The choice of neutral earthing for MV and HV power systems has long been a topic of heated controversy due to the fact that it is impossible to find a single compromise for the various types of power systems. Acquired experience now allows an appropriate choice to be made according to the specific constraints of each system. This chapter compares the different types of neutral earthing, distinguished by the neutral point connection and the operating technique used.
Earthing impedance
The neutral potential can be earthed by five different methods, according to type (capacitive, resistive, inductive) and the value (zero to infinity) of the impedance ZN of the connection between the neutral and earth: b ZN = : isolated neutral, i.e. no intentional earthing connection, b ZN is related to a resistance with a fairly high value, b ZN is related to a reactance, with a generally low value, b ZN is related to a compensation reactance, designed to compensate for the system capacitance, b ZN = 0: the neutral is solidly earthed.
DE57201
ZN
Ik1
Summary of neutral earthing characteristics Characteristics Damping of transient overvoltages Limitation of 50 Hz overvoltages Limitation of fault currents Continuity of service (no tripping required on first fault) Easy implementation of protection discrimination No need for qualified personnel
resistance + + + + +
reactance + + + + +
direct ++ + + +
+ good mediocre