Vous êtes sur la page 1sur 23

5-46kV TRXLPE

URD

CSA

2012.01.25

Description

Design Parameters

Options

Single conductor cable with aluminum or copper conductors,


triple extruded insulation system consisting of a thermosetting
semiconducting conductor shield, high dielectric strength
VOLTALENE TRXLPE insulation, thermosetting semiconducting
insulation shield, copper concentric neutral wires, black
encapsulating linear low-density polyethylene (LLDPE) jacket.

Conductor
Solid Class B compact or compressed concentric strand
aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Black LLDPE jacket with no stripes

Specifications
CSA

CSA C68.5

Ratings
-40C

For 90C continuous, 130C emergency, 250C short-circuit operation.

MEDIUM VOLTAGE
UTILITY

section ii.11 1

Conductor Shield
Extruded thermosetting semiconducting shield which is free
stripping from the conductor and bonded to the insulation.
Insulation
Natural high dielectric strength VOLTALENE TRXLPE insulation,
exhibiting an optimum balance of mechanical and electrical
properties, insuring resistance to treeing.
Insulation Shield
Extruded thermosetting semiconducting shield with controlled
adhesion to the insulation providing the required balance
between electrical integrity and ease of stripping.

Black PVC jacket sleeved over separator tape


No jacket
EPROTENAX (EPR) insulation
Multiplex cables
Tinned round or flat strap neutrals
Strandseal
Super smooth conductor shield
Cables made to AEIC CS8 and/or ICEA S-94-649
46kV

Installations

Metallic Shield
Solid bare copper wires, helically applied and uniformly spaced.

Conduit in Air

Direct Buried

Jacket
Black insulation sunlight resistant linear low-density
polyethylene encapsulating the neutral wires with three
extruded red stripes.

Underground Duct

Isolated in Air

Wet Locations

Dry Locations

With Messenger

Utility Primary

Prysmian Power Cables and Systems


www.prysmianusa.com
www.prysmiancanada.com

United States: 700 Industrial Drive Lexington, South Carolina 29072


Canada: 137 Commerce Drive R. R #3 Prescott, Ontario K0E1T0
1-800-845-8507 (US) 1-800-263-4405 (West-CAN) 1-800-361-1418 (East-CAN)

Product Number

URD

100% 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

5kV

Conductor

(A)

(B)

5kV 100%/133% Aluminum Single Phase Full Neutral


Q4L01ZC
2 SOLID AL
90 10-#14
6.55 12.40
Q4M1ZC
2 AWG AL
90 10-#14
6.81 12.55
Q4N1ZC
1 SOLID AL
90 13-#14
7.34 13.18
Q4O1ZC
1 AWG AL
90 13-#14
7.65 13.39
Q4P1ZC
1/0 SOLID AL
90 16-#14
8.26 14.10
Q4Q1ZC
1/0 AWG AL
90 16-#14
8.59 14.33
Q4R1ZC
2/0 AWG AL
90 13-#12
9.60 15.34
Q4S1ZC
3/0 AWG AL
90 16-#12 10.82 16.56
Q4T1ZC
4/0 AWG AL
90 20-#12 12.14 17.88
Q4U1ZC
250 MCM AL
90 23-#12 13.28 19.28
Q4V1ZC
350 MCM AL
90 33-#12 15.72 21.72
5kV 100%/133% Aluminum Three Phase One-Third Neutral
Q4LZC
2 SOLID AL
90
6-#16
6.55 12.40
Q4MZC
2 AWG AL
90
6-#16
6.81 12.55
Q4NZC
1 SOLID AL
90
7-#16
7.34 13.18
Q4OZC
1 AWG AL
90
7-#16
7.65 13.39
Q4PZC
1/0 SOLID AL
90
9-#16
8.26 14.10
Q4QZC
1/0 AWG AL
90
9-#16
8.59 14.33
Q4RZC
2/0 AWG AL
90 11-#16
9.60 15.34
Q4SZC
3/0 AWG AL
90 14-#16 10.82 16.56
Q4TZC
4/0 AWG AL
90 17-#16 12.14 17.88
Q4UZC
250 MCM AL
90 21-#16 13.28 19.28
Q4VZC
350 MCM AL
90 27-#16 15.72 21.72
Q4WZC
500 MCM AL
90 25-#14 18.80 24.79
Q4XZC
750 MCM AL
90 24-#12 23.11 29.36
Q4YZC
1000 MCM AL
90 31-#12 26.92 33.17

(C)

(D)

90C In Duct

90C Direct Buried

14.27
14.43
15.06
15.27
15.98
16.21
17.22
18.44
19.76
21.16
23.60

20.38
20.53
21.16
21.37
22.08
22.31
24.17
25.39
26.71
28.11
30.55

536
542
629
636
730
738
910
1069
1221
1475
1963

178
178
178
178
178
203
203
203
229
229
254

119
120
136
138
155
156
181
206
235
264
313

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.06

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05

169
170
193
195
219
220
251
285
324
358
423

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.06

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05

14.27
14.43
15.06
15.27
15.98
16.21
17.22
18.44
19.76
21.16
23.60
26.67
31.70
35.51

19.70
19.85
20.49
20.69
21.40
21.63
22.65
23.87
25.19
26.58
29.02
32.77
38.65
43.88

407
412
457
464
526
534
614
720
789
980
1238
1692
2489
3211

178
178
178
178
178
178
203
203
203
229
254
279
330
356

123
122
140
139
159
158
180
206
234
258
311
377
461
520

1.08
1.10
0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.22
0.16
0.11
0.09

0.15
0.15
0.15
0.14
0.14
0.14
0.13
0.13
0.12
0.12
0.11
0.11
0.11
0.10

4.03
4.05
3.39
3.41
2.65
2.67
2.17
1.71
1.40
1.14
0.87
0.58
0.39
0.30

0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04
0.04

180
180
204
204
230
230
260
292
325
349
402
451
506
543

1.10
1.12
0.88
0.90
0.71
0.73
0.59
0.48
0.40
0.35
0.28
0.23
0.19
0.17

0.34
0.34
0.33
0.30
0.32
0.31
0.30
0.29
0.28
0.27
0.25
0.22
0.18
0.15

3.55
3.58
3.33
3.36
2.61
2.63
2.14
1.69
1.38
1.13
0.87
0.58
0.39
0.30

0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04
0.04

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 2

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

100% 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

5kV

Conductor

(A)

(B)

5kV 100%/133% Copper Single Phase Full Neutral


Q4301ZC
2 SOLID CU
90 16-#14
6.55 12.40
Q4401ZC
2 AWG CU
90 16-#14
6.81 12.55
Q4501ZC
1 SOLID CU
90 13-#12
7.34 13.18
Q4601ZC
1 AWG CU
90 13-#12
7.59 13.34
Q4701ZC
1/0 SOLID CU
90 16-#12
8.26 14.10
Q4801ZC
1/0 AWG CU
90 16-#12
8.59 14.33
Q4901ZC
2/0 AWG CU
90 20-#12
9.60 15.34
Q4A01ZC
3/0 AWG CU
90 26-#12 10.82 16.56
Q4B01ZC
4/0 AWG CU
90 32-#12 12.14 17.88
5kV 100%/133% Copper Three Phase One-Third Neutral
Q4300ZC
2 SOLID CU
90
9-#16
6.55 12.40
Q4400ZC
2 AWG CU
90
9-#16
6.81 12.55
Q4500ZC
1 SOLID CU
90 11-#16
7.34 13.18
Q4600ZC
1 AWG CU
90 11-#16
7.59 13.34
Q4700ZC
1/0 SOLID CU
90 14-#16
8.26 14.10
Q4800ZC
1/0 AWG CU
90 14-#16
8.59 14.33
Q4900ZC
2/0 AWG CU
90 17-#16
9.60 15.34
Q4A00ZC
3/0 AWG CU
90 21-#16 10.82 16.56
Q4B00ZC
4/0 AWG CU
90 27-#16 12.14 17.88
Q4C00ZC
250 MCM CU
90 21-#14 13.28 19.28
Q4D00ZC
350 MCM CU
90 28-#14 15.72 21.72
Q4E00ZC
500 MCM CU
90 26-#12 18.77 24.77
Q4F00XC
750 MCM CU
90 25-#10 24.59 30.84
Q4G00XC
1000 MCM CU
90 32-#10 28.37 34.62

(C)

(D)

90C In Duct

90C Direct Buried

14.27
14.43
15.06
15.21
15.98
16.21
17.22
18.44
19.76

20.38
20.53
22.01
22.16
22.93
23.15
24.17
25.39
26.71

849
857
1050
1061
1255
1267
1527
1880
2278

178
178
178
178
203
203
203
203
229

152
153
175
176
198
200
231
262
300

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.08
0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.06

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06

215
217
245
247
277
280
317
359
407

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.08
0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.06

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06

14.27
14.43
15.06
15.21
15.98
16.21
17.22
18.44
19.76
21.16
23.60
26.64
33.17
36.96

19.70
19.85
20.49
20.64
21.40
21.63
22.65
23.87
25.19
27.26
29.70
33.59
41.20
46.41

647
655
760
771
912
923
1101
1326
1618
1943
2581
3619
5448
7112

178
178
178
178
178
178
203
203
203
229
254
279
330
381

157
158
179
180
204
205
233
265
301
331
393
464
542
588

0.66
0.67
0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.15
0.15
0.15
0.14
0.14
0.14
0.13
0.13
0.12
0.12
0.11
0.11
0.11
0.10

