URD
2012.01.17
Description
Design Parameters
Options
Conductor
Solid or Class B Compressed concentric strand Aluminum alloy
1350 or soft drawn annealed copper per ASTM.
Specifications
ICEA
ICEA S-94-649
AEIC
AEIC CS8
Ratings
Conductor Shield
Extruded thermosetting semiconducting shield which is free
stripping from the conductor and bonded to the insulation.
Insulation
Natural high dielectric strength VOLTALENE TRXLPE
insulation, exhibiting an optimum balance of mechanical
and electrical properties, insuring resistance to treeing.
Insulation Shield
Extruded thermosetting semiconducting shield with controlled
adhesion to the insulation providing the required balance
between electrical integrity and ease of stripping.
Metallic Shield
Solid bare copper wires, helically applied and uniformly spaced.
Jacket
Black insulating sunlight resistant linear low density
polyethylene encapsulating the neutral wires with three
extruded red stripes and NESC lightning bolt symbol.
MEDIUM VOLTAGE
UTILITY
section ii.1 1
Installations
Conduit in Air
Direct Buried
Underground Duct
Isolated in Air
Wet Locations
Dry Locations
With Messenger
Utility Primary
Product Number
URD
5kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.80
0.90
0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.86
0.97
0.79
0.82
0.82
0.86
0.86
0.90
0.97
1.02
1.12
1.18
1.30
360
375
422
439
490
509
627
736
914
1076
1362
7
7
7
7
7
8
8
9
9
10
11
119
120
136
138
155
156
181
206
237
264
314
663
669
518
523
415
420
328
263
207
171
130
24
25
23
22
22
21
21
20
19
18
17
663
669
518
523
415
420
328
263
207
171
130
25
25
23
22
22
21
20
19
19
18
17
169
170
193
195
219
220
251
285
323
358
421
663
669
518
523
415
420
328
263
207
171
130
24
25
23
22
22
21
21
20
19
18
17
663
669
518
523
415
420
328
263
207
171
130
25
25
23
22
22
21
20
19
19
18
17
0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.80
0.90
1.03
1.22
1.37
0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.86
0.97
1.12
1.30
1.45
0.79
0.82
0.82
0.86
0.86
0.90
0.94
0.99
1.05
1.10
1.20
1.39
1.58
1.83
313
329
340
357
373
393
447
522
608
693
887
1219
1691
2255
7
7
7
7
7
8
8
8
9
9
10
12
13
15
123
123
140
140
159
160
182
208
237
261
314
381
464
522
329
335
261
266
207
212
168
133
107
91
66
48
34
29
46
46
45
44
43
42
40
39
38
37
35
34
32
31
876
883
809
815
756
762
640
500
407
344
249
175
117
89
25
25
23
22
22
21
20
19
18
17
15
15
14
13
178
179
202
203
229
229
258
290
323
348
399
449
505
541
340
346
272
276
217
222
179
146
122
107
86
70
58
51
103
102
100
98
98
96
93
89
85
82
75
66
54
45
864
872
798
804
746
752
632
495
403
342
247
174
117
88
25
25
23
22
22
21
20
19
18
17
15
15
14
13
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 2
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
5kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.79
0.82
0.85
0.89
0.89
0.93
1.02
1.07
1.15
570
584
704
724
841
862
1076
1291
1590
7
7
7
8
8
8
9
9
10
152
153
175
176
198
200
231
262
300
408
412
318
322
256
258
203
163
130
25
25
24
23
23
22
22
20
20
408
412
318
322
256
258
203
163
130
25
25
24
23
22
22
21
20
19
215
217
245
247
277
280
317
359
407
408
412
