SECTION 2 CEILING SOLUTIONS

CONTENTS Performance tables BORAL SUPRACEIL Concealed Ceiling Systems BORAL SUPRACEIL Close - Fit Concealed Ceiling Systems

2.2 2.3 2.11 2.13 2.14 2.15 2.16 2.18 2.19

Installation requirements - Boarding ceilings - Screw xing of plasterboard - Light xings support - Fire ceiling penetrations BORAL ZERVEBOARD Access Panel BORAL FIRELOCKTEE Exposed Grid Ceiling System

BORAL SUPRATEE Exposed Grid Ceiling System

INTRODUCTION BORAL SUPRACEIL Concealed Ceiling Systems


BORAL SUPRACEIL Concealed Ceiling Systems are ideal for commercial, industrial and residential applications where the ceiling plenum is large and is intended to conceal air conditioning, and other M&E items. BORAL SUPRACEIL Concealed Ceiling Systems not only provide beautiful ush at ceilings but can also provide re protection and sound insulation.

BORAL SUPRACEIL Close-Fit Concealed Ceiling Systems


BORAL SUPRACEIL Close-Fit Concealed Ceilings are typically for commercial and residential applications where nished oor to ceiling heights must be maximized. The simple design allows the framing members to be xed with a simple clip directly to concrete sof ts and can also provide both standard and re rated ceiling performance.

BORAL ZERVEBOARD Access Panel


BORAL ZERVEBOARD is a readymade high quality access panel that is easily incorporated into plasterboard ceilings providing easy access to mechanical and electrical services above the ceiling.

BORAL FIRELOCKTEE Exposed Grid Ceiling System


BORAL FIRELOCKTEE Exposed Grid Ceiling System is typically used for commercial and industrial applications which require aesthetic ceiling nishes or easy access to the ceiling void above. The system consists of high quality pre-painted metal sections that form a grid when locked together into which high quality BORAL Ceiling Tiles can be installed. This system also incorporates a design feature that can allow the ceiling tiles to be secured into position during installation by using the BORAL Firelock Clip if required.

BORAL SUPRATEE Exposed Grid Ceiling System


BORAL SUPRATEE Exposed Grid Ceiling System is typically used for commercial applications which require a higher level of ceiling aesthetics. The system consists of high quality pre-painted metal sections which have a shadow-line recess that adds to the overall aesthetics of the nished ceiling. SUPRATEE sections form a grid when locked together into which high quality BORAL Ceiling Tiles can be installed.

2.1

PERFORMANCE TABLES INTRODUCTION - PERFORMANCE TABLES


CEILING DESIGN

Maximum centres shown for ceiling cross runners, main runners, hanger and brackets are based on a limiting de ection criteria of L/360 CEILING SOFFIT SYMBOLS Concrete slab sof t Timber beam sof t

Steel beam sof t EXAMPLE OF TABLES


System Reference

CC 5
Description Frame:

Ceiling sof t:

BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 800mm maximum centres BORAL Hangers at 1000mm maximum centres

Board: 2 layers 16mm BORAL FIREBLOC Insulation: None Weight: 32 (Kg/m )


60
2

FIRE RATING (minutes)


BS 476 part 22

FIRE RATING and ACOUSTIC With many years of re and acoustic testing around the world Boral have accumulated a wealth of expertise and knowledge with a wide range of system test reports. Indicates that a test report is available Indicates a prediction based on expert opinions, test reports from other similar tests or specialist calculation software like Marshall Day. Fire tests results shown in the ceiling performance tables meet the requirement of either: BS 476: part 22 1987 Methods for determination of the re resistance of non-loadbearing elements of construction or BS 476: part 23 1987 Methods of determination of the contribution of components to the re resistance of a structure. CEILING SAFETY BORAL Ceiling Systems are classed a non-traf cable ceilings and should not be walked upon by installers or other trades people. For traf cable solutions contact: BORAL Technical Support Centre

2.2

SECTION 2 - CEILING SOLUTIONS

Each BORAL ceiling system is carefully designed to maximise the engineering performance of each ceiling component.

