) PUHY-P96THMU-A(-BS)

23.8/21.5 35/32

40

6.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P72THMU-A(-BS)

14.0/12.7 23/21

30

5.1

15

0.92

PUHY-P312TSHMU-A(-BS) PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P96THMU-A(-BS)

23.8/21.5 35/32

40

6.8

15

0.92

PUHY-P336TSHMU-A(-BS) PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P360TSHMU-A(-BS) PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P120THMU-A(-BS)

29.0/26.2 41/38

50

8.8

15

0.92

PUHY-P144TSHMU-A(-BS)
PUHY-P168TSHMU-A(-BS)
PUHY-P192TSHMU-A(-BS)
PUHY-P216TSHMU-A(-BS)
PUHY-P240TSHMU-A(-BS)

PUHY-P264TSHMU-A(-BS) PUHY-P72THMU-A(-BS)

Hz

60Hz

Volts

Voltage range

208 / 230V 188 to 253V

RLA(A)

MCA(A) Max. Fuse(A) Output(kW) SC(A) Output(kW)

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-5

1. Electrical Work

DATA U4
Symbols: MCA : Min. Circuit Amps
SC : Starting Current

PUHY-P-Y(S)HMU

RLA : Rated Load Amps


Compressor

Outdoor Units

Fan

Model

Unit Combnation

PUHY-P72YHMU-A(-BS)

6.3

11

15

5.1

0.92

PUHY-P96YHMU-A(-BS)

10.7

16

20

6.8

0.92

PUHY-P120YHMU-A(-BS)

PUHY-P144YSHMU-A(-BS)
PUHY-P168YSHMU-A(-BS)
PUHY-P192YSHMU-A(-BS)
PUHY-P216YSHMU-A(-BS)

Hz

Volts

Voltage range

RLA(A)

MCA(A) Max. Fuse(A) Output(kW) SC(A) Output(kW)

13.1

19

25

8.8

0.92

PUHY-P72YHMU-A(-BS)

6.3

11

15

5.1

0.92

PUHY-P72YHMU-A(-BS)

6.3

11

15

5.1

0.92

PUHY-P72YHMU-A(-BS)

6.3

11

15

5.1

0.92

PUHY-P96YHMU-A(-BS)

10.7

16

20

6.8

0.92

PUHY-P72YHMU-A(-BS)

6.3

11

15

5.1

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

PUHY-P96YHMU-A(-BS)

10.7

16

20

6.8

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

6.3

11

15

5.1

0.92

6.3

11

15

5.1

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

PUHY-P72YHMU-A(-BS)

6.3

11

15

5.1

0.92

PUHY-P288YSHMU-A(-BS) PUHY-P96YHMU-A(-BS)

10.7

16

20

6.8

0.92

13.1

19

25

8.8

0.92

PUHY-P240YSHMU-A(-BS)

PUHY-P72YHMU-A(-BS)
PUHY-P264YSHMU-A(-BS) PUHY-P72YHMU-A(-BS)

60Hz

460V

414 to 506V

PUHY-P120YHMU-A(-BS)
PUHY-P72YHMU-A(-BS)
PUHY-P312YSHMU-A(-BS) PUHY-P120YHMU-A(-BS)

6.3

11

15

5.1

0.92

13.1

19

25

8.8

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

PUHY-P96YHMU-A(-BS)

10.7

16

20

6.8

0.92

PUHY-P336YSHMU-A(-BS) PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

13.1

19

25

8.8

0.92

13.1

19

25

8.8

0.92

PUHY-P120YHMU-A(-BS)

13.1

19

25

8.8

0.92

Y-SERIES
SYSTEM DESIGN

PUHY-P120YHMU-A(-BS)
PUHY-P360YSHMU-A(-BS) PUHY-P120YHMU-A(-BS)

YSD-6

Y-SERIES SYSTEM DESIGN (Feb. 2009)

1. Electrical Work
1-3. Power Cable Specifications

DATA U4

Thickness of wire for main power supply, ON / OFF capacities


3-phase 3-wire, 208/230V,60Hz
PUHY-P-THMU-A

P72
P96
P120

Indoor unit
3-phase 3-wire, 460V,60Hz
PUHY-P-YHMU-A
Indoor unit

P72
P96
P120

Minimum wire thickness (mm2 / AWG)


Main cable
Branch
Ground
5.3/10
5.3/10
13.3/6
13.3/6
13.3/6
13.3/6
2.1/14
2.1/14
2.1/14

Switch (A)
Capacity
Fuse
30
30
40
40
50
50
15
15

Breaker for
wiring (NFB)
30
40
50
15

30A 30mA or 100mA 0.1sec. or less


40A 30mA or 100mA 0.1sec. or less
50A 100mA0.1sec. or less
20A 30mA or 100mA 0.1sec. or less

Minimum wire thickness (mm2 / AWG)


Main cable
Branch
Ground
2.1/14
2.1/14
3.3/12
3.3/12
5.3/10
5.3/10
2.1/14
2.1/14
2.1/14

Switch (A)
Capacity
Fuse
15
15
20
20
25
25
15
15

Breaker for
wiring (NFB)
15
20
25
15

15A 30mA or 100mA 0.1sec. or less


20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less

Breaker for current leakage

Breaker for current leakage

1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum v alue f or metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1 / 8 in] contact separation in each pole shall be provided by the Air conditioner installation.

WARNING
Be sure to use specified wires to connect so that no external force is impar ted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated over current may include some amount of direct current.

CAUTION
A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-7

1. Electrical Work

DATA U4

1-4. Power Supply Examples


The local standards and/or regulations is applicable at a higher priority.

1-4-1. PUHY-P72, 96, 120THMU/YHMU


Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol
means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC50KUA should be used. The transmission cable (above 1.25mm2
[16AWG] shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is
called central control transmission cable. The shield wire of the central control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40.
5 MA R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less than 200m (656 ft.)
in length, while ME R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less
than 10m (32 ft.) in length. But transmission cable to the ME R/C can be extend using a
M-NET cable (>=1.25mm2 [16AWG]) when the length is counted in the M-Net length.
Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 (18-16AWG) in
thickness.
6 MA remote controller and ME remote controller should not be grouped together.
7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.

<In the case a system controller is connected.>


Note12

Central control
transmission cable
>=1.25mm2 (16AWG)
Shield cable
(CVVS, CPEVS
MVVS)

SC

Connector
CN41 CN40 OU
Note4

Note4
To other OU

Breakers for
current leakage Switch

Power supply
3-phase 3-wire
208-230V 60Hz(THMU)
460V 60Hz(YHMU)
Note10,13

TB1
TB3 TB7
(L1,L2,L3) (M1,M2) (M1,M2)
TB7
(S)

Note3

To *1 or *2
*1
(Using MA remote controller)
Connecting TB5 terminal.

Power supply
1-phase
208-230V 60Hz
Note10

Pull box

Breakers for
current leakage Switch

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

* Power supply
specifications vary with
the model of connected
indoor units

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for

Switch
Power supply current leakage
1-phase
208-230V 60Hz
TB1
(R,S) E
TB2 TB3

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)
MA R/C cable
0.3-1.25mm2 (22-16AWG)
(0.75~1.25mm2 [18-16AWG])
(Shield) S S (Shield)
<=200m (656 ft.)
Note 5, Note11
Transmission
booster
Note8
Note9
MA R/C

Note6
Note7
MA R/C

MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

Breakers for
current leakage Switch

Pull box

Y-SERIES
SYSTEM DESIGN

Power supply
1-phase
208-230V 60Hz
Note10

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

* Power supply
specifications vary with
the model of connected
indoor units

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable
ME R/C

Symbol

Model

BC
OCP
NFB
OU
IU
SC

Breaker capacity
Over-current protector
Non-fuse breaker
Outdoor unit
Indoor unit
System controller

MA R/C

MA remote controller

ME R/C

ME remote controller

YSD-8

PUHY-P72THMU
PUHY-P96THMU
PUHY-P120THMU
PUHY-P72YHMU
PUHY-P96YHMU
PUHY-P120YHMU

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for
current leakage Switch
Power supply
1-phase
208-230V 60Hz

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)
ME R/C cable
0.3~1.25mm2 (22-16AWG)
(Shield) S S (Shield)
(0.75~1.25mm2 [18-16AWG])
<=10m (32 ft.)
Transmission
Note 5, Note11
booster
Note8
Note9
TB1
(R,S) E
TB2 TB3

Note6
Note7
ME R/C

Breakers for current leakage


*1, *2

30A 30mA or 100mA 0.1sec. or less


40A 30mA or 100mA 0.1sec. or less
50A 100mA 0.1sec. or less
15A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less

ME R/C

Switch

Switch

Minimum Wire thickness

BC
<A>

OCP*3
<A>

(NFB)
<A>

Power wire
<mm2/AWG>

G wire
<mm2/AWG>

30
40
50
15
20
25

30
40
50
15
20
25

30
40
50
15
20
25

5.3/10
5.3/10
13.3/6
2.1/14
3.3/12
5.3/10

5.3/10
5.3/10
13.3/6
2.1/14
3.3/12
5.3/10

*1 The breakers for current leakage should support Inverter circuit.


*2 Breakers for current leakage should combine using of switch.
*3 It shows data for B-type fuse of the breaker for current leakage.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

1. Electrical Work

DATA U4

The local standards and/or regulations is applicable at a higher priority.

1-4-2. PUHY-P144, 168, 192, 216, 240TSHMU/YSHMU


<In the case a system controller is connected.>
Note12

Central control
transmission cable
>=1.25mm2 (16AWG)
Shield cable
(CVVS, CPEVS
MVVS)

SC

Connector
CN41 CN40 OU
Note4

Note4

OU

To other OU
Breakers for
current leakage Switch
Power supply
3-phase 3-wire
208-230 60Hz(TSHMU)
460V 60Hz(YSHMU)
Note10,13

TB1
(L1,L2,L3)

TB1
TB3 TB7
(L1,L2,L3) (M1,M2) (M1,M2)

TB3
TB7
(M1,M2) (M1,M2)

Breakers for
current leakage Switch

TB7
(S)

Power supply
3-phase 3-wire
208-230 60Hz(TSHMU)
460V 60Hz(YSHMU)
Note10,13

Note3

Note3

To *1 or *2
*1
(Using MA remote controller)
Connecting TB5 terminal.

Power supply
1-phase
208-230 60Hz
Note10

Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol
means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC50KUA should be used. The transmission cable (above 1.25mm2
[16AWG] shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is
called central control transmission cable. The shield wire of the central control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40.
5 MA R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less than 200m (656 ft.)
in length, while ME R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less
than 10m (32 ft.) in length. But transmission cable to the ME R/C can be extend using a
M-NET cable (>=1.25mm2 [16AWG]) when the length is counted in the M-Net length.
Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 (18-16AWG) in
TB7
thickness.
(S) 6 MA remote controller and ME remote controller should not be grouped together.
7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.

Pull box

Breakers for
current leakage Switch

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

* Power supply
specifications vary with
the model of connected
indoor units

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable

Breakers for

Power supply current leakage Switch


1-phase
208-230 60Hz

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)
MA R/C cable
0.3-1.25mm2 (22-16AWG)
(0.75~1.25mm2 [18-16AWG])
(Shield) S S (Shield)
<=200m (656 ft.)
Note(5, Note11
Transmission
booster
Note8
Note9
MA R/C

Note6
Note7
MA R/C

MA R/C

TB1
(R,S) E
TB2 TB3

*2
(Using ME remote controller)
Connecting TB5 terminal.

Pull box

Breakers for

Power supply current leakage Switch


1-phase
208-230 60Hz
Note10

Note7

* Power supply
specifications vary with
the model of connected
indoor units

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for

Power supply current leakage Switch


1-phase
208-230 60Hz

(Shield)
Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable
ME R/C

Symbol

Model

BC
OCP
NFB
OU
IU
SC

Breaker capacity
Over-current protector
Non-fuse breaker
Outdoor unit
Indoor unit
System controller

MA R/C

MA remote controller

ME R/C

ME remote controller

PUHY-P72THMU
PUHY-P96THMU
PUHY-P120THMU
PUHY-P72YHMU
PUHY-P96YHMU
PUHY-P120YHMU

TB1
(R,S) E
TB2 TB3
S

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

(Shield)

ME R/C cable
0.3~1.25mm2 (22-16AWG)
(0.75~1.25mm2 [18-16AWG])
<=10m (32 ft.)
Note5, Note11

Transmission
booster
Note8
Note9

Note6
Note7
ME R/C

ME R/C

Breakers for current leakage


*1, *2

30A 30mA or 100mA 0.1sec. or less


40A 30mA or 100mA 0.1sec. or less
50A 100mA 0.1sec. or less
15A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less

Switch

Switch

Minimum Wire thickness

BC
<A>

OCP*3
<A>

(NFB)
<A>

Power wire
<mm2/AWG>

G wire
<mm2/AWG>

30
40
50
15
20
25

30
40
50
15
20
25

30
40
50
15
20
25

5.3/10
5.3/10
13.3/6
2.1/14
3.3/12
5.3/10

5.3/10
5.3/10
13.3/6
2.1/14
3.3/12
5.3/10

*1 The breakers for current leakage should support Inverter circuit.


*2 Breakers for current leakage should combine using of switch.
*3 It shows data for B-type fuse of the breaker for current leakage.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-9

Y-SERIES
SYSTEM DESIGN

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)
IU

1. Electrical Work

DATA U4

The local standards and/or regulations is applicable at a higher priority.

1-4-3. PUHY-P264, 288, 312, 336, 360TSHMU/YSHMU


<In the case a system controller is connected.>
Central control
transmission cable
>=1.25mm2 (16AWG)
Shield cable
(CVVS, CPEVS
MVVS)

Note12
SC

Connector
CN41 CN40 OU
Note4

Note4

OU

OU

To other OU

Breakers for
current leakage Switch

TB1
TB3 TB7
(L1,L2,L3) (M1,M2) (M1,M2)

Power supply
3-phase 3-wire
208-230 60Hz(TSHMU)
460V 60Hz(YSHMU)
Note10,13
G

TB1
(L1,L2,L3)

TB1
Breakers for
current leakage Switch (L1,L2,L3)
Power supply
TB7 3-phase 3-wire
(S) 208-230 60Hz(TSHMU)
460V 60Hz(YSHMU)
Note10,13
G

TB3
TB7
(M1,M2) (M1,M2)

Breakers for
current leakage Switch
Power supply
TB7 3-phase 3-wire
60Hz(TSHMU)
(S) 208-230
460V 60Hz(YSHMU)
Note10,13
G

Note3

Note3

TB3
TB7
(M1,M2) (M1,M2)

Note3

To *1 or *2

*1
(Using MA remote controller)
Connecting TB5 terminal.

Breakers for
current leakage Switch

Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol
means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC50KUA should be used. The transmission cable (above 1.25mm2
[16AWG] shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is
called central control transmission cable. The shield wire of the central control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40.
TB7 5 MA R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less than 200m (656 ft.)
(S)
in length, while ME R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less
than 10m (32 ft.) in length. But transmission cable to the ME R/C can be extend using a
M-NET cable (>=1.25mm2 [16AWG]) when the length is counted in the M-Net length.
Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 (18-16AWG) in
thickness.
6 MA remote controller and ME remote controller should not be grouped together.
7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.

Pull box

Power supply
1-phase
208-230 60Hz
Note10

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

* Power supply
specifications vary with
the model of connected
indoor units

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for
current leakage Switch

Power supply
1-phase
208-230 60Hz

TB1
(R,S) E
TB2 TB3
S

(Shield)
Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable

(Shield)

Transmission
booster
Note8
Note9

Note6
Note7
MA R/C

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

MA R/C

MA R/C cable
0.3-1.25mm2 (22-16AWG)
(0.75~1.25mm2 [18-16AWG])
<=200m (656 ft.)
Note(5, Note11

MA R/C

*2
(Using ME remote controller)
Connecting TB5 terminal.

Breakers for
current leakage Switch
Power supply
1-phase
208-230 60Hz
Note10
* Power supply
specifications vary with
the model of connected
indoor units

Pull box
Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for
current leakage Switch

Power supply
1-phase
208-230 60Hz

TB1
(R,S) E
TB2 TB3

Y-SERIES
SYSTEM DESIGN

(Shield)
Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable
ME R/C

Symbol

Model

BC
OCP
NFB
OU
IU
SC

Breaker capacity
Over-current protector
Non-fuse breaker
Outdoor unit
Indoor unit
System controller

MA R/C

MA remote controller

ME R/C

ME remote controller

YSD-10

PUHY-P72THMU
PUHY-P96THMU
PUHY-P120THMU
PUHY-P72YHMU
PUHY-P96YHMU
PUHY-P120YHMU

30A 30mA or 100mA 0.1sec. or less


40A 30mA or 100mA 0.1sec. or less
50A 100mA 0.1sec. or less
15A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less

(Shield)

Transmission
booster
Note8
Note9

Note6
Note7
ME R/C

Breakers for current leakage


*1, *2

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

ME R/C cable
0.3~1.25mm2 (22-16AWG)
(0.75~1.25mm2 [18-16AWG])
<=10m (32 ft.)
Note5, Note11

ME R/C

Switch

Switch

Minimum Wire thickness

BC
<A>

OCP*3
<A>

(NFB)
<A>

Power wire
<mm2/AWG>

G wire
<mm2/AWG>

30
40
50
15
20
25

30
40
50
15
20
25

30
40
50
15
20
25

5.3/10
5.3/10
13.3/6
2.1/14
3.3/12
5.3/10

5.3/10
5.3/10
13.3/6
2.1/14
3.3/12
5.3/10

*1 The breakers for current leakage should support Inverter circuit.


*2 Breakers for current leakage should combine using of switch.
*3 It shows data for B-type fuse of the breaker for current leakage.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-1. Transmission Cable Length Limitation


2-1-1. Using MA Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7
<=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from MA to Indoor
a1+a2, a1+a2+a3+a4, a1
<=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]
DC 24V to AG-150A
n
<=10m[32ft.]
0.75-2.0 mm2 [AWG18-14]
L8

L1

Group1

Group3

Group5

OS2

OS1

OC

IC

IC

IC

IC

(53)

(52)

(51)

(01)

(04)

(05)

(06)

TB3
M1M2

TB3
M1M2

TB3
M1M2

TB5
M1M2 S

TB15
1 2

TB5
M1M2 S

TB15
1 2

TB5
M1M2 S

TB15
1 2

TB15
1 2

TB5
M1M2 S

a2

a1

TB7
M1M2 S

a2

a2

A B

Shielded wire

A B

A B

MA

MA

L2

MA

L3

OC

L4

(54 )
TB7
TB3
M1M2

IC

IC

IC

(02)

(03)

(07)

TB5
M1M2 S

TB5 TB 15
M1M2 S 1 2

TB15
1 2

TB15
1 2

TB5
M1M2 S

L6

M1 M2 S

a4

a3

TB7
M1M2 S

a1

TB7
M1M2 S

A B S

a1

Power Supply Unit


PAC-SC51KUA
24VDC GND

L7

A B

AG-150A

A B S

MA
24VDC GND

OC, OS1, OS2 : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller

2-1-2. Using ME Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5
<=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from ME to Indoor
e1, e2, e3, e4
<=10m[32ft.]*1
0.3-1.25 mm2 [AWG22-16] *1
DC 24V to AG-150A
n
<=10m[32ft.]
0.75-2.0 mm2 [AWG18-14]
*1. If the length from ME to Indoor exceed 10m (32 ft.), use 1.25 mm2 [AWG16] shielded cable and include its length as a part of the max. overall length of the
M-NET transmission cable.
L1

L8

Group3

Group5

OS2

OS1

OC

IC

IC

IC

IC

(53)

(52)

(51)

(01)

(04)

(05)

(06)

TB3
M1M2

TB3
M1M2

TB3
M1M2

TB7
M1M2 S

TB7
M1M2 S

TB7
M1M2 S

TB5
M1M2 S

TB5
M1M2 S

L2

Shielded wire

TB5
M1M2 S

e3

A B

A B

A B

(101)

(105)

(155)

ME

ME

ME

L3

OC

L4

(54 )
TB7
TB3
M1M2

IC

IC

IC

(02)

(03)

(07)

TB5
M1M2 S

TB5
M1M2 S

TB5
M1M2 S

L6

L5

M1 M2 S

e2

e1

TB5
M1M2 S

A B S

e4

Power Supply Unit


PAC-SC51KUA
24VDC GND

A B

L7

(103)
AG-150A

A B S

ME

24VDC GND

OC, OS1, OS2: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-11

Y-SERIES
SYSTEM DESIGN

Group1

2. M-NET Control

DATA U4

2-2. Transmission Cable Specifications


Transmission cables (Li)
Type of cable

ME Remote controller cables

Cable size

1.25

Remarks

[AWG16]

0.3 1.25
(0.75 1.25

YSD-12

2
2

[AWG22 16]
[AWG18 16])

When 10m [32ft] is exceeded, use cables with


the same specification as transmission cables.

0.3 1.25
(0.75 1.25

2
2

[AWG22 16]
[AWG18 16])

Max length : 200m [656ft]

CVVS, MVVS : PVC insulated PVC jacketed shielded control cable


CPEVS : PE insulated PVC jacketed shielded communication cable
CVV
: PV insulated PVC sheathed control cable

Y-SERIES
SYSTEM DESIGN

Connected with simple remote controller.

MA Remote controller cables

Sheathed 2-core cable (unshielded)


CVV

Shielding wire (2-core)


CVVS, CPEVS or MVVS

Y-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-3. System Configuration Restrictions


2-3-1. Common restrictions for the CITY MULTI system
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
B) Maximum 2 remote controllers for 1 Group;
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC50(51)KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.

2-3-2. Ensuring proper communication power for M-NET


In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY and Controllers, the transmission
power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the
power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption by index Indoor units, LOSSNAY, controllers
Indoor unit

Indoor unit

Sized P06-P54

Sized P72,P96

BC controller
CMB

MA RC.LOSSNAY

ME Remote Contr.

PAR-21MAA
PAR-F27MEA
PAC-YT51CRA(B) PZ-52SF
PAR-FA32MA
LGH-RX-E
PZ-41SLB
0
1/4

Timers, System Contr.


PAC-SF44SRA
PAC-YT34STA
G-50A
AG-150A
1/2

ON/OFF Contr.

GB-50A

PAC-YT40ANRA
GB-24

*RC : Remote Controller

Table 2-3-2 The equivalent power supply capability index of Trans.Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster
PAC-SF46EPA
25

Power supply unit


PAC-SC50KUA
6

PAC-SC51KUA
5

Outdoor unit

Outdoor unit

Connector TB3 and TB7 total *


32

Connector TB7 only


6

*If PAC-SC50(51)KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.

With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the airconditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System
controllers.If the total quantity reaches 40, a PAC-SF46EPA should be set.In this case, Indoor unit sized P72, 96 is
counted as 2 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption
reaches 32, a PAC-SF46EPA should be set.Yet, if a PAC-SC50(51)KUA is used to supply power at TB7 side, count from
index TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches
6, a PAC-SF46EPA should be set.

Y-SERIES
SYSTEM DESIGN

System example

TB7

TB3

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

01

Transmission
booster
(No.1)

02

ME remote
controller
TB7

TB3
Outdoor unit

ME remote
controller

N1

N2
Within N2, conditions 1,2 should be followed.
1.The total quantity of Indoor units and ME remote controller
should not exceed 40.
*Indoor unit sized P72, 96 is counted as 2 units.
2.The total equivalent transmission power consumption
should not exceed 25.

Transmission booster (No.1) should be used,


if the total quantity of Indoor units and ME remote controllers
reaches 40, (Indoor unit sized P72, 96 is counted as 2);
or if the total equivalent transmission power consumption reaches 32.

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

LOSSNAY
unit

CENTRALIZED CONTROLLER AG-150A

M-NET

Power supply unit


PAC-SC51KUA

24VDC

Centralized
Controller
AG-150A

PZ-52SF

N3
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 6.

Transmission
booster
PAC-SF46EPA
(No.2)

LOSSNAY
unit
PZ-52SF

N4
Within N4, the total equivalent transmission
power consumption should not exceed 25.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-13

2. M-NET Control

DATA U4

2-3-3. Ensuring proper power supply to System controller


The power to System controller (excluding LMAP03-U) is supplied via M-NET transmission line. M-NET transmission line
at TB7 side is called Central control transmission line while one at TB3 side is called Indoor-Outdoor transmission line.
There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC50KUA.
D) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.

2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB3.
If there is more than 1 Outdoor unit, it is necessary to
replace power supply switch connector CN41 with CN40
on one Outdoor unit.

Fig. 2-3-3-A

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

System controller
(excluding LMAP03-E)
Group

TB3
TB7
Replacement of
CN41 with CN40

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

ME remote controller
System
controller

Maximum 3 System controllers can be connected to TB3,


but maximum 2 in the case of G-50A.

2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB7
and receiving power from the Outdoor unit.
It is necessary to replace power supply switch connector
CN41 with CN40 on one Outdoor unit.

Fig. 2-3-3-B

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Replacement of
CN41 with CN40

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

ME remote controller

Y-SERIES
SYSTEM DESIGN

System
controller

Maximum 3 System controllers can be connected to TB7.

2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC50KUA.
When using PAC-SC50KUA to supply transmission
power, the power supply connector CN41 should be kept
as it is. It is also a factory setting.
1 PAC-SC50KUA supports maximum 2 G-50A units due
to the limited power DC 12V at its TB3.
However, 1 PAC-SC50KUA supplies transmission power
at its TB2 equal to 6 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 6 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.

Fig. 2-3-3-C

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

PAC-SC50KUA

Indoor unit

ME remote controller

System
controller

CAUTION
It is recommended that AG-150A/GB-50A/GB-24A be connected to TB7 because it performs back-up to a number of data.
In an air conditioner system with more than one Outdoor unit, if AG-150A/GB-50A/GB-24A receives transmission power at TB3 or TB7 through one of the
Outdoor units, there would be a risk that if the connected Outdoor unit fails, then power supply to AG-150A/GB-50A/GB-24A would stop and disrupt the
whole system. When applying apportioned electric power function, it is necessary to connect AG-150A/GB-50A to TB7 and have its own power supply unit
PAC-SC50KUA/PAC-SC51KUA.

YSD-14

Y-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-3-3-D. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
When using PAC-SC51KUA to supply transmission
power, the power supply connector CN41 should be kept
as it is. It is also a factory setting.
1 PAC-SC51KUA supports maximum 1 AG-150A unit
due to the limited power DC 24V at its TB3.
However, 1 PAC-SC51KUA supplies transmission power
at its TB2 equal to 5 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 5 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.

Fig. 2-3-3-D

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

PAC-SC51KUA

Indoor unit

ME remote controller

System
controller

CAUTION
It is recommended that AG-150A/GB-50A/GB-24A are connected to TB7 because the controllers perform data backup.
If an air conditioner system has more than one Outdoor unit, AG-150A/GB-50A/GB-24A receiving transmission power at TB3 or TB7 on one of the Outdoor
units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A/GB-50A/GB-24A, and disrupt the whole system.
When applying apportioned electric power function, it is necessary tp connect AG-150A/GB-50A/GB-24A to TB7 and has the own power supply unit
PAC-SC50KUA/PAC-SC51KUA.

2-3-4. Power supply to LM adapter LMAP03U


1-phase 208-230V AC power supply is needed.
The power supply unit is not necessary when connecting only the LMAP03U. Yet, make sure to change the power supply
changeover connector CN41 to CN40 on the LM adapter.

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-15

2. M-NET Control

DATA U4

2-4. Address Setting


2-4-1. Switch operation

Unit address No. setting

7 8

0 1

2 3

45 6

789A

Caution for switch operations

0 1

7 8

2 3

D
BC E

F 0 12

34 5 6

Address No. of outdoor unit, indoor unit and remote controller.


The address No. is set at the address setting board.

Rotary switch
Branch
No. setting

45 6

In order to constitute CITY MULTI in a complete system, switch


operation for setting the unit address No. and connection No. is
required.

 Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.

 No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.

MA remote controller
When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
The factory setting is Main .
ON

Setting the dip switches


1

The dip switches are at the bottom of the remote controller.


Remote controller Main/Sub and other function settings are performed
using these switches.
Ordinarily, only change the Main/Sub setting of SW1. (The factory settings are all ON .)

SW contents Main

ON

OFF

Remote controller
Main/Sub setting

Main

Sub

When remote controller power turned on

Cooling/heating display in AUTO mode

Yes

No

When you do not want to display Cooling and Heating in the


Auto mode, set to No .

Intake temperature
display

Yes

No

When you do not want to display the intake temperature, set to No .

Normally on Timer mode on

Comment
Set one of the two remote controllers at one group to Main .
When you want to return to the timer mode when the power is restored after
a power failure when a Program timer is connected, select Timer mode .