318
322
256
258
203
163
130
25
25
24
23
23
22
22
20
20
408
412
318
322
256
258
203
163
130
25
25
24
23
22
22
21
20
19
0.48
0.51
0.52
0.55
0.55
0.59
0.63
0.68
0.74
0.80
0.90
1.03
1.22
1.37
0.55
0.58
0.58
0.62
0.62
0.66
0.70
0.75
0.81
0.86
0.97
1.12
1.30
1.45
0.79
0.82
0.82
0.86
0.86
0.90
0.94
0.99
1.05
1.10
1.24
1.43
1.70
1.88
453
468
527
545
630
651
775
934
1136
1317
1780
2521
3718
4847
7
7
7
7
7
8
8
8
9
9
10
12
14
16
157
158
179
180
204
205
233
265
301
330
393
464
540
586
200
203
159
162
126
129
103
82
66
57
42
32
26
23
46
46
44
44
43
42
40
39
38
36
35
34
35
29
747
752
628
633
492
495
402
317
248
212
154
105
72
54
25
25
23
22
22
21
20
19
18
17
16
15
14
13
227
228
256
256
286
287
320
353
385
409
452
494
552
607
211
214
171
174
141
143
119
101
88
80
68
58
48
41
103
102
100
98
96
94
90
85
79
75
65
53
40
31
735
740
619
624
485
489
398
314
247
211
154
104
71
53
25
25
23
22
22
21
20
19
18
17
16
15
14
13
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 3
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
5kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.85
0.95
0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.91
1.02
0.84
0.87
0.87
0.91
0.91
0.95
1.02
1.07
1.17
1.23
1.35
386
402
449
467
518
539
659
769
951
1115
1405
7
7
7
8
8
8
9
9
10
10
11
119
120
136
138
155
156
181
206
237
264
314
663
669
518
523
415
420
328
263
207
171
130
24
25
23
22
22
21
21
20
19
18
17
663
669
518
523
415
420
328
263
207
171
130
25
25
23
22
22
21
20
19
19
18
17
169
170
193
195
219
220
251
285
323
358
421
663
669
518
523
415
420
328
263
207
171
130
24
25
23
22
22
21
21
20
19
18
17
663
669
518
523
415
420
328
263
207
171
130
25
25
23
22
22
21
20
19
19
18
17
0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.85
0.95
1.08
1.27
1.42
0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.91
1.02
1.17
1.35
1.50
0.84
0.87
0.87
0.91
0.91
0.95
0.99
1.04
1.10
1.15
1.25
1.44
1.63
1.88
339
356
367
385
401
422
478
554
642
729
926
1264
1742
2314
7
7
7
8
8
8
8
9
9
10
11
12
14
16
123
123
140
140
159
160
182
208
237
261
314
381
464
522
329
335
261
266
207
212
168
133
107
91
66
48
34
29
46
46
45
44
43
42
40
39
38
37
35
34
32
31
876
883
809
815
756
762
640
500
407
344
249
175
117
89
25
25
23
22
22
21
20
19
18
17
15
15
14
13
178
179
202
203
229
229
258
290
323
348
399
449
505
541
340
346
272
276
217
222
179
146
122
107
86
70
58
51
103
102
100
98
98
96
93
89
85
82
75
66
54
45
864
872
798
804
746
752
632
495
403
342
247
174
117
88
25
25
23
22
22
21
20
19
18
17
15
15
14
13
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 4
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
5kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.84
0.87
0.90
0.94
0.94
0.98
1.07
1.12
1.20
596
611
732
753
871
893
1109
1326
1628
7
7
8
8
8
8
9
9
10
152
153
175
176
198
200
231
262
300
408
412
318
322
256
258
203
163
130
25
25
24
23
23
22
22
20
20
408
412
318
322
256
258
203
163
130
25
25
24
23
22
22
21
20
19
215
217
245
247
277
280
317
359
407
408
412
318
322
256
258
203
163
130
25
25
24
23
23
22
22
20
20
408
412
318
322
256
258
203
163
130
25
25
24
23
22
22
21
20
19
0.53
0.56
0.57
0.60
0.60
