TECHNICAL DATA & SERVICE MANUAL

XH2442 / CH2442 XH3642 / CH3642 XH4242 / CH4242 TH2442 / CH2442 TH3642 / CH3642 TH4242 / CH4242 KH2442 / CH2442 KH3642 / CH3642 UH2442 / CH2442 UH3642 / CH3642

FILE NO.

SPLIT SYSTEM AIR CONDITIONER


INDOOR MODEL No. XH2442 XH3642 XH4242 TH2442 TH3642 TH4242 KH2442 KH3642 UH2442 UH3642 PRODUCT CODE No. 854 017 11 854 017 12 854 017 13 854 017 14 854 017 15 854 017 16 854 017 07 854 017 08 854 017 19 854 017 20 OUTDOOR MODEL No. CH2442 CH3642 CH4242 PRODUCT CODE No. 854 017 21 854 017 22 854 017 23

Section

2
Outdoor Unit

Indoor Unit

3
XH2442 XH3642 XH4242 TH2442 TH3642 TH4242 CH2442

UH2442

UH3642

KH2442 KH3642

CH3642 CH4242

85464849182000

REFERENCE NO. SM830082

Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must : q Carefully read this instruction booklet before beginning. q Follow each installation or repair step exactly as shown. q Observe all local, state, and national electrical codes. q Pay close attention to all warning and caution notices given in this manual. This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.

When Installing
In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors. In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.

In an area with High Winds


Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.

In a Snowy Area (for Heat Pump-type Sys-tems)


Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing


Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas. Keep all tubing runs as short as possible. Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run.

CAUTION

If Necessary, Get Help


These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.

In Case of Improper Installation


The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.

NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either narrow or wide rather than as liquid or gas.

SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidentaly injury or death. Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.

When Servicing

Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.

CAUTION
Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas. Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.

When Transporting

Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.

SM830082

WHO SHOULD USE THIS MANUAL


This service manual is made to assist the service technician apply his knowledge and training to this model air conditioner. This manual is written both for experienced service persons and those who are new to air conditioning service. To help those with less experience or who are new to this kind of unit we have included more explanations of basic procedures in simple language than is usual in some service manuals. The experienced technician will of course find he knows many of these things already and can go directly to the procedures and information he needs; the less experienced technician will better understand what to do even before he arrives on the job, and therefore be better able to work by himself as well as assist the more experienced technician.

TABLE OF CONTENTS
1. SPECIFICATIONS ............................................................................................ I - 1 1-1 Unit Specifications .....................................................................................I - 2 1-2 Major Component Specifications ...............................................................I - 12 (A) Indoor Units ..................................................................................................I - 12 (B) Outdoor Units ...............................................................................................I - 22 1-3 Other Component Specifications ...............................................................I - 25 1-4 Dimensional Data ......................................................................................I - 38 (A) Indoor Units ..................................................................................................I - 38 (B) Outdoor Units ...............................................................................................I - 47 1-5 Refrigerant Flow Diagram ..........................................................................I - 49 1-6 Operating Range .......................................................................................I - 50 1-7 Cooling Capacity........................................................................................I - 51 1-8 Heating Capacity .......................................................................................I - 71 1-9 Performance Charts...................................................................................I - 72 1-10 Noise Criterion Curves ...............................................................................I - 90 1-11 Increasing the Fan Speed..........................................................................I - 95 1-12 Air throw Distance Chart ............................................................................I - 96 1-13 Installation Instructions ..............................................................................I - 99 2. PROCESSES AND FUNCTIONS ......................................................................II 2-1 Room Temperature Control ......................................................................II 2-2 Cold Draft Prevention (Heating Cycle) ...................................................... II 2-3 Automatic Fan Speed (Indoor Unit) .......................................................... II 2-4 Outdoor Fan Speed Control ......................................................................II 2-5 Freeze Prevention (Cooling) .....................................................................II 2-6 Condensing Temperature Control (Cooling) ............................................. II 1 2 4 5 6 7 8

ii

SM830082

2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17

Overload Protection (Heating) .................................................................. II - 9 Discharge Temperature Control (Cooling and Heating) ........................... II - 10 Auto. Mode for Automatic Heating/Cooling Switching .............................. II - 11 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) .................... II - 13 4-Way Valve, Solenoid Control .................................................................II - 14 Automatic Restart after Power Interruption ............................................... II - 15 Electronic Expansion Control Valve .......................................................... II - 16 Compressor Discharge Gas Temperature ................................................ II - 16 Compressor Current Detection Circuit ...................................................... II - 17 Electronic Expansion Valve ......................................................................II - 18 Voltage Detection Control ......................................................................... II - 19

3. ELECTRICAL DATA ........................................................................................III - 1 3-1 Indoor Unit (Electric Wiring Diagram, Schematic Diagram) ..................... III - 2 3-2 Outdoor Unit (Electric Wiring Diagram, Schematic Diagram) .................. III - 12 4. SERVICE PROCEDURES ............................................................................... IV - 1 4-1 Troubleshooting ...................................................................................... IV - 2 4-2 Checking the Electrical Components ...................................................... IV - 30

iii

SM830082

1. Specifications

1. SPECIFICATIONS
1-1 Unit Specifications ................................................................................. I - 2 4-Way Air Discharge Semi-concealed Type ........................................... I - 2 Ceiling Mounted Type .............................................................................. I - 5 Concealed Duct Type .............................................................................. I - 8 Wall-Mounted Type.................................................................................. I - 10 Major Component Specifications ............................................................. I - 12 (A) Indoor Units ........................................................................................ I - 12 (B) Outdoor Units ..................................................................................... I - 22 Other Component Specifications ............................................................. I - 25 4-Way Air Discharge Semi-concealed Type ........................................... I - 25 Ceiling Mounted Type .............................................................................. I - 28 Concealed Duct Type .............................................................................. I - 31 Wall-Mounted Type.................................................................................. I - 33 Outdoor Units........................................................................................... I - 35 Dimensional Data .................................................................................... I - 38 (A) Indoor Units ........................................................................................ I - 38 4-Way Air Discharge Semi-concealed Type ....................................... I - 38 Ceiling Mounted Type ........................................................................ I - 40 Concealed Duct Type ......................................................................... I - 42 Wall-Mounted Type ............................................................................ I - 45 (B) Outdoor Units ..................................................................................... I - 47 Refrigerant Flow Diagram ........................................................................ I - 49 Operating Range ..................................................................................... I - 50 Cooling Capacity ...................................................................................... I - 51 Heating Capacity ..................................................................................... I - 71 Performance Charts ................................................................................. I - 72 (1) Operating Current ............................................................................... I - 72 (2) Operating Pressure ............................................................................ I - 84 Noise Criterion Curves ............................................................................. I - 90 Increasing the Fan Speed ........................................................................ I - 95 Air throw distance chart ........................................................................... I - 96 Installation Instructions ............................................................................ I - 99 Tubing Length .......................................................................................... I - 99 SELECTING THE INSTALLATION SITE ................................................. I - 100 ELECTRICAL WIRING ............................................................................ I - 104 Electrical characteristics .......................................................................... I - 108

1-2

1-3

1-4

1-5 1-6 1-7 1-8 1-9

1-10 1-11 1-12 1-13

SM830082

I-1

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 11.2 2,450 11.6 2,350 10.0 230 24,000 8.6 23,400 8.4

XH2442 CH2442 230 - 208 V / 1 Phase / 60 Hz Heating 25,000 16,400 710 / 530 / 450 10.2 208 187 - 253 11.7 2,500 2,150 25 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) / Automatic Washable, easy access, long life fiter (2,500 hr) 38 / 35 / 31 53 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 1 / 4 (6.35) 3 / 4 (19.05) Indoor unit Outdoor unit (380) (776) (776) (22) (78) (860) (860) (5) (338) (835) (845) (26) (0.238) (104) (964) (999) (8) (0.100) 32-17/32 40 16-3/8 170 12.3 28-15/16 37-1/32 13-3/8 157 (826) (1,016) (416) (77) (0.349) (735) (940) (340) (71) 12-1/8 30-9/16 30-9/16 49 3-1/16 33-27/32 33-27/32 11 13-5/16 32-7/8 33-9/32 57 8.4 4-3/32 37-15/16 39-11/32 18 3.5 12.3 2,450 2,020 (7.0) 230 (7.0) 208 24,300 15,800

Maximum overcurrent protection FEATURES Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control Indoor - Hi / Me / Lo Outdoor - Hi

Horizontal / Vertical dB - A dB - A

REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Net weight Indoor grille dimensions PNR-XHS2432 Net weight Indoor / Outdoor unit Height Width Depth Shipping weight Shipping volume Indoor grille Package dimensions PNR-XHS2432 Shipping weight Height Width Depth Height Width Depth in. (mm) in. (mm) in. (mm) lbs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3) Narrow pipe Wide pipe

in. (mm) in. (mm)

Package dimensions

Shipping volume

Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I-2

SM830082

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 15.4 3,350 15.8 3,200 10.7 230 34,500 10.5 33,500 10.6

XH3642 CH3642 230 - 208 V / 1 Phase / 60 Hz Heating 37,500 25,000 (7.0) 230 187 - 253 18.2 3,850 3,150 40 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) / Automatic Washable, easy access, long life fiter (2,500 hr) 44 / 37 / 33 56 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 3 / 8 (9.52) 3 / 4 (19.05) Indoor unit Outdoor unit (368) (1,066) (776) (27) (78) (1,150) (860) (7) (368) (1,125) (845) (32) (0.35) (104) (1,257) (999) (10) (0.131) 52-7/32 40 16-3/8 227 19.8 48-5/8 37-1/32 13-3/8 203 (1,326) (1,016) (416) (103) (0.56) (1,235) (940) (340) (92) 14-1/2 41-31/32 30-9/16 60 3-1/16 45-9/32 33-27/32 15 14-1/2 44-9/32 33-9/32 71 12.4 4-3/32 49-1/2 39-11/32 22 4.6 19.3 3,750 2,950 (7.0) 208 36,500 23,500

1,050 / 840 / 720 11.0 208

Maximum overcurrent protection FEATURES Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Net weight Indoor grille dimensions PNR-XHS2432 Net weight Indoor / Outdoor unit Package dimensions Shipping weight Shipping volume Indoor grille Package dimensions PNR-XHS2432 Shipping weight Shipping volume Height Width Depth Height Width Depth Height Width Depth Narrow pipe Wide pipe Indoor - Hi / Me / Lo Outdoor - Hi

Horizontal / Vertical dB - A dB - A

in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3)

Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I-3

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 20.6 4,200 21.0 4,100 10.4 230 42,000 14.4 40,000 14.0

XH4242 CH4242 230 - 208 V / 1 Phase / 60 Hz Heating 44,000 28,000 (7.0) 230 187 - 253 21.7 4,450 3,700 45 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) / Automatic Washable, easy access, long life fiter (2,500 hr) 45 / 38 / 34 56 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 3 / 8 (9.52) 3 / 4 (19.05) Indoor unit Outdoor unit (368) (1,066) (776) (27) (78) (1,150) (860) (7) (368) (1,125) (845) (32) (0.35) (104) (1,257) (999) (10) (0.131) 52-7/32 40 16-3/8 227 19.8 48-5/8 37-1/32 13-3/8 203 (1,326) (1,016) (416) (103) (0.56) (1,235) (940) (340) (92) 14-1/2 41-31/32 30-9/16 60 3-1/16 45-9/32 33-27/32 15 14-1/2 44-9/32 33-9/32 71 12.4 4-3/32 19-1/2 39-11/32 22 4.6 22.2 4,350 3,550 (7.0) 208 42,000 26,000

1,050 / 840 / 720 10.4 208

Maximum overcurrent protection FEATURES Controls

Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control Indoor - Hi / Me / Lo Outdoor - Hi dB - A dB - A Horizontal / Vertical

REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Net weight Indoor grille dimensions PNR-XHS2432 Net weight Indoor / Outdoor unit Height Width Depth Shipping weight Shipping volume Indoor grille Package dimensions PNR-XHS2432 Shipping weight Height Width Depth Height Width Depth in. (mm) in. (mm) in. (mm) lbs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3) Narrow pipe Wide pipe

in. (mm) in. (mm)

Package dimensions

Shipping volume

Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I-4

SM830082

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 10.7 2,350 11.3 2,280 10.0 230 22,400 8.0 21,600 7.9

TH2442 CH2442 230 - 208 V / 1 Phase / 60 Hz Heating 25,400 15,700 550 / 490 / 460 10.0 208 187 - 253 11.7 2,550 2,070 25 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) Manual / Automatic Washable, easy access 40 / 38 / 36 53 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 1 / 4 (6.35) 3 / 4 (19.05) Indoor unit Outdoor unit (190) (1,300) (670) (240) (1,387) (761) (27) (35) (0.253) 28-15/16 37-1/32 13-3/8 32-17/32 40 16-3/8 157 170 12.3 (735) (940) (340) (826) (1,016) (416) (71) (77) (0.349) 7-15/32 51-3/16 26-3/8 9-7/16 54-19/32 29-31/32 60 77 8.9 12.9 2,500 2,040 (7.0) 230 (7.0) 208 25,000 15,000

Maximum overcurrent protection FEATURES Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Indoor grille dimensions Height Width Depth Net weight Shipping weight Shipping volume Narrow pipe Wide pipe Indoor - Hi / Me / Lo Outdoor - Hi

Horizontal / Vertical dB - A dB - A

in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) lbs. (kg) cu.ft. (m3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

SM830082

I-5

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 15.1 3,350 15.7 3,170 10.4 230 34,000 10.7 33,000 10.8

TH3642 CH3642 230 - 208 V / 1 Phase / 60 Hz Heating 40,000 25,000 (7.3) 230 187 - 253 18.2 3,950 3,000 40 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) Manual / Automatic Washable, easy access 46 / 42 / 37 56 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 3 / 8 (9.52) 3 / 4 (19.05) Indoor unit Outdoor unit (240) (1,575) (670) (317) (1,678) (789) (41) (47) (0.42) 48-5/8 37-1/32 13-3/8 52-7/32 40 16-3/8 203 227 19.8 (1,235) (940) (340) (1,326) (1,016) (416) (92) (103) (0.56) 9-7/16 62-1/32 26-3/8 12-15/32 66-1/16 31-1/16 90 104 14.8 19.6 3,890 2,900 (7.3) 208 39,000 24,000

1,100 / 930 / 750 10.7 208

Maximum overcurrent protection FEATURES Controls

Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control Indoor - Hi / Me / Lo Outdoor - Hi dB - A dB - A Horizontal / Vertical

REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Indoor grille dimensions Height Width Depth Net weight Shipping weight Shipping volume in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) lbs. (kg) cu.ft. (m3) Narrow pipe Wide pipe

in. (mm) in. (mm)

DATA SUBJECT TO CHANGE WITHOUT NOTICE Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

I-6

SM830082

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 20.6 4,300 21.3 4,200 10.0 230 42,000 14.8 40,000 14.3

TH4242 CH4242 230 - 208 V / 1 Phase / 60 Hz Heating 44,000 28,000 (7.0) 230 187 - 253 21.7 4,450 3,700 45 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) Manual / Automatic Washable, easy access 47 / 43 / 38 56 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 3 / 8 (9.52) 3 / 4 (19.05) Indoor unit Outdoor unit (240) (1,575) (670) (317) (1,678) (789) (41) (47) (0.42) 48-5/8 37-1/32 13-3/8 52-7/32 40 16-3/8 203 227 19.8 (1,235) (940) (340) (1326) (1,016) (416) (92) (103) (0.56) 9-7/16 62-1/32 26-3/8 12-15/32 66-1/16 31-1/16 90 104 14.8 22.5 4,350 3,550 (7.0) 208 42,000 26,000

1,100 / 930 / 750 10.4 208

Maximum overcurrent protection FEATURES Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Indoor grille dimensions Height Width Depth Net weight Shipping weight Shipping volume Narrow pipe Wide pipe Indoor - Hi / Me / Lo Outdoor - Hi

Horizontal / Vertical dB - A dB - A

in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) lbs. (kg) cu.ft. (m3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

SM830082

I-7

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) External Static Pressure S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. in.Aq (Pa) BTU / Wh VAC VAC A W (17F)** A 11.5 2,550 12.1 2,480 10.0 230 24,000 8.4 23,400 7.7

UH2442 CH2442 230 - 208 V / 1 Phase / 60 Hz Heating 27,000 16,200 670 / 530 / 460 0.2 (49) : at shipment / 0.4 (100) : using jumper cable 10.0 208 187 - 253 12.0 2,650 2,080 25 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-BH80UA. WL (72-hour ON / OFF) / Optional 34 / 30 / 27 : at shipment / 38 / 34 / 30 : using jumper cable 53 Electronic Expansion Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 1 / 4 (6.35) 3 / 4 (19.05) Indoor unit Outdoor unit (310) (1,000) (630) (32) (358) (1,191) (1,191) (37) (0.334) 28-15/16 37-1/32 13-3/8 32-17/32 40 16-3/8 157 170 12.3 (735) (940) (340) (826) (1,016) (416) (71) (77) (0.349) 12-7/32 39-3/8 24-13/16 1-1/4 14-3/32 46-7/8 30-13/16 82 11.8 12.5 2,550 1,960 (7.0) 230 (7.0) 208 26,500 15,500

Maximum overcurrent protection FEATURES

Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Indoor - Hi / Me / Lo Outdoor - Hi dB - A dB - A Horizontal / Vertical

Refrigerant control REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Narrow pipe Wide pipe Height Width Depth Net weight Package dimensions Height Width Depth Shipping weight

in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) ibs. (kg) in. (mm) in. (mm) in. (mm) lbs. (kg) cu.ft. (m3)

Unit dimensions

Shipping volume

DATA SUBJECT TO CHANGE WITHOUT NOTICE Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

I-8

SM830082

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) External Static Pressure S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. in.Aq (Pa) BTU / Wh VAC VAC A W (17F)** A 15.1 3,350 15.7 3,170 10.3 230 34,500 10.0 33,000 9.9

UH3642 CH3642 230 - 208 V / 1 Phase / 60 Hz Heating 37,500 25,000 36,500 24,000

1,060 / 920 / 750 0.24 (59) : at shipment / 0.38 (94) : using jumper cable 10.5 208 187 - 253 18.2 3,780 3,000 40 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF) / Optional 38 / 33 / 31 : at shipment / 42 / 38 / 33 : using jumper cable 56 Electronic Expansion Valve 19.6 3,760 2,900 (7.0) 230 (7.0) 208

Maximum overcurrent protection FEATURES Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Package dimensions Height Width Depth Net weight Shipping weight Shipping volume Narrow pipe Wide pipe ft. ft. ft. Indoor - Hi / Me / Lo Outdoor - Hi

Horizontal / Vertical dB - A dB - A

(m) (m) (m)

165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 3 / 8 (9.52) 3 / 4 (19.05) Indoor unit Outdoor unit (310) (1,480) (630) (358) (1,671) (783) (47) (52) (0.468) 48-5/8 37-1/32 13-3/8 52-7/32 40 16-3/8 203 227 19.8 (1,235) (940) (340) (1,326) (1,016) (416) (92) (103) (0.56) 12-7/32 58-9/32 24-13/16 14-3/32 65-25/32 30-13/16 104 115 16.5

in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) ibs. (kg) lbs. (kg) cu.ft. (m3)

Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I-9

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 10.3 2,300 10.9 2,220 10.0 230 22,000 7.1 21,000 6.8

KH2442 CH2442 230 - 208 V / 1 Phase / 60 Hz Heating 25,000 16,000 540 / 460 / 380 10.0 208 187 - 253 11.3 2,500 2,100 25 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-BH80UA. WL (72-hour ON / OFF) Manual / Automatic Washable, easy access 45 / 42 / 40 53 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 1 / 4 (6.35) 3 / 4 (19.05) Indoor unit Outdoor unit (370) (1,250) (210) (462) (1,339) (263) (18) (23) (0.163) 28-15/16 37-1/32 13-3/8 32-17/32 40 16-3/8 157 170 12.3 (735) (940) (340) (826) (1,016) (416) (71) (77) (0.349) 14-9/16 49-7/32 8-9/32 18-3/16 52-23/32 10-11/32 40 51 5.8 12.2 2,430 2,070 (7.0) 230 (7.0) 208 24,300 15,300

Maximum overcurrent protection FEATURES Controls

Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control Indoor - Hi / Me / Lo Outdoor - Hi dB - A dB - A Horizontal / Vertical

REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Indoor grille dimensions Height Width Depth Net weight Shipping weight Shipping volume in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) lbs. (kg) cu.ft. (m3) Narrow pipe Wide pipe

in. (mm) in. (mm)

DATA SUBJECT TO CHANGE WITHOUT NOTICE Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

I - 10

SM830082

1. Specifications

1-1 Unit Specifications

MODEL No. POWER SOURCE PERFORMANCE Capacity* Moisture removal (High) Air circulation (H / M / L) S.E.E.R. (H.S.P.F.) ELECTRICAL RATINGS Voltage rating Available voltage range Running amperes Power input*

Indoor Unit Outdoor Unit Cooling (17F)** 230 V BTU / h Pints / h cu.ft. / min. BTU / Wh VAC VAC A W (17F)** A 14.9 3,290 15.5 3,120 10.3 230 33,000 10.6 32,000 10.6

KH3642 CH3642 230 - 208 V / 1 Phase / 60 Hz Heating 40,000 25,000 (7.6) 230 187 - 253 17.8 3,860 3,000 40 Microprocessor Built-in 0F 3 and Automatic control / 3 (Auto) RCS-SH80UG (72-hour ON / OFF) RCS-BH80UA. WL (72-hour ON / OFF) Manual / Automatic Washable, easy access 48 / 44 / 40 56 Electronic Expansion Control Valve ft. ft. ft. (m) (m) (m) 165 (50) 100 (30) Outdoor unit is higher than indoor unit: 165 (50) Outdoor unit is lower than indoor unit: 100 (30) 3 / 8 (9.52) 3 / 4 (19.05) Indoor unit Outdoor unit (370) (1,500) (240) (462) (1,589) (295) (33) (41) (0.217) 48-5/8 37-1/32 13-3/8 52-7/32 40 16-3/8 203 227 19.8 (1,235) (940) (340) (1,326) (1,016) (416) (92) (103) (0.56) 14-9/16 59-1/16 9-7/16 18-3/16 62-9/16 11-5/8 73 90 7.7 19.1 3,810 2,900 (7.6) 208 39,000 24,000

830 / 710 / 590 10.5 208

Maximum overcurrent protection FEATURES Controls Low ambient control Fan speeds Indoor / Outdoor Optional Wired Remote Controller (Timer) Optional Wireless Remote Controller (Timer) Air deflection Air filter Operation sound Refrigerant control REFRIGERANT PIPING Limit of piping length Limit of piping length at shipment Limit of elevation difference between the two units Refrigerant piping Flare type DIMENSIONS & WEIGHT Unit dimensions Height Width Depth Indoor grille dimensions Height Width Depth Net weight Shipping weight Shipping volume Narrow pipe Wide pipe Indoor - Hi / Me / Lo Outdoor - Hi

Horizontal / Vertical dB - A dB - A

in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) lbs. (kg) cu.ft. (m3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE Cooling : Rating conditions (*) : Room temperature 80 F DB / 67 F WB, Ambient temperature 95 F DB / 75 F WB Heating : Rating conditions (*) : Room temperature 70 F DB / 60 F WB, Ambient temperature 47 F DB / 43 F WB Low temp conditions (**) : Room temperature 70 F DB / 60 F WB, Ambient temperature 17 F DB / 15 F WB

SM830082

I - 11

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT - ORG : 170.3 : : 18.1 43.2 SFG6X - 41D6P 230 - 208 V / 1 phase / 60 Hz 6 464 40 , , , ORG - YEL WHT - PNK YEL - BLK : : : 43.2 83.5 60.2 in. (mm) XH2442 230 - 208 VAC / 1 phase / 60 Hz RCS - SH80UA, WL CR - TH2442 250 VAC, 3 A Turbo (117-7/16 (443))

Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil DKV - MOZS726E ORG - GRY RED - GRY Valve body Heat exchanger Coil Rows Fins per inch Face area ft.
2

F F F

266

14.4

174.2 27 440 V , 4.5 F

VAC,

Coil resistance (at 20C)

: :

46 46

, ,

YEL - GRY BLK - GRY

: :

46 46

IKV - 24D18

Aluminum plate fin / Copper tube 2 14.9 (m )


2

3.69 (0.343)

Panel Model No. Auto louver motor Auto louver motor Rated Coil resistance (Ambient temperature 77 F) V, W, rpm PNR - XH2442 MT8 - 3C 240 VAC , 3 W , 3 rpm 16.430 8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 12

SM830082

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil Coil resistance (at 20C) ORG - GRY RED - GRY Valve body Heat exchanger Coil Rows Fins per inch Face area Panel Model No. Auto louver motor Auto louver motor Rated Coil resistance (Ambient temperature 77 F) V, W, rpm PNR - XH3642 MT8 - 3C 240 VAC , 3 W , 3 rpm 16.430 8 % ft.
2

XH3642 230 - 208 VAC / 1 phase / 60 Hz RCS - SH80UA, WL CR - TH2442 250 VAC, 3 A in. (mm) Turbo (117-7/16 (443))

SFG6X - 81A6P 230 - 208 V / 1 phase / 60 Hz 6 467 60 : : : 75.1 6.7 20.6 , , , ORG - YEL VLT - PNK : : : 27.4 42.7 58.0

- ORG

YEL - BLK

F F F

266

14.4

174.2 27 440 V , 5 F

VAC,

EKV - MOZS742E : : 46 46 , , YEL - GRY BLK - GRY : : 46 46

HKV - 30D27

Aluminum plate fin / Copper tube 2 14.9 (m )


2

8.20 (0.762)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 13

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT - ORG : : : 75.1 6.7 20.6 SFG6X - 81A6P 230 - 208 V / 1 phase / 60 Hz 6 506 60 , , , ORG - YEL VLT - PNK : : : 27.4 42.7 58.0 in. (mm) XH4242 230 - 208 VAC / 1 phase / 60 Hz RCS - SH80UA, WL CR - TH2442 250 VAC, 3 A Turbo (117-7/16 (443))

YEL - BLK

Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil EKV - MOZS742E ORG - GRY RED - GRY Valve body Heat exchanger Coil Rows Fins per inch Face area ft.
2

F F F

266

14.4

174.2 27 440 V , 6 F

VAC,

Coil resistance (at 20C)

: :

46 46

, ,

YEL - GRY BLK - GRY

: :

46 46

HKV - 30D27

Aluminum plate fin / Copper tube 2 14.9 (m )


2

8.20 (0.762)

Panel Model No. Auto louver motor Auto louver motor Rated Coil resistance (Ambient temperature 77 F) V, W, rpm PNR - XH3642 MT8 - 3C 240 VAC , 3 W , 3 rpm 16.430 8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 14

SM830082

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT Safety device Operating temperature Open Close Run capacitor Electronic refrigerant control valve Solenoid control model Coil resistance (Ambient temperature 68 F) Solenoid control valve model Heat exchanger Coil Rows Fins per inch Face area Auto louver motor Model No. Auto louver motor Rated Coil resistance (Ambient temperature 77 F) V, W, rpm MT8 - 3C 240 VAC , 3 W , 3 rpm 16,430 8 % ft.
2

TH2442 230 - 208 V / 1 phase / 60 Hz RCS - SH80UA, WL CR - TH2442 250 V, 3 A in. (mm) Centrifugal (4 ... 5-1/8(130))

SR4X - 51A6P 230 - 208 V / 1 phase / 60 Hz 1,179 31 : 111.0 : : 35.4 13.4 , , , ORG - YEL BLK - PNK YEL - BLK : : 16.7 23.9

- ORG

: 136.6

F F F

266

14.4

174.2 27 440 V , 1.5 F

VAC,

DKV - MOZS582E0 ORG - GRY RED - GRY : : 46 46 , , YEL - GRY BLK - GRY : : 46 46

IKV - 24D18

Aluminum plate fin / Copper tube 3 14.9 (m )


2

1.81 (0.168)

3
DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 15

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT - ORG : : : 61.05 KFG4X - 101C6P 230 - 208 V / 1 phase / 60 Hz 4 ... 1,040 100 , ORG - YEL YEL - BLK BLK - PNK : : : 13.23 19.25 10.81 in. (mm) TH3642 230 - 208 V / 1 phase / 60 Hz RCS - SH80UA, WL CR - TH2442 250 V, 3 A Centrifugal (4 ... 5-29/32(150))

9.955 , 9.576 ,

Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil EKV - MOZS584E0 ORG - GRY RED - GRY : : 46 46 , , YEL - GRY BLK - GRY : : 46 46 VAC, F F F 266 14.4 174.2 27 440 V , 4 F

Coil resistance (Ambient temperature 68 F) Valve body Heat exchanger Coil Rows Fins per inch Face area ft.
2

HKV - 30D24

Aluminum plate fin / Copper tube 3 14.9 (m )


2

3.51 (0.326)

Auto louver motor Model No. Auto louver motor Rated Coil resistance (Ambient temperature 77 F) V, W, rpm MT8 - 3C 240 VAC , 3 W , 3 rpm 16,430 8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 16

SM830082

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil Coil resistance (Ambient temperature 68 F) Valve body Heat exchanger Coil Rows Fins per inch Face area Auto louver motor Model No. Auto louver motor Rated Coil resistance (Ambient temperature 77 F) V, W, rpm MT8 - 3C 240 VAC , 3 W , 3 rpm 16,430 8 % ft.
2

TH4242 230 - 208 V / 1 phase / 60 Hz RCS - SH80UA, WL CR - TH2442 250 V, 3 A in. (mm) Centrifugal (4 ... 5-29/32(150))

KFG4X - 101C6P 230 - 208 V / 1 phase / 60 Hz 4 ... 1,099 100 : : : 61.05 , ORG - YEL YEL - BLK BLK - PNK : : : 13.23 19.25 10.81

9.955 , 9.576 ,

- ORG

F F F

266

14.4

174.2 27 440 V , 5 F

VAC,

EKV - MOZS584E0 ORG - GRY RED - GRY : : 46 46 , , YEL - GRY BLK - GRY : : 46 46

HKV - 30D27

Aluminum plate fin / Copper tube 3 14.9 (m )


2

3.51 (0.326)

3
DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 17

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT - ORG : : : 74.7 19.1 10.5 KFG4X - 71B6P 230 - 208 V / 1 phase / 60 Hz 4 ... 920 100 , , , ORG - YEL YEL - BLK BLK - PNK : : : 9.59 10.52 21.72 in. (mm) UH2442 230 - 208 V / 1 phase / 60 Hz RCS - BH80UA, WL CR - TH2442 250 V, 3 A Centrifugal (4 ... 5-29/32(150))

Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil DKV - MOZS697E0 ORG - GRY RED - GRY : : 46 46 , , YEL - GRY BLK - GRY : : 46 46 VAC, F F F 266 14.4 174.2 27 440 V , 5 F

Coil resistance (Ambient temperature 68 F) Valve body Heat exchanger Coil Rows Fins per inch Face area ft.
2

IKV - 24D12

Aluminum plate fin / Copper tube 3 14.9 (m )


2

2.03 (0.189)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 18

SM830082

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan (Number diameter) Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil Coil resistance (Ambient temperature 68 F) Valve body Heat exchanger Coil Rows Fins per inch Face area ft.
2

UH3642 230 - 208 V / 1 phase / 60 Hz RCS - BH80UA, WL CR - TH2442 250 V, 3 A in. (mm) Centrifugal (4 ... 5-29/32(150))

KFG4X - 141A6P 230 - 208 V / 1 phase / 60 Hz 4 ... 940 100 : : : 39.9 6.91 11.4 , , , ORG - YEL YEL - BLK BLK - PNK : : : 9.37 8.86 14.3