Y-SERIES
SYSTEM DESIGN

SW No

ON

YSD-16

Y-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-2. Rule of setting address


Address setting

Example

Note
7 8

9 0 1

4 5 6

10

10

7 8

45 6

45 6

45 6

100

10

0
9 1

0
9 1

0,2

0~5

0~9

100

10

9 0 1

9 0 1

2 3

2 3

7 8

45 6

45 6

45 6

10

4 5 6

4 5 6

The address automatically becomes "200" if it is set


as "00"

01

7 8

7 8

7 8

100

Fixed

The address of main remote controller + 50

01

7 8

7 8

7 8

45 6

45 6

2 3

201 ~ 250

01
2 3

LMAP03U

The smallest address of indoor unit in the group + 100


The place of "100" is fixed to "1"

01

10

2 3

000, 201 ~ 250

01
2 3

GB-24A
G-50A
GB-50A
AG-150A

9
2 3

Fixed

ON/OFF controller 000, 201 ~ 250

01

7 8

7 8

45 6

45 6

Fixed

01

7 8

7 8

2 3

7 8

Local remote controller


System controller

4 5 6

4 5 6

000, 201 ~ 250

01

The smallest address of indoor unit in same refrigerant


system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"

2 3

System controller

101 ~ 150

Use the most recent address within the same group of


indoor units.
Set the address so that (1)<(2)<(3)

2 3

151 ~ 199, 200

2 3

ME, LOSSNAY
Remote controller
(Sub)

10

2 3

ME, LOSSNAY
Remote controller
(Main)

9 0 1

2 3

51 ~ 99, 100
(Note1)

2 3

7 8

9 0 1

Outdoor unit

2 3

01 ~ 50

2 3

7 8

9 0 1

Indoor unit

4 5 6

Unit

10

2-4-3. System examples


Factory setting
Original switch setting of the outdoors, indoors, controllers and LMAP at shipment is as follows.
Outdoor unit
: Address: 00, CN41: U (Jumper), DipSW2-1: OFF
Indoor unit
: Address: 00
Remote controller
: Address: 100
LMAP
: Address: 247, CN41: U (Jumper), DipSW1-2: OFF

Setting at the site


DipSW2-1(Outdoor)
DipSW1-2(LMAP)
CN40/CN41

: When the System Remote Controller is used, all the Dip SW2-1 at the outdoor units should be
set to "ON".
: When the LMAP is used together with System Remote Controller, DipSW1-2 at the LMAP
should be set to "ON".
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole central control system.
Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-17

Y-SERIES
SYSTEM DESIGN

Note1: To set the address to "100", set it to "50"


Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.

2. M-NET

Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
Control the outdoor unit failure may let down the whole central control system.
DATA U4

2-4-3-1. MA remote controller, Single-refrigerant-system, System Controller


<Three outdoor units>
PUHY-P-TSHMU/YSHMU
OC
OS1
OS2

51
CN40

CN41

DipSW2-1

ON
TB3

52
CN40

CN41

53
CN40

51

CN41

DipSW2-1

DipSW2-1

ON

ON

TB3

<Two outdoor units>


PUHY-P-TSHMU/YSHMU
OC
OS1
CN40

52

CN41

CN40

DipSW2-1

ON
TB3

TB3

<One outdoor unit>


PUHY-P-THMU/YHMU
OC

51

CN41

CN40

DipSW2-1

DipSW2-1

ON

ON
TB3

TB3

Group 1

CN41

Group 2

Group 3

Group 4

Indoor unit

01
TB5

02
TB15

201
SC

03

TB5

SRU

TB15

TB5

04
TB15

TB5

05
TB15

TB5

TB15

1*

MA R/C

MA R/C

MA R/C MA R/C
(Main)
(Sub)

1*
Wireless R/C
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

Y-SERIES
SYSTEM DESIGN

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units and central controller.
3. For a system having more than 32 indoor unit (P06-P54), confirm the need of Booster at 2-3 "System configuration
restrictions".

YSD-18

Y-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-2. MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long M-NET wiring
PUHY-P-TSHMU/YSHMU
OC
OS1
TB7
TB7

51
CN40

CN41

DipSW2-1

ON
TB3

52
CN40

CN41

53
CN40

91

CN41

DipSW2-1

DipSW2-1

ON

ON

TB3

PUHY-P-TSHMU/YSHMU
OC
OS1
TB7
TB7

OS2
TB7

CN40

92

CN41

CN40

DipSW2-1

ON
TB3

TB3

PUHY-P-THMU/YHMU
OC
TB7

97

CN41

CN40

DipSW2-1

DipSW2-1

ON

ON
TB3

TB3

Group 1

CN41

Group 2

Group 21

Indoor unit

01
TB5

201

02
TB15

TB5

TB5

30
TB15

TB2

TB3

TB5

TB15

Transmission Booster
PAC-SF46EPA

SRU *1
MA R/C

SC

MA R/C MA R/C
(Main)
(Sub)

*1

PSU
Power supply unit (PSU)
(PAC-SC51KUA)

03
TB15

Wireless R/C

*2
Group 31

Group 32

Indoor unit

42
TB15

SRU *1

Group 34

LOSSNAY

41
TB5

Group 33

TB5

142

45

43

TB5

TB5

46
TB15

TB5

TB15

143

ME R/C PZ-52SF

MA R/C

MA R/C MA R/C
(Main)
(Sub)

*1
Wireless R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-19

Y-SERIES
SYSTEM DESIGN

*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For G-50A,
12V DC should be used with the PSU (PAC-SC50KUA). For AG-150A, 24VDC should be used with the PSU (PAC-SC51KUA).

2. M-NET Control

DATA U4

2-4-3-3. ME remote controller, Single-refrigerant-system, No system controller


<Three outdoor units>
PUHY-P-TSHMU/YSHMU
OC
OS1
OS2

51
CN40

CN41

DipSW2-1

OFF
TB3

52
CN40

CN41

DipSW2-1

OFF
TB3

<Two outdoor units>


PUHY-P-TSHMU/YSHMU
OC
OS1

53
CN40

51

CN41

CN40

DipSW2-1

52

CN41

CN40

DipSW2-1

OFF
TB3

<One outdoor unit>


PUHY-P-THMU/YHMU
OC

51

CN41

CN40

DipSW2-1

OFF
TB3

DipSW2-1

OFF

OFF
TB3

TB3

Group 1

CN41

Group 2

Group 3

Group 4

Indoor unit

01

02

TB5

03

TB5

04

TB5

TB5

05
TB5

101

102

104

ME R/C

ME R/C

ME R/C

105

155

ME R/C ME R/C

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, central controller and ME remote controllers.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

2-4-3-4. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY


<Three outdoor units>
PUHY-P-TSHMU/YSHMU
OC
OS1
OS2

51
CN40

CN41

DipSW2-1

Y-SERIES
SYSTEM DESIGN

ON
TB3

52
CN40

CN41

<Two outdoor units>


PUHY-P-TSHMU/YSHMU
OC
OS1

53
CN40

51

CN41

DipSW2-1

DipSW2-1

ON

ON

TB3

CN40

TB3

Group 1

101
ME R/C

CN40

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 3

Group 4

LOSSNAY

02
TB5

102

04

03

TB5

SC

51

CN41

DipSW2-1

Group 2

01

201

CN40

DipSW2-1

Indoor unit

TB5

52

CN41

ON
TB3

<One outdoor unit>


PUHY-P-THMU/YHMU
OC

103

ME R/C PZ-52SF

TB5

05
TB5

104
ME R/C

105

155

ME R/C ME R/C

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, LOSSNAY central controller, ME remote controllers.
3. For a system having more than 32 indoor unit (P06-P54), confirm the need of Booster at 2-3 "System configuration
restrictions".

YSD-20

Y-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-5. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
PUHY-P-TSHMU/YSHMU
OC
OS1
TB7
TB7

51
CN40

CN41

DipSW2-1

ON
TB3

52
CN40

CN41

53
CN40

91

CN41

DipSW2-1

DipSW2-1

ON

ON

TB3

PUHY-P-TSHMU/YSHMU
OC
OS1
TB7
TB7

OS2
TB7

CN40

92

CN41

CN40

DipSW2-1

ON
TB3

TB3

PUHY-P-THMU/YHMU
OC
TB7

96

CN41

CN40

DipSW2-1

DipSW2-1

ON

ON
TB3

TB3

Group 1

CN41

Group 2

Group 21

Indoor unit

01
TB5

02

03

TB5

TB5

30
TB2

TB3

TB5

Transmission Booster
PAC-SF46EPA

201

101

102

SC

ME R/C

ME R/C

130

180

ME R/C ME R/C

PSU
Power supply unit (PSU)
(PAC-SC51KUA)

*1
Group 31

Group 32

Indoor unit

42

141

TB5

142

44

43

TB5

ME R/C

Group 34

LOSSNAY

41
TB5

Group 33

143

ME R/C PZ-52SF

TB5

45
TB5

144
ME R/C

145

195

ME R/C ME R/C

NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-21

Y-SERIES
SYSTEM DESIGN

*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For G-50A,
12V DC should be used with the PSU (PAC-SC50KUA). For AG-150A, 24VDC should be used with the PSU (PAC-SC51KUA).

2. M-NET Control

DATA U4

2-4-3-6. TG-2000A+G-50A/GB-50A
G-50A/GB-50A can control max. 50 indoor units;
TG-2000A can control max. 40 pieces of G-50A or GB-50A;
TG-2000A can control max. 2000 indoor units.
<Three outdoor units>
PUHY-P-TSHMU/YSHMU

GB-50A

OC

201

TB7

OS1
TB7

51

PSU

CN40

(PAC-SC50KUA or
PAC-SC51KUA)

CN41

OS2
TB7

52
CN40

DipSW2-1

ON
TB3

<Two outdoor units>


PUHY-P-TSHMU/YSHMU
OC
TB7

53

CN41

CN40

DipSW2-1

DipSW2-1

ON

ON

TB3

OS1
TB7

51

CN41

CN40

CN41

TB3

Group 1

OC
TB7

52
CN40

DipSW2-1

ON
TB3

<One outdoor unit>


PUHY-P-THMU/YHMU

51

CN41

CN40

DipSW2-1

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 2

Group 40

Indoor unit

01

HUB

02

TB5

TB15

03

TB5

TB15 TB5

42
TB15 TB2

TB3 TB5

Transmission Booster
PAC-SF46EPA

SRU *1
MA R/C

PC with
TG-2000A

TB15

MA R/C MA R/C
(Main)
(Sub)

*1
Wireless R/C

LAN
PUHY-P-TSHMU/YSHMU

G-50A

OC

202

TB7

OS1
TB7

51
CN40

DC12V

CN41

52
CN40

DipSW2-1

PSU
(PAC-SC50KUA)

ON
TB3

PUHY-P-TSHMU/YSHMU
OS2
TB7

CN41

OC
TB7

53
CN40

91

CN41

CN40

CN41

OC
TB7

92
CN40

96

CN41

DipSW2-1

DipSW2-1

DipSW2-1

DipSW2-1

ON

ON

ON

ON

TB3

TB3

TB3

Group 1

PUHY-P-THMU/YHMU

OS1
TB7

CN40

CN41

DipSW2-1

ON
TB3

TB3

Group 2

Group 21

Indoor unit

Y-SERIES
SYSTEM DESIGN

01
TB5

02

03

TB5

TB5

101

102

ME R/C

ME R/C

Group 31

130

Group 33

Group 34

142

44

43
TB5

143

ME R/C PZ-52SF

TB5

45
TB5

144
ME R/C

145

Y-SERIES SYSTEM DESIGN (Feb. 2009)

195

ME R/C ME R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

YSD-22

180

LOSSNAY

42
TB5

141

TB5

ME R/C ME R/C
Group 32

41

ME R/C

TB3

Transmission Booster
PAC-SF46EPA

Indoor unit

TB5

30
TB2

2. M-NET Control

DATA U4

2-4-3-7. TG-2000A (Ver.5.5*series)+AG-150A (Ver.1** series)


AG-150A can control max. 50 indoor units;
TG-2000A can control max. 40 pieces of AG-150A;
TG-2000A can control max. 2000 indoor units.

AG-150A

<Three outdoor units>


PUHY-P-TSHMU/YSHMU
OC

000

TB7

DC24V

OS1
TB7

51
PSU

(PAC-SC51KUA)

CN40

CN41

OS2
TB7

52
CN40

DipSW2-1

ON
TB3

<Two outdoor units>


PUHY-P-TSHMU/YSHMU
OC
TB7

53

CN41

CN40

DipSW2-1

DipSW2-1

ON

ON

TB3

OS1
TB7

51

CN41

CN40

CN41

TB3

Group 1

OC
TB7

52
CN40

DipSW2-1

ON
TB3

<One outdoor unit>


PUHY-P-THMU/YHMU

51

CN41

CN40

DipSW2-1

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 2

Group 40

Indoor unit

01

HUB

02
TB15

TB5

03
TB15 TB5

TB5

42
TB15 TB2

TB3 TB5

Transmission Booster
PAC-SF46EPA

SRU *1
MA R/C

PC with
TG-2000A

TB15

MA R/C MA R/C
(Main)
(Sub)

*1
Wireless R/C

LAN
PUHY-P-TSHMU/YSHMU

AG-150A

OC

000

TB7

OS1
TB7

51
DC24V

CN40

CN41

52
CN40

DipSW2-1

PSU
(PAC-SC51KUA)

ON
TB3

PUHY-P-TSHMU/YSHMU
OS2
TB7

CN41

OC
TB7

53
CN40

CN41

91
CN40

CN41

OC
TB7

92
CN40

96

CN41

DipSW2-1

DipSW2-1

DipSW2-1

DipSW2-1

ON

ON

ON

ON

TB3

TB3

TB3

Group 1

PUHY-P-THMU/YHMU

OS1
TB7

CN40

CN41

DipSW2-1

ON
TB3

TB3

Group 2

Group 21

01
TB5

02
TB5

03
TB5

101

102

ME R/C

ME R/C

Group 31

TB5

130

180

Group 33

Group 34

LOSSNAY

42
TB5

141

TB3

ME R/C ME R/C
Group 32

41

ME R/C

TB2

Transmission Booster
PAC-SF46EPA

Indoor unit

TB5

30

142

44

43
TB5

143

ME R/C PZ-52SF

TB5

45
TB5

144
ME R/C

145

195

ME R/C ME R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-23

Y-SERIES
SYSTEM DESIGN

Indoor unit

2. M-NET Control

DATA U4

2-4-3-8. LMAP
LMAP can transmission for max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system
controller (SC).
LMAP can transmission for max.
50 indoor units in single-refrigerant-system or multi-refrigerant-system.

LMAP(01)

identified by Neuron ID

(LONWORKS adapter)

<Three outdoor units>


PUHY-P-TSHMU/YSHMU
OC
OS1
OS2
TB7
TB7
TB7

247
CN40 CN41
DipSW1-2
OFF

51
CN40

52

CN41

CN40

DipSW2-1

53

CN41

CN40

DipSW2-1

OFF
TB3

<Two outdoor units>


PUHY-P-TSHMU/YSHMU
OC
OS1
TB7
TB7

51

CN41

CN40

DipSW2-1

OFF
TB3
Group 1

52

CN41

CN40

DipSW2-1

OFF
TB3

<One outdoor unit>


PUHY-P-THMU/YHMU
OC
TB7

OFF
TB3

51

CN41

CN40

DipSW2-1

CN41

DipSW2-1

OFF

OFF
TB3

TB3

Group 2

Group 40

Indoor unit

01

02
TB15

TB5

03
TB15 TB5

TB5

42
TB15

G-50A
Power supply unit
(PAC-SC50KUA)
DC 12V
PSU

TB15

Transmission Booster
PAC-SF46EPA

SRU *1

000

TB3 TB5

TB2

MA R/C

MA R/C MA R/C
(Main) (Sub)

*1
Wireless R/C

LONWORKS

LMAP(02)
identified by Neuron ID

PUHY-P-TSHMU/YSHMU

247
CN40 CN41

OC
TB7

DipSW1-2
ON

CN40

51

CN41

OS1
TB7
CN40

DipSW2-1

ON
TB3

52

CN41

PUHY-P-TSHMU/YSHMU
OS2
TB7
CN40

53

CN41

DipSW2-1

DipSW2-1

ON

ON

TB3

OC
TB7
CN40

Group 1

OS1
TB7

91

CN41

CN40

DipSW2-1

ON
TB3

TB3

PUHY-P-THMU/YHMU
OC
TB7

92

CN41

CN40

DipSW2-1

96

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 2

Group 21

Y-SERIES
SYSTEM DESIGN

Indoor unit

01
TB5

02
TB5

101

102

ME R/C

ME R/C

Group 31
Indoor unit

TB5

30
TB2

TB3

TB5

Transmission Booster
PAC-SF46EPA

130

180

ME R/C ME R/C

Group 32

Group 33

Group 34

LOSSNAY

41
PC

03
TB5

42
TB5

44

43
TB5

TB5

45
TB5

LONWORKS card
141
LONWORKS card
LONWORKS card

ME R/C

142

143

ME R/C PZ-52SF

144
ME R/C

145

195

ME R/C ME R/C

For other equipments (Lighting, security, elevator etc.)


*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

YSD-24

Y-SERIES SYSTEM DESIGN (Feb. 2009)

3. Piping Design

DATA U4

3-1. R410A Piping Material


Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types.
A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand.
B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness.
The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety
under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Ta ble 3-1, or You shall follow the local
industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.
Size (mm)
Size (inch) Radial thickness (mm) Radial thickness (mil)
[32]
6.35
1/4"
0.8
[32]
9.52
3/8"
0.8
[32]
12.7
1/2"
0.8
[40]
15.88
5/8"
1.0
[48]
19.05
3/4"
1.2
[40]
19.05
3/4"
1.0
[40]
22.2
7/8"
1.0
[40]
25.4
1"
1.0
[40]
28.58
1-1/8"
1.0
[44]
31.75
1-1/4"
1.1
[48]
34.93
1-3/8"
1.2
[56]
41.28
1-5/8"
1.4

Pipe type
Type-O
Type-O
Type-O
Type-O
Type-O
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H

* For pipe sized 19.05 (3/4") for R410A air conditioner, choice of pipe type is up to you.
* The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the
local standards.

Flare
Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions
mentioned below so as to achieve enough the air-tightness.

Flare pipe

Pipe size
6.35 [1/4"]
9.52 [3/8"]
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]

A (For R410A)
9.1 [3/8"]
13.2 [9/16"]
16.6 [11/16"]
19.7 [13/16"]
24.0 [1"]

(mm[in.])

Flare nut

Pipe size
6.35 [1/4"]
9.52 [3/8"]
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]

B (For R410A)

(mm[in.])

17.0 [3/4"]
22.0 [7/8"]
26.0 [1-1/16"]
29.0 [1-1/8"]
36.0 [1-7/16"]

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-25

3. Piping Design

DATA U4

3-2. PUHY-P-T(S)HMU/Y(S)HMUs Piping Design


3-2-1. PUHY-P72-120THMU/YHMU Piping
OU
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;
Note2. "-"
Note3. As bends cause pressure loss on transportation of refrigerant, the less bends in the design is better;
Piping length needs to consider the actual length and equivalent length which bends are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bend.

A
Header
B
H' (OU under IU)

H (OU above IU)

1st Joint
Capped
L1
C

L2

Joint

IU

IU

IU

IU

IU

IU

IU

h1

Fig. 3-2-1A Piping scheme

IU : Indoor unit , OU : Outdoor unit

Table3-2-1-1. Piping length


Item
Total piping length
Farthest IU from OU (L1)
Farthest IU from first Joint (L2)
Height between OU and IU (OU above IU)
Height between OU and IU (OU under IU)
Height between IU and IU

(m [ft.]) Table3-2-1-2. Bends equivalent length "M"


Outdoor Model
M (m/bends [ft./bends])
Piping in the figure
Max. length Max. equivalent length
PUHY-P72T/YHMU
0.35 [1.15]
A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280']
PUHY-P96T/YHMU
0.42 [1.38]
A+C+D+E+g / A+B+c
165 [541']
190 [623']
PUHY-P120T/YHMU
0.42 [1.38]
C+D+E+g / B+c
40 [131']*1
40 [131']
H
50 [164']*2
H'
40 [131']*2
h1
15 [49']
-

OU: Outdoor Unit, IU: Indoor Unit


*1. Refer to Figure 3-2-4 for possible pipe extension.
*2. Contact a Mitsubishi representative for possible height extensions.

Y-SERIES
SYSTEM DESIGN

Table3-2-1-3. Piping "A" size selection rule


Outdoor and the first Joint
Pipe(Liquid)
PUHY-P72T/YHMU=CMY-Y102S-G2
9.52 [3/8"]
PUHY-P96T/YHMU=CMY-Y102S/L-G2
9.52 [3/8"] *1
PUHY-P120T/YHMU=CMY-Y102S/L-G2 9.52 [3/8"] *2
*1.A>=90m [295ft.], 12.70mm [1/2in.] ;
*2.A>=40m [131ft.], 12.70mm [1/2in.]

(mm [in.]) Table3-2-1-6. R410A Joint selection rule


Pipe(Gas)
Total downstream Indoor capacity
~ P72
19.05 [3/4"]
P73 ~ P144
22.20 [7/8"]
P145 ~ P240
22.20 [7/8"]
P241 ~
*Concerning detailed usage of Joint parts, refer to its Installation Manual.

Table3-2-1-4. R410A piping"B","C","D","E"size selection rule


Total downstream Indoor capacity
Pipe(Liquid)
~ P54
9.52 [3/8"]
P55 ~ P72
9.52 [3/8"]
P73 ~ P108
9.52 [3/8"]
P109 ~ P144
12.70 [1/2"]
P145 ~ P240
15.88 [5/8"]
P241 ~ P308
19.05 [3/4"]
P309 ~
19.05 [3/4"]

(mm [in.])
Pipe(Gas)
15.88 [5/8"]
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
34.93 [1-3/8"]
41.28 [1-5/8"]

Table3-2-1-7. R410A Header selection rule


4-branch Header 8-branch Header 10-branch Header
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Total downstream Indoor capacity <=P72
<=P144
<=P240
* CMY-Y104-G can directly connect PUHY-P72T/YHMU, but can NOT directly connect PUHY-P96T/YHMU or above;
* CMY-Y108-G can directly connect PUHY-P72~168T/Y(S)HMU, but can NOT directly connect PUHY-P192T/YSHMU or above;
* CMY-Y1010-G can directly connect PUHY-P72~240T/Y(S)HMU;
* CMY-Y104-G can NOT connect P72~P96 Indoor; use CMY-Y108,Y1010-G to connect P72-P96 IDU;
* Concerning detailed usage of Header parts, refer to its Installation Manual.
Note4.
Note5.

Table3-2-1-5. Piping "a","b","c","d","e","f","g" size selection rule


(mm [in.])
Indoor Unit size
Pipe(Liquid)
Pipe(Gas)
P06,P08,P12,P15,P18
6.35 [1/4"]
12.70 [1/2"]
P27,P30,P36,P48,P54
9.52 [3/8"]
15.88 [5/8"]
P72
9.52 [3/8"]
19.05 [3/4"]
P96
9.52 [3/8"]
22.20 [7/8"]

YSD-26

Joint
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2

Note6.

Indoor capacity is described as its model size;


For example, PDFY-P06NMU-E, its capacity is P06;
Total downstream Indoor capacity is the summary of the model size of Indoors downstream.
For example, PDFY-P06NMU-E+PDFY-P08NMU-E: Total Indoor capacity=P06+P08=P14
Piping sized determined by the Total downstream indoor capacity is NOT necessary
to be bigger than the upstream one.
i.e. A>=B; A>=C>=D

Y-SERIES SYSTEM DESIGN (Feb. 2009)

3. Piping Design

DATA U4

3-2-2. PUHY-P144-240TSHMU/YSHMU Piping


Note1. No Joint after Header; Piping direct to Indoor Unit from Header;
Note2. "-"
Note3. As bends cause pressure loss on transportation of refrigerant, the less bends in the design is better;
Piping length needs to consider the actual length and equivalent length which bends are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bend.

OU
OU

OK

Trap (gas
pipe only)

NG

h2
Downward To indoor unit
incline

T
S

2m

Upward To indoor unit


incline

Install the pipes from the outdoor unit to the branch


joint with a downward incline.

To indoor unit

2 m max To indoor unit

If the length of pipe between the branch joint and outdoor


unit exceeds 2 m, provide a trap at a distance 2 m or less
from the branch joint.
Header
Capped

1st Joint
Outdoor Twinning Kit
CMY-Y100VBK

L1
L2
D

IU

IU

IU

IU

IU

IU

Joint

h1

H' (OU under IU)

H (OU above IU)

IU

Fig. 3-2-1B Piping scheme

Table3-2-2-1. Piping length


Item
Total piping length
Distance between OU and OU
Height between OU and OU
Farthest IU from OU (L1)
Farthest IU from the first Joint (L2)
Height between OU and IU (OU above IU)
Height between OU and IU (OU above IU)
Height between IU and IU

IU : Indoor unit , OU : Outdoor unit

(m [ft.]) Table3-2-2-2. Bends equivalent length "M"


Piping in the figure
Max. length Max. equivalent length
Outdoor Model
M (m/bends [ft./bends])
PUHY-P144T/YSHMU
0.50 [1.64]
S+T+A+B+C+D+E+a+b+c+d+e+f+g 1000 [3280']
PUHY-P168T/YSHMU
0.50 [1.64]
S+T
10[32']
PUHY-P192T/YSHMU
0.50 [1.64]
h2
0.1[0.3']
PUHY-P216T/YSHMU
0.50 [1.64]
S(T)+A+C+D+E+g / S(T)+A+B+c 165 [541']
190 [623']
PUHY-P240T/YSHMU
0.50 [1.64]
C+D+E+g / B+c
40 [131']*1
40 [131']
H
50 [164']*2
H'
40 [131']*2
h1
15 [49']
-

OU: Outdoor Unit, IU: Indoor Unit


*1. Refer to Figure 3-2-4 for possible pipe extension.
*2. Contact a Mitsubishi representative for possible height extensions.

Table3-2-2-3. Piping "A" size selection rule


Outdoor and the first Joint
Pipe(Liquid)
CMY-Y100VBK2=CMY-Y202-G2
12.70[1/2"]
15.88[5/8"]

(mm [in.])
Pipe(Gas)
28.58[1-1/8"]*1
28.58[1-1/8"]*2

Table3-2-2-4. Piping"B","C","D","E" size selection rule


Total downstream Indoor capacity
Pipe(Liquid)
~ P54
9.52 [3/8"]
P55 ~ P72
9.52 [3/8"]
P73 ~ P108
9.52 [3/8"]
P109 ~ P144
12.70 [1/2"]
P145 ~ P240
15.88 [5/8"]
P241 ~ P308
19.05 [3/4"]
P309 ~
19.05 [3/4"]

(mm [in.])
Pipe(Gas)
15.88 [5/8"]
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
34.93 [1-3/8"]
41.28 [1-5/8"]

Table3-2-2-5. Piping"a","b","c","d","e","f","g" size selection rule


Indoor Unit size
Pipe(Liquid)
P06,P08,P12,P15,P18
6.35 [1/4"]
P27,P30,P36,P48,P54
9.52 [3/8"]
P72
9.52 [3/8"]
P96
9.52 [3/8"]

(mm [in.])
Pipe(Gas)
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]
22.20 [7/8"]

Joint
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2

*PUHY-P192~240T/YHMU's first Joint is always CMY-Y202-G2;


*Concerning detailed usage of Joint parts, refer to its Installation Manual.
*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that
are connected to the branch joint should be 240 or below.
If the total capacity of the units in the downstream of the branch joints on both lines is 240 or above use
two branch joints (CMY-Y302-G2).

Table3-2-2-7. R410A Header selection rule


4-branch Header 8-branch Header 10-branch Header
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Total downstream Indoor capacity <=P72
<=P144
<=P240
* CMY-Y104-G can directly connect PUHY-P72T/YHMU, but can NOT directly connect PUHY-P96T/YHMU or above;
* CMY-Y108-G can directly connect PUHY-P72~168T/Y(S)HMU, but can NOT directly connect PUHY-P192T/YSHMU or above;
* CMY-Y1010-G can directly connect PUHY-P72~240T/Y(S)HMU;
* CMY-Y104-G can NOT connect P72~P96 Indoor, use CMY-Y108,Y1010-G to connect P72-P96;
* Concerning detailed usage of Header parts, refer to its Installation Manual.
Note4.
Note5.
Note6.

Indoor capacity is described as its model size;


For example, PDFY-P06NMU-E, its capacity is P06;
Total downstream Indoor capacity is the summary of the model size of Indoors downstream.
For example, PDFY-P06NMU-E+PDFY-P08NMU-E: Total Indoor capacity=P06+P08=P14
Piping sized determined by the Total downstream indoor capacity is NOT necessary
to be bigger than the upstream one.
i.e. A>=B; A>=C>=D

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-27

Y-SERIES
SYSTEM DESIGN

*1 PUHY-P144T/YSHMU
*2 PUHY-P168-240T/YSHMU
CMY-Y100VBK2; PUHY-P144-240T/YSHMU
For Piping size "S","T", please refer to specification of the Twining kit CMY-Y100VBK2 at the Outdoor unit's
external drawing.

Table3-2-2-6. R410A Joint selection rule


Total downstream Indoor capacity
~ P72
P73 ~ P144
P145 ~ P240
P241 ~

3. Piping Design

DATA U4

3-2-3. PUHY-P264-360TSHMU/YSHMU Piping


OU

Note1. No Joint after Header; Piping direct to Indoor Unit from Header;
Note2. "-"
Note3. As bends cause pressure loss on transportation of refrigerant, the less bends in the design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.

OU

OK
h2

N
Downward To indoor unit
incline

H' (OU under IU)

To indoor unit

2 m max To indoor unit

If the length of pipe between the branch joint and outdoor


unit exceeds 2 m, provide a trap at a distance 2 m or less
from the branch joint.
Header

1st Outdoor
Twinning Kit
2nd Outdoor
Twinning Kit

2m

Upward To indoor unit


incline

Install the pipes from the outdoor unit to the branch


joint with a downward incline.

