Project Consultant End User EPC Contractor EPC Electrical Contractor

1x35 MW Cogeneration plant Mitcon Consultancy services Ltd. NSL Sugars Ltd. ISGEC JOHN THOMPSON IKE Electric Pvt. Ltd.

GUARANTEED TECHNICAL PARTICULARS FOR 110 KV CURRENT TRANSFORMER ( Ratio: 300/1-1-1-1-1 A ) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Type a) Highest system voltage b) Nominal system voltage Frequency Manufacturer's type designation Conforms to standards Rated primary current Rated secondary current Details of Cores Rated short time withstand current Rated dynamic withstand current Rated continuous thermal current Current ) Current density for primary winding Rated Insulation class : : : : : : : : : : : : : : Single Phase, Outdoor, Dead Tank 123 kV 110 10% kV 50Hz +_5% CT : 145/275/650 IS: 2705 300 A 1A Please refer Table - I 40 KA for 1 Second 100 KAp 1.2 pu ( Where pu = Rated 1.65 A/mm2 230 KV rms / 550 KVp

One minute power frequency withstand test voltage Dry : Wet : 1.2/50 microsecond impulse wave withstand test voltage :

230 kV rms 230 kV rms 550 kV Peak

15.

16.

The dielectric withstand values of : Insulation external and internal insulation

230 kV rms for 1 Minute

Registered Office: CG House, 6th Floor, Dr Annie Besant Road, Mumbai 400 030, India T: +91 22 2423 7777 F: +91 22 2423 7733 W: www.cgglobal.com

Crompton Greaves Limited Vacuum Interrupters & Instrument Transformer Division: Power System
D2, MIDC, Waluj, Aurangabad 431 136, Maharashtra, India T: +91 240 255 8000 F: +91 240 25 54697

Doc. No. 17. 18. 19. 20. 21. 22. 23.

: 413539192 CT1 GTP

Rev : 1 : : : : : : :

Date : 18/Nov/2011 3 KV rms 3815 mm 126 kg 10% 450 kg 10% Pedestal Mounting

Page 2 of 2

One minute power frequency Withstand voltage on secondary Min. creepage distance (mm) Weight of oil (kg) Total weight (kg) Type of Mounting Mounting size requirement (mm) Mounting holes (With Frame) Primary terminals requirement (mm)

450 x 450 x 18 mm Copper dia 30 X 80 mm

24. 25 26. 27.

General Arrangement Drawing Ambient temperature Schematic Rating Plate Drawing Cantilever Test Load

: : : :

Attached. 50 deg C Attached. 350 kG

Table - I : Details of Cores