Calculation Methods Technical Data Spreadsheets Process Equipment Physical Properties Contact Us Inert gases, such as nitrogen are used on process plants for a number of purposes - such as purging equipment and inerting equipment. The most common inert gas used in industry is nitrogen, but carbon dioxide and argon are also encountered. Although usually non-toxic, inert gases can displace oxygen creating an asphyxiating atmosphere. As the common inert gases are colourless, odourless and tasteless, they can build up in the atmosphere without the victim being aware. This makes them very dangerous. This article provides some guidance on safe inert gas system design. It should be noted that this is only an introduction to the subject. The reader is advised to seek professional support when designing an inert gas system.
9/14/12
it is cheap however argon and carbon dioxide are also used. Other inert gases include the other noble gases (i.e. helium, krypton, neon and xenon) although these are only used in specialized applications. The main use of nitrogen in the process industries is to purge air or hydrocarbons from equipment before start-up, during normal operations and during shutdown. It also has a range of other specialist applications, such as in the manufacture of semiconductors, applications in the pharmaceutics and to regenerate catalysts. Argon is much less frequently used than nitrogen because it is more expensive. However in some applications, nitrogen is insufficiently inert (e.g. nitrogen can cause nitriding of metals), in which case argon can be applied. Its main use is as a shield gas for welding. For some applications, such as in the food industry, carbon dioxide is used for inerting. However, its use is limited as it is mildly corrosive when wet.
9/14/12
Mechanical Integrity
Equipment and pipework containing the inert gas should be robust and should meet best engineering practice. Flanges should be avoided as they can leak. Pipelines should be welded as far as possible. Equipment and pipework should be pressure tested before use, as well as after maintenance. Any unused pipelines should be physically disconnected from the live system. The operating pressure of the inert gas system should be kept as low as possible. In the event of a leak, this lowers the rate of gas release.
Location
The designer should consider where inert gases are likely to
w w w .my cheme.com/designguides/designing-inert-gas-sy stems.html
9/14/12
accumulate. Gases that are heavier than air (such as argon) will settle at floor level and at low points. The release of gases with similar densities to air (such as nitrogen) will tend to result in localised regions of depleted oxygen. Particular locations to consider are the following: 1. Gas storage areas Inert gases are often stored in liquefied form. Spillages of liquefied gas will rapidly vaporise, releasing large quantities of gas. Ideally, storage areas should be well ventilated and away from working areas. Access to the gas storage area should be restricted. The area should be equipped with gas monitoring and display warning signs. 2. Relief and ventilation system outlets Relief and vent lines should be clearly identified and should be piped to a safe open air location, away from working areas. 3. Rooms where inert gases are used Use of inert gases in enclosed areas should be avoided if at all possible. They should be well ventilated and equipped with oxygen monitoring equipment. Access should be restricted to trained operators, preferably not working alone. 4. General access areas General access areas (e.g. corridors) present a particular hazard as there is no means of restricting who enters. General access areas and inert gases not mix. Other useful links Gas pressure drop calculator spreadsheet Electronic steam tables spreadsheet Types of Pressure Relief Device
Ventilation
The designer needs to consider the likelihood of an escape of inert gas and whether it will be adequately dispersed. Inert gas systems which are outdoors rely on natural ventilation to dilute and disperse the gas. For indoor areas, dispersion has to be done using reliable forced ventilation. Ventilation rates to disperse the gas may need to be above that required for human comfort. The design of the ventilation system is not straightforward and the designer is advised to seek professional advice.
9/14/12
during the design, often they cannot be eliminated. The remaining hazards must be managed by operating procedures.
ADD COMMENT Please feel free to any comments to this article. We welcome any advice or technical information which may be of interest to other users of this site. All comments are reviewed before they are added to the site. Name (required) E-mail (required, but will not display) Website