Vous êtes sur la page 1sur 4

dIXEL

Installing and Operating Instructions


Digital controller with off cycle defrost
4. FRONT PANEL COMMANDS

1592020020

XR20CX
CONTENTS 1. GENERAL WARNING ___________________________________________________ 1 2. GENERAL DESCRIPTION _______________________________________________ 1 3. CONTROLLING LOADS _________________________________________________ 1 4. FRONT PANEL COMMANDS _____________________________________________ 1 5. MAX & MIN TEMPERATURE MEMORIZATION _______________________________ 1 6. MAIN FUNCTIONS _____________________________________________________ 1 7. PARAMETERS ________________________________________________________ 2 8. DIGITAL INPUT (ENABLED WITH P3P = N) _________________________________ 3 9. TTL SERIAL LINE FOR MONITORING SYSTEMS ___________________________ 3 10. X-REP OUTPUT OPTIONAL ____________________________________________ 3 11. INSTALLATION AND MOUNTING _________________________________________ 3 12. ELECTRICAL CONNECTIONS ____________________________________________ 3 13. HOW TO USE THE HOT KEY_____________________________________________ 3 14. ALARM SIGNALS ______________________________________________________ 3 15. TECHNICAL DATA _____________________________________________________ 3 16. CONNECTIONS _______________________________________________________ 4 17. DEFAULT SETTING VALUES_____________________________________________ 4

: To display target set point; in programming mode it selects a parameter or confirm an operation. (DEF) To start a manual defrost (UP): To see the max. stored temperature; in programming mode it browses the parameter codes or increases the displayed value. (DOWN) To see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value. To switch the instrument off, if onF = oFF. Not enabled KEY COMBINATIONS:

1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. Check the application limits before proceeding.

+ + +
4.1 USE OF LEDS

To lock & unlock the keyboard. To enter in programming mode. To return to the room temperature display.

Each LED function is described in the following table. LED ON Flashing ON ON ON ON C/F ON C/F Flashing MODE Compressor enabled Anti-short cycle delay enabled Defrost enabled An alarm is occurring Continuous cycle is running Energy saving enabled Measurement unit Programming phase FUNCTION

1.2

SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation Warning: disconnect all electrical connections before any kind of maintenance. Fit the probe where it is not accessible by the End User. The instrument must not be opened. In case of failure or faulty operation send the instrument back to the distributor or to Dixell S.p.A. (see address) with a detailed description of the fault. Consider the maximum current which can be applied to each relay (see Technical Data). Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining. In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.

5. MAX & MIN TEMPERATURE MEMORIZATION


5.1 HOW TO SEE THE MIN TEMPERATURE
1. 2. 3. 1. 2. 3.
1. 2. Press and release the n key. The Lo message will be displayed followed by the minimum temperature recorded. By pressing the n key again or by waiting 5s the normal display will be restored.

2. GENERAL DESCRIPTION
Model XR20C, format 32 x 74 mm, is a digital thermostat with off cycle defrost designed for refrigeration applications at normal temperature. It provides a relay output to drive the compressor. It is also provided with 2 NTC or PTC probe inputs, the first one for temperature control, the second one, optional, to connect to the HOT KEY terminals to signal the condenser temperature alarm or to display a temperature. The digital input can operate as third temperature probe. The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It allows to program the controller by means the HOT KEY programming keyboard. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard.

5.2 HOW TO SEE THE MAX TEMPERATURE


Press and release the o key. The Hi message will be displayed followed by the maximum temperature recorded. By pressing the o key again or by waiting 5s the normal display will be restored.

5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED


Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt message will be displayed) To confirm the operation the rSt message starts blinking and the normal temperature will be displayed.

3. CONTROLLING LOADS
3.1 COMPRESSOR
Temper. The regulation is performed according to the temperature measured by the thermostat probe SET with a positive differential from the Time set point: if the temperature increases and reaches set point plus Compr. ON differential the compressor is started and then turned off when the temperature reaches the set point value again. In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF.

6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
Push and immediately release the SET key: the display will show the Set point value; 2. Push and immediately release the SET key or wait for 5 seconds to display the probe value again. 1.

6.2 HOW TO CHANGE THE SETPOINT


1. 2. 3. 4. Push the SET key for more than 2 seconds to change the Set point value; The value of the set point will be displayed and the C or F LED starts blinking; To change the Set value push the o or n arrows within 10s. To memorise the new set point value push the SET key again or wait 10s.