2.45
2.47
2.06
2.08
1.61
1.62
1.32
1.04
0.82
0.70
0.51
0.34
0.24
0.18

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04

227
228
256
256
286
287
320
353
385
408
452
494
550
603

0.69
0.70
0.56
0.57
0.46
0.47
0.39
0.33
0.29
0.26
0.22
0.19
0.16
0.13

0.34
0.34
0.33
0.32
0.31
0.31
0.29
0.28
0.26
0.25
0.21
0.17
0.14
0.11

2.41
2.43
2.03
2.05
1.59
1.60
1.31
1.03
0.81
0.70
0.50
0.34
0.24
0.18

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 3

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

8kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

8kV 100% Aluminum Single Phase Full Neutral


Q5L01ZC
2 SOLID AL
115 10-#14
6.55
Q5M01ZC
2 AWG AL
115 10-#14
6.81
Q5N01ZC
1 SOLID AL
115 13-#14
7.34
Q5O01ZC
1 AWG AL
115 13-#14
7.65
Q5P01ZC
1/0 SOLID AL
115 16-#14
8.26
Q5Q01ZC
1/0 AWG AL
115 16-#14
8.59
Q5R01ZC
2/0 AWG AL
115 13-#12
9.60
Q5S01ZC
3/0 AWG AL
115 16-#12 10.82
Q5T01ZC
4/0 AWG AL
115 20-#12 12.14
Q5U01ZC
250 MCM AL
115 23-#12 13.28
Q5V01ZC
350 MCM AL
115 33-#12 15.72
8kV 100% Aluminum Three Phase One-Third Neutral
Q5L00ZC
2 SOLID AL
115
7-#16
6.55
Q5M00ZC
2 AWG AL
115
7-#16
6.81
Q5N00ZC
1 SOLID AL
115
7-#16
7.34
Q5O00ZC
1 AWG AL
115
7-#16
7.65
Q5P00ZC
1/0 SOLID AL
115
9-#16
8.26
Q5Q00ZC
1/0 AWG AL
115
9-#16
8.59
Q5R00ZC
2/0 AWG AL
115 11-#16
9.60
Q5S00ZC
3/0 AWG AL
115 14-#16 10.82
Q5T00ZC
4/0 AWG AL
115 17-#16 12.14
Q5U00ZC
250 MCM AL
115 21-#16 13.28
Q5V00ZC
350 MCM AL
115 27-#16 15.72
Q5W00ZC
500 MCM AL
115 25-#14 18.80
Q5X00ZC
750 MCM AL
115 24-#12 23.11
Q5Y00ZC
1000 MCM AL
115 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

13.67
13.82
14.45
14.66
15.37
15.60
16.61
17.83
19.15
20.55
22.99

15.54
15.70
16.33
16.54
17.25
17.48
18.49
19.71
21.03
22.43
24.87

21.65
21.80
22.43
22.64
23.35
23.58
25.44
26.66
27.98
29.38
31.82

575
581
669
677
772
781
955
1117
1272
1528
2022

178
178
203
203
203
203
229
229
229
254
279

120
120
138
138
157
156
180
205
234
257
314

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.06
0.06

169
169
193
193
219
218
249
282
320
350
425

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.06
0.06

13.67
13.82
14.45
14.66
15.37
15.60
16.61
17.83
19.15
20.55
22.99
26.06
30.63
34.44

15.54
15.70
16.33
16.54
17.25
17.48
18.49
19.71
21.03
22.43
24.87
28.40
32.97
36.78

20.97
21.12
21.76
21.96
22.67
22.90
23.92
25.14
26.46
27.85
30.29
34.50
39.92
45.15

455
461
496
503
567
576
657
765
837
1031
1293
1784
2563
3293

178
178
178
178
203
203
203
203
229
229
254
279
330
381

123
123
140
140
160
159
181
207
235
259
312
378
461
521

1.08
1.10
0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.22
0.16
0.11
0.09

0.15
0.16
0.15
0.15
0.14
0.14
0.14
0.13
0.13
0.12
0.12
0.11
0.11
0.10

3.50
3.52
3.28
3.30
2.57
2.59
2.10
1.65
1.35
1.11
0.84
0.58
0.38
0.30

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05

178
177
202
201
229
227
256
287
320
345
397
447
501
539

1.10
1.12
0.88
0.90
0.71
0.73
0.59
0.48
0.40
0.35
0.28
0.23
0.19
0.17

0.34
0.34
0.33
0.33
0.32
0.32
0.31
0.30
0.29
0.27
0.25
0.22
0.18
0.15

3.44
3.46
3.23
3.25
2.53
2.55
2.07
1.63
1.34
1.10
0.84
0.58
0.38
0.29

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 4

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

8kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

8kV 100% Copper Single Phase Full Neutral


Q5301ZC
2 SOLID CU
115 16-#14
6.55
Q5401ZC
2 AWG CU
115 16-#14
6.81
Q5501ZC
1 SOLID CU
115 13-#12
7.34
Q5601ZC
1 AWG CU
115 13-#12
7.59
Q5701ZC
1/0 SOLID CU
115 16-#12
8.26
Q5801ZC
1/0 AWG CU
115 16-#12
8.59
Q5901ZC
2/0 AWG CU
115 20-#12
9.60
Q5A01ZC
3/0 AWG CU
115 26-#12 10.82
Q5B01ZC
4/0 AWG CU
115 32-#12 12.14
8kV 100% Copper Three Phase One-Third Neutral
Q5300ZC
2 SOLID CU
115
9-#16
6.55
Q5400ZC
2 AWG CU
115
9-#16
6.81
Q5500ZC
1 SOLID CU
115 11-#16
7.34
Q5600ZC
1 AWG CU
115 11-#16
7.59
Q5700ZC
1/0 SOLID CU
115 14-#16
8.26
Q5800ZC
1/0 AWG CU
115 14-#16
8.59
Q5900ZC
2/0 AWG CU
115 17-#16
9.60
Q5A00ZC
3/0 AWG CU
115 21-#16 10.82
Q5B00ZC
4/0 AWG CU
115 27-#16 12.14
Q5C00ZC
250 MCM CU
115 21-#14 13.28
Q5D00ZC
350 MCM CU
115 28-#14 15.72
Q5E00ZC
500 MCM CU
115 26-#12 18.77
Q5F00XC
750 MCM CU
115 25-#10 24.59
Q5G00XC
1000 MCM CU
115 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

13.67
13.82
14.45
14.61
15.37
15.60
16.61
17.83
19.15

15.54
15.70
16.33
16.48
17.25
17.48
18.49
19.71
21.03

21.65
21.80
23.28
23.43
24.20
24.42
25.44
26.66
27.98

889
896
1093
1104
1299
1312
1573
1929
2329

178
178
203
203
203
203
229
229
229

154
153
177
176
200
200
228
262
298

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.09
0.09
0.08
0.09
0.08
0.08
0.08
0.07
0.07

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06

215
215
245
244
277
277
315
361
408

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.09
0.09
0.08
0.09
0.08
0.08
0.08
0.07
0.07

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06

13.67
13.82
14.45
14.61
15.37
15.60
16.61
17.83
19.15
20.55
22.99
26.04
32.11
35.89

15.54
15.70
16.33
16.48
17.25
17.48
18.49
19.71
21.03
22.43
24.87
28.37
34.44
38.23

20.97
21.12
21.76
21.91
22.67
22.90
23.92
25.14
26.46
28.53
30.97
35.32
43.89
47.68

685
693
800
811
953
964
1144
1372
1666
1996
2637
3714
5606
7199

178
178
178
178
203
203
203
203
229
229
254
305
356
406

158
157
180
179
205
204
232
263
299
328
391
462
542
592

0.66
0.67
0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.15
0.16
0.15
0.15
0.14
0.14
0.14
0.13
0.13
0.13
0.12
0.11
0.11
0.10

2.54
2.55
2.06
2.08
1.63
1.64
1.34
1.08
0.84
0.70
0.52
0.35
0.23
0.18

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04

227
226
256
254
286
285
317
351
383
405
452
493
554
607

0.69
0.70
0.56
0.57
0.46
0.47
0.39
0.33
0.29
0.26
0.22
0.19
0.16
0.13

0.34
0.34
0.33
0.33
0.31
0.31
0.30
0.29
0.27
0.25
0.22
0.18
0.13
0.11

2.49
2.51
2.03
2.04
1.60
1.61
1.32
1.07
0.84
0.69
0.51
0.35
0.23
0.18

0.08
0.08
0.08
0.07
0.07
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
0.04

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 5

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

8kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

8kV 133% Aluminum Single Phase Full Neutral


Q6L01ZC
2 SOLID AL
140 10-#14
6.55
Q6M01ZC
2 AWG AL
140 10-#14
6.81
Q6N01ZC
1 SOLID AL
140 13-#14
7.34
Q6O01ZC
1 AWG AL
140 13-#14
7.65
Q6P01ZC
1/0 SOLID AL
140 16-#14
8.26
Q6Q01ZC
1/0 AWG AL
140 16-#14
8.59
Q6R01ZC
2/0 AWG AL
140 13-#12
9.60
Q6S01ZC
3/0 AWG AL
140 16-#12 10.82
Q6T01ZC
4/0 AWG AL
140 20-#12 12.14
Q6U01ZC
250 MCM AL
140 23-#12 13.28
Q6V01ZC
350 MCM AL
140 33-#12 15.72
8kV 133% Aluminum Three Phase One-Third Neutral
Q6L00ZC
2 SOLID AL
140
7-#16
6.55
Q6M00ZC
2 AWG AL
140
7-#16
6.81
Q6N00ZC
1 SOLID AL
140
8-#16
7.34
Q6O00ZC
1 AWG AL
140
8-#16
7.65
Q6P00ZC
1/0 SOLID AL
140
9-#16
8.26
Q6Q00ZC
1/0 AWG AL
140
9-#16
8.59
Q6R00ZC
2/0 AWG AL
140 11-#16
9.60
Q6S00ZC
3/0 AWG AL
140 14-#16 10.82
Q6T00ZC
4/0 AWG AL
140 17-#16 12.14
Q6U00ZC
250 MCM AL
140 21-#16 13.28
Q6V00ZC
350 MCM AL
140 27-#16 15.72
Q6W00ZC
500 MCM AL
140 25-#14 18.80
Q6X00ZC
750 MCM AL
140 24-#12 23.11
Q6Y00ZC
1000 MCM AL
140 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

14.99
15.14
15.77
15.98
16.69
16.92
17.93
19.15
20.47
21.87
24.31

16.87
17.02
17.65
17.86
18.57
18.80
19.81
21.03
22.35
23.75
26.19

22.97
23.12
23.75
23.96
24.67
24.90
26.76
27.98
29.30
30.70
33.14

618
625
714
722
830
819
1006
1170
1328
1586
2085

203
203
203
203
203
203
229
229
254
254
279

120
120
138
138
157
156
180
205
234
257
314

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.06
0.06

169
169
193
193
219
218
249
282
320
350
425

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.07
0.06
0.06

14.99
15.14
15.77
15.98
16.69
16.92
17.93
19.15
20.47
21.87
24.31
27.38
31.95
35.76

16.87
17.02
17.65
17.86
18.57
18.80
19.81
21.03
22.35
23.75
26.19
29.72
34.29
38.10

22.29
22.44
23.08
23.28
23.99
24.22
25.24
26.46
27.78
29.17
31.61
35.82
41.24
46.47

497
503
550
558
612
621
705
815
889
1086
1352
1852
2641
3381

203
203
203
203
203
203
203
229
229
254
254
305
330
381

124
124
141
141
161
160
182
208
237
260
313
379
463
523

1.08
1.10
0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.22
0.16
0.11
0.09

0.16
0.16
0.15
0.15
0.15
0.15
0.14
0.14
0.13
0.13
0.12
0.12
0.11
0.11

3.50
3.52
2.97
2.99
2.56
2.58
2.10
1.65
1.35
1.11
0.84
0.58
0.38
0.30

0.09
0.09
0.09
0.09
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05

177
176
201
200
227
226
255
286
320
344
397
448
502
541

1.10
1.12
0.88
0.90
0.71
0.72
0.59
0.48
0.40
0.35
0.28
0.23
0.19
0.17

0.34
0.34
0.33
0.33
0.32
0.32
0.31
0.30
0.29
0.27
0.25
0.22
0.18
0.15

3.43
3.46
2.92
2.94
2.52
2.54
2.06
1.63
1.33
1.09
0.84
0.58
0.38
0.29

0.09
0.09
0.09
0.09
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 6

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

8kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

8kV 133% Copper Single Phase Full Neutral


Q6301ZC
2 SOLID CU
140 16-#14
6.55
Q6401ZC
2 AWG CU
140 16-#14
6.81
Q6501ZC
1 SOLID CU
140 13-#12
7.34
Q6601ZC
1 AWG CU
140 13-#12
7.59
Q6701ZC
1/0 SOLID CU
140 16-#12
8.26
Q6801ZC
1/0 AWG CU
140 16-#12
8.59
Q6901ZC
2/0 AWG CU
140 20-#12
9.60
Q6A01ZC
3/0 AWG CU
140 26-#12 10.82
Q6B01ZC
4/0 AWG CU
140 32-#12 12.14
8kV 133% Copper Three Phase One-Third Neutral
Q6300ZC
2 SOLID CU
140
9-#16
6.55
Q6400ZC
2 AWG CU
140
9-#16
6.81
Q6500ZC
1 SOLID CU
140 11-#16
7.34
Q6600ZC
1 AWG CU
140 11-#16
7.59
Q6700ZC
1/0 SOLID CU
140 14-#16
8.26
Q6800ZC
1/0 AWG CU
140 14-#16
8.59
Q6900ZC
2/0 AWG CU
140 17-#16
9.60
Q6A00ZC
3/0 AWG CU
140 21-#16 10.82
Q6B00ZC
4/0 AWG CU
140 27-#16 12.14
Q6C00ZC
250 MCM CU
140 21-#14 13.28
Q6D00ZC
350 MCM CU
140 28-#14 15.72
Q6E00ZC
500 MCM CU
140 26-#12 18.77
Q6F00XC
750 MCM CU
140 25-#10 24.59
Q6G00XC
1000 MCM CU
140 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

14.99
15.14
15.77
15.93
16.69
16.92
17.93
19.15
20.47

16.87
17.02
17.65
17.81
18.57
18.80
19.81
21.03
22.35

22.97
23.12
24.60
24.75
25.52
25.75
26.76
27.98
29.30

932
940
1139
1151
1347
1360
1624
1982
2384

203
203
203
203
229
229
229
229
254

154
153
177
176
200
200
228
262
298

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.09
0.09
0.08
0.09
0.08
0.08
0.08
0.07
0.07

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.07

215
215
245
244
277
277
315
361
408

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.09
0.09
0.08
0.09
0.08
0.08
0.08
0.07
0.07

1.34
1.35
1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.07

14.99
15.14
15.77
15.93
16.69
16.92
17.93
19.15
20.47
21.87
24.31
27.36
33.43
37.21

16.87
17.02
17.65
17.81
18.57
18.80
19.81
21.03
22.35
23.75
26.19
29.69
35.76
39.55

22.29
22.44
23.08
23.23
23.99
24.22
25.24
26.46
27.78
29.85
32.29
36.64
45.21
49.00

727
735
843
854
998
1010
1192
1422
1718
2052
2698
3783
5692
7292

203
203
203
203
203
203
203
229
229
254
279
305
381
406

158
157
180
179
205
204
232
263
299
328
391
462
542
592

0.66
0.67
0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.15
0.16
0.15
0.15
0.14
0.14
0.14
0.13
0.13
0.13
0.12
0.11
0.11
0.10

2.54
2.55
2.06
2.08
1.63
1.64
1.34
1.08
0.84
0.70
0.52
0.35
0.23
0.18

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05

227
226
256
254
286
285
317
351
383
405
452
493
554
607

0.69
0.70
0.56
0.57
0.46
0.47
0.39
0.33
0.29
0.26
0.22
0.19
0.16
0.13

0.34
0.34
0.33
0.33
0.31
0.31
0.30
0.29
0.27
0.25
0.22
0.18
0.13
0.11

2.49
2.51
2.03
2.04
1.60
1.61
1.32
1.07
0.84
0.69
0.51
0.35
0.23
0.18

0.09
0.09
0.08
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 7

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

15kV 100% Aluminum Single Phase Full Neutral


Q7L01ZC
2 SOLID AL
175 10-#14
6.55
Q7M01ZC
2 AWG AL
175 10-#14
6.81
Q7N01ZC
1 SOLID AL
175 13-#14
7.34
Q7O01ZC
1 AWG AL
175 13-#14
7.65
Q7P01ZC
1/0 SOLID AL
175 16-#14
8.26
Q7Q01ZC
1/0 AWG AL
175 16-#14
8.59
Q7R01ZC
2/0 AWG AL
175 13-#12
9.60
Q7S01ZC
3/0 AWG AL
175 16-#12 10.82
Q7T01ZC
4/0 AWG AL
175 20-#12 12.14
Q7U01ZC
250 MCM AL
175 23-#12 13.28
Q7V01ZC
350 MCM AL
175 33-#12 15.72
15kV 100% Aluminum Three Phase One-Third Neutral
Q7L00ZC
2 SOLID AL
175
8-#16
6.55
Q7M00ZC
2 AWG AL
175
8-#16
6.81
Q7N00ZC
1 SOLID AL
175
8-#16
7.34
Q7O00ZC
1 AWG AL
175
8-#16
7.65
Q7P00ZC
1/0 SOLID AL
175
9-#16
8.26
Q7Q00ZC
1/0 AWG AL
175
9-#16
8.59
Q7R00ZC
2/0 AWG AL
175 11-#16
9.60
Q7S00ZC
3/0 AWG AL
175 14-#16 10.82
Q7T00ZC
4/0 AWG AL
175 17-#16 12.14
Q7U00ZC
250 MCM AL
175 21-#16 13.28
Q7V00ZC
350 MCM AL
175 27-#16 15.72
Q7W00ZC
500 MCM AL
175 25-#14 18.80
Q7X00ZC
750 MCM AL
175 24-#12 23.11
Q7Y00ZC
1000 MCM AL
175 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

16.76
16.92
17.55
17.75
18.47
18.69
19.71
20.93
22.25
23.65
26.09

18.64
18.80
19.43
19.63
20.35
20.57
21.59
22.81
24.13
25.53
28.42

24.74
24.90
25.53
25.74
26.45
26.68
28.54
29.76
31.08
32.48
35.37

680
687
778
786
885
895
1078
1245
1406
1669
2204

203
203
229
229
229
229
229
254
254
279
305

123
124
141
143
160
162
186
212
241
270
321

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

169
170
193
194
219
220
251
284
323
358
422

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

16.76
16.92
17.55
17.75
18.47
18.69
19.71
20.93
22.25
23.65
26.09
29.16
33.73
37.54

18.64
18.80
19.43
19.63
20.35
20.57
21.59
22.81
24.13
25.53
28.42
31.50
36.07
39.88

24.07
24.22
24.86
25.06
25.77
26.00
27.02
28.23
29.56
30.95
33.85
37.60
44.44
48.25

568
575
612
620
677
686
772
885
963
1164
1466
1948
2831
3504

203
203
203
203
229
229
229
229
254
254
279
305
356
406

126
126
143
143
163
163
186
212
241
264
319
385
469
531

1.08
1.10
0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.21
0.16
0.11
0.09

0.16
0.16
0.16
0.15
0.15
0.15
0.15
0.14
0.13
0.13
0.12
0.12
0.11
0.11

3.27
3.30
3.05
3.07
2.64
2.65
2.16
1.70
1.39
1.14
0.87
0.58
0.39
0.30

0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05

176
176
200
200
226
226
255
288
322
346
401
453
508
551

1.10
1.12
0.88
0.90
0.71
0.72
0.58
0.47
0.39
0.35
0.27
0.22
0.19
0.16

0.34
0.34
0.33
0.32
0.32
0.32
0.31
0.29
0.28
0.27
0.25
0.22
0.18
0.16

3.21
3.24
2.99
3.02
2.59
2.61
2.12
1.67
1.37
1.12
0.86
0.58
0.39
0.30

0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 8

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

15kV 100% Copper Single Phase Full Neutral


Q7301ZC
2 SOLID CU
175 16-#14
6.55
Q7401ZC
2 AWG CU
175 16-#14
6.81
Q7501ZC
1 SOLID CU
175 13-#12
7.34
Q7601ZC
1 AWG CU
175 13-#12
7.59
Q7701ZC
1/0 SOLID CU
175 16-#12
8.26
Q7801ZC
1/0 AWG CU
175 16-#12
8.59
Q7901ZC
2/0 AWG CU
175 20-#12
9.60
Q7A01ZC
3/0 AWG CU
175 26-#12 10.82
Q7B01ZC
4/0 AWG CU
175 32-#12 12.14
15kV 100% Copper Three Phase One-Third Neutral
Q7300ZC
2 SOLID CU
175
9-#16
6.55
Q7400ZC
2 AWG CU
175
9-#16
6.81
Q7500ZC
1 SOLID CU
175 11-#16
7.34
Q7600ZC
1 AWG CU
175 11-#16
7.59
Q7700ZC
1/0 SOLID CU
175 14-#16
8.26
Q7800ZC
1/0 AWG CU
175 14-#16
8.59
Q7900ZC
2/0 AWG CU
175 17-#16
9.60
Q7A00ZC
3/0 AWG CU
175 21-#16 10.82
Q7B00ZC
4/0 AWG CU
175 27-#16 12.14
Q7C00ZC
250 MCM CU
175 21-#14 13.28
Q7D00ZC
350 MCM CU
175 28-#14 15.72
Q7E00ZC
500 MCM CU
175 26-#12 18.77
Q7F00XC
750 MCM CU
175 25-#10 24.59
Q7G00XC
1000 MCM CU
175 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

16.76
16.92
17.55
17.70
18.47
18.69
19.71
20.93
22.25

18.64
18.80
19.43
19.58
20.35
20.57
21.59
22.81
24.13

24.74
24.90
26.38
26.53
27.29
27.52
28.54
29.76
31.08

994
1002
1206
1218
1416
1430
1696
2057
2463

203
203
229
229
229
229
229
254
254

157
158
181
182
205
207
237
270
307

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

215
217
245
246
277
279
317
359
407

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

16.76
16.92
17.55
17.70
18.47
18.69
19.71
20.93
22.25
23.65
26.09
29.13
35.20
38.99

18.64
18.80
19.43
19.58
20.35
20.57
21.59
22.81
24.13
25.53
28.42
31.47
37.54
42.19

24.07
24.22
24.86
25.01
25.77
26.00
27.02
28.23
29.56
31.63
34.52
38.42
46.99
51.64

787
795
905
917
1062
1075
1259
1493
1793
2132
2814
3881
5811
7494

203
203
203
203
229
229
229
229
254
254
279
330
381
432

162
162
184
184
209
210
238
271
307
336
400
471
550
599

0.66
0.67
0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.17
0.17
0.16
0.16
0.15
0.15
0.15
0.14
0.13
0.13
0.13
0.12
0.11
0.11

2.44
2.45
2.05
2.06
1.60
1.61
1.31
1.04
0.81
0.70
0.50
0.34
0.24
0.18

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05

223
224
252
252
283
284
317
351
385
409
457
501
557
611

0.69
0.70
0.56
0.57
0.46
0.46
0.39
0.33
0.28
0.26
0.22
0.19
0.15
0.13

0.34
0.34
0.33
0.32
0.32
0.31
0.30
0.28
0.26
0.25
0.22
0.18
0.14
0.12

2.39
2.41
2.01
2.03
1.58
1.59
1.29
1.02
0.80
0.69
0.50
0.34
0.24
0.18

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 9

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

15kV 133% Aluminum Single Phase Full Neutral


Q8L01ZC
2 SOLID AL
220 10-#14
6.55
Q8M01ZC
2 AWG AL
220 10-#14
6.81
Q8N01ZC
1 SOLID AL
220 13-#14
7.34
Q8O01ZC
1 AWG AL
220 13-#14
7.65
Q8P01ZC
1/0 SOLID AL
220 16-#14
8.26
Q8Q01ZC
1/0 AWG AL
220 16-#14
8.59
Q8R01ZC
2/0 AWG AL
220 13-#12
9.60
Q8S01ZC
3/0 AWG AL
220 16-#12 10.82
Q8T01ZC
4/0 AWG AL
220 20-#12 12.14
Q8U01ZC
250 MCM AL
220 23-#12 13.28
Q8V01ZC
350 MCM AL
220 33-#12 15.72
15kV 133% Aluminum Three Phase One-Third Neutral
Q8L00ZC
2 SOLID AL
220
9-#16
6.55
Q8M00ZC
2 AWG AL
220
9-#16
6.81
Q8N00ZC
1 SOLID AL
220
9-#16
7.34
Q8O00ZC
1 AWG AL
220
9-#16
7.65
Q8P00ZC
1/0 SOLID AL
220
9-#16
8.26
Q8Q00ZC
1/0 AWG AL
220 10-#16
8.59
Q8R00ZC
2/0 AWG AL
220 11-#16
9.60
Q8S00ZC
3/0 AWG AL
220 14-#16 10.82
Q8T00ZC
4/0 AWG AL
220 17-#16 12.14
Q8U00ZC
250 MCM AL
220 21-#16 13.28
Q8V00ZC
350 MCM AL
220 27-#16 15.72
Q8W00ZC
500 MCM AL
220 25-#14 18.80
Q8X00ZC
750 MCM AL
220 24-#12 23.11
Q8Y00ZC
1000 MCM AL
220 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

19.10
19.25
19.89
20.09
20.80
21.03
22.05
23.27
24.59
25.98
28.42

20.98
21.13
21.77
21.97
22.68
22.91
23.93
25.15
26.47
27.86
30.76

27.08
27.23
27.87
28.07
28.78
29.01
30.88
32.10
33.42
34.81
37.71

769
776
869
878
9779
990
1179
1351
1516
1784
2330

229
229
229
229
254
254
254
279
279
279
305

123
124
141
143
160
162
186
212
241
270
321

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

169
170
193
194
219
220
251
284
323
358
422

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

2.17
2.20
1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.07

19.10
19.25
19.89
20.09
20.80
21.03
22.05
23.27
24.59
25.98
28.42
31.50
36.07
39.88

20.98
21.13
21.77
21.97
22.68
22.91
23.93
25.15
26.47
27.86
30.76
33.83
38.40
43.08

26.41
26.56
27.19
27.40
28.11
28.34
29.35
30.57
31.89
33.29
36.18
39.93
46.78
51.45

665
672
712
720
768
789
868
985
1068
1273
1586
2080
2986
3744

229
229
229
229
229
229
254
254
279
279
305
330
381
432

127
127
144
145
164
165
187
214
243
266
321
387
471
534

1.08
1.10
0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.21
0.16
0.11
0.09

0.17
0.17
0.17
0.16
0.16
0.16
0.15
0.14
0.14
0.13
0.13
0.12
0.12
0.11

3.02
3.04
2.80
2.82
2.63
2.45
2.15
1.69
1.39
1.13
0.87
0.58
0.39
0.30

0.11
0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06
0.05

174
174
198
198
224
224
254
286
320
345
401
454
511
554

1.11
1.13
0.88
0.90
0.70
0.72
0.58
0.47
0.39
0.34
0.27
0.22
0.18
0.16

0.34
0.34
0.33
0.32
0.32
0.31
0.31
0.29
0.28
0.27
0.25
0.22
0.19
0.16

2.96
2.99
2.75
2.77
2.58
2.41
2.11
1.67
1.37
1.12
0.86
0.58
0.39
0.30

0.11
0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 10

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

15kV 133% Copper Single Phase Full Neutral


Q8301ZC
2 SOLID CU
220 16-#14
6.55
Q8401ZC
2 AWG CU
220 16-#14
6.81
Q8501ZC
1 SOLID CU
220 13-#12
7.34
Q8601ZC
1 AWG CU
220 13-#12
7.59
Q8701ZC
1/0 SOLID CU
220 16-#12
8.26
Q8801ZC
1/0 AWG CU
220 16-#12
8.59
Q8901ZC
2/0 AWG CU
220 20-#12
9.60
Q8A01ZC
3/0 AWG CU
220 26-#12 10.82
Q8B01ZC
4/0 AWG CU
220 32-#12 12.14
15kV 133% Copper Three Phase One-Third Neutral
Q8300ZC
2 SOLID CU
220
9-#16
6.55
Q8400ZC
2 AWG CU
220
9-#16
6.81
Q8500ZC
1 SOLID CU
220 11-#16
7.34
Q8600ZC
1 AWG CU
220 11-#16
7.59
Q8700ZC
1/0 SOLID CU
220 14-#16
8.26
Q8800ZC
1/0 AWG CU
220 14-#16
8.59
Q8900ZC
2/0 AWG CU
220 17-#16
9.60
Q8A00ZC
3/0 AWG CU
220 21-#16 10.82
Q8B00ZC
4/0 AWG CU
220 27-#16 12.14
Q8C00ZC
250 MCM CU
220 21-#14 13.28
Q8D00ZC
350 MCM CU
220 28-#14 15.72
Q8E00ZC
500 MCM CU
220 26-#12 18.77
Q8F00XC
750 MCM CU
220 25-#10 24.59
Q8G00XC
1000 MCM CU
220 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

19.10
19.25
19.89
20.04
20.80
21.03
22.05
23.27
24.59

20.98
21.13
21.77
21.92
22.68
22.91
23.93
25.15
26.47

27.08
27.23
28.72
28.87
29.63
29.86
30.88
32.10
33.42

1082
1091
1300
1312
1513
1528
1797
2163
2573

229
229
254
254
254
254
254
279
279

157
158
181
182
205
207
237
270
307

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

215
217
245
246
277
279
317
359
407

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

1.34
1.35
1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08
0.08

19.10
19.25
19.89
20.04
20.80
21.03
22.05
23.27
24.59
25.98
28.42
31.47
37.54
41.33

20.98
21.13
21.77
21.92
22.68
22.91
23.93
25.15
26.47
27.86
30.76
33.81
39.88
44.53

26.41
26.56
27.19
27.35
28.11
28.34
29.35
30.57
31.89
33.96
36.86
40.76
49.33
53.98

873
882
994
1006
1154
1167
1355
1593
1897
2244
2936
4017
5975
7674

229
229
229
229
229
229
254
254
279
279
305
330
406
432

162
162
184
184
209
210
238
271
307
336
400
471
550
599

0.66
0.67
0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.17
0.17
0.16
0.16
0.15
0.15
0.15
0.14
0.13
0.13
0.13
0.12
0.11
0.11

2.44
2.45
2.05
2.06
1.60
1.61
1.31
1.04
0.81
0.70
0.50
0.34
0.24
0.18

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05

223
224
252
252
283
284
317
351
385
409
457
501
557
611

0.69
0.70
0.56
0.57
0.46
0.46
0.39
0.33
0.28
0.26
0.22
0.19
0.15
0.13

0.34
0.34
0.33
0.32
0.32
0.31
0.30
0.28
0.26
0.25
0.22
0.18
0.14
0.12

2.39
2.41
2.01
2.03
1.58
1.59
1.29
1.02
0.80
0.69
0.50
0.34
0.24
0.18

0.10
0.10
0.09
0.09
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06
0.05
0.05

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 11

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

25kV 100% Aluminum Single Phase Full Neutral


Q9N01ZC
1 SOLID AL
260 13-#14
7.34
Q9O01ZC
1 AWG AL
260 13-#14
7.65
Q9P01ZC
1/0 SOLID AL
260 16-#14
8.26
Q9Q01ZC
1/0 AWG AL
260 16-#14
8.59
Q9R01ZC
2/0 AWG AL
260 13-#12
9.60
Q9S01ZC
3/0 AWG AL
260 16-#12 10.82
Q9T01ZC
4/0 AWG AL
260 20-#12 12.14
Q9U01ZC
250 MCM AL
260 23-#12 13.28
Q9V01ZC
350 MCM AL
260 33-#12 15.72
25kV 100% Aluminum Three Phase One-Third Neutral
Q9N00ZC
1 SOLID AL
260 10-#16
7.34
Q9O00ZC
1 AWG AL
260 10-#16
7.65
Q9P00ZC
1/0 SOLID AL
260 10-#16
8.26
Q9Q00ZC
1/0 AWG AL
260 10-#16
8.59
Q9R00ZC
2/0 AWG AL
260 11-#16
9.60
Q9S00ZC
3/0 AWG AL
260 14-#16 10.82
Q9T00ZC
4/0 AWG AL
260 17-#16 12.14
Q9U00ZC
250 MCM AL
260 21-#16 13.28
Q9V00ZC
350 MCM AL
260 27-#16 15.72
Q9W00ZC
500 MCM AL
260 25-#14 18.80
Q9X00ZC
750 MCM AL
260 24-#12 23.11
Q9Y00ZC
1000 MCM AL
260 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

21.97
22.17
22.89
23.11
24.13
25.35
26.67
28.07
30.51

23.85
24.05
24.77
24.99
26.01
27.23
29.01
30.40
32.84

29.95
30.15
30.87
31.09
32.96
34.18
35.96
37.35
39.79

957
966
1070
1081
1276
1451
1652
1926
2448

254
254
254
254
279
279
305
305
330

145
146
165
166
190
217
247
276
326

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08

192
194
218
219
250
283
322
356
418

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08

21.97
22.17
22.89
23.11
24.13
25.35
26.67
28.07
30.51
33.58
38.15
41.96

23.85
24.05
24.77
24.99
26.01
27.23
29.01
30.40
32.84
35.92
40.49
45.16

29.28
29.48
30.19
30.42
31.44
32.65
34.43
35.83
38.27
43.44
48.86
53.53

808
818
867
878
960
1081
1198
1408
1699
2283
3131
3903

254
254
254
254
254
279
279
305
330
356
406
432

146
146
166
166
189
215
244
268
322
389
473
535

0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.21
0.16
0.11
0.09

0.17
0.17
0.16
0.16
0.16
0.15
0.15
0.14
0.13
0.13
0.12
0.12

2.60
2.62
2.43
2.45
2.15
1.69
1.38
1.13
0.86
0.58
0.39
0.30

0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06

196
197
223
223
252
284
318
344
400
453
514
557

0.88
0.90
0.71
0.72
0.58
0.47
0.39
0.34
0.27
0.22
0.18
0.16

0.33
0.32
0.32
0.31
0.31
0.29
0.28
0.27
0.25
0.23
0.19
0.16

2.53
2.57
2.38
2.40
2.11
1.66
1.36
1.12
0.85
0.58
0.39
0.30

0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 12

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

25kV 100% Copper Single Phase Full Neutral


Q9501ZC
1 SOLID CU
260 13-#12
7.34
Q9601ZC
1 AWG CU
260 13-#12
7.59
Q9701ZC
1/0 SOLID CU
260 16-#12
8.26
Q9801ZC
1/0 AWG CU
260 16-#12
8.59
Q9901ZC
2/0 AWG CU
260 20-#12
9.60
Q9A01ZC
3/0 AWG CU
260 26-#12 10.82
Q9B01ZC
4/0 AWG CU
260 32-#12 12.14
25kV 100% Copper Three Phase One-Third Neutral
Q9500ZC
1 SOLID CU
260 11-#16
7.34
Q9600ZC
1 AWG CU
260 11-#16
7.59
Q9700ZC
1/0 SOLID CU
260 14-#16
8.26
Q9800ZC
1/0 AWG CU
260 14-#16
8.59
Q9900ZC
2/0 AWG CU
260 17-#16
9.60
Q9A00ZC
3/0 AWG CU
260 21-#16 10.82
Q9B00ZC
4/0 AWG CU
260 27-#16 12.14
Q9C00ZC
250 MCM CU
260 21-#14 13.28
Q9D00ZC
350 MCM CU
260 28-#14 15.72
Q9E00ZC
500 MCM CU
260 26-#12 18.77
Q9F00XC
750 MCM CU
260 25-#10 24.59
Q9G00XC
1000 MCM CU
260 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

21.97
22.12
22.89
23.11
24.13
25.35
26.67

23.85
24.00
24.77
24.99
26.01
27.23
29.01

30.80
30.95
31.71
31.94
32.96
34.18
35.96

1390
1403
1607
1621
1895
2264
2710

254
254
254
279
279
279
305

186
187
210
212
243
276
314

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

245
246
277
279
317
359
406

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

21.97
22.12
22.89
23.11
24.13
25.35
26.67
28.07
30.51
33.55
39.62
43.41

23.85
24.00
24.77
24.99
26.01
27.23
29.01
30.40
32.84
35.89
42.82
46.61

29.28
29.43
30.19
30.42
31.44
32.65
34.43
36.50
38.94
44.26
52.27
56.06

1079
1092
1242
1256
1447
1689
2027
2382
3052
4224
6201
7842

254
254
254
254
254
279
279
305
330
356
432
457

187
187
213
213
242
275
311
341
405
475
557
606

0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.17
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.13
0.12
0.11

2.04
2.05
1.60
1.61
1.31
1.03
0.81
0.69
0.50
0.34
0.24
0.18

0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06

249
249
280
281
314
349
384
410
460
504
566
618

0.55
0.56
0.45
0.46
0.38
0.32
0.28
0.25
0.21
0.18
0.15
0.13

0.33
0.32
0.32
0.31
0.30
0.28
0.27
0.26
0.23
0.19
0.15
0.12

2.00
2.01
1.57
1.58
1.29
1.02
0.80
0.69
0.50
0.34
0.24
0.18

0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 13

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

25kV 133% Aluminum Single Phase Full Neutral


QAN01ZC
1 SOLID AL
320 13-#14
7.34
QAO01ZC
1 AWG AL
320 13-#14
7.65
QAP01ZC
1/0 SOLID AL
320 16-#14
8.26
QAQ01ZC
1/0 AWG AL
320 16-#14
8.59
QAR01ZC
2/0 AWG AL
320 13-#12
9.60
QAS01ZC
3/0 AWG AL
320 16-#12 10.82
QAT01ZC
4/0 AWG AL
320 20-#12 12.14
QAU01ZC
250 MCM AL
320 23-#12 13.28
QAV01ZC
350 MCM AL
320 33-#12 15.72
25kV 133% Aluminum Three Phase One-Third Neutral
QAN00ZC
1 SOLID AL
320 11-#16
7.34
QAO00ZC
1 AWG AL
320 11-#16
7.65
QAP00ZC
1/0 SOLID AL
320 11-#16
8.26
QAQ00ZC
1/0 AWG AL
320 12-#16
8.59
QAR00ZC
2/0 AWG AL
320 12-#16
9.60
QAS00ZC
3/0 AWG AL
320 14-#16 10.82
QAT00ZC
4/0 AWG AL
320 17-#16 12.14
QAU00ZC
250 MCM AL
320 21-#16 13.28
QAV00ZC
350 MCM AL
320 27-#16 15.72
QAW00ZC
500 MCM AL
320 25-#14 18.80
QAX00ZC
750 MCM AL
320 24-#12 23.11
QAY00ZC
1000 MCM AL
320 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

25.12
25.32
26.04
26.26
27.28
28.50
29.82
31.22
33.66

27.00
27.20
27.91
28.60
29.62
30.84
32.16
33.55
35.99

33.10
33.30
34.02
34.70
36.57
37.79
39.11
40.50
44.36

1110
1112
1218
1261
1467
1648
1825
2105
2719

279
279
279
279
305
305
330
330
356

145
146
165
166
190
217
247
276
326

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08

192
194
218
219
250
283
322
356
418

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.10
0.10
0.10
0.09
0.09
0.09
0.08
0.08

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.09
0.08
0.08

25.12
25.32
26.04
26.26
27.28
28.50
29.82
31.22
33.66
36.73
41.30
45.11

27.00
27.20
27.91
28.60
29.62
30.84
32.16
33.55
35.99
39.07
44.50
48.31

32.43
32.63
33.34
34.03
35.04
36.26
37.58
38.98
41.42
46.59
52.87
56.68

960
971
1024
1077
1153
1270
1363
1580
1882
2489
3436
4156

279
279
279
279
305
305
305
330
356
381
432
457

147
147
167
168
191
217
246
270
324
391
476
538

0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.21
0.16
0.11
0.09

0.18
0.17
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.13
0.12

2.44
2.45
2.26
2.15
2.30
1.68
1.38
1.13
0.86
0.58
0.39
0.30

0.12
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

194
195
220
220
250
282
316
342
399
453
517
561

0.88
0.90
0.71
0.70
0.57
0.47
0.38
0.34
0.26
0.22
0.18
0.16

0.33
0.32
0.32
0.31
0.31
0.30
0.28
0.27
0.26
0.23
0.19
0.17

2.39
2.41
2.22
2.11
2.25
1.65
1.36
1.11
0.85
0.57
0.39
0.30

0.12
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 14

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

25kV 133% Copper Single Phase Full Neutral


QA501ZC
1 SOLID CU
320 13-#12
7.34
QA601ZC
1 AWG CU
320 13-#12
7.59
QA701ZC
1/0 SOLID CU
320 16-#12
8.26
QA801ZC
1/0 AWG CU
320 16-#12
8.59
QA901ZC
2/0 AWG CU
320 20-#12
9.60
QAA01ZC
3/0 AWG CU
320 26-#12 10.82
QAB01ZC
4/0 AWG CU
320 32-#12 12.14
25kV 133% Copper Three Phase One-Third Neutral
QA500ZC
1 SOLID CU
320 11-#16
7.34
QA600ZC
1 AWG CU
320 11-#16
7.59
QA700ZC
1/0 SOLID CU
320 14-#16
8.26
QA800ZC
1/0 AWG CU
320 14-#16
8.59
QA900ZC
2/0 AWG CU
320 17-#16
9.60
QAA00ZC
3/0 AWG CU
320 21-#16 10.82
QAB00ZC
4/0 AWG CU
320 27-#16 12.14
QAC00ZC
250 MCM CU
320 21-#14 13.28
QAD00ZC
350 MCM CU
320 28-#14 15.72
QAE00ZC
500 MCM CU
320 26-#12 18.77
QAF00XC
750 MCM CU
320 25-#10 24.59
QAG00XC
1000 MCM CU
320 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

25.12
25.27
26.04
26.26
27.28
28.50
29.82

27.00
27.15
27.91
28.60
29.62
30.84
32.16

33.95
34.10
34.86
35.55
36.57
37.79
39.11

1539
1552
1760
1806
2085
2461
2883

279
279
279
305
305
305
330

186
187
210
212
243
276
314

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

245
246
277
279
317
359
406

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

1.04
1.06
0.84
0.85
0.67
0.53
0.43

0.11
0.11
0.10
0.10
0.10
0.09
0.09

25.12
25.27
26.04
26.26
27.28
28.50
29.82
31.22
33.66
36.70
42.77
46.56

27.00
27.15
27.91
28.60
29.62
30.84
32.16
33.55
35.99
39.04
45.97
49.76

32.43
32.58
33.34
34.03
35.04
36.26
37.58
39.65
43.52
47.41
55.42
59.21

1220
1234
1388
1433
1628
1877
2193
2557
3317
4434
6449
8107

279
279
279
279
305
305
305
330
356
381
457
483

187
187
213
213
242
275
311
341
405
475
557
606

0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.17
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.13
0.12
0.11

2.04
2.05
1.60
1.61
1.31
1.03
0.81
0.69
0.50
0.34
0.24
0.18

0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06

249
249
280
281
314
349
384
410
460
504
566
618

0.55
0.56
0.45
0.46
0.38
0.32
0.28
0.25
0.21
0.18
0.15
0.13

0.33
0.32
0.32
0.31
0.30
0.28
0.27
0.26
0.23
0.19
0.15
0.12

2.00
2.01
1.57
1.58
1.29
1.02
0.80
0.69
0.50
0.34
0.24
0.18

0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.08
0.07
0.07
0.06
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 15

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

28kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

28kV 100% Aluminum Single Phase Full Neutral


QVN01ZC
1 SOLID AL
280 13-#14
7.34
QVO01ZC
1 AWG AL
280 13-#14
7.65
QVP01ZC
1/0 SOLID AL
280 16-#14
8.26
QVQ01ZC
1/0 AWG AL
280 16-#14
8.59
QVR01ZC
2/0 AWG AL
280 13-#12
9.60
QVS01ZC
3/0 AWG AL
280 16-#12 10.82
QVT01ZC
4/0 AWG AL
280 20-#12 12.14
QVU01ZC
250 MCM AL
280 23-#12 13.28
QVV01ZC
350 MCM AL
280 33-#12 15.72
28kV 100% Aluminum Three Phase One-Third Neutral
QVN00ZC
1 SOLID AL
280 10-#16
7.34
QVO00ZC
1 AWG AL
280 10-#16
7.65
QVP00ZC
1/0 SOLID AL
280 11-#16
8.26
QVQ00ZC
1/0 AWG AL
280 11-#16
8.59
QVR00ZC
2/0 AWG AL
280 11-#16
9.60
QVS00ZC
3/0 AWG AL
280 14-#16 10.82
QVT00ZC
4/0 AWG AL
280 17-#16 12.14
QVU00ZC
250 MCM AL
280 21-#16 13.28
QVV00ZC
350 MCM AL
280 27-#16 15.72
QVW00ZC
500 MCM AL
280 25-#14 18.80
QVX00ZC
750 MCM AL
280 24-#12 23.11
QVY00ZC
1000 MCM AL
280 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

23.04
23.24
23.95
24.18
25.20
26.42
27.74
29.13
31.57

24.92
25.12
25.83
26.06
27.08
28.75
30.07
31.47
33.91

31.02
31.22
31.93
32.16
34.03
35.70
37.02
38.42
40.86

1004
1014
1118
1130
1328
1526
1709
1985
2511

254
254
279
279
279
305
305
330
330

146
146
165
165
189
216
245
268
327

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.11
0.11
0.10
0.10
0.10
0.10
0.09
0.09
0.08

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.11
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08

192
192
218
217
247
281
319
348
423

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.11
0.11
0.10
0.10
0.10
0.10
0.09
0.09
0.08

1.70
1.72
1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.11
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08

23.04
23.24
23.95
24.18
25.20
26.42
27.74
29.13
31.57
34.65
39.22
43.03

24.92
25.12
25.83
26.06
27.08
28.75
30.07
31.47
33.91
36.98
42.42
46.23

30.34
30.55
31.26
31.49
32.50
34.18
35.50
36.90
39.33
44.51
50.79
54.60

854
864
926
937
1010
1163
1252
1465
1759
2351
3279
3987

254
254
254
254
279
279
305
305
330
381
406
457

146
145
166
165
188
214
243
266
320
386
470
531

0.86
0.87
0.68
0.70
0.55
0.44
0.35
0.30
0.21
0.16
0.11
0.09

0.17
0.17
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.13
0.12

2.53
2.55
2.20
2.22
2.08
1.64
1.34
1.10
0.84
0.58
0.38
0.29

0.11
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

195
194
221
220
249
281
314
340
395
449
509
552

0.88
0.90
0.71
0.73
0.58
0.47
0.39
0.34
0.27
0.22
0.18
0.16

0.33
0.33
0.32
0.32
0.31
0.30
0.29
0.28
0.26
0.23
0.19
0.17

2.48
2.50
2.16
2.18
2.04
1.61
1.32
1.08
0.83
0.57
0.38
0.29

0.11
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 16

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

28kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
A
/km anc
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

28kV 100% Copper Single Phase Full Neutral


QV501ZC
1 SOLID CU
280 13-#12
7.34
QV601ZC
1 AWG CU
280 13-#12
7.59
QV701ZC
1/0 SOLID CU
280 16-#12
8.26
QV801ZC
1/0 AWG CU
280 16-#12
8.59
QV901ZC
2/0 AWG CU
280 20-#12
9.60
QVA01ZC
3/0 AWG CU
280 26-#12 10.82
QVB01ZC
4/0 AWG CU
280 32-#12 12.14
28kV 100% Copper Three Phase One-Third Neutral
QV500ZC
1 SOLID CU
280 11-#16
7.34
QV600ZC
1 AWG CU
280 11-#16
7.59
QV700ZC
1/0 SOLID CU
280 14-#16
8.26
QV800ZC
1/0 AWG CU
280 14-#16
8.59
QV900ZC
2/0 AWG CU
280 17-#16
9.60
QVA00ZC
3/0 AWG CU
280 21-#16 10.82
QVB00ZC
4/0 AWG CU
280 27-#16 12.14
QVC00ZC
250 MCM CU
280 21-#14 13.28
QVD00ZC
350 MCM CU
280 28-#14 15.72
QVE00ZC
500 MCM CU
280 26-#12 18.77
QVF00XC
750 MCM CU
280 25-#10 24.59
QVG00XC
1000 MCM CU
280 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

23.04
23.19
23.95
24.18
25.20
26.42
27.74

24.92
25.07
25.83
26.06
27.08
28.75
30.07

31.87
32.02
32.78
33.01
34.03
35.70
37.02

1439
1452
1657
1672
1947
2349
2767

279
279
279
279
279
305
305

187
186
211
211
240
276
312

1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.11
0.11
0.10
0.10
0.09

1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.11
0.11
0.10
0.10
0.09

244
244
277
276
314
359
407

1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.11
0.11
0.10
0.10
0.09

1.04
1.06
0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.11
0.11
0.10
0.10
0.09

23.04
23.19
23.95
24.18
25.20
26.42
27.74
29.13
31.57
34.62
40.69
44.48

24.92
25.07
25.83
26.06
27.08
28.75
30.07
31.47
33.91
36.96
43.89
47.68

30.34
30.50
31.26
31.49
32.50
34.18
35.50
37.57
40.01
45.33
53.34
57.12

1125
1138
1290
1304
1497
1770
2082
2440
3113
4294
6284
7930

254
254
254
254
279
279
305
305
330
381
432
457

188
186
213
212
240
273
309
338
402
473
557
609

0.52
0.53
0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.17
0.17
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.12
0.11

2.04
2.06
1.61
1.62
1.32
1.07
0.84
0.69
0.51
0.35
0.23
0.18

0.11
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

249
247
280
278
312
347
382
407
458
502
568
620

0.55
0.56
0.45
0.46
0.38
0.32
0.27
0.25
0.21
0.18
0.15
0.13

0.33
0.33
0.32
0.32
0.30
0.29
0.28
0.26
0.23
0.19
0.15
0.12

2.00
2.01
1.58
1.59
1.30
1.05
0.83
0.68
0.51
0.35
0.23
0.18

0.11
0.11
0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 17

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

28kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

28kV 133% Aluminum Single Phase Full Neutral


QBP01ZC
1/0 SOLID AL
345 16-#14
8.26
QBQ01ZC
1/0 AWG AL
345 16-#14
8.59
QBR01ZC
2/0 AWG AL
345 13-#12
9.60
QBS01ZC
3/0 AWG AL
345 16-#12 10.82
QBT01ZC
4/0 AWG AL
345 20-#12 12.14
QBU01ZC
250 MCM AL
345 23-#12 13.28
QBV01ZC
350 MCM AL
345 33-#12 15.72
28kV 133% Aluminum Three Phase One-Third Neutral
QBP00ZC
1/0 SOLID AL
345 12-#16
8.26
QBQ00ZC
1/0 AWG AL
345 12-#16
8.59
QBR00ZC
2/0 AWG AL
345 13-#16
9.60
QBS00ZC
3/0 AWG AL
345 14-#16 10.82
QBT00ZC
4/0 AWG AL
345 17-#16 12.14
QBU00ZC
250 MCM AL
345 21-#16 13.28
QBV00ZC
350 MCM AL
345 27-#16 15.72
QBW00ZC
500 MCM AL
345 25-#14 18.80
QBX00ZC
750 MCM AL
345 24-#12 23.11
QBY00ZC
1000 MCM AL
345 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

27.41
27.64
28.65
29.87
31.19
32.59
35.03

29.74
29.97
30.99
32.21
33.53
34.93
37.36

35.84
36.07
37.94
39.16
40.48
41.87
45.74

1319
1332
1541
1725
1905
2188
2810

305
305
305
330
330
356
381

165
165
189
216
245
268
327

1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.10
0.10
0.10
0.10
0.09
0.09
0.08

1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.11
0.11
0.10
0.10
0.09
0.09
0.08

218
217
247
281
319
348
423

1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.10
0.10
0.10
0.10
0.09
0.09
0.08

1.36
1.38
1.08
0.86
0.69
0.59
0.42

0.11
0.11
0.10
0.10
0.09
0.09
0.08

27.41
27.64
28.65
29.87
31.19
32.59
35.03
38.10
42.67
46.48

29.74
29.97
30.99
32.21
33.53
34.93
37.36
40.44
45.87
49.68

35.17
35.40
36.41
37.63
38.95
40.35
44.21
47.96
54.24
58.05

1134
1146
1236
1344
1440
1660
2046
2584
3543
4271

305
305
305
305
330
330
356
406
457
483

168
167
190
216
245
268
322
388
472
534

0.68
0.70
0.55
0.44
0.35
0.30
0.22
0.16
0.11
0.09

0.18
0.18
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.12

2.07
2.09
1.84
1.63
1.33
1.09
0.83
0.58
0.38
0.29

0.12
0.12
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07

219
217
246
279
312
338
393
449
512
557

0.71
0.73
0.58
0.47
0.39
0.34
0.26
0.22
0.18
0.16

0.32
0.32
0.31
0.27
0.29
0.28
0.26
0.23
0.20
0.17

2.03
2.05
1.80
1.60
1.31
1.08
0.82
0.57
0.38
0.29

0.12
0.12
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 18

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

28kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

28kV 133% Copper Single Phase Full Neutral


QB701ZC
1/0 SOLID CU
345 16-#12
8.26
QB801ZC
1/0 AWG CU
345 16-#12
8.59
QB901ZC
2/0 AWG CU
345 20-#12
9.60
QBA01ZC
3/0 AWG CU
345 26-#12 10.82
QBB01ZC
4/0 AWG CU
345 32-#12 12.14
28kV 133% Copper Three Phase One-Third Neutral
QB700ZC
1/0 SOLID CU
345 14-#16
8.26
QB800ZC
1/0 AWG CU
345 14-#16
8.59
QB900ZC
2/0 AWG CU
345 17-#16
9.60
QBA00ZC
3/0 AWG CU
345 21-#16 10.82
QBB00ZC
4/0 AWG CU
345 27-#16 12.14
QBC00ZC
250 MCM CU
345 21-#14 13.28
QBD00ZC
350 MCM CU
345 28-#14 15.72
QBE00ZC
500 MCM CU
345 26-#12 18.77
QBF00XC
750 MCM CU
345 25-#10 24.59
QBG00XC
1000 MCM CU
345 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

27.41
27.64
28.65
29.87
31.19

29.74
29.97
30.99
32.21
33.53

36.69
36.92
37.94
39.16
40.48

1863
1879
2160
2538
2962

305
305
305
330
330

211
211
240
276
312

0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.10
0.10
0.09

0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.10
0.10
0.09

277
276
314
359
407

0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.10
0.10
0.09

0.84
0.85
0.68
0.53
0.42

0.11
0.11
0.10
0.10
0.09

27.41
27.64
28.65
29.87
31.19
32.59
35.03
38.07
44.15
47.93

29.74
29.97
30.99
32.21
33.53
34.93
37.36
40.41
47.35
51.13

35.17
35.40
36.41
37.63
38.95
41.03
44.89
48.78
56.79
60.58

1486
1502
1701
1951
2269
2638
3405
4530
6561
8226

305
305
305
305
330
330
381
406
457
508

213
212
240
273
309
338
402
473
557
609

0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.12
0.11

1.61
1.62
1.32
1.07
0.84
0.69
0.51
0.35
0.23
0.18

0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

280
278
312
347
382
407
458
502
568
620

0.45
0.46
0.38
0.32
0.27
0.25
0.21
0.18
0.15
0.13

0.32
0.32
0.30
0.29
0.28
0.26
0.23
0.19
0.15
0.12

1.58
1.59
1.30
1.05
0.83
0.68
0.51
0.35
0.23
0.18

0.11
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07
0.06

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 19

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

35kV 100% Aluminum Single Phase Full Neutral


QBP01ZC
1/0 SOLID AL
345 16-#14
8.26
QBQ01ZC
1/0 AWG AL
345 16-#14
8.59
QBR01ZC
2/0 AWG AL
345 13-#12
9.60
QBS01ZC
3/0 AWG AL
345 16-#12 10.82
QBT01ZC
4/0 AWG AL
345 20-#12 12.14
QBU01ZC
250 MCM AL
345 23-#12 13.28
QBV01ZC
350 MCM AL
345 33-#12 15.72
35kV 100% Aluminum Three Phase One-Third Neutral
QBP00ZC
1/0 SOLID AL
345 12-#16
8.26
QBQ00ZC
1/0 AWG AL
345 12-#16
8.59
QBR00ZC
2/0 AWG AL
345 13-#16
9.60
QBS00ZC
3/0 AWG AL
345 14-#16 10.82
QBT00ZC
4/0 AWG AL
345 17-#16 12.14
QBU00ZC
250 MCM AL
345 21-#16 13.28
QBV00ZC
350 MCM AL
345 27-#16 15.72
QBW00ZC
500 MCM AL
345 25-#14 18.80
QBX00ZC
750 MCM AL
345 24-#12 23.11
QBY00ZC
1000 MCM AL
345 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

27.41
27.64
28.65
29.87
31.19
32.59
35.03

29.74
29.97
30.99
32.21
33.53
34.93
37.36

35.84
36.07
37.94
39.16
40.48
41.87
45.74

1319
1332
1541
1725
1905
2266
2810

305
305
305
330
330
356
381

168
169
194
220
250
280
331

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.08

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.12
0.11
0.11
0.10
0.10
0.09
0.09

217
218
249
283
321
353
417

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.08

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.12
0.11
0.11
0.10
0.10
0.09
0.09

27.41
27.64
28.65
29.87
31.19
32.59
35.03
38.10
42.67
46.48

29.74
29.97
30.99
32.21
33.53
34.93
37.36
40.44
45.87
49.68

35.17
35.40
36.41
37.63
38.95
40.35
44.21
47.96
54.24
58.05

1134
1146
1236
1344
1440
1660
2046
2584
3543
4271

305
305
305
305
330
330
356
406
457
483

168
167
190
216
245
268
322
388
472
535

0.68
0.70
0.55
0.44
0.35
0.30
0.22
0.16
0.11
0.09

0.18
0.18
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.12

2.07
2.09
1.84
1.63
1.33
1.09
0.83
0.58
0.38
0.29

0.12
0.12
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07

219
217
246
279
312
338
393
449
512
557

0.71
0.73
0.58
0.47
0.39
0.34
0.26
0.22
0.18
0.16

0.32
0.32
0.31
0.27
0.29
0.28
0.26
0.23
0.20
0.17

2.03
2.05
1.80
1.60
1.31
1.08
0.82
0.57
0.38
0.29

0.12
0.12
0.11
0.10
0.10
0.09
0.09
0.08
0.07
0.07

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 20

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 100%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

