Académique Documents
Professionnel Documents
Culture Documents
USER'S GUIDE
M210315en-B March 2003
PUBLISHED BY Vaisala Oyj P.O. Box 26 FIN-00421 Helsinki Finland Phone (int.): +358 9 8949 1 Fax: +358 9 8949 2227
Visit our Internet pages at http://www.vaisala.com/ Vaisala 2003 No part of this manual may be reproduced in any form or by any means, electronic or mechanical (including photocopying), nor may its contents be communicated to a third party without prior written permission of the copyright holder. The contents are subject to change without prior notice.
Please observe that this manual does not create any legally binding obligations for Vaisala towards the customer or end user. All legally binding commitments and agreements are included exclusively in the applicable supply contract or Conditions of Sale.
_________________________________________________________________________________
Table of Contents
CHAPTER 1
GENERAL INFORMATION............................................................................ 5 About This Manual ................................................................... 5 Contents of This Manual ....................................................... 5 Version Information ............................................................... 6 Related Manuals ................................................................... 6 Feedback............................................................................... 6 Safety......................................................................................... 6 General Safety Considerations ............................................. 6 Product Related Safety Precautions ..................................... 7 ESD Protection...................................................................... 8 Warranty .................................................................................... 9 Technical Support .................................................................... 9
CHAPTER 2
PRODUCT OVERVIEW................................................................................ 11 Introduction to DKP206 and DKP210 ................................... 11 Foundation Set .................................................................... 14 Guy Wires............................................................................ 15 Lightning Rod ...................................................................... 16 Winch (Optional).................................................................. 16 Product Nomenclature ........................................................ 17
CHAPTER 3
INSTALLATION............................................................................................ 19 Siting Criteria .......................................................................... 19 Ambient Measurements ...................................................... 19 Tilting Direction.................................................................... 21 Soil Evaluation..................................................................... 21 Site Preparation...................................................................... 21 Power Supply and Communication Lines ........................... 21 Tools Required for Installation ............................................. 22 Unpacking Instructions ......................................................... 22 Inspecting the Delivery........................................................ 22 Contents of the Delivery...................................................... 22 Foundation.............................................................................. 25 Soil and Frost Conditions .................................................... 25 Orientation of the Mast........................................................ 25 Concrete Foundations ......................................................... 28 Making a New Concrete Block....................................... 29 Using an Existing Concrete Block.................................. 32 Assembling the Mast ............................................................. 33 Work Order.......................................................................... 33
VAISALA_________________________________________________________________________ 1
Installing the Pedestal Tube ................................................34 Connecting the Lowest Mast Tube to the Pedestal Tube .....................................................................36 Connecting the Lifting Rod to the Mast ...............................37 Connecting the Guy Wire Set to the Mast ...........................38 Assembling the Mast Tubes ................................................39 Assembling the Lightning Rod.............................................39 Connecting the Grounding Cable to the Insulated Guy Wire..............................................................................41 Routing the Device Cables ..................................................42 Erecting the Mast....................................................................43 Installing and Using the Winch ............................................43 Securing the Hinge ..............................................................46 Connecting the Guy Wires to the Concrete Blocks .............46 Equipment Grounding and Lightning Protection................50 Equipment Grounding..........................................................53 Grounding of the Lightning Rod ..........................................55
CHAPTER 4
MAINTENANCE............................................................................................57 Regular Maintenance..............................................................57 Tilting the Mast .......................................................................57 Disconnecting and Securing the Guy Wire .........................57 Using the Winch ..................................................................58 Tilting the Mast Manually.....................................................58 Erecting the Mast....................................................................59
CHAPTER 5
2 _____________________________________________________________________M210315en-B
_________________________________________________________________________________
List of Figures
