User manual UM EN EEM-MA600


Order No.:

INTERFACE

User manual Energy meter for single, two, and three-phase networks

2011-05-19

Designation: Version: Order No.:

UM EN EEM-MA600 00

This user manual is valid for: Designation EEM-MA600 Revision Order No. 2901366

104413_en_00

PHOENIX CONTACT

EEM-MA600

Please observe the following notes


In order to ensure the safe use of the product described, you have to read and understand this manual. The following notes provide information on how to use this user manual. User group of this manual The use of products described in this manual is oriented exclusively to Phoenix Contact accepts no liability for erroneous handling or damage to products from Phoenix Contact or third-party products resulting from disregard of information contained in this user manual. Explanation of symbols used and signal words This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety measures that follow this symbol to avoid possible injury or death. DANGER This indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING This indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION This indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. The following types of messages provide information about possible property damage and general information concerning proper operation and ease-of-use. NOTE This symbol and the accompanying text alert the reader to a situation which may cause damage or malfunction to the device, hardware or software, or surrounding property. This symbol and the accompanying text provide the reader with additional information, such as tips and advice on the efficient use of hardware and on software optimization. It is also used as a reference to other sources of information (manuals, data sheets) on the subject matter, product, etc.

PHOENIX CONTACT

104413_en_00

General terms and conditions of use for technical documentation Phoenix Contact reserves the right to alter, correct, and/or improve the technical documentation and the products described in the technical documentation at its own discretion and without giving prior notice, insofar as this is reasonable for the user. The same applies to any technical changes that serve the purpose of technical progress. The receipt of technical documentation (in particular data sheets, installation instructions, manuals, etc.) does not constitute any further duty on the part of Phoenix Contact to furnish information on alterations to products and/or technical documentation. Any other agreement shall only apply if expressly confirmed in writing by Phoenix Contact. Please note that the supplied documentation is product-specific documentation only and that you are responsible for checking the suitability and intended use of the products in your specific application, in particular with regard to observing the applicable standards and regulations. Although Phoenix Contact makes every effort to ensure that the information and content are accurate, up-to-date, and state-of-the-art, technical inaccuracies and/or printing errors in the information cannot be ruled out. Phoenix Contact does not offer any guarantees as to the reliability, accuracy or completeness of the information. All information made available in the technical data is supplied without any accompanying guarantee, whether expressly mentioned, implied or tacitly assumed. This information does not include any guarantees regarding quality, does not describe any fair marketable quality, and does not make any claims as to quality guarantees or guarantees regarding the suitability for a special purpose. Phoenix Contact accepts no liability or responsibility for errors or omissions in the content of the technical documentation (in particular data sheets, installation instructions, manuals, etc.). The aforementioned limitations of liability and exemptions from liability do not apply, in so far as liability must be assumed, e.g., according to product liability law, in cases of premeditation, gross negligence, on account of loss of life, physical injury or damage to health or on account of the violation of important contractual obligations. Claims for damages for the violation of important contractual obligations are, however, limited to contract-typical, predictable damages, provided there is no premeditation or gross negligence, or that liability is assumed on account of loss of life, physical injury or damage to health. This ruling does not imply a change in the burden of proof to the detriment of the user.

104413_en_00

PHOENIX CONTACT

EEM-MA600 Statement of legal authority This manual, including all illustrations contained herein, is copyright protected. Use of this manual by any third party is forbidden. Reproduction, translation, and public disclosure, as well as electronic and photographic archiving and modification, require written consent by Phoenix Contact. Violators are liable for damages. Phoenix Contact reserves all rights in the case of patent award or listing of a registered design. Third-party products are always named without reference to patent rights. The existence of such rights shall not be excluded. How to contact us Internet Up-to-date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at: www.phoenixcontact.com. Make sure you always use the latest documentation. It can be downloaded at: www.phoenixcontact.net/catalog. Subsidiaries If there are any problems that cannot be solved using the documentation, please contact your Phoenix Contact subsidiary. Subsidiary contact information is available at www.phoenixcontact.com.

Published by PHOENIX CONTACT GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg DEUTSCHLAND Telefon +49 - (0) 52 35 - 3-00 Telefax +49 - (0) 52 35 - 3-4 12 00 Should you have any suggestions or recommendations for improvement to the contents and layout of our manuals, please send your comments to: tecdoc@phoenixcontact.com

PHOENIX CONTACT

104413_en_00

Table of contents
1 2 Safety notes ............................................................................................................................1-1 Device description ..................................................................................................................2-1
2.1 2.2 2.3 Displaying measured values............................................................................... 2-2 Characteristics.................................................................................................... 2-4 Extension modules ............................................................................................. 2-5 2.3.1 Communication modules ....................................................................2-5 2.3.2 Special function modules ....................................................................2-5

3 4

Operating and indication elements .........................................................................................3-1 Mounting and installation ........................................................................................................4-1


4.1 4.2 4.3 4.4 Cutout dimensions..............................................................................................4-1 Mounting ............................................................................................................4-2 Pin assignment ...................................................................................................4-3 Installation .......................................................................................................... 4-4 4.4.1 External current transformers .............................................................. 4-4 4.4.2 Three-phase network with asymmetrical load (4NBL) ......................... 4-4 4.4.3 Three-phase network with asymmetrical load (3NBL) ......................... 4-5 4.4.4 Three-phase network with symmetrical load (3BL/4BL) ...................... 4-7 4.4.5 Two-phase network (2BL) ................................................................... 4-8 4.4.6 Single-phase network (1BL) ................................................................ 4-8 4.4.7 Voltage transducer .............................................................................. 4-9 Mounting extension modules............................................................................ 4-10

4.5

Configuration ..........................................................................................................................5-1
5.1 5.2 5.3 5.4 Configuration mode (PROG) COdE 100 .......................................................... 5-3 Example: configuring the device for a three-phase network with an asymmetrical load .................................................5-4 Current transformers .......................................................................................... 5-5 Voltage transducer ............................................................................................. 5-6 5.4.1 Voltage transducer primary side .........................................................5-7 5.4.2 Voltage transducer secondary side ..................................................... 5-8 Measuring time of the currents ........................................................................... 5-9 Measuring time of voltages............................................................................... 5-10 Frequency measuring time ............................................................................... 5-11 Power measuring time ......................................................................................5-12 Reset ................................................................................................................ 5-13 Configuring the LCD .........................................................................................5-14 Operating hours counter...................................................................................5-15 Changing the configuration mode access code................................................ 5-16

5.5 5.6 5.7 5.8 5.9 5.10 5.11 5.12

104413_en_00

PHOENIX CONTACT

EEM-MA600 5.13 5.14 Displaying the software version and serial number.................................................. 5-17 Exiting configuration mode ............................................................................... 5-17

Operation displaying the measured values ..........................................................................6-1


6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 Displaying currents and temperatures ................................................................ 6-2 Displaying the voltages and frequency ...............................................................6-3 Displaying the power and power factors ............................................................. 6-5 Displaying the maximum and average values..................................................... 6-7 Displaying the total harmonic distortion and harmonics....................................6-11 Display of energy and operating hours .............................................................6-14 Date and time display ....................................................................................... 6-16 Display the measured values via the pulse input .............................................. 6-17

Function test ...........................................................................................................................7-1


7.1 Calling the function test ...................................................................................... 7-2 7.1.1 Automatic correction of current connections ....................................... 7-3 Repeat function test (started manually) .............................................................. 7-4

7.2

8 9

Troubleshooting ......................................................................................................................8-1 Special function modules ........................................................................................................9-1


9.1 9.2 Connection and installation ................................................................................9-1 Configuration ......................................................................................................9-1 9.2.1 EEM-MEMO-MA600 configuration ..................................................... 9-2 9.2.2 EEM-2DIO-MA600 configuration ...................................................... 9-15 9.2.3 EEM-2AO-MA600 configuration .......................................................9-22

10 Communication modules ......................................................................................................10-1


10.1 MODBUS ......................................................................................................... 10-1 10.1.1 Basics ...............................................................................................10-1 10.1.2 Connecting and installing communication module EEM-RS485-MA600 ......................................................................... 10-2 10.1.3 Configuring communication module EEM-RS485-MA600 ................10-3 10.1.4 MODBUS / JBUS register tables .......................................................10-6 10.1.5 Reading/writing MODBUS RTU registers .........................................10-7 Ethernet..........................................................................................................10-12 10.2.1 Connecting and installing communication modules EEM-ETH-MA600 and EEM-ETH-RS485-MA600 .......................... 10-12 10.2.2 Configuring communication modules EEM-ETH-MA600 and EEM-ETH-RS485-MA600 .......................... 10-12 10.2.3 MODBUS / JBUS register tables .....................................................10-17 10.2.4 Reading/writing MODBUS TCP registers ........................................ 10-17

10.2

ii

PHOENIX CONTACT

104413_en_00

Table of contents 10.2.5 10.2.6 10.2.7 10.3 Access to MODBUS register ...........................................................10-18 "Read" and "Write" function ............................................................ 10-18 Web server ..................................................................................... 10-18

PROFIBUS .....................................................................................................10-19 10.3.1 Basics .............................................................................................10-19 10.3.2 Connecting and installing communication modules EEM-PB-MA600 and EEM-PB12-MA600 .......................................10-19 10.3.3 Configuring communication modules EEM-PB-MA600 and EEM-PB12-MA600 .......................................10-20 10.3.4 PROFIBUS register tables ..............................................................10-23 10.3.5 Starting a PROFIBUS configuration ................................................10-23

11 MODBUS register .................................................................................................................11-1 12 PROFIBUS register ...............................................................................................................12-1


12.1 12.2 12.3 12.4 12.5 12.6 12.7 12.8 12.9 Configuration ....................................................................................................12-1 Module 1 "Main values" .................................................................................... 12-5 Module 2 "Additional values" .......................................................................... 12-11 Module 3 "Undervoltage/Interrupt/Pow&Freq"................................................12-13 Module 4 "Overvoltage/Avg U&V/Max&Avg IN".............................................. 12-13 Module 5 "3I&IN harmonics"........................................................................... 12-14 Module 6 "3U harmonics" ...............................................................................12-16 Module 7 "3V harmonics" ...............................................................................12-17 Module 8 "Instantaneous MinMax" .................................................................12-18

12.10 Module 9 "Specific Data" ................................................................................ 12-18 12.10.1 Configuration of the outputs ............................................................ 12-18 12.10.2 User-defined table .......................................................................... 12-21 12.11 Module 10 (not available) ...............................................................................12-27 12.12 Module 11 "Specific short data"......................................................................12-28 12.13 Diagnostics.....................................................................................................12-29

13 Technical data ......................................................................................................................13-1 A B Specifications according to IEC 61557-12 .............................................................................. A-1 Abbreviations.......................................................................................................................... B-1

104413_en_00

PHOENIX CONTACT

iii

EEM-MA600

Safety notes
DANGER: Risk of electric shocks, burns or explosions The "attention symbol" on the device label means: Carefully read through the installation note. Follow the installation note to avoid impairing the intended protection. Only qualified specialist personnel may install, start up, and operate the device. Observe the national safety and accident prevention regulations. When working on the device, always disconnect it from the power supply. Short circuit the secondary side of each current transformer. Use an appropriate voltage measuring device to ensure that no voltage is present. Mount all equipment, doors, and covers before switching on the device again. Installation should be carried out following the instructions provided in the operating instructions. Access to circuits within the device is not permitted. The device does not require maintenance. Repairs may only be carried out by the manufacturer.

Non-compliance with these safety precautions can result in serious injury.

NOTE: Risk of damage to the device Provide a switch/circuit breaker close to a device, which is labeled as the disconnect device for this device. Provide overcurrent protection (I 16 A) in the installation. Observe the maximum permissible values for the device supply (440 V AC/420 V DC), mains frequency (50/60 Hz), maximum voltage at connection terminal blocks (700 V AC phase/phase or 404 V AC phase/neutral conductor). Observe a maximum current of 10 A at the power supply connection terminal blocks (I1, I2, and I3).

1-1

PHOENIX CONTACT

104413_en_00

Device description

Device description
The EEM-MA600 is a highly accurate energy meter for measuring electrical parameters in low voltage installations up to 700 V. It is designed for front-panel installation and supports the measurement, counting, and display of all electrical parameters in 1-, 2, and 3-phase networks with and without neutral conductors (symmetrical and asymmetrical). The buttons located on the front of the device allow fast, direct access to the required parameters as well as device configuration. The device can be expanded using the special function and communication modules and can be configured using communication modules (Ethernet, PROFIBUS, MODBUS, see page 2-5). The device can also be used to record the total harmonic distortion (THD) of the currents and voltages as well as the content of individual harmonic (odd) vibrations. Values up to the 25thharmonic can be shown on the display. The display up to the 63rdharmonic is possible via the MODBUS registers. A trend calculation can be performed for the real and reactive power, and alarm management can be activated (extension module EEM-2DIO-MA600 required). The following parameters can be measured or monitored:

Current

Actual values I1, I2, I3, IN Average value/maximum value I1, I2, I3, IN Harmonic content and content of individual odd harmonics (displays up to 25th) Actual phase/phase value (U12, U23, U31) Actual phase/N value (V1, V2, V3) Average value/maximum value for phase/phase (U12, U23, U31) and phase/N (V1, V2, V3) Harmonic content and content of individual odd harmonics (displays up to 25th) F Actual value for each phase (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3) Total actual value (P, Q, S) Average value/maximum value (P, Q, S) Trend (PPR, QPR, SPR) Actual value for each phase (PF1, PF2, PF3) Total actual value (PF) Average value/maximum value (PF) Real energy (EA +/-) Reactive energy (ER +/-) Apparent energy (ES)

Voltages

Frequency Real, reactive and apparent power

Power factor

Energy (power meter)

104413_en_00

PHOENIX CONTACT

2-1

EEM-MA600 Harmonics Total harmonic distortion of currents I1, I2, I3, IN Total harmonic distortion of line voltage U12, U23, U31 Total harmonic distortion of line voltage against N V1, V2, V3 Individual harmonic content up to 63rd For currents I1, I2, I3 For line voltages (U12, U23, U31) For line voltages against N (V1, V2, V3) Internal External via 3 PT100 temperature sensors For all parameters (extension module EEM-2DIO-MA600 required)

Temperature

Alarm setting

2.1

Displaying measured values

To switch over to the next measured values within a menu, the corresponding button must be pressed once again. I/C button Currents (I1, I2, I3, IN), real energy (EA) Currents (I1, I2, I3, IN) average value (I), real energy (EA) Temperatures (when extension module EEM-TEMP-MA600 is connected) Line voltages (U12, U23, U31), frequency (F), real energy (EA) Line voltages against N (V1, V2, V3), frequency (F), real energy (EA) Line voltages (U12, U23, U31), average value (U), real energy (EA) Line voltages against N (V1, V2, V3), average value (V), real energy (EA) Real power for each phase (P1, P2, P3), total real power (P), real energy (EA) Reactive power for each phase (Q1, Q2, Q3), total reactive power (Q), real energy (EA) Apparent power for each phase (S1, S2, S3), total apparent power (S), real energy (EA) Power factor for each phase (PF1, PF2, PF3) total power factor (PF), real energy (EA) Real power trend (PPR) Reactive power trend (QPR) Apparent power trend (SPR)

U/F button

P/PF button

2-2

PHOENIX CONTACT

104413_en_00

Device description MAX/AVG button H button E button Average value/maximum value for currents (I1, I2, I3, IN), real energy (EA) Average value/maximum value for line voltages phase/phase (U12, U23, U31), average frequency value (F), real energy (EA) Average value/maximum value for line voltages phase/N (V1, V2, V3), average frequency value (F), real energy (EA) Average value/maximum real power value (P) Average value/maximum reactive power value (Q) Average value/maximum apparent power value (S) Total harmonic distortion of currents (THD I1, THD I2, THD I3, THD IN), real energy (EA) Total harmonic distortion of phase/phase (THD U12, THD U23, THD U31) conductor voltages, real energy (EA) Total harmonic distortion of phase/N (THD V1, THD V2, THD V3) conductor voltages, real energy (EA) Harmonic content for currents (I1, I2, I3, IN), real energy (EA) Harmonic content for conductor voltages L/L (U12, U23, U31), real energy (EA) Harmonic content for line voltages L/N (V1, V2, V3), real energy (EA) Positive real energy (EA +) Positive reactive energy (ER +) Apparent energy (ES) Negative real energy (EA-) Negative reactive energy (ER-) Operating hours

104413_en_00

PHOENIX CONTACT

2-3

EEM-MA600

2.2
Current measurement (TRMS)

Characteristics
9999 A 1 or 5 A 10 mA 0 ... 11 kA < 0.3 VA 1s 0.2% (10 ... 110% IN) 10 A 10 x IN for 1 s 18 ... 700 V AC 11 ... 404 V AC up to 500 kV 60, 100, 110, 115, 120, 173, 190 V AC 1s 0.2% (140 ... 700 V AC) 0 ... 8000 MW/Mvar/MVA 1s 0.5% (-90 ... +90C) 1s 0.5% (0.5 < LF < 1) 45 ... 65 Hz 1s 0.1% (45 ... 65 Hz) Class 0.5 S Class 2

Current transformer primary Current transformer secondary Minimum measured current Display Intrinsic consumption Measured value update Accuracy Continuous overload Short-term overload

Voltage measurement (TRMS)

Direct phase/phase Direct phase/N Voltage transducer primary Voltage transducer secondary Measured value update Accuracy Display Measured value update Accuracy Measured value update Accuracy Measuring range Measured value update Accuracy Real energy (IEC 62053-22) Reactive energy (IEC 62053-23)

Power measurement

Power factor measurement Frequency measurement

Measurement of energy amount

2-4

PHOENIX CONTACT

104413_en_00

Device description

2.3

Extension modules

The device can be extended by means of extension modules. The extension modules are plugged into the back of the device and also secured in place with screws.

The description of the maximum number of individual extension modules and the slots to be used can be found at "Installation" on page 4-4.

2.3.1

Communication modules

To be able to adjust the device to various communication interfaces, the following communication modules are available: JBUS/MODBUS communication (EEM-RS 485-MA600, Order No. 2901367): Serial RS485 JBUS/MODBUS connection in RTU mode with a speed of up to 38,400 baud PROFIBUS-DP communication (EEM-PB-MA600, Order No. 2901368) Serial RS485 PROFIBUS DP connection with a speed of up to 1.5 MBd PROFIBUS-DP communication (EEM-PB12-MA600, Order No. 2901418): serial connection RS485 PROFIBUS with D-SUB connector and a speed of up to 12 MBd Ethernet communication (EEM-ETH-MA600, Order No. 2901373): 100 base-T connection (RJ45), MODBUS TCP protocol, integrated web server Ethernet communication (EEM-ETH-RS485-MA600, Order No. 2901374): MODBUS TCP (RJ45) Ethernet connection or JBUS/MODBUS RTU (RS485) via TCP (gateway function), to 247 JBUS/MODBUS slaves

2.3.2

Special function modules

The functional scope of the device can be extended with the following special function modules: Memory (EEM-MEMO-MA600, Order No. 2901370): Storage of the last 10 alarms with date and time Storage of the last undervoltages, surge voltages and voltage failures with date and time Storage of current minimum and maximum measured values for I, IN, U, V, F, PF, P, Q, S, THD U, THD V, THD I, THD IN Storage of real and reactive P+/- and Q+/- up to 62 days with an internal or external synchronization impulse for an adjustable measurement period of 5, 8, 10, 15, 20 and 30 minutes Storage of course of average values U, V, and F based on the measurement duration (maximum of 60 days) Digital inputs/outputs (EEM-2DIO-MA600, Order No. 2901371): Two switching outputs as alarm for voltage, currents, power, power factor, frequency and harmonic content Two inputs for counting the impulses or for position checking (for example, switch setting)

104413_en_00

PHOENIX CONTACT

2-5

EEM-MA600 Analog outputs (EEM-2AO-MA600, Order No. 2901374): Two analog outputs 4 20 mA or 0 20 mA can be set according to current, voltage, power and power factor Two modules with a maximum of four outputs can be installed Temperature inputs (EEM-TEMP-MA600, Order No. 2901949) Module for measuring temperature from up to three PT100 temperature sensors from -20C ... + 150C. The ambient temperature in the direct vicinity of the module can be acquired from -10C ... +55C.

2-6

PHOENIX CONTACT

104413_en_00

Operating and indication elements

Operating and indication elements

2 3 4 8 9 0

6 7 ! "

Figure 3-1 1.

Operating and indication elements

Pushbuttons with dual functionality: Normal mode: display measured values Programming mode: change configuration 2. Backlit LCD 3. Display measured values in relevant conductor 4. Measured value 5. Unit 6. Current measurement as a % bar indicator 7. Frequency display 8. Alarm relay 1 (if installed) 9. Alarm relay 2 (if installed) 10. Energy display 11. Display of active communication (if optional communication module is installed) 12. Display for recording the real energy (flashes for every kWh)

104413_en_00

PHOENIX CONTACT

3-1

EEM-MA600

Mounting and installation


Avoid being in close proximity to systems that can generate electromagnetic interference. In addition, avoid mechanical vibrations with acceleration rates greater than 1g (9.81 m/s2) at frequencies below 60 Hz.

4.1

Cutout dimensions

45 0 6 0 8

Figure 4-1

Cutout dimensions

4-1

PHOENIX CONTACT

104413_en_00

Mounting and installation

4.2

Mounting

Figure 4-2

Mounting

To ensure that the device is securely placed on the front panel, the device must be pressed into the mounting slot from the front and then secured from behind using the four clamps provided. To mount the device, proceed as follows: 1. 2. 3. Press the device into the mounting slot from the front and hold it in this position. Secure the device from behind with the four clamps, as shown in Figure 4-2. Push the clamps as far as they will go onto the latch, until the device is securely positioned and the clamps snap into place.

104413_en_00

PHOENIX CONTACT

4-2

EEM-MA600

4.3

Pin assignment

s1 s2 s1 s2 s1 s2

I1

I2

I3

V1

V2

V3

VN

AUX

2 1
Figure 4-3 Pin assignment 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC Connection of measured currents: S1 (input) S2 (output) Connection of measured voltage

1 Supply voltage range (AUX): 2 Fuse: I1, I2, I3

V1, V2, V3, VN

Maximum tightening torque for the respective screws: 0.4 Nm.

DANGER: Risk of electric shock When you disconnect the device, you must short-circuit the secondary side of the current transformer. A URTK6 (Order No. 3026272) transformer disconnect terminal block can be used.

4-3

PHOENIX CONTACT

104413_en_00

Mounting and installation

4.4

Installation

The device is intended for connection to various mains types in two, three or four wire mains networks with symmetrical or asymmetrical load. When measuring by means of transformers, the accuracy is greatly influenced by the quality of the transformers used.

4.4.1

External current transformers

When selecting the current transformer, the secondary nominal current must be 1 A or 5 A. The primary nominal current is determined by the current consumption of the load. Appropriate PACT current transformers can be found in the Phoenix Contact INTERFACE catalog. DANGER: Risk of electric shock Only install current transformers and corresponding measuring devices when the power supply is disconnected. Observe the order in which the current transformers are connected when wiring them (direction of current flow). Primary circuit: K-P1 -> L-P2; secondary circuit: k-S1 -> I-S2 When the current transformer is operated with an open secondary circuit, hazardous voltages may occur at the secondary terminal blocks.

4.4.2

Three-phase network with asymmetrical load (4NBL)

Figure 4-4

Three-phase network with asymmetrical load (4NBL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

1 Supply voltage range: 2 Fuse:

104413_en_00

PHOENIX CONTACT

4-4

EEM-MA600

4.4.3

Three-phase network with asymmetrical load (3NBL)

Figure 4-5

Measurement via 3 current transformers

Figure 4-6

Measurement via 2 current transformers

1 Supply voltage range: 2 Fuse:

110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

4-5

PHOENIX CONTACT

104413_en_00

Mounting and installation

Figure 4-7

Measurement via 2 current transformers

1 Supply voltage range: 2 Fuse:

110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

The solution with two current transformers reduces the degree of accuracy of phases by 0.5%, whereby their current is calculated vectorially (without current transformer).

104413_en_00

PHOENIX CONTACT

4-6

EEM-MA600

4.4.4

Three-phase network with symmetrical load (3BL/4BL)

Figure 4-8

Three-phase network with symmetrical load (3BL/4BL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

1 Supply voltage range: 2 Fuse:

The solution with a current transformer reduces the accuracy of phases by 0.5%, whereby their current is calculated vectorially (without current transformer).

4-7

PHOENIX CONTACT

104413_en_00

Mounting and installation

4.4.5

Two-phase network (2BL)

Figure 4-9

Two-phase network (2BL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

1 Supply voltage range: 2 Fuse:

4.4.6

Single-phase network (1BL)

Figure 4-10

Single-phase network (1BL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

1 Supply voltage range: 2 Fuse:

104413_en_00

PHOENIX CONTACT

4-8

EEM-MA600

4.4.7

Voltage transducer
AUX

Figure 4-11

Voltage transducer 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC

1 Supply voltage range: 2 Fuse:

4-9

PHOENIX CONTACT

104413_en_00

Mounting and installation

4.5

Mounting extension modules

The extension modules are plugged into the back of the device and also secured in place with screws.

1 2 3 4

Figure 4-12

Mounting extension modules

You can find information about configuring the communication and extension modules in Section "Communication modules" on page 10-1.

Table 4-1 Designation

Installation overview Order No. 2901367 2901373 2901374 2901368 2901418 2901371 2901370 2901475 2901949 Max. number 1 1 1 1 1 3 1 2 1 Space requirements 1 slot 2 slots 2 slots 2 slots 2 slots 1 slot 1 slot 1 slot 1 slot No. slots 1 ... 4 1 ... 4 1 ... 4 1 ... 4 1 ... 4 1 ... 4 2 or 3 1 or 2 2 or 3

EEM-RS485-MA600 EEM-ETH-MA600 EEM-ETH-RS485-MA600 EEM-PB-MA600 EEM-PB12-MA600 EEM-2DIO-MA600 EEM-MEMO-MA600 EEM-2AO-MA600 EEM-TEMP-MA600

104413_en_00

PHOENIX CONTACT

4-10

EEM-MA600

Configuration
The device can be configured via pushbuttons. The configuration is described in the following subsections. To configure the EEM-MA600, press the gray buttons consecutively, as described in the respective example. The corresponding configuration menu is displayed for the extension/communication module used. You will find the necessary configuration settings in Section "Communication modules" on page 10-1.

