Non-Hazardous Location or
DP/PA Coupler AIS or AEx nA [ia] IIC T 4 or Ex nA [ia] IIC T 4 or Nonincendive T4 (DIV 2 or ZN 2)
Terminator
any NRTL listed termination suitable for FISCO Concept R C
Um 250Vrms IM157
PA
PROFIBUS PA P+ Pintegrated termination
Sub-D connector
X1 DP
RxD/TxD-P RTS DGND P5V RxD/TxD-N Shield / PE 3 4 5 6 8 --
Screw terminal
DC 24 V
M L+ M
DP Master
PROFIBUS DP
Field device
any NRTL approved Intrinsically Safe Apparatus suitable for FISCO Concept
SIMATIC PDM
Power Supply
24 V
Um 250Vrms
1/3
Installation Notes
Installation Notes
1. Approved associated apparatus must be installed in accordance with manufacturer instructions. 2. The maximum non-hazardous area voltage must not exceed 250Vrms. 3. The intrinsically safe apparatus (Div. 1 or Zone 0 or Zone 1) an non-incendive apparatus (Div. 2 or Zone 2) as well as the terminator must meet the following requirements:
2/3
C = C line/line + 0.5 C line/screen, if both lines are floating C= C line/line + C line/screen, if the screen is connected to one line max. 30 m max. 1 km.
or
-
At each end of the trunk cable an approved line terminator with the following parameters is suitable: R = 90 ... 100 C = 0 ... 2.2 F.
One of the two allowed terminators might already be integrated in the associated apparatus (bus supply unit). The number of passive devices like transmitters, actuators, hand held terminals connected to a single bus segment is not limited due to I.S. reasons. If the above rules are respected, the inductance and capacitance of the cable need not to be considered and will not impair the intrinsic safety of the installation.
3/3