Vous êtes sur la page 1sur 17

5-46kV TRXLPE

URD
2012.01.17

Description

Design Parameters

Options

Single conductor cable with aluminum or copper conductors,


triple extruded insulation system consisting of a thermosetting
semiconducting conductor shield, high dielectric strength
VOLTALENE TRXLPE insulation, thermosetting semiconducting
insulation shield, copper concentric neutral wires, black
encapsulating linear low-density polyethylene (LLDPE) jacket.

Conductor
Solid or Class B Compressed concentric strand Aluminum alloy
1350 or soft drawn annealed copper per ASTM.

Black LLDPE jacket with no stripes

Specifications
ICEA

ICEA S-94-649

AEIC

AEIC CS8

Ratings

For 90C continuous, 130C emergency, 250C short-circuit operation.

Conductor Shield
Extruded thermosetting semiconducting shield which is free
stripping from the conductor and bonded to the insulation.
Insulation
Natural high dielectric strength VOLTALENE TRXLPE
insulation, exhibiting an optimum balance of mechanical
and electrical properties, insuring resistance to treeing.
Insulation Shield
Extruded thermosetting semiconducting shield with controlled
adhesion to the insulation providing the required balance
between electrical integrity and ease of stripping.
Metallic Shield
Solid bare copper wires, helically applied and uniformly spaced.
Jacket
Black insulating sunlight resistant linear low density
polyethylene encapsulating the neutral wires with three
extruded red stripes and NESC lightning bolt symbol.

MEDIUM VOLTAGE
UTILITY

section ii.1 1

Prysmian Power Cables and Systems


www.prysmianusa.com
www.prysmiancanada.com

Black PVC jacket sleeved over separator tape


No jacket
Multiplex cables
Tinned round or flat strap neutrals
Strandseal
Compact stranded conductors
Super smooth conductor shield
UL MV-90 Rating if Required
46kV
REA/RUS U-1 where applicable

Installations
Conduit in Air

Direct Buried

Underground Duct

Isolated in Air

Wet Locations

Dry Locations

With Messenger

Utility Primary

United States: 700 Industrial Drive Lexington, South Carolina 29072


Canada: 137 Commerce Drive R. R #3 Prescott, Ontario K0E1T0
1-800-845-8507 (US) 1-800-263-4405 (West-CAN) 1-800-361-1418 (East-CAN)

Product Number

URD

5kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

5kV 100% Aluminum Single Phase - Full Neutral


Q4L010A
2 SOLID AL
90
10-#14 0.258
Q4M010A
2 AWG AL
90
10-#14 0.284
Q4N010A
1 SOLID AL
90
13-#14 0.289
Q4O010A
1 AWG AL
90
13-#14 0.324
Q4P010A
1/0 SOLID AL
90
16-#14 0.325
Q4Q010A
1/0 AWG AL
90
16-#14 0.364
Q4R010A
2/0 AWG AL
90
13-#12 0.408
Q4S010A
3/0 AWG AL
90
16-#12 0.458
Q4T010A
4/0 AWG AL
90
13-#10 0.515
Q4U010A
250 MCM AL
90
16-#10 0.561
Q4V010A
350 MCM AL
90
16-#9 0.664
5kV 100% Aluminum Three Phase - One-Third Neutral
Q4L000A
2 SOLID AL
90
6-#14 0.258
Q4M000A
2 AWG AL
90
6-#14 0.284
Q4N000A
1 SOLID AL
90
6-#14 0.289
Q4O000A
1 AWG AL
90
6-#14 0.324
Q4P000A
1/0 SOLID AL
90
6-#14 0.325
Q4Q000A
1/0 AWG AL
90
6-#14 0.364
Q4R000A
2/0 AWG AL
90
7-#14 0.408
Q4S000A
3/0 AWG AL
90
9-#14 0.458
Q4T000A
4/0 AWG AL
90
11-#14 0.515
Q4U000A
250 MCM AL
90
13-#14 0.561
Q4V000A
350 MCM AL
90
18-#14 0.664
Q4W000A
500 MCM AL
90
16-#12 0.794
Q4X000A
750 MCM AL
90
24-#12 0.974
Q4Y000A
1000 MCM AL
90
20-#10 1.124

(B)

(C)

(D)

0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.80
0.90

0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.86
0.97

0.79
0.82
0.82
0.86
0.86
0.90
0.97
1.02
1.12
1.18
1.30

360
375
422
439
490
509
627
736
914
1076
1362

7
7
7
7
7
8
8
9
9
10
11

119
120
136
138
155
156
181
206
237
264
314

663
669
518
523
415
420
328
263
207
171
130

24
25
23
22
22
21
21
20
19
18
17

663
669
518
523
415
420
328
263
207
171
130

25
25
23
22
22
21
20
19
19
18
17

169
170
193
195
219
220
251
285
323
358
421

663
669
518
523
415
420
328
263
207
171
130

24
25
23
22
22
21
21
20
19
18
17

663
669
518
523
415
420
328
263
207
171
130

25
25
23
22
22
21
20
19
19
18
17

0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.80
0.90
1.03
1.22
1.37

0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.86
0.97
1.12
1.30
1.45

0.79
0.82
0.82
0.86
0.86
0.90
0.94
0.99
1.05
1.10
1.20
1.39
1.58
1.83

313
329
340
357
373
393
447
522
608
693
887
1219
1691
2255

7
7
7
7
7
8
8
8
9
9
10
12
13
15

123
123
140
140
159
160
182
208
237
261
314
381
464
522

329
335
261
266
207
212
168
133
107
91
66
48
34
29

46
46
45
44
43
42
40
39
38
37
35
34
32
31

876
883
809
815
756
762
640
500
407
344
249
175
117
89

25
25
23
22
22
21
20
19
18
17
15
15
14
13

178
179
202
203
229
229
258
290
323
348
399
449
505
541

340
346
272
276
217
222
179
146
122
107
86
70
58
51

103
102
100
98
98
96
93
89
85
82
75
66
54
45

864
872
798
804
746
752
632
495
403
342
247
174
117
88

25
25
23
22
22
21
20
19
18
17
15
15
14
13

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 2

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

5kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

5kV 100% Copper Single Phase - Full Neutral


Q43010A
2 SOLID CU
90
16-#14 0.258
Q44010A
2 AWG CU
90
16-#14 0.284
Q45010A
1 SOLID CU
90
13-#12 0.289
Q46010A
1 AWG CU
90
13-#12 0.324
Q47010A
1/0 SOLID CU
90
16-#12 0.325
Q48010A
1/0 AWG CU
90
16-#12 0.364
Q49010A
2/0 AWG CU
90
13-#10 0.408
Q4A010A
3/0 AWG CU
90
16-#10 0.458
Q4B010A
4/0 AWG CU
90
16-#9 0.515
5kV 100% Copper Three Phase - One-Third Neutral
Q43000A
2 SOLID CU
90
6-#14 0.258
Q44000A
2 AWG CU
90
6-#14 0.284
Q45000A
1 SOLID CU
90
7-#14 0.289
Q46000A
1 AWG CU
90
7-#14 0.324
Q47000A
1/0 SOLID CU
90
9-#14 0.325
Q48000A
1/0 AWG CU
90
9-#14 0.364
Q49000A
2/0 AWG CU
90
11-#14 0.408
Q4A000A
3/0 AWG CU
90
14-#14 0.458
Q4B000A
4/0 AWG CU
90
18-#14 0.515
Q4C000A
250 MCM CU
90
21-#14 0.561
Q4D000A
350 MCM CU
90
18-#12 0.664
Q4E000A
500 MCM CU
90
17-#10 0.794
Q4F000A
750 MCM CU
90
20-#9 0.974
Q4G000A
1000 MCM CU
90
21-#8 1.124