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Figure 44 Figure 45 Figure 46 Figure 47 Figure 48 DKP210 Mast Dimensions (in mm) .......................................... 12 DKP206 Mast Dimensions (in mm) .......................................... 13 Foundation Set for DKP210 and DKP206 Masts ..................... 14 Guy Wires Set .......................................................................... 15 Passive Lightning Rod with the Cable and the Holders ........... 16 Winch (Optional)....................................................................... 16 Recommended Mast Location in Open Area ........................... 20 Recommended Mast Length on Top of a Building ................... 20 Contents of the Mast Delivery (Part 1) ..................................... 23 Contents of the Mast Delivery (Part 2) ..................................... 24 DKP210 Mast Orientation......................................................... 26 DKP206 Mast Orientation......................................................... 27 Main Mast Block and Orientation Plate (Dimensions in mm) ................................................................. 28 Concrete Block for Guy Wire (Dimensions in mm) .................. 29 Reinforcement for the Concrete Blocks ................................... 30 Foundation Assembly for the Mast Base ................................. 31 Foundation Assemblies for a New Concrete Block .................. 31 Accessories for Existing Concrete Block Installation ............... 32 Pedestal Tube Alignment to North-South Direction ................. 34 Pedestal Tube Attachment ....................................................... 34 Pedestal Tube Adjustment with Water Level ........................... 35 Axle for Hinge ........................................................................... 36 Hinge Bolt Installation............................................................... 36 Lifting Rod Installation Accessories ......................................... 37 Lifting Rod Clamp Attachment ................................................. 38 Guy Wire Attachment ............................................................... 38 Alignment of the Mast Tubes.................................................... 39 Lightning Rod Installation to the Mast ...................................... 40 Dimensions (in mm) for Lightning Rod Assembly on the Mast............................................................................... 40 Alignment of the Insulated Guy Wire and the Lightning Rod Holders ..................................................................................... 41 Lightning Rod Cable Attachment ............................................. 42 Winch Installation ..................................................................... 43 Securing Clamp of the Winch................................................... 44 Lower Cable Lead .................................................................... 44 Attaching the Hook ................................................................... 45 Bolts and Washers for Securing the Hinge .............................. 46 Guy Wires................................................................................. 47 Connecting the U-bolt to the Eye Bolt ...................................... 48 Guy Wire 1 Attachment ............................................................ 48 Securing the Guy Wires ........................................................... 49 Installing Cable Shrouds .......................................................... 49 Location of the Grounding Rods and an Optional Grid, the Arrow Points to the Mast Tilt Direction ..................................... 51 Ground Rod Installation............................................................ 52 Installing the Grounding Bar..................................................... 53 Connecting the Grounding Cables to the Bar .......................... 54 Grounding Cable Protection ..................................................... 55 Grounding of the Lightning Rod ............................................... 56 Tilted Mast with Tilting Support ................................................ 58
VAISALA_________________________________________________________________________ 3
List of Tables
Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Manual Revisions .......................................................................6 Product Nomenclature for DKP206 Masts ...............................17 Product Nomenclature for DKP210 Masts ...............................17 Examples of Soil Resistivities, Ohm-Meters.............................52 DKP210 Specifications .............................................................61 DKP206 Specifications .............................................................62
4 _____________________________________________________________________M210315en-B
CHAPTER 1
GENERAL INFORMATION
VAISALA_________________________________________________________________________ 5
Version Information
Table 1
Manual Code M210315en-A M210315en-B
Manual Revisions
Description The first version of the DKP206 and DKP210 Tiltable Pole Mast User's Guide. This manual, the second version of the DKP206 and DKP210 Tiltable Pole Mast User's Guide.
Related Manuals
For sensor and other equipment specific foundation and installation information, refer to the separate instruction manuals that are supplied with the equipment.
Feedback
Vaisala Customer Documentation Team welcomes your comments and suggestions on the quality and usefulness of this publication. If you find errors or have other suggestions for improvement, please indicate the chapter, section, and page number. You can send comments to us by e-mail: manuals@vaisala.com
WARNING
Warning alerts you to a serious hazard. If you do not read and follow instructions very carefully at this point, there is a risk of injury or even death.
CAUTION
Caution warns you of a potential hazard. If you do not read and follow instructions carefully at this point, the product could be damaged or important data could be lost.
6 _____________________________________________________________________M210315en-B
NOTE
WARNING
WARNING
For safety reasons, do not install the mast when the wind speed is over 7 m/s.
WARNING
WARNING
Be careful when erecting the mast. See that there are no power lines or other obstacles above the mast.
WARNING
Secure the mast properly to prevent it from falling. Tighten all the adjustment screws securely.
WARNING
Be sure that there are no persons under the mast during erecting the mast.
WARNING
When erecting the mast with the winch, avoid touching the wire with bare hands. Do not try to guide the wire.
VAISALA_________________________________________________________________________ 7
WARNING
To minimize shock hazard, the instrument chassis and cabinet must be connected to an electrical ground. The power cable must either be plugged into an approved electrical outlet or the instrument must be carefully grounded to a low-resistance safety ground.
