Vous êtes sur la page 1sur 26

CONTROL CHARTS FOR ATTRIBUTES

CHAPTER NO 6 : CONTROL CHARTS FOR ATTRIBUTES

INTRODUCTION
The term attribute, as used in quality, refers to those quality characteristics that conform to specifications or do not conform to specifications. Attributes are used: a. Where measurements are not possible. Example, visually inspected items such as color, number of leaking containers, errors on an invoice, missing parts, scratches and damage on surface. b. Where measurement can be made but not made because of time, cost, or need. In other words, although the diameter of a hole can be measured with an inside micrometer, it may be more convenient to use a go-no-go gage and determine if it conforms or does not conform to specifications.

LEARNING OBJECTIVES
The objectives of this unit are to : 1. Understand the statistical basis of control charts for attributes. 2. Discuss when to use the different types of attribute control charts. 3. Construct the different types of attribute control charts: p & np and c & u chart. 4. Analyze and interpret attribute control charts.

UTeM

100

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6.1

INTRODUCTION
When an attribute does not conform to specifications, various descriptive terms are

used. A nonconformity is a departure of a quality characteristic from its intended level or state that occurs with a severity sufficient to cause an associated product or service not to meet a specification requirement. Defect is appropriate for use when evaluation is in terms of usage, and nonconformity is appropriate for conformance to specifications. The term nonconforming unit is used to describe a unit of product or service containing at least one nonconformity. Defective is analogous to defect and is appropriate for use when a unit of product or service is evaluated in terms of usage rather than conformance to specifications.

6.1.1 LIMITATIONS OF VARIABLE CONTROL CHARTS


When control charts are excellent means for controlling quality and subsequently improving it; however, they have limitations. One obvious limitation is that these charts cannot be used for quality characteristics which are attributes. The converse is not true, since a variable can be changed to an attribute by stating that it conforms or does not conforms to specifications. In other words, nonconformities such as missing parts, incorrect color, and so on, are not measurable and a variable control chart is not applicable.

6.1.2 TYPES OF ATTRIBUTE CHARTS


There are two different groups of control charts for attributes. One group of charts is for nonconforming units. It is based on the binomial distributions. A proportion, p, chart shows the proportion nonconforming in a sample or subgroup. The proportion is expressed as a fraction or a percent. Another chart in the group is for the number nonconforming, a np chart, and it to could also be expressed as number nonconforming. The other group of charts is for nonconformities. It is based on the Poisson distribution. A c chart shows the count of nonconformities in an inspected unit such as an automobile, bolt or cloth, or roll of paper. Another closely related chart is the u chart, which is for the count of nonconformities per unit.

UTeM

101

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6.2

CONTROL CHARTS FOR NONCONFORMING UNITS


6.2.1 INTRODUCTION
The p chart is used fir data that consist of the proportion of the number of

occurrences of an event to the total number of occurrences. It is used in quality to report the fraction or percent nonconforming in a product, quality characteristic, or group of quality characteristics. As such, the fraction nonconforming is the proportion of the number nonconforming in a sample or subgroup to the total number in the sample or subgroup. In symbolic terms the formula is

p=

np n

where p = proportion or fraction nonconforming in the sample or subgroup n = number in the sample or subgroup np = number nonconforming in the sample or subgroup

Example 1: During the first shift, 450 inspections are made of book-of-the month shipments and 5 nonconforming units are found. Production during the shift was 15000 units. What is the fraction nonconforming? Solution:

p=

np 5 = = 0.011 n 450

The fraction nonconforming, p, is usually small, say, 0.10 or less. Except in unusual circumstances, values greater than 0.10 would indicate that the organization is in serious difficulty and that measures more drastic than a control chart are required. Because the fraction nonconforming is very small, the subgroup sizes must be quite large to produce a meaningful chart.

UTeM

102

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

The p chart is an extremely versatile control chart. It can be used to control one quality characteristic, as is done with the X and R chart; to control a group of quality characteristics of the same type or of the same part; or to control the entire product. The p chart can be established to measure the quality produced by a work center, by a department, by a shift, or by entire plant. It is frequently used to report the performance of an operator; group of operators, or management as a means of evaluating their quality performance. The subgroup size of the p chart can be either variable or constant. A constant subgroup size is preferred; however, there may be many situations such as changes in mix and 100% automated inspection, where the subgroup size changes.