(B)

(C)

(D)

0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74

0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81

0.79
0.82
0.85
0.89
0.89
0.93
1.02
1.07
1.15

570
584
704
724
841
862
1076
1291
1590

7
7
7
8
8
8
9
9
10

152
153
175
176
198
200
231
262
300

408
412
318
322
256
258
203
163
130

25
25
24
23
23
22
22
20
20

408
412
318
322
256
258
203
163
130

25
25
24
23
22
22
21
20
19

215
217
245
247
277
280
317
359
407

408
412
318
322
256
258
203
163
130

25
25
24
23
23
22
22
20
20

408
412
318
322
256
258
203
163
130

25
25
24
23
22
22
21
20
19

0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.80
0.90
1.03
1.22
1.37

0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.86
0.97
1.12
1.30
1.45

0.79
0.82
0.82
0.86
0.86
0.90
0.94
0.99
1.05
1.10
1.24
1.43
1.70
1.88

453
468
527
545
630
651
775
934
1136
1317
1780
2521
3718
4847

7
7
7
7
7
8
8
8
9
9
10
12
14
16

157
158
179
180
204
205
233
265
301
330
393
464
540
586

200
203
159
162
126
129
103
82
66
57
42
32
26
23

46
46
44
44
43
42
40
39
38
36
35
34
35
29

747
752
628
633
492
495
402
317
248
212
154
105
72
54

25
25
23
22
22
21
20
19
18
17
16
15
14
13

227
228
256
256
286
287
320
353
385
409
452
494
552
607

211
214
171
174
141
143
119
101
88
80
68
58
48
41

103
102
100
98
96
94
90
85
79
75
65
53
40
31

735
740
619
624
485
489
398
314
247
211
154
104
71
53

25
25
23
22
22
21
20
19
18
17
16
15
14
13

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 3

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

5kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

5kV 133% Aluminum Single Phase - Full Neutral


Q5L010A
2 SOLID AL
115
10-#14 0.258
Q5M010A
2 AWG AL
115
10-#14 0.284
Q5N010A
1 SOLID AL
115
13-#14 0.289
Q5O010A
1 AWG AL
115
13-#14 0.324
Q5P010A
1/0 SOLID AL
115
16-#14 0.325
Q5Q010A
1/0 AWG AL
115
16-#14 0.364
Q5R010A
2/0 AWG AL
115
13-#12 0.408
Q5S010A
3/0 AWG AL
115
16-#12 0.458
Q5T010A
4/0 AWG AL
115
13-#10 0.515
Q5U010A
250 MCM AL
115
16-#10 0.561
Q5V010A
350 MCM AL
115
16-#9 0.664
5kV 133% Aluminum Three Phase - One-Third Neutral
Q5L000A
2 SOLID AL
115
6-#14 0.258
Q5M000A
2 AWG AL
115
6-#14 0.284
Q5N000A
1 SOLID AL
115
6-#14 0.289
Q5O000A
1 AWG AL
115
6-#14 0.324
Q5P000A
1/0 SOLID AL
115
6-#14 0.325
Q5Q000A
1/0 AWG AL
115
6-#14 0.364
Q5R000A
2/0 AWG AL
115
7-#14 0.408
Q5S000A
3/0 AWG AL
115
9-#14 0.458
Q5T000A
4/0 AWG AL
115
11-#14 0.515
Q5U000A
250 MCM AL
115
13-#14 0.561
Q5V000A
350 MCM AL
115
18-#14 0.664
Q5W000A
500 MCM AL
115
16-#12 0.794
Q5X000A
750 MCM AL
115
24-#12 0.974
Q5Y000A
1000 MCM AL
115
20-#10 1.124

(B)

(C)

(D)