H (OU above IU)

Trap (gas
pipe only)

NG

Capped

1st Joint
C

L1
L2
D

IU

IU

IU

IU

IU

IU

Joint

h1

OU

IU

Fig. 3-2-1C Piping scheme

IU : Indoor unit , OU : Outdoor unit

Table3-2-3-1. Piping length


Item
Total piping length
Distance between OU and OU
Height between OU and OU
Farthest IU from OU (L1)
Farthest IU from the first Joint (L2)
Height between OU and IU (OU above IU)
Height between OU and IU (OU above IU)
Height between IU and IU

(m [ft.])
Piping in the figure
Max. length Max. equivalent length
S+T+M+N+A+B+C+D+E+a+b+c+d+e+f+g1000[3280']
M+N+S+T
10[32']
h2
0.1[0.3']
M(N)+S+A+C+D+E+g / M(N)+S+A+B+c 165[541']
190[623']
C+D+E+g / B+c
40[131']*1
40[131']
H
50[164']*2
H'
40[131']*2
h1
15[49']
-

Table3-2-3-2. Bends equivalent length "M"


Outdoor Model
M (m/bends [ft./bends])
PUHY-P264T/YSHMU
0.70 [2.29]
PUHY-P288T/YSHMU
0.70 [2.29]
PUHY-P312T/YSHMU
0.70 [2.29]
PUHY-P336T/YSHMU
0.80 [2.62]
PUHY-P360T/YSHMU
0.80 [2.62]

OU: Outdoor Unit, IU: Indoor Unit


*1. Refer to Figure 3-2-4 for possible pipe extension.
*2. Contact a Mitsubishi representative for possible height extensions.

Table3-2-3-3. Piping "A" size selection rule


Outdoor and the first Joint
Pipe(Liquid)
CMY-Y300VBK2=CMY-Y302-G2
19.05[3/4"]
19.05[3/4"]

(mm [in.])
Pipe(Gas)
34.93[1-3/8"] *1
41.28[1-5/8"] *2

*1 PUHY-P264-312TSHMU/YSHMU
*2 PUHY-P336,360TSHMU/YSHMU

Y-SERIES
SYSTEM DESIGN

For Piping size"M","N","S","T", please refer to specification of the Twining kit


CMY-Y300VBK2 at the Outdoor unit's external drawing.

Table3-2-3-4. Piping"B","C","D","E" size selection rule


Total downstream Indoor capacity
Pipe(Liquid)
~ P54
9.52 [3/8"]
P55 ~ P72
9.52 [3/8"]
P73 ~ P108
9.52 [3/8"]
P109 ~ P144
12.70 [1/2"]
P145 ~ P240
15.88 [5/8"]
P241 ~ P308
19.05 [3/4"]
P309 ~
19.05 [3/4"]
Table3-2-3-5. Piping"a","b","c","d","e","f","g" size selection rule
Indoor Unit size
Pipe(Liquid)
P06,P08,P12,P15,P18
6.35 [1/4"]
P27,P30,P36,P48,P54
9.52 [3/8"]
P72
9.52 [3/8"]
P96
9.52 [3/8"]

YSD-28

(mm [in.])
Pipe(Gas)
15.88 [5/8"]
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
34.93 [1-3/8"]
41.28 [1-5/8"]
(mm [in.])
Pipe(Gas)
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]
22.20 [7/8"]

Table3-2-3-6. R410A Joint selection rule


Total down-stream Indoor capacity
~ P72
P73 ~ P144
P145 ~ P240
P241 ~

Joint
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2

*The total capacity of the units in the downstream of the branch joint on at least one of the piping lines that
are connected to the branch joint should be 240 or below.
If the total capacity of the units in the downstream of the branch joints on both lines is 240 or above use two
branch joints (CMY-Y302-G2).
*Concerning detailed usage of Joint parts, refer to its Installation Manual.

Table3-2-3-7. R410A Header selection rule


4-branch Header 8-branch Header 10-branch Header
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Total downstream Indoor capacity <=P200
<=P400
<=P650
* CMY-Y104-G can directly connect PUHY-P72T/YHMU, but can NOT directly connect PUHY-P96T/YHMU or above;
* CMY-Y108-G can directly connect PUHY-P72~168T/Y(S)HMU, but can NOT directly connect PUHY-P192T/YSHMU or above;
* CMY-Y1010-G can directly connect PUHY-P72~240T/Y(S)HMU;
* CMY-Y104-G can NOT connect P72~P96 Indoor, use CMY-Y108,Y1010-G to connect P72-P96;
* Concerning detailed usage of Header parts, refer to its Installation Manual.
Note4.
Note5.
Note6.

Indoor capacity is described as its model size;


For example, PDFY-P06NMU-E, its capacity is P06;
Total downstream Indoor capacity is the summary of the model size of Indoors downstream.
For example, PDFY-P06NMU-E+PDFY-P08NMU-E: Total Indoor capacity=P06+P08=P14
Piping sized determined by the Total downstream indoor capacity is NOT necessary
to be bigger than the upstream one.
i.e. A>=B; A>=C>=D

Y-SERIES SYSTEM DESIGN (Feb. 2009)

3. Piping Design

DATA U4

3-2-4. Farthest Indoor Unit from First Joint Requirements

Farthest Indoor unit from the first joint (ft.)

Outdoor Unit Above Indoor Unit


197
180
164
148
131
115
98
82
66
98

115

131

148

164

180

Height between Outdoor Unit and Indoor Unit (ft.)

197
180
164
148

Y-SERIES
SYSTEM DESIGN

Farthest Indoor unit from the first joint (ft.)

Outdoor Unit Below Indoor Unit

131
115
98
82
66
66

82

98

115

131

148

Height between Outdoor Unit and Indoor Unit (ft.)

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-29

3. Piping Design

DATA U4

3-2-5. PUHY-P-T(S)HMU/Y(S)HMU's calculation of additional refrigerant charge


At the time of shipping, the outdoor unit is charged with the refrigerant. As this charge does not include the amount needed
for extended piping, additional charging for each refrigerant line will be required on site. In order that future servicing may be
properly provided, always keep a record of the size and length of each refrigerant line and the amount of additional charge
by writing it in the space provided on the outdoor unit.

(1) Calculation of additional refrigerant charge


Calculate the amount of additional charge based on the length of the piping extension and the size of the refrigerant
line.
Use the table to the below as a guide to calculating the amount of additional charging and charge the system
accordingly.
If the calculation results in a fraction of less than 0.1kg[1oz], round up to the next 0.1kg[1oz]. For example, if the result
of the calculation was 12.38kg[435.1oz], round the result up to 12.4kg[436oz].
<Additional Charge>
Additional
refrigerant charge
(kg)
(oz)

Total length of liquid


=

(m) x 0.29 (kg/m)


(ft.) x 3.1 [oz/ft.]

Total length of liquid


+

(m) x 0.20 (kg/m)


(ft.) x 2.15 [oz/ft.]

Table3-2-4-1. Value of
Total capacity of connecting indoor units
Models
27
Models
28
54
Models
55 126
Models 127 144
Models 145 180
Models 181 234
Models 235 273
Models 274 307
Models 308 342
Models 343 411
Models 412 480
Models 481

Total length of liquid


+

2.0 kg
2.5 kg
3.0 kg
3.5 kg
4.5 kg
5.0 kg
6.0 kg
8.0 kg
9.0 kg
10.0 kg
12.0 kg
14.0 kg

(m) x 0.12 (kg/m)


(ft.) x 1.29 [oz/ft.]

Total length of liquid


+

(m) x 0.06 (kg/m)


(ft.) x 0.65 [oz/ft.]

Total length of liquid


+

(m) x 0.024 (kg/m)


(ft.) x 0.26 [oz/ft.]

[71 oz]
[89 oz]
[106 oz]
[124 oz]
[160 oz]
[177 oz]
[212 oz]
[283 oz]
[318 oz]
[353 oz]
[424 oz]
[494 oz]

Example: PUHY-P120THMU/YHMU
m [kg]

Y-SERIES
SYSTEM DESIGN

ft. [oz]

Indoor 1: P48
A:
40 m
a:
10 m
2: P36
B:
10 m
b:
5m
3: P15
15 m
c:
10 m
4: P12
10 m
d:
10 m
5: P24
e:
10 m
The total length of liquid pipe of each size is as follows:
12.7 : A= 40 = 40 m
9.52 : B + C + D+ a + b + e = 10 + 15 + 10 + 10 + 5 + 10 = 60 m
6.35 : c +d = 10 + 10 = 20 m

Indoor 1: P48
A:
131ft.
32ft.
2: P36
B:
32ft.
b:
16ft.
3: P15
C:
49ft.
c:
32ft.
4: P12
D:
32ft.
d:
32ft.
5: P24
e:
32ft.
The total length of liquid pipe of each line is as follows:
A= 131 = 131ft.
+ a + b + e = 32 + 49 + 32 + 32 + 16 + 32 = 193ft.

Total capacity of connecting Indoor units Pt :


Pt = P48 + P36 + P15 + P12 + P24 = P135, therefore

Total capacity of connecting Indoor units Pt :


Pt = P48 + P36 + P15 + P12 + P24 = P135, therefore

m [kg]

Additional
refrigerant charge

(kg)

ft. [oz]

P48

P36

P15

P12

x 0.29 (kg/m)

Additional
refrigerant charge

(oz)

0 (m) x 0.29 (kg/m)

x 3.1 (oz/ft.)

x 0.20 (kg/m)

Total length of liquid


+

0 (m) x 0.20 (kg/m)


+

Total length of liquid


=

x 2.15 (oz/ft.)

40 x 0.12

x 1.29 (oz/ft.)

131 x 1.29

Y-SERIES SYSTEM DESIGN (Feb. 2009)

60 x 0.06

x 0.65 (oz/ft.)

193 x 0.65

+ 3.5

20 x 0.024

+ 3.5

Total length of liquid


+

193 (ft.)x 0.65 (oz/ft.)


+

x 0.024 (kg/m)
20 (m) x 0.024 (kg/m)

Total length of liquid


+

131 (ft.) x 1.29 (oz/ft.)


+

x 0.06 (kg/m)

Total length of liquid


+

60 (m) x 0.06 (kg/m)

Total length of liquid


+

0 (ft.) x 2.15 (oz/ft.)


+

x 0.12 (kg/m)

P24

Total length of liquid


+

40 (m) x 0.12 (kg/m)

Total length of liquid


+

0 (ft.) x 3.1 (oz/ft.)

=
0
= 436 [oz]

YSD-30

Total length of liquid


+

= 124oz

=
0
= 12.4 kg

or

Total length of liquid


=

= 3.5kg

x 0.26 (oz/ft.)

+ 124

64 (ft.) x 0.26 (oz/ft.)


+

64 x 0.26

+ 124

4. Installation

DATA U4

4-1. PUHY-P-T(S)HMU/Y(S)HMUs Installation


4-1-1. PUHY-P-T(S)HMU/Y(S)HMU requirement on installation site
1.
2.
3.
4.
5.
6.
7.
8.

No direct thermal radiation to the unit;


No possibility of annoying the neighbors by the sound of the unit;
Avoid the sites where strong winds blow.
With strength to bear the weight of the unit;
Drain flow from the unit needs to be considered during heating mode;
Enough space for installation and service as shown at 4-1-2;
Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.
The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.

Y-SERIES
SYSTEM DESIGN

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-31

4. Installation

DATA U4

4-1-2. Spacing PUHY-P-T(S)HMU/Y(S)HMU


In case of single installation
Secure enough space around the unit as shown in the figure.
<A> : Top view

A : Front

C : Back

<B> : Side view

B : Unit height

D : Air outlet guide (Procured at the site)

<C> : When there is little space up to an obstruction

(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall

300*
[11-13/16]

450*
[17-23/32]

15* [19/32]

15* [19/32]

<A>
(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall

100*
[3-15/16]

50* [1-31/32]

450*
[17-23/32]

50* [1-31/32]

<A>

500

Y-SERIES
SYSTEM DESIGN

[19-11/16]

(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction

<B>
When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below,
add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.
<Wall height limit> Front: Up to the unit height
Back: Up to 500mm [19-11/16 in.] from the unit bottom
Side: Up to the unit height
(4) If there are obstacles at the upper part of the unit

1000
[39-3/8]

45
240
[9-15/32]

50 [1-31/32]
YSD-32

<C>

Y-SERIES SYSTEM DESIGN (Feb. 2009)

(Unit : mm [in.])

4. Installation

DATA U4

In case of collective installation and continuous installation


A : Front

C : Wall height (H)

B : Must be open

When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and
passageways between groups of units as shown in the figures.
At least two sides must be left open.

300*
300*
[11-13/16] [11-13/16]

100*
[3-15/16]

30
[1-3/16]

450*
[17-23/32]

900
[35-7/16]

B
A

900
[35-7/16]

300*
[11-13/16]

300*
[11-13/16]

As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
an asterisk.

100
[3-15/16]

450*
[17-23/32]

B
A

450

450

Y-SERIES
SYSTEM DESIGN

450*

[17-23/32]

1000*
[39-3/8]

100*

[17-23/32] [17-23/32] [3-15/16]

15*

450
450
[17-23/32] [17-23/32]

(Unit : mm [in.])

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-33

4. Installation

DATA U4

4-1-3. Piping direction to PUHY-P-T(S)HMU/Y(S)HMU


4-1-3-1. Lifting method
When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.
Support the unit at four points with two ropes, and avoid giving mechanical shock.
Suspension rope angle must be 40 or less, so as to avoid compressing fan guard.
Use two ropes, each at least 8m [26 ft.] in length
Use ropes strong enough to support the weight of the unit.
Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempted.)
Use protective pads to keep the ropes from scratching the panels on the unit.

8 [26]

40

Y-SERIES
SYSTEM DESIGN

8 [26]

CAUTION
Exercise caution when transporting products.
Products weighing more than 20 kg [45 LBS] should not be carried alone.
Do not carry the product by the PP bands.
To avoid the risk of injury, do not touch the heat exchanger fins.
Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.
When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.

YSD-34

Y-SERIES SYSTEM DESIGN (Feb. 2009)

4. Installation

DATA U4

4-1-3-2. Installation
Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or
during an earthquake.
Install the unit on a durable base made of such materials as concrete or angle steel.
Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
noise from being transmitted from the unit through walls and floors.
When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.
Install the anchor bolt in such a way that the top end of the anchor bolt does not stick out more than 30 mm [1-3/16 in.].
This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.

WARNING
A

: M10 anchor bolt procured at the site.

: Corner is not seated.

: Fixing bracket for hole-in anchor bolt


(3 locations to fixwith screws).

: Detachable leg
30mm
[1-3/16 in.]

<Without detachable leg>

Properly install the unit on a surface that can withstand the weight of
the unit. Unit installed on an unstable surface may fall and cause injury.

WARNING
Take appropriate safety measures against strong winds and earthquakes to prevent the unit from falling.

Install the unit in such a


way that the corner of
the angle bracket at the
base of the unit shown
in the figure is securely
supported. The brackets
may bend if they are not
securely supported.

Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor units
during operation.), piping route, and wiring route when performing foundation work.

4-1-3-3. Anchor bolt positions

30 [1-3/16]
190 [7-1/2]

(For maintenance)

30 [1-3/16]
190 [7-1/2]

Leave a minimum of 30 mm [1-3/16 in.] between units.

PUHY
A

P72, P96

P120

7602 [29-15/16(29-27/32~30)] 10602 [41-3/4(41-21/32~41-13/16)]

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-35

Y-SERIES
SYSTEM DESIGN

7243 [(28-13/32~28-5/8)]

Collective installation

7243 [(28-13/32~28-5/8)]

Individual installation

4. Installation

DATA U4

4-1-3-4. Installation <PUHY-P-T(S)HMU/Y(S)MHU>


When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height.

760 [29-15/16]
80
(Mounting pitch) [3-5/32]

Bottom view

2X2-14X20
[1/8x1/8-9/16x13/16]
Oval hole

Refrigerant service
valve <liquid>

18
[23/32]

Refrigerant service
valve <gas>
80
[3-5/32]

1060 [41-3/4]
(Mounting pitch)

80
[3-5/32]

Bottom view

Installation base parallel to the units front panel

724(721 727)
[28-13/32~28-5/8]
(Mounting pitch)
(760 [29-15/16])

94 [3-23/32]

145 [5-23/32]
131 [5-3/16]

(Mounting pitch)
(760 [29-15/16])

(Unit : mm [in.])
150
[5-29/32]
83
[3-9/32]

18
[23/32]

80
[3-5/32]

724(721 727)
[28-13/32~28-5/8]

18
[23/32]

86 [3-13/32]

Refrigerant service
valve <gas>

18
[23/32]

Refrigerant service
valve <liquid>

271
[10-11/16]
301
[11-7/8]
216
[8-17/32]

2X2-14X20
[1/8x1/8-9/16x13/16]
Oval hole

92 [3-5/8]

145 [5-23/32]

131 [5-3/16]

145 [5-23/32]

251 83
[9-29/32] [3-9/32]
186
[7-11/32]

P120

84 [3-5/16]

(Unit : mm [in.])

221 150
[8-23/32] [5-29/32]

145 [5-23/32]

P72, P96

Installation base perpendicular to the units front panel

4-1-3-5. Refrigerant pipe routing <PUHY-P-T/Y(S)MHU>


A Example of closure materials (field-supplied)
B Fill the gap at the site

Y-SERIES
SYSTEM DESIGN

Make sure to seal-off the space around


areas where the wires and refrigerant
pipes enter the unit to ensure that small
animals, rainwater, or snow cannot enter
the unit through such openings and cause
damage to the unit.
This unit allows two types of pipe routing:
Bottom piping
Front piping
Caution:
A

YSD-36

Make sure to seal-off the openings for the pipe and wire retrieval.
Small animals, rainwater, or snow entering through the openings may
cause damage to the device.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

4. Installation

DATA U4

4-1-3-6. Twinning on the outdoor unit side <PUHY-P-T(S)HMU/Y(S)HMU>


The tilt angle of the twinning pipe
The tilt angle of the twinning pipe must be within 15 with the horizontal plane.
Tilting the twinning pipe more than specified will cause damage to the unit.
The length of the straight part of the pipe before the branching
For the twinning kit, always use the accessory piping parts.
The length of the straight part of pipe connected in front of the
twinning pipe must be 500 mm [19 in.] or longer.
(Connect the field piping so that the length of the straight part
of pipe connected in front of the twinning pipe can be 500 mm
[19 in.] or longer.)
If the length is less than 500 mm [19 in.], it will cause damage
to the unit.

15

Note: See the following drawing for the fitting


position of the twinning pipe.
Reducer

The tilt angle of the reducer should be


within 15with the horizontal plane.

The piping connection


When connecting the twinning kit to the outdoor unit, note the following:
If the length of piping from the twinning kit to the outdoor unit is more than 2 m [6 ft.],
install a trap within 2 m [6 ft.] from the outdoor unit. The height of the trap must be 200
mm [7 in.] or higher.
Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).
<More than 2 m [6 ft.]>

<2 m [6 ft.] or less>

Trap
(gas pipe only)
200 mm [7 in.]
or over

To Indoor unit
2m [6 ft.]

To Indoor unit

To Indoor unit

Less than 2 m [6 ft.]

When installing the twinning kit in a higher position than the outdoor unit base, make
sure that the twinning kit is installed higher than 200 mm [7 in.] above the outdoor unit
base.

<PUHY-P144TSHMU/YSHMU>

Outdoor unit 1

Outdoor unit 2

Twinning pipe1
To Indoor unit
200 mm [7 in.]
or less

Y-SERIES
SYSTEM DESIGN

<PUHY-P264TSHMU/YSHMU>
Outdoor unit 1

Outdoor unit 2

Twinning pipe 1

Outdoor unit 3

Twinning pipe 2

To Indoor unit
200 mm [7 in.]
or less

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-37

4. Installation

DATA U4

4-1-3-7. Twinning on the outdoor unit side <PUHY-P-T/Y(S)HMU>


See the following drawing for connecting the pipes between the outdoor units.
<PUHY-P144TSHMU/YSHMU>

Field piping
Twinning kit

Field piping

The
le
mus ngth of
t be
t
500 he straig
mm
h
[19 i t pipe
n.] o
r lon
ger

<PUHY-P264TSHMU/YSHMU>

Field piping

Twinning kit

Field piping

Y-SERIES
SYSTEM DESIGN

The
le
Twinning kit
mus ngth of
t be
t
500 he straig
mm
h
[19 i t pipe
n.] o
r lon
ger

CAUTION
The length of the straight pipe must be 500mm[19in.] or longer.
If not, it may cause improper operation.

YSD-38

Y-SERIES SYSTEM DESIGN (Feb. 2009)

Field piping
The
le
mus ngth of
t be
t
500 he straig
mm
h
[19 i t pipe
n.] o
r lon
ger

4. Installation

DATA U4

4-1-4. Weather countermeasure for PUHY-P-T(S)HMU/Y(S)HMU


In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in
normal and good condition in winter time. Even in the other areas, full consideration is required for installation of unit in order
to prevent abnormal operations caused by wind or snow. When rain and snow directly fall on unit in the case of air-conditioning
operations in 10 or less degrees centigrade outdoor air (50 or less degrees fahrenheit outdoor air) , mount inlet and outlet ducts
on unit for assuring stable operations.
Countermeasure to snow and wind
Prevention the Outdoor unit from wind and snow damages in cold or snowy areas, snow hood shown below is recommended
and helpful.
Snow hood
1206 [47-1/2]

906 [35-11/16]

800 [31-1/2]

800 [31-1/2]

750 [29-17/32]

(920)[36-1/4]

1324 [52-5/32]

453
[17-27/32]

453
760 [29-15/16] [17-23/32]

<Side view>

Outlet

B
B

86
[3-13/32]

(760)
[29-15/16]

86
[3-13/32]

1324 [52-5/32]

(1220)[48-1/16]

910 [35-27/32]

<Front view>

453
[17-27/32]

453
[17-27/32]

1210 [47-21/32]

453
[17-27/32]

<Front view>

Inlet

Wind

Install the outdoor unit where seasonal


winds do not blow directly against the
unit, such as behind a building.

Install the outdoor unit to avoid having


seasonal winds against the front of air
outlet/inlet on the unit.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-39

Y-SERIES
SYSTEM DESIGN

Note:
1. Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base
shall not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind
slip through the structure. (If frame base is too wide, snow will be accumulated on it.)
2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3. Build frame base at customer referring to this figure.
Material : Galvanized steel plate 1.2T [1/16 in. T]
Painting : Overall painting with polyester powder
Color : Munsell 5Y8/1 (same as that of unit)
4. To install units side by side, install a filler plate between
the fan guard and the outlet-side snow hood as shown in Figure A.
(The filler plate provided accommodates the installation pitch of between 30-80 mm [1-3/16~3-5/32 in.].)
5. When the unit is used in a cold region and the heating operation is continuously
Figure A
performed for a long time when the outside air temperature is below freezing, install
Filler plate
a heater to the unit base or take other appropriate measures to prevent water from freezing on the base.
Countermeasure to wind
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.
A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.
To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away
from the direction of the wind.

5. Standard and Seacoast Protection (-BS) TreatMenT


5-1. Y-Series
Component

Base Material

Standard
Models

Seacoast
Protection
Models (-BS)

External Panel Base

Alloyed Galvanized Steel


Sheet

External Front Panel

Alloyed Galvanized Steel


Sheet

Alloyed Galvanized Steel


Sheet

Pillar

Galvanized Steel Sheet


Compressor Cover

Galvanized Aluminum
Sheet

External Surface

Internal Surface

Thermoset Polyester-resin
Powder Coating

70m

70m

Polyester-resin Coating

15m

5m

Thermoset Polyester-resin
Powder Coating

85m

75m

Polyester-resin Coating

30m

Thermoset Polyester-resin
Powder Coating

70m

70m

Thermoset Polyester-resin
Powder Coating

70m

70m

300m

300m

Thermoset Polyester-resin
Powder Coating

70m

70m

Cellulose- and Polyurethaneresin Coating (Blue Fin)


(no unusual rust development
to 480 hours)

1m

Cellulose- and Polyurethaneresin Coating (Blue Fin)


(no unusual rust development
to 960 hours)

1 - 1.5m

Fin Guard

Steel Wires

Weather-resistant
Polypropylene-resin Coating

Fan Guard and Drum

Weather-resistant
Polypropylene Plastic

No Treatment

Fan

Weather-resistant Acrylic
Nitrile Styrene Plastic

Fan Motor Frame

Galvanized Steel Sheet

Fan Motor Shaft

High-carbon S35C Steel

Fan Motor Support

Galvanized Steel Sheet

Heat Exchanger
(Fin Only)

Galvanized Steel Sheet


Galvanized Aluminum
Sheet

Printed Circuit Board

Epoxy Resin

Screws

10m

Zinc-nickel Alloy Plating with


a Chromate Film

5m

Thermoset Polyester-resin
Powder Coating

Cellulose- and Polyurethaneresin Coating (Blue Fin)

Test
Conditions

Salt-spray Test Method: JIS


K2371 based on ISO9227

Salt-spray Test Method: JIS Z2371


based on ISO9227

YSD-40

70m

Polyurethane Coating

Material

No unusual rust
development to
480 hours

Thermoset Polyester-resin
Powder Coating

Distance from the Sea


984 (300m)
1,640 (500m)
3,281 (1km)
Direct Exposure to Sea Breezes
Facing Inland Seacoast Protection (-BS) Models Standard Models
Facing Sea
Seacoast Protection (-BS) Models
On an Island
Seacoast Protection (-BS) Models
Indirect Exposure to Sea Breezes
Facing Inland Seacoast Protection (-BS) Models Standard Models
Facing Sea
Seacoast Protection (-BS) Models
On an Island
Seacoast Protection (-BS) Models

Conform to JRA9002 Criteria


(960-hour test)

Rust-prevention Coating

No Treatment

Application Guide

Test
Results

No Treatment

No Treatment

Steel

No Treatment

No Treatment

Aluminum Plate

Electrical Parts Box

Coating Thickness

No Treatment

Y-SERIES
SYSTEM DESIGN

Surface
Treatment

DATA U4

No unusual rust
development to
960 hours

For optimum performance, follow the cautions


listed below.
1. Avoid installing the unit in a location that is
subjected to direct sea winds.
2. Do not attach a sunshade to the unit. Let the rain
wash away any salt residue that may adhere to the
unit.
3. Unit should be installed following instructions
for proper operation and to ensure optimum water
drainage.
4. Periodically wash the unit.
5. If the panels become scratched, repair as soon as
possible.
6. Inspect the unit at regular intervals. Paint the unit
or replace parts when necessary.

Blue Fin treatment is an anti-corrosion treatment that


is applied to the condenser coil to protect it against
airborne contaminants.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

6. Cautions

DATA U4

The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.
The following standard may be applicable if no local regulation or standard is available.

6-1. Refrigerant Properties


R410A refrigerant is harmless and incombustible. R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room
has possibility to lead to a hypoxia situation. Therefore, the critical concentration specified below shall not be exceeded even if the leakage
happens.

Critical concentration
Critical concentration is the maximum refrigerant concentration at which no harm would occur if immediate measures are taken
when refrigerant leakage happens.
Critical concentration of R410a: 0.30kg/m3 [0.0187 lbs./ft3]
(The weight of refrigeration gas per 1 m3 [1 ft3] air conditioning space.);
The critical concentration is per ISO5149, EN378-1 (other codes and standards may establish different values for critical concentration).

For CITY MULTI systems, the concentration of refrigerant leaked should not exceed the critical concentration in any situation.

6-2. Confirm the Critical Concentration and Perform Countermeasures


The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)
leaked into a room divided by its room capacity (V). See Fig. 5-1. The refrigerant weight includes its original charge and additional
charge at the site.
The additional charge is calculated according to 3-2-4."PUHY-P-T(S)HMU/Y(S)HMU's refrigerant charging calculation", and shall not be
over charged at the site. Procedure 6-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take
countermeasures against a possible leakage.
Outdoor unit (No.1)

Outdoor unit (No.1)

Outdoor unit (No.2)

Flow of refrigerant

Flow of refrigerant

Indoor unit

Flow of refrigerant

Indoor unit

Maximum refrigerant leakage concentration (Rmax)


Rmax=Wmax / V

Maximum refrigerant leakage concentration (Rmax)


Rmax=Wmax / V
W1: Refrigerant weight of Outdoor unit No.1
where, Wmax=W1+W2 W2: Refrigerant weight of Outdoor unit No.2

Refrigerant pipe (high pressure pipe)

Ventilation air supply fan (always ON)


Refrigerant pipe

Ventilation air supply fan

Ventilation air supply fan

to Outdoor unit

Indoor unit
Indoor space

(Floor)

(Floor)
Opening

Indoor space

Indoor unit

(Floor)
Opening

Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


[At 0.3m height from the floor]

Fig. 6-2. Ventilation air supply always ON

to Outdoor unit

to Outdoor unit

Indoor unit
Indoor space

Refrigerant stop valve

Refrigerant pipe

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


[At 0.3m height from the floor]

Fig. 6-3. Ventilation air supply upon sensor action Fig. 6-4. Ventilation air supply and refrigerant
shut-off upon sensor action

Note 1. Countermeasure 3 should be done in a proper way in which the ventilation air supply shall be on whenever the leakage happens .
Note 2. In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.
The piping should consider the extension due to the temperature variation.