PERFORMANCE TABLES SUPRACEIL CONCEALED CEILING SYSTEMS


System Reference

CC 1
Description Frame:

Ceiling sof t:

BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 1300mm maximum centres BORAL Hangers at 1500mm maximum centres 1 layer 9mm BORAL STANDARDCORE None 9 (Kg/m2)
0 FIRE RATING (minutes)

Board: Insulation: Weight:

System Reference

CC 2
Description Frame:

Ceiling sof t:

BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 1200mm maximum centres BORAL Hangers at 1400mm maximum centres
1 layer 12.5mm BORAL STANDARDCORE None
FIRE RATING (minutes) 0

Board: Insulation: Weight:

9 (Kg/m )
2

CC 3

System Reference Ceiling sof t:

Description Frame:

BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 900mm maximum centres BORAL Hangers at 1200mm maximum centres

Board: Insulation: Weight:

2 layers 12.5mm BORAL STANDARDCORE 100mm Rock mineral wool density 23kg/m
23 (Kg/m )
2

FIRE RATING (minutes) 30


BS 476 part 23

System Reference

CC 4
Description Frame:

Ceiling sof t:

BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 1100mm maximum centres BORAL Hangers at 1300mm maximum centres

Board: Insulation: Weight:

1 layer 12.5mm BORAL FIREBLOC 50mm Glass mineral wool density 24kg/m
15 (Kg/m2)
30
3

FIRE RATING (minutes)


BS 476 part 23

Note: Maximum centres for ceiling cross runners, main runners, hangers and brackets are based on a limiting de ection criteria of L/360 Performance values are for imperforate, jointed systems using only BORAL components and installed to the Boral Gypsum Vietnam speci cation given. Any alterations may well impair the quoted performance criteria.

2.3

PERFORMANCE TABLES SUPRACEIL CONCEALED CEILING SYSTEMS - continued


System Reference

CC 5

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 800mm maximum centres BORAL Hangers at 1000mm maximum centres Board: 2 layers 16mm BORAL FIREBLOC Insulation: None Weight: 32 (Kg/m2)
60 FIRE RATING (minutes)
BS 476 part 22

System Reference

CC 6

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL main runners at 700mm maximum centres BORAL Hangers at 900mm maximum centres Board: 3 layers 15mm BORAL FIREBLOC Insulation: None Weight: 44 (Kg/m )
2

FIRE RATING (minutes) 120


BS 476 part 23

SUPRACEIL CLOSE-FIT CONCEALED CEILING SYSTEMS


System Reference

CC 7

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL Bracket at 800mm maximum centres
Board: 1 layer 9mm BORAL STANDARDCORE

Insulation: None Weight: 9 (Kg/m )


2

FIRE RATING (minutes) 0

Note: Maximum centres for ceiling cross runners, main runners, hangers and brackets are based on a limiting de ection criteria of L/360 Performance values are for imperforate, jointed systems using only BORAL components and installed to the Boral Gypsum Vietnam speci cation given. Any alterations may well impair the quoted performance criteria.

2.4

SECTION 2 - CEILING SOLUTIONS

PERFORMANCE TABLES SUPRACEIL CLOSE-FIT CONCEALED CEILING SYSTEMS - continued


System Reference

CC 8

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL Bracket at 800mm maximum centres Board: 1 layer 12.5mm BORAL STANDARDCORE Insulation: None Weight: 11 (Kg/m )
2

FIRE RATING (minutes) 0

System Reference

CC 9

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL Bracket at 600mm maximum centres Board: 2 layers 12.5mm BORAL STANDARDCORE Insulation: 100mm Rock mineral wool density 23kg/m3 Weight: 23 (Kg/m )
2

FIRE RATING (minutes) 30


BS 476 part 23

System Reference

CC 10

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL Bracket at 800mm maximum centres Board: 1 layer 12.5mm BORAL FIREBLOC Insulation: 50mm Glass mineral wool density 24kg/m3 Weight: 15 (Kg/m2)
30 FIRE RATING (minutes)
BS 476 part 23

System Reference

CC 11

Ceiling sof t:

Description Frame: BORAL SUPRACEIL cross runners at 406mm maximum centres BORAL SUPRACEIL Bracket at 600mm maximum centres Board: 2 layers 16mm BORAL FIREBLOC Insulation: None Weight: 11 (Kg/m2)
60 FIRE RATING (minutes)
BS 476 part 22

Note: Maximum centres for ceiling cross runners, main runners, hangers and brackets are based on a limiting de ection criteria of L/360 Performance values are for imperforate, jointed systems using only BORAL components and installed to the Boral Gypsum Vietnam speci cation given. Any alterations may well impair the quoted performance criteria.