0.64
0.68
0.73
0.79
0.85
0.95
1.08
1.27
1.42
0.60
0.63
0.63
0.67
0.67
0.71
0.75
0.80
0.86
0.91
1.02
1.17
1.35
1.50
0.84
0.87
0.87
0.91
0.91
0.95
0.99
1.04
1.10
1.15
1.29
1.48
1.75
1.93
479
495
554
573
659
680
805
967
1171
1353
1820
2567
3773
4908
7
7
7
8
8
8
8
9
9
10
11
12
15
16
157
158
179
180
204
205
233
265
301
330
393
464
540
586
200
203
159
162
126
129
103
82
66
57
42
32
26
23
46
46
44
44
43
42
40
39
38
36
35
34
35
29
747
752
628
633
492
495
402
317
248
212
154
105
72
54
25
25
23
22
22
21
20
19
18
17
16
15
14
13
227
228
256
256
286
287
320
353
385
409
452
494
552
607
211
214
171
174
141
143
119
101
88
80
68
58
48
41
103
102
100
98
96
94
90
85
79
75
65
53
40
31
735
740
619
624
485
489
398
314
247
211
154
104
71
53
25
25
23
22
22
21
20
19
18
17
16
15
14
13
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 5
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
15kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
90C In Duct
0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.97
1.07
0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
1.03
1.16
0.96
0.99
0.99
1.03
1.03
1.07
1.14
1.19
1.29
1.35
1.49
455
473
520
541
592
616
742
856
1046
1214
1536
8
8
8
9
9
9
10
10
11
11
12
123
124
141
143
160
162
186
212
243
270
321
663
669
518
523
415
420
328
263
207
171
130
29
30
28
27
27
26
25
24
23
22
21
663
669
518
523
415
420
328
263
207
171
130
30
31
29
28
27
26
25
24
23
22
20
169
170
193
194
219
220
251
284
323
358
420
663
669
518
523
415
420
328
263
207
171
130
29
30
28
27
27
26
25
24
23
22
21
663
669
518
523
415
420
328
263
207
171
130
30
31
29
28
27
26
25
24
23
22
20
0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.97
1.07
1.20
1.39
1.54
0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
1.03
1.16
1.29
1.47
1.65
0.96
0.99
0.99
1.03
1.03
1.07
1.11
1.16
1.22
1.27
1.39
1.56
1.81
2.03
409
427
439
459
475
499
558
638
730
821
1048
1378
1938
2507
8
8
8
9
9
9
9
10
10
11
12
13
15
17
126
126
143
144
163
163
186
212
241
265
319
385
468
529
329
335
261
266
207
212
168
133
106
91
66
48
35
28
51
51
49
48
47
46
44
43
41
40
38
37
35
33
872
879
805
811
752
758
637
498
405
343
247
174
117
89
30
31
29
28
27
26
25
24
23
21
19
18
16
16
175
175
199
199
225
225
255
286
320
345
398
451
507
549
338
344
270
275
216
221
178
145
120
106
84
68
57
49
103
102
100
98
98
96
93
89
86
82
76
67
55
47
857
865
791
798
739
745
627
491
400
339
245
173
116
88
30
31
29
28
27
26
25
24
23
21
19
18
16
16
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 6
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
15kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
0.96
0.99
1.02
1.06
1.06
1.10
1.19
1.24
1.32
665
682
807
830
948
973
1196
1417
1724
8
8
9
9
9
9
10
10
11
157
158
181
182
205
207
237
270
307
408
412
318
322
256
258
203
163
130
31
31
29
28
28
27
26
25
23
408
412
318
322
256
258
203
163
130
30
31
29
28
28
27
26
24
23
215
217
245
246
277
279
317
359
407
408
412
318
322
256
258
203
163
130
31
31
29
28
28
27
26
25
23
408
412
318
322
256
258
203
163
130
30
31
29
28
28
27
26
24
23
0.65
0.68
0.69
0.72
0.72
0.76
0.80
0.85
0.91
0.97
1.07
1.20
1.39
1.54
0.72
0.75
0.75