WARNING
Do not operate the equipment in an explosive environment, for example, in the presence of flammable gases or fumes.
WARNING
Do not attempt internal service or adjustment unless another person, capable of rendering first aid and resuscitation, is present.
WARNING
Operating personnel must not remove instrument covers. Component replacement or internal adjustments must be made by qualified maintenance personnel. Do not replace components with the power cable connected. Under certain conditions, dangerous voltages may exist for some time even with the power cable disconnected. To avoid injuries, disconnect power and discharge circuits before touching them.
CAUTION
Do not install substitute parts or modify the unit. Improper modification can damage the product or lead to malfunction. Contact Vaisala for repairs to ensure that safety features are maintained.
ESD Protection
Electrostatic Discharge (ESD) can cause immediate or latent damage to electronic circuits. Vaisala products are adequately protected against ESD for their intended use. However, it is possible to damage the product by delivering electrostatic discharges when touching, removing, or inserting any objects inside the equipment housing.
8 _____________________________________________________________________M210315en-B
To make sure you are not delivering high static voltages yourself: - Handle ESD sensitive components on a properly grounded and protected ESD workbench. When this is not possible, ground yourself to the equipment chassis before touching the boards. Ground yourself with a wrist strap and a resistive connection cord. When neither of the above is possible, touch a conductive part of the equipment chassis with your other hand before touching the boards. - Always hold the boards by the edges and avoid touching the component contacts.
Warranty
For certain products Vaisala normally gives a limited one year warranty. Please observe that any such warranty may not be valid in case of damage due to normal wear and tear, exceptional operating conditions, negligent handling or installation, or unauthorized modifications. Please see the applicable supply contract or conditions of sale for details of the warranty for each product.
Technical Support
For technical questions, contact the Vaisala technical support: E-mail Telephone Fax helpdesk@vaisala.com +358 9 8949 2789 +358 9 8949 2790
VAISALA_________________________________________________________________________ 9
10 ____________________________________________________________________M210315en-B
CHAPTER 2
PRODUCT OVERVIEW
This chapter introduces the DKP206 and DKP210 mast features, options, and the product nomenclature.
VAISALA________________________________________________________________________ 11
0303-019
Figure 1
12 ____________________________________________________________________M210315en-B
NOTE
50 mm 1.97 in. 60 mm 2.36 in. 75 mm 2.95 in. 101.6 mm 4 in. 1 890 mm 74.4 in 2 353 mm 92.6 in. 4 900 mm 192.9 in. 5 475 mm 215.5 in. 6 000 mm 236.2 in. 7 000 mm 275.6 in. 7 450 mm 293.3 in. 9 000 mm 354.3 in. 10 000 mm 393.7 in. 11 065 mm 435.6 in.
0303-020
Figure 2
VAISALA________________________________________________________________________ 13
Foundation Set
The foundation set includes all the necessary installation accessories both for a new and an existing concrete block.
0303-021
Figure 3
The following numbers refer to Figure 3 above: 1 2 3 4 5 6 7 8 9 = = = = = = = = = Nuts and washers for the foundation bolts Orientation plate for the mast base Eye nuts for the guy wires Wedge bolts for an existing concrete block Plates with the nut for the guy wire blocks Square plate for the mast base Foundation bolts Bar for installing the wedge bolts Key piece for the wedge bolts
14 ____________________________________________________________________M210315en-B
Guy Wires
One set of guy wires is delivered in the basic set. The top fastener of the guy wires is mounted at the uppermost tube of the mast during the installation. The basic delivery contains one set of guy wires and the accessories as shown in Figure 4 below.
0207-090
Figure 4
The following numbers refer to Figure 4 above. 1 2 3 4 5 = = = = = Top fastener Upper mast tube Guy wires Installation accessories Cable shrouds
VAISALA________________________________________________________________________ 15
Lightning Rod
The mast is delivered with a passive lightning rod made from copper. The lightning rod holders are made of non-conductive material to protect the mast devices from overvoltage when lightning occurs. Refer to Figure 5 below. An active type of lightning rod is available as an option for areas where heavy lightning activity occurs frequently.
0303-022
Figure 5
Winch (Optional)
The optional winch is equipped with the friction break, thus stopping automatically when the user releases the handle. The winch is easily installed to the pedestal tube. After erecting the mast, the winch should be removed from the pedestal tube and stored in a dry and warm place.