2.5

BORAL SUPRACEIL CONCEALED CEILING SYSTEM INTRODUCTION


BORAL SUPRACEIL Concealed Ceiling Systems BORAL SUPRACEIL Concealed Ceiling Systems are ideal for commercial, industrial and residential applications where the ceiling plenum is large and is intended to conceal air conditioning, and other M&E items. BORAL SUPRACEIL Concealed Ceiling Systems not only provide beautiful ush at ceilings but can also provide re protection and sound insulation. BORAL SUPRACEIL Concealed Ceiling Systems are designed with simple fast clip together components for easy installation and ceiling alignment. Each ceiling component has been specially engineered to optimise ceiling strength, rigidity and loading performance. Ceiling voids can also be varied to accommodate mechanical and electrical services and air-conditioning ducting. All services installed above the ceiling must be supported by the structure above and not by the concealed ceiling system. Performance The selection of ceiling system and boarding will depend on the performance required for re, refer to performance tables on page 2.3 to 2.4 CONCEALED CEILING SYSTEM

Safety BORAL SUPRACEIL Concealed Ceiling Systems are classed as non-traf cable ceilings and should not be walked upon by installers or other trades people. For traf cable solutions contact: BORAL Technical Support Centre

MAIN COMPONENTS
BORAL SUPRACEIL (used as main runner and cross runner) BORAL Bolt Angle BORAL Wall Angle BORAL Connect Clip BORAL Smart Connector

BORAL Hanger Wire

BORAL Fix Spring

BORAL Hook Wire

BORAL Expansion Bolt

BORAL Screws (as appropriate)

ADD COMPONENTS for re and sound performance

ADD COMPONENT for additional xing support


BORAL Cross Clip (if required)

Intumescent Acoustic Sealant

Glass Wool

2.6

SECTION 2 - CEILING SOLUTIONS

BORAL SUPRACEIL CONCEALED CEILING SYSTEM


CONCEALED CEILING DETAIL
BORAL Bolt Angle and Expansion Bolt Screw x BORAL Plasterboard as speci ed onto cross runner at and ceiling perimeter to be screw xed at 150mm centres BORAL Hanger Wire BORAL Fix Spring BORAL Hook Wire BORAL Hangers - at maximum centres as speci ed First and last hanger are to be placed no greater than 300mm in from perimeter of ceiling

BORAL Wall Angle xed at 600mm maximum centres

BORAL Smart Connector

BORAL Cross Clip

BORAL SUPRACEIL - Used as main runner at maximum centres as speci ed. Fist and last main runners are to be placed no greater than 300mm in from perimeter of ceiling

BORAL Connect Clip

BORAL SUPRACEIL- Used as cross runners at 406mm maximum centres

Note: For maximum centres of BORAL SUPRACEIL main runners, cross runners and hangers refer to performance tables on pages 2.3 and 2.4.

BORAL Smart Connector Used for joining BORAL SUPRACEIL runners together to extend in length. When used to join two SUPRACEIL cross runners, no additional xing is required. When used to join two SUPRACEIL main runners the BORAL Smart Connector must be secured to the main runners using four BORAL Wafer Head Self Tapping Screws as shown opposite. Also used for horizontal to vertical connections. Cut out sides of BORAL Smart Connector at the pre-punched slots, bend the connector to a 90o angle, insert into runners and screw x both runners to the connector. Movement control joints Movement control joints are required in ceilings at intervals not exceeding 10 metres in any direction, and where the ceiling crosses or abuts a structural movement joint. Jointing All joints should be taped and jointed as speci ed in this manual, refer to the Finishing Solutions section for details Main runner position Cross runner position

2.7

BORAL SUPRACEIL CONCEALED CEILING SYSTEM CEILING JUNCTION WITH MASONRY DETAIL
No re or acoustic requirement
BORAL Hanger