0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.85
0.95

0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.91
1.02

0.84
0.87
0.87
0.91
0.91
0.95
1.02
1.07
1.17
1.23
1.35

386
402
449
467
518
539
659
769
951
1115
1405

7
7
7
8
8
8
9
9
10
10
11

119
120
136
138
155
156
181
206
237
264
314

663
669
518
523
415
420
328
263
207
171
130

24
25
23
22
22
21
21
20
19
18
17

663
669
518
523
415
420
328
263
207
171
130

25
25
23
22
22
21
20
19
19
18
17

169
170
193
195
219
220
251
285
323
358
421

663
669
518
523
415
420
328
263
207
171
130

24
25
23
22
22
21
21
20
19
18
17

663
669
518
523
415
420
328
263
207
171
130

25
25
23
22
22
21
20
19
19
18
17

0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.85
0.95
1.08
1.27
1.42

0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.91
1.02
1.17
1.35
1.50

0.84
0.87
0.87
0.91
0.91
0.95
0.99
1.04
1.10
1.15
1.25
1.44
1.63
1.88

339
356
367
385
401
422
478
554
642
729
926
1264
1742
2314

7
7
7
8
8
8
8
9
9
10
11
12
14
16

123
123
140
140
159
160
182
208
237
261
314
381
464
522

329
335
261
266
207
212
168
133
107
91
66
48
34
29

46
46
45
44
43
42
40
39
38
37
35
34
32
31

876
883
809
815
756
762
640
500
407
344
249
175
117
89

25
25
23
22
22
21
20
19
18
17
15
15
14
13

178
179
202
203
229
229
258
290
323
348
399
449
505
541

340
346
272
276
217
222
179
146
122
107
86
70
58
51

103
102
100
98
98
96
93
89
85
82
75
66
54
45

864
872
798
804
746
752
632
495
403
342
247
174
117
88

25
25
23
22
22
21
20
19
18
17
15
15
14
13

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 4

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

5kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

5kV 133% Copper Single Phase - Full Neutral


Q53010A
2 SOLID CU
115
16-#14 0.258
Q54010A
2 AWG CU
115
16-#14 0.284
Q55010A
1 SOLID CU
115
13-#12 0.289
Q56010A
1 AWG CU
115
13-#12 0.324
Q57010A
1/0 SOLID CU
115
16-#12 0.325
Q58010A
1/0 AWG CU
115
16-#12 0.364
Q59010A
2/0 AWG CU
115
13-#10 0.408
Q5A010A
3/0 AWG CU
115
16-#10 0.458
Q5B010A
4/0 AWG CU
115
16-#9 0.515
5kV 133% Copper Three Phase - One-Third Neutral
Q53000A
2 SOLID CU
115
6-#14 0.258
Q54000A
2 AWG CU
115
6-#14 0.284
Q55000A
1 SOLID CU
115
7-#14 0.289
Q56000A
1 AWG CU
115
7-#14 0.324
Q57000A
1/0 SOLID CU
115
9-#14 0.325
Q58000A
1/0 AWG CU
115
9-#14 0.364
Q59000A
2/0 AWG CU
115
11-#14 0.408
Q5A000A
3/0 AWG CU
115
14-#14 0.458
Q5B000A
4/0 AWG CU
115
18-#14 0.515
Q5C000A
250 MCM CU
115
21-#14 0.561
Q5D000A
350 MCM CU
115
18-#12 0.664
Q5E000A
500 MCM CU
115
17-#10 0.794
Q5F000A
750 MCM CU
115
20-#9 0.974
Q5G000A
1000 MCM CU
115
21-#8 1.124

(B)

(C)

(D)

0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79

0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86

0.84
0.87
0.90
0.94
0.94
0.98
1.07
1.12
1.20

596
611
732
753
871
893
1109
1326
1628

7
7
8
8
8
8
9
9
10

152
153
175
176
198
200
231
262
300

408
412
318
322
256
258
203
163
130

25
25
24
23
23
22
22
20
20

408
412
318
322
256
258
203
163
130

25
25
24
23
22
22
21
20
19

215
217
245
247
277
280
317
359
407

408
412
318
322
256
258
203
163
130

25
25
24
23
23
22
22
20
20

408
412
318
322
256
258
203
163
130

25
25
24
23
22
22
21
20
19

0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.85
0.95
1.08
1.27
1.42

0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.91
1.02
1.17
1.35
1.50

0.84
0.87
0.87
0.91
0.91
0.95
0.99
1.04
1.10
1.15
1.29
1.48
1.75
1.93

479
495
554
573
659
680
805
967
1171
1353
1820
2567
3773
4908

7
7
7
8
8
8
8
9
9
10
11
12
15
16

157
158
179
180
204
205
233
265
301
330
393
464
540
586

200
203
159
162
126
129
103
82
66
57
42
32
26
23

46
46
44
44
43
42
40
39
38
36
35
34
35
29

747
752
628
633
492
495
402
317
248
212
154
105
72
54

25
25
23
22
22
21
20
19
18
17
16
15
14
13

227
228
256
256
286
287
320
353
385
409
452
494
552
607

211
214
171
174
141
143
119
101
88
80
68
58
48
41

103
102
100
98
96
94
90
85
79
75
65
53
40
31

735
740
619
624
485
489
398
314
247
211
154
104
71
53

25
25
23
22
22
21
20
19
18
17
16
15
14
13

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 5

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

15kV 100% Aluminum Single Phase - Full Neutral


Q7L010A
2 SOLID AL
175
10-#14 0.258
Q7M010A
2 AWG AL
175
10-#14 0.284
Q7N010A
1 SOLID AL
175
13-#14 0.289
Q7O010A
1 AWG AL
175
13-#14 0.324
Q7P010A
1/0 SOLID AL
175
16-#14 0.325
Q7Q010A
1/0 AWG AL
175
16-#14 0.364
Q7R010A
2/0 AWG AL
175
13-#12 0.408
Q7S010A
3/0 AWG AL
175
16-#12 0.458
Q7T010A
4/0 AWG AL
175
13-#10 0.515
Q7U010A
250 MCM AL
175
16-#10 0.561
Q7V010A
350 MCM AL
175
16-#9 0.664
15kV 100% Aluminum Three Phase - One-Third Neutral
Q7L000A
2 SOLID AL
175
6-#14 0.258
Q7M000A
2 AWG AL
175
6-#14 0.284
Q7N000A
1 SOLID AL
175
6-#14 0.289
Q7O000A
1 AWG AL
175
6-#14 0.324
Q7P000A
1/0 SOLID AL
175
6-#14 0.325
Q7Q000A
1/0 AWG AL
175
6-#14 0.364
Q7R000A
2/0 AWG AL
175
7-#14 0.408
Q7S000A
3/0 AWG AL
175
9-#14 0.458
Q7T000A
4/0 AWG AL
175
11-#14 0.515
Q7U000A
250 MCM AL
175
13-#14 0.561
Q7V000A
350 MCM AL
175
18-#14 0.664
Q7W000A
500 MCM AL
175
16-#12 0.794
Q7X000A
750 MCM AL
175
24-#12 0.974
Q7Y000A
1000 MCM AL
175
20-#10 1.124

(B)

(C)

(D)

90C In Duct

90C Direct Buried

0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.97
1.07

0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
1.03
1.16

0.96
0.99
0.99
1.03
1.03
1.07
1.14
1.19
1.29
1.35
1.49

455
473
520
541
592
616
742
856
1046
1214
1536

8
8
8
9
9
9
10
10
11
11
12

123
124
141
143
160
162
186
212
243
270
321

663
669
518
523
415
420
328
263
207
171
130

29
30
28
27
27
26
25
24
23
22
21

663
669
518
523
415
420
328
263
207
171
130

30
31
29
28
27
26
25
24
23
22
20

169
170
193
194
219
220
251
284
323
358
420

663
669
518
523
415
420
328
263
207
171
130

29
30
28
27
27
26
25
24
23
22
21

663
669
518
523
415
420
328
263
207
171
130

30
31
29
28
27
26
25
24
23
22
20

0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.97
1.07
1.20
1.39
1.54

0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
1.03
1.16
1.29
1.47
1.65

0.96
0.99
0.99
1.03
1.03
1.07
1.11
1.16
1.22
1.27
1.39
1.56
1.81
2.03

409
427
439
459
475
499
558
638
730
821
1048
1378
1938
2507

8
8
8
9
9
9
9
10
10
11
12
13
15
17

126
126
143
144
163
163
186
212
241
265
319
385
468
529

329
335
261
266
207
212
168
133
106
91
66
48
35
28

51
51
49
48
47
46
44
43
41
40
38
37
35
33

872
879
805
811
752
758
637
498
405
343
247
174
117
89

30
31
29
28
27
26
25
24
23
21
19
18
16
16

175
175
199
199
225
225
255
286
320
345
398
451
507
549

338
344
270
275
216
221
178
145
120
106
84
68
57
49

103
102
100
98
98
96
93
89
86
82
76
67
55
47

857
865
791
798
739
745
627
491
400
339
245
173
116
88

30
31
29
28
27
26
25
24
23
21
19
18
16
16

Ampacities are based on the following:

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 6

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

15kV 100% Copper Single Phase - Full Neutral


2 SOLID CU
175
16-#14 0.258
2 AWG CU
175
16-#14 0.284
1 SOLID CU
175
13-#12 0.289
1 AWG CU
175
13-#12 0.324
1/0 SOLID CU
175
16-#12 0.325
1/0 AWG CU
175
16-#12 0.364
2/0 AWG CU
175
13-#10 0.408
3/0 AWG CU
175
16-#10 0.458
4/0 AWG CU
175
16-#9 0.515
15kV 100% Copper Three Phase - One-Third Neutral
Q73000A
2 SOLID CU
175
6-#14 0.258
Q74000A
2 AWG CU
175
6-#14 0.284
Q75000A
1 SOLID CU
175
7-#14 0.289
Q76000A
1 AWG CU
175
7-#14 0.324
Q77000A
1/0 SOLID CU
175
9-#14 0.325
Q78000A
1/0 AWG CU
175
9-#14 0.364
Q79000A
2/0 AWG CU
175
11-#14 0.408
Q7A000A
3/0 AWG CU
175
14-#14 0.458
Q7B000A
4/0 AWG CU
175
18-#14 0.515
Q7C000A
250 MCM CU
175
21-#14 0.561
Q7D000A
350 MCM CU
175
18-#12 0.664
Q7E000A
500 MCM CU
175
17-#10 0.794
Q7F000A
750 MCM CU
175
20-#9 0.974
Q7G000A
1000 MCM CU
175
21-#8 1.124
Q73010A
Q74010A
Q75010A
Q76010A
Q77010A
Q78010A
Q79010A
Q7A010A
Q7B010A

(B)

(C)

(D)

0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91

0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98

0.96
0.99
1.02
1.06
1.06
1.10
1.19
1.24
1.32

665
682
807
830
948
973
1196
1417
1724

8
8
9
9
9
9
10
10
11

157
158
181
182
205
207
237
270
307

408
412
318
322
256
258
203
163
130

31
31
29
28
28
27
26
25
23

408
412
318
322
256
258
203
163
130

30
31
29
28
28
27
26
24
23

215
217
245
246
277
279
317
359
407

408
412
318
322
256
258
203
163
130

31
31
29
28
28
27
26
25
23

408
412
318
322
256
258
203
163
130

30
31
29
28
28
27
26
24
23

0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.97
1.07
1.20
1.39
1.54

0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
1.03
1.16
1.29
1.47
1.65

0.96
0.99
0.99
1.03
1.03
1.07
1.11
1.16
1.22
1.27
1.43
1.60
1.87
2.08

548
566
625
647
733
757
886
1051
1259
1445
1945
2685
3912
5107

8
8
8
9
9
9
9
10
10
11
12
13
15
17

162
162
184
184
209
210
238
271
307
336
400
471
548
596

200
203
159
162
126
129
103
82
66
57
42
32
26
23

51
51
49
48
47
46
44
43
41
40
38
36
34
32

743
747
625
629
489
492
400
316
247
211
154
104
71
54

30
31
29
28
27
26
25
23
22
21
20
18
17
16

223
224
252
252
283
284
317
351
385
410
457
501
559
669

209
213
169
173
139
141
117
99
86
78
66
57
47
41

103
102
100
98
96
94
91
86
81
76
67
55
42
35

728
733
613
618
481
484
395
312
245
210
153
104
71
56

30
31
29
28
27
26
25
23
22
21
20
18
17
16

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 7

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

15kV 133% Aluminum Single Phase - Full Neutral


Q8L010A
2 SOLID AL
220
10-#14 0.258
Q8M010A
2 AWG AL
220
10-#14 0.284
Q8N010A
1 SOLID AL
220
13-#14 0.289
Q8O010A
1 AWG AL
220
13-#14 0.324
Q8P010A
1/0 SOLID AL
220
16-#14 0.325
Q8Q010A
1/0 AWG AL
220
16-#14 0.364
Q8R010A
2/0 AWG AL
220
13-#12 0.408
Q8S010A
3/0 AWG AL
220
16-#12 0.458
Q8T010A
4/0 AWG AL
220
13-#10 0.515
Q8U010A
250 MCM AL
220
16-#10 0.561
Q8V010A
350 MCM AL
220
16-#9 0.664
15kV 133% Aluminum Three Phase - One-Third Neutral
Q8L000A
2 SOLID AL
220
6-#14 0.258
Q8M000A
2 AWG AL
220
6-#14 0.284
Q8N000A
1 SOLID AL
220
6-#14 0.289
Q8O000A
1 AWG AL
220
6-#14 0.324
Q8P000A
1/0 SOLID AL
220
6-#14 0.325
Q8Q000A
1/0 AWG AL
220
6-#14 0.364
Q8R000A
2/0 AWG AL
220
7-#14 0.408
Q8S000A
3/0 AWG AL
220
9-#14 0.458
Q8T000A
4/0 AWG AL
220
11-#14 0.515
Q8U000A
250 MCM AL
220
13-#14 0.561
Q8V000A
350 MCM AL
220
18-#14 0.664
Q8W000A
500 MCM AL
220
16-#12 0.794
Q8X000A
750 MCM AL
220
24-#12 0.974
Q8Y000A
1000 MCM AL
220
20-#10 1.124

(B)

(C)

(D)