- ORG

F F F

266

14.4

174.2 27 440 V , 5 F

VAC,

DKV - MOZS698E0 ORG - GRY RED - GRY : : 46 46 , , YEL - GRY BLK - GRY : : 46 46

HKV - 30D27

Aluminum plate fin / Copper tube 3 12.7 (m )


2

3.32 (0.308)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 19

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Fan Number ... Dia. and length Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W BRW - WHT WHT - VLT VLT Safety device Operating temperature Open Close Run capacitor Electronic refrigerant control valve VAC, F F F 248 171 9 27 - ORG : 197.2 : : 41.4 22.2 UF4Q - 31A6P 230 - 208 V / 1 phase / 60 Hz 4 ... 1,276 30 , , , ORG - YEL YEL - PNK : : 59.1 48.8 in. (mm) KH2442 230 - 208 V / 1 phase / 60 Hz RCS - BH80UA, WL CR - TH2442 250 V, 3 A Cross-flow 1 ... O.D. 4-1/3 (110), L39 (990)

440 V , 1.8 F

Solenoid control model Coil resistance (Ambient temperature 68 F) Solenoid control valve model Heat exchanger Coil Rows ORG - GRY RED - GRY : :

DKV - MOZS582E0 46 46 , , YEL - GRY BLK - GRY : : 46 46

IKV - 24D11

Aluminum plate fin / Copper tube 3 12.7 ft.2 (m2) 2.57 (0.24)

Face area Louver Motor Model Rating No. of pole rpm Output

M2EA24ZA01 208 to 230 V, 60 Hz 83 W k 2.5 16.45 8 %

Coil resistance (Ambient temperature 68 F)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 20

SM830082

1. Specifications

1-2 Major Component Specifications (A) Indoor Unit


MODEL No. Source Remote controller (Option) Controller P. C. B Ass'y Control circuit fuse Switch Ass'y Fan Number ... Dia. and length Fan motor Model Source No. of pole r.p.m. (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) rpm W GRY - WHT WHT - VLT VLT Safety device Operating temperature Open Close Run capacitor Electronic expansion valve Coil Coil resistance (Ambient temperature 68 F) Valve body Heat exchanger Coil Rows Fins per inch Face area Louver Motor Model Rating No. of pole rpm Output Coil resistance (Ambient temperature 68 F) W k M2EA24ZA01 208 to 230 V, 60 Hz 83 2.5 16.45 8 % ft.
2

KH3642 230 - 208 V / 1 phase / 60 Hz RCS - BH80UA, WL CR - TH2442 250 V, 3 A SW - KHS2432 Cross-flow in. (mm) 1 ... O.D. 4-13/18 (120), L46 (1,170)

SFG4Q - 41B6P 230 - 208 V / 1 phase / 60 Hz 4 ... 1,273 50 : 122.3 : : 15.98 11.93 , , , 14.4 ORG - YEL YEL - PNK : : 23.03 9.272

- ORG

F F F

266

174.2 26 440 V , 4 F

VAC,

EKV - MOZS557E0 ORG - GRY RED - GRY : : 46 46 , , YEL - GRY BLK - GRY : : 46 46

HKV - 30D26

Aluminum plate fin / Copper tube 3 12.7 (m )


2

3.23 (0.3)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 21

1. Specifications

1-2 Major Component Specifications (B) Outdoor Unit


MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model Source Nominal output Compressor oil Coil resistance (Ambient temperature 77 F) Safety device Overload relay models Operating temperature Open Close F F A VAC, VAC, lbs. F W (kg)
+ 426.6 +

CH2442 230 - 208 VAC / 1 phase / 60 Hz CR - CH2442 (Microprocessor) 250 VAC, 3 A Rotary (Hermetic) C - 2R160H6T 230 - 208 VAC / 1 phase / 60 Hz W cc 1,700 800 C R : 0.885 , C S : 1.773 Internal type 297 9 198 20 400 VAC, 40 F 230 VAC, 30 W R22 : 6.17 (2.8) ACB - 1UB11 OFF lb/in (kg/cm ) ON lb/in2 (kg/cm2)
2 2

Operating ampere (at 77 F) Run capacitor Crank case heater Refrigerant amount charged at shipment High pressure switch Set pressure

28.44 7.11

(30 +

+ 2.0 0.5

341.3 28.44 (24 2.0) Propeller

Fan Number...diameter Fan speeds Fan motor Model Source in. (mm)

1 ... 18 - 3/32 (460) 2 (AUTO)

KFC6T - 91D6P 230 - 208 VAC / 1 phase / 60 Hz 6 ... 879 W 110 BRN WHT : 67.14 , VLT YEL : 11.42 WHT VLT : 64.85 , YEL PNK : 10.60 Internal type Open Close F F F 248 9 171 27 440 VAC, 4 F

No. of pole ..... rpm (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) Safety device Operating temperature

Run capacitor Heat exchange Coil Rows ..... Fins per inch Face area

VAC,

Aluminum plate fin / Copper tube 2 ... 14.1 ft.


2

(m )

6.78 (0.63)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 22

SM830082

1. Specifications

1-2 Major Component Specifications (B) Outdoor Unit


MODEL No. Source Controller P.C.B. Ass'y Control circuit fuse Compressor Model Source Nominal output Compressor oil Coil resistance (Ambient temperature 77 F) Safety device Overload relay models Operating temperature Operating ampere (at 77 F) Run capacitor Crank case heater Refrigerant amount charged at shipment High pressure switch Set pressure OFF lb/in (kg/cm ) ON lb/in2 (kg/cm2) Fan Number...diameter Fan speeds Fan motor Model Source No. of pole ..... rpm (230 V, High) Nominal output Coil resistance (Ambient temperature 68 F) Safety device Operating temperature Open Close Run capacitor Heat exchange Coil Rows ..... Fins per inch Face area ft.
2 2 2

CH3642 230 - 208 VAC / 1 phase / 60 Hz CR - CH2442 (Microprocessor) 250 V, 3 A Rotary (Hermetic) C - R221H6R 230 - 208 VAC / 1 phase / 60 Hz W cc 2,200 1,500 C R : 0.549 , C S : 1.525 Internal type Open Close F F A VAC, VAC, lbs. F W (kg)
+ 426.6 +

320 9 189 20 400 VAC, 40 F 230 VAC, 30 W R22 : 8.82 (4.0) ACB - 1UB11
28.44 7.11 + 2.0 0.5

(30 +

341.3 28.44 (24 2.0) Propeller

in.

(mm)

2 ... 18 - 3/32 (460) 2 (AUTO) KFC6T - 91D6P 2 230 - 208 V / 1 phase / 60 Hz 6 ... 879 110 2 BRN WHT : 67.14 , VLT YEL : 11.42 WHT VLT : 64.85 , YEL PNK : 10.60 Internal type 248

F F F

171 27 440 VAC, 4 F 2

VAC,

Aluminum plate fin / Copper tube 2 ... 14.1 (m )


2

11.63 (1.08)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 23

1. Specifications

1-2 Major Component Specifications (B) Outdoor Unit


MODEL No. Source Compressor Model Source Nominal output Compressor oil Coil resistance (Ambient temperature 77 F) Safety device Overload relay models Operating temperature Operating ampere (at 77 F) Run capacitor VAC, lbs. Open Close F F A F (kg) W cc CH4242 230 - 208 V / 1 phase / 60 Hz Scroll (Hermetic) ZR47KC - PFV 230 - 208 V / 1 phase / 60 Hz 4,270 1,240 R - W : 0.475 , S - W : 1.850 Internal type 320 9 189 20 400 V, 50 F R22 : 9.7 (4.4) ACB - 1UB11 OFF kg/cm
2

Refrigerant amount charged at shipment High pressure switch Set pressure

30

+ 2.0 + 0.5

ON kg/cm2 Fan Number...diameter in. (mm)

24 2.0 Propeller 1 18-3/32 (460) 2 (AUTO) KFC6T - 91D6P 2 230 - 208 V / 1 phase / 60 Hz

Fan speeds Fan motor Model Source No. of pole rpm (230 V, High) Nominal output Coil resistance rpm W BRW WHT WHT VLT F F F : :

6 879 110 2 67.14 64.85 , , VLT YEL YEL PNK : : 11.42 10.60

(Ambient temperature 68 F) Safety device Operating temperature Open Close Run capacitor Heat exchanger VAC,

248

171 27 440 V, 4 F 2

Coil Rows Fins per inch Face area ft.2 (m2)

Aluminum plate fin / Copper tube 2 12.7 11.63 (1.08)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 24

SM830082

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) : TH2, 3 Coil resistance k 14 F : 23.7 23 F : 18.8 32 F : 15.0 32 F 41 F 50 F 68 F 86 F F WHT - WHT BRN - BRN : : XH2442 ATR II224A 220 VAC, 60 Hz BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A 61.0 , 0.97 , 277 PBC - 41E - S14 , , , KTEC - 35 - S6 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , PJV - 1428AU 230 / 208 VAC, 12.5 W FS - 0218 - 102 50 W, DC 5V, 0.1 mA 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 41 F : 12.1 50 F : 9.7 59 F : 8.0 RED - RED ORG - ORG : : 1.37 3.16

Thermistor (Room sensor) : TH1 Coil resistance

Drain pump Rated Float switch MAX Rated (Contact rated) Solenoid control valve or coil Solenoid control valve Solenoid coil Synchronized Motor

IKV - 24D18 DKV - MOZS726E MT8 - 3C

SM830082

I - 25

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) : TH2, 3 Coil resistance k 14 F : 23.7 23 F : 18.8 32 F : 15.0 32 F 41 F 50 F 68 F 86 F F WHT - WHT BRN - BRN : : XH3642 ATR IIK224A 220 VAC, 60 Hz BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A 61.0 , 0.97 , 277 PBC - 41E - S14 , , , KTEC - 35 - S6 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , PJV - 1428AU 230 / 208 VAC, 12.5 W FS - 0218 - 102 50 W, DC 5V, 0.1 mA 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 41 F : 12.1 50 F : 9.7 59 F : 8.0 RED - RED ORG - ORG : : 1.37 3.16

Thermistor (Room sensor) : TH1 Coil resistance

1
Drain pump Rated Float switch MAX Rated (Contact rated)

Solenoid control valve or coil Solenoid control valve Solenoid coil Synchronized Motor HKV - 30D27 EKV - MOZS742E MT8 - 3C

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 26

SM830082

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) : TH2, 3 Coil resistance k 14 F : 23.7 23 F : 18.8 32 F : 15.0 32 F 41 F 50 F 68 F 86 F F WHT - WHT BRN - BRN : : XH4242 ATR IIK224A 220 VAC, 60 Hz BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A 61.0 , 0.97 , 277 PBC - 41E - S14 , , , KTEC - 35 - S6 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , PJV - 1428AU 230 / 208 VAC, 12.5 W FS - 0218 - 102 50 W, DC 5V, 0.1 mA 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 41 F : 12.1 50 F : 9.7 59 F : 8.0 RED - RED ORG - ORG : : 1.37 3.16

Thermistor (Room sensor) : TH1 Coil resistance

Drain pump Rated Float switch MAX Rated (Contact rated) Solenoid control valve or coil Solenoid control valve Solenoid coil Synchronized Motor

HKV - 30D27 EKV - MOZS742E MT8 - 3C

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 27

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : : TH2442 ATR IIK244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A 48.0 , 0.45 , 277 PBC - 41E - S14 , , , , , PBC - 41E - S14 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor)

Coil resistance

Electronic expansion valve Valve body Coil IKV - 24D18 EKV - MOZS582E0 MT8 - 3C

Synchronized Motor

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 28

SM830082

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : : TH3642 ATR IIK244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.55 A 48.0 , 0.45 , 277 PBC - 41E - S14 , , , , , PBC - 41E - S42 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor) Coil resistance

Electronic expansion valve Valve body Coil Synchronized Motor HKV - 30D24 EKV - MOZS584E0 MT8 - 3C

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 29

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : : TH4242 ATR IIK244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A 48.0 , 0.45 , 277 PBC - 41E - S14 , , , , , KTEC - 35 - S6 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor)

Coil resistance

Electronic expansion valve Valve body Coil HKV - 30D27 EKV - MOZS584E0 MT8 - 3C

Synchronized Motor

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 30

SM830082

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : : UH2442 ATR IIK244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A 48.0 , 0.45 , 277 PBC - 41E - S36 , , , , , KTEC - 35 - S42 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor) Coil resistance

Electronic expansion valve Valve body Coil HKV - 30D16 EKV - MOZS559E0

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 31

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : 48.0 : 0.45 UH3642 ATR IIK244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A , , 277 PBC - 41E - S36 , , , , , KTEC - 35 - S85 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor)

Coil resistance

Electronic expansion valve Valve body Coil HKV - 30D16 EKV - MOZS559E0

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 32

SM830082

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : : KH2442 ATR IIK244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A 48.0 , 0.45 , 277 PBC - 41E - S4 , , , , , KTEC - 35 - S6 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor) Coil resistance

Solenoid control valve or coil Solenoid control valve Solenoid coil Synchronized Motor IKV - 24D11 DKV - MOZS582E0 M2EA24ZA01

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 33

1. Specifications

1-3 Other Component Specifications (A) Indoor Unit


MODEL No. Power Transformer Rated Primary Secondary Capacity Coil resistance (Ambient temprature 77 F) Thermistor cut off temperature Thermistor (Coil sensor) Coil resistance k 14 F 23 F 32 F 41 F 50 F 32 F 41 F 50 F 68 F 86 F : : : : : 23.7 18.8 15.0 12.1 9.7 F WHT - WHT BRN - BRN : : KH3642 ATR II244B AC 220 V, 60 Hz BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A 48.0 , 0.45 , 277 PBC - 41E - S4 , , , , , KTEC - 35 - S6 k : : : : : 16.5 12.8 10.0 6.3 4.0 , , , , , 104 F 113 F 122 F 131 F : : : : 2.7 2.2 1.8 1.5 59 F 68 F 86 F 104 F 113 F : : : : : 8.0 6.5 4.4 3.1 2.6 RED - RED ORG - ORG : : 0.89 2.05

Thermistor (Room or coil sensor)

Coil resistance

Electronic expansion valve Valve body Coil HKV - 30D24 EKV - MOZS557E0 SW - KHS2432 M2EA24ZA01

Switch Assys Synchronized Motor

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 34

SM830082

1. Specifications

1-3 Other Component Specifications (B) Outdoor Unit


MODEL No. Compressor Motor Magnetic Contactor Coil rated Coil resistance (at 77 F) Contact rated (Main) Contact rated (Auxiliary) Power Relay Coil rated Coil resistance (at 77 F) Contact rated Power Transformer Rated Primary Secondary Capacity Coil resistance (at 73 F ) Thermal cut off temperature Thermistor (Coil sensor) : TH6, 7 Coil resistance k F PBC - 41E - S4 14 F 23 F 32 F 41 F : : : : 23.7 18.8 15.0 12.1 WHT WHT : 395.5 220 VAC, 60 Hz 14 V, 0.4 A 5.6 VA , 266 , , , , , PTC - 51H - S1 140 F 158 F 167 F 176 F 185 F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 F 212 F 230 F 248 F 266 F : : : : : 5.1 3.8 2.8 2.2 1.7 PBC - 41E - S26 50 F 68 F 86 F 104 F 113 F : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.19 k CH2442 FC - 1UL 240 VAC, 60 Hz 580 15 % 230 VAC, 20 A 230 VAC, 3 A HH62S 240 VAC, 60 Hz 17.2 220 VAC, 5 A ATR - I65C

Thermistor (Comp. discharge gas sensor) : TH8 Coil resistance k

Solenoid control valve or coil Solenoid control valve Solenoid coil Thermistor (PTC) Rated Max. voltage Max. ampere Resistance (at 77 F) 400 VAC 11.5 A 100 20 %
+ 30

V 389100 LB 59005 TDK 101YV

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 35

1. Specifications

1-3 Other Component Specifications (B) Outdoor Unit


MODEL No. Compressor Motor Magnetic Contactor Coil rated Coil resistance (at 68 F) Contact rated (Main) Contact rated (Auxiliary) Power Relay Coil rated Coil resistance (at 77 F) Contact rated Power Transformer Rated Primary Secondary 220 VAC, 60 Hz 14 V, 0.4 A 5.6 VA F PBC - 41E - S4 k 14 F 23 F 32 F 41 F : : : : 23.7 18.8 15.0 12.1 WHT WHT : 395.5 , 266 , , , , , PTC - 51H - S1 140 F 158 F 167 F 176 F 185 F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 F 212 F 230 F 248 F 266 F : : : : : 5.1 3.8 2.8 2.2 1.7 PBC - 41E - S36 50 F 68 F 86 F 104 F 113 F : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.19 k CH3642 FC - 1SUL 240 VAC, 60 Hz 588 10 % 240 VAC, 26 A 240 VAC, 3 A HH62S 240 VAC, 60 Hz 17.2 220 VAC, 5 A ATR - I65C

Capacity Coil resistance (at 73 F ) Thermal cut off temperature Thermistor (Coil sensor) : TH6, 7 Coil resistance

2
Thermistor (Comp. discharge gas sensor) : TH8 Coil resistance k

Solenoid control valve or coil Solenoid control valve Solenoid coil Thermistor (PTC) Rated Max. voltage Max. ampere 400 VAC 11.5 A 100 20 %
+ 30

V 389100 LB 59005 TDK 101YV

Resistance (at 77 F)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

I - 36

SM830082

1. Specifications

1-3 Other Component Specifications (B) Outdoor Unit


MODEL No. Compressor Motor Magnetic Contactor Coil rated Coil resistance (at 68 F) Contact rated (Main) Contact rated (Auxiliary) Power Relay Coil rated Coil resistance (at 77 F) Contact rated Power Transformer Rated Primary Secondary Capacity Coil resistance (at 73 F ) Thermal cut off temperature Thermistor (Coil sensor) : TH6, 7 Coil resistance k F PBC - 41E - S4 14 F 23 F 32 F 41 F : : : : 23.7 18.8 15.0 12.1 WHT WHT : 395.5 220 VAC, 60 Hz 14 V, 0.4 A 5.6 VA , 266 , , , , , PTC - 51H - S1 140 F 158 F 167 F 176 F 185 F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 F 212 F 230 F 248 F 266 F : : : : : 5.1 3.8 2.8 2.2 1.7 PBC - 41E - S36 50 F 68 F 86 F 104 F 113 F : : : : : 9.7 6.5 4.4 3.1 2.6 BRN BRN : 2.19 k CH4242 FC - 2SUL 240 VAC, 60 Hz 350 10 % 240 VAC, 35 A 240 VAC, 3 A HH62S 240 VAC, 60 Hz 17.2 220 VAC, 5 A ATR - I65C

Thermistor (Comp. discharge gas sensor) : TH8 Coil resistance k

Solenoid control valve or coil Solenoid control valve Solenoid coil Thermistor (PTC) Rated Max. voltage Max. ampere Resistance (at 77 F) 400 VAC 11.5 A 100 20 %
+ 30

V 389100 LB 59005 TDK 101YV

DATA SUBJECT TO CHANGE WITHOUT NOTICE

SM830082

I - 37

1. Specifications

1-4 Dimensional data Indoor unit : 4-Way Air Discharge Semi-concealed Type 24 Type
10-9/32 8-11/16 4-7/8 Min. 2-15/32 13-11/32 3-15/16 Min. 19/32 3

X-view

4-7/8

11-1/2 9-1/8

2-5/16 6-3/16

1
32-9/32 (Ceiling opening) 29-13/16 (Suspention bolt pitch) 12-1/8 4-7/8 1-7/8 1

7-5/32 1-3/16

33-27/32 19-11/16

3-15/16 4-7/8 8-11/16 15/32 15/32

2
X

32-9/32 (Ceiling opening) 22-9/32 (Suspention bolt pitch) 14-27/32

14-1/2

15/32 33-27/32 19-11/16 30-9/16

Grille center

-1
4

3/
1/

32
8

2-3/8

Dimension : inch
ho le

-3/

8-27/32

15/32

29

/32

Detail of
1917_X_S

I - 38

4-

1 /

Air intake grille Air outlet Refrigerant liquid line (3/8" : XH12, 18. 1/4" : XH24) Refrigerant gas line (1/2" : XH12. 5/8" : XH18. 3/4" : XH24) Drain connection Power supply entry (conduit size : 1/2") For discharge duct Suspention bolt mounting For fresh air intake

30-9/16

2-5/32

Detail of 9

ho

le

SM830082

1. Specifications

1-4 Dimensional data Indoor unit : 4-Way Air Discharge Semi-concealed Type 36, 42 Type
4-7/8 11-15/32 9-19/32

13-11/32

3-15/16

Min. 2-15/32 Min. 19/32 3

X-view

11-1/2 9-1/8

2-5/16 4-7/8 32-9/32 (Ceiling opening) 29-13/16 (Suspention bolt pitch) 13-5/16 4-7/8 1-7/8 6-3/16 7-5/32 1-3/16 33-27/32 19-11/16

43-11/16 (Ceiling opening) 33-11/16 (Suspention bolt pitch) 20-9/16

20-3/16

15/32

2
41-31/32 45-9/32 31-3/32

Grille center

3
4-7/8
-1 3/ 3 4 2

15/32

Detail of 9

2-3/8

Dimension : inch Air intake grille Air outlet Refrigerant liquid line (3/8") Refrigerant gas line (3/4") Drain connection Power supply entry (conduit size : 1/2") For discharge duct Suspention bolt mounting For fresh air intake

30-9/16 7-3/32

2-5/32

Detail of

15/32

-3/

9-13/16

29

/32

I - 39

4-

1 /

4-

1 /

ho

le

9-19/32

15/32

ho

le

5
1918_X_S

SM830082

1. Specifications

1-4 Dimensional data Indoor unit : Ceiling Mounted Type 24 Type


6-3/32 5-25/32 3-3/32 3-15/16 1-3/8 12-7/32 2-17/32 5-9/32 11-1/32 5-25/32

3-3/8 11-1/32

3-15/16

5-3/4 4-9/16 3-9/32

5-9/16

Holes in the rear side (View from front) 1-3/32

Hole for wall-through piping (View from front)

6-5/16

(Suspension bolt hole pitch)

12-19/32

5-3/16

2-25/32

48-7/16 (Suspension bolt hole pitch)

1-3/8

50-13/32

6-5/16

26-3/8 7-15/32 8-7/16 9-7/8 5-25/32


1919_THS_I

2
2 ft. or more 9-7/8 Air intake 51-3/16 Front (Service space) (Service space) 3-3/4 10 Air outlet or more 10 or more

3
3-1/2 4-1/16 5-25/32

7-7/32

Dimension : inch Drain connection Drain connection for left side Refrigerant liquid line (1/4") Flare connection Refrigerant gas line (3/4") Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (3-15/16" hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2") Infrared rays receiver for wireless remote controller Cutting position for fresh air intake

4-23/32

I - 40

SM830082

1. Specifications

1-4 Dimensional data Indoor unit : Ceiling Mounted Type 36, 42 Type
6-3/32 7-31/32 12-7/32

7-3/4 5-15/16

1-31/32

4-1/2 7-1/4

11-1/32

7-3/4

3-3/8 11-1/32

3-15/16

5-3/4 4-3/4 3-5/32

5-9/16

Holes in the rear side (View from front)

Hole for wall-through piping (View from front)

6-5/16

(Suspension bolt hole pitch)

12-19/32

5-3/16

2-25/32

6-5/16

1-3/32

6-11/16

1
59-1/4 (Suspension bolt hole pitch) 1-3/8

61-7/32

26-3/8

5-1/2

2 ft. or more

9-7/8 Air intake

62 Front

8-7/16 9-7/8

(Service space)

(Service space)

7-3/4

10 Air outlet or more

10 or more

9-7/16

3
3-1/2 4-1/16 5-25/32 7-7/32

Dimension : inch Drain connection Drain connection for left side Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (3/4") Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (3-15/16" hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2") Infrared rays receiver for wireless remote controller Cutting position for fresh air intake
1920_TS_I

SM830082

I - 41

1. Specifications

1-4 Dimensional data Indoor unit : Concealed Duct Type 24 Type


10
31/32 6-7/8 1-3/8 5-1/8

7-15/32

12-7/32

8-9/32

31/32

6-5/16 1-3/16 24-13/16 2-3/4

31/32 3-11/32

13/32 31/32

(5-29/32)

1-9/16

1
11
1-7/32 3/4

Inspection access (17-23/32 17-23/32) (Field supply)

2-3/4

11-7/32

4-17/32
2-15/16 2-9/16

10-1/4 (Air outlet duct flange)

15/16

16-1/8 (Hole)

42-17/32 (Suspension bolt pitch)

37-7/8 (Air outlet duct flange)

35-7/16

39-3/8

1-7/32

22-27/32 (Suspension bolt pitch)

31/32

Dimension : inch

4
3-17/32

7-9/32

9 10 11

11-13/32

11-12/32

10-23/32

7-3/32

Refrigerant liquid line 3/8 (narrow tube) (Use the tube connector) Refrigerant gas line 5/8 (wide tube) Upper drain port (O.D. 1-1/4) Bottom drain port (O.D. 1-1/32) Suspension lug Power supply inlet (conduit size 1/2") Fresh air intake port (5-29/32) Flange for the flexible air outlet duct (7-7/8) Tube cover Electrical component box Flange for the air intake duct (option or field supply)
1914_U_I

I - 42

SM830082

1. Specifications

1-4 Dimensional data Indoor unit : Concealed Duct Type 36 Type


10
31/32 6-7/8 1-3/8 5-1/8 6-5/16 1-3/16 24-13/16 2-3/4 3-11/32 31/32 Inspection access (17-23/32 17-23/32) (Field supply) 2-3/4 7-15/32

12-7/32

31/32

8-9/32

13/32 31/32

11-7/32

(5-29/32)

1-9/16

1
4-17/32 2-15/16 2-9/16 12-7/32

11

1-7/32

3/4

10-1/4 (Air outlet duct flange)

15/16

9-1/16

18-1/8 (Hole)

61-13/32 (Suspension bolt pitch)

56-25/32 (Air outlet duct flange)

9-1/16 P 6 = 54-11/32

58-9/32

13-3/16

13-3/16

13-3/16

1-7/32

4
22-27/32 (Suspension bolt pitch) 31/32

Dimension : inch

7-9/32

9 10 11

Refrigerant liquid line 3/8 (narrow tube) Refrigerant gas line 3/4 (wide tube) Upper drain port (O.D. 1-1/4) Bottom drain port (O.D. 1-1/32) Suspension lug Power supply inlet (conduit size 1/2") Fresh air intake port (5-29/32) Flange for the flexible air outlet duct (7-7/8) Tube cover Electrical component box Flange for the air intake duct (option or field supply)
1915_U_I

3-17/32

SM830082

I - 43

1. Specifications

1-4 Dimensional data Indoor unit : Concealed Duct Type


2-1/8 (Hole)

s Flange for the air intake duct (Field supply) : For Concealed Duct Type
Thickness more than T1/16 inch

13/32 8-9/32 31/32 12-1/32 31/32 10-1/4 (O.D.) 1/4 (Hole) 13/32 1-7/32 29/32 23/32 B (O.D.) 1-25/32 7-7/8 1-25/32

1
C-1/8 (Hole) D

2
E H A
2118_U_I

3
G

11/32

5/16

31/32

5
24 type 36 type

(mm) H I 15/32 5/8 25/32 SM830082

A 39-9/32

B 37-7/8

C 5/32 1/4 9/32

D 7-7/8 7-3/32 9-1/16

E 3 7-7/8P = 23-5/8 5 7-3/32 = 35-7/16

F 6-11/16

12, 18 type 27-15/32 26-1/16 58-3/16 56-25/32

13-3/4 9-7/16

4-23/32 9-21/32 (9-21/32 1) 9-27/32

6 9-1/16 = 54-11/32 4-23/32 19-9/32 (9-21/32 2)

I - 44

1. Specifications

1-4 Dimensional data Indoor unit : Wall Mounted Type 24 Type

14-9/16

2-3/4 49-7/32 8-9/32

2-1/4

4-5/32

Refrigerant gas line (wide tubing: 3/4) Refrigerant liquid line (narrow tubing: 1/4) Drain hose OD 1-1/4 Dimension : inch
1911_X_S

SM830082

I - 45

1. Specifications

1-4 Dimensional data Indoor unit : Wall Mounted Type 36 Type

14-9/16

2-3/4 59-1/16 9-7/16

1
1-49/64
2-9/16 Refrigerant gas line (wide tubing 3/4") Refrigerant liquid line (narrow tubing 3/8") Drain hose OD 1-1/4 Dimension : inch
1912_X_S

I - 46

SM830082

1. Specifications

1-4 Dimensional Data (B) Outdoor Unit: CH2442


6-11/16 1-31/32 26 1-31/32 4-21/64
1-3/16 13/32 14-31/32 15-3/4

13-3/8

37

1
28-15/16 12-1/16

11

2
Dimension : inch Hole for anchor bolt (4-1/2) Refrigerant tube joint (narrow tube) Flare connection 1/4 in (6.35 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
2179_THS_I

SM830082

I - 47

1. Specifications

1-4 Dimensional Data (B) Outdoor Unit: CH3642, CH4242


6-11/16 1-31/32 26 1-31/32 4-21/64

1-3/16

14-31/32
37
22-27/32

13-3/8

13/32
23-29/32

1
48-5/8

15-3/4

Dimension : inch Hole for anchor bolt (4-13) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
1581_C_S

I - 48

SM830082

1. Specifications

1-5 Refrigerant Flow Diagram Outdoor Unit: CH2442


Compressor Accumulator Accumulator Gas line service valve

Indoor Unit: 24 Type

O.D. 3/4" (19.05mm)

Gas line nipple

High pressure switch

HP 4-way valve EC Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 1/4" (6.35mm) Distributor Strainer Electronic ref.control valve M Liquid line nipple P

1
Strainer

Sub-heat exchanger Cooling Cycle Heating Cycle

2180_THS_I

2
Outdoor Unit: CH3642
Compressor Accumulator Accumulator Gas line service valve

Indoor Unit: 36 Type

O.D. 3/4" (19.05mm)

Gas line nipple

3
EC

High pressure switch

HP Muffler 4-way valve Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 3/8" (9.52mm) Distributor Strainer Electronic ref.control valve M Liquid line nipple P

Sub-heat exchanger Cooling Cycle Heating Cycle

Strainer

5
1398_THS_I

SM830082

I - 49

1. Specifications

1-5 Refrigerant Flow Diagram Outdoor Unit: CH4242


Compressor Accumulator Gas line service valve

Indoor Unit: 42 Type

O.D. 3/4" (19.05mm)

Gas line nipple

High pressure switch

HP Muffler 4-way valve EC Heat exchanger EC Heat exchanger P Distributor Liquid line service valve O.D. 3/8" (9.52mm) Distributor Strainer Electronic ref.control valve M Liquid line nipple P

1
Sub-heat exchanger Cooling Cycle Heating Cycle

Strainer

2181_THS_I

2
1-6 Operating Range
Temperature Indoor Air Intake 95 F DB, 71 F WB 67 F DB, 57 F WB 80 F DB, 67 F WB -DB / -WB Outdoor Air Intake 115 F DB 0 F DB 75 F DB, 65 F WB 17 F DB / 15 F WB