Fire and acoustic requirement

BORAL Connect Clip Maximum 300mm BORAL SUPRACEIL main runner BORAL SUPRACEIL cross runner BORAL Wall Angle Seal gaps using BORAL EASYJOINT Plasterbroad as speci ed Leave a 5-10mm gap and ll with Intumescent Acoustic Sealant Note: If ceiling only has an acoustic requiremet and no re requirement an Acrylic Sealant can be used BORAL Hanger Maximum 300mm

Maximum 300mm

BORAL SUPRACEIL main runner BORAL SUPRACEIL cross runner

Maximum 300mm

BORAL Wall Angle Seal gaps using BORAL EASYJOINT

Plasterbroad as speci ed

Leave a 5-10mm gap and ll with Intumescent Acoustic Sealant Note: If ceiling only has an acoustic requiremet and no re requirement an Acrylic Sealant can be used

CEILING JUNCTION WITH PARTITION DETAIL


No re or acoustic requirement

BORAL Hanger BORAL Connect Clip Maximum 300mm Maximum 300mm BORAL SUPRACEIL main runner BORAL SUPRACEIL cross runner BORAL Wall Angle Seal gaps using BORAL EASYJOINT Plasterbroad as speci ed

Fire and acoustic requirement

Maximum 300mm

Maximum 300mm

Plasterboard as speci ed

Leave a 5-10mm gap and ll with Intumescent Acoustic Sealant Note: If ceiling only has an acoustic requirement and no re requirement an Acrylic Sealant can be used

2.8

SECTION 2 - CEILING SOLUTIONS

BORAL SUPRACEIL CONCEALED CEILING SYSTEM


CEILING JUNCTION - 10mm DEFLECTION DETAIL
Maximum 150mm 50mm Maximum 150mm

Do not screw- x plasterboard to the 30mm x 30mm metal Angle Leave a 15mm gap and ll with Intumescent Acoustic Sealant

Do not screw- x ceiling runner or plasterboard to the 30mm x 30mm metal Angle Leave a 15mm gap and ll with Intumescent Acoustic Sealant

CEILING RECESS DETAIL at right angles to cross runner


BORAL Hanger Maximum 150mm Maximum 150mm BORAL Hanger

Plasterbroad as speci ed

BORAL Wall Angel screw xed onto cross and vertical runners using BORAL Wafer Head Self Tapping Screws BORAL SUPRACEIL used as a vertical brace, screw- x to top and bottom cross runners

BORAL SUPRACEIL main runner BORAL SUPRACEIL cross runner

BORAL Wall Angel screw xed onto cross and vertical runners using BORAL Wafer Head Self Tapping Screws

BORAL SUPRACEIL cross runner and vertical runner connected together using BORAL Smart Connector, Screw xed into runners using BORAL Wafer Head Self Tapping Screws

CEILING RECESS DETAIL parallel to main runner

BORAL Hanger Maximum 150mm BORAL SUPRACEIL main runner BORAL Hanger

Plasterbroad as speci ed BORAL SUPRACEIL used as a vertical brace, screw- x to top and bottom main runners

Maximum 150mm

BORAL SUPRACEIL main runner

BORAL SUPRACEIL used as horizontal runners. The BORAL Connecting Clips must be screw xed to the BORAL SUPRACEIL vertical braces as shown. BORAL SUPRACEIL cross runner

BORAL Wall Angle

2.9

BORAL SUPRACEIL CONCEALED CEILING SYSTEM CEILING OPENING DETAIL


Ceiling opening must be supported on all sides as shown below. Each hanger should not be more than 150mm away from the opening edge

BORAL Hanger Max 150 mm BORAL Connect Clip BORAL SUPRACEIL main runner

BORAL Cross Clip Max 150mm

Additional BORAL SUPRACEIL main runner to support ceiling opening

Additional BORAL SUPRACEIL cross runner to support ceiling opening BORAL SUPRACEIL cross runner

MOVEMENT CONTROL JOINT DETAIL parallel to cross runner


BORAL Connect Clip BORAL Hanger 60 x 60mm rock mineral wool batt to maintain re integrity