Button PROG or or or OK

Description Open configuration mode (press and hold for 3 seconds) Select the next menu item Open edit mode In edit mode: select parameters/values to be changed In edit mode: change parameters/values Confirm setting

5-1

PHOENIX CONTACT

104413_en_00

Configuration

Configuration mode: Mains types: Current transformer:

100 4NBL, 3NBL, 4BL, 3BL, 2BL , 1BL Set primary current Set secondary current Set value 1 A; 5A Set value

Voltage transformer: NO

YES

Primary side:

Secondary side:

110; 115; 120; 173; 190; 60; 100

Measuring time for currents to calculate MAX and average values:

20' min; 30' min; 60' min; 2' sec; 10' sec; 5' min; 8' min; 10' min; 15' min

Measuring time for voltages calculate MAX and average values:

20' min; 30' min; 60' min; 10' sec; 5' min; 8' min; 10' min; 15' min

Measuring time for frequency to calculate MAX and average values: Measuring time for power to calculate MAX and average values:

20' min; 30' min; 60' min; 10' sec; 5' min; 8' min; 10' min; 15' min

20' min; 30' min; 60' min; 10' sec; 5' min; 8' min; 10' min; 15' min

Reset measured values / times:

MAX4I: Maximal value of the currents MAXU: Maximal value of the conductor voltages (1-2 / 2-3 / 3-1) MAXV: Maximal value of the conductor voltages against N (1 / 2 / 3) MAXF: Maximal value of the frequncy MAXP+: Maximal value of positive real power MAXP-: Maximal value of negative real power MAXQ+: Maximal value of positive reactive power MAXQ-: Maximal value of negative reactive power MAXS: Maximal value of appearent power HOUR: Operating hours counter EA+: Positive active energy (+kWh) ER+: Positive reactive power (+kVArh) ES: Appearent power (-kVAh) EA-: Negative active energy (+kWh) ER-: Negative reactive power (+kVArh)

Yes; No

LCD display:

AUX: illuminated, if supply voltage is available I: illuminated, if current is being measured U: illuminated, if voltage is being measured for AUX: Illumination goes out automatically after 2 minutes. The display is illuminated again after pressing any key.

Operating hours counter:

AUX: activated, if supply voltage is available I: activated, if threshold value is set (input current) U: activated, if threshold value is set (input voltage) E1: activated, if digital input 1 is connected E2: activated, if digital input 2 is connected E3: activated, if digital input 3 is connected E4: activated, if digital input 4 is connected E5: activated, if digital input 5 is connected E6: activated, if digital input 6 is connected Threshold value: I/U Set value

see extension module

Access code:

Set value Press until you reach menu item Ser l : serial number is displayed Press until you reach menu item SOFt: software version is displayed

Serial number:

Software version:

Figure 5-1

Flowchart

104413_en_00

PHOENIX CONTACT

5-2

EEM-MA600

5.1

Configuration mode (PROG) COdE 100

In configuration mode, the labeling below the pushbuttons applies.

Once the appropriate setting has been made and confirmed by pressing "OK", the next menu item is called automatically. To switch to configuration mode, press and hold the "PROG" button for a minimum of 3 seconds. Follow the instructions and enter "Code 100". Confirm with "OK".

I C

U F

P PF MAX AVG

1x 3 seconds

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-2

Switching to configuration mode

5-3

PHOENIX CONTACT

104413_en_00

Configuration

5.2

Example: configuring the device for a three-phase network with an asymmetrical load

NET = 3NBL

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x

1BL 2BL 3BL 3NBL 4BL 4NBL

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-3

Setting a three-phase network with an asymmetrical load (3NBL)

104413_en_00

PHOENIX CONTACT

5-4

EEM-MA600

5.3

Current transformers

Enter the ratio of the current transformers used as shown in the following example. Example: transformer ratio CT = 1500/5A

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-4

Setting the transformer ratio CT = 1500/5A

The transformer output can be set to 1 A or 5 A on the secondary side.

5-5

PHOENIX CONTACT

104413_en_00

Configuration

5.4

Voltage transducer

Select whether the connection is to be established via voltage transducers. Example: connection via voltage transducers (YES/NO) Vt = YES

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-5

Setting voltage transducer connection to Vt = YES

104413_en_00

PHOENIX CONTACT

5-6

EEM-MA600

5.4.1

Voltage transducer primary side

Set the primary side voltage as shown in the following example. Example: primary side voltage = 20,000 V PR = 20,000

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-6

Setting voltage transducers on the primary side

5-7

PHOENIX CONTACT

104413_en_00

Configuration

5.4.2

Voltage transducer secondary side

Set the secondary side voltage as shown in the following example. Example: secondary side voltage 110 V SE = 110

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x 7x

110 115 120 173 190 60 100

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-7

Setting voltage transducers on the secondary side

104413_en_00

PHOENIX CONTACT

5-8

EEM-MA600

5.5

Measuring time of the currents

This value specifies over which period the currents are to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME 4I = 20

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x 7x 8x 9x

20 min. 30 min. 60 min. 2 sec. 10 sec. 5 min. 8 min. 10 min. 15 min.

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-8

Setting the measuring time of the currents

5-9

PHOENIX CONTACT

104413_en_00

Configuration

5.6

Measuring time of voltages

This value specifies over which period the voltages are to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME U/V = 20

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x 7x 8x

20 min. 30 min. 60 min. 10 sec. 5 min. 8 min. 10 min. 15 min.

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-9

Setting the measuring time of voltages

104413_en_00

PHOENIX CONTACT

5-10

EEM-MA600

5.7

Frequency measuring time

This value specifies over which period the frequency is to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME F = 20

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x 7x 8x

20 min. 30 min. 60 min. 10 sec. 5 min. 8 min. 10 min. 15 min.

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-10

Setting the measuring time of the frequency

5-11

PHOENIX CONTACT

104413_en_00

Configuration

5.8

Power measuring time

This value specifies over which period the power is to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME P/Q/S = 20

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x 7x 8x

20 min. 30 min. 60 min. 10 sec. 5 min. 8 min. 10 min. 15 min.

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-11

Setting the measuring time of the power

104413_en_00

PHOENIX CONTACT

5-12

EEM-MA600

5.9

Reset

Example: rSET = EA+

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

0 x MAX4I maximum current value 1 x MAX U maximum conductor voltage value (1-2 / 2-3 / 3-1) 2 x MAX V maximum value of conductor voltages against N (1 / 2 / 3) 3 x MAX F maximum frequency value 4 x MAX P+ maximum positive real power value 5 x MAX P- maximum negative real power value 6 x MAX Q+ maximum positive reactive power value 7 x MAX Q- maximum negative reactive power value 8 x MAX S maximum apparent power value 9 x HOUR operating hours counter

10 x 11 x 12 x 13 x 14 x 16 x 17 x 18 x 19 x 20 x 21 x
*

EA+ positive real power (+kWh) ER+ positive reactive energy (+kVArh) ES apparent energy (-kVAh) EA- negative real energy (+kWh) ER- negative reactive energy (+kVArh) E1 digital input 1* E2 digital input 2* E3 digital input 3* E4 digital input 4* E5 digital input 5* E6 digital input 6*

Only displayed if the EEM-2DIO-MA600 (Order No. 2901371) module is available.

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-12

Setting restore rSET = EA+

5-13

PHOENIX CONTACT

104413_en_00

Configuration

5.10

Configuring the LCD

The LCD lighting can be configured in various ways. Configuration options The display is illuminated if: Supply voltage is applied (AUX) Current is measured (I) Voltage is measured (U) For the AUX option (supply voltage is applied) , the display automatically goes out after 2 minutes. Press any button to illuminate the display again. Example: the display is illuminated if supply voltage is applied bACLIT = AUX

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x AUX supply voltage present 2 x I current is measured 3 x U voltage is measured

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-13

Configuring the LCD

104413_en_00

PHOENIX CONTACT

5-14

EEM-MA600

5.11

Operating hours counter

Example: operating hours counter depending on the current flow. The counter is activated if the current is greater than 1000 A.

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

0x 1x 2x 3x 4x
*

AUX supply voltage I input current U input voltage E1 digital input 1* E2 digital input 2*

5x 6x 7x 8x

E3 digital input 3* E4 digital input 4* E5 digital input 5* E6 digital input 6*

Only displayed if the EEM-2DIO-MA600 (Order No. 2901371) module is available.

I C

U F

P PF MAX AVG

1x Confirm

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-14

Setting a current-dependent operating hours counter

5-15

PHOENIX CONTACT

104413_en_00

Configuration

5.12

Changing the configuration mode access code

In order to change the configuration mode access code, proceed as follows: Example: COdE = 200

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 5-15

Changing the configuration mode access code

104413_en_00

PHOENIX CONTACT

5-16

EEM-MA600

5.13

Displaying the software version and serial number

Switch to programming mode.

I C

U F

P PF MAX AVG
1 x SOFt 2 x SEr2 3 x SEr1

Example: SOFt = 300

Example: SErl = 0320100

Figure 5-16

Displaying the software version and serial number

5.14

Exiting configuration mode

Exit configuration mode by pressing and holding the "PROG" button for at least 3 seconds.

I C

U F

P PF MAX AVG

1x 3 seconds

Figure 5-17

Exiting configuration mode

5-17

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

Operation displaying the measured values


To gain fast access to the desired measured values, the device is equipped with six pushbuttons that enable direct access to the respective submenu. In operating mode, the labeling above the pushbuttons applies.

Press the following pushbuttons to display the desired measured values: Table 6-1 Pushbutton
I C

Pushbutton functions in operating mode Displays... Currents, temperatures (with extension module EEM-TEMP-MA600)

U F

Voltages, frequency
P PF

Power, power factor


MAX AVG

Maximum values, average values


H

Total harmonic deviation (TDH), harmonics


E

Energy, operating hours, Date and time (with expansion module EEM-MEMO-MA600) Measured values via pulse input (with function module EEM-2DIO-MA600)

By pressing the appropriate pushbutton several times, further measured values can be displayed within the selected menu (see also "Displaying measured values" on page 2-2). The figures in the following subsections explain the various measured value displays by means of pressing the pushbuttons several times.

104413_en_00

PHOENIX CONTACT

6-1

EEM-MA600

6.1
Press button:
I C

Displaying currents and temperatures

1x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Real energy (EA)

I C

U F

P PF MAX AVG

2x

EMpro

Currents in conductors (I1, I2, I3) ISYS average current value (I1 + I2 + I3) / 3 Real energy (EA)

I C

U F

P PF MAX AVG

3x

EMpro

Temperatures (extension module required)

I C

U F

P PF MAX AVG

6-2

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

6.2
Press button:
U F

Displaying the voltages and frequency

1x

EMpro

Phase/phase conductor voltages (U12 + U23 + U31) Frequency (F) Real energy (EA)

I C

U F

P PF MAX AVG

2x

EMpro

Phase/N conductor voltages (V1, V2, V3) Frequency (F) Real energy (EA)

I C

U F

P PF MAX AVG

3x

EMpro

Phase/N conductor voltages (V1, V2, V3) USYS average conductor voltage value (U12 + U23 + U31)/3 Real energy (EA)

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-3

EEM-MA600

4x

EMpro

Phase/N conductor voltages (V1, V2, V3) Phase/N VSYS average conductor voltage value (V1 + V2 + V3)/3 Real energy (EA)

I C

U F

P PF MAX AVG

6-4

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

6.3
Press button:
P PF

Displaying the power and power factors

1x

EMpro

Real power per phase (P1, P2, P3) Total real power (P) Real energy (EA)

I C

U F

P PF MAX AVG

2x

EMpro

Reactive power per phase (Q1, Q2, Q3) Total reactive power (Q) Real energy (EA)

I C

U F

P PF MAX AVG

3x

EMpro

Apparent power per phase (S1, S2, S3) Total apparent power (S) Real energy (EA)

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-5

EEM-MA600

4x

EMpro

Power factor per phase (PF1, PF2, PF3) Total power factor (PF) Real energy (EA)
= inductive = capacitive

I C

U F

P PF MAX AVG

5x

EMpro

Real power trend (PPR)

I C

U F

P PF MAX AVG

6x

EMpro

Reactive power trend (QPR)

I C

U F

P PF MAX AVG

7x

EMpro

Apparent power trend (SPR)

I C

U F

P PF MAX AVG

6-6

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

6.4
Press button:
MAX AVG

Displaying the maximum and average values

1x

EMpro

Maximum current value (I1, I2, I3, IN) Real energy (EA)

I C

U F

P PF MAX AVG

2x

EMpro

Maximum phase/phase (U12, U23, U31) conductor voltage value Maximum frequency (F) value Real energy (EA)

I C

U F

P PF MAX AVG

3x

EMpro

Maximum phase/N conductor voltage value (V1 + V2 + V3) Maximum frequency (F) value Real energy (EA)

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-7

EEM-MA600

4x

EMpro

Maximum real power (P) value

I C

U F

P PF MAX AVG

5x

EMpro

Maximum reactive power (Q) value

I C

U F

P PF MAX AVG

6x

EMpro

Maximum apparent power (S) value

I C

U F

P PF MAX AVG

7x

EMpro

Average current (I1, I2, I3, IN) value Real energy (EA)

I C

U F

P PF MAX AVG

6-8

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

8x

EMpro

Average phase/phase conductor voltage (U12 + U23 + U31) value Average frequency value (F) Real energy (EA)

I C

U F

P PF MAX AVG

9x

EMpro

Average phase/N conductor voltage (V1, V2, V3) value Average frequency value (F) Real energy (EA)

I C

U F

P PF MAX AVG

10 x

EMpro

Average real power value (P)

I C

U F

P PF MAX AVG

11 x

EMpro

Average reactive power value (Q)

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-9

EEM-MA600

12 x

EMpro

Average apparent power value (S)

I C

U F

P PF MAX AVG

6-10

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

6.5

Displaying the total harmonic distortion and harmonics

By pressing the "H" button, the following values are displayed: 1 touch: 2 touches: 3 touches: 4 touches: 5...15 touches: 16 touches: 17...27 touches: 28 touches: 29...39 touches: THDI: total harmonic distortion of currents (THD I1, THD I2, THD I3, THD IN), real energy (EA) Total harmonic distortion of phase/phase (THD U12, THD U23, THD U31) conductor voltages, real energy (EA) Total harmonic distortion of phase/N (THD V1, THD V2, THD V3) conductor voltages, real energy (EA) Content of 3rd harmonic for current (I1, I2, I3, IN), real energy (EA) Content of 5th - 25th harmonic for currents (I1, I2, I3, IN), real energy (EA) Content of 3rd harmonic for conductive voltages (U12, U23, U31), real energy (EA) Content of 5th - 25th harmonic for conductor voltages L/L (U12, U23, U31), real energy (EA) Content of 3rd harmonic for conductor voltages phase/N (V1, V2, V3), real energy (EA) Content of 5th - 25th harmonic of phase/N (V1, V2, V3) conductor voltages, real energy (EA)

Press button:
H

1x

EMpro

Total harmonic distortion of currents (THD I1, THD I2, THD I3, THD IN) Real energy (EA)

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-11

EEM-MA600

2x

EMpro

Total harmonic distortion of phase/phase (THD U12, THD U23, THD U31) conductor voltages, Real energy (EA)

I C

U F

P PF MAX AVG

3x

EMpro

Total harmonic distortion of phase/N (THD V1, THD V2, THD V3) conductor voltages Real energy (EA)

I C

U F

P PF MAX AVG

4x

EMpro

Content of 3rd harmonic for currents (I1, I2, I3, IN) Real energy (EA)

I C

U F

P PF MAX AVG

18 x

EMpro

Content of 7th harmonic of L/L (U12, U23, U31) conductor voltages Real energy (EA)

I C

U F

P PF MAX AVG

6-12

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

31 x

EMpro

Content of 9th harmonic for phase/N (V1, V2, V3) conductor voltages Real energy (EA)

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-13

EEM-MA600

6.6
Press button:
E

Display of energy and operating hours

1x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Absorbed (positive) real energy (EA+)

I C

U F

P PF MAX AVG

2x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Absorbed (positive) reactive energy

I C

U F

P PF MAX AVG

3x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Apparent energy

I C

U F

P PF MAX AVG

6-14

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

4x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Supplied (negative) real energy (EA-)

I C

U F

P PF MAX AVG

5x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Supplied (negative) reactive energy (ER-)

I C

U F

P PF MAX AVG

6x

EMpro

Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Operating hours

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-15

EEM-MA600

6.7
Press button:
E

Date and time display

The display is only possible when the EEM-MEMO-MA600 storage module is connected.

7x

EMpro

Date

I C

U F

P PF MAX AVG

8x

EMpro

Time

I C

U F

P PF MAX AVG

6-16

PHOENIX CONTACT

104413_en_00

Operation displaying the measured values

6.8
Press button:
E

Display the measured values via the pulse input

You can display the counter pulses of the connected pulse input by pressing the E key several times. The display is only possible when function module EEM-2DIO-MA600 is connected. E 3, E 4 can be displayed when two EEM-2DIO-MA600 function modules are connected. E 5, E 6 can be displayed when three EEM-2DIO-MA600 function modules are connected.

1x

EMpro

Counter pulses E1

I C

U F

P PF MAX AVG

2x

EMpro

Counter pulses E2

I C

U F

P PF MAX AVG

3x

EMpro

Counter pulses E3

I C

U F

P PF MAX AVG

104413_en_00

PHOENIX CONTACT

6-17

EEM-MA600

4x

EMpro

Counter pulses E4

I C

U F

P PF MAX AVG

5x

EMpro

Counter pulses E5

I C

U F

P PF MAX AVG

6x

EMpro

Counter pulses E6

I C

U F

P PF MAX AVG

6-18

PHOENIX CONTACT

104413_en_00

Function test

Function test
To perform the function test, the device must be connected and ready for operation. The power factor (PF) of the system must be between 0.6 > PF < 1. If the power factor is not within this range, this function cannot be used. The connections (without neutral conductors) are checked using the setting 4 BL/3 BL/2BL/1 BL. All connections (with neutral conductors) are checked using the 4 NBL and 3 NBL setting.

The following errors are displayed by the EEM-MA600: Error Err 0 Err 1/2/3 Err 4 Err 5 Err 6 Description No error Current transformer connection phase 1/phase 2/phase 3 Voltage between V1/V2 Voltage between V2/V3 Voltage between V3/V1

To eliminate Err 1, Err 2, and Err 3, change the order of the current connections. To eliminate Err 4, Err 5, and Err 6, change the order of the voltage connections of the measuring transducer.

104413_en_00

PHOENIX CONTACT

7-1

EEM-MA600

7.1
Press button
I C

Calling the function test

The test menu is opened when the "test button" is pressed and held down for at least three seconds. The function test is started automatically if a test has not yet been performed.

EMpro

I C

U F

P PF MAX AVG

1x 3 seconds

Figure 7-1

Calling the function test

Hold down the "test button" for at least three seconds. The test starts automatically, and there are no errors in the example.

I C

U F

P PF MAX AVG

1x 3 seconds

Figure 7-2

Calling the function test

Press and hold down the "test button" again for at least three seconds; the device switches to display mode again.

I C

U F

P PF MAX AVG

1x 3 seconds

Figure 7-3

Exiting the function test

7-2

PHOENIX CONTACT

104413_en_00

Function test

7.1.1

Automatic correction of current connections

If the direction of current flow is mixed up due to the connection order being incorrect, the measurement signals can be corrected automatically. It is not necessary to rewire connection terminal blocks S1 (input) and S2 (output). Example: Err 2 Current transformer connection phase 2

I C

U F

P PF MAX AVG

Calling the function test


1x 3 seconds

Selecting correction

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

Activating correction
1x

Confirming entry

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

Exiting function test, display mode


1x 3 seconds

Figure 7-4

Automatic correction of current connections

104413_en_00

PHOENIX CONTACT

7-3

EEM-MA600

7.2

Repeat function test (started manually)

This menu is only displayed if the device has already been tested.

It is possible to perform an entirely new test, as described below.

I C

U F

P PF MAX AVG

Calling the function test


1x 3 seconds

I C

U F

P PF MAX AVG

Selecting repeat function test


1x

I C

U F

P PF MAX AVG

Activating repeat function test


1x

Figure 7-5

Performing repeat function test

Confirm your entries with "OK".

7-4

PHOENIX CONTACT

104413_en_00

Troubleshooting

Troubleshooting
This section contains a list of possible problems that may occur when working with the device. The action to be taken and the way in which the user must respond in order to solve the issue are described for each individual problem.

Error/fault Device not ready for operation Backlighting goes out Voltages = 0 Currents = 0 or faulty Incorrect display of power, power factor, and energy No display of phases

Remedy Check the power supply Check the configuration of the backlighting (see page 5-14) Check the voltage input Check the current input Check the configuration of the current transformer ratios Start the function test Check the configuration of the device (see page 5-4)

104413_en_00

PHOENIX CONTACT

8-1

EEM-MA600

8-2

PHOENIX CONTACT

104413_en_00

Special function modules

Special function modules


The EEM-MA600 can be extended with the following special function modules. Module EEM-MEMO-MA600 EEM-2DIO-MA600 EEM-2AO-MA600 Function Memory module Digital outputs Analog outputs Description in... Section "EEM-MEMO-MA600 configuration" on page 9-2 Section "EEM-2DIO-MA600 configuration" on page 9-15 Section "EEM-2AO-MA600 configuration" on page 9-22

9.1

Connection and installation

You can find information about connecting and installing the special function modules in the associated package inserts at www.phoenixcontact.net/catalog.

9.2

Configuration

The special function modules can be configured using the pushbuttons on the front side of the EEM-MA600. The configuration is shown in the following subsections. To configure the special function modules, press the gray buttons consecutively, as shown in the respective example. In configuration mode, the labeling below the pushbuttons applies.

Button PROG or or or OK

Description Open configuration mode (press and hold for 3 seconds) Select the next menu item Open edit mode In edit mode: select parameters/values to be changed In edit mode: change parameters/values Confirm setting

104413_en_00

PHOENIX CONTACT

9-1

EEM-MA600

9.2.1

EEM-MEMO-MA600 configuration

EEM-RS485-MA600 EEM-ETH-RS485-MA600

Storing positive real power P+: Storing negative real power P-: Storing positive reactive power Q+: Storing negative reactive power Q-: Internal or external synchronization impulse: Measuring time for storing P+/- und Q+/-:

YES; NO

YES; NO

YES; NO

YES; NO

INT; EXT

15'; 20'; 30'; 5'; 8'; 10' Min.

Undervoltage threshold value:

5; 15; 25; 35; 45; 55; 65; 75; 85; 95 %

Undervoltage hysteresis:

2; 3; 4; 5 %

Surge voltage threshold value:

110; 120; 130; 140; 150 %

Surge voltage hysteresis:

2; 3; 4; 5 %

Activating the date/time function:

YES; NO

Setting the date (day-month-year):

Set value

Setting the time (hours-minutes-seconds):

Set value

Figure 9-1

Flowchart

9-2

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.1.1 Storing positive real power P+

Choose which power you would like to save. Example: MEMO P+ = YES

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x Yes 2 x No

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-2

Storing positive real power P+

The same procedure applies for negative real power P-, positive reactive power Q+, and negative reactive power Q-. Storing P+, P-, Q+ and Q- for 31 days with an internal or external 10-minute synchronization impulse. Storage can be for 62 days when either just the real power or the reactive power is stored. Real and reactive energy values are stored in registers 3005...7655 (see "3000 hex: Course of reactive and real energy over set measurement duration (without consideration of transmission ratios)" on page 11-68). These must be allocated by the set measurement duration in order to determine the real and reactive power.

104413_en_00

PHOENIX CONTACT

9-3

EEM-MA600 9.2.1.2 Selection of internal or external synchronization impulse

Select whether synchronization should take place via an internal or external impulse. Example: MEMO TOP = External

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x EXT 2 x INT

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-3

Select internal or external synchronization impulse

9-4

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.1.3 Setting the synchronization time (measurement duration)

Set the measurement duration as shown in the following example. Example: MEMO TIME = 10 minutes

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x 6x

20 min 30 min 5 min 8 min 10 min 15 min

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-4

Setting synchronization time (measurement duration)

104413_en_00

PHOENIX CONTACT

9-5

EEM-MA600 9.2.1.4 Setting the undervoltage threshold value

5 ... 95% of the nominal voltage is set as the undervoltage threshold value. Set the threshold value as shown in the following example. Example: dAtA SAG = 15%

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-5

Setting the undervoltage threshold value

9-6

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.1.5 Setting the undervoltage hysteresis

The undervoltage hysteresis can be set for 2%, 3%, 4% or 5%. Set the hysteresis as shown in the following example. Example: dAtA HYSt = 5%

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-6

Setting the undervoltage threshold value

104413_en_00

PHOENIX CONTACT

9-7

EEM-MA600 9.2.1.6 Setting the surge voltage threshold value

The surge voltage threshold value can be set for 110 ... 150% of the nominal voltage. Set the threshold value as shown in the following example. Example: dAtA SWELL = 115%

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

5x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-7

Setting the surge voltage threshold value

9-8

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.1.7 Setting the surge voltage hysteresis

The surge voltage hysteresis can be set at 2%, 3%, 4% or 5%. Set the hysteresis as shown in the following example. Example: dAtA HYSt = 5%

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-8

Setting the surge voltage hysteresis

104413_en_00

PHOENIX CONTACT

9-9

EEM-MA600 9.2.1.8 Activating the date/time function

Activate the date/time function as shown in the following example. Example: dAtE tIME = YES

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x YES 2 x NO

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-9

Activate date/time function

9-10

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.1.9 Setting the date

Set the date as shown in the following example. Example: dAtE = 19-07-05

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

9x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

7x

Figure 9-10

Set date - 1st part

104413_en_00

PHOENIX CONTACT

9-11

EEM-MA600

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

5x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-11

Set date - 2nd part

9-12

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.1.10 Setting the time

Set the time as shown in the following example. Example: tIME = 14 h 02 min 30 sec

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

4x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

2x

Figure 9-12

Set time - 1st part

104413_en_00

PHOENIX CONTACT

9-13

EEM-MA600

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-13

Set time - 2nd part

9-14

PHOENIX CONTACT

104413_en_00

Special function modules

9.2.2

EEM-2DIO-MA600 configuration

EEM-2DIO-MA600

Output type:

I: I1, I2, I3 current In: neutral conductor current U: conductor voltages (1-2/2-3/3-1) V: conductor voltages against N (1/2/3) P+: total positive real power P-: total negative real power Q+: total positive reactive power Q-: total negative reactive power S: total apparent power PFL: total inductive power factor PFC: total capacitve power factor F: frequency HOUr: operating hours counter THDI: total harmonic distortion of I1, I2, I3 currents THDIN: total harmonic distortion of neutral conductor current THDU: total harmonic distortion of conductor voltages (1-2 / 2-3 / 3-1) THDV: total harmonic distortion of conductor voltages against N (1 / 2 / 3) TC1: EEM-TEMP-MA600 temperature module input TC2: EEM-TEMP-MA600 temperature module input TC3: EEM-TEMP-MA600 temperature module input TC4: EEM-TEMP-MA600 internal temperature PPR: total effective power (trend) QPR: total reactive power (trend) SPR: total apparent power (trend) CDE: control relay state via RS-485 CD-t: control relay state RS-485, return of relay to idle state

Upper switching threshold:

Set value

Lower switching threshold:

Set value

Hysteresis:

10; 20; 30; 40; 50; 60; 70; 80; 90 %

Trigger delay (s):

Set value

Relay output:

NO; NC

Figure 9-14

Flowchart

104413_en_00

PHOENIX CONTACT

9-15

EEM-MA600 9.2.2.1 Setting the output type

Set the output type for the relay output as shown in the following example. Example: Out I A-Cd type = I

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x I: current I1, I2, I3 2 x In: neutral conductor current 3 x U: conductor voltages (1-2/2-3/3-1) 4 x V: conductor voltages against N (1/2/3) 5 x P+: total positive real power 6 x P-: total negative real power 7 x Q+: total positive reactive power 8 x Q-: total negative reactive power 9 x S: total apparent power 10 x PFL: total inductive power factor 11 x PFC: total capacitive power factor 12 x F: frequency 13 x HOUr: operating hours counter 14 x THDI: total harmonic distortion of I1, I2, I3 currents 15 x THDIN: total harmonic distortion of neutral conductor current 16 x THDU: total harmonic distortion of conductor voltages (1-2/2-3/3-1) 17 x THDV: total harmonic distortion of conductor voltages against N (1/2/3) 18 x TC1: EEM-TEMP-MA600 temperature module input 19 x TC2: EEM-TEMP-MA600 temperature module input 20 x TC3: EEM-TEMP-MA600 temperature module input 21 x TC4: EEM-TEMP-MA600 internal temperature 22 x PPR: total real power (trend) 23 x QPR: total reactive power (trend) 24 x SPR: total apparent power (trend) 25 x CDE: control relay state via RS-485 26 x CD-t: control relay state via RS-485, return of relay to idle state

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-15

Setting the output type

9-16

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.2.2 Setting the upper switching threshold

Set the upper switching threshold for the relay as shown in the following example. Example: Out I Ht = 100 kA

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-16

Setting the upper switching threshold

104413_en_00

PHOENIX CONTACT

9-17

EEM-MA600 9.2.2.3 Setting the lower switching threshold

Set the lower switching threshold for the relay as shown in the following example. Example: Out I Lt = 10 kA

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-17

Setting the lower switching threshold

9-18

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.2.4 Setting the hysteresis

Set the hysteresis (10 ... 90%) for the relay as shown in the following example. Example: Out I HYST = 20%

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-18

Setting the hysteresis

104413_en_00

PHOENIX CONTACT

9-19

EEM-MA600 9.2.2.5 Setting the trigger delay

Set the trigger delay (in seconds) for the relay as shown in the following example. Example: Out I TEMPO = 30 s

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-19

Setting the trigger delay

9-20

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.2.6 Setting the relay output

Set the output relay idle state as shown in the following example. NO: relay open in idle state NC: relay closed in idle state Example: Out I RELAY = NO

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-20

Setting the relay output

Repeat the settings for the other relay outputs Out 2, Out 3, Out 4, Out 5, Out 6.

