Vous êtes sur la page 1sur 2

SYSTEMS 2.

4kW 48V DC

PSX24 SERIES

PSX16 V2

PSX24 V1

PSX24 V2

Enatels PSX24 power systems range in power output up to 2.4kW and have a maximum output current of 50A. They are the ideal solution to meet the requirements of telecommunications applications such as access nodes and micro/pico base stations. The PSX24 range have been designed with the installer in mind giving true front connect for DC outputs and a pull out tray monitor for ease of alarm cabling installation. Utilizing Enatels intelligent controllers and modular rectifiers our standalone 1U micro compact DC power systems have been designed to be easily installed into any standard 19 rack or ETSI 515mm/300mm deep rack and can be customized and configured to meet the individual requirements of each customer. Smart rectifier design allows the RM648/RM848 rectifiers to measure and report AC input voltage to the system supervisory module with out the need for additional hardware. New Zealand made to guarantee design, manufacture and process integrity. Our robust proven conversion topology utilises only the highest specification components, ensuring unparalleled reliability benefits.

- Micro compact size means more room for revenue generating equipment.

- World leading power density. - Telecom grade rectifiers. - Modular 19/515mm ETSI design for ease of installation.

- High reliability means less cost of maintenance.

- Full remote monitoring available means less site visits and less cost.

- Easily customized and configured to suit each customers individual needs.

- AC voltage measurement.

MANUFACTURED IN NEW ZEALAND

smart | power | design

Enatel Ltd 66 Treffers Road Christchurch 8042 New Zealand Tel +64-3-366 4550 Fax +64-3-366 0884 Email sales@enatel.net www.enatel.net

SPECIFICATIONS

ELECTRICAL
AC Input: Frequency Range: Power Factor: Termination:

PSX16 V2 Single phase (refer to rectifier spec for full details) 45-66Hz >0.99 (full load) Single phase, 1.0m unterminated lead

PSX24 V1 Single phase (refer to rectifier spec for full details) 45-66Hz >0.99 (full load) Single phase, 1.0m unterminated lead 48V DC 2.4kW Positive earth 1x load circuit breakers (6-50A) 1x battery circuit breakers (max 50A) Electronic fail detection 16mm screw terminal plug 16mm screw terminal plug 80A magnetically latching battery LVD

PSX24 V2 Single phase (refer to rectifier spec for full details) 45-66Hz >0.99 (full load) Single phase, 1.0m unterminated lead 48V DC 2.4kW Positive earth 4x load circuit breakers (6-30A) 2x battery circuit breakers (max 30A) Electronic fail detection 6mm push-in spring cage 50A power-pole plug-in connectors 80A magnetically latching battery LVD

DC Output: Nominal Voltage: 48V DC Max. Output Power: 1.6kW Polarity: Positive earth DC Distribution: Breaker Fail Detection: DC Terminals Load: (Front Connected): Battery: LVD: 6x load circuit breakers (6-30A) 2x battery circuit breakers (max 30A) Electronic fail detection 6mm push-in spring cage 50A power-pole plug-in connectors 80A magnetically latching battery LVD

MONITORING & CONTROL


Display: Communications: Serial: TCP/IP: Modbus: LED Indicators: Green: Yellow: Red: Audible: Controls: Signal Inputs: Alarms: Alarm Contacts: Logging Capacity: Connections: Multi-lingual alpha numeric backlit display 1x USB port on front panel for local PC interface Ethernet interface for communication using SNMP protocol and internal web based configurator* Supported via TCP/IP* Power on/monitor OK Non urgent alarm Urgent alarm 90dBA buzzer mappable to user defined conditions 3x push buttons for parameter setting or viewing on front panel Serial bus for rectifier control and interface to peripheral modules 6x digital inputs, 2x temperature sensors (one fitted by default) 6x alarm relays, 5x of which can be mapped for customised alarm settings 0.3A 100V volts free changeover contacts Periodic log, 16,384 records (dependant on number of parameters logged) Event log, 16,384 records (dependant on number of parameters logged)

Relay outputs, mini combicon to accept 1.5mm wire USB port, USB mini B *TCP/IP and modbus options only available with SM36 supervisory module.

ENVIRONMENTAL REQUIREMENTS
Ambient Temperature: Storage Temperature: Humidity: Altitude: -20C to +70C (maximum output power is derated above +50C) -30C to +85C 5-95% RH (non-condensing) <2,500m at full power

COMPLIANCES
Safety: Electrostatic Discharge: Radiated Radio Frequency: AC Harmonics: AC Flicker and Fluctuation: Other: EN60950 CISPR24 CISPR22 EN61000-3-2 EN61000-3-3 CE & RoHS compliant

MECHANICAL
Dimensions W, H, D: Weight: Shipping Dimensions W, H, D: Shipping Weight: 482.6mm (19 mount), 44.45mm (1U), 285.0mm 5.0kg (excluding rectifier modules) 540.0mm, 95.0mm, 400.0mm 6.0kg (excluding rectifier modules)

PART NUMBERS
PSX16 V2: PSX24 V1: PSX24 V2: Micro compact system, 2x modular rectifiers, 6x load 2x battery MCBs, SM36 supervisory module Micro compact system, 3x modular rectifiers, 1x load 1x battery MCBs, SM36 supervisory module Micro compact system, 3x modular rectifiers, 4x load 2x battery MCBs, SM36 supervisory module

*System part numbers are dependent on configuration options. For final system part numbers consult our sales staff for configuration advice.

CONFIGURATION OPTIONS
Rectifiers: Supervisory Modules:

To be advised at time of order RM648, 600W modular rectifier, 110/230V AC input, 48V DC output, 12.5A maximum output current RM848, 800W modular rectifier, 230V AC input, 48V DC output, 16.6A maximum output current SM35, standard monitor featuring full temperature compensation, automated and manual battery testing/equalisation SM36, enhanced monitor featuring full temperature compensation, automated and manual battery testing/equalisation with TCP/IP

OPTIONS
ACA-BC08P2: ARBP-0M: 2m, 8mm battery cable kit (other lengths available to special order) Metal rectifier blanking panel

Copyright Enatel Limited 2012. Due to product development specifications are subject to change without prior notice. Pictures may be representative, actual products may differ.

Vous aimerez peut-être aussi