0.79
0.79
0.83
0.87
0.92
0.98
1.03
1.16
1.29
1.47
1.65
0.96
0.99
0.99
1.03
1.03
1.07
1.11
1.16
1.22
1.27
1.43
1.60
1.87
2.08
548
566
625
647
733
757
886
1051
1259
1445
1945
2685
3912
5107
8
8
8
9
9
9
9
10
10
11
12
13
15
17
162
162
184
184
209
210
238
271
307
336
400
471
548
596
200
203
159
162
126
129
103
82
66
57
42
32
26
23
51
51
49
48
47
46
44
43
41
40
38
36
34
32
743
747
625
629
489
492
400
316
247
211
154
104
71
54
30
31
29
28
27
26
25
23
22
21
20
18
17
16
223
224
252
252
283
284
317
351
385
410
457
501
559
669
209
213
169
173
139
141
117
99
86
78
66
57
47
41
103
102
100
98
96
94
91
86
81
76
67
55
42
35
728
733
613
618
481
484
395
312
245
210
153
104
71
56
30
31
29
28
27
26
25
23
22
21
20
18
17
16
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 7
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
15kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
1.06
1.16
0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.14
1.25
1.05
1.08
1.08
1.12
1.12
1.16
1.23
1.28
1.38
1.46
1.58
513
533
580
603
654
680
811
927
1122
1315
1624
9
9
9
9
9
10
10
11
12
12
13
123
124
141
143
160
162
186
212
243
270
321
663
669
518
523
415
420
328
263
207
171
130
29
30
28
27
27
26
25
24
23
22
21
663
669
518
523
415
420
328
263
207
171
130
30
31
29
28
27
26
25
24
23
22
20
169
170
193
194
219
220
251
284
323
358
420
663
669
518
523
415
420
328
263
207
171
130
29
30
28
27
27
26
25
24
23
22
21
663
669
518
523
415
420
328
263
207
171
130
30
31
29
28
27
26
25
24
23
22
20
0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
1.06
1.16
1.29
1.48
1.63
0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.14
1.25
1.38
1.56
1.74
1.05
1.08
1.08
1.12
1.12
1.16
1.20
1.25
1.31
1.38
1.48
1.71
1.90
2.12
466
486
498
521
537
563
624
707
803
917
1130
1534
2043
2626
9
9
9
9
9
10
10
11
11
12
12
14
16
17
126
126
143
144
163
163
186
212
241
265
319
385
468
529
329
335
261
266
207
212
168
133
106
91
66
48
35
28
51
51
49
48
47
46
44
43
41
40
38
37
35
33
872
879
805
811
752
758
637
498
405
343
247
174
117
89
30
31
29
28
27
26
25
24
23
21
19
18
16
16
175
175
199
199
225
225
255
286
320
345
398
451
507
549
338
344
270
275
216
221
178
145
120
106
84
68
57
49
103
102
100
98
98
96
93
89
86
82
76
67
55
47
857
865
791
798
739
745
627
491
400
339
245
173
116
88
30
31
29
28
27
26
25
24
23
21
19
18
16
16
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 8
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
15kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.05
1.08
1.11
1.15
1.15
1.19
1.28
1.33
1.41
723
742
868
893
1011
1039
1266
1490
1803
9
9
9
10
10
10
11
11
12
157
158
181
182
205
207
237
270
307
408
412
318
322
256
258
203
163
130
31
31
29
28
28
27
26
25
23
408
412
318
322
256
258
203
163
130
30
31
29
28
28
27
26
24
23
215
217
245
246
277
279
317
359
407
408
412
318
322
256
258
203
163
130
31
31
29
28
28
27
26
25
23
408
412
318
322
256
258
203
163
130
30
31
29
28
28
27
26
24
23
0.74
0.77
0.78
0.81
0.81
0.85
0.89
0.94
1.00
1.06
1.16
1.29
1.48
1.63
0.81
0.84
0.84
0.88
0.88
0.92
0.96
1.01
1.07
1.14
1.25
1.38
1.56
1.74
1.05
1.08
1.08
1.12
1.12
1.16
1.20
1.25
1.31
1.38
1.52
1.75