0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
1.06
1.16

0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.14
1.25

1.05
1.08
1.08
1.12
1.12
1.16
1.23
1.28
1.38
1.46
1.58

513
533
580
603
654
680
811
927
1122
1315
1624

9
9
9
9
9
10
10
11
12
12
13

123
124
141
143
160
162
186
212
243
270
321

663
669
518
523
415
420
328
263
207
171
130

29
30
28
27
27
26
25
24
23
22
21

663
669
518
523
415
420
328
263
207
171
130

30
31
29
28
27
26
25
24
23
22
20

169
170
193
194
219
220
251
284
323
358
420

663
669
518
523
415
420
328
263
207
171
130

29
30
28
27
27
26
25
24
23
22
21

663
669
518
523
415
420
328
263
207
171
130

30
31
29
28
27
26
25
24
23
22
20

0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
1.06
1.16
1.29
1.48
1.63

0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.14
1.25
1.38
1.56
1.74

1.05
1.08
1.08
1.12
1.12
1.16
1.20
1.25
1.31
1.38
1.48
1.71
1.90
2.12

466
486
498
521
537
563
624
707
803
917
1130
1534
2043
2626

9
9
9
9
9
10
10
11
11
12
12
14
16
17

126
126
143
144
163
163
186
212
241
265
319
385
468
529

329
335
261
266
207
212
168
133
106
91
66
48
35
28

51
51
49
48
47
46
44
43
41
40
38
37
35
33

872
879
805
811
752
758
637
498
405
343
247
174
117
89

30
31
29
28
27
26
25
24
23
21
19
18
16
16

175
175
199
199
225
225
255
286
320
345
398
451
507
549

338
344
270
275
216
221
178
145
120
106
84
68
57
49

103
102
100
98
98
96
93
89
86
82
76
67
55
47

857
865
791
798
739
745
627
491
400
339
245
173
116
88

30
31
29
28
27
26
25
24
23
21
19
18
16
16

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 8

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

15kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

15kV 133% Copper Single Phase - Full Neutral


Q83010A
2 SOLID CU
220
16-#14 0.258
Q84010A
2 AWG CU
220
16-#14 0.284
Q85010A
1 SOLID CU
220
13-#12 0.289
Q86010A
1 AWG CU
220
13-#12 0.324
Q87010A
1/0 SOLID CU
220
16-#12 0.325
Q88010A
1/0 AWG CU
220
16-#12 0.364
Q89010A
2/0 AWG CU
220
13-#10 0.408
Q8A010A
3/0 AWG CU
220
16-#10 0.458
Q8B010A
4/0 AWG CU
220
16-#9 0.515
15kV 133% Copper Three Phase - One-Third Neutral
Q83000A
2 SOLID CU
220
6-#14 0.258
Q84000A
2 AWG CU
220
6-#14 0.284
Q85000A
1 SOLID CU
220
7-#14 0.289
Q86000A
1 AWG CU
220
7-#14 0.324
Q87000A
1/0 SOLID CU
220
9-#14 0.325
Q88000A
1/0 AWG CU
220
9-#14 0.364
Q89000A
2/0 AWG CU
220
11-#14 0.408
Q8A000A
3/0 AWG CU
220
14-#14 0.458
Q8B000A
4/0 AWG CU
220
18-#14 0.515
Q8C000A
250 MCM CU
220
21-#14 0.561
Q8D000A
350 MCM CU
220
18-#12 0.664
Q8E000A
500 MCM CU
220
17-#10 0.794
Q8F000A
750 MCM CU
220
20-#9 0.974
Q8G000A
1000 MCM CU
220
21-#8 1.124

(B)

(C)

(D)

0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00

0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07

1.05
1.08
1.11
1.15
1.15
1.19
1.28
1.33
1.41

723
742
868
893
1011
1039
1266
1490
1803

9
9
9
10
10
10
11
11
12

157
158
181
182
205
207
237
270
307

408
412
318
322
256
258
203
163
130

31
31
29
28
28
27
26
25
23

408
412
318
322
256
258
203
163
130

30
31
29
28
28
27
26
24
23

215
217
245
246
277
279
317
359
407

408
412
318
322
256
258
203
163
130

31
31
29
28
28
27
26
25
23

408
412
318
322
256
258
203
163
130

30
31
29
28
28
27
26
24
23

0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
1.06
1.16
1.29
1.48
1.63

0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.14
1.25
1.38
1.56
1.74

1.05
1.08
1.08
1.12
1.12
1.16
1.20
1.25
1.31
1.38
1.52
1.75
1.96
2.17

606
625
685
709
794
821
952
1120
1331
1541
2029
2845
4022
5229

9
9
9
9
9
10
10
11
11
12
13
14
16
18

162
162
184
184
209
210
238
271
307
336
400
471
548
596

200
203
159
162
126
129
103
82
66
57
42
32
26
23

51
51
49
48
47
46
44
43
41
40
38
36
34
32

743
747
625
629
489
492
400
316
247
211
154
104
71
54

30
31
29
28
27
26
25
23
22
21
20
18
17
16

223
224
252
252
283
284
317
351
385
410
457
501
559
669

209
213
169
173
139
141
117
99
86
78
66
57
47
41

103
102
100
98
96
94
91
86
81
76
67
55
42
35

728
733
613
618
481
484
395
312
245
210
153
104
71
56

30
31
29
28
27
26
25
23
22
21
20
18
17
16

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 9

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

25kV 100% Aluminum Single Phase - Full Neutral


Q9N010A
1 SOLID AL
260
13-#14 0.289
Q9O010A
1 AWG AL
260
13-#14 0.324
Q9P010A
1/0 SOLID AL
260
16-#14 0.325
Q9Q010A
1/0 AWG AL
260
16-#14 0.364
Q9R010A
2/0 AWG AL
260
13-#12 0.408
Q9S010A
3/0 AWG AL
260
16-#12 0.458
Q9T010A
4/0 AWG AL
260
13-#10 0.515
Q9U010A
250 MCM AL
260
16-#10 0.561
Q9V010A
350 MCM AL
260
16-#9 0.664
25kV 100% Aluminum Three Phase - One-Third Neutral
Q9N000A
1 SOLID AL
260
6-#14 0.289
Q9O000A
1 AWG AL
260
6-#14 0.324
Q9P000A
1/0 SOLID AL
260
6-#14 0.325
Q9Q000A
1/0 AWG AL
260
6-#14 0.364
Q9R000A
2/0 AWG AL
260
7-#14 0.408
Q9S000A
3/0 AWG AL
260
9-#14 0.458
Q9T000A
4/0 AWG AL
260
11-#14 0.515
Q9U000A
250 MCM AL
260
13-#14 0.561
Q9V000A
350 MCM AL
260
18-#14 0.664
Q9W000A
500 MCM AL
260
16-#12 0.794
Q9X000A
750 MCM AL
260
24-#12 0.974
Q9Y000A
1000 MCM AL
260
20-#10 1.124

(B)

(C)

(D)