Y-SERIES SYSTEM DESIGN (Feb. 2009)

YSD-41

Y-SERIES
SYSTEM DESIGN

Fig. 6-1 The maximum refrigerant leakage concentration


6-2-1.Find the room capacity (V),
If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space are
considered as one. The total space shall be added up.
6-2-2.Find the possible maximum leakage (Wmax) in the room. If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refrigerant of the Outdoor units.
6-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).
6-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3 [0.0187 lbs./ft.3 ].
If no, then the CITY MULTI is safe against refrigerant leakage.
If yes, following countermeasure is recommended to do at site.
Countermeasure 1: Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.
e.g. make the upper and lower seams of door big enough.
Countermeasure 2: Smaller total charge (making Wmax smaller)
e.g. Avoid connecting more than 1 Outdoor unit to one room.
e.g. Using smaller model size but more Outdoor units.
e.g. Shorten the refrigerant piping as much as possible.
e.g. Remove unit from space.
Countermeasure 3: Ventilation air in from the ceiling.
As the density of the refrigerant is bigger than that of the air. Ventilation air from the ceiling is better than air exhausting from the ceiling.
Ventilation air supply solution refers to Fig. 6-2~4.

DATA U4

CITY MULTI R2-SERIES


System Design
1. Electrical work............................................................................................................................................. R2SD-2
1-1. General Cautions......................................................................................................................................... R2SD-2
1-2. Power Supply for Indoor Unit and Outdoor Unit........................................................................................... R2SD-3
1-3. Power Cable Specifications.......................................................................................................................... R2SD-7
1-4. Power Supply Examples.............................................................................................................................. R2SD-8
2. M-NET control............................................................................................................................................... R2SD-10
2-1. Transmission Cable Length Limitation........................................................................................................ R2SD-10
2-2. Transmission Cable Specifications............................................................................................................. R2SD-11
2-3. System Configuration Restrictions............................................................................................................. R2SD-12
2-4. Address Setting.......................................................................................................................................... R2SD-15
3. Piping Design.................................................................................................................................................. R2SD-26
3-1. R410A Piping Material............................................................................................................................... R2SD-26
3-2. PURY-P-T/Y(S)HMUs Piping Design......................................................................................................... R2SD-27
4. Installation..................................................................................................................................................... R2SD-33
4-1. PURY-P-T/Y(S)HMUs Installation.............................................................................................................. R2SD-33
5. Standard and Seacoast Protection (-BS) Treatment..................................................................... R2SD-42
5-1. R2-Series................................................................................................................................................... R2SD-42
6. CautionS........................................................................................................................................................... R2SD-43
6-1. Refrigerant Properties................................................................................................................................ R2SD-43
6-2. Confirm the Critical Concentration and Perform Countermeasures........................................................... R2SD-43

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-1

1. Electrical Work

DATA U4

1-1. General Cautions


Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 100V, 208~230,460V power source to terminal block of transmission cable. If connected,electrical parts will
be burnt out.
Use 2-core shield cable for transmission cable . If transmission cables of different systems are wired with the same
multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.

Indoor unit

Outdoor
unit

OK
2-core shield cable

NO
Multiplecore cable

Remote
controller
Indoor unit
BC controller

Outdoor
unit

Indoor unit

Outdoor
unit

Outdoor
unit

Remote
controller

BC controller

Indoor unit

2-core shield cable

R2-SERIES
SYSTEM DESIGN

Remote
controller

R2SD-2

R2-SERIES SYSTEM DESIGN (Feb. 2009)

Remote
controller

1. Electrical Work

DATA U4

1-2. Power Supply for Indoor Unit and Outdoor Unit

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-3

1. Electrical Work

PVFY-P12E00A
PVFY-P18E00A
PVFY-P24E00A
PVFY-P30E00A
PVFY-P36E00A

R2-SERIES
SYSTEM DESIGN

PVFY-P48E00A
PVFY-P54E00A

R2SD-4

R2-SERIES SYSTEM DESIGN (Feb. 2009)

DATA U4

0.86 / 0.76
1.85 / 1.64
1.85 / 1.64
2.97 / 2.64

0.262 / 0.262

0.69 / 0.61

0.384 / 0.384
0.384 / 0.384
0.342 / 0.342

1.48 / 1.31
1.48 / 1.31

2.41 / 2.14
2.84 / 2.51
3.53 / 3.14

0.236 / 0.236
0.196 / 0.196
0.210 / 0.210

2.38 / 2.11
1.93 / 1.71
2.27 / 2.01
2.83 / 2.51

1. Electrical Work

DATA U4

1-2-2. Electrical characteristics of Outdoor unit at cooling mode


PURY-P-THMU

Symbols: MCA : Min. Circuit Amps


SC : Starting Current

RLA : Rated Load Amps

Outdoor units

Compressor

Fan

Model

Unit combination

PURY-P72THMU-A(-BS)

14.9/13.5 24/22

30

4.4

15

0.92

PURY-P96THMU-A(-BS)

23.5/21.3 35/32

40

7.0

15

0.92

PURY-P120THMU-A(-BS)

30.5/27.5 43/40

50

8.1

15

0.92

PURY-P72THMU-A(-BS)

14.9/13.5 24/22

30

4.4

15

0.92

PURY-P72THMU-A(-BS)

14.9/13.5 24/22

30

4.4

15

0.92

PURY-P72THMU-A(-BS)

14.9/13.5 24/22

30

4.4

15

0.92

23.5/21.3 35/32

40

7.0

15

0.92

PURY-P96THMU-A(-BS)

23.5/21.3 35/32

40

7.0

15

0.92

PURY-P96THMU-A(-BS)

23.5/21.3 35/32

40

7.0

15

0.92

PURY-P96THMU-A(-BS)

23.5/21.3 35/32

40

7.0

15

0.92

PURY-P120THMU-A(-BS)

30.5/27.5 43/40

50

8.1

15

0.92

PURY-P120THMU-A(-BS)

30.5/27.5 43/40

50

8.1

15

0.92

PURY-P120THMU-A(-BS)

30.5/27.5 43/40

50

8.1

15

0.92

PURY-P144TSHMU-A(-BS)
PURY-P168TSHMU-A(-BS)
PURY-P192TSHMU-A(-BS)
PURY-P216TSHMU-A(-BS)
PURY-P240TSHMU-A(-BS)

PURY-P96THMU-A(-BS)

Hz

60Hz

Volts

Voltage range

208 / 230V 188 to 253V

RLA(A)

MCA(A) Max. Fuse(A) Output(kW) SC(A) Output(kW)

PURY-P-YHMU
Compressor

Outdoor units

Fan

Model

Unit combination

PURY-P72YHMU-A(-BS)

6.7

11

15

4.4

0.92

PURY-P96YHMU-A(-BS)

10.6

16

20

7.0

0.92

PURY-P120YHMU-A(-BS)

13.7

20

25

8.1

0.92

PURY-P72YHMU-A(-BS)

6.7

11

15

4.4

0.92

PURY-P72YHMU-A(-BS)

6.7

11

15

4.4

0.92

PURY-P72YHMU-A(-BS)

6.7

11

15

4.4

0.92

PURY-P144YSHMU-A(-BS)
PURY-P168YSHMU-A(-BS)
PURY-P192YSHMU-A(-BS)
PURY-P216YSHMU-A(-BS)
PURY-P240YSHMU-A(-BS)

PURY-P96YHMU-A(-BS)

Hz

60Hz

Volts

Voltage range

460V

414 to 506V

RLA(A)

MCA(A) Max. Fuse(A) Output(kW) SC(A) Output(kW)

10.6

16

20

7.0

0.92

PURY-P96YHMU-A(-BS)

10.6

16

20

7.0

0.92

PURY-P96YHMU-A(-BS)

10.6

16

20

7.0

0.92

PURY-P96YHMU-A(-BS)

10.6

16

20

7.0

0.92

PURY-P120YHMU-A(-BS)

13.7

20

25

8.1

0.92

PURY-P120YHMU-A(-BS)

13.7

20

25

8.1

0.92

PURY-P120YHMU-A(-BS)

13.7

20

25

8.1

0.92

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-5

1. Electrical Work

DATA U4

1-2-3. Electrical characteristics of BC controller


Symbols: MCA : Min.Circuit Amps (=1.25 x RLA) MOCP : Maximum Overcurrent Protection
RLA : Rated Load Amps
BC-Controller for PURY-P-THMU, PURY-P-YHMU

CMB-P105NU-G
CMB-P106NU-G
CMB-P108NU-G
CMB-P1010NU-G
CMB-P1013NU-G
CMB-P1016NU-G
CMB-P108NU-GA
CMB-P1010NU-GA
CMB-P1013NU-GA
CMB-P1016NU-GA
CMB-P104NU-GB
CMB-P108NU-GB
CMB-P1016NU-HB

Hz

60Hz

Volts

208 / 230V

Voltage range

198 to 253V

188 to 253V

R2-SERIES
SYSTEM DESIGN

R2

Model

R2SD-6

R2-SERIES SYSTEM DESIGN (Feb. 2009)

MCA(A)

MOCP

RLA(A)

0.45 / 0.40
0.53 / 0.48
0.68 / 0.61
0.84 / 0.75
1.08 / 0.98
1.31 / 1.19
0.68 / 0.61
0.84 / 0.75
1.08 / 0.98
1.31 / 1.19
0.33 / 0.30
0.64 / 0.59
1.89 / 1.71

15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15
15 / 15

0.36 / 0.32
0.42 / 0.38
0.54 / 0.49
0.67 / 0.60
0.86 / 0.78
1.05 / 0.95
0.54 / 0.49
0.67 / 0.60
0.86 / 0.78
1.05 / 0.95
0.26 / 0.24
0.51 / 0.47
1.51 / 1.37

1. Electrical Work

DATA U4

1-3. Power Cable Specifications


Thickness of wire for main power supply, ON / OFF capacities
3-phase 3-wire, 208/230V,60Hz
PURY-P-THMU-A

P72
P96
P120

Indoor unit
3-phase 3-wire, 460V,60Hz
PURY-P-YHMU-A
Indoor unit

P72
P96
P120

Minimum wire thickness (mm2 / AWG)


Main cable
Branch
Ground
5.3/10
5.3/10
13.3/6
13.3/6
21.2/4
21.2/4
2.1/14
2.1/14
2.1/14

Switch (A)
Capacity
Fuse
30
30
40
40
50
50
15
15

Breaker for
wiring (NFB)
30
40
50
15

30A 30mA or 100mA 0.1sec. or less


40A 100mA 0.1sec. or less
50A 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less

Minimum wire thickness (mm2 / AWG)


Main cable
Branch
Ground
2.1/14
2.1/14
3.3/12
3.3/12
5.3/10
5.3/10
2.1/14
2.1/14
2.1/14

Switch (A)
Capacity
Fuse
15
15
20
20
25
25
15
15

Breaker for
wiring (NFB)
15
20
25
15

15A 30mA or 100mA 0.1sec. or less


20A 30mA or 100mA 0.1sec. or less
25A 30mA or 100mA 0.1sec. or less
20A 30mA or 100mA 0.1sec. or less

Breaker for current leakage

Breaker for current leakage

1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum v alue f or metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1 / 8 in] contact separation in each pole shall be provided by the Air conditioner installation.

WARNING
Be sure to use specified wires to connect so that no external force is impar ted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated over current may include some amount of direct current.

CAUTION
A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-7

1. Electrical Work

DATA U4

1-4. Power Supply Examples


The local standards and/or regulations is applicable at a higher priority.

1-4-1. PURY-P72, 96, 120THMU/YHMU


Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol
means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC50KUA should be used. The transmission cable (above 1.25mm2
[16AWG] shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is
called central control transmission cable. The shield wire of the central control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40.
5 MA R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less than 200m (656 ft.)
in length, while ME R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less
than 10m (32 ft.) in length. But transmission cable to the ME R/C can be extend using a
M-NET cable (>=1.25mm2 [16AWG]) when the length is counted in the M-Net length.
Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 (18-16AWG) in
thickness.
6 MA remote controller and ME remote controller should not be grouped together.
7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.

<In the case a system controller is connected.>


Note12

Central control
transmission cable
>=1.25mm2 (16AWG)
Shield cable
(CVVS, CPEVS
MVVS)

SC

Connector
CN41 CN40 OU
Note4

Note4
To other OU

Breakers for
current leakage Switch

TB1
TB3 TB7
(L1,L2,L3) (M1,M2) (M1,M2)

Power supply
3-phase 3-wire
208-230V 60Hz(THMU)
460V 60Hz(YHMU)
Note10,13

TB7
(S)

Note3

To *1 or *2
BC controller
*1

TB02
(M1,M2)

TB01
S L,N
(Shield)

(Using MA remote controller)


Connecting TB5 terminal.

Pull box

Breakers for
current leakage Switch

Power supply
1-phase
208-230V 60Hz
Note10
* Power supply
specifications vary with the
model of connected indoor
units or BC controller

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable

Breakers for
current leakage

Power supply
1-phase
208-230V 60Hz

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Note6
Note7
MA R/C

MA R/C

Switch

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
MA R/C cable
(Shield)
0.3-1.25mm2
(22-16AWG)
S
S
(0.75~1.25mm2
(Shield)
(Shield)
[18-16AWG])
<=200m (656 ft.)
Transmission
Note 5, Note11
booster
Note8
Note9
MA R/C
TB1
(R,S) E
TB2 TB3

BC controller
*2

TB02
(M1,M2)

TB01
S L,N
(Shield)

(Using ME remote controller)


Connecting TB5 terminal.

Pull box

Breakers for
current leakage Switch

Power supply
1-phase
208-230V 60Hz
Note10
* Power supply
specifications vary with the
model of connected indoor
units or BC controller

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable

R2-SERIES
SYSTEM DESIGN

ME R/C

Symbol

Model

BKC
OCP

Breaker capacity
Over-current protector

NFB
OU
IU
SC

Non-fuse breaker
Outdoor unit
Indoor unit
System controller

MA R/C

MA remote controller

ME R/C

ME remote controller

R2SD-8

PURY-P72THMU
PURY-P96THMU
PURY-P120THMU
PURY-P72YHMU
PURY-P96YHMU
PURY-P120YHMU

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for
current leakage

Power supply
1-phase
208-230V 60Hz

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Note6
Note7
ME R/C

Breakers for current leakage


*1, *2

30 A 30 mA or 100 mA 0.1 sec. or less


40 A 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less
15 A 30 mA or 100 mA 0.1 sec. or less
20 A 30 mA or 100 mA 0.1 sec. or less
25 A 30 mA or 100 mA 0.1 sec. or less

*1 The breakers for current leakage should support Inverter circuit.


*2 Breakers for current leakage should combine using of switch.
*3 It shows data for B-type fuse of the breaker for current leakage.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

Switch

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)
ME R/C cable
0.3~1.25mm2
(Shield) S S (Shield)
(22-16AWG)
(0.75~1.25mm2
Transmission
[18-16AWG])
booster
<=10m (32 ft.)
Note8
Note5, Note11
Note9
TB1
(R,S) E
TB2 TB3

ME R/C

Switch

Switch

Minimum Wire thickness

BKC
<A>

OCP*3
<A>

(NFB)
<A>

Power wire
<mm2/AWG>

G wire
<mm2/AWG>

30
40
50
15
20
25

30
40
50
15
20
25

30
40
50
15
20
25

5.3/10

5.3/10

13.3/6
21.2/4
2.1/14
3.3/12
5.3/10

13.3/6
21.2/4
2.1/14
3.3/12
5.3/10

1. Electrical Work

DATA U4

The local standards and/or regulations is applicable at a higher priority.

1-4-2. PURY-P144, 168, 192, 216, 240TSHMU/YSHMU


<In the case a system controller is connected.>
Note12

Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol
means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected together.
The broken line at the scheme means shield wire.
4 When the Outdoor unit connected with system controller, power-supply to TB7 of the
outdoor unit(s) is needed. The connector change from CN41 to CN40 at one of the
outdoor units will enable the outdoor unit to supply power to TB7, or an extra power
supplying unit PAC-SC50KUA should be used. The transmission cable (above 1.25mm2
[16AWG] shielded, CVVS/CPEVS/MVVS) among Outdoor units and system controllers is
called central control transmission cable. The shield wire of the central control
transmission cable must be grounded at the Outdoor unit whose CN41 is changed to
CN40.
5 MA R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less than 200m (656 ft.)
in length, while ME R/C transmission cable (0.3-1.25mm2 [ 22-16AWG]) must be less
than 10m (32 ft.) in length. But transmission cable to the ME R/C can be extend using a
M-NET cable (>=1.25mm2 [16AWG]) when the length is counted in the M-Net length.
Both Compact MA and ME R/C transmission cables size 0.75~1.25mm2 (18-16AWG) in
TB7
thickness.
(S)
6 MA remote controller and ME remote controller should not be grouped together.
7 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 2-4. "Address
Setting".
8 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 2-3 "System configuration restrictions".
9 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
10 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
11 Numbers shown with ( ) indicates a diameter of the compact remote controller.
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.

Central control
transmission cable
>=1.25mm2 (16AWG)
Shield cable
(CVVS, CPEVS
MVVS)

SC

Connector
CN41 CN40 OU
Note4

Note4

OU

To other OU
Breakers for
current leakage Switch
Power supply
3-phase 3-wire
208-230V 60Hz(THMU)
460V 60Hz(YHMU)
Note10,13

TB1

TB1
TB3 TB7
(L1,L2,L3) (M1,M2) (M1,M2)

TB7
(S)

TB3
TB7
(M1,M2) (M1,M2)

Breakers for
(L1,L2,L3)
current leakage Switch
Power supply
3-phase 4-wire
208-230V 60Hz(THMU)
460V 60Hz(YHMU)
Note10,13

G
Note3

Note3
To *1 or *2
BC controller(Main)

BC controller(Sub)

TB02
(M1,M2)

*1

TB01
S L,N
(Shield)

(Using MA remote controller)


Connecting TB5 terminal.

TB02
(M1,M2)
G

Breakers for
current leakage Switch

Pull box

Power supply
1-phase
208-230V 60Hz
Note10
* Power supply
specifications vary with the
model of connected indoor
units or BC controller

Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for

Power supply current leakage Switch


1-phase
208-230V 60Hz
TB1
(R,S) E
TB2 TB3

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
MA R/C cable
(Shield)
0.3-1.25mm2
(22-16AWG)
S
S
(Shield)
(Shield)
(0.75~1.25mm2
[18-16AWG])
<=200m (656 ft.)
Transmission
Note 5, Note11
booster
Note8
Note9
MA R/C

Note6
Note7
MA R/C

MA R/C

BC controller(Main)
TB02
(M1,M2)

*2
(Using ME remote controller)
Connecting TB5 terminal.

TB01
S L,N

TB02
(M1,M2)
G

TB01
S L,N

(Shield)
Pull box
Note7
TB5 TB2 TB15
(M1,M2) (L,N) (1,2)
S
(Shield)
IU

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

Breakers for

Power supply current leakage Switch


1-phase
208-230V 60Hz
TB1
(R,S) E
TB2 TB3
(Shield)

Indoor-outdoor
transmission cable
>=1.25mm2 (16AWG)
Shield cable
ME R/C

Model

Symbol

Breaker capacity
Over-current protector

NFB
OU
IU
SC

Non-fuse breaker
Outdoor unit
Indoor unit
System controller

MA R/C

MA remote controller

ME R/C

ME remote controller

PURY-P72THMU
PURY-P96THMU
PURY-P120THMU
PURY-P72YHMU
PURY-P96YHMU
PURY-P120YHMU

TB5 TB2 TB15


(M1,M2) (L,N) (1,2)
S
(Shield)

(Shield)

Transmission
booster
Note8
Note9

Note6
Note7
ME R/C

ME R/C cable
0.3~1.25mm2
(22-16AWG)
(0.75~1.25mm2
[18-16AWG])
<=10m (32 ft.)
Note5, Note11

ME R/C

Breakers for current leakage


*1, *2

30 A 30 mA or 100 mA 0.1 sec. or less


40 A 100 mA 0.1 sec. or less
50 A 100 mA 0.1 sec. or less
15 A 30 mA or 100 mA 0.1 sec. or less
20 A 30 mA or 100 mA 0.1 sec. or less
25 A 30 mA or 100 mA 0.1 sec. or less

Switch

Switch

Minimum Wire thickness

BKC
<A>

OCP*3
<A>

(NFB)
<A>

Power wire
<mm2/AWG>

G wire
<mm2/AWG>

30
40
50
15
20
25

30
40
50
15
20
25

30
40
50
15
20
25

5.3/10

5.3/10

13.3/6
21.2/4
2.1/14
3.3/12
5.3/10

13.3/6
21.2/4
2.1/14
3.3/12
5.3/10

*1 The breakers for current leakage should support Inverter circuit.


*2 Breakers for current leakage should combine using of switch.
*3 It shows data for B-type fuse of the breaker for current leakage.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-9

R2-SERIES
SYSTEM DESIGN

BKC
OCP

BC controller(Sub)

Breakers for
current leakage Switch

Power supply
1-phase
208-230V 60Hz
Note10
* Power supply
specifications vary with the
model of connected indoor
units or BC controller

TB01
S L,N

2. M-NET Control

DATA U4

2-1. Transmission Cable Length Limitation


2-1-1. Using MA Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7
<=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from MA to Indoor
a1+a2, a1+a2+a3+a4, a1
<=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]
DC 24V to AG-150A
n
<=10m[32ft.]
0.75-2.0 mm2 [AWG18-14]
L8

L1

Group1

Group3

Group5

OS

OC

BC(Main)

IC

IC

BC(Sub)

IC

IC

(52)

(51)

(53)

(01)

(04)

(55)

(05)

(06)

TB3
M1M2

TB3
M1M2

TB02
M1M2 S

TB5
M1M2 S

TB15
1 2

TB5
M1M2 S

TB15
1 2

TB02
M1M2 S

TB5
M1M2 S

TB15
1 2

TB15
1 2

TB5
M1M2 S

a2
TB7
M1M2 S

A B

A B

MA

MA

L2

MA

L3

OC
(54 )

IC

IC

BC(Sub)

IC

(56)

(02)

(03)

(57)

(07)

TB3
M1M2

TB5
M1M2 S

TB02
M1M2 S

TB5 TB 15
M1M2 S 1 2

TB15
1 2

TB02
M1M2 S

TB15
1 2

TB5
M1M2 S

L6

M1 M2 S

L4

BC(Main)

TB7

a4

a3

a2

A B

Shielded wire

a2

a1

a1

TB7
M1M2 S

A B S

a1

Power Supply Unit


PAC-SC51KUA
24VDC GND

L7

A B

AG-150A

A B S

MA
24VDC GND

OC, OS : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller

2-1-2. Using ME Remote controller


Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5
<=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from ME to Indoor
e1, e2, e3, e4
<=10m[32ft.]*1
0.3-1.25 mm2 [AWG22-16] *1
DC 24V to AG-150A
n
<=10m[32ft.]
0.75-2.0 mm2 [AWG18-14]
*1. If the length from ME to Indoor exceed 10m (32 ft.), use 1.25 mm2 [AWG16] shielded cable and include its length as a part of the max. overall length of the
M-NET transmission cable.
L1

L8

Group1

Group3

Group5

OS

OC

BC(Main)

IC

IC

BC(Sub)

IC

IC

(52)

(51)

(53)

(01)

(04)

(55)

(05)

(06)

TB3
M1M2

TB3
M1M2

TB02
M1M2 S

TB7
M1M2 S

TB7
M1M2 S

TB5
M1M2 S

TB02
M1M2 S

TB5
M1M2 S

R2-SERIES
SYSTEM DESIGN

e2

TB5
M1M2 S

L2

Shielded wire

TB7

A B

A B

A B

(105)

(155)

ME

ME

ME

TB3
M1M2

L4

BC(Main)

IC

IC

BC(Sub)

IC

(56)

(02)

(03)

(57)

(07)

TB02
M1M2 S

TB5
M1M2 S

TB5
M1M2 S

L6

L5

M1 M2 S

e4

Power Supply Unit


PAC-SC51KUA
A B S

24VDC GND
A B

L7

(103)
AG-150A

A B S

24VDC GND

OC, OS: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller

R2SD-10

e3

(101)

L3

OC
(54 )

TB5
M1M2 S

R2-SERIES SYSTEM DESIGN (Feb. 2009)

ME

TB02
M1M2 S

TB5
M1M2 S

2. M-NET Control

DATA U4

2-2. Transmission Cable Specifications


Transmission cables (Li)
Type of cable

ME Remote controller cables

Cable size
Remarks
Connected with simple remote controller.

1.25

[AWG16]

MA Remote controller cables

Sheathed 2-core cable (unshielded)


CVV

Shielding wire (2-core)


CVVS, CPEVS or MVVS
0.3 1.25
(0.75 1.25

2
2

[AWG22 16]
[AWG18 16])

0.3 1.25
(0.75 1.25

When 10m [32ft] is exceeded, use cables with


the same specification as transmission cables.

2
2

[AWG22 16]
[AWG18 16])

Max length : 200m [656ft]

CVVS, MVVS : PVC insulated PVC jacketed shielded control cable


CPEVS : PE insulated PVC jacketed shielded communication cable
CVV
: PV insulated PVC sheathed control cable

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-11

2. M-NET Control

DATA U4

2-3. System Configuration Restrictions


2-3-1. Common restrictions for the CITY MULTI system
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
B) Maximum 2 remote controllers for 1 Group;
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC50(51)KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.

2-3-2. Ensuring proper communication power for M-NET


In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY and Controllers, the transmission
power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the
power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption by index Indoor units, LOSSNAY, controllers
Indoor, OA unit

Indoor unit

Sized P06-P54

Sized P72,P96

BC controller
CMB

MA RC.LOSSNAY

ME Remote Contr.

PAR-21MAA
PAR-F27MEA
PAC-YT51CRA(B) PZ-52SF
PAR-FA32MA
LGH-RX-E
PZ-41SLB
0
1/4

Timers, System Contr.


PAC-SF44SRA
PAC-YT34STA
G-50A
AG-150A
1/2

ON/OFF Contr.

GB-50A
GB-24

PAC-YT40ANRA
GB-24

*RC : Remote Controller

Table 2-3-2 The equivalent power supply capability index of Trans.Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster
PAC-SF46EPA
25

Power supply unit


PAC-SC50KUA
6

PAC-SC51KUA
5

Outdoor unit

Outdoor unit

Connector TB3 and TB7 total *


32

Connector TB7 only


6

*If PAC-SC50(51)KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.

With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the airconditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System
controllers.If the total quantity reaches 40, a PAC-SF46EPA should be set.In this case, Indoor unit sized P72, 96 is
counted as 2 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption
reaches 32, a PAC-SF46EPA should be set.Yet, if a PAC-SC50(51)KUA is used to supply power at TB7 side, count from
index TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches
6, a PAC-SF46EPA should be set.

System example

TB7

TB3

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

R2-SERIES
SYSTEM DESIGN

01

Transmission
booster
(No.1)

02

ME remote
controller
TB7

TB3
Outdoor unit

ME remote
controller

N1

N2
Within N2, conditions 1,2 should be followed.
1.The total quantity of Indoor units and ME remote controller
should not exceed 40.
*Indoor unit sized P72, 96 is counted as 2 units.
2.The total equivalent transmission power consumption
should not exceed 25.

Transmission booster (No.1) should be used,


if the total quantity of Indoor units and ME remote controllers
reaches 40, (Indoor unit sized P72, 96 is counted as 2);
or if the total equivalent transmission power consumption reaches 32.

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

LOSSNAY
unit

CENTRALIZED CONTROLLER AG-150A

M-NET
24VDC
Power supply unit
PAC-SC51KUA

Centralized
Controller
AG-150A

PZ-52SF

LOSSNAY
unit
PZ-52SF

N4

N3
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 6.

R2SD-12

Transmission
booster
PAC-SF46EPA
(No.2)

Within N4, the total equivalent transmission


power consumption should not exceed 25.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-3-3. Ensuring proper power supply to System controller


The power to System controller (excluding LMAP03-U) is supplied via M-NET transmission line. M-NET transmission line
at TB7 side is called Central control transmission line while one at TB3 side is called Indoor-Outdoor transmission line.
There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC50KUA.
D) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.

2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB3.
If there is more than 1 Outdoor unit, it is necessary to
replace power supply switch connector CN41 with CN40
on one Outdoor unit.

Fig. 2-3-3-A

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

System controller
(excluding LMAP02-E)
Group

TB3
TB7
Replacement of
CN41 with CN40

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

ME remote controller
System
controller

Maximum 3 System controllers can be connected to TB3,


but maximum 2 in the case of G-50A.

2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB7
and receiving power from the Outdoor unit.
It is necessary to replace power supply switch connector
CN41 with CN40 on one Outdoor unit.

Fig. 2-3-3-B

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Replacement of
CN41 with CN40

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

ME remote controller
System
controller

Maximum 3 System controllers can be connected to TB7.

2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC50KUA.
Fig. 2-3-3-C

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

R2-SERIES
SYSTEM DESIGN

When using PAC-SC50KUA to supply transmission


power, the power supply connector CN41 should be kept
as it is. It is also a factory setting.
1 PAC-SC50KUA supports maximum 2 G-50A units due
to the limited power DC 12V at its TB3.
However, 1 PAC-SC50KUA supplies transmission power
at its TB2 equal to 6 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 6 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

PAC-SC50KUA

Indoor unit

ME remote controller

System
controller

CAUTION
It is recommended that AG-150A/GB-50A/GB-24A are connected to TB7 because the controllers perform data backup.
If an air conditioner system has more than one Outdoor unit, AG-150A/GB-50A/GB-24A receiving transmission power at TB3 or TB7 on one of the Outdoor
units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A/GB-50A/GB-24A, and disrupt the whole system.
When applying apportioned electric power function, it is necessary to connect AG-150A/GB-50A/GB-24A to TB7 and has the own power supply unit
PAC-SC50KUA/PAC-SC51KUA.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-13

2. M-NET Control

DATA U4

2-3-3-D. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
When using PAC-SC51KUA to supply transmission
power, the power supply connector CN41 should be kept
as it is. It is also a factory setting.
1 PAC-SC51KUA supports maximum 1 AG-150A unit
due to the limited power DC 24V at its TB3.
However, 1 PAC-SC51KUA supplies transmission power
at its TB2 equal to 5 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 5 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.