1.96
2.17
606
625
685
709
794
821
952
1120
1331
1541
2029
2845
4022
5229
9
9
9
9
9
10
10
11
11
12
13
14
16
18
162
162
184
184
209
210
238
271
307
336
400
471
548
596
200
203
159
162
126
129
103
82
66
57
42
32
26
23
51
51
49
48
47
46
44
43
41
40
38
36
34
32
743
747
625
629
489
492
400
316
247
211
154
104
71
54
30
31
29
28
27
26
25
23
22
21
20
18
17
16
223
224
252
252
283
284
317
351
385
410
457
501
559
669
209
213
169
173
139
141
117
99
86
78
66
57
47
41
103
102
100
98
96
94
91
86
81
76
67
55
42
35
728
733
613
618
481
484
395
312
245
210
153
104
71
56
30
31
29
28
27
26
25
23
22
21
20
18
17
16
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 9
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
25kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.86
0.89
0.89
0.93
0.97
1.02
1.08
1.14
1.24
0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.22
1.33
1.16
1.20
1.20
1.24
1.31
1.38
1.48
1.54
1.72
637
662
713
741
875
1015
1217
1392
1772
10
10
10
10
11
12
12
13
14
145
146
165
166
190
217
248
276
326
518
523
415
420
328
263
207
171
130
33
31
31
30
29
28
26
25
23
518
523
415
420
328
263
207
171
130
33
32
31
30
29
28
27
25
23
192
194
218
219
250
283
322
356
416
518
523
415
420
328
263
207
171
130
33
31
31
30
29
28
26
25
23
518
523
415
420
328
263
207
171
130
33
32
31
30
29
28
27
25
23
0.86
0.89
0.89
0.93
0.97
1.02
1.08
1.14
1.24
1.37
1.56
1.71
0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.22
1.33
1.46
1.67
1.82
1.16
1.20
1.20
1.24
1.28
1.35
1.41
1.46
1.56
1.79
2.01
2.20
555
580
596
624
687
793
892
990
1208
1623
2187
2736
10
10
10
10
11
11
12
12
13
15
17
18
146
146
166
166
189
216
245
269
322
389
473
533
261
266
207
212
168
133
106
90
66
48
34
28
53
52
51
50
48
46
45
43
41
40
37
35
801
807
748
754
634
495
403
341
246
173
116
88
33
32
31
30
29
27
26
25
23
21
19
18
196
196
222
222
251
283
317
343
397
451
513
555
269
274
215
220
177
144
119
104
82
67
55
48
101
99
98
96
93
90
86
83
76
68
57
49
786
792
734
740
622
487
397
337
244
172
116
88
33
32
31
30
29
27
26
25
23
21
19
18
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 10
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
25kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.86
0.89
0.89
0.93
0.97
1.02
1.08
0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.19
1.23
1.23
1.27
1.36
1.43
1.51
927
954
1072
1101
1333
1581
1899
10
10
10
11
11
12
13
186
187
210
212
243
276
314
318
322
256
258
203
163
130
33
32
32
31
29
28
27
318
322
256
258
203
163
130
34
32
32
31
29
28
27
245
246
277
279
317
359
406
318
322
256
258
203
163
130
33
32
32
31
29
28
27
318
322
256
258
203
163
130
34
32
32
31
29
28
27
0.86
0.89
0.89
0.93
0.97
1.02
1.08
1.14
1.24
1.37
1.56
1.71
0.92
0.96
0.96
1.00
1.04
1.11
1.17
1.22
1.33
1.46
1.67
1.82
1.16
1.20
1.20
1.24
1.28
1.35
1.41
1.46
1.60
1.83
2.07
2.25
742
768
853
882
1015
1206
1421
1614
2109
2936
4170
5342
10
10
10
10
11
11
12
12
13
15
17
19
187
187
213
213
242
275
311
341
405
475
556
603
158
162
126
129
103
82
66
56
42
32
25
22
53
52
51
50
48
46
45
43
41
39
36
34
622
626
487
490
398
314
246
210
153
104
71
54
33
32
31
30
29
27
26
25
23
21
20
18
249
249
280