104413_en_00

PHOENIX CONTACT

9-21

EEM-MA600

9.2.3

EEM-2AO-MA600 configuration

EEM-2AO-MA600

Output signal:

0/20 mA; 4/20 mA; 30 V DC

Output type:

I1: I1 current I2: I2 current I3: I3 current In: neutral conductor current U12: conductor voltage (1-2) U23: conductor voltage (2-3) U31: conductor voltage (3-1) V1: conductor voltage against N V2: conductor voltage against N V3: conductor voltage against N P: total real power Q: total reactive power S: total apparent power PFL: total inductive power factor PFC: total capacitive power factor F: frequency ISYS: average value of currents (I1+I2+I3) / 3 USYS: average value of conductor voltages phase/phase (U12 + U23 + U31 ) / 3 VSYS: average value of conductor voltages phase/N (V1 + V2 + V3 ) / 3 PPR: total real power (trend) QPR: total reactive power (trend) SPR: total apparent power (trend) TC1: EEM-TEMP-MA600 temperature module input TC2: EEM-TEMP-MA600 temperature module input TC3: EEM-TEMP-MA600 temperature module input TC4: EEM-TEMP-MA600 temperature module input
Assigning measured value to lower output value 0/4 mA: Assigning measured value to upper output value 20 mA:

Set value

Set value

Figure 9-21

Flowchart

9-22

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.3.1 Setting the output signal

Set the output signal as shown in the following example. Example: Out I 20 MA = 0/20 mA

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x 0/20 mA 2 x 30 V DC 3 x 4/20 mA

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-22

Setting the output signal

104413_en_00

PHOENIX CONTACT

9-23

EEM-MA600 9.2.3.2 Setting the output type

Set the output type as shown in the following example.

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

0 x I1: current I1 1 x I2: current I2 2 x I3: current I3 3 x In: neutral conductor current 4 x U12: conductor voltages (1-2) 5 x U23: conductor voltages (2-3) 6 x U31: conductor voltages (3-1) 7 x V1: conductor voltages against N 8 x V2: conductor voltages against N 9 x V3: conductor voltages against N 10 x P: total real power 11 x Q: total reactive power 12 x S: total apparent power 13 x PFL: total inductive power factor 14 x PFC: total capacitive power factor 15 x F: frequency 16 x ISYS: average current (I1+I2+I3)/3 value 17 x USYS: average phase/phase conductor voltage value (U12 + U23 + U31 )/3 18 x VSYS: average phase/N conductor voltage value (V1 + V2 + V3 )/3 19 x PPR: total real power (trend) 20 x QPR: total reactive power (trend) 21 x SPR: total apparent power (trend) 22 x TC1: EEM-TEMP-MA600 temperature module input 23x TC2: EEM-TEMP-MA600 temperature module input 24 x TC3: EEM-TEMP-MA600 temperature module input 25 x TC4: EEM-TEMP-MA600 internal temperature

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-23

Setting the output type

9-24

PHOENIX CONTACT

104413_en_00

Special function modules 9.2.3.3 Assignment of measured values to lower output value 0 or 4 mA

Set the lower measured value for 0 or 4 mA. Example: Out I 20 mA LV = 1000 kA

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

4x

I C

U F

P PF MAX AVG

1 x K: Kilo 2 x /: A 3 x M: Mega A

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-24

Assign the measured value to the lower output value 0 or 4 mA

104413_en_00

PHOENIX CONTACT

9-25

EEM-MA600 9.2.3.4 Assignment of measured value to upper output value 20 mA

Set the upper measured value to 20 mA. Example: Out I 20 mA HV = 2000 kA

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

4x

I C

U F

P PF MAX AVG

1 x K: Kilo 2 x /: A 3 x M: Mega A

I C

U F

P PF MAX AVG

1x Confirm

Figure 9-25

Assigning measured value to upper output value 20 mA

If the lower and the upper output values are the same, the output value is 0. Configuring the frequency output value: if value is 40 Hz, for example, set value to 4000 Hz. Configuring the power factor output value: if value is 0.5, for example, set to 500; if value is 1, for example, set to 1000. If you assign an alarm to a temperature input, it is automatically triggered if a temperature sensor is not connected. Repeat the settings for the other outputs Out 2, Out 3, Out 4.

9-26

PHOENIX CONTACT

104413_en_00

Communication modules

10 Communication modules
The EEM-MA600 can be extended with different function modules. Module EEM-RS485-MA600 EEM-ETH-MA600 EEM-ETH-RS485-MA600 EEM-PB-MA600 EEM-PB12-MA600 Technology MODBUS Ethernet PROFIBUS Description in... Section "MODBUS" on page 10-1 Section "Ethernet" on page 10-12 Section "PROFIBUS" on page 10-19

10.1
10.1.1

MODBUS
Basics

The data is transmitted for each MODBUS RTU (Remote Terminal Unit) protocol. Communication takes place according to the master-slave procedure. Communication begins when requested by the master (PLC). Each slave (EEM-MA600) has a one-time address (valid range 1 ... 247). If a slave detects that its address is addressed by the master, the slave always sends an answer. The slaves never communicate with each other. They are not able to initiate communication with the master. Connected extension modules write, for example, the analog/digital input and output values to an internal register. The MODBUS master (PLC) can read the individual registers using the PLC address. The data to be transmitted is always present in a fixed frame and is defined as follows: Frame Slave address Function code Address Data Description Here, the slave address is given (valid range 1 ... 247) Here, it is established whether parameters are read or written. Register Address - for example, from the master: which parameters are addressed? - for example, from the slave: content of addressed parameters CRC (Cyclic Redundancy Check) The cyclic redundancy check: test value for data in order to detect errors in data transmission.

Table 10-1 Slave address 05

Example: read device parameters (initiated by the master) Function 03 High quality address C6 Low quality address 5C No. High quality words 00 No. Low quality words 02 CRC 16 3915

104413_en_00

PHOENIX CONTACT

10-1

EEM-MA600

Table 10-2 Slave address 05

Example: answer from a slave (initiated by slave) Function 03 Number of bytes 04 Low quality register value 0011 High quality register value IDDD CRC 16 2FAF

Table 10-3 Slave address 05

Example: write device parameters Function 06 High quality address E0 Low quality address 00 High quality register value 00 Low quality register value 05 CRC 16 7F8D

Each bus device must have a unique address. Slave address 0 is reserved for a broadcast. Function codes in MODBUS Several function codes are defined in MODBUS. They are as follows: Function code 03 Hex 06 Hex 16 Hex Name Read hold register Write single register Write multiple registers Abbreviation R W Description Read device parameters Write individual device parameters word by word, write several device parameters word by word

There are still other function codes, but these are not supported.

10.1.2

Connecting and installing communication module EEM-RS485-MA600

You can find information about connecting and installing the EEM-RS485-MA600 communication module from the associated package inserts at www.phoenixcontact.net/catalog.

10-2

PHOENIX CONTACT

104413_en_00

Communication modules

10.1.3

Configuring communication module EEM-RS485-MA600

The module can be configured using the pushbutton on the front side of the measuring instrument. The configuration is shown in the following subchapters. Button PROG or or or OK Description Open configuration mode (hold down for 3 seconds) Select the next menu item Open edit mode In edit mode: Select parameters/values to be changed In edit mode: change parameters/values Confirm setting

EEM-RS485-MA600

MODBUS address:

0 ... 254 2,4 kBit/s; 4,8 kBit/s; 9,6 kBit/s; 19,2 kBit/s; 38,4 kBit/s Odd; Even; nO

Transmission speed:

Parity:

Stop bits:

1; 2

Figure 10-1

Flow chart

104413_en_00

PHOENIX CONTACT

10-3

EEM-MA600 10.1.3.1 Setting the MODBUS address

Set the MODBUS address as shown in the following example. Example: COM ADR = 7

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x Confirm

Figure 10-2

Setting the MODBUS address

10-4

PHOENIX CONTACT

104413_en_00

Communication modules 10.1.3.2 Setting the transmission speed

Set the transmission speed as shown in the following example. All MODBUS devices must be set to the same transmission speed.

Example: COM BDS = 19200 BDS (bauds)

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x 2x 3x 4x 5x

2.4 kbps 4.8 kbps 9.6 kbps 19.2 kbps 38.4 kbps

I C

U F

P PF MAX AVG

1x Confirm

Figure 10-3 10.1.3.3

Setting the transmission speed Setting the parity

Set the parity as shown in the following example. Example: COM PAR = Even

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x Odd 2 x Even 3 x No

Figure 10-4

Setting the parity

104413_en_00

PHOENIX CONTACT

10-5

EEM-MA600 10.1.3.4 Setting the stop bits

Set the stop bits as shown in the following example. Example: COM STOP = 2

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x 2 bits 2 x 1 bits

I C

U F

P PF MAX AVG

1x Confirm

Figure 10-5

Setting the stop bits

10.1.4

MODBUS / JBUS register tables

You can find the MODBUS/JBUS register tables at Section "MODBUS register" on page 11-1.

10-6

PHOENIX CONTACT

104413_en_00

Communication modules

10.1.5

Reading/writing MODBUS RTU registers

In the following example, some points for testing the MODBUS structure with the "Modbus Poll" simulation software are described. The simulation software is a freeware tool and can be downloaded from the Internet at http://www.modbustools.com/. 10.1.5.1 1. Settings

Open the port settings via "Connection, Connect".

2.

Choose "Connection, Serial Port" as shown in the following example.

104413_en_00

PHOENIX CONTACT

10-7

EEM-MA600 3. Enter the desired serial interface parameters in the fields below. Set "Mode" to RTU.

4.

Confirm the settings with "OK". Access to MODBUS register

10.1.5.2 1. 2. 3. 4. 5.

Open the MODBUS register access settings as follows: "Setup, Read/Write Definition". Set the desired "Slave ID". Under "Function," you can choose the register access type (Read "03" or write "06"/"16"). Under "Address", enter the start address for the desired register. Under "Quantity", enter the register length.

10-8

PHOENIX CONTACT

104413_en_00

Communication modules Example: "Read" function Main measured values read based on current and voltage transducer (see "C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios)" on page 11-2): Hour counter Line voltage U12 1. 2. 3. Data word/decimal address 50512/50513 Data word/decimal address 50514/50515

After you have entered the "Slave ID', choose the "Function" "03 Read Holding Registers". Enter start address 50512 under "Address". Under "Quantity", enter 4 as the number of data words.

4.

Confirm with "OK". The contents of register 5051250515 is displayed.

In order to be able to further use register contents, these must be converted into the corresponding units (see "C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios)" on page 11-2).

104413_en_00

PHOENIX CONTACT

10-9

EEM-MA600 Register 50513 content (hour counter ) = 47032 47032 : 100 = 470.32 h Register 50515 content (line voltage U12) = 35655 35655 : 100 = 356.57 V Example: "Write" function Date time configuration (see "E100 hex: date/time configuration" on page 11-21): 1. After entering the "Slave ID", choose "Function" "16 Write Multiple Registers". 2. Enter start address 57600 under "Address". 3. Enter 6 as the number of data words under "Quantity".

4.

Confirm with "OK".

10-10

PHOENIX CONTACT

104413_en_00

Communication modules 5. Enter the desired date and time in the lines listed below.

Decimal address 57600 57601 57602 57603 57604 57605 Example

Designation Day Month Year Hour Minute Second

Value 22 2 11 9 29 30

Date: 02.22.2011 Time: 09:29:30

104413_en_00

PHOENIX CONTACT

10-11

EEM-MA600

10.2
10.2.1

Ethernet
Connecting and installing communication modules EEM-ETH-MA600 and EEM-ETH-RS485-MA600

You can find information about connecting and installing the EEM-ETH-MA600 and EEM-ETH-RS485-MA600 communication modules from the associated package inserts at www.phoenixcontact.net/catalog.

10.2.2

Configuring communication modules EEM-ETH-MA600 and EEM-ETH-RS485-MA600

The modules can be configured using the pushbutton on the front side of the measuring instrument. The configuration is shown in the following subchapters. Button PROG or or or OK Description Open configuration mode (hold down for 3 seconds) Select the next menu item Open edit mode In edit mode: Select parameters/values to be changed In edit mode: change parameters/values Confirm setting

The default settings are: IP address: Subnet mask: Gateway: DHCP activation: 192.168.1.1 255.255.255.0 0.0.0.0 No

10-12

PHOENIX CONTACT

104413_en_00

Communication modules

EEM-ETH-RS485-MA600 EEM-ETH-MA600

Ethernet address: Set CL. A Repeat setting for CL. B, CL. C, CL. D

Set value

Subnet mask: Set CL. A Repeat setting for CL. B, CL. C, CL. D

Set value

Gateway address: Set CL. A Repeat setting for CL. B, CL. C, CL. D

Set value

DHCP activation:

YES; NO

Figure 10-6 10.2.2.1

Flow chart Setting the IP Address

Set the IP address as shown in the following example. Example: IP address 191.158.1.7 CLASS A = 191

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

Figure 10-7

Setting the Class A IP address

104413_en_00

PHOENIX CONTACT

10-13

EEM-MA600 Example: IP address CLASS B = 158

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

Figure 10-8

Setting the Class B IP address

Example: IP address CLASS C = 1

I C

U F

P PF MAX AVG

3x

Figure 10-9

Setting the Class C IP address

10-14

PHOENIX CONTACT

104413_en_00

Communication modules Example: IP address CLASS D = 7

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

6x

I C

U F

P PF MAX AVG

1x

Figure 10-10 10.2.2.2

Setting the Class D IP address

Setting the subnet mask

Set the subnet mask as shown in the following example. Example: Setting subnet mask 255.255.255.0 The principle is the same as with the IP address (see Section "Setting the IP Address" on page 10-13).

I C

U F

P PF MAX AVG

4x

Figure 10-11

Setting the subnet mask

104413_en_00

PHOENIX CONTACT

10-15

EEM-MA600 10.2.2.3 Setting the gateway address

Set the gateway address as shown in the following example. Example: Gateway address 0.0.0.0 The principle is the same as with the IP address (see Section "Setting the IP Address" on page 10-13).

I C

U F

P PF MAX AVG

4x

Figure 10-12 10.2.2.4

Setting the gateway address

Setting DHCP

Activate the DHCP as shown in the following example. DHCP activation is not recommended. If necessary, contact your network administrator.

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1x

Figure 10-13

Setting DHCP

10-16

PHOENIX CONTACT

104413_en_00

Communication modules

10.2.3

MODBUS / JBUS register tables

The register tables are the same as for MODBUS/JBUS communication (see Section "MODBUS register" on page 11-1).

10.2.4

Reading/writing MODBUS TCP registers

In the following example, some points for testing the Ethernet MODBUS structure with the "Modbus Poll" simulation software are described. The simulation software is a freeware tool and can be downloaded from the Internet at http://www.modbustools.com/. 1. Open the interface settings via "Connection, Connect".

2.

Choose as shown in the following example under "Connection, Modbus TCP/IP".

104413_en_00

PHOENIX CONTACT

10-17

EEM-MA600 3. Enter the desired IP addresses in the fields below (the first three address areas for the IP addresses must be the same for the PC and the EEM-MA600 when 255.255.255.0 is set as the subnet mask). Set the port to 502 (direct access to the connected measuring instrument EEM-MA600 with Ethernet extension module) or 503 (access via the gateway to connected Modbus devices).

4.

5.

Confirm the settings with "OK".

10.2.5

Access to MODBUS register

See Section "Reading/writing MODBUS TCP registers" on page 10-17.

10.2.6

"Read" and "Write" function

See Section "Reading/writing MODBUS RTU registers" on page 10-7.

10.2.7

Web server

You can have the most important current and average measured values and tallies displayed via the web server. By entering the device IP address in the Internet browser, you can access the web server. Example: IP address of measuring instrument EEM-MA600: URL address: 192.168.1.0 http://192.168.1.0/index.htm

10-18

PHOENIX CONTACT

104413_en_00

Communication modules

10.3
10.3.1

PROFIBUS
Basics

The PROFIBUS is a serial bus system that transmits data between control systems and spatially distributed I/O terminals, to which sensors and actuators are connected. The PROFIBUS has a star/tree structure. In the PROFIBUS topology, the individual devices are differentiated on the basis of their addressing. The communication profiles determine how the devices transmit their data serially via the bus. The PROFIBUS DP (distributed I/O) is typically a single-master system, i.e. all devices of a PROFIBUS DP are controlled by one master. PROFIBUS DP is optimized for the straightforward transmission of input and output data and is specifically designed for communication between automation systems and distributed I/O devices. The characteristic communication features of a PROFIBUS DP device are defined in the form of an electronic device data sheet (GSD, device database file). The required GSD file for the measuring instrument is available at www.phoenixcontact.net/catalog.

10.3.2

Connecting and installing communication modules EEM-PB-MA600 and EEM-PB12-MA600

You can find information about connecting and installing communication modules EEM-PB-MA600 and EEM-PB12-MA600 from the associated package inserts at www.phoenixcontact.net/catalog.

104413_en_00

PHOENIX CONTACT

10-19

EEM-MA600

10.3.3

Configuring communication modules EEM-PB-MA600 and EEM-PB12-MA600

Install the GSD file first. The communication module automatically adjusts itself to the speed specified by the PROFIBUS master. The module can be configured using the pushbutton on the front side of the measuring instrument. The configuration is shown in the following subchapters. Button PROG or or or OK Description Open configuration mode (hold down for 3 seconds) Select the next menu item Open edit mode In edit mode: select parameters/values to be changed In edit mode: change parameters/values Confirm setting

EEM-PB-MA600 EEM-PB12-MA600

PROFIBUS adress:

Set value

Diagnostics:

YES; NO

Activating automatic parameterization via the PROFIBUS master:

YES; NO

Figure 10-14

Flow chart EEM-PB-MA600 and EEM-PB12-MA600

10-20

PHOENIX CONTACT

104413_en_00

Communication modules 10.3.3.1 Setting the PROFIBUS address

Set the PROFIBUS address as shown in the following example. Example: COM ADR = 7

I C

U F

P PF MAX AVG

3x

I C

U F

P PF MAX AVG

2x

I C

U F

P PF MAX AVG

1x Confirm

Figure 10-15

Setting the PROFIBUS address

104413_en_00

PHOENIX CONTACT

10-21

EEM-MA600 10.3.3.2 Setting the diagnostics function

The diagnostic function shows the following: Availability of extension modules Serial number of the device Availability of an alarm or overrun Example: COM DIAG = No

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x NO 2 x YES

I C

U F

P PF MAX AVG

1x Confirm

Figure 10-16 10.3.3.3

Setting diagnostic function

Activating automatic parameterization via the PROFIBUS master

With this function, you can activate or deactivate EEM-MA600 parameterization via the PROFIBUS DP master. YES When the measuring instrument is restarted, the device settings are loaded from the GSD file. The information from the GSD file is sent by the PROFIBUS master to the slaves. The last device settings are saved upon restarting.

NO

10-22

PHOENIX CONTACT

104413_en_00

Communication modules Example: COM PARA = YES

I C

U F

P PF MAX AVG

1x

I C

U F

P PF MAX AVG

1 x NO 2 x YES

I C

U F

P PF MAX AVG

1x Confirm

Figure 10-17

Setting automatic parameterization

10.3.4

PROFIBUS register tables

The PROFIBUS register tables are at Section "PROFIBUS register" on page 12-1.

10.3.5

Starting a PROFIBUS configuration

In the following example, some points about PROFIBUS configuration startup are described. This includes hardware implementation (EEM-MA600), calling the variable tables with parameter reading/controlling and importing/transferring parameters in the software. 10.3.5.1 Installing a GSD file

In a new or existing project, the EEM-MA600 should be inserted. The GSD file must be installed first. The required GSD file for the measuring instrument is available at www.phoenixcontact.net/catalog. It can be added in the HW configuration under "Extras".

104413_en_00

PHOENIX CONTACT

10-23

EEM-MA600 10.3.5.2 1. 2. Add EEM-MA600 to hardware

Load your master project after the GSD file installation is successfully implemented. Under the path on the right-hand side, you will find measuring instrument EEM-MA600 under "PROFIBUS DP, Additional field devices, General". This can be linked to the bus through "Drag&Drop". Then a window will automatically be displayed where the module is assigned an address and a name/description for the EEM-MA600 can be given. If the EEM-MA600 already has an assigned address, this should be chosen. When delivered, the EEM-MA600 has address 5.

10-24

PHOENIX CONTACT

104413_en_00

Communication modules 3. After you add the measuring instrument to your PROFIBUS configuration, the EEM-MA600 must still be assigned the desired register tables (see Section "Module 1 "Main values"" on page 12-5, Section "Module 2 "Additional values"" on page 12-11, etc.) and the addresses for the particular inputs and outputs. Only the start address is given, since the prefabricated tables have fixed lengths and the end results from this length. The register tables are available on the right side under "MA600".

104413_en_00

PHOENIX CONTACT

10-25

EEM-MA600 4. You can drag the desired register tables via "Drag&Drop" from the right to the lower left area. The maximum table size is 155 bytes (Input: 95 bytes, output 60 bytes).

5.

Double-click on the green-highlighted area to open the "Properties - DP slave" window. Here, you can determine the start address for input and output registers (for example, start address output: 256, start address input: 256).

6. 7.

Save the changes described above with "Save and compile". Load the changes with "Download to module" in the controller.

10-26

PHOENIX CONTACT

104413_en_00

Communication modules 10.3.5.3 1. 2. 3. Variable table

After the new configuration is loaded, switch to the Simatic Manager window. Under "S7 program", right-click on "Function blocks". In the next window, choose "Insert New Object, Variable Table".

4.

In the variable table, the outputs for previously entered modules can be controlled and the inputs read back. Access takes place via the input and output addresses set in the hardware configuration. The necessary quantities (bytes, words, double words) for the read and displayed data are described in the register tables.

You can, for example, read back the voltages for the individual phases as shown in the following example, Module 1: "Main values" (see Section "Module 1 "Main values"" on page 12-5). Example start address 0 (Register size 2 bytes) IW 14 IW 16 W 18 V1: Conductor voltage against N (V/ 100) V2: Conductor voltage against N (V/ 100) V3: Conductor voltage against N (V/ 100) Measured value: 110,10 V Measured value: 109,97 V Measured value: 109,93 V

Example start address 10 If you have set the start address from 0 to 10 instead, you will find the three words to be read back in the variable tables under: IW 24 IW 26 IW 28 Abbreviations for the tables include: (when English is the set language, these abbreviations can deviate for other language settings) IB IW ID Input byte Input word Input double word QB QW QD Output byte Output word Output double word Input word 10+14=24

104413_en_00

PHOENIX CONTACT

10-27

EEM-MA600 To display the measured values in the table under input words, you must first create a connection to the connected PROFIBUS device. Establish a connection with the "Set Up Connection to Directly Connected CPU" button. When you click on the "Monitor variable" button, the measured values for the values delivered from EEM-MA600 will be specified in the register upon updating.

10.3.5.4

Module 9 Special table

With Module 9, you can compile a specific table from the values from the special tables. This has a length of 33 bytes, with the first byte reserved for the table number. You can freely choose the table number (bit 0...6). In order to write values in the special table and/or have them read out from the table, bit 7 from input byte 1 for the output value must be set to 1. 16 words can be compiled with the desired data. Then, the addresses for the chosen values are written in the following, up to 16 output words, and the table is defined. The readout then takes place as with all other tables. Set output values using the "Modify variable" command. You can activate this by rightclicking on a value or with Ctrl+F9 or the "Variable, Modify" tab. With the help of the "Insert, Range of variables" menu item, a set of input/output values can be added, such as when several values should be added for a type consecutively (for example, IW 0 to IW 27, QW 0 to QW 27).

10-28

PHOENIX CONTACT

104413_en_00

Communication modules Example Tables No. 0 Bit 7 Binary Decimal 1 128 Bit 6 0 Bit 5 0 Bit 4 0 Bit 3 0 Bit 2 0 Bit 1 0 Bit 0 0

Bit 7 must always be set to 1 in order to write values in the special tables and/or to have the table read back.

