12/31/2012
04:19PM
1. General Details:
Air System Name .................................................. ELECTRICAL REPAIR RM
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
ELECTRICAL & REPAIR ROOM
x1
C
C
C
C
K
%
L/s
kW
Page 1 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
298.7
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.8
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
kW
C
%
EER
C
C
Page 2 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name ........................................................... ENGINE OVERHAUL
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
ENGINE OVER HAUL
x1
C
C
C
C
K
%
L/s
kW
Page 3 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
906.1
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.6
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
kW
C
%
EER
C
C
Page 4 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name ................................................... GROUND FLOOR OFFICE
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
CHANGING & LOCKERS ROOM
TOILETS GF
CORRIDOR
DINNING HALL
LOBBY
PRAYER ROOM
RECEPTION LOUNGE & STORE
TEL ROOM
TOILET A
TOILET F
TOILET M
x1
x1
x1
x1
x1
x1
x1
x1
x1
x1
x1
C
C
C
C
K
%
L/s
kW
Page 5 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
1987.8
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
C
%
EER
C
C
Page 6 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name ...................................................................................... HRW
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Ventilation Reclaim Data:
Reclaim Type ............................................................................. Sensible Heat
Thermal Efficiency ......................................................................................... 60 %
Input kW ................................................................................................... 0.000 kW
Schedule .............................................................................. JFMAMJJASOND
Central Cooling Data:
Supply Air Temperature ............................................................................. 15.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
HRW
x1
C
C
C
C
K
%
L/s
kW
Page 7 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
350.0
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.0
Design OAT ................................................................................................ 46.0
Equipment Sizing ........................................................................ User-Defined
Gross Cooling Capacity ............................................................................... 0.3
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
kW
C
kW
EER
C
C
Page 8 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name .............................................................................. LV ROOM
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
LV ROOM
x1
C
C
C
C
K
%
L/s
kW
Page 9 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
319.9
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 5.4
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
kW
C
%
EER
C
C
Page 10 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name ......................................................... MEZZ FLOOR OFFICE
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
FILING AREA M
LOBBY M
OFFICE M
PANTRY M
STAIRS & LOBBY M
TEL ROOM M
TOILETS M
x1
x1
x1
x1
x1
x1
x1
C
C
C
C
K
%
L/s
kW
Page 11 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
4212.0
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
C
%
EER
C
C
Page 12 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name ............................................. SECURITY AND RECEPTION
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
SECURITY ROOM
RECEP/JOB CARD CLERKS
x1
x1
C
C
C
C
K
%
L/s
kW
Page 13 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
463.9
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 10.1
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
kW
C
%
EER
C
C
Page 14 of 16
12/31/2012
04:19PM
1. General Details:
Air System Name ................. WATCHMAN RM AND WORKERS RESTAREA
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
WATCHMANS ROOM M
WORKERS REST ROOM M
x1
x1
C
C
C
C
K
%
L/s
kW
Page 15 of 16
12/31/2012
04:19PM
Zone
Supply Airflow
(L/s)
343.0
Reheat Coil
(kW)
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 6.8
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8
(L/s)
kW
C
%
EER
C
C
Page 16 of 16