281
314
349
384
410
460
504
567
620
168
172
138
140
116
98
84
76
64
55
45
39
100
98
97
95
91
87
82
78
69
57
45
37
609
614
478
481
392
310
243
208
152
104
71
53
33
32
31
30
29
27
26
25
23
21
20
18
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 11
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
25kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.26
1.36
1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.35
1.45
1.29
1.32
1.32
1.38
1.46
1.51
1.61
1.72
1.85
734
761
812
864
1006
1129
1339
1583
1913
11
11
11
12
12
13
13
14
15
145
146
165
166
190
217
248
276
326
518
523
415
420
328
263
207
171
130
33
31
31
30
29
28
26
25
23
518
523
415
420
328
263
207
171
130
33
32
31
30
29
28
27
25
23
192
194
218
219
250
283
322
356
416
518
523
415
420
328
263
207
171
130
33
31
31
30
29
28
26
25
23
518
523
415
420
328
263
207
171
130
33
32
31
30
29
28
27
25
23
0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.26
1.36
1.49
1.68
1.83
1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.35
1.45
1.58
1.80
1.95
1.29
1.32
1.32
1.38
1.42
1.47
1.53
1.59
1.75
1.91
2.13
2.32
652
679
695
747
814
905
1008
1110
1401
1768
2350
2914
11
11
11
12
12
12
13
13
14
16
18
19
146
146
166
166
189
216
245
269
322
389
473
533
261
266
207
212
168
133
106
90
66
48
34
28
53
52
51
50
48
46
45
43
41
40
37
35
801
807
748
754
634
495
403
341
246
173
116
88
33
32
31
30
29
27
26
25
23
21
19
18
196
196
222
222
251
283
317
343
397
451
513
555
269
274
215
220
177
144
119
104
82
67
55
48
101
99
98
96
93
90
86
83
76
68
57
49
786
792
734
740
622
487
397
337
244
172
116
88
33
32
31
30
29
27
26
25
23
21
19
18
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 12
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
25kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.32
1.35
1.35
1.41
1.50
1.55
1.63
1026
1056
1174
1228
1468
1699
2023
11
11
11
12
12
13
14
186
187
210
212
243
276
314
318
322
256
258
203
163
130
33
32
32
31
29
28
27
318
322
256
258
203
163
130
34
32
32
31
29
28
27
245
246
277
279
317
359
406
318
322
256
258
203
163
130
33
32
32
31
29
28
27
318
322
256
258
203
163
130
34
32
32
31
29
28
27
0.98
1.01
1.02
1.05
1.10
1.15
1.21
1.26
1.36
1.49
1.68
1.83
1.05
1.08
1.08
1.14
1.19
1.24
1.29
1.35
1.45
1.58
1.80
1.95
1.29
1.32
1.32
1.38
1.42
1.47
1.53
1.59
1.78
1.95
2.20
2.38
838
867
952
1005
1142
1317
1537
1734
2306
3085
4339
5524
11
11
11
12
12
12
13
13
15
16
18
19
187
187
213
213
242
275
311
341
405
475
556
603
158
162
126
129
103
82
66
56
42
32
25
22
53
52
51
50
48
46
45
43
41
39
36
34
622
626
487
490
398
314
246
210
153
104
71
54
33
32
31
30
29
27
26
25
23
21
20
18
249
249
280
281
314
349
384
410
460
504
567
620
168
172
138
140
116
98
84
76
64
55
45
39
100
98
97
95
91
87
82
78
69
57
45
37
609
614
478
481
392
310
243
208
152
104
71
53
33
32
31
30
29
27
26
25
23
21
20
18
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 13
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
35kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
1.07
1.10
1.15
1.20
1.26
1.31
1.41
1.15
1.19
1.24
1.29
1.34
1.40
1.50
1.39
1.43
1.51
1.56
1.72
1.77
1.90
876
909
1053
1178
1455
1638
1973