Cooling Heating

Maximum Minimum Maximum Minimum

I - 50

SM830082

1. Specifications

1-7 Cooling Capacity Indoor Unit: XH2442


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB 24,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 23,140 21,790 1.86 2.03 16,020 15,280 17,820 17,080 19,700 18,960 21,500 20,760 23,140 21,790 24,100 22,900 1.89 2.06 13,750 13,140 15,550 14,940 17,430 16,820 19,230 18,620 21,030 20,420 25,150 # 24,000 1.9 2.08 11,470 10,940 13,270 12,740 15,150 14,620 16,950 16,420 18,750 18,220 26,620 25,580 1.92 2.11 9,230 8,790 11,030 10,590 12,910 12,470 14,710 14,270 16,510 16,070 27,220 26,260 1.96 2.14 8,500 8,130 10,380 10,010 12,180 11,810 13,980 13,610 540 CFM

Outdoor Unit: CH2442

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 24,310 1.71 16,680 18,480 20,360 22,160 23,960 25,220 1.72 14,330 16,130 18,010 19,810 21,610 26,180 1.74 11,960 13,760 15,640 17,440 19,240 27,580 1.76 9,650 11,450 13,330 15,130 16,930 28,130 1.79 8,850 10,730 12,530 14,330

105 (40.6) 20,280 2.26 14,470 16,270 18,150 19,950 20,280 21,530 2.29 12,460 14,260 16,140 17,940 19,740 22,730 2.32 10,360 12,160 14,040 15,840 17,640 24,460 2.35 8,330 10,130 12,010 13,810 15,610 25,150 2.38 7,720 9,600 11,400 13,200

115 (46.1) 18,600 2.49 13,600 15,400 17,280 18,600 18,600 20,040 2.52 11,750 13,550 15,430 17,230 19,030 21,340 2.55 9,750 11,550 13,430 15,230 17,030 23,210 2.59 7,820 9,620 11,500 13,300 15,100 23,980 2.63 7,290 9,170 10,970 12,770

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

8.55

USpints/h

SM830082

I - 51

1. Specifications

Indoor Unit: XH2442


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442


23,400 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 22,560 21,250 1.92 2.09 15,570 14,840 17,280 16,560 19,080 18,350 20,790 20,060 22,510 21,250 23,490 1.94 13,390 15,110 16,900 18,610 20,330 24,520 1.96 11,220 12,930 14,720 16,440 18,150 25,950 1.98 9,070 10,790 12,580 14,300 16,010 26,540 2.01 8,360 10,150 11,870 13,580 22,320 2.12 12,790 14,510 16,300 18,010 19,730 # 23,400 2.14 10,690 12,410 14,200 15,910 17,630 24,940 2.17 8,640 10,360 12,150 13,860 15,580 25,600 2.2 8,000 9,790 11,500 13,220 510 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 23,700 1.75 16,220 17,930 19,730 21,440 23,160 24,590 1.77 13,970 15,680 17,470 19,190 20,900 25,530 1.79 11,700 13,410 15,210 16,920 18,640 26,890 1.81 9,480 11,200 12,990 14,700 16,420 27,420 1.84 8,700 10,490 12,210 13,920

105 (40.6) 19,770 2.33 14,040 15,760 17,550 19,270 19,770 20,990 2.36 12,130 13,840 15,640 17,350 19,070 22,160 2.39 10,130 11,840 13,630 15,350 17,060 23,840 2.42 8,180 9,890 11,690 13,400 15,120 24,520 2.46 7,590 9,380 11,100 12,810

115 (46.1) 18,140 2.56 13,190 14,910 16,700 18,140 18,140 19,540 2.6 11,430 13,140 14,940 16,650 18,360 20,800 2.63 9,520 11,230 13,030 14,740 16,450 22,630 2.67 7,680 9,400 11,190 12,900 14,620 23,380 2.71 7,170 8,960 10,670 12,390

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

2
71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

8.39

USpints/h

I - 52

SM830082

1. Specifications

Indoor Unit: XH3642


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642


34,500 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 33,260 31,330 2.53 2.76 24,850 23,890 28,220 27,260 31,740 30,790 33,260 31,330 33,260 31,330 34,640 32,910 2.57 2.8 20,830 20,050 24,200 23,420 27,730 26,940 31,100 30,310 34,470 32,910 36,160 # 34,500 2.59 2.83 16,820 16,130 20,190 19,500 23,710 23,020 27,080 26,390 30,450 29,760 38,260 36,780 2.62 2.87 12,800 12,240 16,170 15,610 19,690 19,130 23,060 22,500 26,430 25,870 39,120 37,740 2.66 2.91 11,820 11,350 15,340 14,870 18,710 18,240 22,080 21,610 980 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 34,950 2.32 25,700 29,070 32,590 34,950 34,950 36,260 2.34 21,580 24,950 28,480 31,850 35,220 37,640 2.36 17,450 20,820 24,340 27,710 31,080 39,640 2.39 13,330 16,700 20,220 23,590 26,960 40,430 2.43 12,270 15,800 19,170 22,540

105 (40.6) 29,150 3.06 22,840 26,210 29,150 29,150 29,150 30,950 3.11 19,170 22,540 26,060 29,430 30,950 32,670 3.14 15,380 18,750 22,270 25,640 29,010 35,160 3.19 11,630 15,000 18,520 21,890 25,260 36,160 3.23 10,810 14,330 17,700 21,070

115 (46.1) 26,740 3.36 21,700 25,070 26,740 26,740 26,740 28,810 3.42 18,230 21,600 25,130 28,500 28,810 30,670 3.45 14,570 17,940 21,470 24,840 28,210 33,360 3.5 10,960 14,330 17,860 21,230 24,600 34,470 3.55 10,250 13,770 17,140 20,510

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

10.47

USpints/h

SM830082

I - 53

1. Specifications

Indoor Unit: XH3642


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642


33,500 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 32,290 30,420 2.41 2.62 23,670 22,730 26,750 25,810 29,960 29,020 32,290 30,420 32,290 30,420 33,630 31,960 2.44 2.66 19,970 19,200 23,050 22,270 26,260 25,490 29,340 28,560 32,410 31,640 35,110 # 33,500 2.46 2.69 16,270 15,590 19,350 18,660 22,560 21,880 25,640 24,950 28,710 28,030 37,150 35,710 2.49 2.73 12,570 12,010 15,650 15,090 18,860 18,300 21,940 21,380 25,010 24,450 37,990 36,650 2.53 2.77 11,610 11,150 14,830 14,360 17,900 17,440 20,980 20,510 880 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

2
71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 33,940 2.21 24,520 27,600 30,810 33,890 33,940 35,210 2.23 20,720 23,790 27,010 30,080 33,160 36,550 2.25 16,900 19,970 23,190 26,260 29,340 38,490 2.27 13,100 16,180 19,390 22,470 25,540 39,260 2.31 12,060 15,280 18,350 21,430

105 (40.6) 28,310 2.96 21,690 24,760 27,980 28,310 28,310 30,050 3 18,330 21,400 24,620 27,690 30,050 31,720 3.04 14,840 17,920 21,130 24,210 27,280 34,140 3.08 11,410 14,490 17,700 20,780 23,850 35,110 3.13 10,610 13,830 16,900 19,980

115 (46.1) 25,960 3.3 20,560 23,630 25,960 25,960 25,960 27,970 3.35 17,400 20,470 23,690 26,760 27,970 29,780 3.38 14,050 17,120 20,340 23,410 26,490 32,390 3.43 10,750 13,830 17,040 20,120 23,190 33,470 3.48 10,060 13,270 16,350 19,420

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

10.6

USpints/h

I - 54

SM830082

1. Specifications

Indoor Unit: XH4242


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH4242


42,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 40,490 38,140 3.3 3.6 28,560 27,310 31,930 30,680 35,460 34,210 38,830 37,580 40,490 38,140 42,170 40,070 3.35 3.65 24,390 23,360 27,760 26,730 31,280 30,250 34,650 33,620 38,020 36,990 44,020 # 42,000 3.38 3.69 20,210 19,310 23,580 22,680 27,110 26,200 30,480 29,570 33,850 32,940 46,580 44,770 3.41 3.75 16,070 15,330 19,440 18,700 22,960 22,220 26,330 25,590 29,700 28,960 47,630 45,950 3.47 3.8 14,820 14,200 18,350 17,730 21,720 21,100 25,090 24,470 980 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 42,550 3.03 29,690 33,060 36,580 39,950 42,550 44,140 3.06 25,370 28,740 32,270 35,640 39,010 45,820 3.08 21,040 24,410 27,930 31,300 34,670 48,260 3.11 16,770 20,140 23,660 27,030 30,400 49,220 3.17 15,420 18,940 22,310 25,680

105 (40.6) 35,490 4.02 25,940 29,310 32,830 35,490 35,490 37,670 4.08 22,210 25,580 29,100 32,470 35,840 39,770 4.12 18,330 21,700 25,220 28,590 31,960 42,800 4.18 14,530 17,900 21,430 24,800 28,170 44,020 4.24 13,500 17,020 20,400 23,770

115 (46.1) 32,550 4.44 24,460 27,830 31,350 32,550 32,550 35,070 4.5 20,990 24,360 27,890 31,260 34,630 37,340 4.55 17,280 20,650 24,170 27,540 30,910 40,610 4.62 13,670 17,040 20,560 23,930 27,300 41,960 4.69 12,770 16,290 19,660 23,030

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

14.41

USpints/h

SM830082

I - 55

1. Specifications

Indoor Unit: XH4242


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH4242


40,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 38,560 36,320 3.18 3.46 26,960 25,750 30,040 28,820 33,250 32,040 36,330 35,110 38,560 36,320 40,160 38,160 3.22 3.51 23,110 22,120 26,190 25,190 29,400 28,410 32,480 31,480 35,550 34,560 41,920 # 40,000 3.25 3.55 19,270 18,390 22,340 21,470 25,560 24,680 28,630 27,760 31,710 30,830 44,360 42,640 3.28 3.6 15,460 14,740 18,540 17,820 21,750 21,030 24,830 24,110 27,900 27,180 45,360 43,760 3.34 3.66 14,260 13,660 17,480 16,880 20,550 19,950 23,630 23,030 880 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 40,520 2.91 28,050 31,120 34,340 37,410 40,490 42,040 2.94 24,070 27,150 30,360 33,440 36,510 43,640 2.96 20,070 23,150 26,360 29,440 32,510 45,960 3 16,140 19,220 22,430 25,510 28,580 46,880 3.05 14,840 18,060 21,130 24,210

105 (40.6) 33,800 3.92 24,420 27,490 30,710 33,780 33,800 35,880 3.98 21,010 24,080 27,300 30,370 33,450 37,880 4.02 17,440 20,520 23,730 26,810 29,880 40,760 4.08 13,970 17,050 20,260 23,340 26,410 41,920 4.14 12,980 16,200 19,270 22,350

115 (46.1) 31,000 4.38 22,990 26,060 29,280 31,000 31,000 33,400 4.45 19,830 22,900 26,120 29,190 32,270 35,560 4.49 16,430 19,500 22,720 25,790 28,870 38,680 4.56 13,140 16,210 19,430 22,500 25,580 39,960 4.62 12,270 15,490 18,560 21,640

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

13.97

USpints/h

I - 56

SM830082

1. Specifications

Indoor Unit: TH2442


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442


22,400 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 21,590 20,340 1.86 2.03 14,890 14,190 16,510 15,820 18,210 17,510 19,830 19,140 21,460 20,340 22,490 21,370 1.89 2.06 12,830 12,250 14,450 13,880 16,150 15,570 17,770 17,200 19,400 18,820 23,480 # 22,400 1.9 2.08 10,770 10,260 12,390 11,880 14,090 13,580 15,710 15,200 17,340 16,830 24,840 23,880 1.92 2.11 8,730 8,320 10,360 9,940 12,050 11,640 13,680 13,260 15,300 14,890 25,400 24,510 1.96 2.14 8,050 7,700 9,740 9,400 11,370 11,020 12,990 12,650 460 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 22,690 1.71 15,520 17,140 18,840 20,460 22,090 23,540 1.72 13,380 15,000 16,700 18,320 19,950 24,440 1.74 11,230 12,850 14,550 16,170 17,800 25,740 1.76 9,130 10,750 12,450 14,070 15,690 26,250 1.79 8,380 10,080 11,700 13,320

105 (40.6) 18,930 2.26 13,430 15,050 16,750 18,370 18,930 20,090 2.29 11,610 13,240 14,930 16,560 18,180 21,210 2.32 9,710 11,340 13,030 14,660 16,280 22,830 2.35 7,880 9,500 11,200 12,820 14,440 23,480 2.38 7,310 9,010 10,630 12,250

115 (46.1) 17,360 2.49 12,610 14,230 15,930 17,360 17,360 18,700 2.52 10,940 12,560 14,260 15,880 17,500 19,910 2.55 9,130 10,750 12,450 14,080 15,700 21,660 2.59 7,390 9,020 10,710 12,340 13,960 22,380 2.63 6,900 8,600 10,220 11,850

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

8.04

USpints/h

SM830082

I - 57

1. Specifications

Indoor Unit: TH2442


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442


21,600 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 20,820 19,610 1.92 2.09 14,220 13,530 15,690 15,000 17,230 16,540 18,700 18,010 20,170 19,480 21,690 20,610 1.94 2.12 12,320 11,750 13,800 13,220 15,330 14,760 16,800 16,230 18,280 17,700 22,640 # 21,600 1.96 2.14 10,420 9,920 11,900 11,390 13,430 12,930 14,910 14,400 16,380 15,870 23,950 23,030 1.98 2.17 8,560 8,150 10,030 9,620 11,570 11,160 13,040 12,630 14,510 14,100 24,490 23,630 2.01 2.2 7,880 7,540 9,420 9,080 10,890 10,550 12,360 12,020 410 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 21,880 1.75 14,850 16,320 17,860 19,330 20,800 22,700 1.77 12,870 14,340 15,880 17,350 18,820 23,570 1.79 10,890 12,360 13,900 15,370 16,840 24,820 1.81 8,950 10,420 11,960 13,430 14,900 25,320 1.84 8,220 9,760 11,230 12,700

105 (40.6) 18,250 2.33 12,770 14,240 15,780 17,250 18,250 19,380 2.36 11,120 12,590 14,130 15,600 17,070 20,460 2.39 9,380 10,850 12,390 13,860 15,330 22,010 2.42 7,710 9,180 10,720 12,190 13,660 22,640 2.46 7,150 8,690 10,160 11,630

115 (46.1) 16,740 2.56 11,960 13,430 14,970 16,440 16,740 18,040 2.6 10,450 11,920 13,460 14,930 16,400 19,200 2.63 8,800 10,270 11,810 13,280 14,750 20,890 2.67 7,230 8,700 10,240 11,710 13,180 21,580 2.71 6,750 8,290 9,760 11,230

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

7.91

USpints/h

I - 58

SM830082

1. Specifications

Indoor Unit: TH3642


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642


34,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 32,780 30,870 2.53 2.76 24,120 23,160 27,290 26,330 30,610 29,650 32,780 30,870 32,780 30,870 34,140 32,440 2.57 2.8 20,310 19,520 23,480 22,690 26,800 26,010 29,970 29,180 33,140 32,350 35,630 # 34,000 2.59 2.83 16,500 15,810 19,670 18,980 22,980 22,290 26,160 25,470 29,330 28,640 37,710 36,240 2.62 2.87 12,690 12,120 15,860 15,290 19,180 18,610 22,350 21,780 25,520 24,950 38,560 37,200 2.66 2.91 11,720 11,240 15,030 14,560 18,200 17,730 21,380 20,900 900 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 34,440 2.32 24,970 28,140 31,460 34,440 34,440 35,730 2.34 21,060 24,230 27,540 30,720 33,890 37,090 2.36 17,120 20,300 23,610 26,780 29,960 39,070 2.39 13,220 16,400 19,710 22,880 26,060 39,850 2.43 12,170 15,490 18,660 21,830

105 (40.6) 28,730 3.06 22,110 25,280 28,600 28,730 28,730 30,500 3.11 18,640 21,810 25,130 28,300 30,500 32,200 3.14 15,060 18,230 21,550 24,720 27,890 34,650 3.19 11,520 14,690 18,000 21,180 24,350 35,630 3.23 10,700 14,020 17,190 20,360

115 (46.1) 26,350 3.36 20,970 24,140 26,350 26,350 26,350 28,390 3.42 17,710 20,880 24,190 27,370 28,390 30,230 3.45 14,250 17,420 20,740 23,910 27,080 32,880 3.5 10,850 14,020 17,340 20,510 23,680 33,970 3.55 10,140 13,460 16,630 19,800

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

10.68

USpints/h

SM830082

I - 59

1. Specifications

Indoor Unit: TH3642


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642


33,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 31,810 29,960 2.41 2.62 22,940 21,990 25,810 24,860 28,810 27,860 31,680 29,960 31,810 29,960 33,130 31,480 2.44 2.66 19,450 18,670 22,320 21,540 25,320 24,540 28,190 27,400 31,050 30,270 34,580 # 33,000 2.46 2.69 15,960 15,280 18,830 18,140 21,830 21,140 24,700 24,010 27,560 26,880 36,600 35,180 2.49 2.73 12,490 11,930 15,360 14,790 18,350 17,790 21,220 20,660 24,090 23,530 37,420 36,100 2.53 2.77 11,530 11,060 14,530 14,060 17,390 16,920 20,260 19,790 800 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 33,430 2.21 23,800 26,660 29,660 32,530 33,430 34,680 2.23 20,200 23,070 26,070 28,930 31,800 36,000 2.25 16,590 19,460 22,460 25,320 28,190 37,920 2.27 13,020 15,890 18,890 21,750 24,620 38,680 2.31 11,990 14,980 17,850 20,720

105 (40.6) 27,890 2.96 20,950 23,820 26,810 27,890 27,890 29,600 3 17,800 20,670 23,660 26,530 29,400 31,250 3.04 14,530 17,400 20,400 23,260 26,130 33,630 3.08 11,320 14,190 17,190 20,050 22,920 34,580 3.13 10,520 13,520 16,390 19,260

115 (46.1) 25,580 3.3 19,820 22,690 25,580 25,580 25,580 27,560 3.35 16,870 19,740 22,740 25,600 27,560 29,340 3.38 13,730 16,600 19,600 22,470 25,330 31,910 3.43 10,660 13,530 16,530 19,390 22,260 32,970 3.48 9,970 12,960 15,830 18,700

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

10.82

USpints/h

I - 60

SM830082

1. Specifications

Indoor Unit: TH4242


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH4242


42,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 40,490 38,140 3.3 3.6 28,200 26,920 31,380 30,090 34,690 33,410 37,860 36,580 40,490 38,140 42,170 40,070 3.35 3.65 24,220 23,160 27,390 26,340 30,710 29,650 33,880 32,820 37,050 36,000 44,020 # 42,000 3.38 3.69 20,240 19,310 23,410 22,480 26,730 25,790 29,900 28,970 33,070 32,140 46,580 44,770 3.41 3.75 16,300 15,540 19,470 18,710 22,790 22,020 25,960 25,200 29,130 28,370 47,630 45,950 3.47 3.8 15,030 14,400 18,350 17,710 21,520 20,880 24,690 24,060 900 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 42,550 3.03 29,360 32,530 35,850 39,020 42,190 44,140 3.06 25,230 28,400 31,720 34,890 38,060 45,820 3.08 21,080 24,260 27,570 30,740 33,920 48,260 3.11 17,020 20,190 23,510 26,680 29,850 49,220 3.17 15,640 18,960 22,130 25,300

105 (40.6) 35,490 4.02 25,510 28,690 32,000 35,170 35,490 37,670 4.08 21,990 25,160 28,470 31,650 34,820 39,770 4.12 18,300 21,470 24,790 27,960 31,130 42,800 4.18 14,720 17,890 21,210 24,380 27,550 44,020 4.24 13,680 16,990 20,170 23,340

115 (46.1) 32,550 4.44 24,000 27,170 30,490 32,550 32,550 35,070 4.5 20,740 23,920 27,230 30,400 33,580 37,340 4.55 17,230 20,410 23,720 26,890 30,070 40,610 4.62 13,840 17,010 20,320 23,500 26,670 41,960 4.69 12,930 16,240 19,410 22,590

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

14.78

USpints/h

SM830082

I - 61

1. Specifications

Indoor Unit: TH4242


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH4242


40,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 38,560 36,320 3.18 3.46 26,610 25,360 29,480 28,230 32,480 31,230 35,350 34,090 38,210 36,320 40,160 38,160 3.22 3.51 22,960 21,940 25,830 24,800 28,830 27,800 31,700 30,670 34,560 33,540 41,920 # 40,000 3.25 3.55 19,320 18,410 22,190 21,280 25,190 24,280 28,050 27,150 30,920 30,010 44,360 42,640 3.28 3.6 15,730 14,990 18,600 17,850 21,590 20,850 24,460 23,720 27,330 26,590 45,360 43,760 3.34 3.66 14,510 13,890 17,500 16,880 20,370 19,750 23,240 22,620 800 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 40,520 2.91 27,740 30,610 33,600 36,470 39,340 42,040 2.94 23,960 26,820 29,820 32,690 35,560 43,640 2.96 20,150 23,020 26,010 28,880 31,750 45,960 3 16,430 19,300 22,300 25,160 28,030 46,880 3.05 15,100 18,100 20,970 23,840

105 (40.6) 33,800 4.16 23,990 26,860 29,860 32,730 33,800 35,880 4.22 20,790 23,660 26,660 29,520 32,390 37,880 4.27 17,440 20,300 23,300 26,170 29,040 40,760 4.33 14,190 17,060 20,060 22,920 25,790 41,920 4.39 13,190 16,180 19,050 21,920

115 (46.1) 31,000 4.86 22,520 25,390 28,390 31,000 31,000 33,400 4.93 19,580 22,450 25,450 28,320 31,180 35,560 4.98 16,400 19,260 22,260 25,130 28,000 38,680 5.05 13,330 16,200 19,200 22,060 24,930 39,960 5.13 12,450 15,450 18,320 21,190

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

14.34

USpints/h

I - 62

SM830082

1. Specifications

Indoor Unit: UH2442


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442


24,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 23,140 21,790 1.86 2.03 16,180 15,450 18,080 17,350 20,070 19,340 21,970 21,240 23,140 21,790 24,100 22,900 1.89 2.06 13,810 13,210 15,710 15,110 17,690 17,100 19,600 19,000 21,500 20,900 25,150 # 24,000 1.9 2.08 11,430 10,910 13,330 12,810 15,320 14,800 17,220 16,700 19,120 18,600 26,620 25,580 1.92 2.11 9,090 8,660 10,990 10,560 12,970 12,540 14,870 14,440 16,780 16,340 27,220 26,260 1.96 2.14 8,360 8,000 10,350 9,990 12,250 11,890 14,150 13,790 670 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 24,310 1.71 16,820 18,720 20,710 22,610 24,310 25,220 1.72 14,370 16,270 18,260 20,160 22,060 26,180 1.74 11,910 13,810 15,800 17,700 19,600 27,580 1.76 9,490 11,390 13,380 15,280 17,180 28,130 1.79 8,710 10,690 12,590 14,490

105 (40.6) 20,280 2.26 14,660 16,560 18,550 20,280 20,280 21,530 2.29 12,550 14,450 16,440 18,340 20,240 22,730 2.32 10,350 12,250 14,240 16,140 18,040 24,460 2.35 8,200 10,100 12,090 13,990 15,890 25,150 2.38 7,600 9,590 11,490 13,390

115 (46.1) 18,600 2.49 13,810 15,710 17,700 18,600 18,600 20,040 2.52 11,850 13,750 15,740 17,640 19,540 21,340 2.55 9,750 11,650 13,630 15,530 17,430 23,210 2.59 7,700 9,600 11,590 13,490 15,390 23,980 2.63 7,180 9,160 11,070 12,970

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

8.39

USpints/h

SM830082

I - 63

1. Specifications

Indoor Unit: UH2442


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442

23,400 BTU/h

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

2
71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 23,700 1.75 16,860 18,930 21,090 23,150 23,700 24,590 1.77 14,280 16,340 18,500 20,570 22,630 25,530 1.79 11,680 13,740 15,900 17,970 20,040 26,890 1.81 9,110 11,170 13,330 15,400 17,460 27,420 1.84 8,360 10,520 12,590 14,660

AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 22,560 21,250 1.92 2.09 16,260 15,590 18,330 17,660 20,490 19,820 22,560 21,250 22,560 21,250 23,490 22,320 1.94 2.12 13,750 13,190 15,810 15,260 17,970 17,420 20,040 19,490 22,100 21,550 24,520 # 23,400 1.96 2.14 11,230 10,750 13,300 12,810 15,460 14,970 17,530 17,040 19,590 19,110 25,950 24,940 1.98 2.17 8,730 8,330 10,800 10,400 12,960 12,560 15,020 14,620 17,090 16,690 26,540 25,600 2.01 2.2 8,050 7,710 10,210 9,870 12,270 11,940 14,340 14,000

600 CFM

105 (40.6) 19,770 2.33 14,850 16,910 19,070 19,770 19,770 20,990 2.36 12,580 14,640 16,800 18,870 20,940 22,160 2.39 10,220 12,290 14,450 16,510 18,580 23,840 2.42 7,900 9,970 12,130 14,190 16,260 24,520 2.46 7,330 9,490 11,560 13,630

115 (46.1) 18,140 2.56 14,050 16,120 18,140 18,140 18,140 19,540 2.6 11,920 13,990 16,150 18,210 19,540 20,800 2.63 9,660 11,720 13,880 15,950 18,010 22,630 2.67 7,440 9,500 11,660 13,730 15,800 23,380 2.71 6,940 9,100 11,170 13,230

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

7.69

USpints/h

I - 64

SM830082

1. Specifications

Indoor Unit: UH3642


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642

34,500 BTU/h

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 34,950 2.32 26,210 29,810 33,570 34,950 34,950 36,260 2.34 21,860 25,460 29,230 32,830 36,260 37,640 2.36 17,500 21,100 24,860 28,460 32,060 39,640 2.39 13,150 16,750 20,510 24,110 27,710 40,430 2.43 12,100 15,860 19,460 23,060

AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 33,260 31,330 2.53 2.76 25,370 24,440 28,970 28,040 32,740 31,330 33,260 31,330 33,260 31,330 34,640 32,910 2.57 2.8 21,130 20,360 24,730 23,960 28,490 27,720 32,090 31,320 34,640 32,910 36,160 # 34,500 2.59 2.83 16,890 16,210 20,490 19,810 24,250 23,570 27,850 27,170 31,450 30,770 38,260 36,780 2.62 2.87 12,620 12,070 16,220 15,670 19,990 19,440 23,590 23,040 27,190 26,640 39,120 37,740 2.66 2.91 11,650 11,190 15,420 14,950 19,020 18,550 22,620 22,150

1,060 CFM

105 (40.6) 29,150 3.06 23,400 27,000 29,150 29,150 29,150 30,950 3.11 19,500 23,100 26,860 30,460 30,950 32,670 3.14 15,470 19,070 22,840 26,440 30,040 35,160 3.19 11,480 15,080 18,840 22,440 26,040 36,160 3.23 10,660 14,430 18,030 21,630

115 (46.1) 26,740 3.36 22,280 25,880 26,740 26,740 26,740 28,810 3.42 18,580 22,180 25,940 28,810 28,810 30,670 3.45 14,680 18,280 22,050 25,650 29,250 33,360 3.5 10,820 14,420 18,190 21,790 25,390 34,470 3.55 10,110 13,870 17,470 21,070

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

9.97

USpints/h

SM830082

I - 65

1. Specifications

Indoor Unit: UH3642


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642


33,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 31,810 29,960 2.41 2.62 23,890 22,980 27,180 26,270 30,610 29,700 31,810 29,960 31,810 29,960 33,130 31,480 2.44 2.66 19,980 19,240 23,270 22,530 26,710 25,960 30,000 29,250 33,130 31,480 34,580 # 33,000 2.46 2.69 16,080 15,420 19,370 18,710 22,800 22,150 26,090 25,440 29,380 28,720 36,600 35,180 2.49 2.73 12,170 11,630 15,460 14,920 18,890 18,360 22,180 21,640 25,470 24,930 37,420 36,100 2.53 2.77 11,230 10,780 14,670 14,220 17,960 17,510 21,240 20,790 950 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 33,430 2.21 24,700 27,990 31,420 33,430 33,430 34,680 2.23 20,700 23,980 27,420 30,710 34,000 36,000 2.25 16,680 19,960 23,400 26,690 29,980 37,920 2.27 12,670 15,960 19,400 22,690 25,970 38,680 2.31 11,670 15,100 18,390 21,680

105 (40.6) 27,890 2.96 21,980 25,270 27,890 27,890 27,890 29,600 3 18,400 21,690 25,130 28,410 29,600 31,250 3.04 14,710 18,000 21,440 24,720 28,010 33,630 3.08 11,050 14,340 17,780 21,060 24,350 34,580 3.13 10,270 13,710 16,990 20,280

115 (46.1) 25,580 3.3 20,890 24,180 25,580 25,580 25,580 27,560 3.35 17,510 20,800 24,240 27,520 27,560 29,340 3.38 13,950 17,230 20,670 23,960 27,240 31,910 3.43 10,420 13,710 17,150 20,430 23,720 32,970 3.48 9,740 13,170 16,460 19,750

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

9.89

USpints/h

I - 66

SM830082

1. Specifications

Indoor Unit: KH2442


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442


22,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 21,210 19,980 1.86 2.03 15,430 14,800 17,390 16,760 19,440 18,810 21,210 19,980 21,210 19,980 22,090 20,990 1.89 2.06 13,060 12,540 15,020 14,500 17,070 16,550 19,030 18,510 20,990 20,470 23,060 # 22,000 1.9 2.08 10,690 10,230 12,650 12,190 14,700 14,240 16,660 16,200 18,620 18,160 24,400 23,450 1.92 2.11 8,320 7,950 10,280 9,910 12,330 11,960 14,290 13,920 16,250 15,880 24,950 24,070 1.96 2.14 7,690 7,380 9,740 9,430 11,700 11,390 13,660 13,350 540 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 22,290 1.71 15,990 17,950 20,000 21,960 22,290 23,120 1.72 13,550 15,510 17,560 19,520 21,480 24,000 1.74 11,100 13,060 15,110 17,070 19,030 25,280 1.76 8,670 10,630 12,680 14,640 16,600 25,780 1.79 7,980 10,030 11,990 13,960

105 (40.6) 18,590 2.26 14,110 16,070 18,120 18,590 18,590 19,730 2.29 11,960 13,920 15,970 17,930 19,730 20,830 2.32 9,740 11,700 13,750 15,710 17,670 22,420 2.35 7,550 9,510 11,560 13,520 15,480 23,060 2.38 7,020 9,070 11,030 12,990

115 (46.1) 17,050 2.49 13,360 15,330 17,050 17,050 17,050 18,370 2.52 11,350 13,310 15,360 17,320 18,370 19,560 2.55 9,210 11,170 13,220 15,180 17,140 21,270 2.59 7,110 9,070 11,120 13,080 15,040 21,980 2.63 6,650 8,700 10,660 12,620

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

7.08

USpints/h

SM830082

I - 67

1. Specifications

Indoor Unit: KH2442


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH2442


21,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 20,240 19,070 1.92 2.09 14,730 14,130 16,590 16,000 18,550 17,950 20,240 19,070 20,240 19,070 21,080 20,030 1.94 2.12 12,470 11,970 14,330 13,840 16,290 15,790 18,150 17,660 20,020 19,530 22,010 # 21,000 1.96 2.14 10,210 9,780 12,080 11,640 14,030 13,590 15,900 15,460 17,760 17,330 23,290 22,390 1.98 2.17 7,960 7,600 9,820 9,470 11,780 11,420 13,640 13,290 15,510 15,160 23,810 22,970 2.01 2.2 7,350 7,050 9,300 9,010 11,170 10,870 13,040 12,740 510 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 21,270 1.75 15,260 17,130 19,080 20,950 21,270 22,070 1.77 12,940 14,810 16,760 18,630 20,490 22,910 1.79 10,600 12,470 14,420 16,290 18,160 24,130 1.81 8,290 10,160 12,110 13,980 15,840 24,610 1.84 7,640 9,590 11,460 13,320