6.2.2 OBJECTIVES
The objectives of nonconforming charts are to: 1. Determine the average quality level. Knowledge of the quality average is essential as a benchmark. This information provides the process capability in terms of attributes. 2. Bring to the attention of management any changes in the average. Once the average quality (proportion nonconforming) is known, changes, either increasing or decreasing, become significant. 3. Improve the product quality. In this regard a p chart can motivate operating and management personnel to initiate ideas for quality improvement. The chart will tell whether the idea is an appropriate or inappropriate one. A continual and relentless effort must be made to improve the quality. 4. Evaluate the quality performance of operating and management personnel. Supervisors of activities and especially the Chief Executive Officer (CEO) should be evaluated by a chart for nonconforming units. Other functional areas, such as engineering, sales, finance, and so on, may find a chart for nonconformities more applicable for evaluation purposes. 5. Suggest places to use X and R charts. Even though the cost of computing and

charting X and R charts is more than the chart for nonconforming units, the X and R charts are much more sensitive to variations and are more helpful in diagnosing causes. In other words, the chart for nonconforming units suggests the source of difficulty, and the X and R chart finds the cause. 6. Determine acceptance criteria of a product before shipment to the customer. Knowledge of the proportion nonconforming provides management with information on whether or not to release an order. These objectives indicate the scope and value of a nonconforming chart.
UTeM

103

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6.2.3 p-chart CONSTRUCTION FOR CONSTANT SUBGROUP SIZE.


The general procedures that apply to variable control charts are also apply to the p-chart. 1. Select the quality characteristic(s). The first step in the procedure is to determine the use of the control chart. A p chart can be established to control the proportion nonconforming of (a) a single characteristic, (b) a group of quality characteristics, (c) a part, (d) an entire product, or (e) a number of products. This establishes a hierarchy of utilization so that any inspections applicable for a single quality characteristic also provide data for other p charts, which represent larger groups of characteristics, parts, or products. A p chart can also be established for performance control of an (a) operator, (b) work center, (c) department, (d) shift, (e) plant, or (f) corporation. Using the chart in this manner, comparison may be made between like units. It is also possible to evaluate the quality performance of a unit. A hierarchy of utilization exists so that data collected for one chart can also be used on a more all-inclusive chart. The use for the chart or charts will be based on securing the greatest benefit for a minimum of cost. One chart should measure the CEOs quality performance. 2. Determine the subgroup size and method. The size of the subgroup is a function of the proportion nonconforming. If a part has a proportion nonconforming, p, of 0.001 and a subgroup size, n, of 1000, then the average number nonconforming, np, would be one per subgroup. This would not make a good chart, since a large number of values, posted to the chart, would be zero. If a part has proportion nonconforming of 0.15 and a subgroup size of 50, the average number of nonconforming would be 7.5, which would make a good chart. Therefore, the selection of the subgroup size requires some preliminary observations to obtain a rough idea of the proportion nonconforming and some judgment as to the average number of nonconforming units that will make an adequate graphical chart. A minimum size of 50 is suggested as a starting point. Inspection can either be by audit or on-line. Audits are usually done in a laboratory under optimal conditions. On-line provides immediate feedback for corrective action.

UTeM

104

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

3. Collect the data. The quality technician will need to collect sufficient data for at least 25 subgroups, or the data may be obtained from historical records. Perhaps, the best source is from a check sheet designed by a project team. Table 6.1 gives the inspection results for the blower motor in an electric hair dryer for the motor department. For each subgroup the proportion nonconforming is calculated by the formula p = np/n. the quality technician reported that subgroup 19 had an abnormally large number of nonconforming units, owing to faulty contacts. Table 6.1: Inspection Results of Hair Dryer Blower Motor.
Subgroup Number Number Number Proportion Inspected Nonconforming Nonconforming n np p 1 300 12 0.040 2 300 3 0.010 3 300 9 0.030 4 300 4 0.013 5 300 0 0.000 6 300 6 0.020 7 300 6 0.020 8 300 1 0.003 9 300 8 0.027 10 300 11 0.037 11 300 2 0.007 12 300 10 0.033 13 300 9 0.030 14 300 3 0.010 15 300 0 0.000 16 300 5 0.017 17 300 7 0.023 18 300 8 0.027 19 300 16 0.053 20 300 2 0.007 21 300 5 0.017 22 300 6 0.020 23 300 0 0.000 24 300 3 0.010 25 300 2 0.007 Total 7500 138