0.86
0.89
0.89
0.93
0.97
1.02
1.08
1.14
1.24

0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.22
1.33

1.16
1.20
1.20
1.24
1.31
1.38
1.48
1.54
1.72

637
662
713
741
875
1015
1217
1392
1772

10
10
10
10
11
12
12
13
14

145
146
165
166
190
217
248
276
326

518
523
415
420
328
263
207
171
130

33
31
31
30
29
28
26
25
23

518
523
415
420
328
263
207
171
130

33
32
31
30
29
28
27
25
23

192
194
218
219
250
283
322
356
416

518
523
415
420
328
263
207
171
130

33
31
31
30
29
28
26
25
23

518
523
415
420
328
263
207
171
130

33
32
31
30
29
28
27
25
23

0.86
0.89
0.89
0.93
0.97
1.02
1.08
1.14
1.24
1.37
1.56
1.71

0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.22
1.33
1.46
1.67
1.82

1.16
1.20
1.20
1.24
1.28
1.35
1.41
1.46
1.56
1.79
2.01
2.20

555
580
596
624
687
793
892
990
1208
1623
2187
2736

10
10
10
10
11
11
12
12
13
15
17
18

146
146
166
166
189
216
245
269
322
389
473
533

261
266
207
212
168
133
106
90
66
48
34
28

53
52
51
50
48
46
45
43
41
40
37
35

801
807
748
754
634
495
403
341
246
173
116
88

33
32
31
30
29
27
26
25
23
21
19
18

196
196
222
222
251
283
317
343
397
451
513
555

269
274
215
220
177
144
119
104
82
67
55
48

101
99
98
96
93
90
86
83
76
68
57
49

786
792
734
740
622
487
397
337
244
172
116
88

33
32
31
30
29
27
26
25
23
21
19
18

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 10

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

25kV 100% Copper Single Phase - Full Neutral


Q95010A
1 SOLID CU
260
13-#12 0.289
Q96010A
1 AWG CU
260
13-#12 0.324
Q97010A
1/0 SOLID CU
260
16-#12 0.325
Q98010A
1/0 AWG CU
260
16-#12 0.364
Q99010A
2/0 AWG CU
260
13-#10 0.408
Q9A010A
3/0 AWG CU
260
16-#10 0.458
Q9B010A
4/0 AWG CU
260
16-#9 0.515
25kV 100% Copper Three Phase - One-Third Neutral
Q95000A
1 SOLID CU
260
7-#14 0.289
Q96000A
1 AWG CU
260
7-#14 0.324
Q97000A
1/0 SOLID CU
260
9-#14 0.325
Q98000A
1/0 AWG CU
260
9-#14 0.364
Q99000A
2/0 AWG CU
260
11-#14 0.408
Q9A000A
3/0 AWG CU
260
14-#14 0.458
Q9B000A
4/0 AWG CU
260
18-#14 0.515
Q9C000A
250 MCM CU
260
21-#14 0.561
Q9D000A
350 MCM CU
260
18-#12 0.664
Q9E000A
500 MCM CU
260
17-#10 0.794
Q9F000A
750 MCM CU
260
20-#9 0.974
Q9G000A
1000 MCM CU
260
21-#8 1.124

(B)

(C)

(D)

0.86
0.89
0.89
0.93
0.97
1.02
1.08

0.92
0.96
0.96
1.00
1.04
1.11
1.17

1.19
1.23
1.23
1.27
1.36
1.43
1.51

927
954
1072
1101
1333
1581
1899

10
10
10
11
11
12
13

186
187
210
212
243
276
314

318
322
256
258
203
163
130

33
32
32
31
29
28
27

318
322
256
258
203
163
130

34
32
32
31
29
28
27

245
246
277
279
317
359
406

318
322
256
258
203
163
130

33
32
32
31
29
28
27

318
322
256
258
203
163
130

34
32
32
31
29
28
27

0.86
0.89
0.89
0.93
0.97
1.02
1.08
1.14
1.24
1.37
1.56
1.71

0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.22
1.33
1.46
1.67
1.82

1.16
1.20
1.20
1.24
1.28
1.35
1.41
1.46
1.60
1.83
2.07
2.25

742
768
853
882
1015
1206
1421
1614
2109
2936
4170
5342

10
10
10
10
11
11
12
12
13
15
17
19

187
187
213
213
242
275
311
341
405
475
556
603

158
162
126
129
103
82
66
56
42
32
25
22

53
52
51
50
48
46
45
43
41
39
36
34

622
626
487
490
398
314
246
210
153
104
71
54

33
32
31
30
29
27
26
25
23
21
20
18

249
249
280
281
314
349
384
410
460
504
567
620

168
172
138
140
116
98
84
76
64
55
45
39

100
98
97
95
91
87
82
78
69
57
45
37

609
614
478
481
392
310
243
208
152
104
71
53

33
32
31
30
29
27
26
25
23
21
20
18

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 11

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

25kV 133% Aluminum Single Phase - Full Neutral


QAN010A
1 SOLID AL
320
13-#14 0.289
QAO010A
1 AWG AL
320
13-#14 0.324
QAP010A
1/0 SOLID AL
320
16-#14 0.325
QAQ010A
1/0 AWG AL
320
16-#14 0.364
QAR010A
2/0 AWG AL
320
13-#12 0.408
QAS010A
3/0 AWG AL
320
16-#12 0.458
QAT010A
4/0 AWG AL
320
13-#10 0.515
QAU010A
250 MCM AL
320
16-#10 0.561
QAV010A
350 MCM AL
320
16-#9 0.664
25kV 133% Aluminum Three Phase - One-Third Neutral
QAN000A
1 SOLID AL
320
6-#14 0.289
QAO000A
1 AWG AL
320
6-#14 0.324
QAP000A
1/0 SOLID AL
320
6-#14 0.325
QAQ000A
1/0 AWG AL
320
6-#14 0.364
QAR000A
2/0 AWG AL
320
7-#14 0.408
QAS000A
3/0 AWG AL
320
9-#14 0.458
QAT000A
4/0 AWG AL
320
11-#14 0.515
QAU000A
250 MCM AL
320
13-#14 0.561
QAV000A
350 MCM AL
320
18-#14 0.664
QAW000A
500 MCM AL
320
16-#12 0.794
QAX000A
750 MCM AL
320
24-#12 0.974
QAY000A
1000 MCM AL
320
20-#10 1.124

(B)

(C)

(D)

0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.26
1.36

1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.35
1.45

1.29
1.32
1.32
1.38
1.46
1.51
1.61
1.72
1.85

734
761
812
864
1006
1129
1339
1583
1913

11
11
11
12
12
13
13
14
15

145
146
165
166
190
217
248
276
326

518
523
415
420
328
263
207
171
130

33
31
31
30
29
28
26
25
23

518
523
415
420
328
263
207
171
130

33
32
31
30
29
28
27
25
23

192
194
218
219
250
283
322
356
416

518
523
415
420
328
263
207
171
130

33
31
31
30
29
28
26
25
23

518
523
415
420
328
263
207
171
130

33
32
31
30
29
28
27
25
23

0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.26
1.36
1.49
1.68
1.83

1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.35
1.45
1.58
1.80
1.95

1.29
1.32
1.32
1.38
1.42
1.47
1.53
1.59
1.75
1.91
2.13
2.32

652
679
695
747
814
905
1008
1110
1401
1768
2350
2914

11
11
11
12
12
12
13
13
14
16
18
19

146
146
166
166
189
216
245
269
322
389
473
533

261
266
207
212
168
133
106
90
66
48
34
28

53
52
51
50
48
46
45
43
41
40
37
35

801
807
748
754
634
495
403
341
246
173
116
88

33
32
31
30
29
27
26
25
23
21
19
18

196
196
222
222
251
283
317
343
397
451
513
555

269
274
215
220
177
144
119
104
82
67
55
48

101
99
98
96
93
90
86
83
76
68
57
49

786
792
734
740
622
487
397
337
244
172
116
88

33
32
31
30
29
27
26
25
23
21
19
18

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 12

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

25kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

25kV 133% Copper Single Phase - Full Neutral


QA5010A
1 SOLID CU
320
13-#12 0.289
QA6010A
1 AWG CU
320
13-#12 0.324
QA7010A
1/0 SOLID CU
320
16-#12 0.325
QA8010A
1/0 AWG CU
320
16-#12 0.364
QA9010A
2/0 AWG CU
320
13-#10 0.408
QAA010A
3/0 AWG CU
320
16-#10 0.458
QAB010A
4/0 AWG CU
320
16-#9 0.515
25kV 133% Copper Three Phase - One-Third Neutral
QA5000A
1 SOLID CU
320
7-#14 0.289
QA6000A
1 AWG CU
320
7-#14 0.324
QA7000A
1/0 SOLID CU
320
9-#14 0.325
QA8000A
1/0 AWG CU
320
9-#14 0.364
QA9000A
2/0 AWG CU
320
11-#14 0.408
QAA000A
3/0 AWG CU
320
14-#14 0.458
QAB000A
4/0 AWG CU
320
18-#14 0.515
QAC000A
250 MCM CU
320
21-#14 0.561
QAD000A
350 MCM CU
320
18-#12 0.664
QAE000A
500 MCM CU
320
17-#10 0.794
QAF000A
750 MCM CU
320
20-#9 0.974
QAG000A
1000 MCM CU
320
21-#8 1.124