104413_en_00

PHOENIX CONTACT

10-29

EEM-MA600

10-30

PHOENIX CONTACT

104413_en_00

MODBUS register

11 MODBUS register
In this section, you will find the following registers. Table 11-1 Start address C550 hex C650 hex C750 hex C850 hex 370 hex 741 hex C900 hex C950 hex CB00 hex E000 hex E100 hex E110 hex E200 hex 7700 hex 100 hex 200 hex 400 hex C10 hex D00 hex Register overview Description Display of current main measured values based on current and voltage transducer (under consideration of transmission ratios) Energy values display Display of average values based on current and voltage transducer via the set measurement duration (under consideration of transmission ratios) Display of current main measured values not based on current and voltage transducer (without consideration of transmission ratios) Display of current average current/voltage value based on current and voltage transducer (under consideration of transmission ratios) Display of current average current/voltage value not based on current and voltage transducer (without consideration of transmission ratios) Temperature inputs display Display of current harmonic distortion and harmonics Status of inputs/outputs Measuring instrument terminal configuration Date/time configuration Ethernet communication module configuration Saving configuration and restart for measuring instrument Display of last alarm to digital outputs (EEM-2DIO-MA600) Information about connected extension modules Extension module display and configuration Reset measured values Alarm history display (course of last 10 alarms) Undervoltage (course of last 10 SAG threshold value undervoltages) On page... Table 11-2 on page 11-2 Table 11-3 on page 11-3 Table 11-4 on page 11-5 Table 11-5 on page 11-7 Table 11-6 on page 11-8 Table 11-7 on page 11-9 Table 11-8 on page 11-9 Table 11-9 on page 11-10 Table 11-10 on page 11-20 Table 11-11 on page 11-20 Table 11-13 on page 11-21 Table 11-14 on page 11-22 Table 11-15 on page 11-23 Table 11-17 on page 11-24 Table 11-18 on page 11-28 Table 11-19 on page 11-29 Table 11-20 on page 11-39 Table 11-21 on page 11-42 Table 11-22 on page 11-47

104413_en_00

PHOENIX CONTACT

11-1

EEM-MA600 Table 11-1 Start address E00 hex F00 hex 1000 hex 3000 hex 8000 hex 9000 hex Register overview [...] Description Surge voltage (course of last 10 SWELL surge voltages) Current minimum and maximum measured values (measurement duration of 1 s) Supply voltage failure (course of last 10 voltage interruptions) Course of reactive and real energy over set measurement duration (without consideration of transmission ratios) Course of average values for voltages over the set measurement duration Course of average values for frequency over the set measurement duration On page... Table 11-23 on page 11-53 Table 11-24 on page 11-58 Table 11-25 on page 11-65 Table 11-26 on page 11-68 Table 11-27 on page 11-68 Table 11-28 on page 11-69

Table 11-2

C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios) Hexadecimal address C550 C552 C554 C556 C558 C55A C55C C55E C560 C562 C564 C566 C568 C56A C56C C56E C570 C572 C574 C576 Number of data words 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Designation Unit Register access R R R R R R R R R R R R R R R R R R R R Available through extension module

Decimal address 50512 50514 50516 50518 50520 50522 50524 50526 50528 50530 50532 50534 50536 50538 50540 50542 50544 50546 50548 50550

Hour: operating hours counter U12: line voltage (1-2) U23: line voltage (2-3) U31: line voltage (3-1) V1: line voltage against N V2: line voltage against N V3: line voltage against N F: frequency I1: current I2: current I3: current In: neutral conductor current P: total real power +/Q: total reactive power +/S: total apparent power PF: total power factor -: capacitive and + : inductive P1: real power phase 1 +/P2: real power phase 2 +/P3: real power phase 3 +/Q1: reactive power phase 1 +/-

h/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA mA mA kW/100 kvar/100 kVA/100 0.001 kW/100 kW/100 kW/100 kvar/100

11-2

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-2 C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios) [...] Hexadecimal address C578 C57A C57C C57E C580 C582 C584 C586 C588 C58A C58C Number of data words 2 2 2 2 2 2 2 2 2 2 2 Designation Unit Register access R R R R R R R R R R R Available through extension module

Decimal address 50552 50554 50556 50558 50560 50562 50564 50566 50568 50570 50572

Q2: reactive power phase 2 +/Q3: reactive power phase 3 +/S1: apparent power phase 1 S2: apparent power phase 2 S3: apparent power phase 3 PF1: power factor phase 1 -: capacitive and + : inductive PF2: power factor phase 2 -: capacitive and + : inductive PF3: power factor phase 3 -: capacitive and + : inductive Not available Not available Not available

kvar/100 kvar/100 kVA/100 kVA/100 kVA/100 0.001 0.001 0.001 -

Range extension: 62 words (decimal) or 3E words (hexadecimal).

Table 11-3 Decimal address 50768 50770 50772 50774 50776 50778 50780 50782 50784 50786 50788 50790 50792 50794 50796 50798

C650 hex: energy value display Hexadecimal Number Designation address of data words C650 C652 C654 C656 C658 C65A C65C C65E C660 C662 C664 C666 C668 C66A C66C C66E 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Hour: operating hours counter Not available Not available Not available Not available Not available Ea+: current positive real energy Er +: current positive reactive energy Es: current apparent energy Ea-: current negative real energy Er -: current negative reactive energy No. digital inputs (max 6) Counter reading digital input DI 1 Counter reading digital input DI 2 Counter reading digital input DI 3 Counter reading digital input DI 4 Unit Register Available through access extension module R R R R R R R R R R R R R R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

h/100 kWh kvarh kVAh kWh kvarh -

104413_en_00

PHOENIX CONTACT

11-3

EEM-MA600 Table 11-3 Decimal address 50800 50802 50804 50806 50808 50810 50812 50814 50816 50818 50820 50822 50824 50826 50828 50829 50830 50831 50832 C650 hex: energy value display [...] Hexadecimal Number Designation address of data words C670 C672 C674 C676 C678 C67A C67C C67E C680 C682 C684 C686 C688 C68A C68C C68D C68E C68F C690 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 Counter reading digital input DI 5 Counter reading digital input DI 6 Not available Not available Not available Not available PPR: total real power over set measurement duration (trend) QPR: total reactive power over set measurement duration (trend) SPR: total apparent power over set measurement duration (trend) Ea+: current positive real energy over set measurement duration Ea-: current negative real energy over set measurement duration Er+: current positive reactive energy over set measurement duration Er-: current negative reactive energy over set measurement duration Not available Not available Not available Not available Not available Not available Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R EEM-2DIO-MA600 EEM-2DIO-MA600

kW/100 kvar/100 kVA/100 kWh/10 kWh/10 kvarh/10 kvarh/10 -

Range extension: 65 words (decimal) or 41 words (hexadecimal). Example: In order to read the positive real energy from address C65C, the following data sequence must be sent: Slave address 05 Function 03 High quality address C6 Low quality address 5C No. High quality words 00 No. Low quality words 02 CRC 16 3915

11-4

PHOENIX CONTACT

104413_en_00

MODBUS register EEM-MA600 answer: the register contents correspond to a positive real energy of 177645 kWh. Slave address 05 Function 03 Number of bytes Low quality register value 04 0011 17 High quality register value IDDD 7645 CRC 16 2FAF

Table 11-4

C750 hex: display of average values based on current and voltage transducer via the set measurement duration (under consideration of transmission ratios) Hexadecimal Number Designation address of data words C750 C752 C754 C756 C758 C75A C75C C75E C760 C762 C764 C766 C768 C76A C76C C76E C770 C772 C774 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Avg U12: average line voltage value Avg U23: average line voltage value Avg U31: average line voltage value Avg V1: average line voltage value against N Avg V2: average line voltage value against N Avg V3: average line voltage value against N Avg F: average frequency value Avg I1: current average value Avg I2: current average value Avg I3: current average value Avg In: neutral conductor current average value Avg P+: average total positive real power value Avg P-: average total negative real power value Avg Q+: average total positive reactive power value Avg Q-: average total negative reactive power value Avg S: average total apparent power value Avg U12: average line voltage value Avg U23: average line voltage value Avg U31: average line voltage value Unit Register access R R R R R R R R R R R R R R R R R R R Available through extension module

Decimal address 51024 51026 51028 51030 51032 51034 51036 51038 51040 51042 51044 51046 51048 51050 51052 51054 51056 51058 51060

V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA mA mA kW/100 kW/100 kvar/100 kvar/100 kVA/100 V/100 V/100 V/100

104413_en_00

PHOENIX CONTACT

11-5

EEM-MA600 Table 11-4 C750 hex: display of average values based on current and voltage transducer via the set measurement duration (under consideration of transmission ratios) [...] Hexadecimal Number Designation address of data words C776 C778 C77A C77C C77E C780 C782 C784 C786 C788 C78A C78C C78E C790 C791 C792 C793 C794 C795 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 Max/avg V1: maximum value for line voltage against N Max/avg V2: maximum value for line voltage against N Max/avg V3: maximum value for line voltage against N Unit Register access R R R R R R R R R R R R R R R R R R R Available through extension module

Decimal address 51062 51064 51066 51068 51070 51072 51074 51076 51078 51080 51082 51084 51086 51088 51089 51090 51091 51092 51093

V/100 V/100 V/100

Max/avg F: maximum frequency value Hz/100 Max/avg I1: maximum current value Max/avg I2: maximum current value Max/avg I3: maximum current value Max/avg In: maximum current value Max/avg P+: maximum total positive real power value Max/avg P-: maximum total negative real power value Max/avg Q+: maximum total positive reactive power value Max/avg Q-: maximum total negative reactive power value Max/avg S: maximum total apparent power value Not available Not available Not available Not available Not available Not available mA mA mA mA kW/100 kW/100 kvar/100 kvar/100 kVA/100 -

Range extension: 70 words (decimal) or 46 words (hexadecimal).

11-6

PHOENIX CONTACT

104413_en_00

MODBUS register

When you use this table, you must multiply the values by the transmission ratios for the converter used.

Table 11-5

C850 hex: display of current main measured values not based on current and voltage transducer (without consideration of transmission ratios) Hexadecimal Number address of data words C850 C851 C852 C853 C854 C855 C856 C857 C858 C859 C85A C85B C85C C85D C85E C85F C860 C861 C862 C863 C864 C865 C866 C867 C868 C869 C86A C86B 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Designation Unit Register access R R R R R R R R R R R R R R R R R R R R R R R R R R R R Available through extension module

Decimal address 51280 51281 51282 51283 51284 51285 51286 51287 51288 51289 51290 51291 51292 51293 51294 51295 51296 51297 51298 51299 51300 51301 51302 51303 51304 51305 51306 51307

Hour: operating hours counter U12: line voltage U23: line voltage U31: line voltage V1: line voltage against N V2: line voltage against N V3: line voltage against N F: frequency I1: current I2: current I3: current In: neutral conductor current P: total real power +/Q: total reactive power +/S: total apparent power PF: total power factor -: capacitive and + : inductive P1: real power phase 1 +/P2: real power phase 2 +/P3: real power phase 3 +/Q1: reactive power phase 1 +/Q2: reactive power phase 2 +/Q3: reactive power phase 3 +/S1: apparent power phase 1 S2: apparent power phase 2 S3: apparent power phase 3 PF1: power factor phase 1 -: capacitive and + : inductive PF2: power factor phase 2 -: capacitive and + : inductive PF3: power factor phase 3 -: capacitive and + : inductive

h/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA mA mA kW/100 kvar/100 kVA/100 0.001 kW/100 kW/100 kW/100 kvar/100 kvar/100 kvar/100 kVA/100 kVA/100 kVA/100 0.001 0.001 0.001

104413_en_00

PHOENIX CONTACT

11-7

EEM-MA600 Table 11-5 C850 hex: display of current main measured values not based on current and voltage transducer (without consideration of transmission ratios) [...] Hexadecimal Number address of data words C86C C86D C86E C86F C870 C871 C872 1 1 1 1 1 1 1 Designation Unit Register access R R R MWh R R MWh R R Available through extension module

Decimal address 51308 51309 51310 51311 51312 51313 51314

Not available Not available Not available EA+: Total positive real energy since startup (cannot be reset) Not available EA-: total negative real energy since startup (cannot be reset) Not available

Range extension: 35 words (decimal) or 23 words (hexadecimal). Example: To have all values from table C850 with a length of 35 words read out with one query, the following data sequence must be sent: Slave address 05 Function 03 High quality address C8 Low quality address 50 No. High quality words 00 No. Low quality words 35 CRC 16 BA28

Table 11-6

370 Hex: display of current average current/voltage value based on current and voltage transducer (under consideration of transmission ratios) Hexadecimal address 370 372 374 Number of data words 2 2 2 Designation Unit Register Available through access extension module R R R -

Decimal address 880 882 884

ISYS: current average value ( I1+I2+I3)/3 USYS: line voltages (U12 + U23 + U31)/3 average value

mA V/100

VSYS: average value of line V/100 voltages against N (V1 + V2 + V3 )/3

Range extension: 6 words (decimal) or 6 words (hexadecimal)

11-8

PHOENIX CONTACT

104413_en_00

MODBUS register

When you use this table, you must multiply the values by the transmission ratios for the converter used.

Table 11-7

741 hex: display of current average current/voltage value not based on current and voltage transducer (without consideration of transmission ratios) Hexadecimal address 741 742 743 Number of data words 1 1 1 Designation Unit Register Available through access extension module R R R -

Decimal address 1857 1858 1859

ISYS: current average value ( I1+I2+I3)/3 USYS: line voltages (U12 + U23 + U31)/3 average value VSYS: average value of line voltages against N (V1 + V2 + V3 )/3

mA V/10 V/10

Range extension: 3 words (decimal) or 3 words (hexadecimal)

Table 11-8 Decimal address 51456 51457 51458 51459 51460 51461 51462 51463

C900 hex: temperature inputs display Hexadecimal Number address of data words C900 C901 C902 C903 C904 C905 C906 C907 1 1 1 1 1 1 1 1 Designation Unit Register access R R R R R R R R EEM-TEMP-MA600 EEM-TEMP-MA600 EEM-TEMP-MA600 EEM-TEMP-MA600 Available through extension module

Internal temperature sensor available Internal module temperature Number of temperature sensors (0-3 max) connected External temperature 1 External temperature 2 External temperature 3 Not available Not available

Yes(1)/No(0) C C C C -

Range extension: 8 words (decimal) or 8 words (hexadecimal)

104413_en_00

PHOENIX CONTACT

11-9

EEM-MA600

Table 11-9 Decimal address

C950 hex: display of current harmonic distortion and harmonics Hexadecimal address Number Designation of data words Unit Register Available through access extension module

Total THD harmonic distortion 51536 51537 51538 51539 51540 51541 51542 51543 51544 51545 C950 C951 C952 C953 C954 C955 C956 C957 C958 C959 1 1 1 1 1 1 1 1 1 1 THD U12: total harmonic distortion of line voltage THD U23: total harmonic distortion of line voltage THD U31: total harmonic distortion of line voltage THD V1: total harmonic distortion of line voltage against N THD V2: total harmonic distortion of line voltage against N THD V3: total harmonic distortion of line voltage against N THD I1: total harmonic distortion of current THD I2: total harmonic distortion of current THD I3: total harmonic distortion of current THD In: total harmonic distortion of neutral conductor current 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R R R

Range extension: 10 words (decimal) or A words (hexadecimal). Individual harmonic content for currents: I 51546 51547 51548 51549 51550 51551 51552 51553 51554 51555 51556 51557 51558 51559 51560 C95A C95B C95C C95D C95E C95F C960 C961 C962 C963 C964 C965 C966 C967 C968 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Highest ascertainable harmonic (63) Content of 3rd harmonic I1 Content of 3rd harmonic I2 Content of 3rd harmonic I3 Content of 3rd harmonic IN Content of 5th harmonic I1 Content of 5th harmonic I2 Content of 5th harmonic I3 Content of 5th harmonic IN Content of 7th harmonic I1 Content of 7th harmonic I2 Content of 7th harmonic I3 Content of 7th harmonic IN Content of 9th harmonic I1 Content of 9th harmonic I2 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R R R R R R R

11-10

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-9 Decimal address 51561 51562 51563 51564 51565 51566 51567 51568 51569 51570 51571 51572 51573 51574 51575 51576 51577 51578 51579 51580 51581 51582 51583 51584 51585 51586 51587 51588 51589 51590 51591 51592 51593 51594 51595 51596 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C969 C96A C96B C96C C96D C96E C96F C970 C971 C972 C973 C974 C975 C976 C977 C978 C979 C97A C97B C97C C97D C97E C97F C980 C981 C982 C983 C984 C985 C986 C987 C988 C989 C98A C98B C98C Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 9th harmonic I3 Content of 9th harmonic IN Content of 11th harmonic I1 Content of 11th harmonic I2 Content of 11th harmonic I3 Content of 11th harmonic IN Content of 13th harmonic I1 Content of 13th harmonic I2 Content of 13th harmonic I3 Content of 13th harmonic IN Content of 15th harmonic I1 Content of 15th harmonic I2 Content of 15th harmonic I3 Content of 15th harmonic IN Content of 17th harmonic I1 Content of 17th harmonic I2 Content of 17th harmonic I3 Content of 17th harmonic IN Content of 19th harmonic I1 Content of 19th harmonic I2 Content of 19th harmonic I3 Content of 19th harmonic IN Content of 21st harmonic I1 Content of 21st harmonic I2 Content of 21st harmonic I3 Content of 21st harmonic IN Content of 23rd harmonic I1 Content of 23rd harmonic I2 Content of 23rd harmonic I3 Content of 23rd harmonic IN Content of 25th harmonic I1 Content of 25th harmonic I2 Content of 25th harmonic I3 Content of 25th harmonic IN Content of 27th harmonic I1 Content of 27th harmonic I2 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

104413_en_00

PHOENIX CONTACT

11-11

EEM-MA600 Table 11-9 Decimal address 51597 51598 51599 51600 51601 51602 51603 51604 51605 51606 51607 51608 51609 51610 51611 51612 51613 51614 51615 51616 51617 51618 51619 51620 51621 51622 51623 51624 51625 51626 51627 51628 51629 51630 51631 51632 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C98D C98E C98F C990 C991 C992 C993 C994 C995 C996 C997 C998 C999 C99A C99B C99C C99D C99E C99F C9A0 C9A1 C9A2 C9A3 C9A4 C9A5 C9A6 C9A7 C9A8 C9A9 C9AA C9AB C9AC C9AD C9AE C9AF C9B0 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 27th harmonic I3 Content of 27th harmonic IN Content of 29th harmonic I1 Content of 29th harmonic I2 Content of 29th harmonic I3 Content of 29th harmonic IN Content of 31st harmonic I1 Content of 31st harmonic I2 Content of 31st harmonic I3 Content of 31st harmonic IN Content of 33rd harmonic I1 Content of 33rd harmonic I2 Content of 33rd harmonic I3 Content of 33rd harmonic IN Content of 35th harmonic I1 Content of 35th harmonic I2 Content of 35th harmonic I3 Content of 35th harmonic IN Content of 37th harmonic I1 Content of 37th harmonic I2 Content of 37th harmonic I3 Content of 37th harmonic IN Content of 39th harmonic I1 Content of 39th harmonic I2 Content of 39th harmonic I3 Content of 39th harmonic IN Content of 41st harmonic I1 Content of 41st harmonic I2 Content of 41st harmonic I3 Content of 41st harmonic IN Content of 43rd harmonic I1 Content of 43rd harmonic I2 Content of 43rd harmonic I3 Content of 43rd harmonic IN Content of 45th harmonic I1 Content of 45th harmonic I2 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

11-12

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-9 Decimal address 51633 51634 51635 51636 51637 51638 51639 51640 51641 51642 51643 51644 51645 51646 51647 51648 51649 51650 51651 51652 51653 51654 51655 51656 51657 51658 51659 51660 51661 51662 51663 51664 51665 51666 51667 51668 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C9B1 C9B2 C9B3 C9B4 C9B5 C9B6 C9B7 C9B8 C9B9 C9BA C9BB C9BC C9BD C9BE C9BF C9C0 C9C1 C9C2 C9C3 C9C4 C9C5 C9C6 C9C7 C9C8 C9C9 C9CA C9CB C9CC C9CD C9CE C9CF C9D0 C9D1 C9D2 C9D3 C9D4 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 45th harmonic I3 Content of 45th harmonic IN Content of 47th harmonic I1 Content of 47th harmonic I2 Content of 47th harmonic I3 Content of 47th harmonic IN Content of 49th harmonic I1 Content of 49th harmonic I2 Content of 49th harmonic I3 Content of 49th harmonic IN Content of 51st harmonic I1 Content of 51st harmonic I2 Content of 51st harmonic I3 Content of 51st harmonic IN Content of 53rd harmonic I1 Content of 53rd harmonic I2 Content of 53rd harmonic I3 Content of 53rd harmonic IN Content of 55th harmonic I1 Content of 55th harmonic I2 Content of 55th harmonic I3 Content of 55th harmonic IN Content of 57th harmonic I1 Content of 57th harmonic I2 Content of 57th harmonic I3 Content of 57th harmonic IN Content of 59th harmonic I1 Content of 59th harmonic I2 Content of 59th harmonic I3 Content of 59th harmonic IN Content of 61st harmonic I1 Content of 61st harmonic I2 Content of 61st harmonic I3 Content of 61st harmonic IN Content of 63rd harmonic I1 Content of 63rd harmonic I2 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

104413_en_00

PHOENIX CONTACT

11-13

EEM-MA600 Table 11-9 Decimal address 51669 51670 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C9D5 C9D6 Number Designation of data words 1 1 Content of 63rd harmonic I3 Content of 63rd harmonic IN Unit Register Available through access extension module R R

0.10% 0.10%

Range extension: 125 words (decimal) or 7D words (hexadecimal) Individual harmonic content for line voltages: U (phase/phase) 51671 51672 51673 51674 51675 51676 51677 51678 51679 51680 51681 51682 51683 51684 51685 51686 51687 51688 51689 51690 51691 51692 51693 51694 51695 51696 51697 51698 51699 51700 51701 51702 C9D7 C9D8 C9D9 C9DA C9DB C9DC C9DD C9DE C9DF C9E0 C9E1 C9E2 C9E3 C9E4 C9E5 C9E6 C9E7 C9E8 C9E9 C9EA C9EB C9EC C9ED C9EE C9EF C9F0 C9F1 C9F2 C9F3 C9F4 C9F5 C9F6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Highest ascertainable harmonic (63) Content of 3rd harmonic U12 Content of 3rd harmonic U23 Content of 3rd harmonic U31 Content of 5th harmonic U12 Content of 5th harmonic U23 Content of 5th harmonic U31 Content of 7th harmonic U12 Content of 7th harmonic U23 Content of 7th harmonic U31 Content of 9th harmonic U12 Content of 9th harmonic U23 Content of 9th harmonic U31 Content of 11th harmonic U12 Content of 11th harmonic U23 Content of 11th harmonic U31 Content of 13th harmonic U12 Content of 13th harmonic U23 Content of 13th harmonic U31 Content of 15th harmonic U12 Content of 15th harmonic U23 Content of 15th harmonic U31 Content of 17th harmonic U12 Content of 17th harmonic U23 Content of 17th harmonic U31 Content of 19th harmonic U12 Content of 19th harmonic U23 Content of 19th harmonic U31 Content of 21st harmonic U12 Content of 21st harmonic U23 Content of 21st harmonic U31 Content of 23rd harmonic U12 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

11-14

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-9 Decimal address 51703 51704 51705 51706 51707 51708 51709 51710 51711 51712 51713 51714 51715 51716 51717 51718 51719 51720 51721 51722 51723 51724 51725 51726 51727 51728 51729 51730 51731 51732 51733 51734 51735 51736 51737 51738 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C9F7 C9F8 C9F9 C9FA C9FB C9FC C9FD C9FE C9FF CA00 CA01 CA02 CA03 CA04 CA05 CA06 CA07 CA08 CA09 CA0A CA0B CA0C CA0D CA0E CA0F CA10 CA11 CA12 CA13 CA14 CA15 CA16 CA17 CA18 CA19 CA1A Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 23rd harmonic U23 Content of 23rd harmonic U31 Content of 25th harmonic U12 Content of 25th harmonic U23 Content of 25th harmonic U31 Content of 27th harmonic U12 Content of 27th harmonic U23 Content of 27th harmonic U31 Content of 29th harmonic U12 Content of 29th harmonic U23 Content of 29th harmonic U31 Content of 31st harmonic U12 Content of 31st harmonic U23 Content of 31st harmonic U31 Content of 33rd harmonic U12 Content of 33rd harmonic U23 Content of 33rd harmonic U31 Content of 35th harmonic U12 Content of 35th harmonic U23 Content of 35th harmonic U31 Content of 37th harmonic U12 Content of 37th harmonic U23 Content of 37th harmonic U31 Content of 39th harmonic U12 Content of 39th harmonic U23 Content of 39th harmonic U31 Content of 41st harmonic U12 Content of 41st harmonic U23 Content of 41st harmonic U31 Content of 43rd harmonic U12 Content of 43rd harmonic U23 Content of 43rd harmonic U31 Content of 45th harmonic U12 Content of 45th harmonic U23 Content of 45th harmonic U31 Content of 47th harmonic U12 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

104413_en_00

PHOENIX CONTACT

11-15

EEM-MA600 Table 11-9 Decimal address 51739 51740 51741 51742 51743 51744 51745 51746 51747 51748 51749 51750 51751 51752 51753 51754 51755 51756 51757 51758 51759 51760 51761 51762 51763 51764 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA1B CA1C CA1D CA1E CA1F CA20 CA21 CA22 CA23 CA24 CA25 CA26 CA27 CA28 CA29 CA2A CA2B CA2C CA2D CA2E CA2F CA30 CA31 CA32 CA33 CA34 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 47th harmonic U23 Content of 47th harmonic U31 Content of 49th harmonic U12 Content of 49th harmonic U23 Content of 49th harmonic U31 Content of 51st harmonic U12 Content of 51st harmonic U23 Content of 51st harmonic U31 Content of 53rd harmonic U12 Content of 53rd harmonic U23 Content of 53rd harmonic U31 Content of 55th harmonic U12 Content of 55th harmonic U23 Content of 55th harmonic U31 Content of 57th harmonic U12 Content of 57th harmonic U23 Content of 57th harmonic U31 Content of 59th harmonic U12 Content of 59th harmonic U23 Content of 59th harmonic U31 Content of 61st harmonic U12 Content of 61st harmonic U23 Content of 61st harmonic U31 Content of 63rd harmonic U12 Content of 63rd harmonic U23 Content of 63rd harmonic U31 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

Range extension: 94 words (decimal) or 5E words (hexadecimal) Individual harmonic content for line voltages against N: V (phase/N) 51765 51766 51767 51768 51769 51770 51771 51772 CA35 CA36 CA37 CA38 CA39 CA3A CA3B CA3C 1 1 1 1 1 1 1 1 Highest ascertainable harmonic (63) Content of 3rd harmonic V1 Content of 3rd harmonic V2 Content of 3rd harmonic V3 Content of 5th harmonic V1 Content of 5th harmonic V2 Content of 5th harmonic V3 Content of 7th harmonic V1 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R

11-16

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-9 Decimal address 51773 51774 51775 51776 51777 51778 51779 51780 51781 51782 51783 51784 51785 51786 51787 51788 51789 51790 51791 51792 51793 51794 51795 51796 51797 51798 51799 51800 51801 51802 51803 51804 51805 51806 51807 51808 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA3D CA3E CA3F CA40 CA41 CA42 CA43 CA44 CA45 CA46 CA47 CA48 CA49 CA4A CA4B CA4C CA4D CA4E CA4F CA50 CA51 CA52 CA53 CA54 CA55 CA56 CA57 CA58 CA59 CA5A CA5B CA5C CA5D CA5E CA5F CA60 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 7th harmonic V2 Content of 7th harmonic V3 Content of 9th harmonic V1 Content of 9th harmonic V2 Content of 9th harmonic V3 Content of 11th harmonic V1 Content of 11th harmonic V2 Content of 11th harmonic V3 Content of 13th harmonic V1 Content of 13th harmonic V2 Content of 13th harmonic V3 Content of 15th harmonic V1 Content of 15th harmonic V2 Content of 15th harmonic V3 Content of 17th harmonic V1 Content of 17th harmonic V2 Content of 17th harmonic V3 Content of 19th harmonic V1 Content of 19th harmonic V2 Content of 19th harmonic V3 Content of 21st harmonic V1 Content of 21st harmonic V2 Content of 21st harmonic V3 Content of 23rd harmonic V1 Content of 23rd harmonic V2 Content of 23rd harmonic V3 Content of 25th harmonic V1 Content of 25th harmonic V2 Content of 25th harmonic V3 Content of 27th harmonic V1 Content of 27th harmonic V2 Content of 27th harmonic V3 Content of 29th harmonic V1 Content of 29th harmonic V2 Content of 29th harmonic V3 Content of 31st harmonic V1 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

