Vous êtes sur la page 1sur 16

ELECTRICAL REPAIR RM Input Data

Project Name: UNITED MOTORS


Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name .................................................. ELECTRICAL REPAIR RM
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
ELECTRICAL & REPAIR ROOM

x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND
4. Sizing Data (Computer-Generated):
Hourly Analysis Program v4.51

Page 1 of 16

ELECTRICAL REPAIR RM Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

System Sizing Data:


Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................... 304.8 L/s
Ventilation Airflow ......................................................................................... 7.0 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

298.7

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.8
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

kW
C
%
EER
C
C

Page 2 of 16

ENGINE OVERHAUL Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name ........................................................... ENGINE OVERHAUL
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
ENGINE OVER HAUL

x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND
4. Sizing Data (Computer-Generated):
Hourly Analysis Program v4.51

Page 3 of 16

ENGINE OVERHAUL Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

System Sizing Data:


Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................... 924.6 L/s
Ventilation Airflow ....................................................................................... 14.0 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

906.1

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.6
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

kW
C
%
EER
C
C

Page 4 of 16

GROUND FLOOR OFFICE Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name ................................................... GROUND FLOOR OFFICE
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
CHANGING & LOCKERS ROOM
TOILETS GF
CORRIDOR
DINNING HALL
LOBBY
PRAYER ROOM
RECEPTION LOUNGE & STORE
TEL ROOM
TOILET A
TOILET F
TOILET M

x1
x1
x1
x1
x1
x1
x1
x1
x1
x1
x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Hourly Analysis Program v4.51

Page 5 of 16

GROUND FLOOR OFFICE Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

Zone .............................................................................................................. All


Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................. 2028.4 L/s
Ventilation Airflow ..................................................................................... 127.7 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

1987.8

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

C
%
EER
C
C

Page 6 of 16

HRW Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name ...................................................................................... HRW
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Ventilation Reclaim Data:
Reclaim Type ............................................................................. Sensible Heat
Thermal Efficiency ......................................................................................... 60 %
Input kW ................................................................................................... 0.000 kW
Schedule .............................................................................. JFMAMJJASOND
Central Cooling Data:
Supply Air Temperature ............................................................................. 15.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
HRW

x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 15.5
Cooling T-stat: Unocc. ................................................................................ 15.5
Heating T-stat: Occ. ................................................................................... 12.0
Heating T-stat: Unocc. ............................................................................... 10.0
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Hourly Analysis Program v4.51

Page 7 of 16

HRW Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

Zone Heating Unit Type ........................................................................... None


Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
Cooling Supply Temperature ..................................................................... 15.0 C
Supply Fan Airflow ................................................................................... 357.1 L/s
Ventilation Airflow ..................................................................................... 350.0 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

350.0

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.0
Design OAT ................................................................................................ 46.0
Equipment Sizing ........................................................................ User-Defined
Gross Cooling Capacity ............................................................................... 0.3
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

kW
C
kW
EER
C
C

Page 8 of 16

LV ROOM Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name .............................................................................. LV ROOM
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
LV ROOM

x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND
4. Sizing Data (Computer-Generated):
Hourly Analysis Program v4.51

Page 9 of 16

LV ROOM Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

System Sizing Data:


Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................... 326.5 L/s
Ventilation Airflow ......................................................................................... 7.0 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

319.9

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 5.4
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

kW
C
%
EER
C
C

Page 10 of 16

MEZZ FLOOR OFFICE Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name ......................................................... MEZZ FLOOR OFFICE
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
FILING AREA M
LOBBY M
OFFICE M
PANTRY M
STAIRS & LOBBY M
TEL ROOM M
TOILETS M

x1
x1
x1
x1
x1
x1
x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Hourly Analysis Program v4.51

Page 11 of 16

MEZZ FLOOR OFFICE Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

Zone .............................................................................................................. All


Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................. 4298.0 L/s
Ventilation Airflow ..................................................................................... 140.0 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

4212.0

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

C
%
EER
C
C

Page 12 of 16

SECURITY AND RECEPTION Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name ............................................. SECURITY AND RECEPTION
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
SECURITY ROOM
RECEP/JOB CARD CLERKS

x1
x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND

Hourly Analysis Program v4.51

Page 13 of 16

SECURITY AND RECEPTION Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................... 473.3 L/s
Ventilation Airflow ....................................................................................... 42.0 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

463.9

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 10.1
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

kW
C
%
EER
C
C

Page 14 of 16

WATCHMAN RM AND WORKERS RESTAREA Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

1. General Details:
Air System Name ................. WATCHMAN RM AND WORKERS RESTAREA
Equipment Type ................................................................................ Split AHU
Air System Type ................................................................... Single Zone CAV
Number of zones ............................................................................................. 1
2. System Components:
Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm
Central Cooling Data:
Supply Air Temperature ............................................................................. 14.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND
Capacity Control ................................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type ................................................................................ Forward Curved
Configuration ..................................................................................... Blow-thru
Fan Performance .......................................................................................... 50 Pa
Overall Efficiency .......................................................................................... 54 %
Duct System Data:
Supply Duct Data:
Duct Heat Gain ................................................................................................ 2 %
Duct Leakage .................................................................................................. 2 %
Return Duct or Plenum Data:
Return Air Via ..................................................................... Return Air Plenum
Wall Heat Gain to Plenum ............................................................................. 70 %
Roof Heat Gain to Plenum ............................................................................ 30 %
Lighting Heat Gain to Plenum ....................................................................... 30 %
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
WATCHMANS ROOM M
WORKERS REST ROOM M

x1
x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 24.0
Cooling T-stat: Unocc. ................................................................................ 27.0
Heating T-stat: Occ. ................................................................................... 19.0
Heating T-stat: Unocc. ............................................................................... 15.6
T-stat Throttling Range .............................................................................. 0.83
Diversity Factor ........................................................................................... 100
Direct Exhaust Airflow .................................................................................. 0.0
Direct Exhaust Fan kW ................................................................................ 0.0

C
C
C
C
K
%
L/s
kW

Thermostat Schedule ................................................... FAN & THERMOSTAT


Unoccupied Cooling is ....................................................................... Available
Supply Terminals Data:
Zone .............................................................................................................. All
Terminal Type ...................................................................................... Diffuser
Minimum Airflow ......................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone .............................................................................................................. All
Zone Heating Unit Type ........................................................................... None
Zone Unit Heat Source ..................................................... Electric Resistance
Zone Heating Unit Schedule ................................................ JFMAMJJASOND

Hourly Analysis Program v4.51

Page 15 of 16

WATCHMAN RM AND WORKERS RESTAREA Input Data


Project Name: UNITED MOTORS
Prepared by: TECHNOZONE

12/31/2012
04:19PM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Cooling Supply Temperature ..................................................................... 14.0 C
Supply Fan Airflow ................................................................................... 350.0 L/s
Ventilation Airflow ....................................................................................... 17.5 L/s
Hydronic Sizing Specifications:
Chilled Water Delta-T ................................................................................... 6.0 K
Hot Water Delta-T ...................................................................................... 11.1 K
Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ................................................................................................. 5 %
Heating ............................................................................................................ 0 %
Zone Sizing Data:
Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone

Supply Airflow
(L/s)

343.0

Zone Htg Unit


(kW)

Reheat Coil
(kW)

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 6.8
Design OAT ................................................................................................ 35.0
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0
ARI Performance Rating ............................................................................ 3.22
Conventional Cutoff OAT ........................................................................... 12.8
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8

Hourly Analysis Program v4.51

(L/s)

kW
C
%
EER
C
C

Page 16 of 16