(B)

(C)

(D)

0.98
1.01
1.02
1.05
1.10
1.15
1.21

1.05
1.08
1.08
1.14
1.19
1.24
1.29

1.32
1.35
1.35
1.41
1.50
1.55
1.63

1026
1056
1174
1228
1468
1699
2023

11
11
11
12
12
13
14

186
187
210
212
243
276
314

318
322
256
258
203
163
130

33
32
32
31
29
28
27

318
322
256
258
203
163
130

34
32
32
31
29
28
27

245
246
277
279
317
359
406

318
322
256
258
203
163
130

33
32
32
31
29
28
27

318
322
256
258
203
163
130

34
32
32
31
29
28
27

0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.26
1.36
1.49
1.68
1.83

1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.35
1.45
1.58
1.80
1.95

1.29
1.32
1.32
1.38
1.42
1.47
1.53
1.59
1.78
1.95
2.20
2.38

838
867
952
1005
1142
1317
1537
1734
2306
3085
4339
5524

11
11
11
12
12
12
13
13
15
16
18
19

187
187
213
213
242
275
311
341
405
475
556
603

158
162
126
129
103
82
66
56
42
32
25
22

53
52
51
50
48
46
45
43
41
39
36
34

622
626
487
490
398
314
246
210
153
104
71
54

33
32
31
30
29
27
26
25
23
21
20
18

249
249
280
281
314
349
384
410
460
504
567
620

168
172
138
140
116
98
84
76
64
55
45
39

100
98
97
95
91
87
82
78
69
57
45
37

609
614
478
481
392
310
243
208
152
104
71
53

33
32
31
30
29
27
26
25
23
21
20
18

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 13

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

35kV 100% Aluminum Single Phase - Full Neutral


QBP010A
1/0 SOLID AL
345
16-#14 0.325
QBQ010A
1/0 AWG AL
345
16-#14 0.364
QBR010A
2/0 AWG AL
345
13-#12 0.408
QBS010A
3/0 AWG AL
345
16-#12 0.458
QBT010A
4/0 AWG AL
345
13-#10 0.515
QBU010A
250 MCM AL
345
16-#10 0.561
QBV010A
350 MCM AL
345
16-#9 0.664
35kV 100% Aluminum Three Phase - One-Third Neutral
QBP000A
1/0 SOLID AL
345
6-#14 0.325
QBQ000A
1/0 AWG AL
345
6-#14 0.364
QBR000A
2/0 AWG AL
345
7-#14 0.408
QBS000A
3/0 AWG AL
345
9-#14 0.458
QBT000A
4/0 AWG AL
345
11-#14 0.515
QBU000A
250 MCM AL
345
13-#14 0.561
QBV000A
350 MCM AL
345
18-#14 0.664
QBW000A
500 MCM AL
345
16-#12 0.794
QBX000A
750 MCM AL
345
24-#12 0.974
QBY000A
1000 MCM AL
345
20-#10 1.124

(B)

(C)

(D)

1.07
1.10
1.15
1.20
1.26
1.31
1.41

1.15
1.19
1.24
1.29
1.34
1.40
1.50

1.39
1.43
1.51
1.56
1.72
1.77
1.90

876
909
1053
1178
1455
1638
1973

12
12
13
13
14
15
16

168
169
194
220
252
280
331

415
420
328
263
207
171
130

35
34
32
31
30
28
26

415
420
328
263
207
171
130

35
34
33
31
30
28
26

217
218
249
283
321
353
416

415
420
328
263
207
171
130

35
34
32
31
30
28
26

415
420
328
263
207
171
130

35
34
33
31
30
28
26

1.07
1.10
1.15
1.20
1.26
1.31
1.41
1.54
1.73
1.88

1.15
1.19
1.24
1.29
1.34
1.40
1.50
1.66
1.85
2.00

1.39
1.43
1.47
1.52
1.58
1.70
1.80
1.99
2.18
2.37

759
792
861
952
1058
1224
1457
1875
2419
2989

12
12
12
13
13
14
15
16
18
19

168
168
191
218
247
271
325
392
476
536

207
212
168
133
106
90
66
48
34
28

54
53
51
49
47
47
44
42
39
37

745
751
631
493
401
340
245
173
116
88

35
34
32
31
29
28
25
24
21
20

219
219
248
280
314
339
394
452
517
560

214
219
176
143
117
103
81
65
54
47

98
96
93
90
86
83
77
69
59
51

729
736
618
485
395
335
243
171
115
88

35
34
32
31
29
28
25
24
21
20

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 14

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 100%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

35kV 100% Copper Single Phase - Full Neutral


QB7010A
1/0 SOLID CU
345
16-#12 0.325
QB8010A
1/0 AWG CU
345
16-#12 0.364
QB9010A
2/0 AWG CU
345
13-#10 0.408
QBA010A
3/0 AWG CU
345
16-#10 0.458
QBB010A
4/0 AWG CU
345
16-#9 0.515
35kV 100% Copper Three Phase - One-Third Neutral
QB7000A
1/0 SOLID CU
345
9-#14 0.325
QB8000A
1/0 AWG CU
345
9-#14 0.364
QB9000A
2/0 AWG CU
345
11-#14 0.408
QBA000A
3/0 AWG CU
345
14-#14 0.458
QBB000A
4/0 AWG CU
345
18-#14 0.515
QBC000A
250 MCM CU
345
21-#14 0.561
QBD000A
350 MCM CU
345
18-#12 0.664
QBE000A
500 MCM CU
345
17-#10 0.794
QBF000A
750 MCM CU
345
20-#9 0.974
QBG000A
1000 MCM CU
345
21-#8 1.124

(B)

(C)

(D)