BORAL SUPRACEIL main runner BORAL SUPRACEIL cross runner

Plasterbroad as speci ed

12.5mm

BORAL Movement Control Bead

MOVEMENT CONTROL JOINT DETAIL at right angles to cross runner


BORAL Hanger

BORAL SUPRACEIL main runner 100mm BORAL SUPRACEIL cross runner

60 x 100mm rock mineral wool batt to maintain re integrity

Plasterboard as speci ed

12.5mm

BORAL Movement Control Bead

2.10

SECTION 2 - CEILING SOLUTIONS

BORAL SUPRACEIL CLOSE-FIT CONCEALED CEILING SYSTEM INTRODUCTION


BORAL SUPRACEIL Close-Fit Concealed Ceiling Systems BORAL SUPRACEIL Close-Fit Concealed Ceilings are typically for commercial and residential applications where nished oor to ceiling heights must be maximized. The simple design allows the framing members to be xed with a simple clip directly to concrete sof ts concrete sof t allowing a cavity width between sof t and back of plasterboard ranging from 20mm to 70mm. This system also lends itself to overboarding existing cement render and plaster ceilings where improved aesthetics or acoustic performance is required. For larger ceiling voids use BORAL SUPRACEIL Concealed Ceiling System. BORAL SUPRACEIL Close-Fit Concealed Ceiling Systems are compatible with other BORAL systems providing a ush nish when taped and jointed and are suitable for direct decoration or textured nishes. Performance The selection of the ceiling system and boarding will depend on the performance required for re resistance, refer to performance tables on page 2.4 to 2.5

BORAL Wall Angle BORAL Close-Fit Bracket BORAL SUPRACEIL main runner

Safety

BORAL SUPRACEIL Close-Fit Concealed Ceiling Systems are classed as non-traf cable ceilings and should not be walked upon by installers or other trades people. For traf cable solutions contact: BORAL Technical Support Centre

MAIN COMPONENTS
BORAL SUPRACEIL (used as main runner and cross runner) BORAL Wall Angle BORAL Smart Connector BORAL Screws (as appropriate)

BORAL Expansion Bolt

BORAL Close-Fit Bracket

BORAL Close-Fit Bracket Washer

ADD COMPONENTS for re and sound performance


Intumescent Acoustic Sealant Glass Wool

ADD COMPONENT for additional xing support


BORAL Cross Clip (if required)

2.11

BORAL SUPRACEIL CLOSE-FIT CONCEALED CEILING SYSTEM CLOSE-FIT CONCEALED CEILING DETAIL

Concrete sof t BORAL SUPRACEIL used as cross runners at 406mm maximum centre

BORAL Wall Angle xed at 600mm maximum centres. Screw x BORAL plasterboards onto ceiling runners at 230mm centres in the eld of the board. Cut ends of boards and ceiling perimeter to be screw xed at 150mm centres.

BORAL Close-Fit Bracket centres


Board thickness 12.5mm plasterboard single layer 15mm plasterboard single layer All double layers boarding Maximum (mm) 800 800 600

Movement control joints Movement control joints are required in ceilings at intervals not exceeding 10 metres in any direction, and where the ceiling crosses or abuts a structural movement joint. MOVEMENT CONTROL JOINT DETAIL parallel to cross runner
BORAL Expansion Fixing 60x60mm rock mineral wool batt to maintain re integrity

MOVEMENT CONTROL JOINT DETAIL at right to cross runner


60x60mm rock mineral wool batt to maintain re integrity

BORAL Close-Fit Bracket Washer BORAL Close-Fit Bracket BORAL SUPRACEIL cross runner Plasterboard as speci ed 12.5mm BORAL Movement Control Bead Plasterboard as speci ed 12.5mm BORAL Movement Control Bead 50mm

Jointing All joints should be taped and jointed as speci ed in this manual, refer to the Finishing Solutions section for details

2.12

SECTION 2 - CEILING SOLUTIONS

BORAL Close-Fit Bracket xed to sof t using the BORAL Close-Fit Bracket Washer and BORAL Expansion Bolt

INSTALLATION REQUIREMENTS BOARDING - SINGLE LAYER OF PLASTERBOARD

All plasterboard ends Supported by BORAL SUPRACEIL Cross runners

BORAL SUPRACEIL Cross runners

BORAL Wall Angle

BOARDING-DOUBLE LAYERS OF PLASTERBOARD


Boards cut to stagger joints between layers

All plasterboard ends supported by BORAL SUPRACEIL cross runners on both layers

BORAL Wall Angle

2.13

INSTALLATION REQUIREMENTS SCREW FIXING OF PLASTERBOARD

Screw- x cut ends of boards at 150mm centres Screw- x boards to BORAL SUPRACEIL cross runners at 230mm centres

