- Internal installation
- Installation in ducts
- Open installation
Various basic rules and conditions – including linear thermal expansion, joint method,
working conditions and necessary compensation – are to be considered during installation
process.
Fixed points
This type of fixing is excludes the
possibility of compensation; fixed supports
should be installed at different sections of
the pipe to avoid uncontrolled movement
of the pipe. Fixed points normally must be
positioned where the system changes
direction to ensure
ure expansion points are
not discharged. The distance between
fixed points should be measured properly
and the forces of expansion should be
considered. Never use pivoting clamps as
fixed points.
Sliding points
This type of mounting allows the pipe to
move e axially in both directions without damaging it. Sliding points should be positioned
distantly from the joints (fittings) to ensure the free movement of the pipe without any
damaging. Such type of installation does not restrict any expansion movement.
Key to abbreviations
FP – Fixed Point
SP – Sliding Point
Table 4. Distance between supports for Blue Ocean
PPR pipes and PPR/Al/PPR pipes (horizontal pipeline)
Internal installation
Internal installation is understood as cement or plaster
covering installation, under floor or in-wall
in installation. During
plaster covering installation of the pipeline, the thermal
expansion usually is not considered, but isolating of the
pipeline should be done in accordance with DIN 1988
Standard. The channel of the insulated pipe should be free
and should guarantee compensation of pipeline expansion. If
it is not necessary to insulate pipeline (cement covering
installation, under floor or in-wall
in installation),
llation), than installation can be held without
considering of thermal expansion, the compensation will be absorbed through the
material.
During cold water (potable water) pipeline installation pipes should be insulated against
heat gain and formation of condensation. It is recommended to make insulation in
accordance
cordance with DIN 1988, Part 2.
Installation in ducts
During vertical installation at the time of assembling branches and elbows the
compensation of riser pipe should be considered.
If the installation goes with usage of usual PPR pipes, then it is necessary to pay attention
to compensation.
Changing in length should If the duct has enough If the duct does not has
be guaranteed by space for installing the enough space to install the
compensator, this flexible arm compensator, calculated compensator,
compensator has to then it is recommended the wall hole should be
compensate up and down to use this type of enlarged to guarantee the
movements. compensation. free movement.
Open installation
During open installation attention to the visual appearance of the pipeline should be paid.
PPR pipes have big coefficient of linear expansion, all types of possible compensation
should be considered in advance. Blue Ocean PPR/Al/PPR (PE-RT) (PE RT) and Blue Ocean
Fiber-G
G pipes have much lower linear expansion and it is better to use these pipes when
the strict consideration of compensation is needed.
Example 1:
∆L - ? (mm)
α1 = 0.15mm/mºС С (PPR pipes)
α2 = α=0.03mm/mºС С (PPR/Al/PPR pipes)
α3 = α=0.05mm/mºС С (Blue Ocean Fiber-G
Fiber pipes)
L = 5m
T1 = 60ºСС (Operating temperature)
T2 = 20ºСС (Installation temperature)
∆T = T1 - T2 = 40ºС
Solution:
∆L = 0.15mm/mºС × 5m × 40ºС
40º = 30mm (PPR pipes)
∆L = 0.03mm/mºС × 5m × 40ºС
40º = 6mm (PPR/Al/PPR pipes)
∆L = 0.05mm/mºС × 5m × 40ºС
40º = 10mm (Blue Ocean Fiber-G
G pipes)
Solution:
Ls = 30 × = 1039mm (Length of flexible
flex arm)
Pipe with outside diameter 40mm and length 5m with temperature difference equals to
40ºС should be supported by fixed mounting at the length of 1039mm on the elbowing
side.
U-type compensation
If linear expansion can not be compensated by changing
changing of direction, then it is
recommended to use U-type
type compensation.
Width of U-type
type compensation is calculated according to the following formula:
Wk = 2 × ∆L + SL
Example 3:
Wk - ? (mm)
∆L
L = 30mm (calculated in Example 1)
SL = 150mm
Solution: