Académique Documents
Professionnel Documents
Culture Documents
Abstract—This paper proposes a new method to determine follows. The harmonic reactive power generated by the utility
whether the utility or the customer side has more contribution source is estimated first. An equivalent impedance (or admit-
to the harmonic currents measured at the point of common tance) that absorbs that reactive power is then determined. This
coupling. The method is inspired by the observation that the
direction of harmonic reactive power, instead of active power, is impedance (or admittance) is termed as critical impedance (or
a more reliable indicator on the location of dominant harmonic admittance) (CI or CA). By comparing the CI (or CA) with the
sources. The method needs approximate impedance information known range of the combined utility and customer impedance
to operate. Mathematical analysis, simulation studies, and field (or admittance), the location of the dominant harmonic source
measurements have shown that this is a useful, reliable, and can be found. The method, therefore, takes advantage of both
practical solution for the harmonic source detection problem.
the power direction-based and the impedance-based methods.
Index Terms—Harmonic source detection, harmonics, power In this paper, the validity of the method is demonstrated with
quality. theoretical analysis. The method is also verified using computer
simulations and field test results.
I. INTRODUCTION This paper is organized as follows: Section II describes the
principle of the method, Section III presents simulation as well
(5)
(6)
Fig. 3. Determination of voltage at one point along jX .
Equation (5) can be rewritten as
them into a single index. The new index is called CI and is de-
(7) fined as
Since the reactive power absorbed by is , which is equal (12)
to according to (7), one can conclude that all reactive power
produced by is absorbed by reactance . In other words, where is the reactive power absorbed by , as shown in
is the furthest location where the reactive power output of Fig. 2. Note that CI and have the same signs. So if ,
can flow to. This location also has the lowest voltage along the which implies the utility absorbs reactive power, we can con-
“impedance line” between and . clude directly that the customer side is the dominant harmonic
It is our postulation that if is located closer to the customer source. If , the utility side generates reactive power. In
side ( ), the utility source is expected to have a larger this case, the range of needs to be compared with the absolute
magnitude since the source can “push” its reactive power output value of CI for determining the dominant source. In summary,
beyond halfway ( ) of the “impedance line.” Similarly, if for the case of , the proposed method can be imple-
or is located closer to the utility side, the customer mented as follows.
source is expected to have a large magnitude. A method to deter- 1. Calculate the utility side voltage source by using
mine the relative magnitude of the two sources can, therefore, be , where is known.
established on the basis of comparing the magnitudes of and 2. Calculate the reactive power absorbed by ,
. Mathematical analysis has shown that this postulation is , where is the phase by which leads
correct. In the following, the criterion or will .
be proven to be the necessary and sufficient condition on which 3. Calculate .
one can conclude . 4. If , the utility source absorbs reactive power, the
To prove the above postulation, let us assume customer side is the main harmonic contributor.
where . By considering (5), the new expression for can 5. If , the utility generates reactive power, the fol-
be established as lowing substeps are to be taken:
If , where is the maximum of all pos-
(8) sible values, the utility side is the main harmonic contributor.
This is because the utility side, due to its high source voltage,
The minimum value of is obtained when can “push” its generated reactive power far deep into the cus-
tomer side;
If , where is the minimum of all pos-
(9) sible values, the customer side is the main harmonic contrib-
The above equation indicates that if , all possible utor. This case implies that the customer side source “pushes”
values of will be greater than . That is, is the its reactive power deep into the utility side.
necessary condition for to hold. On the other hand, if If , no definite conclusion can
given , one will get be drawn. But our study results show that such a condition
generally implies that the utility and customer have comparable
contributions to the PCC current. As a result, the exercise to
(10)
determine precisely which side has more contribution may just
have academic significance.
Straightforwardly, the condition for the above equation to hold
is . Therefore, we have proven C. Error Analysis
(11) The practical applicability of the CI method depends on
its robustness. Since the customer impedance may have large
Since the sign of the reactive power absorbed by source and variations, our knowledge about may have large errors. The
the quantity are two important parameters for the proposed method is expected to have a good tolerance to such errors.
method, we introduce a signed fictitious impedance to combine For example, if or , a conclusion can be
674 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 19, NO. 2, APRIL 2004
(13)
(14) (17)
The above equation shows that if the utility side delivers reactive
where . Comparing (14) with those for the case power ( ), will hold. Hence, the conclusions for
of pure reactance [(1) and (2)], one can see the difference is only the capacitive impedance case are just opposite to those of the
a rotation of degrees. Therefore, we introduce the following inductive case. The second special case is . In this case,
rotation transformation matrix: the transformed reactive is equal to the active power and
has the form of
(15) (18)
LI et al.: A “CRITICAL IMPEDANCE”-BASED METHOD FOR IDENTIFYING HARMONIC SOURCES 675
TABLE I
IMPACT OF HARMONIC MAGNITUDE ON ACCURACY OF CI METHOD
D. Robustness of the Method With Respect to Accuracy of 3) The smallest IET has a value of 58%. It means that one
The last factor that may degrade the robustness of the CI can still detect the source correctly even if our knowledge
method is the error of the utility impedance . This impedance about differs from the actual (i.e., measured) value by
is used to estimate and can influence the range of . It should 58%.