104413_en_00

PHOENIX CONTACT

11-17

EEM-MA600 Table 11-9 Decimal address 51809 51810 51811 51812 51813 51814 51815 51816 51817 51818 51819 51820 51821 51822 51823 51824 51825 51826 51827 51828 51829 51830 51831 51832 51833 51834 51835 51836 51837 51838 51839 51840 51841 51842 51843 51844 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA61 CA62 CA63 CA64 CA65 CA66 CA67 CA68 CA69 CA6A CA6B CA6C CA6D CA6E CA6F CA70 CA71 CA72 CA73 CA74 CA75 CA76 CA77 CA78 CA79 CA7A CA7B CA7C CA7D CA7E CA7F CA80 CA81 CA82 CA83 CA84 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 31st harmonic V2 Content of 31st harmonic V3 Content of 33rd harmonic V1 Content of 33rd harmonic V2 Content of 33rd harmonic V3 Content of 35th harmonic V1 Content of 35th harmonic V2 Content of 35th harmonic V3 Content of 37th harmonic V1 Content of 37th harmonic V2 Content of 37th harmonic V3 Content of 39th harmonic V1 Content of 39th harmonic V2 Content of 39th harmonic V3 Content of 41st harmonic V1 Content of 41st harmonic V2 Content of 41st harmonic V3 Content of 43rd harmonic V1 Content of 43rd harmonic V2 Content of 43rd harmonic V3 Content of 45th harmonic V1 Content of 45th harmonic V2 Content of 45th harmonic V3 Content of 47th harmonic V1 Content of 47th harmonic V2 Content of 47th harmonic V3 Content of 49th harmonic V1 Content of 49th harmonic V2 Content of 49th harmonic V3 Content of 51st harmonic V1 Content of 51st harmonic V2 Content of 51st harmonic V3 Content of 53rd harmonic V1 Content of 53rd harmonic V2 Content of 53rd harmonic V3 Content of 55th harmonic V1 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

11-18

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-9 Decimal address 51845 51846 51847 51848 51849 51850 51851 51852 51853 51854 51855 51856 51857 51858 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA85 CA86 CA87 CA88 CA89 CA8A CA8B CA8C CA8D CA8E CA8F CA90 CA91 CA92 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 55th harmonic V2 Content of 55th harmonic V3 Content of 57th harmonic V1 Content of 57th harmonic V2 Content of 57th harmonic V3 Content of 59th harmonic V1 Content of 59th harmonic V2 Content of 59th harmonic V3 Content of 61st harmonic V1 Content of 61st harmonic V2 Content of 61st harmonic V3 Content of 63rd harmonic V1 Content of 63rd harmonic V2 Content of 63rd harmonic V3 Unit Register Available through access extension module R R R R R R R R R R R R R R

0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%

Range extension: 94 words (decimal) or 5E words (hexadecimal) Total range extension: 323 words (decimal) or 143 words (hexadecimal)

104413_en_00

PHOENIX CONTACT

11-19

EEM-MA600

Table 11-10 Decimal address 51968 51969

CB00 hex: status of inputs/outputs Hexadecimal address CB00 CB01 Number of data words 1 1 Designation Unit Register access R R EEM-2DIO-MA600 Available through extension module

No. Digital inputs (max. 6) Bit 0: state input 1 high or low Bit 1: state input 2 high or low Bit 2: state input 3 high or low Bit 3: state input 4 high or low Bit 4: state input 5 high or low Bit 5: state input 6 high or low No. Digital outputs (max. 6) Bit 0: state output 1 high or low Bit 1: state output 2 high or low Bit 2: state output 3 high or low Bit 3: state output 4 high or low Bit 4: state output 5 high or low Bit 5: state output 6 high or low

51970 51971

CB02 CB03

1 1

R R EEM-2DIO-MA600

Range extension: 4 words (decimal) or 4 words (hexadecimal)

Table 11-11 Decimal address 57344

E000 hex: measuring instrument terminal configuration Hexadecimal Number address of data words E000 1 Designation Unit Register Available through access extension module R/W

Network type: 0: 1BL 1: 2BL 2: 3BL 3: 3NBL 4: 4BL 5: 4NBL Current transformer's secondary side: 1: 1 A/5: 5 A Current transformer's primary side Not available Not available Not available Voltage transducer present? 0: No 1: Yes

57345

E001

R/W

57346 57347 57348 57349 57350

E002 E003 E004 E005 E006

1 1 1 1 1

R/W R/W R/W R/W

R/W

11-20

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-11 Decimal address 57351 E000 hex: measuring instrument terminal configuration [...] Hexadecimal Number address of data words E007 1 Designation Unit Register Available through access extension module R/W

Voltage transducer's secondary side: 60: 60 V 100: 100 V 110: 110 V 115: 115 V 120: 120 V 173: 173 V 190: 190 V Voltage transducer's primary side Synchronization impulse start signal Measurement duration for saving the averaged real and reactive power P+/- and Q+/-: 5 min, 8 min, 10 min, 15 min, 20 min, 30 min

57352 57354 57355

E008 E00A E00B

2 1 1

V 1:external/ 0:internal s

R/W R/W R/W EEM-MEMO-MA600 EEM-MEMO-MA600

Range extension: 12 words (decimal) or C words (hexadecimal)

Example: Table 11-12 Slave address 05 Configuring a 4 line network with an asymmetrical load (4 NBL) for the EEM-MA600 Function 06 High quality address E0 Low quality address 00 High quality register value 00 Low quality register value 05 CRC 16 7F8D

The reply for EEM-MA600 is identical to the sent message.

Table 11-13 Decimal address 57600 57601 57602 57603 57604 57605

E100 hex: date/time configuration Hexadecimal Number address of data words E100 E101 E102 E103 E104 E105 1 1 1 1 1 1 Designation Unit Register access R/W R/W R/W R/W R/W R/W Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Day Month Year Hour Minute Second

Range extension: 6 words (decimal) or 6 words (hexadecimal)

104413_en_00

PHOENIX CONTACT

11-21

EEM-MA600

Table 11-14 Decimal address 57616

E110 hex: Ethernet communication module configuration Hexadecimal address E110 Number of data words 1 Designation Unit Register access R/W Available through extension module EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 Yes(1) / No(0) 0: 2400 bps 1: 4800 bps 2: 9600 bps 3: 19200 bps 4: 38400 bps R/W EEM-ETH-RS485-MA600 R/W EEM-ETH-MA600 / EEM-ETH-RS485-MA600

IP = CL. A, B, C, D Ethernet IP address CL. A (0-255) Ethernet IP address CL. B (0-255) Ethernet IP address CL. C (0-255) Ethernet IP address CL. D (0-255)

0 - 255

57617 57618 57619 57620 57621 57622 57623 57624 57625 57626 57627

E111 E112 E113 E114 E115 E116 E117 E118 E119 E11A E11B

1 1 1 1 1 1 1 1 1 1 1

0 - 255 0 - 255 0 - 255

R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W

Ethernet gateway0 - 255 address - CL. A (0-255) Ethernet gateway0 - 255 address - CL. B (0-255) Ethernet gateway0 - 255 address - CL. C (0-255) Ethernet gateway0 - 255 address - CL. D (0-255) Ethernet subnet mask CL. A (0-255) Ethernet subnet mask CL. B (0-255) Ethernet subnet mask CL. C (0-255) Ethernet subnet mask CL. D (0-255) DHCP activated Not available Not available Ethernet gateway: JBUS/MODBUS interface speed 0: 2400 bps 1: 4800 bps 2: 9600 bps 3: 19200 bps 4: 38400 bps 0 - 255 0 - 255 0 - 255 0 - 255

57628 57629 57630 57631

E11C E11D E11E E11F

1 1 1 1

11-22

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-14 Decimal address 57632 E110 hex: Ethernet communication module configuration [...] Hexadecimal address E120 Number of data words 1 Designation Unit Register access R/W Available through extension module EEM-ETH-RS485-MA600

Ethernet gateway: JBUS/MODBUS interface parity 0: none 1: even 2: odd Ethernet gateway: JBUS/MODBUS interface stop bit Not available Ethernet gateway: JBUS/MODBUS slave address

0: none 1: even 2: odd

57633

E121

1: 1 stop bit 2: 2 stop bits 1-247

R/W

EEM-ETH-RS485-MA600

57634 57635

E122 E123

1 1

R/W

EEM-ETH-RS485-MA600

Range extension: 20 words (decimal) or 14 words (hexadecimal)

Table 11-15

E200 hex: saving configuration and restart for measuring instrument Unit Register access W Available through extension module

Decimal Hexadecimal Number Designation address address of data words 57856 E200 1 Action: 0xA1: save settings in EEPROM 0xB2: restart measuring instrument

Range extension: 1 word (decimal) or 1 word (hexadecimal)

Example: Table 11-16 Slave address 05 After changing the configuration parameters, the following command lets them be saved Function 06 High quality address E2 Low quality address 00 High quality register value 00 Low quality register value A1 CRC 16 7F8E

The reply for EEM-MA600 is identical to the sent message.

104413_en_00

PHOENIX CONTACT

11-23

EEM-MA600

Table 11-17 Decimal address

7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) Hexadecimal Number Designation address of data words Unit Register Available through access extension module

OUT 1: Alarm to digital extension module 1 30464 7700 1


OUT 1 Current alarm under threshold (output types): 0: no alarm 1: I1: current 2: I2: current 3: I3: current 4: In: neutral conductor current 5: U12: line voltages (1-2) 6: U23: line voltages (2-3) 7: U31: line voltages (3-1) 8: P: total real power 9: Q: total reactive power 10: S: total apparent power 11: F: frequency 12: PFL: total power factor inductive 15: THD I1: total harmonic distortion of current 16: THD I2: total harmonic distortion of current 17: THD I3: total harmonic distortion of current 18: THD U12: total harmonic distortion of line voltage 19: THD U23: total harmonic distortion of line voltage 20: THD U31: total harmonic distortion of line voltage 21: HOUr: operating hours counter 22: V1: line voltages against N 23: V2: line voltages against N 24: V3: line voltages against N 25: THD IN: total harmonic distortion of neutral conductor current 26: THD V1: total harmonic distortion of line voltage against N 27: THD V2: total harmonic distortion of line voltage against N 28: THD V3: total harmonic distortion of line voltage against N 31: PFC: total capacitive power factor 32: TC1 temperature module input 33: TC2 temperature module input 34: TC3 temperature module input 35: TC4 internal temperature 36: PPR total effective power (trend) 37: QPR total reactive power (trend) 38: SPR total apparent power (trend)

R
0: / 1: mA 2: mA 3: mA 4: mA 5: mV 6: mV 7: mV 8: mW 9: mvar 10: mVA 11: Hz/1000 12: SPFL 15: /1000 16: /1000 17: /1000 18: /1000 19: /1000 20: /1000 21: h/100 22: mV 23: mV 24: mV 25: /1000 26: /1000 27: /1000 28: /1000 31: SPFL 32: C 33: C 34: C 35: C 36: kW/100 37: kvar/100 38: kVA/100

EEM-2DIO-MA600

11-24

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-17 Decimal address 30465 30467 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7701 7703 2 1 OUT 1 Current alarm: lowest measured value OUT 1 Current alarm, upper threshold: output types, see lower threshold current alarm OUT 1 Current alarm: highest measured value OUT 1 Current alarm: duration OUT 1 Alarm n-1: lower threshold: output types, see lower threshold current alarm Unit Register Available through access extension module R R EEM-2DIO-MA600 EEM-2DIO-MA600

/ Units, see lower threshold current alarm / s Units, see lower threshold current alarm / /

30468 30470 30471

7704 7706 7707

2 1 1

R R R

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

30472 30474

7708 770 A

2 1

OUT 1 Alarm n-1: lowest measured value OUT 1 Alarm n-1: upper threshold: output types, see lower threshold current alarm OUT 1 Alarm n-1: highest measured value OUT 1 Alarm n-1: duration OUT 1 Alarm n-2: lower threshold: output types, see lower threshold current alarm

R R

EEM-2DIO-MA600 EEM-2DIO-MA600

30475 30477 30478

770B 770D 770E

2 1 1

/ s Units, see lower threshold current alarm / /

R R R

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

30479 30481

770F 7711

2 1

OUT 1 Alarm n-2: lowest measured value OUT 1 Alarm n-2: upper threshold: output types, see lower threshold current alarm OUT 1 Alarm n-2: highest measured value OUT 1 Alarm n-2: duration OUT 1 Alarm n-3: lower threshold: output types, see lower threshold current alarm

R R

EEM-2DIO-MA600 EEM-2DIO-MA600

30482 30484 30485

7712 7714 7715

2 1 1

/ s Units, see lower threshold current alarm /

R R R

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

30486

7716

OUT 1 Alarm n-3: lowest measured value

EEM-2DIO-MA600

104413_en_00

PHOENIX CONTACT

11-25

EEM-MA600 Table 11-17 Decimal address 30488 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7718 1 OUT 1 Alarm n-3: upper threshold: output types, see lower threshold current alarm OUT 1 Alarm n-3: highest measured value OUT 1 Alarm n-3: duration Unit Register Available through access extension module R EEM-2DIO-MA600

30489 30491

7719 771B

2 1

/ s

R R

EEM-2DIO-MA600 EEM-2DIO-MA600

OUT 2: Alarm to digital extension module 2 30492 30493 30495 771C 771D 771F 1 2 1 OUT 2 Current alarm: output types, see OUT 1 OUT 2 Current alarm: lowest measured value OUT 2 Current alarm: upper threshold: output types, see OUT 1 OUT 2 Current alarm: highest measured value OUT 2 Current alarm: duration OUT 2 Alarm n-1: lower threshold: output types, see OUT 1 OUT 2 Alarm n-1: lowest measured value OUT 2 Alarm n-1: upper threshold: output types, see OUT 1 OUT 2 Alarm n-1: highest measured value OUT 2 Alarm n-1: duration OUT 2 Alarm n-2: lower threshold: output types, see OUT 1 OUT 2 Alarm n-2: lowest measured value OUT 2 Alarm n-2: upper threshold: output types, see OUT 1 OUT 2 Alarm n-2: highest measured value OUT 2 Alarm n-2: duration OUT 2 Alarm n-3: lower threshold: output types, see OUT 1 OUT 2 Alarm n-3: lowest measured value OUT 2 Alarm n-3: upper threshold: output types, see OUT 1 / / / / / s / / / s Units, see OUT 1 / / R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

30496 30498 30499 30500 30502 30503 30505 30506 30507 30509 30510 30512 30513 30514 30516

7720 7722 7723 7724 7726 7727 7729 772 A 772B 772D 772E 7730 7731 7732 7734

2 1 1 2 1 2 1 1 2 1 2 1 1 2 1

/ s

R R R R R R R R R R R R R R R

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

11-26

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-17 Decimal address 30517 30519 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7735 7737 2 1 OUT 2 Alarm n-3: highest measured value OUT 2 Alarm n-3: duration Unit Register Available through access extension module R R EEM-2DIO-MA600 EEM-2DIO-MA600

/ s

OUT 3: Alarm to digital extension module 3 30520 30521 30523 30524 30526 7738 7739 773B 773C 773E 1 2 1 2 1 OUT 3 Current alarm: output types, see OUT 1 OUT 3 Current alarm: lowest measured value OUT 3 Current alarm: upper threshold: output types, see OUT 1 OUT 3 Current alarm: highest measured value OUT 3 Current alarm: duration Units, see OUT 1 / / / s R R R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

OUT 4: Alarm to digital extension module 4 30527 30528 30530 773F 7740 7742 1 2 1 OUT 4 Current alarm: output types, see OUT 1 OUT 4 Current alarm: lowest measured value OUT 4 Current alarm: upper threshold: output types, see OUT 1 OUT 4 Current alarm: highest measured value OUT 4 Current alarm: duration Units, see OUT 1 / / R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

30531 30533

7743 7745

2 1

/ s

R R

EEM-2DIO-MA600 EEM-2DIO-MA600

OUT 5: Alarm to digital extension module 5 30534 30535 30537 7746 7747 7749 1 2 1 OUT 5 Current alarm: output types, see OUT 1 OUT 5 Current alarm: lowest measured value OUT 5 Current alarm: upper threshold: output types, see OUT 1 OUT 5 Current alarm: highest measured value OUT 5 Current alarm: duration Units, see OUT 1 / / R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

30538 30540

774 A 774C

2 1

/ s

R R

EEM-2DIO-MA600 EEM-2DIO-MA600

OUT 6: Alarm to digital extension module 6 30541 30542 774D 774E 1 2 OUT 6 Current alarm: output types, see OUT 1 OUT 6 Current alarm: lowest measured value Units, see OUT 1 / R R EEM-2DIO-MA600 EEM-2DIO-MA600

104413_en_00

PHOENIX CONTACT

11-27

EEM-MA600 Table 11-17 Decimal address 30544 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7750 1 OUT 6 Current alarm: upper threshold: output types, see OUT 1 OUT 6 Current alarm: highest measured value OUT 6 Current alarm: duration Unit Register Available through access extension module R EEM-2DIO-MA600

30545 30547

7751 7753

2 1

/ s

R R

EEM-2DIO-MA600 EEM-2DIO-MA600

Range extension: 164 words (decimal) or A4 words (hexadecimal)

Table 11-18 Decimal address 256 257 258

100 hex: information about connected extension modules Hexadecimal Number Designation address of data words 100 101 102 1 1 1 Not available Manufacturer code Slot 1 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600 Slot 2: see slot 1 Slot 3: see slot 1 Slot 4: see slot 1 Software version Serial number R R Unit Register Available through access extension module

259 260 261 262 263

103 104 105 106 107

1 1 1 1 4

R R R R R

Range extension: 11 words (decimal) or B words (hexadecimal)

11-28

PHOENIX CONTACT

104413_en_00

MODBUS register

Table 11-19

200 hex: extension module display and configuration Designation Unit Register access R/W Available through extension module

Decimal Hexadecimal Number address address of data words 512 200 1

Network type: 0: 1BL 1: 2BL 2: 3BL 3: 3NBL 4: 4BL 5: 4NBL

513 514 515 516

201 202 203 204

1 1 1 2

Current transformer's secondary side: A 1: 1 A/5: 5 A Current transformer's primary side Voltage transducer present? 0: No 1: Yes Voltage transducer's secondary side: 60: 60 V 100: 100 V 110: 110 V 115: 115 V 120: 120 V 173: 173 V 190: 190 V Voltage transducer's primary side Measurement duration to average value/maximum accumulation of value for current: (2 s, 10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Measurement duration to average value/maximum accumulation of value for P,Q,S power: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Not available s A

R/W R/W

518 519

206 207

1 1

R/W

520

208

R/W

521 ... 526

209 ... 20E

Analog extension module EEM-2AO-MA600 527 20F 1 Output signal AO OUT 1: 0: 0/20 mA 1: 4/20 mA 2: 30 V R/W EEM-2AO-MA600

104413_en_00

PHOENIX CONTACT

11-29

EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W 0: A 1: A 2: A 3: A 4: V 5: V 6: V 7: W 8: var 9: VA 10: 1/1000 11: V 12: V 13: V 14: Hz 15: 1/1000 16: A 17: V 18: V 19: W 20: var 21: VA 22: C 23: C 24: C 25: C R/W R/W EEM-2AO-MA600 EEM-2AO-MA600 Available through extension module EEM-2AO-MA600

Decimal Hexadecimal Number address address of data words 528 210 1

Output type AO OUT 1: 0: I1: power 1: I2: power 2: I3: power 3: In: neutral conductor power 4: U12: line voltages (1-2) 5: U23: Line voltages (2-3) 6: U31: Line voltages (3-1) 7: P: Real power sum 8: Q: Reactive power sum 9: S: Apparent power sum 10: PFL: Inductive power factor sum 11: V1: Line voltages against N 12: V2: Line voltages against N 13: V3: Line voltages against N 14: F: Frequency 15: PFC: Capacitive power factor sum 16: I: Power I1, I2, I3 17: U: Line voltage (1-2/2-3/3-1) 18: V: Line voltage against N (1/2/3) 19: PPR: Total real power (trend) 20: QPR: Total reactive power (trend) 21: SPR: Total apparent power (trend) 22: TC1: Temperature module input EEM-TEMP-MA600 23: TC2: Temperature module input EEM-TEMP-MA600 24: TC3: Temperature module input EEM-TEMP-MA600 25: TC4: internal temperature EEMTEMP-MA600 AO OUT 1 output value for 0 or 4mA AO OUT 1 unit of output value for 0 or 4 mA: 0: / 1: k 2: M Output value AO OUT 1 for 20 mA AO OUT 1 unit of output value for 20 mA: 0: / 1: k 2: M

529 530

211 212

1 1

531 532

213 214

1 1

R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600

11-30

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2AO-MA600

Decimal Hexadecimal Number address address of data words 533 215 1

Output signal AO OUT 2: 0: 0/20 mA 1: 4/20 mA 2: 30 V Output type AO OUT 2: see AO OUT 1 AO OUT 2 output value for 0 or 4 mA AO OUT 2 unit of output value for 0 or 4 mA: 0: / 1: k 2: M AO OUT 2 output value for 20 mA AO OUT 2 unit of output value for 20 mA: 0: / 1: k 2: M Output signal AO OUT 3: 0: 0/20 mA 1: 4/20 mA 2: 30 V Output type AO OUT 3: see AO OUT 1 AO OUT 3 output value for 0 or 4 mA AO OUT 3 unit of output value for 0 or 4 mA: 0: / 1: k 2: M Output value AO OUT 3 for 20 mA AO OUT 2 unit of output value for 20 mA: 0: / 1: k 2: M Output signal AO OUT 4: 0: 0/20 mA 1: 4/20 mA 2: 30 V Output type AO OUT 4: see AO OUT 1 AO OUT 4 output value for 0 or 4 mA

534 535 536

216 217 218

1 1 1

R/W R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600 EEM-2AO-MA600

537 538

219 21 A

1 1

R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600

539

21B

R/W

EEM-2AO-MA600

540 541 542

21C 21D 21E

1 1 1

R/W R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600 EEM-2AO-MA600

543 544

21F 220

1 1

R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600

545

221

R/W

EEM-2AO-MA600

546 547

222 223

1 1

R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600

104413_en_00

PHOENIX CONTACT

11-31

EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2AO-MA600

Decimal Hexadecimal Number address address of data words 548 224 1

AO OUT 4 unit of output value for 0 or 4 mA: 0: / 1: k 2: M Output value AO OUT 4 for 20 mA AO OUT 4 unit of output value for 20 mA: 0: / 1: k 2: M

549 550

225 226

1 1

R/W R/W

EEM-2AO-MA600 EEM-2AO-MA600

11-32

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access Available through extension module

Decimal Hexadecimal Number address address of data words

Digital extension module EEM-2DIO-MA600 551 227 1 Output type DO OUT 1: 0: CDE: Controlling relay state via RS485 1: I: Current I1, I2, I3 2: U: Line voltages (1-2/2-3/3-1) 3: P+: Total positive real power 4: Q+: Total positive reactive power 5: S: Total apparent power 6: F: Frequency 7: PFL: Total inductive power factor 8: THDI: Total harmonic distortion for currents I1, I2, I3 9: THDU: Total harmonic distortion for line voltages (1-2/2-3/3-1) 10: In: Neutral conductor current 11: HOUr: Operating hours counter 12: V: Line voltages against N (1/2/3) 13: THD In: Total harmonic distortion of neutral conductor current 14: THDV: Total harmonic distortion of line voltages against N (1 / 2 / 3) 15: P-: Total negative real power 16: Q-: Total negative reactive power 17: PFC: Total capacitive power factor 18: CDT: Controlling relay status via RS485, resetting relay to idle 19: TC1: Input temperature module EEM-TEMP-MA600 20: TC2: Input temperature module EEM-TEMP-MA600 21: TC3: Input temperature module EEM-TEMP-MA600 22: TC4: Internal temperature EEMTEMP-MA600 23: PPR: Total real power (trend) 24: QPR: Total reactive power (trend) 25: SPR: Total apparent power (trend) DO OUT 1 alarm output value for lower switching threshold DO OUT 1 output value unit for the lower switching threshold 0: / 1: k 2: M R/W 0: / 1: A 2: V 3: W 4: var 5: VA 6: 1/10 Hz 7: 1/100 8: % 9: % 10: A 11: h 12: V 13: % 14: % 15: W 16: var 17: 1/100 18: / 19: C 20: C 21: C 22: C 23: W 24: var 25: VA R/W R/W EEM-2DIO-MA600 EEM-2DIO-MA600

552 553

228 229

1 1

104413_en_00

PHOENIX CONTACT

11-33

EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W R/W Available through extension module EEM-2DIO-MA600 EEM-2DIO-MA600

Decimal Hexadecimal Number address address of data words 554 555 22 A 22B 1 1

DO OUT 1 alarm output value for upper switching threshold DO OUT 1 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 1 hysteresis (0-99) DO OUT 1 response delay (0-999) DO OUT 1 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 2: see DO OUT 1 DO OUT 2 alarm output value for lower switching threshold DO OUT 2 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 2 alarm output value for upper switching threshold DO OUT 2 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 2 hysteresis (0-99) DO OUT 2 response delay (0-999) DO OUT 2 relay idle: 0: NO (open) 1: NC (closed) Not available Not available Not available Not available Not available Not available % s % s

556 557 558

22C 22D 22E

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

559 560 561

22F 230 231

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

562 563

232 233

1 1

R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600

564 565 566

234 235 236

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

567 568 569 570 571 572

237 238 239 23 A 23B 23C

1 1 1 1 1 1

11-34

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2DIO-MA600

Decimal Hexadecimal Number address address of data words 573 23D 1

Measurement duration to average value/maximum accumulation of value for line voltages U: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Measurement duration to average value/maximum accumulation of value for frequency F: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Save averaged positive real power P+: 0: No 1: Yes Save averaged negative real power P+: 0: No 1: Yes Store averaged positive reactive power Q+: 0: No 1: Yes Store averaged negative reactive power Q-: 0: No 1: Yes Synchronization impulse start signal Measurement duration for saving the averaged real and reactive power P+/- and Q+/-: 5 min, 8 min, 10 min, 15 min, 20 min, 30 min Output type DO OUT 3: see DO OUT 1 DO OUT 3 alarm output value for lower switching threshold DO OUT 3 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 3 alarm output value for upper switching threshold

574

23E

R/W

EEM-2DIO-MA600

575

23F

R/W

EEM-MEMOMA600

576

240

R/W

EEM-MEMOMA600

577

241

R/W

EEM-MEMOMA600

578

242

R/W

EEM-MEMOMA600

579 580

243 244

1 1

1:external/ 0:internal s

R/W R/W

EEM-MEMOMA600 EEM-MEMOMA600

581 582 583

245 246 247

1 1 1

"R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

584

248

R/W

EEM-2DIO-MA600

104413_en_00

PHOENIX CONTACT

11-35

EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2DIO-MA600

Decimal Hexadecimal Number address address of data words 585 249 1

DO OUT 3 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 3 hysteresis (0-99) DO OUT 3 response delay (0-999) DO OUT 3 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 4: see DO OUT 1 DO OUT 4 alarm output value for lower switching threshold DO OUT 4 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 4 alarm output value for upper switching threshold DO OUT 4 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 4 hysteresis (0-99) DO OUT 4 response delay (0-999) DO OUT 4 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 5: see DO OUT 1 DO OUT 5 alarm output value for lower switching threshold DO OUT 5 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 5 alarm output value for upper switching threshold % s % s