1.07
1.10
1.15
1.20
1.26

1.15
1.19
1.24
1.29
1.34

1.42
1.46
1.55
1.60
1.74

1239
1274
1516
1749
2141

12
12
13
13
14

215
217
248
281
319

256
258
203
163
130

36
34
33
31
30

256
258
203
163
130

36
35
33
31
30

276
278
316
358
402

256
258
203
163
130

36
34
33
31
30

256
258
203
163
130

36
35
33
31
30

1.07
1.10
1.15
1.20
1.26
1.31
1.41
1.54
1.73
1.88

1.15
1.19
1.24
1.29
1.34
1.40
1.50
1.66
1.85
2.00

1.39
1.43
1.47
1.52
1.58
1.70
1.83
2.03
2.25
2.43

1016
1050
1188
1365
1586
1848
2363
3194
4410
5601

12
12
12
13
13
14
15
17
18
20

216
216
245
278
314
344
408
480
561
609

126
129
103
82
66
57
42
32
25
22

54
53
51
49
47
47
44
42
38
36

484
487
396
313
245
210
152
104
71
54

35
34
32
31
29
28
26
24
22
20

277
278
311
347
383
409
461
510
573
626

137
139
115
96
83
74
62
53
44
38

97
95
92
87
83
79
70
59
47
39

474
478
389
308
242
207
151
103
71
53

35
34
32
31
29
28
26
24
22
20

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 15

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

35kV 133% Aluminum Single Phase - Full Neutral


QCP010A
1/0 SOLID AL
420
16-#14 0.325
QCQ010A
1/0 AWG AL
420
16-#14 0.364
QCR010A
2/0 AWG AL
420
13-#12 0.408
QCS010A
3/0 AWG AL
420
16-#12 0.458
QCT010A
4/0 AWG AL
420
13-#10 0.515
QCU010A
250 MCM AL
420
16-#10 0.561
QCV010A
350 MCM AL
420
16-#9 0.664
35kV 133% Aluminum Three Phase - One-Third Neutral
QCP000A
1/0 SOLID AL
420
6-#14 0.325
QCQ000A
1/0 AWG AL
420
6-#14 0.364
QCR000A
2/0 AWG AL
420
7-#14 0.408
QCS000A
3/0 AWG AL
420
9-#14 0.458
QCT000A
4/0 AWG AL
420
11-#14 0.515
QCU000A
250 MCM AL
420
13-#14 0.561
QCV000A
350 MCM AL
420
18-#14 0.664
QCW000A
500 MCM AL
420
16-#12 0.794
QCX000A
750 MCM AL
420
24-#12 0.974
QCY000A
1000 MCM AL
420
20-#10 1.124

(B)

(C)

(D)

1.22
1.26
1.30
1.35
1.41
1.46
1.57

1.31
1.35
1.39
1.44
1.50
1.55
1.68

1.55
1.58
1.72
1.77
1.87
1.93
2.08

1020
1056
1272
1404
1631
1819
2213

13
13
14
15
15
16
17

168
169
194
220
252
280
331

415
420
328
263
207
171
130

35
34
32
31
30
28
26

415
420
328
263
207
171
130

35
34
33
31
30
28
26

217
218
249
283
321
353
416

415
420
328
263
207
171
130

35
34
32
31
30
28
26

415
420
328
263
207
171
130

35
34
33
31
30
28
26

1.22
1.26
1.30
1.35
1.41
1.46
1.57
1.70
1.88
2.03

1.31
1.35
1.39
1.44
1.50
1.55
1.68
1.81
2.00
2.15

1.55
1.58
1.63
1.74
1.80
1.85
1.98
2.15
2.33
2.53

903
939
1012
1174
1287
1398
1685
2077
2640
3228

13
13
14
14
15
15
16
18
19
21

168
168
191
218
247
271
325
392
476
536

207
212
168
133
106
90
66
48
34
28

54
53
51
49
47
47
44
42
39
37

745
751
631
493
401
340
245
173
116
88

35
34
32
31
29
28
25
24
21
20

219
219
248
280
314
339
394
452
517
560

214
219
176
143
117
103
81
65
54
47

98
96
93
90
86
83
77
69
59
51

729
736
618
485
395
335
243
171
115
88

35
34
32
31
29
28
25
24
21
20

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 16

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com

Product Number

URD

35kV 133%

Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q

Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp

ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce

TRXLPE

Conductor

(A)

35kV 133% Copper Single Phase - Full Neutral


QC7010A
1/0 SOLID CU
420
16-#12 0.325
QC8010A
1/0 AWG CU
420
16-#12 0.364
QC9010A
2/0 AWG CU
420
13-#10 0.408
QCA010A
3/0 AWG CU
420
16-#10 0.458
QCB010A
4/0 AWG CU
420
16-#9 0.515
35kV 133% Copper Three Phase - One-Third Neutral
QC7000A
1/0 SOLID CU
420
9-#14 0.325
QC8000A
1/0 AWG CU
420
9-#14 0.364
QC9000A
2/0 AWG CU
420
11-#14 0.408
QCA000A
3/0 AWG CU
420
14-#14 0.458
QCB000A
4/0 AWG CU
420
18-#14 0.515
QCC000A
250 MCM CU
420
21-#14 0.561
QCD000A
350 MCM CU
420
18-#12 0.664
QCE000A
500 MCM CU
420
17-#10 0.794
QCF000A
750 MCM CU
420
20-#9 0.974
QCG000A
1000 MCM CU
420
21-#8 1.124

(B)

(C)

(D)

1.22
1.26
1.30
1.35
1.41

1.31
1.35
1.39
1.44
1.50

1.58
1.62
1.76
1.81
1.90

1386
1425
1742
1981
2319

13
13
15
15
16

215
217
248
281
319

256
258
203
163
130

36
34
33
31
30

256
258
203
163
130

36
35
33
31
30

276
278
316
358
402

256
258
203
163
130

36
34
33
31
30

256
258
203
163
130

36
35
33
31
30

1.22
1.26
1.30
1.35
1.41
1.46
1.57
1.70
1.88
2.03

1.31
1.35
1.39
1.44
1.50
1.55
1.68
1.81
2.00
2.15

1.55
1.58
1.63
1.74
1.80
1.85
2.02
2.19
2.40
2.58

1160
1197
1340
1587
1816
2022
2595
3401
4637
5846

13
13
14
14
15
15
17
18
20
21

216
216
245
278
314
344
408
480
561
609

126
129
103
82
66
57
42
32
25
22

54
53
51
49
47
47
44
42
38
36

484
487
396
313
245
210
152
104
71
54

35
34
32
31
29
28
26
24
22
20

277
278
311
347
383
409
461
510
573
626

137
139
115
96
83
74
62
53
44
38

97
95
92
87
83
79
70
59
47
39

474
478
389
308
242
207
151
103
71
53

35
34
32
31
29
28
26
24
22
20

Ampacities are based on the following:

90C In Duct

90C Direct Buried

Zero Sequence Impedance considers all return in the neutral only.

PRODUCT NOTES:

Single Phase Operation (Full Neutral Design)

Three Phase Operation (1/3 Neutral Design)

Items are Prysmian authorized stock.

In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.

In Duct: Three single cables in plastic duct, direct-buried in a triangular configuration,


90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.

Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.

The above dimensions are approximate and subject


to normal manufacturing tolerances.
Single Phase Impedance Values Assume Full
Return in the Metallic Shield.

MEDIUM VOLTAGE
UTILITY

section ii.1 17

Information Subject to Change without Notice.

1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com