6.3 HOW TO START A MANUAL DEFROST


Push the DEF key for more than 2 seconds and a manual defrost will start.

3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter IdF controls the interval between defrost cycles, while its length is controlled by parameter MdF.

6.4 HOW TO CHANGE A PARAMETER VALUE


To change the parameters value operate as follows: 1592020020 XR20CX GB m&M r1.1 05.03.2007.doc XR20CX 1/4

dIXEL

Installing and Operating Instructions

1592020020

1. Enter the Programming mode by pressing the Set + n keys for 3s (the C or F LED starts blinking). 2. Select the required parameter. Press the SET key to display its value 3. Use UP or DOWN to change its value. 4. Press SET to store the new value and move to the following parameter. To exit: Press SET + UP or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.

6.5 THE HIDDEN MENU


The hidden menu Includes all the parameters of the instrument. 6.5.1 HOW TO ENTER THE HIDDEN MENU 1. Enter the Programming mode by pressing the Set + n keys for 3s (the C or F LED starts blinking). 2. Released the keys, then push again the Set+n keys for more than 7s. The Pr2 label will be displayed immediately followed from the HY parameter. NOW YOU ARE IN THE HIDDEN MENU. 3. Select the required parameter. 4. Press the SET key to display its value 5. Use o or n to change its value. 6. Press SET to store the new value and move to the following parameter. To exit: Press SET + o or wait 15s without pressing a key. NOTE1: if none parameter is present in Pr1, after 3s the noP message is displayed. Keep the keys pushed till the Pr2 message is displayed. NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. 6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL (user level) by pressing SET + n. In HIDDEN MENU when a parameter is present in First Level the decimal point is on.

6.6 HOW TO LOCK THE KEYBOARD


1. 2. 3.
Keep pressed for more than 3 s the UP + DOWN keys. The POF message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set point or the MAX o Min temperature stored If a key is pressed more than 3s the POF message will be displayed.

6.7 TO UNLOCK THE KEYBOARD


Keep pressed together for more than 3s the o and n keys, till the Pon message will be displayed.

6.8 THE CONTINUOUS CYCLE


When defrost is not in progress, it can be activated by holding the o key pressed for about 3 seconds. The compressor operates to maintain the ccS set point for the time set through the CCt parameter. The cycle can be terminated before the end of the set time using the same activation key o for 3 seconds.

6.9 THE ON/OFF FUNCTION


With onF = oFF, pushing the ON/OFF key, the instrument is switched off. The OFF message is displayed. In this configuration, the regulation is disabled. To switch the instrument on, push again the ON/OFF key. WARNING: Loads connected to the normally closed contacts of the relays are always supplied and under voltage, even if the instrument is in stand by mode.

7. PARAMETERS
REGULATION Hy Differential: (0,1 25,5C / 1255 F) Intervention differential for set point. Compressor Cut IN is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. LS Minimum set point: (- 50CSET/-58FSET): Sets the minimum value for the set point. US Maximum set point: (SET110C/ SET230F). Set the maximum value for set point. Ot Thermostat probe calibration: (-12.012.0C; -120120F) allows to adjust possible offset of the thermostat probe. P3P Third probe presence (P3): n= not present:, the terminal operates as digital input.; y= present:, the terminal operates as third probe. O3 Third probe calibration (P3): (-12.012.0C; -120120F). allows to adjust possible offset of the third probe. P4P Fourth probe presence: (n = Not present; y = present). o4 Fourth probe calibration: (-12.012.0C) allows to adjust possible offset of the fourth probe. OdS Outputs activation delay at start up: (0255min) This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter. AC Anti-short cycle delay: (050 min) minimum interval between the compressor stop and the following restart. CCt Compressor ON time during continuous cycle: (0.024.0h; res. 10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products. CCS Set point for continuous cycle: (-50150C) it sets the set point used during the continuous cycle.

