Data sheet

MHD 535 Earth Connecting Box ECB 535


The Earth Connecting Box ECB 535 is a connection and filter module with additional lightning protectors. Whereas the Protection and Filter Module PFM 535 is designed to protect the sensor cable, the Earth Connecting Box ECB 535 is designed to protect the Processor Unit PU and therefore has to be installed in its vicinity. To cope with increased electromagnetic interferences (EMI), an Earth Connecting Box ECB 535 is inserted in the connecting cable CCA 535 after the Processor Unit PU.

Notice
An Earth Connecting Box ECB 535 must be used in all VdS-compliant installations.
In addition to the sensor cable, the connected Processor Unit PU can also be protected against voltage peaks which are coupled via the power input lines. A separate connection with a side cable entry is therefore provided.

Construction of the Earth Connecting Box ECB 535


The Earth Connecting Box ECB 535 comprises a plastic enclosure made of glass fiber reinforced polyester containing the electronic components for the protection of the Processor Unit PU. The printed circuit board features a flat-ribbon connector for the direct connection of the sensor cable, and in addition a seven-pole plug-in terminal for connecting the sensor cable via a connecting cable. Additional lightning protection elements are integrated in the Earth Connecting Box ECB 535. In addition to the sensor cable, the connected Processor Unit PU can also be protected against voltage peaks which are coupled via the supply input voltage lines. A separate connection with a side cable entry is therefore provided.

The connection of the Earth Connecting Box ECB 535 to the ground potential must have good conductivity and use connections that are as short as possible.

Figure 1: Construction of the Earth Connecting Box ECB 535

Terminal block for the connecting cable CCA 535 Flat-ribbon connector Banana connector

Overvoltage arrester for the supply voltage Cable entry sensor cable/connecting cable Cable entry supply line Processor Unit PU

SECURITON AG Alpenstrasse 20 CH - 3052 Zollikofen Switzerland

T 800452

1/4

Data sheet
Mounting the Earth Connecting Box ECB 535
Mounting position of the Earth Connecting Box ECB 535 The Earth Connecting Box ECB 535 can be mounted on the X, Y or Z axis.

Figure 2: Drilling plan of the Earth Connecting Box ECB 535

Selecting the location for the Earth Connecting Box ECB 535 The Earth Connecting Box ECB 535 should be placed immediately next to the Processor Unit PU. Fastening the Earth Connecting Box ECB 535 The Earth Connecting Box ECB 535 is fastened using 4 screws. When mounting on cement or masonry in tunnel applications, special nail anchors CMS 511 with stainless steel V4A screws (5/15x35) should be used. A minimum distance of 15 cm from parts on site (control cabinets, alcoves etc.) should be kept on the entry side of the sensor cable.

Safety Notice
For protection against humidity, the enclosed desiccant bag should be left inside the Earth Connecting Box ECB 535.

2/4 T 800452 Revision: 11/05/09 vb The product specifications contained in this document are subject to change without notice. Copyright by Securiton

MHD535

Data sheet
Technical specifications of the Earth Connecting Box ECB 535

Figure 3: Dimensioned drawing of the Earth Connecting Box ECB 535

Module Type
ECB 535

Parameter
Operating voltage Power consumption Protection class Ambient conditions Temperature range Ambient condition humidity

Values

Remark
+10 ... +20 VDC Via sensor/connecting cable of the
Processor Unit PU

approx. 0 mA (only passive elements) IP65 in accordance with IEC 529 / EN 60529
(1991)

3K5 / 3Z1 in accordance with IEC 721-3-3 / EN


60721-3-3 (1995)

-40 ... +85 C

95 % rel. hum. for a short time without condensation 70 % rel. hum. constant
Connection of connecting cable Connection of sensor cable Cable entry

2.5 mm2 maximum 8-pole

2 x seal inserts MHD 535FX Sensor cable 2 x seal inserts MHD 535SD 2 x seal inserts MHD 535HD 2 x seal inserts 8 - 5 mm Connecting cable
Material of enclosure Approval Dimensions Weight

glass-fiber reinforced polyester VdS EN54 106 x 165 x 56 mm incl. cable entries approx. 460 g

MHD535

T 800452

3/4

Data sheet
Danger
Prior to the implementation and commissioning of an installation, the technical documentation T800469 must be observed.

Connection overview
An overview of the connection of the various devices can be seen in the tables below.

Conductor
Shield pink blue white gray green yellow brown

Processor Unit PU
Tm 0 Tm 1 Tm 2 Tm 3 Tm 4 Tm 5 Tm 6 Tm 7

Earth Connecting Box ECB 535


Tm 0 Tm 1 Tm 2 Tm 3 Tm 4 Tm 5 Tm 6 Tm 7

Sensor cable module


Tm 0 Tm 1 Tm 2 Tm 3 Tm 4 Tm 5 Tm 6

Table 1: Overview of connection of connecting cable

Conductor
Shield Flat-ribbon cable

Processor Unit PU
Tm 0/1 Flat-ribbon connector

Earth Connecting Box ECB 535


Banana connector Flat-ribbon connector

Sensor cable module


Banana connector Flat-ribbon connector

Table 2: Overview of connection of sensor cable

Item numbers of cable module

Brief description
Earth Connecting Box ECB 535 Cable Terminator Module CTM 535 Connection and Filter Module CFM 535 Protection and Filter Module PFM 535 Sensor Separator Module SSM 535

Type
Rev G. Rev G. Rev G. Rev G.

Item number
MECB0000PEFGRST2 MCTM00R0PEFGRST2 MCFM00R0PEFGRST2 MPFM00R0PEFGRST2 MSSM00R0PEFGRST2

4/4 T 800452 Revision: 11/05/09 vb The product specifications contained in this document are subject to change without notice. Copyright by Securiton