105 (40.6) 17,750 2.33 13,470 15,340 17,290 17,750 17,750 18,840 2.36 11,430 13,290 15,250 17,110 18,840 19,890 2.39 9,310 11,170 13,130 14,990 16,860 21,400 2.42 7,220 9,090 11,040 12,910 14,770 22,010 2.46 6,720 8,670 10,540 12,400

115 (46.1) 16,280 2.56 12,760 14,620 16,280 16,280 16,280 17,540 2.6 10,840 12,710 14,660 16,530 17,540 18,670 2.63 8,800 10,670 12,620 14,490 16,360 20,310 2.67 6,800 8,670 10,620 12,490 14,360 20,980 2.71 6,360 8,320 10,180 12,050

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

6.76

USpints/h

I - 68

SM830082

1. Specifications

Indoor Unit: KH3642


230V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642


33,000 BTU/h AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 31,810 29,960 2.53 2.76 23,130 22,190 26,060 25,110 29,110 28,170 31,810 29,960 31,810 29,960 33,130 31,480 2.57 2.8 19,600 18,820 22,520 21,740 25,570 24,800 28,500 27,720 31,420 30,640 34,580 # 33,000 2.59 2.83 16,060 15,380 18,980 18,300 22,040 21,360 24,960 24,280 27,880 27,200 36,600 35,180 2.62 2.87 12,540 11,980 15,460 14,900 18,510 17,950 21,430 20,880 24,360 23,800 37,420 36,100 2.66 2.91 11,590 11,120 14,640 14,170 17,560 17,090 20,480 20,020 830 CFM

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 33,430 2.32 23,980 26,900 29,960 32,880 33,430 34,680 2.34 20,340 23,260 26,320 29,240 32,160 36,000 2.36 16,680 19,600 22,660 25,580 28,500 37,920 2.39 13,060 15,980 19,040 21,960 24,880 38,680 2.43 12,040 15,090 18,010 20,940

105 (40.6) 27,890 3.06 21,160 24,080 27,130 27,890 27,890 29,600 3.11 17,960 20,880 23,930 26,850 29,600 31,250 3.14 14,640 17,560 20,620 23,540 26,460 33,630 3.19 11,380 14,300 17,350 20,280 23,200 34,580 3.23 10,590 13,640 16,560 19,490

115 (46.1) 25,580 3.36 20,030 22,960 25,580 25,580 25,580 27,560 3.42 17,040 19,960 23,010 25,940 27,560 29,340 3.45 13,850 16,770 19,820 22,750 25,670 31,910 3.5 10,720 13,640 16,700 19,620 22,540 32,970 3.55 10,030 13,090 16,010 18,930

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

10.61

USpints/h

SM830082

I - 69

1. Specifications

Indoor Unit: KH3642


208V / 1 phase / 60Hz
RATING CAPACITY : EVAPORATOR ENT.TEMP.F(C) WB DB

Outdoor Unit: CH3642

32,000 BTU/h

59 (15.0)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

63 (17.2)

1
67 (19.4)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

2
71 (21.7)

72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)

75 (23.9)

76(24.4) 80(26.7) 84(28.9) 88(31.1)

TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC SHC TC CI SHC SHC SHC SHC

75 (23.9) 32,420 2.21 22,940 25,620 28,420 31,100 32,420 33,630 2.23 19,550 22,230 25,040 27,720 30,400 34,910 2.25 16,150 18,830 21,630 24,320 27,000 36,770 2.27 12,790 15,470 18,280 20,960 23,640 37,500 2.31 11,780 14,580 17,270 19,950

AIR FLOW RATE: CONDENSER AMBIENT TEMP F(C) 85 95 (29.4) (35.0) 30,850 29,060 2.41 2.62 22,100 21,170 24,780 23,850 27,580 26,650 30,270 29,060 30,850 29,060 32,130 30,530 2.44 2.66 18,820 18,050 21,500 20,730 24,300 23,530 26,980 26,220 29,660 28,900 33,540 # 32,000 2.46 2.69 15,530 14,860 18,220 17,540 21,020 20,340 23,700 23,020 26,380 25,710 35,490 34,110 2.49 2.73 12,270 11,710 14,950 14,400 17,750 17,200 20,440 19,880 23,120 22,560 36,290 35,010 2.53 2.77 11,340 10,870 14,140 13,680 16,820 16,360 19,500 19,040

750 CFM

105 (40.6) 27,040 2.96 20,140 22,820 25,620 27,040 27,040 28,700 3 17,190 19,870 22,670 25,360 28,040 30,300 3.04 14,120 16,810 19,610 22,290 24,970 32,610 3.08 11,120 13,800 16,610 19,290 21,970 33,540 3.13 10,350 13,150 15,840 18,520

115 (46.1) 24,800 3.3 19,030 21,710 24,520 24,800 24,800 26,720 3.35 16,280 18,960 21,770 24,450 26,720 28,450 3.38 13,340 16,020 18,830 21,510 24,190 30,940 3.43 10,470 13,160 15,960 18,640 21,320 31,970 3.48 9,800 12,600 15,290 17,970

TC :Total Cooling Capacity (BTU/h) SHC:Sensible Heat Capacity (BTU/h) CI :Compressor Input (kW) Rating conditions are :Outdoor Ambient Temp.95 FDB :Indoor Unit Entering Air Temp.80 FDB/67 FWB

M.R.=

10.63

USpints/h

I - 70

SM830082

1. Specifications

1-8 Heating Capacity

120

Indoor entering air temperature: 70F

Heating capacity (%)

100

80

1
60 10 20 30 40 50 60
2182_X_S

Outdoor ambient temp. (F DB at 75% RH)

SM830082

I - 71

1. Specifications

1-9 Performance Charts q Cooling Characteristics (1) Operating Current 1 Indoor Unit: XH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
Outdoor fan speed High Low 15 14 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

208V
Outdoor fan speed High Low 15 14
Operating current (A)

Operating current (A)

13 12 11 10 9 8 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

13 12 11 10 9 8 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Outdoor ambient temp. F (C)


2183_X_S

Outdoor ambient temp. F (C)


2184_X_S

2
230V

Indoor Unit: XH3642

Outdoor Unit: CH3642 208V

Outdoor fan speed High Low 19 18

Indoor temp. F (C)

Outdoor fan speed High Low 19 18

Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Outdoor ambient temp. F (C)


2185_X_S

Outdoor ambient temp. F (C)


1467_X_S

I - 72

SM830082

1. Specifications

1-9 Performance Charts q Cooling Characteristics (1) Operating Current 1 Indoor Unit: XH4242 Outdoor Unit: CH4242
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
Outdoor fan speed High Low 24 23 Indoor temp. F (C)

208V
Outdoor fan speed High Low 24 23 85 (30) 80 (27) 75 (24) 70 (21) Operating current (A) 22 21 20 19 18 17 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

22 21 20 19 18 17 59 (15)

1
Outdoor ambient temp. F (C)
2224_X_S

Outdoor ambient temp. F (C)


2223_X_S

SM830082

I - 73

1. Specifications

1-9 Performance Charts q Cooling Characteristics (1) Operating Current 1 Indoor Unit: TH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
Outdoor fan speed High Low 15 14 Indoor temp. F (C)

208V
Outdoor fan speed High Low 15 14 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

Operating current (A)

13 12 11 10 9 8 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) 85 (30) 80 (27) 75 (24) 70 (21)

13 12 11 10 9 8 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Outdoor ambient temp. F (C)


2186_X_S

Outdoor ambient temp. F (C)


2187_X_S

2
230V

Indoor Unit: TH3642

Outdoor Unit: CH3642 208V

Outdoor fan speed High Low 19 18 Operating current (A) 17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Indoor temp. F (C)

Outdoor fan speed High Low 19 18

Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

85 (30) 80 (27) 75 (24) 70 (21)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Outdoor ambient temp. F (C)


1466_X_S

Outdoor ambient temp. F (C)


1467_X_S

I - 74

SM830082

1. Specifications

1-9 Performance Charts q Cooling Characteristics (1) Operating Current 1 Indoor Unit: TH4242 Outdoor Unit: CH4242
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
Outdoor fan speed High Low 24 23 Indoor temp. F (C)

208V
Outdoor fan speed High Low 24 23 85 (30) 80 (27) 75 (24) 70 (21) Operating current (A) 22 21 20 19 18 17 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

22 21 20 19 18 17 59 (15)

1
Outdoor ambient temp. F (C)
2224_X_S

Outdoor ambient temp. F (C)


2223_X_S

SM830082

I - 75

1. Specifications

1-9 Performance Charts q Cooling Characteristics (1) Operating Current 1 Indoor Unit: UH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
Outdoor fan speed High Low 15 14 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

208V
Outdoor fan speed High Low 15 14 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

13 12 11 10 9 8 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Operating current (A)

13 12 11 10 9 8 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Outdoor ambient temp. F (C)


2188_X_S

Outdoor ambient temp. F (C)


2189_X_S

2
230V

Indoor Unit: UH3642

Outdoor Unit: CH3642 208V

Outdoor fan speed High Low 19 18

Indoor temp. F (C)

Outdoor fan speed High Low 19 18

Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Operating current (A)

85 (30) 80 (27) 75 (24) 70 (21)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Outdoor ambient temp. F (C)


1466_X_S

Outdoor ambient temp. F (C)


1467_X_S

I - 76

SM830082

1. Specifications

1-9 Performance Charts q Cooling Characteristics (1) Operating Current 1 Indoor Unit: KH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
Outdoor fan speed High Low 15 14 Indoor temp. F (C)

208V
Outdoor fan speed High Low 15 14 Operating current (A) 13 12 11 10 9 8 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40) Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Operating current (A)

13 12 11 10 9 8 59 (15) 85 (30) 80 (27) 75 (24) 70 (21)

1
Outdoor ambient temp. F (C)
1160_X_S

Outdoor ambient temp. F (C)


1159_X_S

Indoor Unit: KH3642 230V


Outdoor fan speed High Low 19 18

Outdoor Unit: CH3642 208V


Indoor temp. F (C)

2
Indoor temp. F (C)

Outdoor fan speed High Low 19 18 Operating current (A)

Operating current (A)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

85 (30) 80 (27) 75 (24) 70 (21)

17 16 15 14 13 12 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

85 (30) 80 (27) 75 (24) 70 (21)

Outdoor ambient temp. F (C)


2190_X_S

Outdoor ambient temp. F (C)


2191_X_S

SM830082

I - 77

1. Specifications

1-9 Performance Charts q Heating Characteristics (1) Operating Current 1 Indoor Unit: XH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
15 14
Operating current (A)

208V
Indoor temp. F (C) 75 (24) 70 (21) 65 (18) 15 14
Operating current (A)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Outdoor ambient temp. F (C)


2192_X_S

Outdoor ambient temp. F (C)


2232_X_S

2
230V
22 21

Indoor Unit: XH3642

Outdoor Unit: CH3642 208V


Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
22 21 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Operating current (A)

Operating current (A)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Outdoor ambient temp. F (C)


2233_X_S

Outdoor ambient temp. F (C)


2234_X_S

I - 78

SM830082

1. Specifications

1-9 Performance Charts q Heating Characteristics (1) Operating Current 1 Indoor Unit: XH4242 Outdoor Unit: CH4242
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
25 24 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

208V
25 24
Operating current (A)

Operating current (A)

23 22 21 20 19 18 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

23 22 21 20 19 18 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

1
Outdoor ambient temp. F (C)
2226_X_S

Outdoor ambient temp. F (C)


2225_X_S

SM830082

I - 79

1. Specifications

1-9 Performance Charts q Heating Characteristics (1) Operating Current 1 Indoor Unit: TH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
15 14
Operating current (A)

208V
Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
15 14
Operating current (A)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Outdoor ambient temp. F (C)


2192_X_S

Outdoor ambient temp. F (C)


2193_X_S

2
230V
22 21

Indoor Unit: TH3642

Outdoor Unit: CH3642 208V


Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
22 21 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Operating current (A)

Operating current (A)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Outdoor ambient temp. F (C)


2233_X_S

Outdoor ambient temp. F (C)


2234_X_S

I - 80

SM830082

1. Specifications

1-9 Performance Charts q Heating Characteristics (1) Operating Current 1 Indoor Unit: TH4242 Outdoor Unit: CH4242
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
25 24 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

208V
25 24

Operating current (A)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

23 22 21 20 19 18 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Operating current (A)

23 22 21 20 19 18 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

1
2227_X_S

Outdoor ambient temp. F (C)


2225_X_S

Outdoor ambient temp. F (C)

SM830082

I - 81

1. Specifications

1-9 Performance Charts q Heating Characteristics (1) Operating Current 1 Indoor Unit: UH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
15 14
Operating current (A)

208V
Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
15 14
Operating current (A)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Outdoor ambient temp. F (C)


2194_X_S

Outdoor ambient temp. F (C)


2195_X_S

2
230V
22 21

Indoor Unit: UH3642

Outdoor Unit: CH3642 208V


Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
22 21 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Operating current (A)

Operating current (A)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Outdoor ambient temp. F (C)


2233_X_S

Outdoor ambient temp. F (C)


2234_X_S

I - 82

SM830082

1. Specifications

1-9 Performance Charts q Heating Characteristics (1) Operating Current 1 Indoor Unit: KH2442 Outdoor Unit: CH2442
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V
15 14
Operating current (A)

208V
Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
15 14
Operating current (A)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

13 12 11 10 9 8 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

1
Outdoor ambient temp. F (C)
2232_X_S

Outdoor ambient temp. F (C)


2235_X_S

Indoor Unit: KH3642 230V


22 21
Operating current (A)

Outdoor Unit: CH3642 208V


Indoor temp. F (C) 75 (24) 70 (21) 65 (18)
Operating current (A)
22 21 20 19 18 17 16 15 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

20 19 18 17 16 15 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

14 (10)

23 (5)

32 (0)

41 (5)

50 (10)

59 (15)

68 (20)

Outdoor ambient temp. F (C)


2196_X_S

Outdoor ambient temp. F (C)


2197_X_S

SM830082

I - 83

1. Specifications

1-9 Performance Charts q Cooling Characteristics (2) Operating Pressure 1 Indoor Unit: 24 Type High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

Outdoor Unit: CH2442

230V / 208V
Outdoor fan speed High Low 340 320 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Discharge pressure (psig)

300 280 260 240 220 200 180

160 59 (15)

68 (20)

77 (25)

86 (30)

95 (35)

104 (40)
1161_X_S

Outdoor ambient temp. F (C)

Low Pressure

Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V / 208V
Outdoor fan speed Low High

Suction pressure (psig)

100 90 80 70 60 50 40 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Outdoor ambient temp. F (C)


1162_X_S

I - 84

SM830082

1. Specifications

1-9 Performance Charts q Cooling Characteristics (2) Operating Pressure 1 Indoor Unit: 36 Type High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

Outdoor Unit: CH3642

230V / 208V
Outdoor fan speed High Low 320 300 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Discharge pressure (psig)

280 260 240 220 200 180 160 140 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

2
1459_X_S

Outdoor ambient temp. F (C)

Low Pressure
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V / 208V
Outdoor fan speed High Low 100 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Suction pressure (psig)

90 80 70 60 50 40 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

5
1460_X_S

Outdoor ambient temp. F (C)

SM830082

I - 85

1. Specifications

1-9 Performance Charts q Cooling Characteristics (2) Operating Pressure 1 Indoor Unit: 42 Type High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

Outdoor Unit: CH4242

230V / 208V
Outdoor fan speed High Low 340 320 Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Discharge pressure (psig)

300 280 260 240 220 200 180

160 59 (15)

68 (20)

77 (25)

86 (30)

95 (35)

104 (40)
2228_X_S

Outdoor ambient temp. F (C)

Low Pressure

Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V / 208V
Outdoor fan speed Low High

Suction pressure (psig)

100 90 80 70 60 50 40 59 (15) 68 (20) 77 (25) 86 (30) 95 (35) 104 (40)

Indoor temp. F (C) 85 (30) 80 (27) 75 (24) 70 (21)

Outdoor ambient temp. F (C)


1162_X_S

I - 86

SM830082

1. Specifications

1-9 Performance Charts q Heating Characteristics (2) Operating Pressure 1 Indoor Unit: 24 Type High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

Outdoor Unit: CH2442

230V / 208V
340 320 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Discharge pressure (psig)

300 280 260 240 220 200 180 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

2
1165_X_S

Outdoor ambient temp. F (C)

Low Pressure
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V / 208V
90
Suction pressure (psig)

80 70 60 50 40 30 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

5
Outdoor ambient temp. F (C)
1166_X_S

SM830082

I - 87

1. Specifications

1-9 Performance Charts q Heating Characteristics (2) Operating Pressure 1 Indoor Unit: 36 Type High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

Outdoor Unit: CH3642

230V / 208V
340 320 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Discharge pressure (psig)

300 280 260 240 220 200 180

14 (10)

23 (5)

32 (0)

41 (5)

50 (10)

59 (15)

68 (20)

Outdoor ambient temp. F (C)


1165_X_S

I - 88

SM830082

1. Specifications

1-9 Performance Charts q Heating Characteristics (2) Operating Pressure 1 Indoor Unit: 42 Type High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

Outdoor Unit: CH4242

230V / 208V
340 320 Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

Discharge pressure (psig)

300 280 260 240 220 200 180 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

2
2229_X_S

Outdoor ambient temp. F (C)

Low Pressure
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)

230V / 208V
90
Suction pressure (psig)

80 70 60 50 40 30 14 (10) 23 (5) 32 (0) 41 (5) 50 (10) 59 (15) 68 (20)

Indoor temp. F (C) 75 (24) 70 (21) 65 (18)

5
Outdoor ambient temp. F (C)
2230_X_S

SM830082

I - 89

1. Specifications

1-10 Noise Criterion Curves q 4-Way Air Discharge Semi-concealed Type


MODEL : XH2442 38 dB(A), 31 dB(A), NC 31 NC 23 SOUND LEVEL : HIGH LOW CONDITION SOURCE
60

: Center,

Under the unit 4.9 ft.

: 208 - 230 V, 1 Phase, 60 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

NC-50

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

2
MODEL

1000 2000 4000 8000


2108_X_I

BAND CENTER FREQUENCIES, Hz

: XH3642 44 dB(A), 33 dB(A), NC 37 NC 25

MODEL

: XH4242 45 dB(A), 34 dB(A), NC 38 NC 27

SOUND LEVEL : HIGH LOW CONDITION : Center,

SOUND LEVEL : HIGH LOW CONDITION SOURCE


60

Under the unit 4.9 ft.

: Center, Under the unit 4.9 ft. : 208 - 230 V, 1 Phase, 60 Hz

SOURCE
60

: 208 - 230 V, 1 Phase, 60 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

NC-50

50

NC-50

40

NC-40

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

NC-20

1000 2000 4000 8000


2109_X_I

1000 2000 4000 8000


2110_X_I

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

I - 90

SM830082

1. Specifications

1-10 Noise Criterion Curves q Ceiling Mounted Type


MODEL : TH2442 40 dB(A), 36 dB(A), NC 34 NC 26 CONDITION SOURCE
60

MODEL

: TH3642 46 dB(A), 37 dB(A), NC 39 NC 31

SOUND LEVEL : HIGH LOW CONDITION SOURCE


60

SOUND LEVEL : HIGH LOW

: Distance 3.3 ft., Under the unit 3.3 ft. : 208 - 230 V, 1 Phase, 60 Hz

: Distance 3.3 ft., Under the unit 3.3 ft. : 208 - 230 V, 1 Phase, 60 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

NC-50

50

NC-50

40

NC-40

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

NC-20

1000 2000 4000 8000


1221_X_I

1000 2000 4000 8000


2113_X_I

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

MODEL

: TH4242 47 dB(A), 38 dB(A), NC 40 NC 32

SOUND LEVEL : HIGH LOW CONDITION SOURCE


60

: Distance 3.3 ft., Under the unit 3.3 ft. : 208 - 230 V, 1 Phase, 60 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

NC-50

40

4
NC-40 NC-30

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-20

1000 2000 4000 8000


2114_X_I

BAND CENTER FREQUENCIES, Hz

SM830082

I - 91

1. Specifications

1-10 Noise Criterion Curves q Concealed Duct Type


MODEL : UH2442 MODEL : UH3642 SOUND LEVEL : HIGH 34 dB(A), NC 22 / LOW 27 dB(A), NC 18 CONDITION SOURCE : Under the unit 4.9 ft. : 208 - 230 V, 1 Phase, 60 Hz SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21 CONDITION SOURCE : Under the unit 4.9 ft. : 208 - 230 V, 1 Phase, 60 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

60

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

60

50

NC-50

50

NC-50

40

NC-40

40

NC-40

30

NC-30

30

NC-30

20

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

20

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
1761_U_I

10

APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE

NC-20

63 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz
1762_U_I

I - 92

SM830082

1. Specifications

1-10 Noise Criterion Curves q Wall Mounted Type


MODEL : KH2442 45 dB(A), 40 dB(A), NC 38 NC 33 CONDITION SOURCE
60

MODEL

: KH3642 48 dB(A), 40 dB(A), NC 41 NC 33

SOUND LEVEL : HIGH LOW CONDITION SOURCE


60

SOUND LEVEL : HIGH LOW

: Distance 3.3 ft., Under the unit 3.3 ft. : 208 - 230 V, 1 Phase, 60 Hz

: Distance 3.3 ft., Under the unit 3.3 ft. : 208 - 230 V, 1 Phase, 60 Hz

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar)

50

NC-50

50

NC-50

40

NC-40

40

NC-40

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

30 APPROXIMATE THRESHOLD OF 20 HEARING FOR CONTINUOUS NOISE 10 63 125 250 500

NC-30

NC-20

NC-20

1000 2000 4000 8000


2119_K_I

1000 2000 4000 8000


2120_K_I

BAND CENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

SM830082

I - 93

1. Specifications

1-10 Noise Criterion Curves q Outdoor Units


MODEL CONDITION SOURCE
90

: CH2442 NC 44 : Distance 1m, Height 1m : 230 - 208 V, 1 Phase, 60 Hz

MODEL CONDITION SOURCE


90

: CH3642 NC 45 : Distance 1m, Height 1m : 230 - 208 V, 1 Phase, 60 Hz

SOUND LEVEL : 53 dB(A),

SOUND LEVEL : 56 dB(A),

OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)

80

80 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)

70

NC-70

70

NC-70

60

NC-60

60

NC-60

50

NC-50

50

NC-50 NC-40 NC-30

40

40

NC-40 NC-30

30 20 APPROXIMATE THRESHOLD OF CONTINUOUS NOISE 10 60 125 250

30 APPROXIMATE 20 THRESHOLD OF HEARING FOR CONTINUOUS NOISE 10 63 125 250

NC-20

NC-20

500 1000 2000 4000 8000


0598_C_S

500

1000 2000 4000 8000


0597_C_S

BAND CAENTER FREQUENCIES, Hz

BAND CENTER FREQUENCIES, Hz

MODEL

: CH4242 NC 47 : Distance 1m, Height 1m : 230 - 208 V, 1 Phase, 60 Hz

SOUND LEVEL : 56 dB(A), CONDITION SOURCE


90

80
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 bar)

70

NC-70

60

NC-60

50

NC-50

40

NC-40 NC-30

30 APPROXIMATE 20 THRESHOLD OF HEARING FOR CONTINUOUS NOISE 10 63 125 250

NC-20

500

1000 2000 4000 8000


0599_C_S

BAND CENTER FREQUENCIES, Hz

REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an anechoic room. NOTE To evaluate Noise level the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used. Read the number on each BAND CENTER FREQUENCIES (horizontal axis) ranging from 63 Hz to 8000 Hz and select the maximum value (vertical axis) among them.

I - 94

SM830082

1. Specifications

1-11 Increasing the Fan Speed


Electrical component box

If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: (1) (2) (3) (4) Remove 4 screws on the electrical component box and remove the cover plate. Disconnect the fan motor sockets in the box.
External Static Pressure

Fan motor

Jumper cable Jumper cable

Fan motor socket (At shipment)

(Jumper cable installed)


2159_M_I

(inAq)

150

150
(Pa)

(Pa)

line

t line

0.5

0.5 0.4 0.3 0.2 0.1 0 500


1981_U_I

External Static Pressure

ne

Securely connect the jumper cable sockets between the disconnected fan motor sockets in step 2. Place the cable neatly in the box and reinstall the cover plate.

0.3 0.2 0.1

Lim

50 H L 0 200 300

HT HH

50 H L 0 200

Lim i

it li

t lin e

Take out the jumper cable (sockets at both ends) clamped in the box.

Limi

100

0.4

100

Lim it

HT HH

(inAq)

12 Type

18 Type

(5)

0 400
1980_U_I

300

400

Air Flow (CFM)

Air Flow (CFM)

Indoor Fan Performance 24 Type


200
(Pa)

36 Type
0.8
(inAq)

(inAq)

t line

(Pa)

Limit

line

150 External Static Pressure

External Static Pressure

Limi

150

0.6 0.5

0.5 0.4 0.3 HT 0.2 HH H L 0.1


e

Lim it li

ne

Lim

it lin

100

100

0.4 0.3

50

50 H L 0 500

HT HH

0.2 0.1 0

0 300

500

700

0 900
1982_U_I

1000 Air Flow (CFM)


1983_U_I

Air Flow (CFM)

NOTE

HT : Using the booster cable H : At shipment

s How to read the diagram


The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (CFM). The characteristic curves for HT, H, M and L fan speed control are shown. The nameplate values are shown based on the H air flow. For the 24 type, the air flow is 636 CFM, while the external static pressure is 49 Pa at H position. If external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above.
SM830082

I - 95

1. Specifications

1-12 Air throw distance chart q 4-Way Air Discharge Semi-concealed Type
Model: 24 Type

HORIZONTAL DISTANCE (ft.) 0 0 3 7 10 13 17 20

AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.)

AXIS AIR VELOCITY

10

13
2111_X_I

1
Model: 36, 42 Type

HORIZONTAL DISTANCE (ft.) 0


AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.)

10

13

17

20

0 AXIS AIR VELOCITY

10

13
2112_X_I

4
: LOUVER ANGLE 20 in Cooling mode : LOUVER ANGLE 60 in Heating mode Condition Fan Speed : Hi Room air temp. : 80 C DB in cooling mode 68 C DB in heating mode

I - 96

SM830082

1. Specifications

1-12 Air throw distance chart q Ceiling Mounted Type


Model: 24 Type
0 3 7 HORIZONTAL DISTANCE (ft.) 10 13 17 20 23 26 29 33

AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.)

0 3 7 10 13 17 HORIZONTAL DISTANCE (ft.) 3 7 10 13 17 20 23 26 29 33


2115_T_I

AXIS AIR VELOCITY

Model: 36 Type
0 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 3 7 10 13 17

AXIS AIR VELOCITY

2116_T_I

Model: 42 Type
0 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 3 7 10 13 17 3 7

HORIZONTAL DISTANCE (ft.) 10 13 17 20 23 26 29 33

AXIS AIR VELOCITY

3
COOLING HEATING HIGH 68 F 54 : COOLING : HEATING
2117_T_I

FAN SPEED ROOM AIR TEMP. LOUVER ANGLE

HIGH 80 F 7

SM830082

I - 97

1. Specifications

1-12 Air throw distance chart q Wall Mounted Type


MODEL: KHS2442
Horizontal distance (ft.) 0 5 10 15 20 25 30

Axis air velo

city

Axis air velocity (ft./sec.) Vertical distance (ft.)

5 67.5 10

45 0 22.5 45

15
2121_K_S

1
COOLING - - - - - HEATING FAN SPEED ROOM AIR TEMP. FLAP ANGLE HIGH 80F 0, 22.5, 45 HIGH 70F 54, 67.5

2
MODEL: KHS3642
Horizontal distance (ft.) 0 5 10 15 20 25
Axis air velo

30
city

33

Axis air velocity (ft./sec.) Vertical distance (ft.)

5 67.5 10 13

45 0 45 22.5

2122_K_S

COOLING - - - - - HEATING

FAN SPEED ROOM AIR TEMP. FLAP ANGLE

HIGH 80F 0, 22.5, 45

HIGH 70F 45, 67.5

I - 98

SM830082

1. Specifications

1-13 Installation Instructions q Tubing Length


q Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. q Select and decide the installation location so that the length of the refrigerant tubing will be within the limits given in Table 1-10.
INDOOR UNIT Tubing length (L)

Elevation difference (H)

OUTDOOR UNIT

0711_M_I

Fig. 1-1 Table 1-10 Models Tubing Data Tubing size outer dia. Limit of tubing length Limit of elevation difference between the 2 units Narrow tube Wide tube in. (mm) in. (mm) (ft.) Outdoor unit is higher than indoor unit (ft.) Outdoor unit is lower than indoor unit (oz./ft.) CH2442 1/4 (6.35) 3/4 (19.05) 165 165 100 (ft.) 100 0.48
*1

CH3642, CH4242 3/8 (9.52) 3/4 (19.05) 165 165 100 100 0.53*2

Max. allowable tubing length at shipment (ft.) Required additional refrigerant

No additional charge of compressor oil is necessary. *1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.48 oz./ft.. *2 If total tubing length becomes 100 to 165 ft., charge additional refrigerant (R22) by 0.53 oz./ft..

SM830082

I - 99

1. Specifications

s SELECTING THE INSTALLATION SITE


Indoor Unit Ceiling-Mounted Type AVOID: q areas where leakage of flammable gas may be expected. q places where large amounts of oil mist exist. q direct sunlight. q locations near inverter lamps which may affect performance of the unit. q locations near heat sources which may affect performance of the unit. q locations where external air may enter the room directly. This may cause sweating on the air discharge ports, causing them to spray or drip.
Min.10 inch Front view Min.10 inch Wall Ceiling

NOTE
The rear of the indoor unit can be installed flush against the wall.
Air discharge Ceiling

q locations where the remote control unit will be splashed with water or affected by dampness or humidity. q installing the remote control unit behind curtains or furniture. q locations where the receiver in the indoor unit is exposed to the inverter lamp light. Faulty operation of the unit occurs. DO: q select an appropriate position from which every corner of the room can be uniformly cooled.

Min.2 ft.

Air intake

Side view
1091_T_I

4-Way Air Discharge Type Concealed-Duct Type

3 ft. 3 ft.

q select a location where the ceiling is strong enough to support the weight of the unit. q select a location where tubing and drain pipe have the shortest run to the outdoor unit. q allow room for operation and maintenance as well as unrestricted air flow around the unit. q install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length from the outdoor unit as detailed in Table 1-10. q allow room for mounting the remote control unit about 3 ft. off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.

3 ft. 3 ft. 3 ft.

1960_X_I

Wall-Mounted Type

Min. 6 inch Min. 6 inch Min. 12 inch

0930_K_I

NOTE q Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft..

I - 100

SM830082

1. Specifications

Exhaust fan

Outdoor Unit
Hot air

AVOID: q heat sources, exhaust fans, etc. (Fig. 2-1) q damp, humid or uneven locations. DO: q choose a place as cool as possible. q choose a place that is well ventilated and outside air temperature does not exceed maximum 115F constantly. q allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 2-2) q provide a solid base; about 6 inch above ground level to reduce humidity and possible water damage in the unit and decreased service life. (Fig. 2-3) q use lug bolts or equivalent to bolt down unit, reducing vibration and noise. In case of multiple installations
Unit spacing if air discharge chamber is not used. Unit spacing when air discharge chamber is used.