Fig. 2-3-3-D

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

PAC-SC51KUA

Indoor unit

ME remote controller

System
controller

CAUTION
It is recommended that AG-150A/GB-50A/GB-24A are connected to TB7 because the controllers perform data backup.
If an air conditioner system has more than one Outdoor unit, AG-150A/GB-50A/GB-24A receiving transmission power at TB3 or TB7 on one of the Outdoor
units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A/GB-50A/GB-24A, and disrupt the whole system.
When applying apportioned electric power function, it is necessary tp connect AG-150A/GB-50A/GB-24A to TB7 and has the own power supply unit
PAC-SC50KUA/PAC-SC51KUA.

2-3-4. Power supply to LM adapter LMAP03U

R2-SERIES
SYSTEM DESIGN

1-phase 208-230V AC power supply is needed.


The power supply unit is not necessary when connecting only the LMAP03U. Yet, make sure to change the power supply
changeover connector CN41 to CN40 on the LM adapter.

R2SD-14

R2-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4. Address Setting


2-4-1. Switch operation

Unit address No. setting

01

2 3

7 8

01

9
7 8

2 3

45 6

D
BC E

F 0 12
34 5 6

789A

Address No. of outdoor unit, indoor unit and remote controller.


The address No. is set at the address setting board.
In the case of R2 system, it is necessary to set the same No. at the
branch No. switch of indoor unit as that of the BC controller
connected. (When connecting two or more branches, use the lowest
branch No.)
Caution for switch operations

Rotary switch
Branch
No. setting

45 6

In order to constitute CITY MULTI in a complete system, switch


operation for setting the unit address No. and connection No. is
required.

Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.
MA remote controller
When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
The factory setting is Main .
ON

Setting the dip switches


1

The dip switches are at the bottom of the remote controller.


Remote controller Main/Sub and other function settings are performed
using these switches.
Ordinarily, only change the Main/Sub setting of SW1. (The factory settings are all ON .)
SW No

ON

SW contents Main

ON

OFF

Remote controller
Main/Sub setting

Comment

Main

Sub

When remote controller power turned on

Cooling/heating display in AUTO mode

Yes

No

When you do not want to display Cooling and Heating in the


Auto mode, set to No .

Intake temperature
display

Yes

No

When you do not want to display the intake temperature, set to No .

Set one of the two remote controllers at one group to Main .

Normally on Timer mode on

When you want to return to the timer mode when the power is restored after
a power failure when a Program timer is connected, select Timer mode .

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-15

2. M-NET Control

DATA U4

2-4-2. Rule of setting address


Unit

Address setting

Example

Note

7 8
7 8

7 8

9 0 1

7 8

9 0 1

7 8

4 5 6

4 5 6

9 0 1

9 0 1

4 5 6

4 5 6

10

7 8

7 8

45 6

45 6

45 6

100

10

0
9 1

0
9 1

7 8

7 8

0,2

0~5

0~9

100

10

9 0 1

9 0 1
2 3

7 8

45 6

45 6

45 6

7 8

The address automatically becomes "200" if it is set


as "00"

01

10

4 5 6

4 5 6

Fixed

The address of main remote controller + 50

2 3

7 8

100

The smallest address of indoor unit in the group + 100

01

7 8

7 8

7 8

45 6

Lowest address within the indoor units connected to


the BC controller (Sub) plus 50.

2 3

201 ~ 250

01

2 3

LMAP03U

Please reset one of them to an address between 51


and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"

The place of "100" is fixed to "1"

01

10

2 3

000, 201 ~ 250

2 3

GB-24A
G-50A
GB-50A
AG-150A

01

2 3

ON/OFF controller 000, 201 ~ 250

01

45 6

Fixed

7 8

7 8
45 6

45 6

2 3

01

10
9

000, 201 ~ 250

2 3

151 ~ 199, 200

The address of outdoor unit + 1

2 3

7 8

7 8

4 5 6

4 5 6

10

Fixed

The smallest address of indoor unit in same refrigerant


system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"

2 3

ME, LOSSNAY
Remote controller
(Sub)

2 3

10

2 3

Local remote controller

9 0 1

2 3

101 ~ 150

2 3

System controller

9 0 1

0
9 1

R2-SERIES
SYSTEM DESIGN

4 5 6

4 5 6

2 3

52 ~ 99, 100

2 3

52 ~ 99, 100

ME, LOSSNAY
Remote controller
(Main)

System controller

10

2 3

BC controller
(Sub)

51 ~ 99, 100
(Note1)

9 0 1

2 3

BC controller
(Main)

01 ~ 50

2 3

Outdoor unit

7 8

9 0 1

Indoor unit

Use the most recent address within the same group of


indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)

10

Note1: To set the address to "100", set it to "50"


Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.

R2SD-16

R2-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3. System examples


Factory setting
Original switch setting of the outdoors, indoors, controllers and LMAP at shipment is as follows.
Outdoor unit
: Address: 00, CN41: U (Jumper), DipSW2-1: OFF
Indoor unit
: Address: 00
BC controller
: Address: 00
Remote controller
: Address: 100
LMAP
: Address: 247, CN41: U (Jumper), DipSW1-2: OFF

Setting at the site


DipSW2-1(Outdoor)
DipSW1-2(LMAP)
CN40/CN41

: When the System Remote Controller is used, all the Dip SW2-1 at the outdoor units should be
set to "ON".
: When the LMAP is used together with System Remote Controller, DipSW1-2 at the LMAP
should be set to "ON".
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole central control system.

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-17

Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole central control system.

2. M-NET Control

DATA U4

2-4-3-1. MA remote controller, Single-refrigerant-system, System Controller


<Two outdoor units>
PURY-P-TSHMU/YSHMU
OC
OS

51
CN40

CN41

52
CN40

DipSW2-1

ON
TB3

<One outdoor unit>


PURY-P-THMU/YHMU
OC

CN41

DipSW2-1

ON
TB3

51
CN40

CN41

DipSW2-1

ON
TB3
Group 1

BC controller

Indoor unit

53

01

TB02

TB5

02
TB15

201
SC

Group 2

03

TB5

SRU

Group 3

TB15

TB5

Group 4

04
TB15

TB5

05
TB15

TB5

TB15

1*

MA R/C

MA R/C

MA R/C MA R/C
(Main)
(Sub)

1*
Wireless R/C
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

R2-SERIES
SYSTEM DESIGN

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units and central controller.
3. For a system having more than 32 indoor unit (P06-P54), confirm the need of Booster at 2-3 "System configuration
restrictions".
4. Indoor units should be set with a branch number.

R2SD-18

R2-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-2. MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long M-NET wiring
PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

51
CN40

52

CN41

CN40

DipSW2-1

ON
TB3

PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

53

CN41

CN40

DipSW2-1

54

CN41

ON
TB3

TB3

CN40

DipSW2-1

CN41

DipSW2-1

ON
TB3

TB3
Group 2

Group 21

Indoor unit

56
TB02

55

CN41

ON

Group1
BC controller

CN40

DipSW2-1

ON

PURY-P-THMU/YHMU
OC
TB7

01

02
TB15

TB5

03
TB15

TB5

30
TB15

TB5

TB2

TB3

TB5

TB15

Transmission Booster
PAC-SF46EPA

201

SRU *1
MA R/C

SC

MA R/C MA R/C
(Main)
(Sub)

*1

PSU
Power supply
unit (PSU)
(PAC-SC51KUA)

Wireless R/C

*2
Group 31
BC controller
(Main)

Indoor unit

57

41

TB02

TB5

Group 32
LOSSNAY

43

95

42
TB15

SRU *1

TB5

TB5

142

Group 33
BC controller
(Sub1)

Group 34

45
TB5

46
TB15

TB5

TB15

143

ME R/C PZ-52SF

MA R/C

MA R/C MA R/C
(Main)
(Sub)

*1
Wireless R/C

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-19

R2-SERIES
SYSTEM DESIGN

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For G-50A,
12V DC should be used with the PSU (PAC-SC50KUA). For AG-150A, 24VDC should be used with the PSU (PAC-SC51KUA).
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, LOSSNAY and central controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
4. Indoor units should be set with a branch number.
5. Assign an address to each of the sub BC controllers (BS1 and BS2) which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.

2. M-NET Control

DATA U4

2-4-3-3. ME remote controller, Single-refrigerant-system, No system controller


<Two outdoor units>
PURY-P-TSHMU/YSHMU
OC
OS

51
CN40

CN41

52
CN40

DipSW2-1

OFF
TB3

<One outdoor unit>


PURY-P-THMU/YHMU
OC

51

CN41

CN40

DipSW2-1

CN41

DipSW2-1

OFF

OFF
TB3

TB3

Group 1

Group 2

Group 3

Group 4

Indoor unit

BC controller

53

01

TB02

02

TB5

03

TB5

04

TB5

05

TB5

TB5

101

102

104

ME R/C

ME R/C

ME R/C

105

155

ME R/C ME R/C

NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their
address.
2. Address should be set to Indoor units, central controller and ME remote controllers.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
4. Indoor units should be set with a branch number.

2-4-3-4. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY


<Two outdoor units>
PURY-P-TSHMU/YSHMU
OC
OS

51
CN40

CN41

52
CN40

DipSW2-1

ON
TB3

<One outdoor unit>


PURY-P-THMU/YHMU
OC

51

CN41

CN40

DipSW2-1

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 1
BC controller

Indoor unit

53

01

R2-SERIES
SYSTEM DESIGN

TB02

TB5

Group 2

101

SC

ME R/C

Group 4

LOSSNAY

02
TB5

102

04

03

TB5

201

Group 3

103

ME R/C PZ-52SF

TB5

05
TB5

104
ME R/C

105

155

ME R/C ME R/C

*SC can be connected to TB3 side or TB7 side;


Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their
address.
2. Address should be set to Indoor units, LOSSNAY central controller, ME remote controllers.
3. For a system having more than 32 indoor unit (P06-P54), confirm the need of Booster at 2-3 "System configuration
restrictions".
4. Indoor units should be set with a branch number.

R2SD-20

R2-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-5. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

51
CN40

52

CN41

CN40

DipSW2-1

ON
TB3

PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

53

CN41

CN40

DipSW2-1

54

CN41

CN40

DipSW2-1

ON

ON
TB3

TB3

55

CN41

CN40

DipSW2-1

ON
TB3

TB3
Group 2

Group 21
BC controller
(Sub)

Indoor unit

01

56
TB02

02

TB5

03

TB5

102

ME R/C

ME R/C

30

80

TB5

101

201

CN41

DipSW2-1

ON

Group 1
BC controller
(Main)

PURY-P-THMU/YHMU
OC
TB7

TB3

TB2

TB02

TB5

Transmission Booster
PAC-SF46EPA

130

180

ME R/C ME R/C

SC
Group 31

PSU
BC controller
Power supply
unit (PSU)
(PAC-SC51KUA)

57
TB02

*1

Group 32

Indoor unit

Group 33

Group 34

LOSSNAY

41

42

TB5

141

TB5

142

ME R/C

44

43

TB5

45

TB5

143

TB5

144

145

195

ME R/C ME R/C

ME R/C

ME R/C PZ-52SF

*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System . For G-50A,
12V DC should be used with the PSU (PAC-SC50KUA). For AG-150A, 24VDC should be used with the PSU (PAC-SC51KUA).
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
3. Indoor units should be set with a branch number.
4. Assign an address to each of the sub BC controllers (BS1 and BS2) which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.

2-4-3-6. Example : BC, BC sub

NOTE

PURY-P-TSHMU/YSHMU
OS
OC

51
CN40 CN41

DipSW2-1
OFF
TB3

DipSW2-1
OFF
TB3

: Piping

: M-NET wiring

53

54

BC controllers
CMB-V-GA(main)

TB02

01
TB5

02
TB5

101

03

04

TB5

TB5

06

07

TB5

08
TB5

106
Group 2

BC controllers
CMB-V-GB(No.2 sub)

TB02

05
TB5

104
Group 1

57

BC controllers
CMB-V-GB(No.1 sub)

TB02

Group 3

R2-SERIES SYSTEM DESIGN (Feb. 2009)

TB5

107
Group 4

R2SD-21

R2-SERIES
SYSTEM DESIGN

52
CN40 CN41

Indoor units should be set with a branch number.


BC (main) address = O/U address + 1
BC (sub) address = Lowest address within the indoor units connected to the BC controller (sub) + 50
If applicable, set the sub BC controllers in an PURY system in the following order :
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)

2. M-NET Control

DATA U4

2-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit


PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

51
CN40

CN41

DipSW2-1

OFF
TB3

PURY-P-THMU/YHMU
OC
TB7

52
CN40

54

CN41

CN40

DipSW2-1

CN41

DipSW2-1

OFF

OFF
TB3

TB3

Group 1

Group 2

BC controller

01

53

02

03

04

05

TB02

101

105

ME R/C

ME R/C

Group 4

Group 3

BC controller

10

55

09

08

07

06

TB02

110

107

ME R/C

ME R/C

NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

2-4-3-8. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, No Power sypply unit
PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

51
CN40

CN41

DipSW2-1

ON
TB3

PURY-P-THMU/YHMU
OC
TB7

52
CN40

54

CN41

CN40

DipSW2-1

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 1

Group 2

BC controller

01

53

02

03

04

05

TB02

201

101

105

SC

ME R/C

ME R/C

R2-SERIES
SYSTEM DESIGN

Group 4

Group 3

BC controller

55

10

09

08

07

06

TB02

110

107

ME R/C

ME R/C

NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.

R2SD-22

R2-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-9. TG-2000A+G-50A/GB-50A
G-50A/GB-50A can control max. 50 indoor units;
TG-2000A can control max. 40 pieces of G-50A or GB-50A;
TG-2000A can control max. 2000 indoor units.
<Two outdoor units>
PURY-P-TSHMU/YSHMU

GB-50A

OC
TB7

201

OS
TB7

51

PSU

CN40

(PAC-SC50KUA or
PAC-SC51KUA)

OC
TB7

52

CN41

CN40

51

CN41

DipSW2-1

DipSW2-1

ON

ON

TB3

ON
TB3

TB3
Group 2

01

TB02

CN41

Group 40

Indoor unit

53

HUB

CN40

DipSW2-1

Group 1
BC controller

<One outdoor unit>


PURY-P-THMU/YHMU

02
TB15

TB5

03

42

TB15 TB5

TB5

TB15 TB2

TB3 TB5

Transmission Booster
PAC-SF46EPA

SRU *1
MA R/C

PC with
TG-2000A

TB15

MA R/ C MA R/C
(Main)
(Sub)

*1
Wireless R/C

LAN
G-50A

PURY-P-TSHMU/YSHMU
OC

202

OS
TB7

TB7

51
CN40

DC12V

52

CN41

CN40

DipSW2-1

ON

DipSW2-1

Group 2

01
TB5

Group 21

02
TB5

ME R/C

ME R/C

Group 31
Indoor unit

41
TB5

141

TB5

130

180

ME R/C ME R/C
Group 33

LOSSNAY

42

143

ME R/C PZ-52SF

Group 34

BC controller
(Sub)

94

43
TB5

142

TB3

Transmission Booster
PAC-SF46EPA

Group 32

TB5

ME R/C

30
TB2

TB02

44
TB5

45
TB5

144
ME R/C

145

195

ME R/C ME R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-23

R2-SERIES
SYSTEM DESIGN

102

54

03
TB5

101

BC controller
(Main)
TB02

CN41

Indoor unit

55
TB02

CN40

ON
TB3

TB3

Group 1
BC controller

53

CN41

ON
TB3

(PAC-SC50KUA)

OC
TB7

DipSW2-1

PSU

PURY-P-THMU/YHMU

2. M-NET Control

DATA U4

2-4-3-10. TG-2000A(Ver.5.5* series)+AG-150A(Ver.1** series)


AG-150A can control max. 50 indoor units;
TG-2000A can control max. 40 pieces of AG-150A;
TG-2000A can control max. 2000 indoor units.
<Two outdoor units>
PURY-P-TSHMU/YSHMU

AG-150A

OC
TB7

000

OS
TB7

51

DC24V
CN40

<One outdoor unit>


PURY-P-THMU/YHMU
OC
TB7

52

CN41

CN40

51

CN41

CN40

CN41

PSU
(PAC-SC51KUA)

DipSW2-1

DipSW2-1

ON

ON

TB3

DipSW2-1

ON
TB3

TB3

Group 1
BC controller

01

TB02

Group 40

Indoor unit

53

HUB

Group 2

02
TB15

TB5

03

42

TB15 TB5

TB5

TB15 TB2

TB3 TB5

Transmission Booster
PAC-SF46EPA

SRU *1
MA R/C

PC with
TG-2000A

TB15

MA R/ C MA R/C
(Main)
(Sub)

*1
Wireless R/C

LAN
AG-150A

PURY-P-TSHMU/YSHMU
OC

000

TB7

51
CN40

DC24V

52

CN41

CN40

DipSW2-1

ON

R2-SERIES
SYSTEM DESIGN

DipSW2-1

Group 2

01
TB5

Group 21

02
TB5

102

ME R/C

ME R/C

Group 31
Indoor unit

54

41
TB5

141

30
TB2

TB5

130

Group 33

LOSSNAY

94

43
TB5

143

ME R/C PZ-52SF

Group 34

BC controller
(Sub)
TB02

44
TB5

45
TB5

144
ME R/C

145

R2-SERIES SYSTEM DESIGN (Feb. 2009)

195

ME R/C ME R/C

*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

R2SD-24

180

ME R/C ME R/C

42

142

TB3

Transmission Booster
PAC-SF46EPA

Group 32

TB5

ME R/C

03
TB5

101

BC controller
(Main)
TB02

CN41

Indoor unit

55
TB02

CN40

ON
TB3

TB3

Group 1
BC controller

53

CN41

ON
TB3

(PAC-SC51KUA)

OC
TB7

DipSW2-1

PSU

PURY-P-THMU/YHMU

OS
TB7

2. M-NET Control

DATA U4

2-4-3-11. LMAP
LMAP can transmission for max. 50 indoor units;
If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON".
Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system
controller (SC).
LMAP can transmission for max.
50 indoor units in single-refrigerant-system or multi-refrigerant-system.

LMAP(01)

identified by Neuron ID

(LONWORKS adapter)

<Two outdoor units>


PURY-P-TSHMU/YSHMU

247
CN40 CN41

OC
TB7

DipSW1-2
OFF

OS
TB7

51
CN40

OC
TB7

52

CN41

CN40

DipSW2-1

51

CN41

CN40

DipSW2-1

OFF
TB3

CN41

DipSW2-1

OFF

OFF
TB3

TB3

Group 1
BC controller

<One outdoor unit>


PURY-P-THMU/YHMU

Group 2

Group 40

Indoor unit

53

01

TB02

02
TB15

TB5

03
TB15 TB5

TB5

42
TB15

G-50A
Power supply unit
(PAC-SC50KUA)
DC 12V
PSU

TB15

Transmission Booster
PAC-SF46EPA

SRU *1

000

TB3 TB5

TB2

MA R/C

MA R/C MA R/C
(Main) (Sub)

*1
Wireless R/C

LONWORKS

LMAP(02)
identified by Neuron ID

247
CN40 CN41
DipSW1-2
ON

PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7
CN40

51

CN41

DipSW2-1

ON
TB3

CN40

52

CN41

TB02

02

102

ME R/C

ME R/C

Group 31
Indoor unit

03

CN40

DipSW2-1

55

CN41

DipSW2-1

ON

ON
TB3

TB3

Group 21

30
TB3

TB2

TB5

Transmission Booster
PAC-SF46EPA

130

180

ME R/C ME R/C

LOSSNAY

42
TB5

CN41

80
TB02

Group 32

41
TB5

54

BC controller
(Sub)

TB5

101

57

PC

Group 2

TB5

CN40

PURY-P-THMU/YHMU
OC
TB7

BC controller
(Sub)

43
TB5

Group 33

44

94
TB02

Group 34

TB5

45
TB5

LONWORKS card
LONWORKS card
LONWORKS card

141
ME R/C

142

143

ME R/C PZ-52SF

144
ME R/C

145

195

ME R/C ME R/C

For other equipments (Lighting, security, elevator etc.)


*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-25

R2-SERIES
SYSTEM DESIGN

BC controller
(Main)

CN41

ON
TB3

TB3

01
TB5

53

DipSW2-1

ON

Indoor unit

56
TB02

CN40

DipSW2-1

Group 1
BC controller
(Main)

PURY-P-TSHMU/YSHMU
OC
OS
TB7
TB7

3. Piping Design

DATA U4

3-1. R410 Piping Material


Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types.
A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand.
B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness.
The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety
under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Ta ble 3-1, or You shall follow the local
industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.
Size (mm)
Size (inch) Radial thickness (mm) Radial thickness (mil)
[32]
6.35
1/4"
0.8
[32]
9.52
3/8"
0.8
[32]
12.7
1/2"
0.8
[40]
15.88
5/8"
1.0
[48]
19.05
3/4"
1.2
[40]
19.05
3/4"
1.0
[40]
22.2
7/8"
1.0
[40]
25.4
1"
1.0
[40]
28.58
1-1/8"
1.0
[44]
31.75
1-1/4"
1.1
[48]
34.93
1-3/8"
1.2
[56]
41.28
1-5/8"
1.4

Pipe type
Type-O
Type-O
Type-O
Type-O
Type-O
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H

* For pipe sized 19.05 (3/4") for R410A air conditioner, choice of pipe type is up to you.
* The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the
local standards.

Flare
Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions
mentioned below so as to achieve enough the air-tightness.
Pipe size
6.35 [1/4"]
9.52 [3/8"]
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]

A (For R410A)

(mm[in.])

Flare nut

9.1 [3/8"]
13.2 [9/16"]
16.6 [11/16"]
19.7 [13/16"]
24.0 [1"]

R2-SERIES
SYSTEM DESIGN

Flare pipe

R2SD-26

R2-SERIES SYSTEM DESIGN (Feb. 2009)

Pipe size
6.35 [1/4"]
9.52 [3/8"]
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]

B (For R410A)
17.0 [3/4"]
22.0 [7/8"]
26.0 [1-1/16"]
29.0 [1-1/8"]
36.0 [1-7/16"]

(mm[in.])

3. Piping Design

DATA U4

3-2. PURY-P-T(S)HMU/Y(S)HMUs Piping Design


r
3-2-1. IF 16 ports or less are in use, i.e., if only one BC controller is in use with no sub BC controller.
Note1. PURY systems do not require headers.
Note2. Indoor units sized P72-P96 should be connected to a BC controller using the Y-shaped
CMY-R160-J joint adapter. These indoor units cannot use the same BC controller ports
as other units. (They must use their own individual BC controller ports.)
Note3. As bends cause pressure loss on transportation of refrigerant, the fewer bends in the system,
the better it is. Piping length needs to factor in the actual length and equivalent length in
which the bends are counted.
Note4. Indoor units connected to the BC controller sharing one port cannot operate separately in
heating and cooling modes simultaneously; i.e., they must function in either heating or cooling in tandem.
Note5. Indoor unit capacities are included in the model name. For example, PEFY-P24NMSU-E has a capacity
of 24,000 BTUs.
Note6. Total downstream indoor capacity is the total of all the indoor units connected downstream. For example,
PEFY-P24NMSU-E + PEFY-P12NMSU-E: Total Indoor Unit Capacity = P24 + P12 = P36.
OU

A
For outodoor units equal to or larger than a size P120, on
the BC controller please ensure CMB-PNU-GA is used.

BC controller

H'

IU

CMY-Y102S-G2
(Joint)

Reducer (P06~P18)
(attached with BC controller)

h1

h2

IU

IU

(P06-P18)

CMY-R160-J
(Joint)

IU

c
IU

(P24-P54) (P72-P96)

Max.3 sets for 1 port.


Total capacity <= P54

Fig. 3-2-1-1 Piping scheme

(m [ft.])

Table 3-2-1-1. Piping length limitation


Item

Piping in the figure

Max. length

Total piping length


Farthest IU from OU
Distance between OU and BC
Farthest IU from BC controller
Height between OU and IU (OU above IU)

A+B+a+b+c+d
A+B+d
A
B+d
H

*1
165 [541']
110 [360'] *1
40 [131'] *2
50 [164'] *3

Height between OU and IU (OU under IU) H'


Height between IU and BC
h1
Height between IU and IU
h2

Max. equivalent length

40 [131'] *3
15 [49'] (10 [32']) *4
15 [49'] (10 [32']) *4

190 [623']
110 [360'] *1
40 [131'] *2
-

Table3-2-1-2. Bends equivalent length "M"


Outdoor Model

M (m/bends [ft./bends])

P72THMU,YHMU 0.35 [1.15']


P96THMU,YHMU 0.42 [1.38']
P120THMU,YHMU 0.47 [1.54']

OU : Outdoor Unit ; IU : Indoor Unit ; BC : BC controller


*1. Please refer to Fig.3-2-4
*2. Farthest Indoor from BC controller "B + d" can exceed 40m(131ft.) up to 60m(197ft.) if an Indoor unit with a capacity of P72 or P96 is not connected.
Details refer to Fig.3-2-1-2
*3. Contact a Mitsubishi representative for possible height extensions.
*4. Distance of an Indoor unit with a capacity of P72 or P96 must be less than 10m (33ft.) from the BC Controller, if any.
70
60
50
40
30

10
0

10

15

Height difference between the main BC controller


and farthest indoor unit (m)
250

Pipe length between the main BC


controller and farthest indoor unit (ft)

(mm [in.])
Pipe(Low pressure)
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]

Table3-2-1-4. Piping "B" size seleciton rule


Total down-stream Indoor capacity Pipe(Liquid)
P54 or less
9.52 [3/8"]

20

Table3-2-1-3. Piping "A"size selection rule


Outdoor Model
Pipe(High pressure)
P72THMU,YHMU 15.88 [5/8"]
P96THMU,YHMU 19.05 [3/4"]
P120THMU,YHMU 19.05 [3/4"]

200
150

R2-SERIES
SYSTEM DESIGN

Pipe length between the main BC


controller and farthest indoor unit (m)

Fig. 3-2-1-2 Piping length and height between IU and BC controller

(mm [in.])
Pipe(Gas)
15.88 [5/8"]

Table3-2-1-5. Piping "a", "b", "c", "d" size selection rule (mm [in.])
Indoor Unit size
Pipe(Liquid) Pipe(Gas)
P06 to P18
6.35 [1/4"]
12.70 [1/2"]
P24 to P54
9.52 [3/8"]
15.88 [5/8"]
P72
9.52 [3/8"]
19.05 [3/4"]
P96
9.52 [3/8"]
22.20 [7/8"]

100
50
0

10

15

20

25

30

35

40

45

Height difference between the main BC controller


and farthest indoor unit (ft)

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-27

3. Piping Design

DATA U4

3-2-2. If more than 16 ports are in use, or if there is more than one BC controller in use for one outdoor unit
Note1. PURY systems do not require headers.
Note2. Indoor units sized P72-P96 should be connected to a BC controller using the Y-shaped
CMY-R160-J joint adapter. These indoor units cannot use the same BC controller ports
as other units. (They must use their own individual BC controller port.)
Note3. As bends cause pressure loss on transportation of refrigerant, the fewer bends in the system,
the better it is. Piping length needs to factor in the actual length and equivalent length in which
the bends are counted.
Note4. Indoor units connected to the BC controller sharing one port cannot operate separately in heating
and cooling modes simultaneously; i.e., they must function in either heating or cooling in tandem.
Note5. For sub-BC controller CMB-P-NU-GB, the total connectable indoor unit capacity can be 126,000 BTUs or less.
If two sub-BC controllers are used, the total indoor unit capacity connected to BOTH sub-BC controllers also cannot exceed 126,000 BTUs.
For sub-BC controller CMB-P1016NU-HB, the total connectable indoor unit capacity can be 126,000 BTUs or less. However, if two sub-BC
controllers are used and at least one is a CMB-P1016NU-HB, the total indoor unit capacity connected to BOTH sub controllers must NOT exceed 168,000 BTUs.
Note6. Indoor unit capacities are included in the model name. For example, PEFY-P24NMSU-E has a
capacity of 24,000 BTUs.
Note7. Total "downstream indoor capacity" is the total of all the indoor units connected downstream.
For example, PEFY-P24NMSU-E + PEFY-P12NMSU-E: Total Indoor Unit Capacity = P24 + P12 = P36.
OU

IU

e
A

Field supplied

BC controller (Main BC)

h1

BC controller (Sub BC)

h3

C
CMY-Y102S-G2
(Joint)

Reducer (P06-P18)
(attached with BC controller)

H'

BC controller (Sub BC)

h2

h1
IU

IU
(P06-P18)

CMY-R160-J
(Joint)

IU

(P24-P54)

(P72-P96)

IU

IU

Max.3 sets for 1 port.


