Vous êtes sur la page 1sur 18

THE RELAY SPECIALISTS

relay monitoring systems pty ltd

www.rmpl.com.au

2V73 High Impedance Differential Relay

2V73 High Impedance Differential Relay


The 2V73 relay provides high speed differential protection for various items of power system plant including generators, busbars, motors & the individual windings of power transformers. It is also suitable for restricted earth fault protection applications.

2V73 High Impedance Differential Relay


The relay measuring element is basically an attracted armature unit of simple & rugged construction powered from a bridge rectifier. Relay stability can be set in steps (25-115V in 15V steps or 25-325V in 50V steps), by using the front panel mounted selector switch. A capacitor is connected in series with the operating coil to make the relay insensitive to the DC component of fault current.

External Fault
A B C D No current through relay

10000A

5A

9A

6A

20A

F1 15 kA 2500A 4500A 3000A 5000A

EXTERNAL FAULT of 15 kA RELAY CURRENT = 5 + 9 + 6 - 20 = 0A

External Fault Assuming CT Not Saturated

10.2A

10.2A

10.2A

30.6A

External Fault Causing CT Saturation

If CT saturation occurs it is most likely to affect CT with heaviest loading. Unbalance current caused by CT saturation will flow through secy winding of saturated CT and through relay. To obtain a relay operating voltage in excess of the resultant voltage the relay is required to be a HIGH IMPEDANCE. Note this is a relative term i.e. high impedance relative to impedance of saturated CT path

Stability Setting For CT Saturation Condition

30.6A 10.2A 10.2A 10.2A


RL 2 ohms 82.6V RCT 0.7 Ohm

Internal BUS Fault


F2 15 kA
A B C D 30A through relay

5A

9A

6A

10A

2500A

4500A

3000A

5000A

INTERNAL FAULT of 15 kA Relay Current = 5 + 9 + 6 + 10 = 30A

2V73 Operating Current


The primary operating current is given by: I op = n ( IR + N I ) IR = Relay operating current & Metrosil current at setting voltage as per the table below. I = CT magnetizing current at setting voltage (A) n = CT turns ratio N = Number of connected CTs The operating currents shown in the following tables are for both 3 inch & 6 inch Metrosils connected to the 2V73 as per the wiring diagram. Range A (Volts) Nominal (mA) Limits (mA) 25 15 13 to 16 75 15 13 to 17 125 15 13 to 17 175 15 13 to 20 225 17 13 to 27 275 21 15 to 39 325 29 18 to 61

2V73 Operating Current

Range B (Volts) Nominal (mA) Limits (mA)

25 14 13 to 16

40 14 13 to 16

55 14 13 to 16

70 14 13 to 17

85 14 13 to 17

100 14 13 to 17

115 14 13 to 17

Should the natural effective operating current after applying the above formula be lower that desired, it can be raised to the required level by adding a shunt resistor across the differential relay input circuit.

2V73 BUS Protection (Single Phase Representation)

8 10 5
P1 P2

Flag auxiliary Flag auxiliary Flag reset voltage free contact

Magnetic flag option only

Vs

12 14

22 24
P1 P2 L1 L2 L3 N

Trip output 1

26 28 Trip output 2

2V73 Restricted Earth Fault Application

P1

P2

8 10

Flag auxiliary Flag auxiliary Flag reset voltage free contact

P1 P2

5 6

Magnetic flag option only

Vs

12 14

22 24

Trip output 1

26 28 Trip output 2

2V73 Metrosil

An external Metrosil unit having a non-linear resistance characteristic is required for each phase element to limit the peak voltage appearing across the secondary differential circuits under internal fault conditions.

1M123 BUS Bar Protection Rack

3 x 2V73 1 x 2V75 1 x 2HSM 1 x 4M800

Single phase high impedance differential relays 3 phase Metrosil module High speed multi trip relay 4U 19 inch sub rack frame

2V73 Metrosil Selection


Refer 2V75 Metrosil Module

Type 6 3 6 1 3 3 3 1

Specification 600A/S3/I/S887 600A/S1/S887 300A/S3/I/S3063 300A/S1/S646

Rated Energy 33kJ 33kJ 8kJ 8kJ

Part No. 2105C58001 2105C58002 2105C58006 2105C58004

Customer Generated Ordering Code


Generate the required ordering code as follows: General Type Order Code 1 2 3 e.g. 2V73 BAA

2V73
1 A B 2 A B 3 A B C

SETTING RANGE 25-325V AC in 50V steps 25-115V AC in 15V steps RATED FREQUENCY 50 Hz 60 Hz FLAG TRIP INDICATION Mechanical flag Magnetic flag Magnetic flag no flag auxiliary required 24 to 150V DC auxiliary 140 to 300 V DC auxiliary

2V73 Additional Information


Technical Bulletin User Guide Software downloads Auto Cad Mounting Drawings Price & Availability

www.rmspl.com.au/2V73.htm
Test Manuals

www.rmspl.com.au/search.asp
Other Products

www.rmspl.com.au/Products.htm

Vous aimerez peut-être aussi