586 587 588

24 A 24B 24C

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

589 590 591

24D 24E 24F

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

592 593

250 251

1 1

R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600

594 595 596

252 253 254

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

597 598 599

255 256 257

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

600

258

R/W

EEM-2DIO-MA600

11-36

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2DIO-MA600

Decimal Hexadecimal Number address address of data words 601 259 1

DO OUT 5 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 5 hysteresis (0-99) DO OUT 5 response delay (0-999) DO OUT 5 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 6: see DO OUT 1 DO OUT 6 alarm output value for lower switching threshold DO OUT 6 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 6 alarm output value for upper switching threshold DO OUT 6 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 6 hysteresis (0-99) DO OUT 6 response delay (0-999) DO OUT 6 relay idle: 0: NO (open) 1: NC (closed) % s % s

602 603 604

25 A 25B 25C

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

605 606 607

25D 25E 25F

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

608 609

260 261

1 1

R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600

610 611 612

262 263 264

1 1 1

R/W R/W R/W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

Memory module EEM-MEMO-MA600 613 614 615 616 617 265 266 267 268 269 1 1 1 1 1 Threshold value for acquiring undervoltages (SAG) Hysteresis of threshold value undervoltages (SAG) Threshold value for acquiring surge voltages (SWELL) Hysteresis of threshold value surge voltages (SWELL) Not available % % % % R/W R/W R/W R/W R/W

104413_en_00

PHOENIX CONTACT

11-37

EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W R/W Available through extension module

Decimal Hexadecimal Number address address of data words 618 619 26 A 26B 1 1

Not available Not available

Range extension: 108 words (decimal) or 6C words (hexadecimal)

11-38

PHOENIX CONTACT

104413_en_00

MODBUS register

Table 11-20 Decimal address 1024

400 hex: reset measured values Hexadecimal address 400 Number of data words 1 Designation Unit Register Available through access extension module W

Reset: / max/avg I1,I2,I3: maximum value of current (I1, I2, I3): 0x1 max/avg P+: maximum total positive real power value: 0x2 max/avg P-: maximum total negative real power value: 0x4 max/avg Q+: maximum total positive reactive power value: 0x8 max/avg Q-: maximum total negative reactive power value: 0x10 max/avg S: maximum total apparent power value: 0x20 HOUr: Operating hours counter: 0x40 EA+: current positive real energy kWh+: 0x80 ER+: current positive reactive energy kvarh+: 0x100 ES: current apparent energy kVAh: 0x200 EA-: current negative real energy kWh-: 0x400 ER-: current negative reactive energy kvarh-: 0x800 All measured values: 0x1000 max/avg U12, U23, U31: maximum line voltage value (U12, U23, U31): 0x2000 max/avg V1, V2, V3: maximum value of line voltages against N (V1, V2, V3): 0x4000 max/avg F: maximum frequency value: 0x8000

104413_en_00

PHOENIX CONTACT

11-39

EEM-MA600 Table 11-20 Decimal address 1025 400 hex: reset measured values [...] Hexadecimal address 401 Number of data words 1 Designation Unit Register Available through access extension module W

Reset: / E1: Counter status digital input 1: 0x1 E2: Counter status digital input 2: 0x2 E3: Counter status digital input 3: 0x4 E4: Counter status digital input 4: 0x8 E5: Counter status digital input 5: 0x10 E6: Counter status digital input 6: 0x20 Min./Max. I: Min./Max. current from I1, I2, or I3: 0x40 Min./Max. In: Min./Max. neutral conductor current: 0x80 Min./Max. U: Min./Max. line voltage from U12, U23, or U31: 0x100 Min./Max. F: Min./Max. frequency value: 0x200 Min./Max. PF: Min./Max. power factor (total): 0x400 Min./Max. P: Min./Max. positive and negative real power (total): 0x800 Min./Max. Q: Min./Max. positive und negative reactive power (total): 0x1000 Min./Max. THD I: Min./Max. total harmonic distortion of currents from I1, I2, or I3: 0x2000 Min./Max. THD IN: Min./Max. total harmonic distortion of current from neutral conductor current: 0x4000 Min./Max. THD U: Min./Max. total harmonic distortion of line voltages from U12, U23, or U31: 0x8000

11-40

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-20 Decimal address 400 hex: reset measured values [...] Hexadecimal address Number of data words Designation Unit Register Available through access extension module

1026

402

Reset: / Min/Max S: Min./Max. apparent power (total) 0x0001 Min/Max V: Min./Max. line voltage against N from V1, V2, or V3: 0x0002 Min/Max THD V: Min./Max. total harmonic distortion of line voltages against N from V1, V2, or V3: 0x0004 External input (storage module): 0x0008 10 last saved alarms (storage module): 0x0010 10 last saved undervoltages (storage module): 0x0020 10 last saved surge voltages (storage module): 0x0040 10 last saved voltage failures (storage module): 0x0080

Range extension: 3 words (decimal) or 3 words (hexadecimal)

If you want to reset several parameters concurrently, you must add the numbers to the "Designation" column, for example: Resetting max. P+ and kvarh +: 2 + 100 = 102. (Hex)" Example: The following data sequence allows all saved values to be reset:" Slave address 05 Function 06 High quality address 04 Low quality address 00 High quality register value 10 Low quality register value 00 CRC 16 84BE

The reply for EEM-MA600 is identical to the sent message.

104413_en_00

PHOENIX CONTACT

11-41

EEM-MA600

Table 11-21

C10 hex: alarm history display (course of last 10 alarms) Number of data words Designation Unit Register access Available through extension module

Decimal Hexadecimal address address Stored alarm n-1 3088 3089 C10 C11

1 1

Output 1-6 alarm Alarm n-1: lower threshold (output type): 0: no alarm 1: I1: current 2: I2: current 3: I3: current 4: In: neutral conductor current 5: U12: line voltages (1-2) 6: U23: line voltages (2-3) 7: U31: line voltages (3-1) 8: P: total real power 9: Q: total reactive power 10: S: total apparent power 11: F: frequency 12: PFL: total inductive power factor 15: THD I1: total harmonic distortion of current 16: THD I2: total harmonic distortion of current 17: THD I3: total harmonic distortion of current 18: THD U12: total harmonic distortion of line voltage 19: THD U23: total harmonic distortion of line voltage 20: THD U31: total harmonic distortion of line voltage 21: HOUr: operating hours counter 22: V1: line voltages against N 23: V2: line voltages against N 24: V3: line voltages against N 25: THD IN: total harmonic distortion of neutral conductor current Alarm n-1: lowest measured value Alarm n-1: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-1: highest measured value Duration Day Month Year Hour s

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3090 3092

C12 C14

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3094 3095 3096 3097 3098 3099

C15 C17 C18 C19 C1A C1B

2 1 1 1 1 1

R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

11-42

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 1 Designation Unit Register access R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal Hexadecimal address address 3100 3101 C1C C1D

Minute Second

Stored alarm n-2 3102 3103 C1E C1F 1 1 Output 1-6 alarm Alarm n-2: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-2: lowest measured value Alarm n-2: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-2: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600

3105 3106

C21 C22

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3107 3109 3110 3111 3112 3113 3114 3115

C23 C25 C26 C27 C28 C29 C2A C2B

2 1 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-3 3116 3117 C2C C2D 1 1 Output 1-6 alarm Alarm n-3: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-3: lowest measured value: Alarm n-3: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-3: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600

3118 3119

C2E C2F

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3121 3122 3124 3125 3126 3127 3128 3129

C31 C32 C34 C35 C36 C37 C38 C39

1 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-4 3130 C3A 1 Output 1-6 alarm R EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-43

EEM-MA600 Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 Designation Unit Register access R Available through extension module EEM-MEMO-MA600

Decimal Hexadecimal address address 3131 C3B

Alarm n-4: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-4: lower threshold value: Alarm n-4: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-4: highest measured value Duration Day Month Year Hour Minute Second s

3132 3134

C3C C3D

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3135 3136 3138 3139 3140 3141 3142 3143

C3F C40 C42 C43 C44 C45 C46 C47

1 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-5 3144 3145 C48 C49 1 1 Output 1-6 alarm Alarm n-5: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-5: lowest measured value: Alarm n-5: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-5: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600

3146 3147

C4A C4B

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3149 3150 3152 3153 3154 3155 3156 3157

C4C C4D C4F C51 C52 C53 C54 C55

1 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-6 3158 3159 C56 C57 1 1 Output 1-6 alarm Alarm n-6: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-6: lowest measured value: R R EEM-MEMO-MA600 EEM-MEMO-MA600

3160

C58

EEM-MEMO-MA600

11-44

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 2 Designation Unit Register access R Available through extension module EEM-MEMO-MA600

Decimal Hexadecimal address address 3161 C59

Alarm n-6: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-6: highest measured value Duration Day Month Year Hour Minute Second s

3163 3164 3166 3167 3168 3169 3170 3171

C5B C5C C5E C5F C60 C61 C62 C63

1 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-7 3172 3173 C64 C65 1 1 Output 1-6 alarm Alarm n-7: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-7: lowest measured value: Alarm n-7: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-7: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600

3174 3175

C66 C67

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3177 3178 3180 3181 3182 3183 3184 3185

C69 C6A C6C C6D C6E C6F C70 C71

1 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-8 3186 3187 C72 C73 1 1 Output 1-6 alarm Alarm n-8: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-8: lowest measured value: Alarm n-8: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-8: highest measured value Duration s R R EEM-MEMO-MA600 EEM-MEMO-MA600

3188 3189

C74 C75

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3191 3192

C77 C78

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-45

EEM-MA600 Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 1 1 1 1 1 Designation Unit Register access R R R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal Hexadecimal address address 3194 3195 3196 3197 3198 3199 C7A C7B C7C C7D C7E C7F

Day Month Year Hour Minute Second

Stored alarm n-9 3200 3201 C80 C81 1 1 Output 1-6 alarm Alarm n-9: lower threshold: Output types, see alarm n-1 lower threshold Alarm n-9: lowest measured value: Alarm n-9: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-9: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600

3202 3203

C82 C83

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3205 3206 3208 3209 3210 3211 3212 3213

C85 C86 C88 C89 C8A C8B C8C C8D

1 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Stored alarm n-10 3214 3215 C8E C8F 1 1 Output 1-6 alarm Alarm n-10: lower threshold: Output types, see alarm n-1 lower threshold Alarm n-10: lowest measured value Alarm n-10: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-10: highest measured value Duration Day Month Year Hour s R R EEM-MEMO-MA600

3216 3217

C90 C91

1 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3219 3220 3222 3223 3224 3225

C93 C94 C96 C97 C98 C99

1 2 1 1 1 1

R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

11-46

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 1 Designation Unit Register access R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal Hexadecimal address address 3226 3227 C9A C9B

Minute Second

Range extension: 140 words (decimal) or 8C words (hexadecimal)

Table 11-22 Decimal address

D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) Hexadecimal address Number Designation of data words Unit Register access Available through extension module

Threshold value shortfall n-1 3328 D00 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3329 3331

D01 D03

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3332 3334 3336 3337 3338 3339 3340 3341

D04 D06 D08 D09 D0A D0B D0C D0D

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-2 3342 D0E 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value R EEM-MEMO-MA600

3343

D0F

EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-47

EEM-MA600 Table 11-22 Decimal address 3345 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D11 Number Designation of data words 1 Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms Unit Register access R Available through extension module EEM-MEMO-MA600

3346 3348 3350 3351 3352 3353 3354 3355

D12 D14 D16 D17 D18 D19 D1A D1B

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-3 3356 D1C 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3357 3359

D1D D1F

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3360 3362 3364 3365 3366 3367 3368 3369

D20 D22 D24 D25 D26 D27 D28 D29

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

11-48

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-22 Decimal address D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address Number Designation of data words Unit Register access Available through extension module

Threshold value shortfall n-4 3370 D2A 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3371 3373

D2B D2D

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3374 3376 3378 3379 3380 3381 3382 3383

D2E D30 D32 D33 D34 D35 D36 D37

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-5 3384 D38 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year ms R EEM-MEMO-MA600

3385 3387

D39 D3B

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3388 3390 3392 3393 3394

D3C D3E D40 D41 D42

2 2 1 1 1

R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-49

EEM-MA600 Table 11-22 Decimal address 3395 3396 3397 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D43 D44 D45 Number Designation of data words 1 1 1 Hour Minute Second Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-6 3398 D46 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3399 3401

D47 D49

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3402 3404 3406 3407 3408 3409 3410 3411

D4A D4C D4E D4F D50 D51 D52 D53

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-7 3412 D54 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration ms R EEM-MEMO-MA600

3413 3415

D55 D57

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3416 3418

D58 D5A

2 2

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

11-50

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-22 Decimal address 3420 3421 3422 3423 3424 3425 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D5C D5D D5E D5F D60 D61 Number Designation of data words 1 1 1 1 1 1 Day Month Year Hour Minute Second Unit Register access R R R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-8 3426 D62 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3427 3429

D63 D65

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3430 3432 3434 3435 3436 3437 3438 3439

D66 D68 D6A D6B D6C D6D D6E D6F

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-9 3440 D70 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value R EEM-MEMO-MA600

3441

D71

EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-51

EEM-MA600 Table 11-22 Decimal address 3443 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D73 Number Designation of data words 1 Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms Unit Register access R Available through extension module EEM-MEMO-MA600

3444 3446 3448 3449 3450 3451 3452 3453

D74 D76 D78 D79 D7A D7B D7C D7D

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value shortfall n-10 3454 D7E 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3455 3457

D7F D81

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3458 3460 3462 3463 3464 3465 3466 3467

D82 D84 D86 D87 D88 D89 D8A D8B

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Range extension: 140 words (decimal) or 8C words (hexadecimal)

11-52

PHOENIX CONTACT

104413_en_00

MODBUS register

Table 11-23

E00 hex: surge voltage (course of last 10 SWELL surge voltages) Number of data words Designation Unit Register access Available through extension module

Decimal Hexadecimal address address

Threshold value exceedance n-1 3584 E00 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3585 3587

E01 E03

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3588 3590 3592 3593 3594 3595 3596 3597

E04 E06 E08 E09 E0A E0B E0C E0D

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value exceedance n-2 3598 E0E 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month ms R EEM-MEMO-MA600

3599 3601

E0F E11

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3602 3604 3606 3607

E12 E14 E16 E17

2 2 1 1

R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-53

EEM-MA600 Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 1 1 1 1 Designation Unit Register access R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal Hexadecimal address address 3608 3609 3610 3611 E18 E19 E1A E1B

Year Hour Minute Second

Threshold value exceedance n-3 3612 E1C 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3614 3615

E1D E1F

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3616 3618 3620 3621 3622 3623 3624 3625

E20 E22 E24 E25 E26 E27 E28 E29

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value exceedance n-4 3626 E2A 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value R EEM-MEMO-MA600

3627 3629

E2B E2D

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3630

E2E

EEM-MEMO-MA600

11-54

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 2 1 1 1 1 1 1 Designation Unit Register access R R R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal Hexadecimal address address 3632 3634 3635 3636 3637 3638 3639 E30 E32 E33 E34 E35 E36 E37

Duration Day Month Year Hour Minute Second

ms

Threshold value exceedance n-5 3640 E38 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3641 3642

E39 E3B

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3643 3644 3645 3646 3647 3648 3649 3650

E3C E3E E40 E41 E42 E43 E44 E45

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value exceedance n-6 3654 E46 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value R EEM-MEMO-MA600

3655

E47

EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-55

EEM-MA600 Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 1 Designation Unit Register access R Available through extension module EEM-MEMO-MA600

Decimal Hexadecimal address address 3657 E49

Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms

3658 3660 3662 3663 3664 3665 3666 3667

E4A E4C E4E E4F E50 E51 E52 E53

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value exceedance n-7 3668 E54 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3669 3671

E55 E57

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3672 3674 3676 3677 3678 3679 3680 3681

E58 E5A E5C E5D E5E E5F E60 E61

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

11-56

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words Designation Unit Register access Available through extension module

Decimal Hexadecimal address address

Threshold value exceedance n-8 3682 E62 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600

3683 3685

E63 E65

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3686 3688 3690 3691 3692 3693 3694 3695

E66 E68 E6A E6B E6C E6D E6E E6F

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Threshold value exceedance n-9 3696 E70 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year ms R EEM-MEMO-MA600

3697 3699

E71 E73

2 1

R R

EEM-MEMO-MA600 EEM-MEMO-MA600

3700 3702 3704 3705 3706

E74 E76 E78 E79 E7A

2 2 1 1 1

R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-57

EEM-MA600 Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 1 1 1 Designation Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal Hexadecimal address address 3707 3708 3709 E7B E7C E7D

Hour Minute Second

Threshold value exceedance n-10 3710 E7E 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 3711 3713 E7F E81 2 1 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R R EEM-MEMO-MA600 EEM-MEMO-MA600 R EEM-MEMO-MA600

3714 3716 3718 3719 3720 3721 3722 3723

E82 E84 E86 E87 E88 E89 E8A E8B

2 2 1 1 1 1 1 1

R R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Range extension: 140 words (decimal) or 8C words (hexadecimal)

Table 11-24 Decimal address 3840 3842 3843 3844 3845

F00 hex: current minimum and maximum measured values (measurement duration of 1 s) Hexadecimal address F00 F02 F03 F04 F05 Number of data words 2 1 1 1 1 Designation Unit Register access R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module

Min. I: minimum current from I1, I2 or I3 Day Month Year Hour

mA

11-58

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-24 Decimal address 3846 3847 3848 3850 3851 3852 3853 3854 3855 3856 3858 3859 3860 3861 3862 3863 3864 3866 3867 3868 3869 3870 3871 3872 3874 3875 3876 3877 3878 3879 3880 3882 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F06 F07 F08 F0A F0B F0C F0D F0E F0F F10 F12 F13 F14 F15 F16 F17 F18 F1A F1B F1C F1D F1E F1F F20 F22 F23 F24 F25 F26 F27 F28 F2A Number of data words 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 Designation Unit Register access R R mA R R R R R R R mA R R R R R R R mA R R R R R R R V / 100 R R R R R R R V / 100 R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600

Minute Second Max. I: maximum current from I1, I2 or I3 Day Month Year Hour Minute Second Min. IN: minimum neutral conductor current IN Day Month Year Hour Minute Second Max. IN: maximum neutral conductor current IN Day Month Year Hour Minute Second Min. U: minimum line voltage from U12, U23 or U31 Day Month Year Hour Minute Second Max. U: maximum line voltage from U12, U23 or U31 Day

104413_en_00

PHOENIX CONTACT

11-59

EEM-MA600 Table 11-24 Decimal address 3883 3884 3885 3886 3887 3888 3890 3891 3892 3893 3894 3895 3896 3898 3899 3900 3901 3902 3903 3904 3906 3907 3908 3909 3910 3911 3912 3914 3915 3916 3917 3918 3919 3920 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F2B F2C F2D F2E F2F F30 F32 F33 F34 F35 F36 F37 F38 F3A F3B F3C F3D F3E F3F F40 F42 F43 F44 F45 F46 F47 F48 F4A F4B F4C F4D F4E F4F F50 Number of data words 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Designation Unit Register access R R R R R V / 100 R R R R R R R V / 100 R R R R R R R Hz / 100 R R R R R R R Hz / 100 R R R R R R R 1 / 1000 R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Month Year Hour Minute Second Min. V: minimum line voltage against N from V1, V2 or V3 Day Month Year Hour Minute Second Max. V: maximum line voltage against N from V1, V2 or V3 Day Month Year Hour Minute Second Min. F: minimum frequency F Day Month Year Hour Minute Second Max. F: maximum frequency F Day Month Year Hour Minute Second Min. PF: minimum power factor (total)

11-60

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-24 Decimal address 3922 3923 3924 3925 3926 3927 3928 3930 3931 3932 3933 3934 3935 3936 3938 3939 3940 3941 3942 3943 3944 3946 3947 3948 3949 3950 3951 3952 3954 3955 3956 3957 3958 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F52 F53 F54 F55 F56 F57 F58 F5A F5B F5C F5D F5E F5F F60 F62 F63 F64 F65 F66 F67 F68 F6A F6B F6C F6D F6E F6F F70 F72 F73 F74 F75 F76 Number of data words 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 Designation Unit Register access R R R R R R 1 / 1000 R R R R R R R kW / 100 R R R R R R R kW / 100 R R R R R R R kW / 100 R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Day Month Year Hour Minute Second Max. PF: maximum power factor (total) Day Month Year Hour Minute Second Min. P+: minimum positive real power (total) Day Month Year Hour Minute Second Max. P+: maximum positive real power (total) Day Month Year Hour Minute Second Min. P-: minimum negative real power (total) Day Month Year Hour Minute

104413_en_00

PHOENIX CONTACT

11-61

EEM-MA600 Table 11-24 Decimal address 3959 3960 3962 3963 3964 3965 3966 3967 3968 3970 3971 3972 3973 3974 3975 3976 3978 3979 3980 3981 3982 3983 3984 3986 3987 3988 3989 3990 3991 3992 3994 3995 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F77 F78 F7A F7B F7C F7D F7E F7F F80 F82 F83 F84 F85 F86 F87 F88 F8A F8B F8C F8D F8E F8F F90 F92 F93 F94 F95 F96 F97 F98 F9A F9B Number of data words 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 Designation Unit Register access R kW / 100 R R R R R R R kvar / 100 R R R R R R R kvar / 100 R R R R R R R kvar / 100 R R R R R R R kvar / 100 R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600

Second Max. P-: maximum negative real power (total) Day Month Year Hour Minute Second Min. Q+: minimum positive reactive power (total) Day Month Year Hour Minute Second Max. Q+: maximum positive reactive power (total) Day Month Year Hour Minute Second Min. Q-: minimum negative reactive power (total) Day Month Year Hour Minute Second Max. Q-: maximum negative reactive power (total) Day Month

11-62

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-24 Decimal address 3996 3997 3998 3999 4000 4002 4003 4004 4005 4006 4007 4008 4010 4011 4012 4013 4014 4015 4016 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F9C F9D F9E F9F FA0 FA2 FA3 FA4 FA5 FA6 FA7 FA8 FAA FAB FAC FAD FAE FAF FB0 Number of data words 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Designation Unit Register access R R R R kVA / 100 R R R R R R R kVA / 100 R R R R R R R 0.10% R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Year Hour Minute Second Min. S: minimum apparent power (total) Month Day Year Hour Minute Second Max. S: maximum apparent power (total) Day Month Year Hour Minute Second Min. THD I: minimum total harmonic distortion of currents from I1, I2 or I3 Day Month Year Hour Minute Second Max. THD I: maximum total harmonic distortion of currents from I1, I2 or I3 Day Month Year Hour Minute Second 0.10%

4018 4019 4020 4021 4022 4023 4024

FB2 FB3 FB4 FB5 FB6 FB7 FB8

1 1 1 1 1 1 2

R R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

4026 4027 4028 4029 4030 4031

FBA FBB FBC FBD FBE FBF

1 1 1 1 1 1

R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-63

EEM-MA600 Table 11-24 Decimal address 4032 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address FC0 Number of data words 2 Designation Unit Register access R Available through extension module

Min. THD IN: minimum total harmonic distortion of neutral conductor current Day Month Year Hour Minute Second Max. THD IN: maximum total harmonic distortion of neutral conductor current Day Month Year Hour Minute Second Min. THD U: minimum total harmonic distortion of line voltages from U12, U23 or U31 Day Month Year Hour Minute Second Max. THD U: maximum total harmonic distortion of line voltages from U12, U23 or U31 Day Month Year Hour Minute Second

0.10%

4034 4035 4036 4037 4038 4039 4040

FC2 FC3 FC4 FC5 FC6 FC7 FC8

1 1 1 1 1 1 2

R R R R R R 0.10% R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

4042 4043 4044 4045 4046 4047 4048

FCA FCB FCC FCD FCE FCF FD0

1 1 1 1 1 1 2

R R R R R R 0.10% R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

4050 4051 4052 4053 4054 4055 4056

FD2 FD3 FD4 FD5 FD6 FD7 FD8

1 1 1 1 1 1 2

R R R R R R 0.10% R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

4058 4059 4060 4061 4062 4063

FDA FDB FDC FDD FDE FDF

1 1 1 1 1 1

R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

11-64

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-24 Decimal address 4064 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address FE0 Number of data words 2 Designation Unit Register access R Available through extension module

Min. THD V: minimum total harmonic distortion of line voltages against N from V1, V2 or V3 Day Month Year Hour Minute Second Max. THD V: maximum total harmonic distortion of line voltages against N from V1, V2 or V3 Day Month Year Hour Minute Second

0.10%

4066 4067 4068 4069 4070 4071 4072

FE2 FE3 FE4 FE5 FE6 FE7 FE8

1 1 1 1 1 1 2

R R R R R R 0.10% R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

4074 4075 4076 4077 4078 4079

FEA FEB FEC FED FEE FEF

1 1 1 1 1 1

R R R R R R

EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Range extension: 240 words (decimal) or F0 words (hexadecimal)

Table 11-25 Decimal address

1000 hex: supply voltage failure (course of last 10 voltage interruptions) Hexadecimal Number address of data words Designation Unit Register access Available through extension module

Voltage interruption n-1 4096 4097 4098 4099 4100 4101 1000 1001 1002 1003 1004 1005 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-2 4102 4103 1006 1007 1 1 Day Month R R EEM-MEMO-MA600 EEM-MEMO-MA600

104413_en_00

PHOENIX CONTACT

11-65

EEM-MA600 Table 11-25 Decimal address 4104 4105 4106 4107 1000 hex: supply voltage failure (course of last 10 voltage interruptions) [...] Hexadecimal Number address of data words 1008 1009 100A 100B 1 1 1 1 Designation Unit Register access R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Year Hour Minute Second

Voltage interruption n-3 4108 4109 4110 4111 4112 4113 100C 100D 100E 100F 1010 1011 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-4 4114 4115 4116 4117 4118 4119 1012 1013 1014 1015 1016 1017 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-5 4120 4121 4122 4123 4124 4125 1018 1019 101A 101B 101C 101D 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-6 4126 4127 4128 4129 4130 4131 101E 101F 1020 1021 1022 1023 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-7 4132 4133 4134 1024 1025 1026 1 1 1 Day Month Year R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

11-66

PHOENIX CONTACT

104413_en_00

MODBUS register Table 11-25 Decimal address 4135 4136 4137 1000 hex: supply voltage failure (course of last 10 voltage interruptions) [...] Hexadecimal Number address of data words 1027 1028 1029 1 1 1 Designation Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Hour Minute Second

Voltage interruption n-8 4138 4139 4140 4141 4142 4143 102A 102B 102C 102D 102E 102F 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-9 4144 4145 4146 4147 4148 4149 1030 1031 1032 1033 1034 1035 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltage interruption n-10 4150 4151 4152 4153 4154 4155 1036 1037 1038 1039 103A 103B 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Range extension: 60 words (decimal) or 3C words (hexadecimal)

The indicator is a continuous counter that gives the status of the register in which the last value was saved via the set measurement duration. When you use this table, you must multiply the values by the transmission ratios for the converter used. Real and reactive energy values are saved in registers 3005...7655. These must be allocated by the set measurement duration in order to determine the real and reactive power (see "Example: readout of contents of address 3051" on page 11-70, "Storage register entries" on page 11-70).

