Vous êtes sur la page 1sur 3

Qualitrol 509 Configuration Table

12/16/10 Page 1 of 3

Model Number:
Serial Number:
Manufacture Date:
Revision Level:

509-100
76389-03
10/15/08
3.080000

Input Modules:
Enabled:
Type:
Name:
Units:
Offset:
Gain:
Scaling enabled:
Scaling low:
Scaling high:
RTD temp adder:
CT gain:
CT type:
Temperature Rise:
Current Factor:
Time Constant:
CT clamp rating:

1
yes
RTD, Pt, 100 Ohms
T ACEIT
C
0
0.000000
yes
-40.000000
248.000000
1
240.000000
0
15.000000
5.000000
6
10

2
yes
CT, Temperature
T DevAT
C
0
0.000000
no
-40.000000
19960.000000
1
100.000000
0
12.000000
3.982000
6
5

3
no
T DevMT
C
0
0.000000
no
-40.000000
19960.000000
1
240.000000
0
12.000000
4.810000
6
5

4
yes
CT, Temperature
T DevBT
C
0
0.000000
no
-40.000000
19960.000000
1
500.000000
0
12.000000
4.590000
6
5

Input Modules:
Enabled:
Type:
Name:
Units:
Offset:
Gain:
Scaling enabled:
Scaling low:
Scaling high:
RTD temp adder:
CT gain:
CT type:
Temperature Rise:
Current Factor:
Time Constant:
CT clamp rating:

5
yes
Potentiometer
N TnqTR
%
0
0.000000
no
0.000000
100.000000
5
240.000000
0
15.000000
5.000000
6
10

6
yes
RTD, Pt, 100 Ohms
T AMBIE
C
0
0.000000
no
-40.000000
120.000000
6
240.000000
0
15.000000
5.000000
6
10

7
no

8
no

?
?
0
0.000000
no
0.000000
0.000000
7
-1.000000
0
15.000000
5.000000
6
0

?
?
0
0.000000
no
0.000000
0.000000
8
-1.000000
0
15.000000
5.000000
6
0

Qualitrol 509 Configuration Table

12/16/10 Page 2 of 3

Relays:
Enabled:
Controlled:
Failsafe:
Actuation direction:
Test lockout:
Exerciser:
Seasonal Setpoint:
Ambient Forecast:
Time delay:
Bank switching:
Dual Setpoint on:
Low lockout:
Setpoint:
Hysteresis:
Seasonal Setpoint:
Dual Setpoint:
Switching Bank:

1
yes
5
no
up
yes
no
no
no
no
no
no
no
90.000000
5.000000
0.000000
0.000000
0

2
yes
1
no
up
yes
no
no
no
no
no
no
no
90.000000
5.000000
0.000000
0.000000
0

3
yes
1
no
up
yes
no
no
no
no
no
no
no
100.000000
5.000000
0.000000
0.000000
0

4
yes
max 2 4
yes
up
yes
no
no
no
no
no
no
no
60.000000
5.000000
0.000000
0.000000
0

Relays:
Enabled:
Controlled:
Failsafe:
Actuation direction:
Test lockout:
Exerciser:
Seasonal Setpoint:
Ambient Forecast:
Time delay:
Bank switching:
Dual Setpoint on:
Low lockout:
Setpoint:
Hysteresis:
Seasonal Setpoint:
Dual Setpoint:
Switching Bank:

5
yes
max 2 4
no
up
yes
no
no
no
no
no
no
no
95.000000
5.000000
0.000000
0.000000
0

6
yes
max 2 4
no
up
yes
no
no
no
no
no
no
no
105.000000
5.000000
0.000000
0.000000
0

7
yes
5
no
down
yes
no
no
no
no
no
no
no
20.000000
5.000000
0.000000
0.000000
0

8
no
5
no
up
no
no
no
no
no
no
no
no
120.000000
10.000000
0.000000
0.000000
0

Current Loops:
Enabled:
Controlled:
Type:
0/1 offset:
0/1 gain:
4/20 offset:
4/20 gain:

1
yes
1
4/20
0
0.000000
0
0.000000

2
yes
2
4/20
0
0.000000
0
0.000000

3
yes
3
4/20
0
0.000000
0
0.000000

4
yes
4
4/20
0
0.000000
0
0.000000

Qualitrol 509 Configuration Table

12/16/10 Page 3 of 3

Differentials:
Enabled:
Comparison:

1
no
0

2
no
0

3
no
0

4
no
0

Advanced Winding Curves:


Current Factor:
Delta T mod 1:
Delta T mod 2:
Delta T mod 3:
Exponent:
Time constant:
Relay:
Mod 1:
Mod 2:
Mod 3:

1
0.000000
0.000000
0.000000
0.000000
0.000000
0.000000
no
2
3
4

2
0.000000
0.000000
0.000000
0.000000
0.000000
0.000000
1

3
0.000000
0.000000
0.000000
0.000000
0.000000
0.000000
1

4
0.000000
0.000000
0.000000
0.000000
0.000000
0.000000
1

Life variable A:
Life variable B:
Life consumption 1:
Life consumption 2:
Life consumption 3:
Operating Hours:

-11.269000
6328.800000
0.000000
0.000000
0.000000
172

Communications:
Installed:
Optical:
Baud:
Data bits:
Stop bits:
Parity:
Address:
Protocol:

RS232
yes

RS485 MAIN
yes
yes
9600
8
1
none
3
2

RS485x
no

19200

Heater:
Option:
Function:
Setpoint:
Hysteresis:

installed
enabled
0
5

Display:
Type:
Backlight:
Intensity:
Contrast:

character
installed
159
160

System Relay:
Seasonal Start Date:
Seasonal End Date:
Exercise Run Time:
Exercise Cycle Time:
Exceeded Hours:
Threshold Value:
Measurement Period:
Setpoint Temperature Shift:
Forecast Module:

failsafe
00/00
00/00
10
7
0
0
0
0
1

19200
8
1
none
0
0