Vous êtes sur la page 1sur 3

Isolated switch amplifier

KFD2-SR2-Ex1.W

Connection
Input I EEx ia IIC Switch S3 in position I

1-channel Control circuit EEx ia IIC Reversible mode of operation 1 relay output with 1 changeover contact EMC acc. to NAMUR NE 21 LB/SC monitoring LB/SC collective error message via Power Rail Up to SIL2 acc. to IEC 61508

400 R 2 k 10 k

Switch S3 in position I
310 k

1+

without SC without LB, SC


1+ 1+

Switch S3 in position I

2+

33-

Switch S3 in position II

2+

3-

KFD2-SR2-Ex1.W
Function
The transformer isolated barrier transfers digital signals from the hazardous area. Sensors per EN 60947-5-6 (NAMUR) and mechanical contacts may be used as alarms. Control circuits are monitored for lead breakage (LB) and short circuit (SC). The external faults are indicated according to NAMUR NE44 by a red flashing LED. For type KFD2-SR2-Ex1.W, an LB/SC collective error message is in addition transferred through the Power Rail to the power feed module. The intrinsically safe input is per EN 50020 safely isolated from the output and the power supply. The relay output is in accordance with IEC 61140 safely isolated from the power supply.
I S1 &

LB SC II S3

red
+ -

green yellow

+ 7 8 9 14 15

Output

Power supply

Power LB/SC Rail collective error message only KFD2-SR2-Ex1.W

Composition
Front view Removable terminal blue

LED yellow: Relay output


Release date 2007-07-19 14:09 Date of issue 2007-07-20 132958_ENG.xml
1

1 4

2 5

3 6

LED green: Power supply

LED red: LB/SC

OUT CHK PWR

S1 S3

Switch S1 (Mode of operation)

Switch S2 (no functions)

7 10 13

8 11 14

9 12 15

Switch S3 (LB/SC-monitoring)

Removable terminals green

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Safe area

Hazardous area

1+

3-

Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com

1 2 3

Technical data

KFD2-SR2-Ex1.W

Supply Connection Rated voltage Ripple Rated current Power loss Power consumption Input Connection Rated values Open-circuit voltage/short-circuit current Switching point/Switching hysteresis Line fault detection Pulse/Pause ratio Output Connection Output Contact loading Minimum switch current Energized/de-energized delay Mechanical life Transfer characteristics Switching frequency Electrical isolation Output/power supply Directive conformity Electromagnetic compatibility Directive 89/336/EC Low voltage Directive 73/23/EEC Conformity Electromagnetic compatibility Protection degree Protection against electric shock Ambient conditions Ambient temperature Mechanical specifications Protection degree Mass Dimensions Data for application in conjunction with hazardous areas EC-Type Examination Certificate Group, category, type of protection Input Voltage
Release date 2007-07-19 14:09 Date of issue 2007-07-20 132958_ENG.xml

Power Rail or terminals 14+, 1520 ... 30 V DC 10 % 30 mA 0.7 W < 0.9 W terminals 1+, 2+, 3acc. to EN 60947-5-6 (NAMUR) approx. 8 V DC / approx. 8 mA 1.2 ... 2.1 mA / approx. 0.2 mA breakage I 0.1 mA , short-circuit I > 6 mA 20 ms / 20 ms terminals 7, 8, 9 signal ; relay 253 V AC / 2 A / cos > 0.7; 126.5 V AC / 4 A / cos > 0.7; 40 V DC / 2 A resistive load 2 mA / 24 V DC approx. 20 ms / approx. 20 ms 107 switching cycles < 10 Hz reinforced insulation acc. to IEC 61140, rated insulation voltage 300 Veff

EN 61326 IEC 62103 NE 21 IEC 60529 IEC 61140 -20 ... 60 C (253 ... 333 K) IP20 approx. 150 g 20 x 119 x 115 mm (0.8 x 4.6 x 4.5 in)

PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] EEx ia IIC 10.5 V 13 mA 34 mW (linear characteristic) 253 V AC / 125 V DC (Attention! Um is no rated voltage.) IIA 75 F 1H IIB 16.8 F 840 mH IIC 2.41 F 210 mH

Uo Io Po

Current Power Supply

Safety maximum voltage Um Type of protection [EEx ia and EEx ib] Explosion group External capacitance External inductance Output Contact loading Safety maximum voltage Um Statement of conformity Group, category, type of protection Input Voltage Current Power Uo Io Po

253 V AC / 2 A / cos > 0.7; 126.5 V AC / 4 A / cos > 0.7; 40 V DC / 2 A resistive load 253 V AC (Attention! The rated voltage can be lower.) Pepperl+Fuchs starting from february 2005 II (3)G (EEx nL) IIC X [circuit(s) in zone 2] [EEx nL] IIC 10.5 V 13 mA 34 mW (linear characteristic)

Type of protection [EEx nL]


Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com

Technical data
Explosion group External capacitance External inductance Output Contact loading Statement of conformity Group, category, type of protection, temperature classification Output Contact loading Electrical isolation Input/output Input/power supply Directive conformity Directive 94/9 EC Entity parameter FM control drawing Suitable for installation in division 2 Connection Input Voltage Current Safety parameter Certification number CSA control drawing Connection Input Voltage Current General information Supplementary information VOC ISC 12.9 V 19.8 mA LR 36087-19 No. 116-0047 terminals 1, 3; 2, 3 VOC It 12.9 V 19.8 mA No. 116-0035 yes terminals 1, 3; 2, 3 EN 50014, EN 50020, EN 50021 safe electrical isolation acc. to EN 50020, voltage peak value 375 V safe electrical isolation acc. to EN 50020, voltage peak value 375 V 50 V AC/4 A/cos > 0.7; 40 V DC/2 A resistive load IIA 75 F 1H IIB 16.8 F 840 mH IIC 2.41 F 210 mH

KFD2-SR2-Ex1.W

253 V AC / 2 A / cos > 0.7; 126.5 V AC / 4 A / cos > 0.7; 40 V DC / 2 A resistive load TV 99 ATEX 1493 X , observe statement of conformity II 3G EEx nAC IIC T4 [device in zone 2]

EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity and instructions have to be observed. For information see www.pepperl-fuchs.com.

Accessories
Power feed modules KFD2-EB2... The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module can supply up to 100 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical contact uses the Power Rail to transmit collective error messages. Power Rail UPR-03 The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To make electrical contact, the devices are simply engaged. The Power Rail must not be fed via the device terminals of the individual devices!

Release date 2007-07-19 14:09 Date of issue 2007-07-20 132958_ENG.xml

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com