Vous êtes sur la page 1sur 2

A TOGNUM GROUP BRAND

DIESEL GENSET - 60 HZ AIR CHARGE-AIR COOLING


1090 - 1200 kWe 480V BENEFITS
// // // // //

Low installment cost Best fuel consumption values Long maintenance intervals High-efciency components Best-in-class reliability and availability

SYSTEM RATINGS
Standby Power
Genset Type DS 1200 D6S Engine Type 18V 2000 G85 Nominal Rating kWe 1) 1200* Emissions kWe 2) 1180 EPA 2

Prime Power
Genset Type DP 1090 D6S Engine Type 18V 2000 G85 Nominal Rating kWe 1) 1090* Emissions kWe 2) 1060 EPA 2

* Adjustment of fan power demand required

//

REFERENCE CONDITIONS 1) 2)
40C (104F) 55C (131F) 1000 mbar 400 m 25C (77F) 55C (131F) 1000 mbar 100 m

//

ENGINE DATA
130/150 mm (5.1/5.9 in) 90V 1.99 lit. (121 cu in) 18V: 35.8 lit. (2185 cu in) EN 590, Grade No.1-D/2-D (ASTM D975-00)

Ambient air temp.: Charge air coolant temp.: Ambient air pressure: Altitude above sea level:

Bore/Stroke Cyl. conguration Cyl. displacement Displacement, total Fuel specication

Application 3B

Denition Prime Power Continuous operation with variable load Standby Power Standby operation with variable load

3D

Load factor: < 75 % Operating hours/year: unrestricted Overload: 10 % capability (ICXN) Load factor: < 85 % Operating hours/year: max. 500 Overload: Fuel stop power (IFN)

Gensets available also with Water Charge Air Cooling All Gensets are available with optional Voltages 380V and 440V. Ratings can variate please contact your MTU distributor.

Genset Type Engine Type Generator type Fuel Consumption * 100% load g/kWh (l/h) 75% load g/kWh (l/h) 50% load g/kWh (l/h) Mechanical Radiator, unit-mounted Max. air temp. on fan C Ambient temperature C Fan air ow m3/s Air ow restriction Air Intake Intake air depression Intake air ow Exhaust System Exhaust gas ow Exhaust gas temperature Exhaust back pressure Generator Temperature rise Lube System Engine oil capacity Emissions NOx CO Dust Air born noise level at 1m Exhaust noise level at 1 m Genset Lengths Widths Height Total Weight, wet Pascal mbar m3/s m3/s C mbar K l mg/Nm3 mg/Nm3 mg/Nm3 dB(A) dB(A) mm mm mm kg

Fuel Optimized Standby DS1200D6SRA 18V 2000 G85 740RSL7046 204 (322) 211 (250) 213 (168) 45 40 28.6 200 15 1.8 4.4 530 50 130 (F) 130 6400 3500 200 106 118 5050 2140 2426 7959

Prime DP1090D6SRA 18V 2000 G85 740RSL7046 203 (291) 209 (225) 213 (153) 45 40 23.2 200 15 1.7 4 510 50 130 (F) 130 6400 3500 200 105 117 5050 2140 2426 7959

All ratings include power requirement for mechanical driven cooling fan. * Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml. Note: This drawing is provided for reference only and should not be used for planning installation. Please contact your local distributor for more detailed information. Materials and specications subject to change without notice.

// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone +49 7541 90 7060 / Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacic / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore / Phone +65 6861 5922 / Fax +65 6861 3615 / powergenregion2@mtu-online.com // USA / Canada / Mexico / MTU Onsite Energy Corporation / 100 Power Drive / Mankato, MN 56001 / USA / Phone +1 507 625 7973 / Fax +1 507 625 2968 / powergenregion3@mtu-online.com // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich / Germany / Phone +49 89 20 30 42 800 / Fax +49 89 20 30 42 900 / info@mtu-online.com // www.mtu-online.com

Subject to change. | 3233401 | 1/10 | VMD 2010-09.