0303-023
Figure 6
Winch (Optional)
16 ____________________________________________________________________M210315en-B
Product Nomenclature
Table 2
Standard Nomenclature DKP206W DKP206AV DKF200 DKL200 DKP206GW DKP200SW DKP200LR DKW200 DKP200TS DKH200ACCESS DKP200IS
The package contains either of these product alternatives. Optional with DKP206AV Optional Optional Optional with Active Lightning Rod Optional with DKP206AV
Table 3
Standard Nomenclature DKP210W DKP210AV
Optional with DKP210AV Optional Optional Optional Optional with Active Lightning Rod Optional with DKP206AV
VAISALA________________________________________________________________________ 17
18 ____________________________________________________________________M210315en-B
CHAPTER 3
INSTALLATION
This chapter provides instructions for installing the DKP206 and DKP210 masts.
VAISALA________________________________________________________________________ 19
0204-040
Figure 7
NOTE
0204-041
Figure 8
20 ____________________________________________________________________M210315en-B
Tilting Direction
Also note the tilting direction of the mast. When installed in the northern hemisphere, the mast tilts to west. There should be a clear area up to 9 m on the west side of the mast. The area should be free of obstacles preventing the mast from being erected and tilted.
Soil Evaluation
Always, evaluate the soil to determine the appropriate type of the foundation required. When designing the foundation, the local construction companies must be consulted to find out about the soil and frost conditions in your area. When the soil is frost-susceptible, make sure to always use the proper insulation.
CAUTION
For the mast base installation, the soil bearing capacity has to exceed 45 kPa (940 pounds-force/sq. foot).
VAISALA________________________________________________________________________ 21
- Check cable conduit diameters or use additional termination boxes. - Ground the cable shield at both ends. - Use spike and overvoltage protection devices at both ends of field cables. Always make a detailed cabling and wiring plan. Data transmission lines from the outdoor sites to indoor devices have to be prepared carefully. Also the power supply for the equipment used needs to be planned carefully. It is recommended to use a conduit to protect the cables that connect the indoor components to the outdoor components from damage and moisture. Also traffic, standing water, and the twist and stress caused by the connectors will damage the cables.
22 ____________________________________________________________________M210315en-B
0303-024
Figure 9
The following numbers refer to Figure 9 above. 1 2 3 4 5 6 7 = = = = = = = Holders of the lightning rod (2 pcs) Upper mast tube, 60 mm Lightning rod with the cable Guy wires Cable shrouds for the guy wires (yel/blk, 3 sets) Winch Lifting rod, 60 mm
NOTE
Figure 9 above and Figure 10 on page 24 provide only examples of the contents. The contents may vary depending on the model of the mast and on the selected options.
VAISALA________________________________________________________________________ 23
0303-025
Figure 10
The following numbers refer to Figure 10 above: 1 2 3 4 = = = = Tilting support Pedestal tube, 100 mm Lower mast tube, 75 mm Assembly set: Guy wire fasteners (3 pcs) Guy assembly set (1 set) Hinge set (1 set) Lifting rod assembly set (1 set) Lightning rod assembly set (1 set) Foundation set: Foundation bolts, M20 (7pcs) Wedge bolts, M20 (7 pcs) Tool for wedge bolts (1 pc) Eye nuts for guy wires (3 pcs) Spring washers, M20 (10 pcs) Washers, M20 (10 pcs) Nuts, M20 (14 pcs) Nuts with plate, M20 (3 pcsc) Square plate with 4 nuts (1 pc) Orientation plate (1 pc)
24 ____________________________________________________________________M210315en-B
VAISALA________________________________________________________________________ 25
0207-064
Figure 11
NOTE
26 ____________________________________________________________________M210315en-B
0207-065
Figure 12
NOTE
4 m 13.1 ft.
VAISALA________________________________________________________________________ 27
Concrete Foundations
The DKP206 and DKP210 pole masts can be mounted on a new or an existing concrete block. The pole mast is fixed to the concrete block with foundation bolts.
NOTE
The minimum weight of the main mast block is 400 kg (882 lb.).
When constructing a new concrete block, fasten the foundation bolt assembly simultaneously with the concrete pour. If there is an existing concrete foundation, you have to drill the holes for the foundation bolts. In both cases, use the delivered orientation plate for correct placing of the foundation bolts. For the protection of the cables, it is recommended to install a cable conduit, which has a minimum diameter of 70 mm (2.76 in.). See Figure 13 below.