Screw- x boards to BORAL Wall Angle 150mm centres

BORAL Plasterboards are screw xed using BORAL Plasterboard Screws at 230mm centres in eld of board and at 150mm centres around perimeter of ceiling and at cut ends of boards Installing screws Drive screws squarely through plasterboard and into the framing until screw head is just recessed below the plasterboard surface. Position screws: At least 10mm in from paperbound edges of plasterboard At least 13mm in from cut edges of plasterboard At least 3mm in from the edges of metal framing. For recommended screw length see table opposite.
Recommended screw lengths
Number of board layers Single layer Plasterboard thickness mm 9 12.5 15.0 19 9+9 12.5 + 12.5 15.0 + 15.0 12.5 + 18.0 15.0 + 15.0 + 15.0 Minimum Screw length mmm 25 25 32 38 32 38 44 51 60

Double layers Triple layers

2.14

SECTION SECTION 2 - CEILING 2 - CEILING SOLUTIONS SOLUTIONS

INSTALLATION REQUIREMENTS
FIXING SUPPORT DETAIL Using BORAL SUPRACEIL together with BORAL Cross Clips allow easy installation of extra supports needed for supporting lighting panels and lighting xtures
Spring toggle xing BORAL SUPRACEIL Cross runners BORAL SUPRACEIL extra supports

BORAL Cross Clip Light Box Plasterboard as speci ed

Alternative
Timber secured into runner with screw xings both sides Timber insert BORAL SUPRACEIL Cross runners

Light

Light Box

CEILING PENETRATIONS-FIRE DETAIL Cable penetration detail


Cable Fill with Intumescent Acoustic Sealant
Metal pipe

Fire sprinkler penetration

10mm max

Fill with an Expanding Intumescent Acoustic Sealant

Metal pipe penetration detail

Plastic pipe penetration detail


Ceilling frame Fill with Intumescent Acoustic Sealant 10mm max

Fill with Intumescent Acoustic Sealant


Metal pipe

Metal pipe

Fire Collar

2.15

BORAL ZERVEBOARD ACCESS PANEL INTRODUCTION

Pane

Frame

Type and size of ZerveBOARD


(all are applicable to 9mm plasterboard ceilings) Type ZERVEBOARD STANDARDCORE ZERVEBOARD MOISTBLOC Pane Size (Width x Length) 300 x 300mm 450 x 450mm 600 x 600mm 300 x 300mm 450 x 450mm 600 x 600mm Frame Size (Width x Length) 500 x 500mm 650 x 650mm 800 x 800mm 500 x 500mm 650 x 650mm 800 x 800mm

2.16

SECTION 2 - CEILING SOLUTIONS

INSTALLATION REQUIREMENTS ZERVEBOARD ACCESS OPENING


Ceiling opening must be supported on all sides as shown below. Each hanger should not be more than 150mm away from the opening edge

BORAL Hanger

Max 150 mm

BORAL Connect Clip

BORAL SUPRACEIL main runner

BORAL Cross Clip


Max 150mm

BORAL SUPRACEIL cross runner Additional BORAL SUPRACEIL main runner to support ceiling opening

ZERVEBOARD FRAME ATTACHED TO SUPRACEIL RUNNERS

ZERVEBOARD Pane

ZERVEBOARD frame screw xed to BORAL SUPRACEIL Ceilling runners at 100mm maximum centres