104413_en_00

PHOENIX CONTACT

11-67

EEM-MA600

Table 11-26

3000 hex: Course of reactive and real energy over set measurement duration (without consideration of transmission ratios) Hexadecimal address 3000 3001 3002 3005 4199 532D 64C1 7655 Number of data words 1 1 3 4500 4500 4500 4500 End of range Designation Unit Register access R R R kWh/100 kWh/100 kvarh/100 kvarh/100 R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Decimal address 12288 12289 12290 12293 16793 21293 25793 30293

Indicator for average value real power P+/PIndicator for average value reactive power Q+/QDate/time indicator update Range P.1 average value for real power P+/PRange P.2 average value for real power P+/PRange Q.1 average value for reactive power Q+/QRange Q.2 average value for reactive power Q+/Q-

Range extension: 18005 words (decimal) or 4655 words (hexadecimal)

The indicator is a continuous counter that gives the status of the register in which the last value was saved via the set measurement duration. When you use this table, you must multiply the values by the transmission ratios for the converter used.

Table 11-27 Decimal address 32768 32769 32772

8000 hex: course of average values for voltages over the set measurement duration Hexadecimal address 8000 8001 8004 Number of data words 1 3 875 Designation Unit Register Available through access extension module R R V/10 R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Voltages indicator Date/time indicator update Value of line voltages (3U) Value of line voltages against N (3V)

33647

836F

End of range

Range extension: 879 words (decimal) or 36F words (hexadecimal)

11-68

PHOENIX CONTACT

104413_en_00

MODBUS register

The indicator is a continuous counter that gives the status of the register in which the last value was saved via the set measurement duration.

Table 11-28 Decimal address 36864 36865 36868 45568

9000 hex: course of average values for frequency over the set measurement duration Hexadecimal address 9000 9001 9004 B200 Number of data words 1 3 8700 End of range Designation Frequency indicator Date/time indicator update Value of frequency F Hz/100 Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600

Range extension: 8704 words (decimal) or 2200 words (hexadecimal)

Example: readout of register 3002 hex "Date/time indicator update" The register shows the date/time of the last indicator update (last save). Slave address 01 Function 03 High quality address 30 Low quality address 02 The answer for EEM-MA600 is: Slave address 01 Function 03 Number of bytes 06 Register value word 1 071F 07 (month July) / 31. (Day) Register value word 2 100A 16:10 time (16 hour / 10 minutes) Register value word 3 000B 0 (seconds) / 2011 (year) CRC 16 5D0 No. High quality words 00 No. Low quality words 03 CRC 16 AB0B

Example: readout of register 3000 hex "indicator address for real power P+/PThe indicator shows the place in the register where the last value was stored. Slave address 01 Function 03 High quality address 30 Low quality address 00 The answer for EEM-MA600 is: Slave address 01 Function 03 Number of bytes 02 Register value word 1 004C CRC 16 B9B1 No. High quality words 00 No. Low quality words 01 CRC 16 8B0A

The last value was stored in address 3051 (address 3005 + 4C indicator counter).

104413_en_00

PHOENIX CONTACT

11-69

EEM-MA600 Example: readout of contents of address 3051 Measurement duration 10 minutes. Slave address 01 Function 03 High quality address 30 Low quality address 51 No. High quality words 00 No. Low quality words 01 CRC 16 DADB

Address 3005 + 4C = 3051 EEM-MA600's answer is: Slave address 01 Function 03 Number of bytes 02 Register value word 1 statement: 16FA kWh (hex) 5882 kWh/100 (decimal) not based on current and voltage transducer (without consideration of transmission ratios) 58.82 kWh x (1000 A/5 A) = 11764 kWh (for a measurement duration set for 10 minutes at 16:10) Determination of power: P= E/t For a measurement duration of 10 min, you must divide the measured energy by the measurement duration: 11764 kWh/6 (1 h/10 min) = 1960 kW Register value word 1 16FA CRC 16 3667

Storage register entries Table 11-29 Storage of the real energy (measurement duration of 10 minutes) Date/time Register value1 58.28 47.96 35.97 54.67 58.82 Register value2 11656 9592 7194 10934 11764 Calculated Calculated Calculated real power3 real energy4 real power5 9.7 7.9 5.9 9.1 9.8 11656 9592 7194 10934 11764 1942 1598 1199 1822 1960

Hexadecimal Measured value address (decimal) kWh/100 304D 304E 304F 3050 3051
1 2 3

5828 4796 3597 5467 5882

without consideration of transmission ratios (kWh) under consideration of the current transformer transmission ratios 1000 A/5 A (kWh) without consideration of the transmission ratios (kW): Determination of power P= E/t (for example, 58.82 kWh/6 (1 h/10 min) = 9.8 kW under consideration of the current transformer transmission ratios 1000 A/5 A (kWh) under consideration of current transformer transmission ratios 1000 A/5 A (kW): Determination of power P= E/t (for example, 11764 kWh/6 (1 h/10 min) = 1960 kW

4 5

11-70

PHOENIX CONTACT

104413_en_00

MODBUS register Register date/time readout when supply voltage fails Example: moment of deactivation The first word starts with $E Address + 0 Address + 1 Address + 2 $Emdd $hhnn $ssyy 1 word 1 word 1 word m: month 112 dd: day 131 hh: hour 023 nn: minute 060 ss: second 059 yy: year 0255

Example: switch-on moment The first word starts with $F Address + 0 Address + 1 Address + 2 $Fmdd $hhnn $ssyy 1 word 1 word 1 word m: month 112 dd: day 131 hh: hour 023 nn: Minute 060 ss: second 059 yy: year 0255

104413_en_00

PHOENIX CONTACT

11-71

EEM-MA600

11-72

PHOENIX CONTACT

104413_en_00

PROFIBUS register

12 PROFIBUS register
In this section, you will find the following registers. Table 12-1 Description Configuration Module 1 "Main values" Module 2 "Additional values" Module 3 "Undervoltage/Interrupt/Pow&Freq" Module 4 "Overvoltage/Avg U&V/Max&Avg IN" Module 5 "3I&IN harmonics Module 6 "3U harmonics" Module 7 "3V harmonics" Module 8 "Instantaneous MinMax" Module 9 "Specific Data" Module 10 (not available) Module 11 "Specific short data" Diagnostics Register overview For further information See Table 12-2 on page 12-1 See page 12-5 See page 12-11 See page 12-13 See page 12-13 See page 12-14 See page 12-16 See page 12-17 See page 12-18 See page 12-18 See page 12-27 See page 12-28 See page 12-29

12.1

Configuration

Table 12-2 Designation

Configuration (user prm data) Register size (bytes) 1 1 Register access W W Available through extension module

Not available Note: register content is always zero Network type : 0 : 1BL 1 : 2BL 2 : 3BL 3 : 3NBL 4 : 4BL 5 : 4NBL Current transformer secondary side (A) 1:1A 5:5A Current transformer primary side (A)

104413_en_00

PHOENIX CONTACT

12-1

EEM-MA600 Table 12-2 Designation Voltage transducer present? 0 : No 1 : Yes Voltage transducer primary side (V) Voltage transducer secondary side (V) : 60 : 60 V 100 : 100 V 110 : 110 V 115 : 115 V 120 : 120 V 173 : 173 V 190 : 190 V Measurement duration for average value/maximum value accumulation for currents: ( 2 s, 10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Measurement duration for average value/maximum value accumulation for P, Q, S power: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Not available Not available Not available Not available Not available Not available Output signal AO OUT 1: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Configuration (user prm data) [...] Register size (bytes) 1 Register access W Available through extension module

4 1

W W

1 1 1 1 1 1 1

W W W W W W W EEM-2AO-MA600

12-2

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-2 Designation Output type AO OUT 1: 0: I1: current 1: I2: current 2: I3: current 3: In: neutral conductor current 4: U12: line voltages (1-2) 5: U23: line voltages (2-3) 6: U31: line voltages (3-1) 7: P: total real power 8: Q: total real power 9: S: total apparent power 10 : PFL: total inductive power factor 11 : V1: line voltages against N 12 : V2: line voltages against N 13 : V3: line voltages against N 14: F: frequency 15: PFC: total capacitive power factor 16: I: current I1, I2, I3 17: U: line voltages (1-2/2-3/3-1) 18: V: line voltages against N (1/2/3) 19: PPR: total real power (trend) 20: QPR: total reactive power (trend) 21: SPR: total apparent power (trend) 22: TC1: temperature module input EEM-TEMP-MA600 23: TC2: temperature module input EEM-TEMP-MA600 24: TC3: temperature module input EEM-TEMP-MA600 25: TC4: internal temperature EEM-TEMP-MA600 Output value AO OUT 1 for 0 or 4 mA AO OUT 1 unit of output value for 0 or 4 mA: 0: / 1:k 2:M Output value AO OUT 1 for 20 mA AO OUT 1 unit of output value for 20 mA: 0:/ 1:k 2: M Output signal AO OUT 2: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output type AO OUT 2: see AO OUT 1 AO OUT 2 output value for 0 or 4 mA AO OUT 2 unit of output value for 0 or 4 mA: 0:/ 1:k 2:M Configuration (user prm data) [...] Register size (bytes) 1 Register access W Available through extension module EEM-2AO-MA600

2 1

W W

EEM-2AO-MA600 EEM-2AO-MA600

2 1

W W

EEM-2AO-MA600 EEM-2AO-MA600

EEM-2AO-MA600

1 2 1

W W W

EEM-2AO-MA600 EEM-2AO-MA600 EEM-2AO-MA600

104413_en_00

PHOENIX CONTACT

12-3

EEM-MA600 Table 12-2 Designation AO OUT 2 output value for 20 mA AO OUT 2 unit of output value for 20 mA: 0:/ 1:k 2: M Output signal AO OUT 3: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output type AO OUT 3: see AO OUT 1 AO OUT 3 output value for 0 or 4 mA AO OUT 3 unit of output value for 0 or 4 mA: 0:/ 1:k 2: M AO OUT 3 output value for 20 mA AO OUT 2 unit of output value for 20 mA: 0:/ 1:k 2: M Output signal AO OUT 4: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output type AO OUT 4: see AO OUT 1 AO OUT 4 output value for 0 or 4 mA AO OUT 4 unit of output value for 0 or 4 mA: 0:/ 1:k 2:M AO OUT 4 output value for 20 mA AO OUT 4 unit of output value for 20 mA: 0:/ 1:k 2:M Current transformer secondary side (A) 1:1A 5:5A Current transformer primary side (A) Length : 54 bytes Configuration (user prm data) [...] Register size (bytes) 2 1 Register access W W Available through extension module EEM-2AO-MA600 EEM-2AO-MA600

EEM-2AO-MA600

1 2 1

W W W

EEM-2AO-MA600 EEM-2AO-MA600 EEM-2AO-MA600

2 1

W W

EEM-2AO-MA600 EEM-2AO-MA600

EEM-2AO-MA600

1 2 1

W W W

EEM-2AO-MA600 EEM-2AO-MA600 EEM-2AO-MA600

2 1

W W

EEM-2AO-MA600 EEM-2AO-MA600

12-4

PHOENIX CONTACT

104413_en_00

PROFIBUS register

NOTE: Check whether the setting data matches the data provided in the device. When a slave is not recognized by the PROFIBUS master, the master sends GSD file parameters or the default settings. Two options are specified for this procedure: Deactivate the EEM-MA600 programming via the master Configure the EEM-MA600 via the master and then open the "Programming" menu on the front side of the measuring instrument and close again.

The modules feature inputs (display) and outputs (configuration).

12.2
Example:

Module 1 "Main values"

In order to change the idle state for relay 1, you must set bit 4 and bit 0 to 1. Table 12-3 Designation Relay change of state If bit 4 and the allocated bit for the desired relay output is at 1, the relay's idle state can be changed. Bit 0 : relay 1 Bit 1 : relay 2 Bit 2 : relay 3 Bit 3 : relay 4 Bit 4 : changing relay configuration Bit 5 : resetting a size Bit 6 : not available Bit 7 : not available DO OUT 1 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 2 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 3 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 4 relay idle state: 0 : NO (open) 1 : NC (closed) Output table Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600

EEM-2DIO-MA600

EEM-2DIO-MA600

EEM-2DIO-MA600

EEM-2DIO-MA600

104413_en_00

PHOENIX CONTACT

12-5

EEM-MA600 Table 12-3 Designation DO OUT 1 output type : 0 : CDE: Controlling relay state via RS485 1 : I: current I1, I2, I3 2 : U: line voltages (1-2/2-3/3-1) 3 : P+: total positive real power 4 : Q+: total positive reactive power 5 : S: total apparent power 6 : F: frequency 7 : PFL: total inductive power factor 8 : THDI: total harmonic distortion of currents I1, I2, I3 9 : THDU: total harmonic distortion of the conductor voltages (1-2/2-3/3-1) 10 : IN: neutral conductor current 11 : HOUr: operating hours counter 12 : V: conductor voltages against N (1/2/3) 13 : THDIN: total harmonic distortion of neutral conductor current 14 : THDV: total harmonic distortion of conductor voltages against N (1/2/3) 15 : P-: total negative real power 16 : Q-: total negative reactive power 17 : PFC: total capacitative power factor 18 : CDT: control of relay state via RS485, resetting relay with idle state 19 : TC1: temperature module input EEM-TEMP-MA600 20 : TC2: temperature module input EEM-TEMP-MA600 21 : TC3: temperature module input EEM-TEMP-MA600 22 : TC4: internal temperature EEM-TEMP-MA600 23 : PPR: total real power (trend) 24 : QPR: total reactive power (trend) 25 : SPR: total apparent power (trend) DO OUT 1 alarm output value lower switching threshold DO OUT 1 unit of output value for the lower switching threshold 0: / 1: k 2: M DO OUT 1 alarm output value upper switching threshold DO OUT 1 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 1 hysteresis (0-99%) DO OUT 1 trigger delay (0-999 s) Output type DO OUT 2: see DO OUT 1 DO OUT 2 alarm output value lower switching threshold Output table [...] Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600

2 1

W W

EEM-2DIO-MA600 EEM-2DIO-MA600

2 1

W W

EEM-2DIO-MA600 EEM-2DIO-MA600

1 2 1 2

W W W W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

12-6

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-3 Designation DO OUT 2 unit of output value for the lower switching threshold 0: / 1: k 2: M DO OUT 2 alarm output value upper switching threshold DO OUT 2 unit of output value for upper switching threshold 0: / 1: k 2: M DO OUT 2 hysteresis (0-99%) DO OUT 2 trigger delay (0-999 s) Output table [...] Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600

2 1

W W

EEM-2DIO-MA600 EEM-2DIO-MA600

1 2

W W

EEM-2DIO-MA600 EEM-2DIO-MA600

104413_en_00

PHOENIX CONTACT

12-7

EEM-MA600 Table 12-3 Designation Output resetting (Reset) Bit 0 : max/avg I1,I2,I3: maximum value for currents (I1, I2, I3) Bit 1 : max/avg P+: maximum value of total positive real power Bit 2 : max/avg P-: maximum value of total negative real power Bit 3 : max/avg Q+: maximum value of total positive reactive power Bit 4 : max/avg Q-: maximum value of total negative reactive power Bit 5 : max/avg S: maximum value of total apparent power Bit 6 : HOUr: operating hours counter Bit 7 : EA+: current positive real energy kWh+ Bit 8 : ER+: current positive reactive energy kvarh+ Bit 9 : ES: current apparent energy kVAh Bit 10 : EA-: current negative real energy kWhBit 11 : ER-: current negative reactive energy kvarhBit 12 : all measured values Bit 13 : E1: counter state for digital input 1 Bit 14 : E2: counter state for digital input 2 Bit 15 : not available Output resetting (Reset) Bit 0 : E1: counter state for digital input 1 Bit 1 : E2: counter state for digital input 2 Bit 2 : E3: counter state for digital input 3 Bit 3 : E4: counter state for digital input 4 Bit 4 : not available Bit 5 : not available Bit 6 : min./max. I: min./max. power from I1, I2 or I3 Bit 7 : min./max. In: min./max. neutral conductor current Bit 8 : min./max. U: min./max. line voltage from U12, U23 or U31 Bit 9 : min./max. F: min./max. frequency value Bit 10 : min./max. PF: min./max. power factor (total) Bit 11 : min./max. P: min./max. positive and negative real power (total) Bit 12 : min./max. Q: min./max. positive and negative reactive power (total) Bit 13 : min./max. THD I: min./max. total harmonic distortion of currents from I1, I2, or I3 Bit 14 : min./max. THD IN: min./max. total harmonic distortion of neutral conductor current Bit 15 : min./max. THD U: min./max. total harmonic distortion of line voltages from U12, U23 or U31 Length : 29 bytes Output table [...] Register size (bytes) 2 Register access W Available through extension module

12-8

PHOENIX CONTACT

104413_en_00

PROFIBUS register

When you use this table, you must multiply the values by the transformation ratios for the converters used. This module contains the measured values for the currents, voltages, power, frequencies, power factors, positive energy and operating hour counter values.

Table 12-4

Display of main measured values not based on current transformer and voltage transducer (without consideration of transformation ratios) input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Available through extension module

Designation I1: current (mA) I2: current (mA) I3: current (mA) In: neutral conductor current (mA) U12: line voltage (V/100) U23: line voltage (V/100) U31: line voltage (V/100) V1: line voltage against N (V/100) V2: line voltage against N (V/100) V3: line voltage against N (V/100) F: frequency (Hz/100) P: total real power +/- (kW/100) Q: total reactive power +/- (kvar/100) S: total apparent power (kVA/100) PF: total power factor -: capacitive and +: inductive (0.001) Max/avg I1: maximum current value (mA) Max/avg I2: maximum current value (mA) Max/avg I3: maximum current value (mA) Max/avg P+: maximum total positive real power value (W) Max/avg P-: maximum total negative real power value (W) Max/avg Q+: maximum total positive reactive power value (var) Max/avg Q-: maximum total negative reactive power value (var) Max/avg S: maximum total apparent power value (VA) Ea+: current positive real energy < 10,000 kWh Ea+: current positive real energy > 10,000 kWh Er +: current positive reactive energy < 10,000 kvarh Er +: current positive reactive energy > 10,000 kvarh ES: current apparent energy < 10,000 kVAh ES: current apparent energy > 10,000 kVAh ISYS: average current value (I1+I2+I3)/3 (mA)

104413_en_00

PHOENIX CONTACT

12-9

EEM-MA600 Table 12-4 Display of main measured values not based on current transformer and voltage transducer (without consideration of transformation ratios) input table [...] Register size (bytes) 2 Register access R R R R Available through extension module

Designation USYS: average line voltage value (U12 + U23 + U31)/3 (V/10)

VSYS: average line voltage value against N (V1 + V2 + V3 )/3 (V/10) 2 Operating hours counter < 10,000 (h/100) Operating hours counter > 10,000 (h/100) Length: 68 bytes Calculation of affected values 2 2

The currents must be multiplied by the SW ratio, the currents with the SpW ratio (for high voltage) and the power by the SW x SpW ratio. Example: SW = 100/5 = 20 SpW = 20,000/100 = 200 SW x SpW = 20 x 200 = 4000 All power is multiplied by 4000 (without SpW, SpW = 1), currents by 20 and voltages by 200. Description: I system= I1 + I2 + I3 / 3 U system = U12 + U21 + U31 / 3 V system = V1 + V2 + V3 / 3 Conversion of values with and without sign bits When the current, voltages or energy is negative, the following rule must be applied: use the opposite bit per data bit Add 1 to this opposite bit Example Negative value -28864 mV In binary format Opposite corresponds to Opposite +1 corresponds to or 366.72 V in decimal figures 0111 0000 1100 0000 1000 1111 0011 1111 1000 1111 0100 0000

12-10

PHOENIX CONTACT

104413_en_00

PROFIBUS register

12.3

Module 2 "Additional values"

When you use this table, you must multiply the values by the transformation ratios for the converters used. This module contains the measurements per phase, average values, - energy and states (on/off input). The output table is identical to the output table from module 1.

Table 12-5

Display of additional measured values not based on current transformer and voltage transducer (without consideration of transformation ratios), input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R R R EEM-2DIO-MA600 Available through extension module

Designation P1: real power phase 1 +/- (kW/100) P2: real power phase 2 +/- (kW/100) P3: real power phase 3 +/- (kW/100) Q1: reactive power phase 1 +/- (kvar/100) Q2: reactive power phase 2 +/- (kvar/100) Q3: reactive power phase 3 +/- (kvar/100) S1: apparent power phase 1 (kVA/100) S2: apparent power phase 2 (kVA/100) S3: apparent power phase 3 (kVA/100) PF1: power factor phase 1 -: capacitive and +: inductive (0.001) PF2: power factor phase 2 -: capacitive and +: inductive (0.001) PF3: power factor phase 3 -: capacitive and +: inductive (0.001) Avg I1: average current value (mA) Avg I2: average current value (mA) Avg I3: average current value (mA) Avg P+: average total positive real power value (W) Avg P-: average total negative real power value (W) Avg Q+: average total positive reactive power value (var) Avg Q-: average total negative reactive power value (var) Avg S: average total apparent power value (VA) EA-: negative real energy < 10,000 kWh EA-: negative real energy > 10,000 kWh ER-: negative reactive energy < 10,000 kvarh ER-: negative reactive energy > 10,000 kvarh Counter state digital input DI 1 < 10,000

104413_en_00

PHOENIX CONTACT

12-11

EEM-MA600 Table 12-5 Display of additional measured values not based on current transformer and voltage transducer (without consideration of transformation ratios), input table [...] Register size (bytes) 2 2 2 2 2 2 2 2 Register access R R R R R R R R Available through extension module EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

Designation Counter state digital input DI 1 > 10,000 Counter state digital input DI 2 < 10,000 Counter state digital input DI 2 > 10,000 Counter state digital input DI 3 < 10,000 Counter state digital input DI 3 > 10,000 Counter state digital input DI 4 < 10,000 Counter state digital input DI 4 > 10,000 Status of digital inputs 1, 2, 3, 4. Length: 66 bytes Note

The currents must be multiplied by the SW ratio, the currents with the SpW ratio (for high voltage) and the power by the SW x SpW ratio. Example: SW = 100/5 = 20 SpW = 20,000/100 = 200 SW x SpW = 20 x 200 = 4000 All power is multiplied by 4000 (without SpW, SpW = 1), currents by 20 and voltages by 200. Status of the inputs Input 1 = 0 bit Input 2 = 1 bit Input 3 = 2 bit Input 4 = 4 bit When active, bit 1 When inactive, bit 0 Conversion of values with and without sign bits When the current, voltages or energy is negative, the following rule must be applied: use the opposite bit per data bit Add 1 to this opposite bit

12-12

PHOENIX CONTACT

104413_en_00

PROFIBUS register Example Negative value -28864 mV In binary format Opposite corresponds to Opposite +1 corresponds to or 366.72 V in decimal format 0111 0000 1100 0000 1000 1111 0011 1111 1000 1111 0100 0000

12.4

Module 3 "Undervoltage/Interrupt/Pow&Freq"

Module 3 is not available.

12.5

Module 4 "Overvoltage/Avg U&V/Max&Avg IN"

Module 4 is not available.

104413_en_00

PHOENIX CONTACT

12-13

EEM-MA600

12.6

Module 5 "3I&IN harmonics"

This module contains the THD values I and THD IN as well as the individual harmonic content for currents: I up to 15. harmonic. The output table is identical to the output table from module 1.

Table 12-6 Designation

Display of total harmonic distortion (THD) and harmonics for currents, input table Register size (bytes) 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Available through extension module

THD I1: total harmonic distortion of current (0.1%) THD I2: total harmonic distortion of current (0.1%) THD I3: total harmonic distortion of current (0.1%)

THD In: total harmonic distortion of neutral conductor current (0.1%) 2 Content of 3rd harmonic I1 (0.1%) Content of 3rd harmonic I2 (0.1%) Content of 3rd harmonic I3 (0.1%) Content of 3rd harmonic IN (0.1%) Content of 5th harmonic I1 (0.1%) Content of 5th harmonic I2 (0.1%) Content of 5th harmonic I3 (0.1%) Content of 5th harmonic IN (0.1%) Content of 7th harmonic I1 (0.1%) Content of 7th harmonic I2 (0.1%) Content of 7th harmonic I3 (0.1%) Content of 7th harmonic IN (0.1%) Content of 9th harmonic I1 (0.1%) Content of 9th harmonic I2 (0.1%) Content of 9th harmonic I3 (0.1%) Content of 9th harmonic IN (0.1%) Content of 11th harmonic I1 (0.1%) Content of 11th harmonic I2 (0.1%) Content of 11th harmonic I3 (0.1%) Content of 11th harmonic IN (0.1%) Content of 13th harmonic I1 (0.1%) Content of 13th harmonic I2 (0.1%) Content of 13th harmonic I3 (0.1%) Content of 13th harmonic IN (0.1%) Content of 15th harmonic I1 (0.1%) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

12-14

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-6 Designation Content of 15th harmonic I2 (0.1%) Content of 15th harmonic I3 (0.1%) Content of 15th harmonic IN (0.1%) Length: 64 bytes Display of total harmonic distortion (THD) and harmonics for currents, input table [...] Register size (bytes) 2 2 2 Register access R R Available through extension module

104413_en_00

PHOENIX CONTACT

12-15

EEM-MA600

12.7

Module 6 "3U harmonics"

This module contains the THD values as well as the individual harmonic content for line voltages up to 11th harmonic. The output table is identical to the output table from module 1.

Table 12-7 Designation

Display of total harmonic distortion (THD) and harmonics for line voltages U (phase/phase), input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R Available through extension module

THD U12: total harmonic distortion of line voltage (0.1%) THD U23: total harmonic distortion of line voltage (0.1%) THD U31: total harmonic distortion of line voltage (0.1%) Content of 3rd harmonic U12 (0.1%) Content of 3rd harmonic U23 (0.1%) Content of 3rd harmonic U31 (0.1%) Not available Content of 5th harmonic U12 (0.1%) Content of 5th harmonic U23 (0.1%) Content of 5th harmonic U31 (0.1%) Not available Content of 7th harmonic U12 (0.1%) Content of 7th harmonic U23 (0.1%) Content of 7th harmonic U31 (0.1%) Not available Content of 9th harmonic U12 (0.1%) Content of 9th harmonic U23 (0.1%) Content of 9th harmonic U31 (0.1%) Not available Content of 11th harmonic U12 (0.1%) Content of 11th harmonic U23 (0.1%) Content of 11th harmonic U31 (0.1%) Not available Length: 48 bytes

12-16

PHOENIX CONTACT

104413_en_00

PROFIBUS register

12.8

Module 7 "3V harmonics"

This module contains the THD values as well as the individual harmonic content for line voltages against N up to 11th harmonic. The output table is identical to the output table from module 1.