0303-026
Figure 13
NOTE
70 mm 2.76 in. 80 mm 3.15 in. 200 mm 7.87 in. 250 mm 9.84 in. 600 mm 23.62 in. 800 mm 31.50 in.
28 ____________________________________________________________________M210315en-B
Concrete block dimensions for the guy wires are presented in Figure 14 below.
0303-027
Figure 14
NOTE
40 mm 1.57 in. 50 mm 1.97 in. 240 mm 9.45 in. 400 mm 15.75 in. 600 mm 23.62 in. 800 mm 31.50 in.
VAISALA________________________________________________________________________ 29
NOTE
10 mm 0.39 in. 12 mm 0.47 in. 40 mm 1.57 in. 50 mm 1.97 in. 70 mm 2.76 in. 150 mm 5.91 in. 300 mm 11.81 in. 400 mm 15.75 in. 600 mm 23.62 in.
600
0207-068
400
Figure 15 2.
If necessary, place the cable duct tubes into the casting mould prior to casting. The recommended inner diameter of the duct tube is 70 mm (2.76 inches). Place the steel reinforcement into the casting mould. Screw the foundation bolts (number 1 in Figure 16 on page 31) to the nuts (6) which are fixed to the square metal plate (3).
3. 4.
30 ____________________________________________________________________M210315en-B
0207-069
Figure 16 5.
Fix the orientation plate (2) to the upper ends of the foundation bolts (1) with eight nuts (4 and 5), see Figure 16 above. The top of the bolt should be approximately 80 mm above the orientation plate, refer to Figure 13 on page 28.
0207-062
Figure 17 6.
Install the foundation assembly into the mould so that the foundation bolt threads stand above the surface, see Figure 13 on page 28. The orientation plate (number 4 in Figure 17 above) should be at the same height as the top of the finalized concrete block. Protect the threads of the bolts above the orientation plate, for example, by taping them. Also check the correct alignment of the foundation assembly with the orientation plate
VAISALA________________________________________________________________________ 31
(number 4 in Figure 17 on page 31). "N" should face north and "S" should face south. 7. For the guy wires, fix the foundation bolt (number 2 in Figure 17 on page 31) to the plate with a nut (3). Fix the eye nut (1) to the other end of the foundation bolt. Level the assembly so that the top of the bolt will be 40 mm above the concrete in the finalized block. The eye nut will then be one centimeter above the finalized concrete block. Pour in the concrete. Finish the concrete block.
8.
NOTE
0207-070
Figure 18 2.
First, install the key piece (number 3 in Figure 18 above) correctly inside the wedge bolt (4). The narrow end should point to the direction of the lower arrow in Figure 18 above. Assemble the wedge bolts into the holes. There are four bolts for the mast base and one bolt for each of the guy wire blocks.
32 ____________________________________________________________________M210315en-B
3. 4. 5. 6.
Hammer the wedge bolts (4) down using the provided bar (2). Screw the foundation bolts (1) to the wedge bolts and tighten the screws properly. Fill the remaining space of the holes with a suitable compound. Start erecting the mast after the compound is dry.
VAISALA________________________________________________________________________ 33
0303-028
Figure 19 2.
First place the washers and then the spring washers onto the previously installed nuts and lift the pedestal tube through the bolts onto the washers. Install the nuts with the washers and spring washers to the foundation bolts. Refer to Figure 20 below.
3.
0303-029
Figure 20
34 ____________________________________________________________________M210315en-B
The following numbers refer to Figure 20 on page 34: 1 2 3 4 4. = = = = Foundation bolt Spring washers, under and above the plate Washers, under and above the plate Nuts, under and above the plate
Level the pedestal tube to vertical with the nuts that are under the plate. For adjusting the level, use the appropriate wrench and the water level to check that the pedestal tube is vertical. Refer to Figure 21 below. Finally, tighten the bolts with the appropriate wrenches.
5.
0303-030
Figure 21
VAISALA________________________________________________________________________ 35
0303-031
Figure 22 2. 3.
Thread the Allen bolt (4) with the washers (2 and 3) to either end of the axle. Lift the mast end (3) on the hinge (1) and install the axle (2), see Figure 23 below.
0303-032
Figure 23
36 ____________________________________________________________________M210315en-B
4.
Thread the other Allen bolt to the axle and tighten both ends with the Allen key.