Plasterboad

2.17

BORAL FIRELOCKTEE EXPOSED GRID CEILING SYSTEM INTRODUCTION

BORAL FIRELOCKTEE Exposed Grid Ceiling System is typically used for commercial and industrial applications which require aesthetic ceiling nishes or easy access to the ceiling void above. The system consists of high quality pre-painted metal sections that form a grid when easily locked together into which high quality BORAL Ceiling Tiles can be installed. The system is suspended from sof ts by using the BORAL hanger system which incorporates the BORAL Fix Spring for easy adjustments to ceiling atness during installation. This system also incorporates a design feature that can allow the ceiling tiles to be secured into position during installation by using the BORAL Locking Clip if required. Performance The selection of BORAL Ceiling Tiles will depend on the aesthetics requirement, ease of cleaning and if sound absorption performance is required. Due to the extensive range of BORAL Ceiling Tiles and regular introduction of new aesthetic designs contact BORAL Technical Support Centre for further information. Safety BORAL FIRELOCKTEE Exposed Grid Ceiling System is classed as a nontraf cable ceiling and should not be walked upon by installers or other trades people. For traf cable solutions contact: BORAL Technical Support Centre MAIN COMPONENTS
BORAL FIRELOCKTEE Wall Angle BORAL FIRELOCKTEE Main Runner BORAL FIRELOCKTEE Long Cross Runner 1220mm BORAL FIRELOCKTEE Short Cross Runner 610mm

BORAL Bolt Angle

BORAL Expansion Bolt

BORAL Hanger Wire

BORAL Fix Spring

BORAL Locking Clip

2.18

SECTION 2 - CEILING SOLUTIONS SECTION 2 - CEILING SOLUTIONS

BORAL FIRELOCKTEE Exposed Grid Ceiling System

BORAL SUPRATEE EXPOSED GRID CEILING SYSTEM


INTRODUCTION BORAL SUPRATEE Exposed Grid Ceiling System BORAL SUPRATEE Exposed Grid Ceiling System is typically used for commercial applications which require a higher level of ceiling aesthetics. The system consists of high quality pre-painted metal sections which have a shadow-line recess that adds to the overall aesthetics of the nished ceiling. SUPRATEE sections form a grid when locked together into which high quality BORAL Ceiling Tiles can be installed. The system is suspended from sof ts by using the BORAL hanger system which incorporates the BORAL Fix Spring for easy adjustments to ceiling atness during installation. Performance The selection of BORAL Ceiling Tiles will depend on the aesthetics requirement, ease of cleaning and if sound absorption performance is required. Due to the extensive range of BORAL Ceiling Tiles and regular introduction of new aesthetic designs contact BORAL Technical Support Centre for further information. Safety BORAL SUPRATEE Exposed Grid Ceiling System is classed as a nontraf cable ceiling and should not be walked upon by installers or other trades people. For traf cable solutions contact: BORAL Technical Support Centre

MAIN COMPONENTS

BORAL SUPRATEE Wall Angle

BORAL SUPRATEE Main Runner

BORAL SUPRATEE Long Cross Runner 1220mm

BORAL SUPRATEE Short Cross Runner 610mm

BORAL Bolt Angle

BORAL Expansion Bolt

BORAL Hanger Wire

BORAL Fix Spring

2.19

INSTALLATION REQUIREMENTS GRID CEILING DETAIL


ax mm
120 cen 0mm tre ma s x

BORAL Main Runners BORAL Wall Angle xed at 600mm maximum centres

BORAL Long Cross Runners (1220mm)

BORAL Short Cross Runners (610mm) BORAL Ceiling Tile

GRID LAYOUT for 605mm x 605mm ceiling tiles

GRID LAYOUT for 605mm x 1210mm ceiling tiles

BORAL FIRELOCKTEE LOAD CAPACITY


Loading capacity tested in accordance with ASTM-C635-2004 part 8 test method based on a limiting de ection factor of L/360 Gauge Thickness (mm) 0,3 Hanger Spacing (mm) 1220 1200 1000 Main Runner Span (mm) 1220 1220 1220 Max Loading Capacity 2 Kg/m Kg/lm 13.2 10.8 14 11.5 29 23.8

System BORAL FIRELOCKTEE

BORAL SUPRATEE LOAD CAPACITY


Loading capacity tested in accordance with ASTM-C635-2004 part 8 test method based on a limiting de ection factor of L/360 Gauge Thickness (mm) Hanger Spacing (mm) 1220 BORAL SUPRATEE 0,3 915 610 Main Runner Span (mm) 1220 610 1220 610 1220 610 Max Loading Capacity 2 Kg/m Kg/lm 4.5 5.5 9 10 12 19.5 21.5 26.6 43.5

System

2.20

SECTION 2 - CEILING SOLUTIONS

0m 120 res t cen