Table 12-8 Designation

Display of total harmonic distortion (THD) and harmonics for line voltages against N (V), input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R Available through extension module

THD V1: total harmonic distortion of line voltage against N (0.1%) THD V2: total harmonic distortion of line voltage against N (0.1%) THD V3: total harmonic distortion of line voltage against N (0.1%) Content of 3rd harmonic V1 (0.1%) Content of 3rd harmonic V2 (0.1%) Content of 3rd harmonic V3 (0.1%) Not available Content of 5th harmonic V1 (0.1%) Content of 5th harmonic V2 (0.1%) Content of 5th harmonic V3 (0.1%) Not available Content of 7th harmonic V1 (0.1%) Content of 7th harmonic V2 (0.1%) Content of 7th harmonic V3 (0.1%) Not available Content of 9th harmonic V1 (0.1%) Content of 9th harmonic V2 (0.1%) Content of 9th harmonic V3 (0.1%) Not available Content of 11th harmonic V1 (0.1%) Content of 11th harmonic V2 (0.1%) Content of 11th harmonic V3 (0.1%) Not available Length: 48 bytes

104413_en_00

PHOENIX CONTACT

12-17

EEM-MA600

12.9

Module 8 "Instantaneous MinMax"

Module 8 is not available.

12.10 Module 9 "Specific Data"


12.10.1 Configuration of the outputs

When bit 7 of byte 1 is at 0, the table can be used as standard to configure the outputs.

Example: In order to change the idle state for relay 1, you must set bit 4 and bit 0 to 1. Table 12-9 Designation Relay change of state If bit 4 and the allocated bit for the desired relay output is at 1, the relay's idle state can be changed. Bit 0 : relay 1 Bit 1 : relay 2 Bit 2 : relay 3 Bit 3 : relay 4 Bit 4 : changing relay configuration Bit 5 : resetting a size Bit 6 : not used Bit 7 : 0 > activate table for parameterization of digital outputs DO OUT 1 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 2 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 3 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 4 relay idle state: 0 : NO (open) 1 : NC (closed) Special table, output table Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600

EEM-2DIO-MA600

EEM-2DIO-MA600

EEM-2DIO-MA600

EEM-2DIO-MA600

12-18

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-9 Designation Output type DO OUT 1: 0: CDE: controlling relay state via RS485 1: I: current I1, I2, I3 2: U: line voltages (1-2/2-3/3-1) 3: P+: total positive real power 4: Q+: total positive reactive power 5: S: total apparent power 6: F: frequency 7: PFL: total inductive power factor 8: THDI: total harmonic distortion for currents I1, I2, I3 9: THDU: total harmonic distortion for line voltages (1-2/2-3/3-1) 10: In: neutral conductor current 11: HOUr: operating hours counter 12: V: line voltages against N (1/2/3) 13: THDIN: total harmonic distortion of neutral conductor current 14: THDV: total harmonic distortion of line voltages against N (1/2/3) 15: P-: total negative real power 16: Q-: total negative reactive power 17: PFC: total capacitive power factor 18: CDT: controlling relay state via RS485, resetting relay to idle 19: TC1: temperature module input EEM-TEMP-MA600 20: TC2: temperature module input EEM-TEMP-MA600 21: TC3: temperature module input EEM-TEMP-MA600 22: TC4: internal temperature EEM-TEMP-MA600 23: PPR: total real power (trend) 24: QPR: total reactive power (trend) 25: SPR: total apparent power (trend) DO OUT 1 alarm output value lower switching threshold DO OUT 1 unit of output value for the lower switching threshold 0: / 1: k 2: M DO OUT 1 alarm output value upper switching threshold DO OUT 1 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 1 hysteresis (0-99%) DO OUT 1 trigger delay (0-999 s) Output type DO OUT 2: see DO OUT 1 DO OUT 2 alarm output value lower switching threshold DO OUT 2 unit of output value for the lower switching threshold 0: / 1: k 2: M Special table, output table [...] Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600

2 1

W W

EEM-2DIO-MA600 EEM-2DIO-MA600

2 1

W W

EEM-2DIO-MA600 EEM-2DIO-MA600

1 2 1 2 1

W W W W W

EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600

104413_en_00

PHOENIX CONTACT

12-19

EEM-MA600 Table 12-9 Designation DO OUT 2 alarm output value upper switching threshold DO OUT 2 unit of output value for upper switching threshold 0: / 1: k 2: M DO OUT 2 hysteresis (0-99%) DO OUT 2 trigger delay (0-999 s) Special table, output table [...] Register size (bytes) 2 1 Register access W W Available through extension module EEM-2DIO-MA600 EEM-2DIO-MA600

1 2

W W W

EEM-2DIO-MA600 EEM-2DIO-MA600

Resetting outputs (reset) 2 Bit 0 : max/avg I1,I2,I3: maximum value of currents (I1, I2, I3) Bit 1 : max/avg P+: maximum total positive real power value Bit 2 : max/avg P-: maximum total negative real power value Bit 3 : max/avg Q+: maximum total positive reactive power value Bit 4 : max/avg Q-: maximum total negative reactive power value Bit 5 : max/avg S: maximum total apparent power value Bit 6 : HOUr: operating hours counter Bit 7 : EA+: current positive real energy kWh+ Bit 8 : ER+: current positive reactive energy kvarh+ Bit 9 : ES: current apparent energy kVAh Bit 10 : EA-: current negative real energy kWhBit 11 : ER-: current negative reactive energy kvarhBit 12 : all measured values Bit 13 : E1: counter state digital input 1 Bit 14 : E2: counter state digital input 2 Bit 15 : not available Resetting outputs (reset) Bit 0 : E1: counter state digital input 1 Bit 1 : E2: counter state digital input 2 Bit 2 : E3: counter state digital input 3 Bit 3 : E4: counter state digital input 4 Bit 4 : not available Bit 5 : not available Bit 6 : Min./Max. I: min./max. current from I1, I2, or I3 Bit 7 : Min./Max. In: min./max. neutral conductor current Bit 8 : Min./Max. U: min./max. line voltage from U12, U23 or U31 Bit 9 : Min./Max. F: min./max. frequency value Bit 10 : Min./Max. PF: min./max. power factor (total) Bit 11 : Min./Max. P: min./max. positive and negative real power (total) Bit 12 : Min./Max. Q: min./max. positive and negative reactive power (total) Bit 13 : Min./Max. THD I: min./max. total harmonic distortion of currents from I1, I2 or I3 Bit 14 : Min./Max. THD IN: min./max. total harmonic distortion of neutral conductor current Bit 15 : Min./Max. THD U: min./max. total harmonic distortion of line voltages from U12, U23 or U31 Not available Length: 33 bytes 2

12-20

PHOENIX CONTACT

104413_en_00

PROFIBUS register

12.10.2 User-defined table

Users can take advantage of Module 9 by compiling their own specific tables from "all" values. If bit 7 of byte 1 is at 1, the user can assign the outputs. The table number is an identification number that refers to the module table. You can create a table with 16 registers with addresses from module table 9.

Table 12-10 Designation

Special table, output table Register size (bytes) 1 Register access W Available through extension module

Table number Bit 0-6 : table number Bit 7 : 1 > address table Value 1 address Value 2 address Value 3 address Value 4 address Value 5 address Value 6 address Value 7 address Value 8 address Value 9 address Value 10 address Value 11 address Value 12 address Value 13 address Value 14 address Value 15 address Value 16 address

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

W W W W W W W W W W W W W W W W

MSB: most significant byte (for example, 8-bit number with the MSB as bit 0) LSB: least significant byte (for example, 8-bit number with LSB as bit 0)

104413_en_00

PHOENIX CONTACT

12-21

EEM-MA600

Table 12-11 Designation

List of values (assignment of addresses to corresponding measured values), input table Register size (bytes) Decimal address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Hexadecimal Register Available through address access extension module 0000 0001 0002 0003 0004 0005 0006 0007 0008 0009 000 A 000B 000C 000D 000E 000F 0010 0011 0012 0013 0014 0015 0016 0017 0018 0019 001 A 001B 001C R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

I1: current (mA) I2: current (mA) I3: current (mA) In: neutral conductor current (mA) U12: line voltage (V/100) U23: line voltage (V/100) U31: line voltage (V/100) V1: line voltage against N (V/100) V2: line voltage against N (V/100) V3: line voltage against N (V/100) F: frequency (Hz/100) P: total real power +/- (kW/100) Q: total reactive power +/- (kvar/100) S: total apparent power (kVA/100) PF: total power factor -: capacitive and +: inductive (0.001) Max/avg I1: maximum current value (mA) Max/avg I2: maximum current value (mA) Max/avg I3: maximum current value (mA) Max/avg P+: maximum total positive real power value (kW/100) Max/avg P-: maximum total negative real power value (kW/100) Max/avg Q+: maximum total positive reactive power value (kvar/100) Max/avg Q-: maximum total negative reactive power value (kvar/100) Max/avg S: maximum total apparent power value (kVA/100) EA+: current positive real energy < 10,000 (kWh) EA+: current positive real energy > 10,000 (kWh) ER +: current positive reactive energy < 10,000 (kvarh) ER +: current positive reactive energy > 10,000 (kvarh) ES: current apparent energy < 10,000 (kVAh) ES: current apparent energy > 10,000 (kVAh)

12-22

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 Hexadecimal Register Available through address access extension module 001D 001E 001F 0020 0021 0022 0023 0024 0025 0026 0027 0028 0029 002 A 002B 002C 002D 002E 002F 0030 0031 0032 0033 0034 0035 0036 0037 0038 0039 003 A R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

P1: real power phase 1 +/- (kW/100) P2: real power phase 2 +/- (kW/100) P3: real power phase 3 +/- (kW/100) Q1: reactive power phase 1 +/- (kvar/100) Q2: reactive power phase 2 +/- (kvar/100) Q3: reactive power phase 3 +/- (kvar/100) S1: apparent power phase 1 (kVA/100) S2: apparent power phase 2 (kVA/100) S3: apparent power phase 3 (kVA/100) PF1: power factor phase 1 -: capacitive and +: inductive (0.001) PF2: power factor phase 2 -: capacitive and +: inductive (0.001) PF3: power factor phase 3 -: capacitive and +: inductive (0.001) Avg I1: average current value (mA) Avg I2: average current value (mA) Avg I3: average current value (mA) Avg P+: average total positive real power value (W) Avg P-: average total negative real power value (W) Avg Q+: average total positive reactive power value (var) Avg Q-: average total negative reactive power value (var) Avg S: average total apparent value (VA) EA-: current negative real energy < 10,000 (kWh) EA-: current negative real energy > 10,000 (kWh) ER -: current negative reactive energy < 10,000 (kvar) ER -: current negative reactive energy > 10,000 (kvar) Counter state digital input DI 1 < 10,000 Counter state digital input DI 1 > 10,000 Counter state digital input DI 2 < 10,000 Counter state digital input DI 2 > 10,000 Counter state digital input DI 3 < 10,000 Counter state digital input DI 3 > 10,000

104413_en_00

PHOENIX CONTACT

12-23

EEM-MA600 Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 Hexadecimal Register Available through address access extension module 003B 003C 003D 003E 003F 0040 0041 0042 0043 0044 0045 0046 0047 0048 0049 004 A 004B 004C 004D 004E 004F 0050 0051 0052 0053 0054 0055 0056 0057 0058 0059 005 A 005B R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

Counter state digital input DI 4 < 10,000 Counter state digital input DI 4 > 10,000 Status of digital inputs 1, 2, 3, 4 THD I1: total harmonic distortion of current (0.1%) THD I2: total harmonic distortion of current (0.1%) THD I3: total harmonic distortion of current (0.1%) THD In: total harmonic distortion of neutral conductor current (0.1%) Content of 3rd harmonic I1 (0.1%) Content of 3rd harmonic I2 (0.1%) Content of 3rd harmonic I3 (0.1%) Content of 3rd harmonic IN (0.1%) Content of 5th harmonic I1 (0.1%) Content of 5th harmonic I2 (0.1%) Content of 5th harmonic I3 (0.1%) Content of 5th harmonic IN (0.1%) Content of 7th harmonic I1 (0.1%) Content of 7th harmonic I2 (0.1%) Content of 7th harmonic I3 (0.1%) Content of 7th harmonic IN (0.1%) Content of 9th harmonic I1 (0.1%) Content of 9th harmonic I2 (0.1%) Content of 9th harmonic I3 (0.1%) Content of 9th harmonic IN (0.1%) Content of 11th harmonic I1 (0.1%) Content of 11th harmonic I2 (0.1%) Content of 11th harmonic I3 (0.1%) Content of 11th harmonic IN (0.1%) Content of 13th harmonic I1 (0.1%) Content of 13th harmonic I2 (0.1%) Content of 13th harmonic I3 (0.1%) Content of 13th harmonic IN (0.1%) Content of 15th harmonic I1 (0.1%) Content of 15th harmonic I2 (0.1%)

12-24

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 Hexadecimal Register Available through address access extension module 005C 005D 005E 005F 0060 0061 0062 0063 0064 0065 0066 0067 0068 0069 006 A 006B 006C 006D 006E 006F 0070 0071 0072 0073 0074 0075 0076 0077 0078 0079 007 A 007B R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R

Content of 15th harmonic I3 (0.1%) Content of 15th harmonic IN (0.1%) THD U12: total harmonic distortion of line voltage (0.1%) THD U23: total harmonic distortion of line voltage (0.1%) THD U31: total harmonic distortion of line voltage (0.1%) Content of 3rd harmonic U12 (0.1%) Content of 3rd harmonic U23 (0.1%) Content of 3rd harmonic U31 (0.1%) Content of 5th harmonic U12 (0.1%) Content of 5th harmonic U23 (0.1%) Content of 5th harmonic U31 (0.1%) Content of 7th harmonic U12 (0.1%) Content of 7th harmonic U23 (0.1%) Content of 7th harmonic U31 (0.1%) Content of 9th harmonic U12 (0.1%) Content of 9th harmonic U23 (0.1%) Content of 9th harmonic U31 (0.1%) Content of 11th harmonic U12 (0.1%) Content of 11th harmonic U23 (0.1%) Content of 11th harmonic U31 (0.1%) Content of 13th harmonic U12 (0.1%) Content of 13th harmonic U23 (0.1%) Content of 13th harmonic U31 (0.1%) Content of 15th harmonic U12 (0.1%) Content of 15th harmonic U23 (0.1%) Content of 15th harmonic U31 (0.1%) THD V1: total harmonic distortion of line voltage against N (0.1%) THD V2: total harmonic distortion of line voltage against N (0.1%) THD V3: total harmonic distortion of line voltage against N (0.1%) Content of 3rd harmonic V1 (0.1%) Content of 3rd harmonic V2 (0.1%) Content of 3rd harmonic V3 (0.1%)

104413_en_00

PHOENIX CONTACT

12-25

EEM-MA600 Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 Hexadecimal Register Available through address access extension module 007C 007D 007E 007F 0080 0081 0082 0083 0084 0085 0086 0087 0088 0089 008 A 008B 008C 008D 008E 008F 0090 0091 0092 R R R R R R R R R R R R R R R R R R R R R R R

Content of 5th harmonic V1 (0.1%) Content of 5th harmonic V2 (0.1%) Content of 5th harmonic V3 (0.1%) Content of 7th harmonic V1 (0.1%) Content of 7th harmonic V2 (0.1%) Content of 7th harmonic V3 (0.1%) Content of 9th harmonic V1 (0.1%) Content of 9th harmonic V2 (0.1%) Content of 9th harmonic V3 (0.1%) Content of 11th harmonic V1 (0.1%) Content of 11th harmonic V2 (0.1%) Content of 11th harmonic V3 (0.1%) Content of 13th harmonic V1 (0.1%) Content of 13th harmonic V2 (0.1%) Content of 13th harmonic V3 (0.1%) Content of 15th harmonic V1 (0.1%) Content of 15th harmonic V2 (0.1%) Content of 15th harmonic V3 (0.1%) ISYS: average current value (I1 + I2 + I3)/3 (mA) USYS: average line voltage value (U12 + U23 + U31)/3 (V/10) VSYS: average line voltage value against N (V1 + V2 + V3 )/3 (V/10) Operating hours counter < 10,000 (h/100) Operating hours counter > 10,000 (h/100)

The table number is an identification number that refers to the module table. You can create a table with 16 registers with addresses from module table 9.

Table 12-12 Designation Table number Value 1 Value 2

Input table Register size (bytes) 1 2 2 Register access R R R Available through expansion module

12-26

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-12 Designation Value 3 Value 4 Value 5 Value 6 Value 7 Value 8 Value 9 Value 10 Value 11 Value 12 Value 13 Value 14 Value 15 Value 16 Length: 33 bytes Input table [...] Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R Available through expansion module

12.11 Module 10 (not available)

Module 10 is not available.

104413_en_00

PHOENIX CONTACT

12-27

EEM-MA600

12.12 Module 11 "Specific short data"

The table number is an identification number that refers to the module table. You can create a table with 4 registers with addresses from module table 9.

Table 12-13 Designation Table number

Limited special table, output table Register size (bytes) 1 2 2 2 2 W W W W Register access Available through expansion module

Value 1 address Value 2 address Value 3 address Value 4 address Length: 9 bytes

You can read out the assigned addresses using the input table.

Table 12-14 Designation Table number Value 1 Value 2 Value 3 Value 4

Input table Register size (bytes) 1 2 2 2 2 Register access R R R R R Available through expansion module

Length: 9 bytes

12-28

PHOENIX CONTACT

104413_en_00

PROFIBUS register

12.13 Diagnostics
The diagnostics function includes the display of an extension module, serial number, measuring instrument product code as well as of an alarm or value overrun.

Table 12-15 Designation

Diagnostics Register size (bytes) 1 Register access R Available through expansion module

Slot 1 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600

Slot 2 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600 Slot 3 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600

104413_en_00

PHOENIX CONTACT

12-29

EEM-MA600 Table 12-15 Designation Slot 4 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600 Serial number Manufacturer code Diagnostics [...] Register size (bytes) 1 Register access R Available through expansion module

4 1

R R

12-30

PHOENIX CONTACT

104413_en_00

PROFIBUS register Table 12-15 Designation Diagnostics [...] Register size (bytes) Register access R Available through expansion module

OUT 1 Current alarm lower threshold 4 (output types): Bit 0: I: Total current Bit 1: In: Neutral conductor current Bit 2: U: Line voltages (1-2/2-3/3-1) Bit 3: V: Line voltage against N (1/2/3) Bit 4: P+: Total positive real power Bit 5: Q+: Total positive reactive power Bit 6: S: Total apparent power Bit 7: F: Frequency Bit 8: PFL: Total inductive power factor Bit 9: HOUr: operating hours counter Bit 10: THD I: Total harmonic distortion of current Bit 11: THD IN: Total harmonic distortion of neutral conductor current Bit 12: THD U: Total harmonic distortion of line voltage (1-2/2-3/31) Bit 13: THD V: Total harmonic distortion of line voltage against N (1/2/3) Bit 14: P-: Total negative real power Bit 15: Q-: Total negative reactive power Bit 16: PFC: Total capacitative power factor Bit 17...31: not available OUT 1 threshold exceeded 4 (output types): Bit 0: I: Total current Bit 1: In: Neutral conductor current Bit 2: U: Line voltages (1-2/2-3/3-1) Bit 3: V: Line voltage against N (1/2/3) Bit 4: P+: Total positive real power Bit 5: Q+: Total positive reactive power Bit 6: S: Total apparent power Bit 7: F: Frequency Bit 8: PFL: Total inductive power factor Bit 9: HOUr: Operating hours counter Bit 10: THD I: Total harmonic distortion of current Bit 11: THD IN: Total harmonic distortion of neutral conductor current Bit 12: THD U: Total harmonic distortion of line voltage (1-2/2-3/31) Bit 13: THD V: Total harmonic distortion of line voltage against N (1/2/3) Bit 14: P-: Total negative real power Bit 15: Q-: Total negative reactive power Bit 16: PFC: Total capacitative power factor Bit 17...31: not available Length: 17 bytes

104413_en_00

PHOENIX CONTACT

12-31

EEM-MA600

13 Technical data
Input data
Measuring principle Measured value True r.m.s. value measurement (TRMS) up to 63 Harmonic AC sine (45 Hz ... 65 Hz)

Voltage measurement V1, V2, V3


Input voltage range Phase/phase Phase/neutral conductor Accuracy 18 . 700 V AC 11 . 404 V AC 0.2%

Current measurement I1, I2, I3


Input current (via external transformers) Primary Secondary Overload capacity Operate threshold of the nominal measuring range value Accuracy 9999 A 1 A or 5 A 10 A (continuous) 10 mA 0.2%

Power measurement
Measuring range Accuracy Real energy (IEC 62053-22) Reactive energy (IEC 62053-23) 0 ... 8000 MW/Mvar/MVA 0.5% Class 0.5S Class 2

Output data
Optional for special function/communication module

Supply
Supply voltage range Nominal power consumption 110 400 V AC 10% 120 ... 350 V DC 20% < 10 VA (without extension modules) < 20 VA (with extension modules)

Display
Type Refresh Backlit LCD 1s

General data
Dimensions W/H/D Installation depth without extension module Installation depth with extension module Degree of protection Front Back Weight IP52 IP30 400 g 96 x 96 x 82 mm 60 mm 80 mm

13-1

PHOENIX CONTACT

104413_en_00

Technical data

Electrical isolation
Rated insulation voltage < 300 V AC (L/N) surge voltage category III

300 V AC ... 600 V AC surge voltage category II


Measuring instrument input/measuring instrument power supply (measuring instrument IN/measuring instrument POW) Measuring instrument input/extension module (measuring instrument IN/extension module) Measuring instrument power supply/extension module (measuring instrument POW/extension module) Test voltage Pollution degree Safe isolation (EN 61010-1) See extension module See extension module 3.5 kV AC (50 Hz, 1 min.) safe isolation 2

Connection data
Conductor cross section (current) Conductor cross section (voltage and other) Connection method Tightening torque 0.5 mm ... 6 mm 0.5 mm ... 2.5 mm Screw connection 0.4 Nm

Ambient conditions
Ambient temperature (operation) Ambient temperature (storage/transport) Permissible humidity (operation) -10C ... 55C (14F ... 131F) -20C ... +85C (-4F ... 185F) 95%

Conformance/approvals
Conformance CE-compliant

Conformance with EMC Directive 2004/108/EC


Immunity to electrostatic discharge according to Immunity to high-frequency electromagnetic fields according to Immunity to electrical fast transients/burst according to Immunity to surge voltages according to Immunity to power frequency magnetic fields according to Immunity to voltage dips, short-term interruptions and voltage fluctuations Wired and radiated noise emission according to IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-8 IEC 61000-4-11 EN 55011 Class B

Conformance with low-voltage directive 2006/95/EC


Electrical safety for electrical equipment for measurement, control, regulation, and laboratory use EN 61010-1

104413_en_00

PHOENIX CONTACT

13-2

EEM-MA600

13-3

PHOENIX CONTACT

104413_en_00

A Specifications according to IEC 61557-12


Table A-1 Feature type
Features for evaluating power quality (if function is available) PMD classification Temperature Humidity + height Real power or real energy accuracy class (if function is available)

PMD features Examples of possible characteristics


SD K55 0.5

Additional features
-

Table A-2 Function

Functional features Symbols Measuring range Function-related accuracy class in accordance with IEC 61557-12
0.5 1 1 0.5 1 0.5 0.02 0.2

Additional features

Total real power Total reactive power (arithmetic or vectorial) Total apparent power (arithmetic or vectorial) Total real energy Total reactive energy (arithmetic or vectorial) Total apparent energy (arithmetic or vectorial) Frequency Phase current

Pa QA, QV SA, SV Ea ErA, ErV EapA, EapV f I

0 ... 99999999 kW/h 0 ... 99999999 kVar/h 0 ... 99999999 kW/h 45 .. 65 Hz 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase

-90 ... +90 0.02 ... 1.2 In with PF = 0.5 L or 0.8 C 0.1 ... 1.2 In with SinPhi = 0.5 L or 0.5 C 10 ... 110% of In (In = 1 or 5 A depending on current transformer) 10 ... 110% of In (In = 1 or 5 A depending on current transformer) for PF 0.5 ... 1 -

Neutral conductor current

IN, INc

0.2

Voltage Power factor (arithmetic or vectorial) Flicker (short-term, long-term) Voltage dips Excessive voltage

U PFA, PFV Pst, Plt Udip Uswl Utr

0.2 0.5 0.2 or 0.5 0.2 or 0.5 0.5 1 1

Voltage interrupts Voltage asymmetry in terms of amplitude Voltage asymmetry in terms of phase and amplitude Voltage harmonics Voltage THD (based on ground)

Uint Unba Unb Uh THDu

104413_en_00

PHOENIX CONTACT

A-1

EEM-MA600 Table A-2 Function Functional features (...) Symbols Measuring range Function-related accuracy class in accordance with IEC 61557-12
1 1 -

Additional features

Voltage THD (based on harmonic) Current harmonic Current THD (based on ground) Current THD (based on harmonic) Mains signal voltage

THD-Ru Ih THDi THD-Ri Msv

0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer -

Table A-3 Function

Functional features for evaluating mains quality Symbols Measuring range Function-related accuracy class in accordance with IEC 61557-12
0.02 0.2 0.5 0.2 0.2 or 0.5 0.2 or 0.5 0.5 1 1 -

Additional features

Frequency Phase current Neutral conductor current Voltage Flicker (short-term, long-term) Voltage dips Excessive voltage Voltage interrupts Voltage asymmetry in terms of amplitude Voltage asymmetry in terms of phase and amplitude Voltage harmonics Current harmonic Mains signal voltage

f I In, Inc U Pst, Plt Udip Uswl Uint Unba Unb Uh Ih Msv

45 ... 65 Hz 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer -

A-2

PHOENIX CONTACT

104413_en_00

B Abbreviations
1BL 2BL 3BL 3NBL 4BL 4NBL AUX AVG bACLIt Ct Ct In EAEA+ ERER+ ES HOUr ISYS MAX MAX PMAX P+ MAX QMAX Q+ MAX S nEt PF Single-phase network, 2-wire with 1 current transformer Two-phase network, 2-wire with 1 current transformer Three-phase network with symmetrical load, 3-wire with 1 current transformer Three-phase network with asymmetrical load, 3-wire with 2 or 3 current transformers Three-phase network with symmetrical load, 4-wire with 1 current transformer Three-phase network with asymmetrical load, 4-wire with 3 current transformers Supply voltage Average values Backlighting Current transformer Current transformer for neutral conductor Negative real energy (-kWh) Positive real energy (+kWh) Negative reactive energy (-kvarh) Positive reactive energy (+kvarh) Apparent energy (-kVAh) Hour counter Average current value (I1+I2+I3)/3 Maximum values Maximum value of negative real power within the measuring time Maximum value of positive real power within the measuring time Maximum value of negative reactive power within the measuring time Maximum value of positive reactive power within the measuring time Maximum value of the apparent power within the measuring time Network type Power factor

104413_en_00

PHOENIX CONTACT

B-1

EEM-MA600 rSET SErI SOFt THD I THD In THD U THD V tIME 4I tIME F tIME P/Q/S tIME U TRMS Ut Ut PR Ut SE USYS VSYS Reset Serial number Software version Total harmonic distortion of currents Total harmonic distortion of neutral conductor current Total harmonic distortion of conductor voltages (1-2/2-3/3-1) Total harmonic distortion of conductor voltages against N (1/2/3) Measuring time to determine the average and maximum current values Measuring time to determine the average and maximum frequency values Measuring time to determine the average and maximum power values Measuring time to determine the average and maximum voltage values True r.m.s. value measurement (True Root Mean Square) Voltage transducer Voltage transducer primary side Voltage transducer secondary side Average value of the phase/phase conductor voltages (U12 + U23 + U31)/3 Average value of the phase/N conductor voltages (V1 + V2 + V3)/3 Hour counter

B-2

PHOENIX CONTACT