http://electrical- engineering- portal.com/dry- transformer- percent- impedance- definition April 12, 2013
Edvard
Dry T ransf ormer Percent Impedance Def inition (on photo dry type transf ormer by Engineering company B&S, Ukraine)
Introduction
The percent impedance is the percent voltage required to circulate rated current flow through
one transformer winding when another winding is short-circuited at the rated voltage tap at rated frequency. %Z is related to the short circuit capacity of the transformer during short circuit conditions. For a two winding transformer with a 5% impedance, it would require 5% input voltage applied on the high voltage winding to draw 100% rated current on the secondary winding when the secondary winding is short-circuited. If 100% rated voltage is applied to the high voltage winding, approximately 20X rated current would flow in the secondary winding when the secondary winding is short-circuited.
Impedance Levels
Based kVA 0 150 151 300 301 600 601 2,500 2,501 5,000 5,001 7,500 7,501 10,000 Above 10,000 Minimum Impedance, % Manufacturers standard 4 5 6 6.5 7.5 8.5 9.5
Important Notes
1. The impedance of a two-winding transformer shall not vary from the guaranteed value by more that 7.5% 2. The impedance of a transformer having three or more windings or having zigzag windings shall not vary from the guaranteed value by more than 10% 3. The impedance of an auto-transformer shall not vary from the guaranteed value by more than 10% 4. The difference of impedances between transformers of the same design shall not exceed 10% of the guaranteed values 5. Differences of impedance between auto-transformers of the same design shall not exceed 10% of the guaranteed values
inductive reactance, and is expressed in ohms. From the perspective of a load, the total input impedance may include the impedance of the upstream generator, transformer, line reactor and conductors. The power system impedance is useful for estimating the available short circuit current. Sample calculations for a three phase transformer rated 500kVA, 4160:480, 60Hz, 6% impedance: Transformer reactance Xt = (kV2/MVA) x %Z/100 = (0.482 / 0.5) x 0.06 = 0.027648 ohms Approximate available short circuit current = 480/(1.732 x 0.027648) = 10,023.7 amps