UTeM

105

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

4. Calculate the trial central line and control limits. The formula for the trial control limits is given by

UCL = p + 3

p (1 p ) n p (1 p ) n

LCL = p 3

where

p = average proportion nonconforming for many subgroups n = number inspected in a subgroup


The average proportion nonconforming, p , is the central line and is obtained by the formula

p=

np

Calculations for the trial control limits using the data on the electric hair dryer are as follows:

p=

np = 138 = 0.018 n 7500


p (1 p ) 0.018(1 0.018) = 0.018 + 3 = 0.041 n 300 p (1 p ) 0.018(1 0.018) = 0.018 3 = 0.005 or 0.0 300 n

UCL = p + 3

LCL = p 3

Calculations for the lower control limit resulted in a negative value, which is a theoretical result. In practice, a negative proportion nonconforming would be impossible. Therefore, the lower control limit value of -0.005 is changed to zero (0.0).

UTeM

106

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

When the control limit is positive, it may in some cases be changed to zero. If the p chart is to be viewed by operating personnel, it would be difficult to explain why a proportion nonconforming that is below the lower control limit is out of control. In other words, performance of exceptionally good quality would be classified as out of control. To avoid the need to explain this situation to operating personnel, the lower control limit is changed from a positive value to zero. When the p chart is to be used by quality personnel and by management, a positive lower control limit is left unchanged. In this manner exceptionally good performance (below the lower control limit) will be treated as an out-of-control situation and investigated for an assignable cause. It is hoped that the assignable cause will indicate how the situation can be repeated. The central line, p , and the control limits are shown in Figure 6.1; the proportion nonconforming, p, from Table 6.1 is also posted to that chart. This chart is used to determine if the process is stable and is not posted. It is important to recognize that the central line and control limits were determined from the data.

Figure 6.1: p chart to illustrate the trial central line and control limits using the data from table 6.1.

5. Established the revised central line and control limits. In order to determine the revised 3 control limits, the standard or reference value for the proportion nonconforming, p0, needs to be determined. If an analysis of the chart of step 4 above shows good control (a stable process), then p can be considered to be representative of that process. Therefore, the best estimate of p0 at this time is p , and p0 =

p.

UTeM

107

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

Most industrial processes, however, are not in control when first analyzed, and this fact is illustrated in Figure 6.1 by subgroup 19, which is above the upper control limit and therefore out of control. Since subgroup 19 has an assignable cause, it can be discarded from the data and a new p computed with all of the subgroups except 19. The calculations can be simplified by using the formula

p new =
where

np np nn
d

npd = number nonconforming in the discarded subgroups nd = number inspected in the discarded subgroups

In discarding data it must be remembered that only those subgroups with assignable causes are discarded. Those subgroups without assignable causes are left in the data. Also, out-of-control points below the lower control limit are not discarded, since they represent exceptionally good quality. If the out-of-control point on the low side is due to an inspection error, it should be discarded. With an adopted standard or reference value for the proportion nonconforming, p0, the revised control limits are given by

p0 = p new p 0 (1 p 0 ) n p 0 (1 p 0 ) n

UCL = p 0 + 3

LCL = p 0 3

where p0, the central line, represents the reference or standard value for the fraction nonconforming. These formulas are for the control limits for three standard deviations from the central line p0.

UTeM

108

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

Thus, for the preliminary data in Table 6.1, a new p is obtained by discarding subgroup 19.

p new =

np np nn
d

138 16 = 0.017 7500 300

Since p new is the best estimate of the standard or reference value, p0 = 0.017. The revised control limits for the p chart are obtained as follows:

UCL = p 0 + 3

p 0 (1 p 0 ) 0.017(1 0.017) = 0.017 + 3 = 0.039 n 300 p 0 (1 p 0 ) 0.017(1 0.017) = 0.017 3 = 0.005 or 0.0 n 300

LCL = p 0 3

The revised control limits and the central line, p0, are shown in Figure 6.2. This chart, without the plotted point, is posted in an appropriate place, and the proportion nonconforming, p, for each subgroup is plotted as it occurs.

