PROJECT: YELLOW TOWER SECTION: WATER SUPPLY SYSTEM DATE: 5-May-08 REV.

: 01

COLD WATER FLOW RATE REQUIRED


1. Water Supply Flow Rate Required for pumping system Item 1 2 3 4 5 Description Water Closet Wash Basin Urinal Sink Shower TOTAL: Total Sanitary Fixture Total Flow Rate K Facture Total Water Flow Required for Item 1 2. Pipe Sizing Total Water Flow Required Grand Total Water Flow Required (10%) Pipe Sizing Calculated References: a Water Flow Calculation - Le Formulaire Des Installations Sanitaires, Tome 1, Eau Froide (French Standard) Pipe Sizing - 1997 ASHRAE Fundamentals Handbook : : : 1.901 2.38 40 l/s l/s mm Fixture No. 120 100 40 15 5 280 : : : : U/Flow Rate 0.10 0.10 0.15 0.20 0.15 T/Flow Rate 12.000 10.000 6.000 3.000 0.750 31.750 nos l/s

280.000 31.750 0.060 1.901

l/s

PROJECT: YELLOW TOWER SECTION: WATER SUPPLY SYSTEM DATE: 5-May-08 REV.: 01

COLD WATER FLOW RATE REQUIRED


1. Water Supply Flow Rate Required for pumping system Item 1 2 3 4 5 Description Water Closet Wash Basin Urinal Sink Shower TOTAL: Total Sanitary Fixture Total Flow Rate K Facture Total Water Flow Required for Item 1 2. Pipe Sizing Total Water Flow Required Grand Total Water Flow Required (10%) Pipe Sizing Calculated References: a Water Flow Calculation - Le Formulaire Des Installations Sanitaires, Tome 1, Eau Froide (French Standard) Pipe Sizing - 1997 ASHRAE Fundamentals Handbook : : : 1.437 2.01 50 l/s l/s mm Fixture No. 41 42 1 10 42 136 : : : : U/Flow Rate 0.10 0.10 0.10 0.20 0.15 T/Flow Rate 4.100 4.200 0.100 2.000 6.300 16.700 nos l/s

136.000 16.700 0.086 1.437

l/s