Total capacity < = P54

h1

IU

OU : Outdoor unit, IU : Indoor unit

Fig. 3-2-2-1 Piping scheme

Table 3-2-2-1. Piping length limitation


Item
Total piping length
Farthest IU from OU
Distance between OU and BC
Farthest IU from BC controller
Height between OU and IU (OU above IU)
Height between OU and IU (OU under IU)
Height between IU and BC
Height between IU and IU
Height between BC(Main or Sub) and BC(Sub)

Piping in the figure


A+B+C+D+E+a+b+c+d+e+f
A+C+E+f
A
B+d or C+D+e or C+E+f
H
H'
h1
h2
h3

Table3-2-2-2. Bends equivalent length "M"

(m [ft.])
Max. length
Max. equivalent length
*1
165 [541']
190 [623']
110 [360'] *1
110 [360'] *1
40 [131'] *2
40 [131'] *2
50 [164']] *3
40 [131']] *3
15 [49'] (10 [32']) *4
15 [49'] (10 [32']) *4
15 [49'] (10 [32']) *5
-

Outdoor Model
P72THMU,YHMU
P96THMU,YHMU
P120THMU,YHMU

M (m/bends [ft./bends])
0.35 [1.15']
0.42 [1.38']
0.47 [1.54']

OU : Outdoor Unit ; IU : Indoor Unit ; BC : BC controlle


r
*1. Please refer to Fig.3-2-4
*2. Farthest Indoor from BC controller "B + d" or "C + D + e" or "C + E + f" can exceed 40m(131ft.) up to 60m(197ft.) if Indoor unit with a capacity
of P72 or P96 is not connected. Details refer to Fig.3-2-2-2
*3. Contact a Mitsubishi representative for possible height extensions.
*4. Distance of an Indoor unit with P72 or P96 capacity BC must be less than 10m(33ft.) from the BC Controller, if any.
*5. When using 2 Sub BC controllers, max. height "h3" should be considered.
Fig. 3-2-2-2 Piping length and height between IU and BC controller
Table3-2-2-3. Piping "A"size selection rule (mm [in.])
Outdoor Model
P72THMU,YHMU
P96THMU,YHMU
P120THMU,YHMU

Pipe length between the main BC


controller and farthest indoor unit (m)

60
50

R2SD-28

Pipe(High pressure)
15.88 [5/8"]
19.05 [3/4"]
19.05 [3/4"]

Pipe(Low pressure)
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]

40

Table3-2-2-4. Piping "B" size selection rule

30

Total down-stream Indoor capacity


P54 or less

20

Pipe(Liquid)
9.52 [3/8"]

(mm [in.])
Pipe(Gas)
15.88 [5/8"]

10

Table3-2-2-5 . Piping "C", "D", "E" size selection rule

0
0

10

15

Height difference between the main BC controller


and farthest indoor unit (m)
250

Pipe length between the main BC


controller and farthest indoor unit (ft)

R2-SERIES
SYSTEM DESIGN

70

200

Total down-stream Indoor capacity


P72 or less
P73 to P108
P109 to P126
P127 to P144
P145 to P168

Pipe(Liquid)
9.52 [3/8"]
9.52 [3/8"]
12.70 [1/2"]
12.70 [1/2"]
15.88 [5/8"]

Pipe(HP Gas)
15.88 [5/8"]
19.05 [3/4"]
19.05 [3/4"]
22.20 [7/8"]
22.20 [7/8"]

HP : High pressure, LP:Low pressure


150

Table3-2-2-6 . Piping "a", "b", "c", "d" saize selection rule (mm [in.])

100
50
0
0

10

15

20

25

30

35

40

45

Indoor Unit size


P06 to P18
P24 to P54
P72
P96

Height difference between the main BC controller


and farthest indoor unit (ft)

R2-SERIES SYSTEM DESIGN (Feb. 2009)

Pipe(Liquid)
6.35 [1/4"]
9.52 [3/8"]
9.52 [3/8"]
9.52 [3/8"]

Pipe(Gas)
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]
22.20 [7/8"]

(mm [in.])
Pipe(LP Gas)
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]

3. Piping Design

DATA U4

3-2-3. If more than 16 ports are in use, or if there is more than one BC controller in use for two outdoor units
Note1. PURY systems do not require headers.
Note2. Indoor units sized P72-P96 should be connected to a BC controller using the Y-shaped
CMY-R160-J joint adapter. These indoor units cannot use the same BC controller ports
as other units. (They must use their own individual BC controller port.)
Note3. As bends cause pressure loss on transportation of refrigerant, the fewer bends in the system,
the better it is. Piping length needs to factor in the actual length and equivalent length in which
the bends are counted.
Note4. Indoor units connected to the BC controller sharing one port cannot operate separately in heating
and cooling modes simultaneously; i.e., they must function in either heating or cooling in tandem.

Main unit

Sub unit

h4

Outdoor Twinning kit (High/Low press.)


CMY-R100VBK
The Low press. kit must be placed in the outdoor unit that has a larger capacity index
of the two, regardless of the relative positions of the outdoor units or their addresses.
(If outdoor units that have the same capacity are used in combination, the distributor
can be placed in either outdoor unit.)
The High press. kit is to be installed in the field.

IU

H
e

G
Field supplied

A
BC controller (Main BC)

H'

h1

BC controller (Sub BC)

h3

C
E

BC controller (Sub BC)

h2

a
IU

CMY-Y102S-G2
(Joint)

Reducer (P06-P18)
(attached with BC controller)

h1

Note5. For sub-BC controller CMB-P-NU-GB, the total connectable indoor unit capacity can be P126 or less.
However, if two sub-BC controllers are used and at least one is a CMB-P1016NU-HB, the total
indoor unit capacity connected to BOTH sub-BC controllers cannot exceed P168.
Note6. Indoor unit capacities are included in the model name. For example, PEFY-P24NMSU-E has a
capacity of 24,000 BTUs.
Note7. Total "downstream indoor capacity" is the total of all the indoor units connected downstream.
For example, PEFY-P24NMSU-E + PEFY-P12NMSU-E: Total Indoor Unit Capacity = P24 + P12 = P36.

b
IU

IU

(P06-P18) (P24-P54) (P72-P96)

CMY-R160-J
(Joint)

IU

IU

h1

Max.3 sets for 1 port.


Total capacity < = P54

IU

IU : Indoor unit

Fig. 3-2-3-1 Piping scheme


Table3-2-3-1. Piping length limitation
Item
Total piping length
Farthest IU from OU
Distance between OU and BC
Farthest IU from BC controller
Height between OU and IU (OU above IU)
Height between OU and IU (OU under IU)
Height between IU and BC
Height between IU and IU
Height between BC(Main or Sub) and BC(Sub)
Distance between Main unit and Sub unit
Height between Main unit and Sub unit

Piping in the figure


F+G+H+A+B+C+D+E+a+b+c+d+e+f
F(G)+A+C+E+f
F(G)+A
B+d or C+D+e or C+E+f
H
H'
h1
h2
h3
F+G or H
h4

(m [ft.])
Max. length
Max. equivalent length
*1
165 [541']
190 [623']
110 [360'] *1
110 [360'] *1
40 [131'] *2
40 [131'] *2
50 [164']] *3
40 [131']] *3
15 [49'] (10 [32']) *4
15 [49'] (10 [32']) *4
15 [49'] (10 [32']) *5
5 [16']
0.1 [0.3']
-

Table3-2-3-2. Bends equivalent length "M"


Outdoor Model
M (m/bends [ft./bends])
P144TSHMU,YSHMU
0.50 [1.64']
0.50 [1.64']
P168TSHMU,YSHMU
P192TSHMU,YSHMU
0.50 [1.64']
P216TSHMU,YSHMU
0.50 [1.64']
P240TSHMU,YSHMU
0.50 [1.64']

OU : Outdoor Unit ; IU : Indoor Unit ; BC : BC controller


*1. Please refer to Fig.3-2-4
*2. Farthest Indoor from BC controller "B + D" or "C + D + e" or "C + E + f" can exceed 40m(131ft.) up to 60m(197ft.) if an Indoor unit P72 or P96
is not connected. Details refer to Fig.3-2-3-2
*3. Contact a Mitsubishi representative for possible height extensions.
*4. Distance of an Indoor unit with a capacity of P72 or P96 must be less than 10m (33ft.) from the BC Controller, if any.
*5. When using 2 Sub BC controllers, max. height "h3" should be considered.
Fig. 3-2-3-2 Piping length and height between IU and BC controller

Table3-2-3-3. Piping "A"size selection rule


Outdoor Model
Pipe(High pressure)
22.20 [7/8"]
P144TSHMU,YSHMU
P168TSHMU,YSHMU
22.20 [7/8"]
P192TSHMU,YSHMU
22.20 [7/8"]
P216TSHMU,YSHMU
28.58 [1-1/8"]
P240TSHMU,YSHMU
28.58 [1-1/8"]

(mm [in.])
Pipe(Low pressure)
28.58 [1-1/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
(mm [in.])
Pipe(Gas)
15.88 [5/8"]

Table3-2-3-5. Piping "C", "D", "E" size selection rule


Total down-stream Indoor capacity Pipe(Liquid)
P72 or less
9.52 [3/8"]
P73 to P108
9.52 [3/8"]
P109 to P126
12.70 [1/2"]
P127 to P144
12.70 [1/2"]
P145 to P168
15.88 [5/8"]

Pipe(HP Gas)
15.88 [5/8"]
19.05 [3/4"]
19.05 [3/4"]
22.20 [7/8"]
22.20 [7/8"]

(mm [in.])
Pipe(LP Gas)
19.05 [3/4"]
22.20 [7/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]
28.58 [1-1/8"]

R2-SERIES
SYSTEM DESIGN

Table3-2-3-4. Piping "B" size seleciton rule


Total down-stream Indoor capacity Pipe(Liquid)
P54 or less
9.52 [3/8"]

HP : High pressure, LP:Low pressure

Table3-2-3-6. Piping "F", "G", "H" size selection rule


(mm [in.])
Outdoor Model
Pipe(High pressure) Pipe(Low pressure)
P72THMU,YHMU
15.88 [5/8"]
19.05 [3/4"]
P96THMU,YHMU
19.05 [3/4"]
22.20 [7/8"]
P120THMU,YHMU
19.05 [3/4"]
28.58 [1-1/8"]

Table3-2-3-7. Piping "a", "b", "c", "d"size selection rule


(mm [in.])
Indoor Unit size
Pipe(Liquid)
Pipe(Gas)
P06 to P18
6.35 [1/4"]
12.70 [1/2"]
P24 to P54
9.52 [3/8"]
15.88 [5/8"]
P72
9.52 [3/8"]
19.05 [3/4"]
P96
9.52 [3/8"]
22.20 [7/8"]

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-29

3. Piping Design

DATA U4

3-2-4. Total piping length restrictions(m)

[PURY-P72, 96THMU-A, PURY-P72, 96YHMU-A]

[PURY-P192TSHMU-A, PURY-P192YSHMU-A]
1000
Tot al extended pipe length (m)

Tot al extended pipe length (m)

1000
900
800
700
600
500
400
300
200

900
800
700
600
500
400
300
200

10

20

30

40

50

60

70

80

90 100 110

10

Distance between outdoor unit and BC controller(m)

[PURY-P120, 144, 168T(S)HMU-A, PURY-P120, 144, 168Y(S)HMU-A]

40

50

60

70

80

90 100 110

1000
Tot al extended pipe length (m)

Tot al extended pipe length (m)

30

[PURY-P216, 240TSHMU-A, PURY-P216, 240YSHMU-A]

1000
900
800
700
600
500
400
300
200

900
800
700
600
500
400
300
200

10

20

30

40

50

60

70

80

90 100 110

R2-SERIES
SYSTEM DESIGN

Distance between outdoor unit and BC controller(m)

R2SD-30

20

Distance between outdoor unit and BC controller(m)

R2-SERIES SYSTEM DESIGN (Feb. 2009)

10

20

30

40

50

60

70

80

90 100 110

Distance between outdoor unit and BC controller(m)

3. Piping Design

DATA U4

3-2-4. Total piping length restrictions(ft.)

[PURY-P72, 96THMU-A, PURY-P72, 96YHMU-A]

[PURY-P192TSHMU-A, PURY-P192YSHMU-A]
3000
Tot al extended pipe length (ft.)

Tot al extended pipe length (ft.)

3000
2500
2000

1804 ft.

1500

984 ft.
1000
500
0

2500 2461 ft.


2000
1500
1000
500
0

50

100

150

200

250

300

350

50

[PURY-P120, 144, 168T(S)HMU-A, PURY-P120, 144, 168Y(S)HMU-A]

100

150

200

250

300

350

Distance between outdoor unit and BC controller(ft.)

Distance between outdoor unit and BC controller(ft.)

[PURY-P216, 240TSHMU-A, PURY-P216, 240YSHMU-A]

3000

3000
Tot al extended pipe length (ft.)

Tot al extended pipe length (ft.)

1640 ft.

2500
2000 1969 ft.
1500

1148 ft.

1000
500
0

2625 ft.
2500

1969 ft.

2000
1500
1000
500
0

50

100

150

200

250

300

350

Distance between outdoor unit and BC controller(ft.)

50

100

150

200

250

300

350

Distance between outdoor unit and BC controller(ft.)

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-31

3. Piping Design

DATA U4

3-2-5. PURY-P-T(S)HMU/Y(S)HMU's calculation of additional refrigerant charge


Sample connection (with 3 BC controller and 6 indoor units)
OU
(Main unit)

OU
(Sub unit)
Outdoor Twinning kit (High/Low press.)
CMY-R100VBK:
The Low press. kit must be placed in the outdoor unit that has a larger capacity index
of the two, regardless of the relative positions of the outdoor units or their addresses.
(If outdoor units that have the same capacity are used in combination, the distributor
can be placed in either outdoor unit.)
The High press. kit is to be installed in the field.

BC controller (Main BC)

5 : P54

BC controller (Sub BC)

C
CMY-Y102S-G
(Joint)

Reducer (P06-P18)
(attached with BC controller)

IU

CMY-Y202-G2
CMY-Y102L-G2
CMY-Y102S-G2
(Joint)

BC controller (Sub BC)

B
b

IU

IU

IU

IU

1 : P18

2 : P96

3 : P06

4 : P08

CMY-R160-J
(Joint)

IU
6 : P72

Amount of additional refrigerant to be charged


Refrigerant for extended pipes (field piping) is not factory-charged to the outdoor unit. Add an appropriate amount of refrigerant for each pipes on site.
Record the size of each high pressure pipe and liquid pipe, and the amout of refrigerant that was charged on the outdoor unit for future reference.
Calculating the amount of additional refrigerant to be charged
The amount of refrigerant to be charged is calculated with the size of the on-site-installed high pressure pipes and liquid pipes, and their length.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1kg[4oz]. (i.e., 16.08 kg = 16.1 kg)
<Amount of additional refrigerant to be charged>
Calculating the amount of additional refrigerant to be charged
Additional refrigerant
charge

(kg)[oz]

Liquid Piping size


Total length of
15.88mm[5/8 in]
(m)
(ft)

0.2(kg/m)
2.16(oz/ft)

High pressure
pipe size
Total length of
28.58mm[1-1/8 in]
(m) 0.36(kg/m)
(ft) 3.88(oz/ft)

Liquid Piping size


Total length of
12.7mm[1/2 in]
(m)
(ft)

0.12(kg/m)
1.30(oz/ft)

Total Outdoor Unit


Model Name

Additional Charge

P72

3.0 kg[106oz]

P96

4.5 kg[160oz]

High pressure
pipe size
Total length of
22.2mm[7/8 in]
(m) 0.23(kg/m)
(ft) 2.48(oz/ft)

Liquid Piping size


Total length of
9.52mm[3/8 in]
(m)
(ft)

0.06(kg/m)
0.65(oz/ft)

High pressure
pipe size
Total length of
19.05mm[3/4 in]
(m) 0.16(kg/m)
(ft) 1.73(oz/ft)

Liquid Piping size


Total length of
6.35mm[1/4 in]
(m)
(ft)

0.024(kg/m)
0.26(oz/ft)

BC controller
(Sub) Total Units

Additional Charge

1.0 kg[36oz]

Models

~ 27

2.0 kg [71 oz]

2.0 kg[71oz]

Models

28 ~ 54

2.5 kg [89 oz]

Models

55 ~ 126

3.0 kg [106 oz]

P120

Total Capacity of
Connected Indoor Units

Additional Charge

P144

6.0 kg[212oz]

Models 127 ~ 144

3.5 kg [124 oz]

P168

7.5 kg[265oz]

Models 145 ~ 180

4.5 kg [159 oz]

Models 181 ~ 234

5.0 kg [177 oz]

Models 235 ~ 273

6.0 kg [212 oz]

Models 274 ~ 307

8.0 kg [283 oz]

P192
P216

9.0 kg[318oz]

P240

Amount of factory charged refrigerant

R2-SERIES
SYSTEM DESIGN

High pressure
pipe size
Total length of
15.88mm[5/8 in]
(m) 0.11(kg/m)
(ft) 1.19(oz/ft)

Outdoor unit
Model
P72
P96
P120

11.8 kg[416oz]

9.0 kg [318 oz]

Models 343 ~ 411

10.0 kg [353 oz]

Models 412 ~

12.0 kg [424 oz]

Sample calculation

Charged amount
10.5 kg[370oz]

Models 308 ~ 342

A:
B:
C:
D:
E:
F:
G:

28.58 [1-1/8"]
9.52 [3/8"]
12.70 [1/2"]
9.52 [3/8"]
9.52 [3/8"]
22.20 [7/8"]
22.20 [7/8"]

40m [131ft.]
10m [32ft.]
10m [32ft.]
5m [16ft.]
5m [16ft.]
2m [6ft.]
1m [4ft.]

Indoor
1 : P18
2 : P96
3 : P06
4 : P08
5 : P54
6 : P72

a:
b:
c:
d:
e:
f :

6.35 [1/4"]
9.52 [3/8"]
6.35 [1/4"]
6.35 [1/4"]
9.52 [3/8"]
9.52 [3/8"]

5m [16ft.]
3m [10ft.]
2m [6ft.]
3m [10ft.]
3m [10ft.]
10m [32ft.]

Total length for each pipe size :

28.58
A = 40m [131ft.]
22.20
F+G = 2+1 = 3m [10ft.]
12.70
C = 10m [32ft.]
9.52
B+D+E+b+e+f = 36m [116ft.]
6.35
a+c+d =10m [32ft.]
Therefore, additional refrigerant charge
= 40 0.36 + 3 0.23 + 10 0.12 + 36 0.06 + 10 0.024 + 9.0 + 2.0 + 6.0
(kg) = 37.69kg
= 37.7kg
or
Therefore, additional refrigerant charge
(oz)

R2SD-32

= 131 3.58+10 2.48+32 1.30+116 0.65+32 0.26+318+71+212


= 1220.1oz
= 1220oz

R2-SERIES SYSTEM DESIGN (Feb. 2009)

4. Installation

DATA U4

4-1. PURY-P-T(S)HMU/Y(S)HMUs Installation


4-1-1. PURY-P-T(S)HMU/Y(S)HMUs requirement on installation site
1.
2.
3.
4.
5.
6.
7.
8.

No direct thermal radiation to the unit;


No possibility of annoying the neighbors by the sound of the unit;
Avoid the sites where strong winds blow.
With strength to bear the weight of the unit;
Drain flow from the unit needs to be considered during heating mode.
Enough space for installation and service as shown at 4-1-2;
Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.
The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-33

4. Installation

DATA U4

4-1-2. Spacing PURY-P-T(S)HMU/Y(S)HMU


In case of single installation
Secure enough space around the unit as shown in the figure.
<A> : Top view

A : Front

C : Back

<B> : Side view

B : Unit height

D : Air outlet guide (Procured at the site)

<C> : When there is little space up to an obstruction

(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall

300*
[11-13/16]

450*
[17-23/32]

15* [19/32]

15* [19/32]

<A>
(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall

100*
[3-15/16]

50* [1-31/32]

450*
[17-23/32]

50* [1-31/32]

<A>

500

A
[19-11/16]

(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction

<B>

When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below,
add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.
<Wall height limit> Front: Up to the unit height
Back: Up to 500mm [19-11/16 in.] from the unit bottom
Side: Up to the unit height

R2-SERIES
SYSTEM DESIGN

(4) If there are obstacles at the upper part of the unit

1000
[39-3/8]

45

240
[9-15/32]

50 [1-31/32]
R2SD-34

<C>

R2-SERIES SYSTEM DESIGN (Feb. 2009)

(Unit : mm [in.])

4. Installation

DATA U4

In case of collective installation and continuous installation


A : Front

C : Wall height (H)

B : Must be open

When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and
passageways between groups of units as shown in the figures.
At least two sides must be left open.

300*
300*
[11-13/16] [11-13/16]

100*
[3-15/16]

30
[1-3/16]

450*
[17-23/32]

900
[35-7/16]

B
A

900
[35-7/16]

300*
[11-13/16]

300*
[11-13/16]

As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
an asterisk.

100
[3-15/16]

450*
[17-23/32]

B
A

450*

[17-23/32]

1000*
[39-3/8]

450

450

100*

[17-23/32] [17-23/32] [3-15/16]

15*

R2-SERIES
SYSTEM DESIGN

450
450
[17-23/32] [17-23/32]

(Unit : mm [in.])

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-35

4. Installation

DATA U4

4-1-3. Piping direction to PURY-P-T(S)HMU/Y(S)HMU


4-1-3-1. Lifting method
When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.
Support the unit at four points with two ropes, and avoid giving mechanical shock.
Suspension rope angle must be 40 or less, so as to avoid compressing fan guard.
Use two ropes, each at least 8m [26 ft.] in length
Use ropes strong enough to support the weight of the unit.
Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempted.)
Use protective pads to keep the ropes from scratching the panels on the unit.
(Unit : mm [ft.])

8 [26]

40

R2-SERIES
SYSTEM DESIGN

8 [26]

CAUTION
Exercise caution when transporting products.
Products weighing more than 20 kg [45 LBS] should not be carried alone.
Do not carry the product by the PP bands.
To avoid the risk of injury, do not touch the heat exchanger fins.
Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.
When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.

R2SD-36

R2-SERIES SYSTEM DESIGN (Feb. 2009)

4. Installation

DATA U4

4-1-3-2. Installation
Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or
during an earthquake.
Install the unit on a durable base made of such materials as concrete or angle steel.
Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
noise from being transmitted from the unit through walls and floors.
When using a rubber cushion, install it so that the cushion covers the entire width of the unit leg.
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.
Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16 in.].
This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.

WARNING
A

: M10 anchor bolt procured at the site.

: Corner is not seated.

: Fixing bracket for hole-in anchor bolt


(3 locations to fixwith screws).

: Detachable leg

30mm
[1-3/16 in.]

<Without detachable leg>

Properly install the unit on a surface that can withstand the weight of
the unit. Unit installed on an unstable surface may fall and cause injury.

WARNING
Take appropriate safety measures against strong winds and earthquakes to prevent the unit from falling.

Install the unit in such a


way that the corner of
the angle bracket at the
base of the unit shown
in the figure is securely
supported. The brackets
may bend if they are not
securely supported.

Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor units
during operation.), piping route, and wiring route when performing foundation work.

4-1-3-3. Anchor bolt positions


Collective installation

7243 [(28-13/32~28-5/8)]

(Unit : mm [in.])

7243 [(28-13/32~28-5/8)]

Individual installation

30 [1-3/16]
190 [7-1/2]

(For maintenance)

30 [1-3/16]
190 [7-1/2]

Leave a minimum of 30 mm [1-3/16 in.] between units.

P72

P96, P120

7602 [29-15/16(29-27/32~30)] 10602 [41-3/4(41-21/32~41-13/16)]

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-37

R2-SERIES
SYSTEM DESIGN

PURY

4. Installation

DATA U4

4-1-3-4. Installation
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in.] in height.

Bottom view

2X2-14X20
[1/8x1/8-9/16x13/16]
Oval hole

80
[3-5/32]

1060 [41-3/4]
(Mounting pitch)

Bottom view

80
[3-5/32]

(760 [29-15/16])

Refrigerant service
valve <Low pressure>

724(721 727)
[28-13/32~28-5/8]
(Mounting pitch)

Refrigerant service
valve <High pressure>

Installation base parallel to the units front panel

18
[23/32]

84 [3-5/16]

145 [5-23/32]
131 [5-3/16]

(760 [29-15/16])

724(721 727)
[28-13/32~28-5/8]
(Mounting pitch)

18
[23/32]

86 [3-13/32]

760 [29-15/16]
80
(Mounting pitch) [3-5/32]

(Unit : mm [in.])

150
[5-29/32]
83
[3-9/32]

18
[23/32]

80
[3-5/32]

Refrigerant service
valve <Low pressure>

18
[23/32]

Refrigerant service
valve <High pressure>

145 [5-23/32]

186
[7-11/32]

271
[10-11/16]
301
[11-7/8]
216
[8-17/32]

2X2-14X20
[1/8x1/8-9/16x13/16]
Oval hole

92 [3-5/8]

131 [5-3/16]

145 [5-23/32]

251 83
[9-29/32] [3-9/32]

P96, P120

145 [5-23/32]

(Unit : mm [in.])
221 150
[8-23/32] [5-29/32]

94 [3-23/32]

P72

Installation base perpendicular to the units front panel

4-1-3-5. Refrigerant pipe routing


The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.

R2-SERIES
SYSTEM DESIGN

This unit allows two types of pipe routing:


Bottom piping
Front piping

CAUTION

Example of closure materials


Fill the gap at the site
(field supply)

To prevent small animals and water from entering the unit and damage its parts, close the gap
around the edges of through holes for pipes and
wires with filler plates.

The figure above shows a unit on which a low-pressure twinning pipe kit is not installed.

R2SD-38

R2-SERIES SYSTEM DESIGN (Feb. 2009)

4. Installation

DATA U4

4-1-3-6. Twinning on the outdoor unit side <PURY-P-T(S)HMU/Y(S)HMU>


The tilt angle of the twinning pipe
The tilt angle of the twinning pipe must be within 15 with the horizontal plane.
Tilting the twinning pipe more than specified will cause damage to the unit.
Note. Refer to the figure below for the installation
position of the twinning pipe.
Twinning pipe on the
high-pressure side

15

The length of the straight part of the pipe before the branching (high-pressure side)
For the twinning kit, always use the accessory piping parts.
The length of the straight part of pipe connected in front of the
twinning pipe must be 500 mm [19 in.] or longer.
(Connect the field piping so that the length of the straight part
of pipe connected in front of the twinning pipe can be 500 mm
[19 in.] or longer.)
If the length is less than 500 mm [19 in.], it will cause damage
to the unit.

Inclination tolerance of the twinning pipe is 15


relative to the horizontal plane.

The piping connection (high-pressure side only)


Install the pipe between outdoor unit and high-pressure twinning
pipe so that the pipe slopes down toward the twinning pipe.

Downslope

To BC controller

High-pressure twinning pipe

When high-pressure twinning pipe is installed above the base of the


outdoor unit, it should be installed no more than 200mm [7 in.] from the base.

Outdoor unit 1

Outdoor unit 2

High-pressure
twinning pipe
To BC controller
200mm [7 in.] max.

R2-SERIES
SYSTEM DESIGN

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-39

4. Installation

DATA U4

4-1-3-7. Twinning on the outdoor unit side <PURY-P-T(S)HMU/Y(S)HMU>


See the following drawing for connecting the pipes between the outdoor units.

A : Twinning pipe (low-pressure side)


B : Twinning pipe (high-pressure side)

C : On-site piping (low-pressure connecting pipe: between outdoor units)


D : On-site piping (low-pressure main pipe: to BC controller)
E : On-site piping (high-pressure main pipe: to BC controller)
F : Straight run of pipe that is 500 mm [19 in.] or more
See the Installation Manual for the details of Twinning pipe installation.

D
E

CAUTION

R2-SERIES
SYSTEM DESIGN

The length of the straight pipe must be 500mm (19 in.) or longer.
If not, it may cause improper operation.

R2SD-40

R2-SERIES SYSTEM DESIGN (Feb. 2009)

4. Installation

DATA U4

4-1-4. Weather countermeasure for PURY-P-T(S)HMU/Y(S)HMU


In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in normal
and good condition in winter time. Even in the other areas, full consideration is required for installation of unit in order to prevent
abnormal operations caused by wind or snow. When rain and snow directly fall on unit in the case of air-conditioning operations in 10 or less degrees centigrade outdoor air (50 or less degrees fahrenheit outdoor air) , mount inlet and outlet ducts
on unit for assuring stable operations.
Countermeasure to snow and wind
Prevention the Outdoor unit from wind and snow damages in cold or snowy areas, snow hood shown below is recommended
and helpful.
750 [29-17/32]

1206 [47-1/2]

800 [31-1/2]

906 [35-11/16]

800 [31-1/2]

Snow hood

(920)[36-1/4]

1324 [52-5/32]
86
[3-13/32]

453
760 [29-15/16] [17-27/32]

453
[17-27/32]

<Side view>

Outlet

B
B

(760)
[29-15/16]

86
[3-13/32]

1324 [52-5/32]

(1220)[48-1/16]

910 [35-27/32]

453
[17-27/32]

453
[17-27/32]

1210 [47-21/32]

<Front view>

453
[17-27/32]

<Front view>

Inlet

Note:
1. Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base
shall not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind slip
through the structure. (If frame base is too wide, snow will be accumulated on it.)
2. Install unit so that wind will not directly lash against openings of inlet and outlet ducts.
3. Build frame base at customer referring to this figure.
Material : Galvanized steel plate 1.2T [1/16 in. T]
Painting : Overall painting with polyester powder
Color
: Munsell 5Y8/1 (same as that of unit)
4. To install units side by side, install a filler plate between
the fan guard and the outlet-side snow hood as shown in Figure A.
(The filler plate provided accommodates the installation pitch of between 30-80 mm [1-3/16~3-5/32 in.].)
5. When the unit is used in a cold region and the heating operation is continuously
Figure A
performed for a long time when the outside air temperature is below freezing, install
Filler plate
a heater to the unit base or take other appropriate measures to prevent water from freezing on the base.