Figure 6.2: Continuing use of the p chart representative values of the proportion nonconforming, p

UTeM

109

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6. Achieve the objective. The first five steps are planning. The last step involves action and leads to the achievement of the objective. The revised control limits were based on data collected in May. Some representative values of inspection results for the month June are shown in Figure 6.2. Analysis of the June results shows that the quality improved. This improvement is expected, since the posting of a quality control chart usually results in improved quality. Using the June data, a better estimate of the proportion nonconforming is obtained. The new value (p0 = 0.014) is used to obtain the UCL of 0.036. During the latter part of June and the entire month of July, various qualities of improvement ideas generated by a project team are tested. These ideas are new shellac, change in wire size, stronger spring, X and R charts on the armature, and so on. In testing ideas there are three criteria: a minimum of 25 subgroups are required, the 25 subgroups can be compressed in time as long as no sampling bias occurs, and only one idea can be tested at one time. The control chart will tell whether the idea improves the quality, reduces the quality, or has no effect on the quality. The control chart should be located in a conspicuous place so operating personnel can view it. Data for July are used to determine the central line and control limits for August. The pattern of variation for August indicates that no further improvement resulted. However, a 41% improvement occurred from June (0.017) to August (0.010). At this point, we have obtained considerable improvement testing the ideas of the project team. While this improvement is very good, we must continue our relentless pursuit of quality improvement-1 out of every 100 is still nonconforming. Perhaps a detailed failure analysis or technical assistance from product engineering will lead to additional ideas that can be evaluated. A new project team may help. Quality improvement is never terminated. efforts may be redirected to other areas based on need and/or resources available.

UTeM

110

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6.2.4

np-chart NUMBER NONCONFORMING CHART.

The number nonconforming chart (np chart) is almost the same as the p chart; however, you would not use both for the same objective. The np chart is easier for operating personnel to understand than the p chart. Also inspection results are posted directly to the chart without any calculations. If the subgroup size is allowed to vary, the central line and the control limits will vary, which presents a chart that is almost meaningless. Therefore, one limitation of an np chart is the requirement that the subgroup size must be constant. The sample size should be shown on the chart so viewers have a reference point. Since the number nonconforming chart is mathematically equivalent to the proportion nonconforming chart, the central line and control limits are changed by a factor of n. Formulas are

Central line = np0 Control limits = np0 3 np0 (1 p0 )


If the fraction nonconforming po, is unknown, then it must be determine by collecting data, calculating trial control limits, and obtaining the best estimates of po. The trial control limits formulas are obtained by substituting p for po, in the formulas above. An example problem illustrates the technique.

Example 2: A government agency samples 200 documents per day from a daily lot of 6000. From past records the standard or reference value for the fraction nonconforming po, is 0.075. Solution: Central line and control limit calculations are

np0 = 200(0.075) = 15.0 UCL = np0 + 3 np0 (1 p0 ) = 15 + 3 15(1 0.075) = 26.2 LCL = np0 3 np0 (1 p0 ) = 15 3 15(1 0.075) = 3.8

The control chart is shown in Figure 6.3.

UTeM

111

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

Figure 6.3: Number nonconforming chart (np chart).

EXERCISE 6.1
1. Determine the trial central line and control limits for a p chart using the following data, which are for the payment of dental insurance claims (n=200). If there are any out of control out of points, assume an assignable cause and determine the revised central line and control limits.
SUBGROUP NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 NUMBER NONCONFORMING p 3 6 4 6 20 2 6 7 3 0 6 9 5 SUBGROUP NUMBER 14 15 16 17 18 19 20 21 22 23 24 25 NUMBER NONCONFORMING p 6 7 4 5 7 5 0 2 3 6 1 8