35kV 100% Copper Single Phase Full Neutral


QB701ZC
1/0 SOLID CU
345 16-#12
8.26
QB801ZC
1/0 AWG CU
345 16-#12
8.59
QB901ZC
2/0 AWG CU
345 20-#12
9.60
QBA01ZC
3/0 AWG CU
345 26-#12 10.82
QBB01ZC
4/0 AWG CU
345 32-#12 12.14
35kV 100% Copper Three Phase One-Third Neutral
QB700ZC
1/0 SOLID CU
345 14-#16
8.26
QB800ZC
1/0 AWG CU
345 14-#16
8.59
QB900ZC
2/0 AWG CU
345 17-#16
9.60
QBA00ZC
3/0 AWG CU
345 21-#16 10.82
QBB00ZC
4/0 AWG CU
345 27-#16 12.14
QBC00ZC
250 MCM CU
345 21-#14 13.28
QBD00ZC
350 MCM CU
345 28-#14 15.72
QBE00ZC
500 MCM CU
345 26-#12 18.77
QBF00XC
750 MCM CU
345 25-#10 24.59
QBG00XC
1000 MCM CU
345 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

27.41
27.64
28.65
29.87
31.19

29.74
29.97
30.99
32.21
33.53

36.69
36.92
37.94
39.16
40.48

1863
1879
2160
2538
2962

305
305
305
330
330

215
217
248
281
319

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

276
278
316
358
402

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

27.41
27.64
28.65
29.87
31.19
32.59
35.03
38.07
44.15
47.93

29.74
29.97
30.99
32.21
33.53
34.93
37.36
40.41
47.35
51.13

35.17
35.40
36.41
37.63
38.95
41.03
44.89
48.78
56.79
60.58

1486
1502
1701
1951
2269
2638
3405
4530
6561
8226

305
305
305
305
330
330
381
406
457
508

216
216
245
278
314
344
408
480
562
612

0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.18
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.12

1.59
1.60
1.30
1.03
0.80
0.69
0.50
0.34
0.24
0.18

0.12
0.11
0.11
0.10
0.09
0.09
0.08
0.08
0.07
0.07

277
278
311
347
383
408
461
510
572
624

0.45
0.46
0.38
0.32
0.27
0.24
0.20
0.17
0.15
0.13

0.32
0.31
0.30
0.29
0.27
0.26
0.23
0.19
0.16
0.13

1.56
1.57
1.28
1.01
0.79
0.68
0.50
0.34
0.24
0.18

0.12
0.11
0.11
0.10
0.09
0.09
0.08
0.08
0.07
0.07

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 21

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

35kV 133% Aluminum Single Phase Full Neutral


QCP01ZC
1/0 SOLID AL
420 16-#14
8.26
QCQ01ZC
1/0 AWG AL
420 16-#14
8.59
QCR01ZC
2/0 AWG AL
420 13-#12
9.60
QCS01ZC
3/0 AWG AL
420 16-#12 10.82
QCT01ZC
4/0 AWG AL
420 20-#12 12.14
QCU01ZC
250 MCM AL
420 23-#12 13.28
QCV01ZC
350 MCM AL
420 33-#12 15.72
35kV 133% Aluminum Three Phase One-Third Neutral
QCP00ZC
1/0 SOLID AL
420 14-#16
8.26
QCQ00ZC
1/0 AWG AL
420 14-#16
8.59
QCR00ZC
2/0 AWG AL
420 14-#16
9.60
QCS00ZC
3/0 AWG AL
420 15-#16 10.82
QCT00ZC
4/0 AWG AL
420 17-#16 12.14
QCU00ZC
250 MCM AL
420 21-#16 13.28
QCV00ZC
350 MCM AL
420 27-#16 15.72
QCW00ZC
500 MCM AL
420 25-#14 18.80
QCX00ZC
750 MCM AL
420 24-#12 23.11
QCY00ZC
1000 MCM AL
420 31-#12 26.92

(B)

(C)

(D)

90C In Duct

90C Direct Buried

31.37
31.60
32.61
33.83
35.15
36.55
38.99

33.71
33.93
34.95
36.17
37.49
38.89
42.19

39.81
40.04
41.90
44.54
45.86
47.26
50.56

1538
1552
1772
2044
2233
2527
3156

330
330
356
381
381
381
406

168
169
194
220
250
280
331

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.08

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.12
0.11
0.11
0.10
0.10
0.09
0.09

217
218
249
283
321
353
417

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.11
0.11
0.10
0.10
0.10
0.09
0.08

1.36
1.38
1.08
0.86
0.69
0.56
0.42

0.12
0.11
0.11
0.10
0.10
0.09
0.09

31.37
31.60
32.61
33.83
35.15
36.55
38.99
42.06
46.63
50.44

33.71
33.93
34.95
36.17
37.49
38.89
42.19
45.26
49.83
53.64

39.13
39.36
40.38
41.60
44.34
45.74
49.04
52.79
58.21
62.02

1370
1384
1469
1583
1757
1987
2381
2945
3867
4617

330
330
330
356
356
381
406
432
483
508

169
168
191
217
247
270
324
390
474
537

0.68
0.70
0.55
0.44
0.35
0.30
0.21
0.16
0.11
0.09

0.18
0.18
0.18
0.17
0.17
0.16
0.15
0.15
0.14
0.13

1.86
1.88
1.83
1.55
1.33
1.09
0.83
0.58
0.38
0.29

0.12
0.12
0.12
0.11
0.11
0.10
0.09
0.08
0.08
0.07

217
215
244
276
309
335
392
450
521
561

0.71
0.73
0.58
0.47
0.38
0.34
0.26
0.21
0.16
0.15

0.32
0.32
0.31
0.30
0.29
0.28
0.26
0.24
0.20
0.17

1.83
1.85
1.80
1.52
1.31
1.07
0.82
0.57
0.38
0.29

0.12
0.12
0.12
0.11
0.11
0.10
0.09
0.09
0.08
0.07

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 22

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 133%

CSA

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
mm
ula
tio
)
nD
iam
ete
r(
Ins
mm
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
mm
am
ete
)
r(
mm
Ca
)
ble
We
igh
t (k
g/k
M
m)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
mm
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+//km ce
Se
qu
)
Re en
ac ce
tan Im
Ze ce ( peda
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
) e
q
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
A
mp
) e
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
Se
/km ce
qu
)
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
/km nce
S
)
Re eque
sis nc
tan e I
ce mp
Ze
( eda
ro
/km nc
Se
q
) e
Re ue
ac nc
tan e
ce Imp
( ed
/km anc
) e

TRXLPE

Conductor

(A)

35kV 133% Copper Single Phase Full Neutral


QC701ZC
1/0 SOLID CU
420 16-#12
8.26
QC801ZC
1/0 AWG CU
420 16-#12
8.59
QC901ZC
2/0 AWG CU
420 20-#12
9.60
QCA01ZC
3/0 AWG CU
420 26-#12 10.82
QCB01ZC
4/0 AWG CU
420 32-#12 12.14
35kV 133% Copper Three Phase One-Third Neutral
QC700ZC
1/0 SOLID CU
420 14-#16
8.26
QC800ZC
1/0 AWG CU
420 14-#16
8.59
QC900ZC
2/0 AWG CU
420 17-#16
9.60
QCA00ZC
3/0 AWG CU
420 21-#16 10.82
QCB00ZC
4/0 AWG CU
420 27-#16 12.14
QCC00ZC
250 MCM CU
420 21-#14 13.28
QCD00ZC
350 MCM CU
420 28-#14 15.72
QCE00ZC
500 MCM CU
420 26-#12 18.77
QCF00XC
750 MCM CU
420 25-#10 24.59
QCG00XC
1000 MCM CU
420 32-#10 28.37

(B)

(C)

(D)

90C In Duct

90C Direct Buried

31.37
31.60
32.61
33.83
35.15

33.71
33.93
34.95
36.17
37.49

40.66
40.88
41.90
44.54
45.86

2086
2104
2391
2857
3291

330
330
356
381
381

215
217
248
281
319

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

276
278
316
358
402

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

0.84
0.85
0.67
0.53
0.43

0.12
0.11
0.11
0.10
0.10

31.37
31.60
32.61
33.83
35.15
36.55
38.99
42.04
48.11
51.89

33.71
33.93
34.95
36.17
37.49
38.89
42.19
45.24
51.31
55.09

39.13
39.36
40.38
41.60
44.34
46.41
49.71
53.61
60.76
64.54

1701
1718
1923
2180
2586
2970
3745
4898
6901
8588

330
330
330
356
356
381
406
432
508
533

216
216
245
278
314
344
408
480
562
612

0.41
0.42
0.34
0.27
0.22
0.19
0.14
0.11
0.08
0.07

0.18
0.17
0.17
0.16
0.16
0.15
0.15
0.14
0.13
0.12

1.59
1.60
1.30
1.03
0.80
0.69
0.50
0.34
0.24
0.18

0.12
0.11
0.11
0.10
0.09
0.09
0.08
0.08
0.07
0.07

277
278
311
347
383
408
461
510
572
624

0.45
0.46
0.38
0.32
0.27
0.24
0.20
0.17
0.15
0.13

0.32
0.31
0.30
0.29
0.27
0.26
0.23
0.19
0.16
0.13

1.56
1.57
1.28
1.01
0.79
0.68
0.50
0.34
0.24
0.18

0.12
0.11
0.11
0.10
0.09
0.09
0.08
0.08
0.07
0.07

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.


The above dimensions are approximate and subject
to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.
All metric (SI) dimensions are derived from a soft
conversion.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

MEDIUM VOLTAGE
UTILITY

section ii.11 23

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com