0303-033
Figure 24
To attach the lifting rod to the previously installed lower mast tube, follow the procedure below: 1. 2. Place the lifting rod (number 1 in Figure 25 on page 38) on the mast assembly as shown in Figure 25 on page 38. Make sure that both taps on the clamp go into the railing and the hooks (number 3 in Figure 25 on page 38) at the end of the clamp go firmly around the opposite clamp. Install the bolts (number 2 in Figure 25 on page 38) with the washers and tighten them with an Allen key.
3.
VAISALA________________________________________________________________________ 37
0303-034
Figure 25
2.
0303-035
Figure 26
38 ____________________________________________________________________M210315en-B
0303-036
Figure 27
VAISALA________________________________________________________________________ 39
0303-037
Figure 28 4. 5.
Secure the holders to the mast with the bolts in the clamps (4). Check that the dimensions for the installed lightning rod are as illustrated in Figure 29 below.
0303-038
Figure 29
NOTE
20 mm 0.79 in. 150 mm 5.91 in. 350 mm 13.8 in. 440 mm 17.3 in. 1065 mm 41.9 in
40 ____________________________________________________________________M210315en-B
0303-039
Figure 30 2.
Alignment of the Insulated Guy Wire and the Lightning Rod Holders
Attach the grounding cable (number 3 in Figure 31 on page 42) with a wire rope clip (5) below the insulator (4).
NOTE
Leave some extra cable between the lightning rod and the wire rope clip on the guy wire to ensure that the guy wire does not pull the lightning rod downwards.
VAISALA________________________________________________________________________ 41
0303-040
Figure 31
The following numbers refer to Figure 31 above. 1 2 3 4 5 = = = = = Lightning rod Lightning rod holders Grounding cable Insulator Wire rope clip
42 ____________________________________________________________________M210315en-B
Before erecting the mast, check that the bolts of the top fastener are tight. The top fastener (number 1 in Figure 26 on page 38) is mounted on the upper mast tube.
0303-041
Figure 32
Winch Installation
VAISALA________________________________________________________________________ 43
2.
Install the winch towards the pedestal tube so that the tap (3) on the tube goes to the hole (2) on the winch. Make sure that the plastic cover on the winch faces up. Wrap the clamps (1) around the tube to the clamp assemblies (4) and attach them. Finally, secure the clamps with the provided pin clips as shown in Figure 33 below.
3. 4.
0303-042
Figure 33 5.
Attach the cable bearer (number 2 in Figure 34 below) with the quick link (3) to the plate lug (4) of the pedestal plate. Make sure that the wire (1) with the hook points east (when installing in the northern hemisphere).
0303-043
Figure 34 6.
Clip the hook (number 2 in Figure 35 on page 45) to the plate lug (1) of the lifting rod.
44 ____________________________________________________________________M210315en-B
0303-044
Figure 35 7.
Take a good grasp on the handle and turn it clockwise to erect the mast. The winch is equipped with a friction break and thus, it stops automatically when you release the handle.
WARNING
Make sure that there are no people under the mast when the mast is being erected.
WARNING
When erecting the mast with the winch, avoid touching the wire with bare hands. Do not try to guide the wire.
WARNING
Always wear gloves when using the winch. Do not touch the gears of the winch.
VAISALA________________________________________________________________________ 45
NOTE
Always assemble the washers (number 3 in Figure 36 below) under the spring washers (2) to prevent the paint from being damaged.
0303-045
Figure 36
The following numbers refer to Figure 36 above: 1 2 3 = = = Allen bolt Spring washer Washer
46 ____________________________________________________________________M210315en-B
Follow the procedure below to connect the guy wires to the concrete blocks: 1. Connect the guy wires 2 and 3 as instructed in step a. below and connect the guy wire 1 as instructed in step b. below. The guy wire 1 is installed differently from the others, because it is released when the mast is tilted. For the location of the guy wires, refer to Figure 37 below.
0303-046
Figure 37 a.
Guy Wires
For the guy wires 2 and 3, connect the U-bolt (number 2 in Figure 38 on page 48) to the eye bolt (1) installed on the concrete block. Slide the strap (3) onto the U-bolt and thread the nuts.
VAISALA________________________________________________________________________ 47
0207-091
Figure 38 b.
For the guy wire 1, connect the U-bolt (number 3 in Figure 39 below) to the eye nut (1) with an additional bow shackle (2) to enable easy releasing of the wire. The strap (4) is used as with the guy wires 2 and 3.
0303-047
Figure 39
NOTE
The additional bow shackle (number 2 in Figure 39 above) may differ from the one shown in the figure.
2.