UTeM

112

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6.3

CONTROL CHARTS FOR COUNT OF NONCONFORMITIES

6.3.1 INTRODUCTION
The other group of attribute charts is the nonconformity charts. While a p chart controls the proportion nonconforming of the product or service, the nonconformities chart controls the count of nonconformities within the product or service. Remember, an item is classified as a nonconforming unit whether it has one or many nonconformities. There are two types of charts: count of nonconformities (c) chart and count of nonconformities per unit (u) chart. Since these charts are based on the Poisson distribution, two conditions must be met. First, the average count of nonconformities must be much less than the total possible count of nonconformities. In other words, the opportunity for nonconformities is large, whereas the chance of a nonconformity at any one location is very small. This situation is typified by the rivets on a commercial airplane, where there are a large number of rivets but a small chance of any one rivet being a nonconformity. The second condition specifies that the occurrences are independent. In other words, the occurrence of one nonconformity does not increase or decrease the chance of the next occurrence being a nonconformity. For example, if a typist types an incorrect letter there is an equal likelihood of the next letter being incorrect. Any beginning typist knows that this is not always the case because if the hands are not on the home keys, the chance of the second letter being incorrect is almost a certainty. Other places where a chart of nonconformities meets the two conditions are: imperfections in a large roll of paper, typographical errors on a printed page, rust spots on steel sheets, seeds or air pockets in glassware, adhesion defects per 1000 square feet of corrugated board, mold marks on fiberglass canoes, billing errors, and errors on forms.

6.3.2 OBJECTIVES
While the charts for count of nonconformities are not as inclusive as the X and R charts or the p charts, they still have a number of applications, some of which have been mentioned.

UTeM

113

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

The objectives of charts for count of nonconformities are to: 1. Determine the average quality level as a benchmark or starting point. This information gives the initial process capability. 2. Bring to the attention of management any changes in the average. Once the average quality is known, any change become significant. 3. Improve the product quality. In this regard a chart for count of nonconformities can motivate operating and management personnel to initiate ideas for quality improvement. The chart will tell whether the idea is an appropriate or inappropriate one. A continual and relentless effort must be made to improve the quality. 4. Evaluate the quality performance of operating and management personnel. As long as the chart is in control, operating personnel are performing satisfactorily. Since the charts for count of nonconformities are usually applicable to errors, they are very effective in evaluating the quality of the functional areas of finance, sales customer service, and so on. 5. Suggest places to use the X and R charts. Some applications of the charts for count of nonconformities lend themselves to more detailed analysis by X and R charts. 6. Provide information concerning the acceptability of the product prior to shipment. These objectives are almost identical to those for nonconforming charts. Therefore, the reader is cautioned to be sure that the appropriate group of charts is being used. Because of the limitations of the charts for count of nonconformities, many organizations do not have occasion for their use.

6.3.3 c-Chart CONSTRUCTION


The procedures for the construction of a c chart are the same as those for the p chart. If the count of nonconformities, c0, is unknown, it must be found by collecting data, calculating trial control limits, and obtaining the best estimate. 1. Select the quality characteristic(s). The first step in the procedure is to determine the use of the control chart. Like the p chart, it can be established to control (a) a single characteristic, (b) a group of quality characteristics, (c) a part, (d) an entire product, or (e) a number of products. It can also be established for performance control of (a) an operator, (b) work center, (c) department, (d) shift, (e) plant, or (f) a corporation. The use for the chart or charts will be based on securing the greatest benefit for a minimum of cost.
UTeM

114

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

2. Determine the subgroup size and method. The size of a c chart is one inspected unit. An inspected unit could be one airplane, one case of soda cans, one gross of pencils, one bundle of Medicare applications, one stack of labels, and so forth. The method of obtaining the sample can either be by audit or on-line. 3. Collect the data. Data were collected on the count of nonconformities of a blemish nature for fiberglass canoes. These data were collected during the first and second weeks of May by inspecting random production samples. Data are shown in Table 6.2 for 25 canoes, which is the minimum number of subgroups needed for trial control limit calculations. Note that canoes MY132 and MY278 both had production difficulties. Table 6.2: Count of Blemish Nonconformities (c) by Canoe Serial Number
SERIAL COUNT OF NUMBER NONCONFORMITIES MY102 MY113 MY121 MY125 MY132 MY143 MY150 MY152 MY164 MY166 MY172 MY184 MY185 c 7 6 6 3 20 8 6 1 0 5 14 3 1 COMMENT SERIAL COUNT OF NUMBER NONCONFORMITIES MY198 MY208 MY222 MY235 MY241 MY258 MY259 MY264 MY267 MY278 MY281 MY288 Total c 3 2 7 5 7 2 8 0 4 14 4 5 COMMENT