COn Compressor ON time with faulty probe: (0255 min) time during which the compressor is active in case of faulty thermostat probe. With COn=0 compressor is always OFF. COF Compressor OFF time with faulty probe: (0255 min) time during which the compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is always active. CH Type of action: CL = cooling; Ht = heating. DISPLAY CF Temperature measurement unit: C=Celsius; F=Fahrenheit. WARNING: When the measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if necessary). rES Resolution (for C): (in = 1C; dE = 0.1 C) allows decimal point display. dLy Display delay: (0 20.0m; risul. 10s) when the temperature increases, the display is updated of 1 C/1F after this time. DEFROST IdF Interval between defrost cycles: (0120h) Determines the time interval between the beginning of two defrost cycles. MdF (Maximum) length for defrost: (0255min) When P2P = n, (not evaporator probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the maximum length for defrost. dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost start; SEt = set point; dEF = dEF label) dAd MAX display delay after defrost: (0255min). Sets the maximum time between the end of defrost and the restarting of the real room temperature display. ALARMS ALC Temperature alarms configuration: (Ab; rE) Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the SET+ALU or SET-ALL values. ALU MAXIMUM temperature alarm: (SET110C; SET230F) when this temperature is reached the alarm is enabled, after the ALd delay time. ALL Minimum temperature alarm: (-50.0 SETC; -58230F when this temperature is reached the alarm is enabled, after the ALd delay time. AFH Differential for temperature alarm recovery: (0,125,5C; 145F) Intervention differential for recovery of temperature alarm. ALd Temperature alarm delay: (0255 min) time interval between the detection of an alarm condition and alarm signalling. dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the detection of the temperature alarm condition after instrument power on and alarm signalling. CONDENSER TEMPERATURE ALARM (detected by the fourth probe) AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat probe; P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug. AL2 Low temperature alarm of condenser: (-55150C) when this temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay. Au2 High temperature alarm of condenser: (-55150C) when this temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay. AH2 Differential for temperature condenser alarm recovery: (0,125,5C; 145F) Ad2 Condenser temperature alarm delay: (0255 min) time interval between the detection of the condenser alarm condition and alarm signalling. dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min) bLL Compressor off with low temperature alarm of condenser: n = no: compressor keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case regulation restarts after AC time at minimum. AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case regulation restarts after AC time at minimum. DIGITAL INPUT i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the digital input is activated by closing the contact. i1F Digital input configuration: EAL = external alarm: EA message is displayed; bAL = serious alarm CA message is displayed. PAL = pressure switch alarm, CA message is displayed; dor = door switch function; dEF = activation of a defrost cycle; AUS = not enabled; Htr = kind of action inversion (cooling heating); FAn = do not set it; ES = Energy saving. did: (0255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the detection of the external alarm condition and its signalling. with i1F= dor: door open signalling delay with i1F = PAL: time for pressure switch function: time interval to calculate the number of the pressure switch activation. nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during the did interval, before signalling the alarm event (I2F= PAL). If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation. odc Compressor status when open door: no; Fan = normal; CPr; F_C = Compressor OFF. rrd Outputs restart after doA alarm: no = outputs not affected by the doA alarm; yES = outputs restart with the doA alarm; HES Temperature increase during the Energy Saving cycle : (-30,0C30,0C/-2286F) it sets the increasing value of the set point during the Energy Saving cycle. OTHER

1592020020 XR20CX GB m&M r1.1 05.03.2007.doc

XR20CX

2/4

dIXEL

Installing and Operating Instructions


12. ELECTRICAL CONNECTIONS

1592020020

Adr Serial address (1244): Identifies the instrument address when connected to a ModBUS compatible monitoring system. PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc = NTC probe. onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it. dP1 Thermostat probe display dP3 Third probe display- optional. dP4 Fourth probe display. rSE Real set point: (readable only), it shows the set point used during the energy saving cycle or during the continuous cycle. rEL Software release for internal use. Ptb Parameter table code: readable only.

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 mm2. Before connecting cables make sure the power supply complies with the instruments requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.

12.1 PROBE CONNECTION


The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.

8. DIGITAL INPUT (ENABLED WITH P3P = N)


The free voltage digital input is programmable in different configurations by the i1F parameter.

13. HOW TO USE THE HOT KEY


13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. 2. 3. 4. Program one controller with the front keypad. When the controller is ON, insert the Hot key and push o key; the "uPL" message appears followed a by flashing End Push SET key and the End will stop flashing. Turn OFF the instrument remove the Hot Key, then turn it ON again.

8.1 DOOR SWITCH INPUT (i1F = dor)


It signals the door status and the corresponding relay output status through the odc parameter: no, Fan = normal (any change); CPr, F_C = Compressor OFF. Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, the display shows the message dA and the regulation restarts is rtr = yES. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled.

8.2 GENERIC ALARM (i1F = EAL)


As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL alarm message. The outputs status dont change. The alarm stops just after the digital input is de-activated.

NOTE: the Err message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the Hot key to abort the operation.

13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)


1. 2. 3. 4. 5. Turn OFF the instrument. Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON. Automatically the parameter list of the Hot Key is downloaded into the Controller memory, the doL message is blinking followed a by flashing End. After 10 seconds the instrument will restart working with the new parameters. Remove the Hot Key..