Secure the guy wires with the provided wire rope clips (number 3 in Figure 40 on page 49). Place the wire rope clips on the wire so that the forged, grooved part clamps the wire coming from the mast (the tension side) and the U-bolt clamps down on the end-most section of the wire. Check also that the wire is properly in the key groove (1). After assembling the wire rope clips properly, tension the guy wire by tightening the nuts (number 2 in Figure 40 on page 49) to slide the strap, until the initial tension of the guy wires is
3.
48 ____________________________________________________________________M210315en-B
sufficient. When tensioning the guy wires, make sure that the mast remains straight and that all the guy wires are equally tensioned.
0207-092
Figure 40 4. 5.
Cut the extra guy wire. Finally, place the black and yellow cable shrouds around the guy wires, see Figure 41 below. There is one package of shrouds for each wire.
0207-093
Figure 41
The following numbers refer to Figure 41 above. 1 2 = = Guy wire Cable shrouds
VAISALA________________________________________________________________________ 49
WARNING
Failure to provide proper grounding may result in personnel injury or death from electrical shock and may severely damage equipment.
WARNING
Lightning protection is required to prevent personnel injury and equipment damage due to direct lightning strikes and lightninginduced current surges.
- The materials used in the manufacture of the grounding systems must be chosen to prevent them from forming an electrolytic couple. It is recommended to use copper (Cu). - The equipment grounding system and lightning protection grounding system should be located as far as possible from each other. The minimum recommended distance is 5 m (16 ft.). Due to this the lightning rod grounding cable is routed down from the top of the mast via the guy wire which is insulated from the mast construction, refer to number 2 in Figure 42 on page 51. The equipment grounding should be done near the mast block as illustrated in Figure 42 on page 51.
50 ____________________________________________________________________M210315en-B
0303-048
Figure 42
Location of the Grounding Rods and an Optional Grid, the Arrow Points to the Mast Tilt Direction
The following numbers refer to Figure 42 above. 1 2 3 4 5 6 = = = = = = The grounding rod The guy wire block of the insulated guy wire The mast block An optional grounding rod An optional connecting cable The 5-meter minimum distance between the rods
- The recommended grounding resistance is 10 or less for both the grounding of lighting protection rod and for the equipment grounding. Soil conditions (sand, rocks, etc.) and the ground resistance measurement determines the design and construction of the grounding system. Buried ground rods and / or buried wire can be used for the ground network. The type and combination used depend on soil conditions (ease of installation) and on the value of measured ground resistance (the most effective way of reducing
VAISALA________________________________________________________________________ 51
resistance to the required value of 10 or less). Measurements of the earth resistance must be made at least 48 hours after rainfall. - The connection between ground rods and the equipment frames and copper cables should be made with appropriate compression lugs, bolts, nuts, and lock washers. - Optionally, the top of the earth electrode can be housed inside covered pit as illustrated in Figure 43 below. Table 4 Examples of Soil Resistivities, Ohm-Meters
Median 26 33 55 190 300 800 Variation 1 ... 50 10 ... 55 30 ... 80 80 ... 300 100 ... 500 600 ... 1 000
Soil Type Topsoil, loam Inorganic clays of high plasticity Silty or clayey fine sands with slight plasticity Fine sandy or silty clays, silty clays, clean clays Silty sands, poorly graded sand-silt mixtures Well graded gravel, gravel sand mixtures
Due to the above reasons and soil variations, the grounding accessories presented in this manual (rods, connectors, etc.) are only examples of the proper ones, thus recommended to be supplied locally.
0303-049
Figure 43
52 ____________________________________________________________________M210315en-B
The following numbers refer to Figure 43 on page 52: 1 2 3 4 = = = = Access well Grounding rod Compression lug Grounding cable
Equipment Grounding
The equipment grounding cable is connected to the equipment ground system (rod or other) from the one main grounding point, which is normally a grounding bar located underneath the main system enclosure.
CAUTION
Always use clamps for connecting a cable to the grounding rod or two cables together, do not solder.
Consult the local authority for local grounding requirements. A copper grounding cable and conductive grounding rod(s) are recommended. Usually, the customer is responsible for supplying grounding cables, rods, clamps, power cables, long distance signal cables, and conduits for cables.
0207-094
Figure 44
VAISALA________________________________________________________________________ 53
The following numbers refer to Figure 44 on page 53. 1 2 3 = = = Hammer Protective cap Grounding bar
NOTE
The grounding accessories shown in Figure 44 on page 53 are examples of the grounding accessories. It is recommended to supply them locally.