A Wind

A
Install the outdoor unit where seasonal
winds do not blow directly against the
unit, such as behind a building.

Install the outdoor unit to avoid having


seasonal winds against the front of air
outlet/inlet on the unit.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-41

R2-SERIES
SYSTEM DESIGN

Countermeasure to wind
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.
A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.
To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away
from the direction of the wind.

5. STANDARD AND SEACOAST PROTECTION (-BS) TREATMENT


5-1. R2-Series
Component

Base Material

Standard
Models

Seacoast
Protection
Models (-BS)

External Panel Base

Alloyed Galvanized Steel


Sheet

External Front Panel

Alloyed Galvanized Steel


Sheet

Alloyed Galvanized Steel


Sheet

Pillar

Galvanized Steel Sheet


Compressor Cover

Galvanized Aluminum
Sheet

Internal Surface

Thermoset Polyester-resin
Powder Coating

70m

70m

Polyester-resin Coating

15m

5m

Thermoset Polyester-resin
Powder Coating

85m

75m

Polyester-resin Coating

30m

Thermoset Polyester-resin
Powder Coating

70m

70m

Thermoset Polyester-resin
Powder Coating

70m

70m

300m

300m

Thermoset Polyester-resin
Powder Coating

70m

70m

Cellulose- and Polyurethaneresin Coating (Blue Fin)


(no unusual rust development
to 480 hours)

1m

Cellulose- and Polyurethaneresin Coating (Blue Fin)


(no unusual rust development
to 960 hours)

1 - 1.5m

Fin Guard

Steel Wires

Weather-resistant
Polypropylene-resin Coating

Fan Guard and Drum

Weather-resistant
Polypropylene Plastic

No Treatment

Fan

Weather-resistant Acrylic
Nitrile Styrene Plastic

Fan Motor Frame

Galvanized Steel Sheet

Fan Motor Shaft

High-carbon S35C Steel

Fan Motor Support

Galvanized Steel Sheet

Heat Exchanger
(Fin Only)

Galvanized Steel Sheet


Galvanized Aluminum
Sheet

Printed Circuit Board

Epoxy Resin

Screws

10m

Zinc-nickel Alloy Plating with


a Chromate Film

5m

Material

Thermoset Polyester-resin
Powder Coating

Cellulose- and Polyurethaneresin Coating (Blue Fin)

Test
Conditions

Salt-spray Test Method: JIS


K2371 based on ISO9227

Salt-spray Test Method: JIS Z2371


based on ISO9227

R2SD-42

70m

Polyurethane Coating

984 (300m)
Direct Exposure to Sea Breezes
Facing Inland
Seacoast Protection (-BS) Models Standard Models
Facing Sea
Seacoast Protection (-BS) Models
On an Island
Seacoast Protection (-BS) Models
Indirect Exposure to Sea Breezes
Facing Inland
Seacoast Protection (-BS) Models Standard Models
Facing Sea
Seacoast Protection (-BS) Models
On an Island
Seacoast Protection (-BS) Models

No unusual rust
development to
480 hours

Thermoset Polyester-resin
Powder Coating

Distance from the Sea


1,640 (500m)
3,281 (1km)

Conform to JRA9002 Criteria


(960-hour test)

Rust-prevention Coating

No Treatment

Application Guide

Test
Results

No Treatment

No Treatment

Steel

No Treatment

No Treatment

Aluminum Plate

Electrical Parts Box

Coating Thickness
External Surface

No Treatment

R2-SERIES
SYSTEM DESIGN

Surface
Treatment

DATA U4

No unusual rust
development to
960 hours

For optimum performance, follow the cautions


listed below.
1. Avoid installing the unit in a location that is
subjected to direct sea winds.
2. Do not attach a sunshade to the unit. Let the rain
wash away any salt residue that may adhere to the
unit.
3. Unit should be installed following instructions
for proper operation and to ensure optimum water
drainage.
4. Periodically wash the unit.
5. If the panels become scratched, repair as soon as
possible.
6. Inspect the unit at regular intervals. Paint the unit
or replace parts when necessary.
Blue Fin treatment is an anti-corrosion treatment
that is applied to the condenser coil to protect it
against airborne contaminants.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

6. CAUTIONS

DATA U4

The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.
The following standard may be applicable if no local regulation or standard is available.

6-1. Refrigerant Properties


R410A refrigerant is harmless and incombustible. R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room
has possibility to lead to a hypoxia situation. Therefore, the critical concentration specified below shall not be exceeded even if the leakage
happens.

Critical concentration
Critical concentration is the maximum refrigerant concentration at which no harm would occur if immediate measures are taken when
refrigerant leakage happens.
Critical concentration of R410a: 0.30kg/m3 [0.0187 lbs./ft.3]
(The weight of refrigeration gas per 1 m3 [1 ft.3] air conditioning space.);
The critical concentration is per ISO5149, EN378-1 (other codes and standards may establish different values for critical concentration).

For CITY MULTI systems, the concentration of refrigerant leaked should not exceed the critical concentration in any situation.

6-2. Confirm the Critical Concentration and Perform Countermeasures


The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)
leaked into a room divided by its room capacity (V). It is referable to Fig. 6-1. The refrigerant weight includes its original charge and
additional charge at the site.
The additional charge is calculated according to 3-2-5. "PURY-P-T(S)HMU/Y(S)HMU's calculation of additional refrigerant charged", and shall
not be over charged at the site. Procedure 6-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to
take countermeasures against a possible leakage.
Outdoor unit (No.1)

Outdoor unit (No.1)

Outdoor unit (No.2)

Flow of refrigerant

Flow of refrigerant

Indoor unit

Flow of refrigerant

Indoor unit

Maximum refrigerant leakage concentration (Rmax)


Rmax=Wmax / V

Maximum refrigerant leakage concentration (Rmax)


Rmax=Wmax / V
W1: Refrigerant weight of Outdoor unit No.1
where, Wmax=W1+W2 W2: Refrigerant weight of Outdoor unit No.2

Fig. 6-1 The maximum refrigerant leakage concentration

Refrigerant pipe (high pressure pipe)

Ventilation air supply fan (always ON)


Refrigerant pipe

Ventilation air supply fan

Ventilation air supply fan

to Outdoor unit

Indoor unit
Indoor space

(Floor)

(Floor)
Opening

Indoor space

Indoor unit

(Floor)
Opening

Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


[At 0.3m height from the floor]

Fig. 6-2. Ventilation air supply always ON

to Outdoor unit

to Outdoor unit

Indoor unit
Indoor space

Refrigerant stop valve

Refrigerant pipe

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


[At 0.3m height from the floor]

Fig. 6-3. Ventilation air supply upon sensor action Fig. 6-4. Ventilation air supply and refrigerant
shut-off upon sensor action

Note 1. Countermeasure 3 should be done in a proper way in which the ventilation air supply shall be on whenever the leakage happens .
Note 2. In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.
The piping should consider the extension due to the temperature variation.

R2-SERIES SYSTEM DESIGN (Feb. 2009)

R2SD-43

R2-SERIES
SYSTEM DESIGN

6-2-1.Find the room capacity (V),


If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space are
considered as one. The total space shall be added up.
6-2-2.Find the possible maximum leakage (Wmax) in the room. If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refrigerant of the Outdoor units.
6-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).
6-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3 [0.0187 lbs./ft.3].
If no, then the CITY MULTI is safe against refrigerant leakage.
If yes, following countermeasure is recommended to do at site.
Countermeasure 1: Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.
e.g. make the upper and lower seams of door big enough.
Countermeasure 2: Smaller total charge (making Wmax smaller)
e.g. Avoid connecting more than 1 Outdoor unit to one room.
e.g. Using smaller model size but more Outdoor units.
e.g. Shorten the refrigerant piping as much as possible.
e.g. Remove unit from space.
Countermeasure 3: Ventilation air in from the ceiling.
As the density of the refrigerant is bigger than that of the air. Ventilation air from the ceiling is better than air exhausting from the ceiling.
Ventilation air supply solution refers to Fig. 6-2~4.

DATA U4

CITY MULTI S-SERIES


System Design
1. Electrical work............................................................................................................................................... SSD-2
1-1. General Cautions........................................................................................................................................... SSD-2
1-2. Power Supply for Indoor Unit and Outdoor Unit............................................................................................. SSD-3
1-3. Power Cable Specifications............................................................................................................................ SSD-5
1-4. Power Supply Examples................................................................................................................................ SSD-5
2. M-NET control................................................................................................................................................... SSD-6
2-1. Transmission Cable Length Limitation............................................................................................................ SSD-6
2-2. Transmission Cable Specifications................................................................................................................. SSD-7
2-3. System Configuration Restrictions................................................................................................................. SSD-8
2-4. Address Setting............................................................................................................................................ SSD-11
3. Piping Design.................................................................................................................................................... SSD-18
3-1. R410A Piping Material................................................................................................................................. SSD-18
3-2. PUMY-P-NHMUs Piping Design.................................................................................................................. SSD-19
4. Installation....................................................................................................................................................... SSD-21
4-1. PUMY-P-NHMUs Installation....................................................................................................................... SSD-21
5. Standard and Seacoast Protection (-BS) Treatment Specifications........................................ SSD-24
5-1. S-Series....................................................................................................................................................... SSD-24
6. CautionS............................................................................................................................................................. SSD-25
6-1. Refrigerant Properties.................................................................................................................................. SSD-25
6-2. Confirm the Critical Concentration and Perform Countermeasures............................................................. SSD-25

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-1

1. Electrical Work

DATA U4

1-1. General Cautions


Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission cable and power
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 208~230V power source to terminal block of transmission cable . If connected,electrical parts will be burnt
out.
Use 2-core shield cable for transmission cable . If transmission cables of different systems are wired with the same
multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.

Indoor unit

Outdoor
unit

ok
2-core shield cable

no
Multiplecore cable

Remote
controller
BC controller Indoor unit

Outdoor
unit

Indoor unit

Outdoor
unit

BC controller

Remote
controller
Indoor unit

Outdoor
unit

2-core shield cable

S-SERIES
SYSTEM DESIGN

Remote
controller

SSD-2

S-SERIES SYSTEM DESIGN (Feb. 2009)

Remote
controller

1. Electrical Work

DATA U4

1-2. Power Supply for Indoor Unit and Outdoor Unit

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-3

1. Electrical Work

PVFY-P12E00A
PVFY-P18E00A
PVFY-P24E00A
PVFY-P30E00A
PVFY-P36E00A

S-SERIES
SYSTEM DESIGN

PVFY-P48E00A
PVFY-P54E00A

SSD-4

S-SERIES SYSTEM DESIGN (Feb. 2009)

DATA U4

0.86 / 0.76
1.85 / 1.64
1.85 / 1.64
2.97 / 2.64

0.262 / 0.262

0.69 / 0.61

0.384 / 0.384
0.384 / 0.384
0.342 / 0.342

1.48 / 1.31
1.48 / 1.31

2.41 / 2.14
2.84 / 2.51
3.53 / 3.14

0.236 / 0.236
0.196 / 0.196
0.210 / 0.210

2.38 / 2.11
1.93 / 1.71
2.27 / 2.01
2.83 / 2.51

1. Electrical Work

DATA U4

1-2-2. Electrical characteristics of Outdoor unit at cooling mode.


Symbols: MCA : Min.Circuit Amps
SC : Starting Current

PUMY-P-NHMU
Model

RLA(A)

MCA(A)

Max. Fuse(A)

208V / 60Hz 187 to 228V

24.0

26

40

230V / 60Hz 207 to 253V

21.7

26

40

208V / 60Hz 187 to 228V

24.0

26

40

230V / 60Hz 207 to 253V

21.7

26

40

Volts / Hz

PUMY-P36NHMU(-BS)
PUMY-P48NHMU(-BS)

Voltage range

RLA : Rated Load Amps

Compressor

Outdoor Units

Fan

Output(kW)

SC(A)

Output(kW)

2.4

14

0.086X2

2.4

14

0.086X2

1-3. Power Cable Specifications


Thickness of wire for main power supply, ON / OFF capacities
1-phase 2-wire, 208V,60Hz
P36,P48
PUMY-P-NHMU
Indoor unit
1-phase 2-wire, 230V,60Hz
PUMY-P-NHMU
P36,P48
Indoor unit

Minimum wire thickness (mm2 / AWG)


Main cable
Branch
Ground
5.3 / 10
5.3 / 10

2.1 /14
2.1 /14
2.1 /14

Switch (A)
Capacity
Fuse
30
30
15
15

Breaker for
Breaker for current leakage
wiring (NFB)
30
30A 30mA or 100mA 0.1sec. or less
15
20A 30mA or 100mA 0.1 sec. or less

Minimum wire thickness (mm2 / AWG)


Main cable
Branch
Ground
5.3 / 10
5.3 / 10

2.1 /14
2.1 /14
2.1 /14

Switch (A)
Capacity
Fuse
30
30
15
15

Breaker for
Breaker for current leakage
wiring (NFB)
30
30A 30mA or 100mA 0.1sec. or less
15
20A 30mA or 100mA 0.1 sec. or less

1. Use a separate power supply for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum v alue f or metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,
use wiring such as YZW.
6. A switch with at least 3 mm [1 / 8 in] contact separation in each pole shall be provided by the Air conditioner installation.

WARNING
Be sure to use specified wires to connect so that no external force is impar ted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated over current may include some amount of direct current.

CAUTION
A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire.

1-4. Power Supply Examples


The local standards and/or regualtions is applicable at a higher priority.

1-4-1. PUMY-P-NHMU
breakers for wiring
and current leakage

Outdoor
unit

Power supply
1-phase 2 wire.
60Hz 208/230V

Grounded
15A breaker for wiring
and current leakage

Power supply
1-phase 2 wire.
60Hz 208/230V
1.6mm x 2
[AWG14]

pull box

1.25mm2 x 2
[AWG16]

1.6mm x 2
[AWG14]
Indoor unit
Group operation
Remote controller wire

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-5

S-SERIES
SYSTEM DESIGN

0.5~1.25mm2 x 2
[AWG20 ~ AWG16]

2. M-NET Control

DATA U4

2-1. Transmission Cable Length Limitation


2-1-1. Using MA Remote controller
Applicable to Outdoor as follows Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
PUMY-P-NHMU
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7
<=200m[656ft] 1.25mm2 [AWG16] or thicker
Max. length from MA to Indoor
a1+a2, a1+a2+a3+a4, a1
<=200m[656ft] DC 24V to AG-150A
n
<=10m[32ft]
0.75-2.0 mm2 [AWG18-14]
L1

Group1

OC

Group3

Group5

IC

IC

IC

IC

(01)

(04)

(05)

(06)

(51)

M1M2 S
TB7

TB3
M1M2

TB5
M1M2 S

TB15
1 2

TB5
M1M2 S

TB15
1 2

TB5
M1M2 S

TB15
1 2

TB5
M1M2 S

TB15
1 2

A B

A B

MA

MA

MA

L3

OC

L4
IC

(52)
TB7

TB5
M1M2 S

TB3
M1M2

IC

(03)

(07)

TB5 TB 15
M1M2 S 1 2

TB15
1 2

Power Supply Unit


PAC-SC51KUA

TB15
1 2

TB5
M1M2 S

a1

L6

IC

(02)

M1 M2 S

M1M2 S

a4

a3

A B

a2

Shielded
wire

a2

L2

a1

a1

a2

24VDC GND

L7

A B

AG-150A

A B S

MA
24VDC GND

OC: Outdoor unit; IC: Indoor unit; MA: MA remote controller

Ref.:TLLL_Y-MA-U

2-1-2. Using ME Remote controller


Applicable to Outdoor as follows Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
PUMY-P-NHMU
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft] 1.25mm2 [AWG16] or thicker
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7, L3+L5
<=200m[656ft] 1.25mm2 [AWG16] or thicker
Max. length from ME to Indoor
e1,e2,e3,e4
<=10m[32ft] *1 0.3-1.25 mm2[AWG22-16] *1
DC 24V to AG-150A
n
<=10m[32ft]
0.75-2.0 mm2 [AWG18-14]
*1. If the length from ME to Indoor exceed 10m, use 1.25 mm2[AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
L1

Group1

OC

Group3

Group5

IC

IC

IC

IC

(01)

(04)

(05)

(06)

(51)
TB3
M1M2

TB5
M1M2 S

TB5
M1M2 S

TB5
M1M2 S

L2

Shielded
wire

e2

e1

M1M2 S
TB7

A B

A B

A B

(105)

(155)

ME

ME

L3

L4

(52)
TB7
M1 M2 S

IC

IC

(02)

(03)
TB5
M1M2 S

TB5
M1M2 S

TB3
M1M2

IC
(07)
TB5
M1M2 S

Power Supply Unit


PAC-SC51KUA
M1M2S

e4

L6

L5

S-SERIES
SYSTEM DESIGN

e3

(101)
ME

OC

TB5
M1M2 S

24VDC GND
A B

L7

(103)
AG-150A

A B S

ME

24VDC GND

OC: Outdoor unit; IC: Indoor unit; ME: ME remote controller

SSD-6

S-SERIES SYSTEM DESIGN (Feb. 2009)

Ref.:TLLL_Y-ME-U

2. M-NET Control

DATA U4

2-2. Transmission Cable Specifications


Transmission cables (Li)
Type of cable

ME Remote controller cables

Cable size
Remarks
Connected with simple remote controller.

1.25

[AWG16]

MA Remote controller cables

Sheathed 2-core cable (unshielded)


CVV

Shielding wire (2-core)


CVVS, CPEVS or MVVS
0.3 1.25
(0.75 1.25

2
2

[AWG22 16]
[AWG18 16])

0.3 1.25
(0.75 1.25

When 10m [32ft] is exceeded, use cables with


the same specification as transmission cables.

2
2

[AWG22 16]
[AWG18 16])

Max length : 200m [656ft]

CVVS, MVVS : PVC insulated PVC jacketed shielded control cable


CPEVS : PE insulated PVC jacketed shielded communication cable
CVV
: PV insulated PVC sheathed control cable

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-7

2. M-NET Control

DATA U4

2-3. System Configuration Restrictions


2-3-1. Common restrictions for the CITY MULTI system
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
B) Maximum 2 remote controllers for 1 Group;
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC50(51)KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.

2-3-2. Ensuring proper communication power for M-NET


In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY and Controllers, the transmission
power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the
power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption by index Indoor units, LOSSNAY, controllers
Indoor unit

Indoor unit

Sized P06-P54

Sized P72,P96

BC controller
CMB

MA RC.LOSSNAY

ME Remote Contr.

PAR-21MAA
PAR-F27MEA
PAC-YT51CRA(B) PZ-52SF
PAR-FA32MA
LGH-RX-E
PZ-41SLB
0
1/4

Timers, System Contr.


PAC-SF44SRA
PAC-YT34STA
G-50A
AG-150A
1/2

ON/OFF Contr.

GB-50A
GB-24

PAC-YT40ANRA
GB-24

*RC : Remote Controller

Table 2-3-2 The equivalent power supply capability index of Trans.Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster
PAC-SF46EPA
25

Power supply unit


PAC-SC50KUA
6

PAC-SC51KUA
5

Outdoor unit

Outdoor unit

Connector TB3 and TB7 total *


32

Connector TB7 only


6

*If PAC-SC50(51)KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.

With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the airconditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System
controllers.If the total quantity reaches 40, a PAC-SF46EPA should be set.In this case, Indoor unit sized P72, 96 is
counted as 2 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption
reaches 32, a PAC-SF46EPA should be set.Yet, if a PAC-SC50(51)KUA is used to supply power at TB7 side, count from
index TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches
6, a PAC-SF46EPA should be set.

System example

TB7

TB3

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

01

Transmission
booster
(No.1)

02

ME remote
controller

S-SERIES
SYSTEM DESIGN

TB7

TB3
Outdoor unit

ME remote
controller

N1

N2
Within N2, conditions 1,2 should be followed.
1.The total quantity of Indoor units and ME remote controller
should not exceed 40.
*Indoor unit sized P72, 96 is counted as 2 units.
2.The total equivalent transmission power consumption
should not exceed 25.

Transmission booster (No.1) should be used,


if the total quantity of Indoor units and ME remote controllers
reaches 40, (Indoor unit sized P72, 96 is counted as 2);
or if the total equivalent transmission power consumption reaches 32.

UP

TRANSMISSION BOOSTER
MODEL

PAC-SF46EPA

POWER RATING

220-240V:0.7A ~/N
50

WEIGHT

3.4kg

MADE IN JAPAN

LOSSNAY
unit

CENTRALIZED CONTROLLER AG-150A

M-NET

Power supply unit


PAC-SC51KUA

24VDC

Centralized
Controller
AG-150A

PZ-52SF

LOSSNAY
unit
PZ-52SF

N4

N3
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 6.

SSD-8

Transmission
booster
PAC-SF46EPA
(No.2)

Within N4, the total equivalent transmission


power consumption should not exceed 25.

S-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-3-3. Ensuring proper power supply to System controller


The power to System controller (excluding LMAP03-U) is supplied via M-NET transmission line. M-NET transmission line
at TB7 side is called Central control transmission line while one at TB3 side is called Indoor-Outdoor transmission line.
There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC50KUA.
D) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.

2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB3.
If there is more than 1 Outdoor unit, it is necessary to
replace power supply switch connector CN41 with CN40
on one Outdoor unit.

Fig. 2-3-3-A

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

System controller
(excluding LMAP02-E)
Group

TB3
TB7
Replacement of
CN41 with CN40

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

ME remote controller
System
controller

Maximum 3 System controllers can be connected to TB3,


but maximum 2 in the case of G-50A.

2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
Maximum 3 System controllers can be connected to TB7
and receiving power from the Outdoor unit.
It is necessary to replace power supply switch connector
CN41 with CN40 on one Outdoor unit.

Fig. 2-3-3-B

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Replacement of
CN41 with CN40

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

ME remote controller
System
controller

Maximum 3 System controllers can be connected to TB7.

2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC50KUA.
Fig. 2-3-3-C

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

PAC-SC50KUA

Indoor unit

ME remote controller

System
controller

CAUTION
It is recommended that AG-150A/GB-50A/GB-24A are connected to TB7 because the controllers perform data backup.
If an air conditioner system has more than one Outdoor unit, AG-150A/GB-50A/GB-24A receiving transmission power at TB3 or TB7 on one of the Outdoor
units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A/GB-50A/GB-24A, and disrupt the whole system.
When applying apportioned electric power function, it is necessary to connect AG-150A/GB-50A/GB-24A to TB7 and has the own power supply unit
PAC-SC50KUA/PAC-SC51KUA.

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-9

S-SERIES
SYSTEM DESIGN

When using PAC-SC50KUA to supply transmission


power, the power supply connector CN41 should be kept
as it is. It is also a factory setting.
1 PAC-SC50KUA supports maximum 2 G-50A units due
to the limited power DC 12V at its TB3.
However, 1 PAC-SC50KUA supplies transmission power
at its TB2 equal to 6 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 6 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.

2. M-NET Control

DATA U4

2-3-3-D. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
When using PAC-SC51KUA to supply transmission
power, the power supply connector CN41 should be kept
as it is. It is also a factory setting.
1 PAC-SC51KUA supports maximum 1 AG-150A unit
due to the limited power DC 24V at its TB3.
However, 1 PAC-SC51KUA supplies transmission power
at its TB2 equal to 5 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 5 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.

Fig. 2-3-3-D

M-NET transmission lines


(Indoor-Outdoor transmission lines)

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

Indoor unit

M-NET transmission lines


(transmission lines
for central controller)

MA remote controller

Outdoor unit

Group

Group

TB3
TB7
Use CN41
as it is.

PAC-SC51KUA

Indoor unit

ME remote controller

System
controller

CAUTION
AG-150A is recommended to connect to TB7 because it performs back-up to a number of data.
In an air conditioner system has more than 1 Outdoor units, AG-150A receiving transmission power at TB3 or TB7 on one of the Outdoor units would have a
risk that the connected Outdoor unit failure would stop power supply to AG-150A, and disrupt the whole system.
When applying apportioned electric power function, AG-150A is necessary to connected to TB7 and has its own power supply unit
PAC-SC50KUA/PAC-SC51KUA.

2-3-4. Power supply to LM adapter LMAP03U

S-SERIES
SYSTEM DESIGN

1-phase 208-230V AC power supply is needed.


The power supply unit is not necessary when connecting only the LMAP03U. Yet, make sure to change the power supply
changeover connector CN41 to CN40 on the LM adapter.

SSD-10

S-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4. Address Setting


2-4-1. Switch operation

Unit address No. setting

01

2 3

7 8

01

7 8

2 3

45 6

D
BC E

F 0 12
3456

Address No. of outdoor unit, indoor unit and remote controller.


The address No. is set at the address setting board.

Rotary switch
Branch
No. setting

45 6

In order to constitute CITY MULTI in a complete system, switch


operation for setting the unit address No. and connection No. is
required.

789A

Caution for switch operations


Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.
MA remote controller
When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
The factory setting is Main .
ON

Setting the dip switches


1

The dip switches are at the bottom of the remote controller.


Remote controller Main/Sub and other function settings are performed
using these switches.
Ordinarily, only change the Main/Sub setting of SW1. (The factory settings are all ON .)
SW No

ON

SW contents Main

ON

OFF

Remote controller
Main/Sub setting

Comment

Main

Sub

When remote controller power turned on

Cooling/heating display in AUTO mode

Yes

No

When you do not want to display Cooling and Heating in the


Auto mode, set to No .

Intake temperature
display

Yes

No

When you do not want to display the intake temperature, set to No .

Set one of the two remote controllers at one group to Main .

Normally on Timer mode on

When you want to return to the timer mode when the power is restored after
a power failure when a Program timer is connected, select Timer mode .

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-11

2. M-NET Control

DATA U4

2-4-2. Rule of setting address


Unit

Address setting

Example

Note
9 0 1
7 8
7 8
7 8

7 8

45 6

45 6

01

45 6

45 6

45 6

100

10

0
9 1

0
9 1

7 8

7 8

0,2

0~5

0~9

100

10

9 0 1

9 0 1
2 3

7 8

45 6

45 6

45 6

7 8

The address automatically becomes "200" if it is set


as "00"

01

10

4 5 6

4 5 6

The address of main remote controller + 50

2 3

7 8

100

Fixed

The smallest address of indoor unit in the group + 100

01

7 8

7 8

7 8

7 8

7 8
7 8

45 6

45 6
01

10

2 3

201 ~ 250

The smallest address of indoor unit in same refrigerant


system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"

2 3

000, 201 ~ 250

01

Use the most recent address within the same group of


indoor units.
Set the address so that (1)<(2)<(3)

The place of "100" is fixed to "1"

2 3

Local remote controller

4 5 6

4 5 6

2 3

000, 201 ~ 250

01

01
2 3

1
Fixed

000, 201 ~ 250

10
9

151 ~ 199, 200

01

2 3

System controller

4 5 6

4 5 6

2 3

LMAP03U

10

Fixed

2 3

GB-24A
G-50A
GB-50A
AG-150A

9 0 1
2 3

2 3

ON/OFF controller

9 0 1

101 ~ 150

2 3

51 ~ 99, 100
(Note1)

System controller

2 3

ME, LOSSNAY
Remote controller
(Sub)

10

2 3

ME, LOSSNAY
Remote controller
(Main)

01 ~ 50

2 3

Outdoor unit

7 8

9 0 1

Indoor unit

10

S-SERIES
SYSTEM DESIGN

Note1: To set the address to "100", set it to "50"


Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.

SSD-12

S-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3. System example


Factory setting
Original switch setting of the outdoors, indoors, controllers, LMAP03U-E at shipment is as follows.
Outdoor unit
: Address: 00, CN41: ON, DipSW2-1: OFF
Indoor unit
: Address: 00
Remote controller
: Address: 100
LMAP
: Address: 247, CN41: ON, DipSW1-2: OFF

2-4-3-1. Example : Basic, Timer, Sub/main ME remote controller

Outdoor unit
(PUMY)

Main R/C : PAR-F27MEA


Sub R/C : PAR-F27MEA

Group 1

Group 2

Group 3

51
Indoor unit

01

CN41 CN40
DipSW2-1
OFF

02

03

04

05

TB3

101

103

153

105

Simple R/C

Main
R/C

Sub
R/C

Main
R/C

Ref : MA03-U1

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-13

2. M-NET Control

DATA U4

2-4-3-2. Example : AG-150A/GB-50A, TB7


Outdoor unit
(PUMY)

Group 1

Group 2

Group 3

Group 4

Group 5

01

02

03

04

05

51
CN41 CN40
TB7

TB7
DC24V

TB2

TB2

TB3

TB3

Power supply unit


(PAC-SC51KUA)

DipSW2-1
ON

TB3

Power supply unit


(PAC-SC51KUA)

101
Simple R/C

DC24V

000

000

GB-50A

AG-150A

103

104

105

Simple R/C

Simple R/C

Simple R/C

102
Simple R/C

*GB-50A doesnt need DC12V. No TB3 connection to power supply unit.