Heat source Outdoor unit

0591_C_I

Fig. 2-1

Min. 1 inch 4 in.

Min. 1 inch

Obstacle above Min. 7 ft. Air discharge

1
0932_C_I

Min. 2 ft.
0931_C_I

Ground

Fig. 2-2

2
Min. 4 ft. Air discharge chamber

Min. 4 ft.

Min. 5 ft.

Min. 4 ft.

Min. 4 ft.

Min. 8 inch

Min. 1 ft.

Min. 1 ft. 2 inch

Min. 1 ft. 2 inch Min. 12 ft. Min. 1 ft. Min. 8 inch If you would like to make the separation smaller on the air discharge side, use an air discharge chamber. You can install any number of units side-by -side. Min. 1 ft. Only up to 3 units can be installed side-by-side under the above conditions. The next group must be spaced at least 1 ft. away from the first group.
0933_C_S

Air in Air in

Air discharge Concrete block 4 inch 1 ft. 4 inch beams or equal Anchor bolts (4 pieces)

5
Min. 6 inch
0934_C_I

Fig. 2-3
SM830082

I - 101

1. Specifications

s Air Discharge Chamber for Top Discharge


Install the air-discharge chamber in the field when: q it is difficult to keep a space of minimum 2 ft. between the air-discharge outlet and the obstacle. q the air-discharge outlet is facing the sidewalk and discharge hot air can annoy the passers-by. Refer to Fig. 2-4.
Air discharge

0426_C_I

22-5/16"

3-

/ 2-3

8"

ho

le

Recommended outer dimensions of wind shield (field supply)

3-15/16"

11-13/16"
3

/ 1-9

16

"h

ole

17-3/4"

8-

4 1/

"h

ol

9-27/32"

21-13/16"
6 /6 15

4"

ho

le

9-7/8"

23-15/32"

43-15/16"

22-7/16"

21-5/8"

9-7/8"

5-3/16"

15/16"

23-5/16"

5-5/32"

1-7/32"

9-27/32"

9-27/32"

1/2"

5-3/16"

5-5/32"

21-13/16"
1352_C_I

0936_C_I

CH3642 Fig. 2-4

CH2442

s Installing the Outdoor Unit in Heavy Snow Areas

In locations subject to strong winds, snow-proof ducting should be fitted and direct exposure to the wind should be avoided as much as possible. The following problems may occur when the outdoor unit is not provided with a platform and snow-proof ducting.

a) b) c) d)

The outdoor fan may not run and there may be damage to the unit There may be no air flow. The tubing may freeze and burst. The condenser pressure may drop because of strong wind, and the indoor unit may freeze. I - 102
SM830082

1. Specifications

s Precautions When Installing in Heavy Snow Areas


(1) (2) The platform should be higher than the maximum. snow depth. (Fig. 2-5) The two anchoring feet of the outdoor unit should be attached to the platform, and the platform should be installed beneath the air-intake side of the outdoor unit. The platform foundation must be solid and the unit must be secured with anchor bolts. When installing on a roof subject to strong wind, countermeasures must be taken to prevent the unit from being overturned.
In regions with snow fall, the outdoor unit should be provided with a platform and snow-proof duct.

(3) (4)

Dimensions of Snow / Wind-proof Ducting and Refrigerant Tubing Space for Installation

Without snowproof ducting (Low platform)

Snow-proof ducting (High platform)


0937_C_I

Fig. 2-5
Min. 4" Duct Duct Outdoor Unit 12"

Fig. 2-6

Outdoor Unit

Duct Duct
Min. 4" 12" Unit: inch
1117_C_I

2
Higher than the maximum snow depth

Air Intake

Air Intake Platform (foundation) About 1/2 of the unit height


0488_C_I

Fig. 2-7
Example of Installation

5
0490_C_I

Fig. 2-8
SM830082

I - 103

1. Specifications

s ELECTRICAL WIRING q General Precautions on Wiring


(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. (3) To prevent possible hazards from insulation failure, the unit must be grounded. (4) Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged. (5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. (7) Regulations on wire diameters differ from locality to locality. For field wiring rules, must follow your LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations. (8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows: q The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring. q Use shielded wires for inter-unit control wiring between units and ground the shield on both sides. (9) If the power supply cord of this appliance is damaged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required. (10) All wiring must be used class 1.

(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

q Recommended Wire Length and Wire Diameter for Power Supply System
Must follow LOCAL ELECTRICAL CODES for wiring. Outdoor Unit Model Name (A) Power Supply Trade size of Conduit AWG #12 Max. length 69 ft. AWG #12 Max. length 69 ft. AWG #10 Max. length 67 ft. 3/4 in. 3/4 in. 3/4 in. * AWG = American Wire Gauge MOP Power Supply Terminal Base Trade size (Fuse or HACR of Conduit type circuit braker) Capacity Max. Wire Diameter 25 A 35 A/40 A (230/208 V) 45 A 50 A 50 A 50 A AWG #6 AWG #6 AWG #6 1-1/4 in. 1-1/4 in. 1-1/4 in.

CH2442 CH3642 CH4242 Indoor Unit

Type X, K, T, U

(B) Power Supply Trade size of Conduit Max. length 330 ft. 3/4 in.

MOP Power Supply Terminal Base Trade size (Fuse or HACR of Conduit type circuit braker) Capacity Max. Wire Diameter 15 A 25 A AWG #10 3/4 in.

Control Wiring (C) Inter-Unit Control Wiring AWG #18 (0.75 mm2) Use high voltage wire (300 V)*1 Max. 3,300 ft. NOTE

(D) Remote Control Wiring AWG #18* (0.75 mm2) Max. 1,650 ft.

(E) Control Wiring For Group Control AWG #18*2 (0.75 mm2) Max. 1,650 ft. (Total)

*1 With ring type wire terminal. *2 Wire joint connection.


SM830082

I - 104

1. Specifications

q Wiring System Diagrams


(1) Basic wiring diagram for standard control
Indoor Unit B Inter-unit power wiring Single phase 230/208V Inter-unit control wiring (Low voltage) 1 1 1 2 G U1 U2 1 C Ground U1 U2 L1 L2 G A Ground
L1 L2 Power supply Single phase 230/208V

Outdoor Unit 1 2 G
0 R.C. Address on the PCB: 0 (S2, BLK) (0: Factory shipped state)

2 2 2 D Remote controller (Option) *Remote controller wirings are wire joint connection.

2085_M_I

NOTE (1) Refer to Recommended Wire Length and Wide Diameter for Power Supply System for the explanation of A, B, C, D, and E, in the above diagrams. Inter-Unit Control Wiring (C) and remote controller wiring (D), (E) has no polarity. But for other wiring, respect polarity. Be sure to connect as shown in the Wiring System Diagram. R.C. Address should be set before turning the power on. Regarding the R.C. Address setting, refer to Auto. address setting can be executed by a remote controller automatically.
CH Type
5P terminal board + 2P terminal board

1
1 2 G L1 L2 Inter-unit Power power wiring supply U1 U2 Inter-unit control wiring
2086_M_I

(2)

XH, TH, UH Type


5P terminal board

KH Type
4P terminal board

(3) (4)

U1 U2 1 2 U1 U2 1 2 Remote Remote Inter-unit Inter-unit Inter-unit Inter-unit controller wiring power wiring control wiring controller wiring control wiring power wiring
2087_M_I
2103_M_I

2088_M_I

2103_M_I

SM830082

I - 105

1. Specifications

(2)

Basic wiring diagram for group control

This diagram shows when several units (max. 8) are controlled by a remote controller. In this case, a remote controller can be connected at any indoor unit.
Indoor Unit B Inter-unit power wiring single phase 230/208V Inter-unit control wiring (Low voltage) RED BLK 1 2 1 2 1 2 G Ground U1 U2 1 2 C U1 U2 4 L1 L2 G A
L1 L2

Outdoor Unit 1 2 G
*1 R.C. Address on the PCB: 1 (S2, BLK)
1

Power supply single phase 230/208V

Ground

Remote controller (Option) D

E Indoor Unit B Inter-unit power wiring single phase 230/208V Inter-unit control wiring (Low voltage) 1 2 Ground U1 U2 1 2 C U1 U2 4 L1 L2 G A
L1 L2

Outdoor Unit 1
2

R.C. Address on the PCB: 2 (S2, BLK)

2
E

Power supply single phase 230/208V

Ground

Indoor Unit B

Outdoor Unit 1 2 Ground


R.C. Address on the PCB: 8 (S2, BLK)
8

Inter-unit power wiring single phase 230/208V Inter-unit control wiring (Low voltage)

1 2

U1 U2 1 C

U1 U2

4 L1 L2 G A
L1 L2

Power supply single phase 230/208V

4
NOTE

2 *Remote controller wirings are wire joint connection.

Ground

2089_M_I

q R.C. Address should be set before turning the power on.

q Auto. address setting can be executed by a remote controller automatically. Please refer to Automatic Address Setting Method. q Each successive unit will respond at one-second intervals following the order of the R.C. address when the remote controller is operated.

I - 106

SM830082

1. Specifications

Electrical characteristics s Electrical Data Indoor model: XH2442 / Outdoor model: CH2442 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.12 - 0.11 1-1 0.12 - 0.11 0.6 - 0.6

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 9.7 - 10.1 2.15 - 2.07 11.1 - 12.0 2.50 - 2.47 66 - 60 11.2 - 11.6 2.45 - 2.35 12.6 - 13.5 2.80 - 2.75 68 - 62

230 - 208 V / 1 phase / 60 Hz 0.6 - 0.6 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

q Heating

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.09 - 0.08 1-1 0.09 - 0.08 0.4 - 0.4

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 10.4 - 11.0 2.23 - 2.20 10.8 - 11.7 2.43 - 2.40 66 - 60 11.7 - 12.3 2.50 - 2.45 12.1 - 13.0 2.70 - 2.65 68 - 62

230 - 208 V / 1 phase / 60 Hz 0.4 - 0.4 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

Cooling: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature 70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB 80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

SM830082

I - 107

1. Specifications

Indoor model: XH3642 / Outdoor model: CH3642 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW 0.20 - 0.16 1-1 0.20 - 0.16 0.9 - 0.8

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 12.7 - 13.2 2.79 - 2.70 15.4 - 16.7 3.43 - 3.41 95 - 86 15.4 - 15.8 3.35 - 3.20 18.1 - 19.3 3.99 - 3.91 98 - 89

230 - 208 V / 1 phase / 60 Hz 0.9 - 0.8 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Starting amperes

q Heating

Indoor Unit

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 15.7 - 16.9 3.33 - 3.29 14.2 - 15.6 3.16 - 3.21 95 - 86 18.2 - 19.3 3.85 - 3.75 16.7 - 18.0 3.68 - 3.67 98 - 89

Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.16 - 0.12 1-1 0.16 - 0.12 0.7 - 0.6

230 - 208 V / 1 phase / 60 Hz 0.7 - 0.6 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

Heating: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB

I - 108

SM830082

1. Specifications

Electrical characteristics s Electrical Data Indoor model: XH4242 / Outdoor model: CH4242 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.2 2 0.17 2 0.36 2 0.2 1.0 0.17 0.9 0.36 1.8 230 V 1.0 208 V 0.9

Outdoor Unit Complete Unit Fan Motor 230 V 1.8 208 V 1.8 0.34 1.8 0.34 2 Compressor 230 V 17.8 3.64 21.0 4.41 131 208 V 18.3 3.58 21.9 4.33 131 230 V 20.6 4.2 23.8 4.97 134 208 V 21.0 4.09 24.6 4.84 133.9

q Heating

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.19 2 0.16 2 0.36 2 0.19 0.9 0.16 0.8 0.36 1.8 230 V 0.9 208 V 0.8

Outdoor Unit Complete Unit Fan Motor 230 V 1.8 208 V 1.8 0.34 1.8 0.34 2 Compressor 230 V 18.9 3.9 21.2 4.48 131 208 V 19.6 3.85 22.8 4.52 131 230 V 21.6 4.45 23.9 5.03 133.9 208 V 22.2 4.35 25.4 5.02 133.8

Cooling: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature 70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB 80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

SM830082

I - 109

1. Specifications

Indoor model: TH2442 / Outdoor model: CH2442 q Cooling


Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW 0.08 - 0.07 1-1 0.18 - 0.17 1-1 2.45 - 2.42 66 - 60 2.71 - 2.66 68 - 62 0.08 - 0.07 0.4 - 0.4 0.18 - 0.17 0.9 - 0.9 2.09 - 2.04 11.0 - 11.7 2.35 - 2.28 12.3 - 13.0 Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 9.4 - 10.0 10.7 - 11.3

230 - 208 V / 1 phase / 60 Hz 0.4 - 0.4 0.9 - 0.9

Starting amperes

q Heating

Indoor Unit

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 10.4 - 11.6 2.29 - 2.26 11.4 - 11.8 2.55 - 2.44 66 - 60 11.7 - 12.9 2.55 - 2.50 12.7 - 13.1 2.81 - 2.68 68 - 62

2
Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

Fan Motor

230 - 208 V / 1 phase / 60 Hz 0.4 - 0.4 0.08 - 0.07 0.4 - 0.4 0.08 - 0.07 1-1 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions

80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB

I - 110

SM830082

1. Specifications

Indoor model: TH3642 / Outdoor model: CH3642 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.16 - 0.14 1-1 0.16 - 0.14 0.7 - 0.7

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 12.6 - 13.2 2.83 - 2.69 15.4 - 16.8 3.45 - 3.38 95 - 86 15.1 - 15.7 3.35 - 3.17 17.9 - 19.3 3.97 - 3.86 97.7 - 88.7

230 - 208 V / 1 phase / 60 Hz 0.7 - 0.7 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

q Heating

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.16 - 0.14 1-1 0.16 - 0.14 0.7 - 0.7

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 15.7 - 17.1 3.43 - 3.41 13.6 - 14.6 3.02 - 2.98 95 - 86 18.2 - 19.6 3.95 - 3.89 16.1 - 17.1 3.54 - 3.46 97.7 - 88.7

230 - 208 V / 1 phase / 60 Hz 0.7 - 0.7 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Cooling: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature 70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB 80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

SM830082

I - 111

1. Specifications

Indoor model: TH4242 / Outdoor model: CH4242 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW 0.18 1 0.15 1 0.36 2 0.18 0.8 0.15 0.7 0.36 1.8 230 V 0.8 208 V 0.7

Outdoor Unit Complete Unit Fan Motor 230 V 1.8 208 V 1.8 0.34 1.8 0.34 2 Compressor 230 V 18.0 3.76 21.0 4.49 131 208 V 18.8 3.71 22.6 4.49 131 230 V 20.6 4.3 23.6 5.03 133.8 208 V 21.3 4.2 25.1 4.98 133.7

Starting amperes

q Heating

Indoor Unit

Outdoor Unit Complete Unit Fan Motor 230 V 1.8 0.36 1.8 0.36 2 208 V 1.8 0.34 1.8 0.34 2 Compressor 230 V 19.1 3.91 21.2 4.52 131 208 V 20.0 3.86 23.6 4.67 131 230 V 21.7 4.45 23.8 5.06 133.8 208 V 22.5 4.35 26.1 5.16 133.7

2
Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

Fan Motor 230 V 0.8 0.18 0.8 0.18 1 208 V 0.7 0.15 0.7 0.15 1

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating:

80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

Rating Conditions

70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB

I - 112

SM830082

1. Specifications

Indoor model: UH2442 / Outdoor model: CH2442 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.18 - 0.16 2-2 0.18 - 0.16 0.9 - 0.8

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 9.7 - 10.4 2.19 - 2.15 11.1 - 12 2.53 - 2.48 66 - 60 11.5 - 12.1 2.55 - 2.48 12.9 - 13.7 2.89 - 2.81 67.9 - 61.8

230 - 208 V / 1 phase / 60 Hz 0.9 - 0.8 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

q Heating

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.16 - 0.14 2-2 0.16 - 0.14 0.7 - 0.7

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 10.4 - 10.9 2.31 - 2.24 11.2 - 12.2 2.49 - 2.47 66 - 60 12 - 12.5 2.65 - 2.55 12.8 - 13.8 2.83 - 2.8 67.7 - 61.7

230 - 208 V / 1 phase / 60 Hz 0.7 - 0.7 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

Cooling: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature 70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB 80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

SM830082

I - 113

1. Specifications

Indoor model: UH3642 / Outdoor model: CH3642 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW 0.22 - 0.2 2-2 0.22 - 0.2 1-1

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 12.3 - 13.7 2.77 - 2.63 15.4 - 16.8 3.45 - 3.38 95 - 86 15.1 - 15.7 3.35 - 3.17 18.2 - 19.6 4.03 - 3.92 98 - 89

230 - 208 V / 1 phase / 60 Hz 1-1 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Starting amperes

q Heating

Indoor Unit

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 15.5 - 17 3.21 - 3.24 14.7 - 16 3.32 - 3.29 95 - 86 18.2 - 19.6 3.78 - 3.76 17.4 - 18.6 3.89 - 3.81 97.9 - 88.8

2
Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

Fan Motor

230 - 208 V / 1 phase / 60 Hz 0.9 - 0.8 0.21 - 0.18 0.9 - 0.8 0.21 - 0.18 2-2 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

Heating: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB

I - 114

SM830082

1. Specifications

Indoor model: KH2442 / Outdoor model: CH2442 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.08 - 0.07 1-1 0.08 - 0.07 0.4 - 0.4

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 9.0 - 9.6 2.04 - 1.98 11.0 - 11.7 2.46 - 2.44 66 - 60 10.3 - 10.9 2.30 - 2.22 12.3 - 13.0 2.72 - 2.68 68 - 62

230 - 208 V / 1 phase / 60 Hz 0.4 - 0.4 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

q Heating

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW Starting amperes A 0.08 - 0.07 1-1 0.08 - 0.07 0.4 - 0.4

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 10.0 - 10.9 2.24 - 2.19 11.1 - 11.7 2.52 - 2.44 66 - 60 11.3 - 12.2 2.50 - 2.43 12.4 - 13.0 2.78 - 2.68 68 - 62

230 - 208 V / 1 phase / 60 Hz 0.4 - 0.4 0.9 - 0.9 0.18 - 0.17 0.9 - 0.9 0.18 - 0.17 1-1

Cooling: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature 80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

Heating: Rating Conditions : Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature 70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB

SM830082

I - 115

1. Specifications

Indoor model: KH3642 / Outdoor model: CH3642 q Cooling

Indoor Unit Fan Motor Performance at A Rating conditions kW A Full load conditions kW 0.10 - 0.09 1-1 0.10 - 0.09 0.5 - 0.5

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 12.6 - 13.2 2.83 - 2.69 15.4 - 16.8 3.45 - 3.38 95 - 86 14.9 - 15.5 3.29 - 3.12 17.7 - 19.1 3.91 - 3.81 97.5 - 88.5

230 - 208 V / 1 phase / 60 Hz 0.5 - 0.5 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Starting amperes

q Heating

Indoor Unit

Outdoor Unit Complete Unit Fan Motor Compressor 230 - 208 V / 1 phase / 60 Hz 15.5 - 16.8 3.40 - 3.38 14.7 - 16.0 3.32 - 3.29 95 - 86 17.8 - 19.1 3.86 - 3.81 17 - 18.3 3.78 - 3.72 97.5 - 88.5

2
Performance at A Rating conditions kW A Full load conditions kW Starting amperes A

Fan Motor

230 - 208 V / 1 phase / 60 Hz 0.5 - 0.5 0.10 - 0.09 0.5 - 0.5 0.10 - 0.09 1-1 1.8 - 1.8 0.36 - 0.34 1.8 - 1.8 0.36 - 0.34 2-2

Cooling: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

80 F DB / 67 F WB 95 F DB 80 F DB / 67 F WB 115 F DB

Heating: Rating Conditions

: Indoor Air Temperature Outdoor Air Temperature Full Load Conditions : Indoor Air Temperature Outdoor Air Temperature

70 F DB / 60 F WB 47 F DB / 43 F WB 80 F DB / F WB 45 F DB / 35 F WB

I - 116

SM830082

2. Processes and functions

2. PROCESSES AND FUNCTIONS


2-1 Room Temperature Control ...................................................................... II - 2 (A)Cooling ................................................................................................ II - 2 (B)Heating ................................................................................................ II - 3 Cold Draft Prevention (Heating Cycle) ...................................................... II - 4 Automatic Fan Speed (Indoor Unit) .......................................................... II - 5 (A)Cooling ................................................................................................ II - 5 (B)Heating ................................................................................................ II - 5 Outdoor Fan Speed Control ...................................................................... II - 6 (A)Cooling ................................................................................................ II - 6 (B)Heating ................................................................................................ II - 6 Freeze Prevention (Cooling) ..................................................................... II - 7 Condensing Temperature Control (Cooling) ............................................. II - 8 Overload Protection (Heating) .................................................................. II - 9 Discharge Temperature Control (Cooling and Heating) ........................... II -10 Auto. Mode for Automatic Heating/Cooling Switching .............................. II -11 Defrosting Control, Outdoor Heat Exchanger Coil (Heating) .................... II -13 4-Way Valve, Solenoid Control ................................................................. II -14 (A) Normal Control Mode .......................................................................... II -14 (B) AUTO Control Mode ........................................................................... II -15 Automatic Restart after Power Interruption ............................................... II -15 Electronic Refrigerant Control Valve ......................................................... II -16 Compressor Discharge Gas Temperature ................................................ II -16 (A)Cooling ................................................................................................ II -16 (B)Heating (Except During Defrosting) ..................................................... II -16 Compressor Current Detection Circuit ...................................................... II -17 Electronic Refrigerant Control Valve Control ............................................ II -18 Voltage Detection Control ......................................................................... II -19

2-2 2-3

2-4

2-5 2-6 2-7 2-8 2-9 2-10 2-11

Section

2-12 2-13 2-14

2-15 2-16 2-17

SM830082

II - 1

2. Processes and functions

2-1 Room Temperature Control


The Unit adjusts room temperature by turning the outdoor units compressor ON and OFF. This process is controlled by the thermostat located in the remote control unit. The figures on this and the next pages show how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 1 shows about the cooling cycle, and Fig. 2 shows about the heating cycle.

(A) Cooling
THERMO. OFF (THERMO. ON) BODY SENSOR T+2 F SET TEMP. T F T2 F MORE THAN 5 MINUTES 3 MINUTES COMPRESSOR 1 OUTDOOR FAN (H OR M) ON OFF

(THERMO. OFF) ROOM TEMP. THERMO. ON

Section

5 MINUTES ON

MORE THAN 3 MINUTES OFF

MORE THAN 5 MINUTES ON

ON

OFF

ON

OFF

ON

INDOOR FAN

SET SPEED 1. Refer to 2-4 Outdoor Fan Speed Control


1133_THS_I

Fig. 1 Chart Summary and Explanations

u u u u u

Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode (HEAT, COOL, or FAN) during the cooling cycle, the control circuit stops the compressor for 3 minutes. For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off, the compressor is not controlled by the room sensor. Thermo ON: When room temperature rises 2F (4F when set on body sensor) above the set temperature T, (T+2F or T+4F when set on body sensor): Compressor ON

Thermo OFF: When the room temperature is 2F below the set temperature T: Compressor OFF

II - 2

SM830082

2. Processes and functions

(B) Heating
REMOTE CONTROL SENSOR (Only for wireless remote controller) SET. +2F SETTING TEMP. SET. 2F

THERMO. ON THERMO. OFF

THERMO. ON THERMO. OFF THERMO. ON

THERMO. OFF BODY SENSOR +2F SET TEMP.+7F SHIFT 2F SET TEMP. MORE THAN 5 MINUTES ON THERMO. ON THERMO. ON

THERMO. OFF THERMO. ON

5 MINUTES COMPRESSOR 1 OUTDOOR FAN (H OR M) 2 INDOOR FAN 2 STANDBY OFF ON

3 MINUTES OFF

MORE THAN 3 MINUTES OFF ON

Section

OFF

ON 3 SECONDS

OFF

ON

OFF

ON

OFF

L LL L

SET SPEED

LL

SET SPEED

LL

SET SPEED

OFF

ON

OFF

ON

OFF

ON

OFF

(88F) INDOOR HEAT EXCH. COIL 81F TEMP. 77F E2 SOLENOID COIL (4-WAY) TEMP. OPERATION OFF BUTTON

2
ON (REVERSING CYCLE)

ON

3
1134_THS_I

1. Refer to 2-4 Outdoor Fan Speed Control 2. Refer to 2-2 Cold Draft Prevention (Heating)

Chart Summary and Explanations


u u u u Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode (HEAT, COOL or FAN) during the heating cycle, the control circuit stops the compressor for 3 minutes. For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off, the compressor is not controlled by the room sensor.

Fig. 2

When set on remote control sensor Thermo ON: When room temperature is 2F below the set temperature T. Compressor ON Thermo OFF: When the room temperature is 2F above the set temperature T, (T+2F) Compressor OFF When set on body sensor NOTE: In case of Body sensor, operating temperature is shifted to setting temperature +7F.
SM830082

II - 3

2. Processes and functions

2-2 Cold Draft Prevention (Heating Cycle)


The cold draft prevention function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coils have warmed up. u STANDBY shows on the remote controller when the indoor fan speed is LL (very low) or OFF. This condition occurs in the following 3 cases: During Thermo OFF (refer to 2-1 B). Room Temperature Control, Heating) During the defrosting operation (refer to 2-10 Defrosting Control, Heating) Until either the coil temperature E2 reaches 81F or when a maximum of 6 minutes has past. The indoor fan motor operates in L instead of LL for 3 seconds as it starts to give the fan an initial boost.

Section

1
INDOOR UNIT COIL TEMP. E2 (F)

92 MAX. 6 MINUTES 88

81

77

50

SET FAN SPEED

AUTO OR H M L

LL LL LL

LL/OFF LL/OFF LL/OFF

LL LL LL

L L L

M M L

H M L

STANDBY INDICATOR

STANDBY APPEARS LL= Very low speed L= Low speed M= Medium speed H= High speed

1135_THS_I

4
Chart Summary and Explanations
u u u

Fig. 3

The main idea of this chart is to show that the indoor fan speed increases and gets closer to the set fan speed as the coil temperature E2 rises. The indoor units coil temperature is taken from sensor E2 located in the middle of the indoor heat exchange coil. The dotted line shows that the indoor fan motor is OFF. When the temperature at sensor E2 falls below 50F, the indoor fan motor stops running.

II - 4

SM830082

2. Processes and functions

2-3 Automatic Fan Speed (Indoor Unit)


By pressing the FAN SPEED button on the remote controller, the fan speed can be set at one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed will be automatically adjusted to the room temperature as the two charts shown below. (A) Cooling

ROOM TEMP. (deg) +3 +2 +1 SET TEMP.

Section
INDOOR FAN SPEED H : High L : Low M : Middle
1923_M_S

1
Fig. 4

Chart Explanations and notes


u When the fan speed changes, it keeps the speed step for at least 3 minutes, even if the temperature changes to another speed step during the time.

(B) Heating
ROOM TEMP. (deg) SET TEMP. 2 4

INDOOR FAN SPEED H : High L : Low M : Middle

4
H M L M H
1924_M_S

Fig. 5 Chart Explanations and notes


u When the fan speed changes, it keeps the speed step for at least 1 minute, even if the temperature changes to another speed step during the time.

SM830082

II - 5

2. Processes and functions

2-4 Outdoor Fan Speed Control


To optimize the performance of air conditioner, the outdoor fan speed is selected automatically according to the outdoor temperature. u Note that in both Cooling and Heating modes, the fan comes on at first at high speed (H mode) for 5 seconds. Since outdoor conditions sometimes make it difficult for the fan to start, this sudden surge of power may be necessary. The outdoor fan operates in H mode for 3 minutes after the compressor stops (excluding defrosting operation period). Charts below show how the outdoor fan speed changes with the change in outdoor temperature.

Section

(A) Cooling

OUTDOOR TEMPERATURE (F)

Outdoor unit coil temperature [C2] or more 77F 32F or more, less than 77F

Outdoor fan motor (FMo) H M L

77 M 32 L

less than 32F

Fig. 6

3
(B) Heating
OUTDOOR TEMPERATURE (F)

Outdoor coil temperature [C2] or more 57F

Outdoor fan motor (FMo) M H

less than 57F

57

Fig. 7

II - 6

SM830082

2. Processes and functions

2-5 Freeze Prevention (Cooling)


Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost build up on the coil blocks cool air circulation from the indoor unit's fan.

MIN. VALUE OF EITHER E1 OR E2 INDOOR UNIT TEMP. 34 33 32 31 (F) ELECTRONIC REF. CONTROL VALVE SIGNAL COMPRESSOR CONTINUOUS DETECTION FOR 2 MINUTES OPEN OPEN MINIMUM 3 MINUTES

Section

ON

ON
1925_THS_I

Fig. 8

Note: Freeze prevention is controlled by the temperature at the indoor heat exchanger coil as sensed by either sensor E1 (located at the entrance of the coil) or sensor E2 (located on the middle of the coil). Freeze prevention cycle is controlled by the lower temperature sensed at either of the two sensors.
Chart Explanations and notes
u u This chart shows when the electronic refrigerant control valve opens to regulate the temperature of the indoor unit coil to prevent freezing. If the refrigerant control is not effective and the temperature continues to drop and stays below 31F for 2 minutes continuously, the control circuit stops the compressor. The compressor does not start again until the temperature rises above 34F. The compressor stops for 3 minutes minimum.

SM830082

II - 7

2. Processes and functions

2-6 Condensing Temperature Control (Cooling)


Condensing temperature is controlled by the outdoor heat exchanger coil temperature as sensed by sensor C2.
140 OUTDOOR UNIT COIL TEMP. C2 (F)

131

OUTDOOR FAN SPEED ELECTRONIC REF. CONTROL VALVE

H, M or L

Section

FORCED H

H, M or L

OPEN
1926_THS_I

Fig. 9

Chart Explanations and notes

u u u

This chart shows how the outdoor fan speed and the electronic refrigerant control valve react to coil temperature to control condensing temperature. Sensor C2 is located in the middle of the outdoor unit heat exchange coil. When C2 rises above 140F the electronic refrigerant control valve opens at 50 steps/30 seconds, and the outdoor fan speed is forced to change to high (H) until C2 falls below 131F.

II - 8

SM830082

2. Processes and functions

2-7 Overload Protection (Heating)


This function prevents the air conditioner from overloading.

(F) 147 144 140 INDOOR UNIT COIL TEMP. (E2) 138 131 127 OVERLOAD PROTECTION FUZZY CONTROL

OVERLOAD PROTECTION FUZZY CONTROL

Section

1
ELECTRONIC REF. CONTROL VALVE OPEN OPEN START UP COMPENSATION OFF OUTDOOR FM H OR M H L H OR M
1927_THS_I

Fig. 10 Chart Explanations and notes


u u u u u This chart shows how the outdoor fan speed and the electronic refrigerant control valve react to coil temperature to keep the indoor heat exchanger coil from overloading. When sensor E2 rises above 140F the electronic refrigerant control valve opens at 50 steps/30 seconds until E2 falls below 138F. Sensor E2 is located in the middle of the indoor unit heat exchange unit. When sensor E2 rises above 144F, the control circuit stops the outdoor fan motor till the temp. drops to 131F Fuzzy control controls the electronic refrigerant control valve.

SM830082

II - 9

2. Processes and functions

2-8 Discharge Temperature Control (Cooling and Heating)


This function prevents the compressor motor from burnout by overheating.
(42 Type) (24, 36 Type) 275 257 239 235 DISCHARGE GAS TEMP. (F) 230 221 239 221 203 200 194 185

Section

OUTDOOR FAN SPEED COMPRESSOR ELECTRONIC REF. CONTROL VALVE (DISCHARGE TEMP.)