be noted that first of all, the error of is generally small since 4) The first three snapshots have smaller IET than others.
the supply transformer dominates the utility impedance. Even if This is because both the utility and customer sides gen-
there are some errors in , the error can be regarded as changes erate reactive power in these cases. For the other seven
of and . Since results have shown that the method can tol- cases, the utility side generates reactive power and the
erate large impedance and source current variations, it is reason- customer side absorbs; consequently, the tolerance on
able to consider that the impact of variation is insignificant. impedance error can go as high as 258%.
5) The active power produced by the utility source is equal
IV. VERIFICATION USING FIELD MEASUREMENTS to that received by the customer source. This is because,
after the rotation transform, the power is assumed to
The proposed method is further assessed with field measure- transmit through a pure reactance of . There is no
ment data. The system, shown in Fig. 8, exhibits 5th harmonic active power consumption is the rotated case.
distortions at the metering point. Extensive investigations were 6) Further studies show that even if has an error from
conducted to determine which side is the main contributor to to , the location of the main harmonic source can
the harmonic distortion. Due to a lack of other viable harmonic still be correctly detected.
source detection techniques at the time of the project, the
This practical case further proves the robustness of the proposed
expensive impedance-based method was used. The utility and
method. It is shown that the method requires only approximate
customer impedances were determined from a series of field
harmonic impedance data and can tolerate large impedance er-
measurements when disturbances such as line and capacitor
rors. Another advantage of the method is that once we find one
switching were introduced to either side. At the utility side,
side absorbs reactive power (for example, the customer side of
eight operations were performed within several hours to find
snapshots 4 to 10), one can conclude that the main harmonic
the customer-side harmonic impedance. The calculated average
source is located at the other side immediately without exam-
5th harmonic impedance is around . Another
ining the magnitude of .
two capacitor switching operations were performed at the
customer side to find the utility side impedance , the result
is . The system was also modeled for frequency V. DISCUSSIONS
scan studies. The scanned and are found to be very
Our focus so far has been on determining which side has a
close to the measured ones. Eventually, the utility system was
larger contribution to the PCC current distortion. It is equally
identified as the main harmonic contributor with an average 5th
important to find out which source has more contribution to the
harmonic of 2160 V. The customer side source is about
PCC voltage distortion. In fact, limiting the voltage distortions
858 V. The proposed method is applied to the ten snapshots
has become more important in recent developments of harmonic
with the assumption of . The
standards. In this section, the subject of applying the proposed
calculated CI and other key parameters are listed in Table II. method to detect dominant source from the perspective of
The following conclusions can be drawn from the table. voltage distortion is discussed.
1) The CI is always negative, so the utility generates reactive The circuit for voltage distortion analysis is shown in Fig. 9.
power (after rotation of degrees) in all snapshots. The The problem here is to find the larger contributor to the voltage
harmonic source location needs to be detected by com- harmonic measured at PCC, . According to the principle
paring CI with impedance . of superposition, this is equivalent to finding which source or
2) The main harmonic source is located at the utility side has a larger magnitude. If we still assume that the utility side
since is always larger than which is about 563 . admittance is known, the utility side harmonic current
This impedance value is derived from the measured data. can be calculated from the PCC measurements. Consequently,
LI et al.: A “CRITICAL IMPEDANCE”-BASED METHOD FOR IDENTIFYING HARMONIC SOURCES 677
TABLE II
CALCULATION RESULTS OF THE TEN SNAPSHOTS
VI. CONCLUSION
Fig. 9. Equivalent circuit for voltage harmonic analysis. The widely known active power direction method for har-
monic source detection is unfounded. A new reactive power-
the reactive power absorbed by the utility current source can be based method is proposed in this paper. The method assumes
determined as that the utility side impedance and the range of the customer
impedance are approximately known. A fictitious impedance
(19) (or admittance) named CI (or CA) is calculated from voltage
and current measured at the PCC. The result is compared with
the range of the combined utility and customer impedance (or
where . Referring to (2), we can see that if ,
the utility current source receives reactive power, one can con- admittance) to determine which side is the dominant contributor
clude that the customer side has more contribution to . If to the harmonic distortion measured at the PCC. The main con-
or the utility current source generates reactive power, we tributions of this work can be summarized as follows.
need to check how much admittance will completely absorb that • Mathematical analysis has been presented to demonstrate
reactive power. Similarly, imagine the admittance is uniformly the pros and cons of the power direction-based methods.
distributed between and , follow the procedure (4)–(7) and The reactive power direction-based method is found to be
consider: technically sound and is reliable when one source absorbs
reactive power.