Mold Sticking

Fell of skid

c = 141

UTeM

115

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

4. Calculate the trial central line and control limits. The formulas for the trial control limits are

UCL = c + 3 c

LCL = c 3 c
where c is the average count of nonconformities for a number of subgroups. The value of c is obtained from the formula c = c/g where g is the number of subgroups and c is the count of nonconformities. For the data in Table 6.2, the calculations are:

c=

c = 141 = 5.64
g 25

UCL = c + 3 c = 5.64 + 3 5.64 = 12.76


equation pg LCL = c 3 326 c = 5.64 3 5.64 = 1.48 or 0 Since a lower control limit of 1.48 is impossible, it is changed to zero. The upper control limit of 12.76 is left as a fraction so that the plotted point, which is a whole number, cannot lie on the control limit. Figure 6.4 illustrates the central line, c , the control limits, and the count of nonconformities, c, for each canoe of the preliminary data.

Figure 6.4: Control chart for count of nonconformities (c chart), using preliminary data.

UTeM

116

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

5. Established the revised central line and control limits. In order to determine the revised 3 control limits, the standard or reference value for the count of defects, c0, is needed. If an analysis of the preliminary data shows good control, then c can be considered to be representative of that process c0 = c . Usually, however, an analysis of the preliminary data does not show good control, as illustrated in Figure 6.4. A better estimate of c (one that can be adopted for c0) can be obtained by discarding out-ofcontrol values with assignable causes. Low values that do not have an assignable cause represent exceptionally good quality. The calculations can be simplified by using the formula

c new =
where

c c
g gd

cd = count of nonconformities in the discarded subgroups g d = number of discarded subgroups


Once an adopted standard of reference value is obtained, the revised 3 control limits are found using the formulas

UCL = c0 + 3 c0 LCL = c0 3 c0
Where c0 is the reference or standard value for the count of nonconformities. The count of nonconformities, c0, is the central line of the chart and is the best estimate using the available data. It equals c new . Using the information from Figure 6.4 and table 6.2, revised limits can be obtained. An analysis of Figure 6.4 shows that canoe numbers 132, 172, and 278 are out of control. Since canoes 132 and 278 have an assignable cause (Table 6.2), they are discarded; however, canoe 172 may be due to a chance cause, it is not discarded. Therefore, c new is obtained as follows;

c new =

c c
g gd

141 (20 + 14) = 4.65 25 2

UTeM

117

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

Since c new is the best estimate of the central line, c0=4.65. The revised control limits for the c chart are;

UCL = c0 + 3 c0 = 4.65 + 3 4.65 = 11.1 LCL = c0 3 c0 = 4.65 3 4.65 = 1.82 or 0


These control limits are used to start the chart beginning with canoes produced during the third week of May and are shown in Figure 6.5. If c0 had been known, the data collection and trial control limit phase would have been unnecessary.

Figure 6.5: c chart for canoe blemish nonconformities

UTeM

118

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

6. Achieve the objective. The reason for the control chart is to achieve one or more of the previously stated objectives. Once the objectives are reached, the chart is discontinued or inspection activity is reduced and resources are allocated to another quality problem. Some of the objectives, however, such as the first one, can be ongoing. As with the other types of the control charts, an improvement in the quality is expected after the introduction of a chart. At the end of the initial period, a better estimate of the number of nonconformities can be obtained. Figure 6.5 illustrates the change in c0 and in the control limits for August as the chart is continued in use. Quality improvement resulted from the evaluation of ideas generated by the project team such as attaching small pieces of carpet to the skids, faster-drying ink, worker training programs, and so on. The control chart shows whether the idea improves the quality, reduces the quality, or does not change the quality. A minimum of 25 subgroups is needed to evaluate each idea. The subgroups can be taken as often as practical, as long as they are representative of the process. Only one idea should be evaluated at a time. Figure 6.5 also illustrates a technique for reporting the number of nonconformities of individual characteristics, and the graph reports the total. This is an excellent technique for presenting the total picture and one that is accomplished with little additional time or cost. It is interesting to note that the serial numbers of the canoes that were selected for inspection were obtained from a random-number table. The control chart should be placed in a conspicuous place where it can be viewed by operating personnel.