H OR M

L ON OPEN

H OR M

OPEN TRIP IS OPERATED.


1928_THS_I

2
Chart Summary and Explanations
u u Discharge temperature is sensed by TH8 (discharge gas sensor).

Fig. 11

When the temperature rises above 203F (24, 36 Type) the electronic refrigerant control valve opens at 50 steps/30 seconds until the temperature falls below 200F (24, 36 Type) . During HEATING operation, when the temperature rises above 221F (24, 36 Type), the control circuit stops the outdoor fan motor until the temperature falls below 194F (24, 36 Type). Please note that this control does not function during COOLING operation. For both COOLING and HEATING modes, if the temperature reaches 239F (24, 36 Type) the operation shuts down and alarm P3 appears on the remote controller. The outdoor fan speed is controlled on discharge temp. at heating mode.

u u

II - 10

SM830082

2. Processes and functions

2-9 Auto. Mode for Automatic Heating/Cooling Switching


u When the AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to the COOLING or HEATING mode to maintain the desired temperature. Room temp. ] Set temp. COOLING Room temp. < Set temp. HEATING This means that if the room temperature is higher or equal to the set temperature, COOLING operation starts. If the room temperature is lower than the set temperature, HEATING operation starts.

A COOLING SELECTION TEMP. +5 deg SHIFT SET TEMP. +4 deg

Section

1
B

REMOTE CONTROLLED SET TEMP.

SHIFT SET TEMP. 4 deg HEATING SELECTION TEMP. 6 deg C

2
HEATING COOLING HEATING
1142_THS_I

Fig. 12

SM830082

II - 11

2. Processes and functions

Chart summary and Explanations


u This chart shows how the Operation Mode (COOLING or HEATING) is determined by the microprocessor taking the room temperature into consideration. It also shows the temperature points at which the cooling or heating mode is switched, when the AUTO mode is selected. After operation starts, the set temperature shifts automatically by +4 deg. at cooling and by -4 deg. at heating. For example, if cooling is selected, the set temperature changes from 68F to 72F. (The display of the remote controller remains 68F.) The change of the operation mode (heating to cooling, cooling to heating) by the change of the room temperature during the operation is as follows. Heating to Cooling; Room temp. Shifted temp +1.0 deg. Cooling to Heating; Room temp. Shifted temp -2.0deg. For example, if the room temperature rises above 73F (=72+1) during the cooling operation at the room temperature 68F set by the remote controller, the operation changes to cooling. When the room temperature lowers below 63F (=65-2) thereafter, the operation changes to heating again. u In heating operation, using the body sensor, room temperature control is designed so that room air temp. is sensed as 8 deg. lower than suctioned air at indoor unit taking into account of the temperature gap between upper part and lower part of the room. Within 10 minutes after the compressor turns OFF, the operation does not change to cooling (heating), even when the room temperature changes from C to A (A to C). When switching from cooling (heating) to heating (cooling), the actuation of the 4 way valve will delay about 30-50 seconds after the compressor turns ON.

Section

1
u u

II - 12

SM830082

2. Processes and functions

2-10

Defrosting Control, Outdoor Heat Exchanger Coil (Heating)

When the outdoor temperature is low, frost may form on the outdoor heat exchanger coil. When this occurred, the defrosting system operates. The microprocessor in the outdoor unit monitors the relationship between the temperature of the outdoor heat exchanger coil and the outdoor temperature so it can defrost when necessary.
Flow of Defrosting OUTDOOR COIL TEMP. C1 (F) Y RELEASE OF DEFROSTING RANGE 50 OUTDOOR AIR TEMP. (F) 50 X 27 18 Detecting the frost 4 Stand by time for defros: 25 minutes Either continuous 8 minutes or cumulative 60 minutes are required to detect frost in the Frosting range. The area below the heavy line is the frost detection area.

Heating operation

No counting time for detecting frost : 15 minutes

7.3

Section

Defrosting

Refer to time chart. *Minimum continuous operating time by defrosting is 48 minutes (= 15 + 8 + 25). Occurs either when the temperature of C1 (the outdoor heat exchanger coil) has reached 50F or above, or when the maximum defrosting time (9 minutes) has elapsed.
1143_THS_I

2
Fig. 13

Release of defrosting

Time Chart for Defrosting


1 MINUTE MAX. 9 MINUTES 1 MINUTE

COMPRESSOR

ON

ON

ON

SOLENOID COIL (4 WAY VALVE)

ON

ON

OUTDOOR FAN (H OR L)

ON

ON

INDOOR FAN (SET SPEED)

OFF OR LL

OFF OR LL

STANDBY INDICATOR Defrosting Start

STANDBY APPEARS Release of Defrosting

0442_M_S

Fig. 14

u u

During the defrost cycle, STANDBY appears on the remote controller. *......Cold Draft Prevention may operate occasionally
SM830082

II - 13

2. Processes and functions

2-11 4-Way Valve, Solenoid Control


The basic function of the 4-way valve is to direct the refrigerant in the correct direction according to the Operation Mode (COOLING or HEATING) selected. The following two charts show conditions of the controls and functions listed in the left hand column when the solenoid is ON or OFF. Chart (A) on this page shows the relationships when the temperature control is in NORMAL mode, and Chart (B) on the next page shows the relationships when the remote controller is set to AUTO mode. (A) Normal Control Mode

POWER SOURCE OFF

ON

Section

OPERATION BUTTON

ON

OFF

ON

1
COOL MODE BUTTON HEAT COOL HEAT 2 3 MINUTES TURN ON TURN OFF OFF ON THERMO OFF THERMO OFF THERMO THERMO ON ON OFF 2 1 SOLENOID COIL (4-WAY VALVE) OFF ON 1 OFF 2. . . More than 3 minutes 1 ON
0443_M_S

HEAT

COMPRESSOR

ON

ON

OFF 2

ON

1. . . More than 5 minutes

Fig. 15

Chart Summary and Explanations

u u u

For the first 3 minutes after power is applied, the 4way valve remains OFF and the compressor will not operate, even if the ON button is pushed. If the 4way valve is turned OFF with the compressor operating, the air conditioner operates in COOLING mode. See Table below. If the 4way valve is turned ON with the compressor operating, the air conditioner operates in HEATING mode. See Table below. Operation Mode COOLING HEATING 4-way valve solenoid OFF ON Compressor ON

II - 14

SM830082

2. Processes and functions

(B) AUTO Control Mode

POWER SOURCE OFF

ON

OPERATION BUTTON MORE THAN 10 MINUTES (THERMO. OFF) AUTO COOL MODE CONTROL HEAT

ON MORE THAN 10 MINUTES (THERMO. OFF)

COOL HEAT HEAT THERMO. OFF THERMO. ON 3 MINUTES MORE THAN 3 MINUTES OFF ON OFF ON OFF ON

COMPRESSOR

OFF

ON

Section
MORE THAN 30 50 SECONDS SOLENOID COIL (4-WAY VALVE) OFF ON OFF MORE THAN 30 50 SECONDS ON
0445_M_S

Fig. 16

When the Compressor has stopped while in AUTO mode, the 4-way valve switches on (heating) or off (cooling) within 1 minute according to the following conditions:

Compressor has stopped under the operation of AUTO mode condition.

3
4-way valve delays its switching for 30 50 seconds after compressor has been turned ON.
0446_M_S

Fig. 17

2-12 Automatic Restart after Power Interruption


This air conditionner has a power failure recovery function.

SM830082

II - 15

2. Processes and functions

2-13 Electronic Refrigerant Control Valve


u This valve allows very precise and smooth control of the amount of refrigerant flow in the system. Since the valve is operated by a step motor, the control circuits can open or close it in very exact amounts, so the degree of heating or cooling can be changed by just a little, or changed very quickly or slowly. (Completely close 0 step) (Full open................ 480 step)

Model
24 type 36 type 42 type

Min. open HEAT 100 step 90 step 100 step COOL 100 step 90 step 100 step

Max. open

480 step

Section

u Fuzzy Control Fuzzy Control is a controlling system to control electronic refrigerant control valve using fuzzy logic. It regulates the functions of heating and cooling, as well as some of the processes inside the unit, by taking account of many different conditions of temperature, fan speed, etc. These control circuits work automatically to send just the right amount of refrigerant through the Electronic Refrigerant Control Valve.

2-14 Compressor Discharge Gas Temperature


(A) Cooling
68 77 55 or below 104 176 57 61 104 194 79 82 81 95 140 212 84 90 97 109 158 221

Indoor temp. (F) Outdoor temp. (F) Compressor discharge gas temp. (F)

(B)

Heating (Except During Defrosting)


64 70 72 77 79 86 52 70 32 or below 34 50 52 70

Indoor temp. (F)

Outdoor temp. (F) Compressor discharge gas temp. (F)

32 or below 34 50 32 or below 34 50

104 176 122 194 122 194 122 212 140 221 122 194 140 212 158 221

u u

Operate the unit at least 30 minutes to stabilize the discharge temperature. The above discharge temperature was measured with a 15m tubing length. The temperature may vary with tubing length.

II - 16

SM830082

2. Processes and functions

2-15 Compressor Current Detection Circuit


u The Compressor Current Detection Circuit detects the compressor current and, depending on the current range, can stop the compressor motor so it will not be damaged by overcurrent. u Overcurrent can be caused by several factors, particularly mechanical seizing of the compressor or liquid backflow. Either of these conditions can hold the compressor to run, and thus drawing so much current that the motor can burn out.
Comp. Amps.(A) Locked Comp. Cut-off Range Is Is 1.4 Overload Protection Range 1.17 Normal Operation Range

Is Rated Current value

Section
0447_M_S

Fig. 18
Rated Current Value ls (A) 17.1 27.5 34.7 Overload Protection ls x 1.17 (A) 20.0 32.2 40.6 Locked Compressor Cut-off Is x 1.4 (A) 23.9 38.5 48.6

Outdoor Model CH2442 CH3642 CH4242

Chart Summary and Explanations


u Overload Protection When the detected current is 1.17 1.4 times greater than the rated current value (Is) and continues for 30 seconds, both compressor and outdoor fan stop (Thermostat OFF). After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if the condition mentioned above repeats twice within 30 minutes, the remote controller displays the alarm message H01, compressor overload. u Locked Compressor Cut-off When the detected current is 1.4 times greater than the rated current value (ls) and continues for 2 seconds, both compressor and outdoor fan stop (Thermostat OFF). After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, if the condition mentioned above repeats twice, the remote controller displays the alarm message H02, compressor locked. u Failure of Compressor Current Detection When the Compressor Current Detection Circuit fails to detect the compressor current within 2 seconds after compressor starts, both compressor and outdoor fan stop (Thermostat OFF). After 3-minute pause, if the air conditioner is ready for Thermostat ON, it starts again. However, when the circuit fails to detect the current twice in a row, the remote controller displays alarm message H03, Failure of compressor Current Detection.

SM830082

II - 17

2. Processes and functions

2-16

Electronic Refrigerant Control Valve Control

The circulation volume of the refrigerant is controlled by a pulse type electronic control valve. When the power is switched ON, the opening degree of the electronic control valve is controlled between 90 and 480 steps after setting the initial step at the time when the thermostat is ON. Contents and Order of control
Cooling Start Heating Start

Discharge gas temperature control

Discharge gas temperature control

Section

Outdoor unit coil temperature control

High load prevention control

Freeze prevention control

Heating start up control

Refrigerant flow distribution control

Refrigerant flow distribution control

Discharge gas target temperature control (Fuzzy control)

Discharge gas target temperature control (Fuzzy control)

* * Repeat control in accordance with the priority order.

*
0451_M_S

Even though the operation is performed every 30 seconds, the control of discharge gas temperature, high load prevention, outdoor unit coil temperature and freeze prevention activates when it occurs. (1) Refrigerant flow distribution control At the control of flexible combination (a plural number of indoor units are set), the opening degree of the electronic control valve is controlled by the indoor unit coil temperature. Cooling: indoor unit coil E2 temperature (located at the middle of coil) Heating: indoor unit coil E1 temperature (located at the outlet of coil) (2) Fuzzy control (optimal refrigerant flow rate control)

By outputting the fuzzy estimation result corresponding to the fuzzy input variables (the indoor unit coil temp., the deviation between the actual discharge gas temp. and the target discharge gas temperature calculated from the outdoor unit coil temperature and the change thereof), the electronic refrigerant valve is controlled so that the unit can perform its maximum ability in accordance with the indoor and outdoor temperature conditions at the operation.
SM830082

II - 18

2. Processes and functions

2-17

Voltage Detection Control

When the power voltage falls below 160 V or rises above 260 V, operation lamp and stand-by lamp flash alternately to protect the compressor and electrical components.

Section

SM830082

II - 19

3. Electrical data

3. ELECTRICAL DATA
3-1 Indoor Units (Electric Wiring Diagram, Schematic Diagram) .................. 4-Way Air Discharge Semi-concealed Type .......................................... Ceiling Mounted Type ............................................................................. Concealed Duct Type ............................................................................. Concealed Duct High Static Pressure Type ........................................... Outdoor Units (Electric Wiring Diagram, Schematic Diagram) ............... III III III III III III 2 2 4 6 8 12

3-2

SM830082

III - 1

Electric Wiring Diagram

3
3-1

To Outdoor Unit Power Control Line Line GRN/YEL 49FI LM LS PNK BRN BLK YEL ORG VLT WHT GRY GRY PNK GRY GRY BLK GRN/YEL S 1 2 2P (BLU) TR1 S 1 2 3 4 5 6 7 8 9 9P P 1 2 3 4 5 6 7 8 9 (WHT) PNK BRN FS S 1 2 P 1 2 S 1 2 3 2P P 1 2 3 3P (GRN) (WHT) Earth Terminal

Indoor Units

Terminal 2 G U1 U2 Plate (5P)

FMI

Earth Terminal RC1 WHT BLK WHT WHT BRN BRN RED RED ORG ORG BLK YEL ORG GRY GRY PNK GRY ORG BRN BRN

RED

BRN

PNK BLU

GRN/YEL

GRY BLK

BRN

GRN/YEL Earth Terminal


1 3 1 3

BLK BLK

BLK BLK

BLK BLK

BLK BLK

ORG RED YEL BLK GRY

RED RED

4-Way Air Discharge Semi-concealed Type : XH2442, XH3642, XH4242

DP

MOV
TH1 TH2 TH3 TH4 Earth Terminal

GRN/YEL

Earth Terminal

3. Electrical data

SM830082

W 854-2-5268-930-00-1 (X)

GRN/YEL

III - 2
1 3 1 3 1 3 5 7 9 1 2 3 1 2 3 4 5 6 1 3 1 3

1 2

OC (BLU)

RC (BLU)

RS2 (WHT)

VCC (WHT)

FM (WHT)

T20 (GRY)

PNL (GRN)

FS (RED)

LS (WHT)

LM (GRN)

1 3

RS1 (BLK)

Controller (CR-TH2442)
(YEL) Temp Room (RED) 26H
1 3

(BLU) WL
1 2 1 2 1 2 1 3

(RED) E1 Coil (WHT) T6

(BLK) E2 Coil

(BRN) E3 Coil

(YEL) T10
1 2 3 4 5 6

(BLU) DP
1 3

1 2 3 4

1 2 3 4 5

3. Electrical data

4-Way Air Discharge Semi-concealed Type : XH2442, XH3642, XH4242

Schematic Diagram
CN2 1 TH RCU 5P-1 1 F1(5A) T20 1 TR1 1X 5P-2 8 1 2 3 4 5 6 1 3 1 FM 1 DP 3 5 7 1 LM 1 26H 1 FS 3 3 RS2 3 1 3 1 2 3 4 RC

CR
1 2 3 4 5 6 1 2 3 4 5 LS 1 3 1 PNL FS Room Temp Coil E1 2 3 Room Thermistor 1 2 1 2 1 2 1 3 TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4 1 2 LSW

T10 WL

T6 VCC

MOV

2X

RY2

RY1

RY4

49FI

9 3X

5 H

6 HH

7 HT 1

LL L

Coil E2 1X 2X 3X RY1 RY2 RY4 Coil E3

FMI
1 RC1 2

DP

LM

3 F2(5A)

DC12V

OC

1 2 5P5PU2 U1 To Outdoor Unit

Symbols
FMI MOV 49FI RC1 TR1 DP FS TH1 TH2 TH3 TH4 F1, 2

Description
Indoor Fan Motor Motor Operated Valve Indoor Motor Thermal Protector Running Capacitor Power Transformer Drain Pump Float Switch Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3) Fuse

Symbols
1X~3X RY1, 2, 3 CR LSW LM (RCU)

Description
Auxiliary Relay Indoor Controller Limit Switch Auto Louver Motor Remote Control Unit (Optional Parts)

(TH)

Room Thermistor Terminal Plate Connector Terminal

S 854-2-5268-930-00-1 (X)

SM830082

III - 3

Electric Wiring Diagram

To Outdoor Unit Power Control Line Line GRN/YEL Earth Terminal

1
LM BLK Connecter 2P (BLU) TR1 Connecter 2P (BLK) S 1 2 P 1 2 LSW PNK BRN S 1 2 3 4 5 6 7 8 9 Connecter P 1 2 3 4 5 6 7 8 9 9P (WHT) PNK BRN BLK YEL ORG VLT WHT GRY GRY S
1 2

Terminal 2 G U1 U2 Plate (5P)

FMI MOV

Earth Terminal

GRN/YEL

RC1 WHT BLK WHT WHT BRN BRN RED RED ORG ORG BLK BLK BLK YEL ORG GRY GRY BRN BRN PNK GRY
1 3 1 3

RED

BRN

PNK BLU

GRN/YEL

49FI

1 2 1 3 5 7 9

1 3 1 3

1 2 3 4 5 6

1 3 1 2 3 4 5 6

BRN

1 3

Ceiling Mounted Type : TH2442, TH3642, TH4242

OC (BLU)

RC (BLU)

RS2 (WHT)

VCC (WHT)

FS (RED)

LL L H HH S FM (WHT)

T20 (GRY)

T10 (YEL)

LM (GRN)

LS (WHT)

1 3

RS1 (BLK)

Controller (CR-TH2442)
(RED) 26H
1 3 1 2 3 1 2 3 4 1 2

(GRN) PNL (YEL) T10

(YEL) Temp Room

(RED) E1 Coil
1 2

(BLK) E2 Coil
1 2

(BRN) E3 Coil
1 3

(BLU) DP
1 3

ORG

BLK BLK

BLK BLK

BLK BLK

BLK BLK

BLU WHT

Connecter 2P (WHT) S 1 2 TH1 TH2 TH3 TH4

Earth Terminal

3. Electrical data

SM830082

W 854-2-5268-923-00-1 (T)

GRN/YEL

ORG RED YEL BLK GRY


1 2 3 4 5

III - 4

T6 (WHT)

3. Electrical data

Ceiling Mounted Type : TH2442, TH3642, TH4242

Schematic Diagram
CN2 1 TH RCU 5P-1 1 SUP 1X 5P-2 8 F1(5A) T20 1 TR1 1 2 3 4 5 6 1 3 1 LL L H HH 1 3 5 7 LM 1 DP 1 26H 1 3 2 1 3 1 2 3 3 4 5 H 6 HH 7 HT 1 LL L PNL RS2 3 1 3 1 2 3 4 RC

CR
1 2 3 4 5 6

T10 WL

VCC T6

2X

RY1

RY2

RY4

49FI

1 2 3 4 5

MOV

9 3X

LS FS Room Temp Coil E1 Coil E2

1 3 1 2 1 2 1 2 1 3

LSW Room Thermistor TH1 Indoor Coil E1 TH2 Indoor Coil E2 TH3 Indoor Coil E3 TH4

FMI
1 RC1 2

LM

DP 3X 2

1X 2X RY1 RY2 RY4

Coil E3

3 F2 (5A)

DC12V

OC

1 2 5P5PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1, 2 LM TR1 1X~3X RY1, 2, 4 MOV FS LSW TH1

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Auto Louver Motor Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Float Switch Limit Switch Room Thermistor

Symbols
TH2 TH3 TH4 CR (RCU)

Description
Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3) Indoor Controller Remote Control Unit (Optional Parts)

(TH)

Room Thermistor Terminal Plate Connector Terminal

S 854-2-5268-923-00-1 (T)

SM830082

III - 5

Electric Wiring Diagram

To Outdoor Unit Power Control Line Line GRN/YEL

1
TH1
Connecter 2P (BLU) PNK BRN BLK YEL ORG VLT WHT GRY GRY

Terminal 2 G U1 U2 Plate (5P) TH2 TH3 TH4

FMI MOV
RC1 TR1
BRN BRN PNK

49FI

GRN/YEL

S 1 2
Connecter 9P (WHT)

S 1 2 3 4 5 6 7 8 9 P 1 2 3 4 5 6 7 8 9

DP

Concealed Duct Type : UH2442, UH3642

RED

WHT

PNK BLU

WHT BLK

WHT WHT

BRN BRN RED RED ORG ORG

BLK YEL ORG VLT

ORG

GRY GRY

BLK BLK

BLK BLK

BLK BLK

BLK BLK

ORG RED YEL BLK GRY

1 2 1 2 3 1 3 5 7 9 1 3 1 2

1 3 1 3

1 2 3 4 5 6

1 2

1 2

1 3

BLK BLK

1 2 3 4 5

1 3

OC (BLU)

RC (BLU)

RS2 (WHT)

VCC (WHT)

PNL (GRN)

FM (WHT)

T20 (GRN)

Room Temp (YEL)

Coil E1 (BLK)

Coil E2 (RED)

Coil E3 (BRN)

T6 (WHT)

FS (RED)

DP (BLU)

1 3

RS1 (BLK)

Controller (CR-TH2442)
E
1 2 3 4 5 6

(YEL) T10

(BLU) WL
1 2 3 4

GRN

W 854-2-5268-940-00-1 (UH1242)

RED RED
1 3

GRN/YEL

FS

III - 6

3. Electrical data

SM830082

3. Electrical data

Concealed Duct Type : UH2442, UH3642

Schematic Diagram
CN2 1 TH RCU Terminal Plate (5P) -1 -2 1X 8 TR1 1 2 3 4 5 6 1 3 FM 1 DP 3 5 7 1 3 RS2 1 RS1 F1(5A) T20 1 1 2 3 4 2 1 3 RC

CR
1 2 3 4 5 6

T10

WL

2X

RY2

49FI

VCC T6

1 2 3 4 5 1 3 1 2 1 2 1 2 1 3

MOV

3X

FS

FS

Room Temp Coil E1 PNL Coil E2 Coil E3

TH1 TH2 TH3 TH4

5 H

1 2 3 DP 1X 2X 3X RY2

LL L

HH HT

FMI
1 RC1 F2(5A) 3 9 2

DC12V

OC

1 2 5P5PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1, 2 DP FS TR1 1X~3X RY2 MOV TH1 TH2 TH3 TH4

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Drain Pump Float Switch Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3)

Symbols
CR (RCU)

Description
Indoor Controller Remote Control Unit (Optional Parts)

(TH)

Room Thermistor Terminal Plate Connector Terminal

S 854-2-5268-940-00-0 (UH1242)

SM830082

III - 7

Electric Wiring Diagram

To Outdoor Unit Power Control Line Line GRN/YEL

Terminal U1 U2 1 Plate (4P) 49FI TH1 TH2 TH3 TH4

FMI MOV
Connecter 2P (BLU)

Wall Mounted Type : KH2442

Earth Terminal RC1

LM

S 1 2 TR1
BRN PNK

WHT BLK

RED

WHT

PNK BLU

WHT BLK

WHT WHT

BRN BRN RED RED ORG ORG

BLK

ORG

YEL ORG VLT WHT GRY

RED

BLK BLK

BLK BLK

BLK BLK

BLK BLK

1 2 1 3 1 3 5 7 9 1 2 3 1 3 1 2

1 3 1 3

1 2 3 4 5 6

1 2

1 2

1 3

ORG RED YEL BLK GRY

1 2 3 4 5

OC (BLU) RS2 (WHT) VCC (WHT) FS (RED) PNL (GRN) FM (WHT) T20 (GRN)

RC (BLU)

Room Temp (YEL)

Coil E1 (BLK)

Coil E2 (RED)

Coil E3 (BRN)

T6 (WHT)

LM (GRN)

1 3

RS1 (BLK)

Controller (CR-TH2442)
E
1 2 3 4 5 6

(YEL) T10

(BLU) WL
1 2 3 4

GRN

W 854-2-5268-935-00-0 (KH2442)

WHT BLK

1 3

Connecter 2P (WHT)

S 1 2 P 1 2

GRN/YEL

III - 8

3. Electrical data

SM830082

3. Electrical data

Wall Mounted Type : KH2442

Schematic Diagram
CN2 1 TH RCU Terminal Plate (4P) -1 -2 1X TR1 1 2 3 4 5 6 1 3 FM 1 LM 3 5 7 1 3 1 3 3 4 5 H 6 HH 1 FS RS2 1 RS1 F1(5A) T20 1 1 2 3 4 2 1 3 RC

CR
1 2 3 4 5 6

T10

WL

2X

RY1

VCC T6

1 2 3 4 5

1 2 3 4 5

MOV

3X

Room Temp Coil E1

1 2 1 2 1 2 1 3

TH1 TH2 TH3 TH4

1 2 3 PNL

LL L

Coil E2 Coil E3

FMI

LM

1X RC1 F2(5A) 3 9 3 2 3X RY1 DC12V OC 1 2 4P4PU2 U1 To Outdoor Unit 2X

Symbols
FMI 49FI RC1 F1, 2 LM TR1 1X~3X RY1 MOV TH1 TH2 TH3 TH4

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Auto Louver Motor Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3)

Symbols
CR (RCU)

Description
Indoor Controller Remote Control Unit (Optional Parts)

(TH)

Room Thermistor Terminal Plate Connector Terminal

S 854-2-5268-935-00-0 (KH2442)

SM830082

III - 9

Electric Wiring Diagram

To Outdoor Unit Power Control Line Line GRN/YEL

Wall Mounted Type : KH3642

Terminal U1 U2 1 Plate (4P) 49FI TH1


ORG RED YEL BLK GRY

2
TH2 TH3 TH4

FMI MOV
Connecter 2P (BLU) PNK BRN YEL ORG VLT WHT GRY

Earth Terminal RC1 TR1


BRN PNK

S 1 2
Connecter 8P (WHT)

Connecter 5P (WHT)

BLK

ORG

RED

RED

WHT

PNK BLU

WHT BLK

WHT WHT

BRN BRN RED RED ORG ORG

YEL ORG VLT WHT GRY

BLK BLK

BLK BLK

BLK BLK

BLK BLK

1 2 1 3 1 3 5 7 9 1 2 3 1 3 1 2

1 3 1 3

1 2 3 4 5 6

1 2

1 2

1 3

ORG RED YEL BLK GRY

1 2 3 4 5

OC (BLU)

RC (BLU)

RS2 (WHT)

VCC (WHT)

FS (RED)

PNL (GRN)

FM (WHT)

T20 (GRN)

Room Temp (YEL)

Coil E1 (BLK)

Coil E2 (RED)

Coil E3 (BRN)

T6 (WHT)

LM (GRN)

1 3

RS1 (BLK)

Controller (CR-TH2442)
E
1 2 3 4 5 6

(YEL) T10

(BLU) WL
1 2 3 4

GRN

W 854-2-5268-936-00-0 (KH3642)

WHT BLK
1 3

GRN/YEL

S 1 2 3 4 5 6 7 8 P 1 2 3 4 5 6 7 8

S 1 2 3 4 5 P 1 2 3 4 5

LM

III - 10

3. Electrical data

SM830082

3. Electrical data

Wall Mounted Type : KH3642

Schematic Diagram
CN2 1 TH RCU Terminal Plate (4P) -1 -2 1X TR1 1 2 3 4 5 6 1 3 FM 1 LM 3 5 7 1 3 1 3 3 4 5 H 6 HH FS RS2 1 RS1 F1(5A) T20 1 1 2 3 4 2 1 3 RC

CR
1 2 3 4 5 6

T10

WL

2X

RY1

VCC T6

1 2 3 4 5

1 2 3 4 5

MOV

3X

Room Temp Coil E1

1 2 1 2 1 2 1 3

TH1 TH2 TH3 TH4

1 2 3 LM PNL

LL L

Coil E2 Coil E3

FMI
1 RC1 F2(5A) 3 9 2 7

1X 2X 3X RY1 3 DC12V OC 1 2 4P4PU2 U1 To Outdoor Unit

Symbols
FMI 49FI RC1 F1, 2 LM TR1 1X~3X RY1 MOV TH1 TH2 TH3 TH4

Description
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Auto Louver Motor Power Transformer Auxiliary Relay Auxiliary Relay Motor Operated Valve Room Thermistor Thermistor (Indoor Coil E1) Thermistor (Indoor Coil E2) Thermistor (Indoor Coil E3)

Symbols
CR (RCU)

Description
Indoor Controller Remote Control Unit (Optional Parts)

(TH)

Room Thermistor Terminal Plate Connector Terminal

S 854-2-5268-936-00-0 (KH3642)

SM830082

III - 11

Electric Wiring Diagram


TH6
BLU PNK C1 (BLK) 1 2 BLK BLK BLK BLK WHT WHT 2 OC 1 2P (BLU)

3
3-2 Outdoor Units
1 CH2442

To Indoor Unit

Power Supply

L1 L2 G

To Indoor Unit U1 U2 Terminal 1 2 Plate (2P)

Terminal Plate (5P) 1 1 C2 (RED) 2 Discharge 1 Gas (GRN) 2 L

2 G L1 L2

Earth Terminal 3 SUP 1 3P (BLU)

Controller

TH7 TH8

BRN RED

WHT RED RED E 3P(WHT) CT1 1 3


BRN RED RED RED GRY WHT WHT

GRN/YEL

RED

WHT

3P(BLK) 52C 1 3

9P(WHT) CN019 1 3 5 7 9

3P(YEL) 20S 1 3

3P(RED) 3P(WHT) RS 63PH 1 3 3 1

2P(WHT) VCC 1 2
BRN BRN

BLK

CT

GRN/YEL Earth Terminal

BLK

A BRN

S T

31

ORG GRY

TR AC230V
BRN

52C AC14V

V W

32

BLK

YEL BRN

PNK

WHT BLK
PNK BRN GRY GRY WHT VLT YEL

8 P 1 2 3 4 5 6 7 8 Connector S 1 2 3 4 5 6 7 8 8P (WHT)

BLK

RED

WHT

P 1 2 Connector S 1 2 2P (WHT)

WHT WHT

CM
Earth Terminal

CH

20S

RED WHT

BRN GRY BLK WHT VLT YEL

III - 12
RED 7

BLK

5
RC2

RC1 1Y

PTC

FMO
GRN/YEL

63PH 49FO

W 854-2-5268-945-00-0 (CH2442-S)

3. Electrical data

SM830082

3. Electrical data

3-2 Outdoor Units


1 CH2442

Schematic Diagram
Terminal Plate (5P) -1 -2 -G -L1 -L2 49 FO CT 52C 3 1 H 5 M 6 L 7 20S 4 RY4 RY5 9 49 C 1 1 1 DC12V N1 CT1 1 3 FM2 49FO RY3 52C FM1 RY2 52C RY1 20S Outdoor Coil C2 Discharge gas 1 2 1 2 TH8 63PH CR 1 F1(5A) RY3 RY5 RY4 H 3 5 M L 20S 52C 3 3 3 7 AC 14V 1Y TR 2 1 RY1 RY2 63PH 1 1Y AC 230V 1 3 RS CN004 1 2 2P-1 2P-2