12
12
13
13
14
15
16
168
169
194
220
252
280
331
415
420
328
263
207
171
130
35
34
32
31
30
28
26
415
420
328
263
207
171
130
35
34
33
31
30
28
26
217
218
249
283
321
353
416
415
420
328
263
207
171
130
35
34
32
31
30
28
26
415
420
328
263
207
171
130
35
34
33
31
30
28
26
1.07
1.10
1.15
1.20
1.26
1.31
1.41
1.54
1.73
1.88
1.15
1.19
1.24
1.29
1.34
1.40
1.50
1.66
1.85
2.00
1.39
1.43
1.47
1.52
1.58
1.70
1.80
1.99
2.18
2.37
759
792
861
952
1058
1224
1457
1875
2419
2989
12
12
12
13
13
14
15
16
18
19
168
168
191
218
247
271
325
392
476
536
207
212
168
133
106
90
66
48
34
28
54
53
51
49
47
47
44
42
39
37
745
751
631
493
401
340
245
173
116
88
35
34
32
31
29
28
25
24
21
20
219
219
248
280
314
339
394
452
517
560
214
219
176
143
117
103
81
65
54
47
98
96
93
90
86
83
77
69
59
51
729
736
618
485
395
335
243
171
115
88
35
34
32
31
29
28
25
24
21
20
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 14
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
35kV 100%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
1.07
1.10
1.15
1.20
1.26
1.15
1.19
1.24
1.29
1.34
1.42
1.46
1.55
1.60
1.74
1239
1274
1516
1749
2141
12
12
13
13
14
215
217
248
281
319
256
258
203
163
130
36
34
33
31
30
256
258
203
163
130
36
35
33
31
30
276
278
316
358
402
256
258
203
163
130
36
34
33
31
30
256
258
203
163
130
36
35
33
31
30
1.07
1.10
1.15
1.20
1.26
1.31
1.41
1.54
1.73
1.88
1.15
1.19
1.24
1.29
1.34
1.40
1.50
1.66
1.85
2.00
1.39
1.43
1.47
1.52
1.58
1.70
1.83
2.03
2.25
2.43
1016
1050
1188
1365
1586
1848
2363
3194
4410
5601
12
12
12
13
13
14
15
17
18
20
216
216
245
278
314
344
408
480
561
609
126
129
103
82
66
57
42
32
25
22
54
53
51
49
47
47
44
42
38
36
484
487
396
313
245
210
152
104
71
54
35
34
32
31
29
28
26
24
22
20
277
278
311
347
383
409
461
510
573
626
137
139
115
96
83
74
62
53
44
38
97
95
92
87
83
79
70
59
47
39
474
478
389
308
242
207
151
103
71
53
35
34
32
31
29
28
26
24
22
20
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 15
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
35kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
1.22
1.26
1.30
1.35
1.41
1.46
1.57
1.31
1.35
1.39
1.44
1.50
1.55
1.68
1.55
1.58
1.72
1.77
1.87
1.93
2.08
1020
1056
1272
1404
1631
1819
2213
13
13
14
15
15
16
17
168
169
194
220
252
280
331
415
420
328
263
207
171
130
35
34
32
31
30
28
26
415
420
328
263
207
171
130
35
34
33
31
30
28
26
217
218
249
283
321
353
416
415
420
328
263
207
171
130
35
34
32
31
30
28
26
415
420
328
263
207
171
130
35
34
33
31
30
28
26
1.22
1.26
1.30
1.35
1.41
1.46
1.57
1.70
1.88
2.03
1.31
1.35
1.39
1.44
1.50
1.55
1.68
1.81
2.00
2.15
1.55
1.58
1.63
1.74
1.80
1.85
1.98
2.15
2.33
2.53
903
939
1012
1174
1287
1398
1685
2077
2640
3228
13
13
14
14
15
15
16
18
19
21
168
168
191
218
247
271
325
392
476
536
207
212
168
133
106
90
66
48
34
28
54
53
51
49
47
47
44
42
39
37
745
751
631
493
401
340
245
173
116
88
35
34
32
31
29
28
25
24
21
20
219
219
248
280
314
339
394
452
517
560
214
219
176
143
117
103
81
65
54
47
98
96
93
90
86
83
77
69
59
51
729
736
618
485
395
335
243
171
115
88
35
34
32
31
29
28
25
24
21
20
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.