8.3 SERIOUS ALARM MODE (i1F = bAL)


When the digital input is activated, the unit will wait for did delay before signalling the CA alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.

8.4 PRESSURE SWITCH (i1F = PAL)


If during the interval time set by did parameter, the pressure switch has reached the number of activation of the nPS parameter, the CA pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF. If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.

NOTE the message Err is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation.

14. ALARM SIGNALS


Message Cause P1 Room probe failure P3 P4 HA LA "HA2" "LA2" dA EA CA CA Outputs Compressor output acc. to par. Con and COF Third probe failure Outputs unchanged Fourth probe failure Outputs unchanged Maximum temperature alarm Outputs unchanged. Minimum temperature alarm Outputs unchanged. Condenser high temperature It depends on the Ac2 parameter Condenser low temperature It depends on the bLL parameter Door open Compressor according to rrd External alarm Output unchanged. Serious external alarm All outputs OFF. (i1F=bAL) Pressure switch alarm All outputs OFF (i1F=PAL)

8.5 START DEFROST (i1F = dFr)


It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired.

8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)


This function allows to invert the regulation of the controller: from cooling to heating and viceversa.

8.7 ENERGY SAVING (i1F = ES)


The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter) sum. This function is enabled until the digital input is activated.

8.8 DIGITAL INPUTS POLARITY


The digital input polarity depends on the i1P parameter. i1P=CL: the input is activated by closing the contact. i1P=OP: the input is activated by opening the contact

14.1 ALARM RECOVERY


Probe alarms P1, P3 and P4 start some seconds after the fault in the related probe; they automatically stop some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms HA, LA HA2 and LA2 automatically stop as soon as the temperature returns to normal values. Alarms EA and CA (with i1F=bAL) recover as soon as the digital input is disabled. Alarm CA (with i1F=PAL) recovers only by switching off and on the instrument.

9. TTL SERIAL LINE FOR MONITORING SYSTEMS


The TTL serial line, available through the HOT KEY connector, allows by means of the external TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU compatible such as the X-WEB500/3000/300.

10. X-REP OUTPUT OPTIONAL


As optional, an X-REP can be connected to the instrument, trough the HOY KEY connector. The X-REP output EXCLUDES the serial connection. To connect the X-REP to the instrument the following connectors must be used CAB51F(1m), CAB-52F(2m), CAB55F(5m),

14.2 OTHER MESSAGES


Pon PoF noP noA Keyboard unlocked. Keyboard locked In programming mode: none parameter is present in Pr1 On the display or in dP2, dP3, dP4: the selected probe is nor enabled None alarm is recorded.

11. INSTALLATION AND MOUNTING


Instrument XR20CX shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. The temperature range allowed for correct operation is 060 C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.

15. TECHNICAL DATA


Housing: self extinguishing ABS. Case: XR20CX frontal 32x74 mm; depth 60mm; Mounting: XR20CX panel mounting in a 71x29mm panel cut-out Protection: IP20; Frontal protection: XR20CX IP65 Connections: Screw terminal block 2,5 mm2 wiring. Power supply: according to the model: 12Vac/dc, 10%; 24Vac/dc, 10%; 230Vac 10%, 50/60Hz, 110Vac 10%, 50/60Hz Power absorption: 3VA max Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes. 3/4

1592020020 XR20CX GB m&M r1.1 05.03.2007.doc

XR20CX

dIXEL

Installing and Operating Instructions


17. DEFAULT SETTING VALUES

1592020020

Digital input: free voltage contact Relay outputs: compressor SPST 8(3) A, 250Vac; or 20(8)A 250Vac Data storing: on the non-volatile memory (EEPROM). Kind of action: 1B; Pollution grade: 2;Software class: A.; Rated impulsive voltage: 2500V; Overvoltage Category: II Operating temperature: 060 C;Storage temperature: -3085 C. Relative humidity: 2085% (no condensing) Measuring and regulation range: NTC probe: -40110C (-40230F); PTC probe: -50150C (-58302F) Resolution: 0,1 C or 1C or 1 F (selectable); Accuracy (ambient temp. 25C): 1 C 1 digit

16. CONNECTIONS
The X-REP output excludes the TTL output.. Its present in the following codes: XR20CX- xx2xx, XR20CX xx3xx;

16.1 XR20CX 8A COMPRESSOR


Room

9 10 11 12
8(3)A250V

1 2
Comp
Line

3
N.C.

8
Hot Key/IV Probe TTL or X-REP output

12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.