VCC Outdoor Coil C1 1 2 TH7 TH6

52C PTC

CH

1Y

FMO
1 RC2 2

2 RC1 R

CM

3 F2(5A)

Symbols
CM FMO 52C 49FO 63PH CT RC1,2 TR CH 20S F1,2 TH6 TH7 TH8 PTC

Description
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch Current Transmitter Running Capacitor Power Transformer Crank Case Heater Four Way Valve Fuse Thermistor (Outdoor Coil C1) Thermistor (Outdoor Coil C2) Thermistor (Discharge Gas) PTC Thermistor

Symbols
CR RY1~RY5 1Y

Description
Outdoor Controller Auxiliary Relay Auxiliary Relay Terminal Plate Terminal Connector

S 854-2-5268-945-00-0 (CH2442-S)

SM830082

III - 13

Electric Wiring Diagram


TH6
BLU PNK C1 (BLK) 1 2 BLK BLK BLK BLK WHT WHT 2 OC 1 2P (BLU)

3
2 CH3642

3-2 Outdoor Units

To Indoor Unit

Power Supply

L1 L2 G

To Indoor Unit U1 U2 Terminal 1 2 Plate (2P)

Terminal Plate (5P) 1 1 C2 (RED) 2 Discharge 1 Gas (GRN) 2 L

2 G L1 L2

Earth Terminal 3 SUP 1 3P (BLU)

Controller

TH7 TH8

Earth Terminal E 3P(WHT) CT1 1 3


BRN WHT VLT YEL RED RED RED GRY WHT WHT

BRN RED 3P(BLK) 52C 1 3 9P(WHT) CN019 1 3 5 7 9 3P(YEL) 20S 1 3 3P(RED) 3P(WHT) RS 63PH 1 3 3 1 2P(WHT) VCC 1 2
BRN BRN

RED

WHT

WHT RED RED

GRN/YEL

BLK

CT

GRN/YEL Earth Terminal

BLK

S T

31

ORG GRY

TR AC230V AC14V

52C BRN BRN

V W

32

BLK

BRN

BLK RC2
PNK BRN PNK BRN GRY GRY WHT VLT YEL GRY WHT VLT YEL

BRN

YEL BRN

BLK

RED

WHT

WHT WHT

PNK

BRN GRY GRY WHT VLT YEL

PNK

BRN GRY GRY WHT VLT YEL

CM FMO1 49FO1
GRN/YEL GRN/YEL

CH

20S

RED WHT

III - 14
RC3 P 1 2 3 4 5 6 7 8 Connector S 1 2 3 4 5 6 7 8 8P (WHT) P 1 2 3 4 5 6 7 8 Connector S 1 2 3 4 5 6 7 8 8P (WHT)

RED 7 1Y 8

5 3 1 4

6 2

RC1

PTC

WHT

P 1 2 Connector S 1 2 2P (WHT)

BLK

FMO2 49FO2

63PH

W 854-2-5268-946-00-0 (CH3642-S)

3. Electrical data

SM830082

3. Electrical data

3-2 Outdoor Units


2 CH3642

Schematic Diagram
Terminal Plate (5P) -1 -2 -G -L1 -L2 49 FO CT 49FO1 52C 4 1 H 5 M 6 L 7 H 5 M 6 L 7 20S 3 52C 4 9 49 C 1 1 1 DC12V N1 49FO2 RY1 RY2 RY3 RY4 RY5 CT1 1 3 20S 52C FM1 FM2 Outdoor Coil C2 Discharge gas 1 2 1 2 TH8 63PH CR 1 F1(5A) RY3 RY5 RY4 H 3 5 M L 20S 52C 3 3 3 7 3 AC 14V 1Y TR 2 1 RY1 RY2 63PH 1 1Y AC 230V 1 3 RS CN004 1 2 2P-1 2P-2

VCC Outdoor Coil C1 1 2 TH7 TH6

52C PTC

CH

1Y

FMO1
1 RC2 2

FMO2
1 RC3 2

2 RC1 R

CM

3 F2(5A)

Symbols
CM FMO1,2 52C 49FO1,2 63PH CT RC1,2,3 TR CH 20S F1,2 TH6 TH7 TH8 PTC

Description
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch Current Transmitter Running Capacitor Power Transformer Crank Case Heater Four Way Valve Fuse Thermistor (Outdoor Coil C1) Thermistor (Outdoor Coil C2) Thermistor (Discharge Gas) PTC Thermistor

Symbols
CR RY1~RY5 1Y

Description
Outdoor Controller Auxiliary Relay Auxiliary Relay Terminal Plate Terminal Connector

S 854-2-5268-946-00-0 (CH3462-S)

SM830082

III - 15

Electric Wiring Diagram


TH6
BLU PNK C1 (BLK) 1 2 BLK BLK BLK BLK WHT WHT 2 OC 1 2P (BLU)

3
3 CH4242

3-2 Outdoor Units

To Indoor Unit

Power Supply

L1 L2 G

To Indoor Unit U1 U2 Terminal 1 2 Plate (2P)

Terminal Plate (5P) 1 1 C2 (RED) 2 Discharge 1 Gas (GRN) 2 L

2 G L1 L2

Earth Terminal 3 SUP 1 3P (BLU)

Controller

TH7 TH8

Earth Terminal E 3P(WHT) CT1 1 3 BRN WHT VLT YEL RED RED RED GRY WHT WHT 3P(BLK) 52C 1 3 9P(WHT) CN019 1 3 5 7 9 3P(YEL) 20S 1 3 3P(RED) 3P(WHT) RS 63PH 1 3 3 1

BRN RED 2P(WHT) VCC 1 2 BRN BRN TR AC230V AC14V 7 RC2 PNK BRN PNK BRN GRY GRY WHT VLT YEL GRY WHT VLT YEL RC3 1Y 8

RED

WHT

WHT RED RED

GRN/YEL

BLK

CT

GRN/YEL Earth Terminal

BLK

S T

41

ORG GRY

52C BRN BRN

V W

42

BLK

BRN

BRN

YEL BRN

BLK

RED

WHT

WHT WHT

PNK

BRN GRY GRY WHT VLT YEL

PNK

BRN GRY GRY WHT VLT YEL

CM FMO1 49FO1
GRN/YEL GRN/YEL

CH

20S

RED WHT

III - 16
P 1 2 3 4 5 6 7 8 Connector S 1 2 3 4 5 6 7 8 8P (WHT) P 1 2 3 4 5 6 7 8 Connector S 1 2 3 4 5 6 7 8 8P (WHT)

RED

5 3 1 4

6 2

RC1

P 1 2 Connector S 1 2 2P (WHT)

BLK

FMO2 49FO2

63PH

W 854-2-5268-948-00-0 (CH4242-S)

3. Electrical data

SM830082

3. Electrical data

3-2 Outdoor Units


3 CH4242

Schematic Diagram
Terminal Plate (5P) -1 -2 -G -L1 -L2 49 FO CT 49FO1 52C 4 1 H 5 M 6 L 7 H 5 M 6 L 7 20S 3 52C 4 9 49 C 1 1 1 DC12V N1 49FO2 RY1 RY2 RY3 RY4 RY5 CT1 1 3 20S 52C FM1 FM2 Outdoor Coil C2 Discharge gas 1 2 1 2 TH8 63PH CR 1 F1(5A) RY3 RY5 RY4 H 3 5 M L 20S 52C 3 3 3 7 3 AC 14V 1Y TR 2 1 RY1 RY2 63PH 1 1Y AC 230V 1 3 RS CN004 1 2 2P-1 2P-2

VCC Outdoor Coil C1 1 2 TH7 TH6

52C

CH

1Y

FMO1
1 RC2 2

FMO2
1 RC3 2

2 RC1 C R S

CM

3 F2(5A)

Symbols
CM FMO1,2 52C 49FO1,2 63PH CT RC1,2,3 TR CH 20S F1,2 TH6 TH7 TH8

Description
Compressor Motor Outdoor Fan Motor Compressor Motor Magnetic Contactor Outdoor Fan Motor Thermal Protector High Pressure Switch Current Transmitter Running Capacitor Power Transformer Crank Case Heater Four Way Valve Fuse Thermistor (Outdoor Coil C1) Thermistor (Outdoor Coil C2) Thermistor (Discharge Gas)

Symbols
CR RY1~RY5 1Y

Description
Outdoor Controller Auxiliary Relay Auxiliary Relay Terminal Plate Terminal Connector

S 854-2-5268-948-00-0 (CH4242-S)

SM830082

III - 17

4. Service procedures

4. SERVICE PROCEDURES
4-1 Troubleshooting ...................................................................................... IV (1) Check before and after Troubleshooting ......................................... IV (2) General Troubleshooting Flow Chart: Diagnosis and Remedy ....... IV (3) Meanings of alarm messages .......................................................... IV (4) LED Indication on the Outdoor Units P.C.B. Assy ......................... IV (5) Symptoms and parts to inspect ....................................................... IV (6) Procedures When a Specific Component Does Not Work .............. IV (7) Service Functions of Remote Controller .......................................... IV 2 3 4 6 8 9 19 21

Section

4-2

Checking the Electrical Components ...................................................... IV - 30 (1) Measurement of Insulation Resistance ........................................... IV - 30 (2) Checking the Protective Devices ..................................................... IV - 31 (3) Checking the Electrical Parts ........................................................... IV - 32 (4) Thermistor Characteristic Curve ...................................................... IV - 35 (5) PCB Setting ..................................................................................... IV - 36 (6) R.C Address Setting Method ........................................................... IV - 37 (7) Automatic Address Setting Method ................................................. IV - 38 (8) Displaying Indoor / Outdoor Unit Combination Numbers ................. IV - 38 (9) Items to Check Prior to Test Run .................................................... IV - 39 (10) Test Run .......................................................................................... IV - 40 (11) PCBs and Their Location ................................................................. IV - 42 (12) Checking procedure for each PC Board .......................................... IV - 44 (13) TMX60 Pins ..................................................................................... IV - 45

SM830082

IV - 1

4. Service procedures

4-1

Troubleshooting

This section explains: u What the LED codes mean u What the remote control unit display screen messages mean u How to use the flow charts to find and solve problems u How to use the self-diagnostic tests to find parts that arent working right

Section

This unit is made to be trouble free, and not need much service. However, with time, moving parts wear out, electronic components break down, and sometimes misuse damages the unit. The purpose of this section is to help you when the unit is not working properly. Sometimes your experience will tell you right away where to look for a problem, and when you find it you will know how to fix it at once. Often, however, all you have is a symptom like poor cooling or outside fan doesnt come on. Now you must find out the cause of the problem, and then how to fix it. This section provides several ways to help you go from the symptom to the cause and then the solution. The first chart, General Troubleshooting Flow Chart is divided into two sections: Poor heating and Poor Cooling. Under each heading you will find the main things that can go wrong and cause either of these problems. Sometimes you can start with this chart and find the problem right away, but often you will come here for more suggestions after you have looked at the error code on the remote control unit display. This chart gives you the "big picture" of problems and solutions. The other main tool we explain here is the use of the Alarm Messages. When a certain part fails or a safety device has shut the unit down, any alpha-numeric codes appears on the display to guide you to the problem. By understanding the code you can often go right to the problem area and then, with this manual and your knowledge of air conditioning, find the solution.

IV - 2

SM830082

4. Service procedures

(1)

Check before and after Troubleshooting

Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.
1 . Check power supply wiring u Check the power supply wires are correctly connected between terminal No. 1 & 2 on the 5P terminal plates in the indoor unit and the outdoor unit. 2 . Check inter-unit wiring u Check that inter-unit control wiring (DC low voltage) is correctly connected between the indoor unit and outdoor unit. Power Supply: 60 Hz, single-phase, 230/208 V
Outdoor Unit B Inter-unit power wiring Single phase 230/208V Inter-unit control wiring (Low voltage) 1 2 1 2 D 1 2 G U1 U2 1 2 C Ground U1 U2 L1 L2 G A Ground
L1 L2 Power supply Single phase 230/208V

Section

Indoor Unit

1 2 G

R.C. Address on the PCB: 0 (S2, BLK) (0: Factory shipped state)

Remote controller (Option) *Remote controller wirings are wire joint connection.

3
2085_M_I

Fig. IV-1

3.

Check power supply


u Check that voltage is within the specified range (10% of the rating). u Check that power is being supplied.

If the following troubleshooting must be done with power being supplied, be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK.
4 . Check the lead wires and connectors in indoor and outdoor units. u Check that the sheath of lead wires is not damaged. u Check that the lead wires are firmly connected at the terminal plate. u Check that the wiring is correct.

SM830082

IV - 3

4. Service procedures

(2) General Troubleshooting Flow Chart: Diagnosis and Remedy When you have found a major problem, such as refrigerant not flowing in the system or reduced air circulation, come to this section and find the box listing the problem. Connected to the box are the main causes of the problem and their remedies. To find out which malfunction is happening in your case, check the remote controller for an Alarm Message, and follow the steps in section 3).

(A) Cooling
a. Cooling Poor cooling

Section

1
Is setting temp. suitable ? Change the setting temp. Is cooling load too heavy ? Review cooling load estimate.

2
Refrigerant flow failure 4-way valve is defective. Replace the 4-way valve.

Refrigerant shortage

Charge refrigerant gas.

Electronic refrigerant control valve is defective.

Replace the valve.

Compressor is defective.

Replace the compressor.

4
Service valves are not fully open. Open the valves fully.

Not enough air circulation

Air filter is clogged.

Clean the filter.

Is fan speed set to LOW ?

Set the fan speed to either MEDIUM or HIGH.

Refrigerant tubes between indoor and outdoor units are not insulated.

Insulate wide and narrow tubes separately.


0458_M_I

IV - 4

SM830082

4. Service procedures

(B)

Heating
b. Heating Poor heating

Is setting temp. suitable ?

Change the setting temp.

Is heating load too large ?

Review heating load estimate.

Section
Refrigerant flow failure 4-way valve is defective. Replace the valve.

Refrigerant shortage

Charge with refrigerant.

Electronic refrigerant control valve is defective.

Replace the valve.

Compressor is defective.

Replace the compressor.

Service valves are not fully open.

Open the valves fully.

3
Clean the filter.

Not enough air circulation

Air filter is clogged.

Is fan speed set to LOW ?

Set the fan speed to either MEDIUM or HIGH.

Refrigerant tubes between indoor and outdoor units are not insulated.

Insulate wide and narrow tubes separately.

Cold air is discharged.

4-way valve is defective.

Replace the valve.

Cold draft prevention is not working.

STANDBY is displayed.

Replace indoor P.C.B. Ass'y.

Indoor coil sensor E2 is defective.

Replace the sensor.


0459_M_I

SM830082

IV - 5

4. Service procedures

(3)

Meanings of alarm messages


Alarm message E1 E2 E3 E4 E5

Possible Cause of Malfunction


Serial communication errors Mis-setting Remote controller is detecting error signal from indoor unit. Indoor unit is detecting error signal from the remote controller. (No serial communications signal) Indoor unit is detecting error signal from outdoor unit. Outdoor unit is detecting error signal from indoor unit.

Section

E6 Indoor unit is not working correctly. Outdoor unit is transmitting error signal. Improper setting of indoor unit or remote controller. E7 E8 E9 E12 When using group control, main indoor unit address setting is duplicated. (For single heat pump type.) Error in Auto. address setting. (No. or capacity of judged indoor unit is small.) Error in Auto. address setting. (No. or capacity of judged indoor unit is large.) Indoor unit is detecting error signal from another indoor unit. Activation of protective device Protective device in indoor unit is activated. Protective device in outdoor unit is activated. Thermal protector in indoor fan motor is activated. P1 Thermal protector in outdoor fan motor is activated. Comp. thermal protector is activated. Incorrect discharge gas temp. of comp. High-pressure switch is activated. Incorrect power supply voltage . Negative phase, defective phase or voltage drop. P2 P3 P4 P5 P17 P9 P10 E14 E15 E16 E18

4
NOTE q q q q q RCU R.C. comp. temp. PCB : : : : :

Incorrect discharge gas temp. of comp. Protective device in indoor unit is activated. Improper wiring connections of ceiling panel. Float switch is activated.

Remote Control Unit (remote controller) Refrigerant Circuit Compressor Temperature Printed Circuit Board

IV - 6

SM830082

4. Service procedures

Possible Cause of Malfunction


Thermistor failure Indoor thermistor is either open or damaged. Indoor coil temp. (E1 = TH1) cannot be detected. Indoor coil temp. (E2 = TH2) cannot be detected. Indoor coil temp. (E3 = TH3) cannot be detected. Indoor room (air-intake) temp. can not be detected. Outdoor thermistor is either open or damaged. Discharge gas temp. (comp. = TH0A) cannot be detected. Outdoor coil gas temp. (C2 = TH0C) cannot be detected. Outdoor coil liquid temp. (C1 = TH0D) cannot be detected. EEPROM (ICB of PCB) failure Fault with comp. and its circuit Protective device for comp. is activated. Comp. motor is overloaded. Comp. motor is locked. Current of comp. cannot be detected when it is turned on. Current of comp. is detected when it is not operated. Comp. contactor (Mg SW) is chattering.

Alarm message F1 F2 F3 F10 F4 F25 F7 F29 H1 H2 H3 F27 H18

Section

Possible cause of Malfunction Model setting of indoor unit is not matching the outdoor unit. When using group control, main indoor unit address setting is duplicated. (Judging by indoor unit.) Outdoor unit address (R.C. No.) is duplicated. Priority setting of indoor unit is duplicated. Improper wiring between indoor units. (There is group connection wiring in case of individual control.) Capacity code of indoor unit is not set. Improper wiring of group control wiring.

Alarm message L2 L3 L4 L5 L6 L7 L9 L11

Possible Cause of Malfunction (The following messages are displayed only for the system controller.)
Serial communication errors Mis-setting Activation of protective device Indoor or outdoor unit is not working correctly. System controller is transmitting Control lines between indoor unit, outdoor unit, and system incorrect signal. controller are not wired correctly. System controller is detecting incorrect signal. Protective device of the subindoor unit is activated in group contorl. Same as for C05, above. Connector CN1 is not connected correctly. When using wireless remote controller or system controller, connect wired remote controller with the indoor unit temporarily to check the alarm message in detail.

Alarm message C05

4
C06 P30

NOTE q q q q R.C. comp. temp. PCB : Refrigerant Circuit : Compressor : Temperature : Printed Circuit Board

SM830082

IV - 7

4. Service procedures

(4) LED Indication on the Outdoor Units P.C.B. Assy If something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Assy light up to show the cause of the trouble, in addition to the Alarm message on the remote controller.

LED 2 on LED 1 on Remote P.C. board P.C. board controller * * No message E06, E07, L04 No message P02 P04, P05 F04~F09 H01, H02

Possible cause of trouble Normal Outdoor unit serial communication signal is abnormal. Outdoor unit address is duplicated. Other outdoor units are performing auto address and detecting refrigerant shortage. FMo CM thermal protection is in operation. Power supply voltage is abnormal. High voltage SW activates Negative phase protector activates. Sensor is abnormal. (Open or short) Abnormal compressor current value is detected. Auto address failure Auto address is in operation.

Section

* * E15, E16 Flash at the same time * * Flash alternately SETTING flashes.

NOTE

: LED lamps OFF : LED lamps ON (lights up) *: LED lamps ON (blink)
Outdoor control PCB LED2 (D012) LED1 (D011)

2177_C_I

Fig. IV-2

CAUTION

* REFRIGERANT SHORTAGE Note particularly that a shortage of refrigerant is only shown by the outdoor P.C.B. Assy LEDs and the Alarm Message does not appear on the Indoor Remote Controller . The compressor keeps running even when the refrigerant is less, so when you find the LED indication on the outdoor P.C.B. Assy, stop the air conditioner immediately to avoid the compressor damage.

IV - 8

SM830082

4. Service procedures

(5) 1)

Symptoms and parts to inspect Symptom: LCD on the remote controller does not display and remote controller does not operate.
Start

Is the LED (D80) on Yes the indoor unit PCB lit? No

Repair the remote controller wiring.

Section

1
Miswiring of power supply wires and indoor/outdoor control lines Yes Is there 230-208 V AC between U1 and U2 of the terminal plate? No No Is there 230-208 V AC between R and S of the indoor PCB? Yes

Correct the wiring. Remove the socket connected to the OC plug on the PCB and connect to the EMG plug instead.

Check and repair the power breaker etc.

3
Correct the connections No Are the connections for the 4P connector for the indoor units PCB power transformer good? Yes No Has the indoor unit PCB fuse blown? Yes

4
Replace the indoor unit power transformer. No Is there 15 V AC between 1 and 2 of the 4P connector for the indoor units power transformer? Yes Is the primary side of the indoor power transformer shorted? Yes No Is the 230-208 V AC No Replace the circuit shorted? indoor unit PCB. Yes

Replace the indoor unit PCB.

Replace the indoor units power transformer.

Replace or repair.

2095_THS_I

SM830082

IV - 9

4. Service procedures

2)

Symptom: LCD on the remote controller displays CHECK E01. (Unusual communication between remote controller and indoor unit.)
Start

Remote controller judges itself with self-diagnostic functions OK

NG

Replace the remote controller.

Section

Is there an open or a contact defect in the No. 1 line of the remote controller? No

Yes

Correct the wiring.

Is there 230 -208 V AC between U1 and U2 of terminal plate? No

Yes

Mis-wiring between the power supply line and indoor/ outdoor unit operation lines.

Yes

Correct the wiring, and pull out the socket connected to the OC plug to replace with the EMG plug.

Is the indoor unit PCBs inspection Yes pin shorted? No

Open the inspection pin.

Replace the indoor unit PCB.

3
3) Symptom: LCD on the remote controller displays CHECK E02. (Unusual communication between remote controller and indoor unit)
Start

2096_THS_I

Remote controller judges itself with self-diagnostic functions. OK Replace the indoor unit PCB.

NG

Replace the remote controller.

2097_M_I

IV - 10

SM830082

4. Service procedures

4)

Symptom: LCD on the remote controller is displaying CHECK E04. (Unusual communication between the indoor and outdoor units.)
Start

Cut the breaker and remove the indoor/outdoor unit control lines connected to U1 and U2 of the indoor unit 8P terminal plate. After shorting the test pin (CN2) on the indoor unit PCB, switch the breaker on. Does the LED (red) on the PCB light up? Yes

No

Is the contact good at the 2P connector for indoor serial communications on the outdoor unit PCB? Yes Replace the indoor unit PCB.

No

Correct the connections.

Section

1
No Correct the connections.

Cut the breaker, remove the indoor/outdoor unit control lines connected to U1 and U2 of the outdoor unit 8P terminal plate. After shorting the test pin (CN11) on the outdoor unit PCB, switch the breaker on. Do the LEDs (red, 2) on the PCB flash? Yes

No

Is the contact good at the 2P connector for indoor serial communications on the outdoor unit PCB?

Indoor/outdoor unit control lines are cut off

Replace the indoor unit PCB.

3
Correct the wiring.
0335_M_I

5)

Symptom: LCD on the remote controller is displaying CHECK E05. (Unusual communication between the indoor and outdoor units)
Start

Indoor unit PCB transmission/ reception circuit defect

Replace the indoor unit PCB.


0336_M_I

SM830082

IV - 11

4. Service procedures

6)

Symptom: LCD on the remote controller is displaying CHECK E06. (Unusual communication between the indoor and outdoor units)
Start

Is the setting for the indoor address on the indoor unit PCB inappropriate? No Is there a cut line or contact defect between an indoor and outdoor units control line? No Influenced by external noise

Yes

Correct the setting.

Yes

Correct wiring.

Section

0337_M_I

7)

Symptom: LCD on the remote controller is displaying CHECK E08. (Duplicate indoor unit address setting)
Start

Is the setting for the non-volatile memory IC on the indoor unit PCB inappropriate? If the setting is appropriate, F29 is displayed. (Are there two units with the same address?) No Influenced by external noise

Yes

Correct the setting.

0338_M_I

4
8) Symptom: LCD on the remote controller is displaying CHECK E09. (Duplicate setting of RCU address switch of remote controllers)
Start

Are there two remote controllers (master-slave) installed with both remote controllers set as masters? No Replace the remote controller.

Yes

Correct the setting.

0339_M_I

IV - 12

SM830082

4. Service procedures

9)

Symptom: LCD on the remote controller displays CHECK P01. (Indoor fan protection thermostat operation warning)
Start

Yes Yes Is there 230-208 V AC between T20-1 and T20-3 on the indoor unit PCB? No Is the indoor fan wire winding protection thermostat (49FI) off? Yes

No Correct the connection

Section
Replace the indoor unit PCB. Replace the indoor fan.

1
2098_THS_I

SM830082

IV - 13

4. Service procedures

10) Symptom: LCD on the remote controller displays CHECK P02. (Compressor / outdoor fan protection thermostat operation warning / power supply voltage abnormality)
Start

Section

Is the power supply to the outdoor No unit normal? (Voltage / defective phase?) Yes

Check the power breaker etc. and repair.

1
Is the fuse on the outdoor unit PCB blown (F1 and F2)? No

Yes

Replace the fuse.

Is the high pressure switch (63 PH) off? No

Yes

Replace the outdoor unit PCB.

Yes Is there 230-208 V AC between CN19-9 and CN19-7 on the outdoor unit PCB? No

Replace the outdoor unit PCB.

3
No refrigerant High load 4-way valve defect Clogged refrigerant circuit Electronic refrigerant control valve defect (indoor unit)

No Is the outdoor fan wire winding protection thermostat (49FO) off? Yes

Replace the outdoor fan.

Is there connector contact defect? No

Yes

Correct the connection

Replace the outdoor unit PCB.


2099_THS_I

IV - 14

SM830082

4. Service procedures

11) Symptoms: LCD on the remote controller displays CHECK P03. (Alarm for unusual discharge temp. of compressor)

Start

Unusual discharge gas temperature Refrigerant shortage Clogged refrigerant circuit Electronic refrigerant control valve defect (indoor unit)
0343_M_I

Section

12) Symptom: LCD on the remote controller displays CHECK P04. (High-pressure switch activation warning)
Start

2
No Are there connection defects in the wiring? No Yes Repair the wiring.

The system does not operate again. Yes

High-pressure switch activation (Both cooling and heating) Electronic refrigerant control valve defect Refrigerant over-charged (Cooling) Outdoor unit, heat exchanger dirty, clogged Outdoor unit air short Outdoor fan stopped (Heating) Outdoor unit air short Indoor unit, heat exchanger dirty, clogged Large pipe side service valve closed Indoor fan stop Air filter clogged

High-pressure switch defect

0344_M_I

SM830082

IV - 15

4. Service procedures

13) Symptom: LCD on the remote controller displays CHECK P05. (Negative phase detection operation warning)
Start

Is the power supply to the outdoor unit normal? (Voltage defective phase?) Yes

No

Check the power breaker etc. and repair

Section

Does the outdoor unit operate when two of the three phases are changed? (Actuation of negative phase protector) No

Yes

No problem

Is the fuse (F1, F2) on the indoor unit PCB blown? No

Yes

Replace the fuse.

2
Is there a contact defect in the 3P connector? No Yes Correct the connection

Replace the outdoor PCB


0345_M_I

14) Symptom: LCD on the remote controller displays CHECK E15.


Start

When the group of the units are installed, is there any mis-cross between interunit control wiring and refrigerant tubing? No

Yes

Repair the wiring.

Are the total capacities of indoor units to that of outdoor units less than 93%? No

Yes

Select an indoor unit which matches with the outdoor capacity.

Are there no contact failure between outdoor and indoor units? No

Yes

Check the contact.

Perform the same as CHECK E04.


0646_M_S

IV - 16

SM830082

4. Service procedures

15) Symptom: LCD on the remote controller displays CHECK E16.


Start

When the group of the units are installed, is there any mis-cross between inter unit control wiring and refrigerant tubing? No Are the total capacities of indoor units to that of outdoor units more than 107%? No

Yes

Repair the wiring.

Section
Yes Select indoor units which match with the outdoor capacity.

Confirm less than 5 indoor units are connected. No


0647_M_S

16) Symptom: LCD on the remote controller displays CHECK L13.


Start

When the group of the units are installed, is there any mis-cross between inter unit control wiring and refrigerant tubing? No

Yes

Repair the wiring.

Check the capacity of the indoor unit by remote controller. See Test Run Manual.

0648_M_S

17) Check P9 is displayed on the remote control unit.

Start

Is PNL connector socket being attached to panel connected firmly with PNL plug? Yes

Yes

Connect firmly.

Replace P.C.B. Assy in the indoor unit.


2100_M_S

SM830082

IV - 17

4. Service procedures

18) Symptom: LCD on the remote controller displays CHECK H01, H02, H03. (compressor current detection) * Please check the related part described in the following chart after confirming the code setting (S4) of the outdoor units capacity on the PCB in the outdoor unit.
Start

CHECK H01 display Compressor overload detection

CHECK H02 display Compressor lock detection

CHECK H03 display Compressor current detection circuit defect

Section

1
Insufficient voltage Comp. motor magnetic contactor defect Refrigerant over-charged Compressor lock L3 phase wire disconnected Comp. motor magnetic contactor defect Outdoor unit PCB defect
0346_M_I

19) Check the indoor unit (When the alarm of communication failure is not activated) q If the electronic control valve failure occurred in Flexible Combination system (simultaneous operation system), one indoor unit would not be operated normally, then the other units wont be operated either. Due to this, try to detect the troubled unit and correct it.
Operate the unit in cooling mode. (30 minutes after its operation)

4
Cooled air comes out. Is the temperature of each indoor coil sensor almost the same? (Refer to the sensor temperature display function of the remote controller.) No Yes Normal

Does each indoor coil sensor detect the temperature correctly? (Is there any leakage from the pipe of the temperature detection section?) No

Yes

Failure in the electronic control valve activation.

Replace the sensor.


0460_M_I

IV - 18

SM830082

4. Service procedures

(6) 1)

Procedures When a Specific Component Does Not Work Indoor fan does not operate.
Is fan motor capacitor normal ? Yes Is there voltage output of P.C.B. Ass'y for fan motor ? Yes No Replace the capacitor.

No

Replace the P.C.B. Ass'y in the indoor unit.

Section

Check resistance of fan motor winding. Out

Replace the fan motor.


0650_M_S

2)

Flaps in indoor units air outlet does not operate, when you press SWEEP button.
No Check the louver motor resistance. Is auto louver motor normal? Yes Replace the motor.

3
Is PNL connector socket attached to panel connected firmly with PNL plug ? Yes No Connect firmly.

Replace P.C.B. Ass'y in the indoor unit.


2101_M_S

4
button. (When you press SWEEP button,
Replace the switch. No

3)

Flap does not operate, when you press flap operates.)


Does limit switch actuate? Yes

Is PNL connector socket attached to panel connected firmly with PNL plug ? Yes

No Connect firmly.

Replace P.C.B. Ass'y in the indoor unit.


2102_M_S

SM830082

IV - 19

4. Service procedures

4)

Compressor motor does not operate.


Does compressor motor magnetic No contactor (52C) actuate ? Yes Replace the compressor motor magnetic contactor.

Check resistance of compressor motor winding. NG

Section

1
Replace the compressor.
0461_M_I

5)

Outdoor fan does not operate.


Are auxiliary relays (1Y) normal ? Yes No Replace the relays.

Is fan motor capacitor normal ? Yes

No

Replace the capacitor.

Is there voltage output of P.C.B. Assy for fan motor ?

No

Replace P.C.B. Assy in the outdoor unit.

Yes

Check resistance of fan motor winding. NG

Replace the fan motor.