MEDIUM VOLTAGE
UTILITY
section ii.1 16
1-800-845-8507 (US)
1-800-263-4405 (West-CAN)
1-800-361-1418 (East-CAN)
www.prysmianusa.com
www.prysmiancanada.com
Product Number
URD
35kV 133%
Ins
ula
tio
nT
hic
kn
es
Co
s(
nc
mi
en
ls)
tric
Ne
utr
al
Co
nd
uc
tor
Di
am
ete
Ins
r(
in.
ula
)
tio
nD
iam
ete
r(
Ins
in.
ula
)
tio
nS
hie
ld
Di
Ja
am
ck
ete
et
r(
Di
in.
am
)
ete
r(
in.
Ca
)
ble
We
igh
t (l
bs
/kf
M
t)
ini
mu
m
Be
nd
ing
A
Ra
mp
diu
ac
s(
ity
in.
(A
)
mp
+/s
)
Se
q
Re uen
sis ce
tan Im
ce pe
( dan
+/ ce
Se
/ft)
qu
Re en
ac ce
tan Im
Ze ce ( peda
ro
nc
S
/
e
Re eque ft)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
/ft) e
Se
q
Re ue
ac nc
tan e
ce Imp
( ed
an
A
/ft) ce
mp
ac
ity
(A
mp
+/s)
Se
qu
Re en
sis ce
tan Im
ce pe
+/( dan
ce
Se
/ft)
qu
Re en
ac ce
tan Im
ce pe
Ze
( da
ro
nc
S
/f e
Re eque t)
sis nc
tan e I
ce mp
Ze
( eda
ro
nc
Se
/
q
Re ue ft) e
ac nc
tan e
ce Imp
( ed
an
/ft) ce
TRXLPE
Conductor
(A)
(B)
(C)
(D)
1.22
1.26
1.30
1.35
1.41
1.31
1.35
1.39
1.44
1.50
1.58
1.62
1.76
1.81
1.90
1386
1425
1742
1981
2319
13
13
15
15
16
215
217
248
281
319
256
258
203
163
130
36
34
33
31
30
256
258
203
163
130
36
35
33
31
30
276
278
316
358
402
256
258
203
163
130
36
34
33
31
30
256
258
203
163
130
36
35
33
31
30
1.22
1.26
1.30
1.35
1.41
1.46
1.57
1.70
1.88
2.03
1.31
1.35
1.39
1.44
1.50
1.55
1.68
1.81
2.00
2.15
1.55
1.58
1.63
1.74
1.80
1.85
2.02
2.19
2.40
2.58
1160
1197
1340
1587
1816
2022
2595
3401
4637
5846
13
13
14
14
15
15
17
18
20
21
216
216
245
278
314
344
408
480
561
609
126
129
103
82
66
57
42
32
25
22
54
53
51
49
47
47
44
42
38
36
484
487
396
313
245
210
152
104
71
54
35
34
32
31
29
28
26
24
22
20
277
278
311
347
383
409
461
510
573
626
137
139
115
96
83
74
62
53
44
38
97
95
92
87
83
79
70
59
47
39
474
478
389
308
242
207
151
103
71
53
35
34
32
31
29
28
26
24
22
20
90C In Duct
PRODUCT NOTES:
In Duct: One single cable in plastic duct, direct-buried, 90C conductor temperature,
20C ambient temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth
of burial, and shields short-circuited.
Direct Buried: One single cable, direct-buried, 90C conductor temperature, 20C ambient
temperature, earth RHO of 90C-cm/Watt, 100% load factor, 36 inch depth of burial, and
shields short-circuited.
Direct Buried: Three single cables, direct-buried, spaced 7.5 inches horizontally,
90C conductor temperature, 20C ambient temperature, earth RHO of 90C-cm/Watt,
100% load factor, 36 inch depth of burial, and shields short-circuited.