NOTE
It is necessary to turn on the DipSW 2-1 on the outdoor unit control board when the central controller is connected.
Be sure to connect other controllers (Ex. G-50A) when the simple R/C is used because the running mode can not be changed by simple R/C.
Ref : MA04

2-4-3-3. Example : Grouping in different refrigerant system


Outdoor unit
(PUMY)

51

Group 1

01

CN41 CN40
TB7

DipSW2-1
OFF

04

05

105

101
Group 4

56

10

CN41 CN40
DipSW2-1
OFF

03

TB3

Outdoor unit
(PUMY)

TB7

02

Group 2

Group 3

09

08

07

06

TB3

110

107

NOTE
It is necessary to change the connecter to CN40 on the outdoor unit control board (only one Outdoor unit / Heat source unit) when the group is set
between other refrigerant systems.
It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller
installation manual.

S-SERIES
SYSTEM DESIGN

Ref : MA06

SSD-14

S-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-4. Example : 2 Outdoor units, AG-150A, MA

Outdoor unit
(PUMY)

51
CN41 CN40
TB7

DipSW2-1
ON

Group 1

Group 2

Group 3

01

02

03

101

102

103

04

TB3

Outdoor unit
(PUMY)

55

Group 4

Group 5

Group 6

BC controller

56

CN41 CN40
TB7
Power supply unit
(PAC-SC51KUA)
TB2

DipSW2-1
ON

TB3

05

06
TB15

07

08
TB15

09
TB15

TB15

MA R/C
MA R/C

(Main)

(Sub)

MA R/C

TB3
DC24V

000
AG-150A
Ref : MA07-U1

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-15

2. M-NET Control

DATA U4

2-4-3-5. Example : TG-2000A


Outdoor unit
(PUMY)
51

Group 1

CN41 CN40

TB7

DipSW2-1
ON

Group 2

01

02

03

101

151

103

TB3

(000)
Outdoor unit
(PUMY)

AG-150A

54
P/S

Group 3

Group 4

Group 5

04

05

06

104

105

106

BC controller

55

CN41 CN40

LAN

DipSW2-1
ON

TB3

Outdoor unit
(PUMY)
57

Group 6

HUB

07

CN41 CN40

TB7

DipSW2-1
ON

Group 7

08

TB3

LOSSNAY

107

108

Outdoor unit
(PUMY)

TG-2000A

51

Group 8

BC controller

52

CN41 CN40

TB7

TB7

(000)

DipSW2-1
ON

01

02

03

101

151

103

Outdoor unit
(PUMY)
54

Group 10

Group 11

CN41 CN40

04

05

06

104

105

106

DipSW2-1
ON

58

CN41 CN40
DipSW2-1
ON

Group 12

TB3

BC controller
P/S

Group 9

TB3

Outdoor unit
(PUMY)
57

GB-50A

S-SERIES
SYSTEM DESIGN

09

Group 13

156

Group 14

07

08

09

107

108

158

TB3

P/S = Power supply unit


(PAC-SC51KUA)
NOTE
AG-150A/GB-50A can control maximum 50 indoor units.
TG-2000A can control maximum 40 AG-150As.
TG-2000A can control maximum 2000 indoor units.

Ref : MA08

SSD-16

S-SERIES SYSTEM DESIGN (Feb. 2009)

2. M-NET Control

DATA U4

2-4-3-6. Example : LONWORKS

Power supply unit


(PAC-SC51KUA)

Outdoor unit
AG-150A Heat source unit
(PUHY,PQHY,PUMY)
000
51

P/S

Group 1

CN41 CN40

TB7
LMAP

CN41 CN40
DipSW1-2
ON

01

02

03

101

151

103

TB3

DipSW2-1
ON

Outdoor unit
Heat source unit
(PURY,PQRY)
54

247

BC controller

Group 3

Group 4

Group 5

04

05

06

104

105

106

55

CN41 CN40

TB7

TB3

DipSW2-1
ON

Outdoor unit
Heat source unit
(PUHY,PQHY,PUMY)
Group 6

51
LMAP
TB7
CN41 CN40
DipSW1-2
OFF

DipSW2-1
OFF

LONWORKS

101

DipSW2-1
OFF

Outdoor unit
Heat source unit
(PUHY,PQHY,PUMY)

247

02

03

101

151

103

Group 11

Group 12

01

02

03

101

102

103

TB3

DipSW2-1
OFF

Outdoor unit
Heat source unit
(PURY,PQRY)
51

LMAP

Group 13

153

Group 14

BC controller

247

52

CN41 CN40

TB7
CN41 CN40
DipSW1-2
OFF

01

Group 10

CN41 CN40

TB7

Group 9

TB3

51

LONWORKS card

Group 8

52

CN41 CN40

LMAP

PC

102

BC controller

TB7

03
LOSSNAY

Outdoor unit
Heat source unit
(PURY,PQRY)
51

247

CN41 CN40
DipSW1-2
OFF

02

TB3

LMAP

CN41 CN40
DipSW1-2
OFF

Group 7

01

CN41 CN40

247

Group 2

DipSW2-1
OFF

01

02

03

101

102

152

TB3

LONWORKS card
LONWORKS card

Other equipments (lighting, security, elevator etc.)

Ref : MA09

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-17

S-SERIES
SYSTEM DESIGN

NOTE
LMAP (LMAP03U) can control 50 indoor units .
It is necessary to turn on the DipSW1-2 on the LMAP control board and the DipSW2-1 on the outdoor unit control board with central controllers
(Power supply unit).
It is necessary to change the connector to CN40 on the LMAP control board without central controllers (Power supply unit).

3. Piping Design

DATA U4

3-1. R410A Piping Material


Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types.
A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand.
B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness.
The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety
under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Ta ble 3-1, or You shall follow the local
industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.
Size (mm)
Size (inch) Radial thickness (mm) Radial thickness (mil)
[32]
6.35
1/4"
0.8
[32]
9.52
3/8"
0.8
[32]
12.7
1/2"
0.8
[40]
15.88
5/8"
1.0
[48]
19.05
3/4"
1.2
[40]
19.05
3/4"
1.0
[40]
22.2
7/8"
1.0
[40]
25.4
1"
1.0
[40]
28.58
1-1/8"
1.0
[44]
31.75
1-1/4"
1.1
[48]
34.93
1-3/8"
1.2
[56]
41.28
1-5/8"
1.4

Pipe type
Type-O
Type-O
Type-O
Type-O
Type-O
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H
Type-1/2H or H

* For pipe sized 19.05 (3/4") for R410A air conditioner, choice of pipe type is up to you.
* The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the
local standards.

Flare
Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions
mentioned below so as to achieve enough the air-tightness.
Pipe size
6.35 [1/4"]
9.52 [3/8"]
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]

A (For R410A)

(mm[in.])

Flare nut

9.1 [3/8"]
13.2 [9/16"]
16.6 [11/16"]
19.7 [13/16"]
24.0 [1"]

S-SERIES
SYSTEM DESIGN

Flare pipe

SSD-18

S-SERIES SYSTEM DESIGN (Feb. 2009)

Pipe size
6.35 [1/4"]
9.52 [3/8"]
12.70 [1/2"]
15.88 [5/8"]
19.05 [3/4"]

B (For R410A)
17.0 [3/4"]
22.0 [7/8"]
26.0 [1-1/16"]
29.0 [1-1/8"]
36.0 [1-7/16"]

(mm[in.])

3. Piping Design

DATA U4

3-2. PUMY-P-NHMUs Piping Design


3-2-1. PUMY-P-NHMU's piping length limitation, Piping dimension selection, Joint and Header selection rule

PUMY-P-NHMU

Note1. No Joint after Header; Piping direct to Indoor Unit from Header.
Note2. The system can be designed to use only Joints, only Header,
or use both Joints and Header.

Header

Capped

H(H')

The first joint

IU

IU

IU

L1

L2

Joint

IU

IU

IU
IU : Indoor unit , OU : Outdoor unit

Fig. 3-2-1A PUMY-P-NHMU piping scheme


Table3-2-1-1. PUMY-P-NHMU's piping length limitation
(m [ft.])
Item
Piping in the figure
Max. length
Total piping length
A+B+C+D+a+b+c+d+e+f 120 [393']
Farthest IU from OU (L1)
A+C+D+f / A+B+c
80 [262']
Farthest IU from the first Joint (L2)
C+D+f / B+c
30 [98']
Height between OU and IU (OU above IU) H
30 [98']
Height between OU and IU (OU under IU) H'
20 [65']
Height between IU and IU
h
12 [39']

Table3-2-1-2. PUMY-P-NHMU's piping "A"size selection rule


(mm [in.])
Outdoor and the first-Joint/Header
Pipe(Liquid)
Pipe(Gas)
PUMY-P-NHMU=CMY-Y62-G-E
9.52 [3/8"]
15.88 [5/8"]
PUMY-P-NHMU=CMY-Y64,Y68-G-E
9.52 [3/8"] 15.88 [5/8"]
Table3-2-1-3. PUMY-P-NHMU's piping"B","C","D"size selection rule (mm [in.])
Total down-stream Indoor capacity
Pipe(Liquid)
Pipe(Gas)
~ P62
9.52 [3/8"]
15.88 [5/8"]

OU: Outdoor Unit, IU: Indoor Unit

Table3-2-1-4. Indoor Unit's direct piping"a","b","c","d","e","f"size selection rule (mm [in.])


Indoor Unit size
Pipe(Liquid)
Pipe(Gas)
P06,P08,P12,P15,P18
6.35 [1/4"]
12.70 [1/2"]
P24,P27,P30,P36,P48,P54
9.52 [3/8"]
15.88 [5/8"]

PUMY-P-NHMU

Note1. No Joint after Header; Piping direct to Indoor Unit from Header;

Table3-2-1-5. PUMY-P-NHMU's Joint, Header selection rule


Joint
4-branch Header
CMY-Y62-G-E
CMY-Y64-G-E

L1

8-branch Header
CMY-Y68-G-E

* For details of installation of Joint, header, and distributor, refer to its Installation Manual.

L2
H (H')

Header
Capped
b

IU

IU

IU

IU

IU

IU
Fig. 3-2-1B PUMY-P-NHMU piping scheme
(m [ft.])
Max. length
120 [393']
80 [262']
30 [98']
30 [98']
20 [65']
12 [39']

Note4. Indoor capacity is described as its model size.


For example, PDFY-P08NMU-E,capacity P08;
Note5. Total down-stream Indoor capacity is the summary of the model size of Indoors
downstream.
For example, PDFY-P08NMU-E+PDFY-P06NMU-E: Total Indoor
capacity=P08+P06=P14.

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-19

S-SERIES
SYSTEM DESIGN

Table3-2-1B1. PUMY-P-NHMU's piping length limitation


Item
Piping in the figure
Total piping length
A+a+b+c+d+e+f
Farthest IU from OU (L1)
A+f
Farthest IU from Header (L2)
f
Height between OU and IU (OU above IU) H
Height between OU and IU (OU under IU) H'
Height between IU and IU
h

3. Piping Design

DATA U4

3-2-2. PUMY-P-NHMU's refrigerant charging calculation


Original refrigerant charge for PUMY-P-NHMU is 8.5 kg [18.75 lbs], including 3 kg [106 oz] for 50 m [164 ft.] total extended piping length use.
Thus, there is no need to charge additional refrigerant to the system if the total extended piping length is 50 m [164 ft.] or less.
If the total extended piping length is over 50 m [164 ft.], calculate the additional refrigerant using following procedure. Yet, if the calculated
result is negative, no additional charge is needed.
Total length of liquid
pipe sized
=
9.52 x 0.06 (kg/m)
3/8" x 0.65 [oz/ft.]

Additional
refrigerant charge

(kg)
[oz]

Total length of liquid


pipe sized
+
6.35 x 0.024 (kg/m)
1/4" x 0.26 [oz/ft.]

(m) x 0.06 (kg/m)


(ft.) x 0.65 [oz/ft.]

Original charge
-

(m) x 0.024 (kg/m)


(ft.) x 0.26 [oz/ft.]

Indoor 1:
Indoor 2:
Indoor 3:
Indoor 4:

Example:

P24
P15
P08
P06

3.0 (kg)
106 [oz]

A=9.52 [3/8"] 30 m [98 ft.] a=9.52 [3/8"]


b=6.35 [1/4"]
c=6.35 [1/4"]
d=6.35 [1/4"]

Total length of each liquid pipe is as follows


9.52 [3/8"]
A + a = 30 [98] + 15 [49] = 45 m [147 ft.]
6.35 [1/4"]
b + c + d = 10 [32] + 10 [32] + 20 [65] = 40 m [129 ft.]

PUMY-P48NHMU
A ( 30 m [98 ft.] )

a ( 15 m [49 ft.] )

b ( 20 m [65 ft.] )

b ( 10 m [32 ft.] )

P24

c ( 10 m [32 ft.] )

P15

Total length of liquid


pipe sized
=
9.52 x 0.06 (kg/m)

Additional
refrigerant charge
(kg)

P08

Total length of liquid


pipe sized
+
6.35 x 0.024 (kg/m)

45 (m) x 0.06 (kg/m)

2.70

0.66

P06

Original charge
-

40 (m) x 0.024 (kg/m)

0.96

3.0(kg)

3.00

0.7 kg (round-up)
Total length of liquid
pipe sized
=
3/8" x 0.65 [oz/ft.]

Additional
refrigerant charge
(oz)

Total length of liquid


pipe sized
+
1/4" x 0.26 [oz/ft.]

147 (ft.) x 0.65 [oz/ft.]

95.55

23.09 [oz]

S-SERIES
SYSTEM DESIGN

Original charge
-

129 (ft.) x 0.26 [oz/ft.]

33.54

1.5 [lbs] (round-up)

SSD-20

15 m [49 ft.]
10 m [32 ft.]
10 m [32 ft.]
20 m [65 ft.]

S-SERIES SYSTEM DESIGN (Feb. 2009)

106 [oz]

106

4. Installation

DATA U4

4-1. PUMY-P-NHMUs Installation


4-1-1. PUMY-P-NHMU's requirement on installation site
4-1-1-1. General cautions

4-1-1-3. Foundation for PUMY-P-NHMU

A. No direct thermal radiation to the unit.


B. Select a location from which sound emitted by the unit will
not inconvenience the neighbors.
C. Select a location permitting easy wiring and pipe access to
the power source and indoor unit.
D. Avoid locations where combustible gases may leak, be
produced, flow, or accumulate.
E. Note that water may drain from the unit during operation.
F. Select a level location that can bear the weight and
vibration of the unit.
G. Avoid locations where the unit can be covered by snow. In
areas where heavy snow fall is anticipated, special
precautions such as raising the installation location or
installing a hood on the air intake must be taken to prevent
the snow from blocking the air intake or blowing directly
against it. This can reduce the airflow and a malfunction
may result.
H. Avoid locations exposed to oil, steam, or sulfuric gas.
I. Use the transportation handles of the outdoor unit to
transport the unit. If the unit is carried from the bottom,
hands or fingers may be pinched.

A. Be sure to install the unit in a sturdy, level surface to


prevent rattling noises during operation. (see Fig. 4-1-1-3)
mm [in.]
B. Foundation specifications are as follows.
Thickness of concrete
120 [4-3/4"]

Weight-bearing capacity
320 kg [706lbs]

Foundation bolt Bolt length


M10 [3/8"] 70 [2-25/32"]

C. Make sure that the length of the foundation bolt is within 30


mm [1-3/16"] of the bottom surface of the base.
D. Secure the base of the unit firmly with four-M10 [3/8"]
foundation bolts in sturdy locations.

Warning:
A. The foundation base should be strong enough to support
the outdoor unit, otherwise, it may fall down and cause
damage or injures.
B. The unit must be installed according to the instructions in
order to minimize the risk of damage from earthquakes,
typhoons, or strong winds.

(mm [in.])

M10 (3/8") bolt


Base
As long as possible.
Vent

Min. 360
[14-3/16"]

600
[23-5/8"]

Min. 10
[13/32"] 175
[6-29/32"]

175
[6-29/32"]

25
[1"]

330
[13"]

600
[23-5/8"]

370
[14-19/32"]

When installing the outdoor unit on a rooftop or other location


unprotected from the wind, situate the air outlet of the unit so
that it is not directly exposed to strong winds.Strong wind
entering the air outlet may impede the normal airflow and a
malfunction may result.
The following shows two examples of precautions against
strong winds.
Install an optional air guide if the unit is installed in a
location where strong winds from a typhoon, etc. may
directly enter the air outlet. (Fig. 4-1-1-2a)
Air guide
Position the unit so that the air outlet blows perpendicularly
to the seasonal wind direction, if possible. (Fig. 4-1-1-2b)
Wind direction

Max.30[1-3/16"]

4-1-1-2. Installation at windy location.

950
[37-13/32"]

S-SERIES
SYSTEM DESIGN

Fig. 4-1-1-3

Fig. 4-1-1-2a

Fig. 4-1-1-2b

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-21

4. Installation

DATA U4

4-1-2. Spacing PUMY-P-NHMU


PUMY-P36/48NHMU's external dimension. (Fig.4-1-1)

PUMY-P-NHMU can connect Indoor unit sizes as shown


below with total capacity ranged 50%-130% of the outdoor unit
capacity.
Connectable Indoor capacity
Connectable Indoor unit
PUMY-P36NHMU
P18 - P46
P06-P36, 1-6 units

1350
[53-5/32"]

3 0 6"]
/1
0+
3 0 6"+1-3
[37 950
1 3 /1
[11 -13
/32
"

[6

-2

PUMY-P48NHMU

9/ 175
32
"] [ 60
23 0
-5
/8"
]

32
0
37 -19/
[14

P24 - P62

P06-P54, 1-8 units

"]

Fig. 4-1-1 PUMY-P-NHMU dimension

4-1-2-1. Spacing individual PUMY-P-NHMU


4-1-2-2. Spacing grouped PUMY-P-NHMU
Follow Fig. 4-1-2 ~ 7 to space individual PUMY-P-NHMU at the installation site. Follow Fig. 4-1-8 ~ 13 to space grouped PUMY-P-NHMU at the installation site.
mm[in.] Leave 101 mm [4"] space or more between PUMY-P-NHMU units.
mm[in.]

6"]

1/1
9-1

6"]
00
x. 3 -13/1
[11

1500[59-1/16"]

1000
[39-3/8"]

x.

Ma

[1
500

Ma
]
0
30 /16"
-13
[11

[59 1500
-1/
16
"]

0 ]
15 /32"
9
2
[5

Fig. 4-1-2
Obstacles at rear only

6"
0
50 -11/1
[19

6"]

0 "]
30 /16
-13
1
[1
Fig. 4-1-3
Obstacles at rear and above only

-1/1

[59

0
150

* In case of side-by-side installation, <=3 units;


* When using an optional air outlet guide,
* Do not install the optional air outlet guides
the clearance is 1000 mm [39-3/8"] or more. for upward airflow.
Fig. 4-1-8
Obstacles at rear or front only

Fig. 4-1-9
Obstacles at rear and above only

150 ]
32"

29/

[5-

20
[7- 0
7/8
"]

0
30 "]
/16
3
-1

2
[7- 00
7/8
"]

[11

Fig. 4-1-4
Obstacles at rear and sides only

/8"

9-3

00
15 /16"]
-1
[59

[3
00

10

0
]
50 /16"
-11
[19

0
60 /8"]
-5

00 "]
10 -3/8
[39

00
20 /4"]
-3
[78

[23

* Using an optional air outlet guide, the


clearance >= 500 mm [19-11/16"].

* Using an optional air outlet guide, the


clearance >= 1000 mm [39-3/8"].

* Using an optional air outlet guide, the


clearance >= 1000 mm [39-3/8"].

Fig. 4-1-5
Obstacles at front only

Fig. 4-1-10
Obstacles at front and rear only

Fig. 4-1-11
Parallel individuals arrangement

6"]

/1
-11
[19

00

S-SERIES
SYSTEM DESIGN

0
15 "] [ 250
9-27
/32"
/32
9
]
-2

00 ] [5
10 3/8"
[39

1500
[59-1/16"]

150[5-29/32"]

x. 5

Ma

0
50 "]
/16

2
[9-2 50
7/32
"]

500
[19-11/16"]

"]
00
15 -1/16
[59

0
60 /8"]
-5

[23

1
9-1
00
30 1/8"] [1
8[11

1
[59 500
-1/
16
"]

0
80 "]
2
1/

1-

* Using an optional air outlet guide, the


clearance >= 500 mm [19-11/16"].

* NO upward airflow outlet guide.

[3
* Using an optional air outlet guide for upward * Stacked layer <= 2 units;
airflow, the clearance >= 1500 mm [59-1/16"]. * Side-by-side stacked groups <= 2 groups;

Fig. 4-1-6
Obstacles at front and rear only

Fig. 4-1-7
Obstacles at rear, sides and above only

Fig. 4-1-12
Parallel groups arrangement

SSD-22

S-SERIES SYSTEM DESIGN (Feb. 2009)

Fig. 4-1-13
Stacked groups arrangement

4. Installation

DATA U4

4-1-3. Piping direction to PUMY-P-NHMU

Rear piping

Front piping cover


Piping cover
Stop valve
Service panel
Bend radius : 100 mm [3-15/16"] - 150 mm [5-29/32"]

Front piping

Right piping

Bottom piping

S-SERIES
SYSTEM DESIGN

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-23

5. Standard and Seacoast (-BS) Treatment

DATA U4

5-1. S-Series
Component

Standard
Models

Base Material

Aluminum-zincExternal Panel Base magnesiumplated Steel


Sheet
External Top, Front,
Back Panels

Galvanized Steel Sheet

Seacoast
Protection
Models (-BS)

Surface
Treatment

Internal Surface

Acrylic-resin Coating *1

20m

20m

Polyester-resin Coating

20m

Acrylic- and polyesterresin Coating *1

20m

No Treatment

No Treatment

Rust Prevention Oil


Applied

Polypropylene Resin
SWM-B Steel Wire

Fan

Polypropylene Resin

Fan Motor Frame

Undersaturated-polyester
Resin

Fan Motor Shaft

S45C Steel

Fan Motor Support

Galvanized Steel Sheet

Heat Exchanger
(Fin Only)

Aluminum Sheet

No Treatment
Epoxy-resin Coating
Applied to External
Surface
Blue Hydrophilic Coating
(Blue Fin) *2

Heat Exchanger
Side Plate

Galvanized Steel Sheet

Chromate Conversion
Coating

Refrigerant Piping

C1220T Phosphorous
Deoxidation Copper Pipe

No Treatment

Solder for
Refrigerant Piping
Joints

Phosphorous Copper

No Treatment

Electrical Parts Box

Galvanized Steel Sheet

Chromate Conversion
Coating

Printed Circuit
Board

CEM-3 Epoxy Laminate


Composite Material

Water-resistant Coating
on CPU Terminals

Separator

Galvanized Steel Sheet

Galvanized Steel Sheet

External Screws

SWCH18A/SWCH12A
Steel

Polyethylene-resin
Coating *1
No Treatment

Chromate Conversion
Coating

Epoxy-resin Coating

Chromate Conversion
Coating

984 (300m)
3,281 (1km)
Direct Exposure to Sea Breezes
Facing Inland
Seacoast Protection (-BS) Models
Standard Models
Facing Sea
Seacoast Protection (-BS) Models
On an Island
Seacoast Protection (-BS) Models
Indirect Exposure to Sea Breezes
Facing Inland
Seacoast Protection (-BS) Models
Standard Models
Facing Sea
Seacoast Protection (-BS) Models
On an Island
Seacoast Protection (-BS) Models

S-SERIES
SYSTEM DESIGN

Test
Conditions
Test
Results

SSD-24

120g/m2

Epoxy-resin Coating

Distance from the Sea


1,640 (500m)

*1

6m

Chromate Conversion
Coating

Application Guide

Reference

20m

No Treatment

Grille
Back Fin Guard

Valve Bed

Coating Thickness
External Surface

*2

5m

For optimum performance, follow the


cautions listed below.
1. Avoid installing the unit in a location that is
subjected to direct sea winds.
2. Do not attach a sunshade to the unit. Let the
rain wash away any salt residue that may adhere
to the unit.
3. Unit should be installed following instructions
for proper operation and to ensure optimum
water drainage.
4. Periodically wash the unit.
5. If the panels become scratched, repair as
soon as possible.
6. Inspect the unit at regular intervals. Paint the
unit or replace parts when necessary.

Salt-spray Test Method: JIS Z2371 based on ISO9227

No rust or peeling after 240


hour endurance test

No rust or peeling after 960


hour endurance test

S-SERIES SYSTEM DESIGN (Feb. 2009)

Blue Fin treatment is an anti-corrosion


treatment that is applied to the condenser coil
to protect it against airborne contaminants.

6. Cautions

DATA U4

The installer and/or air conditioning system specialist shall secure safety against refrigerant leakage according to local regulations or standards.
The following standard may be applicable if no local regulation or standard is available.

6-1. Refrigerant Properties


R410A refrigerant is harmless and incombustible. R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room
has possibility to lead to a hypoxia situation. Therefore, the critical concentration specified below shall not be exceeded even if the leakage
happens.

Critical concentration
Critical concentration is the maximum refrigerant concentration at which no harm would occur if immediate measures are taken when
refrigerant leakage happens.
Critical concentration of R410a: 0.30kg/m3 [0.0187 lbs./ft.3]
(The weight of refrigeration gas per 1 m3 [1 ft.3] air conditioning space.);
The critical concentration is per ISO5149, EN378-1 (other codes and standards may establish different values for critical concentration).

For CITY MULTI systems, the concentration of refrigerant leaked should not exceed the critical concentration in any situation.

6-2. Confirm the Critical Concentration and Perform Countermeasures


The maximum refrigerant leakage concentration (Rmax) is defined as the result of the possible maximum refrigerant weight (Wmax)
leaked into a room divided by its room capacity (V). It is referable to Fig. 5-1. The refrigerant weight includes its original charge and
additional charge at the site.
The additional charge is calculated according to 3-2-2."PUMY-P-NHMU's refrigerant charging calculation", and shall not be over charged at the site .
Procedure 6-2-1~3 tells how to confirm maximum refrigerant leakage concentration (Rmax) and how to take countermeasures against
a possible leakage.
Outdoor unit (No.1)

Outdoor unit (No.1)

Outdoor unit (No.2)

Flow of refrigerant

Indoor unit

Flow of refrigerant

Flow of refrigerant

Indoor unit

Maximum refrigerant leakage concentration (Rmax)


Rmax=Wmax / V

Maximum refrigerant leakage concentration (Rmax)


Rmax=Wmax / V
W1: Refrigerant weight of Outdoor unit No.1
where, Wmax=W1+W2 W2: Refrigerant weight of Outdoor unit No.2

Fig. 6-1 The maximum refrigerant leakage concentration


6-2-1.Find the room capacity (V),
If a room having total opening area more than 0.15% of the floor area at a low position with another room/space, the two rooms/space are
considered as one. The total space shall be added up.
6-2-2.Find the possible maximum leakage (Wmax) in the room. If a room has Indoor unit(s) from more than 1 Outdoor unit, add up the refrigerant of the Outdoor units.
6-2-3.Divide (Wmax) by (V) to get the maximum refrigerant leakage concentration (Rmax).
6-2-4.Find if there is any room in which the maximum refrigerant leakage concentration (Rmax) is over 0.30kg/m3 [0.087 lbs./ft.3].
If no, then the CITY MULTI is safe against refrigerant leakage.
If yes, following countermeasure is recommended to do at site.
Countermeasure 1: Let-out (making V bigger)
Design an opening of more than 0.15% of the floor area at a low position of the wall to let out the refrigerant whenever leaked.
e.g. make the upper and lower seams of door big enough.
Countermeasure 2: Smaller total charge (making Wmax smaller)
e.g. Avoid connecting more than 1 Outdoor unit to one room.
e.g. Using smaller model size but more Outdoor units.
e.g. Shorten the refrigerant piping as much as possible.
e.g. Remove unit from space.
Countermeasure 3: Ventilation air in from the ceiling.
As the density of the refrigerant is bigger than that of the air. Ventilation air from the ceiling is better than air exhausting from the ceiling.
Ventilation air supply solution refers to Fig. 6-2~4.
Refrigerant pipe (high pressure pipe)
Ventilation air supply fan (always ON)
Refrigerant pipe

Ventilation air supply fan

Ventilation air supply fan

to Outdoor unit

Indoor unit
Indoor space

(Floor)

to Outdoor unit

to Outdoor unit

Indoor unit
Indoor space

Refrigerant stop valve

Refrigerant pipe

Indoor space

(Floor)

(Floor)

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


[At 0.3m height from the floor]

Fig. 6-2. Ventilation air supply always ON

Opening

Opening

Sensor for refrigerant leakage (Oxygen sensor or refrigerant sensor).


[At 0.3m height from the floor]

Fig. 6-3. Ventilation air supply upon sensor action Fig. 6-4. Ventilation air supply and refrigerant
shut-off upon sensor action

Note 1. Countermeasure 3 should be done in a proper way in which the ventilation air supply shall be on whenever the leakage happens .
Note 2. In principle, MITSUBISHI ELECTRIC requires proper piping design, installation and air-tight testing after installation to avoid leakage happening.
In the area should earthquake happen, anti-vibration measures should be fully considered.
The piping should consider the extension due to the temperature variation.

S-SERIES SYSTEM DESIGN (Feb. 2009)

SSD-25

S-SERIES
SYSTEM DESIGN

Opening

Indoor unit