Summarisation of Design Guidelines of Allowable Stress Levels for Turbine and Spherical Valve NAFRA HEP
143525382.doc
Page 1 of 6
2x 60 MW NAFRA HE Project
Allowable Stresses
TABLE OF CONTENTS
1 Voith Hydro Standard for Allowable Stresses 2 Definitions 3 Loading Cases Annex 1 Basic Loading Case Definitions A1.1 Turbine and MIV
Revision -
3 3 3 5 5
143525382.doc
Page 2 of 6
2x 60 MW NAFRA HE Project
Allowable Stresses
1 Voith Hydro Standard for Allowable Stresses
Revision -
The allowable stresses are determined as a fraction of the minimum yield strength. The actual combined stresses calculated according to von Mises Criterion shall not exceed the following allowable values:
2 Definitions
Rp Yield strength or 0,2% offset from the linear region of elongation. Rm Ultimate strength of the material.
Stress value to be evaluated for a component, typically the combined stress according to von Mises criterion. For different stress classes, see chapter 1.
3 Loading Cases
There are three basic loading cases to be evaluated:
143525382.doc
Page 3 of 6
2x 60 MW NAFRA HE Project
Allowable Stresses
Revision -
Such loading case definitions are linked to the stress levels laid down in chapter 1.
143525382.doc
Page 4 of 6
2x 60 MW NAFRA HE Project
Allowable Stresses
Annex 1 Basic Loading Case Definitions
A1.1 Turbine and MIV
Revision -
FRANCIS and PUMP TURBINES Components Runner Operating Loading Case Max. Head Max. Output Speed no Load Pump start Max. Head/Max. Input Min. Head/Max. Input Max. Output 3-phase Short Circuit 2-phase Short Circuit 120 Synchronization Failure Exceptional Loading Case Max. Runaway Extreme Loading Case
Pump turbines
Shaft
Head Cover, Bottom Max. Head/Max. Output Ring Discharge Full Load Rejection Ring Pump Start Pump Load Rejection Pump turbines Spiral Case Stay Ring Wicket Gates Max. static Head incl. Water Hammer Max. static Head + Gate Max. static Head + Water Squeeze Hammer, safety element activated Effective pressure difference during Load Rejection Max. torque on Wicket Gates, Wicket Gates pre-stressed Max. Oil Pressure and Max. force Max. Tail Water pressure inside Pressure Test Installation/Embedment Closing of Distributor at Runaway at Max. Head and Max. Opening
Operating Ring
Shear pin failure of one One Servomotor blocked Wicket Gate under closing operation against during Load Rejection. engaged Lock. Pressure Test Embedment Max. Tail Water pressure outside plus 5m vacuum below Runner
MIV -SPHERICAL VALVE Valve Body Max. static Head + Water Maintenance Seal engaged Pressure Test Hammer (effective Penstock Pressure with Valve closed and other Units facing Full Load Rejection)
143525382.doc
Page 5 of 6
2x 60 MW NAFRA HE Project
Allowable Stresses
Valve Rotor
Revision -
Trunnions
Effective Pressure during Maintenance Seal engaged Pressure Test with Rotor closing at Max. static (Penstock Pressure with closed (if no downstream Head at normal Flow Valve closed and other Test Head foreseen) Units facing Full Load Rejection) Penstock Pressure with Valve closed and other Units facing Full Load Rejection Effective Pressure during Maintenance Seal engaged Pressure Test with Rotor (Penstock Pressure with closing at Max. static closed (if no downstream Valve closed and other Units Test Head foreseen) Head at normal Flow facing Full Load Rejection) Penstock Pressure with Valve closed and other Units facing Full Load Rejection