(20) • The reactive power-based method is expanded with the
concept of critical impedance (or admittance), which
the point where is the smallest can be determined as forms the core idea of the proposed method. Rigorous
theoretical analysis has proven that the concept presents
(21) a powerful alternative solution for the harmonic source
where can be defined as the CA. The reactive power generated detection problem.
by the utility current source will be absorbed by . It can be seen • A rotation transform is introduced to deal with general
that (21) has a similar structure as (7). By comparing with cases. This transform has greatly simplified the analysis
, we can determine the dominant harmonic contributor to and understanding of the harmonic source detection
the . distortion. In other words, the conclusions developed problem. The combination of these three contributions
in the previous sections can be applied to detect the main voltage has resulted in a useful, practical, and reasonably reliable
harmonic contributor by replacing with and with . When method for locating dominant harmonic sources in a
the conductance cannot be ignored, that is , it is power system.
easy to find • The paper has done extensive investigations on the error
characteristics of the proposed method. The method is fur-
ther checked using field measurements. All results have
shown that the method is robust and practical. It has the
potential to become a viable and easy-to-use tool for the
(22)
harmonic source detection problem.
678 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 19, NO. 2, APRIL 2004
REFERENCES Chun Li (S’99–M’01) received the B.E. and Ph.D. degrees in electrical
engineering from Tsinghua University, Beijing, China, in 1996 and 2000,
[1] T. Tanaka and H. Akagi, “A new method of harmonic power detection
respectively.
based on the instantaneous active power in three-phase circuits,” IEEE Currently, he is a Post-doctoral Fellow in the Electrical and Computer Engi-
Trans. Power Delivery, vol. 10, pp. 1737–1742, Oct. 1995.
neering Department at the University of Alberta, Edmonton, AB, Canada. His
[2] P. H. Swart, M. J. Case, and J. D. Van Wyk, “On techniques for localiza- current interests are harmonics and power quality.
tion of sources producing distortion in three-phase networks,” The Eur.
Trans. Elect. Power Eng., vol. 6, no. 6, pp. 391–396, Nov./Dec. 1996.
[3] L. Cristaldi and A. Ferrero, “Harmonic power flow analysis for the mea-
surement of the electric power quality,” IEEE Trans. Instrum. Meas., vol.
44, pp. 683–685, June 1995.
[4] W. Xu, “On the validity of the power direction method of identifying
harmonic source locations,” IEEE Power Eng. Rev., vol. 20, pp. 48–49,
Jan. 2000.
[5] A. E. Emanuel, “On the assessment of harmonic pollution,” IEEE Trans. Wilsun Xu (M’90–SM’95) received the Ph.D. degree from the University of
Power Delivery, vol. 10, pp. 1693–1698, July 1995. British Columbia, Vancouver, BC, Canada, in 1989.
[6] M. Tsukamoto, I. Kouda, Y. Natsuda, Y. Minowa, and S. Nishimura, Currently, he is a Professor with the University of Alberta, Edmonton, AB,
“Advanced method to identify harmonic characteristic between utility Canada, and chairs the Harmonics Modeling and Simulation Task Force of the
grid and harmonic current sources,” in Proc. 8th Int. Conf. Harmonics IEEE Power Engineering Society. He was an Engineer with BC Hydro, BC,
Quality Power, Athens, Greece, Oct. 1998, pp. 419–425. Canada, from 1990 to 1996. His main research interests are power quality and
[7] A. de Oliveira, J. C. de Oliveira, J. W. Resende, and M. S. Miskulin, harmonics.
“Practical approaches for AC system harmonic impedance measure-
ments,” IEEE Trans. Power Delivery, vol. 6, pp. 1721–1726, Oct. 1991.
[8] H. Yang, P. Pirotte, and A. Robert, “Assessing the harmonic emission
level from one particular customer,” in Proc. 3rd Int. Conf. Power
Quality: End-Use Applicat. Perspectives, Amsterdam, The Netherlands,
1994, B-2.08.
[9] E. Thunberg and L. Soder, “A Norton approach to distribution network
modeling for harmonic studies,” IEEE Trans. Power Delivery, vol. 14, Thavatchai Tayjasanant (S’01) received the B.Eng. degree in electrical power
pp. 272–277, Jan. 1999. engineering from Chulalongkorn University, Bangkok, Thailand, in 1994, and
[10] W. Xu and Y. Liu, “A method for determining customer and utility har- the M.Sc. degree from the University of Manchester Institute of Science and
monic contributions at the point of common coupling,” IEEE Trans. Technology (UMIST), Manchester, U.K., in 1996. He is currently pursuing the
Power Delivery, vol. 15, pp. 804–811, Apr. 2000. Ph.D. degree at the University of Alberta, Edmonton, AB, Canada.