Labe Name Range C/F Set Set point LSUS 3.0 Hy Differential 2.0 0,125.5C/ 1 255F LS Minimum set point -50.0 -50CSET/-58FSET US Maximum set point 110 SET110C/ SET 230F Ot Thermostat probe calibration 0.0 -1212C /-120120F P3P Third probe presence n=not present; Y=pres. n O3 Third probe calibration 0 -1212C /-120120F P4P Fourth probe presence n=not present; Y=pres. n O4 Fourth probe calibration 0 -1212C /-120120F OdS Outputs delay at start up 0255 min 0 AC Anti-short cycle delay 1 0 50 min CCt Continuos cycle duration 0.024.0h 0.0 CC Set point for continuous cycle (-55.0150,0C) (-67302F) 3 S CO Compressor ON time with faulty probe 0 255 min 15 n CO Compressor OFF time with faulty 0 255 min 30 F probe CH Kind of action CL=cooling; Ht= heating cL CF Temperature measurement unit C C F in=integer; dE= dec.point rES Resolution dE dLy Display temperature delay 0 20.0 min (10 sec.) 0 1 120 ore IdF Interval between defrost cycles 8 0 255 min MdF (Maximum) length for defrost 20 rt, it, SEt, DEF dFd Displaying during defrost it dAd MAX display delay after defrost 0 255 min 30 rE= related to set; ALc Temperat. alarms configuration Ab Ab = absolute
Set110.0C; Set230F ALU MAXIMUM temperature alarm -50.0CSet/ -58FSet ALL Minimum temperature alarm AFH Differential for temperat. alarm (0,1C25,5C) (1F45F) recovery ALd Temperature alarm delay 0 255 min dAo Delay of temperature alarm at start up 0 23h e 50 AP2 Probe for temperat. alarm of nP; P1; P2; P3; P4 condenser AL2 Condenser for low temperat. alarm (-55 150C) (-67 302F) AU2 Condenser for high temperat. alarm (-55 150C) (-67 302F) Differ. for condenser temp. alar. [0,1C 25,5C] [1F AH2 recovery 45F] Ad2 Condenser temperature alarm delay 0 254 (min.) , 255=nU Delay of cond. temper. alarm at start dA2 up 0.0 23h 50 Compr. off for condenser low n(0) - Y(1) bLL temperature alarm Compr. off for condenser high AC2 temperature alarm n(0) - Y(1) i1P Digital input polarity oP=opening;CL=closing i1F Digital input configuration EAL, bAL, PAL, dor; dEF; Htr, AUS did Digital input alarm delay 0255min nPS Number of activation of pressure 0 15 switch odc Compress status when open door no; Fan; CPr; F_C rrd Regulation restart with door open nY alarm HES Differential for Energy Saving (-30C30C) (-54F54F) Adr Serial address 0247 PbC Kind of probe Ptc; ntc onF on/off key enabling nu, oFF; ES dP1 Room probe display -dP3 Third probe display -dP4 Fourth probe display -rSE Real set point value actual set rEL Software release -Ptb Map code --

--Pr1 Pr2 Pr2 Pr1 Pr2 Pr2 Pr2 Pr2 Pr2 Pr1 Pr2 Pr2 Pr2 Pr2 Pr1 Pr2 Pr1 Pr2 Pr1 Pr1 Pr2 Pr2 Pr2 Pr1 Pr1 Pr2 Pr2 Pr2 Pr2 Pr2 Pr2 Pr2 Pr2 Pr2 Pr2 Pr2 Pr1 Pr1 Pr1 Pr2 Pr2 Pr2 Pr2 Pr2 Pr1 Pr2 Pr1 Pr1 Pr2 Pr2 Pr2 Pr2

16.2 XR20CX 20A COMPRESSOR


Room

110 -50.0 1 15 1.3 P4 -40 110 5 15 1,3 n n cL dor 15 15 no y 0 1 ntc nu -------

9 10 11 12
20(8)A250V

5
Comp

8
Hot Key/IV Probe TTL or X-REP output

Line

12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.

Dixell S.p.A. Z.I. Via dellIndustria, 27 32010 Pieve dAlpago (BL) ITALY tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 E-mail: dixell@dixell.com - http://www.dixell.com 1592020020 XR20CX GB m&M r1.1 05.03.2007.doc XR20CX 4/4

Vous aimerez peut-être aussi