6.3.3 u-Chart CONSTRUCTION (Chart for Count Nonconformities/Unit)


The c chart is applicable where the subgroup size is an inspected unit of one such as a canoe, an airplane, 1000 square feet of cloth, a rim of paper, 100 income tax forms, and a keg of nails. The inspected unit can be any size that meets the objective; however, it must be constant. Recall that the subgroup size, n, is not in the calculations because its value is 1. When situations arise where the subgroup size varies, then the u chart (count of nonconformities/unit) is the appropriate chart. subgroup size is constant. The u chart can also be used when the

UTeM

119

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

The u chart is mathematically equivalent to the c chart. It is developed in the same manner as the c chart, with the collection of 25 subgroups, calculation of trial central line and control limits, acquisition of an estimate of the standard or reference count of nonconformities per unit, and calculation of the revised limits. Formulas used for the procedure are

u=

c n
u n u n

u=

c n

UCL = u + 3

LCL = u 3

where c = count of nonconformities in a subgroup n = number inspected in a subgroup u = count of nonconformities/unit in a subgroup

u = average count of nonconformities/unit for many subgroups


Revised control limits are obtained by substituting u0 in the trial control limit formula. The u chart will be illustrated by an example. Each day clerk inspects the waybills of a small overnight air freight company for errors. Because the number of waybills varies form day to day, a u chart is the appropriate technique. If the number of waybills was constant, either the c or u chart would be appropriate. Data are collected as shown in Table 6.3. The date, number inspected, and count of nonconformities are obtained and posted to the table. The count of nonconformities per unit, u, is calculated and posted. Also, because the subgroup size varies, the control limits are calculated for each subgroup. Data for 5 weeks at 6 days per week are collected for a total of 30 subgroups. Although only 25 subgroups are required, this approach eliminates any bias that could occur from the low activity that occurs on Saturday. The calculation for central line is

u=

c = 3389 = 1.20 n 2823

UTeM

120

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

Table 6.3: Count of nonconformities per unit for way bills


DATE NUMBER INSPECTED n 110 82 96 115 108 56 120 98 102 115 88 71 95 103 113 85 101 42 97 92 100 115 99 57 89 101 122 105 98 48 2823 NONCONFORMITIES COUNT OF PER UNIT NONCONFORMITIES c 120 94 89 162 150 82 143 134 97 145 128 83 120 116 127 92 140 60 121 108 131 119 93 88 107 105 143 132 100 60 3389 u 1.09 1.15 0.93 1.41 1.39 1.46 1.19 1.37 0.95 1.26 1.45 1.17 1.26 1.13 1.12 1.08 1.39 1.43 1.25 1.17 1.31 1.03 0.94 1.54 1.20 1.04 1.17 1.26 1.02 1.25 UCL LCL

Jan-30 31 Feb-01 2 3 4 6 7 8 9 10 11 13 14 15 16 17 18 20 21 22 23 24 25 27 28 March-01 2 3 4 total

1.51 1.56 1.54 1.51 1.52 1.64 1.50 1.53 1.53 1.51 1.55 1.59 1.54 1.52 1.51 1.56 1.53 1.71 1.53 1.54 1.53 1.51 1.53 1.64 1.55 1.53 1.50 1.52 1.53 1.67

0.89 0.84 0.86 0.89 0.88 0.76 0.90 0.87 0.87 0.89 0.85 0.81 0.86 0.88 0.89 0.84 0.87 0.69 0.87 0.86 0.87 0.89 0.87 0.76 0.85 0.87 0.90 0.88 0.87 0.73

Calculations for the trial control limits and the plotted point, u, must be made for each subgroup. For January 30 they are

UCLJan30 = u + 3

u 1.20 = 1.20 + 3 = 1.51 n 110 u 1.20 = 1.20 3 = 0.89 110 n

LCLJan30 = u 3

u Jan 30 =

c 120 = = 1.09 n 110

These calculations must be repeated for 29 subgroups and the values posted to the table.
UTeM

121

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

A comparison of the plotted points with the upper and lower control limits in Figure 6.6 shows that there are no out-of-control values. Therefore, u can be considered the best estimate of u0 and u0 = 1.20. A visual inspection of the plotted points indicates a stable process. This situation is somewhat unusual at the beginning of control-charting activities.