Silver epoxy material or equivalent should be used to bond the interconnecting wire to the ground rods. The cross section of the interconnection copper wire is recommended to be 25 mm2. The length should be about 2 meters. The 2-meter cable can be obtained by first cutting the connection cable of the lightning rod to the correct length. The rest of the cable can be used for grounding the equipment. The original length of the cable is 15 m.
0207-095
Figure 45
The following numbers refer to Figure 45 above. 1 2 3 = = = Grounding cable Clamp Grounding bar
Always protect the grounding cable on the surface of the concrete block as illustrated in Figure 46 on page 55. This applies only when
54 ____________________________________________________________________M210315en-B
the mast is installed on an existing concrete block. It is recommended to use a conduit when you cast the block for the mast.
0303-050
Figure 46
The following numbers refer to Figure 46 above. 1 2 3 4 = = = = Clamp Grounding cables, for the lightning detector and power supply unit Plate to protect the grounding cables and the AC power cable Mast base
VAISALA________________________________________________________________________ 55
0303-051
Figure 47
The following numbers refer to Figure 47 above. 1 2 3 4 = = = = Clamp Rod Cable from the lightning rod Guy wire attachment
56 ____________________________________________________________________M210315en-B
CHAPTER 4
MAINTENANCE
This chapter provides information that is needed for the basic maintenance of the DKP206 and DKP210 masts.
Regular Maintenance
The mast tubes are anodized and painted for durability in demanding harsh environments. Normally there is no need for maintenance. Only the mast should be checked yearly for any damage to the coating. Check also yearly the guy wires for correct tightness. Inspect the guy wires for damage as well.
VAISALA________________________________________________________________________ 57
CAUTION
3.
Lower the mast slowly with the winch by turning the handle.
CAUTION
4. 5.
Install the tilting support to the end of the mast, see Figure 48 below. Lower the mast slowly with the winch so that finally the mast rests on the tilting support.
0303-052
Figure 48
58 ____________________________________________________________________M210315en-B
VAISALA________________________________________________________________________ 59
60 ____________________________________________________________________M210315en-B
CHAPTER 5
TECHNICAL DATA
This chapter provides the technical data of the DKP206 and DKP210 masts.
Specifications
Table 5 DKP210 Specifications
Description/Value 10 m (32.8 feet) 100 mm (3.94 in) 60 mm (2.36 in) 50 m/s (100 knots) 75 m/s (145 knots) 125 kg Stainless steel Aluminum alloy Stainless steel 28 kN (6 295 lbf) Black and yellow colored cable shrouds to the height of 2 meters from the ground Galvanized steel, thread M20, length 300 mm (11.8 in), with M20 wedge bolts (cast or drilled into concrete using the provided orientation plate) Stainless steel Corrosion-resistant powder coating Anodized and painted Galvanized Uncoated -40 +60 C (-40 ... 140 F) Property Height Diameter Lowest section Highest section Maximum wind speed With one set of guy wires With two sets of guy wires Weight (DKP210W with winch) Pedestal tube and hinge Mast tubes and lifting rod Guy wires Material Breaking strength Marking Threaded anchor bolts
Other parts, e.g., bolts Coating/Painting Pedestal tube Aluminum parts Steel parts Stainless steel parts Temperature
VAISALA________________________________________________________________________ 61
Table 6
DKP206 Specifications
Description/Value 6 m (19.7 feet) 100 mm (3.94 in) 60 mm (2.36 in) 50 m/s (100 knots) 105 kg Stainless steel Aluminum alloy Stainless steel 28 kN (6 295 lbf) Black and yellow colored warning pieces to the height of 2 meters from the ground Galvanized steel, thread M20, length 300 mm (11.8 in), with M20 wedge bolts (cast or drilled into concrete using the provided orientation plate) Stainless steel Corrosion-resistant powder coating Anodized and painted Galvanized Uncoated -40 +60 C (-40 ... 140 F)
Property Height Diameter Lowest section Highest section Maximum wind speed With one set of guy wires Weight (DKP206W with winch) Pedestal tube and hinge Mast tubes and lifting rod Guy wires Material Breaking strength Marking Threaded anchor bolts
Other parts, e.g., bolts Coating/Painting Pedestal tube Aluminum parts Steel parts Stainless steel parts Temperature
62 ____________________________________________________________________M210315en-B