1148_THS_I

IV - 20

SM830082

4. Service procedures

(7) Service Functions of Optional Wired Remote Controller From the remote controller you can control both the operation and settings of the unit as well as perform several useful service checks. This section explains how to use the remote controller on the following items from (A) to (I). (A) Use the test run procedure. (B) Check the sensor temperature readings. (C) Accessing the service problem history. (D) Check the remote controller itself for correct operation. (E) Excute the auto. address operation. (F) Confirm and change the indoor unit address. (G) Change the shift temperature in heating mode (H) Set the indoor unit address. ( I ) Change the period of the filter timer

Section

(A)

Use the test run procedure

a After holding down the remote controller button for 4 seconds or more, press the button. While the test is running, TEST shows on the LCD display. In TEST mode, the temperature cannot be adjusted. Do not use this mode except during test run operation. b Use TEST mode in either heating or cooling operation mode. NOTE The outdoor unit will not start running for approximately 3 minutes after the power is turned on or the unit is turned off. c When the unit is not operating normally, a code will be displayed on the remote controller LCD. Refer to the Table of Self-Diagnostic Functions at - - -, and take the corrective measures indicated. d After completing the test run operation, button again and check to press the see that TEST is no longer displayed on the remote controller LCD. (The remote controller is equipped with a timer that terminates test run operation after 60 minutes in order to prevent continuous test run operation.)
a, d
Fig. IV-3
2076_M_I

3
a

SM830082

IV - 21

4. Service procedures

(B) Check the sensor temperature readings The air conditioner has thermo sensors which are used to control the unit. t Each sensor has an address which is made up of the indoor unit address, and the sensor address. The indoor unit address is used only when several units are hooked up to one remote controller (group control). If there is only one unit, made up of one indoor and one outdoor unit, then only the sensor address should be put in, as shown in the procedure below. Follow this procedure to display the temperature of each sensor: a On the remote controller, press both seconds. (Ref. Fig. IV-4) and buttons at the same time for more than 4

b The UNIT No., the address and temperature of the sensors instead of its usual information will flash on the display. t Following example shows the UNIT No. (Indoor unit address) is fixed at 01 01. u In case of group control, select the UNIT NO. (Indoor unit address) which you want to check with button. t Each time you press the , ( ) button you can select a different sensor, and the display shows the sensor address and temperature as shown Fig. IV-4.

Section

Sensor address

2
Sensor temperature F Unit No. (Indoor unit address)

3
a
Fig. IV-4
1929_M_I

IV - 22

SM830082

4. Service procedures

Refer to the table below for the relationship between the sensor address and the location of the sensor.
Relationship between the sensor address and the location of sensor Sensor Address (CODE No.) Indoor Unit 00 01 02 03 04 05 06 07 08 09 Outdoor Unit 0A 0B 0C 0D 0E 0F 10 11 12 13 14 NOTE Location of Sensor (Themistor) A/C controlled room Temp. Remote controller room Temp. Indoor air suction Temp. Indoor coil Temp. (E1) Indoor coil Temp. (E2) Indoor coil Temp. (E3) Indoor electronic expantion valve Temp. Discharge gas Temp. Outdoor coil liquid Temp. (C2) Outdoor coil liquid Temp. (C1)

Section

In case there are no sensor equipped with the unit, - - - is shown on the display. C Resetting the remote controller display to previous mode. t To reset the display, press button, then the remote controller will return to previous mode. (C) Accessing the service problem history The gist of past service problems can be recalled. a Press the and buttons simultaneously for 4 seconds or more to enter the service check mode. The term CHECK SERVICE will be illuminated and code No. 01 will be displayed at first. Then the most recent alarm message will be displayed, showing the number of the indoor unit that generated the alarm and the nature of the alarm. b In order to monitor more of the service problem history, press the SET TEMP , ( ) button. This will change the service problem history number (code number). Code number 01 (most recent)code number 04 (oldest) NOTE The service problem history keeps four problems in memory. c Pressing the button will clear the entire indoor unit alarm history. Pressing the button will restore the normal operating display.

c b a
IV - 23

c
2081_M_I

Fig. IV-5
SM830082

4. Service procedures

Important Never press (clear) button unless you want to erase the accessed data in memory. Follow the procedure below only when erasing is necessary. t To erase accessed data, press the button.

t When erasing is finished,---- mark appears on the controllers display.


CAUTION

After checking the alarm messages, be sure to press the

button.

(D) Check the remote controller itself for correct operation The remote controller has a self-diagnostic function to check for problems in the remote controller itself. In order to check, the shorting plug (2P) inserted in the socket (4P) on the back of the remote controller circuit board should be moved from RCU.Main to RCU.CK. (Ref. Fig. IV-6) NOTE 1) Be sure that the shorting plug is inserted onto RCU.Main during normal operation. 2) The remote controller self-diagnostic function can be run on a remote controller independently if power of 916 VDC is supplied to plug 2P as shown in Figure IV-6. (A 12- 1/4-W resistor must be placed in between.) q Checking serial communications The remote controllers own serial communications sending and receiving circuits can be checked by moving the shorting plug. The indicators will respond as follows for approximately 10 seconds, then turn off: Correct : All indicators light up. Incorrect : All indicators flash on and off. q Checking I/O circuits After completing the serial communications check (for 10 seconds), operate each switch on the remote controller. If the LCD display responds, then the remote controller is normal.

Section

TIMER TMNL.

During normal operation

12 1/4W DC9 ~16V


RCU.Main RCU.CK RCU.Sub

Shor ting plug i s m ove d .


RCU TMNL. RCU.ADR

During selfd i a g n o s t i c c h e ck

5
Fig. IV-6
2079_M_I

IV - 24

SM830082

4. Service procedures

Important Never press (clear) button unless you want to erase the accessed data in memory. Follow the procedure below only when erasing is necessary. t To erase accessed data, press the button.

t When erasing is finished,---- mark appears on the controllers display.


CAUTION

After checking the alarm messages, be sure to press the (E) Execute the auto. address operation

button.

t Auto. address operation is executed by pressing the A. ADD (S1) button of outdoor units PCB usually. For your convenience it can be executed by remote controller also. a Press the and ( ) buttons at the same time for more than 4 seconds. (Fig. IV-7) , ( ) button. In this mode, the auto. address operation is executed at each R.C. (Refrigerant Circuit) line one by one.

Section

b Set CODE No. A1 with

a d
Fig. IV-7

b c 1931_M_I

c Select R.C. No. which you want to execute the auto. address operation with button. d Press the button. The auto. address operation will start. CODE No. changes from flashing to ON state. e If an error occurs during operation, the alarm message will be displayed. Check and remove the cause. If you want to stop the operation, press the button then the unit stands in waiting mode (Press the button again.) f If the automatic address operation finishes, the display will disappear. g Execute the operation of the other R.C. line in the same way by following the above steps c to d .
SM830082

IV - 25

4. Service procedures

(F) Confirm and change the indoor unit address (Ref. Fig. IV-8, IV-9) t The purpose of the above function is to let you confirm the indoor unit address after the auto. address operation, and change the indoor unit address if it is needed. a Press the and ( ) buttons at the same time for more than 4 seconds. (up) or (down)

b Select the R.C. No. which you want to change with the buttons.

button (to confirm the R.C. No.). c Press the The smallest registered indoor No. and the selected R.C. No. will be displayed. d Select the indoor No. which you want to change with button. Once in this mode, the fan motor of selected indoor unit will turn on and let you confirm the indoor unit address. e Set the required new indoor units No. by pressing the f Press the button. UNIT No, SET DATA (0001) and g If you made a mistake, press the h Finally, press the button. , ( ) button.

Section

changes from flashing to ON state. button.

i If you want to change the indoor unit address of the other R.C. No., follow the step a to h in the same way.

3
h

a c
Fig. IV-8

e
b
1932_M_I

f
Fig. IV-9

2077_M_I

IV - 26

SM830082

4. Service procedures

(G) Change the shift temperature in heating mode (Ref. Fig. IV-10) t If the indoor unit is installed at high location (ex. ceiling level), the thermostat tends to turn off at heating mode because of the hot air temperature around ceiling level. In order to solve the problem, the shift temp. (valid while heating only) is set when shipped from factory. t If the shift temp. is not enough (ex. the indoor unit is installed at position higher than 3 m), the shift temp. can be set with remote controller from 0 to +10 deg (F) <from 0 to 20 deg (F)>. manually as follows: a Press the + buttons at same time for more than 4 seconds.

b In case of group control, if you want to change all units in group control collectively, proceed next step remaining ALL displayed. If you want to change a unit individually, select the indoor unit address (UNIT No.) with button. c Select the CODE No. 06 with d Choose the shift temp with e Press the button. CODE No. 06, SET DATA and f If you made a mistake, press the g Finally, press the button. , , ( ( ) button. ) button.

Section

1
change from flashing to ON state. button.

3
c

d e
Fig. IV-10

1933_M_I

SM830082

IV - 27

4. Service procedures

(H)

Set the indoor unit address (Ref. Fig. IV-11, IV-12) t This function is usable if the auto. address operation is not available. Indoor unit address can be set one by one by remote controller in such case.
NOTE

1) In case of group control, branch wiring for group control should be removed temporarily. 2) In case of remote controllerless system, remote controller should be connected with the indoor unit temporarily. (Set the No. of R.C. address) b Press the , and buttons at the same time for more than 4 seconds. c Set the CODE No. 12 to set the No. of R. C. with the d Set the No. of R. C. which you want to set with , ( , ( ) button. ) button.

Section

e Press the button. UNIT No., CODE No. 12,

and SET DATA (0002) change from flashing to ON state.

(Set the indoor address) f Select the CODE No. 13 to set the indoor unit No. with the g Set the indoor unit No. which you want to set with the ,

, (

( ) button. ) button.

h Press the button. UNIT No., CODE No. 13, state.

and SET DATA (0004) change from flashing to ON

(Set the group address) i Select the CODE No. 14 to set group setting with the

( ) button.

j Set the No. of group setting with the button. k Press the UNIT No., CODE No. 14,

) button.

and SET DATA change from flashing to ON state. button so that setting returns to the initial state.

l If you made a mistake, press the

m Press the button to finish this mode. The display is disappeared. n Confirm the indoor unit address (UNIT No.) with the ON / OFF button. button after pressing the

o In case of group control, be sure to restore the branch wiring to its original wiring. In case of remote controllerless system, remove the remote controller.

IV - 28

SM830082

4. Service procedures

R.C. address

d, g, j
R.C. address Indoor address Group address 1 1 0 2 1 0
2078_M_I

3 1 0

c, f, i m e, h, k a
Fig. IV-12
2080_M_I

Fig. IV-11

(I)

Change the period of the filter timer (Ref. Fig. IV-13) t If the period of filter timer is not suitable (for example in case of dirty environment), the period can be shortened to half as follows:

Section

a Press the

buttons at same time for more than 4 seconds.

b In case of group control, if you want to change all units in group control collectively, proceed next step remaining ALL displayed. If you want to change a unit individually, select the indoor unit address (UNIT No.) with button. c Select the CODE No. 02 with button. , ( )

d Change the No. from 0000 to 0001 with , ( ) button. button. e Press the CODE No. 06, SET DATA and change from flashing to ON state. f If you made a mistake, press the button.
1934_M_I

g Finally, press the

button.

Fig. IV-13

SM830082

IV - 29

4. Service procedures

4-2 Checking the Electrical Components (1) Measurement of Insulation Resistance


The electrical insulation is acceptable when the resistance exceeds 1 M. 1 Power Supply Wires
Probe Clip

Earthed wire

Insulation tester
0638_X_S

Fig. IV-14

Section

Clamp the earthed wire of the Power Supply wires with a lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. IV-14) Then measure the resistance between the earthed wire and the other power wires. (Fig. IV-14) 2 Indoor Unit

Terminal plate

Probe

Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on the terminal plate (Fig. IV-15) 3 Outdoor Unit

Clip Copper tube or metallic part Insulation tester


0639_X_S

Fig. IV-15

Measure the resistance by placing a probe on the terminal plate in the same manner as explained above 2 . (Fig. IV-15)
Probe

Measurement of Insulation Resistance for Electrical parts


Clip Copper tube or metallic part

Disconnect the connector of the desired electric part from terminal plate, P.C.B. Assy, etc. (Fig. IV-16)

Similarly, disconnect the lead wires from compressor, capacitor, etc. (Fig. IV-17) Measure the resistance in the same manner as illustrated on the right. Refer to Electrical Wiring Diagram. NOTE If the probe does not enter the hole because the hole is too narrow, use a probe with a thinner pin.

Insulation tester

0640_X_S

Fig. IV-16

From fan motor, compressor and other parts.

Metallic part Clip

Probe

Insulation tester
0641_X_S

Fig. IV-17

IV - 30

SM830082

4. Service procedures

(2)

Checking the Protective Devices


Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device. Then check continuity among plugs (and/or sockets) terminal as in Fig. IV-18. Normality of the protective device can be judged by the following table. The Protective Device is proved normal if there is a continuity between terminals.
socket

Section

Multimeter

Fig. IV-18
0642_X_S

Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit Disconnect the connector which leads to the indoor fan motor (FMI). Check the sockets terminals. Disconnect the wires from terminals of compressor. Check the terminals of compressor. Disconnect both the connector which leads to the outdoor fan motor (FMO). Check sockets terminal.

Compressor motor thermal protector . . . . . . Outdoor unit

Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit

SM830082

IV - 31

4. Service procedures

(3)

Checking the Electrical Parts


1 Power transformer (TR1) ..................... Indoor unit Primary *Measure the coil resistance.

230-208V ; Measure the resistance between No.1 and No.3 (WHT lead wires) terminals of 3P (WHT) socket connected to power transformer. 14.8V ; Measure the resistance between No.1 and No.2 (RED lead wires). 14.8V ; Measure the resistance between No.3 and No.4 (BRN lead wires).

Secondary

Section

1
2

Refer to 1-3 Other component specifications. Power transformer (TR) .................... Outdoor unit Primary *Measure the coil resistance.

230-208V ; Measure the resistance between No.1 and No.3 (WHT lead wires) terminals of 3P(WHT) socket jointed to power transformer. 14 V ; Measure the resistance between No.1 and No.2 (BRN lead wires).

2
3

Secondary

Refer to 1-3 Other component specifications. Indoor fan motor (FMI) ......................... Indoor unit *Measure the coil resistance.

Measure the resistance between each terminal of 9P (WHT) socket connected to the indoor fan motor. Refer to 12(A) Major component specifications.

4 Outdoor fan motor (FMO) .....................Outdoor unit

*Measure the coil resistance.

Measure the resistance in the same manner as explained above 3 . Refer to 12(B)Major component specifications.

IV - 32

SM830082

4. Service procedures

Motor capacitor ............ Both in indoor and outdoor unit

Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. IV-19. Observe the deflection of the pointer, setting the resistanc measuring range of the multimeter to the maximum value. The capacitor is good if the pointer bounces to a great extent and then gradually returns to its original position.
NOTE

The range of deflection and the deflection time differ according to the capacity of the capacitor.
Multimeter

Section

2
Compressor motor capacitor

Fan motor capacitor


1041_X_S

3
Fig. IV-19

Continuity of fuse on P.C.B. Assy Check for continuity using a multimeter as shown in Fig. IV-20.
Fuse

NOTE Method Used to Replace Fuse on PCB Assy 1. Remove the PCB Assy from the electrical component box. 2. Remove the fuse from PCB Assy using pliers while heating the soldered leads on the back side of the PCB Assy with a soldering iron (30W or 60W). (Fig. IV-21) 3. For replacement, insert a fuse of the same rating to the intended position and solder it. (Allow time to radiate heat during soldering so that the fuse does not melt.)
CAUTION
Soldering iron

1042_X_S

Fig. IV-20

PCB Assy Fuse Varistor

When replacing the fuse, be sure not to break down the varistor.

Pliers

1043_X_S

Fig. IV-21
SM830082

IV - 33

4. Service procedures

Solenoid coil of the electronic refrigerant control valve (ERCV) Indoor unit

*Measure the coil resistance.

Measure the resistance between No. 5 (GRY lead wire) and other terminals (another color of lead wires) of 5P (WHT) plug connected to the solenoid coil. Refer to 1-2-(A) Major component specifications.

Compressor motor (CM) Outdoor unit In case of single -phase compressor

*Measure the coil resistance.

Section

Remove the cover of compressor terminal and measure the resistance between terminals. Refer to 1-2 Major component specifications. 9 Compressor motor magnetic contactor (52C) Outdoor unit Measure the resistance between A (ORG lead wire) and B (GRY lead wire) terminals on the compressor motor magnetic contactor. Refer to 1-3 Other component specifications. Check the continuity between contactors.

MODEL Push button on the magnetic contactor no press press


0

FMCA1UL Pair of terminals RU YES SV YES TW YES 31 32 YES


*Measure the coil resistance.

Solenoid coil of 4-way valve (20S) Outdoor unit

Measure the resistance between No.1 (BLK lead wire) and No.2 (BLK lead wire) terminals of 2P (BLK) socket connected to the solenoid coil. Refer 1-3 Other component specifications.

IV - 34

SM830082

4. Service procedures

(4)

Thermistor Characteristic Curv (2) Indoor heat exch. coil sensor : TH2(E1), TH3(E2) Outdoor heat exch. coil sensor : TH6(C1), TH7(C2) ( PBC-41E)
40
10 9

(1) Room temp. sensor : TH1 (KTEC-35)

Section

35 30

Resistance (kn )

8 7 6 5 4 3 2 1 50 59 68 77 86 95 104

Resistance (kn )

25 20 15 10 5 0 4 5 14 23 32 41 50 59 68
1045_M_I

Temperature (F)

Temperature (F)
1044_M_I

(3) Compressor discharge gas temp. sensor : TH8 (PTC-51H)

7 6

Resistance (kn )

5 4 3 2 1

176

194

212

230

248

266
1149_THS_I

Temperature (F)

SM830082

IV - 35

4. Service procedures

(5) PCB Setting


q Setting of outdoor control PCB (A) Standard control (single outdoor unit) In case of single outdoor unit installation, even if in case of twin, triple or quartet type (2, 3 or 4 indoor units), no setting necessary. Keep factory shipment state (R.C. address is set in 0). In this case, auto. address operation takes place automatically for the first time when the power is switched on. This takes about a few minutes. (B) Group control (Multiple outdoor units) In case of group control (up to 8 indoor units can be connected with one remote controller), before turning the power supply on set the R.C. address with S2, S3 on the outdoor control PCB. R.C. address: Refrigerant circuit address 1 ~ 30. (C) Central control (when using the system controller) In case of central control (when using the system controller,that is, when linking outdoor units in a network), (a) Before turning the power supply on, set the R.C. address with S2, S3 on the outdoor control PCB. (b) Remove the short plug (CN006, 2P Black) from all outdoor units except any one of outdoor unit. q Setting of indoor control PCB No setting necessary. Each indoor unit address (UNIT No.: R.C. No.) is decided after auto. address operation. Indoor unit No. Refrigerant Circuit No. (R.C. address) Manual setting for indoor unit address can be performed also by remote controller.

Section

IV - 36

SM830082

4. Service procedures

(6) R.C. Address Setting Method


Outdoor unit R.C. address setting method In case of group control or central control, set the R.C. address to 1, 2, 3, ... according to the No. of outdoor units.
Outdoor control PCB CN006 (2P Black) Refrigerant circuit address (factory setting = 0) Refrigerant circuit address (black)
0

Section

: S2

1
ON side : S3

Refrigerant circuit address (2P DIP switch, green or Blue)


10 20 position position ON

OFF side

A. ADD (S1): Automatic address setting start button Used for central control (link system) and group control (Normally, not used)
2093_C_I

R.C. address 00 auto address (0 when shipped from factory)

R.C. address (S3 2P dip switch, green or blue)


ON ON side

R.C. address (S2 Rotary switch, Black)


0

Both OFF
1 2 OFF side

Set to 0

SM830082

IV - 37

4. Service procedures

(7) Automatic Address Setting Method


For group control and central control with multiple outdoor units Carry out automatic address setting with the remote controller. (1) All auto. address operation 1 Press the and ( ) buttons at the same time for more than 4 seconds. 2 Press the button after confirming the CODE No. AA (CODE No. AA: All Auto. address operation). After addresses are automatically set in order for the outdoor units from No. 1 to No. 30, the system returns to the normal stopped state. (2) Individual auto. address operation for each refrigerant circuit 1 To select each refrigerant circuit individually and set addresses automatically, press the and ( ) buttons at the same time for more than 4 seconds, then press the , ( ) button once to set CODE No. A1. (CODE No. A1: Auto. address operation) 2 Select R.C. No. which you want to execute the auto. address operation with button. button. The auto. address Press the operation will start. CODE No. changes from flashing to ON state. If the error is happened during the operation, the alarm message will display. Check and remove the cause. If you want to interrupt the operation, press the button then the unit stands in waiting mode (Press the button). If the auto. address operation finishes, the display will disappear. Execute the operation of the other R.C. line in the same way by following the above steps 2 to 3. Complete the auto. address operation by pressing the button.

(8) Displaying Indoor / Outdoor Unit Combination Numbers


Display the indoor / outdoor unit address after automatic address setting. (1) When installing multiple units, match the indoor unit address numbers and the outdoor R.C. address numbers and display them at an easy-tocheck location (near the nameplate) with an oilbased magic marker or other indelible marker so that the individual indoor and outdoor unit combinations can be checked. Example: Outdoor Unit 1 Indoor Units 1-1, 1-2, 1-3, .... Outdoor Unit 2 Indoor Units 2-1, 2-2, 2-3, .... (2) This is necessary for maintenance. Always label these. *Check indoor unit address with the remote controller. Press the button for at least 4 seconds and check the indoor unit address with the button. (Each time you press the button, the address changes 1-1, 1-2, ... 2-1, 2-2, ...) The fan for only the selected indoor unit turns on at high speed, so check which indoor unit runs and label the indoor unit address. (If there is 1 outdoor unit, the addresses are 1-1, 1-2, ...) button again, the system When you press the returns to normal remote control mode.

Section

5 6

NOTE Required time for auto. address operation: In case of group control : a few minutes for each R.C. In case of central control : max. about 20 min. for each R.C. IV - 38
SM830082

4. Service procedures

(9) Items to Check Prior to Test Run


(1) (2) (3) Turn on the power supply switch more than 5 hours before in order to charge the crank case heater. Fully open the outdoor service valve after making the leak inspection of field connected tubing, vacuuming, and gas charging if necessary. Check the capacity code setting. * The factory setting is as shown in the table. Double check it. * The capacity code is set by S4 (green or blue, 4P DIP switch) on outdoor control PCB.

Section
Outdoor control PCB

2
S4 (green or Blue) capacity code (4P DIP switch) ON ON side

OFF side
2094_C_I

S4. Capacity code No. Model No. 24 type 36 type 48 type

1 ON OFF ON

Outdoor PCB 2 3 ON ON ON ON OFF OFF

4 OFF ON ON

SM830082

IV - 39

4. Service procedures

(10) Test Run


s Preparing for Test Run q Before attempting to start the air conditioner, check the following: (1) (2) (3) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. The control wiring is correctly connected and all electrical connections are tight. The protective spacers for the compressor used for transportation have been removed. If not, remove them now. The transportation pads for the indoor fan have been removed. If not, remove them now. The power has been connected to the unit for at least 5 hours before starting the compressor. The bottom of the compressor should be warm to the touch and the crankcase heater around the feet of the compressor should be hot to the touch. (Fig. IV-22) Both the wide and narrow tube service valves are open. If not, open them now. (Fig. IV-23)
Wide tube service valve (ball valve)
Power mains switch
0765_C_I

ON (Power must be turned ON at least 5 hours before attempting test run)

Section

Fig. IV-22
Narrow tube service valve (3-way valve)

(4) (5)

2
(6)

Fully OPEN

Fully OPEN
1371_C_I

Fig. IV-23

q Test run procedure t The purpose of the test run function is to let you control the operation of the unit directly without the thermostat turning the unit on or off. As indicated in the following procedure, switch out of TEST RUN when you are finished, or the air conditioner can be damaged because it will not cycle on and off normally. t To protect the air conditioner from overloading, the outdoor unit will not start running for 3 minutes after power is applied or the unit is turned OFF. a Press the (TEST RUN) button on the remote Alarm message controller. (Fig. IV-24)

b c d e

Press the (ON / OFF operation) button to start the test run. (MODE) button to select either Press the COOL or HEAT mode. When the test run has started, TEST shows on display of the remote controller. During the test run, the air conditioner runs continuously and the thermostat does not control the system. After the test run, press the button once again to cancel this mode and check that TEST is not shown on the display.
CAUTION

The TEST RUN button is used only for servicing the air conditioner. Do not press this button for normal operation, or the system may be damaged.

TEST RUN/CHECK button

ON/OFF operation button

MODE button
2057_C_I

Fig. IV-24

IV - 40

SM830082

4. Service procedures

q Test Run Procedure


Start

Multiple remote control? No

Yes

Turn on RCU address SW of sub remote control unit

Recheck the test items before test operation.

Check the indoor and outdoor unit combination (wiring).

Section
Yes Single type? (One indoor unit and one remote controller for one outdoor unit) No Multiple indoor units for one outdoor units? No Yes

Turn on power supply for indoor units side first Then turn on power supply for outdoor unit side. Set the outdoor unit R.C. address. Turn on power supply switch.

Group control for multiple outdoor units? No

Yes

Go next R.C. line or No

Press A. ADD (S1) button (See P87). Execute auto. address operation with the remote controller.

Yes

Finish all R.C. line?

Central control for multiple outdoor units? No

Yes

CN4: Open (*) Set the outdoor unit R.C. address. Turn on power supply switch.

Go next R.C. line No or

Press A. ADD (S1) button (See P87). Execute auto. address operation with the remote controller.

Yes

Finish all R.C. line?

Display the combination number.

Set the remote controller to test operation.

Is operation possible?

No

Check according the self-diagnostics function table, see Sec. 12-8, 9, 10, and if there is a location to correct, correct it. Note: Check the indoor side drain water.

Yes Return the remote controller to normal.

NOTE 1) 2)

End
2231_M_I

One of CN006 of all linked outdoor units shold be short. In case of using system controller, zone registration is required after finishing Test run. Regarding the zone registration, please refer to page 74 and 75.

SM830082

IV - 41

4. Service procedures

(11) PCBs and Their Location


q PCB (CR-TH2442) FOR INDOOR UNITS

CN77 (GRN) : LM CN85 (BLU) : DPH CN78 (BLU) : DP CN74 (WHT) : RS2 F2 : Fuse 250V / 5A

Section
CN81 (GRY) : T20

F1 : Fuse 250V / 5A CN73 (BLK) : RS1

1
CN80 (RED) : 26H

CN75 (WHT) : VCC

CN83 (WHT) : FM

CN201 (WHT) : FAN DRIVE CN8 (WHT) : LS CN6 (RED) : EXCT CN9 (RED) : FS D80 LED : POW CN71 (YEL) : T10 CN33 (YEL) : ROOM TEMP E2P-ROM CN31 (RED) : COIL E1 CN32 (BLK) : COIL E2 CN30 (BRN) : COIL E3

CN70 (WHT) : T6 CN91 (WHT) : CRV CN2 (WHT) : TEST CN3 (WHT) : TMX60 CN5 (WHT) : CHK CN44 (BRN) : EMG

CN35 (GRN) : PNL CN40 (BLU) : OC

CN1 (WHT) : DISP

CR-TH2442

F3 : Fuse 0.5A

CN41 (BLU) : RC

CN42 (BLU) : WL
2124_C_S

IV - 42

SM830082

4. Service procedures

q PCB (CR-CH2442) FOR OUTDOOR UNITS

CN013 (WHT) : CK. H CN012 (WHT) : CK. L CN011 (RED) : TEST CN008 (WHT) CN023 (GRN) : DISCH CN022 (RED) : C2 CN021 (BLK) : C1

CN003 (WHT) : VCC CN026 (YEL) : TMX60 CN007 (RED) : EXCT

Section

CR-CH2442

S001 (A. ADD) : Auto address CN025 (WHT) : CT1

D015 LED : POW CN004 (BLU) : OC CN005 (BRN) : EMG F003 : Fuse 125V / 0.5A CN100 (BLK) : JM

S004 (BLU) : Capacity code

LED1 2 3 4 49C CN019 (WHT)

S003 (BLU) : R.C. address S002 (BLK) : R.C. address

CN015 (YEL) : 20S CN016 (BLK) : 52C CN002 (WHT) : RS

49FO

LL

COM CN017 (RED) : 63PH F001 : Fuse 250V / 3A


2178_C_I

F002 : Fuse 250V / 3A CN001 (BLU) : SUP

SM830082

IV - 43

4. Service procedures

(12) Checking procedure for each PC Board


The indoor and outdoor PCBs have functions to check the signal transmission and reception of the serial circuit and to check the microcomputer operation. (Self-diagnosis function)
q Precautions required when checking

1. After turning off the power to the indoor (outdoor) unit, remove the inter-unit control wiring (U1-U2) and create a short-circuit between U1 and U2. 2. Short the CHECK PIN on the PC board of the indoor (outdoor) unit and turn on the power. 3. When checking the Outdoor controller, remove the compressor wiring from the compressor electromagnetic contactor. 4-1. Checking the serial circuit Indoor controller: A lighted LED indicates normal. A blinking LED indicates abnormal. Outdoor controller: Blinking LEDs (D11 and D22) indicate normal. If one of the LEDs (D11 and D22) goes off, it indicates abnormal. 4-2. Checking microcomputer operation

Section

When the microcomputer works normally, the relays are switched in sequence as below. Indoor controller Output Indoor fan High fan speed (H) ON time 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds Indoor fan Very high fan speed (HH) 0.5 seconds Indoor fan Low fan speed (L) Indoor fan Very low fan speed (LL) Flap motor Drain pump Operation order Electric heater Operation signal

In a lump Electronic control valve A Electronic control valve B Electronic control valve.A Electronic control valve B Outdoor controller Output Outdoor fan High fan speed (H) Operation order Outdoor fan Low fan speed (L) 4-way valve Compressor

ON time 0.5 seconds 0.5 seconds 0.5 seconds 0.5 seconds

IV - 44

SM830082

4. Service procedures

(13) TMX60 pins


When shorting TMX60 pins on the indoor and outdoor PCBs, operations shown on the above table will be performed on each indoor and outdoor unit. Use TMX60 pins to perform a quick check. NOTE When checking pin operation, stop the indoor and outdoor units with the remote control unit. s Shorting CK.L or CK.H pin of the outdoor PCB q When shorting the cooling pin (CN8) with normal operation Relay RY3 is turned ON for 3 seconds The outdoor fan motor operates at the LL fan speed. Relay RY4 is turned ON for 3 seconds The outdoor fan motor oprates at the H fan speed. Turn ON relay RY2 under the above condition The magnet switch (52C) turns ON. It will take about 18 seconds before cooling operation begins. q Shorting the heating pin (CN9) with normal operation Relays RY3 and RY4 are turned ON for 3 seconds The outdoor fan motor operates at the H fan speed. Relay RY3 is turned ON for 3 seconds The outdoor fan motor operates at the LL fan speed. Turn ON relay RY2 under the above conditions The magnet switch (52C) turns ON. If relay RY1 is turned ON, the 4-way valve (20S) turns ON. It will take about 18 seconds before heating operation begins. NOTE The outdoor unit operates independently regardless of the indoor units operation. However, the outdoor unit does not defrost. The indoor and outdoor units stop when the outdoor protection apparatus activates during the checking operation, and automatically restarts, unlike in normal operation.

Section

SM830082

IV - 45

SANYO FISHER Service Company CENTRAL REGION


1739 Sands Place, Suite G Marietta, GA 30067 Phone: (770) 951-8284 Fax: (770) 951-2077 July. / 01

Printed in U.S.A.