Figure 6.6: u chart for errors on waybills. To determine control limits for the next 5-week period, we can use an average subgroup size in the same manner as the variable subgroup size of the p chart. A review of the chart shows that the control limits for Saturday are much wider apart than for the rest of the week. This condition is due to the smaller subgroup size. Therefore, it appears appropriate to establish separate control limits for Saturday. Calculations are as follows:

nsat .avg =

n = (56 + 71 + 42 + 57 + 48) = 55
g
5

UCL = u0 + 3

u0 1.20 = 1.20 + 3 = 1.65 55 n u0 1.20 = 1.20 3 = 0.76 n 55

LCL = u0 3

UTeM

122

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

ndaily.avg =

n = 2823 274 = 102, say, 100


g
25

UCL = u0 + 3

u0 1.20 = 1.20 + 3 = 1.53 n 100 u0 1.20 = 1.20 3 = 0.87 n 100

LCL = u0 3

The u chart is identical to the c chart in all aspects except two. One difference is the scale, which is continuous for a u chart but discrete for the c chart. This difference provides more flexibility for the u chart since the subgroup size can vary. The other difference is the subgroup size, which is 1 for the c chart. The u chart is limited in that we do not know the location of the nonconformities. For example, in Table 6.3, February 4 has 82 nonconformities out of 56 inspected for a value of 1.46. All 82 nonconformities could have been counted on one unit.

UTeM

123

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

EXERCISE 6.2
1. The count of surface nonconformities in 1000 square meters of 20kg kraft paper is given in table. Determine the trial central line and control limits and the revised central line and control limits, assuming that out of control points have assignable causes.
COUNT OF NONCONFORMITIES c 10 8 6 6 2 10 8 10 0 2 8 2 20 10 6 30 COUNT OF NONCONFORMITIES c 2 12 0 6 14 10 8 6 2 14 16 10 2 6 3

LOT NUMBER

LOT NUMBER

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

2. Determine the trial control limits and revised control limits for a u chart using the data in the table for the surface finish of rolls of white paper. Assume any out of control points have assignable causes.
LOT NUMBER SAMPLE COUNT OF LOT SIZE NONCONFORMITIES NUMBER c 45 51 36 48 42 5 33 27 31 22 25 35 32 43 SAMPLE COUNT OF SIZE NONCONFORMITIES c 48 35 39 29 37 33 15 33 27 23 25 41 37 28

1 2 3 4 5 6 7 8 9 10 11 12 13 14

10 10 10 9 10 10 10 8 8 8 12 12 12 10

15 16 17 18 19 20 21 22 23 24 25 26 27 28

10 11 10 10 10 10 10 10 11 10 10 10 9 10

UTeM

124

DMFD3582

CONTROL CHARTS FOR ATTRIBUTES

SUMMARY
In this chapter we have studied that 1. Attributes data is data that can be classified and counted. 2. There are two different groups of control charts for attributes. (1) One group charts is for nonconforming units: p & np charts. (2) and other is for nonconformities: u & c charts. 3. The p chart can help stabilize a process by indicating a lack of statistical control in some characteristic of interest measured as a proportion of output, such as fraction defective. 4. The np chart is mathematically equivalent to a p chart; however, the number, rather than the proportion of items, with the characteristics of interest is charted. 5. A c chart is used when a single unit of output may have multiple events, such as the number of defects in an appliance or in a roll of paper. 6. The u chart is used when the area of opportunity varies from unit to unit, and counts of the number of events are to be control charted.

REFERENCES
1. 2. 3. 4. Dale H. Besterfield, (2004), Quality Control, 7th Edition, Prentice Hall. Douglas C. Montgomery, (2005),Introduction to Statistical Quality Control, 5th Edition, John Wiley and Sons. Dona C. S. Summers, (2003),Quality, 3rd Edition, Prentice Hall. Frank M. Gryna, Richard C.H. Chua, Joseph A. Defeo, (2007), Jurans Quality Planning and Analysis, 5th Edition, Mc Graw-Hill.

UTeM

125

DMFD3582

Vous aimerez peut-être aussi