Air Conditioning Load Estimate

Date : Prepared By Name Of Job Space Used For : Size : Item Area / Qty. Solar Gain - Glass E Glass Glass W Glass Glass N Glass Glass E Glass Glass S Glass Glass SE Glass Glass Sky Light
Orientation-Lb/Sq.Ft.

31-May-13 Mumbai Proposal No. Approved By Estimate Summer For Equipment Operation Conditions Outdoor Room Difference DBT 95 66 29 XXX Job No. Local Time Peak Sun Time Load 12 Hrs./ Day WBT 83 % RH 60 55 XXX XXX DPT Gr. / Lb. 152 60 92 Local Time Sun Time

Anish Shah Location Shoroom - First Floor Length 105 X Breadth = 49 = Area 5145 Sft. X X Height 13 Btu./Hr. = =

Volume 66885 Cu.ft.

Sun Gain X Factor or Temp.Diff 400 680 X X 34 X X X X 11 X 0.56 0.56 0.56 0.8 0.8 0.8 23 0.35 0.35 0.35 0.35 0.35 0.35 1.13 0.35 0.34

152320

Outdoor Air Ventilation 3 AC Per Hr. X 80 People 5145 Sq.Ft. X X 66885 Cu.Ft. / 60 = 3344 600 257

7.5 CFM/ Person = 0.05 CFM/ Sq.Ft. =

N Wall E Wall W Wall S Wall

60 60 60 60

24 26 40 40

X X X X X X

Outdoor Air Quantity = ( Highest Of The Above Three )

3344

Transmission Gain - Except Walls & Roof. All Glass Partition Ceiling Floor Infiltration-CFM Internal Heat People Nos. Power HP Lights Watts/Sq.ft. Appliances PCs Addnl.Heat Gains Safety Factor

Apparatus Dewpoint & Dehumidified Air Quantitiy 29 X 24 X 49 X X X 80 3 3 8 X X X X X ESHF Effective Sensible Heat Factor = Indicated ADP = ERSH ERTH = 238899 281635 Selected ADP = =

0.85 55

ADP 245 2545 3.4 250 19600 7635 19293.8 6800 205649 20565 226214 Dehumidified Rise (1-BF) X ( Trm - Tadp ) Dehumidified CFM ERSH 1.09 X Dehum.Rise Dehumidified CFM =

50
66 T adp 238899 1.09 X

T Rm

55

9.68

3.4

Sub Total 10 % Room Sensible Heat (RSH) # Supply Duct + Loss(%) Fan HP (%) CFM X Temp.Diff.F X BF X 1.09 3344 29 F 0.12 X 1.09 Effective Room Sensible Heat (ESH) # Latent Heat Gr/lb X 0.68

9.68

22642

Supply Duct Heat Gain(%) Outdoor Air Heat

12685 238899

Check: Tonnage as per CFM Tonnage as per Refrigeration load 57 TR 48 TR

People - Nos. Steam Lbs / Hr. Appliances Etc., Additional Heat Gains Vapor Trans.Sq.ft. Safety Factor

80 1050

205

16400

1/100 X Sub Total 7.5 % Room Latent Heat (RLH) # 16400 1230 17630

Supply Duct Leakage Loss Outdoor Air Latent Heat =

% CFM X BF X Gr./Lb. X 0.68 3344 0.12 X 92 X 0.68 Effective Room Latent Heat (ERLH) # Effective Room Total Heat (ERTH) # Outdoor Air Heat Sensible Heat : CFM X Temp.Diff. X (1-BF) X 1.09 3344 29 X 0.88 X 1.09 Latent Heat : CFM X Gr. / Lb. X (1-BF) X 0.68 CFM 3344 92 X 0.88 X 0.68 Return Duct Return Duct Heat Gain %RSH + Leakage Gain % RSH Return Air Blow-thru Fan HP X 2545 Grand Total Heat (GTH) - Dehumidifier Load # Pump HP % GTH + Piping Heat Gain % GTH 2.5 % Refrigeration Load # Total Tonnage #

25106 42736 281635

93026 184110

558772 13969 572741 47.73